1797-6.5.6, FlexEx System Certification Reference Manual

advertisement
FLEX Ex System
Certification
1797 Series
Reference Manual
Important User Information
Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown
in this guide are intended solely for purposes of example. Since there
are many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based upon
the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some
important differences between solid-state equipment and
electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole
or part, without written permission of Rockwell Automation, is
prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
ATTENTION
!
Identifies information about practices or
circumstances that can lead to personal injury or
death, property damage or economic loss
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
IMPORTANT
Identifies information that is critical for successful
application and understanding of the product.
Allen-Bradley and FLEX Ex are trademarks of Rockwell Automation
European Communities (EC)
Directive Compliance
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC
Electromagnetic Compatibility (EMC) by applying the following
standards, in whole or in part, documented in a technical
construction file:
• EN 50081-2 EMC — Generic Emission Standard, Part 2 —
Industrial Environment
• EN 50082-2 EMC — Generic Immunity Standard, Part 2 —
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests. For specific information required by EN 61131-2, see the
appropriate sections in this publication, as well as the Allen-Bradley
publication Industrial Automation Wiring and Grounding Guidelines
For Noise Immunity, publication 1770-4.1.
This equipment is classified as open equipment and must be
mounted in an enclosure during operation to provide safety
protection.
Notes
Preface
What Is Intrinsically Safe?
According to Article 504 of the National Electrical Code, NFPA 70, an
intrinsically safe (I/S) product is defined as one in which no spark or
thermal effect generated during normal functioning and/or during
specific fault conditions is able to ignite a given explosive atmosphere.
One example of an I/S product is FLEX ExTM distributed I/O control.
What are Product
Certifications?
A product certification is a guarantee that the product has been
designed and manufactured with the required I/S specifications and
protection. Considering the potential danger in hazardous locations,
product certification is required for all I/S products.
Two Types of Product Certifications
In this reference manual, we describe two types of product
certifications and how they relate to FLEX Ex products:
• CENELEC - European Electrotechnical Committee for
Standardization. This is the standard in all European Union
countries.
• UL and cUL - Underwriters Laboratories (UL in the United
States and cUL in Canada)
All FLEX Ex products are certified to CENELEC, UL and cUL standards.
What are Entity
Parameters?
Entity parameters provide a system of quantifying and matching safe
levels for voltage, current, inductance, and capacitance when
connecting field devices and system devices together.
FLEX Ex uses entity parameters to quantify safe levels when
connecting I/O modules to field devices. Inputs and outputs are
specified with:
• open-circuit voltage (Uo or Voc)
• short-circuit current (Io or Isc)
• allowed capacitance (Co or Ca)
• allowed inductance (Lo or La)
Switched outputs are specified as if they were inputs.
1
Publication 1797-6.5.6 - November 2000
2
Preface
Field devices using entity parameters are specified with:
• maximum input voltage (Ui or Vmax)
• maximum input current (Ii or Imax)
• maximum internal capacitance (Ci)
• maximum internal inductance (Li)
In use, the sum of all the input Ci and Li in a control loop cannot
exceed the Co and Lo. Also, the sum of all the Uo and Io cannot
exceed the input Ui and Ii.
The following is a short explanation of how entity-based architectures
help simplify IS system design.
Entity Parameters Example
An output channel and the valve it will drive are illustrated in the
following figure. By comparing entity parameters, you can quickly
determine the appropriate match.
cable length = 10m
+
268Ω
21V
P/I transmitter
EEx ia IIC T4
Ui=30V
Ii=165mA
Ci=22.5nF
Li=730uH
Ci<10pF/m
Li<0.5uH/m
R<0.1Ω/m
sig
22Ω
1797-IE8 Analog Input
EEx ia/ib IIB/IIC T4
Uo<23.7V
Io<93.5mA
IIB
Ca=560nF
La=10mH
IIC
Ca=66nF
La=2.5mH
Module
Uo
Io
Ca
La
< or =
< or =
> or =
> or =
Module
Uo<23.7V
Io<92.5mA
Ca=66nF
La=2.5mH
< or =
< or =
> or =
> or =
Total Loop
Ui
Ii
Ci
Li
=
=
=
=
Total Loop
Ui=30V
Ii=165mA
Ci=22.6nF
Li=735uH
=
=
=
=
Transmitter
Ui
Ii
Ci
+
Li
+
Distance
Transmitter
Ui=30V
Ii=165mA
Ci=22.5nF +
+
Li=730uH
Distance
Cable
(length
*
Ci per length)
(length
*
La per length)
Cable
(10m
*
Ci=10pF/m)
(10m
*
La =0.5uH/m)
40052
Publication 1797-6.5.6 - November 2000
Preface
3
In this example, the combination is compatible because the valve can
withstand:
• Ui
• Ii
=
30V
=
165mA
These values are higher than what the 1797-IE8 can provide:
• Uo =
• Io =
23.7V
93.5mA
In the same way, the valve is characterized by:
• Ci
=
22.5nF
• Li
=
730µH
These values are lower than what the 1797-IE8 allows:
Intrinsic Safety
Terminology
• Co =
66nF
• Lo
2.5mH
=
The following sections describe key terms used in this reference
manual:
Hazardous Area Designation
A hazardous area is designated as any location in which a combustible
material is or may be present in the atmosphere in sufficient
concentration to produce an ignitable mixture.
The North American method identifies these areas by Class, Division,
and Group while the IEC (CENELEC) designates these areas by Zone
and Gas Group.
Recently, North America has adopted the Zone method of identifying
hazardous locations as an option to the Division method.
Publication 1797-6.5.6 - November 2000
4
Preface
Class Designation
Class identifies the type of hazardous atmosphere.
Class I
Gas or vapor
Class I
Dust
Class III
Fiber or flying (no group designation)
Division/Zone Designations
Division/Zone identifies the likelihood of a hazardous atmosphere
being present.
Division Method
(North America)
Ignitable mixture present continuously
(long periods)
Division 1
Ignitable mixture present intermittently
Ignitable mixture is not normally present
Division 2
IEC Standard
Zone Method
Zone 0
(Zone 20-Dust)
Zone 1
(Zone 21-Dust)
Zone 2
(Zone 22-Dust)
Gas/Dust Groups
Hazardous locations are grouped according to their ignition
properties.
Typical Gas
IEC Gas Group
North American Gas Group
Acetylene
IIC
A
Hydrogen
IIC
B
Ethylene
IIB
C
Propane
IIA
D
Methane1
I
D1
Metal Dust
-
E
Coal Dust
-
F
Grain Dust
-
-
1
Publication 1797-6.5.6 - November 2000
Mining applications under jurisdiction of MSHA.
Preface
5
FLEX Ex usage in Class II and III (Dusts and Fibers) Hazardous Locations
(North America)
FLEX Ex modules are rated for installation in Class I Division 1 & 2,
Groups A-D hazardous areas. They are also rated to connect to field
devices that are located in Class I, II, or III, Groups A-G hazardous
areas.
If FLEX Ex components are installed in a Class II or III location in your
application, you can mount them in a suitable, dust-proof enclosure
with the appropriate connectors, glans, and seals. For example, a
NEMA 4 enclosure may be appropriate.
As always, observe local code requirements when applying your FLEX
Ex application.
FLEX Ex usage in Zone Method Dusts and Fibers Hazardous Locations
FLEX Ex modules are rated for installation in North American Class I
Zone 1 & 2, Groups IIC, IIB & IIA and European Zone 1 & 2, Groups
IIC, IIB, & IIA hazardous areas. They are also rated to connect to field
devices that are located in North American Class I Zone 0, 1, & 2
Groups IIC, IIB & IIA and European Zone 0, 1, & 2, Groups IIC, IIB, &
IIA hazardous areas.
If FLEX Ex components are installed in a North American or European
Zone method dust or fiber location in your application, you can
mount them in a suitable enclosure with the appropriate connectors,
glans, and seals. For example, a North American NEMA 4 or better
enclosure may be appropriate.
As always, observe local code requirements when applying your FLEX
Ex application.
For Zone application, especially in Europe, normal practice calls for
the end application to obtain the dust and fiber rating due to strong
dependence on wiring and other non-equipment related
requirements. For example, FLEX Ex’s North American Class I Zone 0,
1, & 2 Groups IIC, IIB & IIA and European Zone 0, 1, & 2, Groups IIC,
IIB & IIA hazardous area rating is used as the basis for the overall
application to gains its dust and fiber certification.
Publication 1797-6.5.6 - November 2000
6
Preface
Methods of Protection
The following techniques are rated by methods of protection.
Technique
IEC Symbol for
Protection Method
Permitted Zone
Permitted Division
Oil Immersion
Ex o
1 and 2
*
Pressurization
Ex p
1 and 2
1 and 2
Powder Filling
Ex q
1 and 2
*
Flameproofing
(Explosion Proof)
Ex d
1 and 2
1 and 2
Increased Safety
Ex e
1 and 2
*
Intrinsic Safety
Ex ia
0, 1, and 2
1 and 2
Intrinsic Safety
Ex ib
1 and 2
*
Non-Incendive
Ex n
2
2
Encapsulation
Ex m
1 and 2
*
Special Protection
Ex s
0, 1, and 2
*
*
These protection methods are not recognized in the Division method. However, they may be
suitable for some North American Division applications.
Temperature Category
The temperature category defines the maximum surface temperature
of the device. Ratings are given with reference to 40oC ambient unless
otherwise stated.
T1
450oC (842oF)
T3A
180oC (356oF)
T2
300oC (572oF)
T3B
165oC (329oF)
T2A
280oC (536oF)
T3C
160oC (320oF)
T2B
260oC (500oF)
T4
135oC (275oF)
T2C
230oC (446oF)
T4A
120oC (248oF)
T2D
215oC (419oF)
T5
100oC (212oF)
T3
200oC (392oF)
T6
85oC (185oF)
The additional temperature categories highlighted above are for North America only.
Publication 1797-6.5.6 - November 2000
Preface
Understanding the Layout
of this Manual
7
This reference manual consists of two sections:
• CENELEC Certification Information
• UL, cUL Certification Information
Each section details the specific certification for each FLEX Ex product
as shown in the following tables:
CENELEC Certification Information
For Information On
CENELEC Certification Information
Refer to this Chapter
General CENELEC Certification Information
ControlNet Ex System
1797-TB3 1797-TB3 FLEX Ex Terminal Base Unit
1797-TB3S 1797-TB3S FLEX Ex Terminal Base Unit
1797-IBN16 1797-IBN16 FLEX Ex 16 NAMUR Input
Module
1
2
3
4
5
1797-OB4D 1797-OB4D FLEX Ex 24V dc Non-Isolated
Source 4 Output Module
6
1797-IE8 1797-IE8 FLEX Ex 8 Input Analog Module
7
8
1797-IE8NF 1797-IE8NF FLEX Ex 8 Input Analog
Module with Noise Filter
1797-OE8 1797-OE8 FLEX Ex 8 Output Analog
Module
1797-IRT8 1797-IRT8 FLEX Ex Thermocouple/RTD
Input Module
1797-IJ2 1797-IJ2 FLEX Ex Frequency Input Module
1797-PS2E 1797-PS2E FLEX Ex Power Supply
1797-ACNR15 1797-ACNR15/B ControlNet Ex Redundant
Media Adapter
1797-RPA, 1797-RPA ControlNet Ex Modular Repeater
-RPFM Adapter and 1797-RPFM Fiber Repeater
Module, Medium Distance
9
10
11
12
13
14
Publication 1797-6.5.6 - November 2000
8
Preface
UL, cUL Certification Information
For Information On
UL, cUL Certification Information
General UL, cUL Certification Information
ControlNet Ex System
1797-TB3 1797-TB3 FLEX Ex Terminal Base Unit
1797-TB3S 1797-TB3S FLEX Ex Terminal Base Unit
1797-IBN16 1797-IBN16 FLEX Ex 16 NAMUR Input
Module
15
16
17
18
19
1797-OB4D 1797-OB4D FLEX Ex 24V dc Non-Isolated
Source 4 Output Module
20
1797-IE8 1797-IE8 FLEX Ex 8 Input Analog Module
21
22
1797-IE8NF 1797-IE8NF FLEX Ex 8 Input Analog
Module with Noise Filter
1797-OE8 1797-OE8 FLEX Ex 8 Output Analog
Module
23
1797-IRT8 1797-IRT8 FLEX Ex Thermocouple/RTD
Input Module
24
1797-IJ2 1797-IJ2 FLEX Ex Frequency Input Module
1797-PS2N 1797-PS2N/A FLEX Ex Power Supply
1797-ACNR15 1797-ACNR15/B ControlNet Ex Redundant
Media Adapter
1797-RPA, 1797-RPA ControlNet Ex Modular Repeater
-RPFM Adapter and 1797-RPFM Fiber Repeater
Module, Medium Distance
Publication 1797-6.5.6 - November 2000
Refer to this Chapter
25
26
27
28
Table of Contents
CENELEC Certification Information
General CENELEC Certification
Information
ControlNet Ex System
1797-TB3 FLEX Ex
Terminal Base Unit
1797-TB3S FLEX Ex
Terminal Base Unit
1797-IBN16 FLEX Ex 16 NAMUR
Input Module
i
General Installation . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . .
Electrostatic Charge. . . . . . . . . . . . . . . . . . . . . . . . .
European Community Directive Compliance . . . . . .
Ex Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ControlNet Ex System Diagram . . . . . . . . . . . . . . . .
Describing the ControlNet Ex System Diagram . . . . .
Certified Equivalent ControlNet Ex System
Diagram Items . . . . . . . . . . . . . . . . . . . . . . . . . .
European Community Directive Compliance . . . . . .
Ex Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . .
Electrostatic Charge. . . . . . . . . . . . . . . . . . . . . . . . .
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . .
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . .
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . .
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit. .
General Specifications . . . . . . . . . . . . . . . . . . . . . . .
CE/CENELEC I/O Entity Parameters (Each Channel) .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
1-1
1-2
1-2
1-2
1-2
1-3
2-2
2-3
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
2-4
2-4
2-5
2-5
2-6
2-6
2-7
3-1
3-1
3-1
3-2
3-2
3-3
4-1
4-1
4-1
4-2
4-2
4-3
5-1
5-1
5-1
5-2
5-2
5-3
Publication 1797-6.5.6 - November 2000
Table of Contents
ii
1797-OB4D FLEX Ex 24V dc
Non-Isolated Source 4 Output
Module
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
CE/CENELEC I/O Entity Parameters . . . . . . . . . . . .
1797-IE8 FLEX Ex 8 Input Analog
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
CE/CENELEC I/O Entity Parameters . . . . . . . . . . . .
1797-IE8NF FLEX Ex 8 Input Analog General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module with Noise Filter
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
CE/CENELEC I/O Entity Parameters . . . . . . . . . . . .
1797-OE8 FLEX Ex 8 Output Analog General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
CE, CENELEC I/O Entity Parameters. . . . . . . . . . . .
1797-IRT8 FLEX Ex Thermocouple/ General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
RTD Input Module
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
CE/CENELEC I/O Entity Parameters . . . . . . . . . . . .
1797-IJ2 FLEX Ex Frequency Input General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
CE/CENELEC Input I/O Entity Parameters . . . . . . .
Channel 0 Frequency Input . . . . . . . . . . . . . . .
Channel 1 Frequency Input . . . . . . . . . . . . . . .
Channel 0 Gate Input. . . . . . . . . . . . . . . . . . . .
Channel 1 Gate Input. . . . . . . . . . . . . . . . . . . .
Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1797-6.5.6 - November 2000
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
6-1
6-1
6-1
6-1
6-2
6-2
7-1
7-1
7-1
7-2
7-2
7-3
8-1
8-1
8-1
8-2
8-2
8-3
9-1
9-1
9-1
9-1
9-2
9-2
10-1
10-1
10-1
10-2
10-2
10-3
11-1
11-1
11-1
11-2
11-2
11-3
11-3
11-4
11-5
11-5
11-6
Table of Contents
1797-PS2E FLEX Ex Power Supply
1797-ACNR15/B ControlNet Ex
Redundant Media Adapter
1797-RPA ControlNet Ex Modular
Repeater Adapter and 1797-RPFM
Fiber Repeater Module, Medium
Distance
Installation in Zone 1 . . . . . . . . . . . . . . . . .
