BU4.2:CL6821 December 1995 PROVOXr Process Management Systems Analog I/O Interface with CL6800-Series Cards, Termination Panels, and Modules CL6800-Series Analog I/O instruments are members of the PROVOXr Control I/O family. They interface analog field devices to SR90 and SRx Controllers in PROVOX Process Management Systems. The instruments consist of input and output cards, input modules, termination panels, and cable interface panels. SR90 or SRx Controller The cards convert analog signals between the signal format used by SR90 and SRx Controllers and the analog signals of the field devices. An analog input and output card provides either input or output signal conversion, while an analog input-only card provides cost-effective input-only conversion for control systems which use many more analog inputs than outputs. The selection of input termination panels lets you choose between single-ended or isolated analog input signals and between simplex and redundant applications. Output termination panels let you choose between simplex and redundant outputs. For isolated signals, a complete family of input modules plug into input termination panels to interface a wide selection of high-level, low-level, thermocouple, and RTD signals to match your analog input requirements. Smart I/O Interface D001233X072 For information about smart device (HART Compatible) I/O interface and available smart I/O cards, termination panels, and modules, see product bulletin, BU4.2:CL6825. Analog Card ÇÇ ÇÇ Termination Panel Analog Field Devices Interface Between Analog Field Devices and an SR90 or SRx Controller BU4.2:CL6821 December 1995 Page 2 Analog I/O Instruments Analog I/O Applications The following instruments make up the CL6800-Series for analog I/O interface: The termination panels and modules can be mixed and matched to meet your I/O application. See the Analog I/O Applications table for available combinations. Input and Output Cards Type CL6821 Analog Input/Output (I/O) Card Type CL6824 Analog Input Card Cable Interface Panels Type CL6841 Analog Input Cable Interface Panel Type CL6842 Analog Output Cable Interface Panel Input Termination Panels Type CL6895 Single-Ended Analog/Smart Device Input Termination Panel Type CL6896 Redundant Single-Ended Analog/Smart Device Input Termination Panel Type CL6897 Analog Input Termination Panel Type CL6898 Redundant Analog Input Termination Panel Output Termination Panels Type CL6885 Analog/Smart Device Output Termination Panel Type CL6886 Redundant Analog/Smart Device Output Termination Panel The first combination for high-level inputs lets you accept analog input signals from either traditional analog devices or smart devices. This combination gives you flexibility if you are transitioning your plant to smart device capability. You can install your smart field transmitters and use their analog signals now and later use their full communications capability when you complete your control system upgrade. The second and third combinations for high-level inputs let you select the appropriate ground system, depending on whether the analog transmitter is isolated or non-isolated. Other combinations allow you to use millivolt inputs, RTD inputs, and thermocouple inputs. With the output selection, you can send output signals to either transitional analog or smart final control elements. If you are planning a plant upgrade to smart final control elements, you can operate your smart elements now and later use their full capability when you complete your system upgrade. Configuration The analog interface is configured by ENVOX or PROFLEX Configuration Software, or by the microPROVOXt System. Each channel is configured individually for versatile setup to your system needs. Calibration Input Modules Type CL6855 High-Level Isolated and High-Level Non-Isolated Analog Input Modules Type CL6856 Millivolt Analog Input Module Type CL6857 RTD Input Modules Type CL6858 Thermocouple Input Modules Type CL6859 Analog/Smart Device Input Modules The analog I/O