Transient Overvoltages and Distance Protection: Problems and Solutions A thesis submitted in fulfillment of the requirements for the degree of Master of Engineering by Research Leonardo Torelli B.Eng. (Hons) School of Electrical and Computer Engineering RMIT University November 2010 1/138 Table of Contents The Author ..........................................................................................................................5 Acknowledgement...............................................................................................................6 Declaration ..........................................................................................................................7 Abbreviations ......................................................................................................................8 Executive Summary ..........................................................................................................10 1 Introduction ..................................................................................................................11 2 Neutral Earth Resistor and Transient Overvoltages .....................................................14 2.1 Introduction ..........................................................................................................14 2.2 Method of Earthing...............................................................................................15 2.3 Review of the Existing Body of Knowledge ........................................................16 2.4 Design of the Experiment ....................................................................................25 2.4.1 The Software Package .................................................................................. 25 2.4.2 The Model .................................................................................................... 26 2.4.3 The experimental design............................................................................... 27 2.4.4 System Configuration ................................................................................... 29 2.4.5 Simulation Characteristics............................................................................ 31 2.4.6 Model Components ...................................................................................... 32 2.5 Simulation Results................................................................................................40 2.5.1 Simulation 1 : Unloaded Line - Fault at the End of the Line ....................... 41 2.5.2 Simulation 2 : Unloaded Line - Fault at the Beginning of the Line ............. 47 2.5.3 Simulation 3 : Capacitor Bank. Fault at the End of the Line....................... 50 2.5.4 Simulation 4 : Capacitor Bank. Fault at the Beginning of the Line ............. 56 2.5.5 Simulation 5 : Light inductive Load. Fault at the End of the Line............... 59 2.5.6 Simulation 6 : Energized 66/22kV Transformer Fault at the 66kV Bus. .... 62 2.5.7 Overvoltages and Traveling Waves.............................................................. 63 2.5.8 Impact of Time of Fault with the Overvoltage ............................................. 68 2.5.9 Overvoltage Response on Phase a ,b and c .................................................. 72 2.5.10 Overvoltage Harmonic Response ................................................................. 76 2.6 Conclusion............................................................................................................78 3 CVT and Transient Overvoltages .................................................................................80 3.1 Overview ..............................................................................................................80 2/138 3.2 The CVT Model ..................................................................................................81 3.3 Simulation Settings...............................................................................................84 3.4 Simulation Results................................................................................................86 3.5 CVT Conclusion.................................................................................................100 4 Distance Protection Scheme .......................................................................................101 4.1 Introduction ........................................................................................................101 4.2 MHO Characteristics Theory .............................................................................107 5 Transient Overvoltages and Distance Protection: Solutions ......................................111 5.1 Introduction ........................................................................................................111 5.2 Polarisation Techniques......................................................................................113 5.3 Polarising Techniques ........................................................................................117 5.4 CVT Techniques.................................................................................................119 5.5 Setting Advice ....................................................................................................121 6 Conclusion..................................................................................................................125 6.1 Research Findings ..............................................................................................125 6.2 Areas for Further Investigation...........................................................................127 7 References ..................................................................................................................129 Appendix A .....................................................................................................................133 10th International Conference on Developments in Power System Protection, March 2010, Manchester, UK -Abstract.....................................................................................133 Appendix B .....................................................................................................................134 Overvoltage Study –PSCAD Data ..................................................................................134 Appendix C .....................................................................................................................135 Overvoltage study – Steady State Voltage Data .............................................................135 Appendix D .....................................................................................................................136 Overvoltage Study- PSCAD Model ................................................................................136 Appendix E......................................................................................................................137 Voltage and Current as function of SIR ..........................................................................137 3/138 Appendix F......................................................................................................................138 CVT Study – PSCAD Data .............................................................................................138 4/138 The Author My name is Leonardo Torelli. I have been working for fourteen years in power industry. I have worked in Italy in Utilities and in Australia in consulting firms. I am currently working at Hydro Tasmania Consulting and involved in Protection and Power System Analysis projects. It is not a surprise that the topic of this research goes across these two areas of electrical engineering. The aim of this study was, indeed, proving how important is the knowledge of power system analysis for Protection Engineers. As result of this study, I presented a paper at the 10th International Conference on Developments in Power System Protection, March 2010, Manchester, UK This research has given me the opportunity to expand my skills, challenging my knowledge and improved my analytical skills. I am committed to use this experience at RMIT University as starting point for further studies. 5/138 Acknowledgement I thank Dr Selva Moorthy for his contribution, support and expert advice during this study. I have appreciated his sincere interest in my professional development and support of my personal life. Dr Moorthy’s feedback helped me to stay in line with my schedule and achieve the completion of this research. I would like to thank my former and existing colleagues at Hydro Tasmania Consulting for their encouragement during this journey. Last, I would like to thank my three beautiful children, my family and friends for their warm and enthusiastic appreciation of my work. . 6/138 Declaration I certify that except where due acknowledgement has been made, the work is that of the author alone; the work has not been submitted previously, in whole or in part, to qualify for any other academic award; the content of the thesis is the result of work which has been carried out since the official commencement date of the approved research program; and, any editorial work, paid or unpaid, carried out by a third party is acknowledged. …………………………………. Leonardo Torelli Date 7/138 Abbreviations The following terms are used in this thesis: HVDC - High Voltage Direct Current MHO relay - Distance relay with circular characteristic which passes through the origin of the R-X plane NER - Neutral Earth Resistor NEX - Neutral Earth Reactance PSCAD-EMTDC - Power system software package SIR- Source Impedance Ratio TRV- Transient Recovery Voltage 8/138 9/138 Executive Summary This thesis investigates the relationship between transient overvoltages that follow a fault and the functionality of the digital distance protection. The study is conducted in a 66kV subtransmission network with a neutral earth resistor as method to earth the power system. The results of this study show that fault current limitation and consequent reduction of the thermal stress and aging of the equipment are successfully supported by modern digital distance relays. This thesis begins by performing an extensive power system analysis on ground fault transient overvoltages. The study is conducted by using the PSCAD-EMTC software package. The results of this analysis are discussed to determine the impact of a disturbed voltage signal fed to the distance relay, with particular attention to the polarisation and CVT transient mitigation techniques as implemented by digital distance relays. Finally, this research provides recommendation for the design of the protection settings of the distance relay. This thesis supports the implementation of digital distance protection relays on short lines, lines with ineffective grounding system and weak impedance source as a valuable alternative solution to the differential protection scheme. 10/138 1 Introduction Power systems are designed and operated to supply electrical energy to the customers in a safe, reliable and economical way. Faults represent one of the main challenges for the power system. Among all the types of faults, phase to ground faults represent the majority of the events, with records between 80 to 90 % of all faults. Ground faults are generated from insulation breakdown, atmospheric conditions and accidental contacts of birds or branches of trees with power lines. Therefore, these faults are transitory in nature. During this post fault initial period, the voltage change dramatically from a pre fault steady state value to a post fault steady state value. In addition, the voltage signal is disturbed by higher and lower frequency components. Therefore, transient overvoltages could affect the accuracy of the protection scheme. At the same time, the protection scheme should be able to operate in a fast manner to reduce the risk to personnel, equipment damage, and system stability. It is evident that achieving a short operating time and high accuracy of the protection scheme represents a major challenge for protection relay manufacturers and protection engineers. This research investigated the performance of modern digital distance relay during the transient overvoltages period which follows a ground fault. Initially, this study focused on power system analysis to have a clear understanding of the transient overvoltage phenomena. The overvoltage study was conducted using PSCAD-EMTC software package. The investigation was performed by using the experimental method that involves the scientific manipulation of the variables involved in the process and the systematic study of the behavior of the system. The study was conducted on a radial system using a neutral earth resistor, NER, as a method to earth the 66 kV network. However, the theory and the results 11/138 obtained are largely applicable to higher transmission voltages and in power systems earthed via a neutral earth reactor, NEX. Following the transient overvoltages study, the research focused on the performance of five modern digital distance relays. In summary, the project objectives are as follow: Determine the characteristics of transient overvoltages generated by a phase to ground fault. This work should highlight the main factors that influence the voltage disturbances Analyze the characteristics of modern digital distance relays to determine if the transient overvoltages could affect the accuracy ad operating time of the protection relay Establish a method to predict the performance of the distance protection relay following a phase to ground fault Elaborate a list of setting advice that could enhance the application of the distance protection relay in relation to the transient overvoltages disturbance This study aimed to validate the existing body of knowledge, highlight new insight and views and determine new findings. The research is organised in six Sections: Section 2 -NER and Overvoltage Section 3 - NER and Capacitor Voltage Transformers Section 4- NER and Distance Protection Section 5- Distance Relay Applications 12/138 In the last part of this study, Section 6, research conclusions and recommendations for areas of further investigations are also provided. 13/138 2 Neutral Earth Resistor and Transient Overvoltages 2.1 Introduction This Section investigated the influence of the neutral earth resistor on transient overvoltages. The study focused on a 66kV radial overhead subtransmission system. The expected deliverables of this section are: Documenting the transient overvoltage phenomena under a series of system configurations and a set of neutral earth resistor sizes using PSCAD-EMTC transient software package Determining whether the neutral earth resistor has particular and/or peculiar effect on the overvoltage that may be considered in design and planning of the power system. The research only focused on the impact of the resistor under ground faults. Therefore this work did not pursue the study of overvoltages during normal switching condition and lighting phenomena. The method and the technologies to control the overvoltage and the impact of the size of the resistor to the overall insulation coordination were also excluded from this study. 14/138 2.2 Method of Earthing The earthing of the power system involves the implementation of an electrical connection between the neutral point and the ground. Connection of the neutral to the earth can be done in several methods: Solidly earthing Neutral earth resistor, NER Neutral earth reactance, NEX Compensated earthing Ungrounded The type and size of the earthing system will affect the following system parameters [1-4]: Fault current Personnel safety System Protection Steady state overvoltage during ground faults Transient overvoltage during ground faults Thermal stress on the equipment Effect on communication circuit Harmonic current on neutral connection System stability 15/138 System availability Operating procedure Equipment selection Cost While the power system is operating in normal condition, the method of earthing is not relevant. The method and design of the system earthing becomes critical during a ground fault. In this condition the fault current magnitude and fault duration will affect critical elements of the power system. For a 66 kV subtransmission network, system earthing has developed in different ways in different parts of the world[2]. Generally, English speaking country such as Australia, England and America prefers solidly earthed or low impedance earthing. North European Countries, Italy and France have instead a good experience with compensated earthing using the Petersen Coil at the Substation. High Impedance grounding or isolated earthing is instead limited to a relatively smaller part of systems. It is also noted that the value of the impedance is not consistent among utilities. Moreover, some utilities use a resistor and others use a reactor. For example, In Australia, SPAusnet, Ergon and Energex use a reactor. Jemena and many industrial consumers often prefer a resistor. 2.3 Review of the Existing Body of Knowledge Overvoltages are a common disturbance in power systems. The increase of the system voltage can create malfunction, damage of the equipment and consequently disruption of the service[5]. 16/138 Transient overvoltages are produced by sudden changes in the electrical system as caused by lightning, faults or switching [6]. The method of earthing system does not have any effect on the system during normal operation [4]. However, during the transient period the method of earthing has an impact on the system response and magnitude of the transient overvoltage. Power demand, power generated and system configuration vary continuously with time. Therefore the power system always changes from one steady state to another steady state. In this very short periods current and voltages may reach dangerous values for the equipment and the insulation of the system. Overvoltages are often classified according to their duration in two groups [7, 8]: Temporary Overvoltage above 200 ms Transient Overvoltage below 200 ms Alternatively, overvoltages can be classified according to their origin: External overvoltage caused by atmospheric phenomena as lighting and electrostatic charges Internal overvoltage generated within the power systems This type of disturbances are also classified according to the frequency of the two major overvoltage components [9]: Power frequency overvoltage Natural frequency overvoltage of a short duration superimposed on the power frequency overvoltage The sum of the power and natural frequency overvoltage is the voltage recorded in the field. This voltage is commonly defined as a transient overvoltage. 17/138 The overvoltage component with a power frequency does not theoretically have any decaying component and it often termed as steady state overvoltage. Instead, the short duration component usually decays in less than 100 ms. Above all; the magnitude of the overall overvoltage is of greatest interest for the impact on the planning, design and financial cost of the power system. A fault in the power system can be represented and analysed as the closing of a switch in the electrical system. This change in the power system develops a new redistribution of stored energy in the system [6]. Phase to ground faults represent the majority of faults in the power system. These types of faults are produced by atmospheric condition, mechanical breakdown of the insulation, objects such as birds or branches or trees in contact with the overhead line and poles or structures. Recent statistics conducted by protection relay manufacturers found that these types of faults represent between 80 and 90 % of the faults in a given power system [3, 4, 10]. A large majority of these faults involving overhead lines also have transient characteristics and, therefore, self extinguish in a short period of time. When a phase to ground fault occurs, an overvoltage can be measured in the system during the fault itself or after clearing [10]. The maximum transient overvoltage is obtained by adding the peak of the temporary overvoltage at power frequency overvoltage at 50Hz sinusoidal pattern to the transient overvoltage which usually has a higher frequency. This relation is based on the worst case scenario with the assumptions that the two components will have maximum peak values at the same time. This is plausible because of the different time frames. Power frequency peak lasts long in the context of high frequency oscillations. The magnitude of the power frequency overvoltage is strictly related to the characteristic parameters of the system. This overvoltage can be calculated using the symmetrical components theory. Considering some system simplification as necessary, this engineering technique produces accurate results. The fundamental frequency voltage, which is also referred to the steady state overvoltage, is absent 18/138 in a solidly earthed system. In an ungrounded system the overvoltage reaches the maximum value of √3=1.732. In this latter case, the phase to ground voltage is equal to the phase to phase voltage. Application of the neutral earth resistor as a method of grounding increases the fundamental frequency overvoltage from none to a maximum of 1.732 for the insulated system. Between these two boundaries of the overvoltage measured in the system, the institution of Electrical and Electronic Engineers established an arbitrary limit of the overvoltage measured, which is named “effective grounding” [11]. The effective grounding term indicates that, during a ground fault, the voltage on the healthy phases will not exceed 80 % of the maximum line to line voltage. The term “effective grounding” is commonly used in the power industry as a point of reference for the design of the earthing system and sizing of the neutral impedance. Therefore a power system can be “effectively grounded” or “ineffectively grounded”. In other words, in a 66kV subtransmission system, the phase to ground voltage during fault condition will be: 19/138 V Nominal Vph-ph=66kV Vph-g = 66kV/√3=38.1 kV Solidly Grounded System Vph-g fault= 66/ √3 = 38.1 kV Effective grounding System Vph-g fault= 66 * 0.8= 52.8 kV Ungrounded System Vph-g fault= 66kV The main advantage of having an effective grounded system is limiting the overvoltage magnitude which has a direct impact on the cost of the system. For instance, the required insulation medium can be reduced with direct benefits to the cost of the electrical equipment. This advantage is a key factor for the design of subtransmission and transmission power systems. The effective grounding system is nowadays considered the best compromise between reducing the phase to ground fault and keeping the overvoltages at a reasonable level. Therefore the effective grounding is the preferred solution for the 20/138 higher voltages in countries where the power system is grounded via an impedance[4] . How to achieve an effective grounded system? IEEE “Recommended Practice for Grounding of Industrial and Commercial Power Systems” states the required system conditions: The system must be” grounded through a sufficient low impedance such that for all system conditions the ratio of zero sequence reactance to positive sequence reactance is positive and equal or less than ( X0/X1≤3) and the ratio of zero sequence resistance to positive-sequence reactance is positive and less than 1( R0/X1<1) These system conditions, if satisfied, maintain the power frequency overvoltage within 80 % of the nominal voltage (ground reference) Instead, to limit the natural frequency overvoltage the system conditions are: R0 XC 0 .Total zero sequence resistance less than one third total zero 3 sequence reactance. This condition requires that the current flowing through the neutral earth resistor shall be at least 3 times the charging current per phase of the system[4] Non compliance with this system condition could lead to dangerous faults with subsequent restrikes and overvoltages, usually named as arcing faults R 0 2 X 0 Zero sequence impedance system resistance at least twice the value of zero sequence reactance. This conditions shows that grounding the power system through a resistance contains transient overvoltages 21/138 X0 20 , which is inherently met in resistance grounding and with delta X1 star power transformers [12], unless the power system is earthed via a large reactor From the system conditions stated above, it can be derived that the size of neutral earth resistor or neutral earth reactor is not critical by itself for the magnitude of the overvoltage. The relation with other system parameters determines the magnitude of the overvoltage. The above conditions also highlights that unplanned increase of the size of the resistor will increase the value of the overvoltage due to the fault clearing restrike. Besides, the system conditions show that the reactance of the overall zero sequence network shall be inductive and not capacitive. These system conditions aim to limit transient overvoltages and, at the same time, reduce the phase to ground fault current between 10 and 25 % of the steady state fault current [9]. The lower level is dictated by the minimum current requirement for relay operation. Nowadays with modern digital relays, this requirement could be reconsidered. The 25 % upper level takes into consideration the resistor cost in comparison to the reactive option. Plots of power frequency overvoltage following faults as a function of different system parameters or system parameters or ratios of system parameters have been published and are available in the existing literature[9]. Existing studies on overvoltage and impact of the neutral earth resistor on the measured overvoltages are based on field testing, software simulation and theoretical analysis. First researches on transient overvoltages during faults were conducted before the Second World War. Overvoltages were analytically determined and tested using 22/138 miniature models[9] . Maximum peak voltages were recorded mainly between 3 and 4 pu with 20 % above 4 pu. The researchers also considered current chopping produced by the circuit breakers and restrike phenomena known as transient recovery voltage, usually abbreviated as TRV. Overvoltage calculations and tests using miniature system have also been conducted by other researchers[6, 8]. These papers provide a complete explanation of the maximum overvoltage in relation to system parameters and formed the basis for future IEEE standards. Measurements of overvoltages following a fault were performed in the distribution network in the 10kV Croatian distribution network[13]. The system was earthed using the NER. Maximum overvoltage factors are below 2 pu and minimum variations are recorded for different values of the resistor. A transient software program was used to validate the results. It is possible to determine the maximum transient overvoltage by applying the RLC circuit analysis and the use of symmetrical components. [14]. Generalized plots which took into consideration the damping effect of the resistor were also produced. An overall indication of the effect of the resistor is defined by: R 0 2 X 0 circuit is oscillatory R 0 2 X 0 critical damped R 0 2 X 0 over damped Recent studies usually apply the traveling waves theory. In line with this theory, modern transient software packages also avoid the use of lumped elements [15]. Lumped elements representation is adequate for steady state analysis but give inaccurate results in transient studies. In the latter studies, where travel time of the electromagnetic waves and the energy exchange between capacitance and inductance must be taken into consideration, traveling waves theory is the most 23/138 accurate method for the computation of the overvoltages along the transmission line. Fault generated traveling waves propagates not only on the overhead line to line. but also line to earth with different propagation parameters [16]. A phase to ground fault can be represented as disturbance that generates current and voltage traveling waves on a subtransmission line. At each point of discontinuity the traveling waves will be refracted and reflected according to the surge impedance characteristic of the line [17].It is possible to represent the large number of forward and backwards waves and determine the maximum overvoltage generated as a function of time by using the Bewley Lattice diagram. However, there are also some other considerations which must be dealt with which include mutual coupling with other conductors and wave shape distortion experienced along the transmission line. It is important to point out that overvoltage studies and traveling wave application mainly focus on switching and lightning transients [16]. However, overvoltages produced by switching episode can be used as a reference for this type of study. To conclude, what overvoltage magnitude can be developed under a ground fault? From the existing literature it can be inferred generally that the maximum overvoltages following a phase to ground fault are below 3 pu [18-20]. Maximum overvoltage can instead reach 4.1 pu with trapped charges on the line as in the case of switching a capacitor bank connected on the line [19]. 24/138 2.4 Design of the Experiment 2.4.1 The Software Package Usually, software packages are used to facilitate transient overvoltage studies. In fact, these investigations involve complex and time consuming computation that can be achieved with sufficient accuracy with software packages. PSCAD-EMTDC is a state of the art software package developed using the wave propagation theory first published by DR Hernmann W Dommel in the transaction of IEEE Power Apparatus and Systems in 1969. based on this paper another two transient analysis software packages well known in the industry, EMTP and, later, the ATP software package [21] were developed. PSCAD is a very powerful and flexible graphical interface that uses the EMTDC simulation program. The first version of PSCAD was produced by Denis Woodford to model and simulate the high voltage DC system in Canada. The software is now developed and maintained by the Manitoba HVDSC Research Centre and is continually upgraded to incorporate the latest validated research. The software allows one to model an electrical circuit, run a simulation, analyze the results and manage the data information in an efficient way. The software package is provided with an equipment library, but also allows the creation of new models and building a personal equipment library. It is used by consulting engineers, equipment manufacturers and laboratories for planning and design of power systems. Typical projects involve transient stability, dynamic stability, relay coordination, transformer saturation, insulation coordination studies, HVDC studies, harmonic studies, power electronics studies and optimisation of controller parameters. Further information is located on the website http://www.pscad.com 25/138 All PSCAD software editions must be licensed except for the student license. The student license version, which was used for this research, contains a limitation of 15 electric nodes. However, considering the purpose of this study, PSCAD was still found suitable. PSCAD-EMTDC was selected for its performance, the graphical interface and the technical support provided by Application Engineers at Manitoba HVDC Research Centre. 2.4.2 The Model The system modeled is a basic radial subtransmission system. The model contains a 220 kV source, one 220/66 kV transformer and one overhead line. Although power systems are more complex and contain more components, the overhead line and the power transformer represent the backbone of the system and have the major influence in the transient overvoltage. It also contains the part of the system that is affected by the fault current. This system reduction is in line with previous studies [22]. This type of configuration also allows keeping at minimum the required number of nodes and the use of PSCAD student license version. The measured overvoltage can be represented as the superposition of the temporary overvoltage at power frequency and the natural overvoltage component at higher frequency. Power Frequency V + Natural Frequency V = Measured Overvoltage PSCAD software was used to measured the absolute value of the instantaneous peak of the three phase to ground voltages. Measurement was conducted at the fault location using the maximum/minimum recorder function offered by PSCAD. The maximum value of the three phases was selected for the analysis. 26/138 Steady state overvoltage for a given value of the neutral earth resistor was calculated by applying symmetrical components theory. Factor K2 and K0 were used to determine fault currents and steady state overvoltages[4]. K2 Z2/Z1 K0 Z0/Z1 Where: Z1= Positive system impedance Z2= Negative system impedance Z0= Zero system impedance The factor K0 gives us a prompt understanding of the power frequency overvoltage on the healthy phases during a ground fault. The factor K2 is assumed to be 1. If the fault occurs close to the generator the factor K2 may increase to 1.4 [4]. Knowing the steady state overvoltage and the total overvoltage, the transient component can be calculated with: Natural Frequency V = Measured Overvoltage - Power Frequency V 2.4.3 The experimental design The most relevant factors that influence the overvoltage magnitude during phase to ground faults are as follow: 27/138 Method of earthing Type of fault System configuration Number of earthing points and location in respect to the fault location Electrical parameters of the equipment Size of the neutral earth resistor Location of the fault Time of the fault applied Type of subtransmission network as underground cables and overhead lines have different electrical characteristics Type of overhead line Length of the line Fault impedance Each variable was analyzed in order to determine the most critical and relevant factors to be used in this research. In the end, the study was based on the following five factors: System configuration Type of faults Size of the neutral earth resistor 28/138 Location of the fault Time of the fault 2.4.4 System Configuration Four system configurations were selected. These configurations were considered the most likely configurations to produce the highest overvoltages during a ground fault [5, 14]: #2 R esis #1 + RL T 66kV Subtransmission Line Figure 2.1: Overhead line with no load at the end of the line model T 66kV Subtransmission Line #2 Resis #1 + RL 30 [MVAR] Figure 2.2: Overhead line with capacitor bank at the end of the line 29/138 T 66kV Subtransmission Line #2 Resis #1 + RL 2.0 [MVAR] Figure 2.3: Overhead line with light inductive load at the end of the line #2 #1 #2 Resis #1 + RL Figure 2.4: 66/22kV transformer connected directly to the secondary side of the 220/66kV transformer Type of faults Phase to ground fault and phase to phase to ground fault. Neutral earth resistor The sizes of the resistor selected cover the entire spectrum between a solidly earthed system (no resistor installed) and ungrounded system (infinite resistor installed). 15 resistor sizes were selected. In particular, the data was selected between K0=0 to K0=10 as the research focused on low resistance grounding. System response was assumed to be linear between adjacent samples. Location of the fault 30/138 Faults were simulated at the beginning and at the end of line. Time of fault Considering the symmetry of the alternating voltage cycle, the samples were selected only on one half cycle. As one semi cycle at 50Hz takes 10 ms, 21 sample spaced 0.5 ms apart were selected. Line length Line lengths were set to 100, 10 and 0.2 km. These line lengths are based on the minimum, maximum and typical line length in the Victorian Network. Typical subtransmission lines vary between 10-20 km in the urban area around Melbourne and increase to 30-40 km in the country area. In Victoria the maximum line length is about 80 Km. The line length of 100 km reflects the need to investigate the system in the worst case scenario. 2.4.5 Simulation Characteristics In this study no randomization factor is applied as the chance of biasing the results in a software simulation is considered negligible. Therefore, simulation studies were conducted in a logical order to maximize the efficiency of the work. The simulations were conducted using PSCAD multiple run function. This software tool allows completion of complex studies in an efficient manner by manipulating variables sequentially and automatically. PSCAD Multiple Run tool can run and modulate up to six variables. 31/138 Maximum instantaneous voltage peak was recorded for each run and on each phase. Only the maximum overvoltage among the three phases was selected for the maximum overvoltage record. Duration of the run time was set to 0.6 s with fault start at 0.4 s plus selected time delay. The end time of the fault was 0.1 s with clearing fault at the first zero crossing intersection of the fault current. According to the Nyquist_Shannon Sampling Theorem, to avoid aliasing and incorrect representation of the selected variable, sampling rate should be at least double of the variable frequency to be represented. PSCAD recommends that 50µs for the time step of the process and computation would be sufficient. However, time step resolution was reduced to 20 µs to capture transient components up to 25 kHz [22]. Sampling rate=20 µs Frequency rate= 1/T=106/20= 50kHz 2.4.6 Model Components Source The source represents the power system which is upstream the 220/66 kV power transformer in the substation. The voltage source selected from the PSCAD library enabled to specify the positive, negative and zero-sequence impedance. The impedance value is selected to produce a three fault current of 30 kA on the 220 kV bus at the substation. Positive impedance is equal to negative impedance. Zero impedance was set to be equal to the positive sequence impedance to allow for a phase to ground fault level equal to the three phase fault level. The X/R ratio was set to 10. 32/138 The control system for the output voltage was set using the “Fixed Control” function offered by PSCAD software package. Through several trial and error experiments this type of control produced a model behavior very similar to an “infinite bus”. This setting enhances the robustness of the source model in respect to disturbances on a lower voltage level. It is assumed that the impact of the overvoltage on the 66 kV radial line is limited on the higher transmission network. In summary: Source Type = Three Phase Voltage-Source Model 3 MVA = 100 MVA Vph- Vph = 220 kV Frequency = 50 Hz Time constant = 0.06 s Z1=Z2=Z0= 4.23 Ohm Z1 angle= 84.289 deg Voltage Fixed Control Es = 220 kV Ph = 0.0 deg Frequency = 50 Hz Transformer The two winding 220/66 kV power transformer connects the transmission system to the subtransmission system. 33/138 Often substation have more than one transformer operating in parallel with the bus tie on the 220 kV closed and on the 66 kV bus open or closed according to system requirement, the fault level in the system and the rating of the equipment. To simplify the study the model represents only one transformer. Winding connection of the transformer is delta on the HV side and star on the LV side. Tap changer operation is disabled The transformer is represented in PSCAD according to the classical approach of the transformer theory. Magnetising current is represented as well as core saturation placed on the HV side. In PSCAD the HV side is the closest winding to the core of the transformer. Hysteresis losses in the transformer core are included. Copper losses are disabled to reduce the number of nodes in the system. Considering that a typical X/R for a power transformer of 100 MVA and 220/66 kV is above 30, this simplification was considered acceptable. TRANSFORMER DATA: 3 Phase 2 Winding Transformer MVA Rating: 100.0 MVA Freq= 50 Hz, V ph-ph primary= 220 kV Vph-ph secondary= 66kV No Load Losses= 0.01 pu 34/138 Copper Losses=0.0 pu. Positive Sequence Reactance= 0.15 pu. Saturation enabled simulated on primary winding Air core reactance= 0.3 pu In Rush Decay Time Constant= 0.03 pu. Knee Point Voltage: 1.25 pu Time to release Flux Clipping=0.1s Magnetising Current= 0.02 pu. Overhead line In electromagnetic simulation studies there are two main methods to represent transmission lines[21]:. Simplified studies generally rely on the PI Section model Distributed transmission line, which is most suited for transient line response modeling using a digital computer. This method was used for this study PSCAD operates applying the traveling wave theory but also implementing mutual coupling between conductors and wave shape attenuation produced by the transmission line. Transmission lines under PSCAD transient software packages are modeled using one of the three traveling wave models: Bergeron Model Frequency Dependent Mode Model 35/138 Frequency Dependent Phase Model The Frequency Dependent Phase Model was selected for this study as is the most accurate model. This model is a distributed RLC traveling wave model, which incorporates the frequency dependence of all parameters in the model. This model is recommended by the PSCAD User’s Guide for this type of study. The overhead line parameters are based on a typical 66 kV line as represented in Victoria. Conductor Data 400 mm2 aluminum Conductor Resistance= 0.071 Ohm/km Conductor Geometric Mean Radius 0.00982 m Capacitor bank The capacitor bank is implemented in Simulation 3 and 4. The capacitor bank is connected at the end of the line to produce maximum peak value of the system response during the transient period. The capacitance value was set under the assumption that the load on the overhead line is 60 MVA with a power factor of 0.707. Load Current = S/ ( √ 3 * V ) = 60 *106 / √ 3 * 66000 )= 524.8 A P = S * PF = 52.42 MW If PF is 0.707 Power angle á= 45 degrees 36/138 P=Q = 42.42 MVAR The selected size for the MVAR is set to correct the power factor above 0.95 Q/P= tan ( cos-1 PF ) = tan ( cos-1 0.95 )= 0.3287 Q final= P * 0.3287 = 13.94 MVAR Q capacitor bank = Q load- Q final = 42.42- 13.94= 28.48 MVAR The capacitor bank rating is set to 30 MVAR and connected in star to the network. The star point of the capacitor bank is ungrounded Light Inductive Load The rating of the inductive load is 2 MVAR and a resistive load of 0.2 MW. The load is star connected and is ungrounded. The load size is designed a very light 66 kV subtransmission load or a substation at the end of the line with no load and supplying only the substation auxiliary services. 66/22kV Transformer Simulation 6 is configured to simulate the 220/66 kV transformer that feeds a 66/22 kV transformer within the substation. The 66/22 kV transformer rating is 30 MVA. For simplicity the internal parameters of the transformers are set as the 220/66kV transformer. 37/138 TRANSFORMER DATA: 3 Phase 2 Winding Transformer MVA Rating: 30 MVA Freq= 50.0 Hz, V ph-ph primary=66 kV Vph-ph secondary= 22 kV No Load Losses= 0.1 pu Copper Losses=0.0 pu. Positive Sequence Reactance= 0.15 pu. Saturation enabled simulated on primary wounding Air core reactance= 0.3 pu In Rush Decay Time Constant= 0.03 pu. Knee Point Voltage: 1.25 pu Time to release Flux Clipping=0.1 s Phase to Ground Fault PSCAD fault logic enables to specify the type of fault, time of fault and fault duration. 