European Community Directive Compliance
Ex Directive. . . . . . . . . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Wiring Configurations . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . .
European Community Directive Compliance
Ex Directive. . . . . . . . . . . . . . . . . . . . . .
Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . .
European Community Directive Compliance
Ex Directive. . . . . . . . . . . . . . . . . . . . . .
Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
iii
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
12-1
12-2
12-2
12-2
12-3
12-3
13-1
13-2
13-2
13-2
13-3
14-1
14-2
14-2
14-2
14-3
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Division 1/Zone 1 . . . . . . . . . . . . . . .
Electrostatic Charge. . . . . . . . . . . . . . . . . . . . . . . . .
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.......................................
ControlNet Ex System Diagram . . . . . . . . . . . . . . . .
Describing the ControlNet Ex System Diagram . . . . .
Certified Equivalent ControlNet Ex System
Diagram Items . . . . . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters and Requirements
Installation in Division 1/Zone 1 . . . . . . . . . . . . . . .
Electrostatic Charge. . . . . . . . . . . . . . . . . . . . . . . . .
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Division 1/Zone 1 . . . . . . . . . . . . . . .
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
15-1
15-2
15-2
15-2
16-1
16-2
16-3
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
16-4
16-5
16-5
16-6
16-6
17-1
17-1
17-1
17-2
17-2
17-3
UL, cUL Certification Information
General UL, cUL Certification
Information
ControlNet Ex System
1797-TB3 FLEX Ex
Terminal Base Unit
Publication 1797-6.5.6 - November 2000
Table of Contents
iv
1797-TB3S FLEX Ex
Terminal Base Unit
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Division 1/Zone 1 . . . . . . . . . . . . . .
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . .
1797-IBN16 FLEX Ex 16 NAMUR
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Input Module
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1797-OB4D FLEX Ex 24V dc
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Non-Isolated Source 4 Output
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1797-IE8 FLEX Ex 8 Input Analog
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1797-IE8NF FLEX Ex 8 Input Analog General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module with Noise Filter
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1797-OE8 FLEX Ex 8 Output Analog General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Module
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1797-6.5.6 - November 2000
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
18-1
18-1
18-1
18-2
18-2
18-3
19-1
19-1
19-1
19-1
19-2
19-3
19-3
19-4
20-1
20-1
20-1
20-1
20-2
20-2
20-2
20-4
21-1
21-1
21-1
21-1
21-2
21-3
21-3
21-4
22-1
22-1
22-1
22-2
22-2
22-3
22-3
22-4
23-1
23-1
23-1
23-1
23-2
23-2
23-2
23-4
Table of Contents
v
1797-IRT8 FLEX Ex Thermocouple/ General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-1
Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-1
RTD Input Module
1797-IJ2 FLEX Ex Frequency Input
Module
1797-PS2N/A FLEX Ex
Power Supply
1797-ACNR15/B ControlNet Ex
Redundant Media Adapter
1797-RPA ControlNet Ex Modular
Repeater Adapter and 1797-RPFM
Fiber Repeater Module, Medium
Distance
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring to a 1797-TB3 or -TB3S Terminal Base Unit.
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation in Division 1/Zone 1 . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Wiring Configurations . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL I/O Entity Parameters . . . . . . . . . . . . . . . .
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL Entity Parameters and Requirements . . . . .
Module Installation . . . . . . . . . . . . . . . . . . . . . . . .
Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications . . . . . . . . . . . . . . . . . . . . . .
UL, cUL Entity Parameters and Requirements . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
24-1
24-2
24-2
24-3
24-3
24-5
25-1
25-1
25-1
25-1
25-2
25-2
25-3
25-4
26-1
26-1
26-1
26-2
26-2
26-2
27-1
27-1
27-1
27-2
28-1
28-1
28-2
28-2
Publication 1797-6.5.6 - November 2000
Table of Contents
vi
Notes:
Publication 1797-6.5.6 - November 2000
Chapter
1
General CENELEC Certification Information
(1) keyswitch
(8) flexbus
cover
(2) terminal
base unit
Label here or under here
General Installation
40231
FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S
intrinsically safe terminal base unit.
You will need to rotate the keyswitch (1) to the correct position
depending on the module. Refer to the module’s installation
instructions for more information. Do not change the position of
the keyswitch after wiring the terminal base unit.
Make certain that you only connect terminal base units to other
intrinsically safe system modules, adapters or power supplies to
maintain the integrity of the intrinsically-safe backplane.
41307
Remove cap plug and attach another intrinsically safe terminal base
unit to the right of the terminal base unit (2) if required.
Do not remove the flexbus cover (8) on the right-most terminal base
unit.
CENELEC Certification Information1
Publication 1797-6.5.6 - November 2000
1-2
General CENELEC Certification Information
Installation in Zone 1
Modules, adapters, and terminal base units must not be exposed to
the environment. Provide a suitable enclosure. The modules, adapters,
and terminal base units have a protection factor of IP20.
ATTENTION
!
Modules, adapters, and terminal base units cannot be
used in an intrinsically safe environment after they
have been exposed to non-intrinsically safe signals.
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near each
module: Attention! Avoid electrostatic charge. For your
convenience, a sign which can be cut out and posted is included in
this chapter.
European Community
Directive Compliance
If this product has the CE mark it is approved for installation within
the European Community or EEA regions. It has been designed and
tested to meet the following directives.
Ex Directive
All system components, expect the power supply, are tested to meet
the Council Directive 94/9/EC (ATEX 100a) Equipment and Protective
Systems Intended for Use in Potentially Explosive Atmospheres by
applying the following standards, as appropriate:
• EN50014:1992, Electrical Apparatus for Potentially Explosive
Atmospheres
• EN50020:1994, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsic Safety “i”
• EN50039:1980, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsically Safe Electrical Systems “i”
• prEN50284:1997, Special requirements for construction, test and
marking of electrical apparatus of equipment group II, category
1G
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
General CENELEC Certification Information
1-3
The power supply is tested to meet the Council Directive 76/117/EC
Electrical Apparatus for Explosive Atmospheres by applying the
following standards:
• EN50014:1977 + A1-A5, Electrical Apparatus for
Explosive Atmospheres
• EN50018:1977 + A1-A3, Electrical Apparatus for
Explosive Atmospheres - Flameproof Enclosure
• EN50019:1977 + A1-A5, Electrical Apparatus for
Explosive Atmospheres - Increased Safety “e”
• EN50020:1977 + A1-A5, Electrical Apparatus for
Explosive Atmospheres - Intrinsic Safety “i”
Repair
Potentially
Potentially
“d”
Potentially
Potentially
System components are not field-repairable. Any attempt to open a
system component will void the warranty and the IS certification. If
repair is necessary, return the system component to the manufacturer.
Attention: Avoid electrostatic charge.
ATTENTION
!
ATTENTION
!
CENELEC Certification Information
When installing, commissioning, operating, and
maintaining devices with intrinsically safe circuits,
the certificate of conformity of the devices, as well as
the applicable national and local construction,
installation, and operating regulations must be
heeded (in Germany DIN EN 50020, DIN VDE 0165).
Repairs to devices having intrinsically safe circuitry
may only be carried out by qualified personnel in
accordance with the valid regulations (Elex V).
Publication 1797-6.5.6 - November 2000
1-4
General CENELEC Certification Information
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
2
ControlNet Ex System
Bus Connectors
Adapter
Terminal Base
Keyswitch
Flexbus Connector
Ex I/O Module
1797-ACNR15
Ex
PWR
PWR
Terminal Strips
Field Power
Connection Terminals
CENELEC Certification Information1
20125-M
Publication 1797-6.5.6 - November 2000
Publication 1797-6.5.6 - November 2000
30670-M
Hazardous Area
Zone 0
Safe Area
CNet Ex
tap trm
Ci < 68pF
Li negl.
Li < 1100uH
Li < 560nH
Ci < 60pF
ControlNet Ex tap
Ch0
fiber
.
Ch1
fiber
Ch0
fiber
ControlNet Ex
tap
.
.
Ch1
fiber
.
Flexbus
Uo=5.4V,
Io=400mA,
Po=2.16W,
Co=65µF,
Lo=10µH
ControlNet Ex
tap
ChB
Power Supply Ui=9.5V,
Uo=5.4V,
Ii=1A,
Io=160mA,
Ci<120nF,
F-3>500kHz
Li=negligible
.
1
.
ChA
Uo=5.4V,
Io=160mA,
F-3>500kHz
.
.
.
Flexbus
Uo=5.4V,
Io=400mA,
Po=2.16W,
Co=65µF,
Lo=10µH
ControlNet Ex
tap
CNet Ex
trk trm
ChB
Power Supply Ui=9.5V,
Uo=5.4V,
Ii=1A,
Io=160mA,
Ci<120nF,
F-3>500kHz
Li=negligible
.
Node 4 ... 48
1797-ACNR15/* or
RSD-GW-Ex2.CN
*RG6-CNet is defined as: Cable Impedance = 75 Ohm + or - 3 Ohm
Cable Capacitance <5.94nF per 100m
Cable Resistance >9.08 Ohm per 100m
Cable Attenuation (-20 to +70oC) 0.2MHz > 0.93dB/100m
0.5MHz > 0.95dB/100m
1MHz > 1.07dB/100m
2MHz > 1.16dB/100m
5MHz > 1.39dB/100m
10MHz > 1.86dB/100m
20MHz > 2.73dB/100m
50MHz > 4.33dB/100m
Near the main components of the system a plate with the system marking must be attached. If
the system is installed in a cabinet the plate must be fixed on the inside of the cabinet door.
The ambient temperature range of the ControlNet Ex system is -20 to +70oC.
ControlNet Ex Taps dropping to only 250m with the maximum allowed connected ControlNet Ex
Taps of 48.
ChA
Uo=5.4V,
Io=160mA,
F-3>500kHz
.
.
Node 3
1797-ACNR15/* or
RSD-GW-Ex2.CN
Protect the system against electrostatic charge. Post a sign near the main components of the system:
Attention! Avoid electrostatic charge.
For the transmittal between the safe area and the hazardous area only optical glass-fibers are
permitted. The diameter of a single glass-fiber must be >6um. The power density of the transmitter
diode must be <5mW/mm2.
The ControlNet Ex System is an intrinsically safe system according to EN 50039. When installing the
system, the certificate of conformity and the national installation regulations must be heeded. The
components of the ControlNet Ex system and the interconnections are shown on the installation
drawing (A-B Pub. 1797-6.5.6).
75 Ohm
coax trunk cable
1W
coax trunk cable
Ci negl.
Cable type 1189A, 3092A, or
Li negl.
3092A Blue from manufacturer
Belden Wire or type RG6-CNet* The Coax Trunk Cable is permitted to have a maximum length of 1,000m with only 2 connected
.
1797-RPFM/* or
1797-RPFM/* or
RSD-FC-Ex2.CN 3km RSD-FC-Ex2.CN 3km
Power Supply Ui=9.5V,
Ii=1A,
Ci<120nF,
Li=negligible
.
Li < 1100uH
Node 1
75 Ohm
1W
Ci negl.
Li negl.
CNet Ex
trk trm
Uo=5.4V,
Io=201mA,
F-3>500kHz
.
.
Node 2
1797-RPA/* or
RSD-CFA-Ex.CN
Hazardous Area
Zone 1
2-2
ControlNet Ex System
ControlNet Ex System
Diagram
CENELEC Certification Information
ControlNet Ex System
Describing the ControlNet
Ex System Diagram
2-3
A maximum of 48 ControlNet ExTM nodes may be connected together
by 250m of coax cable and 48 taps. The distance increases to 1000m
when you use only 2 taps. See the table below for more information.
The fiber media of the 1797-RPFM can be installed in a hazardous
location (Zone 0, 1 or 2; Class I, Zones 0, 1, and 2; Class I, Division 1
and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect
two 1797-RPFM modules or they can be installed through different
locations into the non-hazardous location to connect the 1797-RPFM
with any approved associated apparatus.
All cables and fiber media that are not light blue must be marked as IS
using the 1797-EXMK marking kit or other locally approved IS
identification and/or segregation method.
During the installation of the ControlNet Ex system, all metallic parts
must be isolated to prevent an earth connection (high voltage
withstanding of isolating material must be > 500V ac).
System
Diagram
Name
1797-RPA
Catalog Number Catalog Name
1797-RPFM
1797-RPFM
1797-RPA
1797-ACNR15 1797-ACNR15
CNet Ex
Tap Trm
1797-TCAP
ControlNet Ex
Tap
1797-TPx
CNet Ex
Trk Trm
1797-XT
Coax Trunk
Cable
1797-RG6
None
None
CENELEC Certification Information
Description
ControlNet Ex Modular Represents one ControlNet Ex node and
Repeater Adapter
must be connected to a coax trunk cable
by
1797-TPx
ControlNet Ex Fiber
Allows connection of a maximum of two
Repeater Module,
devices per 1797-RPA and is powered
Medium Distance
directly by 1797-RPA
Redundant Media
Represents one ControlNet Ex node and
ControlNet Ex Adapter must be connected to a coax trunk cable
by
1797-TPx -each one with two redundant
output channels that are connected to
different ControlNet Ex networks (coax
cables and 1797-TPx)
ControlNet Ex Tap
Represents one ControlNet Ex node and is
(Dummy) Terminator a simple capacitor (56pF) with a coax
connector
ControlNet Ex Coax Tap Four types of connections available: S
(straight t-tap), R (right angle t-tap), YS
(straight y-tap), and YR (right angle y-tap)
- a maximum of 48 taps can be connected
together by coax trunk cable
ControlNet Ex Trunk
Simple resistor (75Ω) with coax connector
Terminator
that must be on each end of the ControlNet
Ex coax trunk for termination
Quad-Shield, RG-6
Maximum (functional) length between 2
75Ω Coax Trunk Cable 1797-TPx is 3280ft (1000m) - each
1797-TPx reduces the (functional) coax
cable length by 53.4ft (16.3m)
Standard Coax Trunk Different standard cable couplers, 90o,
Cable BNC Couplers
180o, etc.
Publication 1797-6.5.6 - November 2000
2-4
ControlNet Ex System
Certified Equivalent ControlNet Ex System Diagram Items
You may use these items as equivalents for the items shown on the
system diagram.
System Diagram Name
Catalog Number
Source
1797-RPA
1797-RPA
Allen-Bradley
RSD-CFA-Ex.CN
Pepperl+Fuchs
1797-RPFM
Allen-Bradley
RSD-FC-Ex2.CN
Pepperl+Fuchs
1797-ACNR15
Allen-Bradley
RSD-GW-Ex2.CN
Pepperl+Fuchs
1797-RG6
Allen-Bradley
3092A2
Belden Wire & Cable Co.
3092A with blue jacket
Belden Wire & Cable Co.
1797-TPx
Allen-Bradley
RS-TPx-Ex
Pepperl+Fuchs
1797-XT
Allen-Bradley
RS-XT-Ex
Pepperl+Fuchs
1797-TCAP
Allen-Bradley
RS-TCAP-Ex
Pepperl+Fuchs
1797-RPFM
1797-ACNR15
Coax Trunk Cable
1
ControlNet Ex Tap
CNet Ex Trk Trm
CNet Ex Tap Trm
1
2
European Community
Directive Compliance
Publication 1797-6.5.6 - November 2000
In addition to these cable types, the following specification can be followed to allow additional types:
Cable Impedance = 75Ω ± 3Ω
Cable Capacitance = <5.94nF per 100m
Cable Resistance = >9.08Ω per 100m
5MHz > 1.39dB/100m
Cable Attenuation
0.2MHz > 0.93dB/100m
0.5MHz > 0.95dB/100m
10MHz > 1.86dB/100m
(-20 to +70oC)
20MHz > 2.73dB/100m
1MHz > 1.07dB/100m
50MHz > 4.33dB/100m
2MHz > 1.16dB/100m
Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.
If this product has the CE mark it is approved for installation within
the European Community or EEA regions. It has been designed and
tested to meet the following directives.
