Type T19.10 Analog Temperature Transmitter

advertisement
Type T19.10 Analog Temperature Transmitter
Standard Features



Input: PT 100 OR thermocouples
Configurable Co Ranges Using Solder Pads
Output: 4 …20 mA, 2 wire design
RTD or Thermocouple
Programmable Ranges
Economical
Fault Signal: For sensor burnout and sensor short circuiting
Temperature Range: Large ambient temperature range
Size: Compact
Guarantee: 5 years
Type T19.10
Analog Temperature Transmitter
Datasheet: T19.01
Ready-To-Ship Temperature Transmitters
Description
Part #
Type
Pt100 Small Range3656471
Pt100 Large Range
3656609
Price
$120.00
Type T19.30 Analog Temperature Transmitter
Standard Features
Input: PT 100 OR thermocouples
Configurable Co Ranges
Output: 4 …20 mA, 2 wire design
 RTD or Thermocouple
 Programmable Ranges
 DIN Rail Mount
Fault Signal: For sensor burnout and sensor short circuiting
Temperature Range: Large ambient temperature range
Size: Compact
Guarantee: 5 years
Datasheet T19.30
Type T19.30
Analog Temperature Transmitter
Ready-To-Ship Temperature Transmitters
Type
Description
Part #
Pt100 Small Range7827912 Pt100 Large Range
7889178
Price
$148.00
For pricing info, call 1-888-WIKA-USA or visit www.wika.com
Type T24.10 Temperature Transmitter
Standard Features
Configurable with Windows PC without sensor simulation,
remote configuration also possible from the control room via
the current loop



Analog signal processing, ideal for multiplex-systems
RTD Only
Programmable
Potted Electronics
For Pt 100 and resistance-sensors, 3 wire
Analog output 4 … 20 mA, 2 wire design
EMC Conformity per EN 61 326 and NAMUR NE 21
Sensor burnout monitoring in accordance with NAMUR NE 43
Compact design suitable for any DIN connection head of form B
Ready-To-Ship Temperature Transmitters
Type
Standard
Description
Part #
Price
4363048
$210.00
Type T24.10
Temperature Transmitters
Datasheet: T24.10
Type T53.10 Fieldbus Temperature Transmitter
Standard Features
 Field bus protocol PROFIBUS PA
& Foundation Fiedbus
 Configurable for connection to RTDs, Thermocouples,
Resistance - sensor, mV - sensor
 Foundation Fieldbus
 PROFIBUS® Transmitter
 Programmable
 Digital Temperature Transmitter
 Dual sensor capable
 Class protection, intrinsically safe per FISCO-Model
II 1 G EEx ia ll B / II C T4 / T5 / T6
II 2 G EEx ib ll B / II C T4 / T5 / T6
 EMC Directive 89/336/EWG, DIN EN 61 326:2002,
NAMUR NE 21
 Isolation voltage AC 1500 V between sensor and bus
Type T53.10
Fieldbus Temperature Transmitter
 95% Rh protection
 Terminal connections with captive screws
Data sheet: T-53.10
Ready-To-Ship Temperature Transmitters
Type
Standard
Description
Part #
42512236
For pricing info, call 1-888-WIKA-USA or visit www.wika.com
Price
$690.00
Type T12.10 Digital Temperature Transmitter
Standard Features
Inputs: Refer to table
Accuracy: RTD: (Per DIN IEC 770, 23°C ±5°C) ±0.2 °C or 0.1°C + 0.05% of valve; Thermocouple: (Per DIN IEC 770, 23°C ±5°C) 0.5°C or 10uV or 0.05% of value
 Digital Temperature Transmitter
 Programmable
 CE Certified
Thermocouple Break Protection: Program-
mable, Upscale (23 mA) or Downscale (3.8 mA)
Cold Junction Compensation: Programmable internal or external (Pt 100), Accuracy ±1.0°C
RTD Wiring Configuration: 2, 3, or 4 wire
Response Time: Programmable 1 to 60 seconds. Measurement Update Time 2/second
Type T12.10
Maximum Lead Wire Resistance: Thermocouple: 500 Ohm; RTD: 10 Ohm per lead
Output: 4-20 mA
Maximum Output Load: RMAX < (VS - 9v) / 0.021 A
Load Effect: < 0.01% of span/100 Ohm
Power Supply: 9 to 36 Vdc
Power Supply Effect: < 0.005% of span/V
Isolation: 1500 Vac, 60 s
Environmental: Operating Temperature: -40 to 185°F (-40 to 85°C ); Optional Operating Temperature: -40 to 220°F (-40 to 105°C), -58 to 185°F(-50 to 85°C); Humidity: 100% non- condensing Vibration: 10 Hz to 2 KHz, 5 g per DIN IEC 68 2-6; Warm-up time: 5 minutes
Construction: Case Material: Plastic; Dimensions: 1.95" dia. (49.5 mm ), 1.12" ht.
