Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high performance, versatility and standardization in a range of molded case circuit breakers. The ABB Tmax has been developed to complement the performance-proven Isomax line of circuit breakers. This new breaker, with a range up to 225A, has several very big features that go along with its very small size: • Double insulation – this construction characteristic allows for the UL Listed field installation of internal accessories without exposure to the power poles. • Positive operation – all molded case breakers from ABB ensure that the toggle indicates the precise position of the moving contacts. This guarantees safe and reliable signaling by the device. • Installation – Tmax T1, T2 and T3 can be installed in panels and switchboards in either the horizontal or vertical planes while being fed from either end without any derating of their performance characteristics. • Range of accessories – in the pursuit of standardization, all Tmax internal and external accessories can be utilized across the entire range from 10A to 225A. • Interrupt ratings from 22kAIC at 480VAC up to 65kAIC. • Standard depth – all three frames are 2.76 inches deep • UL Listed and IEC rated for global application and acceptance. 15 T MC max CB s The ABB Tmax has the performance and accessories to satisfy all industry requirements in the 480VAC to 500VDC ranges. A single pole molded case version is available for the first time. Standardized sizing and accessories make it easy to design and install these items in all applications. Frame sizes — three basic sizes The ABB Tmax series includes three basic frame sizes as well as the T1 single pole with the range rated from 10A to 225A at 480VAC. The various versions carry the following interrupting capacities: • B basic breaking capacity • N normal breaking capacity • S standard breaking capacity • H high breaking capacity Derived versions • T2 circuit breakers with LS/I electronic trip units • Switch disconnectors in T1 and T3 frames • Circuit breakers for motor circuit protection (MCPs) • Circuit breakers for direct current ABB Tmax versions • • • Fixed: all models Plug-in: T2 & T3 UL UL File #E93565 (breakers and MCPs) #E116596 (Accessories) #E116595 (Molded case switches) Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Spec Tech Industrial 203 Vest Ave. Valley Park, MO 63088 Phone: 888 SPECTECH Fax: 636 537-1405 www.spectechind.com 15.129 AC 1000 - 11/03 15 15 General information Selection guide T1 – T3 ax Tm CBs MC T1 Circuit-breaker type Maximum frame continuous rated current Rated operational voltage Test voltage T2 T3 100 100 225 50/60 Hz V 480 480 480 1 min. 50/60 Hz V 3000 3000 3000 kV 6 6 6 No. 1-3 2-3-4 2-3-4 Performance level 240VAC kA RMS 277VAC kA RMS 480VAC kA RMS 250VDC 1 kA RMS 500VDC 1 kA RMS Icu T1 A Poles IEC-947 rated ultimate short circuit breaking capacity T3 40°C Rated impulse withstand voltage UL/CSA short-circuit interrupting capacity UL 489, File #E93565 CSA, File #LR90467 T2 220/230VAC 300/400/415VAC 440VAC 500VAC 660/690VAC kA RMS kA RMS kA RMS kA RMS kA RMS Overcurrent trip unit/relays Thermal-magnetic Microprocessor-based B (1P) N S H N S — 18 — — — 50 — 22 25 25 65 — 35 — — 100 — 65 — — 50 — 25 25 35 65 — 35 25 35 25 — — — — 50 36 22 15 6 85 50 45 30 7 100 70 55 36 8 50 36 25 20 5 85 50 40 30 8 • • • — • — • • • — • • Version — Terminals Fixed — front or rear Plug-in — front or rear (IEC) 15 Dimensions (fixed circuit-breaker) 2P & 3P (H x W x D) in 5.12 x 3.00 x 2.76 5.12 x 3.54 x 2.76 5.9 x 4.13 x 2.76 4P (H x W x D) in 5.12 x 4.00 x 2.76 5.12 x 4.72 x 2.76 5.9 x 5.51 x 2.76 25,000 Mechanical duration Operations No. 25,000 25,000 Frequency ops./hour 240 240 120 lbs 1.98 2.43 4.63 Weights (Fixed 3P) 1 For use with thermal-magnetic trip only: 250VDC, 2 poles in series 500 VDC, 3 poles in series 15.130 AC 1000 - 11/03 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com General information Catalog number explanation 15 T MC max CB s T3 H 080 T W - 2 xxx Accessories (added in alpha-numeric order) 1 A = Auxiliary Switch S_ = Shunt trip with voltage code U_ = Undervoltage release with voltage code Number of poles -2 = 2 pole -4 = 4 pole None = 3 pole Type connectors W = None L = Lugs included Trip unit function B D T M E5 = = = = = LI/S Molded Case Switch (MCS) Thermal-magnetic – 10X Mag Magnetic only (MCP) Electronic MCP Current rating 015 = 080 = 100 = 225 = 15A 80A 100A 225A 15 Interrupting rating class B N H S = = = = Basic Normal High Standard Frame size T1 = 100A T2 = 100A T3 = 225A 1 Consult ABB for factory installed accessories. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15.131 AC 1000 - 11/03 15 ax Tm CBs MC T1 100A, 480V Standard thermal-magnetic T1 HxWxD 5.12" x 3.00" x 2.76" General The T1 breaker family ranges from 15 through 100 amperes. The T1 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection. Thermal overload protection is provided by heat sensitive bimetals. Short circuit protection for the breaker is accomplished using a precise magnetic coil. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits. Versions The T1 frame is available in two versions: T = Thermal-magnetic, fixed D = Molded case switch Performance levels The T1 breaker has two performance levels available: B = 277V Single pole N = 480V Three pole 15 UL489 / CSA C22.2 Interrupting capacity (kA RMS) Voltage Continuous rating B (1 pole) N 240VAC 15 – 100A — 50 277VAC 15A 20 – 100A 10 18 — — 480VAC 15A 20 – 100A — — 14 22 250VDC 2 pole series 15 – 100A — 25 500VDC 3 pole series 15 – 100A — 25 IEC-947 Interrupting capacity (kA RMS) Voltage Continuous rating B (1 pole) N 230V 15 – 100A 25 50 415V 15 – 100A — 36 Number of poles 440V 15 – 100A — 22 The UL/CSA version of the T1 is available in single, three and four pole versions. IEC versions of the T1 are also available with the same dimensions up to 160 amperes. 500V 15 – 100A — 15 690V 15 – 100A — 6 Accessory mounting 250VDC 2 pole series 15 – 100A — 36 The T1 frame is double insulated allowing for UL/CSA factory or field installation of internal accessories. No extra control cables are required for field installation. Shunt trips or UVRʼs mount in the left cavity and auxiliary contacts with bell alarm mount in the right cavity. 500VDC 3 pole series 15 – 100A — 36 Reverse feeding All versions of the T1 family are suitable for reverse feed applications. Molded case switches UL489 switches include no overcurrent protection except for a high instantaneous trip mechanism for self protection. 