CENELEC Certification Information
ControlNet Ex System
2-5
Ex Directive
This product is tested to meet the Council Directive 94/9/EC (ATEX
100a) Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres by applying the following
standards:
• EN50014:1992, Electrical Apparatus for Potentially Explosive
Atmospheres
• EN50020:1994, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsic Safety “i”
• EN50039:1980, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsically Safe Electrical Systems “i”
• prEN50284:1997, Special requirements for construction, test and
marking of electrical apparatus of equipment group II, category
1G
Installation in Zone 1
Modules must not be exposed to the environment. Provide a suitable
metal enclosure. A label with this system marking must be attached
near the main components of the system. If the system is installed in a
cabinet, this label must be fixed inside the cabinet.
Allen-Bradley
1 Allen-Bradley Dr.
Mayfield Hts., OH USA
ControlNet Ex System
DMT 99 ATEX E 065 X
II (1) 2G SYST EEx ia/ib IIB/C T4
0102
-200C <= Ambient Temperature <= +700C
Attention!
Avoid electrostatic charging!
ATTENTION
!
CENELEC Certification Information
Modules cannot be used in an intrinsically safe
environment after they have been exposed to
non-intrinsically safe signals.
Publication 1797-6.5.6 - November 2000
2-6
ControlNet Ex System
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near each
module: Attention! Avoid electrostatic charge. For your
convenience, a sign which can be cut out and posted is included in
this chapter.
Repair
Modules are not field-repairable. Any attempt to open a module will
void the warranty and the IS certification. If repair is necessary, return
the module to the manufacturer.
Attention: Avoid electrostatic charge.
ATTENTION
!
ATTENTION
!
Publication 1797-6.5.6 - November 2000
When installing, commissioning, operating, and
maintaining devices with intrinsically safe circuits,
the certificate of conformity of the devices, as well as
the applicable national and local construction,
installation, and operating regulations must be
heeded (in Germany DIN EN 50020, DIN VDE 0165).
Repairs to devices having intrinsically safe circuitry
may only be carried out by qualified personnel in
accordance with the valid regulations (Elex V).
CENELEC Certification Information
ControlNet Ex System
General Specifications
2-7
For a full list of specifications, refer to ControlNet Ex Redundant
Media Adapter Installation Instructions, publication 1797-5.14.
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
II (1) 2G SYST EEx ia/ib IIB/IIC T4
Certificates
DMT 99 ATEX E 065 X
CENELEC Certification Information
Publication 1797-6.5.6 - November 2000
2-8
ControlNet Ex System
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
3
1797-TB3 FLEX Ex Terminal Base Unit
(1) keyswitch
Label here
(8) flexbus
cover
0
1 2 3 4 5
6 7
8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
42332
General Information
FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S
intrinsically safe terminal base unit.
Module Installation
You will need to rotate the keyswitch (1) to the correct position
depending on the module. Refer to the module’s installation
instructions for more information. Do not change the position of
the keyswitch after wiring the terminal base unit.
Make certain that you only connect terminal base units to other
intrinsically safe system modules or adapters to maintain the integrity
of the intrinsically-safe backplane.
41307
Installation in Zone 1
Do not remove the flexbus cover (8) on the right-most terminal base
unit.
CENELEC Certification Information1
Publication 1797-6.5.6 - November 2000
3-2
1797-TB3 FLEX Ex Terminal Base Unit
Inputs
Do not apply any non-instrinsically safe signals to the terminal
base.
When using as an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The terminals in the terminal base unit may be electrically connected
to each other by the insertion of FLEX Ex I/O modules. See the
module installation instructions to determine this.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety requirements.
IMPORTANT
Description
The 1797-TB3 terminal base has 36 wiring connections to/from a
plug-in module. The use of each terminal depends on the module
mounted in this base.
The 1797-TB3 terminal base also has connections for cold junction
compensation and terminals designated for shield termination to
chassis ground.
The terminal base is equipped with a factory-installed tab cover for
the backplane bus connection. The tab cover may be removed only
when the terminal base unit is connected to other terminal base units..
Wiring Connections for Terminal Base 1797-TB3
0
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
A
16 17
18 19 20
21 22 23
24 25 26
27 28 29 30 31 32 33
B
34 35
36 37 38
39 40 41
42 43 44
45 46 47 48 49 50 51
C
+V -V
ATTENTION
!
Publication 1797-6.5.6 - November 2000
+V -V
No connections allowed to terminals 36 and 49
41252
• Make certain that you power the terminal base
unit with an intrinsically safe power supply. Do
not exceed the values listed in the specifications
for the terminal base unit.
• Do not use the unused terminals on the terminal
base unit. Using these terminals as supporting
terminals can result in damage to modules and/or
unintended operation of your system.
CENELEC Certification Information
1797-TB3 FLEX Ex Terminal Base Unit
Intrinsically Safe
Specifications
3-3
For a full list of specifications, refer to the FLEX Ex Terminal Base
Installation Instructions, publication 1797-5.1.
Terminals Assignments
+34, -35, +50, -51, and 96
pinifemale I/O connector
pinsi30-32, 62-64, 94-96i
36, 49
All Other Terminals
Only for intrinsically safe circuits
Ui
<10V dc
<2.5A
Ii
< 1nF
Ci
Negligible
Li
Must not be used for any connection
<30V dc
Ui
<100mA
Ii
<1nF
Ci
Negligible
Li
<10V dc
<400mA
<1nF
Negligible
Flexbus Connection Intrinsically Safe
Ui
Ii
Ci
Li
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
II 2G EEx ia IIC T4
Certificates
DMT 98 ATEX E012 U
CENELEC Certification Information
Publication 1797-6.5.6 - November 2000
3-4
1797-TB3 FLEX Ex Terminal Base Unit
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
4
1797-TB3S FLEX Ex Terminal Base Unit
(1) keyswitch
(8) flexbus
cover
Label here
42333
General Information
FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S
intrinsically safe terminal base unit.
Module Installation
You will need to rotate the keyswitch (1) to the correct position
depending on the module. Refer to the module’s installation
instructions for more information. Do not change the position of
the keyswitch after wiring the terminal base unit.
Make certain that you only connect terminal base units to other
intrinsically safe system modules or adapters to maintain the integrity
of the intrinsically-safe backplane.
41307
Installation in Zone 1
Do not remove the flexbus cover (8) on the right-most terminal base
unit.
CENELEC Certification Information1
Publication 1797-6.5.6 - November 2000
4-2
1797-TB3S FLEX Ex Terminal Base Unit
Inputs
Do not apply any non-instrinsically safe signals to the terminal
base.
When using as an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The terminals in the terminal base unit may be electrically connected
to each other by the insertion of FLEX Ex I/O modules. See the
module installation instructions to determine this.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety requirements.
IMPORTANT
Description
The 1797-TB3S terminal base has 36 wiring connections to/from a
plug-in module. The use of each terminal depends on the module
mounted in this base.
The 1797-TB3S terminal base also has connections for cold junction
compensation and terminals designated for shield termination to
chassis ground.
The terminal base is equipped with a factory-installed tab cover for
the backplane bus connection. The tab cover may be removed only
when the terminal base unit is connected to other terminal base units.
Wiring Connections for Terminal Base 1797-TB3S
0
1
16
17
34
35
2
18
36
3
4
5
6
7
8
9
10
11
12
13
14
19
20
21
22
23
24
25
26
27
28
29
30
15
31
32
37
38
39
40
41
42
43
44
45
46
47
48
49
50 51
33
Row A
Row B
Row C
Label placed at top of wiring area
Row A
Row B
Row C
+V -V
+V -V
No connections allowed to terminals 36 and 49
ATTENTION
!
Publication 1797-6.5.6 - November 2000
41254
• Make certain that you power the terminal base
unit with an intrinsically safe power supply. Do
not exceed the values listed in the specifications
for the terminal base unit.
• Do not use the unused terminals on the terminal
base unit. Using these terminals as supporting
terminals can result in damage to modules and/or
unintended operation of your system.
CENELEC Certification Information
1797-TB3S FLEX Ex Terminal Base Unit
Intrinsically Safel
Specifications
4-3
For a full list of specifications, refer to the FLEX Ex Spring Clamp
Terminal Base Installation Instructions, publication 1797-5.2.
Terminals Assignments
+34, -35, +50, -51, and 96
pinifemale I/O connector
pinsi30-32, 62-64, 94-96i
36, 49
All Other Terminals
Only for intrinsically safe circuits
Ui
<10V dc
<2.5A
Ii
< 1nF
Ci
Negligible
Li
Must not be used for any connection
<30V dc
Ui
<100mA
Ii
<1nF
Ci
Negligible
Li
<10V dc
<400mA
<1nF
Negligible
Flexbus Connection Intrinsically Safe
Ui
Ii
Ci
Li
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
II 2G EEx ia IIC T4
Certificates
DMT 98 ATEX E012 U
CENELEC Certification Information
Publication 1797-6.5.6 - November 2000
4-4
1797-TB3S FLEX Ex Terminal Base Unit
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
5
1797-IBN16 FLEX Ex 16 NAMUR Input Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 6 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from a NAMUR sensor or a mechanical
contact (if mechanical inputs are used). Do not apply any
non-intrinsically safe signals to this module.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The channels in this module are electrically connected to each other
and have a common plus-line.
IMPORTANT
CENELEC Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - September 2000
5-2
1797-IBN16 FLEX Ex 16 NAMUR Input Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
3
4
5
+
-
+
-
+
17
18
19
20
21
22
+
-
+
-
+
-
6
7
8
9
10
11
12
13
14
15
+
-
+
-
Row A
Ch 0
16
Ch 1
-
+
Ch 2
-
+
23
24
25
26
27
28
29
30
+
-
+
-
+
-
+
-
Ch 3
-
+
Ch 4
-
Ch 5
Ch 6
Ch 7
31
32
33
Row B
Ch 8
34
Ch 9
35
36
Ch 10
37
38
Ch 11
39
40
Ch 12
41
42
Ch 13
43
44
+
Ch 14
45
46
-
Ch 15
47
48
49
50
51
Row C
41504
+V
-V
No connection allowed to terminals 36 and 49
ATTENTION
!
Instrinsically Safe
Specifications
Publication 1797-6.5.6 - September 2000
+V -V
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 16 NAMUR Input
Module Installation Instructions, publication 1797-5.7.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Ui < 5.8V
Ii < 400mA
Li = Negligible
Ci = Negligible
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci = Negligible
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 98 ATEX E 013 X
CENELEC Certification Information
1797-IBN16 FLEX Ex 16 NAMUR Input Module
CE/CENELEC I/O Entity
Parameters (Each Channel)
Protection
EEx ia
Uo < 14.5V
Io < 15mA
EEx ia
Po < 40mW
Characteristic:
linear
CENELEC Certification Information
5-3
Group
Allowed
Allowed
Lo/Ro Ratio
Capacitance Inductance
IIB
1µF
10mH
2.6mH/Ω
IIC
300nF
2mH
0.65mH/Ω
Publication 1797-6.5.6 - September 2000
5-4
1797-IBN16 FLEX Ex 16 NAMUR Input Module
Notes:
Publication 1797-6.5.6 - September 2000
CENELEC Certification Information
Chapter
6
1797-OB4D FLEX Ex 24V dc Non-Isolated
Source 4 Output Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 7 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Outputs
Each output can operate a discrete field device. Do not apply any
non-intrinsically safe signals to this module.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The channels in this module are electrically connected to each other.
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
+
-
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Row A
+
ch0
16
17
-
+
ch1
18
19
20
21
-
+
ch2
22
23
24
25
-
ch3
26
27
28
29
30
31
32
33
Row B
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
Row C
+V
-V
CENELEC Certification Information1
No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37,
38, 39, 46, 47, 48, 49
+V
-V
40068
Publication 1797-6.5.6 - November 2000
6-2
1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module
ATTENTION
!
Intrinsically Safe
Specifications
CE/CENELEC I/O Entity
Parameters
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 24V dc Non-Isolated
Source 4 Output Module Installation Instructions, publication 1797-5.6.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Ui < 5.8V
Ii < 400mA
Li = Negligible
Ci = 1.35µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci < Negligible
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 98 ATEX E 040 X
Signal output (+ to -) for ch 0 to ch 3 (terminals: 0-1; 4-5; 8-9; 12-13)
1797-OB4D
Uo = 27.4V
Io = 110mA
Protection
Group
Allowed
Allowed
Capacitance Inductance
EEx ia
IIB
677nF
8mH
IIC
87nF
2mH
IIB
150nF
5mH
IIC
30nF
2mH
If
EEx ia
concentrated
capacitance
and/or
inductance
are available,
use the
following
values.
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
7
1797-IE8 FLEX Ex 8 Input Analog Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 3 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from an analog field device signal. Do
not apply any non-intrinsically safe signals to this module.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The channels in this module are electrically connected to each other
and have a common plus-line.
IMPORTANT
CENELEC Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - November 2000
7-2
1797-IE8 FLEX Ex 8 Input Analog Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
+
sig
-
3
4
5
6
+
sig
-
7
8
9
10
11
12
13
14
+
sig
15
Row A
Ch 0
16
+ sig
Ch 1
17
18
19
+
sig
-
20
-
Ch 2
21
22
23
+
sig
-
24
25
-
Ch 3
26
27
28
29
30
31
+
sig
32
33
Row B
Ch 4
34
+ sig
Ch 5
35
36
37
38
39
-
Ch 6
40
41
42
-
Ch 77
43
44
45
46
47
48
49
50
51
Row C
40071
+V -V
+V -V
No connection
allowed
No connection
allowed
ATTENTION
!
Intrinsically Safe
Specifications
Publication 1797-6.5.6 - November 2000
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 8 Input Analog Module
Installation Instructions, publication 1797-5.5.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Ui < 5.8V
Ii < 400mA
Li = Negligible
Ci < 1.35µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci = Negligible
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 98 ATEX E 020 X
CENELEC Certification Information
1797-IE8 FLEX Ex 8 Input Analog Module
CE/CENELEC I/O Entity
Parameters
7-3
Measurement input (sig to -) for ch 0 to ch 7 (terminals: 1-2; 5-6; 9-10;
13-14; 18-19; 22-23; 26-27; 30-31)
Protection
EEx ia
Uo = 5V
Io = 1mA
Po = 1.3mW
Ui = 28V
Ii = 93mA
Ci and Li
negligible
Group
IIB
Allowed
Allowed
Capacitance Inductance
1000µF
1H
IIC
100µF
1H
Source output (+ to sig) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13;
17-18; 21-22; 25-26; 29-30)
Protection
EEx ia
Uo = 23.7V
Io = 92.5mA
Po = 548mW
If concentrated
EEx ia
capacitance and/
or inductance are
available, use the
following values.
IIB
IIC
Allowed
Capacitance
560nF
66nF
Allowed
Inductance
10mH
2.5mH
IIB
IIC
320nF
60nF
10mH
2mH
Group
Source output plus measurement input (+ to -) for ch 0 to ch 7
(terminals: 0-2; 4-6; 8-10; 12-14; 17-19; 21-23; 25-27; 29-31)
Protection
EEx ia
Uo = 23.7V
Io = 93.5mA
Po = 555mW
EEx ia
If concentrated
capacitance and/
or inductance are
available, use the
following values.
CENELEC Certification Information
Group
IIB
IIC
Allowed
Capacitance
560nF
66nF
Allowed
Inductance
10mH
2.5mH
IIB
IIC
320nF
60nF
10mH
2mH
Publication 1797-6.5.6 - November 2000
7-4
1797-IE8 FLEX Ex 8 Input Analog Module
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
8
1797-IE8NF FLEX Ex 8 Input Analog Module
with Noise Filter
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 3 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from an analog field device signal. Do
not apply any non-intrinsically safe signals to this module.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The channels in this module are electrically connected to each other
and have a common plus-line.
IMPORTANT
CENELEC Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - November 2000
8-2
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
+
sig
-
3
4
5
6
+
sig
-
7
8
9
10
11
12
13
14
+
sig
15
Row A
Ch 0
16
+ sig
Ch 1
17
18
19
+
sig
-
20
-
Ch 2
21
22
23
+
sig
-
24
25
-
Ch 3
26
27
28
29
30
31
+
sig
32
33
Row B
Ch 4
34
+ sig
Ch 5
35
36
37
38
39
-
Ch 6
40
41
42
-
Ch 77
43
44
45
46
47
48
49
50
51
Row C
40071
+V -V
+V -V
No connection
allowed
No connection
allowed
ATTENTION
!
