LightHAWK™LH-MT/LH-MT-HL
Intelligent Self-Adjusting Multi-Technology
KEY FEATURES
• INTELLIGENT – Continuously Adapting sensor.
• Replaces existing wall switch with the world’s first
multi-technology sensor.
• Combines great minor motion detection of US with
great major motion detection of PIR.
• All-Digital technology, Microprocessor based.
• Sensor adjusts AUTOMATICALLY to changes in room’s
environment.
• Durable, Tamper-Proof Plastic
• Composite signal technology
• Non-Volatile Memory, settings saved in protected
memory are not lost during power outages.
• Lights Turn On & Off Automatically.
• Dual Mode of Operation: Automatic or manual
• Manual Mode - Lights are manually turned on
and automatically turned off.
• Simple, Fast 2-Wire Installation.
• Built-in Photocell Saves Energy.
• Near Zero Voltage Cross Switching, patent pending.
• First Combination Passive Infrared/Ultrasonic Wall Switch
Replacement.
• Ideal for Offices, Small Conference Rooms.
• Designed & Manufactured in USA.
• Less than 2 years pay back.
• 5 year limited warranty
GENERAL OPERATION
The LH-MT is the world’s first wall switch replacement
occupancy sensor to combine both ultrasonic (US) and
passive infrared (PIR) sensing. Hubbell Building Automation’s
self-adapting LH-MT addresses areas with complex environments that are difficult to control with single technology
sensors. The internal microprocessor analyzes the information
from both the US and PIR technologies and determines the
optimum setting to use in order to properly cover the space.
The “Intelligent software” algorithm determines, for example,
if the lights are staying on due to adjacent hallway traffic and
responds by adapting its program to compensate for the false
trigger and turns out the lights. The LH-MT is the ideal wall
switch replacement combining both superior minor motion
detection of US with excellent long-range major motion
detection of PIR.
Occupancy sensors have two tasks keeping the lights on while
the room is occupied and keeping the lights off when unoccu-
pied. Hubbell Building Automation’s continuously adapting
sensor technology eliminates manual sensitivity and timer
adjustments during installation and over the life of the
product. The self-adapting microprocessor constantly assures
maintenance free “Install and Forget” operation.
In addition, the LH-MT has its own built-in photocell, which
increases Energy Savings when engaged by preventing the
lights from turning on when there is sufficient natural light.
This feature is factory disabled and may be activated by the
installer.
Designed specifically to meet the challenges found in rooms
where tasks entails minor motion for long periods of time,
Hubbell Building Automation’s intelligent software reads the
environment and adapts to meet those specific challenges.
Should the room suddenly be reallocated into a copy room
with high traffic patterns, the intelligent software will adapt as
needed to provide the correct time out for the lights. Using
PIR sensing (high error immunity) with US (high sensitivity)
provides good performance. Conventional ceiling mounted
dual tech sensors use a simple formula for operation: BOTH
for ON, EITHER for KEEP ON. This method requires that
both sensors receive fixed-strength signals for ON or a single
fixed-level signal for KEEP ON. The LH-MT uses a more
sophisticated method called a composite signal where the
Distributed by:
Phone: (480) 782-5600
Fax: (480) 782-5601
www.engenuity.com
signal strengths are added together to form a composite sum.
The advantage of this method is that a weak PIR signal plus a
strong US signal will turn the lights on because the sum is
enough. The installer need not worry that the signal level be
balanced for reliable lights on. This technology eliminates
time consuming adjustments and callbacks.
SPECIFICATIONS
·Adaptive
Functions:
Auto reset from test setting, selfadjusting timer, auto-adjust ultrasonic
and infrared thresholds. False-on, false-off
corrections. Continual self-check.
Photocell
Calibration:
Adjustable ambient light override ranges
from approximately 10 foot-candles (10 lux)
to 500+ foot-candles (500+ lux) to prevent
lights from turning ON automatically during
periods of ample natural light.
Timer Timeout: 8 minutes initially, self-adjusts based on
occupancy.
Ultrasonic
Sensor:
40kHz output. Will not interfere
with hearing aids.
Infrared Sensor: Dual element pyrometer, 12 element
cylindrical rugged lens. 1000 sq. ft coverage,
166°. * HL OPTION Dual element pyrometer, 10 element cylindrical hard lens.
300 sq. ft. coverage, 150°.
Construction:
Housing — High-impact, injection molded
plastic. Color-coded leads are 6” long
(16.24 cm).
Size & Weight: 4.2” x 1.8” x 2.1”, extends out .37”: 2.9 oz.
Color:
Specify White (W) or Ivory (I).
Power
Requirements: 120 or 277VAC, 60 Hz. Auto voltage
selection.
Electrical
Ratings:
120VAC: 25 to 600 watts, incandescent
and ballast. 277VAC: 60 to 1200 watts.
Load
Requirements: Low load: 25 to 240 Watts (120V) and 60
to 550 Watts (277V). 208 mA to 2.0A.
High load: 160 to 600 Watts (120V) and 370
to 1200 Watts (277V). 1.3 - 5A.
Operating
Environment:
32° - 104°F (0o - 40°C); 0 - 95%
relative humidity, non-condensing.
Indoor use only.
Mounting:
Single gang NEMA style switch box,
decorator style wall plate. Sensor requires
line of sight and must be able to see the
area of desired coverage for initial lights-on.
Safety Standard: UL and CUL.
Warranty:
5 years.
Controls:
• Pushbutton Switch: Auto on/off, or manual on/auto off.
• Service Disconnect: Air-gap disconnect switch.
• Photocell: set up or disable.
• Test: Test mode for easy check at installation.
LED Lamp:
RED indicates passive infrared motion
GREEN indicates ultrasonic motion.
MODELS
Cat. No.
Color Coverage
LH-MT-W
White Over 1000 sq. ft.
LH-MT-I
Ivory
Over 1000 sq. ft.
LH-MT-HL-W White Over 300 sq. ft.
LH-MT-HL-I
Ivory
Over 300 sq. ft.
*Hard lens unit; resistant to vandelism
Applications
Office
Office
Office*
Office*
RANGE DIAGRAMS
ORTHOGRAPHIC DIAGRAM
WIRING DIAGRAM
Black
Green
Ground
Hot
208 mA - 2.0A
Yellow
25 - 240W
Load @ 120V or
1.3 - 5A
Red
16 - 600W
Load @ 120V or
60 - 550W
Load @ 277V
370 - 1200W
Load @ 277V
SINGLE CIRCUIT
To Hot
Black
5A max
Red
Green
Ground
Load #1
BI-LEVEL CIRCUIT
Load #2
Download