VERSA-STUD® 1.7 2650 WALL GUIDE for product manufactured in Alexandria [Lena], Louisiana Stronger and Stiffer for Tall Walls and High Wind Loads Straighter for Cabinet and Tile Walls Better homes from better builders — by design . . . with VERSA-STUD® wall framing VERSA-STUD 1.7 2650 WALL GUIDE EAST 11/07/2008 r 07/21/2011 Product Profiles 2 3½", 5½", 7¼"* VERSA-STUD 1.7 2650 ® Engineered Studs for Tall Walls 1½" VERSA-STUD® 1.7 2650 laminated veneer lumber wall framing is engineered for the high quality builder who wants . . . • Stronger walls to resist wind loads • Stiffer walls for a solid feel • Straight walls for a high quality finish Long, continuous VERSA-STUD® 1.7 2650 wall framing will provide superior strength, stiffness, and appearance in any tall wall application. VERSA-STUD® 1.7 2650 wall framing provides more resistance to wind pressure than walls framed with dimension lumber and eliminates the hinge created by platform framing. 1½" x 5½" VERSASTUD® 1.7 2650 wall framing has 2.3 times more bending strength than No. 2 SPF 2x6 studs. Building Code Approved for Both Prescriptive and Engineered Wall Stud Design Table of Contents * 9¼" and 11¼" depths may be available. Check with supplier or Boise Cascade EWP representative for availability. Product profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Prescriptive Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Engineered Design Assumptions for Load Tables. . . . . . . . . . . . . . . . 4 Wall Deflection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Determining Wind Load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Wind Load Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 VERSA-STUD® & VERSA-LAM® Column Design Example. . . . . . . . 8 Stud Load Tables - VERSA-STUD® 1.7 2650 1½" x 3½" . . . . . . . . . . 9 Stud Load Tables - VERSA-STUD® 1.7 2650 1½" x 5½". . . . . . . . . . 10 Stud Load Tables - VERSA-STUD® 1.7 2650 1½" x 7¼". . . . . . . . . . 11 VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 VERSA-STUD® & VERSA-LAM® Column Details. . . . . . . . . . . . . . . 12 VERSA-LAM® 1.7 2650 Exterior Wall Column Table. . . . . . . . . . . . . 13 Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Connectors / Allowable Holes and Notches . . . . . . . . . . . . . . . . . . . . 15 Design Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 VERSA-STUD® Wall Sheathing Nailing . . . . . . . . . . . . . . . . . . . . . . . 17 BC COLUMN® Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Computer Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Information and Support, SFI, Lifetime Guarantee. . . . . . . . Back cover 3 Prescriptive Design VERSA-STUD® may be used as wall studs in accordance with the prescriptive requirements in section 2308.9 of the IBC and section R602 of the IRC. The below table lists span and spacing limits for prescriptive stud design. Prescriptive design is valid for structures where the wind load does not exceed 110 mph (100 mph in hurricane- prone regions), the ground snow load does not exceed 70 psf, dead loads on floors or roof do not exceed 20 psf, and several other provisions listed in both building codes. The building design professional of record shall determine whether the structure qualifies for prescriptive design. Prescriptive Wall Stud Limits for Conventional Construction Wall Type Bearing wall supporting roof and ceiling only Bearing wall supporting one floor only Bearing wall supporting one floor, roof and ceiling Bearing wall supporting two floors, roof and ceiling Non-bearing walls Stud Size 1½" x 3½" 1½" x 5½" 1½" x 3½" 1½" x 5½" 1½" x 3½" 1½" x 5½" 1½" x 3½" 1½" x 5½" 1½" x 3½" 1½" x 5½" Stud Height 10' 10' 10' 10' 10' 10' 10' 10' 14' 20' Max O.C. Spacing 24" 24" 24" 24" 16" 24" — 16" 24" 24" • Limits per IRC Table R602.3(5) Using VERSA-STUD® for Cabinet and Tile Walls Dimension lumber can exceed 30% moisture content. Wood dries to a moisture content of 10-12% once the building is finished. Shrinkage and warping of 2x studs is a problem in walls where cabinets are hung or tile is installed. Though 2x studs cost less, added labor from shimming cabinets, straightening walls and drywall repairs can quickly add up. VERSASTUDS® eliminate these issues, providing a straight and true wall every time. Dimension Lumber Studs Shrinkage Dimension Variance Warp & Twist Wane Max 1/3rd of stud thickness (½") ½ of stud depth (2¾" for 2x6) VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 VERSA-STUD® No wane, shrinkage warp or twist 4 Engineered Design Assumptions for Load Tables Load table values are based upon axial loads applied at the top of the stud and lateral wind loads perpendicular to the wall (out of plane loading). Lateral loads parallel to the wall (in-plane loading), caused by seismic and wind, shall be designed by the project’s design professional of record. Allowable loads based upon the design provisions of the National Design Specification for Wood Construction (NDS), 2005 edition. Studs receive axial load concentrically through a double top plate and thus no eccentricity is assumed. A buckling length coefficient Ke (based on the fixity of stud ends) is 1.0. Load table values based upon assumption that stud walls have structural sheathing applied to one side or a combination of non-structural sheathing on the exterior side and gypsum wallboard on the interior side. Blocking between studs required at a maximum spacing of 8'-0". The repetitive member factor of 1.04 has been applied to the VERSA-STUD® allowable bending stress. Wind load duration factor CD = 1.6. Maximum rough opening height of adjoining openings shall not exceed 84". Double stud members and larger members shown in tables are assumed to be located between openings or at sides of openings. Single stud members shown in tables shall not be used between openings. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 Load Combinations The allowable design loads shown in this guide are based upon load combination equations for allowable stress design (IBC 06 Section 1605.3.1). Specifically for wall applications: 1. roof dead load + roof live or snow load 2. roof dead load + 0.75 x (roof live or snow load + wind load) 3. 