Global Reference Guide for Potentially Explosive Atmospheres and Hazardous Locations 94/9/EC Product Markings Typical IEC/CENELEC Product Markings ATEX Required Markings II 2 GAS G / D Ex de Dust IIC T6 1) Gb / Ex t IIIC Db Electrical Type of Protection for Atmospheres made explosive by gases, vapors and mists Explosion Protection Marking Type of Protection d e ia ib ic Equipment Group Equipment Category Explosive Atmosphere Suitability (G – Gas, vapor or mist) ATEX / IEC Reference Method of Explosion Protection 1) T80°C Explosive Atmosphere Suitability (D – Dust) Explosion Marking Type of protection (Gas) Explosion Group (Gas) Temperature Class (Gas) ma mb mc nA nC nR o op is, op pr, op sh px, py pz q Type of Protection Zone General Requirements Flameproof Enclosure Zone 1 or 2 Increased Safety Zone 1 or 2 Intrinsic Safety Zone 0, 1 or 2 Intrinsic Safety Zone 1 or 2 Intrinsic Safety Zone 2 Intrinsically Safe Systems Zone 1 or 2 Intrinsically Safe Fieldbus Systems (FISCO) Zone 1 or 2 Non-sparking Fieldbus Systems (FNICO) Zone 1 or 2 Encapsulation Zone 0, 1 or 2 Encapsulation Zone 1 or 2 Encapsulation Zone 2 Non-Sparking Zone 2 Enclosed Break Zone 2 Restricted Breathing Zone 2 Oil Immersion Zone 1 or 2 Optical Radiation Zone 0, 1 or 2 Optical Radiation Zone 1 or 2 Pressurized Enclosure Zone 1 or 2 Pressurized Enclosure Zone 2 Powder Filling Zone 1 or 2 Type of Protection ia ib ma mb mc p t Description of Protection General Requirements Intrinsic Safety Intrinsic Safety Encapsulation Encapsulation Encapsulation Pressurized Protection by enclosure / ATEX Category/ EPL CENELEC /IEC Standard EN 60079-0 / IEC 60079-0 /2G / Gb EN 60079-1 / IEC 60079-1 /2G / Gb EN 60079-7 / IEC 60079-7 / 1G / Ga EN 60079-11 / IEC 60079-11 /2G / Gb EN 60079-11 / IEC 60079-11 /3G / Gc EN 60079-11 / IEC 60079-11 /2G / Gb EN 60079-25 / IEC 60079-25 /2G / Gb EN 60079-27 / IEC 60079-27 /3G / Gc EN 60079-27 / IEC 60079-27 /1G / Ga EN 60079-18 / IEC 60079-18 /2G / Gb EN 60079-18 / IEC 60079-18 /3G / Gc EN 60079-18 / IEC 60079-18 /3G / Gc EN 60079-15 / IEC 60079-15 /3G / Gc EN 60079-15 / IEC 60079-15 /3G / Gc EN 60079-15 / IEC 60079-15 /2G / Gb EN 60079-6 / IEC 60079-6 / 1 G, 2 G or 3 G / Ga, Gb, Gc EN 60079-28 / IEC 60079-28 / 2 G or 3 G / Gb, Gc EN 60079-28 / IEC 60079-28 /2G / Gb EN 60079-2 / IEC 60079-2 /3G / Gc EN 60079-2 / IEC 60079-2 /2G / Gb EN 60079-5 / IEC 60079-5 Protection Concept Contain the explosion, prevent the flame propagation No arcs, sparks or hot surfaces Limit the energy of the spark and the surface temperature Limit the energy of the spark and the surface temperature Limit the energy of the spark and the surface temperature Limit the energy of the spark and the surface temperature Limit the energy of the spark and the surface temperature Limit the energy of the spark and the surface temperature Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere No arcs, sparks or hot surfaces Prevent the flame propagation Protection by enclosure Exclusion of Ex-atmosphere Limit or prevent energy transmission from optical radiation Limit or prevent energy transmission from optical radiation Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Prevent the flame propagation Equipment Protection Level (EPL-Gas) Electrical Type of protection for Atmospheres made explosive by dusts Explosion Protection Marking Type of protection (Dust) Explosion Group (Dust) Max. Surface Temperature (Dust) ATEX Zone Zone 20, 21, 22 Zone 21, 22 Zone 20, 21, 22 Zone 21 or 22 Zone 20, 21, 22 Zone 22 Zone 20, 21, 22 / ATEX Category/ EPL CENELEC /IEC Standard EN 60079-0 / IEC 60079-0 /1D / Da EN 61241-11 / IEC 61241-11 /2D / Db EN 61241-11 / IEC 61241-11 /1D / Da EN 60079-18 / IEC 60079-18 /2D / Db EN 60079-18 / IEC 60079-18 /1D / Da EN 60079-18 / IEC 60079-18 /3D / Dc EN 61241-4 / IEC 61241-4 / 1 D, 2 D or 3 D / Da, Db, Dc EN 60079-31 / IEC 60079-31 Protection Concept Limit the surface temperature Limit the surface temperature Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Keep the combustible dust out and avoid hot surfaces Equipment Protection