Sample PDF Report

advertisement
Fire Suppression Inspection Report
537-4
Subject Property
1967 Burke Ln
Farmington
84025
United States
Client Information
Client name:
Kim Glines
Inspection Details
Date/Time:
October 22, 2013 07:05 AM
Inspection Conducted By
Kwikreports Inc
123 Sample St.
Any Where
FL
Inspected by:
Scott Dalrymple
Inspector's Signature:
[signature not uploaded]
United States
Phone: 239-220-5464
Fax: 239-220-5465
info@kwikreports.com
www.kwikreportsfs.com
Fire Suppression Inspection Report
Page 1 of 23
General Section
537-4
Visual inspection of entire system
YES
Have there been any modifications to the system
since the last inspection?
All systems are in service at time of inspection.
YES
Are all areas accessible for inspection?
YES
All water filled piping is located in heated areas.
YES
Control valves are sealed in the open position.
YES
Control valves are monitored by tamper switches.
YES
Is the building occupied?
YES
Is occupancy the same has last inspection?
YES
Are all new building changes and additions
protected?
YES
Are alarm systems in service?
YES
Has monitoring company been notified?
YES
Name of alarm company
Peak Alarms
Phone number of alarm company
Is hydraulic calc card in place?
Are gauges in good working condition?
NA
Password if available
na
5556960666
Any fires reported since last inspection?
NA
YES
Are system identification signs in place?
YES
No
Heat tape in good working condition?
YES
Is system a hydraulic calculated system?
YES
Year of gauges
2000
Is condition of valve room in good condition?
YES
General Deficiencies
Item #1
Location:
System:
Component:
Condition:
Explanation:
Impact:
Recommendation:
General Section537-4
Fire Control Area
General
Gauges
Gauges are over five years old
Gauges that are over 5 years old may not be reading correctly.
Gauges that are not reading properly give false pressure readings and could give false inspection history. Gauges should be
replaced or calibrated every 5 years. Ref.5.3.2
Replace
Page 2 of 23
PIPE, HANGERS & VALVES Section
No indication of serious corrosion?
NA
537-4
Non-system materials or equipment are not
supported from sprinkler piping?
YES
Hangers are secured to piping and the building
structure?
YES
Sway bracing in good condition?
YES
Sway bracing attached to pipe and to structure
satisfactory?
YES
Are conditions of sprinkler pipe satisfactory?
YES
Are conditions of control valves satisfactory?
YES
Gate valve Are conditions of drain valves
satisfactory?
YES
Type of pipe
Black
Type of control valves
G x G butterfly
Are conditions of strainers satisfactory?
NA
Are check valves in good condition?
YES
Piping free of leaks and corrosion?
No
Piping through floors and walls have correct
clearance?
YES
Pipe Deficiencies
Item #1
Location:
System:
Component:
Condition:
Explanation:
Impact:
Recommendation:
Attic
Pipe
Pipes
Piping is leaking
A leak has been noted in the piping
The leak that has been noted in the piping could have a negative impact on the life of the pipe and could cause more serious
damage if not repaired, such as property damage and flooding. This should be repaired as soon as possible to prevent further
problems. Ref 5.2.2
Repair or replace
PIPE, HANGERS & VALVES Section537-4
Page 3 of 23
Fire Department Connection Section
FDC is accessible & unobstructed?
Plugs or caps are in place?
YES
No
537-4
Inlets are not obstructed by foreign material?
YES
Swivel connections turn freely?
YES
Is ball drip functioning satisfactory?
YES
Is check valve holding tight?
YES
Are FDCs in good condition and properly
maintained?
YES
FDC gaskets in place and in good condition?
YES
FDC name plate visible?
YES
Note location of FDC
front of building
FDC Deficiencies
Item #1
Location:
System:
Component:
Condition:
Explanation:
Impact:
Recommendation:
Exterior Front
FDC
FDC
Plugs or caps missing
Plugs and caps must be in place to prevent debris from entering the pipe .
Plugs or caps that are missing may allow birds and hornets to build nests, and other debris to enter the FDC, this may lead to
failure of the FDC in case of a fire. Remove any obstruction and replace caps or plugs. Regular inspections can be performed by
the building owner or representative. Ref. 13.7.1
Repair or replace.
Fire Department Connection Section537-4
Page 4 of 23
Sprinkler Heads Section
Sprinklers are visually free of corrosion, paint or
foreign materials?
