solution 1 - Santa Barbara City College

Santa Barbara City College
Demand Response Technical Audit
Santa Barbara, California
Prepared for:
Facility Director: Julie Hendricks
Account Executive: Lisa Hannaman
Prepared by:
March 8, 2013
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
SCE Job Number 1282
Mechanical Engineers
Principals:
Frank Shadpour, P.E.
Jeremy Clifton, P.E.
Edward Lehman, P.E.
Lyle Willis, P.E.
Joseph Kilcoyne, P.E.
March 8, 2013
Ms. Julie Hendricks
Santa Barbara City College
721 Cliff Dr
Santa Barbara, CA 93109
Project:
Santa Barbara City College
SC Project Number: 09141.021
SCE Job Number: 1282
Subject:
Demand Response Technical Audit (TA) Study
Ms. Hendricks,
SC Engineers is pleased to present the findings for the Demand Response Technical Assistance (TA) Study for Santa Barbara
City College.
The intent of this energy analysis report is to identify and evaluate potential electrical demand reduction savings in accordance
with SCE’s TA/TI program guidelines at the Santa Barbara City College. Appropriate details are included in this report to make
informed decisions regarding implementing demand response measures at this facility. However, this report is not intended to
serve as a detailed engineering design document. The descriptions of the improvements are only diagrammatic in nature to
document the basis of cost estimates and savings, and to demonstrate the feasibility to implement the recommended upgrades.
It should be noted that detailed design efforts may be required to implement several of the improvements evaluated as part of
this energy analysis.
While the recommendations in this report have been reviewed for technical accuracy and are believed to be accurate, the
findings are estimates and actual results will vary based on future building use and weather patterns. All savings and cost
estimates in the report are for informational purposes, and should not be construed as a design document or as guarantees.
Please note that the recommendations included are for your reference only and by no means mandatory.
Thank you for this opportunity to be of service.
Sincerely,
SC ENGINEERS, INC.
Frank Shadpour, P.E., CxA, LEED AP
President
17075 Via Del Campo
First Floor
San Diego, CA 92127
858.946.0333 Tel
858.946.0334 Fax
www.scengineers.net
TABLE OF CONTENTS
EXECUTIVE SUMMARY
PAGE
Scope of the Report........................................................................................................................................................... 1
Synopsis and Findings....................................................................................................................................................... 1
Measures Summary........................................................................................................................................................... 2
TECHNICAL ANALYSIS
Problem Statement............................................................................................................................................................
Existing Conditions............................................................................................................................................................
Demand Response Measure # 1: HVAC - Chilled Water Supply Temperature Reset...................................................
Demand Response Measure # 2: HVAC - Space Temperature Reset...........................................................................
Demand Response Measure # 3: HVAC - Data Center Temperature Reset.................................................................
Demand Response Measure # 4: HVAC - Heating Hot Water Pump Shutdown............................................................
Demand Response Measure # 5: Lighting - Lighting Reduction....................................................................................
Demand Response Measure # 6: Process Load - Fountain Pump Shutdown...............................................................
Demand Response Measure # 7: Process Load - Pre-Cool Refrigeration Spaces........................................................
Demand Response Measure # 8: Process Load - Beverage Vending Machine Compressor Shutdown.......................
3
3
9
10
11
12
13
14
15
16
CONCLUSION
Energy Efficiency Measures Summary.............................................................................................................................. 17
Demand Response Measures Summary........................................................................................................................... 20
APPENDICES
APPENDIX "A" - Equipment Lists
APPENDIX "B" - SCE Technical Analysis Forms
APPENDIX "C" - Calculations and Supporting Information
APPENDIX "D" - TRACE 700 Building Energy Simulation Results
APPENDIX "E" - SCE Fact Sheets
Building Information Model of SBCC Main Buildings
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE i
SCE Job Number 1282
EXECUTIVE SUMMARY
Scope of the Report
This report provides an evaluation of potential electrical kW demand reduction in the Santa Barbara City College, located
at 721 Cliff Dr in Santa Barbara, California in accordance with the SCE Technical Assistance and Audit Report Program.
Synopsis and Findings
This Technical Audit identifies electrical kW demand reduction strategies, their associated projected kW savings, and
recommends measures for automating demand response.
Existing On-peak kW Demand: Based on the average of the top 15 days of 2012 SCE load profile records, the
on-peak electrical demand for the facility is approximately 1,661 kW.
Average On-peak kW Demand Reduction: The total average summer on-peak reduction in kW demand addressed
in this Technical Audit Report is 497 kW (30% of existing facility demand).
▪ Based on a Critical Peak Pricing (CPP) utility rate, the projected demand reduction will result in a $2,123
savings per event if all measures are implemented for the full 4 hour event period.
Existing Annual Energy Consumption: Based on 2012 representative SCE records, the facility's annual energy
consumption is approximately 7,300,000 kWh [11.9 kWh / (sf yr)].
Effect of Demand Response on Peak Load
Demand Response Day Profile
Typical Peak Demand Profile
1,800
Electricity Demand (kW)
1,600
1,400
1,200
1,000
800
600
400
200
23:00
22:00
21:00
20:00
19:00
18:00
17:00
16:00
15:00
14:00
13:00
12:00
11:00
10:00
9:00
8:00
7:00
6:00
5:00
4:00
3:00
2:00
1:00
0:00
0
Time
Peak Day Demand Profile Comparison
• SCE Incentives: Demand Response technology incentives are available as follows:
▪ Semi-Automated: 497 kW x $125/kW = $62,125
▪ Fully Automated*: 497 kW x $300/kW = $149,100
• All measures identified have been discussed with facility operating personnel and are considered possible based on
the functional requirements of the facility.
• Actual incentives available will be based on testing conducted by SCE's third party verification engineer.
* Fully automated measures are those that can be implemented through the building automation system without human intervention
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 1
SCE Job Number 1282
EXECUTIVE SUMMARY
Demand Response Measures Summary
Demand response measures identified for the Santa Barbara City College fall into three (3) categories. The measures for
each category are summarized as follows:
Demand Response Measure # 1:
Demand Response Measure # 2:
Demand Response Measure # 3:
Demand Response Measure # 4:
Demand Response Measure # 5:
Demand Response Measure # 6:
Demand Response Measure # 7:
Demand Response Measure # 8:
HVAC - Chilled Water Supply Temperature Reset - 14.2 kW
HVAC - Space Temperature Reset - 340.9 kW
HVAC - Data Center Temperature Reset - 2.4 kW
HVAC - Heating Hot Water Pump Shutdown - 9.2 kW
Lighting - Lighting Reduction - 113.5 kW
Process Load - Fountain Pump Shutdown - 3.2 kW
Process Load - Pre-Cool Refrigeration Spaces - 2.8 kW
Process Load - Beverage Vending Machine Compressor Shutdown - 11.1 kW
The total potential average demand reduction available during summer on-peak hours is 497 kW.
DR # 2 - Space
Temperature Reset, 340.9
kW, 21%
DR # 3 - Space
Temperature Reset #2:, 2.4
kW, 0%
DR # 4 - Heating Hot Water
Pump Shutdown, 9.2 kW,
1%
DR # 5- Lighting Reduction,
113.5 kW, 7%
DR #1 - Chilled Water
Supply Temperature Reset,
14.2 kW, 1%
DR # 6 - Fountain Pump
Shutdown, 3.2 kW, 0%
DR # 7 - Pre-Cool
Refrigeration Spaces, 2.8
kW, 0%
DR # 8 - Beverage Vending
Machine Compressor
Shutdown, 11.1 kW, 1%
Remaining Facility Peak
Demand Load, 1,163.6 kW,
70%
Facility Peak Electrical Demand Reduction
Construction Estimates: The construction estimates within this report are approximated and have not been verified by
a construction estimator or contractor. The actual cost may vary. Verification of construction cost by the owner is required.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 2
SCE Job Number 1282
TECHNICAL ANALYSIS
Problem Statement
The Technical Assistance & Technology Incentive (TA & TI) program was established to identify opportunities for reducing
the overall demand requirements for SCE's electrical service during critical peak periods known as “Demand Response”
events. This Technical Audit Report identifies the potential for kW demand reduction in the Santa Barbara City College
under SCE's TA & TI Program. Demand reduction opportunities are addressed for the facility’s electrical requirements
during the SCE summer on-peak electrical demand period between June 1 and October 1.
Demand Response Overview:
Demand Response (DR) is a voluntary and short-term reduction in a consumer's use of electricity during a period of peak
electrical demand when the power grid is stressed. SCE Demand Response (DR) program allows customers to
participate in DR events without manual interference using a building management system (BMS). The program enables
customers to choose their level of participation and to pre-select the measures that are implemented during an event
saving energy, time, and money.
The DR program is automated through a Demand Response Automation Server (DRAS) which provides an alert message
to commercial customers or aggregators participating in the program. The DR alert messages are provided to customer
control systems by either the utility company or the California ISO, a company that provides open and non-discriminatory
access to the bulk of the state's wholesale electrical transmission. The complex DR signals are then translated into a
simple to understand language using the OpenADR standard. OpenADR is a communications data model designed
around internet language standards which includes the XML format. The alert message is then either implemented
manually by a facility staff member via a centralized control system (Semi-automated Demand Response) or automated
without human intervention via the central computer system (Fully-automated Demand Response). The DR
communication network is shown in the figure below.
The benefits of Demand Response include the following:
-Price control with minimal to no energy importing
-Increased grid reliability
-No new or peaker power plants
-Reduced natural resource usage
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 3
SCE Job Number 1282
TECHNICAL ANALYSIS
Existing Conditions
The Santa Barbara City College consists of approximately twenty (20) buildings consisting of approximately 550,000 sq.
ft., approximately fifty (50) portable units consisting of approximately 62,500 sq. ft., a parking structure, several parking
lots, and sporting fields. The campus is heavily occupied from 7:00am - 8:00pm as it hosts several evening classes in
addition to a typical school day schedule. The majority of rooms consist of class/lecture and office occupancies. Other
notable areas are the gymnasium located in the Physical Education building and the performance stages located in the
Drama and Music building. These areas may hold additional events not associated directly with the college.
Facility Electrical Demand: The average of the annual top eighteen demand days for the facility is approximately
1,661 kW based on SCE load profile records. The Santa Barbara City College is served by two (2) electric meters
equipped with Internal Data Recorder (IDR) capability. The kW load profile is shown below for the average top fifteen kW
demand days and the twelve event days in the 2012 demand response season.The average summer daily load profile is
also shown for reference. The building's electrical peak is typically 150% times larger than the baseline. This indicates
that the load is dependent on time-of-day loads and outdoor conditions.
2012 Peak Demand Profiles
2,000
9/20
9/10
1,800
8/29
1,600
1,400
8/27
1,200
8/20
1,000
8/13
800
8/9
600
8/7
400
7/23
200
7/12
0
6/29
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Electrical Demand (kW)
9/28
Time of Day
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
Average Top 15
Peak Day
Average Day
June-Sep
PAGE 4
SCE Job Number 1282
SBCC CAMPUS OVERVIEW
The Santa Barbara City College is separated into two (2) main campuses: West Campus and East Campus. These
campuses are divided by Loma Alta Drive, and are connected by a pedestrian bridge. Portable units are found on both
campuses. The details of the campuses are shown in the table below:
Campus
West Campus
East Campus
Portables
Number of
Buildings
6
13
~50
Total Floor Area
(sq ft)
182,520
366,832
62,500
Existing Systems: The details of HVAC electrical loads per each building in the two (2) campuses can be found in the
following pages. Refer to the Equipment List in Appendix A for details. The systems common among both campuses are
described below:
HVAC ~ Control System: The HVAC equipment for the main buildings at the Santa Barbara City College are controlled
and monitored by a Johnson Controls (JCI) DDC system. This system can be accessed through computers located in the
Facilities & Operations building. The system can not be accessed remotely due to strict campus internet security. The
JCI system controls the majority of major HVAC equipment on campus: chillers, air handlers, heat pumps, fan coils, etc.
Facility staff can schedule HVAC equipment through the JCI system and timeclocks. Facility staff noted that they monitor
buildings and adjust schedules as needed. Some chillers at the college are programmed with a chiller wated reset.
Lighting Systems: Interior lighting for the college is provided primarily by 4’, T8 fluorescent fixtures. Some 4', T12
fixtures and high intensity discharge (HID) fixtures serve areas of the college as well. Approximately 85% of the campus
contains bi-level switching capabilities. Refer to Appendix C for a detailed lighting schedule by area.
Lighting Control Systems: Occupancy sensors were found sporadically throughout offices, classrooms, and
laboratories on the campus. No central lighting control system exists. Outdoor lighting is controlled by photocells.
Security lighting serves the campus and is scheduled to be on 100% from dusk to midnight, then 50% from midnight to
dawn. Parking structure lights were noted to be on timers.
Process Loads ~ The college contains the following high energy process loads:
▪
Elevators that serve multi-level buildings.
▪
The Business/Communications Building holds a cafeteria with associated equipment including: several
refrigerator units, one (1) walk-in refrigerator, and one (1) walk-in freezer.
▪
The Campus Center/HRC Building holds a dining area on the second floor and two (2) kitchens on the first
floor with associated equipment including: several refrigerator units, two (2) walk-in refrigerators, and three (3)
walk-in freezers.
▪
A water feature on the West Campus.
▪
A water fountain on the East Campus.
▪
Several vending machines located around the college.
▪
Stadium and field lighting, typically only enabled from dusk to midnight.
Library Interior Lighting
Typical Refrigeration Units
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
Typical Light Occupancy Sensor
PAGE 5
SCE Job Number 1282
WEST CAMPUS OVERVIEW
The Santa Barbara City College West Campus encompasses the following buildings:
Bldg
Bldg Name
BC
C
DM/GT
FO
IDC
L/LRC
Business/Communication Center
Child Center
Drama/Music & Gavin Theatre
Facilities & Operations
Interdisciplinary Center
Luria Library/Learning Resource Center
Floor Area
(sq ft)
35,466
6,375
46,325
2,880
39,147
52,327
Occupancy Type
Class/Café
Child Care
Theatre/Class
Office/Garage
Class/Office
Library
College Map: West Campus Buildings Highlighted
Existing Systems: The electrical demand for the facility is the result of a variety of electrical loads within the building.
These systems are noted as having potential for Demand Reduction. Refer to the Equipment List and Layout in Appendix
A for details.
HVAC ~ Chilled Water Systems: The West Campus has three (3) buildings that are served by a self-contained chiller
plant. These chiller plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below details
specific building chiller plants:
Equipment
Associated
Bldg
Equipment
Qty
Notes
Served
Pump Qty
BC
Air-Cooled Chiller
1 AHU's/Fan Coils
2
IDC
2 AHU's/Fan Coils
Air-Cooled Chiller
1
L/LRC
Air-Cooled Chiller
2
VAV AHU's
2
Redundant
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 5
SCE Job Number 1282
EAST CAMPUS OVERVIEW
HVAC ~ Heating Hot Water Systems: The West Campus has three (3) buildings that are served by a self-contained
boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below
details specific building boiler plants:
Equipment
Associated
Bldg
Equipment
Qty
Notes
Served
Pump Qty
BC
1 Rooftop AHU's
Gas Boiler
2
IDC
Gas Boiler
1 VAV AHU/Fan Coils
1
L/LRC
1
Gas Boiler
VAV AHU's
2
HVAC ~ Air-Side Systems: The buildings with chiller and boiler plants are served by fan coils, constant air volume
(CAV), and variable air volume (VAV) AHU's. The other buildings are conditioned primarily by direct expansion (DX) units:
Bldg
BC
BC
C
C
C
DM/GT
DM/GT
DM/GT
DM/GT
FO
IDC
IDC
IDC
L/LRC
Equipment
Rooftop AHU's
Fan Coils
Ht Furnace
Pckg Unit
Pckg Gas/Elect
Pckg Heat Pump
Pckg Gas/Elect
Split Sys Fan Coil
Heat Pumps
Packaged DX
VAV AHU
CAV AHU
Fan Coils
VAV AHU's
Qty
8
21
1
1
1
4
2
5
10
1
1
1
4
1
Areas Served
Flr 3, Kitchen, Rm232
Flrs 1/2 Major Rms
Major Rms
Major Rms
Major Rms
Changing Rms
Auditorium/Theatre
Varies
Varies
Offices/Conference
Int. Rms - Flrs 1/2
Hallways
Some Rms - Flr 3
All major rooms
Drama/Music Building
LRC AHU Sensor Readings
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
Notes
Htg Only
Some Htg only
IDC Building
BC Air-Cooled Chiller
PAGE 6
SCE Job Number 1282
EAST CAMPUS OVERVIEW
The Santa Barbara City College East Campus encompasses the following buildings:
Bldg
Bldg Name
A
CBS
CC
EBS
HRC
H
IE
MTBLDG
OE
PE
PS
PS
SS
Administration
Bookstore
Campus Center
Earth & Biological Sciences
Hotel/Restaurant/Culinary
Humanities
International Education Center
Marine Technology
Occupational Education
Physical Education/Sports Pavilion
Physical Science
Physical Science Lecture
Student Services
Floor Area
(sq ft)
76,454
18,283
30,384
30,623
5,591
39,912
4,406
8,208
18,389
64,894
22,767
3,883
43,038
Occupancy Type
Offices
Retail
Dining/Kitchen/Class
Class/Lab
Dining/Kitchen/Class
Class/Office/Studio
Class
Class/Office/Marine
Class/Office/Garage
Gymnasium/Activity
Class/Office
Lecture
Offices
College Map: East Campus Buildings Highlighted
Existing Systems: The electrical demand for the facility is the result of a variety of electrical loads within the building.
These systems are noted as having potential for Demand Reduction. Refer to the Equipment List and Layout in Appendix
A for details.
HVAC ~ Chilled Water Systems: The East Campus has five (5) buildings that are served by a self-contained chiller
plant. These chiller plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below details
specific building chiller plants:
Equipment
Associated
Bldg
Equipment
Qty
Notes
Served
Pump Qty
A
Air-Cooled Chiller
1
AHU's 3, 4, 5
2
EBS
Air-Cooled Chiller
1
AHU's
2
H
Air-Cooled Chiller
1 AHU's/Fan Coils
1
OE
Air-Cooled Chiller
1
AHU's
1
SS
Air-Cooled Chiller
2
AHU's
2
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 7
SCE Job Number 1282
EAST CAMPUS OVERVIEW
HVAC ~ Heating Hot Water Systems: The East Campus has seven (7) buildings that are served by a self-contained
boiler plant. These boiler plants serve the building's hydronic air handling units (AHU's) and fan coils. The table below
details specific building boiler plants:
Equipment
Associated
Bldg
Equipment
Qty
Notes
Served
Pump Qty
A
Gas Boiler
2
AHU's
2
Gas Boiler
AHU's
2
CC/HRC
2
EBS
Gas Boiler
1 VAV AHU/Fan Coils
2
H
Gas Boiler
2 AHU's/Fan Coils
1
OE
1
Gas Boiler
AHU
2
PE
Gas Boiler
1
AHU
2
SS
Gas Boiler
2
AHU's
2
HVAC ~ Air-Side Systems: East Campus buildings are served by a combination of DX units, hydronic constant air
volume (CAV), and variable air volume (VAV) AHU's. Specific building air-side equipment is detailed below:
Bldg
Equipment
A
A
A
A
A
CBS
CC/HRC
CC/HRC
CC/HRC
CC/HRC
CC/HRC
EBS
EBS
EBS
H
H
H
MTBLDG
OE
OE
OE
PE
PE
PS
SS
VAV
VAV
Split Heat Pumps
Split System
Hydronic Fan Coils
Gas/Elect Split Sys
AHU
Split Heat Pumps
Pckg Unit
Htg/Clg Unit
Split System
VAV
VAV
Fan Coils
AHU
Split Sys Fan Coils
Split Sys Fan Coils
Gas Furnace
AHU
Multi-Zone AHU
Fan Coils
AHU
Pckg HP
Split Sys Fan Coils
AHU
Qty
2
3
13
4
2
7
1
4
1
3
1
5
5
11
3
3
1
3
4
1
1
4
8
12
3
Areas Served
Notes
Flrs 1 and 2
Flrs 1 and 2
Varies
Server Rooms
Server Rooms
All major areas
Flrs 1 and 2
Offices/Class
Cyber Center
Lobby/Office/Class
Kitchen
Major areas
Major areas
Major areas
Major areas
Some flr 3 rooms
Server Rm
Offices
Shops/Studio/Media
Drafting Rms
Offices
Gym
Offices
Major areas
Major areas
Htg Only
Clg and Htg
EBS Rooftop Equipment
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
Economizers
Htg Only
Clg Only
Htg Only
Htg Only
Htg Only
Student Services Boilers
PAGE 7
SCE Job Number 1282
PORTABLE BUILDING OVERVIEW
Approximately fifty (50) portable buildings are located on the Santa Barbara City College. These units serve mostly as
classrooms, although some serve as offices.
College Map: Portable Buildings Highlighted
Existing Systems: The electrical demand for the portable units is the result of a variety of electrical loads within the
building. These systems are noted as having potential for Demand Reduction.
HVAC Overview: The portables at the Santa Barbara City College are conditioned by wall mounted packaged heat
pumps that are 5 tons or less of cooling. These units are operated via indoor thermostats. None of the portable
packaged heat pumps can be accessed by the college JCI system.
Lighting Systems: Interior lighting for portable buildings is provided primarily by 4’, 2-lamp T8 fluorescent fixtures. Refer
to Appendix C for a detailed lighting schedule by area.
Lighting Control Systems: The portable buildings are not typically equipped with occupancy sensors. The portable
buildings contain bi-level switching capabilities in applicable areas to comply with Title 24 Energy Standards. Lighting in
portable buildings were noted to typically be off when area was unoccupied.
Process Loads ~ The portable buildings contains the following high energy process loads:
▪
Portable buildings serving as classrooms are equipped with overhead projectors.
▪
Some portable buildings have several desktop computers.
Portable Unit Package Heat Pumps
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
Portable Unit Interior
PAGE 8
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 1 : Chilled Water Supply Temperature Reset
Chillers operate more efficiently at higher chilled water temperatures. Raising the chilled water supply temperature by 4ºF
(44ºF to 48ºF) for all buildings served by a chiller plant during a demand response period is recommended.
Projected Peak Demand Savings:
Average Demand Reduction = 14.2 kW (0.9% of facility peak)
Estimated Average Savings* = $61 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
Building control system programming is required to automate this measure.
▪ Estimated Controls and Control and Programming Cost: $17,000
▪ Available Incentive Amount: 14.2 kW x $300/kW = $4,260 (Fully Automated)
Student Services Chiller Plant
* Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 9
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 2: Space Temperature Reset 72°F to 76°F
Buildings consume less space cooling energy the closer their indoor temperature control setpoints are to outside ambient
conditions. Raising the space temperature set point by 4ºF (72ºF to 76ºF) for all areas within the building that can tolerate
higher temperatures during peak demand periods is recommended. These include conditoned lobbies, offices,
classrooms, and all other non-laboratory and non-data center occupancies. Sensitivie laboratory and data center areas
were not included in calculating the savings of this measure.
Projected Peak Demand Savings:
Average Demand Reduction = 340.9 kW (20.5% of facility peak)
Estimated Average Savings* = $1,456 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
Additional DDC programming is required to automate this measure. Including DDC control of portable buildings is
also required. The addition of a global setpoint adjustment control strategy is recommended.
▪ Estimated Portable Controls Cost: $62,500
▪ Estimated Control and Programming Cost: $10,000
▪ Available Incentive Amount: 340.9 kW x $300/kW = $102,270 (Fully Automated)
Typical Campus Facility Wall Thermostat
* Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 10
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 3: Data Center Temperature Reset 70°F to 78°F
The Santa Barbara City College campus contains server rooms that is kept at approximately 70ºF. The ASHRAE 2008
Environmental Guidelines for Datacomm Equipment recommends data centers operate between 64.4ºF and 80.6ºF.
Raising the space temperature of the rooms will decrease the cooling load required from the fan coil system serving the
space. It is recommended to raise the server room temperature set points by 8ºF (70ºF to 78ºF) during a demand
response period.
Projected Peak Demand Savings:
Average Demand Reduction = 2.4 kW (0.1% of facility peak)
Estimated Average Savings* = $10 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
Additional DDC programming is required to automate this measure. The addition of a global setpoint adjustment
control strategy is recommended.
▪ Estimated Control and Programming Cost: $4,000
▪ Available Incentive Amount: 2.4 kW x $300/kW = $720 (Fully Automated)
Data Center AHU Thermostat Controller
* Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 11
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 4 : Heating Hot Water Pump Shutdown
Heating hot water (HHW) is supplied to the air handling units on campus by approximately fifteen (15) alternating hp
pumps, several of which are alternating. Demand response events historically occur on the hottest summer days when
heating is not needed for space temperature or humidity control. Shutdown of all non-critical HHW pumps during a
demand response period is recommended.
Projected Peak Demand Savings:
Average Demand Reduction = 9.2 kW (0.6% of facility peak)
Estimated Average Savings* = $39 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
Additional building control system programming is required to automate this measure.
▪ Estimated Control and Programming Cost: $6,000
▪ Available Incentive Amount: 9.2 kW x $300/kW = $2,760 (Fully Automated)
Typical Campus HHW Pumps
* Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 12
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 5 : Lighting Reduction
Space lighting reduction results in direct peak kW savings and contributes to reduced heat loads and HVAC energy in
conditioned spaces. Depending on the number of fixtures or lamps, a 33% or 50% reduction of lighting in non-classroom
areas is recommended during a demand response. Refer to Appendix C for a detailed lighting reduction schedule by
area.
Projected Peak Demand Savings:
Average Demand Reduction = 113.5 kW (6.8% of facility peak)
Estimated Average Savings* = $485 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
Currently, approximately 85% of the campus has bi-level switching capability. A lighting rewire in the remaining 15%
of the building is required to implement this measure. The implementation of a lighting control system to include
individual control of each lighting circuit to be shutdown is necessary to automate this measure.
▪ Estimated Lighting Rewire Cost: $11,000
▪ Estimated Lighting Control System Cost: $40,000
▪ Available Incentive Amount: 113.5 kW x $300/kW = $34,050 (Fully Automated)
Typical Campus Indoor Lighting
* Average Savings per event is based on a standard SCE Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 13
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 6 : Fountain Pump Shutdown
There are two (2) outdoor water fountains located on the campus. One (1) pump serves a water feature on the West
Campus, and one (1) pump serves a water fountain on the East Campus. Each fountain is served by a continuously
operating pump. Shutdown of the two (2) fountain pumps during a demand response event is recommended.
Projected Peak Demand Savings:
Average Demand Reduction = 3.2 kW (0.2% of facility peak)
Estimated Average Savings* = $13 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
The addition of on/off control of the fountain pumps through the building's DDC system is recommended.
▪ Estimated Control and Programming Cost: $4,000
▪ Available Incentive Amount: 3.2 kW x $300/kW = $960 (Fully Automated)
West Campus Water Feature
* Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 14
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 7 : Pre-Cool Refrigeration Spaces
Many of the dining facilities at the Santa Barbara City College contain walk-in freezers and walk-in refrigerators with
remote compressors. The allowable temperatures within the freezers and refrigerators are 0°F to 17°F and 35°F to
41°F, respectively. The following strategy is recommended during a demand response event:
▪ Pre-cool freezers and refrigerators to the minimum allowed temperature prior to a demand response event.
▪ Reset the freezers/refrigerators to their maximum allowable setpoints and let them float while the compressors idle.
Projected Peak Demand Savings:
Average Demand Reduction = 2.8 kW (0.2% of facility peak)
Estimated Average Savings* = $12 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
The connection of the refrigerators/freezers temperature control system to the proposed DDC network is
recommended to automate this measure.
▪ Estimated Control and Programming Cost: $20,000
▪ Available Incentive Amount: 2.8 kW x $300/kW = $840 (Fully Automated)
Typical Campus Walk-In Condenser Unit
* Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 15
SCE Job Number 1282
TECHNICAL ANALYSIS
Demand Response Measure # 8 : Beverage Vending Machine Compressor Shutdown
There are multiple outdoor vending machines located throughout the campus, as well as several indoor vending
machines/refrigerators at the main dining areas. Approximately thirty (30) total vending machines/refrigerators are located
throughout the campus. The vending machine compressor runs continuously to maintain a cool temperature for the
beverages. Shutdown of all vending machine compressors during a demand response period is recommended.
Projected Peak Demand Savings:
Average Demand Reduction = 11.1 kW (0.7% of facility peak)
Estimated Average Savings* = $47 per event
Refer to Appendix C for Calculations.
System Modification Requirements and Automation Opportunities:
The addition of on/off control for the vending machines through the existing DDC system is recommended to
automate this measure.
▪ Estimated Controls Cost: $15,000
▪ Available Incentive Amount: 11.1 kW x $300/kW = $3,330 (Fully Automated)
Typical Campus Outdoor Vending Machines
* Average Savings per event is based on a standard SDG&E Critical Peak Pricing (CPP) utility rate and a 4 hour (2PM to 6PM)
measure implementation period.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 16
SCE Job Number 1282
ENERGY EFFICIENCY OPPORTUNITIES
During the course of our investigation we observed several conditions that warrant additional analysis. In some cases,
these items have potential for additional kW reduction; while in other cases, they have potential for energy
conservation. Although these items are outside the scope of the SDG&E TA/TI Technical Incentive Program, they have
significant potential for improving the efficiency of the facility and can assist in electrical demand reduction. Further
investigation is required to determine potential energy savings. Energy Efficiency Measures identified for Santa
Barbara City College are summarized as follows:
HVAC Opportunities
EE Meas #1: Chiller VFD Installation and Sequencing Optimization:
Currently, the speed of the chillers cannot modulate depending on the
electrical demand load due to the lack of variable frequency drives.
Variable speed chillers often operate more efficiently together at part load
conditions than alone at full speed. Additionally, variable speed chillers
experience significant increases in efficiency as their CHWS temperature
increases. An investigation to determine the cost and payback of
installing a chiller VFD to optimize chiller operation and set point control is
recommended.
EE Meas #2: CHW Supply Temperature Reset:
The Santa Barbara City College is located in a climate that often has cool
and hot temperatures, even within the same day. By raising the supply
temperature of chilled water, chillers use less energy to chill the water
when the cooling load is below its designed value. Additionally, chillers
operate more efficiently at higher chilled water temperatures. It is
recommended that the feasibility of implementing a chilled water supply
reset is further investigated.
EE Meas #3: Boiler Outside Air Reset and Lockout:
Heating hot water (HHW) is supplied to the air handling units on campus
by multiple boilers and associated pumps. Due to the intermittent climate
of the college, energy can be saved by shutting down HHW systems
when the outside air temperatures are high or when a specific building
becomes unoccupied. Further investigation of the feasibility of
implementing a HHW boiler outside air reset and lockout is
EE Meas #4: Convert CAV AHU's to VAV Systems:
Currently, select buildings at the college are served by CAV AHU's which
run continously throughout the day regardless of the airflow needed to
satisfy the heat loads. Variable air volume systems are able to save
energy by reducing airflow during part-load conditions to the minimum
amount required to maintain space temperatures. Converting the AHU's
in each building to variable air volume systems is recommended.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 17
SCE Job Number 1282
ENERGY EFFICIENCY MEASURES OPPORTUNITIES
HVAC Opportunities
EE Meas #5: AHU Economizer Repair:
On cooler days, the economizers save energy by modulating to the open
position for "free cooling". On warmer days, the economizers modulate to
the minimum outside air intake position, saving energy by cooling the
least amount of outside air required. Further investigation to locate and
repair economizers and related controls is recommended for energy
savings.
EE Meas #6: Fluorescent Lighting Upgrade:
Interior lighting in buildings on the campus is provided primarily by 32W
T8 fluorescent fixtures. Currently 25W T8 lamps produce only slightly
less usable light while consuming approximately 22% less energy. An
upgrade of all 32W T8 lamps to 25W T8 lamps would result in energy
savings.
EE Meas #7: Upgrade Tint on Windows:
Exterior windows of select building are mostly tinted with outdated film.
Some relatively new portables have film that is still effective. Windows
with new film that reflects solar radiation can drastically reduce a
buildings cooling needs and increase occupant comfort. Further
investigation of the cost and payback of upgrading the window tint is
recommended for the college.
EE Meas #8: Parking Structure Lighting Replacement and Controls:
The parking structure and parking lots are currently provided lighting by
high intensity discharge (HID) lighting fixtures. Bi-level induction and LED
fixtures equipped with occupancy sensors are more efficient and partially
reduce power during unoccupied times while still providing minimum
lighting requirements. The upgrade of all parking lights and the
installation of bi-level controls is recommended.
EE Meas #9: Vending Machine Occupancy Controls
Cold beverage vending machines consume power 24 hours a day to keep
items a certain temperature and to operate electronics and lights.
Specialized vending machine controllers with occupancy sensors are
available that automatically reduce vending machine energy consumption
during periods of low use. By monitoring the product temperature, room
temperature, and activity level, these devices can save up to 50% on
consumption.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 18
SCE Job Number 1282
ENERGY EFFICIENCY MEASURES OPPORTUNITIES
HVAC Opportunities
EE Meas #10: Walk-In Cooler Evaporator Controllers:
The air in the walk-in coolers in the kitchen is cooled by forced-circulation
evaporators containing propeller fans. These fans typically run
continuously despite cooling requirements of the space. Controllers can
be installed to slow these fans when full-speed operation is unnecessary
and lead to 10% to 60% fan energy reduction.
EE Meas #11: Computer Power Management:
Many computers and monitors are left on throughout the day and night,
even though the computers are used infrequently. Applying a power
reduction schedule to these computers and monitors would significantly
reduce energy use. Under this program, monitors switch to low power
mode after 15 minutes of inactivity. This program is recommended for
computers located in areas with set occupancies, such as offices,
conference rooms, and computer classrooms.
EE Meas #12: Variable Speed Kitchen Exhaust Hood Fan Controller:
Santa Barbara City College contains a kitchens with associated kitchen
hoods. These hoods are typically operating during times when the
kitchen is occupied. Through advanced heat and smoke monitoring,
retrofit VFD kits are now available for kitchen hoods which can reduce
airflow by as much as 30% during idle periods when cooking surfaces are
not being activated.
EE Meas #13: Window/Door HVAC Interlock for Classrooms:
Windows and doors of some exterior zones at the college were found to
be open. The heating and cooling energy of HVAC equipment can be
compromised by letting in outside air to conditioned rooms. Installing
sensors on exterior doors and windows that shut off HVAC equipment
serving that room when open are available. Further investigation of the
cost and payback of installing window/door HVAC sensors is
recommended for the college.
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 19
SCE Job Number 1282
Conclusion
Demand Response Measures Summary:
During the course of our investigation, a total of eight (8) demand response measures were identified. The proposed
average on-peak reduction in kW demand based on the demand response measures addressed in this Technical Audit
Report accounts for 30% of existing facility peak demand. A summary of the savings and incentives is shown below.
Demand Response Measure Summary
Total Average
On-Peak Reduction
Estimated Average
Savings (per event)
Incentive for SemiAutomated DR
Implementation
Incentive for Fully
Automated DR
Implementation
497 kW
$2,123
$62,125
$149,100
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021 JM
© 2013 SC ENGINEERS, INC.
PAGE 20
SCE Job Number 1282
APPENDIX
APPENDIX "A" - Equipment Lists
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021
© 2013 SC ENGINEERS, INC.
"A"
Santa Barbara City College Equipment List
Description
Serves
Model
Capacity
Two (2) Trane Chillers
(2) CHW Pumps
Boiler Raypak
Air Handler # I
Air Handler It 2.
Air Handler # 3
Trane heat pump # 1
Trane heat pump # 2
Trane heat pump # 3
Pomona Air unit # 1
Pomona Air unit # 2
Boiler
Learning Resource Center
Learning Resource Center
Learning Resource Center
Library 1st floor
Library 2nd floor
Learning Resource Center
Tutor area of LRC
Math lab
Kia lab
LRC
LRC
LRC
M # H163ACCCRRCBA
Model # 39ED36
Model It 39ED36
Model # 39ED36
m # WCH180B400EA
m # WCH060C400BC
m # WCH060C400BC
m # SACC3004404E6
m # SACC300U404E16
m # H1631ACCCRRCBA
15/7.5 Hp
20/10 Hp
15/7.5 Hp
180,000 btu
60,000 btu
60,000 btu
1.5 Hp
1.5 Hp
1.5 Hp
Exhaust fans # 1
Exhaust fans # 2
Exhaust fans # 3
Exhaust fans # 4
Exhaust fans # 5
Exhaust fans # 6
Heat Pump PAC
Heat Pump PAC
LRC
LRC
LRC
LRC
LRC
LRC
roof LRC
Math lab
Kia Lab
Rm #001
LRC 2nd Level
LRC
LRC Roof
LRC Roof
model # GB214
model # GB14-4
model # GB94
model # GB84
model # GB305
model # GB21-5
WCH180B400EA
WCH060C400BC
WCH060C400BC
SACC 3004 404 E6
SACC 300U 404 E16
# 1510 Pump
GB214
GB-14-4
hp 1/4
hp 1/4
hp 1/4
hp 1/4
hp 1/4
hp 1/4
hp 3
hp 3/4
hp 3/4
hp 3/4
hp 3/4
hp 1 1/2
hp 1/4
hp 1/4
AC Split Indoor Blower #1
AC Split Indoor Blower #2
Hot Water Pump for Heat
EF #1
EF #2
120 Tons
5 Hp /Each
EF #3
EF #4
EF #5
EF #6
FC
FC
FC
FC
Rooftop AH 1
AH 2
Chiller
Hot Water Boiler + Pump + Motor
EF #1
EF #2
Air Compressor
Trane Chiller
Cold Water Pump
AH #1 La Salle
AH #2 La Salle
EF
Pump
Pump
AH #1
CFU #1
AH #2
AH # 3
AH #4
AH #5
AH #6
AH #7
AH #8
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
Fan Coil
LRC Roof
LRC Roof
LRC Roof
LRC Roof
IDC #313
IDC #329
IDC #317
IDC #325
all of bldg IDC
IDC Roof
IDC bldg
Roof
Roof bathrooms
Exhaust
IDC Lite Storage
IDC Lite Storage
CHW
IDC
IDC
Hallway (all 3 flrs)
Rm #235
GB94
GB84
GB 30 5
GB 21 5
Trane
Trane
Trane
Trane
LLRT-600
LLRT-600
CGADC259ABAIGHRTY
H1414ACCCHCBX
N/A
SX 205B
CIS075603
CGADC254ABAIGHRTY
B&G
LLRT-600
LLRT-600
BL Chiller
West Side BLC Bldg Lunch 3?
Snack Bar
BC Forum & 237
301
302
Hallway
315
314
313
115 Office
116 Office
117 Office
109
108
106
105
101
214
203 Copy Room Lounge
215-219
30GN 060 600KA
39LF1061CA1129L
CAB-4
39LF1101CA1134L
39LC1031CA1124-R
39LC1061CA1124-I
39LG1031DA1121-R
39LC1061CA1124L
39LC1061CA1124R
39LC106CA1124R
42CEAO3DRCY5AYYYYG
42CEAO3DRCY5AYYYYG
42CEAO3DRCY5AYYYYG
42CEAO3DRCY5AYYYYG
42CEAO3DRCY5AYYYYG
42CEAO3DRY5AYYYYG
42CEAO3DRCY5AYYYYG
42BHB12KD4L61010CAQ
42BHB08KC3R60710BAQ
42BHB12KD4R61110CAQ
42BHB12KD4R61110CAQ
805QIZD
hp 1/4
hp 1/4
hp 1/2
hp 1/4
10.5 MBH, 1/15 Hp
10.5 MBH, 1/15 Hp
10.5 MBH, 1/15 Hp
10.5 MBH, 1/15 Hp
hp 7.5
hp 5
hp 1
hp 2
hp 3/4
hp 2
hp 3/4
25 Tons
hp 1
hp 7.5 & hp 5
hp 5 & hp 2
hp 3/4
hp 1/6?
hp 1/2
hp 1 1/2
hp 3
hp 5
hp 3/4
hp 1
hp 3/4
hp 1
hp 1
hp 1
hp 1/30
hp 1/30
hp 1/30
hp 1/30
hp 1/30
hp 1/30
hp 1/30
hp 1/2
hp 1/3
hp 1/2
hp 1/2
Fan Coil
Fan Coil
Fan Coil
Fan Coil
HW Fan Coil
Fan Coil
Fan Coil #17
Fan Coil
Fan Coil HW,CW
Fan Coil
Fan Coil
CHWP (2)
HWP
EF
EF
EF
Ht Pump Split
OSA Fan Motor
Heat Furnace
Heat or Package
Gas Electric Package
229
222
226
228
BL second flr
230
Hallway 2nd flr
141
237
224 Entry Lobby Area
104 Common Area
144
232
2nd flr mens + womens restroom
Kitchen
114 electric room
312
112 phone room
Child Center
Child Center
Children Center
42BHB08KCR360710BAQ
42BHB12KDR61110CAQ
42BHB08KC3R60710BAQ
42BHB0BKC3L6060BAQ
42BHB08K
42BHB08KC3L60808BAQ
42BHB08KC3R6060
42CEAO3DRCY5AYYYYG
42BHBIZKD4R61011CAQ
42BHBIZKD4L61011CAQ
42BHB16KD4R61514DAG
KM378JM
C535A
120 5QIB
FC-120
485X-042080521AA
East Side
AH #1
AH #2
Boiler
Fan Coil Split HP
Fan Coil Split HP system
Fan coil/Ht Pump
Fan Coil #4
FC/HP #6
FC/HP #7
ADM Boiler Rm
ADM Boiler Rm
ADM Boiler Rm
123-124 Conference Room
130, A,B,C 123A
130 E,D
141
200 H,J,K, AA + Corridor N. part of offices
201 train room
MCCAOZIUBOA
MCCAOZIUBOO
MCCAOZIUBOO
FB4ANF024
NZAHD14A06C
NZAHD16A06C
NZAHD16A06C
FC4BNF030
FC4BNF030
MUH09EW
805015D
hp 1/3
hp 1/2
hp 1/3
hp 1/3
hp 1/3
hp 1/3
hp 1/3
hp 1/30
hp 1/2
hp 1/2
hp 3/4
hp 5
hp 3
hp 1/3
hp 3
hp 1
hp 1/6
hp 1/4
hp 1/4
7.5/3 Hp
10/3 Hp
2 ton
3 ton
3 1/2 tons
hp 1/2, 4 ton
hp 1/3
FC/HP
Fan Coil Heat Pump Split
HP-FC #5
DX-FC-7 (split Ht pump)
A211
Return Fan A211
McQuay AH Unit 4 Pipe
McQuay AH Unit 4 Pipe
Hot + Cold Water Pumps
Hot Water Boiler
McQuay Chiller 4 stage
EF
EF
EF
EF
EF
EF
EF #5
Upflo Gas + Electric Split
Upflo Split Gas And Electric
Upflo Gas + Electric Split
Upflo Gas + Electric Split
Down flo split
Upflo split furnace
Upflo Split Gas And Electric
EF 1 & 2
Split system heat pump & AH mr sum
Furnace 1
Furnace 2,3,4,7
Furnace 5
Furnace 6
Condensing Unit 2,3,4,5,7
Condensing Unit 6
do pg 50
Heat Pump #1
Heat Pump 2,4
Heat Pump 3
Fan Coil #1,2,4
Fan Coil #3
Condensate Pump #1-4
ACU #1
EF #1
EF #2
200 A,AA,B,C,D,E,F,G
210J Offices IT Tech
A 210 D,E,F,G,H,I Tech offices
A 210 A,B,K
3rd flr adm bldg
Roof ADM
1st flr adm digital arts
2nd flr adm nurses flr
A211 McQuay 1 & 2
A211 McQuays
A211 1st 2nd flr S.E. wing
A Bldg Rm 200-2001
Mkens + Womens Restroom
236, 242
223
217
A210 A + B
Lower Flr Storage Work RM
Lower Lvl area in front of stairs
Main flr by atm
Main flr clothes and dressing room area
Lower lvl bathroom + front of same flr
Acct offices
Left side of main flr
roof book store
Apple computer Rm store
Campus Center 2nd flr
Campus Center 2nd flr
Campus Center 2nd flr
FC4BNF048
FC4BNF030
GHC048SA
WZAHDI0A06C
HV ARRI
ZOO CVB
ROS00CLY
H3 1083
AGZ090B5527
U9054
FG1210
FG1209
FG1013
FC111
58GSC045-GB
5GSC080-LB
58GSC080-LB
58GSC080-LB
58DHC075-JC
58GSC045-GB
58GSC080-LB
LB-145
PUH36EK & PLH36FK
P4USD
P4USD
PICC-D
P4USD
HICP060
HICF036
EIFH018
EIFH024
EIFH030
NIFAD10
NIFAD10
VGM-15ULS
48 MA 030 NAT
GB-130
BSQ-90
hp 3/4
hp 1/3
4 ton, hp 3/4
2 ton, hp 1/3
7.5 Hp
3 Hp
hp 20
hp 15
hp 1.5
1,000 BTUH In, 880 BTUH Out
hp 1/2
hp 1/2
hp 1/3
hp 1/6
hp 1/12
hp 1/12
hp 1/3
hp 1/10
5 ton, hp 1/4
5 ton, hp 1/4
5 ton, hp 1/4
5 ton, hp 1/4
3 ton, hp 1/4
5 ton, hp 1/4
hp 1/4
47 MBH Out, 57 MBH In
90 MBH In, 73 MBH Out
90 MBH In, 73 MBH Out
47 MBH Out, 57 MBH In
60 MBH
36 MBH
19 mbh tot,14.9 MBH sens, 17.8 mb
23 mbh tot,17.9 mbh sens, 20.4 mb
29 mbh tot,22.4 mbh sens,24.6 mbh
hp 1/3
hp 1/3
hp 1/50
540000 btu Heat in, 405000 btu hea
hp 1/4
hp 1/3
EF #3
E #1
E#2
E#3
E#4
E#5
E#6
Steam boiler
trane air handler
In Line duct furnaces (2)
MUA #1
MUA #2
EF
Split System Ht pump
Condensor heat pump
Split System ht pump
Split System ht pump
Condensor heat pump
Split System ht pump
Condensor heat pump
Make up air blower fan
Split Heat Pump
Roof gas electric pac
Roof top pac multi zone
Exh Up Blast Fan
MUAU
Gas Heat pac roof top
EF
EF-1
EF #2
Make Up Air WC/ duct heater
Campus Center 2nd flr
kitchen make up
Range hood
Toilet exhaust
Toilet exhaust
Refrigeration
Dishwasher hood
steam tables + dishwasher
Cafeteria
Cafeteria
108
Mech room
C.C. Bldg,116-121 HRC offices
116-121 HRC offices
122
124
Cafeteria + kitchen
HVAC for kitchen food line
Cyber Center
Campus center offices
kitchen
kitchen
Coffee & gourmet shop
Snack shack
kitchen
kitchen
kitchen
BSQ-100
397
397
S-1507
AMER BLW S150D2
S-1507
15L
MCCA02SHCCOOAAOAAOO
HX400 8S MVE
RM3517
YQN56C17D2072F
BSQ-140QD
FISA036R06A
EIFH030506A
EFISA030R06A
FISA036R06A
EFH030506A
FISA030R06A
EIFH024506A
hp 1/4
hp 1
hp 1 1/2
hp 1/4
hp 1/4
hp 1/2
hp 1/2
645000/322500 btu?
hp 7.5
400000/320000 btu?
hp 2
hp 1/2
hp 1/2
2 1/2 tons
hp 1/4, 2 1/2 tons
2 ton, hp 1/3
2 1/2 tons, hp 1/3
2 1/2 tons, hp 1/4
2 ton, hp 1/3
hp 1/4, 2 tons
5K213AG801 (and 307?)
TTA090A300FA
YCH120A3RL
48MA 030
330VCR
ED1430
E3MPV15A1
CUBE 240 LMDG-QD
LO3603
330LBB
4OOL
hp 1
2 (ton?)
10 tons cool, 150000 & 120000 (btu?)
540000 & 405000 (btu?), hp 10
hp 2
hp 1.5
150000/120000 (btu?), hp 3
hp 1 1/2
hp 2
hp 1 1/2
400000/300000 (btu?), hp 2
Make Up Air/duct heater
McQuay Chiller
CWP Chiller
Boiler LAARS
Sup AH & Return AH
AH #2 Sup fan and EF #3
AH #3 Sup fan & EF #4
AHU #4 & #5, McQuay
AH #4 & 5
VAVU
Fan coils (11)
AH #1
AH#2
AH #3
FC/HP
FC/HP
FC/HP
Boiler 1
Boiler 2
Chiller 1
CWP Chiller
Lochinvar Boiler
AH #1 Sup & Ret fan motors
AH #2 Sup & Ret fan motors
AH #3 Sup & Ret fan motors
Chiller H Bldg
HVAC boiler
Hot Water Coil AH
Cold, hot water coils AH
Cold, hot water coils AH
Hot water Boiler for 3rd flr fan coils
Fan Coil CW & HW
Fan Coil CH/HW
Fan Coil CW/HW #3
Down flo Chiller Coil
EF
Dust Collector
Dust Collector
EF #2
EF #3 & 4
EF #5
EF #6
EF #7
kitchen
Earth biology sciences mechanical
Earth biology sciences mechanical
Earth biology sciences mechanical
Mech room 1st flr
mech room 2nd flr
mech room 3rd flr
EBS Rm 309/301
Varies
Varies
EBS 3rd flr offices
Humanities Bldg, 1st and 2nd flrs
Humanities Bldg, 1st and 2nd flrs
3rd flr
334
335
336
AH #1,2,3
FC/HP #1,2,3
AH #1,2,3, FC/HP #1,2,3, FC2P
Humanities
HWP?
1st and 2nd flrs
1st and 2nd flrs
1st and 2nd flrs
H bldg mech rm
1st flr
2nd flr
3rd flr
3rd flr ESC labs
small room
Big lab
Big lab
H 245
Electric Rm 1st flr
107 ceramics
107 ceramics
TV room
Exhaust System
Exhaust System
Exhaust System
Exhaust System
4OOL
ALS141CS27
PH1430EN21KNABXX
FBOUO106000402
FBOUO106000402
CHO14FDAC
RDS708BY
Varies
FALWSD
Varies
Fujitsu AOU36CLX
American Standard
American Standard
Teledyne Laars
Lochnivar
Trane RTAA1254VT01AB000B
B079A
CHN2071
41
41
RTAA 1254, YT01 AB00B
CHN2071
41
41
143495
60 BHW 4A2M
60 BHW 4ALM
60 BHW 4ALM
DACD 1132
1800
1200
FS-222
FG-1807
FG-2405
FG-1807
FG-1807
400000/300000 (btu?), hp 2
hp 1 1/2, 141 ton (2 skrew)
10 hp
hp 3, 1430000-1172000
hp 15 & hp 5
hp 15 & hp 3
hp 7 1/2 & ?
hp 3
Varies
Varies
Varies
5 Hp
5 Hp
5 Hp
2.5 Tons
2.5 Tons
2.5 Tons
266 kBTU
266 kBTU
125 Tons
hp 7.5
hp 2
hp 20, hp 5
hp 30, hp 5
hp 30, hp 5
hp 7 1/2, 125 tons
hp 2
hp 20
hp 30
hp 30
266000 btu, hp 1/2
hp 3
hp 3
hp 3
hp 3
hp 1/2
hp 1/2
hp 1/6
hp 1/2
hp 1/4
hp 1/3
hp 1/4
hp 1/4
EF #8
AC
AD
Furnace #1
Furnace #2
Furnace #3
UH 2-5
UH 1,6-9
EF
EF 2,3
EF
EF
Up flo gas furnace
Up Flo Gas furnace
Up flo gas furnace
Liquid chiller
AH #1
EF #1
AH #2
AH #3
AH #4
MZAH
hot water AH on roof
Horizontal AH, HW, CW coil
Exhaust System
marine tech
marine tech
marine tech
marine tech
marine tech
marine tech
marine tech
marine tech, main flr
bathroom
OE
202
offices 203
OE
OE bldg, transmission and engine shop
OE bldg, transmission and engine shop
bathrooms and storage
digital photo studio
media services
drafting rooms 112/116 & 182
182, auto lab, trans shop, offices
print shop
Horizontal AH, HW, CW
EF
EF 2
EF 3
EF 4
EF 5
EF 6
auto lab
Weld shop
Weld shop
Weld shop
Weld shop
Weld shop
FG-1507
SYCT8-1
F-30
G81-165V
G81-65-82V
G81-65-82V
JS2-3
JS3-3
G81-165V-2
G81-6582V-3
G81-6582V-3
30GA-020-530-3
Trane
hp 1/6?
hp 3/4
hp 1/2
165000 btu in, 132000 btu out, hp 3/4
65000 btu in, 52000 btu out,hp 1/3
65000 btu in, 52000 btu out,hp 1/3
24000 btuh
36000 btuh
hp 1/4
hp 1/4
hp 1/3
hp 1/4
165000 btu in, 137000 btu out, hp 1
82000/65000 btu, hp 1/3
82000/65000 btu, hp 1/3
5/3 Hp
Trane
Trane
Trane
Trane
IJ8224
RDS708BY
10 Hp
Trane
hp 5
hp 1
hp 1/4
hp 1/4
hp 1/4
hp 1/4
hp 1/2
4L220
4L220
4L220
3L220
3L350
hp 3/4
hp 10
EF 7
EF 8
EF 9
EF 10
EF 11
boiler-1
AH #1
AH #2
AH #3
Chiller #1
Chiller #2
Boiler 1
Cool motors
hot water motors
EF 1 & 2
EF 3 & 4
EF 5
SANYO split A/C
Weld shop
Weld shop
Weld shop
Weld shop
Weld shop
HWUH,HWHC
SSB, 1st and 2nd flr south side
1st and 2nd flr south side
2nd flr middle
AH 1/2/3
AH 1/2/3
AH 1/2/3
mens + womens 2nd flr
mens + womens front bldg
mens + womens restroom
phone + computer Rm
3L340
3L350
3L340
3L340
3L350
WGB-1250
Trane
Trane
Trane
Trane
Trane
CHN1441
Z-1/2BB 8-3/4BF
ZAC 6-3/8BF
CL1211
hp 1/2
hp 1/2
hp 1/2
hp 1/2
hp 1/2
1250 mbh in, 1000 mbh out
15/5 Hp
15/5 Hp
7.5 Hp
40 Tons
40 Tons
144000 btu, 120860 btu
hp 7.5
hp 1 1/2
hp 1/2
hp 1/4
hp 1/2
12000 btu
APPENDIX
APPENDIX "B" - SCE Technical Analysis Forms
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021
© 2013 SC ENGINEERS, INC.
"B"
2012
Technical Assistance (TA)
Technical Audit Report
ABOUT THE TECHNICAL AUDIT REPORT
Technical
Audit
Report
(Form#2B)
#2B)
Technical
Audit
Report
(Form
This template is used to conduct a Demand Response Technical Audit for Southern California Edison’s (SCE) Technical Assistance
(TA) Program. Unless specifically requested by SCE, Technical Audits should not be
performed on additional service accounts. The Technical Audit Report can be
General
General Site
SiteInformation
Informationand
andExecutive
ExecutiveSummary
Summary
completed by doing the following:
Provide
Provide site
sitespecific
specificinformation
informationforforallallsites
sites
• Complete the Customer & Engineer Certification form during the site visit.
that received the technical audit.
that received the technical audit.
(Customer signature required)
•
Complete the Technical Audit Report (Form #2B). Complete each of the
Demand Response Solution Recommendations
Demand
Response
Solution
following sections:
(The 2B
Report allows
up Recommendations
to 5 solutions)
(The 2BProvide
Reportdetails
allows
up to 5the
solutions)
regarding
o Engineer Information
recommendation.
Provide
details regarding the
o Technical Audit Summary
recommendation.
o General Site Information and Executive Summary
o Demand Response Solution Recommendations
Solution # - Site # (Repeats to 5 sites per solution)
o
Solution – Site
Which sites are Solution
applicable# to- Site
the aforementioned
#
recommendation? Provide details on how the
Whichrecommendation
sites are applicable
to the aforementioned
applies to each site.
recommendation? Provide details on how the
recommendation applies to each site.
DO NOT PROVIDE THE TECHNICAL AUDIT REPORT TO THE CUSTOMER.
SCE requires the audit be reviewed by the program verification engineer (PVE) prior
to the SCE customer seeing the Solution Recommendations. Email the electric copy
of this document and a scanned copy of the Customer & Engineer Certification form
with the customer’s signature to AUTODR@sce.com.
Note: This form is designed to identify a maximum of 5 solutions for 1 service account. If you exceed the space provided, please
continue on an additional Form #2B.
ENGINEER INFORMATION
Engineering Firm Name
SC Engineers, Inc.
Engineer Name
Frank Shadpour
Mailing Address
17075 Via Del Campo, First Floor
Mailing State
CA
Mailing
City
E-Mail
San Diego
administration@scengineers.n
et
Office Phone
858.946.0333
PE License #
M23923
Mailing Zip
92127
Mobile Phone
AUTO-DR TECHNICAL AUDIT SUMMARY
Customer
Name
Santa Barbara City College
SA#
Site #
Site Address
Site City
000203611
1
721 Cliff Dr.
Santa
Barbara
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
2B Cost
Portfolio (Project)
ID#
1282-1930
# Hours
for 2B
# of
Measures
Total Avg.
kW
8
497
Date(s) of
2B
Page 1 of 15
2012
Technical Assistance (TA)
Technical Audit Report
Appendix Info (The TA and Auto-DR Technology Incentive Programs will not provide technology incentives for manual improvements to
existing equipment, for load reduction enabled by the Customer’s behavior changes, or metering equipment):
Site 1
Service Account #
000203611
Occupancy
Operations
Schedule
EMS
Industrial Controls
GENERAL SITE INFORMATION
Facility Type
Campus
7am - 8pm
AC Sq Ft
615,000
Occupancy %:
No AC Sq Ft
Total Sq Ft
615,000
90%
The equipment operates primarily from 7:00am-8:00pm.
The HVAC equipment for the main buildings at the Santa Barbara City College are
controlled and monitored by a Johnson Controls (JCI) DDC system.
The JCI system can be accessed through computers located in the Facilities & Operations
building. The JCI system controls the majority of major HVAC equipment on campus:
chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC
equipment through the JCI system and timeclocks. Facility staff noted that they monitor
buildings and adjust schedules as needed. Some chillers at the college are programmed
with a chiller wated reset.
IT Infrastructure
The system can not be accessed remotely due to strict campus internt security.
DRAS Interface
Currently non-existent. Recommend interfacing with a Niagra AX JACE equipment with
operating ADR equipment driver.
Other
Considerations
PV panels shade a parking lot on the West Campus.
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 2 of 15
2012
Technical Assistance (TA)
Technical Audit Report
Site 1
Interview Summary
Site Summary
Energy System
Summary
EXECUTIVE SUMMARY
A field investigation or the Santa Barbara City College was conducted on the days of 3rd
of December, 2012, through 5th of December, 2012. Attendees included James
McKechnie of SC Engineers and Julie Hendricks and Brad Gyll of Santa Barbara City
College. HVAC, lighting, and process loads were indicated as most likely targets for
demand response reduction.
The Santa Barbara City College consists of approximately twenty (20) buildings consisting
of approximately 550,000 sq. ft., approximately fifty (50) portable units consisting of
approximately 62,500 sq. ft., a parking structure, several parking lots, and sporting fields.
The campus is heavily occupied from 7:00am - 8:00pm as it hosts several evening classes
in addition to a typical school day schedule. The majority of rooms consist of class/lecture
and office occupancies. Other notable areas are the gymnasium located in the Physical
Education building and the performance stages located in the Drama and Music building.
These areas may hold additional events not associated directly with the college.
HVAC ~ Control System: The HVAC equipment for the main buildings at the Santa
Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC
system. This system can be accessed through computers located in the Facilities &
Operations building. The system can not be accessed remotely due to strict campus
internet security. The JCI system controls most major HVAC equipment on campus:
chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC
equipment through the JCI system and timeclocks. Facility staff noted that they monitor
buildings and adjust schedules as needed. Some chillers at the college are programmed
with a chiller water reset.
Lighting Systems: Interior lighting for the collegel is provided primarily by 4’, T8
fluorescent fixtures. Some 4', T12 fixtures and high intensity discharge (HID) fixtures
serve areas of the college as well. Approximately 85% of the campus contains bi-level
switching capabilities. Refer to Appendix C for a detailed lighting schedule by area.
Lighting Control Systems: Occupancy sensors were found sporadically throughout offices,
classrooms, and laboratories on the campus. No central lighting control system exists.
Outdoor lighting is controlled by photocells. Security lighting serves the campus and is
scheduled to be on 100% from dusk to midnight, then 50% from midnight to dawn.
Parking structure lights were noted to be on timers.
Process Loads ~ The campus contains the following high energy process loads:
▪
Multiple elevators that serve multi-level buildings
▪
The Business/Communications Building holds a cafeteria with associated
equipment including: several refrigerator units, one (1) walk-in refrigerator, and one (1)
walk-in freezer.
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 3 of 15
2012
Technical Assistance (TA)
Technical Audit Report
▪
The Campus Center/HRC Building holds a dining area on the second floor and two
(2) kitchens on the first floor with associated equipment including: several refrigerator
units, two (2) walk-in refrigerator, and three (3) walk-in freezer.
▪
A water feature on the West Campus.
▪
A water fountain on the East Campus.
▪
Several vending machines located around the college.
HVAC Overview: The portables at the Santa Barbara City College are conditioned by
packaged heat pumps that are 5 tons or less of cooling. These units are operated via indoor
thermostats. None of the portable packaged heat pumps can be accessed by the college JCI
system.
HVAC ~ Chilled Water Systems: The West Campus has three (3) buildings that are served
by a self-contained chiller plant. The East Campus has seven (7) buildings that are served
by a self-contained boiler plant. These boiler plants serve the building's hydronic air
handling units (AHU's) and fan coils.
HVAC ~ Heating Hot Water Systems: The West Campus has three (3) buildings that are
served by a self-contained boiler plant. These boiler plants serve the building's hydronic
air handling units (AHU's) and fan coils. The East Campus has seven (7) buildings that are
served by a self-contained boiler plant. These boiler plants serve the building's hydronic
air handling units (AHU's) and fan coils.
HVAC ~ Air-Side Systems: The buildings with chiller and boiler plants are served by fan
coils, constant air volume (CAV), and variable air volume (VAV) AHU's. The other
buildings are conditioned primarily by direct expansion (DX) units. East Campus
buildings are served by a combination of DX units, hydronic constant air volume (CAV),
and variable air volume (VAV) AHU's.
Auto-DR Summary
DR Measure # 1:
DR Measure # 2:
DR Measure # 3:
DR Measure # 4:
DR Measure # 5:
DR Measure # 6:
DR Measure # 7:
DR Measure # 8:
11.1 kW
HVAC - Chilled Water Supply Temperature Reset - 14.2 kW
HVAC - Space Temperature Reset - 340.9 kW
HVAC - Data Center Temperature Reset - 2.4 kW
HVAC - Heating Hot Water Pump Shutdown - 9.2 kW
Lighting - Lighting Reduction - 113.5 kW
Process Load - Fountain Pump Shutdown - 3.2 kW
Process Load - Pre-Cool Refrigeration Spaces - 2.8 kW
Process Load - Beverage Vending Machine Compressor Shutdown -
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 4 of 15
2012
Technical Assistance (TA)
Technical Audit Report
Additional
Information
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 5 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 1
HEATING, VENTILATION AND AIR CONDITIONING
Response Type
Auto-DR
Strategy
Defined in Strategy Details
Strategy Details
kW Reduction
Calculation
Load Factor
Type and Code:
HVAC System Optimization: DR-82993
Chillers operate more efficiently at higher chilled water temperatures. Raising the chilled water
supply temperature by 4ºF (44ºF to 48ºF) for all buildings served by a chiller plant during a
demand response period is recommended.
The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140
compliant building energy analysis software tool. The baseline energy model is based on actual
building construction, occupancies, schedules, and equipment. It has been calibrated to match
the electrical demand profile of the facility's top 18 days of the previous year within 10%. See
Appendix D for detailed Trace 700 building simulation results.
Trace 700 measures were modeled sequentially with the results of each measure used as the
baseline for the following measure to include interactive effects.
SOLUTION 1 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
15
Max kW
System Location
Buildings: BC, IDC, L/LRC, A,
EBS, H, OE, & SS
Energy Usage System
CHW System, see equipment list
Avg. kW
14
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
13
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
Page 6 of 15
2012
Technical Assistance (TA)
Technical Audit Report
SOLUTION 1 – SITE 1 CONTINUED
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
Cost Description and
Breakdown
Implementation
Analysis/Barriers
CHW supply temperature resets on a permanent basis can be implemented to save
energy. Reset can be based on variables such as outside air, load, time of day, etc.
The 4 hours of the DR event.
▪ Estimated Controls and Control and Programming Cost: $17,000
Building control system programming is required to automate this measure.
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 7 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 2
HEATING, VENTILATION AND AIR CONDITIONING
Response Type
Auto-DR
Strategy
Defined in Strategy Details
Strategy Details
kW Reduction
Calculation
Load Factor
Type and Code
HVAC System Optimization: DR-82993
Raising the space temperature set point by 4ºF (72ºF to 76ºF) for all areas within the building
that can tolerate higher temperatures during peak demand periods is recommended. These
include conditoned lobbies, offices, classrooms, and all other non-laboratory and non-data
center occupancies. Sensitivie laboratory and data center areas were not included in
calculating the savings of this measure.
The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140
compliant building energy analysis software tool. The baseline energy model is based on actual
building construction, occupancies, schedules, and equipment. It has been calibrated to match
the electrical demand profile of the facility's top 18 days of the previous year within 10%. The
simulation results for an increase in the space temperature set point from 72°F to 76°F for the
slected areas are shown below. See Appendix D for detailed building simulation results.
Trace 700 measures were modeled sequentially with the results of each measure used as the
baseline for the following measure to include interactive effects.
SOLUTION 2 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
System Location
Energy Usage System
765
Max kW
All buildings but laboratories and
data centers
Central Cooling System, see
equipment list
340
Avg. kW
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
Varies
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
Page 8 of 15
2012
Technical Assistance (TA)
Technical Audit Report
SOLUTION 2 – SITE 1 CONTINUED
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
Implementing the space temperature reset on a permanent basis can save energy.
The 4 hours of the DR event.
▪
Estimated Portable Controls Cost: $62,500
Cost Description and
Breakdown
▪
Estimated Control and Programming Cost: $10,000
Implementation
Analysis/Barriers
Additional DDC programming is required to automate this measure. Including DDC
control of portable buildings is also required. The addition of a global setpoint
adjustment control strategy is recommended.
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 9 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 3
HEATING, VENTILATION AND AIR CONDITIONING
Response Type
Auto-DR
Strategy
Defined in Strategy Details
Strategy Details
kW Reduction
Calculation
Load Factor
HVAC System Optimization: DR-82993
Type and Code
The Santa Barbara City College campus contains server rooms that is kept at approximately
70ºF. The ASHRAE 2008 Environmental Guidelines for Datacomm Equipment recommends
data centers operate between 64.4ºF and 80.6ºF. Raising the space temperature of the rooms will
decrease the cooling load required from the fan coil system serving the space.
The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140
compliant building energy analysis software tool. The baseline energy model is based on actual
building construction, occupancies, schedules, and equipment. It has been calibrated to match
the electrical demand profile of the facility's top 18 days of the previous year within 10%. The
simulation results for an increase in the space temperature set point from 70°F to 78°F for the
data center areas are shown below. See Appendix D for detailed building simulation results.
Trace 700 measures were modeled sequentially with the results of each measure used as the
baseline for the following measure to include interactive effects.
SOLUTION 3 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
6
Max kW
System Location
Server Rooms
Energy Usage System
Central Cooling System, see
equipment list
Avg. kW
2
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
Varies
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
Page 10 of 15
2012
Technical Assistance (TA)
Technical Audit Report
SOLUTION 3 – SITE 1 CONTINUED
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
Cost Description and
Breakdown
Implementation
Analysis/Barriers
The addition of a global setpoint adjustment control strategy is recommended.
The 4 hours of the DR event.
▪
Estimated Control and Programming Cost: $4,000
Additional DDC programming is required to automate this measure.
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 11 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 4
HEATING, VENTILATION AND AIR CONDITIONING
Response Type
Auto-DR
Type and Code
Strategy
Defined in Strategy Details
HVAC System Optimization: DR-82993
Shutdown of all non-critical HHW pumps during a demand response period is recommended.
Strategy Details
kW Reduction
Calculation
Load Factor
See calculations & supporting information. Refer to appendix C of report.
35% - See calculations & supporting information
SOLUTION 4 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
Max kW
9
System Location
Buildings: BC, IDC, L/LRC, A,
CC/HRC, EBS, H, OE, PE & SS
Energy Usage System
HHW System, see equipment list
Avg. kW
9
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
15
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
SOLUTION 4 – SITE 1 CONTINUED
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 12 of 15
2012
Technical Assistance (TA)
Technical Audit Report
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
Cost Description and
Breakdown
Implementation
Analysis/Barriers
Provide premium efficiency motors and VFD's to pump motors. Provide pump
pressure reset.
The 4 hours of the DR event.
▪
Estimated Control and Programming Cost: $6,000
Additional building control system programming is required to automate this measure.
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 13 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 5
HEATING, VENTILATION AND AIR CONDITIONING
Auto-DR
Strategy
Defined in Strategy Details
Strategy Details
Depending on the number of fixtures or lamps, a 33% or 50% reduction of lighting in nonclassroom areas is recommended during a demand response.
kW Reduction
Calculation
Load Factor
Type and Code
Lighting - Other: DR-62019
Response Type
See calculations & supporting information. Refer to appendix C of report.
Varies - See calculations & supporting information
SOLUTION 5 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
113
Max kW
System Location
All building spaces except
classrooms
Energy Usage System
Lighting
Avg. kW
113
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
N/A
Running
Amps
N/A
Unit ID
N/A
Horsepower
N/A
Max kW per Unit
N/A
Volts
N/A
Motor Efficiency
N/A
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
Varies
Watts Per
Fixture
Varies
Panel ID
Room #
Varies
Volts Per Fixture
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Circuit #
Varies
Varies
Solutions
Code
Measured Amps
Varies
Varies
Page 14 of 15
2012
Technical Assistance (TA)
Technical Audit Report
SOLUTION 5 – SITE 1 CONTINUED
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
The 4 hours of the DR event.
▪
Estimated Lighting Rewire Cost: $11,000
Cost Description and
Breakdown
▪
Estimated Lighting Control System Cost: $40,000
Implementation
Analysis/Barriers
Currently, approximately 85% of the campus has bi-level switching capability. A
lighting rewire in the remaining 15% of the building is required to implement this
measure. The implementation of a lighting control system to include individual
control of each lighting circuit to be shutdown is necessary to automate this measure.
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 15 of 15
2012
Technical Assistance (TA)
Technical Audit Report
ABOUT THE TECHNICAL AUDIT REPORT
Technical
Audit
Report
(Form#2B)
#2B)
Technical
Audit
Report
(Form
This template is used to conduct a Demand Response Technical Audit for Southern California Edison’s (SCE) Technical Assistance
(TA) Program. Unless specifically requested by SCE, Technical Audits should not be
performed on additional service accounts. The Technical Audit Report can be
General
General Site
SiteInformation
Informationand
andExecutive
ExecutiveSummary
Summary
completed by doing the following:
Provide
Provide site
sitespecific
specificinformation
informationforforallallsites
sites
• Complete the Customer & Engineer Certification form during the site visit.
that received the technical audit.
that received the technical audit.
(Customer signature required)
•
Complete the Technical Audit Report (Form #2B). Complete each of the
Demand Response Solution Recommendations
Demand
Response
Solution
following sections:
(The 2B
Report allows
up Recommendations
to 5 solutions)
(The 2BProvide
Reportdetails
allows
up to 5the
solutions)
regarding
o Engineer Information
recommendation.
Provide
details regarding the
o Technical Audit Summary
recommendation.
o General Site Information and Executive Summary
o Demand Response Solution Recommendations
Solution # - Site # (Repeats to 5 sites per solution)
o
Solution – Site
Which sites are Solution
applicable# to- Site
the aforementioned
#
recommendation? Provide details on how the
Whichrecommendation
sites are applicable
to the aforementioned
applies to each site.
recommendation? Provide details on how the
recommendation applies to each site.
DO NOT PROVIDE THE TECHNICAL AUDIT REPORT TO THE CUSTOMER.
SCE requires the audit be reviewed by the program verification engineer (PVE) prior
to the SCE customer seeing the Solution Recommendations. Email the electric copy
of this document and a scanned copy of the Customer & Engineer Certification form
with the customer’s signature to AUTODR@sce.com.
Note: This form is designed to identify a maximum of 5 solutions for 1 service account. If you exceed the space provided, please
continue on an additional Form #2B.
ENGINEER INFORMATION
Engineering Firm Name
SC Engineers, Inc.
Engineer Name
Frank Shadpour
Mailing Address
17075 Via Del Campo, First Floor
Mailing State
CA
Mailing
City
E-Mail
San Diego
administration@scengineers.n
et
Office Phone
858.946.0333
PE License #
M23923
Mailing Zip
92127
Mobile Phone
AUTO-DR TECHNICAL AUDIT SUMMARY
Customer
Name
Santa Barbara City College
SA#
Site #
Site Address
Site City
000203611
1
721 Cliff Dr.
Santa
Barbara
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
2B Cost
Portfolio (Project)
ID#
1282-1930
# Hours
for 2B
# of
Measures
Total Avg.
kW
8
497
Date(s) of
2B
Page 1 of 15
2012
Technical Assistance (TA)
Technical Audit Report
Appendix Info (The TA and Auto-DR Technology Incentive Programs will not provide technology incentives for manual improvements to
existing equipment, for load reduction enabled by the Customer’s behavior changes, or metering equipment):
Site 1
Service Account #
000203611
Occupancy
Operations
Schedule
EMS
Industrial Controls
GENERAL SITE INFORMATION
Facility Type
Campus
7am - 8pm
AC Sq Ft
615,000
Occupancy %:
No AC Sq Ft
Total Sq Ft
615,000
90%
The equipment operates primarily from 7:00am-8:00pm.
The HVAC equipment for the main buildings at the Santa Barbara City College are
controlled and monitored by a Johnson Controls (JCI) DDC system.
The JCI system can be accessed through computers located in the Facilities & Operations
building. The JCI system controls the majority of major HVAC equipment on campus:
chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC
equipment through the JCI system and timeclocks. Facility staff noted that they monitor
buildings and adjust schedules as needed. Some chillers at the college are programmed
with a chiller wated reset.
IT Infrastructure
The system can not be accessed remotely due to strict campus internt security.
DRAS Interface
Currently non-existent. Recommend interfacing with a Niagra AX JACE equipment with
operating ADR equipment driver.
Other
Considerations
PV panels shade a parking lot on the West Campus.
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 2 of 15
2012
Technical Assistance (TA)
Technical Audit Report
Site 1
Interview Summary
Site Summary
Energy System
Summary
EXECUTIVE SUMMARY
A field investigation or the Santa Barbara City College was conducted on the days of 3rd
of December, 2012, through 5th of December, 2012. Attendees included James
McKechnie of SC Engineers and Julie Hendricks and Brad Gyll of Santa Barbara City
College. HVAC, lighting, and process loads were indicated as most likely targets for
demand response reduction.
The Santa Barbara City College consists of approximately twenty (20) buildings consisting
of approximately 550,000 sq. ft., approximately fifty (50) portable units consisting of
approximately 62,500 sq. ft., a parking structure, several parking lots, and sporting fields.
The campus is heavily occupied from 7:00am - 8:00pm as it hosts several evening classes
in addition to a typical school day schedule. The majority of rooms consist of class/lecture
and office occupancies. Other notable areas are the gymnasium located in the Physical
Education building and the performance stages located in the Drama and Music building.
These areas may hold additional events not associated directly with the college.
HVAC ~ Control System: The HVAC equipment for the main buildings at the Santa
Barbara City College are controlled and monitored by a Johnson Controls (JCI) DDC
system. This system can be accessed through computers located in the Facilities &
Operations building. The system can not be accessed remotely due to strict campus
internet security. The JCI system controls most major HVAC equipment on campus:
chillers, air handlers, heat pumps, fan coils, etc. Facility staff can schedule HVAC
equipment through the JCI system and timeclocks. Facility staff noted that they monitor
buildings and adjust schedules as needed. Some chillers at the college are programmed
with a chiller water reset.
Lighting Systems: Interior lighting for the collegel is provided primarily by 4’, T8
fluorescent fixtures. Some 4', T12 fixtures and high intensity discharge (HID) fixtures
serve areas of the college as well. Approximately 85% of the campus contains bi-level
switching capabilities. Refer to Appendix C for a detailed lighting schedule by area.
Lighting Control Systems: Occupancy sensors were found sporadically throughout offices,
classrooms, and laboratories on the campus. No central lighting control system exists.
Outdoor lighting is controlled by photocells. Security lighting serves the campus and is
scheduled to be on 100% from dusk to midnight, then 50% from midnight to dawn.
Parking structure lights were noted to be on timers.
Process Loads ~ The campus contains the following high energy process loads:
▪
Multiple elevators that serve multi-level buildings
▪
The Business/Communications Building holds a cafeteria with associated
equipment including: several refrigerator units, one (1) walk-in refrigerator, and one (1)
walk-in freezer.
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 3 of 15
2012
Technical Assistance (TA)
Technical Audit Report
▪
The Campus Center/HRC Building holds a dining area on the second floor and two
(2) kitchens on the first floor with associated equipment including: several refrigerator
units, two (2) walk-in refrigerator, and three (3) walk-in freezer.
▪
A water feature on the West Campus.
▪
A water fountain on the East Campus.
▪
Several vending machines located around the college.
HVAC Overview: The portables at the Santa Barbara City College are conditioned by
packaged heat pumps that are 5 tons or less of cooling. These units are operated via indoor
thermostats. None of the portable packaged heat pumps can be accessed by the college JCI
system.
HVAC ~ Chilled Water Systems: The West Campus has three (3) buildings that are served
by a self-contained chiller plant. The East Campus has seven (7) buildings that are served
by a self-contained boiler plant. These boiler plants serve the building's hydronic air
handling units (AHU's) and fan coils.
HVAC ~ Heating Hot Water Systems: The West Campus has three (3) buildings that are
served by a self-contained boiler plant. These boiler plants serve the building's hydronic
air handling units (AHU's) and fan coils. The East Campus has seven (7) buildings that are
served by a self-contained boiler plant. These boiler plants serve the building's hydronic
air handling units (AHU's) and fan coils.
HVAC ~ Air-Side Systems: The buildings with chiller and boiler plants are served by fan
coils, constant air volume (CAV), and variable air volume (VAV) AHU's. The other
buildings are conditioned primarily by direct expansion (DX) units. East Campus
buildings are served by a combination of DX units, hydronic constant air volume (CAV),
and variable air volume (VAV) AHU's.
Auto-DR Summary
DR Measure # 1:
DR Measure # 2:
DR Measure # 3:
DR Measure # 4:
DR Measure # 5:
DR Measure # 6:
DR Measure # 7:
DR Measure # 8:
11.1 kW
HVAC - Chilled Water Supply Temperature Reset - 14.2 kW
HVAC - Space Temperature Reset - 340.9 kW
HVAC - Data Center Temperature Reset - 2.4 kW
HVAC - Heating Hot Water Pump Shutdown - 9.2 kW
Lighting - Lighting Reduction - 113.5 kW
Process Load - Fountain Pump Shutdown - 3.2 kW
Process Load - Pre-Cool Refrigeration Spaces - 2.8 kW
Process Load - Beverage Vending Machine Compressor Shutdown -
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 4 of 15
2012
Technical Assistance (TA)
Technical Audit Report
Additional
Information
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 5 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 1
PROCESS
Type and Code:
Process Machinery-Other: DR30001
Response Type
Auto-DR
Strategy
Turn off fountains and swimming pool pumps
Strategy Details
Fountain Pump Shutdown
kW Reduction
Calculation
See calculations & supporting information. Refer to appendix C of report.
Load Factor
90% - See calculations & supporting information
SOLUTION 1 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
Max kW
System Location
Energy Usage System
Avg. kW
3
One on east and one on west side
of campus
Fountain Systems, see calculations
and supporting information
3
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
2
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
Page 6 of 15
2012
Technical Assistance (TA)
Technical Audit Report
SOLUTION 1 – SITE 1 CONTINUED
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
The 4 hours of the DR event.
Cost Description and
Breakdown
▪
Estimated Control and Programming Cost: $4,000
Implementation
Analysis/Barriers
The addition of on/off control of the fountain pumps through the building's DDC
system is recommended.
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 7 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 2
PROCESS
Response Type
Auto-DR
Strategy
Defined in Strategy Details
Strategy Details
Pre-Cool Refrigeration Spaces
kW Reduction
Calculation
Load Factor
Type and Code
Process - Refrigeration Syst. Opt: DR-89124
See calculations & supporting information. Refer to appendix C of report.
85% - See calculations & supporting information
SOLUTION 2 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
Max kW
2
System Location
Buildings: CC, HRC, & SCA
Energy Usage System
Refrigeration Systems
Avg. kW
2
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
7
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
SOLUTION 2 – SITE 1 CONTINUED
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 8 of 15
2012
Technical Assistance (TA)
Technical Audit Report
EE Opportunities
(please include calculations of results)
Provide evaporative unit controllers and EC motors.
Recommended Reduction
Time
The 4 hours of the DR event.
Cost Description and
Breakdown
▪
Implementation
Analysis/Barriers
The connection of the refrigerators/freezers temperature control system to the
proposed DDC network is recommended to automate this measure.
Estimated Control and Programming Cost: $20,000
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 9 of 15
2012
Technical Assistance (TA)
Technical Audit Report
AUTOMATED DEMAND RESPONSE SOLUTION RECOMMENDATIONS
Solution 3
PROCESS
Process Machinery-Other: DR30001
Response Type
Auto-DR
Type and Code
Strategy
Defined in Strategy Details
Strategy Details
Beverage Vending Machine Compressor Shutdown
kW Reduction
Calculation
See calculations & supporting information. Refer to appendix C of report.
Load Factor
30% - See calculations & supporting information
SOLUTION 3 – SITE 1
Implementation
18 Days
Time
Hours of
2pm-6pm
Operation
Max kW
11
System Location
Campus Wide
Energy Usage System
Vending Machines
Avg. kW
11
BASED ON THE ENERGY SYSTEM TYPE, PROVIDE ALL APPLICABLE FACTORS
(ONLY Complete Type A or Type B)
TYPE A – HVAC, PROCESS, CONTROLS
T
Y
P
E
A
# of Units
30
Running
Amps
Varies
Unit ID
Varies
Horsepower
Varies
Max kW per Unit
Varies
Volts
Varies
Motor Efficiency
Varies
OR
TYPE B - LIGHTING
T
Y
P
E
B
Floor #
N/A
Watts Per
Fixture
N/A
Panel ID
Room #
N/A
Volts Per Fixture
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Circuit #
N/A
N/A
Solutions
Code
Measured Amps
N/A
N/A
Page 10 of 15
2012
Technical Assistance (TA)
Technical Audit Report
SOLUTION 3 – SITE 1 CONTINUED
EE Opportunities
(please include calculations of results)
Recommended Reduction
Time
The 4 hours of the DR event.
Cost Description and
Breakdown
▪
Implementation
Analysis/Barriers
The addition of on/off control for the vending machines through the existing DDC
system is recommended to automate this measure.
Estimated Controls Cost: $15,000
Additional Comments
Technical Assistance Technical Audit Report (Form #2B - Single) 05-01-2012
Page 11 of 15
APPENDIX
APPENDIX "C" - Calculations and Supporting Information
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021
© 2013 SC ENGINEERS, INC.
"C"
CALCULATIONS
Demand Response Measure # 1: Chilled Water Supply Temperature Reset
The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis
software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It
has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. Demand
response measures were calculated sequentially with the results of each measure used as the baseline for the following measure
to include interactive effects. A chilled water temperature reset was modeled for a 4°F CHW supply temperature increase (44°F
to 48°F) in the facility. See Appendix D for detailed Trace 700 building simulation results.
Effect of Demand Response on Peak Load
1,800
1,600
Facility Demand (kW)
1,400
1,200
1,000
800
600
400
200
0
Cooling Equip
Cooling Tower
Hour
Fan Equip
Pump Equip
Misc Equip
Heating Equip
Base Utility
Baseline
220.7 kW,
13.7%
15. kW,
0.9%
220.7 kW,
13.85%
285.2 kW,
17.7%
19.9 kW,
1.2%
95.9 kW,
6.0%
15. kW,
0.94%
Lights
285.2 kW,
17.89%
19.9 kW,
1.25%
95.6 kW,
5.99%
304.7 kW,
18.9%
304.7 kW,
19.12%
653. kW,
40.96%
Electric Peak Demand for Chilled Water Supply
Temperature Reset
666.8 kW,
41.5%
Electric Peak Demand for Baseline
kW Reduction:
1,608.17 kW - 1,593.99 kW = 14.18 kW
Baseline
DR Measure #1
Demand Reduction
2:00PM
1597.6 kW
1583.4 kW
14.1 kW
3:00 PM
1696.1 kW
1681.2 kW
14.9 kW
Peak Demand (kW)
4:00 PM
1687.1 kW
1671.8 kW
15.3 kW
5:00 PM
1624.0 kW
1609.6 kW
14.3 kW
6:00 PM
1436.2 kW
1424.0 kW
12.2 kW
CALCULATIONS
Demand Response Measure # 2: Space Temperature Reset 72°F to 76°F
The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis
software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It
has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. Demand
response measures were calculated sequentially with the results of each measure used as the baseline for the following measure
to include interactive effects. The simulation results for an increase in the space temperature set point from 72°F to 76°F for the
slected areas are shown below. See Appendix D for detailed building simulation results.
Effect of Demand Response on Peak Load
2,500
Facility Demand (kW)
2,000
1,500
1,000
500
0
Cooling Equip
Pump Equip
Heating Equip
220.7 kW,
14%
Cooling Tower
Lights
Base Utility
15. kW, 1%
285.2 kW,
18%
19.9 kW,
1%
95.9 kW,
6%
Hour
Fan Equip
Misc Equip
Chilled Water Supply Temperature Reset
112.2 kW,
9% 3.4 kW, 0% 15. kW, 1%
19.9 kW,
285.2 kW,
2%
23%
66.3 kW,
5%
304.7 kW,
19%
304.7 kW,
24%
460.6 kW,
36%
666.8 kW,
41%
Electric Peak Demand for Chilled Water Supply
Temperature Reset
Electric Peak Demand for Space Temperature Reset
kW Reduction:
1,608.17 kW - 1,267.30 kW = 340.88 kW
Baseline
DR Measure #1
Demand Reduction
2:00PM
1597.6 kW
832.1 kW
765.5 kW
3:00 PM
1696.1 kW
1249.9 kW
446.2 kW
Peak Demand (kW)
4:00 PM
1687.1 kW
1444.3 kW
242.7 kW
5:00 PM
1624.0 kW
1430.0 kW
194.0 kW
6:00 PM
1436.2 kW
1380.2 kW
56.0 kW
CALCULATIONS
Demand Response Measure # 3: Data Center Temperature Reset 70°F to 78°F
The following analysis was performed using Trace 700, an ANSI/ASHRAE Standard 140 compliant building energy analysis
software tool. The baseline energy model is based on actual building construction, occupancies, schedules, and equipment. It
has been calibrated to match the electrical demand profile of the facility's top 18 days of the previous year within 10%. Demand
response measures were calculated sequentially with the results of each measure used as the baseline for the following measure
to include interactive effects. The simulation results for an increase in the space temperature set point from 70°F to 78°F for the
data center areas are shown below. See Appendix D for detailed building simulation results.
