BS 88 industrial fuses - gG and gM curves BS 88 gG and gM Industrial fuses • The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. • These fuses are designed for : - “General purpose use” protection (gG type) - motor protection (gM type) • This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors. A, B and C types - gG curve Applications Features Power cable protection Distribution panel protection Control Panel Main circuit Distribution panel Lighting, heating and electrical equipments Capacitor, Circuit breakers, batteries DC circuit protection. Fast gG curve Asta 20 Certified Very current limiting Tested in DC Voltage 415VAC and 250VDC High breaking capacity : 80kA @ 415VAC and 40kA @ 250VDC tested A type : bracket connection, B type : blade with single central fixing hole connection C type : blade with two central fixing hole connection. Approval Ratings A type A1 : A2 : A3 : A4 : from from from from 2A to 32A 2A to 32A 40A to 100A 32A to 100A B type B1 : B2 : B3 : B4 : from from from from 32A to 100A 125A to 200A 250A to 315A 355A to 400A C type C1 : from 355A to 400A C2 : from 450A to 630A C3 : from 670A to 800A Overrating till 200A A and B types - gM curve Applications Features Approval Fast curve gM Motor protection Asta 20 Certified Very current limiting Inductive load protections Voltage 415VAC Transient overloads Electrical equipment using motors protection High breaking capacity : 80kA @ 415VAC tested A type : bracket connection, Capacitor B type : blade with single central fixing hole connection Ratings A type A1 : A2 : A3 : A4 : 20A 30A 63A 100A and 200A B type B1 : 100A B2 : 200A B3 : 315A 143 A, B and C types - gG curve A type Type A1 A1 A1 A1 A1 A1 A1 A1 A2 A2 A2 A2 A2 A2 A2 A2 A3 A3 A3 A3 A3 A4 A4 A4 A4 A4 A4 A4X* A4X* A4X* B type Rating Ref. no Designation 2 4 6 10 16 20 25 32 2 4 6 10 16 20 25 32 40 50 63 80 100 32 40 50 63 80 100 125 160 200 N226263 P226264 Q226265 R226266 S226267 T226268 V226269 W226270 Z226273 A226274 B226275 C226276 D226277 V227833 E226278 F226279 L226284 M226285 N226286 P226287 Q226288 T226291 V226292 W226293 X226294 Y226295 Z226296 D226300 E226301 F226302 2A1 4A1 6A1 10A1 16A1 20A1 25A1 32A1 2A2 4A2 6A2 10A2 16A2 20A2 25A2 32A2 40A3 50A3 63A3 80A3 100A3 32A4 40A4 50A4 63A4 80A4 100A4 125A4X 160A4X 200A4X Pack. Type 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5 5 5 5 5 5 5 5 5 Rating Ref. no Designation 32 40 50 63 80 100 125 160 200 250 315 250 315 355 400 J226305 K226306 L226307 M226308 N226309 P226310 T226314 V226315 W226316 Z226319 A226320 C226322 D226323 E226324 F226325 32B1X 40B1X 50B1X 63B1X 80B1 100B1 125B2 160B2 200B2 250B3 315B3 250B3X 315B3X 355B4 400B4 Type Rating Ref. no Designation C1 C1 C2 C2 C2 C2 C3 C3 C3 C3 355 400 450 500 560 630 670 710 750 800 G226326 H226327 J226328 K226329 L226330 M226331 N226332 P226333 Q226334 R226335 355C1 400C1 450C2 500C2 560C2 630C2 670C3 710C3 750C3 800C3 1 1 1 1 1 1 1 1 1 1 B1X* B1X* B1X* B1X* B1 B1 B2 B2 B2 B3 B3 B3X* B3X* B4 