ECE 421: Introduction to Power Systems Session 14; Page 1/13 Fall 2013 ECE 421: Per Unit Examples Define units: MVA 1000kW kVA kW MW MVA kVAR kW pu 1 Example 1: A three-phase transformer rated 5 MVA, 115/13.2 kV has per-phase series impedance of (0.007 + j0.075) per unit. The transformer is connected to a short distribution line which can be represented by a series impedance per phase of (0.02 + j0.10) per unit on a base of 10 MVA, 13.2 kV. The line supplies a balanced three-phase load rated 4MVA, 13.2kV, with lagging power factor 0.85. Srated 5MVA Vhi 115kV Vlo 13.2kV 2 Zbase_Hi Vhi Zbase_Hi 2645 Ω Srated 2 Zbase_Lo Vlo Zbase_Lo 34.848 Ω Srated Zseries 0.007pu j 0.075pu Distribution line: Load: on transformer rating base. Zline 0.02pu j 0.10pu Sload 4MVA VLL_load 13.2kV on 10MVA, 13.2kV base pf 0.85 lagging (a) Draw an equivalent circuit of the system indicating all impedances in per unit. Choose 10MVA, 13.2 kV as the base of the load. 2 VBLL SB 10MVA VBLL 13.2kV ZB ZB 17.424 Ω SB ECE 421: Introduction to Power Systems Session 14; Page 2/13 Fall 2013 Transformer impedance (change of base calculation): 2 Vlo SB Zseries_new Zseries VBLL Srated Zseries_new ( 0.014 0.15i) pu Line impedance (no change of base needed, already on the correct base) Zline ( 0.02 0.1i) pu Load: ϕload acos ( pf ) ϕload 31.788 deg VLL_load 2 j ϕload Zload Sload e Zload_pu positive since lagging power factor Zload ( 37.026 22.947i) Ω Zload Zload_pu 2.125 1.317i ZB Per unit equivalent circuit: Iload 0.014 + j 0.15 p.u. Load Vs = 1.0 p.u. Line Impedance 2.125 + j 1.317 p.u. Transformer 0.02 + j 0.1 p.u. ECE 421: Introduction to Power Systems Session 14; Page 3/13 Fall 2013 (b) With the voltage at the primary side of the transformer held constant at 115kV, the load at the receiving end of the line is disconnected. Find the voltage regulation at the load. Vsource 115kV Vsource_pu Iload LL Vsource Vhi Vsource_pu 1 pu Vsource_pu Zseries_new Zline Zload_pu Iload 0.375 pu Vload_pu Iload Zload_pu Vload_pu 0.937 pu Vregulation Use as reference angle (so 0 deg) Iload ( 0.303 0.22i) pu arg Iload 35.971 deg Vload_pu ( 0.935 0.068i) pu arg Vload_pu 4.183 deg Vsource_pu Vload_pu Vload_pu Vregulation 6.708 % ECE 421: Introduction to Power Systems Session 14; Page 4/13 Fall 2013 Example 2: A transformer rated 200 MVA, 345 Y/20.5 kV connects a balanced load rated 180 MVA, 22.5kV, 0.8 power-factor lag to a transmission line. Determine: Sr 200MVA VHI 345kV VLO 20.5kV Sload 180MVA Vload 22.5kV pf 0.8 lag (a) The rating of each of the three single phase transformers which when properly connected will be equivalent to the above three-phase transformer. Vrating_xfmr_HV VHI 3 Vrating_xfmr_LV VLO Sper_xfmr Sr 3 Vrating_xfmr_HV 199.186 kV Vrating_xfmr_LV 20.5 kV Sper_xfmr 66.667 MVA (b) The complex impedance of the load in per unit in the impedance diagram if the base in the transmission line is 100MVA, 345kV. ϕload