2040 Harnash Boulevard Billings, Montana 59102 406‐245‐0136 (phone) 406‐245‐2084 (fax) SUBMITTAL
REVIEW
To: Bill Goodman, TSP, Inc. From: Terry Jiracek Date In: 07/27/2015 Job: SCSD#2 – HS Locker Room Addition/Remodel Number of Copies Returned: One (1) PDF Date Reviewed: 07/28/2015 Job 14SH4331 Retained: One (1) PDF Submittal Title: spec 260519,260529,260533,262416,262726,262813,262913,265100 & 265600 ‐ Review #001 ASSOCIATED CONSTRUCTION ENGINEERING, INC.
X Reviewed as noted ‐ No re‐submittal required Revise & Resubmit per comments No Exception Taken, Where Noted Reviewed By: Terry Jiracek Date: 07/28/2015 Review is for conformance with design concept & compliance with contract documents only. Contractor shall check & verify all quantities, field measurements & shall be responsible for all errors in shop drawings. Contractor shall be responsible for deviations from contract documents unless he has called attention to such deviation and secured written approval. All in accordance with the general conditions. Submittal Item #1: Specification Section 260519 – Conductors & Cables Comments: a.
Mc cable shall only be utilized for light fixture whips in project. All other uses in project for cable is prohibited. b.
All conductors’s #12 and smaller shall be solid. #10 and larger shall be stranded per specifications. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #2: Specification Section 260529 – Hangers & Supports Comments: Page 1 a.
No Comment, accepted as submitted Review Status: Reviewed, no exception taken. Submittal Item #3: Specification Section 260533 – Raceway & Boxes Comments: a.
Shop drawings contain many sheets of extra information on products that does not apply to project. Example is back boxes that accept NM cable, which is not an approved cable on the project. Only provide information that is applicable to project. b.
Floor box submittal shall be purged of all information that does not apply to project when O&M’s are compiled. Example: there are no 6 gang boxes on the project. c.
Floor box data insert bracket shall be verified for compliance with owners data system/ district standard jacks prior to ordering. d.
The use of surface mounted Hubbell raceway shall only be done when approved by the Architect. All locations of desired use shall be reviewed and approved by Architect. Plans indicate the required locations of surface raceway in finished areas, which will be done with EMT. e.
Architect shall select surface raceway device finish color between Ivory or White, coordinate prior to ordering. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #4: Specification Section 262416 ‐ Panelboards Comments: a.
Lead EC on project shall verify lug feed location as top or bottom. b.
Panel L‐B1H3 shall contain a 100A/3p breaker in place of the 40A/3P per PR#3. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #5: Specification Section 262726 – Wiring Devices Comments: a.
Verify required wiring device finish color with Architect prior to ordering. b.
There is no OS7 in the project. Remove cut sheet from submittal prior to compiling the O&M. Review Status: Reviewed as noted. No re‐submittal required. Page 2 Submittal Item #6: Specification Section 262813 ‐ Fuses Comments: a.
Coordinate exact fuse size required with equipment served prior to ordering. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #7: Specification Section 262913 ‐ Controllers Comments: a.
Verify the required fire alarm interface voltage with fire alarm contractor prior to ordering. Review Status: Reviewed as noted. No re‐submittal required. Submittal Item #8: Specification Section 265100,265600 ‐ Lighting Comments: a.
Fixture C2, C2E: Provide with MWD distribution. b.
Fixture B2: Provide with chain hang kit c.
Fixture L1, L2: color shall be selected by Architect. Provide chip samples for selection by Architect. d.
Fixture X2: Provide with DA chevron arrangement. e.
