3" 1 2 3 4 5 6 GENERAL © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:09:08 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" N M L K J I A. THE FOLLOWING NOTES APPLY TO ALL STRUCTURAL DRAWINGS. NOTES SHALL APPLY UNLESS OTHERWISE INDICATED BY STRUCTURAL DRAWINGS OR SPECIFICATIONS. B. WHERE A DETAIL, TYPICAL DETAIL, SECTION, TYPICAL SECTION OR PLAN NOTE IS SHOWN FOR ONE CONDITION, IT SHALL APPLY FOR ALL SIMILAR OR LIKE CONDITIONS UNLESS NOTED OTHERWISE. C. ALL DESIGN AND CONSTRUCTION IS BASED ON AND SHALL BE IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, 2012 EDITION, WITH GEORGIA AMENDMENTS. ALL REFERENCED STANDARDS SHALL BE OF THE EFFECTIVE DATE NOTED IN THE CONTROLLING BUILDING CODE. D. NO PROVISION OF ANY REFERENCED STANDARD SPECIFICATION, MANUAL OR CODE (WHETHER OR NOT SPECIFICALLY INCORPORATED BY REFERENCE IN THE CONSTRUCTION DOCUMENTS) SHALL BE EFFECTIVE TO CHANGE THE DUTIES AND RESPONSIBILITIES OF OWNER, CONTRACTOR, ENGINEER, SUPPLIER, OR ANY OF THEIR CONSULTANTS, AGENTS, OR EMPLOYEES FROM THOSE SET FORTH IN THE CONSTRUCTION DOCUMENTS. NOR SHALL IT BE EFFECTIVE TO ASSIGN TO THE STRUCTURAL ENGINEER OF RECORD OR ANY OF THE STRUCTURAL ENGINEER OF RECORD'S CONSULTANTS, AGENTS, OR EMPLOYEES ANY DUTY OR AUTHORITY TO SUPERVISE OR DIRECT THE FURNISHING OR PERFORMANCE OF THE WORK OR ANY DUTY OR AUTHORITY TO UNDERTAKE RESPONSIBILITIES CONTRARY TO THE PROVISIONS OF THE CONSTRUCTION DOCUMENTS. E. CONSTRUCTION DOCUMENTS INCLUDE, BUT ARE NOT LIMITED TO, THE STRUCTURAL DOCUMENTS (DRAWINGS AND SPECIFICATIONS), BUT DO NOT INCLUDE SHOP DRAWINGS, VENDOR DRAWINGS, OR MATERIAL PREPARED AND SUBMITTED BY THE GENERAL CONTRACTOR. F. CONSTRUCTION DOCUMENTS SHALL GOVERN IN THE EVENT OF A CONFLICT WITH THE CODE OF PRACTICE OR SPECIFICATIONS OF ACI, PCI, AISC, SJI OR OTHER STANDARDS. WHERE A CONFLICT OCCURS WITHIN THE CONSTRUCTION DOCUMENTS, THE STRICTEST REQUIREMENT SHALL GOVERN. G. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS AND NOTIFY ARCHITECT/STRUCTURAL ENGINEER OF RECORD OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK. FOR DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS, SEE ARCHITECTURAL DRAWINGS. H. DO NOT SCALE FOR DIMENSIONS NOT SHOWN ON DRAWINGS. SEND WRITTEN REQUEST FOR INFORMATION TO THE ARCHITECT FOR DIMENSIONS NOT PROVIDED. I. THE STRUCTURE SHOWN ON THESE DRAWINGS IS SELF-SUPPORTING ONLY IN ITS COMPLETED FORM. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE DESIGN, ADEQUACY, SAFETY, AND STABILITY OF TEMPORARY ERECTION BRACING AND SHORING. J. NO PROVISIONS HAVE BEEN MADE IN THE DESIGN FOR THE SUPPORT OF A CONCENTRATED LOAD FROM PLUMBING, MECHANICAL OR HVAC EXCEPT AS SHOWN ON THE DRAWINGS. K. THE GENERAL CONTRACTOR SHALL COORDINATE ALL SIZES AND LOCATIONS OF FLOOR, ROOF, AND WALL PENETRATIONS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. ALL PENETRATIONS NOT SHOWN ON STRUCTURAL DRAWINGS MUST BE APPROVED BY THE STRUCTURAL ENGINEER OF RECORD UNLESS NOTED OTHERWISE. L. THE GENERAL CONTRACTOR SHALL VERIFY THAT MISCELLANEOUS FRAMING SHOWN ON THE STRUCTURAL DRAWINGS FOR MECHANICAL EQUIPMENT, OWNER-FURNISHED ITEMS, PARTITIONS, ETC. IS CONSISTENT WITH THE REQUIREMENTS OF SUCH ITEMS. M. ELEVATIONS SHOWN ARE TO TOP OF FOUNDATIONS, SLABS OR STEEL BEAMS UNLESS NOTED OTHERWISE. N. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES IN ORDER TO COMPLY WITH THE CONSTRUCTION DOCUMENTS. O. THE GENERAL CONTRACTOR HAS SOLE RESPONSIBILITY TO COMPLY WITH ALL APPLICABLE OSHA REGULATIONS. P. THE STRUCTURAL ENGINEER OF RECORD HAS DELEGATED THE DESIGN OF PRECAST CONCRETE, GLAZING SYSTEMS, COLD FORMED METAL FRAMING, RAILING, SKYLIGHTS, AND STAIRS, OR OTHER SYSTEMS NOT SHOWN IN THE STRUCTURAL DRAWINGS. SUCH SYSTEMS SHALL BE DESIGNED, FURNISHED, AND INSTALLED AS REQUIRED BY OTHER PORTIONS OF THE CONTRACT DOCUMENTS. Q. ALL TESTING SHALL BE PAID FOR BY THE OWNER (CONTRACTOR SHALL COORDINATE WITH OWNER TO ENSURE THAT COST OF TESTING IS ACCURATE AND PRESENTED TO OWNER WITH CONSTRUCTION COSTS). B. A. B. C. D. E. F. G. A. D. B. C. F D. E. F. E G. H. D C I. SOILS, SHALLOW FOUNDATIONS, & RETAINING WALLS A. B. C. D. E. F. G. H. I. J. K. B L. A SLAB CONSTRUCTION JOINTS SHALL BE USED IN PLACE OF CONTROL JOINTS WHERE NEEDED TO INTERRUPT A CONTINUOUS POUR. PLACEMENT OF WELDED WIRE REINFORCEMENT IN SLAB, WHERE SPECIFIED, SHALL BE AT A CONSISTENT DEPTH OF 1 1/2" FROM T/SLAB. WELDED WIRE REINFORCEMENT SHALL BE PROPERLY CHAIRED ABOVE GRADE. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DOCUMENTS FOR SLAB FINISHES, SLAB DEPRESSIONS, THICKENED SLABS (IN ADDITION TO THICKENED SLABS NOTED ON STRUCTURAL DRAWINGS), ELEVATIONS, AND ENCASED OR EMBEDDED ITEMS. PLUMBING AND ELECTRICAL CONDUITS SHALL BE PLACED BELOW THE SLAB AND NOT WITHIN THE SLAB. VERTICAL PENETRATIONS ARE ALLOWED. COLUMN BOX-OUTS SHALL BE USED TO ISOLATE AN ADEQUATE AREA AROUND COLUMN BASE PLATES TO PROVIDE FOR COLUMN PLACEMENT AND LEVELING. BOX-OUTS ARE TO BE CLEAN AND FREE OF DEBRIS TO TOP OF FOOTING PRIOR TO FILLING WITH CONCRETE. THE SITE SHALL BE PREPARED IN ACCORDANCE WITH SPECIFICATIONS AND THE CIVIL DRAWINGS. THE STRUCTURAL DESIGN IS BASED ON RECOMMENDATIONS CONTAINED IN THE REPORT OF SUBSURFACE INVESTIGATION BY GEOHYDRO ENGINEERS NO. 1999 DATED 11/12/2014. THE GENERAL CONTRACTOR SHALL OBTAIN A COPY OF THE REPORT AND REVIEW THE RECOMMENDATIONS AND REQUIREMENTS INCLUDED THEREIN FOR THE SELECTED FOUNDATION SYSTEM IN THE CONSTRUCTION DOCUMENTS. A QUALIFIED GEOTECHNICAL ENGINEER SHALL VERIFY ALL ASSUMPTIONS AND REPORT TO THE ARCHITECT AND STRUCTURAL ENGINEER OF RECORD ANY VARIATIONS. DESIGN SOIL BEARING PRESSURE IS 3000 PSF. DESIGN SOIL LATERAL PRESSURES ON STRUCTURE ARE DUE TO THE FOLLOWING EQUIVALENT FLUID DENSITIES: 1. AT REST CONDITION: 65 PCF 2. ACTIVE CONDITION: 44 PCF 3. PASSIVE CONDITION: 180 PCF 4. COEFFICIENT OF FRICTION FOR SLIDING: 0.40 ALL EXCAVATIONS AND GRADES PREPARED FOR BEARING SHALL BE INSPECTED BY A QUALIFIED GEOTECHNICAL ENGINEER TO VERIFY THE DESIGN ASSUMPTIONS AND REPORT NONCONFORMING CONDITIONS. WHERE FILL IS REQUIRED, IT SHALL BE SELECTED AND PLACED IN ACCORDANCE WITH INSTRUCTIONS OF A QUALIFIED GEOTECHNICAL ENGINEER TO MAINTAIN DESIGN BEARING PRESSURE. FINISHED GRADE SHALL BE MAINTAINED A MINIMUM OF 18" ABOVE BOTTOM OF FOUNDATIONS. TOP OF FOOTING ELEVATIONS PROVIDED ON CONSTRUCTION DRAWINGS ARE FOR PURPOSES OF DESIGN. NOTIFY THE STRUCTURAL ENGINEER OF RECORD IF TOP OF FOOTING ELEVATIONS NEED TO BE ADJUSTED BASED ON CONTRACTOR'S FIELD COORDINATION. 1. GENERAL CONTRACTOR SHALL COORDINATE REQUIRED ADJUSTMENT OF FOOTING ELEVATIONS TO AVOID INFLUENCE BETWEEN FOUNDATIONS AND BURIED UTILITIES. ALL REQUIRED ADJUSTMENTS SHALL BE FORWARDED TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW. SEE "TYPICAL FOOTING ADJACENT TO TRENCH" DETAIL. DO NOT EMBED PIPING WITHIN OR PASS PIPING VERTICALLY OR HORIZONTALLY THROUGH FOUNDATIONS WITHOUT REVIEW AND APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD. PIPING MAY PASS BELOW CONTINUOUS FOOTINGS WHERE INSTALLED IN ACCORDANCE WITH "TYPICAL PIPE UNDER FOOTING" DETAIL. FOOTINGS SHALL BE CENTERED ABOUT COLUMN LINES UNLESS NOTED OTHERWISE. THE DESIGN OF WALLS RETAINING EARTH ASSUMES DRAINAGE SYSTEM IS IN PLACE, AND DOES NOT INCLUDE HYDROSTATIC PRESSURE LOADS UNLESS SPECIFICALLY NOTED ON THE STRUCTURAL DRAWINGS. THE GENERAL CONTRACTOR SHALL PROVIDE DRAINAGE SYSTEM IN ALL BACKFILL CONDITIONS (SEE CIVIL/ARCHITECTURAL DRAWINGS FOR DRAINAGE SPECIFICATIONS). THE DESIGN OF WALLS RETAINING EARTH DOES NOT INCLUDE SURCHARGE LOADS THAT MAY BE INDUCED FROM CONSTRUCTION ACTIVITIES. SEE GENERAL NOTES SECTION REGARDING GENERAL CONTRACTOR'S RESPONSIBILITIES FOR TEMPORARY ERECTION BRACING AND SHORING. BACKFILL SHALL NOT BE PLACED AGAINST WALLS UNTIL THE WALLS HAVE ACHIEVED SPECIFIED DESIGN STRENGTH. BACKFILL AGAINST WALLS SHALL BE DEPOSITED EVENLY IN 12" TO 18" LIFTS AGAINST BOTH SIDES OF WALL UNTIL THE LOWER FINAL GRADE IS REACHED. 1. UNLESS SPECIFICALLY NOTED AS "CANTILEVERED" ON STRUCTURAL DRAWINGS, WALLS RETAINING EARTH SHALL NOT BE BACKFILLED AGAINST UNTIL STRUCTURAL SLABS PROVIDING LATERAL RESTRAINT FOR THE WALLS HAVE BEEN INSTALLED AND HAVE REACHED SPECIFIED DESIGN STRENGTH. WHERE THIS CANNOT BE ACCOMMODATED THE WALL SHALL BE SHORED CONTINUALLY. 14 15 16 17 18 19 POST INSTALLED ANCHORS IN CONCRETE & CONCRETE MASONRY ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH DIVISION 03 SPECIFICATIONS. COORDINATE CONCRETE MIXTURES WITH THE SCHEDULE ON S-003. THE GENERAL CONTRACTOR SHALL SUBMIT TO STRUCTURAL ENGINEER OF RECORD PROPOSED CONSTRUCTION JOINT LOCATIONS FOR APPROVAL. NO HORIZONTAL CONSTRUCTION JOINTS ARE PERMITTED EXCEPT THOSE SHOWN ON THE STRUCTURAL DRAWINGS. WHERE NEW CONCRETE IS TO BE POURED ONTO EXISTING CONCRETE, BONDING IS REQUIRED AS NOTED IN ACI 301. A. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. THE GENERAL CONTRACTOR SHALL OBTAIN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USING POST INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE GIVEN TO AVOID CONFLICTS WITH EXISTING REINFORCING. HOLES SHALL BE DRILLED AND CLEANED PER THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS. D. THE FOLLOWING CRITERIA REGARDING PIPES AND CONDUITS EMBEDDED IN CONCRETE SHALL BE ADHERED TO (SEE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR LOCATION OF SLEEVES, PIPES, CONDUIT, ACCESSORIES, ETC). THIS CRITERIA WILL BE STRICTLY ENFORCED. 1. CONDUITS, PIPES, AND SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE SHALL BE PERMITTED TO BE EMBEDDED IN CONCRETE WITH THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD. 2. CONDUITS AND PIPES OF ALUMINUM SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE. 3. CONDUITS, PIPES, AND SLEEVES PASSING THROUGH A SLAB, WALL, OR BEAM SHALL NOT SIGNIFICANTLY IMPAIR THE STRENGTH OF THE CONSTRUCTION. 4. CONDUITS AND PIPES SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN 1/3 THE OVERALL THICKNESS OF THE SLAB, WALL, OR BEAM IN WHICH THEY ARE EMBEDDED. 5. CONDUITS AND PIPES SHALL NOT BE SPACED CLOSER THAN 3 DIAMETERS OR WIDTHS ON CENTER. CONCRETE COVER FOR PIPES, CONDUITS AND FITTINGS SHALL NOT BE LESS THAN 1 1/2" FOR CONCRETE EXPOSED TO EARTH OR WEATHER, NOR 3/4" FOR CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR IN CONTACT WITH GROUND. 6. CONDUITS AND PIPES SHALL BE PLACED BETWEEN TOP AND BOTTOM SLAB REINFORCEMENT. CONDUITS AND PIPES SHALL BE PLACED IN THE MIDDLE THIRD OF THE SLAB OR WALL THICKNESS UNLESS NOTED OTHERWISE. 7. CONDUITS AND PIPES SHALL BE SO FABRICATED AND INSTALLED THAT CUTTING, BENDING, OR DISPLACEMENT OF REINFORCEMENT FROM ITS PROPER LOCATION WILL NOT BE REQUIRED. 8. CONDUITS AND PIPES, WITH FITTINGS, EMBEDDED WITHIN A COLUMN SHALL NOT DISPLACE MORE THAN 4 PERCENT OF THE AREA OF CROSS SECTION NOTED ON DRAWINGS OR AS REQUIRED BY FIRE PROTECTION. 9. PIPES AND FITTINGS SHALL BE DESIGNED TO RESIST EFFECTS OF MATERIAL, PRESSURE AND TEMPERATURE TO WHICH THEY WILL BE SUBJECTED. 10. REINFORCEMENT WITH AN AREA NOT LESS THAN 0.002 TIMES THE AREA OF CONCRETE SECTION SHALL BE PROVIDED NORMAL TO PIPING. THIS REINFORCEMENT SHALL BE IN ADDITION TO REINFORCEMENT NOTED ON DRAWINGS. 11. REFER TO ACI 318, SECTION 6.3 FOR ADDITIONAL REQUIREMENTS FOR CONDUITS AND PIPES EMBEDDED IN CONCRETE. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FOR DRIPS, CHAMFERS, REGLETS, SLOTS, SLEEVES, RUSTICATIONS, INSERTS ANCHORS AND OTHER EMBEDDED ITEMS NOT NOTED ON STRUCTURAL DRAWINGS. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND PLACING ALL EMBEDDED ITEMS SHOWN ON DRAWINGS & ADDITIONAL ITEMS NOTED IN THIS NOTE, AS REQUIRED BY OTHER TRADES. UNLESS SHOWN ON STRUCTURAL DRAWINGS, NO OPENINGS LARGER THAN 12"x12" SHALL BE PLACED IN SLABS OR WALLS. FOR OPENINGS NOT SHOWN ON STRUCTURAL DRAWINGS, APPROVALS MUST BE OBTAINED FROM THE ARCHITECT/STRUCTURAL ENGINEER OF RECORD PRIOR TO FABRICATION OF STEEL AND PLACEMENT OF CONCRETE. SHOW ALL OPENINGS AND SLEEVES ON THE SHOP DRAWINGS. B. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSE SPECIFIED, SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD WITH CALCULATIONS THAT ARE PREPARED AND SEALED BY A REGISTERED DESIGN PROFESSIONAL IN THE STATE IN WHICH THE PROJECT IS LOCATED SHOWING THAT THE SUBSTITUTED PRODUCT WILL ACHEIVE AN EQUIVALENT CAPACITY USING THE APPROPRIATE DESIGN PROCEDURE REQUIRED BY THE REFERENCED BUILDING CODE. E. THE OWNER WILL NOT PAY FOR ADDITIONAL CHARGES DUE TO RE-DETAILING FEES RESULTING FROM CHANGES OR REVISIONS DURING SHOP DRAWING REVIEW. THE DETAILER SHALL ESTIMATE AND INCLUDE ANY COSTS IN THE BASE BID ASSOCIATED WITH RE-DETAILING FEES AS A RESULT OF CHANGES AND/OR REVISIONS MADE TO THE SHOP DRAWINGS DURING THE SHOP DRAWING REVIEW. CONCRETE SLAB CONTROL JOINTS SHALL BE CUT INTO THE SLABS AT A DEPTH OF 1/4 TIMES THE THICKNESS OF THE SLAB WITHIN 12 HOURS OF PLACING THE CONCRETE. MAXIMUM SPACING OF INTERIOR SLAB CONTROL JOINTS, UNLESS NOTED OTHERWISE, SHALL BE 16'-0" (MAX.) IN EACH DIRECTION. CONSTRUCTION OF CONTROL JOINTS SHALL BE SUCH THAT THE AREA CONTAINED HAS A MAXIMUM RATIO OF LONG SIDE TO SHORT SIDE OF 1.5 TO 1, OR AS SHOWN ON THE CONSTRUCTION DRAWINGS. 13 A. B. C. F. F. DESIGN ROOF DEAD LOAD: 1. 20 PSF DESIGN ROOF LIVE LOAD: 1. 20 PSF 2. REDUCTIONS APPLIED PER TRIBUTARY AREA AS PERMITTED BY CODE DESIGN ROOF RAIN LOAD 1. DESIGN RAINFALL: 3.5"/HR (100-YEAR, 1-HOUR RAINFALL) 2. MAXIMUM DEPTH OF RAINWATER AT LOWEST POINT OF ROOF SHALL NOT EXCEED 4" DURING DESIGN RAINFALL DESIGN FLOOR DEAD LOAD: 1. 65 PSF (ELEVATED SLAB) @ ADDITION 2. 40 PSF (NEW ELEV SLAB @ EXIST) DESIGN FLOOR LIVE LOAD: 1. 125 PSF SLAB-ON-GRADE 2. 100 PSF (@ NEW ELEVATED SLABS & STAIRS) 3. REDUCTIONS APPLIED PER TRIBUTARY AREA AS PERMITTED BY CODE DESIGN SNOW LOAD: 1. GROUND SNOW LOAD, Pg = 5 PSF (DOES NOT CONTROL) DESIGN WIND LOAD: 1. ULTIMATE DESIGN WIND SPEED, Vult = 120 MPH 2. NOMINAL DESIGN WIND SPEED Vasd = 93 MPH 3. RISK CATEGORY: III 4. WIND EXPOSURE CATEGORY: C 5. COMPONENTS AND CLADDING WIND PRESSURE: (SEE SCHEDULE) 6. INTERNAL PRESSURE COEFFICIENT (GCpi): +/- 0.18 DESIGN SEISMIC INFORMATION: 1. RISK CATEGORY: III 2. MAPPED SPECTRAL RESPONSE COEFFICIENT, Ss = 0.208 3. MAPPED SPECTRAL RESPONSE COEFFICIENT, S1 = 0.094 4. SPECTRAL RESPONSE COEFFICIENT, Sds = 0.222 5. SPECTRAL RESPONSE COEFFICIENT, Sd1 = 0.151 6. SITE CLASS: D 7. BASE SEISMIC-FORCE RESISTING SYSTEM: CONCENTRIC STEEL BRACED FRAMES & MOMENT FRAMES NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE 8. DESIGN BASE SHEAR: 65 K 9. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE (ASCE 7, SECTION 12.8) 10. RESPONSE MODIFICATION FACTOR, R: 3.0 11. SEISMIC DESIGN CATEGORY: C 12. SEISMIC IMPORTANCE FACTOR, Ie = 1.25 13. SEISMIC RESPONSE COEFFICIENT, Cs = 0.093 NO PROVISIONS HAVE BEEN MADE FOR FUTURE HORIZONTAL OR VERTICAL EXPANSION. STRUCTURAL DRAWINGS INDICATE TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. SHOP DRAWINGS SHALL DETAIL ALL CONDITIONS IN ACCORDANCE WITH SPECIFIED STANDARDS AND THE SPECIFIC REQUIREMENTS OF THIS PROJECT AS INDICATED IN THE CONSTRUCTION DOCUMENTS. THE GENERAL CONTRACTOR SHALL SUBMIT, AS REQUIRED, PRINTS OR ELECTRONIC COPIES, AS DIRECTED, OF SHOP DRAWINGS FOR ALL FABRICATED MATERIALS TO ARCHITECT FOR REVIEW. REVIEW OF SHOP DRAWINGS BY THE ARCHITECT/STRUCTURAL ENGINEER OF RECORD DOES NOT RELIEVE THE GENERAL CONTRACTOR OF THE SOLE RESPONSIBILITY FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF THOSE SHOP DRAWINGS. SHOP DRAWINGS AND CALCULATIONS FOR DELEGATED DESIGN ITEMS AS DICTATED BY THE CONSTRUCTION DOCUMENTS SHALL BE SIGNED AND SEALED BY A REGISTERED DESIGN PROFESSIONAL LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED BEFORE SUBMITTING FOR REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER OF RECORD. COMPLETE SHOP DRAWINGS FOR CONSTRUCTION OF ALL APPLICABLE SPECIALTY ITEMS INCLUDING, BUT NOT LIMITED TO PRECAST CONCRETE, GLAZING SYSTEMS, COLD FORMED METAL FRAMING, RAILING, SKYLIGHTS, AND STAIRS SHALL BE SIGNED AND SEALED BY A REGISTERED DESIGN PROFESSIONAL LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED, AND SHALL BE AVAILABLE AT THE JOB SITE DURING TIMES OF INSPECTION. REPRODUCTION/DUPLICATION OF THE STRUCTURAL DRAWINGS FOR USE IN THE PRODUCTION OF SHOP DRAWINGS IS PROHIBITED, UNLESS NOTED OTHERWISE. IN THE EVENT THAT THE GENERAL CONTRACTOR OR SUBCONTRACTOR ELECTS TO PRODUCE SHOP DRAWINGS BY COPYING ELECTRONIC OR PAPER COPIES OF THE STRUCTURAL DRAWINGS, THE CONTRACTOR SHALL REQUEST FROM THE STRUCTURAL ENGINEER OF RECORD A SHOP DRAWING WAIVER ALONG WITH THE SPECIFIC SHEETS REQUIRED. SIGNATURE OF THE WAIVER BY THE GENERAL CONTRACTOR, ALONG WITH PAYMENT OF A FEE TO THE STRUCTURAL ENGINEER OF RECORD WILL BE REQUIRED. THE GENERAL CONTRACTOR SHALL CONTINUE TO ASSUME RESPONSIBILITY FOR ERRORS, OMISSIONS AND COORDINATION REQUIRED FOR SHOP DRAWING PRODUCTION, REGARDLESS OF THE USE OF COPIES OF THE STRUCTURAL DRAWINGS FOR SHOP DRAWING PRODUCTION. 12 CONCRETE SLAB-ON-GRADE E. A. 11 SHOP DRAWINGS DESIGN LOADS G 10 B. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL UNDERGROUND UTILITIES IN THE AREA OF CONSTRUCTION THAT MIGHT BE AFFECTED BY OR OTHERWISE INTERFERE WITH INSTALLATION OF NEW WORK. THIS INCLUDES THOSE THAT MIGHT BE DAMAGED BY NEW FOUNDATION OR OTHER WORK, AND THOSE WHOSE PRESENCE MIGHT LEAD TO DAMAGE TO THE NEW WORK (SUCH AS DIFFERENTIAL SETTLEMENT, ETC.). C. SPECIAL INSPECTIONS ARE REQUIRED IN ADDITION TO THE INSPECTIONS SPECIFIED IN SECTION 110 OF THE BUILDING CODE. ALL SPECIAL INSPECTIONS SHALL BE IN ACCORDANCE WITH DIVISION 01 SPECIFICATIONS. 9 A. THE GENERAL CONTRACTOR SHALL SURVEY THE EXISTING STRUCTURE TO DETERMINE THAT ALL MODIFICATIONS AS INDICATED IN THE CONSTRUCTION DOCUMENTS ARE FEASIBLE AND PRACTICAL AND SHALL REPORT ANY DISCREPANCIES OR UNUSUAL CONDITIONS TO THE ARCHITECT/STRUCTURAL ENGINEER OF RECORD. FIELD DIMENSION NEW STRUCTURAL ELEMENTS PRIOR TO THE SUBMISSION OF SHOP DRAWINGS. B. A. 8 EXISTING CONDITIONS SPECIAL INSPECTIONS H 7 G. CORING OF SLABS AND USE OF DRILLED ANCHORS IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD. IF APPROVED, COORDINATE ANCHOR LOCATIONS SO THAT NO CONTACT IS MADE WITH ANY REINFORCING OR P.T. TENDONS. POWDER ACTUATED FASTENERS (OR POWDER DRIVEN FASTENERS) SHALL BE ANCHORED IN CONCRETE WITH MINIMUM FASTENER SPACING OF 3" AND MINIMUM EDGE DISTANCE OF 2". FASTENERS SHALL NOT EXCEED 5/8" EMBEDMENT UNLESS APPROVED BY STRUCTURAL ENGINEER OF RECORD. CONCRETE MASONRY A. B. C. D. E. F. G. H. I. J. K. L. ALL MASONRY WORK SHALL BE IN ACCORDANCE WITH DIVISION 04 SPECIFICATIONS. MASONRY GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2500 psi AT 28-DAYS. F'M SHALL BE 1500 PSI (MIN. CMU COMPRESSIVE STRENGTH = 1900 PSI). JOINT REINFORCING SHALL BE LADDER TYPE, 9 GAUGE SPACED VERTICALLY AT 16" UNLESS NOTED OTHERWISE. PROVIDE JOINT REINFORCING AT 8" AT MASONRY BELOW GRADE, 2 ROWS AT 8" AT TOP AND BOTTOM OF OPENINGS, (EXTEND 24" EACH SIDE) AND 2 ROWS AT 8" AT BOND BEAMS. VERTICAL REINFORCING IN CONCRETE MASONRY (AS REQUIRED) SHALL EXTEND INTO THE BOND BEAM AT THE FLOOR OR ROOF. PROVIDE MIN. 4" X 4" OPENING AT U BLOCK FOR VERTICAL BAR. VERTICAL REINFORCING IN CONCRETE MASONRY GROUTED CELLS SHALL BE PROVIDED AT EACH SIDE OF OPENING, EQUAL TO ONE HALF THE REINFORCING DISPLACED WITH A MINIMUM OF ONE (1) TYPICAL REINFORCEMENT BAR AT EACH SIDE UNLESS SPECIFIED OTHERWISE IN A REINFORCED JAMB OR SHEAR WALL SCHEDULE. ALL CELLS BELOW GRADE AND SLAB ON GRADE SHALL BE FULLY GROUTED. 16" DEEP BOND BEAMS SHALL BE CONSTRUCTED OF 8" U BLOCK BELOW AND 8" STANDARD BLOCK ABOVE WITH BREAK AWAY TOP PART OF WEB UNLESS NOTED OTHERWISE IN CONSTRUCTION DRAWINGS. CONCRETE MASONRY UNITS SHALL BE CUT BELOW BEAMS, LINTELS, OR BOND BEAMS AS REQUIRED IN ORDER TO GET CONTINUOUS BEAM, LINTEL, OR BOND BEAMS AT THE PROPER ELEVATION. SEE ARCHITECTURAL DRAWINGS FOR LAYING MASONRY AND LOCATION OF OPENINGS. LAY IN RUNNING BOND UNLESS NOTED OTHERWISE. CONTROL JOINTS SHALL BE LOCATED PER ARCHITECTURAL DRAWINGS, SHALL MATCH VENEER CONTROL JOINTS WHERE APPLICABLE, AND SHALL NOT EXCEED 25'-0". CONTROL JOINTS SHALL NOT BE LOCATED THROUGH BEAMS OR LINTELS OR THEIR BEARING DISTANCE. CONTROL JOINTS SHALL BE A MINIMUM DISTANCE OF 5'-0" CLEAR FROM WALL EDGES OR CORNERS. DISCONTINUE HORIZONTAL REINFORCING AT CONTROL JOINTS. ONE HALF OF SPECIFIED BOND BEAM REINFORCING SHALL BE CONTINUOUS THROUGH CONTROL JOINTS UNLESS NOTED OTHERWISE. CONTROL JOINTS SHALL NOT BE PLACED IN WALLS DENOTED IN CONSTRUCTION DOCUMENTS AS SHEAR WALLS WITHOUT EXPLICIT APPROVAL BY STRUCTURAL ENGINEER OF RECORD. C. ALTERNATE PRODUCTS SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD FOR APPROVAL SHALL HAVE A VALID RESEARCH REPORT, ALSO KNOWN AS EVALUATION REPORT, INDICATING COMPLIANCE WITH APPROPRIATE ACCEPTANCE CRITERIA REQUIRED BY THE BUILDING CODE FOR THE INTENDED LOAD TYPE AND USE (E.G. WIND, SEISMIC, SUSTAINED TENSION, ETC). RESEARCH REPORTS SHALL BE ISSUED BY A SOURCE APPROVED BY THE AUTHORITY HAVING JURISDICTION. H. ADHESIVE ANCHORS FOR CONCRETE MASONRY AS SHOWN ON CONSTRUCTION DOCUMENTS SHALL CONSIST OF AN ALL-THREAD GRADE 36 STEEL ROD WITH ONE OF THE FOLLOWING ADHESIVE PRODUCTS: HIT-HY70 INJECTION ADHESIVE SUPPLIED BY HILTI FASTENING SYSTEMS, AT-XP ADHESIVE SUPPLIED BY SIMPSON STRONGTIE COMPANY, OR AC100+ GOLD SUPPLIED BY POWERS FASTENERS. WHEN ANCHORING TO CONCRETE MASONRY WITH VOIDS, THE APPROPRIATE SCREEN TUBE SHALL BE USED AS RECOMMENDED BY THE ADHESIVE MANUFACTURER. ADHESIVE FOR ANCHORING REINFORCING BARS INSTALLED IN EXISTING CONCRETE SHALL BE ONE OF THE FOLLOWING ADHESIVE PRODUCTS: HIT-HY200 EPOXY ADHESIVE SUPPLIED BY HILTI FASTENING SYSTEMS, AT-XP ADHESIVE SUPPLIED BY SIMPSON STRONGTIE COMPANY, OR PURE110+ EPOXY ADHESIVE SUPPLIED BY POWERS FASTENERS. J. IN ADDITION TO THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, THE FOLLOWING GUIDELINES SHALL BE FOLLOWED FOR INSTALLATION OF ADHESIVE ANCHORS: 1. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. 2. ADHESIVE ANCHORS SHALL BE INSTALLED IN DRY CONCRETE, AND DURING DRY CONDITIONS. 3. ADHESIVE ANCHORS SHALL BE INSTALLED IN HOLES PREDRILLED WITH A CARBIDE TIPPED DRILL BIT. 4. ADHESIVE ANCHORS SHALL BE INSTALLED WITHIN THE TEMPERATURE RANGE SPECIFIED IN THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, BUT NOT OUTSIDE OF THE DESIGN TEMPERATURE RANGE. LOADS SHALL NOT BE APPLIED TO ADHESIVE ANCHORS UNTIL THE FULL CURING TIME ASSOCIATED WITH THE INSTALLATION TEMPERATURE HAS ELAPSED. K. INSTALLATION OF ADHESIVE ANCHORS SHALL BE PERFORMED BY PERSONNEL CERTIFIED BY AN APPLICABLE CERTIFICATION PROGRAM. CERTIFICATION SHALL INCLUDE WRITTEN AND PERFORMANCE TESTS IN ACCORDANCE WITH THE ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM, OR EQUIVALENT. L. SPECIAL INSPECTIONS SHALL BE PROVIDED FOR POST-INSTALLED ANCHORS IN ACCORDANCE WITH THE ANCHOR MPII AND/OR EVALUATION REPORT, UNLESS MORE SPECIFIC REQUIREMENTS ARE SPECIFIED IN THE CONSTRUCTION DOCUMENTS. B. C. D. E. LONGITUDINAL REINFORCING BARS IN FOOTINGS SHALL BE PLACED CONTINUOUS AT CORNERS AND INTERSECTIONS. FOR EVERY VERTICAL OR HORIZONTAL BAR DISCONTINUED BY AN OPENING, ONE BAR (MIN. OF 2 BARS) SHALL BE ADDED AT SIDE OF OPENING (HALF TO EACH SIDE - TYPICAL). PROVIDE DOWELS FROM FOUNDATIONS, THE SAME SIZE AND NUMBER AS THE VERTICAL WALL OR COLUMN REINFORCING, UNLESS NOTED OTHERWISE. WELDING A. B. C. D. MINIMUM WELD SIZE SHALL BE 3/16" FILLET WELD UNLESS NOTED OTHERWISE. FIELD WELDING SHALL BE SHOWN ON SHOP DRAWINGS AND ERECTION DRAWINGS. REFER TO ARCHITECTURAL DOCUMENTS FOR EXPOSED STEEL AND JOINT LOCATIONS AND REQUIREMENTS. ALL EXPOSED WELDED CONNECTIONS SHALL BE GROUND SMOOTH AND SUBJECT TO ARCHITECT APPROVAL. FABRICATOR SHALL ALTER JOINT DETAILING AS REQUIRED TO ENSURE THAT EFFECTIVE THROAT SPECIFIED IN WELD DETAIL IS MAINTAINED AFTER GRINDING OF WELD SURFACE. PES PROJECT NUMBER: 0214062 I. STRUCTURAL STEEL A. B. C. D. E. F. G. H. UNLESS NOTED OTHERWISE, WHERE MULTIPLE WYTHES OF CONCRETE MASONRY ARE CONSTRUCTED AND/OR WHERE ADDITIONAL WYTHES OF CONCRETE MASONRY ARE ADDED TO EXISTING WYTHES, EACH ADJACENT WYTHE SHALL BE TIED TO THE NEXT WYTHE WITH TYPICAL JOINT REINFORCING (NEW CONSTRUCTION FOR BOTH WYTHES) OR POST-INSTALLED TIES APPROVED BY STRUCTURAL ENGINEER OF RECORD (ADDITION TO EXISTING CONSTRUCTION) WITH SPACING/LOCATIONS MATCHING THE SPACING/LOCATIONS FOR TYPICAL JOINT REINFORCING DESCRIBED IN THE GENERAL NOTES. REINFORCING STEEL AND ACCESSORIES WORK SHALL BE IN ACCORDANCE WITH DIVISION 03 SPECIFICATIONS. ALL TENSION SPLICES, INCLUDING SPLICES FROM BARS LABELED CONTINUOUS, SHALL CONFORM TO ACI 318. SPLICES SHALL BE CLASS B IN ACCORDANCE WITH ACI 318, UNLESS NOTED OTHERWISE. REINFORCEMENT SHALL BE SPLICED ONLY AT LOCATIONS SHOWN OR NOTED IN THE STRUCTURAL DOCUMENTS, EXCEPT REINFORCEMENT MARKED "CONTINUOUS" CAN BE SPLICED AT LOCATIONS DETERMINED BY THE GENERAL CONTRACTOR. SPLICES AT OTHER LOCATIONS SHALL BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD. 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com D. MECHANICAL ANCHORS FOR CONCRETE AS SHOWN ON CONSTRUCTION DOCUMENTS SHALL BE HILTI KWIK BOLT TZ ANCHORS MANUFACTURED BY HILTI FASTENING SYSTEMS, STRONG-BOLT 2 ANCHORS MANUFACTURED BY SIMPSON STRONGTIE COMPANY, OR POWER-STUD+ SD2 ANCHORS MANUFACTURED BY POWERS FASTENERS. E. MECHANICAL ANCHORS FOR CONCRETE MASONRY AS SHOWN ON CONSTRUCTION DOCUMENTS SHALL BE HILTI KWIK BOLT 3 ANCHORS MANUFACTURED BY HILTI FASTENING SYSTEMS, WEDGE-ALL ANCHORS MANUFACTURED BY SIMPSON STRONGTIE COMPANY, OR POWER-STUD+ SD1 ANCHORS MANUFACTURED BY POWERS FASTENERS. F. SCREW ANCHORS AS SHOWN ON CONSTRUCTION DOCUMENTS SHALL BE HILTI HUS EZ ANCHORS MANUFACTURED BY HILTI FASTENING SYSTEMS, TITEN HD ANCHORS MANUFACTURED BY SIMPSON STRONGTIE COMPANY, OR WEDGE-BOLT+ ANCHORS MANUFACTURED BY POWERS FASTENERS. G. ADHESIVE ANCHORS FOR CONCRETE AS SHOWN ON CONSTRUCTION DOCUMENTS SHALL CONSIST OF AN ALL-THREAD GRADE 36 STEEL ROD WITH ONE OF THE FOLLOWING ADHESIVE PRODUCTS: HIT-HY200 EPOXY ADHESIVE SUPPLIED BY HILTI FASTENING SYSTEMS, AT-XP ADHESIVE SUPPLIED BY SIMPSON STRONGTIE COMPANY, OR PURE110+ EPOXY ADHESIVE SUPPLIED BY POWERS FASTENERS. ADHESIVE ANCHOR DESIGN TEMPERATURE RANGE IS 75*F (LONG TERM) AND 104*F (SHORT TERM). REINFORCING STEEL A. Croft & Associates I. ALL STRUCTURAL STEEL WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. SLOTTED HOLES FOR BEAM END CONNECTIONS ARE NOT ALLOWED FOR BEAMS ASSOICATED WITH A BRACED FRAME OR MOMENT FRAME, OR NOTED WITH A REQUIRED AXIAL CONNECTION FORCE, UNLESS NOTED OTHERWISE GUSSET PLATES AND STIFFENER PLATES SHALL BE 3/8" MINIMUM, WELDED BOTH SIDES CONTINUOUSLY, UNLESS NOTED OTHERWISE. MEMBERS SUPPORTING DECK AT THE PERIMETER OF THE BUILDING SHALL BE CONTINUOUS EXCEPT AT EXPANSION JOINTS. SQUARE GROOVE WELD (BUTT JOINT) CONTINUOUS MEMBERS PLACED END TO END UNLESS NOTED OTHERWISE. STEEL COLUMNS AND BASE PLATES SHALL HAVE MINIMUM 3" CONCRETE COVER PROTECTION. POWDER ACTUATED FASTENERS (OR POWDER DRIVEN FASTENERS) SHALL BE ANCHORED IN STEEL WITH MINIMUM FASTENER SPACING OF 1 1/2" AND MINIMUM EDGE DISTANCE OF 1/2". GROUT UNDER BEARING PLATES SHALL BE MIN. 6,000 PSI COMPRESSIVE STRENGTH. LOADING OF STRUCTURE SHALL NOT OCCUR UNTIL GROUT IS INSTALLED UNDER BASE PLATES AND PROPERLY CURED. MATERIALS: 1. W-SHAPES: ASTM A 992. 2. CHANNELS, ANGLES, M, S-SHAPES: ASTM A 36. 3. PLATE AND BAR: ASTM A 36. 4. COLD-FORMED HOLLOW STRUCTURAL SECTIONS: ASTM A 500, GRADE B, STRUCTURAL TUBING. 5. STEEL PIPE: ASTM A 53, TYPE E OR S, GRADE B. 6. HIGH-STRENGTH BOLTS, NUTS, AND WASHERS: ASTM A 325, TYPE 1 OR ASTM A 490 TYPE 1 HEAVY HEX STEEL STRUCTURAL BOLTS ASTM A 563, GRADE DH, HEAVY HEX CARBON-STEEL NUTS; AND ASTM F 436, TYPE 1, HARDENED CARBON-STEEL WASHERS WITH PLAIN FINISH. 7. SHEAR CONNECTORS: ASTM A 108, GRADES 1010 THROUGH 1020, HEADED-STUD TYPE, COLD-FINISHED CARBON STEEL; AWS D1.1, TYPE B. 8. UNHEADED ANCHOR RODS: ASTM F 1554, GRADE 36. CONFIGURATION TO BE STRAIGHT. 9. PLATE WASHERS: ASTM A 36 CARBON STEEL. 10. WASHERS: ASTM F 436, TYPE 1, HARDENED CARBON STEEL. 11. THREADED RODS: ASTM A 36. 12. NONMETALLIC, SHRINKAGE-RESISTANT GROUT: ASTM C 1107, FACTORY-PACKAGED, NONMETALLIC AGGREGATE GROUT, NONCORROSIVE AND NONSTAINING, MIXED WITH WATER TO CONSISTENCY SUITABLE FOR APPLICATION AND A 30-MINUTE WORKING TIME. CONNECTIONS: PROVIDE DETAILS OF CONNECTIONS REQUIRED BY THE CONSTRUCTION DOCUMENTS TO BE SELECTED AND COMPLETED BY STRUCTURAL-STEEL FABRICATOR, INCLUDING COMPREHENSIVE ENGINEERING DESIGN BY A REGISTERED DESIGN PROFESSIONAL LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED, TO WITHSTAND LOADS INDICATED AND COMPLY WITH OTHER INFORMATION AND RESTRICTIONS INDICATED AS PER “OPTION 3” OF THE CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES. 1. SELECT AND COMPLETE CONNECTIONS USING SCHEMATIC DETAILS AND LOADS INDICATED IN CONSTRUCTION DRAWINGS AND AISC 360. 2. USE ASD; DATA ARE GIVEN AT SERVICE-LOAD LEVEL. 3. WHERE BEAM SHEAR IS NOT NOTED, THE CONNECTIONS SHALL DEVELOP THE BEAM SHEAR V = W/2 WHERE W IS THE TOTAL ALLOWABLE BEAM UNIFORM LOAD BASED ON LATERALLY SUPPORTED SIMPLE SPAN MOMENTS PER TABLES LOCATED IN THE AISC MANUAL OF STEEL CONSTRUCTION. 4. CONNECTIONS SHALL BE DESIGNED AS SNUG-TIGHT CONNECTIONS WITH THREADS IN THE SHEAR PLANE, UNLESS NOTED OTHERWISE. ALL BOLTS NOTED AS PRE-TENSIONED OR SLIP CRITICAL IN THE DRAWINGS SHALL BE TIGHTENED TO THE MINIMUM PRETENSION VALUE SHOWN IN TABLE J3.1 OF THE AISC STEEL MANUAL, USING COMPRESSIBLE-WASHER-TYPE DIRECT TENSION INDICATOR DEVICES CONFORMING TO ASTM F959. OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 DRAWN: ABS CHECKED: TRP SHEET TITLE GENERAL NOTES REINFORCING STEEL WELDING SHALL CONFORM TO AWS D1.4, STRUCTURAL WELDING CODE REINFORCING STEEL BY AMERICAN WELDING SOCIETY FOR COMPLIANCE WITH ACI 318, SECTION 3.5.2. METAL FABRICATION A. ALL METAL FABRICATION WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. SHEET NO. S-001 A. ALL HOT-DIP GALVANIZATION WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. B. ALL BOLTS USED FOR CONNECTIONS AT GALVANIZED STEEL MEMBERS SHALL BE GALVANIZED PER STANDARDS NOTED. C. REFER TO ASTM A-143, A-384 AND D-6386 FOR ADDITIONAL STANDARD PRACTICES RELATED TO SPECIAL CONDITIONS FOR HOT-DIP GALVANIZING. D. GALVANIZED FAYING SURFACES AT SLIP CRITICAL CONNECTIONS SHALL BE HOT DIP GALVANIZED IN ACCORDANCE WITH ASTM A-123 AND SHALL BE ROUGHENED BY MEANS OF HAND WIRE BRUSHING. POWER WIRE BRUSHING IS NOT PERMITTED. METAL STAIRS AND RAILING A. ALL METAL STAIR AND RAILING WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. B. SEE ARCHITECTURAL DRAWINGS FOR EXACT LAYOUT AND CONFIGURATION. J I 6 STEEL ROOF DECK A. ALL STEEL ROOF DECK WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS B. ALL INTERIOR STEEL ROOF DECK SHALL BE ASTM A1008 FACTORY PRIMED FOR PAINT. ALL EXPOSED STEEL ROOF DECK SHALL BE ASTM A653 GALVANIZED G90. ALL STEEEL ROOF DECK SHALL BE A MINIMUM YIELD STRENGTH OF 33,000 PSI, UNLESS NOTED OTHERWISE. C. DECK SHALL BE SUPPORTED BY A MINIMUM OF FOUR SUPPORT LOCATIONS (THREE SPAN CONDITION). D. MINIMUM FINAL ROOF SLOPE SHALL BE 1/4" PER 1 FT. WHERE SLOPE IS NOT ACHIEVED BY STEEL STRUCTURE, CREATE IT WITH INSULATION ABOVE THE DECK (SEE ARCHITECTURAL DRAWINGS). E. ALL INTERIOR EXPOSED ROOF DECK SHALL BE ASTM A1008 FACTORY PRIMED FOR PAINT. SEE ARCHITECTURAL DRAWINGS FOR EXTENTS. F. STEEL ROOF DECK SHALL BE ATTACHED TO STEEL SUPPORTS WITH 5/8" DIAMETER PUDDLE WELDS AND TO COLD FORMED METAL FRAMING WITH #12 HEX HEAD SCREWS. WHEN DECK THICKNESS IS LESS THAN 0.028 INCHES, WELDS MUST BE MADE THROUGH MIN. 16 GAUGE WELDING WASHERS. SPACING OF WELDS SHALL BE AS FOLLOWS 1. AT BUTTED ENDS: AT 12" O.C. 2. AT PERIMETER/EDGES OF BUILDING AND WITHIN 12' OF THE PERIMETER/EDGES OF BUILDING : AT 36/7 PATTERN OR 6" O.C. 3. INTERMEDIATE SUPPORTS: AT 36/4 PATTERN OR 12" O.C. 4. SIDE LAPS: PROVIDE 4 CONNECTIONS PER SPAN. HEX HEAD SCREWS SIZE #10 SHALL BE USED AT SIDE LAP CONNECTIONS. H. CONTRACTOR SHALL COORDINATE THE CONSTRUCTION OF WALLS, BEAM FRAMING, METAL DECKING, ETC. WITH THE PITCH AND CAMBER OF STEEL JOISTS TO ENSURE COMPATIBILITY OF ROOF FRAMING AND WALL SYSTEMS. B. B. C. D. E. F F. G. H. I. E D C SUSPENDED LOADS AT STRUCTURE A. C. ALL COLD-FORMED STEEL FRAMING WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. ISOLATION OF NON-LOAD-BEARING FRAMING FROM BUILDING STRUCTURE TO PREVENT TRANSFER OF VERTICAL LOADS SHALL ALLOW FOR A MINIMUM OF X/X" MOVEMENT FROM LIVE LOAD. SEE ARCHITECTURAL DRAWINGS FOR NON-LOAD BEARING WALLS AND TO VERIFY ALL DIMENSIONS SHOWN FOR LOAD BEARING WALLS. SUBMIT STRUCTURAL DESIGN CALCULATIONS INDICATING COMPLIANCE WITH SPECIFIED DESIGN CRITERIA. CALCULATIONS SHALL BEAR THE SEAL OF A REGISTERED DESIGN PROFESSIONAL LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED. PROVIDE COLD-FORMED METAL FRAMING CAPABLE OF WITHSTANDING DESIGN LOADS WITHIN LIMITS AND UNDER CONDITIONS INDICATED IN THE CONSTRUCTION DOCUMENTS. DESIGN FRAMING SYSTEMS TO WITHSTAND DESIGN LOADS WITHOUT DEFLECTIONS GREATER THAN THE FOLLOWING: 1. EXTERIOR WALL FRAMING: HORIZONTAL DEFLECTION OF L/600 FOR BRICK/STONE VENEER, L/360 FOR SIMULATED STONE WALLS OR STUCCO FINISH AND L/240 FOR EIFS OR OTHER FLEXIBLE FINISHES. 2. FLOOR JOIST FRAMING: VERTICAL DEFLECTION OF 1/480 FOR LIVE LOADS AND L/360 FOR TOTAL LOADS OF THE SPAN. 3. ROOF RAFTER FRAMING: HORIZONTAL DEFLECTION OF 1/240 OF THE HORIZONTALLY PROJECTED SPAN. 4. CEILING JOIST FRAMING: VERTICAL DEFLECTION OF 1/240 OF THE SPAN. DESIGN ACCORDING TO AISI S100. IT IS ACCEPTABLE TO DESIGN SPECIFIC ELEMENTS PER THE RECOMMENDATIONS OF THE DESIGN STANDARDS OF AISI S210 THROUGH S214. NON-STRUCTURAL FRAMING MEMBERS SHALL COMPLY WITH ASTM C645. STRUCTURAL FRAMING MEMBERS SHALL COMPLY WITH ASTM 955. IN ADDITION TO DESIGN LOADS ALL COLD FORMED MEMBERS SHALL BE SIZED FOR THE CONNECTION REQUIREMENTS OF THE CLADDING AND/OR FRAMING WHICH ATTACHES TO THEM, INCLUDING BUT NOT LIMITED TO SHEATHING, PANELING, DOORS, WINDOWS, LOUVERS, MINOR CANOPIES, AND SUN SHADES. DESIGN AND COORDINATE INSTALLATION AND LOCATION OF ANCHORS AND INSERTS WITH STRUCTURAL SYSTEM TO WHICH COLD FORMED STEEL FRAMING IS ATTACHED. D. E. F. A. B. C. D. E. F. COMPOSITE STEEL FLOOR SYSTEM G. A. STEEL HEADED STUD ANCHORS (SHEAR CONNECTORS / SHEAR STUDS) SHALL BE TYPE B AND CONFORM TO AWS D1.1 AND ASTM A108 SPECIFICATIONS FOR 1010 THROUGH 1020 MILD STEELS. MINIMUM YIELD STRENGTH= 50,000 PSI. B. WHERE COMPOSITE BEAM DESIGNATION OCCURS ON FRAMING PLAN THROUGH THE CALLING OUT OF A NUMBER OF REQUIRED STEEL HEADED STUD ANCHORS, FLOOR AND BEAM ARE DESIGNED TO ACT COMPOSITE BY USE OF SHEAR STUDS ON TOP BEAM FLANGE. 