Systems Solution Consultant, LLC
SHOP DRAWING REVIEW
SYNERGY SPINE
SSC# E003
ITEMS:
•
Shop Drawings: LIGHTING
APPROVED
APPROVED AS NOTED
APPROVED AS NOTED, RESUBMISSION REQUIRED
NOT APPROVED
COMMENTS:
1. Contractor is responsible for item quantities.
2. Install per manufacturers recommendation and published information.
3. Provide complete and fully functional system with all required devices and components
as required to meet all applicable codes.
4. Contractor is responsible for coverage areas since sensors are not as specified.
5. Coordinate with architect for finish colors.
6. Coordinate lighting switches programming with owner requirements.
DISCIPLINE
ELECTRICAL
MECHANICAL
REVIEWED BY
Miro Stamenkovik
SIGNATURE
MStamenkovik
DATE
07-13-12
REVIEW IS FOR GENERAL CONFORMANCE WITH DESIGN CONCEPT AND CONTRACT DOCUMENTS. MARKING OR
COMMENTS CAN NOT BE CONSTRUED AS RELIEVING THE CONTRACTOR FROM COMPLIANCE WITH THE
CONSTRUCTION DOCUMENTS, SPECIFICATIONS NOR DEPARTURES THEREFROM THE CONTRACTOR REMAINS
RESPONSIBLE FOR ACCURACY, DETAILS, QUANTITIES, DIMENSIONS, WEIGHTS AND TECHNIQUES OF ASSEMBLY.
Ph/Fax 313.221.9933
Ph/Fax 734.213.3387
1001 Woodward Ave., Suite #920, Detroit, MI 48226
2900 S State Street, #R1 Ann Arbor, MI 48104
TRANSMITTAL
Date:
July 10, 2012
cc: 2947-22- G & B Electric
Dave Hatter
To:
Stucky Vitale Architects
27172 Woodward Ave
Royal Oak, MI 48067
Attn:
Mike Blanek
Phone:
248.546.6700
From:
Stephanie Lofgren
Project:
Synergy Spine & Orthopedic Surgery Center Renovation
Subject: Lighting Controls Submittal
Enclosed please find the following:
Item
No.
1
Copies
1
Action
Code
2
Description
Lighting Controls Submittal
Action Codes
1
2
3
4
For Your Use/Review
For Your Approval
Resubmitted for Approval
Resubmit for Record
Sent Via:
5
6
7
8
Approved
Approved as Noted
Not Approved – Resubmit
Other
Email
Comments:
Subcontractor: G & B Electric, Jim Gierlach
830 Orchard St., Ferndale, MI 48220
Office: (248) 547-5441 Cell: (248) 563-7550
226 East Hudson | Royal Oak | Michigan | 48067 | Phone 248.547.1210 | Fax 248.546.1276
GASSER & BUSH INC
30984 INDUSTRIAL
LIVONIA, MI 48150
Phone: 734-266-6705
Synergy Spine & Orthopedic Surgery Center
12-11945-0
7/10/2012
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Submitted By
GASSER & BUSH INC
Type
S20
STS
MUT300
MWT300
PP
SD
LCP
LCP
SDT
SDTM
Manufacturer
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Acuity Brands
Lighting
Catalog Number
WSD WH
Qty
33
PTS 60 WH
4
CM PDT 9 R
4
CM PDT 9 R
33
MP20
29
ISD 600 ADEZ 120 WH M10
20
GR2432 ENC SM NE1
1
GR2432 INT 16NCL 4DPNC DTCMOD 1
DV
CH1 BWH PWH
15
CH6 BWH PWH
1
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
WSD WH
S20
GASSER & BUSH INC
®
WSD
WALL SWITCH DECORATOR SENSOR
LINE VOLTAGE • PASSIVE INFRARED (PIR)
SPECIFICATIONS
FEATURES
PIR Occupancy Detection
Self-Contained Relay No Power Pack Needed
Interchangeable Hot & Load Wires Impossible to Wire Backwards
No Neutral Connection Required
Small Motion Detection to 20 ft (6.10 m)
Self-Grounding Mounting Strap
No Minimum Load
Push-Button Programmable w/o
Removing the Switch Plate
Adjustable Time Delay
3-way & 4-way Switching
Green LED Indicator
PHYSICAL SPECS
SIZE 4.2”H x 1.8”W x 1.5”D
(10.67cm x 4.57cm x 3.81cm)
WEIGHT 5 oz
MOUNTING Single Gang Switch Box
MOUNTING HEIGHT 30-48 in
(76.2-121.9 cm)
COLORS White, Ivory, Gray
Almond, Black
ELECTRICAL SPECS
MAXIMUM LOAD
800 W @ 120 VAC
1200 W @ 277 VAC
1500 W @ 347 VAC
MINIMUM LOAD None
MOTOR LOAD 1/4 HP
FREQUENCY 50/60 Hz
(timers are 1.2x for 50 Hz)
VANDAL-RESISTANT LENS (V)
• Ideal for high abuse or public areas,
where occupants simply come and go
• Decreases detection range by 50%
INHIBIT PHOTOCELL (P)
• Auto set-point calibration
• Photocell prevents lights from turning
on if adequate daylight is available,
but does not turn lights off
347 VAC (347)
• Allows sensor to be powered from
and switch 347 VAC
• Wall Plate Provided
SENSOR OPERATION & MODES
COLOR
The sensor detects changes in the
• White, Ivory, Gray, Almond, Black
• Wall Plate Provided
infrared energy given off by occupants as
they move within the field-of-view. When
LOW TEMP/HIGH HUMIDITY (LT)
occupancy is detected, a self-contained
• Sensor is corrosion resistant
• Operates down to -40º F/C
relay switches the connected lighting
load on. The sensor is line powered and
switches line voltage (see specifications). A timer, factory set at 10 minutes, keeps
the lights on during brief periods of inactivity. This timer is push-button programmable
from 30 seconds to 20 minutes, and resets every time occupancy is re-detected. This
state-of-the-art design requires no field calibration or sensitivity adjustments.
effectively ignoring PIR signals reflected off of surfaces, while still sensing
occupants when they enter the room. Once lights are on, the sensor returns to
maximum sensitivity.
SWITCH MODES
PREDICTIVE OFF MODE (default) - This mode allows occupants to turn lights off
via the switch without losing the convenience of having the lights automatically
turn on when they re-enter the room. Pressing the switch turns the lights off and
temporarily disables the occupancy detection in the sensor. After a short exit
time delay, the occupancy detection reactivates and monitors for an additional
grace period. If no occupancy is detected, the zone will remain in Automatic On
operation. If occupancy is detected, the zone will go to a Permanent Off mode,
requiring the switch to be pressed again in order to turn the lights on and restore
the sensor to Automatic On operation.
PERMANENT OFF - Pressing the switch turns the lights and the sensor off.
Lights will not come on until switch is pressed again.
SWITCH DISABLE - Prevents user from manually turning off the lights via the
push-button. Button can still be utilized for programming.
OTHER
UL and CUL Listed
Title 24 Compliant
5 Year Warranty
Made in the U.S.A.
LENS
OPTIONS
ON MODES
AUTOMATIC ON (default) - Lights come on when occupancy is detected.
MANUAL ON - Requires the occupant manually turn on lights via the push-button.
REDUCED TURN ON - Sensor is initially set to only detect large motions,
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
ORDERING INFO
The WSD is a stylish, easy to install, and
simple to use Wall Switch Decorator style
Passive Infrared (PIR) sensor. It is ideal
for private offices, copy rooms, closets,
or any small enclosed space without
obstructions. A user programmable time
delay ensures that once the room is
vacated the sensor will time out and turn
off the lights. Additionally, the WSD sensor
has several On Modes and Switch Modes
that can be programmed using the front
push-button. For rooms with obstructions,
the Dual Technology WSD PDT Series
sensor is recommended.
WSD [LENS] [PHOTOCELL] [VOLTAGE] [COLOR] [TEMP/HUMIDITY]
PHOTOCELL
VOLTAGE
Blank = None
Blank = None
Blank = 120/277 VAC V = Vandal Resistant
P = Photocell
347 = 347 VAC
COLOR
WH = White
IV = Ivory
GY = Gray
AL = Almond
BK = Black
TEMP/HUMIDITY
Blank = Standard
LT = Low Temp
Catalog Number
Submitted By
Notes
Type
WSD WH
S20
GASSER & BUSH INC
Revised 11.11.09 © 2009 Sensor Switch
COVERAGE PATTERN
WSD
WALL SWITCH DECORATOR LENS
• Small motion (e.g. hand movements) detection up to 20
ft (6.10 m)
• Large motion (e.g. walking) detection up to 50 ft (15.24 m)
• Wall-to-Wall coverage
0m
0 ft
3
5
10
6
15
20
6
3
0m
3
6
20
10
0 ft
10
20
TOP VIEW
4 ft
1.2 m
SIDE VIEW
TOP VIEW
0
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
4 in
10 cm
WIRING (DO NOT WIRE HOT)
STANDARD WIRING
BLACK* - Line Input
*BLACK wires can be reversed
BLACK* - Load Output
GREEN SCREW - Ground (required connection)
}
347 VAC OPTION (347)
Black wires are replaced w/ Red wires
STANDARD CONFIGURATION
BI-LEVEL CONFIGURATION
Note: Connection to Ground required for sensor to function
3-WAY CONFIGURATIONS
Travelers are used to wire sensors (or sensor and 3-way switch) in parallel.