15.132 AC 1000 - 11/03 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 T1 100A, 480V Standard thermal-magnetic T MC max CB s T1N TMF Breaker IC at 480VAC 14kA T1N 22kA Magnetic trip 3 pole, 480VAC/500VDC catalog number 15A 1000A T1N015TL1 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A 1000A 1000A 1000A 1000A 1500A 1500A 1500A 1500A 1500A 1500A T1N020TL T1N025TL T1N030TL T1N040TL T1N050TL T1N060TL T1N070TL T1N080TL T1N090TL T1N100TL Rating List price $ 402 402 402 402 402 402 402 479 479 479 479 T1B TMF — Single pole Breaker T1B IC at 277VAC 18kA Rating 15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A Magnetic trip 1 pole, 277VAC catalog number List price 1000A 1000A 1000A 1000A 1000A 1500A 1500A 1500A 1500A 1500A 1500A T1B015TL-1 T1B020TL-1 T1B025TL-1 T1B030TL-1 T1B040TL-1 T1B050TL-1 T1B060TL-1 T1B070TL-1 T1B080TL-1 T1B090TL-1 T1B100TL-1 $ 230 230 230 230 230 230 230 262 262 262 262 Magnetic trip 480VAC/500VDC catalog number T1N-D — Molded case switch Breaker T1-D Interrupting capacity 2 240V, 50kA Rating 100A 1000A T1N100DL List price $ 431 15 1 Rated 277/480Y for 15A. 2 With fuse or MCCB protected circuit. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule S1T 15.133 AC 1000 - 11/03 15 ax Tm CBs MC T2 100A, 480V Thermal-magnetic/electronic T2 HxWxD 5.12" x 3.54" x 2.76" General The T2 breaker family ranges from 10 through 100 amperes. The T2 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection as well as a version with microprocessor-based electronic trip unit. Thermal overload protection is provided by heat sensitive bimetals. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits. Versions The T2 frame is available in four versions: T = Thermal-magnetic, fixed B = Adjustable LS/I electronic M = Magnetic only (MCP) E5 = Electronic instantaneous only (MCP) Trip functions These tripping functions are available: L = Long time S = Short time I - Instantaneous UL489 / CSA C22.2 Interrupting capacity (kA RMS) Voltage Continuous rating S H 240VAC 15 – 100A 65 100 480VAC 15 – 100A 35 65 IEC-947 Interrupting capacity (kA RMS) Voltage Continuous rating S H 230V 15 – 100A 85 100 415V 15 – 100A 50 70 440V 15 – 100A 45 55 500V 15 – 100A 30 36 690V 15 – 100A 7 8 250VDC 2 pole series 15 – 100A 50 70 500VDC 3 pole series 15 – 100A 50 70 Performance levels The T2 breaker has two performance levels available: S = Standard H = High Number of poles The UL/CSA version of the T2 is available in two, three and four pole versions. IEC 15 versions of the T2 are also available with the same dimensions up to 160 amperes. Accessory mounting The T2 frame is double insulated allowing for UL/CSA factory or field installation of internal accessories. No extra control cables are required for field installation. Shunt trips or UVRʼs mount in the left cavity and auxiliary contacts with bell alarm mount in the right cavity. Reverse feeding All versions of the T2 family are suitable for reverse feed applications. 15.134 AC 1000 - 11/03 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 T2 100A, 480V Thermal-magnetic/electronic T MC max CB s IC at 480VAC T2S 35kA Breaker IC at 480VAC T2H 65kA Rating 15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A Rating 15A 20A 25A 30A 40A 50A 60A 70A 80A 90A 100A Magnetic trip 2 pole, 480VAC catalog number 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A T2S015TW-2 T2S020TW-2 T2S025TW-2 T2S030TW-2 T2S040TW-2 T2S050TW-2 T2S060TW-2 T2S070TW-2 T2S080TW-2 T2S090TW-2 T2S100TW-2 Price & availability