APPLIC ATION NOTE 2011 National Electrical Code Compliance for Advanced Energy TX and NX Inverters Introduction CONTENTS •Introduction Page 1 •2011 NEC Section 690.11 Arc Fault Circuit Protection Page 1 - 2 •2011 NEC Section 690.16(B) Fuse Servicing Page 2 •Designing NEC-compliant Systems with Advanced Energy Inverters Page 3 •Conclusion Page 4 The 2011 version of the National Electrical Code (NEC) makes two significant changes to the 2008 version that apply to photovoltaic (PV) systems. Section 690.11 addresses Arc Fault Circuit Protection (Direct Current), and Section 690.16(B) addresses Fuse Servicing. This application note describes the new requirements, and provides guidance for how PV systems can be designed to comply with each using Advanced Energy TX and NX inver ters. This application note does not address all NEC compliance considerations, including the requirements already in the 2008 version. It focuses instead on how new deployments (assumed to be compliant with the 2008 NEC) can be made compliant with the 2011 version. System designers are encouraged to check with local Authorities Having Jurisdiction (AHJs) to ensure compliance with all per tinent regulations. 2011 NEC Section 690.11 Arc Fault Circuit Protection (Direct Current) Section 690.11 contains the following requirements, repeated here verbatim from the code for convenient reference: Photovoltaic systems with dc source circuits, dc output circuits, or both, on or penetrating a building operating at a PV system maximum system voltage of 80 volts or greater, shall be protected by a listed (dc) arc-fault circuit interrupter, PV type, or other system components listed to provide equivalent protection. The PV arc-fault protection means shall comply with the following requirements: (1) The system shall detect and interrupt arcing faults resulting from a failure in the intended continuity of a conductor, connection, module, or other system component in the dc PV source and output circuits. (2) The system shall disable or disconnect one of the following: a. Inverters or charge controllers connected to the fault circuit when the fault is detected b. System components within the arcing circuit (3) The system shall require that the disabled or disconnected equipment be manually restarted. (4) The system shall have an annunciator that provides a visual indication that the circuit interrupter has operated. This indication shall not reset automatically. AE Solar Energy is a US based company. APPLIC ATION NOTE Combiner Box with Arc Fault Detector and DAQ The purpose of this new section is to reduce the potential for PV system fires caused by series arc faults anywhere in the DC circuitry. The code requires the PV system to have the means to detect DC series arc faults and to isolate the arcing line, and that the circuit affected must be manually reset. Figure 1 shows an example of an NEC 2011-compliant combiner box with integrated Arc Fault Detector and Data Acquisition (DAQ) circuit installed. Inverter Figure 1 – Shown here is a circuit with a combiner-integrated Arc Fault Circuit Interruption and a series arc fault in a string. Common causes of DC arc faults include loose connections between modules, damaged DC cables, and improperly torqued combiner box connections. While these failure causes usually exist upon commissioning, they can also develop over time due to thermal or mechanical cycle fatigue. Figure 2 – Loose connectors are a common cause of arc faults. Image credit: Phoenix Contact It is impor tant to note that for this code cycle Section 690.11 requires the use of Arc Fault Circuit Interruption (AFCI) equipment only for PV systems that are connected to buildings (e.g. roof-top systems), and not for ground-mount systems. Because AFCI only became a requirement in 2011, standards for the design and testing of solutions are only now being developed. As of this writing, for example, very few manufacturers have AFCI devices listed for compliant use. Underwriters Laboratories has created a new standard (UL 1699B) for testing AFCI equipment, and a growing number of vendors are now subjecting their solutions to these tests. Page 2 For this reason, some AHJs have provided waivers for Section 690.11 compliance. Such waivers are permitted under NEC Section 90.4, which permits an exemption for new code requirements when the technology needed for compliance is not yet commercially available. The issuance of waivers is likely to continue until commercial solutions are tested for compliance and made available for deployment. Advanced Energy expects AFCI solutions to be implemented in string inver ters and combiner boxes, rather than in central inver ters, for two reasons. One is that detecting arc faults in central inver ters is technically challenging; as amperage increases, so too does system noise, making string-level arcing difficult to detect at the inver ter. The other involves the requirement that the arcing loop remain offline until the fault has been found and fixed. The advantage of string- and combiner-level detection is that isolating the PV system at these points reduces power loss during troubleshooting, and decreases the time it takes to find and fix the fault. 