Santa Barbara City College Demand Response Technical Audit Santa Barbara, California Prepared for: Facility Director: Julie Hendricks Account Executive: Lisa Hannaman Prepared by: March 8, 2013 TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. SCE Job Number 1282 Mechanical Engineers Principals: Frank Shadpour, P.E. Jeremy Clifton, P.E. Edward Lehman, P.E. Lyle Willis, P.E. Joseph Kilcoyne, P.E. March 8, 2013 Ms. Julie Hendricks Santa Barbara City College 721 Cliff Dr Santa Barbara, CA 93109 Project: Santa Barbara City College SC Project Number: 09141.021 SCE Job Number: 1282 Subject: Demand Response Technical Audit (TA) Study Ms. Hendricks, SC Engineers is pleased to present the findings for the Demand Response Technical Assistance (TA) Study for Santa Barbara City College. The intent of this energy analysis report is to identify and evaluate potential electrical demand reduction savings in accordance with SCE’s TA/TI program guidelines at the Santa Barbara City College. Appropriate details are included in this report to make informed decisions regarding implementing demand response measures at this facility. However, this report is not intended to serve as a detailed engineering design document. The descriptions of the improvements are only diagrammatic in nature to document the basis of cost estimates and savings, and to demonstrate the feasibility to implement the recommended upgrades. It should be noted that detailed design efforts may be required to implement several of the improvements evaluated as part of this energy analysis. While the recommendations in this report have been reviewed for technical accuracy and are believed to be accurate, the findings are estimates and actual results will vary based on future building use and weather patterns. All savings and cost estimates in the report are for informational purposes, and should not be construed as a design document or as guarantees. Please note that the recommendations included are for your reference only and by no means mandatory. Thank you for this opportunity to be of service. Sincerely, SC ENGINEERS, INC. Frank Shadpour, P.E., CxA, LEED AP President 17075 Via Del Campo First Floor San Diego, CA 92127 858.946.0333 Tel 858.946.0334 Fax www.scengineers.net TABLE OF CONTENTS EXECUTIVE SUMMARY PAGE Scope of the Report........................................................................................................................................................... 1 Synopsis and Findings....................................................................................................................................................... 1 Measures Summary........................................................................................................................................................... 2 TECHNICAL ANALYSIS Problem Statement............................................................................................................................................................ Existing Conditions............................................................................................................................................................ Demand Response Measure # 1: HVAC - Chilled Water Supply Temperature Reset................................................... Demand Response Measure # 2: HVAC - Space Temperature Reset........................................................................... Demand Response Measure # 3: HVAC - Data Center Temperature Reset................................................................. Demand Response Measure # 4: HVAC - Heating Hot Water Pump Shutdown............................................................ Demand Response Measure # 5: Lighting - Lighting Reduction.................................................................................... Demand Response Measure # 6: Process Load - Fountain Pump Shutdown............................................................... Demand Response Measure # 7: Process Load - Pre-Cool Refrigeration Spaces........................................................ Demand Response Measure # 8: Process Load - Beverage Vending Machine Compressor Shutdown....................... 3 3 9 10 11 12 13 14 15 16 CONCLUSION Energy Efficiency Measures Summary.............................................................................................................................. 17 Demand Response Measures Summary........................................................................................................................... 20 APPENDICES APPENDIX "A" - Equipment Lists APPENDIX "B" - SCE Technical Analysis Forms APPENDIX "C" - Calculations and Supporting Information APPENDIX "D" - TRACE 700 Building Energy Simulation Results APPENDIX "E" - SCE Fact Sheets Building Information Model of SBCC Main Buildings TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE i SCE Job Number 1282 EXECUTIVE SUMMARY Scope of the Report This report provides an evaluation of potential electrical kW demand reduction in the Santa Barbara City College, located at 721 Cliff Dr in Santa Barbara, California in accordance with the SCE Technical Assistance and Audit Report Program. Synopsis and Findings This Technical Audit identifies electrical kW demand reduction strategies, their associated projected kW savings, and recommends measures for automating demand response. Existing On-peak kW Demand: Based on the average of the top 15 days of 2012 SCE load profile records, the on-peak electrical demand for the facility is approximately 1,661 kW. Average On-peak kW Demand Reduction: The total average summer on-peak reduction in kW demand addressed in this Technical Audit Report is 497 kW (30% of existing facility demand). ▪ Based on a Critical Peak Pricing (CPP) utility rate, the projected demand reduction will result in a $2,123 savings per event if all measures are implemented for the full 4 hour event period. Existing Annual Energy Consumption: Based on 2012 representative SCE records, the facility's annual energy consumption is approximately 7,300,000 kWh [11.9 kWh / (sf yr)]. Effect of Demand Response on Peak Load Demand Response Day Profile Typical Peak Demand Profile 1,800 Electricity Demand (kW) 1,600 1,400 1,200 1,000 800 600 400 200 23:00 22:00 21:00 20:00 19:00 18:00 17:00 16:00 15:00 14:00 13:00 12:00 11:00 10:00 9:00 8:00 7:00 6:00 5:00 4:00 3:00 2:00 1:00 0:00 0 Time Peak Day Demand Profile Comparison • SCE Incentives: Demand Response technology incentives are available as follows: ▪ Semi-Automated: 497 kW x $125/kW = $62,125 ▪ Fully Automated*: 497 kW x $300/kW = $149,100 • All measures identified have been discussed with facility operating personnel and are considered possible based on the functional requirements of the facility. • Actual incentives available will be based on testing conducted by SCE's third party verification engineer. * Fully automated measures are those that can be implemented through the building automation system without human intervention TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 1 SCE Job Number 1282 EXECUTIVE SUMMARY Demand Response Measures Summary Demand response measures identified for the Santa Barbara City College fall into three (3) categories. The measures for each category are summarized as follows: Demand Response Measure # 1: Demand Response Measure # 2: Demand Response Measure # 3: Demand Response Measure # 4: Demand Response Measure # 5: Demand Response Measure # 6: Demand Response Measure # 7: Demand Response Measure # 8: HVAC - Chilled Water Supply Temperature Reset - 14.2 kW HVAC - Space Temperature Reset - 340.9 kW HVAC - Data Center Temperature Reset - 2.4 kW HVAC - Heating Hot Water Pump Shutdown - 9.2 kW Lighting - Lighting Reduction - 113.5 kW Process Load - Fountain Pump Shutdown - 3.2 kW Process Load - Pre-Cool Refrigeration Spaces - 2.8 kW Process Load - Beverage Vending Machine Compressor Shutdown - 11.1 kW The total potential average demand reduction available during summer on-peak hours is 497 kW. DR # 2 - Space Temperature Reset, 340.9 kW, 21% DR # 3 - Space Temperature Reset #2:, 2.4 kW, 0% DR # 4 - Heating Hot Water Pump Shutdown, 9.2 kW, 1% DR # 5- Lighting Reduction, 113.5 kW, 7% DR #1 - Chilled Water Supply Temperature Reset, 14.2 kW, 1% DR # 6 - Fountain Pump Shutdown, 3.2 kW, 0% DR # 7 - Pre-Cool Refrigeration Spaces, 2.8 kW, 0% DR # 8 - Beverage Vending Machine Compressor Shutdown, 11.1 kW, 1% Remaining Facility Peak Demand Load, 1,163.6 kW, 70% Facility Peak Electrical Demand Reduction Construction Estimates: The construction estimates within this report are approximated and have not been verified by a construction estimator or contractor. The actual cost may vary. Verification of construction cost by the owner is required. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 2 SCE Job Number 1282 TECHNICAL ANALYSIS Problem Statement The Technical Assistance & Technology Incentive (TA & TI) program was established to identify opportunities for reducing the overall demand requirements for SCE's electrical service during critical peak periods known as “Demand Response” events. This Technical Audit Report identifies the potential for kW demand reduction in the Santa Barbara City College under SCE's TA & TI Program. Demand reduction opportunities are addressed for the facility’s electrical requirements during the SCE summer on-peak electrical demand period between June 1 and October 1. Demand Response Overview: Demand Response (DR) is a voluntary and short-term reduction in a consumer's use of electricity during a period of peak electrical demand when the power grid is stressed. SCE Demand Response (DR) program allows customers to participate in DR events without manual interference using a building management system (BMS). The program enables customers to choose their level of participation and to pre-select the measures that are implemented during an event saving energy, time, and money. The DR program is automated through a Demand Response Automation Server (DRAS) which provides an alert message to commercial customers or aggregators participating in the program. The DR alert messages are provided to customer control systems by either the utility company or the California ISO, a company that provides open and non-discriminatory access to the bulk of the state's wholesale electrical transmission. The complex DR signals are then translated into a simple to understand language using the OpenADR standard. OpenADR is a communications data model designed around internet language standards which includes the XML format. The alert message is then either implemented manually by a facility staff member via a centralized control system (Semi-automated Demand Response) or automated without human intervention via the central computer system (Fully-automated Demand Response). The DR communication network is shown in the figure below. The benefits of Demand Response include the following: -Price control with minimal to no energy importing -Increased grid reliability -No new or peaker power plants -Reduced natural resource usage TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 3 SCE Job Number 1282 TECHNICAL ANALYSIS Existing Conditions The Santa Barbara City College consists of approximately twenty (20) buildings consisting of approximately 550,000 sq. ft., approximately fifty (50) portable units consisting of approximately 62,500 sq. ft., a parking structure, several parking lots, and sporting fields. The campus is heavily occupied from 7:00am - 8:00pm as it hosts several evening classes in addition to a typical school day schedule. The majority of rooms consist of class/lecture and office occupancies. Other notable areas are the gymnasium located in the Physical Education building and the performance stages located in the Drama and Music building. These areas may hold additional events not associated directly with the college. Facility Electrical Demand: The average of the annual top eighteen demand days for the facility is approximately 1,661 kW based on SCE load profile records. The Santa Barbara City College is served by two (2) electric meters equipped with Internal Data Recorder (IDR) capability. The kW load profile is shown below for the average top fifteen kW demand days and the twelve event days in the 2012 demand response season.The average summer daily load profile is also shown for reference. The building's electrical peak is typically 150% times larger than the baseline. This indicates that the load is dependent on time-of-day loads and outdoor conditions. 2012 Peak Demand Profiles 2,000 9/20 9/10 1,800 8/29 1,600 1,400 8/27 1,200 8/20 1,000 8/13 800 8/9 600 8/7 400 7/23 200 7/12 0 6/29 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 Electrical Demand (kW) 9/28 Time of Day TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. Average Top 15 Peak Day Average Day June-Sep PAGE 4 SCE Job Number 1282 SBCC CAMPUS OVERVIEW The Santa Barbara City College is separated into two (2) main campuses: West Campus and East Campus. These campuses are divided by Loma Alta Drive, and are connected by a pedestrian bridge. Portable units are found on both campuses. The details of the campuses are shown in the table below: Campus West Campus East Campus Portables Number of Buildings 6 13 ~50 Total Floor Area (sq ft) 182,520 366,832 62,500 Existing Systems: The details of HVAC electrical loads per each building in the two (2) campuses can be found in the following pages. Refer to the Equipment List in Appendix A for details. The systems common among both campuses are described below: HVAC ~ Control System: The HVAC equipment for the main buildings at the Santa Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC system. This system can be accessed through computers located in the Facilities & Operations building. The system can not be accessed remotely due to strict campus internet security. The JCI system controls the majority of major HVAC equipment on campus: chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC equipment through the JCI system and timeclocks. Facility staff noted that they monitor buildings and adjust schedules as needed. Some chillers at the college are programmed with a chiller wated reset. Lighting Systems: Interior lighting for the college is provided primarily by 4’, T8 fluorescent fixtures. Some 4', T12 fixtures and high intensity discharge (HID) fixtures serve areas of the college as well. Approximately 85% of the campus contains bi-level switching capabilities. Refer to Appendix C for a detailed lighting schedule by area. Lighting Control Systems: Occupancy sensors were found sporadically throughout offices, classrooms, and laboratories on the campus. No central lighting control system exists. Outdoor lighting is controlled by photocells. Security lighting serves the campus and is scheduled to be on 100% from dusk to midnight, then 50% from midnight to dawn. Parking structure lights were noted to be on timers. Process Loads ~ The college contains the following high energy process loads: ▪ Elevators that serve multi-level buildings. ▪ The Business/Communications Building holds a cafeteria with associated equipment including: several refrigerator units, one (1) walk-in refrigerator, and one (1) walk-in freezer. ▪ The Campus Center/HRC Building holds a dining area on the second floor and two (2) kitchens on the first floor with associated equipment including: several refrigerator units, two (2) walk-in refrigerators, and three (3) walk-in freezers. ▪ A water feature on the West Campus. ▪ A water fountain on the East Campus. ▪ Several vending machines located around the college. ▪ Stadium and field lighting, typically only enabled from dusk to midnight. Library Interior Lighting Typical Refrigeration Units TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. Typical Light Occupancy Sensor PAGE 5 SCE Job Number 1282 WEST CAMPUS OVERVIEW The Santa Barbara City College West Campus encompasses the following buildings: Bldg Bldg Name BC C DM/GT FO IDC L/LRC Business/Communication Center Child Center Drama/Music & Gavin Theatre Facilities & Operations Interdisciplinary Center Luria Library/Learning Resource Center Floor Area (sq ft) 35,466 6,375 46,325 2,880 39,147 52,327 Occupancy Type Class/Café Child Care Theatre/Class Office/Garage Class/Office Library College Map: West Campus Buildings Highlighted Existing Systems: The electrical demand for the facility is the result of a variety of electrical loads within the building. These systems are noted as having potential for Demand Reduction. Refer to the Equipment List and Layout in Appendix A for details. HVAC ~ Chilled Water Systems: The West Campus has three (3) buildings that are served by a self-contained chiller plant. These chiller plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below details specific building chiller plants: Equipment Associated Bldg Equipment Qty Notes Served Pump Qty BC Air-Cooled Chiller 1 AHU's/Fan Coils 2 IDC 2 AHU's/Fan Coils Air-Cooled Chiller 1 L/LRC Air-Cooled Chiller 2 VAV AHU's 2 Redundant TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 5 SCE Job Number 1282 EAST CAMPUS OVERVIEW HVAC ~ Heating Hot Water Systems: The West Campus has three (3) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below details specific building boiler plants: Equipment Associated Bldg Equipment Qty Notes Served Pump Qty BC 1 Rooftop AHU's Gas Boiler 2 IDC Gas Boiler 1 VAV AHU/Fan Coils 1 L/LRC 1 Gas Boiler VAV AHU's 2 HVAC ~ Air-Side Systems: The buildings with chiller and boiler plants are served by fan coils, constant air volume (CAV), and variable air volume (VAV) AHU's. The other buildings are conditioned primarily by direct expansion (DX) units: Bldg BC BC C C C DM/GT DM/GT DM/GT DM/GT FO IDC IDC IDC L/LRC Equipment Rooftop AHU's Fan Coils Ht Furnace Pckg Unit Pckg Gas/Elect Pckg Heat Pump Pckg Gas/Elect Split Sys Fan Coil Heat Pumps Packaged DX VAV AHU CAV AHU Fan Coils VAV AHU's Qty 8 21 1 1 1 4 2 5 10 1 1 1 4 1 Areas Served Flr 3, Kitchen, Rm232 Flrs 1/2 Major Rms Major Rms Major Rms Major Rms Changing Rms Auditorium/Theatre Varies Varies Offices/Conference Int. Rms - Flrs 1/2 Hallways Some Rms - Flr 3 All major rooms Drama/Music Building LRC AHU Sensor Readings TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. Notes Htg Only Some Htg only IDC Building BC Air-Cooled Chiller PAGE 6 SCE Job Number 1282 EAST CAMPUS OVERVIEW The Santa Barbara City College East Campus encompasses the following buildings: Bldg Bldg Name A CBS CC EBS HRC H IE MTBLDG OE PE PS PS SS Administration Bookstore Campus Center Earth & Biological Sciences Hotel/Restaurant/Culinary Humanities International Education Center Marine Technology Occupational Education Physical Education/Sports Pavilion Physical Science Physical Science Lecture Student Services Floor Area (sq ft) 76,454 18,283 30,384 30,623 5,591 39,912 4,406 8,208 18,389 64,894 22,767 3,883 43,038 Occupancy Type Offices Retail Dining/Kitchen/Class Class/Lab Dining/Kitchen/Class Class/Office/Studio Class Class/Office/Marine Class/Office/Garage Gymnasium/Activity Class/Office Lecture Offices College Map: East Campus Buildings Highlighted Existing Systems: The electrical demand for the facility is the result of a variety of electrical loads within the building. These systems are noted as having potential for Demand Reduction. Refer to the Equipment List and Layout in Appendix A for details. HVAC ~ Chilled Water Systems: The East Campus has five (5) buildings that are served by a self-contained chiller plant. These chiller plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below details specific building chiller plants: Equipment Associated Bldg Equipment Qty Notes Served Pump Qty A Air-Cooled Chiller 1 AHU's 3, 4, 5 2 EBS Air-Cooled Chiller 1 AHU's 2 H Air-Cooled Chiller 1 AHU's/Fan Coils 1 OE Air-Cooled Chiller 1 AHU's 1 SS Air-Cooled Chiller 2 AHU's 2 TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 7 SCE Job Number 1282 EAST CAMPUS OVERVIEW HVAC ~ Heating Hot Water Systems: The East Campus has seven (7) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below details specific building boiler plants: Equipment Associated Bldg Equipment Qty Notes Served Pump Qty A Gas Boiler 2 AHU's 2 Gas Boiler AHU's 2 CC/HRC 2 EBS Gas Boiler 1 VAV AHU/Fan Coils 2 H Gas Boiler 2 AHU's/Fan Coils 1 OE 1 Gas Boiler AHU 2 PE Gas Boiler 1 AHU 2 SS Gas Boiler 2 AHU's 2 HVAC ~ Air-Side Systems: East Campus buildings are served by a combination of DX units, hydronic constant air volume (CAV), and variable air volume (VAV) AHU's. Specific building air-side equipment is detailed below: Bldg Equipment A A A A A CBS CC/HRC CC/HRC CC/HRC CC/HRC CC/HRC EBS EBS EBS H H H MTBLDG OE OE OE PE PE PS SS VAV VAV Split Heat Pumps Split System Hydronic Fan Coils Gas/Elect Split Sys AHU Split Heat Pumps Pckg Unit Htg/Clg Unit Split System VAV VAV Fan Coils AHU Split Sys Fan Coils Split Sys Fan Coils Gas Furnace AHU Multi-Zone AHU Fan Coils AHU Pckg HP Split Sys Fan Coils AHU Qty 2 3 13 4 2 7 1 4 1 3 1 5 5 11 3 3 1 3 4 1 1 4 8 12 3 Areas Served Notes Flrs 1 and 2 Flrs 1 and 2 Varies Server Rooms Server Rooms All major areas Flrs 1 and 2 Offices/Class Cyber Center Lobby/Office/Class Kitchen Major areas Major areas Major areas Major areas Some flr 3 rooms Server Rm Offices Shops/Studio/Media Drafting Rms Offices Gym Offices Major areas Major areas Htg Only Clg and Htg EBS Rooftop Equipment TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. Economizers Htg Only Clg Only Htg Only Htg Only Htg Only Student Services Boilers PAGE 7 SCE Job Number 1282 PORTABLE BUILDING OVERVIEW Approximately fifty (50) portable buildings are located on the Santa Barbara City College. These units serve mostly as classrooms, although some serve as offices. College Map: Portable Buildings Highlighted Existing Systems: The electrical demand for the portable units is the result of a variety of electrical loads within the building. These systems are noted as having potential for Demand Reduction. HVAC Overview: The portables at the Santa Barbara City College are conditioned by wall mounted packaged heat pumps that are 5 tons or less of cooling. These units are operated via indoor thermostats. None of the portable packaged heat pumps can be accessed by the college JCI system. Lighting Systems: Interior lighting for portable buildings is provided primarily by 4’, 2-lamp T8 fluorescent fixtures. Refer to Appendix C for a detailed lighting schedule by area. Lighting Control Systems: The portable buildings are not typically equipped with occupancy sensors. The portable buildings contain bi-level switching capabilities in applicable areas to comply with Title 24 Energy Standards. Lighting in portable buildings were noted to typically be off when area was unoccupied. Process Loads ~ The portable buildings contains the following high energy process loads: ▪ Portable buildings serving as classrooms are equipped with overhead projectors. ▪ Some portable buildings have several desktop computers. Portable Unit Package Heat Pumps TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. Portable Unit Interior PAGE 8 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 1 : Chilled Water Supply Temperature Reset Chillers operate more efficiently at higher chilled water temperatures. Raising the chilled water supply temperature by 4ºF (44ºF to 48ºF) for all buildings served by a chiller plant during a demand response period is recommended. Projected Peak Demand Savings: Average Demand Reduction = 14.2 kW (0.9% of facility peak) Estimated Average Savings* = $61 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: Building control system programming is required to automate this measure. ▪ Estimated Controls and Control and Programming Cost: $17,000 ▪ Available Incentive Amount: 14.2 kW x $300/kW = $4,260 (Fully Automated) Student Services Chiller Plant * Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 9 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 2: Space Temperature Reset 72°F to 76°F Buildings consume less space cooling energy the closer their indoor temperature control setpoints are to outside ambient conditions. Raising the space temperature set point by 4ºF (72ºF to 76ºF) for all areas within the building that can tolerate higher temperatures during peak demand periods is recommended. These include conditoned lobbies, offices, classrooms, and all other non-laboratory and non-data center occupancies. Sensitivie laboratory and data center areas were not included in calculating the savings of this measure. Projected Peak Demand Savings: Average Demand Reduction = 340.9 kW (20.5% of facility peak) Estimated Average Savings* = $1,456 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: Additional DDC programming is required to automate this measure. Including DDC control of portable buildings is also required. The addition of a global setpoint adjustment control strategy is recommended. ▪ Estimated Portable Controls Cost: $62,500 ▪ Estimated Control and Programming Cost: $10,000 ▪ Available Incentive Amount: 340.9 kW x $300/kW = $102,270 (Fully Automated) Typical Campus Facility Wall Thermostat * Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 10 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 3: Data Center Temperature Reset 70°F to 78°F The Santa Barbara City College campus contains server rooms that is kept at approximately 70ºF. The ASHRAE 2008 Environmental Guidelines for Datacomm Equipment recommends data centers operate between 64.4ºF and 80.6ºF. Raising the space temperature of the rooms will decrease the cooling load required from the fan coil system serving the space. It is recommended to raise the server room temperature set points by 8ºF (70ºF to 78ºF) during a demand response period. Projected Peak Demand Savings: Average Demand Reduction = 2.4 kW (0.1% of facility peak) Estimated Average Savings* = $10 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: Additional DDC programming is required to automate this measure. The addition of a global setpoint adjustment control strategy is recommended. ▪ Estimated Control and Programming Cost: $4,000 ▪ Available Incentive Amount: 2.4 kW x $300/kW = $720 (Fully Automated) Data Center AHU Thermostat Controller * Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 11 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 4 : Heating Hot Water Pump Shutdown Heating hot water (HHW) is supplied to the air handling units on campus by approximately fifteen (15) alternating hp pumps, several of which are alternating. Demand response events historically occur on the hottest summer days when heating is not needed for space temperature or humidity control. Shutdown of all non-critical HHW pumps during a demand response period is recommended. Projected Peak Demand Savings: Average Demand Reduction = 9.2 kW (0.6% of facility peak) Estimated Average Savings* = $39 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: Additional building control system programming is required to automate this measure. ▪ Estimated Control and Programming Cost: $6,000 ▪ Available Incentive Amount: 9.2 kW x $300/kW = $2,760 (Fully Automated) Typical Campus HHW Pumps * Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 12 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 5 : Lighting Reduction Space lighting reduction results in direct peak kW savings and contributes to reduced heat loads and HVAC energy in conditioned spaces. Depending on the number of fixtures or lamps, a 33% or 50% reduction of lighting in non-classroom areas is recommended during a demand response. Refer to Appendix C for a detailed lighting reduction schedule by area. Projected Peak Demand Savings: Average Demand Reduction = 113.5 kW (6.8% of facility peak) Estimated Average Savings* = $485 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: Currently, approximately 85% of the campus has bi-level switching capability. A lighting rewire in the remaining 15% of the building is required to implement this measure. The implementation of a lighting control system to include individual control of each lighting circuit to be shutdown is necessary to automate this measure. ▪ Estimated Lighting Rewire Cost: $11,000 ▪ Estimated Lighting Control System Cost: $40,000 ▪ Available Incentive Amount: 113.5 kW x $300/kW = $34,050 (Fully Automated) Typical Campus Indoor Lighting * Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 13 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 6 : Fountain Pump Shutdown There are two (2) outdoor water fountains located on the campus. One (1) pump serves a water feature on the West Campus, and one (1) pump serves a water fountain on the East Campus. Each fountain is served by a continuously operating pump. Shutdown of the two (2) fountain pumps during a demand response event is recommended. Projected Peak Demand Savings: Average Demand Reduction = 3.2 kW (0.2% of facility peak) Estimated Average Savings* = $13 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: The addition of on/off control of the fountain pumps through the building's DDC system is recommended. ▪ Estimated Control and Programming Cost: $4,000 ▪ Available Incentive Amount: 3.2 kW x $300/kW = $960 (Fully Automated) West Campus Water Feature * Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 14 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 7 : Pre-Cool Refrigeration Spaces Many of the dining facilities at the Santa Barbara City College contain walk-in freezers and walk-in refrigerators with remote compressors. The allowable temperatures within the freezers and refrigerators are 0°F to 17°F and 35°F to 41°F, respectively. The following strategy is recommended during a demand response event: ▪ Pre-cool freezers and refrigerators to the minimum allowed temperature prior to a demand response event. ▪ Reset the freezers/refrigerators to their maximum allowable setpoints and let them float while the compressors idle. Projected Peak Demand Savings: Average Demand Reduction = 2.8 kW (0.2% of facility peak) Estimated Average Savings* = $12 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: The connection of the refrigerators/freezers temperature control system to the proposed DDC network is recommended to automate this measure. ▪ Estimated Control and Programming Cost: $20,000 ▪ Available Incentive Amount: 2.8 kW x $300/kW = $840 (Fully Automated) Typical Campus Walk-In Condenser Unit * Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 15 SCE Job Number 1282 TECHNICAL ANALYSIS Demand Response Measure # 8 : Beverage Vending Machine Compressor Shutdown There are multiple outdoor vending machines located throughout the campus, as well as several indoor vending machines/refrigerators at the main dining areas. Approximately thirty (30) total vending machines/refrigerators are located throughout the campus. The vending machine compressor runs continuously to maintain a cool temperature for the beverages. Shutdown of all vending machine compressors during a demand response period is recommended. Projected Peak Demand Savings: Average Demand Reduction = 11.1 kW (0.7% of facility peak) Estimated Average Savings* = $47 per event Refer to Appendix C for Calculations. System Modification Requirements and Automation Opportunities: The addition of on/off control for the vending machines through the existing DDC system is recommended to automate this measure. ▪ Estimated Controls Cost: $15,000 ▪ Available Incentive Amount: 11.1 kW x $300/kW = $3,330 (Fully Automated) Typical Campus Outdoor Vending Machines * Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM) measure implementation period. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 16 SCE Job Number 1282 ENERGY EFFICIENCY OPPORTUNITIES During the course of our investigation we observed several conditions that warrant additional analysis. In some cases, these items have potential for additional kW reduction; while in other cases, they have potential for energy conservation. Although these items are outside the scope of the SDG&E TA/TI Technical Incentive Program, they have significant potential for improving the efficiency of the facility and can assist in electrical demand reduction. Further investigation is required to determine potential energy savings. Energy Efficiency Measures identified for Santa Barbara City College are summarized as follows: HVAC Opportunities EE Meas #1: Chiller VFD Installation and Sequencing Optimization: Currently, the speed of the chillers cannot modulate depending on the electrical demand load due to the lack of variable frequency drives. Variable speed chillers often operate more efficiently together at part load conditions than alone at full speed. Additionally, variable speed chillers experience significant increases in efficiency as their CHWS temperature increases. An investigation to determine the cost and payback of installing a chiller VFD to optimize chiller operation and set point control is recommended. EE Meas #2: CHW Supply Temperature Reset: The Santa Barbara City College is located in a climate that often has cool and hot temperatures, even within the same day. By raising the supply temperature of chilled water, chillers use less energy to chill the water when the cooling load is below its designed value. Additionally, chillers operate more efficiently at higher chilled water temperatures. It is recommended that the feasibility of implementing a chilled water supply reset is further investigated. EE Meas #3: Boiler Outside Air Reset and Lockout: Heating hot water (HHW) is supplied to the air handling units on campus by multiple boilers and associated pumps. Due to the intermittent climate of the college, energy can be saved by shutting down HHW systems when the outside air temperatures are high or when a specific building becomes unoccupied. Further investigation of the feasibility of implementing a HHW boiler outside air reset and lockout is EE Meas #4: Convert CAV AHU's to VAV Systems: Currently, select buildings at the college are served by CAV AHU's which run continously throughout the day regardless of the airflow needed to satisfy the heat loads. Variable air volume systems are able to save energy by reducing airflow during part-load conditions to the minimum amount required to maintain space temperatures. Converting the AHU's in each building to variable air volume systems is recommended. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 17 SCE Job Number 1282 ENERGY EFFICIENCY MEASURES OPPORTUNITIES HVAC Opportunities EE Meas #5: AHU Economizer Repair: On cooler days, the economizers save energy by modulating to the open position for "free cooling". On warmer days, the economizers modulate to the minimum outside air intake position, saving energy by cooling the least amount of outside air required. Further investigation to locate and repair economizers and related controls is recommended for energy savings. EE Meas #6: Fluorescent Lighting Upgrade: Interior lighting in buildings on the campus is provided primarily by 32W T8 fluorescent fixtures. Currently 25W T8 lamps produce only slightly less usable light while consuming approximately 22% less energy. An upgrade of all 32W T8 lamps to 25W T8 lamps would result in energy savings. EE Meas #7: Upgrade Tint on Windows: Exterior windows of select building are mostly tinted with outdated film. Some relatively new portables have film that is still effective. Windows with new film that reflects solar radiation can drastically reduce a buildings cooling needs and increase occupant comfort. Further investigation of the cost and payback of upgrading the window tint is recommended for the college. EE Meas #8: Parking Structure Lighting Replacement and Controls: The parking structure and parking lots are currently provided lighting by high intensity discharge (HID) lighting fixtures. Bi-level induction and LED fixtures equipped with occupancy sensors are more efficient and partially reduce power during unoccupied times while still providing minimum lighting requirements. The upgrade of all parking lights and the installation of bi-level controls is recommended. EE Meas #9: Vending Machine Occupancy Controls Cold beverage vending machines consume power 24 hours a day to keep items a certain temperature and to operate electronics and lights. Specialized vending machine controllers with occupancy sensors are available that automatically reduce vending machine energy consumption during periods of low use. By monitoring the product temperature, room temperature, and activity level, these devices can save up to 50% on consumption. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 18 SCE Job Number 1282 ENERGY EFFICIENCY MEASURES OPPORTUNITIES HVAC Opportunities EE Meas #10: Walk-In Cooler Evaporator Controllers: The air in the walk-in coolers in the kitchen is cooled by forced-circulation evaporators containing propeller fans. These fans typically run continuously despite cooling requirements of the space. Controllers can be installed to slow these fans when full-speed operation is unnecessary and lead to 10% to 60% fan energy reduction. EE Meas #11: Computer Power Management: Many computers and monitors are left on throughout the day and night, even though the computers are used infrequently. Applying a power reduction schedule to these computers and monitors would significantly reduce energy use. Under this program, monitors switch to low power mode after 15 minutes of inactivity. This program is recommended for computers located in areas with set occupancies, such as offices, conference rooms, and computer classrooms. EE Meas #12: Variable Speed Kitchen Exhaust Hood Fan Controller: Santa Barbara City College contains a kitchens with associated kitchen hoods. These hoods are typically operating during times when the kitchen is occupied. Through advanced heat and smoke monitoring, retrofit VFD kits are now available for kitchen hoods which can reduce airflow by as much as 30% during idle periods when cooking surfaces are not being activated. EE Meas #13: Window/Door HVAC Interlock for Classrooms: Windows and doors of some exterior zones at the college were found to be open. The heating and cooling energy of HVAC equipment can be compromised by letting in outside air to conditioned rooms. Installing sensors on exterior doors and windows that shut off HVAC equipment serving that room when open are available. Further investigation of the cost and payback of installing window/door HVAC sensors is recommended for the college. TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 19 SCE Job Number 1282 Conclusion Demand Response Measures Summary: During the course of our investigation, a total of eight (8) demand response measures were identified. The proposed average on-peak reduction in kW demand based on the demand response measures addressed in this Technical Audit Report accounts for 30% of existing facility peak demand. A summary of the savings and incentives is shown below. Demand Response Measure Summary Total Average On-Peak Reduction Estimated Average Savings (per event) Incentive for SemiAutomated DR Implementation Incentive for Fully Automated DR Implementation 497 kW $2,123 $62,125 $149,100 TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM © 2013 SC ENGINEERS, INC. PAGE 20 SCE Job Number 1282 APPENDIX APPENDIX "A" - Equipment Lists TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 © 2013 SC ENGINEERS, INC. "A" Santa Barbara City College Equipment List Description Serves Model Capacity Two (2) Trane Chillers (2) CHW Pumps Boiler Raypak Air Handler # I Air Handler It 2. Air Handler # 3 Trane heat pump # 1 Trane heat pump # 2 Trane heat pump # 3 Pomona Air unit # 1 Pomona Air unit # 2 Boiler Learning Resource Center Learning Resource Center Learning Resource Center Library 1st floor Library 2nd floor Learning Resource Center Tutor area of LRC Math lab Kia lab LRC LRC LRC M # H163ACCCRRCBA Model # 39ED36 Model It 39ED36 Model # 39ED36 m # WCH180B400EA m # WCH060C400BC m # WCH060C400BC m # SACC3004404E6 m # SACC300U404E16 m # H1631ACCCRRCBA 15/7.5 Hp 20/10 Hp 15/7.5 Hp 180,000 btu 60,000 btu 60,000 btu 1.5 Hp 1.5 Hp 1.5 Hp Exhaust fans # 1 Exhaust fans # 2 Exhaust fans # 3 Exhaust fans # 4 Exhaust fans # 5 Exhaust fans # 6 Heat Pump PAC Heat Pump PAC LRC LRC LRC LRC LRC LRC roof LRC Math lab Kia Lab Rm #001 LRC 2nd Level LRC LRC Roof LRC Roof model # GB214 model # GB14-4 model # GB94 model # GB84 model # GB305 model # GB21-5 WCH180B400EA WCH060C400BC WCH060C400BC SACC 3004 404 E6 SACC 300U 404 E16 # 1510 Pump GB214 GB-14-4 hp 1/4 hp 1/4 hp 1/4 hp 1/4 hp 1/4 hp 1/4 hp 3 hp 3/4 hp 3/4 hp 3/4 hp 3/4 hp 1 1/2 hp 1/4 hp 1/4 AC Split Indoor Blower #1 AC Split Indoor Blower #2 Hot Water Pump for Heat EF #1 EF #2 120 Tons 5 Hp /Each EF #3 EF #4 EF #5 EF #6 FC FC FC FC Rooftop AH 1 AH 2 Chiller Hot Water Boiler + Pump + Motor EF #1 EF #2 Air Compressor Trane Chiller Cold Water Pump AH #1 La Salle AH #2 La Salle EF Pump Pump AH #1 CFU #1 AH #2 AH # 3 AH #4 AH #5 AH #6 AH #7 AH #8 Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil LRC Roof LRC Roof LRC Roof LRC Roof IDC #313 IDC #329 IDC #317 IDC #325 all of bldg IDC IDC Roof IDC bldg Roof Roof bathrooms Exhaust IDC Lite Storage IDC Lite Storage CHW IDC IDC Hallway (all 3 flrs) Rm #235 GB94 GB84 GB 30 5 GB 21 5 Trane Trane Trane Trane LLRT-600 LLRT-600 CGADC259ABAIGHRTY H1414ACCCHCBX N/A SX 205B CIS075603 CGADC254ABAIGHRTY B&G LLRT-600 LLRT-600 BL Chiller West Side BLC Bldg Lunch 3? Snack Bar BC Forum & 237 301 302 Hallway 315 314 313 115 Office 116 Office 117 Office 109 108 106 105 101 214 203 Copy Room Lounge 215-219 30GN 060 600KA 39LF1061CA1129L CAB-4 39LF1101CA1134L 39LC1031CA1124-R 39LC1061CA1124-I 39LG1031DA1121-R 39LC1061CA1124L 39LC1061CA1124R 39LC106CA1124R 42CEAO3DRCY5AYYYYG 42CEAO3DRCY5AYYYYG 42CEAO3DRCY5AYYYYG 42CEAO3DRCY5AYYYYG 42CEAO3DRCY5AYYYYG 42CEAO3DRY5AYYYYG 42CEAO3DRCY5AYYYYG 42BHB12KD4L61010CAQ 42BHB08KC3R60710BAQ 42BHB12KD4R61110CAQ 42BHB12KD4R61110CAQ 805QIZD hp 1/4 hp 1/4 hp 1/2 hp 1/4 10.5 MBH, 1/15 Hp 10.5 MBH, 1/15 Hp 10.5 MBH, 1/15 Hp 10.5 MBH, 1/15 Hp hp 7.5 hp 5 hp 1 hp 2 hp 3/4 hp 2 hp 3/4 25 Tons hp 1 hp 7.5 & hp 5 hp 5 & hp 2 hp 3/4 hp 1/6? hp 1/2 hp 1 1/2 hp 3 hp 5 hp 3/4 hp 1 hp 3/4 hp 1 hp 1 hp 1 hp 1/30 hp 1/30 hp 1/30 hp 1/30 hp 1/30 hp 1/30 hp 1/30 hp 1/2 hp 1/3 hp 1/2 hp 1/2 Fan Coil Fan Coil Fan Coil Fan Coil HW Fan Coil Fan Coil Fan Coil #17 Fan Coil Fan Coil HW,CW Fan Coil Fan Coil CHWP (2) HWP EF EF EF Ht Pump Split OSA Fan Motor Heat Furnace Heat or Package Gas Electric Package 229 222 226 228 BL second flr 230 Hallway 2nd flr 141 237 224 Entry Lobby Area 104 Common Area 144 232 2nd flr mens + womens restroom Kitchen 114 electric room 312 112 phone room Child Center Child Center Children Center 42BHB08KCR360710BAQ 42BHB12KDR61110CAQ 42BHB08KC3R60710BAQ 42BHB0BKC3L6060BAQ 42BHB08K 42BHB08KC3L60808BAQ 42BHB08KC3R6060 42CEAO3DRCY5AYYYYG 42BHBIZKD4R61011CAQ 42BHBIZKD4L61011CAQ 42BHB16KD4R61514DAG KM378JM C535A 120 5QIB FC-120 485X-042080521AA East Side AH #1 AH #2 Boiler Fan Coil Split HP Fan Coil Split HP system Fan coil/Ht Pump Fan Coil #4 FC/HP #6 FC/HP #7 ADM Boiler Rm ADM Boiler Rm ADM Boiler Rm 123-124 Conference Room 130, A,B,C 123A 130 E,D 141 200 H,J,K, AA + Corridor N. part of offices 201 train room MCCAOZIUBOA MCCAOZIUBOO MCCAOZIUBOO FB4ANF024 NZAHD14A06C NZAHD16A06C NZAHD16A06C FC4BNF030 FC4BNF030 MUH09EW 805015D hp 1/3 hp 1/2 hp 1/3 hp 1/3 hp 1/3 hp 1/3 hp 1/3 hp 1/30 hp 1/2 hp 1/2 hp 3/4 hp 5 hp 3 hp 1/3 hp 3 hp 1 hp 1/6 hp 1/4 hp 1/4 7.5/3 Hp 10/3 Hp 2 ton 3 ton 3 1/2 tons hp 1/2, 4 ton hp 1/3 FC/HP Fan Coil Heat Pump Split HP-FC #5 DX-FC-7 (split Ht pump) A211 Return Fan A211 McQuay AH Unit 4 Pipe McQuay AH Unit 4 Pipe Hot + Cold Water Pumps Hot Water Boiler McQuay Chiller 4 stage EF EF EF EF EF EF EF #5 Upflo Gas + Electric Split Upflo Split Gas And Electric Upflo Gas + Electric Split Upflo Gas + Electric Split Down flo split Upflo split furnace Upflo Split Gas And Electric EF 1 & 2 Split system heat pump & AH mr sum Furnace 1 Furnace 2,3,4,7 Furnace 5 Furnace 6 Condensing Unit 2,3,4,5,7 Condensing Unit 6 do pg 50 Heat Pump #1 Heat Pump 2,4 Heat Pump 3 Fan Coil #1,2,4 Fan Coil #3 Condensate Pump #1-4 ACU #1 EF #1 EF #2 200 A,AA,B,C,D,E,F,G 210J Offices IT Tech A 210 D,E,F,G,H,I Tech offices A 210 A,B,K 3rd flr adm bldg Roof ADM 1st flr adm digital arts 2nd flr adm nurses flr A211 McQuay 1 & 2 A211 McQuays A211 1st 2nd flr S.E. wing A Bldg Rm 200-2001 Mkens + Womens Restroom 236, 242 223 217 A210 A + B Lower Flr Storage Work RM Lower Lvl area in front of stairs Main flr by atm Main flr clothes and dressing room area Lower lvl bathroom + front of same flr Acct offices Left side of main flr roof book store Apple computer Rm store Campus Center 2nd flr Campus Center 2nd flr Campus Center 2nd flr FC4BNF048 FC4BNF030 GHC048SA WZAHDI0A06C HV ARRI ZOO CVB ROS00CLY H3 1083 AGZ090B5527 U9054 FG1210 FG1209 FG1013 FC111 58GSC045-GB 5GSC080-LB 58GSC080-LB 58GSC080-LB 58DHC075-JC 58GSC045-GB 58GSC080-LB LB-145 PUH36EK & PLH36FK P4USD P4USD PICC-D P4USD HICP060 HICF036 EIFH018 EIFH024 EIFH030 NIFAD10 NIFAD10 VGM-15ULS 48 MA 030 NAT GB-130 BSQ-90 hp 3/4 hp 1/3 4 ton, hp 3/4 2 ton, hp 1/3 7.5 Hp 3 Hp hp 20 hp 15 hp 1.5 1,000 BTUH In, 880 BTUH Out hp 1/2 hp 1/2 hp 1/3 hp 1/6 hp 1/12 hp 1/12 hp 1/3 hp 1/10 5 ton, hp 1/4 5 ton, hp 1/4 5 ton, hp 1/4 5 ton, hp 1/4 3 ton, hp 1/4 5 ton, hp 1/4 hp 1/4 47 MBH Out, 57 MBH In 90 MBH In, 73 MBH Out 90 MBH In, 73 MBH Out 47 MBH Out, 57 MBH In 60 MBH 36 MBH 19 mbh tot,14.9 MBH sens, 17.8 mb 23 mbh tot,17.9 mbh sens, 20.4 mb 29 mbh tot,22.4 mbh sens,24.6 mbh hp 1/3 hp 1/3 hp 1/50 540000 btu Heat in, 405000 btu hea hp 1/4 hp 1/3 EF #3 E #1 E#2 E#3 E#4 E#5 E#6 Steam boiler trane air handler In Line duct furnaces (2) MUA #1 MUA #2 EF Split System Ht pump Condensor heat pump Split System ht pump Split System ht pump Condensor heat pump Split System ht pump Condensor heat pump Make up air blower fan Split Heat Pump Roof gas electric pac Roof top pac multi zone Exh Up Blast Fan MUAU Gas Heat pac roof top EF EF-1 EF #2 Make Up Air WC/ duct heater Campus Center 2nd flr kitchen make up Range hood Toilet exhaust Toilet exhaust Refrigeration Dishwasher hood steam tables + dishwasher Cafeteria Cafeteria 108 Mech room C.C. Bldg,116-121 HRC offices 116-121 HRC offices 122 124 Cafeteria + kitchen HVAC for kitchen food line Cyber Center Campus center offices kitchen kitchen Coffee & gourmet shop Snack shack kitchen kitchen kitchen BSQ-100 397 397 S-1507 AMER BLW S150D2 S-1507 15L MCCA02SHCCOOAAOAAOO HX400 8S MVE RM3517 YQN56C17D2072F BSQ-140QD FISA036R06A EIFH030506A EFISA030R06A FISA036R06A EFH030506A FISA030R06A EIFH024506A hp 1/4 hp 1 hp 1 1/2 hp 1/4 hp 1/4 hp 1/2 hp 1/2 645000/322500 btu? hp 7.5 400000/320000 btu? hp 2 hp 1/2 hp 1/2 2 1/2 tons hp 1/4, 2 1/2 tons 2 ton, hp 1/3 2 1/2 tons, hp 1/3 2 1/2 tons, hp 1/4 2 ton, hp 1/3 hp 1/4, 2 tons 5K213AG801 (and 307?) TTA090A300FA YCH120A3RL 48MA 030 330VCR ED1430 E3MPV15A1 CUBE 240 LMDG-QD LO3603 330LBB 4OOL hp 1 2 (ton?) 10 tons cool, 150000 & 120000 (btu?) 540000 & 405000 (btu?), hp 10 hp 2 hp 1.5 150000/120000 (btu?), hp 3 hp 1 1/2 hp 2 hp 1 1/2 400000/300000 (btu?), hp 2 Make Up Air/duct heater McQuay Chiller CWP Chiller Boiler LAARS Sup AH & Return AH AH #2 Sup fan and EF #3 AH #3 Sup fan & EF #4 AHU #4 & #5, McQuay AH #4 & 5 VAVU Fan coils (11) AH #1 AH#2 AH #3 FC/HP FC/HP FC/HP Boiler 1 Boiler 2 Chiller 1 CWP Chiller Lochinvar Boiler AH #1 Sup & Ret fan motors AH #2 Sup & Ret fan motors AH #3 Sup & Ret fan motors Chiller H Bldg HVAC boiler Hot Water Coil AH Cold, hot water coils AH Cold, hot water coils AH Hot water Boiler for 3rd flr fan coils Fan Coil CW & HW Fan Coil CH/HW Fan Coil CW/HW #3 Down flo Chiller Coil EF Dust Collector Dust Collector EF #2 EF #3 & 4 EF #5 EF #6 EF #7 kitchen Earth biology sciences mechanical Earth biology sciences mechanical Earth biology sciences mechanical Mech room 1st flr mech room 2nd flr mech room 3rd flr EBS Rm 309/301 Varies Varies EBS 3rd flr offices Humanities Bldg, 1st and 2nd flrs Humanities Bldg, 1st and 2nd flrs 3rd flr 334 335 336 AH #1,2,3 FC/HP #1,2,3 AH #1,2,3, FC/HP #1,2,3, FC2P Humanities HWP? 1st and 2nd flrs 1st and 2nd flrs 1st and 2nd flrs H bldg mech rm 1st flr 2nd flr 3rd flr 3rd flr ESC labs small room Big lab Big lab H 245 Electric Rm 1st flr 107 ceramics 107 ceramics TV room Exhaust System Exhaust System Exhaust System Exhaust System 4OOL ALS141CS27 PH1430EN21KNABXX FBOUO106000402 FBOUO106000402 CHO14FDAC RDS708BY Varies FALWSD Varies Fujitsu AOU36CLX American Standard American Standard Teledyne Laars Lochnivar Trane RTAA1254VT01AB000B B079A CHN2071 41 41 RTAA 1254, YT01 AB00B CHN2071 41 41 143495 60 BHW 4A2M 60 BHW 4ALM 60 BHW 4ALM DACD 1132 1800 1200 FS-222 FG-1807 FG-2405 FG-1807 FG-1807 400000/300000 (btu?), hp 2 hp 1 1/2, 141 ton (2 skrew) 10 hp hp 3, 1430000-1172000 hp 15 & hp 5 hp 15 & hp 3 hp 7 1/2 & ? hp 3 Varies Varies Varies 5 Hp 5 Hp 5 Hp 2.5 Tons 2.5 Tons 2.5 Tons 266 kBTU 266 kBTU 125 Tons hp 7.5 hp 2 hp 20, hp 5 hp 30, hp 5 hp 30, hp 5 hp 7 1/2, 125 tons hp 2 hp 20 hp 30 hp 30 266000 btu, hp 1/2 hp 3 hp 3 hp 3 hp 3 hp 1/2 hp 1/2 hp 1/6 hp 1/2 hp 1/4 hp 1/3 hp 1/4 hp 1/4 EF #8 AC AD Furnace #1 Furnace #2 Furnace #3 UH 2-5 UH 1,6-9 EF EF 2,3 EF EF Up flo gas furnace Up Flo Gas furnace Up flo gas furnace Liquid chiller AH #1 EF #1 AH #2 AH #3 AH #4 MZAH hot water AH on roof Horizontal AH, HW, CW coil Exhaust System marine tech marine tech marine tech marine tech marine tech marine tech marine tech marine tech, main flr bathroom OE 202 offices 203 OE OE bldg, transmission and engine shop OE bldg, transmission and engine shop bathrooms and storage digital photo studio media services drafting rooms 112/116 & 182 182, auto lab, trans shop, offices print shop Horizontal AH, HW, CW EF EF 2 EF 3 EF 4 EF 5 EF 6 auto lab Weld shop Weld shop Weld shop Weld shop Weld shop FG-1507 SYCT8-1 F-30 G81-165V G81-65-82V G81-65-82V JS2-3 JS3-3 G81-165V-2 G81-6582V-3 G81-6582V-3 30GA-020-530-3 Trane hp 1/6? hp 3/4 hp 1/2 165000 btu in, 132000 btu out, hp 3/4 65000 btu in, 52000 btu out,hp 1/3 65000 btu in, 52000 btu out,hp 1/3 24000 btuh 36000 btuh hp 1/4 hp 1/4 hp 1/3 hp 1/4 165000 btu in, 137000 btu out, hp 1 82000/65000 btu, hp 1/3 82000/65000 btu, hp 1/3 5/3 Hp Trane Trane Trane Trane IJ8224 RDS708BY 10 Hp Trane hp 5 hp 1 hp 1/4 hp 1/4 hp 1/4 hp 1/4 hp 1/2 4L220 4L220 4L220 3L220 3L350 hp 3/4 hp 10 EF 7 EF 8 EF 9 EF 10 EF 11 boiler-1 AH #1 AH #2 AH #3 Chiller #1 Chiller #2 Boiler 1 Cool motors hot water motors EF 1 & 2 EF 3 & 4 EF 5 SANYO split A/C Weld shop Weld shop Weld shop Weld shop Weld shop HWUH,HWHC SSB, 1st and 2nd flr south side 1st and 2nd flr south side 2nd flr middle AH 1/2/3 AH 1/2/3 AH 1/2/3 mens + womens 2nd flr mens + womens front bldg mens + womens restroom phone + computer Rm 3L340 3L350 3L340 3L340 3L350 WGB-1250 Trane Trane Trane Trane Trane CHN1441 Z-1/2BB 8-3/4BF ZAC 6-3/8BF CL1211 hp 1/2 hp 1/2 hp 1/2 hp 1/2 hp 1/2 1250 mbh in, 1000 mbh out 15/5 Hp 15/5 Hp 7.5 Hp 40 Tons 40 Tons 144000 btu, 120860 btu hp 7.5 hp 1 1/2 hp 1/2 hp 1/4 hp 1/2 12000 btu APPENDIX APPENDIX "B" - SCE Technical Analysis Forms TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 © 2013 SC ENGINEERS, INC. "B" 2012 Technical Assistance (TA) Technical Audit Report ABOUT THE TECHNICAL AUDIT REPORT Technical Audit Report (Form#2B) #2B) Technical Audit Report (Form This template is used to conduct a Demand Response Technical Audit for Southern California Edison’s (SCE) Technical Assistance (TA) Program. Unless specifically requested by SCE, Technical Audits should not be performed on additional service accounts. The Technical Audit Report can be General General Site SiteInformation Informationand andExecutive ExecutiveSummary Summary completed by doing the following: Provide Provide site sitespecific specificinformation informationforforallallsites sites • Complete the Customer & Engineer Certification form during the site visit. that received the technical audit. that received the technical audit. (Customer signature required) • Complete the Technical Audit Report (Form #2B). Complete each of the Demand Response Solution Recommendations Demand Response Solution following sections: (The 2B Report allows up Recommendations to 5 solutions) (The 2BProvide Reportdetails allows up to 5the solutions) regarding o Engineer Information recommendation. Provide details regarding the o Technical Audit Summary recommendation. o General Site Information and Executive Summary o Demand Response Solution Recommendations Solution # - Site # (Repeats to 5 sites per solution) o Solution – Site Which sites are Solution applicable# to- Site the aforementioned # recommendation? Provide details on how the Whichrecommendation sites are applicable to the aforementioned applies to each site. recommendation? Provide details on how the recommendation applies to each site. DO NOT PROVIDE THE TECHNICAL AUDIT REPORT TO THE CUSTOMER. SCE requires the audit be reviewed by the program verification engineer (PVE) prior to the SCE customer seeing the Solution Recommendations. Email the electric copy of this document and a scanned copy of the Customer & Engineer Certification form with the customer’s signature to AUTODR@sce.com. Note: This form is designed to identify a maximum of 5 solutions for 1 service account. If you exceed the space provided, please continue on an additional Form #2B. ENGINEER INFORMATION Engineering Firm Name SC Engineers, Inc. Engineer Name Frank Shadpour Mailing Address 17075 Via Del Campo, First Floor Mailing State CA Mailing City E-Mail San Diego administration@scengineers.n et Office Phone 858.946.0333 PE License # M23923 Mailing Zip 92127 Mobile Phone AUTO-DR TECHNICAL AUDIT SUMMARY Customer Name Santa Barbara City College SA# Site # Site Address Site City 000203611 1 721 Cliff Dr. Santa Barbara Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 2B Cost Portfolio (Project) ID# 1282-1930 # Hours for 2B # of Measures Total Avg. kW 8 497 Date(s) of 2B Page 1 of 15 2012 Technical Assistance (TA) Technical Audit Report Appendix Info (The TA and Auto-DR Technology Incentive Programs will not provide technology incentives for manual improvements to existing equipment, for load reduction enabled by the Customer’s behavior changes, or metering equipment): Site 1 Service Account # 000203611 Occupancy Operations Schedule EMS Industrial Controls GENERAL SITE INFORMATION Facility Type Campus 7am - 8pm AC Sq Ft 615,000 Occupancy %: No AC Sq Ft Total Sq Ft 615,000 90% The equipment operates primarily from 7:00am-8:00pm. The HVAC equipment for the main buildings at the Santa Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC system. The JCI system can be accessed through computers located in the Facilities & Operations building. The JCI system controls the majority of major HVAC equipment on campus: chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC equipment through the JCI system and timeclocks. Facility staff noted that they monitor buildings and adjust schedules as needed. Some chillers at the college are programmed with a chiller wated reset. IT Infrastructure The system can not be accessed remotely due to strict campus internt security. DRAS Interface Currently non-existent. Recommend interfacing with a Niagra AX JACE equipment with operating ADR equipment driver. Other Considerations PV panels shade a parking lot on the West Campus. Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 2 of 15 2012 Technical Assistance (TA) Technical Audit Report Site 1 Interview Summary Site Summary Energy System Summary EXECUTIVE SUMMARY A field investigation or the Santa Barbara City College was conducted on the days of 3rd of December, 2012, through 5th of December, 2012. Attendees included James McKechnie of SC Engineers and Julie Hendricks and Brad Gyll of Santa Barbara City College. HVAC, lighting, and process loads were indicated as most likely targets for demand response reduction. The Santa Barbara City College consists of approximately twenty (20) buildings consisting of approximately 550,000 sq. ft., approximately fifty (50) portable units consisting of approximately 62,500 sq. ft., a parking structure, several parking lots, and sporting fields. The campus is heavily occupied from 7:00am - 8:00pm as it hosts several evening classes in addition to a typical school day schedule. The majority of rooms consist of class/lecture and office occupancies. Other notable areas are the gymnasium located in the Physical Education building and the performance stages located in the Drama and Music building. These areas may hold additional events not associated directly with the college. HVAC ~ Control System: The HVAC equipment for the main buildings at the Santa Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC system. This system can be accessed through computers located in the Facilities & Operations building. The system can not be accessed remotely due to strict campus internet security. The JCI system controls most major HVAC equipment on campus: chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC equipment through the JCI system and timeclocks. Facility staff noted that they monitor buildings and adjust schedules as needed. Some chillers at the college are programmed with a chiller water reset. Lighting Systems: Interior lighting for the collegel is provided primarily by 4’, T8 fluorescent fixtures. Some 4', T12 fixtures and high intensity discharge (HID) fixtures serve areas of the college as well. Approximately 85% of the campus contains bi-level switching capabilities. Refer to Appendix C for a detailed lighting schedule by area. Lighting Control Systems: Occupancy sensors were found sporadically throughout offices, classrooms, and laboratories on the campus. No central lighting control system exists. Outdoor lighting is controlled by photocells. Security lighting serves the campus and is scheduled to be on 100% from dusk to midnight, then 50% from midnight to dawn. Parking structure lights were noted to be on timers. Process Loads ~ The campus contains the following high energy process loads: ▪ Multiple elevators that serve multi-level buildings ▪ The Business/Communications Building holds a cafeteria with associated equipment including: several refrigerator units, one (1) walk-in refrigerator, and one (1) walk-in freezer. Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 3 of 15 2012 Technical Assistance (TA) Technical Audit Report ▪ The Campus Center/HRC Building holds a dining area on the second floor and two (2) kitchens on the first floor with associated equipment including: several refrigerator units, two (2) walk-in refrigerator, and three (3) walk-in freezer. ▪ A water feature on the West Campus. ▪ A water fountain on the East Campus. ▪ Several vending machines located around the college. HVAC Overview: The portables at the Santa Barbara City College are conditioned by packaged heat pumps that are 5 tons or less of cooling. These units are operated via indoor thermostats. None of the portable packaged heat pumps can be accessed by the college JCI system. HVAC ~ Chilled Water Systems: The West Campus has three (3) buildings that are served by a self-contained chiller plant. The East Campus has seven (7) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. HVAC ~ Heating Hot Water Systems: The West Campus has three (3) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. The East Campus has seven (7) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. HVAC ~ Air-Side Systems: The buildings with chiller and boiler plants are served by fan coils, constant air volume (CAV), and variable air volume (VAV) AHU's. The other buildings are conditioned primarily by direct expansion (DX) units. East Campus buildings are served by a combination of DX units, hydronic constant air volume (CAV), and variable air volume (VAV) AHU's. Auto-DR Summary DR Measure # 1: DR Measure # 2: DR Measure # 3: DR Measure # 4: DR Measure # 5: DR Measure # 6: DR Measure # 7: DR Measure # 8: 11.1 kW HVAC - Chilled Water Supply Temperature Reset - 14.2 kW HVAC - Space Temperature Reset - 340.9 kW HVAC - Data Center Temperature Reset - 2.4 kW HVAC - Heating Hot Water Pump Shutdown - 9.2 kW Lighting - Lighting Reduction - 113.5 kW Process Load - Fountain Pump Shutdown - 3.2 kW Process Load - Pre-Cool Refrigeration Spaces - 2.8 kW Process Load - Beverage Vending Machine Compressor Shutdown - Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 4 of 15 2012 Technical Assistance (TA) Technical Audit Report Additional Information Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 5 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 1 HEATING, VENTILATION AND AIR CONDITIONING Response Type Auto-DR Strategy Defined in Strategy Details Strategy Details kW Reduction Calculation Load Factor Type and Code: HVAC System Optimization: DR-82993 Chillers operate more efficiently at higher chilled water temperatures. Raising the chilled water supply temperature by 4ºF (44ºF to 48ºF) for all buildings served by a chiller plant during a demand response period is recommended. The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. See Appendix D for detailed Trace 700 building simulation results. Trace 700 measures were modeled sequentially with the results of each measure used as the baseline for the following measure to include interactive effects. SOLUTION 1 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation 15 Max kW System Location Buildings: BC, IDC, L/LRC, A, EBS, H, OE, & SS Energy Usage System CHW System, see equipment list Avg. kW 14 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units 13 Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Circuit # N/A N/A Solutions Code Measured Amps N/A N/A Page 6 of 15 2012 Technical Assistance (TA) Technical Audit Report SOLUTION 1 – SITE 1 CONTINUED EE Opportunities (please include calculations of results) Recommended Reduction Time Cost Description and Breakdown Implementation Analysis/Barriers CHW supply temperature resets on a permanent basis can be implemented to save energy. Reset can be based on variables such as outside air, load, time of day, etc. The 4 hours of the DR event. ▪ Estimated Controls and Control and Programming Cost: $17,000 Building control system programming is required to automate this measure. Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 7 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 2 HEATING, VENTILATION AND AIR CONDITIONING Response Type Auto-DR Strategy Defined in Strategy Details Strategy Details kW Reduction Calculation Load Factor Type and Code HVAC System Optimization: DR-82993 Raising the space temperature set point by 4ºF (72ºF to 76ºF) for all areas within the building that can tolerate higher temperatures during peak demand periods is recommended. These include conditoned lobbies, offices, classrooms, and all other non-laboratory and non-data center occupancies. Sensitivie laboratory and data center areas were not included in calculating the savings of this measure. The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. The simulation results for an increase in the space temperature set point from 72°F to 76°F for the slected areas are shown below. See Appendix D for detailed building simulation results. Trace 700 measures were modeled sequentially with the results of each measure used as the baseline for the following measure to include interactive effects. SOLUTION 2 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation System Location Energy Usage System 765 Max kW All buildings but laboratories and data centers Central Cooling System, see equipment list 340 Avg. kW BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units Varies Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Circuit # N/A N/A Solutions Code Measured Amps N/A N/A Page 8 of 15 2012 Technical Assistance (TA) Technical Audit Report SOLUTION 2 – SITE 1 CONTINUED EE Opportunities (please include calculations of results) Recommended Reduction Time Implementing the space temperature reset on a permanent basis can save energy. The 4 hours of the DR event. ▪ Estimated Portable Controls Cost: $62,500 Cost Description and Breakdown ▪ Estimated Control and Programming Cost: $10,000 Implementation Analysis/Barriers Additional DDC programming is required to automate this measure. Including DDC control of portable buildings is also required. The addition of a global setpoint adjustment control strategy is recommended. Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 9 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 3 HEATING, VENTILATION AND AIR CONDITIONING Response Type Auto-DR Strategy Defined in Strategy Details Strategy Details kW Reduction Calculation Load Factor HVAC System Optimization: DR-82993 Type and Code The Santa Barbara City College campus contains server rooms that is kept at approximately 70ºF. The ASHRAE 2008 Environmental Guidelines for Datacomm Equipment recommends data centers operate between 64.4ºF and 80.6ºF. Raising the space temperature of the rooms will decrease the cooling load required from the fan coil system serving the space. The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. The simulation results for an increase in the space temperature set point from 70°F to 78°F for the data center areas are shown below. See Appendix D for detailed building simulation results. Trace 700 measures were modeled sequentially with the results of each measure used as the baseline for the following measure to include interactive effects. SOLUTION 3 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation 6 Max kW System Location Server Rooms Energy Usage System Central Cooling System, see equipment list Avg. kW 2 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units Varies Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Circuit # N/A N/A Solutions Code Measured Amps N/A N/A Page 10 of 15 2012 Technical Assistance (TA) Technical Audit Report SOLUTION 3 – SITE 1 CONTINUED EE Opportunities (please include calculations of results) Recommended Reduction Time Cost Description and Breakdown Implementation Analysis/Barriers The addition of a global setpoint adjustment control strategy is recommended. The 4 hours of the DR event. ▪ Estimated Control and Programming Cost: $4,000 Additional DDC programming is required to automate this measure. Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 11 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 4 HEATING, VENTILATION AND AIR CONDITIONING Response Type Auto-DR Type and Code Strategy Defined in Strategy Details HVAC System Optimization: DR-82993 Shutdown of all non-critical HHW pumps during a demand response period is recommended. Strategy Details kW Reduction Calculation Load Factor See calculations & supporting information. Refer to appendix C of report. 35% - See calculations & supporting information SOLUTION 4 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation Max kW 9 System Location Buildings: BC, IDC, L/LRC, A, CC/HRC, EBS, H, OE, PE & SS Energy Usage System HHW System, see equipment list Avg. kW 9 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units 15 Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Circuit # N/A N/A Solutions Code Measured Amps N/A N/A SOLUTION 4 – SITE 1 CONTINUED Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 12 of 15 2012 Technical Assistance (TA) Technical Audit Report EE Opportunities (please include calculations of results) Recommended Reduction Time Cost Description and Breakdown Implementation Analysis/Barriers Provide premium efficiency motors and VFD's to pump motors. Provide pump pressure reset. The 4 hours of the DR event. ▪ Estimated Control and Programming Cost: $6,000 Additional building control system programming is required to automate this measure. Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 13 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 5 HEATING, VENTILATION AND AIR CONDITIONING Auto-DR Strategy Defined in Strategy Details Strategy Details Depending on the number of fixtures or lamps, a 33% or 50% reduction of lighting in nonclassroom areas is recommended during a demand response. kW Reduction Calculation Load Factor Type and Code Lighting - Other: DR-62019 Response Type See calculations & supporting information. Refer to appendix C of report. Varies - See calculations & supporting information SOLUTION 5 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation 113 Max kW System Location All building spaces except classrooms Energy Usage System Lighting Avg. kW 113 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units N/A Running Amps N/A Unit ID N/A Horsepower N/A Max kW per Unit N/A Volts N/A Motor Efficiency N/A OR TYPE B - LIGHTING T Y P E B Floor # Varies Watts Per Fixture Varies Panel ID Room # Varies Volts Per Fixture Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Circuit # Varies Varies Solutions Code Measured Amps Varies Varies Page 14 of 15 2012 Technical Assistance (TA) Technical Audit Report SOLUTION 5 – SITE 1 CONTINUED EE Opportunities (please include calculations of results) Recommended Reduction Time The 4 hours of the DR event. ▪ Estimated Lighting Rewire Cost: $11,000 Cost Description and Breakdown ▪ Estimated Lighting Control System Cost: $40,000 Implementation Analysis/Barriers Currently, approximately 85% of the campus has bi-level switching capability. A lighting rewire in the remaining 15% of the building is required to implement this measure. The implementation of a lighting control system to include individual control of each lighting circuit to be shutdown is necessary to automate this measure. Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 15 of 15 2012 Technical Assistance (TA) Technical Audit Report ABOUT THE TECHNICAL AUDIT REPORT Technical Audit Report (Form#2B) #2B) Technical Audit Report (Form This template is used to conduct a Demand Response Technical Audit for Southern California Edison’s (SCE) Technical Assistance (TA) Program. Unless specifically requested by SCE, Technical Audits should not be performed on additional service accounts. The Technical Audit Report can be General General Site SiteInformation Informationand andExecutive ExecutiveSummary Summary completed by doing the following: Provide Provide site sitespecific specificinformation informationforforallallsites sites • Complete the Customer & Engineer Certification form during the site visit. that received the technical audit. that received the technical audit. (Customer signature required) • Complete the Technical Audit Report (Form #2B). Complete each of the Demand Response Solution Recommendations Demand Response Solution following sections: (The 2B Report allows up Recommendations to 5 solutions) (The 2BProvide Reportdetails allows up to 5the solutions) regarding o Engineer Information recommendation. Provide details regarding the o Technical Audit Summary recommendation. o General Site Information and Executive Summary o Demand Response Solution Recommendations Solution # - Site # (Repeats to 5 sites per solution) o Solution – Site Which sites are Solution applicable# to- Site the aforementioned # recommendation? Provide details on how the Whichrecommendation sites are applicable to the aforementioned applies to each site. recommendation? Provide details on how the recommendation applies to each site. DO NOT PROVIDE THE TECHNICAL AUDIT REPORT TO THE CUSTOMER. SCE requires the audit be reviewed by the program verification engineer (PVE) prior to the SCE customer seeing the Solution Recommendations. Email the electric copy of this document and a scanned copy of the Customer & Engineer Certification form with the customer’s signature to AUTODR@sce.com. Note: This form is designed to identify a maximum of 5 solutions for 1 service account. If you exceed the space provided, please continue on an additional Form #2B. ENGINEER INFORMATION Engineering Firm Name SC Engineers, Inc. Engineer Name Frank Shadpour Mailing Address 17075 Via Del Campo, First Floor Mailing State CA Mailing City E-Mail San Diego administration@scengineers.n et Office Phone 858.946.0333 PE License # M23923 Mailing Zip 92127 Mobile Phone AUTO-DR TECHNICAL AUDIT SUMMARY Customer Name Santa Barbara City College SA# Site # Site Address Site City 000203611 1 721 Cliff Dr. Santa Barbara Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 2B Cost Portfolio (Project) ID# 1282-1930 # Hours for 2B # of Measures Total Avg. kW 8 497 Date(s) of 2B Page 1 of 15 2012 Technical Assistance (TA) Technical Audit Report Appendix Info (The TA and Auto-DR Technology Incentive Programs will not provide technology incentives for manual improvements to existing equipment, for load reduction enabled by the Customer’s behavior changes, or metering equipment): Site 1 Service Account # 000203611 Occupancy Operations Schedule EMS Industrial Controls GENERAL SITE INFORMATION Facility Type Campus 7am - 8pm AC Sq Ft 615,000 Occupancy %: No AC Sq Ft Total Sq Ft 615,000 90% The equipment operates primarily from 7:00am-8:00pm. The HVAC equipment for the main buildings at the Santa Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC system. The JCI system can be accessed through computers located in the Facilities & Operations building. The JCI system controls the majority of major HVAC equipment on campus: chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC equipment through the JCI system and timeclocks. Facility staff noted that they monitor buildings and adjust schedules as needed. Some chillers at the college are programmed with a chiller wated reset. IT Infrastructure The system can not be accessed remotely due to strict campus internt security. DRAS Interface Currently non-existent. Recommend interfacing with a Niagra AX JACE equipment with operating ADR equipment driver. Other Considerations PV panels shade a parking lot on the West Campus. Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 2 of 15 2012 Technical Assistance (TA) Technical Audit Report Site 1 Interview Summary Site Summary Energy System Summary EXECUTIVE SUMMARY A field investigation or the Santa Barbara City College was conducted on the days of 3rd of December, 2012, through 5th of December, 2012. Attendees included James McKechnie of SC Engineers and Julie Hendricks and Brad Gyll of Santa Barbara City College. HVAC, lighting, and process loads were indicated as most likely targets for demand response reduction. The Santa Barbara City College consists of approximately twenty (20) buildings consisting of approximately 550,000 sq. ft., approximately fifty (50) portable units consisting of approximately 62,500 sq. ft., a parking structure, several parking lots, and sporting fields. The campus is heavily occupied from 7:00am - 8:00pm as it hosts several evening classes in addition to a typical school day schedule. The majority of rooms consist of class/lecture and office occupancies. Other notable areas are the gymnasium located in the Physical Education building and the performance stages located in the Drama and Music building. These areas may hold additional events not associated directly with the college. HVAC ~ Control System: The HVAC equipment for the main buildings at the Santa Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC system. This system can be accessed through computers located in the Facilities & Operations building. The system can not be accessed remotely due to strict campus internet security. The JCI system controls most major HVAC equipment on campus: chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC equipment through the JCI system and timeclocks. Facility staff noted that they monitor buildings and adjust schedules as needed. Some chillers at the college are programmed with a chiller water reset. Lighting Systems: Interior lighting for the collegel is provided primarily by 4’, T8 fluorescent fixtures. Some 4', T12 fixtures and high intensity discharge (HID) fixtures serve areas of the college as well. Approximately 85% of the campus contains bi-level switching capabilities. Refer to Appendix C for a detailed lighting schedule by area. Lighting Control Systems: Occupancy sensors were found sporadically throughout offices, classrooms, and laboratories on the campus. No central lighting control system exists. Outdoor lighting is controlled by photocells. Security lighting serves the campus and is scheduled to be on 100% from dusk to midnight, then 50% from midnight to dawn. Parking structure lights were noted to be on timers. Process Loads ~ The campus contains the following high energy process loads: ▪ Multiple elevators that serve multi-level buildings ▪ The Business/Communications Building holds a cafeteria with associated equipment including: several refrigerator units, one (1) walk-in refrigerator, and one (1) walk-in freezer. Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 3 of 15 2012 Technical Assistance (TA) Technical Audit Report ▪ The Campus Center/HRC Building holds a dining area on the second floor and two (2) kitchens on the first floor with associated equipment including: several refrigerator units, two (2) walk-in refrigerator, and three (3) walk-in freezer. ▪ A water feature on the West Campus. ▪ A water fountain on the East Campus. ▪ Several vending machines located around the college. HVAC Overview: The portables at the Santa Barbara City College are conditioned by packaged heat pumps that are 5 tons or less of cooling. These units are operated via indoor thermostats. None of the portable packaged heat pumps can be accessed by the college JCI system. HVAC ~ Chilled Water Systems: The West Campus has three (3) buildings that are served by a self-contained chiller plant. The East Campus has seven (7) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. HVAC ~ Heating Hot Water Systems: The West Campus has three (3) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. The East Campus has seven (7) buildings that are served by a self-contained boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. HVAC ~ Air-Side Systems: The buildings with chiller and boiler plants are served by fan coils, constant air volume (CAV), and variable air volume (VAV) AHU's. The other buildings are conditioned primarily by direct expansion (DX) units. East Campus buildings are served by a combination of DX units, hydronic constant air volume (CAV), and variable air volume (VAV) AHU's. Auto-DR Summary DR Measure # 1: DR Measure # 2: DR Measure # 3: DR Measure # 4: DR Measure # 5: DR Measure # 6: DR Measure # 7: DR Measure # 8: 11.1 kW HVAC - Chilled Water Supply Temperature Reset - 14.2 kW HVAC - Space Temperature Reset - 340.9 kW HVAC - Data Center Temperature Reset - 2.4 kW HVAC - Heating Hot Water Pump Shutdown - 9.2 kW Lighting - Lighting Reduction - 113.5 kW Process Load - Fountain Pump Shutdown - 3.2 kW Process Load - Pre-Cool Refrigeration Spaces - 2.8 kW Process Load - Beverage Vending Machine Compressor Shutdown - Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 4 of 15 2012 Technical Assistance (TA) Technical Audit Report Additional Information Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 5 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 1 PROCESS Type and Code: Process Machinery-Other: DR30001 Response Type Auto-DR Strategy Turn off fountains and swimming pool pumps Strategy Details Fountain Pump Shutdown kW Reduction Calculation See calculations & supporting information. Refer to appendix C of report. Load Factor 90% - See calculations & supporting information SOLUTION 1 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation Max kW System Location Energy Usage System Avg. kW 3 One on east and one on west side of campus Fountain Systems, see calculations and supporting information 3 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units 2 Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Circuit # N/A N/A Solutions Code Measured Amps N/A N/A Page 6 of 15 2012 Technical Assistance (TA) Technical Audit Report SOLUTION 1 – SITE 1 CONTINUED EE Opportunities (please include calculations of results) Recommended Reduction Time The 4 hours of the DR event. Cost Description and Breakdown ▪ Estimated Control and Programming Cost: $4,000 Implementation Analysis/Barriers The addition of on/off control of the fountain pumps through the building's DDC system is recommended. Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 7 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 2 PROCESS Response Type Auto-DR Strategy Defined in Strategy Details Strategy Details Pre-Cool Refrigeration Spaces kW Reduction Calculation Load Factor Type and Code Process - Refrigeration Syst. Opt: DR-89124 See calculations & supporting information. Refer to appendix C of report. 85% - See calculations & supporting information SOLUTION 2 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation Max kW 2 System Location Buildings: CC, HRC, & SCA Energy Usage System Refrigeration Systems Avg. kW 2 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units 7 Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Circuit # N/A N/A Solutions Code Measured Amps N/A N/A SOLUTION 2 – SITE 1 CONTINUED Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 8 of 15 2012 Technical Assistance (TA) Technical Audit Report EE Opportunities (please include calculations of results) Provide evaporative unit controllers and EC motors. Recommended Reduction Time The 4 hours of the DR event. Cost Description and Breakdown ▪ Implementation Analysis/Barriers The connection of the refrigerators/freezers temperature control system to the proposed DDC network is recommended to automate this measure. Estimated Control and Programming Cost: $20,000 Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 9 of 15 2012 Technical Assistance (TA) Technical Audit Report AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS Solution 3 PROCESS Process Machinery-Other: DR30001 Response Type Auto-DR Type and Code Strategy Defined in Strategy Details Strategy Details Beverage Vending Machine Compressor Shutdown kW Reduction Calculation See calculations & supporting information. Refer to appendix C of report. Load Factor 30% - See calculations & supporting information SOLUTION 3 – SITE 1 Implementation 18 Days Time Hours of 2pm-6pm Operation Max kW 11 System Location Campus Wide Energy Usage System Vending Machines Avg. kW 11 BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS (ONLY Complete Type A or Type B) TYPE A – HVAC, PROCESS, CONTROLS T Y P E A # of Units 30 Running Amps Varies Unit ID Varies Horsepower Varies Max kW per Unit Varies Volts Varies Motor Efficiency Varies OR TYPE B - LIGHTING T Y P E B Floor # N/A Watts Per Fixture N/A Panel ID Room # N/A Volts Per Fixture Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Circuit # N/A N/A Solutions Code Measured Amps N/A N/A Page 10 of 15 2012 Technical Assistance (TA) Technical Audit Report SOLUTION 3 – SITE 1 CONTINUED EE Opportunities (please include calculations of results) Recommended Reduction Time The 4 hours of the DR event. Cost Description and Breakdown ▪ Implementation Analysis/Barriers The addition of on/off control for the vending machines through the existing DDC system is recommended to automate this measure. Estimated Controls Cost: $15,000 Additional Comments Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012 Page 11 of 15 APPENDIX APPENDIX "C" - Calculations and Supporting Information TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 © 2013 SC ENGINEERS, INC. "C" CALCULATIONS Demand Response Measure # 1: Chilled Water Supply Temperature Reset The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. Demand response measures were calculated sequentially with the results of each measure used as the baseline for the following measure to include interactive effects. A chilled water temperature reset was modeled for a 4°F CHW supply temperature increase (44°F to 48°F) in the facility. See Appendix D for detailed Trace 700 building simulation results. Effect of Demand Response on Peak Load 1,800 1,600 Facility Demand (kW) 1,400 1,200 1,000 800 600 400 200 0 Cooling Equip Cooling Tower Hour Fan Equip Pump Equip Misc Equip Heating Equip Base Utility Baseline 220.7 kW, 13.7% 15. kW, 0.9% 220.7 kW, 13.85% 285.2 kW, 17.7% 19.9 kW, 1.2% 95.9 kW, 6.0% 15. kW, 0.94% Lights 285.2 kW, 17.89% 19.9 kW, 1.25% 95.6 kW, 5.99% 304.7 kW, 18.9% 304.7 kW, 19.12% 653. kW, 40.96% Electric Peak Demand for Chilled Water Supply Temperature Reset 666.8 kW, 41.5% Electric Peak Demand for Baseline kW Reduction: 1,608.17 kW - 1,593.99 kW = 14.18 kW Baseline DR Measure #1 Demand Reduction 2:00PM 1597.6 kW 1583.4 kW 14.1 kW 3:00 PM 1696.1 kW 1681.2 kW 14.9 kW Peak Demand (kW) 4:00 PM 1687.1 kW 1671.8 kW 15.3 kW 5:00 PM 1624.0 kW 1609.6 kW 14.3 kW 6:00 PM 1436.2 kW 1424.0 kW 12.2 kW CALCULATIONS Demand Response Measure # 2: Space Temperature Reset 72°F to 76°F The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. Demand response measures were calculated sequentially with the results of each measure used as the baseline for the following measure to include interactive effects. The simulation results for an increase in the space temperature set point from 72°F to 76°F for the slected areas are shown below. See Appendix D for detailed building simulation results. Effect of Demand Response on Peak Load 2,500 Facility Demand (kW) 2,000 1,500 1,000 500 0 Cooling Equip Pump Equip Heating Equip 220.7 kW, 14% Cooling Tower Lights Base Utility 15. kW, 1% 285.2 kW, 18% 19.9 kW, 1% 95.9 kW, 6% Hour Fan Equip Misc Equip Chilled Water Supply Temperature Reset 112.2 kW, 9% 3.4 kW, 0% 15. kW, 1% 19.9 kW, 285.2 kW, 2% 23% 66.3 kW, 5% 304.7 kW, 19% 304.7 kW, 24% 460.6 kW, 36% 666.8 kW, 41% Electric Peak Demand for Chilled Water Supply Temperature Reset Electric Peak Demand for Space Temperature Reset kW Reduction: 1,608.17 kW - 1,267.30 kW = 340.88 kW Baseline DR Measure #1 Demand Reduction 2:00PM 1597.6 kW 832.1 kW 765.5 kW 3:00 PM 1696.1 kW 1249.9 kW 446.2 kW Peak Demand (kW) 4:00 PM 1687.1 kW 1444.3 kW 242.7 kW 5:00 PM 1624.0 kW 1430.0 kW 194.0 kW 6:00 PM 1436.2 kW 1380.2 kW 56.0 kW CALCULATIONS Demand Response Measure # 3: Data Center Temperature Reset 70°F to 78°F The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. Demand response measures were calculated sequentially with the results of each measure used as the baseline for the following measure to include interactive effects. The simulation results for an increase in the space temperature set point from 70°F to 78°F for the data center areas are shown below. See Appendix D for detailed building simulation results. Effect of Demand Response on Peak Load 2,500 Facility Demand (kW) 2,000 1,500 1,000 500 0 Hour Cooling Tower Lights Base Utility Cooling Equip Pump Equip Heating Equip 112.2 kW, 9% 19.9 kW, 2% 3.4 kW, 0% Fan Equip Misc Equip Space Temperature Reset 15. kW, 1% 285.2 kW, 23% 66.3 kW, 5% 19.9 kW, 2% 111.3 kW, 9% 3.4 kW, 0% 15. kW, 1% 285.2 kW, 23% 66.2 kW, 5% 304.7 kW, 24% 460.6 kW, 36% Electric Peak Demand for Space Temperature Reset 304.7 kW, 24% 459.2 kW, 36% Electric Peak Demand for Data Center Temperature Reset kW Reduction: 1,267.30 kW - 1,264.92 kW = 2.38 kW Baseline DR Measure #1 Demand Reduction 2:00PM 832.1 kW 826.0 kW 6.1 kW 3:00 PM 1249.9 kW 1248.7 kW 1.2 kW Peak Demand (kW) 4:00 PM 5:00 PM 1444.3 kW 1430.0 kW 1442.7 kW 1428.5 kW 1.7 kW 1.6 kW 6:00 PM 1380.2 kW 1378.9 kW 1.3 kW CALCULATIONS Demand Response Measure # 4: Demand Reduction by Heating Hot Water Pump Shutdown Current Manufacturer Equipment Qty HP GPM Ft. Head Load Factor Efficiency 15 2.0 254 75 35% 85% Demand Response Status Demand kW ON 9.2 kW Status Demand kW Pump kW Reduction OFF 0.0 kW 9.2 kW * Varies HHW Pumps Totals 15 * Current: [Demand kW] = [HP] x [Load Factor] x 0.7457 / [Efficiency] ** [Pump kW Reduction] = [Current Demand kW] - [Demand Response Demand kW] Notes: (1) Efficiency is based on motor size (HP) and Load Factor 9.2 kW ** 9.2 kW CALCULATIONS Demand Response Measure # 5: Demand Reduction by Lighting Reduction Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 3 Admin RECEPTIONIST RM 114 432MAXL 4 91.0 3 273 W 50% NO 137 W 4 Admin OFFICE 114A 432MAXL 4 91.0 2 182 W 50% NO 91 W 5 Admin OFFICE 114A 232MAXL 1 24.0 2 48 W 50% Yes 24 W 7 Admin OFFICE 114B 432MAXL 4 91.0 2 182 W 50% NO 91 W 182 W 9 Admin CONFRENCE 113-3 332MAXL 3 68.0 4 272 W 33% NO 10 Admin CONFRENCE 113-3 332MAXL 3 68.0 2 136 W 33% Yes 91 W 11 Admin OFFICE 113-2 332MAXL 3 68.0 4 272 W 33% NO 182 W 12 Admin OFFICE 113-1 332MAXL 3 68.0 4 272 W 33% NO 182 W 13 Admin OPEN OFFICE 113 332MAXL 3 68.0 4 272 W 33% NO 182 W 14 Admin OPEN OFFICE 113 332MAXL 3 68.0 2 136 W 33% Yes 91 W 15 Admin RECEPTIONIST RM 112A 432MAXL 4 91.0 4 364 W 50% NO 182 W 16 Admin OFFICE 111 232MAXN 2 52.0 2 104 W 50% Yes 52 W 17 Admin OFFICE 111 1 25.0 2 50 W 50% Yes 25 W 18 Admin OPEN OFFICE 110 432MAXL 4 91.0 6 546 W 50% NO 273 W 19 Admin WORK ROOM 150A 432MAXL 4 91.0 2 182 W 50% NO 91 W 22 Admin OFFICE 119A 232MAXH 2 70.0 2 140 W 50% Yes 70 W 23 Admin OFFICE 119B 232MAXH 2 70.0 2 140 W 50% Yes 70 W 24 Admin OFFICE 119C 232MAXH 2 70.0 2 140 W 50% Yes 70 W 25 Admin OFFICE 117 432MAXN 2 51.5 4 206 W 50% NO 103 W 26 Admin OFFICE 117A 432MAXN 2 51.5 4 206 W 50% NO 103 W 27 Admin OFFICE 117B 432MAXN 2 51.5 4 206 W 50% NO 103 W 29 Admin OFFICE 116A 432MAXN 2 51.5 4 206 W 50% NO 103 W 30 Admin OFFICE 116 432MAXN 2 51.5 4 206 W 50% NO 103 W 31 Admin HALLWAY #1 232MAXN 2 52.0 7 364 W 50% NO 182 W 32 Admin HALLWAY #1 232MAXN 2 52.0 2 104 W 50% Yes 52 W 34 Admin HALLWAY #2 232MAXN 2 52.0 6 312 W 50% NO 156 W 37 Admin PHONE RM BY 116 232MAXL 2 46.0 4 184 W 50% NO 92 W 39 Admin WAREHOUSE 121 232MAXN 2 52.0 15 780 W 50% NO 390 W 40 Admin OFFICE 122 432MAXN 2 51.5 4 206 W 50% NO 103 W 41 Admin OFFICE 123A 432MAXL 4 91.0 6 546 W 50% NO 273 W 42 Admin OFFICE 123A 432MAXL 4 91.0 1 91 W 50% NO 46 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 43 Admin OFFICE 124A 432MAXL 4 91.0 2 182 W 50% NO 91 W 44 Admin OFFICE 123 332MAXL 3 68.0 3 204 W 33% NO 137 W 45 Admin AUTO SHOP AREA 108 232MAXN 2 52.0 13 676 W 50% NO 338 W 46 Admin SHOP OFFICE 108C 232MAXL 2 46.0 2 92 W 50% Yes 46 W 48 Admin HALLWAY #4 232MAXN 2 52.0 4 208 W 50% NO 104 W 49 Admin HALLWAY #3 232MAXN 2 52.0 5 260 W 50% NO 130 W 50 Admin OFFICE A130 232MAXN 2 52.0 44 2288 W 50% NO 1144 W 51 Admin OFFICE A130 232MAXN 2 52.0 1 52 W 50% NO 26 W 52 Admin OFFICE A130 1 17.0 5 85 W 50% NO 43 W 53 Admin WORK ROOM 130A 332MAXL 3 68.0 3 204 W 33% NO 137 W 54 Admin OFFICE 130C 332MAXL 3 68.0 2 136 W 33% Yes 91 W 55 Admin OFFICE 130C 232MAXL 1 24.0 2 48 W 50% Yes 24 W 56 Admin OFFICE 130D 332MAXL 3 68.0 3 204 W 33% NO 137 W 59 Admin OFFICE 130E 332MAXL 3 68.0 3 204 W 33% NO 137 W 60 Admin HALLWAY #5 332MAXL 3 68.0 6 408 W 33% NO 273 W 61 Admin COPY OFFICE 141A 432MAXL 4 91.0 1 91 W 50% NO 46 W 62 Admin COPY ROOM 141 332MAXL 3 68.0 11 748 W 33% NO 501 W 63 Admin HALLWAY #4 232MAXN 2 52.0 3 156 W 50% NO 78 W 65 Admin MECH ROOM BY 160 *232MAXL 2 46.0 17 782 W 50% NO 391 W 66 Admin MECH ROOM BY 160 232MAXL 2 46.0 4 184 W 50% NO 92 W 67 Admin MECH RM BY 160 UP ELEC *232MAXL 2 46.0 3 138 W 50% NO 69 W 68 Admin MECH RM BY 160 LOW ELEC *232MAXL 2 46.0 2 92 W 50% Yes 46 W 69 Admin HALLWAY #7 232MAXN 2 52.0 6 312 W 50% NO 156 W 70 Admin OFFICE 162A 232MAXN 2 52.0 1 52 W 50% NO 26 W 71 Admin STORAGE 162B 232MAXN 2 52.0 2 104 W 50% Yes 52 W 72 Admin OFFICE A182A 432MAXL 4 91.0 4 364 W 50% NO 182 W 73 Admin HALLWAY #8 232MAXN 2 52.0 4 208 W 50% NO 104 W 75 Admin OFFICE A178 232MAXN 2 52.0 1 52 W 50% NO 26 W 76 Admin OFFICE A176 232MAXN 2 52.0 1 52 W 50% NO 26 W 77 Admin OFFICE A175 232MAXN 2 52.0 1 52 W 50% NO 26 W 78 Admin OFFICE A174 232MAXN 2 52.0 2 104 W 50% Yes 52 W 79 Admin HALLWAY #9 232MAXN 2 52.0 15 780 W 50% NO 390 W 80 Admin OFFICE A179 232MAXN 2 52.0 1 52 W 50% NO 26 W 82 Admin STORAGE A277 232MAXN 2 52.0 2 104 W 50% Yes 52 W 85 Admin HALLWAY A279 232MAXN 2 52.0 8 416 W 50% NO 208 W 86 Admin OFFICE A279 432MAXL 2 45.5 4 182 W 50% NO 91 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 87 Admin OFFICE A276 232MAXN 2 52.0 2 104 W 50% Yes 52 W 88 Admin OFFICE A275 232MAXN 2 52.0 1 52 W 50% NO 26 W 89 Admin OFFICE A274 232MAXN 2 52.0 1 52 W 50% NO 26 W 90 Admin OFFICE A272 232MAXN 2 52.0 1 52 W 50% NO 26 W 91 Admin PHONE ROOM A271 232MAXN 2 52.0 2 104 W 50% Yes 52 W 92 Admin RECEPTIONIST ROOM 218 432MAXL 2 45.5 8 364 W 50% NO 182 W 93 Admin OFFICE KO7 432MAXL 2 45.5 6 273 W 50% NO 137 W 95 Admin CONFRENCE RM 218 C 432MAXL 2 45.5 8 364 W 50% NO 182 W 96 Admin CONFRENCE RM 218 C 432MAXL 2 45.5 4 182 W 50% NO 91 W 97 Admin OFFICE 2118B 432MAXL 2 45.5 4 182 W 50% NO 91 W 98 Admin OFFICE 2118A 432MAXL 2 45.5 6 273 W 50% NO 137 W 99 Admin OFFICE A213 432MAXL 4 91.0 2 182 W 50% NO 91 W 100 Admin OFFICE A213A 432MAXL 4 91.0 2 182 W 50% NO 91 W 101 Admin OFFICE A213B 432MAXL 4 91.0 1 91 W 50% NO 46 W 102 Admin OFFICE A213C 432MAXL 4 91.0 1 91 W 50% NO 46 W 103 Admin OFFICE A211 432MAXL 2 45.5 6 273 W 50% NO 137 W 104 Admin OFFICE A211 432MAXL 2 45.5 3 137 W 50% NO 68 W 105 Admin HALLWAY BY 211 232MAXL 2 46.0 4 184 W 50% NO 92 W 107 Admin HALLWAY BY 214 232MAXN 2 52.0 2 104 W 50% Yes 52 W 108 Admin HALLWAY BY 214 232MAXN 2 52.0 3 156 W 50% NO 78 W 110 Admin HALLWAY BY 210 232MAXN 2 52.0 2 104 W 50% Yes 52 W 111 Admin OFFICE 210 232MAXN 2 52.0 0 0W 50% NO 0W 113 Admin HALLWAY BY 207-208 232MAXN 2 52.0 6 312 W 50% NO 156 W 115 Admin OFFICE 209 232MAXL 2 46.0 2 92 W 50% Yes 46 W 116 Admin OFFICE 208 432MAXL 2 45.5 2 91 W 50% Yes 46 W 117 Admin OFFICE 208 232MAXL 2 46.0 1 46 W 50% NO 23 W 118 Admin OFFICE 207 432MAXL 2 45.5 4 182 W 50% NO 91 W 119 Admin OFFICE 204 232MAXN 2 52.0 2 104 W 50% Yes 52 W 120 Admin OFFICE 205A 432MAXL 2 45.5 2 91 W 50% Yes 46 W 121 Admin OFFICE 205B 432MAXL 2 45.5 2 91 W 50% Yes 46 W 122 Admin HALLWAY BY 205A-B 232MAXL 2 46.0 2 92 W 50% Yes 46 W 124 Admin OFFICE 206 432MAXL 2 45.5 4 182 W 50% NO 91 W 128 Admin HALLWAY BY 200 232MAXN 2 52.0 2 104 W 50% Yes 52 W 129 Admin RADIATION RM 236 232MAXN 2 52.0 8 416 W 50% NO 208 W 131 Admin STORAGE ROOM A236A 232MAXL 2 46.0 2 92 W 50% Yes 46 W 133 Admin OFFICE A240 232MAXN 2 52.0 2 104 W 50% Yes 52 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 26 W 134 Admin OFFICE A239 232MAXN 2 52.0 1 52 W 50% NO 135 Admin OFFICE A238 232MAXN 2 52.0 1 52 W 50% NO 26 W 136 Admin OFFICE A237 232MAXN 2 52.0 2 104 W 50% Yes 52 W 137 Book Str EXTERIOR & ENTRANCE 1 15.0 18 270 W 50% NO 135 W 138 Book Str OFFICE # 1 232MAXL 2 46.0 1 46 W 50% NO 23 W 139 Book Str OFFICE # 1 232MAXN 2 52.0 2 104 W 50% Yes 52 W 140 Book Str OFFICE # 2 232MAXN 2 52.0 3 156 W 50% NO 78 W 141 Book Str OFFICE # 2 232MAXL 2 46.0 2 92 W 50% Yes 46 W 143 Book Str CUSTOMER SRVICE AREA 2 68.0 4 272 W 50% NO 136 W 144 Book Str MEETING RM 232MAXL 2 46.0 3 138 W 50% NO 69 W 145 Book Str MEETING RM 232MAXN 2 52.0 3 156 W 50% NO 78 W 146 Book Str MEETING RM 232MAXN 2 52.0 2 104 W 50% Yes 52 W 147 Book Str RECEIVING STORAGE 432MAXL 4 91.0 7 637 W 50% NO 319 W 149 Book Str OFFICE # 3 232MAXL 2 46.0 1 46 W 50% NO 23 W 150 Book Str OFFICE # 3 232MAXN 2 52.0 2 104 W 50% Yes 52 W 151 Book Str BOOKS DISPLAY AREA 2 68.0 58 3944 W 50% NO 1972 W 152 Book Str BOOKS DISPLAY AREA 232MAXN 2 52.0 16 832 W 50% NO 416 W 153 Book Str BOOKS DISPLAY AREA 232MAXN 2 52.0 94 4888 W 50% NO 2444 W 154 Book Str BOOKS DISPLAY AREA 232MAXN 2 52.0 5 260 W 50% NO 130 W 155 Book Str BOOKS DISPLAY AREA 1 25.0 8 200 W 50% NO 100 W 156 Book Str BOOKS DISPLAY AREA 1 25.0 8 200 W 50% NO 100 W 157 Book Str CENTER STAIRS 1 13.0 12 156 W 50% NO 78 W 158 Book Str COPY ROOM B1 232MAXN 2 28.0 3 84 W 50% NO 42 W 160 Book Str OFICE #B3 232MAXN 2 28.0 7 196 W 50% NO 98 W 161 Book Str BREAKROOM B4 232MAXN 2 28.0 9 252 W 50% NO 126 W 232MAXL 2 46.0 2 92 W 50% Yes 46 W 2 68.0 28 1904 W 50% NO 952 W 163 Book Str BREAKROOM HALLWAY B7 164 Book Str BOOKS DISPLAY AREA BO 165 Book Str BOOKS DISPLAY AREA BO 232MAXN 2 52.0 22 1144 W 50% NO 572 W 166 Book Str BOOKS DISPLAY AREA BO 232MAXN 2 52.0 14 728 W 50% NO 364 W 168 Book Str BOOKS DISPLAY AREA BO 332MAXL 1 22.7 18 409 W 50% NO 204 W 171 Book Str BOOKS DISPLAY AREA BO 332MAXL 1 22.7 4 91 W 50% NO 45 W 174 Book Str BOOK STORAGE 432MAXL 4 91.0 16 1456 W 50% NO 728 W 175 BC HALL 234 232MAXN 2 52.0 2 104 W 50% Yes 52 W 176 BC HALL 223 232MAXN 2 52.0 10 520 W 50% NO 260 W 177 BC HALL 223 232MAXN 2 52.0 4 208 W 50% NO 104 W 179 BC HALL 205 232MAXN 2 52.0 7 364 W 50% NO 182 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 180 BC OFFICE 206 232MAXN 2 52.0 1 52 W 50% NO 26 W 181 BC OFFICE 207 232MAXN 2 52.0 1 52 W 50% NO 26 W 182 BC OFFICE 208 232MAXN 2 52.0 1 52 W 50% NO 26 W 183 BC OFICE 210 232MAXN 2 52.0 1 52 W 50% NO 26 W 184 BC OFICE 211 232MAXN 2 52.0 1 52 W 50% NO 26 W 186 BC MEETING ROOM 214 432MAXL 2 45.5 8 364 W 50% NO 182 W 189 BC HALL 213 232MAXN 2 52.0 6 312 W 50% NO 156 W 190 BC OFFICE 215 232MAXN 2 52.0 2 104 W 50% Yes 52 W 191 BC OFFICE 216 232MAXN 2 52.0 4 208 W 50% NO 104 W 192 BC OFFICE 217 232MAXN 2 52.0 4 208 W 50% NO 104 W 193 BC OFFICE 218 232MAXN 2 52.0 2 104 W 50% Yes 52 W 194 BC OFFICE 219 232MAXN 2 52.0 2 104 W 50% Yes 52 W 195 BC COPY ROOM 203 232MAXN 2 52.0 8 416 W 50% NO 208 W 196 BC CONF. ROOM 204 232MAXN 2 52.0 4 208 W 50% NO 104 W 198 BC ENRTY 202 232MAXN 2 52.0 4 208 W 50% NO 104 W 199 BC OFFICE 306 232MAXN 2 52.0 1 52 W 50% NO 26 W 200 BC OFFICE 307 232MAXN 2 52.0 1 52 W 50% NO 26 W 201 BC OFFICE 308 232MAXN 2 52.0 1 52 W 50% NO 26 W 202 BC OFFICE 309 232MAXN 2 52.0 1 52 W 50% NO 26 W 203 BC OFFICE 310 232MAXN 2 52.0 1 52 W 50% NO 26 W 204 BC OFFICE 311 232MAXN 2 52.0 1 52 W 50% NO 26 W 205 BC OFFICE 312 232MAXN 2 52.0 1 52 W 50% NO 26 W 206 BC HALL 304 232MAXN 2 52.0 7 364 W 50% NO 182 W 209 BC HALL 244-1 1 40.0 7 280 W 50% NO 140 W 215 BC HALL 243 1 40.0 5 200 W 50% NO 100 W 220 BC HALL 107 1 17.0 4 68 W 50% NO 34 W 221 BC OFFICE 102E 332MAXL 3 68.0 2 136 W 33% Yes 91 W 222 BC OFFICE 102E 332MAXL 3 68.0 1 68 W 33% NO 46 W 223 BC OFFICE 102D 232MAXN 2 52.0 1 52 W 50% NO 26 W 224 BC OFFICE 102C 232MAXN 2 52.0 1 52 W 50% NO 26 W 225 BC OFFICE 102B 232MAXN 2 52.0 1 52 W 50% NO 26 W 226 BC OFFICE 102A 232MAXN 2 52.0 1 52 W 50% NO 26 W 227 BC OFFICE 102F 332MAXL 3 68.0 2 136 W 33% Yes 91 W 228 BC OFFICE 102F 332MAXL 3 68.0 1 68 W 33% NO 46 W 229 BC STORAGE 112 232MAXL 2 46.0 2 92 W 50% Yes 46 W 230 BC OFFICE 115 232MAXN 2 52.0 1 52 W 50% NO 26 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 26 W 231 BC OFFICE 116 232MAXN 2 52.0 1 52 W 50% NO 232 BC OFFICE 117 232MAXN 2 52.0 1 52 W 50% NO 26 W 233 BC CAFETERIA 1 25.0 9 225 W 50% NO 113 W 234 BC CAFETERIA 232MAXN 2 52.0 11 572 W 50% NO 286 W 236 BC OFFICE 141 232MAXN 2 52.0 1 52 W 50% NO 26 W 237 BC OFFICE 142 232MAXN 2 52.0 1 52 W 50% NO 26 W 238 BC OFFICE 143 232MAXN 2 52.0 1 52 W 50% NO 26 W 239 BC OFFICE 143 232MAXL 2 46.0 2 92 W 50% Yes 46 W 240 BC HALL 2 232MAXN 2 52.0 2 104 W 50% Yes 52 W 242 BC ENTRY 113 232MAXN 2 52.0 4 208 W 50% NO 104 W 246 BC AUDITORIUM 1 90.0 30 2700 W 50% NO 1350 W 247 BC AUDITORIUM 1 2.0 6 12 W 50% NO 6W 251 Camp Cntr ROOF STORAGE 106 232MAXN 2 52.0 6 312 W 50% NO 156 W 252 Camp Cntr ROOF STORAGE 106 232MAXN 2 52.0 2 104 W 50% Yes 52 W 253 Camp Cntr ROOF STORAGE 106 432MAXL 2 45.5 2 91 W 50% Yes 46 W 255 Camp Cntr MECHANICAL ROOM 105 232MAXL 2 39.0 4 156 W 50% NO 78 W 257 Camp Cntr MECHANICAL ROOM 105 232MAXN 2 52.0 2 104 W 50% Yes 52 W 258 Camp Cntr MECHANICAL ROOM 105 232MAXN 2 52.0 6 312 W 50% NO 156 W 259 Camp Cntr FOOD STORAGE 110 232MAXN 2 52.0 6 312 W 50% NO 156 W 260 Camp Cntr FOOD STORAGE 110 232MAXN 2 52.0 2 104 W 50% Yes 52 W 261 Camp Cntr OFFICE 117 432MAXN 2 51.5 4 206 W 50% NO 103 W 262 Camp Cntr CASHIER OFFICE 232MAXN 2 52.0 3 156 W 50% NO 78 W 263 Camp Cntr OFFICE 118 232MAXN 2 52.0 2 104 W 50% Yes 52 W 264 Camp Cntr OFFICE 119 332MAXL 3 68.0 1 68 W 33% NO 46 W 265 Camp Cntr RECEPTIONIST RM 120 432MAXN 2 51.5 4 206 W 50% NO 103 W 266 Camp Cntr RECEPTIONIST RM 120 1 25.0 5 125 W 50% NO 63 W 267 Camp Cntr STORAGE 121 232MAXL 2 46.0 2 92 W 50% Yes 46 W 271 Camp Cntr HALLWAY BY 114-128 1 25.0 15 375 W 50% NO 188 W 273 Camp Cntr CAFETERIA SEATING RM 201 232MAXH 2 70.0 24 1680 W 50% NO 840 W 274 Camp Cntr CAFETERIA SEATING RM 201 232MAXH 2 70.0 12 840 W 50% NO 420 W 275 Camp Cntr CAFETERIA SEATING RM 201 232MAXH 2 70.0 6 420 W 50% NO 210 W 276 Camp Cntr POTS PANS STORAGE RM 202 432MAXN 2 51.5 2 103 W 50% Yes 52 W 277 Camp Cntr POTS PANS STORAGE RM 202 232MAXN 2 52.0 6 312 W 50% NO 156 W 278 Camp Cntr CAFETERIA BY RM 207 232MAXN 2 28.0 34 952 W 50% NO 476 W 279 Camp Cntr CAFETERIA BY RM 207 232MAXN 2 28.0 2 56 W 50% Yes 28 W 280 Camp Cntr MAIN LOBBY 209 232MAXN 2 52.0 8 416 W 50% NO 208 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 208 W 281 Camp Cntr MAIN LOBBY 209 232MAXN 2 52.0 8 416 W 50% NO 282 Camp Cntr GAME RM 216 232MAXN 2 28.0 4 112 W 50% NO 56 W 283 Camp Cntr MACHANICAL RM 215 232MAXN 2 52.0 3 156 W 50% NO 78 W 284 Camp Cntr HALLWAY 213 232MAXN 2 28.0 5 140 W 50% NO 70 W 285 Camp Cntr RECEPTIONIST AREA KO1 432MAXL 4 91.0 2 182 W 50% NO 91 W 292 Camp Cntr CONFRENCE RM 223 432MAXL 4 91.0 10 910 W 50% NO 455 W 293 Camp Cntr OFFICE 224 232MAXN 2 52.0 3 156 W 50% NO 78 W 294 Camp Cntr MULTI PURPOSE RM 228 432MAXL 4 91.0 14 1274 W 50% NO 637 W 295 Drama OFFICE 160 232MAXN 2 52.0 1 52 W 50% NO 26 W 296 Drama OFFICE 151A 232MAXH 2 70.0 2 140 W 50% Yes 70 W 297 Drama OFFICE 151B 232MAXH 2 70.0 2 140 W 50% Yes 70 W 298 Drama HALL C05 232MAXN 2 52.0 7 364 W 50% NO 182 W 300 Drama HALL C05 1 28.0 5 140 W 50% NO 70 W 303 Drama STORAGE 155A 232MAXN 2 52.0 4 208 W 50% NO 104 W 304 Drama EXTERIOR THEATER LOBBY 2 40.0 12 480 W 50% NO 240 W 305 Drama EXTERIOR THEATER LOBBY 232MAXN 2 52.0 11 572 W 50% NO 286 W 306 Drama MECHANICAL RM 153 232MAXN 2 52.0 4 208 W 50% NO 104 W 308 Drama PREP WORKSHOP 145 B254WHO 2 124.0 12 1488 W 50% NO 744 W 312 Drama PREP WORKSHOP 145 B254WHO 2 124.0 8 992 W 50% NO 496 W 314 Drama PREP WORKSHOP 145 B254WHO 2 124.0 8 992 W 50% NO 496 W 315 Drama PREP WORKSHOP 145 B254WHO 2 124.0 8 992 W 50% NO 496 W 317 Drama PREP WORKSHOP 145 B254WHO 2 124.0 8 992 W 50% NO 496 W 318 Drama LOUNGE 145A 232MAXN 2 52.0 4 208 W 50% NO 104 W 319 Drama OFFICE 145C 232MAXN 2 52.0 1 52 W 50% NO 26 W 320 Drama TOOL RM 232MAXN 2 52.0 8 416 W 50% NO 208 W 321 Drama STAGE *232MAXL 1 24.0 4 96 W 50% NO 48 W 322 Drama STAGE 1 150.0 4 600 W 50% NO 300 W 323 Drama STAGE 232MAXN 2 52.0 2 104 W 50% Yes 52 W 325 Drama STAGE 232MAXN 2 52.0 11 572 W 50% NO 286 W 326 Drama STAGE *232MAXL 2 46.0 4 184 W 50% NO 92 W 327 Drama STAGE *232MAXL 2 46.0 6 276 W 50% NO 138 W 333 Drama HALL 1 232MAXN 2 52.0 9 468 W 50% NO 234 W 334 Drama HALL 1 232MAXN 2 52.0 5 260 W 50% NO 130 W 335 Drama HALL 2 232MAXN 2 52.0 11 572 W 50% NO 286 W 336 Drama HALL 2 232MAXN 2 52.0 5 260 W 50% NO 130 W 339 Drama DRESSING ROOM 130 232MAXN 2 52.0 12 624 W 50% NO 312 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 340 Drama DRESSING ROOM 130 232MAXN 2 52.0 2 104 W 50% Yes 52 W 341 Drama DRESSING ROOM 133 232MAXN 2 52.0 2 104 W 50% Yes 52 W 342 Drama DRESSING ROOM 129 232MAXN 2 52.0 2 104 W 50% Yes 52 W 343 Drama LAUNDRY 126A 232MAXN 2 52.0 4 208 W 50% NO 104 W 344 Drama COSTUMES 126 232MAXN 2 52.0 8 416 W 50% NO 208 W 345 Drama COSTUMES 126 232MAXN 2 52.0 10 520 W 50% NO 260 W 346 Drama COSTUMES 126 232MAXN 2 52.0 2 104 W 50% Yes 52 W 347 Drama OFFICE 125 232MAXH 2 70.0 2 140 W 50% Yes 70 W 348 Drama OFFICE 124 232MAXH 2 70.0 2 140 W 50% Yes 70 W 349 Drama OFFICE 123 232MAXH 2 70.0 2 140 W 50% Yes 70 W 350 Drama OFFICE 122 232MAXH 2 70.0 2 140 W 50% Yes 70 W 351 Drama OFFICE 121 232MAXH 2 70.0 2 140 W 50% Yes 70 W 352 Drama OFFICE 120 232MAXH 2 70.0 2 140 W 50% Yes 70 W 353 Drama OFFICE 119 232MAXH 2 70.0 2 140 W 50% Yes 70 W 354 Drama OFFICE 118 232MAXH 2 70.0 2 140 W 50% Yes 70 W 355 Drama OFFICE 117 232MAXH 2 70.0 2 140 W 50% Yes 70 W 356 Drama OFFICE 116 232MAXH 2 70.0 2 140 W 50% Yes 70 W 357 Drama OFFICE 114D 232MAXN 2 52.0 1 52 W 50% NO 26 W 359 Drama HALL C02 232MAXN 2 52.0 3 156 W 50% NO 78 W 360 Drama HALL C03 232MAXN 2 52.0 6 312 W 50% NO 156 W 361 Drama HALL 3 232MAXN 2 52.0 4 208 W 50% NO 104 W 362 Drama OFFICE 114C 232MAXN 2 52.0 1 52 W 50% NO 26 W 363 Drama OFFICE 114C 1 25.0 4 100 W 50% NO 50 W 364 Drama WORKROOM 114B 232MAXN 2 52.0 2 104 W 50% Yes 52 W 366 Drama OFFICE 114A 232MAXN 2 52.0 4 208 W 50% NO 104 W 367 Drama HALL C01 232MAXN 2 52.0 8 416 W 50% NO 208 W 368 Drama HALL C01 232MAXN 2 52.0 19 988 W 50% NO 494 W 370 Drama OFFICE 103-1 232MAXN 2 52.0 6 312 W 50% NO 156 W 371 Drama OFFICE 103-1 232MAXN 2 52.0 3 156 W 50% NO 78 W 372 Drama OFFICE 103 232MAXN 2 52.0 4 208 W 50% NO 104 W 373 Drama OFFICE 103 232MAXN 2 52.0 2 104 W 50% Yes 52 W 374 Drama OFFICE 104 232MAXN 2 52.0 8 416 W 50% NO 208 W 376 Drama STORAGE 106 432MAXL 2 45.5 8 364 W 50% NO 182 W 378 Drama HALL 111 432MAXL 4 91.0 8 728 W 50% NO 364 W 379 Drama PRACTICE ROOM 111 232MAXN 2 52.0 6 312 W 50% NO 156 W 381 Drama EXTERIOR 232MAXN 2 52.0 8 416 W 50% NO 208 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 382 Drama EXTERIOR 232MAXN 2 52.0 22 1144 W 50% NO 572 W 383 Drama EXTERIOR 50W HPS 1 72.0 5 360 W 50% NO 180 W 385 Humanities HALL 319 232MAXN 2 52.0 2 104 W 50% Yes 52 W 386 Humanities HALL 319 232MAXN 2 52.0 24 1248 W 50% NO 624 W 387 Humanities HALL 319 232MAXN 2 52.0 4 208 W 50% NO 104 W 388 Humanities OFFICE 323 232MAXH 2 70.0 2 140 W 50% Yes 70 W 389 Humanities OFFICE 324 232MAXH 2 70.0 2 140 W 50% Yes 70 W 390 Humanities OFFICE 322 232MAXH 2 70.0 4 280 W 50% NO 140 W 391 Humanities HALL 319 DISPLAY CASES 232MAXN 2 52.0 3 156 W 50% NO 78 W 392 Humanities HALL 326A 232MAXN 2 52.0 2 104 W 50% Yes 52 W 393 Humanities OFFICE 318 & 317 232MAXH 2 70.0 4 280 W 50% NO 140 W 394 Humanities OFFICE 316 232MAXH 2 70.0 2 140 W 50% Yes 70 W 395 Humanities HALL 321 232MAXN 2 52.0 2 104 W 50% Yes 52 W 396 Humanities OFFICE 315 232MAXH 2 70.0 2 140 W 50% Yes 70 W 397 Humanities OFFICE 314 232MAXH 2 70.0 2 140 W 50% Yes 70 W 398 Humanities STORAGE 303A 232MAXH 2 70.0 4 280 W 50% NO 140 W 400 Humanities OFFICE 313 232MAXH 2 70.0 2 140 W 50% Yes 70 W 401 Humanities OFFICE 312 232MAXH 2 70.0 2 140 W 50% Yes 70 W 402 Humanities OFFICE 311 232MAXH 2 70.0 2 140 W 50% Yes 70 W 403 Humanities HALL 320 232MAXN 2 52.0 2 104 W 50% Yes 52 W 404 Humanities STORAGE 320A 232MAXN 2 52.0 4 208 W 50% NO 104 W 405 Humanities OFFICE 310 232MAXH 2 70.0 2 140 W 50% Yes 70 W 406 Humanities OFFICE 309 232MAXH 2 70.0 2 140 W 50% Yes 70 W 407 Humanities GALLERY 202 232MAXN 2 52.0 9 468 W 50% NO 234 W 408 Humanities GALLERY 202 232MAXN 2 52.0 20 1040 W 50% NO 520 W 409 Humanities GALLERY 202 232MAXN 2 52.0 6 312 W 50% NO 156 W 410 Humanities OFFICE 209 232MAXH 2 70.0 2 140 W 50% Yes 70 W 411 Humanities OFFICE 210 232MAXH 2 70.0 2 140 W 50% Yes 70 W 412 Humanities OFFICE 211 232MAXH 2 70.0 2 140 W 50% Yes 70 W 413 Humanities OFFICE 212 232MAXH 2 70.0 2 140 W 50% Yes 70 W 414 Humanities OFFICE 213 232MAXH 2 70.0 2 140 W 50% Yes 70 W 415 Humanities OFFICE 214 232MAXH 2 70.0 2 140 W 50% Yes 70 W 416 Humanities OFFICE 215 232MAXH 2 70.0 2 140 W 50% Yes 70 W 417 Humanities OFFICE 216 232MAXH 2 70.0 2 140 W 50% Yes 70 W 418 Humanities OFFICE 217 232MAXH 2 70.0 2 140 W 50% Yes 70 W 420 Humanities OFFICE 226 232MAXN 2 52.0 2 104 W 50% Yes 52 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 421 Humanities OFFICE 227 232MAXN 2 52.0 2 104 W 50% Yes 52 W 422 Humanities OFFICE 252 232MAXH 2 70.0 9 630 W 50% NO 315 W 423 Humanities STORAGE 253 232MAXH 2 70.0 8 560 W 50% NO 280 W 425 Humanities HALL 242 232MAXN 2 52.0 2 104 W 50% Yes 52 W 426 Humanities HALL 242 232MAXN 2 52.0 20 1040 W 50% NO 520 W 428 Humanities OFFICE 251 232MAXH 2 70.0 2 140 W 50% Yes 70 W 429 Humanities OFFICE 236 232MAXH 2 70.0 2 140 W 50% Yes 70 W 431 Humanities OFFICE 324 1 17.0 5 85 W 50% NO 43 W 433 Humanities OFFICE 233 1 17.0 6 102 W 50% NO 51 W 434 Humanities OFFICE 237 1 17.0 18 306 W 50% NO 153 W 435 Humanities OFFICE 237 232MAXN 2 52.0 7 364 W 50% NO 182 W 436 Humanities OFFICE 238 232MAXN 2 52.0 4 208 W 50% NO 104 W 437 Humanities OFFICE 239 1 17.0 6 102 W 50% NO 51 W 441 Humanities HALL 207 232MAXN 2 52.0 4 208 W 50% NO 104 W 442 Humanities HALL 207 232MAXN 2 52.0 4 208 W 50% NO 104 W 443 Humanities HALL 207 232MAXN 2 52.0 2 104 W 50% Yes 52 W 444 Humanities HALL 207 232MAXN 2 52.0 28 1456 W 50% NO 728 W 447 Humanities STORAGE 218 232MAXN 2 52.0 8 416 W 50% NO 208 W 448 Humanities STORAGE 218 232MAXN 2 52.0 2 104 W 50% Yes 52 W 449 Humanities STORAGE 205 232MAXN 2 52.0 4 208 W 50% NO 104 W 450 Humanities STORAGE 205 232MAXN 2 52.0 2 104 W 50% Yes 52 W 451 Humanities EXTERIOR STAIRS 260 232MAXN 2 52.0 4 208 W 50% NO 104 W 453 Humanities ENTRY 101 232MAXN 2 52.0 2 104 W 50% Yes 52 W 455 Humanities OFFICE 106 232MAXN 2 52.0 2 104 W 50% Yes 52 W 456 Humanities OFFICE 106 232MAXN 2 52.0 4 208 W 50% NO 104 W 459 Humanities HALL 114 232MAXN 2 52.0 28 1456 W 50% NO 728 W 460 Humanities HALL 114 232MAXN 2 52.0 5 260 W 50% NO 130 W 462 Humanities PRINTMAKING 112 232MAXN 2 52.0 20 1040 W 50% NO 520 W 463 Humanities ELECTRICAL 117 1 28.0 5 140 W 50% NO 70 W 467 Humanities MECHANICAL 118 232MAXN 2 52.0 6 312 W 50% NO 156 W 468 Humanities MECHANICAL 118 232MAXN 2 52.0 2 104 W 50% Yes 52 W 471 Humanities MECHANICAL 118 232MAXN 2 52.0 1 52 W 50% NO 26 W 473 Humanities EXTERIOR SCULPTURE PATO 232MAXN 2 52.0 2 104 W 50% Yes 52 W 475 IDC HALL 101 232MAXL 2 46.0 9 414 W 50% NO 207 W 482 IDC ELEC EX02 432MAXL 2 45.5 8 364 W 50% NO 182 W 484 IDC OFFICE 102A 332MAXL 3 68.0 2 136 W 50% Yes 68 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 487 IDC ELEC. RM. *232MAXL 1 24.0 11 264 W 50% NO 132 W 488 IDC HALL208 232MAXL 2 46.0 4 184 W 50% NO 92 W 491 IDC OFFICE 324 332MAXL 3 68.0 2 136 W 50% Yes 68 W 492 IDC OFFICE 323 332MAXL 3 68.0 2 136 W 50% Yes 68 W 493 IDC OFFICE 322 332MAXL 3 68.0 2 136 W 50% Yes 68 W 494 IDC OFFICE 321 332MAXL 3 68.0 2 136 W 50% Yes 68 W 495 IDC OFFICE 320 332MAXL 3 68.0 2 136 W 50% Yes 68 W 496 IDC OFFICE 319 332MAXL 3 68.0 2 136 W 50% Yes 68 W 499 IDC HALL 301-3 232MAXN 2 28.0 4 112 W 50% NO 56 W 502 IDC CONFERENCE ROOM 335 332MAXL 3 68.0 4 272 W 50% NO 136 W 503 IDC OFFICE 336 332MAXL 3 68.0 4 272 W 50% NO 136 W 504 IDC OFFICE 337 332MAXL 3 68.0 2 136 W 50% Yes 68 W 505 IDC OFFICE 338 332MAXL 3 68.0 2 136 W 50% Yes 68 W 506 IDC OFFICE 339 332MAXL 3 68.0 2 136 W 50% Yes 68 W 507 IDC HALL 301 232MAXN 2 28.0 7 196 W 50% NO 98 W 510 IDC OFFICE 331 332MAXL 3 68.0 2 136 W 50% Yes 68 W 511 IDC OFFICE 349 332MAXL 3 68.0 2 136 W 50% Yes 68 W 512 IDC WORK ROOM 333 432MAXL 4 91.0 6 546 W 50% NO 273 W 513 IDC OFFICES 312 432MAXL 2 45.5 4 182 W 50% NO 91 W 514 IDC OFFICES 312 232MAXL 2 46.0 4 184 W 50% NO 92 W 515 IDC OFFICES 312 232MAXL 2 46.0 3 138 W 50% NO 69 W 516 IDC OFFICE 351 332MAXL 3 68.0 2 136 W 50% Yes 68 W 517 IDC HALL 301-1 232MAXN 2 28.0 6 168 W 50% NO 84 W 520 IDC OFFICE 326 232MAXL 2 46.0 2 92 W 50% Yes 46 W 521 IDC OFFICE 327 232MAXL 2 46.0 2 92 W 50% Yes 46 W 522 IDC OFFICE 327 432MAXL 2 45.5 4 182 W 50% NO 91 W 523 IDC OFFICE 328 232MAXL 2 46.0 2 92 W 50% Yes 46 W 524 IDC OFFICE 340 332MAXL 3 68.0 2 136 W 50% Yes 68 W 525 IDC OFFICE 341 332MAXL 3 68.0 2 136 W 50% Yes 68 W 526 IDC OFFICE 342 332MAXL 3 68.0 2 136 W 50% Yes 68 W 528 IDC OFFICE 329-B 232MAXL 2 46.0 2 92 W 50% Yes 46 W 529 IDC OFFICE 330 332MAXL 3 68.0 2 136 W 50% Yes 68 W 530 IDC OFFICE 343 332MAXL 3 68.0 2 136 W 50% Yes 68 W 531 IDC OFFICE 344 332MAXL 3 68.0 2 136 W 50% Yes 68 W 532 IDC OFFICE 345 332MAXL 3 68.0 2 136 W 50% Yes 68 W 533 IDC OFFICE 346 332MAXL 3 68.0 2 136 W 50% Yes 68 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 534 IDC OFFICE 347 332MAXL 3 68.0 2 136 W 50% Yes 68 W 538 IDC EXT 3RD FLOOR 232MAXN 2 52.0 4 208 W 50% NO 104 W 539 IDC OFFICE 348 332MAXL 3 68.0 2 136 W 50% Yes 68 W 540 IDC OFFICE 350 332MAXL 3 68.0 2 136 W 50% Yes 68 W 541 IDC OFFICE 352 332MAXL 3 68.0 2 136 W 50% Yes 68 W 542 IDC OFFICE 353 332MAXL 3 68.0 2 136 W 50% Yes 68 W 543 IDC OFFICE 354 432MAXL 4 91.0 2 182 W 50% NO 91 W 544 IDC OFFICE 355 332MAXL 3 68.0 2 136 W 50% Yes 68 W 545 IDC OFFICE 357 332MAXL 3 68.0 2 136 W 50% Yes 68 W 546 IDC OFFICE 358 332MAXL 3 68.0 2 136 W 50% Yes 68 W 547 IDC OFFICE 359 332MAXL 3 68.0 2 136 W 50% Yes 68 W 548 IDC OFFICE 360 332MAXL 3 68.0 2 136 W 50% Yes 68 W 549 IDC OFFICE 361 332MAXL 3 68.0 2 136 W 50% Yes 68 W 550 IDC OFFICE 362 332MAXL 3 68.0 2 136 W 50% Yes 68 W 557 IDC OFFICE 369 332MAXL 3 68.0 2 136 W 50% Yes 68 W 558 IDC OFFICE 370 332MAXL 3 68.0 2 136 W 50% Yes 68 W 559 IDC OFFICE 371 332MAXL 3 68.0 2 136 W 50% Yes 68 W 560 IDC OFFICE 372 332MAXL 3 68.0 2 136 W 50% Yes 68 W 561 IDC OFFICE 373 332MAXL 3 68.0 2 136 W 50% Yes 68 W 562 IDC OFFICE 374 332MAXL 3 68.0 2 136 W 50% Yes 68 W 563 IDC OFFICE 375 232MAXN 2 52.0 1 52 W 50% NO 26 W 564 IDC OFFICE 375 432MAXL 4 91.0 3 273 W 50% NO 137 W 566 IDC OFFICE 304 332MAXL 3 68.0 2 136 W 50% Yes 68 W 567 IDC OFFICE 305 332MAXL 3 68.0 2 136 W 50% Yes 68 W 568 IDC OFFICE 306 332MAXL 3 68.0 2 136 W 50% Yes 68 W 569 IDC OFFICE 307 332MAXL 3 68.0 2 136 W 50% Yes 68 W 570 IDC OFFICE 308 332MAXL 3 68.0 2 136 W 50% Yes 68 W 571 IDC OFFICE 309 332MAXL 3 68.0 2 136 W 50% Yes 68 W 572 IDC OFFICE 310 332MAXL 3 68.0 2 136 W 50% Yes 68 W 573 IDC OFFICE 315 332MAXL 3 68.0 2 136 W 50% Yes 68 W 574 IDC OFFICE 316 332MAXL 3 68.0 2 136 W 50% Yes 68 W 575 IDC OFFICE 317 432MAXL 4 91.0 3 273 W 50% NO 137 W 576 IDC HALL 301-5 232MAXN 2 28.0 1 28 W 50% NO 14 W 578 IDC OFFICE 311 232MAXN 2 28.0 2 56 W 50% Yes 28 W 581 Int Ed OFFICE 001 432MAXL 2 45.5 4 182 W 50% NO 91 W 582 Int Ed OFFICE 002 232MAXL 2 46.0 6 276 W 50% NO 138 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 584 Int Ed OFFICE 004 232MAXL 2 46.0 4 184 W 50% NO 92 W 585 Int Ed OFFICE 005 232MAXL 2 46.0 6 276 W 50% NO 138 W 587 Int Ed CONFRENCE ROOM 003 232MAXL 2 46.0 4 184 W 50% NO 92 W 589 Int Ed OFFICE 18 232MAXL 2 46.0 4 184 W 50% NO 92 W 590 Int Ed OFFICE 15 232MAXL 2 46.0 4 184 W 50% NO 92 W 591 Int Ed COPY ROOM 17 232MAXL 2 46.0 4 184 W 50% NO 92 W 592 Int Ed OFFICE 16 232MAXL 2 46.0 4 184 W 50% NO 92 W 594 Int Ed OFFICE 13 232MAXL 2 46.0 10 460 W 50% NO 230 W 596 Int Ed OFFICE 001 232MAXL 2 28.0 2 56 W 50% Yes 28 W 597 Int Ed OFFICE 12 232MAXL 2 46.0 2 92 W 50% Yes 46 W 598 Int Ed OFFICE 11 232MAXL 2 46.0 6 276 W 50% NO 138 W 599 Int Ed OFFICE 11C 232MAXL 2 46.0 4 184 W 50% NO 92 W 601 Int Ed OFFICE 11 232MAXN 2 52.0 1 52 W 50% NO 26 W 602 Int Ed OFFICE 11A 232MAXL 2 46.0 2 92 W 50% Yes 46 W 605 Int Ed OFFICE 11B 232MAXL 2 46.0 2 92 W 50% Yes 46 W 607 Int Ed OFFICE 9 232MAXL 2 46.0 4 184 W 50% NO 92 W 608 Int Ed OFFICE 008 232MAXL 2 46.0 4 184 W 50% NO 92 W 609 Int Ed OFFICE 19 232MAXL 2 46.0 4 184 W 50% NO 92 W 610 Int Ed OFFICE 007 232MAXL 2 46.0 4 184 W 50% NO 92 W 611 Int Ed OFFICE 20 232MAXL 2 46.0 2 92 W 50% Yes 46 W 614 Int Ed STORAGE 21 232MAXL 2 46.0 4 184 W 50% NO 92 W 617 LRC MECH RM 011 1 28.0 8 224 W 50% NO 112 W 618 LRC MECH RM 011 1 28.0 4 112 W 50% NO 56 W 622 LRC MECH RM 125 1 28.0 4 112 W 50% NO 56 W 2 52.0 5 260 W 50% NO 130 W 624 Marine Tech STORAGE TANK 232MAXN 627 Marine Tech HALL 103 232MAXN 2 52.0 2 104 W 50% Yes 52 W 628 Marine Tech ELECTRICAL ROOM 232MAXN 2 52.0 3 156 W 50% NO 78 W 629 Marine Tech OFFICE 207 232MAXN 2 52.0 2 104 W 50% Yes 52 W 630 Marine Tech OFFICE 206 232MAXN 2 52.0 4 208 W 50% NO 104 W 631 Marine Tech OFFICE 205 232MAXN 2 52.0 2 104 W 50% Yes 52 W 632 Marine Tech OFFICE 204 232MAXN 2 52.0 2 104 W 50% Yes 52 W 633 Marine Tech OFFICE 203 232MAXN 2 52.0 4 208 W 50% NO 104 W 635 Marine Tech EXTERIOR 232MAXN 2 52.0 2 104 W 50% Yes 52 W 636 Marine Tech EXTERIOR 232MAXN 2 52.0 3 156 W 50% NO 78 W 637 Marine Tech EXTERIOR 232MAXN 2 52.0 11 572 W 50% NO 286 W 639 OFFICE 301 232MAXH 2 70.0 4 280 W 50% NO 140 W Phys Ed Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 640 Phys Ed COPY 302 232MAXN 2 52.0 2 104 W 50% Yes 52 W 641 Phys Ed HALL CO3 232MAXN 2 52.0 7 364 W 50% NO 182 W 642 Phys Ed OFFICE 303 232MAXH 2 70.0 4 280 W 50% NO 140 W 643 Phys Ed OFFICE 304 232MAXH 2 70.0 4 280 W 50% NO 140 W 644 Phys Ed OFFICE 305 232MAXH 2 70.0 4 280 W 50% NO 140 W 645 Phys Ed OFFICE 306 232MAXH 2 70.0 4 280 W 50% NO 140 W 646 Phys Ed OFFICE 307 232MAXH 2 70.0 4 280 W 50% NO 140 W 647 Phys Ed OFFICE 308 232MAXH 2 70.0 4 280 W 50% NO 140 W 648 Phys Ed OFFICE 309 232MAXH 2 70.0 4 280 W 50% NO 140 W 649 Phys Ed CONFERENCE RM 310 232MAXH 2 70.0 10 700 W 50% NO 350 W 650 Phys Ed HALL KO4 232MAXN 2 52.0 2 104 W 50% Yes 52 W 651 Phys Ed MECHANICAL ROOM 232MAXN 2 52.0 7 364 W 50% NO 182 W 652 Phys Ed MECHANICAL ROOM 232MAXN 2 52.0 5 260 W 50% NO 130 W 655 Phys Ed HALL CO1A 232MAXN 2 52.0 2 104 W 50% Yes 52 W 657 Phys Ed ELECTRICAL 232MAXN 2 52.0 6 312 W 50% NO 156 W 659 Phys Ed PRESS ROOM 300 232MAXN 2 52.0 2 104 W 50% Yes 52 W 662 Phys Ed MECH. RM. *232MAXL 2 46.0 8 368 W 50% NO 184 W 663 Phys Ed MECH. RM. *232MAXL 1 24.0 8 192 W 50% NO 96 W 668 Phys Ed HALL C01/311 232MAXN 2 52.0 25 1300 W 50% NO 650 W 669 Phys Ed HALL C02 232MAXN 2 52.0 6 312 W 50% NO 156 W 670 Phys Ed HALL C02 232MAXN 2 52.0 5 260 W 50% NO 130 W 673 Phys Ed EXERCISE ROOM 201 232MAXN 2 52.0 26 1352 W 50% NO 676 W 676 Phys Ed OFFICE 202 232MAXN 2 52.0 8 416 W 50% NO 208 W 677 Phys Ed OFFICE 203A 232MAXN 2 52.0 3 156 W 50% NO 78 W 678 Phys Ed OFFICE 203A 232MAXN 2 52.0 1 52 W 50% NO 26 W 679 Phys Ed HALL C02A 232MAXN 2 52.0 2 104 W 50% Yes 52 W 680 Phys Ed HALL C02A 232MAXN 2 52.0 4 208 W 50% NO 104 W 681 Phys Ed HALL C02A 232MAXN 2 52.0 4 208 W 50% NO 104 W 683 Phys Ed HALL C02A 232MAXN 2 52.0 3 156 W 50% NO 78 W 684 Phys Ed HALL C02 232MAXN 2 52.0 12 624 W 50% NO 312 W 685 Phys Ed HALL C02 232MAXN 2 52.0 6 312 W 50% NO 156 W 686 Phys Ed HALL C02 232MAXN 2 52.0 10 520 W 50% NO 260 W 687 Phys Ed HALL C02 232MAXN 2 52.0 12 624 W 50% NO 312 W 688 Phys Ed HALL C02A DISPLAY 432MAXL 1 22.8 12 274 W 50% NO 137 W 690 Phys Ed HALL C02A DISPLAY 232MAXL 1 24.0 6 144 W 50% NO 72 W 691 Phys Ed HALL C02A DISPLAY 232MAXL 1 24.0 6 144 W 50% NO 72 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 234 W 692 Phys Ed HALL 211A 232MAXN 2 52.0 9 468 W 50% NO 693 Phys Ed OFFICE 212 232MAXN 2 52.0 1 52 W 50% NO 26 W 695 Phys Ed HALL 212A 232MAXN 2 52.0 6 312 W 50% NO 156 W 697 Phys Ed HALL C06A 232MAXN 2 52.0 2 104 W 50% Yes 52 W 699 Phys Ed HALL C06 232MAXN 2 52.0 12 624 W 50% NO 312 W 700 Phys Ed HALL C08 232MAXN 2 28.0 16 448 W 50% NO 224 W 703 Phys Ed ELECTRICAL K04 232MAXN 2 52.0 2 104 W 50% Yes 52 W 708 Phys Ed LAUNDRY ROOM 206 232MAXN 2 52.0 12 624 W 50% NO 312 W 713 Phys Ed LOCKER ROOM 208 232MAXN 2 52.0 9 468 W 50% NO 234 W 714 Phys Ed LOCKER ROOM 208 232MAXN 2 52.0 2 104 W 50% Yes 52 W 715 Phys Ed HALL C01A 232MAXN 2 52.0 2 104 W 50% Yes 52 W 717 Phys Ed HALL C01 232MAXN 2 52.0 9 468 W 50% NO 234 W 719 Phys Ed EQUIPMENT STORAGE 102 232MAXN 2 52.0 6 312 W 50% NO 156 W 720 Phys Ed OFFICE 103 232MAXN 2 52.0 4 208 W 50% NO 104 W 721 Phys Ed HALL 108A 232MAXN 2 52.0 4 208 W 50% NO 104 W 723 Phys Ed HALL 107B 232MAXN 2 52.0 4 208 W 50% NO 104 W 724 Phys Ed EQUIPMENT STORAGE 109 232MAXN 2 52.0 25 1300 W 50% NO 650 W 725 Phys Ed LAUNDRY ROOM 107 232MAXN 2 52.0 2 104 W 50% Yes 52 W 726 Phys Ed OFFICE 110B 232MAXN 2 52.0 1 52 W 50% NO 26 W 727 Phys Ed OFFICE 110A 232MAXN 2 52.0 4 208 W 50% NO 104 W 728 Phys Ed HALL 114B 232MAXN 2 52.0 4 208 W 50% NO 104 W 731 Phys Ed AEROBICS 114 232MAXN 2 52.0 40 2080 W 50% NO 1040 W 733 Phys Ed TEAM ROOM 106 232MAXN 2 52.0 4 208 W 50% NO 104 W 735 Phys Ed TEAM ROOM 106 232MAXN 2 52.0 16 832 W 50% NO 416 W 736 Phys Ed HALL C01B 232MAXN 2 52.0 2 104 W 50% Yes 52 W 738 Phys Ed COACHES' RM 105 232MAXN 2 52.0 6 312 W 50% NO 156 W 739 Phys Ed EXTERIOR 232MAXL 2 28.0 18 504 W 50% NO 252 W 740 Phys Ed WEIGHT TRAINING *NO WORK 1 458.0 6 2748 W 50% NO 1374 W 741 Phys Ed GYM *NO WORK 1 458.0 42 19236 W 50% NO 9618 W 742 Phys Ed EXTERIOR 232MAXN 2 52.0 24 1248 W 50% NO 624 W 743 Phys Ed EXTERIOR 232MAXN 2 52.0 8 416 W 50% NO 208 W 744 Phys Ed EXTERIOR 232MAXN 2 52.0 2 104 W 50% Yes 52 W 745 Phys Ed EXTERIOR 232MAXL 2 28.0 19 532 W 50% NO 266 W 748 Phys Sci OFFICE 112 232MAXH 2 70.0 4 280 W 50% NO 140 W 749 Phys Sci OFFICE 115 232MAXL 2 46.0 4 184 W 50% NO 92 W 750 Phys Sci HALLWAY CO1 232MAXN 2 52.0 12 624 W 50% NO 312 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 753 Phys Sci PHYSIC STORAGE RM 120 232MAXN 2 52.0 15 780 W 50% NO 390 W 754 Phys Sci PHYSIC STORAGE RM 120 232MAXN 2 52.0 6 312 W 50% NO 156 W 755 Phys Sci PHYSIC STORAGE RM 120 232MAXL 2 46.0 6 276 W 50% NO 138 W 756 Phys Sci PHYSIC STORAGE RM 120 232MAXH 2 70.0 6 420 W 50% NO 210 W 757 Phys Sci TEACHER OFFICE 121 232MAXN 2 52.0 12 624 W 50% NO 312 W 758 Phys Sci MECHANICAL RM 129 232MAXN 2 52.0 4 208 W 50% NO 104 W 760 Phys Sci 1ST FLOOR HALLWAY #1 232MAXN 2 52.0 7 364 W 50% NO 182 W 761 Phys Sci 1ST FLOOR HALLWAY #2 232MAXN 2 52.0 6 312 W 50% NO 156 W 762 Phys Sci 1ST FLOOR HALLWAY #3 232MAXN 2 52.0 7 364 W 50% NO 182 W 764 Phys Sci 1ST FLOOR HALLWAY #5 2 40.0 6 240 W 50% NO 120 W 767 Phys Sci ELECTRICAL RM BY 202 232MAXN 2 52.0 2 104 W 50% Yes 52 W 771 Phys Sci OFFICE 206 232MAXL 2 46.0 2 92 W 50% Yes 46 W 772 Phys Sci OFFICE 210 432MAXL 4 91.0 2 182 W 50% NO 91 W 773 Phys Sci OFFICE 212 232MAXN 2 52.0 4 208 W 50% NO 104 W 774 Phys Sci OFFICE 213 232MAXN 2 52.0 6 312 W 50% NO 156 W 777 Phys Sci OFFICE 216 232MAXN 2 52.0 4 208 W 50% NO 104 W 778 Phys Sci OFFICE 217 232MAXN 2 52.0 4 208 W 50% NO 104 W 779 Phys Sci OFFICE 218 232MAXN 2 52.0 9 468 W 50% NO 234 W 780 Phys Sci 2ND FLOOR HALLWAY #1 432MAXL 2 45.5 8 364 W 50% NO 182 W 781 Phys Sci 2ND FLOOR HALLWAY #2 432MAXL 2 45.5 7 319 W 50% NO 159 W 782 Phys Sci 2ND FLOOR HALLWAY #2 1 25.0 7 175 W 50% NO 88 W 783 Phys Sci 2ND FLOOR HALLWAY #3 1 25.0 4 100 W 50% NO 50 W 784 Phys Sci 2ND FLOOR HALLWAY #4 1 25.0 8 200 W 50% NO 100 W 787 Phys Sci LAB STORAGE 300 432MAXL 2 45.5 12 546 W 50% NO 273 W 788 Phys Sci STORAGE 102 232MAXN 2 52.0 3 156 W 50% NO 78 W 789 Phys Sci STORAGE 102 232MAXN 2 52.0 4 208 W 50% NO 104 W 790 Phys Sci MECHANICAL ROOM 232MAXN 2 52.0 2 104 W 50% Yes 52 W 791 Phys Sci EXTERIOR 1 25.0 13 325 W 50% NO 163 W 795 Student Serv OFFICE 144 432MAXL 2 45.5 4 182 W 50% NO 91 W 796 Student Serv OFFICE 144 232MAXL 2 46.0 2 92 W 50% Yes 46 W 799 Student Serv OPEN OFFICE AREA 140 232MAXN 2 52.0 9 468 W 50% NO 234 W 800 Student Serv OPEN OFFICE AREA 140 232MAXN 2 52.0 7 364 W 50% NO 182 W 802 Student Serv DSPS OFFICE 160 232MAXN 2 52.0 8 416 W 50% NO 208 W 809 Student Serv SECURITY OFFICE RM 180 232MAXN 2 28.0 6 168 W 50% NO 84 W 810 Student Serv SECURITY OFFICE RM 180A 232MAXN 2 28.0 2 56 W 50% Yes 28 W 811 Student Serv 232MAXN 2 28.0 4 112 W 50% NO 56 W OFFICE 171 Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 814 Student Serv OFFICE 177 332MAXN 3 46.5 2 93 W 50% Yes 47 W 818 Student Serv ELECTRICAL RM 110A 232MAXN 2 52.0 4 208 W 50% NO 104 W 819 Student Serv ENTRANCE 100 232MAXN 2 52.0 3 156 W 50% NO 78 W 820 Student Serv ADMISSION RM 102 232MAXN 2 52.0 10 520 W 50% NO 260 W 821 Student Serv ADMISSION RM 102 432MAXL 4 91.0 12 1092 W 50% NO 546 W 829 Student Serv OFFICE 111 232MAXN 2 52.0 2 104 W 50% Yes 52 W 831 Student Serv OFFICE 111A 232MAXN 2 28.0 2 56 W 50% Yes 28 W 832 Student Serv OFFICE 111G 232MAXN 2 28.0 2 56 W 50% Yes 28 W 833 Student Serv OFFICE 111H 232MAXN 2 28.0 2 56 W 50% Yes 28 W 834 Student Serv HALLWAY 112 232MAXN 2 28.0 4 112 W 50% NO 56 W 840 Student Serv OFFICE 129 432MAXL 4 91.0 2 182 W 50% NO 91 W 842 Student Serv OFFICE 130 232MAXN 2 52.0 1 52 W 50% NO 26 W 845 Student Serv OFFICE 132 432MAXL 4 91.0 2 182 W 50% NO 91 W 847 Student Serv OFFICE 134 432MAXL 4 91.0 2 182 W 50% NO 91 W 857 Student Serv HALLWAY 139 232MAXN 2 28.0 12 336 W 50% NO 168 W 858 Student Serv HALLWAY 139 232MAXN 2 52.0 4 208 W 50% NO 104 W 859 Student Serv CAREER CENTER 232MAXN 2 52.0 12 624 W 50% NO 312 W 861 Student Serv OFFICE 280A 232MAXN 2 52.0 2 104 W 50% Yes 52 W 862 Student Serv OFFICE 280B 232MAXN 2 52.0 2 104 W 50% Yes 52 W 863 Student Serv OFFICE 280C 232MAXN 2 52.0 2 104 W 50% Yes 52 W 864 Student Serv OFFICE 280D 232MAXN 2 52.0 2 104 W 50% Yes 52 W 867 Student Serv OPEN OFFICE AREA 270 232MAXN 2 52.0 4 208 W 50% NO 104 W 52 W 869 Student Serv OFFICE 270A 232MAXN 2 52.0 2 104 W 50% Yes 870 Student Serv OFFICE 270C 232MAXN 2 52.0 2 104 W 50% Yes 52 W 871 Student Serv OFFICE 270D 232MAXN 2 52.0 3 156 W 50% NO 78 W 873 Student Serv HALLWAY 248 232MAXN 2 28.0 4 112 W 50% NO 56 W 874 Student Serv HALLWAY 248 232MAXN 2 52.0 5 260 W 50% YES 130 W 876 Student Serv OFFICE 251 232MAXN 2 52.0 6 312 W 50% NO 156 W 877 Student Serv HALLWAY 200 232MAXN 2 28.0 7 196 W 50% NO 98 W 878 Student Serv HALLWAY 200 232MAXN 2 52.0 8 416 W 50% NO 208 W 879 Student Serv HALLWAY 200 232MAXN 2 52.0 9 468 W 50% YES 234 W 882 Student Serv OFFICE 240K 332MAXN 3 46.5 10 465 W 50% NO 233 W 883 Student Serv OFFICE 240G 332MAXN 3 46.5 11 512 W 50% NO 256 W 884 Student Serv OFFICE 240L 332MAXN 3 46.5 12 558 W 50% NO 279 W 885 Student Serv OFFICE 240D 232MAXL 2 46.0 13 598 W 50% NO 299 W 886 Student Serv OFFICE 240M 332MAXL 3 68.0 14 952 W 50% NO 476 W Serves # Bldg Lamp Data Area Size/Type Fixture Data Qty Watts Qty1 Full Load Normal Operation Load DR Operation W Rewire Required Demand Reduction (YES/NO) W 510 W 887 Student Serv OFFICE 240B 332MAXL 3 68.0 15 1020 W 50% NO 889 Student Serv OFFICE 240C 332MAXL 3 68.0 16 1088 W 50% NO 544 W 890 Student Serv CONFERENCE ROOM 240E 232MAXN 2 52.0 17 884 W 50% NO 442 W 891 Student Serv CONFERENCE ROOM 240E 232MAXN 2 52.0 18 936 W 50% NO 468 W 894 Student Serv OFFICE 240H 332MAXL 3 68.0 19 1292 W 50% NO 646 W 895 Student Serv OPEN OFFICE AREA 240 232MAXN 2 52.0 20 1040 W 50% NO 520 W 896 Student Serv OPEN OFFICE AREA 240 232MAXN 2 52.0 21 1092 W 50% YES 546 W 900 Student Serv OFFICE 213 332MAXL 3 68.0 22 1496 W 50% NO 748 W 903 Student Serv OFFICE 211 232MAXL 2 46.0 23 1058 W 50% NO 529 W 904 Student Serv OFFICE 214 332MAXL 3 68.0 24 1632 W 50% NO 816 W 906 Student Serv HALLWAY CO1 232MAXL 2 46.0 25 1150 W 50% NO 575 W 908 Student Serv STAFF LOUNGE 220 1 25.0 26 650 W 50% NO 325 W 911 Student Serv STAFF LOUNGE 220 232MAXN 2 28.0 27 756 W 50% NO 378 W 912 Student Serv OFFICE 230A 232MAXN 2 52.0 28 1456 W 50% NO 728 W 915 Student Serv OFFICE 230C 432MAXL 4 91.0 29 2639 W 50% NO 1320 W 916 Student Serv OFFICE 230D 432MAXL 4 91.0 30 2730 W 50% NO 1365 W 917 Student Serv OFFICE 230E 432MAXL 4 91.0 31 2821 W 50% NO 1411 W 919 Student Serv HALLWAY 210 232MAXN 2 28.0 32 896 W 50% NO 448 W 921 Student Serv OFFICE 260 332MAXL 3 68.0 33 2244 W 50% NO 1122 W 923 Student Serv OFFICE 260A 332MAXL 3 68.0 34 2312 W 50% NO 1156 W 930 Student Serv OLD PRINT SHOP (ADDED 5/0 432MAXN 2 51.5 35 1803 W 50% NO 901 W 931 Student Serv OLD PRINT SHOP (ADDED 5/0 232MAXN 2 52.0 36 1872 W 50% NO 936 W 932 Student Serv CAMPUS SECURITY (ADDED 5/ 432MAXN 2 51.5 37 1906 W 50% NO 953 W 3,844 225.6 kW Totals Note: (1) Lighting count based on available as-builts and onsite observations. (2) IIDF rooms, restrooms, and other areas not normally occupied were excluded from the demand reduction calculation. (3) Classrooms were excluded from the demand reduction calculation due to their particular lighting requirements. 113.5 kW CALCULATIONS Demand Response Measure # 6: Demand Reduction by Fountain Pump Shutdown Current Location Equipment Qty HP Load Factor Efficiency Status Demand Response Demand kW Status Demand kW * ** West Campus Water Feature 1 2 90% 85% ON 1.6 kW OFF 0.0 kW East Campus Water Fountain 1 2 90% 85% ON 1.6 kW OFF 0.0 kW Totals 2 * Current: [Demand kW] = [HP] x [Load Factor] x 0.7457 / [Efficiency] ** [Pump kW Reduction] = [Current Demand kW] - [Demand Response Demand kW] Notes: (1) Efficiency is based on motor size (HP) and Load Factor 3.2 kW Pump kW Reduction 1.6 kW 1.6 kW 3.2 kW CALCULATIONS Demand Response Measure # 7 Demand Reduction by Pre-Cool Refrigeration Spaces Current Manufacturer Equipment Qty Volts FLA Phase Maximum kW LRC Coil Company BC Walk-in Ref 1 115 4.4 1 0.5 kW LRC Coil Company BC Walk-in Freezer 1 230 18.8 1 4.3 kW Larkin Campus Ctr Ref 1 115 4.4 1 0.5 kW Demand Response Load Factor Diversity Factor Average kW 85% 60% .3 kW Diversity Factor Average kW *** **** 85% 20% 0.1 kW .2 kW 85% 60% 2.2 kW 85% 85% 60% .3 kW 85% 20% 0.7 kW 1.5 kW 20% 0.1 kW .2 kW ** * Average kW Reduction Load Factor LRC Coil Company Campus Ctr Freezer 1 230 2.2 1 0.5 kW 85% 60% .3 kW 85% 20% 0.1 kW .2 kW LRC Coil Company Campus Ctr Freezer 230 3.3 1 0.8 kW 85% 60% .4 kW 85% 20% 0.1 kW .3 kW Bohn JSB Café Freezer 1 1 230 5.9 1 1.4 kW 85% 60% .7 kW 85% 20% 0.2 kW .5 kW Bohn JSB Café Ref 1 115 2.1 1 0.2 kW 85% 60% .1 kW 85% 20% 0.0 kW .1 kW 1.4 kW 2.8 kW Totals 7 * [Maximum kW] = [Quantity] x [Volts] x [FLA] x SQRT[Phase] / 1000 ** Current: [Average kW] = [Maximum kW] x [Load Factor] *** Demand Response: [Average kW] = [Maximum kW] x [Load Factor] **** [Average kW Reduction] = [Current Average kW] - [Demand Response Average kW] Notes: (1) Load Factor = Percentage of maximum electrical equipment load (2) Diversity Factor = Percentage of continuous running time 8.2 kW 4.2 kW CALCULATIONS Demand Response Measure # 8: Demand Reduction by Beverage Vending Machine Compressor Shutdown Current Manufacturer Equipment Quantity HP Load Factor Efficiency Status Demand Response Demand kW Status Demand kW * Vendo (Varies) Pepsi (Varies) Outdoor Ref Vending Machine Indoor Vending/Storage Units Totals 20 10 30 * Current: [Demand kW] = [HP] x [Load Factor] x 0.7457 / [Efficiency] ** [Pump kW Reduction] = [Current Demand kW] - [Demand Response Demand kW] Notes: (1) Efficiency is based on motor size (HP) and Load Factor (2) Compressor HP based on typical beverage vending machine compressor 1 3 30% 30% 85% 85% ON ON 4.5 kW 6.6 kW 11.1 kW Average kW Reduction ** OFF OFF 0.0 kW 0.0 kW 0.0 kW 4.5 kW 6.6 kW 11.1 kW APPENDIX APPENDIX "D" - TRACE 700 Building Energy Simulation Results TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 © 2013 SC ENGINEERS, INC. "D" ELECTRICAL PEAK CHECKSUMS By SC ENGINEERS Alternative 1 Santa Barbara City College Yearly Time of Peak: 15(Hr) 9(Month) Equipment Description Cooling Equipment Air Cooled CH - Scroll Pckg AC HP Sub total Fan Equipment Sys 12: IDC Fan Coil Sys 1: Admin VAV Sys 2: Admin FC Sys 3: Campus Center FC Sys 4: Campus Center Dual Deck Sys 5: Campus Center Packg RTU-1 Sys 6: Drama/Music HP Sys 7: Drama/Music Fan Coil Sys 8: Drama/Music MZU Sys 9: EBS VAV Sys 11: Humanities Fan Coil Sys 13: LRC VAV Sys 14: OE Pckg AH Sys 15: PE Heat Pump Sys 17: PS Fan Coil Htg Only Sys 18: Stdnt Srv VAV Sys 19: Admin Pckg AHU Sys 20: IDC VAV Sys 21: Portopia HP Sys 22: BC FC Sys 23: BC Hydronic AHU Sys 10: Humanities VAV Sub total Miscellaneous Misc Equipment Lights Base Utilities Sub total Total Alternative 2 Electrical Demand (kw) Percent of Total (%) 340.64 152.78 338.89 20.08 9.01 19.98 832.31 49.07 0.15 8.71 3.41 1.00 6.79 3.79 7.05 0.56 4.54 20.71 1.87 11.56 2.01 1.07 0.62 13.86 8.46 5.25 62.29 7.32 6.94 57.40 0.01 0.51 0.20 0.06 0.40 0.22 0.42 0.03 0.27 1.22 0.11 0.68 0.12 0.06 0.04 0.82 0.50 0.31 3.67 0.43 0.41 3.38 235.36 13.87 314.40 299.07 15.00 18.54 17.63 0.88 628.47 37.05 1,696.14 100 Electrical Demand (kw) Percent of Total (%) 338.89 20.16 SBCC CHWR Yearly Time of Peak: 15(Hr) 9(Month) Equipment Description Cooling Equipment HP Project Name: TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Dataset Name: SBCC TRACE.TRC Alternative - 2 Elect. Peak Checksums Report Page 1 of 4 ELECTRICAL PEAK CHECKSUMS By SC ENGINEERS DR Pckg AC 325.69 152.78 19.37 9.09 817.36 48.62 0.15 8.71 3.41 1.00 6.79 3.79 7.05 0.56 4.54 20.71 1.87 11.56 2.01 1.07 0.62 13.86 8.46 5.25 62.29 7.32 6.94 57.40 0.01 0.52 0.20 0.06 0.40 0.23 0.42 0.03 0.27 1.23 0.11 0.69 0.12 0.06 0.04 0.82 0.50 0.31 3.71 0.44 0.41 3.41 235.36 13.99 314.40 299.07 15.00 18.70 17.79 0.89 628.47 37.38 1,681.19 100 Electrical Demand (kw) Percent of Total (%) 329.76 165.53 373.45 16.86 8.46 19.09 868.74 44.41 0.16 6.10 3.88 2.05 0.01 0.31 0.20 0.10 Sub total Fan Equipment Sys 12: IDC Fan Coil Sys 1: Admin VAV Sys 2: Admin FC Sys 3: Campus Center FC Sys 4: Campus Center Dual Deck Sys 5: Campus Center Packg RTU-1 Sys 6: Drama/Music HP Sys 7: Drama/Music Fan Coil Sys 8: Drama/Music MZU Sys 9: EBS VAV Sys 11: Humanities Fan Coil Sys 13: LRC VAV Sys 14: OE Pckg AH Sys 15: PE Heat Pump Sys 17: PS Fan Coil Htg Only Sys 18: Stdnt Srv VAV Sys 19: Admin Pckg AHU Sys 20: IDC VAV Sys 21: Portopia HP Sys 22: BC FC Sys 23: BC Hydronic AHU Sys 10: Humanities VAV Sub total Miscellaneous Misc Equipment Lights Base Utilities Sub total Total Alternative 3 SBCC Class Temp Reduction Yearly Time of Peak: 19(Hr) 7(Month) Equipment Description Cooling Equipment Main Pckg AC HP Sub total Fan Equipment Sys 12: IDC Fan Coil Sys 1: Admin VAV Sys 2: Admin FC Sys 3: Campus Center FC Project Name: TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Dataset Name: SBCC TRACE.TRC Alternative - 3 Elect. Peak Checksums Report Page 2 of 4 ELECTRICAL PEAK CHECKSUMS By SC ENGINEERS Sys 4: Campus Center Dual Deck Sys 5: Campus Center Packg RTU-1 Sys 6: Drama/Music HP Sys 7: Drama/Music Fan Coil Sys 8: Drama/Music MZU Sys 9: EBS VAV Sys 11: Humanities Fan Coil Sys 13: LRC VAV Sys 14: OE Pckg AH Sys 15: PE Heat Pump Sys 17: PS Fan Coil Htg Only Sys 18: Stdnt Srv VAV Sys 19: Admin Pckg AHU Sys 20: IDC VAV Sys 21: Portopia HP Sys 22: BC FC Sys 23: BC Hydronic AHU Sys 10: Humanities VAV Sub total Miscellaneous Misc Equipment Lights Base Utilities Sub total Total Alternative 4 6.79 3.80 7.07 0.64 5.75 24.96 2.69 10.71 3.44 1.11 0.60 17.08 14.41 4.74 87.21 8.68 7.85 60.72 0.35 0.19 0.36 0.03 0.29 1.28 0.14 0.55 0.18 0.06 0.03 0.87 0.74 0.24 4.46 0.44 0.40 3.10 280.44 14.33 284.71 256.95 265.00 14.56 13.14 13.55 806.66 41.25 1,955.84 100 Electrical Demand (kw) Percent of Total (%) 373.45 333.00 165.53 19.06 16.99 8.45 871.98 44.50 0.16 6.43 3.88 2.05 6.79 3.80 7.07 0.64 5.75 24.96 2.69 10.71 3.44 0.01 0.33 0.20 0.10 0.35 0.19 0.36 0.03 0.29 1.27 0.14 0.55 0.18 SBCC Data Rm TR Yearly Time of Peak: 19(Hr) 7(Month) Equipment Description Cooling Equipment HP Main Pckg AC Sub total Fan Equipment Sys 12: IDC Fan Coil Sys 1: Admin VAV Sys 2: Admin FC Sys 3: Campus Center FC Sys 4: Campus Center Dual Deck Sys 5: Campus Center Packg RTU-1 Sys 6: Drama/Music HP Sys 7: Drama/Music Fan Coil Sys 8: Drama/Music MZU Sys 9: EBS VAV Sys 11: Humanities Fan Coil Sys 13: LRC VAV Sys 14: OE Pckg AH Project Name: TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Dataset Name: SBCC TRACE.TRC Alternative - 4 Elect. Peak Checksums Report Page 3 of 4 ELECTRICAL PEAK CHECKSUMS By SC ENGINEERS Sys 15: PE Heat Pump Sys 17: PS Fan Coil Htg Only Sys 18: Stdnt Srv VAV Sys 19: Admin Pckg AHU Sys 20: IDC VAV Sys 21: Portopia HP Sys 22: BC FC Sys 23: BC Hydronic AHU Sys 10: Humanities VAV Sub total Miscellaneous Lights Base Utilities Misc Equipment Sub total Total 1.11 0.60 17.08 14.41 4.74 87.21 8.68 7.85 60.72 0.06 0.03 0.87 0.74 0.24 4.45 0.44 0.40 3.10 280.77 14.33 256.95 265.00 284.71 13.11 13.52 14.53 806.66 41.16 1,959.41 100 Project Name: TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Dataset Name: SBCC TRACE.TRC Alternative - 4 Elect. Peak Checksums Report Page 4 of 4 ENERGY CONSUMPTION SUMMARY By SC ENGINEERS Elect Cons. (kWh) Gas Cons. (kBtu) % of Total Building Energy Total Building Energy (kBtu/yr) Total Source Energy* (kBtu/yr) Alternative 1 Primary heating Primary heating Other Htg Accessories Heating Subtotal 41,060 37,612 78,672 2,119,439 2,119,439 8.3 % 0.5 % 8.7 % 2,259,578 128,369 2,387,947 2,651,448 385,144 3,036,592 Primary cooling Cooling Compressor Tower/Cond Fans Condenser Pump Other Clg Accessories Cooling Subtotal.... 944,597 134,802 6,590 1,085,989 11.8 1.7 0.0 0.1 13.6 % % % % % 3,223,909 460,078 0 22,492 3,706,479 9,672,694 1,380,373 0 67,483 11,120,549 531,787 212,765 1,317,650 2,062,202 6.7 2.7 16.5 25.8 % % % % 1,814,990 726,167 4,497,139 7,038,296 5,445,516 2,178,718 13,492,767 21,117,000 1,834,367 22.9 % 6,260,693 18,783,956 2,319,306 29.0 % 7,915,790 23,749,744 0.0 % 0 0 100.0 % 27,309,205 77,807,848 Auxiliary Supply Fans Pumps Stand-alone Base Utilities Aux Subtotal.... Lighting Lighting Receptacle Receptacles Cogeneration Cogeneration Totals Totals** 7,380,535 2,119,439 * Note: Resource Utilization factors are included in the Total Source Energy value. ** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total. Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Energy Consumption Summary report page 1 ENERGY CONSUMPTION SUMMARY By SC ENGINEERS Elect Cons. (kWh) Gas Cons. (kBtu) % of Total Building Energy Total Building Energy (kBtu/yr) Total Source Energy* (kBtu/yr) Alternative 2 Primary heating Primary heating Other Htg Accessories Heating Subtotal 41,060 37,612 78,672 2,119,439 2,119,439 8.3 % 0.5 % 8.8 % 2,259,578 128,369 2,387,947 2,651,448 385,144 3,036,592 Primary cooling Cooling Compressor Tower/Cond Fans Condenser Pump Other Clg Accessories Cooling Subtotal.... 928,848 134,376 6,590 1,069,814 11.6 1.7 0.0 0.1 13.4 % % % % % 3,170,157 458,626 0 22,492 3,651,275 9,511,421 1,376,015 0 67,483 10,954,919 531,787 212,765 1,317,650 2,062,202 6.7 2.7 16.5 25.8 % % % % 1,814,990 726,167 4,497,139 7,038,296 5,445,516 2,178,718 13,492,767 21,117,000 1,834,367 23.0 % 6,260,693 18,783,956 2,319,306 29.0 % 7,915,790 23,749,744 0.0 % 0 0 100.0 % 27,254,001 77,642,216 Auxiliary Supply Fans Pumps Stand-alone Base Utilities Aux Subtotal.... Lighting Lighting Receptacle Receptacles Cogeneration Cogeneration Totals Totals** 7,364,361 2,119,439 * Note: Resource Utilization factors are included in the Total Source Energy value. ** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total. Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Energy Consumption Summary report page 1 ENERGY CONSUMPTION SUMMARY By SC ENGINEERS Elect Cons. (kWh) Gas Cons. (kBtu) % of Total Building Energy Total Building Energy (kBtu/yr) Total Source Energy* (kBtu/yr) Alternative 3 Primary heating Primary heating Other Htg Accessories Heating Subtotal 40,315 38,485 78,800 2,109,047 2,109,047 8.4 % 0.5 % 8.9 % 2,246,642 131,348 2,377,991 2,632,878 394,084 3,026,962 Primary cooling Cooling Compressor Tower/Cond Fans Condenser Pump Other Clg Accessories Cooling Subtotal.... 841,834 122,858 6,587 971,279 10.7 1.6 0.0 0.1 12.3 % % % % % 2,873,178 419,315 0 22,481 3,314,974 8,620,397 1,258,070 0 67,448 9,945,915 514,000 216,644 1,317,650 2,048,294 6.5 2.8 16.7 26.0 % % % % 1,754,281 739,407 4,497,139 6,990,828 5,263,371 2,218,443 13,492,767 20,974,580 1,834,367 23.3 % 6,260,693 18,783,956 2,319,306 29.5 % 7,915,790 23,749,744 0.0 % 0 0 100.0 % 26,860,275 76,481,152 Auxiliary Supply Fans Pumps Stand-alone Base Utilities Aux Subtotal.... Lighting Lighting Receptacle Receptacles Cogeneration Cogeneration Totals Totals** 7,252,045 2,109,047 * Note: Resource Utilization factors are included in the Total Source Energy value. ** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total. Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Energy Consumption Summary report page 1 ENERGY CONSUMPTION SUMMARY By SC ENGINEERS Elect Cons. (kWh) Gas Cons. (kBtu) % of Total Building Energy Total Building Energy (kBtu/yr) Total Source Energy* (kBtu/yr) Alternative 4 Primary heating Primary heating Other Htg Accessories Heating Subtotal 40,315 38,485 78,800 2,109,040 2,109,040 8.4 % 0.5 % 8.9 % 2,246,636 131,348 2,377,984 2,632,871 394,084 3,026,955 Primary cooling Cooling Compressor Tower/Cond Fans Condenser Pump Other Clg Accessories Cooling Subtotal.... 838,964 122,530 6,587 968,081 10.7 1.6 0.0 0.1 12.3 % % % % % 2,863,385 418,195 0 22,481 3,304,060 8,591,014 1,254,710 0 67,448 9,913,172 513,328 216,644 1,317,650 2,047,623 6.5 2.8 16.8 26.0 % % % % 1,751,989 739,407 4,497,139 6,988,536 5,256,493 2,218,443 13,492,767 20,967,702 1,834,367 23.3 % 6,260,693 18,783,956 2,319,306 29.5 % 7,915,790 23,749,744 0.0 % 0 0 100.0 % 26,847,063 76,441,528 Auxiliary Supply Fans Pumps Stand-alone Base Utilities Aux Subtotal.... Lighting Lighting Receptacle Receptacles Cogeneration Cogeneration Totals Totals** 7,248,176 2,109,040 * Note: Resource Utilization factors are included in the Total Source Energy value. ** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total. Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Energy Consumption Summary report page 1 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total Electric (kWh) Peak (kW) 155,785.6 300.2 140,710.4 300.2 155,825.9 300.2 150,753.8 300.2 155,805.8 300.2 150,794.1 300.2 155,765.6 300.2 155,825.9 300.2 150,753.9 300.2 155,805.9 300.2 150,774.0 300.2 155,765.6 300.2 1,834,366.4 300.2 Electric (kWh) Peak (kW) 196,983.9 315.2 177,920.8 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,623.4 315.2 196,987.6 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,627.1 315.2 196,987.6 315.2 2,319,305.5 315.2 3.0 0.1 1.0 0.0 2.4 0.0 10.1 0.1 16.3 0.1 23.8 0.1 37.7 0.2 39.2 0.2 43.1 0.2 10.2 0.1 9.2 0.1 1.9 0.1 197.8 0.2 60,450.0 150.0 54,600.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 711,750.0 150.0 11,160.0 15.0 10,080.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 131,400.0 15.0 40,300.0 100.0 36,400.