CENTERLINE 2500 Motor Control Centers Selection Guide Contents CENTERLINE® 2500 Motor Control Centers 5 Unit Design 23 Units 34 Selection Data 69 Unit Selection 72 Technical Data 74 Checklist 79 79 3 4 CENTERLINE® 2500 Motor Control Centers The CENTERLINE 2500 Motor Control Center (MCC) consists of one or more columns secured together forming a rigid, free-standing assembly. The MCC columns are designed to allow the addition of future columns. The MCC is designed with full isolation of electrical components from the front side of the structure. When the doors are latched and the covers are secured, a person on the operating side of the equipment is not exposed to live parts. Units installed in the MCC columns are populated with a full line of IEC components, contactors, overload relays, AC drives, soft starters and other devices. Product Features • Meets Global Standards – Designed to IEC 60439-1 – Designed to IEC 60529 – KEMA (TTA) Certified • Fully withdrawable unit design allows for faster replacement, helping minimize maintenance and downtime – Plug-in line, load, control, ground and network communications – Four unit positions (connected, test, disconnected and withdrawn) – Lever operated mechanism for tool-less withdrawal and insertion • Built-in network and IntelliCENTER® technology – Improve performance through system-wide communications – Share diagnostic information for predictive maintenance – Initiate warnings before potential faults occur • ArcShield helps you reduce arc flash hazards • Three and four wire bus bar power systems available to help meet your local requirements • High unit density optimizes column utilization • Fully isolated structures for maximum arc containment • Multiple column widths of 600, 700, 800, 900 and 1000 mm available for scalable solutions 5 IntelliCENTER Technology Built-in Networking • Media protected behind barriers • Access ports in wireways • Trunk and drop topology allows for addition and removal of devices without shutting down the network Intelligent Motor Controls • • • • PowerFlex Drives SMC™ 3 and SMC™-Flex Soft Starters E1 Plus, E3 Plus Electronic Overload Relays DeviceNet Starter Auxiliaries IntelliCENTER Software • • • • Elevation View Monitor View Documentation View Spreadsheet View Factory Configuration • Network media validation • Node configuration • Device communication check IntelliCENTER Technology improves the intelligence of your MCC using built-in DeviceNet to capture information used for predictive maintenance, process monitoring, and advanced diagnostics. 6 DeviceNet Based on the latest in network technology, DeviceNet is a simply, open networking solution, allowing for real-time control, data exchange, configuration and data connection at regular intervals or on demand. This robust communication link connects industrial devices (such as limit switches, photoelectric sensors, motor starters, push buttons, variable frequency drives and operator interface devices) to a network and eliminates time-consuming and costly hard wiring. The cost and performance of a DeviceNet network makes it ideal for MCC applications. The open specifications and protocol, managed by the Open DeviceNet Vendor Association (ODVA), means vendors are not required to purchase hardware, software or licensing rights to connect to a system. Over 300 vendors offer DeviceNet products with over a half million nodes installed worldwide. IntelliCENTER Software The CENTERLINE 2500 MCC is available with pre-configured IntelliCENTER software. IntelliCENTER software is an intuitive softare package that is customized to your MCC. This software package includes several preconfigured views for easy access to important information and is capable of viewing multiple MCC line-ups. IntelliCENTER software can be installed and operated on Ethernet, EtherNet/IP, ControlNet or DeviceNet. The IntelliCENTER software is capable of functioning as a stand alone software package or as an ActiveX control in a Human Machine Interface (HMI). The IntelliCENTER software displays the following: Elevation View The Elevation View is an easy-to-identify, graphical representation of your entire MCC lineup. The condition of each motor controller is quickly established with status light indicators. Customizable text allows for instant identification of the motor, machine or process. • Navigate immediately to units of concern by simply double-clicking on them • Re-arrange the elevation view using simple drag-and-drop • Select units for which you would like to see manuals, wiring diagrams or spare parts Monitor View The Monitor View displays an overview of the intelligent motor control device being monitored, with configurable gauges, trend graphs, I/O status on the device and configurable data fields. • Monitor parameters from the intelligent devices • Change configuration parameters • Record up to 5000 data points with the trend graph and export • Change which parameters are displayed in the monitor view Documentation Views Documentation View has access to the various manuals and diagrams for your MCC along with other important MCC information. Manuals and Wiring Diagrams The IntelliCENTER Software data CD comes with the complete documentation for your MCC, including wiring diagrams and device manuals. So your manuals are quickly available when you need them most. • Troubleshoot problems using the exact manuals for your MCC • Trace out wiring and understand control circuits using wiring diagrams • Add new documentation ( procedures, engineering notes) associated with your MCC • Substitute ‘as-built’ drawings with your ‘as-installed’ drawings 7 Spreadsheet View The spreadsheet view allows you to access MCC data such as: • Node number (network address) • Unit description • Nameplate data • Device type Event Log View The Event Log records and stores events with date and time information occurring within you MCC and stores them with their date and time. Events can include device warnings and faults as well as parameter or device changes. Spare Parts List The spare parts list provides you with the exact replacement part needed to repair your MCC unit. This helps save time when calling your authorized Allen-Bradley distributor. 8 Networking DeviceNet Cabling All trunk and drop DeviceNet cabling is ODVA certified Class 1, with 600V insulation and 8 A rating. The DeviceNet cabling system for IntelliCENTER Technology has been extensively tested for noise immunity with network cables in close proximity to high current motor leas and VFD outputs. As a result, IntelliCENTER MCCs provide a very robust network solution with no special separation, barriers or internal conduit required. DeviceNet Cable Layout The DeviceNet trunk line is routed through the control and network wireway and top horizontal wireway of the MCC. Trunk lines are routed behind barriers to isolate the cable from the unit space and wireways to help prevent accidental damage. DeviceNet Trunk Line Up to 24 DeviceNet ports can be provided in the control and network wireway. Each DeviceNet component in an MCC unit is connected to the network through a port located in the control and network wireway. Adding or removing units from the network does not interrupt the other units operating in the system. DeviceNet System Performance The DeviceNet system in the MCC is designed to operate at 500 kbaud to maximize performance, unless precluded by the cumulative length of the trunk and drop lines. To achieve best performance, all MCCs are engineered for a 250 kbaud minimum communication rate. The DeviceNet system in the MCC is qualified to communicate and perform under normal and adverse electrical environments (for example, contactor electrical operation, contactor jogging duty and unit short circuit fault). The DeviceNet system has the following capabilities: • Automatic Device Replacement (ADR). • On-Line Scanlist Changes at Run, allowing network modifications to be performed on a DeviceNet system that is running. • Scan modes: Polled, Change of State (COS), Strobe and Cyclic. By choosing the appropriate scan mode for different data, DeviceNet systems can achieve better throughput performance than networks with much higher communication rates. • Transmit and receive data via I/O and explicit messaging. This allows the control system to access every parameter in the device, not just a few registers. 9 DeviceNet Components Each unit can be provided with a DeviceNet component. • Starter units can be provided with an E1 Plus with DeviceNet module, E3 or E3 Plus overload relays or solid-state overload relays with a DeviceNet Starter Auxiliary. • Contactor units can be provided with a DeviceNet Starter Auxiliary. • AC drives can be provided with a DeviceNet communication module. • Solid-state controllers can be provided with DeviceNet communication modules and, in some instances, a DeviceNet Starter Auxiliary. • Fusible disconnect and circuit breaker feeder circuits can be provided with a DeviceNet Starter Auxiliary. Programming of Parameters The DeviceNet node address is programmed for each unit. All other parameters are left at the factory default setting. The DeviceNet components are configured to operate at the specified communication rate. Testing CENTERLINE 2500 motor control centers with IntelliCENTER Technology can save you time because each MCC is powered up, configured and tested at the factory. Each unit is preconfigured with node addresses and communication rates to ensure it communicates properly. For more information on MCCs with DeviceNet, refer to CENTERLINE 2500 DeviceNet Motor Control Centers, publication 2500-TD002. IntelliCENTER Database The IntelliCENTER Database contains all of your order-specific information. One IntelliCENTER Database is needed for each MCC lineup or for individual units (when the unit is purchased separately). The database is installed on the computer or computers running the IntelliCENTER software. The database CD includes the IntelliCENTER data files, all of the electronic documentation, all theup-to-date EDS files for the DeviceNet devices and the DeviceNet configuration file as recorded during the final system test of the MCC. The EDS and configuration files are very useful for programming the control system, allowing the programmer to complete the project before the equipment is even energized. Additionally, when used with RSLogix 5000 and RSNetworx for DeviceNet software, the programmer can use the DeviceNet Tag Generator utility in RSLogix 5000 to instantly generate descriptive tags for every device in the MCC. 10 ArcShield CENTERLINE 2500 MCC’s with ArcShield offers you better protection against harmful arc flash hazards. Using a CENTERLINE 2500 MCC with ArcShield helps protect your personnel if an arc flash were to occur within an MCC. CENTERLINE 2500 MCC with ArcShield provides personnel and assembly protection per IEC/TR 61641:2008 for arcing durations up to 300 ms(1). In combination with the standard safety features built into every CENTERLINE 2500 MCC, choosing ArcShield provides additional benefits, including: • Structures with no front ventilation • Pressure relief system designed to exhaust gases through the top of the structure, away from personnel • Arc containment latches on all doors capable of withstanding the high internal pressure generated by an arc blast • Insulated power bus closing plates included at the ends of each MCC lineup Pressure Relief System Arc Containment Latches For even more protection, optical and current sensing technology for use with crowbar or shunt trip devices is available as an option. (1) 300ms rating is available for systems at 415V (max), with 65kA (max) available current 11 Structure The CENTERLINE 2500 MCC structure consists of columns, wireways, doors and withdrawable or fixed units. Columns The rigid, free-standing columns have heavy duty external mounting channels running the continuous width of the shipping block. Columns are secured at the installation site by bolting together clearance holes in the mounting channels or welding together. All shipping blocks are provided with a removable continuous steel lifting angle. Two lifting angles are provided on all double-front columns. Fault containment is enhanced with two side sheets on every column. This helps prevent a single fault from cascading throughout the structure, limiting equipment damage. The CENTERLINE 2500 MCC’s rigid design helps ensure a longer life. Plug-in units can still be installed and removed and doors close securely after years of dependable service. 