B4-1089 AORC Technical meeting 2014 http : //www.cigre.org 130MVA-STATCOM Installation for Transient Stability Improvement Y. Matsushita, S. Iwasaki, T. Imanishi The Kansai Electric Power Co., Inc. Japan K. Masaki, F. Nakamura Mitsubishi Electric Corp. Japan J. Ieda TMEIC Japan SUMMARY KANSAI (The Kansai Electric Power Co., Inc.) transmits electricity generated by hydroelectric power stations through long-distance 154kV transmission line. There are problems that the whole of potential power is unable to be supplied under heavy load conditions and that a system fault outside of the 154kV line may cause the loss of synchronism of generators. Therefore KANSAI has installed a new STATCOM (STATic synchronous COMpensator) with transient stability improving control to solve these problems. The STATCOM is a parallel system of 3-stage-converter (78MVA GCT (Gate Commutated Turn-off thyristor) -STATCOM) and 2-stage-converter (52MVA GCT-STATCOM). Each converter is connected to 154kV bus through multi-stage transformers. The STATCOM system is equivalent of 130MVA-STATCOM. The STATCOM control scheme is configured by AVR (Automatic Voltage Regulator) control, PSS (Power System Stabilizer) control, and Q (reactive power) bias control to improve the damping force and the synchronizing power of the system. In addition, for improving transient stability, the STATCOM coordinates the AVR and PSS depending on the state of a system phenomenon at the system fault. We performed eigenvalue analysis and transient stability analysis to check the system design. Eigenvalue analysis verified that the STATCOM improved the steady-state stability and had redundancy to it. Transient stability analysis verified that the STATCOM prevented generators from losing synchronism. We performed real-time simulator test to confirm the performance of the STATCOM during a system fault because it is difficult to cause actually a system fault at the hydroelectric power system. We simulated the power system in detail by analog type real-time power system simulator and connected the simulator with STATCOM miniature model, actual control device and multi-stage transformer model. The test confirmed that the STATCOM operated properly at various faults. After installing actual STATCOM in Inuyama Switching Station, we conducted performance tests and field tests. It is confirmed that STATCOM enhanced the steady-state stability of the hydroelectric power system and increases TTC (Total Transfer Capability) to maximum flow. KEYWORDS STATCOM - Transient Stability - Steady State Stability - GCT thyristor Masaki.Kenji@db.MitsubishiElectric.co.jp 1. Introduction It tends to install inexpensive and efficient FACTS devices as a countermeasure against various problems in power system. As restructuring of transmission system has been performed in consideration of reliability and economy recently, requirement for STATCOM has been becoming also more demanding such as improvement of transient stability or prevention of the loss of synchronism [1]. Since KANSAI transmits electricity generated by hydroelectric power generation through longdistance 154kV transmission line, there is a problem that the whole of potential power is unable to be supplied under heavy load conditions. Moreover there is a problem that a system fault outside of the 154kV line may cause the loss of synchronism of generators. Therefore KANSAI has installed a new STATCOM with transient stability improving control to solve these problems. 2. 130MVA-STATCOM (1) Purpose Figure 1 shows the hydroelectric power system with 154kV long-distance transmission line. Power flow from the group of generators is supplied to C-S/S through Inuyama-SW/S and B-S/S via 154kV long-distance transmission line. The distance from the group of generators to C-S/S is about 250km. Therefore, it makes the power system unstable under heavy load condition, and makes full-power operation of all generators impossible (about 300MW). Moreover, system faults outside of the 154kV line in Figure 1 may cause loss of synchronism of generators. Then it is necessary to install the new STATCOM at Inuyama-SW/S which is the electrical median point of the system and improve steadystate stability and transient stability by the STATCOM. (2) Configuration Figure 2 shows the system configuration of the 130MVA-STATCOM. Table 1 shows the specification of 130MVA-STATCOM. The STATCOM is a parallel system of 3-stage-converter (the left-side : 78MVA-STATCOM) and 2-stage-converter (the right-side : 52MVA-STATCOM). Each converter is connected to 154kV bus through multi-stage transformers. By both STATCOMs