0.6 x dead load + wind load Since the chances are extremely remote that the maximum roof live or snow load will be present at the same time as a maximum wind load, the IBC allows for a 25% reduction in both loads when applied simultaneously in load combination #2. Code References When calculating deflection from wind, the design wind load is determined by multiplying the Components & Cladding pressure by 0.7 (IBC 06 Table 1604.3, footnote f & IRC 06 Table R301.7, footnote a). Wall Deflection 5 Deflection of individual wall studs is calculated similar to that of joists and beams. The stud height, on-center spacing and stiffness determine the deflection from a design wind load. Below are the building code deflection limit provisions dependent upon the wall coverings. Wall Type or Component Max Deflection Limit Corresponding Max Deflection for 20' wall height Code Reference Exterior Walls with plaster or stucco finish L/360 0.67 in IRC 06: Table R301.7 Exterior walls with brittle finishes (brick and stone veneer - see note below) L/240 1.0 in IBC 06: Table 1604.3 IRC 06: Table R301.7 Interior walls and partitions L/180 1.33 in IRC 06: Table R301.7 Mullions (members supporting windows or doors) L/175 — Exterior walls with flexible finishes (lap, panel and metal sidings) L/120 2.0 in Wall stud deflection may occur both into the structure (positive pressure) or out from the structure (negative pressure). Thus, the total amount of possible movement is actually almost twice the deflection value shown in the design tables (see detail below). As shown in the table above, using the code minimum L/120 limit for 20' stud height can result in a deflection of 2 inches. More restrictive deflection limits may be used, similar to Boise Cascade’s Three and Four Star Floor Performance tables for BCI® Joists. The allowable load tables on pages 9-11 provide maximum loads for deflection limits ranging from L/360 to L/120. For applications where a tighter deflection limit is needed, the stud may be designed using the BC COLUMN™ software. As is the case with floors, the deflection of tall walls should be considered in the design phase of the project. In regards to brick veneer, though the IBC and IRC list a deflection limit of L/240, the Brick Industry Assocation (BIA) recommends designing studs to a defection limit of L/600 to limit cracking of the veneer caused by excessive deflection. Such designs may be analyzed using BC COLUMN™ software. Caused by wind suction on building Caused by wind load perpendicular to wall VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 IBC 06: Table 1604.3 IRC 06: Table R301.7 Deflection criteria is used to limit serviceability issues such as doors and windows binding, cracking of exterior and interior surface materials, perceived sounds due to wall movement, glass breaking, wall vibration and movement when pushed on. Wind produces pressure and suction loads on a wall producing deflection inward and outward. Vibration of walls can occur with high span/depth ratios much like a floor joist where depth equals the wall thickness. For further information on wall vibration, please contact Boise Cascade EWP Engineering. Outward (negative) deflection Inward (positive) deflection IRC 06: R613.9.3 6 Determining Wind Load In some areas the design wind load, in units of psf [lb/ft2], is provided for residential construction by the local building code jurisdiction. For example, the State of Wisconsin Uniform Dwelling Code mandates a 20 psf design wind load. Please refer to the local building code department for such information. (see IRC 301.2.1.4 for complete definitions): For areas that do not provide a wind load or for nonresidential projects, the wind load may be determined by using the basic wind speed, in units of mph or miles per hour. The wind speed is then converted into a design wind load by calculating all the necessary factors required by ASCE 7, per the IRC and IBC codes. These factors are dependent on the site location of the project and the dimensions of the structure. Typically, the project’s design professional of record performs this analysis. The following is an overview of this procedure: - Exposure D: Flat, unobstructed areas exposed to wind over open water (excluding shorelines in hurricane prone regions) for a distance of at least 1 mile. 1. 2. - Exposure B: Urban and suburban (subdivision) areas, forest land. - Exposure C: Open terrain with scattered obstructions less than 30 feet tall extending more than 1500 feet from the site in any direction. 3. the tributary area, see Effective Wind Area in Wind Load Definitions, page 7. 4. are provided in the IRC & IBC. The majority of the inland U.S. has a wind speed of 90 mph. However, basic wind speeds up to 150 mph are required in coastal areas. In addition, special wind region areas exist where the wind speed is higher. Consult with the local building code jurisdiction for the site’s design wind speed. 5. Determine the project’s exposure category: 6. - Topographical Factor: 1.0 for most structures, higher for buildings on hills or ridges. Determine mean roof height: The distance between grade and a midpoint height between the eave and ridge. The exposure of the site will affect the wind load; wind pressure will be less within a subdivision versus a structure near a body of water. For wood-frame buildings, the three exposure categories are defined Effective Wind Area Determine remaining factors: - Importance Factor: 1.0 for most structures, 1.15 for essential service buildings. Determine basic wind speed: Contour maps Exposure Category Determine the stud or column’s effective wind area: Calculated using the greater of L2/3 or Go to the tables in ASCE 7 to determine the design wind load. For a mean roof height of 33', importance factor = 1.0 and topographical factor = 1.0, the following table may be used: Wind Design Load [psf] 85 mph 90 mph 100 mph 110 mph 120 mph 130 mph 140 mph 150 mph Interior End Interior End Interior End Interior End Interior End Interior End Interior End Interior End Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone <=10 14.5 17.9 16.2 20.1 20.1 24.8 24.3 30.0 28.9 35.6 33.9 41.8 39.3 48.5 45.1 55.7 20 13.9 16.7 15.6 18.7 19.2 23.1 23.3 27.9 27.7 33.2 32.5 39.0 37.7 45.2 43.2 51.9 50 13.1 15.1 14.7 16.9 18.1 20.9 21.6 25.3 26.1 30.1 30.6 35.3 35.5 40.9 40.8 47.0 >=100 12.5 13.9 14.0 15.6 17.3 19.2 20.9 23.3 24.9 27.7 29.2 32.5 33.9 37.7 38.9 43.2 <=10 20.2 24.9 22.6 27.9 27.9 34.5 33.8 41.7 40.2 49.6 47.2 58.2 54.7 67.5 62.8 77.5 20 19.3 23.2 21.7 26.0 26.8 32.1 32.4 38.9 38.5 46.3 45.2 54.3 52.4 63.0 60.2 72.3 50 18.2 21.0 20.4 23.6 25.2 29.1 30.5 35.2 36.3 41.9 42.6 49.1 49.4 57.0 56.8 65.4 >=100 17.4 19.3 19.5 21.7 24.1 26.8 29.1 32.4 34.6 38.5 40.7 45.2 47.2 52.4 54.1 60.2 <=10 23.8 29.4 26.7 32.9 32.9 40.6 39.8 49.2 47.4 58.5 55.6 68.7 64.5 79.6 74.1 91.4 20 22.8 27.4 25.6 30.7 31.6 37.9 38.2 45.8 45.4 54.6 53.3 64.0 61.8 74.3 71.0 85.3 50 21.5 24.8 24.1 27.8 29.7 34.3 36.0 41.5 42.8 49.4 50.3 57.9 58.3 67.2 66.9 77.1 >=100 20.5 22.8 23.0 25.6 28.4 31.5 34.3 38.2 40.9 45.4 48.0 53.3 55.6 61.8 63.8 71.0 B C D • The values shown are based upon the ASCE 7-05 Analytical Procedure, Components & Cladding, Method 2. The corner end zone width of a wall is the smaller of 0.1 x wall length or 0.4 x wall height, but not less than 0.04 x wall length or 3'-0". • For a mean roof height of 30 feet or less, the stated psf loads in the table above may be reduced 2.5 percent to reflect the values shown in the IRC code. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 Wind Load Definitions ASCE 7: A design standard published by the American Society of Civil Engineers (ASCE) that is referenced by the International Building Code (IBC). ASCE 7 – Minimum Design Loads for Buildings and Other Structures establishes the live, snow, seismic and wind loads for the building code. Components and Cladding (CC): Structural components that do not qualify on their own as a MWFRS (see below). An individual wall stud is an example of a CC element. Effective Wind Area: A factor used to calculate the wind load on a stud or column. The effective wind area is the greater value of the following two equations: 1. the square of the stud height divided by 3 or L2/3 (see adjacent value table) or 2. the stud height multiplied by the tributary width (or o.c. spacing for studs). Effective Wind Area Wall Height [ft] Stud/Column Effective Wind Area [ft2] >= 18 100 16 85 14 65 12 48 10 33 8 21 Exposure Category: A factor used to calculate the design wind load (pressure) that accounts for the type of terrain surrounding the structure in question. The wind pressure will be less within a housing development versus a structure near a body of water. The following is summary of the exposure categories: B = Urban and suburban (subdivision) areas, forest land C = Open land with scattered obstructions of heights less than 30 feet D = Flat unobstructed areas and water surfaces Out-of-Plane Loading Wind Load on wall surface Stress and deflection of studs caused by perpendicular loading VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 7 In-Plane Loading: Lateral loads applied along the length of the wall are referred to as in-plane loading (see detail below). Wind loading applied parallel to the wall length must be determined by the design professional of record. Bracing, braced wall panels and tie-down anchors at corners shall be determined by design professional of record and be in accordance with applicable building code Main Wind Force-Resisting System (MWFRS): A classification of structural components. MWFRS generally refers to a system of elements that receives wind loading from more than one surface of the structure. An example of a MWFRS is an exterior wood shear wall. The shear wall receives seismic and wind load along its length (in-plane loading) and wind load perpendicular to its surface (out-of-plane loading). Out-of-Plane Loading: Wind loading perpendicular to the wall length (see detail below). Tables shown in this guide are based on out-of-plane loading only. Wind Speed: The value established by the building code or local building department which is then used, along with other factors, to determine the wind load. Wind Speed in ASCE 7 is now based upon a 3 second gust, determined by meteorological data and statistical analysis. Wind speed is provided in units of miles per hour (mph). Wind Load: The design load used to size a stud or column. The wind load is determined by taking the wind speed and applying all the necessary factors per ASCE 7, including the geometry of the structure, exposure, etc. In some areas, the design wind load is provided for residential construction by the building code jurisdiction. Wind load is in units of pounds per square foot (psf). In-Plane Loading Racking of wall caused by wind and/or seismic loading on opposite wall, applying parallel force on window wall 8 VERSA-STUD® & VERSA-LAM® Column Design Example VERSA-STUD® Design VERSA-LAM® Column Design Given: Wall as shown Determine Vertical Load Wall Height: 16'-0" Preliminary Stud Spacing: 16" o.c. Roof Load: 40 psf snow load, 15 psf dead load. BCI® rafter framing with an 18'-0" horizontal span and 2'-0" overhang Wind Load: 20 psf load per local building department (see wind load section for more information on determining wind loading) Deflection Limit:Possible brittle finish = L/240 (IRC Table R301.7) Column Tributary Width = [6'-0" / 2] + [16 in / 2] = 3'-8" Snow Load [lb] = 440 lb/ft x 3'-8" = 1615 lb Dead Load [lb] = 165 lb/ft x 3'-8" = 606 lb Total Load [lb] = 1615 lb + 606 lb = 2221 lb Wind Load [plf] = 20 lb/ft 2 x 3'-8" = 73.4 lb/ft Solution: Go to VERSA-LAM ® 1.7 2650 Exterior Wall Column Table, page 13 Stud Design Determine Vertical Load Roof Tributary Width =[18'-0" / 2] + 2'-0" = 11'-0" Snow Load [plf] = 40 lb/ft 2 x 11 ft = 440 lb/ft Snow Load [lb] = 440 lb/ft x [16 in / 12] = 587 lb Dead Load [plf] = 15 lb/ft 2 x 11 ft = 165 lb/ft Wall Weight [lb]= 10 lb/ft 2 x 16 ft x [16 in /12] = 213 lb (assume wall self-weight of 10 psf) Dead Load [lb] = 165 lb/ft x [16 in / 12] = 220 lb L/240, 16 ft wall height 3½" x 5¼" Column Vertical Load = 7358 lb > 2221 lb OK! Wind Load = 55.6 lb/ft < 73.4 lb/ft NOT OK 5¼" x 5¼" Column Total Load [lb] = 587 lb + 220 lb + 213 lb = 1020 lb Vertical Load = 10680 lb > 2221 lb OK! Wind Load = 83.4 lb/ft > 73.4 lb/ft OK! VERSA-LAM ® 1.7 2650 Column 5¼" x 5¼" OK! Go to VERSA-STUD ® 1.7 2650 1½" x 5½" load charts, page 10 L/240, 16 ft wall height Max. Loading, Single Stud, Vertical Load = 3609 lb > 1020 lb OK! 20 PSF Wind Load, Max. Stud Spacing = 16" OK! VERSA-STUD ® 1.7 2650 1½" x 5½" @ 16" o.c. OK! 18'-0" 16" 6'-0" Header Stud Tributary = 16" 2'-0" BCI® Rafters Roof Tributary to Wall [18'-0"/2] + 2'-0" = 11'-0" Column Tributary = [16"/2] + [6'-0"/2] = 3'-8" 16’-0" Blocking @ 8'-0" spacing max. 8’-0" End View VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 Side View 9 Stud Load Tables VERSA-STUD® 1.7 2650 1½" x 3½" 10 PSF WIND LOAD 15 PSF WIND LOAD 20 PSF WIND LOAD SPACING & TRIBUTARY SPACING & TRIBUTARY SPACING & TRIBUTARY Double Double Double Single Stud Double Stud Single Stud Single Stud Single Stud Stud Stud Stud Max Stud Max Max Max Stud Max Max Max Stud Max Max Vertical Wind Load Vertical Wind Load Spacing Tributary Tributary Spacing Tributary Tributary Spacing Tributary Tributary Load [lb] [lb/ft] Load [lb] [lb/ft] [in] Width [in] Width [in] [in] Width [in] Width [in] [in] Width [in] Width [in] MAXIMUM LOADING Deflection Limit L/360 L/240 L/180 L/120 Wall Height [ft] 8 9 10 11 12 13 14 8 9 10 11 12 13 14 8 9 10 11 12 13 14 8 9 10 11 12 13 14 2953 2953 2672 2257 1931 1671 1460 2953 2863 2405 2047 1764 1535 1348 2953 2549 2168 1863 1617 1416 1249 2241 1979 1740 1533 1356 1205 1077 37.7 26.5 19.3 14.5 11.2 8.8 7.0 56.5 39.7 28.9 21.7 16.7 13.2 10.5 75.3 52.9 38.6 29.0 22.3 17.6 14.1 113.0 79.4 57.8 43.5 33.5 26.3 21.1 4297 4262 4172 4022 3794 3309 2893 3905 3879 3796 3654 3453 3029 2662 3512 3509 3446 3324 3151 2781 2459 2705 2783 2782 2722 2612 2345 2100 75.3 52.9 38.6 29.0 22.3 17.6 14.1 113.0 79.4 57.8 43.5 33.5 26.3 21.1 150.6 105.8 77.1 57.9 44.6 35.1 28.1 226.0 158.7 115.7 86.9 67.0 52.7 42.2 24 24 19.2 16 12 8 8 24 24 24 24 19.2 12 12 24 24 24 24 24 19.2 16 24 24 24 24 24 24 24 45.2 31.7 23.1 17.4 13.4 10.5 8.4 67.8 47.6 34.7 26.1 20.1 15.8 12.6 90.4 63.5 46.3 34.8 26.8 21.1 16.9 135.6 95.2 69.4 52.2 40.2 31.6 25.3 90.4 63.5 46.3 34.8 26.8 21.1 16.9 135.6 95.2 69.4 52.2 40.2 31.6 25.3 180.8 127.0 92.6 69.5 53.6 42.1 33.7 271.2 190.4 138.8 104.3 80.3 63.2 50.6 24 19.2 12 8 8 6 4 24 24 19.2 16 12 8 8 24 24 24 19.2 16 12 8 24 24 24 24 24 19.2 16 30.1 21.2 15.4 11.6 8.9 7.0 5.6 45.2 31.7 23.1 17.4 13.4 10.5 8.4 60.3 42.3 30.9 23.2 17.9 14.0 11.2 90.4 63.5 46.3 34.8 26.8 21.1 16.9 60.3 42.3 30.9 23.2 17.9 14.0 11.2 90.4 63.5 46.3 34.8 26.8 21.1 16.9 120.5 84.6 61.7 46.4 35.7 28.1 22.5 180.8 127.0 92.6 69.5 53.6 42.1 33.7 19.2 12 8 8 6 4 4 24 19.2 16 12 8 6 6 24 24 19.2 16 12 8 8 24 24 24 24 19.2 12 12 22.6 15.9 11.6 8.7 6.7 5.3 4.2 33.9 23.8 17.4 13.0 10.0 7.9 6.3 45.2 31.7 23.1 17.4 13.4 10.5 8.4 67.8 47.6 34.7 26.1 20.1 15.8 12.6 45.2 31.7 23.1 17.4 13.4 10.5 8.4 67.8 47.6 34.7 26.1 20.1 15.8 12.6 90.4 63.5 46.3 34.8 26.8 21.1 16.9 135.6 95.2 69.4 52.2 40.2 31.6 25.3 25 PSF WIND LOAD 30 PSF WIND LOAD 40 PSF WIND LOAD SPACING & TRIBUTARY SPACING & TRIBUTARY SPACING & TRIBUTARY Double Double Double Single Stud Double Stud Single Stud Single Stud Single Stud Stud Stud Stud Max Stud Max Max Max Stud Max Max Max Stud Max Max Vertical Wind Load Vertical Wind Load Spacing Tributary Tributary Spacing Tributary Tributary