38/138 Phase to ground and phase to phase to ground the fault were simulated. Current interruption was simulated at 0 current crossing to avoid any overvoltage related to magnetic field being trapped in the circuit. This type of overvoltage is usually referred as “ current chopping”[3]. Fault resistance is set to zero to evaluate the impact of the neutral earth resistor by itself. In summary: Fault Type = Phase to ground and phase to phase to ground Fault start =0.4 s to fault 0.410 s Fault length =0.1 s Fault ON resistance = 0.01 ohm Fault OFF resistance = 106 ohm Current Chopping limit= 0 kA 39/138 2.5 Simulation Results Simulation results are organized according to the six system configuration and related simulations. Simulation results data is attached in Appendix B. Each simulation result Section contains two graphs. The first plot summarizes the main objective of this investigation which is the maximum overvoltage as a function of the reduced fault current. The fault current was calculated by applying the symmetrical components theory as illustrated in Appendix B. The second plot highlights the specific weight of the transitory overvoltage component in respect to the steady state overvoltage component. Power frequency overvoltage was subtracted from the measured overvoltage only if the recorded maximum overvoltage took place during the fault and not at fault clearing. After fault clearing, the power frequency overvoltage can be considered absent as the three phases are now connected to a symmetrical voltage source. Additional investigations were also performed on the following topics: Overvoltages and traveling waves Influence of the fault time Overvoltage response on healthy and faulty phases Frequency spectrum analysis 40/138 2.5.1 Simulation 1 : Unloaded Line - Fault at the End of the Line TABLE 2-1 – SIMULATION 1 RESULTS Line Length= 100km Max Measured V from NER PSCAD (Ohm) (kV) 0 126.216 5 124.898 10 126.607 15 128.809 20 128.021 25 129.201 30 131.007 35 131.669 40 132.052 45 132.457 50 132.599 100 103.588 550 112.552 1000 122.539 1000000 140.632 Iph-g with NER/ Iph-g solidly earthed 1.000 0.977 0.946 0.909 0.867 0.824 0.782 0.740 0.700 0.663 0.628 0.394 0.082 0.045 0.000 0 5 10 15 20 25 30 35 40 45 50 100 1.000 0.882 0.705 0.561 0.457 0.383 0.328 0.286 0.253 0.227 0.206 0.105 90.447 99.668 100.711 99.279 99.031 96.724 96.071 95.465 95.437 95.512 95.526 94.901 K0 1.0 1.1 1.3 1.5 1.8 2.0 2.3 2.6 2.9 3.2 3.6 6.8 36.0 65.4 65217.4 V Meas / Power Nominal Frequency Voltage V (pu) 2.342 1.002 2.318 1.103 2.349 1.204 2.390 1.296 2.376 1.378 2.398 1.448 2.431 1.507 2.443 1.555 2.450 1.596 2.458 1.629 2.461 1.656 1.922 1.763 2.089 1.757 2.274 1.747 2.610 1.736 Line Length=10km 1.0 1.678 1.7 1.850 3.0 1.869 4.3 1.842 5.7 1.838 7.1 1.795 8.5 1.783 9.8 1.772 11.2 1.771 12.6 1.772 14.0 1.773 27.9 1.761 41/138 1.006 1.412 1.647 1.745 1.783 1.797 1.802 1.802 1.800 1.797 1.794 1.771 Natural Frequency V (pu) 2.342 2.318 2.349 2.390 2.376 2.398 2.431 2.443 2.450 2.458 2.461 1.922 0.332 0.527 0.873 1.678 1.850 1.869 1.842 0.054 -0.003 -0.019 -0.030 -0.029 -0.025 -0.021 -0.010 Max Measured V from NER PSCAD (Ohm) (kV) 550 101.180 1000 107.676 1000000 120.050 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1000000 76.644 86.617 92.223 95.204 96.245 96.587 96.206 96.501 96.337 96.163 95.991 94.486 96.337 102.533 118.593 Iph-g with NER/ Iph-g solidly earthed 0.019 0.011 0.000 1.000 0.806 0.564 0.415 0.324 0.264 0.223 0.192 0.169 0.151 0.136 0.068 0.012 0.007 0.000 V Meas / Power Nominal Frequency K0 Voltage V (pu) 153.0 1.878 1.740 278.1 1.998 1.736 278041.7 2.228 1.736 Line Length=0.2km 0.9 1.422 2.3 1.607 4.4 1.711 6.5 1.767 8.6 1.786 10.8 1.792 12.9 1.785 15.1 1.791 17.2 1.788 19.3 1.784 21.5 1.781 42.9 1.753 236.1 1.788 429.2 1.903 429200.4 2.201 Natural Frequency V (pu) 0.137 0.262 0.491 1.011 1.358 1.455 1.478 1.822 1.817 1.810 1.804 1.798 1.792 1.788 1.763 1.738 1.735 1.736 1.422 1.607 0.257 0.288 -0.036 -0.025 -0.025 -0.013 -0.010 -0.008 -0.007 -0.010 0.050 0.167 0.464 Configuration 1- Fault at the of the line- No load- Measured Overvoltage 3.0 Overvoltage ( pu) 2.5 2.0 L=100km L = 10km L= 0.2km 1.5 1.0 0.5 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 Ifault/I ph-g solidly earthed (pu) Figure 2.5: Configuration 1 Measured overvoltage result 42/138 0.2 0.1 0.0 The maximum overvoltage reaches 2.5 times the value of the normal phase to earth voltage. Maximum overvoltage below 3.0 pu is in line with existing literature[6, 20]. The maximum overvoltage was recorded with the longest subtransmission line which is 100km. This characteristic is common with previous studies[23] and tests with a miniature circuit. It is also in line with all the other simulations of this study. The characteristic is due to the larger line capacitance and inductance which are proportional to the length of the line. As the capacitance increases, the energy stored in the electric field increases producing more severe transient phenomena upon a sudden change in the power system. The simulation results show that the maximum recorded overvoltage plots have a consistent pattern across the neutral earth resistor spectrum. The increase of the resistor size slightly increases the measured overvoltage due to the highest contribution of the power frequency overvoltage. A high maximum overvoltage is recorded once the resistor size is increased to reduce the phase to ground fault below 0.1 pu. The high value of transient overvoltage is due to the effect of transient phenomena after fault clearing, also called transient restrike, as is also shown in Figure 2.5. As we increase the size of the resistor and the fault current decreases, the maximum overvoltage is recorded during the fault. The restrike is due to the excessive increase of the neutral earth resistor. In other words the ratio R0/Xco becomes well above the recommended limit of 1/3[9]. This factor was found to be more relevant of the positive damping provided by the resistor. As per Reference [14] , the increase of the resistor should damp the transient overvoltage as R0>2ZO Please also note that the shift of the peak voltage from the fault clearing time to the fault period takes place first in the shortest line system configuration, then with line length of 10km and last to the longest subtransmission line. This behavior can be 43/138 explained using the factor K0=Z0/Z1. The implementation of the resistor will increase Z0. As the neutral impedance has a bigger impact on the factor K0, in the shortest line the expected steady state overvoltage has a bigger increase The results show that the maximum overvoltages recorded in the simulation with a line length of 10km are similar to the results obtained from the simulation with a line length of 0.2km. This characteristic is recorded throughout the study. We can explain this characteristic by referring to the overvoltage plots as function of system parameters of IEEE standards[18]. The different line length does not have a particular impact on the Xco/X1. For both line lengths, the ratio is larger than 100 . Beyond this value the expected overvoltage is considered constant.[6]. Xsource= 0.0087 pu X Tx= 0.15 pu X line=0.0088 Ohm/km C= 9.4 nF/Km Line length 10km Xc = 1/(2Ð f C )/ 10 = 1/( 2* Ð 50 * 9.4 10-9 )/ 10 = 33879 Ohm X1= Xsource+ Xtx + X line = 0.0087 + 0.15 + 0.088 ( 10km) = 0.2467 pu Z base = 484 Ohm Xc in pu = Xc value/ Z base= 33879/484= 70 pu Ratio Xco/X1= 70/ 0.2467= 283.7 Line length 0.2km 44/138 Xc = 1/(2Ð f C )/0.2 = 1/( 2* Ð 50 * 9.4 10-9 )/ 0.2 = 1693996 Ohm X1= Xsource+ Xtx + X line( 0.2km) = 0.0087 + 0.15 + 0.0018 = 0.1605 pu Z base = 484 Ohm Xc in pu = Xc value/ Z base= 636/484= 3500 pu Ratio Xco/X1= 3500/ 0.1605= 21806 Line length 100 km Xc = 1/(2Ð f C )/0.2 = 1/( 2* Ð 50 * 9.4 10-9 )/ 100 = 3387.9 Ohm X1= Xsource+ Xtx + X line( 100km) = 0.0087 + 0.15 + 0.88 = 0.1605 pu Z base = 484 Ohm Xc in pu = Xc value/ Z base= 3387.9/484= 7 pu Ratio Xco/X1= 7/ 0.1605= 43.6 The Xco/X1 ratio for line length of 100km is also proved to be below 100. Therefore, the line will produce a higher overvoltage. 45/138 Configuration 1- Fault at the of the line- No load- Transient Overvoltage Contribution Overvoltage ( pu) 3.0 2.5 L=100km L = 10km 2.0 L= 0.2km 1.5 1.0 0.5 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 -0.5 Ifault/I ph-g solidly earthed (pu) Figure 2.6: Configuration 1 Transient overvoltage component Figure 2.6 shows the contribution of the transient overvoltage to the maximum recorded overvoltage. 46/138 2.5.2 Simulation 2 : Unloaded Line - Fault at the Beginning of the Line TABLE 2-2 – SIMULATION 2 RESULTS Line Length= 100km Max Measured V from NER PSCAD (Ohm) (kV) 0 72.597 5 94.147 10 99.371 15 101.219 20 102.529 25 103.542 30 104.549 35 106.192 40 107.291 45 108.035 50 108.486 100 111.955 550 110.022 1000 111.633 1000000 111.941 Iph-g with NER/ Iph-g solidly earthed 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 0.012 0.007 0.000 0 5 10 15 20 25 30 35 40 45 50 100 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 72.781 91.485 97.134 97.917 97.710 97.291 96.880 96.520 96.212 95.950 95.727 94.570 V Meas / Power Nominal Frequency K0 Voltage V (pu) 0.9 1.347 1.011 2.4 1.747 1.361 4.4 1.844 1.456 6.6 1.878 1.479 8.7 1.903 1.488 10.9 1.921 1.817 13.1 1.940 1.810 15.2 1.971 1.803 17.4 1.991 1.797 19.6 2.005 1.792 21.7 2.013 1.788 43.4 2.078 1.763 238.7 2.042 1.738 434.0 2.072 1.735 433986.8 2.077 1.736 Line Length=10km 0.9 1.351 2.4 1.698 4.4 1.802 6.6 1.817 8.7 1.813 10.9 1.805 13.1 1.798 15.2 1.791 17.4 1.785 19.6 1.781 21.7 1.776 43.4 1.755 47/138 1.011 1.361 1.456 1.479 1.488 1.817 1.810 1.803 1.797 1.792 1.788 1.763 Natural Frequency V (pu) 1.347 1.747 1.844 1.878 1.903 0.104 0.130 0.167 0.194 0.213 0.226 0.315 0.304 0.336 0.341 1.351 1.698 1.802 0.338 0.325 -0.012 -0.012 -0.012 -0.012 -0.012 -0.011 -0.008 Max Measured V from NER PSCAD (Ohm) (kV) 550 108.220 1000 112.946 1000000 119.533 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1000000 67.090 91.473 97.117 97.898 97.681 97.272 96.861 96.501 96.193 95.931 95.708 94.570 108.314 112.946 113.404 Iph-g with NER/ Iph-g solidly earthed 0.012 0.007 0.000 V Meas / Power Nominal Frequency K0 Voltage V (pu) 238.7 2.008 1.738 434.0 2.096 1.735 433986.8 2.218 1.736 Line Length=0.2km 0.9 1.245 2.4 1.697 4.4 1.802 6.6 1.817 8.7 1.813 10.9 1.805 13.1 1.797 15.2 1.791 17.4 1.785 19.6 1.780 21.7 1.776 43.4 1.755 238.7 2.010 434.0 2.096 433986.8 2.104 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 0.012 0.007 0.000 1.011 1.361 1.456 1.479 1.488 1.817 1.810 1.803 1.797 1.792 1.788 1.763 1.738 1.735 1.736 Natural Frequency V (pu) 0.270 0.361 0.482 1.245 1.697 0.346 0.338 0.325 -0.012 -0.013 -0.013 -0.012 -0.012 -0.012 -0.008 0.272 0.361 0.368 Configuration 2- Fault at the bus- No load- Measured Overvoltage 2.5 Overvoltage ( pu) 2.0 L=100km L = 10km 1.5 L= 0.2km 1.0 0.5 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 Ifault/I ph-g solidly earthed (pu) Figure 2.7- Configuration 2 Measured overvoltage result 48/138 0.2 0.1 0.0 Configuration 2- Fault at the bus- No load- Transient Ov erv oltage Contribution Overvoltage ( pu) 2.5 2.0 L=100km L = 10km 1.5 L= 0.2km 1.0 0.5 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 -0.5 Ifault/I ph-g solidly earthed (pu) Figure 2.8: Configuration 2 Transient overvoltage component This simulation has the same system configuration of the first study except the location of the fault. The results however show that different transmission line lengths do not produce any particular effect on the maximum overvoltage except to a slightly lower level of the recorded overvoltage. Lower results of the maximum overvoltages are due to different effect produced by the traveling waves that propagates along the subtransmission lines and different impact of the system conditions. 49/138 2.5.3 Simulation 3 : Capacitor Bank. Fault at the End of the Line TABLE 2-3 – SIMULATION 3 RESULTS Line Length= 100km Max Measured V from NER PSCAD (Ohm) (kV) 0 187.403 5 185.285 10 184.351 15 184.572 20 185.656 25 187.384 30 189.670 35 192.279 40 195.097 45 199.190 50 203.527 100 245.786 550 406.039 1000 453.542 1000000 526.382 Iph-g with NER/ Iph-g solidly earthed 1.000 0.977 0.946 0.909 0.867 0.824 0.782 0.740 0.700 0.663 0.628 0.394 0.082 0.045 0.000 0 5 10 15 20 25 30 35 40 45 50 100 1.000 0.882 0.705 0.561 0.457 0.383 0.328 0.286 0.253 0.227 0.206 0.105 110.323 123.489 127.826 128.511 124.144 154.689 160.269 164.680 168.268 171.273 173.731 186.406 K0 1.0 1.1 1.3 1.5 1.8 2.0 2.3 2.6 2.9 3.2 3.6 6.8 36.0 65.4 65217.4 V Meas / Power Nominal Frequency Voltage V (pu) 3.478 1.002 3.438 1.102 3.421 1.204 3.425 1.296 3.445 1.378 3.477 1.448 3.520 1.507 3.568 1.555 3.620 1.596 3.696 1.629 3.777 1.656 4.561 1.763 7.535 1.757 8.416 1.747 9.768 1.732 Line Length=10km 1.0 2.047 1.7 2.292 3.0 2.372 4.3 2.385 5.7 2.304 7.1 2.871 8.5 2.974 9.8 3.056 11.2 3.123 12.6 3.178 14.0 3.224 27.9 3.459 50/138 1.006 1.412 1.647 1.745 1.783 1.797 1.802 1.802 1.800 1.797 1.794 1.771 Natural Frequency V (pu) 2.476 2.336 2.217 2.129 2.067 2.029 2.013 2.013 2.025 2.068 2.121 2.798 5.778 6.669 8.036 1.041 0.879 0.725 0.640 0.521 1.073 1.172 1.254 1.323 1.381 1.430 1.688 Max Measured V from NER PSCAD (Ohm) (kV) 550 198.797 1000 200.148 1000000 182.224 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1000000 109.095 135.208 135.715 127.208 148.710 152.521 162.300 166.755 170.288 173.169 175.588 188.724 200.208 201.435 203.044 Iph-g with NER/ Iph-g solidly earthed 0.019 0.011 0.000 V Meas / Power Nominal Frequency K0 Voltage V (pu) 153.0 3.689 1.740 278.1 3.714 1.736 278041.7 3.381 1.736 Line Length=0.2km 0.9 2.024 2.3 2.509 4.4 2.518 6.5 2.361 8.6 2.760 10.8 2.830 12.9 3.012 15.1 3.094 17.2 3.160 19.3 3.213 21.5 3.258 42.9 3.502 236.1 3.715 429.2 3.738 429200.4 3.768 1.000 0.806 0.564 0.415 0.324 0.264 0.223 0.192 0.169 0.151 0.136 0.068 0.012 0.007 0.000 Natural Frequency V (pu) 1.949 1.978 1.645 1.011 1.358 1.455 1.478 1.822 1.817 1.810 1.804 1.798 1.792 1.788 1.763 1.738 1.735 1.736 1.014 1.151 1.064 0.882 0.937 1.013 1.202 1.291 1.362 1.421 1.471 1.739 1.977 2.003 2.031 Configuration 3- Fault at the end of the line- Cap Bank connected at the end of the line- Measured Overvoltage 12.0 10.0 Overvoltage ( pu) L=100km L = 10km 8.0 L= 0.2km 6.0 4.0 2.0 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 Ifault/I ph-g solidly earthed (pu) Figure 2.9: Configuration 3 Measured overvoltage result 51/138 0.3 0.2 0.1 0.0 Configuration 3- Fault at the end of the line- Cap Bank connected at the end of the lineTransient Overvoltage Contribution 9.0 8.0 L=100km L = 10km 7.0 L= 0.2km Overvoltage ( pu) 6.0 5.0 4.0 3.0 2.0 1.0 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 Ifault/I ph-g solidly e arthe d (pu) Figure 2.10: Configuration 3 Transient overvoltage component The dangerous effects of capacitor switching are well known in the engineering field [23]. The results obtained with this simulation show that, following a fault in the network with no or small loads and a capacitor bank connected to the grid represent a danger to the insulation of the power system. The overvoltages measured in this simulation are the highest of the entire study reported here. The results are in line with previous studies [5, 14] except for results obtained with line length of 100 km . This is due to the combination of the following system parameters: Length of the line NER size These parameters affect the R0 XC 0 transient overvoltages condition. If this 3 condition is not met, dangerous fault restrikes are generated [9]. Is it worth noting that field experience of arcing ground fault above 7 pu are quite rare as the insulation of the power system usually breaks down between 6 to 7 pu [9] 52/138 Line length impact is shown in Figure 2.9 and 2.10. Instead, to review the impact of the NER size further simulations were performed. Four snapshots with a NER of Voltage (kV) 10, 100, 1000 and 1000000 Ohm were taken as shown in Figures 2.11 to 2.14. 100 80 60 40 20 0 -20 -40 -60 -80 Vs Figure 2.11: Configuration 3 Transient overvoltage Snapshot with NER of 10 Ohms 300 200 100 0 -100 -200 -300 53/138 Figure 2.14: Configuration 3 Transient overvoltage Snapshot with NER of 1000000 Ohms The graphs show that the increase of the resistor will increase the transient overvoltages. The dangerous transient overvoltages are also due to the conservative approach in selecting the size of the capacitor bank. A further simulation is conducted to validate this theory. A smaller capacitor bank of 15 MVA was used for the analysis. Configuration 3- Line Length 100km- Comparison between 30MVAR and 15MVAR Capacitor Bank Results- Measured Overvoltage 12.0 10.0 Overvoltage ( pu) 15MVAR 30MVAR 8.0 6.0 4.0 2.0 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 Ifault/I ph-g solidly earthed (pu) Figure 2.15: Configuration 3 30 and 15 MVAR Cap bank overvoltage comparison 54/138 0.0 The system response with a smaller capacitor gives a result which is acceptable and in line with previous studies [5, 19]. Maximum overvoltage with the insulated system is 4.1 pu. 55/138 2.5.4 Simulation 4 : Capacitor Bank. Fault at the Beginning of the Line TABLE 2-4 – SIMULATION 4 RESULTS Line Length= 100km Max Measured V from NER PSCAD (Ohm) (kV) 0 73.660 5 102.229 10 110.677 15 120.455 20 139.620 25 156.662 30 171.647 35 185.697 40 198.103 45 209.035 50 219.140 100 282.383 550 373.638 1000 431.569 1000000 553.568 Iph-g with NER/ Iph-g solidly earthed 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 0.012 0.007 0.000 0 5 10 15 20 25 30 35 40 45 50 100 550 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 0.012 73.885 104.589 115.953 126.137 129.761 140.232 143.196 147.174 151.560 155.590 158.744 173.853 185.633 V Meas / Power Nominal Frequency K0 Voltage V (pu) 0.9 1.367 1.011 2.4 1.897 1.361 4.4 2.054 1.456 6.6 2.235 1.479 8.7 2.591 1.488 10.9 2.907 1.817 13.1 3.185 1.810 15.2 3.446 1.803 17.4 3.676 1.797 19.6 3.879 1.792 21.7 4.067 1.788 43.4 5.240 1.763 238.7 6.934 1.738 434.0 8.009 1.735 433986.8 10.272 1.736 Line Length=10km 0.9 1.371 2.4 1.941 4.4 2.152 6.6 2.341 8.7 2.408 10.9 2.602 13.1 2.657 15.2 2.731 17.4 2.812 19.6 2.887 21.7 2.946 43.4 3.226 238.7 3.445 56/138 1.011 1.361 1.456 1.479 1.488 1.817 1.810 1.803 1.797 1.792 1.788 1.763 1.738 Natural Frequency V (pu) 1.367 1.897 2.054 2.235 2.591 2.907 3.185 3.446 3.676 3.879 4.067 5.240 6.934 8.009 10.272 0.360 0.580 0.696 0.862 0.920 0.785 0.847 0.928 1.015 1.095 1.158 1.463 1.707 Max Measured V from NER PSCAD (Ohm) (kV) 1000 187.731 1000000 200.403 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1000000 90.349 110.113 125.484 142.000 149.540 152.234 157.592 160.073 161.970 163.420 165.426 173.384 178.234 188.233 200.173 Iph-g with NER/ Iph-g solidly earthed K0 0.007 434.0 0.000 433986.8 V Meas / Power Nominal Frequency Voltage V (pu) 3.484 1.735 3.719 1.736 Line Length=0.2km 0.9 1.677 2.4 2.043 4.4 2.329 6.6 2.635 8.7 2.775 10.9 2.825 13.1 2.924 15.2 2.970 17.4 3.006 19.6 3.033 21.7 3.070 43.4 3.217 238.7 3.307 434.0 3.493 433986.8 3.715 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 0.012 0.007 0.000 1.011 1.361 1.456 1.479 1.488 1.817 1.810 1.803 1.797 1.792 1.788 1.763 1.738 1.735 1.736 Natural Frequency V (pu) 1.748 1.982 0.666 0.683 0.873 1.156 1.287 1.008 1.114 1.167 1.208 1.240 1.282 1.454 1.569 1.758 1.978 Configuration 4- Fault at the bus- Cap Bank at the end of the line- Measured Overvoltage 12.0 10.0 Overvoltage ( pu) L=100km 8.0 L = 10km L= 0.2km 6.0 4.0 2.0 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 Ifault/I ph-g solidly earthed (pu) Figure 2.16: Configuration 4 Measured overvoltage result 57/138 0.3 0.2 0.1 0.0 Configuration 4- Fault at the bus- Cap Bank at the end of the lineTransient Overvoltage Contribution 12.0 L=100km L = 10km 10.0 Overvoltage ( pu) L= 0.2km 8.0 6.0 4.0 2.0 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 Ifault/I ph-g solidly e arthe d (pu) Figure 2.17: Configuration 4 Transient overvoltage component This simulation uses the same system configuration of Simulation 3 except for the location of the fault. Measured overvoltage shows that these results are similar to the results obtained from Simulation 3. Maximum overvoltages are recorded with the transmission line of 100km and after fault clearing. As discussed in Simulation 2, location of the fault in proximity of the neutral earth resistor decreases the value of the maximum overvoltages. 58/138 2.5.5 Simulation 5 : Light inductive Load. Fault at the End of the Line. TABLE 2-5 – SIMULATION 5 RESULTS Line Length= 100km Max Measured V from NER PSCAD (Ohm) (kV) 0 123.996 5 121.497 10 127.242 15 124.414 20 125.584 25 126.472 30 127.242 35 127.753 40 128.210 45 128.382 50 128.563 100 125.448 550 106.256 1000 114.514 1000000 131.252 Iph-g with NER/ Iph-g solidly earthed 1.000 0.977 0.946 0.909 0.867 0.824 0.782 0.740 0.700 0.663 0.628 0.394 0.082 0.045 0.000 0 5 10 15 20 25 30 35 40 45 50 100 1.000 0.882 0.705 0.561 0.457 0.383 0.328 0.286 0.253 0.227 0.206 0.105 89.031 98.999 99.542 98.172 97.019 95.755 95.531 95.024 94.367 94.358 94.180 93.855 K0 1.0 1.1 1.3 1.5 1.8 2.0 2.3 2.6 2.9 3.2 3.6 6.8 36.0 65.4 65217.4 V Meas / Power Nominal Frequency Voltage V (pu) 2.301 1.002 2.255 1.102 2.361 1.204 2.309 1.296 2.330 1.378 2.347 1.448 2.361 1.507 2.371 1.555 2.379 1.596 2.382 1.629 2.386 1.656 2.328 1.763 1.972 1.757 2.125 1.747 2.436 1.732 Line Length=10km 1.0 1.652 1.7 1.837 3.0 1.847 4.3 1.822 5.7 1.800 7.1 1.777 8.5 1.773 9.8 1.763 11.2 1.751 12.6 1.751 14.0 1.748 27.9 1.742 59/138 1.006 1.412 1.647 1.745 1.783 1.797 1.802 1.802 1.800 1.797 1.794 1.771 Natural Frequenc y V (pu) 2.301 2.255 2.361 2.309 2.330 2.347 2.361 2.371 2.379 2.382 2.386 2.328 0.215 0.378 0.704 1.652 1.837 1.847 1.822 0.017 -0.021 -0.029 -0.038 -0.049 -0.046 -0.046 -0.029 550 99.236 0.019 153.0 1.841 Max Measured V from NER PSCAD (Ohm) (kV) 1000 109.857 1000000 241.638 Iph-g with NER/ Iph-g solidly earthed K0 0.011 278.1 0.000 278041.7 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1000000 1.000 0.806 0.564 0.415 0.324 0.264 0.223 0.192 0.169 0.151 0.136 0.068 0.012 0.007 0.000 74.717 85.939 91.418 94.402 95.404 95.743 95.531 95.640 95.477 95.301 95.131 94.017 97.021 107.684 126.718 1.740 0.101 V Meas / Power Nominal Frequency Voltage V (pu) 2.039 1.736 4.484 1.736 Line Length=0.2km 0.9 1.387 2.3 1.595 4.4 1.696 6.5 1.752 8.6 1.770 10.8 1.777 12.9 1.773 15.1 1.775 17.2 1.772 19.3 1.768 21.5 1.765 42.9 1.745 236.1 1.800 429.2 1.998 429200.4 2.351 Natural Frequenc y V (pu) 0.302 2.748 1.011 1.358 1.455 1.478 1.822 1.817 1.810 1.804 1.798 1.792 1.788 1.763 1.738 1.735 1.736 1.387 1.595 0.242 0.273 -0.052 -0.040 -0.037 -0.029 -0.026 -0.024 -0.022 -0.019 0.062 0.263 0.615 Configuration 5- Fault at the of end the line- Inductive Load connected at the end of the line- Measured Overvoltage 5.0 4.5 Overvoltage ( pu) 4.0 3.5 L=100km L = 10km 3.0 L= 0.2km 2.5 2.0 1.5 1.0 0.5 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 Ifault/I ph-g solidly earthed (pu) Figure 2.18: Configuration 1 Measured overvoltage result 60/138 0.2 0.1 0.0 Configuration 5- Fault at the end of the line- Inductive Load connected at the end of the lineTransient Overvoltage Contribution 3.0 L=100km L = 10km 2.5 L= 0.2km Overvoltage ( pu) 2.0 1.5 1.0 0.5 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 -0.5 Ifa ult/I ph-g solidly e arthed (pu) Figure 2.19: Configuration 5 Transient overvoltage component Maximum overvoltages recorded are similar to the results from Simulation 1. It is likely that this inductive load was not large enough to produce any relevant impact on the overvoltages. Therefore, not further analysis was conducted using the results of this system configuration. 61/138 2.5.6 Simulation 6 : Energized 66/22kV Transformer Fault at the 66kV Bus. TABLE 2-6 – SIMULATION 61 RESULTS Max Measured V from NER PSCAD (Ohm) (kV) 0 54.929 5 91.224 10 96.846 15 97.661 20 97.464 25 97.053 30 96.646 35 96.287 40 95.982 45 95.721 50 95.499 100 94.343 550 93.211 1000 93.089 1000000 92.838 Iph-g with NER/ Iph-g solidly earthed 1.000 0.804 0.561 0.412 0.321 0.262 0.220 0.190 0.167 0.149 0.134 0.068 0.012 0.007 0.000 V Meas / Power Nominal Frequency K0 Voltage V (pu) 0.9 1.017 1.011 2.4 1.692 1.361 4.4 1.792 1.456 6.6 1.812 1.479 8.7 1.806 1.488 10.9 1.800 1.817 13.1 1.793 1.810 15.2 1.788 1.804 17.4 1.786 1.798 19.6 1.776 1.792 21.7 1.772 1.788 43.4 1.763 1.763 238.7 1.729 1.738 434.0 1.727 1.735 433986.8 1.723 1.732 Configuration 6- Fault at the bus- Tx 30 MVA delta/star at the bus- Measured Overvoltage 2.0 1.8 Overvoltage ( pu) 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 Ifault/I ph-g solidly earthed (pu) Figure 2.20: Configuration 6 Measured overvoltage result 62/138 0.3 0.2 0.1 0.0 Natural Frequenc y V (pu) 0.006 0.331 0.336 0.333 0.318 -0.017 -0.017 -0.016 -0.012 -0.016 -0.016 0.000 -0.009 -0.008 -0.009 Configuration 6- Fault at the bus- Tx 30 MVA at the busTransient Overvoltage Contribution 0.4 0.4 Overvoltage( pu) 0.3 0.3 0.2 0.2 0.1 0.1 0.0 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 -0.1 Ifault/I ph-g s olidly e ar the d (pu) Figure 2.21: Configuration 6- Transient overvoltage result Overvoltages recorded in this study are relatively lower than in the other simulations. Maximum overvoltage reaches a maximum of 1.8pu as phase to ground fault decreases below 0.6 pu. Please note that the transient overvoltage component disappears as the phase to ground fault decreases below 0. 25 pu. Therefore, for high resistor values the overvoltages are only produced by the power frequency voltage. No further analysis was conducted using the data from this simulation 2.5.7 Overvoltages and Traveling Waves This section documents the propagation of the voltage traveling waves along the transmission line. A series of snapshots are presented to describe the behavior of the overvoltages using the data from Simulation 1 – No load at the end of the lineand with the line length of 100 km 63/138 Bus Current,Bus Voltage : Graphs 1.50 Is Current (kA) 1.00 0.50 0.00 -0.50 -1.00 Voltage (kV) -1.50 Time ... 80 60 40 20 0 -20 -40 -60 -80 -100 Vs 0.3850 0.3900 0.3950 0.4000 0.4050 0.4100 0.4150 0.4200 0.4250 0.4300 ... ... ... Figure 2.22: Configuration 1 - Maximum Overvoltage - Phase to Ground Fault – NER 0 Ohm Snapshots were recorded at fault inception and fault clearing time. The graph also shows that the transient overvoltage at higher frequency is superimposed on a lower frequency overvoltage. The overvoltage has a period of 0.7 ms which is equivalent to a frequency of 1400 Hz. The high frequency component decays in approximately 10ms. Traveling waves are triggered at the same time on both healthy phases and travel on the conductors. The steps pattern of the transient overvoltage is the effect of the traveling waves that reflect back and forward between the two ends of the line. 64/138 Bus Current,Bus Voltage : Graphs 1.50 Is Current (kA) 1.00 0.50 0.00 -0.50 -1.00 Voltage (kV) -1.50 Time ... 125 100 75 50 25 0 -25 -50 -75 -100 Vs 0.5050 0.5075 0.5100 0.5125 0.5150 0.5175 0.5200 0.5225 0.5250 0.5275 ... ... ... Figure 2.23: Configuration 1- Snapshot of after clearing overvoltage- Phase to Ground Fault – NER 0 Ohm Transient overvoltage superimposed on the power frequency voltage has a frequency of 590 Hz. Maximum overvoltage appears on the phase which has the highest voltage at the clearing time. The overvoltage is produced by the energy stored in the electric field of the capacitance that will discharge at fault clearing time. 65/138 Bus Current,Bus Voltage : Graphs 1.50 Is Current (kA) 1.00 0.50 0.00 -0.50 -1.00 -1.50 150 Vs Voltage (kV) 100 50 0 -50 -100 Time ... 0.490 0.500 0.510 0.520 0.530 0.540 0.550 ... ... ... Figure 2.24: Configuration 1- Snapshot of Maximum Overvoltage- Phase to Phase to Ground Fault – NER 0 Ohm In the phase to phase ground fault the maximum overvoltage is recorded at the fault clearing time. Frequency of the superimposed transient overvoltage is 590 Hz as in the phase to ground faults. The overvoltages on each phase have the same frequency. This transient overvoltage decays after 30ms. 66/138 Bus Current,Bus Voltage : Graphs Current (kA) 0.80 0.60 Is 0.40 0.20 0.00 -0.20 -0.40 -0.60 -0.80 Voltage (kV) 100 75 50 Vs 25 0 -25 -50 -75 -100 Time ... 0.3950 0.4000 0.4050 0.4100 0.4150 0.4200 0.4250 0.4300 ... ... ... Figure 2.25: Configuration 1- Snapshot of Maximum Overvoltage- Phase to Ground Fault – NER 50 Ohm Bus Current,Bus Voltage : Graphs 0.60 Is Current (kA) 0.40 0.20 0.00 -0.20 -0.40 Voltage (kV) -0.60 Time ... 125 100 75 50 25 0 -25 -50 -75 -100 Vs 0.5025 0.5050 0.5075 0.5100 0.5125 0.5150 0.5175 0.5200 0.5225 ... ... ... Figure 2.26: Configuration 1- Snapshot of Maximum Overvoltage- Phase to Phase to Ground Fault – NER 50 Ohm 67/138 As the NER approaches 50 Ohm, the pattern of the plots remains similar to plots with NER equal to 0 Ohm. Overvoltage frequencies are 590 Hz in all three phases. Bus Current,Bus Voltage : Graphs 0.200 Is Current (kA) 0.150 0.100 0.050 0.000 -0.050 Voltage (kV) -0.100 100 75 50 25 0 -25 -50 -75 -100 -125 Time ... Vs 0.4000 0.4050 0.4100 0.4150 0.4200 0.4250 ... ... ... Figure 2.27: Configuration 1- Snapshot of Maximum Overvoltage- Phase to Ground Fault – NER 1000 Ohm The large size of the resistor now makes the phase to ground fault as the most prominent overvoltage. Traveling waves are visible in the current and voltage plots. 2.5.8 Impact of Time of Fault with the Overvoltage This investigation highlights the relation between the time of fault and the amplitude of the measured overvoltage. Plots are divided into phase to ground fault and phase to phase to ground fault. 68/138 Simulation 1- Measured Overvoltage Ph-g fault- All Data Plot 3 O vervoltage 2.5 2 Solidly Earthed System Insulated System L=100km L=10km L=0.2km 1.5 1 0.5 0 0 50 100 150 200 250 300 350 Sample Figure 2.28: Configuration 1- All Data Plot Simulation 2- Measured Overvoltage Ph-g Fault- All Data Plot 2.5 O vervoltage 2 Solidly Earthed System 1.5 Insulated System L=100km L=10km L=0.2km 1 0.5 0 0 50 100 150 200 250 300 350 Sample Figure 2.29: Configuration 2 All Data Plot Simulation 3- Measured Overvoltage Ph-g Fault- All Data Plot 12 O vervoltage 10 8 Solidly Earthed System Insulated System L=100km L=10km L=0.2km 6 4 2 0 0 50 100 150 200 Sample Figure 2.30: Configuration 3 All data plot 69/138 250 300 350 Simulation 4- Measured Overvoltage Ph-g Fault- All Data Plot 12 Overvoltage 10 8 Solidly Earthed System Insulated System L=100km L=10km L=0.2km 6 4 2 0 0 50 100 150 200 250 300 350 Sample Figure 2.31: Configuration 4- All data plot Simulation 1- Measured Overvoltage Ph-Ph-G Fault- All Data Plot 3 2.5 O vervoltage(p u) 2 1.5 1 Series1 Series2 Insulated System Solidly Earthed System Series3 0.5 0 0 50 100 150 200 250 300 350 Simulation Figure 2.32: Configuration 1- All data plot Simulation 2- Measured Overvoltage Ph-Ph-G Fault- All Data Plot 2.5 O vervoltag e(pu ) 2 1.5 L=100km Insulated System Solidly Earthed System 1 L=10km L=0.2km 0.5 0 0 50 100 150 200 Sim ulation Figure 2.33: Configuration 2 All data plot 70/138 250 300 350 Simulation 3- Measured Overvoltage Ph-Ph-G Fault- All Data Plot 5 4.5 4 O vervoltag e(p u) 3.5 Insulated System 3 2.5 L=100km L=10km L=0.2km Solidly Earthed System 2 1.5 1 0.5 0 0 50 100 150 200 250 300 350 Sim ulation Figure 2.34: Configuration 3- All data plot Simulation 4- Measured Overvoltage Ph-Ph-G Fault- All Data Plot 8 7 O vervoltage(pu) 6 5 Insulated System 4 L=100km L=10km L=0.2km Solidly Earthed System 3 2 1 0 0 50 100 150 200 250 300 350 Simulation Figure 2.35: Configuration 3 All data plot These graphs are produced by using the maximum overvoltage recorded on each simulation. It is reminded that 11 simulations were performed for each NER size configuration. Besides, 1 ms additional delay time was applied on each simulation. Points were plotted sequentially, starting on the simulation with a NER of 0 Ohm to the maximum value of the NER, which corresponds to the insulated system. In these eight plots, Figure 2.28 to Figure 2.35, it is possible to recognize the 15 peaks related to the 15 resistor sizes used in the simulations. 71/138 Phase to ground faults for transmission line of 10 and 0.1km showed a smoother pattern with lower peak values. Only in Simulation 2 there is an irregularity in the maximum overvoltage. Overall, the maximum overvoltage in the phase to ground fault is therefore less dependent on the time of fault. Phase to ground fault maximum overvoltages show a similar pattern across the three different subtransmission line lengths. Maximum overvoltages appear only for a brief period of time and at the same time in all the three line lengths. The 8 plots also show similar results for simulations conducted with subtransmission line of 10km and 0.1km. These graphs confirm that time of fault is relevant in determining the maximum overvoltage during phase to phase to ground faults. 2.5.9 Overvoltage Response on Phase a ,b and c The section investigates the relationship between faults and different overvoltage responses on each phase. This study was conducted only for subtransmission line of 100km in the simulation 1, 2, 3 and 4. Graphs are divided in phase to ground faults and phase to phase to ground faults. On PSCAD software package phase to ground fault takes place on phase a and phase to phase to ground fault takes place on phases a and b. 72/138 Simulation 1-Measured Overvoltage Phase Comparison-Phase to Ground Fault- L=100km 3 2.5 O vervoltage(pu) 2 Phase a Insulated System 1.5 Phase b Phase c Solidly Earthed System 1 0.5 0 0 50 100 150 200 250 300 350 Simulation Figure 2.36: Configuration 1 Phase comparison Simulation 2-Measured Overvoltage Phase Comparison-Phase to Ground Fault- L=100km 2.5 O v e rv o lta g e(p u ) 2 Insulated System 1.5 Phase a Phase b Phase c 1 Solidly Earthed System 0.5 0 0 50 100 150 200 250 300 350 Simulation Figure 2.37: Configuration 2 Phase comparison Simulation 3-Measured Overvoltage Phase Comparison-Phase to Ground Fault- L=100km 12 10 Insulated System O vervoltage(pu) 8 Phase a 6 Phase b Phase c Solidly Earthed System 4 2 0 0 50 100 150 200 Simulation Figure 2.38: Configuration 3 Phase comparison 73/138 250 300 350 Simulation 4-Measured Overvoltage Phase Comparison-Phase to Ground Fault- L=100km 12 10 O vervo ltag e(p u ) 8 Insulated System Phase a 6 Phase b Phase c 4 Solidly Earthed System 2 0 0 50 100 150 200 250 300 350 Simulation Figure 2.39: Configuration 4 Phase comparison Simulation 1-Measured Overvoltage Phase Comparison-Phase to Phase to Ground Fault- L=100km 3 2.5 O vervo ltag e(p u ) 2 Phase a Phase b 1.5 Phase c Insulated System Solidly Earthed System 1 0.5 0 0 50 100 150 200 250 300 350 Simulation Figure 2.40: Configuration 1 Phase comparison Simulation 2-Measured Overvoltage Phase Comparison-Phase to Phase to Ground Fault- L=100km 2.5 O v e rv o lta g e(p u ) 2 1.5 Phase a Phase b Insulated System 1 Phase c Solidly Earthed System 0.5 0 0 50 100 150 200 Simulation Figure 2.41: Configuration 2 Phase comparison 74/138 250 300 350 Simulation 3-Measured Overvoltage Phase Comparison-Phase to Phase to Ground Fault- L=100km 5 4.5 4 O v e rv o lta g e(p u ) 3.5 3 Insulated System 2.5 Phase a Phase b Phase c 2 Solidly Earthed System 1.5 1 0.5 0 0 50 100 150 200 250 300 350 Simulation Figure 2.42: Configuration 3 Phase comparison Simulation 4-Measured Overvoltage Phase Comparison-Phase to Phase to Ground Fault- L=100km 8 7 Insulated System O vervo ltag e(p u ) 6 5 Phase a 4 Phase b Phase c Solidly Earthed System 3 2 1 0 0 50 100 150 200 250 300 350 Simulation Figure 2.43: Configuration 4 Phase comparison This investigation shows that maximum overvoltage can be recorded in the healthy phases as well as in the faulty phases following fault clearing. In this case the impact of the power frequency overvoltage is null. This characteristic is particularly defined on phase to phase to ground faults at clearing time and for both types of faults for Simulation 3 and 4, where the capacitor bank is connected. In each phase the overvoltage pattern is same for all resistor values. Constant overvoltages are broken by regular small “bumps” at the time where the voltage on the related phases have the highest magnitude at fault clearing or fault inception. 75/138 As noted in Section 2.4.9, the plots for the phase to phase to ground faults show that the time of fault is a key element to determine in which phase the maximum overvoltage is recorded. 2.5.10 Overvoltage Harmonic Response A further analysis was conducted on the frequency spectrum of the transient overvoltage. The study was done using the Fast Fourier Transform (FFT) function, which determine the harmonic magnitude and phase of the input signal as a function of time[21]. Base frequency was set to 12.5 Hz to detect noise elements lower than power frequency voltage. Here below few snapshots of the healthy and faulty phases for a phase to ground fault following a fault are provided. Snapshots were captured after 10 ms fault injection. Referring to the graphs left hand side spectrum refers to 12.5 Hz component and right hand side spectrum refers to 322.5 HZ noise element. The number in the plot frame refers to the voltage magnitude in the first frequency band, 12.5 Hz. Ea 60.0 0.0 [1] 1.79434 Figure 2.44: Configuration 1 Harmonic analysis NER 0 ohms –after 10ms 76/138 Ea 60.0 0.0 [1] 3.50508 Figure 2.45: Configuration 1 Harmonic analysis NER 5 ohms –after 10ms Ea 60.0 0.0 [1] 6.13753 Figure 2.46: Configuration 1 Harmonic analysis NER 50 ohms –after 10ms From the graphs we can observe that voltage noise appears at frequencies higher and lower values in respect of the power frequency voltage The major components are in the band close to 50 Hz. Components with lower magnitude, less than 3 % of nominal voltage, are visible on high frequency up to 300 Hz. The harmonics were recorded on the healthy phase. The graphs show that the noise is not limited to odd harmonics. Therefore, filtering this natural frequency component could be problematic and slow down the information process of the digital relays. 77/138 2.6 Conclusion 1. Results obtained from this study are in line with the existing literature and previous studies in this field. Maximum overvoltages are below 2.5 pu for a ground fault in an unloaded subtransmission line and below 4 pu in an unloaded line with a capacitor bank connected at the end of the line 2. Maximum overvoltage is influenced by the power system parameters. The size of the neutral earth resistor itself does not give a clear indication of the system response and expected maximum overvoltage during a ground fault 3. Increasing the size of the neutral earth resistor controls the maximum overvoltage on unloaded line as the resistor has a positive impact in limiting the natural frequency overvoltage until the fault current is equal to 10 % of the fault current with a solidly earthed system 4. The limitation of the transitory overvoltage component is strictly connected to the increase of the ratio R0/X0 until the R0<1/3 Xc0 factor and subsequent fault clearing restrike takes place. Therefore, to design a high impedance grounding , a transient recovery voltage study, TRV, should be conducted to safely determine the magnitude of the resistor 5. The positive effect of the neutral earth resistor is negligible if a capacitor bank is connected to an unloaded line. In this event, further increase of the resistor could generate dangerous overvoltages 6. Phase to ground faults generally produce higher overvoltage than the overvoltage response for phase to phase to ground faults for high value of neutral earth resistor are in the higher end of the of the value considered 7. There is a clear connection between line length and maximum overvoltage. Line length increases transient overvoltages. Requirement for system 78/138 analysis and related transient studies should be carefully considered for long subtransmission lines as is usually done for transmission lines 8. There is also a consistent similarity of results for line length of 10km and 0.2km. This characteristic should be taken into consideration to optimize the work during planning and design activities for short and medium length subtransmission lines 9. Transient overvoltages appear in the faulty and healthy phases. There is a relation between time of fault and location where the maximum overvoltages takes place 10. There is not a strong relation between the time of fault and the magnitude of the maximum overvoltage during phase to ground faults. Relation between the magnitude of the maximum overvoltage and the time of fault is only relevant on the phase to phase to ground faults 11. Considering the overvoltage component at higher frequency, this study shows that beyond the debate of effective or non effective grounding, design of the neutral earth resistors could safely aim to limit the ground fault current to 0.1pu of the fault current in a solidly earthed system without compromising the insulation level of the system 79/138 3 CVT and Transient Overvoltages 3.1 Overview Capacitive voltage transformer, CVT, represents the most common method of voltage source for the impedance protection relays installed for transmission and subtransmission power systems. Until few years ago the use of the CVT was limited to extra high voltage system. In recent years the use of the CVT has become more popular even for application with nominal voltage down to 33kV (as applied by Energex and Ergon in Queensland) due the lower capital cost compared to the traditional voltage transformer, VT. CVTs also offer the advantage to couple power line carrier to inject teleprotection signals between substations. During a fault, ideally, the low voltage source provided by the CVT should be an exact copy of the primary voltage. Unfortunately this is not the reality. CVT contains a large number of stored energy components which must charge and discharge during voltage changes [24-29]. The transfer of energy between capacitances and inductances within the CVT requires some time to take place. Therefore, the CVT introduces some transients that affect the magnitude and shape of the voltage signal. CVT creates some problems to the distance relays especially during faults that severely depress the voltage at the relay location. Faults located at the beginning of the protected line can bring the voltage down to few percents of the nominal voltage and this could affect accuracy and operating time of the relay. This section aims to investigate the CVT transient response during phase to ground fault and the impact that this disturbance can have on the distance relay. 80/138 3.2 The CVT Model Introduction The main component of the CVT are the capacitive voltage divider , a tuning reactor, a voltage transformer, a ferroresonance suppression circuit and the burden made by the relay. The CVT model can be further simplified where the equivalent circuit is referred to the intermediate voltage: The CVT model has been design according to this References [24, 25, 27] Capacitive Voltage Divider The capacitive voltage divider steps down the voltage from 66 to 10-15 kV. A lower voltage is required to reduce the insulation of the subsequent voltage transformation and, therefore, to the overall cost of the CVT. The design of the capacitors is one of the main challenges faced by manufacturers. In fact, the higher the size of the capacitance, the lower is the magnitude of the transient overvoltage during sudden changes in the power system [24]. At the same time, CVT with a high capacitor size are more expensive. CVTs are often classified as normal C, high C and extra high C according to the value of the stack capacitance [25]. Typically the value of the capacitors is in the range of 100nF [24, 27]. A Normal C capacitor with a total value of 100 nF was selected. Tuning reactor 81/138 The tuning reactor is required to cancel out the value of the capacitive divider at the system frequency [24] . Therefore, the reactor prevents the phase shift between the voltage signal at the transmission line and the voltage fed to the relay. The size of the reactor is tuned for the system frequency of 50 Hz. In this study the reactor is 111 H. Voltage transformer The voltage transformer reduces the voltage from 10-15 kV to a voltage suitable for the relay which is usually 100 or 110 V. Copper and iron losses were taken into consideration by adding in the CVT model a resistance of 2000 Ohm. Ferroresonance Suppression Circuit The ferroresonance suppression circuit is installed in the low voltage side of the voltage transformer to prevent dangerous overvoltages due to the saturation of the iron core of the step down transformer. Two types of ferroresonance suppression circuits are normally used by CVT manufacturers [24, 25, 27]: Active ferroresonance suppression circuit Passive ferroresonance suppression circuit The active ferroresonance suppression circuit consists of a parallel tuning circuit in series with a damping resistor. The LC parallel circuit behaves as an open circuit at the nominal power frequency to prevent shunt current flowing through the circuit. During transient condition the tuning circuit will decrease the impedance to the value of the damping resistor. The resistor will attenuate the energy of the transient surge [24] 82/138 The passive ferroresonance suppression circuit has a resistor, a saturable inductor and air gap loading resistor. In normal condition the voltage is not high enough to flash the air gap. During transient conditions, the air gap will flash over through the resistor and will attenuate the transient energy. Existing literature and previous study demonstrated that the passive ferroresonance circuit has better transient performance than the active device [24, 25, 27, 28, 31, 32]. However, as the study aims to test the CVT under the worst case scenario, the active suppression circuit was implemented. Device Data R= 77379 Ohms C=29 nF L=111 H CVT Burden The burden connected at the end of the circuit represents the static or numerical digital relays. Modern relays have a small burden. Typically the burden is below 5 VA . The value of the burden is 1000 Ohms 83/138 3.3 Simulation Settings Fault time System faults can happen at any time. Considering the two voltage magnitude end range, the fault could take place at 0 voltage or at maximum voltage. Fault at zero voltage are less common than faults at the maximum voltage. In fact, this type of fault could only happen during lightning or close of the circuit breaker on fault condition. Faults at the maximum voltage usually take place when insulation failure occurs and are statistically more likely to happen. Simulations were conducted with fault at zero crossing of the primary voltage. At this time the energy store in the capacitor is at the maximum and this condition will generate the worst voltage transient conditions. The sudden change in the system will release the energy stored in the active elements of the CVT creating the worst transient overvoltage condition. These voltage oscillations are composed of lower and higher frequency components. Network and Source Settings 66 kV subtransmission line model is as per the model used in Section 1 (Overvoltage). The line model was set to 2 km and 10 km. Short lines were selected to increase the source impedance ratio, SIR, and testing the performance of the CVT with a higher SIR. It is reminded that SIR is the ration between the source impedance and the line impedance at the relay point. 84/138 The source impedance was set to determine a starting SIR of 1 and 10 without the implementation of the NER. Then, the neutral earth resistor was increased to obtain the desired SIR. To conclude, four network models were investigated: 10km line length- SIR of 1( No NER), 5, 10, 20, 30 and 60 10km line length- SIR of 10( No NER), 20, 30 and 60 2 km line length- SIR of 1( No NER), 5, 10, 20, 30 and 60 10km line length- SIR of 10( No NER), 20, 30 and 60 85/138 3.4 Simulation Results Simulations results are provided in Appendix D and summarised in the graphs here below: Overvoltage( pu) Transient Overvoltage- 10km line- Initial SIR 1 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 SIR 1 SIR 5 SIR 10 SIR 20 SIR 30 SIR 60 10 30 50 70 Time (ms) Figure 3.1: Peak overvoltage after fault- Initial SIR 1- Line length 10 km Overvoltage ( pu) Transient Overvoltage- 10km line- Initial SIR 10 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 SIR 10 SIR 20 SIR 30 SIR 60 10 30 50 70 Time (ms) Figure 3.2: Peak overvoltage after fault- Initial SIR 10- Line length 10 km 86/138 Overvoltage( pu) Transient Overvoltage- 2km line- Initial SIR 1 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 SIR 1 SIR 5 SIR 10 SIR 20 SIR 30 SIR 60 10 30 50 70 Time (ms) Figure 3.3: Peak overvoltage after fault- Initial SIR 1- Line length 2 km Overvoltage( pu) Transient Overvoltage- 2km line- Initial SIR 1 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 SIR 10 SIR 20 SIR 30 SIR 60 10 30 50 70 Time (ms) Figure 3.4: Peak overvoltage after fault – Initial SIR 10 - Line length 2 km Some snapshots of the Voltage are shown in Figure 3.5 to 3.8. Er is the voltage at the CVT output. Ea is the voltage at the CVT input. These snapshots were captured during the simulation with line length of 10 km and increasing SIR from 1 to 60. Please note the transient time constant and phase shift. 