YES
Residential & quick response sprinklers are less
than 20 years old?
NA
The stock of spare sprinklers is of adequate
number and type?
YES
135-170
chrome
Sprinklers are of proper temperature rating?
YES
Make of sprinklers
ssu
2009
Finish of sprinklers.
white
YES
Reliable
Globe
Model of sprinklers.
175-225
Year of sprinklers
Sprinklers are less than 50 years old?
Viking
Temperature of sprinklers.
537-4
ssp
semi recessed
concealed
side wall
Approximately number of sprinklers.
500
Finish of escutcheons
brass
white
chrome
Spare head wrench available?
YES
Sprinkler spray patterns are not obstructed?
YES
All protected areas have adequate sprinkler
coverage?
YES
Dry pendent sprinklers older than 10 years
replaced?
YES
Make of dry pendant
Model of dry pendant
G
Globe
Year of dry pendant
2009
Finish of dry pendant
Approximate number of dry pendant
20
Sprinklers are not subject to recall?
YES
Are all required sprinkler tests up to date?
YES
chrome
Sprinklers with glass bulbs look to be full of liquid?
YES
Heads Descriptive Photos
Sprinkler Heads Section537-4
Page 5 of 23
Item #1
Location:
System:
Component:
Short Description:
Details:
Long Description:
Comments:
Throughout
Heads
Condition of sprinkler heads
Photo of sprinkler heads
A deficiency such as painted, loaded or leaking would be noted. A routine inspection is suggested and any damaged or leaking
heads be reported and repaired. The environment that the heads are located may require more frequent inspections.
Any remodeling may require sprinklers to be added or relocated consult your contractor or designer for any changes that may
need to be done.
Pictures in this section do not show deficiency item but they do show the condition of the sprinkler heads.
Sprinkler Heads Section537-4
Page 6 of 23
Wet Pipe Section
Alarm valves in satisfactory condition?
YES
Retard chamber in satisfactory condition?
All flow indicators in good working condition?
YES
Record time for flow switch in seconds
Were all sectional/floor control valves inspected?
YES
Number of valves
Were all sectional/floor flow switches inspected?
YES
Flow switch average times in seconds
Are all other valves in good condition?
YES
Are cold weather valves open or closed as
needed?
Antifreeze systems satisfactorily tested?
YES
Type of Antifreeze solution
537-4
YES
30
5
30
YES
Propylene glycol
Antifreeze solution tested @ [degrees]
Approximate volume
minus 21
55 gallons
at what percent
51
Are valve room heaters operating properly?
YES
Backflow tested as required?
YES
Forward flow test performed as required?
YES
Are valve rooms accessible with adequate
clearance?
YES
Was a main drain test performed with satisfactory
results?
YES
Static pressure
Size of main drain
If no main drain test was performed state
explanation
Are all other valves open or closed as required?
100 PSI
2
main drain clear
YES
Make of alarm valve
Residual pressure
90 PSI
Main drain fully open and flow observed?
YES
Gauges replaced or calibrated?
YES
Alarm valve identification
Model of alarm valve
2nd north
E1
Viking
Size of alarm valve
6
Year of alarm valve
Has internal investigation been performed in last
5 years?
YES
Date of last inspection
Alarm panel reset and clear of alarms?
YES
Was system tagged?
If Tagged what color
2008
07-04-2011
YES
Green
Wetpipe Descriptive Photos
Wet Pipe Section537-4
Page 7 of 23
Item #1
Location:
System:
Component:
Short Description:
Details:
Long Description:
Comments:
Wet Pipe Section537-4
Fire Control Area
Wetpipe
Alarm Valves
Photo of wet pipe riser
A deficiency such as leaks or damage would be noted. A regular inspection is suggested to verify that there are no leaks and
overall conditions and accessibility are in good order, more frequent inspections may be required depending on the environment
and location of such riser. Consult with your contractor for suggested inspection intervals or other maintenance requirements.
Regular inspections and house cleaning is suggested.
Pictures in this section do not depict any deficiency but do show the condition of the riser.
Page 8 of 23
Dry Pipe Section
Dry valve in service and in good condition?
YES
Make of dry valve
Dry valve identification
Model of dry valve
537-4
3rd north
F1
Viking
Size of dry valve in inches
Main drain test performed with satisfactory
results?
Residual pressure
Air pressure set at correct level?