Effect of Demand Response on Peak Load
2,500
Facility Demand (kW)
2,000
1,500
1,000
500
0
Hour
Cooling Tower
Lights
Base Utility
Cooling Equip
Pump Equip
Heating Equip
112.2 kW,
9%
19.9 kW,
2%
3.4 kW,
0%
Fan Equip
Misc Equip
Space Temperature Reset
15. kW,
1%
285.2 kW,
23%
66.3 kW,
5%
19.9 kW,
2%
111.3 kW,
9%
3.4 kW,
0%
15. kW, 1%
285.2 kW,
23%
66.2 kW,
5%
304.7 kW,
24%
460.6 kW,
36%
Electric Peak Demand for Space Temperature Reset
304.7 kW,
24%
459.2 kW,
36%
Electric Peak Demand for Data Center Temperature Reset
kW Reduction:
1,267.30 kW - 1,264.92 kW = 2.38 kW
Baseline
DR Measure #1
Demand Reduction
2:00PM
832.1 kW
826.0 kW
6.1 kW
3:00 PM
1249.9 kW
1248.7 kW
1.2 kW
Peak Demand (kW)
4:00 PM
5:00 PM
1444.3 kW
1430.0 kW
1442.7 kW
1428.5 kW
1.7 kW
1.6 kW
6:00 PM
1380.2 kW
1378.9 kW
1.3 kW
CALCULATIONS
Demand Response Measure # 4:
Demand Reduction by Heating Hot Water Pump Shutdown
Current
Manufacturer Equipment
Qty
HP
GPM
Ft. Head
Load Factor
Efficiency
15
2.0
254
75
35%
85%
Demand Response
Status
Demand kW
ON
9.2 kW
Status
Demand kW
Pump kW
Reduction
OFF
0.0 kW
9.2 kW
*
Varies
HHW Pumps
Totals
15
* Current: [Demand kW] = [HP] x [Load Factor] x 0.7457 / [Efficiency]
** [Pump kW Reduction] = [Current Demand kW] - [Demand Response Demand kW]
Notes:
(1) Efficiency is based on motor size (HP) and Load Factor
9.2 kW
**
9.2 kW
CALCULATIONS
Demand Response Measure # 5:
Demand Reduction by Lighting Reduction
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
3
Admin
RECEPTIONIST RM 114
432MAXL
4
91.0
3
273 W
50%
NO
137 W
4
Admin
OFFICE 114A
432MAXL
4
91.0
2
182 W
50%
NO
91 W
5
Admin
OFFICE 114A
232MAXL
1
24.0
2
48 W
50%
Yes
24 W
7
Admin
OFFICE 114B
432MAXL
4
91.0
2
182 W
50%
NO
91 W
182 W
9
Admin
CONFRENCE 113-3
332MAXL
3
68.0
4
272 W
33%
NO
10
Admin
CONFRENCE 113-3
332MAXL
3
68.0
2
136 W
33%
Yes
91 W
11
Admin
OFFICE 113-2
332MAXL
3
68.0
4
272 W
33%
NO
182 W
12
Admin
OFFICE 113-1
332MAXL
3
68.0
4
272 W
33%
NO
182 W
13
Admin
OPEN OFFICE 113
332MAXL
3
68.0
4
272 W
33%
NO
182 W
14
Admin
OPEN OFFICE 113
332MAXL
3
68.0
2
136 W
33%
Yes
91 W
15
Admin
RECEPTIONIST RM 112A
432MAXL
4
91.0
4
364 W
50%
NO
182 W
16
Admin
OFFICE 111
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
17
Admin
OFFICE 111
1
25.0
2
50 W
50%
Yes
25 W
18
Admin
OPEN OFFICE 110
432MAXL
4
91.0
6
546 W
50%
NO
273 W
19
Admin
WORK ROOM 150A
432MAXL
4
91.0
2
182 W
50%
NO
91 W
22
Admin
OFFICE 119A
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
23
Admin
OFFICE 119B
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
24
Admin
OFFICE 119C
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
25
Admin
OFFICE 117
432MAXN
2
51.5
4
206 W
50%
NO
103 W
26
Admin
OFFICE 117A
432MAXN
2
51.5
4
206 W
50%
NO
103 W
27
Admin
OFFICE 117B
432MAXN
2
51.5
4
206 W
50%
NO
103 W
29
Admin
OFFICE 116A
432MAXN
2
51.5
4
206 W
50%
NO
103 W
30
Admin
OFFICE 116
432MAXN
2
51.5
4
206 W
50%
NO
103 W
31
Admin
HALLWAY #1
232MAXN
2
52.0
7
364 W
50%
NO
182 W
32
Admin
HALLWAY #1
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
34
Admin
HALLWAY #2
232MAXN
2
52.0
6
312 W
50%
NO
156 W
37
Admin
PHONE RM BY 116
232MAXL
2
46.0
4
184 W
50%
NO
92 W
39
Admin
WAREHOUSE 121
232MAXN
2
52.0
15
780 W
50%
NO
390 W
40
Admin
OFFICE 122
432MAXN
2
51.5
4
206 W
50%
NO
103 W
41
Admin
OFFICE 123A
432MAXL
4
91.0
6
546 W
50%
NO
273 W
42
Admin
OFFICE 123A
432MAXL
4
91.0
1
91 W
50%
NO
46 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
43
Admin
OFFICE 124A
432MAXL
4
91.0
2
182 W
50%
NO
91 W
44
Admin
OFFICE 123
332MAXL
3
68.0
3
204 W
33%
NO
137 W
45
Admin
AUTO SHOP AREA 108
232MAXN
2
52.0
13
676 W
50%
NO
338 W
46
Admin
SHOP OFFICE 108C
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
48
Admin
HALLWAY #4
232MAXN
2
52.0
4
208 W
50%
NO
104 W
49
Admin
HALLWAY #3
232MAXN
2
52.0
5
260 W
50%
NO
130 W
50
Admin
OFFICE A130
232MAXN
2
52.0
44
2288 W
50%
NO
1144 W
51
Admin
OFFICE A130
232MAXN
2
52.0
1
52 W
50%
NO
26 W
52
Admin
OFFICE A130
1
17.0
5
85 W
50%
NO
43 W
53
Admin
WORK ROOM 130A
332MAXL
3
68.0
3
204 W
33%
NO
137 W
54
Admin
OFFICE 130C
332MAXL
3
68.0
2
136 W
33%
Yes
91 W
55
Admin
OFFICE 130C
232MAXL
1
24.0
2
48 W
50%
Yes
24 W
56
Admin
OFFICE 130D
332MAXL
3
68.0
3
204 W
33%
NO
137 W
59
Admin
OFFICE 130E
332MAXL
3
68.0
3
204 W
33%
NO
137 W
60
Admin
HALLWAY #5
332MAXL
3
68.0
6
408 W
33%
NO
273 W
61
Admin
COPY OFFICE 141A
432MAXL
4
91.0
1
91 W
50%
NO
46 W
62
Admin
COPY ROOM 141
332MAXL
3
68.0
11
748 W
33%
NO
501 W
63
Admin
HALLWAY #4
232MAXN
2
52.0
3
156 W
50%
NO
78 W
65
Admin
MECH ROOM BY 160
*232MAXL
2
46.0
17
782 W
50%
NO
391 W
66
Admin
MECH ROOM BY 160
232MAXL
2
46.0
4
184 W
50%
NO
92 W
67
Admin
MECH RM BY 160 UP ELEC
*232MAXL
2
46.0
3
138 W
50%
NO
69 W
68
Admin
MECH RM BY 160 LOW ELEC
*232MAXL
2
46.0
2
92 W
50%
Yes
46 W
69
Admin
HALLWAY #7
232MAXN
2
52.0
6
312 W
50%
NO
156 W
70
Admin
OFFICE 162A
232MAXN
2
52.0
1
52 W
50%
NO
26 W
71
Admin
STORAGE 162B
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
72
Admin
OFFICE A182A
432MAXL
4
91.0
4
364 W
50%
NO
182 W
73
Admin
HALLWAY #8
232MAXN
2
52.0
4
208 W
50%
NO
104 W
75
Admin
OFFICE A178
232MAXN
2
52.0
1
52 W
50%
NO
26 W
76
Admin
OFFICE A176
232MAXN
2
52.0
1
52 W
50%
NO
26 W
77
Admin
OFFICE A175
232MAXN
2
52.0
1
52 W
50%
NO
26 W
78
Admin
OFFICE A174
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
79
Admin
HALLWAY #9
232MAXN
2
52.0
15
780 W
50%
NO
390 W
80
Admin
OFFICE A179
232MAXN
2
52.0
1
52 W
50%
NO
26 W
82
Admin
STORAGE A277
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
85
Admin
HALLWAY A279
232MAXN
2
52.0
8
416 W
50%
NO
208 W
86
Admin
OFFICE A279
432MAXL
2
45.5
4
182 W
50%
NO
91 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
87
Admin
OFFICE A276
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
88
Admin
OFFICE A275
232MAXN
2
52.0
1
52 W
50%
NO
26 W
89
Admin
OFFICE A274
232MAXN
2
52.0
1
52 W
50%
NO
26 W
90
Admin
OFFICE A272
232MAXN
2
52.0
1
52 W
50%
NO
26 W
91
Admin
PHONE ROOM A271
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
92
Admin
RECEPTIONIST ROOM 218
432MAXL
2
45.5
8
364 W
50%
NO
182 W
93
Admin
OFFICE KO7
432MAXL
2
45.5
6
273 W
50%
NO
137 W
95
Admin
CONFRENCE RM 218 C
432MAXL
2
45.5
8
364 W
50%
NO
182 W
96
Admin
CONFRENCE RM 218 C
432MAXL
2
45.5
4
182 W
50%
NO
91 W
97
Admin
OFFICE 2118B
432MAXL
2
45.5
4
182 W
50%
NO
91 W
98
Admin
OFFICE 2118A
432MAXL
2
45.5
6
273 W
50%
NO
137 W
99
Admin
OFFICE A213
432MAXL
4
91.0
2
182 W
50%
NO
91 W
100
Admin
OFFICE A213A
432MAXL
4
91.0
2
182 W
50%
NO
91 W
101
Admin
OFFICE A213B
432MAXL
4
91.0
1
91 W
50%
NO
46 W
102
Admin
OFFICE A213C
432MAXL
4
91.0
1
91 W
50%
NO
46 W
103
Admin
OFFICE A211
432MAXL
2
45.5
6
273 W
50%
NO
137 W
104
Admin
OFFICE A211
432MAXL
2
45.5
3
137 W
50%
NO
68 W
105
Admin
HALLWAY BY 211
232MAXL
2
46.0
4
184 W
50%
NO
92 W
107
Admin
HALLWAY BY 214
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
108
Admin
HALLWAY BY 214
232MAXN
2
52.0
3
156 W
50%
NO
78 W
110
Admin
HALLWAY BY 210
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
111
Admin
OFFICE 210
232MAXN
2
52.0
0
0W
50%
NO
0W
113
Admin
HALLWAY BY 207-208
232MAXN
2
52.0
6
312 W
50%
NO
156 W
115
Admin
OFFICE 209
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
116
Admin
OFFICE 208
432MAXL
2
45.5
2
91 W
50%
Yes
46 W
117
Admin
OFFICE 208
232MAXL
2
46.0
1
46 W
50%
NO
23 W
118
Admin
OFFICE 207
432MAXL
2
45.5
4
182 W
50%
NO
91 W
119
Admin
OFFICE 204
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
120
Admin
OFFICE 205A
432MAXL
2
45.5
2
91 W
50%
Yes
46 W
121
Admin
OFFICE 205B
432MAXL
2
45.5
2
91 W
50%
Yes
46 W
122
Admin
HALLWAY BY 205A-B
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
124
Admin
OFFICE 206
432MAXL
2
45.5
4
182 W
50%
NO
91 W
128
Admin
HALLWAY BY 200
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
129
Admin
RADIATION RM 236
232MAXN
2
52.0
8
416 W
50%
NO
208 W
131
Admin
STORAGE ROOM A236A
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
133
Admin
OFFICE A240
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
26 W
134
Admin
OFFICE A239
232MAXN
2
52.0
1
52 W
50%
NO
135
Admin
OFFICE A238
232MAXN
2
52.0
1
52 W
50%
NO
26 W
136
Admin
OFFICE A237
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
137
Book Str
EXTERIOR & ENTRANCE
1
15.0
18
270 W
50%
NO
135 W
138
Book Str
OFFICE # 1
232MAXL
2
46.0
1
46 W
50%
NO
23 W
139
Book Str
OFFICE # 1
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
140
Book Str
OFFICE # 2
232MAXN
2
52.0
3
156 W
50%
NO
78 W
141
Book Str
OFFICE # 2
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
143
Book Str
CUSTOMER SRVICE AREA
2
68.0
4
272 W
50%
NO
136 W
144
Book Str
MEETING RM
232MAXL
2
46.0
3
138 W
50%
NO
69 W
145
Book Str
MEETING RM
232MAXN
2
52.0
3
156 W
50%
NO
78 W
146
Book Str
MEETING RM
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
147
Book Str
RECEIVING STORAGE
432MAXL
4
91.0
7
637 W
50%
NO
319 W
149
Book Str
OFFICE # 3
232MAXL
2
46.0
1
46 W
50%
NO
23 W
150
Book Str
OFFICE # 3
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
151
Book Str
BOOKS DISPLAY AREA
2
68.0
58
3944 W
50%
NO
1972 W
152
Book Str
BOOKS DISPLAY AREA
232MAXN
2
52.0
16
832 W
50%
NO
416 W
153
Book Str
BOOKS DISPLAY AREA
232MAXN
2
52.0
94
4888 W
50%
NO
2444 W
154
Book Str
BOOKS DISPLAY AREA
232MAXN
2
52.0
5
260 W
50%
NO
130 W
155
Book Str
BOOKS DISPLAY AREA
1
25.0
8
200 W
50%
NO
100 W
156
Book Str
BOOKS DISPLAY AREA
1
25.0
8
200 W
50%
NO
100 W
157
Book Str
CENTER STAIRS
1
13.0
12
156 W
50%
NO
78 W
158
Book Str
COPY ROOM B1
232MAXN
2
28.0
3
84 W
50%
NO
42 W
160
Book Str
OFICE #B3
232MAXN
2
28.0
7
196 W
50%
NO
98 W
161
Book Str
BREAKROOM B4
232MAXN
2
28.0
9
252 W
50%
NO
126 W
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
2
68.0
28
1904 W
50%
NO
952 W
163
Book Str
BREAKROOM HALLWAY B7
164
Book Str
BOOKS DISPLAY AREA BO
165
Book Str
BOOKS DISPLAY AREA BO
232MAXN
2
52.0
22
1144 W
50%
NO
572 W
166
Book Str
BOOKS DISPLAY AREA BO
232MAXN
2
52.0
14
728 W
50%
NO
364 W
168
Book Str
BOOKS DISPLAY AREA BO
332MAXL
1
22.7
18
409 W
50%
NO
204 W
171
Book Str
BOOKS DISPLAY AREA BO
332MAXL
1
22.7
4
91 W
50%
NO
45 W
174
Book Str
BOOK STORAGE
432MAXL
4
91.0
16
1456 W
50%
NO
728 W
175
BC
HALL 234
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
176
BC
HALL 223
232MAXN
2
52.0
10
520 W
50%
NO
260 W
177
BC
HALL 223
232MAXN
2
52.0
4
208 W
50%
NO
104 W
179
BC
HALL 205
232MAXN
2
52.0
7
364 W
50%
NO
182 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
180
BC
OFFICE 206
232MAXN
2
52.0
1
52 W
50%
NO
26 W
181
BC
OFFICE 207
232MAXN
2
52.0
1
52 W
50%
NO
26 W
182
BC
OFFICE 208
232MAXN
2
52.0
1
52 W
50%
NO
26 W
183
BC
OFICE 210
232MAXN
2
52.0
1
52 W
50%
NO
26 W
184
BC
OFICE 211
232MAXN
2
52.0
1
52 W
50%
NO
26 W
186
BC
MEETING ROOM 214
432MAXL
2
45.5
8
364 W
50%
NO
182 W
189
BC
HALL 213
232MAXN
2
52.0
6
312 W
50%
NO
156 W
190
BC
OFFICE 215
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
191
BC
OFFICE 216
232MAXN
2
52.0
4
208 W
50%
NO
104 W
192
BC
OFFICE 217
232MAXN
2
52.0
4
208 W
50%
NO
104 W
193
BC
OFFICE 218
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
194
BC
OFFICE 219
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
195
BC
COPY ROOM 203
232MAXN
2
52.0
8
416 W
50%
NO
208 W
196
BC
CONF. ROOM 204
232MAXN
2
52.0
4
208 W
50%
NO
104 W
198
BC
ENRTY 202
232MAXN
2
52.0
4
208 W
50%
NO
104 W
199
BC
OFFICE 306
232MAXN
2
52.0
1
52 W
50%
NO
26 W
200
BC
OFFICE 307
232MAXN
2
52.0
1
52 W
50%
NO
26 W
201
BC
OFFICE 308
232MAXN
2
52.0
1
52 W
50%
NO
26 W
202
BC
OFFICE 309
232MAXN
2
52.0
1
52 W
50%
NO
26 W
203
BC
OFFICE 310
232MAXN
2
52.0
1
52 W
50%
NO
26 W
204
BC
OFFICE 311
232MAXN
2
52.0
1
52 W
50%
NO
26 W
205
BC
OFFICE 312
232MAXN
2
52.0
1
52 W
50%
NO
26 W
206
BC
HALL 304
232MAXN
2
52.0
7
364 W
50%
NO
182 W
209
BC
HALL 244-1
1
40.0
7
280 W
50%
NO
140 W
215
BC
HALL 243
1
40.0
5
200 W
50%
NO
100 W
220
BC
HALL 107
1
17.0
4
68 W
50%
NO
34 W
221
BC
OFFICE 102E
332MAXL
3
68.0
2
136 W
33%
Yes
91 W
222
BC
OFFICE 102E
332MAXL
3
68.0
1
68 W
33%
NO
46 W
223
BC
OFFICE 102D
232MAXN
2
52.0
1
52 W
50%
NO
26 W
224
BC
OFFICE 102C
232MAXN
2
52.0
1
52 W
50%
NO
26 W
225
BC
OFFICE 102B
232MAXN
2
52.0
1
52 W
50%
NO
26 W
226
BC
OFFICE 102A
232MAXN
2
52.0
1
52 W
50%
NO
26 W
227
BC
OFFICE 102F
332MAXL
3
68.0
2
136 W
33%
Yes
91 W
228
BC
OFFICE 102F
332MAXL
3
68.0
1
68 W
33%
NO
46 W
229
BC
STORAGE 112
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
230
BC
OFFICE 115
232MAXN
2
52.0
1
52 W
50%
NO
26 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
26 W
231
BC
OFFICE 116
232MAXN
2
52.0
1
52 W
50%
NO
232
BC
OFFICE 117
232MAXN
2
52.0
1
52 W
50%
NO
26 W
233
BC
CAFETERIA
1
25.0
9
225 W
50%
NO
113 W
234
BC
CAFETERIA
232MAXN
2
52.0
11
572 W
50%
NO
286 W
236
BC
OFFICE 141
232MAXN
2
52.0
1
52 W
50%
NO
26 W
237
BC
OFFICE 142
232MAXN
2
52.0
1
52 W
50%
NO
26 W
238
BC
OFFICE 143
232MAXN
2
52.0
1
52 W
50%
NO
26 W
239
BC
OFFICE 143
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
240
BC
HALL 2
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
242
BC
ENTRY 113
232MAXN
2
52.0
4
208 W
50%
NO
104 W
246
BC
AUDITORIUM
1
90.0
30
2700 W
50%
NO
1350 W
247
BC
AUDITORIUM
1
2.0
6
12 W
50%
NO
6W
251
Camp Cntr
ROOF STORAGE 106
232MAXN
2
52.0
6
312 W
50%
NO
156 W
252
Camp Cntr
ROOF STORAGE 106
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
253
Camp Cntr
ROOF STORAGE 106
432MAXL
2
45.5
2
91 W
50%
Yes
46 W
255
Camp Cntr
MECHANICAL ROOM 105
232MAXL
2
39.0
4
156 W
50%
NO
78 W
257
Camp Cntr
MECHANICAL ROOM 105
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
258
Camp Cntr
MECHANICAL ROOM 105
232MAXN
2
52.0
6
312 W
50%
NO
156 W
259
Camp Cntr
FOOD STORAGE 110
232MAXN
2
52.0
6
312 W
50%
NO
156 W
260
Camp Cntr
FOOD STORAGE 110
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
261
Camp Cntr
OFFICE 117
432MAXN
2
51.5
4
206 W
50%
NO
103 W
262
Camp Cntr
CASHIER OFFICE
232MAXN
2
52.0
3
156 W
50%
NO
78 W
263
Camp Cntr
OFFICE 118
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
264
Camp Cntr
OFFICE 119
332MAXL
3
68.0
1
68 W
33%
NO
46 W
265
Camp Cntr
RECEPTIONIST RM 120
432MAXN
2
51.5
4
206 W
50%
NO
103 W
266
Camp Cntr
RECEPTIONIST RM 120
1
25.0
5
125 W
50%
NO
63 W
267
Camp Cntr
STORAGE 121
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
271
Camp Cntr
HALLWAY BY 114-128
1
25.0
15
375 W
50%
NO
188 W
273
Camp Cntr
CAFETERIA SEATING RM 201
232MAXH
2
70.0
24
1680 W
50%
NO
840 W
274
Camp Cntr
CAFETERIA SEATING RM 201
232MAXH
2
70.0
12
840 W
50%
NO
420 W
275
Camp Cntr
CAFETERIA SEATING RM 201
232MAXH
2
70.0
6
420 W
50%
NO
210 W
276
Camp Cntr
POTS PANS STORAGE RM 202
432MAXN
2
51.5
2
103 W
50%
Yes
52 W
277
Camp Cntr
POTS PANS STORAGE RM 202
232MAXN
2
52.0
6
312 W
50%
NO
156 W
278
Camp Cntr
CAFETERIA BY RM 207
232MAXN
2
28.0
34
952 W
50%
NO
476 W
279
Camp Cntr
CAFETERIA BY RM 207
232MAXN
2
28.0
2
56 W
50%
Yes
28 W
280
Camp Cntr
MAIN LOBBY 209
232MAXN
2
52.0
8
416 W
50%
NO
208 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
208 W
281
Camp Cntr
MAIN LOBBY 209
232MAXN
2
52.0
8
416 W
50%
NO
282
Camp Cntr
GAME RM 216
232MAXN
2
28.0
4
112 W
50%
NO
56 W
283
Camp Cntr
MACHANICAL RM 215
232MAXN
2
52.0
3
156 W
50%
NO
78 W
284
Camp Cntr
HALLWAY 213
232MAXN
2
28.0
5
140 W
50%
NO
70 W
285
Camp Cntr
RECEPTIONIST AREA KO1
432MAXL
4
91.0
2
182 W
50%
NO
91 W
292
Camp Cntr
CONFRENCE RM 223
432MAXL
4
91.0
10
910 W
50%
NO
455 W
293
Camp Cntr
OFFICE 224
232MAXN
2
52.0
3
156 W
50%
NO
78 W
294
Camp Cntr
MULTI PURPOSE RM 228
432MAXL
4
91.0
14
1274 W
50%
NO
637 W
295
Drama
OFFICE 160
232MAXN
2
52.0
1
52 W
50%
NO
26 W
296
Drama
OFFICE 151A
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
297
Drama
OFFICE 151B
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
298
Drama
HALL C05
232MAXN
2
52.0
7
364 W
50%
NO
182 W
300
Drama
HALL C05
1
28.0
5
140 W
50%
NO
70 W
303
Drama
STORAGE 155A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
304
Drama
EXTERIOR THEATER LOBBY
2
40.0
12
480 W
50%
NO
240 W
305
Drama
EXTERIOR THEATER LOBBY
232MAXN
2
52.0
11
572 W
50%
NO
286 W
306
Drama
MECHANICAL RM 153
232MAXN
2
52.0
4
208 W
50%
NO
104 W
308
Drama
PREP WORKSHOP 145
B254WHO
2
124.0
12
1488 W
50%
NO
744 W
312
Drama
PREP WORKSHOP 145
B254WHO
2
124.0
8
992 W
50%
NO
496 W
314
Drama
PREP WORKSHOP 145
B254WHO
2
124.0
8
992 W
50%
NO
496 W
315
Drama
PREP WORKSHOP 145
B254WHO
2
124.0
8
992 W
50%
NO
496 W
317
Drama
PREP WORKSHOP 145
B254WHO
2
124.0
8
992 W
50%
NO
496 W
318
Drama
LOUNGE 145A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
319
Drama
OFFICE 145C
232MAXN
2
52.0
1
52 W
50%
NO
26 W
320
Drama
TOOL RM
232MAXN
2
52.0
8
416 W
50%
NO
208 W
321
Drama
STAGE
*232MAXL
1
24.0
4
96 W
50%
NO
48 W
322
Drama
STAGE
1
150.0
4
600 W
50%
NO
300 W
323
Drama
STAGE
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
325
Drama
STAGE
232MAXN
2
52.0
11
572 W
50%
NO
286 W
326
Drama
STAGE
*232MAXL
2
46.0
4
184 W
50%
NO
92 W
327
Drama
STAGE
*232MAXL
2
46.0
6
276 W
50%
NO
138 W
333
Drama
HALL 1
232MAXN
2
52.0
9
468 W
50%
NO
234 W
334
Drama
HALL 1
232MAXN
2
52.0
5
260 W
50%
NO
130 W
335
Drama
HALL 2
232MAXN
2
52.0
11
572 W
50%
NO
286 W
336
Drama
HALL 2
232MAXN
2
52.0
5
260 W
50%
NO
130 W
339
Drama
DRESSING ROOM 130
232MAXN
2
52.0
12
624 W
50%
NO
312 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
340
Drama
DRESSING ROOM 130
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
341
Drama
DRESSING ROOM 133
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
342
Drama
DRESSING ROOM 129
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
343
Drama
LAUNDRY 126A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
344
Drama
COSTUMES 126
232MAXN
2
52.0
8
416 W
50%
NO
208 W
345
Drama
COSTUMES 126
232MAXN
2
52.0
10
520 W
50%
NO
260 W
346
Drama
COSTUMES 126
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
347
Drama
OFFICE 125
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
348
Drama
OFFICE 124
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
349
Drama
OFFICE 123
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
350
Drama
OFFICE 122
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
351
Drama
OFFICE 121
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
352
Drama
OFFICE 120
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
353
Drama
OFFICE 119
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
354
Drama
OFFICE 118
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
355
Drama
OFFICE 117
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
356
Drama
OFFICE 116
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
357
Drama
OFFICE 114D
232MAXN
2
52.0
1
52 W
50%
NO
26 W
359
Drama
HALL C02
232MAXN
2
52.0
3
156 W
50%
NO
78 W
360
Drama
HALL C03
232MAXN
2
52.0
6
312 W
50%
NO
156 W
361
Drama
HALL 3
232MAXN
2
52.0
4
208 W
50%
NO
104 W
362
Drama
OFFICE 114C
232MAXN
2
52.0
1
52 W
50%
NO
26 W
363
Drama
OFFICE 114C
1
25.0
4
100 W
50%
NO
50 W
364
Drama
WORKROOM 114B
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
366
Drama
OFFICE 114A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
367
Drama
HALL C01
232MAXN
2
52.0
8
416 W
50%
NO
208 W
368
Drama
HALL C01
232MAXN
2
52.0
19
988 W
50%
NO
494 W
370
Drama
OFFICE 103-1
232MAXN
2
52.0
6
312 W
50%
NO
156 W
371
Drama
OFFICE 103-1
232MAXN
2
52.0
3
156 W
50%
NO
78 W
372
Drama
OFFICE 103
232MAXN
2
52.0
4
208 W
50%
NO
104 W
373
Drama
OFFICE 103
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
374
Drama
OFFICE 104
232MAXN
2
52.0
8
416 W
50%
NO
208 W
376
Drama
STORAGE 106
432MAXL
2
45.5
8
364 W
50%
NO
182 W
378
Drama
HALL 111
432MAXL
4
91.0
8
728 W
50%
NO
364 W
379
Drama
PRACTICE ROOM 111
232MAXN
2
52.0
6
312 W
50%
NO
156 W
381
Drama
EXTERIOR
232MAXN
2
52.0
8
416 W
50%
NO
208 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
382
Drama
EXTERIOR
232MAXN
2
52.0
22
1144 W
50%
NO
572 W
383
Drama
EXTERIOR
50W HPS
1
72.0
5
360 W
50%
NO
180 W
385
Humanities
HALL 319
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
386
Humanities
HALL 319
232MAXN
2
52.0
24
1248 W
50%
NO
624 W
387
Humanities
HALL 319
232MAXN
2
52.0
4
208 W
50%
NO
104 W
388
Humanities
OFFICE 323
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
389
Humanities
OFFICE 324
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
390
Humanities
OFFICE 322
232MAXH
2
70.0
4
280 W
50%
NO
140 W
391
Humanities
HALL 319 DISPLAY CASES
232MAXN
2
52.0
3
156 W
50%
NO
78 W
392
Humanities
HALL 326A
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
393
Humanities
OFFICE 318 & 317
232MAXH
2
70.0
4
280 W
50%
NO
140 W
394
Humanities
OFFICE 316
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
395
Humanities
HALL 321
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
396
Humanities
OFFICE 315
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
397
Humanities
OFFICE 314
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
398
Humanities
STORAGE 303A
232MAXH
2
70.0
4
280 W
50%
NO
140 W
400
Humanities
OFFICE 313
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
401
Humanities
OFFICE 312
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
402
Humanities
OFFICE 311
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
403
Humanities
HALL 320
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
404
Humanities
STORAGE 320A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
405
Humanities
OFFICE 310
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
406
Humanities
OFFICE 309
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
407
Humanities
GALLERY 202
232MAXN
2
52.0
9
468 W
50%
NO
234 W
408
Humanities
GALLERY 202
232MAXN
2
52.0
20
1040 W
50%
NO
520 W
409
Humanities
GALLERY 202
232MAXN
2
52.0
6
312 W
50%
NO
156 W
410
Humanities
OFFICE 209
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
411
Humanities
OFFICE 210
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
412
Humanities
OFFICE 211
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
413
Humanities
OFFICE 212
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
414
Humanities
OFFICE 213
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
415
Humanities
OFFICE 214
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
416
Humanities
OFFICE 215
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
417
Humanities
OFFICE 216
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
418
Humanities
OFFICE 217
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
420
Humanities
OFFICE 226
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
421
Humanities
OFFICE 227
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
422
Humanities
OFFICE 252
232MAXH
2
70.0
9
630 W
50%
NO
315 W
423
Humanities
STORAGE 253
232MAXH
2
70.0
8
560 W
50%
NO
280 W
425
Humanities
HALL 242
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
426
Humanities
HALL 242
232MAXN
2
52.0
20
1040 W
50%
NO
520 W
428
Humanities
OFFICE 251
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
429
Humanities
OFFICE 236
232MAXH
2
70.0
2
140 W
50%
Yes
70 W
431
Humanities
OFFICE 324
1
17.0
5
85 W
50%
NO
43 W
433
Humanities
OFFICE 233
1
17.0
6
102 W
50%
NO
51 W
434
Humanities
OFFICE 237
1
17.0
18
306 W
50%
NO
153 W
435
Humanities
OFFICE 237
232MAXN
2
52.0
7
364 W
50%
NO
182 W
436
Humanities
OFFICE 238
232MAXN
2
52.0
4
208 W
50%
NO
104 W
437
Humanities
OFFICE 239
1
17.0
6
102 W
50%
NO
51 W
441
Humanities
HALL 207
232MAXN
2
52.0
4
208 W
50%
NO
104 W
442
Humanities
HALL 207
232MAXN
2
52.0
4
208 W
50%
NO
104 W
443
Humanities
HALL 207
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
444
Humanities
HALL 207
232MAXN
2
52.0
28
1456 W
50%
NO
728 W
447
Humanities
STORAGE 218
232MAXN
2
52.0
8
416 W
50%
NO
208 W
448
Humanities
STORAGE 218
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
449
Humanities
STORAGE 205
232MAXN
2
52.0
4
208 W
50%
NO
104 W
450
Humanities
STORAGE 205
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
451
Humanities
EXTERIOR STAIRS 260
232MAXN
2
52.0
4
208 W
50%
NO
104 W
453
Humanities
ENTRY 101
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
455
Humanities
OFFICE 106
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
456
Humanities
OFFICE 106
232MAXN
2
52.0
4
208 W
50%
NO
104 W
459
Humanities
HALL 114
232MAXN
2
52.0
28
1456 W
50%
NO
728 W
460
Humanities
HALL 114
232MAXN
2
52.0
5
260 W
50%
NO
130 W
462
Humanities
PRINTMAKING 112
232MAXN
2
52.0
20
1040 W
50%
NO
520 W
463
Humanities
ELECTRICAL 117
1
28.0
5
140 W
50%
NO
70 W
467
Humanities
MECHANICAL 118
232MAXN
2
52.0
6
312 W
50%
NO
156 W
468
Humanities
MECHANICAL 118
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
471
Humanities
MECHANICAL 118
232MAXN
2
52.0
1
52 W
50%
NO
26 W
473
Humanities
EXTERIOR SCULPTURE PATO
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
475
IDC
HALL 101
232MAXL
2
46.0
9
414 W
50%
NO
207 W
482
IDC
ELEC EX02
432MAXL
2
45.5
8
364 W
50%
NO
182 W
484
IDC
OFFICE 102A
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
487
IDC
ELEC. RM.
*232MAXL
1
24.0
11
264 W
50%
NO
132 W
488
IDC
HALL208
232MAXL
2
46.0
4
184 W
50%
NO
92 W
491
IDC
OFFICE 324
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
492
IDC
OFFICE 323
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
493
IDC
OFFICE 322
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
494
IDC
OFFICE 321
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
495
IDC
OFFICE 320
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
496
IDC
OFFICE 319
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
499
IDC
HALL 301-3
232MAXN
2
28.0
4
112 W
50%
NO
56 W
502
IDC
CONFERENCE ROOM 335
332MAXL
3
68.0
4
272 W
50%
NO
136 W
503
IDC
OFFICE 336
332MAXL
3
68.0
4
272 W
50%
NO
136 W
504
IDC
OFFICE 337
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
505
IDC
OFFICE 338
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
506
IDC
OFFICE 339
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
507
IDC
HALL 301
232MAXN
2
28.0
7
196 W
50%
NO
98 W
510
IDC
OFFICE 331
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
511
IDC
OFFICE 349
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
512
IDC
WORK ROOM 333
432MAXL
4
91.0
6
546 W
50%
NO
273 W
513
IDC
OFFICES 312
432MAXL
2
45.5
4
182 W
50%
NO
91 W
514
IDC
OFFICES 312
232MAXL
2
46.0
4
184 W
50%
NO
92 W
515
IDC
OFFICES 312
232MAXL
2
46.0
3
138 W
50%
NO
69 W
516
IDC
OFFICE 351
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
517
IDC
HALL 301-1
232MAXN
2
28.0
6
168 W
50%
NO
84 W
520
IDC
OFFICE 326
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
521
IDC
OFFICE 327
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
522
IDC
OFFICE 327
432MAXL
2
45.5
4
182 W
50%
NO
91 W
523
IDC
OFFICE 328
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
524
IDC
OFFICE 340
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
525
IDC
OFFICE 341
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
526
IDC
OFFICE 342
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
528
IDC
OFFICE 329-B
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
529
IDC
OFFICE 330
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
530
IDC
OFFICE 343
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
531
IDC
OFFICE 344
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
532
IDC
OFFICE 345
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
533
IDC
OFFICE 346
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
534
IDC
OFFICE 347
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
538
IDC
EXT 3RD FLOOR
232MAXN
2
52.0
4
208 W
50%
NO
104 W
539
IDC
OFFICE 348
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
540
IDC
OFFICE 350
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
541
IDC
OFFICE 352
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
542
IDC
OFFICE 353
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
543
IDC
OFFICE 354
432MAXL
4
91.0
2
182 W
50%
NO
91 W
544
IDC
OFFICE 355
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
545
IDC
OFFICE 357
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
546
IDC
OFFICE 358
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
547
IDC
OFFICE 359
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
548
IDC
OFFICE 360
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
549
IDC
OFFICE 361
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
550
IDC
OFFICE 362
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
557
IDC
OFFICE 369
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
558
IDC
OFFICE 370
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
559
IDC
OFFICE 371
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
560
IDC
OFFICE 372
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
561
IDC
OFFICE 373
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
562
IDC
OFFICE 374
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
563
IDC
OFFICE 375
232MAXN
2
52.0
1
52 W
50%
NO
26 W
564
IDC
OFFICE 375
432MAXL
4
91.0
3
273 W
50%
NO
137 W
566
IDC
OFFICE 304
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
567
IDC
OFFICE 305
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
568
IDC
OFFICE 306
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
569
IDC
OFFICE 307
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
570
IDC
OFFICE 308
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
571
IDC
OFFICE 309
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
572
IDC
OFFICE 310
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
573
IDC
OFFICE 315
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
574
IDC
OFFICE 316
332MAXL
3
68.0
2
136 W
50%
Yes
68 W
575
IDC
OFFICE 317
432MAXL
4
91.0
3
273 W
50%
NO
137 W
576
IDC
HALL 301-5
232MAXN
2
28.0
1
28 W
50%
NO
14 W
578
IDC
OFFICE 311
232MAXN
2
28.0
2
56 W
50%
Yes
28 W
581
Int Ed
OFFICE 001
432MAXL
2
45.5
4
182 W
50%
NO
91 W
582
Int Ed
OFFICE 002
232MAXL
2
46.0
6
276 W
50%
NO
138 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
584
Int Ed
OFFICE 004
232MAXL
2
46.0
4
184 W
50%
NO
92 W
585
Int Ed
OFFICE 005
232MAXL
2
46.0
6
276 W
50%
NO
138 W
587
Int Ed
CONFRENCE ROOM 003
232MAXL
2
46.0
4
184 W
50%
NO
92 W
589
Int Ed
OFFICE 18
232MAXL
2
46.0
4
184 W
50%
NO
92 W
590
Int Ed
OFFICE 15
232MAXL
2
46.0
4
184 W
50%
NO
92 W
591
Int Ed
COPY ROOM 17
232MAXL
2
46.0
4
184 W
50%
NO
92 W
592
Int Ed
OFFICE 16
232MAXL
2
46.0
4
184 W
50%
NO
92 W
594
Int Ed
OFFICE 13
232MAXL
2
46.0
10
460 W
50%
NO
230 W
596
Int Ed
OFFICE 001
232MAXL
2
28.0
2
56 W
50%
Yes
28 W
597
Int Ed
OFFICE 12
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
598
Int Ed
OFFICE 11
232MAXL
2
46.0
6
276 W
50%
NO
138 W
599
Int Ed
OFFICE 11C
232MAXL
2
46.0
4
184 W
50%
NO
92 W
601
Int Ed
OFFICE 11
232MAXN
2
52.0
1
52 W
50%
NO
26 W
602
Int Ed
OFFICE 11A
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
605
Int Ed
OFFICE 11B
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
607
Int Ed
OFFICE 9
232MAXL
2
46.0
4
184 W
50%
NO
92 W
608
Int Ed
OFFICE 008
232MAXL
2
46.0
4
184 W
50%
NO
92 W
609
Int Ed
OFFICE 19
232MAXL
2
46.0
4
184 W
50%
NO
92 W
610
Int Ed
OFFICE 007
232MAXL
2
46.0
4
184 W
50%
NO
92 W
611
Int Ed
OFFICE 20
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
614
Int Ed
STORAGE 21
232MAXL
2
46.0
4
184 W
50%
NO
92 W
617
LRC
MECH RM 011
1
28.0
8
224 W
50%
NO
112 W
618
LRC
MECH RM 011
1
28.0
4
112 W
50%
NO
56 W
622
LRC
MECH RM 125
1
28.0
4
112 W
50%
NO
56 W
2
52.0
5
260 W
50%
NO
130 W
624 Marine Tech
STORAGE TANK
232MAXN
627 Marine Tech
HALL 103
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
628 Marine Tech
ELECTRICAL ROOM
232MAXN
2
52.0
3
156 W
50%
NO
78 W
629 Marine Tech
OFFICE 207
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
630 Marine Tech
OFFICE 206
232MAXN
2
52.0
4
208 W
50%
NO
104 W
631 Marine Tech
OFFICE 205
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
632 Marine Tech
OFFICE 204
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
633 Marine Tech
OFFICE 203
232MAXN
2
52.0
4
208 W
50%
NO
104 W
635 Marine Tech
EXTERIOR
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
636 Marine Tech
EXTERIOR
232MAXN
2
52.0
3
156 W
50%
NO
78 W
637 Marine Tech
EXTERIOR
232MAXN
2
52.0
11
572 W
50%
NO
286 W
639
OFFICE 301
232MAXH
2
70.0
4
280 W
50%
NO
140 W
Phys Ed
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
640
Phys Ed
COPY 302
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
641
Phys Ed
HALL CO3
232MAXN
2
52.0
7
364 W
50%
NO
182 W
642
Phys Ed
OFFICE 303
232MAXH
2
70.0
4
280 W
50%
NO
140 W
643
Phys Ed
OFFICE 304
232MAXH
2
70.0
4
280 W
50%
NO
140 W
644
Phys Ed
OFFICE 305
232MAXH
2
70.0
4
280 W
50%
NO
140 W
645
Phys Ed
OFFICE 306
232MAXH
2
70.0
4
280 W
50%
NO
140 W
646
Phys Ed
OFFICE 307
232MAXH
2
70.0
4
280 W
50%
NO
140 W
647
Phys Ed
OFFICE 308
232MAXH
2
70.0
4
280 W
50%
NO
140 W
648
Phys Ed
OFFICE 309
232MAXH
2
70.0
4
280 W
50%
NO
140 W
649
Phys Ed
CONFERENCE RM 310
232MAXH
2
70.0
10
700 W
50%
NO
350 W
650
Phys Ed
HALL KO4
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
651
Phys Ed
MECHANICAL ROOM
232MAXN
2
52.0
7
364 W
50%
NO
182 W
652
Phys Ed
MECHANICAL ROOM
232MAXN
2
52.0
5
260 W
50%
NO
130 W
655
Phys Ed
HALL CO1A
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
657
Phys Ed
ELECTRICAL
232MAXN
2
52.0
6
312 W
50%
NO
156 W
659
Phys Ed
PRESS ROOM 300
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
662
Phys Ed
MECH. RM.
*232MAXL
2
46.0
8
368 W
50%
NO
184 W
663
Phys Ed
MECH. RM.
*232MAXL
1
24.0
8
192 W
50%
NO
96 W
668
Phys Ed
HALL C01/311
232MAXN
2
52.0
25
1300 W
50%
NO
650 W
669
Phys Ed
HALL C02
232MAXN
2
52.0
6
312 W
50%
NO
156 W
670
Phys Ed
HALL C02
232MAXN
2
52.0
5
260 W
50%
NO
130 W
673
Phys Ed
EXERCISE ROOM 201
232MAXN
2
52.0
26
1352 W
50%
NO
676 W
676
Phys Ed
OFFICE 202
232MAXN
2
52.0
8
416 W
50%
NO
208 W
677
Phys Ed
OFFICE 203A
232MAXN
2
52.0
3
156 W
50%
NO
78 W
678
Phys Ed
OFFICE 203A
232MAXN
2
52.0
1
52 W
50%
NO
26 W
679
Phys Ed
HALL C02A
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
680
Phys Ed
HALL C02A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
681
Phys Ed
HALL C02A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
683
Phys Ed
HALL C02A
232MAXN
2
52.0
3
156 W
50%
NO
78 W
684
Phys Ed
HALL C02
232MAXN
2
52.0
12
624 W
50%
NO
312 W
685
Phys Ed
HALL C02
232MAXN
2
52.0
6
312 W
50%
NO
156 W
686
Phys Ed
HALL C02
232MAXN
2
52.0
10
520 W
50%
NO
260 W
687
Phys Ed
HALL C02
232MAXN
2
52.0
12
624 W
50%
NO
312 W
688
Phys Ed
HALL C02A DISPLAY
432MAXL
1
22.8
12
274 W
50%
NO
137 W
690
Phys Ed
HALL C02A DISPLAY
232MAXL
1
24.0
6
144 W
50%
NO
72 W
691
Phys Ed
HALL C02A DISPLAY
232MAXL
1
24.0
6
144 W
50%
NO
72 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
234 W
692
Phys Ed
HALL 211A
232MAXN
2
52.0
9
468 W
50%
NO
693
Phys Ed
OFFICE 212
232MAXN
2
52.0
1
52 W
50%
NO
26 W
695
Phys Ed
HALL 212A
232MAXN
2
52.0
6
312 W
50%
NO
156 W
697
Phys Ed
HALL C06A
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
699
Phys Ed
HALL C06
232MAXN
2
52.0
12
624 W
50%
NO
312 W
700
Phys Ed
HALL C08
232MAXN
2
28.0
16
448 W
50%
NO
224 W
703
Phys Ed
ELECTRICAL K04
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
708
Phys Ed
LAUNDRY ROOM 206
232MAXN
2
52.0
12
624 W
50%
NO
312 W
713
Phys Ed
LOCKER ROOM 208
232MAXN
2
52.0
9
468 W
50%
NO
234 W
714
Phys Ed
LOCKER ROOM 208
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
715
Phys Ed
HALL C01A
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
717
Phys Ed
HALL C01
232MAXN
2
52.0
9
468 W
50%
NO
234 W
719
Phys Ed
EQUIPMENT STORAGE 102
232MAXN
2
52.0
6
312 W
50%
NO
156 W
720
Phys Ed
OFFICE 103
232MAXN
2
52.0
4
208 W
50%
NO
104 W
721
Phys Ed
HALL 108A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
723
Phys Ed
HALL 107B
232MAXN
2
52.0
4
208 W
50%
NO
104 W
724
Phys Ed
EQUIPMENT STORAGE 109
232MAXN
2
52.0
25
1300 W
50%
NO
650 W
725
Phys Ed
LAUNDRY ROOM 107
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
726
Phys Ed
OFFICE 110B
232MAXN
2
52.0
1
52 W
50%
NO
26 W
727
Phys Ed
OFFICE 110A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
728
Phys Ed
HALL 114B
232MAXN
2
52.0
4
208 W
50%
NO
104 W
731
Phys Ed
AEROBICS 114
232MAXN
2
52.0
40
2080 W
50%
NO
1040 W
733
Phys Ed
TEAM ROOM 106
232MAXN
2
52.0
4
208 W
50%
NO
104 W
735
Phys Ed
TEAM ROOM 106
232MAXN
2
52.0
16
832 W
50%
NO
416 W
736
Phys Ed
HALL C01B
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
738
Phys Ed
COACHES' RM 105
232MAXN
2
52.0
6
312 W
50%
NO
156 W
739
Phys Ed
EXTERIOR
232MAXL
2
28.0
18
504 W
50%
NO
252 W
740
Phys Ed
WEIGHT TRAINING
*NO WORK
1
458.0
6
2748 W
50%
NO
1374 W
741
Phys Ed
GYM
*NO WORK
1
458.0
42
19236 W
50%
NO
9618 W
742
Phys Ed
EXTERIOR
232MAXN
2
52.0
24
1248 W
50%
NO
624 W
743
Phys Ed
EXTERIOR
232MAXN
2
52.0
8
416 W
50%
NO
208 W
744
Phys Ed
EXTERIOR
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
745
Phys Ed
EXTERIOR
232MAXL
2
28.0
19
532 W
50%
NO
266 W
748
Phys Sci
OFFICE 112
232MAXH
2
70.0
4
280 W
50%
NO
140 W
749
Phys Sci
OFFICE 115
232MAXL
2
46.0
4
184 W
50%
NO
92 W
750
Phys Sci
HALLWAY CO1
232MAXN
2
52.0
12
624 W
50%
NO
312 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
753
Phys Sci
PHYSIC STORAGE RM 120
232MAXN
2
52.0
15
780 W
50%
NO
390 W
754
Phys Sci
PHYSIC STORAGE RM 120
232MAXN
2
52.0
6
312 W
50%
NO
156 W
755
Phys Sci
PHYSIC STORAGE RM 120
232MAXL
2
46.0
6
276 W
50%
NO
138 W
756
Phys Sci
PHYSIC STORAGE RM 120
232MAXH
2
70.0
6
420 W
50%
NO
210 W
757
Phys Sci
TEACHER OFFICE 121
232MAXN
2
52.0
12
624 W
50%
NO
312 W
758
Phys Sci
MECHANICAL RM 129
232MAXN
2
52.0
4
208 W
50%
NO
104 W
760
Phys Sci
1ST FLOOR HALLWAY #1
232MAXN
2
52.0
7
364 W
50%
NO
182 W
761
Phys Sci
1ST FLOOR HALLWAY #2
232MAXN
2
52.0
6
312 W
50%
NO
156 W
762
Phys Sci
1ST FLOOR HALLWAY #3
232MAXN
2
52.0
7
364 W
50%
NO
182 W
764
Phys Sci
1ST FLOOR HALLWAY #5
2
40.0
6
240 W
50%
NO
120 W
767
Phys Sci
ELECTRICAL RM BY 202
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
771
Phys Sci
OFFICE 206
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
772
Phys Sci
OFFICE 210
432MAXL
4
91.0
2
182 W
50%
NO
91 W
773
Phys Sci
OFFICE 212
232MAXN
2
52.0
4
208 W
50%
NO
104 W
774
Phys Sci
OFFICE 213
232MAXN
2
52.0
6
312 W
50%
NO
156 W
777
Phys Sci
OFFICE 216
232MAXN
2
52.0
4
208 W
50%
NO
104 W
778
Phys Sci
OFFICE 217
232MAXN
2
52.0
4
208 W
50%
NO
104 W
779
Phys Sci
OFFICE 218
232MAXN
2
52.0
9
468 W
50%
NO
234 W
780
Phys Sci
2ND FLOOR HALLWAY #1
432MAXL
2
45.5
8
364 W
50%
NO
182 W
781
Phys Sci
2ND FLOOR HALLWAY #2
432MAXL
2
45.5
7
319 W
50%
NO
159 W
782
Phys Sci
2ND FLOOR HALLWAY #2
1
25.0
7
175 W
50%
NO
88 W
783
Phys Sci
2ND FLOOR HALLWAY #3
1
25.0
4
100 W
50%
NO
50 W
784
Phys Sci
2ND FLOOR HALLWAY #4
1
25.0
8
200 W
50%
NO
100 W
787
Phys Sci
LAB STORAGE 300
432MAXL
2
45.5
12
546 W
50%
NO
273 W
788
Phys Sci
STORAGE 102
232MAXN
2
52.0
3
156 W
50%
NO
78 W
789
Phys Sci
STORAGE 102
232MAXN
2
52.0
4
208 W
50%
NO
104 W
790
Phys Sci
MECHANICAL ROOM
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
791
Phys Sci
EXTERIOR
1
25.0
13
325 W
50%
NO
163 W
795 Student Serv
OFFICE 144
432MAXL
2
45.5
4
182 W
50%
NO
91 W
796 Student Serv
OFFICE 144
232MAXL
2
46.0
2
92 W
50%
Yes
46 W
799 Student Serv
OPEN OFFICE AREA 140
232MAXN
2
52.0
9
468 W
50%
NO
234 W
800 Student Serv
OPEN OFFICE AREA 140
232MAXN
2
52.0
7
364 W
50%
NO
182 W
802 Student Serv
DSPS OFFICE 160
232MAXN
2
52.0
8
416 W
50%
NO
208 W
809 Student Serv SECURITY OFFICE RM 180
232MAXN
2
28.0
6
168 W
50%
NO
84 W
810 Student Serv SECURITY OFFICE RM 180A
232MAXN
2
28.0
2
56 W
50%
Yes
28 W
811 Student Serv
232MAXN
2
28.0
4
112 W
50%
NO
56 W
OFFICE 171
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
814 Student Serv
OFFICE 177
332MAXN
3
46.5
2
93 W
50%
Yes
47 W
818 Student Serv
ELECTRICAL RM 110A
232MAXN
2
52.0
4
208 W
50%
NO
104 W
819 Student Serv
ENTRANCE 100
232MAXN
2
52.0
3
156 W
50%
NO
78 W
820 Student Serv
ADMISSION RM 102
232MAXN
2
52.0
10
520 W
50%
NO
260 W
821 Student Serv
ADMISSION RM 102
432MAXL
4
91.0
12
1092 W
50%
NO
546 W
829 Student Serv
OFFICE 111
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
831 Student Serv
OFFICE 111A
232MAXN
2
28.0
2
56 W
50%
Yes
28 W
832 Student Serv
OFFICE 111G
232MAXN
2
28.0
2
56 W
50%
Yes
28 W
833 Student Serv
OFFICE 111H
232MAXN
2
28.0
2
56 W
50%
Yes
28 W
834 Student Serv
HALLWAY 112
232MAXN
2
28.0
4
112 W
50%
NO
56 W
840 Student Serv
OFFICE 129
432MAXL
4
91.0
2
182 W
50%
NO
91 W
842 Student Serv
OFFICE 130
232MAXN
2
52.0
1
52 W
50%
NO
26 W
845 Student Serv
OFFICE 132
432MAXL
4
91.0
2
182 W
50%
NO
91 W
847 Student Serv
OFFICE 134
432MAXL
4
91.0
2
182 W
50%
NO
91 W
857 Student Serv
HALLWAY 139
232MAXN
2
28.0
12
336 W
50%
NO
168 W
858 Student Serv
HALLWAY 139
232MAXN
2
52.0
4
208 W
50%
NO
104 W
859 Student Serv
CAREER CENTER
232MAXN
2
52.0
12
624 W
50%
NO
312 W
861 Student Serv
OFFICE 280A
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
862 Student Serv
OFFICE 280B
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
863 Student Serv
OFFICE 280C
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
864 Student Serv
OFFICE 280D
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
867 Student Serv
OPEN OFFICE AREA 270
232MAXN
2
52.0
4
208 W
50%
NO
104 W
52 W
869 Student Serv
OFFICE 270A
232MAXN
2
52.0
2
104 W
50%
Yes
870 Student Serv
OFFICE 270C
232MAXN
2
52.0
2
104 W
50%
Yes
52 W
871 Student Serv
OFFICE 270D
232MAXN
2
52.0
3
156 W
50%
NO
78 W
873 Student Serv
HALLWAY 248
232MAXN
2
28.0
4
112 W
50%
NO
56 W
874 Student Serv
HALLWAY 248
232MAXN
2
52.0
5
260 W
50%
YES
130 W
876 Student Serv
OFFICE 251
232MAXN
2
52.0
6
312 W
50%
NO
156 W
877 Student Serv
HALLWAY 200
232MAXN
2
28.0
7
196 W
50%
NO
98 W
878 Student Serv
HALLWAY 200
232MAXN
2
52.0
8
416 W
50%
NO
208 W
879 Student Serv
HALLWAY 200
232MAXN
2
52.0
9
468 W
50%
YES
234 W
882 Student Serv
OFFICE 240K
332MAXN
3
46.5
10
465 W
50%
NO
233 W
883 Student Serv
OFFICE 240G
332MAXN
3
46.5
11
512 W
50%
NO
256 W
884 Student Serv
OFFICE 240L
332MAXN
3
46.5
12
558 W
50%
NO
279 W
885 Student Serv
OFFICE 240D
232MAXL
2
46.0
13
598 W
50%
NO
299 W
886 Student Serv
OFFICE 240M
332MAXL
3
68.0
14
952 W
50%
NO
476 W
Serves
#
Bldg
Lamp Data
Area
Size/Type
Fixture Data
Qty
Watts
Qty1
Full Load
Normal
Operation
Load
DR Operation
W
Rewire
Required
Demand
Reduction
(YES/NO)
W
510 W
887 Student Serv
OFFICE 240B
332MAXL
3
68.0
15
1020 W
50%
NO
889 Student Serv
OFFICE 240C
332MAXL
3
68.0
16
1088 W
50%
NO
544 W
890 Student Serv CONFERENCE ROOM 240E
232MAXN
2
52.0
17
884 W
50%
NO
442 W
891 Student Serv CONFERENCE ROOM 240E
232MAXN
2
52.0
18
936 W
50%
NO
468 W
894 Student Serv
OFFICE 240H
332MAXL
3
68.0
19
1292 W
50%
NO
646 W
895 Student Serv
OPEN OFFICE AREA 240
232MAXN
2
52.0
20
1040 W
50%
NO
520 W
896 Student Serv
OPEN OFFICE AREA 240
232MAXN
2
52.0
21
1092 W
50%
YES
546 W
900 Student Serv
OFFICE 213
332MAXL
3
68.0
22
1496 W
50%
NO
748 W
903 Student Serv
OFFICE 211
232MAXL
2
46.0
23
1058 W
50%
NO
529 W
904 Student Serv
OFFICE 214
332MAXL
3
68.0
24
1632 W
50%
NO
816 W
906 Student Serv
HALLWAY CO1
232MAXL
2
46.0
25
1150 W
50%
NO
575 W
908 Student Serv
STAFF LOUNGE 220
1
25.0
26
650 W
50%
NO
325 W
911 Student Serv
STAFF LOUNGE 220
232MAXN
2
28.0
27
756 W
50%
NO
378 W
912 Student Serv
OFFICE 230A
232MAXN
2
52.0
28
1456 W
50%
NO
728 W
915 Student Serv
OFFICE 230C
432MAXL
4
91.0
29
2639 W
50%
NO
1320 W
916 Student Serv
OFFICE 230D
432MAXL
4
91.0
30
2730 W
50%
NO
1365 W
917 Student Serv
OFFICE 230E
432MAXL
4
91.0
31
2821 W
50%
NO
1411 W
919 Student Serv
HALLWAY 210
232MAXN
2
28.0
32
896 W
50%
NO
448 W
921 Student Serv
OFFICE 260
332MAXL
3
68.0
33
2244 W
50%
NO
1122 W
923 Student Serv
OFFICE 260A
332MAXL
3
68.0
34
2312 W
50%
NO
1156 W
930 Student Serv OLD PRINT SHOP (ADDED 5/0
432MAXN
2
51.5
35
1803 W
50%
NO
901 W
931 Student Serv OLD PRINT SHOP (ADDED 5/0
232MAXN
2
52.0
36
1872 W
50%
NO
936 W
932 Student Serv CAMPUS SECURITY (ADDED 5/
432MAXN
2
51.5
37
1906 W
50%
NO
953 W
3,844
225.6 kW
Totals
Note:
(1) Lighting count based on available as-builts and onsite observations.
(2) IIDF rooms, restrooms, and other areas not normally occupied were excluded from the demand reduction calculation.
(3) Classrooms were excluded from the demand reduction calculation due to their particular lighting requirements.
113.5 kW
CALCULATIONS
Demand Response Measure # 6:
Demand Reduction by Fountain Pump Shutdown
Current
Location
Equipment
Qty
HP
Load Factor
Efficiency
Status
Demand Response
Demand kW
Status
Demand kW
*
**
West Campus Water Feature
1
2
90%
85%
ON
1.6 kW
OFF
0.0 kW
East Campus Water Fountain
1
2
90%
85%
ON
1.6 kW
OFF
0.0 kW
Totals
2
* Current: [Demand kW] = [HP] x [Load Factor] x 0.7457 / [Efficiency]
** [Pump kW Reduction] = [Current Demand kW] - [Demand Response Demand kW]
Notes:
(1) Efficiency is based on motor size (HP) and Load Factor
3.2 kW
Pump kW
Reduction
1.6 kW
1.6 kW
3.2 kW
CALCULATIONS
Demand Response Measure # 7
Demand Reduction by Pre-Cool Refrigeration Spaces
Current
Manufacturer
Equipment
Qty
Volts
FLA
Phase
Maximum kW
LRC Coil Company
BC Walk-in Ref
1
115
4.4
1
0.5 kW
LRC Coil Company
BC Walk-in Freezer
1
230
18.8
1
4.3 kW
Larkin
Campus Ctr Ref
1
115
4.4
1
0.5 kW
Demand Response
Load Factor
Diversity
Factor
Average kW
85%
60%
.3 kW
Diversity
Factor
Average kW
***
****
85%
20%
0.1 kW
.2 kW
85%
60%
2.2 kW
85%
85%
60%
.3 kW
85%
20%
0.7 kW
1.5 kW
20%
0.1 kW
.2 kW
**
*
Average kW
Reduction
Load Factor
LRC Coil Company
Campus Ctr Freezer
1
230
2.2
1
0.5 kW
85%
60%
.3 kW
85%
20%
0.1 kW
.2 kW
LRC Coil Company
Campus Ctr Freezer
230
3.3
1
0.8 kW
85%
60%
.4 kW
85%
20%
0.1 kW
.3 kW
Bohn
JSB Café Freezer
1
1
230
5.9
1
1.4 kW
85%
60%
.7 kW
85%
20%
0.2 kW
.5 kW
Bohn
JSB Café Ref
1
115
2.1
1
0.2 kW
85%
60%
.1 kW
85%
20%
0.0 kW
.1 kW
1.4 kW
2.8 kW
Totals
7
* [Maximum kW] = [Quantity] x [Volts] x [FLA] x SQRT[Phase] / 1000
** Current: [Average kW] = [Maximum kW] x [Load Factor]
*** Demand Response: [Average kW] = [Maximum kW] x [Load Factor]
**** [Average kW Reduction] = [Current Average kW] - [Demand Response Average kW]
Notes:
(1) Load Factor = Percentage of maximum electrical equipment load
(2) Diversity Factor = Percentage of continuous running time
8.2 kW
4.2 kW
CALCULATIONS
Demand Response Measure # 8:
Demand Reduction by Beverage Vending Machine Compressor Shutdown
Current
Manufacturer
Equipment
Quantity
HP
Load Factor
Efficiency
Status
Demand Response
Demand kW
Status
Demand kW
*
Vendo (Varies)
Pepsi (Varies)
Outdoor Ref Vending Machine
Indoor Vending/Storage Units
Totals
20
10
30
* Current: [Demand kW] = [HP] x [Load Factor] x 0.7457 / [Efficiency]
** [Pump kW Reduction] = [Current Demand kW] - [Demand Response Demand kW]
Notes:
(1) Efficiency is based on motor size (HP) and Load Factor
(2) Compressor HP based on typical beverage vending machine compressor
1
3
30%
30%
85%
85%
ON
ON
4.5 kW
6.6 kW
11.1 kW
Average kW
Reduction
**
OFF
OFF
0.0 kW
0.0 kW
0.0 kW
4.5 kW
6.6 kW
11.1 kW
APPENDIX
APPENDIX "D" - TRACE 700 Building Energy Simulation Results
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021
© 2013 SC ENGINEERS, INC.
"D"
ELECTRICAL PEAK CHECKSUMS
By SC ENGINEERS
Alternative 1
Santa Barbara City College
Yearly Time of Peak: 15(Hr) 9(Month)
Equipment Description
Cooling Equipment
Air Cooled CH - Scroll
Pckg AC
HP
Sub total
Fan Equipment
Sys 12: IDC Fan Coil
Sys 1: Admin VAV
Sys 2: Admin FC
Sys 3: Campus Center FC
Sys 4: Campus Center Dual Deck
Sys 5: Campus Center Packg RTU-1
Sys 6: Drama/Music HP
Sys 7: Drama/Music Fan Coil
Sys 8: Drama/Music MZU
Sys 9: EBS VAV
Sys 11: Humanities Fan Coil
Sys 13: LRC VAV
Sys 14: OE Pckg AH
Sys 15: PE Heat Pump
Sys 17: PS Fan Coil Htg Only
Sys 18: Stdnt Srv VAV
Sys 19: Admin Pckg AHU
Sys 20: IDC VAV
Sys 21: Portopia HP
Sys 22: BC FC
Sys 23: BC Hydronic AHU
Sys 10: Humanities VAV
Sub total
Miscellaneous
Misc Equipment
Lights
Base Utilities
Sub total
Total
Alternative 2
Electrical Demand
(kw)
Percent of Total
(%)
340.64
152.78
338.89
20.08
9.01
19.98
832.31
49.07
0.15
8.71
3.41
1.00
6.79
3.79
7.05
0.56
4.54
20.71
1.87
11.56
2.01
1.07
0.62
13.86
8.46
5.25
62.29
7.32
6.94
57.40
0.01
0.51
0.20
0.06
0.40
0.22
0.42
0.03
0.27
1.22
0.11
0.68
0.12
0.06
0.04
0.82
0.50
0.31
3.67
0.43
0.41
3.38
235.36
13.87
314.40
299.07
15.00
18.54
17.63
0.88
628.47
37.05
1,696.14
100
Electrical Demand
(kw)
Percent of Total
(%)
338.89
20.16
SBCC CHWR
Yearly Time of Peak: 15(Hr) 9(Month)
Equipment Description
Cooling Equipment
HP
Project Name:
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Dataset Name: SBCC TRACE.TRC
Alternative - 2 Elect. Peak Checksums Report Page 1 of 4
ELECTRICAL PEAK CHECKSUMS
By SC ENGINEERS
DR
Pckg AC
325.69
152.78
19.37
9.09
817.36
48.62
0.15
8.71
3.41
1.00
6.79
3.79
7.05
0.56
4.54
20.71
1.87
11.56
2.01
1.07
0.62
13.86
8.46
5.25
62.29
7.32
6.94
57.40
0.01
0.52
0.20
0.06
0.40
0.23
0.42
0.03
0.27
1.23
0.11
0.69
0.12
0.06
0.04
0.82
0.50
0.31
3.71
0.44
0.41
3.41
235.36
13.99
314.40
299.07
15.00
18.70
17.79
0.89
628.47
37.38
1,681.19
100
Electrical Demand
(kw)
Percent of Total
(%)
329.76
165.53
373.45
16.86
8.46
19.09
868.74
44.41
0.16
6.10
3.88
2.05
0.01
0.31
0.20
0.10
Sub total
Fan Equipment
Sys 12: IDC Fan Coil
Sys 1: Admin VAV
Sys 2: Admin FC
Sys 3: Campus Center FC
Sys 4: Campus Center Dual Deck
Sys 5: Campus Center Packg RTU-1
Sys 6: Drama/Music HP
Sys 7: Drama/Music Fan Coil
Sys 8: Drama/Music MZU
Sys 9: EBS VAV
Sys 11: Humanities Fan Coil
Sys 13: LRC VAV
Sys 14: OE Pckg AH
Sys 15: PE Heat Pump
Sys 17: PS Fan Coil Htg Only
Sys 18: Stdnt Srv VAV
Sys 19: Admin Pckg AHU
Sys 20: IDC VAV
Sys 21: Portopia HP
Sys 22: BC FC
Sys 23: BC Hydronic AHU
Sys 10: Humanities VAV
Sub total
Miscellaneous
Misc Equipment
Lights
Base Utilities
Sub total
Total
Alternative 3
SBCC Class Temp Reduction
Yearly Time of Peak: 19(Hr) 7(Month)
Equipment Description
Cooling Equipment
Main
Pckg AC
HP
Sub total
Fan Equipment
Sys 12: IDC Fan Coil
Sys 1: Admin VAV
Sys 2: Admin FC
Sys 3: Campus Center FC
Project Name:
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Dataset Name: SBCC TRACE.TRC
Alternative - 3 Elect. Peak Checksums Report Page 2 of 4
ELECTRICAL PEAK CHECKSUMS
By SC ENGINEERS
Sys 4: Campus Center Dual Deck
Sys 5: Campus Center Packg RTU-1
Sys 6: Drama/Music HP
Sys 7: Drama/Music Fan Coil
Sys 8: Drama/Music MZU
Sys 9: EBS VAV
Sys 11: Humanities Fan Coil
Sys 13: LRC VAV
Sys 14: OE Pckg AH
Sys 15: PE Heat Pump
Sys 17: PS Fan Coil Htg Only
Sys 18: Stdnt Srv VAV
Sys 19: Admin Pckg AHU
Sys 20: IDC VAV
Sys 21: Portopia HP
Sys 22: BC FC
Sys 23: BC Hydronic AHU
Sys 10: Humanities VAV
Sub total
Miscellaneous
Misc Equipment
Lights
Base Utilities
Sub total
Total
Alternative 4
6.79
3.80
7.07
0.64
5.75
24.96
2.69
10.71
3.44
1.11
0.60
17.08
14.41
4.74
87.21
8.68
7.85
60.72
0.35
0.19
0.36
0.03
0.29
1.28
0.14
0.55
0.18
0.06
0.03
0.87
0.74
0.24
4.46
0.44
0.40
3.10
280.44
14.33
284.71
256.95
265.00
14.56
13.14
13.55
806.66
41.25
1,955.84
100
Electrical Demand
(kw)
Percent of Total
(%)
373.45
333.00
165.53
19.06
16.99
8.45
871.98
44.50
0.16
6.43
3.88
2.05
6.79
3.80
7.07
0.64
5.75
24.96
2.69
10.71
3.44
0.01
0.33
0.20
0.10
0.35
0.19
0.36
0.03
0.29
1.27
0.14
0.55
0.18
SBCC Data Rm TR
Yearly Time of Peak: 19(Hr) 7(Month)
Equipment Description
Cooling Equipment
HP
Main
Pckg AC
Sub total
Fan Equipment
Sys 12: IDC Fan Coil
Sys 1: Admin VAV
Sys 2: Admin FC
Sys 3: Campus Center FC
Sys 4: Campus Center Dual Deck
Sys 5: Campus Center Packg RTU-1
Sys 6: Drama/Music HP
Sys 7: Drama/Music Fan Coil
Sys 8: Drama/Music MZU
Sys 9: EBS VAV
Sys 11: Humanities Fan Coil
Sys 13: LRC VAV
Sys 14: OE Pckg AH
Project Name:
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Dataset Name: SBCC TRACE.TRC
Alternative - 4 Elect. Peak Checksums Report Page 3 of 4
ELECTRICAL PEAK CHECKSUMS
By SC ENGINEERS
Sys 15: PE Heat Pump
Sys 17: PS Fan Coil Htg Only
Sys 18: Stdnt Srv VAV
Sys 19: Admin Pckg AHU
Sys 20: IDC VAV
Sys 21: Portopia HP
Sys 22: BC FC
Sys 23: BC Hydronic AHU
Sys 10: Humanities VAV
Sub total
Miscellaneous
Lights
Base Utilities
Misc Equipment
Sub total
Total
1.11
0.60
17.08
14.41
4.74
87.21
8.68
7.85
60.72
0.06
0.03
0.87
0.74
0.24
4.45
0.44
0.40
3.10
280.77
14.33
256.95
265.00
284.71
13.11
13.52
14.53
806.66
41.16
1,959.41
100
Project Name:
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Dataset Name: SBCC TRACE.TRC
Alternative - 4 Elect. Peak Checksums Report Page 4 of 4
ENERGY CONSUMPTION SUMMARY
By SC ENGINEERS
Elect
Cons.
(kWh)
Gas
Cons.
(kBtu)
% of Total
Building
Energy
Total Building
Energy
(kBtu/yr)
Total Source
Energy*
(kBtu/yr)
Alternative 1
Primary heating
Primary heating
Other Htg Accessories
Heating Subtotal
41,060
37,612
78,672
2,119,439
2,119,439
8.3 %
0.5 %
8.7 %
2,259,578
128,369
2,387,947
2,651,448
385,144
3,036,592
Primary cooling
Cooling Compressor
Tower/Cond Fans
Condenser Pump
Other Clg Accessories
Cooling Subtotal....
944,597
134,802
6,590
1,085,989
11.8
1.7
0.0
0.1
13.6
%
%
%
%
%
3,223,909
460,078
0
22,492
3,706,479
9,672,694
1,380,373
0
67,483
11,120,549
531,787
212,765
1,317,650
2,062,202
6.7
2.7
16.5
25.8
%
%
%
%
1,814,990
726,167
4,497,139
7,038,296
5,445,516
2,178,718
13,492,767
21,117,000
1,834,367
22.9 %
6,260,693
18,783,956
2,319,306
29.0 %
7,915,790
23,749,744
0.0 %
0
0
100.0 %
27,309,205
77,807,848
Auxiliary
Supply Fans
Pumps
Stand-alone Base Utilities
Aux Subtotal....
Lighting
Lighting
Receptacle
Receptacles
Cogeneration
Cogeneration
Totals
Totals**
7,380,535
2,119,439
* Note: Resource Utilization factors are included in the Total Source Energy value.
** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total.
Project Name:
Dataset Name: SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Energy Consumption Summary report page 1
ENERGY CONSUMPTION SUMMARY
By SC ENGINEERS
Elect
Cons.
(kWh)
Gas
Cons.
(kBtu)
% of Total
Building
Energy
Total Building
Energy
(kBtu/yr)
Total Source
Energy*
(kBtu/yr)
Alternative 2
Primary heating
Primary heating
Other Htg Accessories
Heating Subtotal
41,060
37,612
78,672
2,119,439
2,119,439
8.3 %
0.5 %
8.8 %
2,259,578
128,369
2,387,947
2,651,448
385,144
3,036,592
Primary cooling
Cooling Compressor
Tower/Cond Fans
Condenser Pump
Other Clg Accessories
Cooling Subtotal....
928,848
134,376
6,590
1,069,814
11.6
1.7
0.0
0.1
13.4
%
%
%
%
%
3,170,157
458,626
0
22,492
3,651,275
9,511,421
1,376,015
0
67,483
10,954,919
531,787
212,765
1,317,650
2,062,202
6.7
2.7
16.5
25.8
%
%
%
%
1,814,990
726,167
4,497,139
7,038,296
5,445,516
2,178,718
13,492,767
21,117,000
1,834,367
23.0 %
6,260,693
18,783,956
2,319,306
29.0 %
7,915,790
23,749,744
0.0 %
0
0
100.0 %
27,254,001
77,642,216
Auxiliary
Supply Fans
Pumps
Stand-alone Base Utilities
Aux Subtotal....
Lighting
Lighting
Receptacle
Receptacles
Cogeneration
Cogeneration
Totals
Totals**
7,364,361
2,119,439
* Note: Resource Utilization factors are included in the Total Source Energy value.
** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total.
Project Name:
Dataset Name: SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Energy Consumption Summary report page 1
ENERGY CONSUMPTION SUMMARY
By SC ENGINEERS
Elect
Cons.
(kWh)
Gas
Cons.
(kBtu)
% of Total
Building
Energy
Total Building
Energy
(kBtu/yr)
Total Source
Energy*
(kBtu/yr)
Alternative 3
Primary heating
Primary heating
Other Htg Accessories
Heating Subtotal
40,315
38,485
78,800
2,109,047
2,109,047
8.4 %
0.5 %
8.9 %
2,246,642
131,348
2,377,991
2,632,878
394,084
3,026,962
Primary cooling
Cooling Compressor
Tower/Cond Fans
Condenser Pump
Other Clg Accessories
Cooling Subtotal....
841,834
122,858
6,587
971,279
10.7
1.6
0.0
0.1
12.3
%
%
%
%
%
2,873,178
419,315
0
22,481
3,314,974
8,620,397
1,258,070
0
67,448
9,945,915
514,000
216,644
1,317,650
2,048,294
6.5
2.8
16.7
26.0
%
%
%
%
1,754,281
739,407
4,497,139
6,990,828
5,263,371
2,218,443
13,492,767
20,974,580
1,834,367
23.3 %
6,260,693
18,783,956
2,319,306
29.5 %
7,915,790
23,749,744
0.0 %
0
0
100.0 %
26,860,275
76,481,152
Auxiliary
Supply Fans
Pumps
Stand-alone Base Utilities
Aux Subtotal....
Lighting
Lighting
Receptacle
Receptacles
Cogeneration
Cogeneration
Totals
Totals**
7,252,045
2,109,047
* Note: Resource Utilization factors are included in the Total Source Energy value.
** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total.
Project Name:
Dataset Name: SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Energy Consumption Summary report page 1
ENERGY CONSUMPTION SUMMARY
By SC ENGINEERS
Elect
Cons.
(kWh)
Gas
Cons.
(kBtu)
% of Total
Building
Energy
Total Building
Energy
(kBtu/yr)
Total Source
Energy*
(kBtu/yr)
Alternative 4
Primary heating
Primary heating
Other Htg Accessories
Heating Subtotal
40,315
38,485
78,800
2,109,040
2,109,040
8.4 %
0.5 %
8.9 %
2,246,636
131,348
2,377,984
2,632,871
394,084
3,026,955
Primary cooling
Cooling Compressor
Tower/Cond Fans
Condenser Pump
Other Clg Accessories
Cooling Subtotal....
838,964
122,530
6,587
968,081
10.7
1.6
0.0
0.1
12.3
%
%
%
%
%
2,863,385
418,195
0
22,481
3,304,060
8,591,014
1,254,710
0
67,448
9,913,172
513,328
216,644
1,317,650
2,047,623
6.5
2.8
16.8
26.0
%
%
%
%
1,751,989
739,407
4,497,139
6,988,536
5,256,493
2,218,443
13,492,767
20,967,702
1,834,367
23.3 %
6,260,693
18,783,956
2,319,306
29.5 %
7,915,790
23,749,744
0.0 %
0
0
100.0 %
26,847,063
76,441,528
Auxiliary
Supply Fans
Pumps
Stand-alone Base Utilities
Aux Subtotal....
Lighting
Lighting
Receptacle
Receptacles
Cogeneration
Cogeneration
Totals
Totals**
7,248,176
2,109,040
* Note: Resource Utilization factors are included in the Total Source Energy value.
** Note: This report can display a maximum of 7 utilities. If additional utilities are used, they will be included in the total.