Note: Connection to Ground required for sensor to function
WARNING
Fire Hazard Caution: Maximum Lamps 1500 Watts, Type 347 VAC.
Attention: Risque d’incendie : Pauissance Maximales Des Lampes 1500 Watts, Type 347 VAC.
Warning: The units are intended to be installed by a qualified person with properly rated branch circuit protectors as per applicable local and national regulations (CEC, NEC).
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a
period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material
Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied
warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
T059-004-P
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
0m
0 ft
3
5
10
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
PTS 60 WH
STS
GASSER & BUSH INC
®
PTS 60
PTS 720
PROGRAMMABLE (INTERVAL) TIMER SWITCH
LINE VOLTAGE • DECORATOR STYLE
SPECIFICATIONS
APPLICATIONS
Fluorescent/Incandescent/LED Lighting
in Meeting rooms, Library Aisles, Stock Rooms, & Mechanical Rooms
Exhaust Fans
FEATURES
Self-Contained Relay
Interchangeable Hot & Load Wires Impossible to Wire Backwards
No Neutral Connection Required
Self-Grounding Mounting Strap
No Minimum Load Requirement
Push-Button Programmable w/o Removing Switch Plate
Fixed or Adjustable Preset Times
Optional Audible Timeout Warning
at 45, 30, and 15 sec
Optional Flicker Timeout Warning
at 2 and 1 min
Continous LED Flash for Last 30 sec
of Button’s Time Setting
Green On/Off Switch Status LED
Green LED Time Indicators
PHYSICAL SPECS
SIZE 4.2”H x 1.8”W x 1.5”D
(10.67cm x 4.57cm x 3.81cm)
WEIGHT 5 oz
MOUNTING Single Gang Switch Box
COLORS White, Ivory, Gray, Lt Almond
ELECTRICAL SPECS
MAXIMUM LOAD
800 W @ 120 VAC
1200 W @ 277 VAC
1500 W @ 347 VAC
MINIMUM LOAD None
MOTOR LOAD 1/4 HP
FREQUENCY 50/60 Hz
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
ROHS COMPLIANT
SILICONE FREE
OTHER
ETL Listed
ASHRAE 90.1 Compliant (PTS 60)
IECC Compliant (PTS 60)
Title 24 Compliant (PTS 60)
5 Year Warranty
Assembled in the U.S.A.
ORDERING INFO
TIME SCALE
The PTS 60 and PTS 720 Series
Electronic Auto Shut-off Timer Switches
provide a simple to use and simple to
apply lighting control alternative to wall
switch occupancy sensors. These elegant
decorator style wall stations each provide
six preset countdown timer selections
as well as an on/off push-button. The
PTS 60 and PTS 720 units are powered
from 120/277 VAC (optional 347 VAC)
and are intended to switch a line voltage
lighting load or small motor load (see
specifications). Additionally, the PTS
60 and PTS 720 can be applied without
requiring a neutral wiring connection,
making them ideal for retrofit applications.
OPTIONS
TIME SCALE [60 / 720]
• 60, 30, 15, 10, 5, 2 min
• 12 hr, 8 hr, 4 hr, 2 hr, 60 min, 30 min
347 VAC (347)
• Allows sensor to be powered from and
switch 347 VAC
• Wall plate provided (White/Ivory only)
COLOR
• White, Ivory, Gray, Lt. Almond
• Wall plate provided
• Must be specified
LOW TEMP/HIGH HUMIDITY (LT)
• Sensor is corrosion resistant
• Operates down to -40º F/C
TIMER OPERATION
When the unit’s on/off button is pressed,
the self-contained relay closes, turning the
connected load on. The LED on the button
of the last time selected will also turn on,
indicating the time remaining before the
unit turns the lights off. Optionally, this
default timer setting can be fixed. If a
different timer selection is required, the
user simply presses the button labeled
with the time of their choice. If desired,
a maximum timer setting can also be programmed into the switch. Once time
has elapsed below the point of the next
lowest time option, the LED on that button
will light and the original time selection’s
LED will turn off.
At the two and one minute remaining
point, the unit will issue a flicker warning
to occupants indicating that the lights
will shut off if another time selection
is not chosen. Additionally, an audible
beep warning is issued at 45, 30 and 15
seconds. Both warning indicators can be
disabled if desired. Finally, a button’s LED
will flash continuously during the last 30
seconds of its time setting.
PTS [TIME SCALE] [VOLTAGE] [COLOR] [TEMP/HUMIDITY]
VOLTAGE
COLOR
60 = 60 min max
Blank = 120/277 VAC
WH = White
720 = 12 hr max
347 = 347 VAC
IV = Ivory
GY = Gray
AL = Lt. Almond
TEMP/HUMIDITY
Blank = Standard
LT = Low Temp
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
PTS 60 WH
STS
GASSER & BUSH INC
Revised 4.15.11 © 2011 Sensor Switch
WIRING (DO NOT WIRE HOT)
H
STANDARD WIRING
BLACK* - Line Input
*BLACK wires can be reversed
BLACK* - Load Output
GREEN SCREW - Ground (required connection)
N
BLK
}
BLK
LOAD
GRN
347 VAC OPTION (347)
Black wires are replaced w/ Red wires
Note: Connection to Ground required for sensor to function
PROGRAMMING INSTRUCTIONS
(PLEASE READ ALL 7 STEPS BEFORE PROGRAMMING)
1. Enter programming mode by pressing & holding upper left button until LED flashes rapidly. Release button.
2. Enter a specific programming function by pressing button the number of times as the desired function number from the
tables on the following pages (e.g., for a PTS 60, press five times for function 5, Max Time Allowable).
3. The selected function’s current setting will then be read out in a sequence of LED flashes (e.g., one flash for 60 min). To
change setting, proceed to step 4 before sequence repeats 10 times.
4. While the switch is flashing back current setting, interrupt it by pressing button the number of times for the new desired
setting as indicated in the particular function’s detailed table (e.g., press twice for 30 min). Switch will begin to flash new
setting as confirmation.
5. Next, while the switch is flashing back new setting, interrupt it by pressing and holding button until LED flashes rapidly.
Release button.
6. As final confirmation and activation of the new setting, re-enter the programming function number that was changed (e.g.,
press five times for function 5, Max Time Allowable).
7. LED will flash twice indicating acceptance of new setting. If two flashes are not seen, repeat 7 step process.
Note: To exit programming mode without saving or to change to a different function, wait for blink back sequence to repeat 10 times then return to step 1.
Function
Number
Function
Name
2
Blink Warning
3
Beep Warning
4
Status Tick
5
5
6
6
9
Settings (*indicates default setting)
1. Enabled 2 min & 1 min*
3. Enabled 1 min
2. Disabled
4. Enabled 2 min
1. Enabled*
2. Disabled
1. Enabled
(ticks every 1 sec)
2. Disabled*
3. Enabled,
(ticks every 0.5 sec)
Max Time Allowable
(model # PTS 60)
1. 60 min*
3. 15 min
5. 5 min
2. 30 min
4. 10 min
6. 2 min
Max Time Allowable
(model # PTS 720)
1. 12 hr*
3. 4 hr
5. 60 min
2. 8 hr
4. 2 hr
6. 30 min
Default Time - when on/off
button pressed
(model # PTS 60)
1. 60 min
4. 10 min
7. Last time selected*
2. 30 min
5. 5 min
3. 15 min
6. 2 min
Default Time - when on/off
button pressed
(model # PTS 720)
1. 12 hr
4. 2 hr
2. 8 hr
5. 60 min
3. 4 hr
6. 30 min
1. Maintain current*
2. Restore defaults
Factory Defaults
7. Last time selected*
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a
period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material
Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied
warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TS-PTS-001A
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CM PDT 9 R
MUT300
GASSER & BUSH INC
®
TYPE OS-CP9
CM PDT 9 R
CM PDT 9
STANDARD RANGE 360º SENSOR
CEILING MOUNT • LOW VOLTAGE • DUAL TECHNOLOGY (PDT)
SPECIFICATIONS
OVERVIEW
Open area office lighting control is made costeffective with the use of the CM PDT 9 Series
Standard Range 360° occupancy sensor. This
sensor provides line-of-sight PIR detection of
small motion in a circular pattern, and combines
overlapping Microphonics™ coverage for
detection of occupants working in their cubical
space. By installing multiple CM PDT 9s on
30 ft (9.14 m) centers, large control zones are
created (typically one per circuit of lighting). The
lighting is then controlled in blocks similar to
manual switching. Restrooms with stalls, large
storage areas with shelving, and libraries with
study carrels are also easily and cost-effectively
controlled by the CM PDT 9.
