IEA Electric Power Systems Examination in Electric Power Systems Monday 21 October, 2013, 8.00-13.00 Maximum score for each problem is 10 points. To pass you need 20. Use English or Swedish for your solutions. Motivate all your answers and draw relevant circuit diagrams. Allowed: Calculator, formula sheet, TEFYMA or similar. 1 V11 jx13=j0.2 3 V33 PL3+jQL3 PG1+jQG1 jx12=j0.25 jx23=j0.5 jx34=j0.4 4 2 PL4+jQL4 PG2+jQG2 V22 jx24=j0.2 V44 1a. Set up the p.u. bus admittance matrix for the system above, where p.u. impedances are given. (3p) 1b. Prepare for load flow calculation by writing the active and reactive power balances at bus 2. Use only quantities shown in the figure such as PG, QG, PL, QL, V, and x. (4p) 1c. Suggest a bus type (slack, PV or PQ bus) for each bus. (3p) 2a. For the system shown in problem 1, determine the (p.u. positive sequence) shortcircuit impedance (Thévenin impedance) at bus 2. Assume that the generators have xd”=0.1 p.u. and disregard loads. (3p) 2b. Further assume that the prefault voltage at each generator is 1 p.u. and determine the p.u. short-circuit capacity at bus 2. (2p) The network in problem 1 is meshed with several paths from each generator to each load. If (any) one line is lost and the current limits of the remaining lines are not exceeded, the loads can still be supplied. 2c. Does loss of a line increase or decrease three-phase short-circuit current? Motivate briefly. (1p) 2d. Voltage sensitivity to load changes is inversely proportional to short-circuit capacity. Does loss of a line increase or decrease this sensitivity? Motivate! (1p) 2e. Show that connection of a shunt capacitor increases voltage at a bus where the Thévenin impedance is entirely inductive. (3p) OS 1 IEA 3. Electric Power Systems In order to conveniently analyze the system below all values should be converted to p.u. on common base: Using 125 MVA and 130 kV as bases for the transmission lines gives reactance values for each of x=0.72 p.u. G T2 T1 V0° Eq’ Rated values on component bases: G 125 MVA, 11 kV, 50 Hz, x d’=0.25 p.u. T1 150 MVA, 11/130 kV, xeq=0,07 p.u. T2 125 MVA, 120/72 kV, xeq=0,07 p.u. 3a. Generator output P = 85 MW, Eq’=11.35 kV and x d’=0.25 p.u. Use MVA base and voltage base that agree with 125 MVA and 130 kV and determine p.u. values of P, Eq’ and x d’. (3p) 3b. Use MVA base and voltage base that agree with 125 MVA and 130 kV and determine p.u. value of transformer T1 reactance. (3p) 3c. Transformer T2 has xeq=0,07 and low-side voltage V=70 kV. Use MVA base and voltage base that agree with 125 MVA and 130 kV and determine p.u. values of xeq and V. (4p) 4 A zero three-phase short-circuit occurs on the line side of circuit breaker CB3 in the system below when it operates at steady state. The fault is cleared by tripping the faulted line as reaches its post-fault equilibrium value. Use assumptions common in transient stability analysis and do the following: xtr CB1 x1 CB2 H=3 s Pt=1 p.u. CB3 x2 CB4 x’d= 0.3 p.u. xtr=0.1 p.u. Pt E’ q Vbus0 x1= 0.6 p.u. x2= 0.4 p.u. E’q=1.3 p.u. Vbus=1 p.u. 4a. Compute maximum values of active power that can be delivered by the generator before, during and after the fault. (3p) 4b. Draw Pe() and indicate the accelerating area and the maximum decelerating area. (2p) 4c. Compute relevant equilibrium values of . (3p) 4d. Compare the two areas in b. numerically. Is the system transiently stable? (2p) OS 2 IEA 5 Electric Power Systems Somewhere in Småland, a zero earth fault occurs in the a-phase on the 20 kV side of a 20 MVA, 130/20kV /Y transformer fed from a 130kV, 50 Hz system. The network feeding the transformer can be described as Thévenin equivalents for positive sequence (VTH1=130 kV, ZTH1), negative sequence (VTH2=0, ZTH2=ZTH1) and zero sequence (VTH0=0, ZTH0). The transformer has series reactance Xeq and the neutral point of the Y winding is either left unconnected or grounded through a reactance Xn=Ln – a Petersen coil. The transformer phase shift can be ignored. The transformer feeds a new 40 km long 20 kV cable. It can be represented by a -link with R=X=0 leaving only shunt capacitance represented by susceptances (jC/2) jB/2. jB1=jB2=jB0=j0,016 p.u. using base values 100 MVA and 20 kV. 5a. Draw the three sequence diagrams of the system (including network, transformer and cable) as seen from the 20 kV bus. Let the reactance Xn be connected through a switch. (3p) 5b. With the switch open and transformer ungrounded, consider the fault situation: Set all series impedances Xeq, ZTH1, ZTH2 and ZTH0 to zero as they are small compared to 1/B. Redraw the diagrams that are now connected by the fault. Determine the capacitive earth fault current in the a-phase in Amps. (Hint: B1 should not influence the fault current.) (4p) 5c. With the switch closed (and series impedances still zero), show that the fault current (for this fault) can be brought to zero by selecting a certain value of Xn. (2p) 5d. Determine the p.u. value of the reactance Xn that cancels the capacitive earth fault current. (1p) GOOD LUCK! OS 3