87/138 Figure 3.5: Peak overvoltage - Line length 10 km –SIR 1 Figure 3.6: Peak overvoltage - Line length 10 km –SIR 10 Figure 3.7: Peak overvoltage - Line length 10 km –SIR 30 88/138 Voltage (kV) 12.5 10.0 7.5 5.0 2.5 0.0 -2.5 -5.0 -7.5 -10.0 Er Ea Figure 3.8: Peak overvoltage - Line length 10 km –SIR 60 From this study, the following observations are derived: 1. The application of the resistor increases the SIR ratio. The increase of the SIR ratio decreases the voltage at the relay point during a fault and increases the magnitude and phase shift of the transient overvoltage in respect to the steady state overvoltage 2. Transient overvoltage decay between 2 and 4 cycles after the fault event. The overvoltage decays with a longer time with high SIR ratio. This phenomena is a consequence of the voltage gap between the pre fault and post fault steady state. Transient components are also highlighted from the overvoltage snapshots 3. The results are consistent throughout the 4 simulations. The results are also in line with previous studies [24, 25, 27]. 4. The four simulations produce similar results at the same SIR ratio as shown in Figure 3.9 to 3.12. These results confirm that grounding the system via the resistor do not have a peculiar impact on the CVT performance. The critical element for the transient results is the SIR. It influences more than the length of the transmission line or the source impedance. A high SIR will generate a significant voltage depression at the CVT location. 89/138 Overvoltage Comparison- SIR 10 Overvoltage (pu) 10 8 Simulation 1 6 Simulation 2 ime 4 Simulation 3 Simulation 4 2 0 10 30 50 70 Time (ms) Figure 3.9: Overvoltage comparison - Line length 10 km –SIR 10 Overvoltage Comparison- SIR 20 Overvoltage (pu) 20 15 Simulation 1 Simulation 2 10 Simulation 3 Simulation 4 5 0 10 30 50 70 Time (ms) Figure 3.10: Overvoltage comparison - Line length 10 km –SIR 20 90/138 Overvoltage Comparison- SIR 30 Overvoltage (pu) 25 20 Simulation 1 15 Simulation 2 10 Simulation 3 Simulation 4 5 0 10 30 50 70 Time (ms) Figure 3.11: Overvoltage comparison - Line length 10 km –SIR 30 Overvoltage Comparison- SIR 60 Overvoltage (pu) 50 40 Simulation 1 30 Simulation 2 20 Simulation 3 Simulation 4 10 0 10 30 50 70 Time (ms) Figure 3.12: Overvoltage comparison - Line length 10 km –SIR 60 5. The size of the capacitance has an impact on the transient overvoltage produced by the CVT [24, 27]. Three snapshots shown with a higher Capacitance of 200, 400nF of 1000 nF were recorded as shown on Figure 3.13 to 3.16. 91/138 Figure 3.13: Overvoltage comparison - Line length 10 km –SIR 10-Capacitance of 100 nF Figure 3-14:Overvoltage comparison - Line length 10 km –SIR 10-Capacitance of 200 nF Figure 3.15:- Overvoltage comparison - Line length 10 km –SIR 10-Capacitance of 400 nF 92/138 Figure 3.16: Overvoltage comparison - Line length 10 km –SIR 10-Capacitance of 1000 nF The graphs show that the fist peak decreases from 8.12 kV, with a capacitance of 100 nF to 4.64 kV with a capacitance value of 1000 nF. Decay time is also reduced. These results confirm that CVT manufacturers need to consider the size of the capacitance which needs to be traded off with the higher cost of large capacitors. 6. To verify the CVT transient performance in relation to the power factor of the relay burden, three different simulation with SIR ratio of 10 and burden power factor of 1, 0.7 and 0.1 were performed. Voltage (kV) 10.0 8.0 6.0 Er Ea 4.0 2.0 0.0 -2.0 -4.0 -6.0 Figure 3.17: Overvoltage comparison - Line length 10 km –SIR 10-PF 1 93/138 Voltage (kV) 10.0 8.0 6.0 4.0 2.0 0.0 -2.0 -4.0 -6.0 -8.0 Er Ea Figure 3.18: Overvoltage comparison - Line length 10 km –SIR 10-PF 0.7 Figure 3.19: Overvoltage comparison - Line length 10 km –SIR 10-PF 0.1 The results show that the CVT transient characteristic is affected by the inductive burden. Therefore, it is customary to keep the voltage input relay burden as close as possible to unity power factor. Therefore, digital relays with their resistive burden perform better than the old electromechanical relays with the inductive coil. 7. CVT transients are also affected by the magnitude of the connected burden[24]. A simulation has been conducted to determine the response of the CVT with a SIR 30 and a burden of 100000 Ohm 94/138 15.0 Er Ea Voltage (kV) 10.0 5.0 0.0 -5.0 -10.0 -15.0 Figure 3.20: Overvoltage comparison - Line length 10 km –SIR 10-Burden 10000 Figure 3.21: Overvoltage comparison – Additional simulation- Line length 10 km –SIR 10Burden 100000 The benefit of the additional damping resistor is confirmed as per existing literature [25, 27]. 8. The post fault voltage is the result of the superpositions of several frequency components. To simplify the analysis we can assume that four main frequency components are the major elements: Power frequency component High frequency decay component Low frequency decay component 95/138 DC component. A specific analysis was done on the 10 km model with SIR ratio of 10, 30 and 60 using the Fast Fourier Transformation tool available in PSCAD. Snapshots were taken at the first peak, 45 ms and 105 ms after fault injection. Base frequency was set to 12.5 Hz with 31 harmonics setting. These settings allow monitoring of the noise with a frequency lower than the power frequency components and up to 350 Hz. DC decay components graphs are also provided. SIR 10 – Frequency Response Plots f MAG 1 5 .0 -1 5 .0 kV [13] 0.142098 Figure 3.22: Sir 10 – Frequency response 5 ms after the fault f MAG 1 5.0 -1 5.0 kV [6] 0.735262 Figure 3.23: Sir 10 – Frequency response 45 ms after the fault 96/138 f MAG 15.0 -15.0 kV [6] 0.822083 Figure 3.24: Sir 10 – Frequency response 105 ms after the fault SIR 30 – Frequency Response Plots f MAG 15.0 -15.0 kV [6] 8.43448 Figure 3.25: Sir 30 – Frequency response 5 ms after the fault f MAG 1 5 .0 -1 5 .0 kV [6] 7.99076 Figure 3.26: Sir 30 – Frequency response 45 ms after the fault 97/138 f MAG 1 5 .0 -1 5 .0 kV [6] 2.11216 Figure 3.27: Sir 30 – Frequency response 105 ms after the fault SIR 60 – Frequency Response Plots f MAG 1 5 .0 -1 5 .0 kV [6] 8.92664 Figure 3.28: Sir 60 – Frequency response 5 ms after the fault f MAG 1 5 .0 -1 5 .0 kV [6] 8.15062 Figure 3.29: Sir 60 – Frequency response 45 ms after the fault 98/138 f MAG 15.0 -15.0 kV [6] 2.15804 Figure 3.30: Sir 60 – Frequency response 105 ms after the fault The DC component contained in the signal is shown on Figure 3.34 and 35. As expected, the sudden changes produced by the fault produces a decay a-periodic component damped approximately after 60ms DC 2.0 -2.0 kV [1] -0.802959 Figure 3.31: DC component 5ms after the fault DC 2.0 -2.0 kV [1] -0.0367069 Figure 3.32: DC component after 60ms after the fault 99/138 3.5 CVT Conclusion This study did not find any relevant issues on the CVT performance when a resistor is used in the grounding of the voltage source. Transient overvoltage magnitude, voltage waveform, frequency response and time constant results obtained using the PSCAD software package and the simplified CVT model are in line with the existing body of knowledge. The difference of magnitudes between the steady state voltage pre fault and after fault, which is well represented by the System Impedance Ratio, SIR, is the key element in determine the transient response of the CVT and the impact on the distance protection scheme. This study confirms that the transient overvoltages generated by the overall power systems is made worse by the CVT transient performance. 100/138 4 Distance Protection Scheme 4.1 Introduction Distance protection scheme is extensively implemented in subtransmission and transmission lines. The popularity of this protection scheme is due to its inherent simplicity of implementation, the relative cost and the speed of operation. Distance protection relays are divided in two main characteristic groups: MHO characteristic, also called admittance characteristic. The zone reach, is represented by a circumference that passes through the origin of the X/R plane providing an inherent directional protection capability Quadrilateral characteristics. The quadrilateral shape is made by four reaches in the four directions. The setting reach of each element can be usually controlled independently With the advent of digital technology other impedance characteristics such as elliptical and polygonal have been implemented by relay manufacturers. However, this research will focus on the Mho characteristic which is still a point of reference for protection engineers. In particular, this investigation now pays attention to the accuracy and operating time of the relay to determine how they are affected by transient overvoltages. In fact, it is a standard practice to assess the performance of the relay in terms of accuracy and operating time [4]. The accuracy of the distance reach is a comparison of the measured impedance with the actual impedance. In theory, if correct current and voltage are fed to the relay, and the relay is set with the exact 101/138 impedance data, the distance protection scheme is immune from malfunction or incorrect measurement. In reality the distance protection is not just Z= V/I [4].The operation and the technical performance of the relay can be affected by a large variety of elements such as system configuration, load current, system data, power swing, transients, location of the fault and fault resistance. Therefore, the accuracy of the distance protection relay varies according to the specific application. The operating time, which is the time between the fault and the tripping of the relay output contact, is another key element of the distance protection. In the old electromechanical relays the magnitude of the voltage and current measured by the protection relay had a relevant impact on the performance of the protection schemes. Current and voltage would determine the operating torque of the relay. The latest digital relays have more consistent performance independent of the magnitude of the measured quantities. In terms of accuracy and operating time a critical factor to determine the performance of a distance protection relay is the system impedance ratio, SIR. SIR= Zs/Zl Where: Zs =Source impedance Zl = Line impedance SIR ratio is a term commonly used in the industry. Relay manufacturers use the SIR as reference to specify the performance of their protective devices. The vendors specifies the accuracy of the impedance calculation with ± 3 % error with a SIR lower than 30 [26-29] The same manufacturer also guarantee relay operation 102/138 within two cycles with SIR below 30. In fact, this relays are often named “ two cycle relays”. New digital relay techniques are expanding the SIR limit to 60 [27, 30].At the same time relay manufacturers are now producing relays with excellent accuracy and operating time within one cycle. These relays are often called “one cycle relay” The relevance of the SIR has been successfully captured by IEEE Standard C37.113-1999.”IEEE Guide for protective Relay Application For Transmission Lines”[31]. Preferred protection schemes for transmission lines are classified by the SIR. Three types of lines are defined in the IEEE Standard: 1. Long line with SIR below 0.5 2. Medium line with SIR smaller than 4 and larger than 0.5 3. Short line with SIR above 4 Implementation of the neutral earth resistor increases the source impedance and, therefore, the source impedance ratio. Strong source with a high fault current usually have a low SIR and vice versa. Weak infeed source have high SIR value. From a transmission line point of view, we can also state that, short line have a lower line impedance and, therefore, a higher SIR. As result, it is more appropriate referring to the SIR instead than weighting Zs and Zl magnitude on isolation. With a good approximation it is possible to determine the voltage at the relay location with the following equation: Vr=1/ ( 1+ SIR) 103/138 For a phase to ground fault, more precise computation of the voltage at the relay point can be performed by using this formula: [32]: SIR= Zs/ Zl Where Zs= 2Zs1 + Zs0= Z s1 * (2+Zso/Z s1)= Z s1 ( 2 + p) Zl= 2Zl1 + Zlo = Z l1 * (2+Zlo/Z l1)= Z l1 ( 2 + q) And p= Zso/Z s1 q= Zlo/Z l1 In the event of a fault at the zone reach, it is possible to determine the voltage at the relay by using the following formulas [32] Vr= (1 /( (Zs/Zl) * (( 2+ p)/ ( 2+ q))) V Vr 1 2p (Zs/Zl) * ( ) 1 2q Vl n The impedances in the above formulas refer to the setting reach. This means that if the fault is closer to the relay, SIR will increase and the voltage will decrease. Using PSCAD software and modeling a simple radial system made by the source, a 220/66kV delta/star transformer, and a transmission line. In Figure 4.1 to Figure 4.4, the relation between the SIR, voltage and fault current at the relay point is highlighted. The study was done with a line length of 2, 5 and 10 km. The curve 104/138 points were determined by increasing from 0 Ohm, the value of the NER in steps of 2 Ohms to 30 Ohms. Results are shown in Figure 4.2, 4.3 and 4.4. V at the Relay Fault Current Line 2 km 1.200 Vr an If in pu 1.000 0.800 0.600 0.400 0.200 0.000 4 4. 3 8. .2 12 .1 16 .0 20 .9 23 .8 27 .7 31 .6 35 .5 39 .4 43 .3 47 SIR Figure 4.1: Voltage and Current at the relay point as a function of SIR- Line length 2 km Line 5 km V at the relay Fault Current Vr and If in pu 1.200 1.000 0.800 0.600 0.400 0.200 0.000 8 1. 3 3. 9 4. 4 6. 0 8. 6 9. .1 11 .7 12 .2 14 .8 15 .3 17 .9 18 SIR Figure 4.2: Voltage and Current at the relay point as a function of SIR –Line length 5 km 105/138 Line 10 km V at the Relay Fault Current Vr and If in pu 1.200 1.000 0.800 0.600 0.400 0.200 0.000 9 0. 7 1. 4 2. 2 3. 0 4. 8 4. 6 5. 3 6. 1 7. 9 7. 7 8. 5 9. SIR Figure 4.3: Voltage and Current at the relay point as a function of SIR- Line lenght 10km The increase of the resistor will decrease the voltage at the relay location. Moreover, the increase of the line length will decrease the value of the SIR. It is anticipated by the existing literature [24, 25, 27, 31, 39] that the reduced voltage supplied to the distance relay is in fact a major challenge to the functionality of the distance relay. 106/138 4.2 MHO Characteristics Theory Distance relays measure the impedance in the impedance plane to determine if the measurement is within the reach boundary. To accomplish this result the relay compares the magnitude or phase of two different quantities. In the early stage, since 1920s’, relay manufacturers, for instance Siemens in Germany, employed a line replica impedance to determine if the fault was in the protected zone [33]. To the contrary, English and American manufacturers mainly used an induction cylinder comparator which, according to the torque produced by the current [34] , will operate the tripping mechanism. In both cases, phase comparison was the preferred method to implement the distance protection scheme. The Mho characteristics was a natural outcome of this technology [35]. Therefore, the Mho impedance relays had the majority of attention from the researchers and quadrilateral characteristics appeared on the market only in the late 70’ with the first static relays. As anticipated, in the Mho relay, the basic of the distance protection is achieved by comparing the angle between two voltages which are commonly named the operating signal and the polarising signal. The operating signal is the vectorial subtraction of the voltage produced by the zone reach impedance times the fault current and the voltage measured during fault. S1= I Z – V The polarising signal Voltage IZ is instead the voltage measured during fault V S2= V 107/138 The angle between these two vectors will determine if the fault is inside or outside the zone reach. It is useful reviewing how this is achieved [32-34, 36, 37]. The voltage across the fault impedance, IZ, represents the diameter of the Mho characteristics in the event that the measured impedance Z is equal to the zone reach. In this condition, the angle opposite to IZ is always 90 degrees once intercepts the circumference. Figure 4.4: MHO self polarised- Fault at the zone reach 108/138 Figure 4.5: MHO self polarised- Fault within the zone reach Consequently, if the angle between the operating signal and the polarising signal is less than 90 degrees the impedance is within the zone reach. As shown in Figure 4.5, the angle will move towards 0 degrees as the fault moves towards the relay point [36]. 109/138 Figure 4.6: MHO self polarised- Fault outside the zone reach If the impedance Z is outside the zone reach this angle will be above 90 degrees. 110/138 5 Transient Overvoltages and Distance Protection: Solutions 5.1 Introduction In Section 2 and 3 this research has illustrated that, after fault inception, the power frequency voltage fed to distance protection relay is superimposed by transients generated by the power systems and from the CVT. In Section 4 this study has also highlighted that correct calculation of the zone reach relies on the correctness of the voltage magnitude and angle implemented in the distance algorithm. Besides, using the resistor for grounding will increase the SIR with consequent reduction of the available voltage at the relay location. This research is mainly concerned about the accuracy of the distance measurements As the impedance settings are defined at the power frequency, it is required that the protection relay shall be able to keep the fundamental frequency and reject the other frequency components before data processing is initiated. If a distorted signal is fed to the relay, the relay will perform an incorrect computation of the impedance leading to overreach or underreach measurements. In other words, the relay could see a fault outside the zone reach as if it is inside the protected zone (Underreach problem) and execute the trip command to the circuit breaker. Vice versa, voltage over estimation could determine that a fault inside the zone reach could be seen as that outside the zone reach (Overreach phenomena). The same type of errors could be determined if the voltage noise produces a significant phase angle error. 111/138 While few static distance protection relays are still in use, the study will focus only on the latest generation of numerical protection relays as implemented worldwide in the last 10 years. Modern digital filtering techniques have dramatically improved the performance of the distance protection relays by optimizing the following requirements: Quality of the voltage input to the relay Operating time Cost Reference [38] provides a complete background of the purpose and characteristics of the filters. Although the latest digital filtering techniques have made significant improvements, relay manufactures do not guarantee that the voltage used for the impedance computation will be noise free [35, 37, 38, 44, 45]. Therefore, further engineering techniques are required to enhance the performance of the protection relay. 112/138 5.2 Polarisation Techniques The Mho characteristic relay performs the impedance calculation by comparing two voltage signals, commonly known as operating signal, S1, and polarising signal, S2. S1= Operating V = I fault* Z settings – V meas. S2= Polarising signal= V measured This technique, commonly named Mho self polarised technique, uses the voltage measured during the fault without any signal modification as polarising signal. As the fault gets closer to the relay location, the voltage signal fed to the protection relay will decrease to the point to be so small that it will not allow a reliable computation of the phase comparison algorithm. In particular, the voltage measured could not be sufficient to determine if the fault is on the line side or on the bus side of the voltage transformer placing at risk the inherent directionality of the Mho characteristics [25, 30, 31, 39, 41]. For the old electromagnetic relays the minimum requirement to operate correctly was about 1 V [33]. For the modern digital relays the lower limit is approximately 0.1 V[33]. To overcome these problems, protection engineers have developed several techniques to manipulate the polarizing signal to ensure correct impedance calculation and determination of the direction of the fault. These techniques have been known as” polarisation signal techniques”. The end result of all these engineering methods is expanding the Mho circle to protect the impedance area around the X-R origin without affecting the inherent 113/138 directionality of the Mho characteristic. Besides, the Mho circle is also expanded in the R axis direction which provides a better fault resistance coverage. In other words, the circle is lowered and expanded in the impedance plane to fully cover the area of the origin of the axis. Mho expansion example: Zs= 1 Ohm Z setting= 1 Ohm Memorising setting = 20 % = 0.2 pu Vr=1/ ( 1+ SIR) Mho expansion = [(Polarizing Setting)/(Setting + 1)] . Zs=[27] = (0.2/ 2) * 1= 0.1 pu=10 % 114/138 Figure 5.1: MHO characteristics- Reach expansion with polarising techniques Polarising techniques achieve this result by boosting the polarising voltage. There is a wide literature about the available polarising techniques which also take into consideration critical factors such as fault resistance, load flow and single pole auto-reclose function [25, 30, 40, 41]. Given below is a summary of these techniques: 1. Cross polarisation. The phase to phase voltage between the healthy phases is used. The voltage Vbc is rotated of 90 degrees to be in phase with the faulty phase Va 2. Median.The phase A to the median point of the healthy phase Vbc implemented 115/138 is 3. Lagging and leading polarisation. When a phase to ground fault takes place, another technique is adding a percentage of the lagging or leading healthy phase voltage to the faulty phase voltage. Lagging phase will be added by rotating the vector of 120 degrees. Contrary, leading phase voltage will be added by adding to the vector 120 degrees [35]. The two polarising techniques are similar with the end result of “boosting” the polarizing signal. 4. Faulty phase memory polarisation. This technique consists in using the voltage memorised as polarizing signal. In the past, with analog relays, the memory was available only for few cycles. With digital relays , in theory, the memory does not have any time limit. However, frequency compensation would be required for long length widow to avoid any maloperation Usually the signal used refers to 2 to cycles before the starting element of the distance protection picks up. 5. Positive sequence voltage memory polarisation. With the advent of digital relays, it is standard practice to derive the symmetrical components from the phase values and used those values in the algorithms defined in the relays. Therefore, it is possible to use the positive sequence memory as a polarizing signal 6. Hybrid Polarisation. It must be noted that each polarizing technique can be designed according to the quantity and percentage of each technique used. For instance an hybrid technique could refer to a polarising signal which is made by 50 % of self polarised an 50 % of cross polarisation. 7. Adaptive Polarisation. Latest advance in digital technology have allowed relay designers to accommodate different requirements in the distance protection algorithms. This philosophy which is called adaptive protection is well described in Reference [35]” Adaptive protection is protection philosophy which permits and seek adjustment in various protection 116/138 functions automatically in order to make them more attuned to prevailing power system conditions”. This techniques have created adaptive algorithms that switch from a polarising signal to another according to the voltage at the relay point and the time elapsed from fault inception create Modern digital relays implement adaptive algorithms to detect the best polarizing signal. 5.3 Polarising Techniques This section is to pay attention to the polarising technique implemented in five modern digital relays[27, 29, 30, 39, 40]. Siemens 7SA522 offers to the User the ability to determine the percentage of self and memorized voltage for the polarising signal. The memory polarisation is only used if the available phase to neutral voltage is above 40% of the nominal phase to ground voltage. The threshold is set to 70 % for the phase to phase voltage. Below these thresholds the algorithm uses the cross polarisation voltage. Default setting for both polarisation is 15% with a maximum of 100%. Therefore, the self Polarisation is kept at 85% but could vary from 0 to 100 %. The relay offers independent settings for the phase to ground and phase to phase measuring loops. Even Areva P543 uses a combination of memorizing and self polarised voltage. The User shall determine the best composition of the memory and cross polarised voltage prior to relay configuration. The memorizing voltage can vary between16 % to 83 % of the overall polarising signal. The memorizing voltage is taken from two cycles before fault and is used for 16 cycles after the loss of the voltage supply. After this period, cross polarised voltage is used. Schweitzer SEL 311 relay fully implements the memorised positive sequence voltage as polarising signal. 117/138 ABB-REL 670 employs a memorizing voltage. The memorized voltage is used for 5 cycles and refers to 2 cycles before fault detection. After 100 ms few conditions are checked to determine if a genuine fault is taking place. More details are provided in the Reference [39] General Electric Multilin D30 uses the memory voltage if the actual voltage is below 80% of the nominal voltage. After the memory timer elapsed the voltage is checked. If the voltage is above 10%, the actual voltage is used. Otherwise, the memorised voltage is still used. This brief reviews of five modern distance relays shows that there is a clear choice to use the entire or a percentage of the voltage memory as polarising signal. The use of this voltage will also prevent the feeding of a voltage signal which contains the transient disturbance on the healthy and faulty phases to the relay. The voltage sample used refers to 2 cycles before the fault inceptions. This time gap is considered satisfactory as compromise between two different requirements: Using a voltage sample as close as possible to the fault inception. This will prevent that a frequency change in the network could cause a phase error in the calculation Use a voltage sample recorded well before fault inception to fully prevent a post fault noise being memorised in the relay It is noted that some relays allow the users to determine the composition of the polarising signal [8, 13]. The author suggests that in the future this capability could be implemented by all the relay manufacturers in the next series of distance digital relays. 118/138 5.4 CVT Techniques Modern distance digital relays employ a wide variety of techniques to reduce the negative impact created by CVT transients. Precise details of the algorithms are not published by the Manufacturers who need to protect their intellectual properties. Besides, modern relays use parallel and different computation techniques to validate the measured fault impedance during high SIR condition. All these algorithms obviously are not published in relay manuals. However, relay manuals and existing literature provide some useful information on the algorithms and CVT compensation techniques implemented in modern relays. Areva P543 allows the User to select the type of ferroresonance suppression used in the CVT. At fault inception, the relay will determine the SIR and apply a delay of 5 ms if the SIR is above 2 for active filters. The same delay is applied with the passive filters when the SIR is above a selectable value varying from 5 to 60. SEL 311 relay delays the operating time of Zone 1 reach of 30 ms either if SIR above 5 is detected or the CVT has an active ferroresonance-suppression circuit. Latest technology also provide CVT transient compensation function using customised CVT transient filtering and impedance estimation techniques. GE D30 relay implements a patented special digital filter designed to cope with CVT transients. The relay calculates the SIR and adjusts the voltage signal and the operating time to prevent relay overreach There is no doubt that digital relays are now able to detect CVT transient conditions and, at the same time, calculate the SIR[24]. These CVT transient detection logics determine the required time delay between 20 and 60 ms before issuing the trip command. The time delay will allow the transient to decay and lower the likelihood to have some errors in the impedance measurements at the 119/138 start. The CVT algorithms are also able to recognize if it is a close in fault. In this event the CVT logic will be bypassed to provide a fast protection trip. Another technique includes applying a time delay to CB trip in the zone before the Z1 setting reach. This zone is the most critical area for relay accuracy. An error on the computation of the fault impedance could lead to maloperation as the relay could “overreach” or underreach[25].” There are also researches on new digital filtering methods to include Finite Impulse Response filter with a longer window length in the pre-filtering area of the relay and full cycle Fourier algorithms and least square methods for the phasor estimation [41]. FIR filter performances are dependant on the window length. Longer window allows increasing the error on the measured value. To the contrary, decreasing the window length will improve the operating time but, inevitably, will increase the error on the measured voltage. 120/138 5.5 Setting Advice Modern filtering techniques, CVT adaptive algorithms and the use of memorised voltage as a polarising signal have dramatically improved the performance of the distance protection relays. Nevertheless, protection engineers are still required to “ tune” the distance protection during the preparation of the relay setting for each specific project. In relation to the protection settings, the following items should be considered: 1. Liaise with the planning engineer to determine the size of the neutral earth resistor and consequent SIR. For instance, designing a SIR below 25 at Zone 1 reach will usually ensure adequate relay performance. Please note that SIR is calculated at the end of the line 2. Contact the CVT Manufacturer to determine if the device is provided with an active or passive ferroresonance suppression circuit. Usually this information is not provided in the primary and secondary drawings. Although the CVT will comply with the IEC standard accuracy requirements, the knowledge of the type of suppression circuit will give more confidence in the estimate of the CVT transient behavior 3. Estimate the expected post fault transient overvoltages (magnitude and time to decay), based on system earthing, power system characteristics, SIR, CVT characteristics including ferroresonance suppression filter and relay performance. Although a precise figure can’t be determined unless a power system study is performed, the above data and the existing literature as listed in the Reference should be sufficient to complete the exercise 4. Select the polarising technique according to the estimation above and the SIR at the end of zone 1 reach. The design shall consider the SIR excursion under minimum and maximum fault levels. For the minimum fault level, the 121/138 worst case scenario of a single ( N-1) or double contingencies (N-2) should be adopted according to the project/client requirements 5. Implement multiple group protection settings in the relay to adapt the protection scheme to different system configuration and different SIR 6. Apply a constant time delay to zone 1 longer than the CVT transient. This solution is not dynamic and penalizes fast fault clearing time for close in faults or low SIR condition 7. Reduce the distance reach of Zone 1(instantaneous trip) to less than the traditional 80-85 % 8. Limit the use of distance protection, where practicable, to transmission line with a SIR of less than 25 [33] or higher if specific type of relays are implemented 9. The majority of modern distance relays offer the capability to implement 4 [30] or 5 [27, 39, 40] zones. According to the application a zone could be used to divide zone 1 in two zones, a fast zone and a slow zone. The first zone covers the safe reach area of the line, for instance 60% of the line. The second zone, Z1 “slow”, will cover the reach between 60% and 85% with a time delay longer than the CVT transient. The time delay could vary between 20 and 60 ms 10. CVT transient performance is improved if the transformer is adequately loaded. Considering that modern digital relays have a small burden, it is good engineering practice to increase the load connected to the CVT by using a resistor. The load shall be above 50 % the nominal rating of the CVT[33] 11. Test the protection settings using different SIR to verify and ensure that the performance of the relay is not affected by the reduced input voltage. 122/138 12. Verify the type of polarisation used in the relay to determine the Mho dynamic expansion and additional resistance coverage provided. Implementation of the neutral earth resistor decreases the fault current and , therefore, increase the arc resistance as calculated using the Warrington’s formula. R arc 28700 * length of the arc I arc1.4 If required, the use of quadrilateral characteristics might be considered for this type of application 13. Protection settings shall consider the system stability requirement. In Australia, the Australian National Electricity Rules, NER, Chapter 5,[33] Clause S5.1a.8 [28], requires that the primary protection system during a fault should operate within the relevant time as detailed in Column 2 of Table 1: TABLE 4-I: -NER- FAULT CLEARING TIME Nominal voltage kV Time(milliseconds) Primary Prot 400 kV and above 80 End of line Prot 100 Back up Prot At least 250kV but less than 400 kV More than 100 kV but less than 250 kV Less than or equal 100 kV 100 120 250 120 220 430 175 As necessary to prevent plant damage and meet stability requirements 123/138 On the 66 kV network the application of a time delay between 60 and 85 % of Z1 reach will not affect system stability and the overall performance of the overall protection scheme. For instance, in the Melbourne metropolitan area, system stability could be affected only if a fault is not cleared within 600 ms. The critical fault clearing time exceeds 1000 ms in the Victorian regional area. In a 220 kV network, a small time delay could also be applied. For instance, applying a 20 ms time delay with a modern CB and protection relay, the total CB operating time would be still within the 120 ms limit 124/138 6 Conclusion 6.1 Research Findings The major findings of this research are the following: After a phase to ground fault, the power system generates transient overvoltages. Maximum overvoltage is influenced by all the power system parameter. In particular, the method of earthing was found to be critical. Designing the resistor to limit the phase to ground fault to 10% of the fault current with a solidly earthed system, will contain the transient overvoltages below 3 pu. Time and location of the fault are the other main factors to determine the magnitude and on which phase the maximum overvoltage is recorded. Modern distance relays are capable to operate correctly during the transient period that follows a phase to ground fault. Modern distance relays are provided with digital filters, adaptive algorithm, polarising techniques to overcome the issues created by the transient overvoltages. In the event of a fault with a high source impedance ratio, SIR, the available voltage to the distance relay could be so small to impact the functionality of the relay. In particular, accurate computation of the fault direction and fault loop impedance could be affected. The use of memorising voltage overcomes these issues as well as prevents feeding the relay with a distorted voltage signal caused by the power system itself and, in particular, the CVT transient behavior. To conclude, the results of this research show that fault current limitation and consequent reduction of the thermal stress and aging of the equipment are successfully supported by modern distance relays Distance relay performance can be assessed according to the SIR. This factor provides a correct indication of how the relay performs under transient 125/138 overvoltage conditions. Modern digital relays provide accurate and fast operation with SIR below 30. Applying a typical engineering safety margin, sizing of the NER which produces a SIR above 25 should be evaluated in the early stage of a project Although the satisfactory performance of digital distance relays, preparing the protection settings and determining the correct balance between operating time and accuracy is still a critical activity for protection engineers. This study provides protection setting advices to support the implementation of modern distance protection relays on short lines, ineffective grounding system and weak impedance source 126/138 6.2 Areas for Further Investigation Considering the overvoltage data available, together with the analysis performed on overvoltage and distance protection, this Thesis could be used as starting point to perform further investigations. In the power system analysis field, the author advocates similar studies using a neutral earth reactor in the grounding of power system. This study will facilitate the comparison of the transient response between the resistor and the reactor. The results will be beneficial for the planning activity of Utilities and large industrial plants. It is also advisable to expand this study by modeling in details the substation and the surrounding grid and reperform the same analysis. Results obtained could be used to generate guidelines for power system modeling and allowable model simplifications in relation to transient overvoltage studies. In the distance protection areas, it is envisaged to perform further studies in regards to the percentage of memory or cross polarisation as a function of the neutral earth resistor and /or the source impedance ratio. Relay manufactures have not provided clear design instruction in relation to the typology and size of the earthing connection and calculated SIR. This study should also take into consideration load flow and fault resistance. It would be also recommended to test the proposed algorithms in a three terminal line. This line configuration is becoming more frequent as medium and small wind solar farms connection applications have been increasing in recent years. Besides, implementation of the resistor and consequent fault current reduction creates some difficulties to the fault detection function, often termed as starting element, of the distance relay. Although modern relays are equipped with algorithms that use voltage or different techniques to differentiate genuine faults to 127/138 a simply heavy load current, it is believed that further researches could be performed. This study could be also used to review the traditional guideline used by protection engineers for the zone one reach setting. Zone one is typically set to 80 or 85 percent of the protected line. Consideration of modern CVT and relay performances, together with expected fault current and SIR, could be used to provide newest insight on the matter. Lastly, distance protection scheme is often used to provide primary or back up protection to power transformers. It is envisaged to perform additional studies on this scheme, and, how the size of the resistor could be used to improve the functionality of the distance protection relay. 128/138 7 References [1] J. Roberts, H. J. Alluve, and H. Daqing, "Review of Ground Fault Protection Methods for Grounded, Ungrounded, And Compensated Distribution Systems," 1996. [2] R. Lavorin, D. Hou, J. Altuve, N. Fisher, and F. Calero, "Selecting Directional Elements for Impedance Grounded Distribution Systems," Washington: SEL Labortories, 2007. [3] Areva, "System Earthing," in Analysis and Protection of Power Systems Course Sydney: Areva, 2006. [4] Alstom, "Network Protection & Automation ", 2006. [5] D.Fulchiron, "Overvoltage and Insulation Coordination in MV and HV," in Cahier Technique Merlin Gerin. vol. 151, S. Electric, Ed.: Schneider Electric, 1995. [6] H. A. Peterson, Transients in Power Systems. New York: John Wiley & Sons,Inc. New York -Chapman & Hall,LTD.London, 1951. [7] ABB, Transformer handbook, 2003. [8] E. C. Clarke, S.B.;Peterson,H.A;, "Overvoltages during Power-System Faults " Transactions of the Institute of Electrical Engineers of Japan, Part B, vol. v58, pp. 377-385, Aug-1939 Aug 1939. [9] IEEE, "IEEE guide for the application of neutral grounding in electrical utility systems, part V - transmission systems and subtransmission systems " IEEE Std C62.92.5-1992, 1993. 129/138 [10] A. Switchgear, Protection application Handbook. Vastera,Sweden: ABB Switchgear, 1999. [11] IEEE, "IEEE recommended practice for grounding of industrial and commercial power systems," IEEE Std 142-1991, 1992. [12] F. J. Angelini and D. D. Shipp, "Characteristics of different power systems neutral grounding techniques: fact and fiction," Greenville, SC, USA, 1991, pp. 8-1. [13] I. Uglesic, L. Delbianco, and S. Babic, "Overvoltages provoked by faults in the distribution electrical network," in Proceedings of the Mediterranean Electrotechnical Conference - MELECON, Lemesos, Cyprus, 2000, pp. 895-898. [14] A. Greenwood, Electrical transients in power systems 2nd ed. ed. New York: New York : Wiley Interscience, 1991. [15] L. v. d. Sluis, Transients in Power Systems, 2001. [16] S. X. Shenxing, D.; Shuangxi, Z.;, "Analysis of Single-Phase-to-Ground Fault Generated Initial Travelling Waves," in 2005 IEEE/PES Transmission and Distribution Conference & Exhibition: Asia and Pacific Dalian, China IEEE, 2005. [17] S. Moorthy, Electrical Energy Systems. Melbourne: RMIT University, 2004. [18] IEEE, "IEEE guide for the application of neutral grounding in electrical utility systems, part V - transmission systems and subtransmission systems IEEE guide for the application of neutral grounding in electrical utility systems, part V - transmission systems and subtransmission systems," IEEE Std C62.92.5-1992, 1993. [19] M. S. n. -V.Kamaraju, High Voltage Engineering, Second Edition ed. New York: McGraw-Hill, 1995. 130/138 [20] IEEE, "IEEE guide for the application of neutral grounding in electrical utility systems, part IV - distribution IEEE guide for the application of neutral grounding in electrical utility systems, part IV - distribution," IEEE Std C62.92.4-1991, 1992. [21] PSCAD-EMTC, PSCAD Software Manual vol. 1, 2007. [22] Cigre, "Guidelines for Representation of Transient Network Elements When Calculating Transients," in Study Commitee 33 ( Overvoltages and Insulation Coordination), Cigre, Ed. Paris: Cigre, 2000. [23] P. C. Tusaliu, C; Dias Pinto, J.A.;, "Neutral Influences about Disturbances at Switching Capacitor Banks in A 220kV Electrical Power System," in 38th International Power Engineering Conference Thessalonoik UPEC 2003, 2003. [24] D. Hou and J. Roberts, "Capacitive voltage transformer: transient overreach concerns and solutions for distance relaying," in Electrical and Computer Engineering, 1996. Canadian Conference on, 1996, pp. 119-125 vol.1. [25] B. Kasztenny, D. Sharples, V. Asaro, and M. Pozzuoli, "Distance Relay and Capacitive Voltage Transformers Balancing Speed And Transient Overreach," in 52th Annual Conference For Protective Relay Engineers, Markham, Ontario, 2000. [26] ABB, "REL512 Protection Relay Manual," ABB, Ed., 2008. [27] Areva, "P543 Relay Manual," Areva, Ed., 2008. [28] Siemens, "7SA5 Protection Relay Manual," Siemens, Ed., 2007. [29] G. Multilin, "D30 Protection Relay Manual," G. Multilin, Ed., 2008. [30] Schweitzer, "SEL 311 Manual," 2008. 131/138 [31] IEEE, "IEEE guide for protective relay applications to transmission lines," IEEE Std C37.113-1999, 2000. [32] Alstom, "Network Protection & Automation." vol. 1, 2002. [33] G. Ziegler, Numerical Distance Protection: Public Corporate Publishing, 2008. [34] E. O. Schweitzer and J. Roberts, "Distance Relay Element Design," in 46th Annual Conference For Protective Relay Engineers, Texas A&M University, 1993. [35] Cigre, "Modern Distance Protection Functions and Applications," Cigre, Ed., 2007. [36] G. Alexander and G. Andrichak, "Ground Distance Relaying: Problems and Principles," in 19th Annual Western Protective Relay Conference, Spokane, Washington, 1991. [37] J. Roberts and A. Guzman, "Z=V/I Does Not Make A Distance Relay," in 20th Annual Western Protective Relay Conference, Washinghton, 1993. [38] E. O. Schweitzer and D. Hou, "Filtering for Protective Relays," in 46th Annual Conference For Protective Relay Engineers, Texas A&M University, 1993. [39] ABB, "REL 670 Manual," ABB, Ed., 2007. [40] Siemens, "7SA522 Relay Manual," 2007. [41] D. Hou, A. Guzman, and J. Roberts, "Innovative Solutions Improve Transmission Line Protections," in 24th Annual Conference, 2002. 