FEATURES
100% Digital PIR Detection,
Excellent RF Immunity
360º Coverage Pattern
Patented Dual Technology with
PIR / M
icrophonics Detection
Push-Button Programmable
Adjustable Time Delays
Convenient Test Mode
No Field Calibration or Sensitivity
Adjustments Required
100 hr Lamp Burn-in Timer
Green LED Indicator
®
LAMPMAXIMIZER TECHNOLOGY
• Protects Lamp Life while
Maximizing Energy Savings
• Minimum On Timer (15 min default)
• Occ. Time Delay (10 min defatult)
• LampMaximizer+ Mode Optimizes Lamp Life & Energy Savings (disabled by default)
• Switch Counter (in 1000’s)
• Total Lamp On Time (in khrs)
PHYSICAL SPECS
SIZE 4.55” Dia. (11.56 cm)
1.55” Deep (3.94 cm)
WEIGHT 6 oz
MOUNTING
Ceiling Tile Surface
3.5” Octagon Box
Single Gang Handy Box
COLOR White
ELECTRICAL SPECS
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT DRAW
Standard, 4 mA
w/ R option, 16 mA
DIMMING LOAD Sinks < 20mA;
~40 Ballasts @ .5mA each
RECOMMENDED POWER PACK
PP20
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
SILICONE FREE
ROHS COMPLIANT
ORDERING INFO
Blank = None
R = Low Voltage Relay
LAMPMAXIMIZER®
This sensor also contains patent pending
LampMaximizer technology that allows users
to aggressively target energy savings while still
protecting lamp life. A minimum on timer, factory
set at 15 minutes, helps preserve lamp life by
eliminating all lamp cycles shorter than lamp
warranties specify. A standard occupancy time
delay is also present that ensures lights turn off
(assuming minimum on timer has elapsed) if no
occupancy is detected. This timer is factory set
at 10 minutes to promote energy savings, but is
adjustable between 30 seconds and 20 minutes.
These adjustments can be done manually,
through the units push-button, or automatically
every two weeks through an advanced mode,
called LampMaximizer+, that determines the
optimum time delay in order to maximize both
lamp life and energy savings. Additionally, this
sensor maintains statistics on total lamp on time
and number of cycles.
LOW VOLTAGE RELAY (R)
• Enables sensors to interface with
other systems (e.g., BMS, lighting
panels)
• Provides dry contact closure via a
SPDT, 1 Amp, 40 Volt relay
• Only one relay needed per zone
• Changes state when all connected
sensors register unoccupied
• Relay requires sensor power to
function
OCCUPANCY CONTROLLED
DIMMING (D)
• Provides dimming output to control
0-10 VDC dimmable ballasts
• Provides a second occupancy timeout period that enables the lights to go
to a dim setting before turning off
• Adjustable max/min dim setting
• Only one sensor per zone needs to
have dimming output
PHOTOCELL (P)
• Auto set-point calibration
• Two selectable modes of operation
• On/Off mode: Photocell has full
control during periods of occupancy
• Inhibit mode: Photocell can prevent
lights from turning on if adequate
daylight is available, but cannot turn
lights off
PHOTOCELL W/ DIMMING (ADC)
• Photocell within sensor maintains
total room light level by controlling
levels of 0-10 VDC dimmable ballasts
• Photocell also has full on/off control
during periods of occupancy
• Provides a second occupancy timeout period that enables the lights to go
to a dim setting before turning off
Note: LampMaximizer+ features not
available with ADC option
LOW TEMP/HIGH HUMIDITY (LT)
• Sensor is corrosion resistant to
moisture
• Operates down to -4º F (-20º C)
C
US LISTED
TITLE 24
MADE in U.S.A.
5 YEAR WARRANTY
CM PDT 9 [RELAY] [DIMMING/PHOTOCELL] [TEMP/HUMIDITY]
RELAY
SENSOR OPERATION
Sensors with Passive Dual Technology
(PDT) first see motion using 100% digital
Passive Infrared (PIR) detection and then
engage Microphonics™ to hear sounds that
indicate continued occupancy. This patented
technology uses Automatic Gain Control
(AGC) to dynamically self adapt a sensor
to its environment by filtering out constant
background noise and registering only noises
typical of human activity. When occupancy is
detected, a DC output goes high and can drive
up to 200 mA of connected load. If needed, a
10 second grace period also allows the lights
to be voice reactivated after shutting off. The
sensor is powered with 12-24 VAC/VDC and
typically operates with a PP20 or MP20 power
pack, enabling complete 20 Amp circuits to be
controlled.
OPTIONS
DIMMING / PHOTOCELL
CHOOSE ONE ONLY
Blank = None
D = Occupancy Controlled Dimming
P = Photocell
ADC = Photocell w/ Dimming
TEMP/HUMIDITY
Blank = Standard
LT = Low Temp
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CM PDT 9 R
MUT300
GASSER & BUSH INC
Revised 06.16.10 © 2010 Sensor Switch
COVERAGE PATTERN
9 STANDARD RANGE 360º LENS WITH MICROPHONICS™
SIDE
Note: Screw axis is
aligned with a long
detection segment
• Best choice for small motion (e.g. hand movements) detection
• Viewing angle of 56º in a 360º conical shaped pattern
• Provides 12 ft (3.66 m) radial coverage when mounted to
standard 9 ft (2.74 m) ceiling
• 8 to 15 ft (2.44 to 4.57 m) mounting heights provide 10 to 20 ft
(3.05 to 6.10 m) radial coverage
• Microphonics™ provides overlapping detection of human
activity over the complete PIR coverage area. Advanced
filtering is also utilized to prevent non-occupant noises from
keeping the lights on.
VIEW
0 ft 0SIDE
m
TOP VIEW
3.7 12
TOP
VIEW
VIEW
0 ft 0 m
9
2.7
9 3.7 2.7
12
1.8
3.7
6
12
0m
1.8
1.8 0 ft
0m
6
0 ft
1.8
3.7
6
0m
1.8 6
0 ft
0m
6
0 ft
1.8
1.8
6
3.7
6
1.8
12
6
3.7
3.7
12
STANDARD WIRING
RED - Power Input (12-24 VAC/VDC)
BLACK- Common
WHITE - Occupancy State (high VDC for occupied)
12
3.7
WIRING (DO NOT WIRE HOT)
RED
WHT
BLK
12
12
POWER PACK
(PP20)
(-)
VIO w/ WHT STRIPE (+)
[D, P, ADC] Photocell / Dimming Options
PHOTOCELL/DIMMING OPTIONS (D, P, ADC)
BLUE - Direct output to power pack for providing photocell
control and/or secondary dim time out. Output is high VDC
with occupancy & low light. Output also held high during
secondary dim time out. For multi-level control, use two
power packs and connect White wire to primary load and
Blue to daylight load.
VIOLET w/ WHITE STRIPE - Connect to 0-10 VDC control
wire (typically Violet) from 0-10 VDC dimmable ballast
GRAY from Ballast - Connect to sensor Black wire
[R] Relay Option
RELAY OPTION (R)
GRAY / BROWN - Connected during occupied state
VIOLET / BROWN - Connected during unoccupied state
Note: Relay is energized during unoccupied state
INSTALLATION
• Mount sensor directly to a ceiling tile or a metallic grid (two
self-tapping screws provided)
• Sensor’s mounting holes also align with 3.5” octagon or
single gang handy box (screws not provided)
• Sensor will detect motions crossing segments more
effectively than motions parallel to beams
• For optimal detection, position sensor such that segments
are crossed upon entrance and unable to view outside
the space
• For maximum Microphonics™ sensitivity avoid locating
sensor near HVAC air diffusers.
PUSH BUTTON
PROGRAMMING
Refer to instruction card IC7.001 for default settings and directions on programming the sensor via the push-button.
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for
a period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned
Material Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and
implied warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances
shall Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TS-CM-005A
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CM PDT 9 R
MWT300
GASSER & BUSH INC
®
TYPE OS-CP9
CM PDT 9 R
CM PDT 9
STANDARD RANGE 360º SENSOR
CEILING MOUNT • LOW VOLTAGE • DUAL TECHNOLOGY (PDT)
SPECIFICATIONS
OVERVIEW
Open area office lighting control is made costeffective with the use of the CM PDT 9 Series
Standard Range 360° occupancy sensor. This
sensor provides line-of-sight PIR detection of
small motion in a circular pattern, and combines
overlapping Microphonics™ coverage for
detection of occupants working in their cubical
space. By installing multiple CM PDT 9s on
30 ft (9.14 m) centers, large control zones are
created (typically one per circuit of lighting). The
lighting is then controlled in blocks similar to
manual switching. Restrooms with stalls, large
storage areas with shelving, and libraries with
study carrels are also easily and cost-effectively
controlled by the CM PDT 9.
