Medium Voltage Distribution Application Catalogue A tool for all MV equipment designers May 2008 Application Catalogue A tool for all MV equipment designers Contents Presentation General 4 User guide 5 Selection tables 6 Application DEAI06EN.indd Substation feeder 10 Substation incomer 12 Bus tie 14 Bus riser 16 Busbar VT’s 17 Transformer feeder 18 Transformer incomer 22 Motor feeder 24 Generator incomer 26 3 Presentation General The Medium Voltage Application Catalogue is a tool for all Medium Voltage equipment designers. Purpose b To help you produce Medium Voltage switchgear assemblies which include Schneider Electric components b To help you specify standard solutions. How? By offering you standard applications for the protection of different Medium Voltage network configurations. By providing you with a guarantee of the full protection chain composed of different Schneider Electric components. b With specification of the equipment required for each standard application b And the complete wiring diagram of the Medium Voltage equipment for each application. 4 DEAI06EN.indd Presentation User guide Step 1: Selection table Using the selection table, you select your application from the different standard applications offered: b Based on the network component to be protected: substation incomer or feeder, transformer, motor or generator b Based on the formulated protection, metering and monitoring requirements The application chosen from the selection table is detailed in the application pages. Step 2: Application page Each standard application is presented in a page which includes: b A single-line diagram of the application, with the different components to be combined: v Switching device v Measurement sensors v Protection unit v Details of the functions offered by the protection unit: v Protection functions v Monitoring and control functions b Optional functions available b Reference of the complete wiring diagram for the application. Step 3: Wiring diagrams A diagram library on CD-ROM contains the wiring diagrams, in AutoCad format, of all the standard applications offered. Each diagram: b Corresponds to a standard application b Contains all the information required for the complete wiring, power and control current, of the Medium Voltage equipment b May be easily adapted by you to match the options you choose and your particular needs. DEAI06EN.indd 5 Presentation Selection tables Application Line or substation Feeder Protection and control type Page No. Sepam series 20 Sepam series 40 NEX 17.5 kV diagram 5130… NEX 24 kV diagram 5130… S1 10 S20 Protection function ANSI code Phase overcurrent 50/51 Voltage-restrained phase overcurrent 50V/51V Earth fault, 50N/51N sensitive earth fault 50G/51G Breaker failure 50BF Negative sequence/unbalance 46 Directional phase overcurrent 67 Directional earth fault 67N/67NC Directional active overpower 32P Directional reactive overpower 32Q/40 Thermal overload 49RMS Phase undercurrent 37 Excessive starting time, locked rotor 48/51LR/14 Starts per hour 66 Positive sequence undervoltage 27D Remanent undervoltage 27R Undervoltage 27/27S Overvoltage 59 Neutral voltage displacement 59N Negative sequence overvoltage 47 Overfrequency 81H Underfrequency 81L Rate of change of frequency 81R Recloser (4 cycles) 79 Temperature monitoring (8 to 16 RTDs, 2 set points per RTD) 38/49T Thermostat/Buchholz/DGPT Measurement and diagnostic Phase current I1; I2; I3 RMS, residual current I0 Average current I1; I2; I3; peak demand current IM1, IM2, IM3 Voltage U21; U32; U13; V1; V2; V3; residual voltage V0 Positive sequence voltage Vd/rotation direction; neg. seq. voltage Vi (only S40) Frequency Active; reactive and apparent power P. Q. S Peak demand power PM. QM Power factor Calculated active and reactive energy ( +/-W.h. +/- var.h) Active and reactive energy by pulse counting ( +/-W.h. +/- var.h) Temperature Network and machine diagnosis Tripping context Tripping current Trip1; Trip2; Trip3; Trip0 Unbalance ratio/negative sequence current Ii Phase displacement ϕ0; ϕ1; ϕ2; ϕ3 Disturbance recording Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter/operating time Start current and time Start inhibit time delay, number of starts before inhibition Incomer S2 11 S2 11 S2 11 S3 12 S3 12 S3 12 S4 13 S20 7350 7373 S40 7356 7378 S41 7358 S42 7360 S40 7357 7379 S41 7359 S42 7361 b b b b b b b b b b b b b b b b b b b b b b b b b b b (1) b b b (1) b b (1) b b b b b b b b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b