Building Act 2000 Director’s Specified List 1 October 2014 Building Standards and Occupational Licensing Department of Justice Revised by the Director of Building Control – 1 October 2014 Revised to update Schedule 1, expansion of site and soil report and Design Report in Schedule 2 and other minor editorial amendments as at 1 October 2014 (details of amendments in Schedule 9). Contents Documents and time periods specified for certain applications or actions: Building Act 2000 Building Regulations 2014 Plumbing Regulations 2014 Schedules: 1. 2. 3. Designer’s documentation for application for Certificate of Likely Compliance Documents for a Plumbing Permit application (Parts 1- 4) Documents in relation to a Certificate of Plumbing Compliance Maintenance Schedules – Prescribed Features and Measures (frequency of testing or inspection) 4. 5. 6. Essential Safety and Health Features Essential Safety and Health Measures Other Prescribed Features or Measures 7. 8. 9. 10. Function Control Authorities list Reporting Authorities list List of amendments of this Specified List since last revision History of amendments of the Director’s Specified List. 2 Director’s Specified List / Building Act 2000 /Version: October 2014 The Building Act 2000 requires a number of matters to be specified by the Director of Building Control. The following is a list of those matters. Section of Act Matter required to be specified 3 The Function Control Authorities determined by the Director of Building Control. The period in which the Director of Building Control has to inform an Accredited Building Practitioner of a complaint received. Documents a building surveyor is to forward to the relevant permit authority after resignation from their engagement. 33(1)(a) 53A(3) 60(2)(b) 62 63(2) 64(1) 64(2) 67(1) The period in which a building surveyor is to notify the permit authority that building work is a minor alteration or a minor repair. Matters or documents to be included for an application for a Certificate of Likely Compliance. The period in which a Reporting Authority has to supply the required report to a Building Surveyor. The period in which a Building Surveyor has to forward documents to a Function Control Authority. The period in which a Function Control Authority has to notify the Building Surveyor. The period in which a Building Surveyor has to grant a Certificate of Likely Compliance. Specified requirement Refer to Schedule 7 Within 7 days of receiving complaint. The Certificate of Likely Compliance Any variation to a Certificate of Likely Compliance or building permit consented to by the building surveyor or permit authority under s.87 All documentation accepted by the building surveyor including alternative solutions All Certificates of the responsible designers (Building Work) (Approved Form 35A) All Certificates of Specialists or Other Persons (Form 55) Start work notification and authorisation Inspection notifications from the builder at each mandatory notification stage Building surveyor’s mandatory notification records Inspection reports or reasons for non-inspection under regulation 31 Inspection reports or file notes Inspection Directions unresolved at the date of resignation Any other documents relied on by the building surveyor during construction. Within 2 working days of forming the opinion The documents (if required) referred to in Schedule 1 Relevant permits or approvals required under other legislation Certificates of the responsible designers – building work (Approved Form 35A) Any determination made by the Appeal Tribunal under section 218 or 218A Alternative solution proposal and verification Any other documents relied on by a designer Within 14 days of receiving the request for the required report or a period agreed between the Building Surveyor and the Reporting Authority. Within 2 working days of receiving the application. Within 14 days of receiving the documents. Within 21 days of receiving the request for a certificate or a period agreed between the Applicant and the Building Surveyor 3 Director’s Specified List / Building Act 2000 /Version: October 2014 Section of Act 70(1)(b) 70(2) 72(1) 73(2) 80(1)(b) 80(2) 82(1) 83(2) 87(1) 87(9) Matter required to be specified The documents required to accompany an application for a Building Permit. The period in which an Applicant has to provide documents or amend an application. The period in which a Permit Authority has to grant an application for a Building Permit. The period in which a Permit Authority has to refuse an application for a Building Permit. The documents required to accompany an application for a Plumbing Permit and Special Plumbing Permit. The period in which an Applicant has to provide documents or amend an application for a Plumbing Permit and Special Plumbing Permit. The period in which a Permit Authority has to grant an application for a Plumbing Permit and Special Plumbing Permit. The period in which a Permit Authority has to refuse an application for a Plumbing Permit and Special Plumbing Permit. The period in which building work or plumbing work is to be started. Period in which a building surveyor is to provide to the permit authority in writing details of the builder’s start work notification and the building surveyor’s authorisation to start work. Specified requirement Certificate of Title, Schedule and Plan; Site plans (if and as required for a CLC by the Building Surveyor – e.g. may not be required for internal work in existing buildings); Architectural Plans Certificates of the responsible designers (Building Work) (Approved Form 35A) Outline Plan and procedure of demolition works if applicable Details of proposed work for the protection of persons or property Certificate of Likely Compliance All documents referred to on the Certificate of Likely Compliance All certificates and reports relied on by the designer and the building surveyor Evidence of the contract price of the building work, or if there is no contract, an estimate of the total cost of the building work provided by the relevant building surveyor A certificate for certifiable work (building) if required under the Water and Sewerage Industry Act 2008 The documents (if required) referred to in Schedule 2 Within 7 days of receiving the request or a period agreed between the Applicant and the Permit Authority. Within 7 days of receiving the application or a period agreed between the Applicant and the Permit Authority. Note: Further time may apply if a permit for plumbing work is required. Within 7 days of receiving the application or a period agreed between the Applicant and the Permit Authority. A certificate for certifiable work (plumbing) if required under the Water and Sewerage Industry Act 2008 Certificates of the responsible designers – plumbing work (Approved Form 35B) Any determination made by the Appeal Tribunal under section 218 or 218A The documents (if required) referred to in Schedule 2 Within 7 days of receiving the request or a period agreed between the Applicant and the Permit Authority. Within 14 days of receiving the application or a period agreed between the Applicant and the Permit Authority. Within 14 days of receiving the application or a period agreed between the Applicant and the Permit Authority. Within 12 months after the date of issue of the Building Permit or Plumbing Permit Within 2 working days of the issue of the authorisation to start work 4 Director’s Specified List / Building Act 2000 /Version: October 2014 Section of Act 88(1)(a) Matter required to be specified The period in which a builder is to notify the Building Surveyor before completion of each mandatory stage of the building work. Specified requirement Not less than 2 working days before completion of the stage of building work or such other period agreed between the Building Surveyor and the Builder. 88(2)(a) The period in which a plumber is to notify the Permit Authority before completion of each mandatory stage of the plumbing work. The period in which a Building Surveyor may inspect. The period in which a Permit Authority may inspect. Not less than 2 working days before completion of the stage of plumbing work. Period in which a permit authority is to inspect or cause to be inspected plumbing work. The period in which an oral direction must be confirmed in writing. The period an Applicant has to provide documents or amend an application. Within 2 working days of being notified that a mandatory notification stage is to be completed. Within 2 working days of giving the oral direction. 89(1) 89(3) 89(3A) 91(4) 95(2) 96(2) The period a Reporting Authority has to supply the required report to a Building Surveyor 98(1) The period in which the Building Surveyor has to grant an application for an Occupancy Permit The period in which a Building Surveyor has to refuse an application for an Occupancy Permit. The period in which a Building Surveyor has to notify the Permit Authority of the issue of an Occupancy Permit. The specified documents required to accompany an application for a Temporary Occupancy Permit. Period in which a building surveyor is to notify the reporting authority in writing of the issue of an occupancy permit. The period in which the General Manager has to notify the refusal to grant a Temporary Occupancy Permit. The period in which building work has to be completed. 