The Meaning of LIFE 1 Transformer Life The Meaning of LIFE! IEEE C57.91 Guide for Loading Mineral-Oil Immersed Transformers Thermal Profile air oil Transformer Height h Top Oil core & coil NL (core) Losses I2R NL (core) Losses Bottom Oil Oil Temperature Top Oil Temperature air oil Transformer Height h Note: The FLASH POINT of Transformer Oil is about 140 Deg C! Top Oil core & coil Bottom Oil Oil Temperature Average Winding Rise Resistance - ohms P S S P P S S P Average Winding Rise : Measured by the Resistance of the windings at the shut-down of a heat run... (t = 0) shut down time Limited by ANSI to <= 55/65 deg C... i.e., the basic definition of the kVA Rating of a Transformer! Effective kVA A good approximation for calculating the Effective kVA over the range of parameters normally encountered in Distribution Transformers is... Effective kVA = Rated kVA x 65 Average Winding Rise For example, a Transformer rated at 25 kVA with an AWR of 50 deg C would have the capacity of a 30.4 kVA... 0.75 Hottest Spot P S S P P S S P Transformer Hot Spot - Typically, the Hot Spot Gradient (HSG) is 1.6 - 2 times the difference between the Average Winding Rise (AWR) and the Top Oil Rise (TOR)... Attempts to measure the Hottest Spot involve embedding thermocouples inside the windings... this of course is not typically done on production units... Limited to 140-170 deg C for Mineral Oil Hottest Spot – Disk Wound Typically, the Hot Spot Gradient (HSG) for Power Construction is 1.1 to 1.2 times the difference between the Average Winding Rise (AWR) and the Top Oil Rise (TOR)... Due to the Oil Flow inside the windings, the Hottest Spot is typically near the top… Forced Oil (Directed or Non-directed) flow can effect this relationship… For Core-Type Construction, Embedding Fiber Optic Temperature Transducers inside the disk wound windings can be done when the unit is Unblocked... Typically these are placed near the top (1-3 layers) down near the Center of the Low Voltage winding… Temperature - Deg C Transformer Temperatures Hottest Spot hottest spot gradient (HSG) Top Oil top oil rise (TOR) Ambient time Under Steady-State Load and Ambient Conditions, the temperatures stabilize to constant values... Steady-State Load Conditions Temperature - Deg C Transformer Temperatures Hottest Spot HSG = rated HSG x K2m TOR = rated TOR x K2R+1 n R+1 Top Oil Ambient time The TOR and HSG at any value of Load is a function of the Rated values of TOR and HSG, the Load (K), the Ratio of Losses (R = LL/NL), and the winding (m) and oil (n) exponents... Steady-State Load Conditions Transformer Thermal Calculations The Calculations of the Hottest Spot, Top Oil, and Insulation Life are defined in ANSI C57.91. These procedures were verified in the late 1980’s in actual tests done by several manufacturer’s working with the IEEE Transformers Committee. Thermal Mass Load K2 Tank K1 Oil C&C t=0 time The Temperature response to a change in LOAD is a function of the MASS of the System reflected in the TIME CONSTANT... Oil Time Constant K2 Load for Top Oil... K1 tcoil = C x TOR Total Losses C = .06 x C&C + .04 x Tank + 1.33 x Oil Gallons (note: for OA ratings with Copper Windings...) t=0 time The Top Oil Time Constant is a function of the Capacity Factor, the Rated Top Oil Rise, and the Total Losses... Oil Time Constant K2 Load for Top Oil... K1 tcoil = C x TOR Total Losses C = .06 x (WtCC-WtAL) + .14 x WtAL + .04 x WtTANK + 1.33 x Oil Gal (note: for OA ratings with Aluminum Windings...) t=0 time The Top Oil Time Constant is a function of the Capacity Factor, the Rated Top Oil Rise, and the Total Losses... Hottest Spot Time Constant Load K2 for the Hottest Spot ... K1 tchs = 5 to 15 minutes depending on the winding material and construction... t=0 time The Winding Time Constant is a function of Coil Construction and is usually supplied by the Manufacturer... Top Oil Rise – Increasing Load Load K2 K1 tu TOR = ( tu - ti ) ( 1 - e -t/tc oil ) + ti ti t=0 time The TOR at any point in time is a function of both the Initial and Ultimate Top Oil Temperatures and the Top Oil Time Constant... Hottest Spot – Increasing Load HSG = (gu - gi) (1-e -t/tc hs) + gi gu K2 Load tu K1 gi TOR = ( tu - ti ) ( 1 - e -t/tc oil) + ti ti t=0 time The HSG at any point in time is a function of both the Initial and Ultimate Hot Spot Temperatures and the Hot Spot Time Constant... Top Oil – Decreasing Load Load K1 K2 ti t=0 tu TOR = ( ti - tu ) ( e -t/tc oil) + tu time The TOR at any point in time is a function of both the Initial and Ultimate Top Oil Temperatures and