FEATURES
100% Digital PIR Detection,
Excellent RF Immunity
360º Coverage Pattern
Patented Dual Technology with
PIR / M
icrophonics Detection
Push-Button Programmable
Adjustable Time Delays
Convenient Test Mode
No Field Calibration or Sensitivity
Adjustments Required
100 hr Lamp Burn-in Timer
Green LED Indicator
®
LAMPMAXIMIZER TECHNOLOGY
• Protects Lamp Life while
Maximizing Energy Savings
• Minimum On Timer (15 min default)
• Occ. Time Delay (10 min defatult)
• LampMaximizer+ Mode Optimizes Lamp Life & Energy Savings (disabled by default)
• Switch Counter (in 1000’s)
• Total Lamp On Time (in khrs)
PHYSICAL SPECS
SIZE 4.55” Dia. (11.56 cm)
1.55” Deep (3.94 cm)
WEIGHT 6 oz
MOUNTING
Ceiling Tile Surface
3.5” Octagon Box
Single Gang Handy Box
COLOR White
ELECTRICAL SPECS
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT DRAW
Standard, 4 mA
w/ R option, 16 mA
DIMMING LOAD Sinks < 20mA;
~40 Ballasts @ .5mA each
RECOMMENDED POWER PACK
PP20
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
SILICONE FREE
ROHS COMPLIANT
ORDERING INFO
Blank = None
R = Low Voltage Relay
LAMPMAXIMIZER®
This sensor also contains patent pending
LampMaximizer technology that allows users
to aggressively target energy savings while still
protecting lamp life. A minimum on timer, factory
set at 15 minutes, helps preserve lamp life by
eliminating all lamp cycles shorter than lamp
warranties specify. A standard occupancy time
delay is also present that ensures lights turn off
(assuming minimum on timer has elapsed) if no
occupancy is detected. This timer is factory set
at 10 minutes to promote energy savings, but is
adjustable between 30 seconds and 20 minutes.
These adjustments can be done manually,
through the units push-button, or automatically
every two weeks through an advanced mode,
called LampMaximizer+, that determines the
optimum time delay in order to maximize both
lamp life and energy savings. Additionally, this
sensor maintains statistics on total lamp on time
and number of cycles.
LOW VOLTAGE RELAY (R)
• Enables sensors to interface with
other systems (e.g., BMS, lighting
panels)
• Provides dry contact closure via a
SPDT, 1 Amp, 40 Volt relay
• Only one relay needed per zone
• Changes state when all connected
sensors register unoccupied
• Relay requires sensor power to
function
OCCUPANCY CONTROLLED
DIMMING (D)
• Provides dimming output to control
0-10 VDC dimmable ballasts
• Provides a second occupancy timeout period that enables the lights to go
to a dim setting before turning off
• Adjustable max/min dim setting
• Only one sensor per zone needs to
have dimming output
PHOTOCELL (P)
• Auto set-point calibration
• Two selectable modes of operation
• On/Off mode: Photocell has full
control during periods of occupancy
• Inhibit mode: Photocell can prevent
lights from turning on if adequate
daylight is available, but cannot turn
lights off
PHOTOCELL W/ DIMMING (ADC)
• Photocell within sensor maintains
total room light level by controlling
levels of 0-10 VDC dimmable ballasts
• Photocell also has full on/off control
during periods of occupancy
• Provides a second occupancy timeout period that enables the lights to go
to a dim setting before turning off
Note: LampMaximizer+ features not
available with ADC option
LOW TEMP/HIGH HUMIDITY (LT)
• Sensor is corrosion resistant to
moisture
• Operates down to -4º F (-20º C)
C
US LISTED
TITLE 24
MADE in U.S.A.
5 YEAR WARRANTY
CM PDT 9 [RELAY] [DIMMING/PHOTOCELL] [TEMP/HUMIDITY]
RELAY
SENSOR OPERATION
Sensors with Passive Dual Technology
(PDT) first see motion using 100% digital
Passive Infrared (PIR) detection and then
engage Microphonics™ to hear sounds that
indicate continued occupancy. This patented
technology uses Automatic Gain Control
(AGC) to dynamically self adapt a sensor
to its environment by filtering out constant
background noise and registering only noises
typical of human activity. When occupancy is
detected, a DC output goes high and can drive
up to 200 mA of connected load. If needed, a
10 second grace period also allows the lights
to be voice reactivated after shutting off. The
sensor is powered with 12-24 VAC/VDC and
typically operates with a PP20 or MP20 power
pack, enabling complete 20 Amp circuits to be
controlled.
OPTIONS
DIMMING / PHOTOCELL
CHOOSE ONE ONLY
Blank = None
D = Occupancy Controlled Dimming
P = Photocell
ADC = Photocell w/ Dimming
TEMP/HUMIDITY
Blank = Standard
LT = Low Temp
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CM PDT 9 R
MWT300
GASSER & BUSH INC
Revised 06.16.10 © 2010 Sensor Switch
COVERAGE PATTERN
9 STANDARD RANGE 360º LENS WITH MICROPHONICS™
SIDE
Note: Screw axis is
aligned with a long
detection segment
• Best choice for small motion (e.g. hand movements) detection
• Viewing angle of 56º in a 360º conical shaped pattern
• Provides 12 ft (3.66 m) radial coverage when mounted to
standard 9 ft (2.74 m) ceiling
• 8 to 15 ft (2.44 to 4.57 m) mounting heights provide 10 to 20 ft
(3.05 to 6.10 m) radial coverage
• Microphonics™ provides overlapping detection of human
activity over the complete PIR coverage area. Advanced
filtering is also utilized to prevent non-occupant noises from
keeping the lights on.
VIEW
0 ft 0SIDE
m
TOP VIEW
3.7 12
TOP
VIEW
VIEW
0 ft 0 m
9
2.7
9 3.7 2.7
12
1.8
3.7
6
12
0m
1.8
1.8 0 ft
0m
6
0 ft
1.8
3.7
6
0m
1.8 6
0 ft
0m
6
0 ft
1.8
1.8
6
3.7
6
1.8
12
6
3.7
3.7
12
STANDARD WIRING
RED - Power Input (12-24 VAC/VDC)
BLACK- Common
WHITE - Occupancy State (high VDC for occupied)
12
3.7
WIRING (DO NOT WIRE HOT)
RED
WHT
BLK
12
12
POWER PACK
(PP20)
(-)
VIO w/ WHT STRIPE (+)
[D, P, ADC] Photocell / Dimming Options
PHOTOCELL/DIMMING OPTIONS (D, P, ADC)
BLUE - Direct output to power pack for providing photocell
control and/or secondary dim time out. Output is high VDC
with occupancy & low light. Output also held high during
secondary dim time out. For multi-level control, use two
power packs and connect White wire to primary load and
Blue to daylight load.
VIOLET w/ WHITE STRIPE - Connect to 0-10 VDC control
wire (typically Violet) from 0-10 VDC dimmable ballast
GRAY from Ballast - Connect to sensor Black wire
[R] Relay Option
RELAY OPTION (R)
GRAY / BROWN - Connected during occupied state
VIOLET / BROWN - Connected during unoccupied state
Note: Relay is energized during unoccupied state
INSTALLATION
• Mount sensor directly to a ceiling tile or a metallic grid (two
self-tapping screws provided)
• Sensor’s mounting holes also align with 3.5” octagon or
single gang handy box (screws not provided)
• Sensor will detect motions crossing segments more
effectively than motions parallel to beams
• For optimal detection, position sensor such that segments
are crossed upon entrance and unable to view outside
the space
• For maximum Microphonics™ sensitivity avoid locating
sensor near HVAC air diffusers.
PUSH BUTTON
PROGRAMMING
Refer to instruction card IC7.001 for default settings and directions on programming the sensor via the push-button.
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for
a period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned
Material Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and
implied warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances
shall Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TS-CM-005A
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
MP20
PP
GASSER & BUSH INC
120/277 VOLT MINI
POWER PACKS AND SLAVE PACKS
TECHNICAL DATA
TYPICAL APPLICATIONS
• Used with Low Voltage Sensors
• Multiple Sensors
• Multiple Loads
POWER PACK HIGHLIGHTS
• Dual Voltage Transformer
• Self-Contained Relay
• Powers up to 14 sensors
SPECIFICATIONS
• Size:(1/2” inch chase nipple not inc.)
MP-20 & MSP-20: 21/4” x 3” x 17/8”
• Mounting: 1/2” inch chase nipple
• Operating Voltage: 120, 240, or
277 VAC
• Each Relay: 20 Amps
• 1 HP Motor Load
• Output Voltage: 15 VDC, 150 mA
• Class II: 18 AWG, up to 2,000 ft.
