quicktronic® helios™ 10 t8

advertisement
www.osram-americas.com/QUICKTRONIC
QUICKTRONIC® HELIOS™ 10 T8
Fluorescent Controllable
Lighting Systems
Lamp / Ballast Guide
32W T8 – SYLVANIA OCTRON® lamps
1 or 2 lamp QHE2x32T8/UNV HDIM10-SC
Primary Lamp Types
FO32, FBO32 & FBO31
Also operates:
FBO30/SS, FBO29/SS, FBO28/SS,
FBO27/SS, FO30/SS, FO28/SS, FO25/SS,
FO25/21SS*, FO25*, FO17*, FO17/15SS*,
FBO24* & FBO16*
*T hese lamp types are not compatible with one lamp
operation Key System Features
—— Compatible with low voltage controls
—— High efficiency
—— NEMA Premium Electronic Ballast
Program compliant
—— Lamp Detection Technology
—— Universal voltage (120-277V)
—— 100-10% Dimming Range
—— PROStart® Programmed Rapid Start
—— Anti-flash circuitry – turns on in
dimmed mode
—— Operates at >42 kHz
—— QUICK 7XL+™ or QUICK 60+®
ballast and lamp warranty
—— RoHS compliant
—— Lead-free solder and manufacturing
process
Application Information
OSRAM QUICKTRONIC HELIOS 10
ballasts are ideally suited for:
—— Occupancy sensors
—— Daylight harvesting
—— Energy management
—— Load shedding
—— New construction
—— Retrofit
ECS456 5-14
OSRAM QUICKTRONIC High Efficiency HELIOS 10
T8 electronic ballasts offer several advantages:
—— One or two lamp operation
—— low voltage controls
—— any line voltage from 120V to 277V
—— multiple lamps and wattages to support a wide
range of applications
—— assists in achieving energy code requirements
such as ASHRAE 90.1 and CA Title 24.
NEMA Premium Electronic Program - compliant.
This program promotes the use of high efficiency
T8 electronic ballasts by meeting or exceeding the
Ballast Efficiency Factors (BEF), established by the
CEE (Consortium for Energy Efficiency).
For additional information on this program go to
www.cee1.org or www.nema.org
System Information
QUICKTRONIC HELIOS 10 ballasts operate from
standard low voltage (0-10Vdc) controllers, making
them ideal for individual office lighting or automated
building applications, both in new construction and
retrofit projects.
For advanced systems, such as daylight harvesting
or building automation applications, standard low
voltage devices (0-10Vdc, Class 1 or 2) are used to
control the lighting system.
In this daylight harvesting example, each lighting
fixture (or fixture row) is controlled by its own
photosensor; regulating the light output to
compensate for changes in natural daylight.
Depending upon the specific application, energy
savings of up to 60% compared to fixed output T8
electronic systems can be realized.
QUICKTRONIC HELIOS 10 ballasts include a line
voltage protection circuit, which protects the ballast
in the event that line voltage is inadvertently applied
to the low voltage controls inputs. DAYLIGHT HARVESTING SCENARIO
Fixture
1
Window / Natural Light Source
QUICKTRONIC
HELIOS 10 T8
Universal Voltage Dimming Systems
High Efficiency Series
Light
Sensor 1
Fixture
2
Light
Sensor 2
Fixture
3
Light
Sensor 3
Desired Illuminance Er
Constant setpoint value
Specification Data
Catalog #
Type
Project
Comments
Prepared by
Dimming Curves
2-Lamp Operation
Relative Light Output (%)
100
80
60
40
20
0
0
1
2
3
4
5
6
7
8
9
10
8
9
10
Dimming Control Voltage (VDC)
1-Lamp Operation
Relative Light Output (%)
120
100
80
60
40
20
0
0
1
2
3
4
5
6
7
Dimming Control Voltage (VDC)
70
60
Input Power (W)
HELIOS 10
Dimming Curves
120
50
40
30
FO32XP/XL
20
10
0
10
9
8
7
6
5
4
Dimming Control Voltage (VDC)
3
2
1
QUICKTRONIC ® HELIOS 10™ Controls Information
Please contact controls manfacturer to order/specify controls. For the latest controls list go to www.osram-americas.com
Also, for more information, refer to the LCA (Lighting Controls Association) site: http://lightingcontrolsassociation.org
Product Details
SC enclosure
Overall: 9.5" L x 1.68" W x 1.18" H (241 x 43 x 30 mm)
Mounting: 8.90" (226 mm)
Wiring:
Leads Only (no connectors provided)
Packaging:
Quantity: 10 pcs per case
Weight: 1 lbs each (approx)
Wire Lead Lengths:
Black and White: 22"
Yellow: 46"
Red and Blue: 26"
Green: 1.7"
Violet and Gray: 36"
Height
8.70 mm
Slot
Width
Mounting
Length
Length
WARNING: Install and wire these ballast and controls in accordance with the National Electrical Code (NEC), all applicable Federal, State and local electrical codes, as well as the specific
instructions provided with the compatible control that you purchased. Installation should be performed by qualified personnel only.
