AN909 TESTING OF TRANSFORMER (Using DPATT-3Bi) ILLU STR A TE D B Y E XA M PLE 1 ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 . TESTING OF DISTRIBUTION Transformer Step BY Step These tests are known by various names. Short Circuit Test OR Full Load Test OR Copper Loss Test OR Winding Loss Test Open Circuit Test OR No Load Test OR Iron Loss Test OR Core Loss Test Example of Transformer Name Plate 2 ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 . SHORT CIRCUIT TEST OF TRANSFORMER The test is conducted on the high voltage side of the transformer. Where the secondary winding (usually of low-Voltage Side) of the transformer is short circuited. The full load current is applied on the primary side of transformer. The core losses are very small because applied voltage is only a few percentage of the nominal voltage and hence can be neglected. Thus the wattmeter reading measures only the full load copper loss. Figure 1 SHORT CIRCUIT TEST STEP1 -Before starting the test, Calculate the full load current from the name plate rating. It’s Simple! For the name plate shown above, we can easily see thatTransformer Rating: HT Voltage=11KV LT Voltage=415V (P-P) KVA Rating=200 KVA Take a calculator and solve√ √ 3 . ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 . PREPARE TO SETUP STEP2- Short the LT side of Transformer and apply voltage at HT side of Transformer until the full load current achieved. STEP3- Find out the Impedance Voltage. Note down the voltage show on DPATT-3Bi STEP4- Suppose that 10.49A comes on 463.1 V Impedance Voltage=463.1V % !"#$%&'# 1 . !"#$%&'# ()*+%,# . 100 -%+#$ ()*+%,# . The SC Test of the transformer is displayed after pressing the F2 button as shown below: STEP5- Copper losses are shown on W/PF page of DAPTT-3Bi. Typical Values for Transformers of different values:EXAMPLE: - 11KV/415V Rating of Transformer 100KVA 200KVA 300KVA 400KVA 500KVA 600KVA Full Load Current 5.24A 10.48A 15.72A 20.96A 26.2A 31.44A Impedance Voltage: That voltage at which full load current is achieved is called impedance voltage. 4 ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 . OPEN CIRCUIT TEST OF TRANSFORMERThis test is carried out to determine iron losses in the transformer. This test is important because whenever the transformer is ON it consumes electricity in the form of iron loss. This loss occurs round the clock and it should be minimized through better design of iron core. Figure 2 OPEN CIRCUIT TEST The core loss and magnetizing current depends on applied voltage and frequency. It is recommended, that since we have no control on variation of mains frequency the applied voltage is varied to keep the V/f ratio constant. For example, in the figure above, Standard voltage 240V P-N or 415V P-P is applied on LT side through variac keeping HT side open. STEP1 - Find the value of Rated Voltage:According to name plate:HT Voltage=11KV LT Voltage=415V (P-P) KVA Rating=200 KVA Rated Voltage =11KV (Primary Side) Rated Voltage =415V (Secondary Side) 5 ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 . STEP 2- HT Side of Transformer is kept open and apply voltage through variac on LT side until the rated voltage achieved. In case Supply frequency is different from rated frequency, we have to calculate voltage to be applied according to Supply frequency. Example- Rated LT Voltage, VRT = 415 V Rated Frequency, FRT = 50 Hz The OC Test of the transformer is displayed after pressing the F1 button as shown below: If, Supply frequency, FS =49.50Hz Voltage to be applied, 2 5 67 8 5 34 39 : : ;7 .: . <: V STEP 3Example- Solve: Find the value of No Load Current. Transformer Rating HT Voltage= 11KV LT Voltage=415V Rating of T/F= 200KVA Rated Voltage=415V Full Load Current =10.49A No Load Current= 2.5% of Full Load Current (According to BEE) =>.?@ A B.C =>> STEP4- 6 0.26A Iron losses are shown on W/PF page of DAPTT-3Bi . ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 . The maximum allowable losses at rated voltage and rated frequency permitted at 75 C for 11/o.433 KV transformer can be chosen by the utility from the value of 3 star, 4 star or 5 star rating for transformer up to rating of 200 KVA as indicated below: Voltage Ratio Rating (KVA) 3 Star 4Star 5Star +11000/433-250V 16 Max. Losses at 50% Loading (Watt) 150 11000/433-250V 25 210 695 190 635 175 595 11000/433-250V 63 380 1250 340 1140 300 1050 11000/433-250V 100 520 1800 475 1650 435 1500 11000/433-250V 160 770 2200 670 1950 570 1700 11000/433-250V 200 890 2700 780 2300 670 2100 11000/433-250V Max. Losses at 100% Loading (Watt) 480 Max. Losses at 50% Loading (Watt) 135 Max. Losses at 100% Loading (Watt) 440 Max. Losses at 50% Loading (Watt) 120 Max. Losses at 100% Loading (Watt) 400 The value of impedance of transformers at 75 0C shall be 4.5% for transformers up to and 200 kVA and for ratings above 200 kVA shall be in accordance with IS 2026.(BEE) Typical value of impedance voltage for transformer with two separate winding (At rated current, given as a percentage of the rated voltage of the winding to which the voltage is applied) I S 2026 Rated Power (KVA) Impedance voltage(percent) 4.0 Up to 630 5.0 631 to 1 250 6.25 1 251 to 3 150 7.15 3 151 to 6 300 8.35 6 301 to 1 2500 10.0 12 501 to 2 5000 12.5 25 001 to 200 000 References: 1. I S 2026-1977-Specification for Power Transformer. 2. BEE CODE Transformer-2006 3. Electrical Machines (J.B. Gupta) 7 ©Uma Electronics Enterprise, 2012 http://www.umaelectronics.com Version 3.0 28 Aug 2012 AN909 .