PC based tap changing system-A case study Rupali Vibhute" ,R.M.Holmukhe2 Mr.P.S. Chaudhari", Mr.T.S.Hasarmani4 1.4post Graduate Student, Electrical Engineering Department, 2Assistant Professor, Electrical Engineering Department, Bharati Vidyapeeth Deemed University, College of Engineering, Pune, India 3Scientist ,DRDO, Pune 2rajeshmholmukhe@hotmail.com Abstract: Tap changers have not changed radically since their invention in the early part of this century. They are slow in operation, typically traversing 19 taps in around 100 seconds and require frequent maintenance. A new TRIAC assisted tap changer is introduced here which addresses the problem of previous schemes. It eliminates excessive conduction losses, which are inherent in solid-state tap changers and at the same time provides a fast response speed by means of fast acting vacuum switches. Calculations show that it will be possible to traverse a 19-tap range in around 0.5s. a unit for a 240 MVA transformer will require minimum maintenance as the vacuum switches used in the selector diverter never or braje more than few amperes. I. INTRODUCTION 1.1 Need oftap changing system The excitation control method is satisfactory only for relatively short lines. However, it is not suitable for long lines as the voltage at the alternator terminals will have to be varied too much in order that the voltage at the far end of the line may be constant. Under such situations, the problem of voltage control can be solved by employing other methods. One important method is to use tap changing transformer and is commonly employed where main transformer is necessary. In this method, numbers of tapping are provided on the secondary of transformer. The voltage drop in the line is supplied by changing the secondary e.m.f. of the transformer through the adjustment of its number of turns. Taps are usually provided on the light voltage winding to enable a fire control of voltage; generally the tap changing is done only when the transformer is in the deenergized state. However in some cases tap changing is also possible when transformer is energized and such transformers are known as tap changing under load or "On load tap changing transformer". 1.2 Types of tap changing transformer 1. Off load tap changing transformer. 2. On load tap changing transformer. 1.2.1 Off load tap changing transformer In this method of tap changing tapping are provided on the secondary. As the position of tap is varied, the effective number of secondary turns is varied and hence the output voltage of the secondary can be changed. When the movable arm makes contact with first stud then secondary voltage is minimum and when it makes contact with last stud the secondary voltage is maximum. During the period of light load, the voltage across the primary is not much below the alternator voltage and the movable arm is placed on first stud. When the load increase the voltage across the primary drops but secondary voltage can be kept at previous value by placing the movable arm on higher stud. Whenever tapping's are to be changed in this type of transformer, the load is kept off and hence the named "Off load tap-changing transformer." Off load designs In low power, low voltage transformer, the point can take the form of a connection terminal, requiring a power lead to be disconnected by had and connected to the new terminal. Alternatively, the process may be assisted by means of rotary or slider switch. Because the different tap points are at different voltages, the two connections should not be made simultaneously, as this short circuit number of turns in the winding and would result in an excessive circulating current. This therefore demands that the power to the load be physically interrupted during the switch over time. Off load tap changing is also employed in high voltage transformer design, though it is only applicable to installations in which loss of supply can be tolerated. 1.2.2 On load tap changing transformer The on load tap changer (OL TC) is used the tapping's connection of the transformer winding while the transformer is energized. The tap changer can be designed as a single unit for a single and three applications with one common neutral point. Depending on the three phase rating, it might require three separate units, each having its own insulated phases. Tap changers can be located either inside the transformer, main tank or outside in its own compartment. Switching from one position to another has to be performed through an impedance can be either resistor or reactor. In supply system tap changing has normally to be performed on load so that there is no interruption to supply. The secondary consist of two equal parallel winding which have similar tapping. Under normal working condition each secondary winding carried one half of total current. This way tapping position is changed without interrupting the supply this method has the following disadvantages. 1. During switching the impedance is increased and there will be a voltage surge. 