GENERAL ELECTRICAL NOTES
480V/277Y PANEL
(E.T.R.)
1.
ALL GATE NUMBERS USED IN DRAWING ARE POST TRIP DESIGNATIONS.
2.
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES HAVING JURISDICTION.
3.
THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY FOR INSPECTIONS, TESTS, AND OTHER
SERVICES NECESSARY FOR THE COMPLETION OF HIS WORK
4.
ANY DIFFICULTIES IN COMPLYING WITH THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE D/FW AIRPORT/ENGINEER
BEFORE BIDDING.
5.
IT IS THE INTENT OF THESE DRAWINGS AND OTHER RELATED DOCUMENTS TO PRODUCE A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM. THE
ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL AND OTHER SERVICES AS MAY BE NECESSARY TO ACHIEVE THIS PRODUCT. IT
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO BRING TO THE ATTENTION OF THE ARCHITECT ANY DISCREPANCIES IN THE PLANS AND
SPECIFICATIONS THAT WILL AFFECT THE WORK.
6.
IF, DURING THE COURSE OF THE WORK, THE CONTRACTOR EXPERIENCES A PROBLEM WITH THE PERFORMANCE OF THE INSTALLATION RELATIVE TO
THE PLANS AND SPECIFICATIONS, THE NATIONAL ELECTRICAL CODE, OTHER APPLICABLE CODES AND GOVERNING DOCUMENTS, THE CONTRACTOR
SHALL BRING THE PROBLEM TO THE ATTENTION OF THE D/FW AIRPORT AND/OR THE ENGINEER FOR RESOLUTION PRIOR TO EXECUTION OF THE
WORK.
7.
ALL MATERIAL SHALL BE NEW AND BEAR THE UL LABEL LISTED APPROVAL FOR ITS INSTALLED APPLICATION.
8.
ALL MAJOR COMPONENTS OF THE ELECTRICAL SYSTEMS SUCH AS SAFETY DISCONNECT SWITCHES, AND PANELBOARDS SHALL BE BY THE SAME
MANUFACTURER.
9.
CIRCUIT BREAKERS USED FOR SWITCHING OF LIGHTING OR SIGN CIRCUITS SHALL BE APPROVED FOR SWITCHING DUTY AND SHALL BE MARKED "SWD"
IN ACCORDANCE WITH N.E.C. ART. 240.83 (D).
PCA (E.T.R.)
CP-B11
(R&A)
B11
GPU-B11
(R&A)
B11
CH-B11
(R&A)
CP-B10
(R&A)
PCA (E.T.R.)
B10
480V/277Y PANEL
(E.T.R.)
10. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT LOCATIONS OF HVAC EQUIPMENT.
11. ELECTRICAL PLANS ARE DIAGRAMMATIC. DO NOT SCALE FROM DRAWINGS.
12. ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST INTERFERE WITH THE MAINTENANCE AND OPERATION OF ALL
RELATED OR AFFECTED SYSTEMS. ALL POWER OUTAGES SHALL BE COORDINATED WITH D/FW AIRPORT.
GPU-B10
(R&A)
13. ALL BRANCH CIRCUIT CONDUCTORS FROM THE PANEL TO THE FIRST DISCONNECT SHALL BE INCREASED TO THE NEXT LARGER SIZE WHERE THE
LENGTH OF THE HOME RUN EXCEEDS 2% VOLTAGE DROP FOR THE LOAD CONNECTED.
480V/277Y PANEL
(E.T.R.)
B10
PCA (E.T.R.)
14. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SIZING OF ALL MOTOR OVERLOAD DEVICES (HEATERS) IN STARTERS BASED ON ACTUAL
NAMEPLATE RATINGS ON THE MOTORS BEING INSTALLED.
CP-B9
(R&A)
15. CONTRACTOR SHALL NOTE UL LABELS ON PACKAGE TYPE MECHANICAL EQUIPMENT. IF UL LABEL ON MECHANICAL EQUIPMENT CALLS FOR THE
OVERCURRENT PROTECTIVE DEVICE TO BE FUSES, THE ELECTRICAL CONTRACTOR SHALL PROVIDE A FUSED DISCONNECT SWITCH WITH PROPER
SIZE FUSES AT THE SWITCH LOCATION INDICATED ON DRAWINGS.
B9
CH-B10
(R&A)
16. CONTRACTOR SHALL VERIFY WIRE SIZES, CIRCUIT BREAKER AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION OF THE
ARCHITECT AND/OR THE ENGINEER ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO PROCEEDING.
