ResidualCurrentCircuitBreakers FI,NFI • Residualcurrentcircuitbreakers(RCCB)areusedforprotectionagainstindirectcontact,fireprotectionand additionalprotectionagainstdirectcontact. • Theyaresuitableforisolation. • Nooverloadprotectionorshort-circuitprotectionisbuiltinRCCB. • Twoversionsaccordingtobehaviourinpresenceofd.c.components: -TypeA(markedNFI)-sensitivetoalternatingandpulsatingd.c.residualcurrents. -TypeAC(markedFI)-sensitivetoalternatingresidualcurrentsofsineform. • Assemblytoa35mmwidemountingrailinaccordancewithEN60715. • Optionaloperationposition. • DegreeofprotectionIP20,degreeofprotectionIP40afterinstallationinadistributionbox. • Additionalcolourdisplayofthepositionofmaincontacts(red-contactsclosed,green-contactsopen). • Aterminalshapepreventsconnectionofaconductoroutsidetheconnectionarea. • Specialversions: - Type S:aswitchwithdelayedbreakenablingselectivityregardingageneraltypeandashort-timedelayedtype (typeG)connectedontheloadside.Breaktimeislongerthan40ms.Theswitchesexcelinhigh resistancetosurgecurrents(upto3kA),whichpreventsunwantedtrippings.Theirratedcurrentsarefrom25to 100A,andratedresidualoperatingcurrentsare100,300and500mA.ThisistypeA,andacustomercanchoose betweenNFI2Stwo-poleandNFI4Sfour-poleswitches. - Type G:ashort-timedelayedbreakingcharacteristic(min.non-actuatingperiodis10ms).Theswitchesare resistanttounwantedtrippingsatcurrentimpulsesorwhenbuilt-ininspecialcriticalconditions.Theyexcelinhigh resistancetosurgecurrents(upto3kA)andareliableoperationincaseofhighmakingcurrents.Rated currentsarefrom25to100A,andratedresidualoperatingcurrentsare30,100,300and500mA.ThisistypeA, andacustomercanchoosebetweenNFI2Ktwo-poleandNFI4Kfour-poleswitches. VersionsSandGcomplywiththeEN61008standard.Regardingtrippingtimes,typeGalsocomplieswith ÖVE/ÖNORME8601(supplementtoÖVEEN61008).BothtypesareVDEapproved. - FIR – FIT combination:Itisusedfortheprotectionincircuitswhereoperationalcurrentsarehigherthatrated currentsofresidualcurrentcircuitbreakers.AnactuatingrelayFIRisseparatedfromaFItransformer(FIT).The functionofloadswitchingisperformedbythecontactororacircuit-breakerwithanundervoltagerelease. Acombinationratedcurrentthereforedependsonselectedswitchingdevices.Itislimitedwithcablecross-sectionswhich canbeinsertedthroughtheholeoftheFItransformer.Rateddifferentialcurrentsare0.3A,0.5A,1Aand2A. 99 ResidualCurrentCircuitBreakers FI,NFI TECHNICALDATA TypeAC FI2 FI4 A NFI2 NFI4 A-G NFI2K NFI4K A-S NFI2S NFI4S Standards IEC/EN61008,typeA-Gacc.toÖVEE8601 Approvals VDE,NF,GOST-R No.ofpoles Ratedvoltage V Un Ratedimpulsevoltage 230/400 kV 4 f Hz 50 In IΔn mA Im=IΔm A Ratedcurrent Ratedresidualoperatingcurrent =Ratedresidualmakingandbreakingcapacity 4 230 Uimp Ratedfrequency Ratedmakingandbreakingcapacity 2 A 16,25,40,63,80,100 25,40,63,80,100 10(In=16,25A),30,100,300,500 800(In=16-80A) 30,100,300,500 1000(In=100A) 63(In=16-40A) Max.back-upfuseforshort-circuitcurrent 80(In=63,80A) Iv A Inc kA 10 S mm2 1…35 100(In=100A) Ratedconditionalshort-circuitcurrent Terminalcapacity ms 1xIΔn:≤300ms;5xIΔn:≤40ms ms typeA-G-1xIΔn:10ms<T≤300ms;5xIΔn:10ms<T≤40ms typeA-S-1xIΔn:130ms<T≤500ms;5xIΔn:50ms<T≤150ms Ambiemttemperature °C −25…+40 Storagetemperature °C Weight kg Tighteningtorque Nm Max.trippingtimes,typesAC,A Responsetimedelay,typesA-G,A-S −35…+60 0.23 0.39 2.0 ACCESSORIES Asealingcoverfortwo-pole(SCNFI2)andfour-pole(SCNFI4)switches DIMENSIONS FI2,NFI2 FI4,NFI4,FIR ORDERINGDATA FI2 NFI4 100 - - 25 40 /0,03 /0,3 RatedresidualoperatingcurrentIΔn(A) RatedcurrentIn(A) Type FIT