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 474,500.0 100.0 57,154.1 275.3 55,607.7 267.6 58,909.1 290.6 46,270.8 250.9 24,784.6 210.2 5,482.2 159.9 390,288.9 290.6 Lights Misc. Ld Cooling Coil Condensate Recoverable Water (1000gal) Peak (1000gal/Hr) Bsu 1: Parking lot lights Electric (kWh) Peak (kW) Bsu 2: Decorative Fountains Electric (kWh) Peak (kW) Bsu 3: Stadium Lights Electric (kWh) Peak (kW) Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Air Cooled CH - Scroll [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] Electric (kWh) Peak (kW) 7,804.3 163.6 16,897.3 198.9 17,551.9 187.1 17,618.9 187.3 38,818.7 236.9 (Cooling Equipment) 43,389.2 233.7 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) Project Name: Dataset Name: 1,017.9 19.2 1,886.1 25.7 2,043.9 23.1 2,148.2 24.5 4,323.2 32.5 4,927.6 32.2 6,781.5 36.6 6,568.6 36.0 7,167.1 38.0 4,925.9 32.9 2,724.9 27.8 736.5 18.3 45,251.4 38.0 7,852.7 18.7 8,114.5 18.7 8,413.7 18.7 9,273.7 18.7 9,853.3 18.7 9,535.5 18.7 8,694.1 18.7 8,413.7 18.7 8,114.5 18.7 101,823.9 18.7 (Misc Accessory Equipment) 8,114.5 18.7 SBCC TRACE.TRC 7,329.2 18.7 8,114.5 18.7 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 1 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 434.0 1.0 450.0 1.0 496.0 1.0 527.0 1.0 510.0 1.0 465.0 1.0 450.0 1.0 434.0 1.0 5,446.0 1.0 25,561.1 137.0 24,413.2 133.6 24,620.3 141.0 17,356.0 123.9 11,005.1 94.9 6,311.4 65.0 186,244.5 141.0 Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Cntl panel & interlocks - 1 KW (Misc Accessory Equipment) Electric (kWh) Peak (kW) 434.0 1.0 392.0 1.0 434.0 1.0 420.0 1.0 Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons] Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW] Electric (kWh) Peak (kW) 7,195.2 68.2 8,442.3 85.9 10,275.2 85.6 (Cooling Equipment) 12,448.5 92.4 18,670.5 119.8 19,945.8 117.9 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW] Electric (kWh) Peak (kW) 1,000.7 9.1 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 1,155.4 11.2 1,414.1 11.3 1,720.8 12.3 2,537.8 15.5 2,713.7 15.4 3,435.7 17.5 3,294.8 17.2 3,299.1 17.9 2,311.1 15.6 1,501.2 12.3 879.5 8.7 25,263.9 17.9 43.4 0.1 42.0 0.1 43.4 0.1 43.4 0.1 42.0 0.1 43.4 0.1 42.0 0.1 43.4 0.1 511.0 0.1 (Misc Accessory Equipment) 43.4 0.1 39.2 0.1 43.4 0.1 42.0 0.1 Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW] Electric (kWh) Peak (kW) 10,591.2 143.5 14,300.4 198.8 19,335.6 209.3 HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW] Electric (kWh) Peak (kW) HP 7,170.9 252.5 3,032.1 243.8 3,580.8 215.9 26,810.3 228.0 39,915.7 283.1 42,346.6 282.8 (Cooling Equipment - Cooling Mode) 53,407.1 308.1 50,651.4 296.9 49,940.1 297.2 32,736.0 238.8 18,821.8 217.2 9,207.4 139.5 368,063.4 308.1 (Cooling Equipment - Heating Mode) 1,918.0 161.8 1,826.4 157.6 603.9 135.3 255.1 115.0 258.7 115.0 416.7 125.9 3,097.9 169.0 4,591.5 217.4 14,308.3 282.6 41,060.4 282.6 126.1 1.1 108.8 0.8 102.7 0.8 104.2 0.8 99.5 1.0 146.1 1.8 188.1 2.0 173.6 1.7 1,711.5 2.0 (Cooling Equipment - Heat Recovered From Condenser Loop) Heat Recovered (therms) Peak (therms/Hr) 149.7 1.0 153.1 1.1 194.6 1.5 165.1 1.9 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW] Electric (kWh) Peak (kW) 2,580.6 25.9 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) Project Name: Dataset Name: SBCC TRACE.TRC 61.3 0.1 2,581.9 31.3 3,457.2 32.1 4,544.0 34.6 6,730.0 43.3 7,004.2 43.2 8,748.4 47.2 8,307.1 45.4 8,182.2 45.5 5,594.0 40.0 3,492.1 33.2 3,065.0 25.1 64,286.5 47.2 62.5 0.1 57.4 0.1 52.8 0.1 55.1 0.1 55.3 0.1 61.1 0.1 58.3 0.1 74.4 0.1 703.8 0.1 (Misc Accessory Equipment) 48.1 0.1 57.0 0.1 60.5 0.1 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 2 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh] Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms] Gas (therms) Peak (therms/Hr) Cnst vol cnd water pump Electric (kWh) Peak (kW) Boiler forced draft fan 2,537.3 13.8 2,138.1 11.3 1,925.6 10.4 10,457.4 14.1 1,972.2 2.7 Electric (kWh) Peak (kW) Aug Sept Oct Nov Dec Total (Heating Equipment) 923.2 5.7 734.5 4.2 460.1 3.1 357.8 2.1 366.6 2.2 401.2 2.9 1,070.3 6.5 1,470.7 8.0 2,689.4 11.3 15,074.7 13.8 9,445.4 14.1 10,457.4 14.1 10,120.0 14.1 8,714.5 14.1 8,433.4 14.1 8,053.9 14.1 8,377.2 14.1 7,590.0 14.1 8,714.5 14.1 10,120.1 14.1 10,457.4 14.1 110,941.0 14.1 372.0 0.5 1,781.3 2.7 1,972.2 2.7 1,908.5 2.7 1,643.5 2.7 1,590.5 2.7 1,518.9 2.7 1,579.9 2.7 1,431.4 2.7 1,643.5 2.7 1,908.5 2.7 1,972.2 2.7 20,922.4 2.7 310.0 0.5 300.0 0.5 286.5 0.5 298.0 0.5 270.0 0.5 310.0 0.5 360.0 0.5 372.0 0.5 3,946.5 0.5 (Misc Accessory Equipment) 336.0 0.5 372.0 0.5 360.0 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms] Gas (therms) Peak (therms/Hr) 568.0 4.3 471.9 3.5 438.2 3.1 (Heating Equipment) 232.5 2.2 168.2 1.7 110.8 1.3 74.6 1.0 75.9 0.9 74.7 0.9 222.3 2.6 326.7 3.0 588.0 3.5 3,351.6 4.3 731.9 1.0 690.3 1.0 617.6 1.0 580.1 1.0 649.8 1.0 592.6 1.0 498.0 1.0 699.7 1.0 773.5 1.0 8,079.1 1.0 332.0 0.5 297.0 0.5 279.0 0.5 312.5 0.5 285.0 0.5 239.5 0.5 336.5 0.5 372.0 0.5 3,885.5 0.5 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 773.5 1.0 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 372.0 0.5 698.6 1.0 773.5 1.0 (Misc Accessory Equipment) 336.0 0.5 372.0 0.5 352.0 0.5 Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh] Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms] Gas (therms) Peak (therms/Hr) 799.1 14.4 1,328.8 15.4 640.2 13.8 (Heating Equipment) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2,768.1 15.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 589.6 2.5 (Misc Accessory Equipment) Electric (kWh) Peak (kW) Project Name: Dataset Name: July (Misc Accessory Equipment) Cntl panel & interlocks - 0.5 KW Boiler forced draft fan June (Misc Accessory Equipment) Electric (kWh) Peak (kW) Boiler forced draft fan May SBCC TRACE.TRC 154.9 2.5 279.8 2.5 154.9 2.5 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 3 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 118.0 0.5 1,934.3 8.3 2,127.3 8.7 2,044.4 8.7 1,965.5 8.7 2,011.2 8.7 1,991.1 8.5 2,334.1 8.7 24,698.3 8.7 586.3 3.3 663.8 3.4 653.2 3.5 640.3 3.7 631.5 3.6 545.5 3.2 568.9 3.1 7,248.5 3.7 372.9 2.1 321.5 1.8 282.7 1.4 320.4 1.1 302.5 1.8 379.1 1.4 4,181.6 2.2 2,424.9 6.8 2,426.1 6.8 2,342.4 6.8 2,291.7 6.8 2,009.3 6.8 2,041.1 6.8 26,422.4 6.8 1,261.4 3.8 1,232.4 3.8 1,166.2 3.8 1,055.3 3.7 905.1 3.3 798.1 3.0 12,346.9 3.8 1,863.2 7.0 1,823.6 6.9 1,801.3 7.4 1,733.4 7.2 1,483.3 6.6 1,696.1 6.1 20,258.4 7.4 Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh] Cntl panel & interlocks - 0.5 KW (Misc Accessory Equipment) Electric (kWh) Peak (kW) 31.0 0.5 56.0 0.5 31.0 0.5 0.0 0.0 Sys 1: Admin VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW] Electric (kWh) Peak (kW) 2,366.7 8.7 2,023.1 8.7 2,032.4 8.4 1,816.3 8.7 Sys 2: Admin FC Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW] Electric (kWh) Peak (kW) 578.6 3.3 573.3 3.2 620.7 3.0 (Main Clg Fan) 549.6 3.2 Sys 3: Campus Center FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW] Electric (kWh) Peak (kW) 336.9 1.4 358.8 1.5 381.9 1.5 313.6 1.6 Sys 4: Campus Center Dual Deck AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW] Electric (kWh) Peak (kW) 2,064.2 6.0 1,863.1 6.8 2,161.8 6.8 2,104.7 6.8 Sys 5: Campus Center Packg RTU-1 AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW] Electric (kWh) Peak (kW) 825.8 3.3 787.7 3.4 945.1 3.5 1,052.6 3.6 Sys 6: Drama/Music HP AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW] Electric (kWh) Peak (kW) 1,596.5 6.0 1,580.5 6.5 1,705.2 5.9 (Main Clg Fan) 2,051.9 8.7 1,560.5 6.1 636.8 3.3 (Main Clg Fan) 429.0 2.1 382.5 2.2 (Main Clg Fan) 2,427.7 6.8 2,265.5 6.8 (Main Clg Fan) 1,148.3 3.8 1,169.0 3.8 (Main Clg Fan) 1,752.8 6.8 1,662.2 6.6 Sys 7: Drama/Music Fan Coil Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 4 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 7: Drama/Music Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW] Electric (kWh) Peak (kW) 111.6 0.6 94.6 0.6 96.4 0.6 May 766.5 4.6 731.5 4.4 826.7 4.1 68.8 0.5 857.8 4.6 2,766.0 12.0 2,664.3 16.8 2,867.7 17.4 2,945.8 18.1 9,536.2 43.5 9,096.7 50.5 9,855.1 44.9 8,773.8 38.5 Sys 11: Humanities Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW] Electric (kWh) Peak (kW) 221.6 2.3 256.6 2.2 331.3 2.4 Electric (kWh) Peak (kW) 24.1 0.1 24.5 0.1 31.1 0.1 3,185.3 11.6 2,814.6 11.6 2,895.4 11.6 Nov Dec Total 66.0 0.5 78.2 0.5 73.8 0.6 73.3 0.6 80.4 0.6 83.2 0.6 110.0 0.6 996.6 0.6 1,071.9 4.4 1,062.9 4.5 1,046.1 4.8 969.6 4.7 787.8 4.5 697.9 3.5 10,771.4 4.8 4,158.9 25.0 3,964.9 23.5 3,790.5 22.8 3,131.2 21.5 2,416.5 15.9 2,859.8 12.1 38,717.2 25.0 9,796.9 39.8 11,124.9 44.9 11,138.7 48.1 11,616.0 57.4 10,518.5 61.3 8,480.1 51.4 9,285.7 41.7 119,088.3 61.3 447.0 2.7 479.0 2.7 444.6 2.6 384.9 2.6 338.5 2.2 244.5 2.1 220.2 2.2 4,178.9 2.7 47.0 0.2 51.5 0.2 49.3 0.2 45.8 0.2 38.6 0.2 30.3 0.1 22.9 0.1 449.0 0.2 2,208.9 10.9 2,226.5 11.0 2,291.2 11.6 2,479.2 11.6 2,658.7 11.6 3,315.0 11.6 30,732.7 11.6 962.6 4.1 3,627.0 23.3 (Main Clg Fan) 456.0 2.7 (Main Clg Fan) 38.9 0.1 45.2 0.2 Sys 13: LRC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW] Electric (kWh) Peak (kW) Oct (Main Clg Fan) 9,865.7 41.9 354.7 2.5 Sys 12: IDC Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW] Sept (Main Clg Fan) 3,524.6 23.7 Sys 10: Humanities VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW] Electric (kWh) Peak (kW) Aug (Main Clg Fan) 990.1 4.4 Sys 9: EBS VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) 60.2 0.6 Sys 8: Drama/Music MZU 90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW] Electric (kWh) Peak (kW) June 2,192.9 7.7 (Main Clg Fan) 2,379.9 9.9 2,085.2 9.3 Sys 14: OE Pckg AH Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 5 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May Sys 14: OE Pckg AH FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW] Electric (kWh) Peak (kW) 354.9 1.8 353.2 1.9 362.3 1.6 309.8 1.3 313.0 1.3 348.9 1.4 391.3 2.2 37.2 1.3 12.1 0.4 3.3 0.1 353.5 3.1 Electric (kWh) Peak (kW) 301.1 0.8 273.4 0.8 301.8 0.8 0.3 0.0 3,465.7 13.6 3,054.7 12.9 3,467.3 15.2 289.8 0.8 3,005.2 12.4 1,234.1 5.2 1,217.7 6.2 1,399.7 6.1 1,519.7 6.0 Sys 20: IDC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW] Electric (kWh) Peak (kW) 1,258.8 4.4 1,142.1 5.1 1,287.6 4.6 Nov Dec Total 426.7 2.4 429.5 2.2 449.1 2.1 403.5 2.2 315.8 2.0 365.9 1.7 4,555.4 2.4 444.2 3.4 380.1 3.2 353.5 3.2 370.1 1.7 309.0 1.0 273.1 1.2 4,103.2 3.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.3 0.0 0.4 0.0 31.4 0.4 85.5 1.3 285.7 0.8 315.4 0.8 317.5 0.8 305.0 0.8 293.1 0.8 290.8 0.8 305.5 0.8 3,565.2 0.8 3,552.1 16.4 3,388.5 15.5 3,285.0 15.0 3,450.1 16.6 3,218.2 17.1 3,314.7 13.8 39,813.8 17.1 2,165.1 10.0 1,934.5 8.8 1,737.1 8.6 1,568.4 7.7 1,263.9 5.9 1,187.8 4.9 19,055.3 10.2 1,440.4 4.6 1,460.0 4.9 1,459.7 5.4 1,429.3 5.4 1,290.5 5.3 1,220.3 4.6 15,977.2 5.4 381.4 2.2 342.0 3.3 1,297.2 4.5 (Main Clg Fan) 3,374.4 15.5 Sys 19: Admin Pckg AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW] Electric (kWh) Peak (kW) Oct (Main Clg Fan) 286.2 0.8 Sys 18: Stdnt Srv VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW] Electric (kWh) Peak (kW) Sept (Main Clg Fan) 0.5 0.0 Sys 17: PS Fan Coil Htg Only Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW] Aug (Main Clg Fan) 306.1 1.0 Sys 16: PE VAV Htg Only FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) 322.0 1.5 Sys 15: PE Heat Pump FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW] Electric (kWh) Peak (kW) June 3,237.9 15.2 (Main Clg Fan) 1,888.2 9.1 1,939.2 10.2 (Main Clg Fan) 1,362.7 4.6 1,328.7 4.4 Sys 21: Portopia HP Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 6 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 1 Santa Barbara City College ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May Sys 21: Portopia HP FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW] Electric (kWh) Peak (kW) 8,120.3 41.6 8,501.0 50.6 8,501.8 49.5 7,807.4 48.6 Sys 22: BC FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW] Electric (kWh) Peak (kW) 1,899.4 7.4 1,781.9 7.7 1,948.2 6.8 1,525.5 6.2 Sys 23: BC Hydronic AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 1,354.9 5.1 SBCC TRACE.TRC 1,238.5 5.9 1,258.3 5.4 1,012.3 4.7 June July Aug Sept Oct Nov Dec Total 11,268.1 67.5 10,776.1 64.4 10,538.1 66.9 9,078.9 62.7 6,961.7 49.0 8,077.0 39.4 109,493.0 67.5 1,716.5 6.9 1,704.0 7.4 1,797.4 8.2 1,853.2 8.1 1,548.4 7.9 1,842.4 7.3 21,001.6 8.2 1,150.2 5.8 1,143.8 6.1 1,177.1 7.3 1,238.2 7.3 1,068.3 6.1 1,233.7 5.0 14,047.1 7.3 (Main Clg Fan) 10,073.5 63.2 9,789.2 61.9 (Main Clg Fan) 1,810.9 6.4 1,573.8 6.5 (Main Clg Fan) 1,139.8 5.3 1,032.1 5.0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 1 Equipment Energy Consumption report page 7 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total Electric (kWh) Peak (kW) 155,785.6 300.2 140,710.4 300.2 155,825.9 300.2 150,753.8 300.2 155,805.8 300.2 150,794.1 300.2 155,765.6 300.2 155,825.9 300.2 150,753.9 300.2 155,805.9 300.2 150,774.0 300.2 155,765.6 300.2 1,834,366.4 300.2 Electric (kWh) Peak (kW) 196,983.9 315.2 177,920.8 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,623.4 315.2 196,987.6 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,627.1 315.2 196,987.6 315.2 2,319,305.5 315.2 3.0 0.1 1.0 0.0 2.4 0.0 10.1 0.1 16.3 0.1 23.8 0.1 37.7 0.2 39.2 0.2 43.1 0.2 10.2 0.1 9.2 0.1 1.9 0.1 197.8 0.2 60,450.0 150.0 54,600.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 711,750.0 150.0 11,160.0 15.0 10,080.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 131,400.0 15.0 40,300.0 100.0 36,400.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 474,500.0 100.0 15,652.3 209.5 15,607.9 201.3 16,925.7 198.5 7,968.6 179.6 3,907.9 138.7 401.0 112.9 83,193.7 209.5 Lights Misc. Ld Cooling Coil Condensate Recoverable Water (1000gal) Peak (1000gal/Hr) Bsu 1: Parking lot lights Electric (kWh) Peak (kW) Bsu 2: Decorative Fountains Electric (kWh) Peak (kW) Bsu 3: Stadium Lights Electric (kWh) Peak (kW) Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Main [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] (Cooling Equipment) Electric (kWh) Peak (kW) 677.0 113.5 1,285.4 128.4 1,353.1 125.2 2,714.9 138.6 5,848.7 175.0 10,851.3 186.0 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) Project Name: Dataset Name: 108.0 8.1 178.1 10.8 195.9 12.0 374.3 16.1 735.3 22.7 1,311.6 25.0 1,831.4 29.1 1,826.7 27.6 1,950.5 26.2 909.1 21.2 486.1 14.5 66.7 6.6 9,973.6 29.1 3,365.5 18.7 3,477.7 18.7 3,926.4 18.7 4,636.9 18.7 5,216.5 18.7 5,048.2 18.7 4,057.3 18.7 3,926.4 18.7 3,477.7 18.7 47,228.7 18.7 (Misc Accessory Equipment) 3,477.7 18.7 SBCC TRACE.TRC 3,141.1 18.7 3,477.7 18.7 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 8 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 186.0 1.0 210.0 1.0 248.0 1.0 279.0 1.0 270.0 1.0 217.0 1.0 210.0 1.0 186.0 1.0 2,526.0 1.0 30,869.3 221.7 39,373.5 261.2 37,948.5 253.9 39,830.3 275.7 36,337.9 238.0 19,806.0 199.4 4,820.6 151.7 291,345.9 275.7 Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Cntl panel & interlocks - 1 KW (Misc Accessory Equipment) Electric (kWh) Peak (kW) 186.0 1.0 168.0 1.0 186.0 1.0 180.0 1.0 DR [Clg Nominal Capacity/F.L.Rate=369.0 tons / 455.1 kW] Electric (kWh) Peak (kW) 6,761.8 155.2 14,811.3 188.7 15,368.1 177.5 (Cooling Equipment) 14,139.7 177.7 31,279.1 224.8 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=498.4 tons / 47.35 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) 900.0 19.0 1,686.4 25.4 1,825.5 22.9 1,753.2 24.3 3,542.3 32.1 3,570.8 31.9 4,892.6 36.2 4,686.5 35.7 5,158.5 37.6 3,963.8 32.5 2,209.9 27.5 662.8 18.1 34,852.2 37.6 4,487.3 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 54,595.3 18.7 248.0 1.0 240.0 1.0 248.0 1.0 248.0 1.0 240.0 1.0 248.0 1.0 240.0 1.0 248.0 1.0 2,920.0 1.0 25,561.1 137.0 24,413.2 133.6 24,620.3 141.0 17,356.0 123.9 11,005.1 94.9 6,311.4 65.0 186,244.5 141.0 (Misc Accessory Equipment) 4,636.9 18.7 Cntl panel & interlocks - 1 KW Electric (kWh) Peak (kW) 4,188.1 18.7 4,636.9 18.7 (Misc Accessory Equipment) 248.0 1.0 224.0 1.0 248.0 1.0 240.0 1.0 Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons] Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW] Electric (kWh) Peak (kW) 7,195.2 68.2 8,442.3 85.9 10,275.2 85.6 (Cooling Equipment) 12,448.5 92.4 18,670.5 119.8 19,945.8 117.9 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW] Electric (kWh) Peak (kW) 1,000.7 9.1 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 1,155.4 11.2 1,414.1 11.3 1,720.8 12.3 2,537.8 15.5 2,713.7 15.4 3,435.7 17.5 3,294.8 17.2 3,299.1 17.9 2,311.1 15.6 1,501.2 12.3 879.5 8.7 25,263.9 17.9 43.4 0.1 42.0 0.1 43.4 0.1 43.4 0.1 42.0 0.1 43.4 0.1 42.0 0.1 43.4 0.1 511.0 0.1 32,736.0 238.8 18,821.8 217.2 9,207.4 139.5 368,063.4 308.1 (Misc Accessory Equipment) 43.4 0.1 39.2 0.1 43.4 0.1 42.0 0.1 Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 10,591.2 143.5 SBCC TRACE.TRC 14,300.4 198.8 19,335.6 209.3 26,810.3 228.0 39,915.7 283.1 42,346.6 282.8 (Cooling Equipment - Cooling Mode) 53,407.1 308.1 50,651.4 296.9 49,940.1 297.2 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 9 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW] Electric (kWh) Peak (kW) HP 7,170.9 252.5 3,032.1 243.8 3,580.8 215.9 Apr May June July Aug Sept Oct Nov Dec Total (Cooling Equipment - Heating Mode) 1,918.0 161.8 1,826.4 157.6 603.9 135.3 255.1 115.0 258.7 115.0 416.7 125.9 3,097.9 169.0 4,591.5 217.4 14,308.3 282.6 41,060.4 282.6 126.1 1.1 108.8 0.8 102.7 0.8 104.2 0.8 99.5 1.0 146.1 1.8 188.1 2.0 173.6 1.7 1,711.5 2.0 (Cooling Equipment - Heat Recovered From Condenser Loop) Heat Recovered (therms) Peak (therms/Hr) 149.7 1.0 153.1 1.1 194.6 1.5 165.1 1.9 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW] Electric (kWh) Peak (kW) 2,580.6 25.9 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 2,581.9 31.3 3,457.2 32.1 4,544.0 34.6 Cnst vol cnd water pump Electric (kWh) Peak (kW) Boiler forced draft fan 8,748.4 47.2 8,307.1 45.4 8,182.2 45.5 5,594.0 40.0 3,492.1 33.2 3,065.0 25.1 64,286.5 47.2 48.1 0.1 57.0 0.1 60.5 0.1 62.5 0.1 57.4 0.1 52.8 0.1 55.1 0.1 55.3 0.1 61.1 0.1 58.3 0.1 74.4 0.1 703.8 0.1 2,537.3 13.8 2,138.1 11.3 1,925.6 10.4 (Heating Equipment) 923.2 5.7 734.5 4.2 460.1 3.1 357.8 2.1 366.6 2.2 401.2 2.9 1,070.3 6.5 1,470.7 8.0 2,689.4 11.3 15,074.7 13.8 10,120.0 14.1 8,714.5 14.1 8,433.4 14.1 8,053.9 14.1 8,377.2 14.1 7,590.0 14.1 8,714.5 14.1 10,120.1 14.1 10,457.4 14.1 110,941.0 14.1 1,908.5 2.7 1,643.5 2.7 1,590.5 2.7 1,518.9 2.7 1,579.9 2.7 1,431.4 2.7 1,643.5 2.7 1,908.5 2.7 1,972.2 2.7 20,922.4 2.7 310.0 0.5 300.0 0.5 286.5 0.5 298.0 0.5 270.0 0.5 310.0 0.5 360.0 0.5 372.0 0.5 3,946.5 0.5 74.6 1.0 75.9 0.9 74.7 0.9 222.3 2.6 326.7 3.0 588.0 3.5 3,351.6 4.3 (Misc Accessory Equipment) 10,457.4 14.1 9,445.4 14.1 10,457.4 14.1 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 1,972.2 2.7 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 372.0 0.5 1,781.3 2.7 1,972.2 2.7 (Misc Accessory Equipment) 336.0 0.5 372.0 0.5 360.0 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms] Gas (therms) Peak (therms/Hr) Project Name: Dataset Name: 7,004.2 43.2 (Misc Accessory Equipment) 61.3 0.1 Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh] Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms] Gas (therms) Peak (therms/Hr) 6,730.0 43.3 SBCC TRACE.TRC 568.0 4.3 471.9 3.5 438.2 3.1 232.5 2.2 (Heating Equipment) 168.2 1.7 110.8 1.3 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 10 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 731.9 1.0 690.3 1.0 617.6 1.0 580.1 1.0 649.8 1.0 592.6 1.0 498.0 1.0 699.7 1.0 773.5 1.0 8,079.1 1.0 332.0 0.5 297.0 0.5 279.0 0.5 312.5 0.5 285.0 0.5 239.5 0.5 336.5 0.5 372.0 0.5 3,885.5 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler forced draft fan (Misc Accessory Equipment) Electric (kWh) Peak (kW) 773.5 1.0 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 698.6 1.0 773.5 1.0 (Misc Accessory Equipment) 372.0 0.5 336.0 0.5 372.0 0.5 352.0 0.5 Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh] Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms] 799.1 14.4 Gas (therms) Peak (therms/Hr) Boiler forced draft fan 1,328.8 15.4 640.2 13.8 (Heating Equipment) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2,768.1 15.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 589.6 2.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 118.0 0.5 1,934.3 8.3 2,127.3 8.7 2,044.4 8.7 1,965.5 8.7 2,011.2 8.7 1,991.1 8.5 2,334.1 8.7 24,698.3 8.7 586.3 3.3 663.8 3.4 653.2 3.5 640.3 3.7 631.5 3.6 545.5 3.2 568.9 3.1 7,248.5 3.7 372.9 2.1 321.5 1.8 282.7 1.4 320.4 1.1 302.5 1.8 379.1 1.4 4,181.6 2.2 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 154.9 2.5 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 279.8 2.5 154.9 2.5 (Misc Accessory Equipment) 31.0 0.5 56.0 0.5 31.0 0.5 0.0 0.0 Sys 1: Admin VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW] Electric (kWh) Peak (kW) 2,366.7 8.7 2,023.1 8.7 2,032.4 8.4 1,816.3 8.7 Sys 2: Admin FC Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW] Electric (kWh) Peak (kW) 578.6 3.3 573.3 3.2 620.7 3.0 (Main Clg Fan) 549.6 3.2 Sys 3: Campus Center FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: SBCC TRACE.TRC 336.9 1.4 358.8 1.5 381.9 1.5 (Main Clg Fan) 2,051.9 8.7 313.6 1.6 636.8 3.3 (Main Clg Fan) 429.0 2.1 382.5 2.2 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 11 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 4: Campus Center Dual Deck AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW] Electric (kWh) Peak (kW) 2,064.2 6.0 1,863.1 6.8 2,161.8 6.8 2,104.7 6.8 Sys 5: Campus Center Packg RTU-1 AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW] Electric (kWh) Peak (kW) 825.8 3.3 787.7 3.4 945.1 3.5 1,052.6 3.6 Sys 6: Drama/Music HP AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW] Electric (kWh) Peak (kW) 1,596.5 6.0 1,580.5 6.5 1,705.2 5.9 1,560.5 6.1 Sys 7: Drama/Music Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW] Electric (kWh) Peak (kW) 111.6 0.6 94.6 0.6 96.4 0.6 May 766.5 4.6 731.5 4.4 826.7 4.1 2,427.7 6.8 2,766.0 12.0 2,664.3 16.8 2,867.7 17.4 9,536.2 43.5 9,096.7 50.5 9,855.1 44.9 Sept Oct Nov Dec Total 2,424.9 6.8 2,426.1 6.8 2,342.4 6.8 2,291.7 6.8 2,009.3 6.8 2,041.1 6.8 26,422.4 6.8 1,261.4 3.8 1,232.4 3.8 1,166.2 3.8 1,055.3 3.7 905.1 3.3 798.1 3.0 12,346.9 3.8 1,662.2 6.6 1,863.2 7.0 1,823.6 6.9 1,801.3 7.4 1,733.4 7.2 1,483.3 6.6 1,696.1 6.1 20,258.4 7.4 66.0 0.5 78.2 0.5 73.8 0.6 73.3 0.6 80.4 0.6 83.2 0.6 110.0 0.6 996.6 0.6 1,071.9 4.4 1,062.9 4.5 1,046.1 4.8 969.6 4.7 787.8 4.5 697.9 3.5 10,771.4 4.8 4,158.9 25.0 3,964.9 23.5 3,790.5 22.8 3,131.2 21.5 2,416.5 15.9 2,859.8 12.1 38,717.2 25.0 11,124.9 44.9 11,138.7 48.1 11,616.0 57.4 10,518.5 61.3 8,480.1 51.4 9,285.7 41.7 119,088.3 61.3 2,265.5 6.8 1,148.3 3.8 1,169.0 3.8 (Main Clg Fan) 1,752.8 6.8 (Main Clg Fan) 60.2 0.6 68.8 0.5 857.8 4.6 2,945.8 18.1 8,773.8 38.5 (Main Clg Fan) 990.1 4.4 962.6 4.1 (Main Clg Fan) 3,524.6 23.7 Sys 10: Humanities VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW] Electric (kWh) Peak (kW) Aug (Main Clg Fan) Sys 9: EBS VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) Sys 8: Drama/Music MZU 90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW] Electric (kWh) Peak (kW) June 3,627.0 23.3 (Main Clg Fan) 9,865.7 41.9 9,796.9 39.8 Sys 11: Humanities Fan Coil Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 12 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 11: Humanities Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW] Electric (kWh) Peak (kW) 221.6 2.3 256.6 2.2 331.3 2.4 24.1 0.1 24.5 0.1 31.1 0.1 456.0 2.7 3,185.3 11.6 2,814.6 11.6 2,895.4 11.6 2,192.9 7.7 Sys 14: OE Pckg AH FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW] Electric (kWh) Peak (kW) 354.9 1.8 353.2 1.9 362.3 1.6 322.0 1.5 Sys 15: PE Heat Pump FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW] Electric (kWh) Peak (kW) 309.8 1.3 313.0 1.3 348.9 1.4 306.1 1.0 Sys 16: PE VAV Htg Only FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW] Electric (kWh) Peak (kW) 37.2 1.3 12.1 0.4 3.3 0.1 Sys 17: PS Fan Coil Htg Only Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW] Electric (kWh) Peak (kW) 301.1 0.8 273.4 0.8 301.8 0.8 July Aug Sept Oct Nov Dec Total 447.0 2.7 479.0 2.7 444.6 2.6 384.9 2.6 338.5 2.2 244.5 2.1 220.2 2.2 4,178.9 2.7 47.0 0.2 51.5 0.2 49.3 0.2 45.8 0.2 38.6 0.2 30.3 0.1 22.9 0.1 449.0 0.2 2,208.9 10.9 2,226.5 11.0 2,291.2 11.6 2,479.2 11.6 2,658.7 11.6 3,315.0 11.6 30,732.7 11.6 426.7 2.4 429.5 2.2 449.1 2.1 403.5 2.2 315.8 2.0 365.9 1.7 4,555.4 2.4 444.2 3.4 380.1 3.2 353.5 3.2 370.1 1.7 309.0 1.0 273.1 1.2 4,103.2 3.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.3 0.0 0.4 0.0 31.4 0.4 85.5 1.3 285.7 0.8 315.4 0.8 317.5 0.8 305.0 0.8 293.1 0.8 290.8 0.8 305.5 0.8 3,565.2 0.8 (Main Clg Fan) 38.9 0.1 45.2 0.2 Sys 13: LRC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW] Electric (kWh) Peak (kW) June (Main Clg Fan) 354.7 2.5 Sys 12: IDC Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW] Electric (kWh) Peak (kW) May 0.5 0.0 (Main Clg Fan) 2,379.9 9.9 2,085.2 9.3 (Main Clg Fan) 391.3 2.2 381.4 2.2 (Main Clg Fan) 353.5 3.1 342.0 3.3 (Main Clg Fan) 0.3 0.0 (Main Clg Fan) 286.2 0.8 289.8 0.8 Sys 18: Stdnt Srv VAV Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 13 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 2 SBCC CHWR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May Sys 18: Stdnt Srv VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW] Electric (kWh) Peak (kW) 3,465.7 13.6 3,054.7 12.9 3,467.3 15.2 3,005.2 12.4 1,234.1 5.2 1,217.7 6.2 1,399.7 6.1 1,519.7 6.0 Sys 20: IDC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW] Electric (kWh) Peak (kW) 1,258.8 4.4 1,142.1 5.1 1,287.6 4.6 1,297.2 4.5 8,120.3 41.6 8,501.0 50.6 8,501.8 49.5 7,807.4 48.6 Sys 22: BC FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW] Electric (kWh) Peak (kW) 1,899.4 7.4 1,781.9 7.7 1,948.2 6.8 1,525.5 6.2 Sys 23: BC Hydronic AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 1,354.9 5.1 SBCC TRACE.TRC 1,238.5 5.9 1,258.3 5.4 1,012.3 4.7 Aug Sept Oct Nov Dec Total 3,237.9 15.2 3,552.1 16.4 3,388.5 15.5 3,285.0 15.0 3,450.1 16.6 3,218.2 17.1 3,314.7 13.8 39,813.8 17.1 2,165.1 10.0 1,934.5 8.8 1,737.1 8.6 1,568.4 7.7 1,263.9 5.9 1,187.8 4.9 19,055.3 10.2 1,440.4 4.6 1,460.0 4.9 1,459.7 5.4 1,429.3 5.4 1,290.5 5.3 1,220.3 4.6 15,977.2 5.4 11,268.1 67.5 10,776.1 64.4 10,538.1 66.9 9,078.9 62.7 6,961.7 49.0 8,077.0 39.4 109,493.0 67.5 1,716.5 6.9 1,704.0 7.4 1,797.4 8.2 1,853.2 8.1 1,548.4 7.9 1,842.4 7.3 21,001.6 8.2 1,150.2 5.8 1,143.8 6.1 1,177.1 7.3 1,238.2 7.3 1,068.3 6.1 1,233.7 5.0 14,047.1 7.3 (Main Clg Fan) 1,888.2 9.1 1,939.2 10.2 (Main Clg Fan) 1,362.7 4.6 Sys 21: Portopia HP FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) 3,374.4 15.5 Sys 19: Admin Pckg AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW] Electric (kWh) Peak (kW) June 1,328.7 4.4 (Main Clg Fan) 10,073.5 63.2 9,789.2 61.9 (Main Clg Fan) 1,810.9 6.4 1,573.8 6.5 (Main Clg Fan) 1,139.8 5.3 1,032.1 5.0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 2 Equipment Energy Consumption report page 14 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total Electric (kWh) Peak (kW) 155,785.6 300.2 140,710.4 300.2 155,825.9 300.2 150,753.8 300.2 155,805.8 300.2 150,794.1 300.2 155,765.6 300.2 155,825.9 300.2 150,753.9 300.2 155,805.9 300.2 150,774.0 300.2 155,765.6 300.2 1,834,366.4 300.2 Electric (kWh) Peak (kW) 196,983.9 315.2 177,920.8 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,623.4 315.2 196,987.6 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,627.1 315.2 196,987.6 315.2 2,319,305.5 315.2 4.3 0.1 1.6 0.0 3.2 0.1 10.6 0.1 15.3 0.2 23.0 0.2 36.5 0.2 38.5 0.2 41.8 0.2 11.3 0.1 10.4 0.2 3.2 0.1 199.6 0.2 60,450.0 150.0 54,600.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 711,750.0 150.0 11,160.0 15.0 10,080.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 131,400.0 15.0 40,300.0 100.0 36,400.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 474,500.0 100.0 17,940.2 272.2 18,114.8 269.8 19,558.2 269.4 11,031.7 227.3 6,621.1 176.7 632.9 121.3 105,105.1 272.2 Lights Misc. Ld Cooling Coil Condensate Recoverable Water (1000gal) Peak (1000gal/Hr) Bsu 1: Parking lot lights Electric (kWh) Peak (kW) Bsu 2: Decorative Fountains Electric (kWh) Peak (kW) Bsu 3: Stadium Lights Electric (kWh) Peak (kW) Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Main [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] (Cooling Equipment) Electric (kWh) Peak (kW) 1,252.1 126.6 2,317.7 147.7 2,374.0 145.8 4,468.8 163.3 7,654.7 203.6 13,138.9 220.3 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) Project Name: Dataset Name: 197.4 17.0 313.6 18.8 336.2 19.3 603.9 23.9 965.9 30.2 1,648.4 32.4 2,352.9 37.8 2,333.5 37.8 2,455.3 37.4 1,381.6 32.5 859.9 25.3 105.3 15.6 13,553.8 37.8 3,365.5 18.7 3,477.7 18.7 3,926.4 18.7 4,636.9 18.7 5,216.5 18.7 5,048.2 18.7 4,057.3 18.7 3,926.4 18.7 3,477.7 18.7 47,228.7 18.7 (Misc Accessory Equipment) 3,477.7 18.7 SBCC TRACE.TRC 3,141.1 18.7 3,477.7 18.7 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 15 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 186.0 1.0 210.0 1.0 248.0 1.0 279.0 1.0 270.0 1.0 217.0 1.0 210.0 1.0 186.0 1.0 2,526.0 1.0 23,609.4 199.8 33,316.8 233.4 31,824.8 227.3 34,472.8 248.1 28,282.7 218.7 12,603.7 181.6 3,211.3 134.5 221,910.3 248.1 Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Cntl panel & interlocks - 1 KW (Misc Accessory Equipment) Electric (kWh) Peak (kW) 186.0 1.0 168.0 1.0 186.0 1.0 180.0 1.0 DR [Clg Nominal Capacity/F.L.Rate=369.0 tons / 455.1 kW] Electric (kWh) Peak (kW) 3,730.8 136.3 9,089.0 173.3 9,511.3 164.4 (Cooling Equipment) 8,671.1 165.2 23,586.7 203.4 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=498.4 tons / 47.35 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) 507.9 14.5 1,049.4 20.6 1,148.0 19.1 1,093.0 20.5 2,626.2 28.1 2,705.4 27.6 3,826.3 32.6 3,683.1 32.1 4,116.0 34.5 2,936.9 29.2 1,424.8 22.6 441.9 14.3 25,559.0 34.5 4,487.3 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 54,595.3 18.7 248.0 1.0 240.0 1.0 248.0 1.0 248.0 1.0 240.0 1.0 248.0 1.0 240.0 1.0 248.0 1.0 2,920.0 1.0 23,767.8 146.2 22,837.3 144.1 22,900.3 139.6 15,692.3 121.6 10,066.3 97.2 6,031.8 68.4 172,075.9 146.2 (Misc Accessory Equipment) 4,636.9 18.7 Cntl panel & interlocks - 1 KW Electric (kWh) Peak (kW) 4,188.1 18.7 4,636.9 18.7 (Misc Accessory Equipment) 248.0 1.0 224.0 1.0 248.0 1.0 240.0 1.0 Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons] Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW] Electric (kWh) Peak (kW) 6,760.0 73.5 7,590.0 81.4 9,263.9 87.2 (Cooling Equipment) 11,479.2 104.7 17,110.1 127.1 18,576.8 133.6 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW] Electric (kWh) Peak (kW) 943.8 10.1 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 1,045.4 11.1 1,281.5 11.9 1,591.1 14.2 2,336.1 17.0 2,535.7 17.8 3,206.4 19.2 3,092.1 19.0 3,080.8 18.3 2,103.4 16.0 1,380.0 13.1 843.0 9.4 23,439.2 19.2 43.4 0.1 42.0 0.1 43.4 0.1 43.4 0.1 42.0 0.1 43.4 0.1 42.0 0.1 43.4 0.1 511.0 0.1 29,702.0 251.7 18,337.3 268.0 9,429.7 238.0 342,742.4 323.9 (Misc Accessory Equipment) 43.4 0.1 39.2 0.1 43.4 0.1 42.0 0.1 Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 11,369.3 198.1 SBCC TRACE.TRC 13,430.4 252.3 18,681.2 263.3 24,885.9 287.9 36,538.2 260.3 39,073.2 315.9 (Cooling Equipment - Cooling Mode) 49,183.3 323.9 46,525.8 323.0 45,586.0 321.9 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 16 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW] Electric (kWh) Peak (kW) HP 6,916.3 252.5 2,897.2 243.4 3,623.0 218.8 Apr May June July Aug Sept Oct Nov Dec Total (Cooling Equipment - Heating Mode) 1,916.9 161.8 1,827.1 157.6 599.0 135.3 255.1 115.0 258.7 115.0 416.7 125.9 3,088.7 169.0 4,554.3 217.4 13,962.1 282.2 40,315.2 282.2 126.1 1.1 108.8 0.8 102.7 0.8 104.2 0.8 99.5 1.0 146.6 1.9 192.3 2.0 192.6 1.9 1,779.5 2.0 (Cooling Equipment - Heat Recovered From Condenser Loop) Heat Recovered (therms) Peak (therms/Hr) 166.8 1.3 169.4 1.6 205.4 1.7 165.2 2.0 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW] Electric (kWh) Peak (kW) 2,640.8 35.4 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 2,422.3 38.2 3,286.9 39.9 4,258.0 43.7 Cnst vol cnd water pump Electric (kWh) Peak (kW) Boiler forced draft fan 8,111.4 49.4 7,692.2 49.3 7,547.1 49.2 5,143.9 43.6 3,342.6 40.7 3,141.0 36.1 60,306.1 49.4 48.1 0.1 57.0 0.1 60.5 0.1 62.5 0.1 57.4 0.1 52.8 0.1 55.1 0.1 55.3 0.1 61.1 0.1 58.3 0.1 74.4 0.1 703.8 0.1 2,521.4 13.8 2,127.7 11.3 1,913.6 10.4 (Heating Equipment) 908.2 5.6 735.2 4.2 463.6 3.1 361.9 2.1 354.5 2.2 387.3 2.9 1,055.4 6.5 1,477.0 8.0 2,657.8 11.3 14,963.5 13.8 10,120.0 14.1 9,585.9 14.1 9,276.7 14.1 8,925.3 14.1 9,248.6 14.1 8,011.7 14.1 8,714.5 14.1 10,120.1 14.1 10,457.4 14.1 114,820.3 14.1 1,908.5 2.7 1,807.8 2.7 1,749.5 2.7 1,683.2 2.7 1,744.2 2.7 1,510.9 2.7 1,643.5 2.7 1,908.5 2.7 1,972.2 2.7 21,654.0 2.7 341.0 0.5 330.0 0.5 317.5 0.5 329.0 0.5 285.0 0.5 310.0 0.5 360.0 0.5 372.0 0.5 4,084.5 0.5 74.6 1.0 75.9 0.9 74.7 0.9 222.2 2.6 326.9 3.0 588.8 3.5 3,349.3 4.3 (Misc Accessory Equipment) 10,457.4 14.1 9,445.4 14.1 10,457.4 14.1 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 1,972.2 2.7 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 372.0 0.5 1,781.3 2.7 1,972.2 2.7 (Misc Accessory Equipment) 336.0 0.5 372.0 0.5 360.0 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms] Gas (therms) Peak (therms/Hr) Project Name: Dataset Name: 6,501.3 48.1 (Misc Accessory Equipment) 61.3 0.1 Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh] Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms] Gas (therms) Peak (therms/Hr) 6,218.6 45.8 SBCC TRACE.TRC 566.4 4.3 471.1 3.5 437.5 3.1 232.5 2.2 (Heating Equipment) 168.1 1.7 110.8 1.3 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 17 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 731.9 1.0 690.3 1.0 617.6 1.0 580.1 1.0 649.8 1.0 592.6 1.0 498.0 1.0 699.7 1.0 773.5 1.0 8,079.1 1.0 332.0 0.5 297.0 0.5 279.0 0.5 312.5 0.5 285.0 0.5 239.5 0.5 336.5 0.5 372.0 0.5 3,885.5 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler forced draft fan (Misc Accessory Equipment) Electric (kWh) Peak (kW) 773.5 1.0 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 698.6 1.0 773.5 1.0 (Misc Accessory Equipment) 372.0 0.5 336.0 0.5 372.0 0.5 352.0 0.5 Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh] Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms] 799.1 14.4 Gas (therms) Peak (therms/Hr) Boiler forced draft fan 1,337.7 15.4 640.9 13.8 (Heating Equipment) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2,777.7 15.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 589.6 2.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 118.0 0.5 1,829.8 7.6 1,993.0 7.1 1,902.6 7.2 1,818.7 7.7 1,930.0 8.7 1,939.9 8.5 2,263.5 8.7 23,589.0 8.7 526.4 3.9 597.4 3.9 584.2 3.4 572.7 3.2 567.7 3.0 493.8 2.9 532.6 3.1 6,561.7 3.9 324.0 2.1 278.0 1.7 249.4 1.3 293.6 1.1 284.8 1.8 367.2 1.4 3,810.4 2.2 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 154.9 2.5 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 279.8 2.5 154.9 2.5 (Misc Accessory Equipment) 31.0 0.5 56.0 0.5 31.0 0.5 0.0 0.0 Sys 1: Admin VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW] Electric (kWh) Peak (kW) 2,282.5 8.7 1,973.2 8.7 1,972.4 8.4 1,744.7 8.7 Sys 2: Admin FC Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW] Electric (kWh) Peak (kW) 532.4 3.3 524.7 3.2 563.0 3.2 (Main Clg Fan) 494.3 3.7 Sys 3: Campus Center FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: SBCC TRACE.TRC 321.4 1.4 339.5 1.5 354.6 1.5 (Main Clg Fan) 1,938.7 6.7 280.4 1.5 572.6 3.8 (Main Clg Fan) 381.8 1.9 335.8 2.2 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 18 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 4: Campus Center Dual Deck AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW] Electric (kWh) Peak (kW) 1,818.5 6.0 1,713.8 6.8 1,943.9 6.8 1,954.3 6.8 Sys 5: Campus Center Packg RTU-1 AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW] Electric (kWh) Peak (kW) 768.3 3.6 736.8 3.6 893.4 3.6 1,011.3 3.6 Sys 6: Drama/Music HP AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW] Electric (kWh) Peak (kW) 1,498.8 6.0 1,506.7 6.5 1,629.1 6.4 1,489.2 6.4 Sys 7: Drama/Music Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW] Electric (kWh) Peak (kW) 108.4 0.6 91.3 0.6 92.2 0.6 May 705.5 4.6 663.3 4.4 752.8 4.7 2,232.3 6.8 2,898.9 25.0 2,870.8 25.0 3,095.5 25.0 9,288.6 54.0 8,750.5 58.0 9,426.5 57.9 Sept Oct Nov Dec Total 2,251.7 6.8 2,275.6 6.8 2,202.7 6.8 2,118.5 6.8 1,792.6 6.8 1,847.8 6.8 24,228.1 6.8 1,215.5 3.8 1,191.9 3.8 1,127.7 3.8 1,004.4 3.6 851.7 3.6 748.0 3.5 11,791.9 3.8 1,584.6 7.0 1,782.8 7.1 1,741.5 7.0 1,721.4 7.4 1,647.5 6.1 1,413.3 6.1 1,624.2 6.1 19,306.4 7.4 61.4 0.6 72.8 0.6 68.0 0.6 67.4 0.6 74.3 0.6 78.6 0.6 107.0 0.6 941.9 0.6 972.9 5.8 957.6 5.4 933.9 4.7 870.7 4.5 720.4 4.5 648.6 3.7 9,803.2 5.8 4,233.5 25.0 4,072.2 25.0 3,843.9 25.0 3,316.0 25.0 2,563.4 25.0 2,935.0 25.0 40,525.1 25.0 10,437.4 60.7 10,337.5 60.4 10,581.4 61.3 9,653.8 59.7 7,988.8 53.8 9,108.4 50.7 112,683.8 61.3 2,076.4 6.8 1,108.3 3.6 1,134.8 3.8 (Main Clg Fan) 1,667.2 6.2 (Main Clg Fan) 56.6 0.6 64.0 0.6 790.1 4.9 3,202.0 25.0 8,402.6 55.9 (Main Clg Fan) 902.7 5.5 884.8 5.6 (Main Clg Fan) 3,698.3 25.0 Sys 10: Humanities VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW] Electric (kWh) Peak (kW) Aug (Main Clg Fan) Sys 9: EBS VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) Sys 8: Drama/Music MZU 90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW] Electric (kWh) Peak (kW) June 3,795.6 25.0 (Main Clg Fan) 9,360.5 58.5 9,347.8 59.2 Sys 11: Humanities Fan Coil Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 19 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 11: Humanities Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW] Electric (kWh) Peak (kW) 197.3 2.4 225.7 2.3 288.5 2.4 21.6 0.2 22.0 0.2 28.7 0.2 397.6 2.6 3,117.1 11.6 2,740.5 11.6 2,802.4 11.6 2,103.8 8.3 Sys 14: OE Pckg AH FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW] Electric (kWh) Peak (kW) 352.3 3.4 353.3 3.4 362.7 3.4 322.4 3.4 Sys 15: PE Heat Pump FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW] Electric (kWh) Peak (kW) 309.8 1.3 312.1 1.3 345.3 1.4 298.3 1.1 Sys 16: PE VAV Htg Only FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW] Electric (kWh) Peak (kW) 37.2 1.3 12.1 0.4 3.3 0.1 Sys 17: PS Fan Coil Htg Only Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW] Electric (kWh) Peak (kW) 290.5 0.8 270.9 0.8 301.8 0.8 July Aug Sept Oct Nov Dec Total 391.9 2.7 420.2 2.7 387.7 2.5 337.3 2.3 293.3 1.8 214.6 2.1 201.5 2.2 3,663.8 2.7 44.5 0.2 48.1 0.2 46.3 0.2 43.0 0.2 35.7 0.2 27.5 0.2 20.7 0.2 417.6 0.2 2,092.4 10.7 2,048.2 9.7 2,067.1 9.2 2,315.6 8.7 2,602.6 11.6 3,226.6 11.6 29,409.4 11.6 422.3 3.4 424.8 3.4 439.3 3.7 397.7 3.4 314.5 3.4 365.8 3.2 4,519.3 4.3 440.9 3.8 370.8 3.8 340.9 3.6 354.8 2.0 307.3 1.0 273.1 1.2 4,020.1 3.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.3 0.0 0.4 0.0 31.4 0.4 85.5 1.3 285.7 0.8 315.4 0.8 317.5 0.8 305.0 0.8 293.1 0.8 287.1 0.8 295.5 0.8 3,538.5 0.8 (Main Clg Fan) 36.6 0.2 42.7 0.2 Sys 13: LRC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW] Electric (kWh) Peak (kW) June (Main Clg Fan) 308.3 2.3 Sys 12: IDC Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW] Electric (kWh) Peak (kW) May 0.5 0.0 (Main Clg Fan) 2,288.1 9.6 2,005.2 10.2 (Main Clg Fan) 387.1 3.4 377.1 4.3 (Main Clg Fan) 337.6 3.6 329.3 3.7 (Main Clg Fan) 0.3 0.0 (Main Clg Fan) 286.2 0.8 289.8 0.8 Sys 18: Stdnt Srv VAV Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 20 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 3 SBCC Class Temp Reduction ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May Sys 18: Stdnt Srv VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW] Electric (kWh) Peak (kW) 3,500.5 16.5 3,104.2 16.4 3,527.2 17.1 2,977.0 17.1 1,191.0 13.4 1,266.6 13.7 1,466.8 13.7 1,580.7 13.9 Sys 20: IDC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW] Electric (kWh) Peak (kW) 1,114.1 4.1 1,011.6 4.3 1,142.9 4.5 1,158.2 4.5 8,067.7 79.8 8,722.5 81.8 8,841.8 82.9 8,082.4 83.4 Sys 22: BC FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW] Electric (kWh) Peak (kW) 1,786.2 7.4 1,663.0 7.7 1,811.1 7.9 1,395.2 8.0 Sys 23: BC Hydronic AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 1,306.6 4.6 SBCC TRACE.TRC 1,199.1 5.8 1,218.7 6.3 983.9 6.3 Aug Sept Oct Nov Dec Total 3,144.6 17.1 3,358.9 17.1 3,235.8 17.1 3,105.0 17.1 3,366.0 17.1 3,172.6 17.1 3,337.8 16.1 39,101.7 17.1 2,176.2 14.4 1,940.5 15.3 1,743.7 15.3 1,630.3 14.4 1,306.0 13.9 1,135.3 13.3 19,307.7 15.3 1,276.4 4.7 1,283.5 4.7 1,268.8 4.5 1,246.5 4.6 1,137.9 4.6 1,097.5 4.3 14,143.3 4.7 11,210.6 87.2 10,642.2 87.1 10,272.6 85.7 9,028.5 82.6 7,146.0 79.8 7,868.0 77.7 109,783.5 88.3 1,541.3 8.7 1,527.2 8.6 1,620.4 8.6 1,690.1 8.1 1,426.2 7.9 1,739.0 7.3 19,277.6 8.7 1,101.9 7.9 1,083.4 7.7 1,093.0 7.1 1,170.8 6.0 1,023.8 4.7 1,210.6 3.9 13,490.4 7.9 (Main Clg Fan) 1,908.9 14.4 1,961.8 14.6 (Main Clg Fan) 1,214.3 4.6 Sys 21: Portopia HP FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) 3,272.0 17.1 Sys 19: Admin Pckg AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW] Electric (kWh) Peak (kW) June 1,191.8 4.6 (Main Clg Fan) 10,066.7 86.6 9,834.4 88.3 (Main Clg Fan) 1,653.6 8.4 1,424.3 8.5 (Main Clg Fan) 1,100.2 7.0 998.5 7.1 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 3 Equipment Energy Consumption report page 21 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total Electric (kWh) Peak (kW) 155,785.6 300.2 140,710.4 300.2 155,825.9 300.2 150,753.8 300.2 155,805.8 300.2 150,794.1 300.2 155,765.6 300.2 155,825.9 300.2 150,753.9 300.2 155,805.9 300.2 150,774.0 300.2 155,765.6 300.2 1,834,366.4 300.2 Electric (kWh) Peak (kW) 196,983.9 315.2 177,920.8 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,623.4 315.2 196,987.6 315.2 196,976.5 315.2 190,630.8 315.2 196,980.3 315.2 190,627.1 315.2 196,987.6 315.2 2,319,305.5 315.2 4.3 0.1 1.6 0.0 3.2 0.1 10.6 0.1 15.3 0.2 23.0 0.2 36.4 0.2 38.4 0.2 41.7 0.2 11.2 0.1 10.3 0.2 3.2 0.1 199.1 0.2 60,450.0 150.0 54,600.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 58,500.0 150.0 60,450.0 150.0 711,750.0 150.0 11,160.0 15.0 10,080.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 10,800.0 15.0 11,160.0 15.0 131,400.0 15.0 40,300.0 100.0 36,400.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 39,000.0 100.0 40,300.0 100.0 474,500.0 100.0 17,950.6 275.2 18,122.9 272.7 19,566.7 272.2 11,040.4 228.9 6,628.4 177.0 632.9 121.5 105,187.0 275.2 Lights Misc. Ld Cooling Coil Condensate Recoverable Water (1000gal) Peak (1000gal/Hr) Bsu 1: Parking lot lights Electric (kWh) Peak (kW) Bsu 2: Decorative Fountains Electric (kWh) Peak (kW) Bsu 3: Stadium Lights Electric (kWh) Peak (kW) Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Main [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] (Cooling Equipment) Electric (kWh) Peak (kW) 1,254.2 126.8 2,323.8 147.9 2,379.3 145.9 4,479.0 163.5 7,665.4 204.1 13,143.3 221.0 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) Project Name: Dataset Name: 197.7 17.1 314.4 18.9 336.9 19.3 605.2 24.0 967.3 30.3 1,649.6 32.5 2,356.0 38.1 2,336.2 38.0 2,458.1 37.7 1,384.1 32.7 861.8 25.4 105.3 15.7 13,572.3 38.1 3,365.5 18.7 3,477.7 18.7 3,926.4 18.7 4,636.9 18.7 5,216.5 18.7 5,048.2 18.7 4,057.3 18.7 3,926.4 18.7 3,477.7 18.7 47,228.7 18.7 (Misc Accessory Equipment) 3,477.7 18.7 SBCC TRACE.TRC 3,141.1 18.7 3,477.7 18.7 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 22 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 186.0 1.0 210.0 1.0 248.0 1.0 279.0 1.0 270.0 1.0 217.0 1.0 210.0 1.0 186.0 1.0 2,526.0 1.0 23,349.5 199.5 32,982.5 232.9 31,491.8 226.8 34,097.9 247.4 27,823.1 218.4 12,342.2 181.4 3,160.9 134.5 218,959.1 247.4 Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons] Cntl panel & interlocks - 1 KW (Misc Accessory Equipment) Electric (kWh) Peak (kW) 186.0 1.0 168.0 1.0 186.0 1.0 180.0 1.0 DR [Clg Nominal Capacity/F.L.Rate=369.0 tons / 455.1 kW] Electric (kWh) Peak (kW) 3,643.0 136.3 8,895.1 173.1 9,341.6 163.7 (Cooling Equipment) 8,526.0 164.5 23,305.5 203.1 Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=498.4 tons / 47.35 kW] Electric (kWh) Peak (kW) Cnst vol chill water pump Electric (kWh) Peak (kW) 496.4 14.3 1,027.8 20.5 1,128.3 18.9 1,075.3 20.3 2,595.5 28.0 2,676.6 27.5 3,779.8 32.5 3,641.6 32.0 4,069.3 34.4 2,890.6 29.1 1,396.1 22.6 435.1 14.3 25,212.4 34.4 4,487.3 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 4,487.3 18.7 4,636.9 18.7 54,595.3 18.7 248.0 1.0 240.0 1.0 248.0 1.0 248.0 1.0 240.0 1.0 248.0 1.0 240.0 1.0 248.0 1.0 2,920.0 1.0 23,767.8 146.2 22,837.3 144.1 22,900.3 139.6 15,692.3 121.6 10,066.3 97.2 6,031.8 68.4 172,075.9 146.2 (Misc Accessory Equipment) 4,636.9 18.7 Cntl panel & interlocks - 1 KW Electric (kWh) Peak (kW) 4,188.1 18.7 4,636.9 18.7 (Misc Accessory Equipment) 248.0 1.0 224.0 1.0 248.0 1.0 240.0 1.0 Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons] Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW] Electric (kWh) Peak (kW) 6,760.0 73.5 7,590.0 81.4 9,263.9 87.2 (Cooling Equipment) 11,479.2 104.7 17,110.1 127.1 18,576.8 133.6 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW] Electric (kWh) Peak (kW) 943.8 10.1 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 1,045.4 11.1 1,281.5 11.9 1,591.1 14.2 2,336.1 17.0 2,535.7 17.8 3,206.4 19.2 3,092.1 19.0 3,080.8 18.3 2,103.4 16.0 1,380.0 13.1 843.0 9.4 23,439.2 19.2 43.4 0.1 42.0 0.1 43.4 0.1 43.4 0.1 42.0 0.1 43.4 0.1 42.0 0.1 43.4 0.1 511.0 0.1 29,702.0 251.7 18,337.3 268.0 9,429.7 238.0 342,742.4 323.9 (Misc Accessory Equipment) 43.4 0.1 39.2 0.1 43.4 0.1 42.0 0.1 Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 11,369.3 198.1 SBCC TRACE.TRC 13,430.4 252.3 18,681.2 263.3 24,885.9 287.9 36,538.2 260.3 39,073.2 315.9 (Cooling Equipment - Cooling Mode) 49,183.3 323.9 46,525.8 323.0 45,586.0 321.9 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 23 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons] HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW] Electric (kWh) Peak (kW) HP 6,916.3 252.5 2,897.2 243.4 3,623.0 218.8 Apr May June July Aug Sept Oct Nov Dec Total (Cooling Equipment - Heating Mode) 1,916.9 161.8 1,827.1 157.6 599.0 135.3 255.1 115.0 258.7 115.0 416.7 125.9 3,088.7 169.0 4,554.3 217.4 13,962.1 282.2 40,315.2 282.2 126.1 1.1 108.8 0.8 102.7 0.8 104.2 0.8 99.5 1.0 146.6 1.9 192.3 2.0 192.6 1.9 1,779.5 2.0 (Cooling Equipment - Heat Recovered From Condenser Loop) Heat Recovered (therms) Peak (therms/Hr) 166.8 1.3 169.4 1.6 205.4 1.7 165.2 2.0 Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW] Electric (kWh) Peak (kW) 2,640.8 35.4 Cntl panel & interlocks - 0.1 KW Electric (kWh) Peak (kW) 2,422.3 38.2 3,286.9 39.9 4,258.0 43.7 Cnst vol cnd water pump Electric (kWh) Peak (kW) Boiler forced draft fan 8,111.4 49.4 7,692.2 49.3 7,547.1 49.2 5,143.9 43.6 3,342.6 40.7 3,141.0 36.1 60,306.1 49.4 48.1 0.1 57.0 0.1 60.5 0.1 62.5 0.1 57.4 0.1 52.8 0.1 55.1 0.1 55.3 0.1 61.1 0.1 58.3 0.1 74.4 0.1 703.8 0.1 2,521.3 13.8 2,127.7 11.3 1,913.6 10.4 (Heating Equipment) 908.2 5.6 735.2 4.2 463.6 3.1 361.9 2.1 354.5 2.2 387.3 2.9 1,055.4 6.5 1,477.0 8.0 2,657.8 11.3 14,963.4 13.8 10,120.0 14.1 9,585.9 14.1 9,276.7 14.1 8,925.3 14.1 9,248.6 14.1 8,011.7 14.1 8,714.5 14.1 10,120.1 14.1 10,457.4 14.1 114,820.3 14.1 1,908.5 2.7 1,807.8 2.7 1,749.5 2.7 1,683.2 2.7 1,744.2 2.7 1,510.9 2.7 1,643.5 2.7 1,908.5 2.7 1,972.2 2.7 21,654.0 2.7 341.0 0.5 330.0 0.5 317.5 0.5 329.0 0.5 285.0 0.5 310.0 0.5 360.0 0.5 372.0 0.5 4,084.5 0.5 74.6 1.0 75.9 0.9 74.7 0.9 222.2 2.6 326.9 3.0 588.8 3.5 3,349.3 4.3 (Misc Accessory Equipment) 10,457.4 14.1 9,445.4 14.1 10,457.4 14.1 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 1,972.2 2.7 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 372.0 0.5 1,781.3 2.7 1,972.2 2.7 (Misc Accessory Equipment) 336.0 0.5 372.0 0.5 360.0 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms] Gas (therms) Peak (therms/Hr) Project Name: Dataset Name: 6,501.3 48.1 (Misc Accessory Equipment) 61.3 0.1 Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh] Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms] Gas (therms) Peak (therms/Hr) 6,218.6 45.8 SBCC TRACE.TRC 566.4 4.3 471.1 3.5 437.5 3.1 232.5 2.2 (Heating Equipment) 168.1 1.7 110.8 1.3 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 24 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Total 731.9 1.0 690.3 1.0 617.6 1.0 580.1 1.0 649.8 1.0 592.6 1.0 498.0 1.0 699.7 1.0 773.5 1.0 8,079.1 1.0 332.0 0.5 297.0 0.5 279.0 0.5 312.5 0.5 285.0 0.5 239.5 0.5 336.5 0.5 372.0 0.5 3,885.5 0.5 Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh] Boiler forced draft fan (Misc Accessory Equipment) Electric (kWh) Peak (kW) 773.5 1.0 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 698.6 1.0 773.5 1.0 (Misc Accessory Equipment) 372.0 0.5 336.0 0.5 372.0 0.5 352.0 0.5 Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh] Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms] 799.1 14.4 Gas (therms) Peak (therms/Hr) Boiler forced draft fan 1,337.7 15.4 640.9 13.8 (Heating Equipment) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2,777.7 15.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 589.6 2.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 118.0 0.5 1,767.7 7.6 1,918.5 7.1 1,827.3 6.6 1,744.6 7.7 1,876.4 8.7 1,898.8 8.5 2,222.6 8.7 22,917.4 8.7 526.4 3.9 597.4 3.9 584.2 3.4 572.7 3.2 567.7 3.0 493.8 2.9 532.6 3.1 6,561.7 3.9 324.0 2.1 278.0 1.7 249.4 1.3 293.6 1.1 284.8 1.8 367.2 1.4 3,810.4 2.2 (Misc Accessory Equipment) Electric (kWh) Peak (kW) 154.9 2.5 Cntl panel & interlocks - 0.5 KW Electric (kWh) Peak (kW) 279.8 2.5 154.9 2.5 (Misc Accessory Equipment) 31.0 0.5 56.0 0.5 31.0 0.5 0.0 0.0 Sys 1: Admin VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW] Electric (kWh) Peak (kW) 2,233.4 8.7 1,933.1 8.7 1,927.2 8.4 1,694.3 8.7 Sys 2: Admin FC Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW] Electric (kWh) Peak (kW) 532.4 3.3 524.7 3.2 563.0 3.2 (Main Clg Fan) 494.3 3.7 Sys 3: Campus Center FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: SBCC TRACE.TRC 321.4 1.4 339.5 1.5 354.6 1.5 (Main Clg Fan) 1,873.5 6.0 280.4 1.5 572.6 3.8 (Main Clg Fan) 381.8 1.9 335.8 2.2 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 25 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 4: Campus Center Dual Deck AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW] Electric (kWh) Peak (kW) 1,818.5 6.0 1,713.8 6.8 1,943.9 6.8 1,954.3 6.8 Sys 5: Campus Center Packg RTU-1 AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW] Electric (kWh) Peak (kW) 768.3 3.6 736.8 3.6 893.4 3.6 1,011.3 3.6 Sys 6: Drama/Music HP AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW] Electric (kWh) Peak (kW) 1,498.8 6.0 1,506.7 6.5 1,629.1 6.4 1,489.2 6.4 Sys 7: Drama/Music Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW] Electric (kWh) Peak (kW) 108.4 0.6 91.3 0.6 92.2 0.6 May 705.5 4.6 663.3 4.4 752.8 4.7 2,232.3 6.8 2,898.9 25.0 2,870.8 25.0 3,095.5 25.0 9,288.6 54.0 8,750.5 58.0 9,426.5 57.9 Sept Oct Nov Dec Total 2,251.7 6.8 2,275.6 6.8 2,202.7 6.8 2,118.5 6.8 1,792.6 6.8 1,847.8 6.8 24,228.1 6.8 1,215.5 3.8 1,191.9 3.8 1,127.7 3.8 1,004.4 3.6 851.7 3.6 748.0 3.5 11,791.9 3.8 1,584.6 7.0 1,782.8 7.1 1,741.5 7.0 1,721.4 7.4 1,647.5 6.1 1,413.3 6.1 1,624.2 6.1 19,306.4 7.4 61.4 0.6 72.8 0.6 68.0 0.6 67.4 0.6 74.3 0.6 78.6 0.6 107.0 0.6 941.9 0.6 972.9 5.8 957.6 5.4 933.9 4.7 870.7 4.5 720.4 4.5 648.6 3.7 9,803.2 5.8 4,233.5 25.0 4,072.2 25.0 3,843.9 25.0 3,316.0 25.0 2,563.4 25.0 2,935.0 25.0 40,525.1 25.0 10,437.4 60.7 10,337.5 60.4 10,581.4 61.3 9,653.8 59.7 7,988.8 53.8 9,108.4 50.7 112,683.8 61.3 2,076.4 6.8 1,108.3 3.6 1,134.8 3.8 (Main Clg Fan) 1,667.2 6.2 (Main Clg Fan) 56.6 0.6 64.0 0.6 790.1 4.9 3,202.0 25.0 8,402.6 55.9 (Main Clg Fan) 902.7 5.5 884.8 5.6 (Main Clg Fan) 3,698.3 25.0 Sys 10: Humanities VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW] Electric (kWh) Peak (kW) Aug (Main Clg Fan) Sys 9: EBS VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) Sys 8: Drama/Music MZU 90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW] Electric (kWh) Peak (kW) June 3,795.6 25.0 (Main Clg Fan) 9,360.5 58.5 9,347.8 59.2 Sys 11: Humanities Fan Coil Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 26 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr Sys 11: Humanities Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW] Electric (kWh) Peak (kW) 197.3 2.4 225.7 2.3 288.5 2.4 21.6 0.2 22.0 0.2 28.7 0.2 397.6 2.6 3,117.1 11.6 2,740.5 11.6 2,802.4 11.6 2,103.8 8.3 Sys 14: OE Pckg AH FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW] Electric (kWh) Peak (kW) 352.3 3.4 353.3 3.4 362.7 3.4 322.4 3.4 Sys 15: PE Heat Pump FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW] Electric (kWh) Peak (kW) 309.8 1.3 312.1 1.3 345.3 1.4 298.3 1.1 Sys 16: PE VAV Htg Only FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW] Electric (kWh) Peak (kW) 37.2 1.3 12.1 0.4 3.3 0.1 Sys 17: PS Fan Coil Htg Only Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW] Electric (kWh) Peak (kW) 290.5 0.8 270.9 0.8 301.8 0.8 July Aug Sept Oct Nov Dec Total 391.9 2.7 420.2 2.7 387.7 2.5 337.3 2.3 293.3 1.8 214.6 2.1 201.5 2.2 3,663.8 2.7 44.5 0.2 48.1 0.2 46.3 0.2 43.0 0.2 35.7 0.2 27.5 0.2 20.7 0.2 417.6 0.2 2,092.4 10.7 2,048.2 9.7 2,067.1 9.2 2,315.6 8.7 2,602.6 11.6 3,226.6 11.6 29,409.4 11.6 422.3 3.4 424.8 3.4 439.3 3.7 397.7 3.4 314.5 3.4 365.8 3.2 4,519.3 4.3 440.9 3.8 370.8 3.8 340.9 3.6 354.8 2.0 307.3 1.0 273.1 1.2 4,020.1 3.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.3 0.0 0.4 0.0 31.4 0.4 85.5 1.3 285.7 0.8 315.4 0.8 317.5 0.8 305.0 0.8 293.1 0.8 287.1 0.8 295.5 0.8 3,538.5 0.8 (Main Clg Fan) 36.6 0.2 42.7 0.2 Sys 13: LRC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW] Electric (kWh) Peak (kW) June (Main Clg Fan) 308.3 2.3 Sys 12: IDC Fan Coil Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW] Electric (kWh) Peak (kW) May 0.5 0.0 (Main Clg Fan) 2,288.1 9.6 2,005.2 10.2 (Main Clg Fan) 387.1 3.4 377.1 4.3 (Main Clg Fan) 337.6 3.6 329.3 3.7 (Main Clg Fan) 0.3 0.0 (Main Clg Fan) 286.2 0.8 289.8 0.8 Sys 18: Stdnt Srv VAV Project Name: Dataset Name: SBCC TRACE.TRC TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 27 of 28 EQUIPMENT ENERGY CONSUMPTION By SC ENGINEERS Alternative: 4 SBCC Data Rm TR ------- Monthly Consumption ------- Equipment - Utility Jan Feb Mar Apr May Sys 18: Stdnt Srv VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW] Electric (kWh) Peak (kW) 3,500.5 16.5 3,104.2 16.4 3,527.2 17.1 2,977.0 17.1 1,191.0 13.4 1,266.6 13.7 1,466.8 13.7 1,580.7 13.9 Sys 20: IDC VAV FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW] Electric (kWh) Peak (kW) 1,114.1 4.1 1,011.6 4.3 1,142.9 4.5 1,158.2 4.5 8,067.7 79.8 8,722.5 81.8 8,841.8 82.9 8,082.4 83.4 Sys 22: BC FC AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW] Electric (kWh) Peak (kW) 1,786.2 7.4 1,663.0 7.7 1,811.1 7.9 1,395.2 8.0 Sys 23: BC Hydronic AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW] Electric (kWh) Peak (kW) Project Name: Dataset Name: 1,306.6 4.6 SBCC TRACE.TRC 1,199.1 5.8 1,218.7 6.3 983.9 6.3 Aug Sept Oct Nov Dec Total 3,144.6 17.1 3,358.9 17.1 3,235.8 17.1 3,105.0 17.1 3,366.0 17.1 3,172.6 17.1 3,337.8 16.1 39,101.7 17.1 2,176.2 14.4 1,940.5 15.3 1,743.7 15.3 1,630.3 14.4 1,306.0 13.9 1,135.3 13.3 19,307.7 15.3 1,276.4 4.7 1,283.5 4.7 1,268.8 4.5 1,246.5 4.6 1,137.9 4.6 1,097.5 4.3 14,143.3 4.7 11,210.6 87.2 10,642.2 87.1 10,272.6 85.7 9,028.5 82.6 7,146.0 79.8 7,868.0 77.7 109,783.5 88.3 1,541.3 8.7 1,527.2 8.6 1,620.4 8.6 1,690.1 8.1 1,426.2 7.9 1,739.0 7.3 19,277.6 8.7 1,101.9 7.9 1,083.4 7.7 1,093.0 7.1 1,170.8 6.0 1,023.8 4.7 1,210.6 3.9 13,490.4 7.9 (Main Clg Fan) 1,908.9 14.4 1,961.8 14.6 (Main Clg Fan) 1,214.3 4.6 Sys 21: Portopia HP FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW] Electric (kWh) Peak (kW) July (Main Clg Fan) 3,272.0 17.1 Sys 19: Admin Pckg AHU FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW] Electric (kWh) Peak (kW) June 1,191.8 4.6 (Main Clg Fan) 10,066.7 86.6 9,834.4 88.3 (Main Clg Fan) 1,653.6 8.4 1,424.3 8.5 (Main Clg Fan) 1,100.2 7.0 998.5 7.1 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Alternative - 4 Equipment Energy Consumption report page 28 of 28 PEAK COOLING LOADS MAIN SYSTEM By SC ENGINEERS SPACE Floor Area ft² System Zone Room OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 58.1 58.1 58.1 51.6 51.6 51.6 55.0 55.0 55.0 56.7 56.7 56.7 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.8 57.8 57.8 52.5 52.5 52.5 69.6 69.6 69.6 57.6 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 19,718 19,718 19,718 27,717 27,717 27,717 4,324 4,324 4,324 8,470 8,470 8,470 10,677 10,677 10,677 33,208 33,208 33,208 3,217 3,217 3,217 2,438 2,438 2,438 46,648 46,648 46,648 8,293 8,293 8,293 13,658 13,658 13,658 178,368 649 649 649 6,690 6,690 6,690 0 0 0 601 601 601 686 686 686 2,099 2,099 2,099 935 935 935 708 708 708 1,884 1,884 1,884 1,710 1,710 1,710 -741 -741 -741 15,221 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F Coil Airflow cfm Coil Sensible Load Btu/h 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 21,552 21,552 21,552 27,487 27,487 27,487 4,459 4,459 4,459 10,580 10,580 10,580 12,077 12,077 12,077 35,790 35,790 35,790 8,578 8,578 8,578 6,500 6,500 6,500 64,856 64,856 64,856 8,454 8,454 8,454 27,101 27,101 27,101 227,433 Coil Latent Load Btu/h Alternative 1 spc_A 121 Office UC_0 Zone - 077 Zone - 077 spc_A 130A Class? FC1-4_0 Zone - 078 Zone - 078 spc_A 237-241 Office C_0 Zone - 093 Zone - 093 spc_A 202A Office D_0 Zone - 094 Zone - 094 spc_A 202A Office B_0 Zone - 095 Zone - 095 spc_A 202A Office C_0 Zone - 096 Zone - 096 spc_A 201 Office C_0 Zone - 097 Zone - 097 spc_A 200H-J Office C_0 Zone - 098 Zone - 098 spc_A 200 Office C_0 Zone - 099 Zone - 099 spc_A 210A-B Stairs C_0 Zone - 100 Zone - 100 spc_A 121 Restroom FC05_0 Zone - 118 Zone - 118 Admin FC Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 348 348 348 2,606 2,606 2,606 0 0 0 344 344 344 238 238 238 891 891 891 353 353 353 267 267 267 1,011 1,011 1,011 1,111 1,111 1,111 734 734 734 7,905 10 /16 10 /16 10 /15 10 /15 7 /16 7 /16 6 /10 6 /10 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 7 /18 7 /18 10 /16 10 /16 79 79 79 80 80 80 76 76 76 65 65 65 76 76 76 73 73 73 75 75 75 75 75 75 79 79 79 73 73 73 79 79 79 77 64 64 64 63 63 63 66 66 66 58 58 58 67 67 67 65 65 65 66 66 66 66 66 66 64 64 64 65 65 65 64 64 64 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.9 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 77 77 77 77 77 77 76 76 76 76 76 76 76 76 76 73 73 73 75 75 75 75 75 75 77 77 77 73 73 73 77 77 77 77 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 65 65 65 66 66 66 66 66 66 67 67 67 65 65 65 67 67 67 67 58.4 58.4 58.4 51.8 51.8 51.8 55.0 55.0 55.0 63.1 63.1 63.1 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.9 57.9 57.9 52.5 52.5 52.5 69.8 69.8 69.8 58.0 1,735 1,735 1,735 18,165 18,165 18,165 0 0 0 1,536 1,536 1,536 1,234 1,234 1,234 3,864 3,864 3,864 1,611 1,611 1,611 1,221 1,221 1,221 5,037 5,037 5,037 2,205 2,205 2,205 -7,656 -7,656 -7,656 28,952 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 1 of 100 SPACE Floor Area ft² System Zone Room Admin FC spc_A 161/162 Class C_0 Zone - 091 Zone - 091 spc_A 160 Wrk Rm C_0 Zone - 092 Zone - 092 spc_A 236A/B Offices_0 Zone - 113 Zone - 113 spc_A 244/246 Office C_0 Zone - 114 Zone - 114 spc_A 242/243 Class C_0 Zone - 115 Zone - 115 spc_A 238-246 Offices C_0 Zone - 116 Zone - 116 spc_A 216/218 Office C_0 Zone - 117 Zone - 117 Admin Pckg AHU Admin Pckg AHU spc_A 277F Class_0 Zone - 079 Zone - 079 spc_A 279A Hall C_0 Zone - 080 Zone - 080 spc_A 278A Cond Stair_0 Zone - 081 Zone - 081 spc_A 170/171 Lobby C_0 Zone - 082 Zone - 082 spc_A 172 Wrk Rm C_0 Zone - 083 Zone - 083 spc_A Wrk Rm 173 C_0 Zone - 084 Zone - 084 spc_A 177 Comp C_1 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 7,905 2,273 2,273 2,273 1,806 1,806 1,806 786 786 786 367 367 367 1,839 1,839 1,839 2,547 2,547 2,547 2,057 2,057 2,057 11,676 11,676 1,395 1,395 1,395 7,584 7,584 7,584 321 321 321 1,279 1,279 1,279 2,002 2,002 2,002 671 671 671 626 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 6 /9 6 /9 6 /9 6 /9 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 6/10 6 /10 7 /17 7 /17 6 /10 6 /18 6 /18 6 /10 6 /10 9 /11 9 /11 7 /18 7 /18 6 /9 6 /9 10 /15 10 /15 6 /9 77 62 62 62 62 62 62 75 75 75 75 75 75 79 79 79 65 65 65 75 75 75 65 65 70 70 70 65 65 65 70 70 70 73 73 73 62 62 62 80 80 80 62 67 58 58 58 58 58 58 66 66 66 66 66 66 64 64 64 58 58 58 66 66 66 58 58 63 63 63 58 58 58 63 63 63 65 65 65 58 58 58 63 63 63 58 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.6 54.7 54.7 54.7 54.6 54.6 54.6 49.8 49.8 49.8 49.8 49.8 49.8 55.5 55.5 55.5 57.3 57.3 57.3 49.8 49.8 49.8 55.4 55.4 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,510 2,510 2,510 5,680 5,680 5,680 1,443 1,443 1,443 483 483 483 2,570 2,570 2,570 1,214 1,214 1,214 1,490 160,203 45,748 45,748 45,748 34,617 34,617 34,617 7,681 7,681 7,681 3,589 3,589 3,589 49,570 49,570 49,570 81,320 81,320 81,320 20,104 20,104 20,104 242,629 193,483 46,615 46,615 46,615 105,509 105,509 105,509 26,795 26,795 26,795 8,969 8,969 8,969 47,731 47,731 47,731 22,553 22,553 22,553 27,671 21,247 6,031 6,031 6,031 4,790 4,790 4,790 2,079 2,079 2,079 971 971 971 5,095 5,095 5,095 4,472 4,472 4,472 5,442 5,442 5,442 28,881 25,762 4,376 4,376 4,376 5,555 5,555 5,555 411 411 411 2,208 2,208 2,208 5,370 5,370 5,370 1,747 1,747 1,747 1,303 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 7 /9 7 /9 7 /9 7 /9 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 7 /17 7 /17 7 /16 7 /18 7 /18 7 /16 7 /16 9 /11 9 /11 7 /9 7 /9 7 /9 7 /9 9 /16 9 /16 7 /9 77 64 64 64 64 64 64 75 75 75 75 75 75 77 77 77 76 76 76 75 75 75 76 76 73 73 73 76 76 76 70 70 70 64 64 64 64 64 64 77 77 77 64 67 59 59 59 59 59 59 66 66 66 66 66 66 67 67 67 66 66 66 66 66 66 66 66 65 65 65 66 66 66 63 63 63 59 59 59 59 59 59 67 67 67 59 59.2 55.1 55.1 55.1 54.9 54.9 54.9 49.8 49.8 49.8 49.8 49.8 49.8 55.6 55.6 55.6 64.0 64.0 64.0 49.8 49.8 49.8 58.0 60.0 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 Coil Airflow cfm Coil Sensible Load Btu/h 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,485 2,485 2,485 3,475 3,475 3,475 1,443 1,443 1,443 420 420 420 2,508 2,508 2,508 1,209 1,209 1,209 1,469 211,887 48,957 48,957 48,957 37,048 37,048 37,048 18,754 18,754 18,754 8,763 8,763 8,763 78,514 78,514 78,514 92,985 92,985 92,985 49,087 49,087 49,087 334,108 299,894 66,753 66,753 66,753 177,138 177,138 177,138 30,401 30,401 30,401 10,395 10,395 10,395 48,380 48,380 48,380 23,906 23,906 23,906 28,680 Coil Latent Load Btu/h 30,207 9,347 9,347 9,347 7,420 7,420 7,420 3,579 3,579 3,579 1,672 1,672 1,672 12,862 12,862 12,862 11,426 11,426 11,426 9,369 9,369 9,369 55,677 63,035 9,143 9,143 9,143 15,367 15,367 15,367 511 511 511 2,145 2,145 2,145 8,439 8,439 8,439 4,762 4,762 4,762 2,059 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 2 of 100 SPACE Floor Area ft² System Zone Room Zone - 085 Zone - 085 spc_A 174-176 Data C_0 Zone - 086 Zone - 086 spc_A 177 Comp C_0 Zone - 087 Zone - 087 spc_A 179/178 Data C_0 Zone - 088 Zone - 088 spc_A 180E Com Lab C_0 Zone - 089 Zone - 089 spc_A 271-277 Office C_0 Zone - 111 Zone - 111 spc_A 277 Class_0 Zone - 112 Zone - 112 Admin VAV Admin VAV spc_BC 237 Class_0 Zone - 334 Zone - 334 spc_BC 221 Lobby_0 Zone - 335 Zone - 335 spc_BC 222 Class_0 Zone - 336 Zone - 336 spc_215-219 Office_0 Zone - 337 Zone - 337 spc_BC 224 Class_0 Zone - 338 Zone - 338 spc_BC 2nd 226/228 Class_0 Zone - 339 Zone - 339 spc_BC 2nd 230 Class_0 Zone - 340 Zone - 340 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 626 626 201 201 201 626 626 626 339 339 339 951 951 951 2,656 2,656 2,656 0 0 0 18,650 18,650 166 166 166 120 120 120 196 196 196 262 262 262 146 146 146 281 281 281 187 187 187 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /9 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 10 /15 10 /15 7 /17 7/17 10 /15 10 /15 9 /15 10 /14 10 /14 7 /16 7 /16 7 /18 7 /18 10 /16 10 /16 9 /11 9 /11 9 /10 9 /10 9 /17 9 /17 62 62 77 77 77 76 76 76 76 76 76 80 80 80 75 75 75 80 80 80 78 78 79 79 79 76 76 76 73 73 73 79 79 79 70 70 70 67 67 67 76 76 76 58 58 67 67 67 66 66 66 66 66 66 63 63 63 66 66 66 63 63 63 66 66 62 62 62 66 66 66 65 65 65 64 64 64 63 63 63 61 61 61 67 67 67 72.0 72.0 70.0 70.0 70.0 72.0 72.0 72.0 70.0 70.0 70.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 71.7 71.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 57.5 57.5 57.5 57.3 57.3 57.3 57.1 57.1 57.1 57.5 57.5 57.5 55.6 55.6 55.6 56.0 56.0 56.0 57.2 57.2 57.2 1,490 1,490 1,917 1,917 1,917 1,042 1,042 1,042 2,037 2,037 2,037 2,646 2,646 2,646 1,344 1,344 1,344 4,175 4,175 4,175 28,551 22,316 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 27,671 27,671 31,338 31,338 31,338 19,354 19,354 19,354 33,300 33,300 33,300 49,154 49,154 49,154 24,971 24,971 24,971 77,551 77,551 77,551 521,509 407,618 6,259 6,259 6,259 3,956 3,956 3,956 14,583 14,583 14,583 10,595 10,595 10,595 5,091 5,091 5,091 11,008 11,008 11,008 15,364 15,364 15,364 1,303 1,303 497 497 497 1,843 1,843 1,843 771 771 771 1,906 1,906 1,906 7,134 7,134 7,134 0 0 0 33,121 44,638 375 375 375 194 194 194 681 681 681 491 491 491 468 468 468 889 889 889 658 658 658 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /9 9 /16 9 /16 9 /16 9 /16 9 /19 9 /19 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /14 9 /14 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 9 /12 9 /12 9 /11 9 /11 9 /17 9 /17 64 64 77 77 77 77 77 77 71 71 71 77 77 77 76 76 76 77 77 77 77 77 77 77 77 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 76 76 76 59 59 67 67 67 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 66 66 66 66 66 66 65 65 65 67 67 67 63 63 63 63 63 63 67 67 67 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 58.2 58.2 58.2 57.3 57.3 57.3 57.1 57.1 57.1 57.7 57.7 57.7 56.5 56.5 56.5 56.3 56.3 56.3 57.2 57.2 57.2 Coil Airflow cfm Coil Sensible Load Btu/h 1,469 1,469 1,917 1,917 1,917 1,032 1,032 1,032 2,008 2,008 2,008 2,644 2,644 2,644 1,337 1,337 1,337 4,061 4,061 4,061 26,008 22,285 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 28,680 28,680 33,072 33,072 33,072 19,437 19,437 19,437 33,409 33,409 33,409 51,546 51,546 51,546 32,823 32,823 32,823 77,838 77,838 77,838 651,278 557,619 7,849 7,849 7,849 5,195 5,195 5,195 17,225 17,225 17,225 12,759 12,759 12,759 6,331 6,331 6,331 12,300 12,300 12,300 20,480 20,480 20,480 Coil Latent Load Btu/h 2,059 2,059 835 835 835 3,541 3,541 3,541 1,453 1,453 1,453 5,384 5,384 5,384 12,103 12,103 12,103 0 0 0 65,740 78,660 1,025 1,025 1,025 278 278 278 1,269 1,269 1,269 1,313 1,313 1,313 701 701 701 1,464 1,464 1,464 1,309 1,309 1,309 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 3 of 100 SPACE System Zone Room Floor Area ft² spc_BC 115/116 Office_0 Peak Zone - 351 Peak Zone - 351 Block spc_BC Office 137/139/141/142_0 Peak Zone - 352 Peak Zone - 352 Block spc_BC 143 Office_0 Peak Zone - 353 Peak Zone - 353 Block spc_BC 109 Class_0 Peak Zone - 354 Peak Zone - 354 Block spc_BC 108 Class_0 Peak Zone - 355 Peak Zone - 355 Block spc_BC 106 Class_0 Peak Zone - 356 Peak Zone - 356 Block spc_BC 105 Class_0 Peak Zone - 357 Peak Zone - 357 Block spc_BC 101 Class_0 Peak Zone - 358 Peak Zone - 358 Block BC FC Peak BC FC Block spc_BC 130 Cafe/Kitchen_0 Peak Zone - 341 Peak Zone - 341 Block spc_BC AH-2 245 Lecture_0 Peak Zone - 342 Peak Zone - 342 Block spc_BC AH-3 301 Class_0 Peak Zone - 343 Peak Zone - 343 Block spc_BC AH-4 302 Class_0 Peak Zone - 344 Peak Zone - 344 Block spc_BC 306 Office (AH-5)_0 Peak spc_BC 307-312 Office (AH-5)_0 Peak spc_BC AH-5 304 Hall_0 Peak Zone - 345 Peak Zone - 345 Block 155 155 155 103 103 103 123 123 123 248 248 248 228 228 228 287 287 287 308 308 308 696 696 696 3,507 3,507 1,908 1,908 1,908 809 809 809 162 162 162 188 188 188 17 107 518 642 642 Project Name: Dataset Name: SBCC TRACE.TRC OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /12 9 /12 10 /16 10 /16 10 /16 10 /16 9 /12 9 /12 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /12 7 /19 7 /19 9 /13 9 /13 7 /10 7 /10 11 /13 11 /13 7 /18 10 /16 7 /18 10 /16 73 73 73 79 79 79 79 79 79 73 73 73 73 73 73 70 70 70 70 70 70 70 70 70 73 73 71 71 71 75 75 75 67 67 67 71 71 71 73 79 73 79 79 63 63 63 64 64 64 64 64 64 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 64 64 64 65 65 65 60 60 60 58 58 58 65 64 65 64 64 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 51.8 51.8 51.8 58.7 58.7 58.7 53.9 53.9 53.9 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.8 56.8 49.0 49.0 49.0 48.5 48.5 48.5 57.5 57.5 57.5 55.0 55.0 55.0 57.7 59.1 54.7 58.0 58.0 237 237 237 38 38 38 797 797 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 4,204 4,204 4,204 848 848 848 11,800 11,800 11,800 5,234 5,234 5,234 6,925 6,925 6,925 15,674 15,674 15,674 16,788 16,788 16,788 36,297 36,297 36,297 164,625 128,212 25,681 25,681 25,681 8,768 8,768 8,768 9,949 9,949 9,949 14,106 14,106 14,106 1,203 14,924 6,067 22,194 20,846 340 340 340 192 192 192 231 231 231 766 766 766 704 704 704 918 918 918 985 985 985 2,230 2,230 2,230 10,125 10,014 7,496 7,496 7,496 2,709 2,709 2,709 457 457 457 435 435 435 41 199 801 1,041 657 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /12 9 /12 9 /17 9 /17 10 /16 10 /16 9 /13 9 /13 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /13 7 /19 7 /19 9 /14 9 /14 7 /10 7 /10 9 /15 9 /15 7 /18 10 /16 7 /18 9 /17 73 73 73 76 76 76 79 79 79 75 75 75 73 73 73 70 70 70 70 70 70 70 70 70 75 75 71 71 71 77 77 77 67 67 67 78 78 78 73 79 73 76 76 63 63 63 67 67 67 64 64 64 65 65 65 63 63 63 63 63 63 63 63 63 63 63 63 65 65 64 64 64 66 66 66 60 60 60 66 66 66 65 64 65 67 67 56.1 56.1 56.1 52.2 52.2 52.2 58.7 58.7 58.7 54.5 54.5 54.5 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.9 60.6 49.0 49.0 49.0 48.7 48.7 48.7 57.5 57.5 57.5 57.3 57.3 57.3 57.7 59.1 54.7 58.0 59.1 Coil Airflow cfm Coil Sensible Load Btu/h 237 237 237 38 38 38 797 797 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 5,546 5,546 5,546 1,020 1,020 1,020 13,862 13,862 13,862 6,369 6,369 6,369 8,775 8,775 8,775 17,730 17,730 17,730 19,220 19,220 19,220 40,708 40,708 40,708 195,368 154,845 28,282 28,282 28,282 10,394 10,394 10,394 11,797 11,797 11,797 17,273 17,273 17,273 1,823 19,637 7,596 29,057 27,346 Coil Latent Load Btu/h 517 517 517 535 535 535 308 308 308 1,430 1,430 1,430 1,096 1,096 1,096 1,494 1,494 1,494 1,603 1,603 1,603 3,631 3,631 3,631 17,976 18,247 13,513 13,513 13,513 4,960 4,960 4,960 624 624 624 1,481 1,481 1,481 75 265 1,033 1,373 1,870 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 4 of 100 SPACE Floor Area ft² System Zone Room spc_BC AH-6 315 Lab_0 Zone - 346 Zone - 346 spc_BC AH-7 314 Class_0 Zone - 347 Zone - 347 spc_BC AH-8 313_0 Zone - 348 Zone - 348 BC Hydronic AHU BC Hydronic AHU spc_CC 108 C_0 Zone - 120 Zone - 120 spc_CC 106 Mechanical C_0 Zone - 121 Zone - 121 spc_CC 203 Storage_0 Zone - 122 Zone - 122 spc_CC 202 Storage_0 Zone - 123 Zone - 123 spc_CC 201 Eating Area C_0 Zone - 124 Zone - 124 Campus Center Dual Deck Campus Center Dual Deck spc_CC Class 122-126 C_0 Zone - 119 Zone - 119 Campus Center FC Campus Center FC spc_CC 228 Comp C_0 Zone - 125 Zone - 125 Bookstore 1 Zone - 362 Zone - 362 Bookstore 2 Zone - 363 Zone - 363 Bookstore 3 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 181 181 181 183 183 183 518 518 518 4,592 4,592 381 381 381 530 530 530 159 159 159 133 133 133 1,974 1,974 1,974 3,176 3,176 1,023 1,023 1,023 1,023 1,023 519 519 519 915 915 915 915 915 915 915 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 10 /16 6 /9 6 /9 9 /16 9 /16 10 /15 10 /16 10 /16 9 /17 9/17 9 /17 9 /17 9 /12 9 /12 9 /12 9 /12 10 /14 6 /18 6 /18 6 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 79 79 79 62 62 62 77 77 77 80 80 79 79 79 76 76 76 76 76 76 73 73 73 73 73 73 79 79 70 70 70 70 70 76 76 76 76 76 76 76 76 76 76 64 64 64 58 58 58 67 67 67 63 63 64 64 64 67 67 67 67 67 67 63 63 63 63 63 63 62 62 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 58.3 58.3 58.3 56.9 56.9 56.9 55.0 55.0 55.0 55.2 55.2 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.1 57.1 57.1 57.1 57.1 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 902 902 902 435 435 435 1,005 1,005 1,005 6,464 6,464 797 797 797 480 480 480 556 556 556 430 430 430 1,808 1,808 1,808 4,073 4,073 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 13,789 13,789 13,789 7,351 7,351 7,351 19,025 19,025 19,025 120,862 101,266 12,551 12,551 12,551 11,849 11,849 11,849 8,761 8,761 8,761 6,778 6,778 6,778 28,473 28,473 28,473 68,413 57,628 64,980 64,980 64,980 64,980 64,980 17,432 17,432 17,432 11,760 11,760 11,760 10,160 10,160 10,160 10,160 394 394 394 486 486 486 1,924 1,924 1,924 14,942 6,374 167 167 167 761 761 761 277 277 277 137 137 137 4,445 4,445 4,445 5,787 5,745 3,184 3,184 3,184 3,184 3,184 1,513 1,513 1,513 3,754 3,754 3,754 2,839 2,839 2,839 2,839 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /17 9 /17 9 /13 9 /13 9 /13 9 /13 9 /14 7 /18 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 77 77 75 75 75 77 77 77 77 77 76 76 76 76 76 76 76 76 76 75 75 75 75 75 75 77 77 73 73 73 73 73 76 76 76 76 76 76 76 76 76 76 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 65 65 65 65 65 66 66 66 66 66 66 66 66 66 66 58.5 58.5 58.5 61.5 61.5 61.5 55.0 55.0 55.0 55.8 58.3 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.4 57.4 57.4 57.4 57.4 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 Coil Airflow cfm Coil Sensible Load Btu/h 902 902 902 435 435 435 1,005 1,005 1,005 6,464 6,464 784 784 784 477 477 477 554 554 554 414 414 414 1,746 1,746 1,746 3,974 3,459 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 18,690 18,690 18,690 9,470 9,470 9,470 25,235 25,235 25,235 150,199 134,479 15,748 15,748 15,748 15,813 15,813 15,813 13,075 13,075 13,075 9,068 9,068 9,068 33,559 33,559 33,559 87,263 75,402 69,485 69,485 69,485 69,485 69,485 22,424 22,424 22,424 18,552 18,552 18,552 17,188 17,188 17,188 17,188 Coil Latent Load Btu/h 1,012 1,012 1,012 1,133 1,133 1,133 3,625 3,625 3,625 27,722 25,060 1,787 1,787 1,787 1,129 1,129 1,129 379 379 379 204 204 204 12,956 12,956 12,956 16,454 17,396 6,613 6,613 6,613 6,613 6,613 2,598 2,598 2,598 6,278 6,278 6,278 5,361 5,361 5,361 5,361 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 5 of 100 SPACE System Zone Room Floor Area ft² Zone - 364 Peak Zone - 364 Block Bookstore 4 Peak Zone - 365 Peak Zone - 365 Block Bookstore 5 Peak Zone - 366 Peak Zone - 366 Block Bookstore 6 Peak Zone - 367 Peak Zone - 367 Block Campus Center Packg RTU-1 Peak Campus Center Packg RTU-1 Block spc_DM FC-Music Office_0 Peak Zone - 137 Peak Zone - 137 Block Peak spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0 Zone - 138 Peak Zone - 138 Block spc_DM FC 3-1 Dress Rms Int_0 Peak Zone - 139 Peak Zone - 139 Block spc_DM FC 3-1 Dress Rms_0 Peak Zone - 140 Peak Zone - 140 Block Drama/Music Fan Coil Peak Drama/Music Fan Coil Block spc_HP-9 Office_0 Peak Zone - 126 Peak Zone - 126 Block spc_DM HP-7 Storage_0 Peak Zone - 127 Peak Zone - 127 Block spc_DM HP-7 Dress Rm_0 Peak Zone - 128 Peak Zone - 128 Block spc_DM HP 3/4 Class_0 Peak Zone - 129 Peak Zone - 129 Block spc_DM HP-2 Class_0 Peak Zone - 130 Peak Zone - 130 Block spc_DM HP-5 Performance Rm_0 Peak 915 915 915 915 915 915 915 915 915 915 915 6,007 6,007 338 338 338 892 892 892 267 267 267 327 327 327 1,824 1,824 121 121 121 57 57 57 9,797 9,797 9,797 926 926 926 569 569 569 1,176 Project Name: Dataset Name: SBCC TRACE.TRC OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 7/17 7 /17 7 /16 7 /16 10 /16 10 /16 9 /17 9 /12 9 /12 10 /15 10 /15 10 /15 10 /15 6 /9 6 /9 11 /13 11 /13 9 /12 76 76 76 76 76 76 76 76 76 76 76 76 76 79 79 79 75 75 75 76 76 76 79 79 79 76 76 73 73 73 80 80 80 80 80 80 62 62 62 71 71 71 73 66 66 66 66 66 66 66 66 66 66 66 66 66 64 64 64 66 66 66 66 66 66 64 64 64 67 67 63 63 63 63 63 63 63 63 63 58 58 58 58 58 58 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 51.0 51.0 56.4 56.4 56.4 54.3 54.3 54.3 44.5 44.5 44.5 58.3 58.3 58.3 55.7 55.7 57.0 57.0 57.0 54.8 54.8 54.8 51.3 51.3 51.3 55.4 55.4 55.4 59.2 59.2 59.2 53.5 404 404 404 404 404 404 404 404 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 79,989 79,989 8,123 8,123 8,123 9,831 9,831 9,831 2,946 2,946 2,946 8,853 8,853 8,853 29,753 27,815 4,747 4,747 4,747 261 261 261 99,554 99,554 99,554 21,837 21,837 21,837 35,452 35,452 35,452 27,637 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 19,459 19,459 633 633 633 1,432 1,432 1,432 1,098 1,098 1,098 269 269 269 3,432 4,394 263 263 263 35 35 35 25,148 25,148 25,148 2,451 2,451 2,451 1,082 1,082 1,082 4,324 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /17 9 /13 9 /13 7 /16 7 /16 9 /16 9 /16 7 /16 7 /16 9 /13 9 /13 7 /15 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 75 75 75 77 77 77 79 79 79 76 76 75 75 75 76 76 76 77 77 77 76 76 76 75 75 75 77 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 64 64 64 67 67 65 65 65 66 66 66 67 67 67 66 66 66 65 65 65 66 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 51.0 51.0 56.5 56.5 56.5 54.3 54.3 54.3 45.0 45.0 45.0 58.3 58.3 58.3 55.8 56.8 57.6 57.6 57.6 55.8 55.8 55.8 51.5 51.5 51.5 59.2 59.2 59.2 60.5 60.5 60.5 59.5 Coil Airflow cfm Coil Sensible Load Btu/h 404 404 404 404 404 404 404 404 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 126,914 126,914 12,772 12,772 12,772 21,797 21,797 21,797 2,242 2,242 2,242 10,451 10,451 10,451 47,261 42,971 6,446 6,446 6,446 1,151 1,151 1,151 104,158 104,158 104,158 33,229 33,229 33,229 39,761 39,761 39,761 38,930 Coil Latent Load Btu/h 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 35,683 35,683 1,763 1,763 1,763 1,818 1,818 1,818 2,311 2,311 2,311 330 330 330 6,222 7,103 408 408 408 120 120 120 68,283 68,283 68,283 5,820 5,820 5,820 3,265 3,265 3,265 8,980 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 6 of 100 SPACE Floor Area ft² System Zone Room Zone - 131 Zone - 131 spc_DM HP-10 Prop Rm_0 Zone - 132 Zone - 132 spc_DM HP-1 Main Corridor_0 Zone - 133 Zone - 133 spc_DM HP-9 Class_0 Zone - 148 Zone - 148 spc_DM HP-6 Office_0 Zone - 149 Zone - 149 spc_DM HP-8 Class1_0 Zone - 150 Zone - 150 spc_DM PHP-5-2 Offices_0 Zone - 151 Zone - 151 spc_PHP-2-1 Cargo Elevator_0 Zone - 152 Zone - 152 spc_DM PRP-5-1 Restroom_0 Zone - 153 Zone - 153 spc_DM PRP-5-1 Restroom1_0 Zone - 154 Zone - 154 Drama/Music HP Drama/Music HP spc_AC-1 Auditorium_0 Zone - 141 Zone - 141 spc_DM AN-2 Corridor_0 Zone - 142 Zone - 142 spc_DM AC-2 Rehearsal Rm_0 Zone - 143 Zone - 143 spc_DM ZN-1 Class_0 Zone - 144 Zone - 144 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,176 1,176 1,131 1,131 1,131 7,381 7,381 7,381 192 192 192 220 220 220 592 592 592 292 292 292 122 122 122 848 848 848 1,177 1,177 1,177 24,602 24,602 3,790 3,790 3,790 701 701 701 1,135 1,135 1,135 417 417 417 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /12 7 /18 7 /18 9 /11 9 /11 10 /15 10 /15 6 /9 6 /9 10 /15 10 /15 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 9 /12 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 6 /18 6 /18 73 73 73 73 73 70 70 70 80 80 80 62 62 62 80 80 80 79 79 79 79 79 79 79 79 79 79 79 79 73 73 80 80 80 75 75 75 80 80 80 70 70 70 63 63 65 65 65 63 63 63 63 63 63 58 58 58 63 63 63 64 64 64 64 64 64 64 64 64 64 64 64 63 63 63 63 63 66 66 66 63 63 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 80.0 80.0 80.0 73.1 73.