GST301 Conventional Gas Release Control Panel

advertisement
GST301
Gas Extinguishing Control Panel
(Single Protection Zone)
Operation Manual
Global System Technology PLC
2 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
CONTENTS
1
OVERVIEW........................................................................................................................................... 4
2
TECHNICAL DATA ............................................................................................................................... 4
3
STRUCTURES...................................................................................................................................... 5
3.1
Indicators........................................................................................................................ 5
3.1.2
Keys & Switches ............................................................................................................ 7
3.1.3
Panel Sound................................................................................................................... 7
3.2
4
INTERNAL STRUCTURE ................................................................................................................. 8
3.2.1
Main board.................................................................................................................... 9
3.2.2
Display board ............................................................................................................... 10
TERMINALS & CONNECTIONS........................................................................................................ 10
4.1
TERMINALS ................................................................................................................................ 10
4.2
WIRING ..................................................................................................................................... 11
4.2.1
Zone connections. For Zone1, Zone2 & AUX Zone ..................................................... 11
4.2.2
Emergency Start/Abort Switch.................................................................................... 12
4.2.3
Gas release output....................................................................................................... 12
4.2.4
Sounder outputs, for Sounder1 & Sounder2................................................................ 13
4.2.5
Remote Outputs are using dry contacts. Simply connect to other systems................. 13
4.3
5
FRONT SURFACE DESCRIPTION .................................................................................................... 5
3.1.1
TYPICAL WIRING DIAGRAM........................................................................................................... 13
COMMISSION TIPS ........................................................................................................................... 15
5.1
CONFIGURE THE OUTPUTS .......................................................................................................... 15
5.2
CONFIGURE THE EMERGENCY START SWITCH ............................................................................. 15
5.3
CONFIGURE THE DISCHARGE OUTPUT .......................................................................................... 15
5.4
CONFIGURE THE REMOTE OUTPUT TYPE ...................................................................................... 15
5.5
SET THE GAS RELEASE DELAY TIME ............................................................................................. 16
5.6
SET THE GAS RELEASE OUTPUT PULSE WIDTH .............................................................................. 16
6
CAUSE & EFFECT ............................................................................................................................. 17
7
MANUAL OPERATIONS .................................................................................................................... 18
7.1.1
Start gas release from the panel .................................................................................. 18
7.1.2
Start gas release on field.............................................................................................. 18
7.1.3
Stop gas release from panel ........................................................................................ 18
7.1.4
Stop gas release on field.............................................................................................. 18
7.1.5
Silence the ringing bells & alarming panel ................................................................... 18
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
3 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
8
7.1.6
Ring the bells................................................................................................................ 18
7.1.7
Isolate/De-isolate operation ......................................................................................... 19
7.1.8
Switch Standby Cylinder Output................................................................................... 19
CAUTION............................................................................................................................................ 19
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
4 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
1. Overview
GST301 Gas Release Control Panel is a stand-alone panel intended for use with gas
extinguishing systems. The function of the panel is to monitor zones or areas for fire
conditions and give an appropriate audible/visible indication. The panel also provides a
facility for initiating the gas release to achieve automatic protection, both manually and
automatically.
GST301 Gas Release Control Panel has 2 detection zones to achieve double-knock
function, and a normal detection zone for extra usage. With C-9317 Emergency
Start/Abort Switch, the Gas Release can be controlled on field.
2. Technical Data
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Operating voltage:
Power consumption:
Battery Requirement:
Battery operating time:
AUX power supply:
Sounder output:
Release output:
battery charge current
Temperature:
Humidity:
Dimension:
220VAC +/- 15%
<10W (Monitoring Mode)
2X12VDC, 7AH
24 hours monitoring and half hour alarm
100mA/24VDC
1A/24VDC
2A/24VDC, pulse
≤300mA
-10°C ~ 55°C
≤95%
300X350X104 (HXWXD)
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
5 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
3. Structures
3.1
Front Surface Description
3.1.1 Indicators
POWER
BATT FAULT
AC FAULT
GAS RELEASE
FIRE
Green. Power supplied.
Amber. Battery Fault.(Voltage below 5V)
Amber. AC Fault.
Red. Flashes during delay time. Lighted after gas released.
Extinguished by reset.
Red. General fire indication. Lighted by any fire signal.
Extinguished by reset.
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
6 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
SILENCE
Green. Lighted if panel is silenced. Extinguished when panel
re-sounds.
AUTO ENABLE
Green. Lighted if the panel set in automatic mode. OFF for
manual only mode.
EVACUATE
Green. Flashes when evacuate key pressed. Extinguished by
reset.
DELAY TIME
Red. Indicating the time (in second) before gas releasing.
ZONE1 ACTIVE
Red. Flashes when zone 1 in alarm. Lighted steadily after
silenced. Extinguished by reset.