Project Name:
Dataset Name: SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Energy Consumption Summary report page 1
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
Electric (kWh)
Peak (kW)
155,785.6
300.2
140,710.4
300.2
155,825.9
300.2
150,753.8
300.2
155,805.8
300.2
150,794.1
300.2
155,765.6
300.2
155,825.9
300.2
150,753.9
300.2
155,805.9
300.2
150,774.0
300.2
155,765.6
300.2
1,834,366.4
300.2
Electric (kWh)
Peak (kW)
196,983.9
315.2
177,920.8
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,623.4
315.2
196,987.6
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,627.1
315.2
196,987.6
315.2
2,319,305.5
315.2
3.0
0.1
1.0
0.0
2.4
0.0
10.1
0.1
16.3
0.1
23.8
0.1
37.7
0.2
39.2
0.2
43.1
0.2
10.2
0.1
9.2
0.1
1.9
0.1
197.8
0.2
60,450.0
150.0
54,600.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
711,750.0
150.0
11,160.0
15.0
10,080.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
131,400.0
15.0
40,300.0
100.0
36,400.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
474,500.0
100.0
57,154.1
275.3
55,607.7
267.6
58,909.1
290.6
46,270.8
250.9
24,784.6
210.2
5,482.2
159.9
390,288.9
290.6
Lights
Misc. Ld
Cooling Coil Condensate
Recoverable Water (1000gal)
Peak (1000gal/Hr)
Bsu 1: Parking lot lights
Electric (kWh)
Peak (kW)
Bsu 2: Decorative Fountains
Electric (kWh)
Peak (kW)
Bsu 3: Stadium Lights
Electric (kWh)
Peak (kW)
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Air Cooled CH - Scroll [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW]
Electric (kWh)
Peak (kW)
7,804.3
163.6
16,897.3
198.9
17,551.9
187.1
17,618.9
187.3
38,818.7
236.9
(Cooling Equipment)
43,389.2
233.7
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
1,017.9
19.2
1,886.1
25.7
2,043.9
23.1
2,148.2
24.5
4,323.2
32.5
4,927.6
32.2
6,781.5
36.6
6,568.6
36.0
7,167.1
38.0
4,925.9
32.9
2,724.9
27.8
736.5
18.3
45,251.4
38.0
7,852.7
18.7
8,114.5
18.7
8,413.7
18.7
9,273.7
18.7
9,853.3
18.7
9,535.5
18.7
8,694.1
18.7
8,413.7
18.7
8,114.5
18.7
101,823.9
18.7
(Misc Accessory Equipment)
8,114.5
18.7
SBCC TRACE.TRC
7,329.2
18.7
8,114.5
18.7
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 1 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
434.0
1.0
450.0
1.0
496.0
1.0
527.0
1.0
510.0
1.0
465.0
1.0
450.0
1.0
434.0
1.0
5,446.0
1.0
25,561.1
137.0
24,413.2
133.6
24,620.3
141.0
17,356.0
123.9
11,005.1
94.9
6,311.4
65.0
186,244.5
141.0
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Cntl panel & interlocks - 1 KW (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
434.0
1.0
392.0
1.0
434.0
1.0
420.0
1.0
Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons]
Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW]
Electric (kWh)
Peak (kW)
7,195.2
68.2
8,442.3
85.9
10,275.2
85.6
(Cooling Equipment)
12,448.5
92.4
18,670.5
119.8
19,945.8
117.9
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW]
Electric (kWh)
Peak (kW)
1,000.7
9.1
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
1,155.4
11.2
1,414.1
11.3
1,720.8
12.3
2,537.8
15.5
2,713.7
15.4
3,435.7
17.5
3,294.8
17.2
3,299.1
17.9
2,311.1
15.6
1,501.2
12.3
879.5
8.7
25,263.9
17.9
43.4
0.1
42.0
0.1
43.4
0.1
43.4
0.1
42.0
0.1
43.4
0.1
42.0
0.1
43.4
0.1
511.0
0.1
(Misc Accessory Equipment)
43.4
0.1
39.2
0.1
43.4
0.1
42.0
0.1
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW]
Electric (kWh)
Peak (kW)
10,591.2
143.5
14,300.4
198.8
19,335.6
209.3
HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW]
Electric (kWh)
Peak (kW)
HP
7,170.9
252.5
3,032.1
243.8
3,580.8
215.9
26,810.3
228.0
39,915.7
283.1
42,346.6
282.8
(Cooling Equipment - Cooling Mode)
53,407.1
308.1
50,651.4
296.9
49,940.1
297.2
32,736.0
238.8
18,821.8
217.2
9,207.4
139.5
368,063.4
308.1
(Cooling Equipment - Heating Mode)
1,918.0
161.8
1,826.4
157.6
603.9
135.3
255.1
115.0
258.7
115.0
416.7
125.9
3,097.9
169.0
4,591.5
217.4
14,308.3
282.6
41,060.4
282.6
126.1
1.1
108.8
0.8
102.7
0.8
104.2
0.8
99.5
1.0
146.1
1.8
188.1
2.0
173.6
1.7
1,711.5
2.0
(Cooling Equipment - Heat Recovered From Condenser Loop)
Heat Recovered (therms)
Peak (therms/Hr)
149.7
1.0
153.1
1.1
194.6
1.5
165.1
1.9
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW]
Electric (kWh)
Peak (kW)
2,580.6
25.9
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
SBCC TRACE.TRC
61.3
0.1
2,581.9
31.3
3,457.2
32.1
4,544.0
34.6
6,730.0
43.3
7,004.2
43.2
8,748.4
47.2
8,307.1
45.4
8,182.2
45.5
5,594.0
40.0
3,492.1
33.2
3,065.0
25.1
64,286.5
47.2
62.5
0.1
57.4
0.1
52.8
0.1
55.1
0.1
55.3
0.1
61.1
0.1
58.3
0.1
74.4
0.1
703.8
0.1
(Misc Accessory Equipment)
48.1
0.1
57.0
0.1
60.5
0.1
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 2 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh]
Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms]
Gas (therms)
Peak (therms/Hr)
Cnst vol cnd water pump
Electric (kWh)
Peak (kW)
Boiler forced draft fan
2,537.3
13.8
2,138.1
11.3
1,925.6
10.4
10,457.4
14.1
1,972.2
2.7
Electric (kWh)
Peak (kW)
Aug
Sept
Oct
Nov
Dec
Total
(Heating Equipment)
923.2
5.7
734.5
4.2
460.1
3.1
357.8
2.1
366.6
2.2
401.2
2.9
1,070.3
6.5
1,470.7
8.0
2,689.4
11.3
15,074.7
13.8
9,445.4
14.1
10,457.4
14.1
10,120.0
14.1
8,714.5
14.1
8,433.4
14.1
8,053.9
14.1
8,377.2
14.1
7,590.0
14.1
8,714.5
14.1
10,120.1
14.1
10,457.4
14.1
110,941.0
14.1
372.0
0.5
1,781.3
2.7
1,972.2
2.7
1,908.5
2.7
1,643.5
2.7
1,590.5
2.7
1,518.9
2.7
1,579.9
2.7
1,431.4
2.7
1,643.5
2.7
1,908.5
2.7
1,972.2
2.7
20,922.4
2.7
310.0
0.5
300.0
0.5
286.5
0.5
298.0
0.5
270.0
0.5
310.0
0.5
360.0
0.5
372.0
0.5
3,946.5
0.5
(Misc Accessory Equipment)
336.0
0.5
372.0
0.5
360.0
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms]
Gas (therms)
Peak (therms/Hr)
568.0
4.3
471.9
3.5
438.2
3.1
(Heating Equipment)
232.5
2.2
168.2
1.7
110.8
1.3
74.6
1.0
75.9
0.9
74.7
0.9
222.3
2.6
326.7
3.0
588.0
3.5
3,351.6
4.3
731.9
1.0
690.3
1.0
617.6
1.0
580.1
1.0
649.8
1.0
592.6
1.0
498.0
1.0
699.7
1.0
773.5
1.0
8,079.1
1.0
332.0
0.5
297.0
0.5
279.0
0.5
312.5
0.5
285.0
0.5
239.5
0.5
336.5
0.5
372.0
0.5
3,885.5
0.5
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
773.5
1.0
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
372.0
0.5
698.6
1.0
773.5
1.0
(Misc Accessory Equipment)
336.0
0.5
372.0
0.5
352.0
0.5
Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh]
Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms]
Gas (therms)
Peak (therms/Hr)
799.1
14.4
1,328.8
15.4
640.2
13.8
(Heating Equipment)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2,768.1
15.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
589.6
2.5
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
July
(Misc Accessory Equipment)
Cntl panel & interlocks - 0.5 KW
Boiler forced draft fan
June
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
Boiler forced draft fan
May
SBCC TRACE.TRC
154.9
2.5
279.8
2.5
154.9
2.5
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 3 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
118.0
0.5
1,934.3
8.3
2,127.3
8.7
2,044.4
8.7
1,965.5
8.7
2,011.2
8.7
1,991.1
8.5
2,334.1
8.7
24,698.3
8.7
586.3
3.3
663.8
3.4
653.2
3.5
640.3
3.7
631.5
3.6
545.5
3.2
568.9
3.1
7,248.5
3.7
372.9
2.1
321.5
1.8
282.7
1.4
320.4
1.1
302.5
1.8
379.1
1.4
4,181.6
2.2
2,424.9
6.8
2,426.1
6.8
2,342.4
6.8
2,291.7
6.8
2,009.3
6.8
2,041.1
6.8
26,422.4
6.8
1,261.4
3.8
1,232.4
3.8
1,166.2
3.8
1,055.3
3.7
905.1
3.3
798.1
3.0
12,346.9
3.8
1,863.2
7.0
1,823.6
6.9
1,801.3
7.4
1,733.4
7.2
1,483.3
6.6
1,696.1
6.1
20,258.4
7.4
Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh]
Cntl panel & interlocks - 0.5 KW (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
31.0
0.5
56.0
0.5
31.0
0.5
0.0
0.0
Sys 1: Admin VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW]
Electric (kWh)
Peak (kW)
2,366.7
8.7
2,023.1
8.7
2,032.4
8.4
1,816.3
8.7
Sys 2: Admin FC
Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW]
Electric (kWh)
Peak (kW)
578.6
3.3
573.3
3.2
620.7
3.0
(Main Clg Fan)
549.6
3.2
Sys 3: Campus Center FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW]
Electric (kWh)
Peak (kW)
336.9
1.4
358.8
1.5
381.9
1.5
313.6
1.6
Sys 4: Campus Center Dual Deck
AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW]
Electric (kWh)
Peak (kW)
2,064.2
6.0
1,863.1
6.8
2,161.8
6.8
2,104.7
6.8
Sys 5: Campus Center Packg RTU-1
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW]
Electric (kWh)
Peak (kW)
825.8
3.3
787.7
3.4
945.1
3.5
1,052.6
3.6
Sys 6: Drama/Music HP
AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW]
Electric (kWh)
Peak (kW)
1,596.5
6.0
1,580.5
6.5
1,705.2
5.9
(Main Clg Fan)
2,051.9
8.7
1,560.5
6.1
636.8
3.3
(Main Clg Fan)
429.0
2.1
382.5
2.2
(Main Clg Fan)
2,427.7
6.8
2,265.5
6.8
(Main Clg Fan)
1,148.3
3.8
1,169.0
3.8
(Main Clg Fan)
1,752.8
6.8
1,662.2
6.6
Sys 7: Drama/Music Fan Coil
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 4 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 7: Drama/Music Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW]
Electric (kWh)
Peak (kW)
111.6
0.6
94.6
0.6
96.4
0.6
May
766.5
4.6
731.5
4.4
826.7
4.1
68.8
0.5
857.8
4.6
2,766.0
12.0
2,664.3
16.8
2,867.7
17.4
2,945.8
18.1
9,536.2
43.5
9,096.7
50.5
9,855.1
44.9
8,773.8
38.5
Sys 11: Humanities Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW]
Electric (kWh)
Peak (kW)
221.6
2.3
256.6
2.2
331.3
2.4
Electric (kWh)
Peak (kW)
24.1
0.1
24.5
0.1
31.1
0.1
3,185.3
11.6
2,814.6
11.6
2,895.4
11.6
Nov
Dec
Total
66.0
0.5
78.2
0.5
73.8
0.6
73.3
0.6
80.4
0.6
83.2
0.6
110.0
0.6
996.6
0.6
1,071.9
4.4
1,062.9
4.5
1,046.1
4.8
969.6
4.7
787.8
4.5
697.9
3.5
10,771.4
4.8
4,158.9
25.0
3,964.9
23.5
3,790.5
22.8
3,131.2
21.5
2,416.5
15.9
2,859.8
12.1
38,717.2
25.0
9,796.9
39.8
11,124.9
44.9
11,138.7
48.1
11,616.0
57.4
10,518.5
61.3
8,480.1
51.4
9,285.7
41.7
119,088.3
61.3
447.0
2.7
479.0
2.7
444.6
2.6
384.9
2.6
338.5
2.2
244.5
2.1
220.2
2.2
4,178.9
2.7
47.0
0.2
51.5
0.2
49.3
0.2
45.8
0.2
38.6
0.2
30.3
0.1
22.9
0.1
449.0
0.2
2,208.9
10.9
2,226.5
11.0
2,291.2
11.6
2,479.2
11.6
2,658.7
11.6
3,315.0
11.6
30,732.7
11.6
962.6
4.1
3,627.0
23.3
(Main Clg Fan)
456.0
2.7
(Main Clg Fan)
38.9
0.1
45.2
0.2
Sys 13: LRC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW]
Electric (kWh)
Peak (kW)
Oct
(Main Clg Fan)
9,865.7
41.9
354.7
2.5
Sys 12: IDC Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW]
Sept
(Main Clg Fan)
3,524.6
23.7
Sys 10: Humanities VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW]
Electric (kWh)
Peak (kW)
Aug
(Main Clg Fan)
990.1
4.4
Sys 9: EBS VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
60.2
0.6
Sys 8: Drama/Music MZU
90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW]
Electric (kWh)
Peak (kW)
June
2,192.9
7.7
(Main Clg Fan)
2,379.9
9.9
2,085.2
9.3
Sys 14: OE Pckg AH
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 5 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
Sys 14: OE Pckg AH
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW]
Electric (kWh)
Peak (kW)
354.9
1.8
353.2
1.9
362.3
1.6
309.8
1.3
313.0
1.3
348.9
1.4
391.3
2.2
37.2
1.3
12.1
0.4
3.3
0.1
353.5
3.1
Electric (kWh)
Peak (kW)
301.1
0.8
273.4
0.8
301.8
0.8
0.3
0.0
3,465.7
13.6
3,054.7
12.9
3,467.3
15.2
289.8
0.8
3,005.2
12.4
1,234.1
5.2
1,217.7
6.2
1,399.7
6.1
1,519.7
6.0
Sys 20: IDC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW]
Electric (kWh)
Peak (kW)
1,258.8
4.4
1,142.1
5.1
1,287.6
4.6
Nov
Dec
Total
426.7
2.4
429.5
2.2
449.1
2.1
403.5
2.2
315.8
2.0
365.9
1.7
4,555.4
2.4
444.2
3.4
380.1
3.2
353.5
3.2
370.1
1.7
309.0
1.0
273.1
1.2
4,103.2
3.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.3
0.0
0.4
0.0
31.4
0.4
85.5
1.3
285.7
0.8
315.4
0.8
317.5
0.8
305.0
0.8
293.1
0.8
290.8
0.8
305.5
0.8
3,565.2
0.8
3,552.1
16.4
3,388.5
15.5
3,285.0
15.0
3,450.1
16.6
3,218.2
17.1
3,314.7
13.8
39,813.8
17.1
2,165.1
10.0
1,934.5
8.8
1,737.1
8.6
1,568.4
7.7
1,263.9
5.9
1,187.8
4.9
19,055.3
10.2
1,440.4
4.6
1,460.0
4.9
1,459.7
5.4
1,429.3
5.4
1,290.5
5.3
1,220.3
4.6
15,977.2
5.4
381.4
2.2
342.0
3.3
1,297.2
4.5
(Main Clg Fan)
3,374.4
15.5
Sys 19: Admin Pckg AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW]
Electric (kWh)
Peak (kW)
Oct
(Main Clg Fan)
286.2
0.8
Sys 18: Stdnt Srv VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW]
Electric (kWh)
Peak (kW)
Sept
(Main Clg Fan)
0.5
0.0
Sys 17: PS Fan Coil Htg Only
Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW]
Aug
(Main Clg Fan)
306.1
1.0
Sys 16: PE VAV Htg Only
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
322.0
1.5
Sys 15: PE Heat Pump
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW]
Electric (kWh)
Peak (kW)
June
3,237.9
15.2
(Main Clg Fan)
1,888.2
9.1
1,939.2
10.2
(Main Clg Fan)
1,362.7
4.6
1,328.7
4.4
Sys 21: Portopia HP
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 6 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 1
Santa Barbara City College
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
Sys 21: Portopia HP
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW]
Electric (kWh)
Peak (kW)
8,120.3
41.6
8,501.0
50.6
8,501.8
49.5
7,807.4
48.6
Sys 22: BC FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW]
Electric (kWh)
Peak (kW)
1,899.4
7.4
1,781.9
7.7
1,948.2
6.8
1,525.5
6.2
Sys 23: BC Hydronic AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
1,354.9
5.1
SBCC TRACE.TRC
1,238.5
5.9
1,258.3
5.4
1,012.3
4.7
June
July
Aug
Sept
Oct
Nov
Dec
Total
11,268.1
67.5
10,776.1
64.4
10,538.1
66.9
9,078.9
62.7
6,961.7
49.0
8,077.0
39.4
109,493.0
67.5
1,716.5
6.9
1,704.0
7.4
1,797.4
8.2
1,853.2
8.1
1,548.4
7.9
1,842.4
7.3
21,001.6
8.2
1,150.2
5.8
1,143.8
6.1
1,177.1
7.3
1,238.2
7.3
1,068.3
6.1
1,233.7
5.0
14,047.1
7.3
(Main Clg Fan)
10,073.5
63.2
9,789.2
61.9
(Main Clg Fan)
1,810.9
6.4
1,573.8
6.5
(Main Clg Fan)
1,139.8
5.3
1,032.1
5.0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 1 Equipment Energy Consumption report page 7 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
Electric (kWh)
Peak (kW)
155,785.6
300.2
140,710.4
300.2
155,825.9
300.2
150,753.8
300.2
155,805.8
300.2
150,794.1
300.2
155,765.6
300.2
155,825.9
300.2
150,753.9
300.2
155,805.9
300.2
150,774.0
300.2
155,765.6
300.2
1,834,366.4
300.2
Electric (kWh)
Peak (kW)
196,983.9
315.2
177,920.8
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,623.4
315.2
196,987.6
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,627.1
315.2
196,987.6
315.2
2,319,305.5
315.2
3.0
0.1
1.0
0.0
2.4
0.0
10.1
0.1
16.3
0.1
23.8
0.1
37.7
0.2
39.2
0.2
43.1
0.2
10.2
0.1
9.2
0.1
1.9
0.1
197.8
0.2
60,450.0
150.0
54,600.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
711,750.0
150.0
11,160.0
15.0
10,080.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
131,400.0
15.0
40,300.0
100.0
36,400.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
474,500.0
100.0
15,652.3
209.5
15,607.9
201.3
16,925.7
198.5
7,968.6
179.6
3,907.9
138.7
401.0
112.9
83,193.7
209.5
Lights
Misc. Ld
Cooling Coil Condensate
Recoverable Water (1000gal)
Peak (1000gal/Hr)
Bsu 1: Parking lot lights
Electric (kWh)
Peak (kW)
Bsu 2: Decorative Fountains
Electric (kWh)
Peak (kW)
Bsu 3: Stadium Lights
Electric (kWh)
Peak (kW)
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Main [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] (Cooling Equipment)
Electric (kWh)
Peak (kW)
677.0
113.5
1,285.4
128.4
1,353.1
125.2
2,714.9
138.6
5,848.7
175.0
10,851.3
186.0
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
108.0
8.1
178.1
10.8
195.9
12.0
374.3
16.1
735.3
22.7
1,311.6
25.0
1,831.4
29.1
1,826.7
27.6
1,950.5
26.2
909.1
21.2
486.1
14.5
66.7
6.6
9,973.6
29.1
3,365.5
18.7
3,477.7
18.7
3,926.4
18.7
4,636.9
18.7
5,216.5
18.7
5,048.2
18.7
4,057.3
18.7
3,926.4
18.7
3,477.7
18.7
47,228.7
18.7
(Misc Accessory Equipment)
3,477.7
18.7
SBCC TRACE.TRC
3,141.1
18.7
3,477.7
18.7
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 8 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
186.0
1.0
210.0
1.0
248.0
1.0
279.0
1.0
270.0
1.0
217.0
1.0
210.0
1.0
186.0
1.0
2,526.0
1.0
30,869.3
221.7
39,373.5
261.2
37,948.5
253.9
39,830.3
275.7
36,337.9
238.0
19,806.0
199.4
4,820.6
151.7
291,345.9
275.7
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Cntl panel & interlocks - 1 KW (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
186.0
1.0
168.0
1.0
186.0
1.0
180.0
1.0
DR [Clg Nominal Capacity/F.L.Rate=369.0 tons / 455.1 kW]
Electric (kWh)
Peak (kW)
6,761.8
155.2
14,811.3
188.7
15,368.1
177.5
(Cooling Equipment)
14,139.7
177.7
31,279.1
224.8
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=498.4 tons / 47.35 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
900.0
19.0
1,686.4
25.4
1,825.5
22.9
1,753.2
24.3
3,542.3
32.1
3,570.8
31.9
4,892.6
36.2
4,686.5
35.7
5,158.5
37.6
3,963.8
32.5
2,209.9
27.5
662.8
18.1
34,852.2
37.6
4,487.3
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
54,595.3
18.7
248.0
1.0
240.0
1.0
248.0
1.0
248.0
1.0
240.0
1.0
248.0
1.0
240.0
1.0
248.0
1.0
2,920.0
1.0
25,561.1
137.0
24,413.2
133.6
24,620.3
141.0
17,356.0
123.9
11,005.1
94.9
6,311.4
65.0
186,244.5
141.0
(Misc Accessory Equipment)
4,636.9
18.7
Cntl panel & interlocks - 1 KW
Electric (kWh)
Peak (kW)
4,188.1
18.7
4,636.9
18.7
(Misc Accessory Equipment)
248.0
1.0
224.0
1.0
248.0
1.0
240.0
1.0
Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons]
Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW]
Electric (kWh)
Peak (kW)
7,195.2
68.2
8,442.3
85.9
10,275.2
85.6
(Cooling Equipment)
12,448.5
92.4
18,670.5
119.8
19,945.8
117.9
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW]
Electric (kWh)
Peak (kW)
1,000.7
9.1
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
1,155.4
11.2
1,414.1
11.3
1,720.8
12.3
2,537.8
15.5
2,713.7
15.4
3,435.7
17.5
3,294.8
17.2
3,299.1
17.9
2,311.1
15.6
1,501.2
12.3
879.5
8.7
25,263.9
17.9
43.4
0.1
42.0
0.1
43.4
0.1
43.4
0.1
42.0
0.1
43.4
0.1
42.0
0.1
43.4
0.1
511.0
0.1
32,736.0
238.8
18,821.8
217.2
9,207.4
139.5
368,063.4
308.1
(Misc Accessory Equipment)
43.4
0.1
39.2
0.1
43.4
0.1
42.0
0.1
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
10,591.2
143.5
SBCC TRACE.TRC
14,300.4
198.8
19,335.6
209.3
26,810.3
228.0
39,915.7
283.1
42,346.6
282.8
(Cooling Equipment - Cooling Mode)
53,407.1
308.1
50,651.4
296.9
49,940.1
297.2
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 9 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW]
Electric (kWh)
Peak (kW)
HP
7,170.9
252.5
3,032.1
243.8
3,580.8
215.9
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
(Cooling Equipment - Heating Mode)
1,918.0
161.8
1,826.4
157.6
603.9
135.3
255.1
115.0
258.7
115.0
416.7
125.9
3,097.9
169.0
4,591.5
217.4
14,308.3
282.6
41,060.4
282.6
126.1
1.1
108.8
0.8
102.7
0.8
104.2
0.8
99.5
1.0
146.1
1.8
188.1
2.0
173.6
1.7
1,711.5
2.0
(Cooling Equipment - Heat Recovered From Condenser Loop)
Heat Recovered (therms)
Peak (therms/Hr)
149.7
1.0
153.1
1.1
194.6
1.5
165.1
1.9
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW]
Electric (kWh)
Peak (kW)
2,580.6
25.9
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
2,581.9
31.3
3,457.2
32.1
4,544.0
34.6
Cnst vol cnd water pump
Electric (kWh)
Peak (kW)
Boiler forced draft fan
8,748.4
47.2
8,307.1
45.4
8,182.2
45.5
5,594.0
40.0
3,492.1
33.2
3,065.0
25.1
64,286.5
47.2
48.1
0.1
57.0
0.1
60.5
0.1
62.5
0.1
57.4
0.1
52.8
0.1
55.1
0.1
55.3
0.1
61.1
0.1
58.3
0.1
74.4
0.1
703.8
0.1
2,537.3
13.8
2,138.1
11.3
1,925.6
10.4
(Heating Equipment)
923.2
5.7
734.5
4.2
460.1
3.1
357.8
2.1
366.6
2.2
401.2
2.9
1,070.3
6.5
1,470.7
8.0
2,689.4
11.3
15,074.7
13.8
10,120.0
14.1
8,714.5
14.1
8,433.4
14.1
8,053.9
14.1
8,377.2
14.1
7,590.0
14.1
8,714.5
14.1
10,120.1
14.1
10,457.4
14.1
110,941.0
14.1
1,908.5
2.7
1,643.5
2.7
1,590.5
2.7
1,518.9
2.7
1,579.9
2.7
1,431.4
2.7
1,643.5
2.7
1,908.5
2.7
1,972.2
2.7
20,922.4
2.7
310.0
0.5
300.0
0.5
286.5
0.5
298.0
0.5
270.0
0.5
310.0
0.5
360.0
0.5
372.0
0.5
3,946.5
0.5
74.6
1.0
75.9
0.9
74.7
0.9
222.3
2.6
326.7
3.0
588.0
3.5
3,351.6
4.3
(Misc Accessory Equipment)
10,457.4
14.1
9,445.4
14.1
10,457.4
14.1
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
1,972.2
2.7
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
372.0
0.5
1,781.3
2.7
1,972.2
2.7
(Misc Accessory Equipment)
336.0
0.5
372.0
0.5
360.0
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms]
Gas (therms)
Peak (therms/Hr)
Project Name:
Dataset Name:
7,004.2
43.2
(Misc Accessory Equipment)
61.3
0.1
Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh]
Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms]
Gas (therms)
Peak (therms/Hr)
6,730.0
43.3
SBCC TRACE.TRC
568.0
4.3
471.9
3.5
438.2
3.1
232.5
2.2
(Heating Equipment)
168.2
1.7
110.8
1.3
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 10 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
731.9
1.0
690.3
1.0
617.6
1.0
580.1
1.0
649.8
1.0
592.6
1.0
498.0
1.0
699.7
1.0
773.5
1.0
8,079.1
1.0
332.0
0.5
297.0
0.5
279.0
0.5
312.5
0.5
285.0
0.5
239.5
0.5
336.5
0.5
372.0
0.5
3,885.5
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler forced draft fan (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
773.5
1.0
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
698.6
1.0
773.5
1.0
(Misc Accessory Equipment)
372.0
0.5
336.0
0.5
372.0
0.5
352.0
0.5
Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh]
Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms]
799.1
14.4
Gas (therms)
Peak (therms/Hr)
Boiler forced draft fan
1,328.8
15.4
640.2
13.8
(Heating Equipment)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2,768.1
15.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
589.6
2.5
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
118.0
0.5
1,934.3
8.3
2,127.3
8.7
2,044.4
8.7
1,965.5
8.7
2,011.2
8.7
1,991.1
8.5
2,334.1
8.7
24,698.3
8.7
586.3
3.3
663.8
3.4
653.2
3.5
640.3
3.7
631.5
3.6
545.5
3.2
568.9
3.1
7,248.5
3.7
372.9
2.1
321.5
1.8
282.7
1.4
320.4
1.1
302.5
1.8
379.1
1.4
4,181.6
2.2
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
154.9
2.5
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
279.8
2.5
154.9
2.5
(Misc Accessory Equipment)
31.0
0.5
56.0
0.5
31.0
0.5
0.0
0.0
Sys 1: Admin VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW]
Electric (kWh)
Peak (kW)
2,366.7
8.7
2,023.1
8.7
2,032.4
8.4
1,816.3
8.7
Sys 2: Admin FC
Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW]
Electric (kWh)
Peak (kW)
578.6
3.3
573.3
3.2
620.7
3.0
(Main Clg Fan)
549.6
3.2
Sys 3: Campus Center FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
SBCC TRACE.TRC
336.9
1.4
358.8
1.5
381.9
1.5
(Main Clg Fan)
2,051.9
8.7
313.6
1.6
636.8
3.3
(Main Clg Fan)
429.0
2.1
382.5
2.2
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 11 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 4: Campus Center Dual Deck
AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW]
Electric (kWh)
Peak (kW)
2,064.2
6.0
1,863.1
6.8
2,161.8
6.8
2,104.7
6.8
Sys 5: Campus Center Packg RTU-1
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW]
Electric (kWh)
Peak (kW)
825.8
3.3
787.7
3.4
945.1
3.5
1,052.6
3.6
Sys 6: Drama/Music HP
AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW]
Electric (kWh)
Peak (kW)
1,596.5
6.0
1,580.5
6.5
1,705.2
5.9
1,560.5
6.1
Sys 7: Drama/Music Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW]
Electric (kWh)
Peak (kW)
111.6
0.6
94.6
0.6
96.4
0.6
May
766.5
4.6
731.5
4.4
826.7
4.1
2,427.7
6.8
2,766.0
12.0
2,664.3
16.8
2,867.7
17.4
9,536.2
43.5
9,096.7
50.5
9,855.1
44.9
Sept
Oct
Nov
Dec
Total
2,424.9
6.8
2,426.1
6.8
2,342.4
6.8
2,291.7
6.8
2,009.3
6.8
2,041.1
6.8
26,422.4
6.8
1,261.4
3.8
1,232.4
3.8
1,166.2
3.8
1,055.3
3.7
905.1
3.3
798.1
3.0
12,346.9
3.8
1,662.2
6.6
1,863.2
7.0
1,823.6
6.9
1,801.3
7.4
1,733.4
7.2
1,483.3
6.6
1,696.1
6.1
20,258.4
7.4
66.0
0.5
78.2
0.5
73.8
0.6
73.3
0.6
80.4
0.6
83.2
0.6
110.0
0.6
996.6
0.6
1,071.9
4.4
1,062.9
4.5
1,046.1
4.8
969.6
4.7
787.8
4.5
697.9
3.5
10,771.4
4.8
4,158.9
25.0
3,964.9
23.5
3,790.5
22.8
3,131.2
21.5
2,416.5
15.9
2,859.8
12.1
38,717.2
25.0
11,124.9
44.9
11,138.7
48.1
11,616.0
57.4
10,518.5
61.3
8,480.1
51.4
9,285.7
41.7
119,088.3
61.3
2,265.5
6.8
1,148.3
3.8
1,169.0
3.8
(Main Clg Fan)
1,752.8
6.8
(Main Clg Fan)
60.2
0.6
68.8
0.5
857.8
4.6
2,945.8
18.1
8,773.8
38.5
(Main Clg Fan)
990.1
4.4
962.6
4.1
(Main Clg Fan)
3,524.6
23.7
Sys 10: Humanities VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW]
Electric (kWh)
Peak (kW)
Aug
(Main Clg Fan)
Sys 9: EBS VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
Sys 8: Drama/Music MZU
90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW]
Electric (kWh)
Peak (kW)
June
3,627.0
23.3
(Main Clg Fan)
9,865.7
41.9
9,796.9
39.8
Sys 11: Humanities Fan Coil
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 12 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 11: Humanities Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW]
Electric (kWh)
Peak (kW)
221.6
2.3
256.6
2.2
331.3
2.4
24.1
0.1
24.5
0.1
31.1
0.1
456.0
2.7
3,185.3
11.6
2,814.6
11.6
2,895.4
11.6
2,192.9
7.7
Sys 14: OE Pckg AH
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW]
Electric (kWh)
Peak (kW)
354.9
1.8
353.2
1.9
362.3
1.6
322.0
1.5
Sys 15: PE Heat Pump
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW]
Electric (kWh)
Peak (kW)
309.8
1.3
313.0
1.3
348.9
1.4
306.1
1.0
Sys 16: PE VAV Htg Only
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW]
Electric (kWh)
Peak (kW)
37.2
1.3
12.1
0.4
3.3
0.1
Sys 17: PS Fan Coil Htg Only
Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW]
Electric (kWh)
Peak (kW)
301.1
0.8
273.4
0.8
301.8
0.8
July
Aug
Sept
Oct
Nov
Dec
Total
447.0
2.7
479.0
2.7
444.6
2.6
384.9
2.6
338.5
2.2
244.5
2.1
220.2
2.2
4,178.9
2.7
47.0
0.2
51.5
0.2
49.3
0.2
45.8
0.2
38.6
0.2
30.3
0.1
22.9
0.1
449.0
0.2
2,208.9
10.9
2,226.5
11.0
2,291.2
11.6
2,479.2
11.6
2,658.7
11.6
3,315.0
11.6
30,732.7
11.6
426.7
2.4
429.5
2.2
449.1
2.1
403.5
2.2
315.8
2.0
365.9
1.7
4,555.4
2.4
444.2
3.4
380.1
3.2
353.5
3.2
370.1
1.7
309.0
1.0
273.1
1.2
4,103.2
3.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.3
0.0
0.4
0.0
31.4
0.4
85.5
1.3
285.7
0.8
315.4
0.8
317.5
0.8
305.0
0.8
293.1
0.8
290.8
0.8
305.5
0.8
3,565.2
0.8
(Main Clg Fan)
38.9
0.1
45.2
0.2
Sys 13: LRC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW]
Electric (kWh)
Peak (kW)
June
(Main Clg Fan)
354.7
2.5
Sys 12: IDC Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW]
Electric (kWh)
Peak (kW)
May
0.5
0.0
(Main Clg Fan)
2,379.9
9.9
2,085.2
9.3
(Main Clg Fan)
391.3
2.2
381.4
2.2
(Main Clg Fan)
353.5
3.1
342.0
3.3
(Main Clg Fan)
0.3
0.0
(Main Clg Fan)
286.2
0.8
289.8
0.8
Sys 18: Stdnt Srv VAV
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 13 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 2
SBCC CHWR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
Sys 18: Stdnt Srv VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW]
Electric (kWh)
Peak (kW)
3,465.7
13.6
3,054.7
12.9
3,467.3
15.2
3,005.2
12.4
1,234.1
5.2
1,217.7
6.2
1,399.7
6.1
1,519.7
6.0
Sys 20: IDC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW]
Electric (kWh)
Peak (kW)
1,258.8
4.4
1,142.1
5.1
1,287.6
4.6
1,297.2
4.5
8,120.3
41.6
8,501.0
50.6
8,501.8
49.5
7,807.4
48.6
Sys 22: BC FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW]
Electric (kWh)
Peak (kW)
1,899.4
7.4
1,781.9
7.7
1,948.2
6.8
1,525.5
6.2
Sys 23: BC Hydronic AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
1,354.9
5.1
SBCC TRACE.TRC
1,238.5
5.9
1,258.3
5.4
1,012.3
4.7
Aug
Sept
Oct
Nov
Dec
Total
3,237.9
15.2
3,552.1
16.4
3,388.5
15.5
3,285.0
15.0
3,450.1
16.6
3,218.2
17.1
3,314.7
13.8
39,813.8
17.1
2,165.1
10.0
1,934.5
8.8
1,737.1
8.6
1,568.4
7.7
1,263.9
5.9
1,187.8
4.9
19,055.3
10.2
1,440.4
4.6
1,460.0
4.9
1,459.7
5.4
1,429.3
5.4
1,290.5
5.3
1,220.3
4.6
15,977.2
5.4
11,268.1
67.5
10,776.1
64.4
10,538.1
66.9
9,078.9
62.7
6,961.7
49.0
8,077.0
39.4
109,493.0
67.5
1,716.5
6.9
1,704.0
7.4
1,797.4
8.2
1,853.2
8.1
1,548.4
7.9
1,842.4
7.3
21,001.6
8.2
1,150.2
5.8
1,143.8
6.1
1,177.1
7.3
1,238.2
7.3
1,068.3
6.1
1,233.7
5.0
14,047.1
7.3
(Main Clg Fan)
1,888.2
9.1
1,939.2
10.2
(Main Clg Fan)
1,362.7
4.6
Sys 21: Portopia HP
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
3,374.4
15.5
Sys 19: Admin Pckg AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW]
Electric (kWh)
Peak (kW)
June
1,328.7
4.4
(Main Clg Fan)
10,073.5
63.2
9,789.2
61.9
(Main Clg Fan)
1,810.9
6.4
1,573.8
6.5
(Main Clg Fan)
1,139.8
5.3
1,032.1
5.0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 2 Equipment Energy Consumption report page 14 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
Electric (kWh)
Peak (kW)
155,785.6
300.2
140,710.4
300.2
155,825.9
300.2
150,753.8
300.2
155,805.8
300.2
150,794.1
300.2
155,765.6
300.2
155,825.9
300.2
150,753.9
300.2
155,805.9
300.2
150,774.0
300.2
155,765.6
300.2
1,834,366.4
300.2
Electric (kWh)
Peak (kW)
196,983.9
315.2
177,920.8
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,623.4
315.2
196,987.6
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,627.1
315.2
196,987.6
315.2
2,319,305.5
315.2
4.3
0.1
1.6
0.0
3.2
0.1
10.6
0.1
15.3
0.2
23.0
0.2
36.5
0.2
38.5
0.2
41.8
0.2
11.3
0.1
10.4
0.2
3.2
0.1
199.6
0.2
60,450.0
150.0
54,600.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
711,750.0
150.0
11,160.0
15.0
10,080.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
131,400.0
15.0
40,300.0
100.0
36,400.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
474,500.0
100.0
17,940.2
272.2
18,114.8
269.8
19,558.2
269.4
11,031.7
227.3
6,621.1
176.7
632.9
121.3
105,105.1
272.2
Lights
Misc. Ld
Cooling Coil Condensate
Recoverable Water (1000gal)
Peak (1000gal/Hr)
Bsu 1: Parking lot lights
Electric (kWh)
Peak (kW)
Bsu 2: Decorative Fountains
Electric (kWh)
Peak (kW)
Bsu 3: Stadium Lights
Electric (kWh)
Peak (kW)
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Main [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] (Cooling Equipment)
Electric (kWh)
Peak (kW)
1,252.1
126.6
2,317.7
147.7
2,374.0
145.8
4,468.8
163.3
7,654.7
203.6
13,138.9
220.3
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
197.4
17.0
313.6
18.8
336.2
19.3
603.9
23.9
965.9
30.2
1,648.4
32.4
2,352.9
37.8
2,333.5
37.8
2,455.3
37.4
1,381.6
32.5
859.9
25.3
105.3
15.6
13,553.8
37.8
3,365.5
18.7
3,477.7
18.7
3,926.4
18.7
4,636.9
18.7
5,216.5
18.7
5,048.2
18.7
4,057.3
18.7
3,926.4
18.7
3,477.7
18.7
47,228.7
18.7
(Misc Accessory Equipment)
3,477.7
18.7
SBCC TRACE.TRC
3,141.1
18.7
3,477.7
18.7
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 15 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
186.0
1.0
210.0
1.0
248.0
1.0
279.0
1.0
270.0
1.0
217.0
1.0
210.0
1.0
186.0
1.0
2,526.0
1.0
23,609.4
199.8
33,316.8
233.4
31,824.8
227.3
34,472.8
248.1
28,282.7
218.7
12,603.7
181.6
3,211.3
134.5
221,910.3
248.1
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Cntl panel & interlocks - 1 KW (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
186.0
1.0
168.0
1.0
186.0
1.0
180.0
1.0
DR [Clg Nominal Capacity/F.L.Rate=369.0 tons / 455.1 kW]
Electric (kWh)
Peak (kW)
3,730.8
136.3
9,089.0
173.3
9,511.3
164.4
(Cooling Equipment)
8,671.1
165.2
23,586.7
203.4
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=498.4 tons / 47.35 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
507.9
14.5
1,049.4
20.6
1,148.0
19.1
1,093.0
20.5
2,626.2
28.1
2,705.4
27.6
3,826.3
32.6
3,683.1
32.1
4,116.0
34.5
2,936.9
29.2
1,424.8
22.6
441.9
14.3
25,559.0
34.5
4,487.3
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
54,595.3
18.7
248.0
1.0
240.0
1.0
248.0
1.0
248.0
1.0
240.0
1.0
248.0
1.0
240.0
1.0
248.0
1.0
2,920.0
1.0
23,767.8
146.2
22,837.3
144.1
22,900.3
139.6
15,692.3
121.6
10,066.3
97.2
6,031.8
68.4
172,075.9
146.2
(Misc Accessory Equipment)
4,636.9
18.7
Cntl panel & interlocks - 1 KW
Electric (kWh)
Peak (kW)
4,188.1
18.7
4,636.9
18.7
(Misc Accessory Equipment)
248.0
1.0
224.0
1.0
248.0
1.0
240.0
1.0
Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons]
Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW]
Electric (kWh)
Peak (kW)
6,760.0
73.5
7,590.0
81.4
9,263.9
87.2
(Cooling Equipment)
11,479.2
104.7
17,110.1
127.1
18,576.8
133.6
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW]
Electric (kWh)
Peak (kW)
943.8
10.1
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
1,045.4
11.1
1,281.5
11.9
1,591.1
14.2
2,336.1
17.0
2,535.7
17.8
3,206.4
19.2
3,092.1
19.0
3,080.8
18.3
2,103.4
16.0
1,380.0
13.1
843.0
9.4
23,439.2
19.2
43.4
0.1
42.0
0.1
43.4
0.1
43.4
0.1
42.0
0.1
43.4
0.1
42.0
0.1
43.4
0.1
511.0
0.1
29,702.0
251.7
18,337.3
268.0
9,429.7
238.0
342,742.4
323.9
(Misc Accessory Equipment)
43.4
0.1
39.2
0.1
43.4
0.1
42.0
0.1
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
11,369.3
198.1
SBCC TRACE.TRC
13,430.4
252.3
18,681.2
263.3
24,885.9
287.9
36,538.2
260.3
39,073.2
315.9
(Cooling Equipment - Cooling Mode)
49,183.3
323.9
46,525.8
323.0
45,586.0
321.9
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 16 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW]
Electric (kWh)
Peak (kW)
HP
6,916.3
252.5
2,897.2
243.4
3,623.0
218.8
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
(Cooling Equipment - Heating Mode)
1,916.9
161.8
1,827.1
157.6
599.0
135.3
255.1
115.0
258.7
115.0
416.7
125.9
3,088.7
169.0
4,554.3
217.4
13,962.1
282.2
40,315.2
282.2
126.1
1.1
108.8
0.8
102.7
0.8
104.2
0.8
99.5
1.0
146.6
1.9
192.3
2.0
192.6
1.9
1,779.5
2.0
(Cooling Equipment - Heat Recovered From Condenser Loop)
Heat Recovered (therms)
Peak (therms/Hr)
166.8
1.3
169.4
1.6
205.4
1.7
165.2
2.0
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW]
Electric (kWh)
Peak (kW)
2,640.8
35.4
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
2,422.3
38.2
3,286.9
39.9
4,258.0
43.7
Cnst vol cnd water pump
Electric (kWh)
Peak (kW)
Boiler forced draft fan
8,111.4
49.4
7,692.2
49.3
7,547.1
49.2
5,143.9
43.6
3,342.6
40.7
3,141.0
36.1
60,306.1
49.4
48.1
0.1
57.0
0.1
60.5
0.1
62.5
0.1
57.4
0.1
52.8
0.1
55.1
0.1
55.3
0.1
61.1
0.1
58.3
0.1
74.4
0.1
703.8
0.1
2,521.4
13.8
2,127.7
11.3
1,913.6
10.4
(Heating Equipment)
908.2
5.6
735.2
4.2
463.6
3.1
361.9
2.1
354.5
2.2
387.3
2.9
1,055.4
6.5
1,477.0
8.0
2,657.8
11.3
14,963.5
13.8
10,120.0
14.1
9,585.9
14.1
9,276.7
14.1
8,925.3
14.1
9,248.6
14.1
8,011.7
14.1
8,714.5
14.1
10,120.1
14.1
10,457.4
14.1
114,820.3
14.1
1,908.5
2.7
1,807.8
2.7
1,749.5
2.7
1,683.2
2.7
1,744.2
2.7
1,510.9
2.7
1,643.5
2.7
1,908.5
2.7
1,972.2
2.7
21,654.0
2.7
341.0
0.5
330.0
0.5
317.5
0.5
329.0
0.5
285.0
0.5
310.0
0.5
360.0
0.5
372.0
0.5
4,084.5
0.5
74.6
1.0
75.9
0.9
74.7
0.9
222.2
2.6
326.9
3.0
588.8
3.5
3,349.3
4.3
(Misc Accessory Equipment)
10,457.4
14.1
9,445.4
14.1
10,457.4
14.1
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
1,972.2
2.7
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
372.0
0.5
1,781.3
2.7
1,972.2
2.7
(Misc Accessory Equipment)
336.0
0.5
372.0
0.5
360.0
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms]
Gas (therms)
Peak (therms/Hr)
Project Name:
Dataset Name:
6,501.3
48.1
(Misc Accessory Equipment)
61.3
0.1
Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh]
Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms]
Gas (therms)
Peak (therms/Hr)
6,218.6
45.8
SBCC TRACE.TRC
566.4
4.3
471.1
3.5
437.5
3.1
232.5
2.2
(Heating Equipment)
168.1
1.7
110.8
1.3
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 17 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
731.9
1.0
690.3
1.0
617.6
1.0
580.1
1.0
649.8
1.0
592.6
1.0
498.0
1.0
699.7
1.0
773.5
1.0
8,079.1
1.0
332.0
0.5
297.0
0.5
279.0
0.5
312.5
0.5
285.0
0.5
239.5
0.5
336.5
0.5
372.0
0.5
3,885.5
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler forced draft fan (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
773.5
1.0
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
698.6
1.0
773.5
1.0
(Misc Accessory Equipment)
372.0
0.5
336.0
0.5
372.0
0.5
352.0
0.5
Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh]
Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms]
799.1
14.4
Gas (therms)
Peak (therms/Hr)
Boiler forced draft fan
1,337.7
15.4
640.9
13.8
(Heating Equipment)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2,777.7
15.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
589.6
2.5
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
118.0
0.5
1,829.8
7.6
1,993.0
7.1
1,902.6
7.2
1,818.7
7.7
1,930.0
8.7
1,939.9
8.5
2,263.5
8.7
23,589.0
8.7
526.4
3.9
597.4
3.9
584.2
3.4
572.7
3.2
567.7
3.0
493.8
2.9
532.6
3.1
6,561.7
3.9
324.0
2.1
278.0
1.7
249.4
1.3
293.6
1.1
284.8
1.8
367.2
1.4
3,810.4
2.2
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
154.9
2.5
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
279.8
2.5
154.9
2.5
(Misc Accessory Equipment)
31.0
0.5
56.0
0.5
31.0
0.5
0.0
0.0
Sys 1: Admin VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW]
Electric (kWh)
Peak (kW)
2,282.5
8.7
1,973.2
8.7
1,972.4
8.4
1,744.7
8.7
Sys 2: Admin FC
Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW]
Electric (kWh)
Peak (kW)
532.4
3.3
524.7
3.2
563.0
3.2
(Main Clg Fan)
494.3
3.7
Sys 3: Campus Center FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
SBCC TRACE.TRC
321.4
1.4
339.5
1.5
354.6
1.5
(Main Clg Fan)
1,938.7
6.7
280.4
1.5
572.6
3.8
(Main Clg Fan)
381.8
1.9
335.8
2.2
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 18 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 4: Campus Center Dual Deck
AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW]
Electric (kWh)
Peak (kW)
1,818.5
6.0
1,713.8
6.8
1,943.9
6.8
1,954.3
6.8
Sys 5: Campus Center Packg RTU-1
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW]
Electric (kWh)
Peak (kW)
768.3
3.6
736.8
3.6
893.4
3.6
1,011.3
3.6
Sys 6: Drama/Music HP
AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW]
Electric (kWh)
Peak (kW)
1,498.8
6.0
1,506.7
6.5
1,629.1
6.4
1,489.2
6.4
Sys 7: Drama/Music Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW]
Electric (kWh)
Peak (kW)
108.4
0.6
91.3
0.6
92.2
0.6
May
705.5
4.6
663.3
4.4
752.8
4.7
2,232.3
6.8
2,898.9
25.0
2,870.8
25.0
3,095.5
25.0
9,288.6
54.0
8,750.5
58.0
9,426.5
57.9
Sept
Oct
Nov
Dec
Total
2,251.7
6.8
2,275.6
6.8
2,202.7
6.8
2,118.5
6.8
1,792.6
6.8
1,847.8
6.8
24,228.1
6.8
1,215.5
3.8
1,191.9
3.8
1,127.7
3.8
1,004.4
3.6
851.7
3.6
748.0
3.5
11,791.9
3.8
1,584.6
7.0
1,782.8
7.1
1,741.5
7.0
1,721.4
7.4
1,647.5
6.1
1,413.3
6.1
1,624.2
6.1
19,306.4
7.4
61.4
0.6
72.8
0.6
68.0
0.6
67.4
0.6
74.3
0.6
78.6
0.6
107.0
0.6
941.9
0.6
972.9
5.8
957.6
5.4
933.9
4.7
870.7
4.5
720.4
4.5
648.6
3.7
9,803.2
5.8
4,233.5
25.0
4,072.2
25.0
3,843.9
25.0
3,316.0
25.0
2,563.4
25.0
2,935.0
25.0
40,525.1
25.0
10,437.4
60.7
10,337.5
60.4
10,581.4
61.3
9,653.8
59.7
7,988.8
53.8
9,108.4
50.7
112,683.8
61.3
2,076.4
6.8
1,108.3
3.6
1,134.8
3.8
(Main Clg Fan)
1,667.2
6.2
(Main Clg Fan)
56.6
0.6
64.0
0.6
790.1
4.9
3,202.0
25.0
8,402.6
55.9
(Main Clg Fan)
902.7
5.5
884.8
5.6
(Main Clg Fan)
3,698.3
25.0
Sys 10: Humanities VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW]
Electric (kWh)
Peak (kW)
Aug
(Main Clg Fan)
Sys 9: EBS VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
Sys 8: Drama/Music MZU
90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW]
Electric (kWh)
Peak (kW)
June
3,795.6
25.0
(Main Clg Fan)
9,360.5
58.5
9,347.8
59.2
Sys 11: Humanities Fan Coil
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 19 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 11: Humanities Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW]
Electric (kWh)
Peak (kW)
197.3
2.4
225.7
2.3
288.5
2.4
21.6
0.2
22.0
0.2
28.7
0.2
397.6
2.6
3,117.1
11.6
2,740.5
11.6
2,802.4
11.6
2,103.8
8.3
Sys 14: OE Pckg AH
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW]
Electric (kWh)
Peak (kW)
352.3
3.4
353.3
3.4
362.7
3.4
322.4
3.4
Sys 15: PE Heat Pump
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW]
Electric (kWh)
Peak (kW)
309.8
1.3
312.1
1.3
345.3
1.4
298.3
1.1
Sys 16: PE VAV Htg Only
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW]
Electric (kWh)
Peak (kW)
37.2
1.3
12.1
0.4
3.3
0.1
Sys 17: PS Fan Coil Htg Only
Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW]
Electric (kWh)
Peak (kW)
290.5
0.8
270.9
0.8
301.8
0.8
July
Aug
Sept
Oct
Nov
Dec
Total
391.9
2.7
420.2
2.7
387.7
2.5
337.3
2.3
293.3
1.8
214.6
2.1
201.5
2.2
3,663.8
2.7
44.5
0.2
48.1
0.2
46.3
0.2
43.0
0.2
35.7
0.2
27.5
0.2
20.7
0.2
417.6
0.2
2,092.4
10.7
2,048.2
9.7
2,067.1
9.2
2,315.6
8.7
2,602.6
11.6
3,226.6
11.6
29,409.4
11.6
422.3
3.4
424.8
3.4
439.3
3.7
397.7
3.4
314.5
3.4
365.8
3.2
4,519.3
4.3
440.9
3.8
370.8
3.8
340.9
3.6
354.8
2.0
307.3
1.0
273.1
1.2
4,020.1
3.8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.3
0.0
0.4
0.0
31.4
0.4
85.5
1.3
285.7
0.8
315.4
0.8
317.5
0.8
305.0
0.8
293.1
0.8
287.1
0.8
295.5
0.8
3,538.5
0.8
(Main Clg Fan)
36.6
0.2
42.7
0.2
Sys 13: LRC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW]
Electric (kWh)
Peak (kW)
June
(Main Clg Fan)
308.3
2.3
Sys 12: IDC Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW]
Electric (kWh)
Peak (kW)
May
0.5
0.0
(Main Clg Fan)
2,288.1
9.6
2,005.2
10.2
(Main Clg Fan)
387.1
3.4
377.1
4.3
(Main Clg Fan)
337.6
3.6
329.3
3.7
(Main Clg Fan)
0.3
0.0
(Main Clg Fan)
286.2
0.8
289.8
0.8
Sys 18: Stdnt Srv VAV
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 20 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 3
SBCC Class Temp Reduction
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
Sys 18: Stdnt Srv VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW]
Electric (kWh)
Peak (kW)
3,500.5
16.5
3,104.2
16.4
3,527.2
17.1
2,977.0
17.1
1,191.0
13.4
1,266.6
13.7
1,466.8
13.7
1,580.7
13.9
Sys 20: IDC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW]
Electric (kWh)
Peak (kW)
1,114.1
4.1
1,011.6
4.3
1,142.9
4.5
1,158.2
4.5
8,067.7
79.8
8,722.5
81.8
8,841.8
82.9
8,082.4
83.4
Sys 22: BC FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW]
Electric (kWh)
Peak (kW)
1,786.2
7.4
1,663.0
7.7
1,811.1
7.9
1,395.2
8.0
Sys 23: BC Hydronic AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
1,306.6
4.6
SBCC TRACE.TRC
1,199.1
5.8
1,218.7
6.3
983.9
6.3
Aug
Sept
Oct
Nov
Dec
Total
3,144.6
17.1
3,358.9
17.1
3,235.8
17.1
3,105.0
17.1
3,366.0
17.1
3,172.6
17.1
3,337.8
16.1
39,101.7
17.1
2,176.2
14.4
1,940.5
15.3
1,743.7
15.3
1,630.3
14.4
1,306.0
13.9
1,135.3
13.3
19,307.7
15.3
1,276.4
4.7
1,283.5
4.7
1,268.8
4.5
1,246.5
4.6
1,137.9
4.6
1,097.5
4.3
14,143.3
4.7
11,210.6
87.2
10,642.2
87.1
10,272.6
85.7
9,028.5
82.6
7,146.0
79.8
7,868.0
77.7
109,783.5
88.3
1,541.3
8.7
1,527.2
8.6
1,620.4
8.6
1,690.1
8.1
1,426.2
7.9
1,739.0
7.3
19,277.6
8.7
1,101.9
7.9
1,083.4
7.7
1,093.0
7.1
1,170.8
6.0
1,023.8
4.7
1,210.6
3.9
13,490.4
7.9
(Main Clg Fan)
1,908.9
14.4
1,961.8
14.6
(Main Clg Fan)
1,214.3
4.6
Sys 21: Portopia HP
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
3,272.0
17.1
Sys 19: Admin Pckg AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW]
Electric (kWh)
Peak (kW)
June
1,191.8
4.6
(Main Clg Fan)
10,066.7
86.6
9,834.4
88.3
(Main Clg Fan)
1,653.6
8.4
1,424.3
8.5
(Main Clg Fan)
1,100.2
7.0
998.5
7.1
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 3 Equipment Energy Consumption report page 21 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
Electric (kWh)
Peak (kW)
155,785.6
300.2
140,710.4
300.2
155,825.9
300.2
150,753.8
300.2
155,805.8
300.2
150,794.1
300.2
155,765.6
300.2
155,825.9
300.2
150,753.9
300.2
155,805.9
300.2
150,774.0
300.2
155,765.6
300.2
1,834,366.4
300.2
Electric (kWh)
Peak (kW)
196,983.9
315.2
177,920.8
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,623.4
315.2
196,987.6
315.2
196,976.5
315.2
190,630.8
315.2
196,980.3
315.2
190,627.1
315.2
196,987.6
315.2
2,319,305.5
315.2
4.3
0.1
1.6
0.0
3.2
0.1
10.6
0.1
15.3
0.2
23.0
0.2
36.4
0.2
38.4
0.2
41.7
0.2
11.2
0.1
10.3
0.2
3.2
0.1
199.1
0.2
60,450.0
150.0
54,600.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
58,500.0
150.0
60,450.0
150.0
711,750.0
150.0
11,160.0
15.0
10,080.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
10,800.0
15.0
11,160.0
15.0
131,400.0
15.0
40,300.0
100.0
36,400.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
39,000.0
100.0
40,300.0
100.0
474,500.0
100.0
17,950.6
275.2
18,122.9
272.7
19,566.7
272.2
11,040.4
228.9
6,628.4
177.0
632.9
121.5
105,187.0
275.2
Lights
Misc. Ld
Cooling Coil Condensate
Recoverable Water (1000gal)
Peak (1000gal/Hr)
Bsu 1: Parking lot lights
Electric (kWh)
Peak (kW)
Bsu 2: Decorative Fountains
Electric (kWh)
Peak (kW)
Bsu 3: Stadium Lights
Electric (kWh)
Peak (kW)
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Main [Clg Nominal Capacity/F.L.Rate=369.0 tons / 479.7 kW] (Cooling Equipment)
Electric (kWh)
Peak (kW)
1,254.2
126.8
2,323.8
147.9
2,379.3
145.9
4,479.0
163.5
7,665.4
204.1
13,143.3
221.0
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=505.4 tons / 48.02 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
197.7
17.1
314.4
18.9
336.9
19.3
605.2
24.0
967.3
30.3
1,649.6
32.5
2,356.0
38.1
2,336.2
38.0
2,458.1
37.7
1,384.1
32.7
861.8
25.4
105.3
15.7
13,572.3
38.1
3,365.5
18.7
3,477.7
18.7
3,926.4
18.7
4,636.9
18.7
5,216.5
18.7
5,048.2
18.7
4,057.3
18.7
3,926.4
18.7
3,477.7
18.7
47,228.7
18.7
(Misc Accessory Equipment)
3,477.7
18.7
SBCC TRACE.TRC
3,141.1
18.7
3,477.7
18.7
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 22 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
186.0
1.0
210.0
1.0
248.0
1.0
279.0
1.0
270.0
1.0
217.0
1.0
210.0
1.0
186.0
1.0
2,526.0
1.0
23,349.5
199.5
32,982.5
232.9
31,491.8
226.8
34,097.9
247.4
27,823.1
218.4
12,342.2
181.4
3,160.9
134.5
218,959.1
247.4
Cpl 1: Air Cooled Scroll CH [Sum of dsn coil capacities=335.5 tons]
Cntl panel & interlocks - 1 KW (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
186.0
1.0
168.0
1.0
186.0
1.0
180.0
1.0
DR [Clg Nominal Capacity/F.L.Rate=369.0 tons / 455.1 kW]
Electric (kWh)
Peak (kW)
3,643.0
136.3
8,895.1
173.1
9,341.6
163.7
(Cooling Equipment)
8,526.0
164.5
23,305.5
203.1
Condenser fan for Centrifugal [Design Heat Rejection/F.L.Rate=498.4 tons / 47.35 kW]
Electric (kWh)
Peak (kW)
Cnst vol chill water pump
Electric (kWh)
Peak (kW)
496.4
14.3
1,027.8
20.5
1,128.3
18.9
1,075.3
20.3
2,595.5
28.0
2,676.6
27.5
3,779.8
32.5
3,641.6
32.0
4,069.3
34.4
2,890.6
29.1
1,396.1
22.6
435.1
14.3
25,212.4
34.4
4,487.3
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
4,487.3
18.7
4,636.9
18.7
54,595.3
18.7
248.0
1.0
240.0
1.0
248.0
1.0
248.0
1.0
240.0
1.0
248.0
1.0
240.0
1.0
248.0
1.0
2,920.0
1.0
23,767.8
146.2
22,837.3
144.1
22,900.3
139.6
15,692.3
121.6
10,066.3
97.2
6,031.8
68.4
172,075.9
146.2
(Misc Accessory Equipment)
4,636.9
18.7
Cntl panel & interlocks - 1 KW
Electric (kWh)
Peak (kW)
4,188.1
18.7
4,636.9
18.7
(Misc Accessory Equipment)
248.0
1.0
224.0
1.0
248.0
1.0
240.0
1.0
Cpl 2: Pckg Unit [Sum of dsn coil capacities=129.4 tons]
Pckg AC [Clg Nominal Capacity/F.L.Rate=142.3 tons / 213.5 kW]
Electric (kWh)
Peak (kW)
6,760.0
73.5
7,590.0
81.4
9,263.9
87.2
(Cooling Equipment)
11,479.2
104.7
17,110.1
127.1
18,576.8
133.6
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=203.0 tons / 24.36 kW]
Electric (kWh)
Peak (kW)
943.8
10.1
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
1,045.4
11.1
1,281.5
11.9
1,591.1
14.2
2,336.1
17.0
2,535.7
17.8
3,206.4
19.2
3,092.1
19.0
3,080.8
18.3
2,103.4
16.0
1,380.0
13.1
843.0
9.4
23,439.2
19.2
43.4
0.1
42.0
0.1
43.4
0.1
43.4
0.1
42.0
0.1
43.4
0.1
42.0
0.1
43.4
0.1
511.0
0.1
29,702.0
251.7
18,337.3
268.0
9,429.7
238.0
342,742.4
323.9
(Misc Accessory Equipment)
43.4
0.1
39.2
0.1
43.4
0.1
42.0
0.1
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Clg Nominal Capacity/F.L.Rate=360.5 tons / 362.2 kW] [**Orig F.L.Rate=362.2 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
11,369.3
198.1
SBCC TRACE.TRC
13,430.4
252.3
18,681.2
263.3
24,885.9
287.9
36,538.2
260.3
39,073.2
315.9
(Cooling Equipment - Cooling Mode)
49,183.3
323.9
46,525.8
323.0
45,586.0
321.9
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 23 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Cpl 3: HP Unit [Sum of dsn coil capacities=327.7 tons]
HP [Htg Nominal Capacity/F.L.Rate=5,191 mbh / 493.2 kW]
Electric (kWh)
Peak (kW)
HP
6,916.3
252.5
2,897.2
243.4
3,623.0
218.8
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
(Cooling Equipment - Heating Mode)
1,916.9
161.8
1,827.1
157.6
599.0
135.3
255.1
115.0
258.7
115.0
416.7
125.9
3,088.7
169.0
4,554.3
217.4
13,962.1
282.2
40,315.2
282.2
126.1
1.1
108.8
0.8
102.7
0.8
104.2
0.8
99.5
1.0
146.6
1.9
192.3
2.0
192.6
1.9
1,779.5
2.0
(Cooling Equipment - Heat Recovered From Condenser Loop)
Heat Recovered (therms)
Peak (therms/Hr)
166.8
1.3
169.4
1.6
205.4
1.7
165.2
2.0
Condenser fan for Heat Pump [Design Heat Rejection/F.L.Rate=435.9 tons / 52.30 kW]
Electric (kWh)
Peak (kW)
2,640.8
35.4
Cntl panel & interlocks - 0.1 KW
Electric (kWh)
Peak (kW)
2,422.3
38.2
3,286.9
39.9
4,258.0
43.7
Cnst vol cnd water pump
Electric (kWh)
Peak (kW)
Boiler forced draft fan
8,111.4
49.4
7,692.2
49.3
7,547.1
49.2
5,143.9
43.6
3,342.6
40.7
3,141.0
36.1
60,306.1
49.4
48.1
0.1
57.0
0.1
60.5
0.1
62.5
0.1
57.4
0.1
52.8
0.1
55.1
0.1
55.3
0.1
61.1
0.1
58.3
0.1
74.4
0.1
703.8
0.1
2,521.3
13.8
2,127.7
11.3
1,913.6
10.4
(Heating Equipment)
908.2
5.6
735.2
4.2
463.6
3.1
361.9
2.1
354.5
2.2
387.3
2.9
1,055.4
6.5
1,477.0
8.0
2,657.8
11.3
14,963.4
13.8
10,120.0
14.1
9,585.9
14.1
9,276.7
14.1
8,925.3
14.1
9,248.6
14.1
8,011.7
14.1
8,714.5
14.1
10,120.1
14.1
10,457.4
14.1
114,820.3
14.1
1,908.5
2.7
1,807.8
2.7
1,749.5
2.7
1,683.2
2.7
1,744.2
2.7
1,510.9
2.7
1,643.5
2.7
1,908.5
2.7
1,972.2
2.7
21,654.0
2.7
341.0
0.5
330.0
0.5
317.5
0.5
329.0
0.5
285.0
0.5
310.0
0.5
360.0
0.5
372.0
0.5
4,084.5
0.5
74.6
1.0
75.9
0.9
74.7
0.9
222.2
2.6
326.9
3.0
588.8
3.5
3,349.3
4.3
(Misc Accessory Equipment)
10,457.4
14.1
9,445.4
14.1
10,457.4
14.1
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
1,972.2
2.7
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
372.0
0.5
1,781.3
2.7
1,972.2
2.7
(Misc Accessory Equipment)
336.0
0.5
372.0
0.5
360.0
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler - 002 [Nominal Capacity/F.L.Rate=1,039 mbh / 12.48 Therms]
Gas (therms)
Peak (therms/Hr)
Project Name:
Dataset Name:
6,501.3
48.1
(Misc Accessory Equipment)
61.3
0.1
Hpl 1: HHW Boiler [Sum of dsn coil capacities=2,409 mbh]
Boiler - 001 [Nominal Capacity/F.L.Rate=2,650 mbh / 31.82 Therms]
Gas (therms)
Peak (therms/Hr)
6,218.6
45.8
SBCC TRACE.TRC
566.4
4.3
471.1
3.5
437.5
3.1
232.5
2.2
(Heating Equipment)
168.1
1.7
110.8
1.3
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 24 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
Total
731.9
1.0
690.3
1.0
617.6
1.0
580.1
1.0
649.8
1.0
592.6
1.0
498.0
1.0
699.7
1.0
773.5
1.0
8,079.1
1.0
332.0
0.5
297.0
0.5
279.0
0.5
312.5
0.5
285.0
0.5
239.5
0.5
336.5
0.5
372.0
0.5
3,885.5
0.5
Hpl 2: Pckg Htg [Sum of dsn coil capacities=945.1 mbh]
Boiler forced draft fan (Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
773.5
1.0
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
698.6
1.0
773.5
1.0
(Misc Accessory Equipment)
372.0
0.5
336.0
0.5
372.0
0.5
352.0
0.5
Hpl 3: HP Htg [Sum of dsn coil capacities=2,271 mbh]
Boiler - 003 [Nominal Capacity/F.L.Rate=2,498 mbh / 29.99 Therms]
799.1
14.4
Gas (therms)
Peak (therms/Hr)
Boiler forced draft fan
1,337.7
15.4
640.9
13.8
(Heating Equipment)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2,777.7
15.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
589.6
2.5
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
118.0
0.5
1,767.7
7.6
1,918.5
7.1
1,827.3
6.6
1,744.6
7.7
1,876.4
8.7
1,898.8
8.5
2,222.6
8.7
22,917.4
8.7
526.4
3.9
597.4
3.9
584.2
3.4
572.7
3.2
567.7
3.0
493.8
2.9
532.6
3.1
6,561.7
3.9
324.0
2.1
278.0
1.7
249.4
1.3
293.6
1.1
284.8
1.8
367.2
1.4
3,810.4
2.2
(Misc Accessory Equipment)
Electric (kWh)
Peak (kW)
154.9
2.5
Cntl panel & interlocks - 0.5 KW
Electric (kWh)
Peak (kW)
279.8
2.5
154.9
2.5
(Misc Accessory Equipment)
31.0
0.5
56.0
0.5
31.0
0.5
0.0
0.0
Sys 1: Admin VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=22,315 cfm / 8.68 kW]
Electric (kWh)
Peak (kW)
2,233.4
8.7
1,933.1
8.7
1,927.2
8.4
1,694.3
8.7
Sys 2: Admin FC
Fan coil supply fan [DsnAirflow/F.L.Rate=10,453 cfm / 4.07 kW]
Electric (kWh)
Peak (kW)
532.4
3.3
524.7
3.2
563.0
3.2
(Main Clg Fan)
494.3
3.7
Sys 3: Campus Center FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,916 cfm / 2.18 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
SBCC TRACE.TRC
321.4
1.4
339.5
1.5
354.6
1.5
(Main Clg Fan)
1,873.5
6.0
280.4
1.5
572.6
3.8
(Main Clg Fan)
381.8
1.9
335.8
2.2
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 25 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 4: Campus Center Dual Deck
AF Centrifugal const vol [DsnAirflow/F.L.Rate=4,072 cfm / 6.79 kW]
Electric (kWh)
Peak (kW)
1,818.5
6.0
1,713.8
6.8
1,943.9
6.8
1,954.3
6.8
Sys 5: Campus Center Packg RTU-1
AF Centrifugal const vol [DsnAirflow/F.L.Rate=3,417 cfm / 3.80 kW]
Electric (kWh)
Peak (kW)
768.3
3.6
736.8
3.6
893.4
3.6
1,011.3
3.6
Sys 6: Drama/Music HP
AF Centrifugal const vol [DsnAirflow/F.L.Rate=22,534 cfm / 8.76 kW]
Electric (kWh)
Peak (kW)
1,498.8
6.0
1,506.7
6.5
1,629.1
6.4
1,489.2
6.4
Sys 7: Drama/Music Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=1,638 cfm / 0.64 kW]
Electric (kWh)
Peak (kW)
108.4
0.6
91.3
0.6
92.2
0.6
May
705.5
4.6
663.3
4.4
752.8
4.7
2,232.3
6.8
2,898.9
25.0
2,870.8
25.0
3,095.5
25.0
9,288.6
54.0
8,750.5
58.0
9,426.5
57.9
Sept
Oct
Nov
Dec
Total
2,251.7
6.8
2,275.6
6.8
2,202.7
6.8
2,118.5
6.8
1,792.6
6.8
1,847.8
6.8
24,228.1
6.8
1,215.5
3.8
1,191.9
3.8
1,127.7
3.8
1,004.4
3.6
851.7
3.6
748.0
3.5
11,791.9
3.8
1,584.6
7.0
1,782.8
7.1
1,741.5
7.0
1,721.4
7.4
1,647.5
6.1
1,413.3
6.1
1,624.2
6.1
19,306.4
7.4
61.4
0.6
72.8
0.6
68.0
0.6
67.4
0.6
74.3
0.6
78.6
0.6
107.0
0.6
941.9
0.6
972.9
5.8
957.6
5.4
933.9
4.7
870.7
4.5
720.4
4.5
648.6
3.7
9,803.2
5.8
4,233.5
25.0
4,072.2
25.0
3,843.9
25.0
3,316.0
25.0
2,563.4
25.0
2,935.0
25.0
40,525.1
25.0
10,437.4
60.7
10,337.5
60.4
10,581.4
61.3
9,653.8
59.7
7,988.8
53.8
9,108.4
50.7
112,683.8
61.3
2,076.4
6.8
1,108.3
3.6
1,134.8
3.8
(Main Clg Fan)
1,667.2
6.2
(Main Clg Fan)
56.6
0.6
64.0
0.6
790.1
4.9
3,202.0
25.0
8,402.6
55.9
(Main Clg Fan)
902.7
5.5
884.8
5.6
(Main Clg Fan)
3,698.3
25.0
Sys 10: Humanities VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=37,423 cfm / 62.37 kW]
Electric (kWh)
Peak (kW)
Aug
(Main Clg Fan)
Sys 9: EBS VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=14,929 cfm / 24.88 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
Sys 8: Drama/Music MZU
90.1-04 Min VAV AF Centrifugal [DsnAirflow/F.L.Rate=8,044 cfm / 6.03 kW]
Electric (kWh)
Peak (kW)
June
3,795.6
25.0
(Main Clg Fan)
9,360.5
58.5
9,347.8
59.2
Sys 11: Humanities Fan Coil
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 26 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
Sys 11: Humanities Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=6,103 cfm / 2.71 kW]
Electric (kWh)
Peak (kW)
197.3
2.4
225.7
2.3
288.5
2.4
21.6
0.2
22.0
0.2
28.7
0.2
397.6
2.6
3,117.1
11.6
2,740.5
11.6
2,802.4
11.6
2,103.8
8.3
Sys 14: OE Pckg AH
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,211 cfm / 4.28 kW]
Electric (kWh)
Peak (kW)
352.3
3.4
353.3
3.4
362.7
3.4
322.4
3.4
Sys 15: PE Heat Pump
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,277 cfm / 5.58 kW]
Electric (kWh)
Peak (kW)
309.8
1.3
312.1
1.3
345.3
1.4
298.3
1.1
Sys 16: PE VAV Htg Only
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=1,200 cfm / 1.33 kW]
Electric (kWh)
Peak (kW)
37.2
1.3
12.1
0.4
3.3
0.1
Sys 17: PS Fan Coil Htg Only
Fan coil supply fan [DsnAirflow/F.L.Rate=1,789 cfm / 0.80 kW]
Electric (kWh)
Peak (kW)
290.5
0.8
270.9
0.8
301.8
0.8
July
Aug
Sept
Oct
Nov
Dec
Total
391.9
2.7
420.2
2.7
387.7
2.5
337.3
2.3
293.3
1.8
214.6
2.1
201.5
2.2
3,663.8
2.7
44.5
0.2
48.1
0.2
46.3
0.2
43.0
0.2
35.7
0.2
27.5
0.2
20.7
0.2
417.6
0.2
2,092.4
10.7
2,048.2
9.7
2,067.1
9.2
2,315.6
8.7
2,602.6
11.6
3,226.6
11.6
29,409.4
11.6
422.3
3.4
424.8
3.4
439.3
3.7
397.7
3.4
314.5
3.4
365.8
3.2
4,519.3
4.3
440.9
3.8
370.8
3.8
340.9
3.6
354.8
2.0
307.3
1.0
273.1
1.2
4,020.1
3.8
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.3
0.0
0.4
0.0
31.4
0.4
85.5
1.3
285.7
0.8
315.4
0.8
317.5
0.8
305.0
0.8
293.1
0.8
287.1
0.8
295.5
0.8
3,538.5
0.8
(Main Clg Fan)
36.6
0.2
42.7
0.2
Sys 13: LRC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=12,960 cfm / 11.52 kW]
Electric (kWh)
Peak (kW)
June
(Main Clg Fan)
308.3
2.3
Sys 12: IDC Fan Coil
Fan coil supply fan [DsnAirflow/F.L.Rate=349.5 cfm / 0.16 kW]
Electric (kWh)
Peak (kW)
May
0.5
0.0
(Main Clg Fan)
2,288.1
9.6
2,005.2
10.2
(Main Clg Fan)
387.1
3.4
377.1
4.3
(Main Clg Fan)
337.6
3.6
329.3
3.7
(Main Clg Fan)
0.3
0.0
(Main Clg Fan)
286.2
0.8
289.8
0.8
Sys 18: Stdnt Srv VAV
Project Name:
Dataset Name:
SBCC TRACE.TRC
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 27 of 28
EQUIPMENT ENERGY CONSUMPTION
By SC ENGINEERS
Alternative: 4
SBCC Data Rm TR
------- Monthly Consumption -------
Equipment - Utility
Jan
Feb
Mar
Apr
May
Sys 18: Stdnt Srv VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=21,892 cfm / 17.03 kW]
Electric (kWh)
Peak (kW)
3,500.5
16.5
3,104.2
16.4
3,527.2
17.1
2,977.0
17.1
1,191.0
13.4
1,266.6
13.7
1,466.8
13.7
1,580.7
13.9
Sys 20: IDC VAV
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=3,237 cfm / 5.40 kW]
Electric (kWh)
Peak (kW)
1,114.1
4.1
1,011.6
4.3
1,142.9
4.5
1,158.2
4.5
8,067.7
79.8
8,722.5
81.8
8,841.8
82.9
8,082.4
83.4
Sys 22: BC FC
AF Centrifugal const vol [DsnAirflow/F.L.Rate=9,729 cfm / 10.81 kW]
Electric (kWh)
Peak (kW)
1,786.2
7.4
1,663.0
7.7
1,811.1
7.9
1,395.2
8.0
Sys 23: BC Hydronic AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=6,463 cfm / 10.77 kW]
Electric (kWh)
Peak (kW)
Project Name:
Dataset Name:
1,306.6
4.6
SBCC TRACE.TRC
1,199.1
5.8
1,218.7
6.3
983.9
6.3
Aug
Sept
Oct
Nov
Dec
Total
3,144.6
17.1
3,358.9
17.1
3,235.8
17.1
3,105.0
17.1
3,366.0
17.1
3,172.6
17.1
3,337.8
16.1
39,101.7
17.1
2,176.2
14.4
1,940.5
15.3
1,743.7
15.3
1,630.3
14.4
1,306.0
13.9
1,135.3
13.3
19,307.7
15.3
1,276.4
4.7
1,283.5
4.7
1,268.8
4.5
1,246.5
4.6
1,137.9
4.6
1,097.5
4.3
14,143.3
4.7
11,210.6
87.2
10,642.2
87.1
10,272.6
85.7
9,028.5
82.6
7,146.0
79.8
7,868.0
77.7
109,783.5
88.3
1,541.3
8.7
1,527.2
8.6
1,620.4
8.6
1,690.1
8.1
1,426.2
7.9
1,739.0
7.3
19,277.6
8.7
1,101.9
7.9
1,083.4
7.7
1,093.0
7.1
1,170.8
6.0
1,023.8
4.7
1,210.6
3.9
13,490.4
7.9
(Main Clg Fan)
1,908.9
14.4
1,961.8
14.6
(Main Clg Fan)
1,214.3
4.6
Sys 21: Portopia HP
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=106,096 cfm / 88.41 kW]
Electric (kWh)
Peak (kW)
July
(Main Clg Fan)
3,272.0
17.1
Sys 19: Admin Pckg AHU
FC Centrifugal var freq drv [DsnAirflow/F.L.Rate=13,075 cfm / 15.25 kW]
Electric (kWh)
Peak (kW)
June
1,191.8
4.6
(Main Clg Fan)
10,066.7
86.6
9,834.4
88.3
(Main Clg Fan)
1,653.6
8.4
1,424.3
8.5
(Main Clg Fan)
1,100.2
7.0
998.5
7.1
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Alternative - 4 Equipment Energy Consumption report page 28 of 28
PEAK COOLING LOADS
MAIN SYSTEM
By SC ENGINEERS
SPACE
Floor
Area
ft²
System Zone Room
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
58.1
58.1
58.1
51.6
51.6
51.6
55.0
55.0
55.0
56.7
56.7
56.7
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.8
57.8
57.8
52.5
52.5
52.5
69.6
69.6
69.6
57.6
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
19,718
19,718
19,718
27,717
27,717
27,717
4,324
4,324
4,324
8,470
8,470
8,470
10,677
10,677
10,677
33,208
33,208
33,208
3,217
3,217
3,217
2,438
2,438
2,438
46,648
46,648
46,648
8,293
8,293
8,293
13,658
13,658
13,658
178,368
649
649
649
6,690
6,690
6,690
0
0
0
601
601
601
686
686
686
2,099
2,099
2,099
935
935
935
708
708
708
1,884
1,884
1,884
1,710
1,710
1,710
-741
-741
-741
15,221
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
21,552
21,552
21,552
27,487
27,487
27,487
4,459
4,459
4,459
10,580
10,580
10,580
12,077
12,077
12,077
35,790
35,790
35,790
8,578
8,578
8,578
6,500
6,500
6,500
64,856
64,856
64,856
8,454
8,454
8,454
27,101
27,101
27,101
227,433
Coil
Latent
Load
Btu/h
Alternative 1
spc_A 121 Office UC_0
Zone - 077
Zone - 077
spc_A 130A Class? FC1-4_0
Zone - 078
Zone - 078
spc_A 237-241 Office C_0
Zone - 093
Zone - 093
spc_A 202A Office D_0
Zone - 094
Zone - 094
spc_A 202A Office B_0
Zone - 095
Zone - 095
spc_A 202A Office C_0
Zone - 096
Zone - 096
spc_A 201 Office C_0
Zone - 097
Zone - 097
spc_A 200H-J Office C_0
Zone - 098
Zone - 098
spc_A 200 Office C_0
Zone - 099
Zone - 099
spc_A 210A-B Stairs C_0
Zone - 100
Zone - 100
spc_A 121 Restroom FC05_0
Zone - 118
Zone - 118
Admin FC
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
348
348
348
2,606
2,606
2,606
0
0
0
344
344
344
238
238
238
891
891
891
353
353
353
267
267
267
1,011
1,011
1,011
1,111
1,111
1,111
734
734
734
7,905
10 /16
10 /16
10 /15
10 /15
7 /16
7 /16
6 /10
6 /10
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
7 /18
7 /18
10 /16
10 /16
79
79
79
80
80
80
76
76
76
65
65
65
76
76
76
73
73
73
75
75
75
75
75
75
79
79
79
73
73
73
79
79
79
77
64
64
64
63
63
63
66
66
66
58
58
58
67
67
67
65
65
65
66
66
66
66
66
66
64
64
64
65
65
65
64
64
64
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.9
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
77
77
77
77
77
77
76
76
76
76
76
76
76
76
76
73
73
73
75
75
75
75
75
75
77
77
77
73
73
73
77
77
77
77
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
65
65
65
66
66
66
66
66
66
67
67
67
65
65
65
67
67
67
67
58.4
58.4
58.4
51.8
51.8
51.8
55.0
55.0
55.0
63.1
63.1
63.1
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.9
57.9
57.9
52.5
52.5
52.5
69.8
69.8
69.8
58.0
1,735
1,735
1,735
18,165
18,165
18,165
0
0
0
1,536
1,536
1,536
1,234
1,234
1,234
3,864
3,864
3,864
1,611
1,611
1,611
1,221
1,221
1,221
5,037
5,037
5,037
2,205
2,205
2,205
-7,656
-7,656
-7,656
28,952
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 1 of 100
SPACE
Floor
Area
ft²
System Zone Room
Admin FC
spc_A 161/162 Class C_0
Zone - 091
Zone - 091
spc_A 160 Wrk Rm C_0
Zone - 092
Zone - 092
spc_A 236A/B Offices_0
Zone - 113
Zone - 113
spc_A 244/246 Office C_0
Zone - 114
Zone - 114
spc_A 242/243 Class C_0
Zone - 115
Zone - 115
spc_A 238-246 Offices C_0
Zone - 116
Zone - 116
spc_A 216/218 Office C_0
Zone - 117
Zone - 117
Admin Pckg AHU
Admin Pckg AHU
spc_A 277F Class_0
Zone - 079
Zone - 079
spc_A 279A Hall C_0
Zone - 080
Zone - 080
spc_A 278A Cond Stair_0
Zone - 081
Zone - 081
spc_A 170/171 Lobby C_0
Zone - 082
Zone - 082
spc_A 172 Wrk Rm C_0
Zone - 083
Zone - 083
spc_A Wrk Rm 173 C_0
Zone - 084
Zone - 084
spc_A 177 Comp C_1
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
7,905
2,273
2,273
2,273
1,806
1,806
1,806
786
786
786
367
367
367
1,839
1,839
1,839
2,547
2,547
2,547
2,057
2,057
2,057
11,676
11,676
1,395
1,395
1,395
7,584
7,584
7,584
321
321
321
1,279
1,279
1,279
2,002
2,002
2,002
671
671
671
626
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
6 /9
6 /9
6 /9
6 /9
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
6/10
6 /10
7 /17
7 /17
6 /10
6 /18
6 /18
6 /10
6 /10
9 /11
9 /11
7 /18
7 /18
6 /9
6 /9
10 /15
10 /15
6 /9
77
62
62
62
62
62
62
75
75
75
75
75
75
79
79
79
65
65
65
75
75
75
65
65
70
70
70
65
65
65
70
70
70
73
73
73
62
62
62
80
80
80
62
67
58
58
58
58
58
58
66
66
66
66
66
66
64
64
64
58
58
58
66
66
66
58
58
63
63
63
58
58
58
63
63
63
65
65
65
58
58
58
63
63
63
58
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.6
54.7
54.7
54.7
54.6
54.6
54.6
49.8
49.8
49.8
49.8
49.8
49.8
55.5
55.5
55.5
57.3
57.3
57.3
49.8
49.8
49.8
55.4
55.4
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,510
2,510
2,510
5,680
5,680
5,680
1,443
1,443
1,443
483
483
483
2,570
2,570
2,570
1,214
1,214
1,214
1,490
160,203
45,748
45,748
45,748
34,617
34,617
34,617
7,681
7,681
7,681
3,589
3,589
3,589
49,570
49,570
49,570
81,320
81,320
81,320
20,104
20,104
20,104
242,629
193,483
46,615
46,615
46,615
105,509
105,509
105,509
26,795
26,795
26,795
8,969
8,969
8,969
47,731
47,731
47,731
22,553
22,553
22,553
27,671
21,247
6,031
6,031
6,031
4,790
4,790
4,790
2,079
2,079
2,079
971
971
971
5,095
5,095
5,095
4,472
4,472
4,472
5,442
5,442
5,442
28,881
25,762
4,376
4,376
4,376
5,555
5,555
5,555
411
411
411
2,208
2,208
2,208
5,370
5,370
5,370
1,747
1,747
1,747
1,303
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
7 /9
7 /9
7 /9
7 /9
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
7 /17
7 /17
7 /16
7 /18
7 /18
7 /16
7 /16
9 /11
9 /11
7 /9
7 /9
7 /9
7 /9
9 /16
9 /16
7 /9
77
64
64
64
64
64
64
75
75
75
75
75
75
77
77
77
76
76
76
75
75
75
76
76
73
73
73
76
76
76
70
70
70
64
64
64
64
64
64
77
77
77
64
67
59
59
59
59
59
59
66
66
66
66
66
66
67
67
67
66
66
66
66
66
66
66
66
65
65
65
66
66
66
63
63
63
59
59
59
59
59
59
67
67
67
59
59.2
55.1
55.1
55.1
54.9
54.9
54.9
49.8
49.8
49.8
49.8
49.8
49.8
55.6
55.6
55.6
64.0
64.0
64.0
49.8
49.8
49.8
58.0
60.0
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,485
2,485
2,485
3,475
3,475
3,475
1,443
1,443
1,443
420
420
420
2,508
2,508
2,508
1,209
1,209
1,209
1,469
211,887
48,957
48,957
48,957
37,048
37,048
37,048
18,754
18,754
18,754
8,763
8,763
8,763
78,514
78,514
78,514
92,985
92,985
92,985
49,087
49,087
49,087
334,108
299,894
66,753
66,753
66,753
177,138
177,138
177,138
30,401
30,401
30,401
10,395
10,395
10,395
48,380
48,380
48,380
23,906
23,906
23,906
28,680
Coil
Latent
Load
Btu/h
30,207
9,347
9,347
9,347
7,420
7,420
7,420
3,579
3,579
3,579
1,672
1,672
1,672
12,862
12,862
12,862
11,426
11,426
11,426
9,369
9,369
9,369
55,677
63,035
9,143
9,143
9,143
15,367
15,367
15,367
511
511
511
2,145
2,145
2,145
8,439
8,439
8,439
4,762
4,762
4,762
2,059
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 2 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 085
Zone - 085
spc_A 174-176 Data C_0
Zone - 086
Zone - 086
spc_A 177 Comp C_0
Zone - 087
Zone - 087
spc_A 179/178 Data C_0
Zone - 088
Zone - 088
spc_A 180E Com Lab C_0
Zone - 089
Zone - 089
spc_A 271-277 Office C_0
Zone - 111
Zone - 111
spc_A 277 Class_0
Zone - 112
Zone - 112
Admin VAV
Admin VAV
spc_BC 237 Class_0
Zone - 334
Zone - 334
spc_BC 221 Lobby_0
Zone - 335
Zone - 335
spc_BC 222 Class_0
Zone - 336
Zone - 336
spc_215-219 Office_0
Zone - 337
Zone - 337
spc_BC 224 Class_0
Zone - 338
Zone - 338
spc_BC 2nd 226/228 Class_0
Zone - 339
Zone - 339
spc_BC 2nd 230 Class_0
Zone - 340
Zone - 340
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
626
626
201
201
201
626
626
626
339
339
339
951
951
951
2,656
2,656
2,656
0
0
0
18,650
18,650
166
166
166
120
120
120
196
196
196
262
262
262
146
146
146
281
281
281
187
187
187
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /9
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
10 /15
10 /15
7 /17
7/17
10 /15
10 /15
9 /15
10 /14
10 /14
7 /16
7 /16
7 /18
7 /18
10 /16
10 /16
9 /11
9 /11
9 /10
9 /10
9 /17
9 /17
62
62
77
77
77
76
76
76
76
76
76
80
80
80
75
75
75
80
80
80
78
78
79
79
79
76
76
76
73
73
73
79
79
79
70
70
70
67
67
67
76
76
76
58
58
67
67
67
66
66
66
66
66
66
63
63
63
66
66
66
63
63
63
66
66
62
62
62
66
66
66
65
65
65
64
64
64
63
63
63
61
61
61
67
67
67
72.0
72.0
70.0
70.0
70.0
72.0
72.0
72.0
70.0
70.0
70.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
71.7
71.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
57.5
57.5
57.5
57.3
57.3
57.3
57.1
57.1
57.1
57.5
57.5
57.5
55.6
55.6
55.6
56.0
56.0
56.0
57.2
57.2
57.2
1,490
1,490
1,917
1,917
1,917
1,042
1,042
1,042
2,037
2,037
2,037
2,646
2,646
2,646
1,344
1,344
1,344
4,175
4,175
4,175
28,551
22,316
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
27,671
27,671
31,338
31,338
31,338
19,354
19,354
19,354
33,300
33,300
33,300
49,154
49,154
49,154
24,971
24,971
24,971
77,551
77,551
77,551
521,509
407,618
6,259
6,259
6,259
3,956
3,956
3,956
14,583
14,583
14,583
10,595
10,595
10,595
5,091
5,091
5,091
11,008
11,008
11,008
15,364
15,364
15,364
1,303
1,303
497
497
497
1,843
1,843
1,843
771
771
771
1,906
1,906
1,906
7,134
7,134
7,134
0
0
0
33,121
44,638
375
375
375
194
194
194
681
681
681
491
491
491
468
468
468
889
889
889
658
658
658
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /9
9 /16
9 /16
9 /16
9 /16
9 /19
9 /19
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /14
9 /14
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
9 /12
9 /12
9 /11
9 /11
9 /17
9 /17
64
64
77
77
77
77
77
77
71
71
71
77
77
77
76
76
76
77
77
77
77
77
77
77
77
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
76
76
76
59
59
67
67
67
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
66
66
66
66
66
66
65
65
65
67
67
67
63
63
63
63
63
63
67
67
67
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
58.2
58.2
58.2
57.3
57.3
57.3
57.1
57.1
57.1
57.7
57.7
57.7
56.5
56.5
56.5
56.3
56.3
56.3
57.2
57.2
57.2
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,469
1,469
1,917
1,917
1,917
1,032
1,032
1,032
2,008
2,008
2,008
2,644
2,644
2,644
1,337
1,337
1,337
4,061
4,061
4,061
26,008
22,285
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
28,680
28,680
33,072
33,072
33,072
19,437
19,437
19,437
33,409
33,409
33,409
51,546
51,546
51,546
32,823
32,823
32,823
77,838
77,838
77,838
651,278
557,619
7,849
7,849
7,849
5,195
5,195
5,195
17,225
17,225
17,225
12,759
12,759
12,759
6,331
6,331
6,331
12,300
12,300
12,300
20,480
20,480
20,480
Coil
Latent
Load
Btu/h
2,059
2,059
835
835
835
3,541
3,541
3,541
1,453
1,453
1,453
5,384
5,384
5,384
12,103
12,103
12,103
0
0
0
65,740
78,660
1,025
1,025
1,025
278
278
278
1,269
1,269
1,269
1,313
1,313
1,313
701
701
701
1,464
1,464
1,464
1,309
1,309
1,309
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 3 of 100
SPACE
System Zone Room
Floor
Area
ft²
spc_BC 115/116 Office_0
Peak
Zone - 351
Peak
Zone - 351
Block
spc_BC Office 137/139/141/142_0 Peak
Zone - 352
Peak
Zone - 352
Block
spc_BC 143 Office_0
Peak
Zone - 353
Peak
Zone - 353
Block
spc_BC 109 Class_0
Peak
Zone - 354
Peak
Zone - 354
Block
spc_BC 108 Class_0
Peak
Zone - 355
Peak
Zone - 355
Block
spc_BC 106 Class_0
Peak
Zone - 356
Peak
Zone - 356
Block
spc_BC 105 Class_0
Peak
Zone - 357
Peak
Zone - 357
Block
spc_BC 101 Class_0
Peak
Zone - 358
Peak
Zone - 358
Block
BC FC
Peak
BC FC
Block
spc_BC 130 Cafe/Kitchen_0
Peak
Zone - 341
Peak
Zone - 341
Block
spc_BC AH-2 245 Lecture_0
Peak
Zone - 342
Peak
Zone - 342
Block
spc_BC AH-3 301 Class_0
Peak
Zone - 343
Peak
Zone - 343
Block
spc_BC AH-4 302 Class_0
Peak
Zone - 344
Peak
Zone - 344
Block
spc_BC 306 Office (AH-5)_0
Peak
spc_BC 307-312 Office (AH-5)_0 Peak
spc_BC AH-5 304 Hall_0
Peak
Zone - 345
Peak
Zone - 345
Block
155
155
155
103
103
103
123
123
123
248
248
248
228
228
228
287
287
287
308
308
308
696
696
696
3,507
3,507
1,908
1,908
1,908
809
809
809
162
162
162
188
188
188
17
107
518
642
642
Project Name:
Dataset Name:
SBCC TRACE.TRC
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /12
9 /12
10 /16
10 /16
10 /16
10 /16
9 /12
9 /12
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /12
7 /19
7 /19
9 /13
9 /13
7 /10
7 /10
11 /13
11 /13
7 /18
10 /16
7 /18
10 /16
73
73
73
79
79
79
79
79
79
73
73
73
73
73
73
70
70
70
70
70
70
70
70
70
73
73
71
71
71
75
75
75
67
67
67
71
71
71
73
79
73
79
79
63
63
63
64
64
64
64
64
64
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
64
64
64
65
65
65
60
60
60
58
58
58
65
64
65
64
64
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
51.8
51.8
51.8
58.7
58.7
58.7
53.9
53.9
53.9
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.8
56.8
49.0
49.0
49.0
48.5
48.5
48.5
57.5
57.5
57.5
55.0
55.0
55.0
57.7
59.1
54.7
58.0
58.0
237
237
237
38
38
38
797
797
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
4,204
4,204
4,204
848
848
848
11,800
11,800
11,800
5,234
5,234
5,234
6,925
6,925
6,925
15,674
15,674
15,674
16,788
16,788
16,788
36,297
36,297
36,297
164,625
128,212
25,681
25,681
25,681
8,768
8,768
8,768
9,949
9,949
9,949
14,106
14,106
14,106
1,203
14,924
6,067
22,194
20,846
340
340
340
192
192
192
231
231
231
766
766
766
704
704
704
918
918
918
985
985
985
2,230
2,230
2,230
10,125
10,014
7,496
7,496
7,496
2,709
2,709
2,709
457
457
457
435
435
435
41
199
801
1,041
657
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /12
9 /12
9 /17
9 /17
10 /16
10 /16
9 /13
9 /13
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /13
7 /19
7 /19
9 /14
9 /14
7 /10
7 /10
9 /15
9 /15
7 /18
10 /16
7 /18
9 /17
73
73
73
76
76
76
79
79
79
75
75
75
73
73
73
70
70
70
70
70
70
70
70
70
75
75
71
71
71
77
77
77
67
67
67
78
78
78
73
79
73
76
76
63
63
63
67
67
67
64
64
64
65
65
65
63
63
63
63
63
63
63
63
63
63
63
63
65
65
64
64
64
66
66
66
60
60
60
66
66
66
65
64
65
67
67
56.1
56.1
56.1
52.2
52.2
52.2
58.7
58.7
58.7
54.5
54.5
54.5
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.9
60.6
49.0
49.0
49.0
48.7
48.7
48.7
57.5
57.5
57.5
57.3
57.3
57.3
57.7
59.1
54.7
58.0
59.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
237
237
237
38
38
38
797
797
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
5,546
5,546
5,546
1,020
1,020
1,020
13,862
13,862
13,862
6,369
6,369
6,369
8,775
8,775
8,775
17,730
17,730
17,730
19,220
19,220
19,220
40,708
40,708