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 53.5 53.5 57.4 57.4 57.4 56.2 56.2 56.2 51.3 51.3 51.3 58.2 58.2 58.2 51.3 51.3 51.3 52.2 52.2 52.2 58.6 58.6 58.6 79.6 79.6 79.6 79.6 79.6 79.6 58.9 58.9 54.9 54.9 54.9 55.9 55.9 55.9 50.7 50.7 50.7 56.6 56.6 56.6 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 27,637 27,637 36,017 36,017 36,017 106,822 106,822 106,822 1,946 1,946 1,946 10,408 10,408 10,408 6,020 6,020 6,020 2,564 2,564 2,564 4,056 4,056 4,056 538 538 538 747 747 747 358,606 299,869 74,299 74,299 74,299 11,804 11,804 11,804 10,848 10,848 10,848 20,443 20,443 20,443 4,324 4,324 1,740 1,740 1,740 9,194 9,194 9,194 492 492 492 311 311 311 1,521 1,521 1,521 545 545 545 99 99 99 -2,632 -2,632 -2,632 -3,655 -3,655 -3,655 40,918 47,013 9,753 9,753 9,753 1,126 1,126 1,126 2,908 2,908 2,908 1,296 1,296 1,296 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /15 7 /17 7 /17 9 /11 9 /11 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 77 77 75 75 75 70 70 70 76 76 76 65 65 65 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 77 77 75 75 75 77 77 77 73 73 73 66 66 66 66 66 63 63 63 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 65 65 65 59.5 59.5 57.8 57.8 57.8 56.2 56.2 56.2 51.4 51.4 51.4 58.8 58.8 58.8 51.5 51.5 51.5 52.4 52.4 52.4 58.8 58.8 58.8 79.7 79.7 79.7 79.7 79.7 79.7 59.7 62.3 55.5 55.5 55.5 55.9 55.9 55.9 51.3 51.3 51.3 56.7 56.7 56.7 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 38,930 38,930 57,496 57,496 57,496 120,423 120,423 120,423 5,018 5,018 5,018 11,069 11,069 11,069 6,298 6,298 6,298 2,691 2,691 2,691 6,557 6,557 6,557 5,343 5,343 5,343 7,418 7,418 7,418 445,988 374,351 83,988 83,988 83,988 13,640 13,640 13,640 13,026 13,026 13,026 22,815 22,815 22,815 8,980 8,980 2,459 2,459 2,459 11,397 11,397 11,397 1,203 1,203 1,203 475 475 475 4,129 4,129 4,129 1,517 1,517 1,517 288 288 288 -46,142 -46,142 -46,142 -64,061 -64,061 -64,061 -1,859 7,013 26,500 26,500 26,500 1,430 1,430 1,430 7,893 7,893 7,893 2,691 2,691 2,691 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 7 of 100 SPACE Floor Area ft² System Zone Room spc_DM ZN-3 Hall_0 Zone - 145 Zone - 145 spc_DM Zn-3 Offices_0 Zone - 146 Zone - 146 spc_ZN-3 Conf_0 Zone - 147 Zone - 147 spc_DM Scene Shop HV-1_0 Zone - 155 Zone - 155 Drama/Music MZU Drama/Music MZU spc_EBS 217/Storage C_0 Zone - 156 Zone - 156 spc_EBS 215 Class C_0 Zone - 157 Zone - 157 spc_EBS 209 Class C_0 Zone - 158 Zone - 158 spc_EBS 210 Class C_0 Zone - 159 Zone - 159 spc_EBS 109/127 Lobby C_0 Zone - 160 Zone - 160 spc_EBS 125 Class C_0 Zone - 161 Zone - 161 spc_EBS 102 Class C_0 Zone - 162 Zone - 162 spc_EBS 123 Class C_0 Zone - 163 Zone - 163 spc_EBS 119 Offices C_0 Zone - 164 Zone - 164 spc_EBS 119 Office C_0 Zone - 165 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 209 209 209 177 177 177 405 405 405 1,711 1,711 1,711 8,545 8,545 2,046 2,046 2,046 758 758 758 1,358 1,358 1,358 1,333 1,333 1,333 1,771 1,771 1,771 396 396 396 1,332 1,332 1,332 1,622 1,622 1,622 399 399 399 306 306 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 10 /16 10 /16 10 /16 6 /10 6 /10 10 /13 10 /13 9 /16 7 /15 7/15 7 /16 7 /16 10 /15 10 /15 7 /18 7 /18 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 79 79 79 79 79 79 65 65 65 77 77 77 77 77 77 77 77 76 76 76 80 80 80 73 73 73 75 75 75 73 73 73 73 73 73 73 73 73 75 75 75 75 75 64 64 64 64 64 64 58 58 58 59 59 59 67 67 66 66 66 66 66 66 63 63 63 65 65 65 66 66 66 65 65 65 65 65 65 65 65 65 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.9 49.9 49.9 51.7 51.7 51.7 50.6 50.6 50.6 57.7 57.7 57.7 55.4 55.4 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 24 24 24 64 64 64 206 206 206 1,561 1,561 1,561 8,045 8,045 931 931 931 493 493 493 1,547 1,547 1,547 1,511 1,511 1,511 744 744 744 473 473 473 2,019 2,019 2,019 1,486 1,486 1,486 309 309 309 177 177 583 583 583 1,443 1,443 1,443 4,907 4,907 4,907 24,799 24,799 24,799 149,125 129,890 18,050 18,050 18,050 9,553 9,553 9,553 29,992 29,992 29,992 29,286 29,286 29,286 14,421 14,421 14,421 9,178 9,178 9,178 39,142 39,142 39,142 28,811 28,811 28,811 5,997 5,997 5,997 3,436 3,436 169 169 169 330 330 330 1,311 1,311 1,311 3,134 3,134 3,134 20,027 30,017 3,114 3,114 3,114 2,661 2,661 2,661 3,489 3,489 3,489 4,607 4,607 4,607 2,924 2,924 2,924 1,369 1,369 1,369 4,604 4,604 4,604 5,608 5,608 5,608 1,057 1,057 1,057 811 811 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 9 /14 9 /14 9 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /17 77 77 77 76 76 76 77 77 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 75 75 75 75 75 75 73 73 73 73 73 73 75 75 75 75 75 75 75 75 67 67 67 67 67 67 67 67 67 66 66 66 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 66 66 51.4 51.4 51.4 52.3 52.3 52.3 53.5 53.5 53.5 58.2 58.2 58.2 55.9 57.5 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 24 24 24 64 64 64 206 206 206 1,561 1,561 1,561 8,045 8,045 903 903 903 493 493 493 1,515 1,515 1,515 1,493 1,493 1,493 744 744 744 473 473 473 2,019 2,019 2,019 1,454 1,454 1,454 309 309 309 177 177 715 715 715 1,748 1,748 1,748 5,430 5,430 5,430 30,462 30,462 30,462 171,824 156,601 40,996 40,996 40,996 17,369 17,369 17,369 45,366 45,366 45,366 45,809 45,809 45,809 35,058 35,058 35,058 14,006 14,006 14,006 55,862 55,862 55,862 46,115 46,115 46,115 10,829 10,829 10,829 6,764 6,764 Coil Latent Load Btu/h 468 468 468 919 919 919 3,494 3,494 3,494 10,580 10,580 10,580 53,975 55,726 4,331 4,331 4,331 4,766 4,766 4,766 9,476 9,476 9,476 8,212 8,212 8,212 4,199 4,199 4,199 2,548 2,548 2,548 8,567 8,567 8,567 9,995 9,995 9,995 1,822 1,822 1,822 1,398 1,398 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 8 of 100 SPACE Floor Area ft² System Zone Room Zone - 165 spc_EBS 116 Office C_0 Zone - 166 Zone - 166 spc_EBS 110-113 Office UC_0 Zone - 167 Zone - 167 spc_EBS 114 Class C_0 Zone - 168 Zone - 168 spc_EBS 115 Class C_0 Zone - 169 Zone - 169 spc_EBS 209 Class UC_0 Zone - 172 Zone - 172 spc_EBS 210 Class C_1 Zone - 173 Zone - 173 spc_EBS 215 Class C_1 Zone - 174 Zone - 174 spc_EBS 218 Office C_0 Zone - 175 Zone - 175 spc_EBS 216 Office C_0 Zone - 176 Zone - 176 EBS VAV EBS VAV spc_H 326 Class C_0 Zone - 206 Zone - 206 spc_H 328 Class C_0 Zone - 207 Zone - 207 spc_H 328 Office C_0 Zone - 208 Zone - 208 Humanities Fan Coil Humanities Fan Coil spc_H 104/107/112 Art C_0 Zone - 177 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 306 7 /17 156 7 /18 156 156 7 /18 515 7 /18 515 515 7 /18 893 10 /14 893 893 10 /14 1,659 9 /16 1,659 1,659 9 /16 1,334 7 /16 1,334 1,334 7 /16 1,334 7/16 1,334 1,334 7 /16 790 7 /18 790 790 7 /18 70 7 /18 70 70 7 /18 74 7 /17 74 74 7 /17 18,147 18,147 7 /17 845 5 /17 845 845 5 /17 1,818 7 /16 1,818 1,818 7 /16 300 7 /12 300 300 7 /12 2,963 2,963 7 /17 7,121 7 /16 7,121 75 73 73 73 73 73 73 79 79 79 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 72 72 72 76 76 76 73 73 73 75 75 76 76 66 65 65 65 65 65 65 62 62 62 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 63 63 63 66 66 66 63 63 63 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 54.3 54.3 54.3 56.6 56.6 56.5 56.5 177 220 220 220 624 624 624 1,093 1,093 1,093 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,925 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,288 5,288 3,436 4,262 4,262 4,262 12,097 12,097 12,097 21,186 21,186 21,186 31,380 31,380 31,380 16,818 16,818 16,818 16,818 16,818 16,818 14,759 14,759 14,759 2,665 2,665 2,665 826 826 826 308,677 289,380 76,201 76,201 76,201 24,051 24,051 24,051 4,645 4,645 4,645 104,897 101,595 91,368 91,368 811 368 368 368 1,214 1,214 1,214 2,014 2,014 2,014 6,149 6,149 6,149 4,685 4,685 4,685 4,685 4,685 4,685 2,731 2,731 2,731 166 166 166 195 195 195 52,452 52,299 2,350 2,350 2,350 6,371 6,371 6,371 631 631 631 9,352 9,537 24,945 24,945 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /18 7 /18 7 /18 7 /18 9 /14 9 /14 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /17 7 /15 75 73 73 73 73 73 73 77 77 77 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 73 73 73 76 76 76 76 76 76 75 75 77 77 66 65 65 65 65 65 65 66 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 65 65 65 66 66 66 66 66 66 66 66 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 57.2 57.2 57.2 56.7 57.1 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 177 220 220 220 624 624 624 1,079 1,079 1,079 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,801 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,284 5,284 6,764 6,557 6,557 6,557 19,460 19,460 19,460 22,361 22,361 22,361 49,825 49,825 49,825 30,579 30,579 30,579 30,579 30,579 30,579 23,381 23,381 23,381 3,913 3,913 3,913 1,626 1,626 1,626 504,179 486,608 92,686 92,686 92,686 49,932 49,932 49,932 8,423 8,423 8,423 151,042 148,011 99,527 99,527 Coil Latent Load Btu/h 1,398 677 677 677 2,235 2,235 2,235 5,495 5,495 5,495 11,570 11,570 11,570 8,391 8,391 8,391 8,391 8,391 8,391 5,082 5,082 5,082 305 305 305 336 336 336 97,796 94,521 5,460 5,460 5,460 11,390 11,390 11,390 1,341 1,341 1,341 18,190 17,762 43,603 43,603 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 9 of 100 SPACE Floor Area ft² System Zone Room Zone - 177 spc_H 102 Class C_0 Zone - 178 Zone - 178 spc_H 106 Office C_0 Zone - 179 Zone - 179 spc_H 2444 Class C_0 Zone - 180 Zone - 180 spc_H 245A/B Class C_0 Zone - 181 Zone - 181 spc_H 226/A office C_0 Zone - 182 Zone - 182 spc_H 208-217 Office C_0 Zone - 183 Zone - 183 spc_H 225 Office C_0 Zone - 184 Zone - 184 spc_H 242/207 Corridor C_0 Zone - 185 Zone - 185 spc_H 123U Art AH-1/23_0 Zone - 186 Zone - 186 spc_H 111 Class C_0 Zone - 187 Zone - 187 spc_H 221/220/204 Class C_0 Zone - 188 Zone - 188 spc_H 232A Class C_0 Zone - 189 Zone - 189 spc_H 239 Class Office_0 Zone - 190 Zone - 190 spc_H 237 Office C_0 Zone - 191 Zone - 191 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 7,121 1,004 1,004 1,004 229 229 229 555 555 555 1,686 1,686 1,686 272 272 272 1,065 1,065 1,065 267 267 267 4,126 4,126 4,126 2,482 2,482 2,482 1,805 1,805 1,805 4,564 4,564 4,564 1,111 1,111 1,111 306 306 306 90 90 90 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 11 /13 11 /13 11 /14 11 /14 11 /14 11 /14 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 7 /17 7 /17 76 76 76 76 75 75 75 76 76 76 75 75 75 71 71 71 73 73 73 73 73 73 79 79 79 75 75 75 76 76 76 77 77 77 76 76 76 77 77 77 75 75 75 66 66 66 66 66 66 66 66 66 66 66 66 66 58 58 58 60 60 60 60 60 60 64 64 64 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 5,288 627 627 627 122 122 122 346 346 346 2,157 2,157 2,157 798 798 798 3,496 3,496 3,496 765 765 765 1,412 1,412 1,412 2,382 2,382 2,382 1,127 1,127 1,127 3,577 3,577 3,577 693 693 693 311 311 311 48 48 48 91,368 10,835 10,835 10,835 2,102 2,102 2,102 5,987 5,987 5,987 37,265 37,265 37,265 13,783 13,783 13,783 60,401 60,401 60,401 13,211 13,211 13,211 24,400 24,400 24,400 41,156 41,156 41,156 19,474 19,474 19,474 61,807 61,807 61,807 11,982 11,982 11,982 5,382 5,382 5,382 828 828 828 24,945 3,519 3,519 3,519 604 604 604 1,944 1,944 1,944 5,523 5,523 5,523 89 89 89 766 766 766 192 192 192 3,332 3,332 3,332 8,130 8,130 8,130 6,325 6,325 6,325 15,809 15,809 15,809 3,891 3,891 3,891 1,060 1,060 1,060 238 238 238 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /15 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 9 /14 9 /14 9 /15 9 /15 9 /15 9 /15 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /15 7 /15 9 /16 9 /16 7 /15 7 /15 9 /17 9 /17 77 77 77 77 76 76 76 77 77 77 77 77 77 77 77 77 78 78 78 78 78 78 77 77 77 76 76 76 77 77 77 77 77 77 77 77 77 77 77 77 76 76 76 66 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 5,284 600 600 600 119 119 119 331 331 331 2,071 2,071 2,071 743 743 743 2,999 2,999 2,999 665 665 665 1,401 1,401 1,401 2,313 2,313 2,313 1,078 1,078 1,078 3,577 3,577 3,577 663 663 663 311 311 311 47 47 47 99,527 11,228 11,228 11,228 2,209 2,209 2,209 6,204 6,204 6,204 40,964 40,964 40,964 15,383 15,383 15,383 74,566 74,566 74,566 13,581 13,581 13,581 25,840 25,840 25,840 45,783 45,783 45,783 20,181 20,181 20,181 67,488 67,488 67,488 12,417 12,417 12,417 5,994 5,994 5,994 871 871 871 Coil Latent Load Btu/h 43,603 6,979 6,979 6,979 1,184 1,184 1,184 3,856 3,856 3,856 11,713 11,713 11,713 999 999 999 4,843 4,843 4,843 1,216 1,216 1,216 9,229 9,229 9,229 17,267 17,267 17,267 12,544 12,544 12,544 27,948 27,948 27,948 7,718 7,718 7,718 1,874 1,874 1,874 467 467 467 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 10 of 100 SPACE Floor Area ft² System Zone Room spc_H 236 Office C_0 Zone - 192 Zone - 192 spc_H 241 Class C_0 Zone - 193 Zone - 193 spc_H 309-318 Offices C_0 Zone - 194 Zone - 194 spc_H 240 Class C_0 Zone - 195 Zone - 195 spc_H 300 Restrooms C_0 Zone - 196 Zone - 196 spc_H 322 Office C_0 Zone - 197 Zone - 197 spc_H 323 Office C_0 Zone - 198 Zone - 198 spc_H 300H Hall C_0 Zone - 199 Zone - 199 spc_H 202 Class C_0 Zone - 200 Zone - 200 spc_H 205 Office C_0 Zone - 201 Zone - 201 spc_H 205/203 Class C_0 Zone - 202 Zone - 202 spc_H 232B Office C_0 Zone - 203 Zone - 203 spc_H 223 Class C_0 Zone - 204 Zone - 204 spc_H 223U Storage C_0 Zone - 205 Zone - 205 spc_H 306 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 272 272 272 571 571 571 1,012 1,012 1,012 818 818 818 339 339 339 265 265 265 265 265 265 3,593 3,593 3,593 1,118 1,118 1,118 270 270 270 846 846 846 161 161 161 616 616 616 165 165 165 727 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /16 7 /16 11 /14 11 /14 7 /15 7 /15 9 /17 9 /17 11 /14 11 /14 7 /17 7 /17 10 /16 10 /16 8 /10 8 /10 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 75 75 75 76 76 76 73 73 73 77 77 77 76 76 76 73 73 73 75 75 75 79 79 79 67 67 67 75 75 75 76 76 76 75 75 75 76 76 76 77 77 77 76 66 66 66 66 66 66 60 60 60 66 66 66 67 67 67 60 60 60 66 66 66 64 64 64 61 61 61 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 145 145 145 356 356 356 4,319 4,319 4,319 642 642 642 542 542 542 1,069 1,069 1,069 141 141 141 3,898 3,898 3,898 2,401 2,401 2,401 144 144 144 528 528 528 86 86 86 385 385 385 51 51 51 454 2,500 2,500 2,500 6,155 6,155 6,155 74,623 74,623 74,623 11,100 11,100 11,100 14,193 14,193 14,193 18,478 18,478 18,478 2,434 2,434 2,434 67,353 67,353 67,353 41,487 41,487 41,487 2,483 2,483 2,483 9,121 9,121 9,121 1,483 1,483 1,483 6,648 6,648 6,648 876 876 876 7,841 719 719 719 1,999 1,999 1,999 728 728 728 2,834 2,834 2,834 619 619 619 190 190 190 700 700 700 9,908 9,908 9,908 3,433 3,433 3,433 714 714 714 2,962 2,962 2,962 426 426 426 2,159 2,159 2,159 250 250 250 2,546 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /17 9 /17 9 /16 9 /16 9 /15 9 /15 7 /15 7 /15 9 /17 9 /17 9 /15 9 /15 9 /17 9 /17 9 /16 9 /16 9 /11 9 /11 9 /17 9 /17 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 9 /15 9 /15 7 /16 76 76 76 77 77 77 78 78 78 77 77 77 76 76 76 78 78 78 76 76 76 77 77 77 70 70 70 76 76 76 77 77 77 76 76 76 77 77 77 78 78 78 76 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 63 63 63 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 142 142 142 341 341 341 3,657 3,657 3,657 642 642 642 210 210 210 890 890 890 138 138 138 3,839 3,839 3,839 2,239 2,239 2,239 141 141 141 505 505 505 84 84 84 368 368 368 47 47 47 441 2,628 2,628 2,628 6,379 6,379 6,379 87,004 87,004 87,004 12,091 12,091 12,091 14,647 14,647 14,647 21,157 21,157 21,157 2,558 2,558 2,558 126,357 126,357 126,357 45,716 45,716 45,716 2,609 2,609 2,609 9,452 9,452 9,452 1,558 1,558 1,558 6,890 6,890 6,890 878 878 878 19,161 Coil Latent Load Btu/h 1,408 1,408 1,408 3,965 3,965 3,965 4,603 4,603 4,603 5,010 5,010 5,010 4,236 4,236 4,236 1,203 1,203 1,203 1,371 1,371 1,371 24,964 24,964 24,964 5,771 5,771 5,771 1,399 1,399 1,399 5,875 5,875 5,875 835 835 835 4,282 4,282 4,282 357 357 357 4,551 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 11 of 100 SPACE System Zone Room Zone - 211 Peak Zone - 211 Block spc_H 308 Class H_0 Peak Zone - 212 Peak Zone - 212 Block spc_H 301-307 Classes C_0 Peak Zone - 213 Peak Zone - 213 Block spc_H 301 Class C_0 Peak Zone - 214 Peak Zone - 214 Block spc_H 3281 Hall C_0 Peak Zone - 215 Peak Zone - 215 Block Humanities VAV Peak Humanities VAV Block spc_IDC 335 Office C_0 Peak Zone - 220 Peak Zone - 220 Block spc_IDC 313 Wrk Rm_0 Peak Zone - 221 Peak Zone - 221 Block spc_IDC 317 Wrk Rm C_0 Peak Zone - 222 Peak Zone - 222 Block spc_IDC 329 C_0 Peak Zone - 223 Peak Zone - 223 Block IDC Fan Coil Peak IDC Fan Coil Block Peak spc_IDC 102/103/104/109 Int Class_0 Zone - 216 Peak Zone - 216 Block spc_IDC 205 Class C_0 Peak Zone - 217 Peak Zone - 217 Block spc_IDC 211/210 Class_0 Peak Zone - 218 Peak Zone - 218 Block spc_IDC 333 Office_0 Peak Zone - 219 Peak Zone - 219 Block IDC VAV Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 727 727 512 512 512 3,348 3,348 3,348 633 633 633 228 228 228 42,441 42,441 107 107 107 206 206 206 171 171 171 102 102 102 586 586 3,318 3,318 3,318 460 460 460 1,001 1,001 1,001 414 414 414 5,194 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /16 7 /16 10 /15 7/17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 10 /15 10 /15 10 /15 10 /15 10 /15 10 /15 10 /17 10 /17 76 76 76 76 76 77 77 77 76 76 76 76 76 76 80 80 75 75 75 76 76 76 76 76 76 76 76 76 76 76 80 80 80 80 80 80 80 80 80 77 77 77 80 66 66 66 66 66 66 66 66 66 66 66 66 66 66 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 63 63 63 63 63 63 64 64 64 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.1 72.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 454 454 320 320 320 2,748 2,748 2,748 395 395 395 53 53 53 41,826 37,423 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,694 1,694 1,694 859 859 859 511 511 511 180 180 180 3,244 7,841 7,841 5,526 5,526 5,526 47,476 47,476 47,476 6,823 6,823 6,823 911 911 911 727,491 650,911 1,280 1,280 1,280 2,975 2,975 2,975 2,627 2,627 2,627 1,357 1,357 1,357 8,239 8,216 32,706 32,706 32,706 16,577 16,577 16,577 9,869 9,869 9,869 3,472 3,472 3,472 62,624 2,546 2,546 1,795 1,795 1,795 11,597 11,597 11,597 2,216 2,216 2,216 354 354 354 122,518 95,452 284 284 284 722 722 722 600 600 600 357 357 357 1,962 1,958 8,526 8,526 8,526 1,182 1,182 1,182 2,573 2,573 2,573 855 855 855 13,135 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 9 /16 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 76 76 76 76 76 76 76 76 76 76 76 76 76 76 77 77 75 75 75 76 76 76 76 76 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 75 75 75 77 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 441 441 311 311 311 2,733 2,733 2,733 384 384 384 49 49 49 39,362 36,284 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,668 1,668 1,668 843 843 843 503 503 503 179 179 179 3,194 19,161 19,161 13,504 13,504 13,504 102,755 102,755 102,755 16,673 16,673 16,673 4,252 4,252 4,252 957,271 890,214 2,183 2,183 2,183 4,555 4,555 4,555 3,950 3,950 3,950 2,128 2,128 2,128 12,817 12,798 38,524 38,524 38,524 19,698 19,698 19,698 11,625 11,625 11,625 10,755 10,755 10,755 80,821 4,551 4,551 3,208 3,208 3,208 20,961 20,961 20,961 3,960 3,960 3,960 448 448 448 249,846 272,391 488 488 488 1,291 1,291 1,291 1,072 1,072 1,072 638 638 638 3,490 3,478 23,156 23,156 23,156 3,209 3,209 3,209 6,987 6,987 6,987 1,894 1,894 1,894 35,247 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 12 of 100 SPACE Floor Area ft² System Zone Room IDC VAV spc_LRC 140-01-08 C_0 Zone - 224 Zone - 224 spc_LRC 140-09 C_0 Zone - 225 Zone - 225 spc_LRC 13-15 C_0 Zone - 226 Zone - 226 spc_LRC 16 C_0 Zone - 227 Zone - 227 spc_LRC 17/18_0 Zone - 228 Zone - 228 spc_LRC 5 C (Study?)_0 Zone - 229 Zone - 229 spc_LRC 9 Storage_0 Zone - 230 Zone - 230 spc_LRC 10 Storage_0 Zone - 231 Zone - 231 spc_LRC 7 C_0 Zone - 232 Zone - 232 spc_LRC 8 Stair_0 Zone - 233 Zone - 233 spc_LRC Catalog C_0 Zone - 234 Zone - 234 spc_LRC Computer_0 Zone - 235 Zone - 235 spc_LRC 2/6_0 Zone - 236 Zone - 236 spc_LRC 1st RR C_0 Zone - 237 Zone - 237 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 5,194 1,843 1,843 1,843 250 250 250 153 153 153 66 66 66 94 94 94 57 57 57 29 29 29 24 24 24 119 119 119 302 302 302 56 56 56 525 525 525 137 137 137 226 226 226 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /15 6 /10 6 /10 9 /12 9 /12 9 /11 9 /11 10 /13 10 /13 10 /16 10 /16 7/15 7 /15 7 /15 7 /15 6 /10 6 /10 6 /18 6 /18 7 /18 7 /18 7 /18 7 /18 6 /17 6 /17 7 /15 7 /15 10 /16 10 /16 80 65 65 65 73 73 73 70 70 70 77 77 77 79 79 79 77 77 77 77 77 77 65 65 65 70 70 70 73 73 73 73 73 73 72 72 72 77 77 77 79 79 79 63 58 58 58 63 63 63 63 63 63 59 59 59 64 64 64 66 66 66 66 66 66 58 58 58 63 63 63 65 65 65 65 65 65 63 63 63 66 66 66 64 64 64 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 3,237 1,595 1,595 1,595 797 797 797 632 632 632 296 296 296 800 800 800 34 34 34 9 9 9 43 43 43 499 499 499 178 178 178 119 119 119 1,809 1,809 1,809 78 78 78 362 362 362 62,481 28,266 28,266 28,266 14,118 14,118 14,118 11,205 11,205 11,205 5,239 5,239 5,239 14,180 14,180 14,180 606 606 606 156 156 156 770 770 770 8,836 8,836 8,836 3,148 3,148 3,148 2,112 2,112 2,112 32,061 32,061 32,061 1,384 1,384 1,384 9,633 9,633 9,633 12,972 5,957 5,957 5,957 915 915 915 580 580 580 159 159 159 316 316 316 196 196 196 44 44 44 16 16 16 366 366 366 460 460 460 226 226 226 1,210 1,210 1,210 556 556 556 181 181 181 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 7 /16 7 /16 9 /13 9 /13 9 /11 9 /11 9 /13 9 /13 9 /16 9 /16 9 /16 9 /16 9 /15 9 /15 6 /10 6 /10 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 77 76 76 76 75 75 75 70 70 70 75 75 75 77 77 77 77 77 77 78 78 78 65 65 65 73 73 73 73 73 73 73 73 73 75 75 75 77 77 77 79 79 79 67 66 66 66 65 65 65 63 63 63 65 65 65 67 67 67 67 67 67 66 66 66 58 58 58 65 65 65 65 65 65 65 65 65 66 66 66 67 67 67 64 64 64 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 3,189 1,448 1,448 1,448 757 757 757 632 632 632 289 289 289 781 781 781 34 34 34 8 8 8 43 43 43 495 495 495 178 178 178 119 119 119 1,791 1,791 1,791 77 77 77 186 186 186 79,588 54,618 54,618 54,618 17,332 17,332 17,332 12,865 12,865 12,865 5,989 5,989 5,989 15,724 15,724 15,724 602 602 602 149 149 149 999 999 999 9,606 9,606 9,606 3,388 3,388 3,388 2,494 2,494 2,494 34,140 34,140 34,140 1,369 1,369 1,369 8,860 8,860 8,860 Coil Latent Load Btu/h 35,420 12,597 12,597 12,597 1,569 1,569 1,569 880 880 880 417 417 417 710 710 710 392 392 392 63 63 63 19 19 19 757 757 757 592 592 592 392 392 392 2,556 2,556 2,556 1,032 1,032 1,032 996 996 996 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 13 of 100 SPACE System Zone Room spc_LRC 24_0 Peak Zone - 238 Peak Zone - 238 Block spc_LRC 25_0 Peak Zone - 239 Peak Zone - 239 Block spc_LRC 105 C Work_0 Peak Zone - 240 Peak Zone - 240 Block spc_LRC Tables/124B C_0 Peak Zone - 241 Peak Zone - 241 Block spc_LRC 120/122/123 Office C_0 Peak Zone - 242 Peak Zone - 242 Block spc_LRC Tutor Lab C_0 Peak Zone - 243 Peak Zone - 243 Block spc_LRC Lobby/112B Corridor C_0Peak Zone - 244 Peak Zone - 244 Block spc_LRC Dir Offc C_0 Peak Zone - 245 Peak Zone - 245 Block spc_LRC 108/111/115 Counter_0 Peak Zone - 246 Peak Zone - 246 Block spc_LRC 149A_0 Peak Zone - 247 Peak Zone - 247 Block spc_LRC 137 Work C_0 Peak Zone - 248 Peak Zone - 248 Block spc_LRC 140-142 Director_0 Peak Zone - 249 Peak Zone - 249 Block spc_LRC 145 Office C_0 Peak Zone - 250 Peak Zone - 250 Block spc_LRC 146A Storage_0 Peak Zone - 251 Peak Zone - 251 Block spc_LRC 146_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 564 564 564 325 325 325 62 62 62 647 647 647 58 58 58 63 63 63 582 582 582 36 36 36 335 335 335 25 25 25 59 59 59 38 38 38 23 23 23 14 14 14 80 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 10 /16 7 /18 7 /18 7 /18 7 /18 10 /15 10 /15 6 /11 6 /11 7 /15 7 /15 7 /18 7 /18 6 /18 6 /18 7 /15 7 /15 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 10 /13 79 79 79 73 73 73 73 73 73 80 80 80 68 68 68 77 77 77 73 73 73 70 70 70 77 77 77 73 73 73 73 73 73 75 75 75 75 75 75 79 79 79 77 64 64 64 65 65 65 65 65 65 63 63 63 60 60 60 66 66 66 65 65 65 63 63 63 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 64 64 64 59 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 2,024 2,024 2,024 956 956 956 123 123 123 1,184 1,184 1,184 119 119 119 110 110 110 387 387 387 147 147 147 191 191 191 45 45 45 191 191 191 20 20 20 12 12 12 64 64 64 252 35,871 35,871 35,871 16,939 16,939 16,939 2,178 2,178 2,178 20,983 20,983 20,983 2,116 2,116 2,116 1,946 1,946 1,946 6,866 6,866 6,866 2,614 2,614 2,614 3,378 3,378 3,378 793 793 793 3,381 3,381 3,381 359 359 359 214 214 214 1,140 1,140 1,140 4,464 1,890 1,890 1,890 1,302 1,302 1,302 214 214 214 1,652 1,652 1,652 103 103 103 180 180 180 975 975 975 72 72 72 1,358 1,358 1,358 86 86 86 204 204 204 101 101 101 60 60 60 11 11 11 192 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 9 /16 9 /16 7 /12 7 /12 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 9 /14 77 77 77 73 73 73 73 73 73 77 77 77 73 73 73 76 76 76 75 75 75 73 73 73 76 76 76 73 73 73 73 73 73 75 75 75 75 75 75 76 76 76 77 67 67 67 65 65 65 65 65 65 67 67 67 63 63 63 66 66 66 66 66 66 65 65 65 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 67 67 67 66 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 1,981 1,981 1,981 956 956 956 123 123 123 1,113 1,113 1,113 117 117 117 110 110 110 364 364 364 145 145 145 190 190 190 45 45 45 191 191 191 20 20 20 12 12 12 63 63 63 233 39,177 39,177 39,177 19,463 19,463 19,463 3,446 3,446 3,446 32,086 32,086 32,086 2,850 2,850 2,850 2,980 2,980 2,980 14,670 14,670 14,670 3,509 3,509 3,509 8,372 8,372 8,372 1,278 1,278 1,278 4,731 4,731 4,731 936 936 936 559 559 559 1,612 1,612 1,612 5,818 Coil Latent Load Btu/h 4,243 4,243 4,243 2,256 2,256 2,256 397 397 397 4,480 4,480 4,480 178 178 178 312 312 312 1,365 1,365 1,365 155 155 155 2,288 2,288 2,288 159 159 159 378 378 378 174 174 174 104 104 104 35 35 35 535 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 14 of 100 SPACE System Zone Room Floor Area ft² Zone - 252 Peak Zone - 252 Block spc_LRC Library_0 Peak Zone - 253 Peak Zone - 253 Block spc_LRC 140-14_0 Peak Zone - 254 Peak Zone - 254 Block spc_LRC 140-03_0 Peak Zone - 255 Peak Zone - 255 Block spc_LRC 101 Work C_0 Peak Zone - 256 Peak Zone - 256 Block spc_LRC 108-110 Storage_0 Peak Zone - 257 Peak Zone - 257 Block spc_LRC 109 Work_0 Peak Zone - 258 Peak Zone - 258 Block LRC VAV Peak LRC VAV Block spc_OE 10WM Restrooms AH-2_0Peak Zone - 259 Peak Zone - 259 Block spc_OE 112 Class C_0 Peak Zone - 260 Peak Zone - 260 Block spc_OE 116 Class C_0 Peak Zone - 261 Peak Zone - 261 Block spc_OE 180H/182 Class C_0 Peak Zone - 262 Peak Zone - 262 Block spc_OE 180A Office C_0 Peak Zone - 263 Peak Zone - 263 Block OE Pckg AH Peak OE Pckg AH Block spc_PE 108 Weight Rm HP3/4_0 Peak Zone - 006 Peak Zone - 006 Block spc_PE Locker/RR HP-06/07_0 Peak 80 80 0 0 0 42 42 42 86 86 86 62 62 62 24 24 24 43 43 43 7,052 7,052 172 172 172 522 522 522 1,121 1,121 1,121 509 509 509 66 66 66 2,391 2,391 3,594 3,594 3,594 1,968 Project Name: Dataset Name: SBCC TRACE.TRC OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /13 11 /12 11 /12 9 /12 9 /12 6 /10 6 /10 9 /17 9 /17 7 /15 7/15 9 /17 9 /17 9 /16 7 /18 7 /18 10 /15 10 /15 7 /18 7 /18 9 /11 9 /11 7 /17 7 /17 10 /14 9 /10 9 /10 7 /18 77 77 68 68 68 73 73 73 65 65 65 76 76 76 77 77 77 76 76 76 77 77 73 73 73 80 80 80 73 73 73 70 70 70 75 75 75 79 79 67 67 67 73 59 59 55 55 55 63 63 63 58 58 58 67 67 67 66 66 66 67 67 67 67 67 65 65 65 63 63 63 65 65 65 63 63 63 66 66 66 62 62 61 61 61 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.2 72.2 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.7 72.7 72.0 72.0 72.0 80.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 73.2 73.2 73.2 56.6 56.6 56.6 52.2 52.2 52.2 55.6 55.6 55.6 48.8 48.8 48.8 56.4 56.4 54.5 54.5 54.5 74.3 252 252 2,551 2,551 2,551 190 190 190 207 207 207 186 186 186 7 7 7 143 143 143 16,361 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 4,464 4,464 45,210 45,210 45,210 3,371 3,371 3,371 3,672 3,672 3,672 3,302 3,302 3,302 123 123 123 2,540 2,540 2,540 293,173 232,240 2,089 2,089 2,089 17,559 17,559 17,559 20,357 20,357 20,357 17,712 17,712 17,712 589 589 589 58,307 44,634 41,395 41,395 41,395 19,874 192 192 0 0 0 154 154 154 277 277 277 218 218 218 36 36 36 152 152 152 20,421 25,647 59 59 59 1,340 1,340 1,340 3,874 3,874 3,874 1,628 1,628 1,628 176 176 176 7,077 4,708 4,036 4,036 4,036 668 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /14 9 /11 9 /11 9 /12 9 /12 7 /17 7 /17 9 /17 9 /17 7 /16 7 /16 9 /17 9 /17 9 /16 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 9 /13 9 /13 7 /17 7 /17 9 /16 9 /13 9 /13 9 /17 77 77 70 70 70 73 73 73 75 75 75 76 76 76 76 76 76 76 76 76 77 77 76 76 76 77 77 77 73 73 73 75 75 75 75 75 75 77 77 75 75 75 76 66 66 63 63 63 63 63 63 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 66 67 67 65 65 65 67 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 76.2 76.2 76.2 57.4 57.4 57.4 52.2 52.2 52.2 57.4 57.4 57.4 48.8 48.8 48.8 57.5 60.7 57.2 57.2 57.2 75.4 Coil Airflow cfm Coil Sensible Load Btu/h 233 233 2,488 2,488 2,488 190 190 190 164 164 164 186 186 186 7 7 7 143 143 143 15,679 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 5,818 5,818 47,040 47,040 47,040 4,151 4,151 4,151 4,618 4,618 4,618 4,899 4,899 4,899 475 475 475 3,755 3,755 3,755 382,332 328,402 2,439 2,439 2,439 21,294 21,294 21,294 23,315 23,315 23,315 22,689 22,689 22,689 1,667 1,667 1,667 71,405 61,879 36,526 36,526 36,526 36,640 Coil Latent Load Btu/h 535 535 0 0 0 223 223 223 569 569 569 432 432 432 50 50 50 300 300 300 41,604 50,410 755 755 755 3,639 3,639 3,639 7,205 7,205 7,205 2,921 2,921 2,921 304 304 304 14,824 15,804 19,890 19,890 19,890 8,557 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 15 of 100 SPACE System Zone Room Zone - 008 Peak Zone - 008 Block Peak spc_PE 302-310E Office Partially C_0 Zone - 011 Peak Zone - 011 Block PE Heat Pump Peak PE Heat Pump Block spc_PE Gym AH1_0 Peak Zone - 001 Peak Zone - 001 Block spc_PE Team Lockey RH4_0 Peak Zone - 002 Peak Zone - 002 Block spc_PE 113 RH7/RH8_0 Peak Zone - 003 Peak Zone - 003 Block spc_PE 114 C_0 Peak Zone - 004 Peak Zone - 004 Block spc_PE 109 NC_0 Peak Zone - 005 Peak Zone - 005 Block spc_PE 2nd Flr Lobby_0 Peak Zone - 007 Peak Zone - 007 Block spc_PE 214-218, 201-203 Offices C_0 Peak Zone - 009 Peak Zone - 009 Block spc_PE 3 Press Box RH02 _0 Peak Zone - 010 Peak Zone - 010 Block PE VAV Htg Only Peak PE VAV Htg Only Block spc_sp_55 Peak Zone - 264 Peak Zone - 264 Block spc_sp_56 Peak Zone - 265 Peak Zone - 265 Block spc_sp_57 Peak Zone - 266 Peak Zone - 266 Block spc_sp_58 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 1,968 1,968 498 498 498 6,061 6,061 7,524 7,524 7,524 744 744 744 1,696 1,696 1,696 1,001 1,001 1,001 683 683 683 7,013 7,013 7,013 1,922 1,922 1,922 174 174 174 20,757 20,757 1,130 1,130 1,130 1,130 1,130 1,130 1,159 1,159 1,159 1,087 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 10 /16 10 /16 9 /16 9 /16 9 /10 9 /10 10 /15 10 /15 7 /10 7 /10 7 /18 7 /18 10 /16 10 /16 7 /17 10 /13 10 /13 10 /15 10 /15 9 /12 9 /12 10 /16 73 73 73 73 73 73 73 75 75 75 79 79 79 77 77 77 67 67 67 80 80 80 67 67 67 73 73 73 79 79 79 75 75 77 77 77 80 80 80 73 73 73 79 65 65 65 65 65 65 65 66 66 66 64 64 64 67 67 67 61 61 61 63 63 63 60 60 60 65 65 65 64 64 64 66 66 59 59 59 63 63 63 63 63 63 64 80.0 80.0 72.0 72.0 72.0 76.0 76.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 74.4 74.4 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 74.3 74.3 56.3 56.3 56.3 64.7 64.7 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 58.6 58.6 58.6 55.9 55.9 55.9 54.6 54.6 54.6 56.3 3,150 3,150 1,009 1,009 1,009 6,278 6,278 1,505 1,505 1,505 1,190 1,190 1,190 339 339 339 200 200 200 137 137 137 351 351 351 256 256 256 23 23 23 4,001 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 19,874 19,874 17,669 17,669 17,669 78,937 60,043 -636 -636 -636 10,111 10,111 10,111 -143 -143 -143 -85 -85 -85 -58 -58 -58 -148 -148 -148 -108 -108 -108 -10 -10 -10 8,923 0 25,370 25,370 25,370 30,201 30,201 30,201 29,008 29,008 29,008 37,550 668 668 1,173 1,173 1,173 5,877 7,430 -4,539 -4,539 -4,539 -971 -971 -971 2,691 2,691 2,691 1,039 1,039 1,039 306 306 306 -8,532 -8,532 -8,532 454 454 454 -45 -45 -45 -9,597 -3,178 2,062 2,062 2,062 2,910 2,910 2,910 3,573 3,573 3,573 3,013 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /17 7 /18 7 /18 9 /17 7 /14 7 /14 9 /16 9 /16 9 /16 9 /16 9 /10 9 /10 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 7 /17 9 /14 9 /14 9 /16 9 /16 9 /14 9 /14 9 /16 76 76 73 73 73 76 76 76 76 76 77 77 77 77 77 77 67 67 67 77 77 77 75 75 75 75 75 75 76 76 76 75 75 77 77 77 77 77 77 77 77 77 77 67 67 65 65 65 67 67 65 65 65 67 67 67 67 67 67 61 61 61 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 67 67 67 66 66 66 67 75.4 75.4 56.3 56.3 56.3 66.2 68.1 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 59.2 59.2 59.2 56.9 56.9 56.9 55.6 55.6 55.6 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 3,150 3,150 1,009 1,009 1,009 6,278 6,278 451 451 451 357 357 357 102 102 102 60 60 60 41 41 41 105 105 105 77 77 77 7 7 7 1,200 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 36,640 36,640 27,335 27,335 27,335 100,501 80,404 -191 -191 -191 3,033 3,033 3,033 -43 -43 -43 -25 -25 -25 -17 -17 -17 -44 -44 -44 -32 -32 -32 -3 -3 -3 12,882 0 36,547 36,547 36,547 44,525 44,525 44,525 40,050 40,050 40,050 54,574 Coil Latent Load Btu/h 8,557 8,557 2,160 2,160 2,160 30,607 29,879 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6,959 6,959 6,959 7,908 7,908 7,908 7,147 7,147 7,147 7,605 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 16 of 100 SPACE Floor Area ft² System Zone Room Zone - 267 Zone - 267 spc_sp_59 Zone - 268 Zone - 268 spc_sp_60 Zone - 269 Zone - 269 spc_sp_61 Zone - 270 Zone - 270 spc_sp_62 Zone - 271 Zone - 271 spc_sp_63 Zone - 272 Zone - 272 spc_sp_64 Zone - 273 Zone - 273 spc_sp_65 Zone - 274 Zone - 274 spc_sp_66 Zone - 275 Zone - 275 spc_sp_67 Zone - 276 Zone - 276 spc_sp_68 Zone - 277 Zone - 277 spc_sp_69 Zone - 278 Zone - 278 spc_sp_70 Zone - 279 Zone - 279 spc_sp_38 Zone - 280 Zone - 280 spc_sp_39 Zone - 281 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 1,087 1,087 396 396 396 828 828 828 378 378 378 485 485 485 678 678 678 822 822 822 628 628 628 2,082 2,082 2,082 2,169 2,169 2,169 2,777 2,777 2,777 3,084 3,084 3,084 211 211 211 818 818 818 818 818 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 11 /15 11 /15 7 /18 7 /18 9 /11 9 /11 6 /10 6 /10 10 /16 10 /16 7 /18 7 /18 9 /11 9 /11 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 6 /10 6 /10 9 /16 9 /16 9 /16 79 79 73 73 73 73 73 73 70 70 70 65 65 65 79 79 79 73 73 73 70 70 70 77 77 77 75 75 75 75 75 75 75 75 75 65 65 65 77 77 77 77 77 64 64 62 62 62 65 65 65 63 63 63 58 58 58 64 64 64 65 65 65 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.3 56.3 58.2 58.2 58.2 54.7 54.7 54.7 57.5 57.5 57.5 55.5 55.5 55.5 56.3 56.3 56.3 51.4 51.4 51.4 56.1 56.1 56.1 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.5 52.5 52.5 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 37,550 37,550 33,464 33,464 33,464 25,783 25,783 25,783 28,760 28,760 28,760 11,994 11,994 11,994 23,923 23,923 23,923 13,067 13,067 13,067 26,223 26,223 26,223 53,398 53,398 53,398 48,975 48,975 48,975 57,415 57,415 57,415 55,454 55,454 55,454 13,285 13,285 13,285 28,858 28,858 28,858 28,858 28,858 3,013 3,013 1,051 1,051 1,051 2,864 2,864 2,864 1,212 1,212 1,212 1,286 1,286 1,286 1,878 1,878 1,878 2,838 2,838 2,838 2,011 2,011 2,011 7,723 7,723 7,723 7,128 7,128 7,128 9,122 9,122 9,122 10,121 10,121 10,121 559 559 559 3,036 3,036 3,036 3,036 3,036 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /15 7 /18 7 /18 9 /11 9 /11 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 9 /12 9 /12 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /16 77 77 80 80 80 73 73 73 70 70 70 76 76 76 77 77 77 75 75 75 73 73 73 77 77 77 75 75 75 75 75 75 76 76 76 65 65 65 77 77 77 77 77 67 67 63 63 63 65 65 65 63 63 63 66 66 66 67 67 67 66 66 66 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 56.5 56.5 58.3 58.3 58.3 54.7 54.7 54.7 57.5 57.5 57.5 58.6 58.6 58.6 56.4 56.4 56.4 51.9 51.9 51.9 56.2 56.2 56.2 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.7 52.7 52.7 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 Coil Airflow cfm Coil Sensible Load Btu/h 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 54,574 54,574 40,936 40,936 40,936 38,829 38,829 38,829 32,826 32,826 32,826 16,489 16,489 16,489 33,562 33,562 33,562 23,710 23,710 23,710 32,978 32,978 32,978 80,411 80,411 80,411 79,136 79,136 79,136 95,193 95,193 95,193 95,526 95,526 95,526 14,677 14,677 14,677 41,068 41,068 41,068 41,068 41,068 Coil Latent Load Btu/h 7,605 7,605 1,195 1,195 1,195 5,336 5,336 5,336 1,973 1,973 1,973 3,057 3,057 3,057 4,742 4,742 4,742 5,052 5,052 5,052 3,012 3,012 3,012 14,541 14,541 14,541 13,382 13,382 13,382 17,116 17,116 17,116 19,369 19,369 19,369 694 694 694 5,720 5,720 5,720 5,720 5,720 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 17 of 100 SPACE Floor Area ft² System Zone Room Zone - 281 spc_sp_40 Zone - 282 Zone - 282 spc_sp_41 Zone - 283 Zone - 283 spc_sp_42 Zone - 284 Zone - 284 spc_sp_43 Zone - 285 Zone - 285 spc_sp_44 Zone - 286 Zone - 286 spc_sp_45 Zone - 287 Zone - 287 spc_sp_46 Zone - 288 Zone - 288 spc_sp_47 Zone - 289 Zone - 289 spc_sp_48 Zone - 290 Zone - 290 spc_sp_49 Zone - 291 Zone - 291 spc_sp_50 Zone - 292 Zone - 292 spc_sp_51 Zone - 293 Zone - 293 spc_sp_52 Zone - 294 Zone - 294 spc_sp_53 Zone - 295 Zone - 295 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 818 1,408 1,408 1,408 1,392 1,392 1,392 972 972 972 1,408 1,408 1,408 826 826 826 914 914 914 907 907 907 869 869 869 869 869 869 835 835 835 893 893 893 737 737 737 1,061 1,061 1,061 1,064 1,064 1,064 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 10 /15 10 /15 9 /16 9 /16 9/16 9 /16 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 10 /13 10 /13 10 /13 10 /13 77 77 77 77 77 77 77 77 77 77 80 80 80 77 77 77 77 77 77 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 77 77 77 77 77 77 67 67 67 67 67 67 67 67 67 67 63 63 63 67 67 67 67 67 67 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 59 59 59 59 59 59 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 54.0 54.0 56.0 56.0 56.0 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 53.9 53.9 53.9 54.1 54.1 54.1 54.2 54.2 54.2 54.0 54.0 54.0 55.0 55.0 55.0 58.7 58.7 58.7 58.7 58.7 58.7 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 28,858 35,056 35,056 35,056 34,765 34,765 34,765 27,232 27,232 27,232 38,302 38,302 38,302 27,994 27,994 27,994 26,885 26,885 26,885 25,235 25,235 25,235 22,064 22,064 22,064 22,983 22,983 22,983 22,536 22,536 22,536 23,576 23,576 23,576 24,944 24,944 24,944 24,323 24,323 24,323 24,374 24,374 24,374 3,036 5,223 5,223 5,223 5,163 5,163 5,163 3,608 3,608 3,608 3,626 3,626 3,626 3,067 3,067 3,067 3,393 3,393 3,393 3,140 3,140 3,140 3,008 3,008 3,008 3,009 3,009 3,009 2,891 2,891 2,891 3,092 3,092 3,092 2,553 2,553 2,553 1,935 1,935 1,935 1,941 1,941 1,941 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 9 /14 9 /14 9 /14 9 /14 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 77 77 77 77 77 77 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 54.0 54.0 56.2 56.2 56.2 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 54.1 54.1 54.1 54.2 54.2 54.2 54.3 54.3 54.3 54.2 54.2 54.2 55.0 55.0 55.0 59.2 59.2 59.2 59.2 59.2 59.2 Coil Airflow cfm Coil Sensible Load Btu/h 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 41,068 53,076 53,076 53,076 52,584 52,584 52,584 39,863 39,863 39,863 56,744 56,744 56,744 39,442 39,442 39,442 38,892 38,892 38,892 38,103 38,103 38,103 33,592 33,592 33,592 34,897 34,897 34,897 34,003 34,003 34,003 35,816 35,816 35,816 36,470 36,470 36,470 34,741 34,741 34,741 34,831 34,831 34,831 Coil Latent Load Btu/h 5,720 9,832 9,832 9,832 9,719 9,719 9,719 6,796 6,796 6,796 9,854 9,854 9,854 5,777 5,777 5,777 6,391 6,391 6,391 5,604 5,604 5,604 5,367 5,367 5,367 5,370 5,370 5,370 5,157 5,157 5,157 5,519 5,519 5,519 4,557 4,557 4,557 6,531 6,531 6,531 6,553 6,553 6,553 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 18 of 100 SPACE Floor Area ft² System Zone Room spc_sp_54 Zone - 296 Zone - 296 spc_sp_22 Zone - 297 Zone - 297 spc_sp_23 Zone - 298 Zone - 298 spc_sp_24 Zone - 299 Zone - 299 spc_sp_25 Zone - 300 Zone - 300 spc_sp_26 Zone - 301 Zone - 301 spc_sp_27 Zone - 302 Zone - 302 spc_sp_28 Zone - 303 Zone - 303 spc_sp_29 Zone - 304 Zone - 304 spc_sp_30 Zone - 305 Zone - 305 spc_sp_31 Zone - 306 Zone - 306 spc_sp_32 Zone - 307 Zone - 307 spc_sp_33 Zone - 308 Zone - 308 spc_sp_34 Zone - 309 Zone - 309 spc_sp_35 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 1,061 9 /12 1,061 1,061 9 /12 1,044 7 /18 1,044 1,044 7 /18 1,082 7 /18 1,082 1,082 7 /18 1,074 7 /18 1,074 1,074 7 /18 955 7 /18 955 955 7 /18 995 9 /16 995 995 9 /16 894 7 /17 894 894 7 /17 1,063 10 /15 1,063 1,063 10 /15 684 6 /10 684 684 6 /10 2,070 9 /16 2,070 2,070 9 /16 1,251 9 /16 1,251 1,251 9 /16 1,251 7 /17 1,251 1,251 7 /17 1,525 9 /16 1,525 1,525 9 /16 818 9 /16 818 818 9 /16 818 9 /16 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 77 77 77 75 75 75 80 80 80 65 65 65 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 63 63 63 65 65 65 65 65 65 65 65 65 65 65 65 67 67 67 66 66 66 63 63 63 58 58 58 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.7 54.7 54.7 53.1 53.1 53.1 53.4 53.4 53.4 53.1 53.1 53.1 53.6 53.6 53.6 55.1 55.1 55.1 55.0 55.0 55.0 56.6 56.6 56.6 55.8 55.8 55.8 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 27,301 27,301 27,301 22,248 22,248 22,248 24,586 24,586 24,586 22,945 22,945 22,945 22,834 22,834 22,834 37,026 37,026 37,026 29,118 29,118 29,118 36,090 36,090 36,090 18,202 18,202 18,202 52,942 52,942 52,942 35,189 35,189 35,189 31,103 31,103 31,103 60,677 60,677 60,677 29,082 29,082 29,082 28,858 3,272 3,272 3,272 3,609 3,609 3,609 3,741 3,741 3,741 3,711 3,711 3,711 3,304 3,304 3,304 3,697 3,697 3,697 2,943 2,943 2,943 2,737 2,737 2,737 1,813 1,813 1,813 7,679 7,679 7,679 4,645 4,645 4,645 4,115 4,115 4,115 5,660 5,660 5,660 3,036 3,036 3,036 3,036 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /14 9 /14 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 9 /16 77 77 77 75 75 75 75 75 75 75 75 75 75 75 75 77 77 77 75 75 75 77 77 77 76 76 76 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 55.7 55.7 55.7 53.6 53.6 53.6 53.6 53.6 53.6 53.6 53.6 53.6 53.9 53.9 53.9 55.1 55.1 55.1 55.0 55.0 55.0 56.7 56.7 56.7 60.6 60.6 60.6 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 Coil Airflow cfm Coil Sensible Load Btu/h 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 37,314 37,314 37,314 35,254 35,254 35,254 38,640 38,640 38,640 36,369 36,369 36,369 35,270 35,270 35,270 51,628 51,628 51,628 42,996 42,996 42,996 51,414 51,414 51,414 22,226 22,226 22,226 79,873 79,873 79,873 52,725 52,725 52,725 48,027 48,027 48,027 82,120 82,120 82,120 41,372 41,372 41,372 41,068 Coil Latent Load Btu/h 6,544 6,544 6,544 6,433 6,433 6,433 6,671 6,671 6,671 6,615 6,615 6,615 5,894 5,894 5,894 6,966 6,966 6,966 5,530 5,530 5,530 7,439 7,439 7,439 4,311 4,311 4,311 14,458 14,458 14,458 8,749 8,749 8,749 7,730 7,730 7,730 10,664 10,664 10,664 5,720 5,720 5,720 5,720 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 19 of 100 SPACE Floor Area ft² System Zone Room Zone - 310 Zone - 310 spc_sp_36 Zone - 311 Zone - 311 spc_sp_37 Zone - 312 Zone - 312 spc_sp_7 Zone - 313 Zone - 313 spc_sp_8 Zone - 314 Zone - 314 spc_sp_9 Zone - 315 Zone - 315 spc_sp_10 Zone - 316 Zone - 316 spc_sp_11 Zone - 317 Zone - 317 spc_sp_12 Zone - 318 Zone - 318 spc_sp_13 Zone - 319 Zone - 319 spc_sp_14 Zone - 320 Zone - 320 spc_sp_15 Zone - 321 Zone - 321 spc_sp_16 Zone - 322 Zone - 322 spc_sp_17 Zone - 323 Zone - 323 spc_sp_18 Zone - 324 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 818 818 818 818 818 818 818 818 290 290 290 442 442 442 2,070 2,070 2,070 1,103 1,103 1,103 915 915 915 3,084 3,084 3,084 437 437 437 344 344 344 231 231 231 382 382 382 358 358 358 1,082 1,082 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /11 9 /11 6 /18 6 /18 7 /17 7/17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 6 /18 6 /18 7 /18 7 /18 9 /12 9 /12 6 /10 6 /10 6 /9 6 /9 7 /18 77 77 77 77 77 77 77 77 70 70 70 70 70 70 75 75 75 76 76 76 76 76 76 75 75 75 70 70 70 73 73 73 73 73 73 65 65 65 62 62 62 73 73 67 67 67 67 67 67 67 67 63 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 65 65 65 63 63 63 58 58 58 58 58 58 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 57.0 57.0 57.0 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 56.2 56.2 56.2 56.0 56.0 56.0 53.0 53.0 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 17,557 17,557 17,557 19,208 19,208 19,208 47,533 47,533 47,533 12,788 12,788 12,788 10,607 10,607 10,607 60,225 60,225 60,225 28,451 28,451 28,451 19,387 19,387 19,387 8,323 8,323 8,323 11,887 11,887 11,887 10,175 10,175 10,175 22,813 22,813 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 929 929 929 1,375 1,375 1,375 6,804 6,804 6,804 3,865 3,865 3,865 3,206 3,206 3,206 10,127 10,127 10,127 1,358 1,358 1,358 1,192 1,192 1,192 713 713 713 1,013 1,013 1,013 951 951 951 3,739 3,739 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /12 9 /12 7 /18 7 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /12 9 /12 7 /15 7 /15 7 /16 7 /16 7 /17 77 77 77 77 77 77 77 77 73 73 73 73 73 73 75 75 75 76 76 76 76 76 76 75 75 75 73 73 73 73 73 73 73 73 73 77 77 77 76 76 76 75 75 67 67 67 67 67 67 67 67 63 63 63 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 63 63 63 66 66 66 66 66 66 66 66 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 57.6 57.6 57.6 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 60.1 60.1 60.1 57.9 57.9 57.9 53.5 53.5 Coil Airflow cfm Coil Sensible Load Btu/h 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 20,529 20,529 20,529 26,244 26,244 26,244 76,434 76,434 76,434 26,279 26,279 26,279 21,797 21,797 21,797 101,628 101,628 101,628 36,070 36,070 36,070 25,678 25,678 25,678 11,070 11,070 11,070 14,327 14,327 14,327 14,201 14,201 14,201 36,302 36,302 Coil Latent Load Btu/h 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 1,393 1,393 1,393 2,856 2,856 2,856 12,774 12,774 12,774 6,912 6,912 6,912 5,733 5,733 5,733 18,995 18,995 18,995 2,820 2,820 2,820 2,221 2,221 2,221 1,110 1,110 1,110 2,357 2,357 2,357 2,261 2,261 2,261 6,665 6,665 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 20 of 100 SPACE Floor Area ft² System Zone Room Zone - 324 spc_sp_19 Zone - 325 Zone - 325 spc_sp_20 Zone - 326 Zone - 326 spc_sp_21 Zone - 327 Zone - 327 spc_sp_1 Zone - 328 Zone - 328 spc_sp_2 Zone - 329 Zone - 329 spc_sp_3 Zone - 330 Zone - 330 spc_sp_4 Zone - 331 Zone - 331 spc_sp_5 Zone - 332 Zone - 332 spc_sp_6 Zone - 333 Zone - 333 Child Cntr 2 Zone - 359 Zone - 359 Child Cntr 3 Zone - 360 Zone - 360 Child Cntr 1 Zone - 361 Zone - 361 Portopia HP Portopia HP spc_SS 141/142 Office_0 Zone - 012 Zone - 012 spc_SS 144 Office C_0 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak 1,082 960 960 960 1,040 1,040 1,040 1,040 1,040 1,040 1,272 1,272 1,272 1,074 1,074 1,074 999 999 999 1,613 1,613 1,613 664 664 664 1,956 1,956 1,956 211 211 211 211 211 211 211 211 211 75,038 75,038 313 313 313 168 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 9 /16 9 /16 7 /18 7 /18 7/18 7 /18 10 /15 10 /15 10 /16 10 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 73 73 73 73 73 73 73 73 73 73 77 77 77 73 73 73 73 73 73 80 80 80 79 79 79 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 65 65 65 65 65 65 65 65 65 65 67 67 67 65 65 65 65 65 65 63 63 63 64 64 64 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Supply Dry Bulb °F 53.0 53.2 53.2 53.2 54.2 54.2 54.2 53.1 53.1 53.1 48.6 48.6 48.6 53.1 53.1 53.1 54.3 54.3 54.3 55.5 55.5 55.5 57.1 57.1 57.1 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 54.9 54.9 72.0 72.0 72.0 72.0 Space Air Flow cfm COIL Space Sensible Load Btu/h Space Latent Load Btu/h 1,079 22,813 1,002 20,987 1,002 20,987 1,002 20,987 1,451 28,726 1,451 28,726 1,451 28,726 1,053 22,182 1,053 22,182 1,053 22,182 600 15,648 600 15,648 600 15,648 1,089 22,945 1,089 22,945 1,089 22,945 1,420 28,019 1,420 28,019 1,420 28,019 2,033 37,433 2,033 37,433 2,033 37,433 1,915 31,843 1,915 31,843 1,915 31,843 871 22,688 871 22,688 871 22,688 837 13,285 837 13,285 837 13,285 837 13,285 837 13,285 837 13,285 849 12,931 849 12,931 849 12,931 106,096 2,026,697 106,096 1,809,600 81 0 81 0 81 0 32 0 3,739 3,318 3,318 3,318 3,598 3,598 3,598 3,594 3,594 3,594 4,707 4,707 4,707 3,711 3,711 3,711 3,457 3,457 3,457 4,151 4,151 4,151 1,840 1,840 1,840 6,857 6,857 6,857 559 559 559 559 559 559 370 370 370 246,137 246,507 181 181 181 97 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 75 75 75 75 75 75 75 75 75 75 76 76 76 75 75 75 75 75 75 77 77 77 77 77 77 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 53.5 53.7 53.7 53.7 54.4 54.4 54.4 53.6 53.6 53.6 48.8 48.8 48.8 53.6 53.6 53.6 54.5 54.5 54.5 56.4 56.4 56.4 57.3 57.3 57.3 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 55.1 56.7 72.0 72.0 72.0 72.0 Coil Airflow cfm Coil Sensible Load Btu/h 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 36,302 32,911 32,911 32,911 43,793 43,793 43,793 35,131 35,131 35,131 31,358 31,358 31,358 36,369 36,369 36,369 42,495 42,495 42,495 56,782 56,782 56,782 43,282 43,282 43,282 46,620 46,620 46,620 14,677 14,677 14,677 14,677 14,677 14,677 14,524 14,524 14,524 3,006,774 2,862,181 0 0 0 0 Coil Latent Load Btu/h 6,665 5,915 5,915 5,915 6,420 6,420 6,420 6,406 6,406 6,406 7,970 7,970 7,970 6,615 6,615 6,615 6,169 6,169 6,169 11,281 11,281 11,281 4,645 4,645 4,645 12,262 12,262 12,262 694 694 694 694 694 694 460 460 460 480,065 462,701 0 0 0 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 21 of 100 SPACE Floor Area ft² System Zone Room Zone - 013 Zone - 013 spc_SS 160B-D_0 Zone - 014 Zone - 014 spc_PS 160A Storage_0 Zone - 015 Zone - 015 spc_SS 160 Class C_0 Zone - 016 Zone - 016 spc_SS 162 Class_0 Zone - 017 Zone - 017 spc_PS 112 Office C_0 Zone - 018 Zone - 018 spc_PS 111-115 Office C_0 Zone - 019 Zone - 019 spc_PS Lecture 117 C_0 Zone - 020 Zone - 020 spc_PS Lecture FC-4C_0 Zone - 021 Zone - 021 spc_PS 120-128 Class_0 Zone - 022 Zone - 022 spc_PS Class 121/122_0 Zone - 023 Zone - 023 spc_PS 130 Auditorium C_0 Zone - 024 Zone - 024 PS Fan Coil Htg Only PS Fan Coil Htg Only spc_SS 171-173, 178 Office C_0 Zone - 037 Zone - 037 spc_SS 135 Office_0 Zone - 038 Zone - 038 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block 168 168 0 0 0 102 102 102 565 565 565 967 967 967 215 215 215 602 602 602 1,126 1,126 1,126 1,036 1,036 1,036 886 886 886 695 695 695 1,413 1,413 1,413 8,090 8,090 561 561 561 92 92 92 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /9 10 /15 10 /15 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 10 /16 10 /16 9 /17 9 /17 7 /18 7 /18 6 /9 6 /9 7 /16 7 /16 10 /16 10 /16 10 /16 7 /16 7 /16 7 /16 7 /16 62 62 80 80 80 70 70 70 70 70 70 70 70 70 79 79 79 79 79 79 76 76 76 73 73 73 62 62 62 76 76 76 79 79 79 79 79 76 76 76 76 76 76 58 58 63 63 63 63 63 63 63 63 63 63 63 63 64 64 64 64 64 64 67 67 67 65 65 65 58 58 58 66 66 66 64 64 64 64 64 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 32 32 0 0 0 27 27 27 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 274 274 274 45 45 45 Space Sensible Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,317 5,317 5,317 875 875 875 Space Latent Load Btu/h 97 97 0 0 0 -2 -2 -2 836 836 836 1,430 1,430 1,430 157 157 157 435 435 435 1,356 1,356 1,356 1,374 1,374 1,374 1,392 1,392 1,392 992 992 992 2,191 2,191 2,191 10,439 7,971 1,465 1,465 1,465 241 241 241 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 6 /9 9 /16 9 /16 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 7 /18 7 /18 7 /9 7 /9 7 /16 7 /16 9 /16 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 62 62 77 77 77 70 70 70 70 70 70 70 70 70 79 79 79 76 76 76 76 76 76 73 73 73 64 64 64 76 76 76 77 77 77 77 77 76 76 76 76 76 76 58 58 67 67 67 63 63 63 63 63 63 63 63 63 64 64 64 67 67 67 67 67 67 65 65 65 59 59 59 66 66 66 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm 32 32 0 0 0 27 27 27 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 268 268 268 44 44 44 Coil Sensible Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,089 5,089 5,089 838 838 838 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2,917 2,917 2,917 480 480 480 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 22 of 100 SPACE System Zone Room spc_SS Corridor 120 C_0 Peak Zone - 039 Peak Zone - 039 Block spc_SS 180 Worm Rm VAV-20_0 Peak Zone - 040 Peak Zone - 040 Block spc_SS 110C Wrk Rm C_0 Peak Zone - 041 Peak Zone - 041 Block spc_SS 110 Wrk Rm/Office C_0 Peak Zone - 042 Peak Zone - 042 Block Peak spc_SS 100 100H 111H Main Lobby C_0 Zone - 043 Peak Zone - 043 Block spc_SS 150 Wrk Rm C_0 Peak Zone - 044 Peak Zone - 044 Block spc_SS 177-179 Office_0 Peak Zone - 045 Peak Zone - 045 Block spc_SS Wrk Rm1 V-19_0 Peak Zone - 046 Peak Zone - 046 Block spc_SS 120-124 C_0 Peak Zone - 047 Peak Zone - 047 Block spc_SS 135-139 Office C_0 Peak Zone - 048 Peak Zone - 048 Block spc_SS 140 Wrk Rm C_0 Peak Zone - 049 Peak Zone - 049 Block spc_SS 125-129_0 Peak Zone - 050 Peak Zone - 050 Block spc_SS 230B Office C_0 Peak Zone - 051 Peak Zone - 051 Block spc_SS 214 Office C_0 Peak Zone - 052 Peak Zone - 052 Block spc_SS 282 Wrk Rm C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 1,787 1,787 1,787 326 326 326 766 766 766 1,420 1,420 1,420 37 37 37 301 301 301 635 635 635 207 207 207 703 703 703 586 586 586 848 848 848 642 642 642 285 285 285 130 130 130 136 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 10 /16 10 /16 6 /9 6 /9 9 /17 9 /17 7 /18 7 /18 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 6 /9 6 /9 7 /16 7 /16 9 /16 9 /16 6 /18 6 /18 6 /18 6 /18 10 /16 10 /16 10 /16 76 76 76 79 79 79 62 62 62 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 62 62 62 76 76 76 77 77 77 70 70 70 70 70 70 79 79 79 79 66 66 66 64 64 64 58 58 58 67 67 67 65 65 65 66 66 66 66 66 66 66 66 66 58 58 58 66 66 66 67 67 67 63 63 63 63 63 63 64 64 64 64 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 378 378 378 616 616 616 1,984 1,984 1,984 844 844 844 348 348 348 167 167 167 310 310 310 115 115 115 1,253 1,253 1,253 286 286 286 545 545 545 1,766 1,766 1,766 526 526 526 623 623 623 1,441 7,342 7,342 7,342 11,961 11,961 11,961 38,530 38,530 38,530 16,389 16,389 16,389 6,755 6,755 6,755 3,248 3,248 3,248 6,019 6,019 6,019 2,238 2,238 2,238 24,336 24,336 24,336 5,555 5,555 5,555 10,576 10,576 10,576 34,294 34,294 34,294 10,214 10,214 10,214 12,096 12,096 12,096 27,981 2,794 2,794 2,794 902 902 902 2,030 2,030 2,030 4,101 4,101 4,101 63 63 63 1,044 1,044 1,044 1,658 1,658 1,658 719 719 719 1,862 1,862 1,862 1,530 1,530 1,530 3,146 3,146 3,146 1,992 1,992 1,992 572 572 572 244 244 244 378 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 7 /10 7 /10 9 /17 9 /17 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /10 7 /10 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 9 /16 9 /16 9 /16 77 77 77 77 77 77 67 67 67 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 67 67 67 76 76 76 77 77 77 73 73 73 73 73 73 77 77 77 77 67 67 67 67 67 67 60 60 60 67 67 67 65 65 65 67 67 67 67 67 67 67 67 67 60 60 60 67 67 67 67 67 67 65 65 65 65 65 65 67 67 67 67 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 364 364 364 593 593 593 1,874 1,874 1,874 844 844 844 348 348 348 165 165 165 304 304 304 114 114 114 1,181 1,181 1,181 280 280 280 545 545 545 1,745 1,745 1,745 522 522 522 610 610 610 1,360 5,425 5,425 5,425 13,863 13,863 13,863 40,338 40,338 40,338 16,959 16,959 16,959 8,572 8,572 8,572 3,134 3,134 3,134 5,761 5,761 5,761 2,159 2,159 2,159 25,288 25,288 25,288 5,317 5,317 5,317 10,803 10,803 10,803 37,007 37,007 37,007 11,167 11,167 11,167 14,956 14,956 14,956 32,179 Coil Latent Load Btu/h 4,022 4,022 4,022 2,276 2,276 2,276 2,929 2,929 2,929 7,387 7,387 7,387 90 90 90 2,099 2,099 2,099 3,302 3,302 3,302 1,446 1,446 1,446 2,687 2,687 2,687 3,047 3,047 3,047 5,923 5,923 5,923 4,132 4,132 4,132 1,239 1,239 1,239 651 651 651 953 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 23 of 100 SPACE Floor Area ft² System Zone Room Zone - 053 Zone - 053 spc_SS 280D Office_0 Zone - 054 Zone - 054 spc_SS 280A-C C_0 Zone - 055 Zone - 055 spc_SS 272 Wrk Rm C_0 Zone - 056 Zone - 056 spc_SS 270C/D Office_0 Zone - 057 Zone - 057 spc_SS 111H Hall_0 Zone - 058 Zone - 058 spc_SS 110G/H Offices C_0 Zone - 059 Zone - 059 spc_SS 111A Office C_0 Zone - 060 Zone - 060 spc_SS 242 Wrk Rm C_0 Zone - 061 Zone - 061 spc_SS 240L Office C_0 Zone - 062 Zone - 062 spc_SS 240H Office_0 Zone - 063 Zone - 063 spc_SS 240F/J Office_0 Zone - 064 Zone - 064 spc_SS 240-260A Wrk Rm C_0 Zone - 065 Zone - 065 spc_SS 202/250B Office_0 Zone - 066 Zone - 066 spc_SS 250 Wrk Rm C_0 Zone - 067 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 136 136 154 154 154 459 459 459 778 778 778 287 287 287 397 397 397 269 269 269 216 216 216 642 642 642 149 149 149 181 181 181 274 274 274 865 865 865 214 214 214 0 0 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 7 /17 7 /17 9 /11 9 /11 9 /11 9 /11 9 /12 9 /12 7 /18 7/18 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 10 /16 10 /16 7 /16 7 /16 6 /9 79 79 75 75 75 70 70 70 70 70 70 73 73 73 73 73 73 76 76 76 76 76 76 79 79 79 75 75 75 76 76 76 75 75 75 79 79 79 76 76 76 62 62 64 64 66 66 66 63 63 63 63 63 63 63 63 63 65 65 65 66 66 66 66 66 66 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 66 66 66 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,441 1,441 75 75 75 1,255 1,255 1,255 1,090 1,090 1,090 379 379 379 175 175 175 131 131 131 105 105 105 406 406 406 73 73 73 89 89 89 133 133 133 1,257 1,257 1,257 104 104 104 16 16 27,981 27,981 1,450 1,450 1,450 24,365 24,365 24,365 21,179 21,179 21,179 7,364 7,364 7,364 3,399 3,399 3,399 2,552 2,552 2,552 2,048 2,048 2,048 7,890 7,890 7,890 1,410 1,410 1,410 1,719 1,719 1,719 2,589 2,589 2,589 24,416 24,416 24,416 2,028 2,028 2,028 304 304 378 378 408 408 408 1,469 1,469 1,469 2,489 2,489 2,489 627 627 627 612 612 612 703 703 703 564 564 564 1,777 1,777 1,777 397 397 397 474 474 474 728 728 728 2,394 2,394 2,394 559 559 559 0 0 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 7 /17 7 /17 9 /11 9 /11 9 /13 9 /13 9 /13 9 /13 7 /18 7 /18 9 /17 9 /17 9 /17 9 /17 7 /16 7 /16 7 /17 7 /17 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 9 /17 9 /17 7 /10 77 77 75 75 75 70 70 70 75 75 75 75 75 75 73 73 73 76 76 76 76 76 76 76 76 76 75 75 75 76 76 76 75 75 75 77 77 77 76 76 76 67 67 67 67 66 66 66 63 63 63 65 65 65 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 60 60 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,360 1,360 75 75 75 1,255 1,255 1,255 918 918 918 357 357 357 175 175 175 129 129 129 103 103 103 394 394 394 73 73 73 87 87 87 133 133 133 1,221 1,221 1,221 102 102 102 15 15 32,179 32,179 3,723 3,723 3,723 28,088 28,088 28,088 25,380 25,380 25,380 10,543 10,543 10,543 3,469 3,469 3,469 2,443 2,443 2,443 1,960 1,960 1,960 17,212 17,212 17,212 3,620 3,620 3,620 1,646 1,646 1,646 6,646 6,646 6,646 38,964 38,964 38,964 1,941 1,941 1,941 312 312 Coil Latent Load Btu/h 953 953 703 703 703 2,386 2,386 2,386 4,471 4,471 4,471 973 973 973 790 790 790 1,400 1,400 1,400 1,123 1,123 1,123 4,042 4,042 4,042 684 684 684 943 943 943 1,256 1,256 1,256 6,040 6,040 6,040 1,112 1,112 1,112 0 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 24 of 100 SPACE System Zone Room Zone - 067 Block spc_SS 251 Wrk Rm C_0 Peak Zone - 068 Peak Zone - 068 Block Peak spc_SS 230H, 200-201, 251H, 272H_0 Zone - 069 Peak Zone - 069 Block spc_SS 210/211 Wrk Rm C_0 Peak Zone - 070 Peak Zone - 070 Block spc_SS 230F Office C_0 Peak Zone - 071 Peak Zone - 071 Block spc_SS Wrk Rm 230 C_0 Peak Zone - 072 Peak Zone - 072 Block spc_SS 230C-E Office_0 Peak Zone - 073 Peak Zone - 073 Block spc_SS 240B Wrk Rm C_0 Peak Zone - 074 Peak Zone - 074 Block spc_SS 181 Comp Rm C_0 Peak Zone - 075 Peak Zone - 075 Block spc_SS 182 Comp Rm C_0 Peak Zone - 076 Peak Zone - 076 Block Stdnt Srv VAV Peak Stdnt Srv VAV Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 0 6 /9 388 9 /12 388 388 9 /12 4,383 7 /16 4,383 4,383 7 /16 308 7 /15 308 308 7 /15 180 6 /18 180 180 6 /18 987 7 /16 987 987 7 /16 630 6/18 630 630 6 /18 240 10 /16 240 240 10 /16 854 7 /18 854 854 7 /18 863 9 /11 863 863 9 /11 23,178 23,178 7 /17 62 73 73 73 76 76 76 77 77 77 70 70 70 76 76 76 70 70 70 79 79 79 73 73 73 70 70 70 75 75 58 63 63 63 66 66 66 66 66 66 63 63 63 66 66 66 63 63 63 64 64 64 65 65 65 63 63 63 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 16 387 387 387 2,716 2,716 2,716 171 171 171 330 330 330 550 550 550 1,887 1,887 1,887 607 607 607 2,223 2,223 2,223 2,317 2,317 2,317 27,996 21,892 304 7,518 7,518 7,518 52,749 52,749 52,749 3,325 3,325 3,325 6,408 6,408 6,408 10,680 10,680 10,680 36,641 36,641 36,641 11,782 11,782 11,782 43,184 43,184 43,184 45,011 45,011 45,011 543,738 425,196 0 1,195 1,195 1,195 15,399 15,399 15,399 1,069 1,069 1,069 360 360 360 3,468 3,468 3,468 1,262 1,262 1,262 663 663 663 2,471 2,471 2,471 2,243 2,243 2,243 66,071 67,555 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /10 9 /12 9 /12 7 /16 7 /16 7 /16 7 /16 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 7 /18 7 /18 9 /11 9 /11 7 /17 67 73 73 73 76 76 76 76 76 76 73 73 73 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 75 75 60 63 63 63 66 66 66 66 66 66 65 65 65 66 66 66 65 65 65 67 67 67 65 65 65 63 63 63 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 15 387 387 387 2,716 2,716 2,716 171 171 171 326 326 326 550 550 550 1,854 1,854 1,854 595 595 595 2,223 2,223 2,223 2,317 2,317 2,317 27,337 21,892 312 8,858 8,858 8,858 113,463 113,463 113,463 7,815 7,815 7,815 9,430 9,430 9,430 25,113 25,113 25,113 48,827 48,827 48,827 15,938 15,938 15,938 45,640 45,640 45,640 49,534 49,534 49,534 713,169 592,652 0 1,856 1,856 1,856 27,598 27,598 27,598 1,937 1,937 1,937 781 781 781 6,215 6,215 6,215 2,736 2,736 2,736 1,674 1,674 1,674 4,381 4,381 4,381 3,536 3,536 3,536 122,218 121,687 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 25 of 100 SPACE Floor Area ft² System Zone Room OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 58.1 58.1 58.1 51.6 51.6 51.6 55.0 55.0 55.0 56.7 56.7 56.7 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.8 57.8 57.8 52.5 52.5 52.5 69.6 69.6 69.6 57.6 57.6 54.7 54.7 54.7 54.6 54.6 54.6 49.8 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 19,718 19,718 19,718 27,717 27,717 27,717 4,324 4,324 4,324 8,470 8,470 8,470 10,677 10,677 10,677 33,208 33,208 33,208 3,217 3,217 3,217 2,438 2,438 2,438 46,648 46,648 46,648 8,293 8,293 8,293 13,658 13,658 13,658 178,368 160,203 45,748 45,748 45,748 34,617 34,617 34,617 7,681 649 649 649 6,690 6,690 6,690 0 0 0 601 601 601 686 686 686 2,099 2,099 2,099 935 935 935 708 708 708 1,884 1,884 1,884 1,710 1,710 1,710 -741 -741 -741 15,221 21,247 6,031 6,031 6,031 4,790 4,790 4,790 2,079 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F Coil Airflow cfm Coil Sensible Load Btu/h 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 21,552 21,552 21,552 27,487 27,487 27,487 4,459 4,459 4,459 10,580 10,580 10,580 12,077 12,077 12,077 35,790 35,790 35,790 8,578 8,578 8,578 6,500 6,500 6,500 64,856 64,856 64,856 8,454 8,454 8,454 27,101 27,101 27,101 227,433 211,887 48,957 48,957 48,957 37,048 37,048 37,048 18,754 Coil Latent Load Btu/h Alternative 2 spc_A 121 Office UC_0 Zone - 077 Zone - 077 spc_A 130A Class? FC1-4_0 Zone - 078 Zone - 078 spc_A 237-241 Office C_0 Zone - 093 Zone - 093 spc_A 202A Office D_0 Zone - 094 Zone - 094 spc_A 202A Office B_0 Zone - 095 Zone - 095 spc_A 202A Office C_0 Zone - 096 Zone - 096 spc_A 201 Office C_0 Zone - 097 Zone - 097 spc_A 200H-J Office C_0 Zone - 098 Zone - 098 spc_A 200 Office C_0 Zone - 099 Zone - 099 spc_A 210A-B Stairs C_0 Zone - 100 Zone - 100 spc_A 121 Restroom FC05_0 Zone - 118 Zone - 118 Admin FC Admin FC spc_A 161/162 Class C_0 Zone - 091 Zone - 091 spc_A 160 Wrk Rm C_0 Zone - 092 Zone - 092 spc_A 236A/B Offices_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak 348 348 348 2,606 2,606 2,606 0 0 0 344 344 344 238 238 238 891 891 891 353 353 353 267 267 267 1,011 1,011 1,011 1,111 1,111 1,111 734 734 734 7,905 7,905 2,273 2,273 2,273 1,806 1,806 1,806 786 10 /16 10 /16 10 /15 10 /15 7 /16 7 /16 6 /10 6 /10 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 7 /18 7 /18 10 /16 10 /16 9 /16 6 /9 6 /9 6 /9 6 /9 7 /17 79 79 79 80 80 80 76 76 76 65 65 65 76 76 76 73 73 73 75 75 75 75 75 75 79 79 79 73 73 73 79 79 79 77 77 62 62 62 62 62 62 75 64 64 64 63 63 63 66 66 66 58 58 58 67 67 67 65 65 65 66 66 66 66 66 66 64 64 64 65 65 65 64 64 64 67 67 58 58 58 58 58 58 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 9 /16 7 /9 7 /9 7 /9 7 /9 7 /17 77 77 77 77 77 77 76 76 76 76 76 76 76 76 76 73 73 73 75 75 75 75 75 75 77 77 77 73 73 73 77 77 77 77 77 64 64 64 64 64 64 75 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 65 65 65 66 66 66 66 66 66 67 67 67 65 65 65 67 67 67 67 67 59 59 59 59 59 59 66 58.4 58.4 58.4 51.8 51.8 51.8 55.0 55.0 55.0 63.1 63.1 63.1 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.9 57.9 57.9 52.5 52.5 52.5 69.8 69.8 69.8 58.0 59.2 55.1 55.1 55.1 54.9 54.9 54.9 49.8 1,735 1,735 1,735 18,165 18,165 18,165 0 0 0 1,536 1,536 1,536 1,234 1,234 1,234 3,864 3,864 3,864 1,611 1,611 1,611 1,221 1,221 1,221 5,037 5,037 5,037 2,205 2,205 2,205 -7,656 -7,656 -7,656 28,952 30,207 9,347 9,347 9,347 7,420 7,420 7,420 3,579 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 26 of 100 SPACE Floor Area ft² System Zone Room Zone - 113 Zone - 113 spc_A 244/246 Office C_0 Zone - 114 Zone - 114 spc_A 242/243 Class C_0 Zone - 115 Zone - 115 spc_A 238-246 Offices C_0 Zone - 116 Zone - 116 spc_A 216/218 Office C_0 Zone - 117 Zone - 117 Admin Pckg AHU Admin Pckg AHU spc_A 277F Class_0 Zone - 079 Zone - 079 spc_A 279A Hall C_0 Zone - 080 Zone - 080 spc_A 278A Cond Stair_0 Zone - 081 Zone - 081 spc_A 170/171 Lobby C_0 Zone - 082 Zone - 082 spc_A 172 Wrk Rm C_0 Zone - 083 Zone - 083 spc_A Wrk Rm 173 C_0 Zone - 084 Zone - 084 spc_A 177 Comp C_1 Zone - 085 Zone - 085 spc_A 174-176 Data C_0 Zone - 086 Zone - 086 spc_A 177 Comp C_0 Zone - 087 Zone - 087 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 786 786 367 367 367 1,839 1,839 1,839 2,547 2,547 2,547 2,057 2,057 2,057 11,676 11,676 1,395 1,395 1,395 7,584 7,584 7,584 321 321 321 1,279 1,279 1,279 2,002 2,002 2,002 671 671 671 626 626 626 201 201 201 626 626 626 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 10 /16 10 /16 6 /10 6 /10 7 /17 7 /17 6 /10 6/18 6 /18 6 /10 6 /10 9 /11 9 /11 7 /18 7 /18 6 /9 6 /9 10 /15 10 /15 6 /9 6 /9 9 /16 9 /16 7 /16 7 /16 75 75 75 75 75 79 79 79 65 65 65 75 75 75 65 65 70 70 70 65 65 65 70 70 70 73 73 73 62 62 62 80 80 80 62 62 62 77 77 77 76 76 76 66 66 66 66 66 64 64 64 58 58 58 66 66 66 58 58 63 63 63 58 58 58 63 63 63 65 65 65 58 58 58 63 63 63 58 58 58 67 67 67 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 70.0 70.0 70.