Level (EPL-Dust) 1) Standard marking - alternate marking possible e.g.: Ex db eb IIC T6 / Ex tb IIIC T80°C ATEX (Atmosphères Explosibles) - The Directive 94/9/EC (ATEX) regulates within its scope for the European Market the Essential Health and Safety Requirements for apparatus for use in hazardous areas and conformity assessment procedures which must be applied to equipment. Zone Classification / Equipment Protection Level Hazardous mixture Gas Mist Vapor Dust Period of presence of the flammable substances Zone Classification Continuously for long Zone 0 periods or frequently Occasional occurrence Zone 1 Not likely, but if it does occur only rarely and for a short period Zone 2 Continuously for long Zone 20 periods or frequently Occasional occurrence Zone 21 Not likely, but if it does occur only rarely and for a short period Zone 22 Methane Coal dust Mining Mining Necessary Marking for the Equipment According 94/9/EC According IEC 60079-0 Equipment Category Protection Equipment Group Group Protection Level EPL II 1G II Ga Typical Nameplate Marking Explosion Groups Protection Level very high II 2G II Gb high II 3G II Gc increased III 1D III Da very high III 2D III Db high III 3D III Dc increased I I M1 M2 I I Ma Mb very high high Explosive Atmospheres: Typical Hazardous Material Explosion Group Gases and Vapors Acetylene Hydrogen Ethylene Propane IIC IIC or IIB+H2 IIB IIA Metal dust Coal dust Grain dust IIIC IIIC IIIB Wood, paper, or cotton processing IIIA Dusts Fibres & Flyings SECOND NUMERAL Protection against liquid 0 - NO PROTECTION 0 - NO PROTECTION 1- OBJECTS EQUAL TO OR GREATER THAN 50 mm 1 - VERTICALLY DRIPPING WATER 2 - 75 TO 105°-ANGLED DRIPPING WATER 3 - SPRAYING WATER 4 - SPLASHING WATER 3 - OBJECTS EQUAL TO OR GREATER THAN 2.5 mm 5 - WATER JETS 4 - OBJECTS EQUAL TO OR GREATER THAN 1.0 mm 6 - HEAVY SEAS, POWERFUL WATER JETS IP56 5 - DUST-PROTECTED 7 - EFFECTS OF IMMERSION 6 - DUST-TIGHT 8 - INDEFINITE IMMERSION eLLK 2010XYZ Certificate number May end with U – Component cert. May end with X – Special conditions for safe use www.ceag.de Made in Germany S.Nr.: D123456 Additional certificate (optional) Explosion protection marking (ATEX): Equipment Group (II) and Category (2) Type of explosive atmosphere G – gas, vapor or mist / D – dust 0102 2010 PTB 09 ATEX 12345 110 - 240 V 50 - 60 Hz IECEx BVS 09.12345 110 - 240 V DC II 2 G Ex de IIC T6 Gb II 2 D Ex t IIIC T80°C Db Ta= -25°C - +55°C Lamp: G13 60081 IEC CE marking and number of Notified Body responsible for the monitoring of the Quality System (0102 = PTB Germany) Electrical parameters Ambient temperature -25°C to +55°C (if -20°C to + 40°C, marking is not required - Standard for all equipment) Other essential information required by the used Standards Localisation of Gas and Dust Ex-Zones NEMA Enclosure Types FIRST NUMERAL Protection against solid bodies 2 - OBJECTS EQUAL TO OR GREATER THAN 12.5 mm Equipment name/type Serial number including year of manufacture Marking accd. IEC/CENELEC Ingress Protection (IP) Codes and NEMA Enclosure Types Ingress Protection Codes IP .. according IEC 60079 Name and address of manufacturer Enclosure Type Intended Use 1 3 3R 3S 4 4X 5 6 6P 7** 8** 9** 10** 12 12K 13 Indoor use, limited amounts of falling dirt Outdoor use, rain, sleet, windblown dust, external formation of ice Outdoor use, rain, sleet, external formation of ice Outdoor use, rain, sleet, windblown dust, external mechanisms operable when ice laden Indoor or outdoor use, windblown dust and rain, splashing water, hose directed water, external formation of ice Indoor or outdoor use, windblown dust and rain, splashing water, hose directed water, corrosion, external formation of ice Indoor use, settling airborne dust, falling dirt, non-corrosive liquids Indoor or outdoor use, hose directed water, temporary submersion, external formation of ice Indoor or outdoor use, hose directed water, prolonged submersion, external formation of ice Indoor use, Class I, Division 1, Groups A, B, C, and D hazardous locations, air-break equipment Indoor or outdoor