b b b b b b b b b b b b b b b v v v v b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b v (1) b v (1) b v (1) b v (1) b v (1) b v (1) b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b 7374 b v b b b Standard v According to parameter setting and MES module or MET module (1) Not used in schematic diagram 6 DEAI06EN.indd Bus tie S5 14 S20 S6 15 Bus riser Busbar VT’s Transformer Feeder B2 16 B22 B1 17 B21 B1 17 B22 T1 18 T20 T2 19 T20 7354 7355 7370 7351 7375 Motor Feeder Generator Incomer G1 26 T3 20 T3 20 T6 21 T4 22 T4 22 T5 23 T5 23 M1 24 T40 7362 7380 T42 7365 T40 7352 7376 T42 7366 T40 7364 7383 T42 7367 M41 7353 7368 7382 T40 7363 7381 S40 7371 Incomer M2 25 M20 G40 7369 7372 7377 b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b (1) b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) b b b (1) b (1) b (1) b (1) v v v v v v v v v v b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b v (1) b v (1) v (1) b v (1) v (1) b v (1) v (1) b v (1) v (1) b v (1) v (1) b v (1) v (1) b v (1) v b v (1) v b v (1) v b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b (1) b (1) b (1) b (1) b b b b b b b b b b b b b b (1) b b b v b b b b b b b b b b b b b b b b b b b b b DEAI06EN.indd b b b b v b b b b v v b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b (1) b b b b b b b b b b b b b b b b b (1) b (1) v b b b b b b 7 Presentation Selection tables (cont.) Application Line or substation Feeder Protection and control type Page No. Sepam series 20 Sepam series 40 NEX 17.5 kV diagram 5130… NEX 24 kV diagram 5130… S1 10 S20 Switchgear diagnostic Cumulative breaking current Trip circuit supervision Number of operations, operating time, charging time CT/VT supervision Control and monitoring Circuit breaker/contactor control Latching/acknowledgment Logic discrimination Switching of groups of settings Logic equation editor Optional features 8 temperature sensor inputs - MET148-2 module 1 low level analog output - MSA141 module Logic inputs/outputs - MES114 (10I/4O) module RS485 interface - ACE949-2 (2-wire) or ACE959 (4-wire) module Test box Local remote/switch CT’s option LPCT sensors Core balance CT Incomer S2 11 S2 11 S2 11 S3 12 S3 12 S3 12 S40 7356 7378 S41 7358 S42 7360 S40 7357 7379 S41 7359 S42 7361 b v v b v v b b v v b b v v b b v v b b v v b b v v b b v v v b v b (1) v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) v v v b b b v v v b b b v v v b b b v v v b b b v v v b b b v v v b b b v v v b b b v v v b b b b v b v b v b v b v b v b v b v 7350 7373 S4 13 S20 7374 ANSI code 60FL 94/69 86 68 b Standard v According to parameter setting and MES module or MET module (1) Not used in schematic diagram 8 DEAI06EN.indd Bus tie S5 14 S20 S6 15 Bus riser Busbar VT’s Transformer Feeder B2 16 B22 B1 17 B21 B1 17 B22 T1 18 T20 T2 19 T20 7354 7355 7370 7351 7375 7352 7376 7377 b v v b v v b b v v v b v b (1) 7371 v (1) v (1) v (1) v b v b (1) b v (1) b v (1) b v (1) b v v v b b v v v b b v v v b v v v b v v v b b b DEAI06EN.indd Motor Feeder Generator Incomer G1 26 T3 20 T3 20 T6 21 T4 22 T4 22 T5 23 T5 23 M1 24 T40 7362 7380 T42 7365 T40 T42 7366 T40 7364 7383 T42 7367 M41 7353 7382 T40 7363 7381 b v v b v v b b v v b b v v b b v v b b v v b b v v b b v v b v b v b (1) v b v b (1) v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) b v b v b (1) b v v v v b b v (1) v v v b b v (1) v v v b b v (1) v v v b b v v v v b b v (1) v v v b b v (1) v v v b b b b b b b b b b b b b b b b S40 7372 Incomer M2 25 M20 7368 G40 7369 b v v b v v b b v v b v b v b (1) b v b v b (1) v b v b (1) b v b v b (1) b v v v v b b v v v v b b v v v v b b v v v v b b v v v v b b b b b b b b b b b b 9 Substation feeder S1 b Protection against phase to phase and phase to earth short circuits b Detecting of unbalanced power supplied b Recloser b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection DE56380 Application Trip/close(1) 50/51 50N/51N 46 A MD 86 74 30 79(1) 68 Sepam S20 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 46: negative sequence overcurrent. Measurement and diagnostic Sepam S20, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Disturbance recording. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam S20 Analog Output Remote UMI Modbus RS485 Substation feeder S1 (1) Close by communication and recloser (2) O11 reserved for closing order Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Logic discrimination block receive External tripping Trip circuit supervision (74) Fault and alarm contact (O11(2) to O14) Recloser 4 cycles (79) External network time synchronization External trip Local/remote control selection Inhibition recloser Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch b Logic inputs and outputs module MES114 (10I/4O). 