Intrinsically Safe
Specifications
Publication 1797-6.5.6 - November 2000
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 8 Input Analog Module
with Noise Filter Installation Instructions, publication 1797-5.31.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Ui < 5.8V
Ii < 400mA
Li = Negligible
Ci < 1.35µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci = Negligible
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 98 ATEX E 020 X
CENELEC Certification Information
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
CE/CENELEC I/O Entity
Parameters
8-3
Measurement input (sig to -) for ch 0 to ch 7 (terminals: 1-2; 5-6; 9-10;
13-14; 18-19; 22-23; 26-27; 30-31)
Protection
EEx ia
Uo = 5V
Io = 1mA
Po = 1.3mW
Ui = 28V
Ii = 93mA
Ci and Li
negligible
Group
IIB
Allowed
Allowed
Capacitance Inductance
1000µF
1H
IIC
100µF
1H
Source output (+ to sig) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13;
17-18; 21-22; 25-26; 29-30)
Protection
EEx ia
Uo = 23.7V
Io = 92.5mA
Po = 548mW
If concentrated
EEx ia
capacitance and/
or inductance are
available, use the
following values.
IIB
IIC
Allowed
Capacitance
560nF
66nF
Allowed
Inductance
10mH
2.5mH
IIB
IIC
320nF
60nF
10mH
2mH
Group
Source output plus measurement input (+ to -) for ch 0 to ch 7
(terminals: 0-2; 4-6; 8-10; 12-14; 17-19; 21-23; 25-27; 29-31)
Protection
EEx ia
Uo = 23.7V
Io = 93.5mA
Po = 555mW
EEx ia
If concentrated
capacitance and/
or inductance are
available, use the
following values.
CENELEC Certification Information
Group
IIB
IIC
Allowed
Capacitance
560nF
66nF
Allowed
Inductance
10mH
2.5mH
IIB
IIC
320nF
60nF
10mH
2mH
Publication 1797-6.5.6 - November 2000
8-4
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
9
1797-OE8 FLEX Ex 8 Output Analog Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 4 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Outputs
Each output channel can operate an analog field device. Do not
apply any non-intrinsically safe signals to this module.
When using an intrinsically safe electrical apparatus according to
EN50020, the European Community directives and regulations must be
followed.
The channels in this module are electrically connected to each other.
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
3
4
5
+
-
6
7
8
9
10
11
12
13
14
15
Row A
+
-
ch0
16
17
+
ch1
18
19
20
-
+
ch2
21
22
+
-
23
24
25
-
ch3
26
27
28
29
30
31
32
33
Row B
+
ch4
+
ch5
34
35
+V
-V
36
37
38
-
+
ch7
ch6
39
40
41
42
-
43
44
45
46
47
48
49
50
51
Row C
CENELEC Certification Information1
No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23,
24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49
+V
-V
41440
Publication 1797-6.5.6 - November 2000
9-2
1797-OE8 FLEX Ex 8 Output Analog Module
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
ATTENTION
!
General Specifications
CE, CENELEC I/O Entity
Parameters
For a full list of specifications, refer to FLEX Ex 8 Output Analog
Module Installation Instructions, publication 1797-5.3.
Output (Intrinsically Safe)
(16 pin male and female
flexbus connector)
Ui < 5.8V dc
Ii < 400mA
Li = Negligible
Ci < 1.35µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci = Negligible
Operational Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 00 ATEX E 042 X
Signal output (+ to -) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13;
17-18; 21-22; 25-26; 29-30)
Protection
EEx ia
Uo = 21V
Io = 100mA
Po = 520mW
If concentrated
EEx ia
capacitance and/
or inductance are
available, use the
following values.
Publication 1797-6.5.6 - November 2000
Group
IIB
IIC
Allowed
Capacitance
1.27µF
188nF
Allowed
Inductance
8mH
2mH
IIB
IIC
295nF
70nF
10mH
2mH
CENELEC Certification Information
Chapter
10
1797-IRT8 FLEX Ex Thermocouple/RTD
Input Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 2 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from a thermocouple (TC) or resistance
temperature detector (RTD). Do not apply any non-intrinsically
safe signals to this module.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The channels in this module are electrically connected to each other
and have a common plus-line.
IMPORTANT
CENELEC Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - November 2000
10-2
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
+
H
L
3
4
5
-
+
H
6
7
8
9
+
H
10
11
12
13
14
15
Row A
Ch 0
16
L
-
Ch 1
17
18
19
20
21
+
H
L
-
+
22
L
-
+
H
Ch 2
23
24
L
-
Ch 3
25
26
27
+
H
L
28
29
30
+
H
31
32
33
Row B
H
Ch 4
L
-
Ch 5
34
35
+V
-V
36
37
38
39
-
Ch 6
40
41
42
43
L
-
Ch 7
44
45
46
47
48
49
50
51
Row C
CJC
CJC
0+ chassis 01+ chassis 1GND for
GND for
shield
shield
No connection allowed to terminals 36 and 49
ATTENTION
!
Intrinsically Safe
Specifications
Publication 1797-6.5.6 - November 2000
+V
-V
41505
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex Thermocouple/RTD
Input Module Installation Instructions, publication 1797-5.4.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Ui < 5.8V
Ii < 400mA
Li = Negligible
Ci < 1.35µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci = Negligible
Operational Temperature
-20 to +70oC (-4 to 158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 98 ATEX E 023X
CENELEC Certification Information
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
CE/CENELEC I/O Entity
Parameters
10-3
Input circuits (+ to -) for ch0 to ch7 (terminals: 0-3; 4-7; 8-11; 12-15;
17-20; 21-24; 25-28; 29-32)
Uo = 9V
Io = 37mA
Po = 83mW
Protection
Group
Allowed
Allowed
Lo/Ro Ratio
Capacitance Inductance
EEx ia
IIB
40µF
80mH
1.7mH/Ω
EEx ia
IIC
4.9µF
20mH
0.4mH/Ω
CJC circuits (+ to -) for CJC0 and CJC1 (terminals: 37, 39; 46, 48)
Uo = 9V
Io = 1mA
Po = 3mW
Protection
Group
Allowed
Allowed
Lo/Ro Ratio
Capacitance Inductance
EEx ia
IIB
40µF
1H
63mH/Ω
EEx ia
IIC
4.9µF
1H
15mH/Ω
Input circuits (+ to -) for ch0 to ch7 and CJC circuits (+ to -) for CJC0
and CJC1 (terminals 0-3, 37, 39; 4-7, 37, 39; 8-11, 37, 39; 12-15, 37, 39;
17-20, 37, 39; 21-24, 37, 39; 25-28, 37, 39; 29-32, 37, 39; 0-3, 46, 48;
4-7, 46, 48; 8-11, 46, 48; 12-15, 46, 48; 17-20, 46, 48; 21-14, 46, 48;
25-28, 46, 48; 29-32, 46, 48)
Uo = 9V
Io = 38mA
Po = 86mW
CENELEC Certification Information
Protection
Group
Allowed
Allowed
Lo/Ro Ratio
Capacitance Inductance
EEx ia
IIB
40µF
80mH
1.7mH/Ω
EEx ia
IIC
4.9µF
20mH
0.4mH/Ω
Publication 1797-6.5.6 - November 2000
10-4
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
11
1797-IJ2 FLEX Ex Frequency Input Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 1 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
The frequency input module has 2 input channels. Each input can
accept inputs from magnetic pickups or proximity probes. Each input
channel has 2 input selections: frequency input or gate input. Do not
apply any non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
IMPORTANT
CENELEC Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - November 2000
11-2
1797-IJ2 FLEX Ex Frequency Input Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
3V
6V
17
18
3
4
5
6
7
8
9
10
11
12
13
14
15
Row A
16
V+ GND 50 500/50 N 8V
mV mV
Sel
Channel 0 Frequency Input
19
20
21
22
23
24
8V N 500/50 50 GND V+ 6V 3V
mV mV
Sel
Channel 1 Frequency Input
25
26
27
28
29
30
31
32
33
Row B
R0 NO R0 NC
GND 50 500/50 N 8V
mV mV
Sel
Channel 0 Gate Input
Row C
34
35
+V
-V
36
37
38
39
8V N 500/50 50 GND
mV mV
Sel
R1 NO R1 NC
Channel 1 Gate Input
40
R0 COM
41
42
43
44
45
46
47
48
R1 COM
49
50
+V
No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49
ATTENTION
!
Intrinsically Safe
Specifications
Publication 1797-6.5.6 - November 2000
51
-V
42334
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex Frequency Input
Module Installation Instructions, publication 1797-5.7.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Uo < 5.8V
Io < 400mA
Li = Negligible
Ci < 2.64µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Li = Negligible
Ci = Negligible
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 98 ATEX E 033 X
CENELEC Certification Information
1797-IJ2 FLEX Ex Frequency Input Module
11-3
CE/CENELEC Input I/O Entity Channel 0 Frequency Input
Parameters
Field devices may only be connected to the terminals of one of the
five following circuits. The terminals of the remaining four circuits
must not be connected.
Namur/
Contact
(terminals
6-7)
Uo = 14.7V
Io = 15mA
Po = 30mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Magnetic
500mV
(terminals
5-3)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Magnetic
50mV
(terminals
5-3, 6-4)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
300mH
80mH
600mH
150mH
600mH
150mH
2.6mH/Ω
0.65mH/Ω
4.15mH/Ω
1.03mH/Ω
4.15mH/Ω
1.03mH/Ω
Vortex 6V
(terminals
1, 2-3)
Uo = 26.5V
Io = 82mA
Po = 520mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
730nF
95nF
Vortex 3V
(terminals
0, 2-3)
Uo = 26.5V
Io = 82mA
Po = 520mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
730nF
95nF
CENELEC Certification Information
8mH
2mH
8mH
2mH
0.26mH/Ω
0.06mH/Ω
0.26mH/Ω
0.06mH/Ω
Publication 1797-6.5.6 - November 2000
11-4
1797-IJ2 FLEX Ex Frequency Input Module
Channel 1 Frequency Input
Field devices may only be connected to the terminals of one of the
five following circuits. The terminals of the remaining four circuits
must not be connected.
Namur/
Contact
(terminals
9-8)
Uo = 14.7V
Io = 15mA
Po = 30mW
Publication 1797-6.5.6 - November 2000
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Magnetic
500mV
(terminals
10-12)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Magnetic
50mV
(terminals
10-12,
9-11)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
300mH
80mH
600mH
150mH
600mH
150mH
2.6mH/Ω
0.65mH/Ω
4.15mH/Ω
1.03mH/Ω
4.15mH/Ω
1.03mH/Ω
Vortex 6V
(terminals
14, 13-12)
Uo = 26.5V
Io = 82mA
Po = 520mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
730nF
95nF
Vortex 3V
(terminals
15, 13-12
Uo = 26.5V
Io = 82mA
Po = 520mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
730nF
95nF
8mH
2mH
8mH
2mH
0.26mH/Ω
0.06mH/Ω
0.26mH/Ω
0.06mH/Ω
CENELEC Certification Information
1797-IJ2 FLEX Ex Frequency Input Module
11-5
Channel 0 Gate Input
Field devices may only be connected to the terminal of one of the
three following circuits. The terminals of the remaining two circuits
must not be connected.
Namur/
Contact
(terminals
23-24)
Uo = 14.7V
Io = 15mA
Po = 30mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Magnetic
500mV
(terminals
22-20)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Magnetic
50mV
(terminals
22-20,
23-21)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
300mH
80mH
600mH
150mH
600mH
150mH
2.6mH/Ω
0.65mH/Ω
4.15mH/Ω
1.03mH/Ω
4.15mH/Ω
1.03mH/Ω
Channel 1 Gate Input
Field devices may only be connected to the terminals of one of the
three circuits. The terminals of the remaining two circuits must not be
connected.
Namur/
Contact
(terminals
26-25)
Uo = 14.7V
Io = 15mA
Po = 30mW
CENELEC Certification Information
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
300mH
80mH
2.6mH/Ω
0.65mH/Ω
Publication 1797-6.5.6 - November 2000
11-6
1797-IJ2 FLEX Ex Frequency Input Module
Magnetic
500mV
(terminals
27-29)
Uo = 14.7V
Io = 10mA
Po = 18mW
Magnetic
50mV
(terminals
27-29,
26-28)
Uo = 14.7V
Io = 10mA
Po = 18mW
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
Protection
Group
Allowed
Allowed
LoRo
Capacitance Inductance Ratio
EEx ia
IIB
IIC
3.86µF
620nF
600mH
150mH
600mH
150mH
4.15mH/Ω
1.03mH/Ω
4.15mH/Ω
1.03mH/Ω
Relay Outputs
Relay
Output
(terminals
17, 18, 37 or
31, 32, 46)
Ui = 28V
Ii = 93mA
Pi = 651mW
Publication 1797-6.5.6 - November 2000
Protection
Group
Internal
Internal
Capacitance Inductance
EEx ia
IIB
IIC
Negligible
Negligible
Negligible
Negligible
CENELEC Certification Information
Chapter
12
1797-PS2E FLEX Ex Power Supply
1797-PS2E
30686
Installation in Zone 1
The 1797-PS2E power supply has a protection factor of IP65. Refer to
the specifications table for the IS module type.
ATTENTION
!
CENELEC Certification Information1
The power supply cannot be used in an intrinsically
safe environment after its outputs have been
exposed to non-intrinsically safe signals.
Publication 1797-6.5.6 - November 2000
12-2
1797-PS2E FLEX Ex Power Supply
European Community
Directive Compliance
If this product has the CE mark it is approved for installation within
the European Community or EEA regions. It has been designed and
tested to meet the following directives.
Ex Directive
This product is tested to meet the Council Directive 76/117/EC
Electrical Apparatus for Explosive Atmospheres by applying the
following standards:
• EN50014:1977 + A1-A5, Electrical Apparatus for
Explosive Atmospheres
• EN50018:1977 + A1-A3, Electrical Apparatus for
Explosive Atmospheres - Flameproof Enclosure
• EN50019:1977 + A1-A5, Electrical Apparatus for
Explosive Atmospheres - Increased Safety “e”
• EN50020:1977 + A1-A5, Electrical Apparatus for
Explosive Atmospheres - Intrinsic Safety “i”
Outputs
Potentially
Potentially
“d”
Potentially
Potentially
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
The channels in the power supply are electrically connected to each
other and have a common +V line.
IMPORTANT
Publication 1797-6.5.6 - November 2000
You cannot interconnect lines because of the
intrinsic safety requirements.
CENELEC Certification Information
1797-PS2E FLEX Ex Power Supply
Typical Wiring
Configurations
Terminal Base Assignments
European DC Power Input
1
2 4 5
+
3
-
Vin1
+
IS Power Output
10 11 12 13 14 15 16 17
+V
-
Vin2
-V
+V -V
+V -V
+V -V
Out 1
Out 2
Out 3
Out 4
cha
GND
Intrinsically Safe
Specifications
12-3
42489
For a full list of specifications, refer to FLEX Ex Power Supplies
Installation Instructions, publication 1797-5.12.
Inset Voltage Range
Voltage UO
19 to 32V dc
<9.5V
Current IO
<1A
Co (IIC)
<800 nF
Lo (IIC)
<10 µH
Operational Temperature
Agency Certification
Certificates
-20 to 70oC (-4 to 158oF)
EEx de [ib] IIC T4
BVS 98.D.2055X
ATTENTION
Once power has been applied, wait 15 minutes after
disconnecting before opening cover.
!
CENELEC Certification Information
Publication 1797-6.5.6 - November 2000
12-4
1797-PS2E FLEX Ex Power Supply
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
13
1797-ACNR15/B ControlNet Ex Redundant
Media Adapter
1797-ACNR1
5
PWR
3
2
41408
Module Installation
Use the redundant media adapter module to connect FLEX Ex
modules to the ControlNet Ex network.
CENELEC Certification Information1
Publication 1797-6.5.6 - November 2000
13-2
1797-ACNR15/B ControlNet Ex Redundant Media Adapter
European Community
Directive Compliance
If this product has the CE mark it is approved for installation within
the European Community or EEA regions. It has been designed and
tested to meet the following directives.