(28.5 mm); Weight: 2.47 oz (0.07 kg.)
Warranty: 5 years
T-12 Programmable Inputs and Ranges
Input
Sensor Standard
Range °C
Range °F
Min. Span
J
IEC 584
-100 to 1200 -148 to 2192 50 K
K
IEC 584
-180 to 1372 -292 to 2500 50 K
N
IEC 584
-180 to 1300 -292 to 2372 100 K
T
IEC 584
-200 to 400 -328 to 752
50 K
E
IEC 584
-100 to 1000 -148 to 1832 50 K
Thermocouple L
DIN 43710 -100 to 900 -148 to 1652 50 K
U
DIN 43710 -180 to 600 -292 to 1112 75 K
R
IEC 584
-50 to 1760 -58 to 3200
200 K
S
IEC 584
-50 to 1760 -58 to 3200
200 K
B
IEC 584
400 to 1820 752 to 3308 200 K
W3
ASTM E988 0 to 2300
32 to 4172
200 K
W5
ASTM E988 0 to 2300
32 to 4172
200 K
RTD
Pt 100 Pt 100
-200 to 850 -328 to 1562 25 K
Ni 100 Ni 100
-60 to 250
-76 to 482
25 K
Linear 0 to 5K Ohm
30 Ohm
Resistance
DC Voltage
-10 to 800 mV
5 mV
(Unipolar)
Ready-To-Ship Temperature Transmitters
Type
Standard
Rail Adapter
Configuration Set
Description
Part #
3616933
3593789
11606304
Price
$290.00
$21.35
$264.30
Datasheet: T12.10
For pricing info, call 1-888-WIKA-USA or visit www.wika.com
Type T12.30 Digital Temperature Transmitter
 Digital Temperature Transmitter
 Programmable
 DIN Rail
Standard Features
Inputs: Refer to table
Accuracy: RTD: (Per DIN IEC 770, 23°C ±5°C) ±0.2 °C or 0.025%FS + 0.1;Thermocouple: (Per DIN IEC 770, 23°C ±5°C) ±0.5 or 0.05%FS or ± 10µv Thermocouple Break Protection: Programmable, Upscale (23 mA) or Downscale (3.8 mA)
Cold Junction Compensation: Programmable internal or external (Pt 100), Accuracy ±1.0°C
RTD Wiring Configuration: 2, 3, or 4 wire
Response Time: Programmable 1 to 60 seconds
Measurement Update Time: 2/second
Maximum Lead Wire Resistance: Thermocouple: 500 Ohm; RTD: 10 Ohm per lead
Type T12.30
Output: 4-20 mA
Maximum Output Load: RMAX < (VS - 9v) / 0.021 A
Load Effect: < 0.01% of span/100 Ohm
Power Supply: 9 to 36 Vdc
Power Supply Effect: < 0.005% of span/V
Isolation: 1500 Vac, 60 s
Environmental: T12.30 Operating Temperature:
-14 to 158°F (-25 to 70ºC); Humidity: 100% non-
condensing; Vibration: 10 Hz to 2 KHz, 5 g per DIN IEC 68 2-6; Warm-up time: 5 minutes
Construction: Case Material: Plastic; Weight: T12.10: 2.4oz (0.07kg); T12.30: 7oz (0.2kg)
Warranty: 5 years
T-12 Programmable Inputs and Ranges
Input
Sensor Standard
Range °C
Range °F
Min. Span
J
IEC 584
-100 to 1200 -148 to 2192 50 K
K
IEC 584
-180 to 1372 -292 to 2500 50 K
N
IEC 584
-180 to 1300 -292 to 2372 100 K
T
IEC 584
-200 to 400 -328 to 752
50 K
E
IEC 584
-100 to 1000 -148 to 1832 50 K
Thermocouple L