12 Column Construction Optional ArcShield Pressure Relief Plate Top Horizontal Wireways Vertical Power Bus Vertical Wireway (door closed) Horizontal Power Bus Nameplates Vertical-to-Horizontal Bus Connection Customer Load Terminal Forms of Separation Unit Support Pan Optional ArcShield End Closing Plate Insulator Control and Network Wireway Vertical Bus Covers (Automatic Shutters) Bottom Horizontal Wireways Vertical Plug-in Protective Earth Conductor Horizontal Protective Earth Conductor 13 Column Dimensions The standard column width is 700 mm. Each column is 2300 mm high and 600 mm deep. Double-front columns are also available. Unit size is described in terms of modules. Each module is approximately 80 mm high x 500 mm wide. Columns can accommodate 24 modules of varying unit combinations. Horizontal wireways extend the full depth of the column. Vertical wireways are approximately 350 mm deep. Column Width 700 - 1000 (27.56 - 39.37 170 (6.69) Total Column Width Unit Width Vertical Wireway Width 600 mm(1) 600 mm No vertical wireway 700 mm (standard) 500 mm 200 mm (standard) 800 mm 500 mm 300 mm 900 mm 500 mm 400 mm 1000 mm 500 mm 500 mm (1) Frame mount only. Column Depth Front Only 2300 (90.55) Double-Front 600 mm 1200 mm 800 mm — Column Height 1980 (77.95) Feature Height Total Height 2300 mm Available Unit Height 1980 mm Top Horizontal Wireway 170 mm Bottom Horizontal Wireway 115 mm External Mounting Channel 35 mm Approximate Weight 35 (1.38) 115 (4.53) 600 (23.62) 500 (19.69) 200 - 500 (7.87 - 19.69) This table lists approximate weights for MCC columns. Many factors (number of units, horizontal power bus, wireway width, column depth) affect the weight of columns. Weight is also added when the product is packaged for shipping. Column Width Approximate Weight (1) 600 mm, 700 mm 350 kg 800 mm 400 kg 900 mm 450 kg 1000 mm 500 kg (1) Weights are for a typical Motor Control Center with 6 units per column. Weights do not include packaging. Refer to the packing slip shipped with your MCC for exact shipping weights. 14 Structure You can select the degree of protection and the paint color for your CENTERLINE 2500 MCC. Degree of Protection In accordance with IEC 60529, structures are available with the following IP ratings. • IP 20 (non-filtered vented doors) • IP 30 (filtered vented doors) • IP 42 (non-vented doors, standard) • IP 54 (gasketed with bottom plates) Structure sheet metal has rounded edges and is tightly fitted with no visible air gaps. Paint and Plating Structural metal undergoes a multi-step cleaning, rinsing and painting process resulting in complete uniform-thickness, paint coverage. This process is maintained and controlled by ISO 9001 quality standards. Zinc with trivalent chromate is used to plate unpainted surfaces for corrosion resistance. The standard exterior paint color is Pebble Grey (RAL 7032). Closing plates, channel supports, lifting angles, and horizontal wireway covers are painted Black Grey (RAL 7021). Interior vertical wireways and unit mounting plates are painted high visibility gloss white. Other colors are available by request. 15 Wireways Each MCC has horizontal, vertical and control and network wireways, for continuous dedicated wire and cable location. Continuous Horizonal Top Wireway Horizontal Wireways Continuous Vertical Wireway Continuous Horizonal Bottom Wireway Horizontal wireways are located at the top and bottom of each MCC column. Horizontal wireways extend the full width and depth of the MCC. A barrier is present in the top horizontal wireway to provide a connection point for DeviceNet receptacles. The top horizontal wireway is 170 mm high, while the bottom horizontal wireway is 115 mm high. Complete wireway access from front to rear is available for double-front configured MCC columns.. Horizontal wireways have removable front covers that are held in place by captive screws. Openings in in the side plate of the column allow access to the top and bottome norizontal wireways between joined columns. Plates are provided to cover these openings for columns located at the end of a MCC lineup. Horizontal wireways are isolated from the power bus. Horizontal wireways for incoming line sections are reduced depth to maintain isolation from the incoming line area. Vertical Wireway The vertical wireway is located on the right side of each column and extends 1980 mm, between the top and the bottom horizontal wireway. The vertical wireway is approximately 350 mm deep. The standard vertical wireway is 200 mm wide. Vertical wireways are also available in widths of 300, 400 and 500 mm. Wider wireways are recommended for MCCs with higher bus ratings and higher unit density per section. The vertical wireway is isolated from power bus and is independent of unit space. Vertical wireways are not present in columns with fixed (frame-mounted) units. Vertical wireways are covered with steel doors, held in place by four door latches. See Nameplates on page 32 for more information. Vertical wireway cable supports are available to help you keep your cable wireways organized. 16 Control and Network Wireway A separate wireway isolates control and network cables from power wiring. The control and network wireway is located on the left side of the column in the unit space. Control and network connections are made to withdrawable units through receptacles located in this wireway. Control Wireway DeviceNet Network Connector Units Removed Control Connector 17 Incoming Power The MCC can be configured to work on a system with any of the following incoming line voltages: 380, 400, 415, 440, 480, 600 and 690 V. The MCC can be configured to operate at a frequency of 50 or 60 Hz. CENTERLINE 2500 MCCs are suitable for use on three-phase, three-wire or four-wire, wye connected power systems, rated 690V or less, 50 or 60 Hz, with a solidly grounded neutral. CENTERLINE 2500 MCCs may also be used on other power system configurators, however, some units and options may not be available. Consult the factory for additional information. Power Bus The MCC features the time-proven Allen-Bradley CENTERLINE power bus system. The horizontal power bus is mounted near the vertical center of the structure providing optimum heat dissipation, power distribution, and ease of maintenance and installation. It is mounted in recessed channels of the bus support to protect against accumulation of dust and tracking between phases. The vertical power bus allows power distribution both above and below the center-mounted horizontal bus, effectively doubling the capacity in each column. This feature also helps allow a virtually unrestricted unit arrangement. Horizontal and vertical power bus is fastened together with a two bolt assembly. This two-bolt connection helps minimize the likelihood of “hot spots.” The factory-made horizontal to vertical power bus connection is tightened by a computerized torquing system. The power bus system is supported, braced and isolated by a bus support molded of high strength, non-tracking glass polyester material. The horizontal power bus is mounted on-edge in a vertical plane providing maximum strength against magnetic forces. Vertical power busbars are continuously braced and sandwiched by a polycarbonate molded bus cover isolating the vertical power bus from the other vertical phases and the horizontal power bus. Bus bracing is available with the following rms symmetrical current ratings. • 50 kA for 3 cycles at 60 Hz (standard) • 65 kA for 3 cycles at 60 Hz • 50 kA for 1 second • 50 kA for 3 seconds (horizontal power bus only) • 80 kA for 1 second (horizontal power bus only) 18 CENTERLINE Power Bus and Neutral (Cover Removed) Optional Neutral Horizontal Bus Bar Two-bolt Assembly Optional Neutral Vertical Bus Bar Horizontal Power Bus Vertical Power Bus The standard horizontal power bus material is unplated copper. Tin-plated copper horizontal power bus is optional. The tin-plated copper vertical power bus is cylindrical for optimum contact with the plug-in unit stabs. Horizontal Power Bus Ratings and Descriptions Power Bus Rating Busbar Quantity and Dimensions 800 A (standard) (1) 3 x 100 mm 1250 A (1) 6 x 100 mm 1600 A (2) 6 x 100 mm 2000 A (1) 6 x 100 mm and (1) 10 x 100 mm 2500 A (2) 10 x 100 mm 3200 A (3) 10 x 100 mm with 10 mm spacers 4000 A (4) 10 x 100 mm with 10 mm spacers The standard vertical power bus is rated for 300 A above and below the horizontal power bus for an effective 600 A rating. An optional vertical power bus rated for 600 A above and below the horizontal power bus for an effective 1200 A rating is available. 19 Neutral Bus The optional horizontal neutral bus is provided across the full width of the MCC and located above or below the horizontal power bus. Back of MCC (back plate removed) Neutral bus shown The neutral bus matches the material and specifications of the vertical power bus. The horizontal neutral bus is available with a full or half current rating. The vertical neutral bus is connected to the horizontal neutral bus and provides a neutral connection for units throughout the column. The neutral bus is braced the same way as the horizontal and vertical power bus. Automatic Shutters Automatic shutters are standard on CENTERLINE 2500 MCCs. Automatic shutters open as withdrawable units are inserted and close when the unit is removed. This safety feature helps ensure the vertical bus is immediately isolated when a withdrawable unit is removed. 20 Protective Earth Conductor The horizontal protective earth conductor along with the vertical plug-in protective earth conductor form a complete internal protective earth circuit. Horizontal Protective Earth Conductor The horizontal protective earth conductor (PE) is unplated copper or tin-plated copper is available, and is located in the bottom horizontal wireway. The horizontal PE is continuous for the width of the column and consists of one, two or three 6 x 50 mm conductors. The horizontal PE has 12 holes along the length of the conductor for making equipment connections. A pressure-type mechanical lug is mounted on the horizontal PE conductor in the incoming line section. Vertical Plug-in Protective Earth Conductor An unplated copper vertical plug-in PE conductor is provided in each standard column. An optional tin-plated copper vertical plug-in PE conductor is also available. The vertical plug-in PE conductor is mechanically connected to the horizontal PE conductor. The vertical plug-in PE conductor in combination with the unit PE contact establishes a first make, last break operation of the PE connection with respect to power connections. This first make, last break connection assures the unit to be grounded when inserting or removing the unit. 21 Module Space Unit size is described in modules. One module is approximately 80 mm high x 500 mm wide. Withdrawable units are available in the following sizes: 1, 2, 4, 6, 8, 10 and 12 modules. Fixed units range in size from 2 to 24 modules. Each MCC column can accommodate 24 modules. Continuous Horizontal Wireway 2 Module Unit 4 Module Unit 24 Modules Total Continuous Vertical Wireway 8 Module Unit Continuous Horizontal Wireway 22 Unit Design Units are designed as either withdrawable or fixed. Withdrawable units can be removed from the structure and have a maximum current rating of 225 A. The amount of current drawn by fixed units is determined by the rating of the horizontal power bus. Fixed units are frame-mounted and cannot be moved or rearranged once installed in the column. Two Module Unit Withdrawable Unit Design Features Withdrawable units consist of the unit, unit support pan and unit door. Withdrawable units are held securely in the column when inserted and are designed with an interlock to help ensure that units cannot be inserted or withdrawn when the disconnect means is in the ON/I position. Withdrawable units range from 1 up to 12 module sizes. Tools are not required to insert or remove withdrawable units. Withdrawable units are characterized by being able to release the line, load, control, network and protective earth (PE) connections. Outgoing load and control connections are in the vertical wireway. 23 Withdraw Lever and Alignment Slides Withdrawable units use low friction alignment slides and a mechanical withdraw lever for easy unit inserting and removing. The withdraw lever features a locking mechanism that the user disengages to change positions. Detents are present to help confirm that the unit is secured in each position. Withdraw Lever Operating Positions Withdrawable units have four operating positions: connected, test, disconnected and withdrawn. See the following descriptions for additional information about the features of each position. shows the withdrawable unit operating positions. Connected - Line, load, control, network and PE connections are all engaged. Closing the unit door ensures the withdraw lever is in the connected position. To engage the interlock or turn the disconnect means to the ON/I position, the unit door must be fully closed. 24 Test - Control, network and PE connections are engaged. Line and load connections are isolated. This allows the user to verify control and network wiring. Units can be locked in this position. Disconnected - The unit remains housed in the column, but no connections are present. This is an isolated position. Units can be locked in the disconnected position. Withdrawn - Withdrawable units can be completely removed from the columns. When units are withdrawn from the MCC, they are isolated from connections. Withdrawn units can be locked to prevent insertion. Withdrawable Unit Operating Positions Operating Position Connection Present Line Load PE Control Network Connected x x x x x x(1) x x x x Test Lockable in Position Disconnected Connections not present. Unit remains inserted in column. x Withdrawn Connections not present. Unit is removed from column. x (1) Unit is lockable when door is closed. 