Analog I/O Interface with CL6800-Series Cards, Termination Panels

BU4.2:CL6821
December 1995
PROVOXr Process Management Systems
Analog I/O Interface with CL6800-Series
Cards, Termination Panels, and Modules
CL6800-Series Analog I/O instruments are members
of the PROVOXr Control I/O family. They interface
analog field devices to SR90 and SRx Controllers in
PROVOX Process Management Systems. The
instruments consist of input and output cards, input
modules, termination panels, and cable interface
panels.
SR90 or SRx Controller
The cards convert analog signals between the signal
format used by SR90 and SRx Controllers and the
analog signals of the field devices. An analog input
and output card provides either input or output signal
conversion, while an analog input-only card provides
cost-effective input-only conversion for control systems
which use many more analog inputs than outputs.
The selection of input termination panels lets you
choose between single-ended or isolated analog input
signals and between simplex and redundant
applications. Output termination panels let you choose
between simplex and redundant outputs.
For isolated signals, a complete family of input
modules plug into input termination panels to interface
a wide selection of high-level, low-level, thermocouple,
and RTD signals to match your analog input
requirements.
Smart I/O Interface
D001233X072
For information about smart device (HART
Compatible) I/O interface and available smart I/O
cards, termination panels, and modules, see product
bulletin, BU4.2:CL6825.
Analog Card
ÇÇ
ÇÇ
Termination Panel
Analog Field Devices
Interface Between Analog Field Devices and an
SR90 or SRx Controller
BU4.2:CL6821
December 1995
Page 2
Analog I/O Instruments
Analog I/O Applications
The following instruments make up the CL6800-Series
for analog I/O interface:
The termination panels and modules can be mixed
and matched to meet your I/O application. See the
Analog I/O Applications table for available
combinations.
Input and Output Cards
Type CL6821 Analog Input/Output (I/O) Card
Type CL6824 Analog Input Card
Cable Interface Panels
Type CL6841 Analog Input Cable Interface Panel
Type CL6842 Analog Output Cable Interface Panel
Input Termination Panels
Type CL6895 Single-Ended Analog/Smart Device
Input Termination Panel
Type CL6896 Redundant Single-Ended Analog/Smart
Device Input Termination Panel
Type CL6897 Analog Input Termination Panel
Type CL6898 Redundant Analog Input Termination
Panel
Output Termination Panels
Type CL6885 Analog/Smart Device Output
Termination Panel
Type CL6886 Redundant Analog/Smart Device Output
Termination Panel
The first combination for high-level inputs lets you
accept analog input signals from either traditional
analog devices or smart devices. This combination
gives you flexibility if you are transitioning your plant to
smart device capability. You can install your smart field
transmitters and use their analog signals now and later
use their full communications capability when you
complete your control system upgrade.
The second and third combinations for high-level
inputs let you select the appropriate ground system,
depending on whether the analog transmitter is
isolated or non-isolated. Other combinations allow you
to use millivolt inputs, RTD inputs, and thermocouple
inputs.
With the output selection, you can send output signals
to either transitional analog or smart final control
elements. If you are planning a plant upgrade to smart
final control elements, you can operate your smart
elements now and later use their full capability when
you complete your system upgrade.
Configuration
The analog interface is configured by ENVOX or
PROFLEX Configuration Software, or by the
microPROVOXt System. Each channel is configured
individually for versatile setup to your system needs.
Calibration
Input Modules
Type CL6855 High-Level Isolated and High-Level
Non-Isolated Analog Input Modules
Type CL6856 Millivolt Analog Input Module
Type CL6857 RTD Input Modules
Type CL6858 Thermocouple Input Modules
Type CL6859 Analog/Smart Device Input Modules
The analog I/O card and the analog input card have
self-contained digital calibration capability. Cards are
shipped properly calibrated so that you need only
configure them to your system requirements. Factory
calibration data is stored in non-volatile memory in
each card and the card automatically maintains
calibration in normal operating environments. When
the cards are operated at or near their environmental
limits, they may require periodic calibration using the
Type CL6891 Analog I/O Calibration Adapter.