These instructions are guidelines only. Installation may vary for different controls/fixtures/applications. Be sure to follow the control instructions and all applicable codes and standards when
installing dimming systems.
Please contact controls manufacturer listed in the OSRAM SYLVANIA Inc. controls cross reference for compatible controls and instruction wiring.
NOTE:
Dimming ballasts source <0.5mA (0-10Vdc control input).
HELIOS 10
Controls
Building
Controls 0-10 Vdc
Photo Occupancy Management
ManufacturerControllers
Cells
Sensors
Systems
Acuity Brand Controls
•
•
•
•
www.acuitybrandscontrols.com
Blue Ridge Technologies
•
•
•
•
www.brtint.com
Cooper Greengate
•
•
•
•
http://greengate.coopercontrol.com
ENCELIUM
• •
www.encelium.com
Hunt Dimming
• •
www.huntdimming.com
Lehigh Electric Products
• •
www.lehighdim.com
Leviton
•
•
•
www.leviton.com
Sensor Switch
•
•
www.sensorswitch.com
Siemens Building Technology
•
http://sbt.siemens.com
Starfield Controls
•
•
•
•
www.starfieldcorp.com
Watt Stopper •
•
•
•
www.wattstopper.com
Performance Guide
High Efficiency, T8 Controllable Lighting Systems, UNV (120-277V)
Input Rated
Ballast Input
System1
Item
OSRAM SYLVANIA Current Lamp
Lumens N o. of Factor S ystem Mean Power (W) Efficacy
Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W) BEF 2
50719 QHE2x32T8/UNV HDIM10-SC 0.53/0.22 FO32XP/XL 2950
2
0.88 5200
4890
59
57 88
1.49
0.10
600
560
19
19
0.50/0.21FO30/SS 2850 2
0.86 4900 4610 56 55 88
1.54
0.10
580
550
19
19
0.46/0.19FO28/SS 2725 2
0.86 4680 4400 51 49 92
1.69
0.10
540
510
18
18
0.40/0.17FO25/SS 2475 2
0.86 4260 4000 45 44 95
1.91
0.10
500
470
18
18
0.22/0.09FO17
1400 2
0.88 2460 2310 25 24 98
3.52
0.10
280
260
13
13
Products are all 10-pack.
1
System Efficacy calculation based on lowest input power value.
2
Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
3
Striation may occur when using SUPERSAVER lamps.