25 Fixed (Frame-mounted) Unit Design Features Fixed units are permanently mounted in the column, all connections are made directly to the components. Fixed units range from 2 up to 24 module sizes. For units 12 module size and above, fixed unit design is standard. Fixed (Frame-mounted) Unit Connections In fixed units, line, load, PE and control connections are made directly to components. Network connections can be made through fixed or plug-in terminal blocks. shows possible unit connections. Unit Connections Withdrawable Unit Connections Fixed Unit Connections Line Withdrawable Fixed Load Withdrawable Fixed PE Withdrawable Fixed Control Withdrawable Fixed Network Withdrawable Disconnectable Operating Handle Rotary Operating Handle An industrial, heavy duty, rotary operating handle is supplied for control of the disconnecting means in each unit. When the unit door is closed, the handle is engaged with the disconnect means. The operating handle can be locked in the OFF/O position with up to three 8 mm diameter shackle padlocks. The operating handle can be modified to enable locking in the ON/I position. The unit operating handle is interlocked with the unit door to help prevent opening the unit door unless the disconnect means is in the OFF/O position. An externally operated defeater is provided to access the unit without interrupting service. The operating handle is interlocked with the unit so the unit cannot be inserted or withdrawn with the operating handle in the ON/I position. Rotary Operating Handle 26 Rotary Operating Handle for One Module Units Flange-mounted Handle Vertical Flange Operating Handle Flange style disconnect handles (vertical or horizontal mounted) are available for units with circuit breaker disconnects. The flange handle helps prevent the disconnect from being switched to the ON/I position when the unit door is open. Units with vertical flange handles must be at least 4 modules. Units with horizontal flange handles must be at least 2 modules. Unit Disconnect Means The unit disconnect switch is available as a circuit breaker or fusible disconnect. Withstand ratings for combination starter units are based on the short circuit protective devices and components selected. Circuit Breakers Allen-Bradley circuit breakers are provided as the disconnecting means for units with a circuit breaker unit main switch. Bulletin 140M motor circuit protectors are used for combination motor control units. Bulletin 140M motor protection circuit breakers and Bulletin 140U molded case circuit breakers are utilized for feeder units. Circuit breaker unit main switches are available in the following ratings based on circuit breaker and component selection. Circuit Breaker Ratings Rating Amperage and Voltage Type 1 Up to 100 kA at 400 V Type 2 Up to 65 kA at 400 V Up to 50 kA at 500 V Up to 25 kA at 600 V Up to 10 kA at 690 V 27 Disconnect Switches When specified, Allen-Bradley disconnect switches are provided. The Bulletin 194R fused disconnect switch is used in combination starter and feeder units. One module combination starter and feeder units utilize the Bulletin 194E unfused switch. When requested, NH fuses are supplied in the following styles: DIN gG and DIN aM. Disconnect unit main switches are available in the following ratings based on component and fuse selection. Disconnect Ratings Rating Amperage and Voltage(1) Type 2 Up to 100 kA at 400 V Up to 100 kA at 500 V Up to 100 kA at 600 V (1) For 690V information, please consult the factory. Stab Assembly Power Stab Assembly The two-piece power stab housing is made of high strength, non-tracking glass polyester material and provides a separate, isolated pathway for each phase. The power cable connection at the plug-in stab is made with a maintenance free crimp style connection. There is no exposed wiring at the back of the unit between the disconnecting means and the plug-in stabs. Unit plug-in power stabs are rated 225 A. The stabs are made of tin-plated copper for a low resistance connection and are designed to tighten during heavy current surges. The free-floating and self aligning unit plug-in power stabs are backed by stainless steel spring clips to provide and maintain a high pressure, four-point connection to the vertical power bus. 28 Neutral Stab Neutral Stab Assembly The neutral stab assembly can be supplied on withdrawable units for 4-wire systems. The neutral stab assembly has the same design and features as the power stab assembly, but is a separate piece. One Module Stab Assembly The one module stab assembly consists of a receptacle for line and load connections that plugs into a subplate connected to the vertical power bus. The two guide pins help ensure the connector is properly aligned. Because of the subplate connection, one module units must be installed in pairs. One module units stabs are rated at 32 A. Protective Earth Contact An unplated copper PE contact is provided on withdrawable units. This contact establishes a connection with the PE circuit before other connections are made and is the last withdrawable connection to be disconnected. Control and Network Connections Plug-in control and network connections are made automatically for withdrawable units. A 15-pin connector plug, rated at 10 A, is used for control connections. DeviceNet network connections are made through a separate connector. The control and network connectors use a spring-loaded mechanism to ensure proper connection. 29 PE Contact, Control and Network Connections PE Contact Control Connection Network Connection Unit Doors Each unit is provided with a removable unit door, mounted on hinges with removable pins. Unit doors are held closed with ¼ turn latches. See Door Latches on page 31 for more explanation. The unit door is mounted to the structure so it is not necessary to remove a nit door when installing or removing units. The door can be closed with the unit removed to isolate the power bus. A unit door can be removed from any location on the MCC without disturbing other unit doors. Control stations for pilot devices and low profile external reset buttons for overload relays are often mounted to the unit door. 30 Door Latches There are two types of door latches available for the 2500 MCC. Standard CENTERLINE 2500 MCCs have quarter-turn door latches. If you select an MCC with ArcShield, the MCC will have arc containment door latches. Door Latches (Standard) Door latches are provided on unit and vertical wireway doors to hold the door closed and isolate personel from the column. Door latches can be locked or released by rotating the latch ¼ turn. An arrow on the door latch head indicates the position of the latch. Released Position Locked Position Arc Containment Latch Optional arc containment latches are available. Arc containment latches help protect personnel in the vicinity of an MCC if an arc fault occurs when structure doors are closed and latched. Arc containment latches can be locked or released by rotating the latch ¼ turn. Released Position Locked Position 31 Nameplates The MCC master nameplate, when specified, is available with up to five lines of engraving and is located on the top horizontal wireway cover. Unit nameplates are available and can accommodate three or four lines of engraving. The following types of unit nameplates are available: • Clear cardholders - insert printed cards into cardholder • Engraved acrylic nameplates - white with black lettering or black with white lettering • Engraved phenolic nameplates - white with black lettering, black with white lettering or red with white lettering Nameplates are secured using two steel self-tapping screws. Stainless steel screws are also available. Unit Nameplate Control Power Unit control power is specified as: 24V DC, or 110, 115, 120, 220, 230 or 240V AC. Unit control power is normally supplied by a single common control power transformer unit within each MCC lineup. This common control power allows the test function of withdrawable units to work most effectively. The common control source operates at line voltage with an option for common control fusing. Individual control circuit transformers, mounted in each unit, are available. One leg of the secondary side of the control circuit transformer is fused while the other leg is connected to PE. Primary protection is then provided by primary fusing. Control Wire Control wire is ‘multistrand’ or ‘stranded’ copper. (Need to add type of insulation and rating (90 °C what) Wire markers are sleeve type; heat shrink is optional. Power Wire The power wire is double-insulated copper and rated at 105°C or higher. The power wire is sized to meet the current rating of the unit, with a minimum size of 6 mm2. NEED FAULT FREE ZONE TEXT 32 Mounting Configurations The MCC is available in two mounting configurations – front-only and double-front. • Front-only columns are joined and installed side-by-side. • Double-front columns are two separate columns joined at the rear, back plates are removed. The two columns have separate power bus systems providing the same phasing for all units. The horizontal power bus is linked, front to rear, with a factory installed U-shaped bus splice assembly. For shipping purposes, only 600mm deep columns can have double-front configurations. Front-only (standard configuration) Double-front (optional configuration) 33 Units Columns can be populated with several different types of units, such as mains, feeders, direct on line starters and contactors, soft starters, AC drives and PLCs. One Module Unit DeviceNet Scanner Modules DeviceNet in the MCC requires a DeviceNet scanner module that meets DeviceNet requirements. The scanner module may be located in the MCC or mounted remotely. Network Linking Devices Network linking devices allow CENTERLINE 2500 MCC customers to connect to different communication networks. With network linking devices you are able to connect to ControlNet or EtherNet/IP directly from you MCC. NetLinx technology enables you to link from one network to another easily, making data transfer from the MCC’s DeviceNet network onto the controller’s EtherNet/IP or ControlNet simple. Linking Devices Unit Description Module Size 1 = 80 mm ControlNet to DeviceNet Bridge 2 Ethernet to DeviceNet Bridge 2 Profibus to DeviceNet Bridge 2 DeviceNet Power Supply DeviceNet in the MCC requires a power supply providing 24V DC and rated no less than 8 amperes. A quality power supply is essential to reliable system operation. To ensure system integrity and reliability, the Allen-Bradley Bulletin 2500-DPS 8 A DeviceNet Power Supply unit is recommended. This power supply meets DeviceNet requirements, ODVA approval, and is supplied with a buffer for enhanced ride-through performance. A redundant power supply is also available for added reliability. . DeviceNet Power Supply Units Unit Description Module Size 1 = 80 mm DeviceNet Power Supply 2 Redundant DeviceNet Power Supply 4 Back-up DeviceNet Power Supply 34 Main Incoming Line (Lug-only) Compartment Main incoming line lug compartments are available in either the top or bottom entry and use mechanical screws or crimp/ compression lugs. The compartments are front accessible. Main Incoming Line Compartments Incoming Line Compartment Rating 6 modules (480 mm), variable column width 600 A (using vertical power bus) 24 modules (full column), 700 mm wide 800, 1250, 1600, 2000 A 24 modules (full column), 800 mm wide 2500, 3200, 4000 A Main Incoming Circuit Breaker Air circuit breakers (ACB) or molded case circuit breakers (MCCB) are available for main incoming circuit breakers. Main circuit breaker units are front accessible with removable protective barriers on the line side, helping reduce the possibility of accidental contact with line terminals. The ACB compartments have trip ratings available from 400…4000 A. These ACBs are available with a drawout or fixed style. The ACBs for mains include an option to utilize 4-pole breakers. ACBs may be integrated into auto-transfer switch schemes. This table provides more information on available incoming air circuit breaker compartment arrangements and sizes. MCCBs are inverse time circuit breakers and can be classified as thermal magnetic or electronic. Incoming Air Circuit Breaker Compartment Arrangement Incoming Air Circuit Breaker Compartment Rating 24 modules (full column), 800 mm deep x 800 mm wide 800, 1250, 1600, 2000 A 24 modules (full column), 800 mm deep x 900 mm wide 2500, 3200, 4000 A Main Incoming Fusible Disconnect Mains with fusible disconnects are available. Fuses can be factory installed or supplied and installed by others. 