Occupancy sensor package is duplicated in this section. Remove product data from this section and use comments listed under the 262726 for comments on the package. Review Status: Reviewed as noted. No re‐submittal required. END OF REVIEW Page 3 TRANSMITTAL
5311 Coffeen Avenue
P.O. Box Drawer S
Sheridan, WY 82801
307-745-4866
307-745-4867 (fax)
PROJECT:
TO:
ATTN:
Ph/Fax:
No. 15JW020-0044
DATE: 07/27/2015
SCSD2-SHS Locker Room Addition/Renovation
TSP Inc
One South Scott St
Sherdian WY 82801
RE:
260000-Electrical
William (Bill) Goodman
307-672-6496
JOB:
307-672-7487
WE ARE SENDING:
SUBMITTED FOR:
15JW020
ACTION TAKEN:
Shop Drawings
Approval
Approved as Submitted
Letter
Your Use
Approved as Noted
Prints
As Requested
Returned After Loan
Change Order
Review and Comment
Resubmit
Submit
Plans
SENT VIA:
Samples
Returned
Specifications / Product Data
Attached
Returned for Corrections
Other:
Separate Cover Via:
Due Date: 08/10/2015
NOTES:
Item
Package
Code
Submittal
260000
262913
Rev. Copies Date
1
07/27/2015
Description
Status
Controllers
Submitted For
Review
CC:
Comments noted thus:
Signed:
Clint Moseley
SHERIDAN HIGH SCHOOL
LOCKER ROOM
PAGES 3-7 & 3-13—TILE OR SHRINK PAGE TO FIT WHEN PRINTING 30 AMP FUSED DISCONNECT
Table of Contents
Section 3
Safety Switches
General Duty
General Duty
Fusible & Not Fusible
3-2
Application Data and Dimensions
3-3
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under File E2875.
• NEMA Standards Publication KS1. Enclosed Switches.
Light Duty
Fusible
3-2
Application Data and Dimensions
3-3
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under File E2875.
• NEMA Standards Publication KS1. Enclosed Switches.
Heavy Duty
Fusible
3-4
Not Fusible
3-6
Type 316
Enclosure
Accessories
Application Data and Dimensions
3-7
3-9
3-12
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under File E2875 and E154828.
• NEMA Standards Publication KS1. Enclosed Switches.
Double Throw
Heavy Duty
Fusible and Not Fusible
3-14
Application Data
3-17
Dimensions
3-18
Accessories
3-20
Standards:
• UL 98 Enclosed and Dead Front Switches.
UL Listed under File E2875 (unless otherwise noted).
• NEMA Standards Publication KS1 Enclosed Switches (applies
to Type DT and DTU series F only).
9/21/04
Double Throw
9/21/04
3-1
SAFETY SWITCHES
Special Application Enclosures
3
Light Duty
Heavy Duty Safety Switches
240 Volt
Class 3110
www.SquareD.com
For the most up-to-date information
Visible blade heavy duty safety switches are designed for application
where maximum performance and continuity of service are required. All
heavy duty safety switches feature quick-make, quick-break operating
mechanism, a dual cover interlock and a color coded indicator handle.
They are suitable for use as service equipment when equipped with a field
or factory installed neutral assembly or equipment grounding kit, unless a
600Y/347 V or 480 Y/277 V, 1000 A or greater, solidly grounded WYE
system is used, per NEC 215-10. Heavy duty safety switches are UL
Listed (except as noted), File E2875 & 154828 and meet or exceed the
NEMA Standard KS1. For UL Listed short circuit current ratings, see
page 3-6.
NEMA 1
NEMA 3R
NEMA 4, 4X and 5
Stainless Steel
NEMA 12
240 Volt—Single Throw Fusible
System
Amps
NEMA 1
Indoor
3
SAFETY SWITCHES
Cat. No.
Price
NEMA 3R
Rainproof
(Bolt-on Hubs,
page 3-9)
Cat. No.
Price
2 Wire (2 Blades and Fuseholders)—240 Vac, 250 Vdc
30
30
Use 3 Wire Devices
60
For 2 Wire Applications
100
200
400
H225
$1819. H225R
$ 2589.
600
H226
3616. H226R
4854.
800
H227
5639. H227Rf
7655.
1200
H228
7788. H228Rf
10324.
3 Wire (2 Blades and Fuseholders, 1 Neutral)—240 Vac, 250 Vdc
30
H221N
$ 157. H221NRB
$ 298.
60
H222N
314. H222NRB
561.
100
H223N
477. H223NRB
724.
200
H224N
859. H224NRB
1041.