card and the analog input card have self-contained digital calibration capability. Cards are shipped properly calibrated so that you need only configure them to your system requirements. Factory calibration data is stored in non-volatile memory in each card and the card automatically maintains calibration in normal operating environments. When the cards are operated at or near their environmental limits, they may require periodic calibration using the Type CL6891 Analog I/O Calibration Adapter. BU4.2:CL6821 December 1995 Page 3 Analog I/O Applications I/O Conversion I/O System Termination Panel Module G High-level Input for either Traditional Analog or Smart Device inputs G Single-ended ground (1) Simplex Type CL6895 Single-ended Analog/Smart Device Input Termination Panel Redundant Type CL6896 Redundant Single-ended Analog/Smart Device Input Termination Panel Type CL6859 Analog/Smart Device Input Module (select analog input version). One module per pair of channels.(3) G High-Level Input G Non-isolated transmitter G Isolated ground (2) Simplex Type CL6897 Analog Input Termination Panel Redundant Type CL6898 Redundant Analog Input Termination Panel G High-Level Input G Isolated, Self-powered transmitter G Single-ended ground (1) Simplex Type CL6897 Analog Input Termination Panel Redundant Type CL6898 Redundant Analog Input Termination Panel G Millivolt Input G Isolated ground (2) Simplex Type CL6897 Analog Input Termination Panel Redundant Type CL6898 Redundant Analog Input Termination Panel Simplex Type CL6897 Analog Input Termination Panel Redundant Type CL6898 Redundant Analog Input Termination Panel Simplex Type CL6897 Analog Input Termination Panel Redundant Type CL6898 Redundant Analog Input Termination Panel Simplex Type CL6885 Analog/Smart Device Output Termination Panel Redundant Type CL6886 Redundant Analog/Smart Device Output Termination Panel G RTD Input G Thermocouple Input G Single-ended ground (1) G High-level output for either conventional analog device or smart device G Single-ended ground (1) Type CL6855 High-level Analog Input Module (Select isolated version). One module per channel. Type CL6855 High-level Analog Input Module (Select non-isolated version). One module per channel. Type CL6856 Low-level Isolated Analog Input Module. One module per channel. Type CL6857 RTD Input Module (select desired temperature range). One module per channel, non-isolated.(4) Type CL6858 Thermocouple Input Module (select desired temperature range and dielectric strength rating (5)). One module per channel. No modules required 1. Single-ended ground means that a field device ground is not isolated from the PROVOX system ground 2. Isolated ground means that a field device ground is isolated from the PROVOX system ground 3. The Type CL6859 module sets the Type CL6895 or CL6896 termination panel to the I/O card. You may use the 4 to 20 mA dc signal from either traditional analog or smart field devices, but select the analog version of the Type CL68759 module to match the termination panel to the Type CL6821 or CL6824 card. 4. The module does not provide isolation. If isolation is required, consult your Fisher-Rosemount representative or sales office. 5. Dielectric strength rating is measured between field wiring inputs and PROVOX system ground Intrinsic Safety Applications Analog I/O products may be used in intrinsic safety applications. CL6340-Series termination panels and CL6350-Series intrinsic safety barriers interface field devices in hazardous locations to a PROVOX system. These panels and barriers replace the standard analog I/O termination panels and modules; they are not in addition, so you can save on the number of cabinets required for your I/O system. See product bulletin, CL6349-Series Termination Panels and CL6350-Series Intrinsic Safety Barriers, BU4.2:CL6340, for a detailed description. BU4.2:CL6821 December 1995 Page 4 Termination Panel Interchange Previous Design Termination Panel Rack Units Type CL6861 Single-Ended Analog Input Termination Panel 