B4 Pack. 10 10 10 10 5 5 5 5 5 1 1 1 1 1 1 C type Pack. * Current ratings additional to BS88. A and B types - gM curve A type Type A1 A1 A2 A2 A2 A3 A3 A4 A4 A4 A4X A4X B type Rating Ref. no Designation Pack. 20M25 20M32 32M40 32M50 32M63 63M80 63M100 100M125 100M160 100M200 200M250 200M315 X226271 Y226272 G226280 H226281 K226283 R226289 S226290 A226297 B226298 C226299 G226303 H226304 20M25A1 20M32A1 32M40A2 32M50A2 32M63A2 63M80A3 63M100A3 100M125A4 100M160A4 100M200A4 200M250A4X 200M315A4X 10 10 10 10 10 10 10 5 5 5 1 1 Type B1 B1 B1 B2 B2 B3 144 Rating Ref. no Designation Pack. 100M125 100M160 100M200 200M250 200M315 315M400 Q226311 R226312 S226313 X226317 Y226318 B226321 100M125B1 100M160B1 100M200B1 200M250B2 200M315B2 315M400B3 5 5 5 1 1 1 BS 88 industrial fuses - gG and gM curves Standard fuse ampere rating BS 88 industrial fuses - gG and gM curves Dimensions A type Ref. BS 88 Current ratings (A) A1 2, 4, 6, 10, 16, 20, 25*, 32*, 20M25, 20M32 A2 2, 4, 6, 10, 16, 20, 25, 32, 32M40, 32M50, 32M63 A3 40, 50, 63 A3 80*, 100*, 63M80, 63M100 A4 32, 40, 50, 63 A4 80, 100 A4X 125, 160, 200, 100M125, 100M160, 100M200 A4X 200M250*, 200M315* mm In mm In mm In mm In mm In mm In mm In mm In A max B max D max Dimensions (mm & In) E max F nom G nom H nom J nom K max 33 1-1/4 49 1-15/16 49 1-15/16 49 1-15/16 51 2 51 2 51 2 51 2 12,7 1/2 22 7/8 22 7/8 26 1-1/32 22 7/8 26 1-1/32 35 1-3/8 41 1-5/8 56 2-3/16 86 3-3/8 89 3-1/2 89 3-1/2 110 4-5/16 110 4-5/16 110 4-5/16 110 4-5/16 9,5 3/8 9 11/32 13 1/2 13 1/2 20 3/4 20 3/4 20 3/4 20 3/4 A max B max D max 45 1-3/4 45 1-3/4 45 1-3/4 45 1-3/4 45 1-3/4 45 1-3/4 45 1-3/4 45 1-3/4 52 2-1/16 22 7/8 26 1/32 35 1-3/8 35 1-3/8 41 1-5/8 41 1-5/8 51 2 41 1-5/8 51 2 137 5-3/8 137 5-3/8 137 5-3/8 137 5-3/8 137 5-3/8 137 5-3/8 137 5-3/8 159 6-1/4 137 5-3/8 0,8 1/32 1,2 3/64 1,2 3/64 1,2 3/64 2,4 3/32 2,4 3/32 2,4 3/32 2,4 3/32 44,25 1-3/4 73 2-7/8 73 2-7/8 73 2-7/8 94 3-11/16 94 3-11/16 94 3-11/16 94 3-11/16 4,8 3/16 5,5 7/32 5,5 7/32 5,5 7/32 8,7 11/32 8,7 11/32 8,7 11/32 8,7 11/32 couteau ouvert 8 5/16 couteau ouvert couteau ouvert 11 7/16 11 7/16 11 7/16 11 7/16 14,3 9/16 24 15/16 24 15/16 28 1-3/32 25,4 1 29 1-1/8 38 1-1/2 45 1-3/4 * Current ratings additional to BS88. B type Ref. BS 88 Current ratings (A) B1X 32, 40, 50, 63 B1 80, 100 B1 100M125, 100M160, 100M200 B2 125, 160, 200 B2 200M250, 200M315 B3 250, 315 B3 315M400 B3X 250, 315 B4 355, 400 mm in mm in mm in mm in mm in mm in mm in mm in mm in Dimensions (mm & In) E max F nom G nom 15 9/16 20 3/4 20 3/4 20 3/4 26 1-1/32 26 1-1/32 26 1-1/32 26 1-1/32 26 1-1/32 1,4 3/64 3,2 1/8 3,2 1/8 3,2 1/8 3,2 1/8 3,2 1/8 6,4 1/4 3,2 1/8 6,4 1/4 111 4-3/8 111 4-3/8 111 4-3/8 111 4-3/8 111 4-3/8 111 4-3/8 111 4-3/8 133 5-1/4 111 4-3/8 H nom I nom 8,7 11/32 8,7 11/32 8,7 11/32 8,7 11/32 8,7 11/32 8,7 11/32 8,7 11/32 10,3 13/32 8,7 11/32 14 9/16 14 9/16 14 9/16 14 9/16 14 9/16 14 9/16 14 9/16 14 9/16 16 5/8 C type Ref. BS 88 Current ratings (A) C1 355*, 400 C2 450*, 500, 560*, 630 C3 670*, 710, 750*, 800 mm In mm In mm In A max B max D max 52 2-1/16 54 2-1/8 56 2-1/16 51 2 61 2-3/8 73 2 210 8-1/4 210 8-1/4 210 8-1/4 * Current ratings additional to BS88. 