Cut in pressure
Date of last trip test
Pressures before testing air #
Control valve fully open?
Time it took to trip [seconds]
4
YES
90 PSI
YES
30 PSI
05-04-2011
40 PSI
YES
45
Year of dry valve
Static pressure
Gauges replaced or calibrated?
2005
100 PSI
YES
Cut off pressure
40 PSI
Low air pressure switch activates at
24 PSI
Dry valve successfully trip tested and returned to
service?
Water #
Operated @ air pressure
Time for water to reach inspectors test [seconds]
YES
100 PSI
11 PSI
80
Interior of dry valve was satisfactory including all
moving parts?
YES
Trip test performed without repairs?
YES
Did alarms work during test?
YES
Quick opening devices operate properly and
reset?
YES
Make of quick opening device.
Model of quick opening device
af1
Viking
Year of quick opening device
All supervisory devices successfully tested?
Manual release devices tested?
Priming water level is normal?
Number of auxiliary drains
2007
YES
NA
YES
3
Valve reset dry?
All automatic release devices tested?
NA
Quick-opening devices successfully tested?
YES
All low points drained at fall inspection?
YES
Has an obstruction investigation been performed
in the last 10 years?
YES
NA
Date of last inspection
09-03-2011
Has piping been checked for proper slope in the
last 10 years?
Date of last inspection
01-01-2013
Is valve room adequately heated?
Dry Pipe Section537-4
YES
YES
Page 9 of 23
Are all other valves in their proper position?
YES
Alarm panels reset and clear of alarms?
Was System Tagged?
YES
Tag color?
YES
Green
Drypipe Deficiencies
Item #1
Location:
System:
Component:
Condition:
Explanation:
Impact:
Recommendation:
Dry Pipe Section537-4
Fire Control Area
Drypipe
Dry valve
No five year internal inspection.
A 5 year internal inspection of the valve along with, strainers, filters, orifices, and diaphragm chambers.
year internal inspections are required to insure the operation of the system and to check for corrosion, and obstructions, more
frequent inspections may be needed depending on the conditions of the water supply. Ref. 13.4.3.1.8
repair
Page 10 of 23
Water Tanks Section
537-4
Water temperature- low temperature alarms
tested?
YES
Heating system tested and in satisfactory
condition?
YES
Tank fill valve in satisfactory condition?
YES
Control valves in normal position?
YES
Water level alarms tested?
YES
Air pressure in tank normal?
YES
Condition of exterior of tank satisfactory?
YES
Tank support structure appears to be in good
condition?
YES
Interior of tank in satisfactory condition?
YES
YES
3 year inspections completed as required?
YES
Date of last inspection
01-06-2011
5 year inspections completed as required?
YES
Date of last inspection
01-06-2013
Was System Tagged?
YES
Catwalks and ladders in satisfactory condition?
Area around tank in satisfactory condition?
If Tagged Tag Color
Water Tanks Section537-4
NA
Green
Page 11 of 23
Foam Section
537-4
Discharge device location (Sprinkler)
at roof
Discharge device location (Spray nozzle)
under catwalk
Discharge device position (Sprinkler)
pendant
Discharge device position (Spray nozzle)
pendant
Foam concentrate strainers inspected as
required?
YES
Proportioning systems inspected as required?
YES
Pipe corrosion investigated as required?
YES
Pipe system in satisfactory condition?
YES
Storage tanks for foam supply in satisfactory
condition?
YES
Capacity of tank
600
Type of foam used in system
Number of tanks in system
2
AFFF
Foam concentrate tested and in satisfactory
condition?
YES
Actuation devices tested and in satisfactory
condition?
YES
Detection devices tested as required?
YES
5 year maintenance completed as required?
YES
Date of last 5 year maintenance
06-04-2013
10 year maintenance completed as required
YES
Date of last 10 year maintenance
06-04-2013
Was System Tagged?
YES
Foam Section537-4
Page 12 of 23
Standpipe Section
537-4
Visual inspection of entire system?
YES
There have been no modifications since the last
inspection?
YES
All systems are in service?
YES
Control valves are in the open position?
YES
Control valves are locked open or have tamper
switches?
YES
No indication of serious corrosion?
YES
Hangers and supports are secured to pipe and
building structure?
YES
FDC is accessible and unobstructed?
YES
FDC inlets are not obstructed by foreign material?