3 Type CL6895 Single-Ended Analog/Smart Device Input Termination Panel. (Requires a Type CL6859 Analog/Smart Device Input Module for each channel pair used.) 3 Type CL6862 Redundant Single-Ended Analog Input Termination Panel 4 Type CL6896 Redundant Single-Ended Analog/Smart Device Input Termination Panel. (Requires a Type CL6859 Analog/Smart Device Input Module for each channel pair used.) 3 Type CL6863 Isolated Analog Input Termination Panel 4 Type CL6897 Analog Input Termination Panel 3 Type CL6864 Redundant Isolated Analog Input Termination Panel 5 Type CL6898 Redundant Analog Input Termination Panel 3 Type CL6871 Analog Output Termination Panel 2 Type CL6885 Analog/Smart Device Output Termination Panel 2 Type CL6872 Redundant Analog Output Termination Panel 3 Type CL6886 Redundant Analog/Smart Device Output Termination Panel 2 1. Current Design Termination Panel Rack Units Previous design termination panels are no longer available as a normal order item; they are listed for cabinet sizing purposes to show rack unit comparison between the previous design and the currently available replacement design. You may also use the intrinsic safety products of other manufacturers. These products may add impedance to the 4 to 20 mA current loop which must be taken into account. A typical additional impedance is 180 ohms. To help minimize your system costs, you may be able to use one-for-N backup. In this type of backup, one backup card can support up to eight primary cards. The backup card need not be located in the same file as the primary card. Backup combinations are available, as follows: Termination Panel Interchange On-going termination panel enhancements provide more space-efficient mounting. Many of the currently available termination panels have less height than previous designs and can be used as replacements for the previous designs. See the Termination Panel Interchange table above for replacement sizing information. Electrical isolation methods may vary between termination panels, so compare the electrical ground information provided in the Analog I/O Applications table with your field device ground requirements. Redundancy You can choose one-for-one (1:1) or one-for-N (1:N) backup to meet your process requirements. One-for-one backup requires two analog interface cards, two I/O buses, two multi-pair cables, and one redundant termination panel. An analog I/O card configured for input can be backed up by a similarly configured analog I/O card or analog input card. An analog input card can be backed by an analog I/O card configured for input or another analog input card. An analog I/O card configured for output is backed up by a similarly configured analog I/O card. If a primary card failure is detected and input or output data is not corrupted when inputs are reported or outputs are driven, both input and output values are held at their last values. Switchover is bumpless for outputs. Switchover for input is delayed to allow input filters to stabilize for smooth transitions. Normal input reporting and output driving continues after the switchover is complete. If the failure is detected and the data is corrupted when inputs are reported or outputs are driven, a bump of inputs or outputs at switchover may occur. BU4.2:CL6821 December 1995 Page 5 Primary PROVOXr Highway I/O Cards SR90 or SRx Controller I/O Card File Secondary PROVOX Highway I/O Card to Termination Panel Cables Primary I/O Bus Termination Panel Secondary I/O Bus Termination Panel Simplex Configuration Primary PROVOXr Highway Primary I/O Cards Secondary I/O Cards SR90 or SRx Controller I/O Card File Secondary PROVOX Highway I/O Card to Termination Panel Cables Primary I/O Bus Termination Panel Secondary I/O Bus Termination Panel Redundant 1 for 1 Configuration Several figures illustrate simplex and redundancy configurations. Simplex Configuration shows a simplex termination panel to I/O card configuration with redundant I/O bus setup (not necessary, but recommended). Redundant 1 for 1 Configuration