running, the STATCOM system is equivalent of 130MVA-STATCOM. The large capacity 6kV-6kA GCT (Gate Commutated Turn-off) thyristor in Figure 3, which achieves high reliability, downsizing, and low loss, is employed for the 3-level converter unit. (3) Control The system stability of power system shown in Figure 1 are weak especially under heavy load flow because of its long-distance transmission line. For improving system stability, it is necessary to enhance the damping force and the synchronizing power of the system. Therefore the STATCOM control scheme is configured by AVR (Automatic Voltage Regulator) control, PSS (Power System Stabilizer) control, and Q (reactive power) bias control as shown in Figure 4. The AVR control improves the synchronizing power. The PSS control improves the damping force. The Q bias control reduces transmission loss and improves steady-state stability. In addition, for improving transient D-P/S G C-S/S Infinite Bus System ~ B-S/S G 154kV Hydro generators G Inuyama SW/S 78MVA 52MVA F-P/S J-bus G 154kV 275kV 300MW G H-P/S G Fault-A 77kV 3LG 78MVA 52MVA E-P/S 130MVA STATCOM Figure 1. Power System diagram G G I-P/S G-P/S group Figure 2. STATCOM configuration 1 Table 1. Specification of 130MVA-STATCOM Specification of STATCOM System ±130MVA Capacity AC grid voltage 154kV System configuration 2-parallel ±78MVA, ±52MVA Capacity of each STATCOM Specification of 78MVA-STATCOM ±78MVA Capacity 6kV-6kA GCT,1S1P Power device 3-level full-bridge ×3phase Inverter circuit Multiplex transformer 3-stage multiplex Capacity /stage of converter 26MVA 3846V,2253A Voltage, Current /stage of converter ±3000V DC voltage Specification of 52 MVA-STATCOM ±52MVA Capacity 6kV-6kA GCT,1S1P Power device 3-level full-bridge ×3phase Inverter circuit Multiplex transformer 2-stage multiplex Capacity /stage of converter 26MVA 3846V,2253A Voltage, Current /stage of converter ±3000V DC voltage Figure 3. 6kV-6kA GCT thyristor Transient Stability Coordination control Power flow Bus voltage Power flow PSS control ΔV type AVR control Current control reference Q bias control Steady-State Stability Figure 4. STATCOM control stability much more, the STATCOM coordinates the AVR and PSS by adjusting the gains and limiters of AVR and PSS depending on the state of a system phenomenon at the system fault. This control scheme can maximize the effect of improving transient stability by the STATCOM and prevent the loss of synchronism. Each STATCOM transmits and receives each operating state signals with each other, and shifts to appropriate operating condition depending on operating state signal of other STATCOM. The output of Q bias control is shared with each STATCOM as the capacity ratio when both STATCOM is running. However, if either one halts, the other one bears total output of Q bias control. We performed eigenvalue analyses to check steady-state stability enhancing effects by the 130MVASTATCOM. Figure 5 shows the eigenvalue of the power system. In this case, all generators run at rated power and the steady-state stability is the severest. As shown in Figure 5, real part of the eigenvalue is positive when no STATCOM exists, which means that the power system is unstable. However, real part of the eigenvalue is negative when the 130MVA-STATCOM exists. Moreover, the eigenvalue is negative when capacity of STATCOM is 52MVA. These results show that each STATCOM ensures steady-state stability alone, that is, the STATCOM system has redundancy to steady-state stability. Moreover, we performed transient stability analysis to confirm that 130MVA-STATCOM improves transient stability of the power system and prevent all generators from losing synchronism against any system faults outside of the 154kV line. The following Fault-A are the severest fault points outside of the 154kV line in Figure 1. The 130MVA-STATCOM must prevent all generators from losing synchronism against Fault-A. ・Fault-A : B-S/S 77kV Bus Feeder Line 3LG fault (Fault period : 233ms) Figure 6 shows a result of transient stability analysis of Fault-A. In this case, transient stability is the severest because of heavy power flow which all generators output at rated operation, the closest fault point to 154kV system and the longest duration fault. As shown in Figure 6, generators lose synchronism at first wave when no STATCOM exists. On the other hand 130MVA-STATCOM prevents the loss of synchronism using the control scheme described above against the severest FaultA. 