2040 Harnash Boulevard Billings, Montana 59102 406‐245‐0136 (phone) 406‐245‐2084 (fax) SUBMITTAL REVIEW To: Bill Goodman, TSP, Inc. From: Terry Jiracek Date In: 07/27/2015 Job: SCSD#2 – HS Locker Room Addition/Remodel Number of Copies Returned: One (1) PDF Date Reviewed: 07/28/2015 Job 14SH4331 Retained: One (1) PDF Submittal Title: spec 260519,260529,260533,262416,262726,262813,262913,265100 & 265600 ‐ Review #001 ASSOCIATED CONSTRUCTION ENGINEERING, INC. X Reviewed as noted ‐ No re‐submittal required Revise & Resubmit per comments No Exception Taken, Where Noted Reviewed By: Terry Jiracek Date: 07/28/2015 Review is for conformance with design concept & compliance with contract documents only. Contractor shall check & verify all quantities, field measurements & shall be responsible for all errors in shop drawings. Contractor shall be responsible for deviations from contract documents unless he has called attention to such deviation and secured written approval. All in accordance with the general conditions. Submittal Item #1: Specification Section 260519 – Conductors & Cables Comments: a. Mc cable shall only be utilized for light fixture whips in project. All other uses in project for cable is prohibited. b. All conductors’s #12 and smaller shall be solid. #10 and larger shall be stranded per specifications. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #2: Specification Section 260529 – Hangers & Supports Comments: Page 1 a. No Comment, accepted as submitted Review Status: Reviewed, no exception taken. Submittal Item #3: Specification Section 260533 – Raceway & Boxes Comments: a. Shop drawings contain many sheets of extra information on products that does not apply to project. Example is back boxes that accept NM cable, which is not an approved cable on the project. Only provide information that is applicable to project. b. Floor box submittal shall be purged of all information that does not apply to project when O&M’s are compiled. Example: there are no 6 gang boxes on the project. c. Floor box data insert bracket shall be verified for compliance with owners data system/ district standard jacks prior to ordering. d. The use of surface mounted Hubbell raceway shall only be done when approved by the Architect. All locations of desired use shall be reviewed and approved by Architect. Plans indicate the required locations of surface raceway in finished areas, which will be done with EMT. e. Architect shall select surface raceway device finish color between Ivory or White, coordinate prior to ordering. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #4: Specification Section 262416 ‐ Panelboards Comments: a. Lead EC on project shall verify lug feed location as top or bottom. b. Panel L‐B1H3 shall contain a 100A/3p breaker in place of the 40A/3P per PR#3. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #5: Specification Section 262726 – Wiring Devices Comments: a. Verify required wiring device finish color with Architect prior to ordering. b. There is no OS7 in the project. Remove cut sheet from submittal prior to compiling the O&M. Review Status: Reviewed as noted. No re‐submittal required. Page 2 Submittal Item #6: Specification Section 262813 ‐ Fuses Comments: a. Coordinate exact fuse size required with equipment served prior to ordering. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #7: Specification Section 262913 ‐ Controllers Comments: a. Verify the required fire alarm interface voltage with fire alarm contractor prior to ordering. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #8: Specification Section 265100,265600 ‐ Lighting Comments: a. Fixture C2, C2E: Provide with MWD distribution. b. Fixture B2: Provide with chain hang kit c. Fixture L1, L2: color shall be selected by Architect. Provide chip samples for selection by Architect. d. Fixture X2: Provide with DA chevron arrangement. e. Occupancy sensor package is duplicated in this section. Remove product data from this section and use comments listed under the 262726 for comments on the package. Review Status: Reviewed as noted. No re‐submittal required. END OF REVIEW Page 3 TRANSMITTAL 5311 Coffeen Avenue P.O. Box Drawer S Sheridan, WY 82801 307-745-4866 307-745-4867 (fax) PROJECT: TO: ATTN: Ph/Fax: No. 15JW020-0044 DATE: 07/27/2015 SCSD2-SHS Locker Room Addition/Renovation TSP Inc One South Scott St Sherdian WY 82801 RE: 260000-Electrical William (Bill) Goodman 307-672-6496 JOB: 307-672-7487 WE ARE SENDING: SUBMITTED FOR: 15JW020 ACTION TAKEN: Shop Drawings Approval Approved as Submitted Letter Your Use Approved as Noted Prints As Requested Returned After Loan Change Order Review and Comment Resubmit Submit Plans SENT VIA: Samples Returned Specifications / Product Data Attached Returned for Corrections Other: Separate Cover Via: Due Date: 08/10/2015 NOTES: Item Package Code Submittal 260000 262913 Rev. Copies Date 1 07/27/2015 Description Status Controllers Submitted For Review CC: Comments noted thus: Signed: Clint Moseley SHERIDAN HIGH SCHOOL LOCKER ROOM PAGES 3-7 & 3-13—TILE OR SHRINK PAGE TO FIT WHEN PRINTING 30 AMP FUSED DISCONNECT Table of Contents Section 3 Safety Switches General Duty General Duty Fusible & Not Fusible 3-2 Application Data and Dimensions 3-3 Standards: • UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875. • NEMA Standards Publication KS1. Enclosed Switches. Light Duty Fusible 3-2 Application Data and Dimensions 3-3 Standards: • UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875. • NEMA Standards Publication KS1. Enclosed Switches. Heavy Duty Fusible 3-4 Not Fusible 3-6 Type 316 Enclosure Accessories Application Data and Dimensions 3-7 3-9 3-12 Standards: • UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875 and E154828. • NEMA Standards Publication KS1. Enclosed Switches. Double Throw Heavy Duty Fusible and Not Fusible 3-14 Application Data 3-17 Dimensions 3-18 Accessories 3-20 Standards: • UL 98 Enclosed and Dead Front Switches. UL Listed under File E2875 (unless otherwise noted). • NEMA Standards Publication KS1 Enclosed Switches (applies to Type DT and DTU series F only). 9/21/04 Double Throw 9/21/04 3-1 SAFETY SWITCHES Special Application Enclosures 3 Light Duty Heavy Duty Safety Switches 240 Volt Class 3110 www.SquareD.com For the most up-to-date information Visible blade heavy duty safety switches are designed for application where maximum performance and continuity of service are required. All heavy duty safety switches feature quick-make, quick-break operating mechanism, a dual cover interlock and a color coded indicator handle. They are suitable for use as service equipment when equipped with a field or factory installed neutral assembly or equipment grounding kit, unless a 600Y/347 V or 480 Y/277 V, 1000 A or greater, solidly grounded WYE system is used, per NEC 215-10. Heavy duty safety switches are UL Listed (except as noted), File E2875 & 154828 and meet or exceed the NEMA Standard KS1. For UL Listed short circuit current ratings, see page 3-6. NEMA 1 NEMA 3R NEMA 4, 4X and 5 Stainless Steel NEMA 12 240 Volt—Single Throw Fusible System Amps NEMA 1 Indoor 3 SAFETY SWITCHES Cat. No. Price NEMA 3R Rainproof (Bolt-on Hubs, page 3-9) Cat. No. Price 2 Wire (2 Blades and Fuseholders)—240 Vac, 250 Vdc 30 30 Use 3 Wire Devices 60 For 2 Wire Applications 100 200 400 H225 $1819. H225R $ 2589. 600 H226 3616. H226R 4854. 800 H227 5639. H227Rf 7655. 1200 H228 7788. H228Rf 10324. 