132/138 Western Protective Relay Appendix A 10th International Conference on Developments in Power System Protection, March 2010, Manchester, UK -Abstract 133/138 Abstract This paper investigates the relationship between post fault transient overvoltages and the functionality of the numerical distance protection. The study is conducted on a 66kV network with a neutral earth resistor as method to earth the power system. This paper begins by performing an extensive power system analysis on ground fault transient overvoltages. The study is conducted by using the PSCAD-EMTC software package. The results of this analysis are discussed to determine the impact of a disturbed voltage signal fed to the distance relay, with particular attention to the polarisation and CVT transient mitigation techniques as implemented by modem relays. Finally, this paper provides recommendation for the design of the protection settings of the distance relay. The results of this study show that fault current limitation and consequent reduction of the thermal stress and aging of the equipment are successfully supported by modern distance relays. Appendix B Overvoltage Study –PSCAD Data 134/138 Simulation 1 Variables StartSimulation Delay (s) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 88.86 88.86 88.83 88.82 88.78 88.75 88.62 88.69 88.72 88.76 88.79 88.80 88.81 88.82 88.83 88.83 88.83 88.83 88.83 88.83 88.83 87.37 87.61 123.29 123.30 88.50 88.36 88.14 87.77 87.26 86.61 85.91 85.25 84.93 85.05 85.36 85.76 86.15 86.37 86.77 87.05 87.33 87.84 87.84 87.84 87.84 87.83 87.83 87.79 87.80 87.80 87.80 87.81 87.81 87.81 87.81 87.81 87.81 87.82 87.82 87.82 87.81 87.81 84.98 85.01 124.87 124.89 84.15 84.17 84.20 84.25 84.31 84.31 84.32 84.36 84.45 84.55 84.58 84.60 84.67 84.76 84.84 84.91 84.95 86.68 86.69 86.70 86.69 86.69 86.69 86.65 86.66 86.66 86.66 86.66 86.67 86.65 86.64 86.64 86.65 86.65 86.65 86.65 86.64 75.27 76.76 76.41 74.06 73.20 73.71 73.23 73.02 73.05 72.95 73.59 73.72 73.45 73.90 74.12 73.96 74.01 74.06 74.13 74.13 75.33 125.63 125.70 87.68 87.67 126.22 126.19 126.14 126.19 126.18 126.08 126.12 126.06 126.00 126.01 125.94 125.84 125.85 125.84 125.71 125.74 125.63 75.43 76.95 76.64 74.32 71.81 72.56 72.26 71.99 72.51 72.37 72.09 72.23 72.22 72.05 72.19 72.01 72.01 72.04 72.12 72.19 75.48 124.12 124.14 87.85 87.88 124.16 124.14 124.13 124.12 124.12 124.12 124.13 124.15 124.13 124.11 124.09 124.07 124.05 124.03 124.02 124.06 124.11 75.57 77.14 76.86 74.57 71.23 71.79 71.68 71.19 72.17 72.25 71.71 72.33 72.56 72.29 72.09 72.41 72.35 72.24 72.28 72.28 70.32 70.53 70.55 71.31 71.14 72.55 74.57 77.48 81.28 83.08 82.80 80.51 76.25 70.57 70.69 70.62 70.69 70.72 70.75 70.69 70.38 72.68 72.98 86.13 86.13 73.32 73.29 73.48 73.45 74.22 74.93 75.98 78.61 79.32 78.05 74.86 72.66 72.42 72.49 72.55 72.63 72.68 71.76 71.10 71.97 73.29 73.01 73.79 75.72 77.79 81.59 83.37 83.07 80.75 76.45 71.11 71.17 71.10 71.10 71.12 71.16 71.27 71.73 72.81 72.62 85.20 85.22 72.91 73.76 74.24 73.09 74.70 75.44 76.10 78.74 79.46 78.21 75.02 73.02 72.64 72.89 72.92 72.88 72.83 74.08 73.32 73.92 75.13 74.73 74.98 76.83 78.09 81.88 83.65 83.33 80.99 76.66 72.96 73.29 73.54 73.32 73.23 73.02 73.65 88.86 88.86 88.83 88.82 88.78 88.75 88.62 88.69 88.72 88.76 88.79 88.80 88.81 88.82 88.83 88.83 88.83 88.83 88.83 88.83 88.83 125.63 125.70 123.29 123.30 126.22 126.19 126.14 126.19 126.18 126.08 126.12 126.06 126.00 126.01 125.94 125.84 125.85 125.84 125.71 125.74 125.63 87.84 87.84 87.84 87.84 87.83 87.83 87.79 87.80 87.80 87.80 87.81 87.81 87.81 87.81 87.81 87.81 87.82 87.82 87.82 87.81 87.81 124.12 124.14 124.87 124.89 124.16 124.14 124.13 124.12 124.12 124.12 124.13 124.15 124.13 124.11 124.09 124.07 124.05 124.03 124.02 124.06 124.11 86.68 86.69 86.70 86.69 86.69 86.69 86.65 86.66 86.66 86.66 86.66 86.67 86.65 86.64 86.64 86.65 86.65 86.65 86.65 86.64 1.65 1.65 1.65 1.65 1.65 1.65 1.64 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 2.33 2.33 2.29 2.29 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.33 2.33 2.33 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 2.30 2.30 2.32 2.32 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 2.30 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 71.69 72.64 72.33 72.60 72.61 72.52 72.41 73.00 73.03 72.79 72.72 72.63 71.84 72.56 72.20 72.37 71.54 71.42 71.98 71.52 71.62 71.83 72.55 90.01 90.45 90.35 72.53 72.99 72.71 72.93 72.38 72.70 72.08 72.07 72.28 72.48 72.73 72.14 72.09 71.95 72.18 71.84 67.17 67.21 67.25 67.30 67.36 67.70 67.64 67.57 67.51 67.45 67.39 67.33 67.29 67.25 67.21 67.19 67.18 67.18 67.18 67.20 67.23 71.00 71.53 99.31 99.30 99.67 71.22 71.14 71.09 71.08 71.10 71.13 71.18 71.22 71.24 71.23 71.19 71.09 70.93 70.70 70.49 70.94 58.36 58.37 58.39 58.36 58.37 58.39 58.40 58.41 58.42 58.43 58.44 58.45 58.46 58.45 58.44 58.44 58.43 58.43 58.43 58.44 65.58 67.82 68.39 67.28 64.55 63.82 63.78 63.78 63.82 63.86 63.91 63.95 63.99 64.02 64.05 64.07 64.08 64.08 64.07 64.06 65.60 89.75 89.70 71.95 72.12 72.12 89.73 89.35 89.35 89.22 89.49 89.39 89.24 89.26 89.42 89.52 89.37 89.23 89.10 89.36 89.61 89.73 66.01 67.82 68.39 67.28 64.55 60.41 61.04 61.72 62.45 63.20 63.97 64.72 65.43 66.07 66.61 67.01 67.26 67.31 67.13 66.71 66.01 78.31 78.44 62.95 62.85 62.78 78.20 78.11 78.13 78.18 78.24 78.31 78.27 78.13 78.06 78.06 78.16 78.32 78.16 77.95 78.32 78.32 69.15 67.82 68.39 67.28 64.55 64.80 65.24 65.74 66.31 66.94 67.62 68.32 69.02 69.70 70.31 70.79 71.09 71.16 70.91 70.28 62.82 62.80 62.78 62.75 62.72 62.68 62.66 62.68 62.70 62.74 63.79 65.55 65.69 64.24 62.86 62.88 62.88 62.89 62.88 62.87 62.86 66.04 66.06 66.08 66.11 66.12 66.14 66.15 66.15 66.15 66.15 66.14 66.12 66.29 68.42 68.87 67.65 65.99 65.99 66.02 66.04 66.06 78.05 77.51 76.81 75.95 74.92 74.99 75.33 75.70 76.10 76.52 76.93 77.34 77.73 78.07 78.37 78.59 78.72 78.75 78.65 78.42 78.04 71.75 71.89 71.98 72.02 72.00 71.90 71.71 71.42 71.02 70.49 70.11 70.18 70.32 70.48 70.65 70.83 71.02 71.22 71.41 71.59 71.75 86.10 85.52 84.74 84.29 84.37 84.51 84.67 84.85 85.06 85.29 85.53 85.78 86.03 86.27 86.49 86.66 86.76 86.78 86.70 86.47 71.69 72.64 72.33 72.60 72.61 72.52 72.41 73.00 73.03 72.79 72.72 72.63 71.84 72.56 72.20 72.37 71.54 71.42 71.98 71.52 71.62 89.75 89.70 90.01 90.45 90.35 89.73 89.35 89.35 89.22 89.49 89.39 89.24 89.26 89.42 89.52 89.37 89.23 89.10 89.36 89.61 89.73 78.05 77.51 76.81 75.95 74.92 74.99 75.33 75.70 76.10 76.52 76.93 77.34 77.73 78.07 78.37 78.59 78.72 78.75 78.65 78.42 78.04 78.31 78.44 99.31 99.30 99.67 78.20 78.11 78.13 78.18 78.24 78.31 78.27 78.13 78.06 78.06 78.16 78.32 78.16 77.95 78.32 78.32 86.10 85.52 84.74 84.29 84.37 84.51 84.67 84.85 85.06 85.29 85.53 85.78 86.03 86.27 86.49 86.66 86.76 86.78 86.70 86.47 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.33 1.35 1.34 1.35 1.35 1.35 1.34 1.35 1.36 1.35 1.35 1.35 1.33 1.35 1.34 1.34 1.33 1.33 1.34 1.33 1.33 1.67 1.66 1.67 1.68 1.68 1.67 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.65 1.66 1.66 1.67 1.45 1.44 1.43 1.41 1.39 1.39 1.40 1.40 1.41 1.42 1.43 1.44 1.44 1.45 1.45 1.46 1.46 1.46 1.46 1.46 1.45 1.45 1.46 1.84 1.84 1.85 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.60 1.59 1.57 1.56 1.57 1.57 1.57 1.57 1.58 1.58 1.59 1.59 1.60 1.60 1.60 1.61 1.61 1.61 1.61 1.60 54.23 54.17 55.98 59.44 60.99 63.67 63.42 64.53 63.35 62.19 59.64 56.84 54.12 54.19 54.24 54.27 54.29 54.29 54.28 54.25 54.21 54.25 54.19 68.61 71.27 73.55 62.41 63.67 64.56 64.92 63.72 62.84 59.91 57.90 55.32 54.27 54.30 54.32 54.32 54.31 54.28 54.23 57.11 57.10 57.09 57.08 57.05 57.06 57.08 57.09 57.11 57.12 57.13 57.15 57.16 57.17 57.17 57.18 57.18 57.18 57.18 57.18 57.17 84.20 84.64 86.62 86.08 86.24 85.95 58.41 57.61 56.49 55.32 54.13 54.17 54.20 54.21 54.21 54.19 54.16 79.61 80.13 82.97 84.38 53.79 53.79 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 65.17 67.51 68.18 67.17 64.51 60.25 58.93 58.94 58.96 58.99 59.03 59.06 59.09 59.11 59.14 59.15 59.16 59.16 59.15 61.27 65.20 76.64 76.15 60.77 59.09 56.51 67.20 64.71 62.69 59.94 59.45 59.45 59.43 59.40 59.77 63.11 67.18 70.00 71.35 72.97 76.48 76.62 65.17 67.51 68.18 67.17 64.51 60.25 55.91 56.78 57.73 58.75 59.79 60.84 61.86 62.80 63.61 64.24 64.62 64.70 64.41 63.69 65.20 54.10 53.93 53.87 53.80 53.79 53.86 55.60 54.20 55.21 56.17 56.87 57.34 57.63 57.78 57.76 57.60 57.26 55.44 55.48 54.50 54.10 68.39 67.51 68.18 67.17 65.11 65.36 65.66 66.03 66.47 66.98 67.55 68.17 68.83 69.50 70.13 70.67 71.02 71.10 70.77 69.92 57.94 57.92 57.89 57.86 57.83 57.80 57.79 57.81 57.83 59.78 63.26 65.17 65.49 64.19 61.31 58.00 58.01 58.01 58.01 58.00 57.98 61.00 61.02 61.03 61.04 61.05 61.05 61.04 61.04 61.02 61.01 60.99 61.98 65.86 68.13 68.72 67.62 64.85 60.96 60.99 61.01 61.03 82.86 82.13 81.16 79.94 79.29 79.60 79.95 80.35 80.77 81.21 81.67 82.13 82.57 82.98 83.32 83.59 83.76 83.79 83.66 83.36 82.85 72.30 72.47 72.59 72.66 72.64 72.52 72.27 71.85 71.23 70.79 70.81 70.89 70.99 71.10 71.24 71.39 71.56 71.74 71.93 72.12 72.31 91.60 91.02 90.72 90.71 90.71 90.76 90.85 90.95 91.07 91.20 91.35 91.52 91.68 91.85 92.01 92.14 92.22 92.24 92.16 91.96 65.17 67.51 68.18 67.17 64.51 63.67 63.42 64.53 63.35 62.19 63.26 65.17 65.49 64.19 61.31 59.15 59.16 59.16 59.15 61.27 65.20 76.64 76.15 68.61 71.27 73.55 67.20 64.71 64.56 64.92 63.72 62.84 61.98 65.86 68.13 68.72 67.62 70.00 71.35 72.97 76.48 76.62 82.86 82.13 81.16 79.94 79.29 79.60 79.95 80.35 80.77 81.21 81.67 82.13 82.57 82.98 83.32 83.59 83.76 83.79 83.66 83.36 82.85 84.20 84.64 86.62 86.08 86.24 85.95 72.27 71.85 71.23 70.79 70.81 70.89 70.99 71.10 71.24 71.39 71.56 79.61 80.13 82.97 84.38 91.60 91.02 90.72 90.71 90.71 90.76 90.85 90.95 91.07 91.20 91.35 91.52 91.68 91.85 92.01 92.14 92.22 92.24 92.16 91.96 1.21 1.25 1.27 1.25 1.20 1.18 1.18 1.20 1.18 1.15 1.17 1.21 1.22 1.19 1.14 1.10 1.10 1.10 1.10 1.14 1.21 1.42 1.41 1.27 1.32 1.36 1.25 1.20 1.20 1.20 1.18 1.17 1.15 1.22 1.26 1.28 1.25 1.30 1.32 1.35 1.42 1.42 1.54 1.52 1.51 1.48 1.47 1.48 1.48 1.49 1.50 1.51 1.52 1.52 1.53 1.54 1.55 1.55 1.55 1.55 1.55 1.55 1.54 1.56 1.57 1.61 1.60 1.60 1.60 1.34 1.33 1.32 1.31 1.31 1.32 1.32 1.32 1.32 1.32 1.33 1.48 1.49 1.54 1.57 1.70 1.69 1.68 1.68 1.68 1.68 1.69 1.69 1.69 1.69 1.70 1.70 1.70 1.70 1.71 1.71 1.71 1.71 1.71 1.71 Simulation 1 Variables StartSimulation Delay (s) 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 Type of Fault ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 86.64 84.44 84.44 126.61 126.59 84.33 84.33 84.32 84.31 84.30 84.30 84.29 84.29 84.29 84.31 84.33 84.35 84.36 84.38 84.40 84.41 84.41 85.28 85.29 85.29 85.30 85.31 85.29 85.29 85.28 85.27 85.27 85.26 85.25 85.25 85.24 85.24 85.24 85.24 85.24 85.24 85.24 85.24 84.46 84.48 128.02 128.05 84.42 84.41 84.40 84.39 84.38 84.37 84.36 84.36 84.36 84.37 84.38 84.39 84.39 84.40 84.40 84.41 84.43 83.70 83.71 83.71 83.71 83.72 83.69 83.69 83.68 83.68 83.68 83.68 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 84.88 84.89 129.20 129.18 84.82 84.82 84.82 84.82 84.82 84.82 84.82 84.82 84.83 84.83 84.83 84.84 84.84 84.85 84.85 75.63 122.26 122.30 87.83 87.83 122.22 122.21 122.22 122.22 122.23 122.23 122.23 122.24 122.24 122.23 122.23 122.22 122.22 122.21 122.20 122.22 122.25 75.72 77.32 77.07 74.81 70.81 71.34 71.41 70.75 72.00 72.31 71.86 72.48 72.95 72.71 72.49 73.00 72.92 72.83 72.89 72.53 75.77 120.57 120.56 86.10 86.09 120.57 120.58 120.59 120.60 120.60 120.61 120.62 120.62 120.62 120.62 120.62 120.62 120.61 120.61 120.60 120.59 120.57 75.89 77.50 77.28 75.05 70.99 71.13 71.36 70.79 71.98 72.49 72.11 72.69 73.37 73.16 72.88 73.57 73.48 73.41 73.49 73.00 75.95 119.08 119.07 82.86 82.84 119.07 119.08 119.09 119.10 119.11 119.12 119.12 119.13 119.12 119.12 119.12 119.13 119.12 119.12 119.11 74.04 73.57 73.17 84.01 84.02 72.92 74.39 74.94 73.72 75.17 75.91 76.22 78.87 79.61 78.35 75.17 73.48 73.16 73.47 73.53 73.51 73.58 76.16 75.33 75.75 76.82 76.31 76.12 77.89 78.39 82.17 83.93 83.59 81.22 76.86 75.09 75.44 75.73 75.55 75.47 75.25 75.80 76.12 74.26 73.85 83.67 83.67 73.61 74.98 75.57 74.38 75.60 76.36 76.34 79.00 79.74 78.50 75.31 73.98 73.70 74.08 74.12 74.10 74.27 78.03 77.13 77.48 78.39 77.76 77.24 78.92 78.72 82.46 84.20 83.84 81.44 77.43 77.01 77.38 77.69 77.54 77.47 77.24 77.74 77.99 74.89 74.47 83.61 83.60 74.28 75.51 76.14 74.98 76.00 76.78 76.45 79.13 79.88 78.64 75.45 74.50 74.24 74.67 74.69 86.64 122.26 122.30 126.61 126.59 122.22 122.21 122.22 122.22 122.23 122.23 122.23 122.24 122.24 122.23 122.23 122.22 122.22 122.21 122.20 122.22 122.25 85.28 85.29 85.29 85.30 85.31 85.29 85.29 85.28 85.27 85.27 85.26 85.25 85.25 85.24 85.24 85.24 85.24 85.24 85.24 85.24 85.24 120.57 120.56 128.02 128.05 120.57 120.58 120.59 120.60 120.60 120.61 120.62 120.62 120.62 120.62 120.62 120.62 120.61 120.61 120.60 120.59 120.57 83.70 83.71 83.71 83.71 83.72 83.69 83.69 83.68 83.68 84.20 83.84 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 119.08 119.07 129.20 129.18 119.07 119.08 119.09 119.10 119.11 119.12 119.12 119.13 119.12 119.12 119.12 119.13 119.12 119.12 119.11 1.61 2.27 2.27 2.35 2.35 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 2.27 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 2.24 2.24 2.38 2.38 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.24 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.56 1.56 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 2.21 2.21 2.40 2.40 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 58.45 68.17 68.48 99.95 100.71 68.04 67.94 67.89 67.86 67.87 67.90 67.95 68.00 68.05 68.08 68.07 68.03 67.92 67.76 67.52 67.68 68.11 53.79 53.79 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 65.66 65.46 65.39 99.28 65.06 64.98 64.95 64.95 64.98 65.04 65.11 65.18 65.24 65.27 65.27 65.21 65.09 64.89 64.89 65.22 65.62 53.79 53.78 53.78 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 63.43 62.94 63.31 98.03 63.01 62.96 62.90 62.83 62.75 62.74 62.85 62.94 63.02 63.07 63.06 62.99 62.84 62.69 62.86 69.16 75.40 75.31 53.80 53.81 75.28 75.25 75.24 75.26 75.31 75.37 75.21 75.06 74.94 74.88 74.89 74.97 75.15 75.27 75.03 75.16 75.40 72.39 70.53 69.73 69.83 69.97 70.16 70.38 70.66 70.99 71.38 71.82 72.30 72.81 73.33 73.82 74.24 74.52 74.58 74.32 73.64 72.41 76.44 76.15 76.55 53.80 76.32 76.27 76.26 76.28 76.33 76.23 76.08 75.94 75.85 75.79 75.80 75.87 76.02 76.26 76.01 76.03 76.45 75.28 74.41 74.41 74.44 74.50 74.58 74.68 74.82 75.00 75.21 75.47 75.76 76.10 76.46 76.82 77.14 77.36 77.41 77.18 76.53 75.30 77.78 78.22 78.00 53.80 78.20 78.09 77.96 77.82 77.67 77.52 77.44 77.53 77.60 77.64 77.63 77.57 77.44 77.54 77.81 86.09 75.22 75.30 75.36 75.39 75.37 75.28 75.09 74.79 74.51 74.53 74.54 74.56 74.61 74.66 74.72 74.79 74.86 74.95 75.04 75.13 75.22 90.36 89.88 89.73 89.73 89.74 89.78 89.83 89.91 89.99 90.09 90.20 90.32 90.45 90.58 90.70 90.80 90.87 90.88 90.82 90.65 90.35 77.18 77.21 77.24 77.25 77.23 77.16 77.03 76.97 76.98 77.00 77.01 77.02 77.02 77.02 77.02 77.04 77.06 77.09 77.11 77.15 77.18 92.69 92.59 92.59 92.60 92.60 92.60 92.60 92.60 92.62 92.66 92.71 92.76 92.82 92.88 92.95 93.00 93.04 93.05 93.01 92.90 92.68 78.32 78.33 78.33 78.33 78.32 78.27 78.27 78.28 78.30 78.31 78.33 78.33 78.34 78.34 78.34 78.34 78.33 78.32 78.31 86.09 75.40 75.31 99.95 100.71 75.37 75.28 75.24 75.26 75.31 75.37 75.21 75.06 74.94 74.88 74.89 74.97 75.15 75.27 75.04 75.16 75.40 90.36 89.88 89.73 89.73 89.74 89.78 89.83 89.91 89.99 90.09 90.20 90.32 90.45 90.58 90.70 90.80 90.87 90.88 90.82 90.65 90.35 77.18 77.21 77.24 99.28 77.23 77.16 77.03 76.97 76.98 77.00 77.01 77.02 77.02 77.02 77.02 77.04 77.06 77.09 77.11 77.15 77.18 92.69 92.59 92.59 92.60 92.60 92.60 92.60 92.60 92.62 92.66 92.71 92.76 92.82 92.88 92.95 93.00 93.04 93.05 93.01 92.90 92.68 78.32 78.33 78.33 98.03 78.32 78.27 78.27 78.28 78.30 78.31 78.33 78.33 78.34 78.34 78.34 78.34 78.33 78.32 78.31 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.60 1.40 1.40 1.85 1.87 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.39 1.39 1.39 1.39 1.39 1.39 1.40 1.39 1.39 1.40 1.68 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.68 1.68 1.68 1.68 1.68 1.69 1.69 1.69 1.68 1.68 1.43 1.43 1.43 1.84 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.43 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.73 1.73 1.73 1.73 1.72 1.72 1.45 1.45 1.45 1.82 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 53.81 82.57 83.98 82.93 85.57 84.43 56.31 54.01 53.96 54.03 54.09 54.14 54.18 54.20 54.21 54.21 54.20 54.17 54.13 54.08 54.01 82.56 53.78 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.97 53.89 81.51 82.28 56.20 53.80 53.88 53.96 54.03 54.09 54.14 54.18 54.21 54.22 54.22 54.20 54.17 54.13 54.08 54.02 53.95 53.80 53.80 53.80 53.80 53.80 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.78 53.97 53.89 83.90 81.47 55.68 53.80 53.89 53.97 54.04 54.10 54.15 54.18 54.21 54.22 54.22 54.20 54.18 54.14 54.09 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 68.41 53.96 53.90 53.84 53.78 53.81 59.17 56.52 57.17 57.91 58.52 58.88 59.00 59.11 59.23 59.19 59.18 59.00 58.79 58.33 57.77 53.96 73.59 73.12 73.12 73.12 73.17 73.24 73.34 73.47 73.63 73.83 74.07 74.36 74.69 75.06 75.43 75.77 76.02 76.07 75.80 75.05 73.61 57.98 60.39 53.83 53.77 62.04 61.25 60.00 58.03 58.49 58.93 59.03 59.10 59.13 59.07 59.02 59.05 59.12 58.91 58.97 58.33 57.95 78.25 78.25 78.25 78.25 78.25 78.25 78.27 78.31 78.37 78.44 78.54 78.67 78.83 79.01 79.21 79.42 79.57 79.61 79.41 78.79 78.26 60.45 62.33 53.82 53.77 64.74 63.88 62.89 59.55 58.52 58.99 58.74 58.94 58.75 58.61 58.54 58.55 58.94 58.96 58.61 91.58 76.79 76.83 76.88 76.90 76.89 76.83 76.68 76.58 76.59 76.59 76.59 76.59 76.60 76.60 76.60 76.61 76.63 76.66 76.70 76.74 76.79 94.85 94.82 94.82 94.82 94.82 94.82 94.82 94.82 94.82 94.85 94.89 94.94 94.99 95.05 95.11 95.16 95.20 95.20 95.16 95.05 94.83 78.58 78.58 78.58 78.59 78.59 78.58 78.57 78.57 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.57 96.20 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.21 96.23 96.24 96.25 96.23 96.19 96.19 79.42 79.42 79.42 79.41 79.42 79.41 79.41 79.41 79.41 79.42 79.42 79.42 79.42 79.42 79.42 79.42 79.42 79.42 79.42 91.58 82.57 83.98 82.93 85.57 84.43 76.83 76.68 76.58 76.59 76.59 76.59 76.59 76.60 76.60 76.60 76.61 76.63 76.66 76.70 76.74 82.56 94.85 94.82 94.82 94.82 94.82 94.82 94.82 94.82 94.82 94.85 94.89 94.94 94.99 95.05 95.11 95.16 95.20 95.20 95.16 95.05 94.83 78.58 78.58 81.51 82.28 78.59 78.58 78.57 78.57 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.57 96.20 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.21 96.23 96.24 96.25 96.23 96.19 96.19 79.42 79.42 83.90 81.47 79.42 79.41 79.41 79.41 79.41 79.42 79.42 79.42 79.42 79.42 79.42 79.42 79.42 79.42 79.42 1.70 1.53 1.56 1.54 1.59 1.57 1.43 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.53 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.77 1.77 1.77 1.77 1.76 1.76 1.46 1.46 1.51 1.53 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.78 1.78 1.78 1.78 1.78 1.78 1.79 1.79 1.79 1.79 1.79 1.78 1.78 1.47 1.47 1.56 1.51 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 Simulation 1 Variables StartSimulation Delay (s) 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 Type of Fault ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 84.86 84.86 81.94 81.94 81.94 81.94 81.91 81.91 81.91 81.91 81.91 81.91 81.91 81.91 81.92 81.92 81.92 81.92 81.92 81.92 81.92 81.92 81.92 85.55 85.56 130.27 130.30 85.51 85.50 85.50 85.50 85.49 85.49 85.49 85.49 85.49 85.49 85.49 85.50 85.50 85.50 85.51 85.52 85.52 80.07 80.07 80.07 80.07 80.05 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 80.04 86.45 86.46 131.01 130.99 86.42 86.42 86.41 86.39 86.37 86.36 86.35 86.34 86.33 86.33 86.33 86.33 86.34 86.36 86.37 86.39 86.42 78.08 78.08 78.08 78.08 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 78.07 119.09 119.08 76.08 77.68 77.49 75.28 71.24 71.13 71.50 70.99 72.08 72.77 72.43 72.93 73.81 73.63 73.27 74.12 74.04 73.98 74.07 73.45 76.13 117.74 117.72 79.25 79.23 117.73 117.74 117.75 117.76 117.77 117.77 117.78 117.79 117.79 117.79 117.79 117.79 117.78 117.78 117.77 117.75 117.74 76.26 77.90 77.69 75.51 71.49 71.28 71.77 71.31 72.27 73.11 72.82 73.22 74.26 74.13 73.66 74.66 74.60 74.56 74.64 73.89 76.32 116.67 116.70 76.13 76.12 116.69 116.67 116.66 116.64 116.63 116.61 116.61 116.61 116.62 116.62 116.62 116.62 116.61 116.61 116.62 116.64 116.66 76.44 78.13 77.94 75.73 71.73 71.57 72.15 71.73 72.54 73.50 73.26 73.53 74.71 74.63 74.13 75.18 75.15 75.12 74.66 74.91 79.71 78.74 79.09 79.83 79.09 78.31 79.90 79.60 82.73 84.46 84.09 81.66 79.12 78.74 79.13 79.44 79.31 79.25 79.03 79.48 79.67 75.48 75.05 81.57 81.59 74.88 76.00 76.66 75.52 76.38 77.18 76.57 79.25 80.01 78.78 75.59 75.02 74.78 75.25 75.24 75.19 75.49 81.22 80.18 80.57 81.16 80.32 79.34 80.84 80.44 83.00 84.72 84.33 81.88 80.64 80.30 80.70 81.01 80.88 80.83 80.63 81.04 81.17 76.01 75.57 81.09 81.11 75.41 76.44 77.13 76.00 76.75 77.56 76.68 79.37 80.14 78.91 75.79 75.52 75.29 75.79 75.75 75.67 76.03 82.57 81.46 81.93 82.38 81.43 80.52 81.73 81.24 83.27 84.98 84.56 82.09 82.03 81.70 82.12 82.42 82.29 82.25 119.09 119.08 81.94 81.94 81.94 81.94 81.91 81.91 81.91 81.91 82.73 84.46 84.09 81.91 81.92 81.92 81.92 81.92 81.92 81.92 81.92 81.92 81.92 117.74 117.72 130.27 130.30 117.73 117.74 117.75 117.76 117.77 117.77 117.78 117.79 117.79 117.79 117.79 117.79 117.78 117.78 117.77 117.75 117.74 81.22 80.18 80.57 81.16 80.32 80.04 80.84 80.44 83.00 84.72 84.33 81.88 80.64 80.30 80.70 81.01 80.88 80.83 80.63 81.04 81.17 116.67 116.70 131.01 130.99 116.69 116.67 116.66 116.64 116.63 116.61 116.61 116.61 116.62 116.62 116.62 116.62 116.61 116.61 116.62 116.64 116.66 82.57 81.46 81.93 82.38 81.43 80.52 81.73 81.24 83.27 84.98 84.56 82.09 82.03 81.70 82.12 82.42 82.29 82.25 2.21 2.21 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.54 1.57 1.56 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 2.18 2.18 2.42 2.42 2.18 2.18 2.18 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.18 1.51 1.49 1.50 1.51 1.49 1.49 1.50 1.49 1.54 1.57 1.56 1.52 1.50 1.49 1.50 1.50 1.50 1.50 1.50 1.50 1.51 2.17 2.17 2.43 2.43 2.17 2.17 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 1.53 1.51 1.52 1.53 1.51 1.49 1.52 1.51 1.55 1.58 1.57 1.52 1.52 1.52 1.52 1.53 1.53 1.53 63.11 63.40 53.78 53.78 53.78 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.80 64.20 64.83 65.10 96.72 64.76 64.68 64.56 64.41 64.24 64.07 63.90 63.75 63.70 63.64 63.65 63.68 63.86 64.15 64.56 64.60 64.19 53.78 53.78 53.78 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 62.36 62.25 62.36 96.07 62.42 62.37 62.34 62.31 62.29 62.32 62.31 62.32 62.32 62.32 62.32 62.31 62.30 62.24 62.21 62.35 62.36 53.78 53.78 53.78 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 77.91 77.77 77.89 77.89 77.89 77.88 77.89 77.92 77.97 78.03 78.12 78.23 78.38 78.55 78.76 79.00 79.25 79.48 79.66 79.70 79.49 78.90 77.88 79.53 79.59 79.72 53.80 79.91 79.81 79.69 79.56 79.43 79.30 79.18 79.08 79.00 78.96 78.97 79.02 79.13 79.30 79.53 79.23 79.52 80.44 80.44 80.44 80.44 80.44 80.43 80.43 80.46 80.51 80.57 80.65 80.75 80.87 81.03 81.19 81.36 81.49 81.52 81.35 80.83 80.43 80.89 81.07 81.08 53.80 81.24 81.14 81.03 80.92 80.80 80.68 80.58 80.49 80.43 80.40 80.40 80.45 80.54 80.68 80.87 80.67 80.89 82.35 82.35 82.35 82.34 82.34 82.34 82.34 82.34 82.34 82.37 82.41 82.47 82.55 82.64 82.75 82.87 82.97 82.99 78.31 78.32 94.08 94.08 94.08 94.08 94.08 94.08 94.08 94.09 94.09 94.09 94.09 94.09 94.11 94.14 94.17 94.20 94.22 94.23 94.20 94.13 94.09 79.04 79.02 79.01 79.00 78.99 79.00 79.02 79.03 79.05 79.06 79.08 79.08 79.09 79.09 79.09 79.09 79.08 79.07 79.06 79.04 79.02 94.85 94.85 94.85 94.85 94.85 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 79.50 79.48 79.47 79.45 79.45 79.46 79.48 79.49 79.51 79.52 79.54 79.54 79.55 79.55 79.55 79.55 79.54 79.53 79.52 79.50 79.49 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.26 95.26 95.26 95.26 95.26 95.26 78.31 78.32 94.08 94.08 94.08 94.08 94.08 94.08 94.08 94.09 94.09 94.09 94.09 94.09 94.11 94.14 94.17 94.20 94.22 94.23 94.20 94.13 94.09 79.53 79.59 79.72 96.72 79.91 79.81 79.69 79.56 79.43 79.30 79.18 79.08 79.09 79.09 79.09 79.09 79.13 79.30 79.53 79.23 79.52 94.85 94.85 94.85 94.85 94.85 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 80.89 81.07 81.08 96.07 81.24 81.14 81.03 80.92 80.80 80.68 80.58 80.49 80.43 80.40 80.40 80.45 80.54 80.68 80.87 80.67 80.89 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.25 95.26 95.26 95.26 95.26 95.26 95.26 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.45 1.45 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.48 1.48 1.48 1.79 1.48 1.48 1.48 1.48 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.48 1.47 1.48 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.50 1.50 1.50 1.78 1.51 1.51 1.50 1.50 1.50 1.50 1.50 1.49 1.49 1.49 1.49 1.49 1.49 1.50 1.50 1.50 1.50 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 54.02 53.95 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.77 53.77 53.97 53.89 53.81 82.87 55.07 53.81 53.89 53.97 54.04 54.10 54.15 54.19 54.21 54.22 54.22 54.21 54.18 54.14 54.09 54.03 53.96 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.77 53.77 53.98 53.90 53.81 84.30 54.27 53.81 53.89 53.97 54.04 54.10 54.15 54.19 54.21 54.22 54.22 54.21 54.18 54.14 54.09 54.03 53.96 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 58.79 60.54 81.50 81.50 81.50 81.50 81.50 81.50 81.50 81.50 81.50 81.52 81.56 81.62 81.69 81.78 81.89 82.01 82.10 82.13 81.98 81.51 81.51 62.04 65.21 65.68 53.77 66.76 65.50 64.24 61.72 59.85 58.52 58.59 58.63 58.45 58.30 58.22 58.22 58.60 58.34 58.60 59.81 62.02 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.67 83.68 83.71 83.76 83.82 83.88 83.94 83.96 83.85 83.68 83.68 63.76 65.85 67.19 53.77 68.62 67.62 65.34 63.16 60.40 57.95 58.59 58.19 57.58 57.53 57.95 57.77 58.28 58.30 58.33 61.36 63.86 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.20 85.21 85.24 85.27 85.31 85.32 79.41 79.41 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 79.84 79.84 79.84 79.83 79.84 79.84 79.83 79.83 79.83 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.83 79.83 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 80.08 80.08 80.08 80.07 80.08 80.08 80.07 80.07 80.07 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.07 80.07 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 79.41 79.41 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 96.58 79.84 79.84 79.84 82.87 79.84 79.84 79.83 79.83 79.83 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.84 79.83 79.83 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 96.61 80.08 80.08 80.08 84.30 80.08 80.08 80.07 80.07 80.07 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.08 80.07 80.07 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 1.47 1.47 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.48 1.48 1.48 1.54 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.49 1.49 1.49 1.56 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 Simulation 1 Variables StartSimulation Delay (s) 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 Type of Fault ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 78.07 78.07 78.07 87.16 87.16 131.67 131.69 87.13 87.13 87.13 87.12 87.12 87.12 87.11 87.11 87.11 87.11 87.11 87.11 87.12 87.12 87.13 87.13 87.14 76.03 76.03 76.03 76.03 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 76.01 87.31 87.32 132.03 132.03 87.29 87.28 87.28 87.27 87.26 87.26 87.25 87.25 87.24 87.24 87.24 87.25 87.25 87.25 87.26 87.27 87.28 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 73.96 86.37 86.36 132.46 86.32 86.33 86.34 86.34 86.34 86.33 86.33 86.33 86.33 86.33 86.33 86.33 86.33 86.33 75.19 74.31 76.49 115.82 115.80 73.65 73.65 115.80 115.81 115.83 115.84 115.84 115.82 115.81 115.80 115.80 115.79 115.80 115.80 115.81 115.82 115.83 115.83 115.82 76.61 78.34 78.19 76.01 71.97 71.95 72.60 72.22 72.88 73.94 73.74 73.87 75.18 75.14 74.69 75.68 75.68 75.67 75.73 74.84 76.67 115.05 115.07 71.71 71.71 115.06 115.04 115.03 115.02 115.03 115.04 115.04 115.05 115.06 115.06 115.06 115.05 115.05 115.04 115.03 115.01 115.03 76.79 78.56 78.44 76.29 72.28 72.42 73.11 72.77 73.27 74.41 74.28 74.23 75.64 75.64 75.24 76.17 76.22 76.21 76.26 75.41 76.84 114.60 114.59 70.08 114.58 114.59 114.60 114.59 114.57 114.56 114.55 114.54 114.53 114.53 114.52 114.52 114.53 114.53 82.06 82.45 82.53 76.50 76.06 80.75 80.76 75.89 76.85 77.56 76.45 77.09 77.92 76.84 79.49 80.27 79.04 76.29 76.00 75.79 76.30 76.22 76.13 76.52 83.78 82.62 83.17 83.50 82.45 81.87 82.60 82.00 83.56 85.22 84.79 82.99 83.28 82.98 83.40 83.68 83.56 83.52 83.34 83.72 83.74 76.95 76.51 80.49 80.50 76.31 77.23 77.95 76.85 77.41 78.25 77.17 79.61 80.39 79.17 76.76 76.46 76.25 76.78 76.66 76.55 76.97 84.87 83.66 84.30 84.53 83.39 83.13 83.42 83.07 83.90 85.50 85.02 84.15 84.41 84.13 84.54 84.80 84.68 84.66 84.50 84.85 84.82 77.36 76.92 80.32 77.84 76.70 77.57 78.30 77.21 77.72 78.56 77.48 79.72 80.51 79.30 77.21 76.88 76.69 82.06 82.45 82.53 115.82 115.80 131.67 131.69 115.80 115.81 115.83 115.84 115.84 115.82 115.81 115.80 115.80 115.79 115.80 115.80 115.81 115.82 115.83 115.83 115.82 83.78 82.62 83.17 83.50 82.45 81.87 82.60 82.00 83.56 85.22 84.79 82.99 83.28 82.98 83.40 83.68 83.56 83.52 83.34 83.72 83.74 115.05 115.07 132.03 132.03 115.06 115.04 115.03 115.02 115.03 115.04 115.04 115.05 115.06 115.06 115.06 115.05 115.05 115.04 115.03 115.01 115.03 84.87 83.66 84.30 84.53 83.39 83.13 83.42 83.07 83.90 85.50 85.02 84.15 84.41 84.13 84.54 84.80 84.68 84.66 84.50 84.85 84.82 114.60 114.59 132.46 114.58 114.59 114.60 114.59 114.57 114.56 114.55 114.54 114.53 114.53 114.52 114.52 114.53 114.53 1.52 1.53 1.53 2.15 2.15 2.44 2.44 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 1.55 1.53 1.54 1.55 1.53 1.52 1.53 1.52 1.55 1.58 1.57 1.54 1.55 1.54 1.55 1.55 1.55 1.55 1.55 1.55 1.55 2.13 2.14 2.45 2.45 2.14 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.14 2.14 2.14 2.14 2.13 2.13 2.13 2.13 2.13 1.57 1.55 1.56 1.57 1.55 1.54 1.55 1.54 1.56 1.59 1.58 1.56 1.57 1.56 1.57 1.57 1.57 1.57 1.57 1.57 1.57 2.13 2.13 2.46 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 53.79 53.79 53.79 58.21 58.19 58.52 95.47 58.18 58.12 58.07 58.01 57.99 57.98 57.97 57.97 57.97 57.97 57.97 57.96 57.96 57.94 57.97 58.24 58.28 53.78 53.78 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 58.60 59.12 58.92 95.22 58.73 58.68 58.66 58.66 58.56 58.38 58.21 58.07 57.95 57.89 57.90 57.99 58.18 58.46 58.42 58.28 58.59 53.78 53.78 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 60.71 61.10 61.11 95.15 60.67 60.60 60.55 60.50 60.46 60.42 60.18 59.92 59.72 59.61 59.63 59.79 60.12 82.85 82.40 82.34 82.21 82.10 82.39 53.80 82.23 82.18 82.17 82.21 82.11 82.01 81.92 81.85 81.79 81.77 81.77 81.81 81.88 81.99 81.85 81.97 82.20 83.80 83.80 83.80 83.80 83.80 83.80 83.80 83.80 83.80 83.79 83.80 83.83 83.88 83.94 84.01 84.09 84.16 84.18 84.06 83.80 83.80 83.20 83.17 83.38 53.80 83.47 83.38 83.28 83.19 83.09 83.01 82.93 82.87 82.83 82.81 82.81 82.84 82.90 82.98 83.09 83.02 83.20 84.94 84.94 84.94 84.94 84.94 84.94 84.94 84.94 84.93 84.93 84.93 84.93 84.95 84.98 85.03 85.09 85.14 85.15 85.06 84.94 84.94 82.92 82.64 82.27 53.80 83.11 83.06 83.07 83.12 83.21 83.33 83.18 82.98 82.83 82.75 82.76 82.88 83.13 95.26 95.26 95.26 79.80 79.78 79.77 79.75 79.75 79.76 79.78 79.79 79.81 79.82 79.84 79.84 79.85 79.85 79.85 79.85 79.84 79.83 79.82 79.80 79.79 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 80.01 79.99 79.98 79.96 79.96 79.97 79.98 80.00 80.02 80.03 80.04 80.05 80.06 80.06 80.06 80.06 80.05 80.04 80.02 80.01 79.99 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 80.16 80.14 80.13 80.11 80.10 80.12 80.13 80.15 80.16 80.18 80.19 80.20 80.21 80.21 80.21 80.20 80.20 95.26 95.26 95.26 82.21 82.10 82.39 95.47 82.23 82.18 82.17 82.21 82.11 82.01 81.92 81.85 81.79 81.77 81.77 81.81 81.88 81.99 81.85 81.97 82.20 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 95.44 83.20 83.17 83.38 95.22 83.47 83.38 83.28 83.19 83.09 83.01 82.93 82.87 82.83 82.81 82.81 82.84 82.90 82.98 83.09 83.02 83.20 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.51 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 82.92 82.64 82.27 95.15 83.11 83.06 83.07 83.12 83.21 83.33 83.18 82.98 82.83 82.75 82.76 82.88 83.13 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.77 1.77 1.77 1.53 1.52 1.53 1.77 1.53 1.52 1.52 1.53 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.53 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.54 1.54 1.55 1.77 1.55 1.55 1.55 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.54 1.53 1.53 1.77 1.54 1.54 1.54 1.54 1.54 1.55 1.54 1.54 1.54 1.54 1.54 1.54 1.54 53.78 53.77 53.77 53.98 53.90 53.81 85.45 53.78 53.81 53.90 53.97 54.04 54.10 54.15 54.19 54.21 54.22 54.22 54.21 54.18 54.14 54.09 54.03 53.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.77 53.77 53.98 53.90 53.81 86.38 53.78 53.81 53.90 53.97 54.04 54.10 54.15 54.19 54.21 54.23 54.22 54.21 54.18 54.14 54.09 54.03 53.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.77 53.77 53.98 53.90 53.82 87.15 54.97 53.81 53.90 53.98 54.04 54.10 54.15 54.19 54.21 54.23 54.22 54.21 54.18 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 85.24 85.21 85.21 65.04 67.19 68.46 53.77 69.27 68.90 66.52 64.66 62.16 59.28 57.41 58.19 57.67 57.51 57.42 57.87 58.03 57.66 60.31 62.99 65.03 86.32 86.32 86.32 86.32 86.32 86.32 86.32 86.33 86.33 86.33 86.33 86.33 86.33 86.33 86.33 86.33 86.36 86.36 86.33 86.33 86.33 66.00 68.10 69.84 53.77 69.01 69.25 67.55 65.56 63.27 60.05 57.34 57.12 57.25 57.46 57.25 57.43 57.46 58.31 60.62 63.81 65.98 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.18 87.19 87.19 87.19 87.19 87.19 87.19 87.19 87.19 67.57 69.59 70.54 53.77 66.61 70.23 69.04 66.39 63.89 60.96 58.23 57.31 56.98 56.87 56.83 57.11 57.18 96.50 96.50 96.50 80.23 80.23 80.23 80.22 80.23 80.22 80.22 80.22 80.22 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.22 80.22 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.33 96.33 96.33 96.33 96.34 96.34 80.33 80.33 80.33 80.32 80.33 80.32 80.32 80.32 80.32 80.32 80.33 80.33 80.33 80.33 80.33 80.33 80.33 80.33 80.32 80.32 80.32 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 80.40 80.40 80.39 80.39 80.40 80.39 80.39 80.39 80.39 80.39 80.40 80.40 80.40 80.40 80.40 80.40 80.40 96.50 96.50 96.50 80.23 80.23 80.23 85.45 80.23 80.22 80.22 80.22 80.22 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.23 80.22 80.22 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.34 96.33 96.33 96.33 96.33 96.34 96.34 80.33 80.33 80.33 86.38 80.33 80.32 80.32 80.32 80.32 80.32 80.33 80.33 80.33 80.33 80.33 80.33 80.33 80.33 80.32 80.32 80.32 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 96.16 80.40 80.40 80.39 87.15 80.40 80.39 80.39 80.39 80.39 80.39 80.40 80.40 80.40 80.40 80.40 80.40 80.40 1.79 1.79 1.79 1.49 1.49 1.49 1.59 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.49 1.49 1.49 1.60 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.49 1.49 1.49 1.62 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 Simulation 1 Variables StartSimulation Delay (s) 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 45 45 45 45 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 86.33 86.33 86.34 86.34 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 71.90 84.09 84.09 132.60 84.05 84.06 84.06 84.06 84.06 84.06 84.06 84.07 84.07 84.07 84.08 84.08 84.07 84.07 84.06 84.06 84.06 84.05 59.14 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 59.11 64.85 64.86 131.72 64.87 64.86 64.86 64.85 64.84 64.83 64.82 64.81 64.80 64.79 64.78 64.79 64.79 64.80 64.81 64.83 64.84 64.85 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 55.49 114.54 114.56 114.57 114.59 76.99 78.76 78.69 76.57 72.58 72.95 73.67 73.35 73.70 74.90 74.82 74.60 76.11 76.17 75.78 76.65 76.73 76.73 76.78 75.97 77.05 114.11 114.10 68.52 114.11 114.10 114.10 114.11 114.13 114.14 114.15 114.16 114.16 114.17 114.17 114.17 114.17 114.16 114.15 114.14 114.13 114.11 80.64 81.30 81.35 79.41 78.75 78.85 79.40 79.15 78.90 79.89 79.97 79.26 80.44 80.85 80.40 80.67 81.12 81.09 81.17 80.57 80.64 103.56 103.52 58.28 103.48 103.50 103.53 103.55 103.57 103.59 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.57 103.54 97.95 100.67 100.91 99.30 96.25 91.59 91.79 91.57 91.63 91.84 91.57 91.62 91.84 91.80 91.57 91.57 77.22 77.07 76.95 77.38 85.84 84.59 85.34 85.48 84.24 84.28 84.33 84.21 84.71 85.83 85.27 85.20 85.44 85.17 85.58 85.81 85.70 85.68 85.53 85.88 85.80 77.74 77.30 80.20 78.18 77.04 77.89 78.63 77.54 78.00 78.86 77.79 79.83 80.63 79.42 77.62 77.27 77.10 77.63 77.45 77.31 77.76 91.60 91.39 91.84 91.39 91.39 91.46 91.39 91.39 91.53 91.53 91.39 91.61 91.68 91.50 91.73 91.81 91.73 91.74 91.71 91.92 91.55 80.16 79.74 79.86 80.28 79.52 79.94 80.66 79.70 80.15 81.03 79.94 81.16 82.03 80.86 80.26 79.77 79.84 80.24 79.88 79.75 80.18 95.70 96.03 96.69 96.57 96.93 104.76 110.09 112.70 112.55 111.00 107.48 101.59 95.70 95.70 95.77 95.70 114.54 114.56 114.57 114.59 85.84 84.59 85.34 85.48 84.24 84.28 84.33 84.21 84.71 85.83 85.27 85.20 85.44 85.17 85.58 85.81 85.70 85.68 85.53 85.88 85.80 114.11 114.10 132.60 114.11 114.10 114.10 114.11 114.13 114.14 114.15 114.16 114.16 114.17 114.17 114.17 114.17 114.16 114.15 114.14 114.13 114.11 91.60 91.39 91.84 91.39 91.39 91.46 91.39 91.39 91.53 91.53 91.39 91.61 91.68 91.50 91.73 91.81 91.73 91.74 91.71 91.92 91.55 103.56 103.52 131.72 103.48 103.50 103.53 103.55 103.57 103.59 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.58 103.57 103.54 97.95 100.67 100.91 99.30 96.93 104.76 110.09 112.70 112.55 111.00 107.48 101.59 95.70 95.70 95.77 95.70 2.13 2.13 2.13 2.13 1.59 1.57 1.58 1.59 1.56 1.56 1.56 1.56 1.57 1.59 1.58 1.58 1.59 1.58 1.59 1.59 1.59 1.59 1.59 1.59 1.59 2.12 2.12 2.46 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.71 1.70 1.92 1.92 2.44 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.82 1.87 1.87 1.84 1.80 1.94 2.04 2.09 2.09 2.06 1.99 1.89 1.78 1.78 1.78 1.78 60.37 60.37 60.38 60.68 53.78 53.78 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 62.65 62.61 63.43 94.97 62.23 62.17 62.11 62.06 62.02 61.98 61.95 61.93 61.92 61.92 61.92 61.92 61.92 61.94 61.93 62.44 62.71 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.80 53.80 53.80 67.25 67.38 67.56 67.08 67.03 66.94 66.81 66.84 66.99 66.95 66.86 66.79 66.73 66.71 66.71 66.75 66.83 66.95 66.79 67.39 67.26 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 53.84 83.15 82.72 82.15 82.84 85.85 85.85 85.85 85.85 85.85 85.85 85.84 85.84 85.84 85.84 85.84 85.84 85.84 85.84 85.87 85.91 85.95 85.96 85.88 85.85 85.85 79.72 79.77 79.13 53.80 80.76 80.72 80.74 80.56 80.36 80.15 79.94 79.76 79.62 79.55 79.56 79.67 79.89 80.24 80.45 79.94 79.64 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 89.79 66.23 66.33 66.08 66.70 66.63 66.56 66.51 66.47 66.46 66.36 66.24 66.13 66.05 66.01 66.01 66.07 66.20 66.39 66.34 66.51 66.20 92.62 94.17 98.34 100.09 99.37 96.25 92.62 92.62 92.62 92.62 92.62 92.62 92.62 92.62 92.62 92.62 80.19 80.17 80.16 80.14 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.53 95.53 95.53 95.53 95.53 95.53 95.53 95.53 95.53 80.27 80.25 80.24 80.22 80.21 80.23 80.24 80.26 80.27 80.29 80.30 80.31 80.31 80.32 80.32 80.31 80.31 80.30 80.28 80.27 80.25 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 80.65 80.64 80.62 80.61 80.60 80.61 80.63 80.64 80.66 80.67 80.68 80.69 80.70 80.70 80.70 80.70 80.69 80.68 80.67 80.65 80.64 93.59 93.59 93.59 93.59 93.59 93.59 93.59 94.46 99.04 101.18 100.83 97.99 93.59 93.59 93.59 93.59 83.15 82.72 82.15 82.84 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.52 95.53 95.53 95.53 95.53 95.53 95.53 95.53 95.53 95.53 80.27 80.25 80.24 94.97 80.76 80.72 80.74 80.56 80.36 80.29 80.30 80.31 80.31 80.32 80.32 80.31 80.31 80.30 80.45 80.27 80.25 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 94.93 80.65 80.64 80.62 80.61 80.60 80.61 80.63 80.64 80.66 80.67 80.68 80.69 80.70 80.70 80.70 80.70 80.69 80.68 80.67 80.65 80.64 93.59 94.17 98.34 100.09 99.37 96.25 93.59 94.46 99.04 101.18 100.83 97.99 93.59 93.59 93.59 93.59 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.54 1.53 1.52 1.54 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.49 1.49 1.49 1.76 1.50 1.50 1.50 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.74 1.75 1.82 1.86 1.84 1.79 1.74 1.75 1.84 1.88 1.87 1.82 1.74 1.74 1.74 1.74 54.14 54.09 54.03 53.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.77 53.77 53.77 53.98 53.90 53.82 87.78 55.54 53.82 53.90 53.98 54.05 54.10 54.15 54.19 54.21 54.23 54.23 54.21 54.18 54.14 54.09 54.03 53.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.98 53.91 55.33 63.54 59.52 54.91 53.90 53.98 54.05 54.11 54.16 54.19 54.22 54.23 54.23 54.21 54.19 54.15 54.10 54.04 53.97 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 53.80 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 59.17 62.23 64.87 67.55 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.86 87.87 87.87 87.87 67.98 69.91 71.12 53.77 63.98 71.00 69.43 67.56 64.66 62.21 59.14 57.66 56.84 56.54 56.78 56.74 57.88 59.73 62.64 65.45 67.97 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.70 90.71 90.71 90.71 68.55 64.16 59.72 59.66 58.84 61.39 65.78 70.27 70.51 67.80 64.76 62.20 60.71 59.80 59.58 61.00 63.19 65.62 68.61 71.10 68.60 92.74 92.74 94.12 95.78 95.13 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 80.40 80.39 80.39 80.39 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 80.45 80.45 80.44 80.44 80.45 80.44 80.44 80.44 80.44 80.44 80.45 80.45 80.45 80.45 80.45 80.45 80.45 80.45 80.44 80.44 80.44 94.87 94.87 94.87 94.87 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 80.62 80.62 80.61 80.62 80.61 80.61 80.61 80.61 80.61 80.61 80.61 80.62 80.62 80.62 80.62 80.62 80.62 80.61 80.61 80.61 80.61 93.51 93.51 93.51 93.51 93.51 93.51 93.51 93.51 93.51 95.93 96.34 94.37 93.51 93.51 93.51 93.51 80.40 80.39 80.39 80.39 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 95.99 80.45 80.45 80.44 87.78 80.45 80.44 80.44 80.44 80.44 80.44 80.45 80.45 80.45 80.45 80.45 80.45 80.45 80.45 80.44 80.44 80.44 94.87 94.87 94.87 94.87 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 94.86 80.62 80.62 80.61 80.62 80.61 80.61 80.61 80.61 80.61 80.61 80.61 80.62 80.62 80.62 80.62 80.62 80.62 80.61 80.61 80.61 80.61 93.51 93.51 94.12 95.78 95.13 93.51 93.51 93.51 93.51 95.93 96.34 94.37 93.51 93.51 93.51 93.51 1.49 1.49 1.49 1.49 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.49 1.49 1.49 1.63 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.74 1.74 1.75 1.78 1.77 1.74 1.74 1.74 1.74 1.78 1.79 1.75 1.74 1.74 1.74 1.74 Simulation 1 Variables StartSimulation Delay (s) 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 55.49 55.52 55.52 55.52 55.52 86.84 86.85 86.87 86.88 86.87 86.85 86.84 86.83 86.82 86.81 86.80 86.80 86.79 86.79 86.79 86.79 86.80 86.81 86.82 86.83 86.85 55.47 55.47 55.47 55.47 55.47 55.47 55.47 55.47 55.46 55.46 55.46 55.46 55.46 55.46 55.46 55.48 55.48 55.48 55.48 55.48 55.48 88.07 88.08 88.09 88.09 88.09 88.08 88.08 88.07 88.07 88.06 88.06 88.06 88.06 88.05 88.05 88.06 88.06 88.06 88.07 88.07 88.08 98.33 98.33 98.33 98.34 98.35 98.34 98.33 98.32 98.30 98.31 98.32 98.31 98.30 98.30 98.31 98.31 98.31 98.31 98.31 98.31 98.31 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 91.57 91.57 91.57 92.96 97.95 81.19 81.19 81.19 81.19 81.19 81.19 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 81.18 103.63 107.33 108.47 106.96 103.94 98.87 93.59 93.28 93.04 92.98 92.98 93.96 94.77 94.50 93.29 92.98 92.98 92.98 94.18 97.49 103.64 79.86 79.87 79.88 79.87 79.87 79.86 79.85 79.84 79.83 79.85 79.86 79.87 79.87 79.88 79.88 79.87 79.86 79.85 79.84 79.84 79.85 113.45 119.15 121.90 121.75 118.60 115.49 118.12 118.02 115.16 109.63 112.83 114.09 112.99 109.59 104.19 98.44 97.49 97.49 99.55 105.15 113.47 78.66 78.64 78.62 78.64 78.65 78.66 78.67 78.69 78.68 78.67 78.65 78.64 78.64 78.63 78.63 95.70 95.71 95.71 95.71 95.71 82.14 82.32 82.11 82.23 82.32 82.03 82.16 83.27 84.01 88.28 92.33 94.12 93.66 91.80 88.51 83.09 82.35 82.15 82.37 82.29 82.14 96.61 98.86 99.29 98.44 106.60 114.75 120.10 122.54 121.98 119.50 115.11 108.21 98.92 95.75 95.81 95.44 95.44 95.44 95.44 95.44 96.64 82.17 82.71 82.31 82.35 82.25 82.15 82.33 84.18 86.15 92.81 97.20 99.21 98.77 96.36 92.93 87.30 82.60 82.58 82.44 82.19 82.16 111.60 117.41 120.52 120.82 124.05 132.91 138.46 140.63 139.44 135.39 129.46 120.80 112.72 110.86 106.56 103.70 103.70 103.69 103.70 103.69 111.67 87.28 86.13 83.98 82.49 82.25 83.92 86.59 88.64 92.81 100.62 105.99 108.76 108.84 106.24 102.00 95.70 95.71 95.71 95.71 97.95 86.84 86.85 86.87 86.88 86.87 86.85 86.84 86.83 86.82 88.28 92.33 94.12 93.66 91.80 88.51 86.79 86.80 86.81 86.82 86.83 86.85 103.63 107.33 108.47 106.96 106.60 114.75 120.10 122.54 121.98 119.50 115.11 108.21 98.92 95.75 95.81 95.44 95.44 95.44 95.44 97.49 103.64 88.07 88.08 88.09 88.09 88.09 88.08 88.08 88.07 88.07 92.81 97.20 99.21 98.77 96.36 92.93 88.06 88.06 88.06 88.07 88.07 88.08 113.45 119.15 121.90 121.75 124.05 132.91 138.46 140.63 139.44 135.39 129.46 120.80 112.99 110.86 106.56 103.70 103.70 103.69 103.70 105.15 113.47 89.22 89.22 89.22 89.22 89.22 89.22 89.22 89.22 92.81 100.62 105.99 108.76 108.84 106.24 102.00 1.78 1.78 1.78 1.78 1.82 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.64 1.71 1.75 1.74 1.70 1.64 1.61 1.61 1.61 1.61 1.61 1.61 1.92 1.99 2.01 1.98 1.98 2.13 2.23 2.27 2.26 2.22 2.14 2.01 1.84 1.78 1.78 1.77 1.77 1.77 1.77 1.81 1.92 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.72 1.80 1.84 1.83 1.79 1.72 1.63 1.63 1.63 1.63 1.63 1.63 2.11 2.21 2.26 2.26 2.30 2.47 2.57 2.61 2.59 2.51 2.40 2.24 2.10 2.06 1.98 1.92 1.92 1.92 1.92 1.95 2.11 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.72 1.87 1.97 2.02 2.02 1.97 1.89 53.84 53.84 53.84 53.84 53.84 66.74 66.29 67.10 66.44 66.37 66.32 66.31 66.32 66.36 66.42 66.48 66.35 66.21 66.13 66.14 66.26 66.47 66.31 66.07 66.01 66.77 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 53.88 66.92 66.51 67.30 66.69 66.62 66.57 66.55 66.56 66.59 66.64 66.70 66.69 66.49 66.36 66.38 66.56 66.69 66.53 66.32 66.09 66.95 87.64 87.64 87.64 87.64 87.64 87.64 87.64 87.64 87.65 87.65 87.65 87.65 87.65 87.64 87.64 87.64 87.64 87.64 87.64 87.64 87.64 67.52 67.20 67.75 67.46 67.39 67.34 67.31 67.30 67.32 67.35 67.39 67.42 67.43 67.30 67.31 92.62 92.63 92.63 92.63 92.63 70.39 69.66 70.49 70.22 70.13 70.09 70.09 70.14 70.22 70.33 70.45 70.33 70.18 70.11 70.12 70.23 70.44 70.17 69.79 69.71 70.40 92.87 98.54 103.55 106.01 105.85 103.07 97.76 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.88 92.88 92.88 92.88 70.19 69.43 70.42 69.96 69.87 69.83 69.84 69.89 69.98 70.10 70.22 70.28 70.19 70.07 70.09 70.22 70.21 69.93 69.53 69.63 70.22 96.49 105.48 111.87 115.49 116.25 114.32 109.83 102.64 93.18 93.18 93.18 93.18 93.18 93.18 93.18 93.18 93.18 93.18 93.30 93.87 96.54 69.58 68.72 69.95 69.17 69.08 69.04 69.06 69.13 69.23 69.37 69.51 69.55 69.25 69.14 69.16 93.59 93.59 93.59 93.59 93.59 80.82 80.80 80.79 80.78 80.77 80.78 80.79 80.81 80.82 80.84 80.85 83.53 86.97 88.27 87.40 84.38 80.86 80.85 80.83 80.82 80.80 93.41 93.41 93.41 93.41 93.41 93.41 94.65 101.53 105.91 107.68 106.86 103.67 97.93 93.41 93.41 93.41 93.41 93.41 93.41 93.41 93.41 80.83 80.81 80.80 80.79 80.77 80.79 80.80 80.82 80.83 80.85 81.43 87.14 90.71 92.05 91.12 87.95 82.62 80.86 80.84 80.83 80.81 99.59 99.59 99.59 99.59 99.59 99.59 107.96 115.43 120.05 121.71 120.37 116.07 108.90 99.53 99.53 99.53 99.53 99.53 99.53 99.53 99.53 80.84 80.82 80.81 80.80 80.78 80.79 80.81 80.82 80.84 80.85 87.36 93.81 97.97 99.71 99.00 93.59 93.59 93.59 93.59 93.59 80.82 80.80 80.79 80.78 80.77 80.78 80.79 80.81 80.82 80.84 80.85 83.53 86.97 88.27 87.40 84.38 80.86 80.85 80.83 80.82 80.80 93.41 98.54 103.55 106.01 105.85 103.07 97.76 101.53 105.91 107.68 106.86 103.67 97.93 93.41 93.41 93.41 93.41 93.41 93.41 93.41 93.41 80.83 80.81 80.80 80.79 80.77 80.79 80.80 80.82 80.83 80.85 81.43 87.14 90.71 92.05 91.12 87.95 82.62 80.86 80.84 80.83 80.81 99.59 105.48 111.87 115.49 116.25 114.32 109.83 115.43 120.05 121.71 120.37 116.07 108.90 99.53 99.53 99.53 99.53 99.53 99.53 99.53 99.53 80.84 80.82 80.81 80.80 80.78 80.79 80.81 80.82 80.84 80.85 