Ex Directive
This product is tested to meet the Council Directive 94/9/EC (ATEX
100a) Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres by applying the following
standards:
• EN50014:1992, Electrical Apparatus for Potentially Explosive
Atmospheres
• EN50020:1994, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsic Safety “i”
• prEN50284:1997, Special requirements for construction, test and
marking of electrical apparatus of equipment group II, category
1G
Inputs/Outputs
Do not apply any non-intrinsically safe signals to the adapter.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
1797-ACNR15/B ControlNet Ex Redundant Media Adapter
Intrinsically Safe
Specifications
13-3
For a full list of specifications, refer to ControlNet Ex Redundant
Media Adapter Installation Instructions, publication 1797-5.14.
ControlNet Ex BNC (ChA and ChB)
Oscillation powered by:
Uo < 5.4V dc
Io < 160mA
ac coupled with high-pass filter f-3 > 500kHz
Output (intrinsically safe)
(16 position male/female flexbus
connector)
Uo < 5.8V
Io < 400mA
Po < 2.16W
Lo < 10µH
Co < 65µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Pi < 9.5W
Li = Negligible
Ci < 120nF
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
II 2G EEx ib IIB/IIC T4
Certificates
DMT 99 ATEX E 008 X
CENELEC Certification Information
Publication 1797-6.5.6 - November 2000
13-4
1797-ACNR15/B ControlNet Ex Redundant Media Adapter
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
14
1797-RPA ControlNet Ex Modular Repeater
Adapter and 1797-RPFM Fiber Repeater
Module, Medium Distance
1797-RPA
1797-RPA
COMM MODULE
STATUS STATUS
REPEATER
ADAPTER
PWR
1
2
3
4
+V
-V
+V
-V
41163
1797-RPFM
1797-RPFM
Chan 1
Recv
Chan 2
Xmit
Recv
Xmit
41267
Module Installation
A maximum of two 1797-RPFM modules may be used with one
1797-RPA adapter.
CENELEC Certification Information1
Publication 1797-6.5.6 - November 2000
14-2
1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance
European Community
Directive Compliance
If this product has the CE mark it is approved for installation within
the European Community or EEA regions. It has been designed and
tested to meet the following directives.
Ex Directive
This product is tested to meet the Council Directive 94/9/EC (ATEX
100a) Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres by applying the following
standards:
• EN50014:1992, Electrical Apparatus for Potentially Explosive
Atmospheres
• EN50020:1994, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsic Safety “i”
• prEN50284:1997, Special requirements for construction, test and
marking of electrical apparatus of equipment group II, category
1G
Inputs/Outputs
Do not apply any non-intrinsically safe signals to the adapter or fiber
modules.
When using an intrinsically safe electrical apparatus according to
EN50020, the European directives and regulations must be followed.
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance
Intrinsically Safe
Specifications
14-3
For a full list of specifications, refer to ControlNet Ex Modular
Repeater Adapter and Fiber Repeater Module, Medium Distance
Installation Instructions, publication 1797-5.15.
1797-RPA Specifications
ControlNet Ex BNC
Oscillation powered by:
Uo < 5.4V dc
Io < 201mA
ac coupled with high-pass filter f > 500kHz
Output (intrinsically safe)
(30 pin male TTL bus connector)
Manufacturer specific bus
Uo < 5.4V
Io < 201mA
Po < 1.09W
Lo < 0.45µH
Co < 71µF
Power Supply
(+V, -V Intrinsically Safe)
Ui < 9.5V dc
Ii < 1A
Pi < 9.5W
Li = Negligible
Ci < 120nF
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 99 ATEX E 011 X
1797-RPFM Specifications
Input (intrinsically safe)
(30 pin female TTL bus connector)
Ui < 5.4V
Ii < 201mA
Pi < 1.1W
Li < 15µH
Ci < 41µF
Output (intrinsically safe)
(30 pin male TTL bus connector)
Uo < 5.4V
Io < 201mA
Po < 1.1W
Lo < 0.45mH
Co < 71µF
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
Certificates
DMT 99 ATEX E 011 X
CENELEC Certification Information
Publication 1797-6.5.6 - November 2000
14-4
1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance
Notes:
Publication 1797-6.5.6 - November 2000
CENELEC Certification Information
Chapter
15
General UL, cUL Certification Information
(1) keyswitch
(8) flexbus
cover
(2) terminal
base unit
Label here or under here
Module Installation
40231
FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S
intrinsically safe terminal base unit.
You will need to rotate the keyswitch (1) to the correct position
depending on the module. Refer to the module’s installation
instructions for more information. Do not change the position of
the keyswitch after wiring the terminal base unit.
Make certain that you only connect terminal base units to other
intrinsically safe system modules, adapters and power supplies to
maintain the integrity of the intrinsically-safe system.
41307
Remove cap plug and attach another intrinsically safe terminal base
unit (2) to the right of the terminal base unit if required.
Do not remove the flexbus cover (8) on the right-most terminal base
unit.
UL, cUL Certification Information1
Publication 1797-6.5.6 - November 2000
15-2
General UL, cUL Certification Information
Installation in Division 1/
Zone 1
Modules, adapters, and terminal base units must not be exposed to
the environment. Provide a suitable enclosure.
ATTENTION
!
Modules, adapters, and terminal base units cannot be
used in an intrinsically safe environment after they
have been exposed to non-intrinsically safe signals.
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near each
module: Attention! Avoid electrostatic charge. For your
convenience, a sign which can be cut out and posted is included in
this chapter.
Repair
Modules are not field-repairable. Any attempt to open a module will
void the warranty and the IS certification. If repair is necessary, return
the module to the manufacturer.
Attention: Avoid electrostatic charge.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
16
ControlNet Ex System
Bus Connectors
Adapter
Terminal Base
Keyswitch
Flexbus Connector
Ex I/O Module
1797-ACNR15
Ex
PWR
PWR
Terminal Strips
Field Power
Connection Terminals
UL, cUL Certification Information1
20125-M
Publication 1797-6.5.6 - November 2000
1797-RPFM
1797-RPFM
.
.
.
.
.
.
.
.
.
Node 3
1797-ACNR15
ó
Ch0
Ch1
Ch1
Any IS device with entity
concept parameters
(Vmax, Imax, Ci, Li)
appropriate for connection
to associated apparatus
with entity concept
parameters listed in Table 1.
Maximum devices=8.
fiber optic cable
.
.
öú
.
1
€
.
Any IS device with entity
concept parameters
(Vmax, Imax, Ci, Li)
appropriate for connection
to associated apparatus
with entity concept
parameters listed in Table 1.
Maximum devices=8.
€
Ch0
Node 4 ... 48
1797-ACNR15
€
Power Supply
Vmax=9.5V
Imax=1A
Ci<=120nF
Li=0
To any IS device or
associated apparatus
with entity concept
parameters of
Voc=9.5V and Isc=1A.
.
1
.
ó
ChA
ChB
ó
ChA
ó
Power Supply
Vmax=9.5V
Imax=1A
Ci<=120nF
Li=0
To any IS device or
associated apparatus
with entity concept
parameters of
Voc=9.5V and Isc=1A.
coax trunk cable
ó÷
ControlNet
Ex tap
42475
ControlNet
Ex tap
ControlNet
Ex tap
ControlNet
Ex tap
CNet Ex
trk trm
CNet Ex
trk trm
CNet Ex
trk trm
The ambient temperature range of the
ControlNet Ex System is -20oC to +70oC.
coax trunk cable
ó
Hazardous (Classified) Location
Zone 0, 1 or 2, IIC
Class I, Zones 0, 1 and 2,
Groups IIC, IIB, IIA
Class I Division 1 and 2,
Groups A, B, C, D
Class II, Division 1 and 2,
Groups E, F, G
Class III, Division 1 and 2
÷
UL, cUL Certification Information
Node 1
ChB
€
€
Power Supply
Vmax=9.5V
Imax=1A
Ci<=120nF
Li=0
To any IS device or
associated apparatus
with entity concept
parameters of
Voc=9.5V and Isc=1A.
Hazardous (Classified) Location
Zone 1 or 2, IIC
Class I, Zones 1 and 2, Groups IIC, IIB, IIA
Class I Division 1 and 2, Groups A, B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III, Division 1 and 2
ControlNet Ex System
1786-RPFM
or
Any associated apparatus where the
light emitting diode output is
<5mW/mm2.
16-2
Node 2
1797-RPA
ControlNet Ex System
Diagram
Hazardous (Classified) Location
Zone 1 or 2, IIC
Class I, Zones 1 and 2, Groups IIC, IIB, IIA
Class I Division 1 and 2, Groups A, B, C, D
ì
Publication 1797-6.5.6 - November 2000
Non-Hazardous Location
ControlNet Ex System
Describing the ControlNet
Ex System Diagram
16-3
A maximum of 48 ControlNet ExTM nodes may be connected together
by 250m of coax cable and 48 taps. The distance increases to 1000m
when you use only 2 taps. See the table below for more information.
The fiber media of the 1797-RPFM can be installed in a hazardous
location (Zone 0, 1 or 2; Class I, Zones 0, 1, and 2; Class I, Division 1
and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect
two 1797-RPFM modules or they can be installed through different
locations into the non-hazardous location to connect the 1797-RPFM
with any approved associated apparatus.
All cables and fiber media that are not light blue must be marked as IS
using the 1797-EXMK marking kit or other locally approved IS
identification and/or segregation method.
During the installation of the ControlNet Ex system, all metallic parts
must be isolated to prevent an earth connection (high voltage
withstanding of isolating material must be > 500V ac).
System
Diagram
Name
1797-RPA
Catalog Number Catalog Name
1797-RPFM
1797-RPFM
1797-RPA
1797-ACNR15 1797-ACNR15
CNet Ex
Tap Trm
1797-TCAP
ControlNet Ex
Tap
1797-TPx
CNet Ex
Trk Trm
1797-XT
Coax Trunk
Cable
1797-RG6
None
None
UL, cUL Certification Information
Description
ControlNet Ex Modular Represents one ControlNet Ex node and
Repeater Adapter
must be connected to a coax trunk cable
by
1797-TPx
ControlNet Ex Fiber
Allows connection of a maximum of two
Repeater Module,
devices per 1797-RPA and is powered
Medium Distance
directly by 1797-RPA
Redundant Media
Represents one ControlNet Ex node and
ControlNet Ex Adapter must be connected to a coax trunk cable
by
1797-TPx -each one with two redundant
output channels that are connected to
different ControlNet Ex networks (coax
cables and 1797-TPx)
ControlNet Ex Tap
Represents one ControlNet Ex node and is
(Dummy) Terminator a simple capacitor (56pF) with a coax
connector
ControlNet Ex Coax Tap Four types of connections available: S
(straight t-tap), R (right angle t-tap), YS
(straight y-tap), and YR (right angle y-tap)
- a maximum of 48 taps can be connected
together by coax trunk cable
ControlNet Ex Trunk
Simple resistor (75Ω) with coax connector
Terminator
that must be on each end of the ControlNet
Ex coax trunk for termination
Quad-Shield, RG-6
Maximum (functional) length between 2
75Ω Coax Trunk Cable 1797-TPx is 3280ft (1000m) - each
1797-TPx reduces the (functional) coax
cable length by 53.4ft (16.3m)
Standard Coax Trunk Different standard cable couplers, 90o,
Cable BNC Couplers
180o, etc.
Publication 1797-6.5.6 - November 2000
16-4
ControlNet Ex System
Certified Equivalent ControlNet Ex System Diagram Items
You may use these items as equivalents for the items shown on the
system diagram.
System Diagram Name
Catalog Number
Source
1797-RPA
1797-RPA
Allen-Bradley
RSD-CFA-Ex.CN
Pepperl+Fuchs
1797-RPFM
Allen-Bradley
RSD-FC-Ex2.CN
Pepperl+Fuchs
1797-ACNR15
Allen-Bradley
RSD-GW-Ex2.CN
Pepperl+Fuchs
1797-RG6
Allen-Bradley
3092A2
Belden Wire & Cable Co.
3092A with blue jacket
Belden Wire & Cable Co.
1797-TPx
Allen-Bradley
RS-TPx-Ex
Pepperl+Fuchs
1797-XT
Allen-Bradley
RS-XT-Ex
Pepperl+Fuchs
1797-TCAP
Allen-Bradley
RS-TCAP-Ex
Pepperl+Fuchs
1797-RPFM
1797-ACNR15
Coax Trunk Cable
1
ControlNet Ex Tap
CNet Ex Trk Trm
CNet Ex Tap Trm
1
2
Publication 1797-6.5.6 - November 2000
In addition to these cable types, the following specification can be followed to allow additional types:
Cable Impedance = 75Ω ± 3Ω
Cable Capacitance = <5.94nF per 100m
Cable Resistance = >9.08Ω per 100m
5MHz > 1.39dB/100m
Cable Attenuation
0.2MHz > 0.93dB/100m
0.5MHz > 0.95dB/100m
10MHz > 1.86dB/100m
(-20 to +70oC)
20MHz > 2.73dB/100m
1MHz > 1.07dB/100m
50MHz > 4.33dB/100m
2MHz > 1.16dB/100m
Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.
UL, cUL Certification Information
ControlNet Ex System
16-5
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ì WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
ö If fiber optic cable is provided with a metal shield, it must be
connected to a dedicated intrinsic safety ground in the non-hazardous
location and tied back in the hazardous location or be connected to a
ground in the hazardous location and tied back in the non-hazardous
location.
ú
The glass fiber must have a minimum diameter of 6µm.
Remove cap plug and attach another intrinsically safe terminal base
unit to the right of the terminal base unit if required.
Installation in Division 1/
Zone 1
Modules must not be exposed to the environment. Provide a suitable
metal enclosure. The terminal base units have a protection factor of
IP20.
ATTENTION
!
UL, cUL Certification Information
Modules cannot be used in an intrinsically safe
environment after they have been exposed to
non-intrinsically safe signals.
Publication 1797-6.5.6 - November 2000
16-6
ControlNet Ex System
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near each
module: Attention! Avoid electrostatic charge. For your
convenience, a sign which can be cut out and posted is included in
this chapter.
Repair
Modules are not field-repairable. Any attempt to open a module will
void the warranty and the IS certification. If repair is necessary, return
the module to the manufacturer.
Attention: Avoid electrostatic charge.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
17
1797-TB3 FLEX Ex Terminal Base Unit
(1) keyswitch
Label here
(8) flexbus
cover
0
1 2 3 4 5
6 7
8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
42332
General Information
FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S
intrinsically safe terminal base unit.
Module Installation
You will need to rotate the keyswitch (1) to the correct position
depending on the module. Refer to the module’s installation
instructions for more information. Do not change the position of
the keyswitch after wiring the terminal base unit.
Make certain that you only connect terminal base units to other
intrinsically safe system modules or adapters to maintain the integrity
of the intrinsically-safe backplane.
41307
Installation in Division 1/
Zone 1
Do not remove the flexbus cover (8) on the right-most terminal base
unit.
UL, cUL Certification Information1
Publication 1797-6.5.6 - November 2000
17-2
1797-TB3 FLEX Ex Terminal Base Unit
Inputs
Do not apply any non-instrinsically safe signals to the terminal
base.
The terminals in the terminal base unit may be electrically connected
to each other by the insertion of FLEX Ex I/O modules. See the
module installation instructions to determine this.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety requirements.
IMPORTANT
Description
The 1797-TB3 terminal base has 36 wiring connections to/from a
plug-in module. The use of each terminal depends on the module
mounted in this base.
The 1797-TB3 terminal base also has connections for cold junction
compensation and terminals designated for shield termination to
chassis ground.
The terminal base is equipped with a factory-installed tab cover for
the backplane bus connection. The tab cover may be removed only
when the terminal base unit is connected to other terminal base units..
Wiring Connections for Terminal Base 1797-TB3
0
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
A
16 17
18 19 20
21 22 23
24 25 26
27 28 29 30 31 32 33
B
34 35
36 37 38
39 40 41
42 43 44
45 46 47 48 49 50 51
C
+V -V
ATTENTION
!
