Hitendra Patel SEGE – Air Liquide Avenue Du Bourget 44 Brussels-1130 Belgium Monday, 25 January 2015 Dear Sir, Subject: Power Transformer and Line Loss Calculations at Air Liquide Eggborough Plant The metered 11kV supply at Air Liquide is connected by a 1.3km cable run to the National Grid 400kV connection via the Eggborough Power Limited (EPL) Station Transformer 1 (ST1). Power Transformer Losses: ST1 Losses - note these calculations were performed on 18/02/1991 and original records reside with EPL. The following power transformer compensation values are employed by EPL’s COP1 registered ST1 metering. In = Nominal current. Vn = Nominal voltage. All values quoted at Main Transformer nominal tap position. In (A) Vn (V) 2,500 11,000 Tap No No Load (kW at Vn) Voltage (V) I squared loss (kW at In) NOMINAL TAP 40.5 NOMINAL 383.1 (Iron Loss: 0.085%) (Copper Loss: 0.804%) Following loss calculated for a decreased prevailing load. For Prevailing Load: IPrevailing (A) Voltage (V) I squared loss (kW at IPrevailing) 7.5MW @ 11kV 393.6 NOMINAL 9.5 (Copper Loss: 0.127%) Line Loss: Cable Type XLPE Length (m) 410 Cross Sectional Area (mm2) 630 Resistance per km (Ω/km) 0.0283 Resistance (Ω) 0.0116 XLPE 474 800 0.0221 0.0105 XLPE 487 630 0.0283 0.0138 TOTAL (per phase) 0.0359 Prevailing Load: 7.5MW @ 11kV IPrevailing (A) Total Resistance (Ω) I squared loss (kW at IPrevailing) 393.6 0.1 16.7 Yours Sincerely, John Strachan (Managing Director) (Line Loss: 0.222%)