• Plenum Rated
• Relative Humidity: 20 to 90%
non-condensing
• Operating Temp: 14º to 160º F
• Storage Temp: -14º to 160º F
• UL and CUL Listed
• 5 Year Warranty
• Made in U.S.A.
LOW TEMP/HI HUMIDITY(-LT)
• Conformally Coated PCB
• Operates down to -40º F
• Corrosion resistant from moisture
PLENUM CONSIDERATIONS
Most local codes allow for small
plastic controls in Return Air Plenums;
Some Do Not! To meet local code, the
Power Pack can be mounted inside
an adjacent (Deep) junction box as
shown below.
MP-20
MSP-20
Plenum Rated
M
ini Power Packs are the heart of the Low Voltage Sensor System. The MP20 transforms 120, 240 or 277 Volts to class II 15 VDC to power the remote
sensors. Although Plenum Rated, the elongated mounting nipple allows for the
MP-20 to be mounted either directly thru a 1/2” inch knockout in a junction box, or
to be located inside an adjacent box for specific local code requirements. Up to 14
sensors may be connected to one MP-20. Multi-circuit control can be handled by
multiple MP-20's and Slave Packs (MSP-20) may be configured. MP-20's can be
wired continuously hot (line side), or on the switch leg (load side) without nuisance
delays upon turn "On".
MINI POWER PACK OPERATION
The Mini Power Pack consists of a transformer and a relay. The tranformer has a
dual primary high voltage input, accepting 120, 240, or 277 VAC. The secondary
voltage provides power to Sensor Switch low voltage heads. When the sensor
head detects motion, they electronically signal the power pack to close the relay(s)
connected to the lighting system.
LOW VOLTAGE OPERATION AND TEST
The Low Voltage Wires are color coded Red (15 VDC), Black (Common), and White
(Occupancy Signal). With no sensors connected, touch the Red wire to the White.
The lights should turn "On". Remove the connection and the lights should turn "Off".
With the sensors connected, the Red and Black wires provide DC power to the
remote sensors, and when there is occupancy detected, the White wire produces a
15 VDC signal from the sensor to the power pack initiating the lights to "On". Upon
initial power up, the Sensors automatically send an "On" signal until the sensors
have stabilized and "Timed Out".
SIZING OF THE SYSTEM - VARIOUS COMBINATIONS
Combining Power Packs provides for additional power to drive remote devices.
Maximum numbers of remote sensors are shown below based on the Power Pack/
Slave Pack being used: Maximum number of “Relays” is 30.
Sensors
Sensors with Relay
1 MP-20
14
8
1 MP-20 w/MSP-20
7
6
2 MP-20
28
16
Note 1: Only three relays may be controlled with one Mini Power Pack. If more
than three circuits are required, multiple MiniPower Packs must be used.
Note 2: Only one "Sensor with Relay" is required in most cases. See Technical
Data on Low Voltage Sensors and SPDT EMS Interface Option.
SYSTEMS CONSIDERATIONS
The local override switch may be upstream or downstream of an MP-20. However,
if an MSP-20 Auxiliary Relay controller is being used, the switch(es) should be
downstream on the load side of the relay. If power is disconnected to the Power
Pack all subsequent relays will open, turning off all of the loads. If wiring the local
switches before the Power Pack and Slave Pack, use multiple MP-20's, one for
each circuit. This will allow for one circuit to remain powered, keeping the system
operational when the other is turned off. When controlling a dimming circuit, MP-20
must be wired before dimmer, or MSP-20 may be wired after dimmer.
CATALOG INFORMATION
MODEL#
DESCRIPTION
MP-20
MSP-20
Power Pack with 20 Amp Relays
Slave Pack with 20 Amp Relays
**Add suffix -LT for Low Temp/Hi Humidity
OUTPUT VOLTAGE
15 to 24 VDC
N/A
OUTPUT CURRENT
70 to 110 mA
40 mA(consumption)
T053-001
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
MP20
PP
GASSER & BUSH INC
MP-20 • MSP-20
TYPICAL WIRING DIAGRAMS - DO NOT WIRE HOT
NOTE: The Power Pack must be connected to a single phase Hot and Neutral System. For 120 VAC, connect the Black
wire to Hot, White wire to Neutral, and Cap off the Orange wire. For 240-277 VAC, connect the Orange to Hot, White to
Neutral, and Cap off the Black wire. Never connect both the Black and Orange wires! Low Voltage wire can be 18 to 22
AWG; shielding is not necessary.
Multiple Sensors Controlling One Circuit
N
H
WHT
RED
BLK
WHT
MP-20
BLK/ORN
BLU
BLK - 120V
ORN - 277V
BLU
N
LOAD
SWITCH
Wiring Multiple Mini Power Pack Units Together
H
N
RED
BLK
MP-20
WHT
WHT
BLK/ORN
BLU
N
BLK - 120V
ORN - 277V
BLU
LOAD
SWITCH
N
RED
BLK
WHT
RED
BLK
WHT
MP-20
N
H
WHT
BLK/ORN
BLU
BLK - 120V
ORN - 277V
BLU
LOAD
SWITCH
N
H
RED
BLK
WHT
MSP-20
BLU
BLU
LOAD
SWITCH
One Sensor Controlling One Circuit
N
H
MP-20
ORN - 277V
WHT
BLK/ORN
SWITCH
BLK - 120V
RED
BLK
WHT
N
BLU
BLU
LOAD
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a period of sixty months.
Sensor Switch, Inc., upon prompt notice of such defect will, at its option, provide a Returned Material Authorization number and a replacement product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied warranties (including the implied warranties of
merchantability and fitness for use) and under no circumstances shall Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
SENSOR SWITCH, INC.
900 Northrop Rd., Wallingford, CT 06492
(203) 265-2842 info@sensorswitch.com
www.sensorswitch.com
revised 7/8/2005
copyright Sensor Switch, Inc. 2005
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
ISD 600 ADEZ 120 WH M10
SD
GASSER & BUSH INC
Catalog Number
Notes
Type
Wallbox Dimmers
FEATURES
ISD ADEZ
INTENDED USE
To provide smooth, full-range dimming of fluorescent fixtures equipped with the
Advance Mark X dimming ballast. These dimmers are ideally suited for use with
Lithonia fixtures supplied with the ADEZ dimming option.1
ATTRIBUTES
Fluid slide movement allows fine adjustment of light level over the entire dimming range. Separate ON/OFF preset switch permits switching the lighting without disturbing the light level setting. ISD Series dimmers are compatible with the
DSA Series wallplates and other Decora® devices.
FLUORESCENT DIMMER
CONSTRUCTION
Strap-mount device is designed to fit standard single- or multi-gang switch
boxes.
FINISH
Standard white or ivory finish devices are supplied with a single-gang Decora®
style wallplate. Snap-on color change kits are available to allow field color
change of the device to gray, black, brown, almond, white or ivory. Color change
kits include a matching single-gang Decora® style wallplate.
ELECTRICAL
Uses standard single-pole or three-way wiring. No neutral connection is required.
FUNCTIONAL
Integral push ON/push OFF switch allows lighting to be switched ON and OFF at
the level currently set by the slider. Dimmers can be used with standard three-way
and four-way switches for applications requiring control from multiple locations.
INSTALLATION
Wall-mounts over standard single-gang switch box. Devices can be ganged into
multi-gang assemblies by breaking off the scored aluminum tabs.
Shown with optional DSA FP D1 screwless wallplate
(order separately)
LISTING
UL and CSA listed. (NOM)
WARRANTY
Two-year total customer satisfaction warranty.
®
Decora is a registered trademark of Leviton.
Example:
ORDERING INFORMATION
ISD 1000 ADEZ 120 IV
Choose the boldface catalog nomenclature that best suits your needs and
write it on the appropriate line. Order accessories as separate catalog number.
ISD
ISD
600
ADEZ
ADEZ
120
WH
Series
Capacity2
Lamp Type
Voltage
Color3
ISD
600
1000
1200
600 VA at
120 Volts
1000 VA at
120 Volts
1200 VA at
277 Volts
ADEZ
Fluorescent
(Advance Mark
X Ballast)
120 120 Volts
277 277 Volts
IV
WH
Ivory
White
Accessories
NOTES:
1 Actual dimming range is determined by the ballast used.
Consult the ballast manufacturer for specifications.
2 1200VA unit is not available at 120 volts. 600VA and
1000VA units are not available at 277 volts.
3 ISD dimmers are supplied with standard wallplates.
Order optional IV ivory or WH white screwless designer
wallplates to match dimmer.
Controls
Order as separate item.
ISD CCKIT _ _
DSA FP D# _ _
Color change kit, specify WH (White), IV (Ivory), GY
(Gray), BR (Brown), BK (Black) or AL (Almond).