Publication 1797-6.5.6 - November 2000
+V -V
No connections allowed to terminals 36 and 49
41252
• Make certain that you power the terminal base
unit with an intrinsically safe power supply. Do
not exceed the values listed in the specifications
for the terminal base unit.
• Do not use the unused terminals on the terminal
base unit. Using these terminals as supporting
terminals can result in damage to modules and/or
unintended operation of your system.
UL, cUL Certification Information
1797-TB3 FLEX Ex Terminal Base Unit
Intrinsically Safe
Specifications
17-3
For a full list of specifications, refer to the FLEX Ex Terminal Base
Installation Instructions, publication 1797-5.1.
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ia IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL Certification Information
US
Class I Division 1 Hazardous
Publication 1797-6.5.6 - November 2000
17-4
1797-TB3 FLEX Ex Terminal Base Unit
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
18
1797-TB3S FLEX Ex Terminal Base Unit
(1) keyswitch
(8) flexbus
cover
Label here
42333
General Information
FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S
intrinsically safe terminal base unit.
Module Installation
You will need to rotate the keyswitch (1) to the correct position
depending on the module. Refer to the module’s installation
instructions for more information. Do not change the position of
the keyswitch after wiring the terminal base unit.
Make certain that you only connect terminal base units to other
intrinsically safe system modules or adapters to maintain the integrity
of the intrinsically-safe backplane.
41307
Installation in Division 1/
Zone 1
Do not remove the flexbus cover (8) on the right-most terminal base
unit.
UL, cUL Certification Information1
Publication 1797-6.5.6 - November 2000
18-2
1797-TB3S FLEX Ex Terminal Base Unit
Inputs
Do not apply any non-instrinsically safe signals to the terminal
base.
The terminals in the terminal base unit may be electrically connected
to each other by the insertion of FLEX Ex I/O modules. See the
module installation instructions to determine this.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety requirements.
IMPORTANT
Description
The 1797-TB3S terminal base has 36 wiring connections to/from a
plug-in module. The use of each terminal depends on the module
mounted in this base.
The 1797-TB3S terminal base also has connections for cold junction
compensation and terminals designated for shield termination to
chassis ground.
The terminal base is equipped with a factory-installed tab cover for
the backplane bus connection. The tab cover may be removed only
when the terminal base unit is connected to other terminal base units.
Wiring Connections for Terminal Base 1797-TB3S
0
1
16
17
34
35
2
18
36
3
4
5
6
7
8
9
10
11
12
13
14
15
19
20
21
22
23
24
25
26
27
28
29
30
31
32
37
38
39
40
41
42
43
44
45
46
47
48
49
50 51
33
Row A
Row B
Row C
Label placed at top of wiring area
Row A
Row B
Row C
+V -V
+V -V
No connections allowed to terminals 36 and 49
ATTENTION
!
Publication 1797-6.5.6 - November 2000
41254
• Make certain that you power the terminal base
unit with an intrinsically safe power supply. Do
not exceed the values listed in the specifications
for the terminal base unit.
• Do not use the unused terminals on the terminal
base unit. Using these terminals as supporting
terminals can result in damage to modules and/or
unintended operation of your system.
UL, cUL Certification Information
1797-TB3S FLEX Ex Terminal Base Unit
Intrinsically Safe
Specifications
18-3
For a full list of specifications, refer to the FLEX Ex Spring Clamp
Terminal Base Installation Instructions, publication 1797-5.2.
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ia IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL Certification Information
US
Class I Division 1 Hazardous
Publication 1797-6.5.6 - November 2000
18-4
1797-TB3S FLEX Ex Terminal Base Unit
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
19
1797-IBN16 FLEX Ex 16 NAMUR Input Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 6 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from a NAMUR sensor or a mechanical
contact (if mechanical inputs are used). Do not apply any
non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other
and have a common plus-line.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
IMPORTANT
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
3
4
5
+
-
+
-
+
17
18
19
20
21
22
+
-
+
-
+
-
6
7
8
9
10
11
12
13
14
15
+
-
+
-
Row A
Ch 0
16
Ch 1
-
+
Ch 2
-
+
23
24
25
26
27
28
29
30
+
-
+
-
+
-
+
-
Ch 3
-
+
Ch 4
-
Ch 5
Ch 6
Ch 7
31
32
33
Row B
Ch 8
34
Ch 9
35
36
Ch 10
37
38
Ch 11
39
40
Ch 12
41
42
Ch 13
43
44
+
Ch 14
45
46
-
Ch 15
47
48
49
50
51
Row C
41504
+V
-V
UL, cUL Certification Information1
No connection allowed to terminals 36 and 49
+V -V
Publication 1797-6.5.6 - November 2000
19-2
1797-IBN16 FLEX Ex 16 NAMUR Input Module
ATTENTION
!
Intrinsically Safe
Specifications
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 16 NAMUR Input
Module Installation Instructions, publication 1797-5.7.
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
Publication 1797-6.5.6 - November 2000
US
Class I Division 1 Hazardous
UL, cUL Certification Information
1797-IBN16 FLEX Ex 16 NAMUR Input Module
UL, cUL I/O Entity
Parameters
19-3
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel Terminals
Method
Voc
(V)
1 and 2 Any one 0(+), 1(-)
channel
e.g. ch0
A- B
Isc
Vt
It
(mA) (V) (mA)
14.5 15
-
Allen-Bradley
FLEX Ex NAMUR
Input I/O Module
-
1797- IBN16
16 Point NAMUR Input Module
6
0
1
2
3
4
5
6
LEDs
Female Bus
Connection
Field Wiring
Terminals
7
8
9
10
11
12
13
14
15
PWR
Groups
Ca
La
(µF) (mH)
A, B, IIC
0.3
80.0
C, E, IIB
0.9
320.0
D, F, G, IIA
2.4
640.0
Key Position for
Terminal Base
Insertion
Male Bus
Connection
6
Terminal
Base Key
Terminal
Base
42060
IMPORTANT
UL, cUL Certification Information
A terminal base may or may not have an I/O module
installed.
Publication 1797-6.5.6 - November 2000
19-4
1797-IBN16 FLEX Ex 16 NAMUR Input Module
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
ó
€
Any Simple Apparatus or I.S. device with Entity
Concept parameters (Vmax, Imax, Ci, Li) appropriate
for connection to associated apparatus with Entity
Concept parameters listed in Table 1.
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
ì÷
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
ch8
ch9
ch10
ch11
ch12
ch13
ch14
ch15
0(+)
1(-)
2(+)
3(-)
4(+)
5(-)
6(+)
7(-)
8(+)
9(-)
10(+)
11(-)
12(+)
13(-)
14(+)
15(-)
17(+)
18(-)
19(+)
20(-)
Female Bus Connector
Vmax=5.8V
Imax=400mA
Ci=1350nF
Li=negligible
21(+)
22(-)
23(+)
24(-)
25(+)
26(-)
27(+)
28(-)
29(+)
30(-)
31(+)
32(-)
Male Bus
Connector
ì
34
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
ì
35
ö úø
1797-IBN16
16
33
40
41
42
43
44
45
€
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
51
50
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of Voc
< 5.8V; Isc < 400mA.
ì
€
To any IS device with Entity
Concept parameters of
(Vmax, Imax, Ci, Li) appropriate for
connection to associated
apparatus with Entity
Concept parameters listed in
Table 2.
Shield Connection Only
42061
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
1797-IBN16 FLEX Ex 16 NAMUR Input Module
19-5
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ö This module, 1797-IBN16, must be used with terminal base
1797-TB3 or 1797-TB3S.
ú Terminals 36-39, and 46-49 shall not be connected.
÷ Any combination of up to eight channels may be connected in
parallel and connected to simple apparatus in a hazardous location. If
two channels are connected in parallel, the total cable inductance
must be limited to 20mH for Groups A and B, 80mH for Groups C and
E, and 160mH for Groups D, F, and G. If eight channels are connected
in parallel, the total cable inductance must be limited to 2mH for
Groups A and B, 8mH for Groups C and E and 16mH for Groups D, F,
and G.
ø WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
19-6
1797-IBN16 FLEX Ex 16 NAMUR Input Module
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
20
1797-OB4D FLEX Ex 24V dc Non-Isolated
Source 4 Output Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 7 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Outputs
Each output can operate a discrete field device. Do not apply any
non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other.
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
+
-
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Row A
+
ch0
16
17
-
+
ch1
18
19
20
21
-
+
ch2
22
23
24
25
-
ch3
26
27
28
29
30
31
32
33
Row B
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
Row C
+V
UL, cUL Certification Information1
-V
No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37,
38, 39, 46, 47, 48, 49
+V
-V
40068
Publication 1797-6.5.6 - November 2000
20-2
1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module
ATTENTION
!
Intrinsically Safe
Specifications
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 24V dc Non-Isolated
Source 4 Output Module Installation Instructions, publication 1797-5.6.
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL I/O Entity
Parameters
US
Class I Division 1 Hazardous
Wiring Methods
• Wiring method 1: Each channel is wired separately.
• Wiring method 2: Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel Terminals
Method
1 and 2 Any one 0(+), 1(-)
channel
e.g. ch0
Publication 1797-6.5.6 - November 2000
Voc
(V)
Isc
(mA)
27.4 110.0
Vt
It
(V) (mA)
-
-
Groups
Ca
La
(µF) (mH)
A, B, IIC
0.03 2.0
C, E, IIB
0.09 8.0
D, F, G, IIA
0.24 16.0
UL, cUL Certification Information
1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module
A- B
Allen-Bradley
Key Position for
Terminal Base
Insertion
1797- OB4D
4 Point Source Output Module
FLEX Ex Discrete
Output I/O Module
7
0
1
2
3
4
5
6
7
20-3
PWR
LEDs
Male Bus
Connection
Female Bus
Connection
Terminal
Base Key
Field Wiring
Terminals
Terminal
Base
42058
A terminal base may or may not have an I/O module
installed.
IMPORTANT
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
ó
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (Vmax, Imax, Ci, Li)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.
€
ì
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
ch0
ì
0 (+)
1 (-)
Female Bus
Connector
ch1
4 (+)
5 (-)
Vmax=5.8V
Imax=400mA
Ci=1350nF
Li=negligible
ch2
8 (+)
9 (-)
ch3
12 (+)
13 (-)
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
34
51
50
Male Bus
Connector
öú ÷
1797-OB4D
ì
35
16
33
40
41
42
43
44
45
ì
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 5.8V; Isc < 400mA.
€
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
To any IS device with Entity
Concept parameters of
(Vmax, Imax, Ci, Li) appropriate
for connection to associated
apparatus with Entity Concept
parameters listed in Table 2.
€
Shield Connection Only
42059
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
20-4
1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
Groups
400
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ö This module, 1797-OB4D, must be used with terminal base
1797-TB3 or 1797-TB3S.
ú Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17-32, 36-39, and 46-49 shall
not be connected.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
21
1797-IE8 FLEX Ex 8 Input Analog Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 3 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from an analog field device signal. Do
not apply any non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other
and have a common plus-line.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
IMPORTANT
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
+
sig
-
3
4
5
6
+
sig
-
7
8
9
10
11
12
13
14
+
sig
15
Row A
Ch 0
16
+ sig
Ch 1
17
18
19
+
sig
-
20
-
Ch 2
21
22
23
+
sig
-
24
25
26
-
Ch 3
27
28
29
30
31
+
sig
32
33
Row B
Ch 4
34
+ sig
Ch 5
35
36
37
38
39
-
Ch 6
40
41
42
43
-
Ch 77
44
45
46
47
48
49
50
51
Row C
40071
+V -V
No connection
allowed
UL, cUL Certification Information1
+V -V
No connection
allowed
Publication 1797-6.5.6 - November 2000
21-2
1797-IE8 FLEX Ex 8 Input Analog Module
ATTENTION
!
Intrinsically Safe
Specifications
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 8 Input Analog Module
Installation Instructions, publication 1797-5.5.
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
Publication 1797-6.5.6 - November 2000
US
Class I Division 1 Hazardous
UL, cUL Certification Information
1797-IE8 FLEX Ex 8 Input Analog Module
UL, cUL I/O Entity
Parameters
21-3
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel
Method
Terminals
Voc
(V)
1 and 2 Any one 0(+), 1(sig)
channel
e.g. ch0
Isc
(mA)
Vt
(V)
It
(mA)
23.7 92.5 -
-
Groups
Ca
La
(µF) (mH)
A, B, IIC
0.06 2.0
C, E, IIB
0.18 8.0
D, F, G, IIA 0.48 16.0
1(sig), 2(-)
5
1.0
0(+), 1(sig), 2(-) -
-
-
-
A, B, IIC
100
1000
C, E, IIB
300
1000
D, F, G, IIA 800
1000
23.7 93.5 A, B, IIC
0.06 2.0
C, E, IIB
0.18 8.0
D, F, G, IIA 0.48 16.0
A- B
Allen-Bradley
1797- IE8
8 CHANNEL ANALOG INPUT
FLEX Ex Analog
Input I/O Module
LEDs
Female Bus
Connection
Field Wiring
Terminals
3
0
1
2
3
4
5
6
7
PWR
Key Position for
Terminal Base
Insertion
Male Bus
Connection
Terminal
Base Key
Terminal
Base
42055
IMPORTANT
UL, cUL Certification Information
A terminal base may or may not have an I/O module
installed.
Publication 1797-6.5.6 - November 2000
21-4
1797-IE8 FLEX Ex 8 Input Analog Module
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
ó
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (Vmax, Imax, Ci, Li)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.
€
ì
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
ì
ch0
0 (+)
1 (sig)
2 (-)
ch1
ch2
ch3
4 (+)
5 (sig)
6 (-)
8 (+)
9 (sig)
10 (-)
12 (+)
13 (sig)
14 (-)
ch4
17 (+)
18 (sig)
19 (-)
ch5
21 (+)
22 (sig)
23 (-)
25 (+)
26 (sig)
27 (-)
ch6
ch7
Female Bus
Connector
Vmax=5.8V
Imax=400mA
Ci=1350nF
Li=negligible
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
34
Male Bus
Connector
1797-IE8
29 (+)
30 (sig)
31 (-)
16
33
40
41
42
43
44
45
€
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
35
51
50
öú ÷
ì
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 5.8V; Isc < 400mA.
ì
To any IS device with Entity
Concept parameters of
(Vmax, Imax, Ci, Li) appropriate
for connection to associated
apparatus with Entity Concept
parameters listed in Table 2.
€
Shield Connection Only
42056
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ö This module, 1797-IE8, must be used with terminal base 1797-TB3
or 1797-TB3S.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
1797-IE8 FLEX Ex 8 Input Analog Module
21-5
ú Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be
connected.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
21-6
1797-IE8 FLEX Ex 8 Input Analog Module
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
22
1797-IE8NF FLEX Ex 8 Input Analog Module
with Noise Filter
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 3 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from an analog field device signal. Do
not apply any non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other
and have a common plus-line.
IMPORTANT
UL, cUL Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - November 2000
22-2
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
+
sig
-
3
4
5
6
+
sig
-
7
8
9
10
11
12
13
14
+
sig
15
Row A
Ch 0
16
+ sig
Ch 1
17
18
19
+
sig
-
20
-
Ch 2
21
22
23
+
sig
-
24
25
26
-
Ch 3
27
28
29
30
31
+
sig
32
33
Row B
Ch 4
34
+ sig
Ch 5
35
36
37
38
39
-
Ch 6
40
41
42
43
-
Ch 77
44
45
46
47
48
49
50
51
Row C
40071
+V -V
+V -V
No connection
allowed
No connection
allowed
ATTENTION
!
Intrinsically Safe
Specifications
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 8 Input Analog Module
with Noise Filter Installation Instructions, publication 1797-5.31.