BU4.2:CL6821
December 1995
Page 3
Analog I/O Applications
I/O Conversion
I/O System
Termination Panel
Module
G High-level Input for either
Traditional Analog or Smart
Device inputs
G Single-ended ground (1)
Simplex
Type CL6895 Single-ended
Analog/Smart Device Input
Termination Panel
Redundant
Type CL6896 Redundant
Single-ended Analog/Smart
Device Input Termination Panel
Type CL6859 Analog/Smart Device
Input Module (select analog input
version). One module per pair of
channels.(3)
G High-Level Input
G Non-isolated transmitter
G Isolated ground (2)
Simplex
Type CL6897 Analog Input
Termination Panel
Redundant
Type CL6898 Redundant Analog
Input Termination Panel
G High-Level Input
G Isolated, Self-powered
transmitter
G Single-ended ground (1)
Simplex
Type CL6897 Analog Input
Termination Panel
Redundant
Type CL6898 Redundant Analog
Input Termination Panel
G Millivolt Input
G Isolated ground (2)
Simplex
Type CL6897 Analog Input
Termination Panel
Redundant
Type CL6898 Redundant Analog
Input Termination Panel
Simplex
Type CL6897 Analog Input
Termination Panel
Redundant
Type CL6898 Redundant Analog
Input Termination Panel
Simplex
Type CL6897 Analog Input
Termination Panel
Redundant
Type CL6898 Redundant Analog
Input Termination Panel
Simplex
Type CL6885 Analog/Smart
Device Output Termination Panel
Redundant
Type CL6886 Redundant
Analog/Smart Device Output
Termination Panel
G RTD Input
G Thermocouple Input
G Single-ended ground (1)
G High-level output for either
conventional analog device
or smart device
G Single-ended ground (1)
Type CL6855 High-level Analog
Input Module (Select isolated
version). One module per channel.
Type CL6855 High-level Analog
Input Module (Select non-isolated
version). One module per channel.
Type CL6856 Low-level Isolated
Analog Input Module. One module
per channel.
Type CL6857 RTD Input Module
(select desired temperature range).
One module per channel,
non-isolated.(4)
Type CL6858 Thermocouple Input
Module (select desired temperature
range and dielectric strength
rating (5)). One module per channel.
No modules required
1.
Single-ended ground means that a field device ground is not isolated from the PROVOX system ground
2.
Isolated ground means that a field device ground is isolated from the PROVOX system ground
3.
The Type CL6859 module sets the Type CL6895 or CL6896 termination panel to the I/O card. You may use the 4 to 20 mA dc signal
from either traditional analog or smart field devices, but select the analog version of the Type CL68759 module to match the
termination panel to the Type CL6821 or CL6824 card.
4.
The module does not provide isolation. If isolation is required, consult your Fisher-Rosemount representative or sales office.
5.
Dielectric strength rating is measured between field wiring inputs and PROVOX system ground
Intrinsic Safety Applications
Analog I/O products may be used in intrinsic safety
applications. CL6340-Series termination panels and
CL6350-Series intrinsic safety barriers interface field
devices in hazardous locations to a PROVOX system.
These panels and barriers replace the standard analog
I/O termination panels and modules; they are not in
addition, so you can save on the number of cabinets
required for your I/O system. See product bulletin,
CL6349-Series Termination Panels and
CL6350-Series Intrinsic Safety Barriers,
BU4.2:CL6340, for a detailed description.
BU4.2:CL6821
December 1995
Page 4
Termination Panel Interchange
Previous Design Termination Panel
Rack Units
Type CL6861 Single-Ended Analog Input
Termination Panel
3
Type CL6895 Single-Ended Analog/Smart
Device Input Termination Panel. (Requires a
Type CL6859 Analog/Smart Device Input
Module for each channel pair used.)