87.36 93.81 97.97 99.71 99.00 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.74 1.74 1.74 1.74 1.74 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.55 1.61 1.64 1.62 1.57 1.50 1.50 1.50 1.50 1.50 1.73 1.83 1.92 1.97 1.96 1.91 1.81 1.88 1.97 2.00 1.98 1.92 1.82 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.51 1.62 1.68 1.71 1.69 1.63 1.53 1.50 1.50 1.50 1.50 1.85 1.96 2.08 2.14 2.16 2.12 2.04 2.14 2.23 2.26 2.23 2.15 2.02 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.62 1.74 1.82 1.85 1.84 53.80 53.79 53.79 53.79 53.79 54.00 53.92 56.68 62.23 58.99 55.70 53.92 54.00 54.07 54.13 54.18 54.21 54.24 54.25 54.25 54.23 54.21 54.17 54.12 54.06 53.99 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 53.81 54.02 54.36 57.07 61.78 59.45 56.27 53.94 54.02 54.08 54.14 54.19 54.23 54.25 54.26 54.26 54.25 54.22 54.18 54.13 54.07 54.00 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.32 81.32 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 61.58 59.47 59.93 60.49 60.44 59.57 60.01 62.05 63.82 65.22 66.40 67.29 67.85 68.12 68.04 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 92.74 92.74 92.74 92.74 92.74 67.85 67.29 65.92 61.98 64.13 66.17 67.64 68.22 68.24 67.78 67.17 65.87 65.43 65.04 65.27 65.50 66.50 67.57 67.42 68.24 67.81 92.92 93.80 98.65 101.06 100.97 98.40 93.39 92.92 92.92 92.92 92.92 92.92 92.92 92.92 92.92 92.92 92.92 92.93 92.93 92.93 92.93 67.59 67.12 66.05 62.43 64.51 65.81 66.63 67.15 67.35 66.12 65.49 64.83 64.06 63.66 63.21 64.20 64.67 66.03 66.85 67.44 67.58 93.38 102.71 109.49 113.57 114.85 113.29 108.94 101.90 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.43 60.87 62.39 62.99 63.73 63.51 62.28 61.83 61.00 62.03 62.84 63.52 64.03 64.35 64.50 64.45 93.51 93.51 93.51 93.51 93.51 80.68 80.68 80.68 80.68 80.68 80.68 80.67 80.67 80.67 80.68 80.68 80.68 82.66 84.02 83.31 80.68 80.68 80.68 80.68 80.67 80.67 93.35 93.35 93.35 93.35 93.35 93.35 93.35 95.05 100.02 102.53 102.52 99.97 94.96 93.35 93.35 93.35 93.35 93.35 93.35 93.35 93.35 80.69 80.68 80.68 80.68 80.68 80.68 80.68 80.67 80.68 80.68 80.68 81.33 84.65 85.90 85.03 82.06 80.68 80.68 80.68 80.68 80.67 97.38 97.38 97.38 97.38 97.38 97.38 104.14 111.75 116.61 118.59 117.65 113.81 107.17 97.87 97.33 97.33 97.33 97.33 97.33 97.33 97.33 80.69 80.69 80.68 80.69 80.68 80.68 80.68 80.68 80.68 80.68 80.69 84.57 88.13 89.96 89.58 93.51 93.51 93.51 93.51 93.51 80.68 80.68 80.68 80.68 80.68 80.68 80.67 80.67 80.67 80.68 80.68 80.68 82.66 84.02 83.31 80.68 80.68 80.68 80.68 80.67 80.67 93.35 93.80 98.65 101.06 100.97 98.40 93.39 95.05 100.02 102.53 102.52 99.97 94.96 93.35 93.35 93.35 93.35 93.35 93.35 93.35 93.35 80.69 80.68 80.68 80.68 80.68 80.68 80.68 80.67 80.68 80.68 80.68 81.33 84.65 85.90 85.03 82.06 80.68 80.68 80.68 80.68 80.67 97.38 102.71 109.49 113.57 114.85 113.29 108.94 111.75 116.61 118.59 117.65 113.81 107.17 97.87 97.33 97.33 97.33 97.33 97.33 97.33 97.33 80.69 80.69 80.68 80.69 80.68 80.68 80.68 80.68 80.68 80.68 80.69 84.57 88.13 89.96 89.58 1.74 1.74 1.74 1.74 1.74 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.53 1.56 1.55 1.50 1.50 1.50 1.50 1.50 1.50 1.73 1.74 1.83 1.88 1.87 1.83 1.73 1.76 1.86 1.90 1.90 1.86 1.76 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.51 1.57 1.59 1.58 1.52 1.50 1.50 1.50 1.50 1.50 1.81 1.91 2.03 2.11 2.13 2.10 2.02 2.07 2.16 2.20 2.18 2.11 1.99 1.82 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.57 1.64 1.67 1.66 Simulation 1 Variables StartSimulation Delay (s) 625 626 627 628 629 630 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault NER Duration Size (s) (Ohm) 0.1 0.1 0.1 0.1 0.1 0.1 1E+06 1E+06 1E+06 1E+06 1E+06 1E+06 Line Length=10km Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) 89.22 89.22 89.22 89.22 89.22 89.22 78.64 78.65 78.66 78.68 78.69 78.67 96.19 91.71 90.93 88.12 87.25 87.26 96.19 91.71 90.93 89.22 89.22 89.22 1.78 1.70 1.69 1.66 1.66 1.66 67.44 67.37 67.26 67.09 66.87 67.53 69.36 69.51 69.18 68.73 68.85 69.62 95.85 90.35 82.64 80.85 80.84 80.82 95.85 90.35 82.64 80.85 80.84 80.82 Line Length=0.2km Ratio Vmax/Vnom Va (kV) 1.78 1.68 1.53 1.50 1.50 1.50 67.76 67.10 66.19 64.99 63.45 61.65 Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 64.30 63.92 63.40 62.70 61.81 60.77 86.98 82.26 80.68 80.68 80.68 80.68 86.98 82.26 80.68 80.68 80.68 80.68 1.61 1.53 1.50 1.50 1.50 1.50 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 57.71 59.95 61.97 66.46 69.68 71.46 68.75 71.13 71.60 70.84 68.35 64.53 60.75 58.99 56.41 56.17 55.93 55.82 56.05 56.16 57.68 56.01 58.26 61.17 65.94 69.48 71.45 68.16 70.50 71.24 71.02 68.70 64.16 61.09 58.29 57.48 55.59 57.32 54.76 56.23 57.97 55.98 61.06 61.06 61.06 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 61.07 90.41 88.14 88.52 88.00 86.26 83.45 64.26 60.03 60.15 59.59 91.39 92.96 93.81 94.15 94.13 93.73 92.81 91.18 91.73 91.55 90.40 56.02 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 56.00 57.91 58.38 57.40 55.30 55.61 55.05 56.22 55.98 55.38 56.44 56.77 55.72 56.72 56.49 56.03 56.41 56.21 56.12 56.34 56.32 57.92 71.15 71.62 72.60 69.38 65.62 63.13 58.89 56.69 55.59 55.50 55.37 55.50 55.58 56.66 58.94 61.30 66.20 69.86 70.84 68.42 71.16 65.20 64.26 61.73 57.67 54.77 55.97 56.78 56.36 58.21 58.70 59.67 61.02 61.30 63.17 63.57 63.89 64.29 63.92 64.28 64.55 65.19 62.00 61.15 59.27 60.98 58.61 56.87 55.63 54.02 54.14 54.94 62.20 62.47 62.43 62.26 62.27 62.43 62.46 62.08 60.76 60.49 62.00 73.63 73.89 72.34 72.30 71.89 71.84 72.82 72.14 72.44 73.11 72.08 73.37 73.59 73.29 74.52 74.06 73.83 74.13 74.54 54.77 55.50 56.64 56.74 58.23 59.16 59.05 60.82 61.08 62.56 63.33 62.54 60.20 56.98 56.01 55.12 54.84 54.74 54.98 55.16 54.76 56.39 55.80 56.51 56.38 56.63 58.00 55.69 56.61 57.55 58.07 60.26 60.96 60.16 59.86 60.07 58.79 56.34 56.54 55.95 56.02 56.42 91.06 92.40 91.76 90.05 90.71 89.72 90.17 89.24 90.70 90.90 90.30 91.67 91.50 91.17 92.19 91.60 91.54 91.69 92.00 92.03 91.04 76.62 76.62 75.41 76.16 75.56 75.84 76.27 75.21 78.33 77.08 75.46 76.64 75.92 75.15 75.87 76.46 75.63 76.44 77.01 75.82 76.62 98.62 98.60 97.61 99.32 98.62 97.59 97.27 97.89 97.75 97.32 98.22 97.79 97.40 98.25 97.51 97.33 97.70 97.51 97.55 57.91 59.95 61.97 66.46 69.68 71.46 68.75 71.13 71.60 70.84 68.35 64.53 60.75 58.99 56.41 56.41 56.21 56.12 56.34 56.32 57.92 71.15 71.62 72.60 69.38 69.48 71.45 68.16 70.50 71.24 71.02 68.70 64.16 61.09 59.86 60.07 61.30 66.20 69.86 70.84 68.42 71.16 91.06 92.40 91.76 90.05 90.71 89.72 90.17 89.24 90.70 90.90 90.30 91.67 91.50 91.17 92.19 91.60 91.54 91.69 92.00 92.03 91.04 90.41 88.14 88.52 88.00 86.26 83.45 76.27 75.21 78.33 77.08 91.39 92.96 93.81 94.15 94.13 93.73 92.81 91.18 91.73 91.55 90.40 98.62 98.60 97.61 99.32 98.62 97.59 97.27 97.89 97.75 97.32 98.22 97.79 97.40 98.25 97.51 97.33 97.70 97.51 97.55 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.07 1.11 1.15 1.23 1.29 1.33 1.28 1.32 1.33 1.31 1.27 1.20 1.13 1.09 1.05 1.05 1.04 1.04 1.05 1.05 1.07 1.32 1.33 1.35 1.29 1.29 1.33 1.26 1.31 1.32 1.32 1.27 1.19 1.13 1.11 1.11 1.14 1.23 1.30 1.31 1.27 1.32 1.69 1.71 1.70 1.67 1.68 1.66 1.67 1.66 1.68 1.69 1.68 1.70 1.70 1.69 1.71 1.70 1.70 1.70 1.71 1.71 1.69 1.68 1.64 1.64 1.63 1.60 1.55 1.42 1.40 1.45 1.43 1.70 1.73 1.74 1.75 1.75 1.74 1.72 1.69 1.70 1.70 1.68 1.83 1.83 1.81 1.84 1.83 1.81 1.81 1.82 1.81 1.81 1.82 1.81 1.81 1.82 1.81 1.81 1.81 1.81 1.81 53.78 53.78 56.70 62.30 67.23 70.67 71.06 72.77 70.95 69.47 65.58 60.40 53.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 55.81 61.92 66.58 70.37 71.40 72.78 71.33 69.68 64.88 59.72 54.28 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 56.44 56.44 56.44 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 56.40 82.28 79.43 80.24 80.96 81.02 78.96 59.33 55.54 53.78 53.78 88.32 89.39 90.08 90.41 90.39 90.01 89.28 88.16 86.63 84.68 82.27 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 Vb (kV) Vc (kV) V Max (kV) 57.79 58.26 57.30 54.93 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 55.50 56.72 57.06 56.52 55.75 55.51 56.10 56.85 57.81 71.89 72.45 69.71 67.22 62.57 56.30 53.78 53.78 53.78 53.78 53.78 53.78 55.50 56.81 57.00 56.54 61.84 67.06 70.24 71.41 71.89 60.55 58.63 57.74 55.42 54.40 54.45 55.01 55.67 56.43 57.29 58.23 59.23 60.27 61.28 62.21 62.98 63.49 63.61 63.23 62.23 60.56 53.78 53.78 53.78 53.78 53.78 53.78 53.78 54.46 55.84 56.08 56.40 56.44 57.01 56.29 56.33 57.15 56.69 55.87 55.35 54.97 53.78 71.18 70.95 70.95 70.95 70.99 71.05 71.13 71.24 71.39 71.57 71.79 72.07 72.39 72.76 73.14 73.50 73.77 73.84 73.56 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 55.42 56.46 56.88 55.90 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 54.81 56.68 56.90 56.22 55.26 54.88 55.31 58.08 59.76 59.96 58.68 55.97 53.78 53.78 53.78 53.78 90.61 89.85 88.80 88.62 88.71 88.86 89.03 89.22 89.45 89.70 89.98 90.27 90.56 90.85 91.11 91.32 91.45 91.49 91.38 91.10 90.60 75.16 75.24 75.31 75.36 75.35 75.27 75.06 74.84 76.85 74.83 74.83 74.83 74.83 74.83 74.86 74.89 74.93 74.98 75.03 75.09 75.17 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.87 96.91 96.95 97.00 97.05 97.09 97.13 97.13 97.10 57.79 58.26 57.30 62.30 67.23 70.67 71.06 72.77 70.95 69.47 65.58 60.40 56.46 56.88 57.06 56.52 55.75 55.51 56.10 56.85 57.81 71.89 72.45 69.71 67.22 66.58 70.37 71.40 72.78 71.33 69.68 64.88 59.72 58.08 59.76 59.96 58.68 61.84 67.06 70.24 71.41 71.89 90.61 89.85 88.80 88.62 88.71 88.86 89.03 89.22 89.45 89.70 89.98 90.27 90.56 90.85 91.11 91.32 91.45 91.49 91.38 91.10 90.60 82.28 79.43 80.24 80.96 81.02 78.96 75.06 74.84 76.85 74.83 88.32 89.39 90.08 90.41 90.39 90.01 89.28 88.16 86.63 84.68 82.27 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.85 96.87 96.91 96.95 97.00 97.05 97.09 97.13 97.13 97.10 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.07 1.08 1.06 1.16 1.25 1.31 1.32 1.35 1.32 1.29 1.22 1.12 1.05 1.06 1.06 1.05 1.03 1.03 1.04 1.05 1.07 1.33 1.34 1.29 1.25 1.24 1.31 1.32 1.35 1.32 1.29 1.20 1.11 1.08 1.11 1.11 1.09 1.15 1.24 1.30 1.33 1.33 1.68 1.67 1.65 1.64 1.65 1.65 1.65 1.66 1.66 1.66 1.67 1.68 1.68 1.69 1.69 1.69 1.70 1.70 1.70 1.69 1.68 1.53 1.47 1.49 1.50 1.50 1.47 1.39 1.39 1.43 1.39 1.64 1.66 1.67 1.68 1.68 1.67 1.66 1.64 1.61 1.57 1.53 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 53.77 53.77 53.77 57.19 61.83 64.46 65.97 66.44 65.64 63.12 60.08 55.17 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 57.76 62.74 65.68 66.06 67.09 65.68 63.87 59.76 54.86 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 82.27 79.43 76.17 75.20 74.91 74.03 54.42 53.77 53.77 53.77 88.31 89.38 90.07 90.39 90.37 90.00 89.27 88.14 86.62 84.66 82.26 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 57.78 58.26 57.29 54.92 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 55.94 56.70 57.25 56.27 55.60 55.31 56.14 56.95 57.80 66.14 65.92 63.93 60.57 56.41 53.77 53.77 53.77 53.77 53.77 53.77 53.77 56.16 57.11 57.24 56.50 57.12 62.07 65.27 65.32 66.14 60.43 58.62 57.73 55.41 55.27 55.27 55.27 55.70 56.46 57.32 58.26 59.26 60.29 61.30 62.23 63.00 63.49 63.61 63.23 62.21 60.44 53.77 53.77 53.77 53.77 53.77 53.77 53.77 54.71 56.38 56.57 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 71.15 70.94 70.94 70.96 71.00 71.06 71.15 71.26 71.40 71.59 71.82 72.09 72.41 72.77 73.15 73.50 73.76 73.83 73.56 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 54.64 56.45 56.88 55.90 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 55.39 56.63 56.85 56.06 54.88 54.48 55.06 58.07 59.75 59.95 58.68 55.96 53.78 53.78 53.78 53.78 90.62 89.87 88.83 88.60 88.71 88.85 89.02 89.22 89.45 89.70 89.98 90.27 90.56 90.85 91.10 91.31 91.44 91.47 91.38 91.10 90.61 75.15 75.22 75.29 75.32 75.32 75.24 75.03 74.83 76.84 74.82 74.82 74.82 74.82 74.83 74.85 74.88 74.92 74.97 75.02 75.09 75.16 96.83 96.84 96.84 96.84 96.84 96.84 96.84 96.84 96.84 96.84 96.87 96.90 96.95 96.99 97.04 97.08 97.11 97.12 97.09 57.78 58.26 57.29 57.19 61.83 64.46 65.97 66.44 65.64 63.12 60.08 55.17 56.45 56.88 57.25 56.27 55.60 55.31 56.14 56.95 57.80 66.14 65.92 63.93 60.57 62.74 65.68 66.06 67.09 65.68 63.87 59.76 55.06 58.07 59.75 59.95 58.68 57.12 62.07 65.27 65.32 66.14 90.62 89.87 88.83 88.60 88.71 88.85 89.02 89.22 89.45 89.70 89.98 90.27 90.56 90.85 91.10 91.31 91.44 91.47 91.38 91.10 90.61 82.27 79.43 76.17 75.32 75.32 75.24 75.03 74.83 76.84 74.82 88.31 89.38 90.07 90.39 90.37 90.00 89.27 88.14 86.62 84.66 82.26 96.83 96.84 96.84 96.84 96.84 96.84 96.84 96.84 96.84 96.84 96.87 96.90 96.95 96.99 97.04 97.08 97.11 97.12 97.09 1.07 1.08 1.06 1.06 1.15 1.20 1.22 1.23 1.22 1.17 1.11 1.02 1.05 1.06 1.06 1.04 1.03 1.03 1.04 1.06 1.07 1.23 1.22 1.19 1.12 1.16 1.22 1.23 1.24 1.22 1.19 1.11 1.02 1.08 1.11 1.11 1.09 1.06 1.15 1.21 1.21 1.23 1.68 1.67 1.65 1.64 1.65 1.65 1.65 1.66 1.66 1.66 1.67 1.68 1.68 1.69 1.69 1.69 1.70 1.70 1.70 1.69 1.68 1.53 1.47 1.41 1.40 1.40 1.40 1.39 1.39 1.43 1.39 1.64 1.66 1.67 1.68 1.68 1.67 1.66 1.64 1.61 1.57 1.53 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 56.00 56.00 96.34 94.12 90.39 88.39 86.59 63.63 57.78 56.59 55.78 56.26 56.11 98.64 99.21 99.37 99.36 99.17 98.52 97.05 96.72 97.13 96.32 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.95 55.97 99.08 96.80 92.84 90.94 65.94 62.03 60.75 57.15 55.81 55.93 55.87 55.70 100.07 100.14 100.14 100.04 99.50 98.05 99.06 99.76 99.07 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.38 55.39 55.39 100.17 97.79 94.00 93.58 66.37 63.04 60.87 58.48 56.81 55.32 55.44 55.24 99.84 99.87 99.87 99.82 99.30 74.71 73.63 55.92 55.63 57.15 56.40 55.54 60.16 62.55 55.34 58.31 55.93 57.64 55.89 56.51 56.72 56.71 56.45 55.83 55.70 56.51 57.03 55.92 79.64 80.65 79.72 80.07 79.18 79.79 80.38 79.19 79.99 80.27 79.24 80.24 80.12 79.90 80.68 80.03 79.77 80.00 80.43 80.94 79.65 55.50 56.71 56.78 55.36 58.24 61.93 63.87 62.41 57.67 55.23 58.03 56.30 55.86 56.06 56.04 55.83 55.78 56.33 56.86 56.19 55.49 83.97 85.52 84.97 83.89 83.10 83.90 84.14 83.11 83.99 83.93 83.28 84.04 83.58 83.74 84.23 83.31 83.31 83.51 83.99 84.52 83.98 55.33 56.40 55.62 54.96 59.73 62.25 64.49 64.82 62.38 55.61 58.07 55.88 55.26 55.33 55.32 55.26 55.45 97.37 98.60 80.44 79.92 79.10 79.72 79.08 79.64 79.67 91.65 87.40 85.96 82.27 83.55 82.76 79.94 79.94 79.95 79.16 80.45 80.32 79.27 80.44 99.58 98.51 100.36 101.22 99.64 100.90 101.02 98.83 98.42 98.84 99.04 98.43 98.86 98.92 98.32 98.48 98.34 98.19 98.23 98.57 99.55 81.34 80.55 80.29 80.58 80.02 80.63 80.48 81.72 92.04 90.94 86.56 86.65 85.76 82.76 80.78 80.52 80.32 81.29 80.83 80.49 81.34 99.06 98.16 100.75 101.00 100.75 102.89 102.53 99.65 98.96 98.76 98.43 98.10 98.83 98.32 98.03 98.42 97.98 97.98 97.99 98.58 99.03 81.64 80.69 80.78 80.87 80.37 81.01 80.73 82.34 83.70 93.88 89.43 88.03 87.03 83.89 81.01 80.59 80.78 97.37 98.60 96.34 94.12 90.39 88.39 86.59 79.64 79.67 91.65 87.40 85.96 82.27 98.64 99.21 99.37 99.36 99.17 98.52 97.05 96.72 97.13 96.32 99.58 98.51 100.36 101.22 99.64 100.90 101.02 98.83 98.42 98.84 99.04 98.43 98.86 98.92 98.32 98.48 98.34 98.19 98.23 98.57 99.55 99.08 96.80 92.84 90.94 80.02 80.63 80.48 81.72 92.04 90.94 86.56 86.65 100.07 100.14 100.14 100.04 99.50 98.05 99.06 99.76 99.07 99.06 98.16 100.75 101.00 100.75 102.89 102.53 99.65 98.96 98.76 98.43 98.10 98.83 98.32 98.03 98.42 97.98 97.98 97.99 98.58 99.03 100.17 97.79 94.00 93.58 80.37 81.01 80.73 82.34 83.70 93.88 89.43 88.03 99.84 99.87 99.87 99.82 99.30 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.81 1.83 1.79 1.75 1.68 1.64 1.61 1.48 1.48 1.70 1.62 1.60 1.53 1.83 1.84 1.84 1.84 1.84 1.83 1.80 1.79 1.80 1.79 1.85 1.83 1.86 1.88 1.85 1.87 1.87 1.83 1.83 1.83 1.84 1.83 1.83 1.84 1.82 1.83 1.82 1.82 1.82 1.83 1.85 1.84 1.80 1.72 1.69 1.48 1.50 1.49 1.52 1.71 1.69 1.61 1.61 1.86 1.86 1.86 1.86 1.85 1.82 1.84 1.85 1.84 1.84 1.82 1.87 1.87 1.87 1.91 1.90 1.85 1.84 1.83 1.83 1.82 1.83 1.82 1.82 1.83 1.82 1.82 1.82 1.83 1.84 1.86 1.81 1.74 1.74 1.49 1.50 1.50 1.53 1.55 1.74 1.66 1.63 1.85 1.85 1.85 1.85 1.84 53.78 53.78 89.37 86.46 82.92 78.77 76.70 57.58 53.78 53.78 53.78 53.78 53.78 95.60 96.09 96.32 96.30 96.04 95.52 94.66 93.40 91.66 89.36 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 92.48 89.95 86.59 82.54 59.32 57.24 53.78 53.78 53.78 53.78 53.78 53.78 97.39 97.51 97.50 97.36 97.05 96.51 95.64 94.34 92.47 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 93.98 91.83 88.92 84.99 60.41 54.19 53.78 53.78 53.78 53.78 53.78 53.78 97.45 97.51 97.51 97.44 97.27 Vb (kV) Vc (kV) V Max (kV) 72.74 71.21 53.78 53.78 53.78 53.78 53.78 54.33 54.42 56.58 56.48 56.52 56.46 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 78.90 78.90 78.90 78.90 78.90 78.90 78.90 78.90 78.90 78.94 78.99 79.05 79.14 79.26 79.39 79.54 79.66 79.70 79.53 78.97 78.90 53.78 53.78 53.78 53.78 61.09 59.37 56.56 57.09 55.42 55.43 55.36 55.28 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.90 82.94 82.99 83.04 83.10 83.12 83.02 82.91 82.91 53.78 53.78 53.78 53.78 59.69 62.70 59.93 55.31 56.93 54.57 54.52 54.53 53.78 53.78 53.78 53.78 53.78 96.99 96.85 78.88 78.88 78.88 78.88 78.88 78.88 78.88 88.53 86.13 83.37 80.40 78.88 78.88 78.88 78.88 78.88 78.88 78.88 78.88 78.88 78.88 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 79.82 79.82 79.82 79.82 79.82 79.82 79.82 79.82 90.05 87.46 84.42 81.27 79.82 79.82 79.82 79.82 79.82 79.82 79.82 79.82 79.82 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 80.17 80.17 80.17 80.17 80.17 80.17 80.17 80.17 80.17 89.70 86.83 83.86 80.17 80.17 80.17 80.17 80.17 96.99 96.85 89.37 86.46 82.92 78.88 78.88 78.88 78.88 88.53 86.13 83.37 80.40 95.60 96.09 96.32 96.30 96.04 95.52 94.66 93.40 91.66 89.36 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 97.92 92.48 89.95 86.59 82.54 79.82 79.82 79.82 79.82 90.05 87.46 84.42 81.27 97.39 97.51 97.50 97.36 97.05 96.51 95.64 94.34 92.47 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 97.71 93.98 91.83 88.92 84.99 80.17 80.17 80.17 80.17 80.17 89.70 86.83 83.86 97.45 97.51 97.51 97.44 97.27 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.80 1.80 1.66 1.60 1.54 1.46 1.46 1.46 1.46 1.64 1.60 1.55 1.49 1.77 1.78 1.79 1.79 1.78 1.77 1.76 1.73 1.70 1.66 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.72 1.67 1.61 1.53 1.48 1.48 1.48 1.48 1.67 1.62 1.57 1.51 1.81 1.81 1.81 1.81 1.80 1.79 1.77 1.75 1.72 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.74 1.70 1.65 1.58 1.49 1.49 1.49 1.49 1.49 1.66 1.61 1.56 1.81 1.81 1.81 1.81 1.81 53.77 53.77 89.35 86.44 82.88 78.68 73.86 53.77 53.77 53.77 53.77 53.77 53.77 95.58 96.07 96.30 96.28 96.03 95.50 94.64 93.38 91.64 89.34 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 92.45 89.89 86.58 82.47 56.46 53.77 53.77 53.77 53.77 53.77 53.77 53.77 97.37 97.49 97.48 97.34 97.03 96.49 95.62 94.31 92.43 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 93.95 91.79 88.81 84.92 54.22 53.77 53.77 53.77 53.77 53.77 53.77 53.77 97.43 97.49 97.49 97.42 97.25 72.75 71.18 53.77 53.77 53.77 53.77 53.77 53.77 55.84 56.93 56.74 56.72 56.67 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 78.88 78.88 78.88 78.88 78.88 78.88 78.88 78.89 78.92 78.96 79.01 79.07 79.16 79.27 79.40 79.54 79.66 79.69 79.53 78.98 78.89 53.77 53.77 53.77 53.77 55.11 53.77 55.89 56.59 55.50 55.46 55.37 55.33 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 82.89 82.89 82.89 82.89 82.89 82.89 82.89 82.89 82.89 82.89 82.89 82.89 82.92 82.95 82.99 83.04 83.09 83.11 83.02 82.89 82.89 53.77 53.77 53.77 53.77 57.93 56.08 55.21 56.62 56.36 54.33 54.18 54.23 53.77 53.77 53.77 53.77 53.77 96.99 96.84 78.87 78.87 78.87 78.87 78.87 78.87 78.87 88.51 86.11 83.34 80.22 78.87 78.87 78.87 78.87 78.87 78.87 78.87 78.87 78.87 78.87 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 79.81 79.81 79.81 79.80 79.81 79.81 79.81 79.81 90.03 87.38 84.29 80.79 79.80 79.80 79.80 79.80 79.80 79.80 79.81 79.81 79.81 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 80.16 80.16 80.16 80.16 80.16 80.16 80.16 80.16 80.16 89.62 86.69 83.34 80.16 80.16 80.16 80.15 80.15 96.99 96.84 89.35 86.44 82.88 78.87 78.87 78.87 78.87 88.51 86.11 83.34 80.22 95.58 96.07 96.30 96.28 96.03 95.50 94.64 93.38 91.64 89.34 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 97.90 92.45 89.89 86.58 82.47 79.81 79.81 79.81 79.81 90.03 87.38 84.29 80.79 97.37 97.49 97.48 97.34 97.03 96.49 95.62 94.31 92.43 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 97.69 93.95 91.79 88.81 84.92 80.16 80.16 80.16 80.16 80.16 89.62 86.69 83.34 97.43 97.49 97.49 97.42 97.25 1.80 1.80 1.66 1.60 1.54 1.46 1.46 1.46 1.46 1.64 1.60 1.55 1.49 1.77 1.78 1.79 1.79 1.78 1.77 1.76 1.73 1.70 1.66 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.72 1.67 1.61 1.53 1.48 1.48 1.48 1.48 1.67 1.62 1.56 1.50 1.81 1.81 1.81 1.81 1.80 1.79 1.77 1.75 1.72 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.74 1.70 1.65 1.58 1.49 1.49 1.49 1.49 1.49 1.66 1.61 1.55 1.81 1.81 1.81 1.81 1.80 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 98.45 100.01 100.84 100.15 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.83 54.84 54.84 100.35 97.85 96.58 73.04 67.04 63.88 61.53 58.42 58.00 56.21 55.01 54.70 54.74 99.37 99.37 99.34 98.81 98.68 100.23 101.07 100.34 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.39 54.40 54.40 54.40 100.07 97.45 98.94 73.32 67.83 64.43 62.15 58.83 58.41 57.34 54.53 54.63 54.82 98.86 98.86 98.84 98.30 98.64 100.06 100.87 100.06 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 54.14 56.14 56.15 55.08 55.31 87.16 89.05 88.76 86.33 85.44 86.27 86.25 85.45 86.32 86.00 85.67 86.26 85.66 86.10 86.39 85.53 85.56 85.74 86.26 86.69 87.17 55.32 55.86 55.15 59.07 62.39 62.68 64.81 65.34 64.01 59.86 57.82 55.33 56.10 54.76 54.76 54.79 55.14 55.69 55.42 54.58 55.29 89.54 91.66 91.53 89.20 86.95 87.78 87.54 86.96 87.80 87.28 87.20 87.67 87.15 87.64 87.77 87.03 87.08 87.24 87.77 88.09 89.56 55.17 55.38 54.78 59.10 63.49 64.17 65.08 65.66 64.54 61.52 56.70 55.71 56.67 54.34 54.33 54.41 54.85 55.27 55.05 54.16 55.15 91.34 93.61 93.59 91.31 87.99 88.80 88.40 88.01 88.82 88.15 88.24 88.61 88.17 88.70 88.70 81.52 80.88 80.98 81.65 98.29 98.29 100.44 100.25 101.74 103.54 102.83 101.42 102.29 100.64 97.72 97.92 98.43 97.66 97.63 98.02 97.56 97.56 97.56 98.25 98.27 81.78 80.69 81.04 81.00 80.57 81.23 80.83 82.66 83.91 84.24 91.19 88.59 87.50 84.26 83.30 81.97 81.02 81.58 80.82 81.24 81.78 97.56 98.14 99.95 99.43 102.10 103.63 102.66 103.97 104.59 102.64 98.17 97.67 97.97 97.24 97.32 97.59 97.15 97.15 97.23 97.83 97.54 81.86 80.66 81.19 81.06 80.69 81.36 80.88 82.85 84.02 84.55 87.74 88.76 87.59 85.54 85.50 84.21 81.52 81.58 80.75 81.40 81.86 96.93 97.90 99.45 98.68 102.19 103.50 102.72 105.76 106.19 104.00 99.27 97.42 97.55 96.86 97.03 98.45 100.01 100.84 100.15 98.29 98.29 100.44 100.25 101.74 103.54 102.83 101.42 102.29 100.64 97.72 97.92 98.43 97.66 97.63 98.02 97.56 97.56 97.56 98.25 98.27 100.35 97.85 96.58 81.00 80.57 81.23 80.83 82.66 83.91 84.24 91.19 88.59 87.50 99.37 99.37 99.34 98.81 98.68 100.23 101.07 100.34 97.56 98.14 99.95 99.43 102.10 103.63 102.66 103.97 104.59 102.64 98.17 97.67 97.97 97.24 97.32 97.59 97.15 97.15 97.23 97.83 97.54 100.07 97.45 98.94 81.06 80.69 81.36 80.88 82.85 84.02 84.55 87.74 88.76 87.59 98.86 98.86 98.84 98.30 98.64 100.06 100.87 100.06 96.93 97.90 99.45 98.68 102.19 103.50 102.72 105.76 106.19 104.00 99.27 97.42 97.55 96.86 97.03 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.83 1.86 1.87 1.86 1.82 1.82 1.86 1.86 1.89 1.92 1.91 1.88 1.90 1.87 1.81 1.82 1.83 1.81 1.81 1.82 1.81 1.81 1.81 1.82 1.82 1.86 1.82 1.79 1.50 1.50 1.51 1.50 1.53 1.56 1.56 1.69 1.64 1.62 1.84 1.84 1.84 1.83 1.83 1.86 1.88 1.86 1.81 1.82 1.85 1.85 1.89 1.92 1.91 1.93 1.94 1.90 1.82 1.81 1.82 1.80 1.81 1.81 1.80 1.80 1.80 1.82 1.81 1.86 1.81 1.84 1.50 1.50 1.51 1.50 1.54 1.56 1.57 1.63 1.65 1.63 1.83 1.83 1.83 1.82 1.83 1.86 1.87 1.86 1.80 1.82 1.85 1.83 1.90 1.92 1.91 1.96 1.97 1.93 1.84 1.81 1.81 1.80 1.80 96.95 96.38 95.43 93.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 94.76 92.93 90.28 69.84 61.40 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 97.20 97.20 97.17 97.08 96.90 96.54 95.88 94.75 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.14 93.67 91.30 69.25 62.34 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 96.84 96.82 96.78 96.67 96.45 95.99 95.13 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 Vb (kV) Vc (kV) V Max (kV) 53.78 53.78 53.78 53.78 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.23 85.25 85.26 85.23 85.23 85.23 53.78 53.78 53.78 60.11 60.45 64.63 62.70 57.76 55.44 55.74 54.70 54.03 54.03 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.72 86.73 86.73 86.73 53.78 53.78 53.78 61.48 62.67 63.67 65.26 60.48 55.99 55.36 54.24 53.95 53.88 53.86 53.78 53.78 53.78 53.78 53.78 53.78 53.78 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 87.76 80.17 80.17 80.17 80.17 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 80.34 80.34 80.34 80.34 80.34 80.34 80.34 80.34 80.34 80.34 80.33 85.52 82.33 81.21 81.14 80.33 80.33 80.33 80.34 80.34 80.34 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 80.43 80.43 80.43 80.44 80.43 80.43 80.43 80.43 80.43 80.43 80.43 80.43 80.43 80.43 83.24 82.00 80.43 80.43 80.43 80.43 80.43 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.95 96.38 95.43 93.96 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 97.29 94.76 92.93 90.28 80.34 80.34 80.34 80.34 80.34 80.34 80.34 80.33 85.52 82.33 97.20 97.20 97.17 97.08 96.90 96.54 95.88 94.75 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 96.88 95.14 93.67 91.30 80.44 80.43 80.43 80.43 80.43 80.43 80.43 80.43 80.43 80.43 80.43 96.84 96.82 96.78 96.67 96.45 95.99 95.13 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 96.52 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.80 1.79 1.77 1.74 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.76 1.72 1.68 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.59 1.53 1.80 1.80 1.80 1.80 1.80 1.79 1.78 1.76 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.77 1.74 1.69 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.80 1.80 1.80 1.79 1.79 1.78 1.77 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 96.93 96.35 95.41 93.94 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 94.71 92.89 90.23 64.30 54.93 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 97.18 97.18 97.14 97.06 96.87 96.51 95.84 94.70 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 95.08 93.56 91.18 63.79 55.94 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 96.82 96.80 96.75 96.65 96.42 95.96 95.07 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.77 53.77 53.77 53.77 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.21 85.23 85.24 85.25 85.21 85.22 85.22 53.77 53.77 53.77 53.77 57.49 58.60 56.30 56.12 56.14 55.50 54.44 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.71 86.72 86.72 86.72 53.77 53.77 53.77 55.65 56.47 60.37 57.67 55.73 55.87 54.98 53.94 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 87.74 80.16 80.16 80.16 80.16 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 80.33 80.33 80.32 80.33 80.33 80.33 80.33 80.33 80.32 80.32 80.32 85.06 81.78 80.76 80.69 80.32 80.32 80.32 80.32 80.33 80.33 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.60 82.82 81.55 80.42 80.42 80.42 80.42 80.42 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.93 96.35 95.41 93.94 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 97.27 94.71 92.89 90.23 80.33 80.33 80.33 80.33 80.33 80.32 80.32 80.32 85.06 81.78 97.18 97.18 97.14 97.06 96.87 96.51 95.84 94.70 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 96.86 95.08 93.56 91.18 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.42 80.60 96.82 96.80 96.75 96.65 96.42 95.96 95.07 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 96.50 1.80 1.79 1.77 1.74 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.76 1.72 1.67 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.58 1.52 1.80 1.80 1.80 1.80 1.80 1.79 1.78 1.76 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.76 1.74 1.69 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.50 1.80 1.80 1.80 1.79 1.79 1.78 1.76 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 54.14 54.14 54.14 54.12 54.12 54.12 99.58 99.37 100.90 73.50 68.52 64.76 62.67 59.30 58.90 57.81 55.34 54.01 54.71 54.35 54.39 98.39 97.84 98.49 99.71 100.47 99.57 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.08 54.06 54.06 54.06 99.55 101.08 102.76 73.49 68.91 65.02 63.07 59.73 59.32 58.02 56.01 54.21 54.48 54.32 54.36 54.43 54.21 98.29 99.29 99.97 99.56 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.04 54.02 54.02 54.02 100.41 102.62 104.33 73.44 69.23 65.15 63.34 60.11 59.59 58.19 56.40 54.45 54.16 88.06 88.16 88.30 88.83 89.03 91.36 54.97 55.14 54.48 59.29 64.28 65.65 65.26 65.86 64.86 62.12 58.21 55.65 55.49 55.90 55.96 54.13 54.61 54.93 54.84 54.00 54.94 92.73 95.09 95.14 92.88 88.77 89.54 89.01 88.77 89.55 88.88 88.98 89.28 88.90 89.48 89.35 88.81 88.97 89.08 89.60 89.70 92.75 54.78 55.04 54.25 59.31 64.67 66.65 66.08 66.01 65.06 62.47 60.24 55.35 55.30 55.67 55.63 55.33 55.72 54.69 54.65 54.02 54.75 93.81 96.22 96.30 94.04 89.47 90.09 89.45 89.34 90.10 89.43 89.52 89.76 89.58 90.07 89.82 89.38 89.60 89.68 90.19 90.20 93.83 54.63 54.96 54.08 59.34 64.81 67.23 67.27 66.18 65.20 62.68 59.73 55.85 55.21 97.18 96.79 96.79 96.91 97.43 96.91 81.91 80.68 81.30 81.09 80.77 81.44 80.91 82.97 84.09 84.66 87.78 88.74 87.51 84.12 81.05 85.83 83.22 81.57 80.67 81.52 81.91 96.48 97.64 98.98 98.52 102.17 103.31 104.10 107.02 107.29 104.92 99.97 97.19 97.19 96.53 96.78 96.83 96.48 96.48 96.62 97.06 96.50 81.95 80.71 81.37 81.11 80.83 81.51 80.94 83.05 84.12 84.67 87.73 88.63 87.34 83.90 81.02 80.69 81.36 81.56 80.70 81.62 81.95 96.22 97.41 98.55 98.60 102.13 103.15 105.08 107.89 108.04 105.51 100.41 97.00 96.87 96.25 96.57 96.53 96.22 96.22 96.36 96.74 96.22 81.98 80.73 81.43 81.12 80.87 81.57 80.96 83.10 84.13 84.62 87.62 88.47 87.13 97.18 96.79 96.79 96.91 97.43 96.91 99.58 99.37 100.90 81.09 80.77 81.44 80.91 82.97 84.09 84.66 87.78 88.74 87.51 84.12 81.05 98.39 97.84 98.49 99.71 100.47 99.57 96.48 97.64 98.98 98.52 102.17 103.31 104.10 107.02 107.29 104.92 99.97 97.19 97.19 96.53 96.78 96.83 96.48 96.48 96.62 97.06 96.50 99.55 101.08 102.76 81.11 80.83 81.51 80.94 83.05 84.12 84.67 87.73 88.63 87.34 83.90 81.02 80.69 81.36 98.29 99.29 99.97 99.56 96.22 97.41 98.55 98.60 102.13 103.15 105.08 107.89 108.04 105.51 100.41 97.00 96.87 96.25 96.57 96.53 96.22 96.22 96.36 96.74 96.22 100.41 102.62 104.33 81.12 80.87 81.57 80.96 83.10 84.13 84.62 87.62 88.47 87.13 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.80 1.80 1.80 1.80 1.81 1.80 1.85 1.84 1.87 1.50 1.50 1.51 1.50 1.54 1.56 1.57 1.63 1.65 1.62 1.56 1.50 1.83 1.82 1.83 1.85 1.86 1.85 1.79 1.81 1.84 1.83 1.90 1.92 1.93 1.99 1.99 1.95 1.86 1.80 1.80 1.79 1.80 1.80 1.79 1.79 1.79 1.80 1.79 1.85 1.88 1.91 1.51 1.50 1.51 1.50 1.54 1.56 1.57 1.63 1.64 1.62 1.56 1.50 1.50 1.51 1.82 1.84 1.86 1.85 1.79 1.81 1.83 1.83 1.90 1.91 1.95 2.00 2.00 1.96 1.86 1.80 1.80 1.79 1.79 1.79 1.79 1.79 1.79 1.80 1.79 1.86 1.90 1.94 1.51 1.50 1.51 1.50 1.54 1.56 1.57 1.63 1.64 1.62 53.78 53.78 53.78 53.78 53.78 53.78 95.28 94.07 92.08 69.07 62.74 54.54 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 96.47 96.41 96.27 95.95 95.28 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.31 94.26 92.57 69.19 63.52 55.08 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 96.15 96.07 95.84 95.31 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.32 94.46 92.86 69.16 64.07 54.96 53.78 53.78 53.78 53.78 53.78 53.78 53.78 Vb (kV) Vc (kV) V Max (kV) 87.76 87.76 87.76 87.77 87.77 87.77 53.78 53.78 53.78 62.52 63.05 64.03 65.82 62.47 57.54 54.47 54.33 53.90 53.82 53.82 53.83 53.82 53.78 53.78 53.78 53.78 53.78 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 88.52 53.78 53.78 53.78 63.03 64.51 65.22 65.30 64.18 58.52 54.67 54.28 53.81 53.83 53.83 53.83 53.82 53.80 53.78 53.78 53.78 53.78 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.09 89.10 89.10 89.10 53.78 53.78 53.78 63.11 65.11 65.46 65.89 65.88 59.50 55.75 53.96 53.81 53.82 96.52 96.52 96.52 96.52 96.52 96.52 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 81.30 80.49 80.49 80.49 80.49 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 80.53 80.53 80.53 80.53 80.53 80.53 80.53 80.53 80.53 80.53 80.52 80.52 80.52 80.52 80.52 80.52 80.52 80.52 80.53 80.53 80.53 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 80.55 80.55 80.55 80.56 80.56 80.56 80.56 80.55 80.55 80.55 80.56 80.58 80.59 96.52 96.52 96.52 96.52 96.52 96.52 95.28 94.07 92.08 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 80.49 96.47 96.41 96.27 95.95 95.28 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 96.21 95.31 94.26 92.57 80.53 80.53 80.53 80.53 80.53 80.53 80.53 80.52 80.52 80.52 80.52 80.52 80.52 80.52 96.15 96.07 95.84 95.31 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.95 95.32 94.46 92.86 80.56 80.56 80.56 80.56 80.55 80.55 80.55 80.56 80.58 80.59 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.79 1.79 1.79 1.79 1.79 1.79 1.77 1.75 1.71 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.79 1.79 1.79 1.78 1.77 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.77 1.75 1.72 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.78 1.78 1.78 1.77 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.77 1.75 1.72 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.50 1.50 53.78 53.78 53.78 53.78 53.78 53.78 95.25 93.97 91.83 64.02 56.80 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 96.45 96.39 96.24 95.92 95.24 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.29 94.22 92.30 63.77 58.42 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 96.13 96.04 95.81 95.29 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.28 94.36 92.64 63.61 59.56 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 87.74 87.74 87.74 87.75 87.75 87.75 53.77 53.77 53.77 57.19 54.97 61.67 58.87 56.75 55.25 54.56 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.50 88.51 88.51 88.51 53.77 53.77 53.77 57.73 55.03 60.96 60.08 57.34 54.95 54.67 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.07 89.08 89.08 89.08 53.77 53.77 53.77 58.05 55.83 60.51 61.77 57.04 55.34 54.23 53.77 53.77 53.77 96.50 96.50 96.50 96.50 96.50 96.50 80.48 80.48 80.48 80.48 80.48 80.48 80.48 80.48 80.48 80.48 80.47 80.47 80.47 80.47 80.47 80.47 80.76 80.47 80.48 80.48 80.48 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 80.52 80.51 80.51 80.52 80.52 80.52 80.52 80.52 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.52 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 80.54 80.54 80.54 80.55 80.55 80.54 80.54 80.54 80.54 80.54 80.54 80.54 80.54 96.50 96.50 96.50 96.50 96.50 96.50 95.25 93.97 91.83 80.48 80.48 80.48 80.48 80.48 80.48 80.48 80.47 80.47 80.47 80.47 80.47 80.47 96.45 96.39 96.24 95.92 95.24 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 96.19 95.29 94.22 92.30 80.52 80.52 80.52 80.52 80.52 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 80.51 96.13 96.04 95.81 95.29 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.93 95.28 94.36 92.64 80.55 80.55 80.54 80.54 80.54 80.54 80.54 80.54 80.54 80.54 1.79 1.79 1.79 1.79 1.79 1.79 1.77 1.74 1.70 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.79 1.79 1.79 1.78 1.77 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.77 1.75 1.71 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.78 1.78 1.78 1.77 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.77 1.75 1.72 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 45 45 45 45 45 45 45 45 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 550 550 550 550 550 550 550 550 550 550 550 54.38 54.39 54.15 54.43 56.71 98.95 99.47 100.42 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 54.00 53.98 53.98 53.98 101.25 104.00 105.69 73.40 69.42 65.26 63.60 60.41 59.78 58.45 56.60 54.61 54.33 54.26 54.25 54.40 54.58 56.86 58.71 98.98 101.26 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 53.97 62.02 111.96 73.40 72.82 70.20 65.56 64.25 61.56 60.33 59.23 57.15 55.62 55.35 54.98 55.01 55.40 55.62 57.45 59.43 60.40 62.00 54.35 54.35 54.35 54.35 54.35 54.35 54.35 54.35 54.35 54.35 54.35 54.98 54.98 55.30 56.19 59.62 54.48 54.02 54.59 94.66 97.09 97.19 94.91 90.30 90.52 89.78 89.83 90.54 89.86 89.93 90.13 90.13 90.53 90.17 89.82 90.10 90.15 90.66 90.59 94.68 54.51 54.90 53.98 59.38 64.88 67.79 68.11 66.55 65.25 62.80 59.55 56.40 55.25 54.88 54.91 55.21 57.51 59.80 63.21 54.02 54.48 97.65 99.85 99.66 97.02 92.36 92.40 91.70 92.22 92.54 91.70 91.70 91.97 92.79 92.63 91.80 92.36 92.44 92.24 92.79 93.12 97.67 70.47 54.91 58.29 59.89 65.29 68.78 70.36 70.32 68.27 64.99 61.08 58.01 57.13 55.05 55.11 57.27 58.32 61.57 65.41 68.72 70.47 98.13 101.68 103.84 103.51 100.64 95.30 93.12 94.40 95.24 94.50 93.45 83.65 81.00 80.72 81.43 81.54 80.72 81.69 81.98 95.99 97.19 98.18 98.66 102.10 103.02 105.77 108.49 108.52 105.88 100.64 96.83 96.60 96.00 96.39 96.28 95.99 95.99 96.14 96.46 95.99 82.01 80.75 81.47 81.13 80.91 81.61 80.98 83.14 84.13 84.54 87.49 88.30 86.92 83.40 80.97 80.74 81.49 81.53 80.74 81.76 82.01 95.65 96.43 96.31 99.58 102.56 103.06 106.47 108.69 108.22 105.08 99.36 96.05 95.24 94.83 95.45 94.98 94.83 94.83 94.85 94.86 95.67 82.18 80.81 81.64 81.13 81.03 81.87 81.18 83.11 83.92 83.73 86.42 86.98 86.26 84.61 80.88 80.84 81.86 81.55 80.84 82.13 82.18 96.32 97.42 97.03 102.03 104.79 105.01 103.95 108.32 110.02 109.01 105.40 83.65 81.00 80.72 81.43 81.54 98.95 99.47 100.42 95.99 97.19 98.18 98.66 102.10 103.02 105.77 108.49 108.52 105.88 100.64 96.83 96.60 96.00 96.39 96.28 95.99 95.99 96.14 96.46 95.99 101.25 104.00 105.69 81.13 80.91 81.61 80.98 83.14 84.13 84.54 87.49 88.30 86.92 83.40 80.97 80.74 81.49 81.53 80.74 98.98 101.26 97.65 99.85 99.66 99.58 102.56 103.06 106.47 108.69 108.22 105.08 99.36 96.05 95.24 94.83 95.45 94.98 94.83 94.83 94.85 94.86 97.67 82.18 111.96 81.64 81.13 81.03 81.87 81.18 83.11 83.92 83.73 86.42 86.98 86.26 84.61 80.88 80.84 81.86 81.55 80.84 82.13 82.18 98.13 101.68 103.84 103.51 104.79 105.01 103.95 108.32 110.02 109.01 105.40 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.55 1.50 1.50 1.51 1.51 1.84 1.85 1.86 1.78 1.80 1.82 1.83 1.89 1.91 1.96 2.01 2.01 1.96 1.87 1.80 1.79 1.78 1.79 1.79 1.78 1.78 1.78 1.79 1.78 1.88 1.93 1.96 1.51 1.50 1.51 1.50 1.54 1.56 1.57 1.62 1.64 1.61 1.55 1.50 1.50 1.51 1.51 1.50 1.84 1.88 1.81 1.85 1.85 1.85 1.90 1.91 1.98 2.02 2.01 1.95 1.84 1.78 1.77 1.76 1.77 1.76 1.76 1.76 1.76 1.76 1.81 1.52 2.08 1.51 1.51 1.50 1.52 1.51 1.54 1.56 1.55 1.60 1.61 1.60 1.57 1.50 1.50 1.52 1.51 1.50 1.52 1.53 1.82 1.89 1.93 1.92 1.94 1.95 1.93 2.01 2.04 2.02 1.96 53.78 53.78 53.78 53.78 53.78 53.78 95.69 95.32 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.30 94.63 93.17 69.14 64.01 55.46 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.55 95.29 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 94.55 94.55 68.86 64.49 57.41 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 Vb (kV) Vc (kV) V Max (kV) 53.82 53.82 53.82 53.81 53.90 56.09 53.78 53.78 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.54 89.55 89.55 89.55 53.78 53.78 53.78 63.15 65.66 66.14 66.53 66.07 60.80 56.27 53.81 53.82 53.81 53.80 53.81 53.81 53.84 53.78 56.85 53.78 53.78 91.47 91.60 91.67 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.46 91.46 91.50 69.52 53.78 53.78 63.36 67.09 69.62 70.71 69.31 66.81 62.08 53.97 53.78 53.78 53.78 53.78 53.78 53.78 54.54 62.61 67.35 69.53 92.89 96.68 101.88 104.57 104.68 102.20 97.21 92.87 92.87 92.87 92.87 80.55 80.55 80.55 80.55 80.55 80.55 80.55 80.55 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 80.57 80.57 80.57 80.58 80.58 80.58 80.57 80.57 80.57 80.57 80.58 80.64 80.72 80.57 80.57 80.57 80.57 80.57 80.57 80.57 80.57 94.57 94.57 94.57 94.57 94.57 94.57 94.63 94.84 95.06 95.04 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.76 81.82 82.02 80.97 80.64 80.63 80.64 80.64 80.64 80.64 93.44 93.44 93.44 93.44 93.44 93.44 94.25 101.49 106.22 108.34 107.79 80.55 80.55 80.55 80.55 80.55 80.55 95.69 95.32 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.73 95.30 94.63 93.17 80.58 80.58 80.58 80.57 80.57 80.57 80.57 80.58 80.64 80.72 80.57 80.57 80.57 80.57 80.57 80.57 95.55 95.29 94.57 94.57 94.57 94.57 94.57 94.57 94.63 94.84 95.06 95.04 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 80.64 94.55 94.55 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.76 81.82 82.02 80.97 80.64 80.63 80.64 80.64 80.64 80.64 93.44 96.68 101.88 104.57 104.68 102.20 97.21 101.49 106.22 108.34 107.79 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.49 1.49 1.49 1.49 1.49 1.49 1.78 1.77 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.77 1.76 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.77 1.77 1.75 1.75 1.75 1.75 1.75 1.75 1.76 1.76 1.76 1.76 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.50 1.75 1.75 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.52 1.52 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.73 1.79 1.89 1.94 1.94 1.90 1.80 1.88 1.97 2.01 2.00 53.78 53.78 53.78 53.78 53.78 53.78 95.68 95.27 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.22 94.45 92.88 63.47 59.56 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 53.78 95.53 95.22 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 94.55 94.55 68.86 64.49 57.41 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.79 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.77 53.77 53.77 53.77 53.77 54.23 53.77 53.77 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.52 89.53 89.53 89.53 53.77 53.77 53.77 58.19 56.90 60.69 63.15 58.57 55.80 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 53.77 91.47 91.60 91.67 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.45 91.46 91.46 91.50 69.52 53.78 53.78 63.36 67.09 69.62 70.71 69.31 66.81 62.08 53.97 53.78 53.78 53.78 53.78 53.78 53.78 54.54 62.61 67.35 69.53 92.89 96.68 101.88 104.57 104.68 102.20 97.21 92.87 92.87 92.87 92.87 80.54 80.54 80.54 80.54 80.54 80.54 80.54 80.54 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 80.56 80.56 80.56 80.57 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 94.57 94.57 94.57 94.57 94.57 94.57 94.63 94.84 95.06 95.04 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.76 81.82 82.02 80.97 80.64 80.63 80.64 80.64 80.64 80.64 93.44 93.44 93.44 93.44 93.44 93.44 94.25 101.49 106.22 108.34 107.79 80.54 80.54 80.54 80.54 80.54 80.54 95.68 95.27 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.71 95.22 94.45 92.88 80.57 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 80.56 95.53 95.22 94.57 94.57 94.57 94.57 94.57 94.57 94.63 94.84 95.06 95.04 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 94.57 80.64 94.55 94.55 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.64 80.76 81.82 82.02 80.97 80.64 80.63 80.64 80.64 80.64 80.64 93.44 96.68 101.88 104.57 104.68 102.20 97.21 101.49 106.22 108.34 107.79 1.49 1.49 1.49 1.49 1.49 1.49 1.78 1.77 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.77 1.75 1.72 1.50 1.50 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.77 1.77 1.75 1.75 1.75 1.75 1.75 1.75 1.76 1.76 1.76 1.76 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.50 1.75 1.75 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.52 1.52 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.73 1.79 1.89 1.94 1.94 1.90 1.80 1.88 1.97 2.01 2.00 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 54.35 54.35 54.35 54.35 54.35 54.37 54.37 54.37 54.37 54.37 62.16 64.66 69.70 70.59 69.94 67.80 64.37 61.72 60.60 59.53 57.48 56.59 56.51 56.21 56.24 56.54 56.55 57.79 59.74 60.66 62.14 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.66 54.68 54.68 54.68 54.68 54.68 54.68 63.65 65.85 68.48 69.91 69.93 68.37 65.48 63.26 61.38 60.37 58.35 57.08 56.98 56.67 56.70 57.02 57.05 58.64 60.57 61.43 63.63 97.40 97.40 97.40 97.40 97.40 97.40 97.40 97.40 97.43 97.43 97.43 97.43 97.43 97.43 97.43 97.43 97.43 97.43 97.43 97.43 97.43 73.09 72.33 66.01 68.64 70.25 70.24 72.48 73.05 75.72 95.53 96.56 95.52 93.38 94.87 94.67 94.02 94.92 94.67 98.15 67.41 68.12 58.46 62.37 65.54 67.56 68.09 67.21 65.12 61.71 58.04 58.27 57.76 57.16 57.20 57.84 58.30 57.96 62.14 65.45 67.41 98.36 102.41 104.78 104.55 101.82 96.61 93.26 94.66 95.76 95.00 93.68 96.18 97.12 96.01 93.63 95.26 94.97 94.18 95.08 94.92 98.38 65.63 66.89 58.66 63.15 65.55 66.98 66.79 65.36 62.46 58.65 56.36 55.83 55.01 54.53 54.54 55.09 55.93 56.37 59.28 62.96 65.63 98.53 102.70 105.26 105.19 102.56 97.49 96.52 96.52 96.53 96.54 96.54 96.86 97.74 96.63 96.54 96.54 96.54 96.54 96.54 96.54 98.55 72.33 69.34 61.15 64.63 65.35 65.67 69.83 72.61 74.00 99.22 94.78 93.69 94.50 94.16 93.69 93.69 93.69 93.86 96.33 82.43 80.84 81.74 81.10 81.15 82.23 81.54 82.77 83.84 83.73 85.20 87.21 87.65 85.98 82.19 81.50 82.34 81.82 81.25 82.54 82.43 96.39 97.72 97.43 102.21 104.97 105.15 105.05 109.41 111.16 110.18 106.47 100.14 94.89 93.57 94.37 94.14 93.61 93.57 93.57 93.83 96.40 82.48 80.84 81.75 81.11 81.17 82.27 81.59 82.77 83.94 83.84 85.14 87.31 87.80 86.11 82.31 81.59 82.42 81.88 81.31 82.61 82.48 102.73 102.73 102.73 102.73 104.54 104.70 105.71 110.17 111.94 111.04 107.40 102.73 102.73 102.73 102.73 102.73 102.73 102.73 102.73 102.73 102.73 82.71 80.84 81.97 81.32 80.97 82.20 81.53 82.54 83.81 99.22 96.56 95.52 94.50 94.87 94.67 94.02 94.92 94.67 98.15 82.43 80.84 81.74 81.10 81.15 82.23 81.54 82.77 83.84 83.73 85.20 87.21 87.65 85.98 82.19 81.50 82.34 81.82 81.25 82.54 82.43 98.36 102.41 104.78 104.55 104.97 105.15 105.05 109.41 111.16 110.18 106.47 100.14 97.12 96.01 94.37 95.26 94.97 94.18 95.08 94.92 98.38 82.48 80.84 81.75 81.11 81.17 82.27 81.59 82.77 83.94 83.84 85.14 87.31 87.80 86.11 82.31 81.59 82.42 81.88 81.31 82.61 82.48 102.73 102.73 105.26 105.19 104.54 104.70 105.71 110.17 111.94 111.04 107.40 102.73 102.73 102.73 102.73 102.73 102.73 102.73 102.73 102.73 102.73 82.71 80.84 81.97 81.32 80.97 82.20 81.53 82.54 83.81 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.84 1.79 1.77 1.75 1.76 1.76 1.74 1.76 1.76 1.82 1.53 1.50 1.52 1.51 1.51 1.53 1.51 1.54 1.56 1.55 1.58 1.62 1.63 1.60 1.53 1.51 1.53 1.52 1.51 1.53 1.53 1.83 1.90 1.94 1.94 1.95 1.95 1.95 2.03 2.06 2.04 1.98 1.86 1.80 1.78 1.75 1.77 1.76 1.75 1.76 1.76 1.83 1.53 1.50 1.52 1.51 1.51 1.53 1.51 1.54 1.56 1.56 1.58 1.62 1.63 1.60 1.53 1.51 1.53 1.52 1.51 1.53 1.53 1.91 1.91 1.95 1.95 1.94 1.94 1.96 2.04 2.08 2.06 1.99 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.53 1.50 1.52 1.51 1.50 1.53 1.51 1.53 1.56 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 69.19 67.26 63.68 59.05 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 55.35 67.59 66.43 63.69 60.17 54.35 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.64 