Minneapolis Public Schools Sanford Middle School Expansion & Renovations October 28, 2014 SECTION 262813 - FUSES PART 1 GENERAL 1.01 SCOPE A. Work under this section includes the furnishing of all fuses for all HVAC and electrical equipment. 1.02 RELATED SECTIONS A. Section 260500 - General Requirements B. Section 262413 - Switchboards C. Section 262418 - Equipment Connections D. Section 262812 - Enclosed Switches and Circuit Breakers E. Section 262913 - Enclosed Controllers F. Section 262914 – Variable Frequency Drive – motor controllers 1.03 SUBMITTALS A. Submit shop drawings and product data in accordance with Division 1. B. Submit time current curves for all fuses being supplied as part of this project. PART 2 PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Fuses - Bussmann/McGraw Edison, Brush, Mersen (formerly Ferraz-Shawmut) or Littelfuse. 2.02 FUSES A. Furnish and install secondary fuses in all fusible equipment sized as shown on the drawings. B. All fuses shall be current limiting non-renewable type with 200,000 ampere AIC interrupting capacity and shall not be shipped installed in fusible equipment. C. Fuses shall be by the same manufacturer of the types specified below. Bussmann fuse references are listed to establish type and quality. © LKPB 2014 201402000 FUSES 262813 - 1 Minneapolis Public Schools Sanford Middle School Expansion & Renovations D. October 28, 2014 Fuses 600 amperes and less shall be U.L. Class R rejection type or J type fuses. Time Delay Class RK-1 Bussmann Low-Peak LPS-RK-600V LPN-RK-250V E. Low –Peak LPJ-SP-600V Fuses over 600 amperes shall be UL Class L (with pure silver links only). Time Delay Class L Bussmann Hi-Cap KRP-C F. Apply specific fuses as follows: Panel Feeders - Low-Peak Motors - Low-Peak Equipment - Low-Peak Special Use Non-Motor - (Class L) G. Provide a minimum of three additional spare fuses of the type, size, and rating for each set installed. H. Provide a fuse cabinet for storing spare fuses and puller. Provide an insulating type universal fuse puller. Fuse cabinet shall contain hinged and latched front cover, be designed for surface mounting, and be made of code gauge steel, Bussmann #SFC, Littelfuse #LSFC, or Square D #TC-36356B box and #TC-36356TS cover. Locate panel as directed by Owner or as located on drawings. PART 3 EXECUTION 3.01 FUSES A. The size, voltage and fuse type furnished for each device shall be indicated inside the cover of that device with pressure sensitive tape. B. Spare fuses shall be turned over to the Owner. C. Install spare fuse cabinet adjacent to main switchboard or where shown on drawings. Label cabinet as "FUSE CABINET" per instructions contained in Section 260553. Verify location with Owner. D. Spare fuses shall be placed in the fuse cabinet in their original shipping containers. END OF SECTION 262813 © LKPB 2014 201402000 FUSES 262813 - 2