17. HORSEPOWER RATINGS INDICATED ON DRAWING MAY DIFFER FROM ACTUAL EQUIPMENT FURNISHED. IF FURNISHED EQUIPMENT DIFFERS FROM
RATINGS ON DRAWINGS, CONTRACTOR SHALL NOTIFY ARCHITECT AND/OR THE ENGINEER FOR APPROPRIATE ACTION TO BE TAKEN.
GPU-B9
(R&A)
18. PROVIDE APPROVED "HACR" TYPE CIRCUIT BREAKERS FOR ALL HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT INDICATED FOR
CONNECTION ON ELECTRICAL DRAWINGS.
19. THE CONTRACTOR SHALL GUARANTEE ALL HIS WORK AND MATERIALS FOR A MINIMUM PERIOD OF ONE YEAR AFTER ACCEPTANCE BY OWNER.
B9
20. WIRE AND CABLE SHALL BE COPPER, TYPE THHN/THWN, MINIMUM #12 AWG. SEE DRAWINGS FOR EXCEPTIONS.
21. PANELBOARD DIRECTORIES SHALL BE UPDATED TO REFLECT ALL WORK DONE AS PART OF THIS PROJECT.
CH-B9
(R&A)
22. ALL NEW BRANCH CIRCUITS SHALL BE EQUIPPED WITH A MINIMUM #12 AWG GREEN EQUIPMENT GROUND CONDUCTOR.
23. ALL BUILDING WIRING SHALL BE RUN IN RIGID GALVANIZED STEEL CONDUIT.
24. AS-BUILT CONDITIONS HAVE BEEN SURVEYED BUT VARIOUS PROJECTS IMPLEMENTED OVER THE LIFE OF THE EQUIPMENT HAVE CREATED
NON-STANDARD INSTALLATIONS. SHOULD CONTRACTOR IDENTIFY ANY GAPS IN SCOPE, SUBMIT REQUEST FOR INFORMATION FOR CLARIFICATION.
480V/277Y PANEL
(E.T.R.)
480V/277Y PANEL
(E.T.R.)
B7
CP-B8
(E.T.R.)
B8
25. EXISTING HEAT TRACE SYSTEMS ARE PRESENT FOR ALL PIPING ASSOCIATED WITH WATER. THESE SYSTEMS MUST BE FUNCTIONAL AFTER ALL
UPGRADES HAVE BEEN IMPLEMENTED.
GPU-B8
(R&A)
PCA (E.T.R.)
B8
B3
480V/277Y PANEL
(E.T.R.)
CH-B8
(R&A)
PCA (E.T.R.)
PCA (E.T.R.)
B2
GPU-B1
(R&A)
B7
480V/277Y PANEL
(E.T.R.)
GPU-B6
(R&A)
CH-B6
(R&A)
11
PRE TRIP GATE DESIGNATION
VERIFY GATE NUMBERING STATUS PRIOR TO
PROCEEDING WITH WORK AT GATE.
CH-B5
(R&A)
6
B5
B4
7
8
B1
CP-B1
(R&A)
9
POST TRIP GATE DESIGNATION
GPU-B5
(R&A)
480V/277Y PANEL
(E.T.R.)
10
B10
CP-B5
(E.T.R.)
B6
CH-B1
(R&A)
B11
480V/277Y PANEL
(E.T.R.)
PCA (E.T.R.)
480V/277Y PANEL
(E.T.R.)
CP-B2
(E.T.R.)
PCA (E.T.R.)
PCA = PRE-CONDITIONED AC UNIT
CP = CONDENSATE PUMP
PCA (E.T.R.)
B1
CP-B6
(E.T.R.)
CP-B3
(R&A)
GPU-B2
(R&A)
(R&A) = REMOVE EXISTING & ADD NEW
GPU = GROUND POWER UNIT
B5
B3
CH-B2
(R&A)
(E.T.R.) = EXISTING TO REMAIN
CH-B7
(E.T.R.)
GPU-B3
(R&A)
ABBREVIATIONS
B6
GPU-B7
(E.T.R.)
CH-B3
(R&A)
B2
CP-B7
(R&A)
PCA (E.T.R.)