ZONE1 Fault/ISO Amber. Flashes when zone 1 has any fault. OFF when fault
removed. Steadily lighted when zone 1 isolated.
ZONE2 ACTIVE
Red. Flashes when zone 2 in alarm. Lighted steadily after
silenced. Extinguished by reset.
ZONE2 Fault/ISO Amber. Flashes when zone 2 has any fault. OFF when fault
removed. Steadily lighted when isolated.
AUX ZONE ACTIVE Red. Flashes when the AUX zone in alarm. Lighted steadily
after silenced. Extinguished by reset.
AUX ZONE Fault/ISO Amber. Flashes when the AUX zone has any fault. Steadily
lighted when the AUX zone isolated. OFF when fault removed.
CYLINDER ACTIVE Amber. Flashes when the release output is active. Extinguished
after output finished.
CYLINDER FAULT/ISO Amber. Flashes when the gas release output circuit has any
fault. Lighted steadily in isolated mode.
START ACTIVE
Amber. Flashes when press the START key on panel or the
Emergency Start Button on field.
START FAULT
Amber. Lighted by fault in Emergency Start Button Circuit.
Extinguished when fault removed.
STOP ACTIVE
Amber. Flashes when press the STOP key on panel or the
Emergency Abort Switch on field.
STOP FAULT
Amber. Lighted by fault in Emergency Abort Switch Circuit.
Extinguished when fault removed.
PRESSURE SWITCH ACTIVE Amber. Lighted if the pressure switch active (gas
released) or after gas release output started (no pressure
switch). Extinguished by reset.
PRESSURE SWITCH FAULT
Amber. Lighted by fault in pressure switch Circuit.
Extinguished when fault removed.
SOUNDER1 ACTIVE
Amber. Lighted when sounder 1 output started.
Extinguished when sounder 1 output stopped.
SOUNDER1 FAULT Amber. Lighted by fault in sounder 1 Circuit. Extinguished when
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
7 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
fault removed.
SOUNDER2 ACTIVE
Amber. Lighted when sounder 2 output started.
Extinguished when sounder 2 output stopped.
SOUNDER2 FAULT Amber. Lighted by fault in sounder 2 Circuit. Extinguished when
fault removed.
3.1.2 Keys & Switches
SILENCE
Stop all sounder outputs and local alarm (panel buzzer will beep
at 0.5sON & 9.5sOFF mode). Resume by new fire/fault signal or
pressing Evacuate key. If gas release timer on running, local
alarm will not be stopped, and sounder outputs will be resume
at the last 15 seconds.
RESET
Clear all inputs, indications and outputs.
LAMP TEST
Check indicators.
AUTO ENABLE
Enable the automatic gas release function. If this function is not
enabled, the gas release will not be started even fire detected
by detectors.
EVACUATE
Start the two sounder outputs. Stop by reset.
CONTROL ENABLE
Manual control authorization. In disable mode, only LAMP
TEST and STOP keys can be operated.
OUTPUT SELECTION Switch gas release output between primary and standby.
START
Manual release control button.
STOP
Stop gas release timer (keep remain time on shown). Inhibit gas
output. Stop Sounder2 output.
ISOLATE (ISO1~4) Logically isolate corresponding terminal. Available for Zone1,
Zone2, AUX Zone and Gas Release Output. But ‘ISO4’ is only
functioning for the Automatically Gas Release, the cylinder can
still be discharged manually even it is isolated.
3.1.3 Panel Sound
70~100dB buzzer for local alarm.
Priority
Actions
Sound
Cycle
0
Fire
Start
Stop
Pressure Switch
Evacuate
0.25sON,
0.25sOFF
0.5s
1
Fault
0.5sON,
4.5sOFF
5s
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
8 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
2
Silence
Power ON
Isolate
3.2
0.5sON,
9.5sOFF
0.5sON, OFF
None
10s
Internal Structure
①
②
③
④
⑤
⑥
⑦
⑧
AC transformer: 220-240VAC input, 27VAC output.
Input current fuse of the AC transformer: 1A/250VAC
AC Input: 220VAC input
Main board
Battery: 12VDC 7AH each
Display board
The cylinder output selection switch and manual control enable switch
Buzzer
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
9 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
3.2.1 Main board
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
⑾
Terminals
X5: Discharge remote output mode setting (NO/NC)
X4: Fire remote output mode setting (NO/NC)
X6: Fault remote output mode setting (NO/NC)
X1: Sounder1 output mode setting (Active/NO/NC)
X2: Sounder2 output mode setting (Active/NO/NC)
X3: Cylinder output mode setting (Active/NO/NC)
F5: fuse of cylinder output (active mode)
F4: fuse of sounder2 output (active mode)
F3: fuse of sounder1 output (active mode)
XT1、XT2: battery terminal and AC terminal
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
10 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
⑿
D1: MCU
3.2.2 Display board
①
②
③
④
X1: emergency action mode setting, with delay or without delay
X2: remote discharge output setting, by pressure switch or output action
S1: delay time Setting
S2: cylinder output pulse width setting
4. Terminals & Connections
4.1
Terminals
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
11 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
1. AC220-240V input (L, N)
2. Zone Inputs (Zone 1 +, -, Zone 2 +, -, AUX Zone +, -). Connecting conventional
detectors and manual call points.