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.63 87.63 64.76 61.71 62.52 64.25 64.29 63.28 62.10 65.11 67.75 Vb (kV) Vc (kV) V Max (kV) 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.91 71.03 71.75 59.42 65.00 68.67 71.17 71.79 70.85 68.30 63.91 59.32 53.83 53.78 53.78 53.78 53.78 53.91 59.79 64.88 68.77 71.05 93.02 100.02 105.79 108.94 109.40 107.17 102.29 94.89 93.00 93.00 93.00 93.00 93.00 93.00 93.00 93.00 93.00 93.01 93.01 93.01 93.04 69.10 70.50 61.01 65.84 68.65 70.23 70.46 68.73 65.85 61.32 55.87 53.88 53.78 53.79 53.79 53.79 53.93 56.81 61.53 66.40 69.08 94.54 103.74 110.38 114.29 115.37 113.61 109.05 101.80 93.17 93.17 93.17 93.17 93.17 93.17 93.17 93.17 93.17 93.17 93.17 93.17 94.59 64.93 64.86 66.09 68.05 68.07 67.13 64.21 65.19 67.16 104.58 98.79 93.44 93.44 93.44 93.44 93.44 93.44 93.44 93.44 80.67 80.66 80.67 80.67 80.67 80.67 80.67 80.67 80.66 80.66 80.73 85.82 88.82 89.64 88.25 84.68 80.66 80.66 80.66 80.66 80.67 93.32 93.32 93.32 93.32 93.32 93.32 99.25 106.48 111.08 112.95 112.03 108.36 102.01 93.32 93.32 93.32 93.32 93.32 93.32 93.32 93.32 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.66 81.39 86.51 89.51 90.31 88.89 85.27 80.66 80.66 80.66 80.67 80.67 99.57 99.57 99.57 99.57 99.57 99.57 105.84 113.23 117.84 119.53 118.29 114.12 107.15 99.52 99.52 99.52 99.52 99.52 99.52 99.52 99.52 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 104.58 98.79 93.44 93.44 93.44 93.44 93.44 93.44 93.44 93.44 80.67 80.66 80.67 80.67 80.67 80.67 80.67 80.67 80.66 80.66 80.73 85.82 88.82 89.64 88.25 84.68 80.66 80.66 80.66 80.66 80.67 93.32 100.02 105.79 108.94 109.40 107.17 102.29 106.48 111.08 112.95 112.03 108.36 102.01 93.32 93.32 93.32 93.32 93.32 93.32 93.32 93.32 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.66 81.39 86.51 89.51 90.31 88.89 85.27 80.66 80.66 80.66 80.67 80.67 99.57 103.74 110.38 114.29 115.37 113.61 109.05 113.23 117.84 119.53 118.29 114.12 107.15 99.52 99.52 99.52 99.52 99.52 99.52 99.52 99.52 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.94 1.83 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.59 1.65 1.66 1.64 1.57 1.50 1.50 1.50 1.50 1.50 1.73 1.86 1.96 2.02 2.03 1.99 1.90 1.98 2.06 2.10 2.08 2.01 1.89 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.51 1.61 1.66 1.68 1.65 1.58 1.50 1.50 1.50 1.50 1.50 1.85 1.93 2.05 2.12 2.14 2.11 2.02 2.10 2.19 2.22 2.19 2.12 1.99 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 69.19 67.26 63.68 59.05 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.83 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 55.35 67.59 66.43 63.69 60.17 54.35 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 53.87 81.33 81.33 81.33 81.33 81.32 81.32 81.32 81.32 81.32 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 81.33 64.03 61.26 57.33 58.77 58.53 58.38 61.61 64.35 66.68 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.87 92.91 71.03 71.75 59.42 65.00 68.67 71.17 71.79 70.85 68.30 63.91 59.32 53.83 53.78 53.78 53.78 53.78 53.91 59.79 64.88 68.77 71.05 93.02 100.02 105.79 108.94 109.40 107.17 102.29 94.89 93.00 93.00 93.00 93.00 93.00 93.00 93.00 93.00 93.00 93.01 93.01 93.01 93.04 69.10 70.50 61.01 65.84 68.65 70.23 70.46 68.73 65.85 61.32 55.87 53.88 53.78 53.79 53.79 53.79 53.93 56.81 61.53 66.40 69.08 93.14 99.42 105.53 109.02 109.85 108.15 103.78 96.86 93.14 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 93.15 62.60 60.83 61.24 62.89 62.62 61.59 61.07 62.81 64.30 104.58 98.79 93.44 93.44 93.44 93.44 93.44 93.44 93.44 93.44 80.67 80.66 80.67 80.67 80.67 80.67 80.67 80.67 80.66 80.66 80.73 85.82 88.82 89.64 88.25 84.68 80.66 80.66 80.66 80.66 80.67 93.32 93.32 93.32 93.32 93.32 93.32 99.25 106.48 111.08 112.95 112.03 108.36 102.01 93.32 93.32 93.32 93.32 93.32 93.32 93.32 93.32 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.66 81.39 86.51 89.51 90.31 88.89 85.27 80.66 80.66 80.66 80.67 80.67 97.38 97.38 97.38 97.38 97.38 97.38 98.18 105.90 111.02 113.40 112.99 109.79 103.89 97.32 97.32 97.32 97.32 97.32 97.32 97.32 97.32 80.66 80.66 80.66 80.66 80.66 80.66 80.66 80.66 80.66 104.58 98.79 93.44 93.44 93.44 93.44 93.44 93.44 93.44 93.44 80.67 80.66 80.67 80.67 80.67 80.67 80.67 80.67 80.66 80.66 80.73 85.82 88.82 89.64 88.25 84.68 80.66 80.66 80.66 80.66 80.67 93.32 100.02 105.79 108.94 109.40 107.17 102.29 106.48 111.08 112.95 112.03 108.36 102.01 93.32 93.32 93.32 93.32 93.32 93.32 93.32 93.32 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.67 80.66 81.39 86.51 89.51 90.31 88.89 85.27 80.66 80.66 80.66 80.67 80.67 97.38 99.42 105.53 109.02 109.85 108.15 103.78 105.90 111.02 113.40 112.99 109.79 103.89 97.32 97.32 97.32 97.32 97.32 97.32 97.32 97.32 80.66 80.66 80.66 80.66 80.66 80.66 80.66 80.66 80.66 1.94 1.83 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.59 1.65 1.66 1.64 1.57 1.50 1.50 1.50 1.50 1.50 1.73 1.86 1.96 2.02 2.03 1.99 1.90 1.98 2.06 2.10 2.08 2.01 1.89 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.51 1.61 1.66 1.68 1.65 1.58 1.50 1.50 1.50 1.50 1.50 1.81 1.84 1.96 2.02 2.04 2.01 1.93 1.97 2.06 2.10 2.10 2.04 1.93 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 Simulation 2 Variables Line Length=100km Simulation StartDelay (s) Type of Fault Fault Duration (s) NER Size (Ohm) Va (kV) Vb (kV) Vc (kV) V Max (kV) 619 620 621 622 623 624 625 626 627 628 629 630 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 77.17 77.09 78.01 78.85 78.96 78.98 78.80 77.86 77.19 77.08 75.42 73.07 75.70 77.78 78.61 78.55 78.23 78.27 78.59 78.58 77.61 75.32 73.90 72.33 83.77 84.87 87.21 87.76 86.14 82.39 81.73 82.56 82.01 81.49 82.85 82.71 83.77 84.87 87.21 87.76 86.14 82.39 81.73 82.56 82.01 81.49 82.85 82.71 Line Length=10km Ratio Vmax/Vnom Va (kV) 1.55 1.57 1.62 1.63 1.60 1.53 1.52 1.53 1.52 1.51 1.54 1.53 69.88 71.61 72.81 73.52 73.84 73.81 73.44 72.65 71.40 69.70 67.43 64.74 Vb (kV) Vc (kV) V Max (kV) 68.76 70.05 70.94 71.47 71.72 71.69 71.42 70.83 69.89 68.63 66.93 64.91 80.67 82.31 87.60 90.73 91.64 90.29 86.71 81.00 80.67 80.67 80.67 80.67 80.67 82.31 87.60 90.73 91.64 90.29 86.71 81.00 80.67 80.67 80.67 80.67 Line Length=0.2km Ratio Vmax/Vnom Va (kV) Vb (kV) Vc (kV) V Max (kV) Ratio Vmax/Vnom 1.50 1.53 1.63 1.68 1.70 1.68 1.61 1.50 1.50 1.50 1.50 1.50 68.52 69.95 70.90 71.42 71.64 71.62 71.37 70.78 69.78 68.36 66.40 64.01 65.46 66.38 66.97 67.30 67.44 67.43 67.27 66.90 66.26 65.36 64.12 62.59 80.65 80.65 85.07 88.37 89.50 88.43 85.18 80.65 80.65 80.65 80.66 80.66 80.65 80.65 85.07 88.37 89.50 88.43 85.18 80.65 80.65 80.65 80.66 80.66 1.50 1.50 1.58 1.64 1.66 1.64 1.58 1.50 1.50 1.50 1.50 1.50 Simulation 3 Variables Simulation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 Start-Delay (s) 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 Va (kV) 71.67 71.66 71.65 71.66 71.68 71.72 71.78 71.86 71.95 72.05 72.16 72.27 69.77 69.76 69.75 69.75 69.75 69.75 69.75 69.75 69.76 120.95 120.87 120.82 120.68 120.65 120.64 120.66 120.71 120.78 120.87 120.98 121.08 121.17 121.23 121.27 121.27 121.24 121.18 121.10 121.01 120.93 74.42 74.42 74.42 74.42 74.42 74.43 74.44 74.46 74.48 74.50 74.53 74.55 74.57 74.59 74.60 74.49 74.50 74.50 74.50 74.50 74.49 121.36 121.30 121.25 121.70 121.68 121.67 121.67 121.68 121.70 121.73 121.77 121.81 121.83 121.83 121.81 121.76 121.70 121.61 121.52 121.43 121.34 75.92 75.92 75.92 75.92 75.93 75.93 75.94 75.95 75.95 75.96 75.97 75.97 75.98 75.99 75.99 75.99 75.99 75.99 75.99 75.99 75.99 122.11 122.06 122.03 122.43 122.41 122.40 122.40 122.40 122.42 122.44 122.46 122.49 122.50 122.49 122.47 122.43 122.37 122.30 122.22 122.15 122.08 77.56 77.56 77.56 77.55 Vb (kV) 155.36 156.54 157.70 158.66 159.24 159.29 158.74 157.55 157.57 158.18 158.29 157.94 157.21 156.26 155.23 154.32 153.68 153.44 153.66 154.32 155.31 97.19 97.30 97.38 96.55 96.56 96.57 96.57 96.57 96.55 96.52 96.48 96.45 96.43 96.43 96.47 96.53 96.63 96.75 96.88 97.02 97.14 144.97 146.03 147.12 148.05 148.67 148.85 148.50 147.60 147.33 147.82 147.88 147.55 146.90 146.04 145.11 144.27 143.65 143.39 143.53 144.07 144.94 97.40 97.49 97.55 96.95 96.96 96.97 96.97 96.95 96.92 96.89 96.85 96.82 96.80 96.80 96.82 96.87 96.95 97.04 97.15 97.26 97.36 137.11 138.06 139.03 139.89 140.48 140.67 140.40 139.63 139.22 139.64 139.70 139.43 138.87 138.13 137.32 136.57 136.02 135.77 135.87 136.33 137.09 97.59 97.65 97.70 97.21 97.22 97.23 97.23 97.21 97.19 97.16 97.14 97.11 97.10 97.10 97.12 97.17 97.23 97.30 97.39 97.47 97.54 131.01 131.84 132.71 133.47 Vc (kV) 175.81 177.79 180.06 182.38 184.53 186.26 187.40 187.83 187.48 186.37 184.59 182.31 179.74 177.15 175.21 174.24 173.53 173.24 173.53 174.43 175.93 133.85 132.54 131.19 129.94 129.07 128.67 128.73 129.28 130.01 130.78 131.31 131.34 130.78 129.43 131.53 133.36 134.64 135.31 135.35 134.80 133.80 175.35 176.95 178.82 180.77 182.57 184.03 184.97 185.26 184.86 183.76 182.04 179.85 177.37 175.90 175.12 174.34 173.73 173.45 173.61 174.29 175.47 133.78 132.42 131.00 129.71 128.81 128.37 128.45 129.02 129.79 130.66 131.25 131.42 130.94 129.83 131.97 133.70 134.90 135.48 135.43 134.81 133.74 175.90 177.25 178.85 180.53 182.09 183.34 184.14 184.35 183.93 182.86 181.23 179.14 176.94 176.44 175.80 175.15 174.62 174.37 174.49 175.04 176.02 133.92 132.56 131.14 129.86 128.99 128.56 128.68 129.27 130.06 130.97 131.58 131.79 131.33 130.33 132.39 134.05 135.18 135.71 135.62 134.97 133.88 177.29 178.46 179.85 181.31 V Max (kV) 175.81 177.79 180.06 182.38 184.53 186.26 187.40 187.83 187.48 186.37 184.59 182.31 179.74 177.15 175.21 174.24 173.53 173.24 173.53 174.43 175.93 133.85 132.54 131.19 129.94 129.07 128.67 128.73 129.28 130.01 130.78 131.31 131.34 130.78 129.43 131.53 133.36 134.64 135.31 135.35 134.80 133.80 175.35 176.95 178.82 180.77 182.57 184.03 184.97 185.26 184.86 183.76 182.04 179.85 177.37 175.90 175.12 174.34 173.73 173.45 173.61 174.29 175.47 133.78 132.42 131.00 129.71 128.81 128.37 128.45 129.02 129.79 130.66 131.25 131.42 130.94 129.83 131.97 133.70 134.90 135.48 135.43 134.81 133.74 175.90 177.25 178.85 180.53 182.09 183.34 184.14 184.35 183.93 182.86 181.23 179.14 176.94 176.44 175.80 175.15 174.62 174.37 174.49 175.04 176.02 133.92 132.56 131.14 129.86 128.99 128.56 128.68 129.27 130.06 130.97 131.58 131.79 131.33 130.33 132.39 134.05 135.18 135.71 135.62 134.97 133.88 177.29 178.46 179.85 181.31 Line Length=10km Ratio Vmax/Vnom 3.26 3.30 3.34 3.38 3.42 3.46 3.48 3.49 3.48 3.46 3.43 3.38 3.34 3.29 3.25 3.23 3.22 3.21 3.22 3.24 3.26 2.48 2.46 2.43 2.41 2.40 2.39 2.39 2.40 2.41 2.43 2.44 2.44 2.43 2.40 2.44 2.47 2.50 2.51 2.51 2.50 2.48 3.25 3.28 3.32 3.35 3.39 3.41 3.43 3.44 3.43 3.41 3.38 3.34 3.29 3.26 3.25 3.24 3.22 3.22 3.22 3.23 3.26 2.48 2.46 2.43 2.41 2.39 2.38 2.38 2.39 2.41 2.42 2.44 2.44 2.43 2.41 2.45 2.48 2.50 2.51 2.51 2.50 2.48 3.26 3.29 3.32 3.35 3.38 3.40 3.42 3.42 3.41 3.39 3.36 3.32 3.28 3.27 3.26 3.25 3.24 3.24 3.24 3.25 3.27 2.49 2.46 2.43 2.41 2.39 2.39 2.39 2.40 2.41 2.43 2.44 2.45 2.44 2.42 2.46 2.49 2.51 2.52 2.52 2.50 2.48 3.29 3.31 3.34 3.36 Va (kV) 82.91 82.54 82.13 81.71 81.32 80.98 80.67 81.11 81.74 82.29 82.71 82.97 83.12 83.18 83.22 83.27 83.31 83.32 83.27 83.11 82.84 104.46 104.58 110.25 110.32 110.33 97.73 97.97 98.30 98.70 99.12 99.56 100.00 100.48 101.00 101.58 102.19 102.81 103.37 103.82 104.15 104.37 78.28 78.29 78.29 78.30 78.29 78.29 78.28 78.27 78.26 78.25 78.24 78.24 78.23 78.23 78.23 78.22 78.22 78.22 78.22 78.23 78.23 90.26 90.33 123.49 123.49 123.47 90.00 90.00 89.99 89.98 89.95 89.93 89.91 89.89 89.88 89.89 89.91 89.94 89.99 90.03 90.09 90.15 72.21 72.21 72.23 72.22 72.22 72.22 72.21 72.21 72.21 72.21 72.21 72.21 72.21 72.20 72.20 72.20 72.20 72.20 72.20 72.20 72.20 89.95 90.02 90.10 127.87 89.69 89.70 89.70 89.69 89.68 89.67 89.66 89.64 89.63 89.63 89.63 89.64 89.66 89.69 89.73 89.78 89.84 66.72 66.72 66.71 66.71 Vb (kV) 74.72 75.17 75.69 76.22 76.74 77.77 81.03 83.22 84.21 83.99 82.61 80.22 77.07 74.44 74.25 74.10 73.99 73.96 74.05 74.26 74.61 104.73 104.77 99.19 99.07 98.90 108.40 108.20 107.96 107.68 107.39 107.12 106.85 106.61 106.37 106.10 105.78 105.41 105.00 104.78 104.76 104.76 66.73 65.32 65.32 65.33 65.34 68.42 72.20 75.29 77.49 78.72 78.95 78.25 76.79 74.83 72.81 71.23 70.49 70.40 70.16 69.09 66.82 91.01 90.99 67.80 67.83 67.88 91.40 91.31 91.23 91.17 91.12 91.09 91.08 91.08 91.08 91.09 91.09 91.09 91.07 91.06 91.05 91.03 70.88 69.72 69.76 69.79 69.86 72.21 75.31 77.98 79.98 81.17 81.51 81.02 79.86 78.25 76.55 75.20 74.55 74.46 74.27 73.28 71.07 80.21 80.34 80.48 71.00 80.31 80.23 80.15 80.08 80.01 79.94 79.89 79.84 79.81 79.79 79.79 79.81 79.85 79.90 79.98 80.07 80.19 77.33 77.42 77.60 77.73 Vc (kV) 81.53 81.61 81.68 81.74 83.63 84.94 85.02 83.82 81.75 81.71 81.68 81.68 81.67 81.66 81.64 81.61 81.59 81.59 81.61 81.65 81.72 97.01 96.84 100.47 100.36 100.25 99.59 99.60 99.62 99.65 99.67 99.68 99.64 99.56 99.40 99.16 98.84 98.48 98.09 97.72 97.40 97.15 89.70 92.32 94.93 96.96 98.00 97.82 96.29 93.40 89.93 87.57 84.68 84.06 84.06 84.05 84.05 85.98 86.88 87.03 87.07 87.87 89.79 85.87 85.90 100.31 100.19 100.07 85.76 85.75 85.75 85.74 85.73 85.71 85.68 85.65 85.62 85.60 85.61 85.63 85.67 85.72 85.77 85.81 102.98 105.35 107.50 108.89 109.13 107.98 105.34 101.22 97.09 96.88 96.89 96.90 96.91 96.92 98.05 99.42 99.96 100.02 100.23 101.21 103.11 87.35 88.18 88.14 94.47 87.20 87.37 88.18 89.17 89.71 89.33 88.57 88.67 87.77 86.36 85.78 84.87 84.64 83.95 83.30 85.42 87.39 112.14 114.55 116.56 117.64 Ratio V Max (kV) Vmax/Vnom 82.91 1.54 82.54 1.53 82.13 1.52 81.74 1.52 83.63 1.55 84.94 1.58 85.02 1.58 83.82 1.56 84.21 1.56 83.99 1.56 82.71 1.53 82.97 1.54 83.12 1.54 83.18 1.54 83.22 1.54 83.27 1.55 83.31 1.55 83.32 1.55 83.27 1.55 83.11 1.54 82.84 1.54 104.73 1.94 104.77 1.94 110.25 2.05 110.32 2.05 110.33 2.05 108.40 2.01 108.20 2.01 107.96 2.00 107.68 2.00 107.39 1.99 107.12 1.99 106.85 1.98 106.61 1.98 106.37 1.97 106.10 1.97 105.78 1.96 105.41 1.96 105.00 1.95 104.78 1.94 104.76 1.94 104.76 1.94 89.70 1.66 92.32 1.71 94.93 1.76 96.96 1.80 98.00 1.82 97.82 1.82 96.29 1.79 93.40 1.73 89.93 1.67 87.57 1.62 84.68 1.57 84.06 1.56 84.06 1.56 84.05 1.56 84.05 1.56 85.98 1.60 86.88 1.61 87.03 1.62 87.07 1.62 87.87 1.63 89.79 1.67 91.01 1.69 90.99 1.69 123.49 2.29 123.49 2.29 123.47 2.29 91.40 1.70 91.31 1.69 91.23 1.69 91.17 1.69 91.12 1.69 91.09 1.69 91.08 1.69 91.08 1.69 91.08 1.69 91.09 1.69 91.09 1.69 91.09 1.69 91.07 1.69 91.06 1.69 91.05 1.69 91.03 1.69 102.98 1.91 105.35 1.95 107.50 1.99 108.89 2.02 109.13 2.03 107.98 2.00 105.34 1.95 101.22 1.88 97.09 1.80 96.88 1.80 96.89 1.80 96.90 1.80 96.91 1.80 96.92 1.80 98.05 1.82 99.42 1.84 99.96 1.85 100.02 1.86 100.23 1.86 101.21 1.88 103.11 1.91 89.95 1.67 90.02 1.67 90.10 1.67 127.87 2.37 89.69 1.66 89.70 1.66 89.70 1.66 89.69 1.66 89.71 1.66 89.67 1.66 89.66 1.66 89.64 1.66 89.63 1.66 89.63 1.66 89.63 1.66 89.64 1.66 89.66 1.66 89.69 1.66 89.73 1.67 89.78 1.67 89.84 1.67 112.14 2.08 114.55 2.13 116.56 2.16 117.64 2.18 Line Length=0.2km Va (kV) 93.04 95.63 97.73 98.96 99.04 97.81 88.48 93.10 96.52 98.51 98.96 98.09 96.28 93.96 91.48 89.25 87.74 87.40 88.36 90.38 92.97 91.97 90.21 92.11 110.92 90.46 90.25 89.83 95.35 100.24 104.26 107.24 108.81 108.32 104.82 97.59 87.45 87.98 91.19 92.77 92.99 92.10 87.36 87.36 87.36 87.36 87.29 87.30 87.30 87.30 87.30 87.30 87.31 87.31 87.31 87.31 87.31 87.31 87.31 87.31 87.31 87.31 87.31 134.23 132.61 130.13 126.76 122.54 117.57 80.33 79.92 79.99 80.49 81.21 81.90 82.39 82.62 82.59 82.32 134.49 134.96 135.21 135.02 134.19 74.41 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 74.42 135.76 133.97 131.25 127.57 96.36 94.34 91.53 88.14 84.45 80.83 77.64 75.18 73.60 72.89 72.95 73.83 75.57 78.18 81.48 85.16 135.72 68.76 68.76 68.76 68.76 Vb (kV) 79.91 81.66 83.01 83.64 83.36 82.03 76.14 78.07 80.89 82.89 83.94 83.92 82.89 81.18 79.24 77.53 76.41 76.16 76.84 78.25 80.04 97.99 93.17 94.04 108.72 110.97 110.27 108.84 107.00 105.16 103.75 103.08 103.30 104.37 106.01 107.84 109.41 110.03 109.09 106.60 102.83 98.02 69.22 69.22 69.21 69.20 69.27 69.28 69.29 69.29 69.28 69.27 69.26 69.26 69.26 69.26 69.27 69.27 69.27 69.27 69.27 69.28 69.28 90.84 88.48 84.58 79.32 73.87 70.31 87.30 87.51 86.52 84.59 82.07 79.45 77.29 76.11 76.24 77.63 91.51 91.94 92.18 91.94 90.86 70.98 69.61 69.77 69.88 69.84 69.59 69.58 69.60 71.36 73.33 74.92 75.90 76.25 76.01 75.39 74.70 74.27 74.20 74.05 73.13 71.02 65.64 66.69 68.40 70.46 87.72 86.62 84.37 85.26 85.92 85.46 84.18 82.51 80.98 80.12 80.22 81.24 82.83 84.46 85.62 85.89 65.48 80.44 80.45 80.39 80.45 Vc (kV) 74.66 75.88 78.96 81.58 83.46 84.39 82.04 83.67 84.36 84.07 82.74 80.44 77.43 75.20 74.53 73.79 73.28 73.17 73.46 74.01 74.55 75.77 74.07 72.96 84.33 73.58 72.76 71.78 73.68 74.64 74.71 74.68 78.43 87.33 95.48 100.85 101.85 98.77 93.37 87.10 80.69 75.71 87.42 87.16 88.35 89.88 90.96 91.15 90.19 88.22 90.17 91.62 92.37 92.42 91.90 91.09 90.36 90.07 90.20 90.28 89.85 88.76 87.43 85.09 86.76 87.96 88.20 86.84 85.33 80.36 81.24 81.78 81.54 80.23 77.97 79.89 81.14 81.53 80.99 79.57 79.01 80.99 83.04 84.97 102.08 103.54 105.37 106.83 107.36 106.62 104.42 103.54 103.91 103.83 103.28 102.42 102.08 102.10 102.05 101.98 101.96 102.08 101.95 101.97 102.10 93.72 94.81 94.50 92.60 85.40 86.00 87.22 88.58 89.43 89.28 87.83 86.40 87.64 88.03 87.46 85.93 84.32 84.83 84.84 84.39 93.65 111.22 113.57 115.87 117.43 Ratio V Max (kV) Vmax/Vnom 93.04 1.73 95.63 1.77 97.73 1.81 98.96 1.84 99.04 1.84 97.81 1.82 88.48 1.64 93.10 1.73 96.52 1.79 98.51 1.83 98.96 1.84 98.09 1.82 96.28 1.79 93.96 1.74 91.48 1.70 89.25 1.66 87.74 1.63 87.40 1.62 88.36 1.64 90.38 1.68 92.97 1.73 97.99 1.82 93.17 1.73 94.04 1.75 110.92 2.06 110.97 2.06 110.27 2.05 108.84 2.02 107.00 1.99 105.16 1.95 104.26 1.93 107.24 1.99 108.81 2.02 108.32 2.01 106.01 1.97 107.84 2.00 109.41 2.03 110.03 2.04 109.09 2.02 106.60 1.98 102.83 1.91 98.02 1.82 87.42 1.62 87.36 1.62 88.35 1.64 89.88 1.67 90.96 1.69 91.15 1.69 90.19 1.67 88.22 1.64 90.17 1.67 91.62 1.70 92.37 1.71 92.42 1.72 91.90 1.71 91.09 1.69 90.36 1.68 90.07 1.67 90.20 1.67 90.28 1.68 89.85 1.67 88.76 1.65 87.43 1.62 134.23 2.49 132.61 2.46 130.13 2.41 126.76 2.35 122.54 2.27 117.57 2.18 87.30 1.62 87.51 1.62 86.52 1.61 84.59 1.57 82.07 1.52 81.90 1.52 82.39 1.53 82.62 1.53 82.59 1.53 82.32 1.53 134.49 2.50 134.96 2.50 135.21 2.51 135.02 2.51 134.19 2.49 102.08 1.89 103.54 1.92 105.37 1.96 106.83 1.98 107.36 1.99 106.62 1.98 104.42 1.94 103.54 1.92 103.91 1.93 103.83 1.93 103.28 1.92 102.42 1.90 102.08 1.89 102.10 1.89 102.05 1.89 101.98 1.89 101.96 1.89 102.08 1.89 101.95 1.89 101.97 1.89 102.10 1.89 135.76 2.52 133.97 2.49 131.25 2.44 127.57 2.37 96.36 1.79 94.34 1.75 91.53 1.70 88.58 1.64 89.43 1.66 89.28 1.66 87.83 1.63 86.40 1.60 87.64 1.63 88.03 1.63 87.46 1.62 85.93 1.59 84.32 1.56 84.83 1.57 85.62 1.59 85.89 1.59 135.72 2.52 111.22 2.06 113.57 2.11 115.87 2.15 117.43 2.18 Simulation 3 Variables Simulation 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 Start-Delay (s) 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 Va (kV) 77.55 77.55 77.55 77.55 77.55 77.55 77.56 77.56 77.57 77.58 77.58 77.59 77.64 77.64 77.64 77.64 77.63 122.80 122.77 122.75 123.09 123.08 123.06 123.06 123.06 123.07 123.09 123.10 123.11 123.11 123.11 123.08 123.05 123.00 122.94 122.88 122.82 122.77 79.68 79.68 79.69 79.70 79.71 79.73 79.74 79.76 79.77 79.78 79.80 79.81 79.82 79.82 79.83 79.83 79.65 79.65 79.65 79.65 79.65 123.35 123.32 123.31 123.61 123.60 123.58 123.58 123.58 123.58 123.59 123.60 123.61 123.60 123.59 123.57 123.53 123.49 123.44 123.40 123.35 123.32 84.19 84.19 84.20 84.20 84.21 84.22 84.23 84.23 84.24 84.24 84.25 84.25 84.25 84.25 84.25 84.25 84.16 84.16 84.16 84.16 84.16 123.70 123.68 123.68 123.94 123.93 123.92 123.91 123.91 123.91 123.91 123.92 123.92 123.91 123.90 123.87 123.84 123.81 123.77 123.73 123.69 123.67 87.62 87.62 87.63 87.63 87.63 87.64 87.64 87.64 Vb (kV) 134.00 134.17 133.93 133.22 132.80 133.17 133.24 133.02 132.55 131.92 131.22 130.57 130.09 129.86 129.94 130.34 131.00 97.81 97.86 97.89 97.46 97.47 97.48 97.47 97.46 97.45 97.43 97.41 97.39 97.39 97.40 97.43 97.47 97.52 97.58 97.65 97.71 97.76 126.30 127.03 127.80 128.47 128.93 129.07 128.82 128.16 127.84 128.16 128.22 128.04 127.64 127.10 126.50 125.93 125.51 125.30 125.37 125.71 126.30 98.07 98.10 98.12 97.73 97.74 97.75 97.75 97.74 97.73 97.72 97.70 97.70 97.70 97.71 97.74 97.78 97.83 97.88 97.93 97.98 98.02 122.74 123.39 124.07 124.67 125.06 125.16 124.91 124.26 124.11 124.38 124.43 124.27 123.93 123.46 122.93 122.43 122.06 121.87 121.93 122.24 122.75 98.36 98.38 98.39 98.03 98.04 98.05 98.05 98.05 98.04 98.03 98.03 98.03 98.04 98.05 98.08 98.12 98.16 98.20 98.24 98.28 98.31 120.17 120.75 121.36 121.88 122.22 122.29 122.01 121.38 Vc (kV) 182.66 183.76 184.43 184.57 184.14 183.10 181.55 179.58 178.28 177.84 177.27 176.70 176.24 176.01 176.10 176.57 177.41 134.39 133.05 131.65 130.41 129.56 129.16 129.31 129.90 130.70 131.60 132.19 132.41 131.94 131.05 133.06 134.66 135.74 136.23 136.11 135.46 134.36 179.39 180.42 181.63 182.91 184.09 185.03 185.58 185.66 185.19 184.18 182.69 180.81 180.42 179.98 179.45 178.92 178.50 178.29 178.37 178.78 179.52 135.16 133.83 132.45 131.24 130.42 130.03 130.21 130.79 131.59 132.47 133.03 133.23 132.71 132.03 133.99 135.55 136.58 137.04 136.89 136.23 135.13 182.06 182.96 184.03 185.14 186.16 186.95 187.39 187.38 186.87 185.87 184.41 183.49 183.16 182.70 182.18 181.69 181.30 181.11 181.17 181.53 182.18 136.13 134.81 133.44 132.26 131.46 131.10 131.29 131.85 132.65 133.50 134.03 134.18 133.61 133.23 135.14 136.65 137.65 138.06 137.89 137.21 136.10 185.15 185.94 186.88 187.84 188.71 189.35 189.67 189.57 V Max (kV) 182.66 183.76 184.43 184.57 184.14 183.10 181.55 179.58 178.28 177.84 177.27 176.70 176.24 176.01 176.10 176.57 177.41 134.39 133.05 131.65 130.41 129.56 129.16 129.31 129.90 130.70 131.60 132.19 132.41 131.94 131.05 133.06 134.66 135.74 136.23 136.11 135.46 134.36 179.39 180.42 181.63 182.91 184.09 185.03 185.58 185.66 185.19 184.18 182.69 180.81 180.42 179.98 179.45 178.92 178.50 178.29 178.37 178.78 179.52 135.16 133.83 132.45 131.24 130.42 130.03 130.21 130.79 131.59 132.47 133.03 133.23 132.71 132.03 133.99 135.55 136.58 137.04 136.89 136.23 135.13 182.06 182.96 184.03 185.14 186.16 186.95 187.39 187.38 186.87 185.87 184.41 183.49 183.16 182.70 182.18 181.69 181.30 181.11 181.17 181.53 182.18 136.13 134.81 133.44 132.26 131.46 131.10 131.29 131.85 132.65 133.50 134.03 134.18 133.61 133.23 135.14 136.65 137.65 138.06 137.89 137.21 136.10 185.15 185.94 186.88 187.84 188.71 189.35 189.67 189.57 Line Length=10km Ratio Vmax/Vnom 3.39 3.41 3.42 3.43 3.42 3.40 3.37 3.33 3.31 3.30 3.29 3.28 3.27 3.27 3.27 3.28 3.29 2.49 2.47 2.44 2.42 2.40 2.40 2.40 2.41 2.43 2.44 2.45 2.46 2.45 2.43 2.47 2.50 2.52 2.53 2.53 2.51 2.49 3.33 3.35 3.37 3.39 3.42 3.43 3.44 3.45 3.44 3.42 3.39 3.36 3.35 3.34 3.33 3.32 3.31 3.31 3.31 3.32 3.33 2.51 2.48 2.46 2.44 2.42 2.41 2.42 2.43 2.44 2.46 2.47 2.47 2.46 2.45 2.49 2.52 2.53 2.54 2.54 2.53 2.51 3.38 3.40 3.41 3.44 3.45 3.47 3.48 3.48 3.47 3.45 3.42 3.40 3.40 3.39 3.38 3.37 3.36 3.36 3.36 3.37 3.38 2.53 2.50 2.48 2.45 2.44 2.43 2.44 2.45 2.46 2.48 2.49 2.49 2.48 2.47 2.51 2.54 2.55 2.56 2.56 2.55 2.53 3.44 3.45 3.47 3.49 3.50 3.51 3.52 3.52 Va (kV) 66.70 66.70 66.70 66.70 66.70 66.71 66.71 66.71 66.71 66.70 66.70 66.70 66.70 66.70 66.70 66.69 66.60 96.72 96.82 96.93 128.51 96.91 96.82 96.73 96.65 96.57 96.50 96.44 96.39 96.36 96.35 96.35 96.37 96.40 96.45 96.51 96.59 96.68 64.63 64.63 64.63 64.63 64.63 64.63 64.64 64.64 64.65 64.65 64.64 64.64 64.64 64.64 64.64 64.64 64.64 64.64 64.50 64.50 64.50 100.95 101.02 101.12 101.26 101.17 101.07 100.99 100.91 100.83 100.77 100.72 100.67 100.65 100.63 100.63 100.65 100.68 100.71 100.77 100.84 100.92 66.20 66.20 66.20 66.20 66.20 66.21 66.21 66.22 66.22 66.21 66.21 66.21 66.21 66.21 66.21 66.21 66.21 66.14 66.14 66.14 66.14 102.92 103.00 103.07 72.46 103.18 103.08 103.00 102.91 102.84 102.78 102.72 102.68 102.66 102.64 102.64 102.66 102.68 102.72 102.77 102.83 102.89 66.40 66.39 66.39 66.40 66.40 66.40 66.41 66.41 Vb (kV) 78.17 80.70 83.10 85.06 86.38 86.95 86.72 85.77 84.24 82.38 80.53 79.11 78.41 78.31 78.17 77.41 77.46 83.27 83.20 83.12 75.03 83.37 83.39 83.41 83.44 83.46 83.48 83.50 83.51 83.53 83.53 83.53 83.53 83.51 83.48 83.44 83.39 83.33 83.96 84.14 84.31 84.65 87.05 89.43 91.46 92.89 93.57 93.44 92.52 90.90 88.78 86.43 84.24 83.97 83.97 83.97 83.98 83.99 84.07 83.95 83.86 83.78 84.05 84.06 84.08 84.10 84.12 84.14 84.16 84.19 84.21 84.22 84.23 84.23 84.22 84.20 84.17 84.12 84.07 84.00 89.41 89.46 89.70 92.18 94.81 97.20 99.04 100.10 100.29 99.57 97.99 95.72 92.97 90.09 89.23 89.22 89.18 89.17 89.21 89.27 89.34 83.95 83.87 83.78 100.12 84.07 84.09 84.11 84.13 84.15 84.18 84.20 84.22 84.23 84.24 84.24 84.23 84.21 84.18 84.13 84.07 84.00 93.62 93.69 95.65 98.55 101.43 103.88 105.60 106.41 Vc (kV) 117.41 115.65 112.27 107.30 105.10 105.22 105.23 105.20 105.52 105.96 107.57 108.36 108.52 108.49 108.89 110.18 112.29 90.97 91.49 91.18 90.52 90.10 90.40 91.39 92.51 93.11 92.71 91.41 91.03 89.63 88.56 87.55 87.30 86.73 86.05 86.51 89.35 91.00 118.71 121.23 123.22 124.14 123.63 121.47 117.58 112.01 109.97 110.25 110.81 111.11 111.54 113.39 114.40 114.65 114.47 114.37 114.94 116.51 118.86 93.61 93.84 93.29 92.47 92.03 92.45 93.61 94.87 95.57 95.21 93.48 92.21 90.39 89.46 88.83 88.33 87.58 87.39 89.66 92.26 93.63 123.59 126.24 128.27 129.11 128.41 125.97 121.72 115.70 113.52 114.15 114.48 115.46 117.68 119.03 119.50 119.30 118.82 118.65 119.36 121.18 123.75 95.56 95.56 94.80 154.69 93.38 93.89 95.19 96.60 97.40 97.09 95.36 92.88 90.86 89.83 89.43 88.67 88.37 88.30 92.01 94.43 95.57 127.35 130.13 132.20 133.00 132.18 129.53 125.01 118.64 Ratio V Max (kV) Vmax/Vnom 117.41 2.18 115.65 2.15 112.27 2.08 107.30 1.99 105.10 1.95 105.22 1.95 105.23 1.95 105.20 1.95 105.52 1.96 105.96 1.97 107.57 2.00 108.36 2.01 108.52 2.01 108.49 2.01 108.89 2.02 110.18 2.04 112.29 2.08 96.72 1.79 96.82 1.80 96.93 1.80 128.51 2.38 96.91 1.80 96.82 1.80 96.73 1.80 96.65 1.79 96.57 1.79 96.50 1.79 96.44 1.79 96.39 1.79 96.36 1.79 96.35 1.79 96.35 1.79 96.37 1.79 96.40 1.79 96.45 1.79 96.51 1.79 96.59 1.79 96.68 1.79 118.71 2.20 121.23 2.25 123.22 2.29 124.14 2.30 123.63 2.29 121.47 2.25 117.58 2.18 112.01 2.08 109.97 2.04 110.25 2.05 110.81 2.06 111.11 2.06 111.54 2.07 113.39 2.10 114.40 2.12 114.65 2.13 114.47 2.12 114.37 2.12 114.94 2.13 116.51 2.16 118.86 2.21 100.95 1.87 101.02 1.87 101.12 1.88 101.26 1.88 101.17 1.88 101.07 1.88 100.99 1.87 100.91 1.87 100.83 1.87 100.77 1.87 100.72 1.87 100.67 1.87 100.65 1.87 100.63 1.87 100.63 1.87 100.65 1.87 100.68 1.87 100.71 1.87 100.77 1.87 100.84 1.87 100.92 1.87 123.59 2.29 126.24 2.34 128.27 2.38 129.11 2.40 128.41 2.38 125.97 2.34 121.72 2.26 115.70 2.15 113.52 2.11 114.15 2.12 114.48 2.12 115.46 2.14 117.68 2.18 119.03 2.21 119.50 2.22 119.30 2.21 118.82 2.20 118.65 2.20 119.36 2.22 121.18 2.25 123.75 2.30 102.92 1.91 103.00 1.91 103.07 1.91 154.69 2.87 103.18 1.91 103.08 1.91 103.00 1.91 102.91 1.91 102.84 1.91 102.78 1.91 102.72 1.91 102.68 1.91 102.66 1.90 102.64 1.90 102.64 1.90 102.66 1.90 102.68 1.91 102.72 1.91 102.77 1.91 102.83 1.91 102.89 1.91 127.35 2.36 130.13 2.41 132.20 2.45 133.00 2.47 132.18 2.45 129.53 2.40 125.01 2.32 118.64 2.20 Line Length=0.2km Va (kV) 68.76 68.76 68.76 68.76 68.75 68.75 68.75 68.75 68.75 68.75 68.76 68.75 68.75 68.75 68.75 68.64 68.64 96.35 99.04 100.84 127.21 101.45 100.48 98.52 95.72 92.33 88.66 85.07 81.98 79.75 78.64 78.75 80.09 82.50 85.71 89.35 93.01 96.34 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.07 65.06 65.06 65.06 99.91 101.97 103.08 62.49 103.15 102.88 101.59 99.40 96.52 93.23 89.90 86.95 84.76 83.65 83.77 85.10 87.45 90.51 93.85 97.11 99.90 62.57 62.57 62.57 62.57 62.57 62.56 62.56 62.56 62.56 62.57 62.57 62.57 62.57 62.57 62.57 62.57 62.78 62.78 62.78 62.78 62.78 101.87 103.50 104.14 71.01 103.85 104.06 103.21 101.45 98.95 95.99 92.93 90.15 88.08 87.01 87.12 88.40 90.63 93.48 96.56 99.47 101.88 64.06 64.06 64.06 64.06 64.06 64.06 64.06 64.06 Vb (kV) 80.46 80.42 80.48 82.11 83.61 84.71 85.25 85.18 84.53 83.44 82.16 81.02 80.37 80.37 80.37 80.38 80.40 86.56 88.62 89.68 74.14 89.89 89.71 88.44 86.20 83.47 83.95 83.68 82.97 82.22 81.77 81.82 82.35 83.12 83.77 83.93 83.81 86.72 87.36 87.36 87.32 87.37 87.45 88.46 90.65 92.55 93.87 94.46 94.24 93.28 91.69 89.72 87.70 87.31 87.29 87.29 87.29 87.31 87.33 87.95 89.62 90.33 100.07 90.31 90.42 89.52 87.68 85.10 82.06 81.69 81.33 80.86 80.56 80.59 80.94 81.42 81.73 82.64 85.64 88.11 91.83 91.83 91.89 92.18 93.22 96.18 98.90 100.96 102.15 102.35 101.57 99.90 97.54 94.81 92.12 91.76 91.74 91.74 91.74 91.76 91.77 88.44 89.94 90.52 104.52 90.41 90.64 89.87 88.21 85.83 83.00 80.06 79.50 79.13 78.89 78.91 79.19 79.57 80.59 83.55 86.32 88.60 94.90 94.93 95.38 95.84 98.94 102.55 105.61 107.78 Vc (kV) 117.77 116.57 113.70 109.11 108.34 108.38 108.34 108.33 108.38 108.35 108.27 108.29 108.69 108.75 108.84 109.55 111.23 86.38 87.90 88.42 90.76 88.41 89.23 90.87 92.66 93.84 93.91 92.55 90.21 90.93 90.67 89.37 87.09 87.45 87.37 86.80 85.92 86.47 117.37 120.30 122.94 124.62 124.87 123.42 120.11 114.97 110.86 110.87 110.81 110.88 110.91 111.28 112.41 113.02 113.15 113.13 113.53 114.92 117.37 88.91 90.17 90.41 148.71 90.11 91.10 93.04 95.13 96.59 96.85 95.60 92.69 92.85 92.10 90.24 88.92 88.92 88.34 87.31 87.10 89.00 121.77 125.12 128.02 129.81 130.02 128.39 124.79 119.25 111.89 111.84 111.87 111.96 113.45 115.17 116.18 116.47 116.31 116.22 116.87 118.77 121.76 90.59 91.66 91.69 156.52 91.18 92.29 94.44 96.76 98.42 98.83 97.68 94.82 94.30 93.20 90.91 90.19 89.81 88.80 87.93 88.31 90.69 125.05 128.73 131.84 133.71 133.90 132.15 128.35 122.51 Ratio V Max (kV) Vmax/Vnom 117.77 2.19 116.57 2.16 113.70 2.11 109.11 2.02 108.34 2.01 108.38 2.01 108.34 2.01 108.33 2.01 108.38 2.01 108.35 2.01 108.27 2.01 108.29 2.01 108.69 2.02 108.75 2.02 108.84 2.02 109.55 2.03 111.23 2.06 96.35 1.79 99.04 1.84 100.84 1.87 127.21 2.36 101.45 1.88 100.48 1.86 98.52 1.83 95.72 1.78 93.84 1.74 93.91 1.74 92.55 1.72 90.21 1.67 90.93 1.69 90.67 1.68 89.37 1.66 87.09 1.62 87.45 1.62 87.37 1.62 89.35 1.66 93.01 1.73 96.34 1.79 117.37 2.18 120.30 2.23 122.94 2.28 124.62 2.31 124.87 2.32 123.42 2.29 120.11 2.23 114.97 2.13 110.86 2.06 110.87 2.06 110.81 2.06 110.88 2.06 110.91 2.06 111.28 2.06 112.41 2.09 113.02 2.10 113.15 2.10 113.13 2.10 113.53 2.11 114.92 2.13 117.37 2.18 99.91 1.85 101.97 1.89 103.08 1.91 148.71 2.76 103.15 1.91 102.88 1.91 101.59 1.89 99.40 1.84 96.59 1.79 96.85 1.80 95.60 1.77 92.69 1.72 92.85 1.72 92.10 1.71 90.24 1.67 88.92 1.65 88.92 1.65 90.51 1.68 93.85 1.74 97.11 1.80 99.90 1.85 121.77 2.26 125.12 2.32 128.02 2.38 129.81 2.41 130.02 2.41 128.39 2.38 124.79 2.32 119.25 2.21 111.89 2.08 111.84 2.08 111.87 2.08 111.96 2.08 113.45 2.11 115.17 2.14 116.18 2.16 116.47 2.16 116.31 2.16 116.22 2.16 116.87 2.17 118.77 2.20 121.76 2.26 101.87 1.89 103.50 1.92 104.14 1.93 156.52 2.90 103.85 1.93 104.06 1.93 103.21 1.92 101.45 1.88 98.95 1.84 98.83 1.83 97.68 1.81 94.82 1.76 94.30 1.75 93.20 1.73 90.91 1.69 90.19 1.67 90.63 1.68 93.48 1.73 96.56 1.79 99.47 1.85 101.88 1.89 125.05 2.32 128.73 2.39 131.84 2.45 133.71 2.48 133.90 2.48 132.15 2.45 128.35 2.38 122.51 2.27 Simulation 3 Variables Simulation 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 Start-Delay (s) 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 45 45 45 45 45 45 45 45 45 45 45 45 Va (kV) 87.64 87.64 87.64 87.64 87.64 87.63 87.63 87.63 87.59 87.59 87.59 87.60 87.60 123.85 123.84 123.84 124.08 124.06 124.05 124.04 124.04 124.04 124.04 124.04 124.03 124.02 124.01 123.98 123.96 123.92 123.89 123.86 123.83 123.82 92.62 92.62 92.63 92.64 92.65 92.66 92.67 92.68 92.69 92.70 92.71 92.71 92.71 92.72 92.72 92.71 92.59 92.59 92.59 92.59 92.60 123.80 123.80 123.81 116.99 124.00 123.99 123.98 123.98 123.97 123.97 123.97 123.96 123.95 123.93 123.91 123.88 123.86 123.83 123.80 123.78 123.77 102.05 102.05 102.06 102.06 102.07 102.08 102.08 102.09 102.09 102.09 102.09 102.09 102.09 102.09 102.09 102.09 102.02 102.02 102.02 102.02 102.02 123.59 123.59 122.60 122.60 123.77 123.76 123.75 123.75 123.74 123.74 123.73 123.72 123.71 123.69 123.67 123.64 123.62 123.59 123.57 123.56 123.55 111.14 111.14 111.15 111.15 111.16 111.16 111.16 111.16 111.16 111.16 111.16 111.15 Vb (kV) 121.45 121.66 121.69 121.54 121.24 120.82 120.35 119.92 119.58 119.42 119.47 119.74 120.20 98.67 98.68 98.68 98.36 98.37 98.38 98.38 98.38 98.37 98.37 98.37 98.38 98.39 98.41 98.44 98.47 98.50 98.54 98.57 98.60 98.62 118.45 118.97 119.51 119.98 120.26 120.29 120.01 119.42 119.70 119.86 119.86 119.71 119.43 119.05 118.63 118.24 117.94 117.79 117.84 118.08 118.49 98.99 99.00 99.00 85.08 98.71 98.72 98.72 98.72 98.72 98.72 98.73 98.74 98.75 98.77 98.80 98.83 98.86 98.89 98.92 98.94 98.95 117.46 117.93 118.41 118.82 119.06 119.05 118.75 118.53 118.74 118.83 118.80 118.64 118.37 118.03 117.64 117.29 117.02 116.88 116.92 117.14 117.51 99.32 99.32 86.20 86.22 99.06 99.06 99.07 99.07 99.07 99.08 99.09 99.10 99.12 99.14 99.16 99.19 99.22 99.24 99.26 99.27 99.28 117.09 117.50 117.93 118.29 118.48 118.44 118.12 118.31 118.43 118.47 118.40 118.22 Vc (kV) 189.01 187.98 186.98 186.74 186.35 185.86 185.34 184.86 184.49 184.31 184.37 184.69 185.27 137.23 135.91 134.55 133.39 132.60 132.26 132.47 133.02 133.82 134.62 135.12 135.21 134.59 134.58 136.44 137.91 138.86 139.24 139.03 138.32 137.20 188.51 189.22 190.03 190.86 191.58 192.09 192.28 192.08 191.44 190.82 190.64 190.30 189.84 189.31 188.78 188.30 187.95 187.77 187.82 188.11 188.63 138.40 137.08 135.71 153.50 133.79 133.47 133.69 134.24 135.03 135.79 136.25 136.29 135.61 136.03 137.85 139.27 140.17 140.50 140.26 139.52 138.38 192.06 192.68 193.38 194.08 194.67 195.03 195.10 194.88 194.92 194.79 194.49 194.05 193.51 192.94 192.39 191.91 191.56 191.40 191.45 191.71 192.17 139.61 138.26 154.21 154.16 134.99 134.69 134.92 135.46 136.25 136.97 137.40 137.38 136.65 137.53 139.31 140.68 141.53 141.81 141.53 140.75 139.58 196.35 196.81 197.35 197.91 198.42 198.83 199.09 199.19 199.10 198.84 198.42 197.88 V Max (kV) 189.01 187.98 186.98 186.74 186.35 185.86 185.34 184.86 184.49 184.31 184.37 184.69 185.27 137.23 135.91 134.55 133.39 132.60 132.26 132.47 133.02 133.82 134.62 135.12 135.21 134.59 134.58 136.44 137.91 138.86 139.24 139.03 138.32 137.20 188.51 189.22 190.03 190.86 191.58 192.09 192.28 192.08 191.44 190.82 190.64 190.30 189.84 189.31 188.78 188.30 187.95 187.77 187.82 188.11 188.63 138.40 137.08 135.71 153.50 133.79 133.47 133.69 134.24 135.03 135.79 136.25 136.29 135.61 136.03 137.85 139.27 140.17 140.50 140.26 139.52 138.38 192.06 192.68 193.38 194.08 194.67 195.03 195.10 194.88 194.92 194.79 194.49 194.05 193.51 192.94 192.39 191.91 191.56 191.40 191.45 191.71 192.17 139.61 138.26 154.21 154.16 134.99 134.69 134.92 135.46 136.25 136.97 137.40 137.38 136.65 137.53 139.31 140.68 141.53 141.81 141.53 140.75 139.58 196.35 196.81 197.35 197.91 198.42 198.83 199.09 199.19 199.10 198.84 198.42 197.88 Line Length=10km Ratio Vmax/Vnom 3.51 3.49 3.47 3.47 3.46 3.45 3.44 3.43 3.42 3.42 3.42 3.43 3.44 2.55 2.52 2.50 2.48 2.46 2.45 2.46 2.47 2.48 2.50 2.51 2.51 2.50 2.50 2.53 2.56 2.58 2.58 2.58 2.57 2.55 3.50 3.51 3.53 3.54 3.56 3.56 3.57 3.56 3.55 3.54 3.54 3.53 3.52 3.51 3.50 3.49 3.49 3.48 3.49 3.49 3.50 2.57 2.54 2.52 2.85 2.48 2.48 2.48 2.49 2.51 2.52 2.53 2.53 2.52 2.52 2.56 2.58 2.60 2.61 2.60 2.59 2.57 3.56 3.58 3.59 3.60 3.61 3.62 3.62 3.62 3.62 3.61 3.61 3.60 3.59 3.58 3.57 3.56 3.55 3.55 3.55 3.56 3.57 2.59 2.57 2.86 2.86 2.51 2.50 2.50 2.51 2.53 2.54 2.55 2.55 2.54 2.55 2.59 2.61 2.63 2.63 2.63 2.61 2.59 3.64 3.65 3.66 3.67 3.68 3.69 3.69 3.70 3.69 3.69 3.68 3.67 Va (kV) 66.41 66.41 66.40 66.40 66.40 66.40 66.40 66.41 66.41 66.41 66.41 66.41 66.41 103.94 104.00 104.06 75.64 104.21 104.12 104.03 103.95 103.88 103.82 103.77 103.73 103.70 103.68 103.69 103.70 103.73 103.77 103.81 103.86 103.91 65.87 65.87 65.87 65.88 65.88 65.89 65.89 65.89 65.89 65.88 65.88 65.88 65.88 65.88 65.88 65.94 65.94 65.94 65.94 65.94 65.94 104.51 104.56 104.61 78.63 104.78 104.69 104.60 104.52 104.45 104.39 104.35 104.32 104.29 104.28 104.28 104.30 104.32 104.34 104.38 104.43 104.48 64.97 64.97 64.97 64.98 64.98 64.98 64.99 64.98 64.98 64.98 64.97 64.97 64.98 64.98 64.98 65.08 65.08 65.08 65.08 65.08 65.08 104.84 104.89 104.92 83.18 105.13 105.04 104.95 104.87 104.80 104.74 104.70 104.67 104.64 104.64 104.64 104.65 104.67 104.70 104.73 104.77 104.81 65.72 65.72 65.73 65.73 65.73 65.72 65.72 65.72 65.72 65.71 65.71 65.72 Vb (kV) 106.21 105.00 102.87 100.00 96.69 93.37 93.42 93.36 93.28 93.25 93.32 93.44 93.56 83.86 83.78 83.69 102.90 83.98 84.00 84.02 84.04 84.07 84.09 84.11 84.13 84.14 84.15 84.15 84.14 84.12 84.09 84.04 83.98 83.91 96.85 97.77 100.69 103.96 107.06 109.58 111.24 111.85 111.34 109.72 107.12 103.75 99.92 96.72 96.70 96.56 96.43 96.40 96.49 96.65 96.81 83.79 83.71 83.62 105.26 83.92 83.93 83.95 83.97 83.99 84.02 84.05 84.07 84.08 84.09 84.09 84.08 84.05 84.01 83.97 83.92 83.84 99.39 101.65 104.98 108.56 111.86 114.46 116.07 116.53 115.77 113.82 110.82 107.00 102.73 99.45 99.32 99.10 98.92 98.87 98.98 99.18 99.35 83.77 83.69 83.59 107.26 83.89 83.91 83.93 83.95 83.97 84.00 84.02 84.04 84.05 84.06 84.06 84.05 84.02 83.99 83.95 83.89 83.81 102.05 104.98 108.67 112.52 115.99 118.66 120.25 120.58 119.61 117.38 114.03 109.84 Vc (kV) 116.21 116.62 117.88 120.66 122.55 123.44 123.45 122.85 122.12 121.90 122.73 124.75 127.52 97.04 96.85 95.92 160.26 94.36 94.94 96.36 97.89 98.78 98.53 96.82 93.53 91.20 90.32 89.66 89.01 88.94 90.14 93.80 96.08 97.04 130.33 133.22 135.33 136.12 135.21 132.41 127.67 121.04 118.09 118.82 122.31 124.93 126.49 126.99 126.59 125.64 124.71 124.43 125.37 127.56 130.50 98.19 97.84 96.77 164.68 95.09 95.73 97.25 98.88 99.85 99.66 97.98 94.68 91.40 90.57 89.68 89.43 89.26 91.60 95.19 97.36 98.18 132.74 135.73 137.89 138.66 137.69 134.77 129.86 123.02 119.45 122.54 126.04 128.48 129.75 129.89 129.14 127.90 126.78 126.46 127.48 129.82 132.91 99.10 98.62 97.43 168.27 95.65 96.34 97.94 99.65 100.70 100.56 98.91 95.61 91.54 90.71 89.83 89.69 89.42 92.75 96.29 98.37 99.08 134.72 137.81 140.01 140.78 139.76 136.75 131.69 124.68 121.33 125.76 129.22 131.48 Ratio V Max (kV) Vmax/Vnom 116.21 2.16 116.62 2.16 117.88 2.19 120.66 2.24 122.55 2.27 123.44 2.29 123.45 2.29 122.85 2.28 122.12 2.27 121.90 2.26 122.73 2.28 124.75 2.31 127.52 2.37 103.94 1.93 104.00 1.93 104.06 1.93 160.26 2.97 104.21 1.93 104.12 1.93 104.03 1.93 103.95 1.93 103.88 1.93 103.82 1.93 103.77 1.93 103.73 1.92 103.70 1.92 103.68 1.92 103.69 1.92 103.70 1.92 103.73 1.92 103.77 1.93 103.81 1.93 103.86 1.93 103.91 1.93 130.33 2.42 133.22 2.47 135.33 2.51 136.12 2.53 135.21 2.51 132.41 2.46 127.67 2.37 121.04 2.25 118.09 2.19 118.82 2.20 122.31 2.27 124.93 2.32 126.49 2.35 126.99 2.36 126.59 2.35 125.64 2.33 124.71 2.31 124.43 2.31 125.37 2.33 127.56 2.37 130.50 2.42 104.51 1.94 104.56 1.94 104.61 1.94 164.68 3.06 104.78 1.94 104.69 1.94 104.60 1.94 104.52 1.94 104.45 1.94 104.39 1.94 104.35 1.94 104.32 1.94 104.29 1.94 104.28 1.94 104.28 1.94 104.30 1.94 104.32 1.94 104.34 1.94 104.38 1.94 104.43 1.94 104.48 1.94 132.74 2.46 135.73 2.52 137.89 2.56 138.66 2.57 137.69 2.56 134.77 2.50 129.86 2.41 123.02 2.28 119.45 2.22 122.54 2.27 126.04 2.34 128.48 2.38 129.75 2.41 129.89 2.41 129.14 2.40 127.90 2.37 126.78 2.35 126.46 2.35 127.48 2.37 129.82 2.41 132.91 2.47 104.84 1.95 104.89 1.95 104.92 1.95 168.27 3.12 105.13 1.95 105.04 1.95 104.95 1.95 104.87 1.95 104.80 1.94 104.74 1.94 104.70 1.94 104.67 1.94 104.64 1.94 104.64 1.94 104.64 1.94 104.65 1.94 104.67 1.94 104.70 1.94 104.73 1.94 104.77 1.94 104.81 1.94 134.72 2.50 137.81 2.56 140.01 2.60 140.78 2.61 139.76 2.59 136.75 2.54 131.69 2.44 124.68 2.31 121.33 2.25 125.76 2.33 129.22 2.40 131.48 2.44 Line Length=0.2km Va (kV) 64.06 64.06 64.06 64.06 64.06 64.06 64.06 64.06 64.14 64.14 64.14 64.14 64.14 103.12 104.42 104.74 77.78 104.21 104.73 104.21 102.76 100.54 97.83 94.97 92.36 90.38 89.35 89.46 90.68 92.80 95.49 98.36 101.01 103.12 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.44 65.52 65.52 65.52 65.52 65.52 65.52 103.99 105.06 105.13 83.05 104.41 105.18 104.90 103.68 101.68 99.16 96.46 93.97 92.07 91.09 91.19 92.36 94.39 96.95 99.65 102.11 103.99 66.63 66.63 66.63 66.63 66.63 66.63 66.63 66.64 66.64 66.64 66.64 66.64 66.64 66.64 66.71 66.71 66.71 66.71 66.71 66.71 66.71 104.63 105.52 105.40 87.62 104.54 105.49 105.41 104.37 102.54 100.17 97.60 95.21 93.38 92.43 92.53 93.65 95.61 98.07 100.64 102.94 104.65 67.75 67.75 67.75 67.75 67.75 67.75 67.75 67.75 67.75 67.75 67.75 67.75 Vb (kV) 108.86 108.76 107.52 105.28 102.29 98.91 95.66 94.76 94.74 94.74 94.74 94.75 94.79 88.69 90.09 90.61 107.99 90.47 90.74 90.04 88.48 86.21 83.50 80.68 78.11 77.54 77.31 77.34 77.60 78.54 81.18 84.02 86.68 88.85 97.13 97.57 98.22 99.42 103.75 107.84 111.16 113.40 114.37 114.01 112.40 109.69 106.17 102.27 98.53 96.88 96.86 96.86 96.87 96.95 97.18 88.88 90.23 90.69 110.80 90.53 90.83 90.19 88.69 86.50 83.86 81.11 78.62 76.74 75.94 75.97 77.03 79.04 81.61 84.36 86.95 89.04 99.07 99.79 100.64 102.94 107.83 112.28 115.79 118.07 118.95 118.39 116.46 113.36 109.40 105.04 100.90 98.53 98.56 98.57 98.59 98.76 99.21 89.08 90.37 90.79 113.10 90.60 90.93 90.34 88.89 86.76 84.20 81.51 79.07 77.23 76.28 76.38 77.51 79.48 82.00 84.69 87.21 89.24 100.82 101.74 102.79 105.99 111.32 116.05 119.71 122.02 122.82 122.07 119.88 116.45 Vc (kV) 114.79 112.24 112.67 114.09 116.68 118.38 119.13 119.09 118.67 118.51 119.36 121.65 125.04 91.78 92.70 92.57 162.30 91.89 93.09 95.40 97.90 99.70 100.24 99.18 96.35 95.52 94.18 91.57 91.19 90.48 89.09 88.68 89.60 91.89 127.60 131.53 134.80 136.75 136.94 135.10 131.14 125.07 117.07 113.25 113.82 116.79 119.47 121.02 121.48 121.14 120.49 120.28 121.29 123.87 127.59 92.66 93.46 93.20 166.76 92.39 93.66 96.10 98.73 100.65 101.28 100.29 97.50 96.59 95.08 92.22 92.05 91.06 89.35 89.30 90.56 92.76 129.63 133.76 137.17 139.19 139.37 137.47 133.38 127.14 118.91 114.35 115.33 119.21 121.85 123.21 123.41 122.79 121.94 121.68 122.82 125.65 129.61 93.33 94.03 93.67 170.29 92.77 94.09 96.62 99.36 101.38 102.09 101.15 98.39 97.54 95.89 93.11 92.81 91.60 89.90 89.83 91.30 93.43 131.28 135.58 139.11 141.18 141.37 139.41 135.22 128.84 120.43 115.52 117.39 121.34 Ratio V Max (kV) Vmax/Vnom 114.79 2.13 112.24 2.08 112.67 2.09 114.09 2.12 116.68 2.17 118.38 2.20 119.13 2.21 119.09 2.21 118.67 2.20 118.51 2.20 119.36 2.21 121.65 2.26 125.04 2.32 103.12 1.91 104.42 1.94 104.74 1.94 162.30 3.01 104.21 1.93 104.73 1.94 104.21 1.93 102.76 1.91 100.54 1.87 100.24 1.86 99.18 1.84 96.35 1.79 95.52 1.77 94.18 1.75 91.57 1.70 91.19 1.69 92.80 1.72 95.49 1.77 98.36 1.83 101.01 1.87 103.12 1.91 127.60 2.37 131.53 2.44 134.80 2.50 136.75 2.54 136.94 2.54 135.10 2.51 131.14 2.43 125.07 2.32 117.07 2.17 114.01 2.12 113.82 2.11 116.79 2.17 119.47 2.22 121.02 2.25 121.48 2.25 121.14 2.25 120.49 2.24 120.28 2.23 121.29 2.25 123.87 2.30 127.59 2.37 103.99 1.93 105.06 1.95 105.13 1.95 166.76 3.09 104.41 1.94 105.18 1.95 104.90 1.95 103.68 1.92 101.68 1.89 101.28 1.88 100.29 1.86 97.50 1.81 96.59 1.79 95.08 1.76 92.22 1.71 92.36 1.71 94.39 1.75 96.95 1.80 99.65 1.85 102.11 1.89 103.99 1.93 129.63 2.41 133.76 2.48 137.17 2.55 139.19 2.58 139.37 2.59 137.47 2.55 133.38 2.48 127.14 2.36 118.95 2.21 118.39 2.20 116.46 2.16 119.21 2.21 121.85 2.26 123.21 2.29 123.41 2.29 122.79 2.28 121.94 2.26 121.68 2.26 122.82 2.28 125.65 2.33 129.61 2.41 104.63 1.94 105.52 1.96 105.40 1.96 170.29 3.16 104.54 1.94 105.49 1.96 105.41 1.96 104.37 1.94 102.54 1.90 102.09 1.89 101.15 1.88 98.39 1.83 97.54 1.81 95.89 1.78 93.11 1.73 93.65 1.74 95.61 1.77 98.07 1.82 100.64 1.87 102.94 1.91 104.65 1.94 131.28 2.44 135.58 2.52 139.11 2.58 141.18 2.62 141.37 2.62 139.41 2.59 135.22 2.51 128.84 2.39 122.82 2.28 122.07 2.27 119.88 2.22 121.34 2.25 Simulation 3 Variables Simulation 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 Start-Delay (s) 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 Va (kV) 111.15 111.14 111.14 111.14 111.12 111.11 111.11 111.12 111.12 123.23 123.23 127.84 127.84 123.40 123.39 123.38 123.37 123.37 123.36 123.35 123.34 123.33 123.31 123.29 123.26 123.24 123.22 123.21 123.20 123.19 119.91 119.92 119.92 119.92 119.92 119.92 119.92 119.92 119.91 119.91 119.90 119.90 119.89 119.89 119.88 119.88 119.89 119.89 119.89 119.89 119.89 122.75 122.76 132.72 132.72 122.92 122.91 122.90 122.89 122.88 122.87 122.86 122.85 122.84 122.82 122.80 122.77 122.75 122.74 122.72 122.72 122.72 192.76 192.76 192.75 192.75 192.74 192.74 192.74 192.73 192.74 192.74 192.75 192.75 192.76 192.77 192.78 192.79 192.75 192.75 192.75 192.75 192.74 117.44 117.43 166.26 166.26 166.24 117.52 117.53 117.55 117.56 117.56 117.56 117.55 117.54 117.52 117.51 117.49 117.48 117.47 117.46 117.45 117.44 404.79 404.91 405.08 405.26 405.46 405.65 405.83 405.96 406.06 406.10 406.10 406.04 405.95 405.83 404.78 404.71 Vb (kV) 117.96 117.63 117.28 116.95 116.70 116.58 116.61 116.81 117.14 99.64 99.64 87.06 87.08 99.40 99.40 99.41 99.41 99.42 99.43 99.44 99.45 99.47 99.49 99.51 99.54 99.56 99.58 99.59 99.60 99.60 117.54 117.67 117.98 118.29 118.44 118.36 118.51 118.63 118.68 118.65 118.54 118.35 118.08 117.79 117.61 117.48 117.39 117.35 117.35 117.41 117.51 99.95 99.94 88.22 88.25 99.72 99.73 99.74 99.74 99.75 99.76 99.77 99.79 99.81 99.83 99.85 99.87 99.89 99.90 99.91 99.91 99.91 139.98 140.16 140.37 140.59 140.77 140.88 140.90 140.81 140.59 140.27 140.16 140.18 140.17 140.12 140.05 139.97 139.90 139.87 139.88 139.95 140.08 101.99 101.96 115.15 115.16 115.17 101.95 101.96 101.98 102.00 102.02 102.03 102.05 102.06 102.07 102.07 102.07 102.06 102.04 102.01 101.98 101.95 267.70 267.79 267.89 268.01 268.13 268.23 268.31 268.36 268.37 268.33 268.25 268.13 267.99 267.83 267.68 267.59 Vc (kV) 197.28 196.66 196.29 196.03 195.82 195.71 195.74 195.93 196.27 140.81 139.44 154.86 154.81 136.18 135.89 136.13 136.67 137.45 138.14 138.55 138.46 137.68 139.04 140.78 142.11 142.91 143.14 142.80 141.98 140.79 201.18 201.63 202.13 202.63 203.06 203.37 203.53 203.50 203.29 202.90 202.37 201.80 201.70 201.48 201.19 200.90 200.67 200.55 200.59 200.78 201.11 141.99 140.60 155.51 155.46 137.33 137.06 137.30 137.84 138.62 139.29 139.66 139.52 138.69 140.53 142.24 143.52 144.27 144.45 144.07 143.20 141.97 244.07 244.18 244.42 244.77 245.12 245.44 245.67 245.79 245.75 245.54 245.17 244.66 244.36 244.24 244.11 243.99 243.90 243.86 243.87 243.93 244.02 151.29 149.59 160.92 160.89 160.85 145.83 146.15 146.77 147.56 148.12 148.34 148.63 150.70 152.56 154.04 154.99 155.34 155.07 154.22 152.90 151.28 390.22 390.36 390.59 390.85 391.07 391.23 391.30 391.26 391.19 391.14 391.03 390.88 390.69 390.48 390.27 390.14 V Max (kV) 197.28 196.66 196.29 196.03 195.82 195.71 195.74 195.93 196.27 140.81 139.44 154.86 