99(2) 102 107 102(2) 110(2) 112(1) 112(2) 112(7)(a) 112(7)(b) 112(9) 113(1) The period in which an owner or agent has to obtain (apply for) a Certificate of Completion (Building Works). Period in which a permit authority is to request the advice of the relevant building surveyor regarding incomplete building work. Period in which a building surveyor is to provide advice to the permit authority regarding incomplete building works Period in which a permit authority is to provide a copy of any conditions for extension of a building permit The period in which plumbing work has to be completed. Within 1 working day after the completion of the stage of building work. Within 1 working day after the completion of the stage of plumbing work. Within 7 days of receiving the request or a period agreed between the Applicant and the Building Surveyor Within 14 days of receiving the request for the required report or a period agreed between the Building Surveyor and the Reporting Authority. Within 21 days of receiving the application. Within 21 days of receiving the application. Within 2 working days of issuing the Occupancy Permit. The Director of Building Control has not specified any documents. Within 2 working days of the issue of the permit Within 21 days of receiving a request for the Permit or a period agreed between the Applicant and the General Manager. Within 24 months after the date of issue of the Building Permit or a period agreed between the Applicant and the Permit Authority Within 14 days of receiving a Certificate of Final Inspection – note, where applicable, a certificate of completion (plumbing work) must also be obtained. Within 7 working days of an application for extension of a building permit Within 7 working days of receiving a request for advice Within 7 working days of issuing the extended permit Within 24 months after the date of issue of the Plumbing Permit or a period agreed between the Applicant and the Permit Authority 5 Director’s Specified List / Building Act 2000 /Version: October 2014 Section of Act 113(2) Matter required to be specified The period in which an owner or agent has to obtain (apply for) a Certificate of Completion (Plumbing Works). The documents required to accompany a Certificate of Plumbing Compliance. The period in which an Adjoining Owner has to reply to a notice from an Owner. Specified requirement Within 14 days of completion of the plumbing works. The period in which an Owner has to provide completed drawings and specifications. The period in which the Building Surveyor has to give a copy of drawings and specification to the Permit Authority. The period a person has to consent to a notice under Division 3 of Part 9. Within 14 days of completion of the protection work. 162(3) The matters an Emergency Order is to contain. 163(3) The period in which an owner is required to show cause in relation to a Building Notice. 164(3) The period in which an owner is required to show cause in relation to a Plumbing Notice. The Director of Building Control has not specified any other matters. Within 1 working day of receiving a Building Notice issued under section 163(1)(a), or in any other case, within 14 days of receiving the Building Notice. Within 1 working day of receiving a Plumbing Notice issued under section 164(1), or in any other case, within 14 days of receiving the Plumbing Notice. Within 14 days of receiving a Fire Upgrading Notice. 113(6) 124(1) 135(1) 135(2) 143 166(2)(c) 166(2)(d) 167(2)(a) 174 176(1) The period in which representations may be made in relation to a Fire Upgrading Report. The matters a Fire Upgrading Report are to contain. The period in which an owner is required to show cause in relation to a Fire Upgrade Notice. The period a person who serves a Building or Plumbing Order has to provide a copy to a Permit Authority. The period a Building Surveyor has to grant an application for a Certificate to Proceed. The documents referred to in Schedule 3. Within 21 days of receiving a notice from an Owner. Within 7 days of receiving the drawings and specification from the Owner. Within 6 weeks in accordance with s141(1) or within 10 days of receiving a notice under s142(1). The Director of Building Control has not specified any other matters. Within 14 days of receiving the Fire Upgrading Notice. Within 2 working of serving the Order. Within 21 days of receiving the request for a certificate or a period agreed between the applicant and the Building Surveyor. 6 Director’s Specified List / Building Act 2000 /Version: October 2014 Section of Act 178(2)(b) Matter required to be specified The documents that accompany an application. 178(3) The period in which an applicant has to provide documents or amend an application. The period a Permit Authority has to grant an application for a Permit to Proceed. 180 183(1) 183(2)(b) 183(3) 184(1) 186(1) The period an Owner has to apply for a Certificate of Substantial Compliance. The documents that accompany an application for a Certificate of Substantial Compliance. The period in which an applicant has to provide documents or amend an application. The period a Building Surveyor has to grant an application for a Certificate of Substantial Compliance. The period an Owner has to apply for a Permit of Substantial Compliance. Specified requirement Certificate of Title, Schedule and Plan; Site plans (if and as required by Building Surveyor for a Certificate to Proceed – e.g. for internal work in existing buildings); Architectural Plans Certificates of the Responsible Designers (Building Work) (Approved Form 35A) Outline Plan and procedure of demolition works w/a Details of proposed work for the protection of persons or property Certificate to Proceed All documents referred to on the Certificate to Proceed All certificates and reports relied on by the designer and the building surveyor Evidence of the contract price of the building work, or if there is no contract, an estimate of the total cost of the building work provided by the relevant building surveyor A certificate for certifiable work (building) if required under the Water and Sewerage Industry Act 2008 The documents (if required) referred to in Schedule 2 A Certificate of Others – Plumbing Work – Substantial Compliance (Approved Form 59) Within 21 days of receiving the request or a period agreed between the Applicant and the Permit Authority. Within 7 days of receiving the application or a period agreed between the Applicant and the Permit Authority. Within 28 days of the issue of the Building Order or a period agreed between the Owner and the person who issued the Building Order. 4 copies of documents and certificates as required by the Building Surveyor Within 7 days of receiving the request or a period agreed between the Applicant and the Building Surveyor. Within 28 days of receiving the request for a certificate or a period agreed between the applicant and the Building Surveyor Within 7 days of receiving the Certificate of Substantial Compliance. 7 Director’s Specified List / Building Act 2000 /Version: October 2014 Section of Act 186(2)(b) Matter required to be specified The documents that accompany an application for a Permit of Substantial Compliance. 186(3) The period in which an applicant has to provide documents or amend an application. 188(1) The period a Permit Authority has to grant an application for a Permit of Substantial Compliance. The period after which a General Manager is taken to have refused to amend or revoke a Building Order in relation to a Fire Upgrading Notice. The period in which an appeal or application is to be made to the Appeal Tribunal 200(3) 219(1)(b) 271(2)(a) 271(2)(b) The amount (dollars) a Permit Authority may retain from the levy payable by the owner to the Permit Authority before the issue of a Building Permit, a Permit to Proceed or a Permit of Substantial Compliance. The body the balance of the levy paid is to be forwarded to by the Permit Authority. Specified requirement Certificate of Title, Schedule and Plan; Site plans (if and as required by Building Surveyor for a Certificate of Substantial Compliance – e.g. for internal work in existing buildings); Architectural Plans Certificates of the responsible designers (Building Work) (Approved Form 35A) (if applicable) Outline Plan and procedure of demolition works w/a Details of proposed work for the protection of persons or property Certificate of Substantial Compliance All documents referred to on the Certificate of Substantial Compliance All certificates and reports relied on by the designer and the building surveyor Evidence of the contract price of the building work, or if there is no contract, an estimate of the total cost of the building work provided by the relevant building surveyor A certificate for certifiable work (building) if required under the Water and Sewerage Industry Act 2008 The documents (if required) referred to in Schedule 2 A Certificate of Others – Plumbing Work – Substantial Compliance (Approved Form 59) Within 7 days of receiving the request or a period agreed between the Applicant and the Permit Authority. Within 21 days of receiving the application or a period agreed between the Applicant and the Permit Authority. Within 14 days of receiving the request. Within 14 days of the decision being given that is to be the subject of the appeal or application. $6 for each levy paid for each permit issued. The Department of Justice. 