02 JET BRIDGES B1,B2,B3
SCALE: 1/32" = 1'-0"
01 JET BRIDGES B5 THRU B11
SCALE: 1/32" = 1'-0"
NORTH
0
4'
8'
16'
NORTH
SCALE IN FEET 1/32" = 1'-0"
PRIME CONSULTANT
CONSULTANT
SEAL
OWNER
KEYPLAN
ENGINEER
CH2M HILL
12750 MERIT DRIVE
SUITE 1100
DALLAS, TEXAS 75251
DALLAS / FORT WORTH
INTERNATIONAL AIRPORT
Established 1960
10670 N. CENTRAL EXPWY
DALLAS, TEXAS 75231
FAX (972)789-2606
TEL (972)789-2600
TX. REG. #F-2800
AGUIRRE RODEN
TBPE REGISTRATION #2800
DFW TERMINAL B
LOWER GATE
ELECTRIFICATION
TERMINAL B CONSTRUCTION DOCUMENTS
208C
207C
FILE NAME: E-1
206C
209C
209B
208A
210C
209A
210B
210A
211C
206B
207A
DRAWN BY: EH
CHECKED BY: JV
205C
207B
208B
209D
NORTH
205B
204C
206A
205A
204B
MEP RAMP
LEVEL - GATES B1
THRU B3, B5 THRU
B11
203D
204A
211B
203B
211A
203C
203A
212C
212B
212A
213C
213B
1103A
1102A
1101A
213A
202A
NOTE: SHADED SECTORS ARE
WITHIN THIS SCOPE
OF WORK
201A
202B
202C
201B
201C
REV
DATE
DESCRIPTION
ISSUED FOR BID: 06/17/2016
Contract No.: 9500589
TA # A16-129B
E-1
BORDER RELEASE DATE: 01/16/2012
B21
GPU-B21
(R&A)
CH-B21
(R&A)
CH-B29
(R&A)
PCA-B21
(E.T.R.)
2
B29
B2
GPU-B20
(R&A)
B20
GPU-B29
(R&A)
PCA
(E.T.R.)
1
B2
CP-B21
(R&A)
480V/277Y PANEL
(E.T.R.)
B29
CP-B29
(R&A)
CP-B20
(R&A)
CH-B20
(R&A)
PCA-B20
(R&A)
GPU-B19
(R&A)
0
B2
B19
480V/277Y PANEL
(E.T.R.)
480V/277Y PANEL
(E.T.R.)
CP-B19
(E.T.R.)
CH-B19
(R&A)
PCA-B25
(R&A)
7
B2
480V/277Y PANEL
(E.T.R.)
GPU-B23
(E.T.R.)
B1
8
PCA (E.T.R.)
PCA-B23
(R&A)
B22
480V/277Y PANEL
(E.T.R.)
6
B2
5
B2
B2
4
CH-B23
(E.T.R.)
GPU-B22
(E.T.R.)
GPU-B17
(R&A)
B17
CP-B25
(R&A)
B23
CP-B18
(R&A)
CH-B18
(R&A)
B28
480V/277Y PANEL
(E.T.R.)
GPU-B18
(R&A)
B18
GPU-B25
(R&A)
CH-B25
(R&A)
B1
9
PCA-B19
(E.T.R.)
B25
PCA-B22
(R&A)
CP-B17
(R&A)
CH-B22
(E.T.R.)
CH-B17
(R&A)
CP-B23
(E.T.R.)
PCA (REMOVE)
3
B2
480V/277Y PANEL
(E.T.R.)
B1
7
PCA (E.T.R.)
CP-B22
(E.T.R.)
GPU-B16
(R&A)
B16
2
B2
480V/277Y PANEL
(E.T.R.)
1
B2
CP-B16
(R&A)
01 JET BRIDGES B22, B23, B25 & B29
B16
CH-B16
(R&A)
PCA (E.T.R.)
SCALE: 1/32" = 1'-0"
NORTH
480V/277Y PANEL
(E.T.R.)
GPU-B15
(R&A)
B15
ABBREVIATIONS
CP-B15
(E.T.R.)
(E.T.R.) = EXISTING TO REMAIN
(R&A) = REMOVE EXISTING & ADD NEW
CH-B15
(R&A)
B15
480V/277Y PANEL
(E.T.R.)
PCA (E.T.R.)
CH-B41
(R&A)
GPU = GROUND POWER UNIT
B41
PCA = PRE-CONDITIONED AC UNIT
CP = CONDENSATE PUMP
GPU-B41
(R&A)
B43
GPU-B14
(R&A)
B14
CH-B14
(R&A)
B14
CP-B14
(E.T.R.)