Spacing Tributary Tributary Load [lb] [lb/ft] Load [lb] [lb/ft] [in] Width [in] Width [in] [in] Width [in] Width [in] [in] Width [in] Width [in] MAXIMUM LOADING Deflection Limit L/360 L/240 L/180 L/120 Wall Height [ft] 8 9 10 11 12 13 14 8 9 10 11 12 13 14 8 9 10 11 12 13 14 8 9 10 11 12 13 14 2953 2953 2672 2257 1931 1671 1460 2953 2863 2405 2047 1764 1535 1348 2953 2549 2168 1863 1617 1416 1249 2241 1979 1740 1533 1356 1205 1077 37.7 26.5 19.3 14.5 11.2 8.8 7.0 56.5 39.7 28.9 21.7 16.7 13.2 10.5 75.3 52.9 38.6 29.0 22.3 17.6 14.1 113.0 79.4 57.8 43.5 33.5 26.3 21.1 4297 4262 4172 4022 3794 3309 2893 3905 3879 3796 3654 3453 3029 2662 3512 3509 3446 3324 3151 2781 2459 2705 2783 2782 2722 2612 2345 2100 75.3 52.9 38.6 29.0 22.3 17.6 14.1 113.0 79.4 57.8 43.5 33.5 26.3 21.1 150.6 105.8 77.1 57.9 44.6 35.1 28.1 226.0 158.7 115.7 86.9 67.0 52.7 42.2 16 12 8 6 4 4 -24 16 12 8 8 6 4 24 24 16 12 8 8 6 24 24 24 19.2 16 12 8 Notes • • • • Wall stud analysis per 2005 National Design Specification (NDS) for Wood Construction. For 3-ply and 4-ply built up columns, multiply double stud table values by 1.5 and 2.0. Full depth blocking required at a maximum spacing of 8'-0" for single studs. Structural sheathing or structural siding installed on one side of wall. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 18.1 12.7 9.3 7.0 5.4 4.2 3.4 27.1 19.0 13.9 10.4 8.0 6.3 5.1 36.2 25.4 18.5 13.9 10.7 8.4 6.7 54.2 38.1 27.8 20.9 16.1 12.6 10.1 • • • • • • 36.2 25.4 18.5 13.9 10.7 8.4 6.7 54.2 38.1 27.8 20.9 16.1 12.6 10.1 72.3 50.8 37.0 27.8 21.4 16.9 13.5 108.5 76.2 55.5 41.7 32.1 25.3 20.2 12 8 6 4 4 --19.2 12 8 8 6 4 4 24 19.2 12 8 8 6 4 24 24 19.2 16 12 8 8 15.1 10.6 7.7 5.8 4.5 3.5 2.8 22.6 15.9 11.6 8.7 6.7 5.3 4.2 30.1 21.2 15.4 11.6 8.9 7.0 5.6 45.2 31.7 23.1 17.4 13.4 10.5 8.4 30.1 21.2 15.4 11.6 8.9 7.0 5.6 45.2 31.7 23.1 17.4 13.4 10.5 8.4 60.3 42.3 30.9 23.2 17.9 14.0 11.2 90.4 63.5 46.3 34.8 26.8 21.1 16.9 8 6 4 4 ---16 8 8 6 4 --19.2 12 8 8 6 4 4 24 19.2 16 12 8 6 6 11.3 7.9 5.8 4.3 3.3 2.6 2.1 16.9 11.9 8.7 6.5 5.0 3.9 3.2 22.6 15.9 11.6 8.7 6.7 5.3 4.2 33.9 23.8 17.4 13.0 10.0 7.9 6.3 Double stud values assume unsupported lateral length of 7'-0". Table assumes wind load duration factor of 1.6 and vertical load duration factor of 1.0. Table assumes compression perpendicular to grain for plate of 450 psi. Vertical dead load may not exceed 50% of the total vertical load. Repetitive member increase for bending (1.04) applied to single studs only. Compression perpendicular to grain stress adjusted per NDS 3.10.4 for single studs only. 22.6 15.9 11.6 8.7 6.7 5.3 4.2 33.9 23.8 17.4 13.0 10.0 7.9 6.3 45.2 31.7 23.1 17.4 13.4 10.5 8.4 67.8 47.6 34.7 26.1 20.1 15.8 12.6 10 Stud Load Tables VERSA-STUD® 1.7 2650 1½" x 5½" 10 PSF WIND LOAD 15 PSF WIND LOAD 20 PSF WIND LOAD SPACING & TRIBUTARY SPACING & TRIBUTARY SPACING & TRIBUTARY Double Double Double Single Stud Double Stud Single Stud Single Stud Single Stud Stud Stud Stud Max Stud Max Max Max Stud Max Max Max Stud Max Max Vertical Wind Load Vertical Wind Load Spacing Tributary Tributary Spacing Tributary Tributary Spacing Tributary Tributary Load [lb] [lb/ft] Load [lb] [lb/ft] [in] Width [in] Width [in] [in] Width [in] Width [in] [in] Width [in] Width [in] MAXIMUM LOADING Deflection Limit L/360 L/240 L/180 L/120 Wall Height [ft] 10 12 14 16 17 18 19 20 10 12 14 16 17 18 19 20 10 12 14 16 17 18 19 20 10 12 14 16 17 18 19 20 4641 4641 4641 4025 3615 3266 2965 2704 4641 4641 4493 3609 3261 2960 2699 2471 4641 4641 3968 3242 2948 2691 2465 2267 3704 3459 3009 2577 2385 2207 2049 1903 74.8 43.3 27.3 18.3 15.2 12.8 10.9 9.4 112.2 65.0 40.9 27.4 22.8 19.2 16.4 14.0 149.6 86.6 54.5 36.5 30.5 25.7 21.8 18.7 224.5 129.9 81.8 54.8 45.7 38.5 32.7 28.1 6615 6676 6624 6442 6291 6093 5850 5337 5870 6006 5987 5822 5682 5507 5296 4854 5077 5326 5368 5247 5131 4982 4807 4427 3254 3887 4135 4166 4119 4040 3934 3666 149.6 86.6 54.5 36.5 30.5 25.7 21.8 18.7 224.5 129.9 81.8 54.8 45.7 38.5 32.7 28.1 299.3 173.2 109.1 73.1 60.9 51.3 43.6 37.4 448.9 259.8 163.6 109.6 91.4 77.0 65.5 56.1 24 24 24 19.2 16 12 12 8 24 24 24 24 24 19.2 19.2 16 24 24 24 24 24 24 24 19.2 24 24 24 24 24 24 24 24 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 134.7 77.9 49.1 32.9 27.4 23.1 19.6 16.8 179.6 103.9 65.4 43.8 36.6 30.8 26.2 22.4 269.4 155.9 98.2 65.8 54.8 46.2 39.3 33.7 179.6 103.9 65.4 43.8 36.6 30.8 26.2 22.4 269.4 155.9 98.2 65.8 54.8 46.2 39.3 33.7 359.2 207.8 130.9 87.7 73.1 61.6 52.4 44.9 538.7 311.8 196.3 131.5 109.7 92.4 78.5 67.3 24 24 19.2 12 12 8 8 6 24 24 24 19.2 16 12 12 8 24 24 24 24 24 19.2 16 12 24 24 24 24 24 24 24 19.2 59.9 34.6 21.8 14.6 12.2 10.3 8.7 7.5 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 119.7 69.3 43.6 29.2 24.4 20.5 17.5 15.0 179.6 103.9 65.4 43.8 36.6 30.8 26.2 22.4 119.7 69.3 43.6 29.2 24.4 20.5 17.5 15.0 179.6 103.9 65.4 43.8 36.6 30.8 26.2 22.4 239.4 138.6 87.3 58.5 48.7 41.1 34.9 29.9 359.2 207.8 130.9 87.7 73.1 61.6 52.4 44.9 24 24 16 8 8 6 6 4 24 24 24 16 12 8 8 8 24 24 24 19.2 16 12 12 8 24 24 24 24 24 19.2 19.2 16 44.9 26.0 16.4 11.0 9.1 7.7 6.5 5.6 67.3 39.0 24.5 16.4 13.7 11.5 9.8 8.4 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 134.7 77.9 49.1 32.9 27.4 23.1 19.6 16.8 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 134.7 77.9 49.1 32.9 27.4 23.1 19.6 16.8 179.6 103.9 65.4 43.8 36.6 30.8 26.2 22.4 269.4 155.9 98.2 65.8 54.8 46.2 39.3 33.7 25 PSF WIND LOAD 30 PSF WIND LOAD 40 PSF WIND LOAD SPACING & TRIBUTARY SPACING & TRIBUTARY SPACING & TRIBUTARY Double Double Double Single Stud Double Stud Single Stud Single Stud Single Stud Stud Stud Stud Max Stud Max Max Max Stud Max Max Max Stud Max Max Vertical Wind Load Vertical Wind Load Spacing Tributary Tributary Spacing Tributary Tributary Spacing Tributary Tributary Load [lb] [lb/ft] Load [lb] [lb/ft] [in] Width [in] Width [in] [in] Width [in] Width [in] [in] Width [in] Width [in] MAXIMUM LOADING Deflection Limit L/360 L/240 L/180 L/120 Wall Height [ft] 10 12 14 16 17 18 19 20 10 12 14 16 17 18 19 20 10 12 14 16 17 18 19 20 10 12 14 16 17 18 19 20 4641 4641 4641 4027 3617 3267 2966 2704 4641 4641 4493 3610 3261 2961 2699 2471 4641 4641 3968 3242 2948 2691 2466 2267 3705 3459 3008 2577 2384 2209 2049 1904 74.8 43.3 27.3 18.3 15.2 12.8 10.9 9.4 112.2 65.0 40.9 27.4 22.8 19.2 16.4 14.0 149.6 86.6 54.5 36.5 30.5 25.7 21.8 18.7 224.5 129.9 81.8 54.8 45.7 38.5 32.7 28.1 6615 6676 6624 6442 6291 6093 5850 5337 5870 6006 5987 5822 5682 5507 5296 4854 5077 5326 5368 5247 5131 4982 4807 4427 3254 3887 4135 4166 4119 4040 3934 3666 149.6 86.6 54.5 36.5 30.5 25.7 21.8 18.7 224.5 129.9 81.8 54.8 45.7 38.5 32.7 28.1 299.3 173.2 109.1 73.1 60.9 51.3 43.6 37.4 448.9 259.8 163.6 109.6 91.4 77.0 65.5 56.1 24 19.2 12 8 6 6 4 4 24 24 19.2 12 8 8 6 6 24 24 24 16 12 12 8 8 24 24 24 24 19.2 16 12 12 Notes • • • • Wall stud analysis per 2005 National Design Specification (NDS) for Wood Construction. For 3-ply and 4-ply built up columns, multiply double stud table values by 1.5 and 2.0. Full depth blocking required at a maximum spacing of 8'-0" for single studs. Structural sheathing or structural siding installed on one side of wall. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 35.9 20.8 13.1 8.8 7.3 6.2 5.2 4.5 53.9 31.2 19.6 13.2 11.0 9.2 7.9 6.7 71.8 41.6 26.2 17.5 14.6 12.3 10.5 9.0 107.7 62.4 39.3 26.3 21.9 18.5 15.7 13.5 • • • • • • 71.8 41.6 26.2 17.5 14.6 12.3 10.5 9.0 107.7 62.4 39.3 26.3 21.9 18.5 15.7 13.5 143.7 83.1 52.4 35.1 29.2 24.6 20.9 18.0 215.5 124.7 78.5 52.6 43.9 37.0 31.4 26.9 24 16 8 6 6 4 4 -24 24 16 8 8 6 6 4 24 24 19.2 12 12 8 8 6 24 24 24 19.2 16 12 12 8 29.9 17.3 10.9 7.3 6.1 5.1 4.4 3.7 44.9 26.0 16.4 11.0 9.1 7.7 6.5 5.6 59.9 34.6 21.8 14.6 12.2 10.3 8.7 7.5 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 59.9 34.6 21.8 14.6 12.2 10.3 8.7 7.5 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 119.7 69.3 43.6 29.2 24.4 20.5 17.5 15.0 179.6 103.9 65.4 43.8 36.6 30.8 26.2 22.4 19.2 12 8 4 4 ---24 19.2 12 8 6 4 4 4 24 24 16 8 8 6 6 4 24 24 24 16 12 8 8 8 22.4 13.0 8.2 5.5 4.6 3.8 3.3 2.8 33.7 19.5 12.3 8.2 6.9 5.8 4.9 4.2 44.9 26.0 16.4 11.0 9.1 7.7 6.5 5.6 67.3 39.0 24.5 16.4 13.7 11.5 9.8 8.4 44.9 26.0 16.4 11.0 9.1 7.7 6.5 5.6 67.3 39.0 24.5 16.4 13.7 11.5 9.8 8.4 89.8 52.0 32.7 21.9 18.3 15.4 13.1 11.2 134.7 77.9 49.1 32.9 27.4 23.1 19.6 16.8 Double stud values assume unsupported lateral length of 7'-0". Table assumes wind load duration factor of 1.6 and vertical load duration factor of 1.0. Table assumes compression perpendicular to grain for plate of 450 psi. Vertical dead load may not exceed 50% of the total vertical load. Repetitive member increase for bending (1.04) applied to single studs only. Compression perpendicular to grain stress adjusted per NDS 3.10.4 for single studs only. 11 Stud Load Tables VERSA-STUD® 1.7 2650 1½" x 7¼" 10 PSF WIND LOAD 15 PSF WIND LOAD 20 PSF WIND LOAD SPACING & TRIBUTARY SPACING & TRIBUTARY SPACING & TRIBUTARY Double Double Double Single Stud Double Stud Single Stud Single Stud Single Stud Stud Stud Stud Max Stud Max Max Max Stud Max Max Max Stud Max Max Vertical Wind Load Vertical Wind Load Spacing Tributary Tributary Spacing Tributary Tributary Spacing Tributary Tributary Load [lb] [lb/ft] Load [lb] [lb/ft] [in] Width [in] Width [in] [in] Width [in] Width [in] [in] Width [in] Width [in] MAXIMUM LOADING Deflection Limit L/360 L/240 L/180 L/120 Wall Height [ft] 10 12 14 16 18 20 22 24 10 12 14 16 18 20 22 24 10 12 14 16 18 20 22 24 10 12 14 16 18 20 22 24 6117 6117 6117 6117 6117 5782 4892 4192 6117 6117 6117 6117 6093 5141 4392 3794 6117 6117 6117 6117 5334 4571 3947 3441 6117 4901 4589 4349 3948 3533 3150 2812 171.4 99.2 62.5 41.8 29.4 21.4 16.1 12.4 257.1 148.8 93.7 62.8 44.1 32.1 24.1 18.6 342.8 198.4 124.9 83.7 58.8 42.8 32.2 24.8 408.5 283.7 187.4 125.5 88.2 64.3 48.3 37.2 8249 8529 8669 8713 8669 8529 8278 7888 6911 7405 7675 7791 7786 7668 7437 7099 5354 6183 6627 6853 6919 6855 6675 6397 3869 3603 4258 4863 5168 5284 5258 5124 342.8 198.4 124.9 83.7 58.8 42.8 32.2 24.8 514.2 297.5 187.4 125.5 88.2 64.3 48.3 37.2 685.5 396.7 249.8 167.4 117.5 85.7 64.4 49.6 785.7 545.6 374.7 251.1 176.3 128.5 96.6 74.4 24 24 24 24 24 24 19.2 12 24 24 24 24 24 24 24 19.2 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 24 205.7 119.0 74.9 50.2 35.3 25.7 19.3 14.9 308.5 178.5 112.4 75.3 52.9 38.6 29.0 22.3 411.3 238.0 149.9 100.4 70.5 51.4 38.6 29.8 490.3 340.5 224.8 150.6 105.8 77.1 57.9 44.6 411.3 238.0 149.9 100.4 70.5 51.4 38.6 29.8 617.0 357.1 224.8 150.6 105.8 77.1 57.9 44.6 822.6 476.1 299.8 200.8 141.1 102.8 77.3 59.5 942.8 654.7 449.7 301.3 211.6 154.2 115.9 89.3 24 24 24 24 19.2 16 12 8 24 24 24 24 24 24 19.2 12 24 24 24 24 24 24 24 19.2 24 24 24 24 24 24 24 24 137.1 79.3 50.0 33.5 23.5 17.1 12.9 9.9 205.7 119.0 74.9 50.2 35.3 25.7 19.3 14.9 274.2 158.7 99.9 66.9 47.0 34.3 25.8 19.8 326.8 227.0 149.9 100.4 70.5 51.4 38.6 29.8 274.2 158.7 99.9 66.9 47.0 34.3 25.8 19.8 411.3 238.0 149.9 100.4 70.5 51.4 38.6 29.8 548.4 317.4 199.9 133.9 94.0 68.6 51.5 39.7 628.5 436.5 299.8 200.8 141.1 102.8 77.3 59.5 24 24 24 24 16 12 8 6 24 24 24 24 24 19.2 12 8 24 24 24 24 24 24 19.2 12 24 24 24 24 24 24 24 19.2 102.8 59.5 37.5 25.1 17.6 12.9 9.7 7.4 154.2 89.3 56.2 37.7 26.4 19.3 14.5 11.2 205.7 119.0 74.9 50.2 35.3 25.7 19.3 14.9 245.1 170.2 112.4 75.3 52.9 38.6 29.0 22.3 205.7 119.0 74.9 50.2 35.3 25.7 19.3 14.9 308.5 178.5 112.4 75.3 52.9 38.6 29.0 22.3 411.3 238.0 149.9 100.4 70.5 51.4 38.6 29.8 471.4 327.4 224.8 150.6 105.8 77.1 57.9 44.6 25 PSF WIND LOAD 30 PSF WIND LOAD 40 PSF WIND LOAD SPACING & TRIBUTARY SPACING & TRIBUTARY SPACING & TRIBUTARY Double Double Double Single Stud Double Stud Single Stud Single Stud Single Stud Stud Stud Stud Max Stud Max Max Max Stud Max Max Max Stud Max Max Vertical Wind Load Vertical Wind Load Spacing Tributary Tributary Spacing Tributary Tributary Spacing Tributary Tributary Load [lb] [lb/ft] Load [lb] [lb/ft] [in] Width [in] Width [in] [in] Width [in] Width [in] [in] Width [in] Width [in] MAXIMUM LOADING Deflection Limit L/360 L/240 L/180 L/120 Wall Height [ft] 10 12 14 16 18 20 22 24 10 12 14 16 18 20 22 24 10 12 14 16 18 20 22 24 10 12 14 16 18 20 22 24 6117 6117 6117 6117 6117 5782 4892 4192 6117 6117 6117 6117 6093 5141 4392 3794 6117 6117 6117 6117 5334 4571 3947 3441 6117 4901 4589 4349 3948 3533 3150 2812 171.4 99.2 62.5 41.8 29.4 21.4 16.1 12.4 257.1 148.8 93.7 62.8 44.1 32.1 24.1 18.6 342.8 198.4 124.9 83.7 58.8 42.8 32.2 24.8 408.5 283.7 187.4 125.5 88.2 64.3 48.3 37.2 8249 8529 8669 8713 8669 8529 8278 7888 6911 7405 7675 7791 7786 7668 7437 7099 5354 6183 6627 6853 6919 6855 6675 6397 3869 3603 4258 4863 5168 5284 5258 5124 342.8 198.4 124.9 83.7 58.8 42.8 32.2 24.8 514.2 297.5 187.4 125.5 88.2 64.3 48.3 37.2 685.5 396.7 249.8 167.4 117.5 85.7 64.4 49.6 785.7 545.6 374.7 251.1 176.3 128.5 96.6 74.4 24 24 24 19.2 12 8 6 4 24 24 24 24 19.2 12 8 8 24 24 24 24 24 19.2 12 8 24 24 24 24 24 24 19.2 16 Notes • • • • Wall stud analysis per 2005 National Design Specification (NDS) for Wood Construction. For 3-ply and 4-ply built up columns, multiply double stud table values by 1.5 and 2.0. Full depth blocking required at a maximum spacing of 8'-0" for single studs. Structural sheathing or structural siding installed on one side of wall. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 82.3 47.6 30.0 20.1 14.1 10.3 7.7 6.0 123.4 71.4 45.0 30.1 21.2 15.4 11.6 8.9 164.5 95.2 60.0 40.2 28.2 20.6 15.5 11.9 196.1 136.2 89.9 60.3 42.3 30.8 23.2 17.9 • • • • • • 164.5 95.2 60.0 40.2 28.2 20.6 15.5 11.9 246.8 142.8 89.9 60.3 42.3 30.8 23.2 17.9 329.1 190.4 119.9 80.3 56.4 41.1 30.9 23.8 377.1 261.9 179.9 120.5 84.6 61.7 46.4 35.7 24 24 24 16 8 8 6 4 24 24 24 24 16 12 8 6 24 24 24 24 19.2 16 12 8 24 24 24 24 24 24 19.2 12 68.6 39.7 25.0 16.7 11.8 8.6 6.4 5.0 102.8 59.5 37.5 25.1 17.6 12.9 9.7 7.4 137.1 79.3 50.0 33.5 23.5 17.1 12.9 9.9 163.4 113.5 74.9 50.2 35.3 25.7 19.3 14.9 137.1 79.3 50.0 33.5 23.5 17.1 12.9 9.9 205.7 119.0 74.9 50.2 35.3 25.7 19.3 14.9 274.2 158.7 99.9 66.9 47.0 34.3 25.8 19.8 314.3 218.2 149.9 100.4 70.5 51.4 38.6 29.8 24 24 16 12 8 6 4 -24 24 24 16 12 8 6 4 24 24 24 24 16 12 8 6 24 24 24 24 24 19.2 12 8 51.4 29.8 18.7 12.6 8.8 6.4 4.8 3.7 77.1 44.6 28.1 18.8 13.2 9.6 7.2 5.6 102.8 59.5 37.5 25.1 17.6 12.9 9.7 7.4 122.6 85.1 56.2 37.7 26.4 19.3 14.5 11.2 102.8 59.5 37.5 25.1 17.6 12.9 9.7 7.4 154.2 89.3 56.2 37.7 26.4 19.3 14.5 11.2 205.7 119.0 74.9 50.2 35.3 25.7 19.3 14.9 235.7 163.7 112.4 75.3 52.9 38.6 29.0 22.3 Double stud values assume unsupported lateral length of 7'-0". Table assumes wind load