the Top Oil Time Constant... Hottest Spot – Decreasing Load Load K1 K2 HSG = (gi - gu) (e -t/tc hs ) + gu ti gu t=0 TOR = ( ti - tu ) ( e -t/tc oil) + tu tu time The HSG at any point in time is a function of both the Initial and Ultimate Hot Spot Temperatures and the Hot Spot Time Constant... Insulation Life The Insulation LIFE of a Transformer is a function of Temperature and Time at Temperature... Insulation Life – Montsinger’s 8 degree Rule The LIFE of “varnished cambric tape”, as defined by a reduction in the tensile strength, is reduced by one half for each 8 deg C increase in continuous temperature... This work was done in the 1920’s and later refined to 6 to 10 degrees based on the temperature range involved... End-of-Life was defined as the point where the tensile strength was reduced by 50% of the initial value... Insulation Life – Retained Tensile Strength Life vs. Temperature Temperature In the 1940’s, Dakin postulated that transformer insulation deteriorated following a modification of Arrhenius’ chemical reaction rate theory. Log LIFE = A + B/T where T is the ABSOLUTE Temperature of the Hottest Spot within the Winding... T LIFE Hours to Failure note: shown as a log-log relationship... Hottest Spot Temperature - Deg C Life Testing Based on AIEE Transformer’s Committee tests done in the mid-1950’s, LIFE curves for Transformers were established... 220 group 1 Log LIFE = A + B/T group 2 180 group 3 140 Lockie Tests Hours to Failure Insulation Life Testing - ANSI C57.100 log-log relationship... Life Testing Insulation Life Testing - ANSI C57.100 Hottest Spot Temperature - Deg C Life Testing Based on AIEE Transformer’s Committee tests done in the mid-1950’s, LIFE curves for Transformers were established... 220 group 1 Log LIFE = A + B/T group 2 180 group 3 140 Lockie Tests Hours to Failure Insulation Life Testing - ANSI C57.100 log-log relationship... Hottest Spot Temperature - Deg C Life Testing Based on AIEE Transformer’s Committee tests done in the mid-1950’s, LIFE curves for Transformers were established... group 1 220 Log LIFE = A + B/T 1/5 180 140 C5 7.9 1-1 981 group 2 Dis trib uti on group 3 Lockie Tests Hours to Failure Insulation Life Testing - ANSI C57.100 log-log relationship... Hottest Spot Temperature - Deg C Life Testing Based on AIEE Transformer’s Committee tests done in the mid-1950’s, LIFE curves for Transformers were established... group 1 220 Log LIFE = A + B/T 1/5 180 140 1/2 C5 7.9 1-1 981 C5 7.9 2-1 981 Pow er group 2 Dis trib uti on group 3 Lockie Tests Hours to Failure Insulation Life Testing - ANSI C57.100 log-log relationship... Standard Life Curves Hottest Spot - Deg C 1960 - 1980’s C57.91-1981 110 100 90 C57.92-1981 10 30 50 70 Relative Insulation Life - years ANSI Loading Guides - 65 deg C Life Equations Insulation Life Based on work done on model power transformers in the 1980’s by EPRI... a) It was decided that the insulation life curves for both Power and Distribution Transformers are similar...C57.91, C57.92 and C57.115 were combined into C57.91.1995 b) ANSI C57.100 should be used for the evaluation of the thermal life of new insulation systems... c) The chemical test measurement of degree of polymerization (DP) is a much better indication of cellulose insulation mechanical characteristics than loss of tensile strength... ANSI Loading Guide - C57.91-1995 Per-Unit Life B Per Unit Life = A exp ΘH + 273 A = 9.8 x 10 -18 B = 15000 Per Unit of Normal Life 1000 (based on 180,000 hours, i.e., 20.55 years at 110 Deg C for 1 NORMAL Life) 100 10 1.0 0.1 0.01 0.001 50 110 Hottest Spot Temperature - deg C ΘH = Hottest Spot Temperature - Deg C ANSI Loading Guide - C57.91 1995 190 Normal Insulation Life for a well-dried, oxygen free 65 deg C average winding temperature rise insulation system at the reference temperature of 110 deg C... Hours Years 50% retained tensile strength of insulation (former C57.92-1981 criterion) 65,000 7.42 25% retained tensile strength of insulation 135,000 15.41 200 retained degree of polymerization in insulation 150,000 17.12 Interpretation of distribution Transformer functional life test data ( C57.91-1981 criteria) 180,000 20.55 ANSI Loading Guide - C57.91 1995 Non-Invasive Testing - Furans The DP of paper can be determined utilizing ASTM method D-4243. Acquisition of a paper sample is an invasive and expensive procedure that requires taking the unit off line. A non-invasive alternative has been developed recently based on the determination of oil soluble cellulose decomposition products called “furans”. These compounds can analyze