2. There are twice as many tapping as the voltage steps. A transformer tap is connection point a transformer winding that allows the number of turns to be selected. By this means, a transformer with a variable turn's ratio is produced, enabling voltage regulation of the secondary side. Selection of the tap in use is made via a tap changer mechanism. Voltage considerations Tap points are usually made on the high voltage, or low current, side of the winding in order to minimize the current handling requirements of the contacts. To minimize the number of windings and thus reduce the physical size of a transformer, use may be made of a 'reversing' winding, which is a portion of the main winding able to be connected in its opposite direction and thus oppose the voltage. Insulation requirements place the tap points at the low voltage end of the winding. This is near the star point in a star connected winding. In delta connected windings, the tapping's are usually at the centre of the winding. In an autotransformer, the taps are usually made between the series and common windings, or as a series 'buck-boost' section of the common winding. A mechanical on load tap changer design, changing back and front between tap positions 2 and 3. Because interrupting the supply is usually unacceptable for a power transformer, there are often fitted with a more expensive and compels on load tap changing mechanism. On load tap changers may be generally classified as mechanical, or as electronic, which in turn may be either assisted or solid state. 1.2.3 Mechanical tap changers A mechanical tap changer physically makes the new connection before the old, but avoids the high current from the short-circuited turns by temporarily placing a large diverter resistor (sometimes an inductor) in series with the short -circuited turns before breaking the original connection. This technique overcomes the problems with open or short circuit taps. The changeover nevertheless must be made rapidly to avoid overheating of the diverter. Powerful springs are wound up, usually by a low power motor, and then rapidly released to affect the tap changing operation. To avoid arcing at the contacts, the tap changer is filled with insulating transformer oil. Tapping normally takes place in separate compartment to the main transformer tank to prevent contamination of its oil. One possible design of on-load mechanical tap changer is shown to the right. It commences operation at tap position 2, with load supplied directly via the right hand connection. Diverter resistor A is short circuited; diverter B is unused. In moving to tap 3, the following sequence occurs: 1. Switch 3 closes, an off -load operation. 2. Rotary switch turns, breaking one connection and supplying load current through diverter resistor A. 3. Rotary switch continues to turn, connecting between contacts A and B. Load now supplied via diverter resistors A and B, winding turns bridged via A and B. 4. Rotary switch continues to turn, breaking contact with diverter A. Load now supplied via diverter B alone, winding turns no longer bridged. 5. Rotary switch continues to turn, shorting diverter B. Load now supplied directly via left hand connection. Diverter A is unused. 6. Switch 2 opens, an off load operation. The sequence is then carried out in reserve to return to tap position 2. 1.2.4 Thyristor assisted tap changers Thyristor assisted tap changers use thyristors to take the on load current whilst the main contacts change over from one tap to the next. This prevents arcing on the main contacts and can lead to a longer service life between maintenance activities. The disadvantages is that these tap changers are more complex and require a low voltage power supply for the thyristor circuitry. They also can be more costly. 1.2.5 Solid state (thyristor) tap changers These are relatively recent developments which use thyristors both to switch the load current and to pass the load current in the steady state. Their disadvantage is that all of the non conducting thyristors connected to the unselected taps still dissipate power due to their leakage current. This power can add up to a few kilowatts which has to be removed as heat and leads to a reduction in the overall efficiency of the transformer. They are therefore only employed on smaller power transformers. 1.3 Block diagram: Internal block diagram of the pc based tap changer consist of: 1. Voltage sensing unit 2. Main transformer unit 3. Zero crossing detector 4. Reference and logic generation 5. Relay / Static Switched, isolation ~nd dri.ver 6. Add-on card interface chip decoding logic 7. Pc 8. Load Voltage sensing unit: In this unit a 230 V ac supply is given as input and regulated too 12V supply and it is given to. voltage sensing unit which comprises of two amplifiers I.n differential mode and it is given to reference and logic generation unit and to the main transformer. Main transformer unit: It is most important part of tap changing system. Its rating is 500W but it can withstand lo~d up to.1 KW. Tapping's are provided on the primary side of transformer so that we can get constant voltage irrespective of changes in load. Output of main transformer is given to load. It gets input from voltag.e sensing unit and feedback is given to relay/static switches unit. Zero crossing detectors:ZCD gets input from a main that is 230 V ac supply. It detects the zero point of ac sine wave because at the point both current and voltage is zero (in case of resistive load) Its output is given to the ADDON card. Reference and logic generation:This unit gets input from the voltage sensing unit. It consists of circuitry which generates binary logic as (00, 01, 10, 11). This binary signal is given to the ADDON card, which is then feed to the computer. Relay/Static Switches, isolation and driver:This unit consists of relays and static switches such as TRIAC. TRIAC is a bidirectional device that means it can conduct in both directions. Isolation is provided to reduce the