3
Type CL6862 Redundant Single-Ended
Analog Input Termination Panel
4
Type CL6896 Redundant Single-Ended
Analog/Smart Device Input Termination
Panel. (Requires a Type CL6859
Analog/Smart Device Input Module for each
channel pair used.)
3
Type CL6863 Isolated Analog Input
Termination Panel
4
Type CL6897 Analog Input Termination
Panel
3
Type CL6864 Redundant Isolated Analog
Input Termination Panel
5
Type CL6898 Redundant Analog Input
Termination Panel
3
Type CL6871 Analog Output Termination
Panel
2
Type CL6885 Analog/Smart Device Output
Termination Panel
2
Type CL6872 Redundant Analog Output
Termination Panel
3
Type CL6886 Redundant Analog/Smart
Device Output Termination Panel
2
1.
Current Design Termination Panel
Rack Units
Previous design termination panels are no longer available as a normal order item; they are listed for cabinet sizing purposes to show
rack unit comparison between the previous design and the currently available replacement design.
You may also use the intrinsic safety products of other
manufacturers. These products may add impedance to
the 4 to 20 mA current loop which must be taken into
account. A typical additional impedance is 180 ohms.
To help minimize your system costs, you may be able
to use one-for-N backup. In this type of backup, one
backup card can support up to eight primary cards.
The backup card need not be located in the same file
as the primary card.
Backup combinations are available, as follows:
Termination Panel Interchange
On-going termination panel enhancements provide
more space-efficient mounting. Many of the currently
available termination panels have less height than
previous designs and can be used as replacements for
the previous designs. See the Termination Panel
Interchange table above for replacement sizing
information. Electrical isolation methods may vary
between termination panels, so compare the electrical
ground information provided in the Analog I/O
Applications table with your field device ground
requirements.
Redundancy
You can choose one-for-one (1:1) or one-for-N (1:N)
backup to meet your process requirements.
One-for-one backup requires two analog interface
cards, two I/O buses, two multi-pair cables, and one
redundant termination panel.
An analog I/O card configured for input can be
backed up by a similarly configured analog I/O card
or analog input card.
An analog input card can be backed by an analog
I/O card configured for input or another analog
input card.
An analog I/O card configured for output is backed
up by a similarly configured analog I/O card.
If a primary card failure is detected and input or output
data is not corrupted when inputs are reported or
outputs are driven, both input and output values are
held at their last values. Switchover is bumpless for
outputs. Switchover for input is delayed to allow input
filters to stabilize for smooth transitions. Normal input
reporting and output driving continues after the
switchover is complete.
If the failure is detected and the data is corrupted
when inputs are reported or outputs are driven, a
bump of inputs or outputs at switchover may occur.
BU4.2:CL6821
December 1995
Page 5
Primary PROVOXr Highway
I/O Cards
SR90 or SRx
Controller
I/O Card File
Secondary PROVOX Highway
I/O Card to Termination Panel Cables
Primary
I/O Bus
Termination Panel
Secondary
I/O Bus
Termination Panel
Simplex Configuration
Primary PROVOXr Highway
Primary I/O Cards
Secondary I/O Cards
SR90 or SRx
Controller
I/O Card File
Secondary PROVOX Highway
I/O Card to Termination Panel Cables
Primary
I/O Bus
Termination Panel
Secondary
I/O Bus
Termination Panel
Redundant 1 for 1 Configuration
Several figures illustrate simplex and redundancy
configurations. Simplex Configuration shows a simplex
termination panel to I/O card configuration with
redundant I/O bus setup (not necessary, but
recommended). Redundant 1 for 1 Configuration
shows a redundant 1 : 1 I/O setup. Redundant 1 for N
(N = 2) Configuration shows one backup card for two
primary cards. Both input and output I/O can be
simplex or redundant.
