Continuing Education Course #042 "Basic Tools for Electrical Protection and Short Circuit" Test Worksheet 6. The zero sequence vector is normally expressed by: a. Va = 1/3(Va + aVb + a2Vc) b. Vb = 1/3(Va + Vb + Vc) c. none of the above 1. Overcurrent is________. 7. The negative sequence components system. Vector a. the amount of current that flowing in appropriately Va cuts the axis ____ on rotation, then aVc ____ designed equipment will result in loss, damage or both degrees later and then a2Vb ____ degrees later. b. to be in excess of the equipment design and of the a. 120, first, 240 correct design value b. first, 249, 129 c. Both of the above c. first, 120, 240 d. None of the above 8. For transformers, the impedances are the zero, 2. A symmetrical AC is described by a system positive and negative but the ____ sequences are equal. a. with three voltage waveforms of equal magnitude. a. positive and negative b. separated by 90 degrees. b. reactance c. separated by 120 degrees. c. resistance d. a and b e. a and c 9. Three phase core type transformers exhibit zero f. None of the above sequence reactances that are equivalent to a closed delta winding due to its magnetic design are present in 3. The basic principle of symmetrical components three phase_____. method is applied to a. core type transformers a. unbalanced system represented by three phase b. Shell type transformers circuit vectors. c. Saturable reactors b. balanced system of vectors separated by 120 degrees. 10. Normally synchronous rotating equipment, such as c. None of the above generators and synchronous motors specify ______ reactances. 4. The vector “a” can be expressed in the following a. Zero manner: b. Three a. 1|120. c. Positive sequence j90 b. ε . c. 1+j45. 11. ____ allows highest initial fault current value. a. High speed relay 5. We can represent any three vector system by three b. Low speed relay vectors systems that are _______in magnitude and c. Subtransient reactance separated by either 120° or Zero. a. zero 12. For a synchronous generator the ____ is the b. equal reactance value after about 0.1 s of the start of a fault. c. different a. transient reactance b. subtransient reactance c. synchronous reactance 13. The _____ relay provides protection for large generators as well as smaller generators in back up units, such as in peaking plants. a. Positive sequence b. Zero sequence c. Negative-sequence 20. If the Base KVA of a system is 4000 KVA, the base voltage is 100 V and the impedance of the equivalent impedance at the short circuit point is 5.0 ohm at an angle of 36.8699 degrees, the p.u. value of its reactance is _______. a. 0.0001 b. 0.0012 14. _____ will permit the protection engineer to set the c. 0.0005 protective devices as well as evaluate the proper settings of electrical equipment. 21. The most common per unit values chosen as base a. ANSI Standard C38.010-1979 are the _________. b. IEEE 323 a. base Voltage and the base KVA c. Short circuit calculations b. base impedance and the current c. none of the above 15. For high voltage (above 600V) breakers, the ratings use _______ current values based on ANSI 22. In a 1000 KVA transformer with an impedance of Standard C37.5-1979. 8.5% it is to be converted to a 20000 KVA base, the a. Asymmetrical per unit value of the reactance is (assuming zero b. Symmetrical resistance): c. Zero sequence a. 0.044 b. 0.17 16. The per unit value of a voltage in a system is the c. 0.055 ratio of the voltage to the ____ voltage. a. Design 23. A 500 HP induction motor has an approximate b. Equivalent KVA of: c. Base a. 450 b. 475 17. The value used for impedance in the sources is the c. 500 _____ Reactance "X". a. Subtransient 24. In order to perform coordination between b. Transient protection devices, the curve of the device that trips c. Zero first must be located _____ the curve used by the next tripping device. 18. If the base voltage for a system is 69000 V and the a. to the Left of voltage at a motor in the HV MCC is 13.8 kV. The p.u. b. to the Right of value of the voltage at the motor is_____. c. Intercepting a. 0.100 b. 0.300 25. The main purpose of coordination is to ______ the c. 0.200 fault area without interruption of service or power to the rest of the components of the system. 19. The resistance in a transformer can be normally a. isolate _____in short-circuit calculations. b. modify a. neglected c. coordinate b. added to the reactance c. set to j0.45