to be announced Breaker Magnetic trip 2 pole, 480VAC catalog number List price 500A 500A 500A 500A 500A 500A 600A 700A 800A 900A 1000A T2H015TW-2 T2H020TW-2 T2H025TW-2 T2H030TW-2 T2H040TW-2 T2H050TW-2 T2H060TW-2 T2H070TW-2 T2H080TW-2 T2H090TW-2 T2H100TW-2 Price & availability to be announced T2 — 100A TMF List price CT rating 2 pole, 480VAC catalog number List price 3 pole, 480VAC catalog number T2S015TW T2S020TW T2S025TW T2S030TW T2S040TW T2S050TW T2S060TW T2S070TW T2S080TW T2S090TW T2S100TW 3 pole, 480VAC catalog number T2H015TW T2H020TW T2H025TW T2H030TW T2H040TW T2H050TW T2H060TW T2H070TW T2H080TW T2H090TW T2H100TW List price $ 575 575 575 575 575 575 575 661 661 661 661 List price $ 785 785 785 785 785 785 785 961 961 961 961 Breaker IC at 480VAC Trip unit type T2S 35kA PR221DS-LS/I 25A 60A 100A T2S025BW-2 T2S060BW-2 T2S100BW-2 T2H 65kA PR221DS-LS/I 25A 60A 100A T2H025BW-2 T2H060BW-2 T2H100BW-2 Price & availability to be announced T2 — 100A frame electronic trip unit 3 pole, 480VAC catalog number List price T2S025BW T2S060BW T2S100BW $ 1033 1033 1119 T2H025BW T2H060BW T2H100BW 1243 1243 1419 T2 — 100A frame magnetic only (MCP) Breaker IC at 480VAC Trip unit type Rating Adjustment range T2S 35kA Mag only 20A 50A 100A T2H 65kA Mag only 20A 50A 100A 3 pole, 480VAC catalog number List price 120 - 240 300 - 600 600 – 1200 T2S020MW T2S050MW T2S100MW $ 498 558 670 120 - 240 300 - 600 600 – 1200 T2H020MW T2H050MW T2H100MW 561 628 753 3 pole, 480VAC catalog number List price Breaker IC at 480VAC T2S 35kA T2H 65kA Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Trip unit type Rating Adjustment range Instantaneous only 25A 60A 100A 25 - 250 60 - 600 100 - 1000 T2S025E5W T2S060E5W T2S100E5W Instantaneous only 25A 60A 100A 25 - 250 60 - 600 100 - 1000 T2H025E5W T2H060E5W T2H100E5W Discount schedule S2T Price & availability to be announced T2 — 100A frame instantaneous only, electronic (MCP) 15.135 AC 1000 - 11/03 15 15 ax Tm CBs MC T3 225A, 480V Standard thermal-magnetic T3 HxWxD 5.9" x 4.13" x 2.76" General The T3 breaker family ranges from 60 through 225 amperes. The T3 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection. Thermal overload protection is provided by heat sensitive bimetals. Short circuit protection begins at 10 times the thermal rating of the breaker using a precise magnetic coil. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits. Versions The T3 frame is available in three versions: T = Thermal-magnetic, fixed M = Magnetic only (MCP) D = Molded case switch UL489 / CSA C22.2 Interrupting capacity (kA RMS) Voltage Continuous rating N S 240VAC 60 – 225A 50 65 480VAC 60 – 225A 25 35 250VDC 2 pole series 60 – 225A 25 35 500VDC 3 pole series 60 – 225A 25 35 IEC-947 Interrupting capacity (kA RMS) Voltage Continuous rating N S 230V 60 – 225A 50 85 415V 60 – 225A 36 50 440V 60 – 225A 25 40 500V 60 – 225A 20 30 690V 60 – 225A 5 8 Number of poles 250VDC 2 pole series 60 – 225A 36 50 The UL/CSA version of the T3 is available in two, three and four pole versions. IEC versions of the T3 are also available with the same dimensions up to 250 amperes. 