Wiring Diagrams
LAMP 2
LAMP 2
Red
Blue
Black (Hot)
Blue
Blue
White (Neutral)
Black (Hot)
Blue Yellow
ELECTRONIC
Yellow
White (Neutral)
Violet(+)
Yellow
BALLAST
ELECTRONIC
Grey(-)
Yellow Red
Violet(+)
BALLAST
Red
Grey(-)
Red
Red
LAMP 1
Red
LAMP 1
Blue
Blue
LAMP 1
2 lamp
Black (Hot)
White (Neutral)
Black (Hot)
Blue
ELECTRONIC
White (Neutral)
Blue
Violet(+)
BALLAST
ELECTRONIC
Grey(-)
Violet(+)
BALLAST Red
Grey(-)
Red
LAMP 1
1 lamp
Specifications
Data based on F32T8
Starting Method: P rogrammed Rapid Start
Circuit Type: Series
Lamp Frequency: >42 kHz
Lamp CCF: Less than 1.7
Starting Temp: 50°F/10°C minimum
for OCTRON T8 lamps
Input Voltage: 120-277V, ±10%
Input Frequency: 50/60 Hz
THD: <10% @ Full Output
Power Factor: >98% @ Full Output
UL Listed Class P, Type 1 Outdoor
CSA or C/UL Certified
70°C Max Case Temperature
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
RoHS compliant3
ANSI C62.41 Cat. A Transient Protection
Remote mounting (Max. wire length from ballast
case to lampholder)
— up to 8ft for full wattage T8s
— no remote mounting for SUPERSAVER
3
omplies with European Union Restriction of Hazardous
C
Substances Directive (Directive EC 2002/95)
Control Information
QUICKTRONIC HELIOS 10 ballasts are compatible with a
wide range of low voltage (0-10Vdc) controllers available
from various manufacturers.
Low Voltage Control Specs: ballast will source up to 0.5mA
for 0-10Vdc control purposes.
May be wired as a Class 1 or Class 2 circuit- consult Local
and National Electrical Codes.
r one lamp application, cap any yellow lead to insulate to 600 volts.
ne lamp application, cap any yellow lead to insulate to 600 System
volts.Life / Warranty
Output Wiring: Lamp wiring for dimming ballasts can differ significantly from non-dimming ballasts and from other manufacturers dimming ballasts. Take care to connect lamp lead
wires as shown on the applicable ballast diagram. Lamp Seasoning: For optimal performance, fluorescent lamps may require seasoning for up to 12 hours prior to low temperature
starting & low level dimming. Refer to NEMA LSD 23-2002 Lighting Systems Division: Recommended Practice — Lamp Seasoning for Fluorescent Dimming Systems
Input & Control
Wiring Options:
QUICKTRONIC products are covered by the QUICK 7XL+™ or
QUICK 60+® warranties; comprehensive lamp and ballast
system warranties.
For additional information refer to the warranty section of
www.osram-americas.com
LOW-VOLTAGE CONTROL
LINE
LOW-VOLTAGE
CONTROLBLACK
BLACK WHITE
VIOLET(+)
WHITE
NEUTRALClass 1
0-10V
DC
or
GREY(-)
VIOLET(+)
<0.5mA
Class 1Class 20-10V
DC
or
GREY(-)
<0.5mA
Class 2
LINE NEUTRAL
Ordering Guide
Item Number
50719 QHE 2 x 32T8 / UNV HDIM10-SC
System Type - DIMMING/Case Size
QUICKTRONIC High Efficiency
Line Voltage (120-277V)
Number of Lamps (2)
Primary Lamp Wattage
Americas Headquarters
OSRAM SYLVANIA Inc.
100 Endicott Street
Danvers, MA 01923 USA
Phone 1-800-LIGHTBULB
(1-800-544-4828)
OSRAM and QUICKTRONIC are registered trademarks of OSRAM, GmbH. The System Solution, OCTRON, POWERSENSE, XP, SUPERSAVER, PROStart,
and QUICK 60+ are registered trademarks of OSRAM SYLVANIA Inc. QUICK 7XL and HELIOS are trademarks. www.osram-americas.com
Specifications subject to change. © 2014 OSRAM
HELIOS 10
T8 DIM
0.28/0.12FO32XP/XL2950 1
0.88 2600 2440 31 30 84
2.84
0.10
300
275
10
10
0.26/0.11FO30/SS 2850 1
0.86 2450 2300 29 28 84
2.97
0.10
290
270
9
9
0.23/0.10FO28/SS 2725 1
0.86 2340 2200 26 25 90
3.31
0.10
270
250
9
9
0.21/0.09FO25/SS 2475 1
0.86 2130 2000 23 22 93
3.74
0.10
250
240
8
8
Data based on SYLVANIA OCTRON® lamps shown.
QUICKTRONIC® HELIOS™ 10 ballasts are also compatible with other manufacturers equivalent lamp types
that meet ANSI specifications, including F17, F25,
F32, U-bend equivalent lamps and SUPERSAVER®
lamps.
Download