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.8 49.8 49.8 49.8 49.8 55.5 55.5 55.5 57.3 57.3 57.3 49.8 49.8 49.8 55.4 55.4 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,510 2,510 2,510 5,680 5,680 5,680 1,443 1,443 1,443 483 483 483 2,570 2,570 2,570 1,214 1,214 1,214 1,490 1,490 1,490 1,917 1,917 1,917 1,042 1,042 1,042 7,681 7,681 3,589 3,589 3,589 49,570 49,570 49,570 81,320 81,320 81,320 20,104 20,104 20,104 242,629 193,483 46,615 46,615 46,615 105,509 105,509 105,509 26,795 26,795 26,795 8,969 8,969 8,969 47,731 47,731 47,731 22,553 22,553 22,553 27,671 27,671 27,671 31,338 31,338 31,338 19,354 19,354 19,354 2,079 2,079 971 971 971 5,095 5,095 5,095 4,472 4,472 4,472 5,442 5,442 5,442 28,881 25,762 4,376 4,376 4,376 5,555 5,555 5,555 411 411 411 2,208 2,208 2,208 5,370 5,370 5,370 1,747 1,747 1,747 1,303 1,303 1,303 497 497 497 1,843 1,843 1,843 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 7 /17 7 /17 7 /16 7 /18 7 /18 7 /16 7 /16 9 /11 9 /11 7 /9 7 /9 7 /9 7 /9 9 /16 9 /16 7 /9 7 /9 9 /16 9 /16 9 /16 9 /16 75 75 75 75 75 77 77 77 76 76 76 75 75 75 76 76 73 73 73 76 76 76 70 70 70 64 64 64 64 64 64 77 77 77 64 64 64 77 77 77 77 77 77 66 66 66 66 66 67 67 67 66 66 66 66 66 66 66 66 65 65 65 66 66 66 63 63 63 59 59 59 59 59 59 67 67 67 59 59 59 67 67 67 67 67 67 49.8 49.8 49.8 49.8 49.8 55.6 55.6 55.6 64.0 64.0 64.0 49.8 49.8 49.8 58.0 60.0 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 Coil Airflow cfm Coil Sensible Load Btu/h 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,485 2,485 2,485 3,475 3,475 3,475 1,443 1,443 1,443 420 420 420 2,508 2,508 2,508 1,209 1,209 1,209 1,469 1,469 1,469 1,917 1,917 1,917 1,032 1,032 1,032 18,754 18,754 8,763 8,763 8,763 78,514 78,514 78,514 92,985 92,985 92,985 49,087 49,087 49,087 334,108 299,894 66,753 66,753 66,753 177,138 177,138 177,138 30,401 30,401 30,401 10,395 10,395 10,395 48,380 48,380 48,380 23,906 23,906 23,906 28,680 28,680 28,680 33,072 33,072 33,072 19,437 19,437 19,437 Coil Latent Load Btu/h 3,579 3,579 1,672 1,672 1,672 12,862 12,862 12,862 11,426 11,426 11,426 9,369 9,369 9,369 55,677 63,035 9,143 9,143 9,143 15,367 15,367 15,367 511 511 511 2,145 2,145 2,145 8,439 8,439 8,439 4,762 4,762 4,762 2,059 2,059 2,059 835 835 835 3,541 3,541 3,541 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 27 of 100 SPACE System Zone Room spc_A 179/178 Data C_0 Peak Zone - 088 Peak Zone - 088 Block spc_A 180E Com Lab C_0 Peak Zone - 089 Peak Zone - 089 Block spc_A 271-277 Office C_0 Peak Zone - 111 Peak Zone - 111 Block spc_A 277 Class_0 Peak Zone - 112 Peak Zone - 112 Block Peak Admin VAV Admin VAV Block spc_BC 237 Class_0 Peak Zone - 334 Peak Zone - 334 Block spc_BC 221 Lobby_0 Peak Zone - 335 Peak Zone - 335 Block spc_BC 222 Class_0 Peak Zone - 336 Peak Zone - 336 Block spc_215-219 Office_0 Peak Zone - 337 Peak Zone - 337 Block spc_BC 224 Class_0 Peak Zone - 338 Peak Zone - 338 Block spc_BC 2nd 226/228 Class_0 Peak Zone - 339 Peak Zone - 339 Block spc_BC 2nd 230 Class_0 Peak Zone - 340 Peak Zone - 340 Block spc_BC 115/116 Office_0 Peak Zone - 351 Peak Zone - 351 Block spc_BC Office 137/139/141/142_0 Peak Zone - 352 Peak Zone - 352 Block spc_BC 143 Office_0 Peak Zone - 353 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 339 339 339 951 951 951 2,656 2,656 2,656 0 0 0 18,650 18,650 166 166 166 120 120 120 196 196 196 262 262 262 146 146 146 281 281 281 187 187 187 155 155 155 103 103 103 123 123 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 9 /15 10 /14 10 /14 7 /16 7 /16 7 /18 7 /18 10 /16 10 /16 9 /11 9 /11 9 /10 9 /10 9 /17 9 /17 9 /12 9 /12 10 /16 10 /16 10 /16 76 76 76 80 80 80 75 75 75 80 80 80 78 78 79 79 79 76 76 76 73 73 73 79 79 79 70 70 70 67 67 67 76 76 76 73 73 73 79 79 79 79 79 66 66 66 63 63 63 66 66 66 63 63 63 66 66 62 62 62 66 66 66 65 65 65 64 64 64 63 63 63 61 61 61 67 67 67 63 63 63 64 64 64 64 64 70.0 70.0 70.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 71.7 71.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 57.5 57.5 57.5 57.3 57.3 57.3 57.1 57.1 57.1 57.5 57.5 57.5 55.6 55.6 55.6 56.0 56.0 56.0 57.2 57.2 57.2 56.1 56.1 56.1 51.8 51.8 51.8 58.7 58.7 2,037 2,037 2,037 2,646 2,646 2,646 1,344 1,344 1,344 4,175 4,175 4,175 28,551 22,316 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 237 237 237 38 38 38 797 797 33,300 33,300 33,300 49,154 49,154 49,154 24,971 24,971 24,971 77,551 77,551 77,551 521,509 407,618 6,259 6,259 6,259 3,956 3,956 3,956 14,583 14,583 14,583 10,595 10,595 10,595 5,091 5,091 5,091 11,008 11,008 11,008 15,364 15,364 15,364 4,204 4,204 4,204 848 848 848 11,800 11,800 771 771 771 1,906 1,906 1,906 7,134 7,134 7,134 0 0 0 33,121 44,638 375 375 375 194 194 194 681 681 681 491 491 491 468 468 468 889 889 889 658 658 658 340 340 340 192 192 192 231 231 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /19 9 /19 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /14 9 /14 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 9 /12 9 /12 9 /11 9 /11 9 /17 9 /17 9 /12 9 /12 9 /17 9 /17 10 /16 71 71 71 77 77 77 76 76 76 77 77 77 77 77 77 77 77 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 76 76 76 73 73 73 76 76 76 79 79 66 66 66 67 67 67 66 66 66 67 67 67 67 67 66 66 66 66 66 66 65 65 65 67 67 67 63 63 63 63 63 63 67 67 67 63 63 63 67 67 67 64 64 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 58.2 58.2 58.2 57.3 57.3 57.3 57.1 57.1 57.1 57.7 57.7 57.7 56.5 56.5 56.5 56.3 56.3 56.3 57.2 57.2 57.2 56.1 56.1 56.1 52.2 52.2 52.2 58.7 58.7 Coil Airflow cfm Coil Sensible Load Btu/h 2,008 2,008 2,008 2,644 2,644 2,644 1,337 1,337 1,337 4,061 4,061 4,061 26,008 22,285 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 237 237 237 38 38 38 797 797 33,409 33,409 33,409 51,546 51,546 51,546 32,823 32,823 32,823 77,838 77,838 77,838 651,278 557,619 7,849 7,849 7,849 5,195 5,195 5,195 17,225 17,225 17,225 12,759 12,759 12,759 6,331 6,331 6,331 12,300 12,300 12,300 20,480 20,480 20,480 5,546 5,546 5,546 1,020 1,020 1,020 13,862 13,862 Coil Latent Load Btu/h 1,453 1,453 1,453 5,384 5,384 5,384 12,103 12,103 12,103 0 0 0 65,740 78,660 1,025 1,025 1,025 278 278 278 1,269 1,269 1,269 1,313 1,313 1,313 701 701 701 1,464 1,464 1,464 1,309 1,309 1,309 517 517 517 535 535 535 308 308 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 28 of 100 SPACE System Zone Room Zone - 353 spc_BC 109 Class_0 Zone - 354 Zone - 354 spc_BC 108 Class_0 Zone - 355 Zone - 355 spc_BC 106 Class_0 Zone - 356 Zone - 356 spc_BC 105 Class_0 Zone - 357 Zone - 357 spc_BC 101 Class_0 Zone - 358 Zone - 358 Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block BC FC Peak BC FC Block spc_BC 130 Cafe/Kitchen_0 Peak Zone - 341 Peak Zone - 341 Block spc_BC AH-2 245 Lecture_0 Peak Zone - 342 Peak Zone - 342 Block spc_BC AH-3 301 Class_0 Peak Zone - 343 Peak Zone - 343 Block spc_BC AH-4 302 Class_0 Peak Zone - 344 Peak Zone - 344 Block spc_BC 306 Office (AH-5)_0 Peak spc_BC 307-312 Office (AH-5)_0 Peak spc_BC AH-5 304 Hall_0 Peak Zone - 345 Peak Zone - 345 Block spc_BC AH-6 315 Lab_0 Peak Zone - 346 Peak Zone - 346 Block spc_BC AH-7 314 Class_0 Peak Zone - 347 Peak Zone - 347 Block spc_BC AH-8 313_0 Peak Zone - 348 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 123 248 248 248 228 228 228 287 287 287 308 308 308 696 696 696 3,507 3,507 1,908 1,908 1,908 809 809 809 162 162 162 188 188 188 17 107 518 642 642 181 181 181 183 183 183 518 518 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 9 /12 9 /12 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /12 7 /19 7 /19 9 /13 9 /13 7 /10 7 /10 11 /13 11 /13 7 /18 10 /16 7 /18 10/16 10 /16 10 /16 6 /9 6 /9 9 /16 79 73 73 73 73 73 73 70 70 70 70 70 70 70 70 70 73 73 71 71 71 75 75 75 67 67 67 71 71 71 73 79 73 79 79 79 79 79 62 62 62 77 77 64 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 64 64 64 65 65 65 60 60 60 58 58 58 65 64 65 64 64 64 64 64 58 58 58 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 58.7 53.9 53.9 53.9 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.8 56.8 49.0 49.0 49.0 48.5 48.5 48.5 57.5 57.5 57.5 55.0 55.0 55.0 57.7 59.1 54.7 58.0 58.0 58.3 58.3 58.3 56.9 56.9 56.9 55.0 55.0 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 902 902 902 435 435 435 1,005 1,005 11,800 5,234 5,234 5,234 6,925 6,925 6,925 15,674 15,674 15,674 16,788 16,788 16,788 36,297 36,297 36,297 164,625 128,212 25,681 25,681 25,681 8,768 8,768 8,768 9,949 9,949 9,949 14,106 14,106 14,106 1,203 14,924 6,067 22,194 20,846 13,789 13,789 13,789 7,351 7,351 7,351 19,025 19,025 231 766 766 766 704 704 704 918 918 918 985 985 985 2,230 2,230 2,230 10,125 10,014 7,496 7,496 7,496 2,709 2,709 2,709 457 457 457 435 435 435 41 199 801 1,041 657 394 394 394 486 486 486 1,924 1,924 10 /16 9 /13 9 /13 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /13 7 /19 7 /19 9 /14 9 /14 7 /10 7 /10 9 /15 9 /15 7 /18 10 /16 7 /18 9 /17 9 /16 9 /16 7 /17 7 /17 9 /16 79 75 75 75 73 73 73 70 70 70 70 70 70 70 70 70 75 75 71 71 71 77 77 77 67 67 67 78 78 78 73 79 73 76 76 77 77 77 75 75 75 77 77 64 65 65 65 63 63 63 63 63 63 63 63 63 63 63 63 65 65 64 64 64 66 66 66 60 60 60 66 66 66 65 64 65 67 67 67 67 67 66 66 66 67 67 58.7 54.5 54.5 54.5 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.9 60.6 49.0 49.0 49.0 48.7 48.7 48.7 57.5 57.5 57.5 57.3 57.3 57.3 57.7 59.1 54.7 58.0 59.1 58.5 58.5 58.5 61.5 61.5 61.5 55.0 55.0 Coil Airflow cfm Coil Sensible Load Btu/h 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 902 902 902 435 435 435 1,005 1,005 13,862 6,369 6,369 6,369 8,775 8,775 8,775 17,730 17,730 17,730 19,220 19,220 19,220 40,708 40,708 40,708 195,368 154,845 28,282 28,282 28,282 10,394 10,394 10,394 11,797 11,797 11,797 17,273 17,273 17,273 1,823 19,637 7,596 29,057 27,346 18,690 18,690 18,690 9,470 9,470 9,470 25,235 25,235 Coil Latent Load Btu/h 308 1,430 1,430 1,430 1,096 1,096 1,096 1,494 1,494 1,494 1,603 1,603 1,603 3,631 3,631 3,631 17,976 18,247 13,513 13,513 13,513 4,960 4,960 4,960 624 624 624 1,481 1,481 1,481 75 265 1,033 1,373 1,870 1,012 1,012 1,012 1,133 1,133 1,133 3,625 3,625 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 29 of 100 SPACE Floor Area ft² System Zone Room Zone - 348 BC Hydronic AHU BC Hydronic AHU spc_CC 108 C_0 Zone - 120 Zone - 120 spc_CC 106 Mechanical C_0 Zone - 121 Zone - 121 spc_CC 203 Storage_0 Zone - 122 Zone - 122 spc_CC 202 Storage_0 Zone - 123 Zone - 123 spc_CC 201 Eating Area C_0 Zone - 124 Zone - 124 Campus Center Dual Deck Campus Center Dual Deck spc_CC Class 122-126 C_0 Zone - 119 Zone - 119 Campus Center FC Campus Center FC spc_CC 228 Comp C_0 Zone - 125 Zone - 125 Bookstore 1 Zone - 362 Zone - 362 Bookstore 2 Zone - 363 Zone - 363 Bookstore 3 Zone - 364 Zone - 364 Bookstore 4 Zone - 365 Zone - 365 Bookstore 5 Zone - 366 Zone - 366 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 518 4,592 4,592 381 381 381 530 530 530 159 159 159 133 133 133 1,974 1,974 1,974 3,176 3,176 1,023 1,023 1,023 1,023 1,023 519 519 519 915 915 915 915 915 915 915 915 915 915 915 915 915 915 915 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 9 /12 9 /12 9 /12 9 /12 10 /14 6 /18 6 /18 6 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 80 80 79 79 79 76 76 76 76 76 76 73 73 73 73 73 73 79 79 70 70 70 70 70 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 67 63 63 64 64 64 67 67 67 67 67 67 63 63 63 63 63 63 62 62 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.0 55.2 55.2 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.1 57.1 57.1 57.1 57.1 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 1,005 6,464 6,464 797 797 797 480 480 480 556 556 556 430 430 430 1,808 1,808 1,808 4,073 4,073 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 404 404 404 404 404 404 404 404 19,025 120,862 101,266 12,551 12,551 12,551 11,849 11,849 11,849 8,761 8,761 8,761 6,778 6,778 6,778 28,473 28,473 28,473 68,413 57,628 64,980 64,980 64,980 64,980 64,980 17,432 17,432 17,432 11,760 11,760 11,760 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 1,924 14,942 6,374 167 167 167 761 761 761 277 277 277 137 137 137 4,445 4,445 4,445 5,787 5,745 3,184 3,184 3,184 3,184 3,184 1,513 1,513 1,513 3,754 3,754 3,754 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /17 9 /17 9 /13 9 /13 9 /13 9 /13 9 /14 7 /18 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 77 77 76 76 76 76 76 76 76 76 76 75 75 75 75 75 75 77 77 73 73 73 73 73 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 67 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 65 65 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 55.0 55.8 58.3 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.4 57.4 57.4 57.4 57.4 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 Coil Airflow cfm Coil Sensible Load Btu/h 1,005 6,464 6,464 784 784 784 477 477 477 554 554 554 414 414 414 1,746 1,746 1,746 3,974 3,459 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 404 404 404 404 404 404 404 404 25,235 150,199 134,479 15,748 15,748 15,748 15,813 15,813 15,813 13,075 13,075 13,075 9,068 9,068 9,068 33,559 33,559 33,559 87,263 75,402 69,485 69,485 69,485 69,485 69,485 22,424 22,424 22,424 18,552 18,552 18,552 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 Coil Latent Load Btu/h 3,625 27,722 25,060 1,787 1,787 1,787 1,129 1,129 1,129 379 379 379 204 204 204 12,956 12,956 12,956 16,454 17,396 6,613 6,613 6,613 6,613 6,613 2,598 2,598 2,598 6,278 6,278 6,278 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 30 of 100 SPACE System Zone Room Floor Area ft² Bookstore 6 Peak Zone - 367 Peak Zone - 367 Block Campus Center Packg RTU-1 Peak Campus Center Packg RTU-1 Block spc_DM FC-Music Office_0 Peak Zone - 137 Peak Zone - 137 Block Peak spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0 Zone - 138 Peak Zone - 138 Block spc_DM FC 3-1 Dress Rms Int_0 Peak Zone - 139 Peak Zone - 139 Block spc_DM FC 3-1 Dress Rms_0 Peak Zone - 140 Peak Zone - 140 Block Drama/Music Fan Coil Peak Drama/Music Fan Coil Block spc_HP-9 Office_0 Peak Zone - 126 Peak Zone - 126 Block spc_DM HP-7 Storage_0 Peak Zone - 127 Peak Zone - 127 Block spc_DM HP-7 Dress Rm_0 Peak Zone - 128 Peak Zone - 128 Block spc_DM HP 3/4 Class_0 Peak Zone - 129 Peak Zone - 129 Block spc_DM HP-2 Class_0 Peak Zone - 130 Peak Zone - 130 Block spc_DM HP-5 Performance Rm_0 Peak Zone - 131 Peak Zone - 131 Block spc_DM HP-10 Prop Rm_0 Peak Zone - 132 Peak Zone - 132 Block spc_DM HP-1 Main Corridor_0 Peak Zone - 133 Peak Zone - 133 Block 915 915 915 6,007 6,007 338 338 338 892 892 892 267 267 267 327 327 327 1,824 1,824 121 121 121 57 57 57 9,797 9,797 9,797 926 926 926 569 569 569 1,176 1,176 1,176 1,131 1,131 1,131 7,381 7,381 7,381 Project Name: Dataset Name: SBCC TRACE.TRC OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 10 /16 10 /16 9 /17 9 /12 9 /12 10 /15 10 /15 10 /15 10 /15 6 /9 6 /9 11 /13 11 /13 9 /12 9 /12 7 /18 7 /18 9 /11 9 /11 76 76 76 76 76 79 79 79 75 75 75 76 76 76 79 79 79 76 76 73 73 73 80 80 80 80 80 80 62 62 62 71 71 71 73 73 73 73 73 73 70 70 70 66 66 66 66 66 64 64 64 66 66 66 66 66 66 64 64 64 67 67 63 63 63 63 63 63 63 63 63 58 58 58 58 58 58 63 63 63 65 65 65 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.4 49.4 49.4 51.0 51.0 56.4 56.4 56.4 54.3 54.3 54.3 44.5 44.5 44.5 58.3 58.3 58.3 55.7 55.7 57.0 57.0 57.0 54.8 54.8 54.8 51.3 51.3 51.3 55.4 55.4 55.4 59.2 59.2 59.2 53.5 53.5 53.5 57.4 57.4 57.4 56.2 56.2 56.2 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 10,160 10,160 10,160 79,989 79,989 8,123 8,123 8,123 9,831 9,831 9,831 2,946 2,946 2,946 8,853 8,853 8,853 29,753 27,815 4,747 4,747 4,747 261 261 261 99,554 99,554 99,554 21,837 21,837 21,837 35,452 35,452 35,452 27,637 27,637 27,637 36,017 36,017 36,017 106,822 106,822 106,822 2,839 2,839 2,839 19,459 19,459 633 633 633 1,432 1,432 1,432 1,098 1,098 1,098 269 269 269 3,432 4,394 263 263 263 35 35 35 25,148 25,148 25,148 2,451 2,451 2,451 1,082 1,082 1,082 4,324 4,324 4,324 1,740 1,740 1,740 9,194 9,194 9,194 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /17 9 /13 9 /13 7 /16 7 /16 9 /16 9 /16 7 /16 7 /16 9 /13 9 /13 7 /15 7 /15 7 /17 7 /17 9 /11 9 /11 76 76 76 76 76 76 76 76 75 75 75 77 77 77 79 79 79 76 76 75 75 75 76 76 76 77 77 77 76 76 76 75 75 75 77 77 77 75 75 75 70 70 70 66 66 66 66 66 67 67 67 66 66 66 67 67 67 64 64 64 67 67 65 65 65 66 66 66 67 67 67 66 66 66 65 65 65 66 66 66 66 66 66 63 63 63 49.4 49.4 49.4 51.0 51.0 56.5 56.5 56.5 54.3 54.3 54.3 45.0 45.0 45.0 58.3 58.3 58.3 55.8 56.8 57.6 57.6 57.6 55.8 55.8 55.8 51.5 51.5 51.5 59.2 59.2 59.2 60.5 60.5 60.5 59.5 59.5 59.5 57.8 57.8 57.8 56.2 56.2 56.2 Coil Airflow cfm Coil Sensible Load Btu/h 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 17,188 17,188 17,188 126,914 126,914 12,772 12,772 12,772 21,797 21,797 21,797 2,242 2,242 2,242 10,451 10,451 10,451 47,261 42,971 6,446 6,446 6,446 1,151 1,151 1,151 104,158 104,158 104,158 33,229 33,229 33,229 39,761 39,761 39,761 38,930 38,930 38,930 57,496 57,496 57,496 120,423 120,423 120,423 Coil Latent Load Btu/h 5,361 5,361 5,361 35,683 35,683 1,763 1,763 1,763 1,818 1,818 1,818 2,311 2,311 2,311 330 330 330 6,222 7,103 408 408 408 120 120 120 68,283 68,283 68,283 5,820 5,820 5,820 3,265 3,265 3,265 8,980 8,980 8,980 2,459 2,459 2,459 11,397 11,397 11,397 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 31 of 100 SPACE Floor Area ft² System Zone Room spc_DM HP-9 Class_0 Zone - 148 Zone - 148 spc_DM HP-6 Office_0 Zone - 149 Zone - 149 spc_DM HP-8 Class1_0 Zone - 150 Zone - 150 spc_DM PHP-5-2 Offices_0 Zone - 151 Zone - 151 spc_PHP-2-1 Cargo Elevator_0 Zone - 152 Zone - 152 spc_DM PRP-5-1 Restroom_0 Zone - 153 Zone - 153 spc_DM PRP-5-1 Restroom1_0 Zone - 154 Zone - 154 Drama/Music HP Drama/Music HP spc_AC-1 Auditorium_0 Zone - 141 Zone - 141 spc_DM AN-2 Corridor_0 Zone - 142 Zone - 142 spc_DM AC-2 Rehearsal Rm_0 Zone - 143 Zone - 143 spc_DM ZN-1 Class_0 Zone - 144 Zone - 144 spc_DM ZN-3 Hall_0 Zone - 145 Zone - 145 spc_DM Zn-3 Offices_0 Zone - 146 Zone - 146 spc_ZN-3 Conf_0 Zone - 147 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 192 192 192 220 220 220 592 592 592 292 292 292 122 122 122 848 848 848 1,177 1,177 1,177 24,602 24,602 3,790 3,790 3,790 701 701 701 1,135 1,135 1,135 417 417 417 209 209 209 177 177 177 405 405 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /15 10 /15 6 /9 6 /9 10 /15 10 /15 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 9 /12 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 6 /18 6 /18 10 /16 10 /16 10 /16 10 /16 6 /10 80 80 80 62 62 62 80 80 80 79 79 79 79 79 79 79 79 79 79 79 79 73 73 80 80 80 75 75 75 80 80 80 70 70 70 79 79 79 79 79 79 65 65 63 63 63 58 58 58 63 63 63 64 64 64 64 64 64 64 64 64 64 64 64 63 63 63 63 63 66 66 66 63 63 63 63 63 63 64 64 64 64 64 64 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 80.0 80.0 80.0 73.1 73.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 51.3 51.3 51.3 58.2 58.2 58.2 51.3 51.3 51.3 52.2 52.2 52.2 58.6 58.6 58.6 79.6 79.6 79.6 79.6 79.6 79.6 58.9 58.9 54.9 54.9 54.9 55.9 55.9 55.9 50.7 50.7 50.7 56.6 56.6 56.6 49.9 49.9 49.9 51.7 51.7 51.7 50.6 50.6 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 24 24 24 64 64 64 206 206 1,946 1,946 1,946 10,408 10,408 10,408 6,020 6,020 6,020 2,564 2,564 2,564 4,056 4,056 4,056 538 538 538 747 747 747 358,606 299,869 74,299 74,299 74,299 11,804 11,804 11,804 10,848 10,848 10,848 20,443 20,443 20,443 583 583 583 1,443 1,443 1,443 4,907 4,907 492 492 492 311 311 311 1,521 1,521 1,521 545 545 545 99 99 99 -2,632 -2,632 -2,632 -3,655 -3,655 -3,655 40,918 47,013 9,753 9,753 9,753 1,126 1,126 1,126 2,908 2,908 2,908 1,296 1,296 1,296 169 169 169 330 330 330 1,311 1,311 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 76 76 76 65 65 65 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 77 77 75 75 75 77 77 77 73 73 73 77 77 77 76 76 76 77 77 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 65 65 65 67 67 67 67 67 67 67 67 51.4 51.4 51.4 58.8 58.8 58.8 51.5 51.5 51.5 52.4 52.4 52.4 58.8 58.8 58.8 79.7 79.7 79.7 79.7 79.7 79.7 59.7 62.3 55.5 55.5 55.5 55.9 55.9 55.9 51.3 51.3 51.3 56.7 56.7 56.7 51.4 51.4 51.4 52.3 52.3 52.3 53.5 53.5 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 24 24 24 64 64 64 206 206 5,018 5,018 5,018 11,069 11,069 11,069 6,298 6,298 6,298 2,691 2,691 2,691 6,557 6,557 6,557 5,343 5,343 5,343 7,418 7,418 7,418 445,988 374,351 83,988 83,988 83,988 13,640 13,640 13,640 13,026 13,026 13,026 22,815 22,815 22,815 715 715 715 1,748 1,748 1,748 5,430 5,430 1,203 1,203 1,203 475 475 475 4,129 4,129 4,129 1,517 1,517 1,517 288 288 288 -46,142 -46,142 -46,142 -64,061 -64,061 -64,061 -1,859 7,013 26,500 26,500 26,500 1,430 1,430 1,430 7,893 7,893 7,893 2,691 2,691 2,691 468 468 468 919 919 919 3,494 3,494 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 32 of 100 SPACE Floor Area ft² System Zone Room Zone - 147 spc_DM Scene Shop HV-1_0 Zone - 155 Zone - 155 Drama/Music MZU Drama/Music MZU spc_EBS 217/Storage C_0 Zone - 156 Zone - 156 spc_EBS 215 Class C_0 Zone - 157 Zone - 157 spc_EBS 209 Class C_0 Zone - 158 Zone - 158 spc_EBS 210 Class C_0 Zone - 159 Zone - 159 spc_EBS 109/127 Lobby C_0 Zone - 160 Zone - 160 spc_EBS 125 Class C_0 Zone - 161 Zone - 161 spc_EBS 102 Class C_0 Zone - 162 Zone - 162 spc_EBS 123 Class C_0 Zone - 163 Zone - 163 spc_EBS 119 Offices C_0 Zone - 164 Zone - 164 spc_EBS 119 Office C_0 Zone - 165 Zone - 165 spc_EBS 116 Office C_0 Zone - 166 Zone - 166 spc_EBS 110-113 Office UC_0 Zone - 167 Zone - 167 spc_EBS 114 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 405 1,711 1,711 1,711 8,545 8,545 2,046 2,046 2,046 758 758 758 1,358 1,358 1,358 1,333 1,333 1,333 1,771 1,771 1,771 396 396 396 1,332 1,332 1,332 1,622 1,622 1,622 399 399 399 306 306 306 156 156 156 515 515 515 893 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /10 10 /13 10 /13 9 /16 7 /15 7 /15 7 /16 7 /16 10 /15 10 /15 7 /18 7 /18 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 10 /14 65 77 77 77 77 77 77 77 77 76 76 76 80 80 80 73 73 73 75 75 75 73 73 73 73 73 73 73 73 73 75 75 75 75 75 75 73 73 73 73 73 73 79 58 59 59 59 67 67 66 66 66 66 66 66 63 63 63 65 65 65 66 66 66 65 65 65 65 65 65 65 65 65 66 66 66 66 66 66 65 65 65 65 65 65 62 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 50.6 57.7 57.7 57.7 55.4 55.4 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 206 1,561 1,561 1,561 8,045 8,045 931 931 931 493 493 493 1,547 1,547 1,547 1,511 1,511 1,511 744 744 744 473 473 473 2,019 2,019 2,019 1,486 1,486 1,486 309 309 309 177 177 177 220 220 220 624 624 624 1,093 4,907 24,799 24,799 24,799 149,125 129,890 18,050 18,050 18,050 9,553 9,553 9,553 29,992 29,992 29,992 29,286 29,286 29,286 14,421 14,421 14,421 9,178 9,178 9,178 39,142 39,142 39,142 28,811 28,811 28,811 5,997 5,997 5,997 3,436 3,436 3,436 4,262 4,262 4,262 12,097 12,097 12,097 21,186 1,311 3,134 3,134 3,134 20,027 30,017 3,114 3,114 3,114 2,661 2,661 2,661 3,489 3,489 3,489 4,607 4,607 4,607 2,924 2,924 2,924 1,369 1,369 1,369 4,604 4,604 4,604 5,608 5,608 5,608 1,057 1,057 1,057 811 811 811 368 368 368 1,214 1,214 1,214 2,014 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /14 9 /14 9 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /14 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 75 75 75 75 75 75 73 73 73 73 73 73 75 75 75 75 75 75 75 75 75 73 73 73 73 73 73 77 67 66 66 66 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 66 53.5 58.2 58.2 58.2 55.9 57.5 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 206 1,561 1,561 1,561 8,045 8,045 903 903 903 493 493 493 1,515 1,515 1,515 1,493 1,493 1,493 744 744 744 473 473 473 2,019 2,019 2,019 1,454 1,454 1,454 309 309 309 177 177 177 220 220 220 624 624 624 1,079 5,430 30,462 30,462 30,462 171,824 156,601 40,996 40,996 40,996 17,369 17,369 17,369 45,366 45,366 45,366 45,809 45,809 45,809 35,058 35,058 35,058 14,006 14,006 14,006 55,862 55,862 55,862 46,115 46,115 46,115 10,829 10,829 10,829 6,764 6,764 6,764 6,557 6,557 6,557 19,460 19,460 19,460 22,361 Coil Latent Load Btu/h 3,494 10,580 10,580 10,580 53,975 55,726 4,331 4,331 4,331 4,766 4,766 4,766 9,476 9,476 9,476 8,212 8,212 8,212 4,199 4,199 4,199 2,548 2,548 2,548 8,567 8,567 8,567 9,995 9,995 9,995 1,822 1,822 1,822 1,398 1,398 1,398 677 677 677 2,235 2,235 2,235 5,495 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 33 of 100 SPACE Floor Area ft² System Zone Room Zone - 168 Zone - 168 spc_EBS 115 Class C_0 Zone - 169 Zone - 169 spc_EBS 209 Class UC_0 Zone - 172 Zone - 172 spc_EBS 210 Class C_1 Zone - 173 Zone - 173 spc_EBS 215 Class C_1 Zone - 174 Zone - 174 spc_EBS 218 Office C_0 Zone - 175 Zone - 175 spc_EBS 216 Office C_0 Zone - 176 Zone - 176 EBS VAV EBS VAV spc_H 326 Class C_0 Zone - 206 Zone - 206 spc_H 328 Class C_0 Zone - 207 Zone - 207 spc_H 328 Office C_0 Zone - 208 Zone - 208 Humanities Fan Coil Humanities Fan Coil spc_H 104/107/112 Art C_0 Zone - 177 Zone - 177 spc_H 102 Class C_0 Zone - 178 Zone - 178 spc_H 106 Office C_0 Zone - 179 Zone - 179 spc_H 2444 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 893 893 10 /14 1,659 9 /16 1,659 1,659 9 /16 1,334 7 /16 1,334 1,334 7 /16 1,334 7 /16 1,334 1,334 7 /16 790 7 /18 790 790 7 /18 70 7 /18 70 70 7/18 74 7 /17 74 74 7 /17 18,147 18,147 7 /17 845 5 /17 845 845 5 /17 1,818 7 /16 1,818 1,818 7 /16 300 7 /12 300 300 7 /12 2,963 2,963 7 /17 7,121 7 /16 7,121 7,121 7 /16 1,004 7 /16 1,004 1,004 7 /16 229 7 /17 229 229 7 /17 555 7 /16 79 79 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 72 72 72 76 76 76 73 73 73 75 75 76 76 76 76 76 76 75 75 75 76 62 62 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 63 63 63 66 66 66 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 54.3 54.3 54.3 56.6 56.6 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 1,093 1,093 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,925 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,288 5,288 5,288 627 627 627 122 122 122 346 21,186 21,186 31,380 31,380 31,380 16,818 16,818 16,818 16,818 16,818 16,818 14,759 14,759 14,759 2,665 2,665 2,665 826 826 826 308,677 289,380 76,201 76,201 76,201 24,051 24,051 24,051 4,645 4,645 4,645 104,897 101,595 91,368 91,368 91,368 10,835 10,835 10,835 2,102 2,102 2,102 5,987 2,014 2,014 6,149 6,149 6,149 4,685 4,685 4,685 4,685 4,685 4,685 2,731 2,731 2,731 166 166 166 195 195 195 52,452 52,299 2,350 2,350 2,350 6,371 6,371 6,371 631 631 631 9,352 9,537 24,945 24,945 24,945 3,519 3,519 3,519 604 604 604 1,944 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /14 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /17 7 /15 7 /15 9 /16 9 /16 9 /17 9 /17 9 /16 77 77 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 73 73 73 76 76 76 76 76 76 75 75 77 77 77 77 77 77 76 76 76 77 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 65 65 65 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 57.2 57.2 57.2 56.7 57.1 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 1,079 1,079 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,801 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,284 5,284 5,284 600 600 600 119 119 119 331 22,361 22,361 49,825 49,825 49,825 30,579 30,579 30,579 30,579 30,579 30,579 23,381 23,381 23,381 3,913 3,913 3,913 1,626 1,626 1,626 504,179 486,608 92,686 92,686 92,686 49,932 49,932 49,932 8,423 8,423 8,423 151,042 148,011 99,527 99,527 99,527 11,228 11,228 11,228 2,209 2,209 2,209 6,204 Coil Latent Load Btu/h 5,495 5,495 11,570 11,570 11,570 8,391 8,391 8,391 8,391 8,391 8,391 5,082 5,082 5,082 305 305 305 336 336 336 97,796 94,521 5,460 5,460 5,460 11,390 11,390 11,390 1,341 1,341 1,341 18,190 17,762 43,603 43,603 43,603 6,979 6,979 6,979 1,184 1,184 1,184 3,856 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 34 of 100 SPACE Floor Area ft² System Zone Room Zone - 180 Zone - 180 spc_H 245A/B Class C_0 Zone - 181 Zone - 181 spc_H 226/A office C_0 Zone - 182 Zone - 182 spc_H 208-217 Office C_0 Zone - 183 Zone - 183 spc_H 225 Office C_0 Zone - 184 Zone - 184 spc_H 242/207 Corridor C_0 Zone - 185 Zone - 185 spc_H 123U Art AH-1/23_0 Zone - 186 Zone - 186 spc_H 111 Class C_0 Zone - 187 Zone - 187 spc_H 221/220/204 Class C_0 Zone - 188 Zone - 188 spc_H 232A Class C_0 Zone - 189 Zone - 189 spc_H 239 Class Office_0 Zone - 190 Zone - 190 spc_H 237 Office C_0 Zone - 191 Zone - 191 spc_H 236 Office C_0 Zone - 192 Zone - 192 spc_H 241 Class C_0 Zone - 193 Zone - 193 spc_H 309-318 Offices C_0 Zone - 194 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 555 555 1,686 1,686 1,686 272 272 272 1,065 1,065 1,065 267 267 267 4,126 4,126 4,126 2,482 2,482 2,482 1,805 1,805 1,805 4,564 4,564 4,564 1,111 1,111 1,111 306 306 306 90 90 90 272 272 272 571 571 571 1,012 1,012 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /17 7 /17 11 /13 11 /13 11 /14 11 /14 11 /14 11 /14 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 11 /14 76 76 75 75 75 71 71 71 73 73 73 73 73 73 79 79 79 75 75 75 76 76 76 77 77 77 76 76 76 77 77 77 75 75 75 75 75 75 76 76 76 73 73 66 66 66 66 66 58 58 58 60 60 60 60 60 60 64 64 64 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 60 60 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 346 346 2,157 2,157 2,157 798 798 798 3,496 3,496 3,496 765 765 765 1,412 1,412 1,412 2,382 2,382 2,382 1,127 1,127 1,127 3,577 3,577 3,577 693 693 693 311 311 311 48 48 48 145 145 145 356 356 356 4,319 4,319 5,987 5,987 37,265 37,265 37,265 13,783 13,783 13,783 60,401 60,401 60,401 13,211 13,211 13,211 24,400 24,400 24,400 41,156 41,156 41,156 19,474 19,474 19,474 61,807 61,807 61,807 11,982 11,982 11,982 5,382 5,382 5,382 828 828 828 2,500 2,500 2,500 6,155 6,155 6,155 74,623 74,623 1,944 1,944 5,523 5,523 5,523 89 89 89 766 766 766 192 192 192 3,332 3,332 3,332 8,130 8,130 8,130 6,325 6,325 6,325 15,809 15,809 15,809 3,891 3,891 3,891 1,060 1,060 1,060 238 238 238 719 719 719 1,999 1,999 1,999 728 728 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /14 9 /14 9 /15 9 /15 9 /15 9 /15 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /15 7 /15 9 /16 9 /16 7 /15 7 /15 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /15 77 77 77 77 77 77 77 77 78 78 78 78 78 78 77 77 77 76 76 76 77 77 77 77 77 77 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 78 78 67 67 67 67 67 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 331 331 2,071 2,071 2,071 743 743 743 2,999 2,999 2,999 665 665 665 1,401 1,401 1,401 2,313 2,313 2,313 1,078 1,078 1,078 3,577 3,577 3,577 663 663 663 311 311 311 47 47 47 142 142 142 341 341 341 3,657 3,657 6,204 6,204 40,964 40,964 40,964 15,383 15,383 15,383 74,566 74,566 74,566 13,581 13,581 13,581 25,840 25,840 25,840 45,783 45,783 45,783 20,181 20,181 20,181 67,488 67,488 67,488 12,417 12,417 12,417 5,994 5,994 5,994 871 871 871 2,628 2,628 2,628 6,379 6,379 6,379 87,004 87,004 Coil Latent Load Btu/h 3,856 3,856 11,713 11,713 11,713 999 999 999 4,843 4,843 4,843 1,216 1,216 1,216 9,229 9,229 9,229 17,267 17,267 17,267 12,544 12,544 12,544 27,948 27,948 27,948 7,718 7,718 7,718 1,874 1,874 1,874 467 467 467 1,408 1,408 1,408 3,965 3,965 3,965 4,603 4,603 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 35 of 100 SPACE Floor Area ft² System Zone Room Zone - 194 spc_H 240 Class C_0 Zone - 195 Zone - 195 spc_H 300 Restrooms C_0 Zone - 196 Zone - 196 spc_H 322 Office C_0 Zone - 197 Zone - 197 spc_H 323 Office C_0 Zone - 198 Zone - 198 spc_H 300H Hall C_0 Zone - 199 Zone - 199 spc_H 202 Class C_0 Zone - 200 Zone - 200 spc_H 205 Office C_0 Zone - 201 Zone - 201 spc_H 205/203 Class C_0 Zone - 202 Zone - 202 spc_H 232B Office C_0 Zone - 203 Zone - 203 spc_H 223 Class C_0 Zone - 204 Zone - 204 spc_H 223U Storage C_0 Zone - 205 Zone - 205 spc_H 306 Class C_0 Zone - 211 Zone - 211 spc_H 308 Class H_0 Zone - 212 Zone - 212 spc_H 301-307 Classes C_0 Zone - 213 Zone - 213 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,012 818 818 818 339 339 339 265 265 265 265 265 265 3,593 3,593 3,593 1,118 1,118 1,118 270 270 270 846 846 846 161 161 161 616 616 616 165 165 165 727 727 727 512 512 512 3,348 3,348 3,348 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 11 /14 7 /15 7 /15 9 /17 9 /17 11 /14 11 /14 7 /17 7 /17 10 /16 10 /16 8/10 8 /10 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /16 7 /16 7 /15 7 /15 73 77 77 77 76 76 76 73 73 73 75 75 75 79 79 79 67 67 67 75 75 75 76 76 76 75 75 75 76 76 76 77 77 77 76 76 76 76 76 76 77 77 77 60 66 66 66 67 67 67 60 60 60 66 66 66 64 64 64 61 61 61 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 4,319 642 642 642 542 542 542 1,069 1,069 1,069 141 141 141 3,898 3,898 3,898 2,401 2,401 2,401 144 144 144 528 528 528 86 86 86 385 385 385 51 51 51 454 454 454 320 320 320 2,748 2,748 2,748 74,623 11,100 11,100 11,100 14,193 14,193 14,193 18,478 18,478 18,478 2,434 2,434 2,434 67,353 67,353 67,353 41,487 41,487 41,487 2,483 2,483 2,483 9,121 9,121 9,121 1,483 1,483 1,483 6,648 6,648 6,648 876 876 876 7,841 7,841 7,841 5,526 5,526 5,526 47,476 47,476 47,476 728 2,834 2,834 2,834 619 619 619 190 190 190 700 700 700 9,908 9,908 9,908 3,433 3,433 3,433 714 714 714 2,962 2,962 2,962 426 426 426 2,159 2,159 2,159 250 250 250 2,546 2,546 2,546 1,795 1,795 1,795 11,597 11,597 11,597 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /15 7 /15 7 /15 9 /17 9 /17 9 /15 9 /15 9 /17 9 /17 9 /16 9 /16 9 /11 9 /11 9 /17 9 /17 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 9 /15 9 /15 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 78 77 77 77 76 76 76 78 78 78 76 76 76 77 77 77 70 70 70 76 76 76 77 77 77 76 76 76 77 77 77 78 78 78 76 76 76 76 76 76 76 76 76 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 63 63 63 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 3,657 642 642 642 210 210 210 890 890 890 138 138 138 3,839 3,839 3,839 2,239 2,239 2,239 141 141 141 505 505 505 84 84 84 368 368 368 47 47 47 441 441 441 311 311 311 2,733 2,733 2,733 87,004 12,091 12,091 12,091 14,647 14,647 14,647 21,157 21,157 21,157 2,558 2,558 2,558 126,357 126,357 126,357 45,716 45,716 45,716 2,609 2,609 2,609 9,452 9,452 9,452 1,558 1,558 1,558 6,890 6,890 6,890 878 878 878 19,161 19,161 19,161 13,504 13,504 13,504 102,755 102,755 102,755 Coil Latent Load Btu/h 4,603 5,010 5,010 5,010 4,236 4,236 4,236 1,203 1,203 1,203 1,371 1,371 1,371 24,964 24,964 24,964 5,771 5,771 5,771 1,399 1,399 1,399 5,875 5,875 5,875 835 835 835 4,282 4,282 4,282 357 357 357 4,551 4,551 4,551 3,208 3,208 3,208 20,961 20,961 20,961 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 36 of 100 SPACE System Zone Room spc_H 301 Class C_0 Peak Zone - 214 Peak Zone - 214 Block spc_H 3281 Hall C_0 Peak Zone - 215 Peak Zone - 215 Block Humanities VAV Peak Humanities VAV Block spc_IDC 335 Office C_0 Peak Zone - 220 Peak Zone - 220 Block spc_IDC 313 Wrk Rm_0 Peak Zone - 221 Peak Zone - 221 Block spc_IDC 317 Wrk Rm C_0 Peak Zone - 222 Peak Zone - 222 Block spc_IDC 329 C_0 Peak Zone - 223 Peak Zone - 223 Block IDC Fan Coil Peak IDC Fan Coil Block Peak spc_IDC 102/103/104/109 Int Class_0 Zone - 216 Peak Zone - 216 Block spc_IDC 205 Class C_0 Peak Zone - 217 Peak Zone - 217 Block spc_IDC 211/210 Class_0 Peak Zone - 218 Peak Zone - 218 Block spc_IDC 333 Office_0 Peak Zone - 219 Peak Zone - 219 Block IDC VAV Peak IDC VAV Block spc_LRC 140-01-08 C_0 Peak Zone - 224 Peak Zone - 224 Block spc_LRC 140-09 C_0 Peak Zone - 225 Peak Zone - 225 Block spc_LRC 13-15 C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 633 633 633 228 228 228 42,441 42,441 107 107 107 206 206 206 171 171 171 102 102 102 586 586 3,318 3,318 3,318 460 460 460 1,001 1,001 1,001 414 414 414 5,194 5,194 1,843 1,843 1,843 250 250 250 153 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 10 /15 7 /17 7 /17 7 /16 7 /16 7 /16 7/16 7 /16 7 /16 7 /16 10 /15 10 /15 10 /15 10 /15 10 /15 10 /15 10 /17 10 /17 10 /15 6 /10 6 /10 9 /12 9 /12 9 /11 76 76 76 76 76 76 80 80 75 75 75 76 76 76 76 76 76 76 76 76 76 76 80 80 80 80 80 80 80 80 80 77 77 77 80 80 65 65 65 73 73 73 70 66 66 66 66 66 66 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 63 63 63 63 63 63 64 64 64 63 63 58 58 58 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.1 72.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 395 395 395 53 53 53 41,826 37,423 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,694 1,694 1,694 859 859 859 511 511 511 180 180 180 3,244 3,237 1,595 1,595 1,595 797 797 797 632 6,823 6,823 6,823 911 911 911 727,491 650,911 1,280 1,280 1,280 2,975 2,975 2,975 2,627 2,627 2,627 1,357 1,357 1,357 8,239 8,216 32,706 32,706 32,706 16,577 16,577 16,577 9,869 9,869 9,869 3,472 3,472 3,472 62,624 62,481 28,266 28,266 28,266 14,118 14,118 14,118 11,205 2,216 2,216 2,216 354 354 354 122,518 95,452 284 284 284 722 722 722 600 600 600 357 357 357 1,962 1,958 8,526 8,526 8,526 1,182 1,182 1,182 2,573 2,573 2,573 855 855 855 13,135 12,972 5,957 5,957 5,957 915 915 915 580 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 9 /16 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 7 /16 7 /16 9 /13 9 /13 9 /11 76 76 76 76 76 76 77 77 75 75 75 76 76 76 76 76 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 75 75 75 77 77 76 76 76 75 75 75 70 66 66 66 66 66 66 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 66 66 66 65 65 65 63 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 384 384 384 49 49 49 39,362 36,284 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,668 1,668 1,668 843 843 843 503 503 503 179 179 179 3,194 3,189 1,448 1,448 1,448 757 757 757 632 16,673 16,673 16,673 4,252 4,252 4,252 957,271 890,214 2,183 2,183 2,183 4,555 4,555 4,555 3,950 3,950 3,950 2,128 2,128 2,128 12,817 12,798 38,524 38,524 38,524 19,698 19,698 19,698 11,625 11,625 11,625 10,755 10,755 10,755 80,821 79,588 54,618 54,618 54,618 17,332 17,332 17,332 12,865 3,960 3,960 3,960 448 448 448 249,846 272,391 488 488 488 1,291 1,291 1,291 1,072 1,072 1,072 638 638 638 3,490 3,478 23,156 23,156 23,156 3,209 3,209 3,209 6,987 6,987 6,987 1,894 1,894 1,894 35,247 35,420 12,597 12,597 12,597 1,569 1,569 1,569 880 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 37 of 100 SPACE Floor Area ft² System Zone Room Zone - 226 Zone - 226 spc_LRC 16 C_0 Zone - 227 Zone - 227 spc_LRC 17/18_0 Zone - 228 Zone - 228 spc_LRC 5 C (Study?)_0 Zone - 229 Zone - 229 spc_LRC 9 Storage_0 Zone - 230 Zone - 230 spc_LRC 10 Storage_0 Zone - 231 Zone - 231 spc_LRC 7 C_0 Zone - 232 Zone - 232 spc_LRC 8 Stair_0 Zone - 233 Zone - 233 spc_LRC Catalog C_0 Zone - 234 Zone - 234 spc_LRC Computer_0 Zone - 235 Zone - 235 spc_LRC 2/6_0 Zone - 236 Zone - 236 spc_LRC 1st RR C_0 Zone - 237 Zone - 237 spc_LRC 24_0 Zone - 238 Zone - 238 spc_LRC 25_0 Zone - 239 Zone - 239 spc_LRC 105 C Work_0 Zone - 240 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 153 153 66 66 66 94 94 94 57 57 57 29 29 29 24 24 24 119 119 119 302 302 302 56 56 56 525 525 525 137 137 137 226 226 226 564 564 564 325 325 325 62 62 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 10 /13 10 /13 10 /16 10 /16 7 /15 7 /15 7 /15 7 /15 6 /10 6/10 6 /18 6 /18 7 /18 7 /18 7 /18 7 /18 6 /17 6 /17 7 /15 7 /15 10 /16 10/16 10 /16 10 /16 7 /18 7 /18 7 /18 70 70 77 77 77 79 79 79 77 77 77 77 77 77 65 65 65 70 70 70 73 73 73 73 73 73 72 72 72 77 77 77 79 79 79 79 79 79 73 73 73 73 73 63 63 59 59 59 64 64 64 66 66 66 66 66 66 58 58 58 63 63 63 65 65 65 65 65 65 63 63 63 66 66 66 64 64 64 64 64 64 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 632 632 296 296 296 800 800 800 34 34 34 9 9 9 43 43 43 499 499 499 178 178 178 119 119 119 1,809 1,809 1,809 78 78 78 362 362 362 2,024 2,024 2,024 956 956 956 123 123 11,205 11,205 5,239 5,239 5,239 14,180 14,180 14,180 606 606 606 156 156 156 770 770 770 8,836 8,836 8,836 3,148 3,148 3,148 2,112 2,112 2,112 32,061 32,061 32,061 1,384 1,384 1,384 9,633 9,633 9,633 35,871 35,871 35,871 16,939 16,939 16,939 2,178 2,178 580 580 159 159 159 316 316 316 196 196 196 44 44 44 16 16 16 366 366 366 460 460 460 226 226 226 1,210 1,210 1,210 556 556 556 181 181 181 1,890 1,890 1,890 1,302 1,302 1,302 214 214 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /13 9 /13 9 /16 9 /16 9 /16 9 /16 9 /15 9 /15 6 /10 6 /10 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /16 9 /16 7 /18 7 /18 7 /18 70 70 75 75 75 77 77 77 77 77 77 78 78 78 65 65 65 73 73 73 73 73 73 73 73 73 75 75 75 77 77 77 79 79 79 77 77 77 73 73 73 73 73 63 63 65 65 65 67 67 67 67 67 67 66 66 66 58 58 58 65 65 65 65 65 65 65 65 65 66 66 66 67 67 67 64 64 64 67 67 67 65 65 65 65 65 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 632 632 289 289 289 781 781 781 34 34 34 8 8 8 43 43 43 495 495 495 178 178 178 119 119 119 1,791 1,791 1,791 77 77 77 186 186 186 1,981 1,981 1,981 956 956 956 123 123 12,865 12,865 5,989 5,989 5,989 15,724 15,724 15,724 602 602 602 149 149 149 999 999 999 9,606 9,606 9,606 3,388 3,388 3,388 2,494 2,494 2,494 34,140 34,140 34,140 1,369 1,369 1,369 8,860 8,860 8,860 39,177 39,177 39,177 19,463 19,463 19,463 3,446 3,446 Coil Latent Load Btu/h 880 880 417 417 417 710 710 710 392 392 392 63 63 63 19 19 19 757 757 757 592 592 592 392 392 392 2,556 2,556 2,556 1,032 1,032 1,032 996 996 996 4,243 4,243 4,243 2,256 2,256 2,256 397 397 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 38 of 100 SPACE System Zone Room Zone - 240 Block spc_LRC Tables/124B C_0 Peak Zone - 241 Peak Zone - 241 Block spc_LRC 120/122/123 Office C_0 Peak Zone - 242 Peak Zone - 242 Block spc_LRC Tutor Lab C_0 Peak Zone - 243 Peak Zone - 243 Block spc_LRC Lobby/112B Corridor C_0Peak Zone - 244 Peak Zone - 244 Block spc_LRC Dir Offc C_0 Peak Zone - 245 Peak Zone - 245 Block spc_LRC 108/111/115 Counter_0 Peak Zone - 246 Peak Zone - 246 Block spc_LRC 149A_0 Peak Zone - 247 Peak Zone - 247 Block spc_LRC 137 Work C_0 Peak Zone - 248 Peak Zone - 248 Block spc_LRC 140-142 Director_0 Peak Zone - 249 Peak Zone - 249 Block spc_LRC 145 Office C_0 Peak Zone - 250 Peak Zone - 250 Block spc_LRC 146A Storage_0 Peak Zone - 251 Peak Zone - 251 Block spc_LRC 146_0 Peak Zone - 252 Peak Zone - 252 Block spc_LRC Library_0 Peak Zone - 253 Peak Zone - 253 Block spc_LRC 140-14_0 Peak Zone - 254 Peak Zone - 254 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 62 647 647 647 58 58 58 63 63 63 582 582 582 36 36 36 335 335 335 25 25 25 59 59 59 38 38 38 23 23 23 14 14 14 80 80 80 0 0 0 42 42 42 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 10 /15 10 /15 6 /11 6 /11 7 /15 7 /15 7 /18 7 /18 6 /18 6 /18 7/15 7 /15 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 10 /13 10 /13 11 /12 11 /12 9 /12 9 /12 73 80 80 80 68 68 68 77 77 77 73 73 73 70 70 70 77 77 77 73 73 73 73 73 73 75 75 75 75 75 75 79 79 79 77 77 77 68 68 68 73 73 73 65 63 63 63 60 60 60 66 66 66 65 65 65 63 63 63 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 64 64 64 59 59 59 55 55 55 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 123 1,184 1,184 1,184 119 119 119 110 110 110 387 387 387 147 147 147 191 191 191 45 45 45 191 191 191 20 20 20 12 12 12 64 64 64 252 252 252 2,551 2,551 2,551 190 190 190 2,178 20,983 20,983 20,983 2,116 2,116 2,116 1,946 1,946 1,946 6,866 6,866 6,866 2,614 2,614 2,614 3,378 3,378 3,378 793 793 793 3,381 3,381 3,381 359 359 359 214 214 214 1,140 1,140 1,140 4,464 4,464 4,464 45,210 45,210 45,210 3,371 3,371 3,371 214 1,652 1,652 1,652 103 103 103 180 180 180 975 975 975 72 72 72 1,358 1,358 1,358 86 86 86 204 204 204 101 101 101 60 60 60 11 11 11 192 192 192 0 0 0 154 154 154 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /18 9 /16 9 /16 7 /12 7 /12 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 9 /14 9 /14 9 /11 9 /11 9 /12 9 /12 73 77 77 77 73 73 73 76 76 76 75 75 75 73 73 73 76 76 76 73 73 73 73 73 73 75 75 75 75 75 75 76 76 76 77 77 77 70 70 70 73 73 73 65 67 67 67 63 63 63 66 66 66 66 66 66 65 65 65 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 67 67 67 66 66 66 63 63 63 63 63 63 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 123 1,113 1,113 1,113 117 117 117 110 110 110 364 364 364 145 145 145 190 190 190 45 45 45 191 191 191 20 20 20 12 12 12 63 63 63 233 233 233 2,488 2,488 2,488 190 190 190 3,446 32,086 32,086 32,086 2,850 2,850 2,850 2,980 2,980 2,980 14,670 14,670 14,670 3,509 3,509 3,509 8,372 8,372 8,372 1,278 1,278 1,278 4,731 4,731 4,731 936 936 936 559 559 559 1,612 1,612 1,612 5,818 5,818 5,818 47,040 47,040 47,040 4,151 4,151 4,151 Coil Latent Load Btu/h 397 4,480 4,480 4,480 178 178 178 312 312 312 1,365 1,365 1,365 155 155 155 2,288 2,288 2,288 159 159 159 378 378 378 174 174 174 104 104 104 35 35 35 535 535 535 0 0 0 223 223 223 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 39 of 100 SPACE OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F System Zone Room Floor Area ft² spc_LRC 140-03_0 Peak Zone - 255 Peak Zone - 255 Block spc_LRC 101 Work C_0 Peak Zone - 256 Peak Zone - 256 Block spc_LRC 108-110 Storage_0 Peak Zone - 257 Peak Zone - 257 Block spc_LRC 109 Work_0 Peak Zone - 258 Peak Zone - 258 Block LRC VAV Peak LRC VAV Block spc_OE 10WM Restrooms AH-2_0Peak Zone - 259 Peak Zone - 259 Block spc_OE 112 Class C_0 Peak Zone - 260 Peak Zone - 260 Block spc_OE 116 Class C_0 Peak Zone - 261 Peak Zone - 261 Block spc_OE 180H/182 Class C_0 Peak Zone - 262 Peak Zone - 262 Block spc_OE 180A Office C_0 Peak Zone - 263 Peak Zone - 263 Block OE Pckg AH Peak OE Pckg AH Block spc_PE 108 Weight Rm HP3/4_0 Peak Zone - 006 Peak Zone - 006 Block spc_PE Locker/RR HP-06/07_0 Peak Zone - 008 Peak Zone - 008 Block Peak spc_PE 302-310E Office Partially C_0 Zone - 011 Peak Zone - 011 Block PE Heat Pump Peak PE Heat Pump Block spc_PE Gym AH1_0 Peak 86 6 /10 86 86 6 /10 62 9 /17 62 62 9 /17 24 7 /15 24 24 7 /15 43 9 /17 43 43 9 /17 7,052 7,052 9 /16 172 7 /18 172 172 7/18 522 10 /15 522 522 10 /15 1,121 7 /18 1,121 1,121 7 /18 509 9 /11 509 509 9 /11 66 7 /17 66 66 7 /17 2,391 2,391 10 /14 3,594 9 /10 3,594 3,594 9 /10 1,968 7 /18 1,968 1,968 7 /18 498 7 /18 498 498 7 /18 6,061 6,061 7 /18 7,524 7 /17 Project Name: Dataset Name: SBCC TRACE.TRC 65 65 65 76 76 76 77 77 77 76 76 76 77 77 73 73 73 80 80 80 73 73 73 70 70 70 75 75 75 79 79 67 67 67 73 73 73 73 73 73 73 73 75 58 58 58 67 67 67 66 66 66 67 67 67 67 67 65 65 65 63 63 63 65 65 65 63 63 63 66 66 66 62 62 61 61 61 65 65 65 65 65 65 65 65 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.2 72.2 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.7 72.7 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 76.0 76.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 73.2 73.2 73.2 56.6 56.6 56.6 52.2 52.2 52.2 55.6 55.6 55.6 48.8 48.8 48.8 56.4 56.4 54.5 54.5 54.5 74.3 74.3 74.3 56.3 56.3 56.3 64.7 64.7 72.4 207 207 207 186 186 186 7 7 7 143 143 143 16,361 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 3,150 3,150 1,009 1,009 1,009 6,278 6,278 1,505 3,672 3,672 3,672 3,302 3,302 3,302 123 123 123 2,540 2,540 2,540 293,173 232,240 2,089 2,089 2,089 17,559 17,559 17,559 20,357 20,357 20,357 17,712 17,712 17,712 589 589 589 58,307 44,634 41,395 41,395 41,395 19,874 19,874 19,874 17,669 17,669 17,669 78,937 60,043 -636 277 277 277 218 218 218 36 36 36 152 152 152 20,421 25,647 59 59 59 1,340 1,340 1,340 3,874 3,874 3,874 1,628 1,628 1,628 176 176 176 7,077 4,708 4,036 4,036 4,036 668 668 668 1,173 1,173 1,173 5,877 7,430 -4,539 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 9 /17 9 /17 7 /16 7 /16 9 /17 9 /17 9 /16 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 9 /13 9 /13 7 /17 7 /17 9 /16 9 /13 9 /13 9 /17 9 /17 7 /18 7 /18 9 /17 7 /14 75 75 75 76 76 76 76 76 76 76 76 76 77 77 76 76 76 77 77 77 73 73 73 75 75 75 75 75 75 77 77 75 75 75 76 76 76 73 73 73 76 76 76 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 66 67 67 65 65 65 67 67 67 65 65 65 67 67 65 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 76.2 76.2 76.2 57.4 57.4 57.4 52.2 52.2 52.2 57.4 57.4 57.4 48.8 48.8 48.8 57.5 60.7 57.2 57.2 57.2 75.4 75.4 75.4 56.3 56.3 56.3 66.2 68.1 72.4 Coil Airflow cfm Coil Sensible Load Btu/h 164 164 164 186 186 186 7 7 7 143 143 143 15,679 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 3,150 3,150 1,009 1,009 1,009 6,278 6,278 451 4,618 4,618 4,618 4,899 4,899 4,899 475 475 475 3,755 3,755 3,755 382,332 328,402 2,439 2,439 2,439 21,294 21,294 21,294 23,315 23,315 23,315 22,689 22,689 22,689 1,667 1,667 1,667 71,405 61,879 36,526 36,526 36,526 36,640 36,640 36,640 27,335 27,335 27,335 100,501 80,404 -191 Coil Latent Load Btu/h 569 569 569 432 432 432 50 50 50 300 300 300 41,604 50,410 755 755 755 3,639 3,639 3,639 7,205 7,205 7,205 2,921 2,921 2,921 304 304 304 14,824 15,804 19,890 19,890 19,890 8,557 8,557 8,557 2,160 2,160 2,160 30,607 29,879 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 40 of 100 SPACE System Zone Room Zone - 001 Peak Zone - 001 Block spc_PE Team Lockey RH4_0 Peak Zone - 002 Peak Zone - 002 Block spc_PE 113 RH7/RH8_0 Peak Zone - 003 Peak Zone - 003 Block spc_PE 114 C_0 Peak Zone - 004 Peak Zone - 004 Block spc_PE 109 NC_0 Peak Zone - 005 Peak Zone - 005 Block spc_PE 2nd Flr Lobby_0 Peak Zone - 007 Peak Zone - 007 Block Peak spc_PE 214-218, 201-203 Offices C_0 Zone - 009 Peak Zone - 009 Block spc_PE 3 Press Box RH02 _0 Peak Zone - 010 Peak Zone - 010 Block PE VAV Htg Only Peak PE VAV Htg Only Block spc_sp_55 Peak Zone - 264 Peak Zone - 264 Block spc_sp_56 Peak Zone - 265 Peak Zone - 265 Block spc_sp_57 Peak Zone - 266 Peak Zone - 266 Block spc_sp_58 Peak Zone - 267 Peak Zone - 267 Block spc_sp_59 Peak Zone - 268 Peak Zone - 268 Block spc_sp_60 Peak Zone - 269 Peak Zone - 269 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 7,524 7,524 744 744 744 1,696 1,696 1,696 1,001 1,001 1,001 683 683 683 7,013 7,013 7,013 1,922 1,922 1,922 174 174 174 20,757 20,757 1,130 1,130 1,130 1,130 1,130 1,130 1,159 1,159 1,159 1,087 1,087 1,087 396 396 396 828 828 828 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 10 /16 10 /16 9 /16 9 /16 9 /10 9 /10 10 /15 10 /15 7 /10 7 /10 7/18 7 /18 10 /16 10 /16 7 /17 10 /13 10 /13 10 /15 10 /15 9 /12 9 /12 10 /16 10 /16 11 /15 11 /15 7 /18 7 /18 75 75 79 79 79 77 77 77 67 67 67 80 80 80 67 67 67 73 73 73 79 79 79 75 75 77 77 77 80 80 80 73 73 73 79 79 79 73 73 73 73 73 73 66 66 64 64 64 67 67 67 61 61 61 63 63 63 60 60 60 65 65 65 64 64 64 66 66 59 59 59 63 63 63 63 63 63 64 64 64 62 62 62 65 65 65 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 74.4 74.4 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 58.6 58.6 58.6 55.9 55.9 55.9 54.6 54.6 54.6 56.3 56.3 56.3 58.2 58.2 58.2 54.7 54.7 54.7 1,505 1,505 1,190 1,190 1,190 339 339 339 200 200 200 137 137 137 351 351 351 256 256 256 23 23 23 4,001 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 -636 -636 10,111 10,111 10,111 -143 -143 -143 -85 -85 -85 -58 -58 -58 -148 -148 -148 -108 -108 -108 -10 -10 -10 8,923 0 25,370 25,370 25,370 30,201 30,201 30,201 29,008 29,008 29,008 37,550 37,550 37,550 33,464 33,464 33,464 25,783 25,783 25,783 -4,539 -4,539 -971 -971 -971 2,691 2,691 2,691 1,039 1,039 1,039 306 306 306 -8,532 -8,532 -8,532 454 454 454 -45 -45 -45 -9,597 -3,178 2,062 2,062 2,062 2,910 2,910 2,910 3,573 3,573 3,573 3,013 3,013 3,013 1,051 1,051 1,051 2,864 2,864 2,864 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /14 9 /16 9 /16 9 /16 9 /16 9 /10 9 /10 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 7 /17 9 /14 9 /14 9 /16 9 /16 9 /14 9 /14 9 /16 9 /16 10 /15 10 /15 7 /18 7 /18 76 76 77 77 77 77 77 77 67 67 67 77 77 77 75 75 75 75 75 75 76 76 76 75 75 77 77 77 77 77 77 77 77 77 77 77 77 80 80 80 73 73 73 65 65 67 67 67 67 67 67 61 61 61 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 67 67 67 66 66 66 67 67 67 63 63 63 65 65 65 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 59.2 59.2 59.2 56.9 56.9 56.9 55.6 55.6 55.6 56.5 56.5 56.5 58.3 58.3 58.3 54.7 54.7 54.7 Coil Airflow cfm Coil Sensible Load Btu/h 451 451 357 357 357 102 102 102 60 60 60 41 41 41 105 105 105 77 77 77 7 7 7 1,200 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 -191 -191 3,033 3,033 3,033 -43 -43 -43 -25 -25 -25 -17 -17 -17 -44 -44 -44 -32 -32 -32 -3 -3 -3 12,882 0 36,547 36,547 36,547 44,525 44,525 44,525 40,050 40,050 40,050 54,574 54,574 54,574 40,936 40,936 40,936 38,829 38,829 38,829 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6,959 6,959 6,959 7,908 7,908 7,908 7,147 7,147 7,147 7,605 7,605 7,605 1,195 1,195 1,195 5,336 5,336 5,336 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 41 of 100 SPACE Floor Area ft² System Zone Room spc_sp_61 Zone - 270 Zone - 270 spc_sp_62 Zone - 271 Zone - 271 spc_sp_63 Zone - 272 Zone - 272 spc_sp_64 Zone - 273 Zone - 273 spc_sp_65 Zone - 274 Zone - 274 spc_sp_66 Zone - 275 Zone - 275 spc_sp_67 Zone - 276 Zone - 276 spc_sp_68 Zone - 277 Zone - 277 spc_sp_69 Zone - 278 Zone - 278 spc_sp_70 Zone - 279 Zone - 279 spc_sp_38 Zone - 280 Zone - 280 spc_sp_39 Zone - 281 Zone - 281 spc_sp_40 Zone - 282 Zone - 282 spc_sp_41 Zone - 283 Zone - 283 spc_sp_42 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 378 9 /11 378 378 9 /11 485 6 /10 485 485 6 /10 678 10 /16 678 678 10 /16 822 7 /18 822 822 7 /18 628 9 /11 628 628 9 /11 2,082 9 /16 2,082 2,082 9 /16 2,169 7 /17 2,169 2,169 7 /17 2,777 7 /17 2,777 2,777 7 /17 3,084 7 /17 3,084 3,084 7 /17 211 6 /10 211 211 6 /10 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 1,408 9 /16 1,408 1,408 9 /16 1,392 9 /16 1,392 1,392 9 /16 972 9 /16 70 70 70 65 65 65 79 79 79 73 73 73 70 70 70 77 77 77 75 75 75 75 75 75 75 75 75 65 65 65 77 77 77 77 77 77 77 77 77 77 77 77 77 63 63 63 58 58 58 64 64 64 65 65 65 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.5 57.5 57.5 55.5 55.5 55.5 56.3 56.3 56.3 51.4 51.4 51.4 56.1 56.1 56.1 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.5 52.5 52.5 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 28,760 28,760 28,760 11,994 11,994 11,994 23,923 23,923 23,923 13,067 13,067 13,067 26,223 26,223 26,223 53,398 53,398 53,398 48,975 48,975 48,975 57,415 57,415 57,415 55,454 55,454 55,454 13,285 13,285 13,285 28,858 28,858 28,858 28,858 28,858 28,858 35,056 35,056 35,056 34,765 34,765 34,765 27,232 1,212 1,212 1,212 1,286 1,286 1,286 1,878 1,878 1,878 2,838 2,838 2,838 2,011 2,011 2,011 7,723 7,723 7,723 7,128 7,128 7,128 9,122 9,122 9,122 10,121 10,121 10,121 559 559 559 3,036 3,036 3,036 3,036 3,036 3,036 5,223 5,223 5,223 5,163 5,163 5,163 3,608 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /11 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 9 /12 9 /12 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 70 70 70 76 76 76 77 77 77 75 75 75 73 73 73 77 77 77 75 75 75 75 75 75 76 76 76 65 65 65 77 77 77 77 77 77 77 77 77 77 77 77 77 63 63 63 66 66 66 67 67 67 66 66 66 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 57.5 57.5 57.5 58.6 58.6 58.6 56.4 56.4 56.4 51.9 51.9 51.9 56.2 56.2 56.2 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.7 52.7 52.7 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 Coil Airflow cfm Coil Sensible Load Btu/h 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 32,826 32,826 32,826 16,489 16,489 16,489 33,562 33,562 33,562 23,710 23,710 23,710 32,978 32,978 32,978 80,411 80,411 80,411 79,136 79,136 79,136 95,193 95,193 95,193 95,526 95,526 95,526 14,677 14,677 14,677 41,068 41,068 41,068 41,068 41,068 41,068 53,076 53,076 53,076 52,584 52,584 52,584 39,863 Coil Latent Load Btu/h 1,973 1,973 1,973 3,057 3,057 3,057 4,742 4,742 4,742 5,052 5,052 5,052 3,012 3,012 3,012 14,541 14,541 14,541 13,382 13,382 13,382 17,116 17,116 17,116 19,369 19,369 19,369 694 694 694 5,720 5,720 5,720 5,720 5,720 5,720 9,832 9,832 9,832 9,719 9,719 9,719 6,796 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 42 of 100 SPACE Floor Area ft² System Zone Room Zone - 284 Zone - 284 spc_sp_43 Zone - 285 Zone - 285 spc_sp_44 Zone - 286 Zone - 286 spc_sp_45 Zone - 287 Zone - 287 spc_sp_46 Zone - 288 Zone - 288 spc_sp_47 Zone - 289 Zone - 289 spc_sp_48 Zone - 290 Zone - 290 spc_sp_49 Zone - 291 Zone - 291 spc_sp_50 Zone - 292 Zone - 292 spc_sp_51 Zone - 293 Zone - 293 spc_sp_52 Zone - 294 Zone - 294 spc_sp_53 Zone - 295 Zone - 295 spc_sp_54 Zone - 296 Zone - 296 spc_sp_22 Zone - 297 Zone - 297 spc_sp_23 Zone - 298 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 972 972 1,408 1,408 1,408 826 826 826 914 914 914 907 907 907 869 869 869 869 869 869 835 835 835 893 893 893 737 737 737 1,061 1,061 1,061 1,064 1,064 1,064 1,061 1,061 1,061 1,044 1,044 1,044 1,082 1,082 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /15 9 /16 9 /16 9 /16 9 /16 7 /18 7 /18 7 /18 7/18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 10 /13 10 /13 10 /13 10 /13 9 /12 9 /12 7 /18 7 /18 7 /18 77 77 80 80 80 77 77 77 77 77 77 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 77 77 77 77 77 77 73 73 73 73 73 73 73 73 67 67 63 63 63 67 67 67 67 67 67 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 59 59 59 59 59 59 63 63 63 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.0 54.0 56.0 56.0 56.0 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 53.9 53.9 53.9 54.1 54.1 54.1 54.2 54.2 54.2 54.0 54.0 54.0 55.0 55.0 55.0 58.7 58.7 58.7 58.7 58.7 58.7 54.7 54.7 54.7 53.1 53.1 53.1 53.4 53.4 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 27,232 27,232 38,302 38,302 38,302 27,994 27,994 27,994 26,885 26,885 26,885 25,235 25,235 25,235 22,064 22,064 22,064 22,983 22,983 22,983 22,536 22,536 22,536 23,576 23,576 23,576 24,944 24,944 24,944 24,323 24,323 24,323 24,374 24,374 24,374 27,301 27,301 27,301 22,248 22,248 22,248 24,586 24,586 3,608 3,608 3,626 3,626 3,626 3,067 3,067 3,067 3,393 3,393 3,393 3,140 3,140 3,140 3,008 3,008 3,008 3,009 3,009 3,009 2,891 2,891 2,891 3,092 3,092 3,092 2,553 2,553 2,553 1,935 1,935 1,935 1,941 1,941 1,941 3,272 3,272 3,272 3,609 3,609 3,609 3,741 3,741 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 9 /14 9 /14 9 /14 9 /14 9 /14 9 /14 7 /17 7 /17 7 /17 77 77 77 77 77 77 77 77 77 77 77 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 77 77 77 77 77 77 77 77 77 75 75 75 75 75 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 54.0 54.0 56.2 56.2 56.2 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 54.1 54.1 54.1 54.2 54.2 54.2 54.3 54.3 54.3 54.2 54.2 54.2 55.0 55.0 55.0 59.2 59.2 59.2 59.2 59.2 59.2 55.7 55.7 55.7 53.6 53.6 53.6 53.6 53.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 39,863 39,863 56,744 56,744 56,744 39,442 39,442 39,442 38,892 38,892 38,892 38,103 38,103 38,103 33,592 33,592 33,592 34,897 34,897 34,897 34,003 34,003 34,003 35,816 35,816 35,816 36,470 36,470 36,470 34,741 34,741 34,741 34,831 34,831 34,831 37,314 37,314 37,314 35,254 35,254 35,254 38,640 38,640 Coil Latent Load Btu/h 6,796 6,796 9,854 9,854 9,854 5,777 5,777 5,777 6,391 6,391 6,391 5,604 5,604 5,604 5,367 5,367 5,367 5,370 5,370 5,370 5,157 5,157 5,157 5,519 5,519 5,519 4,557 4,557 4,557 6,531 6,531 6,531 6,553 6,553 6,553 6,544 6,544 6,544 6,433 6,433 6,433 6,671 6,671 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 43 of 100 SPACE Floor Area ft² System Zone Room Zone - 298 spc_sp_24 Zone - 299 Zone - 299 spc_sp_25 Zone - 300 Zone - 300 spc_sp_26 Zone - 301 Zone - 301 spc_sp_27 Zone - 302 Zone - 302 spc_sp_28 Zone - 303 Zone - 303 spc_sp_29 Zone - 304 Zone - 304 spc_sp_30 Zone - 305 Zone - 305 spc_sp_31 Zone - 306 Zone - 306 spc_sp_32 Zone - 307 Zone - 307 spc_sp_33 Zone - 308 Zone - 308 spc_sp_34 Zone - 309 Zone - 309 spc_sp_35 Zone - 310 Zone - 310 spc_sp_36 Zone - 311 Zone - 311 spc_sp_37 Zone - 312 Zone - 312 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 1,082 7 /18 1,074 7 /18 1,074 1,074 7 /18 955 7 /18 955 955 7 /18 995 9 /16 995 995 9 /16 894 7 /17 894 894 7 /17 1,063 10 /15 1,063 1,063 10 /15 684 6/10 684 684 6 /10 2,070 9 /16 2,070 2,070 9 /16 1,251 9 /16 1,251 1,251 9 /16 1,251 7 /17 1,251 1,251 7 /17 1,525 9 /16 1,525 1,525 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 73 73 73 73 73 73 73 77 77 77 75 75 75 80 80 80 65 65 65 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 65 65 65 65 65 65 65 67 67 67 66 66 66 63 63 63 58 58 58 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 53.4 53.1 53.1 53.1 53.6 53.6 53.6 55.1 55.1 55.1 55.0 55.0 55.0 56.6 56.6 56.6 55.8 55.8 55.8 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 24,586 22,945 22,945 22,945 22,834 22,834 22,834 37,026 37,026 37,026 29,118 29,118 29,118 36,090 36,090 36,090 18,202 18,202 18,202 52,942 52,942 52,942 35,189 35,189 35,189 31,103 31,103 31,103 60,677 60,677 60,677 29,082 29,082 29,082 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 3,741 3,711 3,711 3,711 3,304 3,304 3,304 3,697 3,697 3,697 2,943 2,943 2,943 2,737 2,737 2,737 1,813 1,813 1,813 7,679 7,679 7,679 4,645 4,645 4,645 4,115 4,115 4,115 5,660 5,660 5,660 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 75 75 75 75 75 75 75 77 77 77 75 75 75 77 77 77 76 76 76 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 66 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 53.6 53.6 53.6 53.6 53.9 53.9 53.9 55.1 55.1 55.1 55.0 55.0 55.0 56.7 56.7 56.7 60.6 60.6 60.6 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 Coil Airflow cfm Coil Sensible Load Btu/h 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 38,640 36,369 36,369 36,369 35,270 35,270 35,270 51,628 51,628 51,628 42,996 42,996 42,996 51,414 51,414 51,414 22,226 22,226 22,226 79,873 79,873 79,873 52,725 52,725 52,725 48,027 48,027 48,027 82,120 82,120 82,120 41,372 41,372 41,372 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 Coil Latent Load Btu/h 6,671 6,615 6,615 6,615 5,894 5,894 5,894 6,966 6,966 6,966 5,530 5,530 5,530 7,439 7,439 7,439 4,311 4,311 4,311 14,458 14,458 14,458 8,749 8,749 8,749 7,730 7,730 7,730 10,664 10,664 10,664 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 44 of 100 SPACE Floor Area ft² System Zone Room spc_sp_7 Zone - 313 Zone - 313 spc_sp_8 Zone - 314 Zone - 314 spc_sp_9 Zone - 315 Zone - 315 spc_sp_10 Zone - 316 Zone - 316 spc_sp_11 Zone - 317 Zone - 317 spc_sp_12 Zone - 318 Zone - 318 spc_sp_13 Zone - 319 Zone - 319 spc_sp_14 Zone - 320 Zone - 320 spc_sp_15 Zone - 321 Zone - 321 spc_sp_16 Zone - 322 Zone - 322 spc_sp_17 Zone - 323 Zone - 323 spc_sp_18 Zone - 324 Zone - 324 spc_sp_19 Zone - 325 Zone - 325 spc_sp_20 Zone - 326 Zone - 326 spc_sp_21 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 290 290 290 442 442 442 2,070 2,070 2,070 1,103 1,103 1,103 915 915 915 3,084 3,084 3,084 437 437 437 344 344 344 231 231 231 382 382 382 358 358 358 1,082 1,082 1,082 960 960 960 1,040 1,040 1,040 1,040 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 6 /18 6 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 6 /18 6 /18 7 /18 7 /18 9 /12 9 /12 6 /10 6 /10 6 /9 6 /9 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 70 70 70 70 70 70 75 75 75 76 76 76 76 76 76 75 75 75 70 70 70 73 73 73 73 73 73 65 65 65 62 62 62 73 73 73 73 73 73 73 73 73 73 63 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 65 65 65 63 63 63 58 58 58 58 58 58 65 65 65 65 65 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.0 57.0 57.0 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 56.2 56.2 56.2 56.0 56.0 56.0 53.0 53.0 53.0 53.2 53.2 53.2 54.2 54.2 54.2 53.1 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 17,557 17,557 17,557 19,208 19,208 19,208 47,533 47,533 47,533 12,788 12,788 12,788 10,607 10,607 10,607 60,225 60,225 60,225 28,451 28,451 28,451 19,387 19,387 19,387 8,323 8,323 8,323 11,887 11,887 11,887 10,175 10,175 10,175 22,813 22,813 22,813 20,987 20,987 20,987 28,726 28,726 28,726 22,182 929 929 929 1,375 1,375 1,375 6,804 6,804 6,804 3,865 3,865 3,865 3,206 3,206 3,206 10,127 10,127 10,127 1,358 1,358 1,358 1,192 1,192 1,192 713 713 713 1,013 1,013 1,013 951 951 951 3,739 3,739 3,739 3,318 3,318 3,318 3,598 3,598 3,598 3,594 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /12 9 /12 7 /18 7 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /12 9 /12 7 /15 7 /15 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 73 73 73 73 73 73 75 75 75 76 76 76 76 76 76 75 75 75 73 73 73 73 73 73 73 73 73 77 77 77 76 76 76 75 75 75 75 75 75 75 75 75 75 63 63 63 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 57.6 57.6 57.6 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 60.1 60.1 60.1 57.9 57.9 57.9 53.5 53.5 53.5 53.7 53.7 53.7 54.4 54.4 54.4 53.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 20,529 20,529 20,529 26,244 26,244 26,244 76,434 76,434 76,434 26,279 26,279 26,279 21,797 21,797 21,797 101,628 101,628 101,628 36,070 36,070 36,070 25,678 25,678 25,678 11,070 11,070 11,070 14,327 14,327 14,327 14,201 14,201 14,201 36,302 36,302 36,302 32,911 32,911 32,911 43,793 43,793 43,793 35,131 Coil Latent Load Btu/h 1,393 1,393 1,393 2,856 2,856 2,856 12,774 12,774 12,774 6,912 6,912 6,912 5,733 5,733 5,733 18,995 18,995 18,995 2,820 2,820 2,820 2,221 2,221 2,221 1,110 1,110 1,110 2,357 2,357 2,357 2,261 2,261 2,261 6,665 6,665 6,665 5,915 5,915 5,915 6,420 6,420 6,420 6,406 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 45 of 100 SPACE Floor Area ft² System Zone Room Zone - 327 Zone - 327 spc_sp_1 Zone - 328 Zone - 328 spc_sp_2 Zone - 329 Zone - 329 spc_sp_3 Zone - 330 Zone - 330 spc_sp_4 Zone - 331 Zone - 331 spc_sp_5 Zone - 332 Zone - 332 spc_sp_6 Zone - 333 Zone - 333 Child Cntr 2 Zone - 359 Zone - 359 Child Cntr 3 Zone - 360 Zone - 360 Child Cntr 1 Zone - 361 Zone - 361 Portopia HP Portopia HP spc_SS 141/142 Office_0 Zone - 012 Zone - 012 spc_SS 144 Office C_0 Zone - 013 Zone - 013 spc_SS 160B-D_0 Zone - 014 Zone - 014 spc_PS 160A Storage_0 Zone - 015 Zone - 015 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,040 1,040 1,272 1,272 1,272 1,074 1,074 1,074 999 999 999 1,613 1,613 1,613 664 664 664 1,956 1,956 1,956 211 211 211 211 211 211 211 211 211 75,038 75,038 313 313 313 168 168 168 0 0 0 102 102 102 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 10 /15 10 /15 10 /16 10 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 6 /9 10 /15 10 /15 9 /11 9 /11 73 73 77 77 77 73 73 73 73 73 73 80 80 80 79 79 79 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 62 62 80 80 80 70 70 70 65 65 67 67 67 65 65 65 65 65 65 63 63 63 64 64 64 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 58 58 63 63 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Supply Dry Bulb °F 53.1 53.1 48.6 48.6 48.6 53.1 53.1 53.1 54.3 54.3 54.3 55.5 55.5 55.5 57.1 57.1 57.1 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 54.9 54.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 32 32 0 0 0 27 27 27 22,182 22,182 15,648 15,648 15,648 22,945 22,945 22,945 28,019 28,019 28,019 37,433 37,433 37,433 31,843 31,843 31,843 22,688 22,688 22,688 13,285 13,285 13,285 13,285 13,285 13,285 12,931 12,931 12,931 2,026,697 1,809,600 0 0 0 0 0 0 0 0 0 0 0 0 3,594 3,594 4,707 4,707 4,707 3,711 3,711 3,711 3,457 3,457 3,457 4,151 4,151 4,151 1,840 1,840 1,840 6,857 6,857 6,857 559 559 559 559 559 559 370 370 370 246,137 246,507 181 181 181 97 97 97 0 0 0 -2 -2 -2 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 6 /9 9 /16 9 /16 9 /11 9 /11 75 75 76 76 76 75 75 75 75 75 75 77 77 77 77 77 77 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 62 62 77 77 77 70 70 70 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 58 58 67 67 67 63 63 63 53.6 53.6 48.8 48.8 48.8 53.6 53.6 53.6 54.5 54.5 54.5 56.4 56.4 56.4 57.3 57.3 57.3 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 55.1 56.