35 Pilot Devices Pilot devices are housed in a door mounted control station. Each control station can accommodate up to four 22 mm devices. Multiple control stations can be mounted on a unit door, if more than four pilot devices are required. Control stations are equipped with a quick connect plug for ease in connecting and disconnecting control wiring. The control station is easily removed using captive screws. If a control station is removed, closing plates are available to cover the opening in the unit door and provide isolation. Main and Feeder Units Incoming Main Lug Compartments and Outgoing Feeder Lug Compartments The line lug compartments provide a lug connection for incoming lines (mains) to distribute power to the motor control center or for outgoing cables (feeders) to feed power from the motor control center to an external load. Line lug compartments are available in ratings from 300…4000 A and are fixed mounted. Main and Feeder Circuit Breaker Units The circuit breaker units have trip ratings available from 15…4000 A. These units are available with thermal magnetic trip circuit breaker up to 1200 A and electronic trip circuit breaker 100 A and above. The feeder circuit breaker units are available in a withdrawable unit style up to 225 A and are fixed mounted for ratings 250 A and above. The main circuit breaker units are fixed mounted for all ratings. For main and feeder circuit breaker unit selection go to page . For main and feeder circuit breaker option selection go to page . Mains, Air Circuit Breakers Amperes Circuit Breaker Catalog Number Module Size (1) 1 = 80 mm Column Width (mm)(3) Column Depth (mm)(4) 800 140RX-NS**D-D80 24(2) 700 600, 800 1250 140RX-NS**D-E12 24(2) 700 600, 800 1600 140RX-NS**D-E16 (2) 700 600, 800 2000 140RX-RS**D-E20 (2) 24 800 800 2500 140RX-RS**D-E25 24(2) 800 800 3200 140RX-SS**D-E32 (2) 900 800 4000 140RX-SS**D-E40 (2) 900 800 (1) (2) (3) (4) 36 24 24 24 To complete the catalog numbers, please contact the factory Fixed mount style Available column widths Available column depths Mains, Thermal Magnetic Circuit Breakers Amperes Circuit Breaker Module Size Catalog Number 1 = 80 mm Column Width (mm)(2) Column Depth (mm)(3) 150 140U-J*D3-D15 4 (1) 700, 800, 900, 1000 600, 800 200 140U-J*D3-D20 4 (1) 700, 800, 900, 1000 600, 800 250 140U-J*D3-D25 4(1) 700, 800, 900, 1000 600, 800 300 140U-L*D3-D30 8 (1) 700, 800, 900, 1000 600, 800 350 140U-L*D3-D35 8 (1) 700, 800, 900, 1000 600, 800 400 140U-L*D3-D40 8 (1) 700, 800, 900, 1000 600, 800 500 140U-L*D3-D50 8 (1) 700, 800, 900, 1000 600, 800 600 140U-L*D3-D60 8 (1) 700, 800, 900, 1000 600, 800 700 140U-M*D3-D70 (1) 700, 800, 900, 1000 600, 800 800 140U-M*D3-D80 (1) 700, 800, 900, 1000 600, 800 12 12 (1) Fixed mount style (2) Available column widths (3) Available column depths Mains, Electronic with LSI Protection Type Amperes Circuit Breaker Module Size Catalog Number 1 = 80 mm Column Width (mm)(2) Column Depth (mm)(3) 150 140U-J*H3-D16 2 700, 800, 900, 1000 600, 800 250 140U-J*H3-D25 4 (1) 700, 800, 900, 1000 600, 800 400 140U-L*H3-D40 8 (1) 700, 800, 900, 1000 600, 800 600 140U-L*H3-D60 8(1) 700, 800, 900, 1000 600, 800 800 140U-M*H3-D80 (1) 700, 800, 900, 1000 600, 800 1200 140U-N*H3-E12 700, 800, 900, 1000 600, 800 8 (1) 12 (1) Fixed mount style (2) Available column widths (3) Available column depths Main Unit Options • • • • • Auxiliary contact for circuit breaker Shunt trip coil for circuit breaker Alarm contact for circuit breaker Minimum voltage coil (undervoltage) for circuit breaker Combination auxiliary contact and alarm contact for circuit breaker 37 Feeders, Air Circuit Breakers Amperes Circuit Breaker Catalog Number Module Size (1) 1 = 80 mm Column Width (mm)(3) Column Depth (mm)(4) 800 140RX-NS**D-D80 24(2) 700 600, 800 1250 140RX-NS**D-E12 24(2) 700 600, 800 1600 140RX-NS**D-E16 24 (2) 700 600, 800 2000 140RX-RS**D-E20 24 (2) 800 800 2500 140RX-RS**D-E25 24(2) 800 800 3200 140RX-SS**D-E32 24 (2) 900 800 4000 140RX-SS**D-E40 24 (2) 900 800 (1) (2) (3) (4) To complete the catalog numbers, please contact the factory Fixed mount style Available column widths Available column depths Feeders, Thermal Magnetic Amperes Circuit Breaker Module Size Catalog Number 1 = 80 mm Column Width (mm)(2) Column Depth (mm)(3) 10 140M-C2E-C10 1 700, 800, 900, 1000 600, 800 16 140M-D8E-C16 1 700, 800, 900, 1000 600, 800 20 140M-D8E-C20 1 700, 800, 900, 1000 600, 800 25 140M-D8E-C25 1 700, 800, 900, 1000 600, 800 30 140M-F8E-C32 2 700, 800, 900, 1000 600, 800 35 140M-F8E-C45 2 700, 800, 900, 1000 600, 800 40 140M-F8E-C45 2 700, 800, 900, 1000 600, 800 45 140M-F8E-C45 2 700, 800, 900, 1000 600, 800 50 140U-H*C3-C50 2 700, 800, 900, 1000 600, 800 60 140U-H*C3-C60 2 700, 800, 900, 1000 600, 800 70 140U-H*C3-C70 2 700, 800, 900, 1000 600, 800 80 140U-H*C3-C80 2 700, 800, 900, 1000 600, 800 90 140U-H*C3-C90 2 700, 800, 900, 1000 600, 800 100 140U-H*C3-D10 2 700, 800, 900, 1000 600, 800 110 140U-H*C3-D11 2 700, 800, 900, 1000 600, 800 125 140U-H*C3-D12 2 700, 800, 900, 1000 600, 800 150 140U-J*D3-D15 2 700, 800, 900, 1000 600, 800 175 140U-J*D3-D17 2 700, 800, 900, 1000 600, 800 200 140U-J*D3-D20 2 700, 800, 900, 1000 600, 800 225 140U-J*D3-D22 2 700, 800, 900, 1000 600, 800 250 140U-J*D3-D25 (1) 700, 800, 900, 1000 600, 800 300 140U-L*D3-D30 (1) 700, 800, 900, 1000 600, 800 350 140U-L*D3-D35 (1) 8 700, 800, 900, 1000 600, 800 400 140U-L*D3-D40 8(1) 700, 800, 900, 1000 600, 800 500 140U-L*D3-D50 (1) 700, 800, 900, 1000 600, 800 600 140U-L*D3-D60 (1) 700, 800, 900, 1000 600, 800 38 4 8 8 8 Feeders, Thermal Magnetic Amperes Circuit Breaker Module Size Catalog Number 1 = 80 mm 700 140U-M*D3-D70 800 140U-M*D3-D80 1200 140U-N*H3-E12 Column Width (mm)(2) Column Depth (mm)(3) 8 (1) 700, 800, 900, 1000 600, 800 8 (1) 700, 800, 900, 1000 600, 800 700, 800, 900, 1000 600, 800 (1) 12 (1) Fixed mount style (2) Available column widths (3) Available column depths Feeders, Electronic with LSI Protection Type Amperes Circuit Breaker Module Size Catalog Number 1 = 80 mm Column Width (mm)(2) Column Depth (mm)(3) 150 140U-J*H3-D16 2 700, 800, 900, 1000 600, 800 250 140U-J*H3-D25 4(1) 700, 800, 900, 1000 600, 800 400 140U-L*H3-D40 8 (1) 700, 800, 900, 1000 600, 800 600 140U-L*H3-D60 8(1) 700, 800, 900, 1000 600, 800 800 140U-M*H3-D80 (1) 700, 800, 900, 1000 600, 800 1200 140U-N*H3-E12 700, 800, 900, 1000 600, 800 8 (1) 12 (1) Fixed mount style (2) Available column widths (3) Available column depths Feeder Unit Options • • • • • Auxiliary contact for circuit breaker Shunt trip coil for circuit breaker Alarm contact for circuit breaker Minimum voltage coil (undervoltage) for circuit breaker Combination auxiliary contact and alarm contact for circuit breaker 39 Starter Units Direct On Line Non-reversing Starter Units These combination direct on line non-reversing starter units are supplied with Allen-Bradley Bulletin 100C or 100D contactors and either a fusible or circuit breaker disconnect. These units are available with a E1 Plus or E3 Plus overload relay and available with or without an external reset button for the overload relay. These units are available in a withdrawable unit style and a fixed unit style. For direct on line non-reversing starter unit selection, go to page . For direct on line non -reversing starter option selection, go to page . Direct On Line Non-reversing Starter Units Motor Rating Circuit Breaker Non-reversing Contactor Electronic Overload Relay Module Size Input Voltage kW(1) Cat. No.(2) Cat. No.(2) E1 Plus Cat. No.(3) E3 Plus Cat. No. 1 = 80 mm 380/415V 0.8 140M-C2N-*** 100-C16*10 193-EECB --- 1 0.8 140M-C2N-*** 100-C16*10 --- 193-EC2AB 3 140M-D8N-*** 100-C16*10 193-EEDB --- 3 140M-D8N-*** 100-C16*10 --- 193-EC2BB 5.5 140M-D8N-*** 100-C16*10 193-EEDB --- 5.5 140M-D8N-*** 100-C16*10 --- 193-EC2BB 7.5 140M-D8N-*** 100-C16*10 193-EEEB --- 7.5 140M-D8N-*** 100-C16*10 --- 193-EC2CB 11 140M-D8N-*** 100-C23*10 193-EEEB --- 11 140M-D8N-*** 100-C23*10 --- 193-EC2CB 15 140M-F8N-*** 100-C37*10 193-EEFD --- 15 140M-F8N-*** 100-C37*10 --- 193-EC2DD 18.5 140M-H8P-*** 100-C37*10 193-EEFD --- 18.5 140M-H8P-*** 100-C37*10 --- 193-EC2DD 22 140M-H8P-*** 100-C85*10 193-EEGE --- 22 140M-H8P-*** 100-C85*10 --- 193-EC2EE 37 140M-H8P-*** 100-C85*10 193-EEGE --- 37 140M-H8P-*** 100-C85*10 --- 193-EC2EE 45 140M-H8P-*** 100-C85*10 193-EEGE --- 45 140M-H8P-*** 100-C85*10 --- 193-EC2EE 75 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10 75 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10 90 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10 90 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10 110 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10 110 140M-J8P-*** 100-D210*11 --- 193-EC3HG 193-CBCT4 10 160 140M-L8P-*** 100-D300*11 193-EELG --- --- 12(4) 160 140M-L8P-*** 100-D300*11 --- 193-EC3HG 193-CBCT4 12(4) 185 140M-L8P-*** 100-D420*11 193-EELG --- --- 14(4) 185 140M-L8P-*** 100-D420*11 --- 193-EC3JG 193-CBCT4 14(4) IP20/42/54 (1) (2) (3) (4) 40 --- 1 --- 1 1 --- 1 1 --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 4 4 --- 4 4 --- 4 4 220 140M-L8P-*** 100-D420*11 193-EELG --- --- 14(4) 220 140M-L8P-*** 100-D420*11 --- 193-EC3JG 193-CBCT4 14(4) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Fixed mount style Direct On Line Non-reversing Starter Units (continued) Motor Rating Circuit Breaker Non-reversing Contactor Electronic Overload Relay Cat. No.(2) Cat. No.(2) E1 Plus Cat. No.(3) E3+ Cat. No. Input Voltage kW(1) 440/460/480V 0.75 140M-C2N-*** 100-C16*10 193-EECB --- IP20/42/54 0.75 140M-C2N-*** 100-C16*10 --- 193-EC2AB 3 140M-D8N-*** 100-C16*10 193-EEDB --- 3 140M-D8N-*** 100-C16*10 --- 193-EC2BB 5.5 140M-D8N-*** 100-C16*10 193-EEDB --- 5.5 140M-D8N-*** 100-C16*10 --- 193-EC2BB 7.5 140M-D8N-*** 100-C16*10 193-EEEB --- 7.5 140M-D8N-*** 100-C16*10 --- 193-EC2CB (1) (2) (3) (4) Module Size 11 140M-D8N-*** 100-C23*10 193-EEEB --- 11 140M-D8N-*** 100-C23*10 --- 193-EC2CB 15 140M-F8N-*** 100-C37*10 193-EEFD --- 15 140M-F8N-*** 100-C37*10 --- 193-EC2DD 18.5 140M-F8N-*** 100-C37*10 193-EEFD --- 18.5 140M-F8N-*** 100-C37*10 --- 193-EC2DD 22 140M-H8P-*** 100-C43*10 193-EEFD --- 22 140M-H8P-*** 100-C43*10 --- 193-EC2DD 37 140M-H8P-*** 100-C85*10 193-EEGE --- 37 140M-H8P-*** 100-C85*10 --- 193-EC2EE 45 140M-H8P-*** 100-C85*10 193-EEGE --- 45 140M-H8P-*** 100-C85*10 --- 193-EC2EE 1 = 80 mm --- 1 1 --- 1 1 --- 1 1 --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 4 4 --- 4 4 --- 4 4 75 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10 75 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10 90 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10 90 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10 110 140M-J8P-*** 100-D210*11 193-EEJG --- --- 10 110 140M-J8P-*** 100-D210*11 --- 193-EC3GG 193-CBCT4 10 160 140M-L8P-*** 100-D300*11 193-EELG --- --- 12(4) 160 140M-L8P-*** 100-D300*11 --- 193-EC3HG 193-CBCT4 12(4) 185 140M-L8P-*** 100-D300*11 193-EELG --- --- 12(4) 185 140M-L8P-*** 100-D300*11 --- 193-EC3JG 193-CBCT4 12(4) 220 140M-L8P-*** 100-D420*11 193-EELG --- --- 14(4) 220 140M-L8P-*** 100-D420*11 --- 193-EC3JG 193-CBCT4 14(4) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Fixed mount style 41 Direct On Line Non-reversing Starter Unit Options • • • • • • Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test • Selector switch – Two position – Three position • DeviceNet starter auxiliary – (4) 120V AC inputs and (2) 120V AC outputs – (4) 24V DC inputs and (2) 120V AC outputs • Back-up DeviceNet power supply 42 Direct On Line Reversing Starter Units These combination direct on line reversing starter units are supplied with Allen-Bradley Bulletin 104C or 104D contactors and either a fusible or circuit breaker disconnect. The starters are mechanically and electrically interlocked to avoid both contactors being closed simultaneously. These units are available with an E1 Plus or E3 Plus overload relay and available with or without an external reset button for the overload relay. These units are available in a withdrawable unit style and a fixed unit style. Direct On Line Reversing Starter Units Motor Rating Circuit Breaker Reversing Contactor Electronic Overload Relay Input Voltage kW(1) Cat. No.(2) Cat. No.(2) E1 Plus Cat. No.(3) E3 Plus Cat. No. 380/415V 0.8 140M-C2N-*** 104-C16*22 193-EECB --- IP20/42/54 0.8 140M-C2N-*** 104-C16*22 --- 193-EC2AB 3 140M-D8N-*** 104-C16*22 193-EEDB --- 3 140M-D8N-*** 104-C16*22 --- 193-EC2BB 5.5 140M-D8N-*** 104-C16*22 193-EEDB --- (1) (2) (3) (4) 5.5 140M-D8N-*** 104-C16*22 --- 193-EC2BB 7.5 140M-D8N-*** 104-C16*22 193-EEEB --- 7.5 140M-D8N-*** 104-C16*22 --- 193-EC2CB 11 140M-D8N-*** 104-C23*22 193-EEEB --- 11 140M-D8N-*** 104-C23*22 --- 193-EC2CB 15 140M-F8N-*** 104-C37*22 193-EEFD --- 15 140M-F8N-*** 104-C37*22 --- 193-EC2DD 18.5 140M-H8P-*** 104-C37*22 193-EEFD --- 18.5 140M-H8P-*** 104-C37*22 --- 193-EC2DD 22 140M-H8P-*** 104-C85*22 193-EEGE --- 22 140M-H8P-*** 104-C85*22 --- 193-EC2EE 37 140M-H8P-*** 104-C85*22 193-EEGE --- 37 140M-H8P-*** 104-C85*22 --- 193-EC2EE 45 140M-H8P-*** 104-C85*22 193-EEGE --- 45 140M-H8P-*** 104-C85*22 --- 193-EC2EE 75 140M-J8P-*** 104-D210*24 193-EEJG --- 75 140M-J8P-*** 104-D210*24 --- 90 140M-J8P-*** 104-D210*24 193-EEJG 90 140M-J8P-*** 104-D210*24 110 140M-J8P-*** 110 160 Module Size 1 = 80 mm --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 4 4 --- 4 4 --- 4 4 --- 10 193-EC3GG 193-CBCT4 10 --- --- 10 --- 193-EC3GG 193-CBCT4 10 104-D210*24 193-EEJG --- --- 10 140M-J8P-*** 104-D210*24 --- 193-EC3HG 193-CBCT4 10 140M-L8P-*** 104-D300*24 193-EELG --- --- 14(4) 160 140M-L8P-*** 104-D300*24 --- 193-EC3HG 193-CBCT4 14(4) 185 140M-L8P-*** 104-D420*24 193-EELG --- --- 14(4) 185 140M-L8P-*** 104-D420*24 --- 193-EC3JG 193-CBCT4 14(4) 220 140M-L8P-*** 104-D420*24 193-EELG --- --- 14(4) 220 140M-L8P-*** 104-D420*24 --- 193-EC3JG 193-CBCT4 14(4) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Fixed mount style 43 Direct On Line Reversing Starter Units (continued) Motor Rating Circuit Breaker Reversing Contactor Electronic Overload Relay Cat. No.