10 DEAI06EN.indd DE56385 Application Substation feeder S2 b Protection against phase to phase and phase to earth short circuits b Detecting of unbalanced power supplied b Recloser b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic To Busbar VT’s 50/51 50N/51N 50BF Open/close 46 trip 67N/67NC(1) 27/27S 59 A 94 V 69 F 86 MD 74 KW 30 KVAR 68 KVA 60LF PF 79 KW.h KVar.h Analog Output Remote UMI Modbus RS485 Substation feeder S2 Protection Sepam S40/S41/S42 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings) b 67N/67NC: directional earth fault (1) - IDMT, DT (2 settings) b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings). (1) On Sepam S41 and S42 (2) O11 reserved for closing order DEAI06EN.indd Sepam S40/S41/S42, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam S40/S41/S42 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive Bl1 CB closing order Fault and alarm contact (O11(2) to O14) Recloser 4 cycles (79) CB opening order Inhibit closing External tripping Local/remote control selection Inhibition recloser External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. 11 Substation incomer S3 b Protection against phase to phase and phase to earth short circuits b Detecting of unbalanced power supplied b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic DE56386 Application Modbus RS485 Remote UMI Analog Output 50/51 A 94 50N/51N V 69 F 86 50BF 46 MD 74 KW 30 67(1) 67N/67NC(2) KVAR 68 32P KVA 60LF 27/27S PF 59 KW.h 59N KVar.h 47 Open/close 81H 81L trip Substation incomer S3 Protection Sepam S40/S41/S42 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings) b 67: directional phase overcurrent (1) - IDMT, DT (2 settings) b 67N/67NC: directional earth fault (2) - IDMT, DT (2 settings) b 32P: directional active overpower (2) b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings) b 47: negative sequence overvoltage b 81H: overfrequency (2 settings) b 81L: underfrequency (4 settings). Sepam S40/S41/S42, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage : V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam S40/S41/S42 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive Bl1 CB closing order Fault and alarm contact (O11(3) to O14) CB opening order Inhibit closing External tripping Local/remote control selection External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. (1) On Sepam S42 only (2) On Sepam S41 and S42 (3) O11 reserved for closing order 12 DEAI06EN.indd Substation incomer S4 b Protection against phase to phase and phase to earth short circuits b Detecting of unbalanced power supplied b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection DE56381 Application Modbus RS485 Remote UMI Substation incomer S4 (1) Close by communication and recloser (2) O11 reserved for closing order Sepam S20, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Disturbance recording. A MD Open/close trip Measurement and diagnostic CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Analog Output 50/51 50N/51N Sepam S20 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 46: negative sequence overcurrent. 86 74 30 68 Control Sepam S20 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Logic discrimination block receive External tripping Trip circuit supervision (74) Fault and alarm contact (O11(2) to O14) External network time synchronization External trip Local/remote control selection Inhibition recloser Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch b Logic inputs and outputs module MES114 (10I/4O). DEAI06EN.indd 13 Bus tie S5 b Protection against phase to phase and phase to earth short circuits b Detecting of unbalanced power supplied b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection DE56382 Application Trip/close(1) 50/51 50N/51N A MD 86 74 30 68 Sepam S20 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 46: negative sequence overcurrent. Measurement and diagnostic Sepam S20, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Disturbance recording. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam S20 Analog Output Remote UMI Modbus RS485 Bus tie S5 (1) Close by communication and recloser (2) O11 reserved for closing order Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Logic discrimination block receive External tripping Trip circuit supervision (74) Fault and alarm contact (O11(2) to O14) External network time synchronization External trip Local/remote control selection Inhibition recloser Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch b Logic inputs and outputs module MES114 (10I/4O). 14 DEAI06EN.indd DE56383 Application Bus tie S6 b Protection against phase to phase and phase to earth short circuits b Detecting of unbalanced power supplied b Recloser b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection To Busbar VT’s 50/51 50N/51N 50BF Open/close 46 (1) trip A 94 V 69 F 86 MD 74 KW 30 KVAR 68 KVA 60LF PF KW.h KVar.h Sepam S40 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings). Measurement and diagnostic Sepam S40, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Analog Output Remote UMI Modbus RS485 Bus tie S6 (1) Close by communication (2) O11 reserved for closing order Control Sepam S40 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive Bl1 CB closing order Fault and alarm contact (O11(2) to O14) CB opening order Inhibit closing External tripping Local/remote control selection Inhibition recloser External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. DEAI06EN.indd 15 Application Bus riser B2 b Detecting of variation in network voltage or frequency b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection Sepam B22 b 27D/47: positive sequence undervoltage (2 sets) b 27R: remanent undervoltage b 27: phase to phase undervoltage (2 sets) b 27S: phase to neutral undervoltage b 59: phase to phase overvoltage (2 sets) b 59N: neutral voltage displacement (2 sets) b 81H: overfrequency b 81L: underfrequency (2 sets) b 81R: rate of change of frequency (B22 only). DE56384 Measurement and diagnostic 27D/47 27R 27 27S 59 59N 81L 81H 81R (B22) Analog Output Remote UMI Modbus RS485 Bus riser B2 V F 86 30 Sepam B22, LCD display LED (Light Emitting Diode) b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Disturbance recording. Control Sepam B22 Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) Fault and alarm contact (O11 to O14) External network time synchronization Basic apparatus b b b b b MES114 module (10 I/4 O) b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Logic inputs and outputs module MES114 (10I/4O). 16 DEAI06EN.indd Application Busbar VT’s B1 b Detecting of variation in network voltage or frequency b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection Sepam B21/B22 b 27D/47: positive sequence undervoltage (2 sets) b 27R: remanent undervoltage b 27: phase to phase undervoltage (2 sets) b 27S: phase to neutral undervoltage b 59: phase to phase overvoltage (2 sets) b 59N: neutral voltage displacement (2 sets) b 81H: overfrequency b 81L: underfrequency (2 sets) b 81R: rate of change of frequency (B22 only). DE56387 Measurement and diagnostic 27D/47 27R 27 27S 59 59N 81L 81H 81R (B22) Analog Output Remote UMI Modbus RS485 Busbar VT’s B1 V F 86 30 Sepam B21/B22, LCD display LED (Light Emitting Diode) b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Disturbance recording. Control Sepam B21/B22 Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) Fault and alarm contact (O11 to O14) External network time synchronization Basic apparatus b b b b b MES114 module (10 I/4 O) b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Logic inputs and outputs module MES114 (10I/4O). DEAI06EN.indd 17 Transformer feeder T1 b Protection against internal faults and overload protection b It also monitors the winding temperature by probes providing local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection DE56388 Application Trip/close(1) A MD Temp 86 74 30 68 Inter trip 50/51 50N/51N 49RMS 38/49T Temp Sensor Analog Output Remote UMI Modbus RS485 Transformer feeder T1 (1) Close by communication (2) O11 reserved for closing order Sepam T20 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 46: negative sequence overcurrent b 49RMS: thermal overload (2 settings) b 38/49T: temperature monitoring (2 settings/probe). Measurement and diagnostic Sepam T20, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Temperature measurement b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam T20 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Logic discrimination block receive External tripping Trip circuit supervision (74) Fault and alarm contact (O11(2) to O14) Local/remote control selection Inhibition thermal overload Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b 8 temperature sensor inputs (38/49T) MET148-2 module b Logic inputs and outputs module MES114 (10I/4O) b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. 