CENTERLINE 2500 Motor Control Centers

advertisement
CENTERLINE 2500 Motor Control Centers
Selection Guide
Contents
CENTERLINE® 2500 Motor Control Centers 5
Unit Design 23
Units 34
Selection Data 69
Unit Selection 72
Technical Data 74
Checklist 79
79
3
4
CENTERLINE® 2500 Motor Control
Centers
The CENTERLINE 2500 Motor Control Center (MCC) consists of one or more
columns secured together forming a rigid, free-standing assembly. The MCC
columns are designed to allow the addition of future columns.
The MCC is designed with full isolation of electrical components from the
front side of the structure. When the doors are latched and the covers are
secured, a person on the operating side of the equipment is not exposed to
live parts.
Units installed in the MCC columns are populated with a full line of IEC
components, contactors, overload relays, AC drives, soft starters and other
devices.
Product Features
• Meets Global Standards
– Designed to IEC 60439-1
– Designed to IEC 60529
– KEMA (TTA) Certified
• Fully withdrawable unit design allows for faster replacement, helping
minimize maintenance and downtime
– Plug-in line, load, control, ground and network communications
– Four unit positions (connected, test, disconnected and withdrawn)
– Lever operated mechanism for tool-less withdrawal and insertion
• Built-in network and IntelliCENTER® technology
– Improve performance through system-wide communications
– Share diagnostic information for predictive maintenance
– Initiate warnings before potential faults occur
• ArcShield helps you reduce arc flash hazards
• Three and four wire bus bar power systems available to help meet your
local requirements
• High unit density optimizes column utilization
• Fully isolated structures for maximum arc containment
• Multiple column widths of 600, 700, 800, 900 and 1000 mm available for
scalable solutions
5
IntelliCENTER Technology
Built-in Networking
• Media protected behind barriers
• Access ports in wireways
• Trunk and drop topology allows for addition and
removal of devices without shutting down the
network
Intelligent Motor Controls
•
•
•
•
PowerFlex Drives
SMC™ 3 and SMC™-Flex Soft Starters
E1 Plus, E3 Plus Electronic Overload Relays
DeviceNet Starter Auxiliaries
IntelliCENTER Software
•
•
•
•
Elevation View
Monitor View
Documentation View
Spreadsheet View
Factory Configuration
• Network media validation
• Node configuration
• Device communication check
IntelliCENTER Technology improves the intelligence of
your MCC using built-in DeviceNet to capture information
used for predictive maintenance, process monitoring, and
advanced diagnostics.
6
DeviceNet
Based on the latest in network technology, DeviceNet is a
simply, open networking solution, allowing for real-time
control, data exchange, configuration and data
connection at regular intervals or on demand. This robust
communication link connects industrial devices (such as
limit switches, photoelectric sensors, motor starters, push
buttons, variable frequency drives and operator interface
devices) to a network and eliminates time-consuming and
costly hard wiring.
The cost and performance of a DeviceNet network makes
it ideal for MCC applications. The open specifications and
protocol, managed by the Open DeviceNet Vendor
Association (ODVA), means vendors are not required to
purchase hardware, software or licensing rights to connect
to a system. Over 300 vendors offer DeviceNet products
with over a half million nodes installed worldwide.
IntelliCENTER Software
The CENTERLINE 2500 MCC is available with pre-configured IntelliCENTER software. IntelliCENTER software is an intuitive
softare package that is customized to your MCC. This software package includes several preconfigured views for easy
access to important information and is capable of viewing multiple MCC line-ups. IntelliCENTER software can be installed
and operated on Ethernet, EtherNet/IP, ControlNet or DeviceNet. The IntelliCENTER software is capable of functioning as a
stand alone software package or as an ActiveX control in a Human Machine Interface (HMI). The IntelliCENTER software
displays the following:
Elevation View
The Elevation View is an easy-to-identify, graphical representation of your entire
MCC lineup. The condition of each motor controller is quickly established with
status light indicators. Customizable text allows for instant identification of the
motor, machine or process.
• Navigate immediately to units of concern by simply double-clicking on them
• Re-arrange the elevation view using simple drag-and-drop
• Select units for which you would like to see manuals, wiring diagrams or
spare parts
Monitor View
The Monitor View displays an overview of the intelligent motor control device
being monitored, with configurable gauges, trend graphs, I/O status on the device
and configurable data fields.
• Monitor parameters from the intelligent devices
• Change configuration parameters
• Record up to 5000 data points with the trend graph and export
• Change which parameters are displayed in the monitor view
Documentation Views
Documentation View has access to the various manuals and diagrams for your MCC along with other important MCC
information.
Manuals and Wiring Diagrams
The IntelliCENTER Software data CD comes with the complete documentation for your MCC, including wiring diagrams
and device manuals. So your manuals are quickly available when you need them most.
• Troubleshoot problems using the exact manuals for your MCC
• Trace out wiring and understand control circuits using wiring diagrams
• Add new documentation ( procedures, engineering notes) associated with your MCC
• Substitute ‘as-built’ drawings with your ‘as-installed’ drawings
7
Spreadsheet View
The spreadsheet view allows you to access MCC data such as:
• Node number (network address)
• Unit description
• Nameplate data
• Device type
Event Log View
The Event Log records and stores events with date and time
information occurring within you MCC and stores them with
their date and time. Events can include device warnings and
faults as well as parameter or device changes.
Spare Parts List
The spare parts list provides you with the exact replacement
part needed to repair your MCC unit. This helps save time when
calling your authorized Allen-Bradley distributor.
8
Networking
DeviceNet Cabling
All trunk and drop DeviceNet cabling is ODVA certified Class 1, with 600V insulation and 8 A rating. The DeviceNet cabling
system for IntelliCENTER Technology has been extensively tested for noise immunity with network cables in close
proximity to high current motor leas and VFD outputs. As a result, IntelliCENTER MCCs provide a very robust network
solution with no special separation, barriers or internal conduit required.
DeviceNet Cable Layout
The DeviceNet trunk line is routed through the control and network wireway and top horizontal wireway of the MCC.
Trunk lines are routed behind barriers to isolate the cable from the unit space and wireways to help prevent accidental
damage.
DeviceNet Trunk Line
Up to 24 DeviceNet ports can be provided in the control and network wireway. Each DeviceNet component in an MCC unit
is connected to the network through a port located in the control and network wireway. Adding or removing units from
the network does not interrupt the other units operating in the system.
DeviceNet System Performance
The DeviceNet system in the MCC is designed to operate at 500 kbaud to maximize performance, unless precluded by the
cumulative length of the trunk and drop lines. To achieve best performance, all MCCs are engineered for a 250 kbaud
minimum communication rate.
The DeviceNet system in the MCC is qualified to communicate and perform under normal and adverse electrical
environments (for example, contactor electrical operation, contactor jogging duty and unit short circuit fault).
The DeviceNet system has the following capabilities:
• Automatic Device Replacement (ADR).
• On-Line Scanlist Changes at Run, allowing network modifications to be performed on a DeviceNet system that is
running.
• Scan modes: Polled, Change of State (COS), Strobe and Cyclic. By choosing the appropriate scan mode for different
data, DeviceNet systems can achieve better throughput performance than networks with much higher
communication rates.
• Transmit and receive data via I/O and explicit messaging. This allows the control system to access every parameter
in the device, not just a few registers.
9
DeviceNet Components
Each unit can be provided with a DeviceNet component.
• Starter units can be provided with an E1 Plus with DeviceNet module, E3 or E3 Plus overload relays or solid-state
overload relays with a DeviceNet Starter Auxiliary.
• Contactor units can be provided with a DeviceNet Starter Auxiliary.
• AC drives can be provided with a DeviceNet communication module.
• Solid-state controllers can be provided with DeviceNet communication modules and, in some instances, a
DeviceNet Starter Auxiliary.
• Fusible disconnect and circuit breaker feeder circuits can be provided with a DeviceNet Starter Auxiliary.
Programming of Parameters
The DeviceNet node address is programmed for each unit. All other parameters are left at the factory default setting.
The DeviceNet components are configured to operate at the specified communication rate.
Testing
CENTERLINE 2500 motor control centers with IntelliCENTER Technology can save you time because each MCC is powered
up, configured and tested at the factory. Each unit is preconfigured with node addresses and communication rates to
ensure it communicates properly.
For more information on MCCs with DeviceNet, refer to CENTERLINE 2500 DeviceNet Motor Control Centers, publication
2500-TD002.
IntelliCENTER Database
The IntelliCENTER Database contains all of your order-specific information. One IntelliCENTER Database is needed for each
MCC lineup or for individual units (when the unit is purchased separately). The database is installed on the computer or
computers running the IntelliCENTER software. The database CD includes the IntelliCENTER data files, all of the electronic
documentation, all theup-to-date EDS files for the DeviceNet devices and the DeviceNet configuration file as recorded
during the final system test of the MCC. The EDS and configuration files are very useful for programming the control
system, allowing the programmer to complete the project before the equipment is even energized. Additionally, when
used with RSLogix 5000 and RSNetworx for DeviceNet software, the programmer can use the DeviceNet Tag Generator
utility in RSLogix 5000 to instantly generate descriptive tags for every device in the MCC.
10
ArcShield
CENTERLINE 2500 MCC’s with ArcShield offers you better protection against harmful arc flash hazards. Using a
CENTERLINE 2500 MCC with ArcShield helps protect your personnel if an arc flash were to occur within an MCC.
CENTERLINE 2500 MCC with ArcShield provides personnel and assembly protection per IEC/TR 61641:2008 for arcing
durations up to 300 ms(1).
In combination with the standard safety features built into every CENTERLINE
2500 MCC, choosing ArcShield provides additional benefits, including:
• Structures with no front ventilation
• Pressure relief system designed to exhaust gases through the top of the
structure, away from personnel
• Arc containment latches on all doors capable of withstanding the high
internal pressure generated by an arc blast
• Insulated power bus closing plates included at the ends of each MCC lineup
Pressure Relief
System
Arc Containment
Latches
For even more protection, optical and current sensing technology for use with
crowbar or shunt trip devices is available as an option.
(1) 300ms rating is available for systems at 415V (max), with 65kA (max) available current
11
Structure
The CENTERLINE 2500 MCC structure consists of columns, wireways, doors and withdrawable or fixed units.
Columns
The rigid, free-standing columns have heavy duty external mounting channels running the continuous width of the
shipping block. Columns are secured at the installation site by bolting together clearance holes in the mounting channels
or welding together.
All shipping blocks are provided with a removable continuous steel lifting angle. Two lifting angles are provided on all
double-front columns.
Fault containment is enhanced with two side sheets on every column. This helps prevent a single fault from cascading
throughout the structure, limiting equipment damage.
The CENTERLINE 2500 MCC’s rigid design helps ensure a longer life. Plug-in units can still be installed and removed and
doors close securely after years of dependable service.
12
Column Construction
Optional ArcShield
Pressure Relief
Plate
Top Horizontal Wireways
Vertical Power Bus
Vertical Wireway
(door closed)
Horizontal Power Bus
Nameplates
Vertical-to-Horizontal Bus
Connection
Customer Load Terminal
Forms of Separation
Unit Support Pan
Optional ArcShield End Closing
Plate Insulator
Control and Network Wireway
Vertical Bus Covers
(Automatic Shutters)
Bottom Horizontal
Wireways
Vertical Plug-in
Protective Earth
Conductor
Horizontal Protective
Earth Conductor
13
Column Dimensions
The standard column width is 700 mm. Each column is
2300 mm high and 600 mm deep. Double-front columns
are also available.
Unit size is described in terms of modules. Each module is
approximately 80 mm high x 500 mm wide. Columns can
accommodate 24 modules of varying unit combinations.
Horizontal wireways extend the full depth of the column.
Vertical wireways are approximately 350 mm deep.
Column Width
700 - 1000
(27.56 - 39.37
170 (6.69)
Total Column
Width
Unit Width
Vertical Wireway
Width
600 mm(1)
600 mm
No vertical
wireway
700 mm (standard)
500 mm
200 mm
(standard)
800 mm
500 mm
300 mm
900 mm
500 mm
400 mm
1000 mm
500 mm
500 mm
(1) Frame mount only.
Column Depth
Front Only
2300 (90.55)
Double-Front
600 mm
1200 mm
800 mm
—
Column Height
1980 (77.95)
Feature
Height
Total Height
2300 mm
Available Unit Height
1980 mm
Top Horizontal Wireway
170 mm
Bottom Horizontal
Wireway
115 mm
External Mounting Channel 35 mm
Approximate Weight
35 (1.38)
115 (4.53)
600 (23.62)
500
(19.69)
200 - 500
(7.87 - 19.69)
This table lists approximate weights for MCC columns.
Many factors (number of units, horizontal power bus,
wireway width, column depth) affect the weight of
columns. Weight is also added when the product is
packaged for shipping.
Column Width
Approximate Weight (1)
600 mm, 700 mm
350 kg
800 mm
400 kg
900 mm
450 kg
1000 mm
500 kg
(1) Weights are for a typical Motor Control Center with 6 units per
column. Weights do not include packaging. Refer to the packing slip
shipped with your MCC for exact shipping weights.
14
Structure
You can select the degree of protection and the paint color for your CENTERLINE 2500 MCC.
Degree of Protection
In accordance with IEC 60529, structures are available with the following IP ratings.
• IP 20 (non-filtered vented doors)
• IP 30 (filtered vented doors)
• IP 42 (non-vented doors, standard)
• IP 54 (gasketed with bottom plates)
Structure sheet metal has rounded edges and is tightly fitted with no visible air gaps.
Paint and Plating
Structural metal undergoes a multi-step cleaning, rinsing and painting process resulting in complete uniform-thickness,
paint coverage. This process is maintained and controlled by ISO 9001 quality standards.
Zinc with trivalent chromate is used to plate unpainted surfaces for corrosion resistance.
The standard exterior paint color is Pebble Grey (RAL 7032). Closing plates, channel supports, lifting angles, and horizontal
wireway covers are painted Black Grey (RAL 7021). Interior vertical wireways and unit mounting plates are painted high
visibility gloss white.
Other colors are available by request.
15
Wireways
Each MCC has horizontal, vertical and control and network
wireways, for continuous dedicated wire and cable location.
Continuous Horizonal Top Wireway
Horizontal Wireways
Continuous
Vertical
Wireway
Continuous Horizonal Bottom Wireway
Horizontal wireways are located at the top and bottom of
each MCC column. Horizontal wireways extend the full width
and depth of the MCC. A barrier is present in the top
horizontal wireway to provide a connection point for
DeviceNet receptacles. The top horizontal wireway is 170
mm high, while the bottom horizontal wireway is 115 mm
high. Complete wireway access from front to rear is available
for double-front configured MCC columns..
Horizontal wireways have removable front covers that are
held in place by captive screws. Openings in in the side plate
of the column allow access to the top and bottome
norizontal wireways between joined columns. Plates are
provided to cover these openings for columns located at the
end of a MCC lineup.
Horizontal wireways are isolated from the power bus. Horizontal wireways for incoming line sections are reduced depth to
maintain isolation from the incoming line area.
Vertical Wireway
The vertical wireway is located on the right side of each column and extends 1980 mm, between the top and the bottom
horizontal wireway. The vertical wireway is approximately 350 mm deep. The standard vertical wireway is 200 mm wide.
Vertical wireways are also available in widths of 300, 400 and 500 mm. Wider wireways are recommended for MCCs with
higher bus ratings and higher unit density per section.