B43
PCA
(E.T.R.)
480V/277Y PANEL
(E.T.R.)
CH-B43
(R&A)
B13
CP-B41
(R&A)
GPU-B13
(R&A)
PRE TRIP GATE DESIGNATION
VERIFY GATE NUMBERING STATUS PRIOR TO
PROCEEDING WITH WORK AT GATE.
PCA (E.T.R.)
CP-B13
(R&A)
B43
POST TRIP GATE DESIGNATION
GPU-B43
(R&A)
B40
B41
480V/277Y PANEL
(E.T.R.)
PCA
(E.T.R.)
CP-B43
(R&A)
B13
480V/277Y PANEL
(E.T.R.)
PCA (R&A)
CH-B13
(R&A)
CP-B12
(R&A)
B12
PCA-B12
(E.T.R.)
480V/277Y PANEL
(E.T.R.)
480V/277Y PANEL
(E.T.R.)
GPU-B12
(R&A)
B42
B43
B12
CH-B12
(R&A)
B44
02 JET BRIDGES B41 & B43
03 JET BRIDGES B12 THRU B21
0
SCALE: 1/32" = 1'-0"
SCALE: 1/32" = 1'-0"
PRIME CONSULTANT
CONSULTANT
SEAL
ENGINEER
CH2M HILL
12750 MERIT DRIVE
SUITE 1100
DALLAS, TEXAS 75251
10670 N. CENTRAL EXPWY
DALLAS, TEXAS 75231
FAX (972)789-2606
TEL (972)789-2600
TX. REG. #F-2800
DALLAS / FORT WORTH
INTERNATIONAL AIRPORT
AGUIRRE RODEN
TBPE REGISTRATION #2800
16'
OWNER
KEYPLAN
Established 1960
8'
SCALE IN FEET 1/32" = 1'-0"
NORTH
NORTH
4'
DFW TERMINAL B
LOWER GATE
ELECTRIFICATION
TERMINAL B CONSTRUCTION DOCUMENTS
208C
207C
FILE NAME: E-2
206C
209C
209B
208A
210C
209A
210B
210A
211C
206B
207A
DRAWN BY: EH
CHECKED BY: JV
205C
207B
208B
209D
NORTH
205B
204C
206A
205A
204B
MEP RAMP
LEVEL - GATES B12
THRU B23, B25, B29,
B41, & B43
203D
204A
211B
203B
211A
203C
203A
212C
212B
212A
213C
213B
1103A
1102A
1101A
213A
202A
NOTE: SHADED SECTORS ARE
WITHIN THIS SCOPE
OF WORK
201A
202B
202C
201B
201C
REV
DATE
DESCRIPTION
ISSUED FOR BID: 06/17/2016
Contract No.: 9500589
TA # A16-129B
E-2
BORDER RELEASE DATE: 01/16/2012
PROVIDE 2-1/2" DUAL TUBE PANTOGRAPH OR EQUAL
FOR GATES B1 THRU B8, B10, B12, B13, B20 THRU B25,
B29, B41, & B43 AS REQUIRED.
EXISTING TERMINAL FACE
ROTUNDA
( EXISTING )
CH-B##
DUAL CABLE HOIST
EXISTING RTU
4
EXISTING CABLE HOIST
1
EXISTING GATE BOX
ROUTE CABLES THRU CONDUIT SLEEVES
WITH NYLON BUSHINGS ON EACH END ALONG
FIXED STRUCTURE.
EXISTING FIXED WALKWAY
EXISTING CONNECTIONS TO TERMINAL SYSTEMS
WRAP CABLES WITH PROTECTIVE SLEEVE AT
SUPPORT POINTS.
ROUTE CABLES THRU
PANTOGRAPH OR EQUAL
GPU-B##
HEAT TRACE ALL EXERIOR EXPOSED DISCHARGE
CONDENSATE/DOM. WTR. PIPING FROM POTABLE
WATER CABINET TO RAMP
100/NF/3
4
PCA UNIT
PCA-B##
9
AIRCRAFT GROUND POWER UNIT
ON 'C' TUNNEL OF PBB
2
8
ELECTRICAL POWER ALONG EXISTING WALKWAY
30/NF/3
3
PROVIDE NEW 1-5/8" SLOTTED CHANNEL
UNISTRUT FRAMING FOR MOUNTING OF
DISCONNECTS AT GATES B24, B25, AND B27.