shows a redundant 1 : 1 I/O setup. Redundant 1 for N (N = 2) Configuration shows one backup card for two primary cards. Both input and output I/O can be simplex or redundant. Installation Both the analog I/O card and the analog input card are installed in the Type CP6701 Control Input/Output Cardfile. These cards can be mixed with other CL6700-Series, CL6800-Series, and CL6900-Series I/O cards in the same cardfile. The cardfile is installed on standard EIA rails located in a Type CP7010 System Cabinet or factory-supplied custom cabinet. BU4.2:CL6821 December 1995 Page 6 Primary PROVOXr Highway Primary I/O Cards 1 and 2 SR90 or SRx Controller Backup I/O Card I/O Card File Secondary PROVOX Highway Primary I/O Bus Termination Panel Secondary I/O Bus Termination Panel I/O Card to Termination Panel Cables Cable Interface Panel Redundant 1 for N (N = 2) Configuration Termination panels are installed on standard EIA rails in a Type CP7005 Half-Depth Cabinet, a Type CP7010 System Cabinet, or a factory-supplied custom cabinet. These cabinets provide environmentally protected, temperature controlled mounting. Termination panels can be installed front and back in a Type CP7010 cabinet for efficient space usage. For this installation, front and back doors make panels easily accessible. Termination panels can be intermixed with other family panels wherever there is adequate rack space on the EIA rails. Since the interface card and termination panels are part of the Control I/O product family, all of the physical-distribution characteristics of the family apply. The analog cards and termination panels can be placed in a control room or placed outside the control room closer to the process field devices. An I/O bus connects the I/O cards installed in the I/O card file to an SR90 or SRx controller. A multi-pair cable connects an I/O card to a termination panel. The I/O bus and multi-pair cables allow for local or remote I/O locations. Termination panels accept twisted-pair cable from field devices. Power Failure and Recovery A power failure involving the entire I/O subsystem causes all outputs to be cleared to a de-activated state. When power is restored, a power up sequence returns outputs to the configured power-up states. System response to power failures of individual analog I/O components depends upon the component experiencing the power failure and whether there is a redundant or backup for that component. Power failures within a cardfile only cause redundancy switchover if the failure is a blown fuse on an active card. Further information is available in Control I/O family installation planning manuals. Specifications Specifications for accuracy, repeatability, operating conditions, and so forth listed in the Specifications table are the values for the complete input or output signal path from the field wiring terminals on a termination panel to the Control I/O Bus connector. The path includes the termination panel, the modules installed on the panel, and the I/O card. BU4.2:CL6821 December 1995 Page 7 Specifications I/O Card Capacity Types CL6821 and CL6824 input: 16 channels. Type CL6821 output: 8 channels. Isolated High-Level Input for Non-isolated Transmitters (Uses Type CL6855 Module, isolated version) 1 to 5 Vdc Input Resistance: 10 Megohms Nominal 3db Bandwidth: 3 Hz Accuracy: 0.3% reference, 0.6% operating Resolution: 12 bit Dielectric Strength: 1500 Vdc 0 to 10 Vdc Input Resistance: 100 kohms Nominal 3db Bandwidth: 3 Hz Accuracy: 0.3% reference, 0.6% operating Resolution: 12 bit Dielectric Strength: 1500 Vdc 4 to 20 mA Input Resistance: 250 ohm range resistor Nominal 3db Bandwidth: 3 Hz Accuracy: 0.4% reference, 0.7% operating Resolution: 12 bit Dielectric Strength: 1500 Vdc Output Signal 1 to 5 Vdc Accuracy: 0.2% reference, 0.35% operating 4 to 20 mA Accuracy: 0.1% reference, 0.25% operating Drive capability: up to 820 ohms with 24 Vdc applied to cardfile Single-Ended High-Level Input from either Traditional Analog or Smart Device (Uses Type CL6859 