40,708
195,368
154,845
28,282
28,282
28,282
10,394
10,394
10,394
11,797
11,797
11,797
17,273
17,273
17,273
1,823
19,637
7,596
29,057
27,346
Coil
Latent
Load
Btu/h
517
517
517
535
535
535
308
308
308
1,430
1,430
1,430
1,096
1,096
1,096
1,494
1,494
1,494
1,603
1,603
1,603
3,631
3,631
3,631
17,976
18,247
13,513
13,513
13,513
4,960
4,960
4,960
624
624
624
1,481
1,481
1,481
75
265
1,033
1,373
1,870
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 4 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_BC AH-6 315 Lab_0
Zone - 346
Zone - 346
spc_BC AH-7 314 Class_0
Zone - 347
Zone - 347
spc_BC AH-8 313_0
Zone - 348
Zone - 348
BC Hydronic AHU
BC Hydronic AHU
spc_CC 108 C_0
Zone - 120
Zone - 120
spc_CC 106 Mechanical C_0
Zone - 121
Zone - 121
spc_CC 203 Storage_0
Zone - 122
Zone - 122
spc_CC 202 Storage_0
Zone - 123
Zone - 123
spc_CC 201 Eating Area C_0
Zone - 124
Zone - 124
Campus Center Dual Deck
Campus Center Dual Deck
spc_CC Class 122-126 C_0
Zone - 119
Zone - 119
Campus Center FC
Campus Center FC
spc_CC 228 Comp C_0
Zone - 125
Zone - 125
Bookstore 1
Zone - 362
Zone - 362
Bookstore 2
Zone - 363
Zone - 363
Bookstore 3
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
181
181
181
183
183
183
518
518
518
4,592
4,592
381
381
381
530
530
530
159
159
159
133
133
133
1,974
1,974
1,974
3,176
3,176
1,023
1,023
1,023
1,023
1,023
519
519
519
915
915
915
915
915
915
915
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
10 /16
6 /9
6 /9
9 /16
9 /16
10 /15
10 /16
10 /16
9 /17
9/17
9 /17
9 /17
9 /12
9 /12
9 /12
9 /12
10 /14
6 /18
6 /18
6 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
79
79
79
62
62
62
77
77
77
80
80
79
79
79
76
76
76
76
76
76
73
73
73
73
73
73
79
79
70
70
70
70
70
76
76
76
76
76
76
76
76
76
76
64
64
64
58
58
58
67
67
67
63
63
64
64
64
67
67
67
67
67
67
63
63
63
63
63
63
62
62
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
58.3
58.3
58.3
56.9
56.9
56.9
55.0
55.0
55.0
55.2
55.2
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.1
57.1
57.1
57.1
57.1
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
902
902
902
435
435
435
1,005
1,005
1,005
6,464
6,464
797
797
797
480
480
480
556
556
556
430
430
430
1,808
1,808
1,808
4,073
4,073
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
13,789
13,789
13,789
7,351
7,351
7,351
19,025
19,025
19,025
120,862
101,266
12,551
12,551
12,551
11,849
11,849
11,849
8,761
8,761
8,761
6,778
6,778
6,778
28,473
28,473
28,473
68,413
57,628
64,980
64,980
64,980
64,980
64,980
17,432
17,432
17,432
11,760
11,760
11,760
10,160
10,160
10,160
10,160
394
394
394
486
486
486
1,924
1,924
1,924
14,942
6,374
167
167
167
761
761
761
277
277
277
137
137
137
4,445
4,445
4,445
5,787
5,745
3,184
3,184
3,184
3,184
3,184
1,513
1,513
1,513
3,754
3,754
3,754
2,839
2,839
2,839
2,839
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /17
9 /17
9 /13
9 /13
9 /13
9 /13
9 /14
7 /18
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
77
77
75
75
75
77
77
77
77
77
76
76
76
76
76
76
76
76
76
75
75
75
75
75
75
77
77
73
73
73
73
73
76
76
76
76
76
76
76
76
76
76
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
65
65
65
65
65
66
66
66
66
66
66
66
66
66
66
58.5
58.5
58.5
61.5
61.5
61.5
55.0
55.0
55.0
55.8
58.3
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.4
57.4
57.4
57.4
57.4
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
902
902
902
435
435
435
1,005
1,005
1,005
6,464
6,464
784
784
784
477
477
477
554
554
554
414
414
414
1,746
1,746
1,746
3,974
3,459
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
18,690
18,690
18,690
9,470
9,470
9,470
25,235
25,235
25,235
150,199
134,479
15,748
15,748
15,748
15,813
15,813
15,813
13,075
13,075
13,075
9,068
9,068
9,068
33,559
33,559
33,559
87,263
75,402
69,485
69,485
69,485
69,485
69,485
22,424
22,424
22,424
18,552
18,552
18,552
17,188
17,188
17,188
17,188
Coil
Latent
Load
Btu/h
1,012
1,012
1,012
1,133
1,133
1,133
3,625
3,625
3,625
27,722
25,060
1,787
1,787
1,787
1,129
1,129
1,129
379
379
379
204
204
204
12,956
12,956
12,956
16,454
17,396
6,613
6,613
6,613
6,613
6,613
2,598
2,598
2,598
6,278
6,278
6,278
5,361
5,361
5,361
5,361
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 5 of 100
SPACE
System Zone Room
Floor
Area
ft²
Zone - 364
Peak
Zone - 364
Block
Bookstore 4
Peak
Zone - 365
Peak
Zone - 365
Block
Bookstore 5
Peak
Zone - 366
Peak
Zone - 366
Block
Bookstore 6
Peak
Zone - 367
Peak
Zone - 367
Block
Campus Center Packg RTU-1
Peak
Campus Center Packg RTU-1
Block
spc_DM FC-Music Office_0
Peak
Zone - 137
Peak
Zone - 137
Block
Peak
spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0
Zone - 138
Peak
Zone - 138
Block
spc_DM FC 3-1 Dress Rms Int_0 Peak
Zone - 139
Peak
Zone - 139
Block
spc_DM FC 3-1 Dress Rms_0
Peak
Zone - 140
Peak
Zone - 140
Block
Drama/Music Fan Coil
Peak
Drama/Music Fan Coil
Block
spc_HP-9 Office_0
Peak
Zone - 126
Peak
Zone - 126
Block
spc_DM HP-7 Storage_0
Peak
Zone - 127
Peak
Zone - 127
Block
spc_DM HP-7 Dress Rm_0
Peak
Zone - 128
Peak
Zone - 128
Block
spc_DM HP 3/4 Class_0
Peak
Zone - 129
Peak
Zone - 129
Block
spc_DM HP-2 Class_0
Peak
Zone - 130
Peak
Zone - 130
Block
spc_DM HP-5 Performance Rm_0 Peak
915
915
915
915
915
915
915
915
915
915
915
6,007
6,007
338
338
338
892
892
892
267
267
267
327
327
327
1,824
1,824
121
121
121
57
57
57
9,797
9,797
9,797
926
926
926
569
569
569
1,176
Project Name:
Dataset Name:
SBCC TRACE.TRC
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
7/17
7 /17
7 /16
7 /16
10 /16
10 /16
9 /17
9 /12
9 /12
10 /15
10 /15
10 /15
10 /15
6 /9
6 /9
11 /13
11 /13
9 /12
76
76
76
76
76
76
76
76
76
76
76
76
76
79
79
79
75
75
75
76
76
76
79
79
79
76
76
73
73
73
80
80
80
80
80
80
62
62
62
71
71
71
73
66
66
66
66
66
66
66
66
66
66
66
66
66
64
64
64
66
66
66
66
66
66
64
64
64
67
67
63
63
63
63
63
63
63
63
63
58
58
58
58
58
58
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
51.0
51.0
56.4
56.4
56.4
54.3
54.3
54.3
44.5
44.5
44.5
58.3
58.3
58.3
55.7
55.7
57.0
57.0
57.0
54.8
54.8
54.8
51.3
51.3
51.3
55.4
55.4
55.4
59.2
59.2
59.2
53.5
404
404
404
404
404
404
404
404
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
79,989
79,989
8,123
8,123
8,123
9,831
9,831
9,831
2,946
2,946
2,946
8,853
8,853
8,853
29,753
27,815
4,747
4,747
4,747
261
261
261
99,554
99,554
99,554
21,837
21,837
21,837
35,452
35,452
35,452
27,637
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
19,459
19,459
633
633
633
1,432
1,432
1,432
1,098
1,098
1,098
269
269
269
3,432
4,394
263
263
263
35
35
35
25,148
25,148
25,148
2,451
2,451
2,451
1,082
1,082
1,082
4,324
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /17
9 /13
9 /13
7 /16
7 /16
9 /16
9 /16
7 /16
7 /16
9 /13
9 /13
7 /15
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
75
75
75
77
77
77
79
79
79
76
76
75
75
75
76
76
76
77
77
77
76
76
76
75
75
75
77
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
64
64
64
67
67
65
65
65
66
66
66
67
67
67
66
66
66
65
65
65
66
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
51.0
51.0
56.5
56.5
56.5
54.3
54.3
54.3
45.0
45.0
45.0
58.3
58.3
58.3
55.8
56.8
57.6
57.6
57.6
55.8
55.8
55.8
51.5
51.5
51.5
59.2
59.2
59.2
60.5
60.5
60.5
59.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
404
404
404
404
404
404
404
404
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
126,914
126,914
12,772
12,772
12,772
21,797
21,797
21,797
2,242
2,242
2,242
10,451
10,451
10,451
47,261
42,971
6,446
6,446
6,446
1,151
1,151
1,151
104,158
104,158
104,158
33,229
33,229
33,229
39,761
39,761
39,761
38,930
Coil
Latent
Load
Btu/h
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
35,683
35,683
1,763
1,763
1,763
1,818
1,818
1,818
2,311
2,311
2,311
330
330
330
6,222
7,103
408
408
408
120
120
120
68,283
68,283
68,283
5,820
5,820
5,820
3,265
3,265
3,265
8,980
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 6 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 131
Zone - 131
spc_DM HP-10 Prop Rm_0
Zone - 132
Zone - 132
spc_DM HP-1 Main Corridor_0
Zone - 133
Zone - 133
spc_DM HP-9 Class_0
Zone - 148
Zone - 148
spc_DM HP-6 Office_0
Zone - 149
Zone - 149
spc_DM HP-8 Class1_0
Zone - 150
Zone - 150
spc_DM PHP-5-2 Offices_0
Zone - 151
Zone - 151
spc_PHP-2-1 Cargo Elevator_0
Zone - 152
Zone - 152
spc_DM PRP-5-1 Restroom_0
Zone - 153
Zone - 153
spc_DM PRP-5-1 Restroom1_0
Zone - 154
Zone - 154
Drama/Music HP
Drama/Music HP
spc_AC-1 Auditorium_0
Zone - 141
Zone - 141
spc_DM AN-2 Corridor_0
Zone - 142
Zone - 142
spc_DM AC-2 Rehearsal Rm_0
Zone - 143
Zone - 143
spc_DM ZN-1 Class_0
Zone - 144
Zone - 144
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,176
1,176
1,131
1,131
1,131
7,381
7,381
7,381
192
192
192
220
220
220
592
592
592
292
292
292
122
122
122
848
848
848
1,177
1,177
1,177
24,602
24,602
3,790
3,790
3,790
701
701
701
1,135
1,135
1,135
417
417
417
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /12
7 /18
7 /18
9 /11
9 /11
10 /15
10 /15
6 /9
6 /9
10 /15
10 /15
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
9 /12
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
6 /18
6 /18
73
73
73
73
73
70
70
70
80
80
80
62
62
62
80
80
80
79
79
79
79
79
79
79
79
79
79
79
79
73
73
80
80
80
75
75
75
80
80
80
70
70
70
63
63
65
65
65
63
63
63
63
63
63
58
58
58
63
63
63
64
64
64
64
64
64
64
64
64
64
64
64
63
63
63
63
63
66
66
66
63
63
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
80.0
80.0
80.0
73.1
73.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
53.5
53.5
57.4
57.4
57.4
56.2
56.2
56.2
51.3
51.3
51.3
58.2
58.2
58.2
51.3
51.3
51.3
52.2
52.2
52.2
58.6
58.6
58.6
79.6
79.6
79.6
79.6
79.6
79.6
58.9
58.9
54.9
54.9
54.9
55.9
55.9
55.9
50.7
50.7
50.7
56.6
56.6
56.6
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
27,637
27,637
36,017
36,017
36,017
106,822
106,822
106,822
1,946
1,946
1,946
10,408
10,408
10,408
6,020
6,020
6,020
2,564
2,564
2,564
4,056
4,056
4,056
538
538
538
747
747
747
358,606
299,869
74,299
74,299
74,299
11,804
11,804
11,804
10,848
10,848
10,848
20,443
20,443
20,443
4,324
4,324
1,740
1,740
1,740
9,194
9,194
9,194
492
492
492
311
311
311
1,521
1,521
1,521
545
545
545
99
99
99
-2,632
-2,632
-2,632
-3,655
-3,655
-3,655
40,918
47,013
9,753
9,753
9,753
1,126
1,126
1,126
2,908
2,908
2,908
1,296
1,296
1,296
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /15
7 /17
7 /17
9 /11
9 /11
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
77
77
75
75
75
70
70
70
76
76
76
65
65
65
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
77
77
75
75
75
77
77
77
73
73
73
66
66
66
66
66
63
63
63
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
65
65
65
59.5
59.5
57.8
57.8
57.8
56.2
56.2
56.2
51.4
51.4
51.4
58.8
58.8
58.8
51.5
51.5
51.5
52.4
52.4
52.4
58.8
58.8
58.8
79.7
79.7
79.7
79.7
79.7
79.7
59.7
62.3
55.5
55.5
55.5
55.9
55.9
55.9
51.3
51.3
51.3
56.7
56.7
56.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
38,930
38,930
57,496
57,496
57,496
120,423
120,423
120,423
5,018
5,018
5,018
11,069
11,069
11,069
6,298
6,298
6,298
2,691
2,691
2,691
6,557
6,557
6,557
5,343
5,343
5,343
7,418
7,418
7,418
445,988
374,351
83,988
83,988
83,988
13,640
13,640
13,640
13,026
13,026
13,026
22,815
22,815
22,815
8,980
8,980
2,459
2,459
2,459
11,397
11,397
11,397
1,203
1,203
1,203
475
475
475
4,129
4,129
4,129
1,517
1,517
1,517
288
288
288
-46,142
-46,142
-46,142
-64,061
-64,061
-64,061
-1,859
7,013
26,500
26,500
26,500
1,430
1,430
1,430
7,893
7,893
7,893
2,691
2,691
2,691
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 7 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_DM ZN-3 Hall_0
Zone - 145
Zone - 145
spc_DM Zn-3 Offices_0
Zone - 146
Zone - 146
spc_ZN-3 Conf_0
Zone - 147
Zone - 147
spc_DM Scene Shop HV-1_0
Zone - 155
Zone - 155
Drama/Music MZU
Drama/Music MZU
spc_EBS 217/Storage C_0
Zone - 156
Zone - 156
spc_EBS 215 Class C_0
Zone - 157
Zone - 157
spc_EBS 209 Class C_0
Zone - 158
Zone - 158
spc_EBS 210 Class C_0
Zone - 159
Zone - 159
spc_EBS 109/127 Lobby C_0
Zone - 160
Zone - 160
spc_EBS 125 Class C_0
Zone - 161
Zone - 161
spc_EBS 102 Class C_0
Zone - 162
Zone - 162
spc_EBS 123 Class C_0
Zone - 163
Zone - 163
spc_EBS 119 Offices C_0
Zone - 164
Zone - 164
spc_EBS 119 Office C_0
Zone - 165
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
209
209
209
177
177
177
405
405
405
1,711
1,711
1,711
8,545
8,545
2,046
2,046
2,046
758
758
758
1,358
1,358
1,358
1,333
1,333
1,333
1,771
1,771
1,771
396
396
396
1,332
1,332
1,332
1,622
1,622
1,622
399
399
399
306
306
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
10 /16
10 /16
10 /16
6 /10
6 /10
10 /13
10 /13
9 /16
7 /15
7/15
7 /16
7 /16
10 /15
10 /15
7 /18
7 /18
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
79
79
79
79
79
79
65
65
65
77
77
77
77
77
77
77
77
76
76
76
80
80
80
73
73
73
75
75
75
73
73
73
73
73
73
73
73
73
75
75
75
75
75
64
64
64
64
64
64
58
58
58
59
59
59
67
67
66
66
66
66
66
66
63
63
63
65
65
65
66
66
66
65
65
65
65
65
65
65
65
65
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.9
49.9
49.9
51.7
51.7
51.7
50.6
50.6
50.6
57.7
57.7
57.7
55.4
55.4
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
24
24
24
64
64
64
206
206
206
1,561
1,561
1,561
8,045
8,045
931
931
931
493
493
493
1,547
1,547
1,547
1,511
1,511
1,511
744
744
744
473
473
473
2,019
2,019
2,019
1,486
1,486
1,486
309
309
309
177
177
583
583
583
1,443
1,443
1,443
4,907
4,907
4,907
24,799
24,799
24,799
149,125
129,890
18,050
18,050
18,050
9,553
9,553
9,553
29,992
29,992
29,992
29,286
29,286
29,286
14,421
14,421
14,421
9,178
9,178
9,178
39,142
39,142
39,142
28,811
28,811
28,811
5,997
5,997
5,997
3,436
3,436
169
169
169
330
330
330
1,311
1,311
1,311
3,134
3,134
3,134
20,027
30,017
3,114
3,114
3,114
2,661
2,661
2,661
3,489
3,489
3,489
4,607
4,607
4,607
2,924
2,924
2,924
1,369
1,369
1,369
4,604
4,604
4,604
5,608
5,608
5,608
1,057
1,057
1,057
811
811
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
9 /14
9 /14
9 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /17
77
77
77
76
76
76
77
77
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
75
75
75
75
75
75
73
73
73
73
73
73
75
75
75
75
75
75
75
75
67
67
67
67
67
67
67
67
67
66
66
66
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
66
66
51.4
51.4
51.4
52.3
52.3
52.3
53.5
53.5
53.5
58.2
58.2
58.2
55.9
57.5
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
24
24
24
64
64
64
206
206
206
1,561
1,561
1,561
8,045
8,045
903
903
903
493
493
493
1,515
1,515
1,515
1,493
1,493
1,493
744
744
744
473
473
473
2,019
2,019
2,019
1,454
1,454
1,454
309
309
309
177
177
715
715
715
1,748
1,748
1,748
5,430
5,430
5,430
30,462
30,462
30,462
171,824
156,601
40,996
40,996
40,996
17,369
17,369
17,369
45,366
45,366
45,366
45,809
45,809
45,809
35,058
35,058
35,058
14,006
14,006
14,006
55,862
55,862
55,862
46,115
46,115
46,115
10,829
10,829
10,829
6,764
6,764
Coil
Latent
Load
Btu/h
468
468
468
919
919
919
3,494
3,494
3,494
10,580
10,580
10,580
53,975
55,726
4,331
4,331
4,331
4,766
4,766
4,766
9,476
9,476
9,476
8,212
8,212
8,212
4,199
4,199
4,199
2,548
2,548
2,548
8,567
8,567
8,567
9,995
9,995
9,995
1,822
1,822
1,822
1,398
1,398
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 8 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 165
spc_EBS 116 Office C_0
Zone - 166
Zone - 166
spc_EBS 110-113 Office UC_0
Zone - 167
Zone - 167
spc_EBS 114 Class C_0
Zone - 168
Zone - 168
spc_EBS 115 Class C_0
Zone - 169
Zone - 169
spc_EBS 209 Class UC_0
Zone - 172
Zone - 172
spc_EBS 210 Class C_1
Zone - 173
Zone - 173
spc_EBS 215 Class C_1
Zone - 174
Zone - 174
spc_EBS 218 Office C_0
Zone - 175
Zone - 175
spc_EBS 216 Office C_0
Zone - 176
Zone - 176
EBS VAV
EBS VAV
spc_H 326 Class C_0
Zone - 206
Zone - 206
spc_H 328 Class C_0
Zone - 207
Zone - 207
spc_H 328 Office C_0
Zone - 208
Zone - 208
Humanities Fan Coil
Humanities Fan Coil
spc_H 104/107/112 Art C_0
Zone - 177
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
306
7 /17
156
7 /18
156
156
7 /18
515
7 /18
515
515
7 /18
893 10 /14
893
893 10 /14
1,659
9 /16
1,659
1,659
9 /16
1,334
7 /16
1,334
1,334
7 /16
1,334
7/16
1,334
1,334 7 /16
790
7 /18
790
790
7 /18
70
7 /18
70
70
7 /18
74
7 /17
74
74
7 /17
18,147
18,147 7 /17
845
5 /17
845
845
5 /17
1,818 7 /16
1,818
1,818 7 /16
300
7 /12
300
300
7 /12
2,963
2,963 7 /17
7,121
7 /16
7,121
75
73
73
73
73
73
73
79
79
79
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
72
72
72
76
76
76
73
73
73
75
75
76
76
66
65
65
65
65
65
65
62
62
62
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
63
63
63
66
66
66
63
63
63
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
54.3
54.3
54.3
56.6
56.6
56.5
56.5
177
220
220
220
624
624
624
1,093
1,093
1,093
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,925
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,288
5,288
3,436
4,262
4,262
4,262
12,097
12,097
12,097
21,186
21,186
21,186
31,380
31,380
31,380
16,818
16,818
16,818
16,818
16,818
16,818
14,759
14,759
14,759
2,665
2,665
2,665
826
826
826
308,677
289,380
76,201
76,201
76,201
24,051
24,051
24,051
4,645
4,645
4,645
104,897
101,595
91,368
91,368
811
368
368
368
1,214
1,214
1,214
2,014
2,014
2,014
6,149
6,149
6,149
4,685
4,685
4,685
4,685
4,685
4,685
2,731
2,731
2,731
166
166
166
195
195
195
52,452
52,299
2,350
2,350
2,350
6,371
6,371
6,371
631
631
631
9,352
9,537
24,945
24,945
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /18
7 /18
7 /18
7 /18
9 /14
9 /14
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /17
7 /15
75
73
73
73
73
73
73
77
77
77
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
73
73
73
76
76
76
76
76
76
75
75
77
77
66
65
65
65
65
65
65
66
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
65
65
65
66
66
66
66
66
66
66
66
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
57.2
57.2
57.2
56.7
57.1
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
177
220
220
220
624
624
624
1,079
1,079
1,079
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,801
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,284
5,284
6,764
6,557
6,557
6,557
19,460
19,460
19,460
22,361
22,361
22,361
49,825
49,825
49,825
30,579
30,579
30,579
30,579
30,579
30,579
23,381
23,381
23,381
3,913
3,913
3,913
1,626
1,626
1,626
504,179
486,608
92,686
92,686
92,686
49,932
49,932
49,932
8,423
8,423
8,423
151,042
148,011
99,527
99,527
Coil
Latent
Load
Btu/h
1,398
677
677
677
2,235
2,235
2,235
5,495
5,495
5,495
11,570
11,570
11,570
8,391
8,391
8,391
8,391
8,391
8,391
5,082
5,082
5,082
305
305
305
336
336
336
97,796
94,521
5,460
5,460
5,460
11,390
11,390
11,390
1,341
1,341
1,341
18,190
17,762
43,603
43,603
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 9 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 177
spc_H 102 Class C_0
Zone - 178
Zone - 178
spc_H 106 Office C_0
Zone - 179
Zone - 179
spc_H 2444 Class C_0
Zone - 180
Zone - 180
spc_H 245A/B Class C_0
Zone - 181
Zone - 181
spc_H 226/A office C_0
Zone - 182
Zone - 182
spc_H 208-217 Office C_0
Zone - 183
Zone - 183
spc_H 225 Office C_0
Zone - 184
Zone - 184
spc_H 242/207 Corridor C_0
Zone - 185
Zone - 185
spc_H 123U Art AH-1/23_0
Zone - 186
Zone - 186
spc_H 111 Class C_0
Zone - 187
Zone - 187
spc_H 221/220/204 Class C_0
Zone - 188
Zone - 188
spc_H 232A Class C_0
Zone - 189
Zone - 189
spc_H 239 Class Office_0
Zone - 190
Zone - 190
spc_H 237 Office C_0
Zone - 191
Zone - 191
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
7,121
1,004
1,004
1,004
229
229
229
555
555
555
1,686
1,686
1,686
272
272
272
1,065
1,065
1,065
267
267
267
4,126
4,126
4,126
2,482
2,482
2,482
1,805
1,805
1,805
4,564
4,564
4,564
1,111
1,111
1,111
306
306
306
90
90
90
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
11 /13
11 /13
11 /14
11 /14
11 /14
11 /14
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
7 /17
7 /17
76
76
76
76
75
75
75
76
76
76
75
75
75
71
71
71
73
73
73
73
73
73
79
79
79
75
75
75
76
76
76
77
77
77
76
76
76
77
77
77
75
75
75
66
66
66
66
66
66
66
66
66
66
66
66
66
58
58
58
60
60
60
60
60
60
64
64
64
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
5,288
627
627
627
122
122
122
346
346
346
2,157
2,157
2,157
798
798
798
3,496
3,496
3,496
765
765
765
1,412
1,412
1,412
2,382
2,382
2,382
1,127
1,127
1,127
3,577
3,577
3,577
693
693
693
311
311
311
48
48
48
91,368
10,835
10,835
10,835
2,102
2,102
2,102
5,987
5,987
5,987
37,265
37,265
37,265
13,783
13,783
13,783
60,401
60,401
60,401
13,211
13,211
13,211
24,400
24,400
24,400
41,156
41,156
41,156
19,474
19,474
19,474
61,807
61,807
61,807
11,982
11,982
11,982
5,382
5,382
5,382
828
828
828
24,945
3,519
3,519
3,519
604
604
604
1,944
1,944
1,944
5,523
5,523
5,523
89
89
89
766
766
766
192
192
192
3,332
3,332
3,332
8,130
8,130
8,130
6,325
6,325
6,325
15,809
15,809
15,809
3,891
3,891
3,891
1,060
1,060
1,060
238
238
238
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /15
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
9 /14
9 /14
9 /15
9 /15
9 /15
9 /15
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /15
7 /15
9 /16
9 /16
7 /15
7 /15
9 /17
9 /17
77
77
77
77
76
76
76
77
77
77
77
77
77
77
77
77
78
78
78
78
78
78
77
77
77
76
76
76
77
77
77
77
77
77
77
77
77
77
77
77
76
76
76
66
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
5,284
600
600
600
119
119
119
331
331
331
2,071
2,071
2,071
743
743
743
2,999
2,999
2,999
665
665
665
1,401
1,401
1,401
2,313
2,313
2,313
1,078
1,078
1,078
3,577
3,577
3,577
663
663
663
311
311
311
47
47
47
99,527
11,228
11,228
11,228
2,209
2,209
2,209
6,204
6,204
6,204
40,964
40,964
40,964
15,383
15,383
15,383
74,566
74,566
74,566
13,581
13,581
13,581
25,840
25,840
25,840
45,783
45,783
45,783
20,181
20,181
20,181
67,488
67,488
67,488
12,417
12,417
12,417
5,994
5,994
5,994
871
871
871
Coil
Latent
Load
Btu/h
43,603
6,979
6,979
6,979
1,184
1,184
1,184
3,856
3,856
3,856
11,713
11,713
11,713
999
999
999
4,843
4,843
4,843
1,216
1,216
1,216
9,229
9,229
9,229
17,267
17,267
17,267
12,544
12,544
12,544
27,948
27,948
27,948
7,718
7,718
7,718
1,874
1,874
1,874
467
467
467
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 10 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_H 236 Office C_0
Zone - 192
Zone - 192
spc_H 241 Class C_0
Zone - 193
Zone - 193
spc_H 309-318 Offices C_0
Zone - 194
Zone - 194
spc_H 240 Class C_0
Zone - 195
Zone - 195
spc_H 300 Restrooms C_0
Zone - 196
Zone - 196
spc_H 322 Office C_0
Zone - 197
Zone - 197
spc_H 323 Office C_0
Zone - 198
Zone - 198
spc_H 300H Hall C_0
Zone - 199
Zone - 199
spc_H 202 Class C_0
Zone - 200
Zone - 200
spc_H 205 Office C_0
Zone - 201
Zone - 201
spc_H 205/203 Class C_0
Zone - 202
Zone - 202
spc_H 232B Office C_0
Zone - 203
Zone - 203
spc_H 223 Class C_0
Zone - 204
Zone - 204
spc_H 223U Storage C_0
Zone - 205
Zone - 205
spc_H 306 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
272
272
272
571
571
571
1,012
1,012
1,012
818
818
818
339
339
339
265
265
265
265
265
265
3,593
3,593
3,593
1,118
1,118
1,118
270
270
270
846
846
846
161
161
161
616
616
616
165
165
165
727
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /16
7 /16
11 /14
11 /14
7 /15
7 /15
9 /17
9 /17
11 /14
11 /14
7 /17
7 /17
10 /16
10 /16
8 /10
8 /10
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
75
75
75
76
76
76
73
73
73
77
77
77
76
76
76
73
73
73
75
75
75
79
79
79
67
67
67
75
75
75
76
76
76
75
75
75
76
76
76
77
77
77
76
66
66
66
66
66
66
60
60
60
66
66
66
67
67
67
60
60
60
66
66
66
64
64
64
61
61
61
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
145
145
145
356
356
356
4,319
4,319
4,319
642
642
642
542
542
542
1,069
1,069
1,069
141
141
141
3,898
3,898
3,898
2,401
2,401
2,401
144
144
144
528
528
528
86
86
86
385
385
385
51
51
51
454
2,500
2,500
2,500
6,155
6,155
6,155
74,623
74,623
74,623
11,100
11,100
11,100
14,193
14,193
14,193
18,478
18,478
18,478
2,434
2,434
2,434
67,353
67,353
67,353
41,487
41,487
41,487
2,483
2,483
2,483
9,121
9,121
9,121
1,483
1,483
1,483
6,648
6,648
6,648
876
876
876
7,841
719
719
719
1,999
1,999
1,999
728
728
728
2,834
2,834
2,834
619
619
619
190
190
190
700
700
700
9,908
9,908
9,908
3,433
3,433
3,433
714
714
714
2,962
2,962
2,962
426
426
426
2,159
2,159
2,159
250
250
250
2,546
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /17
9 /17
9 /16
9 /16
9 /15
9 /15
7 /15
7 /15
9 /17
9 /17
9 /15
9 /15
9 /17
9 /17
9 /16
9 /16
9 /11
9 /11
9 /17
9 /17
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
9 /15
9 /15
7 /16
76
76
76
77
77
77
78
78
78
77
77
77
76
76
76
78
78
78
76
76
76
77
77
77
70
70
70
76
76
76
77
77
77
76
76
76
77
77
77
78
78
78
76
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
63
63
63
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
142
142
142
341
341
341
3,657
3,657
3,657
642
642
642
210
210
210
890
890
890
138
138
138
3,839
3,839
3,839
2,239
2,239
2,239
141
141
141
505
505
505
84
84
84
368
368
368
47
47
47
441
2,628
2,628
2,628
6,379
6,379
6,379
87,004
87,004
87,004
12,091
12,091
12,091
14,647
14,647
14,647
21,157
21,157
21,157
2,558
2,558
2,558
126,357
126,357
126,357
45,716
45,716
45,716
2,609
2,609
2,609
9,452
9,452
9,452
1,558
1,558
1,558
6,890
6,890
6,890
878
878
878
19,161
Coil
Latent
Load
Btu/h
1,408
1,408
1,408
3,965
3,965
3,965
4,603
4,603
4,603
5,010
5,010
5,010
4,236
4,236
4,236
1,203
1,203
1,203
1,371
1,371
1,371
24,964
24,964
24,964
5,771
5,771
5,771
1,399
1,399
1,399
5,875
5,875
5,875
835
835
835
4,282
4,282
4,282
357
357
357
4,551
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 11 of 100
SPACE
System Zone Room
Zone - 211
Peak
Zone - 211
Block
spc_H 308 Class H_0
Peak
Zone - 212
Peak
Zone - 212
Block
spc_H 301-307 Classes C_0
Peak
Zone - 213
Peak
Zone - 213
Block
spc_H 301 Class C_0
Peak
Zone - 214
Peak
Zone - 214
Block
spc_H 3281 Hall C_0
Peak
Zone - 215
Peak
Zone - 215
Block
Humanities VAV
Peak
Humanities VAV
Block
spc_IDC 335 Office C_0
Peak
Zone - 220
Peak
Zone - 220
Block
spc_IDC 313 Wrk Rm_0
Peak
Zone - 221
Peak
Zone - 221
Block
spc_IDC 317 Wrk Rm C_0
Peak
Zone - 222
Peak
Zone - 222
Block
spc_IDC 329 C_0
Peak
Zone - 223
Peak
Zone - 223
Block
IDC Fan Coil
Peak
IDC Fan Coil
Block
Peak
spc_IDC 102/103/104/109 Int Class_0
Zone - 216
Peak
Zone - 216
Block
spc_IDC 205 Class C_0
Peak
Zone - 217
Peak
Zone - 217
Block
spc_IDC 211/210 Class_0
Peak
Zone - 218
Peak
Zone - 218
Block
spc_IDC 333 Office_0
Peak
Zone - 219
Peak
Zone - 219
Block
IDC VAV
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
727
727
512
512
512
3,348
3,348
3,348
633
633
633
228
228
228
42,441
42,441
107
107
107
206
206
206
171
171
171
102
102
102
586
586
3,318
3,318
3,318
460
460
460
1,001
1,001
1,001
414
414
414
5,194
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /16
7 /16
10 /15
7/17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
10 /15
10 /15
10 /15
10 /15
10 /15
10 /15
10 /17
10 /17
76
76
76
76
76
77
77
77
76
76
76
76
76
76
80
80
75
75
75
76
76
76
76
76
76
76
76
76
76
76
80
80
80
80
80
80
80
80
80
77
77
77
80
66
66
66
66
66
66
66
66
66
66
66
66
66
66
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
63
63
63
63
63
63
64
64
64
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.1
72.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
454
454
320
320
320
2,748
2,748
2,748
395
395
395
53
53
53
41,826
37,423
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,694
1,694
1,694
859
859
859
511
511
511
180
180
180
3,244
7,841
7,841
5,526
5,526
5,526
47,476
47,476
47,476
6,823
6,823
6,823
911
911
911
727,491
650,911
1,280
1,280
1,280
2,975
2,975
2,975
2,627
2,627
2,627
1,357
1,357
1,357
8,239
8,216
32,706
32,706
32,706
16,577
16,577
16,577
9,869
9,869
9,869
3,472
3,472
3,472
62,624
2,546
2,546
1,795
1,795
1,795
11,597
11,597
11,597
2,216
2,216
2,216
354
354
354
122,518
95,452
284
284
284
722
722
722
600
600
600
357
357
357
1,962
1,958
8,526
8,526
8,526
1,182
1,182
1,182
2,573
2,573
2,573
855
855
855
13,135
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
9 /16
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
76
76
76
76
76
76
76
76
76
76
76
76
76
76
77
77
75
75
75
76
76
76
76
76
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
75
75
75
77
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
441
441
311
311
311
2,733
2,733
2,733
384
384
384
49
49
49
39,362
36,284
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,668
1,668
1,668
843
843
843
503
503
503
179
179
179
3,194
19,161
19,161
13,504
13,504
13,504
102,755
102,755
102,755
16,673
16,673
16,673
4,252
4,252
4,252
957,271
890,214
2,183
2,183
2,183
4,555
4,555
4,555
3,950
3,950
3,950
2,128
2,128
2,128
12,817
12,798
38,524
38,524
38,524
19,698
19,698
19,698
11,625
11,625
11,625
10,755
10,755
10,755
80,821
4,551
4,551
3,208
3,208
3,208
20,961
20,961
20,961
3,960
3,960
3,960
448
448
448
249,846
272,391
488
488
488
1,291
1,291
1,291
1,072
1,072
1,072
638
638
638
3,490
3,478
23,156
23,156
23,156
3,209
3,209
3,209
6,987
6,987
6,987
1,894
1,894
1,894
35,247
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 12 of 100
SPACE
Floor
Area
ft²
System Zone Room
IDC VAV
spc_LRC 140-01-08 C_0
Zone - 224
Zone - 224
spc_LRC 140-09 C_0
Zone - 225
Zone - 225
spc_LRC 13-15 C_0
Zone - 226
Zone - 226
spc_LRC 16 C_0
Zone - 227
Zone - 227
spc_LRC 17/18_0
Zone - 228
Zone - 228
spc_LRC 5 C (Study?)_0
Zone - 229
Zone - 229
spc_LRC 9 Storage_0
Zone - 230
Zone - 230
spc_LRC 10 Storage_0
Zone - 231
Zone - 231
spc_LRC 7 C_0
Zone - 232
Zone - 232
spc_LRC 8 Stair_0
Zone - 233
Zone - 233
spc_LRC Catalog C_0
Zone - 234
Zone - 234
spc_LRC Computer_0
Zone - 235
Zone - 235
spc_LRC 2/6_0
Zone - 236
Zone - 236
spc_LRC 1st RR C_0
Zone - 237
Zone - 237
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
5,194
1,843
1,843
1,843
250
250
250
153
153
153
66
66
66
94
94
94
57
57
57
29
29
29
24
24
24
119
119
119
302
302
302
56
56
56
525
525
525
137
137
137
226
226
226
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /15
6 /10
6 /10
9 /12
9 /12
9 /11
9 /11
10 /13
10 /13
10 /16
10 /16
7/15
7 /15
7 /15
7 /15
6 /10
6 /10
6 /18
6 /18
7 /18
7 /18
7 /18
7 /18
6 /17
6 /17
7 /15
7 /15
10 /16
10 /16
80
65
65
65
73
73
73
70
70
70
77
77
77
79
79
79
77
77
77
77
77
77
65
65
65
70
70
70
73
73
73
73
73
73
72
72
72
77
77
77
79
79
79
63
58
58
58
63
63
63
63
63
63
59
59
59
64
64
64
66
66
66
66
66
66
58
58
58
63
63
63
65
65
65
65
65
65
63
63
63
66
66
66
64
64
64
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
3,237
1,595
1,595
1,595
797
797
797
632
632
632
296
296
296
800
800
800
34
34
34
9
9
9
43
43
43
499
499
499
178
178
178
119
119
119
1,809
1,809
1,809
78
78
78
362
362
362
62,481
28,266
28,266
28,266
14,118
14,118
14,118
11,205
11,205
11,205
5,239
5,239
5,239
14,180
14,180
14,180
606
606
606
156
156
156
770
770
770
8,836
8,836
8,836
3,148
3,148
3,148
2,112
2,112
2,112
32,061
32,061
32,061
1,384
1,384
1,384
9,633
9,633
9,633
12,972
5,957
5,957
5,957
915
915
915
580
580
580
159
159
159
316
316
316
196
196
196
44
44
44
16
16
16
366
366
366
460
460
460
226
226
226
1,210
1,210
1,210
556
556
556
181
181
181
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
7 /16
7 /16
9 /13
9 /13
9 /11
9 /11
9 /13
9 /13
9 /16
9 /16
9 /16
9 /16
9 /15
9 /15
6 /10
6 /10
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
77
76
76
76
75
75
75
70
70
70
75
75
75
77
77
77
77
77
77
78
78
78
65
65
65
73
73
73
73
73
73
73
73
73
75
75
75
77
77
77
79
79
79
67
66
66
66
65
65
65
63
63
63
65
65
65
67
67
67
67
67
67
66
66
66
58
58
58
65
65
65
65
65
65
65
65
65
66
66
66
67
67
67
64
64
64
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
3,189
1,448
1,448
1,448
757
757
757
632
632
632
289
289
289
781
781
781
34
34
34
8
8
8
43
43
43
495
495
495
178
178
178
119
119
119
1,791
1,791
1,791
77
77
77
186
186
186
79,588
54,618
54,618
54,618
17,332
17,332
17,332
12,865
12,865
12,865
5,989
5,989
5,989
15,724
15,724
15,724
602
602
602
149
149
149
999
999
999
9,606
9,606
9,606
3,388
3,388
3,388
2,494
2,494
2,494
34,140
34,140
34,140
1,369
1,369
1,369
8,860
8,860
8,860
Coil
Latent
Load
Btu/h
35,420
12,597
12,597
12,597
1,569
1,569
1,569
880
880
880
417
417
417
710
710
710
392
392
392
63
63
63
19
19
19
757
757
757
592
592
592
392
392
392
2,556
2,556
2,556
1,032
1,032
1,032
996
996
996
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 13 of 100
SPACE
System Zone Room
spc_LRC 24_0
Peak
Zone - 238
Peak
Zone - 238
Block
spc_LRC 25_0
Peak
Zone - 239
Peak
Zone - 239
Block
spc_LRC 105 C Work_0
Peak
Zone - 240
Peak
Zone - 240
Block
spc_LRC Tables/124B C_0
Peak
Zone - 241
Peak
Zone - 241
Block
spc_LRC 120/122/123 Office C_0 Peak
Zone - 242
Peak
Zone - 242
Block
spc_LRC Tutor Lab C_0
Peak
Zone - 243
Peak
Zone - 243
Block
spc_LRC Lobby/112B Corridor C_0Peak
Zone - 244
Peak
Zone - 244
Block
spc_LRC Dir Offc C_0
Peak
Zone - 245
Peak
Zone - 245
Block
spc_LRC 108/111/115 Counter_0 Peak
Zone - 246
Peak
Zone - 246
Block
spc_LRC 149A_0
Peak
Zone - 247
Peak
Zone - 247
Block
spc_LRC 137 Work C_0
Peak
Zone - 248
Peak
Zone - 248
Block
spc_LRC 140-142 Director_0
Peak
Zone - 249
Peak
Zone - 249
Block
spc_LRC 145 Office C_0
Peak
Zone - 250
Peak
Zone - 250
Block
spc_LRC 146A Storage_0
Peak
Zone - 251
Peak
Zone - 251
Block
spc_LRC 146_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
564
564
564
325
325
325
62
62
62
647
647
647
58
58
58
63
63
63
582
582
582
36
36
36
335
335
335
25
25
25
59
59
59
38
38
38
23
23
23
14
14
14
80
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
10 /16
7 /18
7 /18
7 /18
7 /18
10 /15
10 /15
6 /11
6 /11
7 /15
7 /15
7 /18
7 /18
6 /18
6 /18
7 /15
7 /15
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
10 /13
79
79
79
73
73
73
73
73
73
80
80
80
68
68
68
77
77
77
73
73
73
70
70
70
77
77
77
73
73
73
73
73
73
75
75
75
75
75
75
79
79
79
77
64
64
64
65
65
65
65
65
65
63
63
63
60
60
60
66
66
66
65
65
65
63
63
63
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
64
64
64
59
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
2,024
2,024
2,024
956
956
956
123
123
123
1,184
1,184
1,184
119
119
119
110
110
110
387
387
387
147
147
147
191
191
191
45
45
45
191
191
191
20
20
20
12
12
12
64
64
64
252
35,871
35,871
35,871
16,939
16,939
16,939
2,178
2,178
2,178
20,983
20,983
20,983
2,116
2,116
2,116
1,946
1,946
1,946
6,866
6,866
6,866
2,614
2,614
2,614
3,378
3,378
3,378
793
793
793
3,381
3,381
3,381
359
359
359
214
214
214
1,140
1,140
1,140
4,464
1,890
1,890
1,890
1,302
1,302
1,302
214
214
214
1,652
1,652
1,652
103
103
103
180
180
180
975
975
975
72
72
72
1,358
1,358
1,358
86
86
86
204
204
204
101
101
101
60
60
60
11
11
11
192
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
9 /16
9 /16
7 /12
7 /12
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
9 /14
77
77
77
73
73
73
73
73
73
77
77
77
73
73
73
76
76
76
75
75
75
73
73
73
76
76
76
73
73
73
73
73
73
75
75
75
75
75
75
76
76
76
77
67
67
67
65
65
65
65
65
65
67
67
67
63
63
63
66
66
66
66
66
66
65
65
65
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
67
67
67
66
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,981
1,981
1,981
956
956
956
123
123
123
1,113
1,113
1,113
117
117
117
110
110
110
364
364
364
145
145
145
190
190
190
45
45
45
191
191
191
20
20
20
12
12
12
63
63
63
233
39,177
39,177
39,177
19,463
19,463
19,463
3,446
3,446
3,446
32,086
32,086
32,086
2,850
2,850
2,850
2,980
2,980
2,980
14,670
14,670
14,670
3,509
3,509
3,509
8,372
8,372
8,372
1,278
1,278
1,278
4,731
4,731
4,731
936
936
936
559
559
559
1,612
1,612
1,612
5,818
Coil
Latent
Load
Btu/h
4,243
4,243
4,243
2,256
2,256
2,256
397
397
397
4,480
4,480
4,480
178
178
178
312
312
312
1,365
1,365
1,365
155
155
155
2,288
2,288
2,288
159
159
159
378
378
378
174
174
174
104
104
104
35
35
35
535
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 14 of 100
SPACE
System Zone Room
Floor
Area
ft²
Zone - 252
Peak
Zone - 252
Block
spc_LRC Library_0
Peak
Zone - 253
Peak
Zone - 253
Block
spc_LRC 140-14_0
Peak
Zone - 254
Peak
Zone - 254
Block
spc_LRC 140-03_0
Peak
Zone - 255
Peak
Zone - 255
Block
spc_LRC 101 Work C_0
Peak
Zone - 256
Peak
Zone - 256
Block
spc_LRC 108-110 Storage_0
Peak
Zone - 257
Peak
Zone - 257
Block
spc_LRC 109 Work_0
Peak
Zone - 258
Peak
Zone - 258
Block
LRC VAV
Peak
LRC VAV
Block
spc_OE 10WM Restrooms AH-2_0Peak
Zone - 259
Peak
Zone - 259
Block
spc_OE 112 Class C_0
Peak
Zone - 260
Peak
Zone - 260
Block
spc_OE 116 Class C_0
Peak
Zone - 261
Peak
Zone - 261
Block
spc_OE 180H/182 Class C_0
Peak
Zone - 262
Peak
Zone - 262
Block
spc_OE 180A Office C_0
Peak
Zone - 263
Peak
Zone - 263
Block
OE Pckg AH
Peak
OE Pckg AH
Block
spc_PE 108 Weight Rm HP3/4_0 Peak
Zone - 006
Peak
Zone - 006
Block
spc_PE Locker/RR HP-06/07_0 Peak
80
80
0
0
0
42
42
42
86
86
86
62
62
62
24
24
24
43
43
43
7,052
7,052
172
172
172
522
522
522
1,121
1,121
1,121
509
509
509
66
66
66
2,391
2,391
3,594
3,594
3,594
1,968
Project Name:
Dataset Name:
SBCC TRACE.TRC
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /13
11 /12
11 /12
9 /12
9 /12
6 /10
6 /10
9 /17
9 /17
7 /15
7/15
9 /17
9 /17
9 /16
7 /18
7 /18
10 /15
10 /15
7 /18
7 /18
9 /11
9 /11
7 /17
7 /17
10 /14
9 /10
9 /10
7 /18
77
77
68
68
68
73
73
73
65
65
65
76
76
76
77
77
77
76
76
76
77
77
73
73
73
80
80
80
73
73
73
70
70
70
75
75
75
79
79
67
67
67
73
59
59
55
55
55
63
63
63
58
58
58
67
67
67
66
66
66
67
67
67
67
67
65
65
65
63
63
63
65
65
65
63
63
63
66
66
66
62
62
61
61
61
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.2
72.2
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.7
72.7
72.0
72.0
72.0
80.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
73.2
73.2
73.2
56.6
56.6
56.6
52.2
52.2
52.2
55.6
55.6
55.6
48.8
48.8
48.8
56.4
56.4
54.5
54.5
54.5
74.3
252
252
2,551
2,551
2,551
190
190
190
207
207
207
186
186
186
7
7
7
143
143
143
16,361
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
4,464
4,464
45,210
45,210
45,210
3,371
3,371
3,371
3,672
3,672
3,672
3,302
3,302
3,302
123
123
123
2,540
2,540
2,540
293,173
232,240
2,089
2,089
2,089
17,559
17,559
17,559
20,357
20,357
20,357
17,712
17,712
17,712
589
589
589
58,307
44,634
41,395
41,395
41,395
19,874
192
192
0
0
0
154
154
154
277
277
277
218
218
218
36
36
36
152
152
152
20,421
25,647
59
59
59
1,340
1,340
1,340
3,874
3,874
3,874
1,628
1,628
1,628
176
176
176
7,077
4,708
4,036
4,036
4,036
668
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /14
9 /11
9 /11
9 /12
9 /12
7 /17
7 /17
9 /17
9 /17
7 /16
7 /16
9 /17
9 /17
9 /16
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
9 /13
9 /13
7 /17
7 /17
9 /16
9 /13
9 /13
9 /17
77
77
70
70
70
73
73
73
75
75
75
76
76
76
76
76
76
76
76
76
77
77
76
76
76
77
77
77
73
73
73
75
75
75
75
75
75
77
77
75
75
75
76
66
66
63
63
63
63
63
63
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
66
67
67
65
65
65
67
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
76.2
76.2
76.2
57.4
57.4
57.4
52.2
52.2
52.2
57.4
57.4
57.4
48.8
48.8
48.8
57.5
60.7
57.2
57.2
57.2
75.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
233
233
2,488
2,488
2,488
190
190
190
164
164
164
186
186
186
7
7
7
143
143
143
15,679
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
5,818
5,818
47,040
47,040
47,040
4,151
4,151
4,151
4,618
4,618
4,618
4,899
4,899
4,899
475
475
475
3,755
3,755
3,755
382,332
328,402
2,439
2,439
2,439
21,294
21,294
21,294
23,315
23,315
23,315
22,689
22,689
22,689
1,667
1,667
1,667
71,405
61,879
36,526
36,526
36,526
36,640
Coil
Latent
Load
Btu/h
535
535
0
0
0
223
223
223
569
569
569
432
432
432
50
50
50
300
300
300
41,604
50,410
755
755
755
3,639
3,639
3,639
7,205
7,205
7,205
2,921
2,921
2,921
304
304
304
14,824
15,804
19,890
19,890
19,890
8,557
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 15 of 100
SPACE
System Zone Room
Zone - 008
Peak
Zone - 008
Block
Peak
spc_PE 302-310E Office Partially C_0
Zone - 011
Peak
Zone - 011
Block
PE Heat Pump
Peak
PE Heat Pump
Block
spc_PE Gym AH1_0
Peak
Zone - 001
Peak
Zone - 001
Block
spc_PE Team Lockey RH4_0
Peak
Zone - 002
Peak
Zone - 002
Block
spc_PE 113 RH7/RH8_0
Peak
Zone - 003
Peak
Zone - 003
Block
spc_PE 114 C_0
Peak
Zone - 004
Peak
Zone - 004
Block
spc_PE 109 NC_0
Peak
Zone - 005
Peak
Zone - 005
Block
spc_PE 2nd Flr Lobby_0
Peak
Zone - 007
Peak
Zone - 007
Block
spc_PE 214-218, 201-203 Offices C_0
Peak
Zone - 009
Peak
Zone - 009
Block
spc_PE 3 Press Box RH02 _0
Peak
Zone - 010
Peak
Zone - 010
Block
PE VAV Htg Only
Peak
PE VAV Htg Only
Block
spc_sp_55
Peak
Zone - 264
Peak
Zone - 264
Block
spc_sp_56
Peak
Zone - 265
Peak
Zone - 265
Block
spc_sp_57
Peak
Zone - 266
Peak
Zone - 266
Block
spc_sp_58
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
1,968
1,968
498
498
498
6,061
6,061
7,524
7,524
7,524
744
744
744
1,696
1,696
1,696
1,001
1,001
1,001
683
683
683
7,013
7,013
7,013
1,922
1,922
1,922
174
174
174
20,757
20,757
1,130
1,130
1,130
1,130
1,130
1,130
1,159
1,159
1,159
1,087
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
10 /16
10 /16
9 /16
9 /16
9 /10
9 /10
10 /15
10 /15
7 /10
7 /10
7 /18
7 /18
10 /16
10 /16
7 /17
10 /13
10 /13
10 /15
10 /15
9 /12
9 /12
10 /16
73
73
73
73
73
73
73
75
75
75
79
79
79
77
77
77
67
67
67
80
80
80
67
67
67
73
73
73
79
79
79
75
75
77
77
77
80
80
80
73
73
73
79
65
65
65
65
65
65
65
66
66
66
64
64
64
67
67
67
61
61
61
63
63
63
60
60
60
65
65
65
64
64
64
66
66
59
59
59
63
63
63
63
63
63
64
80.0
80.0
72.0
72.0
72.0
76.0
76.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
74.4
74.4
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
74.3
74.3
56.3
56.3
56.3
64.7
64.7
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
58.6
58.6
58.6
55.9
55.9
55.9
54.6
54.6
54.6
56.3
3,150
3,150
1,009
1,009
1,009
6,278
6,278
1,505
1,505
1,505
1,190
1,190
1,190
339
339
339
200
200
200
137
137
137
351
351
351
256
256
256
23
23
23
4,001
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
19,874
19,874
17,669
17,669
17,669
78,937
60,043
-636
-636
-636
10,111
10,111
10,111
-143
-143
-143
-85
-85
-85
-58
-58
-58
-148
-148
-148
-108
-108
-108
-10
-10
-10
8,923
0
25,370
25,370
25,370
30,201
30,201
30,201
29,008
29,008
29,008
37,550
668
668
1,173
1,173
1,173
5,877
7,430
-4,539
-4,539
-4,539
-971
-971
-971
2,691
2,691
2,691
1,039
1,039
1,039
306
306
306
-8,532
-8,532
-8,532
454
454
454
-45
-45
-45
-9,597
-3,178
2,062
2,062
2,062
2,910
2,910
2,910
3,573
3,573
3,573
3,013
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /17
7 /18
7 /18
9 /17
7 /14
7 /14
9 /16
9 /16
9 /16
9 /16
9 /10
9 /10
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
7 /17
9 /14
9 /14
9 /16
9 /16
9 /14
9 /14
9 /16
76
76
73
73
73
76
76
76
76
76
77
77
77
77
77
77
67
67
67
77
77
77
75
75
75
75
75
75
76
76
76
75
75
77
77
77
77
77
77
77
77
77
77
67
67
65
65
65
67
67
65
65
65
67
67
67
67
67
67
61
61
61
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
67
67
67
66
66
66
67
75.4
75.4
56.3
56.3
56.3
66.2
68.1
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
59.2
59.2
59.2
56.9
56.9
56.9
55.6
55.6
55.6
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
3,150
3,150
1,009
1,009
1,009
6,278
6,278
451
451
451
357
357
357
102
102
102
60
60
60
41
41
41
105
105
105
77
77
77
7
7
7
1,200
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
36,640
36,640
27,335
27,335
27,335
100,501
80,404
-191
-191
-191
3,033
3,033
3,033
-43
-43
-43
-25
-25
-25
-17
-17
-17
-44
-44
-44
-32
-32
-32
-3
-3
-3
12,882
0
36,547
36,547
36,547
44,525
44,525
44,525
40,050
40,050
40,050
54,574
Coil
Latent
Load
Btu/h
8,557
8,557
2,160
2,160
2,160
30,607
29,879
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6,959
6,959
6,959
7,908
7,908
7,908
7,147
7,147
7,147
7,605
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 16 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 267
Zone - 267
spc_sp_59
Zone - 268
Zone - 268
spc_sp_60
Zone - 269
Zone - 269
spc_sp_61
Zone - 270
Zone - 270
spc_sp_62
Zone - 271
Zone - 271
spc_sp_63
Zone - 272
Zone - 272
spc_sp_64
Zone - 273
Zone - 273
spc_sp_65
Zone - 274
Zone - 274
spc_sp_66
Zone - 275
Zone - 275
spc_sp_67
Zone - 276
Zone - 276
spc_sp_68
Zone - 277
Zone - 277
spc_sp_69
Zone - 278
Zone - 278
spc_sp_70
Zone - 279
Zone - 279
spc_sp_38
Zone - 280
Zone - 280
spc_sp_39
Zone - 281
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
1,087
1,087
396
396
396
828
828
828
378
378
378
485
485
485
678
678
678
822
822
822
628
628
628
2,082
2,082
2,082
2,169
2,169
2,169
2,777
2,777
2,777
3,084
3,084
3,084
211
211
211
818
818
818
818
818
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
11 /15
11 /15
7 /18
7 /18
9 /11
9 /11
6 /10
6 /10
10 /16
10 /16
7 /18
7 /18
9 /11
9 /11
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
6 /10
6 /10
9 /16
9 /16
9 /16
79
79
73
73
73
73
73
73
70
70
70
65
65
65
79
79
79
73
73
73
70
70
70
77
77
77
75
75
75
75
75
75
75
75
75
65
65
65
77
77
77
77
77
64
64
62
62
62
65
65
65
63
63
63
58
58
58
64
64
64
65
65
65
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.3
56.3
58.2
58.2
58.2
54.7
54.7
54.7
57.5
57.5
57.5
55.5
55.5
55.5
56.3
56.3
56.3
51.4
51.4
51.4
56.1
56.1
56.1
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.5
52.5
52.5
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
37,550
37,550
33,464
33,464
33,464
25,783
25,783
25,783
28,760
28,760
28,760
11,994
11,994
11,994
23,923
23,923
23,923
13,067
13,067
13,067
26,223
26,223
26,223
53,398
53,398
53,398
48,975
48,975
48,975
57,415
57,415
57,415
55,454
55,454
55,454
13,285
13,285
13,285
28,858
28,858
28,858
28,858
28,858
3,013
3,013
1,051
1,051
1,051
2,864
2,864
2,864
1,212
1,212
1,212
1,286
1,286
1,286
1,878
1,878
1,878
2,838
2,838
2,838
2,011
2,011
2,011
7,723
7,723
7,723
7,128
7,128
7,128
9,122
9,122
9,122
10,121
10,121
10,121
559
559
559
3,036
3,036
3,036
3,036
3,036
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /15
7 /18
7 /18
9 /11
9 /11
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
9 /12
9 /12
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /16
77
77
80
80
80
73
73
73
70
70
70
76
76
76
77
77
77
75
75
75
73
73
73
77
77
77
75
75
75
75
75
75
76
76
76
65
65
65
77
77
77
77
77
67
67
63
63
63
65
65
65
63
63
63
66
66
66
67
67
67
66
66
66
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
56.5
56.5
58.3
58.3
58.3
54.7
54.7
54.7
57.5
57.5
57.5
58.6
58.6
58.6
56.4
56.4
56.4
51.9
51.9
51.9
56.2
56.2
56.2
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.7
52.7
52.7
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
54,574
54,574
40,936
40,936
40,936
38,829
38,829
38,829
32,826
32,826
32,826
16,489
16,489
16,489
33,562
33,562
33,562
23,710
23,710
23,710
32,978
32,978
32,978
80,411
80,411
80,411
79,136
79,136
79,136
95,193
95,193
95,193
95,526
95,526
95,526
14,677
14,677
14,677
41,068
41,068
41,068
41,068
41,068
Coil
Latent
Load
Btu/h
7,605
7,605
1,195
1,195
1,195
5,336
5,336
5,336
1,973
1,973
1,973
3,057
3,057
3,057
4,742
4,742
4,742
5,052
5,052
5,052
3,012
3,012
3,012
14,541
14,541
14,541
13,382
13,382
13,382
17,116
17,116
17,116
19,369
19,369
19,369
694
694
694
5,720
5,720
5,720
5,720
5,720
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 17 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 281
spc_sp_40
Zone - 282
Zone - 282
spc_sp_41
Zone - 283
Zone - 283
spc_sp_42
Zone - 284
Zone - 284
spc_sp_43
Zone - 285
Zone - 285
spc_sp_44
Zone - 286
Zone - 286
spc_sp_45
Zone - 287
Zone - 287
spc_sp_46
Zone - 288
Zone - 288
spc_sp_47
Zone - 289
Zone - 289
spc_sp_48
Zone - 290
Zone - 290
spc_sp_49
Zone - 291
Zone - 291
spc_sp_50
Zone - 292
Zone - 292
spc_sp_51
Zone - 293
Zone - 293
spc_sp_52
Zone - 294
Zone - 294
spc_sp_53
Zone - 295
Zone - 295
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
818
1,408
1,408
1,408
1,392
1,392
1,392
972
972
972
1,408
1,408
1,408
826
826
826
914
914
914
907
907
907
869
869
869
869
869
869
835
835
835
893
893
893
737
737
737
1,061
1,061
1,061
1,064
1,064
1,064
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
10 /15
10 /15
9 /16
9 /16
9/16
9 /16
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
10 /13
10 /13
10 /13
10 /13
77
77
77
77
77
77
77
77
77
77
80
80
80
77
77
77
77
77
77
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
77
77
77
77
77
77
67
67
67
67
67
67
67
67
67
67
63
63
63
67
67
67
67
67
67
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
59
59
59
59
59
59
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
54.0
54.0
56.0
56.0
56.0
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
53.9
53.9
53.9
54.1
54.1
54.1
54.2
54.2
54.2
54.0
54.0
54.0
55.0
55.0
55.0
58.7
58.7
58.7
58.7
58.7
58.7
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
28,858
35,056
35,056
35,056
34,765
34,765
34,765
27,232
27,232
27,232
38,302
38,302
38,302
27,994
27,994
27,994
26,885
26,885
26,885
25,235
25,235
25,235
22,064
22,064
22,064
22,983
22,983
22,983
22,536
22,536
22,536
23,576
23,576
23,576
24,944
24,944
24,944
24,323
24,323
24,323
24,374
24,374
24,374
3,036
5,223
5,223
5,223
5,163
5,163
5,163
3,608
3,608
3,608
3,626
3,626
3,626
3,067
3,067
3,067
3,393
3,393
3,393
3,140
3,140
3,140
3,008
3,008
3,008
3,009
3,009
3,009
2,891
2,891
2,891
3,092
3,092
3,092
2,553
2,553
2,553
1,935
1,935
1,935
1,941
1,941
1,941
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
9 /14
9 /14
9 /14
9 /14
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
77
77
77
77
77
77
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
54.0
54.0
56.2
56.2
56.2
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
54.1
54.1
54.1
54.2
54.2
54.2
54.3
54.3
54.3
54.2
54.2
54.2
55.0
55.0
55.0
59.2
59.2
59.2
59.2
59.2
59.2
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
41,068
53,076
53,076
53,076
52,584
52,584
52,584
39,863
39,863
39,863
56,744
56,744
56,744
39,442
39,442
39,442
38,892
38,892
38,892
38,103
38,103
38,103
33,592
33,592
33,592
34,897
34,897
34,897
34,003
34,003
34,003
35,816
35,816
35,816
36,470
36,470
36,470
34,741
34,741
34,741
34,831
34,831
34,831
Coil
Latent
Load
Btu/h
5,720
9,832
9,832
9,832
9,719
9,719
9,719
6,796
6,796
6,796
9,854
9,854
9,854
5,777
5,777
5,777
6,391
6,391
6,391
5,604
5,604
5,604
5,367
5,367
5,367
5,370
5,370
5,370
5,157
5,157
5,157
5,519
5,519
5,519
4,557
4,557
4,557
6,531
6,531
6,531
6,553
6,553
6,553
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 18 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_54
Zone - 296
Zone - 296
spc_sp_22
Zone - 297
Zone - 297
spc_sp_23
Zone - 298
Zone - 298
spc_sp_24
Zone - 299
Zone - 299
spc_sp_25
Zone - 300
Zone - 300
spc_sp_26
Zone - 301
Zone - 301
spc_sp_27
Zone - 302
Zone - 302
spc_sp_28
Zone - 303
Zone - 303
spc_sp_29
Zone - 304
Zone - 304
spc_sp_30
Zone - 305
Zone - 305
spc_sp_31
Zone - 306
Zone - 306
spc_sp_32
Zone - 307
Zone - 307
spc_sp_33
Zone - 308
Zone - 308
spc_sp_34
Zone - 309
Zone - 309
spc_sp_35
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
1,061 9 /12
1,061
1,061 9 /12
1,044
7 /18
1,044
1,044
7 /18
1,082
7 /18
1,082
1,082
7 /18
1,074
7 /18
1,074
1,074
7 /18
955
7 /18
955
955
7 /18
995
9 /16
995
995
9 /16
894
7 /17
894
894
7 /17
1,063 10 /15
1,063
1,063 10 /15
684
6 /10
684
684
6 /10
2,070 9 /16
2,070
2,070 9 /16
1,251 9 /16
1,251
1,251 9 /16
1,251 7 /17
1,251
1,251 7 /17
1,525 9 /16
1,525
1,525 9 /16
818
9 /16
818
818
9 /16
818
9 /16
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
77
77
77
75
75
75
80
80
80
65
65
65
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
63
63
63
65
65
65
65
65
65
65
65
65
65
65
65
67
67
67
66
66
66
63
63
63
58
58
58
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.7
54.7
54.7
53.1
53.1
53.1
53.4
53.4
53.4
53.1
53.1
53.1
53.6
53.6
53.6
55.1
55.1
55.1
55.0
55.0
55.0
56.6
56.6
56.6
55.8
55.8
55.8
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
27,301
27,301
27,301
22,248
22,248
22,248
24,586
24,586
24,586
22,945
22,945
22,945
22,834
22,834
22,834
37,026
37,026
37,026
29,118
29,118
29,118
36,090
36,090
36,090
18,202
18,202
18,202
52,942
52,942
52,942
35,189
35,189
35,189
31,103
31,103
31,103
60,677
60,677
60,677
29,082
29,082
29,082
28,858
3,272
3,272
3,272
3,609
3,609
3,609
3,741
3,741
3,741
3,711
3,711
3,711
3,304
3,304
3,304
3,697
3,697
3,697
2,943
2,943
2,943
2,737
2,737
2,737
1,813
1,813
1,813
7,679
7,679
7,679
4,645
4,645
4,645
4,115
4,115
4,115
5,660
5,660
5,660
3,036
3,036
3,036
3,036
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /14
9 /14
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
9 /16
77
77
77
75
75
75
75
75
75
75
75
75
75
75
75
77
77
77
75
75
75
77
77
77
76
76
76
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
55.7
55.7
55.7
53.6
53.6
53.6
53.6
53.6
53.6
53.6
53.6
53.6
53.9
53.9
53.9
55.1
55.1
55.1
55.0
55.0
55.0
56.7
56.7
56.7
60.6
60.6
60.6
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
37,314
37,314
37,314
35,254
35,254
35,254
38,640
38,640
38,640
36,369
36,369
36,369
35,270
35,270
35,270
51,628
51,628
51,628
42,996
42,996
42,996
51,414
51,414
51,414
22,226
22,226
22,226
79,873
79,873
79,873
52,725
52,725
52,725
48,027
48,027
48,027
82,120
82,120
82,120
41,372
41,372
41,372
41,068
Coil
Latent
Load
Btu/h
6,544
6,544
6,544
6,433
6,433
6,433
6,671
6,671
6,671
6,615
6,615
6,615
5,894
5,894
5,894
6,966
6,966
6,966
5,530
5,530
5,530
7,439
7,439
7,439
4,311
4,311
4,311
14,458
14,458
14,458
8,749
8,749
8,749
7,730
7,730
7,730
10,664
10,664
10,664
5,720
5,720
5,720
5,720
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 19 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 310
Zone - 310
spc_sp_36
Zone - 311
Zone - 311
spc_sp_37
Zone - 312
Zone - 312
spc_sp_7
Zone - 313
Zone - 313
spc_sp_8
Zone - 314
Zone - 314
spc_sp_9
Zone - 315
Zone - 315
spc_sp_10
Zone - 316
Zone - 316
spc_sp_11
Zone - 317
Zone - 317
spc_sp_12
Zone - 318
Zone - 318
spc_sp_13
Zone - 319
Zone - 319
spc_sp_14
Zone - 320
Zone - 320
spc_sp_15
Zone - 321
Zone - 321
spc_sp_16
Zone - 322
Zone - 322
spc_sp_17
Zone - 323
Zone - 323
spc_sp_18
Zone - 324
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
818
818
818
818
818
818
818
818
290
290
290
442
442
442
2,070
2,070
2,070
1,103
1,103
1,103
915
915
915
3,084
3,084
3,084
437
437
437
344
344
344
231
231
231
382
382
382
358
358
358
1,082
1,082
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /11
9 /11
6 /18
6 /18
7 /17
7/17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
6 /18
6 /18
7 /18
7 /18
9 /12
9 /12
6 /10
6 /10
6 /9
6 /9
7 /18
77
77
77
77
77
77
77
77
70
70
70
70
70
70
75
75
75
76
76
76
76
76
76
75
75
75
70
70
70
73
73
73
73
73
73
65
65
65
62
62
62
73
73
67
67
67
67
67
67
67
67
63
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
65
65
65
63
63
63
58
58
58
58
58
58
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
57.0
57.0
57.0
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
56.2
56.2
56.2
56.0
56.0
56.0
53.0
53.0
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
17,557
17,557
17,557
19,208
19,208
19,208
47,533
47,533
47,533
12,788
12,788
12,788
10,607
10,607
10,607
60,225
60,225
60,225
28,451
28,451
28,451
19,387
19,387
19,387
8,323
8,323
8,323
11,887
11,887
11,887
10,175
10,175
10,175
22,813
22,813
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
929
929
929
1,375
1,375
1,375
6,804
6,804
6,804
3,865
3,865
3,865
3,206
3,206
3,206
10,127
10,127
10,127
1,358
1,358
1,358
1,192
1,192
1,192
713
713
713
1,013
1,013
1,013
951
951
951
3,739
3,739
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /12
9 /12
7 /18
7 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /12
9 /12
7 /15
7 /15
7 /16
7 /16
7 /17
77
77
77
77
77
77
77
77
73
73
73
73
73
73
75
75
75
76
76
76
76
76
76
75
75
75
73
73
73
73
73
73
73
73
73
77
77
77
76
76
76
75
75
67
67
67
67
67
67
67
67
63
63
63
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
63
63
63
66
66
66
66
66
66
66
66
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
57.6
57.6
57.6
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
60.1
60.1
60.1
57.9
57.9
57.9
53.5
53.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
20,529
20,529
20,529
26,244
26,244
26,244
76,434
76,434
76,434
26,279
26,279
26,279
21,797
21,797
21,797
101,628
101,628
101,628
36,070
36,070
36,070
25,678
25,678
25,678
11,070
11,070
11,070
14,327
14,327
14,327
14,201
14,201
14,201
36,302
36,302
Coil
Latent
Load
Btu/h
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
1,393
1,393
1,393
2,856
2,856
2,856
12,774
12,774
12,774
6,912
6,912
6,912
5,733
5,733
5,733
18,995
18,995
18,995
2,820
2,820
2,820
2,221
2,221
2,221
1,110
1,110
1,110
2,357
2,357
2,357
2,261
2,261
2,261
6,665
6,665
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 20 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 324
spc_sp_19
Zone - 325
Zone - 325
spc_sp_20
Zone - 326
Zone - 326
spc_sp_21
Zone - 327
Zone - 327
spc_sp_1
Zone - 328
Zone - 328
spc_sp_2
Zone - 329
Zone - 329
spc_sp_3
Zone - 330
Zone - 330
spc_sp_4
Zone - 331
Zone - 331
spc_sp_5
Zone - 332
Zone - 332
spc_sp_6
Zone - 333
Zone - 333
Child Cntr 2
Zone - 359
Zone - 359
Child Cntr 3
Zone - 360
Zone - 360
Child Cntr 1
Zone - 361
Zone - 361
Portopia HP
Portopia HP
spc_SS 141/142 Office_0
Zone - 012
Zone - 012
spc_SS 144 Office C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
1,082
960
960
960
1,040
1,040
1,040
1,040
1,040
1,040
1,272
1,272
1,272
1,074
1,074
1,074
999
999
999
1,613
1,613
1,613
664
664
664
1,956
1,956
1,956
211
211
211
211
211
211
211
211
211
75,038
75,038
313
313
313
168
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
9 /16
9 /16
7 /18
7 /18
7/18
7 /18
10 /15
10 /15
10 /16
10 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
73
73
73
73
73
73
73
73
73
73
77
77
77
73
73
73
73
73
73
80
80
80
79
79
79
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
65
65
65
65
65
65
65
65
65
65
67
67
67
65
65
65
65
65
65
63
63
63
64
64
64
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Supply
Dry
Bulb
°F
53.0
53.2
53.2
53.2
54.2
54.2
54.2
53.1
53.1
53.1
48.6
48.6
48.6
53.1
53.1
53.1
54.3
54.3
54.3
55.5
55.5
55.5
57.1
57.1
57.1
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
54.9
54.9
72.0
72.0
72.0
72.0
Space
Air
Flow
cfm
COIL
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
1,079
22,813
1,002
20,987
1,002
20,987
1,002
20,987
1,451
28,726
1,451
28,726
1,451
28,726
1,053
22,182
1,053
22,182
1,053
22,182
600
15,648
600
15,648
600
15,648
1,089
22,945
1,089
22,945
1,089
22,945
1,420
28,019
1,420
28,019
1,420
28,019
2,033
37,433
2,033
37,433
2,033
37,433
1,915
31,843
1,915
31,843
1,915
31,843
871
22,688
871
22,688
871
22,688
837
13,285
837
13,285
837
13,285
837
13,285
837
13,285
837
13,285
849
12,931
849
12,931
849
12,931
106,096 2,026,697
106,096 1,809,600
81
0
81
0
81
0
32
0
3,739
3,318
3,318
3,318
3,598
3,598
3,598
3,594
3,594
3,594
4,707
4,707
4,707
3,711
3,711
3,711
3,457
3,457
3,457
4,151
4,151
4,151
1,840
1,840
1,840
6,857
6,857
6,857
559
559
559
559
559
559
370
370
370
246,137
246,507
181
181
181
97
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
75
75
75
75
75
75
75
75
75
75
76
76
76
75
75
75
75
75
75
77
77
77
77
77
77
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
53.5
53.7
53.7
53.7
54.4
54.4
54.4
53.6
53.6
53.6
48.8
48.8
48.8
53.6
53.6
53.6
54.5
54.5
54.5
56.4
56.4
56.4
57.3
57.3
57.3
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
55.1
56.7
72.0
72.0
72.0
72.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
36,302
32,911
32,911
32,911
43,793
43,793
43,793
35,131
35,131
35,131
31,358
31,358
31,358
36,369
36,369
36,369
42,495
42,495
42,495
56,782
56,782
56,782
43,282
43,282
43,282
46,620
46,620
46,620
14,677
14,677
14,677
14,677
14,677
14,677
14,524
14,524
14,524
3,006,774
2,862,181
0
0
0
0
Coil
Latent
Load
Btu/h
6,665
5,915
5,915
5,915
6,420
6,420
6,420
6,406
6,406
6,406
7,970
7,970
7,970
6,615
6,615
6,615
6,169
6,169
6,169
11,281
11,281
11,281
4,645
4,645
4,645
12,262
12,262
12,262
694
694
694
694
694
694
460
460
460
480,065
462,701
0
0
0
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 21 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 013
Zone - 013
spc_SS 160B-D_0
Zone - 014
Zone - 014
spc_PS 160A Storage_0
Zone - 015
Zone - 015
spc_SS 160 Class C_0
Zone - 016
Zone - 016
spc_SS 162 Class_0
Zone - 017
Zone - 017
spc_PS 112 Office C_0
Zone - 018
Zone - 018
spc_PS 111-115 Office C_0
Zone - 019
Zone - 019
spc_PS Lecture 117 C_0
Zone - 020
Zone - 020
spc_PS Lecture FC-4C_0
Zone - 021
Zone - 021
spc_PS 120-128 Class_0
Zone - 022
Zone - 022
spc_PS Class 121/122_0
Zone - 023
Zone - 023
spc_PS 130 Auditorium C_0
Zone - 024
Zone - 024
PS Fan Coil Htg Only
PS Fan Coil Htg Only
spc_SS 171-173, 178 Office C_0
Zone - 037
Zone - 037
spc_SS 135 Office_0
Zone - 038
Zone - 038
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
168
168
0
0
0
102
102
102
565
565
565
967
967
967
215
215
215
602
602
602
1,126
1,126
1,126
1,036
1,036
1,036
886
886
886
695
695
695
1,413
1,413
1,413
8,090
8,090
561
561
561
92
92
92
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /9
10 /15
10 /15
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
10 /16
10 /16
9 /17
9 /17
7 /18
7 /18
6 /9
6 /9
7 /16
7 /16
10 /16
10 /16
10 /16
7 /16
7 /16
7 /16
7 /16
62
62
80
80
80
70
70
70
70
70
70
70
70
70
79
79
79
79
79
79
76
76
76
73
73
73
62
62
62
76
76
76
79
79
79
79
79
76
76
76
76
76
76
58
58
63
63
63
63
63
63
63
63
63
63
63
63
64
64
64
64
64
64
67
67
67
65
65
65
58
58
58
66
66
66
64
64
64
64
64
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
32
32
0
0
0
27
27
27
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
274
274
274
45
45
45
Space
Sensible
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,317
5,317
5,317
875
875
875
Space
Latent
Load
Btu/h
97
97
0
0
0
-2
-2
-2
836
836
836
1,430
1,430
1,430
157
157
157
435
435
435
1,356
1,356
1,356
1,374
1,374
1,374
1,392
1,392
1,392
992
992
992
2,191
2,191
2,191
10,439
7,971
1,465
1,465
1,465
241
241
241
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
6 /9
9 /16
9 /16
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
7 /18
7 /18
7 /9
7 /9
7 /16
7 /16
9 /16
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
62
62
77
77
77
70
70
70
70
70
70
70
70
70
79
79
79
76
76
76
76
76
76
73
73
73
64
64
64
76
76
76
77
77
77
77
77
76
76
76
76
76
76
58
58
67
67
67
63
63
63
63
63
63
63
63
63
64
64
64
67
67
67
67
67
67
65
65
65
59
59
59
66
66
66
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
32
32
0
0
0
27
27
27
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
268
268
268
44
44
44
Coil
Sensible
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,089
5,089
5,089
838
838
838
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2,917
2,917
2,917
480
480
480
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 22 of 100
SPACE
System Zone Room
spc_SS Corridor 120 C_0
Peak
Zone - 039
Peak
Zone - 039
Block
spc_SS 180 Worm Rm VAV-20_0 Peak
Zone - 040
Peak
Zone - 040
Block
spc_SS 110C Wrk Rm C_0
Peak
Zone - 041
Peak
Zone - 041
Block
spc_SS 110 Wrk Rm/Office C_0 Peak
Zone - 042
Peak
Zone - 042
Block
Peak
spc_SS 100 100H 111H Main Lobby
C_0
Zone - 043
Peak
Zone - 043
Block
spc_SS 150 Wrk Rm C_0
Peak
Zone - 044
Peak
Zone - 044
Block
spc_SS 177-179 Office_0
Peak
Zone - 045
Peak
Zone - 045
Block
spc_SS Wrk Rm1 V-19_0
Peak
Zone - 046
Peak
Zone - 046
Block
spc_SS 120-124 C_0
Peak
Zone - 047
Peak
Zone - 047
Block
spc_SS 135-139 Office C_0
Peak
Zone - 048
Peak
Zone - 048
Block
spc_SS 140 Wrk Rm C_0
Peak
Zone - 049
Peak
Zone - 049
Block
spc_SS 125-129_0
Peak
Zone - 050
Peak
Zone - 050
Block
spc_SS 230B Office C_0
Peak
Zone - 051
Peak
Zone - 051
Block
spc_SS 214 Office C_0
Peak
Zone - 052
Peak
Zone - 052
Block
spc_SS 282 Wrk Rm C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
1,787
1,787
1,787
326
326
326
766
766
766
1,420
1,420
1,420
37
37
37
301
301
301
635
635
635
207
207
207
703
703
703
586
586
586
848
848
848
642
642
642
285
285
285
130
130
130
136
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
10 /16
10 /16
6 /9
6 /9
9 /17
9 /17
7 /18
7 /18
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
6 /9
6 /9
7 /16
7 /16
9 /16
9 /16
6 /18
6 /18
6 /18
6 /18
10 /16
10 /16
10 /16
76
76
76
79
79
79
62
62
62
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
62
62
62
76
76
76
77
77
77
70
70
70
70
70
70
79
79
79
79
66
66
66
64
64
64
58
58
58
67
67
67
65
65
65
66
66
66
66
66
66
66
66
66
58
58
58
66
66
66
67
67
67
63
63
63
63
63
63
64
64
64
64
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
378
378
378
616
616
616
1,984
1,984
1,984
844
844
844
348
348
348
167
167
167
310
310
310
115
115
115
1,253
1,253
1,253
286
286
286
545
545
545
1,766
1,766
1,766
526
526
526
623
623
623
1,441
7,342
7,342
7,342
11,961
11,961
11,961
38,530
38,530
38,530
16,389
16,389
16,389
6,755
6,755
6,755
3,248
3,248
3,248
6,019
6,019
6,019
2,238
2,238
2,238
24,336
24,336
24,336
5,555
5,555
5,555
10,576
10,576
10,576
34,294
34,294
34,294
10,214
10,214
10,214
12,096
12,096
12,096
27,981
2,794
2,794
2,794
902
902
902
2,030
2,030
2,030
4,101
4,101
4,101
63
63
63
1,044
1,044
1,044
1,658
1,658
1,658
719
719
719
1,862
1,862
1,862
1,530
1,530
1,530
3,146
3,146
3,146
1,992
1,992
1,992
572
572
572
244
244
244
378
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
7 /10
7 /10
9 /17
9 /17
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /10
7 /10
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
9 /16
9 /16
9 /16
77
77
77
77
77
77
67
67
67
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
67
67
67
76
76
76
77
77
77
73
73
73
73
73
73
77
77
77
77
67
67
67
67
67
67
60
60
60
67
67
67
65
65
65
67
67
67
67
67
67
67
67
67
60
60
60
67
67
67
67
67
67
65
65
65
65
65
65
67
67
67
67
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
364
364
364
593
593
593
1,874
1,874
1,874
844
844
844
348
348
348
165
165
165
304
304
304
114
114
114
1,181
1,181
1,181
280
280
280
545
545
545
1,745
1,745
1,745
522
522
522
610
610
610
1,360
5,425
5,425
5,425
13,863
13,863
13,863
40,338
40,338
40,338
16,959
16,959
16,959
8,572
8,572
8,572
3,134
3,134
3,134
5,761
5,761
5,761
2,159
2,159
2,159
25,288
25,288
25,288
5,317
5,317
5,317
10,803
10,803
10,803
37,007
37,007
37,007
11,167
11,167
11,167
14,956
14,956
14,956
32,179
Coil
Latent
Load
Btu/h
4,022
4,022
4,022
2,276
2,276
2,276
2,929
2,929
2,929
7,387
7,387
7,387
90
90
90
2,099
2,099
2,099
3,302
3,302
3,302
1,446
1,446
1,446
2,687
2,687
2,687
3,047
3,047
3,047
5,923
5,923
5,923
4,132
4,132
4,132
1,239
1,239
1,239
651
651
651
953
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 23 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 053
Zone - 053
spc_SS 280D Office_0
Zone - 054
Zone - 054
spc_SS 280A-C C_0
Zone - 055
Zone - 055
spc_SS 272 Wrk Rm C_0
Zone - 056
Zone - 056
spc_SS 270C/D Office_0
Zone - 057
Zone - 057
spc_SS 111H Hall_0
Zone - 058
Zone - 058
spc_SS 110G/H Offices C_0
Zone - 059
Zone - 059
spc_SS 111A Office C_0
Zone - 060
Zone - 060
spc_SS 242 Wrk Rm C_0
Zone - 061
Zone - 061
spc_SS 240L Office C_0
Zone - 062
Zone - 062
spc_SS 240H Office_0
Zone - 063
Zone - 063
spc_SS 240F/J Office_0
Zone - 064
Zone - 064
spc_SS 240-260A Wrk Rm C_0
Zone - 065
Zone - 065
spc_SS 202/250B Office_0
Zone - 066
Zone - 066
spc_SS 250 Wrk Rm C_0
Zone - 067
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
136
136
154
154
154
459
459
459
778
778
778
287
287
287
397
397
397
269
269
269
216
216
216
642
642
642
149
149
149
181
181
181
274
274
274
865
865
865
214
214
214
0
0
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
7 /17
7 /17
9 /11
9 /11
9 /11
9 /11
9 /12
9 /12
7 /18
7/18
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
10 /16
10 /16
7 /16
7 /16
6 /9
79
79
75
75
75
70
70
70
70
70
70
73
73
73
73
73
73
76
76
76
76
76
76
79
79
79
75
75
75
76
76
76
75
75
75
79
79
79
76
76
76
62
62
64
64
66
66
66
63
63
63
63
63
63
63
63
63
65
65
65
66
66
66
66
66
66
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
66
66
66
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,441
1,441
75
75
75
1,255
1,255
1,255
1,090
1,090
1,090
379
379
379
175
175
175
131
131
131
105
105
105
406
406
406
73
73
73
89
89
89
133
133
133
1,257
1,257
1,257
104
104
104
16
16
27,981
27,981
1,450
1,450
1,450
24,365
24,365
24,365
21,179
21,179
21,179
7,364
7,364
7,364
3,399
3,399
3,399
2,552
2,552
2,552
2,048
2,048
2,048
7,890
7,890
7,890
1,410
1,410
1,410
1,719
1,719
1,719
2,589
2,589
2,589
24,416
24,416
24,416
2,028
2,028
2,028
304
304
378
378
408
408
408
1,469
1,469
1,469
2,489
2,489
2,489
627
627
627
612
612
612
703
703
703
564
564
564
1,777
1,777
1,777
397
397
397
474
474
474
728
728
728
2,394
2,394
2,394
559
559
559
0
0
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
7 /17
7 /17
9 /11
9 /11
9 /13
9 /13
9 /13
9 /13
7 /18
7 /18
9 /17
9 /17
9 /17
9 /17
7 /16
7 /16
7 /17
7 /17
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
9 /17
9 /17
7 /10
77
77
75
75
75
70
70
70
75
75
75
75
75
75
73
73
73
76
76
76
76
76
76
76
76
76
75
75
75
76
76
76
75
75
75
77
77
77
76
76
76
67
67
67
67
66
66
66
63
63
63
65
65
65
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
60
60
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,360
1,360
75
75
75
1,255
1,255
1,255
918
918
918
357
357
357
175
175
175
129
129
129
103
103
103
394
394
394
73
73
73
87
87
87
133
133
133
1,221
1,221
1,221
102
102
102
15
15
32,179
32,179
3,723
3,723
3,723
28,088
28,088
28,088
25,380
25,380
25,380
10,543
10,543
10,543
3,469
3,469
3,469
2,443
2,443
2,443
1,960
1,960
1,960
17,212
17,212
17,212
3,620
3,620
3,620
1,646
1,646
1,646
6,646
6,646
6,646
38,964
38,964
38,964
1,941
1,941
1,941
312
312
Coil
Latent
Load
Btu/h
953
953
703
703
703
2,386
2,386
2,386
4,471
4,471
4,471
973
973
973
790
790
790
1,400
1,400
1,400
1,123
1,123
1,123
4,042
4,042
4,042
684
684
684
943
943
943
1,256
1,256
1,256
6,040
6,040
6,040
1,112
1,112
1,112
0
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 24 of 100
SPACE
System Zone Room
Zone - 067
Block
spc_SS 251 Wrk Rm C_0
Peak
Zone - 068
Peak
Zone - 068
Block
Peak
spc_SS 230H, 200-201, 251H, 272H_0
Zone - 069
Peak
Zone - 069
Block
spc_SS 210/211 Wrk Rm C_0
Peak
Zone - 070
Peak
Zone - 070
Block
spc_SS 230F Office C_0
Peak
Zone - 071
Peak
Zone - 071
Block
spc_SS Wrk Rm 230 C_0
Peak
Zone - 072
Peak
Zone - 072
Block
spc_SS 230C-E Office_0
Peak
Zone - 073
Peak
Zone - 073
Block
spc_SS 240B Wrk Rm C_0
Peak
Zone - 074
Peak
Zone - 074
Block
spc_SS 181 Comp Rm C_0
Peak
Zone - 075
Peak
Zone - 075
Block
spc_SS 182 Comp Rm C_0
Peak
Zone - 076
Peak
Zone - 076
Block
Stdnt Srv VAV
Peak
Stdnt Srv VAV
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
0
6 /9
388
9 /12
388
388
9 /12
4,383
7 /16
4,383
4,383
7 /16
308
7 /15
308
308
7 /15
180
6 /18
180
180
6 /18
987
7 /16
987
987
7 /16
630
6/18
630
630
6 /18
240 10 /16
240
240 10 /16
854
7 /18
854
854
7 /18
863
9 /11
863
863
9 /11
23,178
23,178 7 /17
62
73
73
73
76
76
76
77
77
77
70
70
70
76
76
76
70
70
70
79
79
79
73
73
73
70
70
70
75
75
58
63
63
63
66
66
66
66
66
66
63
63
63
66
66
66
63
63
63
64
64
64
65
65
65
63
63
63
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
16
387
387
387
2,716
2,716
2,716
171
171
171
330
330
330
550
550
550
1,887
1,887
1,887
607
607
607
2,223
2,223
2,223
2,317
2,317
2,317
27,996
21,892
304
7,518
7,518
7,518
52,749
52,749
52,749
3,325
3,325
3,325
6,408
6,408
6,408
10,680
10,680
10,680
36,641
36,641
36,641
11,782
11,782
11,782
43,184
43,184
43,184
45,011
45,011
45,011
543,738
425,196
0
1,195
1,195
1,195
15,399
15,399
15,399
1,069
1,069
1,069
360
360
360
3,468
3,468
3,468
1,262
1,262
1,262
663
663
663
2,471
2,471
2,471
2,243
2,243
2,243
66,071
67,555
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /10
9 /12
9 /12
7 /16
7 /16
7 /16
7 /16
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
7 /18
7 /18
9 /11
9 /11
7 /17
67
73
73
73
76
76
76
76
76
76
73
73
73
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
75
75
60
63
63
63
66
66
66
66
66
66
65
65
65
66
66
66
65
65
65
67
67
67
65
65
65
63
63
63
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
15
387
387
387
2,716
2,716
2,716
171
171
171
326
326
326
550
550
550
1,854
1,854
1,854
595
595
595
2,223
2,223
2,223
2,317
2,317
2,317
27,337
21,892
312
8,858
8,858
8,858
113,463
113,463
113,463
7,815
7,815
7,815
9,430
9,430
9,430
25,113
25,113
25,113
48,827
48,827
48,827
15,938
15,938
15,938
45,640
45,640
45,640
49,534
49,534
49,534
713,169
592,652
0
1,856
1,856
1,856
27,598
27,598
27,598
1,937
1,937
1,937
781
781
781
6,215
6,215
6,215
2,736
2,736
2,736
1,674
1,674
1,674
4,381
4,381
4,381
3,536
3,536
3,536
122,218
121,687
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 25 of 100
SPACE
Floor
Area
ft²
System Zone Room
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
58.1
58.1
58.1
51.6
51.6
51.6
55.0
55.0
55.0
56.7
56.7
56.7
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.8
57.8
57.8
52.5
52.5
52.5
69.6
69.6
69.6
57.6
57.6
54.7
54.7
54.7
54.6
54.6
54.6
49.8
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
19,718
19,718
19,718
27,717
27,717
27,717
4,324
4,324
4,324
8,470
8,470
8,470
10,677
10,677
10,677
33,208
33,208
33,208
3,217
3,217
3,217
2,438
2,438
2,438
46,648
46,648
46,648
8,293
8,293
8,293
13,658
13,658
13,658
178,368
160,203
45,748
45,748
45,748
34,617
34,617
34,617
7,681
649
649
649
6,690
6,690
6,690
0
0
0
601
601
601
686
686
686
2,099
2,099
2,099
935
935
935
708
708
708
1,884
1,884
1,884
1,710
1,710
1,710
-741
-741
-741
15,221
21,247
6,031
6,031
6,031
4,790
4,790
4,790
2,079
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
21,552
21,552
21,552
27,487
27,487
27,487
4,459
4,459
4,459
10,580
10,580
10,580
12,077
12,077
12,077
35,790
35,790
35,790
8,578
8,578
8,578
6,500
6,500