The vertical wireway is isolated from power bus and is independent of unit space. Vertical wireways are not present in
columns with fixed (frame-mounted) units.
Vertical wireways are covered with steel doors, held in place by four door latches.
See Nameplates on page 32 for more information.
Vertical wireway cable supports are available to help you keep your cable wireways organized.
16
Control and Network Wireway
A separate wireway isolates control and network cables from power wiring.
The control and network wireway is located on the left side of the column in the unit space. Control and network
connections are made to withdrawable units through receptacles located in this wireway.
Control
Wireway
DeviceNet
Network
Connector
Units Removed
Control
Connector
17
Incoming Power
The MCC can be configured to work on a system with any of the following incoming line voltages: 380, 400, 415, 440, 480,
600 and 690 V.
The MCC can be configured to operate at a frequency of 50 or 60 Hz.
CENTERLINE 2500 MCCs are suitable for use on three-phase, three-wire or four-wire, wye connected power systems, rated
690V or less, 50 or 60 Hz, with a solidly grounded neutral. CENTERLINE 2500 MCCs may also be used on other power
system configurators, however, some units and options may not be available. Consult the factory for additional
information.
Power Bus
The MCC features the time-proven Allen-Bradley CENTERLINE power bus system. The horizontal power bus is mounted
near the vertical center of the structure providing optimum heat dissipation, power distribution, and ease of maintenance
and installation. It is mounted in recessed channels of the bus support to protect against accumulation of dust and
tracking between phases.
The vertical power bus allows power distribution both above and below the center-mounted horizontal bus, effectively
doubling the capacity in each column. This feature also helps allow a virtually unrestricted unit arrangement.
Horizontal and vertical power bus is fastened together with a two bolt assembly. This two-bolt connection helps minimize
the likelihood of “hot spots.” The factory-made horizontal to vertical power bus connection is tightened by a
computerized torquing system.
The power bus system is supported, braced and isolated by a bus support molded of high strength, non-tracking glass
polyester material. The horizontal power bus is mounted on-edge in a vertical plane providing maximum strength against
magnetic forces. Vertical power busbars are continuously braced and sandwiched by a polycarbonate molded bus cover
isolating the vertical power bus from the other vertical phases and the horizontal power bus.
Bus bracing is available with the following rms symmetrical current ratings.
• 50 kA for 3 cycles at 60 Hz (standard)
• 65 kA for 3 cycles at 60 Hz
• 50 kA for 1 second
• 50 kA for 3 seconds (horizontal power bus only)
• 80 kA for 1 second (horizontal power bus only)
18
CENTERLINE Power Bus and Neutral (Cover Removed)
Optional Neutral
Horizontal Bus Bar
Two-bolt Assembly
Optional Neutral Vertical
Bus Bar
Horizontal Power Bus
Vertical Power Bus
The standard horizontal power bus material is unplated
copper. Tin-plated copper horizontal power bus is
optional.
The tin-plated copper vertical power bus is cylindrical for
optimum contact with the plug-in unit stabs.
Horizontal Power Bus Ratings and Descriptions
Power Bus Rating
Busbar Quantity and Dimensions
800 A (standard)
(1) 3 x 100 mm
1250 A
(1) 6 x 100 mm
1600 A
(2) 6 x 100 mm
2000 A
(1) 6 x 100 mm and (1) 10 x 100 mm
2500 A
(2) 10 x 100 mm
3200 A
(3) 10 x 100 mm with 10 mm spacers
4000 A
(4) 10 x 100 mm with 10 mm spacers
The standard vertical power bus is rated for 300 A above
and below the horizontal power bus for an effective 600 A
rating. An optional vertical power bus rated for 600 A
above and below the horizontal power bus for an effective
1200 A rating is available.
19
Neutral Bus
The optional horizontal neutral bus is provided across the full width of
the MCC and located above or below the horizontal power bus.
Back of MCC
(back plate
removed) Neutral bus
shown
The neutral bus matches the material and specifications of the vertical
power bus.
The horizontal neutral bus is available with a full or half current rating.
The vertical neutral bus is connected to the horizontal neutral bus and
provides a neutral connection for units throughout the column.
The neutral bus is braced the same way as the horizontal and vertical
power bus.
Automatic Shutters
Automatic shutters are standard on CENTERLINE 2500 MCCs. Automatic shutters open as withdrawable units are inserted
and close when the unit is removed. This safety feature helps ensure the vertical bus is immediately isolated when a
withdrawable unit is removed.
20
Protective Earth Conductor
The horizontal protective earth conductor along with the vertical plug-in protective earth conductor form a complete
internal protective earth circuit.
Horizontal Protective Earth Conductor
The horizontal protective earth conductor (PE) is unplated copper or
tin-plated copper is available, and is located in the bottom
horizontal wireway. The horizontal PE is continuous for the width of
the column and consists of one, two or three 6 x 50 mm conductors.
The horizontal PE has 12 holes along the length of the conductor for
making equipment connections.
A pressure-type mechanical lug is mounted on the horizontal PE
conductor in the incoming line section.
Vertical Plug-in Protective Earth Conductor
An unplated copper vertical plug-in PE conductor is provided in each standard column. An optional tin-plated copper
vertical plug-in PE conductor is also available. The vertical plug-in PE conductor is mechanically connected to the
horizontal PE conductor.
The vertical plug-in PE conductor in combination with the unit PE contact establishes a first make, last break operation of
the PE connection with respect to power connections. This first make, last break connection assures the unit to be
grounded when inserting or removing the unit.
21
Module Space
Unit size is described in modules. One module is approximately 80 mm high x 500 mm wide. Withdrawable units are
available in the following sizes: 1, 2, 4, 6, 8, 10 and 12 modules. Fixed units range in size from 2 to 24 modules.
Each MCC column can accommodate 24 modules.
Continuous Horizontal Wireway
2 Module
Unit
4 Module
Unit
24 Modules
Total
Continuous
Vertical
Wireway
8 Module
Unit
Continuous Horizontal Wireway
22
Unit Design
Units are designed as either withdrawable or fixed. Withdrawable units can be removed from the structure and have a
maximum current rating of 225 A.
The amount of current drawn by fixed units is determined by the rating of the horizontal power bus. Fixed units are
frame-mounted and cannot be moved or rearranged once installed in the column.
Two Module Unit
Withdrawable Unit Design Features
Withdrawable units consist of the unit, unit support pan and unit door. Withdrawable units are held securely in the
column when inserted and are designed with an interlock to help ensure that units cannot be inserted or withdrawn when
the disconnect means is in the ON/I position. Withdrawable units range from 1 up to 12 module sizes.
Tools are not required to insert or remove withdrawable units.
Withdrawable units are characterized by being able to release the line, load, control, network and protective earth (PE)
connections. Outgoing load and control connections are in the vertical wireway.
23
Withdraw Lever and Alignment Slides
Withdrawable units use low friction alignment slides and a mechanical withdraw lever for easy unit inserting and
removing. The withdraw lever features a locking mechanism that the user disengages to change positions. Detents are
present to help confirm that the unit is secured in each position.
Withdraw Lever
Operating Positions
Withdrawable units have four operating positions: connected, test, disconnected and withdrawn. See the following
descriptions for additional information about the features of each position. shows the withdrawable unit operating
positions.
Connected - Line, load, control, network and PE
connections are all engaged. Closing the unit door
ensures the withdraw lever is in the connected position.
To engage the interlock or turn the disconnect means to
the ON/I position, the unit door must be fully closed.
24
Test - Control, network and PE connections are engaged.
Line and load connections are isolated. This allows the user
to verify control and network wiring. Units can be locked in
this position.
Disconnected - The unit remains housed in the column,
but no connections are present. This is an isolated position.
Units can be locked in the disconnected position.
Withdrawn - Withdrawable units can be completely
removed from the columns. When units are withdrawn
from the MCC, they are isolated from connections.
Withdrawn units can be locked to prevent insertion.
Withdrawable Unit Operating Positions
Operating
Position
Connection Present
Line
Load
PE
Control
Network
Connected
x
x
x
x
x
x(1)
x
x
x
x
Test
Lockable in
Position
Disconnected
Connections not present. Unit remains inserted in column.
x
Withdrawn
Connections not present. Unit is removed from column.
x
(1) Unit is lockable when door is closed.
25
Fixed (Frame-mounted) Unit Design Features
Fixed units are permanently mounted in the column, all connections are made directly to the components. Fixed units
range from 2 up to 24 module sizes. For units 12 module size and above, fixed unit design is standard.
Fixed (Frame-mounted) Unit Connections
In fixed units, line, load, PE and control connections are made directly to components. Network connections can be made
through fixed or plug-in terminal blocks. shows possible unit connections.
Unit Connections
Withdrawable Unit
Connections
Fixed Unit Connections
Line
Withdrawable
Fixed
Load
Withdrawable
Fixed
PE
Withdrawable
Fixed
Control
Withdrawable
Fixed
Network
Withdrawable
Disconnectable
Operating Handle
Rotary Operating Handle
An industrial, heavy duty, rotary operating handle is supplied for control of the disconnecting means in each unit. When
the unit door is closed, the handle is engaged with the disconnect means.
The operating handle can be locked in the OFF/O position with up to three 8 mm diameter shackle padlocks. The
operating handle can be modified to enable locking in the ON/I position.
The unit operating handle is interlocked with the unit door to help prevent opening the unit door unless the disconnect
means is in the OFF/O position. An externally operated defeater is provided to access the unit without interrupting service.
The operating handle is interlocked with the unit so the unit cannot be inserted or withdrawn with the operating handle
in the ON/I position.
Rotary Operating
Handle
26
Rotary Operating
Handle for One
Module Units
Flange-mounted Handle
Vertical Flange
Operating
Handle
Flange style disconnect handles (vertical or horizontal
mounted) are available for units with circuit breaker
disconnects. The flange handle helps prevent the disconnect
from being switched to the ON/I position when the unit door is
open.
Units with vertical flange handles must be at least 4 modules.
Units with horizontal flange handles must be at least 2
modules.
Unit Disconnect Means
The unit disconnect switch is available as a circuit breaker or fusible disconnect.
Withstand ratings for combination starter units are based on the short circuit protective devices and components
selected.
Circuit Breakers
Allen-Bradley circuit breakers are provided as the disconnecting means for units with a circuit breaker unit main switch.
Bulletin 140M motor circuit protectors are used for combination motor control units. Bulletin 140M motor protection
circuit breakers and Bulletin 140U molded case circuit breakers are utilized for feeder units.
Circuit breaker unit main switches are available in the following ratings based on circuit breaker and component selection.
Circuit Breaker Ratings
Rating
Amperage and Voltage
Type 1
Up to 100 kA at 400 V
Type 2
Up to 65 kA at 400 V
Up to 50 kA at 500 V
Up to 25 kA at 600 V
Up to 10 kA at 690 V
27
Disconnect Switches
When specified, Allen-Bradley disconnect switches are provided. The Bulletin 194R fused disconnect switch is used in
combination starter and feeder units. One module combination starter and feeder units utilize the Bulletin 194E unfused
switch.
When requested, NH fuses are supplied in the following styles: DIN gG and DIN aM.
Disconnect unit main switches are available in the following ratings based on component and fuse selection.
Disconnect Ratings
Rating
Amperage and Voltage(1)
Type 2
Up to 100 kA at 400 V
Up to 100 kA at 500 V
Up to 100 kA at 600 V
(1) For 690V information, please consult the factory.
Stab Assembly
Power Stab Assembly
The two-piece power stab housing is made of high strength,
non-tracking glass polyester material and provides a separate,
isolated pathway for each phase.
The power cable connection at the plug-in stab is made with a
maintenance free crimp style connection. There is no exposed
wiring at the back of the unit between the disconnecting means
and the plug-in stabs.
Unit plug-in power stabs are rated 225 A. The stabs are made of tin-plated copper for a low resistance connection and are
designed to tighten during heavy current surges.
The free-floating and self aligning unit plug-in power stabs are backed by stainless steel spring clips to provide and
maintain a high pressure, four-point connection to the vertical power bus.
28
Neutral Stab
Neutral Stab Assembly
The neutral stab assembly can be
supplied on withdrawable units for
4-wire systems. The neutral stab
assembly has the same design and
features as the power stab assembly,
but is a separate piece.
One Module Stab Assembly
The one module stab assembly
consists of a receptacle for line and
load connections that plugs into a
subplate connected to the vertical
power bus. The two guide pins help
ensure the connector is properly
aligned. Because of the subplate
connection, one module units must be
installed in pairs.
One module units stabs are rated
at 32 A.
Protective Earth Contact
An unplated copper PE contact is provided on withdrawable units. This contact establishes a connection with the PE
circuit before other connections are made and is the last withdrawable connection to be disconnected.
Control and Network Connections
Plug-in control and network connections are made automatically for withdrawable units. A 15-pin connector plug, rated
at 10 A, is used for control connections. DeviceNet network connections are made through a separate connector. The
control and network connectors use a spring-loaded mechanism to ensure proper connection.
29
PE Contact, Control and Network Connections
PE Contact
Control
Connection
Network
Connection
Unit Doors
Each unit is provided with a removable unit door, mounted on hinges with
removable pins. Unit doors are held closed with ¼ turn latches. See Door
Latches on page 31 for more explanation.
The unit door is mounted to the structure so it is not necessary to remove a nit
door when installing or removing units. The door can be closed with the unit
removed to isolate the power bus. A unit door can be removed from any
location on the MCC without disturbing other unit doors.
Control stations for pilot devices and low profile external reset buttons for overload relays are often mounted to the unit
door.
30
Door Latches
There are two types of door latches available for the 2500 MCC. Standard CENTERLINE 2500 MCCs have quarter-turn door
latches. If you select an MCC with ArcShield, the MCC will have arc containment door latches.
Door Latches (Standard)
Door latches are provided on unit and vertical wireway doors to hold the door closed and isolate personel from the
column. Door latches can be locked or released by rotating the latch ¼ turn. An arrow on the door latch head indicates the
position of the latch.
Released Position
Locked Position
Arc Containment Latch
Optional arc containment latches are available. Arc containment latches help protect personnel in the vicinity of an MCC if
an arc fault occurs when structure doors are closed and latched. Arc containment latches can be locked or released by
rotating the latch ¼ turn.
Released Position
Locked Position
31
Nameplates
The MCC master nameplate, when specified, is available with up to five lines of engraving and is located on the top
horizontal wireway cover.
Unit nameplates are available and can accommodate three or four lines of engraving. The following types of unit
nameplates are available:
• Clear cardholders - insert printed cards into cardholder
• Engraved acrylic nameplates - white with black lettering or black with white lettering
• Engraved phenolic nameplates - white with black lettering, black with white lettering or red with white lettering
Nameplates are secured using two steel self-tapping screws. Stainless steel screws are also available.
Unit Nameplate
Control Power
Unit control power is specified as: 24V DC, or 110, 115, 120, 220, 230 or 240V AC.
Unit control power is normally supplied by a single common control power transformer unit within each MCC lineup. This
common control power allows the test function of withdrawable units to work most effectively. The common control
source operates at line voltage with an option for common control fusing.
Individual control circuit transformers, mounted in each unit, are available. One leg of the secondary side of the control
circuit transformer is fused while the other leg is connected to PE. Primary protection is then provided by primary fusing.
Control Wire
Control wire is ‘multistrand’ or ‘stranded’ copper. (Need to add type of insulation and rating (90 °C what)
Wire markers are sleeve type; heat shrink is optional.