these compounds from an oil sample with High Performance Liquid Chromatography. The most significant compound is 2Furfuraldehyde where concentrations of this compound have been correlated with DP. Chendong has developed an empirical correlation between the concentration of 2-Furfuraldehyde and the DP. Log [Fur] = 1.51 - 0.0035 DP where [Fur] = conc. of 2-Furfuraldehyde in PPM. This equation, though not exact, allows one to estimate the DP of cellulose insulation. Knowing the DP value, one can estimate the remaining insulation life of a transformer. Limitations • The flash point of standard transformer oil is about 135-140 deg C. ANSI C57.91 recommends that the maximum allowable temperature for Top Oil should not exceed 110 deg C! (Mineral Oil) • Due to the potential of gas bubble generation in mineral oil, the Hottest Spot temperature should be limited to a maximum of 140 deg C (Mineral Oil) in the Spring/Fall and summer seasons. Temperatures up to 170 deg C can typically be allowed in the winter seasons. • The thermal limitations of equipment and components such as bushings, gaskets, tap changers, switches, etc. should be considered. • For normal 55/65C Oil-Paper insulation systems, Thermal run-away begins around 200 deg C. All Transformers will eventually fail… Lots of problems can be avoided by reducing the risk of an eventful failure… Transformer Case Studies 36 Transformer Applications – FECA Agenda June 11, 2009 08:30-10:00 Transformer Overview - Basic Construction - Lightning / LV Surges - Voltage Regulation / Flicker - Life Cycle Costing / DOE Efficiency Ruling 10:00-10:15 Break 10:15-12:15 Insulation Life (C57.91) + TAP Simulations - The “Meaning of Life”the C57.91 Loading Guide - Over Head – Residential + flicker - Padmount – Residential + fusing + Short Circuit - Padmount 3Φ + harmonics - Vault 3Φ + vault restrictions - Substation/Power Transformers - Ratings/Cooling Modes – Settings - Contingency Modeling 1:00 – 2:45 Power Transformer Maintenance, Monitoring & DGA 2:45 – 3:00 Exams/Discussions/wrap-up Revised May 29, 2009 dad Case Studies Case Studies : 1. Overhead Residential – OH/Res 3. Padmounted Residential – PM/Res 5. Commercial Padmount – PM/3Φ Com 7. Commercial Vault – Vault/3Φ Com 9. Substation/Power Case Study – OH/Res Case Study – OH/Res Ambient Case Study – OH/Res Load Case Study – OH/Res Transformer Case Study – OH/Res Load Summary Case Study – OH/Res Secondary Case Study – PM/Res Case Study – PM/Res Load Case Study – PM/Res Transformer Case Study – PM/Res Bayonet Fusing Case Study – PM/Res Load Summary Case Study – PM/Res Touch Temps Case Study – PM/Res SCA & VR Case Study – PM/Res Customer Letter Case Study – PM/3Φ Com Case Study – PM/3Φ Com Load Case Study – PM/3Φ Com Transformer Case Study – PM/3Φ Com Transformer Case Study – PM/3Φ Com Harmonics Case Study – PM/3Φ Com Harmonics Case Study – PM/3Φ Com w/Harmonics Case Study – VAULT/3Φ Com Case Study – VAULT/3Φ Com Transformer Case Study – VAULT/3Φ Com FUSING Case Study – VAULT/3Φ Com Load Summary Case Study – VAULT/3Φ Com Secondary Case Study – VAULT/3Φ Com Secondary Case Study – VAULT/3Φ Com Secondary Case Study – Substation Case Study – Substation AMBIENT Case Study – Substation LOAD Case Study – Substation TRANSFORMER Case Study – Substation OPTIONS Case Study – Substation Load Summary Case Study – Substation NATURAL ESTER Case Study – Contingency Modeling North American Transformer 200//333/373 55/65C MVA Pershing Sub - #6 Case Study – Contingency Modeling With 85% of peak top rating applied (317050 kVA) during the peak season (extreme summer) a switching operation adds an additional 130550 kVA (about 120% of Peak) for 15 minutes… the Hottest Spot peaks to 89.8 degrees C and is still within the NERC specified requirements (max is 105C). The losses, Top Oil Rise and Hottest Spot Gradients used to develop the review on this unit is based on supplied manufacturer test reports… this is using Clause 7 of C57.91… Case Study – Contingency Modeling Using the Annex G procedure, with 85% of peak rating applied (317050 kVA) during the peak season (extreme summer) the switching operation (120% of peak) shows the Hottest Spot peaks to 95.43 degrees C which is still within the requirements (max is 105C). Note the difference between the results of the Clause 7 procedure vs. Annex G… note that Annex G routines provide a metric on ‘duct’ oil which might be useful in predicting potential gassing… Case Study – Summary Q/A? Don A. Duckett, P.E. Technical Sales Engineer HD Supply Utilities (407) 402-0944 Don.Duckett@ieee.org