18 DEAI06EN.indd Transformer feeder T2 b Protection against internal faults and overload protection b It also monitors the winding temperature and Buchholz providing local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection DE56389 Application Trip/close(1) A MD 86 74 30 68 Inter trip 50/51 50N/51N 49RMS Thermos Buchholz Sepam T20 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 46: negative sequence overcurrent b 49RMS: thermal overload (2 settings) b Thermostat/Buchholz. Measurement and diagnostic Sepam T20, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam T20 Analog Output Remote UMI Modbus RS485 Transformer feeder T2 (1) Close by communication (2) O11 reserved for closing order Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Logic discrimination block receive External tripping Trip circuit supervision (74) Fault and alarm contact (O11(2) to O14) External tripping (Buchholz) External tripping (Winding temperature) Buchholz alarm Winding temperature alarm Local/remote control selection Inhibition thermal overload Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Logic inputs and outputs module MES114 (10I/4O) b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. DEAI06EN.indd 19 Transformer feeder T3 b Protection against internal faults and overload protection b It also monitors pressure device providing local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic DE56390 Application To Busbar VT’s 67N/67NC(1) 49RMS 27/27S 59 A 94 V 69 F 86 MD 74 KW 30 KVAR 68 KVA 60LF PF KW.h KVar.h DGPT2 CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Inter trip 50/51 50N/51N 50BF Open/close 46 trip Sepam T40 or T42, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Running hours counter/Operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Tripping context. Control Sepam T40 or T42 Analog Output Remote UMI Modbus RS485 Transformer feeder T3 Protection Sepam T40 or T42 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings) b 67: directional phase overcurrent (1) - IDMT, DT (2 settings) b 67N/67NC: directional earth fault (1) - IDMT, DT (2 settings) b 49RMS: thermal overload (2 settings) b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings). Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive BI1 CB closing order Fault and alarm contact (O11(2) to O14) CB opening order Pressure alarm Pressure tripping Thermostat alarm Thermostat tripping External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. (1) On Sepam T42 only (2) O11 reserved for closing order 20 DEAI06EN.indd Transformer feeder T6 b Protection against internal faults and overload protection b It also monitors the windings by probes providing device local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic To Busbar VT’s 50/51 50N/51N 50BF Open/close 46 trip 67N/67NC(1) 49RMS 27/27S 59 A 94 V 69 F 86 MD 74 KW 30 KVAR 68 KVA 60LF PF KW.h KVar.h DGPT2 Sepam T40, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Inter trip DE56390 Application Control Sepam T40 Analog Output Remote UMI Modbus RS485 Transformer feeder T6 Protection Sepam T40 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings) b 67: directional phase overcurrent (1) - IDMT, DT (2 settings) b 67N/67NC: directional earth fault (1) - IDMT, DT (2 settings) b 49RMS: thermal overload (2 settings) b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings) b 38/49T: temperature monitoring. (1) On Sepam T42 only (2) O11 reserved for closing order DEAI06EN.indd Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive BI1 CB closing order Fault and alarm contact (O11(2) to O14) CB opening order Pressure alarm Pressure tripping Thermostat alarm Thermostat tripping External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b 8 temperature sensor inputs (38/49T) MET148-2 module b Remote advanced UMI user machine interface (type DSM303) b Test box b Local/remote switch. 