Ivory screwless thermoplastic wallplate for ISD or Decora®
compatible devices. Specify number of gangs (# =1 to 6) and
color [WH (white), IV (ivory), GY (gray), BR (brown), BK (black)
or AL (almond)].
Sheet #: ISD-ADEZ
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
ISD 600 ADEZ 120 WH M10
SD
GASSER & BUSH INC
ISD ADEZ Wallbox Dimmers, Fluorescent Dimmer
SPECIFICATIONS
DIMENSIONS
ELECTRICAL
All dimensions are inches (centimeters).
Standard three-way operation.
•
Maximum Loading is model specific.
•
Deration required in 120 VAC multi-gang dimmer installations.
•
(See Capacity and Derating tables.)
No derating is required on 277 volt units.
4.15 (105.4 mm)
•
2.68 (68.1 mm)
Input: 120 VAC or 277 VAC, model specific @ 60Hz.
Integral RFI noise supression.
3.28 (83.3 mm)
•
•
(See Capacity and Derating tables.)
MECHANICAL
•
1.41
(35.8 mm)
2.12 (53.8 mm)
0.38
(9.7 mm)
Captured wrap around slide mechanism, 20 mm total travel.
• Air-gap push ON/OFF preset switch.
ENVIRONMENTAL
•
Operating range, 0 – 55oC, 20 – 90% relative humidity, non condensing.
CAPACITES AND DERATING
Single-Location Control Application
ISD 600 ADEZ 120 (120 Volt) Table
Advance
Mark XTM
Part No.
REZ – 2Q26
Lamp
Type
One-Gang
PLC 26W
10
8
6
REZ – 132
T8/32W
16
14
11
REZ – 2S32
T8/32W
8
7
5
Maximum Number Ballast/Dimmer
Two-Gang
T8/32W
5
4
3
REZ – IT32
PLT 32-26W
15
12
10
REZ – IT42
PLT 42W
12
10
8
REZ – 1TTS40
CF 40W
14
11
9
REZ – 2TTS40
CF 40W
7
6
5
Maximum Number Ballast/Dimmer
One-Gang
PLC 26W
17
Advance Mark X®two-wire fluorescent
dimming ballast
Black
Red
Black
Hot (Black)
Red
Load
Line
Voltage
Green
Ground
}
White
Neutral (White)
Two-Location Control Application
ISD 1000 ADEZ 120 (120 Volt) Table
Lamp
Type
Dimmer
Cap with
Wire Connector
More than Two-Gang
REZ – 3S32
Advance
Mark XTM
Part No.
REZ – 2Q26
WIRING DIAGRAM
Two-Gang
13
More than Two-Gang
Common
Terminal
(Black Screw)
Dimmer
3-Way Switch
®
11
REZ – 132
T8/32W
27
22
19
REZ – 2S32
T8/32W
14
11
9
REZ – 3S32
T8/32W
9
7
6
REZ – IT32
PLT 32-26W
25
20
17
REZ – IT42
PLT 42W
20
16
14
REZ – 1TTS40
CF 40W
23
19
16
REZ – 2TTS40
CF 40W
12
9
8
ISD 1200 ADEZ 277 (277 Volt) Table
Advance Mark X two-wire fluorescent
dimming ballast
Hot (Black)
Red
Black
Black
Red
Line
Voltage
Load
Green
Ground
Green
Ground
}
White
Neutral (White)
Three-Location Control Application
Advance
Mark XTM
Part No.
VEZ – 2Q26
Lamp
Type
One-Gang
PLC 26W
20
20
20
VEZ – 132
T8/32W
33
33
33
VEZ – 2S32
T8/32W
17
17
17
VEZ – 3S32
T8/32W
11
11
11
Maximum Number Ballast/Dimmer
Two-Gang
More than Two-Gang
VEZ – IT32
PLT 32-26W
30
30
30
VEZ – IT42
PLT 42W
24
24
24
VEZ – 1TTS40
CF 40W
28
28
28
VEZ – 2TTS40
CF 40W
14
14
14
Common
Terminal
(Black Screw)
4-Way Switch
3-Way Switch
Dimmer
®
Hot (Black)
1
2
Red
1
2
Red
Advance Mark X two-wire fluorescent
dimming ballast
Black
Black
Line
Voltage
Load
Green
Ground
Green
Ground
Green
Ground
}
White
Neutral (White)
1 Travelers between switches "IN"
2 Travelers between switches "OUT"
NOTE:
"Two-gang" and "More than Two-Gang" columns indicate dimmer capacity when
more than one dimmer is installed under a single multi-gang faceplate.
"Two-gang" = two dimmers under a common faceplate
"More than Two-gang" = more than two dimmers under a common faceplate.
Synergy Lighting Controls
Sheet #: ISD-ADEZ
©2001 Acuity Brands Lighting, Inc., Rev. 10/25/07
1335 Industrial Blvd, Conyers, GA 30012
Phone: 800-533-2719
www.synergylightingcontrols.com
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
GR2432 ENC SM NE1
LCP
GASSER & BUSH INC
GR 2400
CONTROL PANELS
™
C o n t ro l P a n e l
GR 2400™ Relay Panel
Description: The GR 2400 system is a 100% digital solution to lighting control. Panels and switches daisy-chain
together, using Cat. 5 patch cable with RJ45 connectors in any sequence.
Features: • 32-channel, 365-day/astronomical time clock. Large display (21 x 8 characters) acts as the programming interface for the entire system. Non-volatile memory holds all programming indefinitely. Ten-year battery back-up for time-of-day
• Modem includes free lifetime factory programming
• May control mixed voltages (i.e., 120V, 277V)
• May control normal or emergency power
• Ideal for all applications
• Manual override of individual relays, zones or entire panel
• Link up to 127 addresses of digital devices via Cat. 5 patch cable with RJ45 connectors
Specifications:
Enclosure dimensions: 25.5" h x 20" w x 6" d (32 relays)
37.5" h x 20" w x 6" d (48 relays)
Enclosure type: Surface mount, hinged locking door, NEMA 1
Optional enclosures: NEMA 4, NEMA 4X, NEMA 12, flush mount
Relay:
Optional relays:
Normally Closed (NCL)
30A @ 277VAC Ballast
20A @ 120VAC Tungsten
20A @ 347VAC Ballast
SCCR 18kA @ 277VAC Rated 250,000 Cycles
Normally Open, (NOL) Spec same as NCL,
Two Pole — NO or NC (480VAC);
Double Throw 20A 277VAC
Addresses used: GR 2432 (4), GR 2448 (6)
Listings: UL and cUL 916 listed, ETL listed to UL 924 (for
emergency circuit use)
Programming: Via DTC clock, via PC with
Unity 2™ Lighting Control
Software
Max. humidity: 10 – 90% non-condensing
Ambient temperature: 32–105° F (0 – 41° C)
Power supply voltage: 120/277VAC or 120/347VAC
Bus protocol: RS 485 (GR 2400 bus)
Bus connector: RJ45 connectors
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
GR2432 ENC SM NE1
LCP
GASSER & BUSH INC
Overview
Power Supply:
120/277V or 120/347V
DTC Clock:
32-channel, 365-day astro clock Access and program the entire system
Modem:
Remote programming and control, includes free
lifetime dial-up programming
Bus connectors
RJ45 connectors
Lighting Relays:
Normally Closed (NCL), 30A @ 277V Ballast,
20A @ 120V Tungsten, 20A @ 347V Ballast,
SCCR 18K A @ 277V, Rated 250,000 Cycles
Optional Relays:
Normally Open, (NOL) Spec same as NCL,
Two Pole — NO or NC (480V); Double Throw 20A 277V
High/Low Voltage Barrier:
(16 gauge steel)
Master Relay
Panel
Photosensor
Chelsea
DigitalSwitch
Slave Relay Panel
w/PCC1 card
Chelsea
DigitalSwitch™
Relay Control Card
(manual control of zones
or individual relays)
Up to 127 digital addresses • Up to 4,000 ft.
Cat. 5 patch cable with RJ45 connectors
ORDERING LOGIC
Enclosure
GR2432 ENC
Enclosure Mounting, NEMA Rating, Knockouts
Relay Panel Enclosure
GR2448 ENC = 48 Relay Enclosure
GR2432 ENC = 32 Relay Enclosure
Examples:
SM NE1
SM NE1 = Surface Mount, NEMA-1 with knockouts
FM NE1 = Flush Mount, NEMA-1 with knockouts
SM NE1 NKO = Surface Mount, NEMA-1 no knockouts
FM NE1 NKO = Flush Mount, NEMA-1 no knockouts
SM NE4 = Surface Mount, NEMA-4
SM NE12 = Surface Mount, NEMA-12
SM NE4X = Surface Mount, NEMA-4X
GR2448 ENC SM NE1
GR2448 INT 12NCL 12DPNC DTCMOD DV
48 relay, surface mount NEMA-1 enclosure with knockouts,
with 12 normally closed relays, 12 double pole normally
closed relays, with a digital time clock and modem (master
panel), and a 120V/277V dual voltage transformer (also, no
voltage barriers).