acos ( 0.8) ϕload 36.87 deg Vload2 j ϕload Zload_ohm_LV Sload e Zload_ohm_LV 2.812 Ω arg Zload_ohm_LV 36.87 deg SBASE 100MVA ECE 421: Introduction to Power Systems Session 14; Page 5/13 Fall 2013 VBHI 345kV VLO VHI VBLV VBHI VBLV 20.5 kV 2 ZBLV VBLV ZBLV 4.202 Ω SBASE Zload_pu Zload_ohm_LV Zload_pu ( 0.535 0.402i) pu ZBLV arg Zload_pu 36.87 deg Zload_pu 0.669 pu Example 3: Sketch a per unit impedance diagram for the system shown below. Use a 100MVA impedance base, and the generator 1 rated voltage as your reference voltage base. Use pi models for the lines. BUS 1 G1 BUS 2 T1 BUS 3 BUS 4 Line 2 Line 1 BUS 5 T2 G2 Load G1: 50MVA, 13.8kV G2: 20MVA, 14.4kV T1: 40MVA, -Y, 13.2:161kV, X = 10% T2: 25MVA, Y-, 161kV:13.2kV, X = 10% Load: 45MVA, 0.8pf lagging (Y connected, parallel impedances) Line 1: 100 mile, Z = 0.28 + j0.73 ohm/mi, Y = 5.9*10-6 mho/mi Line 2: 75 mile, Z = 0.28 + j0.73 ohm/mi, Y = 5.9*10-6 mho/mi ECE 421: Introduction to Power Systems Define Base Quantities: Session 14; Page 6/13 Fall 2013 Section I (left of T1) SB 100MVA VB1 13.8kV Line to line voltage 2 ZB1 IB1 VB1 SB SB 3 VB1 Section II (between T1 and T2) 161kV 13.2kV VB2 VB1 ZB1 1.904 Ω IB1 4183.698 A Section II (right of T2) VB2 168.318 kV 13.2kV 161kV VB3 VB2 2 ZB2 IB2 VB2 SB SB 3 VB2 VB3 13.8 kV 2 ZB2 283.31 Ω IB2 343.011 A ZB3 IB3 VB3 SB SB 3 VB3 ZB3 1.904 Ω IB3 4183.698 A ECE 421: Introduction to Power Systems Session 14; Page 7/13 Fall 2013 Transmission Line Models: Line 1: Length1 100mi Zline1 ( 0.28 j 0.73) 6 mho Yline1 j 5.9 10 mi ohm Length1 mi Zline1 ( 28 73i) ohm Length1 Yline1 5.9i 10 4 mho Yline1 2 4 2.95i 10 mho Line 1 is in section II, so use Zbase2 Zline1pu Zline1 Zline1pu ( 0.099 0.258i) pu ZB2 Note that Ybase is 1/Zbase: Yline1pu Yline1 ZB2 Yline1pu 0.167i pu We actually need Y/2 for the pi model: Yline1pi Yline1pu Yline1pi 0.084i pu 2 Line 2: length2 75mi ohm Zline2 ( 0.28 j 0.73) length2 mi 6 mho Yline2 j 5.9 10 mi length2 Zline2 ( 21 54.75i) ohm 4 Yline2 4.425i 10 mho Yline2 2 4 2.212i 10 mho ECE 421: Introduction to Power Systems Session 14; Page 8/13 Fall 2013 Line 2 is also in section II, so use Zbase2 Zline2pu Zline2 Zline2pu ( 0.074 0.193i) pu ZB2 Yline2pu Yline2 ZB2 Yline2pu 0.125i pu We actually need Y/2 for the pi model: Yline2pi Yline2pu Yline2pi 0.0627i pu 2 Transformer Model Calculations Transformer 1: ST1 40MVA VT1Low 13.2kV VT1hi 161kV XT1 0.10pu Impedance change of base calculation VT1Low XT1new XT1 VB1 2 SB ST1 XT1new 0.229 pu Transformer 2: ST2 25MVA VT2Low 13.2kV VT2hi 161kV Impedance change of base calculation 2 VT2Low SB XT2new XT2 VB3 ST2 XT2new 0.366 pu XT2 0.10pu ECE 421: Introduction to Power Systems Session 14; Page 9/13 Fall 2013 Load Model magSload 45MVA pfload 0.8 Vloadrated 161kV lagging ϕload acos ( pfload) ϕload 36.87 deg j ϕload Sload magSload e Sload ( 36 27i) MVA Since the load is wye connected with parallel impedances: Rload Vloadrated