use, Class I, Division 1 Groups A, B, C, and D hazardous locations, oil-immersed equipment Indoor use, Class II, Division 1, Groups E, F, and G hazardous locations, air-break equipment Mining applications Indoor use, circulating dust, falling dirt, dripping noncorrosive liquids Indoor use, circulating dust, falling dirt, dripping noncorrosive liquids, provided with knockouts Indoor use, lint, dust, spraying of water, oil and noncorrosive coolant Temperature Classification Maximum Surface Temperature Equivalent IP Rating* Zone 21 Zone Zone11 Zone 20 Zone Zone00 Tank Tank 54 54 54 NEC 500 Table 500.8(C) Zone 22 Zone Zone22 20 55 54 55 56 56 53 67 68 IEC NEC® 505 Flammable brennbare liquid Flüssigkeit brennbarer Staub Flammable Dust 450ºC (842ºF) 300ºC (572ºF) 280ºC (536ºF) 260ºC (500ºF) 230ºC (446ºF) 215ºC (419ºF) 200ºC (392ºF) 180ºC (356ºF) 165ºC (329ºF) 160ºC (320ºF) 135ºC (275ºF) 120ºC (248ºF) 100ºC (212ºF) 85ºC (185ºF) T1 T2 T3 T4 T5 T6 T1 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6 * NEMA Enclosure Type can be converted to IP Code rating, but IP Codes cannot be converted to NEMA Enclosure Type (Ref. NEMA 250) ** Enclosure Types for U.S. only (Ref. NEMA 250) Typical NEC/CEC Product Markings NEC 500 NEC 505/ CEC 18 Class I Division 1 Groups A, B, C & D T6 Class I Zone 1 AEx e IIC T6 Hazard Category Method of Explosion Protection Type of Protection Description of Protection Permitted for use in Protection United States Canada Concept NEC 500 NEC 505 CEC 18 CEC 18 Division Zone Division Zone e n Increased Safety Non-Incendive 2 NEC / CEC Reference Area Classification Hazardous Atmosphere Category (Gas or Dust Grouping) 1, 2 2 2 1, 2 2 No arcs, sparks or hot surfaces Temperature Classification Hazard Category Area Classification Explosion Protection Standard (EX-IEC/ATEX/CEC, AEx-NEC) Method of Explosion Protection d q Flameproof Explosionproof Powder Filled 1, 2 - 1, 2 1, 2 1, 2 - 1, 2 1, 2 ia ib Intrinsic Safety Intrinsic Safety 1, 2 - 0, 1, 2 1, 2 1, 2 - 0, 1, 2 Limit the energy of 1, 2 the spark and the surface temperature p Pressurized (Purged) Encapsulation Oil Immersion 1, 2 2 1, 2 1, 2 1, 2 1, 2 2 1, 2 1, 2 1, 2 m o Hazardous Atmosphere Category (Gas or Dust Grouping) Contain the explosion, prevent the flame propagation Keep the flammable gas out CENELEC (European Committee for Electro-technical Standardization) publishes standards covering the electrotechnical field for countries in Europe. INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC) global organization that prepares and publishes international standards for electrical, electronic and related technologies. NEMA (National Electrical Manufacturers Association) NEMA 250 series standards for enclosure types covers both hazardous areas (potentially explosive atmospheres) and non-hazardous areas. NEC – National Electrical Code (USA) CEC – Canadian Electrical Code (Canada) Temperature Classification Hazardous Atmosphere Category (Gas or Dust Grouping) Explosive Atmosphere Typical Hazard Material North America NEC 500-503 / CEC 18 Hazard Category Grouping NEC 505*/CEC 18 Gas Grouping Gases and Vapors Acetylene Hydrogen Ethylene Propane Class I Class I Class I Class I Group A Group B Group C Group D IIC IIC or IIB+H2 IIB IIA Dusts Metal dust Coal dust Grain dust Class II Class II Class II Group E Group F Group G - Fibres & Flyings Wood, paper, Class III or cotton processing - - Area Classification North America/ NEC 500-503/CEC 18 NEC 505-506/CEC 18 Continuous Hazard Intermittent Hazard Hazard under Abnormal Conditions Division 1 Division 1 Division 2 Zone 0 (Zone 20 dust) Zone 1 (Zone 21 dust) Zone 2 (Zone 22 dust) * NEC 505 covers explosive gases and vapors only. Cooper Crouse-Hinds GmbH Neuer Weg-Nord 49 D-69412 Eberbach/Germany Phone: +49 6271 806-500 Fax: +49 6271 806 476 E-mail sales.CCH.de@cooperindustries.com For more information visit: www.ceag.de www.crouse-hinds.com Crouse-Hinds is a registered trademark of Cooper Industries, Inc. © 2010 Cooper Industries, Inc./ 300 8000 2154/3/02.10/SL YOUR LOCAL REPRESENTATIVE