Power Wire
The power wire is double-insulated copper and rated at 105°C or higher. The power wire is sized to meet the current rating
of the unit, with a minimum size of 6 mm2.
NEED FAULT FREE ZONE TEXT
32
Mounting Configurations
The MCC is available in two mounting configurations – front-only and
double-front.
• Front-only columns are joined and installed side-by-side.
• Double-front columns are two separate columns joined at the rear, back
plates are removed. The two columns have separate power bus systems
providing the same phasing for all units. The horizontal power bus is linked,
front to rear, with a factory installed U-shaped bus splice assembly.
For shipping purposes, only 600mm deep columns can have double-front
configurations.
Front-only (standard configuration)
Double-front (optional configuration)
33
Units
Columns can be populated with several different types of units, such as mains,
feeders, direct on line starters and contactors, soft starters, AC drives and PLCs.
One Module Unit
DeviceNet Scanner Modules
DeviceNet in the MCC requires a DeviceNet scanner module that meets DeviceNet requirements. The scanner module
may be located in the MCC or mounted remotely.
Network Linking Devices
Network linking devices allow CENTERLINE 2500 MCC customers to connect to different communication networks. With
network linking devices you are able to connect to ControlNet or EtherNet/IP directly from you MCC. NetLinx technology
enables you to link from one network to another easily, making data transfer from the MCC’s DeviceNet network onto the
controller’s EtherNet/IP or ControlNet simple.
Linking Devices
Unit Description
Module Size
1 = 80 mm
ControlNet to DeviceNet Bridge
2
Ethernet to DeviceNet Bridge
2
Profibus to DeviceNet Bridge
2
DeviceNet Power Supply
DeviceNet in the MCC requires a power supply providing 24V DC and rated no less than 8 amperes.
A quality power supply is essential to reliable system operation. To ensure system integrity and reliability, the
Allen-Bradley Bulletin 2500-DPS 8 A DeviceNet Power Supply unit is recommended. This power supply meets DeviceNet
requirements, ODVA approval, and is supplied with a buffer for enhanced ride-through performance. A redundant power
supply is also available for added reliability.
.
DeviceNet Power Supply Units
Unit Description
Module Size
1 = 80 mm
DeviceNet Power Supply
2
Redundant DeviceNet Power Supply
4
Back-up DeviceNet Power Supply
34
Main Incoming Line (Lug-only) Compartment
Main incoming line lug compartments are available in either the top or bottom entry and use mechanical screws or crimp/
compression lugs. The compartments are front accessible.
Main Incoming Line Compartments
Incoming Line Compartment
Rating
6 modules (480 mm), variable column width
600 A (using vertical power bus)
24 modules (full column), 700 mm wide
800, 1250, 1600, 2000 A
24 modules (full column), 800 mm wide
2500, 3200, 4000 A
Main Incoming Circuit Breaker
Air circuit breakers (ACB) or molded case circuit breakers (MCCB) are
available for main incoming circuit breakers.
Main circuit breaker units are front accessible with removable protective
barriers on the line side, helping reduce the possibility of accidental
contact with line terminals.
The ACB compartments have trip ratings available from 400…4000 A.
These ACBs are available with a drawout or fixed style. The ACBs for
mains include an option to utilize 4-pole breakers. ACBs may be
integrated into auto-transfer switch schemes.
This table provides more information on available incoming air circuit
breaker compartment arrangements and sizes.
MCCBs are inverse time circuit breakers and can be classified as thermal
magnetic or electronic.
Incoming Air Circuit Breaker Compartment Arrangement
Incoming Air Circuit Breaker Compartment
Rating
24 modules (full column), 800 mm deep x 800 mm wide
800, 1250, 1600, 2000 A
24 modules (full column), 800 mm deep x 900 mm wide
2500, 3200, 4000 A
Main Incoming Fusible Disconnect
Mains with fusible disconnects are available. Fuses can be factory installed or supplied and installed by others.
35
Pilot Devices
Pilot devices are housed in a door mounted control station. Each
control station can accommodate up to four 22 mm devices.
Multiple control stations can be mounted on a unit door, if more
than four pilot devices are required.
Control stations are equipped with a quick connect plug for ease
in connecting and disconnecting control wiring.
The control station is easily removed using captive screws. If a control station is removed, closing plates are available to
cover the opening in the unit door and provide isolation.
Main and Feeder Units
Incoming Main Lug Compartments and Outgoing Feeder Lug Compartments
The line lug compartments provide a lug connection for incoming lines (mains) to distribute power to the motor control
center or for outgoing cables (feeders) to feed power from the motor control center to an external load. Line lug
compartments are available in ratings from 300…4000 A and are fixed mounted.
Main and Feeder Circuit Breaker Units
The circuit breaker units have trip ratings available from 15…4000 A. These units are available with thermal magnetic trip
circuit breaker up to 1200 A and electronic trip circuit breaker 100 A and above. The feeder circuit breaker units are
available in a withdrawable unit style up to 225 A and are fixed mounted for ratings 250 A and above. The main circuit
breaker units are fixed mounted for all ratings.
For main and feeder circuit breaker unit selection go to page .
For main and feeder circuit breaker option selection go to page .
Mains, Air Circuit Breakers
Amperes
Circuit Breaker
Catalog Number
Module Size
(1)
1 = 80 mm
Column Width (mm)(3)
Column Depth (mm)(4)
800
140RX-NS**D-D80
24(2)
700
600, 800
1250
140RX-NS**D-E12
24(2)
700
600, 800
1600
140RX-NS**D-E16
(2)
700
600, 800
2000
140RX-RS**D-E20
(2)
24
800
800
2500
140RX-RS**D-E25
24(2)
800
800
3200
140RX-SS**D-E32
(2)
900
800
4000
140RX-SS**D-E40
(2)
900
800
(1)
(2)
(3)
(4)
36
24
24
24
To complete the catalog numbers, please contact the factory
Fixed mount style
Available column widths
Available column depths
Mains, Thermal Magnetic Circuit Breakers
Amperes
Circuit Breaker
Module Size
Catalog Number
1 = 80 mm
Column Width (mm)(2)
Column Depth (mm)(3)
150
140U-J*D3-D15
4
(1)
700, 800, 900, 1000
600, 800
200
140U-J*D3-D20
4
(1)
700, 800, 900, 1000
600, 800
250
140U-J*D3-D25
4(1)
700, 800, 900, 1000
600, 800
300
140U-L*D3-D30
8
(1)
700, 800, 900, 1000
600, 800
350
140U-L*D3-D35
8
(1)
700, 800, 900, 1000
600, 800
400
140U-L*D3-D40
8
(1)
700, 800, 900, 1000
600, 800
500
140U-L*D3-D50
8
(1)
700, 800, 900, 1000
600, 800
600
140U-L*D3-D60
8
(1)
700, 800, 900, 1000
600, 800
700
140U-M*D3-D70
(1)
700, 800, 900, 1000
600, 800
800
140U-M*D3-D80
(1)
700, 800, 900, 1000
600, 800
12
12
(1) Fixed mount style
(2) Available column widths
(3) Available column depths
Mains, Electronic with LSI Protection Type
Amperes
Circuit Breaker
Module Size
Catalog Number
1 = 80 mm
Column Width (mm)(2)
Column Depth (mm)(3)
150
140U-J*H3-D16
2
700, 800, 900, 1000
600, 800
250
140U-J*H3-D25
4
(1)
700, 800, 900, 1000
600, 800
400
140U-L*H3-D40
8
(1)
700, 800, 900, 1000
600, 800
600
140U-L*H3-D60
8(1)
700, 800, 900, 1000
600, 800
800
140U-M*H3-D80
(1)
700, 800, 900, 1000
600, 800
1200
140U-N*H3-E12
700, 800, 900, 1000
600, 800
8
(1)
12
(1) Fixed mount style
(2) Available column widths
(3) Available column depths
Main Unit Options
•
•
•
•
•
Auxiliary contact for circuit breaker
Shunt trip coil for circuit breaker
Alarm contact for circuit breaker
Minimum voltage coil (undervoltage) for circuit breaker
Combination auxiliary contact and alarm contact for circuit breaker
37
Feeders, Air Circuit Breakers
Amperes
Circuit Breaker
Catalog Number
Module Size
(1)
1 = 80 mm
Column Width (mm)(3)
Column Depth (mm)(4)
800
140RX-NS**D-D80
24(2)
700
600, 800
1250
140RX-NS**D-E12
24(2)
700
600, 800
1600
140RX-NS**D-E16
24
(2)
700
600, 800
2000
140RX-RS**D-E20
24
(2)
800
800
2500
140RX-RS**D-E25
24(2)
800
800
3200
140RX-SS**D-E32
24
(2)
900
800
4000
140RX-SS**D-E40
24
(2)
900
800
(1)
(2)
(3)
(4)
To complete the catalog numbers, please contact the factory
Fixed mount style
Available column widths
Available column depths
Feeders, Thermal Magnetic
Amperes
Circuit Breaker
Module Size
Catalog Number
1 = 80 mm
Column Width (mm)(2)
Column Depth (mm)(3)
10
140M-C2E-C10
1
700, 800, 900, 1000
600, 800
16
140M-D8E-C16
1
700, 800, 900, 1000
600, 800
20
140M-D8E-C20
1
700, 800, 900, 1000
600, 800
25
140M-D8E-C25
1
700, 800, 900, 1000
600, 800
30
140M-F8E-C32
2
700, 800, 900, 1000
600, 800
35
140M-F8E-C45
2
700, 800, 900, 1000
600, 800
40
140M-F8E-C45
2
700, 800, 900, 1000
600, 800
45
140M-F8E-C45
2
700, 800, 900, 1000
600, 800
50
140U-H*C3-C50
2
700, 800, 900, 1000
600, 800
60
140U-H*C3-C60
2
700, 800, 900, 1000
600, 800
70
140U-H*C3-C70
2
700, 800, 900, 1000
600, 800
80
140U-H*C3-C80
2
700, 800, 900, 1000
600, 800
90
140U-H*C3-C90
2
700, 800, 900, 1000
600, 800
100
140U-H*C3-D10
2
700, 800, 900, 1000
600, 800
110
140U-H*C3-D11
2
700, 800, 900, 1000
600, 800
125
140U-H*C3-D12
2
700, 800, 900, 1000
600, 800
150
140U-J*D3-D15
2
700, 800, 900, 1000
600, 800
175
140U-J*D3-D17
2
700, 800, 900, 1000
600, 800
200
140U-J*D3-D20
2
700, 800, 900, 1000
600, 800
225
140U-J*D3-D22
2
700, 800, 900, 1000
600, 800
250
140U-J*D3-D25
(1)
700, 800, 900, 1000
600, 800
300
140U-L*D3-D30
(1)
700, 800, 900, 1000
600, 800
350
140U-L*D3-D35
(1)
8
700, 800, 900, 1000
600, 800
400
140U-L*D3-D40
8(1)
700, 800, 900, 1000
600, 800
500
140U-L*D3-D50
(1)
700, 800, 900, 1000
600, 800
600
140U-L*D3-D60
(1)
700, 800, 900, 1000
600, 800
38
4
8
8
8
Feeders, Thermal Magnetic
Amperes
Circuit Breaker
Module Size
Catalog Number
1 = 80 mm
700
140U-M*D3-D70
800
140U-M*D3-D80
1200
140U-N*H3-E12
Column Width (mm)(2)
Column Depth (mm)(3)
8
(1)
700, 800, 900, 1000
600, 800
8
(1)
700, 800, 900, 1000
600, 800
700, 800, 900, 1000
600, 800
(1)
12
(1) Fixed mount style
(2) Available column widths
(3) Available column depths
Feeders, Electronic with LSI Protection Type
Amperes
Circuit Breaker
Module Size
Catalog Number
1 = 80 mm
Column Width
(mm)(2)
Column Depth (mm)(3)
150
140U-J*H3-D16
2
700, 800, 900, 1000
600, 800
250
140U-J*H3-D25
4(1)
700, 800, 900, 1000
600, 800
400
140U-L*H3-D40
8
(1)
700, 800, 900, 1000
600, 800
600
140U-L*H3-D60
8(1)
700, 800, 900, 1000
600, 800
800
140U-M*H3-D80
(1)
700, 800, 900, 1000
600, 800
1200
140U-N*H3-E12
700, 800, 900, 1000
600, 800
8
(1)
12
(1) Fixed mount style
(2) Available column widths
(3) Available column depths
Feeder Unit Options
•
•
•
•
•
Auxiliary contact for circuit breaker
Shunt trip coil for circuit breaker
Alarm contact for circuit breaker
Minimum voltage coil (undervoltage) for circuit breaker
Combination auxiliary contact and alarm contact for circuit breaker
39
Starter Units
Direct On Line Non-reversing Starter Units
These combination direct on line non-reversing starter units are supplied with
Allen-Bradley Bulletin 100C or 100D contactors and either a fusible or circuit
breaker disconnect. These units are available with a E1 Plus or E3 Plus overload
relay and available with or without an external reset button for the overload
relay. These units are available in a withdrawable unit style and a fixed unit style.
For direct on line non-reversing starter unit selection, go to page .
For direct on line non -reversing starter option selection, go to page .
Direct On Line Non-reversing Starter Units
Motor Rating
Circuit Breaker
Non-reversing
Contactor
Electronic Overload Relay
Module Size
Input Voltage
kW(1)
Cat. No.(2)
Cat. No.(2)
E1 Plus Cat. No.(3)
E3 Plus Cat. No.
1 = 80 mm
380/415V
0.8
140M-C2N-***
100-C16*10
193-EECB
---
1
0.8
140M-C2N-***
100-C16*10
---
193-EC2AB
3
140M-D8N-***
100-C16*10
193-EEDB
---
3
140M-D8N-***
100-C16*10
---
193-EC2BB
5.5
140M-D8N-***
100-C16*10
193-EEDB
---
5.5
140M-D8N-***
100-C16*10
---
193-EC2BB
7.5
140M-D8N-***
100-C16*10
193-EEEB
---
7.5
140M-D8N-***
100-C16*10
---
193-EC2CB
11
140M-D8N-***
100-C23*10
193-EEEB
---
11
140M-D8N-***
100-C23*10
---
193-EC2CB
15
140M-F8N-***
100-C37*10
193-EEFD
---
15
140M-F8N-***
100-C37*10
---
193-EC2DD
18.5
140M-H8P-***
100-C37*10
193-EEFD
---
18.5
140M-H8P-***
100-C37*10
---
193-EC2DD
22
140M-H8P-***
100-C85*10
193-EEGE
---
22
140M-H8P-***
100-C85*10
---
193-EC2EE
37
140M-H8P-***
100-C85*10
193-EEGE
---
37
140M-H8P-***
100-C85*10
---
193-EC2EE
45
140M-H8P-***
100-C85*10
193-EEGE
---
45
140M-H8P-***
100-C85*10
---
193-EC2EE
75
140M-J8P-***
100-D210*11
193-EEJG
---
---
10
75
140M-J8P-***
100-D210*11
---
193-EC3GG
193-CBCT4
10
90
140M-J8P-***
100-D210*11
193-EEJG
---
---
10
90
140M-J8P-***
100-D210*11
---
193-EC3GG
193-CBCT4
10
110
140M-J8P-***
100-D210*11
193-EEJG
---
---
10
110
140M-J8P-***
100-D210*11
---
193-EC3HG
193-CBCT4
10
160
140M-L8P-***
100-D300*11
193-EELG
---
---
12(4)
160
140M-L8P-***
100-D300*11
---
193-EC3HG
193-CBCT4
12(4)
185
140M-L8P-***
100-D420*11
193-EELG
---
---
14(4)
185
140M-L8P-***
100-D420*11
---
193-EC3JG
193-CBCT4
14(4)
IP20/42/54
(1)
(2)
(3)
(4)
40
---
1
---
1
1
---
1
1
---
2
2
---
2
2
---
2
2
---
2
2
---
4
4
---
4
4
---
4
4
220
140M-L8P-***
100-D420*11
193-EELG
---
---
14(4)
220
140M-L8P-***
100-D420*11
---
193-EC3JG
193-CBCT4
14(4)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Fixed mount style
Direct On Line Non-reversing Starter Units (continued)
Motor Rating
Circuit Breaker
Non-reversing
Contactor
Electronic Overload Relay
Cat. No.(2)
Cat. No.(2)
E1 Plus Cat. No.(3)
E3+ Cat. No.
