2:
5:
SYS19: BASE2
50:
95:
98:
JOB: CH62318A-0130-1 Name: 4F-50
4F
100:
DATE: JUL 19 2002
Time: 8:59:56 AM Operator: CP COLOR: CMYK
Condulet Conduit Outlet Boxes
With Covers for Threaded Rigid and IMC
Application:
GUA series conduit outlet boxes
are installed within hazardous
area conduit systems to:
ɀ protect conductors in threaded
rigid conduit
ɀ act as pull and splice boxes
ɀ connect lengths of conduit
ɀ change conduit direction
ɀ provide access to conductors
for maintenance and future
system changes
ɀ act as mounting outlets for
fixtures (with appropriate covers)
ɀ act as sealing fittings (with
appropriate covers)
Features:
GUA conduit boxes have:
ɀ Neoprene ‘‘O’’ ring standard to
meet NEMA 4 requirements
ɀ Cast brackets on cover to
permit easy removal and
tightening
ɀ Internal green ground screw
ɀ Four standard mounting pads
except for boxes with bottom
hubs
ɀ threaded cover openings
ɀ ten different hub arrangements
ɀ taper threaded hubs to provide
grounding continuity
ɀ smooth integral hub bushing
protects conductor insulation
when pulling
ɀ surface covers furnished with
boxes
ɀ sealing covers, dome covers,
and fixture hanger covers are
available.
ɀ cover threads are 12 pitch.
Standard Materials:
ɀ Bodies – Feraloy iron alloy
ɀ Covers – Copper-free
aluminum
Standard Finishes:
ɀ Feraloy iron alloy –
electrogalvanized and aluminum
acrylic paint
ɀ Aluminum – natural
Options:
Cl. I, Div. 1 & 2, Groups C,D
Cl. II, Div. 1, Groups E,F,G
Cl. II, Div. 2, Groups F,G
Cl. III
NEMA 3,4,7CD,9EFG
Bodies – copper-free
aluminum . . . . . . . . . . . . . . . SA †*
Covers – Feraloy
iron alloy – electrogalvanized
and aluminum acrylic
paint . . . . . . . . . . . . . . . . . . . . WOD
Corro-free epoxy
powder coat . . . . . . . . . . . . . S752
To order box less cover add ⍯0⍯
to end of catalog number
ie.GUAT260.
Certifications and
Compliances:
ɀ NEC/CEC:
Class I, Division 1 & 2, Groups
C,D
Class II, Division 1, Groups E,F,G
Class II, Division 2, Groups F,G
Class III
ɀ UL Standard: 886
ɀ ANSI Standard: C33.27
ɀ CSA Standard: C22.2 No. 30
ɀ NEMA/EEMAC 3,4
NOTE: When assembled with
sealing type cover, GUA series
outlet boxes provide adequate
sealing for 40% fill in hazardous
areas – Class I, Groups C,D;
Class II, Groups E,F,G; and
Class III. Seals can be made in
either horizontal or vertical
positions. Use Chico ‘‘A’’
sealing compound only.
Conductor splices or
connections must not be made
in enclosures where sealing
compound is to be used per
NEC.
Dimensions
GUA
Hub
Size
1⁄2
3⁄4
1⁄2
3⁄4
1
11⁄4
11⁄2
GUAB
Hub
Size
1⁄2
3⁄4
1⁄2
3⁄4
1
11⁄4
11⁄2
2
Cover
Opening
Dia.
2
2
3
3
3
35⁄8
5
Cover
Opening
Dia.
2
2
3
3
3
35⁄8
5
5
All others
Size Ranges:
STIBOINFO((CRH:MAIN:4F:50))
CH0 0 4 F - 2
GUAC
Cat. #
GUA14
GUA24
GUA16
GUA26*
GUA36
GUA47
GUA59
Hub
Size
1⁄2
3⁄4
1⁄2
3⁄4
1
11⁄4
11⁄4
11⁄2
2
GUAD
Cat. #
GUAB14†
GUAB24
GUAB16*
GUAB26*
GUAB36*
GUAB47†
GUAB59*
GUAB69*
Hub
Size
1⁄2
3⁄4
1⁄2
3⁄4
1
11⁄4
Length of Hub
Hub Size
1⁄2-3⁄4
1-11⁄4
11⁄2-2
Cat. #
14
24
16
26
36
37
47
49
59
69
† Available in copper-free aluminum, add
suffix -SA.
* Available in copper-free aluminum, add
suffix -SA. GUA outlet boxes marked with *
when ordered with suffix -SA are suitable for
Class I, Division 1 & 2, Groups B, C and D,
Class II, Division 1, Groups E, F, G and
Class III. Covers have 16 pitch threads.
Replacement cover is a GUA06-GB.
PDFINFO
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Cover
Opening
Dia.
2
2
3
3
3
35⁄8
5
5
5
Cat. #
GUAC14†
GUAC24†
GUAC16*
GUAC26*
GUAC36*
GUAC47†
GUAC49
GUAC59*
GUAC69*
Cover
Opening
Dia.
2
2
3
3
3
5
Cat. #
GUAD14†
GUAD24
GUAD16
GUAD26†
GUAD36†
GUAD49
Dimension ‘‘e’’
Length
7⁄8
1
11⁄16
GUA, GUAD, GUAM, GUAW,
GUAX
ɀ Hub – 1⁄2⍯ to 2⍯
ɀ Cover opening – 2⍯ to 5⍯ dia.
50
Typedriver Name: TS name csm no.: 100
Suffix to be
Added to
Cat. #
Description
GUAB Only
TCP: 15001
Copyright 2002 Cooper Industries, Inc.
a
21⁄2
21⁄2
31⁄2
31⁄2
31⁄2
41⁄4
41⁄4
53⁄4
53⁄4
53⁄4
b
113⁄16
2
2
2
25⁄16
25⁄16
211⁄16
313⁄16
313⁄16
41⁄16
c
13⁄4
2
17⁄8
17⁄8
23⁄16
23⁄8
23⁄4
33⁄4
33⁄4
4
d
5⁄8
3⁄4
5⁄8
3⁄4
7⁄8
7⁄8
13⁄32
13⁄32
19⁄32