3 Wire (2 Blades and Fuseholders, 1 Neutral)—240 Vac, 250 Vdc 30 H221N $ 157. H221NRB $ 298. 60 H222N 314. H222NRB 561. 100 H223N 477. H223NRB 724. 200 H224N 859. H224NRB 1041. 400 H225N 2061. H225NR 2830. 600 H226N 3879. H226NR 5118. 800 H227N 6711. H227NRf 8144. 1200 H228N 8281. H228NRf 11110. 3 Wire (3 Blades and Fuseholders)—240 Vac, 250 Vdc 30 Use 4 Wire Devices 60 For 3 Wire Applications 100 200 400 H325 $2283. H325R $ 2650. 600 H326 4113. H326R 5524. 800 H327 7637. H327Rf 9899. 1200 H328 9678. H328Rf 12485. 4 Wire (3 Blades and Fuseholders, 1 Neutral)—240 Vac, 250 Vdc 30 H321N $ 209. H321NRB $ 370. 60 H322N 352. H322NRB 594. 100 H323N 561. H323NRB 852. 200 H324N 967. H324NRB 1165. 400 H325N 2525. H325NR 2881. 600 H326N 4346. H326NR 5748. 800 H327N 8126. H327NRf 10375. 1200 H328N 10209. H328NRf 13139. 4 Wire (4 Blades and Fuseholders) 30 60 100 200 400 600 a b c d e f g NEMA 4, 4X, 5, a 304 Stainless Steel (for 316 stainless, see page 3-7) Dusttight, Watertight, Corrosion Resistant (Watertight Hubs, page 3-9) Cat. No. H221DS – H222DS H223DS H224DS H225DS H226DS – – Price $ 1298. – 1558. 3396. 4640. 9654. 13848. – – Horsepower Ratings b NEMA 12K With Knockouts (Watertight Hubs, page 3-9) NEMA 12, 3Rc Without Knockouts (Watertight Hubs, page 3-9) Cat. No. Price Cat. No. H221A – – H223A H224A – – – – $ 336. – – 672. 1158. – – – – H221AWK H2212AWK e H222AWK H223AWK H224AWK H225AWK H226AWK H227AWK H228AWK $ 9858. 14054. – – H321DS H322DS H323DS H324DS H325DS H326DS – – $ 1366. 1688. 3564. 4997. 9974. 14266. – – – – – – H321A H322A H323A H324A – – – – – – – – $ 426. 609. 941. 1360. – – – – 1Ø 3Ø 315. 392. 431. 632. 1095. 2775. 4362. 6883. 10543. 1 1 3 7 15 – – 50 50 3 d – 7 d 15 d 25 d – 75 d – – H225NAWK H226NAWK H227NAWK H228NAWK $ 2869. 4624. 8225. 11456. 1 3 7 15 – – 50 50 3 7 15 25 50 75 H321AWK H322AWK H323AWK H324AWK H325AWK H326AWK H327AWK H328AWK $ $ $10214. 14506. – – – – – – – – – – H325NAWK H326NAWK H327NAWK H328NAWK d d d d d d – – Max. (Using Dual Element, Time Delay Fuses) 1Ø 250 Vdc g 3Ø 3 3 10 15 – – – 50 50 7 d – 15 d 30 d 60 d – 200 d – – 5 5 10 20 40 50 50 50 50 3 10 15 – – – 50 50 7 15 30 60 125 200 d d d d d d – – 5 10 20 40 50 50 50 50 403. 576. 887. 1284. 2835. 4910. 9685. 11633. 1 3 7 15 – – 50 50 3 7 15 25 50 75 100 100 3 10 15 – – – 50 50 7 15 30 60 125 200 250 250 5 10 20 40 50 50 50 50 $ 3090. 5171. 10586. 13343. 1 3 7 15 – – 50 50 3 7 15 25 50 75 100 100 3 10 15 – – – 50 50 7 15 30 60 125 200 250 250 5 10 20 40 50 50 50 50 Use 3 Wire Devices, Field Installable Solid Neutral Assemblies Order Separately. See page 3-10 H325NDS H326NDS – – Std. (Using Fast Acting, One Time Fuses) Price Use 2 Wire Devices, Field Installable Solid Neutral Assemblies Order Separately. See page 3-10 H225NDS H226NDS – – 240 Vac Use 600 Vac Devices. See page 3-5. Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. For NEMA 3R applications, remove drain screw from bottom endwall. Refer to page 6-35 for additional motor application data. The starting current of motors of more than standard horsepower may require the use of fuses with appropriate time delay characteristics. Also suitable for NEMA 3R application by removing drain screw from bottom endwall. For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors. 60 ampere switch with 30 ampere fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks. Suitable for NEMA 5 applications with drain screw installed. For switching DC, use two switching poles. Dimensions NEMA 1 and 3R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-12 NEMA 4, 4X and 5 Stainless and NEMA 12 . . . . . . . . . . . . . . .page 3-13 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3-9 through 3-11 For