6,500
64,856
64,856
64,856
8,454
8,454
8,454
27,101
27,101
27,101
227,433
211,887
48,957
48,957
48,957
37,048
37,048
37,048
18,754
Coil
Latent
Load
Btu/h
Alternative 2
spc_A 121 Office UC_0
Zone - 077
Zone - 077
spc_A 130A Class? FC1-4_0
Zone - 078
Zone - 078
spc_A 237-241 Office C_0
Zone - 093
Zone - 093
spc_A 202A Office D_0
Zone - 094
Zone - 094
spc_A 202A Office B_0
Zone - 095
Zone - 095
spc_A 202A Office C_0
Zone - 096
Zone - 096
spc_A 201 Office C_0
Zone - 097
Zone - 097
spc_A 200H-J Office C_0
Zone - 098
Zone - 098
spc_A 200 Office C_0
Zone - 099
Zone - 099
spc_A 210A-B Stairs C_0
Zone - 100
Zone - 100
spc_A 121 Restroom FC05_0
Zone - 118
Zone - 118
Admin FC
Admin FC
spc_A 161/162 Class C_0
Zone - 091
Zone - 091
spc_A 160 Wrk Rm C_0
Zone - 092
Zone - 092
spc_A 236A/B Offices_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
348
348
348
2,606
2,606
2,606
0
0
0
344
344
344
238
238
238
891
891
891
353
353
353
267
267
267
1,011
1,011
1,011
1,111
1,111
1,111
734
734
734
7,905
7,905
2,273
2,273
2,273
1,806
1,806
1,806
786
10 /16
10 /16
10 /15
10 /15
7 /16
7 /16
6 /10
6 /10
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
7 /18
7 /18
10 /16
10 /16
9 /16
6 /9
6 /9
6 /9
6 /9
7 /17
79
79
79
80
80
80
76
76
76
65
65
65
76
76
76
73
73
73
75
75
75
75
75
75
79
79
79
73
73
73
79
79
79
77
77
62
62
62
62
62
62
75
64
64
64
63
63
63
66
66
66
58
58
58
67
67
67
65
65
65
66
66
66
66
66
66
64
64
64
65
65
65
64
64
64
67
67
58
58
58
58
58
58
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
9 /16
7 /9
7 /9
7 /9
7 /9
7 /17
77
77
77
77
77
77
76
76
76
76
76
76
76
76
76
73
73
73
75
75
75
75
75
75
77
77
77
73
73
73
77
77
77
77
77
64
64
64
64
64
64
75
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
65
65
65
66
66
66
66
66
66
67
67
67
65
65
65
67
67
67
67
67
59
59
59
59
59
59
66
58.4
58.4
58.4
51.8
51.8
51.8
55.0
55.0
55.0
63.1
63.1
63.1
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.9
57.9
57.9
52.5
52.5
52.5
69.8
69.8
69.8
58.0
59.2
55.1
55.1
55.1
54.9
54.9
54.9
49.8
1,735
1,735
1,735
18,165
18,165
18,165
0
0
0
1,536
1,536
1,536
1,234
1,234
1,234
3,864
3,864
3,864
1,611
1,611
1,611
1,221
1,221
1,221
5,037
5,037
5,037
2,205
2,205
2,205
-7,656
-7,656
-7,656
28,952
30,207
9,347
9,347
9,347
7,420
7,420
7,420
3,579
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 26 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 113
Zone - 113
spc_A 244/246 Office C_0
Zone - 114
Zone - 114
spc_A 242/243 Class C_0
Zone - 115
Zone - 115
spc_A 238-246 Offices C_0
Zone - 116
Zone - 116
spc_A 216/218 Office C_0
Zone - 117
Zone - 117
Admin Pckg AHU
Admin Pckg AHU
spc_A 277F Class_0
Zone - 079
Zone - 079
spc_A 279A Hall C_0
Zone - 080
Zone - 080
spc_A 278A Cond Stair_0
Zone - 081
Zone - 081
spc_A 170/171 Lobby C_0
Zone - 082
Zone - 082
spc_A 172 Wrk Rm C_0
Zone - 083
Zone - 083
spc_A Wrk Rm 173 C_0
Zone - 084
Zone - 084
spc_A 177 Comp C_1
Zone - 085
Zone - 085
spc_A 174-176 Data C_0
Zone - 086
Zone - 086
spc_A 177 Comp C_0
Zone - 087
Zone - 087
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
786
786
367
367
367
1,839
1,839
1,839
2,547
2,547
2,547
2,057
2,057
2,057
11,676
11,676
1,395
1,395
1,395
7,584
7,584
7,584
321
321
321
1,279
1,279
1,279
2,002
2,002
2,002
671
671
671
626
626
626
201
201
201
626
626
626
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
10 /16
10 /16
6 /10
6 /10
7 /17
7 /17
6 /10
6/18
6 /18
6 /10
6 /10
9 /11
9 /11
7 /18
7 /18
6 /9
6 /9
10 /15
10 /15
6 /9
6 /9
9 /16
9 /16
7 /16
7 /16
75
75
75
75
75
79
79
79
65
65
65
75
75
75
65
65
70
70
70
65
65
65
70
70
70
73
73
73
62
62
62
80
80
80
62
62
62
77
77
77
76
76
76
66
66
66
66
66
64
64
64
58
58
58
66
66
66
58
58
63
63
63
58
58
58
63
63
63
65
65
65
58
58
58
63
63
63
58
58
58
67
67
67
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
70.0
70.0
70.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.8
49.8
49.8
49.8
49.8
55.5
55.5
55.5
57.3
57.3
57.3
49.8
49.8
49.8
55.4
55.4
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,510
2,510
2,510
5,680
5,680
5,680
1,443
1,443
1,443
483
483
483
2,570
2,570
2,570
1,214
1,214
1,214
1,490
1,490
1,490
1,917
1,917
1,917
1,042
1,042
1,042
7,681
7,681
3,589
3,589
3,589
49,570
49,570
49,570
81,320
81,320
81,320
20,104
20,104
20,104
242,629
193,483
46,615
46,615
46,615
105,509
105,509
105,509
26,795
26,795
26,795
8,969
8,969
8,969
47,731
47,731
47,731
22,553
22,553
22,553
27,671
27,671
27,671
31,338
31,338
31,338
19,354
19,354
19,354
2,079
2,079
971
971
971
5,095
5,095
5,095
4,472
4,472
4,472
5,442
5,442
5,442
28,881
25,762
4,376
4,376
4,376
5,555
5,555
5,555
411
411
411
2,208
2,208
2,208
5,370
5,370
5,370
1,747
1,747
1,747
1,303
1,303
1,303
497
497
497
1,843
1,843
1,843
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
7 /17
7 /17
7 /16
7 /18
7 /18
7 /16
7 /16
9 /11
9 /11
7 /9
7 /9
7 /9
7 /9
9 /16
9 /16
7 /9
7 /9
9 /16
9 /16
9 /16
9 /16
75
75
75
75
75
77
77
77
76
76
76
75
75
75
76
76
73
73
73
76
76
76
70
70
70
64
64
64
64
64
64
77
77
77
64
64
64
77
77
77
77
77
77
66
66
66
66
66
67
67
67
66
66
66
66
66
66
66
66
65
65
65
66
66
66
63
63
63
59
59
59
59
59
59
67
67
67
59
59
59
67
67
67
67
67
67
49.8
49.8
49.8
49.8
49.8
55.6
55.6
55.6
64.0
64.0
64.0
49.8
49.8
49.8
58.0
60.0
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,485
2,485
2,485
3,475
3,475
3,475
1,443
1,443
1,443
420
420
420
2,508
2,508
2,508
1,209
1,209
1,209
1,469
1,469
1,469
1,917
1,917
1,917
1,032
1,032
1,032
18,754
18,754
8,763
8,763
8,763
78,514
78,514
78,514
92,985
92,985
92,985
49,087
49,087
49,087
334,108
299,894
66,753
66,753
66,753
177,138
177,138
177,138
30,401
30,401
30,401
10,395
10,395
10,395
48,380
48,380
48,380
23,906
23,906
23,906
28,680
28,680
28,680
33,072
33,072
33,072
19,437
19,437
19,437
Coil
Latent
Load
Btu/h
3,579
3,579
1,672
1,672
1,672
12,862
12,862
12,862
11,426
11,426
11,426
9,369
9,369
9,369
55,677
63,035
9,143
9,143
9,143
15,367
15,367
15,367
511
511
511
2,145
2,145
2,145
8,439
8,439
8,439
4,762
4,762
4,762
2,059
2,059
2,059
835
835
835
3,541
3,541
3,541
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 27 of 100
SPACE
System Zone Room
spc_A 179/178 Data C_0
Peak
Zone - 088
Peak
Zone - 088
Block
spc_A 180E Com Lab C_0
Peak
Zone - 089
Peak
Zone - 089
Block
spc_A 271-277 Office C_0
Peak
Zone - 111
Peak
Zone - 111
Block
spc_A 277 Class_0
Peak
Zone - 112
Peak
Zone - 112
Block
Peak
Admin VAV
Admin VAV
Block
spc_BC 237 Class_0
Peak
Zone - 334
Peak
Zone - 334
Block
spc_BC 221 Lobby_0
Peak
Zone - 335
Peak
Zone - 335
Block
spc_BC 222 Class_0
Peak
Zone - 336
Peak
Zone - 336
Block
spc_215-219 Office_0
Peak
Zone - 337
Peak
Zone - 337
Block
spc_BC 224 Class_0
Peak
Zone - 338
Peak
Zone - 338
Block
spc_BC 2nd 226/228 Class_0
Peak
Zone - 339
Peak
Zone - 339
Block
spc_BC 2nd 230 Class_0
Peak
Zone - 340
Peak
Zone - 340
Block
spc_BC 115/116 Office_0
Peak
Zone - 351
Peak
Zone - 351
Block
spc_BC Office 137/139/141/142_0 Peak
Zone - 352
Peak
Zone - 352
Block
spc_BC 143 Office_0
Peak
Zone - 353
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
339
339
339
951
951
951
2,656
2,656
2,656
0
0
0
18,650
18,650
166
166
166
120
120
120
196
196
196
262
262
262
146
146
146
281
281
281
187
187
187
155
155
155
103
103
103
123
123
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
9 /15
10 /14
10 /14
7 /16
7 /16
7 /18
7 /18
10 /16
10 /16
9 /11
9 /11
9 /10
9 /10
9 /17
9 /17
9 /12
9 /12
10 /16
10 /16
10 /16
76
76
76
80
80
80
75
75
75
80
80
80
78
78
79
79
79
76
76
76
73
73
73
79
79
79
70
70
70
67
67
67
76
76
76
73
73
73
79
79
79
79
79
66
66
66
63
63
63
66
66
66
63
63
63
66
66
62
62
62
66
66
66
65
65
65
64
64
64
63
63
63
61
61
61
67
67
67
63
63
63
64
64
64
64
64
70.0
70.0
70.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
71.7
71.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
57.5
57.5
57.5
57.3
57.3
57.3
57.1
57.1
57.1
57.5
57.5
57.5
55.6
55.6
55.6
56.0
56.0
56.0
57.2
57.2
57.2
56.1
56.1
56.1
51.8
51.8
51.8
58.7
58.7
2,037
2,037
2,037
2,646
2,646
2,646
1,344
1,344
1,344
4,175
4,175
4,175
28,551
22,316
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
237
237
237
38
38
38
797
797
33,300
33,300
33,300
49,154
49,154
49,154
24,971
24,971
24,971
77,551
77,551
77,551
521,509
407,618
6,259
6,259
6,259
3,956
3,956
3,956
14,583
14,583
14,583
10,595
10,595
10,595
5,091
5,091
5,091
11,008
11,008
11,008
15,364
15,364
15,364
4,204
4,204
4,204
848
848
848
11,800
11,800
771
771
771
1,906
1,906
1,906
7,134
7,134
7,134
0
0
0
33,121
44,638
375
375
375
194
194
194
681
681
681
491
491
491
468
468
468
889
889
889
658
658
658
340
340
340
192
192
192
231
231
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /19
9 /19
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /14
9 /14
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
9 /12
9 /12
9 /11
9 /11
9 /17
9 /17
9 /12
9 /12
9 /17
9 /17
10 /16
71
71
71
77
77
77
76
76
76
77
77
77
77
77
77
77
77
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
76
76
76
73
73
73
76
76
76
79
79
66
66
66
67
67
67
66
66
66
67
67
67
67
67
66
66
66
66
66
66
65
65
65
67
67
67
63
63
63
63
63
63
67
67
67
63
63
63
67
67
67
64
64
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
58.2
58.2
58.2
57.3
57.3
57.3
57.1
57.1
57.1
57.7
57.7
57.7
56.5
56.5
56.5
56.3
56.3
56.3
57.2
57.2
57.2
56.1
56.1
56.1
52.2
52.2
52.2
58.7
58.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
2,008
2,008
2,008
2,644
2,644
2,644
1,337
1,337
1,337
4,061
4,061
4,061
26,008
22,285
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
237
237
237
38
38
38
797
797
33,409
33,409
33,409
51,546
51,546
51,546
32,823
32,823
32,823
77,838
77,838
77,838
651,278
557,619
7,849
7,849
7,849
5,195
5,195
5,195
17,225
17,225
17,225
12,759
12,759
12,759
6,331
6,331
6,331
12,300
12,300
12,300
20,480
20,480
20,480
5,546
5,546
5,546
1,020
1,020
1,020
13,862
13,862
Coil
Latent
Load
Btu/h
1,453
1,453
1,453
5,384
5,384
5,384
12,103
12,103
12,103
0
0
0
65,740
78,660
1,025
1,025
1,025
278
278
278
1,269
1,269
1,269
1,313
1,313
1,313
701
701
701
1,464
1,464
1,464
1,309
1,309
1,309
517
517
517
535
535
535
308
308
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 28 of 100
SPACE
System Zone Room
Zone - 353
spc_BC 109 Class_0
Zone - 354
Zone - 354
spc_BC 108 Class_0
Zone - 355
Zone - 355
spc_BC 106 Class_0
Zone - 356
Zone - 356
spc_BC 105 Class_0
Zone - 357
Zone - 357
spc_BC 101 Class_0
Zone - 358
Zone - 358
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
BC FC
Peak
BC FC
Block
spc_BC 130 Cafe/Kitchen_0
Peak
Zone - 341
Peak
Zone - 341
Block
spc_BC AH-2 245 Lecture_0
Peak
Zone - 342
Peak
Zone - 342
Block
spc_BC AH-3 301 Class_0
Peak
Zone - 343
Peak
Zone - 343
Block
spc_BC AH-4 302 Class_0
Peak
Zone - 344
Peak
Zone - 344
Block
spc_BC 306 Office (AH-5)_0
Peak
spc_BC 307-312 Office (AH-5)_0 Peak
spc_BC AH-5 304 Hall_0
Peak
Zone - 345
Peak
Zone - 345
Block
spc_BC AH-6 315 Lab_0
Peak
Zone - 346
Peak
Zone - 346
Block
spc_BC AH-7 314 Class_0
Peak
Zone - 347
Peak
Zone - 347
Block
spc_BC AH-8 313_0
Peak
Zone - 348
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
123
248
248
248
228
228
228
287
287
287
308
308
308
696
696
696
3,507
3,507
1,908
1,908
1,908
809
809
809
162
162
162
188
188
188
17
107
518
642
642
181
181
181
183
183
183
518
518
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
9 /12
9 /12
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /12
7 /19
7 /19
9 /13
9 /13
7 /10
7 /10
11 /13
11 /13
7 /18
10 /16
7 /18
10/16
10 /16
10 /16
6 /9
6 /9
9 /16
79
73
73
73
73
73
73
70
70
70
70
70
70
70
70
70
73
73
71
71
71
75
75
75
67
67
67
71
71
71
73
79
73
79
79
79
79
79
62
62
62
77
77
64
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
64
64
64
65
65
65
60
60
60
58
58
58
65
64
65
64
64
64
64
64
58
58
58
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
58.7
53.9
53.9
53.9
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.8
56.8
49.0
49.0
49.0
48.5
48.5
48.5
57.5
57.5
57.5
55.0
55.0
55.0
57.7
59.1
54.7
58.0
58.0
58.3
58.3
58.3
56.9
56.9
56.9
55.0
55.0
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
902
902
902
435
435
435
1,005
1,005
11,800
5,234
5,234
5,234
6,925
6,925
6,925
15,674
15,674
15,674
16,788
16,788
16,788
36,297
36,297
36,297
164,625
128,212
25,681
25,681
25,681
8,768
8,768
8,768
9,949
9,949
9,949
14,106
14,106
14,106
1,203
14,924
6,067
22,194
20,846
13,789
13,789
13,789
7,351
7,351
7,351
19,025
19,025
231
766
766
766
704
704
704
918
918
918
985
985
985
2,230
2,230
2,230
10,125
10,014
7,496
7,496
7,496
2,709
2,709
2,709
457
457
457
435
435
435
41
199
801
1,041
657
394
394
394
486
486
486
1,924
1,924
10 /16
9 /13
9 /13
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /13
7 /19
7 /19
9 /14
9 /14
7 /10
7 /10
9 /15
9 /15
7 /18
10 /16
7 /18
9 /17
9 /16
9 /16
7 /17
7 /17
9 /16
79
75
75
75
73
73
73
70
70
70
70
70
70
70
70
70
75
75
71
71
71
77
77
77
67
67
67
78
78
78
73
79
73
76
76
77
77
77
75
75
75
77
77
64
65
65
65
63
63
63
63
63
63
63
63
63
63
63
63
65
65
64
64
64
66
66
66
60
60
60
66
66
66
65
64
65
67
67
67
67
67
66
66
66
67
67
58.7
54.5
54.5
54.5
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.9
60.6
49.0
49.0
49.0
48.7
48.7
48.7
57.5
57.5
57.5
57.3
57.3
57.3
57.7
59.1
54.7
58.0
59.1
58.5
58.5
58.5
61.5
61.5
61.5
55.0
55.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
902
902
902
435
435
435
1,005
1,005
13,862
6,369
6,369
6,369
8,775
8,775
8,775
17,730
17,730
17,730
19,220
19,220
19,220
40,708
40,708
40,708
195,368
154,845
28,282
28,282
28,282
10,394
10,394
10,394
11,797
11,797
11,797
17,273
17,273
17,273
1,823
19,637
7,596
29,057
27,346
18,690
18,690
18,690
9,470
9,470
9,470
25,235
25,235
Coil
Latent
Load
Btu/h
308
1,430
1,430
1,430
1,096
1,096
1,096
1,494
1,494
1,494
1,603
1,603
1,603
3,631
3,631
3,631
17,976
18,247
13,513
13,513
13,513
4,960
4,960
4,960
624
624
624
1,481
1,481
1,481
75
265
1,033
1,373
1,870
1,012
1,012
1,012
1,133
1,133
1,133
3,625
3,625
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 29 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 348
BC Hydronic AHU
BC Hydronic AHU
spc_CC 108 C_0
Zone - 120
Zone - 120
spc_CC 106 Mechanical C_0
Zone - 121
Zone - 121
spc_CC 203 Storage_0
Zone - 122
Zone - 122
spc_CC 202 Storage_0
Zone - 123
Zone - 123
spc_CC 201 Eating Area C_0
Zone - 124
Zone - 124
Campus Center Dual Deck
Campus Center Dual Deck
spc_CC Class 122-126 C_0
Zone - 119
Zone - 119
Campus Center FC
Campus Center FC
spc_CC 228 Comp C_0
Zone - 125
Zone - 125
Bookstore 1
Zone - 362
Zone - 362
Bookstore 2
Zone - 363
Zone - 363
Bookstore 3
Zone - 364
Zone - 364
Bookstore 4
Zone - 365
Zone - 365
Bookstore 5
Zone - 366
Zone - 366
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
518
4,592
4,592
381
381
381
530
530
530
159
159
159
133
133
133
1,974
1,974
1,974
3,176
3,176
1,023
1,023
1,023
1,023
1,023
519
519
519
915
915
915
915
915
915
915
915
915
915
915
915
915
915
915
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
9 /12
9 /12
9 /12
9 /12
10 /14
6 /18
6 /18
6 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
80
80
79
79
79
76
76
76
76
76
76
73
73
73
73
73
73
79
79
70
70
70
70
70
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
63
63
64
64
64
67
67
67
67
67
67
63
63
63
63
63
63
62
62
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.0
55.2
55.2
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.1
57.1
57.1
57.1
57.1
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
1,005
6,464
6,464
797
797
797
480
480
480
556
556
556
430
430
430
1,808
1,808
1,808
4,073
4,073
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
404
404
404
404
404
404
404
404
19,025
120,862
101,266
12,551
12,551
12,551
11,849
11,849
11,849
8,761
8,761
8,761
6,778
6,778
6,778
28,473
28,473
28,473
68,413
57,628
64,980
64,980
64,980
64,980
64,980
17,432
17,432
17,432
11,760
11,760
11,760
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
1,924
14,942
6,374
167
167
167
761
761
761
277
277
277
137
137
137
4,445
4,445
4,445
5,787
5,745
3,184
3,184
3,184
3,184
3,184
1,513
1,513
1,513
3,754
3,754
3,754
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /17
9 /17
9 /13
9 /13
9 /13
9 /13
9 /14
7 /18
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
77
77
76
76
76
76
76
76
76
76
76
75
75
75
75
75
75
77
77
73
73
73
73
73
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
65
65
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
55.0
55.8
58.3
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.4
57.4
57.4
57.4
57.4
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,005
6,464
6,464
784
784
784
477
477
477
554
554
554
414
414
414
1,746
1,746
1,746
3,974
3,459
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
404
404
404
404
404
404
404
404
25,235
150,199
134,479
15,748
15,748
15,748
15,813
15,813
15,813
13,075
13,075
13,075
9,068
9,068
9,068
33,559
33,559
33,559
87,263
75,402
69,485
69,485
69,485
69,485
69,485
22,424
22,424
22,424
18,552
18,552
18,552
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
Coil
Latent
Load
Btu/h
3,625
27,722
25,060
1,787
1,787
1,787
1,129
1,129
1,129
379
379
379
204
204
204
12,956
12,956
12,956
16,454
17,396
6,613
6,613
6,613
6,613
6,613
2,598
2,598
2,598
6,278
6,278
6,278
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 30 of 100
SPACE
System Zone Room
Floor
Area
ft²
Bookstore 6
Peak
Zone - 367
Peak
Zone - 367
Block
Campus Center Packg RTU-1
Peak
Campus Center Packg RTU-1
Block
spc_DM FC-Music Office_0
Peak
Zone - 137
Peak
Zone - 137
Block
Peak
spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0
Zone - 138
Peak
Zone - 138
Block
spc_DM FC 3-1 Dress Rms Int_0 Peak
Zone - 139
Peak
Zone - 139
Block
spc_DM FC 3-1 Dress Rms_0
Peak
Zone - 140
Peak
Zone - 140
Block
Drama/Music Fan Coil
Peak
Drama/Music Fan Coil
Block
spc_HP-9 Office_0
Peak
Zone - 126
Peak
Zone - 126
Block
spc_DM HP-7 Storage_0
Peak
Zone - 127
Peak
Zone - 127
Block
spc_DM HP-7 Dress Rm_0
Peak
Zone - 128
Peak
Zone - 128
Block
spc_DM HP 3/4 Class_0
Peak
Zone - 129
Peak
Zone - 129
Block
spc_DM HP-2 Class_0
Peak
Zone - 130
Peak
Zone - 130
Block
spc_DM HP-5 Performance Rm_0 Peak
Zone - 131
Peak
Zone - 131
Block
spc_DM HP-10 Prop Rm_0
Peak
Zone - 132
Peak
Zone - 132
Block
spc_DM HP-1 Main Corridor_0
Peak
Zone - 133
Peak
Zone - 133
Block
915
915
915
6,007
6,007
338
338
338
892
892
892
267
267
267
327
327
327
1,824
1,824
121
121
121
57
57
57
9,797
9,797
9,797
926
926
926
569
569
569
1,176
1,176
1,176
1,131
1,131
1,131
7,381
7,381
7,381
Project Name:
Dataset Name:
SBCC TRACE.TRC
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
10 /16
10 /16
9 /17
9 /12
9 /12
10 /15
10 /15
10 /15
10 /15
6 /9
6 /9
11 /13
11 /13
9 /12
9 /12
7 /18
7 /18
9 /11
9 /11
76
76
76
76
76
79
79
79
75
75
75
76
76
76
79
79
79
76
76
73
73
73
80
80
80
80
80
80
62
62
62
71
71
71
73
73
73
73
73
73
70
70
70
66
66
66
66
66
64
64
64
66
66
66
66
66
66
64
64
64
67
67
63
63
63
63
63
63
63
63
63
58
58
58
58
58
58
63
63
63
65
65
65
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.4
49.4
49.4
51.0
51.0
56.4
56.4
56.4
54.3
54.3
54.3
44.5
44.5
44.5
58.3
58.3
58.3
55.7
55.7
57.0
57.0
57.0
54.8
54.8
54.8
51.3
51.3
51.3
55.4
55.4
55.4
59.2
59.2
59.2
53.5
53.5
53.5
57.4
57.4
57.4
56.2
56.2
56.2
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
10,160
10,160
10,160
79,989
79,989
8,123
8,123
8,123
9,831
9,831
9,831
2,946
2,946
2,946
8,853
8,853
8,853
29,753
27,815
4,747
4,747
4,747
261
261
261
99,554
99,554
99,554
21,837
21,837
21,837
35,452
35,452
35,452
27,637
27,637
27,637
36,017
36,017
36,017
106,822
106,822
106,822
2,839
2,839
2,839
19,459
19,459
633
633
633
1,432
1,432
1,432
1,098
1,098
1,098
269
269
269
3,432
4,394
263
263
263
35
35
35
25,148
25,148
25,148
2,451
2,451
2,451
1,082
1,082
1,082
4,324
4,324
4,324
1,740
1,740
1,740
9,194
9,194
9,194
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /17
9 /13
9 /13
7 /16
7 /16
9 /16
9 /16
7 /16
7 /16
9 /13
9 /13
7 /15
7 /15
7 /17
7 /17
9 /11
9 /11
76
76
76
76
76
76
76
76
75
75
75
77
77
77
79
79
79
76
76
75
75
75
76
76
76
77
77
77
76
76
76
75
75
75
77
77
77
75
75
75
70
70
70
66
66
66
66
66
67
67
67
66
66
66
67
67
67
64
64
64
67
67
65
65
65
66
66
66
67
67
67
66
66
66
65
65
65
66
66
66
66
66
66
63
63
63
49.4
49.4
49.4
51.0
51.0
56.5
56.5
56.5
54.3
54.3
54.3
45.0
45.0
45.0
58.3
58.3
58.3
55.8
56.8
57.6
57.6
57.6
55.8
55.8
55.8
51.5
51.5
51.5
59.2
59.2
59.2
60.5
60.5
60.5
59.5
59.5
59.5
57.8
57.8
57.8
56.2
56.2
56.2
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
17,188
17,188
17,188
126,914
126,914
12,772
12,772
12,772
21,797
21,797
21,797
2,242
2,242
2,242
10,451
10,451
10,451
47,261
42,971
6,446
6,446
6,446
1,151
1,151
1,151
104,158
104,158
104,158
33,229
33,229
33,229
39,761
39,761
39,761
38,930
38,930
38,930
57,496
57,496
57,496
120,423
120,423
120,423
Coil
Latent
Load
Btu/h
5,361
5,361
5,361
35,683
35,683
1,763
1,763
1,763
1,818
1,818
1,818
2,311
2,311
2,311
330
330
330
6,222
7,103
408
408
408
120
120
120
68,283
68,283
68,283
5,820
5,820
5,820
3,265
3,265
3,265
8,980
8,980
8,980
2,459
2,459
2,459
11,397
11,397
11,397
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 31 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_DM HP-9 Class_0
Zone - 148
Zone - 148
spc_DM HP-6 Office_0
Zone - 149
Zone - 149
spc_DM HP-8 Class1_0
Zone - 150
Zone - 150
spc_DM PHP-5-2 Offices_0
Zone - 151
Zone - 151
spc_PHP-2-1 Cargo Elevator_0
Zone - 152
Zone - 152
spc_DM PRP-5-1 Restroom_0
Zone - 153
Zone - 153
spc_DM PRP-5-1 Restroom1_0
Zone - 154
Zone - 154
Drama/Music HP
Drama/Music HP
spc_AC-1 Auditorium_0
Zone - 141
Zone - 141
spc_DM AN-2 Corridor_0
Zone - 142
Zone - 142
spc_DM AC-2 Rehearsal Rm_0
Zone - 143
Zone - 143
spc_DM ZN-1 Class_0
Zone - 144
Zone - 144
spc_DM ZN-3 Hall_0
Zone - 145
Zone - 145
spc_DM Zn-3 Offices_0
Zone - 146
Zone - 146
spc_ZN-3 Conf_0
Zone - 147
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
192
192
192
220
220
220
592
592
592
292
292
292
122
122
122
848
848
848
1,177
1,177
1,177
24,602
24,602
3,790
3,790
3,790
701
701
701
1,135
1,135
1,135
417
417
417
209
209
209
177
177
177
405
405
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /15
10 /15
6 /9
6 /9
10 /15
10 /15
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
9 /12
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
6 /18
6 /18
10 /16
10 /16
10 /16
10 /16
6 /10
80
80
80
62
62
62
80
80
80
79
79
79
79
79
79
79
79
79
79
79
79
73
73
80
80
80
75
75
75
80
80
80
70
70
70
79
79
79
79
79
79
65
65
63
63
63
58
58
58
63
63
63
64
64
64
64
64
64
64
64
64
64
64
64
63
63
63
63
63
66
66
66
63
63
63
63
63
63
64
64
64
64
64
64
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
80.0
80.0
80.0
73.1
73.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
51.3
51.3
51.3
58.2
58.2
58.2
51.3
51.3
51.3
52.2
52.2
52.2
58.6
58.6
58.6
79.6
79.6
79.6
79.6
79.6
79.6
58.9
58.9
54.9
54.9
54.9
55.9
55.9
55.9
50.7
50.7
50.7
56.6
56.6
56.6
49.9
49.9
49.9
51.7
51.7
51.7
50.6
50.6
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
24
24
24
64
64
64
206
206
1,946
1,946
1,946
10,408
10,408
10,408
6,020
6,020
6,020
2,564
2,564
2,564
4,056
4,056
4,056
538
538
538
747
747
747
358,606
299,869
74,299
74,299
74,299
11,804
11,804
11,804
10,848
10,848
10,848
20,443
20,443
20,443
583
583
583
1,443
1,443
1,443
4,907
4,907
492
492
492
311
311
311
1,521
1,521
1,521
545
545
545
99
99
99
-2,632
-2,632
-2,632
-3,655
-3,655
-3,655
40,918
47,013
9,753
9,753
9,753
1,126
1,126
1,126
2,908
2,908
2,908
1,296
1,296
1,296
169
169
169
330
330
330
1,311
1,311
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
76
76
76
65
65
65
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
77
77
75
75
75
77
77
77
73
73
73
77
77
77
76
76
76
77
77
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
65
65
65
67
67
67
67
67
67
67
67
51.4
51.4
51.4
58.8
58.8
58.8
51.5
51.5
51.5
52.4
52.4
52.4
58.8
58.8
58.8
79.7
79.7
79.7
79.7
79.7
79.7
59.7
62.3
55.5
55.5
55.5
55.9
55.9
55.9
51.3
51.3
51.3
56.7
56.7
56.7
51.4
51.4
51.4
52.3
52.3
52.3
53.5
53.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
24
24
24
64
64
64
206
206
5,018
5,018
5,018
11,069
11,069
11,069
6,298
6,298
6,298
2,691
2,691
2,691
6,557
6,557
6,557
5,343
5,343
5,343
7,418
7,418
7,418
445,988
374,351
83,988
83,988
83,988
13,640
13,640
13,640
13,026
13,026
13,026
22,815
22,815
22,815
715
715
715
1,748
1,748
1,748
5,430
5,430
1,203
1,203
1,203
475
475
475
4,129
4,129
4,129
1,517
1,517
1,517
288
288
288
-46,142
-46,142
-46,142
-64,061
-64,061
-64,061
-1,859
7,013
26,500
26,500
26,500
1,430
1,430
1,430
7,893
7,893
7,893
2,691
2,691
2,691
468
468
468
919
919
919
3,494
3,494
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 32 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 147
spc_DM Scene Shop HV-1_0
Zone - 155
Zone - 155
Drama/Music MZU
Drama/Music MZU
spc_EBS 217/Storage C_0
Zone - 156
Zone - 156
spc_EBS 215 Class C_0
Zone - 157
Zone - 157
spc_EBS 209 Class C_0
Zone - 158
Zone - 158
spc_EBS 210 Class C_0
Zone - 159
Zone - 159
spc_EBS 109/127 Lobby C_0
Zone - 160
Zone - 160
spc_EBS 125 Class C_0
Zone - 161
Zone - 161
spc_EBS 102 Class C_0
Zone - 162
Zone - 162
spc_EBS 123 Class C_0
Zone - 163
Zone - 163
spc_EBS 119 Offices C_0
Zone - 164
Zone - 164
spc_EBS 119 Office C_0
Zone - 165
Zone - 165
spc_EBS 116 Office C_0
Zone - 166
Zone - 166
spc_EBS 110-113 Office UC_0
Zone - 167
Zone - 167
spc_EBS 114 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
405
1,711
1,711
1,711
8,545
8,545
2,046
2,046
2,046
758
758
758
1,358
1,358
1,358
1,333
1,333
1,333
1,771
1,771
1,771
396
396
396
1,332
1,332
1,332
1,622
1,622
1,622
399
399
399
306
306
306
156
156
156
515
515
515
893
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /10
10 /13
10 /13
9 /16
7 /15
7 /15
7 /16
7 /16
10 /15
10 /15
7 /18
7 /18
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
10 /14
65
77
77
77
77
77
77
77
77
76
76
76
80
80
80
73
73
73
75
75
75
73
73
73
73
73
73
73
73
73
75
75
75
75
75
75
73
73
73
73
73
73
79
58
59
59
59
67
67
66
66
66
66
66
66
63
63
63
65
65
65
66
66
66
65
65
65
65
65
65
65
65
65
66
66
66
66
66
66
65
65
65
65
65
65
62
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
50.6
57.7
57.7
57.7
55.4
55.4
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
206
1,561
1,561
1,561
8,045
8,045
931
931
931
493
493
493
1,547
1,547
1,547
1,511
1,511
1,511
744
744
744
473
473
473
2,019
2,019
2,019
1,486
1,486
1,486
309
309
309
177
177
177
220
220
220
624
624
624
1,093
4,907
24,799
24,799
24,799
149,125
129,890
18,050
18,050
18,050
9,553
9,553
9,553
29,992
29,992
29,992
29,286
29,286
29,286
14,421
14,421
14,421
9,178
9,178
9,178
39,142
39,142
39,142
28,811
28,811
28,811
5,997
5,997
5,997
3,436
3,436
3,436
4,262
4,262
4,262
12,097
12,097
12,097
21,186
1,311
3,134
3,134
3,134
20,027
30,017
3,114
3,114
3,114
2,661
2,661
2,661
3,489
3,489
3,489
4,607
4,607
4,607
2,924
2,924
2,924
1,369
1,369
1,369
4,604
4,604
4,604
5,608
5,608
5,608
1,057
1,057
1,057
811
811
811
368
368
368
1,214
1,214
1,214
2,014
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /14
9 /14
9 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /14
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
75
75
75
75
75
75
73
73
73
73
73
73
75
75
75
75
75
75
75
75
75
73
73
73
73
73
73
77
67
66
66
66
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
66
53.5
58.2
58.2
58.2
55.9
57.5
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
206
1,561
1,561
1,561
8,045
8,045
903
903
903
493
493
493
1,515
1,515
1,515
1,493
1,493
1,493
744
744
744
473
473
473
2,019
2,019
2,019
1,454
1,454
1,454
309
309
309
177
177
177
220
220
220
624
624
624
1,079
5,430
30,462
30,462
30,462
171,824
156,601
40,996
40,996
40,996
17,369
17,369
17,369
45,366
45,366
45,366
45,809
45,809
45,809
35,058
35,058
35,058
14,006
14,006
14,006
55,862
55,862
55,862
46,115
46,115
46,115
10,829
10,829
10,829
6,764
6,764
6,764
6,557
6,557
6,557
19,460
19,460
19,460
22,361
Coil
Latent
Load
Btu/h
3,494
10,580
10,580
10,580
53,975
55,726
4,331
4,331
4,331
4,766
4,766
4,766
9,476
9,476
9,476
8,212
8,212
8,212
4,199
4,199
4,199
2,548
2,548
2,548
8,567
8,567
8,567
9,995
9,995
9,995
1,822
1,822
1,822
1,398
1,398
1,398
677
677
677
2,235
2,235
2,235
5,495
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 33 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 168
Zone - 168
spc_EBS 115 Class C_0
Zone - 169
Zone - 169
spc_EBS 209 Class UC_0
Zone - 172
Zone - 172
spc_EBS 210 Class C_1
Zone - 173
Zone - 173
spc_EBS 215 Class C_1
Zone - 174
Zone - 174
spc_EBS 218 Office C_0
Zone - 175
Zone - 175
spc_EBS 216 Office C_0
Zone - 176
Zone - 176
EBS VAV
EBS VAV
spc_H 326 Class C_0
Zone - 206
Zone - 206
spc_H 328 Class C_0
Zone - 207
Zone - 207
spc_H 328 Office C_0
Zone - 208
Zone - 208
Humanities Fan Coil
Humanities Fan Coil
spc_H 104/107/112 Art C_0
Zone - 177
Zone - 177
spc_H 102 Class C_0
Zone - 178
Zone - 178
spc_H 106 Office C_0
Zone - 179
Zone - 179
spc_H 2444 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
893
893 10 /14
1,659
9 /16
1,659
1,659
9 /16
1,334
7 /16
1,334
1,334
7 /16
1,334
7 /16
1,334
1,334
7 /16
790
7 /18
790
790
7 /18
70
7 /18
70
70
7/18
74
7 /17
74
74
7 /17
18,147
18,147 7 /17
845
5 /17
845
845
5 /17
1,818 7 /16
1,818
1,818 7 /16
300
7 /12
300
300
7 /12
2,963
2,963 7 /17
7,121 7 /16
7,121
7,121 7 /16
1,004 7 /16
1,004
1,004 7 /16
229
7 /17
229
229
7 /17
555
7 /16
79
79
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
72
72
72
76
76
76
73
73
73
75
75
76
76
76
76
76
76
75
75
75
76
62
62
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
63
63
63
66
66
66
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
54.3
54.3
54.3
56.6
56.6
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
1,093
1,093
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,925
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,288
5,288
5,288
627
627
627
122
122
122
346
21,186
21,186
31,380
31,380
31,380
16,818
16,818
16,818
16,818
16,818
16,818
14,759
14,759
14,759
2,665
2,665
2,665
826
826
826
308,677
289,380
76,201
76,201
76,201
24,051
24,051
24,051
4,645
4,645
4,645
104,897
101,595
91,368
91,368
91,368
10,835
10,835
10,835
2,102
2,102
2,102
5,987
2,014
2,014
6,149
6,149
6,149
4,685
4,685
4,685
4,685
4,685
4,685
2,731
2,731
2,731
166
166
166
195
195
195
52,452
52,299
2,350
2,350
2,350
6,371
6,371
6,371
631
631
631
9,352
9,537
24,945
24,945
24,945
3,519
3,519
3,519
604
604
604
1,944
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /14
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /17
7 /15
7 /15
9 /16
9 /16
9 /17
9 /17
9 /16
77
77
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
73
73
73
76
76
76
76
76
76
75
75
77
77
77
77
77
77
76
76
76
77
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
65
65
65
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
57.2
57.2
57.2
56.7
57.1
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,079
1,079
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,801
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,284
5,284
5,284
600
600
600
119
119
119
331
22,361
22,361
49,825
49,825
49,825
30,579
30,579
30,579
30,579
30,579
30,579
23,381
23,381
23,381
3,913
3,913
3,913
1,626
1,626
1,626
504,179
486,608
92,686
92,686
92,686
49,932
49,932
49,932
8,423
8,423
8,423
151,042
148,011
99,527
99,527
99,527
11,228
11,228
11,228
2,209
2,209
2,209
6,204
Coil
Latent
Load
Btu/h
5,495
5,495
11,570
11,570
11,570
8,391
8,391
8,391
8,391
8,391
8,391
5,082
5,082
5,082
305
305
305
336
336
336
97,796
94,521
5,460
5,460
5,460
11,390
11,390
11,390
1,341
1,341
1,341
18,190
17,762
43,603
43,603
43,603
6,979
6,979
6,979
1,184
1,184
1,184
3,856
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 34 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 180
Zone - 180
spc_H 245A/B Class C_0
Zone - 181
Zone - 181
spc_H 226/A office C_0
Zone - 182
Zone - 182
spc_H 208-217 Office C_0
Zone - 183
Zone - 183
spc_H 225 Office C_0
Zone - 184
Zone - 184
spc_H 242/207 Corridor C_0
Zone - 185
Zone - 185
spc_H 123U Art AH-1/23_0
Zone - 186
Zone - 186
spc_H 111 Class C_0
Zone - 187
Zone - 187
spc_H 221/220/204 Class C_0
Zone - 188
Zone - 188
spc_H 232A Class C_0
Zone - 189
Zone - 189
spc_H 239 Class Office_0
Zone - 190
Zone - 190
spc_H 237 Office C_0
Zone - 191
Zone - 191
spc_H 236 Office C_0
Zone - 192
Zone - 192
spc_H 241 Class C_0
Zone - 193
Zone - 193
spc_H 309-318 Offices C_0
Zone - 194
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
555
555
1,686
1,686
1,686
272
272
272
1,065
1,065
1,065
267
267
267
4,126
4,126
4,126
2,482
2,482
2,482
1,805
1,805
1,805
4,564
4,564
4,564
1,111
1,111
1,111
306
306
306
90
90
90
272
272
272
571
571
571
1,012
1,012
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /17
7 /17
11 /13
11 /13
11 /14
11 /14
11 /14
11 /14
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
11 /14
76
76
75
75
75
71
71
71
73
73
73
73
73
73
79
79
79
75
75
75
76
76
76
77
77
77
76
76
76
77
77
77
75
75
75
75
75
75
76
76
76
73
73
66
66
66
66
66
58
58
58
60
60
60
60
60
60
64
64
64
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
60
60
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
346
346
2,157
2,157
2,157
798
798
798
3,496
3,496
3,496
765
765
765
1,412
1,412
1,412
2,382
2,382
2,382
1,127
1,127
1,127
3,577
3,577
3,577
693
693
693
311
311
311
48
48
48
145
145
145
356
356
356
4,319
4,319
5,987
5,987
37,265
37,265
37,265
13,783
13,783
13,783
60,401
60,401
60,401
13,211
13,211
13,211
24,400
24,400
24,400
41,156
41,156
41,156
19,474
19,474
19,474
61,807
61,807
61,807
11,982
11,982
11,982
5,382
5,382
5,382
828
828
828
2,500
2,500
2,500
6,155
6,155
6,155
74,623
74,623
1,944
1,944
5,523
5,523
5,523
89
89
89
766
766
766
192
192
192
3,332
3,332
3,332
8,130
8,130
8,130
6,325
6,325
6,325
15,809
15,809
15,809
3,891
3,891
3,891
1,060
1,060
1,060
238
238
238
719
719
719
1,999
1,999
1,999
728
728
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /14
9 /14
9 /15
9 /15
9 /15
9 /15
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /15
7 /15
9 /16
9 /16
7 /15
7 /15
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /15
77
77
77
77
77
77
77
77
78
78
78
78
78
78
77
77
77
76
76
76
77
77
77
77
77
77
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
78
78
67
67
67
67
67
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
331
331
2,071
2,071
2,071
743
743
743
2,999
2,999
2,999
665
665
665
1,401
1,401
1,401
2,313
2,313
2,313
1,078
1,078
1,078
3,577
3,577
3,577
663
663
663
311
311
311
47
47
47
142
142
142
341
341
341
3,657
3,657
6,204
6,204
40,964
40,964
40,964
15,383
15,383
15,383
74,566
74,566
74,566
13,581
13,581
13,581
25,840
25,840
25,840
45,783
45,783
45,783
20,181
20,181
20,181
67,488
67,488
67,488
12,417
12,417
12,417
5,994
5,994
5,994
871
871
871
2,628
2,628
2,628
6,379
6,379
6,379
87,004
87,004
Coil
Latent
Load
Btu/h
3,856
3,856
11,713
11,713
11,713
999
999
999
4,843
4,843
4,843
1,216
1,216
1,216
9,229
9,229
9,229
17,267
17,267
17,267
12,544
12,544
12,544
27,948
27,948
27,948
7,718
7,718
7,718
1,874
1,874
1,874
467
467
467
1,408
1,408
1,408
3,965
3,965
3,965
4,603
4,603
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 35 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 194
spc_H 240 Class C_0
Zone - 195
Zone - 195
spc_H 300 Restrooms C_0
Zone - 196
Zone - 196
spc_H 322 Office C_0
Zone - 197
Zone - 197
spc_H 323 Office C_0
Zone - 198
Zone - 198
spc_H 300H Hall C_0
Zone - 199
Zone - 199
spc_H 202 Class C_0
Zone - 200
Zone - 200
spc_H 205 Office C_0
Zone - 201
Zone - 201
spc_H 205/203 Class C_0
Zone - 202
Zone - 202
spc_H 232B Office C_0
Zone - 203
Zone - 203
spc_H 223 Class C_0
Zone - 204
Zone - 204
spc_H 223U Storage C_0
Zone - 205
Zone - 205
spc_H 306 Class C_0
Zone - 211
Zone - 211
spc_H 308 Class H_0
Zone - 212
Zone - 212
spc_H 301-307 Classes C_0
Zone - 213
Zone - 213
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,012
818
818
818
339
339
339
265
265
265
265
265
265
3,593
3,593
3,593
1,118
1,118
1,118
270
270
270
846
846
846
161
161
161
616
616
616
165
165
165
727
727
727
512
512
512
3,348
3,348
3,348
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
11 /14
7 /15
7 /15
9 /17
9 /17
11 /14
11 /14
7 /17
7 /17
10 /16
10 /16
8/10
8 /10
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /16
7 /16
7 /15
7 /15
73
77
77
77
76
76
76
73
73
73
75
75
75
79
79
79
67
67
67
75
75
75
76
76
76
75
75
75
76
76
76
77
77
77
76
76
76
76
76
76
77
77
77
60
66
66
66
67
67
67
60
60
60
66
66
66
64
64
64
61
61
61
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
4,319
642
642
642
542
542
542
1,069
1,069
1,069
141
141
141
3,898
3,898
3,898
2,401
2,401
2,401
144
144
144
528
528
528
86
86
86
385
385
385
51
51
51
454
454
454
320
320
320
2,748
2,748
2,748
74,623
11,100
11,100
11,100
14,193
14,193
14,193
18,478
18,478
18,478
2,434
2,434
2,434
67,353
67,353
67,353
41,487
41,487
41,487
2,483
2,483
2,483
9,121
9,121
9,121
1,483
1,483
1,483
6,648
6,648
6,648
876
876
876
7,841
7,841
7,841
5,526
5,526
5,526
47,476
47,476
47,476
728
2,834
2,834
2,834
619
619
619
190
190
190
700
700
700
9,908
9,908
9,908
3,433
3,433
3,433
714
714
714
2,962
2,962
2,962
426
426
426
2,159
2,159
2,159
250
250
250
2,546
2,546
2,546
1,795
1,795
1,795
11,597
11,597
11,597
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /15
7 /15
7 /15
9 /17
9 /17
9 /15
9 /15
9 /17
9 /17
9 /16
9 /16
9 /11
9 /11
9 /17
9 /17
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
9 /15
9 /15
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
78
77
77
77
76
76
76
78
78
78
76
76
76
77
77
77
70
70
70
76
76
76
77
77
77
76
76
76
77
77
77
78
78
78
76
76
76
76
76
76
76
76
76
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
63
63
63
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
3,657
642
642
642
210
210
210
890
890
890
138
138
138
3,839
3,839
3,839
2,239
2,239
2,239
141
141
141
505
505
505
84
84
84
368
368
368
47
47
47
441
441
441
311
311
311
2,733
2,733
2,733
87,004
12,091
12,091
12,091
14,647
14,647
14,647
21,157
21,157
21,157
2,558
2,558
2,558
126,357
126,357
126,357
45,716
45,716
45,716
2,609
2,609
2,609
9,452
9,452
9,452
1,558
1,558
1,558
6,890
6,890
6,890
878
878
878
19,161
19,161
19,161
13,504
13,504
13,504
102,755
102,755
102,755
Coil
Latent
Load
Btu/h
4,603
5,010
5,010
5,010
4,236
4,236
4,236
1,203
1,203
1,203
1,371
1,371
1,371
24,964
24,964
24,964
5,771
5,771
5,771
1,399
1,399
1,399
5,875
5,875
5,875
835
835
835
4,282
4,282
4,282
357
357
357
4,551
4,551
4,551
3,208
3,208
3,208
20,961
20,961
20,961
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 36 of 100
SPACE
System Zone Room
spc_H 301 Class C_0
Peak
Zone - 214
Peak
Zone - 214
Block
spc_H 3281 Hall C_0
Peak
Zone - 215
Peak
Zone - 215
Block
Humanities VAV
Peak
Humanities VAV
Block
spc_IDC 335 Office C_0
Peak
Zone - 220
Peak
Zone - 220
Block
spc_IDC 313 Wrk Rm_0
Peak
Zone - 221
Peak
Zone - 221
Block
spc_IDC 317 Wrk Rm C_0
Peak
Zone - 222
Peak
Zone - 222
Block
spc_IDC 329 C_0
Peak
Zone - 223
Peak
Zone - 223
Block
IDC Fan Coil
Peak
IDC Fan Coil
Block
Peak
spc_IDC 102/103/104/109 Int Class_0
Zone - 216
Peak
Zone - 216
Block
spc_IDC 205 Class C_0
Peak
Zone - 217
Peak
Zone - 217
Block
spc_IDC 211/210 Class_0
Peak
Zone - 218
Peak
Zone - 218
Block
spc_IDC 333 Office_0
Peak
Zone - 219
Peak
Zone - 219
Block
IDC VAV
Peak
IDC VAV
Block
spc_LRC 140-01-08 C_0
Peak
Zone - 224
Peak
Zone - 224
Block
spc_LRC 140-09 C_0
Peak
Zone - 225
Peak
Zone - 225
Block
spc_LRC 13-15 C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
633
633
633
228
228
228
42,441
42,441
107
107
107
206
206
206
171
171
171
102
102
102
586
586
3,318
3,318
3,318
460
460
460
1,001
1,001
1,001
414
414
414
5,194
5,194
1,843
1,843
1,843
250
250
250
153
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
10 /15
7 /17
7 /17
7 /16
7 /16
7 /16
7/16
7 /16
7 /16
7 /16
10 /15
10 /15
10 /15
10 /15
10 /15
10 /15
10 /17
10 /17
10 /15
6 /10
6 /10
9 /12
9 /12
9 /11
76
76
76
76
76
76
80
80
75
75
75
76
76
76
76
76
76
76
76
76
76
76
80
80
80
80
80
80
80
80
80
77
77
77
80
80
65
65
65
73
73
73
70
66
66
66
66
66
66
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
63
63
63
63
63
63
64
64
64
63
63
58
58
58
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.1
72.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
395
395
395
53
53
53
41,826
37,423
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,694
1,694
1,694
859
859
859
511
511
511
180
180
180
3,244
3,237
1,595
1,595
1,595
797
797
797
632
6,823
6,823
6,823
911
911
911
727,491
650,911
1,280
1,280
1,280
2,975
2,975
2,975
2,627
2,627
2,627
1,357
1,357
1,357
8,239
8,216
32,706
32,706
32,706
16,577
16,577
16,577
9,869
9,869
9,869
3,472
3,472
3,472
62,624
62,481
28,266
28,266
28,266
14,118
14,118
14,118
11,205
2,216
2,216
2,216
354
354
354
122,518
95,452
284
284
284
722
722
722
600
600
600
357
357
357
1,962
1,958
8,526
8,526
8,526
1,182
1,182
1,182
2,573
2,573
2,573
855
855
855
13,135
12,972
5,957
5,957
5,957
915
915
915
580
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
9 /16
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
7 /16
7 /16
9 /13
9 /13
9 /11
76
76
76
76
76
76
77
77
75
75
75
76
76
76
76
76
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
75
75
75
77
77
76
76
76
75
75
75
70
66
66
66
66
66
66
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
66
66
66
65
65
65
63
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
384
384
384
49
49
49
39,362
36,284
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,668
1,668
1,668
843
843
843
503
503
503
179
179
179
3,194
3,189
1,448
1,448
1,448
757
757
757
632
16,673
16,673
16,673
4,252
4,252
4,252
957,271
890,214
2,183
2,183
2,183
4,555
4,555
4,555
3,950
3,950
3,950
2,128
2,128
2,128
12,817
12,798
38,524
38,524
38,524
19,698
19,698
19,698
11,625
11,625
11,625
10,755
10,755
10,755
80,821
79,588
54,618
54,618
54,618
17,332
17,332
17,332
12,865
3,960
3,960
3,960
448
448
448
249,846
272,391
488
488
488
1,291
1,291
1,291
1,072
1,072
1,072
638
638
638
3,490
3,478
23,156
23,156
23,156
3,209
3,209
3,209
6,987
6,987
6,987
1,894
1,894
1,894
35,247
35,420
12,597
12,597
12,597
1,569
1,569
1,569
880
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 37 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 226
Zone - 226
spc_LRC 16 C_0
Zone - 227
Zone - 227
spc_LRC 17/18_0
Zone - 228
Zone - 228
spc_LRC 5 C (Study?)_0
Zone - 229
Zone - 229
spc_LRC 9 Storage_0
Zone - 230
Zone - 230
spc_LRC 10 Storage_0
Zone - 231
Zone - 231
spc_LRC 7 C_0
Zone - 232
Zone - 232
spc_LRC 8 Stair_0
Zone - 233
Zone - 233
spc_LRC Catalog C_0
Zone - 234
Zone - 234
spc_LRC Computer_0
Zone - 235
Zone - 235
spc_LRC 2/6_0
Zone - 236
Zone - 236
spc_LRC 1st RR C_0
Zone - 237
Zone - 237
spc_LRC 24_0
Zone - 238
Zone - 238
spc_LRC 25_0
Zone - 239
Zone - 239
spc_LRC 105 C Work_0
Zone - 240
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
153
153
66
66
66
94
94
94
57
57
57
29
29
29
24
24
24
119
119
119
302
302
302
56
56
56
525
525
525
137
137
137
226
226
226
564
564
564
325
325
325
62
62
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
10 /13
10 /13
10 /16
10 /16
7 /15
7 /15
7 /15
7 /15
6 /10
6/10
6 /18
6 /18
7 /18
7 /18
7 /18
7 /18
6 /17
6 /17
7 /15
7 /15
10 /16
10/16
10 /16
10 /16
7 /18
7 /18
7 /18
70
70
77
77
77
79
79
79
77
77
77
77
77
77
65
65
65
70
70
70
73
73
73
73
73
73
72
72
72
77
77
77
79
79
79
79
79
79
73
73
73
73
73
63
63
59
59
59
64
64
64
66
66
66
66
66
66
58
58
58
63
63
63
65
65
65
65
65
65
63
63
63
66
66
66
64
64
64
64
64
64
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
632
632
296
296
296
800
800
800
34
34
34
9
9
9
43
43
43
499
499
499
178
178
178
119
119
119
1,809
1,809
1,809
78
78
78
362
362
362
2,024
2,024
2,024
956
956
956
123
123
11,205
11,205
5,239
5,239
5,239
14,180
14,180
14,180
606
606
606
156
156
156
770
770
770
8,836
8,836
8,836
3,148
3,148
3,148
2,112
2,112
2,112
32,061
32,061
32,061
1,384
1,384
1,384
9,633
9,633
9,633
35,871
35,871
35,871
16,939
16,939
16,939
2,178
2,178
580
580
159
159
159
316
316
316
196
196
196
44
44
44
16
16
16
366
366
366
460
460
460
226
226
226
1,210
1,210
1,210
556
556
556
181
181
181
1,890
1,890
1,890
1,302
1,302
1,302
214
214
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /13
9 /13
9 /16
9 /16
9 /16
9 /16
9 /15
9 /15
6 /10
6 /10
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /16
9 /16
7 /18
7 /18
7 /18
70
70
75
75
75
77
77
77
77
77
77
78
78
78
65
65
65
73
73
73
73
73
73
73
73
73
75
75
75
77
77
77
79
79
79
77
77
77
73
73
73
73
73
63
63
65
65
65
67
67
67
67
67
67
66
66
66
58
58
58
65
65
65
65
65
65
65
65
65
66
66
66
67
67
67
64
64
64
67
67
67
65
65
65
65
65
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
632
632
289
289
289
781
781
781
34
34
34
8
8
8
43
43
43
495
495
495
178
178
178
119
119
119
1,791
1,791
1,791
77
77
77
186
186
186
1,981
1,981
1,981
956
956
956
123
123
12,865
12,865
5,989
5,989
5,989
15,724
15,724
15,724
602
602
602
149
149
149
999
999
999
9,606
9,606
9,606
3,388
3,388
3,388
2,494
2,494
2,494
34,140
34,140
34,140
1,369
1,369
1,369
8,860
8,860
8,860
39,177
39,177
39,177
19,463
19,463
19,463
3,446
3,446
Coil
Latent
Load
Btu/h
880
880
417
417
417
710
710
710
392
392
392
63
63
63
19
19
19
757
757
757
592
592
592
392
392
392
2,556
2,556
2,556
1,032
1,032
1,032
996
996
996
4,243
4,243
4,243
2,256
2,256
2,256
397
397
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 38 of 100
SPACE
System Zone Room
Zone - 240
Block
spc_LRC Tables/124B C_0
Peak
Zone - 241
Peak
Zone - 241
Block
spc_LRC 120/122/123 Office C_0 Peak
Zone - 242
Peak
Zone - 242
Block
spc_LRC Tutor Lab C_0
Peak
Zone - 243
Peak
Zone - 243
Block
spc_LRC Lobby/112B Corridor C_0Peak
Zone - 244
Peak
Zone - 244
Block
spc_LRC Dir Offc C_0
Peak
Zone - 245
Peak
Zone - 245
Block
spc_LRC 108/111/115 Counter_0 Peak
Zone - 246
Peak
Zone - 246
Block
spc_LRC 149A_0
Peak
Zone - 247
Peak
Zone - 247
Block
spc_LRC 137 Work C_0
Peak
Zone - 248
Peak
Zone - 248
Block
spc_LRC 140-142 Director_0
Peak
Zone - 249
Peak
Zone - 249
Block
spc_LRC 145 Office C_0
Peak
Zone - 250
Peak
Zone - 250
Block
spc_LRC 146A Storage_0
Peak
Zone - 251
Peak
Zone - 251
Block
spc_LRC 146_0
Peak
Zone - 252
Peak
Zone - 252
Block
spc_LRC Library_0
Peak
Zone - 253
Peak
Zone - 253
Block
spc_LRC 140-14_0
Peak
Zone - 254
Peak
Zone - 254
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
62
647
647
647
58
58
58
63
63
63
582
582
582
36
36
36
335
335
335
25
25
25
59
59
59
38
38
38
23
23
23
14
14
14
80
80
80
0
0
0
42
42
42
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
10 /15
10 /15
6 /11
6 /11
7 /15
7 /15
7 /18
7 /18
6 /18
6 /18
7/15
7 /15
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
10 /13
10 /13
11 /12
11 /12
9 /12
9 /12
73
80
80
80
68
68
68
77
77
77
73
73
73
70
70
70
77
77
77
73
73
73
73
73
73
75
75
75
75
75
75
79
79
79
77
77
77
68
68
68
73
73
73
65
63
63
63
60
60
60
66
66
66
65
65
65
63
63
63
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
64
64
64
59
59
59
55
55
55
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
123
1,184
1,184
1,184
119
119
119
110
110
110
387
387
387
147
147
147
191
191
191
45
45
45
191
191
191
20
20
20
12
12
12
64
64
64
252
252
252
2,551
2,551
2,551
190
190
190
2,178
20,983
20,983
20,983
2,116
2,116
2,116
1,946
1,946
1,946
6,866
6,866
6,866
2,614
2,614
2,614
3,378
3,378
3,378
793
793
793
3,381
3,381
3,381
359
359
359
214
214
214
1,140
1,140
1,140
4,464
4,464
4,464
45,210
45,210
45,210
3,371
3,371
3,371
214
1,652
1,652
1,652
103
103
103
180
180
180
975
975
975
72
72
72
1,358
1,358
1,358
86
86
86
204
204
204
101
101
101
60
60
60
11
11
11
192
192
192
0
0
0
154
154
154
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /18
9 /16
9 /16
7 /12
7 /12
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
9 /14
9 /14
9 /11
9 /11
9 /12
9 /12
73
77
77
77
73
73
73
76
76
76
75
75
75
73
73
73
76
76
76
73
73
73
73
73
73
75
75
75
75
75
75
76
76
76
77
77
77
70
70
70
73
73
73
65
67
67
67
63
63
63
66
66
66
66
66
66
65
65
65
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
67
67
67
66
66
66
63
63
63
63
63
63
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
123
1,113
1,113
1,113
117
117
117
110
110
110
364
364
364
145
145
145
190
190
190
45
45
45
191
191
191
20
20
20
12
12
12
63
63
63
233
233
233
2,488
2,488
2,488
190
190
190
3,446
32,086
32,086
32,086
2,850
2,850
2,850
2,980
2,980
2,980
14,670
14,670
14,670
3,509
3,509
3,509
8,372
8,372
8,372
1,278
1,278
1,278
4,731
4,731
4,731
936
936
936
559
559
559
1,612
1,612
1,612
5,818
5,818
5,818
47,040
47,040
47,040
4,151
4,151
4,151
Coil
Latent
Load
Btu/h
397
4,480
4,480
4,480
178
178
178
312
312
312
1,365
1,365
1,365
155
155
155
2,288
2,288
2,288
159
159
159
378
378
378
174
174
174
104
104
104
35
35
35
535
535
535
0
0
0
223
223
223
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 39 of 100
SPACE
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
System Zone Room
Floor
Area
ft²
spc_LRC 140-03_0
Peak
Zone - 255
Peak
Zone - 255
Block
spc_LRC 101 Work C_0
Peak
Zone - 256
Peak
Zone - 256
Block
spc_LRC 108-110 Storage_0
Peak
Zone - 257
Peak
Zone - 257
Block
spc_LRC 109 Work_0
Peak
Zone - 258
Peak
Zone - 258
Block
LRC VAV
Peak
LRC VAV
Block
spc_OE 10WM Restrooms AH-2_0Peak
Zone - 259
Peak
Zone - 259
Block
spc_OE 112 Class C_0
Peak
Zone - 260
Peak
Zone - 260
Block
spc_OE 116 Class C_0
Peak
Zone - 261
Peak
Zone - 261
Block
spc_OE 180H/182 Class C_0
Peak
Zone - 262
Peak
Zone - 262
Block
spc_OE 180A Office C_0
Peak
Zone - 263
Peak
Zone - 263
Block
OE Pckg AH
Peak
OE Pckg AH
Block
spc_PE 108 Weight Rm HP3/4_0 Peak
Zone - 006
Peak
Zone - 006
Block
spc_PE Locker/RR HP-06/07_0 Peak
Zone - 008
Peak
Zone - 008
Block
Peak
spc_PE 302-310E Office Partially C_0
Zone - 011
Peak
Zone - 011
Block
PE Heat Pump
Peak
PE Heat Pump
Block
spc_PE Gym AH1_0
Peak
86
6 /10
86
86
6 /10
62
9 /17
62
62
9 /17
24
7 /15
24
24
7 /15
43
9 /17
43
43
9 /17
7,052
7,052
9 /16
172
7 /18
172
172
7/18
522 10 /15
522
522 10 /15
1,121 7 /18
1,121
1,121 7 /18
509
9 /11
509
509
9 /11
66
7 /17
66
66
7 /17
2,391
2,391 10 /14
3,594 9 /10
3,594
3,594 9 /10
1,968 7 /18
1,968
1,968 7 /18
498
7 /18
498
498
7 /18
6,061
6,061
7 /18
7,524
7 /17
Project Name:
Dataset Name:
SBCC TRACE.TRC
65
65
65
76
76
76
77
77
77
76
76
76
77
77
73
73
73
80
80
80
73
73
73
70
70
70
75
75
75
79
79
67
67
67
73
73
73
73
73
73
73
73
75
58
58
58
67
67
67
66
66
66
67
67
67
67
67
65
65
65
63
63
63
65
65
65
63
63
63
66
66
66
62
62
61
61
61
65
65
65
65
65
65
65
65
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.2
72.2
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.7
72.7
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
76.0
76.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
73.2
73.2
73.2
56.6
56.6
56.6
52.2
52.2
52.2
55.6
55.6
55.6
48.8
48.8
48.8
56.4
56.4
54.5
54.5
54.5
74.3
74.3
74.3
56.3
56.3
56.3
64.7
64.7
72.4
207
207
207
186
186
186
7
7
7
143
143
143
16,361
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
3,150
3,150
1,009
1,009
1,009
6,278
6,278
1,505
3,672
3,672
3,672
3,302
3,302
3,302
123
123
123
2,540
2,540
2,540
293,173
232,240
2,089
2,089
2,089
17,559
17,559
17,559
20,357
20,357
20,357
17,712
17,712
17,712
589
589
589
58,307
44,634
41,395
41,395
41,395
19,874
19,874
19,874
17,669
17,669
17,669
78,937
60,043
-636
277
277
277
218
218
218
36
36
36
152
152
152
20,421
25,647
59
59
59
1,340
1,340
1,340
3,874
3,874
3,874
1,628
1,628
1,628
176
176
176
7,077
4,708
4,036
4,036
4,036
668
668
668
1,173
1,173
1,173
5,877
7,430
-4,539
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
9 /17
9 /17
7 /16
7 /16
9 /17
9 /17
9 /16
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
9 /13
9 /13
7 /17
7 /17
9 /16
9 /13
9 /13
9 /17
9 /17
7 /18
7 /18
9 /17
7 /14
75
75
75
76
76
76
76
76
76
76
76
76
77
77
76
76
76
77
77
77
73
73
73
75
75
75
75
75
75
77
77
75
75
75
76
76
76
73
73
73
76
76
76
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
66
67
67
65
65
65
67
67
67
65
65
65
67
67
65
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
76.2
76.2
76.2
57.4
57.4
57.4
52.2
52.2
52.2
57.4
57.4
57.4
48.8
48.8
48.8
57.5
60.7
57.2
57.2
57.2
75.4
75.4
75.4
56.3
56.3
56.3
66.2
68.1
72.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
164
164
164
186
186
186
7
7
7
143
143
143
15,679
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
3,150
3,150
1,009
1,009
1,009
6,278
6,278
451
4,618
4,618
4,618
4,899
4,899
4,899
475
475
475
3,755
3,755
3,755
382,332
328,402
2,439
2,439
2,439
21,294
21,294
21,294
23,315
23,315
23,315
22,689
22,689
22,689
1,667
1,667
1,667
71,405
61,879
36,526
36,526
36,526
36,640
36,640
36,640
27,335
27,335
27,335
100,501
80,404
-191
Coil
Latent
Load
Btu/h
569
569
569
432
432
432
50
50
50
300
300
300
41,604
50,410
755
755
755
3,639
3,639
3,639
7,205
7,205
7,205
2,921
2,921
2,921
304
304
304
14,824
15,804
19,890
19,890
19,890
8,557
8,557
8,557
2,160
2,160
2,160
30,607
29,879
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 40 of 100
SPACE
System Zone Room
Zone - 001
Peak
Zone - 001
Block
spc_PE Team Lockey RH4_0
Peak
Zone - 002
Peak
Zone - 002
Block
spc_PE 113 RH7/RH8_0
Peak
Zone - 003
Peak
Zone - 003
Block
spc_PE 114 C_0
Peak
Zone - 004
Peak
Zone - 004
Block
spc_PE 109 NC_0
Peak
Zone - 005
Peak
Zone - 005
Block
spc_PE 2nd Flr Lobby_0
Peak
Zone - 007
Peak
Zone - 007
Block
Peak
spc_PE 214-218, 201-203 Offices C_0
Zone - 009
Peak
Zone - 009
Block
spc_PE 3 Press Box RH02 _0
Peak
Zone - 010
Peak
Zone - 010
Block
PE VAV Htg Only
Peak
PE VAV Htg Only
Block
spc_sp_55
Peak
Zone - 264
Peak
Zone - 264
Block
spc_sp_56
Peak
Zone - 265
Peak
Zone - 265
Block
spc_sp_57
Peak
Zone - 266
Peak
Zone - 266
Block
spc_sp_58
Peak
Zone - 267
Peak
Zone - 267
Block
spc_sp_59
Peak
Zone - 268
Peak
Zone - 268
Block
spc_sp_60
Peak
Zone - 269
Peak
Zone - 269
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
7,524
7,524
744
744
744
1,696
1,696
1,696
1,001
1,001
1,001
683
683
683
7,013
7,013
7,013
1,922
1,922
1,922
174
174
174
20,757
20,757
1,130
1,130
1,130
1,130
1,130
1,130
1,159
1,159
1,159
1,087
1,087
1,087
396
396
396
828
828
828
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
10 /16
10 /16
9 /16
9 /16
9 /10
9 /10
10 /15
10 /15
7 /10
7 /10
7/18
7 /18
10 /16
10 /16
7 /17
10 /13
10 /13
10 /15
10 /15
9 /12
9 /12
10 /16
10 /16
11 /15
11 /15
7 /18
7 /18
75
75
79
79
79
77
77
77
67
67
67
80
80
80
67
67
67
73
73
73
79
79
79
75
75
77
77
77
80
80
80
73
73
73
79
79
79
73
73
73
73
73
73
66
66
64
64
64
67
67
67
61
61
61
63
63
63
60
60
60
65
65
65
64
64
64
66
66
59
59
59
63
63
63
63
63
63
64
64
64
62
62
62
65
65
65
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
74.4
74.4
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
58.6
58.6
58.6
55.9
55.9
55.9
54.6
54.6
54.6
56.3
56.3
56.3
58.2
58.2
58.2
54.7
54.7
54.7
1,505
1,505
1,190
1,190
1,190
339
339
339
200
200
200
137
137
137
351
351
351
256
256
256
23
23
23
4,001
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
-636
-636
10,111
10,111
10,111
-143
-143
-143
-85
-85
-85
-58
-58
-58
-148
-148
-148
-108
-108
-108
-10
-10
-10
8,923
0
25,370
25,370
25,370
30,201
30,201
30,201
29,008
29,008
29,008
37,550
37,550
37,550
33,464
33,464
33,464
25,783
25,783
25,783
-4,539
-4,539
-971
-971
-971
2,691
2,691
2,691
1,039
1,039
1,039
306
306
306
-8,532
-8,532
-8,532
454
454
454
-45
-45
-45
-9,597
-3,178
2,062
2,062
2,062
2,910
2,910
2,910
3,573
3,573
3,573
3,013
3,013
3,013
1,051
1,051
1,051
2,864
2,864
2,864
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /14
9 /16
9 /16
9 /16
9 /16
9 /10
9 /10
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
7 /17
9 /14
9 /14
9 /16
9 /16
9 /14
9 /14
9 /16
9 /16
10 /15
10 /15
7 /18
7 /18
76
76
77
77
77
77
77
77
67
67
67
77
77
77
75
75
75
75
75
75
76
76
76
75
75
77
77
77
77
77
77
77
77
77
77
77
77
80
80
80
73
73
73
65
65
67
67
67
67
67
67
61
61
61
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
67
67
67
66
66
66
67
67
67
63
63
63
65
65
65
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
59.2
59.2
59.2
56.9
56.9
56.9
55.6
55.6
55.6
56.5
56.5
56.5
58.3
58.3
58.3
54.7
54.7
54.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
451
451
357
357
357
102
102
102
60
60
60
41
41
41
105
105
105
77
77
77
7
7
7
1,200
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
-191
-191
3,033
3,033
3,033
-43
-43
-43
-25
-25
-25
-17
-17
-17
-44
-44
-44
-32
-32
-32
-3
-3
-3
12,882
0
36,547
36,547
36,547
44,525
44,525
44,525
40,050
40,050
40,050
54,574
54,574
54,574
40,936
40,936
40,936
38,829
38,829
38,829
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6,959
6,959
6,959
7,908
7,908
7,908
7,147
7,147
7,147
7,605
7,605
7,605
1,195
1,195
1,195
5,336
5,336
5,336
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 41 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_61
Zone - 270
Zone - 270
spc_sp_62
Zone - 271
Zone - 271
spc_sp_63
Zone - 272
Zone - 272
spc_sp_64
Zone - 273
Zone - 273
spc_sp_65
Zone - 274
Zone - 274
spc_sp_66
Zone - 275
Zone - 275
spc_sp_67
Zone - 276
Zone - 276
spc_sp_68
Zone - 277
Zone - 277
spc_sp_69
Zone - 278
Zone - 278
spc_sp_70
Zone - 279
Zone - 279
spc_sp_38
Zone - 280
Zone - 280
spc_sp_39
Zone - 281
Zone - 281
spc_sp_40
Zone - 282
Zone - 282
spc_sp_41
Zone - 283
Zone - 283
spc_sp_42
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
378
9 /11
378
378
9 /11
485
6 /10
485
485
6 /10
678 10 /16
678
678 10 /16
822
7 /18
822
822
7 /18
628
9 /11
628
628
9 /11
2,082 9 /16
2,082
2,082 9 /16
2,169 7 /17
2,169
2,169 7 /17
2,777 7 /17
2,777
2,777 7 /17
3,084 7 /17
3,084
3,084 7 /17
211
6 /10
211
211
6 /10
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
1,408 9 /16
1,408
1,408 9 /16
1,392 9 /16
1,392
1,392
9 /16
972
9 /16
70
70
70
65
65
65
79
79
79
73
73
73
70
70
70
77
77
77
75
75
75
75
75
75
75
75
75
65
65
65
77
77
77
77
77
77
77
77
77
77
77
77
77
63
63
63
58
58
58
64
64
64
65
65
65
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.5
57.5
57.5
55.5
55.5
55.5
56.3
56.3
56.3
51.4
51.4
51.4
56.1
56.1
56.1
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.5
52.5
52.5
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
28,760
28,760
28,760
11,994
11,994
11,994
23,923
23,923
23,923
13,067
13,067
13,067
26,223
26,223
26,223
53,398
53,398
53,398
48,975
48,975
48,975
57,415
57,415
57,415
55,454
55,454
55,454
13,285
13,285
13,285
28,858
28,858
28,858
28,858
28,858
28,858
35,056
35,056
35,056
34,765
34,765
34,765
27,232
1,212
1,212
1,212
1,286
1,286
1,286
1,878
1,878
1,878
2,838
2,838
2,838
2,011
2,011
2,011
7,723
7,723
7,723
7,128
7,128
7,128
9,122
9,122
9,122
10,121
10,121
10,121
559
559
559
3,036
3,036
3,036
3,036
3,036
3,036
5,223
5,223
5,223
5,163
5,163
5,163
3,608
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
9 /12
9 /12
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
70
70
70
76
76
76
77
77
77
75
75
75
73
73
73
77
77
77
75
75
75
75
75
75
76
76
76
65
65
65
77
77
77
77
77
77
77
77
77
77
77
77
77
63
63
63
66
66
66
67
67
67
66
66
66
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
57.5
57.5
57.5
58.6
58.6
58.6
56.4
56.4
56.4
51.9
51.9
51.9
56.2
56.2
56.2
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.7
52.7
52.7
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
32,826
32,826
32,826
16,489
16,489
16,489
33,562
33,562
33,562
23,710
23,710
23,710
32,978
32,978
32,978
80,411
80,411
80,411
79,136
79,136
79,136
95,193
95,193
95,193
95,526
95,526
95,526
14,677
14,677
14,677
41,068
41,068
41,068
41,068
41,068
41,068
53,076
53,076
53,076
52,584
52,584
52,584
39,863
Coil
Latent
Load
Btu/h
1,973
1,973
1,973
3,057
3,057
3,057
4,742
4,742
4,742
5,052
5,052
5,052
3,012
3,012
3,012
14,541
14,541
14,541
13,382
13,382
13,382
17,116
17,116
17,116
19,369
19,369
19,369
694
694
694
5,720
5,720
5,720
5,720
5,720
5,720
9,832
9,832
9,832
9,719
9,719
9,719
6,796
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 42 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 284
Zone - 284
spc_sp_43
Zone - 285
Zone - 285
spc_sp_44
Zone - 286
Zone - 286
spc_sp_45
Zone - 287
Zone - 287
spc_sp_46
Zone - 288
Zone - 288
spc_sp_47
Zone - 289
Zone - 289
spc_sp_48
Zone - 290
Zone - 290
spc_sp_49
Zone - 291
Zone - 291
spc_sp_50
Zone - 292
Zone - 292
spc_sp_51
Zone - 293
Zone - 293
spc_sp_52
Zone - 294
Zone - 294
spc_sp_53
Zone - 295
Zone - 295
spc_sp_54
Zone - 296
Zone - 296
spc_sp_22
Zone - 297
Zone - 297
spc_sp_23
Zone - 298
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
972
972
1,408
1,408
1,408
826
826
826
914
914
914
907
907
907
869
869
869
869
869
869
835
835
835
893
893
893
737
737
737
1,061
1,061
1,061
1,064
1,064
1,064
1,061
1,061
1,061
1,044
1,044
1,044
1,082
1,082
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /15
9 /16
9 /16
9 /16
9 /16
7 /18
7 /18
7 /18
7/18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
10 /13
10 /13
10 /13
10 /13
9 /12
9 /12
7 /18
7 /18
7 /18
77
77
80
80
80
77
77
77
77
77
77
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
77
77
77
77
77
77
73
73
73
73
73
73
73
73
67
67
63
63
63
67
67
67
67
67
67
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
59
59
59
59
59
59
63
63
63
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.0
54.0
56.0
56.0
56.0
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
53.9
53.9
53.9
54.1
54.1
54.1
54.2
54.2
54.2
54.0
54.0
54.0
55.0
55.0
55.0
58.7
58.7
58.7
58.7
58.7
58.7
54.7
54.7
54.7
53.1
53.1
53.1
53.4
53.4
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
27,232
27,232
38,302
38,302
38,302
27,994
27,994
27,994
26,885
26,885
26,885
25,235
25,235
25,235
22,064
22,064
22,064
22,983
22,983
22,983
22,536
22,536
22,536
23,576
23,576
23,576
24,944
24,944
24,944
24,323
24,323
24,323
24,374
24,374
24,374
27,301
27,301
27,301
22,248
22,248
22,248
24,586
24,586
3,608
3,608
3,626
3,626
3,626
3,067
3,067
3,067
3,393
3,393
3,393
3,140
3,140
3,140
3,008
3,008
3,008
3,009
3,009
3,009
2,891
2,891
2,891
3,092
3,092
3,092
2,553
2,553
2,553
1,935
1,935
1,935
1,941
1,941
1,941
3,272
3,272
3,272
3,609
3,609
3,609
3,741
3,741
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
9 /14
9 /14
9 /14
9 /14
9 /14
9 /14
7 /17
7 /17
7 /17
77
77
77
77
77
77
77
77
77
77
77
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
77
77
77
77
77
77
77
77
77
75
75
75
75
75
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
54.0
54.0
56.2
56.2
56.2
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
54.1
54.1
54.1
54.2
54.2
54.2
54.3
54.3
54.3
54.2
54.2
54.2
55.0
55.0
55.0
59.2
59.2
59.2
59.2
59.2
59.2
55.7
55.7
55.7
53.6
53.6
53.6
53.6
53.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
39,863
39,863
56,744
56,744
56,744
39,442
39,442
39,442
38,892
38,892
38,892
38,103
38,103
38,103
33,592
33,592
33,592
34,897
34,897
34,897
34,003
34,003
34,003
35,816
35,816
35,816
36,470
36,470
36,470
34,741
34,741
34,741
34,831
34,831
34,831
37,314
37,314
37,314
35,254
35,254
35,254
38,640
38,640
Coil
Latent
Load
Btu/h
6,796
6,796
9,854
9,854
9,854
5,777
5,777
5,777
6,391
6,391
6,391
5,604
5,604
5,604
5,367
5,367
5,367
5,370
5,370
5,370
5,157
5,157
5,157
5,519
5,519
5,519
4,557
4,557
4,557
6,531
6,531
6,531
6,553
6,553
6,553
6,544
6,544
6,544
6,433
6,433
6,433
6,671
6,671
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 43 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 298
spc_sp_24
Zone - 299
Zone - 299
spc_sp_25
Zone - 300
Zone - 300
spc_sp_26
Zone - 301
Zone - 301
spc_sp_27
Zone - 302
Zone - 302
spc_sp_28
Zone - 303
Zone - 303
spc_sp_29
Zone - 304
Zone - 304
spc_sp_30
Zone - 305
Zone - 305
spc_sp_31
Zone - 306
Zone - 306
spc_sp_32
Zone - 307
Zone - 307
spc_sp_33
Zone - 308
Zone - 308
spc_sp_34
Zone - 309
Zone - 309
spc_sp_35
Zone - 310
Zone - 310
spc_sp_36
Zone - 311
Zone - 311
spc_sp_37
Zone - 312
Zone - 312
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
1,082
7 /18
1,074
7 /18
1,074
1,074
7 /18
955
7 /18
955
955
7 /18
995
9 /16
995
995
9 /16
894
7 /17
894
894
7 /17
1,063 10 /15
1,063
1,063 10 /15
684
6/10
684
684
6 /10
2,070 9 /16
2,070
2,070 9 /16
1,251 9 /16
1,251
1,251 9 /16
1,251 7 /17
1,251
1,251 7 /17
1,525 9 /16
1,525
1,525 9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
73
73
73
73
73
73
73
77
77
77
75
75
75
80
80
80
65
65
65
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
65
65
65
65
65
65
65
67
67
67
66
66
66
63
63
63
58
58
58
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
53.4
53.1
53.1
53.1
53.6
53.6
53.6
55.1
55.1
55.1
55.0
55.0
55.0
56.6
56.6
56.6
55.8
55.8
55.8
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
24,586
22,945
22,945
22,945
22,834
22,834
22,834
37,026
37,026
37,026
29,118
29,118
29,118
36,090
36,090
36,090
18,202
18,202
18,202
52,942
52,942
52,942
35,189
35,189
35,189
31,103
31,103
31,103
60,677
60,677
60,677
29,082
29,082
29,082
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
3,741
3,711
3,711
3,711
3,304
3,304
3,304
3,697
3,697
3,697
2,943
2,943
2,943
2,737
2,737
2,737
1,813
1,813
1,813
7,679
7,679
7,679
4,645
4,645
4,645
4,115
4,115
4,115
5,660
5,660
5,660
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
75
75
75
75
75
75
75
77
77
77
75
75
75
77
77
77
76
76
76
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
66
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
53.6
53.6
53.6
53.6
53.9
53.9
53.9
55.1
55.1
55.1
55.0
55.0
55.0
56.7
56.7
56.7
60.6
60.6
60.6
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
38,640
36,369
36,369
36,369
35,270
35,270
35,270
51,628
51,628
51,628
42,996
42,996
42,996
51,414
51,414
51,414
22,226
22,226
22,226
79,873
79,873
79,873
52,725
52,725
52,725
48,027
48,027
48,027
82,120
82,120
82,120
41,372
41,372
41,372
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
Coil
Latent
Load
Btu/h
6,671
6,615
6,615
6,615
5,894
5,894
5,894
6,966
6,966
6,966
5,530
5,530
5,530
7,439
7,439
7,439
4,311
4,311
4,311
14,458
14,458
14,458
8,749
8,749
8,749
7,730
7,730
7,730
10,664
10,664
10,664
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 44 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_7
Zone - 313
Zone - 313
spc_sp_8
Zone - 314
Zone - 314
spc_sp_9
Zone - 315
Zone - 315
spc_sp_10
Zone - 316
Zone - 316
spc_sp_11
Zone - 317
Zone - 317
spc_sp_12
Zone - 318
Zone - 318
spc_sp_13
Zone - 319
Zone - 319
spc_sp_14
Zone - 320
Zone - 320
spc_sp_15
Zone - 321
Zone - 321
spc_sp_16
Zone - 322
Zone - 322
spc_sp_17
Zone - 323
Zone - 323
spc_sp_18
Zone - 324
Zone - 324
spc_sp_19
Zone - 325
Zone - 325
spc_sp_20
Zone - 326
Zone - 326
spc_sp_21
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
290
290
290
442
442
442
2,070
2,070
2,070
1,103
1,103
1,103
915
915
915
3,084
3,084
3,084
437
437
437
344
344
344
231
231
231
382
382
382
358
358
358
1,082
1,082
1,082
960
960
960
1,040
1,040
1,040
1,040
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
6 /18
6 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
6 /18
6 /18
7 /18
7 /18
9 /12
9 /12
6 /10
6 /10
6 /9
6 /9
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
70
70
70
70
70
70
75
75
75
76
76
76
76
76
76
75
75
75
70
70
70
73
73
73
73
73
73
65
65
65
62
62
62
73
73
73
73
73
73
73
73
73
73
63
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
65
65
65
63
63
63
58
58
58
58
58
58
65
65
65
65
65
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.0
57.0
57.0
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
56.2
56.2
56.2
56.0
56.0
56.0
53.0
53.0
53.0
53.2
53.2
53.2
54.2
54.2
54.2
53.1
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
17,557
17,557
17,557
19,208
19,208
19,208
47,533
47,533
47,533
12,788
12,788
12,788
10,607
10,607
10,607
60,225
60,225
60,225
28,451
28,451
28,451
19,387
19,387
19,387
8,323
8,323
8,323
11,887
11,887
11,887
10,175
10,175
10,175
22,813
22,813
22,813
20,987
20,987
20,987
28,726
28,726
28,726
22,182
929
929
929
1,375
1,375
1,375
6,804
6,804
6,804
3,865
3,865
3,865
3,206
3,206
3,206
10,127
10,127
10,127
1,358
1,358
1,358
1,192
1,192
1,192
713
713
713
1,013
1,013
1,013
951
951
951
3,739
3,739
3,739
3,318
3,318
3,318
3,598
3,598
3,598
3,594
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /12
9 /12
7 /18
7 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /12
9 /12
7 /15
7 /15
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
73
73
73
73
73
73
75
75
75
76
76
76
76
76
76
75
75
75
73
73
73
73
73
73
73
73
73
77
77
77
76
76
76
75
75
75
75
75
75
75
75
75
75
63
63
63
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
57.6
57.6
57.6
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
60.1
60.1
60.1
57.9
57.9
57.9
53.5
53.5
53.5
53.7
53.7
53.7
54.4
54.4
54.4
53.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
20,529
20,529
20,529
26,244
26,244
26,244
76,434
76,434
76,434
26,279
26,279
26,279
21,797
21,797
21,797
101,628
101,628
101,628
36,070
36,070
36,070
25,678
25,678
25,678
11,070
11,070
11,070
14,327
14,327
14,327
14,201
14,201
14,201
36,302
36,302
36,302
32,911
32,911
32,911
43,793
43,793
43,793
35,131
Coil
Latent
Load
Btu/h
1,393
1,393
1,393
2,856
2,856
2,856
12,774
12,774
12,774
6,912
6,912
6,912
5,733
5,733
5,733
18,995
18,995
18,995
2,820
2,820
2,820
2,221
2,221
2,221
1,110
1,110
1,110
2,357
2,357
2,357
2,261
2,261
2,261
6,665
6,665
6,665
5,915
5,915
5,915
6,420
6,420
6,420
6,406
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 45 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 327
Zone - 327
spc_sp_1
Zone - 328
Zone - 328
spc_sp_2
Zone - 329
Zone - 329
spc_sp_3
Zone - 330
Zone - 330
spc_sp_4
Zone - 331
Zone - 331
spc_sp_5
Zone - 332
Zone - 332
spc_sp_6
Zone - 333
Zone - 333
Child Cntr 2
Zone - 359
Zone - 359
Child Cntr 3
Zone - 360
Zone - 360
Child Cntr 1
Zone - 361
Zone - 361
Portopia HP
Portopia HP
spc_SS 141/142 Office_0
Zone - 012
Zone - 012
spc_SS 144 Office C_0
Zone - 013
Zone - 013
spc_SS 160B-D_0
Zone - 014
Zone - 014
spc_PS 160A Storage_0
Zone - 015
Zone - 015
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,040
1,040
1,272
1,272
1,272
1,074
1,074
1,074
999
999
999
1,613
1,613
1,613
664
664
664
1,956
1,956
1,956
211
211
211
211
211
211
211
211
211
75,038
75,038
313
313
313
168
168
168
0
0
0
102
102
102
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
10 /15
10 /15
10 /16
10 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
6 /9
10 /15
10 /15
9 /11
9 /11
73
73
77
77
77
73
73
73
73
73
73
80
80
80
79
79
79
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
62
62
80
80
80
70
70
70
65
65
67
67
67
65
65
65
65
65
65
63
63
63
64
64
64
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
58
58
63
63
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Supply
Dry
Bulb
°F
53.1
53.1
48.6
48.6
48.6
53.1
53.1
53.1
54.3
54.3
54.3
55.5
55.5
55.5
57.1
57.1
57.1
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
54.9
54.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
32
32
0
0
0
27
27
27
22,182
22,182
15,648
15,648
15,648
22,945
22,945
22,945
28,019
28,019
28,019
37,433
37,433
37,433
31,843
31,843
31,843
22,688
22,688
22,688
13,285
13,285
13,285
13,285
13,285
13,285
12,931
12,931
12,931
2,026,697
1,809,600
0
0
0
0
0
0
0
0
0
0
0
0
3,594
3,594
4,707
4,707
4,707
3,711
3,711
3,711
3,457
3,457
3,457
4,151
4,151
4,151
1,840
1,840
1,840
6,857
6,857
6,857
559
559
559
559
559
559
370
370
370
246,137
246,507
181
181
181
97
97
97
0
0
0
-2
-2
-2
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
6 /9
9 /16
9 /16
9 /11
9 /11
75
75
76
76
76
75
75
75
75
75
75
77
77
77
77
77
77
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
62
62
77
77
77
70
70
70
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
58
58
67
67
67
63
63
63
53.6
53.6
48.8
48.8
48.8
53.6
53.6
53.6
54.5
54.5
54.5
56.4
56.4
56.4
57.3
57.3
57.3
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
55.1
56.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Coil
Airflow
cfm
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
32
32
0
0
0
27
27
27
Coil
Sensible
Load
Btu/h
35,131
35,131
31,358
31,358
31,358
36,369
36,369
36,369
42,495
42,495
42,495
56,782
56,782
56,782
43,282
43,282
43,282
46,620
46,620
46,620
14,677
14,677
14,677
14,677
14,677
14,677
14,524
14,524
14,524
3,006,774
2,862,181
0
0
0
0
0
0
0
0
0
0
0
0
Coil
Latent
Load
Btu/h
6,406
6,406
7,970
7,970
7,970
6,615
6,615
6,615
6,169
6,169
6,169
11,281
11,281
11,281
4,645
4,645
4,645
12,262
12,262
12,262
694
694
694
694
694
694
460
460
460
480,065
462,701
0
0
0
0
0
0
0
0
0
0
0
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 46 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_SS 160 Class C_0
Zone - 016
Zone - 016
spc_SS 162 Class_0
Zone - 017
Zone - 017
spc_PS 112 Office C_0
Zone - 018
Zone - 018
spc_PS 111-115 Office C_0
Zone - 019
Zone - 019
spc_PS Lecture 117 C_0
Zone - 020
Zone - 020
spc_PS Lecture FC-4C_0
Zone - 021
Zone - 021
spc_PS 120-128 Class_0
Zone - 022
Zone - 022
spc_PS Class 121/122_0
Zone - 023
Zone - 023
spc_PS 130 Auditorium C_0
Zone - 024
Zone - 024
PS Fan Coil Htg Only
PS Fan Coil Htg Only
spc_SS 171-173, 178 Office C_0
Zone - 037
Zone - 037
spc_SS 135 Office_0
Zone - 038
Zone - 038
spc_SS Corridor 120 C_0
Zone - 039
Zone - 039
spc_SS 180 Worm Rm VAV-20_0
Zone - 040
Zone - 040
spc_SS 110C Wrk Rm C_0
Zone - 041
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
565
565
565
967
967
967
215
215
215
602
602
602
1,126
1,126
1,126
1,036
1,036
1,036
886
886
886
695
695
695
1,413
1,413
1,413
8,090
8,090
561
561
561
92
92
92
1,787
1,787
1,787
326
326
326
766
766
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