Input Voltage
kW(1)
440/460/480V
0.75
140M-C2N-***
100-C16*10
193-EECB
---
IP20/42/54
0.75
140M-C2N-***
100-C16*10
---
193-EC2AB
3
140M-D8N-***
100-C16*10
193-EEDB
---
3
140M-D8N-***
100-C16*10
---
193-EC2BB
5.5
140M-D8N-***
100-C16*10
193-EEDB
---
5.5
140M-D8N-***
100-C16*10
---
193-EC2BB
7.5
140M-D8N-***
100-C16*10
193-EEEB
---
7.5
140M-D8N-***
100-C16*10
---
193-EC2CB
(1)
(2)
(3)
(4)
Module Size
11
140M-D8N-***
100-C23*10
193-EEEB
---
11
140M-D8N-***
100-C23*10
---
193-EC2CB
15
140M-F8N-***
100-C37*10
193-EEFD
---
15
140M-F8N-***
100-C37*10
---
193-EC2DD
18.5
140M-F8N-***
100-C37*10
193-EEFD
---
18.5
140M-F8N-***
100-C37*10
---
193-EC2DD
22
140M-H8P-***
100-C43*10
193-EEFD
---
22
140M-H8P-***
100-C43*10
---
193-EC2DD
37
140M-H8P-***
100-C85*10
193-EEGE
---
37
140M-H8P-***
100-C85*10
---
193-EC2EE
45
140M-H8P-***
100-C85*10
193-EEGE
---
45
140M-H8P-***
100-C85*10
---
193-EC2EE
1 = 80 mm
---
1
1
---
1
1
---
1
1
---
2
2
---
2
2
---
2
2
---
2
2
---
4
4
---
4
4
---
4
4
75
140M-J8P-***
100-D210*11
193-EEJG
---
---
10
75
140M-J8P-***
100-D210*11
---
193-EC3GG
193-CBCT4
10
90
140M-J8P-***
100-D210*11
193-EEJG
---
---
10
90
140M-J8P-***
100-D210*11
---
193-EC3GG
193-CBCT4
10
110
140M-J8P-***
100-D210*11
193-EEJG
---
---
10
110
140M-J8P-***
100-D210*11
---
193-EC3GG
193-CBCT4
10
160
140M-L8P-***
100-D300*11
193-EELG
---
---
12(4)
160
140M-L8P-***
100-D300*11
---
193-EC3HG
193-CBCT4
12(4)
185
140M-L8P-***
100-D300*11
193-EELG
---
---
12(4)
185
140M-L8P-***
100-D300*11
---
193-EC3JG
193-CBCT4
12(4)
220
140M-L8P-***
100-D420*11
193-EELG
---
---
14(4)
220
140M-L8P-***
100-D420*11
---
193-EC3JG
193-CBCT4
14(4)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Fixed mount style
41
Direct On Line Non-reversing Starter Unit Options
•
•
•
•
•
•
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
• Selector switch
– Two position
– Three position
• DeviceNet starter auxiliary
– (4) 120V AC inputs and (2) 120V AC outputs
– (4) 24V DC inputs and (2) 120V AC outputs
• Back-up DeviceNet power supply
42
Direct On Line Reversing Starter Units
These combination direct on line reversing starter units are
supplied with Allen-Bradley Bulletin 104C or 104D contactors
and either a fusible or circuit breaker disconnect. The starters
are mechanically and electrically interlocked to avoid both
contactors being closed simultaneously.
These units are available with an E1 Plus or E3 Plus overload relay and available with or without an external reset button
for the overload relay. These units are available in a withdrawable unit style and a fixed unit style.
Direct On Line Reversing Starter Units
Motor Rating
Circuit Breaker
Reversing
Contactor
Electronic Overload Relay
Input Voltage
kW(1)
Cat. No.(2)
Cat. No.(2)
E1 Plus Cat. No.(3)
E3 Plus Cat. No.
380/415V
0.8
140M-C2N-***
104-C16*22
193-EECB
---
IP20/42/54
0.8
140M-C2N-***
104-C16*22
---
193-EC2AB
3
140M-D8N-***
104-C16*22
193-EEDB
---
3
140M-D8N-***
104-C16*22
---
193-EC2BB
5.5
140M-D8N-***
104-C16*22
193-EEDB
---
(1)
(2)
(3)
(4)
5.5
140M-D8N-***
104-C16*22
---
193-EC2BB
7.5
140M-D8N-***
104-C16*22
193-EEEB
---
7.5
140M-D8N-***
104-C16*22
---
193-EC2CB
11
140M-D8N-***
104-C23*22
193-EEEB
---
11
140M-D8N-***
104-C23*22
---
193-EC2CB
15
140M-F8N-***
104-C37*22
193-EEFD
---
15
140M-F8N-***
104-C37*22
---
193-EC2DD
18.5
140M-H8P-***
104-C37*22
193-EEFD
---
18.5
140M-H8P-***
104-C37*22
---
193-EC2DD
22
140M-H8P-***
104-C85*22
193-EEGE
---
22
140M-H8P-***
104-C85*22
---
193-EC2EE
37
140M-H8P-***
104-C85*22
193-EEGE
---
37
140M-H8P-***
104-C85*22
---
193-EC2EE
45
140M-H8P-***
104-C85*22
193-EEGE
---
45
140M-H8P-***
104-C85*22
---
193-EC2EE
75
140M-J8P-***
104-D210*24
193-EEJG
---
75
140M-J8P-***
104-D210*24
---
90
140M-J8P-***
104-D210*24
193-EEJG
90
140M-J8P-***
104-D210*24
110
140M-J8P-***
110
160
Module Size
1 = 80 mm
---
2
2
---
2
2
---
2
2
---
2
2
---
2
2
---
2
2
---
2
2
---
4
4
---
4
4
---
4
4
---
10
193-EC3GG
193-CBCT4
10
---
---
10
---
193-EC3GG
193-CBCT4
10
104-D210*24
193-EEJG
---
---
10
140M-J8P-***
104-D210*24
---
193-EC3HG
193-CBCT4
10
140M-L8P-***
104-D300*24
193-EELG
---
---
14(4)
160
140M-L8P-***
104-D300*24
---
193-EC3HG
193-CBCT4
14(4)
185
140M-L8P-***
104-D420*24
193-EELG
---
---
14(4)
185
140M-L8P-***
104-D420*24
---
193-EC3JG
193-CBCT4
14(4)
220
140M-L8P-***
104-D420*24
193-EELG
---
---
14(4)
220
140M-L8P-***
104-D420*24
---
193-EC3JG
193-CBCT4
14(4)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Fixed mount style
43
Direct On Line Reversing Starter Units (continued)
Motor Rating
Circuit Breaker
Reversing
Contactor
Electronic Overload Relay
Cat. No.(2)
Cat. No.(2)
E1 Plus Cat. No.(3)
E3 Plus Cat. No.
Input Voltage
kW(1)
440/460/480V
0.75
140M-C2N-***
104-C16*22
193-EECB
---
IP20/42/54
0.75
140M-C2N-***
104-C16*22
---
193-EC2AB
3
140M-D8N-***
104-C16*22
193-EEDB
---
3
140M-D8N-***
104-C16*22
---
193-EC2BB
(1)
(2)
(3)
(4)
44
Module Size
5.5
140M-D8N-***
104-C16*22
193-EEDB
---
5.5
140M-D8N-***
104-C16*22
---
193-EC2BB
7.5
140M-D8N-***
104-C16*22
193-EEEB
---
7.5
140M-D8N-***
104-C16*22
---
193-EC2CB
1 = 80 mm
---
2
2
---
2
2
---
2
2
---
2
2
---
2
11
140M-D8N-***
104-C23*22
193-EEEB
---
11
140M-D8N-***
104-C23*22
---
193-EC2CB
15
140M-F8N-***
104-C37*22
193-EEFD
---
15
140M-F8N-***
104-C37*22
---
193-EC2DD
18.5
140M-F8N-***
104-C37*22
193-EEFD
---
18.5
140M-F8N-***
104-C37*22
---
193-EC2DD
22
140M-H8P-***
104-C43*22
193-EEFD
---
22
140M-H8P-***
104-C43*22
---
193-EC2DD
37
140M-H8P-***
104-C85*22
193-EEGE
---
37
140M-H8P-***
104-C85*22
---
193-EC2DD
45
140M-H8P-***
104-C85*22
193-EEGE
---
45
140M-H8P-***
104-C85*22
---
193-EC2EE
75
140M-J8P-***
104-D210*24
193-EEJG
---
---
10
75
140M-J8P-***
104-D210*24
---
193-EC3GG
193-CBCT4
10
90
140M-J8P-***
104-D210*24
193-EEJG
---
---
10
90
140M-J8P-***
104-D210*24
---
193-EC3GG
193-CBCT4
10
110
140M-J8P-***
104-D210*24
193-EEJG
---
---
10
110
140M-J8P-***
104-D210*24
---
193-EC3GG
193-CBCT4
10
160
140M-L8P-***
104-D300*24
193-EELG
---
---
14(4)
160
140M-L8P-***
104-D300*24
---
193-EC3HG
193-CBCT4
14(4)
185
140M-L8P-***
104-D300*24
193-EELG
---
---
14(4)
185
140M-L8P-***
104-D300*24
---
193-EC3JG
193-CBCT4
14(4)
220
140M-L8P-***
104-D420*24
193-EELG
---
---
14(4)
220
140M-L8P-***
104-D420*24
---
193-EC3JG
193-CBCT4
14(4)
2
---
2
2
---
2
2
---
4
4
---
4
4
---
4
4
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
If side mount modules are required, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Fixed mount style
Direct On Line Reversing Starter Unit Options
•
•
•
•
•
•
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
• Selector switch
– Two position
– Three position
• DeviceNet starter auxiliary
– (4) 120V AC inputs and (2) 120V AC outputs
– (4) 24V DC inputs and (2) 120V AC outputs
• Back-up DeviceNet power supply
45
Soft Starter Units
Soft staters, referred to as reduced voltage solid state units, contain a
microprocessor-controlled motor controller, control circuit transformer and
either a fusible or circuit breaker disconnect. These units are available as
withdrawable or fixed units.
The following soft starters are available for CENTERLINE 2500 MCC’s:
• SMC-3 soft starter
• SMC Flex soft starter
SMC-3 Soft Starters features:
• Three starting modes: soft start, kick start and current limit
• Electronic overload protection with selectable overload trip class
• Motor and system diagnostics
• Soft stop
• Integrated bypass contactor
SMC Flex Soft Starters features:
• Seven standard modes of operation: soft start, current limit start, dual
ramp, full voltage, linear speed acceleration, preset slow speed and soft
stop
• Optional modes of operation: pump control, Smart Motor BrakingTM,
Accu-StopTM and slow speed with braking
• Integral SCR bypass
• Electronic overload protection with selectable overload trip class
• Full metering and diagnostics
• DPI communication
For soft starter unit selection, go to page .
For soft starter option selection, go to page .