Module, analog version) 1 to 5 Vdc 4 to 20 mA Input Resistance: 10 Megohms Rolloff Frequency: 9 decibels down at 3.0 Hz, 6 decibels down at 2.1 Hz, 3 decibels down at 1.1 Hz Accuracy: 0.15% reference, 0.2% operating Repeatability: 0.05% of span Resolution: 12 bit Input Resistance: 250 ohms Rolloff frequency: 9 decibels down at 3.0 Hz, 6 decibels down at 2.1 Hz, 3 decibels down at 1.1 Hz Accuracy: 0.25% reference, 0.3% operating Repeatability: 0.05% of span Resolution: 12 bit High-Level Input for Isolated, Self-powered Transmitters (Uses Type CL6855 Module, non-isolated version) 1 to 5 Vdc Input Resistance: 10 Megohms Nominal 3db Bandwidth: 3 Hz Accuracy: 0.25% reference, 0.3% operating Resolution: 12 bit 4 to 20 mA Input Resistance: 250 ohm range resistor Nominal 3db Bandwidth: 3 Hz Accuracy: 0.25% reference, 0.3% operating Resolution: 12 bit Isolated Millivolt Input (Uses Type CL6856 Module) –10 to 70 mV Input Resistance: 10 Megohms Nominal 3db Bandwidth: 3 Hz Accuracy: 0.32% reference, 0.62% operating Resolution: 12 bit Dielectric Strength: 1500 Vdc BU4.2:CL6821 December 1995 Page 8 Specifications (continued) RTD Input (Uses Type CL6857 Modules) Thermocouple Input (Uses Type CL6858 Modules) Input Range: twelve temperature ranges. Refer to the RTD Input Ranges table. Nominal 3db Bandwidth: 3 Hz RTD Type: can be 2, 3 or 4 wire RTD Input Ranges Input Range Accuracy Rating (1) –270 to 140oF 0.40% (–168 to 60oC) –148 to 212oF 0.40% (–100 to 100oC) –100 to 600oF 0.39% (–73 to 315oC) 32 to 392oF 0.42% (0 to 200oC) 32 to 1112oF 0.35% (0 to 600oC) 100 to 500oF 0.43% (38 to 260oC) o –270 to 140 F 0.40% (–168 to 60oC) –148 to 212oF 0.40% (–100 to100oC) –100 to 600oF 0.39% (–73 to 315oC) 32 to 392oF 0.42% (0 to 200oC) 32 to 1112oF 0.35% (0 to 600oC) o 100 to 500 F 0.43% (38 to 260oC) o 32 to 300 F 0.90% (0 to 149oC) Accuracy Oper (1) Input Range: nine temperature ranges. Refer to the Thermocouple Input Ranges table Thermocouple burnout: upscale Cold junction compensation: provided on each channel Reference Junction Accuracy: ±0.5°C drift maximum at 77°F (25°C) Dielectric Strength: Available at 1500 Vdc or 100 Vrms Type 0.70% 0.70% 0.69% 100 ohm platinum with a temperature coefficient of 0.00392 ohm/oC Thermocouple Input Ranges Accuracy Input Range Oper Type 0.31% 0.61% J High –60 to 640oF (–51 to 338oC) 0.33% 0.63% J Low 0.70% –148 to 2462oF (–100 to 1350oC) 0.31% 0.63% K High 0.70% 0 to 1000oF (–18 to 538oC) 0.33% 0.63% K Low 32 to 3182oF (0 to 1750oC) 0.35% 0.65% R –300 to 600oF (–184 to 315oC 0.35% 0.65% T –100 to 1600oF (–73 to 871oC) 0.30% 0.60% E 32 to 3272oF (0 to 1800oC) 0.45% 0.75% B 32 to 3182oF (0 to 1750oC) 0.35% 0.65% S 0.72% 0.65% 0.73% 0.69% 0.72% 0.65% 100 ohm platinum with a temperature coefficient of 0.00385 ohm/oC 0.73% 1.95% (1) When operated in 3 or 4 wire mode 10 ohm copper –148 to 1400oF (–100 to 760oC) Ref BU4.2:CL6821 December 1995 Page 9 Specifications (continued) General Specifications I/O Card Power +24 Vdc nominal from the system cabinet power bus bar at the current listed: Type CL6821 Analog I/O Card: 300 mA for input, 175 mA for output Type CL6824 Analog Input Card: 300 mA Interface Panel Power Type CL6841 Cable Interface: 0 mA Type CL6842 Cable Interface: 0 mA Termination Panel Power +24 Vdc nominal from the system cabinet power bus bar at the current listed: Type CL6861 Single-Ended Analog Input: 30 mA (Add 22 mA for each 2-wire transmitter) Type CL6862 Redundant Single-Ended Analog Input: 60 mA (Add 22 mA for each 2-wire transmitter) Type CL6895 Single-Ended Analog/ Smart Device Input: 30 mA (Add 22 mA for each 2-wire transmitter) Type CL6896 Redundant Single-Ended Analog/Smart Device Input — 100 mA (Add 22 mA for each 2-wire transmitter) Type CL6897 Analog Input: 25 mA (Add 35 mA for each module) Type CL6898 Redundant Analog Input: 75 mA (Add 35 mA for each module) Type CL6885 Analog Output: 0 mA Type CL6886 Redundant Analog Output: 125 mA Switches One momentary pushbutton switch located on the Type CL6821 I/O cad and the Type CL6824 input