D R I V E S & S W I T C H G E A R his article discusses the application of fuse technology in low voltage distribution and motor control circuits. The effects of short circuit current on electrical equipment can be dramatic if no appropriate protection is provided. T Is fuse technology in electrical installations alive or blown? Some of the effects include: Melting of conductors or busbars; Vaporization of metal; Ionization of gases; Arcing, fire and explosion; Insulation damage. Apart from being hazardous to personnel, significant economic losses can result from downtime and the repairs required to restore damaged equipment. These downtimes can be very significant depending on the installation concerned. In some cases they can cause production stops for a long period. If we look at the thermal stress in switchgear, we can say that this is not a major issue due to the short period of a short circuit. This short period would not probably increase the temperature of bus-bar systems above 200 °C, which does not create much damage on the busbar system. However the dynamic stresses are far more important. This stress causes vibrations, magnetic effects, etc. which stretch the busbars and supports in different directions and could potentially cause another massive short of the busbar systems. This is why the highest short circuit peak current needs to be considered when calculating effects of dynamic stress. According to IEC 60364, each circuit needs to be provided with over-current protection (over-load and short circuit), which breaks the over-current of the circuit before it causes danger due to by Hakan Bergqvist, ABB Oy, Finland temperature and mechanical effects. These protective devices can be of the following types: Protection against both overload and short-circuits Only short circuit protection Only overload protection Complete protection by fuse technology The current-limiting fuse provides complete protection against the effects of over-currents (over 5. Indicator wire loads and short circuits), by 1. Blade contact protecting both electric circuits 2. Fuse-element 6. M-effect material and their components. The fuse 3. Fuse body 7. Quartz sand technology offers a combination 8. Indicator of exceptional features, such 4. Endplate (with gripping lug) as high breaking capacity: a Fig. 1: Typical LV fuse link. fuse has a breaking capacity of minimum 50 kA, and normally the industrial fuses available on the market not consist of any moving parts to wear today have a breaking capacity >100 out or become contaminated by dust, oil kA. Thanks to this high breaking capacity or corrosion. Fuse replacement ensures there is no need for complex short-circuit protection is restored to its original state calculations to design the electrical of integrity. This increases the reliability system. Also, the breaking capacity of the protection for the electrical allows an easy and inexpensive system expansion involving increased fault installation. currents in the electrical installation. Fuse technology is very compact in design, which offers low cost Unlike other short-circuit protective over- current protection at high devices (SCPD), fuses cannot be reset, short-circuit levels. This can easily thus forcing the user to identify and be seen in motor protection (type correct the over-current condition before 2 coordination) according to re-energizing the circuit. The fuse does May 2005 - Vector - Page 27 Fuse type Rated voltage Maximum operational voltage gG, gM, aM, 230V 253V aR, gR, gS 400V 500V 690V Fuse type Application Breaking range Gg General purpose mainly for conductor protection Full range gL, gF, gl, gll Former type of fuse for conductor protection (replaced by gG type) Full range 440V aM Motor circuit protection Full range 550V aM Short-circiut protection of motor circuits Partial range (back up) 725V aR Semiconductor protection Partial range (back up) gR, gS Full range Table 1. Table 2. IEC 60947-4-1. By limiting the shortcircuit energy and peak currents to extremely low levels, other equipment can be used to its maximum rating, and therefore the complete switchgear will be more compact and cost effective. To this can be added that the fuse is completely safe in operation. There is no emission of gas, flames, arcs or other materials when the fuse is clearing the highest levels of short-circuit currents. In addition, the speed of operation at high short-circuit currents significantly limits the arc flash hazard at the fault location. This will also reduce the total space necessary for the equipment. Fuse-links are standardised according to IEC 60269, which ensures availability of replacements with standardized characteristics throughout the world. Standardized fuse characteristics and a high degree of current limitation ensure effective coordination between fuses and other devices. Design and different fuse types The design of typical low voltage fuselinks for industrial application is shown in Fig.1 and consists of different elements. The main elements are the internal fuse element, the blade contacts and the fuse body. Such fuse-links are commonly called current-limiting or high breaking capacity fuse-links. The most common fuses are DIN, BS, NFC and UL. DIN types are widely used in Europe and German influenced countries. The BS types are used widely in UK, Australia and other UK influenced countries. The NFC type of fuse is used in France & North Africa, due to its French origin. UL types of fuses are used in North America, but can also be found in other parts of the world where there are requirements for fuses according to UL standards. Fuse markings All fuses are marked with two letters that describe the characteristics of the fuse. Fuses for both overload and short circuit protection or “Full range” means that the fuse can break any current able to melt the fuse-element up to the rated breaking capacity. These have the first letter “g”. Full range fuses can be used as stand-alone protection devices. Fuses for only short circuit protection or partial range, or back-up fuses, are designed to interrupt short-circuit currents only. These have the first letter “a”. They are generally used to increase the breaking capacity of other overcurrent protection devices. The second letter expresses the main application for the fuse: “G” for cable protection, “M” for motor protection, and “R” for semiconductor protection. Fuse operation total operation phase of the fuse. The rapid current limitation minimises the stresses caused by the short-circuit and therefore there is no need for over dimensioning of other devices e.g. in motor starters. Fuse selection Fuse selection needs to consider the equipment to be protected and the power supply that has to be interrupted. Fuse selection for a specific application involves consideration of the time-current characteristics and the breaking range. The time-current characteristics determine the field of application, while the breaking range indicates whether fuses are to be used together with additional over-current protection devices: g - Both overload and short circuit protection “Full range” means that the fuse can break any current able to melt the fuse-element up to the rated breaking capacity. Full range fuses can be used as stand-alone protection devices. a - Only short circuit protection “Partial range”, or back-up fuses, are designed to interrupt short-circuit currents only. They are generally used to increase the breaking capacity of other over- current protection devices. The maximum operational voltage of the fuses is presented in Table 1: The intended applications for the fuses are presented in Table 2: During a short-circuit, the restrictions in the fuse element melt simultaneously forming a series of arcs equal to the number of restrictions in the fuse element. The resulting arc voltage ensures rapid current limitation and forces the fault current to zero. The fuse operation occurs in two stages. The first is called the pre-arcing stage. This is the heating of the restrictions to the melting point and vaporization of the material. The second stage is the arcing stage, where the arc begins and is then extinguished by the filler (usually quartz Fig. 2: The co-ordination between the sand). Both stages together make up the different devices in the motor starter. May 2005 - Vector - Page 28 Fuse selection for cable protection The rated current In of the fuse-link is selected to: IB ≤ In ≤Iz Fuse-links of type gG are able to break over-currents in the conductors before such currents can cause a temperature rise detrimental to insulation. The fuselink selection can be easily made, taking the following steps: The maximum operational voltage of the fuse-link is selected to be greater or equal to the maximum system voltage. The operational current IB of the circuit is calculated. T h e c o n t i n u o u s c u r r e n tcarrying capacity of the conductor I z is selected from IEC 60364-5-52. Fuse selection for motor protection According to the standard IEC 947-41, the co-ordination classes for motor protection are: Type 1: where the contactor or starter should not cause harm to personnel, and after the short circuit, a repair or change of the components must be done to achieve full integrity again. Type 2: where the contactor or starter should not cause harm for personnel or the equipment, and after the short circuit, full integrity of components should be available again. Possible contact welding should be considered and manufacturer must inform necessary maintenance procedure. This means that Type 1 co-ordination allows the contactor and thermal overload relay to be damaged by the short circuit. It is the responsibility of the end-user to inspect the starter after the short, and to replace damaged components. If inspection is not done, the circuit is potentially damaged and without overload protection. This has the potential to destroy the motor. The Type 2 co-ordination guarantees functionality of starter components even after the short circuit. This means that the overload protection is functional after the short circuit and will protect the motor from overload. To assure the co-ordination between the different components in the motor starter, each manufacturer publishes co-ordination tables. Their tables are based on tests between the different components. Selectivity or discrimination Discrimination of protective devices is a major point to be considered when designing low voltage installations. The aim of discrimination is to minimize the effects of a fault. Only the faulted circuit shall be disconnected while the others shall remain in service. The discrimination is achieved if a fault is cleared by the protective device situated immediately upstream of the fault without operation of other protective devices. The essential tools to investigate discrimination between protective devices are the time-current characteristics and I2t values. Discrimination between fuses The discrimination between fuselinks is verified by means of the timecurrent characteristics for operating times ≥ 0,1 s and the pre-arcing and operating I2t values for operating times < 0,1 s. These verifications are made by examination of the time-current characteristics, and I2t values shall be met to achieve total discrimination between fuses. Fuses according to IEC 60269-2-1 of the same type, with rated currents ≥ 16 A, meet these total discrimination requirements by definition if the ratio of rated currents is 1,6:1 or higher. No additional verification by the user is therefore needed. Discrimination of circuit breakers upstream of a fuse The discrimination is verified by using time-current characteristics and I2t values. May 2005 - Vector - Page 30 Verification of discrimination for operating time ≥ 0,1 s: the maximum operating time of the fuse shall be lower than the minimum unlatching time of the circuit breaker. Verification of discrimination for operating time < 0,1 s: the discrimination may be determined using the I2t values Verification of total discrimination: the requirements of both shall be fulfilled to obtain total discrimination. In practice, circuit-breaker manufacturers give discrimination tables between circuit breakers and selected fuses. Discrimination of a fuse upstream of circuit breaker The discrimination is verified by using time-current characteristics and I2t values of the fuse. Verification of discrimination for operating time < 0,1 s: the discrimination may be determined using the I2t values. The maximum operating I2t values of the circuit breaker shall be lower than the minimum pre-arcing I2t values of the fuse. Contact Andre van der Elst, Electromechanica, Tel (011) 249-5000, andre@em.co.za ∆ May 2005 - Vector - Page 31