8 Director’s Specified List / Building Act 2000 /Version: October 2014 The Building Regulations 2014 requires a number of matters to be specified by the Director of Building Control. The following is a list of those matters. Regulation No. 18(5) 19(8) 24(3) 24(2) 29(d) 32(1) 35(b) 40(3) Matter required to be specified The period in which the Building Surveyor has to notify the Chief Officer. Within 2 working days of granting a Certificate of Likely Compliance. The period in which the Building Surveyor has to notify the Environmental Health Officer. The period in which the parties involved in building work are to advise a change of name or address or that they have ceased to be the owner, agent, designer or builder. . Period in which a building surveyor is to advise the Permit Authoriity that they are no longer engaged or responsible for a matter. Within 2 working days of granting a Certificate of Likely Compliance. Within 7 days after the change, if the change occurs after a permit is granted and before the building work is completed. The period in which a person must advise the Chief Officer. The period in which the builder has to notify the Building Surveyor. The period in which a Builder has to wait before proceeding. The period in which the Chief Officer is to provide a required report. Not less than 7 days prior to undertaking the work. 40(5) The period in which the Environmental Health Officer is to provide a required report. 40(7) The period in which the Building Surveyor has to notify the Chief Officer or Environmental Health Officer. Relevant frequency of testing or inspection for maintenance of essential safety and health features for a building completed or altered before 1/7/2004 Relevant frequency of testing or inspection for maintenance of essential safety and health features for a building completed or altered after 1/7/2004 Relevant frequency of testing or inspection for maintenance of essential safety and health measures. 49(1)(a) 49(1)(b) 49(2) 49(3) 55(1) 55(2) Specified requirement Relevant frequency of testing or inspection for maintenance of other prescribed features or measures. The period in which a person has to notify that they intend to install a heating appliance. The period in which a person has to notify the completion of the installation of a heating appliance. Within 7 days of the change if the change occurs after a permit is granted and before the building work is completed. Not less than 2 working days before starting the work. At least 1 working day after completion of a stage of building work. Within 14 days of receiving the request or a period agreed between the Building Surveyor and Chief Officer. Within 14 days of receiving the request or a period agreed between the Building Surveyor and the Environmental Health Officer. Within 2 working days of granting an Occupancy Permit. The documents (if required) referred to in Schedule 4 of this List The documents (if required) referred to in Schedule 4 of this List The documents (if required) referred to in Schedule 5 of this List The documents (if required) referred to in Schedule 6 of this List Not less than 2 working days before installation of the heating appliance. Within 7 days of completing the installation of a heating appliance. 9 Director’s Specified List / Building Act 2000 /Version: October 2014 The Plumbing Regulations 2014 requires a number of matters to be specified by the Director of Building Control. The following is a list of those matters. Regulation No. 21(4)(b) 23(1) 28(1)(b)(i) 37(4) 43(b) Matter required to be specified The specified day The period in which the parties involved in plumbing work are to advise a change of name or address or that they have ceased to be the owner, agent, designer or plumber. The frequency for testing testable backflow prevention device The period in which a Permit Authority is to confirm in writing a start work authorisation given orally The period in which a plumber has to wait before proceeding Specified requirement The expiration of 7 days after the day on which the notice was forwarded. Within 7 days after the change, if the change occurs after a permit is granted and before the plumbing work is completed. Annually. Within 5 days of giving the authorisation. At least 1 working day after completion of a stage of plumbing work. 10 Director’s Specified List / Building Act 2000 /Version: October 2014 SCHEDULE 1 Minimum requirements for design documentation for Class 1 and Class 10 buildings. Note: Drawings may be combined with another drawing or omitted if the information is not applicable to the project. The information may also be provided within a schedule, specification or by another consultant. To be read in conjunction with the National Construction Code and the Explanatory Information at the end of this schedule. All Projects Item applies to Class 10: Drawing Title Block Y Title block on every drawing to contain: Accredited designer (usually name, address and contact number) Y Drawing number (including revision numbers and date) and number of drawings in set Y Project address Y Client name Y Cover Page Designer’s name and accreditation number Y Land title reference number (certificate folio and volume) Y Index of all drawings, specifications, schedules and attachments Y Total floor areas of each level and decks Y Design wind speed Y Soil classification Note: A soil classification for Class 10 buildings may not be required for simplistic or small structures or where preengineered designs contain a range of soil designs. For large Class 10 buildings the designer must consider whether a soil classification is required. Climate zone Note: Class 10 if containing a conditioned space. Designated Bushfire-Prone Area BAL rating (Bushfire Attack Level) Y Alpine area (900m above AHD) Corrosion environment considerations Other known site hazards (flooding, landslip, dispersive soils, saline soils, sand dunes, mine subsidence, landfill etc) 11 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Site Plan (1:200) Note: Site plans may be drawn at different scales where necessary. Y The title boundaries, dimensions and directions of the land, including the north point, building line (distance between front of the building and front boundary line). Note: “Standalone” Class 10 buildings (the only building on the allotment), need not be drawn to scale, provided the detailed site plan contains dimensions, set back etc. The sketch or other document must contain the basic information requirements in this part (boundaries, north point, easements etc) where they can be described. The position and dimensions of any drains or service easements on the land Y The name of any street or way onto which the land abuts The position and dimensions on the allotment of the proposed building or building work Y Note: A “building” includes part of a building and non-habitable structures such as retaining walls, swimming pools, masts etc. Driveways, parking areas and kerb crossovers Note: Consideration must be given to surface levels from the road access to the allotment and within the allotment where driveways, parking areas and crossovers are proposed. Note: Plans to consider stormwater flow over driveways, parking areas and crossovers. Finished floor and site levels relative to site datum The relationship of the proposed building or building work to the boundaries of the land Y The position of any buildings on adjoining properties within 3m of the boundary of the land Y Note: The site plan must indicate any existing buildings, structures, retaining walls, tree removal or the like within 3 metres of the boundary of the land. Where this occurs, further designs may be required detailing any measures of “protection works” under section 121 of the Act. An owner who commissions building work that requires protection work must notify the relevant adjacent land owner using Form 6 (Building and Protection Work Notice). Detailed contours of the land at 0.5m intervals over the building site referenced to a project site datum for all new Class 1 buildings Note: Contours must be detailed over the building envelope of class 1 additions if they are available from recent drawings or plans containing contour information. Note: For Class 1 additions or Class 10 buildings (where the existing ground level over the buildings footprint of the new work exceeds 1m deep) drawing plans must contain sufficient detail regarding dimensions, depths, bulk excavations, cuts, batters and any required methods of drainage control. Earthworks (excavations or fill levels relative to the site datum and compaction details) and associated soil and water management strategies The position of any existing building, structure or trees or recently removed building or structures on the land and the purpose for which the building or structures is, or was used Note: Abnormal moisture conditions in soil may arise on sites where existing trees or buildings have been removed, dams or in ground swimming pools or tanks filled prior to construction. Consideration must be given to the correct detailing of site drainage where abnormal site conditions occur. Note: The location of existing building is required where Bushfire protection measures apply. 