10 /16
10 /16
9 /17
9 /17
7 /18
7 /18
6 /9
6 /9
7 /16
7 /16
10 /16
10 /16
10 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
6 /9
70
70
70
70
70
70
79
79
79
79
79
79
76
76
76
73
73
73
62
62
62
76
76
76
79
79
79
79
79
76
76
76
76
76
76
76
76
76
79
79
79
62
62
63
63
63
63
63
63
64
64
64
64
64
64
67
67
67
65
65
65
58
58
58
66
66
66
64
64
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
274
274
274
45
45
45
378
378
378
616
616
616
1,984
1,984
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,317
5,317
5,317
875
875
875
7,342
7,342
7,342
11,961
11,961
11,961
38,530
38,530
836
836
836
1,430
1,430
1,430
157
157
157
435
435
435
1,356
1,356
1,356
1,374
1,374
1,374
1,392
1,392
1,392
992
992
992
2,191
2,191
2,191
10,439
7,971
1,465
1,465
1,465
241
241
241
2,794
2,794
2,794
902
902
902
2,030
2,030
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
7 /18
7 /18
7 /9
7 /9
7 /16
7 /16
9 /16
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
7 /10
70
70
70
70
70
70
79
79
79
76
76
76
76
76
76
73
73
73
64
64
64
76
76
76
77
77
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
67
67
63
63
63
63
63
63
64
64
64
67
67
67
67
67
67
65
65
65
59
59
59
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
60
60
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
268
268
268
44
44
44
364
364
364
593
593
593
1,874
1,874
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,089
5,089
5,089
838
838
838
5,425
5,425
5,425
13,863
13,863
13,863
40,338
40,338
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2,917
2,917
2,917
480
480
480
4,022
4,022
4,022
2,276
2,276
2,276
2,929
2,929
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 47 of 100
SPACE
System Zone Room
Zone - 041
Block
spc_SS 110 Wrk Rm/Office C_0 Peak
Zone - 042
Peak
Zone - 042
Block
Peak
spc_SS 100 100H 111H Main Lobby
C_0
Zone - 043
Peak
Zone - 043
Block
spc_SS 150 Wrk Rm C_0
Peak
Zone - 044
Peak
Zone - 044
Block
spc_SS 177-179 Office_0
Peak
Zone - 045
Peak
Zone - 045
Block
spc_SS Wrk Rm1 V-19_0
Peak
Zone - 046
Peak
Zone - 046
Block
spc_SS 120-124 C_0
Peak
Zone - 047
Peak
Zone - 047
Block
spc_SS 135-139 Office C_0
Peak
Zone - 048
Peak
Zone - 048
Block
spc_SS 140 Wrk Rm C_0
Peak
Zone - 049
Peak
Zone - 049
Block
spc_SS 125-129_0
Peak
Zone - 050
Peak
Zone - 050
Block
spc_SS 230B Office C_0
Peak
Zone - 051
Peak
Zone - 051
Block
spc_SS 214 Office C_0
Peak
Zone - 052
Peak
Zone - 052
Block
spc_SS 282 Wrk Rm C_0
Peak
Zone - 053
Peak
Zone - 053
Block
spc_SS 280D Office_0
Peak
Zone - 054
Peak
Zone - 054
Block
spc_SS 280A-C C_0
Peak
Zone - 055
Peak
Zone - 055
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
766
1,420
1,420
1,420
37
37
37
301
301
301
635
635
635
207
207
207
703
703
703
586
586
586
848
848
848
642
642
642
285
285
285
130
130
130
136
136
136
154
154
154
459
459
459
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /9
9 /17
9 /17
7 /18
7 /18
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
6/9
6 /9
7 /16
7 /16
9 /16
9 /16
6 /18
6 /18
6 /18
6 /18
10 /16
10 /16
10 /16
10 /16
7 /17
7 /17
9 /11
9 /11
62
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
62
62
62
76
76
76
77
77
77
70
70
70
70
70
70
79
79
79
79
79
79
75
75
75
70
70
70
58
67
67
67
65
65
65
66
66
66
66
66
66
66
66
66
58
58
58
66
66
66
67
67
67
63
63
63
63
63
63
64
64
64
64
64
64
66
66
66
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,984
844
844
844
348
348
348
167
167
167
310
310
310
115
115
115
1,253
1,253
1,253
286
286
286
545
545
545
1,766
1,766
1,766
526
526
526
623
623
623
1,441
1,441
1,441
75
75
75
1,255
1,255
1,255
38,530
16,389
16,389
16,389
6,755
6,755
6,755
3,248
3,248
3,248
6,019
6,019
6,019
2,238
2,238
2,238
24,336
24,336
24,336
5,555
5,555
5,555
10,576
10,576
10,576
34,294
34,294
34,294
10,214
10,214
10,214
12,096
12,096
12,096
27,981
27,981
27,981
1,450
1,450
1,450
24,365
24,365
24,365
2,030
4,101
4,101
4,101
63
63
63
1,044
1,044
1,044
1,658
1,658
1,658
719
719
719
1,862
1,862
1,862
1,530
1,530
1,530
3,146
3,146
3,146
1,992
1,992
1,992
572
572
572
244
244
244
378
378
378
408
408
408
1,469
1,469
1,469
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /10
9 /17
9 /17
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /10
7 /10
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /11
9 /11
67
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
67
67
67
76
76
76
77
77
77
73
73
73
73
73
73
77
77
77
77
77
77
75
75
75
70
70
70
60
67
67
67
65
65
65
67
67
67
67
67
67
67
67
67
60
60
60
67
67
67
67
67
67
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
63
63
63
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,874
844
844
844
348
348
348
165
165
165
304
304
304
114
114
114
1,181
1,181
1,181
280
280
280
545
545
545
1,745
1,745
1,745
522
522
522
610
610
610
1,360
1,360
1,360
75
75
75
1,255
1,255
1,255
40,338
16,959
16,959
16,959
8,572
8,572
8,572
3,134
3,134
3,134
5,761
5,761
5,761
2,159
2,159
2,159
25,288
25,288
25,288
5,317
5,317
5,317
10,803
10,803
10,803
37,007
37,007
37,007
11,167
11,167
11,167
14,956
14,956
14,956
32,179
32,179
32,179
3,723
3,723
3,723
28,088
28,088
28,088
Coil
Latent
Load
Btu/h
2,929
7,387
7,387
7,387
90
90
90
2,099
2,099
2,099
3,302
3,302
3,302
1,446
1,446
1,446
2,687
2,687
2,687
3,047
3,047
3,047
5,923
5,923
5,923
4,132
4,132
4,132
1,239
1,239
1,239
651
651
651
953
953
953
703
703
703
2,386
2,386
2,386
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 48 of 100
SPACE
System Zone Room
spc_SS 272 Wrk Rm C_0
Peak
Zone - 056
Peak
Zone - 056
Block
spc_SS 270C/D Office_0
Peak
Zone - 057
Peak
Zone - 057
Block
spc_SS 111H Hall_0
Peak
Zone - 058
Peak
Zone - 058
Block
spc_SS 110G/H Offices C_0
Peak
Zone - 059
Peak
Zone - 059
Block
spc_SS 111A Office C_0
Peak
Zone - 060
Peak
Zone - 060
Block
spc_SS 242 Wrk Rm C_0
Peak
Zone - 061
Peak
Zone - 061
Block
spc_SS 240L Office C_0
Peak
Zone - 062
Peak
Zone - 062
Block
spc_SS 240H Office_0
Peak
Zone - 063
Peak
Zone - 063
Block
spc_SS 240F/J Office_0
Peak
Zone - 064
Peak
Zone - 064
Block
spc_SS 240-260A Wrk Rm C_0 Peak
Zone - 065
Peak
Zone - 065
Block
spc_SS 202/250B Office_0
Peak
Zone - 066
Peak
Zone - 066
Block
spc_SS 250 Wrk Rm C_0
Peak
Zone - 067
Peak
Zone - 067
Block
spc_SS 251 Wrk Rm C_0
Peak
Zone - 068
Peak
Zone - 068
Block
Peak
spc_SS 230H, 200-201, 251H, 272H_0
Zone - 069
Peak
Zone - 069
Block
spc_SS 210/211 Wrk Rm C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
778
778
778
287
287
287
397
397
397
269
269
269
216
216
216
642
642
642
149
149
149
181
181
181
274
274
274
865
865
865
214
214
214
0
0
0
388
388
388
4,383
4,383
4,383
308
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /12
9 /12
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
10 /16
10 /16
7 /16
7 /16
6 /9
6 /9
9 /12
9 /12
7 /16
7 /16
7 /15
70
70
70
73
73
73
73
73
73
76
76
76
76
76
76
79
79
79
75
75
75
76
76
76
75
75
75
79
79
79
76
76
76
62
62
62
73
73
73
76
76
76
77
63
63
63
63
63
63
65
65
65
66
66
66
66
66
66
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
66
66
66
58
58
58
63
63
63
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,090
1,090
1,090
379
379
379
175
175
175
131
131
131
105
105
105
406
406
406
73
73
73
89
89
89
133
133
133
1,257
1,257
1,257
104
104
104
16
16
16
387
387
387
2,716
2,716
2,716
171
21,179
21,179
21,179
7,364
7,364
7,364
3,399
3,399
3,399
2,552
2,552
2,552
2,048
2,048
2,048
7,890
7,890
7,890
1,410
1,410
1,410
1,719
1,719
1,719
2,589
2,589
2,589
24,416
24,416
24,416
2,028
2,028
2,028
304
304
304
7,518
7,518
7,518
52,749
52,749
52,749
3,325
2,489
2,489
2,489
627
627
627
612
612
612
703
703
703
564
564
564
1,777
1,777
1,777
397
397
397
474
474
474
728
728
728
2,394
2,394
2,394
559
559
559
0
0
0
1,195
1,195
1,195
15,399
15,399
15,399
1,069
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /13
9 /13
9 /13
9 /13
7 /18
7 /18
9 /17
9 /17
9 /17
9 /17
7 /16
7 /16
7 /17
7 /17
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
9 /17
9 /17
7 /10
7 /10
9 /12
9 /12
7 /16
7 /16
7 /16
75
75
75
75
75
75
73
73
73
76
76
76
76
76
76
76
76
76
75
75
75
76
76
76
75
75
75
77
77
77
76
76
76
67
67
67
73
73
73
76
76
76
76
65
65
65
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
60
60
60
63
63
63
66
66
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
918
918
918
357
357
357
175
175
175
129
129
129
103
103
103
394
394
394
73
73
73
87
87
87
133
133
133
1,221
1,221
1,221
102
102
102
15
15
15
387
387
387
2,716
2,716
2,716
171
25,380
25,380
25,380
10,543
10,543
10,543
3,469
3,469
3,469
2,443
2,443
2,443
1,960
1,960
1,960
17,212
17,212
17,212
3,620
3,620
3,620
1,646
1,646
1,646
6,646
6,646
6,646
38,964
38,964
38,964
1,941
1,941
1,941
312
312
312
8,858
8,858
8,858
113,463
113,463
113,463
7,815
Coil
Latent
Load
Btu/h
4,471
4,471
4,471
973
973
973
790
790
790
1,400
1,400
1,400
1,123
1,123
1,123
4,042
4,042
4,042
684
684
684
943
943
943
1,256
1,256
1,256
6,040
6,040
6,040
1,112
1,112
1,112
0
0
0
1,856
1,856
1,856
27,598
27,598
27,598
1,937
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 49 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 070
Zone - 070
spc_SS 230F Office C_0
Zone - 071
Zone - 071
spc_SS Wrk Rm 230 C_0
Zone - 072
Zone - 072
spc_SS 230C-E Office_0
Zone - 073
Zone - 073
spc_SS 240B Wrk Rm C_0
Zone - 074
Zone - 074
spc_SS 181 Comp Rm C_0
Zone - 075
Zone - 075
spc_SS 182 Comp Rm C_0
Zone - 076
Zone - 076
Stdnt Srv VAV
Stdnt Srv VAV
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
308
308
7 /15
180
6 /18
180
180
6 /18
987
7 /16
987
987
7 /16
630
6 /18
630
630
6 /18
240 10 /16
240
240 10 /16
854
7 /18
854
854
7/18
863
9 /11
863
863
9 /11
23,178
23,178 7 /17
77
77
70
70
70
76
76
76
70
70
70
79
79
79
73
73
73
70
70
70
75
75
66
66
63
63
63
66
66
66
63
63
63
64
64
64
65
65
65
63
63
63
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
171
171
330
330
330
550
550
550
1,887
1,887
1,887
607
607
607
2,223
2,223
2,223
2,317
2,317
2,317
27,996
21,892
3,325
3,325
6,408
6,408
6,408
10,680
10,680
10,680
36,641
36,641
36,641
11,782
11,782
11,782
43,184
43,184
43,184
45,011
45,011
45,011
543,738
425,196
1,069
1,069
360
360
360
3,468
3,468
3,468
1,262
1,262
1,262
663
663
663
2,471
2,471
2,471
2,243
2,243
2,243
66,071
67,555
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
7 /18
7 /18
9 /11
9 /11
7 /17
76
76
73
73
73
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
75
75
66
66
65
65
65
66
66
66
65
65
65
67
67
67
65
65
65
63
63
63
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
171
171
326
326
326
550
550
550
1,854
1,854
1,854
595
595
595
2,223
2,223
2,223
2,317
2,317
2,317
27,337
21,892
7,815
7,815
9,430
9,430
9,430
25,113
25,113
25,113
48,827
48,827
48,827
15,938
15,938
15,938
45,640
45,640
45,640
49,534
49,534
49,534
713,169
592,652
1,937
1,937
781
781
781
6,215
6,215
6,215
2,736
2,736
2,736
1,674
1,674
1,674
4,381
4,381
4,381
3,536
3,536
3,536
122,218
121,687
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 50 of 100
SPACE
Floor
Area
ft²
System Zone Room
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
58.1
58.1
58.1
51.6
51.6
51.6
55.0
55.0
55.0
56.7
56.7
56.7
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.8
57.8
57.8
52.5
52.5
52.5
69.6
69.6
69.6
57.6
57.6
54.7
54.7
54.7
54.6
54.6
54.6
49.8
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
19,718
19,718
19,718
27,717
27,717
27,717
4,324
4,324
4,324
8,470
8,470
8,470
10,677
10,677
10,677
33,208
33,208
33,208
3,217
3,217
3,217
2,438
2,438
2,438
46,648
46,648
46,648
8,293
8,293
8,293
13,658
13,658
13,658
178,368
160,203
45,748
45,748
45,748
34,617
34,617
34,617
7,681
649
649
649
6,690
6,690
6,690
0
0
0
601
601
601
686
686
686
2,099
2,099
2,099
935
935
935
708
708
708
1,884
1,884
1,884
1,710
1,710
1,710
-741
-741
-741
15,221
21,247
6,031
6,031
6,031
4,790
4,790
4,790
2,079
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
21,552
21,552
21,552
27,487
27,487
27,487
4,459
4,459
4,459
10,580
10,580
10,580
12,077
12,077
12,077
35,790
35,790
35,790
8,578
8,578
8,578
6,500
6,500
6,500
64,856
64,856
64,856
8,454
8,454
8,454
27,101
27,101
27,101
227,433
211,887
48,957
48,957
48,957
37,048
37,048
37,048
18,754
Coil
Latent
Load
Btu/h
Alternative 3
spc_A 121 Office UC_0
Zone - 077
Zone - 077
spc_A 130A Class? FC1-4_0
Zone - 078
Zone - 078
spc_A 237-241 Office C_0
Zone - 093
Zone - 093
spc_A 202A Office D_0
Zone - 094
Zone - 094
spc_A 202A Office B_0
Zone - 095
Zone - 095
spc_A 202A Office C_0
Zone - 096
Zone - 096
spc_A 201 Office C_0
Zone - 097
Zone - 097
spc_A 200H-J Office C_0
Zone - 098
Zone - 098
spc_A 200 Office C_0
Zone - 099
Zone - 099
spc_A 210A-B Stairs C_0
Zone - 100
Zone - 100
spc_A 121 Restroom FC05_0
Zone - 118
Zone - 118
Admin FC
Admin FC
spc_A 161/162 Class C_0
Zone - 091
Zone - 091
spc_A 160 Wrk Rm C_0
Zone - 092
Zone - 092
spc_A 236A/B Offices_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
348
348
348
2,606
2,606
2,606
0
0
0
344
344
344
238
238
238
891
891
891
353
353
353
267
267
267
1,011
1,011
1,011
1,111
1,111
1,111
734
734
734
7,905
7,905
2,273
2,273
2,273
1,806
1,806
1,806
786
10 /16
10 /16
10 /15
10 /15
7 /16
7 /16
6 /10
6 /10
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
7 /18
7 /18
10 /16
10 /16
9 /16
6 /9
6 /9
6 /9
6 /9
7 /17
79
79
79
80
80
80
76
76
76
65
65
65
76
76
76
73
73
73
75
75
75
75
75
75
79
79
79
73
73
73
79
79
79
77
77
62
62
62
62
62
62
75
64
64
64
63
63
63
66
66
66
58
58
58
67
67
67
65
65
65
66
66
66
66
66
66
64
64
64
65
65
65
64
64
64
67
67
58
58
58
58
58
58
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
9 /16
7 /9
7 /9
7 /9
7 /9
7 /17
77
77
77
77
77
77
76
76
76
76
76
76
76
76
76
73
73
73
75
75
75
75
75
75
77
77
77
73
73
73
77
77
77
77
77
64
64
64
64
64
64
75
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
65
65
65
66
66
66
66
66
66
67
67
67
65
65
65
67
67
67
67
67
59
59
59
59
59
59
66
58.4
58.4
58.4
51.8
51.8
51.8
55.0
55.0
55.0
63.1
63.1
63.1
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.9
57.9
57.9
52.5
52.5
52.5
69.8
69.8
69.8
58.0
59.2
55.1
55.1
55.1
54.9
54.9
54.9
49.8
1,735
1,735
1,735
18,165
18,165
18,165
0
0
0
1,536
1,536
1,536
1,234
1,234
1,234
3,864
3,864
3,864
1,611
1,611
1,611
1,221
1,221
1,221
5,037
5,037
5,037
2,205
2,205
2,205
-7,656
-7,656
-7,656
28,952
30,207
9,347
9,347
9,347
7,420
7,420
7,420
3,579
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 51 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 113
Zone - 113
spc_A 244/246 Office C_0
Zone - 114
Zone - 114
spc_A 242/243 Class C_0
Zone - 115
Zone - 115
spc_A 238-246 Offices C_0
Zone - 116
Zone - 116
spc_A 216/218 Office C_0
Zone - 117
Zone - 117
Admin Pckg AHU
Admin Pckg AHU
spc_A 277F Class_0
Zone - 079
Zone - 079
spc_A 279A Hall C_0
Zone - 080
Zone - 080
spc_A 278A Cond Stair_0
Zone - 081
Zone - 081
spc_A 170/171 Lobby C_0
Zone - 082
Zone - 082
spc_A 172 Wrk Rm C_0
Zone - 083
Zone - 083
spc_A Wrk Rm 173 C_0
Zone - 084
Zone - 084
spc_A 177 Comp C_1
Zone - 085
Zone - 085
spc_A 174-176 Data C_0
Zone - 086
Zone - 086
spc_A 177 Comp C_0
Zone - 087
Zone - 087
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
786
786
367
367
367
1,839
1,839
1,839
2,547
2,547
2,547
2,057
2,057
2,057
11,676
11,676
1,395
1,395
1,395
7,584
7,584
7,584
321
321
321
1,279
1,279
1,279
2,002
2,002
2,002
671
671
671
626
626
626
201
201
201
626
626
626
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
10 /16
10 /16
6 /10
6 /10
7 /17
7 /17
6 /10
6/18
6 /18
6 /10
6 /10
9 /11
9 /11
7 /18
7 /18
6 /9
6 /9
10 /15
10 /15
6 /9
6 /9
9 /16
9 /16
7 /16
7 /16
75
75
75
75
75
79
79
79
65
65
65
75
75
75
65
65
70
70
70
65
65
65
70
70
70
73
73
73
62
62
62
80
80
80
62
62
62
77
77
77
76
76
76
66
66
66
66
66
64
64
64
58
58
58
66
66
66
58
58
63
63
63
58
58
58
63
63
63
65
65
65
58
58
58
63
63
63
58
58
58
67
67
67
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
70.0
70.0
70.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.8
49.8
49.8
49.8
49.8
55.5
55.5
55.5
57.3
57.3
57.3
49.8
49.8
49.8
55.4
55.4
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,510
2,510
2,510
5,680
5,680
5,680
1,443
1,443
1,443
483
483
483
2,570
2,570
2,570
1,214
1,214
1,214
1,490
1,490
1,490
1,917
1,917
1,917
1,042
1,042
1,042
7,681
7,681
3,589
3,589
3,589
49,570
49,570
49,570
81,320
81,320
81,320
20,104
20,104
20,104
242,629
193,483
46,615
46,615
46,615
105,509
105,509
105,509
26,795
26,795
26,795
8,969
8,969
8,969
47,731
47,731
47,731
22,553
22,553
22,553
27,671
27,671
27,671
31,338
31,338
31,338
19,354
19,354
19,354
2,079
2,079
971
971
971
5,095
5,095
5,095
4,472
4,472
4,472
5,442
5,442
5,442
28,881
25,762
4,376
4,376
4,376
5,555
5,555
5,555
411
411
411
2,208
2,208
2,208
5,370
5,370
5,370
1,747
1,747
1,747
1,303
1,303
1,303
497
497
497
1,843
1,843
1,843
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
7 /17
7 /17
7 /16
7 /18
7 /18
7 /16
7 /16
9 /11
9 /11
7 /9
7 /9
7 /9
7 /9
9 /16
9 /16
7 /9
7 /9
9 /16
9 /16
9 /16
9 /16
75
75
75
75
75
77
77
77
76
76
76
75
75
75
76
76
73
73
73
76
76
76
70
70
70
64
64
64
64
64
64
77
77
77
64
64
64
77
77
77
77
77
77
66
66
66
66
66
67
67
67
66
66
66
66
66
66
66
66
65
65
65
66
66
66
63
63
63
59
59
59
59
59
59
67
67
67
59
59
59
67
67
67
67
67
67
49.8
49.8
49.8
49.8
49.8
55.6
55.6
55.6
64.0
64.0
64.0
49.8
49.8
49.8
58.0
60.0
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,485
2,485
2,485
3,475
3,475
3,475
1,443
1,443
1,443
420
420
420
2,508
2,508
2,508
1,209
1,209
1,209
1,469
1,469
1,469
1,917
1,917
1,917
1,032
1,032
1,032
18,754
18,754
8,763
8,763
8,763
78,514
78,514
78,514
92,985
92,985
92,985
49,087
49,087
49,087
334,108
299,894
66,753
66,753
66,753
177,138
177,138
177,138
30,401
30,401
30,401
10,395
10,395
10,395
48,380
48,380
48,380
23,906
23,906
23,906
28,680
28,680
28,680
33,072
33,072
33,072
19,437
19,437
19,437
Coil
Latent
Load
Btu/h
3,579
3,579
1,672
1,672
1,672
12,862
12,862
12,862
11,426
11,426
11,426
9,369
9,369
9,369
55,677
63,035
9,143
9,143
9,143
15,367
15,367
15,367
511
511
511
2,145
2,145
2,145
8,439
8,439
8,439
4,762
4,762
4,762
2,059
2,059
2,059
835
835
835
3,541
3,541
3,541
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 52 of 100
SPACE
System Zone Room
spc_A 179/178 Data C_0
Peak
Zone - 088
Peak
Zone - 088
Block
spc_A 180E Com Lab C_0
Peak
Zone - 089
Peak
Zone - 089
Block
spc_A 271-277 Office C_0
Peak
Zone - 111
Peak
Zone - 111
Block
spc_A 277 Class_0
Peak
Zone - 112
Peak
Zone - 112
Block
Peak
Admin VAV
Admin VAV
Block
spc_BC 237 Class_0
Peak
Zone - 334
Peak
Zone - 334
Block
spc_BC 221 Lobby_0
Peak
Zone - 335
Peak
Zone - 335
Block
spc_BC 222 Class_0
Peak
Zone - 336
Peak
Zone - 336
Block
spc_215-219 Office_0
Peak
Zone - 337
Peak
Zone - 337
Block
spc_BC 224 Class_0
Peak
Zone - 338
Peak
Zone - 338
Block
spc_BC 2nd 226/228 Class_0
Peak
Zone - 339
Peak
Zone - 339
Block
spc_BC 2nd 230 Class_0
Peak
Zone - 340
Peak
Zone - 340
Block
spc_BC 115/116 Office_0
Peak
Zone - 351
Peak
Zone - 351
Block
spc_BC Office 137/139/141/142_0 Peak
Zone - 352
Peak
Zone - 352
Block
spc_BC 143 Office_0
Peak
Zone - 353
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
339
339
339
951
951
951
2,656
2,656
2,656
0
0
0
18,650
18,650
166
166
166
120
120
120
196
196
196
262
262
262
146
146
146
281
281
281
187
187
187
155
155
155
103
103
103
123
123
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
9 /15
10 /14
10 /14
7 /16
7 /16
7 /18
7 /18
10 /16
10 /16
9 /11
9 /11
9 /10
9 /10
9 /17
9 /17
9 /12
9 /12
10 /16
10 /16
10 /16
76
76
76
80
80
80
75
75
75
80
80
80
78
78
79
79
79
76
76
76
73
73
73
79
79
79
70
70
70
67
67
67
76
76
76
73
73
73
79
79
79
79
79
66
66
66
63
63
63
66
66
66
63
63
63
66
66
62
62
62
66
66
66
65
65
65
64
64
64
63
63
63
61
61
61
67
67
67
63
63
63
64
64
64
64
64
70.0
70.0
70.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
71.7
71.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
57.5
57.5
57.5
57.3
57.3
57.3
57.1
57.1
57.1
57.5
57.5
57.5
55.6
55.6
55.6
56.0
56.0
56.0
57.2
57.2
57.2
56.1
56.1
56.1
51.8
51.8
51.8
58.7
58.7
2,037
2,037
2,037
2,646
2,646
2,646
1,344
1,344
1,344
4,175
4,175
4,175
28,551
22,316
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
237
237
237
38
38
38
797
797
33,300
33,300
33,300
49,154
49,154
49,154
24,971
24,971
24,971
77,551
77,551
77,551
521,509
407,618
6,259
6,259
6,259
3,956
3,956
3,956
14,583
14,583
14,583
10,595
10,595
10,595
5,091
5,091
5,091
11,008
11,008
11,008
15,364
15,364
15,364
4,204
4,204
4,204
848
848
848
11,800
11,800
771
771
771
1,906
1,906
1,906
7,134
7,134
7,134
0
0
0
33,121
44,638
375
375
375
194
194
194
681
681
681
491
491
491
468
468
468
889
889
889
658
658
658
340
340
340
192
192
192
231
231
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /19
9 /19
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /14
9 /14
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
9 /12
9 /12
9 /11
9 /11
9 /17
9 /17
9 /12
9 /12
9 /17
9 /17
10 /16
71
71
71
77
77
77
76
76
76
77
77
77
77
77
77
77
77
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
76
76
76
73
73
73
76
76
76
79
79
66
66
66
67
67
67
66
66
66
67
67
67
67
67
66
66
66
66
66
66
65
65
65
67
67
67
63
63
63
63
63
63
67
67
67
63
63
63
67
67
67
64
64
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
58.2
58.2
58.2
57.3
57.3
57.3
57.1
57.1
57.1
57.7
57.7
57.7
56.5
56.5
56.5
56.3
56.3
56.3
57.2
57.2
57.2
56.1
56.1
56.1
52.2
52.2
52.2
58.7
58.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
2,008
2,008
2,008
2,644
2,644
2,644
1,337
1,337
1,337
4,061
4,061
4,061
26,008
22,285
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
237
237
237
38
38
38
797
797
33,409
33,409
33,409
51,546
51,546
51,546
32,823
32,823
32,823
77,838
77,838
77,838
651,278
557,619
7,849
7,849
7,849
5,195
5,195
5,195
17,225
17,225
17,225
12,759
12,759
12,759
6,331
6,331
6,331
12,300
12,300
12,300
20,480
20,480
20,480
5,546
5,546
5,546
1,020
1,020
1,020
13,862
13,862
Coil
Latent
Load
Btu/h
1,453
1,453
1,453
5,384
5,384
5,384
12,103
12,103
12,103
0
0
0
65,740
78,660
1,025
1,025
1,025
278
278
278
1,269
1,269
1,269
1,313
1,313
1,313
701
701
701
1,464
1,464
1,464
1,309
1,309
1,309
517
517
517
535
535
535
308
308
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 53 of 100
SPACE
System Zone Room
Zone - 353
spc_BC 109 Class_0
Zone - 354
Zone - 354
spc_BC 108 Class_0
Zone - 355
Zone - 355
spc_BC 106 Class_0
Zone - 356
Zone - 356
spc_BC 105 Class_0
Zone - 357
Zone - 357
spc_BC 101 Class_0
Zone - 358
Zone - 358
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
BC FC
Peak
BC FC
Block
spc_BC 130 Cafe/Kitchen_0
Peak
Zone - 341
Peak
Zone - 341
Block
spc_BC AH-2 245 Lecture_0
Peak
Zone - 342
Peak
Zone - 342
Block
spc_BC AH-3 301 Class_0
Peak
Zone - 343
Peak
Zone - 343
Block
spc_BC AH-4 302 Class_0
Peak
Zone - 344
Peak
Zone - 344
Block
spc_BC 306 Office (AH-5)_0
Peak
spc_BC 307-312 Office (AH-5)_0 Peak
spc_BC AH-5 304 Hall_0
Peak
Zone - 345
Peak
Zone - 345
Block
spc_BC AH-6 315 Lab_0
Peak
Zone - 346
Peak
Zone - 346
Block
spc_BC AH-7 314 Class_0
Peak
Zone - 347
Peak
Zone - 347
Block
spc_BC AH-8 313_0
Peak
Zone - 348
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
123
248
248
248
228
228
228
287
287
287
308
308
308
696
696
696
3,507
3,507
1,908
1,908
1,908
809
809
809
162
162
162
188
188
188
17
107
518
642
642
181
181
181
183
183
183
518
518
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
9 /12
9 /12
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /12
7 /19
7 /19
9 /13
9 /13
7 /10
7 /10
11 /13
11 /13
7 /18
10 /16
7 /18
10/16
10 /16
10 /16
6 /9
6 /9
9 /16
79
73
73
73
73
73
73
70
70
70
70
70
70
70
70
70
73
73
71
71
71
75
75
75
67
67
67
71
71
71
73
79
73
79
79
79
79
79
62
62
62
77
77
64
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
64
64
64
65
65
65
60
60
60
58
58
58
65
64
65
64
64
64
64
64
58
58
58
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
58.7
53.9
53.9
53.9
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.8
56.8
49.0
49.0
49.0
48.5
48.5
48.5
57.5
57.5
57.5
55.0
55.0
55.0
57.7
59.1
54.7
58.0
58.0
58.3
58.3
58.3
56.9
56.9
56.9
55.0
55.0
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
902
902
902
435
435
435
1,005
1,005
11,800
5,234
5,234
5,234
6,925
6,925
6,925
15,674
15,674
15,674
16,788
16,788
16,788
36,297
36,297
36,297
164,625
128,212
25,681
25,681
25,681
8,768
8,768
8,768
9,949
9,949
9,949
14,106
14,106
14,106
1,203
14,924
6,067
22,194
20,846
13,789
13,789
13,789
7,351
7,351
7,351
19,025
19,025
231
766
766
766
704
704
704
918
918
918
985
985
985
2,230
2,230
2,230
10,125
10,014
7,496
7,496
7,496
2,709
2,709
2,709
457
457
457
435
435
435
41
199
801
1,041
657
394
394
394
486
486
486
1,924
1,924
10 /16
9 /13
9 /13
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /13
7 /19
7 /19
9 /14
9 /14
7 /10
7 /10
9 /15
9 /15
7 /18
10 /16
7 /18
9 /17
9 /16
9 /16
7 /17
7 /17
9 /16
79
75
75
75
73
73
73
70
70
70
70
70
70
70
70
70
75
75
71
71
71
77
77
77
67
67
67
78
78
78
73
79
73
76
76
77
77
77
75
75
75
77
77
64
65
65
65
63
63
63
63
63
63
63
63
63
63
63
63
65
65
64
64
64
66
66
66
60
60
60
66
66
66
65
64
65
67
67
67
67
67
66
66
66
67
67
58.7
54.5
54.5
54.5
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.9
60.6
49.0
49.0
49.0
48.7
48.7
48.7
57.5
57.5
57.5
57.3
57.3
57.3
57.7
59.1
54.7
58.0
59.1
58.5
58.5
58.5
61.5
61.5
61.5
55.0
55.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
902
902
902
435
435
435
1,005
1,005
13,862
6,369
6,369
6,369
8,775
8,775
8,775
17,730
17,730
17,730
19,220
19,220
19,220
40,708
40,708
40,708
195,368
154,845
28,282
28,282
28,282
10,394
10,394
10,394
11,797
11,797
11,797
17,273
17,273
17,273
1,823
19,637
7,596
29,057
27,346
18,690
18,690
18,690
9,470
9,470
9,470
25,235
25,235
Coil
Latent
Load
Btu/h
308
1,430
1,430
1,430
1,096
1,096
1,096
1,494
1,494
1,494
1,603
1,603
1,603
3,631
3,631
3,631
17,976
18,247
13,513
13,513
13,513
4,960
4,960
4,960
624
624
624
1,481
1,481
1,481
75
265
1,033
1,373
1,870
1,012
1,012
1,012
1,133
1,133
1,133
3,625
3,625
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 54 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 348
BC Hydronic AHU
BC Hydronic AHU
spc_CC 108 C_0
Zone - 120
Zone - 120
spc_CC 106 Mechanical C_0
Zone - 121
Zone - 121
spc_CC 203 Storage_0
Zone - 122
Zone - 122
spc_CC 202 Storage_0
Zone - 123
Zone - 123
spc_CC 201 Eating Area C_0
Zone - 124
Zone - 124
Campus Center Dual Deck
Campus Center Dual Deck
spc_CC Class 122-126 C_0
Zone - 119
Zone - 119
Campus Center FC
Campus Center FC
spc_CC 228 Comp C_0
Zone - 125
Zone - 125
Bookstore 1
Zone - 362
Zone - 362
Bookstore 2
Zone - 363
Zone - 363
Bookstore 3
Zone - 364
Zone - 364
Bookstore 4
Zone - 365
Zone - 365
Bookstore 5
Zone - 366
Zone - 366
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
518
4,592
4,592
381
381
381
530
530
530
159
159
159
133
133
133
1,974
1,974
1,974
3,176
3,176
1,023
1,023
1,023
1,023
1,023
519
519
519
915
915
915
915
915
915
915
915
915
915
915
915
915
915
915
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
9 /12
9 /12
9 /12
9 /12
10 /14
6 /18
6 /18
6 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
80
80
79
79
79
76
76
76
76
76
76
73
73
73
73
73
73
79
79
70
70
70
70
70
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
63
63
64
64
64
67
67
67
67
67
67
63
63
63
63
63
63
62
62
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.0
55.2
55.2
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.1
57.1
57.1
57.1
57.1
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
1,005
6,464
6,464
797
797
797
480
480
480
556
556
556
430
430
430
1,808
1,808
1,808
4,073
4,073
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
404
404
404
404
404
404
404
404
19,025
120,862
101,266
12,551
12,551
12,551
11,849
11,849
11,849
8,761
8,761
8,761
6,778
6,778
6,778
28,473
28,473
28,473
68,413
57,628
64,980
64,980
64,980
64,980
64,980
17,432
17,432
17,432
11,760
11,760
11,760
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
1,924
14,942
6,374
167
167
167
761
761
761
277
277
277
137
137
137
4,445
4,445
4,445
5,787
5,745
3,184
3,184
3,184
3,184
3,184
1,513
1,513
1,513
3,754
3,754
3,754
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /17
9 /17
9 /13
9 /13
9 /13
9 /13
9 /14
7 /18
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
77
77
76
76
76
76
76
76
76
76
76
75
75
75
75
75
75
77
77
73
73
73
73
73
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
65
65
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
55.0
55.8
58.3
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.4
57.4
57.4
57.4
57.4
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,005
6,464
6,464
784
784
784
477
477
477
554
554
554
414
414
414
1,746
1,746
1,746
3,974
3,459
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
404
404
404
404
404
404
404
404
25,235
150,199
134,479
15,748
15,748
15,748
15,813
15,813
15,813
13,075
13,075
13,075
9,068
9,068
9,068
33,559
33,559
33,559
87,263
75,402
69,485
69,485
69,485
69,485
69,485
22,424
22,424
22,424
18,552
18,552
18,552
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
Coil
Latent
Load
Btu/h
3,625
27,722
25,060
1,787
1,787
1,787
1,129
1,129
1,129
379
379
379
204
204
204
12,956
12,956
12,956
16,454
17,396
6,613
6,613
6,613
6,613
6,613
2,598
2,598
2,598
6,278
6,278
6,278
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 55 of 100
SPACE
System Zone Room
Floor
Area
ft²
Bookstore 6
Peak
Zone - 367
Peak
Zone - 367
Block
Campus Center Packg RTU-1
Peak
Campus Center Packg RTU-1
Block
spc_DM FC-Music Office_0
Peak
Zone - 137
Peak
Zone - 137
Block
Peak
spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0
Zone - 138
Peak
Zone - 138
Block
spc_DM FC 3-1 Dress Rms Int_0 Peak
Zone - 139
Peak
Zone - 139
Block
spc_DM FC 3-1 Dress Rms_0
Peak
Zone - 140
Peak
Zone - 140
Block
Drama/Music Fan Coil
Peak
Drama/Music Fan Coil
Block
spc_HP-9 Office_0
Peak
Zone - 126
Peak
Zone - 126
Block
spc_DM HP-7 Storage_0
Peak
Zone - 127
Peak
Zone - 127
Block
spc_DM HP-7 Dress Rm_0
Peak
Zone - 128
Peak
Zone - 128
Block
spc_DM HP 3/4 Class_0
Peak
Zone - 129
Peak
Zone - 129
Block
spc_DM HP-2 Class_0
Peak
Zone - 130
Peak
Zone - 130
Block
spc_DM HP-5 Performance Rm_0 Peak
Zone - 131
Peak
Zone - 131
Block
spc_DM HP-10 Prop Rm_0
Peak
Zone - 132
Peak
Zone - 132
Block
spc_DM HP-1 Main Corridor_0
Peak
Zone - 133
Peak
Zone - 133
Block
915
915
915
6,007
6,007
338
338
338
892
892
892
267
267
267
327
327
327
1,824
1,824
121
121
121
57
57
57
9,797
9,797
9,797
926
926
926
569
569
569
1,176
1,176
1,176
1,131
1,131
1,131
7,381
7,381
7,381
Project Name:
Dataset Name:
SBCC TRACE.TRC
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
10 /16
10 /16
9 /17
9 /12
9 /12
10 /15
10 /15
10 /15
10 /15
6 /9
6 /9
11 /13
11 /13
9 /12
9 /12
7 /18
7 /18
9 /11
9 /11
76
76
76
76
76
79
79
79
75
75
75
76
76
76
79
79
79
76
76
73
73
73
80
80
80
80
80
80
62
62
62
71
71
71
73
73
73
73
73
73
70
70
70
66
66
66
66
66
64
64
64
66
66
66
66
66
66
64
64
64
67
67
63
63
63
63
63
63
63
63
63
58
58
58
58
58
58
63
63
63
65
65
65
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.4
49.4
49.4
51.0
51.0
56.4
56.4
56.4
54.3
54.3
54.3
44.5
44.5
44.5
58.3
58.3
58.3
55.7
55.7
57.0
57.0
57.0
54.8
54.8
54.8
51.3
51.3
51.3
55.4
55.4
55.4
59.2
59.2
59.2
53.5
53.5
53.5
57.4
57.4
57.4
56.2
56.2
56.2
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
10,160
10,160
10,160
79,989
79,989
8,123
8,123
8,123
9,831
9,831
9,831
2,946
2,946
2,946
8,853
8,853
8,853
29,753
27,815
4,747
4,747
4,747
261
261
261
99,554
99,554
99,554
21,837
21,837
21,837
35,452
35,452
35,452
27,637
27,637
27,637
36,017
36,017
36,017
106,822
106,822
106,822
2,839
2,839
2,839
19,459
19,459
633
633
633
1,432
1,432
1,432
1,098
1,098
1,098
269
269
269
3,432
4,394
263
263
263
35
35
35
25,148
25,148
25,148
2,451
2,451
2,451
1,082
1,082
1,082
4,324
4,324
4,324
1,740
1,740
1,740
9,194
9,194
9,194
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /17
9 /13
9 /13
7 /16
7 /16
9 /16
9 /16
7 /16
7 /16
9 /13
9 /13
7 /15
7 /15
7 /17
7 /17
9 /11
9 /11
76
76
76
76
76
76
76
76
75
75
75
77
77
77
79
79
79
76
76
75
75
75
76
76
76
77
77
77
76
76
76
75
75
75
77
77
77
75
75
75
70
70
70
66
66
66
66
66
67
67
67
66
66
66
67
67
67
64
64
64
67
67
65
65
65
66
66
66
67
67
67
66
66
66
65
65
65
66
66
66
66
66
66
63
63
63
49.4
49.4
49.4
51.0
51.0
56.5
56.5
56.5
54.3
54.3
54.3
45.0
45.0
45.0
58.3
58.3
58.3
55.8
56.8
57.6
57.6
57.6
55.8
55.8
55.8
51.5
51.5
51.5
59.2
59.2
59.2
60.5
60.5
60.5
59.5
59.5
59.5
57.8
57.8
57.8
56.2
56.2
56.2
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
17,188
17,188
17,188
126,914
126,914
12,772
12,772
12,772
21,797
21,797
21,797
2,242
2,242
2,242
10,451
10,451
10,451
47,261
42,971
6,446
6,446
6,446
1,151
1,151
1,151
104,158
104,158
104,158
33,229
33,229
33,229
39,761
39,761
39,761
38,930
38,930
38,930
57,496
57,496
57,496
120,423
120,423
120,423
Coil
Latent
Load
Btu/h
5,361
5,361
5,361
35,683
35,683
1,763
1,763
1,763
1,818
1,818
1,818
2,311
2,311
2,311
330
330
330
6,222
7,103
408
408
408
120
120
120
68,283
68,283
68,283
5,820
5,820
5,820
3,265
3,265
3,265
8,980
8,980
8,980
2,459
2,459
2,459
11,397
11,397
11,397
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 56 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_DM HP-9 Class_0
Zone - 148
Zone - 148
spc_DM HP-6 Office_0
Zone - 149
Zone - 149
spc_DM HP-8 Class1_0
Zone - 150
Zone - 150
spc_DM PHP-5-2 Offices_0
Zone - 151
Zone - 151
spc_PHP-2-1 Cargo Elevator_0
Zone - 152
Zone - 152
spc_DM PRP-5-1 Restroom_0
Zone - 153
Zone - 153
spc_DM PRP-5-1 Restroom1_0
Zone - 154
Zone - 154
Drama/Music HP
Drama/Music HP
spc_AC-1 Auditorium_0
Zone - 141
Zone - 141
spc_DM AN-2 Corridor_0
Zone - 142
Zone - 142
spc_DM AC-2 Rehearsal Rm_0
Zone - 143
Zone - 143
spc_DM ZN-1 Class_0
Zone - 144
Zone - 144
spc_DM ZN-3 Hall_0
Zone - 145
Zone - 145
spc_DM Zn-3 Offices_0
Zone - 146
Zone - 146
spc_ZN-3 Conf_0
Zone - 147
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
192
192
192
220
220
220
592
592
592
292
292
292
122
122
122
848
848
848
1,177
1,177
1,177
24,602
24,602
3,790
3,790
3,790
701
701
701
1,135
1,135
1,135
417
417
417
209
209
209
177
177
177
405
405
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /15
10 /15
6 /9
6 /9
10 /15
10 /15
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
9 /12
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
6 /18
6 /18
10 /16
10 /16
10 /16
10 /16
6 /10
80
80
80
62
62
62
80
80
80
79
79
79
79
79
79
79
79
79
79
79
79
73
73
80
80
80
75
75
75
80
80
80
70
70
70
79
79
79
79
79
79
65
65
63
63
63
58
58
58
63
63
63
64
64
64
64
64
64
64
64
64
64
64
64
63
63
63
63
63
66
66
66
63
63
63
63
63
63
64
64
64
64
64
64
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
80.0
80.0
80.0
73.1
73.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
51.3
51.3
51.3
58.2
58.2
58.2
51.3
51.3
51.3
52.2
52.2
52.2
58.6
58.6
58.6
79.6
79.6
79.6
79.6
79.6
79.6
58.9
58.9
54.9
54.9
54.9
55.9
55.9
55.9
50.7
50.7
50.7
56.6
56.6
56.6
49.9
49.9
49.9
51.7
51.7
51.7
50.6
50.6
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
24
24
24
64
64
64
206
206
1,946
1,946
1,946
10,408
10,408
10,408
6,020
6,020
6,020
2,564
2,564
2,564
4,056
4,056
4,056
538
538
538
747
747
747
358,606
299,869
74,299
74,299
74,299
11,804
11,804
11,804
10,848
10,848
10,848
20,443
20,443
20,443
583
583
583
1,443
1,443
1,443
4,907
4,907
492
492
492
311
311
311
1,521
1,521
1,521
545
545
545
99
99
99
-2,632
-2,632
-2,632
-3,655
-3,655
-3,655
40,918
47,013
9,753
9,753
9,753
1,126
1,126
1,126
2,908
2,908
2,908
1,296
1,296
1,296
169
169
169
330
330
330
1,311
1,311
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
76
76
76
65
65
65
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
77
77
75
75
75
77
77
77
73
73
73
77
77
77
76
76
76
77
77
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
65
65
65
67
67
67
67
67
67
67
67
51.4
51.4
51.4
58.8
58.8
58.8
51.5
51.5
51.5
52.4
52.4
52.4
58.8
58.8
58.8
79.7
79.7
79.7
79.7
79.7
79.7
59.7
62.3
55.5
55.5
55.5
55.9
55.9
55.9
51.3
51.3
51.3
56.7
56.7
56.7
51.4
51.4
51.4
52.3
52.3
52.3
53.5
53.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
24
24
24
64
64
64
206
206
5,018
5,018
5,018
11,069
11,069
11,069
6,298
6,298
6,298
2,691
2,691
2,691
6,557
6,557
6,557
5,343
5,343
5,343
7,418
7,418
7,418
445,988
374,351
83,988
83,988
83,988
13,640
13,640
13,640
13,026
13,026
13,026
22,815
22,815
22,815
715
715
715
1,748
1,748
1,748
5,430
5,430
1,203
1,203
1,203
475
475
475
4,129
4,129
4,129
1,517
1,517
1,517
288
288
288
-46,142
-46,142
-46,142
-64,061
-64,061
-64,061
-1,859
7,013
26,500
26,500
26,500
1,430
1,430
1,430
7,893
7,893
7,893
2,691
2,691
2,691
468
468
468
919
919
919
3,494
3,494
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 57 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 147
spc_DM Scene Shop HV-1_0
Zone - 155
Zone - 155
Drama/Music MZU
Drama/Music MZU
spc_EBS 217/Storage C_0
Zone - 156
Zone - 156
spc_EBS 215 Class C_0
Zone - 157
Zone - 157
spc_EBS 209 Class C_0
Zone - 158
Zone - 158
spc_EBS 210 Class C_0
Zone - 159
Zone - 159
spc_EBS 109/127 Lobby C_0
Zone - 160
Zone - 160
spc_EBS 125 Class C_0
Zone - 161
Zone - 161
spc_EBS 102 Class C_0
Zone - 162
Zone - 162
spc_EBS 123 Class C_0
Zone - 163
Zone - 163
spc_EBS 119 Offices C_0
Zone - 164
Zone - 164
spc_EBS 119 Office C_0
Zone - 165
Zone - 165
spc_EBS 116 Office C_0
Zone - 166
Zone - 166
spc_EBS 110-113 Office UC_0
Zone - 167
Zone - 167
spc_EBS 114 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
405
1,711
1,711
1,711
8,545
8,545
2,046
2,046
2,046
758
758
758
1,358
1,358
1,358
1,333
1,333
1,333
1,771
1,771
1,771
396
396
396
1,332
1,332
1,332
1,622
1,622
1,622
399
399
399
306
306
306
156
156
156
515
515
515
893
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /10
10 /13
10 /13
9 /16
7 /15
7 /15
7 /16
7 /16
10 /15
10 /15
7 /18
7 /18
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
10 /14
65
77
77
77
77
77
77
77
77
76
76
76
80
80
80
73
73
73
75
75
75
73
73
73
73
73
73
73
73
73
75
75
75
75
75
75
73
73
73
73
73
73
79
58
59
59
59
67
67
66
66
66
66
66
66
63
63
63
65
65
65
66
66
66
65
65
65
65
65
65
65
65
65
66
66
66
66
66
66
65
65
65
65
65
65
62
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
50.6
57.7
57.7
57.7
55.4
55.4
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
206
1,561
1,561
1,561
8,045
8,045
931
931
931
493
493
493
1,547
1,547
1,547
1,511
1,511
1,511
744
744
744
473
473
473
2,019
2,019
2,019
1,486
1,486
1,486
309
309
309
177
177
177
220
220
220
624
624
624
1,093
4,907
24,799
24,799
24,799
149,125
129,890
18,050
18,050
18,050
9,553
9,553
9,553
29,992
29,992
29,992
29,286
29,286
29,286
14,421
14,421
14,421
9,178
9,178
9,178
39,142
39,142
39,142
28,811
28,811
28,811
5,997
5,997
5,997
3,436
3,436
3,436
4,262
4,262
4,262
12,097
12,097
12,097
21,186
1,311
3,134
3,134
3,134
20,027
30,017
3,114
3,114
3,114
2,661
2,661
2,661
3,489
3,489
3,489
4,607
4,607
4,607
2,924
2,924
2,924
1,369
1,369
1,369
4,604
4,604
4,604
5,608
5,608
5,608
1,057
1,057
1,057
811
811
811
368
368
368
1,214
1,214
1,214
2,014
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /14
9 /14
9 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /14
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
75
75
75
75
75
75
73
73
73
73
73
73
75
75
75
75
75
75
75
75
75
73
73
73
73
73
73
77
67
66
66
66
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
66
53.5
58.2
58.2
58.2
55.9
57.5
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
206
1,561
1,561
1,561
8,045
8,045
903
903
903
493
493
493
1,515
1,515
1,515
1,493
1,493
1,493
744
744
744
473
473
473
2,019
2,019
2,019
1,454
1,454
1,454
309
309
309
177
177
177
220
220
220
624
624
624
1,079
5,430
30,462
30,462
30,462
171,824
156,601
40,996
40,996
40,996
17,369
17,369
17,369
45,366
45,366
45,366
45,809
45,809
45,809
35,058
35,058
35,058
14,006
14,006
14,006
55,862
55,862
55,862
46,115
46,115
46,115
10,829
10,829
10,829
6,764
6,764
6,764
6,557
6,557
6,557
19,460
19,460
19,460
22,361
Coil
Latent
Load
Btu/h
3,494
10,580
10,580
10,580
53,975
55,726
4,331
4,331
4,331
4,766
4,766
4,766
9,476
9,476
9,476
8,212
8,212
8,212
4,199
4,199
4,199
2,548
2,548
2,548
8,567
8,567
8,567
9,995
9,995
9,995
1,822
1,822
1,822
1,398
1,398
1,398
677
677
677
2,235
2,235
2,235
5,495
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 58 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 168
Zone - 168
spc_EBS 115 Class C_0
Zone - 169
Zone - 169
spc_EBS 209 Class UC_0
Zone - 172
Zone - 172
spc_EBS 210 Class C_1
Zone - 173
Zone - 173
spc_EBS 215 Class C_1
Zone - 174
Zone - 174
spc_EBS 218 Office C_0
Zone - 175
Zone - 175
spc_EBS 216 Office C_0
Zone - 176
Zone - 176
EBS VAV
EBS VAV
spc_H 326 Class C_0
Zone - 206
Zone - 206
spc_H 328 Class C_0
Zone - 207
Zone - 207
spc_H 328 Office C_0
Zone - 208
Zone - 208
Humanities Fan Coil
Humanities Fan Coil
spc_H 104/107/112 Art C_0
Zone - 177
Zone - 177
spc_H 102 Class C_0
Zone - 178
Zone - 178
spc_H 106 Office C_0
Zone - 179
Zone - 179
spc_H 2444 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
893
893 10 /14
1,659
9 /16
1,659
1,659
9 /16
1,334
7 /16
1,334
1,334
7 /16
1,334
7 /16
1,334
1,334
7 /16
790
7 /18
790
790
7 /18
70
7 /18
70
70
7/18
74
7 /17
74
74
7 /17
18,147
18,147 7 /17
845
5 /17
845
845
5 /17
1,818 7 /16
1,818
1,818 7 /16
300
7 /12
300
300
7 /12
2,963
2,963 7 /17
7,121 7 /16
7,121
7,121 7 /16
1,004 7 /16
1,004
1,004 7 /16
229
7 /17
229
229
7 /17
555
7 /16
79
79
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
72
72
72
76
76
76
73
73
73
75
75
76
76
76
76
76
76
75
75
75
76
62
62
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
63
63
63
66
66
66
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
54.3
54.3
54.3
56.6
56.6
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
1,093
1,093
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,925
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,288
5,288
5,288
627
627
627
122
122
122
346
21,186
21,186
31,380
31,380
31,380
16,818
16,818
16,818
16,818
16,818
16,818
14,759
14,759
14,759
2,665
2,665
2,665
826
826
826
308,677
289,380
76,201
76,201
76,201
24,051
24,051
24,051
4,645
4,645
4,645
104,897
101,595
91,368
91,368
91,368
10,835
10,835
10,835
2,102
2,102
2,102
5,987
2,014
2,014
6,149
6,149
6,149
4,685
4,685
4,685
4,685
4,685
4,685
2,731
2,731
2,731
166
166
166
195
195
195
52,452
52,299
2,350
2,350
2,350
6,371
6,371
6,371
631
631
631
9,352
9,537
24,945
24,945
24,945
3,519
3,519
3,519
604
604
604
1,944
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /14
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /17
7 /15
7 /15
9 /16
9 /16
9 /17
9 /17
9 /16
77
77
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
73
73
73
76
76
76
76
76
76
75
75
77
77
77
77
77
77
76
76
76
77
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
65
65
65
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
57.2
57.2
57.2
56.7
57.1
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,079
1,079
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,801
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,284
5,284
5,284
600
600
600
119
119
119
331
22,361
22,361
49,825
49,825
49,825
30,579
30,579
30,579
30,579
30,579
30,579
23,381
23,381
23,381
3,913
3,913
3,913
1,626
1,626
1,626
504,179
486,608
92,686
92,686
92,686
49,932
49,932
49,932
8,423
8,423
8,423
151,042
148,011
99,527
99,527
99,527
11,228
11,228
11,228
2,209
2,209
2,209
6,204
Coil
Latent
Load
Btu/h
5,495
5,495
11,570
11,570
11,570
8,391
8,391
8,391
8,391
8,391
8,391
5,082
5,082
5,082
305
305
305
336
336
336
97,796
94,521
5,460
5,460
5,460
11,390
11,390
11,390
1,341
1,341
1,341
18,190
17,762
43,603
43,603
43,603
6,979
6,979
6,979
1,184
1,184
1,184
3,856
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 59 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 180
Zone - 180
spc_H 245A/B Class C_0
Zone - 181
Zone - 181
spc_H 226/A office C_0
Zone - 182
Zone - 182
spc_H 208-217 Office C_0
Zone - 183
Zone - 183
spc_H 225 Office C_0
Zone - 184
Zone - 184
spc_H 242/207 Corridor C_0
Zone - 185
Zone - 185
spc_H 123U Art AH-1/23_0
Zone - 186
Zone - 186
spc_H 111 Class C_0
Zone - 187
Zone - 187
spc_H 221/220/204 Class C_0
Zone - 188
Zone - 188
spc_H 232A Class C_0
Zone - 189
Zone - 189
spc_H 239 Class Office_0
Zone - 190
Zone - 190
spc_H 237 Office C_0
Zone - 191
Zone - 191
spc_H 236 Office C_0
Zone - 192
Zone - 192
spc_H 241 Class C_0
Zone - 193
Zone - 193
spc_H 309-318 Offices C_0
Zone - 194
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
555
555
1,686
1,686
1,686
272
272
272
1,065
1,065
1,065
267
267
267
4,126
4,126
4,126
2,482
2,482
2,482
1,805
1,805
1,805
4,564
4,564
4,564
1,111
1,111
1,111
306
306
306
90
90
90
272
272
272
571
571
571
1,012
1,012
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /17
7 /17
11 /13
11 /13
11 /14
11 /14
11 /14
11 /14
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
11 /14
76
76
75
75
75
71
71
71
73
73
73
73
73
73
79
79
79
75
75
75
76
76
76
77
77
77
76
76
76
77
77
77
75
75
75
75
75
75
76
76
76
73
73
66
66
66
66
66
58
58
58
60
60
60
60
60
60
64
64
64
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
60
60
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
346
346
2,157
2,157
2,157
798
798
798
3,496
3,496
3,496
765
765
765
1,412
1,412
1,412
2,382
2,382
2,382
1,127
1,127
1,127
3,577
3,577
3,577
693
693
693
311
311
311
48
48
48
145
145
145
356
356
356
4,319
4,319
5,987
5,987
37,265
37,265
37,265
13,783
13,783
13,783
60,401
60,401
60,401
13,211
13,211
13,211
24,400
24,400
24,400
41,156
41,156
41,156
19,474
19,474
19,474
61,807
61,807
61,807
11,982
11,982
11,982
5,382
5,382
5,382
828
828
828
2,500
2,500
2,500
6,155
6,155
6,155
74,623
74,623
1,944
1,944
5,523
5,523
5,523
89
89
89
766
766
766
192
192
192
3,332
3,332
3,332
8,130
8,130
8,130
6,325
6,325
6,325
15,809
15,809
15,809
3,891
3,891
3,891
1,060
1,060
1,060
238
238
238
719
719
719
1,999
1,999
1,999
728
728
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /14
9 /14
9 /15
9 /15
9 /15
9 /15
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /15
7 /15
9 /16
9 /16
7 /15
7 /15
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /15
77
77
77
77
77
77
77
77
78
78
78
78
78
78
77
77
77
76
76
76
77
77
77
77
77
77
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
78
78
67
67
67
67
67
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
331
331
2,071
2,071
2,071
743
743
743
2,999
2,999
2,999
665
665
665
1,401
1,401
1,401
2,313
2,313
2,313
1,078
1,078
1,078
3,577
3,577
3,577
663
663
663
311
311
311
47
47
47
142
142
142
341
341
341
3,657
3,657
6,204
6,204
40,964
40,964
40,964
15,383
15,383
15,383
74,566
74,566
74,566
13,581
13,581
13,581
25,840
25,840
25,840
45,783
45,783
45,783
20,181
20,181
20,181
67,488
67,488
67,488
12,417
12,417
12,417
5,994
5,994
5,994
871
871
871
2,628
2,628
2,628
6,379
6,379
6,379
87,004
87,004
Coil
Latent
Load
Btu/h
3,856
3,856
11,713
11,713
11,713
999
999
999
4,843
4,843
4,843
1,216
1,216
1,216
9,229
9,229
9,229
17,267
17,267
17,267
12,544
12,544
12,544
27,948
27,948
27,948
7,718
7,718
7,718
1,874
1,874
1,874
467
467
467
1,408
1,408
1,408
3,965
3,965
3,965
4,603
4,603
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 60 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 194
spc_H 240 Class C_0
Zone - 195
Zone - 195
spc_H 300 Restrooms C_0
Zone - 196
Zone - 196
spc_H 322 Office C_0
Zone - 197
Zone - 197
spc_H 323 Office C_0
Zone - 198
Zone - 198
spc_H 300H Hall C_0
Zone - 199
Zone - 199
spc_H 202 Class C_0
Zone - 200
Zone - 200
spc_H 205 Office C_0
Zone - 201
Zone - 201
spc_H 205/203 Class C_0
Zone - 202
Zone - 202
spc_H 232B Office C_0
Zone - 203
Zone - 203
spc_H 223 Class C_0
Zone - 204
Zone - 204
spc_H 223U Storage C_0
Zone - 205
Zone - 205
spc_H 306 Class C_0
Zone - 211
Zone - 211
spc_H 308 Class H_0
Zone - 212
Zone - 212
spc_H 301-307 Classes C_0
Zone - 213
Zone - 213
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,012
818
818
818
339
339
339
265
265
265
265
265
265
3,593
3,593
3,593
1,118
1,118
1,118
270
270
270
846
846
846
161
161
161
616
616
616
165
165
165
727
727
727
512
512
512
3,348
3,348
3,348
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
11 /14
7 /15
7 /15
9 /17
9 /17
11 /14
11 /14
7 /17
7 /17
10 /16
10 /16
8/10
8 /10
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /16
7 /16
7 /15
7 /15
73
77
77
77
76
76
76
73
73
73
75
75
75
79
79
79
67
67
67
75
75
75
76
76
76
75
75
75
76
76
76
77
77
77
76
76
76
76
76
76
77
77
77
60
66
66
66
67
67
67
60
60
60
66
66
66
64
64
64
61
61
61
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
4,319
642
642
642
542
542
542
1,069
1,069
1,069
141
141
141
3,898
3,898
3,898
2,401
2,401
2,401
144
144
144
528
528
528
86
86
86
385
385
385
51
51
51
454
454
454
320
320
320
2,748
2,748
2,748
74,623
11,100
11,100
11,100
14,193
14,193
14,193
18,478
18,478
18,478
2,434
2,434
2,434
67,353
67,353
67,353
41,487
41,487
41,487
2,483
2,483
2,483
9,121
9,121
9,121
1,483
1,483
1,483
6,648
6,648
6,648
876
876
876
7,841
7,841
7,841
5,526
5,526
5,526
47,476
47,476
47,476
728
2,834
2,834
2,834
619
619
619
190
190
190
700
700
700
9,908
9,908
9,908
3,433
3,433
3,433
714
714
714
2,962
2,962
2,962
426
426
426
2,159
2,159
2,159
250
250
250
2,546
2,546
2,546
1,795
1,795
1,795
11,597
11,597
11,597
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /15
7 /15
7 /15
9 /17
9 /17
9 /15
9 /15
9 /17
9 /17
9 /16
9 /16
9 /11
9 /11
9 /17
9 /17
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
9 /15
9 /15
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
78
77
77
77
76
76
76
78
78
78
76
76
76
77
77
77
70
70
70
76
76
76
77
77
77
76
76
76
77
77
77
78
78
78
76
76
76
76
76
76
76
76
76
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
63
63
63
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
3,657
642
642
642
210
210
210
890
890
890
138
138
138
3,839
3,839
3,839
2,239
2,239
2,239
141
141
141
505
505
505
84
84
84
368
368
368
47
47
47
441
441
441
311
311
311
2,733
2,733
2,733
87,004
12,091
12,091
12,091
14,647
14,647
14,647
21,157
21,157
21,157
2,558
2,558
2,558
126,357
126,357
126,357
45,716
45,716
45,716
2,609
2,609
2,609
9,452
9,452
9,452
1,558
1,558
1,558
6,890
6,890
6,890
878
878
878
19,161
19,161
19,161
13,504
13,504
13,504
102,755
102,755
102,755
Coil
Latent
Load
Btu/h
4,603
5,010
5,010
5,010
4,236
4,236
4,236
1,203
1,203
1,203
1,371
1,371
1,371
24,964
24,964
24,964
5,771
5,771
5,771
1,399
1,399
1,399
5,875
5,875
5,875
835
835
835
4,282
4,282
4,282
357
357
357
4,551
4,551
4,551
3,208
3,208
3,208
20,961
20,961
20,961
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 61 of 100
SPACE
System Zone Room
spc_H 301 Class C_0
Peak
Zone - 214
Peak
Zone - 214
Block
spc_H 3281 Hall C_0
Peak
Zone - 215
Peak
Zone - 215
Block
Humanities VAV
Peak
Humanities VAV
Block
spc_IDC 335 Office C_0
Peak
Zone - 220
Peak
Zone - 220
Block
spc_IDC 313 Wrk Rm_0
Peak
Zone - 221
Peak
Zone - 221
Block
spc_IDC 317 Wrk Rm C_0
Peak
Zone - 222
Peak
Zone - 222
Block
spc_IDC 329 C_0
Peak
Zone - 223
Peak
Zone - 223
Block
IDC Fan Coil
Peak
IDC Fan Coil
Block
Peak
spc_IDC 102/103/104/109 Int Class_0
Zone - 216
Peak
Zone - 216
Block
spc_IDC 205 Class C_0
Peak
Zone - 217
Peak
Zone - 217
Block
spc_IDC 211/210 Class_0
Peak
Zone - 218
Peak
Zone - 218
Block
spc_IDC 333 Office_0
Peak
Zone - 219
Peak
Zone - 219
Block
IDC VAV
Peak
IDC VAV
Block
spc_LRC 140-01-08 C_0
Peak
Zone - 224
Peak
Zone - 224
Block
spc_LRC 140-09 C_0
Peak
Zone - 225
Peak
Zone - 225
Block
spc_LRC 13-15 C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
633
633
633
228
228
228
42,441
42,441
107
107
107
206
206
206
171
171
171
102
102
102
586
586
3,318
3,318
3,318
460
460
460
1,001
1,001
1,001
414
414
414
5,194
5,194
1,843
1,843
1,843
250
250
250
153
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
10 /15
7 /17
7 /17
7 /16
7 /16
7 /16
7/16
7 /16
7 /16
7 /16
10 /15
10 /15
10 /15
10 /15
10 /15
10 /15
10 /17
10 /17
10 /15
6 /10
6 /10
9 /12
9 /12
9 /11
76
76
76
76
76
76
80
80
75
75
75
76
76
76
76
76
76
76
76
76
76
76
80
80
80
80
80
80
80
80
80
77
77
77
80
80
65
65
65
73
73
73
70
66
66
66
66
66
66
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
63
63
63
63
63
63
64
64
64
63
63
58
58
58
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.1
72.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
395
395
395
53
53
53
41,826
37,423
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,694
1,694
1,694
859
859
859
511
511
511
180
180
180
3,244
3,237
1,595
1,595
1,595
797
797
797
632
6,823
6,823
6,823
911
911
911
727,491
650,911
1,280
1,280
1,280
2,975
2,975
2,975
2,627
2,627
2,627
1,357
1,357
1,357
8,239
8,216
32,706
32,706
32,706
16,577
16,577
16,577
9,869
9,869
9,869
3,472
3,472
3,472
62,624
62,481
28,266
28,266
28,266
14,118
14,118
14,118
11,205
2,216
2,216
2,216
354
354
354
122,518
95,452
284
284
284
722
722
722
600
600
600
357
357
357
1,962
1,958
8,526
8,526
8,526
1,182
1,182
1,182
2,573
2,573
2,573
855
855
855
13,135
12,972
5,957
5,957
5,957
915
915
915
580
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
9 /16
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
7 /16
7 /16
9 /13
9 /13
9 /11
76
76
76
76
76
76
77
77
75
75
75
76
76
76
76
76
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
75
75
75
77
77
76
76
76
75
75
75
70
66
66
66
66
66
66
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
66
66
66
65
65
65
63
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
384
384
384
49
49
49
39,362
36,284
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,668
1,668
1,668
843
843
843
503
503
503
179
179
179
3,194
3,189
1,448
1,448
1,448
757
757
757
632
16,673
16,673
16,673
4,252
4,252
4,252
957,271
890,214
2,183
2,183
2,183
4,555
4,555
4,555
3,950
3,950
3,950
2,128
2,128
2,128
12,817
12,798
38,524
38,524
38,524
19,698
19,698
19,698
11,625
11,625
11,625
10,755
10,755
10,755
80,821
79,588
54,618
54,618
54,618
17,332
17,332
17,332
12,865
3,960
3,960
3,960
448
448
448
249,846
272,391
488
488
488
1,291
1,291
1,291
1,072
1,072
1,072
638
638
638
3,490
3,478
23,156
23,156
23,156
3,209
3,209
3,209
6,987
6,987
6,987
1,894
1,894
1,894
35,247
35,420
12,597
12,597
12,597
1,569
1,569
1,569
880
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 62 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 226
Zone - 226
spc_LRC 16 C_0
Zone - 227
Zone - 227
spc_LRC 17/18_0
Zone - 228
Zone - 228
spc_LRC 5 C (Study?)_0
Zone - 229
Zone - 229
spc_LRC 9 Storage_0
Zone - 230
Zone - 230
spc_LRC 10 Storage_0
Zone - 231
Zone - 231
spc_LRC 7 C_0
Zone - 232
Zone - 232
spc_LRC 8 Stair_0
Zone - 233
Zone - 233
spc_LRC Catalog C_0
Zone - 234
Zone - 234
spc_LRC Computer_0
Zone - 235
Zone - 235
spc_LRC 2/6_0
Zone - 236
Zone - 236
spc_LRC 1st RR C_0
Zone - 237
Zone - 237
spc_LRC 24_0
Zone - 238
Zone - 238
spc_LRC 25_0
Zone - 239
Zone - 239
spc_LRC 105 C Work_0
Zone - 240
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
153
153
66
66
66
94
94
94
57
57
57
29
29
29
24
24
24
119
119
119
302
302
302
56
56
56
525
525
525
137
137
137
226
226
226
564
564
564
325
325
325
62
62
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
10 /13
10 /13
10 /16
10 /16
7 /15
7 /15
7 /15
7 /15
6 /10
6/10
6 /18
6 /18
7 /18
7 /18
7 /18
7 /18
6 /17
6 /17
7 /15
7 /15
10 /16
10/16
10 /16
10 /16
7 /18
7 /18
7 /18
70
70
77
77
77
79
79
79
77
77
77
77
77
77
65
65
65
70
70
70
73
73
73
73
73
73
72
72
72
77
77
77
79
79
79
79
79
79
73
73
73
73
73
63
63
59
59
59
64
64
64
66
66
66
66
66
66
58
58
58
63
63
63
65
65
65
65
65
65
63
63
63
66
66
66
64
64
64
64
64
64
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
632
632
296
296
296
800
800
800
34
34
34
9
9
9
43
43
43
499
499
499
178
178
178
119
119
119
1,809
1,809
1,809
78
78
78
362
362
362
2,024
2,024
2,024
956
956
956
123
123
11,205
11,205
5,239
5,239
5,239
14,180
14,180
14,180
606
606
606
156
156
156
770
770
770
8,836
8,836
8,836
3,148
3,148
3,148
2,112
2,112
2,112
32,061
32,061
32,061
1,384
1,384
1,384
9,633
9,633
9,633
35,871
35,871
35,871
16,939
16,939
16,939
2,178
2,178
580
580
159
159
159
316
316
316
196
196
196
44
44
44
16
16
16
366
366
366
460
460
460
226
226
226
1,210
1,210
1,210
556
556
556
181
181
181
1,890
1,890
1,890
1,302
1,302
1,302
214
214
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /13
9 /13
9 /16
9 /16
9 /16
9 /16
9 /15
9 /15
6 /10
6 /10
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /16
9 /16
7 /18
7 /18
7 /18
70
70
75
75
75
77
77
77
77
77
77
78
78
78
65
65
65
73
73
73
73
73
73
73
73
73
75
75
75
77
77
77
79
79
79
77
77
77
73
73
73
73
73
63
63
65
65
65
67
67
67
67
67
67
66
66
66
58
58
58
65
65
65
65
65
65
65
65
65
66
66
66
67
67
67
64
64
64
67
67
67
65
65
65
65
65
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
632
632
289
289
289
781
781
781
34
34
34
8
8
8
43
43
43
495
495
495
178
178
178
119
119
119
1,791
1,791
1,791
77
77
77
186
186
186
1,981
1,981
1,981
956
956
956
123
123
12,865
12,865
5,989
5,989
5,989
15,724
15,724
15,724
602
602
602
149
149
149
999
999
999
9,606
9,606
9,606
3,388
3,388
3,388
2,494
2,494
2,494
34,140
34,140
34,140
1,369
1,369
1,369
8,860
8,860
8,860
39,177
39,177
39,177
19,463
19,463
19,463
3,446
3,446
Coil
Latent
Load
Btu/h
880
880
417
417
417
710
710
710
392
392
392
63
63
63
19
19
19
757
757
757
592
592
592
392
392
392
2,556
2,556
2,556
1,032
1,032
1,032
996
996
996
4,243
4,243
4,243
2,256
2,256
2,256
397
397
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 63 of 100
SPACE
System Zone Room
Zone - 240
Block
spc_LRC Tables/124B C_0
Peak
Zone - 241
Peak
Zone - 241
Block
spc_LRC 120/122/123 Office C_0 Peak
Zone - 242
Peak
Zone - 242
Block
spc_LRC Tutor Lab C_0
Peak
Zone - 243
Peak
Zone - 243
Block
spc_LRC Lobby/112B Corridor C_0Peak
Zone - 244
Peak
Zone - 244
Block
spc_LRC Dir Offc C_0
Peak
Zone - 245
Peak
Zone - 245
Block
spc_LRC 108/111/115 Counter_0 Peak
Zone - 246
Peak
Zone - 246
Block
spc_LRC 149A_0
Peak
Zone - 247
Peak
Zone - 247
Block
spc_LRC 137 Work C_0
Peak
Zone - 248
Peak
Zone - 248
Block
spc_LRC 140-142 Director_0
Peak
Zone - 249
Peak
Zone - 249
Block
spc_LRC 145 Office C_0
Peak
Zone - 250
Peak
Zone - 250
Block
spc_LRC 146A Storage_0
Peak
Zone - 251
Peak
Zone - 251
Block
spc_LRC 146_0
Peak
Zone - 252
Peak
Zone - 252
Block
spc_LRC Library_0
Peak
Zone - 253
Peak
Zone - 253
Block
spc_LRC 140-14_0
Peak
Zone - 254
Peak
Zone - 254
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
62
647
647
647
58
58
58
63
63
63
582
582
582
36
36
36
335
335
335
25
25
25
59
59
59
38
38
38
23
23
23
14
14
14
80
80
80
0
0
0
42
42
42
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
10 /15
10 /15
6 /11
6 /11
7 /15
7 /15
7 /18
7 /18
6 /18
6 /18
7/15
7 /15
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
10 /13
10 /13
11 /12
11 /12
9 /12
9 /12
73
80
80
80
68
68
68
77
77
77
73
73
73
70
70
70
77
77
77
73
73
73
73
73
73
75
75
75
75
75
75
79
79
79
77
77
77
68
68
68
73
73
73
65
63
63
63
60
60
60
66
66
66
65
65
65
63
63
63
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
64
64
64
59
59
59
55
55
55
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
123
1,184
1,184
1,184
119
119
119
110
110
110
387
387
387
147
147
147
191
191
191
45
45
45
191
191
191
20
20
20
12
12
12
64
64
64
252
252
252
2,551
2,551
2,551
190
190
190
2,178
20,983
20,983
20,983
2,116
2,116
2,116
1,946
1,946
1,946
6,866
6,866
6,866
2,614
2,614
2,614
3,378
3,378
3,378
793
793
793
3,381
3,381
3,381
359
359
359
214
214
214
1,140
1,140
1,140
4,464
4,464
4,464
45,210
45,210
45,210
3,371
3,371
3,371
214
1,652
1,652
1,652
103
103
103
180
180
180
975
975
975
72
72
72
1,358
1,358
1,358
86
86
86
204
204
204
101
101
101
60
60
60
11
11
11
192
192
192
0
0
0
154
154
154
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /18
9 /16
9 /16
7 /12
7 /12
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
9 /14
9 /14
9 /11
9 /11
9 /12
9 /12
73
77
77
77
73
73
73
76
76
76
75
75
75
73
73
73
76
76
76
73
73
73
73
73
73
75
75
75
75
75
75
76
76
76
77
77
77
70
70
70
73
73
73
65
67
67
67
63
63
63
66
66
66
66
66
66
65
65
65
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
67
67
67
66
66
66
63
63
63
63
63
63
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
123
1,113
1,113
1,113
117
117
117
110
110
110
364
364
364
145
145
145
190
190
190
45
45
45
191
191
191
20
20
20
12
12
12
63
63
63
233
233
233
2,488
2,488
2,488
190
190
190
3,446
32,086
32,086
32,086
2,850
2,850
2,850
2,980
2,980
2,980
14,670
14,670
14,670
3,509
3,509
3,509
8,372
8,372
8,372
1,278
1,278
1,278
4,731
4,731
4,731
936
936
936
559
559
559
1,612
1,612
1,612
5,818
5,818
5,818
47,040
47,040
47,040
4,151
4,151
4,151
Coil
Latent
Load
Btu/h
397
4,480
4,480
4,480
178
178
178
312
312
312
1,365
1,365
1,365
155
155
155
2,288
2,288
2,288
159
159
159
378
378
378
174
174
174
104
104
104
35
35
35
535
535
535
0
0
0
223
223
223
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 64 of 100
SPACE
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
System Zone Room
Floor
Area
ft²
spc_LRC 140-03_0
Peak
Zone - 255
Peak
Zone - 255
Block
spc_LRC 101 Work C_0
Peak
Zone - 256
Peak
Zone - 256
Block
spc_LRC 108-110 Storage_0
Peak
Zone - 257
Peak
Zone - 257
Block
spc_LRC 109 Work_0
Peak
Zone - 258
Peak
Zone - 258
Block
LRC VAV
Peak
LRC VAV
Block
spc_OE 10WM Restrooms AH-2_0Peak
Zone - 259
Peak
Zone - 259
Block
spc_OE 112 Class C_0
Peak
Zone - 260
Peak
Zone - 260
Block
spc_OE 116 Class C_0
Peak
Zone - 261
Peak
Zone - 261
Block
spc_OE 180H/182 Class C_0
Peak
Zone - 262
Peak
Zone - 262
Block
spc_OE 180A Office C_0
Peak
Zone - 263
Peak
Zone - 263
Block
OE Pckg AH
Peak
OE Pckg AH
Block
spc_PE 108 Weight Rm HP3/4_0 Peak
Zone - 006
Peak
Zone - 006
Block
spc_PE Locker/RR HP-06/07_0 Peak
Zone - 008
Peak
Zone - 008
Block
Peak
spc_PE 302-310E Office Partially C_0
Zone - 011
Peak
Zone - 011
Block
PE Heat Pump
Peak
PE Heat Pump
Block
spc_PE Gym AH1_0
Peak
86
6 /10
86
86
6 /10
62
9 /17
62
62
9 /17
24
7 /15
24
24
7 /15
43
9 /17
43
43
9 /17
7,052
7,052
9 /16
172
7 /18
172
172
7/18
522 10 /15
522
522 10 /15
1,121 7 /18
1,121
1,121 7 /18
509
9 /11
509
509
9 /11
66
7 /17
66
66
7 /17
2,391
2,391 10 /14
3,594 9 /10
3,594
3,594 9 /10
1,968 7 /18
1,968
1,968 7 /18
498
7 /18
498
498
7 /18
6,061
6,061
7 /18
7,524
7 /17
Project Name:
Dataset Name:
SBCC TRACE.TRC
65
65
65
76
76
76
77
77
77
76
76
76
77
77
73
73
73
80
80
80
73
73
73
70
70
70
75
75
75
79
79
67
67
67
73
73
73
73
73
73
73
73
75
58
58
58
67
67
67
66
66
66
67
67
67
67
67
65
65
65
63
63
63
65
65
65
63
63
63
66
66
66
62
62
61
61
61
65
65
65
65
65
65
65
65
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.2
72.2
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.7
72.7
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
76.0
76.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
73.2
73.2
73.2
56.6
56.6
56.6
52.2
52.2
52.2
55.6
55.6
55.6
48.8
48.8
48.8
56.4
56.4
54.5
54.5
54.5
74.3
74.3
74.3
56.3
56.3
56.3
64.7
64.7
72.4
207
207
207
186
186
186
7
7
7
143
143
143
16,361
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
3,150
3,150
1,009
1,009
1,009
6,278
6,278
1,505
3,672
3,672
3,672
3,302
3,302
3,302
123
123
123
2,540
2,540
2,540
293,173
232,240
2,089
2,089
2,089
17,559
17,559
17,559
20,357
20,357
20,357
17,712
17,712
17,712
589
589
589
58,307
44,634
41,395
41,395
41,395
19,874
19,874
19,874
17,669
17,669
17,669
78,937
60,043
-636
277
277
277
218
218
218
36
36
36
152
152
152
20,421
25,647
59
59
59
1,340
1,340
1,340
3,874
3,874
3,874
1,628
1,628
1,628
176
176
176
7,077
4,708
4,036
4,036
4,036
668
668
668
1,173
1,173
1,173
5,877
7,430
-4,539
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
9 /17
9 /17
7 /16
7 /16
9 /17
9 /17
9 /16
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
9 /13
9 /13
7 /17
7 /17
9 /16
9 /13
9 /13
9 /17
9 /17
7 /18
7 /18
9 /17
7 /14
75
75
75
76
76
76
76
76
76
76
76
76
77
77
76
76
76
77
77
77
73
73
73
75
75
75
75
75
75
77
77
75
75
75
76
76
76
73
73
73
76
76
76
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
66
67
67
65
65
65
67
67
67
65
65
65
67
67
65
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
76.2
76.2
76.2
57.4
57.4
57.4
52.2
52.2
52.2
57.4
57.4
57.4
48.8
48.8
48.8
57.5
60.7
57.2
57.2
57.2
75.4
75.4
75.4
56.3
56.3
56.3
66.2
68.1
72.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
164
164
164
186
186
186
7
7
7
143
143
143
15,679
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
3,150
3,150
1,009
1,009
1,009
6,278
6,278
451
4,618
4,618
4,618
4,899
4,899
4,899
475
475
475
3,755
3,755
3,755
382,332
328,402
2,439
2,439
2,439
21,294
21,294
21,294
23,315
23,315
23,315
22,689
22,689
22,689
1,667
1,667
1,667
71,405
61,879
36,526
36,526
36,526
36,640
36,640
36,640
27,335
27,335
27,335
100,501
80,404
-191
Coil
Latent
Load
Btu/h
569
569
569
432
432
432
50
50
50
300
300
300
41,604
50,410
755
755
755
3,639
3,639
3,639
7,205
7,205
7,205
2,921
2,921
2,921
304
304
304
14,824
15,804
19,890
19,890
19,890
8,557
8,557
8,557
2,160
2,160
2,160
30,607
29,879
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 65 of 100
SPACE
System Zone Room
Zone - 001
Peak
Zone - 001
Block
spc_PE Team Lockey RH4_0
Peak
Zone - 002
Peak
Zone - 002
Block
spc_PE 113 RH7/RH8_0
Peak
Zone - 003
Peak
Zone - 003
Block
spc_PE 114 C_0
Peak
Zone - 004
Peak
Zone - 004
Block
spc_PE 109 NC_0
Peak
Zone - 005
Peak
Zone - 005
Block
spc_PE 2nd Flr Lobby_0
Peak
Zone - 007
Peak
Zone - 007
Block
Peak
spc_PE 214-218, 201-203 Offices C_0
Zone - 009
Peak
Zone - 009
Block
spc_PE 3 Press Box RH02 _0
Peak
Zone - 010
Peak
Zone - 010
Block
PE VAV Htg Only
Peak
PE VAV Htg Only
Block
spc_sp_55
Peak
Zone - 264
Peak
Zone - 264
Block
spc_sp_56
Peak
Zone - 265
Peak
Zone - 265
Block
spc_sp_57
Peak
Zone - 266
Peak
Zone - 266
Block
spc_sp_58
Peak
Zone - 267
Peak
Zone - 267
Block
spc_sp_59
Peak
Zone - 268
Peak
Zone - 268
Block
spc_sp_60
Peak
Zone - 269
Peak
Zone - 269
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
7,524
7,524
744
744
744
1,696
1,696
1,696
1,001
1,001
1,001
683
683
683
7,013
7,013
7,013
1,922
1,922
1,922
174
174
174
20,757
20,757
1,130
1,130
1,130
1,130
1,130
1,130
1,159
1,159
1,159
1,087
1,087
1,087
396
396
396
828
828
828
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
10 /16
10 /16
9 /16
9 /16
9 /10
9 /10
10 /15
10 /15
7 /10
7 /10
7/18
7 /18
10 /16
10 /16
7 /17
10 /13
10 /13
10 /15
10 /15
9 /12
9 /12
10 /16
10 /16
11 /15
11 /15
7 /18
7 /18
75
75
79
79
79
77
77
77
67
67
67
80
80
80
67
67
67
73
73
73
79
79
79
75
75
77
77
77
80
80
80
73
73
73
79
79
79
73
73
73
73
73
73
66
66
64
64
64
67
67
67
61
61
61
63
63
63
60
60
60
65
65
65
64
64
64
66
66
59
59
59
63
63
63
63
63
63
64
64
64
62
62
62
65
65
65
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
74.4
74.4
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
58.6
58.6
58.6
55.9
55.9
55.9
54.6
54.6
54.6
56.3
56.3
56.3
58.2
58.2
58.2
54.7
54.7
54.7
1,505
1,505
1,190
1,190
1,190
339
339
339
200
200
200
137
137
137
351
351
351
256
256
256
23
23
23
4,001
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
-636
-636
10,111
10,111
10,111
-143
-143
-143
-85
-85
-85
-58
-58
-58
-148
-148
-148
-108
-108
-108
-10
-10
-10
8,923
0
25,370
25,370
25,370
30,201
30,201
30,201
29,008
29,008
29,008
37,550
37,550
37,550
33,464
33,464
33,464
25,783
25,783
25,783
-4,539
-4,539
-971
-971
-971
2,691
2,691
2,691
1,039
1,039
1,039
306
306
306
-8,532
-8,532
-8,532
454
454
454
-45
-45
-45
-9,597
-3,178
2,062
2,062
2,062
2,910
2,910
2,910
3,573
3,573
3,573
3,013
3,013
3,013
1,051
1,051
1,051
2,864
2,864
2,864
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /14
9 /16
9 /16
9 /16
9 /16
9 /10
9 /10
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
7 /17
9 /14
9 /14
9 /16
9 /16
9 /14
9 /14
9 /16
9 /16
10 /15
10 /15
7 /18
7 /18
76
76
77
77
77
77
77
77
67
67
67
77
77
77
75
75
75
75
75
75
76
76
76
75
75
77
77
77
77
77
77
77
77
77
77
77
77
80
80
80
73
73
73
65
65
67
67
67
67
67
67
61
61
61
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
67
67
67
66
66
66
67
67
67
63
63
63
65
65
65
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
59.2
59.2
59.2
56.9
56.9
56.9
55.6
55.6
55.6
56.5
56.5
56.5
58.3
58.3
58.3
54.7
54.7
54.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
451
451
357
357
357
102
102
102
60
60
60
41
41
41
105
105
105
77
77
77
7
7
7
1,200
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
-191
-191
3,033
3,033
3,033
-43
-43
-43
-25
-25
-25
-17
-17
-17
-44
-44
-44
-32
-32
-32
-3
-3
-3
12,882
0
36,547
36,547
36,547
44,525
44,525
44,525
40,050
40,050
40,050
54,574
54,574
54,574
40,936
40,936
40,936
38,829
38,829
38,829
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6,959
6,959
6,959
7,908
7,908
7,908
7,147
7,147
7,147
7,605
7,605
7,605
1,195
1,195
1,195
5,336
5,336
5,336
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 66 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_61
Zone - 270
Zone - 270
spc_sp_62
Zone - 271
Zone - 271
spc_sp_63
Zone - 272
Zone - 272
spc_sp_64
Zone - 273
Zone - 273
spc_sp_65
Zone - 274
Zone - 274
spc_sp_66
Zone - 275
Zone - 275
spc_sp_67
Zone - 276
Zone - 276
spc_sp_68
Zone - 277
Zone - 277
spc_sp_69
Zone - 278
Zone - 278
spc_sp_70
Zone - 279
Zone - 279
spc_sp_38
Zone - 280
Zone - 280
spc_sp_39
Zone - 281
Zone - 281
spc_sp_40
Zone - 282
Zone - 282
spc_sp_41
Zone - 283
Zone - 283
spc_sp_42
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
378
9 /11
378
378
9 /11
485
6 /10
485
485
6 /10
678 10 /16
678
678 10 /16
822
7 /18
822
822
7 /18
628
9 /11
628
628
9 /11
2,082 9 /16
2,082
2,082 9 /16
2,169 7 /17
2,169
2,169 7 /17
2,777 7 /17
2,777
2,777 7 /17
3,084 7 /17
3,084
3,084 7 /17
211
6 /10
211
211
6 /10
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
1,408 9 /16
1,408
1,408 9 /16
1,392 9 /16
1,392
1,392
9 /16
972
9 /16
70
70
70
65
65
65
79
79
79
73
73
73
70
70
70
77
77
77
75
75
75
75
75
75
75
75
75
65
65
65
77
77
77
77
77
77
77
77
77
77
77
77
77
63
63
63
58
58
58
64
64
64
65
65
65
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.5
57.5
57.5
55.5
55.5
55.5
56.3
56.3
56.3
51.4
51.4
51.4
56.1
56.1
56.1
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.5
52.5
52.5
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
28,760
28,760
28,760
11,994
11,994
11,994
23,923
23,923
23,923
13,067
13,067
13,067
26,223
26,223
26,223
53,398
53,398
53,398
48,975
48,975
48,975
57,415
57,415
57,415
55,454
55,454
55,454
13,285
13,285
13,285
28,858
28,858
28,858
28,858
28,858
28,858
35,056
35,056
35,056
34,765
34,765
34,765
27,232
1,212
1,212
1,212
1,286
1,286
1,286
1,878
1,878
1,878
2,838
2,838
2,838
2,011
2,011
2,011
7,723
7,723
7,723
7,128
7,128
7,128
9,122
9,122
9,122
10,121
10,121
10,121
559
559
559
3,036
3,036
3,036
3,036
3,036
3,036
5,223
5,223
5,223
5,163
5,163
5,163
3,608
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
9 /12
9 /12
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
70
70
70
76
76
76
77
77
77
75
75
75
73
73
73
77
77
77
75
75
75
75
75
75
76
76
76
65
65
65
77
77
77
77
77
77
77
77
77
77
77
77
77
63
63
63
66
66
66
67
67
67
66
66
66
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
57.5
57.5
57.5
58.6
58.6
58.6
56.4
56.4
56.4
51.9
51.9
51.9
56.2
56.2
56.2
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.7
52.7
52.7
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
32,826
32,826
32,826
16,489
16,489
16,489
33,562
33,562
33,562
23,710
23,710
23,710
32,978
32,978
32,978
80,411
80,411
80,411
79,136
79,136
79,136
95,193
95,193
95,193
95,526
95,526
95,526
14,677
14,677
14,677
41,068
41,068
41,068
41,068
41,068
41,068
53,076
53,076
53,076
52,584
52,584
52,584
39,863
Coil
Latent
Load
Btu/h
1,973
1,973
1,973
3,057
3,057
3,057
4,742
4,742
4,742
5,052
5,052
5,052
3,012
3,012
3,012
14,541
14,541
14,541
13,382
13,382
13,382
17,116
17,116
17,116
19,369
19,369
19,369
694
694
694
5,720
5,720
5,720
5,720
5,720
5,720
9,832
9,832
9,832
9,719
9,719
9,719
6,796
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 67 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 284
Zone - 284
spc_sp_43
Zone - 285
Zone - 285
spc_sp_44
Zone - 286
Zone - 286
spc_sp_45
Zone - 287
Zone - 287
spc_sp_46
Zone - 288
Zone - 288
spc_sp_47
Zone - 289
Zone - 289
spc_sp_48
Zone - 290
Zone - 290
spc_sp_49
Zone - 291
Zone - 291
spc_sp_50
Zone - 292
Zone - 292
spc_sp_51
Zone - 293
Zone - 293
spc_sp_52
Zone - 294
Zone - 294
spc_sp_53
Zone - 295
Zone - 295
spc_sp_54
Zone - 296
Zone - 296
spc_sp_22
Zone - 297
Zone - 297
spc_sp_23
Zone - 298
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
972
972
1,408
1,408
1,408
826
826
826
914
914
914
907
907
907
869
869
869
869
869
869
835
835
835
893
893
893
737
737
737
1,061
1,061
1,061
1,064
1,064
1,064
1,061
1,061
1,061
1,044
1,044
1,044
1,082
1,082
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /15
9 /16
9 /16
9 /16
9 /16
7 /18
7 /18
7 /18
7/18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
10 /13
10 /13
10 /13
10 /13
9 /12
9 /12
7 /18
7 /18
7 /18
77
77
80
80
80
77
77
77
77
77
77
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
77
77
77
77
77
77
73
73
73
73
73
73
73
73
67
67
63
63
63
67
67
67
67
67
67
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
59
59
59
59
59
59
63
63
63
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.0
54.0
56.0
56.0
56.0
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
53.9
53.9
53.9
54.1
54.1
54.1
54.2
54.2
54.2
54.0
54.0
54.0
55.0
55.0
55.0
58.7
58.7
58.7
58.7
58.7
58.7
54.7
54.7
54.7
53.1
53.1
53.1
53.4
53.4
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