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
Publication 1797-6.5.6 - November 2000
US
Class I Division 1 Hazardous
UL, cUL Certification Information
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
UL, cUL I/O Entity
Parameters
22-3
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel
Method
Terminals
Voc
(V)
1 and 2 Any one 0(+), 1(sig)
channel
e.g. ch0
Isc
(mA)
Vt
(V)
It
(mA)
23.7 92.5 -
-
Groups
Ca
La
(µF) (mH)
A, B, IIC
0.06 2.0
C, E, IIB
0.18 8.0
D, F, G, IIA 0.48 16.0
1(sig), 2(-)
5
1.0
0(+), 1(sig), 2(-) -
-
-
-
A, B, IIC
100
1000
C, E, IIB
300
1000
D, F, G, IIA 800
1000
23.7 93.5 A, B, IIC
0.06 2.0
C, E, IIB
0.18 8.0
D, F, G, IIA 0.48 16.0
A- B
Allen-Bradley
1797- IE8NF
8 CHANNEL ANALOG INPUT NOISE FILTER
FLEX Ex Analog
Input I/O Module
LEDs
Female Bus
Connection
Field Wiring
Terminals
3
0
1
2
3
4
5
6
7
PWR
Key Position for
Terminal Base
Insertion
Male Bus
Connection
Terminal
Base Key
Terminal
Base
42479
IMPORTANT
UL, cUL Certification Information
A terminal base may or may not have an I/O module
installed.
Publication 1797-6.5.6 - November 2000
22-4
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
ó
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (Vmax, Imax, Ci, Li)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.
€
ì
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
ì
ch0
0 (+)
1 (sig)
2 (-)
ch1
ch2
ch3
4 (+)
5 (sig)
6 (-)
8 (+)
9 (sig)
10 (-)
12 (+)
13 (sig)
14 (-)
ch4
17 (+)
18 (sig)
19 (-)
ch5
21 (+)
22 (sig)
23 (-)
25 (+)
26 (sig)
27 (-)
ch6
ch7
Female Bus
Connector
Vmax=5.8V
Imax=400mA
Ci=1350nF
Li=negligible
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
34
Male Bus
Connector
16
33
40
1797-IE8NF41
42
43
29 (+)
30 (sig)
44
45
31 (-)
€
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
35
51
50
öú ÷
ì
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 5.8V; Isc < 400mA.
ì
To any IS device with Entity
Concept parameters of
(Vmax, Imax, Ci, Li) appropriate
for connection to associated
apparatus with Entity Concept
parameters listed in Table 2.
€
Shield Connection Only
42481
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ö This module, 1797-IE8NF, must be used with terminal base
1797-TB3 or 1797-TB3S.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
22-5
ú Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be
connected.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
22-6
1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
23
1797-OE8 FLEX Ex 8 Output Analog Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 4 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Outputs
Each output channel can operate an analog field device. Do not
apply any non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other.
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
3
4
5
+
-
6
7
8
9
10
11
12
13
14
15
Row A
+
-
ch0
16
17
+
ch1
18
19
20
-
+
ch2
21
22
+
-
23
24
25
-
ch3
26
27
28
29
30
31
32
33
Row B
+
ch4
+
ch5
34
35
+V
-V
36
37
38
-
+
ch6
39
40
41
42
-
ch7
43
44
45
46
47
48
49
50
51
Row C
UL, cUL Certification Information1
No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23,
24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49
+V
-V
41440
Publication 1797-6.5.6 - November 2000
23-2
1797-OE8 FLEX Ex 8 Output Analog Module
ATTENTION
!
Intrinsically Safe
Specifications
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex 8 Output Analog
Module Installation Instructions, publication 1797-5.3.
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL I/O Entity
Parameters
US
Class I Division 1 Hazardous
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel
Method
Terminals
Voc
(V)
Isc
(mA)
1 and 2 Any one
channel
e.g. ch0
0(+), 1(-)
21.0 100.0
Vt
(V)
It
(mA)
-
-
Groups
Ca
La
(µF) (mH)
A, B, IIC
0.08 2.0
C, E, IIB
0.24 8.0
D, F, G, IIA 0.64 16.0
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
1797-OE8 FLEX Ex 8 Output Analog Module
A- B
Allen-Bradley
Key Position for
Terminal Base
Insertion
1797- OE8
8 CHANNEL ANALOG OUTPUT
FLEX Ex Analog
Output I/O Module
4
OUT 0
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
23-3
PWR
LEDs
Male Bus
Connection
Female Bus
Connection
Terminal
Base Key
Field Wiring
Terminals
Terminal
Base
42013
A terminal base may or may not have an I/O module
installed.
IMPORTANT
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB,
IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
ó
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (Vmax, Imax, Ci, Li)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.
€
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
ì
ch0
ch1
ch2
ch3
0 (+)
1 (-)
4 (+)
5 (-)
8 (+)
9 (-)
any intrinsically safe
ì Todevice
or associated
Female Bus
Connector
Vmax=5.8V
Imax=400mA
Ci=1350nF
Li=negligible
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
12 (+)
13 (-)
€
34
35
51
50
ch4 17 (+)
18 (-)
ch5 21 (+)
22 (-)
ch6
ch7
UL, cUL Certification Information
25 (+)
26 (-)
29 (+)
30 (-)
Male Bus
Connector
öú ÷
1797-OE8
apparatus with Entity
Concept parameters of
Voc < 5.8V; Isc < 400mA.
16
33
40
41
42
43
44
45
ì
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
any IS device with Entity
ì ToConcept
€ parameters of
(Vmax, Imax, Ci, Li) appropriate
for connection to associated
apparatus with Entity Concept
parameters listed in Table 2.
Shield Connection Only
42484
Publication 1797-6.5.6 - November 2000
23-4
1797-OE8 FLEX Ex 8 Output Analog Module
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ö This module, 1797-IE8, must be used with terminal base 1797-TB3
or 1797-TB3S.
ú Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be
connected.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
24
1797-IRT8 FLEX Ex Thermocouple/RTD
Input Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 2 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
Each input can be operated from a thermocouple (TC) or resistance
temperature detector (RTD). Do not apply any non-intrinsically
safe signals to this module.
The channels in this module are electrically connected to each other
and have a common plus-line.
IMPORTANT
UL, cUL Certification Information1
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
Publication 1797-6.5.6 - November 2000
24-2
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
+
H
L
3
4
5
-
+
H
6
7
8
9
+
H
10
11
12
13
14
15
Row A
Ch 0
16
L
-
Ch 1
17
18
19
20
21
+
H
L
-
+
22
L
-
+
H
Ch 2
23
24
L
-
Ch 3
25
26
27
+
H
L
28
29
30
+
H
31
32
33
Row B
H
Ch 4
L
-
Ch 5
34
35
+V
-V
36
37
38
39
-
Ch 6
40
41
42
L
-
Ch 7
43
44
45
46
47
48
49
50
51
Row C
CJC
CJC
0+ chassis 01+ chassis 1GND for
GND for
shield
shield
No connection allowed to terminals 36 and 49
ATTENTION
!
Intrinsically Safe
Specifications
-V
41505
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex Thermocouple/RTD
Input Module Installation Instructions, publication 1797-5.4.
Operational Temperature
-20 to +70oC (-4 to 158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
Publication 1797-6.5.6 - November 2000
+V
US
Class I Division 1 Hazardous
UL, cUL Certification Information
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
UL, cUL I/O Entity
Parameters
24-3
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel
Method
Terminals
Voc
(V)
Isc
Vt
It
(mA) (V) (mA)
Groups
Ca
(µF)
La
(mH)
1 and 2 Any one
channel
e.g. ch0
0(+), 1(H),
2(L), 3(-)
9.0
37.0
A, B, IIC
4.9
20.0
C, E, IIB
14.7
80.0
UL, cUL Certification Information
37, 38, 39
(CJC0)
or
46, 47, 48
(CJC1)
9.0
0(+), 1(H),
2(L), 3(-)
37, 38, 39
(CJC0)
or
46, 47, 48
(CJC1)
-
1.0
-
-
-
-
-
9.0 38.0
D, F, G, IIA
39.2 160.0
A, B, IIC
4.9 1000.0
C, E, IIB
14.7 1000.0
D, F, G, IIA
39.2 1000.0
A, B, IIC
4.9
20.0
C, E, IIB
14.7
80.0
D, F, G, IIA
39.2 160.0
Publication 1797-6.5.6 - November 2000
24-4
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
FLEX Ex
Temperature Input
I/O Module
A- B
Allen-Bradley
Key Position for
Terminal Base
Insertion
1797- IRT8
8 Point RTD/Thermocouple mV Input Module
2
0
1
2
3
4
5
6
7
PWR
LEDs
Male Bus
Connection
Female Bus
Connection
Terminal
Base Key
Field Wiring
Terminals
Terminal
Base
42020
IMPORTANT
A terminal base may or may not have an I/O module
installed.
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
ó
€
Any Simple Apparatus or I.S. device with Entity
Concept parameters (Vmax, Imax, Ci, Li) appropriate
for connection to associated apparatus with Entity
Concept parameters listed in Table 1.
CJC0
CJC1
37 38 39
ì
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
0(+)
1(H)
2(L)
3(-)
4(+)
5(H)
6(L)
7(-)
8(+)
9(H)
10(L)
11(-)
12(+)
13(H)
14(L)
15(-)
17(+)
18(H)
19(L)
20(-)
21(+)
22(H)
23(L)
24(-)
25(+)
26(H)
27(L)
28(-)
29(+)
30(H)
31(L)
32(-)
46 47 48
ì
Female Bus Connector
Vmax=5.8V
Imax=400mA
Ci=1350nF
Li=negligible
34
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
ì
35
Male Bus
Connector
ö ú÷
1797-IRT8
16
33
40
41
42
43
44
45
€
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
51
50
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of Voc
< 5.8V; Isc < 400mA.
ì
€
To any IS device with Entity
Concept parameters of
(Vmax, Imax, Ci, Li) appropriate for
connection to associated
apparatus with Entity
Concept parameters listed in
Table 2.
Shield Connection Only
42021
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
24-5
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
ö This module, 1797-IRT8, must be used with terminal base
1797-TB3 or 1797-TB3S.
ú Terminals 36 and 49 shall not be connected.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
24-6
1797-IRT8 FLEX Ex Thermocouple/RTD Input Module
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
25
1797-IJ2 FLEX Ex Frequency Input Module
General Information
Modules must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Module Installation
Rotate keyswitch on terminal base unit clockwise to position 1 as
required for this type of module. Do not change the position of the
keyswitch after wiring the terminal base unit.
Inputs
The frequency input module has 2 input channels. Each input can
accept inputs from magnetic pickups or proximity probes. Each input
channel has 2 input selections: frequency input or gate input. Do not
apply any non-intrinsically safe signals to this module.
The channels in this module are electrically connected to each other.
When interconnecting several lines, you must
consider the total accumulated power and check for
intrinsic safety.
IMPORTANT
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
0
1
2
3V
6V
17
18
3
4
5
6
7
8
9
10
11
12
13
14
15
Row A
16
V+ GND 50 500/50 N 8V
mV mV
Sel
Channel 0 Frequency Input
19
20
21
22
23
24
8V N 500/50 50 GND V+ 6V 3V
mV mV
Sel
Channel 1 Frequency Input
25
26
27
28
29
30
31
32
33
Row B
R0 NO R0 NC
GND 50 500/50 N 8V
mV mV
Sel
Channel 0 Gate Input
Row C
34
35
+V
-V
36
37
R0 COM
38
39
8V N 500/50 50 GND
mV mV
Sel
R1 NO R1 NC
Channel 1 Gate Input
40
41
42
43
44
45
46
47
48
R1 COM
49
50
+V
51
-V
No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49
42334
UL, cUL Certification Information1
Publication 1797-6.5.6 - November 2000
25-2
1797-IJ2 FLEX Ex Frequency Input Module
ATTENTION
!
Intrinsically Safe
Specifications
Do not use any unused terminals on this terminal
base unit. Using these terminals as supporting
terminals can result in damage to the module and/or
unintended operation of your system.
For a full list of specifications, refer to FLEX Ex Frequency Input
Module Installation Instructions, publication 1797-5.7.
Operating Temperature
-20 to +70oC (-4 to +158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib/[ia] IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL I/O Entity
Parameters
Publication 1797-6.5.6 - November 2000
US
Class I Division 1 Hazardous
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
UL, cUL Certification Information
1797-IJ2 FLEX Ex Frequency Input Module
25-3
Isc
Vt
It
(mA) (V) (mA)
Table 1
Wiring Channel
Method
Terminals
1 and 2 Any one
channel
6, 7;
9, 8;
23, 24
26, 25
14.7 15.0
5, 3;
10, 12;
22, 20;
27, 29
14.7 10.0
1 and 2 Any one
channel
1 and 2 Any one
channel
Voc
(V)
-
-
-
-
Groups
Ca
(µF)
La
(mH)
A, B, IIC
0.62
80.0
C, E, IIB
1.82
320.0
D, F, G, IIA
4.96
640.0
A, B, IIC
0.62
150.0
C, E, IIB
1.82
600.0
D, F, G, IIA
5, 3, 6, 4;
14.7 10.0
10, 12, 9, 11;
22, 20, 21, 23;
27, 29, 26, 28
-
0, 2, 3;
1, 2, 3;
14, 12, 13;
15, 12, 13
26.5 82.0
-
Wiring Channel
Method
Terminals
Vmax Imax
(V) (mA)
Groups
Ci
(µF)
Li
(mH)
1 and 2 Any one
channel
17, 18, 37
or
31, 32, 46
28
A, B, IIC
0.0
0.0
C, E, IIB
0.0
0.0
D, F, G, IIA
0.0
0.0
1 and 2 Any one
channel
A- B
1797- IJ2
2 Point Frequency Input Module
1
0
LEDs
Female Bus
Connection
Field Wiring
Terminals
1
2
3
4
5
6
7
A, B, IIC
0.62
150.0
C, E, IIB
1.82
600.0
D, F, G, IIA
93.0
Allen-Bradley
FLEX Ex Frequency
Input I/O Module
-
4.96 1200.0
PWR
-
4.96 1200.0
A, B, IIC
0.095
2.0
C, E, IIB
0.285
8.0
D, F, G, IIA
0.76
16.0
Key Position for
Terminal Base
Insertion
Male Bus
Connection
Terminal
Base Key
Terminal
Base
42066
IMPORTANT
UL, cUL Certification Information
A terminal base may or may not have an I/O module
installed.
Publication 1797-6.5.6 - November 2000
25-4
1797-IJ2 FLEX Ex Frequency Input Module
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
To any intrinsically safe device
or associated apparatus with
Entity Concept parameters
of Voc < 28V; Isc < 93mA.
17 18 37
ch0
Freq. In
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (Vmax, Imax, Ci, Li)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.
ó
€
ì
0
1
2
3
4
5
6
7
ó
Vmax=28V
Imax=93mA
Ci=negligible
Li=negligible
ì
Female Bus
Connector
Vmax=5.8V
Imax=400mA
Ci=13500nF
Li=negligible
34
8
9
10
11
12
13
14
15
ch0
Gate
Any Simple Apparatus or I.S.
device with Entity Concept
parameters (Vmax, Imax, Ci, Li)
appropriate for connection to
associated apparatus with Entity
Concept parameters listed in
Table 1.
€
31 32 46
Vmax=28V
Imax=93mA
Ci=negligible
Li=negligible
ch1
Freq. In
€
To any intrinsically safe device
or associated apparatus with
Entity Concept parameters
of Voc < 28V; Isc < 93mA.
€
Vmax=9.5V
Imax=1A
Ci=negligible
Li=negligible
51
50
Male Bus
Connector
25
26
27
28
29
öú ÷
1797-IJ2
16
33
40
41
42
43
44
45
€
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
Voc < 9.5V; Isc < 1A.
€
35
20
21
22
23
24
ch1
Gate
ì
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of Voc
< 5.8V; Isc < 400mA.
ì
€
To any IS device with Entity
Concept parameters of
(Vmax, Imax, Ci, Li) appropriate for
connection to associated
apparatus with Entity
Concept parameters listed in
Table 2.
Shield Connection Only
42057
Table 2
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc or Vt
and It of the associated apparatus are less than or equal to Vmax and Imax
of the intrinsically safe apparatus and the approved values of Ca and La
of the associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Simple apparatus is defined as a device which neither generates
nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.
ì Wiring methods must be in accordance with the National Electric
Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
1797-IJ2 FLEX Ex Frequency Input Module
25-5
ö This module, 1797-IJ2, must be used with terminal base 1797-TB3
or 1797-TB3S.