1. SEE DISTRIBUTED STEEL HEADED STUD ANCHORS PLACEMENT DETAIL FOR PLACEMENT REQUIREMENTS. 2. IF LONGITUDINAL STUD SPACING EXCEEDS 12", PLUG WELD DECK TO BEAM BETWEEN STUDS. C. ALL STEEL HEADED STUD ANCHORS SHALL BE 3/4" DIAMETER x (FLUTE HT. + 1 1/2") AFTER WELDING, UNLESS OTHERWISE NOTED. 1. MINIMUM CLEARANCE FROM TOP OF STUD TO TOP OF SLAB IS 1". D. MAINTAIN INDICATED MINIMUM SLAB THICKNESS OVER BEAMS THROUGHOUT SPAN. ELEVATED SLAB SHALL BE PLACED WITH MINIMUM THICKNESS THROUGHOUT WITH NO MORE THAN 1/2" OF ADDITIONAL THICKNESS IN ANY LOCATION TO HELP WITIH THE LEVELING OF THE SLAB. H. I. J. A A. ALL COMPOSITE STEEL FLOOR DECK WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. B. STEEL COMPOSITE DECK SHALL BE ASTM A653 GALVANIZED G90, WITH A MINIMUM YIELD STRENGTH OF 50,000 PSI, UNLESS NOTED OTHERWISE. C. DECK SHALL BE SUPPORTED BY A MINIMUM OF FOUR SUPPORT LOCATIONS (THREE SPAN CONDITION). D. COMPOSITE STEEL FLOOR DECK SHALL BE ATTACHED TO THE SUPPORTS WITH 5/8" DIAMETER PUDDLE WELDS. WHEN DECK THICKNESS IS LESS THAN 0.028 INCHES, WELDS MUST BE MADE THROUGH MIN. 16 GAUGE WELDING WASHERS. SPACING OF WELDS SHALL BE AS FOLLOWS: 1. AT BUTTED ENDS: AT 12" O.C. 2. AT PERIMETER/EDGES OF BUILDING: AT 12" O.C. 3. INTERMEDIATE SUPPORTS: AT 12" O.C. 4. SIDE LAPS: AT MID-SPAN OR AT 3'-0" O.C., WHICHEVER IS SMALLER. HEX HEAD SCREWS SIZE #10 OR CRIMPING (BUTTON PUNCHING) MAY BE USED AT SIDE LAP CONNECTIONS. ATTACHMENT TO ROOF DECK FOR ANY SUSPENDED LOADS IS PROHIBITED WITHOUT WRITTEN APPROVAL FROM ARCHITECT/STRUCTURAL ENGINEER OF RECORD. PIPE HANGERS SHALL BE ATTACHED TO BOTTOM FLANGES OF JOISTS OR BEAMS WITH APPROVED CLAMPS/CONNECTIONS. ALL MULTIPLE TIER CABLE TRAYS, PIPE RACKS OR GROUPS OF PIPES OR DUCTS SHALL BE SUPPORTED FROM EACH ROOF FRAMING MEMBER WHERE THE GROUP CROSSES THE MEMBER OR AT 8'-0" O.C. MAX. WHERE GROUP IS ORIENTED PARALLEL TO THE MEMBER, UNLESS NOTED OTHERWISE ON DRAWINGS. HANGERS SHALL BE ADDED AT ALL PIPE VALVE AND FITTING LOCATIONS. CONTRACTORS AND SUBCONTRACTORS SUSPENDING LOADS FROM STRUCTURE SHALL ACCOUNT FOR AND PROVIDE ALL CONNECTIONS, STRUTS, TIES AND RIGGING REQUIRED FOR COMPLETE INSTALLATION AND SHALL FURNISH DRAWINGS SHOWING POINTS OF SUPPORT, SUPPORT LOADS AND ALL REQUIRED SUPPLEMENTAL BRACING. PROVIDE SUPPORTS AND HANGERS AS REQUIRED FOR PIPING AND EQUIPMENT SO THAT ALL COMBINED LOADING SHALL NOT EXCEED ALLOWABLE LOADINGS OF STRUCTURE AS SHOWN ON STRUCTURAL DRAWINGS. SUPPORT LOCATIONS SHALL BE COORDINATED WITH OTHER TRADES AND SHALL BE INSTALLED IN ACCORDANCE WITH SPECIFICATIONS OF THE ITEMS SUPPORTED. EXPENSE RESULTING FROM IMPROPER COORDINATION OR LOCATION OF ANCHOR BOLTS, OPENINGS, SLEEVES, INSERTS, HANGERS OR OTHER SUPPORTS REQUIRED FOR PIPING AND EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. WOOD FRAMING K. L. COMPOSITE STEEL FLOOR DECK B 9 A. ALL STRUCTURAL STEEL JOIST AND JOIST GIRDER WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. B. JOISTS SHALL BE EQUALLY SPACED BETWEEN COLUMN LINES OR OTHER SPECIFICALLY LOCATED FRAMING MEMBERS UNLESS NOTED OTHERWISE. C. STAGGER CONNECTION FOR BEARING NOTE. D. EXTEND LOWER JOIST CHORD AT ALL COLUMNS. DO NOT WELD TO STEEL TAB PLATE. E. UNLESS NOTED OTHERWISE, K-SERIES STEEL JOIST SHALL HAVE 2 1/2" DEEP BEARING, LH-SERIES SHALL HAVE 5" DEEP BEARING. 1. WHERE STEEL JOIST OR GIRDER SLOPE EXCEEDS 1/4" PER FT., PROVIDE SLOPED BEARING AS NOTED IN SLOPED SEAT REQUIREMENTS OF SJI. F. HORIZONTAL BRIDGING SHALL BE PER SJI REQUIREMENTS. 1. BRIDGING SHALL BE DESIGNED TO FULLY BRACE TOP CHORD OF JOISTS UNDER SERVICE LOADS FOR JOISTS NOT BRACED BY STEEL ROOF DECK. 2. BOTTOM CHORD OF ROOF JOISTS SHALL BE DESIGNED FOR NET UPLIFT OF XXXX PSF (COMPONENTS & CLADDING), UNLESS NOTED OTHERWISE. 3. BOTTOM CHORD OF ROOF JOIST GIRDERS SHALL BE DESIGNED FOR NET UPLIFT OF XXXX PSF (MAIN WIND FORCE RESISTING SYSTEM). 4. PROVIDE ADDITIONAL BOTTOM CHORD BRIDGING AS REQUIRED FOR NET UPLIFT OF XXXX PSF (MAIN WIND FORCE RESISTING SYSTEM) FOR ROOF FRAMING. G. AT A MINIMUM, K-SERIES STEEL JOISTS SHALL BE CONNECTED TO STEEL BY 1/8" WELD, 1 1/2" EACH SIDE OR (2) 1/2" DIAMETER BOLTS. AT A MINIMUM, LONG SPAN STEEL JOISTS SHALL BE CONNECTED TO STEEL BY 1/4" WELD, 2" LONG EACH SIDE OR (2) 3/4" DIAMETER BOLTS. AT A MINIMUM, JOIST GIRDERS SHALL BE CONNECTED TO STEEL BY 1/4" WELD, 6" LONG EACH SIDE OR (2) 3/4" DIAMETER BOLTS. JOIST SEAT CONNECTION DETAILS SHALL BE PROVIDED BY FABRICATOR (BOLTED OR WELDED CONNECTIONS) BASED ON SJI AND LOADING REQUIREMENTS. A. G 8 A. ALL NONCOMPOSITE STEEL FORM DECK WORK SHALL BE IN ACCORDANCE WITH DIVISION 05 SPECIFICATIONS. B. STEEL FORM DECK SHALL BE ASTM A653 GALVANIZED G90, WITH A MINIMUM YIELD STRENGTH OF 60,000 PSI, UNLESS NOTED OTHERWISE. C. DECK SHALL BE SUPPORTED BY A MINIMUM OF FOUR SUPPORT LOCATIONS (THREE SPAN CONDITION). D. NONCOMPOSITE STEEL FORM DECK SHALL BE ATTACHED TO THE SUPPORTS WITH 5/8" DIAMETER PUDDLE WELDS. WHEN DECK THICKNESS IS LESS THAN 0.028 INCHES, WELDS MUST BE MADE THROUGH MIN. 16 GAUGE WELDING WASHERS. SPACING OF WELDS SHALL BE AS FOLLOWS 1. AT BUTTED ENDS: AT 10" O.C. 2. AT PERIMETER/EDGES OF BUILDING: AT 10" O.C. 3. INTERMEDIATE SUPPORTS: AT 10" O.C. 4. SIDE LAPS: FOR FORM DECK WITH SPANS 3'-6" OR GREATER, PROVIDE 2 CONNECTIONS PER SPAN. HEX HEAD SCREWS SIZE #10 OR CRIMPING (BUTTON PUNCHING) MAY BE USED AT SIDE LAP CONNECTIONS. COLD-FORMED STEEL FRAMING (STUDS AND JOISTS) H 7 10 11 12 13 14 15 16 17 18 19 STEEL NONCOMPOSITE FORM DECK OPEN-WEB STEEL JOISTS L K 5 M. N. O. P. Q. R. CONFORM TO NATIONAL DESIGN SPECIFICATIONS FOR WOOD CONSTRUCTION, PUBLISHED BY THE NATIONAL FOREST PRODUCTS ASSOCIATION, AF & PA NDS AND AF & PA SPECIAL DESIGN PROVISIONS FOR WIND & SEISMC. UNLESS NOTED OTHERWISE, USE SPRUCE-PINE-FIR , 19% MAX. MOISTURE CONTENT, AS FOLLOWS: 1. BEAMS, HEADERS NO. 1/NO. 2 2. LOAD BEARING STUDS, & EXTERIOR STUDS NO. 1/NO. 2 3. JOISTS, PURLINS NO. 1/NO. 2 4. SUB-PURLINS, PLATES, BLOCKING NO. 1/NO. 2 5. NON-LOAD BEARING INTERIOR STUDS STUD GRADE ANY WOOD IN CONTACT WITH CONCRETE, MASONRY, SOIL, OR EXPOSED TO THE ELEMENTS SHALL BE PRESSURE TREATED. METALS (PLATES, NAILS, BOLTS, ETC) IN CONTACT WITH PRESSURE TREATED, FIRE-RETARDANT OR WOLMANIZED WOOD SHALL HAVE G185 ZINC GALVANIZED COATING. ALL OTHER METALS IN CONTACT WITH WOOD SHALL HAVE G90 ZINC GALVANIZED COATING. METAL CONNECTORS SHALL BE FASTENED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS TO DEVELOP THE MAXIMUM PUBLISHED CAPACITY. TIMBER FASTENING SHALL BE PER GOVERNING BUILDING CODE "MINIMUM FASTENING SCHEDULE" UNLESS NOTED AS GREATER ON CONSTRUCTION DRAWINGS. CONNECTORS TO BE SIMPSON OR APPROVED ALTERNATE, WITH MINIMUM CAPACITY AS NOTED. TOE NAILS SHALL BE DRIVEN AT AN ANGLE OF 30 DEGREES TO THE PIECE AND BE STARTED AT 1/3 THE NAIL LENGTH FROM THE END OF THE PIECE. ALL BOLTS SHALL BE FURNISHED WITH STANDARD NUT WASHER. ALL NAILS SHALL BE COMMON WIRE NAILS. GENERAL STRUCTURAL WOOD NOTES: 1. (3)-2x, (2)-2x AND (2)-2x + 1/2" PLYWOOD PLATE BEAMS SHALL BE SPIKED TOGETHER W/12d NAILS @ 12" O.C. TOP & BOTTOM. (4)-2x AND LARGER BEAMS SHALL BE BOLTED TOGETHER W/ 1/2" DIAMETER BOLTS @ 2'-6" O.C. MAX. TOP & BOTTOM. 2. ROOF BEAMS WITH SPANS GREATER THAN 5'-0" SHALL BE ANCHORED EACH END WITH (1)-1/4" X 16 GA. (MIN.) STRAP WITH (4)-8D NAILS INTO BEAM AND INTO JAMB STUDS. 3. MULTIPLE STUD OR SOLID COLUMNS SHALL BE CONTINUOUS FROM FRAMING LEVEL, WHERE SHOWN, TO THE FOUNDATION. THIS WILL REQUIRE SOLID BLOCKING WITHIN THE FLOOR FRAMING EQUAL TO THE COLUMN DIMENSION (SEE TYPICAL DETAIL). 4. MULTIPLE STUD PACK COLUMNS SHALL BE CONNECTED LATERALLY TO ONE ANOTHER WITH 16d NAILS AT 16" O.C. VERTICALLY. PROVIDE ONE ROW OF BRIDGING FOR EACH 8'-0" SPAN FOR ROOF JOISTS. WALL SHEATHING NOTED ON STRUCTURAL DRAWINGS OR SCHEDULES SHALL BE ATTACHED DIRECTLY TO THE FACE OF FRAMING MEMBERS. SEE ARCHITECTURAL DRAWINGS FOR ALL NON-STRUCTURAL SHEATHING REQUIREMENTS. ADDITIONAL SHEATHING REQUIRED BY ARCHITECTURAL DRAWINGS SHALL BE ATTACHED TO THE OUTSIDE FACE OF STRUCTURAL SHEATHING. AT CONTRACTOR'S OPTION, FINGER-JOINTED LUMBER MAY BE USED FOR WALL STUDS ONLY. ALL NON-LOAD BEARING, AND NON-SHEAR WALLS MAY BE ANCHORED USING POWDER-DRIVEN FASTENERS, 3/4" MAX. EMBEDMENT DEPTH. ALL WALL DOUBLE TOP PLATES SHALL BE LAPPED AT CORNERS AND INTERSECTIONS AND FASTENED PER GOVERNING BUILDING CODE "MINIMUM FASTENING SCHEDULE" UNLESS NOTED OTHERWISE. ALL DOUBLE PLATE END JOINTS SHALL BE OFFSET AT LEAST 24". DOUBLE PLATES TO BE FASTENED TOGETHER PER GOVERNING BUILDING CODE "MINIMUM FASTENING SCHEDULE", UNLESS NOTED OTHERWISE. AT LOAD-BEARING WALLS, FASTEN EA. PLATE TO PLATE WITH (2) ROWS 12d NAILS AT 8" O.C. JOISTS OR STUDS SHALL NOT BE CUT TO INSTALL PLUMBING OR WIRING UNLESS METAL OR WOOD SIDE PIECES/PLATES ARE PROVIDED TO STRENGTHEN THE MEMBER. WALL FRAMING MAY BE PANELIZED (WITHOUT GYPSUM WALLBOARD OR SHEATHING). SUBMIT PANEL DRAWINGS FOR REVIEW. LET-IN BRACING FOR WALL PANELS IS NOT ALLOWED. SHEATHING FASTENED TO FACE OF WALL AT SHOP MAY SERVE AS PANEL BRACING. COMPONENTS & CLADDING EXTERNAL PRESSURE LOADS (PSF) ABBREVIATIONS ACI AMERICAN CONCRETE INSTITUTE K KIPS (KILOPOUNDS) ADDL ADDITIONAL KLF KIPS PER LINEAL FOOT AESS ARCHITECTURAL EXPOSED STRUCTURAL STEEL KSI KSF KIPS PER SQUARE INCH KIPS PER SQUARE FOOT AFF ABOVE FINISHED FLOOR L LENGTH AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION AISI LONG FACE HORIZONTAL LONG FACE VERTICAL LG LONG ALTN AMERICAN IRON ANDSTEEL INSTITUTE ALTERNATE LFH LFV LL LIVE LOAD AR ANCHOR ROD LLH LLV LO LONG LEG HORIZONTAL LONG LEG VERTICAL LOW LOCS LOCATIONS >100 LRFD LSH LOAD RESISTANCE FACTORED DESIGN LONG SIDE HORIZONTAL >500 ARCH ASD ASTM ARCHITECT ALLOWABLE STRESS DESIGN EFFECTIVE WIND AREA (FT 2 ) <10 20 50 IBC 2012: LOCATION PER ASCE 7-10: FIGURE 30.4-1, 30.4-2A 1 16.5 -40.6 2 16.5 -68.1 3 16.5 -102.6 4 5 40.6 -44.1 6 7 40.6 -54.4 33.5 -61.4 8 Croft & Associates 9 33.5 -92.4 87.13 -67.83 114.71 -76.1 84.82 -67.5 109.33 -75.6 77.88 -66.48 93.2 -74.08 66.31 -64.79 66.31 -71.55 59.56 -51.29 59.56 -51.29 16.0 16.0 16.0 38.8 38.8 33.33 33.3 -39.6 -60.9 -84.9 -42.2 -50.7 -59.0 -86.6 16.0 16.0 16.0 36.4 36.4 32.8 32.8 -38.2 -51.3 -61.7 -39.8 -45.9 -51.8 -69.0 16.0 16.0 16.0 34.5 34.5 32.0 32.0 -37.2 -44.1 -44.1 -38.0 -42.2 -39.7 -39.7 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com AWS AMERICAN SOCIETY OF TESTING AND MATERIALS AMERICAN WELDING SOCIETY B/ BOTTOM OF BD BETW BLDG BOARD BETWEEN BUILDING LSV LW LONG SIDE VERTICAL LONG WAY LWC LIGHT WEIGHT CONCRETE BM BOT BP BEAM BOTTOM BASE PLATE MAX MEP MAXIMUM BRDG BRG C/C CFSF BRIDGING BEARING CENTER-CENTER COLD FORMED STEEL FRAMING MEZZ MFR MEZZANINE MANUFACTURER MIN MINIMUM CJ CONTROL JOINT CL CENTERLINE CLR CLEAR MISC MTL NIC NS MISCELLANEOUS METAL NOT IN CONTRACT NEAR SIDE CMU CONCRETE MASONRY UNIT NTS NOT TO SCALE OC ON CENTER OD OH OPNG OUTSIDE DIAMETER OPPOSITE HAND OPENING PAF POWDER ACTUATED FASTENERS OWNER PEMB PJF PL PLF PPHCC PRE-ENGINEERED METAL BUILDING PREFORMED JOINT FILLER PLATE POUNDS PER LINEAL FOOT COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS MECHANICAL, ELECTRICAL & PLUMBING 16.0 16.0 16.0 30.3 30.3 25.1 25.1 -37.2 -44.1 -44.1 -33.7 -33.7 -39.7 -39.7 NOTES: 1. a = 15'-0" a 2. POSITIVE PRESSURE VALUES REFER TO FORCES ACTING TOWARDS BUILDING, NEGATIVE PRESSURE VALUES REFER TO FORCES ACTING AWAY FROM BUILDING. 3. EACH COMPONENT MUST BE DESIGNED FOR MAXIMUM POSITIVE AND NEGATIVE FORCES. 4. FOR COMPONENTS HAVING EFFECTIVE AREAS IN BETWEEN TABULATED VALUES, DESIGN LOADS MAY BE INTERPOLATED. OTHERWISE DESIGN LOAD MUST BE TAKEN FROM THE NEXT LOWEST EFFECTIVE AREA. DESIGN VALUES SHOWN IN THIS TABLE ARE ULTIMATE VALUES FOR USE WITH LRFD DESIGN. VALUES MAY BE MULTIPLED BY 0.6 FOR USE WITH SERVICE LEVEL OR ASD DESIGN. REFER TO THE BUILDING CODE FOR APPLICABLE LOAD COMBINATIONS. 5. a 9 5 a 8 9 4 (TYP) 3 2 3 2 1 2 5 PES PROJECT NUMBER: 0214062 3 2 COL COLUMN CONC CONCRETE CONN CONNECTION CONT CONTINUOUS CTR D&E CENTER DRILL & EPOXY D DBA DEEP DEFORMED BAR ANCHOR DBL DOUBLE DEP DEPRESSED DIA DIAMETER PREFAB PRE-FABRICATED DIAG DIAGONAL PSI POUNDS PER SQUARE INCH DL DEAD LOAD PSF POUNDS PER SQUARE FOOT DWL DN EA EF DOWEL DOWN EACH EACH FACE PT POST TENSIONED P.T. PRESSURE TREATED QTY RAD QUANTITY RADIUS EJ ELEV EXPANSION JOINT ELEVATION RD ROOF DRAIN REF REFERENCE ENG ENGINEER OR ENGINEERING EOS EDGE OF SLAB EQ EW EXIST EQUAL EACH WAY EXISTING REINF REQD REV REINFORCING REQUIRED REVISION RTU ROOF TOP UNIT SCHED SCHEDULE EXP EXT EXPANSION SER STRUCTURAL ENGINEER OF RECORD F/ FACE OF SF SQUARE FOOT FD FLOOR DRAIN SHTHG SHEATHING FDN FF FOUNDATION FINISH FLOOR SIM SLH SIMILAR SHORT LEG HORIZONTAL FLR FLOOR SLV SHORT LEG VERTICAL FRT FIRE RETARDANT TIMBER SPA SPACES FS FAR SIDE SPEC SPECIFICATION FTG FV FOOTING FIELD VERIFY SS STD STAINLESS STEEL STANDARD GA GALV GC GDR GENL GYP GAUGE, GAGE GALVANIZED GENERAL CONTRACTOR GIRDER GENERAL GYPSUM STIFF STL SW SYM T/ T&B STIFFENER STEEL SHORT WAY SYMMETRICAL TOP OF TOP & BOTTOM HCA HDR HGR HEADED CONCRETE ANCHORS HEADER HANGER T&G TEMP THK TONGUE & GROOVE TEMPORARY THICKENED or THICK HI HIGH THRU THROUGH C&C LOADS HKD HOOKED TYP TYPICAL SCALE: 3/64" = 1'-0" HORIZ HSS HORIZONTAL HOLLOW STRUCTURAL SECTION UNO VERT UNLESS NOTED OTHERWISE VERTICAL H.T. ID HEAVY TIMBER INSIDE DIAMETER W W/ WIDE WITH IE INVERT ELEVATION W/O WITHOUT INSUL INSULATION OR INSULATING WD WOOD INT JST INTERIOR JOIST WP WORK POINT WWR WELDED WIRE REINFORCEMENT JT JOINT EXTERIOR PRESTRESSED PRECAST HOLLOW CORE CONCRETE (TYP) 4 a © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 2" 1" 1/2" 0 12/19/2014 5:09:16 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 3 HOT-DIP GALVANIZED STRUCTURAL STEEL N M 2 PARAPET 3" 1 WALL ELEVATION 3 ROOF PLAN 7 2 3 6 7 7 7 2 1 6 6 6 7 6 3 6 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 1 2 6 7 7 3 1 6 7 7 3 S-002 D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 LEGEND DRAWN: ABS FX (+/-) X' - X" CHECKED: TRP FOOTING SIZE DESIGNATION SHEET TITLE TOP/FOOTING ELEVATION VERSUS PROJECT 0'-0" ELEVATION GENERAL NOTES & SCHEDULES SHEET NO. S-002 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 N © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:09:24 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" NON-LOAD BEARING STEEL STUD HEADER SCHEDULE SIZE OF OPENING MIN. LAP SPLICE LENGTH SCHEDULE FOR CONCRETE MASONRY UNITS (CMU) WITH REINFORCEMENT IN CENTER OF WALL BAR SIZE REMARKS HEADER SIZE CONCRETE MIXTURES M CMU TYPE 0'-0" - 4'-0" (2) 800S162-43 8'-0" - 12'-0" 8" CMU SEE DETAIL B BELOW (2) 600S162-43 4'-0" - 8'-0" L SEE DETAIL A BELOW TRACK ONLY SEE DETAIL B BELOW #4 #5 #6 #7 #8 #9 12" 15" 23" 43" 60" 72" M 10" CMU 12" 12" 18" 34" 46" 71" 82" 12" CMU 12" 12" 15" 28" 38" 57" 74" NOTES: DETAIL A: 1/2 OF VERT STUDS DISPLACED BY OPNG (2-MIN) K #3 1. F'm = 1500 psi 2. REBAR IS ASSUMED TO BE UNCOATED (NO EPOXY COATING) 3. REBAR IS LOCATED IN CENTER OF CELL. 4. 'M' DENOTED MECHANICAL BAR SPLICE IS REQUIRED. SPLICE SHALL DEVELOP 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR IN TENSION OR COMPRESSION. APPLICATION EXPOSURE F'c MAXIMUM W/C AIR CONTENT NOMINAL MAXIMUM AGGREGATE SIZE (NOTE 4) MAXIMUM CONCRETE WEIGHT FOOTINGS F0 3000 PSI SEE NOTE 2 SEE NOTE 3 1" 150 PCF EXTERIOR SLABON-GRADE F1 4000 PSI 0.45 4.5% + 1.5% 1" 150 PCF INTERIOR SLABON-GRADE F0 3000 PSI SEE NOTE 2 SEE NOTE 3 1" 150 PCF WALLS F0 3000 PSI SEE NOTE 2 SEE NOTE 3 3/4" 150 PCF ELEVATED SLAB F0 4000 PSI SEE NOTE 2 SEE NOTE 3 3/4" 120 PCF Croft & Associates 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com NOTES: J MIN. LAP SPLICE LENGTH SCHEDULE FOR CONCRETE MASONRY UNITS (CMU) WITH REINFORCEMENT OFF-CENTER DETAIL B: 8" OR 12" CMU 1/2 OF VERT STUDS DISPLACED BY OPNG (2-MIN) #4 #5 #6 #7 #8 #9 15" 26" 40" 54" 63" 72" 82" WHERE NO MAXIMUM WATER CEMENT RATIO IS NOTED FOR DURABILITY, PROPORTIONING OF WATER/CEMENT RATIO SHALL BE AS REQUIRED FOR SPECIFIED CONCRETE MIX DESIGN . WATER/CEMENT RATIO IS NOT APPLICABLE FOR DURABILITY REQUIREMENTS IN LIGHTWEIGHT CONCRETE. WHERE AIR ENTRAINMENT IS NOT REQUIRED BY DESIGN, THE CONTRACTOR, INSTALLER, AND SUPPLIER MAY CHOOSE TO INCLUDE AIR ENTRAINMENT TO IMPROVE PLACEMENT AND FINISHING CHARACTERISTICS. AIR ENTRAINMENT IS NOT PERMITTED IN CONCRETE TO RECEIVE A HARD TROWEL FINISH AND ENTRAPPED AIR SHALL NOT EXCEED 3%. 4. CMU TYPE #3 EXPOSURE CATEGORIES AND CLASSES FOR SULFATES, PERMEABILITY, AND CORROSION PROTECTION OF REINFORCEMENT IS CLASS ZERO UNLESS NOTED OTHERWISE. 2. 3. BAR SIZE 54 MIL (MIN) CONN PLATES EA SIDE 1. COURSE AGGREGATE SHALL BE ASTM C 33, GRADED. SELECT GRADING CLASS PER TYPE OF CONSTRUCTION OR LOCATION USED, AND IN RELATION TO SPECIFIC WEATHERING REGION. AGGREGATE SHALL BE FROM A SINGLE SOURCE. #67 GRADING SHALL BE USED FOR CONCRETE WITH 3/4 INCH MAXIMUM; #57 GRADING SHALL BE USED FOR CONCRETE WITH 1 INCH MAXIMUM; A WELL BLENDED MIX OF #4, #57 AND #89 (1 1/2" TO 3/8" NOMINAL SIZE ) SHALL BE USED FOR CONCRETE WITH 1 1/2 INCH MAXIMUM. I 2 JACK STUDS (4) SCREWS OR 4" TOT WELD MEMBER-TO-MEMBER @ TOP OF JACKS T&B TRACKS SAME GAUGE AS HEADER 1. F'm = 1500 psi 2. REBAR IS ASSUMED TO BE UNCOATED (NO EPOXY COATING) 3. REBAR IS LOCATED OFF-CENTER IN CELL WITH MASONRY COVER (DISTANCE FROM NEAREST EXT F/CMU TO OUTERMOST F/REBAR) OF 2". NOTES: H 4. 