27,232
27,232
38,302
38,302
38,302
27,994
27,994
27,994
26,885
26,885
26,885
25,235
25,235
25,235
22,064
22,064
22,064
22,983
22,983
22,983
22,536
22,536
22,536
23,576
23,576
23,576
24,944
24,944
24,944
24,323
24,323
24,323
24,374
24,374
24,374
27,301
27,301
27,301
22,248
22,248
22,248
24,586
24,586
3,608
3,608
3,626
3,626
3,626
3,067
3,067
3,067
3,393
3,393
3,393
3,140
3,140
3,140
3,008
3,008
3,008
3,009
3,009
3,009
2,891
2,891
2,891
3,092
3,092
3,092
2,553
2,553
2,553
1,935
1,935
1,935
1,941
1,941
1,941
3,272
3,272
3,272
3,609
3,609
3,609
3,741
3,741
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
9 /14
9 /14
9 /14
9 /14
9 /14
9 /14
7 /17
7 /17
7 /17
77
77
77
77
77
77
77
77
77
77
77
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
77
77
77
77
77
77
77
77
77
75
75
75
75
75
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
54.0
54.0
56.2
56.2
56.2
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
54.1
54.1
54.1
54.2
54.2
54.2
54.3
54.3
54.3
54.2
54.2
54.2
55.0
55.0
55.0
59.2
59.2
59.2
59.2
59.2
59.2
55.7
55.7
55.7
53.6
53.6
53.6
53.6
53.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
39,863
39,863
56,744
56,744
56,744
39,442
39,442
39,442
38,892
38,892
38,892
38,103
38,103
38,103
33,592
33,592
33,592
34,897
34,897
34,897
34,003
34,003
34,003
35,816
35,816
35,816
36,470
36,470
36,470
34,741
34,741
34,741
34,831
34,831
34,831
37,314
37,314
37,314
35,254
35,254
35,254
38,640
38,640
Coil
Latent
Load
Btu/h
6,796
6,796
9,854
9,854
9,854
5,777
5,777
5,777
6,391
6,391
6,391
5,604
5,604
5,604
5,367
5,367
5,367
5,370
5,370
5,370
5,157
5,157
5,157
5,519
5,519
5,519
4,557
4,557
4,557
6,531
6,531
6,531
6,553
6,553
6,553
6,544
6,544
6,544
6,433
6,433
6,433
6,671
6,671
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 68 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 298
spc_sp_24
Zone - 299
Zone - 299
spc_sp_25
Zone - 300
Zone - 300
spc_sp_26
Zone - 301
Zone - 301
spc_sp_27
Zone - 302
Zone - 302
spc_sp_28
Zone - 303
Zone - 303
spc_sp_29
Zone - 304
Zone - 304
spc_sp_30
Zone - 305
Zone - 305
spc_sp_31
Zone - 306
Zone - 306
spc_sp_32
Zone - 307
Zone - 307
spc_sp_33
Zone - 308
Zone - 308
spc_sp_34
Zone - 309
Zone - 309
spc_sp_35
Zone - 310
Zone - 310
spc_sp_36
Zone - 311
Zone - 311
spc_sp_37
Zone - 312
Zone - 312
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
1,082
7 /18
1,074
7 /18
1,074
1,074
7 /18
955
7 /18
955
955
7 /18
995
9 /16
995
995
9 /16
894
7 /17
894
894
7 /17
1,063 10 /15
1,063
1,063 10 /15
684
6/10
684
684
6 /10
2,070 9 /16
2,070
2,070 9 /16
1,251 9 /16
1,251
1,251 9 /16
1,251 7 /17
1,251
1,251 7 /17
1,525 9 /16
1,525
1,525 9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
73
73
73
73
73
73
73
77
77
77
75
75
75
80
80
80
65
65
65
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
65
65
65
65
65
65
65
67
67
67
66
66
66
63
63
63
58
58
58
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
53.4
53.1
53.1
53.1
53.6
53.6
53.6
55.1
55.1
55.1
55.0
55.0
55.0
56.6
56.6
56.6
55.8
55.8
55.8
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
24,586
22,945
22,945
22,945
22,834
22,834
22,834
37,026
37,026
37,026
29,118
29,118
29,118
36,090
36,090
36,090
18,202
18,202
18,202
52,942
52,942
52,942
35,189
35,189
35,189
31,103
31,103
31,103
60,677
60,677
60,677
29,082
29,082
29,082
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
3,741
3,711
3,711
3,711
3,304
3,304
3,304
3,697
3,697
3,697
2,943
2,943
2,943
2,737
2,737
2,737
1,813
1,813
1,813
7,679
7,679
7,679
4,645
4,645
4,645
4,115
4,115
4,115
5,660
5,660
5,660
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
75
75
75
75
75
75
75
77
77
77
75
75
75
77
77
77
76
76
76
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
66
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
53.6
53.6
53.6
53.6
53.9
53.9
53.9
55.1
55.1
55.1
55.0
55.0
55.0
56.7
56.7
56.7
60.6
60.6
60.6
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
38,640
36,369
36,369
36,369
35,270
35,270
35,270
51,628
51,628
51,628
42,996
42,996
42,996
51,414
51,414
51,414
22,226
22,226
22,226
79,873
79,873
79,873
52,725
52,725
52,725
48,027
48,027
48,027
82,120
82,120
82,120
41,372
41,372
41,372
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
Coil
Latent
Load
Btu/h
6,671
6,615
6,615
6,615
5,894
5,894
5,894
6,966
6,966
6,966
5,530
5,530
5,530
7,439
7,439
7,439
4,311
4,311
4,311
14,458
14,458
14,458
8,749
8,749
8,749
7,730
7,730
7,730
10,664
10,664
10,664
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 69 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_7
Zone - 313
Zone - 313
spc_sp_8
Zone - 314
Zone - 314
spc_sp_9
Zone - 315
Zone - 315
spc_sp_10
Zone - 316
Zone - 316
spc_sp_11
Zone - 317
Zone - 317
spc_sp_12
Zone - 318
Zone - 318
spc_sp_13
Zone - 319
Zone - 319
spc_sp_14
Zone - 320
Zone - 320
spc_sp_15
Zone - 321
Zone - 321
spc_sp_16
Zone - 322
Zone - 322
spc_sp_17
Zone - 323
Zone - 323
spc_sp_18
Zone - 324
Zone - 324
spc_sp_19
Zone - 325
Zone - 325
spc_sp_20
Zone - 326
Zone - 326
spc_sp_21
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
290
290
290
442
442
442
2,070
2,070
2,070
1,103
1,103
1,103
915
915
915
3,084
3,084
3,084
437
437
437
344
344
344
231
231
231
382
382
382
358
358
358
1,082
1,082
1,082
960
960
960
1,040
1,040
1,040
1,040
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
6 /18
6 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
6 /18
6 /18
7 /18
7 /18
9 /12
9 /12
6 /10
6 /10
6 /9
6 /9
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
70
70
70
70
70
70
75
75
75
76
76
76
76
76
76
75
75
75
70
70
70
73
73
73
73
73
73
65
65
65
62
62
62
73
73
73
73
73
73
73
73
73
73
63
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
65
65
65
63
63
63
58
58
58
58
58
58
65
65
65
65
65
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.0
57.0
57.0
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
56.2
56.2
56.2
56.0
56.0
56.0
53.0
53.0
53.0
53.2
53.2
53.2
54.2
54.2
54.2
53.1
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
17,557
17,557
17,557
19,208
19,208
19,208
47,533
47,533
47,533
12,788
12,788
12,788
10,607
10,607
10,607
60,225
60,225
60,225
28,451
28,451
28,451
19,387
19,387
19,387
8,323
8,323
8,323
11,887
11,887
11,887
10,175
10,175
10,175
22,813
22,813
22,813
20,987
20,987
20,987
28,726
28,726
28,726
22,182
929
929
929
1,375
1,375
1,375
6,804
6,804
6,804
3,865
3,865
3,865
3,206
3,206
3,206
10,127
10,127
10,127
1,358
1,358
1,358
1,192
1,192
1,192
713
713
713
1,013
1,013
1,013
951
951
951
3,739
3,739
3,739
3,318
3,318
3,318
3,598
3,598
3,598
3,594
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /12
9 /12
7 /18
7 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /12
9 /12
7 /15
7 /15
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
73
73
73
73
73
73
75
75
75
76
76
76
76
76
76
75
75
75
73
73
73
73
73
73
73
73
73
77
77
77
76
76
76
75
75
75
75
75
75
75
75
75
75
63
63
63
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
57.6
57.6
57.6
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
60.1
60.1
60.1
57.9
57.9
57.9
53.5
53.5
53.5
53.7
53.7
53.7
54.4
54.4
54.4
53.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
20,529
20,529
20,529
26,244
26,244
26,244
76,434
76,434
76,434
26,279
26,279
26,279
21,797
21,797
21,797
101,628
101,628
101,628
36,070
36,070
36,070
25,678
25,678
25,678
11,070
11,070
11,070
14,327
14,327
14,327
14,201
14,201
14,201
36,302
36,302
36,302
32,911
32,911
32,911
43,793
43,793
43,793
35,131
Coil
Latent
Load
Btu/h
1,393
1,393
1,393
2,856
2,856
2,856
12,774
12,774
12,774
6,912
6,912
6,912
5,733
5,733
5,733
18,995
18,995
18,995
2,820
2,820
2,820
2,221
2,221
2,221
1,110
1,110
1,110
2,357
2,357
2,357
2,261
2,261
2,261
6,665
6,665
6,665
5,915
5,915
5,915
6,420
6,420
6,420
6,406
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 70 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 327
Zone - 327
spc_sp_1
Zone - 328
Zone - 328
spc_sp_2
Zone - 329
Zone - 329
spc_sp_3
Zone - 330
Zone - 330
spc_sp_4
Zone - 331
Zone - 331
spc_sp_5
Zone - 332
Zone - 332
spc_sp_6
Zone - 333
Zone - 333
Child Cntr 2
Zone - 359
Zone - 359
Child Cntr 3
Zone - 360
Zone - 360
Child Cntr 1
Zone - 361
Zone - 361
Portopia HP
Portopia HP
spc_SS 141/142 Office_0
Zone - 012
Zone - 012
spc_SS 144 Office C_0
Zone - 013
Zone - 013
spc_SS 160B-D_0
Zone - 014
Zone - 014
spc_PS 160A Storage_0
Zone - 015
Zone - 015
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,040
1,040
1,272
1,272
1,272
1,074
1,074
1,074
999
999
999
1,613
1,613
1,613
664
664
664
1,956
1,956
1,956
211
211
211
211
211
211
211
211
211
75,038
75,038
313
313
313
168
168
168
0
0
0
102
102
102
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
10 /15
10 /15
10 /16
10 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
6 /9
10 /15
10 /15
9 /11
9 /11
73
73
77
77
77
73
73
73
73
73
73
80
80
80
79
79
79
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
62
62
80
80
80
70
70
70
65
65
67
67
67
65
65
65
65
65
65
63
63
63
64
64
64
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
58
58
63
63
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Supply
Dry
Bulb
°F
53.1
53.1
48.6
48.6
48.6
53.1
53.1
53.1
54.3
54.3
54.3
55.5
55.5
55.5
57.1
57.1
57.1
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
54.9
54.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
32
32
0
0
0
27
27
27
22,182
22,182
15,648
15,648
15,648
22,945
22,945
22,945
28,019
28,019
28,019
37,433
37,433
37,433
31,843
31,843
31,843
22,688
22,688
22,688
13,285
13,285
13,285
13,285
13,285
13,285
12,931
12,931
12,931
2,026,697
1,809,600
0
0
0
0
0
0
0
0
0
0
0
0
3,594
3,594
4,707
4,707
4,707
3,711
3,711
3,711
3,457
3,457
3,457
4,151
4,151
4,151
1,840
1,840
1,840
6,857
6,857
6,857
559
559
559
559
559
559
370
370
370
246,137
246,507
181
181
181
97
97
97
0
0
0
-2
-2
-2
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
6 /9
9 /16
9 /16
9 /11
9 /11
75
75
76
76
76
75
75
75
75
75
75
77
77
77
77
77
77
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
62
62
77
77
77
70
70
70
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
58
58
67
67
67
63
63
63
53.6
53.6
48.8
48.8
48.8
53.6
53.6
53.6
54.5
54.5
54.5
56.4
56.4
56.4
57.3
57.3
57.3
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
55.1
56.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Coil
Airflow
cfm
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
32
32
0
0
0
27
27
27
Coil
Sensible
Load
Btu/h
35,131
35,131
31,358
31,358
31,358
36,369
36,369
36,369
42,495
42,495
42,495
56,782
56,782
56,782
43,282
43,282
43,282
46,620
46,620
46,620
14,677
14,677
14,677
14,677
14,677
14,677
14,524
14,524
14,524
3,006,774
2,862,181
0
0
0
0
0
0
0
0
0
0
0
0
Coil
Latent
Load
Btu/h
6,406
6,406
7,970
7,970
7,970
6,615
6,615
6,615
6,169
6,169
6,169
11,281
11,281
11,281
4,645
4,645
4,645
12,262
12,262
12,262
694
694
694
694
694
694
460
460
460
480,065
462,701
0
0
0
0
0
0
0
0
0
0
0
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 71 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_SS 160 Class C_0
Zone - 016
Zone - 016
spc_SS 162 Class_0
Zone - 017
Zone - 017
spc_PS 112 Office C_0
Zone - 018
Zone - 018
spc_PS 111-115 Office C_0
Zone - 019
Zone - 019
spc_PS Lecture 117 C_0
Zone - 020
Zone - 020
spc_PS Lecture FC-4C_0
Zone - 021
Zone - 021
spc_PS 120-128 Class_0
Zone - 022
Zone - 022
spc_PS Class 121/122_0
Zone - 023
Zone - 023
spc_PS 130 Auditorium C_0
Zone - 024
Zone - 024
PS Fan Coil Htg Only
PS Fan Coil Htg Only
spc_SS 171-173, 178 Office C_0
Zone - 037
Zone - 037
spc_SS 135 Office_0
Zone - 038
Zone - 038
spc_SS Corridor 120 C_0
Zone - 039
Zone - 039
spc_SS 180 Worm Rm VAV-20_0
Zone - 040
Zone - 040
spc_SS 110C Wrk Rm C_0
Zone - 041
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
565
565
565
967
967
967
215
215
215
602
602
602
1,126
1,126
1,126
1,036
1,036
1,036
886
886
886
695
695
695
1,413
1,413
1,413
8,090
8,090
561
561
561
92
92
92
1,787
1,787
1,787
326
326
326
766
766
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
10 /16
10 /16
9 /17
9 /17
7 /18
7 /18
6 /9
6 /9
7 /16
7 /16
10 /16
10 /16
10 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
6 /9
70
70
70
70
70
70
79
79
79
79
79
79
76
76
76
73
73
73
62
62
62
76
76
76
79
79
79
79
79
76
76
76
76
76
76
76
76
76
79
79
79
62
62
63
63
63
63
63
63
64
64
64
64
64
64
67
67
67
65
65
65
58
58
58
66
66
66
64
64
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
274
274
274
45
45
45
378
378
378
616
616
616
1,984
1,984
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,317
5,317
5,317
875
875
875
7,342
7,342
7,342
11,961
11,961
11,961
38,530
38,530
836
836
836
1,430
1,430
1,430
157
157
157
435
435
435
1,356
1,356
1,356
1,374
1,374
1,374
1,392
1,392
1,392
992
992
992
2,191
2,191
2,191
10,439
7,971
1,465
1,465
1,465
241
241
241
2,794
2,794
2,794
902
902
902
2,030
2,030
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
7 /18
7 /18
7 /9
7 /9
7 /16
7 /16
9 /16
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
7 /10
70
70
70
70
70
70
79
79
79
76
76
76
76
76
76
73
73
73
64
64
64
76
76
76
77
77
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
67
67
63
63
63
63
63
63
64
64
64
67
67
67
67
67
67
65
65
65
59
59
59
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
60
60
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
268
268
268
44
44
44
364
364
364
593
593
593
1,874
1,874
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,089
5,089
5,089
838
838
838
5,425
5,425
5,425
13,863
13,863
13,863
40,338
40,338
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2,917
2,917
2,917
480
480
480
4,022
4,022
4,022
2,276
2,276
2,276
2,929
2,929
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 72 of 100
SPACE
System Zone Room
Zone - 041
Block
spc_SS 110 Wrk Rm/Office C_0 Peak
Zone - 042
Peak
Zone - 042
Block
Peak
spc_SS 100 100H 111H Main Lobby
C_0
Zone - 043
Peak
Zone - 043
Block
spc_SS 150 Wrk Rm C_0
Peak
Zone - 044
Peak
Zone - 044
Block
spc_SS 177-179 Office_0
Peak
Zone - 045
Peak
Zone - 045
Block
spc_SS Wrk Rm1 V-19_0
Peak
Zone - 046
Peak
Zone - 046
Block
spc_SS 120-124 C_0
Peak
Zone - 047
Peak
Zone - 047
Block
spc_SS 135-139 Office C_0
Peak
Zone - 048
Peak
Zone - 048
Block
spc_SS 140 Wrk Rm C_0
Peak
Zone - 049
Peak
Zone - 049
Block
spc_SS 125-129_0
Peak
Zone - 050
Peak
Zone - 050
Block
spc_SS 230B Office C_0
Peak
Zone - 051
Peak
Zone - 051
Block
spc_SS 214 Office C_0
Peak
Zone - 052
Peak
Zone - 052
Block
spc_SS 282 Wrk Rm C_0
Peak
Zone - 053
Peak
Zone - 053
Block
spc_SS 280D Office_0
Peak
Zone - 054
Peak
Zone - 054
Block
spc_SS 280A-C C_0
Peak
Zone - 055
Peak
Zone - 055
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
766
1,420
1,420
1,420
37
37
37
301
301
301
635
635
635
207
207
207
703
703
703
586
586
586
848
848
848
642
642
642
285
285
285
130
130
130
136
136
136
154
154
154
459
459
459
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /9
9 /17
9 /17
7 /18
7 /18
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
6/9
6 /9
7 /16
7 /16
9 /16
9 /16
6 /18
6 /18
6 /18
6 /18
10 /16
10 /16
10 /16
10 /16
7 /17
7 /17
9 /11
9 /11
62
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
62
62
62
76
76
76
77
77
77
70
70
70
70
70
70
79
79
79
79
79
79
75
75
75
70
70
70
58
67
67
67
65
65
65
66
66
66
66
66
66
66
66
66
58
58
58
66
66
66
67
67
67
63
63
63
63
63
63
64
64
64
64
64
64
66
66
66
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,984
844
844
844
348
348
348
167
167
167
310
310
310
115
115
115
1,253
1,253
1,253
286
286
286
545
545
545
1,766
1,766
1,766
526
526
526
623
623
623
1,441
1,441
1,441
75
75
75
1,255
1,255
1,255
38,530
16,389
16,389
16,389
6,755
6,755
6,755
3,248
3,248
3,248
6,019
6,019
6,019
2,238
2,238
2,238
24,336
24,336
24,336
5,555
5,555
5,555
10,576
10,576
10,576
34,294
34,294
34,294
10,214
10,214
10,214
12,096
12,096
12,096
27,981
27,981
27,981
1,450
1,450
1,450
24,365
24,365
24,365
2,030
4,101
4,101
4,101
63
63
63
1,044
1,044
1,044
1,658
1,658
1,658
719
719
719
1,862
1,862
1,862
1,530
1,530
1,530
3,146
3,146
3,146
1,992
1,992
1,992
572
572
572
244
244
244
378
378
378
408
408
408
1,469
1,469
1,469
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /10
9 /17
9 /17
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /10
7 /10
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /11
9 /11
67
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
67
67
67
76
76
76
77
77
77
73
73
73
73
73
73
77
77
77
77
77
77
75
75
75
70
70
70
60
67
67
67
65
65
65
67
67
67
67
67
67
67
67
67
60
60
60
67
67
67
67
67
67
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
63
63
63
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,874
844
844
844
348
348
348
165
165
165
304
304
304
114
114
114
1,181
1,181
1,181
280
280
280
545
545
545
1,745
1,745
1,745
522
522
522
610
610
610
1,360
1,360
1,360
75
75
75
1,255
1,255
1,255
40,338
16,959
16,959
16,959
8,572
8,572
8,572
3,134
3,134
3,134
5,761
5,761
5,761
2,159
2,159
2,159
25,288
25,288
25,288
5,317
5,317
5,317
10,803
10,803
10,803
37,007
37,007
37,007
11,167
11,167
11,167
14,956
14,956
14,956
32,179
32,179
32,179
3,723
3,723
3,723
28,088
28,088
28,088
Coil
Latent
Load
Btu/h
2,929
7,387
7,387
7,387
90
90
90
2,099
2,099
2,099
3,302
3,302
3,302
1,446
1,446
1,446
2,687
2,687
2,687
3,047
3,047
3,047
5,923
5,923
5,923
4,132
4,132
4,132
1,239
1,239
1,239
651
651
651
953
953
953
703
703
703
2,386
2,386
2,386
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 73 of 100
SPACE
System Zone Room
spc_SS 272 Wrk Rm C_0
Peak
Zone - 056
Peak
Zone - 056
Block
spc_SS 270C/D Office_0
Peak
Zone - 057
Peak
Zone - 057
Block
spc_SS 111H Hall_0
Peak
Zone - 058
Peak
Zone - 058
Block
spc_SS 110G/H Offices C_0
Peak
Zone - 059
Peak
Zone - 059
Block
spc_SS 111A Office C_0
Peak
Zone - 060
Peak
Zone - 060
Block
spc_SS 242 Wrk Rm C_0
Peak
Zone - 061
Peak
Zone - 061
Block
spc_SS 240L Office C_0
Peak
Zone - 062
Peak
Zone - 062
Block
spc_SS 240H Office_0
Peak
Zone - 063
Peak
Zone - 063
Block
spc_SS 240F/J Office_0
Peak
Zone - 064
Peak
Zone - 064
Block
spc_SS 240-260A Wrk Rm C_0 Peak
Zone - 065
Peak
Zone - 065
Block
spc_SS 202/250B Office_0
Peak
Zone - 066
Peak
Zone - 066
Block
spc_SS 250 Wrk Rm C_0
Peak
Zone - 067
Peak
Zone - 067
Block
spc_SS 251 Wrk Rm C_0
Peak
Zone - 068
Peak
Zone - 068
Block
Peak
spc_SS 230H, 200-201, 251H, 272H_0
Zone - 069
Peak
Zone - 069
Block
spc_SS 210/211 Wrk Rm C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
778
778
778
287
287
287
397
397
397
269
269
269
216
216
216
642
642
642
149
149
149
181
181
181
274
274
274
865
865
865
214
214
214
0
0
0
388
388
388
4,383
4,383
4,383
308
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /12
9 /12
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
10 /16
10 /16
7 /16
7 /16
6 /9
6 /9
9 /12
9 /12
7 /16
7 /16
7 /15
70
70
70
73
73
73
73
73
73
76
76
76
76
76
76
79
79
79
75
75
75
76
76
76
75
75
75
79
79
79
76
76
76
62
62
62
73
73
73
76
76
76
77
63
63
63
63
63
63
65
65
65
66
66
66
66
66
66
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
66
66
66
58
58
58
63
63
63
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,090
1,090
1,090
379
379
379
175
175
175
131
131
131
105
105
105
406
406
406
73
73
73
89
89
89
133
133
133
1,257
1,257
1,257
104
104
104
16
16
16
387
387
387
2,716
2,716
2,716
171
21,179
21,179
21,179
7,364
7,364
7,364
3,399
3,399
3,399
2,552
2,552
2,552
2,048
2,048
2,048
7,890
7,890
7,890
1,410
1,410
1,410
1,719
1,719
1,719
2,589
2,589
2,589
24,416
24,416
24,416
2,028
2,028
2,028
304
304
304
7,518
7,518
7,518
52,749
52,749
52,749
3,325
2,489
2,489
2,489
627
627
627
612
612
612
703
703
703
564
564
564
1,777
1,777
1,777
397
397
397
474
474
474
728
728
728
2,394
2,394
2,394
559
559
559
0
0
0
1,195
1,195
1,195
15,399
15,399
15,399
1,069
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /13
9 /13
9 /13
9 /13
7 /18
7 /18
9 /17
9 /17
9 /17
9 /17
7 /16
7 /16
7 /17
7 /17
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
9 /17
9 /17
7 /10
7 /10
9 /12
9 /12
7 /16
7 /16
7 /16
75
75
75
75
75
75
73
73
73
76
76
76
76
76
76
76
76
76
75
75
75
76
76
76
75
75
75
77
77
77
76
76
76
67
67
67
73
73
73
76
76
76
76
65
65
65
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
60
60
60
63
63
63
66
66
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
918
918
918
357
357
357
175
175
175
129
129
129
103
103
103
394
394
394
73
73
73
87
87
87
133
133
133
1,221
1,221
1,221
102
102
102
15
15
15
387
387
387
2,716
2,716
2,716
171
25,380
25,380
25,380
10,543
10,543
10,543
3,469
3,469
3,469
2,443
2,443
2,443
1,960
1,960
1,960
17,212
17,212
17,212
3,620
3,620
3,620
1,646
1,646
1,646
6,646
6,646
6,646
38,964
38,964
38,964
1,941
1,941
1,941
312
312
312
8,858
8,858
8,858
113,463
113,463
113,463
7,815
Coil
Latent
Load
Btu/h
4,471
4,471
4,471
973
973
973
790
790
790
1,400
1,400
1,400
1,123
1,123
1,123
4,042
4,042
4,042
684
684
684
943
943
943
1,256
1,256
1,256
6,040
6,040
6,040
1,112
1,112
1,112
0
0
0
1,856
1,856
1,856
27,598
27,598
27,598
1,937
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 74 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 070
Zone - 070
spc_SS 230F Office C_0
Zone - 071
Zone - 071
spc_SS Wrk Rm 230 C_0
Zone - 072
Zone - 072
spc_SS 230C-E Office_0
Zone - 073
Zone - 073
spc_SS 240B Wrk Rm C_0
Zone - 074
Zone - 074
spc_SS 181 Comp Rm C_0
Zone - 075
Zone - 075
spc_SS 182 Comp Rm C_0
Zone - 076
Zone - 076
Stdnt Srv VAV
Stdnt Srv VAV
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
308
308
7 /15
180
6 /18
180
180
6 /18
987
7 /16
987
987
7 /16
630
6 /18
630
630
6 /18
240 10 /16
240
240 10 /16
854
7 /18
854
854
7/18
863
9 /11
863
863
9 /11
23,178
23,178 7 /17
77
77
70
70
70
76
76
76
70
70
70
79
79
79
73
73
73
70
70
70
75
75
66
66
63
63
63
66
66
66
63
63
63
64
64
64
65
65
65
63
63
63
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
171
171
330
330
330
550
550
550
1,887
1,887
1,887
607
607
607
2,223
2,223
2,223
2,317
2,317
2,317
27,996
21,892
3,325
3,325
6,408
6,408
6,408
10,680
10,680
10,680
36,641
36,641
36,641
11,782
11,782
11,782
43,184
43,184
43,184
45,011
45,011
45,011
543,738
425,196
1,069
1,069
360
360
360
3,468
3,468
3,468
1,262
1,262
1,262
663
663
663
2,471
2,471
2,471
2,243
2,243
2,243
66,071
67,555
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
7 /18
7 /18
9 /11
9 /11
7 /17
76
76
73
73
73
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
75
75
66
66
65
65
65
66
66
66
65
65
65
67
67
67
65
65
65
63
63
63
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
171
171
326
326
326
550
550
550
1,854
1,854
1,854
595
595
595
2,223
2,223
2,223
2,317
2,317
2,317
27,337
21,892
7,815
7,815
9,430
9,430
9,430
25,113
25,113
25,113
48,827
48,827
48,827
15,938
15,938
15,938
45,640
45,640
45,640
49,534
49,534
49,534
713,169
592,652
1,937
1,937
781
781
781
6,215
6,215
6,215
2,736
2,736
2,736
1,674
1,674
1,674
4,381
4,381
4,381
3,536
3,536
3,536
122,218
121,687
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 75 of 100
SPACE
Floor
Area
ft²
System Zone Room
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
58.1
58.1
58.1
51.6
51.6
51.6
55.0
55.0
55.0
56.7
56.7
56.7
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.8
57.8
57.8
52.5
52.5
52.5
69.6
69.6
69.6
57.6
57.6
54.7
54.7
54.7
54.6
54.6
54.6
49.8
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
19,718
19,718
19,718
27,717
27,717
27,717
4,324
4,324
4,324
8,470
8,470
8,470
10,677
10,677
10,677
33,208
33,208
33,208
3,217
3,217
3,217
2,438
2,438
2,438
46,648
46,648
46,648
8,293
8,293
8,293
13,658
13,658
13,658
178,368
160,203
45,748
45,748
45,748
34,617
34,617
34,617
7,681
649
649
649
6,690
6,690
6,690
0
0
0
601
601
601
686
686
686
2,099
2,099
2,099
935
935
935
708
708
708
1,884
1,884
1,884
1,710
1,710
1,710
-741
-741
-741
15,221
21,247
6,031
6,031
6,031
4,790
4,790
4,790
2,079
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,270
1,270
1,270
1,220
1,220
1,220
228
228
228
496
496
496
614
614
614
1,911
1,911
1,911
126
126
126
96
96
96
2,937
2,937
2,937
381
381
381
1,175
1,175
1,175
10,454
10,454
2,377
2,377
2,377
1,780
1,780
1,780
311
21,552
21,552
21,552
27,487
27,487
27,487
4,459
4,459
4,459
10,580
10,580
10,580
12,077
12,077
12,077
35,790
35,790
35,790
8,578
8,578
8,578
6,500
6,500
6,500
64,856
64,856
64,856
8,454
8,454
8,454
27,101
27,101
27,101
227,433
211,887
48,957
48,957
48,957
37,048
37,048
37,048
18,754
Coil
Latent
Load
Btu/h
Alternative 4
spc_A 121 Office UC_0
Zone - 077
Zone - 077
spc_A 130A Class? FC1-4_0
Zone - 078
Zone - 078
spc_A 237-241 Office C_0
Zone - 093
Zone - 093
spc_A 202A Office D_0
Zone - 094
Zone - 094
spc_A 202A Office B_0
Zone - 095
Zone - 095
spc_A 202A Office C_0
Zone - 096
Zone - 096
spc_A 201 Office C_0
Zone - 097
Zone - 097
spc_A 200H-J Office C_0
Zone - 098
Zone - 098
spc_A 200 Office C_0
Zone - 099
Zone - 099
spc_A 210A-B Stairs C_0
Zone - 100
Zone - 100
spc_A 121 Restroom FC05_0
Zone - 118
Zone - 118
Admin FC
Admin FC
spc_A 161/162 Class C_0
Zone - 091
Zone - 091
spc_A 160 Wrk Rm C_0
Zone - 092
Zone - 092
spc_A 236A/B Offices_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
348
348
348
2,606
2,606
2,606
0
0
0
344
344
344
238
238
238
891
891
891
353
353
353
267
267
267
1,011
1,011
1,011
1,111
1,111
1,111
734
734
734
7,905
7,905
2,273
2,273
2,273
1,806
1,806
1,806
786
10 /16
10 /16
10 /15
10 /15
7 /16
7 /16
6 /10
6 /10
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
7 /18
7 /18
10 /16
10 /16
9 /16
6 /9
6 /9
6 /9
6 /9
7 /17
79
79
79
80
80
80
76
76
76
65
65
65
76
76
76
73
73
73
75
75
75
75
75
75
79
79
79
73
73
73
79
79
79
77
77
62
62
62
62
62
62
75
64
64
64
63
63
63
66
66
66
58
58
58
67
67
67
65
65
65
66
66
66
66
66
66
64
64
64
65
65
65
64
64
64
67
67
58
58
58
58
58
58
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
9 /17
9 /17
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
9 /16
7 /9
7 /9
7 /9
7 /9
7 /17
77
77
77
77
77
77
76
76
76
76
76
76
76
76
76
73
73
73
75
75
75
75
75
75
77
77
77
73
73
73
77
77
77
77
77
64
64
64
64
64
64
75
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
65
65
65
66
66
66
66
66
66
67
67
67
65
65
65
67
67
67
67
67
59
59
59
59
59
59
66
58.4
58.4
58.4
51.8
51.8
51.8
55.0
55.0
55.0
63.1
63.1
63.1
56.4
56.4
56.4
56.4
56.4
56.4
49.2
49.2
49.2
49.2
49.2
49.2
57.9
57.9
57.9
52.5
52.5
52.5
69.8
69.8
69.8
58.0
59.2
55.1
55.1
55.1
54.9
54.9
54.9
49.8
1,735
1,735
1,735
18,165
18,165
18,165
0
0
0
1,536
1,536
1,536
1,234
1,234
1,234
3,864
3,864
3,864
1,611
1,611
1,611
1,221
1,221
1,221
5,037
5,037
5,037
2,205
2,205
2,205
-7,656
-7,656
-7,656
28,952
30,207
9,347
9,347
9,347
7,420
7,420
7,420
3,579
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 76 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 113
Zone - 113
spc_A 244/246 Office C_0
Zone - 114
Zone - 114
spc_A 242/243 Class C_0
Zone - 115
Zone - 115
spc_A 238-246 Offices C_0
Zone - 116
Zone - 116
spc_A 216/218 Office C_0
Zone - 117
Zone - 117
Admin Pckg AHU
Admin Pckg AHU
spc_A 277F Class_0
Zone - 079
Zone - 079
spc_A 279A Hall C_0
Zone - 080
Zone - 080
spc_A 278A Cond Stair_0
Zone - 081
Zone - 081
spc_A 170/171 Lobby C_0
Zone - 082
Zone - 082
spc_A 172 Wrk Rm C_0
Zone - 083
Zone - 083
spc_A Wrk Rm 173 C_0
Zone - 084
Zone - 084
spc_A 177 Comp C_1
Zone - 085
Zone - 085
spc_A 174-176 Data C_0
Zone - 086
Zone - 086
spc_A 177 Comp C_0
Zone - 087
Zone - 087
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
786
786
367
367
367
1,839
1,839
1,839
2,547
2,547
2,547
2,057
2,057
2,057
11,676
11,676
1,395
1,395
1,395
7,584
7,584
7,584
321
321
321
1,279
1,279
1,279
2,002
2,002
2,002
671
671
671
626
626
626
201
201
201
626
626
626
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
10 /16
10 /16
6 /10
6 /10
7 /17
7 /17
6 /10
6/18
6 /18
6 /10
6 /10
9 /11
9 /11
7 /18
7 /18
6 /9
6 /9
10 /15
10 /15
6 /9
6 /9
9 /16
9 /16
7 /16
7 /16
75
75
75
75
75
79
79
79
65
65
65
75
75
75
65
65
70
70
70
65
65
65
70
70
70
73
73
73
62
62
62
80
80
80
62
62
62
77
77
77
76
76
76
66
66
66
66
66
64
64
64
58
58
58
66
66
66
58
58
63
63
63
58
58
58
63
63
63
65
65
65
58
58
58
63
63
63
58
58
58
67
67
67
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
70.0
70.0
70.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.8
49.8
49.8
49.8
49.8
55.5
55.5
55.5
57.3
57.3
57.3
49.8
49.8
49.8
55.4
55.4
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,510
2,510
2,510
5,680
5,680
5,680
1,443
1,443
1,443
483
483
483
2,570
2,570
2,570
1,214
1,214
1,214
1,490
1,490
1,490
1,917
1,917
1,917
1,042
1,042
1,042
7,681
7,681
3,589
3,589
3,589
49,570
49,570
49,570
81,320
81,320
81,320
20,104
20,104
20,104
242,629
193,483
46,615
46,615
46,615
105,509
105,509
105,509
26,795
26,795
26,795
8,969
8,969
8,969
47,731
47,731
47,731
22,553
22,553
22,553
27,671
27,671
27,671
31,338
31,338
31,338
19,354
19,354
19,354
2,079
2,079
971
971
971
5,095
5,095
5,095
4,472
4,472
4,472
5,442
5,442
5,442
28,881
25,762
4,376
4,376
4,376
5,555
5,555
5,555
411
411
411
2,208
2,208
2,208
5,370
5,370
5,370
1,747
1,747
1,747
1,303
1,303
1,303
497
497
497
1,843
1,843
1,843
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
7 /17
7 /17
7 /16
7 /18
7 /18
7 /16
7 /16
9 /11
9 /11
7 /9
7 /9
7 /9
7 /9
9 /16
9 /16
7 /9
7 /9
9 /16
9 /16
9 /16
9 /16
75
75
75
75
75
77
77
77
76
76
76
75
75
75
76
76
73
73
73
76
76
76
70
70
70
64
64
64
64
64
64
77
77
77
64
64
64
77
77
77
77
77
77
66
66
66
66
66
67
67
67
66
66
66
66
66
66
66
66
65
65
65
66
66
66
63
63
63
59
59
59
59
59
59
67
67
67
59
59
59
67
67
67
67
67
67
49.8
49.8
49.8
49.8
49.8
55.6
55.6
55.6
64.0
64.0
64.0
49.8
49.8
49.8
58.0
60.0
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
311
311
145
145
145
2,701
2,701
2,701
4,948
4,948
4,948
813
813
813
13,075
13,075
2,485
2,485
2,485
3,475
3,475
3,475
1,443
1,443
1,443
420
420
420
2,508
2,508
2,508
1,209
1,209
1,209
1,469
1,469
1,469
1,917
1,917
1,917
1,032
1,032
1,032
18,754
18,754
8,763
8,763
8,763
78,514
78,514
78,514
92,985
92,985
92,985
49,087
49,087
49,087
334,108
299,894
66,753
66,753
66,753
177,138
177,138
177,138
30,401
30,401
30,401
10,395
10,395
10,395
48,380
48,380
48,380
23,906
23,906
23,906
28,680
28,680
28,680
33,072
33,072
33,072
19,437
19,437
19,437
Coil
Latent
Load
Btu/h
3,579
3,579
1,672
1,672
1,672
12,862
12,862
12,862
11,426
11,426
11,426
9,369
9,369
9,369
55,677
63,035
9,143
9,143
9,143
15,367
15,367
15,367
511
511
511
2,145
2,145
2,145
8,439
8,439
8,439
4,762
4,762
4,762
2,059
2,059
2,059
835
835
835
3,541
3,541
3,541
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 77 of 100
SPACE
System Zone Room
spc_A 179/178 Data C_0
Peak
Zone - 088
Peak
Zone - 088
Block
spc_A 180E Com Lab C_0
Peak
Zone - 089
Peak
Zone - 089
Block
spc_A 271-277 Office C_0
Peak
Zone - 111
Peak
Zone - 111
Block
spc_A 277 Class_0
Peak
Zone - 112
Peak
Zone - 112
Block
Peak
Admin VAV
Admin VAV
Block
spc_BC 237 Class_0
Peak
Zone - 334
Peak
Zone - 334
Block
spc_BC 221 Lobby_0
Peak
Zone - 335
Peak
Zone - 335
Block
spc_BC 222 Class_0
Peak
Zone - 336
Peak
Zone - 336
Block
spc_215-219 Office_0
Peak
Zone - 337
Peak
Zone - 337
Block
spc_BC 224 Class_0
Peak
Zone - 338
Peak
Zone - 338
Block
spc_BC 2nd 226/228 Class_0
Peak
Zone - 339
Peak
Zone - 339
Block
spc_BC 2nd 230 Class_0
Peak
Zone - 340
Peak
Zone - 340
Block
spc_BC 115/116 Office_0
Peak
Zone - 351
Peak
Zone - 351
Block
spc_BC Office 137/139/141/142_0 Peak
Zone - 352
Peak
Zone - 352
Block
spc_BC 143 Office_0
Peak
Zone - 353
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
339
339
339
951
951
951
2,656
2,656
2,656
0
0
0
18,650
18,650
166
166
166
120
120
120
196
196
196
262
262
262
146
146
146
281
281
281
187
187
187
155
155
155
103
103
103
123
123
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
9 /15
10 /14
10 /14
7 /16
7 /16
7 /18
7 /18
10 /16
10 /16
9 /11
9 /11
9 /10
9 /10
9 /17
9 /17
9 /12
9 /12
10 /16
10 /16
10 /16
76
76
76
80
80
80
75
75
75
80
80
80
78
78
79
79
79
76
76
76
73
73
73
79
79
79
70
70
70
67
67
67
76
76
76
73
73
73
79
79
79
79
79
66
66
66
63
63
63
66
66
66
63
63
63
66
66
62
62
62
66
66
66
65
65
65
64
64
64
63
63
63
61
61
61
67
67
67
63
63
63
64
64
64
64
64
70.0
70.0
70.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
71.7
71.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
57.5
57.5
57.5
57.3
57.3
57.3
57.1
57.1
57.1
57.5
57.5
57.5
55.6
55.6
55.6
56.0
56.0
56.0
57.2
57.2
57.2
56.1
56.1
56.1
51.8
51.8
51.8
58.7
58.7
2,037
2,037
2,037
2,646
2,646
2,646
1,344
1,344
1,344
4,175
4,175
4,175
28,551
22,316
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
237
237
237
38
38
38
797
797
33,300
33,300
33,300
49,154
49,154
49,154
24,971
24,971
24,971
77,551
77,551
77,551
521,509
407,618
6,259
6,259
6,259
3,956
3,956
3,956
14,583
14,583
14,583
10,595
10,595
10,595
5,091
5,091
5,091
11,008
11,008
11,008
15,364
15,364
15,364
4,204
4,204
4,204
848
848
848
11,800
11,800
771
771
771
1,906
1,906
1,906
7,134
7,134
7,134
0
0
0
33,121
44,638
375
375
375
194
194
194
681
681
681
491
491
491
468
468
468
889
889
889
658
658
658
340
340
340
192
192
192
231
231
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /19
9 /19
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /14
9 /14
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
9 /12
9 /12
9 /11
9 /11
9 /17
9 /17
9 /12
9 /12
9 /17
9 /17
10 /16
71
71
71
77
77
77
76
76
76
77
77
77
77
77
77
77
77
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
76
76
76
73
73
73
76
76
76
79
79
66
66
66
67
67
67
66
66
66
67
67
67
67
67
66
66
66
66
66
66
65
65
65
67
67
67
63
63
63
63
63
63
67
67
67
63
63
63
67
67
67
64
64
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
55.3
58.2
58.2
58.2
57.3
57.3
57.3
57.1
57.1
57.1
57.7
57.7
57.7
56.5
56.5
56.5
56.3
56.3
56.3
57.2
57.2
57.2
56.1
56.1
56.1
52.2
52.2
52.2
58.7
58.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
2,008
2,008
2,008
2,644
2,644
2,644
1,337
1,337
1,337
4,061
4,061
4,061
26,008
22,285
388
388
388
242
242
242
877
877
877
656
656
656
278
278
278
617
617
617
929
929
929
237
237
237
38
38
38
797
797
33,409
33,409
33,409
51,546
51,546
51,546
32,823
32,823
32,823
77,838
77,838
77,838
651,278
557,619
7,849
7,849
7,849
5,195
5,195
5,195
17,225
17,225
17,225
12,759
12,759
12,759
6,331
6,331
6,331
12,300
12,300
12,300
20,480
20,480
20,480
5,546
5,546
5,546
1,020
1,020
1,020
13,862
13,862
Coil
Latent
Load
Btu/h
1,453
1,453
1,453
5,384
5,384
5,384
12,103
12,103
12,103
0
0
0
65,740
78,660
1,025
1,025
1,025
278
278
278
1,269
1,269
1,269
1,313
1,313
1,313
701
701
701
1,464
1,464
1,464
1,309
1,309
1,309
517
517
517
535
535
535
308
308
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 78 of 100
SPACE
System Zone Room
Zone - 353
spc_BC 109 Class_0
Zone - 354
Zone - 354
spc_BC 108 Class_0
Zone - 355
Zone - 355
spc_BC 106 Class_0
Zone - 356
Zone - 356
spc_BC 105 Class_0
Zone - 357
Zone - 357
spc_BC 101 Class_0
Zone - 358
Zone - 358
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
BC FC
Peak
BC FC
Block
spc_BC 130 Cafe/Kitchen_0
Peak
Zone - 341
Peak
Zone - 341
Block
spc_BC AH-2 245 Lecture_0
Peak
Zone - 342
Peak
Zone - 342
Block
spc_BC AH-3 301 Class_0
Peak
Zone - 343
Peak
Zone - 343
Block
spc_BC AH-4 302 Class_0
Peak
Zone - 344
Peak
Zone - 344
Block
spc_BC 306 Office (AH-5)_0
Peak
spc_BC 307-312 Office (AH-5)_0 Peak
spc_BC AH-5 304 Hall_0
Peak
Zone - 345
Peak
Zone - 345
Block
spc_BC AH-6 315 Lab_0
Peak
Zone - 346
Peak
Zone - 346
Block
spc_BC AH-7 314 Class_0
Peak
Zone - 347
Peak
Zone - 347
Block
spc_BC AH-8 313_0
Peak
Zone - 348
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
123
248
248
248
228
228
228
287
287
287
308
308
308
696
696
696
3,507
3,507
1,908
1,908
1,908
809
809
809
162
162
162
188
188
188
17
107
518
642
642
181
181
181
183
183
183
518
518
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /16
9 /12
9 /12
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /12
7 /19
7 /19
9 /13
9 /13
7 /10
7 /10
11 /13
11 /13
7 /18
10 /16
7 /18
10/16
10 /16
10 /16
6 /9
6 /9
9 /16
79
73
73
73
73
73
73
70
70
70
70
70
70
70
70
70
73
73
71
71
71
75
75
75
67
67
67
71
71
71
73
79
73
79
79
79
79
79
62
62
62
77
77
64
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
64
64
64
65
65
65
60
60
60
58
58
58
65
64
65
64
64
64
64
64
58
58
58
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
58.7
53.9
53.9
53.9
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.8
56.8
49.0
49.0
49.0
48.5
48.5
48.5
57.5
57.5
57.5
55.0
55.0
55.0
57.7
59.1
54.7
58.0
58.0
58.3
58.3
58.3
56.9
56.9
56.9
55.0
55.0
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
902
902
902
435
435
435
1,005
1,005
11,800
5,234
5,234
5,234
6,925
6,925
6,925
15,674
15,674
15,674
16,788
16,788
16,788
36,297
36,297
36,297
164,625
128,212
25,681
25,681
25,681
8,768
8,768
8,768
9,949
9,949
9,949
14,106
14,106
14,106
1,203
14,924
6,067
22,194
20,846
13,789
13,789
13,789
7,351
7,351
7,351
19,025
19,025
231
766
766
766
704
704
704
918
918
918
985
985
985
2,230
2,230
2,230
10,125
10,014
7,496
7,496
7,496
2,709
2,709
2,709
457
457
457
435
435
435
41
199
801
1,041
657
394
394
394
486
486
486
1,924
1,924
10 /16
9 /13
9 /13
9 /12
9 /12
9 /11
9 /11
9 /11
9 /11
9 /11
9 /11
9 /13
7 /19
7 /19
9 /14
9 /14
7 /10
7 /10
9 /15
9 /15
7 /18
10 /16
7 /18
9 /17
9 /16
9 /16
7 /17
7 /17
9 /16
79
75
75
75
73
73
73
70
70
70
70
70
70
70
70
70
75
75
71
71
71
77
77
77
67
67
67
78
78
78
73
79
73
76
76
77
77
77
75
75
75
77
77
64
65
65
65
63
63
63
63
63
63
63
63
63
63
63
63
65
65
64
64
64
66
66
66
60
60
60
66
66
66
65
64
65
67
67
67
67
67
66
66
66
67
67
58.7
54.5
54.5
54.5
55.3
55.3
55.3
56.8
56.8
56.8
56.8
56.8
56.8
56.7
56.7
56.7
56.9
60.6
49.0
49.0
49.0
48.7
48.7
48.7
57.5
57.5
57.5
57.3
57.3
57.3
57.7
59.1
54.7
58.0
59.1
58.5
58.5
58.5
61.5
61.5
61.5
55.0
55.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
797
259
259
259
372
372
372
925
925
925
990
990
990
2,124
2,124
2,124
9,730
9,730
1,003
1,003
1,003
334
334
334
616
616
616
744
744
744
75
1,035
314
1,425
1,425
902
902
902
435
435
435
1,005
1,005
13,862
6,369
6,369
6,369
8,775
8,775
8,775
17,730
17,730
17,730
19,220
19,220
19,220
40,708
40,708
40,708
195,368
154,845
28,282
28,282
28,282
10,394
10,394
10,394
11,797
11,797
11,797
17,273
17,273
17,273
1,823
19,637
7,596
29,057
27,346
18,690
18,690
18,690
9,470
9,470
9,470
25,235
25,235
Coil
Latent
Load
Btu/h
308
1,430
1,430
1,430
1,096
1,096
1,096
1,494
1,494
1,494
1,603
1,603
1,603
3,631
3,631
3,631
17,976
18,247
13,513
13,513
13,513
4,960
4,960
4,960
624
624
624
1,481
1,481
1,481
75
265
1,033
1,373
1,870
1,012
1,012
1,012
1,133
1,133
1,133
3,625
3,625
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 79 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 348
BC Hydronic AHU
BC Hydronic AHU
spc_CC 108 C_0
Zone - 120
Zone - 120
spc_CC 106 Mechanical C_0
Zone - 121
Zone - 121
spc_CC 203 Storage_0
Zone - 122
Zone - 122
spc_CC 202 Storage_0
Zone - 123
Zone - 123
spc_CC 201 Eating Area C_0
Zone - 124
Zone - 124
Campus Center Dual Deck
Campus Center Dual Deck
spc_CC Class 122-126 C_0
Zone - 119
Zone - 119
Campus Center FC
Campus Center FC
spc_CC 228 Comp C_0
Zone - 125
Zone - 125
Bookstore 1
Zone - 362
Zone - 362
Bookstore 2
Zone - 363
Zone - 363
Bookstore 3
Zone - 364
Zone - 364
Bookstore 4
Zone - 365
Zone - 365
Bookstore 5
Zone - 366
Zone - 366
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
518
4,592
4,592
381
381
381
530
530
530
159
159
159
133
133
133
1,974
1,974
1,974
3,176
3,176
1,023
1,023
1,023
1,023
1,023
519
519
519
915
915
915
915
915
915
915
915
915
915
915
915
915
915
915
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
9 /12
9 /12
9 /12
9 /12
10 /14
6 /18
6 /18
6 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
80
80
79
79
79
76
76
76
76
76
76
73
73
73
73
73
73
79
79
70
70
70
70
70
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
63
63
64
64
64
67
67
67
67
67
67
63
63
63
63
63
63
62
62
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.9
72.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
55.0
55.2
55.2
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.1
57.1
57.1
57.1
57.1
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
1,005
6,464
6,464
797
797
797
480
480
480
556
556
556
430
430
430
1,808
1,808
1,808
4,073
4,073
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
404
404
404
404
404
404
404
404
19,025
120,862
101,266
12,551
12,551
12,551
11,849
11,849
11,849
8,761
8,761
8,761
6,778
6,778
6,778
28,473
28,473
28,473
68,413
57,628
64,980
64,980
64,980
64,980
64,980
17,432
17,432
17,432
11,760
11,760
11,760
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
10,160
1,924
14,942
6,374
167
167
167
761
761
761
277
277
277
137
137
137
4,445
4,445
4,445
5,787
5,745
3,184
3,184
3,184
3,184
3,184
1,513
1,513
1,513
3,754
3,754
3,754
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
2,839
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /17
9 /17
9 /13
9 /13
9 /13
9 /13
9 /14
7 /18
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
77
77
77
76
76
76
76
76
76
76
76
76
75
75
75
75
75
75
77
77
73
73
73
73
73
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
76
67
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
65
65
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
55.0
55.8
58.3
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.9
57.4
57.4
57.4
57.4
57.4
55.7
55.7
55.7
48.1
48.1
48.1
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
49.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,005
6,464
6,464
784
784
784
477
477
477
554
554
554
414
414
414
1,746
1,746
1,746
3,974
3,459
3,917
3,917
3,917
3,917
3,917
958
958
958
441
441
441
404
404
404
404
404
404
404
404
404
404
404
404
25,235
150,199
134,479
15,748
15,748
15,748
15,813
15,813
15,813
13,075
13,075
13,075
9,068
9,068
9,068
33,559
33,559
33,559
87,263
75,402
69,485
69,485
69,485
69,485
69,485
22,424
22,424
22,424
18,552
18,552
18,552
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
17,188
Coil
Latent
Load
Btu/h
3,625
27,722
25,060
1,787
1,787
1,787
1,129
1,129
1,129
379
379
379
204
204
204
12,956
12,956
12,956
16,454
17,396
6,613
6,613
6,613
6,613
6,613
2,598
2,598
2,598
6,278
6,278
6,278
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
5,361
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 80 of 100
SPACE
System Zone Room
Floor
Area
ft²
Bookstore 6
Peak
Zone - 367
Peak
Zone - 367
Block
Campus Center Packg RTU-1
Peak
Campus Center Packg RTU-1
Block
spc_DM FC-Music Office_0
Peak
Zone - 137
Peak
Zone - 137
Block
Peak
spc_DM FC-5-2/5-3/PHP-5-3 Aud Corridor_0
Zone - 138
Peak
Zone - 138
Block
spc_DM FC 3-1 Dress Rms Int_0 Peak
Zone - 139
Peak
Zone - 139
Block
spc_DM FC 3-1 Dress Rms_0
Peak
Zone - 140
Peak
Zone - 140
Block
Drama/Music Fan Coil
Peak
Drama/Music Fan Coil
Block
spc_HP-9 Office_0
Peak
Zone - 126
Peak
Zone - 126
Block
spc_DM HP-7 Storage_0
Peak
Zone - 127
Peak
Zone - 127
Block
spc_DM HP-7 Dress Rm_0
Peak
Zone - 128
Peak
Zone - 128
Block
spc_DM HP 3/4 Class_0
Peak
Zone - 129
Peak
Zone - 129
Block
spc_DM HP-2 Class_0
Peak
Zone - 130
Peak
Zone - 130
Block
spc_DM HP-5 Performance Rm_0 Peak
Zone - 131
Peak
Zone - 131
Block
spc_DM HP-10 Prop Rm_0
Peak
Zone - 132
Peak
Zone - 132
Block
spc_DM HP-1 Main Corridor_0
Peak
Zone - 133
Peak
Zone - 133
Block
915
915
915
6,007
6,007
338
338
338
892
892
892
267
267
267
327
327
327
1,824
1,824
121
121
121
57
57
57
9,797
9,797
9,797
926
926
926
569
569
569
1,176
1,176
1,176
1,131
1,131
1,131
7,381
7,381
7,381
Project Name:
Dataset Name:
SBCC TRACE.TRC
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
10 /16
10 /16
9 /17
9 /12
9 /12
10 /15
10 /15
10 /15
10 /15
6 /9
6 /9
11 /13
11 /13
9 /12
9 /12
7 /18
7 /18
9 /11
9 /11
76
76
76
76
76
79
79
79
75
75
75
76
76
76
79
79
79
76
76
73
73
73
80
80
80
80
80
80
62
62
62
71
71
71
73
73
73
73
73
73
70
70
70
66
66
66
66
66
64
64
64
66
66
66
66
66
66
64
64
64
67
67
63
63
63
63
63
63
63
63
63
58
58
58
58
58
58
63
63
63
65
65
65
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
49.4
49.4
49.4
51.0
51.0
56.4
56.4
56.4
54.3
54.3
54.3
44.5
44.5
44.5
58.3
58.3
58.3
55.7
55.7
57.0
57.0
57.0
54.8
54.8
54.8
51.3
51.3
51.3
55.4
55.4
55.4
59.2
59.2
59.2
53.5
53.5
53.5
57.4
57.4
57.4
56.2
56.2
56.2
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
10,160
10,160
10,160
79,989
79,989
8,123
8,123
8,123
9,831
9,831
9,831
2,946
2,946
2,946
8,853
8,853
8,853
29,753
27,815
4,747
4,747
4,747
261
261
261
99,554
99,554
99,554
21,837
21,837
21,837
35,452
35,452
35,452
27,637
27,637
27,637
36,017
36,017
36,017
106,822
106,822
106,822
2,839
2,839
2,839
19,459
19,459
633
633
633
1,432
1,432
1,432
1,098
1,098
1,098
269
269
269
3,432
4,394
263
263
263
35
35
35
25,148
25,148
25,148
2,451
2,451
2,451
1,082
1,082
1,082
4,324
4,324
4,324
1,740
1,740
1,740
9,194
9,194
9,194
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /17
9 /13
9 /13
7 /16
7 /16
9 /16
9 /16
7 /16
7 /16
9 /13
9 /13
7 /15
7 /15
7 /17
7 /17
9 /11
9 /11
76
76
76
76
76
76
76
76
75
75
75
77
77
77
79
79
79
76
76
75
75
75
76
76
76
77
77
77
76
76
76
75
75
75
77
77
77
75
75
75
70
70
70
66
66
66
66
66
67
67
67
66
66
66
67
67
67
64
64
64
67
67
65
65
65
66
66
66
67
67
67
66
66
66
65
65
65
66
66
66
66
66
66
63
63
63
49.4
49.4
49.4
51.0
51.0
56.5
56.5
56.5
54.3
54.3
54.3
45.0
45.0
45.0
58.3
58.3
58.3
55.8
56.8
57.6
57.6
57.6
55.8
55.8
55.8
51.5
51.5
51.5
59.2
59.2
59.2
60.5
60.5
60.5
59.5
59.5
59.5
57.8
57.8
57.8
56.2
56.2
56.2
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
404
404
404
3,418
3,418
466
466
466
498
498
498
96
96
96
579
579
579
1,639
1,639
284
284
284
14
14
14
4,309
4,309
4,309
1,177
1,177
1,177
2,491
2,491
2,491
1,342
1,342
1,342
2,211
2,211
2,211
6,059
6,059
6,059
17,188
17,188
17,188
126,914
126,914
12,772
12,772
12,772
21,797
21,797
21,797
2,242
2,242
2,242
10,451
10,451
10,451
47,261
42,971
6,446
6,446
6,446
1,151
1,151
1,151
104,158
104,158
104,158
33,229
33,229
33,229
39,761
39,761
39,761
38,930
38,930
38,930
57,496
57,496
57,496
120,423
120,423
120,423
Coil
Latent
Load
Btu/h
5,361
5,361
5,361
35,683
35,683
1,763
1,763
1,763
1,818
1,818
1,818
2,311
2,311
2,311
330
330
330
6,222
7,103
408
408
408
120
120
120
68,283
68,283
68,283
5,820
5,820
5,820
3,265
3,265
3,265
8,980
8,980
8,980
2,459
2,459
2,459
11,397
11,397
11,397
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 81 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_DM HP-9 Class_0
Zone - 148
Zone - 148
spc_DM HP-6 Office_0
Zone - 149
Zone - 149
spc_DM HP-8 Class1_0
Zone - 150
Zone - 150
spc_DM PHP-5-2 Offices_0
Zone - 151
Zone - 151
spc_PHP-2-1 Cargo Elevator_0
Zone - 152
Zone - 152
spc_DM PRP-5-1 Restroom_0
Zone - 153
Zone - 153
spc_DM PRP-5-1 Restroom1_0
Zone - 154
Zone - 154
Drama/Music HP
Drama/Music HP
spc_AC-1 Auditorium_0
Zone - 141
Zone - 141
spc_DM AN-2 Corridor_0
Zone - 142
Zone - 142
spc_DM AC-2 Rehearsal Rm_0
Zone - 143
Zone - 143
spc_DM ZN-1 Class_0
Zone - 144
Zone - 144
spc_DM ZN-3 Hall_0
Zone - 145
Zone - 145
spc_DM Zn-3 Offices_0
Zone - 146
Zone - 146
spc_ZN-3 Conf_0
Zone - 147
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
192
192
192
220
220
220
592
592
592
292
292
292
122
122
122
848
848
848
1,177
1,177
1,177
24,602
24,602
3,790
3,790
3,790
701
701
701
1,135
1,135
1,135
417
417
417
209
209
209
177
177
177
405
405
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
10 /15
10 /15
6 /9
6 /9
10 /15
10 /15
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
10 /16
9 /12
10 /15
10 /15
7 /17
7 /17
10 /15
10 /15
6 /18
6 /18
10 /16
10 /16
10 /16
10 /16
6 /10
80
80
80
62
62
62
80
80
80
79
79
79
79
79
79
79
79
79
79
79
79
73
73
80
80
80
75
75
75
80
80
80
70
70
70
79
79
79
79
79
79
65
65
63
63
63
58
58
58
63
63
63
64
64
64
64
64
64
64
64
64
64
64
64
63
63
63
63
63
66
66
66
63
63
63
63
63
63
64
64
64
64
64
64
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
80.0
80.0
80.0
73.1
73.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
51.3
51.3
51.3
58.2
58.2
58.2
51.3
51.3
51.3
52.2
52.2
52.2
58.6
58.6
58.6
79.6
79.6
79.6
79.6
79.6
79.6
58.9
58.9
54.9
54.9
54.9
55.9
55.9
55.9
50.7
50.7
50.7
56.6
56.6
56.6
49.9
49.9
49.9
51.7
51.7
51.7
50.6
50.6
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
24
24
24
64
64
64
206
206
1,946
1,946
1,946
10,408
10,408
10,408
6,020
6,020
6,020
2,564
2,564
2,564
4,056
4,056
4,056
538
538
538
747
747
747
358,606
299,869
74,299
74,299
74,299
11,804
11,804
11,804
10,848
10,848
10,848
20,443
20,443
20,443
583
583
583
1,443
1,443
1,443
4,907
4,907
492
492
492
311
311
311
1,521
1,521
1,521
545
545
545
99
99
99
-2,632
-2,632
-2,632
-3,655
-3,655
-3,655
40,918
47,013
9,753
9,753
9,753
1,126
1,126
1,126
2,908
2,908
2,908
1,296
1,296
1,296
169
169
169
330
330
330
1,311
1,311
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
76
76
76
65
65
65
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
77
77
75
75
75
77
77
77
73
73
73
77
77
77
76
76
76
77
77
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
65
65
65
67
67
67
67
67
67
67
67
51.4
51.4
51.4
58.8
58.8
58.8
51.5
51.5
51.5
52.4
52.4
52.4
58.8
58.8
58.8
79.7
79.7
79.7
79.7
79.7
79.7
59.7
62.3
55.5
55.5
55.5
55.9
55.9
55.9
51.3
51.3
51.3
56.7
56.7
56.7
51.4
51.4
51.4
52.3
52.3
52.3
53.5
53.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
84
84
84
678
678
678
261
261
261
116
116
116
271
271
271
1,356
1,356
1,356
1,883
1,883
1,883
22,534
22,534
3,889
3,889
3,889
656
656
656
458
458
458
1,188
1,188
1,188
24
24
24
64
64
64
206
206
5,018
5,018
5,018
11,069
11,069
11,069
6,298
6,298
6,298
2,691
2,691
2,691
6,557
6,557
6,557
5,343
5,343
5,343
7,418
7,418
7,418
445,988
374,351
83,988
83,988
83,988
13,640
13,640
13,640
13,026
13,026
13,026
22,815
22,815
22,815
715
715
715
1,748
1,748
1,748
5,430
5,430
1,203
1,203
1,203
475
475
475
4,129
4,129
4,129
1,517
1,517
1,517
288
288
288
-46,142
-46,142
-46,142
-64,061
-64,061
-64,061
-1,859
7,013
26,500
26,500
26,500
1,430
1,430
1,430
7,893
7,893
7,893
2,691
2,691
2,691
468
468
468
919
919
919
3,494
3,494
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 82 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 147
spc_DM Scene Shop HV-1_0
Zone - 155
Zone - 155
Drama/Music MZU
Drama/Music MZU
spc_EBS 217/Storage C_0
Zone - 156
Zone - 156
spc_EBS 215 Class C_0
Zone - 157
Zone - 157
spc_EBS 209 Class C_0
Zone - 158
Zone - 158
spc_EBS 210 Class C_0
Zone - 159
Zone - 159
spc_EBS 109/127 Lobby C_0
Zone - 160
Zone - 160
spc_EBS 125 Class C_0
Zone - 161
Zone - 161
spc_EBS 102 Class C_0
Zone - 162
Zone - 162
spc_EBS 123 Class C_0
Zone - 163
Zone - 163
spc_EBS 119 Offices C_0
Zone - 164
Zone - 164
spc_EBS 119 Office C_0
Zone - 165
Zone - 165
spc_EBS 116 Office C_0
Zone - 166
Zone - 166
spc_EBS 110-113 Office UC_0
Zone - 167
Zone - 167
spc_EBS 114 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
405
1,711
1,711
1,711
8,545
8,545
2,046
2,046
2,046
758
758
758
1,358
1,358
1,358
1,333
1,333
1,333
1,771
1,771
1,771
396
396
396
1,332
1,332
1,332
1,622
1,622
1,622
399
399
399
306
306
306
156
156
156
515
515
515
893
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /10
10 /13
10 /13
9 /16
7 /15
7 /15
7 /16
7 /16
10 /15
10 /15
7 /18
7 /18
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
10 /14
65
77
77
77
77
77
77
77
77
76
76
76
80
80
80
73
73
73
75
75
75
73
73
73
73
73
73
73
73
73
75
75
75
75
75
75
73
73
73
73
73
73
79
58
59
59
59
67
67
66
66
66
66
66
66
63
63
63
65
65
65
66
66
66
65
65
65
65
65
65
65
65
65
66
66
66
66
66
66
65
65
65
65
65
65
62
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
50.6
57.7
57.7
57.7
55.4
55.4
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
206
1,561
1,561
1,561
8,045
8,045
931
931
931
493
493
493
1,547
1,547
1,547
1,511
1,511
1,511
744
744
744
473
473
473
2,019
2,019
2,019
1,486
1,486
1,486
309
309
309
177
177
177
220
220
220
624
624
624
1,093
4,907
24,799
24,799
24,799
149,125
129,890
18,050
18,050
18,050
9,553
9,553
9,553
29,992
29,992
29,992
29,286
29,286
29,286
14,421
14,421
14,421
9,178
9,178
9,178
39,142
39,142
39,142
28,811
28,811
28,811
5,997
5,997
5,997
3,436
3,436
3,436
4,262
4,262
4,262
12,097
12,097
12,097
21,186
1,311
3,134
3,134
3,134
20,027
30,017
3,114
3,114
3,114
2,661
2,661
2,661
3,489
3,489
3,489
4,607
4,607
4,607
2,924
2,924
2,924
1,369
1,369
1,369
4,604
4,604
4,604
5,608
5,608
5,608
1,057
1,057
1,057
811
811
811
368
368
368
1,214
1,214
1,214
2,014
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /14
9 /14
9 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /14
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
75
75
75
75
75
75
73
73
73
73
73
73
75
75
75
75
75
75
75
75
75
73
73
73
73
73
73
77
67
66
66
66
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
66
53.5
58.2
58.2
58.2
55.9
57.5
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
206
1,561
1,561
1,561
8,045
8,045
903
903
903
493
493
493
1,515
1,515
1,515
1,493
1,493
1,493
744
744
744
473
473
473
2,019
2,019
2,019
1,454
1,454
1,454
309
309
309
177
177
177
220
220
220
624
624
624
1,079
5,430
30,462
30,462
30,462
171,824
156,601
40,996
40,996
40,996
17,369
17,369
17,369
45,366
45,366
45,366
45,809
45,809
45,809
35,058
35,058
35,058
14,006
14,006
14,006
55,862
55,862
55,862
46,115
46,115
46,115
10,829
10,829
10,829
6,764
6,764
6,764
6,557
6,557
6,557
19,460
19,460
19,460
22,361
Coil
Latent
Load
Btu/h
3,494
10,580
10,580
10,580
53,975
55,726
4,331
4,331
4,331
4,766
4,766
4,766
9,476
9,476
9,476
8,212
8,212
8,212
4,199
4,199
4,199
2,548
2,548
2,548
8,567
8,567
8,567
9,995
9,995
9,995
1,822
1,822
1,822
1,398
1,398
1,398
677
677
677
2,235
2,235
2,235
5,495
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 83 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 168
Zone - 168
spc_EBS 115 Class C_0
Zone - 169
Zone - 169
spc_EBS 209 Class UC_0
Zone - 172
Zone - 172
spc_EBS 210 Class C_1
Zone - 173
Zone - 173
spc_EBS 215 Class C_1
Zone - 174
Zone - 174
spc_EBS 218 Office C_0
Zone - 175
Zone - 175
spc_EBS 216 Office C_0
Zone - 176
Zone - 176
EBS VAV
EBS VAV
spc_H 326 Class C_0
Zone - 206
Zone - 206
spc_H 328 Class C_0
Zone - 207
Zone - 207
spc_H 328 Office C_0
Zone - 208
Zone - 208
Humanities Fan Coil
Humanities Fan Coil
spc_H 104/107/112 Art C_0
Zone - 177
Zone - 177
spc_H 102 Class C_0
Zone - 178
Zone - 178
spc_H 106 Office C_0
Zone - 179
Zone - 179
spc_H 2444 Class C_0
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
893
893 10 /14
1,659
9 /16
1,659
1,659
9 /16
1,334
7 /16
1,334
1,334
7 /16
1,334
7 /16
1,334
1,334
7 /16
790
7 /18
790
790
7 /18
70
7 /18
70
70
7/18
74
7 /17
74
74
7 /17
18,147
18,147 7 /17
845
5 /17
845
845
5 /17
1,818 7 /16
1,818
1,818 7 /16
300
7 /12
300
300
7 /12
2,963
2,963 7 /17
7,121 7 /16
7,121
7,121 7 /16
1,004 7 /16
1,004
1,004 7 /16
229
7 /17
229
229
7 /17
555
7 /16
79
79
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
72
72
72
76
76
76
73
73
73
75
75
76
76
76
76
76
76
75
75
75
76
62
62
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
63
63
63
66
66
66
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
54.3
54.3
54.3
56.6
56.6
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
1,093
1,093
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,925
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,288
5,288
5,288
627
627
627
122
122
122
346
21,186
21,186
31,380
31,380
31,380
16,818
16,818
16,818
16,818
16,818
16,818
14,759
14,759
14,759
2,665
2,665
2,665
826
826
826
308,677
289,380
76,201
76,201
76,201
24,051
24,051
24,051
4,645
4,645
4,645
104,897
101,595
91,368
91,368
91,368
10,835
10,835
10,835
2,102
2,102
2,102
5,987
2,014
2,014
6,149
6,149
6,149
4,685
4,685
4,685
4,685
4,685
4,685
2,731
2,731
2,731
166
166
166
195
195
195
52,452
52,299
2,350
2,350
2,350
6,371
6,371
6,371
631
631
631
9,352
9,537
24,945
24,945
24,945
3,519
3,519
3,519
604
604
604
1,944
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /14
9 /16
9 /16
7 /16
7 /16
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
7 /17
7 /15
7 /15
9 /16
9 /16
9 /17
9 /17
9 /16
77
77
77
77
77
76
76
76
76
76
76
73
73
73
73
73
73
75
75
75
75
75
73
73
73
76
76
76
76
76
76
75
75
77
77
77
77
77
77
76
76
76
77
66
66
67
67
67
66
66
66
66
66
66
65
65
65
65
65
65
66
66
66
66
66
65
65
65
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
58.0
58.0
58.0
50.0
50.0
50.0
57.2
57.2
57.2
56.7
57.1
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,079
1,079
1,619
1,619
1,619
868
868
868
868
868
868
761
761
761
138
138
138
43
43
43
15,801
14,929
4,888
4,888
4,888
980
980
980
236
236
236
6,103
6,103
5,284
5,284
5,284
600
600
600
119
119
119
331
22,361
22,361
49,825
49,825
49,825
30,579
30,579
30,579
30,579
30,579
30,579
23,381
23,381
23,381
3,913
3,913
3,913
1,626
1,626
1,626
504,179
486,608
92,686
92,686
92,686
49,932
49,932
49,932
8,423
8,423
8,423
151,042
148,011
99,527
99,527
99,527
11,228
11,228
11,228
2,209
2,209
2,209
6,204
Coil
Latent
Load
Btu/h
5,495
5,495
11,570
11,570
11,570
8,391
8,391
8,391
8,391
8,391
8,391
5,082
5,082
5,082
305
305
305
336
336
336
97,796
94,521
5,460
5,460
5,460
11,390
11,390
11,390
1,341
1,341
1,341
18,190
17,762
43,603
43,603
43,603
6,979
6,979
6,979
1,184
1,184
1,184
3,856
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 84 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 180
Zone - 180
spc_H 245A/B Class C_0
Zone - 181
Zone - 181
spc_H 226/A office C_0
Zone - 182
Zone - 182
spc_H 208-217 Office C_0
Zone - 183
Zone - 183
spc_H 225 Office C_0
Zone - 184
Zone - 184
spc_H 242/207 Corridor C_0
Zone - 185
Zone - 185
spc_H 123U Art AH-1/23_0
Zone - 186
Zone - 186
spc_H 111 Class C_0
Zone - 187
Zone - 187
spc_H 221/220/204 Class C_0
Zone - 188
Zone - 188
spc_H 232A Class C_0
Zone - 189
Zone - 189
spc_H 239 Class Office_0
Zone - 190
Zone - 190
spc_H 237 Office C_0
Zone - 191
Zone - 191
spc_H 236 Office C_0
Zone - 192
Zone - 192
spc_H 241 Class C_0
Zone - 193
Zone - 193
spc_H 309-318 Offices C_0
Zone - 194
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
555
555
1,686
1,686
1,686
272
272
272
1,065
1,065
1,065
267
267
267
4,126
4,126
4,126
2,482
2,482
2,482
1,805
1,805
1,805
4,564
4,564
4,564
1,111
1,111
1,111
306
306
306
90
90
90
272
272
272
571
571
571
1,012
1,012
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /17
7 /17
11 /13
11 /13
11 /14
11 /14
11 /14
11 /14
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
11 /14
76
76
75
75
75
71
71
71
73
73
73
73
73
73
79
79
79
75
75
75
76
76
76
77
77
77
76
76
76
77
77
77
75
75
75
75
75
75
76
76
76
73
73
66
66
66
66
66
58
58
58
60
60
60
60
60
60
64
64
64
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
60
60
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
346
346
2,157
2,157
2,157
798
798
798
3,496
3,496
3,496
765
765
765
1,412
1,412
1,412
2,382
2,382
2,382
1,127
1,127
1,127
3,577
3,577
3,577
693
693
693
311
311
311
48
48
48
145
145
145
356
356
356
4,319
4,319
5,987
5,987
37,265
37,265
37,265
13,783
13,783
13,783
60,401
60,401
60,401
13,211
13,211
13,211
24,400
24,400
24,400
41,156
41,156
41,156
19,474
19,474
19,474
61,807
61,807
61,807
11,982
11,982
11,982
5,382
5,382
5,382
828
828
828
2,500
2,500
2,500
6,155
6,155
6,155
74,623
74,623
1,944
1,944
5,523
5,523
5,523
89
89
89
766
766
766
192
192
192
3,332
3,332
3,332
8,130
8,130
8,130
6,325
6,325
6,325
15,809
15,809
15,809
3,891
3,891
3,891
1,060
1,060
1,060
238
238
238
719
719
719
1,999
1,999
1,999
728
728
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /14
9 /14
9 /15
9 /15
9 /15
9 /15
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /15
7 /15
9 /16
9 /16
7 /15
7 /15
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /15
77
77
77
77
77
77
77
77
78
78
78
78
78
78
77
77
77
76
76
76
77
77
77
77
77
77
77
77
77
77
77
77
76
76
76
76
76
76
77
77
77
78
78
67
67
67
67
67
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
331
331
2,071
2,071
2,071
743
743
743
2,999
2,999
2,999
665
665
665
1,401
1,401
1,401
2,313
2,313
2,313
1,078
1,078
1,078
3,577
3,577
3,577
663
663
663
311
311
311
47
47
47
142
142
142
341
341
341
3,657
3,657
6,204
6,204
40,964
40,964
40,964
15,383
15,383
15,383
74,566
74,566
74,566
13,581
13,581
13,581
25,840
25,840
25,840
45,783
45,783
45,783
20,181
20,181
20,181
67,488
67,488
67,488
12,417
12,417
12,417
5,994
5,994
5,994
871
871
871
2,628
2,628
2,628
6,379
6,379
6,379
87,004
87,004
Coil
Latent
Load
Btu/h
3,856
3,856
11,713
11,713
11,713
999
999
999
4,843
4,843
4,843
1,216
1,216
1,216
9,229
9,229
9,229
17,267
17,267
17,267
12,544
12,544
12,544
27,948
27,948
27,948
7,718
7,718
7,718
1,874
1,874
1,874
467
467
467
1,408
1,408
1,408
3,965
3,965
3,965
4,603
4,603
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 85 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 194
spc_H 240 Class C_0
Zone - 195
Zone - 195
spc_H 300 Restrooms C_0
Zone - 196
Zone - 196
spc_H 322 Office C_0
Zone - 197
Zone - 197
spc_H 323 Office C_0
Zone - 198
Zone - 198
spc_H 300H Hall C_0
Zone - 199
Zone - 199
spc_H 202 Class C_0
Zone - 200
Zone - 200
spc_H 205 Office C_0
Zone - 201
Zone - 201
spc_H 205/203 Class C_0
Zone - 202
Zone - 202
spc_H 232B Office C_0
Zone - 203
Zone - 203
spc_H 223 Class C_0
Zone - 204
Zone - 204
spc_H 223U Storage C_0
Zone - 205
Zone - 205
spc_H 306 Class C_0
Zone - 211
Zone - 211
spc_H 308 Class H_0
Zone - 212
Zone - 212
spc_H 301-307 Classes C_0
Zone - 213
Zone - 213
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,012
818
818
818
339
339
339
265
265
265
265
265
265
3,593
3,593
3,593
1,118
1,118
1,118
270
270
270
846
846
846
161
161
161
616
616
616
165
165
165
727
727
727
512
512
512
3,348
3,348
3,348
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
11 /14
7 /15
7 /15
9 /17
9 /17
11 /14
11 /14
7 /17
7 /17
10 /16
10 /16
8/10
8 /10
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
7 /16
7 /16
7 /15
7 /15
7 /16
7 /16
7 /16
7 /16
7 /15
7 /15
73
77
77
77
76
76
76
73
73
73
75
75
75
79
79
79
67
67
67
75
75
75
76
76
76
75
75
75
76
76
76
77
77
77
76
76
76
76
76
76
77
77
77
60
66
66
66
67
67
67
60
60
60
66
66
66
64
64
64
61
61
61
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
4,319
642
642
642
542
542
542
1,069
1,069
1,069
141
141
141
3,898
3,898
3,898
2,401
2,401
2,401
144
144
144
528
528
528
86
86
86
385
385
385
51
51
51
454
454
454
320
320
320
2,748
2,748
2,748
74,623
11,100
11,100
11,100
14,193
14,193
14,193
18,478
18,478
18,478
2,434
2,434
2,434
67,353
67,353
67,353
41,487
41,487
41,487
2,483
2,483
2,483
9,121
9,121
9,121
1,483
1,483
1,483
6,648
6,648
6,648
876
876
876
7,841
7,841
7,841
5,526
5,526
5,526
47,476
47,476
47,476
728
2,834
2,834
2,834
619
619
619
190
190
190
700
700
700
9,908
9,908
9,908
3,433
3,433
3,433
714
714
714
2,962
2,962
2,962
426
426
426
2,159
2,159
2,159
250
250
250
2,546
2,546
2,546
1,795
1,795
1,795
11,597
11,597
11,597
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /15
7 /15
7 /15
9 /17
9 /17
9 /15
9 /15
9 /17
9 /17
9 /16
9 /16
9 /11
9 /11
9 /17
9 /17
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
9 /15
9 /15
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
78
77
77
77
76
76
76
78
78
78
76
76
76
77
77
77
70
70
70
76
76
76
77
77
77
76
76
76
77
77
77
78
78
78
76
76
76
76
76
76
76
76
76
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
63
63
63
67
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
3,657
642
642
642
210
210
210
890
890
890
138
138
138
3,839
3,839
3,839
2,239
2,239
2,239
141
141
141
505
505
505
84
84
84
368
368
368
47
47
47
441
441
441
311
311
311
2,733
2,733
2,733
87,004
12,091
12,091
12,091
14,647
14,647
14,647
21,157
21,157
21,157
2,558
2,558
2,558
126,357
126,357
126,357
45,716
45,716
45,716
2,609
2,609
2,609
9,452
9,452
9,452
1,558
1,558
1,558
6,890
6,890
6,890
878
878
878
19,161
19,161
19,161
13,504
13,504
13,504
102,755
102,755
102,755
Coil
Latent
Load
Btu/h
4,603
5,010
5,010
5,010
4,236
4,236
4,236
1,203
1,203
1,203
1,371
1,371
1,371
24,964
24,964
24,964
5,771
5,771
5,771
1,399
1,399
1,399
5,875
5,875
5,875
835
835
835
4,282
4,282
4,282
357
357
357
4,551
4,551
4,551
3,208
3,208
3,208
20,961
20,961
20,961
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 86 of 100
SPACE
System Zone Room
spc_H 301 Class C_0
Peak
Zone - 214
Peak
Zone - 214
Block
spc_H 3281 Hall C_0
Peak
Zone - 215
Peak
Zone - 215
Block
Humanities VAV
Peak
Humanities VAV
Block
spc_IDC 335 Office C_0
Peak
Zone - 220
Peak
Zone - 220
Block
spc_IDC 313 Wrk Rm_0
Peak
Zone - 221
Peak
Zone - 221
Block
spc_IDC 317 Wrk Rm C_0
Peak
Zone - 222
Peak
Zone - 222
Block
spc_IDC 329 C_0
Peak
Zone - 223
Peak
Zone - 223
Block
IDC Fan Coil
Peak
IDC Fan Coil
Block
Peak
spc_IDC 102/103/104/109 Int Class_0
Zone - 216
Peak
Zone - 216
Block
spc_IDC 205 Class C_0
Peak
Zone - 217
Peak
Zone - 217
Block
spc_IDC 211/210 Class_0
Peak
Zone - 218
Peak
Zone - 218
Block
spc_IDC 333 Office_0
Peak
Zone - 219
Peak
Zone - 219
Block
IDC VAV
Peak
IDC VAV
Block
spc_LRC 140-01-08 C_0
Peak
Zone - 224
Peak
Zone - 224
Block
spc_LRC 140-09 C_0
Peak
Zone - 225
Peak
Zone - 225
Block
spc_LRC 13-15 C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
633
633
633
228
228
228
42,441
42,441
107
107
107
206
206
206
171
171
171
102
102
102
586
586
3,318
3,318
3,318
460
460
460
1,001
1,001
1,001
414
414
414
5,194
5,194
1,843
1,843
1,843
250
250
250
153
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
10 /15
7 /17
7 /17
7 /16
7 /16
7 /16
7/16
7 /16
7 /16
7 /16
10 /15
10 /15
10 /15
10 /15
10 /15
10 /15
10 /17
10 /17
10 /15
6 /10
6 /10
9 /12
9 /12
9 /11
76
76
76
76
76
76
80
80
75
75
75
76
76
76
76
76
76
76
76
76
76
76
80
80
80
80
80
80
80
80
80
77
77
77
80
80
65
65
65
73
73
73
70
66
66
66
66
66
66
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
63
63
63
63
63
63
64
64
64
63
63
58
58
58
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.1
72.1
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
395
395
395
53
53
53
41,826
37,423
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,694
1,694
1,694
859
859
859
511
511
511
180
180
180
3,244
3,237
1,595
1,595
1,595
797
797
797
632
6,823
6,823
6,823
911
911
911
727,491
650,911
1,280
1,280
1,280
2,975
2,975
2,975
2,627
2,627
2,627
1,357
1,357
1,357
8,239
8,216
32,706
32,706
32,706
16,577
16,577
16,577
9,869
9,869
9,869
3,472
3,472
3,472
62,624
62,481
28,266
28,266
28,266
14,118
14,118
14,118
11,205
2,216
2,216
2,216
354
354
354
122,518
95,452
284
284
284
722
722
722
600
600
600
357
357
357
1,962
1,958
8,526
8,526
8,526
1,182
1,182
1,182
2,573
2,573
2,573
855
855
855
13,135
12,972
5,957
5,957
5,957
915
915
915
580
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /16
7 /16
7 /16
9 /16
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
7 /16
7 /16
9 /13
9 /13
9 /11
76
76
76
76
76
76
77
77
75
75
75
76
76
76
76
76
76
76
76
76
76
76
77
77
77
77
77
77
77
77
77
75
75
75
77
77
76
76
76
75
75
75
70
66
66
66
66
66
66
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
67
67
67
66
66
66
67
67
66
66
66
65
65
65
63
56.5
56.5
56.5
56.5
56.5
56.5
56.5
56.5
51.4
51.4
51.4
50.7
50.7
50.7
51.1
51.1
51.1
50.0
50.0
50.0
50.9
50.9
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
54.7
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
384
384
384
49
49
49
39,362
36,284
56
56
56
125
125
125
113
113
113
55
55
55
349
349
1,668
1,668
1,668
843
843
843
503
503
503
179
179
179
3,194
3,189
1,448
1,448
1,448
757
757
757
632
16,673
16,673
16,673
4,252
4,252
4,252
957,271
890,214
2,183
2,183
2,183
4,555
4,555
4,555
3,950
3,950
3,950
2,128
2,128
2,128
12,817
12,798
38,524
38,524
38,524
19,698
19,698
19,698
11,625
11,625
11,625
10,755
10,755
10,755
80,821
79,588
54,618
54,618
54,618
17,332
17,332
17,332
12,865
3,960
3,960
3,960
448
448
448
249,846
272,391
488
488
488
1,291
1,291
1,291
1,072
1,072
1,072
638
638
638
3,490
3,478
23,156
23,156
23,156
3,209
3,209
3,209
6,987
6,987
6,987
1,894
1,894
1,894
35,247
35,420
12,597
12,597
12,597
1,569
1,569
1,569
880
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 87 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 226
Zone - 226
spc_LRC 16 C_0
Zone - 227
Zone - 227
spc_LRC 17/18_0
Zone - 228
Zone - 228
spc_LRC 5 C (Study?)_0
Zone - 229
Zone - 229
spc_LRC 9 Storage_0
Zone - 230
Zone - 230
spc_LRC 10 Storage_0
Zone - 231
Zone - 231
spc_LRC 7 C_0
Zone - 232
Zone - 232
spc_LRC 8 Stair_0
Zone - 233
Zone - 233
spc_LRC Catalog C_0
Zone - 234
Zone - 234
spc_LRC Computer_0
Zone - 235
Zone - 235
spc_LRC 2/6_0
Zone - 236
Zone - 236
spc_LRC 1st RR C_0
Zone - 237
Zone - 237
spc_LRC 24_0
Zone - 238
Zone - 238
spc_LRC 25_0
Zone - 239
Zone - 239
spc_LRC 105 C Work_0
Zone - 240
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
153
153
66
66
66
94
94
94
57
57
57
29
29
29
24
24
24
119
119
119
302
302
302
56
56
56
525
525
525
137
137
137
226
226
226
564
564
564
325
325
325
62
62
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
10 /13
10 /13
10 /16
10 /16
7 /15
7 /15
7 /15
7 /15
6 /10
6/10
6 /18
6 /18
7 /18
7 /18
7 /18
7 /18
6 /17
6 /17
7 /15
7 /15
10 /16
10/16
10 /16
10 /16
7 /18
7 /18
7 /18
70
70
77
77
77
79
79
79
77
77
77
77
77
77
65
65
65
70
70
70
73
73
73
73
73
73
72
72
72
77
77
77
79
79
79
79
79
79
73
73
73
73
73
63
63
59
59
59
64
64
64
66
66
66
66
66
66
58
58
58
63
63
63
65
65
65
65
65
65
63
63
63
66
66
66
64
64
64
64
64
64
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
632
632
296
296
296
800
800
800
34
34
34
9
9
9
43
43
43
499
499
499
178
178
178
119
119
119
1,809
1,809
1,809
78
78
78
362
362
362
2,024
2,024
2,024
956
956
956
123
123
11,205
11,205
5,239
5,239
5,239
14,180
14,180
14,180
606
606
606
156
156
156
770
770
770
8,836
8,836
8,836
3,148
3,148
3,148
2,112
2,112
2,112
32,061
32,061
32,061
1,384
1,384
1,384
9,633
9,633
9,633
35,871
35,871
35,871
16,939
16,939
16,939
2,178
2,178
580
580
159
159
159
316
316
316
196
196
196
44
44
44
16
16
16
366
366
366
460
460
460
226
226
226
1,210
1,210
1,210
556
556
556
181
181
181
1,890
1,890
1,890
1,302
1,302
1,302
214
214
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /13
9 /13
9 /16
9 /16
9 /16
9 /16
9 /15
9 /15
6 /10
6 /10
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
9 /16
9 /16
10 /16
10 /16
9 /16
9 /16
7 /18
7 /18
7 /18
70
70
75
75
75
77
77
77
77
77
77
78
78
78
65
65
65
73
73
73
73
73
73
73
73
73
75
75
75
77
77
77
79
79
79
77
77
77
73
73
73
73
73
63
63
65
65
65
67
67
67
67
67
67
66
66
66
58
58
58
65
65
65
65
65
65
65
65
65
66
66
66
67
67
67
64
64
64
67
67
67
65
65
65
65
65
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
632
632
289
289
289
781
781
781
34
34
34
8
8
8
43
43
43
495
495
495
178
178
178
119
119
119
1,791
1,791
1,791
77
77
77
186
186
186
1,981
1,981
1,981
956
956
956
123
123
12,865
12,865
5,989
5,989
5,989
15,724
15,724
15,724
602
602
602
149
149
149
999
999
999
9,606
9,606
9,606
3,388
3,388
3,388
2,494
2,494
2,494
34,140
34,140
34,140
1,369
1,369
1,369
8,860
8,860
8,860
39,177
39,177
39,177
19,463
19,463
19,463
3,446
3,446
Coil
Latent
Load
Btu/h
880
880
417
417
417
710
710
710
392
392
392
63
63
63
19
19
19
757
757
757
592
592
592
392
392
392
2,556
2,556
2,556
1,032
1,032
1,032
996
996
996
4,243
4,243
4,243
2,256
2,256
2,256
397
397
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 88 of 100
SPACE
System Zone Room
Zone - 240
Block
spc_LRC Tables/124B C_0
Peak
Zone - 241
Peak
Zone - 241
Block
spc_LRC 120/122/123 Office C_0 Peak
Zone - 242
Peak
Zone - 242
Block
spc_LRC Tutor Lab C_0
Peak
Zone - 243
Peak
Zone - 243
Block
spc_LRC Lobby/112B Corridor C_0Peak
Zone - 244
Peak
Zone - 244
Block
spc_LRC Dir Offc C_0
Peak
Zone - 245
Peak
Zone - 245
Block
spc_LRC 108/111/115 Counter_0 Peak
Zone - 246
Peak
Zone - 246
Block
spc_LRC 149A_0
Peak
Zone - 247
Peak
Zone - 247
Block
spc_LRC 137 Work C_0
Peak
Zone - 248
Peak
Zone - 248
Block
spc_LRC 140-142 Director_0
Peak
Zone - 249
Peak
Zone - 249
Block
spc_LRC 145 Office C_0
Peak
Zone - 250
Peak
Zone - 250
Block
spc_LRC 146A Storage_0
Peak
Zone - 251
Peak
Zone - 251
Block
spc_LRC 146_0
Peak
Zone - 252
Peak
Zone - 252
Block
spc_LRC Library_0
Peak
Zone - 253
Peak
Zone - 253
Block
spc_LRC 140-14_0
Peak
Zone - 254
Peak
Zone - 254
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
62
647
647
647
58
58
58
63
63
63
582
582
582
36
36
36
335
335
335
25
25
25
59
59
59
38
38
38
23
23
23
14
14
14
80
80
80
0
0
0
42
42
42
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
10 /15
10 /15
6 /11
6 /11
7 /15
7 /15
7 /18
7 /18
6 /18
6 /18
7/15
7 /15
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
10 /16
10 /16
10 /13
10 /13
11 /12
11 /12
9 /12
9 /12
73
80
80
80
68
68
68
77
77
77
73
73
73
70
70
70
77
77
77
73
73
73
73
73
73
75
75
75
75
75
75
79
79
79
77
77
77
68
68
68
73
73
73
65
63
63
63
60
60
60
66
66
66
65
65
65
63
63
63
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
64
64
64
59
59
59
55
55
55
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
123
1,184
1,184
1,184
119
119
119
110
110
110
387
387
387
147
147
147
191
191
191
45
45
45
191
191
191
20
20
20
12
12
12
64
64
64
252
252
252
2,551
2,551
2,551
190
190
190
2,178
20,983
20,983
20,983
2,116
2,116
2,116
1,946
1,946
1,946
6,866
6,866
6,866
2,614
2,614
2,614
3,378
3,378
3,378
793
793
793
3,381
3,381
3,381
359
359
359
214
214
214
1,140
1,140
1,140
4,464
4,464
4,464
45,210
45,210
45,210
3,371
3,371
3,371
214
1,652
1,652
1,652
103
103
103
180
180
180
975
975
975
72
72
72
1,358
1,358
1,358
86
86
86
204
204
204
101
101
101
60
60
60
11
11
11
192
192
192
0
0
0
154
154
154
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /18
9 /16
9 /16