12 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Site Plan continued Surface and sub-surface site drainage including location of sewer drains, on-site wastewater management systems including their land application area Y Levels of overflow relief gully (ORG) rim relative to the lowest sanitary plumbing fixture outlet and the surrounding finished surface level Y Note: This part also applies to Class 10 buildings that contain sanitary plumbing fixtures. Levels of inverts to existing and proposed drainage services at point of connection to approved disposal system Y Note: Include roof stormwater drainage systems to Class 10 buildings (where applicable) Floor Plan (1:100) Y Dimensions (including room dimensions) Y Room uses Floor levels Facilities Windows and openings Location and specification of solid fuel, oil or gas heating appliances Garage doors Identification of existing structure Identify demolition, any asbestos containing material, heritage considerations Note: “Protection Works” may need to be considered when undertaking demolition works. See explanatory box requirements under “Site Plan”. Safe movement and access details (direction of stairs and ramps) Fire separation requirements Slab Plan / Floor Framing Plan (1:100) and Details (1:20) Y Dimensioned plan and construction details of footings including penetrations, step down details and placement of reinforcement including cover Y Nominated founding depth and description of founding material Dimensioned plan and construction details of slabs including levels, falls or gradients Slab preparation including materials, thicknesses, compaction requirements, vapour barrier specifications and installation details Construction details of penetrations, step downs in beams, set downs in slabs and placement details of reinforcement including cover Sub-floor vents (location and size per metre) Note: Drawings must detail location of sub floor vents required for dead air spaces and cross flow air. Sub-floor bracing (masonry shear walls) Specify dimensions of engaged and isolated piers 13 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Slab Plan / Floor Framing Plan and Details (continued) Retaining walls, dimensioned and showing position of drainage, founding levels and heights (see Project Specific Information) Concrete strength, finishing and curing requirements Y Specifications and installation details of proprietary and other systems Y Show minimum clearances to ground level of flooring system members Framing drawings or schedules to indicate each structural member, dimensions, orientation, material, grade and size, spacing and span Y Joint, support and bearing details Roof Plan (1:100) Y Dimensions Y Roof sheeting or tile specification including: Roof pitch Batten spacing Fixing requirements Flashing details Roof drainage Y Roof lights Roof ventilators Eaves and overhang information Show location of roof mounted solar panels, hot water service or air conditioners 14 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Roof Framing / Bracing Plan (1:100) Y Indicate details and type of supporting framework, load bearing and non-load bearing parts, lintels, beams, eaves details, roof pitch, ceiling height, roof shape or angle Framing drawings or schedules to indicate each structural member, dimensions, orientation, material, grade and size, spacing and span Y Joint, support and bearing details Bracing, tie downs and fixings Roof pitch, eave / overhang details Show location of roof mounted solar panels, hot water service or air conditioners Fire rating construction details Pre-Assembled Roof Trusses (timber or steel) (where specified) Y Where pre-assembled roof trusses are used, drawings or specifications need only contain sufficient information to ensure that any point loads imposed by the pre-assembled roof trusses on any supporting framework (lintels, structural framework and the like) are adequately designed to support the loads from the roof framework, coverings and live loads. Factory manufactured “roof trusses” must be designed in accordance with Part 3.4.0.2 of the Building Code of Australia (ABCB protocol for structural software: including geometric design limitations) where the design is in accordance with AS1720.1 and their manufacture and use complies with the relevant Australian/ New Zealand Standards. Y Note: As a minimum drawings or specifications must include: ceiling levels (raised, truncated, sloping or flat), roof pitch or angle of roof, truss spacing and layout, skillion roof height at lowest eaves point (as applicable), any boxed gutters or parapets, extent of truss roof system and eaves/gable overhang. Pre-assembled trusses handled and braced in accordance with recommendations contained in AS4440. Note: Designs may need to detail additional structural work to support imposed loads from pre-assembled roof trusses or products, such as floor slab thickenings, additional pad or strip footings within the footprint of the external walls, special connections, tie downs, lateral restraint and the like. Note: Location of roof mounted solar panels, hot water systems and air conditioners need to be sufficiently clear to ensure they are taken into account by truss Manufacturer. Other Engineered designed products (beams, girders and the like) shall be noted on drawing as being “engineered designed” to a manufacturer’s standard (as applicable) Y Note: Glue-laminated timber members, I-Beams, and the like must be noted on the drawings to be installed in accordance with current manufacturer’s printed design manuals (as selected). 15 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Drainage Plan (1:100) Y (Information may be shown on Site Plan or Floor Plan if legible) Documentation in accordance with Schedule 2 of the Director’s Specified List Reflected Ceiling Plan (1:100) Indicating ceiling penetrations, skylights, and exhausts fans (for conditioned spaces) Note: The plan is to indicate design of all light fittings (watts per fitting, whether ceiling mounted or downlights or both, lighting control per circuit - dimmers, timers, movement sensors and on/off switches). Where penetrations formed in insulated ceilings, any adjustment to minimum R-value for “ceiling insulation” to be made in accordance with BCA table 3.12.1.1b. Room heights Elevations (1:100) Y All elevations should be drawn Y Position of all windows and doors Y Ceiling heights and floor levels Differentiate wall and roof cladding types Y Natural ground line dotted Y Roof lights / vents, air conditioning units, solar panels or solar hot water Sections (1:100) Y Generally taken through the highest and widest points of the building and should reveal details or facts which are otherwise concealed Y Section through stairs (where applicable) Ceiling / eaves heights and floor levels 16 Director’s Specified List / Building Act 2000 /Version: October 2014 Project Specific Information Note: May be included within drawings, schedules or specifications, including consultant’s documents. Item applies to Class 10: Retaining Walls (where permit required - i.e. greater than 1 metre) Y Dimensioned construction details Y Drainage, tanking and protection details Y Backfill specifications Y Concrete mix, reinforcement placement, washout requirements Y Specifications and installation details of proprietary and other systems Y Masonry Construction (if applicable) Y Show unreinforced, reinforced or earthwall construction specifications and details Identify structural and non-structural walls Reinforcing specified for reinforced walls Y Identify fire rating requirements Masonry unit sizes and bond patterns and tooling of joints Y Specification of brick ties and anchorages Y Mortar specification Y Cavity dimension and clean out specification Knockout blocks for washout Control joint location and detail Y Sub-floor vents. Location and size per metre Note: drawings must detail location of sub-floor vents required for dead air spaces and cross-flow air. Specify lintels and bond beams Weatherproofing and waterproofing details Flashings, damp proof course and weep holes Weephole guards (insects, bushfire-prone areas) Exterior Wall Cladding Y Cladding system description, manufacturer, material, pattern and colour, cavity detailing Y Fixings, flashings and other details Sub-floor ventilation Interior Wall Lining Specify material and system Wet areas specification (extent and system e.g. membrane, manufacturer and type) 17 Director’s Specified List / Building Act 2000 /Version: October 2014 Flooring Specify material and system Item applies to Class 10: Wet Areas Waterproofing and water resistance requirements for building elements in “Wet Areas” Note: Designs shall indicate wet area locations; provide wet area specifications, location of propriety fixtures (shower trays etc.) or whether an “open wet floor” system is proposed that requires waterproofing or both. The extent of wet areas must be indicated. Fire Safety Smoke and heat alarms, location and type (interconnection where more than one) Emergency lighting (for Class 1b) Fire separation details Bushfire-Prone Area specifications Y Note: Specifications to include requirements from AS3959. General construction: subfloor supports, floors, walls, external glazing elements and assemblies, external doors and windows, roofs, verandas and attached carport roofs, penetrations, eaves, fascia, gables, gutters and down pipes, verandas, decks, steps, ramps and landings. Water and gas pipe supply. Alpine area requirements (900m above AHD) Safe Movement and Access (including stairs and ramps) Stair design details, balustrade construction and spacing of openings (gaps <125mm) and handrail details Y Clearance height above stair nosings Winders detail Dimensions of landings, risers and goings, non-slip nosings Note: Sections to indicate acceptable ceiling height between levels (2m minimum) Method of construction, including aperture size, non-slip requirements Ramp slope and surface finish Disability access requirements (for Class 1b) Swimming Pools and Pool Spas Construction details, waterproofing, drainage, pool water recirculation and filtration systems Y Pool safety barrier details and height Y Gates and latches as part of safety barriers Y Additional Construction Requirements High wind, earthquake, flood prone, landslide hazards, Bushfire-Prone Areas (others are shown on cover page of example drawings) Y Heritage buildings 18 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Glazing Y Window and Door systems description (i.e. single or double glazed, tinted or low E glass window and door frame material) Glazing specification Y Opening size for ventilation calculation Other glazing: Internal glazing specifications including wet area glazing, shower screens, doors Balustrading system specification (glass and fixings) including height Overhead glazing, roof or sky lights Energy Efficiency details: U Value, Solar Heat Gain Coefficient Protection of openable