additional information, reference Catalog #3100CT9801. DE1 3-4 9/21/04 Discount Schedule © 2004 Schneider Electric All Rights Reserved 9/21/04 Heavy Duty Safety Switches 600 Volt Class 3110 www.SquareD.com For the most up-to-date information 600 Volts—Single Throw Fusible Amps NEMA 12K With Knockouts (Watertight Hubs, page 3-9) NEMA 12, 3Rc Without Knockouts (Watertight Hubs, page 3-9) Cat. No. Price Cat. No. Price Cat. No. Price Cat. No. Price Cat. No. 2 Wire (2 Blades and Fuseholders)—600 Vac, 600 Vdc 30 Use 3 Wire Devices 60 For 2 Wire Applications 100 200 400 H265 $ 2804. H265R $ 3616. H265DS $ 9974. – – H265AWK 600 H266 4435. H266R 7124. H266DS 14266. – – H266AWK 800 H267 6910. H267Rh 10923. – – – – H267AWK 1200 H268 9713. H268Rh 11994. – – – – H268AWK 3 Wire (3 Blades and Fuseholders)—600 Vac, 600 Vdc e 30 H361 $ 352. H361RB $ 599. H361DS $ 1680. H361A $ 676. H361AWK 30 H361-2g 411. H3612RBg 699. – – H361-2A g 690. H3612AWKg 60 H362 425. H362RB 703. H362DS 1847. H362A 698. H362AWK 100 H363 792. H363RB 1096. H363DS 3662. H363A 1084. H363AWK 200 H364 1138. H364RB 1506. H364DS 5123. H364A 1696. H364AWK 400 H365 3034. H365R 3688. H365DS 10214. – – H365AWK 600 H366 5099. H366R 7266. H366DS 14056. – – H366AWK 800 H367 8879. H367Rh 11000. – – – – H367AWK 1200 H368 11671. H368Rh 13339. – – – – H368AWK 4 Wire (3 Blades and Fuseholders, 1 Neutral)—600 Vac, 600 Vdce 30 H361N $ 411. H361NRB $ 657. Use 3 Wire Devices Field Installable Solid Neutral 60 H362N 473. H362NRB 756. Assemblies. Order Separately. See page 3-10 100 H363N 852. H363NRB 1158. 200 H364N 1246. H364NRB 1605. H364NDS $ 5247. H364NA $ 1810. H364NAWK 400 H365N 3265. H365NR 3843. H365NDS 10445. – – H365NAWK 600 H366N 5346. H366NR 7369. H366NDS 14748. – – H366NAWK 800 H367N 9362. H367NRh 11470. – – – – H367NAWK H368NAWK 1200 H368N 12076. H368NRh 13995. – – – – 4 Wire (4 Blades and Fuseholders)—600 Vac, 600 Vdci 30 H461 $ 609. – – H461DS $ 1958. – – H461AWK 60 H462 710. – – H462DS 2046. – – H462AWK 100 H463 1185. – – H463DS 5563. – – H463AWK 200 H464 1971. – – H464DS 8397. – – H464AWK 400 H465f 4140. – – – – – – H465AWK 600 H466f 6736. – – – – – – – 6 Wire (6 Blades and Fuseholders)—600 Vac i 100 – – – – H663DS $17309. – – H663AWK 200 a b c d e f g h i – – – – H664DS 23595. – – H664AWK Price Horsepower Ratingsb 480 Vac 600 Vac Max. Std. Max. Std. (Using (Using (Using (Using dc Dual Fast Dual Fast e Acting, Element, Acting, Element, Time One Time One Time Delay Time Delay Fuses) Fuses) Fuses) Fuses) 3Ø 3Ø 3Ø 3Ø 250 600 – – – – $ 3350. 100 d 4894. 150 d 10184. – 12029. – $ 637. 651. 656. 1026. 1600. 3641. 6135. 10901. 13137. $ 1705. 3882. 6400. 11502. 13880. $ 743. 838. 1288. 2148. 4538. – $ 3408. 8148. 5 5 15 25 50 100 150 200 200 – – – – 250 d 400 d – – – – – – – – – – – – – – – – – – – – – – 50 50 50 50 – – – – 50 50 50 50 15 15 30 60 125 250 400 500 500 7 7 15 30 60 125 200 250 250 20 20 50 75 150 350 500 500 500 5 – – – 40 50 50 50 50 15 15 30 50 50 50 50 50 50 5 15 7 20 – 15 30 15 50 – 25 60 30 75 – 50 125 60 150 40 100 250 125 350 50 150 400 200 500 50 200 500 250 500 50 200 500 250 500 50 2Ø 2Ø 2Ø 2Ø 7 20 10 25 5 15 40 20 50 10 25 50 30 75 20 50 – 50 – 40 – – – – – – – – – – 3Ø 3Ø 3Ø 3Ø 25 60 30 75 – For applications requiring motor disconnect capability, use electrical interlock. Refer to page 3-9. 