7 /12
7 /12
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
7 /18
7 /18
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
9 /14
9 /14
9 /11
9 /11
9 /12
9 /12
73
77
77
77
73
73
73
76
76
76
75
75
75
73
73
73
76
76
76
73
73
73
73
73
73
75
75
75
75
75
75
76
76
76
77
77
77
70
70
70
73
73
73
65
67
67
67
63
63
63
66
66
66
66
66
66
65
65
65
66
66
66
65
65
65
65
65
65
66
66
66
66
66
66
67
67
67
66
66
66
63
63
63
63
63
63
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
123
1,113
1,113
1,113
117
117
117
110
110
110
364
364
364
145
145
145
190
190
190
45
45
45
191
191
191
20
20
20
12
12
12
63
63
63
233
233
233
2,488
2,488
2,488
190
190
190
3,446
32,086
32,086
32,086
2,850
2,850
2,850
2,980
2,980
2,980
14,670
14,670
14,670
3,509
3,509
3,509
8,372
8,372
8,372
1,278
1,278
1,278
4,731
4,731
4,731
936
936
936
559
559
559
1,612
1,612
1,612
5,818
5,818
5,818
47,040
47,040
47,040
4,151
4,151
4,151
Coil
Latent
Load
Btu/h
397
4,480
4,480
4,480
178
178
178
312
312
312
1,365
1,365
1,365
155
155
155
2,288
2,288
2,288
159
159
159
378
378
378
174
174
174
104
104
104
35
35
35
535
535
535
0
0
0
223
223
223
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 89 of 100
SPACE
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
System Zone Room
Floor
Area
ft²
spc_LRC 140-03_0
Peak
Zone - 255
Peak
Zone - 255
Block
spc_LRC 101 Work C_0
Peak
Zone - 256
Peak
Zone - 256
Block
spc_LRC 108-110 Storage_0
Peak
Zone - 257
Peak
Zone - 257
Block
spc_LRC 109 Work_0
Peak
Zone - 258
Peak
Zone - 258
Block
LRC VAV
Peak
LRC VAV
Block
spc_OE 10WM Restrooms AH-2_0Peak
Zone - 259
Peak
Zone - 259
Block
spc_OE 112 Class C_0
Peak
Zone - 260
Peak
Zone - 260
Block
spc_OE 116 Class C_0
Peak
Zone - 261
Peak
Zone - 261
Block
spc_OE 180H/182 Class C_0
Peak
Zone - 262
Peak
Zone - 262
Block
spc_OE 180A Office C_0
Peak
Zone - 263
Peak
Zone - 263
Block
OE Pckg AH
Peak
OE Pckg AH
Block
spc_PE 108 Weight Rm HP3/4_0 Peak
Zone - 006
Peak
Zone - 006
Block
spc_PE Locker/RR HP-06/07_0 Peak
Zone - 008
Peak
Zone - 008
Block
Peak
spc_PE 302-310E Office Partially C_0
Zone - 011
Peak
Zone - 011
Block
PE Heat Pump
Peak
PE Heat Pump
Block
spc_PE Gym AH1_0
Peak
86
6 /10
86
86
6 /10
62
9 /17
62
62
9 /17
24
7 /15
24
24
7 /15
43
9 /17
43
43
9 /17
7,052
7,052
9 /16
172
7 /18
172
172
7/18
522 10 /15
522
522 10 /15
1,121 7 /18
1,121
1,121 7 /18
509
9 /11
509
509
9 /11
66
7 /17
66
66
7 /17
2,391
2,391 10 /14
3,594 9 /10
3,594
3,594 9 /10
1,968 7 /18
1,968
1,968 7 /18
498
7 /18
498
498
7 /18
6,061
6,061
7 /18
7,524
7 /17
Project Name:
Dataset Name:
SBCC TRACE.TRC
65
65
65
76
76
76
77
77
77
76
76
76
77
77
73
73
73
80
80
80
73
73
73
70
70
70
75
75
75
79
79
67
67
67
73
73
73
73
73
73
73
73
75
58
58
58
67
67
67
66
66
66
67
67
67
67
67
65
65
65
63
63
63
65
65
65
63
63
63
66
66
66
62
62
61
61
61
65
65
65
65
65
65
65
65
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.2
72.2
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.7
72.7
72.0
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
76.0
76.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
73.2
73.2
73.2
56.6
56.6
56.6
52.2
52.2
52.2
55.6
55.6
55.6
48.8
48.8
48.8
56.4
56.4
54.5
54.5
54.5
74.3
74.3
74.3
56.3
56.3
56.3
64.7
64.7
72.4
207
207
207
186
186
186
7
7
7
143
143
143
16,361
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
3,150
3,150
1,009
1,009
1,009
6,278
6,278
1,505
3,672
3,672
3,672
3,302
3,302
3,302
123
123
123
2,540
2,540
2,540
293,173
232,240
2,089
2,089
2,089
17,559
17,559
17,559
20,357
20,357
20,357
17,712
17,712
17,712
589
589
589
58,307
44,634
41,395
41,395
41,395
19,874
19,874
19,874
17,669
17,669
17,669
78,937
60,043
-636
277
277
277
218
218
218
36
36
36
152
152
152
20,421
25,647
59
59
59
1,340
1,340
1,340
3,874
3,874
3,874
1,628
1,628
1,628
176
176
176
7,077
4,708
4,036
4,036
4,036
668
668
668
1,173
1,173
1,173
5,877
7,430
-4,539
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
9 /17
9 /17
7 /16
7 /16
9 /17
9 /17
9 /16
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
9 /13
9 /13
7 /17
7 /17
9 /16
9 /13
9 /13
9 /17
9 /17
7 /18
7 /18
9 /17
7 /14
75
75
75
76
76
76
76
76
76
76
76
76
77
77
76
76
76
77
77
77
73
73
73
75
75
75
75
75
75
77
77
75
75
75
76
76
76
73
73
73
76
76
76
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
65
65
65
65
65
65
66
66
66
67
67
65
65
65
67
67
67
65
65
65
67
67
65
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
56.1
76.2
76.2
76.2
57.4
57.4
57.4
52.2
52.2
52.2
57.4
57.4
57.4
48.8
48.8
48.8
57.5
60.7
57.2
57.2
57.2
75.4
75.4
75.4
56.3
56.3
56.3
66.2
68.1
72.4
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
164
164
164
186
186
186
7
7
7
143
143
143
15,679
12,961
275
275
275
1,022
1,022
1,022
924
924
924
968
968
968
23
23
23
3,212
3,212
2,119
2,119
2,119
3,150
3,150
3,150
1,009
1,009
1,009
6,278
6,278
451
4,618
4,618
4,618
4,899
4,899
4,899
475
475
475
3,755
3,755
3,755
382,332
328,402
2,439
2,439
2,439
21,294
21,294
21,294
23,315
23,315
23,315
22,689
22,689
22,689
1,667
1,667
1,667
71,405
61,879
36,526
36,526
36,526
36,640
36,640
36,640
27,335
27,335
27,335
100,501
80,404
-191
Coil
Latent
Load
Btu/h
569
569
569
432
432
432
50
50
50
300
300
300
41,604
50,410
755
755
755
3,639
3,639
3,639
7,205
7,205
7,205
2,921
2,921
2,921
304
304
304
14,824
15,804
19,890
19,890
19,890
8,557
8,557
8,557
2,160
2,160
2,160
30,607
29,879
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 90 of 100
SPACE
System Zone Room
Zone - 001
Peak
Zone - 001
Block
spc_PE Team Lockey RH4_0
Peak
Zone - 002
Peak
Zone - 002
Block
spc_PE 113 RH7/RH8_0
Peak
Zone - 003
Peak
Zone - 003
Block
spc_PE 114 C_0
Peak
Zone - 004
Peak
Zone - 004
Block
spc_PE 109 NC_0
Peak
Zone - 005
Peak
Zone - 005
Block
spc_PE 2nd Flr Lobby_0
Peak
Zone - 007
Peak
Zone - 007
Block
Peak
spc_PE 214-218, 201-203 Offices C_0
Zone - 009
Peak
Zone - 009
Block
spc_PE 3 Press Box RH02 _0
Peak
Zone - 010
Peak
Zone - 010
Block
PE VAV Htg Only
Peak
PE VAV Htg Only
Block
spc_sp_55
Peak
Zone - 264
Peak
Zone - 264
Block
spc_sp_56
Peak
Zone - 265
Peak
Zone - 265
Block
spc_sp_57
Peak
Zone - 266
Peak
Zone - 266
Block
spc_sp_58
Peak
Zone - 267
Peak
Zone - 267
Block
spc_sp_59
Peak
Zone - 268
Peak
Zone - 268
Block
spc_sp_60
Peak
Zone - 269
Peak
Zone - 269
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
7,524
7,524
744
744
744
1,696
1,696
1,696
1,001
1,001
1,001
683
683
683
7,013
7,013
7,013
1,922
1,922
1,922
174
174
174
20,757
20,757
1,130
1,130
1,130
1,130
1,130
1,130
1,159
1,159
1,159
1,087
1,087
1,087
396
396
396
828
828
828
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /17
10 /16
10 /16
9 /16
9 /16
9 /10
9 /10
10 /15
10 /15
7 /10
7 /10
7/18
7 /18
10 /16
10 /16
7 /17
10 /13
10 /13
10 /15
10 /15
9 /12
9 /12
10 /16
10 /16
11 /15
11 /15
7 /18
7 /18
75
75
79
79
79
77
77
77
67
67
67
80
80
80
67
67
67
73
73
73
79
79
79
75
75
77
77
77
80
80
80
73
73
73
79
79
79
73
73
73
73
73
73
66
66
64
64
64
67
67
67
61
61
61
63
63
63
60
60
60
65
65
65
64
64
64
66
66
59
59
59
63
63
63
63
63
63
64
64
64
62
62
62
65
65
65
72.0
72.0
80.0
80.0
80.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
74.4
74.4
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
58.6
58.6
58.6
55.9
55.9
55.9
54.6
54.6
54.6
56.3
56.3
56.3
58.2
58.2
58.2
54.7
54.7
54.7
1,505
1,505
1,190
1,190
1,190
339
339
339
200
200
200
137
137
137
351
351
351
256
256
256
23
23
23
4,001
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
-636
-636
10,111
10,111
10,111
-143
-143
-143
-85
-85
-85
-58
-58
-58
-148
-148
-148
-108
-108
-108
-10
-10
-10
8,923
0
25,370
25,370
25,370
30,201
30,201
30,201
29,008
29,008
29,008
37,550
37,550
37,550
33,464
33,464
33,464
25,783
25,783
25,783
-4,539
-4,539
-971
-971
-971
2,691
2,691
2,691
1,039
1,039
1,039
306
306
306
-8,532
-8,532
-8,532
454
454
454
-45
-45
-45
-9,597
-3,178
2,062
2,062
2,062
2,910
2,910
2,910
3,573
3,573
3,573
3,013
3,013
3,013
1,051
1,051
1,051
2,864
2,864
2,864
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /14
9 /16
9 /16
9 /16
9 /16
9 /10
9 /10
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
9 /17
9 /17
7 /17
9 /14
9 /14
9 /16
9 /16
9 /14
9 /14
9 /16
9 /16
10 /15
10 /15
7 /18
7 /18
76
76
77
77
77
77
77
77
67
67
67
77
77
77
75
75
75
75
75
75
76
76
76
75
75
77
77
77
77
77
77
77
77
77
77
77
77
80
80
80
73
73
73
65
65
67
67
67
67
67
67
61
61
61
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
66
66
67
67
67
66
66
66
67
67
67
63
63
63
65
65
65
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
72.4
59.2
59.2
59.2
56.9
56.9
56.9
55.6
55.6
55.6
56.5
56.5
56.5
58.3
58.3
58.3
54.7
54.7
54.7
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
451
451
357
357
357
102
102
102
60
60
60
41
41
41
105
105
105
77
77
77
7
7
7
1,200
0
1,702
1,702
1,702
1,687
1,687
1,687
1,499
1,499
1,499
2,144
2,144
2,144
2,178
2,178
2,178
1,338
1,338
1,338
-191
-191
3,033
3,033
3,033
-43
-43
-43
-25
-25
-25
-17
-17
-17
-44
-44
-44
-32
-32
-32
-3
-3
-3
12,882
0
36,547
36,547
36,547
44,525
44,525
44,525
40,050
40,050
40,050
54,574
54,574
54,574
40,936
40,936
40,936
38,829
38,829
38,829
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6,959
6,959
6,959
7,908
7,908
7,908
7,147
7,147
7,147
7,605
7,605
7,605
1,195
1,195
1,195
5,336
5,336
5,336
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 91 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_61
Zone - 270
Zone - 270
spc_sp_62
Zone - 271
Zone - 271
spc_sp_63
Zone - 272
Zone - 272
spc_sp_64
Zone - 273
Zone - 273
spc_sp_65
Zone - 274
Zone - 274
spc_sp_66
Zone - 275
Zone - 275
spc_sp_67
Zone - 276
Zone - 276
spc_sp_68
Zone - 277
Zone - 277
spc_sp_69
Zone - 278
Zone - 278
spc_sp_70
Zone - 279
Zone - 279
spc_sp_38
Zone - 280
Zone - 280
spc_sp_39
Zone - 281
Zone - 281
spc_sp_40
Zone - 282
Zone - 282
spc_sp_41
Zone - 283
Zone - 283
spc_sp_42
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
378
9 /11
378
378
9 /11
485
6 /10
485
485
6 /10
678 10 /16
678
678 10 /16
822
7 /18
822
822
7 /18
628
9 /11
628
628
9 /11
2,082 9 /16
2,082
2,082 9 /16
2,169 7 /17
2,169
2,169 7 /17
2,777 7 /17
2,777
2,777 7 /17
3,084 7 /17
3,084
3,084 7 /17
211
6 /10
211
211
6 /10
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
1,408 9 /16
1,408
1,408 9 /16
1,392 9 /16
1,392
1,392
9 /16
972
9 /16
70
70
70
65
65
65
79
79
79
73
73
73
70
70
70
77
77
77
75
75
75
75
75
75
75
75
75
65
65
65
77
77
77
77
77
77
77
77
77
77
77
77
77
63
63
63
58
58
58
64
64
64
65
65
65
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.5
57.5
57.5
55.5
55.5
55.5
56.3
56.3
56.3
51.4
51.4
51.4
56.1
56.1
56.1
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.5
52.5
52.5
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
28,760
28,760
28,760
11,994
11,994
11,994
23,923
23,923
23,923
13,067
13,067
13,067
26,223
26,223
26,223
53,398
53,398
53,398
48,975
48,975
48,975
57,415
57,415
57,415
55,454
55,454
55,454
13,285
13,285
13,285
28,858
28,858
28,858
28,858
28,858
28,858
35,056
35,056
35,056
34,765
34,765
34,765
27,232
1,212
1,212
1,212
1,286
1,286
1,286
1,878
1,878
1,878
2,838
2,838
2,838
2,011
2,011
2,011
7,723
7,723
7,723
7,128
7,128
7,128
9,122
9,122
9,122
10,121
10,121
10,121
559
559
559
3,036
3,036
3,036
3,036
3,036
3,036
5,223
5,223
5,223
5,163
5,163
5,163
3,608
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
7 /16
7 /16
9 /16
9 /16
7 /17
7 /17
9 /12
9 /12
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /16
7 /16
6 /10
6 /10
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
70
70
70
76
76
76
77
77
77
75
75
75
73
73
73
77
77
77
75
75
75
75
75
75
76
76
76
65
65
65
77
77
77
77
77
77
77
77
77
77
77
77
77
63
63
63
66
66
66
67
67
67
66
66
66
63
63
63
67
67
67
66
66
66
66
66
66
66
66
66
58
58
58
67
67
67
67
67
67
67
67
67
67
67
67
67
57.5
57.5
57.5
58.6
58.6
58.6
56.4
56.4
56.4
51.9
51.9
51.9
56.2
56.2
56.2
53.6
53.6
53.6
53.6
53.6
53.6
53.2
53.2
53.2
52.7
52.7
52.7
57.8
57.8
57.8
54.9
54.9
54.9
54.9
54.9
54.9
53.5
53.5
53.5
53.5
53.5
53.5
54.0
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,775
1,775
1,775
652
652
652
1,371
1,371
1,371
570
570
570
1,481
1,481
1,481
2,604
2,604
2,604
2,386
2,386
2,386
2,736
2,736
2,736
2,545
2,545
2,545
837
837
837
1,512
1,512
1,512
1,512
1,512
1,512
1,697
1,697
1,697
1,685
1,685
1,685
1,355
32,826
32,826
32,826
16,489
16,489
16,489
33,562
33,562
33,562
23,710
23,710
23,710
32,978
32,978
32,978
80,411
80,411
80,411
79,136
79,136
79,136
95,193
95,193
95,193
95,526
95,526
95,526
14,677
14,677
14,677
41,068
41,068
41,068
41,068
41,068
41,068
53,076
53,076
53,076
52,584
52,584
52,584
39,863
Coil
Latent
Load
Btu/h
1,973
1,973
1,973
3,057
3,057
3,057
4,742
4,742
4,742
5,052
5,052
5,052
3,012
3,012
3,012
14,541
14,541
14,541
13,382
13,382
13,382
17,116
17,116
17,116
19,369
19,369
19,369
694
694
694
5,720
5,720
5,720
5,720
5,720
5,720
9,832
9,832
9,832
9,719
9,719
9,719
6,796
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 92 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 284
Zone - 284
spc_sp_43
Zone - 285
Zone - 285
spc_sp_44
Zone - 286
Zone - 286
spc_sp_45
Zone - 287
Zone - 287
spc_sp_46
Zone - 288
Zone - 288
spc_sp_47
Zone - 289
Zone - 289
spc_sp_48
Zone - 290
Zone - 290
spc_sp_49
Zone - 291
Zone - 291
spc_sp_50
Zone - 292
Zone - 292
spc_sp_51
Zone - 293
Zone - 293
spc_sp_52
Zone - 294
Zone - 294
spc_sp_53
Zone - 295
Zone - 295
spc_sp_54
Zone - 296
Zone - 296
spc_sp_22
Zone - 297
Zone - 297
spc_sp_23
Zone - 298
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
972
972
1,408
1,408
1,408
826
826
826
914
914
914
907
907
907
869
869
869
869
869
869
835
835
835
893
893
893
737
737
737
1,061
1,061
1,061
1,064
1,064
1,064
1,061
1,061
1,061
1,044
1,044
1,044
1,082
1,082
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /16
10 /15
10 /15
9 /16
9 /16
9 /16
9 /16
7 /18
7 /18
7 /18
7/18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
10 /13
10 /13
10 /13
10 /13
9 /12
9 /12
7 /18
7 /18
7 /18
77
77
80
80
80
77
77
77
77
77
77
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
73
77
77
77
77
77
77
73
73
73
73
73
73
73
73
67
67
63
63
63
67
67
67
67
67
67
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
59
59
59
59
59
59
63
63
63
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.0
54.0
56.0
56.0
56.0
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
53.9
53.9
53.9
54.1
54.1
54.1
54.2
54.2
54.2
54.0
54.0
54.0
55.0
55.0
55.0
58.7
58.7
58.7
58.7
58.7
58.7
54.7
54.7
54.7
53.1
53.1
53.1
53.4
53.4
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
27,232
27,232
38,302
38,302
38,302
27,994
27,994
27,994
26,885
26,885
26,885
25,235
25,235
25,235
22,064
22,064
22,064
22,983
22,983
22,983
22,536
22,536
22,536
23,576
23,576
23,576
24,944
24,944
24,944
24,323
24,323
24,323
24,374
24,374
24,374
27,301
27,301
27,301
22,248
22,248
22,248
24,586
24,586
3,608
3,608
3,626
3,626
3,626
3,067
3,067
3,067
3,393
3,393
3,393
3,140
3,140
3,140
3,008
3,008
3,008
3,009
3,009
3,009
2,891
2,891
2,891
3,092
3,092
3,092
2,553
2,553
2,553
1,935
1,935
1,935
1,941
1,941
1,941
3,272
3,272
3,272
3,609
3,609
3,609
3,741
3,741
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
9 /14
9 /14
9 /14
9 /14
9 /14
9 /14
7 /17
7 /17
7 /17
77
77
77
77
77
77
77
77
77
77
77
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
75
77
77
77
77
77
77
77
77
77
75
75
75
75
75
67
67
67
67
67
67
67
67
67
67
67
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
54.0
54.0
56.2
56.2
56.2
54.7
54.7
54.7
54.2
54.2
54.2
54.3
54.3
54.3
54.1
54.1
54.1
54.2
54.2
54.2
54.3
54.3
54.3
54.2
54.2
54.2
55.0
55.0
55.0
59.2
59.2
59.2
59.2
59.2
59.2
55.7
55.7
55.7
53.6
53.6
53.6
53.6
53.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,355
1,355
2,146
2,146
2,146
1,455
1,455
1,455
1,354
1,354
1,354
1,277
1,277
1,277
1,092
1,092
1,092
1,148
1,148
1,148
1,133
1,133
1,133
1,178
1,178
1,178
1,316
1,316
1,316
1,635
1,635
1,635
1,639
1,639
1,639
1,419
1,419
1,419
1,055
1,055
1,055
1,186
1,186
39,863
39,863
56,744
56,744
56,744
39,442
39,442
39,442
38,892
38,892
38,892
38,103
38,103
38,103
33,592
33,592
33,592
34,897
34,897
34,897
34,003
34,003
34,003
35,816
35,816
35,816
36,470
36,470
36,470
34,741
34,741
34,741
34,831
34,831
34,831
37,314
37,314
37,314
35,254
35,254
35,254
38,640
38,640
Coil
Latent
Load
Btu/h
6,796
6,796
9,854
9,854
9,854
5,777
5,777
5,777
6,391
6,391
6,391
5,604
5,604
5,604
5,367
5,367
5,367
5,370
5,370
5,370
5,157
5,157
5,157
5,519
5,519
5,519
4,557
4,557
4,557
6,531
6,531
6,531
6,553
6,553
6,553
6,544
6,544
6,544
6,433
6,433
6,433
6,671
6,671
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 93 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 298
spc_sp_24
Zone - 299
Zone - 299
spc_sp_25
Zone - 300
Zone - 300
spc_sp_26
Zone - 301
Zone - 301
spc_sp_27
Zone - 302
Zone - 302
spc_sp_28
Zone - 303
Zone - 303
spc_sp_29
Zone - 304
Zone - 304
spc_sp_30
Zone - 305
Zone - 305
spc_sp_31
Zone - 306
Zone - 306
spc_sp_32
Zone - 307
Zone - 307
spc_sp_33
Zone - 308
Zone - 308
spc_sp_34
Zone - 309
Zone - 309
spc_sp_35
Zone - 310
Zone - 310
spc_sp_36
Zone - 311
Zone - 311
spc_sp_37
Zone - 312
Zone - 312
Project Name:
Dataset Name:
SBCC TRACE.TRC
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
1,082
7 /18
1,074
7 /18
1,074
1,074
7 /18
955
7 /18
955
955
7 /18
995
9 /16
995
995
9 /16
894
7 /17
894
894
7 /17
1,063 10 /15
1,063
1,063 10 /15
684
6/10
684
684
6 /10
2,070 9 /16
2,070
2,070 9 /16
1,251 9 /16
1,251
1,251 9 /16
1,251 7 /17
1,251
1,251 7 /17
1,525 9 /16
1,525
1,525 9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
818
9 /16
818
818
9 /16
73
73
73
73
73
73
73
77
77
77
75
75
75
80
80
80
65
65
65
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
65
65
65
65
65
65
65
67
67
67
66
66
66
63
63
63
58
58
58
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
53.4
53.1
53.1
53.1
53.6
53.6
53.6
55.1
55.1
55.1
55.0
55.0
55.0
56.6
56.6
56.6
55.8
55.8
55.8
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
24,586
22,945
22,945
22,945
22,834
22,834
22,834
37,026
37,026
37,026
29,118
29,118
29,118
36,090
36,090
36,090
18,202
18,202
18,202
52,942
52,942
52,942
35,189
35,189
35,189
31,103
31,103
31,103
60,677
60,677
60,677
29,082
29,082
29,082
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
28,858
3,741
3,711
3,711
3,711
3,304
3,304
3,304
3,697
3,697
3,697
2,943
2,943
2,943
2,737
2,737
2,737
1,813
1,813
1,813
7,679
7,679
7,679
4,645
4,645
4,645
4,115
4,115
4,115
5,660
5,660
5,660
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
3,036
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
7 /16
7 /16
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
9 /16
75
75
75
75
75
75
75
77
77
77
75
75
75
77
77
77
76
76
76
77
77
77
77
77
77
75
75
75
77
77
77
77
77
77
77
77
77
77
77
77
77
77
77
66
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
53.6
53.6
53.6
53.6
53.9
53.9
53.9
55.1
55.1
55.1
55.0
55.0
55.0
56.7
56.7
56.7
60.6
60.6
60.6
53.6
53.6
53.6
54.0
54.0
54.0
54.0
54.0
54.0
55.3
55.3
55.3
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
54.9
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,186
1,089
1,089
1,089
1,115
1,115
1,115
1,960
1,960
1,960
1,538
1,538
1,538
2,104
2,104
2,104
1,005
1,005
1,005
2,580
2,580
2,580
1,753
1,753
1,753
1,549
1,549
1,549
3,258
3,258
3,258
1,526
1,526
1,526
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
1,512
38,640
36,369
36,369
36,369
35,270
35,270
35,270
51,628
51,628
51,628
42,996
42,996
42,996
51,414
51,414
51,414
22,226
22,226
22,226
79,873
79,873
79,873
52,725
52,725
52,725
48,027
48,027
48,027
82,120
82,120
82,120
41,372
41,372
41,372
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
41,068
Coil
Latent
Load
Btu/h
6,671
6,615
6,615
6,615
5,894
5,894
5,894
6,966
6,966
6,966
5,530
5,530
5,530
7,439
7,439
7,439
4,311
4,311
4,311
14,458
14,458
14,458
8,749
8,749
8,749
7,730
7,730
7,730
10,664
10,664
10,664
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
5,720
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 94 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_sp_7
Zone - 313
Zone - 313
spc_sp_8
Zone - 314
Zone - 314
spc_sp_9
Zone - 315
Zone - 315
spc_sp_10
Zone - 316
Zone - 316
spc_sp_11
Zone - 317
Zone - 317
spc_sp_12
Zone - 318
Zone - 318
spc_sp_13
Zone - 319
Zone - 319
spc_sp_14
Zone - 320
Zone - 320
spc_sp_15
Zone - 321
Zone - 321
spc_sp_16
Zone - 322
Zone - 322
spc_sp_17
Zone - 323
Zone - 323
spc_sp_18
Zone - 324
Zone - 324
spc_sp_19
Zone - 325
Zone - 325
spc_sp_20
Zone - 326
Zone - 326
spc_sp_21
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
290
290
290
442
442
442
2,070
2,070
2,070
1,103
1,103
1,103
915
915
915
3,084
3,084
3,084
437
437
437
344
344
344
231
231
231
382
382
382
358
358
358
1,082
1,082
1,082
960
960
960
1,040
1,040
1,040
1,040
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
6 /18
6 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
6 /18
6 /18
7 /18
7 /18
9 /12
9 /12
6 /10
6 /10
6 /9
6 /9
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
7 /18
70
70
70
70
70
70
75
75
75
76
76
76
76
76
76
75
75
75
70
70
70
73
73
73
73
73
73
65
65
65
62
62
62
73
73
73
73
73
73
73
73
73
73
63
63
63
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
63
63
63
65
65
65
63
63
63
58
58
58
58
58
58
65
65
65
65
65
65
65
65
65
65
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
57.0
57.0
57.0
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
56.2
56.2
56.2
56.0
56.0
56.0
53.0
53.0
53.0
53.2
53.2
53.2
54.2
54.2
54.2
53.1
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
17,557
17,557
17,557
19,208
19,208
19,208
47,533
47,533
47,533
12,788
12,788
12,788
10,607
10,607
10,607
60,225
60,225
60,225
28,451
28,451
28,451
19,387
19,387
19,387
8,323
8,323
8,323
11,887
11,887
11,887
10,175
10,175
10,175
22,813
22,813
22,813
20,987
20,987
20,987
28,726
28,726
28,726
22,182
929
929
929
1,375
1,375
1,375
6,804
6,804
6,804
3,865
3,865
3,865
3,206
3,206
3,206
10,127
10,127
10,127
1,358
1,358
1,358
1,192
1,192
1,192
713
713
713
1,013
1,013
1,013
951
951
951
3,739
3,739
3,739
3,318
3,318
3,318
3,598
3,598
3,598
3,594
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /12
9 /12
7 /18
7 /18
7 /17
7 /17
7 /16
7 /16
7 /16
7 /16
7 /17
7 /17
7 /18
7 /18
7 /18
7 /18
9 /12
9 /12
7 /15
7 /15
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
7 /17
73
73
73
73
73
73
75
75
75
76
76
76
76
76
76
75
75
75
73
73
73
73
73
73
73
73
73
77
77
77
76
76
76
75
75
75
75
75
75
75
75
75
75
63
63
63
65
65
65
66
66
66
66
66
66
66
66
66
66
66
66
65
65
65
65
65
65
63
63
63
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
57.6
57.6
57.6
56.3
56.3
56.3
53.7
53.7
53.7
48.7
48.7
48.7
48.7
48.7
48.7
52.9
52.9
52.9
57.2
57.2
57.2
56.5
56.5
56.5
55.9
55.9
55.9
60.1
60.1
60.1
57.9
57.9
57.9
53.5
53.5
53.5
53.7
53.7
53.7
54.4
54.4
54.4
53.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,050
1,050
1,050
1,094
1,094
1,094
2,325
2,325
2,325
491
491
491
407
407
407
2,828
2,828
2,828
1,723
1,723
1,723
1,121
1,121
1,121
463
463
463
676
676
676
569
569
569
1,079
1,079
1,079
1,002
1,002
1,002
1,451
1,451
1,451
1,053
20,529
20,529
20,529
26,244
26,244
26,244
76,434
76,434
76,434
26,279
26,279
26,279
21,797
21,797
21,797
101,628
101,628
101,628
36,070
36,070
36,070
25,678
25,678
25,678
11,070
11,070
11,070
14,327
14,327
14,327
14,201
14,201
14,201
36,302
36,302
36,302
32,911
32,911
32,911
43,793
43,793
43,793
35,131
Coil
Latent
Load
Btu/h
1,393
1,393
1,393
2,856
2,856
2,856
12,774
12,774
12,774
6,912
6,912
6,912
5,733
5,733
5,733
18,995
18,995
18,995
2,820
2,820
2,820
2,221
2,221
2,221
1,110
1,110
1,110
2,357
2,357
2,357
2,261
2,261
2,261
6,665
6,665
6,665
5,915
5,915
5,915
6,420
6,420
6,420
6,406
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 95 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 327
Zone - 327
spc_sp_1
Zone - 328
Zone - 328
spc_sp_2
Zone - 329
Zone - 329
spc_sp_3
Zone - 330
Zone - 330
spc_sp_4
Zone - 331
Zone - 331
spc_sp_5
Zone - 332
Zone - 332
spc_sp_6
Zone - 333
Zone - 333
Child Cntr 2
Zone - 359
Zone - 359
Child Cntr 3
Zone - 360
Zone - 360
Child Cntr 1
Zone - 361
Zone - 361
Portopia HP
Portopia HP
spc_SS 141/142 Office_0
Zone - 012
Zone - 012
spc_SS 144 Office C_0
Zone - 013
Zone - 013
spc_SS 160B-D_0
Zone - 014
Zone - 014
spc_PS 160A Storage_0
Zone - 015
Zone - 015
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
1,040
1,040
1,272
1,272
1,272
1,074
1,074
1,074
999
999
999
1,613
1,613
1,613
664
664
664
1,956
1,956
1,956
211
211
211
211
211
211
211
211
211
75,038
75,038
313
313
313
168
168
168
0
0
0
102
102
102
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
7 /18
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
10 /15
10 /15
10 /16
10 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
6 /9
10 /15
10 /15
9 /11
9 /11
73
73
77
77
77
73
73
73
73
73
73
80
80
80
79
79
79
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
62
62
80
80
80
70
70
70
65
65
67
67
67
65
65
65
65
65
65
63
63
63
64
64
64
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
58
58
63
63
63
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Supply
Dry
Bulb
°F
53.1
53.1
48.6
48.6
48.6
53.1
53.1
53.1
54.3
54.3
54.3
55.5
55.5
55.5
57.1
57.1
57.1
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
54.9
54.9
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
32
32
0
0
0
27
27
27
22,182
22,182
15,648
15,648
15,648
22,945
22,945
22,945
28,019
28,019
28,019
37,433
37,433
37,433
31,843
31,843
31,843
22,688
22,688
22,688
13,285
13,285
13,285
13,285
13,285
13,285
12,931
12,931
12,931
2,026,697
1,809,600
0
0
0
0
0
0
0
0
0
0
0
0
3,594
3,594
4,707
4,707
4,707
3,711
3,711
3,711
3,457
3,457
3,457
4,151
4,151
4,151
1,840
1,840
1,840
6,857
6,857
6,857
559
559
559
559
559
559
370
370
370
246,137
246,507
181
181
181
97
97
97
0
0
0
-2
-2
-2
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /17
7 /16
7 /16
7 /17
7 /17
7 /17
7 /17
9 /16
9 /16
9 /16
9 /16
7 /16
7 /16
6 /10
6 /10
6 /10
6 /10
6 /10
6 /10
7 /17
6 /9
6 /9
6 /9
6 /9
9 /16
9 /16
9 /11
9 /11
75
75
76
76
76
75
75
75
75
75
75
77
77
77
77
77
77
76
76
76
65
65
65
65
65
65
65
65
65
75
75
62
62
62
62
62
62
77
77
77
70
70
70
66
66
66
66
66
66
66
66
66
66
66
67
67
67
67
67
67
66
66
66
58
58
58
58
58
58
58
58
58
66
66
58
58
58
58
58
58
67
67
67
63
63
63
53.6
53.6
48.8
48.8
48.8
53.6
53.6
53.6
54.5
54.5
54.5
56.4
56.4
56.4
57.3
57.3
57.3
48.7
48.7
48.7
57.8
57.8
57.8
57.8
57.8
57.8
58.3
58.3
58.3
55.1
56.7
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
Coil
Airflow
cfm
1,053
1,053
600
600
600
1,089
1,089
1,089
1,420
1,420
1,420
2,033
2,033
2,033
1,915
1,915
1,915
871
871
871
837
837
837
837
837
837
849
849
849
106,096
106,096
81
81
81
32
32
32
0
0
0
27
27
27
Coil
Sensible
Load
Btu/h
35,131
35,131
31,358
31,358
31,358
36,369
36,369
36,369
42,495
42,495
42,495
56,782
56,782
56,782
43,282
43,282
43,282
46,620
46,620
46,620
14,677
14,677
14,677
14,677
14,677
14,677
14,524
14,524
14,524
3,006,774
2,862,181
0
0
0
0
0
0
0
0
0
0
0
0
Coil
Latent
Load
Btu/h
6,406
6,406
7,970
7,970
7,970
6,615
6,615
6,615
6,169
6,169
6,169
11,281
11,281
11,281
4,645
4,645
4,645
12,262
12,262
12,262
694
694
694
694
694
694
460
460
460
480,065
462,701
0
0
0
0
0
0
0
0
0
0
0
0
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 96 of 100
SPACE
Floor
Area
ft²
System Zone Room
spc_SS 160 Class C_0
Zone - 016
Zone - 016
spc_SS 162 Class_0
Zone - 017
Zone - 017
spc_PS 112 Office C_0
Zone - 018
Zone - 018
spc_PS 111-115 Office C_0
Zone - 019
Zone - 019
spc_PS Lecture 117 C_0
Zone - 020
Zone - 020
spc_PS Lecture FC-4C_0
Zone - 021
Zone - 021
spc_PS 120-128 Class_0
Zone - 022
Zone - 022
spc_PS Class 121/122_0
Zone - 023
Zone - 023
spc_PS 130 Auditorium C_0
Zone - 024
Zone - 024
PS Fan Coil Htg Only
PS Fan Coil Htg Only
spc_SS 171-173, 178 Office C_0
Zone - 037
Zone - 037
spc_SS 135 Office_0
Zone - 038
Zone - 038
spc_SS Corridor 120 C_0
Zone - 039
Zone - 039
spc_SS 180 Worm Rm VAV-20_0
Zone - 040
Zone - 040
spc_SS 110C Wrk Rm C_0
Zone - 041
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
565
565
565
967
967
967
215
215
215
602
602
602
1,126
1,126
1,126
1,036
1,036
1,036
886
886
886
695
695
695
1,413
1,413
1,413
8,090
8,090
561
561
561
92
92
92
1,787
1,787
1,787
326
326
326
766
766
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
10 /16
10 /16
9 /17
9 /17
7 /18
7 /18
6 /9
6 /9
7 /16
7 /16
10 /16
10 /16
10 /16
7 /16
7 /16
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
6 /9
70
70
70
70
70
70
79
79
79
79
79
79
76
76
76
73
73
73
62
62
62
76
76
76
79
79
79
79
79
76
76
76
76
76
76
76
76
76
79
79
79
62
62
63
63
63
63
63
63
64
64
64
64
64
64
67
67
67
65
65
65
58
58
58
66
66
66
64
64
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
58
58
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
274
274
274
45
45
45
378
378
378
616
616
616
1,984
1,984
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,317
5,317
5,317
875
875
875
7,342
7,342
7,342
11,961
11,961
11,961
38,530
38,530
836
836
836
1,430
1,430
1,430
157
157
157
435
435
435
1,356
1,356
1,356
1,374
1,374
1,374
1,392
1,392
1,392
992
992
992
2,191
2,191
2,191
10,439
7,971
1,465
1,465
1,465
241
241
241
2,794
2,794
2,794
902
902
902
2,030
2,030
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /11
9 /11
10 /16
10 /16
9 /17
9 /17
9 /17
9 /17
7 /18
7 /18
7 /9
7 /9
7 /16
7 /16
9 /16
9 /16
9 /16
9 /17
9 /17
9 /17
9 /17
9 /16
9 /16
9 /16
9 /16
7 /10
70
70
70
70
70
70
79
79
79
76
76
76
76
76
76
73
73
73
64
64
64
76
76
76
77
77
77
77
77
76
76
76
76
76
76
77
77
77
77
77
77
67
67
63
63
63
63
63
63
64
64
64
67
67
67
67
67
67
65
65
65
59
59
59
66
66
66
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
67
60
60
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
113
113
113
193
193
193
71
71
71
240
240
240
225
225
225
207
207
207
177
177
177
139
139
139
283
283
283
1,790
1,790
268
268
268
44
44
44
364
364
364
593
593
593
1,874
1,874
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5,089
5,089
5,089
838
838
838
5,425
5,425
5,425
13,863
13,863
13,863
40,338
40,338
Coil
Latent
Load
Btu/h
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2,917
2,917
2,917
480
480
480
4,022
4,022
4,022
2,276
2,276
2,276
2,929
2,929
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 97 of 100
SPACE
System Zone Room
Zone - 041
Block
spc_SS 110 Wrk Rm/Office C_0 Peak
Zone - 042
Peak
Zone - 042
Block
Peak
spc_SS 100 100H 111H Main Lobby
C_0
Zone - 043
Peak
Zone - 043
Block
spc_SS 150 Wrk Rm C_0
Peak
Zone - 044
Peak
Zone - 044
Block
spc_SS 177-179 Office_0
Peak
Zone - 045
Peak
Zone - 045
Block
spc_SS Wrk Rm1 V-19_0
Peak
Zone - 046
Peak
Zone - 046
Block
spc_SS 120-124 C_0
Peak
Zone - 047
Peak
Zone - 047
Block
spc_SS 135-139 Office C_0
Peak
Zone - 048
Peak
Zone - 048
Block
spc_SS 140 Wrk Rm C_0
Peak
Zone - 049
Peak
Zone - 049
Block
spc_SS 125-129_0
Peak
Zone - 050
Peak
Zone - 050
Block
spc_SS 230B Office C_0
Peak
Zone - 051
Peak
Zone - 051
Block
spc_SS 214 Office C_0
Peak
Zone - 052
Peak
Zone - 052
Block
spc_SS 282 Wrk Rm C_0
Peak
Zone - 053
Peak
Zone - 053
Block
spc_SS 280D Office_0
Peak
Zone - 054
Peak
Zone - 054
Block
spc_SS 280A-C C_0
Peak
Zone - 055
Peak
Zone - 055
Block
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
766
1,420
1,420
1,420
37
37
37
301
301
301
635
635
635
207
207
207
703
703
703
586
586
586
848
848
848
642
642
642
285
285
285
130
130
130
136
136
136
154
154
154
459
459
459
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
6 /9
9 /17
9 /17
7 /18
7 /18
7 /15
7 /15
7 /16
7 /16
7 /15
7 /15
6/9
6 /9
7 /16
7 /16
9 /16
9 /16
6 /18
6 /18
6 /18
6 /18
10 /16
10 /16
10 /16
10 /16
7 /17
7 /17
9 /11
9 /11
62
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
62
62
62
76
76
76
77
77
77
70
70
70
70
70
70
79
79
79
79
79
79
75
75
75
70
70
70
58
67
67
67
65
65
65
66
66
66
66
66
66
66
66
66
58
58
58
66
66
66
67
67
67
63
63
63
63
63
63
64
64
64
64
64
64
66
66
66
63
63
63
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,984
844
844
844
348
348
348
167
167
167
310
310
310
115
115
115
1,253
1,253
1,253
286
286
286
545
545
545
1,766
1,766
1,766
526
526
526
623
623
623
1,441
1,441
1,441
75
75
75
1,255
1,255
1,255
38,530
16,389
16,389
16,389
6,755
6,755
6,755
3,248
3,248
3,248
6,019
6,019
6,019
2,238
2,238
2,238
24,336
24,336
24,336
5,555
5,555
5,555
10,576
10,576
10,576
34,294
34,294
34,294
10,214
10,214
10,214
12,096
12,096
12,096
27,981
27,981
27,981
1,450
1,450
1,450
24,365
24,365
24,365
2,030
4,101
4,101
4,101
63
63
63
1,044
1,044
1,044
1,658
1,658
1,658
719
719
719
1,862
1,862
1,862
1,530
1,530
1,530
3,146
3,146
3,146
1,992
1,992
1,992
572
572
572
244
244
244
378
378
378
408
408
408
1,469
1,469
1,469
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /10
9 /17
9 /17
7 /18
7 /18
9 /16
9 /16
9 /17
9 /17
9 /16
9 /16
7 /10
7 /10
9 /17
9 /17
9 /16
9 /16
7 /18
7 /18
7 /18
7 /18
9 /16
9 /16
9 /16
9 /16
7 /17
7 /17
9 /11
9 /11
67
76
76
76
73
73
73
77
77
77
76
76
76
77
77
77
67
67
67
76
76
76
77
77
77
73
73
73
73
73
73
77
77
77
77
77
77
75
75
75
70
70
70
60
67
67
67
65
65
65
67
67
67
67
67
67
67
67
67
60
60
60
67
67
67
67
67
67
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
63
63
63
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
1,874
844
844
844
348
348
348
165
165
165
304
304
304
114
114
114
1,181
1,181
1,181
280
280
280
545
545
545
1,745
1,745
1,745
522
522
522
610
610
610
1,360
1,360
1,360
75
75
75
1,255
1,255
1,255
40,338
16,959
16,959
16,959
8,572
8,572
8,572
3,134
3,134
3,134
5,761
5,761
5,761
2,159
2,159
2,159
25,288
25,288
25,288
5,317
5,317
5,317
10,803
10,803
10,803
37,007
37,007
37,007
11,167
11,167
11,167
14,956
14,956
14,956
32,179
32,179
32,179
3,723
3,723
3,723
28,088
28,088
28,088
Coil
Latent
Load
Btu/h
2,929
7,387
7,387
7,387
90
90
90
2,099
2,099
2,099
3,302
3,302
3,302
1,446
1,446
1,446
2,687
2,687
2,687
3,047
3,047
3,047
5,923
5,923
5,923
4,132
4,132
4,132
1,239
1,239
1,239
651
651
651
953
953
953
703
703
703
2,386
2,386
2,386
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 98 of 100
SPACE
System Zone Room
spc_SS 272 Wrk Rm C_0
Peak
Zone - 056
Peak
Zone - 056
Block
spc_SS 270C/D Office_0
Peak
Zone - 057
Peak
Zone - 057
Block
spc_SS 111H Hall_0
Peak
Zone - 058
Peak
Zone - 058
Block
spc_SS 110G/H Offices C_0
Peak
Zone - 059
Peak
Zone - 059
Block
spc_SS 111A Office C_0
Peak
Zone - 060
Peak
Zone - 060
Block
spc_SS 242 Wrk Rm C_0
Peak
Zone - 061
Peak
Zone - 061
Block
spc_SS 240L Office C_0
Peak
Zone - 062
Peak
Zone - 062
Block
spc_SS 240H Office_0
Peak
Zone - 063
Peak
Zone - 063
Block
spc_SS 240F/J Office_0
Peak
Zone - 064
Peak
Zone - 064
Block
spc_SS 240-260A Wrk Rm C_0 Peak
Zone - 065
Peak
Zone - 065
Block
spc_SS 202/250B Office_0
Peak
Zone - 066
Peak
Zone - 066
Block
spc_SS 250 Wrk Rm C_0
Peak
Zone - 067
Peak
Zone - 067
Block
spc_SS 251 Wrk Rm C_0
Peak
Zone - 068
Peak
Zone - 068
Block
Peak
spc_SS 230H, 200-201, 251H, 272H_0
Zone - 069
Peak
Zone - 069
Block
spc_SS 210/211 Wrk Rm C_0
Peak
Project Name:
Dataset Name:
SBCC TRACE.TRC
Floor
Area
ft²
778
778
778
287
287
287
397
397
397
269
269
269
216
216
216
642
642
642
149
149
149
181
181
181
274
274
274
865
865
865
214
214
214
0
0
0
388
388
388
4,383
4,383
4,383
308
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
9 /11
9 /11
9 /12
9 /12
7 /18
7 /18
7 /16
7 /16
7 /16
7 /16
10 /16
10 /16
7 /17
7 /17
7 /16
7 /16
7 /17
7 /17
10 /16
10 /16
7 /16
7 /16
6 /9
6 /9
9 /12
9 /12
7 /16
7 /16
7 /15
70
70
70
73
73
73
73
73
73
76
76
76
76
76
76
79
79
79
75
75
75
76
76
76
75
75
75
79
79
79
76
76
76
62
62
62
73
73
73
76
76
76
77
63
63
63
63
63
63
65
65
65
66
66
66
66
66
66
64
64
64
66
66
66
66
66
66
66
66
66
64
64
64
66
66
66
58
58
58
63
63
63
66
66
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
1,090
1,090
1,090
379
379
379
175
175
175
131
131
131
105
105
105
406
406
406
73
73
73
89
89
89
133
133
133
1,257
1,257
1,257
104
104
104
16
16
16
387
387
387
2,716
2,716
2,716
171
21,179
21,179
21,179
7,364
7,364
7,364
3,399
3,399
3,399
2,552
2,552
2,552
2,048
2,048
2,048
7,890
7,890
7,890
1,410
1,410
1,410
1,719
1,719
1,719
2,589
2,589
2,589
24,416
24,416
24,416
2,028
2,028
2,028
304
304
304
7,518
7,518
7,518
52,749
52,749
52,749
3,325
2,489
2,489
2,489
627
627
627
612
612
612
703
703
703
564
564
564
1,777
1,777
1,777
397
397
397
474
474
474
728
728
728
2,394
2,394
2,394
559
559
559
0
0
0
1,195
1,195
1,195
15,399
15,399
15,399
1,069
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
9 /13
9 /13
9 /13
9 /13
7 /18
7 /18
9 /17
9 /17
9 /17
9 /17
7 /16
7 /16
7 /17
7 /17
9 /17
9 /17
7 /17
7 /17
9 /16
9 /16
9 /17
9 /17
7 /10
7 /10
9 /12
9 /12
7 /16
7 /16
7 /16
75
75
75
75
75
75
73
73
73
76
76
76
76
76
76
76
76
76
75
75
75
76
76
76
75
75
75
77
77
77
76
76
76
67
67
67
73
73
73
76
76
76
76
65
65
65
65
65
65
65
65
65
67
67
67
67
67
67
66
66
66
66
66
66
67
67
67
66
66
66
67
67
67
67
67
67
60
60
60
63
63
63
66
66
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
918
918
918
357
357
357
175
175
175
129
129
129
103
103
103
394
394
394
73
73
73
87
87
87
133
133
133
1,221
1,221
1,221
102
102
102
15
15
15
387
387
387
2,716
2,716
2,716
171
25,380
25,380
25,380
10,543
10,543
10,543
3,469
3,469
3,469
2,443
2,443
2,443
1,960
1,960
1,960
17,212
17,212
17,212
3,620
3,620
3,620
1,646
1,646
1,646
6,646
6,646
6,646
38,964
38,964
38,964
1,941
1,941
1,941
312
312
312
8,858
8,858
8,858
113,463
113,463
113,463
7,815
Coil
Latent
Load
Btu/h
4,471
4,471
4,471
973
973
973
790
790
790
1,400
1,400
1,400
1,123
1,123
1,123
4,042
4,042
4,042
684
684
684
943
943
943
1,256
1,256
1,256
6,040
6,040
6,040
1,112
1,112
1,112
0
0
0
1,856
1,856
1,856
27,598
27,598
27,598
1,937
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 99 of 100
SPACE
Floor
Area
ft²
System Zone Room
Zone - 070
Zone - 070
spc_SS 230F Office C_0
Zone - 071
Zone - 071
spc_SS Wrk Rm 230 C_0
Zone - 072
Zone - 072
spc_SS 230C-E Office_0
Zone - 073
Zone - 073
spc_SS 240B Wrk Rm C_0
Zone - 074
Zone - 074
spc_SS 181 Comp Rm C_0
Zone - 075
Zone - 075
spc_SS 182 Comp Rm C_0
Zone - 076
Zone - 076
Stdnt Srv VAV
Stdnt Srv VAV
Project Name:
Dataset Name:
SBCC TRACE.TRC
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Peak
Block
Peak
Block
OA
Room
Peak Condition
Dry
Time DB WB Bulb
°F
°F
Mo/Hr °F
308
308
7 /15
180
6 /18
180
180
6 /18
987
7 /16
987
987
7 /16
630
6 /18
630
630
6 /18
240 10 /16
240
240 10 /16
854
7 /18
854
854
7/18
863
9 /11
863
863
9 /11
23,178
23,178 7 /17
77
77
70
70
70
76
76
76
70
70
70
79
79
79
73
73
73
70
70
70
75
75
66
66
63
63
63
66
66
66
63
63
63
64
64
64
65
65
65
63
63
63
66
66
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
72.0
COIL
Supply
Dry
Bulb
°F
Space
Air
Flow
cfm
Space
Sensible
Load
Btu/h
Space
Latent
Load
Btu/h
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
171
171
330
330
330
550
550
550
1,887
1,887
1,887
607
607
607
2,223
2,223
2,223
2,317
2,317
2,317
27,996
21,892
3,325
3,325
6,408
6,408
6,408
10,680
10,680
10,680
36,641
36,641
36,641
11,782
11,782
11,782
43,184
43,184
43,184
45,011
45,011
45,011
543,738
425,196
1,069
1,069
360
360
360
3,468
3,468
3,468
1,262
1,262
1,262
663
663
663
2,471
2,471
2,471
2,243
2,243
2,243
66,071
67,555
OA
Peak Condition Supply
Time DB WB Dry Bulb
°F
°F
Mo/Hr °F
7 /16
7 /18
7 /18
7 /16
7 /16
7 /18
7 /18
9 /16
9 /16
7 /18
7 /18
9 /11
9 /11
7 /17
76
76
73
73
73
76
76
76
73
73
73
77
77
77
73
73
73
70
70
70
75
75
66
66
65
65
65
66
66
66
65
65
65
67
67
67
65
65
65
63
63
63
66
66
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
54.6
Coil
Airflow
cfm
Coil
Sensible
Load
Btu/h
Coil
Latent
Load
Btu/h
171
171
326
326
326
550
550
550
1,854
1,854
1,854
595
595
595
2,223
2,223
2,223
2,317
2,317
2,317
27,337
21,892
7,815
7,815
9,430
9,430
9,430
25,113
25,113
25,113
48,827
48,827
48,827
15,938
15,938
15,938
45,640
45,640
45,640
49,534
49,534
49,534
713,169
592,652
1,937
1,937
781
781
781
6,215
6,215
6,215
2,736
2,736
2,736
1,674
1,674
1,674
4,381
4,381
4,381
3,536
3,536
3,536
122,218
121,687
TRACE® 700 v6.2.8 calculated at 03:30 PM on 02/25/2013
Peak Clg Loads Main System Report Page 100 of 100
APPENDIX
APPENDIX "E" - SCE Fact Sheets
TECHNICAL AUDIT REPORT - Santa Barbara City College - 09141.021
© 2013 SC ENGINEERS, INC.
"E"
DEMAND RESPONSE
Technical Assistance
with Technology Incentives
Technical Assistance provides on-site facility
evaluations ranging from simple site assessments
to comprehensive engineering studies to SDG&E®
business customers at no cost. These assessments
are designed to determine load reduction potential.
• Technical incentives help off-set
Technology Incentives help off-set the installation
and equipment costs of demand response
measures. Technology incentives follow the
completion of the Technical Assistance assessment
and the identification of verifiable load reduction.
Incentive amounts are up to $125/kW.
Businesses with annual maximum
demands equal to or greater than
20 kilowatts are eligible.
Who should participate?
TECHNICAL ASSISTANCE:
Business customers who want to
identify how to reduce their energy
demand during critical peak periods,
known as Demand Response events.
The evaluation ranges from simple site
assessments to a complete engineering
study with no cost to the customer.
The depth of the assessment will be
determined by the facility’s potential
to reduce electric load.
TECHNOLOGY INCENTIVES:
Customers who want to implement
demand reduction measures to reduce
their energy use during critical peak
periods. Qualified measures are those
that aid in the facility’s ability to
reduce load when called upon by the
utility. Additionally, these measures
allow customers to participate in
voluntary Demand Response programs
for additional financial incentives.
A higher incentive of $300/kW is
available to customers who can fully
automate their demand response
strategy utilizing their Energy
Management System.
Customer benefits
• Technical assessments can assist
customers in identifying effective
energy management strategies
that can result in cost savings
and incentives.
installation and equipment costs,
which can help justify energy
improvement projects and potentially
shorten pay-back periods.
Who is eligible
to participate?
How does the
program work?
Customers interested in participating
should call 1-800-644-6133. After
a review of the customer’s demand
response potential, an on-site assessment
will be scheduled. Customers will receive
a report with demand reduction potential
and load reduction strategies such
as enhanced EMS equipment, or
automation measures and other
demand response measures.
Customers can either utilize the
engineering or consulting firm of their
choice or opt to have SDG&E assign
a firm to complete the audit. If you
prefer to select your own engineering
firm to perform the assessment, the
cost is reimbursable up to $125/kW
load reduction, not to exceed the cost
of the assessment, provided the results
are approved by SDG&E.
After the Technical Assistance audit
has been approved, customers may
then choose to apply for Technology
Incentives. These incentives can pay
for or help offset the cost of putting
controls on an Energy Management
System to automate the demand
response strategy. This automation
will aid in the facility’s ability to reduce
load when called upon by the utility.
Customers who wish to receive
technology incentives must demonstrate
their actual ability to reduce demand
and enroll in an SDG&E Demand
Response program in order to receive
100% of the incentive.
Technical Assistance with Technology
Incentives program gives business
customers the necessary information and
means to participate in various voluntary
Demand Response programs offered
by SDG&E. The Demand Response
programs offer incentives for load
reduction during critical peak periods.
Managing your energy use
SDG&E has programs and services to
help your business get more out of the
energy that you use. Information on
everything from seminars to online energy
analysis tools, rebates and other financial
incentives can be found 24 hours a day,
seven days a week on our Energy Savings
Center website at www.sdge.com/esc.
For more information
Technical Assistance with Technology
Incentives is part of SDG&E’s Demand
Response programs — a component of
SDG&E’s long-term resource plan, and
one of the ways SDG&E is developing
energy solutions for the region. For
more details on Technical Assistance
with Technology Incentives, please
contact your SDG&E Account
Executive, call 1-800-644-6133,
or email drp@semprautilites.com.
This program is available throughout California and is offered
by the state’s investor-owned utilities.
SAN DIEGO GAS & ELECTRIC®
P. O . B OX 1 2 9 8 3 1 , S A N D I E G O, C A 92 1 1 2- 9 8 3 1
1-800-411-SDGE (7343)
w w w. s d g e . c o m /d r p
© 2009 San Diego Gas & Electric Company. All copyright and trademark rights reserved.
0980252 1109
E N E R GY E F F I C I E N C Y
COMMERCIAL & INDUSTRIAL
Energy Efficiency
Business Incentives
What are Energy Efficiency
Business Incentives?
These programs and
services are one way
SDG&E is here for you
every day.
Energy Efficiency Business Incentives
(EEBI) offers incentive payments for energy
efficiency projects involving the installation
of new, high-efficiency equipment or systems.
A project may consist of the retrofit of
existing equipment/systems or the installation of equipment associated with new/
added load.
Estimation software or engineering calculations are used to estimate the energy
savings and incentive depending on the
type of energy efficiency measure installed.
Some projects may require a measured
savings approach. Incentives are paid based
on the quantity of kilowatt-hours (kWh) or
therms saved resulting from the installation
of the new equipment or system.
required to benchmark their building
using ENERGY STAR® Portfolio Manager.
Please note that not all buildings are eligible
to receive a benchmark score.
What are the Project
Requirements?
Who is Eligible?
Any commercial, industrial or agricultural
customer who pays the public goods charge
and/or demand-side management surcharge
is eligible to participate regardless of size
or project scope. Customers who participate
in our energy efficiency programs and are
eligible to receive a benchmark score are
The equipment must exceed government
standards, must operate at least five years
and must not overlap other incentive
programs offered by the utility.
Pre-inspections are required for
all projects.
Incentives for Calculated Savings Approach
Lighting
$0.05/kWh
$100/Peak kW*
A/C & Refrigeration
$0.15/kWh
$100/Peak kW*
Other (motors, fans, etc.)
$0.09/kWh
$100/Peak kW*
Natural Gas
$1.00/Therm
Incentives for Measured Savings Approach will receive
an additional 10% to help offset the measurement costs.
* Peak Demand Reduction Incentive
Are there Any
Limitations?
Applicants are eligible to
receive up to 50% of the
cost for each project for
calculated (EEBI) measures
or the calculated savings
amount, whichever is less.
Measures involving cogeneration or fuel-switching
projects are not eligible.
(Continued on back)
How Do I Apply?
Complete and submit the program application
forms which can be found at sdge.com/eebi or e-mail us at
eebi@semprautilities.com for assistance with completing
the application forms.
What is the Deadline for Participation?
Program incentive funds will be allocated on a first-come,
first-served basis, until all funds are committed or until
December 31, 2012, whichever occurs first. If all funds
are committed prior to December 31, 2012, applications
received by December 31 will be placed on a waiting list
by SDG&E®, and will be notified in order of receipt if
additional funds become available.
Managing Your Energy Use
SDG&E has programs and services to help your business get
more out of the energy that you use. Information on everything from seminars to online energy analysis tools, rebates
and other financial incentives can be found on our Energy
Savings Center website at sdge.com/business. Helping
businesses manage their energy use is one of the ways SDG&E
is committed to providing exceptional customer service.
Payment Schedule:*
Benchmarking
Benchmarking with the Environmental Protection Agency’s
ENERGY STAR Portfolio Manager allows you to track and
assess energy performance across your entire portfolio of
buildings in a secure online environment. Portfolio Manager
will rate your facility’s energy performance on a scale
of 1 to 100 relative to similar buildings nationwide. Additional
information on energy planning is available through our
Continuous Energy Improvements initiative at sdge.com/cei.
Programs are funded by California utility customers and administered by San Diego Gas & Electric®
(SDG&E) under the auspices of the California Public Utilities Commission. Program incentive funds
will be allocated on a first-come, first-served basis, until all funds are committed or until December 31,
2012, whichever occurs first. The selection, purchase, and ownership of goods and services are the
sole responsibility of the customer. SDG&E makes no warranty, whether express or implied, including
warranty of merchantability or fitness for any particular purpose, use or application of selected
goods and services.
Measurement &
Verification (M&V)
Approach
Payment Schedule
Calculated Savings
Approach
100% — after installation
and verification
none
Measured Savings
Approach
60% — after installation
and verification
1 year
40% — one (1) year after
installation date with
verification
* If the project is very complex and/or involves new technology, we
reserve the right to require a 2-year M&V period for customers. In this
case, a 40%-30%-30% payment schedule will apply.
1-80 0 -411-SDGE ( 7 343)
sdge.com
©2010 San Diego Gas & Electric Company.
All copyright and trademark rights reserved.
1080056 0410 XXM
E N E R GY E F F I C I E N C Y
COMMERCIAL & INDUSTRIAL
Energy Efficiency
Business Rebates
What are Energy Efficiency
Business Rebates?
Offers rebates to help
business customers offset
the cost of installing
energy-efficient equipment.
Energy Efficiency Business Rebates (EEBR)
offer rebates to eligible business customers
for installing energy-efficient lighting,
refrigeration, foodservice, natural gas and
other technologies. Installing energy-efficient
equipment in a business can help reduce
energy consumption and operating expenses,
which leads to greater profitability, productivity
and efficiency. Rebates are designed to encourage
such installations by helping to offset the cost
of installing energy efficient equipment.
Who is eligible?
EEBR is open to nonresidential customers
with existing buildings that have an electric or
natural gas account with SDG&E®. Nonresidential
customers include commercial, industrial
and agricultural customers.
What are the project requirements?
The equipment must meet the requirements
listed in the Rebate Application and the
Product Catalog. All equipment must be new.
Used or rebuilt equipment is not eligible for a
rebate. If a customer has received an incentive
or service from another state or local Public
Goods Charge program, they are ineligible to
receive a rebate for the same measure(s).
Are there any limitations?
Fuel switching and new construction do not
qualify. The total rebate limit is $350,000 per
service account, per fuel, per calendar year.
Customers with multiple service accounts or
chain account customers may receive rebates
for multiple projects; provided that each
individual service account or site limit of $350,000
is not exceeded. There is no limit on the number
of service accounts that may participate.
How do I apply?
You must complete and submit the application forms along with your benchmarking
ENERGY STAR® Statement of Energy Performance.
The Rebate Application forms and the Product
Catalog can be found at sdge.com/businessrebates,
while information about benchmarking can be
found at sdge.com/benchmarking.
Managing Your Energy Use
SDG&E has programs and services to help
your business get more out of the energy
that you use. For more information please visit
our Energy Savings Center at sdge.com/esc or
call us at 1-800-644-6133. Helping businesses
manage their energy use is one of the ways
SDG&E is committed to providing exceptional
customer service.
SDG&E rebate programs are funded by California utility customers
and administered by SDG&E under the auspices of the California
Public Utilities Commission. This program is provided to qualified
participants on a first-come, first-served basis until program funds
are no longer available. SDG&E is not responsible for any goods or
services that you or a vendor may select. This program may be
modified or terminated without prior notice.
1-80 0 -411-SDGE ( 7 343)
sdge.com
©2010 San Diego Gas & Electric Company.
All copyright and trademark rights reserved.
1080062 0410 XXM
ONLINE TOOLS &
OTHER RESOURCES
kWickview: Online Energy Monitor
Track and manage your business energy usage online.
• Export data – view data as graphs
or charts, and export them into a
spreadsheet program or into a PDF.
You can also have reports automatically
emailed to you at pre-determined
intervals.
How do I access kWickview?
You can either:
• Visit www.sdge.com/kwickview.
• Click on the kWickview link at
www.sdge.com/drp.
What is kWickview?
®
kWickview is an online tool from SDG&E
that provides energy use data via the
Internet to businesses with special interval
data recorder (IDR) meters. The energy
use data is measured in 15 minute intervals
over a 24-hour period, and can be
downloaded and viewed the next morning.
Who can use kWickview?
kWickview is available to business
customers with an installed IDR meter.
Also, business customers participating in
a Demand Response program have access
to kWickview.
Is special software needed to
use kWickview?
No, kWickview is a web-based online tool.
© 2006 San Diego Gas & Electric Company.
All copyright and trademark rights reserved.
All you need is a computer with Internet
access and a web browser.
What can I do with kWickview?
How can I learn more
about kWickview?
kWickview can help you track and manage
your energy usage online. Here’s some of
the things you can do with kWickview:
Visit www.sdge.com/kwickview and
view an interactive flash-based demo
of kWickview, or to sign up for regularly
scheduled kWickview trainings.
• Load profile comparisons – know when
and how you are using energy. Conduct
detailed analysis with pinpoint
accuracy.
Managing your energy use
• View usage history – view daily, weekly
or monthly total consumption and peak
demand. View usage over different time
periods.
• Run energy-use comparisons –
compare individual meters or sites, or
group them for side-by-side analysis.
You can also normalize data to help put
comparison data in better context.
S A N D I EG O G A S & E L EC T R I C ®
P. O . B OX 1 2 9 8 3 1 , S A N D I EG O, C A 92 1 1 2- 9 8 3 1
w w w. s d g e . c o m
SDG&E has programs and services to help
your business get more out of the energy
that you use. Information on everything
from seminars, online energy analysis
tools, rebates and other financial
incentives can be found 24 hours a day,
seven days a week at
www.sdge.com/business.
Helping businesses manage their energy
use is one of the ways SDG&E is committed
to providing exceptional customer service.
E Printed on Recycled Paper
0640060 1106
TECHNICAL INFORMATION
& RESOURCES
Optimize Your IT Infrastructure and
Reduce Costs with Server Virtualization
Financial incentives
from SDG&E® may help
you save thousands
of dollars per year on
your operating costs
Growing enterprises have ever-increasing
needs for more computing power. Yet the
costs associated with obtaining that added
capacity go beyond the purchase of new
server hardware. Additional power, facility
Server virtualization
adds up to real savings
20 Conventional servers under
moderate conditions consumes about
90,000 kWh / year
1 new host server, supporting 20
virtual machines under moderate
conditions consumes about
6,600 kWh / year
90,000 kWh – 6,600 kWh =
83,400 kWh savings
cooling, network and storage infrastructure,
administration, maintenance, and data center upgrades or construction are also part
of the equation that can add up quickly.
To help you meet your organization’s
expanding IT requirements while at the
same time reducing your operating and
energy costs, SDG&E® provides significant
financial incentives when you implement
server virtualization.
What is server virtualization?
83,400 x $0.08 =
$6,672 SDG&E Energy Efficiency
Program Incentive
Server virtualization consolidates many
physical servers running individual operating
systems and programs into one physical
server with multiple virtual server
partitions that act as independent servers.
In other words, one server efficiently
doing the work of many.
Server CPUs typically run at about 5-15
percent efficiency, meaning you’re paying
for a lot of unused computing power. With
server virtualization, software is used to
boost a server’s operating efficiency to
over 80 percent in many situations.1 The
end result: the workload currently handled
by 20 servers could now be accomplished
with just one—without any anticipated
decrease in performance. To the end-user,
server virtualization is transparent. To
your IT staff, the improvements might be
substantial…along with your cost savings.
(continued)
1
CPU efficiency improvement varies according to
workloads, hardware, configuration and other factors.
OPTIMIZE YOUR IT INFRASTRUCTURE (continued)
Lowering your TCO, improving
IT deliverables
For CFOs, server virtualization means
fewer servers working more efficiently.
Capital spending on costly equipment
upgrades, installation and maintenance
may be reduced because less equipment is
required—equipment that can be placed in
a smaller space. This equates to lower
power consumption and facility cooling
requirements, and may lessen the need
to add more support infrastructure and
IT staff.
For CIOs, server virtualization could
provide improved manageability. By
consolidating the number of servers you
must maintain, you may have more quality
staff time for improving services instead
of managing hardware. And with a smaller
equipment footprint, it is likely you could
deliver greater responsiveness to changing
company needs. System backup would be
© 2007 San Diego Gas & Electric Company.
All copyright and trademarks rights reserved.
easier, because a complete virtual machine
environment is saved as a single file. Disaster
recovery may be faster, too, since virtual
servers are isolated from the host and
other virtual machines. If a virtual machine
crashes, all others should be unaffected.
How SDG&E can help you pay
for server improvements
Server virtualization is an important part
of SDG&E’s energy efficiency incentive
programs that can help lower your ROI
on such projects tremendously. Incentives
of 8 cents per kilowatt hour saved are
available, meaning you may receive thousands of dollars toward energy saving
server virtualization project costs. Your
company could be able to both run more
efficiently and lower it’s operating costs
at the same time. Plus, you would help
make more energy available for homes and
businesses throughout Southern California.
SAN DIEGO GAS & ELECTRIC®
P. O . B OX 1 2 9 8 3 1 , S A N D I E G O, C A 92 1 1 2- 9 8 3 1
w w w. s d g e . c o m
Give us a call—we’ll help you get started
SDG&E can help you estimate your energy savings in advance and determine just what your
financial incentives from SDG&E might be.
Whether you’re a co-location company, a
biotech firm, data service center, or server
farm…anyone with multiple servers can
save substantial time and money—and
utilize more computing power with lower
equipment, support and energy costs—
through server virtualization.
Providing customers with energy
efficiency information is one of the
ways SDG&E works to provide exceptional
customer service. To learn more, call
1-800-644-6133 or visit www.sdge.com
Rebate/incentive programs are funded by California utility
customers and administered by SDG&E, under the auspices
of the California Public Utilities Commission. Programs may be
modified or terminated without prior notice, and are provided
on a first-come, first-served basis until program funds are no
longer available. SDG&E is not responsible for any goods or
services selected by the customer.
E Printed on recycled paper
0740053 0807 2.5M
INTEREST-FREE FINANCING
On-Bill Financing Option
energy savings not to exceed the maximum
loan term. Loan funds must be used for the
purchase and installation of qualifying
energy efficiency measures.
What are the loan limits?
The project cost (after reduced rebates or
incentives are applied) must be a minimum
of $5,000. Loan maximums per meter are:
• $100,000 for business customers with
a 5-year maximum loan term
• $250,000 for tax-payer funded
customers with a 10-year maximum
loan term
How do I apply?
What is On-Bill Financing?
The On-Bill Financing (OBF) Program
helps qualified commercial and taxpayerfunded customers pay for energy-efficient
business improvements through their
SDG&E® bill. OBF works in conjunction with
the SDG&E rebate and incentive programs
listed to provide an interest-free financing
option for customers eligible to participate
in such rebate and incentive programs.
Who is eligible?
Customers that are eligible for On-Bill
Financing must meet the following criteria:
• The customer must receive a rebate
or incentive through an SDG&E energyefficiency program.
• The customer must have had an active
SDG&E account for the past two years
for the same business.
• The customer's SDG&E account must
be in good standing, with no deposit
on record and no disconnect notices
in the last 12 months.
Participation in one of the following
programs is required for On-Bill Financing:
Small Business Super Saver, Express
Efficiency, Standard Performance Contract,
Energy Savings Bid and select Utility Third
Party Programs.
Owners of multi-family units who do not
live on the premises may qualify for financing
through the Multi-Family Rebate program.
Will On-Bill Financing affect
the measure rebate amount?
Rebates and incentives awarded to
customers who complete non-comprehensive
projects will be reduced by 10%.
Comprehensive projects are defined as two
or more distinct measures not including
CFLs or delamping.
How is the loan term calculated?
The loan term for the project is determined
by the repayment period of the equipment
selected through the eligible program(s)
and is calculated based on estimated annual
To find out more about this program,
including details, terms and conditions,
and a list of all of the energy-efficiency
applications with which OBF can be used,
please visit www.sdge.com/obf. Or, call
or e-mail us:
• Energy Information Center
(Monday - Friday, 8am - 5pm)
1-800-644-6133
• SDGEOBF@semprautilities.com
Managing Your Energy Use
SDG&E has programs and services to help
your business get more out of the energy
that you use. Information on everything
from seminars to online energy analysis
tools, rebates and other financial incentives
can be found 24 hours a day, seven days
a week on our Energy Savings Center
website at www.sdge.com/esc.
Helping businesses manage their energy
use is one of the ways SDG&E is committed
to providing exceptional customer service.
On-Bill Financing is provided to eligible customers on a first-come,
first-served basis until program funds are no longer available. OBF
is funded by California utility customers and administered by SDG&E
under the auspices of the California Public Utilities Commission.
SAN DIEGO GAS & ELECTRIC®
P. O . B OX 1 2 9 8 3 1 , S A N D I EG O, C A 92 1 1 2- 9 8 3 1
w w w. s d g e . c o m
© 2009 San Diego Gas & Electric Company. All copyright and trademark rights reserved.
E Printed on recycled paper with soy-based inks.
0980007 0109
INTEREST-FREE FINANCING
On-Bill Financing Option
Frequently Asked Questions
be reduced by 10%. Comprehensive projects
are defined as two or more distinct
measures not including CFLs or delamping.
6. How is my loan term calculated?
Below is a sample of a project:
Energy savings is based on equipment
installed multiplied by your average cost
per kilowatt hour.
1. Who qualifies for On-Bill Financing?
On-Bill Financing is available to any
commercial or taxpayer-funded customer
participating in the following programs:
Small Business Super Saver, Express
Efficiency, Standard Performance Contract,
Energy Savings Bid, Multi-Family Rebate
Program (for owners not living at the
premises) and Utility Third Party Programs.
Financing is available for measures
qualifying for a rebate or incentive.
2. Is there a credit check involved?
SDG&E® determines eligibility by checking:
• If you have had an active account
for at least two years, or if you have
moved your business from another
location you must have at least one
year of energy usage at new location
• If there are any disconnect notices
in the last 12 months
• If there is a deposit on hand
3. Can I finance any new equipment I want?
Only equipment qualifying for SDG&E
rebates or incentives can be financed
through OBF.
4. Are there any other requirements that
I need to know about?
If your equipment qualifies for a rebate or
an incentive, you must also make sure that
your project meets these requirements:
• For business customers, loans must
have a minimum of $5,000, and a
maximum up to $100,000 per meter,
with a simple payback of no more than
5 years.
• For taxpayer-funded customers,
loans must have a minimum of $5,000
financed and a maximum up to
$250,000 per meter, with a simple
payback of no more than 10 years.
5. Do I get my full rebate if I participate
in OBF?
Customers who complete comprehensive
projects will receive a full rebate. Rebates
and incentives awarded to customers who
complete non-comprehensive projects will
Project Cost
$10,000
Rebate/Incentive amount
with 10% OBF reduction
$4,000
Loan Amount
$6,000
Estimated Annual savings
for new equipment
$4,000
Simple payback period
1.6 years
On-Bill Financing
Loan Installment
(1.6 year + 1 month)
$320
7. What if I move to a new location?
If you have a loan through OBF and you move
to a new location, your loan must be paid
in full on your final bill. Payment arrangements
may be made when opening your new account.
8. Can I have more than one loan?
Yes, you can have one loan per meter.
9. Can I install the equipment myself
to finance?
Yes, SDG&E has a loan agreement for
self-installed projects. A pre-inspection by
SDG&E is required for every site prior to
removing old equipment.
10. How do I get started?
Call the Energy Information Center at
1-800-644-6133 to request an application
or download one at www.sdge.com/obf.
SAN DIEGO GAS & ELECTRIC®
P. O . B OX 1 2 9 8 3 1 , S A N D I EG O, C A 92 1 1 2- 9 8 3 1
w w w. s d g e . c o m
© 2009 San Diego Gas & Electric Company.
All copyright and trademark rights reserved.
E Printed on recycled paper with soy-based inks.
0980009 0109
ENERGY-EFFICIENCY
CASE STUDIES
SC
ENGINEERS
ABOUT SAVINGS
BY DESIGN
Energy-efficient buildings
happen by design. They
happen because they
make sense — for the
owner, the design team,
the bottom line, and
the environment.
No matter how you are
involved in the design
and construction of a
commercial or industrial
project, SDG&E’s Savings
By Design Program can
help provide long-term
savings in the use of
the building as well
as cash incentives to
the design team and
the building owner.
SC Engineers designs better buildings
There is no off-the-shelf solution for energy-efficient
buildings. For maximum energy savings, efficiency must be
designed into the building from scratch. And that’s where
Shadpour Consulting Engineers, Inc. shines as a pioneer
in creative design solutions.
SC Engineers is a consulting mechanical engineering
firm based in Rancho Bernardo, a community within the city
of San Diego. They provide innovative design solutions for
HVAC, plumbing, and building automation systems, as well
as services for total building commissioning and energy
management programs. They strive to forge integrated
business partnerships with their clients and produce
long-term, sustainable design solutions.
An educated approach
Company president Frank Shadpour is a registered
Mechanical Engineer, LEED® accredited professional, and
ASHRAE Fellow. Since 1987, he has taught courses in HVAC
Design and Control Systems Engineering at the University
of California, San Diego.
SC Engineers is recognized as a local leader in
sustainable design and energy-efficiency planning.
With those credentials, it’s not surprising that Shadpour
is a long-time believer in sustainable building design.
“In addition to teaching at UCSD, I’ve been part of
SDG&E’s Education & Training Program,” Shadpour says. “I
feel fortunate to have a platform for touting energy efficiency.”
SC Engineers was founded on the principles of “lean
thinking.” This carries through into all aspects of their
engineering design and corporate philosophy.
“People can save energy and money through smart building
design and efficient management of the various building
systems. The energy savings often offset the associated costs.
It doesn’t cost extra to go green if you do it right from the start.”
“We’ve made it our business to know SDG&E’s incentive
and rebate programs inside and out,” says Shadpour. “This
knowledge means our clients can maximize every opportunity.
And when that happens, we know we’ve done our job.”
Their efforts have helped SDG&E® customers realize
significant energy and financial savings through
intelligent, energy-efficient designs and retrofits.
Education & Training
An excellent result
SDG&E business seminars
and training opportunities
cover the latest energyefficiency technologies for
motors, lighting, heating,
air-conditioning (HVAC)
systems, and more.
SC Engineers is an innovative leader and approved
provider for SDG&E’s Retrocommissioning Program (RCx).
RCx is a systematic process for optimizing a building’s
operating and maintenance profile, focusing on low-cost or
no-cost operational measures. Most projects see a 5% to 20%
reduction in utility costs as a result of SC Engineers’
retrocommissioning efforts.
SC Engineers also provides demand response studies,
which help identify opportunities to reduce demand. In
the last year alone, SC Engineers identified over 4.5
megawatts (MW) in peak electrical demand reduction,
averaging more than a 10% reduction per customer.
SC Engineers incorporates energy savings into their own
design projects as well. Recent projects include the Rady
Children’s Acute Care Tower and Ronald McDonald House,
with a combined projected energy savings of nearly 1.4 million
kilowatt-hours (kWh) and 38,000 therms per year.
“The Children’s Hospital project is likely to be the first
LEED® hospital in California,” says Chip Fox, Manager of SDG&E’s
New Construction Energy-Efficiency Programs. “Frank is also
heavily involved in the community doing a variety of
fundraising for the local Cancer Society.”
To date, SC Engineers & Friends has raised more than
$200,000 benefiting non-profit organizations in San Diego
Seminars include rebate
and incentive information,
so you can learn which
energy-efficiency programs
make the most sense for
your facility.
These free events are held
throughout the year at
various locations. Register
at sdge.com/training.
Retrocommissioning
The Retrocommissioning
Program (RCx) provides
incentives and training
for large businesses to
achieve energy savings
and improve occupant
comfort through costeffective optimization
of building performance.
For more information,
contact Margaret Finley,
SDG&E Program Manager,
at 858-636-5732.
Demand Response
Financial incentives, like
bill credits and electric rate
discounts are available to
companies that can save
energy during temporary
critical times through
SDG&E’s Demand
Response programs.
Programs are available
for companies of all types
and sizes. To identify
demand response
opportunities at your
facility, visit sdge.com/esc.
Lyle Willis, Jeremy Clifton,
Frank Shadpour (L to R)
including the American Cancer Society and City of Hope.
“Our combined efforts in the future Rady Children’s Hospital
and Ronald McDonald House will result in very healthy and
well-designed buildings,” says Marianne Sy, Account Executive
for SDG&E's Savings By Design Program. “SC Engineers has
done an excellent job in influencing owners and the design
community to do the right thing — simply because they
believe in it themselves.”
Energy efficiency starts with a plan.
To see how the Savings by Design
Program can work for your business,
contact your SDG&E account
executive, call 1-800-411-7343
or visit sdge.com/savingsbydesign.
© 2008 San Diego Gas & Electric Company. All trademarks belonging to their respective owners.
All rights reserved. Some materials used under license, with all rights reserved by licensor.
C Please recycle.
0850038-BT 0508