3. Emergency Start/Abort Switch (L1, G, L3). Connecting to C-9317.
4. Pressure Switch input (K1, K2). Connecting to cylinder pressure switch. Dry contact
input.
5. Gas Release Output (Primary +, -, Standby +, -). Connecting to primary and
standby cylinder. 2A/24VDC active output. Can be set to NO/NC type. 2 to 45
seconds adjustable pulse output.
6. Sounder Outputs (Sounder 1 +, -, Sounder 2 +, -). Connecting to Audio/Visual
devices. 1A/24VDC active output. Can be set to NO/NC type.
7. Fire (Fire). Fire remote indication output. NO/NC dry contact.
8. Stage 2 (Stage2). Pre-release remote output. NO dry contact.
9. Fault (Fault). Fault remote indication output. NO/NC dry contact.
10. Discharge (Discharge). Gas discharge remote indication output. NO/NC dry contact.
11. AUX Power Supply (AUX+, AUX-). 100mA/24VDC for assistance use.
12. Battery input (Batt+, -). Connecting to internal battery or external battery.
13. AC27V. AC input from transformer.
4.2
Wiring
(1) 1.5mm2 fire cable for Zone, Sounder, Remote Output, Emergency Start/Abort switch and AUX
Power.
(2) 1.5mm2 fire cable for Cylinder Output (Primary & Standby) and Battery connection. If the cable
length is more than 50 meters, 2.5mm2 cable should be used.
4.2.1 Zone connections. For Zone1, Zone2 & AUX Zone
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
12 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
Using Active End of Line unit
Using End of Line resistor
4.2.2 Emergency Start/Abort Switch
4.2.3 Gas release output
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
13 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
4.2.4 Sounder outputs, for Sounder1 & Sounder2.
4.2.5 Remote Outputs are using dry contacts. Simply connect to other systems.
4.3
Typical wiring diagram
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
14 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
15 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
5. Commission tips
5.1
Configure the outputs
The sounder outputs and gas release output are default set at 24VDC Active type.
To meet the condition on site, these outputs can be changed to Normally-Open or
Normally-Close dry contact output. These output types can be configured through
X1、X2、X3、F3、F4、F5 (on the main board ).
X1 and F3 for sounder1. X2 and F4 for sounder2. X3 and F5 for gas release output.
Please refer to the below forms to set X1、X2 or X3.
Note, if configure the output type to Normally-open or Normally-close dry
contact, the current fuse(F3、F4 or F5) must be removed.
5.2
Configure the Emergency Start Switch
Press the emergency Start Switch on field can start the gas release with or without
delay. Short X1 (on the display board) to set with delay and remove the jumper to
set without delay. Default set is with delay.
5.3
Configure the discharge output
The discharge output can be started by pressure switch or directly by gas release
output. Short X2 (on the display board) to set using pressure switch, remove the
jumper to set not using pressure switch (active after gas release output). Default set
is using pressure switch.
5.4
Configure the remote output type
The discharge、fire、fault remote output types can be changed to Normally-Open or
Normally-Close dry contact type through setting X5、X4、X6. X5 for discharge
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
16 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
remote output. X4 for fire remote output. X6 for fault remote output. Please refer to
the below forms to set X4、X5 and X6.
5.5
Set the gas release delay time
The gas release delay time can be set from 0 to 90 seconds by adjusting S1 (on the
display board). Details are shown in the following table. Default set is 30s.
Position of S1
Delay time
5.6
0
0
1
2
3
4
5
6
7
8
9
10 20 30 40 50 60 70 80 90
Set the gas release output pulse width
The gas release output is in pulse type. The pulse width can be set from 2 to 45
seconds by adjusting S2 (on the display board). Details are shown in the following
table. Default set is 5 seconds.
Position of S2
Pulse width
0
2
1
5
2
3
4
5
6
7
8
9
10 15 20 25 30 35 40 45
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
17 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
6. Cause & Effect
The following table shows the actions of the panel under different conditions.
No.