1. UNLESS NOTED OTHERWISE, END CONNECTIONS FOR HEADER SHALL BE THE FOLLOWING: A. THRU CONNECTIONS TO JACK STUDS W/ (2) SCREWS AT TOP OF JACK STUD TO ADJACENT FULL HEIGHT STUDS (FOR SPANS LESS THAN 6-FT) CLASS B TENSION LAP SPLICE LENGTHS (ACI 318, SECTION 12.2.2 AND 12.15) F'c = 3000 PSI NOTE B: T&B OF HEADER TOP BARS BAR SIZE 2. UNLESS NOTED OTHERWISE, AT SILL, PROVIDE 54 MIL x WALL STUD WIDTH CONTINUOUS TRACK W/ 68 MIL CLIP EACH END OF TRACK (3-SCREWS PER LEG AT EACH CLIP) F STEEL STUD SILL SCHEDULE E SIZE OF OPENING 0'-0" - 4'-0" SILL SIZE (2) 600S162-43 REMARKS 8.5 12 3 11.5 12 4 17.0 12 5 24.5 12 6 32.5 6 8 52.0 6 CASE 1 CASE 2 CASE 1 CASE 2 #3 28 42 21 32 #4 37 56 28 #5 46 69 #6 56 #7 TOP BARS BAR SIZE SEE DETAIL BELOW 1. 2. 12'-0" - 14'-0" (2) 1000S162-54 (2) 1200S162-54 SEE DETAIL BELOW OTHER BARS CASE 1 CASE 2 CASE 1 CASE 2 #3 24 36 18 28 43 #4 32 48 25 37 36 53 #5 40 60 31 46 83 43 64 #6 48 72 37 55 81 131 62 93 #7 70 105 54 81 #8 93 139 71 107 #8 80 120 62 92 #9 104 157 80 120 #9 90 136 70 104 #10 118 176 90 136 #10 102 153 78 117 #11 131 196 100 151 #11 113 170 87 130 CASE 2 CLEAR SPACING < 2.0 BAR DIA CASE 1 CONCRETE COVER > 1.0 BAR DIA AND CLEAR SPACING > 2.0 BAR DIA CASE 2 CONCRETE COVER < 1.0 BAR DIA OR CLEAR SPACING < 2.0 BAR DIA 1 1/2 IN CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: SLABS, WALLS, JOISTS: #14 AND #18 BARS 3/4 IN BEAMS, COLUMNS: PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS 7. NO PIPING SHALL RUN BELOW THE BOTTOM CHORD OF THE BAR JOIST. 5" DIA. PIPE OR GREATER (LOCATE IN MIDDLE THIRD) (ABOVE OR BELOW BRIDGING, COORD. W/ JOIST MANUF'R) SPAN (OPENING) LINTEL SIZE 0'-0" - 4'-0" L5 x 3 1/2 x 5/16 (LLH) 4'-0" - 6'-0" L5 x 5 x 5/16 6'-0" - 8'-0" BENT PLATE 6 x 5 x 1/4 (LLV) L/3 WALL STUDS VENEER (SEE ARCH) SHEATHING (SEE ARCH) 54 MIL (MIN) CONN PLATES EA SIDE 1/2 OF VERT STUDS DISPLACED BY OPNG (2-MIN) B D C No. WALL HEADER PER SCHEDULE ALL OTHERS T&B TRACKS SAME GAUGE AS HEADER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 DETAILS: L/3 C DETAIL: 1 1/2 IN DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER BRICK/STONE VENEER LINTEL SCHEDULE (FLUSH-TO-STUD) 6. ANY PIPE OR COMBINATION OF PIPES WITH TOTAL DIAMETERS GREATER THAN 8" SHALL BE HUNG PER THE DIRECTION OF THE ARCH. NOTIFY ARCH. PRIOR TO PROCEEDING W/WORK. 4" DIA. PIPE OR LESS 1 1/2 IN #11 BAR AND SMALLER CASE 1 AND CASE 2 DEPEND ON THE TYPE OF STRUCTURAL MEMBER, CONCRETE COVER, AND BAR SPACING AND ARE DEFINED AS FOLLOWS: BEAMS & COLUMNS SEE DETAIL BELOW 2 IN #5 BAR, W31 OR D31 WIRE, AND SMALLER TABULATED VALUES ARE BASED ON MINIMUM YIELD STRENGTH OF 60 KSI. LENGTHS ARE IN INCHES. CLEAR SPACING > 2.0 BAR DIA 3 IN #6 THROUGH #18 BARS STRUTS/CLIPS BY PIPE ERECTOR CASE 1 COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS CONCRETE IN CONTACT WITH GROUND OR WEATHER: 3. EXACT PIPE LOCATIONS TO BE COORDINATED W/ MECHANICAL DRAWINGS. 4. PIPES RUNNING PARALLEL TO JOISTS W/ DIA. GREATER THAN 4" OR RUNNING IN COMBINATION W/ OTHER PIPES SHALL BE DISTRIBUTED TO A MINIMUM OF 2 JOISTS. 5. MEMBER SIZES ON PLANS HAVE BEEN ADJUSTED TO SUPPORT WATER PIPING LOADS IN THIS TABLE. L/3 8'-0" - 12'-0" CONCRETE COVER CONCRETE CAST AGAINST AND PERMANTLY IN CONTACT WITH GROUND 1. PIPES IN TABLE ARE SCHEDULE 40 OR STANDARD (S) TYPE. 2. PIPE WEIGHT INCLUDES: PIPE + INSULATION + WATER F'c = 4000 PSI OTHER BARS OWNER NOTES: NOTES (2) 800S162-43 2 1/2 SEE DETAIL BELOW D 4'-0" - 8'-0" PIPE SUPPORT SPACING (MAX.) (FT.) HEADER NOTE A: SHORT TRACK W/ (4) SCREWS TO HEADER & SCREW EACH FLANGE TO EACH JACK G PIPE DIA. (IN.) PIPE WEIGHT (LB./FT.) 'M' DENOTED MECHANICAL BAR SPLICE IS REQUIRED. SPLICE SHALL DEVELOP 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR IN TENSION OR COMPRESSION. B. 68 MIL CLIP CONN, IN ADDITION TO CONN NOTED IN A., W/ (3) SCREWS PER LEG AT EACH CLIP CONN LIP DIRECTLY TO FULL HEIGHT STUDS AND PROVIDE CLIP AT T&B OF HEADER. CAST-IN-PLACE CONCRETE (NONPRESTRESSED) CLEAR COVER SCHEDULE WATER PIPING SUPPORT SCHEDULE NOTES: PES PROJECT NUMBER: 0214062 12.19.14 10.27.14 Date 3. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES OF FRESH CONCRETE PLACED BELOW THE DEVELOPEMENT OR SPLICE. 4. REBAR IS ASSUMED TO BE UNCOATED (NO EPOXY COATING). INCREASE DEVELOPMENT LENGTHS SHOWN BY 1.3 FOR TOP, AND 1.5 FOR OTHER EPOXY COATED BARS. 14116 5. FOR LIGHTWEIGHT CONCRETE, MULTIPLY TABULATED VALUES BY 1.3. 6. LAP SPLICE LENGTHS SHALL BE AS SHOWN IN THE TABLE ABOVE, UNLESS NOTED OTHERWISE. DRAWN: ABS PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER (4) SCREWS OR 4" TOT WELD MEMBER-TO-MEMBER @ TOP OF JACKS 1" MAX LINTEL (SEE SCHEDULE) 2 JACK STUDS CHECKED: TRP SHEET TITLE GENERAL SCHEDULES NOTES: A 1. PROVIDE 4" BEARING (MIN) AT EACH END OF LINTEL ANGLES. SHEET NO. S-003 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2" N H F G 10' - 10 3/8" 13' - 7 5/8" Croft & Associates M 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com X 1 SLOPE SLAB TO DRAIN (TYP) SEE NOTE 14 24' - 6" L K NEW CMU PARTITION WALLS @ RESTROOM (SEE ARCH FOR WALL SIZE) REINF PER 6/S302, 3/S302, INC NEW THICKENED SLABS BELOW WALLS NEW CMU PARTITION WALLS @ RESTROOM (SEE ARCH FOR WALL SIZE) REINF PER 6/S302, 3/S302, INC NEW THICKENED SLABS BELOW WALLS SEE NOTE 12 SLOPE SLAB TO DRAIN (TYP). SEE NOTE 14 SEE NOTE 12 4" CONCRETE SLAB-ON-GRADE REINFORCED W/ WWR 6X6-W2.1XW2.1 @ 1-1/2" BELOW T/SLAB OVER 4" CRUSHED STONE BASE (SEE ARCH FOR VAPOR RETARDER LOCATIONS). . T/SLAB = 0'-0" REF T/SLAB = 0'-0" 2 29' - 7 7/8" SEE NOTE 11 J SEE NOTE 11 UP NEW CONC WALL REINF PER 1/S304 W/ 24" DEEP CONC BEAM OVER DOOR REINF W/ (4)-#6 EA FACE & #4 TIES @ 6" OC SEE NOTE 11 T/FTG = -1' - 4" 8"X8" TURNDOWN @ PERIMETER OF NEW SLAB W/ 2" BELOW EXIST 4" SLAB-ON-GRADE T/FTG = 2' - 8" 41' T/FTG-=3"0' - 8" T/FTG = 4' - 8" T/FTG = 6' - 8" PES PROJECT NUMBER: 0214062 SEE NOTE 10 S S S S I 5 1 EXIST BLDG 75 .0 0° 4" CONCRETE SLAB-ON-GRADE REINFORCED W/ WWR 6X6-W2.1XW2.1 . @ 1-1/2" BELOW T/SLAB OVER 4" CRUSHED STONE BASE (SEE ARCH FOR VAPOR RETARDER LOCATIONS). 23' - 1 5/8" SEE NOTE 10 S-304 OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 18' - 5 3/8" 1 (TYP 2 SIDES) S-303 SEE NOTE 12 3 18' - 6" 8" 11 5/ 23' - T/SLAB = 0'-0" REF T/SLAB = 0'-0" 43' - 8" 0° .0 6 8 S-302 S-304 H UP 11' - 0 3/8" 3 2 S-304 2" EXP JOINT DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER G EXIST 8" CONC WALL ON 3'-0"W X 1'-0"D FTG REINF W/ #3 @ 18" OC SW & (2)-#3 CONT LW (TYP @ PERIMETER OF EXIST BLDG) 5 5 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 S-303 16' - 0 7/8" F T/EXIST EXT FTG = -1' - 0" (GC FV) (TYP UNO) UP SEE NOTE 11 NOTES: 1. F#: DENOTES FOOTING MARK (SEE SCHEDULE ON S-201). UP 6 2. P#: DENOTES CONCRETE PEDESTAL MARK (SEE 3/S-201). 13' - 7 1/4" 3. C#: DENOTES STRUCTURAL COLUMN MARK (SEE SCHEDULE ON S-201). 9 7 4. BP-#: DENOTES BASE PLATE MARK (SEE SCHEDULE ON 4/S-201). 5. CJ: DENOTES SLAB-ON-GRADE CONTROL JOINT (SEE 3/S-301). 6. SEE DETAILS 1/S-301 AND 2/S-301 FOR STANDARD DETAILS OF TRENCHES ADJACENT TO FOOTINGS AND PIPING PASSING UNDER WALL FOOTINGS. PIPING PASSING UNDER FOOTING MUST BE PLACED AND INSPECTED BEFORE FOOTINGS ARE PREPARED. 4' - 10" E 7. GC SHALL COORDINATE PLUMBING AND UTILITIES LOCATIONS WITH FOUNDATION AS NEEDED. ADDITIONALLY GC SHALL COORDINATE FOUNDATION ELEVATIONS WITH PLUMBING AND UTILITIES AS NEEDED. FORWARD ANY FOUNDATION LOCATION CHANGE REQUESTS TO STRUCTURAL ENGINEER OF RECORD FOR REVIEW AND APPROVAL. 8. DENOTES STEP IN FOUNDATION (SEE 4/S-301). S NEW STEEL STAIR (BY STAIR MANUF) D 9. 19' - 8" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 1/2" 0 29' - 8" S C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt 43' - 8" A S 12/19/2014 5:09:34 PM 29' - 8" B S THIS SHEET PLOTS ON 22" x 34" ANSI D 18' - 6" C D S 1" 6' - 0" E DENOTES STEEL BRACE (SEE DETAILS & ELEVATIONS ON S-601 & S-602). 10. NEW DOOR OPNG IN EXIST 8" CONC WALL (SEE ARCH). SEE 5 & 6/S-402 FOR HEADER REQUIREMENTS & ORDER OF CONSTRUCTION. 11. NEW DOOR OPNG IN EXIST CMU WALL. SEE 5 & 6/S-402 FOR HEADER REQUIREMENTS & ORDER OF CONSTRUCTION. CHANNEL HEADER SHALL BE CONTINUOUS ACROSS (2)DRWYS WHERE DRWYS LESS THAN 2'-0" APART. 12. INFILL EXIST WALL OPNGS W/ 8" CMU REINF PER 6/S-302. DRILL & EPOXY NEW VERT REINF 6" INTO EXIST WALL FTG BELOW & CMU WALL ABOVE. 13. G.C. SHALL F.V. EXIST CONDITIONS PRIOR TO DEMO OF EXIST OR FABR/INSTALLATION OF NEW CONSTRUCTION. COORD VARIATIONS W/ ARCH & EOR. 8 C H B LOWER LEVEL FOUNDATION PLAN SCALE: 3/32" = 1'-0" G F E D C B A B0.5 14. DENOTES DEPRESSED SLAB. SEE ARCH FOR DEPTH & EXTENTS. SEE 5/S-301. D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE Z PROJECT NUMBER 14116 1 S-101 DRAWN: ABS N CHECKED: TRP SHEET TITLE A EXISTING BUILDING NEW ADDITION ABOVE LOWER LEVEL FOUNDATION PLAN SHEET NO. S-101 12 13 14 15 16 C1 C2 H M F G E C D B 21' - 8" 18' - 6" 29' - 8" 43' - 8" 29' - 8" 10' - 10 3/8" 13' - 7 5/8" F6 /C1/BP-1 4 S-303 F6 /C1 /BP-1 BRACE UP 8' - 6" F6 /C1 /BP-1 9' - 0" 9' - 0" 9' - 0" 4 (TYP @ EXT COL UNO S-201 CJ (TYP) STORM LINE (SEE PLUMBING) 9' - 0" 9' - 0" CJ (TYP) 9' - 0" 9' - 0" (TYP @ INT S-201 COL) SEE 3/S-402 FOR TYP STL BM BRG ON CONC WALL 5. CJ: DENOTES SLAB-ON-GRADE CONTROL JOINT (SEE 3/S-301). NEW STAIR OPNG 5 1/2 " /C10/BP-8 F9 /C2 /BP-2 7' - 0" /P 9' - 0" S-304 R2 FD S-403 F7/C8 /BP-8 R3 3 3 S-403 S-201 4' - 10" 9' - 0" BRACE UP /C1/BP-1 F8.5x6 /C3/BP-3 S-201 9' - 0" 4 7' - 0" /P 8 8' - 0' - 6" (GC FV) Y1 E D C B 4' 9' - Y1.5 MAIN LEVEL FOUNDATION & FRAMING PLAN SCALE: 3/32" = 1'-0" 3' - 6" 4' - 6" 5' - 10" 1 S-102 2' - 0" 1' - 11" N B0.5 B1 B2 B2.6 UP B3 B4.7 B5 B5.7 0' - 3" 1' - 2" 9' - 6 1/8" 2' - 9"5' - 7 1/2" A6.1 A6 A5 A4 -8 11' - 1" 7/8 " -0 X2 X2.3 A3 A2 A1 B6 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE 14116 X3 Y3 2' - 6 3/8" 2' - 0 1/4" D C No. PROJECT NUMBER 7" 3" 8' - 6 5/8" Y2 6' - 8" A6.2 9' - 0" 8" A Z F6 /C5 /BP-5 S-303 A6.3 15 '- 4 A6.4 11 S-303 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 A6.5 4' - 0" 3 /C8 /BP-8 F8.5x6 /C8 /BP-8 4' S-303 S-304 STORM LINE (SEE PLUMBING) 9' - 0" 7/8 " 19' - 8" 3 X1 9' 4 F6 /C1/BP-1 A6.6 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER " S-304 9' - 0" F 8' - 8" RA 4 F12/C5 /BP-5 G 6' - 9 1/4" 9' - 0" 4 SEE NOTE 16 10' - 2" /C10 F10X9/C8/BP-8 9' - 0" F6 /C8 /BP-8 F12/C2 /BP-2 HSS10X6X3/8 EXIST SLAB & JOISTS SHALL BE DEMOED FOR NEW STAIR OPNG. PROVIDE ADD'L REINF @ EXIST CONC WALL & EXTEND FTG 11' - 7 1/8" Y0.5 7" A6.7 11' - 5 1/2" F4/C10/BP-8 9' - 0" BRACE UP H 6' - 7" 1' - 8" C 4 10 3' - BRACE UP FD 3 S-403 13 '- A6.9 0' - 7 1/2" DENOTES DEPRESSED SLAB. SEE ARCH FOR DEPTH & EXTENTS. SEE 5/S-301. 9' - 0" 4' - 8 5/8" FD 20. PRE-ENGINEERED ALUMINUM COLUMNS (BY OTHERS - SEE SHOP DWGS NOTE D ON S-001). 13' - 7 1/4" BRACE UP A7 2' - 3 1/2" 19. RB F12 /C7/BP-7 6' - 11" DN 6 /C2/BP-2 UP NEW STEEL STAIR (BY STAIR MANUF) (TYP 3 S-304 LOC'NS) /C6/BP-6 S-403 S-403 6 COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS A7.2 A6.8 Y0.3 /C3/BP-3 6 2 9' - 0" 9' - 0" 2' - 6" DENOTES 3" LIGHT WEIGHT CONC SLAB ON 9/16"-26 GA STEEL FORM DECK ON C8X11.5 CHANNELS @ 2'-0" OC MAX. MINIMUM DECK PROPERTIES: lp = 0.015 IN^4/FT ln = 0.015 IN^4/FT Sp = 0.043 IN^3/FT Sn = 0.043 IN^3/FT T/STEEL = (+) 10' - 9", T/SLAB = 11'-0" (UNLESS NOTED OTHERWISE) F12/C7/BP-7 F20X12 HSS12X8X1/2 3 16' - 0 7/8" 18. RC T/SLAB = SEE CIVIL REF T/SLAB = 11'-0" /C5/BP-5 17. G.C. SHALL F.V. EXIST CONDITIONS PRIOR TO DEMO OF EXIST OR FABR/INSTALLATION OF NEW CONSTRUCTION. COORD VARIATIONS W/ ARCH & EOR. OWNER A7.3 5' - 5 1/2" 16. NEW DOOR OPNG IN EXIST 8" CONC WALL (SEE ARCH). SEE 5 & 6/S-402 FOR HEADER REQUIREMENTS & ORDER OF CONSTRUCTION. 2 4" CONCRETE SLAB-ON-GRADE REINFORCED W/ WWR 6X6-W2.1XW2.1 @ 1-1/2" BELOW T/SLAB OVER 4" CRUSHED STONE BASE (SEE ARCH FOR VAPOR RETARDER LOCATIONS). (GC FV) 10' - 0" 15. FOR SLAB REINFORCING AT FLOOR OPENINGS SEE 5/S-401. A7.6 A7.4 S-304 S-402 (GC FV) 17' - 0" 3 14. "xx kip" AT END OF BEAMS DENOTE MINIMUM UNFACTORED (ASD) REACTIONS FOR CONNECTION DESIGN. IF REACTION IS NOT SHOWN, DESIGN CONNECTION PER STRUCTURAL STEEL NOTE I ON S-001 (TYP). 9' - 0" CONC STAIR (SEE 5/S-302) 4 S-403 F12 /C7/BP-7 S-304 PES PROJECT NUMBER: 0214062 A8 A7.5 4' - 4" 4 DN S-301 E/SLAB 13. GC SHALL VERIFY ALL OPENING DIMENSIONS WITH MECHANICAL. 5 OPEN 4 4 EQ SPA 12. FOR TYPICAL COMPOSITE FLOOR BEAM SEE DETAIL 3/S-401. G 3 5.00° S-403 1 W12X19 (10) W12X19 (12) 1 (GC FV) 10' - 0" 1 (GC FV) 43' - 8" H W12X19 (10) /BP-9 DENOTES STEEL BRACE (SEE DETAILS & ELEVATIONS ON S-601 & S-602). BRACE UP BRACE UP 9' - 0" 9' - 0" A9 /BP-4 (GC FV) DENOTES 3 1/2" LIGHT WEIGHT CONCRETE ON 2"-20 GAUGE COMPOSITE METAL DECK (TOTAL DEPTH: 5 1/2") W/ WWR 6X6-W2.1 X W2.1 IN FLAT SHEETS AT MID-DEPTH OF SLAB. T/SLAB = (+) 11'-0" MINIMUM DECK PROPERTIES: Ip = 0.409 IN^4/FT C12X20.7 CHANNELS @ PERIMETER In = 0.406 IN^4/FT OF EXIST SLAB OPNG BOLTED TO Sp = 0.341 IN^3/FT EXIST CONC BMS W/ 3/4" DIA Sn = 0.346 IN^3/FT EPOXY ANCHORS @ 12" OC T/STEEL = (+) 10'-6 1/2" (UNLESS NOTED OTHERWISE) (STAGGERED) (EMBED 8") (TYP) OPEN 11. (#) DENOTES QUANTITY OF 3/4" DIA x 4" LG HCA WELDED TO TOP FLANGE OF STEEL BEAM. F8.5x6/C3/BP-3 F6 /C3 /BP-3 8.53° 5' - 0" 37' - 0" 10. U P C 3 U P 2 (TYP) S-402 W12X19 (15) 9. F9 /C3 /BP-3 9' - 0" S-403 S 3 1' - 4 1/8" 7. GC SHALL COORDINATE PLUMBING AND UTILITIES LOCATIONS WITH FOUNDATION AS NEEDED. ADDITIONALLY GC SHALL COORDINATE FOUNDATION ELEVATIONS WITH PLUMBING AND UTILITIES AS NEEDED. FORWARD ANY FOUNDATION LOCATION CHANGE REQUESTS TO STRUCTURAL ENGINEER OF RECORD FOR REVIEW AND APPROVAL. 8. DENOTES STEP IN FOUNDATION (SEE 4/S-301). 2 A9.2 A8.1 9' - 0" BRACE UP 6. SEE DETAILS 1/S-301 AND 2/S-301 FOR STANDARD DETAILS OF TRENCHES ADJACENT TO FOOTINGS AND PIPING PASSING UNDER WALL FOOTINGS. PIPING PASSING UNDER FOOTING MUST BE PLACED AND INSPECTED BEFORE FOOTINGS ARE PREPARED. A9.7 A9.3 1' - 2" SEE 1 & 2/S-402 FOR TYP COL BRG ON CONC WALL 4. BP-#: DENOTES BASE PLATE MARK (SEE SCHEDULE ON 4/S-201). F6 /C3 /BP-3 9' - 0" 6' - 10" 62' - 2" A9.8 A9.4 F7.6 3. C#: DENOTES STRUCTURAL COLUMN MARK (SEE SCHEDULE ON S-201). 8.48 ° 29' - 7 7/8" DN SEE NOTE 20 (TYP) S-303 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com A9.1 9' - 0" 4 Croft & Associates A9.5 F7.6 2. P#: DENOTES CONCRETE PEDESTAL MARK (SEE 3/S-201). I A F7.6 F6 /C3/BP-3 9' - 0" EXIST CONC BEAM & PAN JOIST FLOOR 1. F#: DENOTES FOOTING MARK (SEE SCHEDULE ON S-201). J B A10 1 F6 /C1/BP-1 FD NOTES: C A11 F7.6 9' - 0" 7 A12 2 SEE NOTE 16 2 1' - 2" A9.6 F7.6 9' - 0" BRACE UP BRACE UP FD 9 9' - 0" F6 /C3/BP-3 F6 /C1/BP-1 D F7.6 8' - 6" 9' - 0" F6 /C1 /BP-1 S-303 K 8' - 6" F5 /C9 /BP-10 S-303 4 24' - 6" 8' - 6" F5 /C9 /BP-10 F6 /C1/BP-1 1 C6 F5/C9/BP-10 9' - 0" E 8' - 6" F5/C9 /BP-10 F5 /C9/BP-10 2" EXP JOINT F 21' - 9 1/2" 57' - 3 1/8" X C5 1' - 2" 8' - 6" 6' - 0" L C4 19 F5/C9 /BP-10 CANOPY FOUNDATIONS SHALL BE A MINIMUM OF 1'-6" BELOW FINISH GRADE (GC FIELD VERIFY) A 18 C3 1' - 2" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:09:47 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" N 17 1' - 2 3/8" 11 0' - 1 3/4" 10 1' - 5" 9 0' - 7" 8 1' - 2" 7 0' - 7" 6 9' - 5 3/4" 5 12' - 0 1/4" 4 7' - 5" 3 6' - 10" 1' - 2" 6' - 10" 2 8.0 0° 3" 1 4' - 10" DRAWN: ABS 5' - 8 3/8" 3' - 11 5/8" 3' - 2 1/8" 0' - 7 7/8" B6.3 B6.5 B7 2' - 0 7/8" 4' - 10" 9' - 5" SHEET TITLE 2' - 4" EXISTING BUILDING 1' - 1 7/8" B8 B8.5 B9 B10 B11 B12 B13 CHECKED: TRP B14 NEW ADDITION MAIN LEVEL FOUNDATION & FRAMING PLAN SHEET NO. S-102 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 C1 18 C2 C3 19 C4 C5 C6 N 21' - 8" ST PO 8' - ST PO C B 4' 3" Y1.5 1' - 2" 1' - 2" HSS12X6X1/2 22' - 0 3/8" 0' - 7" 0' - 7" 6' - 10" 1' - 2" 0' - 3" 6' - 7" 6' - 10" 1' - 2" HSS12X6X1/2 22' - 0 3/8" HSS8X4X3/8 PES PROJECT NUMBER: 0214062 A8 1' - 8" 8' - 8" 6' - 9 1/4" A7.5 A7.4 A7.3 RC A6.9 10' - 2" 8.53° 11' - 7 1/8" 3' - 4 3/8" RB 11' - 5 1/2" 2' - 3 1/8" 4' - 4" 6' - 11" 5' - 5 1/2" 8.0 0° A7 A6.7 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER A6.6 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 A6.3 A6.2 A6.1 A6 2' - 3 1/2" A5 11' - 1" X1 4' - 0" X2 X2.3 A4 A3 A2 A1 D C No. X3 LOW ROOF FRAMING PLAN SCALE: 3/32" = 1'-0" A 1 S-151 N 2' - 0" B0.5 B1 B2 B2.6 B3 1' - 11" PROJECT NUMBER B4.7 B5 B5.7 B6 B6.1 B6.3 DRAWN: ABS 3' - 2 1/8" 4' - 10" 2' - 6 3/8" 0' - 5" 5' - 8 3/8" 3' - 11 5/8" 1' - 7 1/4" B7 2' - 0 7/8" 4' - 10" 1' - 1 7/8" B6.5 PERMIT SET DD PRICING SET Description ISSUANCE 14116 Y3 8' - 6 5/8" 12.19.14 10.27.14 Date 7" Y2 6' - 8" COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS A7.2 B 3' - 6" 4' - 6" 5' - 10" OWNER A6.5 A6.4 2' - 9" 8.48 ° 9' - 6 1/8" 5.00° 21' - 7" HSS6X 4X1/4 A7.6 T/STL = 24' - 10 1/2" S-502 A 7' - 5" 26' - 0 1/4" W18X35 W18X35 26' - 0 1/4" HSS10 P U T S W18X46 (S) PO 3 9' - HSS8X4X3/8 HSS8X4X3/8 HSS8X4X3/8 HSS8X4X3/8 P 1 U C 8" Y1 D W18X35 25' - 9 3/4" 4' ST PO P 1 U C S-502 E 5 EQ SPA HSS 10X 6X3 /8 21 HSS '-1 6X4 1" X1/4 RAD IAL HS 21' - 7" RAD S6X IAL 6X5/ HSS 16 10X 6X3 /8 2 1' 11" 4 EQE SPA 1 C A8.1 RA S-502 4 F X6X3/8 21' - 11" W14X22 PO C3 ST U P ST PO P U S-505 0' - 7 1/2" PO C3 ST U P ST PO P 1 U C 8 G 25' - 9 3/4" W14X22 2 55 KIP 35 K-FT 2 CB P 1 U C 24' - 3 1/2" W12X19 C H 5 EQ SPA W18X35 25' - 0" CB CB 24' - 6" 4 EQ SPA W18X35 24' - 0" W18X35 1 C 3 7/8 " PROVIDE 12" VERTICAL SLOTTED CONNECTION @ T/COL TO B/BM CONN (TYP @ 2 COL LOC'NS @ COILING DOOR) -0 23. 