GRID-CONNECTED PHOTOVOLTAIC SYSTEM OF CUSTOMER’S INSTALLATION CONNECTED AT LOW VOLTAGE - POWER QUALITY The power quality (PQ) requirements at the electricity supply network point of common coupling (PCC) are covered in the Energy Market Authority (EMA)’s Handbook for Photovoltaic (PV) Systems and the Transmission Code. The PCC is the point in the distribution network, electrically nearest to a connected person’s (definition refer to Transmission Code) installation, at which other customers’ loads are, or may be, connected. The EMA’s Handbook for PV Systems and Transmission Code can be found at EMA’s website www.ema.gov.sg. 1 Technical Requirements 1.1 Harmonics The generation of harmonics by the PV Systems shall not cause the maximum total harmonic voltage distortion at the PCC to exceed total harmonic voltage distortion of 5%, with no individual odd harmonic greater than 4% and no individual even harmonic greater than 2%. These limits include existing levels of harmonic distortion at PCC. 1.2 Voltage Fluctuations including Flicker The connection of the PV Systems shall not cause voltage fluctuation at the PCC to exceed 3% of the nominal voltage. The connection of the PV Systems shall also comply with Engineering Recommendation P28 – that is it shall not cause the shortterm severity value Pst and the long-term severity value Plt at the PCC to exceed 1.0 and 0.8 respectively. 1.3 Voltage Unbalance The connection of the PV Systems shall not cause the maximum negative phase sequence component of phase voltage at the PCC to exceed 1%. 1.4 DC Injection DC injection into the distribution network is deprecated. DC injection into the distribution network at the PCC shall not exceed 20mA under normal operating condition, and not more than 0.5% of the PV inverter rating under any abnormal operating conditions, with a maximum cap limit of 100mA. The Licensed Electrical Worker (LEW) shall submit technical justification (including effect on the distribution network) to SP PowerGrid (SPPG) for consideration, if their PV system DC injection to the PCC deviates from this requirement. 1.5 Voltage Disturbance The design operation of the PV systems shall take into consideration of voltage disturbance phenomenon such as voltage dip in the distribution network. Page 1 of 3 2 Submission of Compliance The LEW shall confirm compliance with regard to the PQ requirements specified in Clause 1. This shall include but not limited to the following: • • • • Letter confirming compliance Supporting data on power quality compliance Single line drawing of the PV systems connected to the switchboard of customer installation Any other technical documentation deemed necessary by SPPG officer in the course of clarification The above should be submitted to SPPG at the time of application to connect to the distribution network or 2 weeks after the clarification with the SPPG officer. Technical justification shall be submitted to SPPG for consideration for deviation or non-compliance, if any. 3 Power Quality Measurement at the Connected Person’s Premises Where deemed necessary by SPPG, SPPG may carry out measurements at the connected person’s incoming switchboard to verify the compliance report submitted under Clause 2. The connected person shall make provision at their incoming switchboard to facilitate the connection of SPPG’s power quality monitor. All connection and disconnection of SPPG’s power quality monitor from the switchboard shall be carried out by the LEW. The monitoring schedule shall be jointly agreed by both parties. The monitoring period shall cover before PV system turn on and after PV System turn on. The monitoring period will be for a period of minimum 7-day. Before the commencement of this work, the connected person would have to agree and sign SPPG’s testing/measurement services agreement. Alternatively, the LEW can carry out their measurements verifying the declared compliance for submission. Page 2 of 3 INFORMATION TO BE SUBMITTED The LEW responsible for the installation shall complete and submit the following to SPPG, Power Quality and Transient Management (PQTM) Section. 1 General Information State the level of supply voltage intake, and any non-compliance with the power quality requirements as specified in Clause 1 of the “Grid-Connected Photovoltaic System Of Customer’s Installation Connected At Low Voltage - Power Quality”. 2 Harmonics 2.1 State the Harmonic current (1st harmonic order to 50th harmonic order) contributed by the PV Systems at point of common coupling (PCC) to the SP PowerAssets’ electricity supply network. 2.2 For installations that have non-linear loads in addition to the PV Systems, 2 set of harmonic current data to be provided. One set as above, and the other set shall be for aggregation of the harmonic current injection at the PCC. 3 Voltage Fluctuation and Flickering 3.1 State maximum voltage fluctuation (voltage step change in % of nominal voltage) at the PCC in relation to PV Systems connection and operation. 3.2 Flicker levels at the PCC: Pst during PV Systems starting Plt during PV Systems starting Pst during PV Systems normal operation Plt during PV Systems normal operation 4 Voltage Unbalance State maximum voltage unbalance (% of nominal voltage) at the PCC in relation to PV Systems connection and operation. 5 DC Injection Maximum DC injected into the network from the PV Systems during normal and abnormal operating conditions Normal Condition = mA Abnormal Condition = mA Mains Isolation Transformer installed for PV Systems? Yes / No DC injection detection device installed for PV Systems? Yes / No Note:(1) Isolation transformer installed, if any - please provide nameplate information, e.g. KVA, voltage rating etc. (2) DC injection detection device installed, if any - please provide DC injection trip setting for the PV Systems. Page 3 of 3