15 30 50 50 50 50 50 50 15 30 30 50 – – – Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. Refer to page 6-35 for additional motor application data. The starting current of motors of more than standard horsepower may require the use of fuses with appropriate time delay characteristics. Also suitable for NEMA 3R application by removing drain screw from bottom endwall. For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors. On 3-Pole devices, use two outside poles for switching DC. 600 Vac only. 60 ampere switch with 30 ampere fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks. Suitable for NEMA 5 applications with drain screw installed. Not suitable for use as service equipment. Class J Fuse Provisions: Fusible Square D 30 through 600 ampere heavy duty safety switches accept Class H fuses as standard. With Class H fuses installed, the switch is UL Listed for use on systems with up to 10,000 RMS symmetrical amperes available fault current. Provisions for installing Class J fuses are included in 30 through 400 ampere 600 Volt, and 100 through 400 ampere 240 Volt, fusible heavy duty safety switches. Conversion to Class J fuse spacing requires relocating the load side fuse base assembly from the standard Class H fuse location to an alternate position as marked in the enclosure. With Class J fuses installed, the switch is UL Listed for use on systems with up to 200,000 RMS symmetrical amperes available fault current. Switches rated 600 amperes, 240 or 600 Volt, require the addition of an adapter kit, H600J at $304. One kit per 3-pole switch. Class R Fuse Provisions: Fusible Square D 30 through 600 ampere heavy duty safety switches will accept Class R fuses as standard. A field installable rejection kit is available which, when installed, rejects all but Class R fuses. With the installation of the rejection kit and Class R fuses, the switch is UL Listed for use on systems with up to 200,000 RMS symmetrical amperes available fault current. See Class R fuse kits on page 3-9. 3 Class H Fuse Provisions: Class L Fuse Provisions: Fusible 800 A and 1200 A safety switches use Class L bolt-in fuses and are rated for use on systems with up to 200,000 RMS symmetrical amperes at 600 Vac maximum. 1200 A switches accept class L fuses from 601–1200 A, 800 A switches accept class L fuses from 601–800 A. Dimensions NEMA 1 and 3R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-12 NEMA 4, 4X and 5 Stainless and NEMA 12 . . . . . . . . . . . . . . . . . page 3-13 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3-9 through 3-11 For additional information, reference Catalog #3100CT9801. © 2004 Schneider Electric All Rights Reserved 9/21/04 9/21/04 DE1 Discount Schedule SAFETY SWITCHES System NEMA 3R Rainproof (Bolt-on Hubs, page 3-9) NEMA 1 Indoor NEMA 4, 4X, 5a 304 Stainless Steel (for 316 stainless, see page 3-7) Dusttight, Watertight, Corrosion Resistant (Watertight Hubs, page 3-9) 3-5 Bussmann® Fusetron FRS-R ® Dual-Element, Time-Delay Fuses Class RK5 – 600 Volt Dimensional Data ± ± ⁄Ω¡ºA to 30A ± ± 35A to 60A Catalog Symbol: FRS-R Dual-Element, Time-Delay – 10 second (minimum) at 500% rated current Current-Limiting Ampere Rating: ⁄Ω¡º to 60A Voltage Rating: 600Vac (or less) Interrupting Rating: 200,000A RMS Sym. dc Ratings (20,000AIC @ 250Vdc) Agency Information: UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273 CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787 Catalog Numbers FRS-R-⁄Ω¡º FRS-R-1°Ω¡º FRS-R-8 FRS-R-⁄Ω• FRS-R-2 FRS-R-9 FRS-R-⁄fiΩ¡ºº FRS-R-2⁄Ω¢ FRS-R-10 FRS-R-¤Ω¡º FRS-R-2⁄Ω™ FRS-R-12 FRS-R-⁄Ω¢ FRS-R-2°Ω¡º FRS-R-15 FRS-R-‹Ω¡º FRS-R-3 FRS-R-17⁄Ω™ FRS-R-›Ω¡º FRS-R-3¤Ω¡º FRS-R-20 FRS-R-⁄Ω™ FRS-R-3⁄Ω™ FRS-R-25 FRS-R-flΩ¡º FRS-R-4 FRS-R-30 FRS-R-°Ω¡º FRS-R-4⁄Ω™ FRS-R-35 FRS-R-1 FRS-R-5 FRS-R-40 FRS-R-1⁄Ω• FRS-R-5flΩ¡º FRS-R-45 FRS-R-1⁄Ω¢ FRS-R-6 FRS-R-50 FRS-R-1›Ω¡º FRS-R-6⁄Ω¢ FRS-R-60 FRS-R-1⁄Ω™ FRS-R-7 — FRS-R-1flΩ¡º FRS-R-7⁄Ω™ — General Information: • Provides motor overload, ground fault and short-circuit protection. When used in circuits subject to surge currents such as those caused by motors, transformers