DIN 43710 -100 to 900 -148 to 1652 50 K
U
DIN 43710 -180 to 600 -292 to 1112 75 K
R
IEC 584
-50 to 1760 -58 to 3200
200 K
S
IEC 584
-50 to 1760 -58 to 3200
200 K
B
IEC 584
400 to 1820 752 to 3308 200 K
W3
ASTM E988 0 to 2300
32 to 4172
200 K
W5
ASTM E988 0 to 2300
32 to 4172
200 K
RTD
Pt 100 Pt 100
-200 to 850 -328 to 1562 25 K
Ni 100 Ni 100
-60 to 250
-76 to 482
25 K
Linear 0 to 5K Ohm
30 Ohm
Resistance
DC Voltage
-10 to 800 mV
5 mV
(Unipolar)
Ready-To-Ship Temperature Transmitters
Type
Standard
Configuration Set
Description
Part #
3625321
11606304
Datasheet: T12.30
For pricing info, call 1-888-WIKA-USA or visit www.wika.com
Price
$392.00
$264.30
Type T32.1S/T32.3S
Digital Temperature Transmitter with Hart® protocol
 Digital Temperature Transmitter
 Programmable
 HART® Communicator
Standard Features
Output: 4-20 mA
Inputs: Refer to table
TÜV certified SIL version for protective equipment
Type T32.1S
 Universal connection for one or two sensors
Sensor drift detection allows an error signal to be sent if deviation between sensor 1 and sensor 2 exceeds user selectable value
Type T32.3S
Sensor break detection in accordance to
NAMUR NE89
Isolation: voltage AC 12--V between server and current loop
Warranty: 5 years
Ready-To-Ship Temperature Transmitters
Type
T32.1S - Standard
T32.3S - Standard
Description
Part #
12655423
12655458
Datasheet: T32.1S & T32.3S
For pricing info, call 1-888-WIKA-USA or visit www.wika.com
Price
$440.00
$555.00
Type T32.1S/T32.3S
Digital Temperature Transmitter with Hart® protocol
Temperature transmitter input
Resistance sensor
Pt100
Pt(x)
4)
JPt100
10 ... 1000
Ni100
Resistance sensor
max. configurable
measuring range 1)
-200...+850 °C
Standard
α values
IEC 60751: 2008 α = 0.00385
-200...+850 °C
IEC 60751: 2008
-60...+250 °C
DIN 43760: 1987 α = 0.00618
-200...+500 °C
0...8,370 Ω
JIS C1606: 1989
Minimum measuring
span 14)
10 K or 3.8 Ω
whichever is
greater
α = 0.00385
α = 0.003916
4Ω
0... 100 %
Sensor current at the measurement
max. 0.3 mA (Pt100)
Max. wire resistance
50 Ω each wire, 3-/4-wire
Potentiometer
9)
10 %
Type J (Fe-CuNi)
Type K (NiCr-Ni)
Type L (Fe-CuNi)
Type E (NiCr-Cu)
max. configurable
measuring range 1)
Standard
-270... +1,372 °C
IEC 60584-1: 1995
-210... +1,200 °C
IEC 60584-1: 1995
-200... +900 °C
DIN 43760: 1987
-270... +1,000 °C
Type N (NiCrSi-NiSi) -270... +1,300 °C
Type T (Cu-CuNi)
-270... +400 °C
Type R (PtRh-Pt)
-50... +1,768 °C
Type U (Cu-CuNi)
Type S (PtRh-Pt)
Type B (PtRh-Pt)
mV sensor
Connection type