Interior
Relay Panel Interior
Relays
Clock Option
GR2448 INT = 48 Relay
Interior
GR2432 INT = 32 Relay
Interior
[qty]NCL = Normally Closed Latching
[qty]NOL = Normally Open Latching
[qty]DPNC = Double Pole Normally Closed
[qty]DPNO = Double Pole Normally Open
[qty]RRNO = Reed Relay Normally Open (pair)
[qty]SPDT = Single Pole Double Throw
[qty]SPDTC = Single Pole Double Throw Contactor
DTCMOD = Digital time clock
with modem
DTC = Digital time clock
without modem
REMOTE = Remote panel,
no clock
Lighting Control & Design • Glendale, CA
Transformer
Voltage Barrier1
DV = Dual voltage 120V/277V
347V = 120V/347V
[blank] = No barrier
1VB = 1 barrier
2VB = 2 barriers
3VB = 3 barriers
4VB = 4 barriers
1 = Check with NEC, State and
local regulations and your electrical
inspector about allowances for
voltage barriers within panels
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
GR2432 INT 16NCL 4DPNC DTCMOD DV
LCP
GASSER & BUSH INC
GR 2400
CONTROL PANELS
™
C o n t ro l P a n e l
GR 2400™ Relay Panel
Description: The GR 2400 system is a 100% digital solution to lighting control. Panels and switches daisy-chain
together, using Cat. 5 patch cable with RJ45 connectors in any sequence.
Features: • 32-channel, 365-day/astronomical time clock. Large display (21 x 8 characters) acts as the programming interface for the entire system. Non-volatile memory holds all programming indefinitely. Ten-year battery back-up for time-of-day
• Modem includes free lifetime factory programming
• May control mixed voltages (i.e., 120V, 277V)
• May control normal or emergency power
• Ideal for all applications
• Manual override of individual relays, zones or entire panel
• Link up to 127 addresses of digital devices via Cat. 5 patch cable with RJ45 connectors
Specifications:
Enclosure dimensions: 25.5" h x 20" w x 6" d (32 relays)
37.5" h x 20" w x 6" d (48 relays)
Enclosure type: Surface mount, hinged locking door, NEMA 1
Optional enclosures: NEMA 4, NEMA 4X, NEMA 12, flush mount
Relay:
Optional relays:
Normally Closed (NCL)
30A @ 277VAC Ballast
20A @ 120VAC Tungsten
20A @ 347VAC Ballast
SCCR 18kA @ 277VAC Rated 250,000 Cycles
Normally Open, (NOL) Spec same as NCL,
Two Pole — NO or NC (480VAC);
Double Throw 20A 277VAC
Addresses used: GR 2432 (4), GR 2448 (6)
Listings: UL and cUL 916 listed, ETL listed to UL 924 (for
emergency circuit use)
Programming: Via DTC clock, via PC with
Unity 2™ Lighting Control
Software
Max. humidity: 10 – 90% non-condensing
Ambient temperature: 32–105° F (0 – 41° C)
Power supply voltage: 120/277VAC or 120/347VAC
Bus protocol: RS 485 (GR 2400 bus)
Bus connector: RJ45 connectors
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
GR2432 INT 16NCL 4DPNC DTCMOD DV
LCP
GASSER & BUSH INC
Overview
Power Supply:
120/277V or 120/347V
DTC Clock:
32-channel, 365-day astro clock Access and program the entire system
Modem:
Remote programming and control, includes free
lifetime dial-up programming
Bus connectors
RJ45 connectors
Lighting Relays:
Normally Closed (NCL), 30A @ 277V Ballast,
20A @ 120V Tungsten, 20A @ 347V Ballast,
SCCR 18K A @ 277V, Rated 250,000 Cycles
Optional Relays:
Normally Open, (NOL) Spec same as NCL,
Two Pole — NO or NC (480V); Double Throw 20A 277V
High/Low Voltage Barrier:
(16 gauge steel)
Master Relay
Panel
Photosensor
Chelsea
DigitalSwitch
Slave Relay Panel
w/PCC1 card
Chelsea
DigitalSwitch™
Relay Control Card
(manual control of zones
or individual relays)
Up to 127 digital addresses • Up to 4,000 ft.
Cat. 5 patch cable with RJ45 connectors
ORDERING LOGIC
Enclosure
Examples:
Enclosure Mounting, NEMA Rating, Knockouts
Relay Panel Enclosure
GR2448 ENC = 48 Relay Enclosure
GR2432 ENC = 32 Relay Enclosure
SM NE1 = Surface Mount, NEMA-1 with knockouts
FM NE1 = Flush Mount, NEMA-1 with knockouts
SM NE1 NKO = Surface Mount, NEMA-1 no knockouts
FM NE1 NKO = Flush Mount, NEMA-1 no knockouts
SM NE4 = Surface Mount, NEMA-4
SM NE12 = Surface Mount, NEMA-12
SM NE4X = Surface Mount, NEMA-4X
GR2448 ENC SM NE1
GR2448 INT 12NCL 12DPNC DTCMOD DV
48 relay, surface mount NEMA-1 enclosure with knockouts,
with 12 normally closed relays, 12 double pole normally
closed relays, with a digital time clock and modem (master
panel), and a 120V/277V dual voltage transformer (also, no
voltage barriers).
Interior
16NCL, 4DPNC
Relay Panel Interior
Relays
Clock Option
GR2448 INT = 48 Relay
Interior
GR2432 INT = 32 Relay
Interior
[qty]NCL = Normally Closed Latching
[qty]NOL = Normally Open Latching
[qty]DPNC = Double Pole Normally Closed
[qty]DPNO = Double Pole Normally Open
[qty]RRNO = Reed Relay Normally Open (pair)
[qty]SPDT = Single Pole Double Throw
[qty]SPDTC = Single Pole Double Throw Contactor
DTCMOD = Digital time clock
with modem
DTC = Digital time clock
without modem
REMOTE = Remote panel,
no clock
Lighting Control & Design • Glendale, CA
Transformer
Voltage Barrier1
DV = Dual voltage 120V/277V
347V = 120V/347V
[blank] = No barrier
1VB = 1 barrier
2VB = 2 barriers
3VB = 3 barriers
4VB = 4 barriers
1 = Check with NEC, State and
local regulations and your electrical
inspector about allowances for
voltage barriers within panels
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CH1 BWH PWH
SDT
GASSER & BUSH INC
GR 2400
™
Chelsea
Switch
Chelsea Digital Switch ™
Description: The Chelsea DigitalSwitch is a 100% digital switch which connects directly to the GR 2400 bus via
Cat. 5 patch cable with RJ45 connectors. Chelsea DigitalSwitches can be ordered with 1, 2, 3, 4 or 6
buttons per gang and can be mounted in any standard 2.25" deep switch box with a decorator style
switch plate. All Chelsea DigitalSwitches are 100% backwards compatible with all LC&D systems.
to control any relay,
Features: • May be programmed
™
• Factory preprogrammed. May be reprogrammed
in the field using the DTC (Digital Time Clock)
SmartBreaker or dimmer in any panel
• Custom button engraving at no cost
(2 lines 8 character/line)
• Link up to 127 digital addresses via Cat. 5 patch
cable with RJ45 connectors
• Available in a choice of plate and button colors
• Can be enabled/disabled by optional
KeyEnable™ switch
• All push buttons are annunciated with a pilot light
Advanced • A programmable green “Locator Light” at the top
Programming of each unit is always on, can be programmed
Features: to blink to show Horn Driver Mode or help locate
• Audible beep alert for warning or switch locating
• Programmable Status LED logic
• Alternate button programming to allow more
flexibility of use, for example the same button
can perform a different task at different times of
the day
• Adjustable debounce time to avoid
accidental trigger
• Capable of being digitally enabled/disabled over
the bus on a per button or per switch basis
a switch
Specifications:
Dimensions:
Switch plate:
Mounting:
Switch addresses
available:
Address per switch:
Function:
1.3" w x 4" h x 1.3" d
Decorator style
2.25" deep-switch box
1–119
1
ON, OFF, Mixed, Group
Control, Toggle, Scene Control
Programming:
Humidity:
Ambient temperature:
Power supply:
Bus connector:
Bus termination:
43
Via DTC
10 – 90% non-condensing
32 –105° F (0 – 41° C) Powered from GR 2400 bus
Two RJ45 connectors
Manual end-of-line termination
with jumper
SWITCHES / PHOTOSENSORS
Cover plate provided by contractor
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CH1 BWH PWH
SDT
GASSER & BUSH INC
Ordering Information
Chelsea DigitalSwitches™ are available in 1, 2, 3, 4 or 6 buttons. Center plates are available in white, ivory and brushed stainless steel.