unwanted noise signal. This unit is connected with the tapping of main transformer. This unit is also connected with the ADDON card. ADDON card interface chip decoding logic:ADDON card plays very important role in connecting our hardware with software. It consist of four ic's namely magnitude comparator, buffer, peripheral interface 8~55 ic, AND gate ic. This unit gets signals from zero crossing detector reference and logic generation. It gives signal to the r~lay and static switches. This ADDON card is inserted in the PC. PC:It is any personal computer having ISA slot in it, so th~t we can insert ADDON card in that computer generally It is P1 or P2 pc. Load:- It may be any load bank, from where we can very the load. II. MODELLING AND DEVELOPMENT 2.1 Wiring diagram: . Wiring diagram provides assembly of all of tap c~an~lng system. In our wiring diagram a 230 V ac supply ISgiven to a step down transformer whose secondary rating is .12 V. This secondary voltage is applied to Voltage sensing unit. In Voltage sensing unit the change in Voltage rating depends on tap changer. The Voltaqe sen~ing .u~it provides negative or positive error signal. This u.nlt IS connected to port A of 8255 supply voltage to primary side of load tap changing transformer, tapping are also provided on this side of transformer. Secondary. si~e of load tap changing transformers connected to resistive to resistive load. Lower tap of transformer is connected to NO ~f rel~y land its Pole is connected to NO of relay 3. The higher IS connected to NO of relay 2 with its pole to NO of relay 4. NO of triac 3 is connected to NO of relay of triac 4. The common terminals of two triacs are connected to primary side of current transformer. The main use of triac is that when triac is on secondary is fully loaded at the same time primary ~ide have the minimum opposition to flow of current which decreases amount of current flow at the time of tap changing. •m '" . ......." NO NO VA 0S1 P OSlVB P T_ CHANGING SV-STEM III. SYSTEM ANALYSIS 3.1 Digital input - output ADDON card:As we are aware that PC has a motherboard on which the main CPU and the RAM/ROM memory chips are located. All other functionalities like disk controllers, parallel and series ports and the display adapter are located on the ADDON cards which plug into the expansion slots on the motherboard. This general purpose ADDON card is useful in many applications like EPROM programmer and copier, process controller, logic monitor etc. It consists of four ics namely: 1. 74HCT08 Quad 2 - input AND gate 2. 74HCT688 Magnitude comparator 3. 74HCT245 8-bit bidirectional bus driver 4. 8255A programmable peripheral interface. For designing this card we need a PCB edge connector with 62 pins which are arranged as two rows of 31 pins on each side of expansion slot, named side A and side B. The circuit is based on IC8255 which is a programmable digital I/O (input/output) device with three external 8-bit ports. That means we get 24 general purpose input and / or output pins. As shown in the circuit diagram A 1 to A8 bits of the IC3 are connected with the 07 to DO bits of the A side of PCB edge connector pin no. 20 is connected to VCC and pin no. 10 to ground. Chip select of IC2, IC3 and IC4 is connected together. B1 to B8 bits of IC3 are given to 07 to DO bit of IC4. Two AND gates are used (N1, N2) and connected to the IC2. IC2 (74HCT688) is an 8 bit magnitude comparator. The address bus lines A2 through A9 are monitored by it, and compared with the address set by the resistor and the DIP switches on the of IC2. The AEN signal is also invovled in the address selection as can seen from connection to pin no 12 of IC2. This is done in order to disable our circuit during DMA operations. When the two address (the one on the address bus of IBM pc as extended to left side of IC2 and the other set with the help of Dip switches on the right hand side of IC2) match, IC2 issues an active low chip select signal to IC3 and IC4. Here was we have specified an address of 300 hex which is a vacant slot on the IBM pc. This address has been reserved by IBM for experimental work. If you want to change this address be sure that no other device with the intended address exists on the pc, to avoid clash . The bi-directional bus transceiver IC3 (74HCLT245) connects the data bus of PC to the data lines of IC4 (8255A). The direction in which data is transmitted is determined by the DIR pin no. 1 of the transceiver IC3. This pin is controlled by active low READ signal. This ensures proper direction data flow. IC4 8255A is versatile clip which can be programmed in three modes. Mode 0 is a basic input - output mode. Mode 1 and 2 involve advanced I/O operations. The clip has three 8-bit ports named A,B and C and a control port (internal) which determine how the clip is programmed. The two pins marked AO and A 1 (pin 9 and 8 respectively) determine which of these four ports are accessed. This is why the two least significant address bits of the Pc bus are directly connected to these pins. With our address assignment of 300 (hex) as base address, the addresses of these 4 ports will be given below: Address (hex) 300 301 302 303 Port accessed portA port B port C control The three 8-bit ports A, Band C together with +5V and ground connection are brought out on a 26-pin FRC type male connector for external use. Incidentally, this circuit does not need an external power supply. A positive 5 Volt supply is readily available on pins B3 and B29 of the 62-pin PC edge connectors