EXISTING POTABLE WATER CABINET (PWC)
30/NF/3
CP-B##
30/NF/3
7
EXISTING 480V/3Ø
DISTRIBUTION PANEL
6
5
CONTROL STATIONS ON WHITE ENAMEL
PAINTED TO MATCH JETWAY 1/4" STEEL
PLATE BOLTED TO SUPPORT. SEE DETAIL
ON SHEET E-5
HT-B##
CONDENSATE RECEIVER. PROVIDE AUTO
REGULATING BASIN HEATER. PROVIDE
POWER FROM CONDENSATE/SUMP PUMP
ELECTRICAL CIRCUIT
EXISTING FIXED
WALKWAY COLUMN
01 ELECTRICAL - JET BRIDGE ELEVATION
NOT TO SCALE
ELECTRICAL KEYED NOTES
X
1. REMOVE EXISTING GATE BOX, GPU, AND CABLE HOIST(S) AND RETURN TO DFW AIRPORT FOR GATES B1, B2, B3, B5, B6, B8 THRU B21, B25, B29, B41, AND B43.
2. REMOVE EXISTING GATE BOX, GPU, AND CABLE HOIST(S) DISCONNECTS AND RETURN TO DFW AIRPORT FOR GATES B1, B2, B3, B5, B6, B8 THRU B21, B25, B29, B41,
AND B43.
3. REMOVE EXISTING CONDENSATE PUMP AND HEAT TRACE DISCONNECTS AND RETURN TO D/FW AIRPORT FOR GATES B1, B2, B3, B7 THRU B21, B25, B29, B41, AND
B43.
4. PROVIDE AIRCRAFT GROUND POWER UNIT CABLES AND CABLE HOIST FOR GATES B1, B2, B3, B5, B6, B8 THRU B21, B25, B29, B41, AND B43.
POWER CABLE THRU PANTOGRAPH TO DISCONNECT AT ROTUNDA.
ROUTE INCOMING
5. PROVIDE CH (CABLE HOIST) CONTROL STATION FOR GATES B1, B2, B3, B5, B6, B8 THRU B21, B25, B29, B41, AND B43.
6. PROVIDE PCA CONTROL STATION FOR GATES B13, B20, B22, B23, AND B25.
7. PROVIDE CONDENSATE PUMP AND HEAT TRACE FUSED DISCONNECTS FOR GATES B1, B2, B3, B7 THRU B21, B25, B29, B41, AND B43. MOUNT DISCONNECT SUCH
THAT NO HANDLE IS ABOVE 6' 6".
8. PROVIDE AIRCRAFT GROUND POWER UNIT AND CABLE HOIST DISCONNECTS FOR GATES B1, B2, B3, B5, B6, B8 THRU B21, B25, B29, B41, AND B43. MOUNT
DISCONNECT SUCH THAT NO HANDLE IS ABOVE 6' 6".
9. PROVIDE PCA DISCONNECT FOR GATES B13, B20, B22, B23, AND B25. MOUNT DISCONNECT SUCH THAT NO HANDLE IS ABOVE 6'-6".
PRIME CONSULTANT
CONSULTANT
SEAL
OWNER
FILE NAME: E-3
ENGINEER
CH2M HILL
12750 MERIT DRIVE
SUITE 1100
DALLAS, TEXAS 75251
DALLAS / FORT WORTH
INTERNATIONAL AIRPORT
Established 1960
10670 N. CENTRAL EXPWY
DALLAS, TEXAS 75231
FAX (972)789-2606
TEL (972)789-2600
TX. REG. #F-2800
AGUIRRE RODEN
TBPE REGISTRATION #2800
EH
DRAWN BY:
CHECKED BY: JV
DFW TERMINAL B
LOWER GATE
ELECTRIFICATION
TERMINAL B CONSTRUCTION DOCUMENTS
ELECTRICAL
ELEVATION
REV
DATE
DESCRIPTION
ISSUED FOR BID: 06/17/2016
Contract No.: 9500589
TA # A16-129B
E-3
BORDER RELEASE DATE: 01/16/2012
GATE BOX AIRCRAFT GROUND POWER UNIT (GPU)
OUTPUT
@400HZ
MANUFACTURER
RATING
@400HZ
MODEL
RATING
@28VDC
MODEL
B1
J&B AVIATION
260
TG9516-60
600A
JB2840-65
ALL
B2
J&B AVIATION
260
TG9516-60
600A
JB2840-65
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B3
J&B AVIATION
260
TG9516-60
600A
JB2840-65
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B5
J&B AVIATION
260
TG9516-60
600A
JB2840-65
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B6
J&B AVIATION
260
TG9516-60
600A
JB2840-65
OUTPUT
@28VDC
MANUFACTURER
MODEL
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
600/2500A MAX
VOLTAGE
PHASE
B1
480V
3
150A
108.3A
B2
480V
3
150A
B3
480V
3
B5
480V
3
GPU-
AIRCRAFT CABLE ASSEMBLY
MOCP
MCA
NOTES
CABLE HOIST MODEL
CABLE
B6
480V
3
150A
108.3A
260A
B8
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B8
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B9
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B9
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B10
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B10
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B11
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B11
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B12
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B12
J&B AVIATION
260
TG9516-60
600A
JB2840-65
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B13
J&B AVIATION
260
TG9516-60
600A
JB2840-65
3#4, #4G
TYPE W CORD WITH LIQUID TIGHT STRAIN
RELIEF CONNECTOR AT EACH END
3#1, #6G, 1-1/2" RGS.