-200... +600 °C
Minimum measuring
span 14)
50 K or 2 mV
whichever is greater
IEC 60584-1: 1995
IEC 60584-1: 1995
IEC 60584-1: 1995
DIN 43710: 1985
0... +1,820 °C 15) IEC 60584-1: 1995
200 K
IEC 60584-1: 1995
- 500...+1,800 mV
Cold junction compensation, configurable
1)
2)
≤ ±0.12 °C
≤ ±0.0094 °C 6) 7)
≤ ±0.12 °C
≤ ±0.12 °C
5)
≤ ±1.68 Ω
≤ 0.50 %
5)
8)
10)
≤ ±0.0094 °C 6) 7)
≤ ±0.0094 °C 6) 7)
≤ ±0.1584 Ω 8)
≤ ±0.0100 % 10)
Typical measuring Temperature coefficient
deviation 2)
per °C typical 3)
≤ ±0.91 °C 11)
≤ ±0.0217 °C 7) 11)
≤ ±0.91 °C 11)
≤ ±0.0203 °C 7) 11)
≤ ±0.91 °C 11)
≤ ±1.02 °C 11)
≤ ±0.92 °C 11)
150 K
Max. wire resistance
≤ ±0.0094 °C 6) 7)
5)
≤ ±0.98 °C 11)
IEC 60584-1: 1995
-50... +1,768 °C
≤ ±0.12 °C 5)
1 sensor 2- /4- /3-wire or 2 sensors 2-wire
(for further information, please refer to designation of terminal connections)
Connection type
Thermocouple
Typical measuring Temperature coefficient
deviation 2)
per °C typical 3)
150 K
4 mV
≤ ±0.92 °C 11)
≤ ±1.66 °C 11)
≤ ±1.66 °C 11)
≤ ±1.73 °C 12)
≤ ±0.33 mV 13)
≤ ±0.0238 °C 7) 11)
≤ ±0.0224 °C 7) 11)
≤ ±0.0238 °C 7) 11)
≤ ±0.0191 °C 7) 11)
≤ ±0.0191 °C 7) 11)
≤ ±0.0338 °C 7) 11)
≤ ±0.0338 °C 7) 11)
≤ ±0.0500 °C 7) 12)
≤ ±0.0311 mV 7) 13)
1 sensor or 2 sensors
(for further information, please refer to "designation of terminal connections")
5 kΩ each wire
internal compensation or external with Pt100, with thermostat or off
Other units e. g. °F and K possible
Measuring deviation (input + output) at ambient temperature 23 °C ±3 K, without
influence of lead resistance; example calculation see page 4
3) Temperature coefficient (input + output) per °C
4) x configurable between 10 … 1,000
5) Based on 3-wire Pt100, Ni100, 150 °C MV
6) Based on 150 °C MV
7) In ambient temperature range -40 … +85 °C
8) Based on a sensor with max. 5 kΩ
9) Rtotal: 10 ... 100 kΩ
10) Based on a potentiometer value of 50 %
11)
12)
13)
14)
Based on 400 °C MV with cold junction compensation error
Based on 1000 °C MV with cold junction compensation error
Based on measuring range 0 ... 1 V, 400 mV MV
The transmitter can be configured below these limits but not recommended due to loss
of accuracy.
15) Specification valid only for measuring range between 450 ... 1,820 °C
bold: basic configuration
italic: This sensors are not allowed at option SIL (T32.xS.xxx-S)
MV = Measuring value (temperature measuring values in °C)
Datasheet: T32.1S & T32.3S
For pricing info, call 1-888-WIKA-USA or visit www.wika.com
Download