Indicator light is red and locator light is green.
GR 2400™ Master
Relay Panel
GR 2400 Remote
Relay Panel
Chelsea
DigitalSwitch™
Chelsea
DigitalSwitch™
To phone line for
remote dial up
Example: Typical wiring
of a GR 2400 bus.
Cat. 5 patch cable with RJ45 connectors • Up to 127 digital addresses • Up to 4,000 ft.
ordering logic
Chelsea Digital Switch™
CH1
BWH
Number of Buttons
CH1 = 1 button Chelsea
CH2 = 2 button Chelsea
CH3 = 3 button Chelsea
CH4 = 4 button Chelsea
CH6 = 6 button Chelsea
Single/Multicolor
BWH = All buttons white
BIV = All buttons ivory
BGY = All buttons gray
BBK = All buttons black
BRD = All buttons red
BGR = All buttons green
BBU = All buttons blue
BYL = All buttons yellow
BOR = All buttons orange
MC = Multicolored buttons
(please select quantities from
the multicolor button section)
Examples:
PWH
Multicolor Button Colors
Button Quantity
1B = 1 button
2B = 2 buttons
3B = 3 buttons
4B = 4 buttons
6B = 6 buttons
Color
WH = White
IV = Ivory
GY = Gray
BK = Black
RD = Red
GR = Green
BU = Blue
YL = Yellow
OR = Orange
Plate Colors
Multicolor Examples:
CH6 MC 2BWH 4BBK PST
6 button Chelsea with 2 white and 4 black buttons and
a stainless steel faceplate PWH = White plate
PIV = Ivory plate
PST = Stainless steel plate
PBK = Black plate
CH4 MC 2BBU 1BGR 1BYL PWH
4 button Chelsea with 2 blue, 1 green, and 1 yellow
button and a white faceplate Button Quantity represents the number of buttons on
a switch that will be in the selected color— number may
not exceed total number of buttons on switch - total of
all button color quantities must equal total number of
buttons on switch (refer to examples).
CH6 BWH PWH = 6 button Chelsea with all white buttons and a white faceplate
CH3 MC 1BRD 2BBK PST = 3 button Chelsea with 1 red button, 2 black buttons, and a stainless steel faceplate
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
44
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CH6 BWH PWH
SDTM
GASSER & BUSH INC
GR 2400
™
Chelsea
Switch
Chelsea Digital Switch ™
Description: The Chelsea DigitalSwitch is a 100% digital switch which connects directly to the GR 2400 bus via
Cat. 5 patch cable with RJ45 connectors. Chelsea DigitalSwitches can be ordered with 1, 2, 3, 4 or 6
buttons per gang and can be mounted in any standard 2.25" deep switch box with a decorator style
switch plate. All Chelsea DigitalSwitches are 100% backwards compatible with all LC&D systems.
to control any relay,
Features: • May be programmed
™
• Factory preprogrammed. May be reprogrammed
in the field using the DTC (Digital Time Clock)
SmartBreaker or dimmer in any panel
• Custom button engraving at no cost
(2 lines 8 character/line)
• Link up to 127 digital addresses via Cat. 5 patch
cable with RJ45 connectors
• Available in a choice of plate and button colors
• Can be enabled/disabled by optional
KeyEnable™ switch
• All push buttons are annunciated with a pilot light
Advanced • A programmable green “Locator Light” at the top
Programming of each unit is always on, can be programmed
Features: to blink to show Horn Driver Mode or help locate
• Audible beep alert for warning or switch locating
• Programmable Status LED logic
• Alternate button programming to allow more
flexibility of use, for example the same button
can perform a different task at different times of
the day
• Adjustable debounce time to avoid
accidental trigger
• Capable of being digitally enabled/disabled over
the bus on a per button or per switch basis
a switch
Specifications:
Dimensions:
Switch plate:
Mounting:
Switch addresses
available:
Address per switch:
Function:
1.3" w x 4" h x 1.3" d
Decorator style
2.25" deep-switch box
1–119
1
ON, OFF, Mixed, Group
Control, Toggle, Scene Control
Programming:
Humidity:
Ambient temperature:
Power supply:
Bus connector:
Bus termination:
43
Via DTC
10 – 90% non-condensing
32 –105° F (0 – 41° C) Powered from GR 2400 bus
Two RJ45 connectors
Manual end-of-line termination
with jumper
SWITCHES / PHOTOSENSORS
Cover plate provided by contractor
Project 12-11945-0
Synergy Spine & Orthopedic Surgery Center
Catalog Number
Submitted By
Notes
Type
CH6 BWH PWH
SDTM
GASSER & BUSH INC
Ordering Information
Chelsea DigitalSwitches™ are available in 1, 2, 3, 4 or 6 buttons. Center plates are available in white, ivory and brushed stainless steel.
Indicator light is red and locator light is green.
GR 2400™ Master
Relay Panel
GR 2400 Remote
Relay Panel
Chelsea
DigitalSwitch™
Chelsea
DigitalSwitch™
To phone line for
remote dial up
Example: Typical wiring
of a GR 2400 bus.
Cat. 5 patch cable with RJ45 connectors • Up to 127 digital addresses • Up to 4,000 ft.
ordering logic
Chelsea Digital Switch™
CH6
BWH
PWH
Number of Buttons
Single/Multicolor
Multicolor Button Colors
CH1 = 1 button Chelsea
CH2 = 2 button Chelsea
CH3 = 3 button Chelsea
CH4 = 4 button Chelsea
CH6 = 6 button Chelsea
BWH = All buttons white
BIV = All buttons ivory
BGY = All buttons gray
BBK = All buttons black
BRD = All buttons red
BGR = All buttons green
BBU = All buttons blue
BYL = All buttons yellow
BOR = All buttons orange
MC = Multicolored buttons
(please select quantities from
the multicolor button section)
Button Quantity
1B = 1 button
2B = 2 buttons
3B = 3 buttons
4B = 4 buttons
6B = 6 buttons
Examples:
Color
WH = White
IV = Ivory
GY = Gray
BK = Black
RD = Red
GR = Green
BU = Blue
YL = Yellow
OR = Orange
Plate Colors
Multicolor Examples:
CH6 MC 2BWH 4BBK PST
6 button Chelsea with 2 white and 4 black buttons and
a stainless steel faceplate PWH = White plate
PIV = Ivory plate
PST = Stainless steel plate
PBK = Black plate
CH4 MC 2BBU 1BGR 1BYL PWH
4 button Chelsea with 2 blue, 1 green, and 1 yellow
button and a white faceplate Button Quantity represents the number of buttons on
a switch that will be in the selected color— number may
not exceed total number of buttons on switch - total of
all button color quantities must equal total number of
buttons on switch (refer to examples).
CH6 BWH PWH = 6 button Chelsea with all white buttons and a white faceplate
CH3 MC 1BRD 2BBK PST = 3 button Chelsea with 1 red button, 2 black buttons, and a stainless steel faceplate
Lighting Control & Design • Glendale, CA
Phone (323) 226-0000 • F (323) 226-1000 • Sales Hot Line (800) 345-4448 • sales@lightingcontrols.com • www.lightingcontrols.com
© 2010 Acuity Brands Lighting, All Rights Reserved.
44
GBA / LC&D SYSTEM COMMISSIONING REQUEST FORM
FAX COMPLETED FORM TO GBA CONTROLS DEPT 734-266-6732.
The following checklist has to be completed by the day of requested startup
TWO WEEKS NOTICE REQUIRED!!!
□
□
□
All equipment received, inspected (documented for any damage during shipment) and installed
□
□
All loads landed per panel schedules and switches installed in correct locations via switch address #
Will this system be commissioned in phases? Y/N
If YES, please contact GBA 734-266-6705
All equipment installed as shown by approved submittals, installation instructions, riser, and wiring diagrams
provided by GBA or Factory?
Cat 5 wires run in a daisy chain topology, and remain within network specified lengths
(Failure to use specified wire, wire lengths, and topologies will jeopardize completion of this Startup)
□
Cat 5 terminated to the specified T568B standard network wiring code. Tested with
Professional Lan Cable Tester with Remote and connected to appropriate terminals on all devices
□
□
□
BAS Equipment (Phone Modem, Network Interface, BACnet device) also connected?
Provide a list of any changes to system
Electrician available on site who is familiar with installation
Owner or representative must be available for Training same day of Startup. No allowances made for
return training visits unless defined in submittals
ANY QUESTIONS CONTACT GBA CONTROLS DEPT 723-266-6705
Project/Site Name:
Address/Location:
Site Contact & Company
Phone/Fax:
Requested Startup Date:
TWO WEEKS NOTICE REQUIRED!!!
Today’s Date:
Customer Signature:
Print Name:
FAX COMPLETED FORM TO GBA CONTROLS DEPT 734-266-6732