Installation
Both the analog I/O card and the analog input card are
installed in the Type CP6701 Control Input/Output
Cardfile. These cards can be mixed with other
CL6700-Series, CL6800-Series, and CL6900-Series
I/O cards in the same cardfile. The cardfile is installed
on standard EIA rails located in a Type CP7010
System Cabinet or factory-supplied custom cabinet.
BU4.2:CL6821
December 1995
Page 6
Primary PROVOXr Highway
Primary I/O Cards 1 and 2
SR90 or SRx
Controller
Backup I/O Card
I/O Card File
Secondary PROVOX Highway
Primary
I/O Bus
Termination Panel
Secondary
I/O Bus
Termination Panel
I/O Card to Termination Panel Cables
Cable Interface Panel
Redundant 1 for N (N = 2) Configuration
Termination panels are installed on standard EIA rails
in a Type CP7005 Half-Depth Cabinet, a Type CP7010
System Cabinet, or a factory-supplied custom cabinet.
These cabinets provide environmentally protected,
temperature controlled mounting.
Termination panels can be installed front and back in a
Type CP7010 cabinet for efficient space usage. For
this installation, front and back doors make panels
easily accessible. Termination panels can be
intermixed with other family panels wherever there is
adequate rack space on the EIA rails.
Since the interface card and termination panels are
part of the Control I/O product family, all of the
physical-distribution characteristics of the family apply.
The analog cards and termination panels can be
placed in a control room or placed outside the control
room closer to the process field devices.
An I/O bus connects the I/O cards installed in the I/O
card file to an SR90 or SRx controller. A multi-pair
cable connects an I/O card to a termination panel. The
I/O bus and multi-pair cables allow for local or remote
I/O locations. Termination panels accept twisted-pair
cable from field devices.
Power Failure and Recovery
A power failure involving the entire I/O subsystem
causes all outputs to be cleared to a de-activated
state. When power is restored, a power up sequence
returns outputs to the configured power-up states.
System response to power failures of individual analog
I/O components depends upon the component
experiencing the power failure and whether there is a
redundant or backup for that component. Power
failures within a cardfile only cause redundancy
switchover if the failure is a blown fuse on an active
card. Further information is available in Control I/O
family installation planning manuals.
Specifications
Specifications for accuracy, repeatability, operating
conditions, and so forth listed in the Specifications
table are the values for the complete input or output
signal path from the field wiring terminals on a
termination panel to the Control I/O Bus connector.
The path includes the termination panel, the modules
installed on the panel, and the I/O card.
BU4.2:CL6821
December 1995
Page 7