7/8 " C#: DENOTES STRUCTURAL COLUMN MARK (SEE SCHEDULE ON S-201). 11 22. A9 15 '- PRE-ENGINEERED ALUMINUM CANOPY ( BY OTHERS - SEE SHOP DRAWINGS NOTE D ON S-001). 2 21. T/S T/S TL = TL W14X22 2 W1 = 2 4' - 6 4X 4' W8X10 -5 " 22 3/4 W1 " 3 4X Y0.3 W14X22 22 ( 25' - 11" S) S-503 W16X40 16K3 W16X40 T/S T/S T T W8X10 HS L = L = 2 16K3 S8 24' 4' HS Y0.5 -1 S X6 BRACE 03 21'- 10X6 X5 6" X1/ 1 / / 4 1" 16 W1 DN " 4 (LS 2 6X 16K3 1 V 3 12K1 ) 6( S) S-503 19 COL DN - SEE NOTE 23 'S-506 8" 16K2 W1 16K3 BRACE UP & DN 4X .2 22 ( 4 S) 1 3' 2E HS -6 Q S-503 S8 1/2 12K1 SP 16K3 S-502 W X3 " HS A 14 X X2 S1 1/4 BRACE DN 2 0 2 BRACE DN EQ X6X .2 SP 3/8 (S) W18X40 A W14X22 (S) 3 W 4 12K1 '14 P C 7" X3 U 0 T (S) S PO 20KCS4 RTU-2 12K1 6 CONT COL TO 2000# 1 1 P C W1 T/PARAPET S-502 U 20KCS4 4X T S-503 22 S 7 (S) 12K1 PO SEE 5/S-506 (SIM) S-502 20KCS4 1 1 3 P P C C U U T/STL = 25' - 1" 12K1 (S) S-506 ST ST O (S) 2 W18X35 POW18X35 P CB ROOF HATCH. SEE 1/S-501 & ARCH. A9.2 A6.8 H 21'-11SS10X6X " 1/4 W14X22 2 EXIST BLDG 20. HSS10X6X1/4 21'-11" (TYP 3 LOC'NS) OPEN .2 W1 HS 4X22 S1 0X 6X 3/8 HS S8 X3 X1 /4 3' -3 9' -8 1/4 " " DENOTES 22 GAUGE 1 1/2" B WIDE RIB METAL ROOF DECK. MINIMUM DECK PROPERTIES: Ip = 0.162 IN^4/FT IN = 0.175 IN^4/FT Sp = 0.183 IN^3/FT Sn = 0.189 IN^3/FT S-504 S-502 HSS10X8X3/8 20' - 10" 0" 2 SEE NOTE 21 HSS10X8X3/8 29' - 3 7/8" R = 12 6' - 3" W1 8X 35( S) 12 K1 (S) DENOTES SLOPING ROOF BEAM. T/STEEL = DECK BRG (TYP UNO). (S) 24' - 8 3/4" 4 EQ SPA 18. A9.3 1 2 HSS10X8X3/8 29' - 3 7/8" W18X35 NEW EXHAUST FAN TO BE INSTALLED ON EXIST MEZZ. CUT OUT SQUARE OF EXIST SLOPED ROOF ABOVE TO VENT & PROVIDE ADD'L FRAMING TO SUPPORT EDGES OF ROOF DECK (SEE ARCH & MEP FOR LOC'N). BRACE DN 24K9 4 EQ SPA 17. S-505 W14X22 A9.4 A9.1 CB W14X22 24' - 5 1/2" MOVEABLE PARTITION BELOW. PROVIDE C8X11.5 CONT ALONG LENGTH @ T/PARTITION. HANG FROM ROOF BEAM W/ L4X4X1/4 VERT & HORIZ ANGLES @ 24" O.C. (2 SPAN COND MIN) & L4X4X1/4 KICKERAS @ 4'-0" O.C. (ALT SIDES). S-504 (S) W16X36 16. 1 24K9 2 W14 X22 G.C. SHALL F.V. EXIST CONDITIONS PRIOR TO DEMO OF EXIST OR FABR/INSTALLATION OF NEW CONSTRUCTION. COORD VARIATIONS W/ ARCH & EOR. 2 CB 15. W14X22 SEE NOTE 16 ST PO W18X35 (S) A10 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com A9.5 5 HSS10X6X1/4 21'-11" W14X22 PO C3 ST U P PROVIDE 1/4" WEB STIFF PL'S @ 4'-0" O.C. @ ALL ROOF EDGE BEAMS. P U PO C3 ST W1 UP 4X2 2 14. 4' - 10" 7 CB PROVIDE L4X4X1/4 CONT DECK EDGE ANGLE @ PERIMETER OF EACH ROOF LEVEL. W27X146 (LO) 25' - 11" 13. T/STL = 27' - 0 3/4" TYP FOR W14X22 BTWN A6.4 & A7 (UNO) W18X35 (S) 1 C A11 A9.6 0" TYP S-502 Croft & Associates S-507 A9.7 (SIM) S-502 3 A9.8 0" TYP CB SEE 8/S-501 FOR TYP TUBE BEAM TO COL CONN. 6 9 D 12. 19. 13' - 7 1/4" E SEE 11/S-501 FOR TYP STEEL POST-UP COL CONN. 5 16' - 0 7/8" F 11. S-507 W18X35 (S) ST O P 1 P C U ST PO 1 P C U ST PO BRACE DN W16X40 25' - 11" W14X22 W14X22 W18X35 (S) P U 20K3 55 KIP 35 K-FT G SEE 7/S-501 FOR TYP STEEL BEAM OVER COL CONN. W18X35 (S) BRACE UP & DN W14X22 W14X22 CB W18X35 (S) S-506 5 EQ SPA 43' - 8" 10. W16X45 H "xx kip" AT END OF BEAMS DENOTE MINIMUM UNFACTORED (ASD) REACTIONS FOR CONNECTION DESIGN. IF REACTION IS NOT SHOWN, DESIGN CONNECTION PER STRUCTURAL STEEL NOTE I ON S-001 (TYP). 27' - 0 3/4" "CB" DENOTES L4X4X3/8 X 4'-0" LG (MIN) COL BRACE. WELD BRACE TO COL CAP PL & TOP CHORD OF JOIST OR TOP FLANGE OF BEAM W/ 3/16" FILLET WELD x 2" LG. USE (2) ANGLES @ T-SHAPED AREAS. WELD DECK TO EA ANGLE W/ 3/4" DIA PUDDLE WELDS @ 6" OC. W14X22 W18X35 8. 9. 1 C BRACE DN W18X35 (S) C 1 PO ST U P C 1 PO ST U P S-506 20K3 24' - 0" "BB" DENOTES BEAM BOTTOM FLANGE BRACE PER 5/S-501. 2 EQ SPA 7. 20K3 20K3 W14X22 2 EQ SPA 3 RTU-1 3000# W18X46 (S) SEE NOTE 20 W16X40 2 EQ SPA DENOTES MOMENT CONNECTION. DESIGN CONNECTIONS FOR FORCES INDICATED ON PLAN AND IN ELEVATIONS. DESIGN CONENCTIONS FOR THE FOLLOWING FORCES UNLESS NOTED OTHERWISE MOMENT: 20 K-FT SHEAR: 25 K 2 EQ SPA MAXIMUM DEPTH OF PONDING AT LOWEST POINT OF ROOF SHALL NOT EXCEED 4" UNDER PEAK INTENSITY STORM 5' - 1 5/8" DENOTES STEEL BRACE (SEE DETAILS & ELEVATIONS ON S-601 & S-602). 6. I S-502 REMOVE EXIST ROOF OVERHANG ALONG NEW ADDITION (GC LOCATE E/REMOVAL @ E/EXIST BEAM NEAREST 'A9.6' & 'A2' - G.C. F.V.) 5" 4. 5. 1 DO NOT SUPPORT MULTIPLE SPRINKLER MAINS FROM THE SAME JOIST. CONTRACTOR TO PROVIDE SPRINKER DRAWINGS TO STRUCTURAL ENGINEER AND JOIST MANUFACTURER FOR REVIEW AND COORDINATION PRIOR TO JOIST FABRICATION. 5" 29' - 7 7/8" SEE "WATER PIPING SUPPORT SCHEDULE" ON SHEET S-002 FOR ALL PIPING SUPPORTED FROM ROOF STRUCTURE. NOTIFY EOR IF PIPING WEIGHT IS IN EXCESS OF THOSE NOTED IN SCHEDULE. 7" 3. 20KCS3 P U 4 20KCS3 6 7/8" 2. ST PO PROVIDE STANDARD HORIZONTAL BRIDGING PER SJI. 1' - 4 1/8" 1. 1 C P U 20K3 5 EQ SPA 2 ST PO S-507 2 S-506 W18X35 25' - 0" W18X35 24' - 6" CB 24' - 6" NOTES: 1 C 20K3 W14X22 (S) 1 3 W16X26 (S) W18X35 (S) K J BRACE DN W14X22 (S) 4 EQ SPA 2 2 L S-502 W16X26 25' - 5 3/8" S-502 3 CB 4 2" EXP JT W18X35 1 BRACE DN 25' - 2 1/2" S-502 CONT COL UP TO T/PARAPET (SIM) HSS12X4X3/8 22' - 6" HSS8X4X3/8 6' - 10" 7 HSS8X4X3/8 1' - 2 3/8" 0' - 1 3/4" 13' - 7 5/8" 12 K1 10' - 10 3/8" 12 K1 29' - 8" A12 HSS12X4X3/8 22' - 6" 4 EQ SPA (S) 43' - 8" 12 K1 29' - 5 3/8" 1' - 2" EXIST BLDG HSS12X4X3/8 22' - 6" W1 6X 26 18' - 8 5/8" 12' - 0 1/4" M 6' - 0" HSS8X4X3/8 A CB B 9' - 5 3/4" C D 19' - 8" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 1" 1/2" 0 E W14X22 C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt F G 1 P C U ST PO 1 P C U ST PO 1 P C U ST PO 1 P C U ST PO 12/19/2014 5:09:57 PM 21' - 9 1/2" HSS12X4X3/8 22' - 6" H THIS SHEET PLOTS ON 22" x 34" ANSI D 1' - 2" 1' - 5" 2" 1' - 2" 9' - 5" SHEET TITLE 2' - 4" 0' - 7 7/8" B8 B8.5 B9 B10 B11 CHECKED: TRP B12 B13 B14 EXISTING BUILDING NEW ADDITION LOW ROOF FRAMING PLAN SHEET NO. S-151 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 H G F E C D B A Croft & Associates M 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com HSS6X3X1/4 (LSH) 32'-0" (TYP @ T/PARAPET) 1 L 3 7 4 S-502 S-502 S-506 NOTES: (S) DENOTES SLOPING ROOF BEAM. T/STEEL = DECK BRG (TYP UNO). 21. SEE 11/S-501 FOR TYPICAL POST UP DETAIL. 18' - 0" 26' - 11" S-503 1 S-502 S-503 W1 4X 22 9 (SIM) 7 4 (S ) W1 4X 22 S-502 S-506 S-502 T/S T T/S L = 3 6' TL -0 =3 " 7' -8 1/8 " 1 S-503 (S ) 8 4 S-502 G F E C D B Y1 A Y1.5 B 2' - 0" 3' - 6" 4' - 6" 5' - 10" HIGH ROOF FRAMING PLAN A SCALE: 3/32" = 1'-0" 1 S-152 B1 B2 B2.6 4' - Y2 6' - 8" 8' - 6 5/8" 2' - 6 3/8" B3 B4.7 B5 B5.7 B6 6' - 9 1/4" 9' - 6 1/8" 10' - 2" A6.5 A6.4 A6.3 A6.2 A6.1 A6 A5 A3 A2 A1 3" 1' - 11" DN B0.5 9' - 2' 2' - 9" - 33'1/8" - 4 3/8" 11' - 7 1/8" 4' - 0" C B6.1 7" D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 Y3 0' - 7 7/8" 4' - 10" 3' - 2 1/8" DRAWN: ABS 4' - 10" 1' - 1 7/8" 5' - 8 3/8" 3' - 11 5/8" 2' - 4" 9' - 5" HIGH ROOF FRAMING PLAN 2' - 0 7/8" 0' - 5" B6.5 B7 B8 B8.5 B9 B10 B11 CHECKED: TRP SHEET TITLE 1' - 7 1/4" B6.3 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 A4 X2 X2.3 HSS6X3X1/4 (LSH) T/STL = 32'-0" (TYP @ 8' T/PARAPET) -8 " 8.53° X1 4' -0 7/8 " S-506 H 5.00° 3 EQ SPA 3 EQ S PA RADIAL RA X3 3 HSS10X 6X1/4 ED W1 2X19 TAPER RADIAL W18X46 W1 4X 22 W1 16 HI K2 4X (S ) 22 6 D 7 RADIAL HSS10X6X1/4 CB RADIAL W18X46 W1 S-503 HI 4X2 (S 2 ) W1 4X 22 BRACE DN 4 SEE S-151 FOR LOW ROOF BELOW 2 11' - 5 1/2" NEW EXHAUST FAN TO BE INSTALLED ON EXIST MEZZ. CUT OUT SQUARE OF EXIST SLOPED ROOF ABOVE TO VENT & PROVIDE ADD'L FRAMING TO SUPPORT EDGES OF ROOF DECK (SEE ARCH & MEP FOR LOC'N). Y0.5 4' - 4" 19. 3 TAP ERE D W2 1X8 3 (S ) A6.6 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 6' - 11" MOVEABLE PARTITION BELOW. PROVIDE C8X11.5 CONT ALONG LENGTH @ T/PARTITION. HANG FROM ROOF BEAM W/ L4X4X1/4 VERT & HORIZ ANGLES @ 24" O.C. (2 SPAN COND MIN) & L4X4X1/4 KICKERS @ 4'-0" O.C. (ALT SIDES). T/S TL =3 W1 4' 8X -1 50 1" (S ) 5' - 5 1/2" 18. K-F T 11' - 1" G.C. SHALL F.V. EXIST CONDITIONS PRIOR TO DEMO OF EXIST OR FABR/INSTALLATION OF NEW CONSTRUCTION. COORD VARIATIONS W/ ARCH & EOR. 4" WY0.3 21X 55 (S) RB 0' - 7 1/2" 25 17. 20. (S ) 1 3/ 2' - 3 1/2" FOR PARAPETS GREATER THAN 2'-6" IN HEIGHT, EXTEND COLS TO T/PARAPET & PROVIDE HSS5X5X5/16 STEEL POSTS @ 5'-0" O.C. (MAX) W/ HORIZ HSS6X3X1/4 (LSH) CONT @ T/PARAPET. PROVIDE L3X3X1/4 KICKERS @ 4'-0" O.C. FROM SUPPORTING BEAM BOTT FLANGE TO TOP CHORD OF ADJACENT JOIST (OR @ EA JOIST WHERE JOISTS ARE PERPENDICULAR). W1 6X 45 K-F T 9' - 8.48 ° 16. 25 T/STL = 29' - 11 1/2" R= 12 (S) S-505 E SP A PROVIDE 1/4" WEB STIFF PL'S @ 4'-0" O.C. @ ALL ROOF EDGE BEAMS. W2 1X8 3 COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS A6.9 A6.7 2 3 EQ 15. S-505 TAPE R W21X ED 83 (S) A7 A6.8 8.0 0° PROVIDE L4X4X1/4 CONT DECK EDGE ANGLE @ PERIMETER OF EACH ROOF LEVEL. 1 SLO PE D N 1 1/2 "/FT W21 X68 (S) " 14. EXIST BLDG S10 X6X 1/4 SEE 8/S-501 FOR TYP TUBE BEAM TO COL CONN. 1' - 2" 3E QS PA 13. R = 12 W21X 101 (S) RC -8 SEE 11/S-501 FOR TYP STEEL POST-UP COL CONN. W21X7 3 (S) SP A 12. TAPERED W21X83 (S) 9' SEE 7/S-501 FOR TYP STEEL BEAM OVER COL CONN. W21X93 (S) RAD IAL HS 11. W21X55 (S) W18X35 (S) 2E Q 6 "xx kip" AT END OF BEAMS DENOTE MINIMUM UNFACTORED (ASD) REACTIONS FOR CONNECTION DESIGN. IF REACTION IS NOT SHOWN, DESIGN CONNECTION PER STRUCTURAL STEEL NOTE I ON S-001 (TYP). W18X35 (S) OWNER TAPERED W12X19 RAD W18 IAL X46 TAP ERE DW 12 X 19 "CB" DENOTES L4X4X3/8 X 4'-0" LG (MIN) COL BRACE. WELD BRACE TO COL CAP PL & TOP CHORD OF JOIST OR TOP FLANGE OF BEAM W/ 3/16" FILLET WELD x 2" LG. USE (2) ANGLES @ T-SHAPED AREAS. WELD DECK TO EA ANGLE W/ 3/4" DIA PUDDLE WELDS @ 6" OC. W18X35 (S) W1 4X 39 2 '31 2 /4" 9. TAPER END OF W18X35 PER 2/S-505 RA W1 DIAL TA 8X PE 46 RE DW 12X 19 RA DIA HS L S1 0X 6X 1/4 E DENOTES MOMENT CONNECTION. DESIGN CONNECTIONS FOR FORCES INDICATED ON PLAN AND IN ELEVATIONS. DESIGN CONENCTIONS FOR THE FOLLOWING FORCES UNLESS NOTED OTHERWISE MOMENT: 20 K-FT SHEAR: 25 K "BB" DENOTES BEAM BOTTOM FLANGE BRACE PER 5/S-501. G 5 MAXIMUM DEPTH OF PONDING AT LOWEST POINT OF ROOF SHALL NOT EXCEED 4" UNDER PEAK INTENSITY STORM 8. 10. F DENOTES STEEL BRACE (SEE DETAILS & ELEVATIONS ON S-601 & S-602). S-504 2 H PES PROJECT NUMBER: 0214062 1 BRACE DN T/STL = 28' - 10 1/2" CB 7. S-504 CB 6. S-506 CB 5. 2 4 3 DO NOT SUPPORT MULTIPLE SPRINKLER MAINS FROM THE SAME JOIST. CONTRACTOR TO PROVIDE SPRINKER DRAWINGS TO STRUCTURAL ENGINEER AND JOIST MANUFACTURER FOR REVIEW AND COORDINATION PRIOR TO JOIST FABRICATION. 2 EQ SPA I 2 S-502 2 EQ SPA 4. 1 CB SEE "WATER PIPING SUPPORT SCHEDULE" ON SHEET S-002 FOR ALL PIPING SUPPORTED FROM ROOF STRUCTURE. NOTIFY EOR IF PIPING WEIGHT IS IN EXCESS OF THOSE NOTED IN SCHEDULE. W1 4X 22 38 '95 /8" 3. 62' - 2" CB PROVIDE STANDARD HORIZONTAL BRIDGING PER SJI. SEE S-151 FOR LOW ROOF BELOW CB 2. S-502 A9 2 EQ SPA J DENOTES 22 GAUGE 1 1/2" B WIDE RIB METAL ROOF DECK. MINIMUM DECK PROPERTIES: Ip = 0.162 IN^4/FT IN = 0.175 IN^4/FT Sp = 0.183 IN^3/FT Sn = 0.189 IN^3/FT 25 K-FT 25 K-FT W18X46 2 5 S-506 W18X46 2 4 W18X46 K DENOTES 22 GAUGE 2" GALVANIZED DOVE-TAIL ACOUSTICAL STEEL ROOF DECK (BASIS OF DESIGN: 2"-22 GA VERSA-DEK S ACOUSTICAL ROOF DECK BY CSi METAL DEK GROUP). NOTE: DECK SPAN PERPENDICULAR TO GRID 'RB.' MINIMUM DECK PROPERTIES: I_D = 0.385 IN^4/FT Sp = 0.284 IN^3/FT Sn = 0.267 IN^3/FT 30 K-FT 30 K-FT W18X46 4 2 EQ SPA 1. A9.6 1' - 4 1/8" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:10:08 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" N B12 B13 B14 SHEET NO. S-152 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 N COL., BASE PL. & FTG. 1' - 4" 1' - 4" 1' - 6" 1' - 6" 1' - 6" 1' - 6" 1' - 6" 1' - 6" 2' - 0" 2' - 0" (5) #5 EA WAY T & B (6) #6 EA WAY T & B (7) #6 EA WAY T & B (8) #6 EA WAY T & B #6 @ 12" O.C. EA WAY T & B #6 @ 12" O.C. EA WAY T & B (10) #6 EA WAY T & B #6 @ 12" O.C. EA WAY T & B (15) # 6 EA WAY T & B #6 @ 12" O.C. EA WAY T & B PROVIDE NUT, WASHER, & LEVELING NUT (TYP.) Croft & Associates APPLY MASTIC TO STEEL COLUMN BELOW SLAB LEVEL TO PROTECT COLUMN FROM CORROSION PROVIDE NUT, WASHER, & LEVELING NUT (TYP.) T/SLAB T/GRADE (SEE PLAN) (SEE CIVIL) 1/2" PJF L PROVIDE NUT, WASHER, & LEVELING NUT (TYP.) T/SLAB (SEE PLAN) Structural Column Schedule Type Mark Type VAPOR RETARDER 1 3" "TYP. INTERIOR COLUMN FOOTING" SECTION SCALE: 1" = 1'-0" NOTE: DISTANCE FROM BOTT/BOLT TO TOP OF WASHER TO BE 1 1/4" MAX. NOTE: SEE 3/S-201 FOR TYPICAL CONC. PIER @ COL. BASE WHERE T/FTG. ELEV. IS BELOW (-)2'-8" SEE FTG. SCHEDULE FOR SIZE & REINF. NOTE: DISTANCE FROM BOTT/BOLT TO TOP OF WASHER TO BE 1 1/4" MAX J SEE FTG. SCHEDULE FOR FOOTING SIZE AND REINF. CLR. (SEE PLAN) 3" T/FTG. (SEE PLAN) SHRINK GROUT 1 1/2" (MIN.) NON- HSS5X5X3/8 HSS5X5X1/2 HSS6X6X1/2 HSS7X7X5/8 HSS6X0.500 HSS8.625X0.500 HSS12.750X0.500 HSS6X6X5/8 DOUBLE HSS10X6X3/8 HSS6X4X1/4 SHRINK GROUT K 2 T/FTG. 1 1/2" (MIN.) NON- C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com WWR (SEE PLAN) CL ANCHOR ROD W/ HEX HEAD NUT & PL, TOP 10" THREADED AND PROJECTED (FOR LOCATION & SIZE, SEE BASE PLATE DETAIL) EMBED OF A.R. TO BE DEPTH OF FTG MINUS 3" CLR. 4' - 0" 5' - 0" 6' - 0" 7' - 0" 6' - 0" 6' - 0" 9' - 0" 10' - 0" 12' - 0" 12' - 0" CL ANCHOR ROD W/ HEX HEAD NUT & PL, TOP 10" THREADED AND PROJECTED (FOR LOCATION & SIZE, SEE BASE PLATE DETAIL) EMBED OF A.R. TO BE DEPTH OF FTG MINUS 3" STEEL COLUMN (SEE PLAN) BASE PLATE (SEE DETAIL 4/S-201) MIN. 4' - 0" 5' - 0" 6' - 0" 7' - 0" 7' - 3" 8' - 6" 9' - 0" 9' - 0" 12' - 0" 20' - 0" NOTE: SEE 3/S-201 FOR TYPICAL CONC. PIER @ COL. BASE WHERE T/FTG. ELEV. IS BELOW (-)2'-8" Comments 0' - 3" M Length STEEL COLUMN (SEE PLAN) (FOR BASE PLATE SEE DETAIL 4/S-201) (MIN) F4 F5 F6 F7 F7.6 F8.5X6 F9 F10X9 F12 F20X12 "TYP. EXTERIOR COLUMN FOOTING" SECTION 1 S-201 PES PROJECT NUMBER: 0214062 2 S-201 SCALE: 1" = 1'-0" I OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS H CL ANCHOR ROD W/ HEX HEAD NUT & PL, TOP 10" THREADED AND PROJECTED (FOR LOCATION & SIZE, SEE BASE PLATE DETAIL) 2' - 8" STD. HOOK @ (4) CORNER BARS @ ALL PIERS STEEL BEAM (SEE PLAN) 2' - 8" G Type Mark BP-1 BP-2 BP-3 BP-4 BP-5 BP-6 BP-7 BP-8 BP-9 BP-10 SEE PLAN FOR LOCATIONS OF OFFSET PIERS @ EXT. COLS. COL., BASE PL., PIER, & FTG. 1 1/2" BASE PLATE (SEE 4/S-201) N 1' - 1" 1' - 5" 1' - 2" 2' - 2" 1' - 2" 1' - 9" 2' - 3" 1' - 9" 2' - 2" 3' - 0" B 1' - 1" 1' - 5" 1' - 2" 1' - 2" 1' - 2" 1' - 9" 2' - 3" 1' - 9" 1' - 2" 1' - 6" Column Base Plate Schedule Plate Hole Dia. (d) c e f 0' - 2" 0' - 2" 0' - 2" 0' - 1 1/4" 0' - 3" 0' - 3" 0' - 3" 0' - 1 9/16" 0' - 2" 0' - 2" 0' - 2" 0' - 1 1/4" 0' - 3" 0' - 3" 0' - 3" 0' - 1 13/16" 0' - 2" 0' - 2" 0' - 2" 0' - 1 1/4" 0' - 3" 0' - 3" 0' - 3" 0' - 1 1/4" 0' - 3 1/2" 0' - 3 1/2" 0' - 3 1/2" 0' - 1 9/16" 0' - 2" 0' - 2" 0' - 2" 0' - 1 1/4" 0' - 3" 0' - 3" 0' - 3" 0' - 1 1/4" 0' - 2" 0' - 2" 0' - 2" 0' - 1 9/16" a 0' - 2" 0' - 3" 0' - 2" 0' - 3" 0' - 2" 0' - 3" 0' - 3 1/2" 0' - 2" 0' - 3" 0' - 2" t 0' - 1" 0' - 1 3/4" 0' - 1 1/2" 0' - 1 3/4" 0' - 1 1/2" 0' - 1 3/4" 0' - 2 1/4" 0' - 1 1/4" 0' - 1 1/4" 0' - 1 1/2" Rod Diameter 0' - 1" 0' - 1 1/4" 0' - 1" 0' - 1 1/2" 0' - 1" 0' - 1" 0' - 1 1/4" 0' - 1" 0' - 1" 0' - 1 1/4" L 0' - 9" 1' - 3" 0' - 9" 1' - 3" 1' - 3" 0' - 9" 1' - 9" 0' - 9" 0' - 9" 0' - 9" P 0' - 10" 0' - 10" 0' - 10" 0' - 10" 0' - 10" 0' - 10" 0' - 10" 0' - 10" 0' - 10" 0' - 10" DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 CLR. (TYP.) e c c * "A-A" TSLAB (SEE PLAN) a d B B (8)-#8 3 S-201 MIN. WASHER THICKNESS a BP-10 t = PLATE THICKNESS 3/4" USE STANDARD WASHER 7/8" 2 1/2" 5/16" 1" 3" 3/8" 1 1/4" 3" 1/2" 1 1/2" 3 1/2" 1/2" 1 3/4" 4" 5/8" 2" 5" 3/4" 5 1/2" 7/8" 2 1/2" D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER * WELD SIZE SHALL BE: 3/16" FOR COLUMN WALL OR WEB THICKNESS < 1/2" 1/4" FOR COLUMN WALL OR WEB THICKNESS BETWEEN 1/2" & 3/4" 5/16" FOR COLUMN WALL OR WEB THICKNESS > 3/4" PROVIDE LEVELING NUTS & WASHERS, SHIM STACKS, OR LEVELING PLATE TO TEMPORARILY SUPPORT COLUMN DURING LEVELING AND GROUTING. 14116 3. WELD REQUIRED ONLY AT BRACED FRAME & MOMENT FRAME COLUMNS. SHEET TITLE 4. PROVIDE ADEQUATE PROJECTION FOR INSTALLATION OF NUT ABOVE BASE PL, 10" MIN 1. 