145 Dimensions (mm & In) E max F nom G nom H nom J nom L nom 26 1-1/32 26 1-1/32 26 1-1/32 6,3 1/4 7,8 5/16 9,5 3/8 133 5-1/4 133 5-1/4 133 5-1/4 10,3 13/32 10,3 13/32 10,3 13/32 16 5/8 16 5/8 16 5/8 25,4 1 25,4 1 25,4 1 Fuse-link selection for 3 phase 415 V AC induction motor circuit Motor rating kW HP 0,75 1 1,1 1,5 1,5 2 2,2 3 3 4 4 5 5,5 7,5 7,5 10 10 13,5 11 15 15 20 18,5 25 22 30 26 35 30 40 33 45 37 50 45 60 53 70 55 75 60 80 67 90 75 100 90 120 93 125 110 150 130 175 150 200 160 215 170 225 180 250 200 270 220 300 250 335 260 350 300 400 * Current ratings additional to BS88. In 2 2,5 3,5 5 6,5 8 11 14 19 21 28 35 41 48 55 62 69 83 97 100 110 120 135 160 170 200 230 260 280 290 320 350 380 420 450 500 Direct-on-line start (7 x FLC for 10 sec) Fuse-link rating (amperes) gG gM 6 10 10 16 20 25 20M25 32 20M32 40 32M40 50 32M50 50 32M50 63 32M63 80 63M80 100 63M100 100 63M100 125 100M125 160 100M160 160 100M160 200 100M200 200 100M200 200 100M200 250 200M250 250 200M250 250 200M250 315 200M315 355* 315M400* 400 315M400* 400 315M400* 450* 400M500* 500 400M500* 500 400M500* 560* 630 670* 710* 750* 800 - Assisted start (3,5 x FLC for 20 sec) Fuse-link rating (amperes) gG gM 4 6 6 10 16 16 20 25 20M25 32 20M32 32 40 32M40 50 50 63 80 63M80 80 63M80 100 100 125 100M125 125 100M125 160 160 160 200 200 250 200M250 315 315 355* 315M400* 355* 315M400* 400 400 450 400M500* 500 560* 630 - Maximum full load current starting capability Direct-on-line start (7 x FLC for 10 sec) Maximum Fuse-link motor rating (amperes) gG gM In 2 0,6 4 1,3 6 2,3 10 4,1 16 6,0 20 7,9 25 20M25 10 32 20M32 13 40 32M40 18 50 32M50 26 63 32M63 30 80 63M80 40 100 63M100 54 125 100M125 61 160 100M160 82 200 110 250 200M250 150 315 200M315 170 355* 315M400* 200 400 315M400* 240 450* 400M500* 280 500 400M500* 310 560* 350 630 380 670* 420 710* 450 750* 480 800 510 * Current ratings additional to BS88. Assisted start (3,5 x FLC for 20 sec) Maximum Fuse-link motor rating (amperes) gG gM In 2 1,3 4 2,4 6 4,3 10 6,4 16 11 20 14 25 20M25 19 32 24 40 32M40 31 50 46 63 51 80 69 100 94 125 110 160 150 200 180 250 220 315 250 355* 310 400 340 450* 400M500* 380 500 430 560* 460 630 500 670* 530 710* 550 750* 570 800 600 146 gM This data is based upon normal starting conditions and usual efficiency and power factor. Conditions such as long run-up times, large numbers of start in succession, high ambient temperature or abnormal transients during start/delta switching may necessitate adjustments to fuse-link selection. BS 88 industrial fuses - gG and gM curves gG and gM fuse-link selection 20000 4 hours 10000 gG Pre-arcing time (sec) 1000 Fuse-link rating (A) 100 10 1 0,1 0,005 1 10 100 1000 10000 100000 Prospective current (R.M.S. symmetrical A) 20000 4 heures 10000 gM 1000 Fuse-link rating (A) Temps de préarc (A) Pre-arcing time (s) BS 88 industrial fuses - gG and gM curves Time/current data 100 10 1 0,1 0,005 1 10 100 1000 Courant présumé symétrique en A) A) Prospective current(R.M.S. (R.M.S. symmetrical Curves from BS88 standard part 1 and 2 (sections 2.1 and 2.2) of 1988. Voltage rating : 415 V. Interrupting rating : 80 kA under 415 V. * Current ratings additional to BS88. 