Specifications
I/O Card Capacity
Types CL6821 and CL6824 input:
16 channels.
Type CL6821 output: 8 channels.
Isolated High-Level Input for Non-isolated
Transmitters (Uses Type CL6855 Module,
isolated version)
1 to 5 Vdc
Input Resistance: 10 Megohms
Nominal 3db Bandwidth: 3 Hz
Accuracy: 0.3% reference, 0.6% operating
Resolution: 12 bit
Dielectric Strength: 1500 Vdc
0 to 10 Vdc
Input Resistance: 100 kohms
Nominal 3db Bandwidth: 3 Hz
Accuracy: 0.3% reference, 0.6% operating
Resolution: 12 bit
Dielectric Strength: 1500 Vdc
4 to 20 mA
Input Resistance: 250 ohm range resistor
Nominal 3db Bandwidth: 3 Hz
Accuracy: 0.4% reference, 0.7% operating
Resolution: 12 bit
Dielectric Strength: 1500 Vdc
Output Signal
1 to 5 Vdc
Accuracy: 0.2% reference, 0.35%
operating
4 to 20 mA
Accuracy: 0.1% reference, 0.25%
operating
Drive capability: up to 820 ohms with
24 Vdc applied to cardfile
Single-Ended High-Level Input from either
Traditional Analog or Smart Device (Uses
Type CL6859 Module, analog version)
1 to 5 Vdc
4 to 20 mA
Input Resistance: 10 Megohms
Rolloff Frequency: 9 decibels down at 3.0
Hz, 6 decibels down at 2.1 Hz, 3 decibels
down at 1.1 Hz
Accuracy: 0.15% reference, 0.2%
operating
Repeatability: 0.05% of span
Resolution: 12 bit
Input Resistance: 250 ohms
Rolloff frequency: 9 decibels down at 3.0
Hz, 6 decibels down at 2.1 Hz, 3 decibels
down at 1.1 Hz
Accuracy: 0.25% reference, 0.3%
operating
Repeatability: 0.05% of span
Resolution: 12 bit
High-Level Input for Isolated, Self-powered
Transmitters (Uses Type CL6855 Module,
non-isolated version)
1 to 5 Vdc
Input Resistance: 10 Megohms
Nominal 3db Bandwidth: 3 Hz
Accuracy: 0.25% reference,
0.3% operating
Resolution: 12 bit
4 to 20 mA
Input Resistance: 250 ohm range resistor
Nominal 3db Bandwidth: 3 Hz
Accuracy: 0.25% reference,
0.3% operating
Resolution: 12 bit
Isolated Millivolt Input (Uses Type CL6856
Module)
–10 to 70 mV
Input Resistance: 10 Megohms
Nominal 3db Bandwidth: 3 Hz
Accuracy: 0.32% reference,
0.62% operating
Resolution: 12 bit
Dielectric Strength: 1500 Vdc
BU4.2:CL6821
December 1995
Page 8
Specifications (continued)
RTD Input (Uses Type CL6857 Modules)
Thermocouple Input
(Uses Type CL6858 Modules)
Input Range: twelve temperature ranges.
Refer to the RTD Input Ranges table.
Nominal 3db Bandwidth: 3 Hz
RTD Type: can be 2, 3 or 4 wire
RTD Input Ranges
Input Range
Accuracy
Rating (1)
–270 to 140oF
0.40%
(–168 to 60oC)
–148 to 212oF
0.40%
(–100 to 100oC)
–100 to 600oF
0.39%
(–73 to 315oC)
32 to 392oF
0.42%
(0 to 200oC)
32 to 1112oF
0.35%
(0 to 600oC)
100 to 500oF
0.43%
(38 to 260oC)
o
–270 to 140 F
0.40%
(–168 to 60oC)
–148 to 212oF
0.40%
(–100 to100oC)
–100 to 600oF
0.39%
(–73 to 315oC)
32 to 392oF
0.42%
(0 to 200oC)
32 to 1112oF
0.35%
(0 to 600oC)
o
100 to 500 F
0.43%
(38 to 260oC)
o
32 to 300 F
0.90%
(0 to 149oC)
Accuracy
Oper (1)
Input Range: nine temperature ranges.