1
6
B13
480V
3
150A
108.3A
260A
B14
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B14
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B15
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B15
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B16
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B16
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B17
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B17
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B18
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B18
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B19
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B19
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B20
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B20
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B21
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B21
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B25
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B25
J&B AVIATION
260
TG9516-60
600A
JB2840-65
JB2840-65
B29
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B29
J&B AVIATION
260
TG9516-60
600A
B41
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B41
J&B AVIATION
260
TG9516-60
600A
JB2840-65
B43
480V
3
150A
108.3A
260A
600/2500A MAX
HOBART SYSTEMS
90SX200
CCCPCH-60-480BM-RC-N4X-DCH-FWL-BBS (OR APPROVED EQUIVALENT)
ALL
B43
J&B AVIATION
260
TG9516-60
600A
JB2840-65
7
100/NF/3/4X
PCA
3#4, #4G
TYPE W CORD WITH LIQUID TIGHT STRAIN
RELIEF CONNECTOR AT EACH END
3#1/0, #6G, 2"RGS.
2
6
5
7
200/NF/3/4X
GPU
3#12, #12G
TYPE SOOW CORD WITH LIQUID TIGHT
STRAIN RELIEF CONNECTOR AT EACH
END
3#12, #12G, 1"RGS.
3
6
7
30/NF/3/4X
CH
NOTES :
1.
2.
3.
4.
5.
6.
7.
8.
PROVIDE 28.5 VDC AS 2ND OUTPUT.
PROVIDE BRIDGE AND TRAILER MOUNTING KITS.
PROVIDE REMOTE OPERATOR STATION.
PROVIDE LOCKABLE DOOR.
PROVIDE COVER FOR OPERABLE PANEL.
PROVIDE RS422/RS485 COMMUNICATION PORT.
PROVIDE TCP/IP INTERFACE.
PROVIDE OUTPUT TERMINAL EXTENSIONS FOR TWO 7-CONDUCTOR
CABLES.
9. PROVIDE BROKEN NEUTRAL DETECTION.
10. PROVIDE GPU INTERLOCK.
11. PROVIDE PLUG INSERTION INTERLOCK.
12. PROVIDE SERVICE TOOL.
2#10, #10G
1" RGS
2#10, #10G, 1" RGS.
SAFETY SWITCH
DESIGNATION
4
7
30/NF/1/4X
CP
DISCONNECT SIZE
FUSE RATING (NF=NON FUSED)
7
PHASE(S)
NEMA ENCLOSURE RATING
(IF NOT 1)
2#12, #12G
1" RGS
2#10, #10G, 1"RGS.
60/60/3/3R
4
7
30/NF/1/4X
HTC
7
NOTE: RGS = RIGID GALVANIZED
STEEL METALLIC CONDUIT
1
1/4" STEEL PLATE PAINT ENAMEL TO MATCH
JETBRIDGE. MOUNT ON JET BRIDGE SUPPORT
EQUIPMENT CONNECTION ONE-LINES
NOT TO SCALE
KEYED NOTES:
1. ROUTE CONDUIT AND WIRE TO EXISTING 480V/277Y 4 WIRE PANEL AT ROTUNDA. PROVIDE HACR RATED
100A CIRCUIT BREAKER IN PANEL AT ROTUNDA OF SAME TYPE AND AIC RATING AS OTHERS IN THIS PANEL.