card for manual switchover to the backup card Input Bump 1% of span maximum Electrical Classification Refer to Non-Hazardous Area Classification Bulletin, BU4.7:001 Electromagnetic Compatibility Complies with European Standards EN50081-2:1993 and EN50082-2:1995 Surge Withstand All termination panels meet IEEE STD C37.90–1989 for Relays and Relay Systems Associated with Electrical Power Apparatus (transient protection) at all field wiring terminals Field Wiring Connections Printed circuit board connectors with screw lock; each connector can accept one 12 AWG or two 14 AWG wires Cable Trays 1-inch (25.4 mm): Included with termination panels and cable interface panels.19 inches (483 mm) wide Optional 2-inch (50.8 mm): 19 inches (483 mm) wide; requires 1.75 inch mounting height (1 rack-unit) above termination panels. Termination Panel to Analog Card Cables Type: Gray PVC jacket, multi-twisted-pair conductor, one aluminum-polyester shield with 24 AWG stranded tinned copper drain wire. Meets VW-1 Vertical Wire Flame Test Conductors: Cable between I/O card and input termination panel — 19-twisted pair, tinned copper, S-R PVC insulated, 24 AWG. Cable between I/O card and output termination panel — 13-twisted pairs, tinned copper, S-R PVC insulated, 24 AWG. Nominal capacitance: 30pf/ft (98 pf/m) between mutual conductors, 50pf/ft (164 pf/m) between one conductor and other conductors connected to the shield Resistance: 24 ohms/1000 ft connector. 14 ohms/1000 ft drain wire, Lengths: Includes molded connectors on both cable ends, in standard lengths of 5, 10, 20, 50, 100, 200 feet (1.52, 3.05, 6.1, 15.2, 30.5, 61 m). The 50, 100, and 200 foot cables are supplied with a field termination kit for custom installation. 200 ft (61 m) is the maximum allowable cable length. BU4.2:CL6821 December 1995 Page 10 Specifications Mounting Depth All termination panels have a mounting depth of 4 inches (102 mm) Dimensions and Weight Type CL6821 Analog I/O Card and Type CL6824 Analog Input Card: 8.66 inches x 9.18 inches (220 mm x 233 mm) 1 pound (0.45 kg) Type CL6861 Termination Panel: 5.25 inches (3 rack units) x 19 inches (133 mm x 483 mm) including 1-inch cable tray. 3.3 pounds (1.5 kg) Type CL6862 Termination Panel: 7 inches (4 rack units) x19 inches (178 mm x 483 mm)including 1-inch cable tray. 4.5 pounds (2 kg) Type CL6895 Termination Panel: 5.25 inches (3 rack units) x 19 inches (133 mm x 483 mm) including 1-inch cable tray. 3.2 pounds (1.4 kg) Type CL6896 Termination Panel: 5.25 inches (3 rack units) x19 inches (133 mm x 483 mm) including 1-inch cable tray. 3.3 pounds (1.5 kg) Type CL6897 Termination Panel: 5.25 inches (3 rack units) x 19 inches (133 mm x 483 mm) including 1-inch cable tray. 3.0 pounds (1.4 kg) Type CL6898 Termination Panel: 5.25 inches (3 rack units) x 19 inches (133 mm x 483 mm) including 1-inch cable tray. 3.1 pounds (1.4 kg) Type CL6885 Termination Panel: 3.5 inches (2 rack units) x 19 inches (89 mm x 483 mm) including 1-inch cable tray. 2.1 pounds (0.96 kg) Ordering Information Type CL6886 Termination Panel: 3.5 inches (2 rack units) x 19 inches (89 mm x 483 mm) including 1-inch cable tray. 2.2 pounds (0.99 kg) Type CL6841 and Type CL6842 Cable Interface Panels: 5.25 inches (3 rack units) x 19 inches (133 mm x 483 mm) 3 pounds (1.36 kg) not including a cable tray. One–inch cable tray adds 1.5 inches (38 mm), two–inch cable tray adds 3 inches (89 mm) to panel height Operating Conditions Reference Conditions Limits (1) Ambient Temperature Maximum Temperature Variation Ambient Relative Humidity (without condensation) 1. Normal Limits (1) Operative Limits (1) Transport & Storage Limits (1) 73 & 81oF 41 & 131oF 32 & 131oF (23 & 27oC) (5 & 55oC) (0 & 55oC) –40 & 149oF (–40 & 65oC) 3.5oF/h (2oC/h) 36oF/hr (20oC/hr) 9oF/min (5oC/min) 18oF/min (10oC/min) 35 to 45% 10 to 90% 5 to 95% 5 to 95% These terms are defined in ISA Standard ISA-S51.1-1979. Analog I/O Cards Type CL6821 Analog Input/Output (I/O) Card Type CL6824 Analog Input Card Note See the Analog I/O Application