400
H225N
2061. H225NR
2830.
600
H226N
3879. H226NR
5118.
800
H227N
6711. H227NRf
8144.
1200
H228N
8281. H228NRf
11110.
3 Wire (3 Blades and Fuseholders)—240 Vac, 250 Vdc
30
Use 4 Wire Devices
60
For 3 Wire Applications
100
200
400
H325
$2283. H325R
$ 2650.
600
H326
4113. H326R
5524.
800
H327
7637. H327Rf
9899.
1200
H328
9678. H328Rf
12485.
4 Wire (3 Blades and Fuseholders, 1 Neutral)—240 Vac, 250 Vdc
30
H321N
$ 209. H321NRB
$ 370.
60
H322N
352. H322NRB
594.
100
H323N
561. H323NRB
852.
200
H324N
967. H324NRB
1165.
400
H325N
2525. H325NR
2881.
600
H326N
4346. H326NR
5748.
800
H327N
8126. H327NRf
10375.
1200
H328N
10209. H328NRf
13139.
4 Wire (4 Blades and Fuseholders)
30
60
100
200
400
600
a
b
c
d
e
f
g
NEMA
4, 4X, 5, a
304 Stainless Steel
(for 316 stainless,
see page 3-7)
Dusttight, Watertight,
Corrosion Resistant
(Watertight Hubs,
page 3-9)
Cat. No.
H221DS
–
H222DS
H223DS
H224DS
H225DS
H226DS
–
–
Price
$ 1298.
–
1558.
3396.
4640.
9654.
13848.
–
–
Horsepower Ratings b
NEMA 12K
With
Knockouts
(Watertight
Hubs,
page 3-9)
NEMA
12, 3Rc
Without
Knockouts
(Watertight
Hubs, page 3-9)
Cat. No.
Price
Cat. No.
H221A
–
–
H223A
H224A
–
–
–
–
$ 336.
–
–
672.
1158.
–
–
–
–
H221AWK
H2212AWK e
H222AWK
H223AWK
H224AWK
H225AWK
H226AWK
H227AWK
H228AWK
$ 9858.
14054.
–
–
H321DS
H322DS
H323DS
H324DS
H325DS
H326DS
–
–
$ 1366.
1688.
3564.
4997.
9974.
14266.
–
–
–
–
–
–
H321A
H322A
H323A
H324A
–
–
–
–
–
–
–
–
$ 426.
609.
941.
1360.
–
–
–
–
1Ø
3Ø
315.
392.
431.
632.
1095.
2775.
4362.
6883.
10543.
1
1
3
7
15
–
–
50
50
3 d
–
7 d
15 d
25 d
–
75 d
–
–
H225NAWK
H226NAWK
H227NAWK
H228NAWK
$ 2869.
4624.
8225.
11456.
1
3
7
15
–
–
50
50
3
7
15
25
50
75
H321AWK
H322AWK
H323AWK
H324AWK
H325AWK
H326AWK
H327AWK
H328AWK
$
$
$10214.
14506.
–
–
–
–
–
–
–
–
–
–
H325NAWK
H326NAWK
H327NAWK
H328NAWK
d
d
d
d
d
d
–
–
Max.
(Using Dual
Element, Time
Delay Fuses)
1Ø
250 Vdc
g
3Ø
3
3
10
15
–
–
–
50
50
7 d
–
15 d
30 d
60 d
–
200 d
–
–
5
5
10
20
40
50
50
50
50
3
10
15
–
–
–
50
50
7
15
30
60
125
200
d
d
d
d
d
d
–
–
5
10
20
40
50
50
50
50
403.
576.
887.
1284.
2835.
4910.
9685.
11633.
1
3
7
15
–
–
50
50
3
7
15
25
50
75
100
100
3
10
15
–
–
–
50
50
7
15
30
60
125
200
250
250
5
10
20
40
50
50
50
50
$ 3090.
5171.
10586.
13343.
