SECTION 26 28 13 FUSES PART 1 1.01 1.02 DESCRIPTION A. Furnish and install 600 volt and 250 volt fuses as herein specified and sized as shown on the Drawings. B. Provide all accessories as specified. C. All fuses shall be provided by the same Manufacturer. D. For fuses greater than 600 volts, refer to appropriate equipment Specification Section. QUALITY ASSURANCE A. 1.03 1.04 A. For Review: 1. Product data sheets of fuses and accessories 2. Fuse curves and selectivity ratio charts B. To be included in Record and Information Manuals: 1. One (1) copy of each approved submittal 2. Certificate of Material Receipt MANUFACTURERS PART 2 PRODUCTS Fuses shall be 600 volt, UL Class L, current limiting, 200,000 Ampere interrupting rating with minimum time delay of 4 seconds at 500 percent rating. Fuse terminals shall be silver-plated, and fuse links shall be silver. 1. Bussmann KRP-C HI-CAP FUSES - 600 AMPERES AND BELOW A. 15-089 Fuses 1. Bussmann 2. Littelfuse FUSES - 601 AMPERES AND ABOVE A. 2.02 All equipment shall be UL listed and labeled and in accordance with applicable NEMA and ANSI Standards. SUBMITTALS A. 2.01 GENERAL Fuses shall be rated 600 volt for nominal 480 volt systems and 250 volt for nominal 240 or 208 volt systems. Fuses shall be UL Class RK, current limiting, 200,000 Ampere interrupting rating, dual element, with minimum time delay of 10 seconds at 500 percent rating. 1. Bussmann LPN-RK (250 volt) or LPS-RK (600 volt) 26 28 13 - 1 26 28 13 - FUSES 2.03 B. In-line fuse and fuse holders for high intensity discharge luminaires shall be 600 volt, UL Class CC, current limiting, 200,000 Ampere interrupting rating, single element non-time delay fuses in a waterproof single or two (2) pole fuse holder. 1. Bussmann KTK-R in HEB or HEY holder C. Motor control circuits shall use 600 volt, UL Class CC, current limiting, 200,000 Ampere interrupting rating, single element, non-time delay fuses. 1. Bussmann KTK-R D. In-line fuse and holder combination units for fluorescent luminaires shall be glass ferrule fuses in a two (2) piece insulating fuse holder with 6 inch pigtail conductors. 1. Bussmann GLR with HLR holder FUSE REDUCERS A. 2.04 SPARE FUSE CABINET A. Spare fuse cabinet shall be heavy 0.080" gauge aluminum wall mountable cabinet with internal shelves, 30" x 24" x 12", locking handle with cylinder type lock. B. Bussmann SFC PART 3 3.01 3.02 Fuse reducers shall be Bussmann 200-R or 600-R Series. EXECUTION INSTALLATION A. Install fuses in all fusible devices with name and fuse size facing outward. B. Install spare fuse cabinets in main electrical room. Provide a list of all spare fuse sizes, types and quantities on inside of door. C. Install fuse reducers in equipment where required. SPARE PARTS A. Provide spare fuses in the following quantities: 1. 601 Amperes and above - three (3) of each current rating 2. 600 Amperes and below - 10% of quantity used (minimum three (3)) of each voltage and current rating and UL Class B. Refer to Section 26 00 99, "Requirements for Contract Completion." END OF SECTION 26 28 13 15-089 26 28 13 - 2