2 2.0 1.8 Period [sec] With 1.6 130MVA-STATCOM 1.4 ] c e 1.2 s[ With 1.0 d 52MVA-STATCOM o rie 0.8 p Without STATCOM 0.6 0.4 0.2 -0.5 -0.4 -0.3 -0.2 -0.1 0.0 0.0 0.1 0.2 0.3 -Damping [1/sec] Damping [1/sec] Figure 5. System study for steady-state stability by eigenvalue analysis Figure 6. System study for transient stability at Fault-A by simulation 3. Real time Simulator Test We performed real-time simulator test to confirm the performance of the STATCOM during a system fault because it is difficult to cause actual system fault at the hydroelectric power system. The hydroelectric power system containing 154kV long-distance transmission line as shown in Figure 1 was simulated in detail by analog type real-time power system simulator. We connected the simulator with STATCOM miniature model which is composed of the same constitution as the actual system, actual control device and multi-stage transformer model. This real time simulator test verified operation of the STATCOM at the time of various system faults. Figure 7 shows impedance-frequency characteristic of the hydroelectric power system by the real-time simulator and one by electromagnetic transient analysis. The upper figure is f-z characteristics of simulator. The lower figure is one of electromagnetic transient analysis model. Both characteristics are very well matched. These show that the power system is simulated with great accuracy by real-time simulator. Figure 8 shows simulator test result of a close-in 3LG fault. Voltage of the STATCOM connection bus drops to 0pu. The STATCOM detects a voltage drop and performs gate-block (GB) until the fault is cleared. After the fault is cleared, the STATCOM detects a restoration voltage and performs gate deblock(DEB) immediately. The test confirmed that the STATCOM operates properly at a close-in 3LG fault. 4. Field Test After installing actual STATCOM in Inuyama SW/S, we conducted performance tests and field tests. Figure 9 shows performance test result to verify the the operational mode changing function as one of performance tests. Before 52MVA-STATCOM is stopped, the 130MVA-STATCOM outputs Figure 7. Impedance-Frequency characteristics Figure 8. Simulator test result of a close-in 3LG fault 3 Figure 9. Test result of the mode switching of the STATCOM control Figure 10. Test result of transmission capability 10Mvar by Q bias control (78MVA-STATCOM outputs 6Mvar and 52MVA-STATCOM outputs 4Mvar). After 52MVA-STATCOM is stopped, 78MVA-STATCOM performs gate-block (GB) temporarily and changes from double bundle operational mode to single operational mode. Q bias control of 78MVA-STATCOM sets command value into 10Mvar. 78MVA-STATCOM performs gate de-block(DEB) immediately. This test confirmed that the STATCOM operates stably without current fluctuation of it when changing operational mode. We also performed a field test which checks that the STATCOM increases TTC of hydroelectric power system. As in figure 5 in the absence of STATCOM, the power system becomes unstable under full-power operation of all generators. That is, TTC is less than the maximum flow. In this test, the STATCOM was operated and the output of the generators was increased gradually. Figure 10 shows result of the field test under maximum flow. Figure 10-① shows that the power system is stable under maximum flow by the 130MVA-STATCOM actuating and outputting reactive power by Q bias control. Additionally, in order to confirm the redundancy for the steady-state stability, 78MVASTATCOM is stopped when both STATCOM operate at the maximum flow. After 78MVASTATCOM is stopped, 52MVA-STATCOM changes operational mode and increases reactive current output by Q bias control. Figure 10-② shows that even 52MVA-STATCOM solely ensures steadystate stability and increases TTC to maximum flow. Then 78MVA-STATCOM restarts, and 52MVASTATCOM changes operational mode and returns reactive current output to previous value in Figure 10-③. This test confirmed that the STATCOM enhances the steady-state stability of the hydroelectric power system and increaces TTC to maximum power flow since system voltage, power flow and output of reactive current of the STATCOM are stable regardless of the operational mode of the STATCOM. 5. Conclusions A new STATCOM has been installed for stable power transmission of hydroelectric power. The STATCOM has the smart effect of transient stability improvement as well as the effect of steady-state stability improvement. The system stability improvement effected by the STATCOM was confirmed by simulator test and field test. This STATCOM has started the commercial operation in 2013. References [1] S. Mori, "Initiatives perspectives by the power industry towards a low carbon emission society," Keynote address of Paris Session CIGRE 2010. 4