1
3
7
15
–
–
50
50
3
7
15
25
50
75
100
100
3
10
15
–
–
–
50
50
7
15
30
60
125
200
250
250
5
10
20
40
50
50
50
50
Use 3 Wire Devices,
Field Installable Solid Neutral Assemblies
Order Separately. See page 3-10
H325NDS
H326NDS
–
–
Std.
(Using Fast
Acting,
One Time Fuses)
Price
Use 2 Wire Devices,
Field Installable Solid Neutral Assemblies
Order Separately. See page 3-10
H225NDS
H226NDS
–
–
240 Vac
Use 600 Vac Devices. See page 3-5.
Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12. For NEMA 3R applications, remove drain screw from bottom endwall.
Refer to page 6-35 for additional motor application data. The starting current of motors of more than standard horsepower may require the use of fuses with appropriate time delay characteristics.
Also suitable for NEMA 3R application by removing drain screw from bottom endwall.
For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors.
60 ampere switch with 30 ampere fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks.
Suitable for NEMA 5 applications with drain screw installed.
For switching DC, use two switching poles.
Dimensions NEMA 1 and 3R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-12
NEMA 4, 4X and 5 Stainless and NEMA 12 . . . . . . . . . . . . . . .page 3-13
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3-9 through 3-11
For additional information, reference Catalog #3100CT9801.
DE1
3-4
9/21/04
Discount
Schedule
© 2004 Schneider Electric
All Rights Reserved
9/21/04
Heavy Duty Safety Switches
600 Volt
Class 3110
www.SquareD.com
For the most up-to-date information
600 Volts—Single Throw Fusible
Amps
NEMA 12K
With Knockouts
(Watertight Hubs,
page 3-9)
NEMA 12, 3Rc
Without Knockouts
(Watertight Hubs,
page 3-9)
Cat. No. Price
Cat. No.
Price
Cat. No.
Price
Cat. No.
Price
Cat. No.
2 Wire (2 Blades and Fuseholders)—600 Vac, 600 Vdc
30
Use 3 Wire Devices
60
For 2 Wire Applications
100
200
400 H265
$ 2804. H265R
$ 3616. H265DS
$ 9974.
–
–
H265AWK
600 H266
4435. H266R
7124. H266DS
14266.
–
–
H266AWK
800 H267
6910. H267Rh
10923.
–
–
–
–
H267AWK
1200 H268
9713. H268Rh
11994.
–
–
–
–
H268AWK
3 Wire (3 Blades and Fuseholders)—600 Vac, 600 Vdc e
30 H361
$ 352. H361RB
$ 599. H361DS
$ 1680. H361A
$ 676. H361AWK
30 H361-2g
411. H3612RBg
699.
–
–
H361-2A g
690. H3612AWKg
60 H362
425. H362RB
703. H362DS
1847. H362A
698. H362AWK
100 H363
792. H363RB
1096. H363DS
3662. H363A
1084. H363AWK
200 H364
1138. H364RB
1506. H364DS
5123. H364A
1696. H364AWK
400 H365
3034. H365R
3688. H365DS
10214.
–
–
H365AWK
600 H366
5099. H366R
7266. H366DS
14056.
–
–
H366AWK
800 H367
8879. H367Rh
11000.
–
–
–
–
H367AWK
1200 H368
11671. H368Rh
13339.
–
–
–
–
H368AWK
4 Wire (3 Blades and Fuseholders, 1 Neutral)—600 Vac, 600 Vdce
30 H361N
$ 411. H361NRB $ 657.
Use 3 Wire Devices Field Installable Solid Neutral
60 H362N
473. H362NRB
756.
Assemblies. Order Separately. See page 3-10
100 H363N
852. H363NRB
1158.
200 H364N
1246. H364NRB
1605. H364NDS
$ 5247. H364NA
$ 1810. H364NAWK
400 H365N
3265. H365NR
3843. H365NDS
10445.
–
–
H365NAWK
600 H366N
5346. H366NR
7369. H366NDS
14748.
–
–
H366NAWK
800 H367N
9362. H367NRh
11470.
–
–
–
–
H367NAWK
H368NAWK
1200 H368N
12076. H368NRh
13995.
–
–
–
–
4 Wire (4 Blades and Fuseholders)—600 Vac, 600 Vdci
30 H461
$ 609.