2. (TYP.) SCALE: 1" = 1'-0" HEAVY HEX NUT AT EMBEDDED END. TACK WELD NUT TO ROD. NOTES: (TYP ) 3" CLR. L c 3" B SECTION N t = PLATE THICKNESS "A-A" 1 1/2" (MIN) NONSHRINK GROUT c a 2' - 4" (VARIES) * TYPICALS (SEE PLAN) MIN. WASHER DIMENSION T/FTG SEE NOTE 2 N T/FTG A.R. DIA. d f * CLR. (TYP.) C SEE FOUNDATION PLAN AND FTG. SCHEDULE BP-7 e * 1 1/2" FOR FOOTING SIZE AND REINFORCING NOTE 3 t = PLATE THICKNESS f P e (SEE PLAN) A . S-201 MIN. PLATE WASHER DIMENSIONS t = PLATE THICKNESS (MIN. OF 3 TIES) A. 9 A N 3" ANCHOR ROD EMBED = 18" (TYP) PLATE WASHER W/ STANDARD HOLE (SEE TABLE) N 2' - 4" #4 TIES @ 6" O.C. SHRINK GROUT T/PIER D * FILL ALL VOIDS BETWEEN ANCHOR ROD & HOLES W/ GROUT OR EPOXY PRIOR TO INSTALLING WASHER & NUT (12)-#9 (TYP @ MOM FRAME ONLY) #4 TIES REQ'D @ 3" O.C. ALONG LENGTH OF ANCHOR RODS d a E f STD. HOOK @ TOP OF CORNER BARS (TYP.) B WWR (SEE PLAN) e d 1'-0" @ INT COLS 2'-0" @ EXT COLS (UNO ON PLAN) PROVIDE NUT, WASHER, & LEVELING NUT (TYP.) f B COL. BOX-OUT (24" x 24" MIN.) F 1 1/2" MIN. NON- © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:10:20 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" Mark COL., BASE PLATE, AND FTG. 1'-0" 2" Structural Foundation Schedule Size Width Thickness Reinf. EXTERIOR FINISH (SEE ARCH.) DETAIL SCALE: 1" = 1'-0" 4 S-201 DRAWN: ABS CHECKED: TRP STEEL COLUMN BEARING SCHEDULES & DETAILS SHEET NO. S-201 2 3 4 5 6 7 8 9 10 11 12 13 SAWCUT CONTRACTION JOINT - DEPTH = 1/4 THE SLAB THICKNESS. SAWCUT SLAB WITHIN 12 HOURS OF CONC PLACEMENT N 1/8" SAWCUT 2" 14 15 16 17 18 (1)-#4 LAP SPLICE 19 FTG STEP (SEE PLAN) 3" 1 T/FTG (SEE PLAN) T/4 FOOTING (SEE PLAN) (SEE PLAN) 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com SAWCUT CONTRACTION JOINT (1)-#4 MAINTAIN SPECIFIED FOOTING DEPTH T/FTG TYPICAL FOOTING STEP WOOD BULKHEAD (REMOVE AFTER FIRST POUR) METAL OR PLASTIC KEY FORMER NAILED TO BULKHEAD (REMOVE AFTER FIRST POUR) SLAB REINF (SEE PLAN) DISCONTINUOUS @ JOINT 1 1 K 3000 PSI CONCRETE (POUR 1) TRENCH 1 NOTES: 1. SEE KEYED SECTIONS AND DETAILS FOR FOOTING DEPTH AND REINFORCING. DETAIL 4 S-301 SCALE: 1" = 1'-0" 1 DUCTILE IRON PIPE SECOND POUR FIRST POUR STEEL SLEEVE TYPICAL PIPE UNDER FOOTING DETAIL SCALE: 3/4" = 1'-0" TYPICAL FOOTING ADJACENT TO TRENCH DETAIL 1 S-301 SCALE: 1" = 1'-0" CONSTRUCTION JOINT PES PROJECT NUMBER: 0214062 DETAIL 2 S-301 WWR (SEE PLAN) D (SEE ARCH) (SEE PLAN) 3 S-301 SCALE: 1" = 1'-0" 3D I T VAPOR RETARDER (SEE ARCH) T (SEE PLAN) T/FTG (SEE PLAN) (SEE PLAN) L J Croft & Associates SLAB REINF (SEE PLAN) WALL/ COLUMN (SEE PLAN) FOOTING (POUR 2) T/FTG (SEE PLAN) T M T © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:10:26 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" FILL SAWCUT W/ JOINT FILLER TYPICAL DEPRESSED SLAB DETAIL H SCALE: 1" = 1'-0" OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 5 S-301 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER G GROUT CELLS AS SHOWN AND PLACE (1)-TYP REINF BAR (UNO) 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 PREFAB LADDER TYPE CORNER JOINT REINF (MATCH SPA OF TYP HORIZ JOINT REINF) F CONTROL JOINT PLACE (1)-TYP REINF BAR IN GROUTED CELL EACH SIDE OF CONTROL JOINT (UNLESS NOTED OTHERWISE) SEE ARCH FOR ANY JOINT FILLER REQUIREMENTS AT RATED WALLS E PREFAB LADDER TYPE TEE JOINT REINF (MATCH SPA OF TYP HORIZ JOINT REINF) GROUT CELLS AS SHOWN AND PLACE (1)-TYP REINF BAR (UNO) D C TYPICAL CMU WALL CORNER/INTERSECTION REINFORCEMNT NOTES: 1. PREFABRICATED CORNER/INTERSECTION JOINT REINFORCEMENT SHALL BE LAPPED 8" MIN WITH THE TYPICAL LADDER TYPE JOINT REINFORCEMENT & EXTEND A MINIMUM OF 30" IN EACH DIRECTION AT THE INTERSECTION B 2. SEE GENERAL NOTES FOR SPACING OF TYPICAL HORIZONTAL JOINT REINFORCEMENT (NOT SHOWN FOR CLARITY) PLAN DETAIL SCALE: 1" = 1'-0" A 6 S-301 TYPICAL CMU WALL CONTROL JOINT 1'-0" NOTES: 1. CONTROL JOINTS SHALL BE LOCATED PER ARCHITECTURAL DRAWINGS AND SHALL MATCH VENEER CONTROL JOINTS WHERE APPLICABLE 2. CONTROL JOINTS SHALL NOT BE LOCATED THROUGH BEAMS OR LINTELS, THEIR BEARING DISTANCE, OR THE REQUIRED JAMB ON EITHER SIDE OF THE OPENING 3. CONTROL JOINTS SHALL NOT BE LOCATED WITHIN A WALL DESIGNATED ON THE STRUCTURAL PLANS AS A SHEAR WALL WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD 4. HORIZONTAL JOINT REINFORCEMENT TO STOP AT EACH SIDE OF CONTROL JOINT. TYPICAL HORIZONTAL JOINT REINFORCEMENT NOT SHOWN FOR CLARITY 5. DO NOT CUT CONTINUOUS BOND BEAMS OR BOND BEAM REINFORCEMENT AT CONTROL JOINTS. PROVIDE APPEARANCE OF CONTROL JOINT IN BOND BEAM WHERE JOINT IS EXPOSED (SEE ARCH) 6. WHERE NOT EXPLICITLY NOTED OR SHOWN OTHERWISE, GC SHALL INSTALL CONTROL JOINTS AS FOLLOWS: • SPACING NOT TO EXCEED 25’-0” IN CONTINUOUS WALLS • LOCATED NOT CLOSER THAN 5’-0” AND NOT FURTHER THAN 12’-6” FROM WALL CORNERS • AT LOCATIONS WHERE WALL HEIGHT CHANGES • AT LOCATIONS WHERE WALL THICKNESS CHANGES PLAN DETAIL SCALE: 1" = 1'-0" 7 S-301 BOND BEAM REINF (TYP) MATCH BOND BEAM REINF 1' - 4" D C No. DRILL HOLE THRU BOTT OF DEP WEB BLOCK FOR DOWEL TO PASS THRU SCALE: 1" = 1'-0" 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 "TYP. STEP IN MASONRY BOND BEAM" DETAIL 1'-0" DRAWN: ABS CHECKED: TRP SHEET TITLE 8 S-301 FOUNDATION SECTIONS & DETAILS SHEET NO. S-301 3" 1 3 4 8 9 10 11 12 13 14 15 16 17 LAP SPLICE 3/4" 1/2" LAP SPLICE 3/4" CHAMFER (TYP @ ALL EXPOSED CORNERS) 18 19 PLACE HALF THE NUMBER OF INTERRUPTED BARS ON EA SIDE OF OPNG @ 3" OC @ SCHED LENGTH. SCHEDULED REINF INTERRUPTED BY OPNG A MINIMUM OF: (1)-#5 x L WHEN OPENING IS LESS THAN 12" (2)-#5 x L WHEN OPENING IS GREATER THAN 12" (TYP EA LAYER OF REINF) SCHEDULED REINF JOINT DISCONTINUE 50% OF HORIZ REINF @ JOINT (TYP) M Croft & Associates (2)-#5 X 8'-0" LG T&B & EA SIDE WALL OPNG (SEE PLAN) 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com 0" 0" HORIZ REINF W/ STD 90° HOOK SQUARE OR CIRCULAR OPNG TYPICAL WALL CONTROL JOINT 12 "( M AX ) L ALT HOOK DIRECTION NOTES: 1. CONTROL JOINT SPACING NOT TO EXCEED 25'-0" MAXIMUM & 5'-0" MINIMUM FROM CORNERS. 3/4" 3/4" K (1)-#5 x 4'-0" LG WHEN OPENING IS LESS THAN 12" (2)-#5 x 4'-0" LG WHEN OPENING IS GREATER THAN 12" (TYP TOP & BOT) 1/2" (1)-#5 X 6'-0" LG T&B @ EA CORNER JOINT J WATER STOP (SEE ARCH) TYPICAL REINFORCING AT WALL CORNERS & INTERSECTIONS DETAIL I ELEVATION 2 S-302 SCALE: 1" = 1'-0" LAP SPLICE TYPICAL REINFORCING AT WALL OPENING TYPICAL REINFORCING AT WALL OPENINGS NOTES: PES PROJECT NUMBER: 0214062 1. L = OPENING SIZE + (2) X DEVELOPMENT LENGTH. DETAIL 3 S-302 SCALE: 1" = 1'-0" 4 S-302 SCALE: 1" = 1'-0" OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS TYPICAL WALL CONSTRUCTION JOINT NOTES: CANTILEVER CMU SCHEDULE (INT. NON-LOAD BEARING) 1 S-302 G EQUAL TREADS LAP SPLICE #4 X CONT @ NOSING (TYP) CJ @ EA. SIDE (U.N.O.) C "H" (SEE SCHED) 1' - 4" CJ @ EA. SIDE (U.N.O.) WWR (SEE PLAN) CJ @ EA. SIDE (U.N.O.) CJ @ EA. SIDE (U.N.O.) T/SLAB T/SLAB (SEE PLAN) 1' - 0" (3) - #4 X CONT VAPOR RETARDER B SEE NOTE 2 TYPICAL STAIR ON GRADE 5 S-302 (SEE PLAN) 8" 2x4 KEY CONT. "A" BARS SEE NOTE 2 1' - 0" "A" BARS "CMU PART. W/ DEPR. SLAB" DETAIL SCALE: 1" = 1'-0" 6 S-302 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE 14116 "B" BARS "TYP. CMU PART." D C No. PROJECT NUMBER VAPOR RETARDER 1' - 6" SCALE: 1" = 1'-0" CMU PARTITION (SEE ARCH.) VERT. REINF. (SEE SCHED.) SEE PLAN WWR (SEE PLAN) SECTION (SEE ARCH.) DEPR. WEB BOND BEAM (SEE SCHED.) CMU PARTITION (SEE ARCH.) VERT. REINF. (SEE SCHED.) (SEE PLAN) A T/CMU (SEE ARCH.) #4 @ 12" OC 10" 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 DEPR. WEB BOND BEAM (SEE SCHED.) #4 X CONT @ 12" OC T/SLAB DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER T/CMU 1/2" PJF D #4 @ 12" O.C. #4 @ 12" O.C. #4 @ 12" O.C. #4 @ 12" O.C. #4 @ 12" O.C. #4 @ 12" O.C. #4 @ 12" O.C. #5 @ 12" O.C. #5 @ 12" O.C. #4 @ 12" O.C. #5 @ 12" O.C. (MIN) (SEE ARCH) 6" ) IN (M EQUAL RISERS E "B" BARS "H" (SEE SCHED) (SEE PLAN) SEE PLAN T/LANDING DEPR. WEB "A" BARS BOND BEAM * ≤ 10'-0" #4 @ 32" O.C. (1)-#4 (3)-#4 12'-0" #4 @ 24" O.C. (1)-#4 (3)-#4 14'-0" #4 @ 8" O.C. (1)-#4 (3)-#4 16'-0" #5 @ 16" O.C. (2)-#4 (3)-#4 18'-0" #5 @ 8" O.C. (2)-#4 (3)-#4 ≤10'-0" #4 @ 40" O.C. (2)-#4 (3)-#4 14'-0" #5 @ 32" O.C. (2)-#4 (3)-#4 20'-0" #5 @ 24" O.C. (2)-#5 (3)-#5 24'-0" (2)-#5 @ 24" O.C. (2)-#5 (3)-#5 14'-0" #5 @ 40" O.C. (2)-#4 (3)-#4 24'-0" #5 @ 40" O.C. (2)-#5 (3)-#5 NOTES: 1. DETAIL APPLIES @ INT NON-LOAD BEARING CMU PARTITIONS ON SLABS ON GRADE AND ON ELEVATED SLABS THAT STOP JUST ABOVE CEILING OR BELOW. 2. WHERE CMU WALL BEARS ON ELEVATED SLAB, VERT REINF TO BE DRILLED & EPOXIED 3" INTO SLAB (SEE POST-INSTALLED ANCHOR NOTES ON S-0.01 FOR REQ'D EPOXY). SLAB REINF, EA WAY (SEE PLAN) (SEE ARCH) VERT. REINF. 1' - 0" F "H" SEE PLAN SCALE: 1" = 1'-0" CMU SIZE 6" 6" 6" 6" 6" 8" 8" 8" 8" 12" 12" SEE ARCH. DETAIL (MIN) H 1. CONTROL JOINT SPACING NOT TO EXCEED 100'-0" MAXIMUM & 5'-0" MINIMUM FROM CORNERS. R CL © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 1" 1/2" 0 7 3" 12/19/2014 5:10:33 PM 6 CORNER BARS (MATCH SIZE & SPACING OF HORIZ BARS) 3" C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 5 3/4" 2" N 2 DRAWN: ABS CHECKED: TRP SHEET TITLE FOUNDATION SECTIONS & DETAILS SHEET NO. S-302 3" 1 2 3 4 5 6 1" (CLR) N 7 2" (CLR) 8 9 10 11 12 13 14 15 16 #6 @ 12" O.C. 17 18 19 1' - 3" 2" #5 @ 12" O.C. #6 @ 12" O.C. DRAINAGE MAT M DOWELS TO MATCH VERT. WALL REBAR IN SIZE & SPACING (USE 2'-0" HOOK INTO FTG.) 1/2" PJF G.C. NOTE: WALL MUST BE BACKFILLED BEFORE ELEVATED SLAB FRAMING IS ATTACHED TO WALL (2)-#4 CONT Croft & Associates SEE PLAN FOR FTG REINF (TYP) 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com T/FTG (SEE PLAN) 7 1/2" #5 @ 20" OC 2x4 KEY (TYP) WWR (SEE PLAN) 2' - 6" 4" PERF. PVC DRAIN PIPE IN GRAVEL FILL (DRAIN TO DAYLIGHTSEE CIVIL) T/SLAB L (SEE PLAN) #5 @ 12" O.C. T&B VAPOR RETARDER SEE PLAN FOR FTG REINF TO BE DOWELED AND EPOXIED INTO CONCRETE FOUNDATION WALL (EMBED 7 1/2" MIN) #6 @ 10" O.C. #6 @ 10" O.C. CONC FND WALL (SEE PLAN) T/FTG. (SEE PLAN) K 3" CLR 1' - 6" (4)-#5 CONT. SECTION J 3" CLR #6 @ 10" O.C. SCALE: 1" = 1'-0" 2 S-303 PES PROJECT NUMBER: 0214062 2' - 6" 1' - 0" NOTE: SEE 1/S-302 & 2/S-302 FOR TYP CONC WALL JOINTS & CORNERS. SEE 3 & 4/S-302 FOR TYP REINF @ WALL PENETRATIONS. I 3" (CLR) OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 1' - 6" 2' - 7" 1' - 2" 2' - 6" H 6' - 3" SECTION 1 S-303 SCALE: 1" = 1'-0" G DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 F COL B0.5 STAIR STRINGER 3" 2" EJ INT FINISH (SEE ARCH) EXT F/STUD E/SLAB INT FINISH (SEE ARCH) 4" 8" METAL STUDS (DESIGN PER SPEC CRITERIA) EXIST 8" CONC WALL (GC FV) D 30" 36" 18" 3/4" EXP ANCHOR (EMBED = 4 3/4") AT EACH STRINGER #5 @ 24" OC 19" EXT FINISH (SEE ARCH) #5 @ 24" OC 18" EXIST ELEV CONC SLAB & FLOOR JOIST (SEE PLAN - GC FV) L3X3 MIN (BY STAIR FABRICATOR) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) 10" 2' - 6" WWR (SEE PLAN) WWR (SEE PLAN) SLAB REINF (SEE PLAN) 3' - 0" T/SLAB (SEE PLAN) T/SIDEWALK (SEE CIVIL) 2 1/2" PJF 2 1 1 B VAPOR RETARDER (SEE ARCH) 2' - 0" T/SLAB T/SLAB (SEE PLAN) (SEE PLAN) 2' - 0" C #4 X 4'-0" LG @ 36" OC 1' - 4" E 2' - 0" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:10:39 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" MAIN LEVEL COL FTG (SEE PLAN) VAPOR RETARDER (SEE ARCH) 1' - 6" (2)-#4 X CONT (TOP & BOT) VAPOR RETARDER (SEE ARCH) 1' - 4" (4)-#4 CONT (4)-#4 CONT TYPICAL THICKENED SLAB AT STAIR D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 DRAWN: ABS CHECKED: TRP SHEET TITLE SECTION SCALE: 1" = 1'-0" A 3 S-303 SECTION SCALE: 1" = 1'-0" 4 S-303 SECTION SCALE: 1" = 1'-0" 5 S-303 FOUNDATION SECTIONS & DETAILS SHEET NO. S-303 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 N 2" #5 @ 24" OC #5 CONT WWR (SEE PLAN) 1' - 0" 2 WWR (SEE PLAN) 1 #5 @ 12" O.C. 2' - 6" T/SLAB L 2x4 KEY MAX. WALL HEIGHT 6'-0" K #4 X CONT @ NOSING (TYP) #5 @ 12" O.C. 2 1 6" #4 STAIR REINF DRILLED & EPOXIED 6" INTO CONC WALL VAPOR RETARDER (SEE ARCH) N MI EXIST CONC WALL CUT @ NEW DOOR OPNG (SEE ARCH) (SEE PLAN) DRAINAGE MAT (SEE ARCH) CONC STAIR J #5 CONT 2x4 KEY " VAPOR RETARDER (SEE ARCH) DOWELS TO MATCH VERT. WALL REBAR IN SIZE & SPACING (USE 2'-0" HOOK INTO FTG.) #5 @ 12" O.C. DRAINAGE (SEE ARCH) #4 x CONT @ 12" OC #5 @ 24" OC 2" EJ 2x4 KEY WWR (SEE PLAN) 2' - 6" EXIST CONC SLAB WATERSTOP (SEE ARCH) T/SLAB #5 @ 12" O.C. T&B #6 @ 10" O.C. #4@12" OC DRILLED & EPOXIED 6" INTO CONC WALL #6 @ 10" O.C. PES PROJECT NUMBER: 0214062 #5 @ 12" O.C. T&B T/FTG T/FTG (SEE PLAN) (SEE PLAN) 1' - 6" 1' - 0" 2x4 KEY #5 @ 12" O.C. (GC FV) I #4 X CONT @ 12" OC #6 @ 10" O.C. (SEE PLAN) H VAPOR RETARDER (SEE ARCH) 3" TYP 3" TYP (GC FV) 1 1' - 6" 2 1' - 0" (3)-#4 CONT 1' - 5" 1' - 5" EXIST CONC FTG (GC FV) 2' - 0" 1' - 0" (GC FV) (GC FV) SECTION G SCALE: 1" = 1'-0" 1' - 0" 1' - 0" OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 2' - 1" 3" TYP 2' - 1" 3" TYP 4' - 6" 4' - 6" 1 S-304 SECTION USE OF THIS DETAIL SHALL BE RESTRICTED TO A MAX WALL HEIGHT OF 6'-0". IF WALL HEIGHT EXCEEDS 6'-0", REFER TO DETAIL 1/S-303 SECTION SCALE: 1" = 1'-0" DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 3 S-304 SCALE: 1" = 1'-0" 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 2 S-304 COL F COL, BASE PL & FND @ BASE OF COL 1/2" PJF COL 2' - 6" WWR (SEE PLAN) 80 .0 0° E 10.00° #5 @ 24" OC WINDOW (SEE ARCH) 4" INT FINISH (SEE ARCH) EXT F/STUD T/SIDEWALK 6" METAL STUDS (DESIGN PER SPEC CRITERIA) (SEE CIVIL) (SEE PLAN) GROUT CAVITY SOLID BELOW GRADE T/SIDEWALK T/SLAB (SEE CIVIL) 1/2" PJF VAPOR RETARDER (SEE ARCH) PROVIDE NUT, WASHER, & LEVELING NUT (TYP.) 2 (4)-#4 CONT 1 (SEE PLAN) T/FTG. C 2 1/2" PJF 1' - 4" 2x4 KEY 1 T/FTG (SEE PLAN) VAPOR RETARDER (SEE ARCH) D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 3" FOUNDATION SECTIONS & DETAILS #5 @ 24" OC SCALE: 1" = 1'-0" CHECKED: TRP SHEET TITLE NOTE: DISTANCE FROM BOTT/BOLT TO TOP OF WASHER TO BE 1 1/4" MAX 4 S-304 DRAWN: ABS SEE FTG SCHEDULE FOR SIZE & REINF (3)-#5 CONT SECTION CLR. 14116 B A (SEE PLAN) SHRINK GROUT WWR (SEE PLAN) 2' - 6" 1 1/2" (MIN.) NON- 2' - 0" D T/SLAB #5 @ 24" OC EXT VENEER (SEE ARCH) 1' - 0" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com #5 @ 24" OC -3 12/19/2014 5:10:47 PM Croft & Associates (SEE PLAN) M 0' C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" T/SLAB SECTION SCALE: 1" = 1'-0" 6 S-304 SHEET NO. S-304 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 BEAM (UNO) SEE NOTES N 6" MIN 6" MIN 2" 6" MIN Croft & Associates A 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com POUR 1 CAMBER AT MIDPOINT (SEE PLAN) #4 x 4'-0" @ 24" OC CENTERED ON KEYED CONSTRUCTION JOINT DISTRIBUTED SHEAR STUD PLACEMENT NOTES: J 3. I b. IF THERE ARE CONNECTORS REMAINING, ASSIGN ONE CONNECTOR TO EVERY OTHER RIB WITHOUT A CONNECTOR STARTING AT EACH END OF THE BEAM. c. IF THERE ARE STILL CONNECTORS REMAINING, ASSIGN ONE CONNECTOR TO EACH RIB WITHOUT A CONNECTOR, AGAIN STARTING AT EACH END OF THE BEAM. d. IF NUMBER OF CONNECTORS EXCEEDS NUMBER OF RIBS, ASSIGN ONE CONNECTOR TO EACH RIB. ASSIGN SECOND CONNECTOR TO EACH RIB STARTING AT EACH END OF BEAM UNTIL ALL CONNECTORS ARE USED. LOCATE EACH ROW 1 1/2" FROM CENTER OF BEAM WEB (3" GAUGE). WELD CONNECTORS AFTER ASSIGNING IS COMPLETE. A-A POUR 2 POUR 1 #4 x 4'-0" @ 24" OC CENTERED ON KEYED CONSTRUCTION JOINT FOR BEAMS PARALLEL TO DECK SPAN: CONSTRUCTION JOINT B EQ 2. EQUALLY SPACE CONNECTORS IN ONE ROW ALONG BEAM AT A MAXIMUM SPACING OF 24" OC. NOTIFY ENGINEER IF THERE ARE INSUFFICIENT CONNECTORS TO SPACE AT 24" OC ALONG THE BEAM. POUR 2 B EQ a. K CONSTRUCTION JOINT FOR BEAMS PERPENDICULAR TO DECK SPAN: GIRDER SPAN 1. GIRDER SPAN L B-B a. EQUALLY SPACE TOTAL QUANTITY OF CONNECTORS IN ONE ROW ALONG BEAM. IF QUANTITY OF CONNECTORS EXCEEDS THE MINIMUM SPACING IN NOTE b BELOW, INSTALL CONNECTORS IN TWO ROWS ALONG BEAM. b. MINIMUM CONNECTOR SPACING ALONG BEAM IS 4 1/2" OC (6x STUD DIAMETER). c. FOR ONE ROW OF CONNECTORS, LOCATE CONNECTORS OVER BEAM WEB. FOR TWO ROWS OF CONNECTORS, LOCATE EACH ROW 1 1/2" FROM CENTER OF BEAM WEB (3" GAUGE). PES PROJECT NUMBER: 0214062 SEE COMPOSITE FLOOR SYSTEM NOTES AND FRAMING PLAN FOR STUD SIZE, LENGTH AND QUANTITY. DETAIL SCALE: 1" = 1'-0" 4' - 0" 1 S-401 BEAM SPAN OWNER BEAM SPAN COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS COMPOSITE FRAMING CONSTRUCTION JOINT LOCATION DETAIL H SCALE: 1/2" = 1'-0" 2 S-401 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER G 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 F 1'-0" MIN 2'-0" MAX E BEAM NOT TO EXCEED 9" (SEE ARCH) WELDED HCA (SEE PLANS AND NOTES FOR QTY AND SPACING) WELDED HCA (SEE PLANS & NOTES) (1)-#4 @ EA CORNER (1)-#6 EA SIDE OF OPNG ON 3/4" CHAIR IN B/ DECK RIB D 2'-0" MAX WWR (SEE PLAN) T/SLAB WWR (SEE PLAN) DECK RIBS (TYP) (SEE PLAN FOR DECK TYPE) 3-12 CONC SLAB ON COMPOSITE STL FLOOR DECK (SEE PLAN). DECK TURNED 90° @ SIM CONDITION. CONC SLAB ON COMPOSITE STL FLOOR DECK (SEE PLAN). DECK TURNED 90° @ SIM CONDITION. BETWEEN EDGE/OPNG (SEE PLAN) 9" DIA MAX OPNG. SHORE DECK TO SUPPORT CONC WEIGHT AND CONST LOADS IF DECK IS CUT PRIOR TO CONC PLACEMENT. 6" MIN 3/16 DECK RIBS (TYP) (SEE PLAN FOR DECK TYPE) BEAM OMIT DECK AT OPNG PROVIDE LG CLOSURE ANGLE. T/SLAB (SEE PLAN) (2)-#6 CONT BETWEEN BMS ON 3/4" CHAIR IN B/ DECK RIB BENT PL 1/4"X5 1/2"XL X CONT (L = EOS TO BM CL MINUS 1/2") (1)-#4 CONT BETWEEN BEAMS ON 3/4" CHAIR IN B/ DECK RIB EA SIDE OF OPNG C STL BM (SEE PLAN) STL BEAM (SEE PLAN) B TYP COMPOSITE STEEL BEAM DETAIL SCALE: 1" = 1'-0" 3 S-401 EDGE OF SLAB DETAIL AT INTERIOR CONDITIONS SECTION SCALE: 1" = 1'-0" 4 S-401 BEAM © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. A M BEAM 12/19/2014 5:10:52 PM SEE NOTES BEAM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" SEE NOTES MULTIPLE SLEEVES IN SINGLE OPENING 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE ISOLATED OPENINGS NOTES: NOTES: 1. REINFORCING SHALL EXTEND 2'-0" MINIMUM PAST EACH SIDE OF OPENING. 