154.81 136.18 135.89 136.13 136.67 137.45 138.14 138.55 138.46 137.68 139.04 140.78 142.11 142.91 143.14 142.80 141.98 140.79 201.18 201.63 202.13 202.63 203.06 203.37 203.53 203.50 203.29 202.90 202.37 201.80 201.70 201.48 201.19 200.90 200.67 200.55 200.59 200.78 201.11 141.99 140.60 155.51 155.46 137.33 137.06 137.30 137.84 138.62 139.29 139.66 139.52 138.69 140.53 142.24 143.52 144.27 144.45 144.07 143.20 141.97 244.07 244.18 244.42 244.77 245.12 245.44 245.67 245.79 245.75 245.54 245.17 244.66 244.36 244.24 244.11 243.99 243.90 243.86 243.87 243.93 244.02 151.29 149.59 166.26 166.26 166.24 145.83 146.15 146.77 147.56 148.12 148.34 148.63 150.70 152.56 154.04 154.99 155.34 155.07 154.22 152.90 151.28 404.79 404.91 405.08 405.26 405.46 405.65 405.83 405.96 406.06 406.10 406.10 406.04 405.95 405.83 404.78 404.71 Line Length=10km Ratio Vmax/Vnom 3.66 3.65 3.64 3.64 3.63 3.63 3.63 3.64 3.64 2.61 2.59 2.87 2.87 2.53 2.52 2.53 2.54 2.55 2.56 2.57 2.57 2.55 2.58 2.61 2.64 2.65 2.66 2.65 2.63 2.61 3.73 3.74 3.75 3.76 3.77 3.77 3.78 3.78 3.77 3.77 3.76 3.74 3.74 3.74 3.73 3.73 3.72 3.72 3.72 3.73 3.73 2.63 2.61 2.89 2.88 2.55 2.54 2.55 2.56 2.57 2.58 2.59 2.59 2.57 2.61 2.64 2.66 2.68 2.68 2.67 2.66 2.63 4.53 4.53 4.54 4.54 4.55 4.55 4.56 4.56 4.56 4.56 4.55 4.54 4.53 4.53 4.53 4.53 4.53 4.53 4.53 4.53 4.53 2.81 2.78 3.09 3.09 3.08 2.71 2.71 2.72 2.74 2.75 2.75 2.76 2.80 2.83 2.86 2.88 2.88 2.88 2.86 2.84 2.81 7.51 7.51 7.52 7.52 7.52 7.53 7.53 7.53 7.54 7.54 7.54 7.53 7.53 7.53 7.51 7.51 Va (kV) 65.72 65.72 65.78 65.78 65.78 65.78 65.78 65.78 65.78 105.06 105.09 105.13 87.31 105.36 105.27 105.18 105.10 105.03 104.97 104.92 104.89 104.87 104.86 104.86 104.87 104.90 104.92 104.95 104.98 105.02 67.89 67.89 67.89 67.89 67.89 67.89 67.88 67.88 67.88 67.88 67.88 67.88 67.88 67.88 67.93 67.93 67.93 67.93 67.93 67.93 67.93 105.19 105.23 105.26 91.17 105.50 105.41 105.32 105.24 105.17 105.11 105.07 105.04 105.03 105.02 105.02 105.03 105.04 105.06 105.09 105.13 105.15 83.10 83.11 83.11 83.11 83.11 83.10 83.08 83.07 83.06 83.04 83.03 82.97 82.98 82.98 82.98 82.98 82.98 82.98 82.98 82.99 82.99 105.49 105.52 105.56 120.48 105.87 105.78 105.69 105.62 105.57 105.55 105.54 105.53 105.52 105.49 105.46 105.43 105.40 105.39 105.38 105.41 105.45 115.57 115.48 115.11 114.40 113.36 112.08 110.72 109.48 115.61 116.29 116.66 116.72 116.51 116.12 115.66 115.27 Vb (kV) 105.18 101.71 101.48 101.16 100.92 100.87 101.00 101.22 102.25 83.78 83.70 83.60 108.98 83.91 83.92 83.94 83.96 83.99 84.01 84.03 84.05 84.06 84.07 84.06 84.06 84.04 84.00 83.96 83.90 83.83 104.58 107.86 111.86 115.95 119.57 122.31 123.88 124.11 122.96 120.48 116.84 112.31 107.32 103.63 103.28 102.87 102.57 102.51 102.66 102.91 104.78 83.82 83.73 83.64 110.46 83.94 83.96 83.98 84.00 84.02 84.04 84.06 84.08 84.10 84.10 84.10 84.09 84.07 84.04 84.00 83.94 83.87 118.48 123.71 129.41 134.83 139.33 142.47 143.99 143.71 141.63 137.85 132.59 126.24 119.33 114.69 113.21 111.96 112.04 111.98 112.64 114.81 118.72 84.53 84.43 84.31 118.65 84.66 84.67 84.69 84.71 84.72 84.74 84.76 84.79 84.81 84.83 84.84 84.85 84.83 84.80 84.74 84.67 84.57 133.68 141.05 148.65 155.54 161.06 164.72 166.24 165.48 162.43 157.26 150.25 141.87 136.91 132.88 128.82 125.44 Vc (kV) 132.47 132.31 131.24 129.75 128.47 128.12 129.22 131.68 134.89 99.83 99.25 97.96 171.23 96.09 96.82 98.49 100.28 101.39 101.29 99.67 96.37 91.66 90.79 90.08 89.85 89.53 93.68 97.18 99.19 99.81 136.38 139.55 141.80 142.57 141.50 138.42 133.25 126.09 124.03 128.56 131.95 134.04 134.79 134.35 133.02 131.30 129.88 129.50 130.66 133.24 136.55 100.43 99.76 98.39 173.73 96.45 97.21 98.94 100.79 101.95 101.90 100.30 97.01 92.00 90.83 90.27 89.94 89.70 94.44 97.91 99.87 100.40 144.74 148.38 150.90 151.74 150.53 147.09 141.37 133.48 139.46 143.95 146.67 147.62 146.93 144.90 142.03 139.04 136.84 136.30 137.81 140.99 144.92 103.23 102.14 100.34 186.41 98.01 98.93 100.97 103.15 104.60 104.77 103.32 100.11 95.09 91.81 90.94 90.61 93.03 97.99 101.32 103.01 103.18 152.67 156.87 159.77 160.76 159.50 155.78 151.12 150.61 156.75 160.66 162.30 161.77 159.32 155.42 150.77 146.32 Ratio V Max (kV) Vmax/Vnom 132.47 2.46 132.31 2.46 131.24 2.44 129.75 2.41 128.47 2.38 128.12 2.38 129.22 2.40 131.68 2.44 134.89 2.50 105.06 1.95 105.09 1.95 105.13 1.95 171.23 3.18 105.36 1.96 105.27 1.95 105.18 1.95 105.10 1.95 105.03 1.95 104.97 1.95 104.92 1.95 104.89 1.95 104.87 1.95 104.86 1.95 104.86 1.95 104.87 1.95 104.90 1.95 104.92 1.95 104.95 1.95 104.98 1.95 105.02 1.95 136.38 2.53 139.55 2.59 141.80 2.63 142.57 2.65 141.50 2.63 138.42 2.57 133.25 2.47 126.09 2.34 124.03 2.30 128.56 2.39 131.95 2.45 134.04 2.49 134.79 2.50 134.35 2.49 133.02 2.47 131.30 2.44 129.88 2.41 129.50 2.40 130.66 2.42 133.24 2.47 136.55 2.53 105.19 1.95 105.23 1.95 105.26 1.95 173.73 3.22 105.50 1.96 105.41 1.96 105.32 1.95 105.24 1.95 105.17 1.95 105.11 1.95 105.07 1.95 105.04 1.95 105.03 1.95 105.02 1.95 105.02 1.95 105.03 1.95 105.04 1.95 105.06 1.95 105.09 1.95 105.13 1.95 105.15 1.95 144.74 2.69 148.38 2.75 150.90 2.80 151.74 2.82 150.53 2.79 147.09 2.73 143.99 2.67 143.71 2.67 141.63 2.63 143.95 2.67 146.67 2.72 147.62 2.74 146.93 2.73 144.90 2.69 142.03 2.64 139.04 2.58 136.84 2.54 136.30 2.53 137.81 2.56 140.99 2.62 144.92 2.69 105.49 1.96 105.52 1.96 105.56 1.96 186.41 3.46 105.87 1.96 105.78 1.96 105.69 1.96 105.62 1.96 105.57 1.96 105.55 1.96 105.54 1.96 105.53 1.96 105.52 1.96 105.49 1.96 105.46 1.96 105.43 1.96 105.40 1.96 105.39 1.96 105.38 1.96 105.41 1.96 105.45 1.96 152.67 2.83 156.87 2.91 159.77 2.96 160.76 2.98 161.06 2.99 164.72 3.06 166.24 3.08 165.48 3.07 162.43 3.01 160.66 2.98 162.30 3.01 161.77 3.00 159.32 2.96 155.42 2.88 150.77 2.80 146.32 2.72 Line Length=0.2km Va (kV) 67.75 67.75 67.81 67.81 67.81 67.81 67.81 67.81 67.81 105.15 105.88 105.60 91.78 104.61 105.73 105.80 104.91 103.22 100.98 98.51 96.20 94.42 93.50 93.60 94.69 96.59 98.96 101.41 103.59 105.16 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.82 68.87 68.87 68.87 68.87 68.87 68.87 68.87 68.87 105.57 106.17 105.76 95.68 104.68 105.92 106.12 105.35 103.77 101.64 99.25 97.02 95.29 94.38 94.47 95.54 97.39 99.68 102.05 104.12 105.58 78.13 78.12 78.12 78.12 78.13 78.15 78.17 78.20 78.22 78.23 78.24 78.05 78.04 78.04 78.03 78.03 78.03 78.03 78.03 78.03 78.02 107.58 107.56 124.17 124.95 104.90 106.78 107.63 107.50 106.53 104.93 103.00 101.05 99.49 98.65 98.71 99.64 101.25 103.22 105.16 106.72 107.60 105.92 106.94 107.91 108.57 108.75 108.33 107.42 108.62 109.14 101.46 100.49 101.66 102.90 103.84 104.37 104.54 Vb (kV) 112.11 107.37 102.87 99.88 99.99 100.01 100.06 100.33 100.95 89.29 90.53 90.90 115.02 90.68 91.06 90.50 89.11 87.04 84.53 81.90 79.50 77.69 76.76 76.86 77.97 79.91 82.38 85.02 87.48 89.45 102.36 103.49 104.72 108.64 114.32 119.28 123.07 125.40 126.12 125.22 122.80 119.07 114.42 109.35 104.55 101.09 101.21 101.22 101.31 101.69 102.49 89.52 90.70 91.03 116.64 90.77 91.18 90.69 89.35 87.33 84.87 82.28 79.93 78.15 77.24 77.33 78.43 80.34 82.76 85.35 87.76 89.68 112.40 115.12 117.69 123.34 130.67 136.70 141.03 143.39 143.67 141.90 138.23 132.97 126.57 119.70 113.24 108.45 108.34 108.26 108.76 110.20 112.51 91.88 92.53 130.15 125.18 91.63 92.60 92.64 91.82 90.29 88.27 86.08 84.04 82.49 81.70 81.80 82.77 84.44 86.53 88.71 90.64 92.05 129.14 134.59 139.48 143.12 148.33 155.31 160.07 162.36 162.10 159.35 154.33 147.39 139.11 130.29 123.37 120.61 Vc (kV) 123.89 125.05 125.00 124.14 123.11 122.81 124.06 127.09 131.26 93.85 94.48 94.04 173.17 93.05 94.42 97.03 99.85 101.95 102.72 101.82 99.09 98.37 96.63 93.94 93.51 92.10 90.49 90.30 91.88 93.96 132.65 137.10 140.71 142.84 143.03 141.04 136.76 130.26 121.70 116.73 119.25 123.21 125.65 126.61 126.34 125.26 124.08 123.75 125.09 128.29 132.63 94.27 94.84 94.33 175.56 93.27 94.67 97.35 100.25 102.40 103.23 102.37 99.67 99.11 97.30 94.68 94.15 92.58 91.03 90.73 92.35 94.38 139.41 144.57 148.69 151.08 151.32 149.16 144.50 137.43 128.13 127.37 130.15 133.59 135.07 134.79 133.16 130.85 128.83 128.30 130.13 134.17 139.38 96.14 96.41 188.72 187.32 94.18 95.77 98.77 102.00 104.47 105.55 104.89 103.72 103.38 101.33 99.37 98.35 96.01 94.69 93.73 94.44 96.25 145.69 151.55 156.19 158.89 159.22 156.93 151.95 145.50 148.43 149.20 147.89 144.87 144.96 143.10 139.86 136.13 Ratio V Max (kV) Vmax/Vnom 123.89 2.30 125.05 2.32 125.00 2.32 124.14 2.30 123.11 2.28 122.81 2.28 124.06 2.30 127.09 2.36 131.26 2.44 105.15 1.95 105.88 1.96 105.60 1.96 173.17 3.21 104.61 1.94 105.73 1.96 105.80 1.96 104.91 1.95 103.22 1.92 102.72 1.91 101.82 1.89 99.09 1.84 98.37 1.83 96.63 1.79 93.94 1.74 94.69 1.76 96.59 1.79 98.96 1.84 101.41 1.88 103.59 1.92 105.16 1.95 132.65 2.46 137.10 2.54 140.71 2.61 142.84 2.65 143.03 2.65 141.04 2.62 136.76 2.54 130.26 2.42 126.12 2.34 125.22 2.32 122.80 2.28 123.21 2.29 125.65 2.33 126.61 2.35 126.34 2.34 125.26 2.32 124.08 2.30 123.75 2.30 125.09 2.32 128.29 2.38 132.63 2.46 105.57 1.96 106.17 1.97 105.76 1.96 175.56 3.26 104.68 1.94 105.92 1.97 106.12 1.97 105.35 1.95 103.77 1.93 103.23 1.92 102.37 1.90 99.67 1.85 99.11 1.84 97.30 1.81 94.68 1.76 95.54 1.77 97.39 1.81 99.68 1.85 102.05 1.89 104.12 1.93 105.58 1.96 139.41 2.59 144.57 2.68 148.69 2.76 151.08 2.80 151.32 2.81 149.16 2.77 144.50 2.68 143.39 2.66 143.67 2.67 141.90 2.63 138.23 2.57 133.59 2.48 135.07 2.51 134.79 2.50 133.16 2.47 130.85 2.43 128.83 2.39 128.30 2.38 130.13 2.41 134.17 2.49 139.38 2.59 107.58 2.00 107.56 2.00 188.72 3.50 187.32 3.48 104.90 1.95 106.78 1.98 107.63 2.00 107.50 1.99 106.53 1.98 105.55 1.96 104.89 1.95 103.72 1.92 103.38 1.92 101.33 1.88 99.37 1.84 99.64 1.85 101.25 1.88 103.22 1.92 105.16 1.95 106.72 1.98 107.60 2.00 145.69 2.70 151.55 2.81 156.19 2.90 158.89 2.95 159.22 2.95 156.93 2.91 160.07 2.97 162.36 3.01 162.10 3.01 159.35 2.96 154.33 2.86 147.39 2.74 144.96 2.69 143.10 2.66 139.86 2.60 136.13 2.53 Simulation 3 Variables Simulation 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 198765 Start-Delay (s) 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 3.1500 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g #NAME? Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 63 NER Size (Ohm) Va (kV) 550 404.66 550 404.63 550 404.64 550 404.69 550 404.78 550 121.28 550 218.98 550 218.98 550 218.96 550 218.92 550 218.88 550 120.82 550 120.82 550 120.81 550 120.79 550 120.77 550 120.75 550 120.76 550 120.78 550 120.82 550 120.89 550 120.96 550 121.05 550 121.14 550 121.21 550 121.27 1000 451.99 1000 452.19 1000 452.44 1000 452.72 1000 452.99 1000 453.26 1000 453.48 1000 453.65 1000 453.74 1000 453.75 1000 453.68 1000 453.54 1000 453.35 1000 453.14 1000 452.01 1000 451.89 1000 451.80 1000 451.75 1000 451.76 1000 451.84 1000 451.98 1000 121.13 1000 226.53 1000 226.54 1000 226.52 1000 226.48 1000 226.44 1000 120.53 1000 120.53 1000 120.50 1000 120.47 1000 120.44 1000 120.43 1000 120.43 1000 120.46 1000 120.52 1000 120.60 1000 120.71 1000 120.83 1000 120.94 1000 121.04 1000 121.12 1E+06 523.78 1E+06 524.13 1E+06 524.55 1E+06 525.00 1E+06 525.44 1E+06 525.83 1E+06 526.14 1E+06 526.33 1E+06 526.39 1E+06 526.31 1E+06 526.09 1E+06 525.77 1E+06 525.37 1E+06 524.15 1E+06 523.89 1E+06 523.65 1E+06 523.47 1E+06 523.38 1E+06 523.40 1E+06 523.54 1E+06 523.79 1E+06 120.82 1E+06 236.68 1E+06 236.69 1E+06 236.67 1E+06 236.63 1E+06 236.58 1E+06 120.03 1E+06 120.01 1E+06 119.97 1E+06 119.92 1E+06 119.88 1E+06 119.85 1E+06 119.85 1E+06 119.89 1E+06 119.96 1E+06 120.08 1E+06 120.23 1E+06 120.39 1E+06 120.55 1E+06 120.70 1E+06 120.81 4E+07 93833.05 Vb (kV) 267.54 267.51 267.52 267.55 267.62 104.91 175.97 175.95 175.92 175.90 175.88 105.53 105.55 105.56 105.56 105.53 105.49 105.43 105.35 105.26 105.18 105.09 105.01 104.95 104.90 104.87 310.12 310.25 310.40 310.57 310.75 310.93 311.09 311.22 311.31 311.35 311.35 311.30 311.22 311.10 310.14 310.06 310.01 309.98 309.99 310.03 310.12 105.43 187.06 187.03 186.99 186.96 186.94 106.23 106.25 106.25 106.24 106.20 106.14 106.05 105.95 105.84 105.72 105.62 105.53 105.46 105.42 105.39 381.91 382.15 382.43 382.75 383.06 383.34 383.58 383.74 383.82 383.80 383.70 383.51 383.27 382.15 381.97 381.80 381.68 381.63 381.64 381.73 381.90 106.17 203.01 202.97 202.92 202.87 202.85 107.29 107.31 107.30 107.27 107.20 107.10 106.98 106.83 106.68 106.53 106.40 106.29 106.21 106.16 106.14 85603.89 Vc (kV) 390.05 390.01 390.02 390.08 390.18 166.91 172.48 172.50 172.50 172.47 172.42 160.06 160.96 162.01 162.87 165.47 168.15 170.63 172.68 174.08 174.70 174.47 173.44 171.70 169.44 166.90 422.14 422.35 422.58 422.82 423.03 423.21 423.32 423.36 423.31 423.24 423.10 422.91 422.69 422.46 422.24 422.05 421.92 421.86 421.87 421.96 422.11 168.80 174.26 174.30 174.30 174.28 174.23 161.69 162.63 163.74 164.80 167.53 170.33 172.91 175.03 176.46 177.07 176.80 175.69 173.85 171.46 168.79 469.64 469.94 470.28 470.65 471.00 471.29 471.48 471.57 471.53 471.38 471.11 470.76 470.36 470.06 469.82 469.60 469.44 469.36 469.38 469.50 469.72 171.09 176.60 176.67 176.69 176.66 176.62 163.62 164.64 165.82 166.99 169.89 172.86 175.58 177.80 179.29 179.91 179.59 178.40 176.44 173.91 171.08 120491.21 V Max (kV) 404.66 404.63 404.64 404.69 404.78 166.91 218.98 218.98 218.96 218.92 218.88 160.06 160.96 162.01 162.87 165.47 168.15 170.63 172.68 174.08 174.70 174.47 173.44 171.70 169.44 166.90 451.99 452.19 452.44 452.72 452.99 453.26 453.48 453.65 453.74 453.75 453.68 453.54 453.35 453.14 452.01 451.89 451.80 451.75 451.76 451.84 451.98 168.80 226.53 226.54 226.52 226.48 226.44 161.69 162.63 163.74 164.80 167.53 170.33 172.91 175.03 176.46 177.07 176.80 175.69 173.85 171.46 168.79 523.78 524.13 524.55 525.00 525.44 525.83 526.14 526.33 526.39 526.31 526.09 525.77 525.37 524.15 523.89 523.65 523.47 523.38 523.40 523.54 523.79 171.09 236.68 236.69 236.67 236.63 236.58 163.62 164.64 165.82 166.99 169.89 172.86 175.58 177.80 179.29 179.91 179.59 178.40 176.44 173.91 171.08 123384.60 Line Length=10km Ratio Vmax/Vnom 7.51 7.51 7.51 7.51 7.51 3.10 4.06 4.06 4.06 4.06 4.06 2.97 2.99 3.01 3.02 3.07 3.12 3.17 3.20 3.23 3.24 3.24 3.22 3.19 3.14 3.10 8.39 8.39 8.40 8.40 8.41 8.41 8.42 8.42 8.42 8.42 8.42 8.42 8.41 8.41 8.39 8.39 8.38 8.38 8.38 8.38 8.39 3.13 4.20 4.20 4.20 4.20 4.20 3.00 3.02 3.04 3.06 3.11 3.16 3.21 3.25 3.27 3.29 3.28 3.26 3.23 3.18 3.13 9.72 9.73 9.73 9.74 9.75 9.76 9.76 9.77 9.77 9.77 9.76 9.76 9.75 9.73 9.72 9.72 9.71 9.71 9.71 9.72 9.72 3.17 4.39 4.39 4.39 4.39 4.39 3.04 3.06 3.08 3.10 3.15 3.21 3.26 3.30 3.33 3.34 3.33 3.31 3.27 3.23 3.17 2289.61 Va (kV) 115.02 114.97 115.08 115.25 115.35 105.20 105.42 105.57 179.57 105.94 105.85 105.81 105.86 106.00 106.19 106.35 106.40 106.28 106.00 105.61 105.20 104.88 104.72 104.75 104.92 105.17 121.89 121.75 121.15 120.04 118.43 116.43 114.26 112.26 122.69 123.65 124.12 124.10 123.68 122.99 122.23 121.57 121.18 121.09 121.26 121.52 121.67 105.09 105.38 105.55 189.13 105.93 105.84 105.82 105.90 106.10 106.35 106.57 106.64 106.48 106.13 105.63 105.11 104.70 104.51 104.55 104.76 105.06 131.61 131.41 130.48 128.70 126.07 122.73 119.13 134.26 135.52 136.13 136.26 136.01 135.11 133.80 132.40 131.21 130.50 130.35 130.64 131.11 131.40 104.91 105.29 105.52 202.20 105.91 105.82 105.82 105.96 106.25 106.61 106.91 107.01 106.82 106.35 105.68 104.99 104.44 104.17 104.21 104.49 104.88 57831.31 Vb (kV) 123.42 122.99 124.02 127.87 133.93 86.43 86.28 86.14 139.34 86.68 86.69 86.70 86.71 86.74 86.80 86.88 86.96 87.05 87.11 87.13 87.09 87.00 86.89 86.75 86.60 86.46 135.41 143.04 150.85 157.92 163.56 167.28 168.81 167.99 164.84 159.51 152.30 143.98 140.24 135.79 131.31 127.59 125.35 124.88 125.80 129.36 135.67 86.71 86.58 86.44 153.92 87.02 87.03 87.03 87.06 87.10 87.18 87.28 87.39 87.48 87.54 87.53 87.46 87.34 87.19 87.04 86.89 86.75 137.59 145.53 153.62 160.91 166.70 170.50 172.04 171.15 167.87 162.34 154.87 149.05 144.78 139.75 134.71 130.52 129.09 129.00 129.13 131.22 137.84 87.08 86.97 86.84 175.84 87.47 87.48 87.49 87.52 87.60 87.72 87.87 88.02 88.12 88.16 88.10 87.96 87.78 87.58 87.40 87.24 87.12 60492.27 Vc (kV) 143.23 142.50 144.39 148.24 152.85 105.46 104.00 101.83 198.80 99.11 100.18 102.50 105.00 106.74 107.15 105.88 102.78 97.80 95.15 93.53 92.35 95.75 100.76 104.01 105.50 105.37 153.52 157.78 160.72 161.74 160.47 156.73 154.68 152.62 158.74 162.56 164.07 163.35 160.69 156.57 151.71 147.09 143.90 143.14 145.08 149.00 153.69 105.67 104.17 101.96 200.15 99.20 100.29 102.64 105.17 106.95 107.38 106.13 103.04 98.34 95.85 94.12 92.82 95.99 101.01 104.25 105.72 105.58 154.55 158.90 161.90 162.95 161.68 160.30 159.57 156.72 161.24 164.95 166.27 165.33 162.41 158.00 152.87 148.03 144.71 143.92 145.92 149.94 154.73 105.91 104.37 102.12 201.83 99.31 100.41 102.80 105.37 107.19 107.65 106.43 103.36 99.37 96.87 95.01 93.55 96.28 101.31 104.54 106.00 105.82 70313.61 Ratio V Max (kV) Vmax/Vnom 143.23 2.66 142.50 2.64 144.39 2.68 148.24 2.75 152.85 2.84 105.46 1.96 105.42 1.96 105.57 1.96 198.80 3.69 105.94 1.97 105.85 1.96 105.81 1.96 105.86 1.96 106.74 1.98 107.15 1.99 106.35 1.97 106.40 1.97 106.28 1.97 106.00 1.97 105.61 1.96 105.20 1.95 104.88 1.95 104.72 1.94 104.75 1.94 105.50 1.96 105.37 1.96 153.52 2.85 157.78 2.93 160.72 2.98 161.74 3.00 163.56 3.04 167.28 3.10 168.81 3.13 167.99 3.12 164.84 3.06 162.56 3.02 164.07 3.04 163.35 3.03 160.69 2.98 156.57 2.91 151.71 2.82 147.09 2.73 143.90 2.67 143.14 2.66 145.08 2.69 149.00 2.76 153.69 2.85 105.67 1.96 105.38 1.96 105.55 1.96 200.15 3.71 105.93 1.97 105.84 1.96 105.82 1.96 105.90 1.97 106.95 1.98 107.38 1.99 106.57 1.98 106.64 1.98 106.48 1.98 106.13 1.97 105.63 1.96 105.11 1.95 104.70 1.94 104.51 1.94 104.55 1.94 105.72 1.96 105.58 1.96 154.55 2.87 158.90 2.95 161.90 3.00 162.95 3.02 166.70 3.09 170.50 3.16 172.04 3.19 171.15 3.18 167.87 3.12 164.95 3.06 166.27 3.09 165.33 3.07 162.41 3.01 158.00 2.93 152.87 2.84 148.03 2.75 144.71 2.69 143.92 2.67 145.92 2.71 149.94 2.78 154.73 2.87 105.91 1.97 105.29 1.95 105.52 1.96 202.20 3.75 105.91 1.97 105.82 1.96 105.82 1.96 105.96 1.97 107.19 1.99 107.65 2.00 106.91 1.98 107.01 1.99 106.82 1.98 106.35 1.97 105.68 1.96 104.99 1.95 104.44 1.94 104.17 1.93 104.54 1.94 106.00 1.97 105.82 1.96 72715.63 1349.36 Line Length=0.2km Va (kV) 104.51 104.48 104.67 105.20 106.07 109.67 109.03 181.85 181.13 104.85 107.38 108.95 109.73 109.75 108.93 107.29 105.22 103.32 102.18 102.08 102.97 104.56 106.42 108.14 109.32 109.70 115.48 117.12 118.66 119.75 120.15 119.69 118.31 117.07 117.63 106.43 106.40 108.56 110.64 112.12 112.92 113.16 113.09 113.04 113.35 114.23 115.63 109.91 109.21 190.86 189.88 104.80 107.40 109.06 109.99 110.20 109.52 107.91 105.74 103.70 102.44 102.29 103.19 104.81 106.70 108.43 109.61 109.95 130.27 133.17 135.88 137.91 138.87 138.52 138.19 136.75 134.16 114.14 114.12 118.69 122.24 124.57 125.74 125.99 125.77 125.67 126.27 127.89 130.41 110.20 109.43 203.04 201.71 104.71 107.39 109.18 110.33 110.82 110.35 108.76 106.42 104.15 102.69 102.46 103.37 105.05 107.01 108.77 109.95 110.25 57498.23 Vb (kV) 119.40 119.04 120.53 124.14 129.20 98.09 97.25 139.78 137.53 93.59 96.12 97.68 98.32 98.15 97.29 96.01 94.65 93.58 93.06 93.19 93.93 95.07 96.37 97.52 98.23 98.26 131.61 137.45 142.68 146.60 150.36 157.43 162.23 164.51 164.19 161.33 156.14 149.01 140.52 131.47 126.18 122.87 121.03 120.62 122.27 126.20 131.66 99.18 98.07 150.45 151.39 93.90 96.70 98.54 99.47 99.55 98.92 97.78 96.50 95.47 94.98 95.13 95.84 96.92 98.09 99.07 99.57 99.36 134.90 141.26 146.95 151.23 153.58 160.10 164.95 167.21 166.80 163.80 158.42 151.05 142.27 134.39 130.16 126.24 123.65 123.09 124.59 128.95 134.94 100.68 99.20 171.53 171.85 94.30 97.49 99.72 101.05 101.53 101.22 100.27 99.06 98.07 97.60 97.77 98.45 99.44 100.45 101.20 101.41 100.86 61339.80 Vc (kV) 133.17 132.44 134.75 139.60 145.65 97.56 97.58 200.21 198.36 94.77 96.52 99.80 103.34 106.09 107.41 106.93 108.44 108.25 106.16 105.63 104.30 101.35 100.38 98.71 96.05 97.68 146.35 152.30 156.99 159.72 160.06 157.76 152.76 148.99 151.90 152.56 151.02 147.53 146.07 144.02 140.59 136.69 133.63 132.87 135.23 140.17 146.32 97.69 97.68 201.44 199.54 94.82 96.58 99.90 103.47 106.25 107.59 107.33 108.98 108.81 106.72 106.42 105.06 102.05 101.17 99.41 96.51 97.81 147.17 153.22 157.98 160.76 161.12 158.81 153.76 153.68 156.56 157.04 155.22 151.32 147.46 145.17 141.50 137.39 134.19 133.41 135.83 140.88 147.14 97.85 97.81 202.95 201.00 94.87 96.66 100.01 103.62 106.44 107.81 107.94 109.65 109.51 107.43 107.42 106.04 102.97 102.18 100.32 97.28 97.97 69216.59 Ratio V Max (kV) Vmax/Vnom 133.17 2.47 132.44 2.46 134.75 2.50 139.60 2.59 145.65 2.70 109.67 2.04 109.03 2.02 200.21 3.72 198.36 3.68 104.85 1.95 107.38 1.99 108.95 2.02 109.73 2.04 109.75 2.04 108.93 2.02 107.29 1.99 108.44 2.01 108.25 2.01 106.16 1.97 105.63 1.96 104.30 1.94 104.56 1.94 106.42 1.97 108.14 2.01 109.32 2.03 109.70 2.04 146.35 2.72 152.30 2.83 156.99 2.91 159.72 2.96 160.06 2.97 157.76 2.93 162.23 3.01 164.51 3.05 164.19 3.05 161.33 2.99 156.14 2.90 149.01 2.77 146.07 2.71 144.02 2.67 140.59 2.61 136.69 2.54 133.63 2.48 132.87 2.47 135.23 2.51 140.17 2.60 146.32 2.72 109.91 2.04 109.21 2.03 201.44 3.74 199.54 3.70 104.80 1.94 107.40 1.99 109.06 2.02 109.99 2.04 110.20 2.04 109.52 2.03 107.91 2.00 108.98 2.02 108.81 2.02 106.72 1.98 106.42 1.97 105.06 1.95 104.81 1.94 106.70 1.98 108.43 2.01 109.61 2.03 109.95 2.04 147.17 2.73 153.22 2.84 157.98 2.93 160.76 2.98 161.12 2.99 160.10 2.97 164.95 3.06 167.21 3.10 166.80 3.10 163.80 3.04 158.42 2.94 151.32 2.81 147.46 2.74 145.17 2.69 141.50 2.63 137.39 2.55 134.19 2.49 133.41 2.48 135.83 2.52 140.88 2.61 147.14 2.73 110.20 2.04 109.43 2.03 203.04 3.77 201.71 3.74 104.71 1.94 107.39 1.99 109.18 2.03 110.33 2.05 110.82 2.06 110.35 2.05 108.76 2.02 109.65 2.03 109.51 2.03 107.43 1.99 107.42 1.99 106.04 1.97 105.05 1.95 107.01 1.99 108.77 2.02 109.95 2.04 110.25 2.05 72407.43 1343.64 Simulation 4 Variables Simulation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 Start-Delay (s) 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Va (kV) 60.18 60.30 60.74 61.94 62.50 63.42 63.73 64.16 64.00 63.88 63.34 62.79 62.15 61.44 61.04 60.57 60.40 60.39 60.41 60.78 60.19 67.16 67.70 68.26 68.42 69.10 68.98 64.07 64.59 64.66 65.14 64.43 64.08 63.29 62.84 62.95 63.51 64.03 64.70 65.23 66.35 67.18 76.26 76.23 76.21 76.23 76.07 76.08 76.09 76.07 76.05 76.07 76.11 76.14 76.17 76.21 76.23 76.26 76.27 76.27 76.26 76.25 76.23 92.12 88.78 85.17 81.48 77.16 73.09 68.38 67.87 94.87 97.71 99.84 101.16 101.85 102.23 102.20 101.78 101.03 99.64 97.41 94.49 92.12 98.54 98.48 98.42 98.02 98.00 98.01 98.03 98.04 98.09 98.16 98.25 98.33 98.41 98.48 98.55 98.59 98.62 98.63 98.61 98.57 98.52 100.04 96.41 92.37 88.17 82.99 78.35 77.19 76.31 75.04 105.97 108.03 109.20 Vb (kV) 66.37 66.78 65.54 62.70 58.30 56.59 57.53 58.52 58.74 59.50 59.34 59.32 58.98 58.81 58.04 57.87 57.27 57.37 60.75 64.37 66.40 60.10 60.54 60.22 60.34 59.58 59.48 57.01 56.99 57.06 57.51 57.59 57.68 57.78 57.84 57.85 57.79 57.77 59.06 59.34 60.24 60.13 72.26 73.90 73.72 71.73 67.96 62.76 62.73 62.70 62.66 62.63 62.60 62.57 64.07 65.04 66.08 66.66 66.96 67.06 67.57 68.89 72.30 74.23 72.49 71.42 70.87 69.32 68.68 68.43 68.01 74.99 76.32 76.33 77.19 77.35 77.27 77.23 77.23 76.97 76.09 76.04 74.68 74.23 77.01 79.61 80.26 78.92 76.67 76.58 76.50 76.42 76.37 76.32 76.30 76.28 76.28 76.29 76.30 76.31 76.32 76.32 76.54 76.84 77.05 87.68 86.15 83.75 82.24 80.51 78.05 79.70 78.09 77.67 91.54 92.12 92.74 Vc (kV) 61.03 61.37 61.12 61.24 61.57 61.96 62.90 62.96 67.69 71.46 73.46 73.67 72.06 68.67 63.59 61.44 61.10 60.95 61.26 61.48 61.02 57.25 57.75 58.19 58.80 59.03 59.57 61.50 61.42 61.87 61.87 66.98 70.44 72.17 72.13 70.31 66.76 61.57 57.50 57.33 57.15 57.24 94.19 94.03 94.14 94.07 93.52 93.26 92.89 92.33 92.99 93.45 93.67 94.05 94.16 94.05 94.10 94.04 93.93 93.95 93.93 94.08 94.21 79.95 79.69 79.16 78.79 78.67 78.38 78.70 79.02 79.30 79.47 79.60 79.67 81.21 81.22 79.99 80.14 80.27 80.28 80.31 80.17 79.98 103.68 103.71 103.51 102.84 102.48 101.86 101.38 101.94 102.40 102.82 103.32 103.59 103.69 103.88 103.90 103.83 103.86 103.84 103.87 103.90 103.70 84.33 84.05 83.63 82.97 82.87 83.15 83.58 83.80 83.95 84.32 84.59 85.72 V Max (kV) 66.37 66.78 65.54 62.70 62.50 63.42 63.73 64.16 67.69 71.46 73.46 73.67 72.06 68.67 63.59 61.44 61.10 60.95 61.26 64.37 66.40 67.16 67.70 68.26 68.42 69.10 68.98 64.07 64.59 64.66 65.14 66.98 70.44 72.17 72.13 70.31 66.76 64.03 64.70 65.23 66.35 67.18 94.19 94.03 94.14 94.07 93.52 93.26 92.89 92.33 92.99 93.45 93.67 94.05 94.16 94.05 94.10 94.04 93.93 93.95 93.93 94.08 94.21 92.12 88.78 85.17 81.48 78.67 78.38 78.70 79.02 94.87 97.71 99.84 101.16 101.85 102.23 102.20 101.78 101.03 99.64 97.41 94.49 92.12 103.68 103.71 103.51 102.84 102.48 101.86 101.38 101.94 102.40 102.82 103.32 103.59 103.69 103.88 103.90 103.83 103.86 103.84 103.87 103.90 103.70 100.04 96.41 92.37 88.17 82.99 83.15 83.58 83.80 83.95 105.97 108.03 109.20 Line Length=10km Ratio Vmax/Vnom 1.23 1.24 1.22 1.16 1.16 1.18 1.18 1.19 1.26 1.33 1.36 1.37 1.34 1.27 1.18 1.14 1.13 1.13 1.14 1.19 1.23 1.25 1.26 1.27 1.27 1.28 1.28 1.19 1.20 1.20 1.21 1.24 1.31 1.34 1.34 1.30 1.24 1.19 1.20 1.21 1.23 1.25 1.75 1.74 1.75 1.75 1.74 1.73 1.72 1.71 1.73 1.73 1.74 1.75 1.75 1.75 1.75 1.75 1.74 1.74 1.74 1.75 1.75 1.71 1.65 1.58 1.51 1.46 1.45 1.46 1.47 1.76 1.81 1.85 1.88 1.89 1.90 1.90 1.89 1.87 1.85 1.81 1.75 1.71 1.92 1.92 1.92 1.91 1.90 1.89 1.88 1.89 1.90 1.91 1.92 1.92 1.92 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.92 1.86 1.79 1.71 1.64 1.54 1.54 1.55 1.56 1.56 1.97 2.00 2.03 Va (kV) 68.35 71.09 72.92 68.86 69.59 68.99 69.61 70.82 70.65 71.78 73.03 73.34 72.30 69.86 66.79 63.86 61.82 61.35 62.62 65.26 68.34 66.55 68.95 65.05 67.39 68.80 68.92 67.48 67.00 68.28 71.11 72.48 73.00 73.89 72.58 65.87 65.00 63.77 61.96 60.79 62.95 66.47 68.16 68.16 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 68.14 102.88 100.56 97.09 92.48 86.78 80.15 67.99 65.09 67.33 104.59 104.29 103.66 102.99 102.55 102.58 103.02 103.67 104.28 104.53 104.14 102.85 61.78 61.78 61.78 61.78 61.77 61.77 61.77 61.78 61.78 61.79 61.79 61.79 61.78 61.78 61.78 61.78 61.78 61.78 61.78 61.69 61.69 107.74 105.34 101.51 96.26 81.02 65.03 66.49 66.14 64.36 62.33 108.08 107.00 Vb (kV) 67.46 69.59 69.96 68.57 67.31 66.50 68.49 70.67 71.39 70.62 68.43 64.92 60.30 59.94 59.81 59.28 58.72 58.56 58.97 63.65 67.34 70.73 71.06 70.58 71.81 71.29 69.98 67.78 64.61 62.08 62.37 62.01 61.70 62.03 64.85 66.36 67.18 68.43 68.68 67.70 68.49 70.67 68.23 70.56 71.10 69.86 66.88 67.95 68.28 67.32 65.09 61.68 63.21 65.71 66.91 66.88 65.81 64.16 62.80 62.57 62.44 64.20 68.12 67.30 70.08 71.52 70.85 68.56 65.91 63.55 61.22 59.58 64.20 63.41 63.12 63.10 63.15 63.15 63.12 63.19 63.54 64.34 65.59 67.34 76.60 77.94 82.19 86.04 88.89 90.42 90.45 88.94 85.92 81.53 76.35 77.15 77.76 77.93 77.72 77.33 77.04 76.99 77.04 76.97 76.61 67.20 68.48 68.77 68.27 70.37 67.21 62.81 59.94 57.45 58.28 64.02 63.25 Vc (kV) 58.89 59.15 60.52 64.78 67.98 69.94 70.54 69.73 67.52 64.47 66.74 68.56 68.69 67.13 63.93 59.16 58.70 58.62 58.80 58.81 58.81 65.83 62.02 72.20 72.37 71.21 68.89 66.07 65.21 65.12 64.33 62.33 66.65 70.29 72.21 72.37 70.75 67.40 67.73 68.06 67.83 65.82 97.26 97.44 100.61 103.04 104.06 103.35 100.79 97.46 96.88 96.08 96.02 99.20 101.53 102.43 102.16 101.23 100.46 100.32 100.23 99.36 97.40 85.40 82.91 83.18 86.03 88.91 91.04 92.01 91.58 89.63 86.17 81.20 80.86 81.30 81.72 82.57 82.70 84.24 84.56 85.94 86.54 85.41 110.19 112.96 115.90 117.73 117.88 116.06 112.16 107.93 108.11 111.06 114.14 115.76 115.95 114.93 113.17 111.48 110.64 110.54 110.36 109.84 110.30 91.45 88.28 88.58 91.22 93.84 113.91 105.18 95.73 93.36 89.62 85.66 86.44 Ratio V Max (kV) Vmax/Vnom 68.35 1.27 71.09 1.32 72.92 1.35 68.86 1.28 69.59 1.29 69.94 1.30 70.54 1.31 70.82 1.31 71.39 1.32 71.78 1.33 73.03 1.36 73.34 1.36 72.30 1.34 69.86 1.30 66.79 1.24 63.86 1.19 61.82 1.15 61.35 1.14 62.62 1.16 65.26 1.21 68.34 1.27 70.73 1.31 71.06 1.32 72.20 1.34 72.37 1.34 71.29 1.32 69.98 1.30 67.78 1.26 67.00 1.24 68.28 1.27 71.11 1.32 72.48 1.35 73.00 1.35 73.89 1.37 72.58 1.35 72.37 1.34 70.75 1.31 68.43 1.27 68.68 1.27 68.06 1.26 68.49 1.27 70.67 1.31 97.26 1.80 97.44 1.81 100.61 1.87 103.04 1.91 104.06 1.93 103.35 1.92 100.79 1.87 97.46 1.81 96.88 1.80 96.08 1.78 96.02 1.78 99.20 1.84 101.53 1.88 102.43 1.90 102.16 1.90 101.23 1.88 100.46 1.86 100.32 1.86 100.23 1.86 99.36 1.84 97.40 1.81 102.88 1.91 100.56 1.87 97.09 1.80 92.48 1.72 88.91 1.65 91.04 1.69 92.01 1.71 91.58 1.70 89.63 1.66 104.59 1.94 104.29 1.94 103.66 1.92 102.99 1.91 102.55 1.90 102.58 1.90 103.02 1.91 103.67 1.92 104.28 1.94 104.53 1.94 104.14 1.93 102.85 1.91 110.19 2.04 112.96 2.10 115.90 2.15 117.73 2.18 117.88 2.19 116.06 2.15 112.16 2.08 107.93 2.00 108.11 2.01 111.06 2.06 114.14 2.12 115.76 2.15 115.95 2.15 114.93 2.13 113.17 2.10 111.48 2.07 110.64 2.05 110.54 2.05 110.36 2.05 109.84 2.04 110.30 2.05 107.74 2.00 105.34 1.95 101.51 1.88 96.26 1.79 93.84 1.74 113.91 2.11 105.18 1.95 95.73 1.78 93.36 1.73 89.62 1.66 108.08 2.01 107.00 1.99 Line Length=0.2km Va (kV) 73.26 77.75 67.12 68.28 70.67 71.91 72.40 76.98 80.60 83.29 83.62 81.99 79.53 75.50 70.65 66.12 62.78 61.95 64.03 68.27 73.22 68.52 72.17 75.17 80.31 77.80 72.70 73.28 74.46 80.02 82.80 84.34 84.41 80.22 76.87 75.08 66.11 63.34 65.79 66.82 66.54 68.50 75.15 75.15 75.13 75.13 75.13 75.14 75.14 75.14 75.13 75.13 75.13 75.14 75.14 75.14 75.13 75.13 75.13 75.13 75.13 75.14 75.14 109.27 107.27 104.03 99.54 93.92 87.31 72.72 74.84 71.69 109.88 109.18 108.24 107.45 106.98 107.03 107.54 108.37 109.29 110.00 110.12 109.27 66.13 66.13 66.13 66.14 66.14 66.14 66.14 66.14 66.13 66.13 66.13 66.13 66.13 66.14 66.14 66.14 66.14 66.14 66.14 66.03 66.03 113.46 111.12 107.36 102.20 89.11 64.82 65.00 66.40 68.36 68.60 113.52 112.57 Vb (kV) 65.71 67.41 67.43 65.82 67.24 69.64 70.52 69.81 67.57 70.36 71.61 71.27 69.35 66.50 63.51 60.72 58.79 58.35 59.48 62.23 65.67 76.94 78.22 81.89 90.35 85.62 75.80 72.47 68.24 65.25 68.19 70.75 72.67 71.61 68.48 72.40 77.12 81.75 66.87 70.28 73.94 76.98 68.29 67.87 67.98 66.44 65.39 65.40 65.40 65.89 69.85 72.17 72.86 72.00 69.66 66.57 67.99 68.00 67.01 66.60 67.82 68.72 68.37 74.39 69.59 65.55 67.47 71.08 72.69 64.24 69.76 66.87 76.66 75.71 75.17 74.84 74.76 74.75 74.69 74.97 75.96 77.29 77.35 74.42 79.79 78.71 76.02 79.15 81.88 83.10 82.65 80.53 85.27 88.25 89.43 88.71 86.29 82.37 77.42 76.03 76.39 76.31 77.73 79.42 79.89 64.89 66.85 69.47 71.91 81.04 72.51 66.91 61.50 59.15 61.81 64.96 65.27 Vc (kV) 63.56 63.97 62.07 62.64 63.80 68.75 72.19 73.99 74.07 72.50 69.29 65.77 65.11 64.37 63.07 61.79 60.63 60.31 61.06 62.36 63.47 68.36 68.46 65.85 65.09 77.03 78.05 74.57 72.65 72.91 72.23 70.05 66.39 67.00 69.24 76.29 76.16 74.34 62.64 63.82 65.95 68.40 101.31 103.36 103.60 101.79 97.86 98.79 101.45 103.44 103.51 101.66 98.06 97.96 100.33 100.85 99.80 97.82 96.38 96.31 95.59 98.07 101.33 81.26 83.94 85.09 84.22 81.34 86.50 92.41 96.56 98.73 98.80 96.76 92.61 90.20 87.72 84.88 83.88 81.79 83.59 84.09 83.33 81.25 114.79 116.23 115.60 112.73 110.94 113.79 114.40 112.54 108.29 106.93 107.37 109.49 109.77 108.40 106.91 106.90 107.35 107.51 108.79 111.91 114.79 89.27 91.65 91.89 90.13 86.36 125.48 117.94 107.44 105.69 105.70 103.54 99.19 V Max (kV) 73.26 77.75 67.43 68.28 70.67 71.91 72.40 76.98 80.60 83.29 83.62 81.99 79.53 75.50 70.65 66.12 62.78 61.95 64.03 68.27 73.22 76.94 78.22 81.89 90.35 85.62 78.05 74.57 74.46 80.02 82.80 84.34 84.41 80.22 76.87 76.29 77.12 81.75 66.87 70.28 73.94 76.98 101.31 103.36 103.60 101.79 97.86 98.79 101.45 103.44 103.51 101.66 98.06 97.96 100.33 100.85 99.80 97.82 96.38 96.31 95.59 98.07 101.33 109.27 107.27 104.03 99.54 93.92 87.31 92.41 96.56 98.73 109.88 109.18 108.24 107.45 106.98 107.03 107.54 108.37 109.29 110.00 110.12 109.27 114.79 116.23 115.60 112.73 110.94 113.79 114.40 112.54 108.29 106.93 107.37 109.49 109.77 108.40 106.91 106.90 107.35 107.51 108.79 111.91 114.79 113.46 111.12 107.36 102.20 89.11 125.48 117.94 107.44 105.69 105.70 113.52 112.57 Ratio Vmax/Vnom 1.36 1.44 1.25 1.27 1.31 1.33 1.34 1.43 1.50 1.55 1.55 1.52 1.48 1.40 1.31 1.23 1.16 1.15 1.19 1.27 1.36 1.43 1.45 1.52 1.68 1.59 1.45 1.38 1.38 1.48 1.54 1.57 1.57 1.49 1.43 1.42 1.43 1.52 1.24 1.30 1.37 1.43 1.88 1.92 1.92 1.89 1.82 1.83 1.88 1.92 1.92 1.89 1.82 1.82 1.86 1.87 1.85 1.82 1.79 1.79 1.77 1.82 1.88 2.03 1.99 1.93 1.85 1.74 1.62 1.71 1.79 1.83 2.04 2.03 2.01 1.99 1.99 1.99 2.00 2.01 2.03 2.04 2.04 2.03 2.13 2.16 2.15 2.09 2.06 2.11 2.12 2.09 2.01 1.98 1.99 2.03 2.04 2.01 1.98 1.98 1.99 2.00 2.02 2.08 2.13 2.11 2.06 1.99 1.90 1.65 2.33 2.19 1.99 1.96 1.96 2.11 2.09 Simulation 4 Variables Simulation 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 Start-Delay (s) 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Va (kV) 109.96 110.61 110.58 109.87 109.06 107.78 105.61 102.63 100.03 120.31 120.21 119.61 119.56 119.51 119.50 119.51 119.55 119.63 119.72 119.84 119.97 120.09 120.22 120.33 120.40 120.45 120.46 120.43 120.37 120.29 103.05 99.27 95.98 91.50 86.91 85.45 86.14 84.76 83.57 108.74 110.66 111.78 112.49 113.03 113.00 112.40 111.62 110.38 108.33 105.46 103.05 139.41 139.25 138.60 138.51 138.44 138.41 138.42 138.45 138.54 138.67 138.80 138.97 139.15 139.31 139.45 139.55 139.61 139.62 139.58 139.50 139.39 104.27 100.91 97.72 94.68 91.68 91.99 94.85 93.09 91.66 109.78 111.62 112.76 113.45 113.99 113.96 113.35 112.59 111.33 109.36 106.81 104.26 156.41 156.24 155.54 155.40 155.33 155.29 155.25 155.31 155.41 155.53 155.72 155.92 156.09 156.29 156.46 156.59 156.66 156.68 156.63 156.53 156.39 104.83 102.76 101.81 Vb (kV) 93.35 93.46 93.38 93.10 92.35 91.61 90.88 88.98 87.67 90.36 90.27 91.13 91.02 90.89 90.76 90.65 90.56 90.48 90.42 90.40 90.39 90.40 90.42 90.44 90.47 90.49 90.49 90.48 90.44 90.38 99.49 96.59 94.74 92.04 89.19 86.81 88.53 86.67 85.92 103.41 104.20 105.06 105.21 105.25 105.13 104.90 104.53 103.47 102.56 100.99 99.48 103.16 103.01 104.12 103.96 103.78 103.61 103.46 103.33 103.24 103.18 103.15 103.15 103.18 103.23 103.28 103.33 103.36 103.37 103.34 103.28 103.17 108.78 106.40 102.58 99.86 97.91 95.57 96.47 94.38 93.40 114.30 115.43 116.17 116.85 117.02 116.88 116.44 115.48 114.54 113.16 111.12 108.76 115.73 115.55 116.77 116.57 116.37 116.18 116.00 115.86 115.76 115.70 115.67 115.69 115.74 115.80 115.87 115.93 115.98 115.98 115.95 115.87 115.74 116.71 114.00 111.05 Vc (kV) 87.04 87.05 84.91 84.33 84.52 84.65 84.68 84.63 84.36 105.75 105.39 105.22 104.83 103.99 103.56 103.74 103.95 104.42 104.78 105.10 105.46 105.65 105.71 105.83 105.86 105.84 105.86 105.82 105.84 105.78 85.27 84.99 84.58 83.97 84.13 84.39 84.81 85.03 85.16 86.20 87.38 88.60 90.83 90.83 88.58 85.20 85.38 85.53 85.59 85.59 85.30 106.02 105.75 105.28 104.96 104.68 104.78 104.92 105.08 105.24 105.40 105.55 105.68 105.92 106.02 106.10 106.19 106.19 106.20 106.18 106.09 106.04 85.63 85.30 84.90 84.32 84.68 84.91 85.31 85.53 85.67 86.93 88.69 91.07 93.33 93.30 90.97 86.40 85.65 85.80 85.89 85.89 85.65 106.25 105.99 105.67 105.29 105.28 105.35 105.45 105.58 105.72 105.87 106.01 106.14 106.26 106.37 106.46 106.53 106.58 106.59 106.55 106.45 106.27 85.79 85.44 85.03 V Max (kV) 109.96 110.61 110.58 109.87 109.06 107.78 105.61 102.63 100.03 120.31 120.21 119.61 119.56 119.51 119.50 119.51 119.55 119.63 119.72 119.84 119.97 120.09 120.22 120.33 120.40 120.45 120.46 120.43 120.37 120.29 103.05 99.27 95.98 92.04 89.19 86.81 88.53 86.67 85.92 108.74 110.66 111.78 112.49 113.03 113.00 112.40 111.62 110.38 108.33 105.46 103.05 139.41 139.25 138.60 138.51 138.44 138.41 138.42 138.45 138.54 138.67 138.80 138.97 139.15 139.31 139.45 139.55 139.61 139.62 139.58 139.50 139.39 108.78 106.40 102.58 99.86 97.91 95.57 96.47 94.38 93.40 114.30 115.43 116.17 116.85 117.02 116.88 116.44 115.48 114.54 113.16 111.12 108.76 156.41 156.24 155.54 155.40 155.33 155.29 155.25 155.31 155.41 155.53 155.72 155.92 156.09 156.29 156.46 156.59 156.66 156.68 156.63 156.53 156.39 116.71 114.00 111.05 Line Length=10km Ratio Vmax/Vnom 2.04 2.05 2.05 2.04 2.02 2.00 1.96 1.90 1.86 2.23 2.23 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.23 2.23 2.23 2.23 2.23 2.24 2.24 2.23 2.23 2.23 1.91 1.84 1.78 1.71 1.66 1.61 1.64 1.61 1.59 2.02 2.05 2.07 2.09 2.10 2.10 2.09 2.07 2.05 2.01 1.96 1.91 2.59 2.58 2.57 2.57 2.57 2.57 2.57 2.57 2.57 2.57 2.58 2.58 2.58 2.59 2.59 2.59 2.59 2.59 2.59 2.59 2.59 2.02 1.97 1.90 1.85 1.82 1.77 1.79 1.75 1.73 2.12 2.14 2.16 2.17 2.17 2.17 2.16 2.14 2.13 2.10 2.06 2.02 2.90 2.90 2.89 2.88 2.88 2.88 2.88 2.88 2.88 2.89 2.89 2.89 2.90 2.90 2.90 2.91 2.91 2.91 2.91 2.90 2.90 2.17 2.12 2.06 Va (kV) 106.06 105.56 105.63 106.20 107.14 108.18 108.88 108.84 107.72 60.58 60.58 60.57 60.57 60.58 60.58 60.59 60.59 60.59 60.59 60.58 60.58 60.58 60.57 60.58 60.58 60.58 60.58 60.53 60.53 60.53 110.67 108.26 76.98 79.10 69.84 68.76 66.24 63.61 62.06 60.74 60.85 108.70 107.63 107.16 107.25 107.86 108.97 110.32 111.37 111.60 110.64 60.71 60.71 60.71 60.71 60.71 60.72 60.72 60.72 60.72 60.71 60.71 60.70 60.70 60.70 60.71 60.71 60.71 60.71 60.71 60.71 60.71 112.61 76.26 76.57 70.92 70.29 68.38 65.67 62.80 62.39 62.19 61.99 109.72 108.60 108.19 108.30 108.88 110.09 111.66 112.96 113.42 112.58 60.06 60.06 60.06 60.06 60.07 60.07 60.07 60.07 60.06 60.06 60.05 60.05 60.05 60.05 60.05 60.09 60.09 60.09 60.09 60.09 60.09 113.95 76.07 70.06 Vb (kV) 62.65 62.32 62.34 62.67 63.28 64.04 64.69 65.05 67.19 88.68 92.61 96.98 100.73 103.30 104.36 103.75 101.44 97.52 92.17 88.31 88.72 88.71 88.32 87.73 87.44 87.40 87.42 87.18 87.03 88.78 67.24 68.44 71.01 71.79 71.03 63.38 60.06 57.36 56.73 57.25 59.93 66.43 65.84 65.50 65.52 65.89 66.47 67.01 67.20 66.76 67.18 97.23 101.67 106.20 109.89 112.23 112.91 111.81 108.92 104.35 98.37 95.15 95.04 94.48 93.61 93.42 93.43 93.64 93.69 93.59 94.35 97.31 68.36 68.66 71.00 83.66 76.38 67.34 57.91 56.99 58.17 58.43 58.94 66.66 66.12 65.79 65.81 66.17 66.70 67.10 67.06 66.41 68.28 102.87 107.65 112.28 115.92 118.09 118.50 117.03 113.71 108.69 102.30 99.66 99.09 98.04 96.84 96.92 97.29 97.65 97.71 97.82 99.30 102.95 70.06 68.78 92.98 Vc (kV) 87.37 87.95 89.18 90.84 91.32 92.63 94.02 93.60 91.48 116.89 120.19 123.13 124.73 124.46 122.09 117.52 112.24 116.95 120.41 122.34 122.70 121.66 119.60 117.18 115.34 114.63 114.54 114.52 114.89 116.95 93.48 90.08 90.55 93.07 126.14 118.55 109.48 100.11 94.06 90.15 88.10 88.99 89.73 90.33 92.63 93.93 93.95 96.15 97.06 96.12 93.52 120.66 124.25 127.20 128.66 128.15 125.44 120.48 118.00 122.43 125.30 126.51 126.10 124.35 121.73 119.07 117.31 116.70 116.62 116.79 117.89 120.70 94.41 90.91 91.49 134.63 128.72 120.87 111.74 102.56 95.18 90.21 89.42 90.34 90.95 92.24 94.47 95.58 95.41 97.91 98.54 97.32 94.46 123.04 126.80 129.76 131.13 130.46 127.53 122.30 121.54 125.69 128.15 128.87 127.97 125.77 122.86 120.13 118.50 117.95 117.87 118.21 119.81 123.06 94.91 91.38 140.23 Ratio V Max (kV) Vmax/Vnom 106.06 1.97 105.56 1.96 105.63 1.96 106.20 1.97 107.14 1.99 108.18 2.01 108.88 2.02 108.84 2.02 107.72 2.00 116.89 2.17 120.19 2.23 123.13 2.28 124.73 2.31 124.46 2.31 122.09 2.27 117.52 2.18 112.24 2.08 116.95 2.17 120.41 2.23 122.34 2.27 122.70 2.28 121.66 2.26 119.60 2.22 117.18 2.17 115.34 2.14 114.63 2.13 114.54 2.13 114.52 2.13 114.89 2.13 116.95 2.17 110.67 2.05 108.26 2.01 90.55 1.68 93.07 1.73 126.14 2.34 118.55 2.20 109.48 2.03 100.11 1.86 94.06 1.75 90.15 1.67 88.10 1.63 108.70 2.02 107.63 2.00 107.16 1.99 107.25 1.99 107.86 2.00 108.97 2.02 110.32 2.05 111.37 2.07 111.60 2.07 110.64 2.05 120.66 2.24 124.25 2.31 127.20 2.36 128.66 2.39 128.15 2.38 125.44 2.33 120.48 2.24 118.00 2.19 122.43 2.27 125.30 2.33 126.51 2.35 126.10 2.34 124.35 2.31 121.73 2.26 119.07 2.21 117.31 2.18 116.70 2.17 116.62 2.16 116.79 2.17 117.89 2.19 120.70 2.24 112.61 2.09 90.91 1.69 91.49 1.70 134.63 2.50 128.72 2.39 120.87 2.24 111.74 2.07 102.56 1.90 95.18 1.77 90.21 1.67 89.42 1.66 109.72 2.04 108.60 2.02 108.19 2.01 108.30 2.01 108.88 2.02 110.09 2.04 111.66 2.07 112.96 2.10 113.42 2.10 112.58 2.09 123.04 2.28 126.80 2.35 129.76 2.41 131.13 2.43 130.46 2.42 127.53 2.37 122.30 2.27 121.54 2.26 125.69 2.33 128.15 2.38 128.87 2.39 127.97 2.37 125.77 2.33 122.86 2.28 120.13 2.23 118.50 2.20 117.95 2.19 117.87 2.19 118.21 2.19 119.81 2.22 123.06 2.28 113.95 2.11 91.38 1.70 140.23 2.60 Line Length=0.2km Va (kV) 111.64 111.05 111.10 111.66 112.59 113.63 114.43 114.50 113.47 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.11 62.08 62.08 62.08 116.81 114.25 110.17 60.89 62.12 63.42 64.61 67.35 68.60 67.74 65.81 115.85 114.75 114.07 114.12 114.75 115.83 117.03 117.90 117.95 116.81 59.98 59.98 59.98 59.98 59.98 59.98 59.97 59.97 59.97 59.98 59.98 59.98 59.98 59.98 59.98 59.98 60.14 60.14 60.14 60.14 60.14 119.32 116.60 64.15 66.55 68.88 70.44 70.65 69.09 67.65 66.57 64.95 118.20 116.92 116.16 116.23 116.96 118.19 119.54 120.48 120.53 119.32 59.99 59.99 59.99 59.99 59.99 59.99 59.99 59.99 59.99 60.00 60.00 59.99 59.99 59.99 59.99 59.99 60.05 60.05 60.05 60.05 60.05 121.20 65.69 69.04 Vb (kV) 65.25 65.13 65.15 65.30 65.29 64.85 64.20 63.96 64.77 86.98 86.27 87.20 91.13 93.57 94.29 93.25 94.11 98.79 101.41 101.96 100.46 97.10 92.19 86.28 86.07 86.06 86.02 86.16 86.39 87.08 65.84 68.88 71.59 82.37 75.34 67.10 61.73 58.33 59.08 61.20 62.66 61.41 61.37 61.38 61.38 61.34 61.38 61.70 62.45 63.62 65.72 91.82 91.33 94.61 98.36 100.47 100.76 99.22 104.83 109.17 111.26 111.08 108.76 104.49 98.61 91.80 91.28 91.19 91.15 91.17 91.12 91.92 69.71 69.73 93.99 88.47 81.07 71.93 61.23 57.13 58.18 59.18 60.44 64.07 63.35 63.14 63.17 63.54 64.38 65.69 67.28 68.73 69.68 95.26 95.33 99.35 102.91 104.76 104.73 106.75 112.97 116.99 118.62 117.84 114.84 109.79 103.11 95.59 94.45 94.27 94.23 94.22 94.11 95.36 72.87 102.35 98.47 Vc (kV) 93.89 90.36 89.36 87.30 86.76 86.64 86.33 85.28 89.29 120.45 121.47 120.34 116.96 120.18 122.59 122.55 119.89 114.74 109.21 111.78 112.67 111.80 109.64 110.86 112.89 113.20 113.05 114.72 117.84 120.44 93.38 95.05 94.61 142.73 140.39 134.80 126.13 114.79 108.38 108.34 106.09 101.56 95.43 92.16 90.85 88.33 88.16 87.48 85.97 89.49 93.37 123.35 124.03 122.63 121.81 126.14 128.22 127.74 124.62 118.91 110.93 113.03 113.24 111.85 113.06 115.97 116.89 116.39 116.05 117.88 120.95 123.33 95.66 96.90 149.32 149.59 146.54 140.29 131.04 119.21 109.68 109.60 107.27 102.64 96.71 93.77 92.02 89.63 88.93 87.77 86.71 92.21 95.66 124.99 125.50 123.90 125.98 130.19 132.12 131.41 127.94 121.82 113.15 113.12 112.96 113.05 117.26 119.31 119.43 118.33 117.86 119.78 122.78 124.96 97.09 151.09 154.21 V Max (kV) 111.64 111.05 111.10 111.66 112.59 113.63 114.43 114.50 113.47 120.45 121.47 120.34 116.96 120.18 122.59 122.55 119.89 114.74 109.21 111.78 112.67 111.80 109.64 110.86 112.89 113.20 113.05 114.72 117.84 120.44 116.81 114.25 110.17 142.73 140.39 134.80 126.13 114.79 108.38 108.34 106.09 115.85 114.75 114.07 114.12 114.75 115.83 117.03 117.90 117.95 116.81 123.35 124.03 122.63 121.81 126.14 128.22 127.74 124.62 118.91 111.26 113.03 113.24 111.85 113.06 115.97 116.89 116.39 116.05 117.88 120.95 123.33 119.32 116.60 149.32 149.59 146.54 140.29 131.04 119.21 109.68 109.60 107.27 118.20 116.92 116.16 116.23 116.96 118.19 119.54 120.48 120.53 119.32 124.99 125.50 123.90 125.98 130.19 132.12 131.41 127.94 121.82 118.62 117.84 114.84 113.05 117.26 119.31 119.43 118.33 117.86 119.78 122.78 124.96 121.20 151.09 154.21 Ratio Vmax/Vnom 2.07 2.06 2.06 2.07 2.09 2.11 2.12 2.12 2.11 2.24 2.25 2.23 2.17 2.23 2.27 2.27 2.22 2.13 2.03 2.07 2.09 2.07 2.03 2.06 2.09 2.10 2.10 2.13 2.19 2.23 2.17 2.12 2.04 2.65 2.61 2.50 2.34 2.13 2.01 2.01 1.97 2.15 2.13 2.12 2.12 2.13 2.15 2.17 2.19 2.19 2.17 2.29 2.30 2.28 2.26 2.34 2.38 2.37 2.31 2.21 2.06 2.10 2.10 2.08 2.10 2.15 2.17 2.16 2.15 2.19 2.24 2.29 2.21 2.16 2.77 2.78 2.72 2.60 2.43 2.21 2.04 2.03 1.99 2.19 2.17 2.16 2.16 2.17 2.19 2.22 2.24 2.24 2.21 2.32 2.33 2.30 2.34 2.42 2.45 2.44 2.37 2.26 2.20 2.19 2.13 2.10 2.18 2.21 2.22 2.20 2.19 2.22 2.28 2.32 2.25 2.80 2.86 Simulation 4 Variables Simulation 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 Start-Delay (s) 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 Va (kV) 103.68 101.40 99.94 102.92 100.82 99.13 110.24 112.04 113.18 113.88 114.42 114.39 113.78 113.01 111.74 109.82 107.39 104.82 171.65 171.42 170.71 170.58 170.48 170.39 170.38 170.43 170.51 170.68 170.86 171.07 171.31 171.54 171.73 171.88 171.96 171.98 171.93 171.81 171.63 111.00 112.39 108.60 110.68 110.91 107.72 110.40 107.95 106.03 111.39 112.33 113.38 114.10 114.65 114.62 113.99 113.20 112.02 110.84 111.47 111.04 185.35 185.12 184.41 184.24 184.09 184.02 183.97 184.02 184.12 184.27 184.49 184.72 184.97 185.23 185.44 185.60 185.70 185.72 185.66 185.53 185.33 117.58 119.78 117.28 116.79 117.26 116.17 117.25 114.49 112.40 119.10 120.51 119.02 119.12 119.43 119.33 118.89 118.75 120.07 118.45 120.19 117.62 197.68 197.41 196.74 196.53 196.39 196.29 196.23 196.28 196.36 196.55 196.76 197.02 197.31 197.58 197.81 Vb (kV) 107.69 104.53 102.31 103.20 100.79 99.69 123.13 125.04 125.78 126.36 126.66 126.50 125.87 124.99 123.96 121.78 120.04 116.70 126.84 126.63 127.93 127.70 127.48 127.26 127.07 126.92 126.81 126.75 126.74 126.76 126.83 126.91 126.99 127.07 127.12 127.13 127.09 127.00 126.84 124.35 120.34 117.79 114.78 111.24 108.09 108.84 106.19 104.99 131.25 133.13 134.30 134.78 135.02 134.82 134.21 133.41 131.86 129.74 127.37 124.35 136.65 136.42 137.78 137.53 137.28 137.05 136.85 136.69 136.57 136.51 136.51 136.55 136.62 136.72 136.82 136.91 136.97 136.98 136.94 136.83 136.65 130.95 126.88 123.44 120.69 117.26 114.04 113.66 111.07 109.51 138.52 140.18 141.72 142.30 142.46 142.26 141.70 140.70 138.78 136.85 133.72 130.94 146.10 145.81 147.28 146.99 146.70 146.43 146.20 146.02 145.89 145.84 145.84 145.91 146.01 146.14 146.27 Vc (kV) 84.47 84.97 85.17 85.56 85.79 85.90 87.26 89.34 92.71 94.99 94.92 92.52 87.85 85.75 85.90 86.02 86.01 85.81 106.48 106.22 105.89 105.60 105.60 105.64 105.72 105.83 105.95 106.08 106.22 106.35 106.48 106.59 106.69 106.78 106.83 106.84 106.79 106.68 106.50 85.86 85.50 85.10 84.57 85.14 85.34 85.72 85.95 86.03 87.44 89.69 93.81 96.09 96.00 93.54 88.79 85.80 85.95 86.07 86.07 85.89 106.59 106.32 105.99 105.81 105.79 105.81 105.86 105.95 106.06 107.02 106.31 106.44 106.57 106.70 106.80 106.89 106.95 106.96 106.91 106.80 106.61 85.90 85.54 85.13 84.65 85.26 85.44 85.82 86.06 86.10 87.54 89.96 94.55 96.82 96.70 94.20 89.39 85.82 85.97 86.10 86.10 85.93 106.64 106.37 106.03 105.93 105.90 105.90 105.94 106.02 107.83 108.94 107.37 106.48 106.61 106.74 106.86 V Max (kV) 107.69 104.53 102.31 103.20 100.82 99.69 123.13 125.04 125.78 126.36 126.66 126.50 125.87 124.99 123.96 121.78 120.04 116.70 171.65 171.42 170.71 170.58 170.48 170.39 170.38 170.43 170.51 170.68 170.86 171.07 171.31 171.54 171.73 171.88 171.96 171.98 171.93 171.81 171.63 124.35 120.34 117.79 114.78 111.24 108.09 110.40 107.95 