21 Transformer incomer T4 b Protection against internal faults and overload protection b It also monitors the winding temperature and Buchholz device providing local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic DE56391 Application Modbus RS485 Remote UMI 50/51 A 94 50N/51N V 69 F 86 50BF 46 MD 74 KW 30 67(1) 67N/67NC(1) KVAR 68 49RMS KVA 60LF 27/27S PF 59 KW.h 59N KVar.h Thermost Open/close Buchholz trip Transformer feeder T4 Protection Sepam T40 or T42 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings) b 67: directional phase overcurrent (1) - IDMT, DT (2 settings) b 67N/67NC: directional earth fault (1) - IDMT, DT (2 settings) b 49RMS: thermal overload (2 settings) b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings). Inter trip Analog Output Sepam T40 or T42, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Running hours counter/Operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam T40 or T42 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive BI1 CB closing order Fault and alarm contact (O11(2) to O14) CB opening order Buchholz alarm Buchholz tripping Thermostat alarm Thermostat tripping External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b Remote advanced UMI user machine interface (type DSM303) b Test box b Local/remote switch. (1) On Sepam T42 only (2) O11 reserved for closing order 22 DEAI06EN.indd Transformer incomer T5 b Protection against internal faults and overload protection b It also monitors the winding by probes providing device local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic DE56392 Application Modbus RS485 Remote UMI Analog Output 50/51 50N/51N 50BF 46 67(1) 67N/67NC(1) 49RMS 27/27S 59 59N 38/49T A 94 V 69 F 86 MD 74 KW 30 KVAR 68 KVA 60LF PF KW.h KVar.h Temp Open/close trip Transformer feeder T5 Protection Sepam T40 or T42 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent - IDMT, DT (2 settings) b 67: directional phase overcurrent - IDMT, DT (2 settings) b 67N/67NC: directional earth fault - IDMT, DT (2 settings) b 49RMS: thermal overload (2 settings) b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings) b 38/49T: temperature monitoring. (1) O11 reserved for closing order DEAI06EN.indd Inter trip Temp Sensor Sepam T40 or T42, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam T40 or T42 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive BI1 CB closing order Fault and alarm contact (O11(1) to O14) CB opening order Inhibit closing External tripping Local/remote control selection Inhibition thermal overload External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b 8 temperature sensor inputs (38/49T) MET148-2 module b Remote advanced UMI user machine interface (type DSM303) b Test box b Local/remote switch. 23 Motor feeder M1 b Protection against internal faults and loads faults b Monitoring of motor starting conditions and winding temperature by probes providing local and remote indication of operation b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection DE56393 Application Trip/close(1) 50/51 A 50N/51N MD 49RMS Temp 46 37 48/51LR/14 66 38/49T M Temp Sensor 86 74 30 68 Sepam M20 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 46: negative sequence overcurrent b 49RMS: thermal overload (2 settings) b 37: undercurrent b 48/51LR: exces. start. time, locked rotor b 66: starts per hour b 38/49T: temperature monitoring. Measurement and diagnostic Sepam M20, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Temperature measurement b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Starting current and time/overload b Start inhibit time delay/numb. start before inhibition. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Analog Output Remote UMI Modbus RS485 Motor feeder M1 (1) Close by communication (2) O11 reserved for closing order Control Sepam M20 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time External trip Trip circuit supervision (74) Fault and alarm contact (O11(2) to O14) Motor reacceleration Motor shaft rotation Local/remote control selection Inhibition thermal overload External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b 8 temperature sensor inputs (38/49T) MET148-2 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch b Logic inputs and outputs module MES114 (10I/4O). 