1. REINFORCING SHALL EXTEND 2'-0" MINIMUM PAST EACH SIDE OF OPENING. PROJECT NUMBER 14116 DRAWN: ABS 2. ALL OPENINGS TO BE REVIEWED AND APPROVED BY EOR. ADDITIONAL FRAMING MAY BE REQUIRED. CHECKED: TRP SHEET TITLE COMPOSITE SLAB PIPE PENETRATION A D C No. DETAIL SCALE: 1" = 1'-0" 5 S-401 FLOOR FRAMING SECTIONS & DETAILS SHEET NO. S-401 3" 1 2 3 4 5 6 7 8 9 N CL ANCHOR ROD W/ HEX HEAD NUT & PL, TOP 10" THREADED AND PROJECTED (FOR LOCATION & SIZE, SEE BASE PLATE DETAIL) 12 13 14 15 16 17 STEEL COLUMN (SEE PLAN) L CONC. WALL (BEYOND) COL. BOX-OUT (24" x 24" MIN.) #4 CONT PROVIDE NUT, WASHER, & LEVELING NUT (TYP.) CONC SLAB ON COMPOSITE METAL DECK (SEE PLAN) 5/16" STIFF PL (BOTH SIDES) #6 @ 12" OC CONC SLAB ON COMPOSITE FLOOR DECK (SEE PLAN) WWR (SEE PLAN) WWR (SEE PLAN) T/SLAB 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com G.C. NOTE: WALL MUST BE BACKFILLED BEFORE ELEVATED SLAB FRAMING IS ATTACHED TO WALL 5 1/2"x4 1/2"x1/4 BENT PL (LLV) CONT BASE PLATE (SEE 11/S-201) BLOCK OUT FOR COL./BM. CONNECTION (GROUT SOLID AFTER FRAMING IS INSTALLED) 19 Croft & Associates 3/16 CL. HEADED BOLT TOP 10" THREADED & PROJECTED (FOR LOCATION & SIZE, SEE BASE PLATE DETAIL) 18 STEEL BEAM (SEE PLAN) COLUMN WWR (SEE PLAN) 1'-0". 3/16 (SEE PLAN) (SEE PLAN) 3" 2" 6" (MIN) T/CONC LEDGE= (VARIES) (SEE PLAN) A . S-201 1/2" DIA x 4" LG HEADED STUDS @ 12" OC BEAM BRG (SEE PLAN) STEEL BEAM (SEE PLAN) PES PROJECT NUMBER: 0214062 COL BRG 3" PL 3/8"x12"x 8" W/ (4)-1/2" DIA x 5" LG H.S. HEADED STUDS @ EA BM #7 @ 12" OC T/FTG ANCHOR ROD EMBED = 18" (TYP) INSTALL BEAM IN 1'-6" WIDE WALL POCKET (GROUT POCKET SOLID AFTER BEAM INSTALLED) #8 @ 8" OC #5 @ 12" OC (SEE PLAN) CONC WALL SEE 4/S-201 FOR T/WALL BASE PLATE INFO. CONC. WALL (SEE 1/S-303 FOR REINF) (SEE 2/S-402 FOR WALL REINF @ COL BRG) (+)10'-6 1/2" CONC WALL ANCHOR ROD EMBED = 18" (TYP) DO NOT CONTINUE HORIZ BARS THROUGH COL BOX-OUT T/WALL VAPOR RETARDER A. 9 COL. BRG. I SHRINK GROUT STEEL BEAM (SEE PLAN) #4 TIES REQ'D @ 3" O.C. ALONG LENGTH OF ANCHOR RODS #4 TIES @ 6" O.C. J T/SLAB (SEE PLAN) T/PIER 1 1/2" MIN. NON- K BEARING ON BOXOUTS IN WALLS) TSLAB 1'-6" WIDE (FOR COLUMNS OWNER (SEE PLAN) STEEL COLUMN BEARING (BEYOND) (SEE PLAN) (SEE 1/S-402 FOR COL & BOXOUT (FULL WALL THICKNESS) 1' - 2" STD. HOOK @ (4) CORNER BARS @ ALL PIERS 0' - 1 1/2" CLR FOR FOOTING SIZE AND REINFORCING SECTION 1 S-402 SCALE: 1" = 1'-0" 2 S-402 SCALE: 1" = 1'-0" 3 S-402 SCALE: 1" = 1'-0" (SEE PLAN) DETAIL SEE FOUNDATION PLAN AND FTG. SCHEDULE SECTION DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER G STD. HOOK @ TOP OF CORNER BARS (TYP.) (12) #6 "A-A" F 5 1/2"x4 1/2"x1/4" BENT PL (LLV) CONT (TYP); 7 1/2"x4 1/2"x1/4" BENT PL (LLV) CONT (@ DEPRESSED SLAB SEE PLAN FOR LOC'N) COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 1' - 6" "TYP. COL. BRG. AT CONC. WALL" CONC WALL (SEE PLAN) 2' - 4" (TYP.) H 3" CLR. CONTINUE WALL REFIN THROUGH CONC PIER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 PL 3/8"x5"x CONT W/ 1/2" DIA x 5" LG H.S. HEADED STUDS @ 24" OC #4 CONT ORDER OF CONSTRUCTION FOR NEW OPENINGS IN EXISTING LOAD BEARING WALLS: CONC SLAB ON COMPOSITE FLOOR DECK (SEE PLAN) #6 @ 12" OC WWR (SEE PLAN) WWR (SEE PLAN) E T/SLAB G.C. NOTE: WALL MUST BE BACKFILLED BEFORE ELEVATED SLAB FRAMING IS ATTACHED TO WALL 6 (SEE PLAN) S-402 T/WALL HEADER SCHEDULE 1. INSTALL HORIZONTAL CHANNEL (SECTIONS 5/S-402 & 6/S-402), COMPLETING ALL WELDS AND TIGHTENING ALL THRU-BOLTS. 4" 8" 4" 2. CUT OUT NEW OPENING IN EXISTING WALL FLUSH WITH BOTTOM OF HEADER CHANNEL. CHANNEL SIZE LOCATION C12X20.7 TYP ALL LOCN’S (UNO) 3. INSTALL HEADER PLATE AT BOTTOM OF HEADER CHANNELS (SEE 6/S-402). 4" E/OPNG 8" 4" (+)10'-6 1/2" (TYP) VAPOR RETARDER D STEEL CHANNEL (SEE SCHED) X LENGTH OF OPNG + 8” BRG EA END W/ (2)-1” DIA THRUBOLTS @ 12” OC (TYPSTAGGERED) T/CONC LEDGE= 1/2" DIA x 4" LG HEADED STUDS @ 12" OC COL BRG C (SEE 1/S-402) SEE 3/S-402 FOR TYP STEEL BEAM TO CONCRETE WALL CONN (CONNECT BEAM TO COLUMN AT LOCATIONS WHERE BEAM INTERSECTS COL - TYP) SEE 1/S-303 SEE 1/S-303 1/4 2-6 1/4 2-6 D C No. #4 @ 12" OC 2" (CLR) 1" (CLR) 6" B 8" SCALE: 1" = 1'-0" "W" STEEL COLUMN BEARING (BEYOND) (SEE PLAN) (SEE 1/S-402 FOR COL & BOXOUT (FULL WALL THICKNESS) 4 S-402 1' - 4" 12" (MIN) (TYP) 1' - 4" OPNG SEE 2/S-402 FOR ADD'L REINF REQ'D @ COL BRG LOCATIONS ON CONC WALL 1' - 2" SECTION A STEEL BEAM (SEE PLAN) 2" (CLR) #6 @ 12" OC (EXTEND 3'-0" DOWN PAST LEDGE) 4" BEAM BRG (SEE PLAN) EXIST WALL (GC FV) 4" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 2" 1" 1/2" 0 12/19/2014 5:11:00 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 11 SEE PLAN FOR LOCATIONS OF OFFSET PIERS @ EXT. COLS. COL., BASE PL., PIER, & FTG. M 10 (MIN) 4 ANCHORS (SPACED AS SHOWN) PL 1/2” THICK X “W” + 2” WIDE X LENGTH OF OPNG GC RESPONSIBLE FOR SHORING EXISTING WALL IN ORDER TO INSTALL NEW HEADER. NO CONSTRUCTION LOADS OR LIVE LOADS TO BE PLACED ON STRUCTURE ABOVE HEADER PRIOR TO BOTTOM PLATE INSTALLATION. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 DRAWN: ABS CHECKED: TRP SHEET TITLE SECTION SCALE: 1" = 1'-0" 5 S-402 SECTION SCALE: 1" = 1'-0" 6 S-402 FLOOR FRAMING SECTIONS & DETAILS SHEET NO. S-402 3" 1 2 3 4 5 6 8 9 10 11 12 13 14 15 16 17 18 19 2" EJ N BENT PL 1/4" X 5 1/2" X 4" (LLV) CONT CONC SLAB ON COMPOSITE FLOOR DECK (SEE PLAN) DOORWAY (SEE ARCH) 2" 7 WWR (SEE PLAN) 3/16 3-12 (SEE PLAN) EXIST CONC SLAB T/STEEL M L4X4X3/8" X 8" LG (NS & FS) CONC SLAB ON METAL FLOOR DECK (SEE PLAN) (SEE PLAN) 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com STEEL TUBE (SEE PLAN) T/EXIST SLAB WWR (SEE PLAN) Croft & Associates (FIELD VERIFY) T/STEEL = T/SLAB BOT/SLAB (SEE PLAN) EXIST CONC WALL CUT @ NEW OPNG L STEEL EMBED PL 3/8" X 6" CONT W/ 1/2" DIA X 5" LG HS STUDS @ 24" OC STEEL BEAM (SEE PLAN) 1/4 (2) 3/4" HILTI KWIK BOLT TZ EXP ANCHORS X 6" LG (2 EA SIDE) CONC BEAM W/ (3)-#6 EA FACE & #4 TIES @ 6" OC EXIST CONC BEAM K STEEL CHANNEL (TYP - SEE PLAN) EXIST CONC JOIST DOORWAY (SEE ARCH) SECTION J SECTION 1 S-403 SCALE: 1" = 1'-0" SECTION 2 S-403 SCALE: 1" = 1'-0" SCALE: 1" = 1'-0" 3 S-403 PES PROJECT NUMBER: 0214062 B0.5 3 5/8” METAL STUDS (DESIGN PER SPEC CRITERIA) I 2" EJ INT FINISH (SEE ARCH) 4" OWNER 8" METAL STUDS (DESIGN PER SPEC CRITERIA) 3 5/8” METAL STUDS (DESIGN PER SPEC CRITERIA) EXIST CONC BEAM (GC FV) EXIST CONC SLAB & JOIST EXIST CONC JOISTS & SLAB SHALL BE DEMOLISHED WITHIN NEW STAIR OPNG TO EXTENTS SHOWN COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 36" #5 @ 24" OC 11" 18" H STEEL CHANNEL (SEE PLAN) W/ 3/4” EXP ANCHORS @ 24” OC STAGGERED (TYP BOTH SIDES) (EMBED 6” INTO CONC) WWR (SEE PLAN) 6" 3' - 0" T/SLAB (SEE PLAN) #4 CONT CONC SLAB ON METAL FLOOR DECK (SEE PLAN) #5 @ 24” OC DRILLED & EPOXIED INTO CONC (8” EMBED INTO CONC) WWR (SEE PLAN) T/SLAB= G 2 1' - 0" 1 (GC FV) T/EXIST SLAB (GC FV) 2' - 0" EXIST CONC BEAM EXIST CONC BEAM & SLAB (GC FV) STEEL CHANNEL (SEE PLAN) F 3 5/8” METAL STUDS (DESIGN PER SPEC CRITERIA) EXIST CONC STAIR (GC FV) EXIST 8” CMU WALL (GC FV) 4" NEW STAIR OPNG (SEE ARCH) (STEEL STAIR BY STAIR MANUF) T/STEEL= (4)-#4 CONT B/EXIST CONC JOIST MINUS 7” SECTION STEEL BEAM (SEE PLAN) X LENGTH OF NEW STAIR OPNG + 48” (EXTEND 24” PAST E/OPNG BOTH SIDES) 8" SCALE: 1" = 1'-0" 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 L6X6X3/8 X LENGTH OF BEAM W/ 5/8” DIA EPOXY ANCHORS @ 24” OC (SPACE @ 8” OC @ 2’-0” LENGTHS EA END OF STAIR OPNG) (EMBED 5 5/8” INTO EXIST CONC WALL) (TOP & BOTT) (GC FV) SECTION 4 S-403 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER GC SHALL SHORE EXIST CONC WALL UNTIL STEEL TUBE BEAM HAS BEEN INSTALLED. EXIST 8” CMU WALL (GC FV) E DEMO EXIST LANDING & STAIRS BELOW 1' - 0" VAPOR RETARDER (SEE ARCH) 1' - 4" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:11:07 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" T/SLAB SCALE: 1" = 1'-0" 5 S-403 D EXIST 8” CMU WALL (GC FV) C 5" EXIST CONC SLAB (GC FV) DEMO EXIST CONC SLAB & JOISTS WITHIN STAIR OPNG (sEE PLAN & ARCH) (MIN) D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 B DRAWN: ABS EXIST CONC DOUBLE JOIST (GC FV) A SECTION SCALE: 1" = 1'-0" NEW STAIR OPNG 6 S-403 CHECKED: TRP SHEET TITLE FLOOR FRAMING SECTIONS & DETAILS SHEET NO. S-403 3" 1 2 SPAN ANGLE SIZE UP TO 4'-0" 4'-1" TO 6'-0" L3X3X3/16 L4X3X1/4 (LLV) 6'-1" TO 8'-0" 8'-1" TO 10'-0" L5X3X1/4 (LLV) L6X4X5/16 (LLV) 4 5 6 7 8 9 10 11 12 13 14 15 16 BM 17 18 19 3/16 1/8 STL ROOF DECK (SEE PLAN) M 1/8 TYP 1/8 Croft & Associates L2 1/2X2 1/2X1/4 X CONT STEEL JOISTS (SEE PLAN) (TYP.) 3/16 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com 3/16 2-12 OPENING L4x4x1/4 BETWEEN JOISTS 300# LOAD (MAX) L L3X3X1/4 EA SIDE @ JST GDR L2x2X1/4 EA SIDE @ K-JST L2 1/2X2 1/2X1/4 EA SIDE @ LH-JST FOR SIZE AND LOCATION OF REQUIRED ROOF OPENINGS OR HVAC CURB SUPPORT, SEE MECHANICAL DRAWINGS AND/OR HVAC MANUFACTURER. EXTEND FRAME TO SUPPORT ALL SIDES OF OPENING OR HVAC CURB. MAY REQUIRE ADDITIONAL FRAME IN ADJACENT JOIST BAYS. K STL BEAM (SEE PLAN) STL JOIST (SEE PLAN) STEEL BEAM (SEE PLAN) W/3/8" STIFFENER PL AT BOT. FLANGE BRACE LOCATION TYPICAL WHERE DECK CHANGES DIRECTIONS STEEL ANGLES (SEE TABLE) NOTE: COPE VERTICAL LEG OF BEARING ANGLE 3" (TYP) JOIST BRIDGING (SEE PLAN) SECTION SCALE: 1" = 1'-0" 3 S-501 (TYP.) TYPICAL ROOF OPENING SUPPORT FRAMING 3/16 P = #.#K SERVICE (TYP) NOTES: J 1. PROVIDE SIMILAR FRAMING AT ROOF DRAINS. 2. WELD/CONNECT DECK TO ALL FRAMING AT 6" OC MAXIMUM SPACING. COORDINATE WITH ENGINEER FOR SPECIAL DETAILS REQUIRED TO CONNECT ANGLES TO EXISTING DECK IN AN INSTALLATION OF NEW UNIT ON EXISTING ROOF FRAMING. 3. I 4. TYP WHEN JOIST BRIDGING CONFLICTS WITH ROOF OPENING FRAMES, STOP BRIDGING AT EACH SIDE OF OPENING, PROVIDE CROSS BRIDGING AT LAST BRIDGING SPACE EACH SIDE OF OPENING AND CONNECT ENDS OF BRIDGING TO OPENING FRAMING. ADD ADDITIONAL BRIDGING AND CROSS BRIDGING ON EACH SIDE OF OPENING ON EACH SIDE OF CUT BRIDGING AREA WITH BRIDGING EXTENDED ONE BAY BEYOND EACH SIDE OF OPENING. SCALE: 3/8" = 1'-0" 3/16 STEEL BEAM (SEE PLAN) W/3/8" STIFFENER PL AT BOT. FLANGE BRACE LOCATION NOTE: 1. STRUT IS NOT NEEDED WHERE THE DISTANCE FROM PANEL POINT DOES NOT EXCEED 6" FOR JST GDR, OR 3" FOR K-JST. 1. JOIST FABRICATOR TO DESIGN JOIST BEARING SEAT FOR LOAD SHOWN. PROVIDE BEARING SEAT STIFF AS NEEDED. DETAIL DETAIL 2 S-501 SCALE: 1" = 1'-0" 1/8 L4x4x1/4 AT LOCATIONS SHOWN ON PLAN PES PROJECT NUMBER: 0214062 TYPICAL JOIST ROLLOVER DESIGN FORCE NOTE: 1 S-501 STEEL JOIST (SEE PLAN) JST BRG SEAT TYPICAL JOIST/JOIST GIRDER CHORD SUPPORT ANCHOR EQUIPMENT AND CURB TO MISCELLANEOUS FRAMING SHOWN AS REQUIRED FOR WIND AND/OR SEISMIC FORCES. COORDINATE WITH EQUIPMENT/CURB MANUFACTURER (CONNECTION DESIGN NOT BY PES STRUCTURAL ENGINEERS). PLAN DETAIL 300# LOAD (MAX) © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:11:13 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" N 3 SCALE: 1" = 1'-0" "TYP. BEAM BOTT. FLANGE BRACE" DETAIL 4 S-501 SCALE: 1" = 1'-0" 5 S-501 OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS H COLUMN 3/16 STIFF PL (EA SIDE OF BEAM). MATCH THICKNESS OF COL WALLS AND ALIGN W/ COL WALLS BEAM SPLICE (SEE PLAN) W = WIDTH OF BEAM OR COL, WHICHEVER IS GREATER PLUS 1" * 1/4" PLATE NEAR AND FAR SIDE * G COL = WELD SIZE EQUAL TO COL WALL THICKNESS DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 4" TYP. CONT STL ANGLE (SEE PLAN AND DETAILS) * 3/16 PL 3/4"X2" X 0'-8" STEEL BEAM (SEE PLAN) F STL. BEAM (SEE PLAN) * CONNECTION SHALL DEVELOP THE SHEAR CAPACITY OF THE WEAKER MEMBER E 3/4" DIA. BOLTS * "TYPICAL STEEL BEAM SPLICE (SP)" DETAIL 6 S-501 SCALE: 1" = 1'-0" D DETAIL 1/2" CAP PL. * WELD SIZE EQUAL TO COLUMN WALL THICKNESS SCALE: 3" = 1'-0" "TYP BEAM OVER COLUMN CONN" GROUT POCKET SOLID AROUND BEAM STEEL BEAM (SEE PLAN) DETAIL 7 S-501 SCALE: 1" = 1'-0" L4x4x3/8 x W (TYP) L8x6x1/2 (LSV) x W" FOR HSS10x & LARGER WHERE INTERSECTING BEAM EXISTS "TYP TUBE BEAM TO COL CONN" COLUMN * 3/16 3/4"-DIA. BOLT (TYP. 4-TOTAL) DETAIL 1/2" CAP PL. B/STL SCALE: 1" = 1'-0" STEEL BEAM (SEE PLAN) (SEE PLAN) 8 S-501 D C No. STL PL 3/8"X6" X 10" LG W/ (4)-1/2" DIA X 5" LG HCA USE 1/2" CAP PLATE @ END IF TUBE BM. 2-GROUTED CELLS W/#5 @ EACH CELL (U.N.) 1" (TYP) TYP SEAM TYPICAL STEEL BEAM BEARING ON TOP OF CMU WALL SECTION SCALE: 1" = 1'-0" 10 S-501 12.19.14 10.27.14 Date STOREFRONT (SEE ARCH) CMU WALL (SEE PLAN FOR SIZE AND REINF) B A L3X3X5/16 NOT REQUIRED STEEL COLUMN (SEE PLAN) STEEL POST-UP (SEE PLAN) 9 S-501 * 1/4" STIFF PLATE @ BEAM CENTERLINE (TYP) STL BM (SEE PLAN) 5/16" STIFF. PLATE (NEAR AND FAR SIDES WELD 1/8" ALL-AROUND) C TYPICAL CONTINUOUS ROOF ANGLE SPLICE * 3/4"-DIA. BOLT (TYP. 4-TOTAL) STEEL COLUMN (SEE PLAN) 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 * WELD SIZE EQUAL TO COLUMN WALL THICKNESS (NOT TO EXCEED 5/16") STIFF PL (EA SIDE OF BEAM). MATCH THICKNESS OF COL WALLS AND ALIGN W/ COL WALLS PIPE COL (SEE PLAN) "TYP POST-UP COLUMN CONN" DETAIL SCALE: 1" = 1'-0" 11 S-501 DETAIL SCALE: 1" = 1'-0" 12 S-501 3/16 DECK SUPPORT ANGLE AT HSS COLUMN DETAIL SCALE: 1" = 1'-0" PROJECT NUMBER 14116 DRAWN: ABS L3X3X5/16 13 S-501 PERMIT SET DD PRICING SET Description ISSUANCE CHECKED: TRP SHEET TITLE ROOF FRAMING SECTIONS & DETAILS SHEET NO. S-501 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 2" E/ANGLE T/PARAPET (SEE ARCH) 3" M 3" F/STUD= E/ANGLE F/STUD 2" F/STUD=E/ANGLE=F/POST=F/TUBE BEAM T/PARAPET T/PARAPET 6" METAL STUDS (DESIGN PER SPEC CRITERIA) (SEE ARCH) L3X3X1/4 CONT 6" METAL STUDS (DESIGN PER SPEC CRITERIA) T/PARAPET HSS5X5X3/8 @ 5’-6" OC (MAX) STEEL PL 3/8" X 8" CONT STEEL ROOF DECK 1/4 METAL STUD CLIP (DESIGN PER SPEC CRITERIA) 1/4 6" METAL STUD INFILL (DESIGN PER SPEC CRITERIA) METAL STUD CLIP (DESIGN PER SPEC CRITERIA) STEEL PL 3/8" X 8" CONT STEEL ROOF DECK T/STEEL (SEE PLAN) T/STEEL HSS5X5X3/8 @ 5’-6" OC 6" METAL STUDS (DESIGN PER SPEC CRITERIA) STEEL ROOF DECK 1/8 HSS6X3X1/4 CONT K EXIST STRUCTURE 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com (SEE ARCH) (SEE ARCH) L Croft & Associates (TYP T & B) 1/4 BEAM 4" HSS6X3X1/4 (LSH) CONT F/STUD (SEE PLAN) 6" (GC FV) T/STEEL 3/16 (SEE PLAN) 3/16 3-12 6" EXT FINISH (SEE ARCH) STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC J STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL JOIST (SEE PLAN) 1/8 3/16 STEEL JOIST (STEEL BEAM @ SIM COND) (SEE PLAN) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) L3X3X1/4 CONT 1/8 SECTION STEEL ROOF DECK I 2 S-502 SCALE: 1" = 1'-0" 1/4 SECTION JOIST BRIDGING (TYP - SEE PLAN) SCALE: 1" = 1'-0" 3-12 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC 6" METAL STUDS (DESIGN PER SPEC CRITERIA) SECTION SCALE: 1" = 1'-0" 1/8 JOIST BRIDGING (TYP - SEE PLAN) L3X3X1/4 @ 4'-0" OC 4 S-502 OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS E/ANGLE COL & BEAM T/PARAPET H (SEE ARCH) 4" HSS6X3X1/4 (LSH) CONT F/STUD HSS8X3X1/4 (LSH) (CONT) COL & BEAM STEEL JOIST (SEE PLAN) EXIST CONC WALL 8" METAL STUDS (DESIGN PER SPEC CRITERIA) 3" F/STUD= E/ANGLE 6" METAL STUDS (DESIGN PER SPEC CRITERIA) L4X4X1/4 CONT SECTION SCALE: 1" = 1'-0" STEEL PL 3/8" X 10" CONT 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 STEEL ROOF DECK (SEE PLAN) 2" EJ 1 S-502 T/STEEL STEEL ROOF DECK (SEE PLAN) METAL STUD CLIP (DESIGN PER SPEC CRITERIA) (SEE PLAN) 3/16 7" T/STEEL (SEE PLAN) E METAL STUD CLIP (DESIGN PER SPEC CRITERIA) DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 2" EJ 1/8 F HSS5X5X3/8 @ 5’-6" OC (MAX) (TYP T&B) 1/4 HSS5X5X3/8 @ 5’-6” OC (MAX) WHERE H> 2’-6” T/PARAPET (SEE ARCH) 8" 8" METAL STUDS (DESIGN PER SPEC CRITERIA) T/PARAPET (SEE ARCH) STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC & AT EA JOIST) G (TYP T & B) 1/4 3/16 L3X3X1/4 KICKER @ EA JOIST PES PROJECT NUMBER: 0214062 COL & BEAM 3" F/STUD= T/STEEL (SEE PLAN) 3/16 STEEL JOIST (SEE PLAN) 3 S-502 "H" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 0 1/2" 1" COL & BEAM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt 19 COL & BEAM 3" F/STUD= CUT EXIST STEEL BEAMS BACK OVER NEW ADDITION ROOF (TYP) COL & BEAM 12/19/2014 5:11:19 PM 18 EXIST COL 1' - 3 7/8" N THIS SHEET PLOTS ON 22" x 34" ANSI D 17 3/16 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC 3-12 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL JOIST (SEE PLAN) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) PRE-ENGINEERED ALUMINUM CANOPY (DESIGN & CONNS BY OTHERS) EXIST STEEL BEAM (GC VERIFY) JOIST BRIDGING (TYP - SEE PLAN) STEEL BEAM (SEE PLAN) D 6" METAL STUDS (DESIGN PER SPEC CRITERIA) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) SEE 3/S-501 FOR DECK DIRECTION CHANGE STEEL PL 3/8" X 8" CONT STEEL ROOF DECK STL ROOF DECK (SEE PLAN) T/STEEL C (SEE PLAN) T/STEEL 6" (SEE PLAN) 3/16 STEEL BEAM (SEE PLAN) 3/16 JOIST BRIDGING (SEE PLAN) STL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC SECTION SCALE: 1" = 1'-0" 5 S-502 SECTION SCALE: 1" = 1'-0" 