Refer to the Thermocouple Input Ranges
table
Thermocouple burnout: upscale
Cold junction compensation: provided on
each channel
Reference Junction Accuracy: ±0.5°C
drift maximum at 77°F (25°C)
Dielectric Strength: Available at 1500 Vdc
or 100 Vrms
Type
0.70%
0.70%
0.69%
100 ohm
platinum with a
temperature
coefficient of
0.00392
ohm/oC
Thermocouple Input Ranges
Accuracy
Input Range
Oper
Type
0.31%
0.61%
J High
–60 to 640oF
(–51 to 338oC)
0.33%
0.63%
J Low
0.70%
–148 to 2462oF
(–100 to 1350oC)
0.31%
0.63%
K High
0.70%
0 to 1000oF
(–18 to 538oC)
0.33%
0.63%
K Low
32 to 3182oF
(0 to 1750oC)
0.35%
0.65%
R
–300 to 600oF
(–184 to 315oC
0.35%
0.65%
T
–100 to 1600oF
(–73 to 871oC)
0.30%
0.60%
E
32 to 3272oF
(0 to 1800oC)
0.45%
0.75%
B
32 to 3182oF
(0 to 1750oC)
0.35%
0.65%
S
0.72%
0.65%
0.73%
0.69%
0.72%
0.65%
100 ohm
platinum with a
temperature
coefficient of
0.00385
ohm/oC
0.73%
1.95%
(1) When operated in 3 or 4 wire mode
10 ohm copper
–148 to 1400oF
(–100 to 760oC)
Ref
BU4.2:CL6821
December 1995
Page 9
Specifications (continued)
General Specifications
I/O Card
Power
+24 Vdc nominal from the system cabinet
power bus bar at the current listed:
Type CL6821 Analog I/O Card:
300 mA for input, 175 mA for output
Type CL6824 Analog Input Card:
300 mA
Interface
Panel Power
Type CL6841 Cable Interface: 0 mA
Type CL6842 Cable Interface: 0 mA
Termination
Panel Power
+24 Vdc nominal from the system cabinet
power bus bar at the current listed:
Type CL6861 Single-Ended Analog
Input: 30 mA (Add 22 mA for each 2-wire
transmitter)
Type CL6862 Redundant Single-Ended
Analog Input: 60 mA (Add 22 mA for
each 2-wire transmitter)
Type CL6895 Single-Ended Analog/
Smart Device Input: 30 mA (Add 22 mA
for each 2-wire transmitter)
Type CL6896 Redundant Single-Ended
Analog/Smart Device Input — 100 mA
(Add 22 mA for each 2-wire transmitter)
Type CL6897 Analog Input: 25 mA (Add
35 mA for each module)
Type CL6898 Redundant Analog Input:
75 mA (Add 35 mA for each module)
Type CL6885 Analog Output: 0 mA
Type CL6886 Redundant Analog
Output: 125 mA
Switches
One momentary pushbutton switch
located on the Type CL6821 I/O cad and
the Type CL6824 input card for manual
switchover to the backup card
Input Bump
1% of span maximum
Electrical
Classification
Refer to Non-Hazardous Area
Classification Bulletin, BU4.7:001
Electromagnetic
Compatibility
Complies with European Standards
EN50081-2:1993 and EN50082-2:1995
Surge
Withstand
All termination panels meet IEEE STD
C37.90–1989 for Relays and Relay
Systems Associated with Electrical Power
Apparatus (transient protection) at all field
wiring terminals
Field Wiring
Connections
Printed circuit board connectors with
screw lock; each connector can accept
one 12 AWG or two 14 AWG wires
Cable Trays
1-inch (25.4 mm): Included with
termination panels and cable interface
panels.19 inches (483 mm) wide
Optional 2-inch (50.8 mm): 19 inches
(483 mm) wide; requires 1.75 inch
mounting height (1 rack-unit) above
termination panels.
Termination
Panel to
Analog Card
Cables
Type: Gray PVC jacket, multi-twisted-pair
conductor, one aluminum-polyester shield
with 24 AWG stranded tinned copper
drain wire. Meets VW-1 Vertical Wire
Flame Test
Conductors: Cable between I/O card and
input termination panel — 19-twisted pair,
tinned copper, S-R PVC insulated, 24
AWG. Cable between I/O card and output
termination panel — 13-twisted pairs,
tinned copper, S-R PVC insulated, 24
AWG.
Nominal capacitance: 30pf/ft (98 pf/m)
between mutual conductors, 50pf/ft (164
pf/m) between one conductor and other
conductors connected to the shield
Resistance: 24 ohms/1000 ft connector.
14 ohms/1000 ft drain wire,
Lengths: Includes molded connectors on
both cable ends, in standard lengths of 5,
10, 20, 50, 100, 200 feet (1.52, 3.05, 6.1,
15.2, 30.5, 61 m). The 50, 100, and 200
foot cables are supplied with a field
termination kit for custom installation. 200
ft (61 m) is the maximum allowable cable
length.