500VDC 3 pole series 60 – 225A 36 50 Performance levels The T3 breaker has two performance levels available: N = Normal S = Standard Accessory mounting 15 The T3 frame is double insulated allowing for UL/CSA factory or field installation of internal accessories. No extra control cables are required for field installation. Shunt trips or UVRʼs mount in the left cavity and auxiliary contacts with bell alarm mount in the right cavity. Reverse feeding All versions of the T3 family are suitable for reverse feed applications. Molded case switches UL489 switches include no overcurrent protecction except for a high instantaneous trip mechanism for self protection. 15.136 AC 1000 - 11/03 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 T3 225A, 480V Standard thermal-magnetic T MC max CB s T3 — 225A Frame TMF Breaker IC at 480VAC T3N 25kA Breaker IC at 480VAC T3S 35kA Rating 60A 70A 80A 90A 100A 125A 150A 175A 200A 225A Rating 60A 70A 80A 90A 100A 125A 150A 175A 200A 225A Magnetic trip 3 pole, 480VAC/500VDC catalog number 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A T3N060TW T3N070TW T3N080TW T3N090TW T3N100TW T3N125TW T3N150TW T3N175TW T3N200TW T3N225TW Magnetic trip 3 pole, 480VAC/500VDC catalog number 600A 700A 800A 900A 1000A 1250A 1500A 1750A 2000A 2250A T3S060TW T3S070TW T3S080TW T3S090TW T3S100TW T3S125TW T3S150TW T3S175TW T3S200TW T3S225TW List price $ 406 489 489 489 489 1034 1034 1034 1034 1034 List price $ 523 641 641 641 641 1430 1430 1430 1430 1430 T3 — 225A frame magnetic only, (MCP) Breaker IC at 480VAC T3S 35kA Trip unit type Rating Adjustment range Mag only 100A 125A 150A 200A 600 – 1200 750 - 1500 900 - 1800 1200 - 2400 3 pole, 480VAC catalog number List price T3S100MW T3S125MW T3S150MW T3S200MW $ 711 734 860 915 T3S-D — Molded case switch Breaker T3S-D Interrupting capacity 240V, 65kA 1 480V, 35kA Rating 150A 225A Magnetic trip 2 pole, 480VAC/500VDC catalog number 1500A 2250A T3S150DW T3S225DW List price $ 714 1003 15 1 With fuse or MCCB protected circuit. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com Discount schedule S3T 15.137 AC 1000 - 11/03 15 ax Tm CBs MC Accessories Electrical Shunt trips Factory installation KT3S4 Voltage Catalog number suffix 1 480 – 500VAC 220/250VAC/DC 380 – 440VAC 110 – 125VAC/DC 48 – 60VAC/DC 24 – 30VAC/DC 12VDC S1 S2 S3 S4 S7 S8 S9 Field installation List price adder Catalog number T1 – T3 List price $ 324 KT3S1 KT3S2 KT3S3 KT3S4 KT3S7 KT3S8 KT3S9 $ 298 For remote opening of circuit breaker and includes internal cut-off switch to protect solenoid. All shunt trips are left pole mounted and can not be used with undervoltage releases. All shunt trips are approved for use in ground fault systems. Electrical specifications Voltage AC VA DC Watts 24, 120, 240 48 - 60 480 - 500 50 60 55 50 60 — Undervoltage releases Factory installation T1 with KT3S4 Voltage Catalog number suffix 1 480 – 500VAC 220 – 250VAC/DC 380 – 440VAC 110 – 125VAC/DC 60VAC/DC 48VAC/DC 24 – 30VAC/DC U1 U2 U3 U4 U5 U7 U8 List price adder $ 324 Field installation Catalog number T1 – T3 List Price KT3U1 KT3U2 KT3U3 KT3U4 KT3U5 KT3U7 KT3U8 $ 298 Will trip circuit breaker when connected voltage drops to 35 – 70% of undervoltage release voltage rating. Will allow circuit breaker to close (ON) when voltage is approximately 85% of rated voltage. All undervoltage releases are left pole mounted and can not be used with shunt trips. Electrical specifications KT3U2 15 Voltage AC VA DC Watts 24 48 - 60 120 220 - 250 480 - 500 1.5 1 2 2.5 4 1.5 1 2 2.5 — Auxiliary contacts — T1 - T3 Factory installation Contacts Catalog number suffix 1 Form C + 1 BA 3 Form C + 1 BA A A3 List price adder $ 205 262 Field installation Catalog number KT3AS KT3AS3 List Price $ 190 247 Motor operators Field installation T1 with K3TAS Voltage Catalog number 48 – 60VAC/DC 110 – 250VAC/DC KT3M1 KT3M2 List Price $ 645 Electrical specifications Voltage range 85 - 110% rated voltage Inrush power 2500VA / 1000W KT3M1 1 For factory installation add suffix given to end of circuit breaker catalog number per accessory format. 