2011 NEC Section 690.16(B) Fuse Servicing Section 690.16(B) contains the following requirements, repeated here verbatim from the code for convenient reference: Disconnecting means shall be installed on PV output circuits where overcurrent devices (fuses) must be serviced that cannot be isolated from energized circuits. The disconnecting means shall be within sight of, and accessible to, the location of the fuse or integral with fuse holder and shall comply with 690.17. Where the disconnecting means are located more than 1.8m (6 ft) from the over current device, a directory showing the location of each disconnect shall be installed at the overcurrent device location. Non-load-break-rated disconnecting means shall be marked “Do not open under load.” Previous versions of the NEC required a disconnecting means, but did not specify a location. For example, the disconnecting means could have been in roof-mounted combiner boxes, while the inver ter was on the ground. In some cases, this led to unsafe work practices if a disconnecting means was not readily accessible. This new section in the NEC now requires that the disconnecting means be within sight of the fuses. APPLIC ATION NOTE Figure 3 shows the additional disconnecting means required for fused sub-array combiners. The purpose of this change is to enhance human safety by ensuring that DC source circuits are not live during overcurrent device servicing. Combiner Box Inverter DC Disconnect AC Disconnect Additional Disconnects Required per 2011 NEC 690.16 [B] Combiner Box Figure 3 – The additional disconnecting means required under Section 690.16(B) are shown here highlighted in red. In this example, the potential exists to service fuses while DC circuits are live. Because this new requirement places limitations on inver ters with integral fused sub-array combiners, the change is likely to drive inver ter manufacturers away from fused subsystems that have a down-stream disconnect, and towards breaker-based subsystems with dead-fronts. This is par ticularly true because system-level compliance can easily be achieved using external disconnects. Designing NEC-Compliant Systems with Advanced Energy Inverters Table 1 summarizes the combiner, recombiner, and inver ter requirements for 2011 NEC compliance in PV systems using Advanced Energy TX series inverters. Note that for rooftop systems, all TX inver ters require an AFCI for the combiner boxes (except in cases where a waiver has been issued by the AHJ). For ground-mount systems, there is no such requirement for an AFCI. Combiner Box Requirements AE 35TX AE 50TX AFCI Combiner required for rooftop applications* AE 75TX AE 100TX AFCI Combiner required for rooftop applications* AE 250TX AE 260TX AFCI Combiner required for rooftop applications* AE 500TX AFCI Combiner required for rooftop applications* Combiner Box Fused Sub-array Combiner Combiner Box Table 1 – Quick-guide to NEC 2011 Compliant Systems for TX inverters Recombiner / Inverter Requirements No recombiner required for single combiner box installation. Inverter has integrated dc disconnect for service. Option a) External disconnect required with optional inverter-integrated subcombiner. Option b) If an external circuit breaker based recombiner is used, the inverter has an integrated dc disconnect for service. Option a) Optional inverter integrated circuit breaker based subcombiner available in 2H 2013. Option b) If an external circuit breaker based recombiner is used, the inverter has an integrated dc disconnect for service. Inverter integrated circuit breaker subcombiner option *As solutions are tested and become available Refer to the AE 500TX Integrated DC circuit breaker based subcombiner option application note from Advanced Energy for more information on inver ter integrated circuit breaker subcombiners. Table 2 summarizes the combiner, recombiner, and inver ter requirements for 2011 NEC compliance in PV systems using Advanced Energy NX series inverters. Note that for rooftop systems, all NX inver ters require an AFCI for the combiner boxes (except in cases where a waiver has been issued by the AHJ). For ground-mount systems, there is no such requirement for an AFCI. Table 2 – Quick-guide to NEC 2011 Compliant Systems for NX inverters Inverter Combiner Box Requirements Recombiner Requirements AE 250NX AE 333NX AE 500NX AFCI Combiner required for rooftop applications* Use the inverter Field Wiring Enclosure (FWE) option with a disconnecting or circuit breaker based recombiner or disconnect. AE 1000NX AFCI Combiner required for rooftop applications* No external recombiner is required with standard integrated contactor based DC subcombiner. *As solutions are tested and become available Page 3 APPLIC ATION NOTE Conclusion Safety is the purpose of the National Electrical Code, and the 2011 version enhances worker safety with two new provisions that are applicable to PV systems: DC arc fault circuit protection and fuse servicing. Because NEC enforcement varies greatly by region, system designers are encouraged to consult with the AHJs to determine if and how these new provisions are being enforced, and whether or not a waiver is available until AFCI equipment can be tested and made commercially available. These new provisions will require changes to be made to combiner boxes, recombiners, inver ters, and system designs. Advanced Energy will be monitoring these changes and will provide regular updates about compatibility of new AFCI equipment and other solutions with the TX and NX series of inver ters in an *NEC Compatibility Table on our website. Additional information about NEC compliance and other design considerations can also be obtained by calling AE Solar Energy’s service team at (877)312-3832. * http://solarenergy.advanced-energy.com/upload/file/applicationnotes/neccompatibilitytable.pdf AE Solar Energy • 20720 Brinson Blvd • Bend, OR 97701 U.S.A. www.advanced-energy.com/solarenergy 877.312.3832 • sales.support@aei.com • invertersupport@aei.com Please see www.advanced-energy.com for worldwide contact information. Advanced Energy is a registered U.S. trademark of Advanced Energy Industries, Inc. © Advanced Energy Industries, Inc. All rights reserved. Printed in U.S.A. ENG-NEC-260-01 4/13