windows Note: The location of certain window openings in buildings require special methods of protection that restricts the opening of a window to prevent a person (especially young children) from falling through the window when open. Energy Efficiency Also applies to a Class 10 where containing a conditioned space Y Building fabric thermal efficiency specification (including climate zone) Walls, ceiling, floors and roof Insulation location and R-value Type of Sarking/ Wallwrap (Note: consider vapour permeability) Window energy specification (see also under glazing) Lighting design plan (see Reflected Ceiling Plan) Energy rating documentation Building sealing, air movement Pipe and services insulation Glazing calculator to be supplied if a Deemed-to-Satisfy solution Note: Glazing Calculators have been developed by the ABCB to help industry meet the deemed-to-satisfy provisions of The National Construction Code. Once users have entered data into the spread sheet, all calculations are carried out automatically. Calculators can be downloaded from the ABCB website www.abcb.gov.au Lighting calculator to be supplied if a Deemed-to-Satisfy solution Note: A Lighting Calculator has been developed by the ABCB to help industry meet the deemed-to-satisfy provisions of The Building Code of Australia for maximum lighting power consumption. Once users have entered data into the spread sheet, all calculations are carried out automatically. Calculators can be downloaded from the ABCB web site www.abcb.gov.au Under slab or slab edge insulation 19 Director’s Specified List / Building Act 2000 /Version: October 2014 Item applies to Class 10: Condensation in Buildings Note: The building design should provide adequate means of ventilation to the structure to ensure the long term safety of the building. Some considerations may be: Eliminate water vapour generated by occupants, entering roof or wall cavities Ensure fans are appropriately sized to remove water vapour not just odours. Duct gas appliances, kitchen range hoods, clothes dryers, bathroom exhausts to outside air. Ensure sufficient makeup air is provided e.g. undercut doors, install vents and open windows more frequently Provide adequate well-distributed sub-floor ventilation, and use impermeable ground coverings in damp soil areas Ensure adequate roof ventilation Introduce ventilated cavities by the use of wall battens spaces and the like for polystyrene, hardboard and cement sheet external wall claddings Ceiling insulation in preference to roof insulation Note: Insulation should be installed with due consideration of condensation and associated interactions with adjoining building materials. As an example, reflective insulation or sarkings installed on the cold side of the building envelope should be vapour permeable. Note: More information on condensation issues can be found on the ABCB website www.abcb.gov.au Explanatory Information The above information is the minimum documentation required to obtain a Certificate of Likely Compliance. For guidance on a complete domestic construction project specification, refer to the current NATSPEC Simple Domestic Specification (www.natspec.com.au) It is not the intent of this schedule to reduce the standard of Design Specification, but to provide for a mandatory minimum level of documentation. This Schedule specifies the mandatory minimum level of design details required to be provided by an accredited designer to enable a builder or plumber to undertake the construction of Class 1 and 10 buildings and for a building surveyor to assess the works for compliance with the Building Act 2000, National Construction Code and relevant Australian Standards. The Schedule allows designers the freedom to produce a mixture of graphic designs or specifications or both, provided the design work contains sufficient information and details to comply with the Act. This Schedule does not diminish the relevant Building Surveyor’s right to ask for further design information to be supplied before a certificate of likely compliance can be issued. Application to Class 10 Buildings and Structures This Schedule specifically identifies the minimum level of design information required for Class 10 buildings. This is shown by the notation (Y) against particular headings. Designers may only need to provide the required minimum level of documentation for Class 10 buildings where a heading refers to that notation. 20 Director’s Specified List / Building Act 2000 /Version: October 2014 Documentation Information Requirements Detailed information provided on drawings or within specifications must be job specific to the proposed project. e.g. structural timber to comply with AS1684 should instead be expressed as: Joists 150x35 MGP10 @ 450mm c/c. Alternative Design Solutions Documentation should include all calculations, reports, certificates and manufacturer’s information together with a written proposition to support a building solution which is not in accordance with the Deemed-to-Satisfy provisions of the National Construction Code (see Part 1.2 BCA Vol. 2) Duties of Designers The Building Act 2000 Section 13 A designer is to ensure that – (a) he or she acts only within the area of his or her competence; and (b) so far as is reasonably practicable – (i) the design of the building or plumbing work is in accordance with the standards and requirements of this Act; and (ii) the documentation relating to the design includes sufficient information for the assessment of the work in accordance with this Act; and (iii) the documentation relating to the design is sufficiently detailed for a builder or a plumber to carry out the work in accordance with the documents and this Act. 21 Director’s Specified List / Building Act 2000 /Version: October 2014 SCHEDULE 2 DOCUMENTS – PLUMBING WORK PART 1 DOCUMENTS IN RELATION TO A PLUMBING PERMIT The documents listed below are required to accompany an application for a Plumbing Permit: 1. A plan of the land, drawn to a scale of not less than 1:500, showing the following: (a) the title boundaries, dimensions and directions of the land; (b) the position and dimensions of any easement which affects or runs with the land; (c) the name and level of any street or way onto which the land abuts; (d) the position of any existing and proposed buildings on the land and the purpose for which the building is, or is intended to be, used; (e) the location of the network utility operator’s sewer system, stormwater system and water main and the approximate position of the branch of those systems to which proposed services are to be connected; (f) the size and approximate depth of the network utility operator’s sewer system, stormwater system and water main; (g) the position of the proposed plumbing work. 2. For any sewerage, stormwater or trade waste installation on a single floor, complete drawings of the installation drawn to a scale of not less than 1:200, including dimensions, showing the following: (a) the position of each building, in relation to the installation; (b) for each existing and proposed drain – (i) its location; and (ii) its status, existing or new; and (iii) its size; and (iv) any drainage vents; and (v) any fittings; and (vi) the type of material of which it is, or is proposed to be, made; (c) the approximate location of the proposed fixture, indicated by the abbreviation for that fixture specified in Part 4. 3. For any sewerage, stormwater or trade waste installation on more than one floor, complete drawings of the installation drawn to a scale of not less than 1:200, including dimensions, showing – (a) for each storey on which a proposed fixture is to be installed – (i) the nature and position of each fixture, indicated by the abbreviation specified in Part 4; and (ii) the size and arrangement of stacks and discharge pipes; and (b) the intended use of each room in which a fixture is, or is to be, installed; and (c) the floor layout, indicating the position and pipe sizes of fixtures, ducts and stacks; and (d) for a building other than a Class 1 or 10, the plumbing system with stacks and discharge pipes indicated by a clearly labelled isometric plumbing layout. 4. For any water service, complete drawings of the installation drawn to a scale of not less than 1:200, including dimensions, showing – (a) the location and size of any regulating device, flow control fitting or service pipe 25mm diameter or larger; and (b) details of any existing or proposed fire protection devices to be supplied with water from the proposed water service; and 22 Director’s Specified List / Building Act 2000 /Version: October 2014 (c) the location and size of any storage tank; and (d) the purpose for which water is conveyed, measured, supplied or regulated by the proposed water service is required. 5. For the connection of a new unregistrable relocatable building to the network utility operator’s sewerage or stormwater system or water main – (a) a statement detailing the chassis number of the unregistrable relocatable building, together with the licence number of the licensed plumber (certifier) responsible for the installation of the plumbing work within that unregistrable relocatable building; or (b) a signed declaration, in an approved form, by a licensed plumber (certifier) that the plumbing work contained in the unregistrable relocatable building has been tested, and complies with the regulations. 6. For the re-connection of an unregistrable relocatable building to the network utility operator’s sewerage or stormwater systems or water main, a signed declaration, by a licensed plumber (certifier) that the plumbing work contained in the unregistrable relocatable building complies with the regulations. 