itself. This is to be connected to the Vcc pins of all the four ICs. Similarly the ground pins of all four ICs are tied to the common ground point of the PC edge connector (B1, B10, B31). ADD ON CARD , ! : i ADDON CARD (8255) 3.2 8255: The 8255 Programmable Interface (PPI) is a very popular and versatile input/output chip that is easily configured to function in several different configurations. The 8255 is used on several of our range of cards that plug into an available slot in your IBM PC. This clip allows you to do both digital input and output (010) with your PC. For example, you may want to have your PC turn on a switch, or have a switch electronically activate your PC to execute a program. Each 8255 has 3 off 8 bit TTL compatible I/O ports which will allows the control of up to 24 individual outputs or to read 24 individual inputs, or indeed a mixture of both input or output. For example, you could attach this to a robotic device to control movement by use of motors to control motion and switches to detect position etc. _{_.IN ----+ af..Ptl'UO CJHO ..."" Ci--~ Our range of cards plug into any available 8 or 16 - bit slot (also known as an AT or ISA slot) on your PC's motherboard, just like a sound card or disk drive controller card does. Your CPU (Central Processing Unit) communicates with cards by knowing the card's address and sending data to it. By physically using jumpers on the card, we can assign a set of addresses to the card, then in software, we can tell the CPU what these addresses are (more about this in the Programming Section). Table 2: DC-0600 Address Option I: default Option (JP2 Open) (JP2 Linked) 8255 Port Address (Hex Dee) Address (Hex dee) Port l A 300 H (768) 360 H (864) Port IB 301 H (769) 361 H (865) Port l C 302 H (770) 362 H (866) Port I Control 303 H (771) 363 H (867) Reg. Port 2A 304 H (772) 364 H (868) Port 2B 305 H (773) 365 H (869) Port 2C 306 H (774) 366 H (870) Port 2 Control 307 H (775) 367 H (871) Reg. 3.2.1 8255 Configuration The first thing that must be done, before the chip can be used, is to tell it which configuration is required. The configuration tells the 8255 whether ports are input or output and even some strange arrangements called bidirectional and strobed, but these 'funny' modges go a little beyond the scope of this tutorial. The 8255 allows for three distinct operating modes (Modes 0, 1 and 2) as follows: • Mode 0: Ports A and B operate as either inputs or outputs and Port C is divided into two 4-bit groups either of which can be operated as inputs or outputs. • Mode 1: Same as Mode 0 but Port C is used for handshaking and control • Mode 2: Port A is bidirectional (both input and output) and port C is used for handshaking. Port B is not used. For most applications using this range of cards Mode 0 will be used. Each of the 3 ports has 8 bits, each of these bits can be individually set on or off, its a bit like having 3 banks of 8 light switches. These bits are configured in groups to be inputs or outputs allowing their function to either read data into the computer or control data out of the computer. The various modes can be set by sending a value to the control port. The control port is Base Address + 3 (i.e. 768 + 3 = 771 Decimal). The table below shows the different arrangements that can be configured and the values to be sent to the configuration port. Table 3 : 8255 Control Re Control Word (Hex(Dee) 80H (128) 82H(l30) 85H(133) 87H(l35) 88H(l36) 8AH(138) 8CH(l40) 8FH(l43) ister Conti uration (Mode 0:) Port A Port B Port C OUT OUT OUT OUT IN IN IN IN OUT IN OUT IN OUT IN OUT IN OUT OUT IN IN OUT OUT IN IN As mentioned the control port is Base Address + 3. Port A is always at Base Address; Port B is Base Address + 1; Port C is Base Address +2. Thus in our example Ports A, Band C are at 768, 769 and 770 (Decimal) respectively. By writing say, 128 to the Control port will then configure the 8255 to have all three Port set for output. This can be done using Quick Basic's OUT Statement, for example: 3.3 Buffer: This class of amplifier is designed to follow low level stages; one example is a crystal oscillator. An oscillator for optimum performance can NOT be loaded down, it needs an intermediate stage following. This will then present a sufficiently high enough input impedance so it is not considered a significant load to the oscillator. The intermediate or buffer stage, while not representing a load must then have a sufficiently low output impedance to drive successive stage. If these concepts of impedance confuse or worry you then look at my other page it's a rough and ready explanation, followed by a more technical explanation of impedance matching but hopeful you will come back with a considerably better understanding. From what I said above, two described traits of a buffer amplifier are high input impedance and low output impedance. Obliviously succeeding stages should also be linear because we don't want to introduce distortion. As a matter of interest a buffer amplifier is not solely limited to following an oscillator. You could have a requirement of wanting to sample the output of the first mixer for what is called a "Pandaptor", a means of visually seeing adjacent signals on an oscilloscope. Also a high quality agc system should be derived from the last Lf. stage, it should be buffered before going to the agc amplifier and then on to the agc detector. Other examples are low level outputs of audio amplifier stages such as microphone inputs where the microphone is a high impedance type/ Although not so common now, phono inputs to audio am pliers alsc needed buffering. IV. ADVANTAGES Advantage of pc based tap changing transformer. 