THIS NOTE APPLIES TO GATES B13, B20, B23, AND B25. SEE SHEET E-1 AND E-2 FOR PANEL LOCATION.
GALVANIZED UNISTRUT
CHANNEL
400Hz
CABLE
RAISE
LOWER
400 Hz ON
PRECONDITIONED AIR
ON
28VDC
CABLE
RAISE
LOWER
2. ROUTE CONDUIT AND WIRE TO EXISTING 480V/277Y 4 WIRE PANEL AT ROTUNDA. PROVIDE 150A CIRCUIT
BREAKER IN PANEL AT ROTUNDA OF SAME TYPE AIC RATING AS OTHERS IN THIS PANEL. THIS NOTE
APPLIES FOR GATES B1, B2, B3, B5, B6, B8, B13 THRU B21, B25, B29, B41, AND B43. SEE SHEET E-1 AND E-2 FOR
PANEL LOCATION.
DISCONNECTS TO BE
MOUNTED TO RACK
NOTE: GALVANIZED STEEL SUPPORT
RACK BY STRUCTURAL ENGINEER.
OFF
28VDC Hz ON
3. ROUTE CONDUIT AND WIRE TO EXISTING 480V/277Y 4 WIRE PANEL AT ROTUNDA. PROVIDE 20A CIRCUIT
BREAKER IN PANEL AT ROTUNDA OF SAME TYPE AND AIC RATING AS OTHERS IN THIS PANEL. THIS
NOTE APPLIES TO GATES B1, B2, B3, B5, B6, B8, B9, B13 THRU B21, B25, B29, B41, AND B43. SEE SHEET E-1 AND
E-2 FOR PANEL LOCATION.
4. ROUTE CONDUIT AND WIRE TO EXISTING 208V/120Y 4 WIRE PANEL AT TERMINAL. FIELD VERIFY EXACT
LOCATION OF NEAREST 208V/120Y 4 WIRE PANEL IN RAMP LEVEL OF TERMINAL. PROVIDE 20A 1-POLE FOR
CONDENSATE PUMP AND A 20A 2-POLE FOR HEAT TRACE IN PANEL OF SAME TYPE AND AIC RATING AS
OTHERS IN THIS PANEL. THIS NOTE APPLIES TO GATES B1, B3, B7, B9, B10, B11, B12, B13, B14, B16, B17, B18,
B20, B21, B25, B29, B41, AND B43.
AIRCRAFT SELECT
400 Hz OFF
X
28VDC Hz OFF
5. ROUTE CONDUIT AND WIRE TO EXISTING 480V/277Y 4 WIRE PANEL AT TERMINAL. PROVIDE 150A CIRCUIT
BREAKER IN PANEL AT TERMINAL OF SAME TYPE AND AIC RATING AS OTHERS IN THIS PANEL. THIS NOTE
APPLIES TO GATE B9.
6. ROUTE GPU CORD SEPARATE FROM PCA AND CH. SEE SHEET E-1 AND E-2 FOR PANEL LOCATION.
6' - 6" MAXIMUM
7. CONNECT RGS TO BOX WITH LIQUID TIGHT MEYERS HUB.
DECK
2
PRIME CONSULTANT
CONTROL STATION DETAIL
3
NOT TO SCALE
CONSULTANT
SEAL
UNISTRUT RACK ASSEMBLY DETAIL
NOT TO SCALE
OWNER
FILE NAME: E-4
ENGINEER
CH2M HILL
12750 MERIT DRIVE
SUITE 1100
DALLAS, TEXAS 75251
DALLAS / FORT WORTH
INTERNATIONAL AIRPORT
Established 1960
10670 N. CENTRAL EXPWY
DALLAS, TEXAS 75231
FAX (972)789-2606
TEL (972)789-2600
TX. REG. #F-2800
AGUIRRE RODEN
TBPE REGISTRATION #2800
DRAWN BY:
EH
CHECKED BY: JV
DFW TERMINAL B
LOWER GATE
ELECTRIFICATION
TERMINAL B CONSTRUCTION DOCUMENTS
ELECTRICAL
DETAILS AND
SCHEDULES
REV
DATE
DESCRIPTION
ISSUED FOR BID: 06/17/2016
Contract No.: 9500589
TA # A16-129B
E-4
BORDER RELEASE DATE: 01/16/2012