–
–
H461DS
$ 1958.
–
–
H461AWK
60 H462
710.
–
–
H462DS
2046.
–
–
H462AWK
100 H463
1185.
–
–
H463DS
5563.
–
–
H463AWK
200 H464
1971.
–
–
H464DS
8397.
–
–
H464AWK
400 H465f
4140.
–
–
–
–
–
–
H465AWK
600 H466f
6736.
–
–
–
–
–
–
–
6 Wire (6 Blades and Fuseholders)—600 Vac i
100
–
–
–
–
H663DS
$17309.
–
–
H663AWK
200
a
b
c
d
e
f
g
h
i
–
–
–
–
H664DS
23595.
–
–
H664AWK
Price
Horsepower Ratingsb
480 Vac
600 Vac
Max.
Std.
Max.
Std.
(Using (Using (Using
(Using
dc
Dual
Fast
Dual
Fast
e
Acting, Element,
Acting, Element,
Time
One
Time
One Time Delay
Time
Delay
Fuses)
Fuses) Fuses) Fuses)
3Ø
3Ø
3Ø
3Ø
250 600
–
–
–
–
$ 3350. 100 d
4894. 150 d
10184.
–
12029.
–
$
637.
651.
656.
1026.
1600.
3641.
6135.
10901.
13137.
$ 1705.
3882.
6400.
11502.
13880.
$
743.
838.
1288.
2148.
4538.
–
$ 3408.
8148.
5
5
15
25
50
100
150
200
200
–
–
–
–
250 d
400 d
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
50
50
50
50
–
–
–
–
50
50
50
50
15
15
30
60
125
250
400
500
500
7
7
15
30
60
125
200
250
250
20
20
50
75
150
350
500
500
500
5
–
–
–
40
50
50
50
50
15
15
30
50
50
50
50
50
50
5
15
7
20
–
15
30
15
50
–
25
60
30
75
–
50
125
60
150
40
100
250
125
350
50
150
400
200
500
50
200
500
250
500
50
200
500
250
500
50
2Ø
2Ø
2Ø
2Ø
7
20
10
25
5
15
40
20
50
10
25
50
30
75
20
50
–
50
–
40
–
–
–
–
–
–
–
–
–
–
3Ø
3Ø
3Ø
3Ø
25
60
30
75
–
For applications requiring motor disconnect
capability, use electrical interlock.
Refer to page 3-9.
15
30
50
50
50
50
50
50
15
30
30
50
–
–
–
Complete rating is NEMA 3, 3R, 4, 4X, 5 and 12.
Refer to page 6-35 for additional motor application data. The starting current of motors of more than standard horsepower may require the use of fuses with appropriate time delay characteristics.
Also suitable for NEMA 3R application by removing drain screw from bottom endwall.
For corner grounded delta systems only and with neutral assembly installed. Use switching poles for ungrounded conductors.
On 3-Pole devices, use two outside poles for switching DC.
600 Vac only.
60 ampere switch with 30 ampere fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks.
Suitable for NEMA 5 applications with drain screw installed.
Not suitable for use as service equipment.
Class J Fuse Provisions:
Fusible Square D 30 through 600 ampere heavy duty safety switches
accept Class H fuses as standard. With Class H fuses installed, the
switch is UL Listed for use on systems with up to 10,000 RMS
symmetrical amperes available fault current.
Provisions for installing Class J fuses are included in 30 through 400
ampere 600 Volt, and 100 through 400 ampere 240 Volt, fusible heavy
duty safety switches. Conversion to Class J fuse spacing requires
relocating the load side fuse base assembly from the standard Class H
fuse location to an alternate position as marked in the enclosure. With
Class J fuses installed, the switch is UL Listed for use on systems with
up to 200,000 RMS symmetrical amperes available fault current.
Switches rated 600 amperes, 240 or 600 Volt, require the addition of an
adapter kit, H600J at $304. One kit per 3-pole switch.