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Coil Airflow cfm 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 32 32 0 0 0 27 27 27 Coil Sensible Load Btu/h 35,131 35,131 31,358 31,358 31,358 36,369 36,369 36,369 42,495 42,495 42,495 56,782 56,782 56,782 43,282 43,282 43,282 46,620 46,620 46,620 14,677 14,677 14,677 14,677 14,677 14,677 14,524 14,524 14,524 3,006,774 2,862,181 0 0 0 0 0 0 0 0 0 0 0 0 Coil Latent Load Btu/h 6,406 6,406 7,970 7,970 7,970 6,615 6,615 6,615 6,169 6,169 6,169 11,281 11,281 11,281 4,645 4,645 4,645 12,262 12,262 12,262 694 694 694 694 694 694 460 460 460 480,065 462,701 0 0 0 0 0 0 0 0 0 0 0 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 46 of 100 SPACE Floor Area ft² System Zone Room spc_SS 160 Class C_0 Zone - 016 Zone - 016 spc_SS 162 Class_0 Zone - 017 Zone - 017 spc_PS 112 Office C_0 Zone - 018 Zone - 018 spc_PS 111-115 Office C_0 Zone - 019 Zone - 019 spc_PS Lecture 117 C_0 Zone - 020 Zone - 020 spc_PS Lecture FC-4C_0 Zone - 021 Zone - 021 spc_PS 120-128 Class_0 Zone - 022 Zone - 022 spc_PS Class 121/122_0 Zone - 023 Zone - 023 spc_PS 130 Auditorium C_0 Zone - 024 Zone - 024 PS Fan Coil Htg Only PS Fan Coil Htg Only spc_SS 171-173, 178 Office C_0 Zone - 037 Zone - 037 spc_SS 135 Office_0 Zone - 038 Zone - 038 spc_SS Corridor 120 C_0 Zone - 039 Zone - 039 spc_SS 180 Worm Rm VAV-20_0 Zone - 040 Zone - 040 spc_SS 110C Wrk Rm C_0 Zone - 041 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 565 565 565 967 967 967 215 215 215 602 602 602 1,126 1,126 1,126 1,036 1,036 1,036 886 886 886 695 695 695 1,413 1,413 1,413 8,090 8,090 561 561 561 92 92 92 1,787 1,787 1,787 326 326 326 766 766 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 10 /16 10 /16 9 /17 9 /17 7 /18 7 /18 6 /9 6 /9 7 /16 7 /16 10 /16 10 /16 10 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 6 /9 70 70 70 70 70 70 79 79 79 79 79 79 76 76 76 73 73 73 62 62 62 76 76 76 79 79 79 79 79 76 76 76 76 76 76 76 76 76 79 79 79 62 62 63 63 63 63 63 63 64 64 64 64 64 64 67 67 67 65 65 65 58 58 58 66 66 66 64 64 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 274 274 274 45 45 45 378 378 378 616 616 616 1,984 1,984 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,317 5,317 5,317 875 875 875 7,342 7,342 7,342 11,961 11,961 11,961 38,530 38,530 836 836 836 1,430 1,430 1,430 157 157 157 435 435 435 1,356 1,356 1,356 1,374 1,374 1,374 1,392 1,392 1,392 992 992 992 2,191 2,191 2,191 10,439 7,971 1,465 1,465 1,465 241 241 241 2,794 2,794 2,794 902 902 902 2,030 2,030 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 7 /18 7 /18 7 /9 7 /9 7 /16 7 /16 9 /16 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 7 /10 70 70 70 70 70 70 79 79 79 76 76 76 76 76 76 73 73 73 64 64 64 76 76 76 77 77 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 67 67 63 63 63 63 63 63 64 64 64 67 67 67 67 67 67 65 65 65 59 59 59 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 60 60 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 268 268 268 44 44 44 364 364 364 593 593 593 1,874 1,874 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,089 5,089 5,089 838 838 838 5,425 5,425 5,425 13,863 13,863 13,863 40,338 40,338 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2,917 2,917 2,917 480 480 480 4,022 4,022 4,022 2,276 2,276 2,276 2,929 2,929 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 47 of 100 SPACE System Zone Room Zone - 041 Block spc_SS 110 Wrk Rm/Office C_0 Peak Zone - 042 Peak Zone - 042 Block Peak spc_SS 100 100H 111H Main Lobby C_0 Zone - 043 Peak Zone - 043 Block spc_SS 150 Wrk Rm C_0 Peak Zone - 044 Peak Zone - 044 Block spc_SS 177-179 Office_0 Peak Zone - 045 Peak Zone - 045 Block spc_SS Wrk Rm1 V-19_0 Peak Zone - 046 Peak Zone - 046 Block spc_SS 120-124 C_0 Peak Zone - 047 Peak Zone - 047 Block spc_SS 135-139 Office C_0 Peak Zone - 048 Peak Zone - 048 Block spc_SS 140 Wrk Rm C_0 Peak Zone - 049 Peak Zone - 049 Block spc_SS 125-129_0 Peak Zone - 050 Peak Zone - 050 Block spc_SS 230B Office C_0 Peak Zone - 051 Peak Zone - 051 Block spc_SS 214 Office C_0 Peak Zone - 052 Peak Zone - 052 Block spc_SS 282 Wrk Rm C_0 Peak Zone - 053 Peak Zone - 053 Block spc_SS 280D Office_0 Peak Zone - 054 Peak Zone - 054 Block spc_SS 280A-C C_0 Peak Zone - 055 Peak Zone - 055 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 766 1,420 1,420 1,420 37 37 37 301 301 301 635 635 635 207 207 207 703 703 703 586 586 586 848 848 848 642 642 642 285 285 285 130 130 130 136 136 136 154 154 154 459 459 459 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /9 9 /17 9 /17 7 /18 7 /18 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 6/9 6 /9 7 /16 7 /16 9 /16 9 /16 6 /18 6 /18 6 /18 6 /18 10 /16 10 /16 10 /16 10 /16 7 /17 7 /17 9 /11 9 /11 62 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 62 62 62 76 76 76 77 77 77 70 70 70 70 70 70 79 79 79 79 79 79 75 75 75 70 70 70 58 67 67 67 65 65 65 66 66 66 66 66 66 66 66 66 58 58 58 66 66 66 67 67 67 63 63 63 63 63 63 64 64 64 64 64 64 66 66 66 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,984 844 844 844 348 348 348 167 167 167 310 310 310 115 115 115 1,253 1,253 1,253 286 286 286 545 545 545 1,766 1,766 1,766 526 526 526 623 623 623 1,441 1,441 1,441 75 75 75 1,255 1,255 1,255 38,530 16,389 16,389 16,389 6,755 6,755 6,755 3,248 3,248 3,248 6,019 6,019 6,019 2,238 2,238 2,238 24,336 24,336 24,336 5,555 5,555 5,555 10,576 10,576 10,576 34,294 34,294 34,294 10,214 10,214 10,214 12,096 12,096 12,096 27,981 27,981 27,981 1,450 1,450 1,450 24,365 24,365 24,365 2,030 4,101 4,101 4,101 63 63 63 1,044 1,044 1,044 1,658 1,658 1,658 719 719 719 1,862 1,862 1,862 1,530 1,530 1,530 3,146 3,146 3,146 1,992 1,992 1,992 572 572 572 244 244 244 378 378 378 408 408 408 1,469 1,469 1,469 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /10 9 /17 9 /17 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /10 7 /10 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /11 9 /11 67 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 67 67 67 76 76 76 77 77 77 73 73 73 73 73 73 77 77 77 77 77 77 75 75 75 70 70 70 60 67 67 67 65 65 65 67 67 67 67 67 67 67 67 67 60 60 60 67 67 67 67 67 67 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 63 63 63 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,874 844 844 844 348 348 348 165 165 165 304 304 304 114 114 114 1,181 1,181 1,181 280 280 280 545 545 545 1,745 1,745 1,745 522 522 522 610 610 610 1,360 1,360 1,360 75 75 75 1,255 1,255 1,255 40,338 16,959 16,959 16,959 8,572 8,572 8,572 3,134 3,134 3,134 5,761 5,761 5,761 2,159 2,159 2,159 25,288 25,288 25,288 5,317 5,317 5,317 10,803 10,803 10,803 37,007 37,007 37,007 11,167 11,167 11,167 14,956 14,956 14,956 32,179 32,179 32,179 3,723 3,723 3,723 28,088 28,088 28,088 Coil Latent Load Btu/h 2,929 7,387 7,387 7,387 90 90 90 2,099 2,099 2,099 3,302 3,302 3,302 1,446 1,446 1,446 2,687 2,687 2,687 3,047 3,047 3,047 5,923 5,923 5,923 4,132 4,132 4,132 1,239 1,239 1,239 651 651 651 953 953 953 703 703 703 2,386 2,386 2,386 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 48 of 100 SPACE System Zone Room spc_SS 272 Wrk Rm C_0 Peak Zone - 056 Peak Zone - 056 Block spc_SS 270C/D Office_0 Peak Zone - 057 Peak Zone - 057 Block spc_SS 111H Hall_0 Peak Zone - 058 Peak Zone - 058 Block spc_SS 110G/H Offices C_0 Peak Zone - 059 Peak Zone - 059 Block spc_SS 111A Office C_0 Peak Zone - 060 Peak Zone - 060 Block spc_SS 242 Wrk Rm C_0 Peak Zone - 061 Peak Zone - 061 Block spc_SS 240L Office C_0 Peak Zone - 062 Peak Zone - 062 Block spc_SS 240H Office_0 Peak Zone - 063 Peak Zone - 063 Block spc_SS 240F/J Office_0 Peak Zone - 064 Peak Zone - 064 Block spc_SS 240-260A Wrk Rm C_0 Peak Zone - 065 Peak Zone - 065 Block spc_SS 202/250B Office_0 Peak Zone - 066 Peak Zone - 066 Block spc_SS 250 Wrk Rm C_0 Peak Zone - 067 Peak Zone - 067 Block spc_SS 251 Wrk Rm C_0 Peak Zone - 068 Peak Zone - 068 Block Peak spc_SS 230H, 200-201, 251H, 272H_0 Zone - 069 Peak Zone - 069 Block spc_SS 210/211 Wrk Rm C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 778 778 778 287 287 287 397 397 397 269 269 269 216 216 216 642 642 642 149 149 149 181 181 181 274 274 274 865 865 865 214 214 214 0 0 0 388 388 388 4,383 4,383 4,383 308 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /12 9 /12 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 10 /16 10 /16 7 /16 7 /16 6 /9 6 /9 9 /12 9 /12 7 /16 7 /16 7 /15 70 70 70 73 73 73 73 73 73 76 76 76 76 76 76 79 79 79 75 75 75 76 76 76 75 75 75 79 79 79 76 76 76 62 62 62 73 73 73 76 76 76 77 63 63 63 63 63 63 65 65 65 66 66 66 66 66 66 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 66 66 66 58 58 58 63 63 63 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,090 1,090 1,090 379 379 379 175 175 175 131 131 131 105 105 105 406 406 406 73 73 73 89 89 89 133 133 133 1,257 1,257 1,257 104 104 104 16 16 16 387 387 387 2,716 2,716 2,716 171 21,179 21,179 21,179 7,364 7,364 7,364 3,399 3,399 3,399 2,552 2,552 2,552 2,048 2,048 2,048 7,890 7,890 7,890 1,410 1,410 1,410 1,719 1,719 1,719 2,589 2,589 2,589 24,416 24,416 24,416 2,028 2,028 2,028 304 304 304 7,518 7,518 7,518 52,749 52,749 52,749 3,325 2,489 2,489 2,489 627 627 627 612 612 612 703 703 703 564 564 564 1,777 1,777 1,777 397 397 397 474 474 474 728 728 728 2,394 2,394 2,394 559 559 559 0 0 0 1,195 1,195 1,195 15,399 15,399 15,399 1,069 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /13 9 /13 9 /13 9 /13 7 /18 7 /18 9 /17 9 /17 9 /17 9 /17 7 /16 7 /16 7 /17 7 /17 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 9 /17 9 /17 7 /10 7 /10 9 /12 9 /12 7 /16 7 /16 7 /16 75 75 75 75 75 75 73 73 73 76 76 76 76 76 76 76 76 76 75 75 75 76 76 76 75 75 75 77 77 77 76 76 76 67 67 67 73 73 73 76 76 76 76 65 65 65 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 60 60 60 63 63 63 66 66 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 918 918 918 357 357 357 175 175 175 129 129 129 103 103 103 394 394 394 73 73 73 87 87 87 133 133 133 1,221 1,221 1,221 102 102 102 15 15 15 387 387 387 2,716 2,716 2,716 171 25,380 25,380 25,380 10,543 10,543 10,543 3,469 3,469 3,469 2,443 2,443 2,443 1,960 1,960 1,960 17,212 17,212 17,212 3,620 3,620 3,620 1,646 1,646 1,646 6,646 6,646 6,646 38,964 38,964 38,964 1,941 1,941 1,941 312 312 312 8,858 8,858 8,858 113,463 113,463 113,463 7,815 Coil Latent Load Btu/h 4,471 4,471 4,471 973 973 973 790 790 790 1,400 1,400 1,400 1,123 1,123 1,123 4,042 4,042 4,042 684 684 684 943 943 943 1,256 1,256 1,256 6,040 6,040 6,040 1,112 1,112 1,112 0 0 0 1,856 1,856 1,856 27,598 27,598 27,598 1,937 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 49 of 100 SPACE Floor Area ft² System Zone Room Zone - 070 Zone - 070 spc_SS 230F Office C_0 Zone - 071 Zone - 071 spc_SS Wrk Rm 230 C_0 Zone - 072 Zone - 072 spc_SS 230C-E Office_0 Zone - 073 Zone - 073 spc_SS 240B Wrk Rm C_0 Zone - 074 Zone - 074 spc_SS 181 Comp Rm C_0 Zone - 075 Zone - 075 spc_SS 182 Comp Rm C_0 Zone - 076 Zone - 076 Stdnt Srv VAV Stdnt Srv VAV Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 308 308 7 /15 180 6 /18 180 180 6 /18 987 7 /16 987 987 7 /16 630 6 /18 630 630 6 /18 240 10 /16 240 240 10 /16 854 7 /18 854 854 7/18 863 9 /11 863 863 9 /11 23,178 23,178 7 /17 77 77 70 70 70 76 76 76 70 70 70 79 79 79 73 73 73 70 70 70 75 75 66 66 63 63 63 66 66 66 63 63 63 64 64 64 65 65 65 63 63 63 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 171 171 330 330 330 550 550 550 1,887 1,887 1,887 607 607 607 2,223 2,223 2,223 2,317 2,317 2,317 27,996 21,892 3,325 3,325 6,408 6,408 6,408 10,680 10,680 10,680 36,641 36,641 36,641 11,782 11,782 11,782 43,184 43,184 43,184 45,011 45,011 45,011 543,738 425,196 1,069 1,069 360 360 360 3,468 3,468 3,468 1,262 1,262 1,262 663 663 663 2,471 2,471 2,471 2,243 2,243 2,243 66,071 67,555 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 7 /18 7 /18 9 /11 9 /11 7 /17 76 76 73 73 73 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 75 75 66 66 65 65 65 66 66 66 65 65 65 67 67 67 65 65 65 63 63 63 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 171 171 326 326 326 550 550 550 1,854 1,854 1,854 595 595 595 2,223 2,223 2,223 2,317 2,317 2,317 27,337 21,892 7,815 7,815 9,430 9,430 9,430 25,113 25,113 25,113 48,827 48,827 48,827 15,938 15,938 15,938 45,640 45,640 45,640 49,534 49,534 49,534 713,169 592,652 1,937 1,937 781 781 781 6,215 6,215 6,215 2,736 2,736 2,736 1,674 1,674 1,674 4,381 4,381 4,381 3,536 3,536 3,536 122,218 121,687 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 50 of 100 SPACE Floor Area ft² System Zone Room OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 58.1 58.1 58.1 51.6 51.6 51.6 55.0 55.0 55.0 56.7 56.7 56.7 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.8 57.8 57.8 52.5 52.5 52.5 69.6 69.6 69.6 57.6 57.6 54.7 54.7 54.7 54.6 54.6 54.6 49.8 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 19,718 19,718 19,718 27,717 27,717 27,717 4,324 4,324 4,324 8,470 8,470 8,470 10,677 10,677 10,677 33,208 33,208 33,208 3,217 3,217 3,217 2,438 2,438 2,438 46,648 46,648 46,648 8,293 8,293 8,293 13,658 13,658 13,658 178,368 160,203 45,748 45,748 45,748 34,617 34,617 34,617 7,681 649 649 649 6,690 6,690 6,690 0 0 0 601 601 601 686 686 686 2,099 2,099 2,099 935 935 935 708 708 708 1,884 1,884 1,884 1,710 1,710 1,710 -741 -741 -741 15,221 21,247 6,031 6,031 6,031 4,790 4,790 4,790 2,079 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F Coil Airflow cfm Coil Sensible Load Btu/h 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 21,552 21,552 21,552 27,487 27,487 27,487 4,459 4,459 4,459 10,580 10,580 10,580 12,077 12,077 12,077 35,790 35,790 35,790 8,578 8,578 8,578 6,500 6,500 6,500 64,856 64,856 64,856 8,454 8,454 8,454 27,101 27,101 27,101 227,433 211,887 48,957 48,957 48,957 37,048 37,048 37,048 18,754 Coil Latent Load Btu/h Alternative 3 spc_A 121 Office UC_0 Zone - 077 Zone - 077 spc_A 130A Class? FC1-4_0 Zone - 078 Zone - 078 spc_A 237-241 Office C_0 Zone - 093 Zone - 093 spc_A 202A Office D_0 Zone - 094 Zone - 094 spc_A 202A Office B_0 Zone - 095 Zone - 095 spc_A 202A Office C_0 Zone - 096 Zone - 096 spc_A 201 Office C_0 Zone - 097 Zone - 097 spc_A 200H-J Office C_0 Zone - 098 Zone - 098 spc_A 200 Office C_0 Zone - 099 Zone - 099 spc_A 210A-B Stairs C_0 Zone - 100 Zone - 100 spc_A 121 Restroom FC05_0 Zone - 118 Zone - 118 Admin FC Admin FC spc_A 161/162 Class C_0 Zone - 091 Zone - 091 spc_A 160 Wrk Rm C_0 Zone - 092 Zone - 092 spc_A 236A/B Offices_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak 348 348 348 2,606 2,606 2,606 0 0 0 344 344 344 238 238 238 891 891 891 353 353 353 267 267 267 1,011 1,011 1,011 1,111 1,111 1,111 734 734 734 7,905 7,905 2,273 2,273 2,273 1,806 1,806 1,806 786 10 /16 10 /16 10 /15 10 /15 7 /16 7 /16 6 /10 6 /10 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 7 /18 7 /18 10 /16 10 /16 9 /16 6 /9 6 /9 6 /9 6 /9 7 /17 79 79 79 80 80 80 76 76 76 65 65 65 76 76 76 73 73 73 75 75 75 75 75 75 79 79 79 73 73 73 79 79 79 77 77 62 62 62 62 62 62 75 64 64 64 63 63 63 66 66 66 58 58 58 67 67 67 65 65 65 66 66 66 66 66 66 64 64 64 65 65 65 64 64 64 67 67 58 58 58 58 58 58 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 9 /16 7 /9 7 /9 7 /9 7 /9 7 /17 77 77 77 77 77 77 76 76 76 76 76 76 76 76 76 73 73 73 75 75 75 75 75 75 77 77 77 73 73 73 77 77 77 77 77 64 64 64 64 64 64 75 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 65 65 65 66 66 66 66 66 66 67 67 67 65 65 65 67 67 67 67 67 59 59 59 59 59 59 66 58.4 58.4 58.4 51.8 51.8 51.8 55.0 55.0 55.0 63.1 63.1 63.1 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.9 57.9 57.9 52.5 52.5 52.5 69.8 69.8 69.8 58.0 59.2 55.1 55.1 55.1 54.9 54.9 54.9 49.8 1,735 1,735 1,735 18,165 18,165 18,165 0 0 0 1,536 1,536 1,536 1,234 1,234 1,234 3,864 3,864 3,864 1,611 1,611 1,611 1,221 1,221 1,221 5,037 5,037 5,037 2,205 2,205 2,205 -7,656 -7,656 -7,656 28,952 30,207 9,347 9,347 9,347 7,420 7,420 7,420 3,579 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 51 of 100 SPACE Floor Area ft² System Zone Room Zone - 113 Zone - 113 spc_A 244/246 Office C_0 Zone - 114 Zone - 114 spc_A 242/243 Class C_0 Zone - 115 Zone - 115 spc_A 238-246 Offices C_0 Zone - 116 Zone - 116 spc_A 216/218 Office C_0 Zone - 117 Zone - 117 Admin Pckg AHU Admin Pckg AHU spc_A 277F Class_0 Zone - 079 Zone - 079 spc_A 279A Hall C_0 Zone - 080 Zone - 080 spc_A 278A Cond Stair_0 Zone - 081 Zone - 081 spc_A 170/171 Lobby C_0 Zone - 082 Zone - 082 spc_A 172 Wrk Rm C_0 Zone - 083 Zone - 083 spc_A Wrk Rm 173 C_0 Zone - 084 Zone - 084 spc_A 177 Comp C_1 Zone - 085 Zone - 085 spc_A 174-176 Data C_0 Zone - 086 Zone - 086 spc_A 177 Comp C_0 Zone - 087 Zone - 087 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 786 786 367 367 367 1,839 1,839 1,839 2,547 2,547 2,547 2,057 2,057 2,057 11,676 11,676 1,395 1,395 1,395 7,584 7,584 7,584 321 321 321 1,279 1,279 1,279 2,002 2,002 2,002 671 671 671 626 626 626 201 201 201 626 626 626 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 10 /16 10 /16 6 /10 6 /10 7 /17 7 /17 6 /10 6/18 6 /18 6 /10 6 /10 9 /11 9 /11 7 /18 7 /18 6 /9 6 /9 10 /15 10 /15 6 /9 6 /9 9 /16 9 /16 7 /16 7 /16 75 75 75 75 75 79 79 79 65 65 65 75 75 75 65 65 70 70 70 65 65 65 70 70 70 73 73 73 62 62 62 80 80 80 62 62 62 77 77 77 76 76 76 66 66 66 66 66 64 64 64 58 58 58 66 66 66 58 58 63 63 63 58 58 58 63 63 63 65 65 65 58 58 58 63 63 63 58 58 58 67 67 67 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 70.0 70.0 70.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.8 49.8 49.8 49.8 49.8 55.5 55.5 55.5 57.3 57.3 57.3 49.8 49.8 49.8 55.4 55.4 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,510 2,510 2,510 5,680 5,680 5,680 1,443 1,443 1,443 483 483 483 2,570 2,570 2,570 1,214 1,214 1,214 1,490 1,490 1,490 1,917 1,917 1,917 1,042 1,042 1,042 7,681 7,681 3,589 3,589 3,589 49,570 49,570 49,570 81,320 81,320 81,320 20,104 20,104 20,104 242,629 193,483 46,615 46,615 46,615 105,509 105,509 105,509 26,795 26,795 26,795 8,969 8,969 8,969 47,731 47,731 47,731 22,553 22,553 22,553 27,671 27,671 27,671 31,338 31,338 31,338 19,354 19,354 19,354 2,079 2,079 971 971 971 5,095 5,095 5,095 4,472 4,472 4,472 5,442 5,442 5,442 28,881 25,762 4,376 4,376 4,376 5,555 5,555 5,555 411 411 411 2,208 2,208 2,208 5,370 5,370 5,370 1,747 1,747 1,747 1,303 1,303 1,303 497 497 497 1,843 1,843 1,843 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 7 /17 7 /17 7 /16 7 /18 7 /18 7 /16 7 /16 9 /11 9 /11 7 /9 7 /9 7 /9 7 /9 9 /16 9 /16 7 /9 7 /9 9 /16 9 /16 9 /16 9 /16 75 75 75 75 75 77 77 77 76 76 76 75 75 75 76 76 73 73 73 76 76 76 70 70 70 64 64 64 64 64 64 77 77 77 64 64 64 77 77 77 77 77 77 66 66 66 66 66 67 67 67 66 66 66 66 66 66 66 66 65 65 65 66 66 66 63 63 63 59 59 59 59 59 59 67 67 67 59 59 59 67 67 67 67 67 67 49.8 49.8 49.8 49.8 49.8 55.6 55.6 55.6 64.0 64.0 64.0 49.8 49.8 49.8 58.0 60.0 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 Coil Airflow cfm Coil Sensible Load Btu/h 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,485 2,485 2,485 3,475 3,475 3,475 1,443 1,443 1,443 420 420 420 2,508 2,508 2,508 1,209 1,209 1,209 1,469 1,469 1,469 1,917 1,917 1,917 1,032 1,032 1,032 18,754 18,754 8,763 8,763 8,763 78,514 78,514 78,514 92,985 92,985 92,985 49,087 49,087 49,087 334,108 299,894 66,753 66,753 66,753 177,138 177,138 177,138 30,401 30,401 30,401 10,395 10,395 10,395 48,380 48,380 48,380 23,906 23,906 23,906 28,680 28,680 28,680 33,072 33,072 33,072 19,437 19,437 19,437 Coil Latent Load Btu/h 3,579 3,579 1,672 1,672 1,672 12,862 12,862 12,862 11,426 11,426 11,426 9,369 9,369 9,369 55,677 63,035 9,143 9,143 9,143 15,367 15,367 15,367 511 511 511 2,145 2,145 2,145 8,439 8,439 8,439 4,762 4,762 4,762 2,059 2,059 2,059 835 835 835 3,541 3,541 3,541 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 52 of 100 SPACE System Zone Room spc_A 179/178 Data C_0 Peak Zone - 088 Peak Zone - 088 Block spc_A 180E Com Lab C_0 Peak Zone - 089 Peak Zone - 089 Block spc_A 271-277 Office C_0 Peak Zone - 111 Peak Zone - 111 Block spc_A 277 Class_0 Peak Zone - 112 Peak Zone - 112 Block Peak Admin VAV Admin VAV Block spc_BC 237 Class_0 Peak Zone - 334 Peak Zone - 334 Block spc_BC 221 Lobby_0 Peak Zone - 335 Peak Zone - 335 Block spc_BC 222 Class_0 Peak Zone - 336 Peak Zone - 336 Block spc_215-219 Office_0 Peak Zone - 337 Peak Zone - 337 Block spc_BC 224 Class_0 Peak Zone - 338 Peak Zone - 338 Block spc_BC 2nd 226/228 Class_0 Peak Zone - 339 Peak Zone - 339 Block spc_BC 2nd 230 Class_0 Peak Zone - 340 Peak Zone - 340 Block spc_BC 115/116 Office_0 Peak Zone - 351 Peak Zone - 351 Block spc_BC Office 137/139/141/142_0 Peak Zone - 352 Peak Zone - 352 Block spc_BC 143 Office_0 Peak Zone - 353 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 339 339 339 951 951 951 2,656 2,656 2,656 0 0 0 18,650 18,650 166 166 166 120 120 120 196 196 196 262 262 262 146 146 146 281 281 281 187 187 187 155 155 155 103 103 103 123 123 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 9 /15 10 /14 10 /14 7 /16 7 /16 7 /18 7 /18 10 /16 10 /16 9 /11 9 /11 9 /10 9 /10 9 /17 9 /17 9 /12 9 /12 10 /16 10 /16 10 /16 76 76 76 80 80 80 75 75 75 80 80 80 78 78 79 79 79 76 76 76 73 73 73 79 79 79 70 70 70 67 67 67 76 76 76 73 73 73 79 79 79 79 79 66 66 66 63 63 63 66 66 66 63 63 63 66 66 62 62 62 66 66 66 65 65 65 64 64 64 63 63 63 61 61 61 67 67 67 63 63 63 64 64 64 64 64 70.0 70.0 70.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 71.7 71.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 57.5 57.5 57.5 57.3 57.3 57.3 57.1 57.1 57.1 57.5 57.5 57.5 55.6 55.6 55.6 56.0 56.0 56.0 57.2 57.2 57.2 56.1 56.1 56.1 51.8 51.8 51.8 58.7 58.7 2,037 2,037 2,037 2,646 2,646 2,646 1,344 1,344 1,344 4,175 4,175 4,175 28,551 22,316 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 237 237 237 38 38 38 797 797 33,300 33,300 33,300 49,154 49,154 49,154 24,971 24,971 24,971 77,551 77,551 77,551 521,509 407,618 6,259 6,259 6,259 3,956 3,956 3,956 14,583 14,583 14,583 10,595 10,595 10,595 5,091 5,091 5,091 11,008 11,008 11,008 15,364 15,364 15,364 4,204 4,204 4,204 848 848 848 11,800 11,800 771 771 771 1,906 1,906 1,906 7,134 7,134 7,134 0 0 0 33,121 44,638 375 375 375 194 194 194 681 681 681 491 491 491 468 468 468 889 889 889 658 658 658 340 340 340 192 192 192 231 231 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /19 9 /19 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /14 9 /14 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 9 /12 9 /12 9 /11 9 /11 9 /17 9 /17 9 /12 9 /12 9 /17 9 /17 10 /16 71 71 71 77 77 77 76 76 76 77 77 77 77 77 77 77 77 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 76 76 76 73 73 73 76 76 76 79 79 66 66 66 67 67 67 66 66 66 67 67 67 67 67 66 66 66 66 66 66 65 65 65 67 67 67 63 63 63 63 63 63 67 67 67 63 63 63 67 67 67 64 64 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 58.2 58.2 58.2 57.3 57.3 57.3 57.1 57.1 57.1 57.7 57.7 57.7 56.5 56.5 56.5 56.3 56.3 56.3 57.2 57.2 57.2 56.1 56.1 56.1 52.2 52.2 52.2 58.7 58.7 Coil Airflow cfm Coil Sensible Load Btu/h 2,008 2,008 2,008 2,644 2,644 2,644 1,337 1,337 1,337 4,061 4,061 4,061 26,008 22,285 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 237 237 237 38 38 38 797 797 33,409 33,409 33,409 51,546 51,546 51,546 32,823 32,823 32,823 77,838 77,838 77,838 651,278 557,619 7,849 7,849 7,849 5,195 5,195 5,195 17,225 17,225 17,225 12,759 12,759 12,759 6,331 6,331 6,331 12,300 12,300 12,300 20,480 20,480 20,480 5,546 5,546 5,546 1,020 1,020 1,020 13,862 13,862 Coil Latent Load Btu/h 1,453 1,453 1,453 5,384 5,384 5,384 12,103 12,103 12,103 0 0 0 65,740 78,660 1,025 1,025 1,025 278 278 278 1,269 1,269 1,269 1,313 1,313 1,313 701 701 701 1,464 1,464 1,464 1,309 1,309 1,309 517 517 517 535 535 535 308 308 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 53 of 100 SPACE System Zone Room Zone - 353 spc_BC 109 Class_0 Zone - 354 Zone - 354 spc_BC 108 Class_0 Zone - 355 Zone - 355 spc_BC 106 Class_0 Zone - 356 Zone - 356 spc_BC 105 Class_0 Zone - 357 Zone - 357 spc_BC 101 Class_0 Zone - 358 Zone - 358 Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block BC FC Peak BC FC Block spc_BC 130 Cafe/Kitchen_0 Peak Zone - 341 Peak Zone - 341 Block spc_BC AH-2 245 Lecture_0 Peak Zone - 342 Peak Zone - 342 Block spc_BC AH-3 301 Class_0 Peak Zone - 343 Peak Zone - 343 Block spc_BC AH-4 302 Class_0 Peak Zone - 344 Peak Zone - 344 Block spc_BC 306 Office (AH-5)_0 Peak spc_BC 307-312 Office (AH-5)_0 Peak spc_BC AH-5 304 Hall_0 Peak Zone - 345 Peak Zone - 345 Block spc_BC AH-6 315 Lab_0 Peak Zone - 346 Peak Zone - 346 Block spc_BC AH-7 314 Class_0 Peak Zone - 347 Peak Zone - 347 Block spc_BC AH-8 313_0 Peak Zone - 348 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 123 248 248 248 228 228 228 287 287 287 308 308 308 696 696 696 3,507 3,507 1,908 1,908 1,908 809 809 809 162 162 162 188 188 188 17 107 518 642 642 181 181 181 183 183 183 518 518 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 9 /12 9 /12 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /12 7 /19 7 /19 9 /13 9 /13 7 /10 7 /10 11 /13 11 /13 7 /18 10 /16 7 /18 10/16 10 /16 10 /16 6 /9 6 /9 9 /16 79 73 73 73 73 73 73 70 70 70 70 70 70 70 70 70 73 73 71 71 71 75 75 75 67 67 67 71 71 71 73 79 73 79 79 79 79 79 62 62 62 77 77 64 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 64 64 64 65 65 65 60 60 60 58 58 58 65 64 65 64 64 64 64 64 58 58 58 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 58.7 53.9 53.9 53.9 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.8 56.8 49.0 49.0 49.0 48.5 48.5 48.5 57.5 57.5 57.5 55.0 55.0 55.0 57.7 59.1 54.7 58.0 58.0 58.3 58.3 58.3 56.9 56.9 56.9 55.0 55.0 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 902 902 902 435 435 435 1,005 1,005 11,800 5,234 5,234 5,234 6,925 6,925 6,925 15,674 15,674 15,674 16,788 16,788 16,788 36,297 36,297 36,297 164,625 128,212 25,681 25,681 25,681 8,768 8,768 8,768 9,949 9,949 9,949 14,106 14,106 14,106 1,203 14,924 6,067 22,194 20,846 13,789 13,789 13,789 7,351 7,351 7,351 19,025 19,025 231 766 766 766 704 704 704 918 918 918 985 985 985 2,230 2,230 2,230 10,125 10,014 7,496 7,496 7,496 2,709 2,709 2,709 457 457 457 435 435 435 41 199 801 1,041 657 394 394 394 486 486 486 1,924 1,924 10 /16 9 /13 9 /13 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /13 7 /19 7 /19 9 /14 9 /14 7 /10 7 /10 9 /15 9 /15 7 /18 10 /16 7 /18 9 /17 9 /16 9 /16 7 /17 7 /17 9 /16 79 75 75 75 73 73 73 70 70 70 70 70 70 70 70 70 75 75 71 71 71 77 77 77 67 67 67 78 78 78 73 79 73 76 76 77 77 77 75 75 75 77 77 64 65 65 65 63 63 63 63 63 63 63 63 63 63 63 63 65 65 64 64 64 66 66 66 60 60 60 66 66 66 65 64 65 67 67 67 67 67 66 66 66 67 67 58.7 54.5 54.5 54.5 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.9 60.6 49.0 49.0 49.0 48.7 48.7 48.7 57.5 57.5 57.5 57.3 57.3 57.3 57.7 59.1 54.7 58.0 59.1 58.5 58.5 58.5 61.5 61.5 61.5 55.0 55.0 Coil Airflow cfm Coil Sensible Load Btu/h 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 902 902 902 435 435 435 1,005 1,005 13,862 6,369 6,369 6,369 8,775 8,775 8,775 17,730 17,730 17,730 19,220 19,220 19,220 40,708 40,708 40,708 195,368 154,845 28,282 28,282 28,282 10,394 10,394 10,394 11,797 11,797 11,797 17,273 17,273 17,273 1,823 19,637 7,596 29,057 27,346 18,690 18,690 18,690 9,470 9,470 9,470 25,235 25,235 Coil Latent Load Btu/h 308 1,430 1,430 1,430 1,096 1,096 1,096 1,494 1,494 1,494 1,603 1,603 1,603 3,631 3,631 3,631 17,976 18,247 13,513 13,513 13,513 4,960 4,960 4,960 624 624 624 1,481 1,481 1,481 75 265 1,033 1,373 1,870 1,012 1,012 1,012 1,133 1,133 1,133 3,625 3,625 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 54 of 100 SPACE Floor Area ft² System Zone Room Zone - 348 BC Hydronic AHU BC Hydronic AHU spc_CC 108 C_0 Zone - 120 Zone - 120 spc_CC 106 Mechanical C_0 Zone - 121 Zone - 121 spc_CC 203 Storage_0 Zone - 122 Zone - 122 spc_CC 202 Storage_0 Zone - 123 Zone - 123 spc_CC 201 Eating Area C_0 Zone - 124 Zone - 124 Campus Center Dual Deck Campus Center Dual Deck spc_CC Class 122-126 C_0 Zone - 119 Zone - 119 Campus Center FC Campus Center FC spc_CC 228 Comp C_0 Zone - 125 Zone - 125 Bookstore 1 Zone - 362 Zone - 362 Bookstore 2 Zone - 363 Zone - 363 Bookstore 3 Zone - 364 Zone - 364 Bookstore 4 Zone - 365 Zone - 365 Bookstore 5 Zone - 366 Zone - 366 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 518 4,592 4,592 381 381 381 530 530 530 159 159 159 133 133 133 1,974 1,974 1,974 3,176 3,176 1,023 1,023 1,023 1,023 1,023 519 519 519 915 915 915 915 915 915 915 915 915 915 915 915 915 915 915 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 9 /12 9 /12 9 /12 9 /12 10 /14 6 /18 6 /18 6 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 80 80 79 79 79 76 76 76 76 76 76 73 73 73 73 73 73 79 79 70 70 70 70 70 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 67 63 63 64 64 64 67 67 67 67 67 67 63 63 63 63 63 63 62 62 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.0 55.2 55.2 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.1 57.1 57.1 57.1 57.1 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 1,005 6,464 6,464 797 797 797 480 480 480 556 556 556 430 430 430 1,808 1,808 1,808 4,073 4,073 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 404 404 404 404 404 404 404 404 19,025 120,862 101,266 12,551 12,551 12,551 11,849 11,849 11,849 8,761 8,761 8,761 6,778 6,778 6,778 28,473 28,473 28,473 68,413 57,628 64,980 64,980 64,980 64,980 64,980 17,432 17,432 17,432 11,760 11,760 11,760 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 1,924 14,942 6,374 167 167 167 761 761 761 277 277 277 137 137 137 4,445 4,445 4,445 5,787 5,745 3,184 3,184 3,184 3,184 3,184 1,513 1,513 1,513 3,754 3,754 3,754 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /17 9 /17 9 /13 9 /13 9 /13 9 /13 9 /14 7 /18 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 77 77 76 76 76 76 76 76 76 76 76 75 75 75 75 75 75 77 77 73 73 73 73 73 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 67 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 65 65 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 55.0 55.8 58.3 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.4 57.4 57.4 57.4 57.4 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 Coil Airflow cfm Coil Sensible Load Btu/h 1,005 6,464 6,464 784 784 784 477 477 477 554 554 554 414 414 414 1,746 1,746 1,746 3,974 3,459 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 404 404 404 404 404 404 404 404 25,235 150,199 134,479 15,748 15,748 15,748 15,813 15,813 15,813 13,075 13,075 13,075 9,068 9,068 9,068 33,559 33,559 33,559 87,263 75,402 69,485 69,485 69,485 69,485 69,485 22,424 22,424 22,424 18,552 18,552 18,552 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 Coil Latent Load Btu/h 3,625 27,722 25,060 1,787 1,787 1,787 1,129 1,129 1,129 379 379 379 204 204 204 12,956 12,956 12,956 16,454 17,396 6,613 6,613 6,613 6,613 6,613 2,598 2,598 2,598 6,278 6,278 6,278 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 55 of 100 SPACE System Zone Room Floor Area ft² Bookstore 6 Peak Zone - 367 Peak Zone - 367 Block Campus Center Packg RTU-1 Peak Campus Center Packg RTU-1 Block spc_DM FC-Music Office_0 Peak Zone - 137 Peak Zone - 137 Block Peak spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0 Zone - 138 Peak Zone - 138 Block spc_DM FC 3-1 Dress Rms Int_0 Peak Zone - 139 Peak Zone - 139 Block spc_DM FC 3-1 Dress Rms_0 Peak Zone - 140 Peak Zone - 140 Block Drama/Music Fan Coil Peak Drama/Music Fan Coil Block spc_HP-9 Office_0 Peak Zone - 126 Peak Zone - 126 Block spc_DM HP-7 Storage_0 Peak Zone - 127 Peak Zone - 127 Block spc_DM HP-7 Dress Rm_0 Peak Zone - 128 Peak Zone - 128 Block spc_DM HP 3/4 Class_0 Peak Zone - 129 Peak Zone - 129 Block spc_DM HP-2 Class_0 Peak Zone - 130 Peak Zone - 130 Block spc_DM HP-5 Performance Rm_0 Peak Zone - 131 Peak Zone - 131 Block spc_DM HP-10 Prop Rm_0 Peak Zone - 132 Peak Zone - 132 Block spc_DM HP-1 Main Corridor_0 Peak Zone - 133 Peak Zone - 133 Block 915 915 915 6,007 6,007 338 338 338 892 892 892 267 267 267 327 327 327 1,824 1,824 121 121 121 57 57 57 9,797 9,797 9,797 926 926 926 569 569 569 1,176 1,176 1,176 1,131 1,131 1,131 7,381 7,381 7,381 Project Name: Dataset Name: SBCC TRACE.TRC OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 10 /16 10 /16 9 /17 9 /12 9 /12 10 /15 10 /15 10 /15 10 /15 6 /9 6 /9 11 /13 11 /13 9 /12 9 /12 7 /18 7 /18 9 /11 9 /11 76 76 76 76 76 79 79 79 75 75 75 76 76 76 79 79 79 76 76 73 73 73 80 80 80 80 80 80 62 62 62 71 71 71 73 73 73 73 73 73 70 70 70 66 66 66 66 66 64 64 64 66 66 66 66 66 66 64 64 64 67 67 63 63 63 63 63 63 63 63 63 58 58 58 58 58 58 63 63 63 65 65 65 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.4 49.4 49.4 51.0 51.0 56.4 56.4 56.4 54.3 54.3 54.3 44.5 44.5 44.5 58.3 58.3 58.3 55.7 55.7 57.0 57.0 57.0 54.8 54.8 54.8 51.3 51.3 51.3 55.4 55.4 55.4 59.2 59.2 59.2 53.5 53.5 53.5 57.4 57.4 57.4 56.2 56.2 56.2 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 10,160 10,160 10,160 79,989 79,989 8,123 8,123 8,123 9,831 9,831 9,831 2,946 2,946 2,946 8,853 8,853 8,853 29,753 27,815 4,747 4,747 4,747 261 261 261 99,554 99,554 99,554 21,837 21,837 21,837 35,452 35,452 35,452 27,637 27,637 27,637 36,017 36,017 36,017 106,822 106,822 106,822 2,839 2,839 2,839 19,459 19,459 633 633 633 1,432 1,432 1,432 1,098 1,098 1,098 269 269 269 3,432 4,394 263 263 263 35 35 35 25,148 25,148 25,148 2,451 2,451 2,451 1,082 1,082 1,082 4,324 4,324 4,324 1,740 1,740 1,740 9,194 9,194 9,194 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /17 9 /13 9 /13 7 /16 7 /16 9 /16 9 /16 7 /16 7 /16 9 /13 9 /13 7 /15 7 /15 7 /17 7 /17 9 /11 9 /11 76 76 76 76 76 76 76 76 75 75 75 77 77 77 79 79 79 76 76 75 75 75 76 76 76 77 77 77 76 76 76 75 75 75 77 77 77 75 75 75 70 70 70 66 66 66 66 66 67 67 67 66 66 66 67 67 67 64 64 64 67 67 65 65 65 66 66 66 67 67 67 66 66 66 65 65 65 66 66 66 66 66 66 63 63 63 49.4 49.4 49.4 51.0 51.0 56.5 56.5 56.5 54.3 54.3 54.3 45.0 45.0 45.0 58.3 58.3 58.3 55.8 56.8 57.6 57.6 57.6 55.8 55.8 55.8 51.5 51.5 51.5 59.2 59.2 59.2 60.5 60.5 60.5 59.5 59.5 59.5 57.8 57.8 57.8 56.2 56.2 56.2 Coil Airflow cfm Coil Sensible Load Btu/h 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 17,188 17,188 17,188 126,914 126,914 12,772 12,772 12,772 21,797 21,797 21,797 2,242 2,242 2,242 10,451 10,451 10,451 47,261 42,971 6,446 6,446 6,446 1,151 1,151 1,151 104,158 104,158 104,158 33,229 33,229 33,229 39,761 39,761 39,761 38,930 38,930 38,930 57,496 57,496 57,496 120,423 120,423 120,423 Coil Latent Load Btu/h 5,361 5,361 5,361 35,683 35,683 1,763 1,763 1,763 1,818 1,818 1,818 2,311 2,311 2,311 330 330 330 6,222 7,103 408 408 408 120 120 120 68,283 68,283 68,283 5,820 5,820 5,820 3,265 3,265 3,265 8,980 8,980 8,980 2,459 2,459 2,459 11,397 11,397 11,397 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 56 of 100 SPACE Floor Area ft² System Zone Room spc_DM HP-9 Class_0 Zone - 148 Zone - 148 spc_DM HP-6 Office_0 Zone - 149 Zone - 149 spc_DM HP-8 Class1_0 Zone - 150 Zone - 150 spc_DM PHP-5-2 Offices_0 Zone - 151 Zone - 151 spc_PHP-2-1 Cargo Elevator_0 Zone - 152 Zone - 152 spc_DM PRP-5-1 Restroom_0 Zone - 153 Zone - 153 spc_DM PRP-5-1 Restroom1_0 Zone - 154 Zone - 154 Drama/Music HP Drama/Music HP spc_AC-1 Auditorium_0 Zone - 141 Zone - 141 spc_DM AN-2 Corridor_0 Zone - 142 Zone - 142 spc_DM AC-2 Rehearsal Rm_0 Zone - 143 Zone - 143 spc_DM ZN-1 Class_0 Zone - 144 Zone - 144 spc_DM ZN-3 Hall_0 Zone - 145 Zone - 145 spc_DM Zn-3 Offices_0 Zone - 146 Zone - 146 spc_ZN-3 Conf_0 Zone - 147 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 192 192 192 220 220 220 592 592 592 292 292 292 122 122 122 848 848 848 1,177 1,177 1,177 24,602 24,602 3,790 3,790 3,790 701 701 701 1,135 1,135 1,135 417 417 417 209 209 209 177 177 177 405 405 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /15 10 /15 6 /9 6 /9 10 /15 10 /15 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 9 /12 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 6 /18 6 /18 10 /16 10 /16 10 /16 10 /16 6 /10 80 80 80 62 62 62 80 80 80 79 79 79 79 79 79 79 79 79 79 79 79 73 73 80 80 80 75 75 75 80 80 80 70 70 70 79 79 79 79 79 79 65 65 63 63 63 58 58 58 63 63 63 64 64 64 64 64 64 64 64 64 64 64 64 63 63 63 63 63 66 66 66 63 63 63 63 63 63 64 64 64 64 64 64 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 80.0 80.0 80.0 73.1 73.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 51.3 51.3 51.3 58.2 58.2 58.2 51.3 51.3 51.3 52.2 52.2 52.2 58.6 58.6 58.6 79.6 79.6 79.6 79.6 79.6 79.6 58.9 58.9 54.9 54.9 54.9 55.9 55.9 55.9 50.7 50.7 50.7 56.6 56.6 56.6 49.9 49.9 49.9 51.7 51.7 51.7 50.6 50.6 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 24 24 24 64 64 64 206 206 1,946 1,946 1,946 10,408 10,408 10,408 6,020 6,020 6,020 2,564 2,564 2,564 4,056 4,056 4,056 538 538 538 747 747 747 358,606 299,869 74,299 74,299 74,299 11,804 11,804 11,804 10,848 10,848 10,848 20,443 20,443 20,443 583 583 583 1,443 1,443 1,443 4,907 4,907 492 492 492 311 311 311 1,521 1,521 1,521 545 545 545 99 99 99 -2,632 -2,632 -2,632 -3,655 -3,655 -3,655 40,918 47,013 9,753 9,753 9,753 1,126 1,126 1,126 2,908 2,908 2,908 1,296 1,296 1,296 169 169 169 330 330 330 1,311 1,311 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 76 76 76 65 65 65 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 77 77 75 75 75 77 77 77 73 73 73 77 77 77 76 76 76 77 77 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 65 65 65 67 67 67 67 67 67 67 67 51.4 51.4 51.4 58.8 58.8 58.8 51.5 51.5 51.5 52.4 52.4 52.4 58.8 58.8 58.8 79.7 79.7 79.7 79.7 79.7 79.7 59.7 62.3 55.5 55.5 55.5 55.9 55.9 55.9 51.3 51.3 51.3 56.7 56.7 56.7 51.4 51.4 51.4 52.3 52.3 52.3 53.5 53.5 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 24 24 24 64 64 64 206 206 5,018 5,018 5,018 11,069 11,069 11,069 6,298 6,298 6,298 2,691 2,691 2,691 6,557 6,557 6,557 5,343 5,343 5,343 7,418 7,418 7,418 445,988 374,351 83,988 83,988 83,988 13,640 13,640 13,640 13,026 13,026 13,026 22,815 22,815 22,815 715 715 715 1,748 1,748 1,748 5,430 5,430 1,203 1,203 1,203 475 475 475 4,129 4,129 4,129 1,517 1,517 1,517 288 288 288 -46,142 -46,142 -46,142 -64,061 -64,061 -64,061 -1,859 7,013 26,500 26,500 26,500 1,430 1,430 1,430 7,893 7,893 7,893 2,691 2,691 2,691 468 468 468 919 919 919 3,494 3,494 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 57 of 100 SPACE Floor Area ft² System Zone Room Zone - 147 spc_DM Scene Shop HV-1_0 Zone - 155 Zone - 155 Drama/Music MZU Drama/Music MZU spc_EBS 217/Storage C_0 Zone - 156 Zone - 156 spc_EBS 215 Class C_0 Zone - 157 Zone - 157 spc_EBS 209 Class C_0 Zone - 158 Zone - 158 spc_EBS 210 Class C_0 Zone - 159 Zone - 159 spc_EBS 109/127 Lobby C_0 Zone - 160 Zone - 160 spc_EBS 125 Class C_0 Zone - 161 Zone - 161 spc_EBS 102 Class C_0 Zone - 162 Zone - 162 spc_EBS 123 Class C_0 Zone - 163 Zone - 163 spc_EBS 119 Offices C_0 Zone - 164 Zone - 164 spc_EBS 119 Office C_0 Zone - 165 Zone - 165 spc_EBS 116 Office C_0 Zone - 166 Zone - 166 spc_EBS 110-113 Office UC_0 Zone - 167 Zone - 167 spc_EBS 114 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 405 1,711 1,711 1,711 8,545 8,545 2,046 2,046 2,046 758 758 758 1,358 1,358 1,358 1,333 1,333 1,333 1,771 1,771 1,771 396 396 396 1,332 1,332 1,332 1,622 1,622 1,622 399 399 399 306 306 306 156 156 156 515 515 515 893 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /10 10 /13 10 /13 9 /16 7 /15 7 /15 7 /16 7 /16 10 /15 10 /15 7 /18 7 /18 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 10 /14 65 77 77 77 77 77 77 77 77 76 76 76 80 80 80 73 73 73 75 75 75 73 73 73 73 73 73 73 73 73 75 75 75 75 75 75 73 73 73 73 73 73 79 58 59 59 59 67 67 66 66 66 66 66 66 63 63 63 65 65 65 66 66 66 65 65 65 65 65 65 65 65 65 66 66 66 66 66 66 65 65 65 65 65 65 62 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 50.6 57.7 57.7 57.7 55.4 55.4 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 206 1,561 1,561 1,561 8,045 8,045 931 931 931 493 493 493 1,547 1,547 1,547 1,511 1,511 1,511 744 744 744 473 473 473 2,019 2,019 2,019 1,486 1,486 1,486 309 309 309 177 177 177 220 220 220 624 624 624 1,093 4,907 24,799 24,799 24,799 149,125 129,890 18,050 18,050 18,050 9,553 9,553 9,553 29,992 29,992 29,992 29,286 29,286 29,286 14,421 14,421 14,421 9,178 9,178 9,178 39,142 39,142 39,142 28,811 28,811 28,811 5,997 5,997 5,997 3,436 3,436 3,436 4,262 4,262 4,262 12,097 12,097 12,097 21,186 1,311 3,134 3,134 3,134 20,027 30,017 3,114 3,114 3,114 2,661 2,661 2,661 3,489 3,489 3,489 4,607 4,607 4,607 2,924 2,924 2,924 1,369 1,369 1,369 4,604 4,604 4,604 5,608 5,608 5,608 1,057 1,057 1,057 811 811 811 368 368 368 1,214 1,214 1,214 2,014 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /14 9 /14 9 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /14 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 75 75 75 75 75 75 73 73 73 73 73 73 75 75 75 75 75 75 75 75 75 73 73 73 73 73 73 77 67 66 66 66 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 66 53.5 58.2 58.2 58.2 55.9 57.5 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 206 1,561 1,561 1,561 8,045 8,045 903 903 903 493 493 493 1,515 1,515 1,515 1,493 1,493 1,493 744 744 744 473 473 473 2,019 2,019 2,019 1,454 1,454 1,454 309 309 309 177 177 177 220 220 220 624 624 624 1,079 5,430 30,462 30,462 30,462 171,824 156,601 40,996 40,996 40,996 17,369 17,369 17,369 45,366 45,366 45,366 45,809 45,809 45,809 35,058 35,058 35,058 14,006 14,006 14,006 55,862 55,862 55,862 46,115 46,115 46,115 10,829 10,829 10,829 6,764 6,764 6,764 6,557 6,557 6,557 19,460 19,460 19,460 22,361 Coil Latent Load Btu/h 3,494 10,580 10,580 10,580 53,975 55,726 4,331 4,331 4,331 4,766 4,766 4,766 9,476 9,476 9,476 8,212 8,212 8,212 4,199 4,199 4,199 2,548 2,548 2,548 8,567 8,567 8,567 9,995 9,995 9,995 1,822 1,822 1,822 1,398 1,398 1,398 677 677 677 2,235 2,235 2,235 5,495 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 58 of 100 SPACE Floor Area ft² System Zone Room Zone - 168 Zone - 168 spc_EBS 115 Class C_0 Zone - 169 Zone - 169 spc_EBS 209 Class UC_0 Zone - 172 Zone - 172 spc_EBS 210 Class C_1 Zone - 173 Zone - 173 spc_EBS 215 Class C_1 Zone - 174 Zone - 174 spc_EBS 218 Office C_0 Zone - 175 Zone - 175 spc_EBS 216 Office C_0 Zone - 176 Zone - 176 EBS VAV EBS VAV spc_H 326 Class C_0 Zone - 206 Zone - 206 spc_H 328 Class C_0 Zone - 207 Zone - 207 spc_H 328 Office C_0 Zone - 208 Zone - 208 Humanities Fan Coil Humanities Fan Coil spc_H 104/107/112 Art C_0 Zone - 177 Zone - 177 spc_H 102 Class C_0 Zone - 178 Zone - 178 spc_H 106 Office C_0 Zone - 179 Zone - 179 spc_H 2444 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 893 893 10 /14 1,659 9 /16 1,659 1,659 9 /16 1,334 7 /16 1,334 1,334 7 /16 1,334 7 /16 1,334 1,334 7 /16 790 7 /18 790 790 7 /18 70 7 /18 70 70 7/18 74 7 /17 74 74 7 /17 18,147 18,147 7 /17 845 5 /17 845 845 5 /17 1,818 7 /16 1,818 1,818 7 /16 300 7 /12 300 300 7 /12 2,963 2,963 7 /17 7,121 7 /16 7,121 7,121 7 /16 1,004 7 /16 1,004 1,004 7 /16 229 7 /17 229 229 7 /17 555 7 /16 79 79 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 72 72 72 76 76 76 73 73 73 75 75 76 76 76 76 76 76 75 75 75 76 62 62 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 63 63 63 66 66 66 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 54.3 54.3 54.3 56.6 56.6 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 1,093 1,093 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,925 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,288 5,288 5,288 627 627 627 122 122 122 346 21,186 21,186 31,380 31,380 31,380 16,818 16,818 16,818 16,818 16,818 16,818 14,759 14,759 14,759 2,665 2,665 2,665 826 826 826 308,677 289,380 76,201 76,201 76,201 24,051 24,051 24,051 4,645 4,645 4,645 104,897 101,595 91,368 91,368 91,368 10,835 10,835 10,835 2,102 2,102 2,102 5,987 2,014 2,014 6,149 6,149 6,149 4,685 4,685 4,685 4,685 4,685 4,685 2,731 2,731 2,731 166 166 166 195 195 195 52,452 52,299 2,350 2,350 2,350 6,371 6,371 6,371 631 631 631 9,352 9,537 24,945 24,945 24,945 3,519 3,519 3,519 604 604 604 1,944 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /14 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /17 7 /15 7 /15 9 /16 9 /16 9 /17 9 /17 9 /16 77 77 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 73 73 73 76 76 76 76 76 76 75 75 77 77 77 77 77 77 76 76 76 77 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 65 65 65 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 57.2 57.2 57.2 56.7 57.1 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 1,079 1,079 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,801 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,284 5,284 5,284 600 600 600 119 119 119 331 22,361 22,361 49,825 49,825 49,825 30,579 30,579 30,579 30,579 30,579 30,579 23,381 23,381 23,381 3,913 3,913 3,913 1,626 1,626 1,626 504,179 486,608 92,686 92,686 92,686 49,932 49,932 49,932 8,423 8,423 8,423 151,042 148,011 99,527 99,527 99,527 11,228 11,228 11,228 2,209 2,209 2,209 6,204 Coil Latent Load Btu/h 5,495 5,495 11,570 11,570 11,570 8,391 8,391 8,391 8,391 8,391 8,391 5,082 5,082 5,082 305 305 305 336 336 336 97,796 94,521 5,460 5,460 5,460 11,390 11,390 11,390 1,341 1,341 1,341 18,190 17,762 43,603 43,603 43,603 6,979 6,979 6,979 1,184 1,184 1,184 3,856 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 59 of 100 SPACE Floor Area ft² System Zone Room Zone - 180 Zone - 180 spc_H 245A/B Class C_0 Zone - 181 Zone - 181 spc_H 226/A office C_0 Zone - 182 Zone - 182 spc_H 208-217 Office C_0 Zone - 183 Zone - 183 spc_H 225 Office C_0 Zone - 184 Zone - 184 spc_H 242/207 Corridor C_0 Zone - 185 Zone - 185 spc_H 123U Art AH-1/23_0 Zone - 186 Zone - 186 spc_H 111 Class C_0 Zone - 187 Zone - 187 spc_H 221/220/204 Class C_0 Zone - 188 Zone - 188 spc_H 232A Class C_0 Zone - 189 Zone - 189 spc_H 239 Class Office_0 Zone - 190 Zone - 190 spc_H 237 Office C_0 Zone - 191 Zone - 191 spc_H 236 Office C_0 Zone - 192 Zone - 192 spc_H 241 Class C_0 Zone - 193 Zone - 193 spc_H 309-318 Offices C_0 Zone - 194 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 555 555 1,686 1,686 1,686 272 272 272 1,065 1,065 1,065 267 267 267 4,126 4,126 4,126 2,482 2,482 2,482 1,805 1,805 1,805 4,564 4,564 4,564 1,111 1,111 1,111 306 306 306 90 90 90 272 272 272 571 571 571 1,012 1,012 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /17 7 /17 11 /13 11 /13 11 /14 11 /14 11 /14 11 /14 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 11 /14 76 76 75 75 75 71 71 71 73 73 73 73 73 73 79 79 79 75 75 75 76 76 76 77 77 77 76 76 76 77 77 77 75 75 75 75 75 75 76 76 76 73 73 66 66 66 66 66 58 58 58 60 60 60 60 60 60 64 64 64 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 60 60 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 346 346 2,157 2,157 2,157 798 798 798 3,496 3,496 3,496 765 765 765 1,412 1,412 1,412 2,382 2,382 2,382 1,127 1,127 1,127 3,577 3,577 3,577 693 693 693 311 311 311 48 48 48 145 145 145 356 356 356 4,319 4,319 5,987 5,987 37,265 37,265 37,265 13,783 13,783 13,783 60,401 60,401 60,401 13,211 13,211 13,211 24,400 24,400 24,400 41,156 41,156 41,156 19,474 19,474 19,474 61,807 61,807 61,807 11,982 11,982 11,982 5,382 5,382 5,382 828 828 828 2,500 2,500 2,500 6,155 6,155 6,155 74,623 74,623 1,944 1,944 5,523 5,523 5,523 89 89 89 766 766 766 192 192 192 3,332 3,332 3,332 8,130 8,130 8,130 6,325 6,325 6,325 15,809 15,809 15,809 3,891 3,891 3,891 1,060 1,060 1,060 238 238 238 719 719 719 1,999 1,999 1,999 728 728 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /14 9 /14 9 /15 9 /15 9 /15 9 /15 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /15 7 /15 9 /16 9 /16 7 /15 7 /15 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /15 77 77 77 77 77 77 77 77 78 78 78 78 78 78 77 77 77 76 76 76 77 77 77 77 77 77 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 78 78 67 67 67 67 67 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 331 331 2,071 2,071 2,071 743 743 743 2,999 2,999 2,999 665 665 665 1,401 1,401 1,401 2,313 2,313 2,313 1,078 1,078 1,078 3,577 3,577 3,577 663 663 663 311 311 311 47 47 47 142 142 142 341 341 341 3,657 3,657 6,204 6,204 40,964 40,964 40,964 15,383 15,383 15,383 74,566 74,566 74,566 13,581 13,581 13,581 25,840 25,840 25,840 45,783 45,783 45,783 20,181 20,181 20,181 67,488 67,488 67,488 12,417 12,417 12,417 5,994 5,994 5,994 871 871 871 2,628 2,628 2,628 6,379 6,379 6,379 87,004 87,004 Coil Latent Load Btu/h 3,856 3,856 11,713 11,713 11,713 999 999 999 4,843 4,843 4,843 1,216 1,216 1,216 9,229 9,229 9,229 17,267 17,267 17,267 12,544 12,544 12,544 27,948 27,948 27,948 7,718 7,718 7,718 1,874 1,874 1,874 467 467 467 1,408 1,408 1,408 3,965 3,965 3,965 4,603 4,603 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 60 of 100 SPACE Floor Area ft² System Zone Room Zone - 194 spc_H 240 Class C_0 Zone - 195 Zone - 195 spc_H 300 Restrooms C_0 Zone - 196 Zone - 196 spc_H 322 Office C_0 Zone - 197 Zone - 197 spc_H 323 Office C_0 Zone - 198 Zone - 198 spc_H 300H Hall C_0 Zone - 199 Zone - 199 spc_H 202 Class C_0 Zone - 200 Zone - 200 spc_H 205 Office C_0 Zone - 201 Zone - 201 spc_H 205/203 Class C_0 Zone - 202 Zone - 202 spc_H 232B Office C_0 Zone - 203 Zone - 203 spc_H 223 Class C_0 Zone - 204 Zone - 204 spc_H 223U Storage C_0 Zone - 205 Zone - 205 spc_H 306 Class C_0 Zone - 211 Zone - 211 spc_H 308 Class H_0 Zone - 212 Zone - 212 spc_H 301-307 Classes C_0 Zone - 213 Zone - 213 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,012 818 818 818 339 339 339 265 265 265 265 265 265 3,593 3,593 3,593 1,118 1,118 1,118 270 270 270 846 846 846 161 161 161 616 616 616 165 165 165 727 727 727 512 512 512 3,348 3,348 3,348 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 11 /14 7 /15 7 /15 9 /17 9 /17 11 /14 11 /14 7 /17 7 /17 10 /16 10 /16 8/10 8 /10 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /16 7 /16 7 /15 7 /15 73 77 77 77 76 76 76 73 73 73 75 75 75 79 79 79 67 67 67 75 75 75 76 76 76 75 75 75 76 76 76 77 77 77 76 76 76 76 76 76 77 77 77 60 66 66 66 67 67 67 60 60 60 66 66 66 64 64 64 61 61 61 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 4,319 642 642 642 542 542 542 1,069 1,069 1,069 141 141 141 3,898 3,898 3,898 2,401 2,401 2,401 144 144 144 528 528 528 86 86 86 385 385 385 51 51 51 454 454 454 320 320 320 2,748 2,748 2,748 74,623 11,100 11,100 11,100 14,193 14,193 14,193 18,478 18,478 18,478 2,434 2,434 2,434 67,353 67,353 67,353 41,487 41,487 41,487 2,483 2,483 2,483 9,121 9,121 9,121 1,483 1,483 1,483 6,648 6,648 6,648 876 876 876 7,841 7,841 7,841 5,526 5,526 5,526 47,476 47,476 47,476 728 2,834 2,834 2,834 619 619 619 190 190 190 700 700 700 9,908 9,908 9,908 3,433 3,433 3,433 714 714 714 2,962 2,962 2,962 426 426 426 2,159 2,159 2,159 250 250 250 2,546 2,546 2,546 1,795 1,795 1,795 11,597 11,597 11,597 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /15 7 /15 7 /15 9 /17 9 /17 9 /15 9 /15 9 /17 9 /17 9 /16 9 /16 9 /11 9 /11 9 /17 9 /17 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 9 /15 9 /15 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 78 77 77 77 76 76 76 78 78 78 76 76 76 77 77 77 70 70 70 76 76 76 77 77 77 76 76 76 77 77 77 78 78 78 76 76 76 76 76 76 76 76 76 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 63 63 63 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 3,657 642 642 642 210 210 210 890 890 890 138 138 138 3,839 3,839 3,839 2,239 2,239 2,239 141 141 141 505 505 505 84 84 84 368 368 368 47 47 47 441 441 441 311 311 311 2,733 2,733 2,733 87,004 12,091 12,091 12,091 14,647 14,647 14,647 21,157 21,157 21,157 2,558 2,558 2,558 126,357 126,357 126,357 45,716 45,716 45,716 2,609 2,609 2,609 9,452 9,452 9,452 1,558 1,558 1,558 6,890 6,890 6,890 878 878 878 19,161 19,161 19,161 13,504 13,504 13,504 102,755 102,755 102,755 Coil Latent Load Btu/h 4,603 5,010 5,010 5,010 4,236 4,236 4,236 1,203 1,203 1,203 1,371 1,371 1,371 24,964 24,964 24,964 5,771 5,771 5,771 1,399 1,399 1,399 5,875 5,875 5,875 835 835 835 4,282 4,282 4,282 357 357 357 4,551 4,551 4,551 3,208 3,208 3,208 20,961 20,961 20,961 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 61 of 100 SPACE System Zone Room spc_H 301 Class C_0 Peak Zone - 214 Peak Zone - 214 Block spc_H 3281 Hall C_0 Peak Zone - 215 Peak Zone - 215 Block Humanities VAV Peak Humanities VAV Block spc_IDC 335 Office C_0 Peak Zone - 220 Peak Zone - 220 Block spc_IDC 313 Wrk Rm_0 Peak Zone - 221 Peak Zone - 221 Block spc_IDC 317 Wrk Rm C_0 Peak Zone - 222 Peak Zone - 222 Block spc_IDC 329 C_0 Peak Zone - 223 Peak Zone - 223 Block IDC Fan Coil Peak IDC Fan Coil Block Peak spc_IDC 102/103/104/109 Int Class_0 Zone - 216 Peak Zone - 216 Block spc_IDC 205 Class C_0 Peak Zone - 217 Peak Zone - 217 Block spc_IDC 211/210 Class_0 Peak Zone - 218 Peak Zone - 218 Block spc_IDC 333 Office_0 Peak Zone - 219 Peak Zone - 219 Block IDC VAV Peak IDC VAV Block spc_LRC 140-01-08 C_0 Peak Zone - 224 Peak Zone - 224 Block spc_LRC 140-09 C_0 Peak Zone - 225 Peak Zone - 225 Block spc_LRC 13-15 C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 633 633 633 228 228 228 42,441 42,441 107 107 107 206 206 206 171 171 171 102 102 102 586 586 3,318 3,318 3,318 460 460 460 1,001 1,001 1,001 414 414 414 5,194 5,194 1,843 1,843 1,843 250 250 250 153 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 10 /15 7 /17 7 /17 7 /16 7 /16 7 /16 7/16 7 /16 7 /16 7 /16 10 /15 10 /15 10 /15 10 /15 10 /15 10 /15 10 /17 10 /17 10 /15 6 /10 6 /10 9 /12 9 /12 9 /11 76 76 76 76 76 76 80 80 75 75 75 76 76 76 76 76 76 76 76 76 76 76 80 80 80 80 80 80 80 80 80 77 77 77 80 80 65 65 65 73 73 73 70 66 66 66 66 66 66 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 63 63 63 63 63 63 64 64 64 63 63 58 58 58 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.1 72.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 395 395 395 53 53 53 41,826 37,423 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,694 1,694 1,694 859 859 859 511 511 511 180 180 180 3,244 3,237 1,595 1,595 1,595 797 797 797 632 6,823 6,823 6,823 911 911 911 727,491 650,911 1,280 1,280 1,280 2,975 2,975 2,975 2,627 2,627 2,627 1,357 1,357 1,357 8,239 8,216 32,706 32,706 32,706 16,577 16,577 16,577 9,869 9,869 9,869 3,472 3,472 3,472 62,624 62,481 28,266 28,266 28,266 14,118 14,118 14,118 11,205 2,216 2,216 2,216 354 354 354 122,518 95,452 284 284 284 722 722 722 600 600 600 357 357 357 1,962 1,958 8,526 8,526 8,526 1,182 1,182 1,182 2,573 2,573 2,573 855 855 855 13,135 12,972 5,957 5,957 5,957 915 915 915 580 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 9 /16 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 7 /16 7 /16 9 /13 9 /13 9 /11 76 76 76 76 76 76 77 77 75 75 75 76 76 76 76 76 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 75 75 75 77 77 76 76 76 75 75 75 70 66 66 66 66 66 66 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 66 66 66 65 65 65 63 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 384 384 384 49 49 49 39,362 36,284 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,668 1,668 1,668 843 843 843 503 503 503 179 179 179 3,194 3,189 1,448 1,448 1,448 757 757 757 632 16,673 16,673 16,673 4,252 4,252 4,252 957,271 890,214 2,183 2,183 2,183 4,555 4,555 4,555 3,950 3,950 3,950 2,128 2,128 2,128 12,817 12,798 38,524 38,524 38,524 19,698 19,698 19,698 11,625 11,625 11,625 10,755 10,755 10,755 80,821 79,588 54,618 54,618 54,618 17,332 17,332 17,332 12,865 3,960 3,960 3,960 448 448 448 249,846 272,391 488 488 488 1,291 1,291 1,291 1,072 1,072 1,072 638 638 638 3,490 3,478 23,156 23,156 23,156 3,209 3,209 3,209 6,987 6,987 6,987 1,894 1,894 1,894 35,247 35,420 12,597 12,597 12,597 1,569 1,569 1,569 880 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 62 of 100 SPACE Floor Area ft² System Zone Room Zone - 226 Zone - 226 spc_LRC 16 C_0 Zone - 227 Zone - 227 spc_LRC 17/18_0 Zone - 228 Zone - 228 spc_LRC 5 C (Study?)_0 Zone - 229 Zone - 229 spc_LRC 9 Storage_0 Zone - 230 Zone - 230 spc_LRC 10 Storage_0 Zone - 231 Zone - 231 spc_LRC 7 C_0 Zone - 232 Zone - 232 spc_LRC 8 Stair_0 Zone - 233 Zone - 233 spc_LRC Catalog C_0 Zone - 234 Zone - 234 spc_LRC Computer_0 Zone - 235 Zone - 235 spc_LRC 2/6_0 Zone - 236 Zone - 236 spc_LRC 1st RR C_0 Zone - 237 Zone - 237 spc_LRC 24_0 Zone - 238 Zone - 238 spc_LRC 25_0 Zone - 239 Zone - 239 spc_LRC 105 C Work_0 Zone - 240 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 153 153 66 66 66 94 94 94 57 57 57 29 29 29 24 24 24 119 119 119 302 302 302 56 56 56 525 525 525 137 137 137 226 226 226 564 564 564 325 325 325 62 62 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 10 /13 10 /13 10 /16 10 /16 7 /15 7 /15 7 /15 7 /15 6 /10 6/10 6 /18 6 /18 7 /18 7 /18 7 /18 7 /18 6 /17 6 /17 7 /15 7 /15 10 /16 10/16 10 /16 10 /16 7 /18 7 /18 7 /18 70 70 77 77 77 79 79 79 77 77 77 77 77 77 65 65 65 70 70 70 73 73 73 73 73 73 72 72 72 77 77 77 79 79 79 79 79 79 73 73 73 73 73 63 63 59 59 59 64 64 64 66 66 66 66 66 66 58 58 58 63 63 63 65 65 65 65 65 65 63 63 63 66 66 66 64 64 64 64 64 64 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 632 632 296 296 296 800 800 800 34 34 34 9 9 9 43 43 43 499 499 499 178 178 178 119 119 119 1,809 1,809 1,809 78 78 78 362 362 362 2,024 2,024 2,024 956 956 956 123 123 11,205 11,205 5,239 5,239 5,239 14,180 14,180 14,180 606 606 606 156 156 156 770 770 770 8,836 8,836 8,836 3,148 3,148 3,148 2,112 2,112 2,112 32,061 32,061 32,061 1,384 1,384 1,384 9,633 9,633 9,633 35,871 35,871 35,871 16,939 16,939 16,939 2,178 2,178 580 580 159 159 159 316 316 316 196 196 196 44 44 44 16 16 16 366 366 366 460 460 460 226 226 226 1,210 1,210 1,210 556 556 556 181 181 181 1,890 1,890 1,890 1,302 1,302 1,302 214 214 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /13 9 /13 9 /16 9 /16 9 /16 9 /16 9 /15 9 /15 6 /10 6 /10 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /16 9 /16 7 /18 7 /18 7 /18 70 70 75 75 75 77 77 77 77 77 77 78 78 78 65 65 65 73 73 73 73 73 73 73 73 73 75 75 75 77 77 77 79 79 79 77 77 77 73 73 73 73 73 63 63 65 65 65 67 67 67 67 67 67 66 66 66 58 58 58 65 65 65 65 65 65 65 65 65 66 66 66 67 67 67 64 64 64 67 67 67 65 65 65 65 65 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 632 632 289 289 289 781 781 781 34 34 34 8 8 8 43 43 43 495 495 495 178 178 178 119 119 119 1,791 1,791 1,791 77 77 77 186 186 186 1,981 1,981 1,981 956 956 956 123 123 12,865 12,865 5,989 5,989 5,989 15,724 15,724 15,724 602 602 602 149 149 149 999 999 999 9,606 9,606 9,606 3,388 3,388 3,388 2,494 2,494 2,494 34,140 34,140 34,140 1,369 1,369 1,369 8,860 8,860 8,860 39,177 39,177 39,177 19,463 19,463 19,463 3,446 3,446 Coil Latent Load Btu/h 880 880 417 417 417 710 710 710 392 392 392 63 63 63 19 19 19 757 757 757 592 592 592 392 392 392 2,556 2,556 2,556 1,032 1,032 1,032 996 996 996 4,243 4,243 4,243 2,256 2,256 2,256 397 397 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 63 of 100 SPACE System Zone Room Zone - 240 Block spc_LRC Tables/124B C_0 Peak Zone - 241 Peak Zone - 241 Block spc_LRC 120/122/123 Office C_0 Peak Zone - 242 Peak Zone - 242 Block spc_LRC Tutor Lab C_0 Peak Zone - 243 Peak Zone - 243 Block spc_LRC Lobby/112B Corridor C_0Peak Zone - 244 Peak Zone - 244 Block spc_LRC Dir Offc C_0 Peak Zone - 245 Peak Zone - 245 Block spc_LRC 108/111/115 Counter_0 Peak Zone - 246 Peak Zone - 246 Block spc_LRC 149A_0 Peak Zone - 247 Peak Zone - 247 Block spc_LRC 137 Work C_0 Peak Zone - 248 Peak Zone - 248 Block spc_LRC 140-142 Director_0 Peak Zone - 249 Peak Zone - 249 Block spc_LRC 145 Office C_0 Peak Zone - 250 Peak Zone - 250 Block spc_LRC 146A Storage_0 Peak Zone - 251 Peak Zone - 251 Block spc_LRC 146_0 Peak Zone - 252 Peak Zone - 252 Block spc_LRC Library_0 Peak Zone - 253 Peak Zone - 253 Block spc_LRC 140-14_0 Peak Zone - 254 Peak Zone - 254 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 62 647 647 647 58 58 58 63 63 63 582 582 582 36 36 36 335 335 335 25 25 25 59 59 59 38 38 38 23 23 23 14 14 14 80 80 80 0 0 0 42 42 42 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 10 /15 10 /15 6 /11 6 /11 7 /15 7 /15 7 /18 7 /18 6 /18 6 /18 7/15 7 /15 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 10 /13 10 /13 11 /12 11 /12 9 /12 9 /12 73 80 80 80 68 68 68 77 77 77 73 73 73 70 70 70 77 77 77 73 73 73 73 73 73 75 75 75 75 75 75 79 79 79 77 77 77 68 68 68 73 73 73 65 63 63 63 60 60 60 66 66 66 65 65 65 63 63 63 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 64 64 64 59 59 59 55 55 55 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 123 1,184 1,184 1,184 119 119 119 110 110 110 387 387 387 147 147 147 191 191 191 45 45 45 191 191 191 20 20 20 12 12 12 64 64 64 252 252 252 2,551 2,551 2,551 190 190 190 2,178 20,983 20,983 20,983 2,116 2,116 2,116 1,946 1,946 1,946 6,866 6,866 6,866 2,614 2,614 2,614 3,378 3,378 3,378 793 793 793 3,381 3,381 3,381 359 359 359 214 214 214 1,140 1,140 1,140 4,464 4,464 4,464 45,210 45,210 45,210 3,371 3,371 3,371 214 1,652 1,652 1,652 103 103 103 180 180 180 975 975 975 72 72 72 1,358 1,358 1,358 86 86 86 204 204 204 101 101 101 60 60 60 11 11 11 192 192 192 0 0 0 154 154 154 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /18 9 /16 9 /16 7 /12 7 /12 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 9 /14 9 /14 9 /11 9 /11 9 /12 9 /12 73 77 77 77 73 73 73 76 76 76 75 75 75 73 73 73 76 76 76 73 73 73 73 73 73 75 75 75 75 75 75 76 76 76 77 77 77 70 70 70 73 73 73 65 67 67 67 63 63 63 66 66 66 66 66 66 65 65 65 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 67 67 67 66 66 66 63 63 63 63 63 63 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 123 1,113 1,113 1,113 117 117 117 110 110 110 364 364 364 145 145 145 190 190 190 45 45 45 191 191 191 20 20 20 12 12 12 63 63 63 233 233 233 2,488 2,488 2,488 190 190 190 3,446 32,086 32,086 32,086 2,850 2,850 2,850 2,980 2,980 2,980 14,670 14,670 14,670 3,509 3,509 3,509 8,372 8,372 8,372 1,278 1,278 1,278 4,731 4,731 4,731 936 936 936 559 559 559 1,612 1,612 1,612 5,818 5,818 5,818 47,040 47,040 47,040 4,151 4,151 4,151 Coil Latent Load Btu/h 397 4,480 4,480 4,480 178 178 178 312 312 312 1,365 1,365 1,365 155 155 155 2,288 2,288 2,288 159 159 159 378 378 378 174 174 174 104 104 104 35 35 35 535 535 535 0 0 0 223 223 223 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 64 of 100 SPACE OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F System Zone Room Floor Area ft² spc_LRC 140-03_0 Peak Zone - 255 Peak Zone - 255 Block spc_LRC 101 Work C_0 Peak Zone - 256 Peak Zone - 256 Block spc_LRC 108-110 Storage_0 Peak Zone - 257 Peak Zone - 257 Block spc_LRC 109 Work_0 Peak Zone - 258 Peak Zone - 258 Block LRC VAV Peak LRC VAV Block spc_OE 10WM Restrooms AH-2_0Peak Zone - 259 Peak Zone - 259 Block spc_OE 112 Class C_0 Peak Zone - 260 Peak Zone - 260 Block spc_OE 116 Class C_0 Peak Zone - 261 Peak Zone - 261 Block spc_OE 180H/182 Class C_0 Peak Zone - 262 Peak Zone - 262 Block spc_OE 180A Office C_0 Peak Zone - 263 Peak Zone - 263 Block OE Pckg AH Peak OE Pckg AH Block spc_PE 108 Weight Rm HP3/4_0 Peak Zone - 006 Peak Zone - 006 Block spc_PE Locker/RR HP-06/07_0 Peak Zone - 008 Peak Zone - 008 Block Peak spc_PE 302-310E Office Partially C_0 Zone - 011 Peak Zone - 011 Block PE Heat Pump Peak PE Heat Pump Block spc_PE Gym AH1_0 Peak 86 6 /10 86 86 6 /10 62 9 /17 62 62 9 /17 24 7 /15 24 24 7 /15 43 9 /17 43 43 9 /17 7,052 7,052 9 /16 172 7 /18 172 172 7/18 522 10 /15 522 522 10 /15 1,121 7 /18 1,121 1,121 7 /18 509 9 /11 509 509 9 /11 66 7 /17 66 66 7 /17 2,391 2,391 10 /14 3,594 9 /10 3,594 3,594 9 /10 1,968 7 /18 1,968 1,968 7 /18 498 7 /18 498 498 7 /18 6,061 6,061 7 /18 7,524 7 /17 Project Name: Dataset Name: SBCC TRACE.TRC 65 65 65 76 76 76 77 77 77 76 76 76 77 77 73 73 73 80 80 80 73 73 73 70 70 70 75 75 75 79 79 67 67 67 73 73 73 73 73 73 73 73 75 58 58 58 67 67 67 66 66 66 67 67 67 67 67 65 65 65 63 63 63 65 65 65 63 63 63 66 66 66 62 62 61 61 61 65 65 65 65 65 65 65 65 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.2 72.2 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.7 72.7 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 76.0 76.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 73.2 73.2 73.2 56.6 56.6 56.6 52.2 52.2 52.2 55.6 55.6 55.6 48.8 48.8 48.8 56.4 56.4 54.5 54.5 54.5 74.3 74.3 74.3 56.3 56.3 56.3 64.7 64.7 72.4 207 207 207 186 186 186 7 7 7 143 143 143 16,361 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 3,150 3,150 1,009 1,009 1,009 6,278 6,278 1,505 3,672 3,672 3,672 3,302 3,302 3,302 123 123 123 2,540 2,540 2,540 293,173 232,240 2,089 2,089 2,089 17,559 17,559 17,559 20,357 20,357 20,357 17,712 17,712 17,712 589 589 589 58,307 44,634 41,395 41,395 41,395 19,874 19,874 19,874 17,669 17,669 17,669 78,937 60,043 -636 277 277 277 218 218 218 36 36 36 152 152 152 20,421 25,647 59 59 59 1,340 1,340 1,340 3,874 3,874 3,874 1,628 1,628 1,628 176 176 176 7,077 4,708 4,036 4,036 4,036 668 668 668 1,173 1,173 1,173 5,877 7,430 -4,539 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 9 /17 9 /17 7 /16 7 /16 9 /17 9 /17 9 /16 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 9 /13 9 /13 7 /17 7 /17 9 /16 9 /13 9 /13 9 /17 9 /17 7 /18 7 /18 9 /17 7 /14 75 75 75 76 76 76 76 76 76 76 76 76 77 77 76 76 76 77 77 77 73 73 73 75 75 75 75 75 75 77 77 75 75 75 76 76 76 73 73 73 76 76 76 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 66 67 67 65 65 65 67 67 67 65 65 65 67 67 65 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 76.2 76.2 76.2 57.4 57.4 57.4 52.2 52.2 52.2 57.4 57.4 57.4 48.8 48.8 48.8 57.5 60.7 57.2 57.2 57.2 75.4 75.4 75.4 56.3 56.3 56.3 66.2 68.1 72.4 Coil Airflow cfm Coil Sensible Load Btu/h 164 164 164 186 186 186 7 7 7 143 143 143 15,679 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 3,150 3,150 1,009 1,009 1,009 6,278 6,278 451 4,618 4,618 4,618 4,899 4,899 4,899 475 475 475 3,755 3,755 3,755 382,332 328,402 2,439 2,439 2,439 21,294 21,294 21,294 23,315 23,315 23,315 22,689 22,689 22,689 1,667 1,667 1,667 71,405 61,879 36,526 36,526 36,526 36,640 36,640 36,640 27,335 27,335 27,335 100,501 80,404 -191 Coil Latent Load Btu/h 569 569 569 432 432 432 50 50 50 300 300 300 41,604 50,410 755 755 755 3,639 3,639 3,639 7,205 7,205 7,205 2,921 2,921 2,921 304 304 304 14,824 15,804 19,890 19,890 19,890 8,557 8,557 8,557 2,160 2,160 2,160 30,607 29,879 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 65 of 100 SPACE System Zone Room Zone - 001 Peak Zone - 001 Block spc_PE Team Lockey RH4_0 Peak Zone - 002 Peak Zone - 002 Block spc_PE 113 RH7/RH8_0 Peak Zone - 003 Peak Zone - 003 Block spc_PE 114 C_0 Peak Zone - 004 Peak Zone - 004 Block spc_PE 109 NC_0 Peak Zone - 005 Peak Zone - 005 Block spc_PE 2nd Flr Lobby_0 Peak Zone - 007 Peak Zone - 007 Block Peak spc_PE 214-218, 201-203 Offices C_0 Zone - 009 Peak Zone - 009 Block spc_PE 3 Press Box RH02 _0 Peak Zone - 010 Peak Zone - 010 Block PE VAV Htg Only Peak PE VAV Htg Only Block spc_sp_55 Peak Zone - 264 Peak Zone - 264 Block spc_sp_56 Peak Zone - 265 Peak Zone - 265 Block spc_sp_57 Peak Zone - 266 Peak Zone - 266 Block spc_sp_58 Peak Zone - 267 Peak Zone - 267 Block spc_sp_59 Peak Zone - 268 Peak Zone - 268 Block spc_sp_60 Peak Zone - 269 Peak Zone - 269 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 7,524 7,524 744 744 744 1,696 1,696 1,696 1,001 1,001 1,001 683 683 683 7,013 7,013 7,013 1,922 1,922 1,922 174 174 174 20,757 20,757 1,130 1,130 1,130 1,130 1,130 1,130 1,159 1,159 1,159 1,087 1,087 1,087 396 396 396 828 828 828 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 10 /16 10 /16 9 /16 9 /16 9 /10 9 /10 10 /15 10 /15 7 /10 7 /10 7/18 7 /18 10 /16 10 /16 7 /17 10 /13 10 /13 10 /15 10 /15 9 /12 9 /12 10 /16 10 /16 11 /15 11 /15 7 /18 7 /18 75 75 79 79 79 77 77 77 67 67 67 80 80 80 67 67 67 73 73 73 79 79 79 75 75 77 77 77 80 80 80 73 73 73 79 79 79 73 73 73 73 73 73 66 66 64 64 64 67 67 67 61 61 61 63 63 63 60 60 60 65 65 65 64 64 64 66 66 59 59 59 63 63 63 63 63 63 64 64 64 62 62 62 65 65 65 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 74.4 74.4 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 58.6 58.6 58.6 55.9 55.9 55.9 54.6 54.6 54.6 56.3 56.3 56.3 58.2 58.2 58.2 54.7 54.7 54.7 1,505 1,505 1,190 1,190 1,190 339 339 339 200 200 200 137 137 137 351 351 351 256 256 256 23 23 23 4,001 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 -636 -636 10,111 10,111 10,111 -143 -143 -143 -85 -85 -85 -58 -58 -58 -148 -148 -148 -108 -108 -108 -10 -10 -10 8,923 0 25,370 25,370 25,370 30,201 30,201 30,201 29,008 29,008 29,008 37,550 37,550 37,550 33,464 33,464 33,464 25,783 25,783 25,783 -4,539 -4,539 -971 -971 -971 2,691 2,691 2,691 1,039 1,039 1,039 306 306 306 -8,532 -8,532 -8,532 454 454 454 -45 -45 -45 -9,597 -3,178 2,062 2,062 2,062 2,910 2,910 2,910 3,573 3,573 3,573 3,013 3,013 3,013 1,051 1,051 1,051 2,864 2,864 2,864 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /14 9 /16 9 /16 9 /16 9 /16 9 /10 9 /10 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 7 /17 9 /14 9 /14 9 /16 9 /16 9 /14 9 /14 9 /16 9 /16 10 /15 10 /15 7 /18 7 /18 76 76 77 77 77 77 77 77 67 67 67 77 77 77 75 75 75 75 75 75 76 76 76 75 75 77 77 77 77 77 77 77 77 77 77 77 77 80 80 80 73 73 73 65 65 67 67 67 67 67 67 61 61 61 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 67 67 67 66 66 66 67 67 67 63 63 63 65 65 65 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 59.2 59.2 59.2 56.9 56.9 56.9 55.6 55.6 55.6 56.5 56.5 56.5 58.3 58.3 58.3 54.7 54.7 54.7 Coil Airflow cfm Coil Sensible Load Btu/h 451 451 357 357 357 102 102 102 60 60 60 41 41 41 105 105 105 77 77 77 7 7 7 1,200 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 -191 -191 3,033 3,033 3,033 -43 -43 -43 -25 -25 -25 -17 -17 -17 -44 -44 -44 -32 -32 -32 -3 -3 -3 12,882 0 36,547 36,547 36,547 44,525 44,525 44,525 40,050 40,050 40,050 54,574 54,574 54,574 40,936 40,936 40,936 38,829 38,829 38,829 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6,959 6,959 6,959 7,908 7,908 7,908 7,147 7,147 7,147 7,605 7,605 7,605 1,195 1,195 1,195 5,336 5,336 5,336 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 66 of 100 SPACE Floor Area ft² System Zone Room spc_sp_61 Zone - 270 Zone - 270 spc_sp_62 Zone - 271 Zone - 271 spc_sp_63 Zone - 272 Zone - 272 spc_sp_64 Zone - 273 Zone - 273 spc_sp_65 Zone - 274 Zone - 274 spc_sp_66 Zone - 275 Zone - 275 spc_sp_67 Zone - 276 Zone - 276 spc_sp_68 Zone - 277 Zone - 277 spc_sp_69 Zone - 278 Zone - 278 spc_sp_70 Zone - 279 Zone - 279 spc_sp_38 Zone - 280 Zone - 280 spc_sp_39 Zone - 281 Zone - 281 spc_sp_40 Zone - 282 Zone - 282 spc_sp_41 Zone - 283 Zone - 283 spc_sp_42 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 378 9 /11 378 378 9 /11 485 6 /10 485 485 6 /10 678 10 /16 678 678 10 /16 822 7 /18 822 822 7 /18 628 9 /11 628 628 9 /11 2,082 9 /16 2,082 2,082 9 /16 2,169 7 /17 2,169 2,169 7 /17 2,777 7 /17 2,777 2,777 7 /17 3,084 7 /17 3,084 3,084 7 /17 211 6 /10 211 211 6 /10 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 1,408 9 /16 1,408 1,408 9 /16 1,392 9 /16 1,392 1,392 9 /16 972 9 /16 70 70 70 65 65 65 79 79 79 73 73 73 70 70 70 77 77 77 75 75 75 75 75 75 75 75 75 65 65 65 77 77 77 77 77 77 77 77 77 77 77 77 77 63 63 63 58 58 58 64 64 64 65 65 65 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.5 57.5 57.5 55.5 55.5 55.5 56.3 56.3 56.3 51.4 51.4 51.4 56.1 56.1 56.1 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.5 52.5 52.5 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 28,760 28,760 28,760 11,994 11,994 11,994 23,923 23,923 23,923 13,067 13,067 13,067 26,223 26,223 26,223 53,398 53,398 53,398 48,975 48,975 48,975 57,415 57,415 57,415 55,454 55,454 55,454 13,285 13,285 13,285 28,858 28,858 28,858 28,858 28,858 28,858 35,056 35,056 35,056 34,765 34,765 34,765 27,232 1,212 1,212 1,212 1,286 1,286 1,286 1,878 1,878 1,878 2,838 2,838 2,838 2,011 2,011 2,011 7,723 7,723 7,723 7,128 7,128 7,128 9,122 9,122 9,122 10,121 10,121 10,121 559 559 559 3,036 3,036 3,036 3,036 3,036 3,036 5,223 5,223 5,223 5,163 5,163 5,163 3,608 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /11 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 9 /12 9 /12 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 70 70 70 76 76 76 77 77 77 75 75 75 73 73 73 77 77 77 75 75 75 75 75 75 76 76 76 65 65 65 77 77 77 77 77 77 77 77 77 77 77 77 77 63 63 63 66 66 66 67 67 67 66 66 66 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 57.5 57.5 57.5 58.6 58.6 58.6 56.4 56.4 56.4 51.9 51.9 51.9 56.2 56.2 56.2 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.7 52.7 52.7 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 Coil Airflow cfm Coil Sensible Load Btu/h 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 32,826 32,826 32,826 16,489 16,489 16,489 33,562 33,562 33,562 23,710 23,710 23,710 32,978 32,978 32,978 80,411 80,411 80,411 79,136 79,136 79,136 95,193 95,193 95,193 95,526 95,526 95,526 14,677 14,677 14,677 41,068 41,068 41,068 41,068 41,068 41,068 53,076 53,076 53,076 52,584 52,584 52,584 39,863 Coil Latent Load Btu/h 1,973 1,973 1,973 3,057 3,057 3,057 4,742 4,742 4,742 5,052 5,052 5,052 3,012 3,012 3,012 14,541 14,541 14,541 13,382 13,382 13,382 17,116 17,116 17,116 19,369 19,369 19,369 694 694 694 5,720 5,720 5,720 5,720 5,720 5,720 9,832 9,832 9,832 9,719 9,719 9,719 6,796 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 67 of 100 SPACE Floor Area ft² System Zone Room Zone - 284 Zone - 284 spc_sp_43 Zone - 285 Zone - 285 spc_sp_44 Zone - 286 Zone - 286 spc_sp_45 Zone - 287 Zone - 287 spc_sp_46 Zone - 288 Zone - 288 spc_sp_47 Zone - 289 Zone - 289 spc_sp_48 Zone - 290 Zone - 290 spc_sp_49 Zone - 291 Zone - 291 spc_sp_50 Zone - 292 Zone - 292 spc_sp_51 Zone - 293 Zone - 293 spc_sp_52 Zone - 294 Zone - 294 spc_sp_53 Zone - 295 Zone - 295 spc_sp_54 Zone - 296 Zone - 296 spc_sp_22 Zone - 297 Zone - 297 spc_sp_23 Zone - 298 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 972 972 1,408 1,408 1,408 826 826 826 914 914 914 907 907 907 869 869 869 869 869 869 835 835 835 893 893 893 737 737 737 1,061 1,061 1,061 1,064 1,064 1,064 1,061 1,061 1,061 1,044 1,044 1,044 1,082 1,082 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /15 9 /16 9 /16 9 /16 9 /16 7 /18 7 /18 7 /18 7/18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 10 /13 10 /13 10 /13 10 /13 9 /12 9 /12 7 /18 7 /18 7 /18 77 77 80 80 80 77 77 77 77 77 77 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 77 77 77 77 77 77 73 73 73 73 73 73 73 73 67 67 63 63 63 67 67 67 67 67 67 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 59 59 59 59 59 59 63 63 63 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.0 54.0 56.0 56.0 56.0 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 53.9 53.9 53.9 54.1 54.1 54.1 54.2 54.2 54.2 54.0 54.0 54.0 55.0 55.0 55.0 58.7 58.7 58.7 58.7 58.7 58.7 54.7 54.7 54.7 53.1 53.1 53.1 53.4 53.4 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 27,232 27,232 38,302 38,302 38,302 27,994 27,994 27,994 26,885 26,885 26,885 25,235 25,235 25,235 22,064 22,064 22,064 22,983 22,983 22,983 22,536 22,536 22,536 23,576 23,576 23,576 24,944 24,944 24,944 24,323 24,323 24,323 24,374 24,374 24,374 27,301 27,301 27,301 22,248 22,248 22,248 24,586 24,586 3,608 3,608 3,626 3,626 3,626 3,067 3,067 3,067 3,393 3,393 3,393 3,140 3,140 3,140 3,008 3,008 3,008 3,009 3,009 3,009 2,891 2,891 2,891 3,092 3,092 3,092 2,553 2,553 2,553 1,935 1,935 1,935 1,941 1,941 1,941 3,272 3,272 3,272 3,609 3,609 3,609 3,741 3,741 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 9 /14 9 /14 9 /14 9 /14 9 /14 9 /14 7 /17 7 /17 7 /17 77 77 77 77 77 77 77 77 77 77 77 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 77 77 77 77 77 77 77 77 77 75 75 75 75 75 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 54.0 54.0 56.2 56.2 56.2 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 54.1 54.1 54.1 54.2 54.2 54.2 54.3 54.3 54.3 54.2 54.2 54.2 55.0 55.0 55.0 59.2 59.2 59.2 59.2 59.2 59.2 55.7 55.7 55.7 53.6 53.6 53.6 53.6 53.