15.138 AC 1000 - 11/03 Discount schedule SAT Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 Accessories Mechanical T MC max CB s Direct mount rotary operator handle Catalog number List price KT3RH $ 146 Handle catalog number List price Direct mount rotary Variable depth rotary handles Frame Mechanism catalog number List price Shaft catalog number List price NEMA 1, 3R, 12 Tmax KT3RH KT3VD-M $ 72 OXP6X430 1 $ 28 OHY65J6 1 OHB65J6 1 $ 80 KT3VD-M 72 OXP6X430 1 28 OHY80L6 1 OHB80L6 1 130 KT3VD-M 72 KT3VD-S 35 KT3VD-H NEMA 4, 4X Tmax NEMA 1 Tmax 87 Locking device Locking device Catalog number List price KT3LD $ 21 OHB65J6 Lugs For breakers Amps Wire size Set of 2 catalog number List price Set of 3 catalog number List price Set of 4 catalog number List price KT2100-2 $6 KT2100-3 $9 KT2100-4 $ 12 — — — — KT3060-3 KT3100-3 KT3150-3 KT3225-3 9 9 12 18 KT3060-4 KT3100-4 KT3150-4 KT3225-4 12 12 18 24 Standard cable lugs T2 100 14AWG-1/0 T3 60 100 150 225 14AWG -2AWG 14AWG -1/0 2AWG-4/0 4AWG-350kcmil OHY65J6 — — — — Extended front terminals Set of 3 Set of 4 For breakers Amps Catalog number List price adder Catalog number T2 T3 100 225 KT2EF-3 KT3EF-3 $ 26 33 KT2EF-4 KT3EF-4 For breakers Amps Catalog number List price adder Catalog number T2 T3 100 225 KT2R-3 KT3R-3 $ 78 98 KT2R-4 KT3R-4 List Price $ 35 44 KT3LD Rear terminals Set of 3 Set of 4 List Price $ 105 131 OHB 65 J 6 KT3100-3 Color Shaft size (diameter in mm) B =Black Y =Red/Yellow Physical size (length in mm) J = Type 1, 3R, 12 L = Type 1, 3R, 12, 4, 4X KT2EF-3 KT2R-3 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 1 Use Discount Schedule H6. Discount schedule SAT Discount schedule H6 — Handles 15.139 AC 1000 - 11/03 15 15 ax Tm CBs MC Accessories Mechanical DIN Rail mounting kits — 35mm DIN For breakers Catalog number List price T1 / T2 T3 KT2DIN KT3DIN $ 33 41 Terminal covers for fixed breakers Low profile 3-pole Low Profile KT2DIN Low profile 4-pole For breakers Catalog number List price Catalog number T1 T2 T3 KT1LTC-3 KT2LTC-3 KT3LTC-3 $ 35 40 50 KT1LTC-4 KT2LTC-4 KT3LTC-4 For breakers Catalog number List price Catalog number T1 T2 T3 KT1HTC-3 KT2HTC-3 KT3HTC-3 $ 37 43 53 KT1HTC-4 KT2HTC-4 KT3HTC-4 List price Catalog number High profile 3-pole High Profile List Price $ 47 54 68 High profile 4-pole List Price $ 50 58 72 Kit consists of two pieces. Plug-in kits for T2 and T3 KT1LTC-3 Moving part For breakers Catalog number T2 — 3-Pole T3 — 3-Pole KT2PMK KT3PMK Fixed part $ 171 190 KT2PFF KT3PFF List Price $ 238 264 Fixed parts accept the same cable and rear terminal kits as the circuit breakers. Sliding bar interlock — front mounted For 2 breakers For breakers Catalog number T1 – T3 KT3MIF2 For 3 breakers List price $ 452 Catalog number KT3MIF3 List Price $ 904 KT1HTC-3 15 KT2PMK KT3MIF2 15.140 AC 1000 - 11/03 Discount schedule SAT Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 Technical data Trip curves Tmax T1 T MC max CB s Tmax T1 100 TMF In = 15 ... 