(2) Cat. No.(2) E1 Plus Cat. No.(3) E3 Plus Cat. No. Input Voltage kW(1) 440/460/480V 0.75 140M-C2N-*** 104-C16*22 193-EECB --- IP20/42/54 0.75 140M-C2N-*** 104-C16*22 --- 193-EC2AB 3 140M-D8N-*** 104-C16*22 193-EEDB --- 3 140M-D8N-*** 104-C16*22 --- 193-EC2BB (1) (2) (3) (4) 44 Module Size 5.5 140M-D8N-*** 104-C16*22 193-EEDB --- 5.5 140M-D8N-*** 104-C16*22 --- 193-EC2BB 7.5 140M-D8N-*** 104-C16*22 193-EEEB --- 7.5 140M-D8N-*** 104-C16*22 --- 193-EC2CB 1 = 80 mm --- 2 2 --- 2 2 --- 2 2 --- 2 2 --- 2 11 140M-D8N-*** 104-C23*22 193-EEEB --- 11 140M-D8N-*** 104-C23*22 --- 193-EC2CB 15 140M-F8N-*** 104-C37*22 193-EEFD --- 15 140M-F8N-*** 104-C37*22 --- 193-EC2DD 18.5 140M-F8N-*** 104-C37*22 193-EEFD --- 18.5 140M-F8N-*** 104-C37*22 --- 193-EC2DD 22 140M-H8P-*** 104-C43*22 193-EEFD --- 22 140M-H8P-*** 104-C43*22 --- 193-EC2DD 37 140M-H8P-*** 104-C85*22 193-EEGE --- 37 140M-H8P-*** 104-C85*22 --- 193-EC2DD 45 140M-H8P-*** 104-C85*22 193-EEGE --- 45 140M-H8P-*** 104-C85*22 --- 193-EC2EE 75 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10 75 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10 90 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10 90 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10 110 140M-J8P-*** 104-D210*24 193-EEJG --- --- 10 110 140M-J8P-*** 104-D210*24 --- 193-EC3GG 193-CBCT4 10 160 140M-L8P-*** 104-D300*24 193-EELG --- --- 14(4) 160 140M-L8P-*** 104-D300*24 --- 193-EC3HG 193-CBCT4 14(4) 185 140M-L8P-*** 104-D300*24 193-EELG --- --- 14(4) 185 140M-L8P-*** 104-D300*24 --- 193-EC3JG 193-CBCT4 14(4) 220 140M-L8P-*** 104-D420*24 193-EELG --- --- 14(4) 220 140M-L8P-*** 104-D420*24 --- 193-EC3JG 193-CBCT4 14(4) 2 --- 2 2 --- 2 2 --- 4 4 --- 4 4 --- 4 4 Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Fixed mount style Direct On Line Reversing Starter Unit Options • • • • • • Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test • Selector switch – Two position – Three position • DeviceNet starter auxiliary – (4) 120V AC inputs and (2) 120V AC outputs – (4) 24V DC inputs and (2) 120V AC outputs • Back-up DeviceNet power supply 45 Soft Starter Units Soft staters, referred to as reduced voltage solid state units, contain a microprocessor-controlled motor controller, control circuit transformer and either a fusible or circuit breaker disconnect. These units are available as withdrawable or fixed units. The following soft starters are available for CENTERLINE 2500 MCC’s: • SMC-3 soft starter • SMC Flex soft starter SMC-3 Soft Starters features: • Three starting modes: soft start, kick start and current limit • Electronic overload protection with selectable overload trip class • Motor and system diagnostics • Soft stop • Integrated bypass contactor SMC Flex Soft Starters features: • Seven standard modes of operation: soft start, current limit start, dual ramp, full voltage, linear speed acceleration, preset slow speed and soft stop • Optional modes of operation: pump control, Smart Motor BrakingTM, Accu-StopTM and slow speed with braking • Integral SCR bypass • Electronic overload protection with selectable overload trip class • Full metering and diagnostics • DPI communication For soft starter unit selection, go to page . For soft starter option selection, go to page . 46 One Line Diagram SMC-3 Soft Starter Units Motor Rating Input Voltage kW(1) Circuit Breaker SMC-3 High Interrupting Capacity Fuses Module Size Cat. No.(2) Cat. No.(2) Cat. No.(3) 1 = 80 mm 380/415V, 0.75 140M-C2N-*** 150-C3NBD --- 1 IP20/42/54 0.75 140M-C2N-*** 150-C3NBD 4A, SIZE 000 6 1.1 140M-D8N-*** 150-C3NBD --- 1 1.1 140M-D8N-*** 150-C3NBD 4A, SIZE 000 6 4 140M-D8N-*** 150-C9NBD --- 1 4 140M-D8N-*** 150-C9NBD 16A, SIZE 000 6 7.5 140M-D8N-*** 150-C19NBD --- 2 (1) (2) (3) (4) 7.5 140M-D8N-*** 150-C19NBD 20A, SIZE 000 6 11 140M-D8N-*** 150-C25NBD --- 2 11 140M-D8N-*** 150-C25NBD 40A, SIZE 000 6 15 140M-F8P-*** 150-C30NBD --- 2 15 140M-F8P-*** 150-C30NBD 40A, SIZE 000 6 18.5 140M-H8P-*** 150-C37NBD --- 2 18.5 140M-H8P-*** 150-C37NBD 50A, SIZE 000 6 22 140M-H8P-*** 150-C43NBD --- 4 22 140M-H8P-*** 150-C43NBD 63A, SIZE 000 6 30 140M-H8P-*** 150-C60NBD --- 4 30 140M-H8P-*** 150-C60NBD 80A, SIZE 00 6 45 140M-H8P-*** 150-C85NBD --- 4 45 140M-H8P-*** 150-C85NBD 125A, SIZE 00 6 55 140M-J8P-*** 150-C108NBD --- 12(4) 55 140M-J8P-*** 150-C108NBD 125A, SIZE 00 12(4) 75 140M-J8P-*** 150-C135NBD --- 12(4) 75 140M-J8P-*** 150-C135NBD 200A, SIZE 1 12(4) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ High interrupting capacity fuses are optional Fixed mount style 47 SMC-3 Soft Starter Units (continued) Motor Rating Circuit Breaker SMC-3 High Interrupting Capacity Fuses Module Size Cat. No.(2) Cat. No.(2) Cat. No.(3) 1 = 80 mm Input Voltage kW(1) 440/460/480V, 0.75 140M-C2N-*** 150-C3NBD --- 1 IP20/42/54 0.75 140M-C2N-*** 150-C3NBD 4A, SIZE 000 6 1.1 140M-D8N-*** 150-C3NBD --- 1 1.1 140M-D8N-*** 150-C3NBD 4A, SIZE 000 6 4 140M-D8N-*** 150-C9NBD --- 1 4 140M-D8N-*** 150-C9NBD 16A, SIZE 000 6 7.5 140M-D8N-*** 150-C19NBD --- 2 7.5 140M-D8N-*** 150-C19NBD 20A, SIZE 000 6 (1) (2) (3) (4) 48 11 140M-D8N-*** 150-C25NBD --- 2 11 140M-D8N-*** 150-C25NBD 40A, SIZE 000 6 15 140M-F8P-*** 150-C30NBD --- 2 15 140M-F8P-*** 150-C30NBD 40A, SIZE 000 6 18.5 140M-H8P-*** 150-C37NBD --- 2 18.5 140M-H8P-*** 150-C37NBD 50A, SIZE 000 6 22 140M-H8P-*** 150-C43NBD --- 4 22 140M-H8P-*** 150-C43NBD 63A, SIZE 000 6 30 140M-H8P-*** 150-C60NBD --- 4 30 140M-H8P-*** 150-C60NBD 80A, SIZE 00 6 45 140M-H8P-*** 150-C85NBD --- 4 45 140M-H8P-*** 150-C85NBD 125A, SIZE 00 6 55 140M-J8P-*** 150-C108NBD --- 12(4) 55 140M-J8P-*** 150-C108NBD 125A, SIZE 00 12(4) 75 140M-J8P-*** 150-C135NBD --- 12(4) 75 140M-J8P-*** 150-C135NBD 200A, SIZE 1 12(4) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ High interrupting capacity fuses are optional Fixed mount style SMC-3 Soft Starter Unit Options • • • • • • • • • • • • • Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test Selector switch – Two position – Three position DeviceNet starter auxiliary – (4) 120VAC inputs and (2) 120VAC outputs – (4) 24VDC inputs and (2) 120VAC outputs DeviceNet communication module, mounted internal to Solid State Starter Isolation contactor Human interface module – Blank cover, no functionality, door mounted in bezel – LCD display, full numeric keypad, door mounted in bezel – LCD display, programmer only, door mounted in bezel Pump control, provides pump start and stop Braking control, provides Smart Motor braking, Accu-Stop and Slow Speed braking 49 SMC Flex Soft Starter Units Motor Rating Circuit Breaker SMC Flex High Interrupting Capacity Fuses Module Size Input Voltage kW(1) Cat. No.(2) Cat. No.(2) Cat. No.(3) 1 = 80 mm 380/415V, 0.75 140M-C2N-*** 150-F5NBD --- 8 0.75 140M-C2N-*** 150-F5NBD 4A, SIZE 000 8 2.2 140M-D8N-*** 150-F5NBD --- 8 2.2 140M-D8N-*** 150-F5NBD 6A, SIZE 000 8 4 140M-D8N-*** 150-F25NBD --- 8 4 140M-D8N-*** 150-F25NBD 16A, SIZE 000 8 7.5 140M-D8N-*** 150-F25NBD --- 8 7.5 140M-D8N-*** 150-F25NBD 20A, SIZE 000 8 11 140M-D8N-*** 150-F25NBD --- 8 11 140M-D8N-*** 150-F25NBD 40A, SIZE 000 8 15 140M-F8P-*** 150-F43NBD --- 8 15 140M-F8P-*** 150-F43NBD 40A, SIZE 000 8 22 140M-H8P-*** 150-F43NBD --- 8 22 140M-H8P-*** 150-F43NBD 63A, SIZE 000 8 30 140M-H8P-*** 150-F60NBD --- 8 30 140M-H8P-*** 150-F60NBD 80A, SIZE 00 8 45 140M-H8P-*** 150-F85NBD --- 8 45 140M-H8P-*** 150-F85NBD 125A, SIZE 00 8 55 140M-J8P-*** 150-F108NBD --- 12(4) 55 140M-J8P-*** 150-F108NBD 125A, SIZE 00 12(4) IP20/42/54 (1) (2) (3) (4) (5) 50 75 140M-J8P-*** 150-F201NBD --- 24(5) 75 140M-J8P-*** 150-F201NBD 200A, SIZE 1 24(5) 90 140M-J8P-*** 150-F201NBD --- 24(5) 90 140M-J8P-*** 150-F201NBD 250A, SIZE 1 24(5) 110 140M-J8P-*** 150-F251NBD --- 24(5) 110 140M-J8P-*** 150-F251NBD 355A, SIZE 2 24(5) 132 140M-L8P-*** 150-F251NBD --- 24(5) 132 140M-L8P-*** 150-F251NBD 355A, SIZE 2 24(5) 160 140M-L8P-*** 150-F317NBD --- 24(5) 160 140M-L8P-*** 150-F317NBD 500A, SIZE 3 24(5) 185 140M-L8P-*** 150-F361NBD --- 24(5) 185 140M-L8P-*** 150-F361NBD 500A, SIZE 3 24(5) 220 140M-L8P-*** 150-F480NBD --- 24(5) 220 140M-L8P-*** 150-F480NBD 630A, SIZE 3 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ High interrupting capacity fuses are optional Fixed mount style 600 mm wide column SMC Flex Soft Starter Units Motor Rating Circuit Breaker SMC Flex High Interrupting Capacity Fuses Module Size Input Voltage kW(1) Cat. No.(2) Cat. No.(2) Cat. No.(3) 1 = 80 mm 440/460/480V, 0.75 140M-C2N-*** 150-F5NBD --- 8 0.75 140M-C2N-*** 150-F5NBD 4A, SIZE 000 8 2.2 140M-D8N-*** 150-F5NBD --- 8 2.2 140M-D8N-*** 150-F5NBD 6A, SIZE 000 8 4 140M-D8N-*** 150-F25NBD --- 8 4 140M-D8N-*** 150-F25NBD 16A, SIZE 000 8 7.5 140M-D8N-*** 150-F25NBD --- 8 7.5 140M-D8N-*** 150-F25NBD 20A, SIZE 000 8 11 140M-D8N-*** 150-F25NBD --- 8 11 140M-D8N-*** 150-F25NBD 40A, SIZE 000 8 15 140M-F8P-*** 150-F43NBD --- 8 15 140M-F8P-*** 150-F43NBD 40A, SIZE 000 8 22 140M-H8P-*** 150-F43NBD --- 8 22 140M-H8P-*** 150-F43NBD 63A, SIZE 000 8 30 140M-H8P-*** 150-F60NBD --- 8 30 140M-H8P-*** 150-F60NBD 80A, SIZE 00 8 45 140M-H8P-*** 150-F85NBD --- 8 45 140M-H8P-*** 150-F85NBD 125A, SIZE 00 8 55 140M-J8P-*** 150-F108NBD --- 12(4) 55 140M-J8P-*** 150-F108NBD 125A, SIZE 00 12(4) 75 140M-J8P-*** 150-F135NBD --- 12(4) 75 140M-J8P-*** 150-F135NBD 200A, SIZE 1 12(4) 90 140M-J8P-*** 150-F201NBD --- 24(5) 90 140M-J8P-*** 150-F201NBD 250A, SIZE 1 24(5) 110 140M-J8P-*** 150-F201NBD --- 24(5) 110 140M-J8P-*** 150-F201NBD 355A, SIZE 2 24(5) 132 140M-L8P-*** 150-F251NBD --- 24(5) 132 140M-L8P-*** 150-F251NBD 355A, SIZE 2 24(5) 160 140M-L8P-*** 150-F317NBD --- 24(5) 160 140M-L8P-*** 150-F317NBD 500A, SIZE 3 24(5) IP20/42/54 (1) (2) (3) (4) (5) 185 140M-L8P-*** 150-F361NBD --- 24(5) 185 140M-L8P-*** 150-F361NBD 500A, SIZE 3 24(5) 220 140M-L8P-*** 150-F480NBD --- 24(5) 220 140M-L8P-*** 150-F480NBD 630A, SIZE 3 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ High interrupting capacity fuses are optional Fixed mount style 600 mm wide column 51 SMC Flex Soft Starter Unit Options • • • • • • • • • • • • • 52 Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test Selector switch – Two position – Three position DeviceNet starter auxiliary – (4) 120VAC inputs and (2) 120VAC outputs – (4) 24VDC inputs and (2) 120VAC outputs DeviceNet communication module, mounted internal to Solid State Starter Isolation contactor Human interface module – Blank cover, no functionality, door mounted in bezel – LCD display, full numeric keypad, door mounted in bezel – LCD display, programmer only, door mounted in bezel Pump control, provides pump start and stop Braking control, provides Smart Motor braking, Accu-Stop and Slow Speed braking Variable Frequency Drive Units PowerFlex® Variable Frequency AC Drives The combination variable frequency AC drive units are specifically designed for use in the CENTERLINE 2500 Motor Control Centers. Each unit contains a variable frequency AC drive and either a fusible disconnect switch or circuit breaker. These units are available in a withdrawable unit style and a fixed unit style. Available models include: • PowerFlex 40 Variable Frequency AC drive • PowerFlex 70 Variable Frequency AC drive • PowerFlex 700 Variable Frequency AC drive PowerFlex drive features include: • Isolated logic and power • Produce a three-phase, pulse width modulated (PWM) adjustable frequency output and voltage output for exceptional control of motor speed and torque • Are digitally programmed with access to mode programming, providing precise and repeatedly accurate setup, control and operation, and adaptability to handle a variety of applications One Line Diagram For drive unit selection go to page . For drive unit option selection go to page . PowerFlex 40 Variable Frequency Drive Units Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size Cat. No. Cat. No. 1 = 80 mm 22B-D1P4N104 --- 4 22B-D1P4N104 1321-3R2-B 6 22B-D2P3N104 --- 4 22B-D2P3N104 1321-3R4-C 6 140M-D8N-*** 22B-D4P0N104 --- 4 1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6 2.2 140M-D8N-*** 22B-D6P0N104 --- 4 2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6 3.7 140M-D8N-*** 22B-D010N104 --- 4 3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6 5.5 140M-D8N-*** 22B-D012N104 --- 8 5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 8 7.5 140M-D8N-*** 22B-D017N104 --- 8 7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 8 11 140M-D8N-*** 22B-D024N104 --- 8 11 140M-D8N-*** 22B-D024N104 1321-3R25-B 8 Input Voltage kW 380/415V, 0.37 IP20 0.37 140M-C2N-*** 0.75 140M-C2N-*** 0.75 140M-C2N-*** 1.5 (1) Cat. No. (2) 140M-C2N-*** (3) (1) Approximate range of kilowatt ratings (2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ (3) Line or load reactors are optional 53 PowerFlex 40 Variable