147 10000 100000 BS 88 industrial fuses - gG and gM curves I2t characteristics 7 10 6 10 5 4 Operating I2t at 415 V. Pre-arcing I2t 10 3 10 2 10 10 0 Fuse-link rating (amperes) * Current ratings additional to BS88 Dissipated power 70 60 50 Power (Watts) I2t (A2S) 10 40 BS 88 part 2 (Section 2.2) standardized limit 30 20 10 0 Fuse-link rating (Amperes) * Current ratings additional to BS88 148 Maximum value of current (kA peak) BS 88 industrial fuses - gG and gM curves Peak let-through current Prospective current (kA R.M.S. symmetrical) * Current ratings additional to BS88 Nominal current derating by temperature Fuse-link rating (A) 2, 4, 6, 10 16 20 25 32 40 50 63 80 100 125 160 200 250 315 355* 400 450* 500 560* 630 670* 710* 750* 800 Current carrying capability (in amperes) at elevated temperatures 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C 80°C FUSE-LINKS FULLY RATED 620 660 700 740 780 610 640 680 730 760 390 445 490 550 590 620 660 710 740 195 240 310 345 380 430 480 530 570 600 640 690 720 155 190 230 300 335 370 410 460 510 550 580 620 670 700 23 31 39 49 61 79 98 122 150 185 220 290 320 350 390 440 490 530 560 600 650 680 18 21 30 38 48 59 78 96 119 145 180 210 270 300 330 370 420 470 510 540 580 630 660 15 16 19 29 37 47 57 76 94 116 140 175 200 250 280 310 350 400 450 490 520 560 600 640 149 Curves and derating comply with BS88 standard part 1 and 2 sections 2.1 and 2.2 of 1988. * Derating also applies, to additional current ratings. - When the fuse-link is mounted in the open, the elevated temperature is the ambient air temperature (Ta). - When the fuse-link is mounted in an enclosure, the elevated temperature is the internal “fluid environment temperature” (Te) within the enclosure. When it is not known, it should be assumed to be 15°C higher than the ambient air temperature external to the enclosure, i.e. Te = Ta + 15°C. Examples : - 100 fuse-link mounted in the open at an ambient air temperature of 65°C. Current carrying capability = 100A. - 200A fuse-link mounted in the open at an ambient air temperature of 60°C. Current carrying capability = 195A. - 400A fuse-link mounted in an enclosure having an internal temperature of 65°C. Current carrying capability = 370A. - 800A fuse-link mounted in an enclosure with an unknown internal temperature and an external ambient air temperature of 40°C. Assume the internal temperature is 55°C (40°C + 15°C). Current carrying temperature = 740A. • The fuse comply with standard EN 60269-2 section II and standard BS88 part 2. • This fuses are designed for : - “general purpose use” protection, (gG