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 39,863 39,863 56,744 56,744 56,744 39,442 39,442 39,442 38,892 38,892 38,892 38,103 38,103 38,103 33,592 33,592 33,592 34,897 34,897 34,897 34,003 34,003 34,003 35,816 35,816 35,816 36,470 36,470 36,470 34,741 34,741 34,741 34,831 34,831 34,831 37,314 37,314 37,314 35,254 35,254 35,254 38,640 38,640 Coil Latent Load Btu/h 6,796 6,796 9,854 9,854 9,854 5,777 5,777 5,777 6,391 6,391 6,391 5,604 5,604 5,604 5,367 5,367 5,367 5,370 5,370 5,370 5,157 5,157 5,157 5,519 5,519 5,519 4,557 4,557 4,557 6,531 6,531 6,531 6,553 6,553 6,553 6,544 6,544 6,544 6,433 6,433 6,433 6,671 6,671 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 68 of 100 SPACE Floor Area ft² System Zone Room Zone - 298 spc_sp_24 Zone - 299 Zone - 299 spc_sp_25 Zone - 300 Zone - 300 spc_sp_26 Zone - 301 Zone - 301 spc_sp_27 Zone - 302 Zone - 302 spc_sp_28 Zone - 303 Zone - 303 spc_sp_29 Zone - 304 Zone - 304 spc_sp_30 Zone - 305 Zone - 305 spc_sp_31 Zone - 306 Zone - 306 spc_sp_32 Zone - 307 Zone - 307 spc_sp_33 Zone - 308 Zone - 308 spc_sp_34 Zone - 309 Zone - 309 spc_sp_35 Zone - 310 Zone - 310 spc_sp_36 Zone - 311 Zone - 311 spc_sp_37 Zone - 312 Zone - 312 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 1,082 7 /18 1,074 7 /18 1,074 1,074 7 /18 955 7 /18 955 955 7 /18 995 9 /16 995 995 9 /16 894 7 /17 894 894 7 /17 1,063 10 /15 1,063 1,063 10 /15 684 6/10 684 684 6 /10 2,070 9 /16 2,070 2,070 9 /16 1,251 9 /16 1,251 1,251 9 /16 1,251 7 /17 1,251 1,251 7 /17 1,525 9 /16 1,525 1,525 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 73 73 73 73 73 73 73 77 77 77 75 75 75 80 80 80 65 65 65 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 65 65 65 65 65 65 65 67 67 67 66 66 66 63 63 63 58 58 58 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 53.4 53.1 53.1 53.1 53.6 53.6 53.6 55.1 55.1 55.1 55.0 55.0 55.0 56.6 56.6 56.6 55.8 55.8 55.8 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 24,586 22,945 22,945 22,945 22,834 22,834 22,834 37,026 37,026 37,026 29,118 29,118 29,118 36,090 36,090 36,090 18,202 18,202 18,202 52,942 52,942 52,942 35,189 35,189 35,189 31,103 31,103 31,103 60,677 60,677 60,677 29,082 29,082 29,082 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 3,741 3,711 3,711 3,711 3,304 3,304 3,304 3,697 3,697 3,697 2,943 2,943 2,943 2,737 2,737 2,737 1,813 1,813 1,813 7,679 7,679 7,679 4,645 4,645 4,645 4,115 4,115 4,115 5,660 5,660 5,660 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 75 75 75 75 75 75 75 77 77 77 75 75 75 77 77 77 76 76 76 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 66 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 53.6 53.6 53.6 53.6 53.9 53.9 53.9 55.1 55.1 55.1 55.0 55.0 55.0 56.7 56.7 56.7 60.6 60.6 60.6 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 Coil Airflow cfm Coil Sensible Load Btu/h 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 38,640 36,369 36,369 36,369 35,270 35,270 35,270 51,628 51,628 51,628 42,996 42,996 42,996 51,414 51,414 51,414 22,226 22,226 22,226 79,873 79,873 79,873 52,725 52,725 52,725 48,027 48,027 48,027 82,120 82,120 82,120 41,372 41,372 41,372 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 Coil Latent Load Btu/h 6,671 6,615 6,615 6,615 5,894 5,894 5,894 6,966 6,966 6,966 5,530 5,530 5,530 7,439 7,439 7,439 4,311 4,311 4,311 14,458 14,458 14,458 8,749 8,749 8,749 7,730 7,730 7,730 10,664 10,664 10,664 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 69 of 100 SPACE Floor Area ft² System Zone Room spc_sp_7 Zone - 313 Zone - 313 spc_sp_8 Zone - 314 Zone - 314 spc_sp_9 Zone - 315 Zone - 315 spc_sp_10 Zone - 316 Zone - 316 spc_sp_11 Zone - 317 Zone - 317 spc_sp_12 Zone - 318 Zone - 318 spc_sp_13 Zone - 319 Zone - 319 spc_sp_14 Zone - 320 Zone - 320 spc_sp_15 Zone - 321 Zone - 321 spc_sp_16 Zone - 322 Zone - 322 spc_sp_17 Zone - 323 Zone - 323 spc_sp_18 Zone - 324 Zone - 324 spc_sp_19 Zone - 325 Zone - 325 spc_sp_20 Zone - 326 Zone - 326 spc_sp_21 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 290 290 290 442 442 442 2,070 2,070 2,070 1,103 1,103 1,103 915 915 915 3,084 3,084 3,084 437 437 437 344 344 344 231 231 231 382 382 382 358 358 358 1,082 1,082 1,082 960 960 960 1,040 1,040 1,040 1,040 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 6 /18 6 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 6 /18 6 /18 7 /18 7 /18 9 /12 9 /12 6 /10 6 /10 6 /9 6 /9 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 70 70 70 70 70 70 75 75 75 76 76 76 76 76 76 75 75 75 70 70 70 73 73 73 73 73 73 65 65 65 62 62 62 73 73 73 73 73 73 73 73 73 73 63 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 65 65 65 63 63 63 58 58 58 58 58 58 65 65 65 65 65 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.0 57.0 57.0 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 56.2 56.2 56.2 56.0 56.0 56.0 53.0 53.0 53.0 53.2 53.2 53.2 54.2 54.2 54.2 53.1 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 17,557 17,557 17,557 19,208 19,208 19,208 47,533 47,533 47,533 12,788 12,788 12,788 10,607 10,607 10,607 60,225 60,225 60,225 28,451 28,451 28,451 19,387 19,387 19,387 8,323 8,323 8,323 11,887 11,887 11,887 10,175 10,175 10,175 22,813 22,813 22,813 20,987 20,987 20,987 28,726 28,726 28,726 22,182 929 929 929 1,375 1,375 1,375 6,804 6,804 6,804 3,865 3,865 3,865 3,206 3,206 3,206 10,127 10,127 10,127 1,358 1,358 1,358 1,192 1,192 1,192 713 713 713 1,013 1,013 1,013 951 951 951 3,739 3,739 3,739 3,318 3,318 3,318 3,598 3,598 3,598 3,594 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /12 9 /12 7 /18 7 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /12 9 /12 7 /15 7 /15 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 73 73 73 73 73 73 75 75 75 76 76 76 76 76 76 75 75 75 73 73 73 73 73 73 73 73 73 77 77 77 76 76 76 75 75 75 75 75 75 75 75 75 75 63 63 63 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 57.6 57.6 57.6 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 60.1 60.1 60.1 57.9 57.9 57.9 53.5 53.5 53.5 53.7 53.7 53.7 54.4 54.4 54.4 53.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 20,529 20,529 20,529 26,244 26,244 26,244 76,434 76,434 76,434 26,279 26,279 26,279 21,797 21,797 21,797 101,628 101,628 101,628 36,070 36,070 36,070 25,678 25,678 25,678 11,070 11,070 11,070 14,327 14,327 14,327 14,201 14,201 14,201 36,302 36,302 36,302 32,911 32,911 32,911 43,793 43,793 43,793 35,131 Coil Latent Load Btu/h 1,393 1,393 1,393 2,856 2,856 2,856 12,774 12,774 12,774 6,912 6,912 6,912 5,733 5,733 5,733 18,995 18,995 18,995 2,820 2,820 2,820 2,221 2,221 2,221 1,110 1,110 1,110 2,357 2,357 2,357 2,261 2,261 2,261 6,665 6,665 6,665 5,915 5,915 5,915 6,420 6,420 6,420 6,406 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 70 of 100 SPACE Floor Area ft² System Zone Room Zone - 327 Zone - 327 spc_sp_1 Zone - 328 Zone - 328 spc_sp_2 Zone - 329 Zone - 329 spc_sp_3 Zone - 330 Zone - 330 spc_sp_4 Zone - 331 Zone - 331 spc_sp_5 Zone - 332 Zone - 332 spc_sp_6 Zone - 333 Zone - 333 Child Cntr 2 Zone - 359 Zone - 359 Child Cntr 3 Zone - 360 Zone - 360 Child Cntr 1 Zone - 361 Zone - 361 Portopia HP Portopia HP spc_SS 141/142 Office_0 Zone - 012 Zone - 012 spc_SS 144 Office C_0 Zone - 013 Zone - 013 spc_SS 160B-D_0 Zone - 014 Zone - 014 spc_PS 160A Storage_0 Zone - 015 Zone - 015 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,040 1,040 1,272 1,272 1,272 1,074 1,074 1,074 999 999 999 1,613 1,613 1,613 664 664 664 1,956 1,956 1,956 211 211 211 211 211 211 211 211 211 75,038 75,038 313 313 313 168 168 168 0 0 0 102 102 102 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 10 /15 10 /15 10 /16 10 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 6 /9 10 /15 10 /15 9 /11 9 /11 73 73 77 77 77 73 73 73 73 73 73 80 80 80 79 79 79 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 62 62 80 80 80 70 70 70 65 65 67 67 67 65 65 65 65 65 65 63 63 63 64 64 64 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 58 58 63 63 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Supply Dry Bulb °F 53.1 53.1 48.6 48.6 48.6 53.1 53.1 53.1 54.3 54.3 54.3 55.5 55.5 55.5 57.1 57.1 57.1 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 54.9 54.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 32 32 0 0 0 27 27 27 22,182 22,182 15,648 15,648 15,648 22,945 22,945 22,945 28,019 28,019 28,019 37,433 37,433 37,433 31,843 31,843 31,843 22,688 22,688 22,688 13,285 13,285 13,285 13,285 13,285 13,285 12,931 12,931 12,931 2,026,697 1,809,600 0 0 0 0 0 0 0 0 0 0 0 0 3,594 3,594 4,707 4,707 4,707 3,711 3,711 3,711 3,457 3,457 3,457 4,151 4,151 4,151 1,840 1,840 1,840 6,857 6,857 6,857 559 559 559 559 559 559 370 370 370 246,137 246,507 181 181 181 97 97 97 0 0 0 -2 -2 -2 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 6 /9 9 /16 9 /16 9 /11 9 /11 75 75 76 76 76 75 75 75 75 75 75 77 77 77 77 77 77 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 62 62 77 77 77 70 70 70 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 58 58 67 67 67 63 63 63 53.6 53.6 48.8 48.8 48.8 53.6 53.6 53.6 54.5 54.5 54.5 56.4 56.4 56.4 57.3 57.3 57.3 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 55.1 56.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Coil Airflow cfm 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 32 32 0 0 0 27 27 27 Coil Sensible Load Btu/h 35,131 35,131 31,358 31,358 31,358 36,369 36,369 36,369 42,495 42,495 42,495 56,782 56,782 56,782 43,282 43,282 43,282 46,620 46,620 46,620 14,677 14,677 14,677 14,677 14,677 14,677 14,524 14,524 14,524 3,006,774 2,862,181 0 0 0 0 0 0 0 0 0 0 0 0 Coil Latent Load Btu/h 6,406 6,406 7,970 7,970 7,970 6,615 6,615 6,615 6,169 6,169 6,169 11,281 11,281 11,281 4,645 4,645 4,645 12,262 12,262 12,262 694 694 694 694 694 694 460 460 460 480,065 462,701 0 0 0 0 0 0 0 0 0 0 0 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 71 of 100 SPACE Floor Area ft² System Zone Room spc_SS 160 Class C_0 Zone - 016 Zone - 016 spc_SS 162 Class_0 Zone - 017 Zone - 017 spc_PS 112 Office C_0 Zone - 018 Zone - 018 spc_PS 111-115 Office C_0 Zone - 019 Zone - 019 spc_PS Lecture 117 C_0 Zone - 020 Zone - 020 spc_PS Lecture FC-4C_0 Zone - 021 Zone - 021 spc_PS 120-128 Class_0 Zone - 022 Zone - 022 spc_PS Class 121/122_0 Zone - 023 Zone - 023 spc_PS 130 Auditorium C_0 Zone - 024 Zone - 024 PS Fan Coil Htg Only PS Fan Coil Htg Only spc_SS 171-173, 178 Office C_0 Zone - 037 Zone - 037 spc_SS 135 Office_0 Zone - 038 Zone - 038 spc_SS Corridor 120 C_0 Zone - 039 Zone - 039 spc_SS 180 Worm Rm VAV-20_0 Zone - 040 Zone - 040 spc_SS 110C Wrk Rm C_0 Zone - 041 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 565 565 565 967 967 967 215 215 215 602 602 602 1,126 1,126 1,126 1,036 1,036 1,036 886 886 886 695 695 695 1,413 1,413 1,413 8,090 8,090 561 561 561 92 92 92 1,787 1,787 1,787 326 326 326 766 766 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 10 /16 10 /16 9 /17 9 /17 7 /18 7 /18 6 /9 6 /9 7 /16 7 /16 10 /16 10 /16 10 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 6 /9 70 70 70 70 70 70 79 79 79 79 79 79 76 76 76 73 73 73 62 62 62 76 76 76 79 79 79 79 79 76 76 76 76 76 76 76 76 76 79 79 79 62 62 63 63 63 63 63 63 64 64 64 64 64 64 67 67 67 65 65 65 58 58 58 66 66 66 64 64 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 274 274 274 45 45 45 378 378 378 616 616 616 1,984 1,984 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,317 5,317 5,317 875 875 875 7,342 7,342 7,342 11,961 11,961 11,961 38,530 38,530 836 836 836 1,430 1,430 1,430 157 157 157 435 435 435 1,356 1,356 1,356 1,374 1,374 1,374 1,392 1,392 1,392 992 992 992 2,191 2,191 2,191 10,439 7,971 1,465 1,465 1,465 241 241 241 2,794 2,794 2,794 902 902 902 2,030 2,030 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 7 /18 7 /18 7 /9 7 /9 7 /16 7 /16 9 /16 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 7 /10 70 70 70 70 70 70 79 79 79 76 76 76 76 76 76 73 73 73 64 64 64 76 76 76 77 77 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 67 67 63 63 63 63 63 63 64 64 64 67 67 67 67 67 67 65 65 65 59 59 59 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 60 60 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 268 268 268 44 44 44 364 364 364 593 593 593 1,874 1,874 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,089 5,089 5,089 838 838 838 5,425 5,425 5,425 13,863 13,863 13,863 40,338 40,338 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2,917 2,917 2,917 480 480 480 4,022 4,022 4,022 2,276 2,276 2,276 2,929 2,929 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 72 of 100 SPACE System Zone Room Zone - 041 Block spc_SS 110 Wrk Rm/Office C_0 Peak Zone - 042 Peak Zone - 042 Block Peak spc_SS 100 100H 111H Main Lobby C_0 Zone - 043 Peak Zone - 043 Block spc_SS 150 Wrk Rm C_0 Peak Zone - 044 Peak Zone - 044 Block spc_SS 177-179 Office_0 Peak Zone - 045 Peak Zone - 045 Block spc_SS Wrk Rm1 V-19_0 Peak Zone - 046 Peak Zone - 046 Block spc_SS 120-124 C_0 Peak Zone - 047 Peak Zone - 047 Block spc_SS 135-139 Office C_0 Peak Zone - 048 Peak Zone - 048 Block spc_SS 140 Wrk Rm C_0 Peak Zone - 049 Peak Zone - 049 Block spc_SS 125-129_0 Peak Zone - 050 Peak Zone - 050 Block spc_SS 230B Office C_0 Peak Zone - 051 Peak Zone - 051 Block spc_SS 214 Office C_0 Peak Zone - 052 Peak Zone - 052 Block spc_SS 282 Wrk Rm C_0 Peak Zone - 053 Peak Zone - 053 Block spc_SS 280D Office_0 Peak Zone - 054 Peak Zone - 054 Block spc_SS 280A-C C_0 Peak Zone - 055 Peak Zone - 055 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 766 1,420 1,420 1,420 37 37 37 301 301 301 635 635 635 207 207 207 703 703 703 586 586 586 848 848 848 642 642 642 285 285 285 130 130 130 136 136 136 154 154 154 459 459 459 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /9 9 /17 9 /17 7 /18 7 /18 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 6/9 6 /9 7 /16 7 /16 9 /16 9 /16 6 /18 6 /18 6 /18 6 /18 10 /16 10 /16 10 /16 10 /16 7 /17 7 /17 9 /11 9 /11 62 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 62 62 62 76 76 76 77 77 77 70 70 70 70 70 70 79 79 79 79 79 79 75 75 75 70 70 70 58 67 67 67 65 65 65 66 66 66 66 66 66 66 66 66 58 58 58 66 66 66 67 67 67 63 63 63 63 63 63 64 64 64 64 64 64 66 66 66 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,984 844 844 844 348 348 348 167 167 167 310 310 310 115 115 115 1,253 1,253 1,253 286 286 286 545 545 545 1,766 1,766 1,766 526 526 526 623 623 623 1,441 1,441 1,441 75 75 75 1,255 1,255 1,255 38,530 16,389 16,389 16,389 6,755 6,755 6,755 3,248 3,248 3,248 6,019 6,019 6,019 2,238 2,238 2,238 24,336 24,336 24,336 5,555 5,555 5,555 10,576 10,576 10,576 34,294 34,294 34,294 10,214 10,214 10,214 12,096 12,096 12,096 27,981 27,981 27,981 1,450 1,450 1,450 24,365 24,365 24,365 2,030 4,101 4,101 4,101 63 63 63 1,044 1,044 1,044 1,658 1,658 1,658 719 719 719 1,862 1,862 1,862 1,530 1,530 1,530 3,146 3,146 3,146 1,992 1,992 1,992 572 572 572 244 244 244 378 378 378 408 408 408 1,469 1,469 1,469 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /10 9 /17 9 /17 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /10 7 /10 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /11 9 /11 67 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 67 67 67 76 76 76 77 77 77 73 73 73 73 73 73 77 77 77 77 77 77 75 75 75 70 70 70 60 67 67 67 65 65 65 67 67 67 67 67 67 67 67 67 60 60 60 67 67 67 67 67 67 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 63 63 63 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,874 844 844 844 348 348 348 165 165 165 304 304 304 114 114 114 1,181 1,181 1,181 280 280 280 545 545 545 1,745 1,745 1,745 522 522 522 610 610 610 1,360 1,360 1,360 75 75 75 1,255 1,255 1,255 40,338 16,959 16,959 16,959 8,572 8,572 8,572 3,134 3,134 3,134 5,761 5,761 5,761 2,159 2,159 2,159 25,288 25,288 25,288 5,317 5,317 5,317 10,803 10,803 10,803 37,007 37,007 37,007 11,167 11,167 11,167 14,956 14,956 14,956 32,179 32,179 32,179 3,723 3,723 3,723 28,088 28,088 28,088 Coil Latent Load Btu/h 2,929 7,387 7,387 7,387 90 90 90 2,099 2,099 2,099 3,302 3,302 3,302 1,446 1,446 1,446 2,687 2,687 2,687 3,047 3,047 3,047 5,923 5,923 5,923 4,132 4,132 4,132 1,239 1,239 1,239 651 651 651 953 953 953 703 703 703 2,386 2,386 2,386 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 73 of 100 SPACE System Zone Room spc_SS 272 Wrk Rm C_0 Peak Zone - 056 Peak Zone - 056 Block spc_SS 270C/D Office_0 Peak Zone - 057 Peak Zone - 057 Block spc_SS 111H Hall_0 Peak Zone - 058 Peak Zone - 058 Block spc_SS 110G/H Offices C_0 Peak Zone - 059 Peak Zone - 059 Block spc_SS 111A Office C_0 Peak Zone - 060 Peak Zone - 060 Block spc_SS 242 Wrk Rm C_0 Peak Zone - 061 Peak Zone - 061 Block spc_SS 240L Office C_0 Peak Zone - 062 Peak Zone - 062 Block spc_SS 240H Office_0 Peak Zone - 063 Peak Zone - 063 Block spc_SS 240F/J Office_0 Peak Zone - 064 Peak Zone - 064 Block spc_SS 240-260A Wrk Rm C_0 Peak Zone - 065 Peak Zone - 065 Block spc_SS 202/250B Office_0 Peak Zone - 066 Peak Zone - 066 Block spc_SS 250 Wrk Rm C_0 Peak Zone - 067 Peak Zone - 067 Block spc_SS 251 Wrk Rm C_0 Peak Zone - 068 Peak Zone - 068 Block Peak spc_SS 230H, 200-201, 251H, 272H_0 Zone - 069 Peak Zone - 069 Block spc_SS 210/211 Wrk Rm C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 778 778 778 287 287 287 397 397 397 269 269 269 216 216 216 642 642 642 149 149 149 181 181 181 274 274 274 865 865 865 214 214 214 0 0 0 388 388 388 4,383 4,383 4,383 308 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /12 9 /12 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 10 /16 10 /16 7 /16 7 /16 6 /9 6 /9 9 /12 9 /12 7 /16 7 /16 7 /15 70 70 70 73 73 73 73 73 73 76 76 76 76 76 76 79 79 79 75 75 75 76 76 76 75 75 75 79 79 79 76 76 76 62 62 62 73 73 73 76 76 76 77 63 63 63 63 63 63 65 65 65 66 66 66 66 66 66 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 66 66 66 58 58 58 63 63 63 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,090 1,090 1,090 379 379 379 175 175 175 131 131 131 105 105 105 406 406 406 73 73 73 89 89 89 133 133 133 1,257 1,257 1,257 104 104 104 16 16 16 387 387 387 2,716 2,716 2,716 171 21,179 21,179 21,179 7,364 7,364 7,364 3,399 3,399 3,399 2,552 2,552 2,552 2,048 2,048 2,048 7,890 7,890 7,890 1,410 1,410 1,410 1,719 1,719 1,719 2,589 2,589 2,589 24,416 24,416 24,416 2,028 2,028 2,028 304 304 304 7,518 7,518 7,518 52,749 52,749 52,749 3,325 2,489 2,489 2,489 627 627 627 612 612 612 703 703 703 564 564 564 1,777 1,777 1,777 397 397 397 474 474 474 728 728 728 2,394 2,394 2,394 559 559 559 0 0 0 1,195 1,195 1,195 15,399 15,399 15,399 1,069 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /13 9 /13 9 /13 9 /13 7 /18 7 /18 9 /17 9 /17 9 /17 9 /17 7 /16 7 /16 7 /17 7 /17 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 9 /17 9 /17 7 /10 7 /10 9 /12 9 /12 7 /16 7 /16 7 /16 75 75 75 75 75 75 73 73 73 76 76 76 76 76 76 76 76 76 75 75 75 76 76 76 75 75 75 77 77 77 76 76 76 67 67 67 73 73 73 76 76 76 76 65 65 65 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 60 60 60 63 63 63 66 66 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 918 918 918 357 357 357 175 175 175 129 129 129 103 103 103 394 394 394 73 73 73 87 87 87 133 133 133 1,221 1,221 1,221 102 102 102 15 15 15 387 387 387 2,716 2,716 2,716 171 25,380 25,380 25,380 10,543 10,543 10,543 3,469 3,469 3,469 2,443 2,443 2,443 1,960 1,960 1,960 17,212 17,212 17,212 3,620 3,620 3,620 1,646 1,646 1,646 6,646 6,646 6,646 38,964 38,964 38,964 1,941 1,941 1,941 312 312 312 8,858 8,858 8,858 113,463 113,463 113,463 7,815 Coil Latent Load Btu/h 4,471 4,471 4,471 973 973 973 790 790 790 1,400 1,400 1,400 1,123 1,123 1,123 4,042 4,042 4,042 684 684 684 943 943 943 1,256 1,256 1,256 6,040 6,040 6,040 1,112 1,112 1,112 0 0 0 1,856 1,856 1,856 27,598 27,598 27,598 1,937 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 74 of 100 SPACE Floor Area ft² System Zone Room Zone - 070 Zone - 070 spc_SS 230F Office C_0 Zone - 071 Zone - 071 spc_SS Wrk Rm 230 C_0 Zone - 072 Zone - 072 spc_SS 230C-E Office_0 Zone - 073 Zone - 073 spc_SS 240B Wrk Rm C_0 Zone - 074 Zone - 074 spc_SS 181 Comp Rm C_0 Zone - 075 Zone - 075 spc_SS 182 Comp Rm C_0 Zone - 076 Zone - 076 Stdnt Srv VAV Stdnt Srv VAV Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 308 308 7 /15 180 6 /18 180 180 6 /18 987 7 /16 987 987 7 /16 630 6 /18 630 630 6 /18 240 10 /16 240 240 10 /16 854 7 /18 854 854 7/18 863 9 /11 863 863 9 /11 23,178 23,178 7 /17 77 77 70 70 70 76 76 76 70 70 70 79 79 79 73 73 73 70 70 70 75 75 66 66 63 63 63 66 66 66 63 63 63 64 64 64 65 65 65 63 63 63 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 171 171 330 330 330 550 550 550 1,887 1,887 1,887 607 607 607 2,223 2,223 2,223 2,317 2,317 2,317 27,996 21,892 3,325 3,325 6,408 6,408 6,408 10,680 10,680 10,680 36,641 36,641 36,641 11,782 11,782 11,782 43,184 43,184 43,184 45,011 45,011 45,011 543,738 425,196 1,069 1,069 360 360 360 3,468 3,468 3,468 1,262 1,262 1,262 663 663 663 2,471 2,471 2,471 2,243 2,243 2,243 66,071 67,555 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 7 /18 7 /18 9 /11 9 /11 7 /17 76 76 73 73 73 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 75 75 66 66 65 65 65 66 66 66 65 65 65 67 67 67 65 65 65 63 63 63 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 171 171 326 326 326 550 550 550 1,854 1,854 1,854 595 595 595 2,223 2,223 2,223 2,317 2,317 2,317 27,337 21,892 7,815 7,815 9,430 9,430 9,430 25,113 25,113 25,113 48,827 48,827 48,827 15,938 15,938 15,938 45,640 45,640 45,640 49,534 49,534 49,534 713,169 592,652 1,937 1,937 781 781 781 6,215 6,215 6,215 2,736 2,736 2,736 1,674 1,674 1,674 4,381 4,381 4,381 3,536 3,536 3,536 122,218 121,687 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 75 of 100 SPACE Floor Area ft² System Zone Room OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 58.1 58.1 58.1 51.6 51.6 51.6 55.0 55.0 55.0 56.7 56.7 56.7 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.8 57.8 57.8 52.5 52.5 52.5 69.6 69.6 69.6 57.6 57.6 54.7 54.7 54.7 54.6 54.6 54.6 49.8 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 19,718 19,718 19,718 27,717 27,717 27,717 4,324 4,324 4,324 8,470 8,470 8,470 10,677 10,677 10,677 33,208 33,208 33,208 3,217 3,217 3,217 2,438 2,438 2,438 46,648 46,648 46,648 8,293 8,293 8,293 13,658 13,658 13,658 178,368 160,203 45,748 45,748 45,748 34,617 34,617 34,617 7,681 649 649 649 6,690 6,690 6,690 0 0 0 601 601 601 686 686 686 2,099 2,099 2,099 935 935 935 708 708 708 1,884 1,884 1,884 1,710 1,710 1,710 -741 -741 -741 15,221 21,247 6,031 6,031 6,031 4,790 4,790 4,790 2,079 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F Coil Airflow cfm Coil Sensible Load Btu/h 1,270 1,270 1,270 1,220 1,220 1,220 228 228 228 496 496 496 614 614 614 1,911 1,911 1,911 126 126 126 96 96 96 2,937 2,937 2,937 381 381 381 1,175 1,175 1,175 10,454 10,454 2,377 2,377 2,377 1,780 1,780 1,780 311 21,552 21,552 21,552 27,487 27,487 27,487 4,459 4,459 4,459 10,580 10,580 10,580 12,077 12,077 12,077 35,790 35,790 35,790 8,578 8,578 8,578 6,500 6,500 6,500 64,856 64,856 64,856 8,454 8,454 8,454 27,101 27,101 27,101 227,433 211,887 48,957 48,957 48,957 37,048 37,048 37,048 18,754 Coil Latent Load Btu/h Alternative 4 spc_A 121 Office UC_0 Zone - 077 Zone - 077 spc_A 130A Class? FC1-4_0 Zone - 078 Zone - 078 spc_A 237-241 Office C_0 Zone - 093 Zone - 093 spc_A 202A Office D_0 Zone - 094 Zone - 094 spc_A 202A Office B_0 Zone - 095 Zone - 095 spc_A 202A Office C_0 Zone - 096 Zone - 096 spc_A 201 Office C_0 Zone - 097 Zone - 097 spc_A 200H-J Office C_0 Zone - 098 Zone - 098 spc_A 200 Office C_0 Zone - 099 Zone - 099 spc_A 210A-B Stairs C_0 Zone - 100 Zone - 100 spc_A 121 Restroom FC05_0 Zone - 118 Zone - 118 Admin FC Admin FC spc_A 161/162 Class C_0 Zone - 091 Zone - 091 spc_A 160 Wrk Rm C_0 Zone - 092 Zone - 092 spc_A 236A/B Offices_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak 348 348 348 2,606 2,606 2,606 0 0 0 344 344 344 238 238 238 891 891 891 353 353 353 267 267 267 1,011 1,011 1,011 1,111 1,111 1,111 734 734 734 7,905 7,905 2,273 2,273 2,273 1,806 1,806 1,806 786 10 /16 10 /16 10 /15 10 /15 7 /16 7 /16 6 /10 6 /10 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 7 /18 7 /18 10 /16 10 /16 9 /16 6 /9 6 /9 6 /9 6 /9 7 /17 79 79 79 80 80 80 76 76 76 65 65 65 76 76 76 73 73 73 75 75 75 75 75 75 79 79 79 73 73 73 79 79 79 77 77 62 62 62 62 62 62 75 64 64 64 63 63 63 66 66 66 58 58 58 67 67 67 65 65 65 66 66 66 66 66 66 64 64 64 65 65 65 64 64 64 67 67 58 58 58 58 58 58 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 9 /17 9 /17 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 9 /16 7 /9 7 /9 7 /9 7 /9 7 /17 77 77 77 77 77 77 76 76 76 76 76 76 76 76 76 73 73 73 75 75 75 75 75 75 77 77 77 73 73 73 77 77 77 77 77 64 64 64 64 64 64 75 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 65 65 65 66 66 66 66 66 66 67 67 67 65 65 65 67 67 67 67 67 59 59 59 59 59 59 66 58.4 58.4 58.4 51.8 51.8 51.8 55.0 55.0 55.0 63.1 63.1 63.1 56.4 56.4 56.4 56.4 56.4 56.4 49.2 49.2 49.2 49.2 49.2 49.2 57.9 57.9 57.9 52.5 52.5 52.5 69.8 69.8 69.8 58.0 59.2 55.1 55.1 55.1 54.9 54.9 54.9 49.8 1,735 1,735 1,735 18,165 18,165 18,165 0 0 0 1,536 1,536 1,536 1,234 1,234 1,234 3,864 3,864 3,864 1,611 1,611 1,611 1,221 1,221 1,221 5,037 5,037 5,037 2,205 2,205 2,205 -7,656 -7,656 -7,656 28,952 30,207 9,347 9,347 9,347 7,420 7,420 7,420 3,579 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 76 of 100 SPACE Floor Area ft² System Zone Room Zone - 113 Zone - 113 spc_A 244/246 Office C_0 Zone - 114 Zone - 114 spc_A 242/243 Class C_0 Zone - 115 Zone - 115 spc_A 238-246 Offices C_0 Zone - 116 Zone - 116 spc_A 216/218 Office C_0 Zone - 117 Zone - 117 Admin Pckg AHU Admin Pckg AHU spc_A 277F Class_0 Zone - 079 Zone - 079 spc_A 279A Hall C_0 Zone - 080 Zone - 080 spc_A 278A Cond Stair_0 Zone - 081 Zone - 081 spc_A 170/171 Lobby C_0 Zone - 082 Zone - 082 spc_A 172 Wrk Rm C_0 Zone - 083 Zone - 083 spc_A Wrk Rm 173 C_0 Zone - 084 Zone - 084 spc_A 177 Comp C_1 Zone - 085 Zone - 085 spc_A 174-176 Data C_0 Zone - 086 Zone - 086 spc_A 177 Comp C_0 Zone - 087 Zone - 087 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 786 786 367 367 367 1,839 1,839 1,839 2,547 2,547 2,547 2,057 2,057 2,057 11,676 11,676 1,395 1,395 1,395 7,584 7,584 7,584 321 321 321 1,279 1,279 1,279 2,002 2,002 2,002 671 671 671 626 626 626 201 201 201 626 626 626 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 10 /16 10 /16 6 /10 6 /10 7 /17 7 /17 6 /10 6/18 6 /18 6 /10 6 /10 9 /11 9 /11 7 /18 7 /18 6 /9 6 /9 10 /15 10 /15 6 /9 6 /9 9 /16 9 /16 7 /16 7 /16 75 75 75 75 75 79 79 79 65 65 65 75 75 75 65 65 70 70 70 65 65 65 70 70 70 73 73 73 62 62 62 80 80 80 62 62 62 77 77 77 76 76 76 66 66 66 66 66 64 64 64 58 58 58 66 66 66 58 58 63 63 63 58 58 58 63 63 63 65 65 65 58 58 58 63 63 63 58 58 58 67 67 67 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 70.0 70.0 70.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.8 49.8 49.8 49.8 49.8 55.5 55.5 55.5 57.3 57.3 57.3 49.8 49.8 49.8 55.4 55.4 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,510 2,510 2,510 5,680 5,680 5,680 1,443 1,443 1,443 483 483 483 2,570 2,570 2,570 1,214 1,214 1,214 1,490 1,490 1,490 1,917 1,917 1,917 1,042 1,042 1,042 7,681 7,681 3,589 3,589 3,589 49,570 49,570 49,570 81,320 81,320 81,320 20,104 20,104 20,104 242,629 193,483 46,615 46,615 46,615 105,509 105,509 105,509 26,795 26,795 26,795 8,969 8,969 8,969 47,731 47,731 47,731 22,553 22,553 22,553 27,671 27,671 27,671 31,338 31,338 31,338 19,354 19,354 19,354 2,079 2,079 971 971 971 5,095 5,095 5,095 4,472 4,472 4,472 5,442 5,442 5,442 28,881 25,762 4,376 4,376 4,376 5,555 5,555 5,555 411 411 411 2,208 2,208 2,208 5,370 5,370 5,370 1,747 1,747 1,747 1,303 1,303 1,303 497 497 497 1,843 1,843 1,843 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 7 /17 7 /17 7 /16 7 /18 7 /18 7 /16 7 /16 9 /11 9 /11 7 /9 7 /9 7 /9 7 /9 9 /16 9 /16 7 /9 7 /9 9 /16 9 /16 9 /16 9 /16 75 75 75 75 75 77 77 77 76 76 76 75 75 75 76 76 73 73 73 76 76 76 70 70 70 64 64 64 64 64 64 77 77 77 64 64 64 77 77 77 77 77 77 66 66 66 66 66 67 67 67 66 66 66 66 66 66 66 66 65 65 65 66 66 66 63 63 63 59 59 59 59 59 59 67 67 67 59 59 59 67 67 67 67 67 67 49.8 49.8 49.8 49.8 49.8 55.6 55.6 55.6 64.0 64.0 64.0 49.8 49.8 49.8 58.0 60.0 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 Coil Airflow cfm Coil Sensible Load Btu/h 311 311 145 145 145 2,701 2,701 2,701 4,948 4,948 4,948 813 813 813 13,075 13,075 2,485 2,485 2,485 3,475 3,475 3,475 1,443 1,443 1,443 420 420 420 2,508 2,508 2,508 1,209 1,209 1,209 1,469 1,469 1,469 1,917 1,917 1,917 1,032 1,032 1,032 18,754 18,754 8,763 8,763 8,763 78,514 78,514 78,514 92,985 92,985 92,985 49,087 49,087 49,087 334,108 299,894 66,753 66,753 66,753 177,138 177,138 177,138 30,401 30,401 30,401 10,395 10,395 10,395 48,380 48,380 48,380 23,906 23,906 23,906 28,680 28,680 28,680 33,072 33,072 33,072 19,437 19,437 19,437 Coil Latent Load Btu/h 3,579 3,579 1,672 1,672 1,672 12,862 12,862 12,862 11,426 11,426 11,426 9,369 9,369 9,369 55,677 63,035 9,143 9,143 9,143 15,367 15,367 15,367 511 511 511 2,145 2,145 2,145 8,439 8,439 8,439 4,762 4,762 4,762 2,059 2,059 2,059 835 835 835 3,541 3,541 3,541 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 77 of 100 SPACE System Zone Room spc_A 179/178 Data C_0 Peak Zone - 088 Peak Zone - 088 Block spc_A 180E Com Lab C_0 Peak Zone - 089 Peak Zone - 089 Block spc_A 271-277 Office C_0 Peak Zone - 111 Peak Zone - 111 Block spc_A 277 Class_0 Peak Zone - 112 Peak Zone - 112 Block Peak Admin VAV Admin VAV Block spc_BC 237 Class_0 Peak Zone - 334 Peak Zone - 334 Block spc_BC 221 Lobby_0 Peak Zone - 335 Peak Zone - 335 Block spc_BC 222 Class_0 Peak Zone - 336 Peak Zone - 336 Block spc_215-219 Office_0 Peak Zone - 337 Peak Zone - 337 Block spc_BC 224 Class_0 Peak Zone - 338 Peak Zone - 338 Block spc_BC 2nd 226/228 Class_0 Peak Zone - 339 Peak Zone - 339 Block spc_BC 2nd 230 Class_0 Peak Zone - 340 Peak Zone - 340 Block spc_BC 115/116 Office_0 Peak Zone - 351 Peak Zone - 351 Block spc_BC Office 137/139/141/142_0 Peak Zone - 352 Peak Zone - 352 Block spc_BC 143 Office_0 Peak Zone - 353 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 339 339 339 951 951 951 2,656 2,656 2,656 0 0 0 18,650 18,650 166 166 166 120 120 120 196 196 196 262 262 262 146 146 146 281 281 281 187 187 187 155 155 155 103 103 103 123 123 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 9 /15 10 /14 10 /14 7 /16 7 /16 7 /18 7 /18 10 /16 10 /16 9 /11 9 /11 9 /10 9 /10 9 /17 9 /17 9 /12 9 /12 10 /16 10 /16 10 /16 76 76 76 80 80 80 75 75 75 80 80 80 78 78 79 79 79 76 76 76 73 73 73 79 79 79 70 70 70 67 67 67 76 76 76 73 73 73 79 79 79 79 79 66 66 66 63 63 63 66 66 66 63 63 63 66 66 62 62 62 66 66 66 65 65 65 64 64 64 63 63 63 61 61 61 67 67 67 63 63 63 64 64 64 64 64 70.0 70.0 70.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 71.7 71.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 57.5 57.5 57.5 57.3 57.3 57.3 57.1 57.1 57.1 57.5 57.5 57.5 55.6 55.6 55.6 56.0 56.0 56.0 57.2 57.2 57.2 56.1 56.1 56.1 51.8 51.8 51.8 58.7 58.7 2,037 2,037 2,037 2,646 2,646 2,646 1,344 1,344 1,344 4,175 4,175 4,175 28,551 22,316 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 237 237 237 38 38 38 797 797 33,300 33,300 33,300 49,154 49,154 49,154 24,971 24,971 24,971 77,551 77,551 77,551 521,509 407,618 6,259 6,259 6,259 3,956 3,956 3,956 14,583 14,583 14,583 10,595 10,595 10,595 5,091 5,091 5,091 11,008 11,008 11,008 15,364 15,364 15,364 4,204 4,204 4,204 848 848 848 11,800 11,800 771 771 771 1,906 1,906 1,906 7,134 7,134 7,134 0 0 0 33,121 44,638 375 375 375 194 194 194 681 681 681 491 491 491 468 468 468 889 889 889 658 658 658 340 340 340 192 192 192 231 231 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /19 9 /19 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /14 9 /14 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 9 /12 9 /12 9 /11 9 /11 9 /17 9 /17 9 /12 9 /12 9 /17 9 /17 10 /16 71 71 71 77 77 77 76 76 76 77 77 77 77 77 77 77 77 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 76 76 76 73 73 73 76 76 76 79 79 66 66 66 67 67 67 66 66 66 67 67 67 67 67 66 66 66 66 66 66 65 65 65 67 67 67 63 63 63 63 63 63 67 67 67 63 63 63 67 67 67 64 64 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 55.3 58.2 58.2 58.2 57.3 57.3 57.3 57.1 57.1 57.1 57.7 57.7 57.7 56.5 56.5 56.5 56.3 56.3 56.3 57.2 57.2 57.2 56.1 56.1 56.1 52.2 52.2 52.2 58.7 58.7 Coil Airflow cfm Coil Sensible Load Btu/h 2,008 2,008 2,008 2,644 2,644 2,644 1,337 1,337 1,337 4,061 4,061 4,061 26,008 22,285 388 388 388 242 242 242 877 877 877 656 656 656 278 278 278 617 617 617 929 929 929 237 237 237 38 38 38 797 797 33,409 33,409 33,409 51,546 51,546 51,546 32,823 32,823 32,823 77,838 77,838 77,838 651,278 557,619 7,849 7,849 7,849 5,195 5,195 5,195 17,225 17,225 17,225 12,759 12,759 12,759 6,331 6,331 6,331 12,300 12,300 12,300 20,480 20,480 20,480 5,546 5,546 5,546 1,020 1,020 1,020 13,862 13,862 Coil Latent Load Btu/h 1,453 1,453 1,453 5,384 5,384 5,384 12,103 12,103 12,103 0 0 0 65,740 78,660 1,025 1,025 1,025 278 278 278 1,269 1,269 1,269 1,313 1,313 1,313 701 701 701 1,464 1,464 1,464 1,309 1,309 1,309 517 517 517 535 535 535 308 308 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 78 of 100 SPACE System Zone Room Zone - 353 spc_BC 109 Class_0 Zone - 354 Zone - 354 spc_BC 108 Class_0 Zone - 355 Zone - 355 spc_BC 106 Class_0 Zone - 356 Zone - 356 spc_BC 105 Class_0 Zone - 357 Zone - 357 spc_BC 101 Class_0 Zone - 358 Zone - 358 Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block BC FC Peak BC FC Block spc_BC 130 Cafe/Kitchen_0 Peak Zone - 341 Peak Zone - 341 Block spc_BC AH-2 245 Lecture_0 Peak Zone - 342 Peak Zone - 342 Block spc_BC AH-3 301 Class_0 Peak Zone - 343 Peak Zone - 343 Block spc_BC AH-4 302 Class_0 Peak Zone - 344 Peak Zone - 344 Block spc_BC 306 Office (AH-5)_0 Peak spc_BC 307-312 Office (AH-5)_0 Peak spc_BC AH-5 304 Hall_0 Peak Zone - 345 Peak Zone - 345 Block spc_BC AH-6 315 Lab_0 Peak Zone - 346 Peak Zone - 346 Block spc_BC AH-7 314 Class_0 Peak Zone - 347 Peak Zone - 347 Block spc_BC AH-8 313_0 Peak Zone - 348 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 123 248 248 248 228 228 228 287 287 287 308 308 308 696 696 696 3,507 3,507 1,908 1,908 1,908 809 809 809 162 162 162 188 188 188 17 107 518 642 642 181 181 181 183 183 183 518 518 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /16 9 /12 9 /12 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /12 7 /19 7 /19 9 /13 9 /13 7 /10 7 /10 11 /13 11 /13 7 /18 10 /16 7 /18 10/16 10 /16 10 /16 6 /9 6 /9 9 /16 79 73 73 73 73 73 73 70 70 70 70 70 70 70 70 70 73 73 71 71 71 75 75 75 67 67 67 71 71 71 73 79 73 79 79 79 79 79 62 62 62 77 77 64 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 64 64 64 65 65 65 60 60 60 58 58 58 65 64 65 64 64 64 64 64 58 58 58 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 58.7 53.9 53.9 53.9 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.8 56.8 49.0 49.0 49.0 48.5 48.5 48.5 57.5 57.5 57.5 55.0 55.0 55.0 57.7 59.1 54.7 58.0 58.0 58.3 58.3 58.3 56.9 56.9 56.9 55.0 55.0 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 902 902 902 435 435 435 1,005 1,005 11,800 5,234 5,234 5,234 6,925 6,925 6,925 15,674 15,674 15,674 16,788 16,788 16,788 36,297 36,297 36,297 164,625 128,212 25,681 25,681 25,681 8,768 8,768 8,768 9,949 9,949 9,949 14,106 14,106 14,106 1,203 14,924 6,067 22,194 20,846 13,789 13,789 13,789 7,351 7,351 7,351 19,025 19,025 231 766 766 766 704 704 704 918 918 918 985 985 985 2,230 2,230 2,230 10,125 10,014 7,496 7,496 7,496 2,709 2,709 2,709 457 457 457 435 435 435 41 199 801 1,041 657 394 394 394 486 486 486 1,924 1,924 10 /16 9 /13 9 /13 9 /12 9 /12 9 /11 9 /11 9 /11 9 /11 9 /11 9 /11 9 /13 7 /19 7 /19 9 /14 9 /14 7 /10 7 /10 9 /15 9 /15 7 /18 10 /16 7 /18 9 /17 9 /16 9 /16 7 /17 7 /17 9 /16 79 75 75 75 73 73 73 70 70 70 70 70 70 70 70 70 75 75 71 71 71 77 77 77 67 67 67 78 78 78 73 79 73 76 76 77 77 77 75 75 75 77 77 64 65 65 65 63 63 63 63 63 63 63 63 63 63 63 63 65 65 64 64 64 66 66 66 60 60 60 66 66 66 65 64 65 67 67 67 67 67 66 66 66 67 67 58.7 54.5 54.5 54.5 55.3 55.3 55.3 56.8 56.8 56.8 56.8 56.8 56.8 56.7 56.7 56.7 56.9 60.6 49.0 49.0 49.0 48.7 48.7 48.7 57.5 57.5 57.5 57.3 57.3 57.3 57.7 59.1 54.7 58.0 59.1 58.5 58.5 58.5 61.5 61.5 61.5 55.0 55.0 Coil Airflow cfm Coil Sensible Load Btu/h 797 259 259 259 372 372 372 925 925 925 990 990 990 2,124 2,124 2,124 9,730 9,730 1,003 1,003 1,003 334 334 334 616 616 616 744 744 744 75 1,035 314 1,425 1,425 902 902 902 435 435 435 1,005 1,005 13,862 6,369 6,369 6,369 8,775 8,775 8,775 17,730 17,730 17,730 19,220 19,220 19,220 40,708 40,708 40,708 195,368 154,845 28,282 28,282 28,282 10,394 10,394 10,394 11,797 11,797 11,797 17,273 17,273 17,273 1,823 19,637 7,596 29,057 27,346 18,690 18,690 18,690 9,470 9,470 9,470 25,235 25,235 Coil Latent Load Btu/h 308 1,430 1,430 1,430 1,096 1,096 1,096 1,494 1,494 1,494 1,603 1,603 1,603 3,631 3,631 3,631 17,976 18,247 13,513 13,513 13,513 4,960 4,960 4,960 624 624 624 1,481 1,481 1,481 75 265 1,033 1,373 1,870 1,012 1,012 1,012 1,133 1,133 1,133 3,625 3,625 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 79 of 100 SPACE Floor Area ft² System Zone Room Zone - 348 BC Hydronic AHU BC Hydronic AHU spc_CC 108 C_0 Zone - 120 Zone - 120 spc_CC 106 Mechanical C_0 Zone - 121 Zone - 121 spc_CC 203 Storage_0 Zone - 122 Zone - 122 spc_CC 202 Storage_0 Zone - 123 Zone - 123 spc_CC 201 Eating Area C_0 Zone - 124 Zone - 124 Campus Center Dual Deck Campus Center Dual Deck spc_CC Class 122-126 C_0 Zone - 119 Zone - 119 Campus Center FC Campus Center FC spc_CC 228 Comp C_0 Zone - 125 Zone - 125 Bookstore 1 Zone - 362 Zone - 362 Bookstore 2 Zone - 363 Zone - 363 Bookstore 3 Zone - 364 Zone - 364 Bookstore 4 Zone - 365 Zone - 365 Bookstore 5 Zone - 366 Zone - 366 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 518 4,592 4,592 381 381 381 530 530 530 159 159 159 133 133 133 1,974 1,974 1,974 3,176 3,176 1,023 1,023 1,023 1,023 1,023 519 519 519 915 915 915 915 915 915 915 915 915 915 915 915 915 915 915 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 9 /12 9 /12 9 /12 9 /12 10 /14 6 /18 6 /18 6 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 80 80 79 79 79 76 76 76 76 76 76 73 73 73 73 73 73 79 79 70 70 70 70 70 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 67 63 63 64 64 64 67 67 67 67 67 67 63 63 63 63 63 63 62 62 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.9 72.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 55.0 55.2 55.2 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.1 57.1 57.1 57.1 57.1 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 1,005 6,464 6,464 797 797 797 480 480 480 556 556 556 430 430 430 1,808 1,808 1,808 4,073 4,073 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 404 404 404 404 404 404 404 404 19,025 120,862 101,266 12,551 12,551 12,551 11,849 11,849 11,849 8,761 8,761 8,761 6,778 6,778 6,778 28,473 28,473 28,473 68,413 57,628 64,980 64,980 64,980 64,980 64,980 17,432 17,432 17,432 11,760 11,760 11,760 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 10,160 1,924 14,942 6,374 167 167 167 761 761 761 277 277 277 137 137 137 4,445 4,445 4,445 5,787 5,745 3,184 3,184 3,184 3,184 3,184 1,513 1,513 1,513 3,754 3,754 3,754 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 2,839 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /17 9 /17 9 /13 9 /13 9 /13 9 /13 9 /14 7 /18 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 77 77 77 76 76 76 76 76 76 76 76 76 75 75 75 75 75 75 77 77 73 73 73 73 73 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 76 67 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 65 65 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 55.0 55.8 58.3 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.9 57.4 57.4 57.4 57.4 57.4 55.7 55.7 55.7 48.1 48.1 48.1 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 49.4 Coil Airflow cfm Coil Sensible Load Btu/h 1,005 6,464 6,464 784 784 784 477 477 477 554 554 554 414 414 414 1,746 1,746 1,746 3,974 3,459 3,917 3,917 3,917 3,917 3,917 958 958 958 441 441 441 404 404 404 404 404 404 404 404 404 404 404 404 25,235 150,199 134,479 15,748 15,748 15,748 15,813 15,813 15,813 13,075 13,075 13,075 9,068 9,068 9,068 33,559 33,559 33,559 87,263 75,402 69,485 69,485 69,485 69,485 69,485 22,424 22,424 22,424 18,552 18,552 18,552 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 17,188 Coil Latent Load Btu/h 3,625 27,722 25,060 1,787 1,787 1,787 1,129 1,129 1,129 379 379 379 204 204 204 12,956 12,956 12,956 16,454 17,396 6,613 6,613 6,613 6,613 6,613 2,598 2,598 2,598 6,278 6,278 6,278 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 5,361 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 80 of 100 SPACE System Zone Room Floor Area ft² Bookstore 6 Peak Zone - 367 Peak Zone - 367 Block Campus Center Packg RTU-1 Peak Campus Center Packg RTU-1 Block spc_DM FC-Music Office_0 Peak Zone - 137 Peak Zone - 137 Block Peak spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0 Zone - 138 Peak Zone - 138 Block spc_DM FC 3-1 Dress Rms Int_0 Peak Zone - 139 Peak Zone - 139 Block spc_DM FC 3-1 Dress Rms_0 Peak Zone - 140 Peak Zone - 140 Block Drama/Music Fan Coil Peak Drama/Music Fan Coil Block spc_HP-9 Office_0 Peak Zone - 126 Peak Zone - 126 Block spc_DM HP-7 Storage_0 Peak Zone - 127 Peak Zone - 127 Block spc_DM HP-7 Dress Rm_0 Peak Zone - 128 Peak Zone - 128 Block spc_DM HP 3/4 Class_0 Peak Zone - 129 Peak Zone - 129 Block spc_DM HP-2 Class_0 Peak Zone - 130 Peak Zone - 130 Block spc_DM HP-5 Performance Rm_0 Peak Zone - 131 Peak Zone - 131 Block spc_DM HP-10 Prop Rm_0 Peak Zone - 132 Peak Zone - 132 Block spc_DM HP-1 Main Corridor_0 Peak Zone - 133 Peak Zone - 133 Block 915 915 915 6,007 6,007 338 338 338 892 892 892 267 267 267 327 327 327 1,824 1,824 121 121 121 57 57 57 9,797 9,797 9,797 926 926 926 569 569 569 1,176 1,176 1,176 1,131 1,131 1,131 7,381 7,381 7,381 Project Name: Dataset Name: SBCC TRACE.TRC OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 10 /16 10 /16 9 /17 9 /12 9 /12 10 /15 10 /15 10 /15 10 /15 6 /9 6 /9 11 /13 11 /13 9 /12 9 /12 7 /18 7 /18 9 /11 9 /11 76 76 76 76 76 79 79 79 75 75 75 76 76 76 79 79 79 76 76 73 73 73 80 80 80 80 80 80 62 62 62 71 71 71 73 73 73 73 73 73 70 70 70 66 66 66 66 66 64 64 64 66 66 66 66 66 66 64 64 64 67 67 63 63 63 63 63 63 63 63 63 58 58 58 58 58 58 63 63 63 65 65 65 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 49.4 49.4 49.4 51.0 51.0 56.4 56.4 56.4 54.3 54.3 54.3 44.5 44.5 44.5 58.3 58.3 58.3 55.7 55.7 57.0 57.0 57.0 54.8 54.8 54.8 51.3 51.3 51.3 55.4 55.4 55.4 59.2 59.2 59.2 53.5 53.5 53.5 57.4 57.4 57.4 56.2 56.2 56.2 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 10,160 10,160 10,160 79,989 79,989 8,123 8,123 8,123 9,831 9,831 9,831 2,946 2,946 2,946 8,853 8,853 8,853 29,753 27,815 4,747 4,747 4,747 261 261 261 99,554 99,554 99,554 21,837 21,837 21,837 35,452 35,452 35,452 27,637 27,637 27,637 36,017 36,017 36,017 106,822 106,822 106,822 2,839 2,839 2,839 19,459 19,459 633 633 633 1,432 1,432 1,432 1,098 1,098 1,098 269 269 269 3,432 4,394 263 263 263 35 35 35 25,148 25,148 25,148 2,451 2,451 2,451 1,082 1,082 1,082 4,324 4,324 4,324 1,740 1,740 1,740 9,194 9,194 9,194 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /17 9 /13 9 /13 7 /16 7 /16 9 /16 9 /16 7 /16 7 /16 9 /13 9 /13 7 /15 7 /15 7 /17 7 /17 9 /11 9 /11 76 76 76 76 76 76 76 76 75 75 75 77 77 77 79 79 79 76 76 75 75 75 76 76 76 77 77 77 76 76 76 75 75 75 77 77 77 75 75 75 70 70 70 66 66 66 66 66 67 67 67 66 66 66 67 67 67 64 64 64 67 67 65 65 65 66 66 66 67 67 67 66 66 66 65 65 65 66 66 66 66 66 66 63 63 63 49.4 49.4 49.4 51.0 51.0 56.5 56.5 56.5 54.3 54.3 54.3 45.0 45.0 45.0 58.3 58.3 58.3 55.8 56.8 57.6 57.6 57.6 55.8 55.8 55.8 51.5 51.5 51.5 59.2 59.2 59.2 60.5 60.5 60.5 59.5 59.5 59.5 57.8 57.8 57.8 56.2 56.2 56.2 Coil Airflow cfm Coil Sensible Load Btu/h 404 404 404 3,418 3,418 466 466 466 498 498 498 96 96 96 579 579 579 1,639 1,639 284 284 284 14 14 14 4,309 4,309 4,309 1,177 1,177 1,177 2,491 2,491 2,491 1,342 1,342 1,342 2,211 2,211 2,211 6,059 6,059 6,059 17,188 17,188 17,188 126,914 126,914 12,772 12,772 12,772 21,797 21,797 21,797 2,242 2,242 2,242 10,451 10,451 10,451 47,261 42,971 6,446 6,446 6,446 1,151 1,151 1,151 104,158 104,158 104,158 33,229 33,229 33,229 39,761 39,761 39,761 38,930 38,930 38,930 57,496 57,496 57,496 120,423 120,423 120,423 Coil Latent Load Btu/h 5,361 5,361 5,361 35,683 35,683 1,763 1,763 1,763 1,818 1,818 1,818 2,311 2,311 2,311 330 330 330 6,222 7,103 408 408 408 120 120 120 68,283 68,283 68,283 5,820 5,820 5,820 3,265 3,265 3,265 8,980 8,980 8,980 2,459 2,459 2,459 11,397 11,397 11,397 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 81 of 100 SPACE Floor Area ft² System Zone Room spc_DM HP-9 Class_0 Zone - 148 Zone - 148 spc_DM HP-6 Office_0 Zone - 149 Zone - 149 spc_DM HP-8 Class1_0 Zone - 150 Zone - 150 spc_DM PHP-5-2 Offices_0 Zone - 151 Zone - 151 spc_PHP-2-1 Cargo Elevator_0 Zone - 152 Zone - 152 spc_DM PRP-5-1 Restroom_0 Zone - 153 Zone - 153 spc_DM PRP-5-1 Restroom1_0 Zone - 154 Zone - 154 Drama/Music HP Drama/Music HP spc_AC-1 Auditorium_0 Zone - 141 Zone - 141 spc_DM AN-2 Corridor_0 Zone - 142 Zone - 142 spc_DM AC-2 Rehearsal Rm_0 Zone - 143 Zone - 143 spc_DM ZN-1 Class_0 Zone - 144 Zone - 144 spc_DM ZN-3 Hall_0 Zone - 145 Zone - 145 spc_DM Zn-3 Offices_0 Zone - 146 Zone - 146 spc_ZN-3 Conf_0 Zone - 147 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 192 192 192 220 220 220 592 592 592 292 292 292 122 122 122 848 848 848 1,177 1,177 1,177 24,602 24,602 3,790 3,790 3,790 701 701 701 1,135 1,135 1,135 417 417 417 209 209 209 177 177 177 405 405 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 10 /15 10 /15 6 /9 6 /9 10 /15 10 /15 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 10 /16 9 /12 10 /15 10 /15 7 /17 7 /17 10 /15 10 /15 6 /18 6 /18 10 /16 10 /16 10 /16 10 /16 6 /10 80 80 80 62 62 62 80 80 80 79 79 79 79 79 79 79 79 79 79 79 79 73 73 80 80 80 75 75 75 80 80 80 70 70 70 79 79 79 79 79 79 65 65 63 63 63 58 58 58 63 63 63 64 64 64 64 64 64 64 64 64 64 64 64 63 63 63 63 63 66 66 66 63 63 63 63 63 63 64 64 64 64 64 64 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 80.0 80.0 80.0 73.1 73.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 51.3 51.3 51.3 58.2 58.2 58.2 51.3 51.3 51.3 52.2 52.2 52.2 58.6 58.6 58.6 79.6 79.6 79.6 79.6 79.6 79.6 58.9 58.9 54.9 54.9 54.9 55.9 55.9 55.9 50.7 50.7 50.7 56.6 56.6 56.6 49.9 49.9 49.9 51.7 51.7 51.7 50.6 50.6 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 24 24 24 64 64 64 206 206 1,946 1,946 1,946 10,408 10,408 10,408 6,020 6,020 6,020 2,564 2,564 2,564 4,056 4,056 4,056 538 538 538 747 747 747 358,606 299,869 74,299 74,299 74,299 11,804 11,804 11,804 10,848 10,848 10,848 20,443 20,443 20,443 583 583 583 1,443 1,443 1,443 4,907 4,907 492 492 492 311 311 311 1,521 1,521 1,521 545 545 545 99 99 99 -2,632 -2,632 -2,632 -3,655 -3,655 -3,655 40,918 47,013 9,753 9,753 9,753 1,126 1,126 1,126 2,908 2,908 2,908 1,296 1,296 1,296 169 169 169 330 330 330 1,311 1,311 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 76 76 76 65 65 65 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 77 77 75 75 75 77 77 77 73 73 73 77 77 77 76 76 76 77 77 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 65 65 65 67 67 67 67 67 67 67 67 51.4 51.4 51.4 58.8 58.8 58.8 51.5 51.5 51.5 52.4 52.4 52.4 58.8 58.8 58.8 79.7 79.7 79.7 79.7 79.7 79.7 59.7 62.3 55.5 55.5 55.5 55.9 55.9 55.9 51.3 51.3 51.3 56.7 56.7 56.7 51.4 51.4 51.4 52.3 52.3 52.3 53.5 53.5 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 84 84 84 678 678 678 261 261 261 116 116 116 271 271 271 1,356 1,356 1,356 1,883 1,883 1,883 22,534 22,534 3,889 3,889 3,889 656 656 656 458 458 458 1,188 1,188 1,188 24 24 24 64 64 64 206 206 5,018 5,018 5,018 11,069 11,069 11,069 6,298 6,298 6,298 2,691 2,691 2,691 6,557 6,557 6,557 5,343 5,343 5,343 7,418 7,418 7,418 445,988 374,351 83,988 83,988 83,988 13,640 13,640 13,640 13,026 13,026 13,026 22,815 22,815 22,815 715 715 715 1,748 1,748 1,748 5,430 5,430 1,203 1,203 1,203 475 475 475 4,129 4,129 4,129 1,517 1,517 1,517 288 288 288 -46,142 -46,142 -46,142 -64,061 -64,061 -64,061 -1,859 7,013 26,500 26,500 26,500 1,430 1,430 1,430 7,893 7,893 7,893 2,691 2,691 2,691 468 468 468 919 919 919 3,494 3,494 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 82 of 100 SPACE Floor Area ft² System Zone Room Zone - 147 spc_DM Scene Shop HV-1_0 Zone - 155 Zone - 155 Drama/Music MZU Drama/Music MZU spc_EBS 217/Storage C_0 Zone - 156 Zone - 156 spc_EBS 215 Class C_0 Zone - 157 Zone - 157 spc_EBS 209 Class C_0 Zone - 158 Zone - 158 spc_EBS 210 Class C_0 Zone - 159 Zone - 159 spc_EBS 109/127 Lobby C_0 Zone - 160 Zone - 160 spc_EBS 125 Class C_0 Zone - 161 Zone - 161 spc_EBS 102 Class C_0 Zone - 162 Zone - 162 spc_EBS 123 Class C_0 Zone - 163 Zone - 163 spc_EBS 119 Offices C_0 Zone - 164 Zone - 164 spc_EBS 119 Office C_0 Zone - 165 Zone - 165 spc_EBS 116 Office C_0 Zone - 166 Zone - 166 spc_EBS 110-113 Office UC_0 Zone - 167 Zone - 167 spc_EBS 114 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 405 1,711 1,711 1,711 8,545 8,545 2,046 2,046 2,046 758 758 758 1,358 1,358 1,358 1,333 1,333 1,333 1,771 1,771 1,771 396 396 396 1,332 1,332 1,332 1,622 1,622 1,622 399 399 399 306 306 306 156 156 156 515 515 515 893 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /10 10 /13 10 /13 9 /16 7 /15 7 /15 7 /16 7 /16 10 /15 10 /15 7 /18 7 /18 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 10 /14 65 77 77 77 77 77 77 77 77 76 76 76 80 80 80 73 73 73 75 75 75 73 73 73 73 73 73 73 73 73 75 75 75 75 75 75 73 73 73 73 73 73 79 58 59 59 59 67 67 66 66 66 66 66 66 63 63 63 65 65 65 66 66 66 65 65 65 65 65 65 65 65 65 66 66 66 66 66 66 65 65 65 65 65 65 62 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 50.6 57.7 57.7 57.7 55.4 55.4 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 206 1,561 1,561 1,561 8,045 8,045 931 931 931 493 493 493 1,547 1,547 1,547 1,511 1,511 1,511 744 744 744 473 473 473 2,019 2,019 2,019 1,486 1,486 1,486 309 309 309 177 177 177 220 220 220 624 624 624 1,093 4,907 24,799 24,799 24,799 149,125 129,890 18,050 18,050 18,050 9,553 9,553 9,553 29,992 29,992 29,992 29,286 29,286 29,286 14,421 14,421 14,421 9,178 9,178 9,178 39,142 39,142 39,142 28,811 28,811 28,811 5,997 5,997 5,997 3,436 3,436 3,436 4,262 4,262 4,262 12,097 12,097 12,097 21,186 1,311 3,134 3,134 3,134 20,027 30,017 3,114 3,114 3,114 2,661 2,661 2,661 3,489 3,489 3,489 4,607 4,607 4,607 2,924 2,924 2,924 1,369 1,369 1,369 4,604 4,604 4,604 5,608 5,608 5,608 1,057 1,057 1,057 811 811 811 368 368 368 1,214 1,214 1,214 2,014 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /14 9 /14 9 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /14 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 75 75 75 75 75 75 73 73 73 73 73 73 75 75 75 75 75 75 75 75 75 73 73 73 73 73 73 77 67 66 66 66 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 66 53.5 58.2 58.2 58.2 55.9 57.5 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 206 1,561 1,561 1,561 8,045 8,045 903 903 903 493 493 493 1,515 1,515 1,515 1,493 1,493 1,493 744 744 744 473 473 473 2,019 2,019 2,019 1,454 1,454 1,454 309 309 309 177 177 177 220 220 220 624 624 624 1,079 5,430 30,462 30,462 30,462 171,824 156,601 40,996 40,996 40,996 17,369 17,369 17,369 45,366 45,366 45,366 45,809 45,809 45,809 35,058 35,058 35,058 14,006 14,006 14,006 55,862 55,862 55,862 46,115 46,115 46,115 10,829 10,829 10,829 6,764 6,764 6,764 6,557 6,557 6,557 19,460 19,460 19,460 22,361 Coil Latent Load Btu/h 3,494 10,580 10,580 10,580 53,975 55,726 4,331 4,331 4,331 4,766 4,766 4,766 9,476 9,476 9,476 8,212 8,212 8,212 4,199 4,199 4,199 2,548 2,548 2,548 8,567 8,567 8,567 9,995 9,995 9,995 1,822 1,822 1,822 1,398 1,398 1,398 677 677 677 2,235 2,235 2,235 5,495 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 83 of 100 SPACE Floor Area ft² System Zone Room Zone - 168 Zone - 168 spc_EBS 115 Class C_0 Zone - 169 Zone - 169 spc_EBS 209 Class UC_0 Zone - 172 Zone - 172 spc_EBS 210 Class C_1 Zone - 173 Zone - 173 spc_EBS 215 Class C_1 Zone - 174 Zone - 174 spc_EBS 218 Office C_0 Zone - 175 Zone - 175 spc_EBS 216 Office C_0 Zone - 176 Zone - 176 EBS VAV EBS VAV spc_H 326 Class C_0 Zone - 206 Zone - 206 spc_H 328 Class C_0 Zone - 207 Zone - 207 spc_H 328 Office C_0 Zone - 208 Zone - 208 Humanities Fan Coil Humanities Fan Coil spc_H 104/107/112 Art C_0 Zone - 177 Zone - 177 spc_H 102 Class C_0 Zone - 178 Zone - 178 spc_H 106 Office C_0 Zone - 179 Zone - 179 spc_H 2444 Class C_0 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 893 893 10 /14 1,659 9 /16 1,659 1,659 9 /16 1,334 7 /16 1,334 1,334 7 /16 1,334 7 /16 1,334 1,334 7 /16 790 7 /18 790 790 7 /18 70 7 /18 70 70 7/18 74 7 /17 74 74 7 /17 18,147 18,147 7 /17 845 5 /17 845 845 5 /17 1,818 7 /16 1,818 1,818 7 /16 300 7 /12 300 300 7 /12 2,963 2,963 7 /17 7,121 7 /16 7,121 7,121 7 /16 1,004 7 /16 1,004 1,004 7 /16 229 7 /17 229 229 7 /17 555 7 /16 79 79 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 72 72 72 76 76 76 73 73 73 75 75 76 76 76 76 76 76 75 75 75 76 62 62 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 63 63 63 66 66 66 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 54.3 54.3 54.3 56.6 56.6 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 1,093 1,093 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,925 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,288 5,288 5,288 627 627 627 122 122 122 346 21,186 21,186 31,380 31,380 31,380 16,818 16,818 16,818 16,818 16,818 16,818 14,759 14,759 14,759 2,665 2,665 2,665 826 826 826 308,677 289,380 76,201 76,201 76,201 24,051 24,051 24,051 4,645 4,645 4,645 104,897 101,595 91,368 91,368 91,368 10,835 10,835 10,835 2,102 2,102 2,102 5,987 2,014 2,014 6,149 6,149 6,149 4,685 4,685 4,685 4,685 4,685 4,685 2,731 2,731 2,731 166 166 166 195 195 195 52,452 52,299 2,350 2,350 2,350 6,371 6,371 6,371 631 631 631 9,352 9,537 24,945 24,945 24,945 3,519 3,519 3,519 604 604 604 1,944 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /14 9 /16 9 /16 7 /16 7 /16 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 7 /17 7 /15 7 /15 9 /16 9 /16 9 /17 9 /17 9 /16 77 77 77 77 77 76 76 76 76 76 76 73 73 73 73 73 73 75 75 75 75 75 73 73 73 76 76 76 76 76 76 75 75 77 77 77 77 77 77 76 76 76 77 66 66 67 67 67 66 66 66 66 66 66 65 65 65 65 65 65 66 66 66 66 66 65 65 65 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 58.0 58.0 58.0 50.0 50.0 50.0 57.2 57.2 57.2 56.7 57.1 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 1,079 1,079 1,619 1,619 1,619 868 868 868 868 868 868 761 761 761 138 138 138 43 43 43 15,801 14,929 4,888 4,888 4,888 980 980 980 236 236 236 6,103 6,103 5,284 5,284 5,284 600 600 600 119 119 119 331 22,361 22,361 49,825 49,825 49,825 30,579 30,579 30,579 30,579 30,579 30,579 23,381 23,381 23,381 3,913 3,913 3,913 1,626 1,626 1,626 504,179 486,608 92,686 92,686 92,686 49,932 49,932 49,932 8,423 8,423 8,423 151,042 148,011 99,527 99,527 99,527 11,228 11,228 11,228 2,209 2,209 2,209 6,204 Coil Latent Load Btu/h 5,495 5,495 11,570 11,570 11,570 8,391 8,391 8,391 8,391 8,391 8,391 5,082 5,082 5,082 305 305 305 336 336 336 97,796 94,521 5,460 5,460 5,460 11,390 11,390 11,390 1,341 1,341 1,341 18,190 17,762 43,603 43,603 43,603 6,979 6,979 6,979 1,184 1,184 1,184 3,856 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 84 of 100 SPACE Floor Area ft² System Zone Room Zone - 180 Zone - 180 spc_H 245A/B Class C_0 Zone - 181 Zone - 181 spc_H 226/A office C_0 Zone - 182 Zone - 182 spc_H 208-217 Office C_0 Zone - 183 Zone - 183 spc_H 225 Office C_0 Zone - 184 Zone - 184 spc_H 242/207 Corridor C_0 Zone - 185 Zone - 185 spc_H 123U Art AH-1/23_0 Zone - 186 Zone - 186 spc_H 111 Class C_0 Zone - 187 Zone - 187 spc_H 221/220/204 Class C_0 Zone - 188 Zone - 188 spc_H 232A Class C_0 Zone - 189 Zone - 189 spc_H 239 Class Office_0 Zone - 190 Zone - 190 spc_H 237 Office C_0 Zone - 191 Zone - 191 spc_H 236 Office C_0 Zone - 192 Zone - 192 spc_H 241 Class C_0 Zone - 193 Zone - 193 spc_H 309-318 Offices C_0 Zone - 194 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 555 555 1,686 1,686 1,686 272 272 272 1,065 1,065 1,065 267 267 267 4,126 4,126 4,126 2,482 2,482 2,482 1,805 1,805 1,805 4,564 4,564 4,564 1,111 1,111 1,111 306 306 306 90 90 90 272 272 272 571 571 571 1,012 1,012 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /17 7 /17 11 /13 11 /13 11 /14 11 /14 11 /14 11 /14 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 11 /14 76 76 75 75 75 71 71 71 73 73 73 73 73 73 79 79 79 75 75 75 76 76 76 77 77 77 76 76 76 77 77 77 75 75 75 75 75 75 76 76 76 73 73 66 66 66 66 66 58 58 58 60 60 60 60 60 60 64 64 64 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 60 60 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 346 346 2,157 2,157 2,157 798 798 798 3,496 3,496 3,496 765 765 765 1,412 1,412 1,412 2,382 2,382 2,382 1,127 1,127 1,127 3,577 3,577 3,577 693 693 693 311 311 311 48 48 48 145 145 145 356 356 356 4,319 4,319 5,987 5,987 37,265 37,265 37,265 13,783 13,783 13,783 60,401 60,401 60,401 13,211 13,211 13,211 24,400 24,400 24,400 41,156 41,156 41,156 19,474 19,474 19,474 61,807 61,807 61,807 11,982 11,982 11,982 5,382 5,382 5,382 828 828 828 2,500 2,500 2,500 6,155 6,155 6,155 74,623 74,623 1,944 1,944 5,523 5,523 5,523 89 89 89 766 766 766 192 192 192 3,332 3,332 3,332 8,130 8,130 8,130 6,325 6,325 6,325 15,809 15,809 15,809 3,891 3,891 3,891 1,060 1,060 1,060 238 238 238 719 719 719 1,999 1,999 1,999 728 728 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /14 9 /14 9 /15 9 /15 9 /15 9 /15 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /15 7 /15 9 /16 9 /16 7 /15 7 /15 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /15 77 77 77 77 77 77 77 77 78 78 78 78 78 78 77 77 77 76 76 76 77 77 77 77 77 77 77 77 77 77 77 77 76 76 76 76 76 76 77 77 77 78 78 67 67 67 67 67 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 331 331 2,071 2,071 2,071 743 743 743 2,999 2,999 2,999 665 665 665 1,401 1,401 1,401 2,313 2,313 2,313 1,078 1,078 1,078 3,577 3,577 3,577 663 663 663 311 311 311 47 47 47 142 142 142 341 341 341 3,657 3,657 6,204 6,204 40,964 40,964 40,964 15,383 15,383 15,383 74,566 74,566 74,566 13,581 13,581 13,581 25,840 25,840 25,840 45,783 45,783 45,783 20,181 20,181 20,181 67,488 67,488 67,488 12,417 12,417 12,417 5,994 5,994 5,994 871 871 871 2,628 2,628 2,628 6,379 6,379 6,379 87,004 87,004 Coil Latent Load Btu/h 3,856 3,856 11,713 11,713 11,713 999 999 999 4,843 4,843 4,843 1,216 1,216 1,216 9,229 9,229 9,229 17,267 17,267 17,267 12,544 12,544 12,544 27,948 27,948 27,948 7,718 7,718 7,718 1,874 1,874 1,874 467 467 467 1,408 1,408 1,408 3,965 3,965 3,965 4,603 4,603 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 85 of 100 SPACE Floor Area ft² System Zone Room Zone - 194 spc_H 240 Class C_0 Zone - 195 Zone - 195 spc_H 300 Restrooms C_0 Zone - 196 Zone - 196 spc_H 322 Office C_0 Zone - 197 Zone - 197 spc_H 323 Office C_0 Zone - 198 Zone - 198 spc_H 300H Hall C_0 Zone - 199 Zone - 199 spc_H 202 Class C_0 Zone - 200 Zone - 200 spc_H 205 Office C_0 Zone - 201 Zone - 201 spc_H 205/203 Class C_0 Zone - 202 Zone - 202 spc_H 232B Office C_0 Zone - 203 Zone - 203 spc_H 223 Class C_0 Zone - 204 Zone - 204 spc_H 223U Storage C_0 Zone - 205 Zone - 205 spc_H 306 Class C_0 Zone - 211 Zone - 211 spc_H 308 Class H_0 Zone - 212 Zone - 212 spc_H 301-307 Classes C_0 Zone - 213 Zone - 213 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,012 818 818 818 339 339 339 265 265 265 265 265 265 3,593 3,593 3,593 1,118 1,118 1,118 270 270 270 846 846 846 161 161 161 616 616 616 165 165 165 727 727 727 512 512 512 3,348 3,348 3,348 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 11 /14 7 /15 7 /15 9 /17 9 /17 11 /14 11 /14 7 /17 7 /17 10 /16 10 /16 8/10 8 /10 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 7 /16 7 /16 7 /15 7 /15 7 /16 7 /16 7 /16 7 /16 7 /15 7 /15 73 77 77 77 76 76 76 73 73 73 75 75 75 79 79 79 67 67 67 75 75 75 76 76 76 75 75 75 76 76 76 77 77 77 76 76 76 76 76 76 77 77 77 60 66 66 66 67 67 67 60 60 60 66 66 66 64 64 64 61 61 61 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 4,319 642 642 642 542 542 542 1,069 1,069 1,069 141 141 141 3,898 3,898 3,898 2,401 2,401 2,401 144 144 144 528 528 528 86 86 86 385 385 385 51 51 51 454 454 454 320 320 320 2,748 2,748 2,748 74,623 11,100 11,100 11,100 14,193 14,193 14,193 18,478 18,478 18,478 2,434 2,434 2,434 67,353 67,353 67,353 41,487 41,487 41,487 2,483 2,483 2,483 9,121 9,121 9,121 1,483 1,483 1,483 6,648 6,648 6,648 876 876 876 7,841 7,841 7,841 5,526 5,526 5,526 47,476 47,476 47,476 728 2,834 2,834 2,834 619 619 619 190 190 190 700 700 700 9,908 9,908 9,908 3,433 3,433 3,433 714 714 714 2,962 2,962 2,962 426 426 426 2,159 2,159 2,159 250 250 250 2,546 2,546 2,546 1,795 1,795 1,795 11,597 11,597 11,597 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /15 7 /15 7 /15 9 /17 9 /17 9 /15 9 /15 9 /17 9 /17 9 /16 9 /16 9 /11 9 /11 9 /17 9 /17 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 9 /15 9 /15 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 78 77 77 77 76 76 76 78 78 78 76 76 76 77 77 77 70 70 70 76 76 76 77 77 77 76 76 76 77 77 77 78 78 78 76 76 76 76 76 76 76 76 76 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 63 63 63 67 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 Coil Airflow cfm Coil Sensible Load Btu/h 3,657 642 642 642 210 210 210 890 890 890 138 138 138 3,839 3,839 3,839 2,239 2,239 2,239 141 141 141 505 505 505 84 84 84 368 368 368 47 47 47 441 441 441 311 311 311 2,733 2,733 2,733 87,004 12,091 12,091 12,091 14,647 14,647 14,647 21,157 21,157 21,157 2,558 2,558 2,558 126,357 126,357 126,357 45,716 45,716 45,716 2,609 2,609 2,609 9,452 9,452 9,452 1,558 1,558 1,558 6,890 6,890 6,890 878 878 878 19,161 19,161 19,161 13,504 13,504 13,504 102,755 102,755 102,755 Coil Latent Load Btu/h 4,603 5,010 5,010 5,010 4,236 4,236 4,236 1,203 1,203 1,203 1,371 1,371 1,371 24,964 24,964 24,964 5,771 5,771 5,771 1,399 1,399 1,399 5,875 5,875 5,875 835 835 835 4,282 4,282 4,282 357 357 357 4,551 4,551 4,551 3,208 3,208 3,208 20,961 20,961 20,961 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 86 of 100 SPACE System Zone Room spc_H 301 Class C_0 Peak Zone - 214 Peak Zone - 214 Block spc_H 3281 Hall C_0 Peak Zone - 215 Peak Zone - 215 Block Humanities VAV Peak Humanities VAV Block spc_IDC 335 Office C_0 Peak Zone - 220 Peak Zone - 220 Block spc_IDC 313 Wrk Rm_0 Peak Zone - 221 Peak Zone - 221 Block spc_IDC 317 Wrk Rm C_0 Peak Zone - 222 Peak Zone - 222 Block spc_IDC 329 C_0 Peak Zone - 223 Peak Zone - 223 Block IDC Fan Coil Peak IDC Fan Coil Block Peak spc_IDC 102/103/104/109 Int Class_0 Zone - 216 Peak Zone - 216 Block spc_IDC 205 Class C_0 Peak Zone - 217 Peak Zone - 217 Block spc_IDC 211/210 Class_0 Peak Zone - 218 Peak Zone - 218 Block spc_IDC 333 Office_0 Peak Zone - 219 Peak Zone - 219 Block IDC VAV Peak IDC VAV Block spc_LRC 140-01-08 C_0 Peak Zone - 224 Peak Zone - 224 Block spc_LRC 140-09 C_0 Peak Zone - 225 Peak Zone - 225 Block spc_LRC 13-15 C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 633 633 633 228 228 228 42,441 42,441 107 107 107 206 206 206 171 171 171 102 102 102 586 586 3,318 3,318 3,318 460 460 460 1,001 1,001 1,001 414 414 414 5,194 5,194 1,843 1,843 1,843 250 250 250 153 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 10 /15 7 /17 7 /17 7 /16 7 /16 7 /16 7/16 7 /16 7 /16 7 /16 10 /15 10 /15 10 /15 10 /15 10 /15 10 /15 10 /17 10 /17 10 /15 6 /10 6 /10 9 /12 9 /12 9 /11 76 76 76 76 76 76 80 80 75 75 75 76 76 76 76 76 76 76 76 76 76 76 80 80 80 80 80 80 80 80 80 77 77 77 80 80 65 65 65 73 73 73 70 66 66 66 66 66 66 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 63 63 63 63 63 63 64 64 64 63 63 58 58 58 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.1 72.1 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 395 395 395 53 53 53 41,826 37,423 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,694 1,694 1,694 859 859 859 511 511 511 180 180 180 3,244 3,237 1,595 1,595 1,595 797 797 797 632 6,823 6,823 6,823 911 911 911 727,491 650,911 1,280 1,280 1,280 2,975 2,975 2,975 2,627 2,627 2,627 1,357 1,357 1,357 8,239 8,216 32,706 32,706 32,706 16,577 16,577 16,577 9,869 9,869 9,869 3,472 3,472 3,472 62,624 62,481 28,266 28,266 28,266 14,118 14,118 14,118 11,205 2,216 2,216 2,216 354 354 354 122,518 95,452 284 284 284 722 722 722 600 600 600 357 357 357 1,962 1,958 8,526 8,526 8,526 1,182 1,182 1,182 2,573 2,573 2,573 855 855 855 13,135 12,972 5,957 5,957 5,957 915 915 915 580 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /16 7 /16 7 /16 9 /16 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 7 /16 7 /16 9 /13 9 /13 9 /11 76 76 76 76 76 76 77 77 75 75 75 76 76 76 76 76 76 76 76 76 76 76 77 77 77 77 77 77 77 77 77 75 75 75 77 77 76 76 76 75 75 75 70 66 66 66 66 66 66 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 67 67 67 66 66 66 67 67 66 66 66 65 65 65 63 56.5 56.5 56.5 56.5 56.5 56.5 56.5 56.5 51.4 51.4 51.4 50.7 50.7 50.7 51.1 51.1 51.1 50.0 50.0 50.0 50.9 50.9 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 54.7 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 384 384 384 49 49 49 39,362 36,284 56 56 56 125 125 125 113 113 113 55 55 55 349 349 1,668 1,668 1,668 843 843 843 503 503 503 179 179 179 3,194 3,189 1,448 1,448 1,448 757 757 757 632 16,673 16,673 16,673 4,252 4,252 4,252 957,271 890,214 2,183 2,183 2,183 4,555 4,555 4,555 3,950 3,950 3,950 2,128 2,128 2,128 12,817 12,798 38,524 38,524 38,524 19,698 19,698 19,698 11,625 11,625 11,625 10,755 10,755 10,755 80,821 79,588 54,618 54,618 54,618 17,332 17,332 17,332 12,865 3,960 3,960 3,960 448 448 448 249,846 272,391 488 488 488 1,291 1,291 1,291 1,072 1,072 1,072 638 638 638 3,490 3,478 23,156 23,156 23,156 3,209 3,209 3,209 6,987 6,987 6,987 1,894 1,894 1,894 35,247 35,420 12,597 12,597 12,597 1,569 1,569 1,569 880 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 87 of 100 SPACE Floor Area ft² System Zone Room Zone - 226 Zone - 226 spc_LRC 16 C_0 Zone - 227 Zone - 227 spc_LRC 17/18_0 Zone - 228 Zone - 228 spc_LRC 5 C (Study?)_0 Zone - 229 Zone - 229 spc_LRC 9 Storage_0 Zone - 230 Zone - 230 spc_LRC 10 Storage_0 Zone - 231 Zone - 231 spc_LRC 7 C_0 Zone - 232 Zone - 232 spc_LRC 8 Stair_0 Zone - 233 Zone - 233 spc_LRC Catalog C_0 Zone - 234 Zone - 234 spc_LRC Computer_0 Zone - 235 Zone - 235 spc_LRC 2/6_0 Zone - 236 Zone - 236 spc_LRC 1st RR C_0 Zone - 237 Zone - 237 spc_LRC 24_0 Zone - 238 Zone - 238 spc_LRC 25_0 Zone - 239 Zone - 239 spc_LRC 105 C Work_0 Zone - 240 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 153 153 66 66 66 94 94 94 57 57 57 29 29 29 24 24 24 119 119 119 302 302 302 56 56 56 525 525 525 137 137 137 226 226 226 564 564 564 325 325 325 62 62 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 10 /13 10 /13 10 /16 10 /16 7 /15 7 /15 7 /15 7 /15 6 /10 6/10 6 /18 6 /18 7 /18 7 /18 7 /18 7 /18 6 /17 6 /17 7 /15 7 /15 10 /16 10/16 10 /16 10 /16 7 /18 7 /18 7 /18 70 70 77 77 77 79 79 79 77 77 77 77 77 77 65 65 65 70 70 70 73 73 73 73 73 73 72 72 72 77 77 77 79 79 79 79 79 79 73 73 73 73 73 63 63 59 59 59 64 64 64 66 66 66 66 66 66 58 58 58 63 63 63 65 65 65 65 65 65 63 63 63 66 66 66 64 64 64 64 64 64 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 632 632 296 296 296 800 800 800 34 34 34 9 9 9 43 43 43 499 499 499 178 178 178 119 119 119 1,809 1,809 1,809 78 78 78 362 362 362 2,024 2,024 2,024 956 956 956 123 123 11,205 11,205 5,239 5,239 5,239 14,180 14,180 14,180 606 606 606 156 156 156 770 770 770 8,836 8,836 8,836 3,148 3,148 3,148 2,112 2,112 2,112 32,061 32,061 32,061 1,384 1,384 1,384 9,633 9,633 9,633 35,871 35,871 35,871 16,939 16,939 16,939 2,178 2,178 580 580 159 159 159 316 316 316 196 196 196 44 44 44 16 16 16 366 366 366 460 460 460 226 226 226 1,210 1,210 1,210 556 556 556 181 181 181 1,890 1,890 1,890 1,302 1,302 1,302 214 214 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /13 9 /13 9 /16 9 /16 9 /16 9 /16 9 /15 9 /15 6 /10 6 /10 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 9 /16 9 /16 10 /16 10 /16 9 /16 9 /16 7 /18 7 /18 7 /18 70 70 75 75 75 77 77 77 77 77 77 78 78 78 65 65 65 73 73 73 73 73 73 73 73 73 75 75 75 77 77 77 79 79 79 77 77 77 73 73 73 73 73 63 63 65 65 65 67 67 67 67 67 67 66 66 66 58 58 58 65 65 65 65 65 65 65 65 65 66 66 66 67 67 67 64 64 64 67 67 67 65 65 65 65 65 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 632 632 289 289 289 781 781 781 34 34 34 8 8 8 43 43 43 495 495 495 178 178 178 119 119 119 1,791 1,791 1,791 77 77 77 186 186 186 1,981 1,981 1,981 956 956 956 123 123 12,865 12,865 5,989 5,989 5,989 15,724 15,724 15,724 602 602 602 149 149 149 999 999 999 9,606 9,606 9,606 3,388 3,388 3,388 2,494 2,494 2,494 34,140 34,140 34,140 1,369 1,369 1,369 8,860 8,860 8,860 39,177 39,177 39,177 19,463 19,463 19,463 3,446 3,446 Coil Latent Load Btu/h 880 880 417 417 417 710 710 710 392 392 392 63 63 63 19 19 19 757 757 757 592 592 592 392 392 392 2,556 2,556 2,556 1,032 1,032 1,032 996 996 996 4,243 4,243 4,243 2,256 2,256 2,256 397 397 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 88 of 100 SPACE System Zone Room Zone - 240 Block spc_LRC Tables/124B C_0 Peak Zone - 241 Peak Zone - 241 Block spc_LRC 120/122/123 Office C_0 Peak Zone - 242 Peak Zone - 242 Block spc_LRC Tutor Lab C_0 Peak Zone - 243 Peak Zone - 243 Block spc_LRC Lobby/112B Corridor C_0Peak Zone - 244 Peak Zone - 244 Block spc_LRC Dir Offc C_0 Peak Zone - 245 Peak Zone - 245 Block spc_LRC 108/111/115 Counter_0 Peak Zone - 246 Peak Zone - 246 Block spc_LRC 149A_0 Peak Zone - 247 Peak Zone - 247 Block spc_LRC 137 Work C_0 Peak Zone - 248 Peak Zone - 248 Block spc_LRC 140-142 Director_0 Peak Zone - 249 Peak Zone - 249 Block spc_LRC 145 Office C_0 Peak Zone - 250 Peak Zone - 250 Block spc_LRC 146A Storage_0 Peak Zone - 251 Peak Zone - 251 Block spc_LRC 146_0 Peak Zone - 252 Peak Zone - 252 Block spc_LRC Library_0 Peak Zone - 253 Peak Zone - 253 Block spc_LRC 140-14_0 Peak Zone - 254 Peak Zone - 254 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 62 647 647 647 58 58 58 63 63 63 582 582 582 36 36 36 335 335 335 25 25 25 59 59 59 38 38 38 23 23 23 14 14 14 80 80 80 0 0 0 42 42 42 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 10 /15 10 /15 6 /11 6 /11 7 /15 7 /15 7 /18 7 /18 6 /18 6 /18 7/15 7 /15 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 10 /16 10 /16 10 /13 10 /13 11 /12 11 /12 9 /12 9 /12 73 80 80 80 68 68 68 77 77 77 73 73 73 70 70 70 77 77 77 73 73 73 73 73 73 75 75 75 75 75 75 79 79 79 77 77 77 68 68 68 73 73 73 65 63 63 63 60 60 60 66 66 66 65 65 65 63 63 63 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 64 64 64 59 59 59 55 55 55 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 123 1,184 1,184 1,184 119 119 119 110 110 110 387 387 387 147 147 147 191 191 191 45 45 45 191 191 191 20 20 20 12 12 12 64 64 64 252 252 252 2,551 2,551 2,551 190 190 190 2,178 20,983 20,983 20,983 2,116 2,116 2,116 1,946 1,946 1,946 6,866 6,866 6,866 2,614 2,614 2,614 3,378 3,378 3,378 793 793 793 3,381 3,381 3,381 359 359 359 214 214 214 1,140 1,140 1,140 4,464 4,464 4,464 45,210 45,210 45,210 3,371 3,371 3,371 214 1,652 1,652 1,652 103 103 103 180 180 180 975 975 975 72 72 72 1,358 1,358 1,358 86 86 86 204 204 204 101 101 101 60 60 60 11 11 11 192 192 192 0 0 0 154 154 154 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /18 9 /16 9 /16 7 /12 7 /12 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 7 /18 7 /18 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 9 /14 9 /14 9 /11 9 /11 9 /12 9 /12 73 77 77 77 73 73 73 76 76 76 75 75 75 73 73 73 76 76 76 73 73 73 73 73 73 75 75 75 75 75 75 76 76 76 77 77 77 70 70 70 73 73 73 65 67 67 67 63 63 63 66 66 66 66 66 66 65 65 65 66 66 66 65 65 65 65 65 65 66 66 66 66 66 66 67 67 67 66 66 66 63 63 63 63 63 63 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 Coil Airflow cfm Coil Sensible Load Btu/h 123 1,113 1,113 1,113 117 117 117 110 110 110 364 364 364 145 145 145 190 190 190 45 45 45 191 191 191 20 20 20 12 12 12 63 63 63 233 233 233 2,488 2,488 2,488 190 190 190 3,446 32,086 32,086 32,086 2,850 2,850 2,850 2,980 2,980 2,980 14,670 14,670 14,670 3,509 3,509 3,509 8,372 8,372 8,372 1,278 1,278 1,278 4,731 4,731 4,731 936 936 936 559 559 559 1,612 1,612 1,612 5,818 5,818 5,818 47,040 47,040 47,040 4,151 4,151 4,151 Coil Latent Load Btu/h 397 4,480 4,480 4,480 178 178 178 312 312 312 1,365 1,365 1,365 155 155 155 2,288 2,288 2,288 159 159 159 378 378 378 174 174 174 104 104 104 35 35 35 535 535 535 0 0 0 223 223 223 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 89 of 100 SPACE OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F System Zone Room Floor Area ft² spc_LRC 140-03_0 Peak Zone - 255 Peak Zone - 255 Block spc_LRC 101 Work C_0 Peak Zone - 256 Peak Zone - 256 Block spc_LRC 108-110 Storage_0 Peak Zone - 257 Peak Zone - 257 Block spc_LRC 109 Work_0 Peak Zone - 258 Peak Zone - 258 Block LRC VAV Peak LRC VAV Block spc_OE 10WM Restrooms AH-2_0Peak Zone - 259 Peak Zone - 259 Block spc_OE 112 Class C_0 Peak Zone - 260 Peak Zone - 260 Block spc_OE 116 Class C_0 Peak Zone - 261 Peak Zone - 261 Block spc_OE 180H/182 Class C_0 Peak Zone - 262 Peak Zone - 262 Block spc_OE 180A Office C_0 Peak Zone - 263 Peak Zone - 263 Block OE Pckg AH Peak OE Pckg AH Block spc_PE 108 Weight Rm HP3/4_0 Peak Zone - 006 Peak Zone - 006 Block spc_PE Locker/RR HP-06/07_0 Peak Zone - 008 Peak Zone - 008 Block Peak spc_PE 302-310E Office Partially C_0 Zone - 011 Peak Zone - 011 Block PE Heat Pump Peak PE Heat Pump Block spc_PE Gym AH1_0 Peak 86 6 /10 86 86 6 /10 62 9 /17 62 62 9 /17 24 7 /15 24 24 7 /15 43 9 /17 43 43 9 /17 7,052 7,052 9 /16 172 7 /18 172 172 7/18 522 10 /15 522 522 10 /15 1,121 7 /18 1,121 1,121 7 /18 509 9 /11 509 509 9 /11 66 7 /17 66 66 7 /17 2,391 2,391 10 /14 3,594 9 /10 3,594 3,594 9 /10 1,968 7 /18 1,968 1,968 7 /18 498 7 /18 498 498 7 /18 6,061 6,061 7 /18 7,524 7 /17 Project Name: Dataset Name: SBCC TRACE.TRC 65 65 65 76 76 76 77 77 77 76 76 76 77 77 73 73 73 80 80 80 73 73 73 70 70 70 75 75 75 79 79 67 67 67 73 73 73 73 73 73 73 73 75 58 58 58 67 67 67 66 66 66 67 67 67 67 67 65 65 65 63 63 63 65 65 65 63 63 63 66 66 66 62 62 61 61 61 65 65 65 65 65 65 65 65 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.2 72.2 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.7 72.7 72.0 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 76.0 76.