sKVA Rating • Generator sKVA represents the generator sets ability to start induction motor loads • CAT spec sheet sKVA ratings are expressed at 30% voltage drop • Competition often expresses sKVA capability at differing scales – 35% voltage drop – 90% sustained voltage Ratings Voltage Drop • sKVA capability of a generator set increases as % of voltage drop increases • Loads are adversely affected by high levels of voltage drop • ISO 8528-5 defines allowable voltage drop as follows: Voltage % Acceptance Class G1 General purpose applications. Lighting and electrical loads Class G2 Lighting systems, pumps, fans and hoists Class G3 Telecommunications equipment Class G3 Dataprocessing & Computer equipment -25 -20 -15 Agreed between manufacturer and customer Ratings sKVA Capability Comparison • sKVA ability must be compared with an equivalent measurement technique, at equivalent voltage drop, and with the same generator excitation. • Example: CAT 3456 Kohler Generac Rating Spec Sheet Value 35% voltage Drop w/ PMG 500 eKW 1205 sKVA 1815 sKVA 9 500 eKW 1350 sKVA 1350 sKVA 500 eKW 1300 sKVA 1300 skVA Ratings “90% Rated Sustained Voltage” • Cummins/Onan quotes sKVA at “90% Rated Sustained Voltage” • “Sustained Voltage” is a misnomer as a properly designed system will see a transient voltage dip and complete recovery as part of a motor starting event. Ratings Typical Motor Starting Scenario Motor Starting Load Applied to Generator 30% Voltage Dip 100% Normal Line Voltage Connected loads are subject to the full sequence and magnitude of voltage dip “90% Rated Sustained Voltage” • Cummins Application Manual T-030 defines Sustained Voltage Dip: “Following the relatively short (typically less than 10 cycles), steep transient voltage dip is a sustained period of voltage recovery as shown in Figure 65. The maximum motor starting kVA on the generator set Specification Sheet is the maximum kVA the generator can sustain and still recover to 90 percent of rated voltage” Level of voltage drop undefined Timeframe to the start of 90% sustained level undefined Potential Negative Results • No direct correlation can be made from 90% sustained voltage and % voltage drop • The two calculations are not equivalent measures of sKVA capability • Initial voltage drop, though short in duration, can have adverse effect on connected loads such as relays, VFD’s or computer equipment • Extended timeframe to full recovery of voltage can have adverse effect on connected loads such as motors and under voltage relays • Specifications should be influenced to % voltage drop