duration factor of 1.6 and vertical load duration factor of 1.0. Table assumes compression perpendicular to grain for plate of 450 psi. Vertical dead load may not exceed 50% of the total vertical load. Repetitive member increase for bending (1.04) applied to single studs only. Compression perpendicular to grain stress adjusted per NDS 3.10.4 for single studs only. 12 VERSA-STUD® & VERSA-LAM® Column Details Header to Column Multiple-Ply Stud Connections Header to Column Column Framing angles for lateral support 9" Header Plate size to equal wall thickness Stagger rows 2-Ply 1½" Connection - 2 rows 10d (min) nails @ 9" o.c. - 3 rows for 9¼" and greater studs Trimmer(s) for vertical support 3-Ply 1½" Connection - 2 rows 10d (min) nails @ 9" o.c. - Nail from each side - 3 rows for 9¼" and greater studs Column to Bottom Plate Column to Bottom Plate 4-Ply 1½" Connection - 2 rows 10d (min) nails @ 9" o.c., nailed from each ply to each ply - 3 rows for 9¼" and greater studs Column Sole plate Trimmer(s) stud Rimboard Framing angles for lateral support 3½" Studs - 24" o.c. Blocking panel as required Sill Plate Joist, Rafter or Truss spaced greater than 16" o.c. Solid blocking required if column & trimmer(s) do not extend to sill plate Column to Top Plate Double Top Plate Column to Top Plate Double top plate For 24" o.c. stud spacing (3½" deep studs only), joists, rafters or trusses above shall be offset no greater than 5" from stud below. VERSA-STUD® VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 Framing angles for lateral support Column Trimmer Stud(s) 13 Deflection Limit VERSA-LAM® 1.7 2650 Exterior Wall Column Table L/360 L/240 L/180 L/120 3½" Thick Wall 3½" x 3½" 5½" Thick Wall 7" x 3½" 3½" x 5¼" 5¼" x 5¼" 7¼" Thick Wall 5¼" x 7" 7" x 7" Column Vertical Wind Vertical Wind Vertical Wind Vertical Wind Vertical Wind Vertical Wind Vertical Wind Vertical Wind Vertical Wind Height Load Load Load Load Load Load Load Load Load Load Load Load Load Load Load Load Load Load [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [lb] [lb/ft] [ft] 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 5¼" x 3½" 7" x 5¼" 5513 5513 5513 5513 5113 4383 3799 3324 131.2 87.9 61.7 45.0 33.8 26.0 20.5 16.4 8269 8269 8269 8269 7670 6575 5699 4987 196.8 131.8 92.6 67.5 50.7 39.1 30.7 24.6 11025 11025 11025 11025 10226 8765 7597 6648 262.3 175.8 123.4 90.0 67.6 52.1 41.0 32.8 8269 8269 8269 8269 8269 8269 8269 8269 8269 8195 7362 6649 6034 5500 5036 442.7 296.6 208.3 151.8 114.1 87.9 69.1 55.3 45.0 37.1 30.9 26.0 22.1 19.0 16.4 12403 12403 12403 12403 12403 12403 12403 12403 12403 12016 10802 9764 8869 8096 7416 664.1 444.9 312.4 227.8 171.1 131.8 103.7 83.0 67.5 55.6 46.4 39.1 33.2 28.5 24.6 16538 16538 16538 16538 16538 16538 16538 16538 16538 16021 14405 13022 11829 10793 9887 885.4 593.2 416.6 303.7 228.2 175.8 138.2 110.7 90.0 74.1 61.8 52.1 44.3 38.0 32.8 5513 5513 5513 5359 4581 3959 3455 3040 196.8 131.8 92.6 67.5 50.7 39.1 30.7 24.6 8269 8269 8269 8037 6870 5937 5180 4559 295.1 197.7 138.9 101.2 76.1 58.6 46.1 36.9 11025 11025 11025 10718 9162 7917 6908 6080 393.5 263.6 185.2 135.0 101.4 78.1 61.4 49.2 8269 8269 8269 8269 8269 8269 8269 8269 8191 7357 6646 6033 5496 5035 4623 664.1 444.9 312.4 227.8 171.1 131.8 103.7 83.0 67.5 55.6 46.4 39.1 33.2 28.5 24.6 12403 12403 12403 12403 12403 12403 12403 12403 11861 10680 9664 8785 8019 7348 6758 996.1 667.3 468.7 341.7 256.7 197.7 155.5 124.5 101.2 83.4 69.5 58.6 49.8 42.7 36.9 16538 16538 16538 16538 16538 16538 16538 16538 15814 14240 12886 11714 10693 9799 9012 1328.1 889.7 624.9 455.5 342.3 263.6 207.3 166.0 135.0 111.2 92.7 78.1 66.4 56.9 49.2 5513 5513 5513 4751 4109 3584 3151 2791 262.3 175.8 123.4 90.0 67.6 52.1 41.0 32.8 8269 8269 8269 7125 6163 5375 4726 4185 393.5 263.6 185.2 135.0 101.4 78.1 61.4 49.2 11025 11025 11025 9501 8217 7168 6302 5581 524.7 351.5 246.9 180.0 135.2 104.1 81.9 65.6 8269 8269 8269 8269 8269 8269 8269 8111 7310 6616 6017 5490 5029 4622 4261 885.4 593.2 416.6 303.7 228.2 175.8 138.2 110.7 90.0 74.1 61.8 52.1 44.3 38.0 32.8 12403 12403 12403 12403 12403 12403 12403 11540 10448 9491 8653 7916 7267 6692 6181 1328.1 889.7 624.9 455.5 342.3 263.6 207.3 166.0 135.0 111.2 92.7 78.1 66.4 56.9 49.2 16538 16538 16538 16538 16538 16538 16538 15387 13930 12655 11537 10555 9689 8922 8241 1770.8 1186.3 833.2 607.4 456.3 351.5 276.5 221.4 180.0 148.3 123.6 104.1 88.6 75.9 65.6 4634 4435 4056 3643 3257 2912 2610 2347 393.5 263.6 185.2 135.0 101.4 78.1 61.4 49.2 6936 6645 6078 5462 4883 4366 3914 3520 590.3 395.4 277.7 202.5 152.1 117.2 92.2 73.8 9266 8869 8104 7282 6511 5822 5218 4693 787.0 527.3 370.3 270.0 202.8 156.2 122.9 98.4 8269 8269 8133 7719 7533 7135 6662 6181 5717 5279 4879 4520 4190 3891 3620 996.9 763.2 603.1 455.5 342.3 263.6 207.3 166.0 135.0 111.2 92.7 78.1 66.4 56.9 49.2 12403 12403 11596 9429 9520 9344 8920 8402 7860 7327 6820 6348 5912 5512 5150 1381.2 1057.5 835.6 676.8 513.4 395.4 311.0 249.0 202.5 166.8 139.1 117.2 99.6 85.4 73.8 16538 16538 15485 12587 12715 12471 11893 11204 10481 9771 9097 8468 7888 7355 6867 1841.6 1410.0 1114.1 902.4 684.5 527.3 414.7 332.0 270.0 222.4 185.4 156.2 132.8 113.9 98.4 3½" x 7" 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 10276 9500 8807 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 10800 9971 9227 8566 7966 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 11025 10366 9599 8916 8292 7737 7231 11025 11025 11025 11025 11025 10342 9560 9654 9471 9137 8731 8294 7851 7422 7000 6615 6251 5906 1049.4 703.0 493.7 359.9 270.4 208.3 163.8 131.2 106.6 87.9 73.3 61.7 52.5 45.0 38.9 33.8 29.6 26.0 1574.1 1054.5 740.6 539.9 405.6 312.4 245.7 196.8 160.0 131.8 109.9 92.6 78.7 67.5 58.3 50.7 44.4 39.1 1697.2 1299.4 987.5 719.9 540.9 416.6 327.7 262.3 213.3 175.8 146.5 123.4 105.0 90.0 77.7 67.6 59.2 52.1 1697.2 1299.4 1026.7 831.6 687.3 577.5 491.5 393.5 319.9 263.6 219.8 185.2 157.4 135.0 116.6 101.4 88.7 78.1 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 15422 14249 13209 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16198 14952 13844 12850 11959 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 16538 15548 14405 13375 12446 11607 10847 16538 16538 16538 16538 16538 15906 14306 14483 14185 13705 13089 12428 11780 11133 10513 9926 9373 8856 1574.1 1054.5 740.6 539.9 405.6 312.4 245.7 196.8 160.0 131.8 109.9 92.6 78.7 67.5 58.3 50.7 44.4 39.1 2361.1 1581.8 1110.9 809.9 608.5 468.7 368.6 295.1 240.0 197.7 164.8 138.9 118.1 101.2 87.4 76.1 66.6 58.6 2598.3 1989.4 1481.2 1079.8 811.3 624.9 491.5 393.5 319.9 263.6 219.8 185.2 157.4 135.0 116.6 101.4 88.7 78.1 2598.3 1989.4 1571.8 1273.2 1052.2 884.2 737.2 590.3 479.9 395.4 329.7 277.7 236.1 202.5 174.9 152.1 133.1 117.2 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 21781 20090 18585 17242 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 20830 19258 17853 16594 15461 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 22050 21172 19647 18261 17004 15862 14825 13882 22050 22050 22050 22050 22050 20647 17619 15542 15894 15767 15368 14818 14192 13536 12877 12233 11612 11033 2098.8 1406.0 987.5 719.9 540.9 416.6 327.7 262.3 213.3 175.8 146.5 123.4 105.0 90.0 77.7 67.6 59.2 52.1 3148.1 2109.0 1481.2 1079.8 811.3 624.9 491.5 393.5 319.9 263.6 219.8 185.2 157.4 135.0 116.6 101.4 88.7 78.1 3171.0 2427.8 1918.3 1439.8 1081.7 833.2 655.3 524.7 426.6 351.5 293.0 246.9 209.9 180.0 155.5 135.2 118.3 104.1 3171.0 2427.8 1918.3 1553.8 1284.1 1079.0 919.4 787.0 639.9 527.3 439.6 370.3 314.9 270.0 233.2 202.8 177.5 156.2 Notes • Column analysis per 2005 National Design Specification (NDS) for Wood Construction. • Allowable loads are based upon one-piece (solid) columns used in dry service conditions. • Install columns with depth (second dimension listed in table) matching wall thickness. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 • Load values are not shown for longer lengths if the controlling slenderness ration exceeds 50 (per NDS) • Full depth blocking required at a maximum spacing of 8'-0" • Table assumes wind load duration of 1.6 and axial load duration of 1.0. • Vertical dead load may not exceed 50% of the total vertical load. • Table assumes compression perpendicular to grain for plate of 450 psi. 14 Connectors VERSA-STUD® 1.7 2650 Nail Design Values Nail Type Nail Diameter Nail Length Lateral End Grain Capacity [lb] Lateral Capacity [lb] Lateral Toe-Nail Capacity [lb] 8d box 0.113" 2.5" 116 78 96 8d common 0.131" 2.5" 143 96 119 10d box 0.128" 3" 148 99 123 10d common 0.148" 3" 188 126 156 12d box 0.128" 3.25" 148 99 123 12d common 0.148" 3.25" 188 126 156 16d box 0.135" 3.5" 165 111 137 16d sinker 0.148" 3.25" 188 126 156 16d common 0.162" 3.5" 225 151 187 Notes • Nail values per 2005 National Design Specification (NDS) for Wood Construction. • Nail values based upon a load duration factor of 1.60 and an equivalent specific gravity of 0.5. • Lateral capacites based upon a side-member thickness of 1½”. • For end grain connections, a reduction factor of 0.67 is applied (NDS 11.5.2). • For toe-nailed connections, a reduction factor of 0.83 is applied (NDS 11.5.4). Wall Connectors FRAMING ANGLES STUD/PLATE TIES Simpson Strong-Tie Simpson Strong-Tie Model Stud No. Length Size A23 A34 L30 LS30 L50 LS50 L70 LS70 L70 2¾" 2½" 3" 33/8" 5" 47/8" 7" 63/8" 7" 3½" 3½" 3½" 3½" 5½" 5½" 7¼" 7¼" 7¼" Allowable Load [lb] Nailing (8) 10d x 1½" (8) 8d x 1½" (4) 10d (6) 10d (6) 10d (8) 10d (8) 10d (10) 10d (8) 10d F1 565 365 240 395 445 560 565 665 565 F2 585 280 240 445 565 565 USP Structural Connectors Model Stud No. Length Size A3 AC3 MP3 AC5 MP5 AC7 L70 2¾" 27/8" 33/8" 47/8" 45/8" 615/16" 57/8" 3½" 3½" 3½" 5½" 5½" 7¼" 7¼" Allowable Load [lb] Nailing (8) 10d x 1½" (4) 10d x 1½" (6) 10d (6) 10d x 1½" (8) 10d (8) 10d (10) 10d F1 590 285 485 555 730 740 910 F2 600 320 555 740 - VERSA-STUD® Framing Anchor F2 F1 VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 Model No. Nailing Uplift [lb] RSP4 SSP DSP SP1 SP2 (8) 8d x 1½" (7) 10d x 1½" (14) 10d x 1½" (10) 10d (12) 10d 315 350 775 585 1065 USP Structural Connectors Model No. Nailing RSPT4 RSPT6 RSPT6-2 SPT22 SPT24 (8) 8d x 1½" (8) 10d x 1½" (14) 10d x 1½" (8) 10d (12) 10d Uplift [lb] 470 700 955 725 1085 HEADER CLIPS/HANGERS Simpson Strong-Tie Model No. FC4 FC6 HH4 HH6 Width 9 16 3/ " 5½" 3½" 5½" Nailing Allow Vertical Load [lb] (8) 16d (10) 16d (13) 16d (18) 16d 800 920 1195 1595 USP Structural Connectors Model No. Width Nailing Allow Vertical Load [lb] SFC4 SFC6 HH44 HH66 9 16 (8) 16d (10) 16d (13) 16d (18) 16d 550 690 1240 1650 3/ " 5½" 39/16" 5½" Connection values based upon a load duration factor of 1.6 and an equivalent specific gravity of 0.5. 15 Connectors / Allowable Holes and Notches Base and Top Lateral Wind Reactions for Connectors [lb] 20 PSF Wind Load See footnote 1 for conversions for other wind loads Height [ft] 8 10 12 14 16 18 20 22 24 Stud / Column Tributary Width [in] 12 80 100 120 140 160 180 200 220 240 16 107 133 160 187 213 240 267 293 320 19.2 128 160 192 224 256 288 320 352 384 24 160 200 240 280 320 360 400 440 480 36 240 300 360 420 480 540 600 660 720 48 320 400 480 560 640 720 800 880 960 60 400 500 600 700 800 900 1000 1100 1200 Note 72 480 600 720 840 960 1080 1200 1320 1440 84 560 700 840 980 1120 1260 1400 1540 1680 96 640 800 960 1120 1280 1440 1600 1760 1920 1)For other wind loads, multiply reaction in table by the following factors: 10 PSF = 0.5 15 PSF = 0.75 25 PSF = 1.25 30 PSF = 1.5 40 PSF = 2.0 VERSA-STUD® Allowable Holes and Notches Prescriptive Provisions Engineered Design Provisions Allowable Hole Zone Hole Edge Distance Min. of 5/8" • Middle 1/3rd of stud • No holes within 8" of top or bottom Max. Hole Diameter 1½" x 3½" = 13/8" 1½" x 5½" = 21/8" 1½" x 7¼" & deeper = 27/8" Max. Hole Diameter 1½" x 3½" = 3/4" 1½" x 5½" = 1" 1½" x 7¼" & deeper = 11/4" (1) max. dia hole allowed per stud, located at any location along stud length. DO NOT cut hole and notch at same location. Max. Notch Depth 1½" x 3½" = 7/8" 1½" x 5½" = 13/8" 1½" x 7¼" & deeper = 13/4" Max. Notch Height = 3" (1) notch allowed per stud. DO NOT cut notch and hole at same location. Notes: 1) Provisions valid only for studs within precriptive design (see page 3). 2) Shield plates or nail stops to prevent nailing into wiring or piping shall be installed per the governing building code. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 1/3rd stud width Middle 1/3rd stud width 8" Notes: 1) DO NOT drill more than 3 holes in any 4-foot-long section of stud. 2) The vertical distance between adjacent holes must be at least 2 times the size of the larger hole 3) Holes no greater than 3/4" dia may be cut in the hole zone shown in VERSA-LAM® columns. 4) For notches and larger holes, contact Boise EWP Engineering. 16 Design Properties 1½" VERSA-STUD® 1.7 2650 Design Properties Width [in] Depth [in] Weight [lb/ft] Allowable Shear [lb] Allowable Moment [lb-ft] Moment of Inertia (l) [in4] 1½ 3½ 1.5 998 776 5.4 1½ 5½ 2.4 1568 1821 20.8 1½ 7¼ 3.2 2066 3069 47.6 1½ 9¼ 4.0 2636 4862 98.9 1½ 11¼ 4.9 3206 7038 178.0 VERSA-LAM® 1.7 2650 Column Design Properties Width [in] 3½ 3½ 3½ 5¼ 5¼ 7 Depth [in] 3½ 5¼ 7 5¼ 7 7 Weight [lb/ft] 3.6 5.4 7.1 8.0 10.7 14.3 Allowable Moment Allowable Moment Edge (1) Flat (1) [lb-ft] [lb-ft] 1810 1639 3892 3525 6702 6069 5838 5287 10053 9104 13403 12139 Moment of Inertia (l) [in4] 12.5 42.2 100.0 63.3 150.1 200.1 1) Allowable bending stress is 2650 psi on edge (parallel to gluelines), 2400 psi flat (perpendicular to gluelines) Allowable Stress Value Comparison Product Bending Fb [psi] Compression Parallel to Grain Fc [psi] Compression Perp to Grain Fc┴ [psi] Modulus of Elasticity E [psi] Horizontal Shear Fv [psi] VERSA-STUD® 1.7 2650 2650 3000 450 1700000 285 875 1150 425 1400000 135 850 1300 405 1300000 150 675 900 335 1000000 135 Spruce Pine Fir (North) #1/2 Grade Hem-Fir # 2 Grade Western Woods #2 Grade • Design values are for loads applied to the narrow face of the studs. • Dimension lumber values taken from 2005 Edition, NDS Design Values for Wood Construction. (per 2006 IBC/IRC) • Repetitive member and size factors have not been applied. VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 17 VERSA-STUD® Wall Sheathing Nailing Prescriptive Nailing Shear Walls Since VERSA-STUD® may be used in prescriptive design in the IBC and IRC, it may be installed as studs in braced wall panels. Standard nailing for prescriptive wood stud walls with structural sheathing is 6d common nails for panels 5/16" to ½" thick, 8d common nails for panels 19/32" to 1" thick, spaced at 6" on-center on panel edges and 12" on-center in intermediate studs. VERSA-STUD® may be used in shear wall construction. Allowable shear /8" Sheathing Gap 1 values may be determined by using Table 2306.4.1 of the IBC, shear walls with Douglas fir-Larch framing, subject to the following conditions: 1. A double VERSA-STUD® must be used at all panel edges of shear walls. Studs must be stitch-nailed together with two rows of 10d common nails at 8" on-center, staggered. 