70A t [s ] Tmax T1 100 TMF In = 80 ... 100A 10 4 t [s ] 10 4 10 3 10 3 10 2 10 2 10 10 1 1 10 -1 10 -1 90A 40A 60A 30A 70A 50A 100A 20A 25A 80A 15A 10 -2 10 -1 10 -2 10 -1 1 10 Tmax T2 100 TMF In = 15 ... 50A t [s] 1 10 10 2 x In 10 2 x In Tmax T2 100 In = 60 ... 100A 104 t [s ] 103 10 4 10 3 15 102 10 2 10 10 1 1 60∏100A 10-1 10 -1 40A 50A 35A 30A 25A 20A 15A 10-2 10 -2 10-1 1 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 10 102 x In 10 -1 1 10 10 2 x In 15.141 AC 1000 - 11/03 15 Technical data Trip curves Tmax T2 & T3 ax Tm CBs MC Tmax T2 100 PR221DS-LS, function L-I t [s] 104 Tmax T2 100 PR221DS-I, function I t [s] 0.4-0.44-0.48-0.52-0.56-0.60-0.64-0.680.72-0.76-0.80-0.84-0.88-0.92-0.96-1 L 104 6.5 7 7.5 8 8.5 9 10 1 0.4 1 I 103 1.5 2 2.5 3 3.5 4.5 5.5 103 1.5 B 2 B 2.5 1 3 A A 102 3.5 4.5 102 6.5 7 7.5 8 8.5 9 10 5.5 10 10 102 102 1 1 I 10-1 10-1 10-2 10-2 10-3 10-3 10-1 10-1 10 1 1 x In 10-1 10 1 x In 1 10 Iu [kA] Tmax T2 & T3 100 MCP Magnetic only, adjustable Tmax T2 100 PR221DS-LS, function L-S t [s ] 10-1 10 Iu [kA] t [s] 104 10 4 L 0.4-0.44-0.48-0.52-0.56-0.60-0.64-0.680.72-0.76-0.80-0.84-0.88-0.92-0.96-1 0.4 1 10 3 103 1 1.5 15 B B 10 2 2 2.5 A A 3 3.5 102 4.5 6.5 7 7.5 8 8.5 9 10 5.5 10 S C 10 10 2 B 1 1 10 -1 10-1 10 -2 10-2 6 12 10-3 10 -3 10 -1 15.142 AC 1000 - 11/03 1 10 -1 10 x In 1 10 Iu [kA] 10-1 1 10 102 x In Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 Technical data Trip curves Tmax T3 T MC max CB s Tmax T3 225 TMF In = 60 ... 100A t [s] Tmax T3 225 TMF In = 125 ... 225A t [s] 104 104 103 103 102 102 10 10 1 1 125÷225A 60÷100A 10-1 10-1 10-2 10-2 10-1 1 10 102 x In 10-1 1 10 102 x In 15 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15.143 AC 1000 - 11/03 15 Technical data Temperature performances ax Tm CBs MC Tmax T1 and T1 1P In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C 15 20 25 30 40 50 60 70 80 90 100 18 24 29 35 47 60 71 83 94 106 121 17 22 28 34 45 57 68 79 90 101 114 16 21 27 32 43 53 64 75 85 96 107 15 20 25 30 40 50 60 70 80 90 100 14 19 23 28 37 46 56 65 75 84 92 13 17 22 26 34 42 51 60 69 78 84 In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C 15 20 25 30 35 40 50 60 70 80 90 100 18 24 30 35 40 46 56 71 83 96 109 115 17 23 28 33 39 44 54 68 79 91 103 110 16 21 27 32 37 42 52 64 75 86 97 105 15 20 25 30 35 40 50 60 70 80 90 100 14 18 23 28 33 38 48 56 65 74 83 95 12 17 21 26 31 35 45 51 60 67 75 89 In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C 60 70 80 90 100 125 150 175 200 225 70 82 92 104 117 145 175 205 236 264 67 78 88 100 112 139 167 195 224 251 64 74 84 95 106 132 159 185 213 239 60 70 80 90 100 125 150 175 200 225 56 66 75 85 94 118 141 164 187 211 52 61 71 79 87 110 131 152 172 195 Tmax T2 Tmax T3 15 15.144 AC 1000 - 11/03 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 15 Approximate dimensions T1 & T2 T MC max CB s T1 — 3 pole T1 — Single pole 15 83 78 90 30 70 30 ¯9.38 Y 17 X X 45 181 130 65 53.25 76.2 106.5 T2 — 2 & 3 pole Y >3 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com 103 <2 15.145 AC 1000 - 11/03 15 ax Tm CBs MC Approximate dimensions T3 T3 — 2 & 3 pole Door cut-out for Tmax without faceplate 15 15.146 AC 1000 - 11/03 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com