table to determine the termination panels and modules to use to obtain the desired signal conversions. Input Termination Panels Type CL6895 Single-Ended Analog/Smart Device Input Termination Panel Type CL6896 Redundant Single-Ended Analog/Smart Device Input Termination Panel Type CL6897 Analog Input Termination Panel When ordering, specify: Type CL6898 Redundant Analog Input Termination Panel BU4.2:CL6821 December 1995 Page 11 Output Termination Panels –270 to 140oF Type CL6885 Analog/Smart Device Output Termination Panel –148 to 212oF Type CL6886 Redundant Analog/Smart Device Output Termination Panel 32 to 392oF –100 to 600oF 32 to 1112oF Modules for High-Level Inputs Select one module for each channel used; up to sixteen modules. Not all channels on a termination panel need be used. Type CL6855 High-Level Isolated Analog Input Module, and input range: For Isolated Transmitters 1 to 5 volts 4 to 20 mA For Non-isolated Transmitters 100 to 500oF 10 ohm copper RTD type. Temperature range is 32 to 300oF. Modules for Thermocouple Inputs Select one module for each channel used; up to sixteen modules. Not all channels on a termination panel need be used. Type CL6858 Thermocouple Input Modules, thermocouple type, and isolation capability: Thermocouple type: 0 to 10 volts Type J high (–148 to 1400oF) 1 to 5 Vdc Type J low (–60 to 640oF) 4 to 20 mA Type K high (–148 to 2462oF) Type K low (0 to 1000oF) Modules for Isolated Millivolt Inputs Type R (32 to 3182oF) Select one module for each channel used; up to sixteen modules. Not all channels on a termination panel need be used. Type T (–300 to 600oF) Type CL6856 Low Level Isolated Analog Input Module (–10 to 70 mV) Type B (32 to 3272oF) Modules for RTD Inputs Select one module for each channel used; up to sixteen modules. Not all channels on a termination panel need be used. Type CL6857 RTD Input Module, RTD type, and temperature range: Platinum RTD types. Specify the temperature coefficient: 0.00385 ohms/oC 0.00392 ohms/oC Specify the temperature range: Type E (–100 to 1600oF) Type S (32 to 3182oF) Dielectric Strength: 100 Vrms 1500 Vdc Modules for Analog/Smart Device Inputs Select one module per pair of channels used; up to eight modules. Not all channels on a termination panel need be used. Type CL6859 Analog/Smart Device Input Modules, and input signal type: Analog input signal Smart device input signal BU4.2:CL6821 December 1995 Page 12 Cable Interface Panels Specify only if using 1 for N redundancy: Type CL6841 Analog Input Cable Interface Panel 100 foot (30.5 m). Includes an extra connector for field alterations 200 foot (61 m). Includes an extra connector for field alterations Type CL6842 Analog Output Cable Interface Panel I/O Card to Termination Panel Cables A simplex termination panel requires one cable. A redundant termination panel requires two cables: one to the primary I/O card and the other to the redundant I/O card (for 1 : 1 redundancy) or to the cable interface panel (for 1 : N redundancy). Factory specified up to 20 feet for cabling between adjacent cabinets. If the cabinets are not adjacent, specify the lengths below: Cable Trays All termination panels include a one-inch wide horizontal cable tray for field-wiring. An optional two-inch wide cable tray is available to replace the one-inch tray. The wider tray, which mounts horizontally above the panel, increases both the cable capacity and the cable-bend area. Specify the optional wider tray if desired. 5 feet (1.525 m) Calibration Equipment 10 feet (3.05 m) Type CL6891 Analog Calibration Adapter, and input range: 20 feet (6.1 m) 4 to 20 mA (includes 250 ohm range resistor) 50 foot (15.2 m). Includes an extra connector for field alterations 1 to 5 Vdc The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. ENVOX, microPROVOX, PROFLEX, and PROVOX, are marks of one or more of the Fisher-Rosemount group of companies. All other marks are the property of their respective owners. Fisher-Rosemount Systems, Inc. 1995. All rights reserved. Printed in USA.