Class R Fuse Provisions:
Fusible Square D 30 through 600 ampere heavy
duty safety switches will accept Class R fuses as
standard. A field installable rejection kit is
available which, when installed, rejects all but
Class R fuses. With the installation of the
rejection kit and Class R fuses, the switch is UL
Listed for use on systems with up to 200,000
RMS symmetrical amperes available fault
current. See Class R fuse kits on page 3-9.
3
Class H Fuse Provisions:
Class L Fuse Provisions:
Fusible 800 A and 1200 A safety switches use Class L bolt-in fuses and
are rated for use on systems with up to 200,000 RMS symmetrical
amperes at 600 Vac maximum. 1200 A switches accept class L fuses
from 601–1200 A, 800 A switches accept class L fuses from 601–800 A.
Dimensions NEMA 1 and 3R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-12
NEMA 4, 4X and 5 Stainless and NEMA 12 . . . . . . . . . . . . . . . . . page 3-13
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3-9 through 3-11
For additional information, reference Catalog #3100CT9801.
© 2004 Schneider Electric
All Rights Reserved
9/21/04
9/21/04
DE1
Discount
Schedule
SAFETY SWITCHES
System
NEMA 3R
Rainproof
(Bolt-on Hubs,
page 3-9)
NEMA 1
Indoor
NEMA 4, 4X, 5a
304 Stainless Steel
(for 316 stainless,
see page 3-7)
Dusttight, Watertight,
Corrosion Resistant
(Watertight Hubs,
page 3-9)
3-5
Bussmann®
Fusetron
FRS-R
®
Dual-Element, Time-Delay Fuses
Class RK5 – 600 Volt
Dimensional Data
±
±
⁄Ω¡ºA to 30A
±
±
35A to 60A
Catalog Symbol: FRS-R
Dual-Element, Time-Delay – 10 second (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: ⁄Ω¡º to 60A
Voltage Rating: 600Vac (or less)
Interrupting Rating: 200,000A RMS Sym.
dc Ratings (20,000AIC @ 250Vdc)
Agency Information:
UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers
FRS-R-⁄Ω¡º
FRS-R-1°Ω¡º
FRS-R-8
FRS-R-⁄Ω•
FRS-R-2
FRS-R-9
FRS-R-⁄fiΩ¡ºº
FRS-R-2⁄Ω¢
FRS-R-10
FRS-R-¤Ω¡º
FRS-R-2⁄Ω™
FRS-R-12
FRS-R-⁄Ω¢
FRS-R-2°Ω¡º
FRS-R-15
FRS-R-‹Ω¡º
FRS-R-3
FRS-R-17⁄Ω™
FRS-R-›Ω¡º
FRS-R-3¤Ω¡º
FRS-R-20
FRS-R-⁄Ω™
FRS-R-3⁄Ω™
FRS-R-25
FRS-R-flꭧ
FRS-R-4
FRS-R-30
FRS-R-°Ω¡º
FRS-R-4⁄Ω™
FRS-R-35
FRS-R-1
FRS-R-5
FRS-R-40
FRS-R-1⁄Ω•
FRS-R-5flꭧ
FRS-R-45
FRS-R-1⁄Ω¢
FRS-R-6
FRS-R-50
FRS-R-1›Ω¡º
FRS-R-6⁄Ω¢
FRS-R-60
FRS-R-1⁄Ω™
FRS-R-7
—
FRS-R-1flꭧ
FRS-R-7⁄Ω™
—
General Information:
• Provides motor overload, ground fault and short-circuit protection. When used in circuits subject to surge currents such
as those caused by motors, transformers and other inductive
components, these fuses can be sized close to full-load
amperes to give maximum overcurrent protection.
• Permits the use of smaller and less costly switches. The timedelay feature makes it possible to use fuse ampere ratings
which are much smaller than those of non-time-delay fuses.
Considerable cost saving occurs by permitting the use of
smaller size switches, panels and fuses themselves.
• Provides a higher degree of short-circuit protection (greater
current-limitation) in circuits in which surge currents or temporary overloads occur.
• Helps protect motors against burnout from overloads.
• Gives motor running back-up protection to motors without
extra costs.
• Helps protect motors against burnout from single phasing on
three phase systems.