YES
FDC plugs and caps are in place?
YES
FDC swivel connections turn freely?
YES
Hose valves are operable and have caps?
YES
Are hoses in service as required?
YES
Hose in racks have been tested in last 5 years
and have adjustable nozzles?
YES
Date of last test
01-05-2011
Standpipe classification.
Number of hose racks
4
Was 5 year flow test performed as required?
YES
Wet standpipe
Date of last flow test inspection
06-04-2013
Was 5 year hydrostatic test performed as
required
YES
Date of last hydrostatic test inspection
06-04-2013
Was system tagged?
YES
If tagged what color
Green
Standpipe Descriptive Photos
Item #1
Location:
System:
Component:
Short Description:
Details:
Long Description:
Comments:
Standpipe Section537-4
2nd Floor
Standpipe
Condition of the hose valves
Photo of hose valves
A deficiency such as leakage or missing caps would be noted. Regular inspections and testing are suggested, consult your
contractor for further information, depending on the environmental conditions the stand pipe is located more frequent inspections
may be required. Inspect hose cabinets and hoses frequently.
Inspect regularly for missing hose valve caps and obstructions.
Pictures in this section do not depict any deficiency but do show the conditions of the stand pipe system.
Page 13 of 23
Pump Section
Pump Manufacturer
537-4
Type of pump
horizontal
Serial number
5555
Model number
ccc
750
Rated pressure
65
Aurora
Pump Label
Rated volume
Rated rpm
Pump Section537-4
1725
Driver
Diesel
Page 14 of 23
Driver Serial number
Driver Rated horse power
5555
150
Driver Model number
Driver Rated speed
GGGG
1725
If electric motor: Driver rated voltage
0
Driver Operating voltage
0
Rated amps
0
Phase cycles
0
Controller: manufacturer
Model number
Pump Section537-4
Firetrol
Controller Serial number
9999
UUUUU
Page 15 of 23
Controller Label
Jockey pump on system?
Off pressure
Pump Section537-4
YES
JOCKEY PUMP settings: on pressure
150 PSI
165 PSI
Page 16 of 23
Jockey Label
Pump Section537-4
Page 17 of 23
Flow Test
100
October 22, 2013
Theoretical
90
PRESSURE - PSI
80
70
60
50
40
0
100
200
300
400
500
600
700
800
900
1000
1100
RATED FLOW
FLOW TEST
DRIVER SPEED/RPM
SUCTION
DISCHARGE
Churn
1725
80
155
100%
1725
70
140
150%
1725
60
125
Pump Section537-4
Page 18 of 23
FOR ELECTRIC DRIVEN FIRE PUMPS RECORD VOLTAGE AND AMPS
Voltage
Amps
Churn
0
0
0
0
0
0
100%
0
0
0
0
0
0
150%
0
0
0
0
0
0
Flow test completed with the use of # of pitot tubes
3
Flow Meter is functional
Pitot pressure used to measure flow
21 PSI
Main drain test static
Residual presure
90 PSI
Time for supply to reach normal pressure
NA
100 PSI
5
Adequate drainage provided before flow testing?
YES
Pump suction and discharge pressures and flow
measurements at each hose stream used to
determine total pump output where hose streams
used in testing?
YES
Care taken to prevent water damage by verifying
adequate drainage?
YES
Flow test conducted under minimum, rated and
peak fire pump flows?
YES
Flow test conducted by controlling quantity of water
discharged through test devices?
YES
Fire pump operated at maximum allowable
discharge?
YES
Fire pump suction supply provided required flow at
0 pressure or higher gauge pressure at pump
suction flange?
YES
Electric fire pump driver did not overload beyond
rating while delivering necessary brake
horsepower?
YES
Pump suction and discharge pressures and flowmeter measurements used to determine total pump
output where flow meter used in testing?
YES
Flow meter adjusted immediately prior to testing in
accordance with mfg. instructions?
YES
Test results using flow meter consistent with
previous annual test results (IF no, complete flow
test using hose streams OR calibrate flow meter)
YES
Pump Section537-4
Page 19 of 23
While Pump Is Running
At churn, circulation relief valve checked for
operation and water discharge?
YES
At churn, pressure relief valve checked for proper
operation?
YES
At churn, pressure control valve checked for proper
operation?
YES
At churn, test continued for minimum of [Minutes]
30
At each flow condition, electric motor voltage and
current in all lines recorded?