ú Terminals 19, 30, 36, 38-39, and 47-49 shall not be connected.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
25-6
1797-IJ2 FLEX Ex Frequency Input Module
Notes:
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
26
1797-PS2N/A FLEX Ex Power Supply
Installation in Division 1/
Zone 1
The 1797-PS2N power supply has a protection factor of IP66. Refer to
the specifications table for the IS module type.
ATTENTION
!
Outputs
The channels in the power supply are electrically connected to each
other and have a common +V line.
IMPORTANT
Typical Wiring
Configurations
The power supply cannot be used in an intrinsically
safe environment after its outputs have been
exposed to non-intrinsically safe signals.
You cannot interconnect lines because of the
intrinsic safety requirements.
Terminal Base Assignments
North America DC Power Input
1 2 3 4 5
+
Vin1
-
cha + GND
Vin2
IS Power Output
10 11 12 13 14 15 16 17
+V -V
+V -V
+V -V
+V -V
Out 1
Out 2
Out 3
Out 4
41256
UL, cUL Certification Information1
Publication 1797-6.5.6 - November 2000
26-2
1797-PS2N/A FLEX Ex Power Supply
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex Power Supplies
Installation Instructions, publication 1797-5.12.
Inset Voltage Range
Operational Temperature
Agency Certification
Certificates
19 to 32V dc
-20 to 70oC (-4 to 158oF)
Class I Division 1 Groups C-D T4
Class I Division 2 Groups A-D T4
UL Certificate Number 99.19699
C
ATTENTION
US
Class I Division 1 Hazardous
Once power has been applied, wait 15 minutes after
disconnecting before opening cover.
!
UL, cUL I/O Entity
Parameters
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing
each channel is separated in accordance with the National
Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring Channel
Method
Terminals
1 and 2 Any one 10(+), 11(-)
channel
e.g. ch1
Publication 1797-6.5.6 - November 2000
Voc
(V)
9.5
Isc
(A)
1.0
Groups
Ca
La
(µF) (µH)
A, B, IIC
0.8
10
C, E, IIB
2.4
40
D, F, G, IIA
6.4
80
UL, cUL Certification Information
1797-PS2N/A FLEX Ex Power Supply
Hazardous (Classified) Location
1797-PS2N/A
Class I, Division 1, Groups C, D
Class I, Division 2, Groups A, B, C, D
Nonhazardous Location
26-3
Hazardous (Classified) Location
Class I, Division 1 and 2, Groups A, B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III Division 1 and 2
1797-PS2N/B
Class I, Division 1, Groups B, C, D
Class I, Division 2, Groups A, B, C, D
intrinsically safe wiring
nonintrinsically safe wiring
1 2 3 4 5
ì ö
24V
power
supply
17
16
15
14
13
12
11
10
ì ö
÷
To any IS device with entity
concept parameters of
(Vmax, Imax, Ci, Li) appropriate
Ch1 for connection to associated
apparatus with entity
concept parameters listed in
Table 1.
Ch4
Ch3
Ch2
24V dc to
next power
supply
€
42101
€ The entity concept allows interconnection of intrinsically safe
apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of Voc and Isc of
the associated apparatus are less than or equal to Vmax and Imax of the
intrinsically safe apparatus and the approved values of Ca and La of the
associated apparatus are greater than Ci + Ccable and Li + Lcable
respectively for the intrinsically safe apparatus.
ó Wiring methods must be in accordance with the NEC, ANSI/NFPA
70, Article 504 or the CEC CSA C22.1, Part 1, Appendix F. For
additional information refer to ANSI/ISA RP12.6.
ì Wiring methods must be in accordance with the NEC, ANSI/NFPA
70, Article 501 or the CEC CSA C22.1, Part 1, Section 18.
ö For mounting of the power supply, conduit runs must have
sealing fittings connected within 6 inches of enclosure.
UL, cUL Certification Information
Publication 1797-6.5.6 - November 2000
26-4
1797-PS2N/A FLEX Ex Power Supply
ú The wiring contained within the nonintrinsically safe wiring
compartment and the intrinsically safe wiring compartment shall be
separated from each other. Care must be taken to guarantee the
separation of nonintrinsically safe and intrinsically safe wiring. The
partitions within the power supply provide the necessary isolation for
the electronics and the wiring, however, extreme care must be taken
to guarantee wires are contained within their appropriate
compartment and cannot contact any of the electronics.
÷ WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
27
1797-ACNR15/B ControlNet Ex Redundant
Media Adapter
1797-ACNR1
5
PWR
3
2
41408
Module Installation
Use the redundant media adapter module to connect FLEX Ex
modules to the ControlNet Ex network.
Inputs/Outputs
Do not apply any non-intrinsically safe signals to the adapter.
General Specifications
For a full list of specifications, refer to ControlNet Ex Redundant
Media Adapter Installation Instructions, publication 1797-5.14.
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL Certification Information1
US
Class I Division 1 Hazardous
Publication 1797-6.5.6 - November 2000
27-2
1797-ACNR15/B ControlNet Ex Redundant Media Adapter
UL, cUL Entity Parameters
and Requirements
UL, cUL I/O Entity Parameters and Requirements
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
See the ControlNet Ex System chapter on page 16-1.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Chapter
28
1797-RPA ControlNet Ex Modular Repeater
Adapter and 1797-RPFM Fiber Repeater
Module, Medium Distance
1797-RPA
1797-RPA
COMM MODULE
STATUS STATUS
REPEATER
ADAPTER
PWR
1
2
3
4
+V
-V
+V
-V
41163
1797-RPFM
1797-RPFM
Chan 1
Recv
Chan 2
Xmit
Recv
Xmit
41267
Module Installation
A maximum of two 1797-RPFM modules may be used with one
1797-RPA adapter.
Inputs/Outputs
Do not apply any non-intrinsically safe signals to the adapter or
repeater module.
UL, cUL Certification Information1
Publication 1797-6.5.6 - November 2000
28-2
1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance
Intrinsically Safe
Specifications
For a full list of specifications, refer to ControlNet Ex Modular
Repeater Adapter and Fiber Repeater Module Installation Instructions,
publication 1797-5.15.
Operational Temperature
-20 to 70oC (-4 to 158oF)
Agency Certification
Class I Division 1 & 2 Groups A-D T4
Class I Zone 1 & 2 AEx ib IIC T4
Certificates
UL Certificate Number 99.19699
C
UL, cUL Entity Parameters
and Requirements
US
Class I Division 1 Hazardous
UL, cUL I/O Entity Parameters and Requirements
Terminals
Male Bus
Connector
Vt (V)
5.8
It (mA)
400
Groups
A-G
Ca (µF)
3.0
La (µH)
3.0
See the ControlNet Ex System chapter on page 16-1.
Publication 1797-6.5.6 - November 2000
UL, cUL Certification Information
Index
Numerics
1797-ACNR15/B
Ex directive 2-5, 13-2, 14-2
inputs/outputs 13-2, 14-2, 27-1, 28-1, 41-1, 42-1
module installation 13-1, 14-1, 27-1, 28-1, 41-1, 42-1
specifications 2-7, 13-3, 14-3, 27-1, 28-2, 41-1, 42-2
1797-IBN16
entity parameters
CE/CENELEC 5-3, 33-2
UL 19-3, 33-2
inputs 5-1, 19-1, 33-1
specifications 5-2, 19-2, 33-2
wiring 5-2, 19-1, 33-1
1797-IE8
electrostatic charge 1-2, 2-6, 15-2, 16-6, 29-2
entity parameters
CE/CENELEC 7-3, 8-3, 35-4, 36-4
UL 21-3, 22-3, 23-2, 35-2, 36-2, 37-2
Ex directive 1-2
inputs 7-1, 8-1, 21-1, 22-1, 35-1, 36-1
installation in Zone 1 1-2, 2-5, 15-2, 16-5, 29-2
module installation 1-1, 3-1, 5-1, 6-1, 7-1, 8-1, 9-1, 10-1,
11-1, 15-1, 17-1, 19-1, 20-1, 21-1, 22-1, 23-1,
24-1, 25-1, 29-1
repair 1-3, 2-6, 15-2, 16-6, 29-2
specifications 7-2, 8-2, 21-2, 22-2, 23-2, 35-2, 36-2
wiring 7-2, 8-2, 21-1, 22-2, 23-1, 35-1, 36-1
1797-IJ2
entity parameters
CE/CENELEC 11-3, 39-2
output 11-6
UL 25-2, 39-2
inputs 11-1, 25-1, 39-1
specifications 11-2, 25-2, 39-2
wiring 11-2, 25-1, 39-1
1797-IRT8
entity parameters
CE/CENELEC 10-3, 38-2
UL 24-3, 38-2
inputs 10-1, 24-1, 38-1
specifications 10-2, 24-2, 38-2
wiring 10-2, 24-2, 38-1
1797-OB4D
entity parameters
CE/CENELEC 6-2, 34-2
outputs 6-1, 20-1, 34-1
specifications 6-2, 20-2, 34-2
wiring 6-1, 20-1, 34-1
1797-OE8
entity parameters
CE/CENELEC 9-2, 37-2
outputs 9-1, 23-1, 37-1
specifications 9-1, 37-1
wiring 9-1, 37-1
1797-PS2N, -PS2E
entity parameters
UL 26-2, 40-2
Ex directive 12-2
installation in Zone 1 12-1, 26-1, 40-1
outputs 12-2, 26-1, 40-1
specifications 12-3, 26-2, 40-2
wiring 12-3, 26-1, 40-1
Publication 1797-6.5.6 - November 2000
2
Index
1797-TB3 3-1, 4-1, 17-1, 18-1, 31-1, 32-1
description 3-2, 17-2, 31-2
inputs 3-2, 4-2, 17-2, 18-2, 31-2, 32-2
installation in Zone 1 3-1, 4-1, 17-1, 18-1, 31-1, 32-1
module installation 3-1, 4-1, 17-1, 18-1, 31-1, 32-1
specifications 3-3, 4-3, 17-3, 18-3, 31-3, 32-3
wiring diagram 3-2, 17-2, 31-2
1797-TB3S
wiring diagram 3-2, 4-2, 17-2, 18-2, 31-2, 32-2
A
Adapter
See 1797-ACNR15/B 13-1, 14-1, 27-1, 28-1, 41-1, 42-1
Analog module
See 1797-IE8 1-1, 2-1, 7-1, 8-1, 15-1, 16-1, 21-1, 22-1,
23-1, 29-1, 30-1, 35-1, 36-1
Analog modules
See 1797-OE8 9-1, 37-1
C
CE/CENELEC
entity parameters
1797-IBN16 5-3, 33-2
1797-IE8 7-3, 8-3, 35-4, 36-4
1797-IJ2 11-3, 39-2
output 11-6
1797-IRT8 10-3, 38-2
1797-OB4D 6-2, 34-2
1797-OE8 9-2, 37-2
ControlNet Ex redundant media adapter
See 1797-ACNR15/B 13-1, 14-1, 27-1, 28-1, 41-1, 42-1
D
Description
1797-TB3 3-2, 17-2, 31-2
E
Electrostatic charge
1797-IE8 1-2, 2-6, 15-2, 16-6, 29-2
Publication 1797-6.5.6 - November 2000
Entity parameters
CE/CENELEC
1797-IBN16 5-3, 33-2
1797-IE8 7-3, 8-3, 35-4, 36-4
1797-IJ2 11-3, 39-2
output 11-6
1797-IRT8 10-3, 38-2
1797-OB4D 6-2, 34-2
1797-OE8 9-2, 37-2
UL
1797-IBN16 19-3, 33-2
1797-IE8 21-3, 22-3, 23-2, 35-2, 36-2, 37-2
1797-IJ2 25-2, 39-2
1797-IRT8 24-3, 38-2
1797-OB4D 20-2, 34-2
1797-PS2N, -PS2E 26-2, 40-2
Ex directive
1797-ACNR15/B 2-5, 13-2, 14-2
1797-IE8 1-2
1797-PS2N, -PS2E 12-2
F
FLEX Ex 16 NAMUR input module
See 1797-IBN16 5-1, 19-1, 33-1
FLEX Ex 24V dc non-isolated source 4 output module
See 1797-OB4D 6-1, 20-1, 34-1
FLEX Ex 8 input analog module
See 1797-IE8 1-1, 2-1, 7-1, 8-1, 15-1, 16-1, 21-1, 22-1,
23-1, 29-1, 30-1, 35-1, 36-1
FLEX Ex 8 output analog module
See 1797-OE8 9-1, 37-1
FLEX Ex frequency input module
See 1797-IJ2 11-1, 25-1, 39-1
FLEX Ex terminal base unit
See 1797-TB3 3-1, 4-1, 17-1, 18-1, 31-1, 32-1
FLEX Ex thermocouple/RTD input module
See 1797-IRT8 10-1, 24-1, 38-1
I
Inputs
1797-IBN16 5-1, 19-1, 33-1
1797-IE8 7-1, 8-1, 21-1, 22-1, 35-1, 36-1
1797-IJ2 11-1, 25-1, 39-1
1797-IRT8 10-1, 24-1, 38-1
1797-TB3 3-2, 4-2, 17-2, 18-2, 31-2, 32-2
Inputs/Outputs
1797-ACNR15/B 13-2, 14-2, 27-1, 28-1, 41-1, 42-1
Index
Installation in Zone
1797-TB3 3-1, 4-1, 17-1, 18-1, 31-1, 32-1
Installation in Zone 1
1797-IE8 1-2, 2-5, 15-2, 16-5, 29-2
1797-PS2N, -PS2E 12-1, 26-1, 40-1
M
Module installation
1797-ACNR15/B 13-1, 14-1, 27-1, 28-1, 41-1, 42-1
1797-IE8 1-1, 3-1, 5-1, 6-1, 7-1, 8-1, 9-1, 10-1, 11-1, 15-1,
17-1, 19-1, 20-1, 21-1, 22-1, 23-1, 24-1, 25-1,
29-1
1797-TB3 3-1, 4-1, 17-1, 18-1, 31-1, 32-1
O
Outputs
1797-OB4D 6-1, 20-1, 34-1
1797-OE8 9-1, 23-1, 37-1
1797-PS2N, -PS2E 12-2, 26-1, 40-1
3
S
Specifications
1797-ACNR15/B 2-7, 13-3, 14-3, 27-1, 28-2, 41-1, 42-2
1797-IBN16 5-2, 19-2, 33-2
1797-IE8 7-2, 8-2, 21-2, 22-2, 23-2, 35-2, 36-2
1797-IJ2 11-2, 25-2, 39-2
1797-IRT8 10-2, 24-2, 38-2
1797-OB4D 6-2, 20-2, 34-2
1797-OE8 9-1, 37-1
1797-PS2N, -PS2E 12-3, 26-2, 40-2
1797-TB3 3-3, 4-3, 17-3, 18-3, 31-3, 32-3
T
Terminal base
See 1797-TB3 or 1797-TB3S 3-1, 4-1, 17-1, 18-1, 31-1,
32-1
U
UL
entity parameters
P
Power supplies
See 1797-PS2N, -PS2E 12-1, 26-1, 40-1
R
Repair
1797-IE8 1-3, 2-6, 15-2, 16-6, 29-2
1797-IBN16 19-3, 33-2
1797-IE8 21-3, 22-3, 23-2, 35-2, 36-2, 37-2
1797-IJ2 25-2, 39-2
1797-IRT8 24-3, 38-2
1797-OB4D 20-2, 34-2
1797-PS2N, -PS2E 26-2, 40-2
W
Wiring
1797-IBN16 5-2, 19-1, 33-1
1797-IE8 7-2, 8-2, 21-1, 22-2, 23-1, 35-1, 36-1
1797-IJ2 11-2, 25-1, 39-1
1797-IRT8 10-2, 24-2, 38-1
1797-OB4D 6-1, 20-1, 34-1
1797-OE8 9-1, 37-1
1797-PS2N, -PS2E 12-3, 26-1, 40-1
Wiring diagram
1797-TB3 3-2, 17-2, 31-2
1797-TB3S 3-2, 4-2, 17-2, 18-2, 31-2, 32-2
Publication 1797-6.5.6 - November 2000
4
Index
Notes:
Publication 1797-6.5.6 - November 2000