BU4.2:CL6821
December 1995
Page 10
Specifications
Mounting
Depth
All termination panels have a mounting
depth of 4 inches (102 mm)
Dimensions
and Weight
Type CL6821 Analog I/O Card and
Type CL6824 Analog Input Card: 8.66
inches x 9.18 inches (220 mm x 233
mm) 1 pound (0.45 kg)
Type CL6861 Termination Panel: 5.25
inches (3 rack units) x 19 inches (133
mm x 483 mm) including 1-inch cable
tray. 3.3 pounds (1.5 kg)
Type CL6862 Termination Panel: 7
inches (4 rack units) x19 inches (178
mm x 483 mm)including 1-inch cable
tray. 4.5 pounds (2 kg)
Type CL6895 Termination Panel: 5.25
inches (3 rack units) x 19 inches (133
mm x 483 mm) including 1-inch cable
tray. 3.2 pounds (1.4 kg)
Type CL6896 Termination Panel: 5.25
inches (3 rack units) x19 inches (133
mm x 483 mm) including 1-inch cable
tray. 3.3 pounds (1.5 kg)
Type CL6897 Termination Panel: 5.25
inches (3 rack units) x 19 inches (133
mm x 483 mm) including 1-inch cable
tray. 3.0 pounds (1.4 kg)
Type CL6898 Termination Panel: 5.25
inches (3 rack units) x 19 inches (133
mm x 483 mm) including 1-inch cable
tray. 3.1 pounds (1.4 kg)
Type CL6885 Termination Panel: 3.5
inches (2 rack units) x 19 inches (89 mm
x 483 mm) including 1-inch cable tray.
2.1 pounds (0.96 kg)
Ordering Information
Type CL6886 Termination Panel: 3.5
inches (2 rack units) x 19 inches (89 mm
x 483 mm) including 1-inch cable tray.
2.2 pounds (0.99 kg)
Type CL6841 and Type CL6842 Cable
Interface Panels: 5.25 inches (3 rack
units) x 19 inches (133 mm x 483 mm) 3
pounds (1.36 kg) not including a cable
tray. One–inch cable tray adds 1.5
inches (38 mm), two–inch cable tray
adds 3 inches (89 mm) to panel height
Operating Conditions
Reference
Conditions Limits (1)
Ambient
Temperature
Maximum
Temperature
Variation
Ambient
Relative
Humidity
(without
condensation)
1.
Normal
Limits (1)
Operative
Limits (1)
Transport &
Storage
Limits (1)
73 & 81oF
41 & 131oF 32 & 131oF
(23 & 27oC) (5 & 55oC) (0 & 55oC)
–40 & 149oF
(–40 & 65oC)
3.5oF/h
(2oC/h)
36oF/hr
(20oC/hr)
9oF/min
(5oC/min)
18oF/min
(10oC/min)
35 to 45%
10 to 90%
5 to 95%
5 to 95%
These terms are defined in ISA Standard ISA-S51.1-1979.
Analog I/O Cards
Type CL6821 Analog Input/Output (I/O) Card
Type CL6824 Analog Input Card
Note
See the Analog I/O Application table
to determine the termination panels
and modules to use to obtain the
desired signal conversions.
Input Termination Panels
Type CL6895 Single-Ended Analog/Smart Device
Input Termination Panel
Type CL6896 Redundant Single-Ended
Analog/Smart Device Input Termination Panel
Type CL6897 Analog Input Termination Panel
When ordering, specify:
Type CL6898 Redundant Analog Input Termination
Panel
BU4.2:CL6821
December 1995
Page 11
Output Termination Panels
–270 to 140oF
Type CL6885 Analog/Smart Device Output
Termination Panel
–148 to 212oF
Type CL6886 Redundant Analog/Smart Device
Output Termination Panel
32 to 392oF
–100 to 600oF
32 to 1112oF
Modules for High-Level Inputs
Select one module for each channel used; up to
sixteen modules. Not all channels on a termination
panel need be used.