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 73.2 73.2 73.2 56.6 56.6 56.6 52.2 52.2 52.2 55.6 55.6 55.6 48.8 48.8 48.8 56.4 56.4 54.5 54.5 54.5 74.3 74.3 74.3 56.3 56.3 56.3 64.7 64.7 72.4 207 207 207 186 186 186 7 7 7 143 143 143 16,361 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 3,150 3,150 1,009 1,009 1,009 6,278 6,278 1,505 3,672 3,672 3,672 3,302 3,302 3,302 123 123 123 2,540 2,540 2,540 293,173 232,240 2,089 2,089 2,089 17,559 17,559 17,559 20,357 20,357 20,357 17,712 17,712 17,712 589 589 589 58,307 44,634 41,395 41,395 41,395 19,874 19,874 19,874 17,669 17,669 17,669 78,937 60,043 -636 277 277 277 218 218 218 36 36 36 152 152 152 20,421 25,647 59 59 59 1,340 1,340 1,340 3,874 3,874 3,874 1,628 1,628 1,628 176 176 176 7,077 4,708 4,036 4,036 4,036 668 668 668 1,173 1,173 1,173 5,877 7,430 -4,539 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 9 /17 9 /17 7 /16 7 /16 9 /17 9 /17 9 /16 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 9 /13 9 /13 7 /17 7 /17 9 /16 9 /13 9 /13 9 /17 9 /17 7 /18 7 /18 9 /17 7 /14 75 75 75 76 76 76 76 76 76 76 76 76 77 77 76 76 76 77 77 77 73 73 73 75 75 75 75 75 75 77 77 75 75 75 76 76 76 73 73 73 76 76 76 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 65 65 65 65 65 65 66 66 66 67 67 65 65 65 67 67 67 65 65 65 67 67 65 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 76.2 76.2 76.2 57.4 57.4 57.4 52.2 52.2 52.2 57.4 57.4 57.4 48.8 48.8 48.8 57.5 60.7 57.2 57.2 57.2 75.4 75.4 75.4 56.3 56.3 56.3 66.2 68.1 72.4 Coil Airflow cfm Coil Sensible Load Btu/h 164 164 164 186 186 186 7 7 7 143 143 143 15,679 12,961 275 275 275 1,022 1,022 1,022 924 924 924 968 968 968 23 23 23 3,212 3,212 2,119 2,119 2,119 3,150 3,150 3,150 1,009 1,009 1,009 6,278 6,278 451 4,618 4,618 4,618 4,899 4,899 4,899 475 475 475 3,755 3,755 3,755 382,332 328,402 2,439 2,439 2,439 21,294 21,294 21,294 23,315 23,315 23,315 22,689 22,689 22,689 1,667 1,667 1,667 71,405 61,879 36,526 36,526 36,526 36,640 36,640 36,640 27,335 27,335 27,335 100,501 80,404 -191 Coil Latent Load Btu/h 569 569 569 432 432 432 50 50 50 300 300 300 41,604 50,410 755 755 755 3,639 3,639 3,639 7,205 7,205 7,205 2,921 2,921 2,921 304 304 304 14,824 15,804 19,890 19,890 19,890 8,557 8,557 8,557 2,160 2,160 2,160 30,607 29,879 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 90 of 100 SPACE System Zone Room Zone - 001 Peak Zone - 001 Block spc_PE Team Lockey RH4_0 Peak Zone - 002 Peak Zone - 002 Block spc_PE 113 RH7/RH8_0 Peak Zone - 003 Peak Zone - 003 Block spc_PE 114 C_0 Peak Zone - 004 Peak Zone - 004 Block spc_PE 109 NC_0 Peak Zone - 005 Peak Zone - 005 Block spc_PE 2nd Flr Lobby_0 Peak Zone - 007 Peak Zone - 007 Block Peak spc_PE 214-218, 201-203 Offices C_0 Zone - 009 Peak Zone - 009 Block spc_PE 3 Press Box RH02 _0 Peak Zone - 010 Peak Zone - 010 Block PE VAV Htg Only Peak PE VAV Htg Only Block spc_sp_55 Peak Zone - 264 Peak Zone - 264 Block spc_sp_56 Peak Zone - 265 Peak Zone - 265 Block spc_sp_57 Peak Zone - 266 Peak Zone - 266 Block spc_sp_58 Peak Zone - 267 Peak Zone - 267 Block spc_sp_59 Peak Zone - 268 Peak Zone - 268 Block spc_sp_60 Peak Zone - 269 Peak Zone - 269 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 7,524 7,524 744 744 744 1,696 1,696 1,696 1,001 1,001 1,001 683 683 683 7,013 7,013 7,013 1,922 1,922 1,922 174 174 174 20,757 20,757 1,130 1,130 1,130 1,130 1,130 1,130 1,159 1,159 1,159 1,087 1,087 1,087 396 396 396 828 828 828 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /17 10 /16 10 /16 9 /16 9 /16 9 /10 9 /10 10 /15 10 /15 7 /10 7 /10 7/18 7 /18 10 /16 10 /16 7 /17 10 /13 10 /13 10 /15 10 /15 9 /12 9 /12 10 /16 10 /16 11 /15 11 /15 7 /18 7 /18 75 75 79 79 79 77 77 77 67 67 67 80 80 80 67 67 67 73 73 73 79 79 79 75 75 77 77 77 80 80 80 73 73 73 79 79 79 73 73 73 73 73 73 66 66 64 64 64 67 67 67 61 61 61 63 63 63 60 60 60 65 65 65 64 64 64 66 66 59 59 59 63 63 63 63 63 63 64 64 64 62 62 62 65 65 65 72.0 72.0 80.0 80.0 80.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 74.4 74.4 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 58.6 58.6 58.6 55.9 55.9 55.9 54.6 54.6 54.6 56.3 56.3 56.3 58.2 58.2 58.2 54.7 54.7 54.7 1,505 1,505 1,190 1,190 1,190 339 339 339 200 200 200 137 137 137 351 351 351 256 256 256 23 23 23 4,001 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 -636 -636 10,111 10,111 10,111 -143 -143 -143 -85 -85 -85 -58 -58 -58 -148 -148 -148 -108 -108 -108 -10 -10 -10 8,923 0 25,370 25,370 25,370 30,201 30,201 30,201 29,008 29,008 29,008 37,550 37,550 37,550 33,464 33,464 33,464 25,783 25,783 25,783 -4,539 -4,539 -971 -971 -971 2,691 2,691 2,691 1,039 1,039 1,039 306 306 306 -8,532 -8,532 -8,532 454 454 454 -45 -45 -45 -9,597 -3,178 2,062 2,062 2,062 2,910 2,910 2,910 3,573 3,573 3,573 3,013 3,013 3,013 1,051 1,051 1,051 2,864 2,864 2,864 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /14 9 /16 9 /16 9 /16 9 /16 9 /10 9 /10 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 9 /17 9 /17 7 /17 9 /14 9 /14 9 /16 9 /16 9 /14 9 /14 9 /16 9 /16 10 /15 10 /15 7 /18 7 /18 76 76 77 77 77 77 77 77 67 67 67 77 77 77 75 75 75 75 75 75 76 76 76 75 75 77 77 77 77 77 77 77 77 77 77 77 77 80 80 80 73 73 73 65 65 67 67 67 67 67 67 61 61 61 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 66 66 67 67 67 66 66 66 67 67 67 63 63 63 65 65 65 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 72.4 59.2 59.2 59.2 56.9 56.9 56.9 55.6 55.6 55.6 56.5 56.5 56.5 58.3 58.3 58.3 54.7 54.7 54.7 Coil Airflow cfm Coil Sensible Load Btu/h 451 451 357 357 357 102 102 102 60 60 60 41 41 41 105 105 105 77 77 77 7 7 7 1,200 0 1,702 1,702 1,702 1,687 1,687 1,687 1,499 1,499 1,499 2,144 2,144 2,144 2,178 2,178 2,178 1,338 1,338 1,338 -191 -191 3,033 3,033 3,033 -43 -43 -43 -25 -25 -25 -17 -17 -17 -44 -44 -44 -32 -32 -32 -3 -3 -3 12,882 0 36,547 36,547 36,547 44,525 44,525 44,525 40,050 40,050 40,050 54,574 54,574 54,574 40,936 40,936 40,936 38,829 38,829 38,829 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6,959 6,959 6,959 7,908 7,908 7,908 7,147 7,147 7,147 7,605 7,605 7,605 1,195 1,195 1,195 5,336 5,336 5,336 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 91 of 100 SPACE Floor Area ft² System Zone Room spc_sp_61 Zone - 270 Zone - 270 spc_sp_62 Zone - 271 Zone - 271 spc_sp_63 Zone - 272 Zone - 272 spc_sp_64 Zone - 273 Zone - 273 spc_sp_65 Zone - 274 Zone - 274 spc_sp_66 Zone - 275 Zone - 275 spc_sp_67 Zone - 276 Zone - 276 spc_sp_68 Zone - 277 Zone - 277 spc_sp_69 Zone - 278 Zone - 278 spc_sp_70 Zone - 279 Zone - 279 spc_sp_38 Zone - 280 Zone - 280 spc_sp_39 Zone - 281 Zone - 281 spc_sp_40 Zone - 282 Zone - 282 spc_sp_41 Zone - 283 Zone - 283 spc_sp_42 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 378 9 /11 378 378 9 /11 485 6 /10 485 485 6 /10 678 10 /16 678 678 10 /16 822 7 /18 822 822 7 /18 628 9 /11 628 628 9 /11 2,082 9 /16 2,082 2,082 9 /16 2,169 7 /17 2,169 2,169 7 /17 2,777 7 /17 2,777 2,777 7 /17 3,084 7 /17 3,084 3,084 7 /17 211 6 /10 211 211 6 /10 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 1,408 9 /16 1,408 1,408 9 /16 1,392 9 /16 1,392 1,392 9 /16 972 9 /16 70 70 70 65 65 65 79 79 79 73 73 73 70 70 70 77 77 77 75 75 75 75 75 75 75 75 75 65 65 65 77 77 77 77 77 77 77 77 77 77 77 77 77 63 63 63 58 58 58 64 64 64 65 65 65 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.5 57.5 57.5 55.5 55.5 55.5 56.3 56.3 56.3 51.4 51.4 51.4 56.1 56.1 56.1 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.5 52.5 52.5 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 28,760 28,760 28,760 11,994 11,994 11,994 23,923 23,923 23,923 13,067 13,067 13,067 26,223 26,223 26,223 53,398 53,398 53,398 48,975 48,975 48,975 57,415 57,415 57,415 55,454 55,454 55,454 13,285 13,285 13,285 28,858 28,858 28,858 28,858 28,858 28,858 35,056 35,056 35,056 34,765 34,765 34,765 27,232 1,212 1,212 1,212 1,286 1,286 1,286 1,878 1,878 1,878 2,838 2,838 2,838 2,011 2,011 2,011 7,723 7,723 7,723 7,128 7,128 7,128 9,122 9,122 9,122 10,121 10,121 10,121 559 559 559 3,036 3,036 3,036 3,036 3,036 3,036 5,223 5,223 5,223 5,163 5,163 5,163 3,608 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /11 7 /16 7 /16 9 /16 9 /16 7 /17 7 /17 9 /12 9 /12 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /16 7 /16 6 /10 6 /10 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 70 70 70 76 76 76 77 77 77 75 75 75 73 73 73 77 77 77 75 75 75 75 75 75 76 76 76 65 65 65 77 77 77 77 77 77 77 77 77 77 77 77 77 63 63 63 66 66 66 67 67 67 66 66 66 63 63 63 67 67 67 66 66 66 66 66 66 66 66 66 58 58 58 67 67 67 67 67 67 67 67 67 67 67 67 67 57.5 57.5 57.5 58.6 58.6 58.6 56.4 56.4 56.4 51.9 51.9 51.9 56.2 56.2 56.2 53.6 53.6 53.6 53.6 53.6 53.6 53.2 53.2 53.2 52.7 52.7 52.7 57.8 57.8 57.8 54.9 54.9 54.9 54.9 54.9 54.9 53.5 53.5 53.5 53.5 53.5 53.5 54.0 Coil Airflow cfm Coil Sensible Load Btu/h 1,775 1,775 1,775 652 652 652 1,371 1,371 1,371 570 570 570 1,481 1,481 1,481 2,604 2,604 2,604 2,386 2,386 2,386 2,736 2,736 2,736 2,545 2,545 2,545 837 837 837 1,512 1,512 1,512 1,512 1,512 1,512 1,697 1,697 1,697 1,685 1,685 1,685 1,355 32,826 32,826 32,826 16,489 16,489 16,489 33,562 33,562 33,562 23,710 23,710 23,710 32,978 32,978 32,978 80,411 80,411 80,411 79,136 79,136 79,136 95,193 95,193 95,193 95,526 95,526 95,526 14,677 14,677 14,677 41,068 41,068 41,068 41,068 41,068 41,068 53,076 53,076 53,076 52,584 52,584 52,584 39,863 Coil Latent Load Btu/h 1,973 1,973 1,973 3,057 3,057 3,057 4,742 4,742 4,742 5,052 5,052 5,052 3,012 3,012 3,012 14,541 14,541 14,541 13,382 13,382 13,382 17,116 17,116 17,116 19,369 19,369 19,369 694 694 694 5,720 5,720 5,720 5,720 5,720 5,720 9,832 9,832 9,832 9,719 9,719 9,719 6,796 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 92 of 100 SPACE Floor Area ft² System Zone Room Zone - 284 Zone - 284 spc_sp_43 Zone - 285 Zone - 285 spc_sp_44 Zone - 286 Zone - 286 spc_sp_45 Zone - 287 Zone - 287 spc_sp_46 Zone - 288 Zone - 288 spc_sp_47 Zone - 289 Zone - 289 spc_sp_48 Zone - 290 Zone - 290 spc_sp_49 Zone - 291 Zone - 291 spc_sp_50 Zone - 292 Zone - 292 spc_sp_51 Zone - 293 Zone - 293 spc_sp_52 Zone - 294 Zone - 294 spc_sp_53 Zone - 295 Zone - 295 spc_sp_54 Zone - 296 Zone - 296 spc_sp_22 Zone - 297 Zone - 297 spc_sp_23 Zone - 298 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 972 972 1,408 1,408 1,408 826 826 826 914 914 914 907 907 907 869 869 869 869 869 869 835 835 835 893 893 893 737 737 737 1,061 1,061 1,061 1,064 1,064 1,064 1,061 1,061 1,061 1,044 1,044 1,044 1,082 1,082 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /16 10 /15 10 /15 9 /16 9 /16 9 /16 9 /16 7 /18 7 /18 7 /18 7/18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 10 /13 10 /13 10 /13 10 /13 9 /12 9 /12 7 /18 7 /18 7 /18 77 77 80 80 80 77 77 77 77 77 77 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 77 77 77 77 77 77 73 73 73 73 73 73 73 73 67 67 63 63 63 67 67 67 67 67 67 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 59 59 59 59 59 59 63 63 63 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.0 54.0 56.0 56.0 56.0 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 53.9 53.9 53.9 54.1 54.1 54.1 54.2 54.2 54.2 54.0 54.0 54.0 55.0 55.0 55.0 58.7 58.7 58.7 58.7 58.7 58.7 54.7 54.7 54.7 53.1 53.1 53.1 53.4 53.4 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 27,232 27,232 38,302 38,302 38,302 27,994 27,994 27,994 26,885 26,885 26,885 25,235 25,235 25,235 22,064 22,064 22,064 22,983 22,983 22,983 22,536 22,536 22,536 23,576 23,576 23,576 24,944 24,944 24,944 24,323 24,323 24,323 24,374 24,374 24,374 27,301 27,301 27,301 22,248 22,248 22,248 24,586 24,586 3,608 3,608 3,626 3,626 3,626 3,067 3,067 3,067 3,393 3,393 3,393 3,140 3,140 3,140 3,008 3,008 3,008 3,009 3,009 3,009 2,891 2,891 2,891 3,092 3,092 3,092 2,553 2,553 2,553 1,935 1,935 1,935 1,941 1,941 1,941 3,272 3,272 3,272 3,609 3,609 3,609 3,741 3,741 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 9 /14 9 /14 9 /14 9 /14 9 /14 9 /14 7 /17 7 /17 7 /17 77 77 77 77 77 77 77 77 77 77 77 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 77 77 77 77 77 77 77 77 77 75 75 75 75 75 67 67 67 67 67 67 67 67 67 67 67 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 54.0 54.0 56.2 56.2 56.2 54.7 54.7 54.7 54.2 54.2 54.2 54.3 54.3 54.3 54.1 54.1 54.1 54.2 54.2 54.2 54.3 54.3 54.3 54.2 54.2 54.2 55.0 55.0 55.0 59.2 59.2 59.2 59.2 59.2 59.2 55.7 55.7 55.7 53.6 53.6 53.6 53.6 53.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,355 1,355 2,146 2,146 2,146 1,455 1,455 1,455 1,354 1,354 1,354 1,277 1,277 1,277 1,092 1,092 1,092 1,148 1,148 1,148 1,133 1,133 1,133 1,178 1,178 1,178 1,316 1,316 1,316 1,635 1,635 1,635 1,639 1,639 1,639 1,419 1,419 1,419 1,055 1,055 1,055 1,186 1,186 39,863 39,863 56,744 56,744 56,744 39,442 39,442 39,442 38,892 38,892 38,892 38,103 38,103 38,103 33,592 33,592 33,592 34,897 34,897 34,897 34,003 34,003 34,003 35,816 35,816 35,816 36,470 36,470 36,470 34,741 34,741 34,741 34,831 34,831 34,831 37,314 37,314 37,314 35,254 35,254 35,254 38,640 38,640 Coil Latent Load Btu/h 6,796 6,796 9,854 9,854 9,854 5,777 5,777 5,777 6,391 6,391 6,391 5,604 5,604 5,604 5,367 5,367 5,367 5,370 5,370 5,370 5,157 5,157 5,157 5,519 5,519 5,519 4,557 4,557 4,557 6,531 6,531 6,531 6,553 6,553 6,553 6,544 6,544 6,544 6,433 6,433 6,433 6,671 6,671 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 93 of 100 SPACE Floor Area ft² System Zone Room Zone - 298 spc_sp_24 Zone - 299 Zone - 299 spc_sp_25 Zone - 300 Zone - 300 spc_sp_26 Zone - 301 Zone - 301 spc_sp_27 Zone - 302 Zone - 302 spc_sp_28 Zone - 303 Zone - 303 spc_sp_29 Zone - 304 Zone - 304 spc_sp_30 Zone - 305 Zone - 305 spc_sp_31 Zone - 306 Zone - 306 spc_sp_32 Zone - 307 Zone - 307 spc_sp_33 Zone - 308 Zone - 308 spc_sp_34 Zone - 309 Zone - 309 spc_sp_35 Zone - 310 Zone - 310 spc_sp_36 Zone - 311 Zone - 311 spc_sp_37 Zone - 312 Zone - 312 Project Name: Dataset Name: SBCC TRACE.TRC Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 1,082 7 /18 1,074 7 /18 1,074 1,074 7 /18 955 7 /18 955 955 7 /18 995 9 /16 995 995 9 /16 894 7 /17 894 894 7 /17 1,063 10 /15 1,063 1,063 10 /15 684 6/10 684 684 6 /10 2,070 9 /16 2,070 2,070 9 /16 1,251 9 /16 1,251 1,251 9 /16 1,251 7 /17 1,251 1,251 7 /17 1,525 9 /16 1,525 1,525 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 818 9 /16 818 818 9 /16 73 73 73 73 73 73 73 77 77 77 75 75 75 80 80 80 65 65 65 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 65 65 65 65 65 65 65 67 67 67 66 66 66 63 63 63 58 58 58 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 53.4 53.1 53.1 53.1 53.6 53.6 53.6 55.1 55.1 55.1 55.0 55.0 55.0 56.6 56.6 56.6 55.8 55.8 55.8 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 24,586 22,945 22,945 22,945 22,834 22,834 22,834 37,026 37,026 37,026 29,118 29,118 29,118 36,090 36,090 36,090 18,202 18,202 18,202 52,942 52,942 52,942 35,189 35,189 35,189 31,103 31,103 31,103 60,677 60,677 60,677 29,082 29,082 29,082 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 28,858 3,741 3,711 3,711 3,711 3,304 3,304 3,304 3,697 3,697 3,697 2,943 2,943 2,943 2,737 2,737 2,737 1,813 1,813 1,813 7,679 7,679 7,679 4,645 4,645 4,645 4,115 4,115 4,115 5,660 5,660 5,660 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 3,036 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 7 /16 7 /16 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 9 /16 75 75 75 75 75 75 75 77 77 77 75 75 75 77 77 77 76 76 76 77 77 77 77 77 77 75 75 75 77 77 77 77 77 77 77 77 77 77 77 77 77 77 77 66 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 53.6 53.6 53.6 53.6 53.9 53.9 53.9 55.1 55.1 55.1 55.0 55.0 55.0 56.7 56.7 56.7 60.6 60.6 60.6 53.6 53.6 53.6 54.0 54.0 54.0 54.0 54.0 54.0 55.3 55.3 55.3 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 54.9 Coil Airflow cfm Coil Sensible Load Btu/h 1,186 1,089 1,089 1,089 1,115 1,115 1,115 1,960 1,960 1,960 1,538 1,538 1,538 2,104 2,104 2,104 1,005 1,005 1,005 2,580 2,580 2,580 1,753 1,753 1,753 1,549 1,549 1,549 3,258 3,258 3,258 1,526 1,526 1,526 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 1,512 38,640 36,369 36,369 36,369 35,270 35,270 35,270 51,628 51,628 51,628 42,996 42,996 42,996 51,414 51,414 51,414 22,226 22,226 22,226 79,873 79,873 79,873 52,725 52,725 52,725 48,027 48,027 48,027 82,120 82,120 82,120 41,372 41,372 41,372 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 41,068 Coil Latent Load Btu/h 6,671 6,615 6,615 6,615 5,894 5,894 5,894 6,966 6,966 6,966 5,530 5,530 5,530 7,439 7,439 7,439 4,311 4,311 4,311 14,458 14,458 14,458 8,749 8,749 8,749 7,730 7,730 7,730 10,664 10,664 10,664 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 5,720 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 94 of 100 SPACE Floor Area ft² System Zone Room spc_sp_7 Zone - 313 Zone - 313 spc_sp_8 Zone - 314 Zone - 314 spc_sp_9 Zone - 315 Zone - 315 spc_sp_10 Zone - 316 Zone - 316 spc_sp_11 Zone - 317 Zone - 317 spc_sp_12 Zone - 318 Zone - 318 spc_sp_13 Zone - 319 Zone - 319 spc_sp_14 Zone - 320 Zone - 320 spc_sp_15 Zone - 321 Zone - 321 spc_sp_16 Zone - 322 Zone - 322 spc_sp_17 Zone - 323 Zone - 323 spc_sp_18 Zone - 324 Zone - 324 spc_sp_19 Zone - 325 Zone - 325 spc_sp_20 Zone - 326 Zone - 326 spc_sp_21 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak 290 290 290 442 442 442 2,070 2,070 2,070 1,103 1,103 1,103 915 915 915 3,084 3,084 3,084 437 437 437 344 344 344 231 231 231 382 382 382 358 358 358 1,082 1,082 1,082 960 960 960 1,040 1,040 1,040 1,040 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 6 /18 6 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 6 /18 6 /18 7 /18 7 /18 9 /12 9 /12 6 /10 6 /10 6 /9 6 /9 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 7 /18 70 70 70 70 70 70 75 75 75 76 76 76 76 76 76 75 75 75 70 70 70 73 73 73 73 73 73 65 65 65 62 62 62 73 73 73 73 73 73 73 73 73 73 63 63 63 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 63 63 63 65 65 65 63 63 63 58 58 58 58 58 58 65 65 65 65 65 65 65 65 65 65 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 57.0 57.0 57.0 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 56.2 56.2 56.2 56.0 56.0 56.0 53.0 53.0 53.0 53.2 53.2 53.2 54.2 54.2 54.2 53.1 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 17,557 17,557 17,557 19,208 19,208 19,208 47,533 47,533 47,533 12,788 12,788 12,788 10,607 10,607 10,607 60,225 60,225 60,225 28,451 28,451 28,451 19,387 19,387 19,387 8,323 8,323 8,323 11,887 11,887 11,887 10,175 10,175 10,175 22,813 22,813 22,813 20,987 20,987 20,987 28,726 28,726 28,726 22,182 929 929 929 1,375 1,375 1,375 6,804 6,804 6,804 3,865 3,865 3,865 3,206 3,206 3,206 10,127 10,127 10,127 1,358 1,358 1,358 1,192 1,192 1,192 713 713 713 1,013 1,013 1,013 951 951 951 3,739 3,739 3,739 3,318 3,318 3,318 3,598 3,598 3,598 3,594 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /12 9 /12 7 /18 7 /18 7 /17 7 /17 7 /16 7 /16 7 /16 7 /16 7 /17 7 /17 7 /18 7 /18 7 /18 7 /18 9 /12 9 /12 7 /15 7 /15 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 7 /17 73 73 73 73 73 73 75 75 75 76 76 76 76 76 76 75 75 75 73 73 73 73 73 73 73 73 73 77 77 77 76 76 76 75 75 75 75 75 75 75 75 75 75 63 63 63 65 65 65 66 66 66 66 66 66 66 66 66 66 66 66 65 65 65 65 65 65 63 63 63 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 66 57.6 57.6 57.6 56.3 56.3 56.3 53.7 53.7 53.7 48.7 48.7 48.7 48.7 48.7 48.7 52.9 52.9 52.9 57.2 57.2 57.2 56.5 56.5 56.5 55.9 55.9 55.9 60.1 60.1 60.1 57.9 57.9 57.9 53.5 53.5 53.5 53.7 53.7 53.7 54.4 54.4 54.4 53.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,050 1,050 1,050 1,094 1,094 1,094 2,325 2,325 2,325 491 491 491 407 407 407 2,828 2,828 2,828 1,723 1,723 1,723 1,121 1,121 1,121 463 463 463 676 676 676 569 569 569 1,079 1,079 1,079 1,002 1,002 1,002 1,451 1,451 1,451 1,053 20,529 20,529 20,529 26,244 26,244 26,244 76,434 76,434 76,434 26,279 26,279 26,279 21,797 21,797 21,797 101,628 101,628 101,628 36,070 36,070 36,070 25,678 25,678 25,678 11,070 11,070 11,070 14,327 14,327 14,327 14,201 14,201 14,201 36,302 36,302 36,302 32,911 32,911 32,911 43,793 43,793 43,793 35,131 Coil Latent Load Btu/h 1,393 1,393 1,393 2,856 2,856 2,856 12,774 12,774 12,774 6,912 6,912 6,912 5,733 5,733 5,733 18,995 18,995 18,995 2,820 2,820 2,820 2,221 2,221 2,221 1,110 1,110 1,110 2,357 2,357 2,357 2,261 2,261 2,261 6,665 6,665 6,665 5,915 5,915 5,915 6,420 6,420 6,420 6,406 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 95 of 100 SPACE Floor Area ft² System Zone Room Zone - 327 Zone - 327 spc_sp_1 Zone - 328 Zone - 328 spc_sp_2 Zone - 329 Zone - 329 spc_sp_3 Zone - 330 Zone - 330 spc_sp_4 Zone - 331 Zone - 331 spc_sp_5 Zone - 332 Zone - 332 spc_sp_6 Zone - 333 Zone - 333 Child Cntr 2 Zone - 359 Zone - 359 Child Cntr 3 Zone - 360 Zone - 360 Child Cntr 1 Zone - 361 Zone - 361 Portopia HP Portopia HP spc_SS 141/142 Office_0 Zone - 012 Zone - 012 spc_SS 144 Office C_0 Zone - 013 Zone - 013 spc_SS 160B-D_0 Zone - 014 Zone - 014 spc_PS 160A Storage_0 Zone - 015 Zone - 015 Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block 1,040 1,040 1,272 1,272 1,272 1,074 1,074 1,074 999 999 999 1,613 1,613 1,613 664 664 664 1,956 1,956 1,956 211 211 211 211 211 211 211 211 211 75,038 75,038 313 313 313 168 168 168 0 0 0 102 102 102 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 7 /18 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 10 /15 10 /15 10 /16 10 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 6 /9 10 /15 10 /15 9 /11 9 /11 73 73 77 77 77 73 73 73 73 73 73 80 80 80 79 79 79 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 62 62 80 80 80 70 70 70 65 65 67 67 67 65 65 65 65 65 65 63 63 63 64 64 64 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 58 58 63 63 63 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Supply Dry Bulb °F 53.1 53.1 48.6 48.6 48.6 53.1 53.1 53.1 54.3 54.3 54.3 55.5 55.5 55.5 57.1 57.1 57.1 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 54.9 54.9 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 32 32 0 0 0 27 27 27 22,182 22,182 15,648 15,648 15,648 22,945 22,945 22,945 28,019 28,019 28,019 37,433 37,433 37,433 31,843 31,843 31,843 22,688 22,688 22,688 13,285 13,285 13,285 13,285 13,285 13,285 12,931 12,931 12,931 2,026,697 1,809,600 0 0 0 0 0 0 0 0 0 0 0 0 3,594 3,594 4,707 4,707 4,707 3,711 3,711 3,711 3,457 3,457 3,457 4,151 4,151 4,151 1,840 1,840 1,840 6,857 6,857 6,857 559 559 559 559 559 559 370 370 370 246,137 246,507 181 181 181 97 97 97 0 0 0 -2 -2 -2 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /17 7 /16 7 /16 7 /17 7 /17 7 /17 7 /17 9 /16 9 /16 9 /16 9 /16 7 /16 7 /16 6 /10 6 /10 6 /10 6 /10 6 /10 6 /10 7 /17 6 /9 6 /9 6 /9 6 /9 9 /16 9 /16 9 /11 9 /11 75 75 76 76 76 75 75 75 75 75 75 77 77 77 77 77 77 76 76 76 65 65 65 65 65 65 65 65 65 75 75 62 62 62 62 62 62 77 77 77 70 70 70 66 66 66 66 66 66 66 66 66 66 66 67 67 67 67 67 67 66 66 66 58 58 58 58 58 58 58 58 58 66 66 58 58 58 58 58 58 67 67 67 63 63 63 53.6 53.6 48.8 48.8 48.8 53.6 53.6 53.6 54.5 54.5 54.5 56.4 56.4 56.4 57.3 57.3 57.3 48.7 48.7 48.7 57.8 57.8 57.8 57.8 57.8 57.8 58.3 58.3 58.3 55.1 56.7 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 Coil Airflow cfm 1,053 1,053 600 600 600 1,089 1,089 1,089 1,420 1,420 1,420 2,033 2,033 2,033 1,915 1,915 1,915 871 871 871 837 837 837 837 837 837 849 849 849 106,096 106,096 81 81 81 32 32 32 0 0 0 27 27 27 Coil Sensible Load Btu/h 35,131 35,131 31,358 31,358 31,358 36,369 36,369 36,369 42,495 42,495 42,495 56,782 56,782 56,782 43,282 43,282 43,282 46,620 46,620 46,620 14,677 14,677 14,677 14,677 14,677 14,677 14,524 14,524 14,524 3,006,774 2,862,181 0 0 0 0 0 0 0 0 0 0 0 0 Coil Latent Load Btu/h 6,406 6,406 7,970 7,970 7,970 6,615 6,615 6,615 6,169 6,169 6,169 11,281 11,281 11,281 4,645 4,645 4,645 12,262 12,262 12,262 694 694 694 694 694 694 460 460 460 480,065 462,701 0 0 0 0 0 0 0 0 0 0 0 0 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 96 of 100 SPACE Floor Area ft² System Zone Room spc_SS 160 Class C_0 Zone - 016 Zone - 016 spc_SS 162 Class_0 Zone - 017 Zone - 017 spc_PS 112 Office C_0 Zone - 018 Zone - 018 spc_PS 111-115 Office C_0 Zone - 019 Zone - 019 spc_PS Lecture 117 C_0 Zone - 020 Zone - 020 spc_PS Lecture FC-4C_0 Zone - 021 Zone - 021 spc_PS 120-128 Class_0 Zone - 022 Zone - 022 spc_PS Class 121/122_0 Zone - 023 Zone - 023 spc_PS 130 Auditorium C_0 Zone - 024 Zone - 024 PS Fan Coil Htg Only PS Fan Coil Htg Only spc_SS 171-173, 178 Office C_0 Zone - 037 Zone - 037 spc_SS 135 Office_0 Zone - 038 Zone - 038 spc_SS Corridor 120 C_0 Zone - 039 Zone - 039 spc_SS 180 Worm Rm VAV-20_0 Zone - 040 Zone - 040 spc_SS 110C Wrk Rm C_0 Zone - 041 Project Name: Dataset Name: SBCC TRACE.TRC Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak 565 565 565 967 967 967 215 215 215 602 602 602 1,126 1,126 1,126 1,036 1,036 1,036 886 886 886 695 695 695 1,413 1,413 1,413 8,090 8,090 561 561 561 92 92 92 1,787 1,787 1,787 326 326 326 766 766 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 10 /16 10 /16 9 /17 9 /17 7 /18 7 /18 6 /9 6 /9 7 /16 7 /16 10 /16 10 /16 10 /16 7 /16 7 /16 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 6 /9 70 70 70 70 70 70 79 79 79 79 79 79 76 76 76 73 73 73 62 62 62 76 76 76 79 79 79 79 79 76 76 76 76 76 76 76 76 76 79 79 79 62 62 63 63 63 63 63 63 64 64 64 64 64 64 67 67 67 65 65 65 58 58 58 66 66 66 64 64 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 58 58 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 274 274 274 45 45 45 378 378 378 616 616 616 1,984 1,984 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,317 5,317 5,317 875 875 875 7,342 7,342 7,342 11,961 11,961 11,961 38,530 38,530 836 836 836 1,430 1,430 1,430 157 157 157 435 435 435 1,356 1,356 1,356 1,374 1,374 1,374 1,392 1,392 1,392 992 992 992 2,191 2,191 2,191 10,439 7,971 1,465 1,465 1,465 241 241 241 2,794 2,794 2,794 902 902 902 2,030 2,030 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /11 9 /11 10 /16 10 /16 9 /17 9 /17 9 /17 9 /17 7 /18 7 /18 7 /9 7 /9 7 /16 7 /16 9 /16 9 /16 9 /16 9 /17 9 /17 9 /17 9 /17 9 /16 9 /16 9 /16 9 /16 7 /10 70 70 70 70 70 70 79 79 79 76 76 76 76 76 76 73 73 73 64 64 64 76 76 76 77 77 77 77 77 76 76 76 76 76 76 77 77 77 77 77 77 67 67 63 63 63 63 63 63 64 64 64 67 67 67 67 67 67 65 65 65 59 59 59 66 66 66 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 60 60 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 113 113 113 193 193 193 71 71 71 240 240 240 225 225 225 207 207 207 177 177 177 139 139 139 283 283 283 1,790 1,790 268 268 268 44 44 44 364 364 364 593 593 593 1,874 1,874 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5,089 5,089 5,089 838 838 838 5,425 5,425 5,425 13,863 13,863 13,863 40,338 40,338 Coil Latent Load Btu/h 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2,917 2,917 2,917 480 480 480 4,022 4,022 4,022 2,276 2,276 2,276 2,929 2,929 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 97 of 100 SPACE System Zone Room Zone - 041 Block spc_SS 110 Wrk Rm/Office C_0 Peak Zone - 042 Peak Zone - 042 Block Peak spc_SS 100 100H 111H Main Lobby C_0 Zone - 043 Peak Zone - 043 Block spc_SS 150 Wrk Rm C_0 Peak Zone - 044 Peak Zone - 044 Block spc_SS 177-179 Office_0 Peak Zone - 045 Peak Zone - 045 Block spc_SS Wrk Rm1 V-19_0 Peak Zone - 046 Peak Zone - 046 Block spc_SS 120-124 C_0 Peak Zone - 047 Peak Zone - 047 Block spc_SS 135-139 Office C_0 Peak Zone - 048 Peak Zone - 048 Block spc_SS 140 Wrk Rm C_0 Peak Zone - 049 Peak Zone - 049 Block spc_SS 125-129_0 Peak Zone - 050 Peak Zone - 050 Block spc_SS 230B Office C_0 Peak Zone - 051 Peak Zone - 051 Block spc_SS 214 Office C_0 Peak Zone - 052 Peak Zone - 052 Block spc_SS 282 Wrk Rm C_0 Peak Zone - 053 Peak Zone - 053 Block spc_SS 280D Office_0 Peak Zone - 054 Peak Zone - 054 Block spc_SS 280A-C C_0 Peak Zone - 055 Peak Zone - 055 Block Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 766 1,420 1,420 1,420 37 37 37 301 301 301 635 635 635 207 207 207 703 703 703 586 586 586 848 848 848 642 642 642 285 285 285 130 130 130 136 136 136 154 154 154 459 459 459 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 6 /9 9 /17 9 /17 7 /18 7 /18 7 /15 7 /15 7 /16 7 /16 7 /15 7 /15 6/9 6 /9 7 /16 7 /16 9 /16 9 /16 6 /18 6 /18 6 /18 6 /18 10 /16 10 /16 10 /16 10 /16 7 /17 7 /17 9 /11 9 /11 62 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 62 62 62 76 76 76 77 77 77 70 70 70 70 70 70 79 79 79 79 79 79 75 75 75 70 70 70 58 67 67 67 65 65 65 66 66 66 66 66 66 66 66 66 58 58 58 66 66 66 67 67 67 63 63 63 63 63 63 64 64 64 64 64 64 66 66 66 63 63 63 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,984 844 844 844 348 348 348 167 167 167 310 310 310 115 115 115 1,253 1,253 1,253 286 286 286 545 545 545 1,766 1,766 1,766 526 526 526 623 623 623 1,441 1,441 1,441 75 75 75 1,255 1,255 1,255 38,530 16,389 16,389 16,389 6,755 6,755 6,755 3,248 3,248 3,248 6,019 6,019 6,019 2,238 2,238 2,238 24,336 24,336 24,336 5,555 5,555 5,555 10,576 10,576 10,576 34,294 34,294 34,294 10,214 10,214 10,214 12,096 12,096 12,096 27,981 27,981 27,981 1,450 1,450 1,450 24,365 24,365 24,365 2,030 4,101 4,101 4,101 63 63 63 1,044 1,044 1,044 1,658 1,658 1,658 719 719 719 1,862 1,862 1,862 1,530 1,530 1,530 3,146 3,146 3,146 1,992 1,992 1,992 572 572 572 244 244 244 378 378 378 408 408 408 1,469 1,469 1,469 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /10 9 /17 9 /17 7 /18 7 /18 9 /16 9 /16 9 /17 9 /17 9 /16 9 /16 7 /10 7 /10 9 /17 9 /17 9 /16 9 /16 7 /18 7 /18 7 /18 7 /18 9 /16 9 /16 9 /16 9 /16 7 /17 7 /17 9 /11 9 /11 67 76 76 76 73 73 73 77 77 77 76 76 76 77 77 77 67 67 67 76 76 76 77 77 77 73 73 73 73 73 73 77 77 77 77 77 77 75 75 75 70 70 70 60 67 67 67 65 65 65 67 67 67 67 67 67 67 67 67 60 60 60 67 67 67 67 67 67 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 63 63 63 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 1,874 844 844 844 348 348 348 165 165 165 304 304 304 114 114 114 1,181 1,181 1,181 280 280 280 545 545 545 1,745 1,745 1,745 522 522 522 610 610 610 1,360 1,360 1,360 75 75 75 1,255 1,255 1,255 40,338 16,959 16,959 16,959 8,572 8,572 8,572 3,134 3,134 3,134 5,761 5,761 5,761 2,159 2,159 2,159 25,288 25,288 25,288 5,317 5,317 5,317 10,803 10,803 10,803 37,007 37,007 37,007 11,167 11,167 11,167 14,956 14,956 14,956 32,179 32,179 32,179 3,723 3,723 3,723 28,088 28,088 28,088 Coil Latent Load Btu/h 2,929 7,387 7,387 7,387 90 90 90 2,099 2,099 2,099 3,302 3,302 3,302 1,446 1,446 1,446 2,687 2,687 2,687 3,047 3,047 3,047 5,923 5,923 5,923 4,132 4,132 4,132 1,239 1,239 1,239 651 651 651 953 953 953 703 703 703 2,386 2,386 2,386 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 98 of 100 SPACE System Zone Room spc_SS 272 Wrk Rm C_0 Peak Zone - 056 Peak Zone - 056 Block spc_SS 270C/D Office_0 Peak Zone - 057 Peak Zone - 057 Block spc_SS 111H Hall_0 Peak Zone - 058 Peak Zone - 058 Block spc_SS 110G/H Offices C_0 Peak Zone - 059 Peak Zone - 059 Block spc_SS 111A Office C_0 Peak Zone - 060 Peak Zone - 060 Block spc_SS 242 Wrk Rm C_0 Peak Zone - 061 Peak Zone - 061 Block spc_SS 240L Office C_0 Peak Zone - 062 Peak Zone - 062 Block spc_SS 240H Office_0 Peak Zone - 063 Peak Zone - 063 Block spc_SS 240F/J Office_0 Peak Zone - 064 Peak Zone - 064 Block spc_SS 240-260A Wrk Rm C_0 Peak Zone - 065 Peak Zone - 065 Block spc_SS 202/250B Office_0 Peak Zone - 066 Peak Zone - 066 Block spc_SS 250 Wrk Rm C_0 Peak Zone - 067 Peak Zone - 067 Block spc_SS 251 Wrk Rm C_0 Peak Zone - 068 Peak Zone - 068 Block Peak spc_SS 230H, 200-201, 251H, 272H_0 Zone - 069 Peak Zone - 069 Block spc_SS 210/211 Wrk Rm C_0 Peak Project Name: Dataset Name: SBCC TRACE.TRC Floor Area ft² 778 778 778 287 287 287 397 397 397 269 269 269 216 216 216 642 642 642 149 149 149 181 181 181 274 274 274 865 865 865 214 214 214 0 0 0 388 388 388 4,383 4,383 4,383 308 OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 9 /11 9 /11 9 /12 9 /12 7 /18 7 /18 7 /16 7 /16 7 /16 7 /16 10 /16 10 /16 7 /17 7 /17 7 /16 7 /16 7 /17 7 /17 10 /16 10 /16 7 /16 7 /16 6 /9 6 /9 9 /12 9 /12 7 /16 7 /16 7 /15 70 70 70 73 73 73 73 73 73 76 76 76 76 76 76 79 79 79 75 75 75 76 76 76 75 75 75 79 79 79 76 76 76 62 62 62 73 73 73 76 76 76 77 63 63 63 63 63 63 65 65 65 66 66 66 66 66 66 64 64 64 66 66 66 66 66 66 66 66 66 64 64 64 66 66 66 58 58 58 63 63 63 66 66 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 1,090 1,090 1,090 379 379 379 175 175 175 131 131 131 105 105 105 406 406 406 73 73 73 89 89 89 133 133 133 1,257 1,257 1,257 104 104 104 16 16 16 387 387 387 2,716 2,716 2,716 171 21,179 21,179 21,179 7,364 7,364 7,364 3,399 3,399 3,399 2,552 2,552 2,552 2,048 2,048 2,048 7,890 7,890 7,890 1,410 1,410 1,410 1,719 1,719 1,719 2,589 2,589 2,589 24,416 24,416 24,416 2,028 2,028 2,028 304 304 304 7,518 7,518 7,518 52,749 52,749 52,749 3,325 2,489 2,489 2,489 627 627 627 612 612 612 703 703 703 564 564 564 1,777 1,777 1,777 397 397 397 474 474 474 728 728 728 2,394 2,394 2,394 559 559 559 0 0 0 1,195 1,195 1,195 15,399 15,399 15,399 1,069 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 9 /13 9 /13 9 /13 9 /13 7 /18 7 /18 9 /17 9 /17 9 /17 9 /17 7 /16 7 /16 7 /17 7 /17 9 /17 9 /17 7 /17 7 /17 9 /16 9 /16 9 /17 9 /17 7 /10 7 /10 9 /12 9 /12 7 /16 7 /16 7 /16 75 75 75 75 75 75 73 73 73 76 76 76 76 76 76 76 76 76 75 75 75 76 76 76 75 75 75 77 77 77 76 76 76 67 67 67 73 73 73 76 76 76 76 65 65 65 65 65 65 65 65 65 67 67 67 67 67 67 66 66 66 66 66 66 67 67 67 66 66 66 67 67 67 67 67 67 60 60 60 63 63 63 66 66 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h 918 918 918 357 357 357 175 175 175 129 129 129 103 103 103 394 394 394 73 73 73 87 87 87 133 133 133 1,221 1,221 1,221 102 102 102 15 15 15 387 387 387 2,716 2,716 2,716 171 25,380 25,380 25,380 10,543 10,543 10,543 3,469 3,469 3,469 2,443 2,443 2,443 1,960 1,960 1,960 17,212 17,212 17,212 3,620 3,620 3,620 1,646 1,646 1,646 6,646 6,646 6,646 38,964 38,964 38,964 1,941 1,941 1,941 312 312 312 8,858 8,858 8,858 113,463 113,463 113,463 7,815 Coil Latent Load Btu/h 4,471 4,471 4,471 973 973 973 790 790 790 1,400 1,400 1,400 1,123 1,123 1,123 4,042 4,042 4,042 684 684 684 943 943 943 1,256 1,256 1,256 6,040 6,040 6,040 1,112 1,112 1,112 0 0 0 1,856 1,856 1,856 27,598 27,598 27,598 1,937 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 99 of 100 SPACE Floor Area ft² System Zone Room Zone - 070 Zone - 070 spc_SS 230F Office C_0 Zone - 071 Zone - 071 spc_SS Wrk Rm 230 C_0 Zone - 072 Zone - 072 spc_SS 230C-E Office_0 Zone - 073 Zone - 073 spc_SS 240B Wrk Rm C_0 Zone - 074 Zone - 074 spc_SS 181 Comp Rm C_0 Zone - 075 Zone - 075 spc_SS 182 Comp Rm C_0 Zone - 076 Zone - 076 Stdnt Srv VAV Stdnt Srv VAV Project Name: Dataset Name: SBCC TRACE.TRC Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Peak Block Peak Block OA Room Peak Condition Dry Time DB WB Bulb °F °F Mo/Hr °F 308 308 7 /15 180 6 /18 180 180 6 /18 987 7 /16 987 987 7 /16 630 6 /18 630 630 6 /18 240 10 /16 240 240 10 /16 854 7 /18 854 854 7/18 863 9 /11 863 863 9 /11 23,178 23,178 7 /17 77 77 70 70 70 76 76 76 70 70 70 79 79 79 73 73 73 70 70 70 75 75 66 66 63 63 63 66 66 66 63 63 63 64 64 64 65 65 65 63 63 63 66 66 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 72.0 COIL Supply Dry Bulb °F Space Air Flow cfm Space Sensible Load Btu/h Space Latent Load Btu/h 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 171 171 330 330 330 550 550 550 1,887 1,887 1,887 607 607 607 2,223 2,223 2,223 2,317 2,317 2,317 27,996 21,892 3,325 3,325 6,408 6,408 6,408 10,680 10,680 10,680 36,641 36,641 36,641 11,782 11,782 11,782 43,184 43,184 43,184 45,011 45,011 45,011 543,738 425,196 1,069 1,069 360 360 360 3,468 3,468 3,468 1,262 1,262 1,262 663 663 663 2,471 2,471 2,471 2,243 2,243 2,243 66,071 67,555 OA Peak Condition Supply Time DB WB Dry Bulb °F °F Mo/Hr °F 7 /16 7 /18 7 /18 7 /16 7 /16 7 /18 7 /18 9 /16 9 /16 7 /18 7 /18 9 /11 9 /11 7 /17 76 76 73 73 73 76 76 76 73 73 73 77 77 77 73 73 73 70 70 70 75 75 66 66 65 65 65 66 66 66 65 65 65 67 67 67 65 65 65 63 63 63 66 66 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 54.6 Coil Airflow cfm Coil Sensible Load Btu/h Coil Latent Load Btu/h 171 171 326 326 326 550 550 550 1,854 1,854 1,854 595 595 595 2,223 2,223 2,223 2,317 2,317 2,317 27,337 21,892 7,815 7,815 9,430 9,430 9,430 25,113 25,113 25,113 48,827 48,827 48,827 15,938 15,938 15,938 45,640 45,640 45,640 49,534 49,534 49,534 713,169 592,652 1,937 1,937 781 781 781 6,215 6,215 6,215 2,736 2,736 2,736 1,674 1,674 1,674 4,381 4,381 4,381 3,536 3,536 3,536 122,218 121,687 TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013 Peak Clg Loads Main System Report Page 100 of 100 APPENDIX APPENDIX "E" - SCE Fact Sheets TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 © 2013 SC ENGINEERS, INC. "E" DEMAND RESPONSE Technical Assistance with Technology Incentives Technical Assistance provides on-site facility evaluations ranging from simple site assessments to comprehensive engineering studies to SDG&E® business customers at no cost. These assessments are designed to determine load reduction potential. • Technical incentives help off-set Technology Incentives help off-set the installation and equipment costs of demand response measures. Technology incentives follow the completion of the Technical Assistance assessment and the identification of verifiable load reduction. Incentive amounts are up to $125/kW. Businesses with annual maximum demands equal to or greater than 20 kilowatts are eligible. Who should participate? TECHNICAL ASSISTANCE: Business customers who want to identify how to reduce their energy demand during critical peak periods, known as Demand Response events. The evaluation ranges from simple site assessments to a complete engineering study with no cost to the customer. The depth of the assessment will be determined by the facility’s potential to reduce electric load. TECHNOLOGY INCENTIVES: Customers who want to implement demand reduction measures to reduce their energy use during critical peak periods. Qualified measures are those that aid in the facility’s ability to reduce load when called upon by the utility. Additionally, these measures allow customers to participate in voluntary Demand Response programs for additional financial incentives. A higher incentive of $300/kW is available to customers who can fully automate their demand response strategy utilizing their Energy Management System. Customer benefits • Technical assessments can assist customers in identifying effective energy management strategies that can result in cost savings and incentives. installation and equipment costs, which can help justify energy improvement projects and potentially shorten pay-back periods. Who is eligible to participate? How does the program work? Customers interested in participating should call 1-800-644-6133. After a review of the customer’s demand response potential, an on-site assessment will be scheduled. Customers will receive a report with demand reduction potential and load reduction strategies such as enhanced EMS equipment, or automation measures and other demand response measures. Customers can either utilize the engineering or consulting firm of their choice or opt to have SDG&E assign a firm to complete the audit. If you prefer to select your own engineering firm to perform the assessment, the cost is reimbursable up to $125/kW load reduction, not to exceed the cost of the assessment, provided the results are approved by SDG&E. After the Technical Assistance audit has been approved, customers may then choose to apply for Technology Incentives. These incentives can pay for or help offset the cost of putting controls on an Energy Management System to automate the demand response strategy. This automation will aid in the facility’s ability to reduce load when called upon by the utility. Customers who wish to receive technology incentives must demonstrate their actual ability to reduce demand and enroll in an SDG&E Demand Response program in order to receive 100% of the incentive. Technical Assistance with Technology Incentives program gives business customers the necessary information and means to participate in various voluntary Demand Response programs offered by SDG&E. The Demand Response programs offer incentives for load reduction during critical peak periods. Managing your energy use SDG&E has programs and services to help your business get more out of the energy that you use. Information on everything from seminars to online energy analysis tools, rebates and other financial incentives can be found 24 hours a day, seven days a week on our Energy Savings Center website at www.sdge.com/esc. For more information Technical Assistance with Technology Incentives is part of SDG&E’s Demand Response programs — a component of SDG&E’s long-term resource plan, and one of the ways SDG&E is developing energy solutions for the region. For more details on Technical Assistance with Technology Incentives, please contact your SDG&E Account Executive, call 1-800-644-6133, or email drp@semprautilites.com. This program is available throughout California and is offered by the state’s investor-owned utilities. SAN DIEGO GAS & ELECTRIC® P. O . B OX 1 2 9 8 3 1 , S A N D I E G O, C A 92 1 1 2- 9 8 3 1 1-800-411-SDGE (7343) w w w. s d g e . c o m /d r p © 2009 San Diego Gas & Electric Company. All copyright and trademark rights reserved. 0980252 1109 E N E R GY E F F I C I E N C Y COMMERCIAL & INDUSTRIAL Energy Efficiency Business Incentives What are Energy Efficiency Business Incentives? These programs and services are one way SDG&E is here for you every day. Energy Efficiency Business Incentives (EEBI) offers incentive payments for energy efficiency projects involving the installation of new, high-efficiency equipment or systems. A project may consist of the retrofit of existing equipment/systems or the installation of equipment associated with new/ added load. Estimation software or engineering calculations are used to estimate the energy savings and incentive depending on the type of energy efficiency measure installed. Some projects may require a measured savings approach. Incentives are paid based on the quantity of kilowatt-hours (kWh) or therms saved resulting from the installation of the new equipment or system. required to benchmark their building using ENERGY STAR® Portfolio Manager. Please note that not all buildings are eligible to receive a benchmark score. What are the Project Requirements? Who is Eligible? Any commercial, industrial or agricultural customer who pays the public goods charge and/or demand-side management surcharge is eligible to participate regardless of size or project scope. Customers who participate in our energy efficiency programs and are eligible to receive a benchmark score are The equipment must exceed government standards, must operate at least five years and must not overlap other incentive programs offered by the utility. Pre-inspections are required for all projects. Incentives for Calculated Savings Approach Lighting $0.05/kWh $100/Peak kW* A/C & Refrigeration $0.15/kWh $100/Peak kW* Other (motors, fans, etc.) $0.09/kWh $100/Peak kW* Natural Gas $1.00/Therm Incentives for Measured Savings Approach will receive an additional 10% to help offset the measurement costs. * Peak Demand Reduction Incentive Are there Any Limitations? Applicants are eligible to receive up to 50% of the cost for each project for calculated (EEBI) measures or the calculated savings amount, whichever is less. Measures involving cogeneration or fuel-switching projects are not eligible. (Continued on back) How Do I Apply? Complete and submit the program application forms which can be found at sdge.com/eebi or e-mail us at eebi@semprautilities.com for assistance with completing the application forms. What is the Deadline for Participation? Program incentive funds will be allocated on a first-come, first-served basis, until all funds are committed or until December 31, 2012, whichever occurs first. If all funds are committed prior to December 31, 2012, applications received by December 31 will be placed on a waiting list by SDG&E®, and will be notified in order of receipt if additional funds become available. Managing Your Energy Use SDG&E has programs and services to help your business get more out of the energy that you use. Information on everything from seminars to online energy analysis tools, rebates and other financial incentives can be found on our Energy Savings Center website at sdge.com/business. Helping businesses manage their energy use is one of the ways SDG&E is committed to providing exceptional customer service. Payment Schedule:* Benchmarking Benchmarking with the Environmental Protection Agency’s ENERGY STAR Portfolio Manager allows you to track and assess energy performance across your entire portfolio of buildings in a secure online environment. Portfolio Manager will rate your facility’s energy performance on a scale of 1 to 100 relative to similar buildings nationwide. Additional information on energy planning is available through our Continuous Energy Improvements initiative at sdge.com/cei. Programs are funded by California utility customers and administered by San Diego Gas & Electric® (SDG&E) under the auspices of the California Public Utilities Commission. Program incentive funds will be allocated on a first-come, first-served basis, until all funds are committed or until December 31, 2012, whichever occurs first. The selection, purchase, and ownership of goods and services are the sole responsibility of the customer. SDG&E makes no warranty, whether express or implied, including warranty of merchantability or fitness for any particular purpose, use or application of selected goods and services. Measurement & Verification (M&V) Approach Payment Schedule Calculated Savings Approach 100% — after installation and verification none Measured Savings Approach 60% — after installation and verification 1 year 40% — one (1) year after installation date with verification * If the project is very complex and/or involves new technology, we reserve the right to require a 2-year M&V period for customers. In this case, a 40%-30%-30% payment schedule will apply. 1-80 0 -411-SDGE ( 7 343) sdge.com ©2010 San Diego Gas & Electric Company. All copyright and trademark rights reserved. 1080056 0410 XXM E N E R GY E F F I C I E N C Y COMMERCIAL & INDUSTRIAL Energy Efficiency Business Rebates What are Energy Efficiency Business Rebates? Offers rebates to help business customers offset the cost of installing energy-efficient equipment. Energy Efficiency Business Rebates (EEBR) offer rebates to eligible business customers for installing energy-efficient lighting, refrigeration, foodservice, natural gas and other technologies. Installing energy-efficient equipment in a business can help reduce energy consumption and operating expenses, which leads to greater profitability, productivity and efficiency. Rebates are designed to encourage such installations by helping to offset the cost of installing energy efficient equipment. Who is eligible? EEBR is open to nonresidential customers with existing buildings that have an electric or natural gas account with SDG&E®. Nonresidential customers include commercial, industrial and agricultural customers. What are the project requirements? The equipment must meet the requirements listed in the Rebate Application and the Product Catalog. All equipment must be new. Used or rebuilt equipment is not eligible for a rebate. If a customer has received an incentive or service from another state or local Public Goods Charge program, they are ineligible to receive a rebate for the same measure(s). Are there any limitations? Fuel switching and new construction do not qualify. The total rebate limit is $350,000 per service account, per fuel, per calendar year. Customers with multiple service accounts or chain account customers may receive rebates for multiple projects; provided that each individual service account or site limit of $350,000 is not exceeded. There is no limit on the number of service accounts that may participate. How do I apply? You must complete and submit the application forms along with your benchmarking ENERGY STAR® Statement of Energy Performance. The Rebate Application forms and the Product Catalog can be found at sdge.com/businessrebates, while information about benchmarking can be found at sdge.com/benchmarking. Managing Your Energy Use SDG&E has programs and services to help your business get more out of the energy that you use. For more information please visit our Energy Savings Center at sdge.com/esc or call us at 1-800-644-6133. Helping businesses manage their energy use is one of the ways SDG&E is committed to providing exceptional customer service. SDG&E rebate programs are funded by California utility customers and administered by SDG&E under the auspices of the California Public Utilities Commission. This program is provided to qualified participants on a first-come, first-served basis until program funds are no longer available. SDG&E is not responsible for any goods or services that you or a vendor may select. This program may be modified or terminated without prior notice. 1-80 0 -411-SDGE ( 7 343) sdge.com ©2010 San Diego Gas & Electric Company. All copyright and trademark rights reserved. 1080062 0410 XXM ONLINE TOOLS & OTHER RESOURCES kWickview: Online Energy Monitor Track and manage your business energy usage online. • Export data – view data as graphs or charts, and export them into a spreadsheet program or into a PDF. You can also have reports automatically emailed to you at pre-determined intervals. How do I access kWickview? You can either: • Visit www.sdge.com/kwickview. • Click on the kWickview link at www.sdge.com/drp. What is kWickview? ® kWickview is an online tool from SDG&E that provides energy use data via the Internet to businesses with special interval data recorder (IDR) meters. The energy use data is measured in 15 minute intervals over a 24-hour period, and can be downloaded and viewed the next morning. Who can use kWickview? kWickview is available to business customers with an installed IDR meter. Also, business customers participating in a Demand Response program have access to kWickview. Is special software needed to use kWickview? No, kWickview is a web-based online tool. © 2006 San Diego Gas & Electric Company. All copyright and trademark rights reserved. All you need is a computer with Internet access and a web browser. What can I do with kWickview? How can I learn more about kWickview? kWickview can help you track and manage your energy usage online. Here’s some of the things you can do with kWickview: Visit www.sdge.com/kwickview and view an interactive flash-based demo of kWickview, or to sign up for regularly scheduled kWickview trainings. • Load profile comparisons – know when and how you are using energy. Conduct detailed analysis with pinpoint accuracy. Managing your energy use • View usage history – view daily, weekly or monthly total consumption and peak demand. View usage over different time periods. • Run energy-use comparisons – compare individual meters or sites, or group them for side-by-side analysis. You can also normalize data to help put comparison data in better context. S A N D I EG O G A S & E L EC T R I C ® P. O . B OX 1 2 9 8 3 1 , S A N D I EG O, C A 92 1 1 2- 9 8 3 1 w w w. s d g e . c o m SDG&E has programs and services to help your business get more out of the energy that you use. Information on everything from seminars, online energy analysis tools, rebates and other financial incentives can be found 24 hours a day, seven days a week at www.sdge.com/business. Helping businesses manage their energy use is one of the ways SDG&E is committed to providing exceptional customer service. E Printed on Recycled Paper 0640060 1106 TECHNICAL INFORMATION & RESOURCES Optimize Your IT Infrastructure and Reduce Costs with Server Virtualization Financial incentives from SDG&E® may help you save thousands of dollars per year on your operating costs Growing enterprises have ever-increasing needs for more computing power. Yet the costs associated with obtaining that added capacity go beyond the purchase of new server hardware. Additional power, facility Server virtualization adds up to real savings 20 Conventional servers under moderate conditions consumes about 90,000 kWh / year 1 new host server, supporting 20 virtual machines under moderate conditions consumes about 6,600 kWh / year 90,000 kWh – 6,600 kWh = 83,400 kWh savings cooling, network and storage infrastructure, administration, maintenance, and data center upgrades or construction are also part of the equation that can add up quickly. To help you meet your organization’s expanding IT requirements while at the same time reducing your operating and energy costs, SDG&E® provides significant financial incentives when you implement server virtualization. What is server virtualization? 83,400 x $0.08 = $6,672 SDG&E Energy Efficiency Program Incentive Server virtualization consolidates many physical servers running individual operating systems and programs into one physical server with multiple virtual server partitions that act as independent servers. In other words, one server efficiently doing the work of many. Server CPUs typically run at about 5-15 percent efficiency, meaning you’re paying for a lot of unused computing power. With server virtualization, software is used to boost a server’s operating efficiency to over 80 percent in many situations.1 The end result: the workload currently handled by 20 servers could now be accomplished with just one—without any anticipated decrease in performance. To the end-user, server virtualization is transparent. To your IT staff, the improvements might be substantial…along with your cost savings. (continued) 1 CPU efficiency improvement varies according to workloads, hardware, configuration and other factors. OPTIMIZE YOUR IT INFRASTRUCTURE (continued) Lowering your TCO, improving IT deliverables For CFOs, server virtualization means fewer servers working more efficiently. Capital spending on costly equipment upgrades, installation and maintenance may be reduced because less equipment is required—equipment that can be placed in a smaller space. This equates to lower power consumption and facility cooling requirements, and may lessen the need to add more support infrastructure and IT staff. For CIOs, server virtualization could provide improved manageability. By consolidating the number of servers you must maintain, you may have more quality staff time for improving services instead of managing hardware. And with a smaller equipment footprint, it is likely you could deliver greater responsiveness to changing company needs. System backup would be © 2007 San Diego Gas & Electric Company. All copyright and trademarks rights reserved. easier, because a complete virtual machine environment is saved as a single file. Disaster recovery may be faster, too, since virtual servers are isolated from the host and other virtual machines. If a virtual machine crashes, all others should be unaffected. How SDG&E can help you pay for server improvements Server virtualization is an important part of SDG&E’s energy efficiency incentive programs that can help lower your ROI on such projects tremendously. Incentives of 8 cents per kilowatt hour saved are available, meaning you may receive thousands of dollars toward energy saving server virtualization project costs. Your company could be able to both run more efficiently and lower it’s operating costs at the same time. Plus, you would help make more energy available for homes and businesses throughout Southern California. SAN DIEGO GAS & ELECTRIC® P. O . B OX 1 2 9 8 3 1 , S A N D I E G O, C A 92 1 1 2- 9 8 3 1 w w w. s d g e . c o m Give us a call—we’ll help you get started SDG&E can help you estimate your energy savings in advance and determine just what your financial incentives from SDG&E might be. Whether you’re a co-location company, a biotech firm, data service center, or server farm…anyone with multiple servers can save substantial time and money—and utilize more computing power with lower equipment, support and energy costs— through server virtualization. Providing customers with energy efficiency information is one of the ways SDG&E works to provide exceptional customer service. To learn more, call 1-800-644-6133 or visit www.sdge.com Rebate/incentive programs are funded by California utility customers and administered by SDG&E, under the auspices of the California Public Utilities Commission. Programs may be modified or terminated without prior notice, and are provided on a first-come, first-served basis until program funds are no longer available. SDG&E is not responsible for any goods or services selected by the customer. E Printed on recycled paper 0740053 0807 2.5M INTEREST-FREE FINANCING On-Bill Financing Option energy savings not to exceed the maximum loan term. Loan funds must be used for the purchase and installation of qualifying energy efficiency measures. What are the loan limits? The project cost (after reduced rebates or incentives are applied) must be a minimum of $5,000. Loan maximums per meter are: • $100,000 for business customers with a 5-year maximum loan term • $250,000 for tax-payer funded customers with a 10-year maximum loan term How do I apply? What is On-Bill Financing? The On-Bill Financing (OBF) Program helps qualified commercial and taxpayerfunded customers pay for energy-efficient business improvements through their SDG&E® bill. OBF works in conjunction with the SDG&E rebate and incentive programs listed to provide an interest-free financing option for customers eligible to participate in such rebate and incentive programs. Who is eligible? Customers that are eligible for On-Bill Financing must meet the following criteria: • The customer must receive a rebate or incentive through an SDG&E energyefficiency program. • The customer must have had an active SDG&E account for the past two years for the same business. • The customer's SDG&E account must be in good standing, with no deposit on record and no disconnect notices in the last 12 months. Participation in one of the following programs is required for On-Bill Financing: Small Business Super Saver, Express Efficiency, Standard Performance Contract, Energy Savings Bid and select Utility Third Party Programs. Owners of multi-family units who do not live on the premises may qualify for financing through the Multi-Family Rebate program. Will On-Bill Financing affect the measure rebate amount? Rebates and incentives awarded to customers who complete non-comprehensive projects will be reduced by 10%. Comprehensive projects are defined as two or more distinct measures not including CFLs or delamping. How is the loan term calculated? The loan term for the project is determined by the repayment period of the equipment selected through the eligible program(s) and is calculated based on estimated annual To find out more about this program, including details, terms and conditions, and a list of all of the energy-efficiency applications with which OBF can be used, please visit www.sdge.com/obf. Or, call or e-mail us: • Energy Information Center (Monday - Friday, 8am - 5pm) 1-800-644-6133 • SDGEOBF@semprautilities.com Managing Your Energy Use SDG&E has programs and services to help your business get more out of the energy that you use. Information on everything from seminars to online energy analysis tools, rebates and other financial incentives can be found 24 hours a day, seven days a week on our Energy Savings Center website at www.sdge.com/esc. Helping businesses manage their energy use is one of the ways SDG&E is committed to providing exceptional customer service. On-Bill Financing is provided to eligible customers on a first-come, first-served basis until program funds are no longer available. OBF is funded by California utility customers and administered by SDG&E under the auspices of the California Public Utilities Commission. SAN DIEGO GAS & ELECTRIC® P. O . B OX 1 2 9 8 3 1 , S A N D I EG O, C A 92 1 1 2- 9 8 3 1 w w w. s d g e . c o m © 2009 San Diego Gas & Electric Company. All copyright and trademark rights reserved. E Printed on recycled paper with soy-based inks. 0980007 0109 INTEREST-FREE FINANCING On-Bill Financing Option Frequently Asked Questions be reduced by 10%. Comprehensive projects are defined as two or more distinct measures not including CFLs or delamping. 6. How is my loan term calculated? Below is a sample of a project: Energy savings is based on equipment installed multiplied by your average cost per kilowatt hour. 1. Who qualifies for On-Bill Financing? On-Bill Financing is available to any commercial or taxpayer-funded customer participating in the following programs: Small Business Super Saver, Express Efficiency, Standard Performance Contract, Energy Savings Bid, Multi-Family Rebate Program (for owners not living at the premises) and Utility Third Party Programs. Financing is available for measures qualifying for a rebate or incentive. 2. Is there a credit check involved? SDG&E® determines eligibility by checking: • If you have had an active account for at least two years, or if you have moved your business from another location you must have at least one year of energy usage at new location • If there are any disconnect notices in the last 12 months • If there is a deposit on hand 3. Can I finance any new equipment I want? Only equipment qualifying for SDG&E rebates or incentives can be financed through OBF. 4. Are there any other requirements that I need to know about? If your equipment qualifies for a rebate or an incentive, you must also make sure that your project meets these requirements: • For business customers, loans must have a minimum of $5,000, and a maximum up to $100,000 per meter, with a simple payback of no more than 5 years. • For taxpayer-funded customers, loans must have a minimum of $5,000 financed and a maximum up to $250,000 per meter, with a simple payback of no more than 10 years. 5. Do I get my full rebate if I participate in OBF? Customers who complete comprehensive projects will receive a full rebate. Rebates and incentives awarded to customers who complete non-comprehensive projects will Project Cost $10,000 Rebate/Incentive amount with 10% OBF reduction $4,000 Loan Amount $6,000 Estimated Annual savings for new equipment $4,000 Simple payback period 1.6 years On-Bill Financing Loan Installment (1.6 year + 1 month) $320 7. What if I move to a new location? If you have a loan through OBF and you move to a new location, your loan must be paid in full on your final bill. Payment arrangements may be made when opening your new account. 8. Can I have more than one loan? Yes, you can have one loan per meter. 9. Can I install the equipment myself to finance? Yes, SDG&E has a loan agreement for self-installed projects. A pre-inspection by SDG&E is required for every site prior to removing old equipment. 10. How do I get started? Call the Energy Information Center at 1-800-644-6133 to request an application or download one at www.sdge.com/obf. SAN DIEGO GAS & ELECTRIC® P. O . B OX 1 2 9 8 3 1 , S A N D I EG O, C A 92 1 1 2- 9 8 3 1 w w w. s d g e . c o m © 2009 San Diego Gas & Electric Company. All copyright and trademark rights reserved. E Printed on recycled paper with soy-based inks. 0980009 0109 ENERGY-EFFICIENCY CASE STUDIES SC ENGINEERS ABOUT SAVINGS BY DESIGN Energy-efficient buildings happen by design. They happen because they make sense — for the owner, the design team, the bottom line, and the environment. No matter how you are involved in the design and construction of a commercial or industrial project, SDG&E’s Savings By Design Program can help provide long-term savings in the use of the building as well as cash incentives to the design team and the building owner. SC Engineers designs better buildings There is no off-the-shelf solution for energy-efficient buildings. For maximum energy savings, efficiency must be designed into the building from scratch. And that’s where Shadpour Consulting Engineers, Inc. shines as a pioneer in creative design solutions. SC Engineers is a consulting mechanical engineering firm based in Rancho Bernardo, a community within the city of San Diego. They provide innovative design solutions for HVAC, plumbing, and building automation systems, as well as services for total building commissioning and energy management programs. They strive to forge integrated business partnerships with their clients and produce long-term, sustainable design solutions. An educated approach Company president Frank Shadpour is a registered Mechanical Engineer, LEED® accredited professional, and ASHRAE Fellow. Since 1987, he has taught courses in HVAC Design and Control Systems Engineering at the University of California, San Diego. SC Engineers is recognized as a local leader in sustainable design and energy-efficiency planning. With those credentials, it’s not surprising that Shadpour is a long-time believer in sustainable building design. “In addition to teaching at UCSD, I’ve been part of SDG&E’s Education & Training Program,” Shadpour says. “I feel fortunate to have a platform for touting energy efficiency.” SC Engineers was founded on the principles of “lean thinking.” This carries through into all aspects of their engineering design and corporate philosophy. “People can save energy and money through smart building design and efficient management of the various building systems. The energy savings often offset the associated costs. It doesn’t cost extra to go green if you do it right from the start.” “We’ve made it our business to know SDG&E’s incentive and rebate programs inside and out,” says Shadpour. “This knowledge means our clients can maximize every opportunity. And when that happens, we know we’ve done our job.” Their efforts have helped SDG&E® customers realize significant energy and financial savings through intelligent, energy-efficient designs and retrofits. Education & Training An excellent result SDG&E business seminars and training opportunities cover the latest energyefficiency technologies for motors, lighting, heating, air-conditioning (HVAC) systems, and more. SC Engineers is an innovative leader and approved provider for SDG&E’s Retrocommissioning Program (RCx). RCx is a systematic process for optimizing a building’s operating and maintenance profile, focusing on low-cost or no-cost operational measures. Most projects see a 5% to 20% reduction in utility costs as a result of SC Engineers’ retrocommissioning efforts. SC Engineers also provides demand response studies, which help identify opportunities to reduce demand. In the last year alone, SC Engineers identified over 4.5 megawatts (MW) in peak electrical demand reduction, averaging more than a 10% reduction per customer. SC Engineers incorporates energy savings into their own design projects as well. Recent projects include the Rady Children’s Acute Care Tower and Ronald McDonald House, with a combined projected energy savings of nearly 1.4 million kilowatt-hours (kWh) and 38,000 therms per year. “The Children’s Hospital project is likely to be the first LEED® hospital in California,” says Chip Fox, Manager of SDG&E’s New Construction Energy-Efficiency Programs. “Frank is also heavily involved in the community doing a variety of fundraising for the local Cancer Society.” To date, SC Engineers & Friends has raised more than $200,000 benefiting non-profit organizations in San Diego Seminars include rebate and incentive information, so you can learn which energy-efficiency programs make the most sense for your facility. These free events are held throughout the year at various locations. Register at sdge.com/training. Retrocommissioning The Retrocommissioning Program (RCx) provides incentives and training for large businesses to achieve energy savings and improve occupant comfort through costeffective optimization of building performance. For more information, contact Margaret Finley, SDG&E Program Manager, at 858-636-5732. Demand Response Financial incentives, like bill credits and electric rate discounts are available to companies that can save energy during temporary critical times through SDG&E’s Demand Response programs. Programs are available for companies of all types and sizes. To identify demand response opportunities at your facility, visit sdge.com/esc. Lyle Willis, Jeremy Clifton, Frank Shadpour (L to R) including the American Cancer Society and City of Hope. “Our combined efforts in the future Rady Children’s Hospital and Ronald McDonald House will result in very healthy and well-designed buildings,” says Marianne Sy, Account Executive for SDG&E's Savings By Design Program. “SC Engineers has done an excellent job in influencing owners and the design community to do the right thing — simply because they believe in it themselves.” Energy efficiency starts with a plan. To see how the Savings by Design Program can work for your business, contact your SDG&E account executive, call 1-800-411-7343 or visit sdge.com/savingsbydesign. © 2008 San Diego Gas & Electric Company. All trademarks belonging to their respective owners. All rights reserved. Some materials used under license, with all rights reserved by licensor. C Please recycle. 0850038-BT 0508