4 Remote I/O Digital Input Module 24 V Type 9471 ● For active 0 / 24 V signals ● 16 channels ● Without explosion protection for installation in safe areas ● Galvanic isolation between inputs and system ● Functions can be parameterized ● Two channels can be parameterized as frequency inputs or counters up to 20 kHz ● Conversion time 1 ms ● Status LEDs for RUN and ERROR ● Connection of the field cables with plug-in terminals ● Module can be hot swapped while powered up 09271E02 The inputs are passive voltage inputs for 0 / 24 V signals. All 16 channels have a common earth (0 V). Channels 14 and 15 are equipped with rapid comparators and can also be parameterized for frequency measurement or as pulse counters. In this operation mode, the input signals of channels 14 and 15 are also transferred into the data word for the digital inputs. Communication with the CPU & Power Module is achieved using the address and data circuits of the BusRail, which also contain the circuits for the power supply to the module. The interface of the Digital Input Module with the internal data bus of the BusRail is designed with redundancy. Safe Area General Catalogue 27.01.2006 4/1 4 Digital Input Module 24 V Type 9471 Selection table Version Description Ordering code Weight Without Ex-protection For intstallation in safe areas only. 9471/10-16-11 kg 0,267 The module may not be operated on a BusRail together with Ex i I/O modules. Technical Data Digital inputs, channels 0 to 15 Number of channels 16 Measurement dimensions Voltage Min. voltage for ON 13V Max. voltage for OFF 5V Max. voltage 30V Switching threshold approx. 8 ... 10 V Hysteresis approx. 2 V Internal resistance approx. 6 kOhm Min. pulse width of input signal channel 0 ... 15 as digital input approx. 1 ms channel 14 or 15 as frequency input or counter approx. 2 ms Channel 14 and 15 as frequency input or counter Max. switching frequency 20 kHz, only with push-pull sensor *) (at frequencies > 1 kHz the maximum line length decreases, e.g. at 5 kHz to approx. 75 m) *) the inputs must be switched to + 24 V and to 0 V. Schematic representation: 09272E00 Min. pulse width 25 ms Frequency input Measurement ranges 1 Hz ... 1 kHz, 1 Hz ... 20 kHz (parameterizable for each channel) Resolution Measurement range 1 Hz ... 1 kHz 0,05 Hz Measurement range 1 Hz ... 20 kHz 1 Hz Accuracy 0.02 % Counter 4/2 Counter control signal Start, Stop, Reset Counter range 0 ... 65535 General Catalogue 27.01.2006 4 Digital Input Module 24 V Type 9471 Technical Data Characteristic values Max. signal delay from digital inputs to internal bus from frequency inputs to internal bus channels 0 ... 15 as digital inputs approx. 1 ms channel 14 or 15 as frequency input or counter approx. 2 ms measurement range 1 Hz ... 1 kHz for measuring frequency f = 1 ... 35 Hz 2 ms + 1/f measurement range1 Hz ... 1 kHz for measuring frequency f = 35 Hz ... 1 kHz 34 ms + 1/f measurement range 1 Hz ... 20 kHz gate time 50 ms approx. 50 ms 200 ms approx. 200 ms 1s approx. 1 s from counter inputs to internal bus MTBF acc. MIL approx. 2 ms approx. 25 years Further parameters Invert input value ON, OFF (for all channels) Pulse width extension 0 s, 0,6 s, 1,2 s, 2,4 s (for channel groups) Gate time for frequency measurement range 1 Hz ... 20 kHz 50 ms, 200 ms, 1 s (channels 14, 15) Active edge for counter (channels 14, 15) positive (voltage ¤) negative (voltage ¥) Retrievable parameters Manufacturer, type, version, serial number Fault diagnostics Module faults • • • • • Internal primary bus fault Internal redundant bus fault No response Dissimilar module configuration Hardware fault Signal fault None Power supply Max. power consumption 1,4 W Max. power loss 3,8 W Engineering and mounting • • • • The module is without Ex-protection and for installation in safe areas only The module may not be operated on a BusRail together with Ex i I/O modules Maximum input voltage: 30 V Recommended fuse: 2 A fuse or current limitation each fieldstation Accessories see page 4/77 Dimension drawings see page 4/80 We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without notice. The illustrations cannot be considered binding. General Catalogue 27.01.2006 4/3