Frequency Drive Units (continued) Motor Rating Circuit Breaker PowerFlex 40 VFD Module Size 1 = 80 mm 22B-D1P4N104 --- 6 22B-D1P4N104 1321-3R2-B 6 22B-D2P3N104 --- 6 140M-C2N-*** 22B-D2P3N104 1321-3R4-C 6 140M-D8N-*** 22B-D4P0N104 --- 6 1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6 2.2 140M-D8N-*** 22B-D6P0N104 --- 6 2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6 3.7 140M-D8N-*** 22B-D010N104 --- 6 3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6 5.5 140M-D8N-*** 22B-D012N104 --- 10 5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 10 7.5 140M-D8N-*** 22B-D017N104 --- 10 7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 10 11 140M-D8N-*** 22B-D024N104 --- 10 11 140M-D8N-*** 22B-D024N104 1321-3R25-B 10 kW 380/415V, 0.37 140M-C2N-*** IP42/54 0.37 140M-C2N-*** 0.75 140M-C2N-*** 0.75 1.5 (1) (2) Cat. No. Cat. No. Reactor Cat. No. Input Voltage (3) (1) Approximate range of kilowatt ratings (2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ (3) Line or load reactors are optional 54 PowerFlex 40 Variable Frequency Drive Units (continued) Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size Cat. No. Cat. No. 1 = 80 mm 140M-C2N-*** 22B-D1P4N104 --- 4 140M-C2N-*** 22B-D1P4N104 1321-3R2-B 6 140M-C2N-*** 22B-D2P3N104 --- 4 0.75 140M-C2N-*** 22B-D2P3N104 1321-3R4-C 6 1.5 140M-D8N-*** 22B-D4P0N104 --- 4 1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6 2.2 140M-D8N-*** 22B-D6P0N104 --- 4 2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6 3.7 140M-D8N-*** 22B-D010N104 --- 4 3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6 5.5 140M-D8N-*** 22B-D012N104 --- 8 5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 8 7.5 140M-D8N-*** 22B-D017N104 --- 8 7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 8 11 140M-D8N-*** 22B-D024N104 --- 8 11 140M-D8N-*** 22B-D024N104 1321-3R25-B 8 Input Voltage kW 440/460/480V, 0.37 IP20 0.37 0.75 (1) Cat. No. (2) (3) (1) Approximate range of kilowatt ratings (2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ (3) Line or load reactors are optional 55 PowerFlex 40 Variable Frequency Drive Units (continued) Motor Rating Circuit Breaker PowerFlex 40 VFD Reactor Module Size Cat. No.(2) Cat. No. Cat. No.(3) 1 = 80 mm 22B-D1P4N104 --- 6 22B-D1P4N104 1321-3R2-B 6 22B-D2P3N104 --- 6 22B-D2P3N104 1321-3R4-C 6 Input Voltage kW(1) 440/460/480V, 0.37 140M-C2N-*** IP42/54 0.37 140M-C2N-*** 0.75 140M-C2N-*** 0.75 140M-C2N-*** 1.5 140M-D8N-*** 22B-D4P0N104 --- 6 1.5 140M-D8N-*** 22B-D4P0N104 1321-3R4-B 6 2.2 140M-D8N-*** 22B-D6P0N104 --- 6 2.2 140M-D8N-*** 22B-D6P0N104 1321-3R8-C 6 3.7 140M-D8N-*** 22B-D010N104 --- 6 3.7 140M-D8N-*** 22B-D010N104 1321-3R8-B 6 5.5 140M-D8N-*** 22B-D012N104 --- 10 5.5 140M-D8N-*** 22B-D012N104 1321-3R12-B 10 7.5 140M-D8N-*** 22B-D017N104 --- 10 7.5 140M-D8N-*** 22B-D017N104 1321-3R18-B 10 11 140M-D8N-*** 22B-D024N104 --- 10 11 140M-D8N-*** 22B-D024N104 1321-3R25-B 10 (1) Approximate range of kilowatt ratings (2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ (3) Line or load reactors are optional 56 PF40 Drive Unit Options • • • • • • • • • • • • • Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test Selector switch – Two position – Three positio DeviceNet starter auxiliary – (4) 120VAC inputs and (2) 120V AC outputs – (4) 24VDC inputs and (2) 120V AC outputs DeviceNet communication module, mounted internal to Solid State Starter ControlNet communication module, mounted internal to drive Isolation contactor Human interface module – Blank cover, no functionality, door mounted in bezel – LCD display, full numeric keypad, door mounted in bezel – LCD display, programmer only, door mounted in bezel I/O control interface type – 24V DC control voltage interface with vector control – 120V AC control voltage interface with vector control – 24V DC control voltage interface with sensorless vector control – 120V AC control voltage interface with sensorless vector control 57 PowerFlex 70 Variable Frequency Drive Units (Normal Duty) Motor Rating Input Voltage Circuit Breaker kW (1) PowerFlex 70 VFD Isolation Contactor Cat. No. Cat. No. Cat. No. (2) (2) Reactor Module Size Cat. No. 1 = 80 mm (3) 380/415V, 0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 --- 6 IP20 0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 1321-3R2-B 8 0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 --- 6 0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 1321-3R2-B 8 1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 --- 6 1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 1321-3R4-B 8 2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 --- 6 2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 1321-3R4-B 8 3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 --- 6 3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 1321-3R8-B 8 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 8 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 10 7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 --- 8 7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 1321-3R18-B 10 11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 --- 10 11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 1321-3R25-B 10 15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 --- 10 15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 1321-3R35-B 10 18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 --- 10 (1) (2) (3) (4) 58 18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 1321-3R35-B 10 22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 --- 10 22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 1321-3R45-B 10 30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 --- 14(4) 30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 1321-3R55-B 14(4) 37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 --- 14(4) 37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 1321-3R80-B 14(4) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Line or load reactors are optional Fixed mount style PowerFlex 70 Variable Frequency Drive Units (Normal Duty, continued) Motor Rating Input Voltage Circuit Breaker (1) kW Cat. No. (2) PowerFlex 70 VFD Cat. No. Isolation Contactor (2) Cat. No. Reactor Cat. No. (3) Module Size 1 = 80 mm 380/415V, 0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 --- 8 IP42/54 0.37 140M-C2N-*** 20AC1P3A0AYNANC0 100-C09*10 1321-3R2-B 10 0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 --- 8 0.75 140M-C2N-*** 20AC2P1A0AYNANC0 100-C09*10 1321-3R2-B 10 1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 --- 8 1.5 140M-D8N-*** 20AC3P5A0AYNANC0 100-C09*10 1321-3R4-B 10 2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 --- 8 2.2 140M-D8N-*** 20AC5P0A0AYNANC0 100-C09*10 1321-3R4-B 10 3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 --- 8 3.7 140M-D8N-*** 20AC8P7A0AYNANC0 100-C09*10 1321-3R8-B 10 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 12 (1) (2) (3) (4) (5) 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 12 7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 --- 12 7.5 140M-D8N-*** 20AC015A0AYNANC0 100-C23*10 1321-3R18-B 12 11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 --- 14(4) 11 140M-D8N-*** 20AC022A0AYNANC0 100-C37*10 1321-3R25-B 14(4) 15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 --- 14(4) 15 140M-F8N-*** 20AC030A0AYNANC0 100-C37*10 1321-3R35-B 14(4) 18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 --- 14(4) 18.5 140M-H8N-*** 20AC037A0AYNANC0 100-C43*10 1321-3R35-B 14(4) 22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 --- 14 (4) 22 140M-H8N-*** 20AC043A0AYNANC0 100-C85*10 1321-3R45-B 14(4) 30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 --- 16(4) 30 140M-H8N-*** 20AC060A0AYNANC0 100-C85*10 1321-3R55-B 24(5) 37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 --- 16(4) 37 140M-H8N-*** 20AC072A0AYNANC0 100-C85*10 1321-3R80-B 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Line or load reactors are optional Fixed mount style. 600 mm wide column 59 PowerFlex 70 Variable Frequency Drive Units (Normal Duty,continued) Motor Rating Input Voltage Circuit Breaker kW (1) PowerFlex 70 VFD Isolation Contactor Cat. No. Cat. No. Cat. No. (2) (2) Reactor Module Size Cat. No. 1 = 80 mm (3) 440/460/480V, 0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 --- 6 IP20 0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 1321-3R2-B 8 0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 --- 6 0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 1321-3R2-B 8 1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 --- 6 1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 1321-3R4-B 8 2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 --- 6 2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 1321-3R4-B 8 3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 --- 6 3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 1321-3R8-B 8 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 8 (1) (2) (3) (4) (5) 60 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 10 7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 --- 8 7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 1321-3R18-B 10 11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 --- 10 11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 1321-3R25-B 10 15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 --- 10 15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 1321-3R35-B 10 18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 --- 10 18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 1321-3R35-B 10 22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 --- 10 22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 1321-3R45-B 10 30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 --- 14(4) 30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 1321-3R55-B 24(5) 37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 --- 14(4) 37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 1321-3R80-B 24 (5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Line or load reactors are optional Fixed mount style 600 mm wide column PowerFlex 70 Variable Frequency Drive Units (Normal Duty, continued) Motor Rating Input Voltage kW(1) Circuit Breaker PowerFlex 70 VFD Isolation Contactor Reactor Module Size Cat. No.(2) Cat. No. Cat. No.(2) Cat. No.(3) 1 = 80 mm 440/460/480V, 0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 --- 8 IP42/54 0.37 140M-C2N-*** 20AD1P1A0AYNANC0 100-C09*10 1321-3R2-B 10 0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 --- 8 0.75 140M-C2N-*** 20AD2P1A0AYNANC0 100-C09*10 1321-3R2-B 10 (1) (2) (3) (4) (5) 1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 --- 8 1.5 140M-D8N-*** 20AD3P4A0AYNANC0 100-C09*10 1321-3R4-B 10 2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 --- 8 2.2 140M-D8N-*** 20AD5P0A0AYNANC0 100-C09*10 1321-3R4-B 10 3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 --- 8 3.7 140M-D8N-*** 20AD8P0A0AYNANC0 100-C09*10 1321-3R8-B 10 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 --- 12 5.5 140M-D8N-*** 20AD011A0AYNANC0 100-C16*10 1321-3R12-B 12 7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 --- 12 7.5 140M-D8N-*** 20AD014A0AYNANC0 100-C16*10 1321-3R18-B 12 11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 --- 14(4) 11 140M-D8N-*** 20AD022A0AYNANC0 100-C23*10 1321-3R25-B 14(4) 15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 --- 14(4) 15 140M-F8N-*** 20AD027A0AYNANC0 100-C37*10 1321-3R35-B 14(4) 18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 --- 14(4) 18.5 140M-F8N-*** 20AD034A0AYNANC0 100-C37*10 1321-3R35-B 14(4) 22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 --- 14(4) 22 140M-H8N-*** 20AD040A0AYNANC0 100-C43*10 1321-3R45-B 14(4) 30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 --- 16(4) 30 140M-H8N-*** 20AD052A0AYNANC0 100-C85*10 1321-3R55-B 24(5) 37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 --- 16(4) 37 140M-H8N-*** 20AD065A0AYNANC0 100-C85*10 1321-3R80-B 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/ Line or load reactors are optional Fixed mount style 600 mm wide column 61 PF70 Drive Unit Options • • • • • • • • • • • • • 62 Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test Selector switch – Two position – Three position DeviceNet starter auxiliary – (4) 120V AC inputs and (2) 120V AC outputs – (4) 24V DC inputs and (2) 120V AC outputs DeviceNet communication module, mounted internal to Solid State Starter ControlNet communication module, mounted internal to drive Isolation contactor Human interface module – Blank cover, no functionality, door mounted in bezel – LCD display, full numeric keypad, door mounted in bezel – LCD display, programmer only, door mounted in bezel I/O control interface type – 24V DC control voltage interface with vector control – 120V AC control voltage interface with vector control – 24V DC control voltage interface with sensorless vector control – 120V AC control voltage interface with sensorless vector control PowerFlex 700 Variable Frequency Drive Units (Normal Duty) Motor Rating Circuit Breaker Isolation Contactor Reactor Module Size Cat. No. Cat. No. 