NA
At each flow condition, pump speed recorded?
YES
At each flow condition, simultaneous readings of
pump suction and discharge pressures and pump
discharge flow recorded?
YES
Pressure relief valve closely observed during each
flow condition?
YES
Pressure control valve closely observed during
each flow condition?
YES
Pressure relief valve functioning properly?
YES
Pressure control valve functioning properly?
YES
Pressure relief valve reset to normal position at
pump test conclusion?
YES
Pump Section537-4
Page 20 of 23
Check List
System in service on arrival?
YES
Responsible parties notified before testing?
YES
Control valves in normally open or normally closed
position?
YES
Control valves properly locked or supervised?
YES
Control valve supervisory switches initiate signal
properly?
YES
Signal restored only when valve returned to normal
position?
YES
Operating stems of OS&Y valves lubricated?
YES
Control valves operated through full range and
returned to normal position?
YES
Control valves are free from external leaks?
YES
Control valve identification signs in place?
YES
Battery systems in satisfactory condition?
YES
Battery system charger and charge rate
operational, normal and equalized?
YES
Circuit breakers or fuses checked?
YES
Isolating switch exercised?
Circuit breakers exercised?
NA
NA
crankcase breather inspected and in good
condition?
YES
Engine exhaust system inspected and in
satisfactory condition?
YES
Electrical wiring subject to movement free from
chafing?
YES
Strainer, filter or dirt leg (or combination thereof)
cleaned?
YES
Crankcase breather cleaned or changed (as
necessary)?
YES
Water strainer cleaned?
YES
Manual starting means of electrically driven pumps
operated?
YES
Antifreeze protection level tested and adjusted as
necessary?
YES
Electrical system safety devices and alarms
operated?
YES
Electrical system boxes, panels and cabinets
cleaned ?
YES
Hangers and seismic bracing appear undamaged
and tightly attached?
YES
Piping appears free of mechanical damage and in
satisfactory condition?
YES
Building is secure such as not to expose piping to
freezing conditions?
YES
Adequate heat is provided maintaining temp at
40°F / 4.4°C or higher?
YES
Pump shaft end play with specified tolerances?
YES
Pressure gauge and sensor accuracy verified to be
within 5%?
YES
Pump coupling alignment within specified
tolerances?
YES
Electrical connections tightened as necessary?
YES
Mechanical moving parts lubrication verified?
YES
Pressure switch setting calibration verified?
YES
Fuel tank vents and overflow piping free from
obstructions?
YES
Fuel piping in good condition?
YES
Combustion air ductwork and louvers in good
condition?
YES
Pump Section537-4
Page 21 of 23
Electrical control and power wiring connections
checked for tightness?
YES
pump bearing lubricated?
Gauges recalibrated or changed?
YES
Wet pit suction screens checked (cleaned as
necessary) after every operation?
NA
Mechanical transmission right-angle gear drive
lubricated?
NA
Mechanical transmission coupling lubricated?
NA
YES
Electric drive motor bearings lubricated?
YES
Diesel engine maintenance schedule up to date as
required?
YES
Diesel engine cooling system antifreeze checked?
YES
Electrical system circuit breakers or fuses changed
(every 2 years)?
NA
Pump Section537-4
Page 22 of 23
Transfer Switch
Power failure condition simulated while pump
operating at peak load?
NA
Transfer switch transfer of power to alternate power
source verified?
NA
Pump maintenance of peak load performance
verified?
NA
Power failure condition removed?
NA
Pump reconnected to normal power source after a
time delay?
NA
Extinguishers Section
Total number of extinguishers inspected.
22
537-4
Are all extinguishers visible?
YES
Are all extinguishers accessible?
YES
Are all extinguishers in good condition?
YES
Are extinguisher cabinets in good condition?
YES
Are all pressure gauges and pull pins in good
condition?
YES
Are all extinguishers of the proper class?
YES
Do extinguishers cover the proper square footage
for the hazard protected?
YES
Are all extinguisher labels in place?
YES
Have all maintenance intervals been performed?
YES
Date of last maintenance interval
01-02-2013
6 year maintenance
01-02-2013
12 year hydro test
01-02-2013
5 year hydro test
01-02-2013
Are all hoses and nozzles in good condition?
Extinguishers Section537-4
YES
Was system tagged?
YES
Page 23 of 23
Related documents
Download