46
One Line Diagram
SMC-3 Soft Starter Units
Motor Rating
Input Voltage
kW(1)
Circuit Breaker
SMC-3
High Interrupting
Capacity Fuses
Module Size
Cat. No.(2)
Cat. No.(2)
Cat. No.(3)
1 = 80 mm
380/415V,
0.75
140M-C2N-***
150-C3NBD
---
1
IP20/42/54
0.75
140M-C2N-***
150-C3NBD
4A, SIZE 000
6
1.1
140M-D8N-***
150-C3NBD
---
1
1.1
140M-D8N-***
150-C3NBD
4A, SIZE 000
6
4
140M-D8N-***
150-C9NBD
---
1
4
140M-D8N-***
150-C9NBD
16A, SIZE 000
6
7.5
140M-D8N-***
150-C19NBD
---
2
(1)
(2)
(3)
(4)
7.5
140M-D8N-***
150-C19NBD
20A, SIZE 000
6
11
140M-D8N-***
150-C25NBD
---
2
11
140M-D8N-***
150-C25NBD
40A, SIZE 000
6
15
140M-F8P-***
150-C30NBD
---
2
15
140M-F8P-***
150-C30NBD
40A, SIZE 000
6
18.5
140M-H8P-***
150-C37NBD
---
2
18.5
140M-H8P-***
150-C37NBD
50A, SIZE 000
6
22
140M-H8P-***
150-C43NBD
---
4
22
140M-H8P-***
150-C43NBD
63A, SIZE 000
6
30
140M-H8P-***
150-C60NBD
---
4
30
140M-H8P-***
150-C60NBD
80A, SIZE 00
6
45
140M-H8P-***
150-C85NBD
---
4
45
140M-H8P-***
150-C85NBD
125A, SIZE 00
6
55
140M-J8P-***
150-C108NBD
---
12(4)
55
140M-J8P-***
150-C108NBD
125A, SIZE 00
12(4)
75
140M-J8P-***
150-C135NBD
---
12(4)
75
140M-J8P-***
150-C135NBD
200A, SIZE 1
12(4)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
High interrupting capacity fuses are optional
Fixed mount style
47
SMC-3 Soft Starter Units (continued)
Motor Rating
Circuit Breaker
SMC-3
High Interrupting
Capacity Fuses
Module Size
Cat. No.(2)
Cat. No.(2)
Cat. No.(3)
1 = 80 mm
Input Voltage
kW(1)
440/460/480V,
0.75
140M-C2N-***
150-C3NBD
---
1
IP20/42/54
0.75
140M-C2N-***
150-C3NBD
4A, SIZE 000
6
1.1
140M-D8N-***
150-C3NBD
---
1
1.1
140M-D8N-***
150-C3NBD
4A, SIZE 000
6
4
140M-D8N-***
150-C9NBD
---
1
4
140M-D8N-***
150-C9NBD
16A, SIZE 000
6
7.5
140M-D8N-***
150-C19NBD
---
2
7.5
140M-D8N-***
150-C19NBD
20A, SIZE 000
6
(1)
(2)
(3)
(4)
48
11
140M-D8N-***
150-C25NBD
---
2
11
140M-D8N-***
150-C25NBD
40A, SIZE 000
6
15
140M-F8P-***
150-C30NBD
---
2
15
140M-F8P-***
150-C30NBD
40A, SIZE 000
6
18.5
140M-H8P-***
150-C37NBD
---
2
18.5
140M-H8P-***
150-C37NBD
50A, SIZE 000
6
22
140M-H8P-***
150-C43NBD
---
4
22
140M-H8P-***
150-C43NBD
63A, SIZE 000
6
30
140M-H8P-***
150-C60NBD
---
4
30
140M-H8P-***
150-C60NBD
80A, SIZE 00
6
45
140M-H8P-***
150-C85NBD
---
4
45
140M-H8P-***
150-C85NBD
125A, SIZE 00
6
55
140M-J8P-***
150-C108NBD
---
12(4)
55
140M-J8P-***
150-C108NBD
125A, SIZE 00
12(4)
75
140M-J8P-***
150-C135NBD
---
12(4)
75
140M-J8P-***
150-C135NBD
200A, SIZE 1
12(4)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
High interrupting capacity fuses are optional
Fixed mount style
SMC-3 Soft Starter Unit Options
•
•
•
•
•
•
•
•
•
•
•
•
•
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
Selector switch
– Two position
– Three position
DeviceNet starter auxiliary
– (4) 120VAC inputs and (2) 120VAC outputs
– (4) 24VDC inputs and (2) 120VAC outputs
DeviceNet communication module, mounted internal to Solid State Starter
Isolation contactor
Human interface module
– Blank cover, no functionality, door mounted in bezel
– LCD display, full numeric keypad, door mounted in bezel
– LCD display, programmer only, door mounted in bezel
Pump control, provides pump start and stop
Braking control, provides Smart Motor braking, Accu-Stop and Slow Speed braking
49
SMC Flex Soft Starter Units
Motor Rating
Circuit Breaker
SMC Flex
High Interrupting
Capacity Fuses
Module Size
Input Voltage
kW(1)
Cat. No.(2)
Cat. No.(2)
Cat. No.(3)
1 = 80 mm
380/415V,
0.75
140M-C2N-***
150-F5NBD
---
8
0.75
140M-C2N-***
150-F5NBD
4A, SIZE 000
8
2.2
140M-D8N-***
150-F5NBD
---
8
2.2
140M-D8N-***
150-F5NBD
6A, SIZE 000
8
4
140M-D8N-***
150-F25NBD
---
8
4
140M-D8N-***
150-F25NBD
16A, SIZE 000
8
7.5
140M-D8N-***
150-F25NBD
---
8
7.5
140M-D8N-***
150-F25NBD
20A, SIZE 000
8
11
140M-D8N-***
150-F25NBD
---
8
11
140M-D8N-***
150-F25NBD
40A, SIZE 000
8
15
140M-F8P-***
150-F43NBD
---
8
15
140M-F8P-***
150-F43NBD
40A, SIZE 000
8
22
140M-H8P-***
150-F43NBD
---
8
22
140M-H8P-***
150-F43NBD
63A, SIZE 000
8
30
140M-H8P-***
150-F60NBD
---
8
30
140M-H8P-***
150-F60NBD
80A, SIZE 00
8
45
140M-H8P-***
150-F85NBD
---
8
45
140M-H8P-***
150-F85NBD
125A, SIZE 00
8
55
140M-J8P-***
150-F108NBD
---
12(4)
55
140M-J8P-***
150-F108NBD
125A, SIZE 00
12(4)
IP20/42/54
(1)
(2)
(3)
(4)
(5)
50
75
140M-J8P-***
150-F201NBD
---
24(5)
75
140M-J8P-***
150-F201NBD
200A, SIZE 1
24(5)
90
140M-J8P-***
150-F201NBD
---
24(5)
90
140M-J8P-***
150-F201NBD
250A, SIZE 1
24(5)
110
140M-J8P-***
150-F251NBD
---
24(5)
110
140M-J8P-***
150-F251NBD
355A, SIZE 2
24(5)
132
140M-L8P-***
150-F251NBD
---
24(5)
132
140M-L8P-***
150-F251NBD
355A, SIZE 2
24(5)
160
140M-L8P-***
150-F317NBD
---
24(5)
160
140M-L8P-***
150-F317NBD
500A, SIZE 3
24(5)
185
140M-L8P-***
150-F361NBD
---
24(5)
185
140M-L8P-***
150-F361NBD
500A, SIZE 3
24(5)
220
140M-L8P-***
150-F480NBD
---
24(5)
220
140M-L8P-***
150-F480NBD
630A, SIZE 3
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
High interrupting capacity fuses are optional
Fixed mount style
600 mm wide column
SMC Flex Soft Starter Units
Motor Rating
Circuit Breaker
SMC Flex
High Interrupting
Capacity Fuses
Module Size
Input Voltage
kW(1)
Cat. No.(2)
Cat. No.(2)
Cat. No.(3)
1 = 80 mm
440/460/480V,
0.75
140M-C2N-***
150-F5NBD
---
8
0.75
140M-C2N-***
150-F5NBD
4A, SIZE 000
8
2.2
140M-D8N-***
150-F5NBD
---
8
2.2
140M-D8N-***
150-F5NBD
6A, SIZE 000
8
4
140M-D8N-***
150-F25NBD
---
8
4
140M-D8N-***
150-F25NBD
16A, SIZE 000
8
7.5
140M-D8N-***
150-F25NBD
---
8
7.5
140M-D8N-***
150-F25NBD
20A, SIZE 000
8
11
140M-D8N-***
150-F25NBD
---
8
11
140M-D8N-***
150-F25NBD
40A, SIZE 000
8
15
140M-F8P-***
150-F43NBD
---
8
15
140M-F8P-***
150-F43NBD
40A, SIZE 000
8
22
140M-H8P-***
150-F43NBD
---
8
22
140M-H8P-***
150-F43NBD
63A, SIZE 000
8
30
140M-H8P-***
150-F60NBD
---
8
30
140M-H8P-***
150-F60NBD
80A, SIZE 00
8
45
140M-H8P-***
150-F85NBD
---
8
45
140M-H8P-***
150-F85NBD
125A, SIZE 00
8
55
140M-J8P-***
150-F108NBD
---
12(4)
55
140M-J8P-***
150-F108NBD
125A, SIZE 00
12(4)
75
140M-J8P-***
150-F135NBD
---
12(4)
75
140M-J8P-***
150-F135NBD
200A, SIZE 1
12(4)
90
140M-J8P-***
150-F201NBD
---
24(5)
90
140M-J8P-***
150-F201NBD
250A, SIZE 1
24(5)
110
140M-J8P-***
150-F201NBD
---
24(5)
110
140M-J8P-***
150-F201NBD
355A, SIZE 2
24(5)
132
140M-L8P-***
150-F251NBD
---
24(5)
132
140M-L8P-***
150-F251NBD
355A, SIZE 2
24(5)
160
140M-L8P-***
150-F317NBD
---
24(5)
160
140M-L8P-***
150-F317NBD
500A, SIZE 3
24(5)
IP20/42/54
(1)
(2)
(3)
(4)
(5)
185
140M-L8P-***
150-F361NBD
---
24(5)
185
140M-L8P-***
150-F361NBD
500A, SIZE 3
24(5)
220
140M-L8P-***
150-F480NBD
---
24(5)
220
140M-L8P-***
150-F480NBD
630A, SIZE 3
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
High interrupting capacity fuses are optional
Fixed mount style
600 mm wide column
51
SMC Flex Soft Starter Unit Options
•
•
•
•
•
•
•
•
•
•
•
•
•
52
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
Selector switch
– Two position
– Three position
DeviceNet starter auxiliary
– (4) 120VAC inputs and (2) 120VAC outputs
– (4) 24VDC inputs and (2) 120VAC outputs
DeviceNet communication module, mounted internal to Solid State Starter
Isolation contactor
Human interface module
– Blank cover, no functionality, door mounted in bezel
– LCD display, full numeric keypad, door mounted in bezel
– LCD display, programmer only, door mounted in bezel
Pump control, provides pump start and stop
Braking control, provides Smart Motor braking, Accu-Stop and Slow Speed braking
Variable Frequency Drive Units
PowerFlex® Variable Frequency AC Drives
The combination variable frequency AC drive units are specifically designed
for use in the CENTERLINE 2500 Motor Control Centers. Each unit contains a
variable frequency AC drive and either a fusible disconnect switch or circuit
breaker. These units are available in a withdrawable unit style and a fixed unit
style. Available models include:
• PowerFlex 40 Variable Frequency AC drive
• PowerFlex 70 Variable Frequency AC drive
• PowerFlex 700 Variable Frequency AC drive
PowerFlex drive features include:
• Isolated logic and power
• Produce a three-phase, pulse width modulated (PWM) adjustable frequency
output and voltage output for exceptional control of motor speed and
torque
• Are digitally programmed with access to mode programming, providing
precise and repeatedly accurate setup, control and operation, and
adaptability to handle a variety of applications
One Line Diagram
For drive unit selection go to page .
For drive unit option selection go to page .
PowerFlex 40 Variable Frequency Drive Units
Motor Rating
Circuit Breaker
PowerFlex 40 VFD
Reactor
Module Size
Cat. No.
Cat. No.
1 = 80 mm
22B-D1P4N104
---
4
22B-D1P4N104
1321-3R2-B
6
22B-D2P3N104
---
4
22B-D2P3N104
1321-3R4-C
6
140M-D8N-***
22B-D4P0N104
---
4
1.5
140M-D8N-***
22B-D4P0N104
1321-3R4-B
6
2.2
140M-D8N-***
22B-D6P0N104
---
4
2.2
140M-D8N-***
22B-D6P0N104
1321-3R8-C
6
3.7
140M-D8N-***
22B-D010N104
---
4
3.7
140M-D8N-***
22B-D010N104
1321-3R8-B
6
5.5
140M-D8N-***
22B-D012N104
---
8
5.5
140M-D8N-***
22B-D012N104
1321-3R12-B
8
7.5
140M-D8N-***
22B-D017N104
---
8
7.5
140M-D8N-***
22B-D017N104
1321-3R18-B
8
11
140M-D8N-***
22B-D024N104
---
8
11
140M-D8N-***
22B-D024N104
1321-3R25-B
8
Input Voltage
kW
380/415V,
0.37
IP20
0.37
140M-C2N-***
0.75
140M-C2N-***
0.75
140M-C2N-***
1.5
(1)
Cat. No.
(2)
140M-C2N-***
(3)
(1) Approximate range of kilowatt ratings
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
(3) Line or load reactors are optional
53
PowerFlex 40 Variable Frequency Drive Units (continued)
Motor Rating
Circuit Breaker
PowerFlex 40 VFD
Module Size
1 = 80 mm
22B-D1P4N104
---
6
22B-D1P4N104
1321-3R2-B
6
22B-D2P3N104
---
6
140M-C2N-***
22B-D2P3N104
1321-3R4-C
6
140M-D8N-***
22B-D4P0N104
---
6
1.5
140M-D8N-***
22B-D4P0N104
1321-3R4-B
6
2.2
140M-D8N-***
22B-D6P0N104
---
6
2.2
140M-D8N-***
22B-D6P0N104
1321-3R8-C
6
3.7
140M-D8N-***
22B-D010N104
---
6
3.7
140M-D8N-***
22B-D010N104
1321-3R8-B
6
5.5
140M-D8N-***
22B-D012N104
---
10
5.5
140M-D8N-***
22B-D012N104
1321-3R12-B
10
7.5
140M-D8N-***
22B-D017N104
---
10
7.5
140M-D8N-***
22B-D017N104
1321-3R18-B
10
11
140M-D8N-***
22B-D024N104
---
10
11
140M-D8N-***
22B-D024N104
1321-3R25-B
10
kW
380/415V,
0.37
140M-C2N-***
IP42/54
0.37
140M-C2N-***
0.75
140M-C2N-***
0.75
1.5
(1)
(2)
Cat. No.
Cat. No.
Reactor
Cat. No.
Input Voltage
(3)
(1) Approximate range of kilowatt ratings
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
(3) Line or load reactors are optional
54
PowerFlex 40 Variable Frequency Drive Units (continued)
Motor Rating
Circuit Breaker
PowerFlex 40 VFD
Reactor
Module Size
Cat. No.
Cat. No.
1 = 80 mm
140M-C2N-***
22B-D1P4N104
---
4
140M-C2N-***
22B-D1P4N104
1321-3R2-B
6
140M-C2N-***
22B-D2P3N104
---
4
0.75
140M-C2N-***
22B-D2P3N104
1321-3R4-C
6
1.5
140M-D8N-***
22B-D4P0N104
---
4
1.5
140M-D8N-***
22B-D4P0N104
1321-3R4-B
6
2.2
140M-D8N-***
22B-D6P0N104
---
4
2.2
140M-D8N-***
22B-D6P0N104
1321-3R8-C
6
3.7
140M-D8N-***
22B-D010N104
---
4
3.7
140M-D8N-***
22B-D010N104
1321-3R8-B
6
5.5
140M-D8N-***
22B-D012N104
---
8
5.5
140M-D8N-***
22B-D012N104
1321-3R12-B
8
7.5
140M-D8N-***
22B-D017N104
---
8
7.5
140M-D8N-***
22B-D017N104
1321-3R18-B
8
11
140M-D8N-***
22B-D024N104
---
8
11
140M-D8N-***
22B-D024N104
1321-3R25-B
8
Input Voltage
kW
440/460/480V,
0.37
IP20
0.37
0.75
(1)
Cat. No.
(2)
(3)
(1) Approximate range of kilowatt ratings
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
(3) Line or load reactors are optional
55
PowerFlex 40 Variable Frequency Drive Units (continued)
Motor Rating
Circuit Breaker
PowerFlex 40 VFD
Reactor
Module Size
Cat. No.(2)
Cat. No.
Cat. No.(3)
1 = 80 mm
22B-D1P4N104
---
6
22B-D1P4N104
1321-3R2-B
6
22B-D2P3N104
---
6
22B-D2P3N104
1321-3R4-C
6
Input Voltage
kW(1)
440/460/480V,
0.37
140M-C2N-***
IP42/54
0.37
140M-C2N-***
0.75
140M-C2N-***
0.75
140M-C2N-***
1.5
140M-D8N-***
22B-D4P0N104
---
6
1.5
140M-D8N-***
22B-D4P0N104
1321-3R4-B
6
2.2
140M-D8N-***
22B-D6P0N104
---
6
2.2
140M-D8N-***
22B-D6P0N104
1321-3R8-C
6
3.7
140M-D8N-***
22B-D010N104
---
6
3.7
140M-D8N-***
22B-D010N104
1321-3R8-B
6
5.5
140M-D8N-***
22B-D012N104
---
10
5.5
140M-D8N-***
22B-D012N104
1321-3R12-B
10
7.5
140M-D8N-***
22B-D017N104
---
10
7.5
140M-D8N-***
22B-D017N104
1321-3R18-B
10
11
140M-D8N-***
22B-D024N104
---
10
11
140M-D8N-***
22B-D024N104
1321-3R25-B
10
(1) Approximate range of kilowatt ratings
(2) To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
(3) Line or load reactors are optional
56
PF40 Drive Unit Options
•
•
•
•
•
•
•
•
•
•
•
•
•
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
Selector switch
– Two position
– Three positio
DeviceNet starter auxiliary
– (4) 120VAC inputs and (2) 120V AC outputs
– (4) 24VDC inputs and (2) 120V AC outputs
DeviceNet communication module, mounted internal to Solid State Starter
ControlNet communication module, mounted internal to drive
Isolation contactor
Human interface module
– Blank cover, no functionality, door mounted in bezel
– LCD display, full numeric keypad, door mounted in bezel
– LCD display, programmer only, door mounted in bezel
I/O control interface type
– 24V DC control voltage interface with vector control
– 120V AC control voltage interface with vector control
– 24V DC control voltage interface with sensorless vector control
– 120V AC control voltage interface with sensorless vector control
57
PowerFlex 70 Variable Frequency Drive Units (Normal Duty)
Motor Rating
Input Voltage
Circuit Breaker
kW
(1)
PowerFlex 70 VFD
Isolation Contactor
Cat. No.