Type CL6855 High-Level Isolated Analog Input
Module, and input range:
For Isolated Transmitters
1 to 5 volts
4 to 20 mA
For Non-isolated Transmitters
100 to 500oF
10 ohm copper RTD type. Temperature range is 32
to 300oF.
Modules for Thermocouple Inputs
Select one module for each channel used; up to
sixteen modules. Not all channels on a termination
panel need be used.
Type CL6858 Thermocouple Input Modules,
thermocouple type, and isolation capability:
Thermocouple type:
0 to 10 volts
Type J high (–148 to 1400oF)
1 to 5 Vdc
Type J low (–60 to 640oF)
4 to 20 mA
Type K high (–148 to 2462oF)
Type K low (0 to 1000oF)
Modules for Isolated Millivolt Inputs
Type R (32 to 3182oF)
Select one module for each channel used; up to
sixteen modules. Not all channels on a termination
panel need be used.
Type T (–300 to 600oF)
Type CL6856 Low Level Isolated Analog Input Module
(–10 to 70 mV)
Type B (32 to 3272oF)
Modules for RTD Inputs
Select one module for each channel used; up to
sixteen modules. Not all channels on a termination
panel need be used.
Type CL6857 RTD Input Module, RTD type, and
temperature range:
Platinum RTD types.
Specify the temperature coefficient:
0.00385 ohms/oC
0.00392 ohms/oC
Specify the temperature range:
Type E (–100 to 1600oF)
Type S (32 to 3182oF)
Dielectric Strength:
100 Vrms
1500 Vdc
Modules for Analog/Smart Device Inputs
Select one module per pair of channels used; up to
eight modules. Not all channels on a termination panel
need be used.
Type CL6859 Analog/Smart Device Input Modules,
and input signal type:
Analog input signal
Smart device input signal
BU4.2:CL6821
December 1995
Page 12
Cable Interface Panels
Specify only if using 1 for N redundancy:
Type CL6841 Analog Input Cable Interface Panel
100 foot (30.5 m). Includes an extra connector for
field alterations
200 foot (61 m). Includes an extra connector for
field alterations
Type CL6842 Analog Output Cable Interface Panel
I/O Card to Termination Panel Cables
A simplex termination panel requires one cable. A
redundant termination panel requires two cables: one
to the primary I/O card and the other to the redundant
I/O card (for 1 : 1 redundancy) or to the cable interface
panel (for 1 : N redundancy).
Factory specified up to 20 feet for cabling between
adjacent cabinets. If the cabinets are not adjacent,
specify the lengths below:
Cable Trays
All termination panels include a one-inch wide
horizontal cable tray for field-wiring. An optional
two-inch wide cable tray is available to replace the
one-inch tray. The wider tray, which mounts
horizontally above the panel, increases both the cable
capacity and the cable-bend area. Specify the optional
wider tray if desired.
5 feet (1.525 m)
Calibration Equipment
10 feet (3.05 m)
Type CL6891 Analog Calibration Adapter, and input
range:
20 feet (6.1 m)
4 to 20 mA (includes 250 ohm range resistor)
50 foot (15.2 m). Includes an extra connector for
field alterations
1 to 5 Vdc
The contents of this publication are presented for informational purposes only, and
while every effort has been made to ensure their accuracy, they are not to be construed
as warranties or guarantees, express or implied, regarding the products or services
described herein or their use or applicability. We reserve the right to modify or improve
the designs or specifications of such products at any time without notice.
ENVOX, microPROVOX, PROFLEX, and PROVOX, are marks of one or more of the
Fisher-Rosemount group of companies. All other marks are the property of their
respective owners.
 Fisher-Rosemount Systems, Inc. 1995. All rights reserved. Printed in USA.