type) - motor protection (gM type) • This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in the F type range. They are compact and can be connected with clips. Applications Features Power cable protection Distribution panel protection Control panel Main circuit Lighting, heating and electrical equipments Capacitor, batteries Can be used with circuit breakers. Compact design Curve gG and gM Very current limiting Tested in DC Voltage 415VAC High breaking capacity : 80kA @ 415VAC Connection by clips or appropriate fuse holders. Ratings Approval F1 type from 2A to 32A Asta 20 Certified F2 type from 10A to 63A Fuses designations and ratings F1 type Type F1 F1 F1 F1 F1 F1 F1 F1 F1* F1* F2 type Rating Ref. no Designation Pack. 2 4 6 10 16 20 25 32 20M25 20M32 S226336 T226337 V226338 W226339 X226340 Y226341 Z226342 A226343 B226344 C226345 2F1 4F1 6F1 10F1 16F1 20F1 25F1 32F1 20M25F1 20M32F1 10 10 10 10 10 10 10 10 10 10 * Selection table for gM fuses : refer to A, B and C types 150 Type Rating Ref. no Designation F2 F2 F2 F2 F2 F2 F2 F2 10 16 20 25 32 40 50 63 D226346 E226347 F226348 G226349 H226350 J226351 K226352 L226353 10F2 16F2 20F2 25F2 32F2 40F2 50F2 63F2 Pack. 10 10 10 10 10 10 10 10 BS 88 industrial fuses - gG and gM curves Industrial fuses BS 88 gG and gM - F1 and F2 types BS 88 industrial fuses - gG and gM curves Dimensions Ref. BS 88 Current ratings (A) Voltage (Vac) F1 415V 2, 4, 6, 10, 16, 20, 25, 32, 20M25*, 20M32* F2 415V 10, 16, 20, 25, 32, 40, 50, 63 A max mm 35,5 in 1-2/5 mm 39 In 1-7/13 B max 14,3 9/16 17,5 11/16 Dimensions (mm) D max E max 62 11,5 2-7/16 9/20 69 15 2-13/8 9/16 F nom 0,8 1/32 1,4 1/18 N nom 3,5 1/8 3,5 1/8 * Current ratings additional to BS88 also comply to the BS 88 standard part 6 of 1988. Time/current data 20000 4 hours 10000 Fuse-link ampere rating Pre-arcing time (sec.) 1000 100 10 1 0,1 0,01 0,005 1 10 100 1000 Prospective current (RMS symmetrical A) 151 10000 100000 Ip 7 10 6 10 5 10 4 10 3 Curves from BS88 standard part 6 of 1988. Voltage rating : 415 VAC. Interrupting rating : 40 kA under 415 VAC. ASTA 20 certified * Current ratings additional to BS88 also comply to the BS 88 standard part 6 of 1988. Operating I2t at 415 V. pre-arcing I2t 10 2 10 0 2 4 6 10 16 20 25 & 50 32 40 & 20 20 M 25 M32 * $ 63 Dissipated power Fuse-link rating (Amperes) 5 Curves from BS88 standard part 6 of 1988. Voltage rating : 415 VAC. Interrupting rating : 40 kA under 415 VAC. Power (Watts) * Current ratings additional to BS88 also comply to the BS 88 standard part 6 of 1988. 4 BS 88-part 6 standardized limit 3 2 1 Peak let-through current 0 Fuse-link rating (Amperes) Curves from BS88 standard part 6 of 1988. Voltage rating : 415 VAC. Interrupting rating : 40 kA under 415 VAC. * Current ratings additional to BS88 also comply to the BS 88 standard part 6 of 1988. Prospective current (kA R.M.S. symmetrical) 152 BS 88 industrial fuses - gG and gM curves 10 Maximum value of current (kA) I2t (A2S) I2t characteristics