1. These are easily checked and reset by the operator from the front panel or through digital communication. 2. Contractor life is more due to absence of resister type OL TC. 3. Voltage Fluctuation is minimum during a tap change. 4. Low operating temperature. 5. True "current zero crossing" switches. 6. High over load capacity 7. Operation and coordinated control of fixed and variable speed wind. 8. This technology is accurate and very efficient. 9. On the following phase current zero relay A is turned on and relay C is turned off. 10. It eliminates excessive conduction losses. 11. In this design scheme inter tap circulating current does not flow not during a tap change thus it is possible to make multiple tap. 12. An approximate solution to lower tap changing or capacitor times in reactive power control in distribution system. 13. Voltage control integrated in distribution management system. 14. Tap changing transformer role in voltage stability. 15. Avoiding sustained oscillation in power system with tap changing transformer. 16. Combined use of tap changing transformer and static VAR compensation for enhancement of steady state voltage stability. 17. Voltage regulations via automatic load tap changing transformer evolution of voltage stability condition. 18. A mixed integer program for optimal static capacitor system. 19. Highest winding current and highest, winding temperature can also read through the digital and analog output. 20. To control the timing of relay operation, each enhanced alarm includes settable pickup and dropout delay This feature reduces momentary equipment activation or false alarm due to transient conduction. 21. The relay as operated sensor on fault condition. 22. The software is written in C and is designed for PC use, the advantage of using Care • Direct Oil Temperature • Simulated Winding Temperature • Calculated Winding Temperature(CT Models) • LTC Temperature Difference (LTC Models) • Single, Dual and Three RTD Units • Multi-Stage Fan/Pump Control • Analog and Digital Inputs • Weatherproof NEMA4X Metal Case • SCADA Ready - Analog, Digital, DNP3 V. DISADVANTAGES Disadvantage of pc base tap changing transformer: 1. Increased computerization of the Substation costs. 2. Pc base limitation which signals analog or digital 3. A disadvantage of the binary coded method is section describes a populated diversity. 4. Voltage control simulated annealing that it Borland c+= and implemented on pc Pentium computer. 5. Normally does not provided isolation has moving part. 6. Normally do not provide short circuit protection slower response time 7. rr ~ It is slower produces arching each time the tap setting is changed and need regular maintenance. 8. A pc based man machine interface work station was installed There are large space required. 9. In spite of the operating the inductance to observe the change in voltage during transient the we can use a steady the analysis based on the system. 10. The software is written in C is designed for pc use calculation method. 11. High capital cost. VI. COMPARISON BETWEEN RESISTIVE TYPE ONLOAD TAP CHANGER AND NEW PC BASED TAP CHANGER Resistor type OLTC PC Based OL TC 1) Mechanical operated Here mechanical operated mechanism is required to mechanism is not required change taps many time to change taps. Taps get such system may fail changed automatically with help of programmed in computer. 2) It uses solid state Here fast acting switches switches therefore fast are used due to which a response speed cannot be fast response speed is obtained. obtained. 3) It has excessive It eliminates excessive conduction losses conduction losses 4) They are slow in They are fast in operation. operation 5) here frequent In this there is no need of maintenance is required frequent maintenance 6) In this solid state There is no need as swithes are permanently protection as solid state connected in a circuit they switches are not used. require protection from high voltage surges. 7) In this full scale tap In this full scale tap changing can not be changing is obtained obtained 8) Here sparking may take Here sparking does not place at time of tap take place at time of tap chanqinq changing 9) Here deterioration as Here contactor has long contact take place life as there is no detritions therefore contactor life is to contact less CONCLUSION The operating of new scheme has been shown to work and tap changer combination. The tap changer has a fast response speed. Since the inter tap circulating current is small, so multiple tap change are feasible. A pc base operated mechanism is required to change the taps many times such system more accurate as compare to mechanical operated. On the following phase current zero relay A is turned on and relay C is off. So to minimize switching losses. It eliminates excessive conduction losses. In this way, loss of transformer due to tap changer failure will be avoided A patent is pending upon the techniques out lined above. Additional analogI digital inputs are available on the enchanted version of any transformer advantage these inputs handle AC or DC from 5 to 300 V. REFERENCES 1) http://en.wikipedia.org 2) "Electronics for you" January 99 edition 3) IEEE paper presented by R. Shuttle worth, X. Tian, C. Fan, A. Power on New tap changing Scheme. 4) Paper published by Douglas M. Getson on "On load tap changer"