2. Nails at panel edges must be staggered along two nailing lines spaced approximately ½" apart. Nails at panel edges must also be at least 3/8" from the edges of the VERSA-STUD ® and the wood structural panel (see detail below). 3. The tabulated shear values for nailed wood structural panel shear walls using 8d or 10d box or common nails at a panel edge nailing of 2" must be multiplied by a factor of 0.9. 4. The tabulated shear values for nailed wood structural panel shear walls using 10d box or common nails at a panel edge 1 nailing of 3" must /8" Sheathing be multiplied by Gap a factor of 0.9. 3 6" o.c. Nail Spacing (per code) /8" min. edge distance to panel edge ½" stagger 3 Stich Nailing 2 rows 10d common 8" o.c., staggered /8" min. edge distance to stud Closest nail spacing = 2" o.c. (with stagger and shear wall reduction, 8d & 10d nails only) Double Stud Nailing Edges Shear Wall Only Single Stud Nailing at Panel Edges Fire Assemblies VERSA-STUD® are permitted as a direct replacement for solid-sawn lumber in any fire-resistance-rated wall assembly listed in Table 720.1(2) of the IBC, provided the VERSA-STUD® have a minimum depth of 5½". VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 18 BC COLUMN® Software Boise Cascade EWP is proud to introduce BC COLUMN®. BC COLUMN® is new software that will allow customers the ability to design columns using Boise Cascade Engineered Wood Products. BC COLUMN™ Using BC COLUMN®, users can quickly: • Design a column or stud using Boise Cascade Engineered Wood Products. • Add gravity and out-of-plane lateral loads. • Add bracing/supports. • Select and test products in the design. • Refine performance factors. • Print design reports. The steps are simple. To use: • Set up the project: • Launch BC COLUMN®. • Enter project information. • Specify the design and select a product. • Describe the type of column or stud, its height and its bracing. • Adjust the axial load and add additional out-of-plane lateral loads. • Select a product. Specify the Deflection. • Specify the column/stud deflection. • Analyze and refine designs. • Review and print design reports. BC COLUMN® is installed with BC CALC for the US market ONLY. To request a CD or Download of BC CALC/BC COLUMN US http://www.bc.com/wood/ewp/software/bccalc/order/US-form.html VERSA-STUD ® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 19 Computer Software BC FRAMER® CADD Framing Software BC FRAMER® is an easy-to-use, stand-alone computer-aided drafting program with 3D capability designed to quickly create floor and roof framing layouts. Draw walls, add framing areas, locate beams and rough open­ings, define cross-sections and on-center spacing. In minutes, BC FRAMER® frames your layout, builds a piece and price report, creates a framing drawing with schedule, all using Boise Cascade Engineered Wood Products. Easy-to-use editing and drawing tools allow flexibility when modifying members and adding details, symbols and accessories. Training classes for BC FRAMER® are provided at Boise Cascade's training centers located in Oregon, Louisiana and Georgia. RECOMMENDED HARDWARE • Current Pentium Processor 8VHWKH/RDGVWRROEDUWRDGGORDGV 8VHWKH1HZ'HVLJQWRROEDU • 2GB RAM (min.) 8VHWKH+ROHVWRROEDUWRDGGKROHVLQMRLVWV WRFUHDWHDQHZGHVLJQ For questions, comments or a free demonstration •Microsoft ® Intellimouse CD visit our website at www.bcewp.com or email us • Windows 7, Vista or XP Professional at EWPSupport@BC.com. Information can also be 'DWD(QWU\7DEV obtained at 1-800-405-5969. 0HPEHU'LDJUDP (QWHUGHVLJQ Improvements in capacity or speed 6DPHDV%&&$/&D FULWHULDDQGVHOHFW SURGXFWVKHUH Give Us of these components will yield better 'RXEOH&OLFNRQ$QDO\VLVWR performance. a Try! DQDO\]HGHVLJQ %&&$/&>-51'HVLJQ9LHZ%&&@ BC CALC® Sizing Software )LOWHUWRVKRUWHQ SURGXFWVHOHFWLRQ OLVW 'RXEOH&OLFNRQ&DXWLRQVWR DQDO\]HGHVLJQDQGGLVSOD\ 5HSRUW GRXEOHFOLFNRQD SURGXFWWR BC CALC® is Boise Cascade's sizing software 'RXEOH&OLFNRQDQ\LWHPWR for BCI® Joists and VERSA-LAM ® Beams. GLVSOD\DQGFKDQJHGHVLJQ SDUDPHWHUV BC CALC® is simple to use, yet flexible enough to analyze most joist and beam applications. Span, load 9LHZWDEV&OLFNRU&WUO' &WUO5&WUO(WRVHHWKH and hole information entered by the user 'HVLJQZLQGRZ5HSRUWRU is analyzed (QJLQHHULQJ'DWD by the program to correctly size Boise Cascade Engineered Wood Products. A comprehensive Help File menu is included in the program. 3URMHFW0DQDJHUWDE 'HVLJQ7DEV(DFKGHVLJQKDVLWV RZQ&OLFNRU&WUO$UURZWRVHOHFW 8VHWKH/RDGVWRROEDUWRDGGORDGV 8VHWKH1HZ'HVLJQWRROEDU WRFUHDWHDQHZGHVLJQ 2SHQ9LHZ PHQXDQG DQDO\]HGHVLJQ to designers, architects and BC CALC ® is available VHOHFW$GMXVW engineers on CD-ROM or by download at 'HVLJQ9LHZ /D\RXWWR GLVSOD\'DWD (QWU\7DE www.bcewp.com Hardware requirements include UHORFDWHER[ Pentium ® Processor with a recommended ®'DWD(QWU\7DE minimum of 1GB RAM. To order BC CALC UHVL]HEXWWRQ , call 1-800‑405-5969 or email EWPSupport@BC.com. $QDO\VLV5HVXOWV 'HVLJQ9LHZ:LQGRZ To request a CD or Download of BC CALC US, http://www. bc.com/wood/ewp/software/bccalc/order/US-calc-form.html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® 1.7 2650 Wall Guide - Eastern UNITED STATES 11/07/2008 r 07/21/2011 2SHQ:LQGRZPHQXWRKLGHVKRZDOOGHVLJQV 'UDJFROXPQ ERUGHUWRUHVL]H 'UDJFROXPQ KHDGLQJWRPRYH 5LJKW&OLFNWR DGGGURSFROXPQV If in doubt ask! For the closest Boise Cascade EWP distributor/support center, call 1-800-232-0788 Boise Cascade EWP is a participant in the Sustainable Forestry Initiative® (SFI®), a comprehensive forest management program that is a combination of environmental responsibilities and sound business practices. The procurement systems of Boise Cascade’s engineered wood product facilities have been audited by PricewaterhouseCoopers to the SFI® Standard and its products will carry the SFI® Label. These procurement systems provide tracking information on Boise Cascade’s supply chain sources. Great products are only the beginning.™ Lifetime Guaranteed Quality and Performance Boise Cascade warrants its BCI® Joist, VERSA-LAM®, and ALLJOIST® products to comply with our specifications, to be free from defects in material and workmanship, and to meet or exceed our performance specifications for the normal and expected life of the structure when correctly stored, installed and used according to our Installation Guide. For information about Boise Cascade's engineered wood products, including sales terms and conditions, warranties and disclaimers, visit our website at www.BCewp.com BOISE CASCADE, TREE-IN-A-CIRCLE, BCI, BC CALC, BC FRAMER , BC RIM BOARD, BOISE GLULAM, SIMPLE FRAMING SYSTEM, VERSA-LAM, VERSA-RIM, VERSA-STRAND, and VERSA-STUD are trademarks of Boise Cascade, L.L.C. or its affiliates. Your Dealer is: If no dealer is listed, call 1-800-232-0788 Copyright © Boise Cascade, L.L.C. 2011 (QJLQHHUHG:RRG3URGXFWV EVSWG 11/2008 r 07/21/2011