Cat. No.
Cat. No.
(2)
(2)
Reactor
Module Size
Cat. No.
1 = 80 mm
(3)
380/415V,
0.37
140M-C2N-***
20AC1P3A0AYNANC0
100-C09*10
---
6
IP20
0.37
140M-C2N-***
20AC1P3A0AYNANC0
100-C09*10
1321-3R2-B
8
0.75
140M-C2N-***
20AC2P1A0AYNANC0
100-C09*10
---
6
0.75
140M-C2N-***
20AC2P1A0AYNANC0
100-C09*10
1321-3R2-B
8
1.5
140M-D8N-***
20AC3P5A0AYNANC0
100-C09*10
---
6
1.5
140M-D8N-***
20AC3P5A0AYNANC0
100-C09*10
1321-3R4-B
8
2.2
140M-D8N-***
20AC5P0A0AYNANC0
100-C09*10
---
6
2.2
140M-D8N-***
20AC5P0A0AYNANC0
100-C09*10
1321-3R4-B
8
3.7
140M-D8N-***
20AC8P7A0AYNANC0
100-C09*10
---
6
3.7
140M-D8N-***
20AC8P7A0AYNANC0
100-C09*10
1321-3R8-B
8
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
---
8
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
1321-3R12-B
10
7.5
140M-D8N-***
20AC015A0AYNANC0
100-C23*10
---
8
7.5
140M-D8N-***
20AC015A0AYNANC0
100-C23*10
1321-3R18-B
10
11
140M-D8N-***
20AC022A0AYNANC0
100-C37*10
---
10
11
140M-D8N-***
20AC022A0AYNANC0
100-C37*10
1321-3R25-B
10
15
140M-F8N-***
20AC030A0AYNANC0
100-C37*10
---
10
15
140M-F8N-***
20AC030A0AYNANC0
100-C37*10
1321-3R35-B
10
18.5
140M-H8N-***
20AC037A0AYNANC0
100-C43*10
---
10
(1)
(2)
(3)
(4)
58
18.5
140M-H8N-***
20AC037A0AYNANC0
100-C43*10
1321-3R35-B
10
22
140M-H8N-***
20AC043A0AYNANC0
100-C85*10
---
10
22
140M-H8N-***
20AC043A0AYNANC0
100-C85*10
1321-3R45-B
10
30
140M-H8N-***
20AC060A0AYNANC0
100-C85*10
---
14(4)
30
140M-H8N-***
20AC060A0AYNANC0
100-C85*10
1321-3R55-B
14(4)
37
140M-H8N-***
20AC072A0AYNANC0
100-C85*10
---
14(4)
37
140M-H8N-***
20AC072A0AYNANC0
100-C85*10
1321-3R80-B
14(4)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Line or load reactors are optional
Fixed mount style
PowerFlex 70 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating
Input Voltage
Circuit Breaker
(1)
kW
Cat. No.
(2)
PowerFlex 70 VFD
Cat. No.
Isolation Contactor
(2)
Cat. No.
Reactor
Cat. No.
(3)
Module Size
1 = 80 mm
380/415V,
0.37
140M-C2N-***
20AC1P3A0AYNANC0
100-C09*10
---
8
IP42/54
0.37
140M-C2N-***
20AC1P3A0AYNANC0
100-C09*10
1321-3R2-B
10
0.75
140M-C2N-***
20AC2P1A0AYNANC0
100-C09*10
---
8
0.75
140M-C2N-***
20AC2P1A0AYNANC0
100-C09*10
1321-3R2-B
10
1.5
140M-D8N-***
20AC3P5A0AYNANC0
100-C09*10
---
8
1.5
140M-D8N-***
20AC3P5A0AYNANC0
100-C09*10
1321-3R4-B
10
2.2
140M-D8N-***
20AC5P0A0AYNANC0
100-C09*10
---
8
2.2
140M-D8N-***
20AC5P0A0AYNANC0
100-C09*10
1321-3R4-B
10
3.7
140M-D8N-***
20AC8P7A0AYNANC0
100-C09*10
---
8
3.7
140M-D8N-***
20AC8P7A0AYNANC0
100-C09*10
1321-3R8-B
10
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
---
12
(1)
(2)
(3)
(4)
(5)
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
1321-3R12-B
12
7.5
140M-D8N-***
20AC015A0AYNANC0
100-C23*10
---
12
7.5
140M-D8N-***
20AC015A0AYNANC0
100-C23*10
1321-3R18-B
12
11
140M-D8N-***
20AC022A0AYNANC0
100-C37*10
---
14(4)
11
140M-D8N-***
20AC022A0AYNANC0
100-C37*10
1321-3R25-B
14(4)
15
140M-F8N-***
20AC030A0AYNANC0
100-C37*10
---
14(4)
15
140M-F8N-***
20AC030A0AYNANC0
100-C37*10
1321-3R35-B
14(4)
18.5
140M-H8N-***
20AC037A0AYNANC0
100-C43*10
---
14(4)
18.5
140M-H8N-***
20AC037A0AYNANC0
100-C43*10
1321-3R35-B
14(4)
22
140M-H8N-***
20AC043A0AYNANC0
100-C85*10
---
14 (4)
22
140M-H8N-***
20AC043A0AYNANC0
100-C85*10
1321-3R45-B
14(4)
30
140M-H8N-***
20AC060A0AYNANC0
100-C85*10
---
16(4)
30
140M-H8N-***
20AC060A0AYNANC0
100-C85*10
1321-3R55-B
24(5)
37
140M-H8N-***
20AC072A0AYNANC0
100-C85*10
---
16(4)
37
140M-H8N-***
20AC072A0AYNANC0
100-C85*10
1321-3R80-B
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Line or load reactors are optional
Fixed mount style.
600 mm wide column
59
PowerFlex 70 Variable Frequency Drive Units (Normal Duty,continued)
Motor Rating
Input Voltage
Circuit Breaker
kW
(1)
PowerFlex 70 VFD
Isolation Contactor
Cat. No.
Cat. No.
Cat. No.
(2)
(2)
Reactor
Module Size
Cat. No.
1 = 80 mm
(3)
440/460/480V,
0.37
140M-C2N-***
20AD1P1A0AYNANC0
100-C09*10
---
6
IP20
0.37
140M-C2N-***
20AD1P1A0AYNANC0
100-C09*10
1321-3R2-B
8
0.75
140M-C2N-***
20AD2P1A0AYNANC0
100-C09*10
---
6
0.75
140M-C2N-***
20AD2P1A0AYNANC0
100-C09*10
1321-3R2-B
8
1.5
140M-D8N-***
20AD3P4A0AYNANC0
100-C09*10
---
6
1.5
140M-D8N-***
20AD3P4A0AYNANC0
100-C09*10
1321-3R4-B
8
2.2
140M-D8N-***
20AD5P0A0AYNANC0
100-C09*10
---
6
2.2
140M-D8N-***
20AD5P0A0AYNANC0
100-C09*10
1321-3R4-B
8
3.7
140M-D8N-***
20AD8P0A0AYNANC0
100-C09*10
---
6
3.7
140M-D8N-***
20AD8P0A0AYNANC0
100-C09*10
1321-3R8-B
8
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
---
8
(1)
(2)
(3)
(4)
(5)
60
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
1321-3R12-B
10
7.5
140M-D8N-***
20AD014A0AYNANC0
100-C16*10
---
8
7.5
140M-D8N-***
20AD014A0AYNANC0
100-C16*10
1321-3R18-B
10
11
140M-D8N-***
20AD022A0AYNANC0
100-C23*10
---
10
11
140M-D8N-***
20AD022A0AYNANC0
100-C23*10
1321-3R25-B
10
15
140M-F8N-***
20AD027A0AYNANC0
100-C37*10
---
10
15
140M-F8N-***
20AD027A0AYNANC0
100-C37*10
1321-3R35-B
10
18.5
140M-F8N-***
20AD034A0AYNANC0
100-C37*10
---
10
18.5
140M-F8N-***
20AD034A0AYNANC0
100-C37*10
1321-3R35-B
10
22
140M-H8N-***
20AD040A0AYNANC0
100-C43*10
---
10
22
140M-H8N-***
20AD040A0AYNANC0
100-C43*10
1321-3R45-B
10
30
140M-H8N-***
20AD052A0AYNANC0
100-C85*10
---
14(4)
30
140M-H8N-***
20AD052A0AYNANC0
100-C85*10
1321-3R55-B
24(5)
37
140M-H8N-***
20AD065A0AYNANC0
100-C85*10
---
14(4)
37
140M-H8N-***
20AD065A0AYNANC0
100-C85*10
1321-3R80-B
24 (5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Line or load reactors are optional
Fixed mount style
600 mm wide column
PowerFlex 70 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating
Input Voltage
kW(1)
Circuit Breaker
PowerFlex 70 VFD
Isolation Contactor
Reactor
Module Size
Cat. No.(2)
Cat. No.
Cat. No.(2)
Cat. No.(3)
1 = 80 mm
440/460/480V,
0.37
140M-C2N-***
20AD1P1A0AYNANC0
100-C09*10
---
8
IP42/54
0.37
140M-C2N-***
20AD1P1A0AYNANC0
100-C09*10
1321-3R2-B
10
0.75
140M-C2N-***
20AD2P1A0AYNANC0
100-C09*10
---
8
0.75
140M-C2N-***
20AD2P1A0AYNANC0
100-C09*10
1321-3R2-B
10
(1)
(2)
(3)
(4)
(5)
1.5
140M-D8N-***
20AD3P4A0AYNANC0
100-C09*10
---
8
1.5
140M-D8N-***
20AD3P4A0AYNANC0
100-C09*10
1321-3R4-B
10
2.2
140M-D8N-***
20AD5P0A0AYNANC0
100-C09*10
---
8
2.2
140M-D8N-***
20AD5P0A0AYNANC0
100-C09*10
1321-3R4-B
10
3.7
140M-D8N-***
20AD8P0A0AYNANC0
100-C09*10
---
8
3.7
140M-D8N-***
20AD8P0A0AYNANC0
100-C09*10
1321-3R8-B
10
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
---
12
5.5
140M-D8N-***
20AD011A0AYNANC0
100-C16*10
1321-3R12-B
12
7.5
140M-D8N-***
20AD014A0AYNANC0
100-C16*10
---
12
7.5
140M-D8N-***
20AD014A0AYNANC0
100-C16*10
1321-3R18-B
12
11
140M-D8N-***
20AD022A0AYNANC0
100-C23*10
---
14(4)
11
140M-D8N-***
20AD022A0AYNANC0
100-C23*10
1321-3R25-B
14(4)
15
140M-F8N-***
20AD027A0AYNANC0
100-C37*10
---
14(4)
15
140M-F8N-***
20AD027A0AYNANC0
100-C37*10
1321-3R35-B
14(4)
18.5
140M-F8N-***
20AD034A0AYNANC0
100-C37*10
---
14(4)
18.5
140M-F8N-***
20AD034A0AYNANC0
100-C37*10
1321-3R35-B
14(4)
22
140M-H8N-***
20AD040A0AYNANC0
100-C43*10
---
14(4)
22
140M-H8N-***
20AD040A0AYNANC0
100-C43*10
1321-3R45-B
14(4)
30
140M-H8N-***
20AD052A0AYNANC0
100-C85*10
---
16(4)
30
140M-H8N-***
20AD052A0AYNANC0
100-C85*10
1321-3R55-B
24(5)
37
140M-H8N-***
20AD065A0AYNANC0
100-C85*10
---
16(4)
37
140M-H8N-***
20AD065A0AYNANC0
100-C85*10
1321-3R80-B
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at http://www.ab.com/en/epub/catalogs/12768/229240/
Line or load reactors are optional
Fixed mount style
600 mm wide column
61
PF70 Drive Unit Options
•
•
•
•
•
•
•
•
•
•
•
•
•
62
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
Selector switch
– Two position
– Three position
DeviceNet starter auxiliary
– (4) 120V AC inputs and (2) 120V AC outputs
– (4) 24V DC inputs and (2) 120V AC outputs
DeviceNet communication module, mounted internal to Solid State Starter
ControlNet communication module, mounted internal to drive
Isolation contactor
Human interface module
– Blank cover, no functionality, door mounted in bezel
– LCD display, full numeric keypad, door mounted in bezel
– LCD display, programmer only, door mounted in bezel
I/O control interface type
– 24V DC control voltage interface with vector control
– 120V AC control voltage interface with vector control
– 24V DC control voltage interface with sensorless vector control
– 120V AC control voltage interface with sensorless vector control
PowerFlex 700 Variable Frequency Drive Units (Normal Duty)
Motor Rating
Circuit Breaker
Isolation Contactor
Reactor
Module Size
Cat. No.
Cat. No.
140M-C2N-***
20BC1P3A0AYNANC0
100-C09*10
---
8
140M-C2N-***
20BC1P3A0AYNANC0
100-C09*10
1321-3R2-B
8
0.75
140M-C2N-***
20BC2P1A0AYNANC0
100-C09*10
---
8
0.75
140M-C2N-***
20BC2P1A0AYNANC0
100-C09*10
1321-3R2-B
8
1.5
140M-D8N-***
20BC3P5A0AYNANC0
100-C09*10
---
8
1.5
140M-D8N-***
20BC3P5A0AYNANC0
100-C09*10
1321-3R4-B
8
2.2
140M-D8N-***
20BC5P0A0AYNANC0
100-C09*10
---
8
2.2
140M-D8N-***
20BC5P0A0AYNANC0
100-C09*10
1321-3R4-B
8
3.7
140M-D8N-***
20BC8P7A0AYNANC0
100-C09*10
---
8
3.7
140M-D8N-***
20BC8P7A0AYNANC0
100-C09*10
1321-3R8-B
8
5.5
140M-D8N-***
20BC011A0AYNANC0
100-C16*10
---
8
5.5
140M-D8N-***
20BC011A0AYNANC0
100-C16*10
1321-3R12-B
8
7.5
140M-D8N-***
20BC015A0AYNANC0
100-C23*10
---
8
7.5
140M-D8N-***
20BC015A0AYNANC0
100-C23*10
1321-3R18-B
8
11
140M-D8N-***
20BC022A0AYNANC0
100-C37*10
---
8
11
140M-D8N-***
20BC022A0AYNANC0
100-C37*10
1321-3R25-B
8
15
140M-F8N-***
20BC030A0AYNANC0
100-C37*10
---
8
15
140M-F8N-***
20BC030A0AYNANC0
100-C37*10
1321-3R35-B
10
18.5
140M-H8N-***
20BC037A0AYNANC0
100-C43*10
---
8
kW
380/415V,
0.37
IP20
0.37
(1)
(2)
(3)
(4)
(5)
PowerFlex 40 VFD
Cat. No.
Input Voltage
(1)
Cat. No.