7. Construction details of the plumbing work, drawn to a scale of not less than 1:20. 8. A written specification or schedule of the plumbing work containing any other information required to show that the plumbing work will comply with the Building Act and Regulations. 9. If the land is not capable of being drained into a common sewer – (a) an application for a special plumbing permit to install an on-site waste water management system, together with the documents specified in Part 3 of this Schedule; or (b) a special plumbing permit to install an on-site waste water management system. PART 2 DOCUMENTS IN RELATION TO A SPECIAL PLUMBING PERMIT FOR TRADE WASTE SYSTEMS CONNECTED TO AN APPROVED DISPOSAL SYSTEM, OTHER THAN A SEWERAGE SYSTEM The documents listed below are required to accompany an application for a special plumbing permit for trade waste systems connected to an approved disposal system other than a sewerage system. Documents containing details of the following: (a) the processes leading to the types of trade waste streams to be generated; (b) the quality of trade waste; (c) the quantity and rate of trade waste discharge; (d) any treatment processes designed to make trade waste meet the requirements of the Permit Authority; (e) any equipment to be used for the treatment, and for monitoring the quality, quantity and rate of discharge, of the trade waste; and (f) any other information, document or certificate required by the Permit Authority. 23 Director’s Specified List / Building Act 2000 /Version: October 2014 PART 3 DOCUMENTS IN RELATION TO A SPECIAL PLUMBING PERMIT FOR AN ON-SITE WASTE WATER MANAGEMENT SYSTEM The documents listed below are required to accompany an application for a special plumbing permit for the installation of an on-site waste water management system. 1. Complete drawings of the installation, drawn to a scale of not less than 1:200 or as agreed to by the Permit Authority, showing the following: (a) the title boundaries of the land; (b) the position of any existing or proposed buildings on the land and their use; (c) the position of any roads or driveways on the land; (d) the location of any water courses; (e) the contours on the land; (f) the position of the disposal system, absorption trenches or other disposal methods; (g) the location and size of any drains and vents; (h) the location of any cut-off drains diverting surface or ground water; (i) the location of the outlets from the building. 2. Written details of the proposed fixture unit load on the system or parts of the system. 3. A site-and-soil evaluation report detailing the results of the assessment of the lot or lots for the public health, environmental and legal factors which are likely to impact on the siting and design of a land application system; and an evaluation of the site-and-soil characteristics to determine feasible options for designing and sizing a land application system. (See AS/NZS 1547 Clause 5.2.4 and Appendices B, C, D, E, and G) 4. A Design report consisting of the following: (a) Relevant aspects of the site-and-soil evaluation report; (b) A report on the selection of the land application system (see AS/NZS 1547 Clause 5.5.7); (c) A report on the selection of the wastewater treatment unit (see AS/NZS 1547 Clause 5.5.4, Appendix H, and Appendix J). For non-conventional waste water management systems the report is to provide sufficient information to show that the performance requirements in Part F1 of the PCA have been met; (d) A loading certificate setting out the design criteria and the limitations associated with use of the system incorporating the following: System capacity (number of persons and daily flow) Summary of design criteria The location of and use of the reserve area Use of water efficient fittings, fixtures, or appliances Allowable variation from design flows (peak loading events) Consequences of changes in loading (due to varying wastewater characteristics) Consequences of overloading the system Consequences of underloading the system Consequences of lack of operation, maintenance, and monitoring attention Any other relevant considerations related to use of the system; and (e) The results of the risk management process undertaken in accordance with AS/NZS 1547 Clause A3.2. 24 Director’s Specified List / Building Act 2000 /Version: October 2014 5. A written specification and construction details of the land application system to be used, including details of the following: (a) the type of system; (b) the trade name, if any; (c) the manufacturer's name and address; (d) the design capacity of the system; and (e) a section (drawing detail) through the land application system, of not less than 1:20, specifying its construction. 6. Copy of Certificate of Accreditation issued under the Building Act for the on-site waste water management system (where applicable). 7. Any other document or certificate required by the relevant environmental health officer. 25 Director’s Specified List / Building Act 2000 /Version: October 2014 PART 4 FIXTURE ABBREVIATIONS FOR PLAN PREPARATION The abbreviations listed below are required to be used on the documents listed in Schedule 2: FIXTURE Autopsy table Bain marie Backflow prevention device Basin Bath – standard (with or without shower) foot baby shower Bed pan sterilizer Bed pan washer Bed pan washer/sterilizer Bidet Circular wash fountain Closet pan (non-flushing) Clothes washing machine Dental unit Dishwashing machine Drinking fountain Floor waste gully Garbage disposal unit Glass washing machine Gully Floor waste gully Overflow relief gully Hot water cylinder Potato peeler Sanitary napkin disposal unit Shower, single or multiple Sink Single, domestic tea bar, domestic bar, commercial cleaner's laboratory pot or utility Slop hopper Spa Swimming pool Trough, ablution Trough, laundry (single or double) Urinal (slab, stall or wallhung) Water closet pan ABBREVIATION AT BM BPD B Bth Bth (foot) Bth (baby) Bth (shr) BPS BPW BPWS Bid CWF CP CWM DU DWM DF FW GDU GWM FWG ORG HWC PP SNDU Shr S TS BS(D) BS(C) CS LS PS SH Spa S Pool Tr (A) Tr (L) UrWC WC Note: This is not a comprehensive list of abbreviations. For further abbreviations refer to the Standards Australia publication HB24-1992; ‘Handbook of Symbols and Abbreviations for Building and Construction’. 26 Director’s Specified List / Building Act 2000 /Version: October 2014 SCHEDULE 3 DOCUMENTS IN RELATION TO A CERTIFICATE OF PLUMBING COMPLIANCE The documents listed below are required to be submitted to a Permit Authority with a Certificate of Plumbing Compliance. 1. Complete set of as constructed drawings of the installation, drawn to a scale of not less than 1:200 or as agreed to by the Permit Authority, showing the following: (a) the title boundaries of the land; (b) the position of any existing or new buildings or structures on the land; (c) the position of any roads or driveways on the land; (d) the location, size, material and depth of any drains, pipes, inspection openings and vents; (e) the location of any cut-off drains diverting surface or ground water; (f) the location of any fixtures in the building; (g) the location of any valves or other devices on the system (where required); and (h) any other matter required by the Permit Authority. 2. Any other documents required by the Permit Authority. Note: The abbreviations listed in Part 4 of Schedule 2 are to be used on the above documents. 27 Director’s Specified List / Building Act 2000 /Version: October 2014 Schedules of Prescribed Features and Measures required to be maintained Schedules 4, 5 and 6 have been specifically developed for the creation of a Maintenance Schedule (on the Approved Form No. 46) by the relevant building surveyor for new building work (constructed or altered after 1 July 2004) listing the prescribed features or measures of a building required to be maintained by the Building Act 2000 and the Building Regulations 2014. For buildings completed before 1 July 2004, the Schedules can also be used by a building surveyor or the owner to create a maintenance schedule or checklist of the features or measures in an existing building. Transitional provision applicable to the adoption of the 2012 edition of AS1851 Maintenance regimes and contracts that have been agreed between parties prior to 1st January 2014 for the maintenance of any prescribed features and measures, including safety and health features or measures, which are in compliance with the Director’s Specified List dated 28 November 2012, comply with this amended Specified List until the expiry of that contract. SCHEDULE 4 DETAILS OF THE RELEVANT FREQUENCY OF TESTING OR INSPECTION FOR THE MAINTENANCE OF ESSENTIAL SAFETY AND HEALTH FEATURES. “NCC” refers to National Construction Code provisions in Volumes One and Two (building features or measures) or Volume Three (plumbing features). Table 1.1 BUILDING FIRE INTEGRITY Feature NCC provisions for determining standard of performance Frequency of testing or inspection specified by the Director of Building Control: Building elements required to satisfy prescribed fire resistance levels Materials and assemblies required to have fire hazard properties Elements required to be noncombustible, provide fire protection, compartmentation or separation Section C, D1.12 C1.10 As prescribed in AS1851-2012. C2.5 to C2.14, C3.3, C3.11, D1.7, D1.8, E1.3, G3.4 C3.4, C3.8, C3.11, D1.7, D1.8, G3.8 As prescribed in AS1851-2012. C2.12, C2.13, C3.4 to C3.8, C3.10, C3.11, D1.7, D1.8, D1.12 As prescribed in AS1851-2012 C3.4, C3.8, C3.11, D1.7, D1.8 As prescribed in AS1851-2012. C3.4, C3.5, D1.7 to D1.8 C3.11 As prescribed in AS1851-2012. C3.12, C3.13, C3.15 As prescribed in AS1851-2012. Wall-wetting sprinklers (including doors and windows required in conjunction with wall-wetting sprinklers) Fire doors (including sliding fire doors and their associated warning systems) and associated self-closing, automatic closing and latching mechanisms Fire windows (including windows that are automatic or permanently fixed in the closed position) Fire shutters Solid core doors and associated selfclosing, automatic closing and latching mechanisms Fire-protection at service penetrations through elements required to be fire-resisting with respect to integrity or insulation, or to have a resistance to the incipient spread of fire As prescribed in AS1851-2012. As prescribed in AS1851-2012. As prescribed in AS1851-2012. 