6 S-502 PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 14116 STL JOIST (SEE PLAN) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) A 12.19.14 10.27.14 Date 3-12 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC B GLAZING (SEE ARCH) D C No. SECTION SCALE: 1" = 1'-0" 7 S-502 STEEL JOIST (SEE PLAN) DRAWN: ABS JOIST BRIDGING (TYP - SEE PLAN) SHEET TITLE L3X3X1/4 @ 4'-0" OC CHECKED: TRP ROOF FRAMING SECTIONS & DETAILS SHEET NO. S-502 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2" N M F/STUD= E/ANGLE Croft & Associates 4" 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com 3/16 3-12 L4X4X1/4 CONT STEEL ROOF DECK (SEE PLAN) L T/STEEL (SEE PLAN) K STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC JOIST BRIDGING (TYP-SEE PLAN) COL & BEAM 4" F/STUD J HSS8X3X1/4 (LSH) (CONT) EXT FINISH (SEE ARCH) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) PES PROJECT NUMBER: 0214062 T/PARAPET (TYP T&B) 1/4 (SEE ARCH) BEAM 8" METAL STUDS (DESIGN PER SPEC CRITERIA) I L4X4X1/4 CONT T/PARAPET 8" METAL STUDS (DESIGN PER SPEC CRITERIA) HSS5X5X3/8 @ 5’-6” OC (MAX) WHERE H> 2’-6” (SEE ARCH) STEEL ROOF DECK H COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS STEEL ROOF DECK (SEE PLAN) 1/8 METAL STUD CLIP (DESIGN PER SPEC CRITERIA) OWNER STEEL PL 3/8" X 10" CONT "H" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:11:25 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" X1 METAL STUD CLIP (DESIGN PER SPEC CRITERIA) L3X3X1/4 KICKER @ 4’-0” OC T/STEEL T/STEEL (SEE PLAN) BEAM & COL (SEE PLAN) F/STUD= E/ANGLE 7" EXT FINISH (SEE ARCH) 3/16 L4X4X1/4 CONT 3-12 1/8 G STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL PL 3/8" X 10" CONT STEEL ROOF DECK (SEE PLAN) EXTERIOR VENEER (SEE ARCH) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) T/STEEL JOIST BRIDGING (TYP - SEE PLAN) STEEL ROOF DECK (SEE PLAN) (SEE PLAN) STEEL PL 3/8” X 14” CONT T/STEEL (SEE PLAN) 7" E EXT FINISH (SEE ARCH) 3/16 T/STEEL 3-12 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC (SEE PLAN) 11" STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL BEAM (SEE PLAN) W/ 1/4” STIFF PL @ 4’-0” OC 3/16 STEEL JOIST (SEE PLAN) 8" METAL STUDS (TYP-DESIGN PER SPEC CRITERIA) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) 1/4 D HSS6x6x3/8 @ 48" O.C. EXT FINISH (SEE ARCH) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) STEEL JOIST (SEE PLAN) EXTEND TOP CHORD AS SHOWN (TYPE R1) STEEL BEAM (SEE PLAN) W/ 1/4” STIFF PL @ 32” OC BOTH SIDES JOIST BRIDGING (TYP - SEE PLAN) STEEL ROOF DECK (SEE PLAN) 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 T/STEEL (SEE PLAN) 3/16 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER STEEL ROOF DECK (SEE PLAN) L3X2X1/4 (LLH) CONT 1/8 STEEL JOIST (SEE PLAN) STEEL ROOF DECK (SEE PLAN) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) F 3/16 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL JOIST (SEE PLAN) 4" STEEL JOIST (SEE PLAN) SEE 3/S-501 FOR DECK DIR CHANGE STEEL ROOF DECK (SEE PLAN) L4X4X1/4 CONT T/STEEL (SEE PLAN) 1/8 STEEL ROOF DECK STEEL BEAM (SEE PLAN) C D C No. 1/4 STEEL BEAM (SEE PLAN) 1/4 GLAZING (SEE ARCH) T/STEEL T/STEEL (SEE PLAN) PROJECT NUMBER 14116 B STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL JOIST (SEE PLAN) SECTION SCALE: 1" = 1'-0" PERMIT SET DD PRICING SET Description ISSUANCE (SEE PLAN) STEEL BEAM (SEE PLAN) A 12.19.14 10.27.14 Date 1 S-503 SECTION SCALE: 1" = 1'-0" 2 S-503 STEEL BEAM (SEE PLAN) W/ 1/4” STIFF PL @ 4’-0” OC COILING DOOR (SEE ARCH) (CONN TO STEEL FRMG BY COILING DOOR MANUF) SECTION SCALE: 1" = 1'-0" 3 S-503 SECTION SCALE: 1" = 1'-0" 4 S-503 STEEL JOIST (SEE PLAN) DRAWN: ABS JOIST BRIDGING (TYP-SEE PLAN) SHEET TITLE CHECKED: TRP ROOF FRAMING SECTIONS & DETAILS SHEET NO. S-503 3" 1 2 3 N 5 7 8 9 10 11 12 13 14 15 16 17 18 19 1/4 1/4 4' - 0" Croft & Associates T/STEEL M 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com (SLOPES - SEE PLAN) L4X4X1/4 CONT 1/4 EXT FINISH (SEE ARCH) L STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL BEAM W/ 5/16" STIFF PL @ 4'0" OC BOTH SIDES L4X4X1/4 1/4 4' - 0" L3X3X1/4 KICKER @ 4'-0" OC K STEEL ROOF DECK (SEE PLAN) 1/4 1/4 L4X4X1/4 CONT T/STEEL J (SLOPES - SEE PLAN) PES PROJECT NUMBER: 0214062 1/4 EXT VENEER (SEE ARCH) EXT FINISH (SEE ARCH) I OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS L4X4X1/4 @ 48" OC 1/4 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC T/STL H (SEE PLAN) GLAZING (SEE ARCH) L3X3X1/4 KICKER @ 4'-0" OC G METAL STUD CLIP (TYP - DESIGN PER SPEC CRITERIA) METAL STUD CLIP (TYP DESIGN PER SPEC CRITERIA) STEEL BEAM W/ 5/16" STIFF PL @ 4'-0" OC BOTH SIDES DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER EXT VENEER (TYP - SEE ARCH) STEEL BEAM (SEE PLAN) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) T/STEEL (SEE PLAN) 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 C8X11.5 @ 32" OC INFILLED W/ 8" METAL STUDS (DESIGN PER SPEC CRITERIA) 6" METAL STUDS (DESIGN PER SPEC CRITERIA) F EXT VENEER (TYP SEE ARCH) STEEL BEAM (SEE PLAN) (TYP TOP & BOTT) 3/16 E 3/16 STEEL PL 3/8" X 10" CONT 2" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 6 BEAM & COL STEEL ROOF DECK (SEE PLAN) 2" 1" 1/2" 0 12/19/2014 5:11:32 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 4 STEEL ROOF DECK (SEE PLAN) BEETN PL 6" X 12" (LLH) CONT W/ 5/16" X 6" X 6" STIFF PL'S @ 24" OC D 7" 3/16 PRE-ENGINEERED ALUMINUM CANOPY ( BY OTHERS) (SEE ARCH) C 3-12 STEEL BEAM (SEE PLAN) W/ 1/4" STILL PL @ 4'-0" OC D C No. 8" METAL STUDS (DESIGN PER SPEC CRITERIA) STEEL BEAM (SEE PLAN) 12.19.14 10.27.14 Date STEEL JOIST (SEE PLAN) PERMIT SET DD PRICING SET Description ISSUANCE T/STL (SEE PLAN) B STEEL PL 3/8" X 2'-8" X WIDTH OF OPNG 1 3/8"X6"X6" STIFF PL @ 16" OC BOTH SIDES OF BEAM FOR LENGTH OF OPNG 6" METAL STUDS (DESIGN PER SPEC CRITERIA) JOIST BRIDGING (TYP - SEE PLAN) 1 PROJECT NUMBER 14116 DRAWN: ABS CHECKED: TRP SHEET TITLE ROOF FRAMING SECTIONS & DETAILS A SECTION SCALE: 1" = 1'-0" 1 S-504 SECTION SCALE: 1" = 1'-0" 2 S-504 SHEET NO. S-504 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2" N W-BEAM & POST-UP E/ANGLE F/STUD 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com L4X4X1/4 CONT 3/16 L Croft & Associates 3-12 EXIST SOFFIT SHALL BE CUT BACK FROM OVER NEW ROOF HSS6X3X1/4 CONT T/PARAPET T/STEEL (SEE ARCH) (SEE PLAN) (TYP TOP & BOT) 1/4 HSS5X5X3/8 @ 5'-0" OC MAX INFILLED W/ 6" METAL STUDS (DESIGN PER SPEC CRITERIA) K STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC L4X4X1/4 CONT L4X4X1/4 CONT 3/16 6" METAL STUDS (DESIGN PER SPEC CRITERIA) 3/16 L4X3X3/8 (LLV) CONT (TYP TOP & BOT) METAL STUD CLIP (TYP-DESIGN PER SPEC CRITERIA) J T/STEEL (SEE PLAN) PES PROJECT NUMBER: 0214062 STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PLATE @ 4'-0" OC T/STEEL (SEE PLAN) I (TYP) STEEL BEAM (SEE PLAN) STEEL BEAM W/ 1/4" STIFF PL @ 4'-0" 3/16 OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 3-12 STEEL BEAM (SEE PLAN) W/ 5/16" STIFF PLATE BOTH SIDES @ POST-UP & BM BRG LOC'NS H 3 5/8" METAL STUDS (DESIGN PER SPEC CRITERIA) G DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 6" METAL STUD S (DESIGN PER SPEC CRITERIA) SECTION EXIST DRWY (GC FV) 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 1 S-505 SCALE: 1" = 1'-0" F L6X4X5/16 (LLV) CONT E . CO L T/STEEL 3/16 STEEL ROOF DECK (SEE PLAN) BM 2X PT BLOCKING (SEE ARCH) 1/2" (MIN) COL CATR TUBE BM TUBE BM TUBE BM 0' - 11" 4' - 3 3/8" 1' - 7 1/4" COL STEEL BEAM (SEE PLAN) T/BEAM = T/COL = N) -SEE PLA (SLOPES RADIAL STEEL TUBE (SEE PLAN) L2 1/2X1 1/2X1/4 (LLH) CONT 3 1/2 12 TAPERED BEAM (SEE PLAN) STEEL TUBE (SEE PLAN) L2 1/2X2 1/2X1/4 CONT STEEL ROOF DECK (SEE PLAN) 3/16 COL @ T/TUBE BM 1' - 3 1/4" GLAZING (SEE ARCH) 3" D TUBE BM 6" © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. M 4 1/2" 12/19/2014 5:11:39 PM STEEL BEAM (SEE PLAN) STEEL ROOF DECK (SEE PLAN) BEAMS & COL 1' - 1 1/4" 9.97° STEEL TUBE (SEE PLAN) 3-12 T/STEEL T/STEEL (SEE PLAN) (SEE PLAN) C 3/16 3/8" BENT PL 1/4" CAP PL STEEL BEAM (SEE PLAN) STEEL BEAM (SEE PLAN) B STEEL COL (SEE PLAN) 1/4 3/16 RADIAL STEEL TUBE (SEE PLAN) 1/4 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER 1/4 1/4 D C No. 5/16 3-12 GLAZING (SEE ARCH) 0° .0 80 C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" F/STUD = F/NBE = E/ANGLE 14116 5/16 DRAWN: ABS CHECKED: TRP GLAZING (SEE ARCH) SHEET TITLE ROOF FRAMING SECTIONS & DETAILS A SECTION SCALE: 1" = 1'-0" 2 S-505 SECTION SCALE: 1" = 1'-0" 3 S-505 SHEET NO. S-505 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:11:45 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" N M Croft & Associates BEAM & COL BEAM & COL 1' - 6 5/8" @ 'RA' L3X3X1/4 CONT E/PLATE 4' - 0" 11 5/8" @ 'RC' 1/4 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com STEEL ROOF DECK (SEE PLAN) 3/16 T/STEEL = (SEE PLAN) 1/4 L T/STEEL = (SEE PLAN) 3/8" PL CONT STEEL ROOF DECK (SEE PLAN) 1/4 L4X4X1/4 CONT T/STEEL RADIAL STEEL TUBE BEAM (BEYOND- SEE PLAN) 3/16 C10X15.3 @ 32" O.C. (SLOPES - SEE PLAN) K SECTION 1/4 SCALE: 1" = 1'-0" STEEL BEAM (SEE PLAN) 1 S-506 EXT FINISH (SEE ARCH) J L4X4X1/4 @ 48" OC PES PROJECT NUMBER: 0214062 1/4 I 8" METAL STUDS (TYP DESIGN PER SPEC CRITERIA) STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC OWNER EXT FINISH (TYP - SEE ARCH) F/STUD = 3" W-BEAM, HSS BEAM, & HSS POST UP HSS6X3X1/4 (LSH) CONT L3X3X1/4 KICKER @ 4'-0" OC T/STL (SEE PLAN) BEAM & POSTUP F/STUD = 3" HSS5X5X3/8 @ 5'-6" OC MAX INFILLED W/ 6" METAL STUDS (DESIGN PER SPEC CRITERIA) H STEEL BEAM W/ 5/16" STIFF PL @ 4'-0" OC BOTH SIDES 1/4 HSS6X3X1/4 (LSH) CONT T/STL (SEE PLAN) HSS5X5X3/8 @ 5'-6" OC MAX INFILLED W/ 6" METAL STUDS (DESIGN PER SPEC CRITERIA) STEEL ROOF DECK (SEE PLAN) STEEL PL 3/8" X 10" CONT COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 1/4 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER EXT FINISH (SEE ARCH) G EXT FINISH (SEE ARCH) 3/16 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 3-12 F STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 4'-0" OC STEEL ROOF DECK (SEE PLAN) 8" METAL STUDS (DESIGN PER SPEC CRITERIA) STEEL JOIST (SEE PLAN) E STEEL ROOF DECK (SEE PLAN) JOIST BRIDGING (TYP - SEE PLAN) T/STL (SEE PLAN) T/STL (SEE PLAN) D SECTION SCALE: 1" = 1'-0" 5" 2 S-506 (TYP) STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 32" OC C 3/16 L3X3X1/4 KICKER @ 32" OC (ALTERNATE SIDES) STEEL BEAM (SEE PLAN) W/ 5/16" STIFF PL @ 32" OC BOTH SIDES STEEL BEAM (SEE PLAN) W/ 1/4" STIFF PL @ 32" OC 5/16" STIFF PL BOTH SIDES @ POST UP STEEL BEAM (SEE PLAN) No. Date Description ISSUANCE PROJECT NUMBER 14116 B DRAWN: ABS CHECKED: TRP SHEET TITLE ROOF FRAMING SECTIONS & DETAILS A SECTION SCALE: 1" = 1'-0" 3 S-506 SECTION SCALE: 1" = 1'-0" 4 S-506 SHEET NO. S-506 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 12/19/2014 5:11:51 PM C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" 2" N M ROOF (SEE ARCH) TYP 1/4 ROOF (SEE ARCH) 1/4 1/4 ALUMINUM CANOPY (BY OTHERS) ROOF (SEE ARCH) STEEL TUBE (SEE PLAN) 1/4 TYP 1/4 1/4 1/4 Croft & Associates TAPERED END (SEE ARCH) 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com L STEEL TUBE (SEE PLAN) STEEL TUBE (SEE PLAN) K 1/2" STEEL CAP PL (TYP) (ALL OPEN ENDED TUBES SHALL HAVE CAP PLATES) STEEL TUBE (SEE PLAN) STEEL TUBE (SEE PLAN) 1/4 1/4 TYP STEEL TUBE COLUMN (SEE PLAN) J NOTES: 1. ALL EXPOSED STEEL SHALL BE GALVANIZED 2. GRIND SMOOTH ALL EXPOSED WELDS NOTES: 1. ALL EXPOSED STEEL SHALL BE GALVANIZED 2. GRIND SMOOTH ALL EXPOSED WELDS NOTES: 1. ALL EXPOSED STEEL SHALL BE GALVANIZED 2. GRIND SMOOTH ALL EXPOSED WELDS PES PROJECT NUMBER: 0214062 SECTION SCALE: 1" = 1'-0" I 1 S-507 SECTION SCALE: 1" = 1'-0" 2 S-507 SECTION SCALE: 1" = 1'-0" 3 S-507 OWNER COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS H G DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 F E D C No. Date Description ISSUANCE PROJECT NUMBER 14116 B DRAWN: ABS CHECKED: TRP SHEET TITLE THEATER ENTRY CANOPY A SHEET NO. S-507 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 COLUMN 2" N R EQ D AS STL BRACE (SEE BRACE ELEV) 2" ) IN (M R EQ 'D L GUSSET PLATE (EXTEND THROUGH COLUMN IF REQUIRED FOR CONNECTION FORCES AND DESIGN STL BEAM (SEE PLAN) STIFF PLATES (AS REQD). ALIGN AS REQD BASED ON CONN METHOD AND FORCES. ERECTION BOLT (FABRICATOR OPTION) AS WP K ) IN (M STEEL BRACE (SEE BRACE ELEVATIONS) WP J BOTH SIDES BOTH SIDES 2" ( WP T/SLAB M IN ) ERECTION BOLT (FABRICATOR OPTION) (SEE PLAN) STL BEAM (SEE PLAN) GUSSET PL PES PROJECT NUMBER: 0214062 T/FTG BOTH SIDES (SEE PLAN) 2 WIDE FLANGE BEAM WITH BRACE CONNECTION NOTES: NOTES: 1. FABRICATOR SHALL SUBMIT BRACE CONNECTION CALCULATIONS WITH SHOP DRAWINGS. CONNECTIONS SHALL BE DESIGNED FOR FORCES SHOWN ON BRACE ELEVATIONS AND FRAMING PLANS. 1. FABRICATOR SHALL SUBMIT BRACE CONNECTION CALCULATIONS WITH SHOP DRAWINGS. CONNECTIONS SHALL BE DESIGNED FOR FORCES SHOWN ON BRACE ELEVATIONS AND FRAMING PLANS. 2. FABRICATOR HAS THE OPTION TO USE BOLTED GUSSET CONNECTIONS. SUBMIT DETAIL FOR REVIEW AND ACCEPTANCE PRIOR TO SUBMITTING SHOP DRAWINGS. DETAIL SCALE: 1" = 1'-0" G OWNER STL BRACE (SEE BRACE ELEV) WIDE FLANGE BEAM TO HSS COLUMN WITH BRACE CONNECTION H ) IN M ( " ERECTION BOLT (FABRICATOR OPTION) I 1. FABRICATOR SHALL SUBMIT BRACE CONNECTION CALCULATIONS WITH SHOP DRAWINGS. CONNECTIONS SHALL BE DESIGNED FOR FORCES SHOWN ON BRACE ELEVATIONS AND FRAMING PLANS. 3. AT SIMILAR CONDITIONS EITHER THE TOP OR BOTTOM BRACE WILL NOT BE PRESENT. 2. AT SIMILAR CONDITIONS THE BRACING COULD BE PRESENT AT THE TOP OF THE BEAM. DETAIL 1 S-601 DETAIL 2 S-601 SCALE: 1" = 1'-0" COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS NOTES: 2. FABRICATOR HAS THE OPTION TO USE BOLTED GUSSET CONNECTIONS. SUBMIT DETAIL FOR REVIEW AND ACCEPTANCE PRIOR TO SUBMITTING SHOP DRAWINGS. SCALE: 1" = 1'-0" 3 S-601 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 F B2 HSS6X3X1/4 (LSH) B5 HSS6X3X1/4 (LSH) HSS6X3X1/4 (LSH) HSS6X3X1/4 (LSH) T/STEEL B2 B3 T/STEEL W16X40 (SEE PLAN) 2' - 11" 10' - 0". T/STEEL W18X40 T/STEEL W18X35 (SLOPES) HS S5 X5 X3 /8 P = 15 K HSS5X5X3/8 HSS5X5X1/2 HSS6X6X1/2 HSS5X5X1/2 HS S5 X5 X3 /8 P = 15 K HSS5X5X1/2 HSS5X5X3/8 (SLOPES) D C HSS5X5X3/8 B4.7 HSS5X5X3/8 B2 E HSS5X5X3/8 (SLOPES) /8 X3 X5 K S5 25 HS P= © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. 0 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com ) IN (M STANDARD SHEAR CONN TO BE DESIGNED FOR FORCES SHOWN ON PLAN (TYP). USE THRU-PLATE IF AXIAL FORCE TRANSFER IS REQD. STEEL COLUMN (SEE PLAN) 2" C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt Croft & Associates ) IN (M 12/19/2014 5:11:58 PM M 2" THIS SHEET PLOTS ON 22" x 34" ANSI D GUSSET PL (CONNECT TO COL WITH DOUBLE ANGLE WELDED CONNECTION) 2" 1/2" 1" STL COL (SEE PLAN) D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE T/SLAB PROJECT NUMBER (SEE PLAN) B 14116 T/SLAB T/SLAB (SEE PLAN) (SEE PLAN) DRAWN: ABS CHECKED: TRP SHEET TITLE BRACE ALONG A5 A SCALE: 1/4" = 1'-0" 4 S-601 BRACE ALONG A6.4 SCALE: 1/4" = 1'-0" 5 S-601 BRACE ALONG A10 SCALE: 1/4" = 1'-0" 6 S-601 STEEL BRACE DETAILS & ELEVATIONS SHEET NO. S-601 3" 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 N B8 B12 2" B5 T/STEEL (SLOPES - SEE PLAN) 3400 Blue Springs Road, Suite 200 Kennesaw, Georgia 30144 770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com B12 W18X35 HSS10X8X3/8 3/8 X6X 6 S HS K 15 P= L W14X22 T/STEEL T/STEEL (SEE PLAN) (SLOPES - SEE PLAN) W16X26 W16X26 T/STEEL P HSS5X5X3/8 HS S5 X5 X3 /8 P =1 5K HSS5X5X3/8 HS S6 X6 HSS6X6X1/2 K HSS6X6X1/2 HSS7X7X5/8 (SLOPES - SEE PLAN) 3/8 6X X S6 5K HS =1 P X3 /8 =3 5K T/SLAB J (SEE PLAN) PES PROJECT NUMBER: 0214062 T/SLAB (SEE PLAN) I OWNER BRACE ALONG A7 BRACE ALONG A11 1 S-602 SCALE: 1/4" = 1'-0" COBB COUNTY PARKS, RECREATION & CULTURAL AFFAIRS 2 S-602 SCALE: 1/4" = 1'-0" H X2.3 X2 X1 DESIGN IMPROVEMENTS AT COBB COUNTY CIVIC CENTER G T/STEEL W14X22 (SEE PLAN) 548 SOUTH MARIETTA PARKWAY, MARIETTA GA 30060 HSS6X6X1/2 F E A5 A7 A6.3 A9 A9.6 A10 13' - 9" W18X35 W18X35 W18X35 T/STEEL T/STEEL K 8 3/ X 5 5X K S S 20 H = P HSS6X6X5/8 HSS5X5X3/8 35 HSS5X5X3/8 P = HSS5X5X3/8 SS 5X 5X 3/ 8 H HSS8.625X0.500 HSS7X7X5/8 C HS S5 X5 X1 /2 P= 35 K (SLOPES) (SEE PLAN) (SEE PLAN) D T/STEEL W18X35 HSS6X0.500 W16X36 HSS5X5X1/2 © Copyright 2013 by Croft & Associates, PC. All rights reserved. This document is property of Croft & Associates, PC. It is to be used only for the specific project referred to or identified herein and is not to be used on other projects, in whole or in part, except by the express written agreement of Croft & Associates, PC. B8 /8 X3 X5 S5 5K HS =1 P 12/19/2014 5:12:04 PM Croft & Associates M /8 X3 X5 S5 5K HS =1 P C:\Users\bxu\Documents\0214062-Cobb County Civic Center Reno_S13_central_bxu.rvt THIS SHEET PLOTS ON 22" x 34" ANSI D 0 1/2" 1" W18X35 D C No. 12.19.14 10.27.14 Date PERMIT SET DD PRICING SET Description ISSUANCE PROJECT NUMBER B T/SLAB T/SLAB T/SLAB (SEE PLAN) (SEE PLAN) (SEE PLAN) 14116 DRAWN: ABS CHECKED: TRP SHEET TITLE A BRACE ALONG B4.7 SCALE: 1/4" = 1'-0" 3 S-602 BRACE ALONG B5 SCALE: 1/4" = 1'-0" STEEL BRACE ELEVATIONS 4 S-602 BRACE ALONG Y1 SCALE: 1/4" = 1'-0" 5 S-602 SHEET NO. S-602