• Simplifies and improves blackout prevention (selective
coordination).
• Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both
high-performance, short-circuit and overload protection.
• The overload element provides protection against low level
overcurrent of overloads and will hold an overload which is
five times greater than the ampere rating of the fuse for a
minimum of ten seconds.
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
60A
100A
200A
Desired
Fuse (Case)
Size
Catalog Number
(Pairs)
600V
30A
No. 663-R
30A
No. 216-R
60A
No. 616-R
60A
No. 626-R
Recommended fuseblocks for
Class R 600V fuses
See Data Sheet: 1111
Carton Quantity and Weight
Ampere
Ratings
⁄Ω¡º-60A
Weight*
Carton
Qty.
Lbs.
Kg.
⁄Ω¡º–15
10
0.40
0.181
17.5–30
10
0.50
0.277
35-60
10
3.10
1.406
*Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
$
Form No. FRS-R 1/10-60
Page 1 of 2
Data Sheet: 1017
Bussmann®
Fusetron
FRS-R
®
Dual-Element, Time-Delay Fuses
Class RK5 – 600 Volt
⁄Ω¡º-60A
.1
.15
300
AMPERE
RATING
60A
30A
300
AMPERE RATING
15A
.2
.3
.4
.5
.6 .8
1 1.25
1.6
2 2.5
3.2 4
5 6.25
8
10
12
Time-Current Characteristic Curves–Average Melt
100
100
10
1
TIME IN SECONDS
TIME IN SECONDS
10
.1
1
1,000
100
10
1
.1
.01
CURRENT IN AMPERES
.1
60
30,000
10,000
20
.01
1,000
100,000
100
B
400,000
CURRENT IN AMPERES
30
10,000
15
200,000
1,000
1,000
100,000
A
10,000
INSTANTANEOUS PEAK LET-THROUGH
CURRENT IN AMPERES
AMPERE
RATING
Current-Limitation Curves
PROSPECTIVE SHORT-CIRCUIT CURRENT
SYMMETRICAL RMS AMPERES
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
$
Form No. FRS-R 1/10-60
Page 2 of 2
Data Sheet: 1017
Technical Data 1145
Effective July 2014
Supersedes June 2012
Quik-Spec Power Module Switch
SHERIDAN HIGH SCHOOL LOCKER
ROOM
ELEVATOR DISCONNECT
All-in-one elevator disconnect
Standard features:
30-400 amp 600Vac 3-phase fused power
switch
200kA RMS short-circuit current rating
Shunt trip 120V
Fire safety interface relay
Fire alarm voltage monitoring relay (to monitor
shunt trip voltage)
Ground lug
Class J fuse mounting only1
Mechanically interlocked auxiliary contacts for
hydraulic elevators with battery backup (5 amp
120Vac rated)
Optional features:
Control power transformer with fuses and
blocks
Key to test switch
Pilot light – “ON”
Isolated neutral lug2
NEMA 3R, 4, and 12 enclosures available
For added protection, use the Bussmann
SAMI™ fuse covers to improve maintenance
personnel protection [OSHA 1910.335(A)(2)(ii)]3
Agency information:
Product description:
The Quik-Spec™ Power Module Switch is an
all-in-one elevator disconnect switch available in
configurations to meet virtually any single elevator
shutdown and disconnect requirement.
UL 98 enclosed and dead-front switch - Guide
WIAX, WIAX7 (Canada), File E182262
cULus, NEMA 1, UL 50, listed enclosure cUL
per Canadian Standards C22.2, No. 0-M91-CAN/
CSA C22.2, No. 4-M89 enclosed switch
U.B.C. and C.B.C. Seismic Qualified, and I.B.C.
Approved
1Class J fuses not included.
2Oversized 200% rated neutral option available where required by
excessive non-linear loads.
3Covers available up to 100A.