28 Director’s Specified List / Building Act 2000 /Version: October 2014 Fire protection associated with construction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation. Smoke doors and associated selfclosing, automatic closing and latching mechanisms C3.16 As prescribed in AS1851-2012. Specification C2.5, D2.6 As prescribed in AS1851-2012. Proscenium walls (including proscenium curtains) H1.3 Annual inspection for damage, deterioration or unauthorised alteration. Table 1.2 MEANS OF EGRESS Feature Paths of travel to exits NCC provisions for determining standard of performance D1.6 Frequency of testing or inspection specified by the Director of Building Control: Inspection every 3 months to ensure there are no obstructions and no alterations. Discharge from exits (including paths of travel from open spaces to the public roads to which they are connected) D1.7, D1.9 to D1.11, D2.12, G4.3, G4.6, G4.7 Inspection every 3 months to ensure there are no obstructions and no alterations. Exits (including fire-isolated stairways and ramps, non-fire isolated stairways and ramps, stair treads, balustrades and handrails associated with exits, and fire-isolated passageways) Smoke lobbies to fire-isolated exits D2.2, D2.3, D2.8 to D2.11, D2.13, D2.16, D2.17 Inspection every 3 months to ensure there are no obstructions and no alterations. D1.7, D2.6 Open access ramps or balconies for fire-isolated exits D2.19 to D2.23 Doors (other than fire or smoke doors) in a required exit, forming part of a required exit or in a path of travel to a required exit, and associated selfclosing, automatic closing and latching mechanisms D1.6, D2.19 to D2.21, D2.23 Annual inspection for damage, deterioration, or unauthorised alteration. Annual inspection for damage, deterioration, or unauthorised alteration. Inspection every 3 months to ensure doors are intact, operational and fitted with conforming hardware. Table 1.3 SIGNS Feature Exit signs (including direction signs) Signs warning against the use of lifts in the event of fire Warning signs on sliding fire doors and doors to non-required stairways, ramps and escalators Signs, intercommunication systems, or alarm systems on doors of fireisolated exits stating that re-entry to a storey is available NCC provisions for determining standard of performance Specification D1.12, E4.5, E4.6, E4.8 E3.3 C3.6, Specification D1.12 D2.22 Frequency of testing or inspection specified by the Director of Building Control: Every 6 months to AS/NZS 2293.2 1995. Annual inspection to ensure the warning sign is in place and legible. Annual inspection to ensure the warning sign is in place and legible. Annual inspection to ensure the warning sign is in place and legible. 29 Director’s Specified List / Building Act 2000 /Version: October 2014 Signs alerting persons that the operation of doors must not be impaired Signs required on doors, in alpine areas, alerting people that they open inwards Fire order notices required in alpine areas Table 1.4 LIGHTING Feature D2.23 Annual inspection to ensure the warning sign is in place and legible. G4.3 Annual inspection to ensure the warning sign is in place and legible. G4.9 Annual inspection to ensure the warning sign is in place and legible. Emergency lighting NCC provisions for determining standard of performance E4.2, E4.4 Artificial lighting required to assist occupants movement and egress F4.4, H1.7 Table 1.5 FIRE FIGHTING SERVICES AND EQUIPMENT Feature NCC provisions for determining standard of performance Fire hydrant system (including onE1.3 site pump set and fire-service booster connection) Fire hose reel system E1.4 Sprinkler system E1.5, G3.8, H1.2 Sprinkler system designed in E1.5 accordance with AS2118 as a residential or domestic system Fire control centres (or rooms) E1.8 Provisions for special hazards Portable fire extinguishers E1.10 E1.6 Fire blankets - Frequency of testing or inspection specified by the Director of Building Control: Every 6 months to AS/NZS 2293.2 1995 Inspection every 3 months Frequency of testing or inspection specified by the Director of Building Control: As prescribed in AS1851-2012 As prescribed in AS1851-2012 As prescribed in AS1851-2012 As prescribed in AS1851-2012. Annual inspection to ensure compliance of construction and contents with NCC. As prescribed in AS1851- 2012 Inspection every 6 months as prescribed in AS1851-2012. Inspection every 6 months as prescribed in AS1851-2012. 30 Director’s Specified List / Building Act 2000 /Version: October 2014 Table 1.6 AIR HANDLING SYSTEMS Feature NCC provisions for determining standard of performance Smoke hazard management systems: E2.2 Frequency of testing or inspection specified by the Director of Building Control: Automatic air pressurisation systems for fire-isolated exits As prescribed in AS1851-2012 Zone smoke control system As prescribed in AS1851-2012 Automatic smoke exhaust system As prescribed in AS1851-2012 Automatic smoke and heat vents As prescribed in AS1851-2012 Air handling systems that do not form part of smoke hazard management system and which may unduly contribute to the spread of smoke As prescribed in AS1851-2012 Miscellaneous air-handling systems covered by Sections 5 and 11 of AS/NZS 1668.1 serving more than one fire compartment As prescribed in AS1851-2012. Other air-handling systems As prescribed in AS1851-2012. Carpark mechanical ventilation system Atrium smoke control system F4.11 As prescribed in AS1851-2012. Specification G3.8 As prescribed in AS1851-2012. Table 1.7 AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS Feature NCC provisions for determining standard of performance Smoke and heat alarm system Clause 3 of Specification E2.2a Frequency of testing or inspection specified by the Director of Building Control: Smoke and heat detection system Atrium fire detection and alarm systems As prescribed in AS1851-2012. As prescribed in AS1851-2012. Clause 4 of Specification E2.2a Clause 4 of Specification G3.8 As prescribed in AS1851-2012. Table 1.8 OCCUPANT WARNING SYSTEMS Feature NCC provisions for determining standard of performance Frequency of testing or inspection specified by the Director of Building Control: Sound system and intercom system for emergency purposes Building occupant warning system As prescribed in AS1851-2012. E4.9 Clause 5 of Specification G3.8 Clause 8 of Specification E1.5, Clause 6 of Specification E2.2a As prescribed in AS1851-2012. 31 Director’s Specified List / Building Act 2000 /Version: October 2014 Table 1.9 LIFTS Feature Stretcher facilities in lifts NCC provisions for determining standard of performance E3.2 Emergency lifts E3.4 Passenger lift fire service controls E3.7 Frequency of testing or inspection specified by the Director of Building Control: Annual inspection to ensure compliance of facilities with NCC. Periodic inspection as per manufacturer’s specification, however no less than annual inspection. Periodic inspection as per manufacturer’s specification, however no less than annual inspection. Table 1.10 STANDBY POWER SUPPLY SYSTEMS Feature NCC provisions for determining standard of performance Standby power supply system E3.4, Clause 6 of Specification G3.8 Frequency of testing or inspection specified by the Director of Building Control: Table 1.11 OTHER FEATURES Feature Frequency of testing or inspection specified by the Director of Building Control: Glazed assemblies NCC provisions for determining standard of performance B1.4, F1.13 Balconies Part B1 Balustrades and barriers Part B1, D2.16 Swimming pool safety fencing G1.1 Refrigerated chambers, strong rooms and vaults G1.2 Bushfire protection features G5.2 Testing every 6 months to ensure auxiliary power is operable. Annual Inspection to ensure no changes and that replacement complies with standard of performance. Annual inspection to ensure that deterioration of the balcony has not occurred. Annual inspection to ensure that balustrades and barriers are in place and check for damage and deterioration. Annual inspection to ensure that barriers, safety fencing and gates are in place and check for damage and deterioration. Inspection every 3 months to ensure safety devices are in place and operable. Annual inspection to ensure continuing compliance. 