Re Sload 2 Rload 720.028 Ω Xload Vloadrated Im Sload 2 Xload 960.037 Ω As a check: Zequivload 1 1 Rload j Xload 1 Zequivload 576.022 Ω arg Zequivload 36.87 deg Zequivload ( 460.818 345.613i) Ω Scheck Vloadrated Zequivload 2 Scheck ( 36 27i) MVA note complex conjugate in equation Convert to per unit (load in section II): Rloadpu Rload ZB2 Rloadpu 2.541 pu Xloadpu Xload ZB2 Xloadpu 3.389 pu ECE 421: Introduction to Power Systems Session 14; Page 10/13 Fall 2013 Per Unit Equivalent Circuit: j0.229pu 0.099 + j 0.258 pu Y/2=j 0.084 pu 2.54 pu Ea1 Line 1 j 3.39pu Transformer1 0.074 + j 0.193 pu Load Line 2 Y/2=j 0.0627 pu j0.366pu Transformer2 Ea2 Generator2 Generator1 (b) Suppose G1 is operating at 13.6kV and G2 is set to operate at the same magnitude. Suppose also, that the two generators are in phase with each other. Determine the phase A line to neutral voltage in Volts and in per unit and the phase A current at the load in Amperes and in per unit. Determine magnitude and phase is each case. Use the generator 1 voltage as your reference angle. Create a Thevenin equivalent circuit looking back to the two sources from the load: Circuit to left of the load: Zleft j XT1new Zline1pu Zleft ( 0.099 0.486i) pu 13.6kV j 0deg Vgen1pu e VB1 Vgen1pu 0.986 pu Create a Norton equivalent: Ileft Vgen1pu Zleft Ileft 1.986 arg Ileft 78.514 deg ECE 421: Introduction to Power Systems Session 14; Page 11/13 Fall 2013 Circuit to right of load: Zright j XT2new Zline2pu Zright ( 0.074 0.559i) pu 13.6kV j 0deg Vgen2pu e VB3 Vgen2pu 0.986 pu Vload 2.54 pu Zleft j 3.39pu Ea Zleft Ea Zright Zright Zleft Zright Vload ( Ea Zleft E + Za ) Zleft Zright right Create a Norton equivalent: Iright Vgen2pu Zright Iright 1.747 arg Iright 82.45 deg 2.54 pu Zleft Zright j 3.39pu right 2.54 pu E + Za j 3.39pu Ea Zleft Vload ECE 421: Introduction to Power Systems Session 14; Page 12/13 Fall 2013 Combine the two parallel impedances from the sources: 1 1 Zpara Zleft Zright 1 Zpara 0.264 arg Zpara 80.356 deg Combine the two current sources: Ipara Ileft Iright arg Ipara 80.356 deg Ipara 3.73 Find the Thevenin equivalent source voltage: Vthev Ipara Zpara Vthev 0.986 pu Zthev Zpara Zloadequiv 1 1 Rloadpu j Xloadpu Now we can find the load current: Iloadpu Vthev Zthev Zloadequiv 1 Zloadequiv 2.033 pu arg Zloadequiv 36.87 deg Zloadequiv 1.627 1.22i Iloadpu 0.441 pu arg Iloadpu 41.542 deg Vloadpu 0.898 pu arg Vloadpu 4.672 deg And the voltage across the load: Vloadpu Iloadpu Zloadequiv ECE 421: Introduction to Power Systems Session 14; Page 13/13 Fall 2013 Now convert to Ampere and Volts: IloadAmps Iloadpu IB2 arg IloadAmps 41.542 deg IloadAmps 151.433 A VANload Vloadpu VB2 Note that we are using a line to neutral voltage base, since the angles in per unit correspond to the line to neutral voltages. 3 VANload 87.229 kV VABload arg VANload 4.672 deg j 30deg 3 VANload e VABload 151.084 kV arg VABload 25.328 deg