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 --- 8 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 1321-3R2-B 8 0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 --- 8 0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 1321-3R2-B 8 1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 --- 8 1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 1321-3R4-B 8 2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 --- 8 2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 1321-3R4-B 8 3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 --- 8 3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 1321-3R8-B 8 5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 --- 8 5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 1321-3R12-B 8 7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 --- 8 7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 1321-3R18-B 8 11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 --- 8 11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 1321-3R25-B 8 15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 --- 8 15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 1321-3R35-B 10 18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 --- 8 kW 380/415V, 0.37 IP20 0.37 (1) (2) (3) (4) (5) PowerFlex 40 VFD Cat. No. Input Voltage (1) Cat. No. (2) (2) (3) 1 = 80 mm 18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 1321-3R45-B 10 22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 --- 12 22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 1321-3R45-B 14(4) 37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 --- 12 37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 1321-3R80-B 14(4) 55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 --- 24(5) 55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 1321-3R130-B 24(5) 75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5) 75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R160-B 24(5) 90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5) 90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R200-B 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs Line or load reactors are optional Fixed mount style 600 mm wide column 63 PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued) Motor Rating Circuit Breaker Reactor Module Size Cat. No. Cat. No. 0.37 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 --- 8 0.37 140M-C2N-*** 20BC1P3A0AYNANC0 100-C09*10 1321-3R2-B 10 0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 --- 8 0.75 140M-C2N-*** 20BC2P1A0AYNANC0 100-C09*10 1321-3R2-B 10 1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 --- 8 1.5 140M-D8N-*** 20BC3P5A0AYNANC0 100-C09*10 1321-3R4-B 10 2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 --- 8 2.2 140M-D8N-*** 20BC5P0A0AYNANC0 100-C09*10 1321-3R4-B 10 3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 --- 8 3.7 140M-D8N-*** 20BC8P7A0AYNANC0 100-C09*10 1321-3R8-B 10 5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 --- 8 5.5 140M-D8N-*** 20BC011A0AYNANC0 100-C16*10 1321-3R12-B 10 7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 --- 8 7.5 140M-D8N-*** 20BC015A0AYNANC0 100-C23*10 1321-3R18-B 10 11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 --- 12 11 140M-D8N-*** 20BC022A0AYNANC0 100-C37*10 1321-3R25-B 14(4) 15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 --- 12 15 140M-F8N-*** 20BC030A0AYNANC0 100-C37*10 1321-3R35-B 14(4) 380/415V, IP42/54 64 Isolation Contactor Cat. No. kW (1) (2) (3) (4) (5) PowerFlex 40 VFD Cat. No. Input Voltage (1) (2) (2) (3) 1 = 80 mm 18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 --- 12 18.5 140M-H8N-*** 20BC037A0AYNANC0 100-C43*10 1321-3R45-B 14(4) 22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 --- 14(4) 22 140M-H8N-*** 20BC043A0AYNANC0 100-C85*10 1321-3R45-B 16(4) 37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 --- 14(4) 37 140M-H8N-*** 20BC072A0AYNANC0 100-C85*10 1321-3R80-B 16(4) 55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 --- 24(5) 55 140M-J8N-*** 20BC105A0ANNANC0 100-D180*11 1321-3R130-B 24(5) 75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5) 75 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R160-B 24(5) 90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 --- 24(5) 90 140M-J8N-*** 20BC170A0ANNANC0 100-D180*11 1321-3R200-B 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs Line or load reactors are optional Fixed mount style 600 mm wide column PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued) Motor Rating Circuit Breaker Isolation Contactor Reactor Module Size Cat. No. Cat. No. 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 --- 8 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 1321-3R2-B 8 0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 --- 8 0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 1321-3R2-B 8 1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 --- 8 1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 1321-3R4-B 8 2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 --- 8 2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 1321-3R4-B 8 3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 --- 8 3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 1321-3R8-B 8 5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 --- 8 5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 1321-3R12-B 8 7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 --- 8 7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 1321-3R18-B 8 11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 --- 8 11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 1321-3R25-B 8 15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 --- 8 15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 1321-3R35-B 10 18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 --- 8 kW 440/460/480V, 0.37 IP20 0.37 (1) (2) (3) (4) (5) PowerFlex 40 VFD Cat. No. Input Voltage (1) Cat. No. (2) (2) (3) 1 = 80 mm 18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 1321-3R35-B 10 22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 --- 12(4) 22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 1321-3R45-B 14(4) 37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 --- 12(4) 37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 1321-3R80-B 14(4) 55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 --- 24(5) 55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 1321-3R100-B 24(5) 75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 --- 24(5) 75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 1321-3R130-B 24(5) 90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 --- 24(5) 90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 1321-3R160-B 24(5) 110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 --- 24(5) 110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 1321-3R200-B 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs Line or load reactors are optional Fixed mount style 600 mm wide column 65 PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued) Motor Rating Circuit Breaker PowerFlex 40 VFD Isolation Contactor Reactor Module Size 1 = 80 mm Input Voltage kW Cat. No. Cat. No. Cat. No. Cat. No. 440/460/480V, 0.37 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 --- 8 IP42/54 0.37 140M-C2N-*** 20BD1P1A0AYNANC0 100-C09*10 1321-3R2-B 10 0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 --- 8 0.75 140M-C2N-*** 20BD2P1A0AYNANC0 100-C09*10 1321-3R2-B 10 1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 --- 8 1.5 140M-D8N-*** 20BD3P4A0AYNANC0 100-C09*10 1321-3R4-B 10 2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 --- 8 2.2 140M-D8N-*** 20BD5P0A0AYNANC0 100-C09*10 1321-3R4-B 10 3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 --- 8 3.7 140M-D8N-*** 20BD8P0A0AYNANC0 100-C09*10 1321-3R8-B 10 5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 --- 8 5.5 140M-D8N-*** 20BD011A0AYNANC0 100-C16*10 1321-3R12-B 10 7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 --- 8 7.5 140M-D8N-*** 20BD014A0AYNANC0 100-C16*10 1321-3R18-B 10 11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 --- 12 11 140M-D8N-*** 20BD022A0AYNANC0 100-C23*10 1321-3R25-B 14(4) 15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 --- 12 15 140M-F8N-*** 20BD027A0AYNANC0 100-C37*10 1321-3R35-B 14(4) (1) (2) (3) (4) (5) 66 (1) (2) (2) (3) 18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 --- 12 18.5 140M-F8N-*** 20BD034A0AYNANC0 100-C37*10 1321-3R35-B 14(4) 22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 --- 14[(4) 22 140M-H8N-*** 20BD040A0AYNANC0 100-C43*10 1321-3R45-B 16(4) 37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 --- 14(4) 37 140M-H8N-*** 20BD065A0AYNANC0 100-C85*10 1321-3R80-B 16(4) 55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 --- 24(5) 55 140M-J8N-*** 20BD096A0AYNANC0 100-D180*11 1321-3R100-B 24(5) 75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 --- 24(5) 75 140M-J8N-*** 20BD125A0AYNANC0 100-D180*11 1321-3R130-B 24(5) 90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 --- 24(5) 90 140M-J8N-*** 20BD156A0AYNANC0 100-D180*11 1321-3R160-B 24(5) 110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 --- 24(5) 110 140M-J8N-*** 20BD180A0AYNANC0 100-D210*11 1321-3R200-B 24(5) Approximate range of kilowatt ratings To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs Line or load reactors are optional Fixed mount style 600 mm wide column PF700 Drive Unit Options • • • • • • • • • • • • • Auxiliary contact for contactors Auxiliary contact for circuit breaker Surge suppressor Control circuit transformer Push buttons Pilot lights – Incandescent – LED – Incandescent, Push-to-Test – LED, Push-to-Test Selector switch – Two position – Three position DeviceNet starter auxiliary – (4) 120VAC inputs and (2) 120VAC outputs – (4) 24VDC inputs and (2) 120VAC outputs DeviceNet communication module, mounted internal to Solid State Starter ControlNet communication module, mounted internal to drive Isolation contactor Human interface module – Blank cover, no functionality, door mounted in bezel – LCD display, full numeric keypad, door mounted in bezel – LCD display, programmer only, door mounted in bezel I/O control interface type – 24 VDC control voltage interface with vector control – 120 VAC control voltage interface with vector control – 24 VDC control voltage interface with sensorless vector control – 120 VAC control voltage interface with sensorless vector control 67 Distribution Panels PLC and I/O Compartments 68 Selection Data Column Selection The following tables outline the CENTERLINE 2500 MCC product offering. Please select your columns and unit types. Column Dimensions mm (in) 700 - 1000 (27.56 - 39.37 Delete? 170 (6.69) 2300 (90.55) 1980 (77.95) 35 (1.38) 115 (4.53) 600 (23.62) 500 (19.69) 200 - 500 (7.87 - 19.69) Column Options Column Type Width Depth Height IP Rating Separation Withdrawable Units 700 mm (200 mm wireway) 600 mm 2300 mm IP 20 Form 3b 800 mm (300 mm wireway) 800 mm IP 30 Form 4b 900 mm (400 mm wireway) 1200 mm (double-front) IP 42 1000 mm (500 mm wireway) Fixed Units IP 54 700 mm (no vertical wireway) 800 mm (no vertical wireway) 900 mm (no vertical wireway) 1000 mm (no vertical wireway) 69 Horizontal Power Bus Options Horizontal Power Bus Bus Rating Short Circuit Withstand Rating Short Circuit Peak Withstand Rating Material 800 A 50 kA for 1 second 110 kA 1250 A 50 kA for 3 second and 80 kA for 1 second 176 kA Bare Copper or Tin-plated Copper 50 kA for 3 second and 100 kA for 1 second 220 kA 1600A 2000 A 2500 A 3200 A 4000 A Vertical Power Bus Options Vertical Power Bus Bus Rating Short Circuit Withstand Rating Short Circuit Peak Withstand 300 A 50 kA for 0.2 second 110 kA for 3 second 600 A 50 kA for 1 second Material Tin-Plated Copper Neutral Power Bus Options Vertical Power Bus Bus Rating Short Circuit Withstand Rating Full 50 kA for 0.2 second 110 kA for 3 second Half 50 kA for 1 second 70 Short Circuit Peak Withstand Material Tin-Plated Copper Incoming Power and Control Power Selection Incoming Power and Control Voltage Options Line/System Voltage (V) Frequency (Hz) Control/Coil Voltage (V) Control Type 380 50 24 DC; 110, 220 AC 60 24 DC; 110, 120, 220 AC Transformer, Separate, or line to neutral 50 24 DC; 110, 230 AC 400 60 415 440 480 50 24 DC; 110, 240 AC 60 24 DC; 120, 240 AC 50 24 DC; 110, 220 AC 60 24 DC; 110, 120, 220 AC 50 60 600 50 60 (1) 690 24 DC; 120, 240 AC 24 DC; 120, 240 AC 50 60 (1) Consult the factory 71 Unit Selection Incoming Main Lug Compartments and Outgoing Feeder Lug Compartments The line lug compartments provide a lug connection for incoming lines (mains) to distribute power to the motor control center for outgoing cables (feeders) to feed power from the motor control center to an external load. Mechanical or crimp style lugs are available. Lug compartments are a fixed-unit design and may be located at the top or bottom of the column. Main and Feeder Lugs Feeder Lug Main Lug Lug Compartments Amperes Cable Provisions, Maximum Number per Phase and Maximum Cable Size Module Size Mechanical Type Lugs(1) (Single Cable) Crimp Type Lugs(1) 300 (2) 185 mm2 (2) 185 mm2 (2) 400 (2) (2) (2) 600 2 (2) 185 mm 6(2) (1) 240 mm2 (2) 185 mm2 6(2) 2 2 (1) 400 mm 6(2) (2) 240 mm2 6(2) (4) 400 mm2 (4) 400 mm2 6(2) 2 2 (2) 400 mm 6(2) (4) 300 mm2 (4) 240 mm2 24(2) (1) 400 mm2 (3) 240 mm2 24(2) 2 2 24(2) (2) 185 mm (2) 400 mm 2 (1) 800 (2) 400 mm (2) 300 mm (4) 185 mm (4) 240 mm2 24(2) (1) 400 mm2 (2) 400 mm2 24(2) 2 2 24(2) (2) 400 mm (4) 240 mm (4) 300 mm2 24(2) (4) 400 mm2 (4) 400 mm2 24(2) 1250 (2) (2) 24(2) 1600 (4) 400 mm2 (4) 400 mm2 24(2) 2000 (6) 400 mm2 (6) 400 mm2 24(2) 2500 (2) (2) 24(2) 3200 (2) (2) 24(2) 4000 (2) (2) 24(2) (1) Fixed mount style (2) Consult factory 72 Miscellaneous Units DeviceNet Power Supply DeviceNet Power Supply Units are supplied with a circuit breaker or fusible disconnect Central Control Transformer Units Module Size Unit Description 4 Central Control Transformer DeviceNet Power Supply Units Module Size Unit Description 2 DeviceNet Power Supply 4 Redundant DeviceNet Power Supply Bridge Units Module Size Unit Description 2 ControlNet to DeviceNet Bridge 2 Ethernet to DeviceNet Bridge 2 Profibus to DeviceNet Bridge 73 Technical Data Technical Standards and Certifications The MCC is designed and tested to meet or exceed the requirements defined by the following IEC standards and directives. • EN 60439-1:1999 + A1:2004, the standard for type-tested and partially type-tested assemblies of low voltage switchgear and control gear assemblies (TTA, PTA) • EN 60204-1:2006, the general requirements for the safety of electrical equipment of machines • 2006/95/EC, Low Voltage Directive • 2004/108/EC, EMC Directive • 2002/95/EC, the restriction of hazardous substances directive (RoHS) • KEMA certified (TTA) The MCC columns, units and components are available with the CE Conformance Mark and the China Compulsory Certification (CCC). The MCC is designed, manufactured and tested in facilities registered to ISO 9001 quality standards. Operating Environment The MCC is intended for use in a pollution degree 3 environment. The MCC is designed to operate in the following ambient conditions. The ambient operating temperature shall range from -5…40 °C, with the average temperature in any 24 hour period not exceeding 35 °C. The MCC is designed to operate at altitudes up to 1000 m. For altitudes exceeding 1000 m, contact your Rockwell Automation representative for derating information. 74 Forms of Separation Internal isolation and separation exists between the following: • Individual units • Units and wireways • Units and the bus system • Wireways and the bus system In addition, the vertical wireway for power wiring is separate from the vertical wireway for control and network wiring. Standard internal separation within the MCC is Form 3b. Form 4b is available by enclosing terminals for external conductors in a metal box within the vertical wireway. Internal Separation Form 3b Form 4b 75 CENTERLINE 2500 Specifications Standards EN 60439-1:1999 + A1:2004 EN 60204-1:2006 EC Directives 2006/95/EC 2004/108/EC 2002/95/EC(1) Low-voltage switchgear and controlgear assemblies Part 1: Type-tested and partially type-tested assemblies Safety of machinery – Electrical equipment of machines Part 1: General requirements Low Voltage Directive EMC Directive Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment (RoHS) Certifications and Markings China Compulsory Certificate (CCC) CE Conformance Marked KEMA certified (TTA) Rated Voltages Rated Operating Voltage, Ue Up to 690 V, 3-Phase Rated Frequency, fn 50 – 60 Hz 1000 V, 3-Phase Rated Insulation Voltage, Ui Rated Currents Horizontal Bus Vertical Bus Continuous Current Rating, Ie Up to 4000 A Up to 600 A Up to 176 kA for 1 second Up to 110 kA for 3 second Short Circuit Peak Withstand, Ipk Short Time Withstand Rating, Icw Up to 80 kA for 1 second Up to 50 kA for 1 second Neutral (N) Full or half rated Creepage Distances and Clearances Rated Impulse Withstand Voltage, Uimp 6, 8, or 12 kV Material Group (Overvoltage Category) IIIa (175 </= CTI < 400) Pollution Degree 3 Bus Material and Plating Horizontal Power Bus Copper (optional tin plating) Vertical Distribution Bus Copper with tin plating Protective Earth Conductor (PE) Copper (optional tin plating) Degrees of Protection IEC 60529 IP 20, 40, 42 or 54 Forms of Separation IEC 60439-1 Form 3b or 4b Column Dimensions Height 2300 mm Width 700, 800, 900, or 1000 mm Depth 600 or 800 mm (1200 mm, double-front) Units Approximate Module Size 80 mm high x 500 mm wide = 1 module Modules per Column 24 Withdrawable Unit Sizes 1, 2, 4, 6, 8, 10, 12 modules Structural Surface Treatments Interior High Visibility White Paint (Additional colors available by request.) Exterior RAL 7032 Pebble Grey Paint or Munsell 6.5 Paint (Additional colors available by request.) Environment Storage Temperature -25…55°C Operating (Ambient) Temperature -5…40°C Altitude Up to 1000 m (1) Low voltage Motor Control Center products are exempt under Category 9, however Rockwell Automation is committed to demonstrating the highest standard of global environmental management. It is the goal of Rockwell Automation to meet the material restrictions on products, even where compliance is not legally required. 76 Structure Material This list has the approximate thickness and gauge of the MCC structural components and external covers. CENTERLINE 2500 MCC Structure Details Structural Components Thickness (mm) Side Plate 2.0 Back Plate 2.5 Covers and Panels Top Plate 2.0 Bottom Plate 2.0 End Closing Plate 2.0 Horizontal Wireway Cover 2.0 Doors Unit Door 2.0 Vertical Wireway Door 2.0 Other Steel External Mounting Channel 3.5 77 78 Checklist Explanation of why using the checklist is important. Customer User Reviewed the customer documents prior to filling out this form Office Standards and Certifications CE KEMA CCC Other ____________ Incoming Power Line Voltage: 380V 400V System Power: 415V 440V 480V Grounded Wye Grounded Wye with Impedance 50 Hz Available Fault Current: 690V Grounded Delta Delta Frequency: 600V 60 Hz kA Control Power Voltage: 24V DC 110V AC 115V AC Source: Individual Control Transformer 120V AC Standard VA 220V AC 230V AC 240V AC Extra Capacity Common Control Power Transformer Separate Control Power Source Top Horizontal Wireway Control Terminal Blocks Location: Vertical Wireway Structure Enclosure Rating: IP 20 (vented doors) IP 42 (non-vented, standard) IP 40 (vented doors with filters) IP 54 (fully gasketed, doors and bottom plates) Forms of Internal Separation: 3b (standard) 4b Mounting Configuration Stand Alone Add to Existing Front Only Double-front 600mm 800mm Depth: Width: Options: 700mm (200mm vertical wireway, standard) 900mm (400mm vertical wireway) 800mm (300mm vertical wireway) 1000mm (500mm vertical wireway) Space Heater w/ Thermostat Arc Containment Latches Cable Supports Other ________________________ External Paint: RAL7032 Pebble Grey (standard) Other _____________ Internal Paint: High Visibility Gloss White Other _____________ Ambient Temperature: °C maximum Altitude: meters 79 Bus Fault Rating/Bracing: 50kA for 3 cycles 65kA for 3 cycles 50kA for 3 seconds (horizontal power bus only) Horizontal Power Bus Rating: 2000A 800A (standard) 1250A 1600A 2500A 3200A 4000A Rating: Half Rated 300A (provides 600A capacity, standard) Material: 600A (provides 1200A capacity) Copper, Tin Plated Horizontal Location: Bottom (standard) Material: Copper, Unplated Size: 1-6 x 50 mm Vertical (Plug-in): Stab Openings: Copper, Tin Plated Full Rated Vertical Distribution Bus Protective Earth Conductor (PE) 80kA for 1 second (horizontal power bus only) Copper Material: Neutral Bus: 50kA for 1 second 2-6 x 50 mm Copper, Tin Plated 3-6 x 50 mm Copper, Unplated Copper, Tin Plated Automatic Shutters (standard) IntelliCENTER Technology IntelliCENTER: DeviceNet Cabling DeviceNet Cabling with IntelliCENTER Software Linking Device: EtherNET/IP ControlNet ArcShield Yes 80 Profibus Other _____________ Incoming Cable Termination/Provision Ampere Rating: __________A Located in Column Number: __________ Number of cables per phase: __________ Top Cable Size _______________________ Crimp Compression Lugs Main Lug Only (MLO): Mechanical Lugs Fuses Supplied Main Fusible Disconnect (MFD): Bottom Lugs Not Supplied Fuse Type __________________ Fuses Not Supplied Main Circuit Breaker (MCB): Ground Fault Shunt Trip Auxiliary Contacts - Qty. __________ Other ______________ Number of current transformers required _______________ Number of potential transformers required ______________ Incoming Metering Options: Analog Ammeter Ammeter Switch Analog Voltmeter Voltmeter Switch Powermonitor 3000 1404-M5 1404-M6 Digital Volt/Ammeter 1405-M610 Outgoing Cable Termination/Provision Ampere Rating:__________A Number of cables per phase __________ Crimp Compression Lugs Lug Type: Cable Size _______________________ Mechanical Lugs Lugs Not Supplied Feeder Units Fuses Supplied Fuse Switch: Fuse Type _____________________ Fuses Not Supplied Circuit Breaker (Thermal Magnetic): Interrupting Rating _______________kA Ampere Rating ________A Other__________________________________________ Nameplates Unit Nameplates: Cardholder Engraved Acrylic Engraved Phenolic Black letters on white Color Scheme White letters on black White letters on black (phenolic only) Door Latches Door Latch Type: 1/4 Turn 1/4 Turn with T-handle Arc Containment Arc Containment with T-handle Wire Markers Wire Marker Type: Sleeve Data Tab Heat Shrink Spares Spare Parts Spare Units 81 Direct On Line Starter Units (copy and complete for each unit needed) Non-reversing Starter Unit Type: Ampere Rating: ________A Reversing Starter Kilowatt Rating: _______kw Fused (rotary operator only) Disconnecting Means: Fuse Type _____________ Fuses not supplied Circuit Breaker Handle Operator: Type: Overload: Reset: Rotary Operator Flange Operator (2 module minimum) E1 Plus E1 Plus with Ground Fault E3 Plus E3 Plus with Ground Fault External (door mounted) Duty Rating: AC3 (standard) AC4 Protection: Type 1 Type 2 Withdrawable Unit Type: Semi-withdrawable Fixed Options and Accessories Pilot Lights: Qty_______ Transformer Type Push-to-test Text on Legend Plate: On Off Emergency LED Lamps Fault Other ____________________________ Pushbuttons: Qty_______ Text on Legend Plate: On Emergency Selector Switch: Normally Open, Qty _____ Relays or Timers, Describe ____________________________ Others, Describe ____________________________ 82 Reset Other ____________________________ Yes Starter Auxillary Contacts: Notes Off Normally Closed, Qty _____ Soft Starter Units (copy and complete for each unit needed) Unit Type: SMC-3 SMC Flex Connection: Line Connection Delta Connection Ampere Rating: ________A Kilowatt Rating: _______kw Fused (rotary operator only) Disconnecting Means: Fuse Type _____________ Fuses not supplied Circuit Breaker Rotary Operator Handle Operator: Withdrawable Unit Type: Flange Operator (2 module minimum) Semi-withdrawable Fixed Options and Accessories Pilot Lights: Qty_______ Transformer Type Push-to-test Text on Legend Plate: Start Stop LED Lamps Other ____________________________ Pushbuttons: Qty_______ Text on Legend Plate: On Off Fault Other ____________________________ Selector Switch: Yes Human Interface Module (HIM): LCD Display, Full Numeric Keypad Starting Mode: Pump Control Others, Describe LCD Display, Programmer Only Braking Control ____________________________ Notes 83 Variable Frequency AC Drive Units (copy and complete for each unit needed) Unit Type: Rating: Ampere Rating: ________A PowerFlex 40 PowerFlex 70 PowerFlex 700 PowerFlex 700H Normal Duty Heavy Duty Kilowatt Rating: _______kw Disconnecting Means: Fused (rotary operator only) Fuse Type ________________ Fuses not supplied Circuit Breaker Rotary Operator Handle Operator: Withdrawable Unit Type: Flange Operator (2 module minimum) Semi-withdrawable Fixed Options and Accessories Pilot Lights: Qty_______ Transformer Type Push-to-test Text on Legend Plate: Start Stop LED Lamps Other ____________________________ Pushbuttons: Qty_______ Text on Legend Plate: On Off Fault Other ____________________________ Yes Selector Switch: LCD Display, Programmer Only Human Interface Module (HIM): LCD Display, Full Numeric Keypad Braking Mode: Pump Control Braking Control Reactors: Line Reactor Load Reactor Others, Describe Notes 84 ____________________________ Miscellaneous Units (copy and complete for each unit needed) DeviceNet Power Supply Unit Redundant DeviceNet Power Supply Unit DeviceNet Back-up Power Supply Unit Programmable Controllers: Specify unit location _____________________________ Number of Slots ___________ Power Supply___________ Describe: ________________________________________ Other Units, Options or Modifications: Describe: ________________________________________ ________________________________________________ Extra Space for Future Units: Describe: ________________________________________ ________________________________________________ Comments / Additional Notes: 85 Fill in blanks as required. Motor List Unit Description Comments/Additional Notes 86 Rating Module Size Publication 2500-SG001B-EN-P—May 200988 Supersedes Publication 2500-SG001A-EN-P—January 2008 Copyright © 2009 Rockwell Automation, Inc. Printed in the U.S.A.