Power Transfer Switches - Puerto Rico Suppliers .com

advertisement
Fire Pump Controllers for
Business Critical Continuity ™
Power Transfer Switches
Completely assembled with fire pump controllers.
Firetrol® power transfer switches are available completely assembled with Firetrol electric fire pump
controllers – full voltage or reduced voltage types.
The entire package of power transfer switch and
controller is completely factory assembled, wired,
tested and shipped as a complete unit for easy field
connection to the power sources and the fire pump
motor. The power transfer switch and the electric
fire pump controller are assembled in separate but
connected enclosure compartments. All wiring between the two enclosures in completed by Firetrol.
Approvals
The power transfer switches are listed by Underwriters Laboratories, Inc. for transfer switch service and
also meet the requirements of NFPA 20, Standard
for the Installation of Stationary Pumps for Fire Protection and NFPA 70, National Electrical Code. The
automatic/manual power transfer switches are
listed by Underwriters Laboratories, Inc. under UL1008, Automatic Transfer Switches, as well as UL-508,
Industrial Control Equipment.
Construction
The construction of the FTA950 power transfer
switch includes an isolating disconnect switch/
circuit breaker assembly, designed for fire pump
service, providing short circuit, locked rotor and
running current protection for the fire pump controller and the motor. The operating handle has a
mechanical interlock so that the enclosure door
can not be opened with the isolating disconnect
switch in the ON position. The operating handle
mechanism closes and opens both the isolating disconnect switch and the circuit breaker in the proper
sequence. When the handle is moved to the ON
position, the isolating disconnect switch is closed
first and then the circuit breaker. When moved to
the OFF position, the circuit breaker opens first and
then the isolating disconnect switch. The circuit
breaker always “makes” and “breaks” the load.
The transfer switch is electrically operated and
mechanically held. The electrical operator is a momentarily energized, single solenoid mechanism.
The switch is mechanically interlocked to ensure
only two possible positions, normal or emergency.
The transfer switch control panel features a 4 line,
20 character LCD display and keypad for viewing
all available data and setting desired operational
parameters. Source status screens are provided
for both normal & emergency to provide digital
readout of voltage, frequency and phase rotation
on all 3 phases.
Included on the fire pump Mark IIXG user interface
panel are LED’s for TRANSFER SWITCH NORMAL,
TRANSFER SWITCH EMERGENCY and EMERGENCY
ISOLATING SWITCH OFF. Mounted on the enclosure
flange are TEST and TRANSFER BYPASS selector
switches and the audible alarm.
FTA976 power transfer switches for use with Limited
Service Controllers are constructed identically as
the FTA950 except that a thermal magnetic circuit
breaker is supplied and no disconnect switch is
required.
Short Circuit Current Rating
The short circuit current rating for the normal
power source and the emergency power source side
of the power transfer switch will be the same as the
rating of the fire pump controller assembled with
the power transfer switch.
User Interface
ASCO Group 5 Control Panel
Separately mounted transfer
switches.
Firetrol® brand Separately Mounted Fire Pump
Automatic Transfer Switches are designed for use
when pump room size constraints will not allow an
integral controller/transfer switch configuration, or
where a transfer switch is now being required on an
existing installation. They are intended for use with
Listed and Approved fire pump controllers.
Approvals
Firetrol® Separately Mounted Fire Pump Automatic
Transfer Switches are listed by Underwriters’ Laboratories, Inc., for transfer switch service and also
meet the requirements of NFPA 20, Standard for the
Installation of Stationary Pumps for Fire Protection
and NFPA 70, National Electrical Code. The transfer
switches are listed by Underwriters Laboratories,
Inc. under UL-1008, Automatic Transfer Switches,
as well as UL-508, Industrial Control Equipment.
Configurations
Firetrol Separately Mounted Automatic Transfer
Switches are available in the following configurations:
FTA902 – Provides the transfer of 3-phase power to a
fire pump controller between a utility on
the normal side and a generator on the
alternate (emergency) side. The disconnecting means and overcurrent protective devices required for the normal side
of the transfer switch are NOT supplied.
FTA903 – Provides the transfer of 3-phase power to a
fire pump controller between a utility on
the normal side and a generator on the
alternate (emergency) side. The disconnecting means and overcurrent protective devices required for the normal side
of the transfer switch ARE provided.
FTA952 – Provides the transfer of 3-phase power to a
fire pump controller between a utility on
the normal side and a 2nd utility on the
alternate (emergency) side. The disconnecting means and overcurrent protective devices required for the normal side
are NOT supplied. The disconnecting
means and overcurrent protective for the
alternate (emergency) side ARE supplied.
FTA953 – Provides the transfer of 3-phase power to a
fire pump controller between a utility on
the normal side and a 2nd Utility on the
alternate (emergency) side. The disconnecting means and overcurrent protective devices required for the normal side
and alternate side of the transfer switch
ARE provided.
Features
Firetrol Separately Mounted Automatic Transfer Switches feature the ASCO 7000 series transfer
switch with Group 5 controller as standard. The
microprocessor based controller includes a built-in
keypad and four line LCD display mounted through
the enclosure door. This allows all monitoring and
control functions to be done with the door closed,
providing convenience and safety.
The menu driven user interface allows setting
changes to be made easily. These settings include:
• Voltage and Frequency
• Time Delays
• Features
• Engine Exerciser
• Event Log
• Service Features
Bypass-Isolation transfer
switches
Firetrol® Automatic Transfer & Bypass-Isolation
Switches are designed to be used with any Firetrol®
Electric Fire Pump Controller. The entire package of
Automatic Transfer & Bypass-Isolation Switch and
Electric Fire Pump Controller is completely factory
assembled, wired, tested and shipped as a complete
unit for easy field connection to the power sources
and the fire pump motor.
Automatic Transfer & Bypass-Isolation Switches
are designed for critical applications where the
transfer switch cannot be taken out of service for
maintenance or repair purposes; these applications
include health care facilities, data centers, retirement facilities and correctional institutions.
Approvals
Firetrol Automatic Transfer & Bypass-Isolation
Switches are listed by Underwriters Laboratories,
Inc. for transfer switch service and also meet the
requirements of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection and
NFPA 70, National Electrical Code. The Automatic
Transfer & Bypass-Isolation Switches are listed by
Download