and other inductive components, these fuses can be sized close to full-load amperes to give maximum overcurrent protection. • Permits the use of smaller and less costly switches. The timedelay feature makes it possible to use fuse ampere ratings which are much smaller than those of non-time-delay fuses. Considerable cost saving occurs by permitting the use of smaller size switches, panels and fuses themselves. • Provides a higher degree of short-circuit protection (greater current-limitation) in circuits in which surge currents or temporary overloads occur. • Helps protect motors against burnout from overloads. • Gives motor running back-up protection to motors without extra costs. • Helps protect motors against burnout from single phasing on three phase systems. • Simplifies and improves blackout prevention (selective coordination). • Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high-performance, short-circuit and overload protection. • The overload element provides protection against low level overcurrent of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of ten seconds. Fuse Reducers For Class R Fuses Equipment Fuse Clips 60A 100A 200A Desired Fuse (Case) Size Catalog Number (Pairs) 600V 30A No. 663-R 30A No. 216-R 60A No. 616-R 60A No. 626-R Recommended fuseblocks for Class R 600V fuses See Data Sheet: 1111 Carton Quantity and Weight Ampere Ratings ⁄Ω¡º-60A Weight* Carton Qty. Lbs. Kg. ⁄Ω¡º–15 10 0.40 0.181 17.5–30 10 0.50 0.277 35-60 10 3.10 1.406 *Weight per carton. CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact Bussmann Application Engineering at 314-527-1270 for more information. $ Form No. FRS-R 1/10-60 Page 1 of 2 Data Sheet: 1017 Bussmann® Fusetron FRS-R ® Dual-Element, Time-Delay Fuses Class RK5 – 600 Volt ⁄Ω¡º-60A .1 .15 300 AMPERE RATING 60A 30A 300 AMPERE RATING 15A .2 .3 .4 .5 .6 .8 1 1.25 1.6 2 2.5 3.2 4 5 6.25 8 10 12 Time-Current Characteristic Curves–Average Melt 100 100 10 1 TIME IN SECONDS TIME IN SECONDS 10 .1 1 1,000 100 10 1 .1 .01 CURRENT IN AMPERES .1 60 30,000 10,000 20 .01 1,000 100,000 100 B 400,000 CURRENT IN AMPERES 30 10,000 15 200,000 1,000 1,000 100,000 A 10,000 INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPERES AMPERE RATING Current-Limitation Curves PROSPECTIVE SHORT-CIRCUIT CURRENT SYMMETRICAL RMS AMPERES The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. $ Form No. FRS-R 1/10-60 Page 2 of 2 Data Sheet: 1017 Technical Data 1145 Effective July 2014 Supersedes June 2012 Quik-Spec Power Module Switch SHERIDAN HIGH SCHOOL LOCKER ROOM ELEVATOR DISCONNECT All-in-one elevator disconnect Standard features: 30-400 amp 600Vac 3-phase fused power switch 200kA RMS short-circuit current rating Shunt trip 120V Fire safety interface relay Fire alarm voltage monitoring relay (to monitor shunt trip voltage) Ground lug Class J fuse mounting only1 Mechanically interlocked auxiliary contacts for hydraulic elevators with battery backup (5 amp 120Vac rated) Optional features: Control power transformer with fuses and blocks Key to test switch Pilot light – “ON” Isolated neutral lug2 NEMA 3R, 4, and 12 enclosures available For added protection, use the Bussmann SAMI™ fuse covers to improve maintenance personnel protection [OSHA 1910.335(A)(2)(ii)]3 Agency information: Product description: The Quik-Spec™ Power Module Switch is an all-in-one elevator disconnect switch available in configurations to meet virtually any single elevator shutdown and disconnect requirement. UL 98 enclosed and dead-front switch - Guide WIAX, WIAX7 (Canada), File E182262 cULus, NEMA 1, UL 50, listed enclosure cUL per Canadian Standards C22.2, No. 0-M91-CAN/ CSA C22.2, No. 4-M89 enclosed switch U.B.C. and C.B.C. Seismic Qualified, and I.B.C. Approved 1Class J fuses not included. 