(2)
(2)
(3)
1 = 80 mm
18.5
140M-H8N-***
20BC037A0AYNANC0
100-C43*10
1321-3R45-B
10
22
140M-H8N-***
20BC043A0AYNANC0
100-C85*10
---
12
22
140M-H8N-***
20BC043A0AYNANC0
100-C85*10
1321-3R45-B
14(4)
37
140M-H8N-***
20BC072A0AYNANC0
100-C85*10
---
12
37
140M-H8N-***
20BC072A0AYNANC0
100-C85*10
1321-3R80-B
14(4)
55
140M-J8N-***
20BC105A0ANNANC0
100-D180*11
---
24(5)
55
140M-J8N-***
20BC105A0ANNANC0
100-D180*11
1321-3R130-B
24(5)
75
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
---
24(5)
75
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
1321-3R160-B
24(5)
90
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
---
24(5)
90
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
1321-3R200-B
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Line or load reactors are optional
Fixed mount style
600 mm wide column
63
PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating
Circuit Breaker
Reactor
Module Size
Cat. No.
Cat. No.
0.37
140M-C2N-***
20BC1P3A0AYNANC0
100-C09*10
---
8
0.37
140M-C2N-***
20BC1P3A0AYNANC0
100-C09*10
1321-3R2-B
10
0.75
140M-C2N-***
20BC2P1A0AYNANC0
100-C09*10
---
8
0.75
140M-C2N-***
20BC2P1A0AYNANC0
100-C09*10
1321-3R2-B
10
1.5
140M-D8N-***
20BC3P5A0AYNANC0
100-C09*10
---
8
1.5
140M-D8N-***
20BC3P5A0AYNANC0
100-C09*10
1321-3R4-B
10
2.2
140M-D8N-***
20BC5P0A0AYNANC0
100-C09*10
---
8
2.2
140M-D8N-***
20BC5P0A0AYNANC0
100-C09*10
1321-3R4-B
10
3.7
140M-D8N-***
20BC8P7A0AYNANC0
100-C09*10
---
8
3.7
140M-D8N-***
20BC8P7A0AYNANC0
100-C09*10
1321-3R8-B
10
5.5
140M-D8N-***
20BC011A0AYNANC0
100-C16*10
---
8
5.5
140M-D8N-***
20BC011A0AYNANC0
100-C16*10
1321-3R12-B
10
7.5
140M-D8N-***
20BC015A0AYNANC0
100-C23*10
---
8
7.5
140M-D8N-***
20BC015A0AYNANC0
100-C23*10
1321-3R18-B
10
11
140M-D8N-***
20BC022A0AYNANC0
100-C37*10
---
12
11
140M-D8N-***
20BC022A0AYNANC0
100-C37*10
1321-3R25-B
14(4)
15
140M-F8N-***
20BC030A0AYNANC0
100-C37*10
---
12
15
140M-F8N-***
20BC030A0AYNANC0
100-C37*10
1321-3R35-B
14(4)
380/415V,
IP42/54
64
Isolation Contactor
Cat. No.
kW
(1)
(2)
(3)
(4)
(5)
PowerFlex 40 VFD
Cat. No.
Input Voltage
(1)
(2)
(2)
(3)
1 = 80 mm
18.5
140M-H8N-***
20BC037A0AYNANC0
100-C43*10
---
12
18.5
140M-H8N-***
20BC037A0AYNANC0
100-C43*10
1321-3R45-B
14(4)
22
140M-H8N-***
20BC043A0AYNANC0
100-C85*10
---
14(4)
22
140M-H8N-***
20BC043A0AYNANC0
100-C85*10
1321-3R45-B
16(4)
37
140M-H8N-***
20BC072A0AYNANC0
100-C85*10
---
14(4)
37
140M-H8N-***
20BC072A0AYNANC0
100-C85*10
1321-3R80-B
16(4)
55
140M-J8N-***
20BC105A0ANNANC0
100-D180*11
---
24(5)
55
140M-J8N-***
20BC105A0ANNANC0
100-D180*11
1321-3R130-B
24(5)
75
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
---
24(5)
75
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
1321-3R160-B
24(5)
90
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
---
24(5)
90
140M-J8N-***
20BC170A0ANNANC0
100-D180*11
1321-3R200-B
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Line or load reactors are optional
Fixed mount style
600 mm wide column
PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating
Circuit Breaker
Isolation Contactor
Reactor
Module Size
Cat. No.
Cat. No.
140M-C2N-***
20BD1P1A0AYNANC0
100-C09*10
---
8
140M-C2N-***
20BD1P1A0AYNANC0
100-C09*10
1321-3R2-B
8
0.75
140M-C2N-***
20BD2P1A0AYNANC0
100-C09*10
---
8
0.75
140M-C2N-***
20BD2P1A0AYNANC0
100-C09*10
1321-3R2-B
8
1.5
140M-D8N-***
20BD3P4A0AYNANC0
100-C09*10
---
8
1.5
140M-D8N-***
20BD3P4A0AYNANC0
100-C09*10
1321-3R4-B
8
2.2
140M-D8N-***
20BD5P0A0AYNANC0
100-C09*10
---
8
2.2
140M-D8N-***
20BD5P0A0AYNANC0
100-C09*10
1321-3R4-B
8
3.7
140M-D8N-***
20BD8P0A0AYNANC0
100-C09*10
---
8
3.7
140M-D8N-***
20BD8P0A0AYNANC0
100-C09*10
1321-3R8-B
8
5.5
140M-D8N-***
20BD011A0AYNANC0
100-C16*10
---
8
5.5
140M-D8N-***
20BD011A0AYNANC0
100-C16*10
1321-3R12-B
8
7.5
140M-D8N-***
20BD014A0AYNANC0
100-C16*10
---
8
7.5
140M-D8N-***
20BD014A0AYNANC0
100-C16*10
1321-3R18-B
8
11
140M-D8N-***
20BD022A0AYNANC0
100-C23*10
---
8
11
140M-D8N-***
20BD022A0AYNANC0
100-C23*10
1321-3R25-B
8
15
140M-F8N-***
20BD027A0AYNANC0
100-C37*10
---
8
15
140M-F8N-***
20BD027A0AYNANC0
100-C37*10
1321-3R35-B
10
18.5
140M-F8N-***
20BD034A0AYNANC0
100-C37*10
---
8
kW
440/460/480V,
0.37
IP20
0.37
(1)
(2)
(3)
(4)
(5)
PowerFlex 40 VFD
Cat. No.
Input Voltage
(1)
Cat. No.
(2)
(2)
(3)
1 = 80 mm
18.5
140M-F8N-***
20BD034A0AYNANC0
100-C37*10
1321-3R35-B
10
22
140M-H8N-***
20BD040A0AYNANC0
100-C43*10
---
12(4)
22
140M-H8N-***
20BD040A0AYNANC0
100-C43*10
1321-3R45-B
14(4)
37
140M-H8N-***
20BD065A0AYNANC0
100-C85*10
---
12(4)
37
140M-H8N-***
20BD065A0AYNANC0
100-C85*10
1321-3R80-B
14(4)
55
140M-J8N-***
20BD096A0AYNANC0
100-D180*11
---
24(5)
55
140M-J8N-***
20BD096A0AYNANC0
100-D180*11
1321-3R100-B
24(5)
75
140M-J8N-***
20BD125A0AYNANC0
100-D180*11
---
24(5)
75
140M-J8N-***
20BD125A0AYNANC0
100-D180*11
1321-3R130-B
24(5)
90
140M-J8N-***
20BD156A0AYNANC0
100-D180*11
---
24(5)
90
140M-J8N-***
20BD156A0AYNANC0
100-D180*11
1321-3R160-B
24(5)
110
140M-J8N-***
20BD180A0AYNANC0
100-D210*11
---
24(5)
110
140M-J8N-***
20BD180A0AYNANC0
100-D210*11
1321-3R200-B
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Line or load reactors are optional
Fixed mount style
600 mm wide column
65
PowerFlex 700 Variable Frequency Drive Units (Normal Duty, continued)
Motor Rating
Circuit Breaker
PowerFlex 40 VFD
Isolation Contactor
Reactor
Module Size
1 = 80 mm
Input Voltage
kW
Cat. No.
Cat. No.
Cat. No.
Cat. No.
440/460/480V,
0.37
140M-C2N-***
20BD1P1A0AYNANC0
100-C09*10
---
8
IP42/54
0.37
140M-C2N-***
20BD1P1A0AYNANC0
100-C09*10
1321-3R2-B
10
0.75
140M-C2N-***
20BD2P1A0AYNANC0
100-C09*10
---
8
0.75
140M-C2N-***
20BD2P1A0AYNANC0
100-C09*10
1321-3R2-B
10
1.5
140M-D8N-***
20BD3P4A0AYNANC0
100-C09*10
---
8
1.5
140M-D8N-***
20BD3P4A0AYNANC0
100-C09*10
1321-3R4-B
10
2.2
140M-D8N-***
20BD5P0A0AYNANC0
100-C09*10
---
8
2.2
140M-D8N-***
20BD5P0A0AYNANC0
100-C09*10
1321-3R4-B
10
3.7
140M-D8N-***
20BD8P0A0AYNANC0
100-C09*10
---
8
3.7
140M-D8N-***
20BD8P0A0AYNANC0
100-C09*10
1321-3R8-B
10
5.5
140M-D8N-***
20BD011A0AYNANC0
100-C16*10
---
8
5.5
140M-D8N-***
20BD011A0AYNANC0
100-C16*10
1321-3R12-B
10
7.5
140M-D8N-***
20BD014A0AYNANC0
100-C16*10
---
8
7.5
140M-D8N-***
20BD014A0AYNANC0
100-C16*10
1321-3R18-B
10
11
140M-D8N-***
20BD022A0AYNANC0
100-C23*10
---
12
11
140M-D8N-***
20BD022A0AYNANC0
100-C23*10
1321-3R25-B
14(4)
15
140M-F8N-***
20BD027A0AYNANC0
100-C37*10
---
12
15
140M-F8N-***
20BD027A0AYNANC0
100-C37*10
1321-3R35-B
14(4)
(1)
(2)
(3)
(4)
(5)
66
(1)
(2)
(2)
(3)
18.5
140M-F8N-***
20BD034A0AYNANC0
100-C37*10
---
12
18.5
140M-F8N-***
20BD034A0AYNANC0
100-C37*10
1321-3R35-B
14(4)
22
140M-H8N-***
20BD040A0AYNANC0
100-C43*10
---
14[(4)
22
140M-H8N-***
20BD040A0AYNANC0
100-C43*10
1321-3R45-B
16(4)
37
140M-H8N-***
20BD065A0AYNANC0
100-C85*10
---
14(4)
37
140M-H8N-***
20BD065A0AYNANC0
100-C85*10
1321-3R80-B
16(4)
55
140M-J8N-***
20BD096A0AYNANC0
100-D180*11
---
24(5)
55
140M-J8N-***
20BD096A0AYNANC0
100-D180*11
1321-3R100-B
24(5)
75
140M-J8N-***
20BD125A0AYNANC0
100-D180*11
---
24(5)
75
140M-J8N-***
20BD125A0AYNANC0
100-D180*11
1321-3R130-B
24(5)
90
140M-J8N-***
20BD156A0AYNANC0
100-D180*11
---
24(5)
90
140M-J8N-***
20BD156A0AYNANC0
100-D180*11
1321-3R160-B
24(5)
110
140M-J8N-***
20BD180A0AYNANC0
100-D210*11
---
24(5)
110
140M-J8N-***
20BD180A0AYNANC0
100-D210*11
1321-3R200-B
24(5)
Approximate range of kilowatt ratings
To complete the catalog numbers, please refer to the Industrial Controls Catalog at www.ab.com/catalogs
Line or load reactors are optional
Fixed mount style
600 mm wide column
PF700 Drive Unit Options
•
•
•
•
•
•
•
•
•
•
•
•
•
Auxiliary contact for contactors
Auxiliary contact for circuit breaker
Surge suppressor
Control circuit transformer
Push buttons
Pilot lights
– Incandescent
– LED
– Incandescent, Push-to-Test
– LED, Push-to-Test
Selector switch
– Two position
– Three position
DeviceNet starter auxiliary
– (4) 120VAC inputs and (2) 120VAC outputs
– (4) 24VDC inputs and (2) 120VAC outputs
DeviceNet communication module, mounted internal to Solid State Starter
ControlNet communication module, mounted internal to drive
Isolation contactor
Human interface module
– Blank cover, no functionality, door mounted in bezel
– LCD display, full numeric keypad, door mounted in bezel
– LCD display, programmer only, door mounted in bezel
I/O control interface type
– 24 VDC control voltage interface with vector control
– 120 VAC control voltage interface with vector control
– 24 VDC control voltage interface with sensorless vector control
– 120 VAC control voltage interface with sensorless vector control
67
Distribution Panels
PLC and I/O Compartments
68
Selection Data
Column Selection
The following tables outline the CENTERLINE 2500 MCC product offering. Please select your columns and unit types.
Column Dimensions mm (in)
700 - 1000
(27.56 - 39.37
Delete?
170 (6.69)
2300 (90.55)
1980 (77.95)
35 (1.38)
115 (4.53)
600 (23.62)
500
(19.69)
200 - 500
(7.87 - 19.69)
Column Options
Column Type
Width
Depth
Height
IP Rating
Separation
Withdrawable Units
700 mm (200 mm wireway)
600 mm
2300 mm
IP 20
Form 3b
800 mm (300 mm wireway)
800 mm
IP 30
Form 4b
900 mm (400 mm wireway)
1200 mm (double-front)
IP 42
1000 mm (500 mm wireway)
Fixed Units
IP 54
700 mm (no vertical wireway)
800 mm (no vertical wireway)
900 mm (no vertical wireway)
1000 mm (no vertical wireway)
69
Horizontal Power Bus Options
Horizontal Power Bus
Bus Rating
Short Circuit
Withstand Rating
Short Circuit Peak
Withstand Rating
Material
800 A
50 kA for 1 second
110 kA
1250 A
50 kA for 3 second
and 80 kA for 1
second
176 kA
Bare Copper or
Tin-plated Copper
50 kA for 3 second
and 100 kA for 1
second
220 kA
1600A
2000 A
2500 A
3200 A
4000 A
Vertical Power Bus Options
Vertical Power Bus
Bus Rating
Short Circuit
Withstand Rating
Short Circuit Peak
Withstand
300 A
50 kA for 0.2 second 110 kA for 3 second
600 A
50 kA for 1 second
Material
Tin-Plated Copper
Neutral Power Bus Options
Vertical Power Bus
Bus Rating
Short Circuit
Withstand Rating
Full
50 kA for 0.2 second 110 kA for 3 second
Half
50 kA for 1 second
70
Short Circuit Peak
Withstand
Material
Tin-Plated Copper
Incoming Power and Control Power Selection
Incoming Power and Control Voltage Options
Line/System
Voltage (V)
Frequency (Hz)
Control/Coil Voltage (V)
Control Type
380
50
24 DC; 110, 220 AC
60
24 DC; 110, 120, 220 AC
Transformer,
Separate, or line
to neutral
50
24 DC; 110, 230 AC
400
60
415
440
480
50
24 DC; 110, 240 AC
60
24 DC; 120, 240 AC
50
24 DC; 110, 220 AC
60
24 DC; 110, 120, 220 AC
50
60
600
50
60
(1)
690
24 DC; 120, 240 AC
24 DC; 120, 240 AC
50
60
(1) Consult the factory
71
Unit Selection
Incoming Main Lug Compartments and Outgoing Feeder Lug Compartments
The line lug compartments provide a lug connection for incoming lines (mains) to distribute power to the motor control
center for outgoing cables (feeders) to feed power from the motor control center to an external load. Mechanical or crimp
style lugs are available. Lug compartments are a fixed-unit design and may be located at the top or bottom of the column.