Cause
Effect
1
Zone1 alarm
2
Zone2 alarm
3
AUX Zone alarm
4
Zone1 & Zone2 alarm
5
Emergency Start switch
pressed
6
Start key on panel pressed
7
Emergency Abort Switch
pressed
8
Stop Key on panel pressed
9
Pressure Switch active
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
Sounder1 start immediately
Fire remote output active immediately
Sounder1 start immediately
Fire remote output active immediately
Sounder1 start immediately
Fire remote output active immediately
Sounder1 start immediately
Sounder2 start immediately
Fire remote output active immediately
Stage 2 remote output active immediately
Gas release timer start immediately
Gas release output start after timer finished
If pressure switch is not used, start the discharge
output after the release output started
♦ Sounder1 start immediately
♦ Sounder2 start immediately
♦ Fire remote output active immediately
♦ Stage 2 remote output active immediately
♦ Start the release delay timer or start the gas release
output immediately (select the option by jumper when
commissioning)
♦ If pressure switch is not used, start the discharge
output after the release output started
♦ Sounder1 start immediately
♦ Sounder2 start immediately
♦ Fire remote output active immediately
♦ Gas start immediately without delay
♦ If pressure switch is not used, start the discharge
output after the release output started
During gas delay timing
♦ Stop Sounder2 output.
♦ Stop Timer. Show remaining time.
No gas delay timer
♦ No action
During gas delay timing
♦ Stop Sounder2 output.
♦ Stop Timer. Show remaining time.
No gas delay timer
♦ No action
♦ Start discharge remote output If pressure switch is
used, otherwise it will not be cared.
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
18 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
10
♦
♦
Any Fault
Start Fault Remote output
Light corresponding LED
Note: If the gas release action has finished, the panel will not start timer again.
But it can be started by pressing the ‘START’ key on the panel, the action will be
kept until the pressed key released.
7. Manual Operations
7.1.1 Start gas release from the panel
Press the START button on the panel will start the gas release output without any
delay. This operation is controlled under CONTROL ENABLE switch (by key).
7.1.2 Start gas release on field.
Press the Emergency Start button on field will start the gas release output with or
without delay (configurable). This function is not inhibited by AUTO ENABLE
setting.
7.1.3 Stop gas release from panel
During the gas release delay timer, press the STOP button will stop the timer. The
output terminal will be electronically isolated. This function is not inhibited by AUTO
ENABLE and CONTROL ENABLE setting. Note, if the timer is finished and the
panel is starting the gas release action, the stop operation will not function.
7.1.4 Stop gas release on field
During the gas release delay timer, press the emergency abort switch will stop the
timer. The output terminal will be electronically isolated. This function is not inhibited
by AUTO ENABLE and CONTROL ENABLE setting. Note, if the timer is finished
and the panel is starting the gas release action, the stop operation will not
function.
7.1.5 Silence the ringing bells & alarming panel
Press the SILENCE key to stop sounder outputs and the buzzer in panel. This
operation is controlled under CONTROL ENABLE switch. Note, if the EVACUATE
key is active, the SILENCE key will not act.
7.1.6 Ring the bells
Press EVACUATE key to start the sounder outputs. This operation is controlled
under CONTROL ENABLE switch.
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com
19 of 19
GST301 Gas Release Control Panel
Global System Technology (UK) PLC
The Intelligent Solution
7.1.7 Isolate/De-isolate operation
In case of False-alarm and Fault, if the problem cannot be removed currently, to
avoid false-release and making noise, the faulty zone can be logically isolated. After
solve the problem, De-isolate to resume the functions. The Isolate/De-isolate
operation is available for Zone1, Zone2, AUX Zone and the Gas Release Output.
Press the corresponding ISO (ISO1-4) key to change the isolation condition. This
operation is controlled under CONTROL ENABLE switch.
7.1.8 Switch Standby Cylinder Output
To ensure the fire protection, the field should prepare 2 sets of gas cylinders. In
case of faulty on the primary (discharge, low pressure or other problems), switch
the output to standby terminal. Note, only the circuit on use is monitored.
8. CAUTION
1. If the cylinder’s output or the sounder’s output is set as a Normally-open
or Normally-closed type, the corresponding current fuse must be
removed!
2. ‘ISO4’ operation is only valid for gas release actions caused by
Emergency Start button and detection zones. The START button on the
panel is not under controlled. That means even the output is isolated, it
can still be active by the start button.
So, only when both ‘ISO4’ is active and ‘Control Enable’ is OFF, the gas
release output is completely inhibited.
3. If there is any serious internal error during the self-test, the panel will
show flashing ‘E0’ on the surface and start the fault remote output. In this
case, maintenance must be done.
4. For safety reasons, the panel must be properly grounded.
5. The panel must be maintained or repaired by authorised skilled person.
Global System Technology PLC
London EC1R 3AU England
E-mail: tech.support@gst.uk.com;
www.gst.uk.com