Quik-Spec Power Module Switch
All-in-one elevator disconnect
Technical Data 1145
Effective July 2014
Quik-Spec Power Module Switch catalog numbering system
T48
1
PS
Prefix
PS = Power
Module
Switch
R1
G
K
N1
Control
Transformer*
Key Test
Switch (Optional)
Neutral Lug
(Optional)
T20 = 208V
T24 = 240V
T48 = 480V
T60 = 600V
K = Key
N6 = 30-60A
N1 = 100A
N2 = 200A
N4 = 400A
Amp Rating
3 = 30A
6 = 60A
1 = 100A
2 = 200A
4 = 400A
H
29.6”
29.6”
29.6”
32.6”
54.6”
W
17.3”
17.3”
17.3”
21.3”
26.5”
Auxiliary
Contacts
(3PDT, 10A, 12V)
R1 = 120Vac Coil
R2 = 24Vdc Coil
G = Green
R = Red
W = White
B = 2 NO/NC
D1
6.9”
6.9”
6.9”
7”
7.5”
D2
11.2”
11.2”
11.2”
11.3”
12.7”
Lug size
#14 - #8 Al or Cu
#14 - #2 Al or Cu
#8 - 1/0 Al or Cu
#6 - 250 kcmil Al or Cu
(2) 1/0 - 500 kcmil Al or Cu
A
28.4”
28.4”
28.4”
31.1”
53.3”
PS4 dimensions shown for TYPE 1 only. Contact Bussmann for availability of other types of enclosures.
1
B
D2
A
H
D1
2
EATON www.eaton.com
To monitor shunt
trip voltage
F1 = 1-Pole Relay
F3 = 3-Pole Relay**
Pilot Light ON
(Optional)
Dimensions and Lug Data
W
B
10”
10”
10”
17”
22”
U
Fire Alarm Voltage
Monitoring Relay
(Optional)
Fire Safety
Interface Relay
* 100VA with primary and secondary fusing (120V secondary).
** For use only with R1 option.
† Type 1 standard, no suffix designator required.
Catalog
number Amps
PS3
30
PS6
60
PS1
100
PS2
200
PS41
400
F1
B
Enclosure
† = Type 1
U = Type 3R
Z = Type 12
Y = Type 4
Quik-Spec Power Module Switch
All-in-one elevator disconnect
Technical Data 1145
Effective July 2014
Maximum horsepower rating of switch – sizing based on
motor type and time-delay fuses
Voltage/Phase
208Vac/3-Phase
240Vac/3-Phase
480Vac/3-Phase
600Vac/3-Phase
30A
PS3
5
5
10
15
Switch Amp Rating
60A 100A 200A 400A
PS6 PS1 PS2
PS4
10
15
40
75
10
20
40
75
25
40
75
150
30
50
100
200
The above table can be used for estimating switch size for motor
loads based upon the motor horsepower. For general applications,
excluding wound rotor and DC motors, NEC® 430.52 allows sizing
at 175% of motor full load amps or the next standard size per NEC®
240.6. If sizing at 175% will not allow the motor to start, NEC®
430.52 will allow the fuses to be sized up to 225% of motor full load
amps or the next size down.
NOTE: In sizing the fuses, the motor FLA is per NEC® Table
430.250, not per nameplate information. Inrush currents
of motors may vary, consult motor manufacturer data for
correct sizing. On elevator applications, motor load plus
auxiliary loads need to be considered. Follow elevator
manufacturer’s recommendation for correct fuse sizing.
3
EATON www.eaton.com
Standard shunt trip ratings: 30-100A, 200A & 400A
Voltage
120Vac, 60Hz
Max inrush
4 amps
Will handle up to 447VA inrush.
1
Max ontime1
1.5 cycles
Momentary inrush
140VA
Technical Data 1145
Effective July 2014
4
EATON www.eaton.com
Quik-Spec Power Module Switch
All-in-one elevator disconnect
Technical Data 1145
Effective July 2014
5
EATON www.eaton.com
Quik-Spec Power Module Switch
All-in-one elevator disconnect
Quik-Spec Power Module Switch
All-in-one elevator disconnect
Technical Data 1145
Effective July 2014
The only controlled copy of this data sheet is the electronic read-only version located on the Bussmann network drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue
or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this
bulletin. Once a product has been selected, it should be tested by the user in all possible applications.