Main and Feeder Lugs
Feeder Lug
Main Lug
Lug Compartments
Amperes
Cable Provisions, Maximum Number per Phase and
Maximum Cable Size
Module Size
Mechanical Type Lugs(1)
(Single Cable)
Crimp Type Lugs(1)
300
(2) 185 mm2
(2) 185 mm2
(2)
400
(2)
(2)
(2)
600
2
(2) 185 mm
6(2)
(1) 240 mm2
(2) 185 mm2
6(2)
2
2
(1) 400 mm
6(2)
(2) 240 mm2
6(2)
(4) 400 mm2
(4) 400 mm2
6(2)
2
2
(2) 400 mm
6(2)
(4) 300 mm2
(4) 240 mm2
24(2)
(1) 400 mm2
(3) 240 mm2
24(2)
2
2
24(2)
(2) 185 mm
(2) 400 mm
2
(1)
800
(2) 400 mm
(2) 300 mm
(4) 185 mm
(4) 240 mm2
24(2)
(1) 400 mm2
(2) 400 mm2
24(2)
2
2
24(2)
(2) 400 mm
(4) 240 mm
(4) 300 mm2
24(2)
(4) 400 mm2
(4) 400 mm2
24(2)
1250
(2)
(2)
24(2)
1600
(4) 400 mm2
(4) 400 mm2
24(2)
2000
(6) 400 mm2
(6) 400 mm2
24(2)
2500
(2)
(2)
24(2)
3200
(2)
(2)
24(2)
4000
(2)
(2)
24(2)
(1) Fixed mount style
(2) Consult factory
72
Miscellaneous Units
DeviceNet Power Supply
DeviceNet Power Supply
Units are supplied with a circuit breaker or fusible disconnect
Central Control Transformer Units
Module
Size
Unit Description
4
Central Control Transformer
DeviceNet Power Supply Units
Module
Size
Unit Description
2
DeviceNet Power Supply
4
Redundant DeviceNet Power Supply
Bridge Units
Module
Size
Unit Description
2
ControlNet to DeviceNet Bridge
2
Ethernet to DeviceNet Bridge
2
Profibus to DeviceNet Bridge
73
Technical Data
Technical Standards and Certifications
The MCC is designed and tested to meet or exceed the requirements defined by the following IEC standards and
directives.
• EN 60439-1:1999 + A1:2004, the standard for type-tested and partially type-tested assemblies of low voltage
switchgear and control gear assemblies (TTA, PTA)
• EN 60204-1:2006, the general requirements for the safety of electrical equipment of machines
• 2006/95/EC, Low Voltage Directive
• 2004/108/EC, EMC Directive
• 2002/95/EC, the restriction of hazardous substances directive (RoHS)
• KEMA certified (TTA)
The MCC columns, units and components are available with the CE Conformance Mark and the China Compulsory
Certification (CCC).
The MCC is designed, manufactured and tested in facilities registered to ISO 9001 quality standards.
Operating Environment
The MCC is intended for use in a pollution degree 3 environment.
The MCC is designed to operate in the following ambient conditions. The ambient operating temperature shall range from
-5…40 °C, with the average temperature in any 24 hour period not exceeding 35 °C.
The MCC is designed to operate at altitudes up to 1000 m. For altitudes exceeding 1000 m, contact your Rockwell
Automation representative for derating information.
74
Forms of Separation
Internal isolation and separation exists between the following:
• Individual units
• Units and wireways
• Units and the bus system
• Wireways and the bus system
In addition, the vertical wireway for power wiring is separate from the vertical wireway for control and network wiring.
Standard internal separation within the MCC is Form 3b. Form 4b is available by enclosing terminals for external
conductors in a metal box within the vertical wireway.
Internal Separation
Form 3b
Form 4b
75
CENTERLINE 2500 Specifications
Standards
EN 60439-1:1999 + A1:2004
EN 60204-1:2006
EC Directives
2006/95/EC
2004/108/EC
2002/95/EC(1)
Low-voltage switchgear and controlgear assemblies
Part 1: Type-tested and partially type-tested assemblies
Safety of machinery – Electrical equipment of machines
Part 1: General requirements
Low Voltage Directive
EMC Directive
Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic
Equipment (RoHS)
Certifications and Markings
China Compulsory Certificate (CCC)
CE Conformance Marked
KEMA certified (TTA)
Rated Voltages
Rated Operating Voltage, Ue
Up to 690 V, 3-Phase
Rated Frequency, fn
50 – 60 Hz
1000 V, 3-Phase
Rated Insulation Voltage, Ui
Rated Currents
Horizontal Bus
Vertical Bus
Continuous Current Rating, Ie
Up to 4000 A
Up to 600 A
Up to 176 kA for 1 second
Up to 110 kA for 3 second
Short Circuit Peak Withstand, Ipk
Short Time Withstand Rating, Icw
Up to 80 kA for 1 second
Up to 50 kA for 1 second
Neutral (N)
Full or half rated
Creepage Distances and Clearances
Rated Impulse Withstand Voltage, Uimp 6, 8, or 12 kV
Material Group (Overvoltage Category) IIIa (175 </= CTI < 400)
Pollution Degree
3
Bus Material and Plating
Horizontal Power Bus
Copper (optional tin plating)
Vertical Distribution Bus
Copper with tin plating
Protective Earth Conductor (PE)
Copper (optional tin plating)
Degrees of Protection
IEC 60529
IP 20, 40, 42 or 54
Forms of Separation
IEC 60439-1
Form 3b or 4b
Column Dimensions
Height
2300 mm
Width
700, 800, 900, or 1000 mm
Depth
600 or 800 mm (1200 mm, double-front)
Units
Approximate Module Size
80 mm high x 500 mm wide = 1 module
Modules per Column
24
Withdrawable Unit Sizes
1, 2, 4, 6, 8, 10, 12 modules
Structural Surface Treatments
Interior
High Visibility White Paint (Additional colors available by request.)
Exterior
RAL 7032 Pebble Grey Paint or Munsell 6.5 Paint (Additional colors available by request.)
Environment
Storage Temperature
-25…55°C
Operating (Ambient) Temperature
-5…40°C
Altitude
Up to 1000 m
(1) Low voltage Motor Control Center products are exempt under Category 9, however Rockwell Automation is committed to demonstrating the highest
standard of global environmental management. It is the goal of Rockwell Automation to meet the material restrictions on products, even where
compliance is not legally required.
76
Structure Material
This list has the approximate thickness and gauge of the MCC structural components and external covers.
CENTERLINE 2500 MCC Structure Details
Structural Components
Thickness (mm)
Side Plate
2.0
Back Plate
2.5
Covers and Panels
Top Plate
2.0
Bottom Plate
2.0
End Closing Plate
2.0
Horizontal Wireway Cover
2.0
Doors
Unit Door
2.0
Vertical Wireway Door
2.0
Other Steel
External Mounting Channel 3.5
77
78
Checklist
Explanation of why using the checklist is important.
Customer
User
Reviewed the customer documents prior to filling out this form
Office
Standards and Certifications
CE
KEMA
CCC
Other ____________
Incoming Power
Line Voltage:
380V
400V
System Power:
415V
440V
480V
Grounded Wye
Grounded Wye with Impedance
50 Hz
Available Fault Current:
690V
Grounded Delta
Delta
Frequency:
600V
60 Hz
kA
Control Power
Voltage:
24V DC
110V AC
115V AC
Source:
Individual Control Transformer
120V AC
Standard VA
220V AC
230V AC
240V AC
Extra Capacity
Common Control Power Transformer
Separate Control Power Source
Top Horizontal Wireway
Control Terminal Blocks Location:
Vertical Wireway
Structure
Enclosure
Rating:
IP 20 (vented doors)
IP 42 (non-vented, standard)
IP 40 (vented doors with filters)
IP 54 (fully gasketed, doors and bottom plates)
Forms of Internal Separation:
3b (standard)
4b
Mounting Configuration
Stand Alone
Add to Existing
Front Only
Double-front
600mm
800mm
Depth:
Width:
Options:
700mm (200mm vertical wireway, standard)
900mm (400mm vertical wireway)
800mm (300mm vertical wireway)
1000mm (500mm vertical wireway)
Space Heater w/ Thermostat
Arc Containment Latches
Cable Supports
Other ________________________
External Paint:
RAL7032 Pebble Grey (standard)
Other _____________
Internal Paint:
High Visibility Gloss White
Other _____________
Ambient Temperature:
°C maximum
Altitude:
meters
79
Bus
Fault Rating/Bracing:
50kA for 3 cycles
65kA for 3 cycles
50kA for 3 seconds
(horizontal power bus only)
Horizontal Power Bus
Rating:
2000A
800A (standard)
1250A
1600A
2500A
3200A
4000A
Rating:
Half Rated
300A
(provides 600A capacity, standard)
Material:
600A
(provides 1200A capacity)
Copper, Tin Plated
Horizontal Location:
Bottom (standard)
Material:
Copper, Unplated
Size:
1-6 x 50 mm
Vertical (Plug-in):
Stab Openings:
Copper, Tin Plated
Full Rated
Vertical Distribution Bus
Protective Earth Conductor
(PE)
80kA for 1 second
(horizontal power bus only)
Copper
Material:
Neutral Bus:
50kA for 1 second
2-6 x 50 mm
Copper, Tin Plated
3-6 x 50 mm
Copper, Unplated
Copper, Tin Plated
Automatic Shutters (standard)
IntelliCENTER Technology
IntelliCENTER:
DeviceNet Cabling
DeviceNet Cabling with IntelliCENTER Software
Linking Device:
EtherNET/IP
ControlNet
ArcShield
Yes
80
Profibus
Other _____________
Incoming Cable Termination/Provision
Ampere Rating: __________A
Located in Column Number:
__________
Number of cables per phase:
__________
Top
Cable Size _______________________
Crimp Compression Lugs
Main Lug Only (MLO):
Mechanical Lugs
Fuses Supplied
Main Fusible Disconnect (MFD):
Bottom
Lugs Not Supplied
Fuse Type __________________
Fuses Not Supplied
Main Circuit Breaker (MCB):
Ground Fault
Shunt Trip
Auxiliary Contacts - Qty. __________
Other ______________
Number of current transformers required _______________
Number of potential transformers required ______________
Incoming Metering Options:
Analog Ammeter
Ammeter Switch
Analog Voltmeter
Voltmeter Switch
Powermonitor 3000
1404-M5
1404-M6
Digital Volt/Ammeter
1405-M610
Outgoing Cable Termination/Provision
Ampere Rating:__________A
Number of cables per phase __________
Crimp Compression Lugs
Lug Type:
Cable Size _______________________
Mechanical Lugs
Lugs Not Supplied
Feeder Units
Fuses Supplied
Fuse Switch:
Fuse Type _____________________
Fuses Not Supplied
Circuit Breaker (Thermal Magnetic):
Interrupting Rating _______________kA
Ampere Rating ________A
Other__________________________________________
Nameplates
Unit Nameplates:
Cardholder
Engraved Acrylic
Engraved Phenolic
Black letters on white
Color Scheme
White letters on black
White letters on black (phenolic only)
Door Latches
Door Latch Type:
1/4 Turn
1/4 Turn with T-handle
Arc Containment
Arc Containment with T-handle
Wire Markers
Wire Marker Type:
Sleeve
Data Tab
Heat Shrink
Spares
Spare Parts
Spare Units
81
Direct On Line Starter Units (copy and complete for each unit needed)
Non-reversing Starter
Unit Type:
Ampere Rating: ________A
Reversing Starter
Kilowatt Rating: _______kw
Fused (rotary operator only)
Disconnecting Means:
Fuse Type _____________
Fuses not supplied
Circuit Breaker
Handle Operator:
Type:
Overload:
Reset:
Rotary Operator
Flange Operator (2 module minimum)
E1 Plus
E1 Plus with Ground Fault
E3 Plus
E3 Plus with Ground Fault
External (door mounted)
Duty Rating:
AC3 (standard)
AC4
Protection:
Type 1
Type 2
Withdrawable
Unit Type:
Semi-withdrawable
Fixed
Options and Accessories
Pilot Lights:
Qty_______
Transformer Type
Push-to-test
Text on Legend Plate:
On
Off
Emergency
LED Lamps
Fault
Other ____________________________
Pushbuttons: Qty_______
Text on Legend Plate:
On
Emergency
Selector
Switch:
Normally Open, Qty _____
Relays or Timers, Describe
____________________________
Others, Describe
____________________________
82
Reset
Other ____________________________
Yes
Starter Auxillary Contacts:
Notes
Off
Normally Closed, Qty _____
Soft Starter Units (copy and complete for each unit needed)
Unit Type:
SMC-3
SMC Flex
Connection:
Line Connection
Delta Connection
Ampere Rating: ________A
Kilowatt Rating: _______kw
Fused (rotary operator only)
Disconnecting Means:
Fuse Type _____________
Fuses not supplied
Circuit Breaker
Rotary Operator
Handle Operator:
Withdrawable
Unit Type:
Flange Operator (2 module minimum)
Semi-withdrawable
Fixed
Options and Accessories
Pilot Lights:
Qty_______
Transformer Type
Push-to-test
Text on Legend Plate:
Start
Stop
LED Lamps
Other ____________________________
Pushbuttons: Qty_______
Text on Legend Plate:
On
Off
Fault
Other ____________________________
Selector Switch:
Yes
Human Interface Module (HIM):
LCD Display, Full Numeric Keypad
Starting Mode:
Pump Control
Others, Describe
LCD Display,
Programmer Only
Braking Control
____________________________
Notes
83
Variable Frequency AC Drive Units (copy and complete for each unit needed)
Unit Type:
Rating:
Ampere Rating: ________A
PowerFlex 40
PowerFlex 70
PowerFlex 700
PowerFlex 700H
Normal Duty
Heavy Duty
Kilowatt Rating: _______kw
Disconnecting Means:
Fused (rotary operator only)
Fuse Type ________________
Fuses not supplied
Circuit Breaker
Rotary Operator
Handle Operator:
Withdrawable
Unit Type:
Flange Operator (2 module minimum)
Semi-withdrawable
Fixed
Options and Accessories
Pilot Lights:
Qty_______
Transformer Type
Push-to-test
Text on Legend Plate:
Start
Stop
LED Lamps
Other ____________________________
Pushbuttons: Qty_______
Text on Legend Plate:
On
Off
Fault
Other ____________________________
Yes
Selector Switch:
LCD Display,
Programmer Only
Human Interface Module (HIM):
LCD Display, Full Numeric Keypad
Braking Mode:
Pump Control
Braking Control
Reactors:
Line Reactor
Load Reactor
Others, Describe
Notes
84
____________________________
Miscellaneous Units (copy and complete for each unit needed)
DeviceNet Power Supply Unit
Redundant DeviceNet Power Supply Unit
DeviceNet Back-up Power Supply Unit
Programmable Controllers:
Specify unit location _____________________________
Number of Slots ___________
Power Supply___________
Describe: ________________________________________
Other Units, Options or Modifications:
Describe: ________________________________________
________________________________________________
Extra Space for Future Units:
Describe: ________________________________________
________________________________________________
Comments / Additional Notes:
85
Fill in blanks as required.
Motor List
Unit Description
Comments/Additional Notes
86
Rating
Module Size
Publication 2500-SG001B-EN-P—May 200988
Supersedes Publication 2500-SG001A-EN-P—January 2008
Copyright © 2009 Rockwell Automation, Inc. Printed in the U.S.A.