32 Director’s Specified List / Building Act 2000 /Version: October 2014 Table 1.12 MECHANICAL VENTILATION AND HOT WATER, WARM WATER AND COOLING WATER SYSTEMS Feature NCC provisions for determining standard of performance Mechanical ventilation and hot F2.7, F4.5, F4.11, F4.12 water, warm water and cooling AS 1668.2 water systems in buildings other than a system only serving a single soleoccupancy unit in a Class 2 or 3 building or a Class 4 part Frequency of testing or inspection specified by the Director of Building Control: Table 1.13 PLUMBING FEATURES DESIGNATED BY PART 7 OF THE PLUMBING REGULATIONS 2014 Feature NCC (Volume Three) provisions for determining standard of performance On-site wastewater management F1.2; systems or The Certificate of Accreditation issued by the Director of Building Control. Testable Backflow Prevention B.12 Devices Thermostatic mixing valves and B2.2 tempering valves installed in early childhood centres, primary and secondary schools, hospitals and nursing homes, or similar facilities for people with a disability, young people, elderly people or sick people On-site liquid trade waste preF2.2 treatment equipment Frequency of testing or inspection specified by the Director of Building Control: As prescribed in the “Guidelines for the Control of Legionella in Regulated Systems” issued by the Director of Public Health under the Public Health Act 1997 on 23 April 2012. As prescribed in the relevant Certificate of Accreditation issued by the Director of Building Control; or As prescribed by the relevant Permit Authority. As prescribed in AS2845.3 – 2010. As prescribed in AS4032.3 – 2004. As prescribed in the Special Plumbing Permit issued by the relevant Permit Authority. SCHEDULE 5 DETAILS OF THE RELEVANT FREQUENCY OF TESTING OR INSPECTION FOR THE MAINTENANCE OF ESSENTIAL SAFETY AND HEALTH MEASURES Table 2.1 BUILDING CLEARANCE AND FIRE APPLIANCES Measure NCC provisions for determining standard of performance Open space around large isolated C2.3, C2.4 buildings Frequency of testing or inspection specified by the Director of Building Control: Vehicular access around large isolated buildings Annual inspect to ensure clearances are maintained. C2.3, C2.4 Annual inspection to ensure that unobstructed access to buildings and fire fighting facilities are maintained. 33 Director’s Specified List / Building Act 2000 /Version: October 2014 Table 2.2 BUILDING USE AND APPLICATION Measure Classification and use of building NCC provisions for determining standard of performance A3.2 to A3.4 Occupancy hazard E1.5, E1.6, E1.10 Frequency of testing or inspection specified by the Director of Building Control: Annual inspection to ensure that building is being used and occupied in accordance with its classification. Annual inspection to ensure hazards do not exceed approved levels. Table 2.3 EMERGENCY EVACUATION PROCEDURES Measure Provisions for determining standard of performance Frequency of testing or inspection specified by the Director of Building Control: Emergency control organisation and procedures As prescribed in the relevant Standard and Section 14 of AS18512012. AS 3745 – 2010; AS 4083-2010 (specifically for Class 9a and 9c Health care buildings) Notes: AS 3745 Planning for Emergencies in Facilities, applies to all buildings and workplaces. Part 14 of AS 1851-2012 provides requirements for inspection and testing of the emergency plan and associated elements developed in accordance with AS 3745. AS 4083 Planning for Emergencies: Health Care Facilities can be used in conjunction with AS 3745 to develop emergency procedures appropriate to Health care buildings. SCHEDULE 6 DETAILS OF THE RELEVANT FREQUENCY OF TESTING OR INSPECTION FOR THE MAINTENANCE OF OTHER PRESCRIBED FEATURES OR MEASURES Feature or measure (provided in or associated with a building) Provisions for determining standard of performance Frequency of testing or inspection specified by the Director of Building Control For access for a person with a disability. Relevant parts of Volume One of the NCC. Inspection every 3 months to ensure no changes and continuing compliance. For the energy efficiency of the building. Not less than the standard when built. Annual inspection to ensure no changes and continuing compliance. For the water efficiency of the building. Not less than the standard when built. Annual inspection to ensure no changes and continuing compliance. In a bushfire-prone area, for the safety of occupants (including firefighting water supply and access road). Not less than the standard when built. Annual inspection to ensure no changes and continuing compliance. 34 Director’s Specified List / Building Act 2000 /Version: October 2014 SCHEDULE 7 FUNCTION CONTROL AUTHORITIES The following are Function Control Authorities for the listed type of special-use buildings in accordance with the requirements of sections 3 and 64 of the Building Act 2000: Type of special-use building Certificate, licence, registration, permit, inspection or control Controlling Act or Regulation Name of Function Control Authority Relevant BCA APPENDIX TASMANIA provision Early childhood centre and school aged care facilities Approval Certificate; or Education and Care Services National Law or TAS PART H122 Licence Child Care Act 2001 Education and Care Unit of the Department of Education Farm dairy premise Licence Dairy Industry Act 1994 Tasmanian Dairy Industry Authority TAS PART H107 Health Service Establishments Licence and includes a temporary licence Health Service Establishments Act 2006 Secretary of the Department of Health TAS PART H109 Licensed (liquor) premise Licence/permit Liquor and Accommodation Act 1990 Commissioner for Licensing TAS PART H103 Location where a hazardous chemical or group of hazardous chemicals exceed the “manifest quantity” Information and Notification Work Health and Safety Act 2012 WorkSafe Tasmania TAS PART H120 Meat premise Licence Meat Hygiene Act 1985 Chief Inspector of Meat Hygiene TAS PART H106 Place of assembly (assembly building) Licence Public Health Act 1997 Local Council TAS PART H123 (for temporary structures) * Primary Production Food Premise regulated by a Food Safety Scheme Operator Accreditation Primary Produce Safety Act 2011 Chief Inspector in Department of Primary Industry, Parks, Water and Environment TAS PART H102 Skin penetration (tattoo and body piercing) premise Registration Public Health Act 1997 Local Council TAS PART H110 * Note on Food Premises: The role of the council Environmental Health Officer (EHO) in relation to the registration of a food premises under the Food Act 2003 has not been listed above as a Function Control Authority, as an EHO already has a role as a Reporting Authority in accordance with regulation 19 of the Building Regulations 2014. The introduction of the new Primary Product Safety Act 2011 (PPSA) has meant that Food Safety Schemes are being introduced for some types of primary produce food processing premises. The Chief Inspector of the PPSA at the Department of Primary Industry, Parks, Water and Environment is then responsible for processing of applications for those types of premises as a Function Control Authority instead of the council EHO. See the Building Regulation Advisory Note No. 3 of 2014 for more details. SCHEDULE 8 REPORTING AUTHORITIES Regulation 17 of the Building Regulations 2014 provides that the following persons are required to report on an application for a certificate of likely compliance or an application for an occupancy permit: 1. The Chief Officer of the Tasmania Fire Service appointed under the Fire Service Act 1979. 2. The relevant Council’s Environmental Health Officer appointed under the Public Health Act 1997. 3. The Anti-Discrimination Commissioner appointed under the Anti-Discrimination Act 1998 (only for applications that are made to the Resource Management and Planning Appeals Tribunal under s.218A of the Building Act 2000 on the grounds of undue hardship of compliance with disability access provisions). SCHEDULE 9 TABLE OF AMENDMENTS Amendments specified by the Director on 1 October 2014: Documents and Time Periods amended: Building Act 2000 The reference (where applicable) to the mandatory number of copies of the required documents, has been deleted, as most councils now accept electronic lodgement of the required documents. Clarifies that a site plan is not always necessary when the work is internal and in an existing building. Sections 70(1)(b), 178(2)(b) and 186(2)(b): Aligns language with Act - an estimate of the cost of building work by a building surveyor is only to be provided where there is no contract for the work. Section 70(1)(b): site plans for a building permit, will depend on if they were required by the Building Surveyor for a CLC– e.g. may not be required for internal work in existing buildings; Section 72: the time for processing of an application for a building permit; a longer time period may apply where there is also a concurrent application for a plumbing permit related to the building work Section 112: When considering a certificate of Completion of Building Work, where applicable, ensure there is a Certificate of Completion (Plumbing Work) Schedules amended: Schedule 1 (Designer’s documentation): Previous Schedule 1 has been rescinded and replaced with a revised version (major revision). Schedule 2 (Documents – Plumbing Work Part 1: Minor editorial changes inserted. Part 3: Revised requirements for submission of a Design Report, including site and soil reports, land application system and a loading certificate. Schedule 4 (table 1.13): Standard for maintenance of an on-site wastewater system is the Certificate of Accreditation issued by the Director of Building Control. Schedule 5 (item 2.3): Reference to updated versions of AS3745 and AS4083 for emergency evacuation procedures. Schedule 7 (Function Control Authorities): Updating of name: Worksafe Tasmania instead of Workplace Standards. Insertion of reference to the Primary Produce Safety Act 2011 and DPIPWE as the relevant Function Control Authority. 36 Director’s Specified List / Building Act 2000 /Version: October 2014 SCHEDULE 10 HISTORY OF DSL AMENDMENTS Specified List issued by the Director of Building Control 14 May 2004 Reissued with amendments 18 June 2004 Reissued with amendments 30 June 2009 Reissued with amendments 29 April 2010 Reissued with amendments 2 May 2011 Reissued with amendments 28 November 2012 Reissued with amendments 1 September 2013 Reissued with amendments 1 July 2014 Reissued with amendments 1 October 2014 37 Director’s Specified List / Building Act 2000 /Version: October 2014