2Oversized 200% rated neutral option available where required by excessive non-linear loads. 3Covers available up to 100A. Quik-Spec Power Module Switch All-in-one elevator disconnect Technical Data 1145 Effective July 2014 Quik-Spec Power Module Switch catalog numbering system T48 1 PS Prefix PS = Power Module Switch R1 G K N1 Control Transformer* Key Test Switch (Optional) Neutral Lug (Optional) T20 = 208V T24 = 240V T48 = 480V T60 = 600V K = Key N6 = 30-60A N1 = 100A N2 = 200A N4 = 400A Amp Rating 3 = 30A 6 = 60A 1 = 100A 2 = 200A 4 = 400A H 29.6” 29.6” 29.6” 32.6” 54.6” W 17.3” 17.3” 17.3” 21.3” 26.5” Auxiliary Contacts (3PDT, 10A, 12V) R1 = 120Vac Coil R2 = 24Vdc Coil G = Green R = Red W = White B = 2 NO/NC D1 6.9” 6.9” 6.9” 7” 7.5” D2 11.2” 11.2” 11.2” 11.3” 12.7” Lug size #14 - #8 Al or Cu #14 - #2 Al or Cu #8 - 1/0 Al or Cu #6 - 250 kcmil Al or Cu (2) 1/0 - 500 kcmil Al or Cu A 28.4” 28.4” 28.4” 31.1” 53.3” PS4 dimensions shown for TYPE 1 only. Contact Bussmann for availability of other types of enclosures. 1 B D2 A H D1 2 EATON www.eaton.com To monitor shunt trip voltage F1 = 1-Pole Relay F3 = 3-Pole Relay** Pilot Light ON (Optional) Dimensions and Lug Data W B 10” 10” 10” 17” 22” U Fire Alarm Voltage Monitoring Relay (Optional) Fire Safety Interface Relay * 100VA with primary and secondary fusing (120V secondary). ** For use only with R1 option. † Type 1 standard, no suffix designator required. Catalog number Amps PS3 30 PS6 60 PS1 100 PS2 200 PS41 400 F1 B Enclosure † = Type 1 U = Type 3R Z = Type 12 Y = Type 4 Quik-Spec Power Module Switch All-in-one elevator disconnect Technical Data 1145 Effective July 2014 Maximum horsepower rating of switch – sizing based on motor type and time-delay fuses Voltage/Phase 208Vac/3-Phase 240Vac/3-Phase 480Vac/3-Phase 600Vac/3-Phase 30A PS3 5 5 10 15 Switch Amp Rating 60A 100A 200A 400A PS6 PS1 PS2 PS4 10 15 40 75 10 20 40 75 25 40 75 150 30 50 100 200 The above table can be used for estimating switch size for motor loads based upon the motor horsepower. For general applications, excluding wound rotor and DC motors, NEC® 430.52 allows sizing at 175% of motor full load amps or the next standard size per NEC® 240.6. If sizing at 175% will not allow the motor to start, NEC® 430.52 will allow the fuses to be sized up to 225% of motor full load amps or the next size down. NOTE: In sizing the fuses, the motor FLA is per NEC® Table 430.250, not per nameplate information. Inrush currents of motors may vary, consult motor manufacturer data for correct sizing. On elevator applications, motor load plus auxiliary loads need to be considered. Follow elevator manufacturer’s recommendation for correct fuse sizing. 3 EATON www.eaton.com Standard shunt trip ratings: 30-100A, 200A & 400A Voltage 120Vac, 60Hz Max inrush 4 amps Will handle up to 447VA inrush. 1 Max ontime1 1.5 cycles Momentary inrush 140VA Technical Data 1145 Effective July 2014 4 EATON www.eaton.com Quik-Spec Power Module Switch All-in-one elevator disconnect Technical Data 1145 Effective July 2014 5 EATON www.eaton.com Quik-Spec Power Module Switch All-in-one elevator disconnect Quik-Spec Power Module Switch All-in-one elevator disconnect Technical Data 1145 Effective July 2014 The only controlled copy of this data sheet is the electronic read-only version located on the Bussmann network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton’s Bussmann Business 114 Old State Road Ellisville, MO 63021 United States www.bussmann.com © 2014 Eaton All Rights Reserved Publication No. 1145 - BU-SB14455 July 2014 Eaton is a registered trademark. All other trademarks are property of their respective owners.