24 DEAI06EN.indd Motor feeder M2 b Protection against internal faults, network related and loads faults b Monitoring of motor starting conditions and the winding temperature b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic DE56394 Application To Busbar VT’s 50/51 A 94 50N/51N V 69 50BF F 86 46 MD 74 KW 30 Open/close 67N/67NC 32P KVAR 68 trip 32Q/40 KVA 60LF 49RMS PF 37 KW.h 48/51LR/14 KVar.h 66 Temp 27D 27R 27/27S 59 59N 47 38/49T M Temp Sensor Analog Output Remote UMI Modbus RS485 Motor feeder M2 Protection Sepam M41 b 50/51: overcurrent - IDMT, DT (4 settings) b 50N/51N: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent b 67N/67NC: directional earth fault - IDMT, DT (2 settings) b 32P: directional active overpower b 32Q/40: directional reactive overpower b 49RMS: thermal overload (2 settings) b 37: phase undercurrent b 48/51LR/14: exces. start. time, locked rotor b 66: starts per hour b 27D: positive sequence undervoltage (2 settings) b 27R: remanent undervoltage b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings) b 47: negative sequence overvoltage b 38/49T: temperature monitoring. Sepam M41, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Starting current and time b Start inhibit time delay/number of start before inhibition b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam M41 Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Motor rotation detection CB closing order Fault and alarm contact (O11(1) to O14) CB opening order Inhibit closing External tripping Local/remote control selection Inhibition thermal overload External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b 8/16 temperature sensors inputs MET148-2 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. (1) O11 reserved for closing order DEAI06EN.indd 25 Generator incomer G1 b Protection against faults, network and loads faults b Monitoring of winding temperature b It suited for integration into a supervisory system using Modbus serial interface. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Measurement and diagnostic DE56395 Application 50/51 50V/51V 50G/51G 50BF Open/close 46 32P trip 32Q/40 49RMS 27/27S 59 59N 47 81H 81L 38/49T A 94 V 69 F 86 MD 74 KW 30 KVAR 68 KVA 60LF PF KW.h KVar.h Temp Sepam G40, LCD display LED (Light Emitting Diode) b Phase current: I1, I2, I3 RMS b Residual current: I0 b Average currents: I1, I2, I3 b Peak demand phase currents b Line voltage: U21, U32, U13 b Phase to neutral voltage: V1, V2, V3 b Residual voltage: V0 b Positive sequence voltage/rotation direction b Frequency b Active, reactive and apparent power: P, Q, S b Peak demand power PM, QM and power factor b Active and reactive energy b Tripping currents: I1, I2, I3, I0 b Unbalance ratio/negative sequence current Ii b Phase displacement b Disturbance recording b Running hours counter/operating time b Thermal capacity used b Remaining operating time before overload trip b Waiting time after overload tripping b Tripping context. CT’s option b CLP1: LPCT sensors 100 A to 1250 A b Core balance CT: CSH120 or CSH200. Control Sepam G40 G Temp Sensor Analog Output Remote UMI Modbus RS485 Generator incomer G1 Protection Sepam G40 b 50/51: overcurrent - IDMT, DT (4 settings) b 50G/51G: earth fault - IDMT, DT (4 settings) b 50BF: breaker failure b 46: negative sequence overcurrent b 32P: directional active overpower b 32Q/40: directional reactive overpower b 49RMS: thermal overload b 27/27S: undervoltage (2 settings) b 59: overvoltage (2 settings) b 59N: neutral voltage displacement (2 settings) b 47: negative sequence overvoltage b 81H: overfrequency (2 settings) b 81L: underfrequency (4 settings) b 38/49T: temperature monitoring. Cumulative breaking current Trip CB output (O1) Closing lockout (O2) Logic discrimination block send (O3) Watch dog (O4) CB control (86) CB open/closed status indication Number of operations, operating time Trip circuit supervision (74) Logic discrimination block receive Bl1 CB closing order Fault and alarm contact (O11(1) to O14) CB opening order Inhibit closing External tripping Local/remote control selection Inhibition thermal overload External network time synchronization Basic apparatus b b b b b b MES114 module (10 I/4 O) b b b b b b b b b b b b b b b b b b Optional features b Communication interface module, 2 wires (ACE949-2) Modbus b Communication interface module, 4 wires (ACE959) Modbus b Logic inputs and outputs module MES114 (10I/4O) b One low level analog output (0-10 mA/ 4-20 mA/ 0-20 mA) MSA141 module b 8/16 temperature sensors inputs MET148-2 module b Remote advanced UMI (type DSM303) b Test box b Local/remote switch. (1) O11 reserved for closing order 26 DEAI06EN.indd ART.960249 © Schneider Electric Industries SAS - All rights reserved Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F-92505 Rueil-Malmaison Cedex Tel.: +33 (0)1 41 29 85 00 www.schneider-electric.com As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Publishing: Schneider Electric Industries SAS Production: Graphème Printing: DEAI06EN 05-2008