106.03 131.25 133.13 134.30 134.78 135.02 134.82 134.21 133.41 131.86 129.74 127.37 124.35 185.35 185.12 184.41 184.24 184.09 184.02 183.97 184.02 184.12 184.27 184.49 184.72 184.97 185.23 185.44 185.60 185.70 185.72 185.66 185.53 185.33 130.95 126.88 123.44 120.69 117.26 116.17 117.25 114.49 112.40 138.52 140.18 141.72 142.30 142.46 142.26 141.70 140.70 138.78 136.85 133.72 130.94 197.68 197.41 196.74 196.53 196.39 196.29 196.23 196.28 196.36 196.55 196.76 197.02 197.31 197.58 197.81 Line Length=10km Ratio Vmax/Vnom 2.00 1.94 1.90 1.92 1.87 1.85 2.28 2.32 2.33 2.34 2.35 2.35 2.34 2.32 2.30 2.26 2.23 2.17 3.19 3.18 3.17 3.17 3.16 3.16 3.16 3.16 3.16 3.17 3.17 3.17 3.18 3.18 3.19 3.19 3.19 3.19 3.19 3.19 3.18 2.31 2.23 2.19 2.13 2.06 2.01 2.05 2.00 1.97 2.44 2.47 2.49 2.50 2.51 2.50 2.49 2.48 2.45 2.41 2.36 2.31 3.44 3.44 3.42 3.42 3.42 3.41 3.41 3.41 3.42 3.42 3.42 3.43 3.43 3.44 3.44 3.44 3.45 3.45 3.45 3.44 3.44 2.43 2.35 2.29 2.24 2.18 2.16 2.18 2.12 2.09 2.57 2.60 2.63 2.64 2.64 2.64 2.63 2.61 2.58 2.54 2.48 2.43 3.67 3.66 3.65 3.65 3.64 3.64 3.64 3.64 3.64 3.65 3.65 3.66 3.66 3.67 3.67 Va (kV) 70.25 69.24 67.28 64.96 64.96 64.66 64.28 63.64 62.07 109.23 108.89 109.02 109.58 110.83 112.55 114.05 114.66 113.93 59.19 59.19 59.20 59.20 59.20 59.20 59.20 59.19 59.19 59.18 59.17 59.17 59.17 59.17 59.17 59.25 59.25 59.25 59.25 59.25 59.25 74.62 70.37 69.20 69.16 68.10 67.32 67.76 67.61 67.14 66.45 65.36 63.48 109.66 109.39 109.54 110.06 111.34 113.17 114.82 115.57 74.61 58.51 58.51 58.50 58.49 58.49 58.48 58.48 58.48 58.48 58.50 58.51 58.52 58.53 58.54 58.56 58.56 58.56 58.56 58.55 58.55 58.55 74.73 71.84 69.59 68.12 69.28 70.36 70.61 70.27 69.55 68.52 67.02 64.82 109.96 109.75 109.92 110.42 111.72 113.64 115.40 116.24 74.72 60.22 60.21 60.20 60.19 60.18 60.17 60.17 60.18 60.19 60.21 60.23 60.25 60.27 60.26 60.26 Vb (kV) 87.46 80.00 70.76 60.01 58.07 59.14 59.35 58.68 59.47 65.59 65.26 65.28 65.64 66.14 66.48 66.38 67.95 69.98 106.83 111.83 116.53 120.13 122.16 122.36 120.62 116.99 111.64 104.98 102.98 102.00 100.55 98.94 99.33 100.02 100.46 100.51 100.82 102.81 106.90 67.79 99.35 95.80 90.18 82.59 73.22 62.33 58.80 59.81 59.97 59.30 59.10 64.90 64.56 64.58 64.94 65.45 65.77 67.19 69.79 67.84 109.74 114.90 119.65 123.20 125.13 125.15 123.21 119.34 113.75 106.90 105.58 104.25 102.45 100.54 101.16 102.07 102.52 102.56 103.05 105.42 109.80 67.11 101.53 97.92 92.22 84.54 75.06 64.06 59.34 60.30 60.42 59.74 58.89 64.20 63.86 63.88 64.26 64.78 66.05 69.04 71.71 67.16 111.96 117.24 122.01 125.54 127.37 127.26 125.15 121.09 115.32 108.55 107.69 106.07 103.97 101.81 102.62 Vc (kV) 136.32 130.24 123.96 115.32 104.76 96.86 91.63 90.25 91.17 91.71 93.42 95.61 96.60 96.57 98.93 99.40 97.99 94.96 124.66 128.53 131.51 132.82 132.03 128.95 123.52 123.85 127.78 129.94 130.32 129.08 126.59 123.51 120.81 119.31 118.79 118.69 119.18 121.13 124.67 95.22 143.20 141.47 140.12 136.07 129.14 119.78 108.67 98.03 92.67 90.82 91.75 92.22 94.23 96.38 97.29 97.33 99.59 99.94 98.42 95.28 125.82 129.79 132.77 134.03 133.16 129.95 124.39 125.45 129.21 131.14 131.26 129.77 127.09 123.92 121.28 119.89 119.38 119.27 119.88 122.08 125.83 95.42 145.73 147.17 145.43 140.62 133.29 123.57 112.07 99.52 93.45 91.23 92.17 92.60 94.81 96.94 97.78 97.86 100.05 100.32 98.70 95.48 126.70 130.73 133.72 134.95 134.00 130.71 125.04 126.61 130.23 131.97 131.91 130.24 127.41 124.19 121.63 Ratio V Max (kV) Vmax/Vnom 136.32 2.53 130.24 2.42 123.96 2.30 115.32 2.14 104.76 1.94 96.86 1.80 91.63 1.70 90.25 1.67 91.17 1.69 109.23 2.03 108.89 2.02 109.02 2.02 109.58 2.03 110.83 2.06 112.55 2.09 114.05 2.12 114.66 2.13 113.93 2.11 124.66 2.31 128.53 2.39 131.51 2.44 132.82 2.46 132.03 2.45 128.95 2.39 123.52 2.29 123.85 2.30 127.78 2.37 129.94 2.41 130.32 2.42 129.08 2.40 126.59 2.35 123.51 2.29 120.81 2.24 119.31 2.21 118.79 2.20 118.69 2.20 119.18 2.21 121.13 2.25 124.67 2.31 95.22 1.77 143.20 2.66 141.47 2.63 140.12 2.60 136.07 2.53 129.14 2.40 119.78 2.22 108.67 2.02 98.03 1.82 92.67 1.72 90.82 1.69 91.75 1.70 109.66 2.03 109.39 2.03 109.54 2.03 110.06 2.04 111.34 2.07 113.17 2.10 114.82 2.13 115.57 2.14 95.28 1.77 125.82 2.33 129.79 2.41 132.77 2.46 134.03 2.49 133.16 2.47 129.95 2.41 124.39 2.31 125.45 2.33 129.21 2.40 131.14 2.43 131.26 2.44 129.77 2.41 127.09 2.36 123.92 2.30 121.28 2.25 119.89 2.22 119.38 2.22 119.27 2.21 119.88 2.22 122.08 2.27 125.83 2.33 95.42 1.77 145.73 2.70 147.17 2.73 145.43 2.70 140.62 2.61 133.29 2.47 123.57 2.29 112.07 2.08 99.52 1.85 93.45 1.73 91.23 1.69 92.17 1.71 109.96 2.04 109.75 2.04 109.92 2.04 110.42 2.05 111.72 2.07 113.64 2.11 115.40 2.14 116.24 2.16 95.48 1.77 126.70 2.35 130.73 2.43 133.72 2.48 134.95 2.50 134.00 2.49 130.71 2.43 125.15 2.32 126.61 2.35 130.23 2.42 131.97 2.45 131.91 2.45 130.24 2.42 127.41 2.36 124.19 2.30 121.63 2.26 Line Length=0.2km Va (kV) 72.17 74.39 75.24 74.35 71.61 67.43 65.50 64.14 63.33 118.45 117.62 117.69 118.53 119.91 121.39 122.40 122.46 121.20 61.06 61.06 61.06 61.06 61.05 61.05 61.06 61.06 61.06 61.06 61.06 61.06 61.06 61.06 61.06 61.12 61.12 61.12 61.12 61.12 61.12 87.76 69.65 73.63 76.77 78.54 78.64 76.88 73.47 68.99 65.14 63.47 62.71 119.56 118.67 118.75 119.68 121.18 122.78 123.86 123.93 122.63 62.02 62.02 62.02 62.01 62.01 62.01 62.02 62.02 62.02 62.02 62.01 62.01 62.02 62.02 62.08 62.08 62.08 62.08 62.08 62.08 62.08 88.65 73.69 77.80 80.68 81.96 81.41 79.07 75.29 70.64 67.31 64.38 62.20 120.39 119.45 119.55 120.54 122.16 123.85 125.00 125.08 68.90 62.98 62.97 62.97 62.97 62.97 62.97 62.97 62.97 62.97 62.97 62.97 62.97 62.97 62.97 63.03 Vb (kV) 92.68 85.02 75.62 64.66 59.41 59.65 59.62 59.97 59.59 66.03 65.56 65.60 66.24 67.46 69.11 70.86 72.26 72.85 97.84 98.90 102.53 105.93 107.58 107.36 113.12 119.24 123.00 124.25 122.99 119.43 113.75 106.42 98.32 96.58 96.37 96.34 96.31 96.37 97.94 76.94 105.82 101.74 95.75 87.89 78.30 67.17 61.03 61.05 60.16 60.21 59.89 68.40 67.69 67.75 68.58 70.06 71.95 73.79 75.07 75.35 99.83 101.80 104.80 108.08 109.55 109.91 118.17 124.19 127.68 128.66 127.04 122.99 116.80 108.95 100.35 98.18 97.94 97.91 97.89 98.25 99.93 77.13 108.46 104.23 98.09 90.08 80.33 69.05 62.22 62.08 61.08 60.36 60.07 70.67 69.78 69.85 70.82 72.50 74.56 76.43 77.58 110.86 101.41 104.23 106.96 109.59 110.95 113.96 122.16 128.14 131.52 132.17 130.25 125.80 119.21 110.93 101.94 Vc (kV) 154.03 150.53 143.87 134.25 122.14 110.42 110.36 107.91 103.24 97.79 95.10 93.04 90.66 89.55 88.64 88.68 93.91 97.09 126.05 126.41 124.75 128.96 133.15 134.94 134.07 130.41 123.96 114.95 114.19 113.02 116.68 120.28 121.65 121.16 119.63 119.07 121.02 123.95 126.02 98.04 154.77 157.59 157.12 153.33 146.39 136.54 126.58 113.47 110.79 108.32 103.62 98.66 96.19 93.94 91.54 90.12 89.36 90.07 95.10 98.04 126.74 127.02 125.29 131.27 135.42 137.11 136.12 132.26 125.57 116.33 115.35 114.03 119.45 122.54 123.39 122.40 120.54 119.91 121.88 124.74 126.70 98.74 157.47 160.07 159.41 155.42 148.27 140.78 129.69 116.23 111.10 108.60 103.85 99.39 97.10 94.71 92.30 90.64 89.98 91.06 95.96 151.65 127.25 127.44 127.02 133.10 137.20 138.84 137.66 133.69 126.88 117.35 116.46 116.53 121.59 124.29 124.72 V Max (kV) 154.03 150.53 143.87 134.25 122.14 110.42 110.36 107.91 103.24 118.45 117.62 117.69 118.53 119.91 121.39 122.40 122.46 121.20 126.05 126.41 124.75 128.96 133.15 134.94 134.07 130.41 123.96 124.25 122.99 119.43 116.68 120.28 121.65 121.16 119.63 119.07 121.02 123.95 126.02 98.04 154.77 157.59 157.12 153.33 146.39 136.54 126.58 113.47 110.79 108.32 103.62 119.56 118.67 118.75 119.68 121.18 122.78 123.86 123.93 122.63 126.74 127.02 125.29 131.27 135.42 137.11 136.12 132.26 127.68 128.66 127.04 122.99 119.45 122.54 123.39 122.40 120.54 119.91 121.88 124.74 126.70 98.74 157.47 160.07 159.41 155.42 148.27 140.78 129.69 116.23 111.10 108.60 103.85 120.39 119.45 119.55 120.54 122.16 123.85 125.00 125.08 151.65 127.25 127.44 127.02 133.10 137.20 138.84 137.66 133.69 131.52 132.17 130.25 125.80 121.59 124.29 124.72 Ratio Vmax/Vnom 2.86 2.79 2.67 2.49 2.27 2.05 2.05 2.00 1.92 2.20 2.18 2.18 2.20 2.23 2.25 2.27 2.27 2.25 2.34 2.35 2.32 2.39 2.47 2.50 2.49 2.42 2.30 2.31 2.28 2.22 2.17 2.23 2.26 2.25 2.22 2.21 2.25 2.30 2.34 1.82 2.87 2.92 2.92 2.85 2.72 2.53 2.35 2.11 2.06 2.01 1.92 2.22 2.20 2.20 2.22 2.25 2.28 2.30 2.30 2.28 2.35 2.36 2.33 2.44 2.51 2.54 2.53 2.45 2.37 2.39 2.36 2.28 2.22 2.27 2.29 2.27 2.24 2.23 2.26 2.31 2.35 1.83 2.92 2.97 2.96 2.88 2.75 2.61 2.41 2.16 2.06 2.02 1.93 2.23 2.22 2.22 2.24 2.27 2.30 2.32 2.32 2.81 2.36 2.36 2.36 2.47 2.55 2.58 2.55 2.48 2.44 2.45 2.42 2.33 2.26 2.31 2.31 Simulation 4 Variables Simulation 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 Start-Delay (s) 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100 Va (kV) 197.98 198.08 198.10 198.04 197.89 197.66 124.08 126.09 125.01 123.35 122.90 123.76 123.52 120.47 118.25 125.96 127.79 127.03 126.52 126.79 126.70 126.26 126.77 127.22 125.29 127.25 124.12 208.83 208.54 207.87 207.65 207.48 207.37 207.31 207.34 207.44 207.63 207.85 208.13 208.44 208.72 208.97 209.15 209.26 209.28 209.21 209.05 208.82 130.96 131.65 131.38 129.62 128.62 129.99 129.25 125.91 123.61 132.47 134.27 134.23 133.31 133.50 133.40 133.04 133.91 133.61 131.95 133.41 130.99 218.93 218.61 217.95 217.72 217.53 217.39 217.33 217.36 217.46 217.64 217.90 218.19 218.50 218.81 219.07 219.27 219.39 219.41 219.34 219.17 218.91 137.42 136.90 137.19 135.17 133.96 135.32 134.44 130.88 128.47 138.77 140.21 140.70 139.65 139.66 139.55 139.39 140.30 139.47 138.32 139.00 137.45 281.33 280.88 280.32 279.98 279.66 279.46 Vb (kV) 146.38 146.45 146.47 146.41 146.28 146.07 136.63 132.74 128.63 125.66 122.46 119.42 118.00 115.65 113.97 144.88 146.51 148.21 148.98 149.16 148.94 148.32 147.10 145.01 143.04 139.54 136.63 154.65 154.34 155.85 155.55 155.24 154.95 154.71 154.52 154.40 154.34 154.36 154.43 154.55 154.69 154.84 154.96 155.04 155.06 155.00 154.85 154.62 141.55 137.84 133.59 130.01 126.95 124.07 122.22 119.64 117.90 150.47 152.27 153.96 154.90 155.13 154.89 154.17 152.76 150.70 148.48 144.94 141.56 162.29 161.96 163.50 163.18 162.86 162.56 162.30 162.11 161.98 161.93 161.96 162.04 162.17 162.33 162.48 162.62 162.70 162.72 162.66 162.50 162.26 145.93 142.29 138.10 133.94 130.88 128.14 125.93 123.17 121.37 155.43 157.49 159.09 160.16 160.44 160.19 159.40 157.82 155.82 153.29 149.86 145.93 210.69 210.22 212.00 211.55 211.11 210.72 Vc (kV) 106.95 107.01 107.02 106.97 106.85 106.65 85.92 85.56 85.15 84.70 85.34 85.52 85.89 86.13 86.14 87.62 90.45 95.04 97.29 97.15 94.62 89.76 85.84 85.98 86.11 86.11 85.95 112.31 112.07 110.33 110.18 110.09 110.08 110.13 110.27 110.49 110.77 111.10 111.45 111.81 112.12 112.39 112.59 112.70 112.72 112.66 112.51 112.31 85.94 85.57 85.16 84.74 85.41 85.58 85.94 86.18 86.17 87.67 90.78 95.36 97.60 97.44 94.87 89.98 86.30 85.99 86.11 86.12 85.96 122.82 122.55 120.80 120.64 120.54 120.50 120.55 120.69 120.92 121.20 121.55 121.92 122.29 122.63 122.91 123.12 123.24 123.26 123.19 123.04 122.82 85.94 85.57 85.17 84.77 85.45 85.62 85.98 86.22 86.21 87.71 90.99 95.57 97.79 97.61 95.02 90.09 87.37 85.99 86.11 86.13 85.97 192.70 192.32 190.30 190.07 189.88 189.82 V Max (kV) 197.98 198.08 198.10 198.04 197.89 197.66 136.63 132.74 128.63 125.66 122.90 123.76 123.52 120.47 118.25 144.88 146.51 148.21 148.98 149.16 148.94 148.32 147.10 145.01 143.04 139.54 136.63 208.83 208.54 207.87 207.65 207.48 207.37 207.31 207.34 207.44 207.63 207.85 208.13 208.44 208.72 208.97 209.15 209.26 209.28 209.21 209.05 208.82 141.55 137.84 133.59 130.01 128.62 129.99 129.25 125.91 123.61 150.47 152.27 153.96 154.90 155.13 154.89 154.17 152.76 150.70 148.48 144.94 141.56 218.93 218.61 217.95 217.72 217.53 217.39 217.33 217.36 217.46 217.64 217.90 218.19 218.50 218.81 219.07 219.27 219.39 219.41 219.34 219.17 218.91 145.93 142.29 138.10 135.17 133.96 135.32 134.44 130.88 128.47 155.43 157.49 159.09 160.16 160.44 160.19 159.40 157.82 155.82 153.29 149.86 145.93 281.33 280.88 280.32 279.98 279.66 279.46 Line Length=10km Ratio Vmax/Vnom 3.67 3.68 3.68 3.67 3.67 3.67 2.54 2.46 2.39 2.33 2.28 2.30 2.29 2.24 2.19 2.69 2.72 2.75 2.76 2.77 2.76 2.75 2.73 2.69 2.65 2.59 2.54 3.88 3.87 3.86 3.85 3.85 3.85 3.85 3.85 3.85 3.85 3.86 3.86 3.87 3.87 3.88 3.88 3.88 3.88 3.88 3.88 3.87 2.63 2.56 2.48 2.41 2.39 2.41 2.40 2.34 2.29 2.79 2.83 2.86 2.87 2.88 2.87 2.86 2.83 2.80 2.76 2.69 2.63 4.06 4.06 4.04 4.04 4.04 4.03 4.03 4.03 4.04 4.04 4.04 4.05 4.05 4.06 4.07 4.07 4.07 4.07 4.07 4.07 4.06 2.71 2.64 2.56 2.51 2.49 2.51 2.49 2.43 2.38 2.88 2.92 2.95 2.97 2.98 2.97 2.96 2.93 2.89 2.84 2.78 2.71 5.22 5.21 5.20 5.20 5.19 5.19 Va (kV) 60.26 60.26 60.26 60.25 60.25 60.25 74.69 73.53 71.20 70.50 72.40 73.29 73.35 72.79 71.80 70.42 68.55 66.07 110.19 110.03 110.22 110.70 112.00 114.00 115.84 72.50 74.73 61.88 61.87 61.85 61.83 61.82 61.81 61.81 61.82 61.84 61.87 61.91 61.94 61.96 61.91 61.91 61.90 61.90 61.90 61.90 61.90 61.89 76.76 75.50 73.18 73.60 75.35 76.06 75.91 75.13 73.87 72.17 69.96 67.23 110.61 111.08 111.27 111.15 112.22 114.28 116.20 72.84 76.80 63.49 63.47 63.45 63.42 63.40 63.39 63.40 63.42 63.45 63.50 63.54 63.59 63.54 63.53 63.52 63.51 63.51 63.51 63.51 63.50 63.49 78.98 77.70 75.42 76.49 78.09 78.63 78.29 77.28 75.75 73.75 71.25 68.29 112.46 112.89 113.11 113.07 112.40 114.50 116.49 79.08 79.01 76.80 76.65 76.48 76.35 76.28 76.30 Vb (kV) 103.67 104.11 104.12 104.76 107.41 112.02 104.76 103.22 99.55 93.79 86.04 76.50 65.41 59.74 60.66 60.76 60.07 58.87 63.63 63.92 63.96 63.74 64.72 67.80 70.88 66.21 104.77 113.71 119.07 123.87 127.36 129.12 128.90 126.65 122.45 116.54 110.51 109.45 107.59 105.23 102.84 103.82 104.96 105.35 105.36 106.11 108.98 113.76 106.13 104.55 100.85 95.04 87.24 77.64 66.48 60.05 60.94 61.02 60.32 59.01 65.52 65.81 65.87 65.66 66.32 69.51 72.68 65.50 106.13 115.11 120.55 125.36 128.82 130.51 130.21 127.85 123.52 117.49 112.19 110.95 108.88 106.29 103.71 104.82 106.00 106.36 106.35 107.20 110.25 115.16 107.24 105.64 101.91 96.07 88.21 78.56 67.35 60.27 61.15 61.22 60.51 59.28 67.44 67.74 67.81 67.62 67.87 71.16 74.38 106.82 107.25 121.49 127.20 132.05 135.35 136.71 135.95 Vc (kV) 120.34 119.82 119.69 120.40 122.80 126.70 146.68 150.73 151.56 149.49 144.43 136.66 126.64 114.81 101.97 94.06 91.55 92.48 92.88 95.25 97.36 98.16 98.25 100.39 100.59 98.91 146.76 127.39 131.47 134.46 135.66 134.66 131.30 125.54 127.48 130.98 132.58 132.36 130.55 127.62 124.38 121.90 120.68 120.15 120.02 120.81 123.36 127.38 151.20 154.63 155.31 152.85 147.55 139.63 129.36 117.27 104.12 94.55 91.80 92.73 93.10 95.59 97.69 98.45 98.55 100.65 100.80 99.07 151.27 127.93 132.06 135.06 136.23 135.19 131.77 125.94 128.15 131.55 133.04 132.70 130.78 127.77 124.52 122.12 120.96 120.42 120.28 121.13 123.81 127.92 154.53 157.98 158.28 155.74 150.29 142.17 131.65 119.35 105.98 94.95 92.01 92.94 93.28 95.87 97.95 98.68 98.79 100.85 100.97 148.65 154.60 130.35 134.67 137.69 138.76 137.53 133.83 Ratio V Max (kV) Vmax/Vnom 120.34 2.23 119.82 2.22 119.69 2.22 120.40 2.23 122.80 2.28 126.70 2.35 146.68 2.72 150.73 2.80 151.56 2.81 149.49 2.77 144.43 2.68 136.66 2.54 126.64 2.35 114.81 2.13 101.97 1.89 94.06 1.75 91.55 1.70 92.48 1.72 110.19 2.04 110.03 2.04 110.22 2.05 110.70 2.05 112.00 2.08 114.00 2.12 115.84 2.15 98.91 1.84 146.76 2.72 127.39 2.36 131.47 2.44 134.46 2.50 135.66 2.52 134.66 2.50 131.30 2.44 126.65 2.35 127.48 2.37 130.98 2.43 132.58 2.46 132.36 2.46 130.55 2.42 127.62 2.37 124.38 2.31 121.90 2.26 120.68 2.24 120.15 2.23 120.02 2.23 120.81 2.24 123.36 2.29 127.38 2.36 151.20 2.81 154.63 2.87 155.31 2.88 152.85 2.84 147.55 2.74 139.63 2.59 129.36 2.40 117.27 2.18 104.12 1.93 94.55 1.75 91.80 1.70 92.73 1.72 110.61 2.05 111.08 2.06 111.27 2.06 111.15 2.06 112.22 2.08 114.28 2.12 116.20 2.16 99.07 1.84 151.27 2.81 127.93 2.37 132.06 2.45 135.06 2.51 136.23 2.53 135.19 2.51 131.77 2.45 127.85 2.37 128.15 2.38 131.55 2.44 133.04 2.47 132.70 2.46 130.78 2.43 127.77 2.37 124.52 2.31 122.12 2.27 120.96 2.24 120.42 2.23 120.28 2.23 121.13 2.25 123.81 2.30 127.92 2.37 154.53 2.87 157.98 2.93 158.28 2.94 155.74 2.89 150.29 2.79 142.17 2.64 131.65 2.44 119.35 2.21 105.98 1.97 94.95 1.76 92.01 1.71 92.94 1.72 112.46 2.09 112.89 2.09 113.11 2.10 113.07 2.10 112.40 2.09 114.50 2.12 116.49 2.16 148.65 2.76 154.60 2.87 130.35 2.42 134.67 2.50 137.69 2.56 138.76 2.57 137.53 2.55 135.95 2.52 Line Length=0.2km Va (kV) 63.03 63.03 63.03 63.03 63.03 63.03 72.59 77.58 81.61 84.19 85.01 83.98 81.24 77.21 72.42 69.36 65.98 62.43 121.05 120.06 120.16 121.22 122.93 124.71 125.90 85.30 72.52 63.96 63.96 63.96 63.96 63.96 63.96 63.95 63.95 63.95 63.95 63.96 63.96 63.96 64.01 64.01 64.01 64.01 64.01 64.01 64.01 64.01 76.21 81.29 85.18 87.44 87.87 86.48 83.47 79.23 74.31 71.25 67.46 63.56 61.49 120.55 120.66 121.76 123.56 125.40 80.55 86.07 76.12 64.97 64.97 64.97 64.97 64.96 64.96 64.96 64.95 64.95 64.96 64.97 64.97 64.97 65.01 65.01 65.01 65.01 65.01 65.01 65.01 65.01 79.72 84.81 88.52 90.51 90.63 88.97 85.73 81.29 76.41 72.97 68.83 64.61 62.60 120.95 121.06 122.21 124.06 125.97 81.35 73.75 79.63 74.68 74.60 74.50 74.38 74.29 74.25 Vb (kV) 99.48 99.20 99.16 99.15 99.74 101.51 113.02 110.54 106.19 99.93 91.80 81.93 70.52 63.20 62.95 61.86 60.46 60.20 72.91 71.86 71.94 73.03 74.88 77.05 78.93 72.94 113.04 102.81 106.32 109.14 110.74 111.98 117.31 125.53 131.40 134.62 135.07 132.85 128.11 121.17 112.54 103.25 100.58 100.25 100.20 100.22 100.95 102.88 114.78 112.21 107.78 101.41 93.18 83.21 71.72 64.11 63.75 62.57 60.71 60.29 59.44 73.94 74.03 75.21 77.19 79.46 67.91 73.27 114.80 104.42 108.12 111.05 112.57 112.78 120.02 128.28 134.08 137.13 137.45 135.03 130.03 122.79 113.86 104.30 101.53 101.15 101.10 101.13 101.92 104.49 116.23 113.59 109.08 102.64 94.32 84.26 72.69 65.01 64.55 63.27 61.33 60.35 59.56 75.99 76.09 77.36 79.45 81.79 68.04 117.15 116.25 113.57 118.32 121.92 123.77 123.64 133.59 Vc (kV) 123.34 121.20 120.52 122.50 125.32 127.21 153.91 159.53 161.97 161.15 157.00 152.44 143.66 132.06 118.35 111.34 108.79 103.99 99.97 97.88 95.36 92.96 91.11 90.53 91.81 96.60 153.85 127.62 127.72 128.42 134.51 138.68 140.30 139.04 134.91 127.91 118.26 117.51 118.58 123.34 125.68 125.76 124.06 121.71 120.99 122.97 125.75 127.57 155.63 161.13 163.47 162.52 160.67 154.96 145.89 134.04 120.13 111.50 108.94 104.13 100.46 98.53 95.94 93.54 91.53 90.99 92.40 97.10 155.58 127.89 127.97 129.52 135.74 139.90 141.41 140.09 135.84 128.71 119.28 118.48 120.25 124.76 126.81 126.60 124.63 122.11 121.36 123.34 126.08 127.84 157.03 162.44 164.67 165.43 163.07 157.03 147.69 135.63 121.56 111.60 109.07 104.21 100.87 99.09 96.43 94.04 92.00 91.41 92.85 148.73 156.96 128.92 128.86 134.91 141.32 145.44 146.78 V Max (kV) 123.34 121.20 120.52 122.50 125.32 127.21 153.91 159.53 161.97 161.15 157.00 152.44 143.66 132.06 118.35 111.34 108.79 103.99 121.05 120.06 120.16 121.22 122.93 124.71 125.90 96.60 153.85 127.62 127.72 128.42 134.51 138.68 140.30 139.04 134.91 134.62 135.07 132.85 128.11 123.34 125.68 125.76 124.06 121.71 120.99 122.97 125.75 127.57 155.63 161.13 163.47 162.52 160.67 154.96 145.89 134.04 120.13 111.50 108.94 104.13 100.46 120.55 120.66 121.76 123.56 125.40 92.40 97.10 155.58 127.89 127.97 129.52 135.74 139.90 141.41 140.09 135.84 137.13 137.45 135.03 130.03 124.76 126.81 126.60 124.63 122.11 121.36 123.34 126.08 127.84 157.03 162.44 164.67 165.43 163.07 157.03 147.69 135.63 121.56 111.60 109.07 104.21 100.87 120.95 121.06 122.21 124.06 125.97 92.85 148.73 156.96 128.92 128.86 134.91 141.32 145.44 146.78 Ratio Vmax/Vnom 2.29 2.25 2.24 2.27 2.33 2.36 2.86 2.96 3.01 2.99 2.91 2.83 2.67 2.45 2.20 2.07 2.02 1.93 2.25 2.23 2.23 2.25 2.28 2.31 2.34 1.79 2.85 2.37 2.37 2.38 2.50 2.57 2.60 2.58 2.50 2.50 2.51 2.47 2.38 2.29 2.33 2.33 2.30 2.26 2.25 2.28 2.33 2.37 2.89 2.99 3.03 3.02 2.98 2.88 2.71 2.49 2.23 2.07 2.02 1.93 1.86 2.24 2.24 2.26 2.29 2.33 1.71 1.80 2.89 2.37 2.37 2.40 2.52 2.60 2.62 2.60 2.52 2.54 2.55 2.51 2.41 2.32 2.35 2.35 2.31 2.27 2.25 2.29 2.34 2.37 2.91 3.01 3.06 3.07 3.03 2.91 2.74 2.52 2.26 2.07 2.02 1.93 1.87 2.24 2.25 2.27 2.30 2.34 1.72 2.76 2.91 2.39 2.39 2.50 2.62 2.70 2.72 Simulation 4 Variables Simulation 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 Start-Delay (s) 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Va (kV) 279.31 279.33 279.42 279.67 279.97 280.38 280.80 281.19 281.55 281.84 282.00 282.03 281.93 281.68 281.32 179.02 177.68 175.06 175.41 173.03 169.95 170.44 165.78 162.58 158.70 183.01 184.36 184.65 184.26 184.06 184.14 183.42 181.82 181.67 179.86 179.06 372.50 371.79 372.80 372.19 371.62 371.15 370.79 370.60 370.58 370.75 371.06 371.50 371.99 372.51 372.98 373.35 373.60 373.64 373.48 373.12 372.56 254.19 252.42 241.90 237.89 239.31 231.48 230.09 227.55 222.73 216.98 271.44 273.13 275.97 276.51 276.09 274.72 270.94 269.23 265.53 261.62 254.20 430.45 429.65 430.88 430.22 429.50 428.93 428.51 428.30 428.22 428.48 428.75 429.31 429.87 430.41 430.97 431.43 431.70 431.76 431.57 431.15 430.52 283.26 279.68 273.95 256.33 269.40 255.08 263.88 263.00 257.36 250.87 304.49 306.22 309.78 310.37 309.88 308.24 303.66 301.45 Vb (kV) 210.39 210.16 210.03 210.02 210.10 210.29 210.52 210.78 211.04 211.25 211.38 211.41 211.31 211.08 210.73 174.28 168.69 164.90 160.28 156.10 152.53 148.32 144.49 142.31 139.35 188.80 190.76 191.86 192.36 192.01 190.84 189.14 186.53 182.91 179.05 174.30 312.87 312.31 312.69 312.23 311.79 311.44 311.20 311.09 311.12 311.29 311.57 311.95 312.37 312.80 313.19 313.49 313.68 313.72 313.59 313.30 312.87 225.08 220.19 215.10 211.46 208.03 206.11 198.84 192.32 189.24 185.49 238.89 240.94 242.46 242.89 242.48 241.25 238.95 236.52 233.27 229.20 225.09 346.32 345.50 346.45 345.78 345.02 344.49 344.03 343.88 343.83 344.12 344.44 345.04 345.57 346.24 346.82 347.30 347.58 347.63 347.44 347.01 346.36 236.32 231.88 226.99 223.03 219.74 217.86 210.35 203.13 199.83 195.83 251.00 252.94 254.40 254.85 254.45 253.21 251.00 248.48 Vc (kV) 189.83 190.01 190.26 190.65 191.08 191.57 192.07 192.52 192.90 193.19 193.36 193.39 193.29 193.06 192.74 96.50 94.79 93.20 91.52 90.19 88.78 86.15 86.39 86.37 87.96 101.59 102.25 102.70 102.79 102.61 102.18 101.45 100.60 99.33 98.09 96.50 338.48 337.83 335.96 335.46 335.17 334.86 334.87 334.91 335.26 335.65 336.29 336.89 337.62 338.31 338.87 339.29 339.49 339.54 339.38 339.02 338.49 196.42 193.34 190.60 187.96 185.85 184.16 175.68 168.79 166.62 163.99 207.26 208.78 209.70 210.08 209.74 208.71 207.19 205.16 202.38 199.64 196.46 403.37 402.63 400.79 400.36 399.77 399.51 399.31 399.47 399.62 400.27 400.74 401.60 402.32 403.02 403.70 404.24 404.55 404.61 404.41 403.99 403.38 217.77 214.30 211.43 208.62 206.40 205.09 195.29 188.17 185.52 182.38 229.55 231.22 232.44 232.88 232.50 231.35 229.47 227.21 V Max (kV) 279.31 279.33 279.42 279.67 279.97 280.38 280.80 281.19 281.55 281.84 282.00 282.03 281.93 281.68 281.32 179.02 177.68 175.06 175.41 173.03 169.95 170.44 165.78 162.58 158.70 188.80 190.76 191.86 192.36 192.01 190.84 189.14 186.53 182.91 179.86 179.06 372.50 371.79 372.80 372.19 371.62 371.15 370.79 370.60 370.58 370.75 371.06 371.50 371.99 372.51 372.98 373.35 373.60 373.64 373.48 373.12 372.56 254.19 252.42 241.90 237.89 239.31 231.48 230.09 227.55 222.73 216.98 271.44 273.13 275.97 276.51 276.09 274.72 270.94 269.23 265.53 261.62 254.20 430.45 429.65 430.88 430.22 429.50 428.93 428.51 428.30 428.22 428.48 428.75 429.31 429.87 430.41 430.97 431.43 431.70 431.76 431.57 431.15 430.52 283.26 279.68 273.95 256.33 256.33 255.08 263.88 263.00 257.36 250.87 304.49 306.22 309.78 310.37 309.88 308.24 303.66 301.45 Line Length=10km Ratio Vmax/Vnom 5.18 5.18 5.19 5.19 5.20 5.20 5.21 5.22 5.22 5.23 5.23 5.23 5.23 5.23 5.22 3.32 3.30 3.25 3.26 3.21 3.15 3.16 3.08 3.02 2.94 3.50 3.54 3.56 3.57 3.56 3.54 3.51 3.46 3.39 3.34 3.32 6.91 6.90 6.92 6.91 6.90 6.89 6.88 6.88 6.88 6.88 6.89 6.89 6.90 6.91 6.92 6.93 6.93 6.93 6.93 6.92 6.91 4.72 4.68 4.49 4.41 4.44 4.30 4.27 4.22 4.13 4.03 5.04 5.07 5.12 5.13 5.12 5.10 5.03 5.00 4.93 4.85 4.72 7.99 7.97 8.00 7.98 7.97 7.96 7.95 7.95 7.95 7.95 7.96 7.97 7.98 7.99 8.00 8.01 8.01 8.01 8.01 8.00 7.99 5.26 5.19 5.08 4.76 4.76 4.73 4.90 4.88 4.78 4.66 5.65 5.68 5.75 5.76 5.75 5.72 5.63 5.59 Va (kV) 76.43 76.67 76.98 77.32 77.50 77.30 77.12 77.00 76.93 76.91 76.92 76.93 76.90 76.83 76.70 101.91 101.05 99.24 96.76 96.60 95.82 93.94 91.21 87.81 83.87 79.56 75.23 71.51 121.61 122.00 122.37 75.94 97.97 100.30 101.66 101.91 106.10 105.46 105.13 105.29 105.92 106.93 108.34 114.20 112.95 111.47 109.95 108.59 107.59 107.04 106.91 107.03 107.21 107.26 107.06 106.59 105.94 160.53 160.03 157.75 153.92 148.79 142.49 134.99 126.27 116.47 106.06 95.84 87.01 81.53 79.09 78.81 80.50 146.89 151.79 156.12 159.18 160.52 111.40 110.89 110.92 111.63 112.82 114.14 121.97 120.84 119.29 117.49 115.64 114.02 112.86 112.28 112.20 112.40 112.63 112.69 112.46 111.93 111.27 170.74 170.18 167.67 163.42 157.71 150.68 142.34 132.73 122.01 110.74 99.69 90.23 82.79 80.55 80.21 81.66 155.95 161.24 Vb (kV) 133.04 128.13 122.00 121.16 119.00 115.79 111.98 109.27 109.86 110.94 110.98 110.87 112.21 116.04 121.52 112.41 110.72 106.86 100.85 92.80 82.91 71.45 66.88 62.91 64.49 65.03 64.59 63.43 84.50 84.70 84.83 67.58 106.91 109.99 112.06 112.42 126.64 132.54 137.37 140.48 141.52 140.33 136.92 131.97 132.29 130.82 127.73 123.33 118.18 116.27 114.53 115.13 114.75 114.54 116.30 120.75 126.66 134.11 137.14 138.55 137.84 134.86 129.62 122.29 113.18 102.73 95.23 90.02 85.05 81.63 79.67 79.50 80.94 124.96 126.94 128.67 130.76 134.16 127.14 133.07 137.89 140.98 141.99 140.75 137.29 133.18 133.47 131.93 128.73 124.20 118.90 117.15 115.31 115.56 115.12 114.90 116.71 121.21 127.16 150.15 153.02 154.09 152.81 149.02 142.74 134.18 123.70 111.79 101.19 94.93 89.14 85.06 83.23 82.97 84.14 139.63 142.25 Vc (kV) 127.67 130.79 133.72 134.68 133.78 131.38 128.10 125.02 123.16 122.21 121.55 121.36 122.53 125.78 130.31 170.86 173.53 173.25 169.99 163.74 154.69 143.21 129.95 115.65 101.43 92.96 93.87 94.10 97.12 99.15 99.75 99.83 149.39 158.08 165.57 170.91 132.22 136.70 139.75 140.75 139.35 135.42 128.98 132.36 134.87 135.36 134.02 131.27 127.94 125.34 124.07 123.19 122.36 122.11 123.58 127.30 132.17 183.07 185.63 185.13 181.45 174.66 165.03 152.90 139.32 125.22 111.23 98.85 94.69 94.95 98.18 100.15 100.64 153.10 161.67 170.37 177.84 183.12 132.40 136.90 139.95 140.93 139.52 135.58 129.10 132.48 134.95 135.39 134.00 131.23 127.90 125.37 124.16 123.28 122.43 122.18 123.68 127.44 132.35 184.83 187.73 187.22 184.23 178.25 169.01 157.58 144.15 129.68 115.08 101.73 94.77 95.06 98.28 100.25 100.73 154.41 163.01 Ratio V Max (kV) Vmax/Vnom 133.04 2.47 130.79 2.43 133.72 2.48 134.68 2.50 133.78 2.48 131.38 2.44 128.10 2.38 125.02 2.32 123.16 2.29 122.21 2.27 121.55 2.26 121.36 2.25 122.53 2.27 125.78 2.33 130.31 2.42 170.86 3.17 173.53 3.22 173.25 3.21 169.99 3.15 163.74 3.04 154.69 2.87 143.21 2.66 129.95 2.41 115.65 2.15 101.43 1.88 92.96 1.72 93.87 1.74 94.10 1.75 121.61 2.26 122.00 2.26 122.37 2.27 99.83 1.85 149.39 2.77 158.08 2.93 165.57 3.07 170.91 3.17 132.22 2.45 136.70 2.54 139.75 2.59 140.75 2.61 141.52 2.63 140.33 2.60 136.92 2.54 132.36 2.46 134.87 2.50 135.36 2.51 134.02 2.49 131.27 2.44 127.94 2.37 125.34 2.33 124.07 2.30 123.19 2.29 122.36 2.27 122.11 2.27 123.58 2.29 127.30 2.36 132.17 2.45 183.07 3.40 185.63 3.44 185.13 3.44 181.45 3.37 174.66 3.24 165.03 3.06 152.90 2.84 139.32 2.59 125.22 2.32 111.23 2.06 98.85 1.83 94.69 1.76 94.95 1.76 98.18 1.82 100.15 1.86 100.64 1.87 153.10 2.84 161.67 3.00 170.37 3.16 177.84 3.30 183.12 3.40 132.40 2.46 136.90 2.54 139.95 2.60 140.98 2.62 141.99 2.63 140.75 2.61 137.29 2.55 133.18 2.47 134.95 2.50 135.39 2.51 134.00 2.49 131.23 2.44 127.90 2.37 125.37 2.33 124.16 2.30 123.28 2.29 122.43 2.27 122.18 2.27 123.68 2.30 127.44 2.36 132.35 2.46 184.83 3.43 187.73 3.48 187.22 3.47 184.23 3.42 178.25 3.31 169.01 3.14 157.58 2.92 144.15 2.67 129.68 2.41 115.08 2.14 101.73 1.89 94.77 1.76 95.06 1.76 98.28 1.82 100.25 1.86 100.73 1.87 155.95 2.89 163.01 3.02 Line Length=0.2km Va (kV) 74.29 74.40 74.56 74.72 75.00 74.96 74.89 74.82 74.75 74.70 74.68 74.68 74.68 74.66 74.61 106.73 111.45 114.25 115.04 113.81 110.68 105.86 99.72 92.78 85.75 79.47 74.57 71.23 69.52 69.72 70.55 73.19 79.61 92.99 100.29 106.61 101.57 102.48 104.04 105.95 107.81 109.31 110.22 107.87 107.89 107.23 106.01 104.46 102.91 101.76 101.28 101.34 101.52 101.56 101.47 101.40 101.66 160.27 165.34 167.75 167.32 164.03 158.03 149.53 139.06 127.23 114.99 103.47 83.98 83.02 82.63 82.86 83.08 132.98 137.17 143.81 152.80 160.14 107.93 109.51 111.90 114.64 117.24 119.31 114.47 115.24 115.12 114.14 112.45 110.34 108.26 106.83 106.57 107.06 107.48 107.57 107.43 107.42 108.03 168.89 174.07 176.44 175.82 172.19 165.68 156.57 145.34 132.68 119.55 107.17 85.90 84.89 84.46 84.68 84.85 143.86 148.57 Vb (kV) 141.89 147.40 149.88 149.32 145.76 139.41 130.67 120.25 109.21 107.32 106.54 106.42 106.67 108.73 113.61 123.23 120.29 115.40 108.55 99.79 89.29 77.30 75.76 74.04 71.44 68.24 64.89 62.08 60.62 60.68 60.88 61.51 66.67 123.81 124.36 123.25 124.39 130.42 134.95 137.42 137.58 146.31 154.64 159.86 161.77 160.33 155.63 148.02 137.87 125.93 119.05 116.04 114.46 114.19 114.92 117.88 124.41 129.54 128.19 131.83 133.88 133.96 131.94 127.86 121.87 114.22 105.45 96.26 75.89 76.41 76.66 76.62 75.99 125.04 128.09 130.18 130.78 130.27 125.70 131.90 136.54 139.11 139.33 147.65 156.00 161.17 162.99 161.49 156.70 148.92 138.62 126.51 120.48 117.27 115.57 115.27 116.09 119.00 125.72 138.44 142.44 146.11 147.81 147.29 144.43 139.30 132.08 123.09 112.93 102.39 79.25 79.79 80.06 80.00 79.25 126.59 130.80 Vc (kV) 145.14 140.43 132.80 126.56 124.95 128.36 131.52 132.12 130.46 127.16 123.79 122.88 124.86 127.38 128.85 168.52 174.81 177.73 177.20 173.25 166.05 155.83 143.05 128.33 112.70 109.46 105.60 103.08 102.05 99.12 96.84 94.68 93.78 147.85 159.16 168.49 129.49 131.59 139.72 146.29 150.37 151.54 149.63 144.58 136.77 136.37 134.02 135.55 137.45 136.67 133.60 129.08 124.93 123.91 125.83 128.14 129.41 178.51 184.35 186.97 186.21 181.96 174.39 163.69 150.37 134.97 118.56 109.80 107.59 106.08 105.04 101.94 99.99 149.45 154.54 159.26 169.90 178.47 129.56 132.05 140.19 146.73 150.85 152.02 150.09 144.99 138.07 137.62 135.19 136.31 138.05 137.13 133.92 129.25 125.03 124.00 125.92 128.20 129.49 179.64 185.51 188.15 187.38 183.12 175.48 164.72 151.31 135.83 119.31 109.79 107.80 106.40 105.38 102.26 100.35 154.66 160.04 V Max (kV) 145.14 147.40 149.88 149.32 145.76 139.41 131.52 132.12 130.46 127.16 123.79 122.88 124.86 127.38 128.85 168.52 174.81 177.73 177.20 173.25 166.05 155.83 143.05 128.33 112.70 109.46 105.60 103.08 102.05 99.12 96.84 94.68 93.78 147.85 159.16 168.49 129.49 131.59 139.72 146.29 150.37 151.54 154.64 159.86 161.77 160.33 155.63 148.02 137.87 136.67 133.60 129.08 124.93 123.91 125.83 128.14 129.41 178.51 184.35 186.97 186.21 181.96 174.39 163.69 150.37 134.97 118.56 109.80 107.59 106.08 105.04 101.94 99.99 149.45 154.54 159.26 169.90 178.47 129.56 132.05 140.19 146.73 150.85 152.02 156.00 161.17 162.99 161.49 156.70 148.92 138.62 137.13 133.92 129.25 125.03 124.00 125.92 128.20 129.49 179.64 185.51 188.15 187.38 183.12 175.48 164.72 151.31 135.83 119.55 109.79 107.80 106.40 105.38 102.26 100.35 154.66 160.04 Ratio Vmax/Vnom 2.69 2.74 2.78 2.77 2.70 2.59 2.44 2.45 2.42 2.36 2.30 2.28 2.32 2.36 2.39 3.13 3.24 3.30 3.29 3.21 3.08 2.89 2.65 2.38 2.09 2.03 1.96 1.91 1.89 1.84 1.80 1.76 1.74 2.74 2.95 3.13 2.40 2.44 2.59 2.71 2.79 2.81 2.87 2.97 3.00 2.98 2.89 2.75 2.56 2.54 2.48 2.40 2.32 2.30 2.34 2.38 2.40 3.31 3.42 3.47 3.46 3.38 3.24 3.04 2.79 2.50 2.20 2.04 2.00 1.97 1.95 1.89 1.86 2.77 2.87 2.96 3.15 3.31 2.40 2.45 2.60 2.72 2.80 2.82 2.89 2.99 3.02 3.00 2.91 2.76 2.57 2.54 2.49 2.40 2.32 2.30 2.34 2.38 2.40 3.33 3.44 3.49 3.48 3.40 3.26 3.06 2.81 2.52 2.22 2.04 2.00 1.97 1.96 1.90 1.86 2.87 2.97 Simulation 4 Variables Simulation 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 Start-Delay (s) 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km NER Fault Duration Size (s) (Ohm) 0.1 1000 0.1 1000 0.1 1000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 0.1 1000000 Va (kV) 296.77 292.83 283.27 551.84 553.75 552.86 551.69 550.96 550.21 549.65 549.21 549.30 549.33 549.97 550.39 551.30 552.11 552.85 553.29 553.57 553.63 553.39 552.82 551.92 343.73 330.77 336.33 299.31 330.85 301.83 336.27 337.09 329.68 321.58 367.61 371.65 376.51 377.09 376.51 374.36 368.11 363.34 359.94 351.52 343.72 Vb (kV) 244.97 240.66 236.33 472.04 473.43 472.67 471.57 470.57 470.08 469.26 469.11 469.06 469.20 469.85 470.46 471.15 472.17 473.06 473.53 473.82 473.88 473.64 473.05 472.11 275.67 271.35 264.92 254.29 259.90 248.06 257.14 250.11 244.53 239.16 295.29 299.35 301.29 301.33 300.84 299.79 296.70 291.89 288.46 283.32 275.67 Vc (kV) 224.30 220.98 217.82 530.47 529.08 528.28 527.49 526.78 526.29 525.99 526.00 526.25 526.78 527.50 528.39 529.31 530.26 531.10 531.72 532.09 532.16 531.91 531.35 530.51 255.16 250.92 246.84 242.67 241.03 238.51 264.57 263.68 255.64 247.13 269.42 272.13 274.14 273.87 273.44 272.37 269.98 266.59 263.57 259.28 255.21 V Max (kV) 296.77 292.83 283.27 551.84 553.75 552.86 551.69 550.96 550.21 549.65 549.21 549.30 549.33 549.97 550.39 551.30 552.11 552.85 553.29 553.57 553.63 553.39 552.82 551.92 343.73 330.77 336.33 299.31 330.85 301.83 336.27 337.09 329.68 321.58 367.61 371.65 376.51 377.09 376.51 374.36 368.11 363.34 359.94 351.52 343.72 Line Length=10km Ratio Vmax/Vnom 5.51 5.43 5.26 10.24 10.28 10.26 10.24 10.22 10.21 10.20 10.19 10.19 10.19 10.21 10.21 10.23 10.25 10.26 10.27 10.27 10.27 10.27 10.26 10.24 6.38 6.14 6.24 5.55 6.14 5.60 6.24 6.26 6.12 5.97 6.82 6.90 6.99 7.00 6.99 6.95 6.83 6.74 6.68 6.52 6.38 Va (kV) 165.95 169.26 170.73 120.98 121.01 121.85 123.51 125.75 128.25 131.82 130.28 128.29 125.98 123.64 121.64 120.64 120.48 120.86 121.45 121.91 122.01 121.73 121.22 120.78 184.97 184.30 181.40 176.52 169.94 161.87 152.38 141.52 129.57 117.07 104.97 94.96 88.63 88.16 87.63 87.02 168.60 174.46 179.69 183.35 184.96 Vb (kV) 144.52 146.84 150.18 127.76 133.71 138.53 141.59 142.56 141.26 137.73 134.70 134.95 133.33 130.00 125.30 120.56 120.40 120.79 121.36 121.80 121.90 121.61 121.77 127.78 174.78 176.92 177.39 175.21 170.19 162.35 151.98 139.42 125.35 113.38 103.33 95.44 89.90 88.53 88.08 88.69 162.34 165.94 168.96 171.91 174.72 Vc (kV) 171.75 179.22 184.86 132.61 137.13 140.19 141.16 139.73 135.76 131.05 132.63 135.04 135.42 133.98 131.16 127.84 125.41 124.27 123.39 122.52 122.26 123.80 127.61 132.56 196.29 200.08 200.40 198.04 191.96 181.70 170.17 155.16 138.32 121.55 106.61 95.97 95.18 98.41 100.37 100.84 162.87 170.47 179.90 188.89 196.23 Ratio V Max (kV) Vmax/Vnom 171.75 3.19 179.22 3.33 184.86 3.43 132.61 2.46 137.13 2.54 140.19 2.60 141.59 2.63 142.56 2.65 141.26 2.62 137.73 2.56 134.70 2.50 135.04 2.51 135.42 2.51 133.98 2.49 131.16 2.43 127.84 2.37 125.41 2.33 124.27 2.31 123.39 2.29 122.52 2.27 122.26 2.27 123.80 2.30 127.61 2.37 132.56 2.46 196.29 3.64 200.08 3.71 200.40 3.72 198.04 3.67 191.96 3.56 181.70 3.37 170.17 3.16 155.16 2.88 138.32 2.57 121.55 2.26 106.61 1.98 95.97 1.78 95.18 1.77 98.41 1.83 100.37 1.86 100.84 1.87 168.60 3.13 174.46 3.24 179.90 3.34 188.89 3.51 196.23 3.64 Line Length=0.2km Va (kV) 152.24 161.19 168.76 117.14 119.91 123.69 127.82 131.63 134.65 133.03 131.05 128.38 125.65 122.43 119.12 116.29 114.55 114.29 115.44 116.31 116.50 116.05 115.90 117.22 181.15 186.66 188.90 188.27 183.92 176.75 166.96 154.64 140.71 126.37 89.53 89.86 88.39 87.65 87.88 154.25 159.40 164.90 169.36 173.13 180.91 Vb (kV) 134.66 137.43 138.54 127.39 133.78 138.59 141.26 141.53 149.33 157.64 162.83 164.59 162.90 157.99 150.03 139.53 127.23 122.37 118.89 117.03 116.70 117.63 120.43 127.40 167.93 169.39 168.41 168.55 167.07 162.95 156.26 147.22 136.24 124.00 87.26 88.33 87.59 87.31 87.53 145.21 148.99 154.01 159.46 164.38 167.91 Vc (kV) 164.28 170.96 179.60 129.60 132.57 140.72 147.33 151.47 152.61 150.61 145.50 139.85 139.25 136.70 137.23 138.79 137.68 134.28 129.46 125.15 124.11 126.02 128.29 129.53 188.09 195.95 198.06 200.17 192.94 184.34 176.42 162.00 144.90 128.01 109.82 108.06 106.83 105.79 102.66 157.06 162.44 168.31 172.82 179.85 186.93 V Max (kV) 164.28 170.96 179.60 129.60 133.78 140.72 147.33 151.47 152.61 157.64 162.83 164.59 162.90 157.99 150.03 139.53 137.68 134.28 129.46 125.15 124.11 126.02 128.29 129.53 188.09 195.95 198.06 200.17 192.94 184.34 176.42 162.00 144.90 128.01 109.82 108.06 106.83 105.79 102.66 157.06 162.44 168.31 172.82 179.85 186.93 Ratio Vmax/Vnom 3.05 3.17 3.33 2.41 2.48 2.61 2.73 2.81 2.83 2.93 3.02 3.05 3.02 2.93 2.78 2.59 2.55 2.49 2.40 2.32 2.30 2.34 2.38 2.40 3.49 3.64 3.68 3.71 3.58 3.42 3.27 3.01 2.69 2.38 2.04 2.01 1.98 1.96 1.90 2.91 3.01 3.12 3.21 3.34 3.47 Simulation 5 Variables Simulation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 Start-Delay (s) 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Va (kV) 87.86 87.79 87.83 87.80 87.72 87.59 87.38 87.52 87.58 87.62 87.67 87.73 87.81 87.75 87.74 87.77 87.79 87.81 87.75 87.82 87.81 86.91 87.13 119.94 119.88 88.52 88.52 88.48 88.33 88.05 87.60 86.96 86.07 85.31 84.95 85.13 85.55 85.82 86.05 86.38 86.64 86.91 87.03 87.00 86.96 86.92 86.81 86.77 86.57 86.58 86.70 86.78 86.80 86.84 86.89 86.92 86.99 86.97 87.04 87.04 87.01 86.96 86.98 85.38 85.45 121.50 121.44 84.32 84.29 84.24 84.18 84.09 83.98 83.92 83.91 83.96 84.09 84.28 84.51 84.73 84.97 85.09 85.25 85.36 85.93 85.93 85.88 85.81 85.69 85.66 85.36 85.50 85.53 85.68 85.73 85.77 85.81 85.86 85.93 85.89 85.96 85.97 85.93 85.91 85.88 85.03 85.13 123.02 123.05 82.40 82.41 82.47 82.52 82.56 82.65 82.80 83.00 83.26 83.54 83.85 84.11 84.33 84.57 84.75 84.87 85.02 84.60 84.55 84.51 84.43 84.34 83.83 84.00 84.05 84.20 84.25 84.37 84.41 84.46 84.50 84.55 84.60 84.60 84.59 84.60 84.54 84.57 85.11 85.26 124.41 124.36 81.32 81.36 81.49 81.64 81.83 82.08 82.37 82.68 83.01 83.33 83.62 83.88 Vb (kV) 73.11 74.36 73.80 71.63 71.10 71.48 71.25 71.00 71.16 71.07 71.55 71.80 71.69 71.92 72.17 72.12 72.13 72.16 72.19 72.20 73.15 122.38 122.30 86.78 86.85 123.01 123.04 123.01 123.01 123.05 123.03 122.99 122.98 122.95 122.90 122.82 122.76 122.71 122.62 122.53 122.44 122.35 73.26 74.54 74.02 71.58 70.00 70.47 70.36 70.05 70.33 70.32 70.19 70.32 70.15 70.24 70.42 70.32 70.31 70.32 70.37 70.43 73.30 120.85 120.81 86.65 86.73 121.06 121.11 121.10 121.13 121.15 121.16 121.16 121.14 121.12 121.08 121.09 121.04 121.02 120.96 120.93 120.89 120.82 73.41 74.73 74.24 71.82 69.37 69.81 69.79 69.32 70.06 70.15 69.75 70.21 70.31 70.20 70.09 70.26 70.23 70.15 70.10 70.39 73.44 119.13 119.10 86.37 86.52 119.38 119.37 119.42 119.42 119.42 119.43 119.43 119.41 119.39 119.42 119.37 119.31 119.31 119.23 119.21 119.18 119.10 73.55 74.90 74.45 72.06 68.98 69.44 69.51 69.01 69.95 70.15 69.89 70.38 70.68 70.58 70.46 70.81 70.75 70.68 70.67 70.52 73.58 117.57 117.48 85.01 85.05 117.76 117.83 117.80 117.84 117.87 117.88 117.88 117.86 117.83 117.79 117.81 117.75 Vc (kV) 68.31 68.24 68.46 68.92 68.86 69.96 71.98 74.62 78.38 80.19 80.00 77.88 73.84 68.36 68.59 68.58 68.57 68.59 68.60 68.64 68.36 70.94 71.21 82.55 82.52 71.47 71.58 71.68 71.51 72.34 72.95 74.02 76.52 77.14 75.84 72.67 70.87 70.66 70.73 70.80 70.91 70.93 69.38 68.92 69.40 70.78 70.61 71.14 73.09 74.92 78.68 80.48 80.27 78.11 74.04 68.98 69.10 69.07 69.03 69.04 69.06 69.14 69.35 71.07 70.88 81.33 81.30 71.10 71.95 72.40 71.20 72.80 73.45 74.14 76.65 77.28 75.98 72.82 71.23 70.88 71.01 71.01 71.15 71.09 71.52 70.94 71.21 72.49 72.23 72.26 74.13 75.22 78.96 80.75 80.52 78.34 74.24 70.69 70.61 70.98 70.85 70.76 70.54 71.00 71.49 71.77 71.19 80.74 80.72 71.12 72.56 73.06 71.84 73.24 73.91 74.26 76.78 77.42 76.13 72.96 71.67 71.36 71.57 71.61 71.74 71.79 73.44 72.79 72.89 74.08 73.70 73.36 75.15 75.51 79.25 81.02 80.77 78.57 74.43 72.64 72.60 72.99 72.90 72.82 72.58 72.98 73.41 72.42 71.85 80.49 80.47 71.79 73.11 73.66 72.47 73.66 74.35 74.37 76.90 77.55 76.27 73.11 72.16 V Max (kV) 87.86 87.79 87.83 87.80 87.72 87.59 87.38 87.52 87.58 87.62 87.67 87.73 87.81 87.75 87.74 87.77 87.79 87.81 87.75 87.82 87.81 122.38 122.30 119.94 119.88 123.01 123.04 123.01 123.01 123.05 123.03 122.99 122.98 122.95 122.90 122.82 122.76 122.71 122.62 122.53 122.44 122.35 87.03 87.00 86.96 86.92 86.81 86.77 86.57 86.58 86.70 86.78 86.80 86.84 86.89 86.92 86.99 86.97 87.04 87.04 87.01 86.96 86.98 120.85 120.81 121.50 121.44 121.06 121.11 121.10 121.13 121.15 121.16 121.16 121.14 121.12 121.08 121.09 121.04 121.02 120.96 120.93 120.89 120.82 85.93 85.93 85.88 85.81 85.69 85.66 85.36 85.50 85.53 85.68 85.73 85.77 85.81 85.86 85.93 85.89 85.96 85.97 85.93 85.91 85.88 119.13 119.10 123.02 123.05 119.38 119.37 119.42 119.42 119.42 119.43 119.43 119.41 119.39 119.42 119.37 119.31 119.31 119.23 119.21 119.18 119.10 84.60 84.55 84.51 84.43 84.34 83.83 84.00 84.05 84.20 84.25 84.37 84.41 84.46 84.50 84.55 84.60 84.60 84.59 84.60 84.54 84.57 117.57 117.48 124.41 124.36 117.76 117.83 117.80 117.84 117.87 117.88 117.88 117.86 117.83 117.79 117.81 117.75 Line Length=10km Ratio Vmax/Vnom 1.63 1.63 1.63 1.63 1.63 1.63 1.62 1.62 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 2.27 2.27 2.23 2.22 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.28 2.27 2.27 2.27 1.62 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.62 1.62 1.61 1.61 1.61 2.24 2.24 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.24 2.24 2.24 2.24 1.59 1.59 1.59 1.59 1.59 1.59 1.58 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.60 1.60 1.59 1.59 1.59 2.21 2.21 2.28 2.28 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.21 2.21 2.21 2.21 2.21 2.21 1.57 1.57 1.57 1.57 1.57 1.56 1.56 1.56 1.56 1.56 1.57 1.57 1.57 1.57 1.57 1.57 1.57 1.57 1.57 1.57 1.57 2.18 2.18 2.31 2.31 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 2.19 Va (kV) 71.63 71.68 72.04 71.79 72.14 71.79 72.25 72.57 72.30 71.77 71.45 71.38 71.77 71.62 71.95 71.63 71.34 71.14 71.82 71.31 71.67 71.40 72.01 89.81 89.41 89.91 72.58 72.01 71.98 72.44 71.74 72.38 72.36 72.18 72.09 71.99 71.76 71.29 72.05 71.23 71.40 71.41 67.01 67.37 66.92 66.64 67.20 66.63 67.01 67.04 66.55 67.30 66.87 66.65 67.22 67.14 66.82 66.60 66.49 66.53 66.53 66.70 66.97 70.74 71.27 98.68 98.53 99.00 70.22 70.41 70.68 70.61 70.20 69.80 70.24 70.69 70.47 70.19 70.00 69.91 70.01 70.08 70.36 70.78 57.75 57.88 57.33 57.41 57.90 57.49 57.91 57.46 58.00 57.44 57.96 57.56 57.61 57.90 57.60 57.39 57.35 57.39 57.32 57.48 57.74 68.00 67.60 99.54 99.49 67.60 67.40 67.15 66.85 66.63 67.10 67.32 66.96 66.62 67.02 67.46 67.49 67.44 67.49 67.65 67.94 67.94 53.62 53.56 54.92 54.80 54.68 54.54 54.39 54.24 54.10 53.96 53.82 53.70 53.59 53.57 53.63 53.68 53.71 53.72 53.70 53.66 53.60 64.64 65.15 65.76 98.17 63.99 64.01 64.30 64.56 64.27 63.96 64.07 64.59 64.31 64.08 64.10 64.51 Vb (kV) 65.19 67.40 67.94 66.83 64.11 63.47 63.42 63.42 63.46 63.51 63.56 63.60 63.64 63.67 63.70 63.71 63.72 63.73 63.72 63.71 65.22 88.74 88.77 71.57 70.82 70.85 88.80 88.52 89.04 88.51 88.79 88.92 88.78 88.84 88.88 88.72 88.52 88.69 89.03 88.85 88.72 88.73 65.59 67.40 67.94 66.83 64.11 60.13 60.74 61.40 62.12 62.85 63.60 64.33 65.03 65.65 66.18 66.58 66.82 66.87 66.69 66.28 65.59 78.03 77.95 62.27 62.33 62.34 77.72 77.79 77.86 77.94 77.95 77.75 77.61 77.55 77.58 77.72 77.77 77.56 77.51 77.89 77.55 77.95 68.66 67.40 67.94 66.83 64.11 64.45 64.87 65.36 65.91 66.52 67.18 67.86 68.55 69.21 69.80 70.27 70.57 70.63 70.39 69.76 68.66 75.02 74.72 53.72 53.75 75.02 75.09 75.16 74.99 74.75 74.54 74.41 74.43 74.42 74.36 74.37 74.60 74.86 74.54 74.81 74.71 75.10 71.82 69.98 69.31 69.40 69.53 69.70 69.92 70.18 70.50 70.87 71.29 71.75 72.25 72.76 73.24 73.65 73.92 73.98 73.72 73.05 71.84 75.73 75.80 76.23 53.93 76.16 76.16 75.93 75.71 75.50 75.40 75.45 75.48 75.46 75.39 75.26 75.38 Vc (kV) 62.46 62.43 62.41 62.38 62.35 62.32 62.29 62.31 62.34 62.37 63.33 65.09 65.26 63.85 62.50 62.51 62.52 62.52 62.51 62.50 62.49 65.68 65.70 65.72 65.74 65.76 65.77 65.78 65.79 65.79 65.78 65.77 65.76 65.90 68.01 68.45 67.25 65.62 65.63 65.65 65.67 65.70 77.41 76.89 76.20 75.35 74.35 74.46 74.79 75.15 75.53 75.93 76.34 76.73 77.10 77.44 77.73 77.94 78.07 78.09 78.00 77.77 77.40 71.31 71.45 71.54 71.58 71.56 71.46 71.27 70.98 70.58 70.06 69.71 69.78 69.92 70.07 70.24 70.41 70.60 70.79 70.98 71.16 71.32 85.29 84.73 83.96 83.59 83.67 83.80 83.94 84.12 84.31 84.52 84.75 84.99 85.23 85.46 85.66 85.83 85.93 85.95 85.87 85.65 85.27 74.74 74.81 74.87 74.90 74.88 74.79 74.61 74.31 74.06 74.07 74.08 74.11 74.15 74.20 74.25 74.32 74.39 74.47 74.56 74.65 74.74 89.43 88.97 88.90 88.89 88.89 88.93 88.98 89.04 89.11 89.20 89.30 89.41 89.53 89.65 89.76 89.86 89.92 89.94 89.88 89.71 89.42 76.67 76.70 76.73 76.74 76.72 76.65 76.52 76.49 76.50 76.51 76.52 76.53 76.53 76.53 76.53 76.54 V Max (kV) 71.63 71.68 72.04 71.79 72.14 71.79 72.25 72.57 72.30 71.77 71.45 71.38 71.77 71.62 71.95 71.63 71.34 71.14 71.82 71.31 71.67 88.74 88.77 89.81 89.41 89.91 88.80 88.52 89.04 88.51 88.79 88.92 88.78 88.84 88.88 88.72 88.52 88.69 89.03 88.85 88.72 88.73 77.41 76.89 76.20 75.35 74.35 74.46 74.79 75.15 75.53 75.93 76.34 76.73 77.10 77.44 77.73 77.94 78.07 78.09 78.00 77.77 77.40 78.03 77.95 98.68 98.53 99.00 77.72 77.79 77.86 77.94 77.95 77.75 77.61 77.55 77.58 77.72 77.77 77.56 77.51 77.89 77.55 77.95 85.29 84.73 83.96 83.59 83.67 83.80 83.94 84.12 84.31 84.52 84.75 84.99 85.23 85.46 85.66 85.83 85.93 85.95 85.87 85.65 85.27 75.02 74.81 99.54 99.49 75.02 75.09 75.16 74.99 74.75 74.54 74.41 74.43 74.42 74.36 74.37 74.60 74.86 74.54 74.81 74.71 75.10 89.43 88.97 88.90 88.89 88.89 88.93 88.98 89.04 89.11 89.20 89.30 89.41 89.53 89.65 89.76 89.86 89.92 89.94 89.88 89.71 89.42 76.67 76.70 76.73 98.17 76.72 76.65 76.52 76.49 76.50 76.51 76.52 76.53 76.53 76.53 76.53 76.54 Line Length=0.2km Ratio Vmax/Vnom 1.33 1.33 1.34 1.33 1.34 1.33 1.34 1.35 1.34 1.33 1.33 1.32 1.33 1.33 1.34 1.33 1.32 1.32 1.33 1.32 1.33 1.65 1.65 1.67 1.66 1.67 1.65 1.64 1.65 1.64 1.65 1.65 1.65 1.65 1.65 1.65 1.64 1.65 1.65 1.65 1.65 1.65 1.44 1.43 1.41 1.40 1.38 1.38 1.39 1.39 1.40 1.41 1.42 1.42 1.43 1.44 1.44 1.45 1.45 1.45 1.45 1.44 1.44 1.45 1.45 1.83 1.83 1.84 1.44 1.44 1.44 1.45 1.45 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.45 1.44 1.45 1.58 1.57 1.56 1.55 1.55 1.55 1.56 1.56 1.56 1.57 1.57 1.58 1.58 1.59 1.59 1.59 1.59 1.59 1.59 1.59 1.58 1.39 1.39 1.85 1.85 1.39 1.39 1.39 1.39 1.39 1.38 1.38 1.38 1.38 1.38 1.38 1.38 1.39 1.38 1.39 1.39 1.39 1.66 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.65 1.66 1.66 1.66 1.66 1.66 1.67 1.67 1.67 1.67 1.67 1.66 1.66 1.42 1.42 1.42 1.82 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1.42 Va (kV) 54.03 53.97 55.35 58.74 60.13 62.71 62.49 63.68 62.66 61.29 58.91 56.10 53.92 53.99 54.04 54.07 54.09 54.09 54.08 54.06 54.01 54.05 53.99 67.33 69.82 72.12 61.67 62.84 63.80 63.99 62.75 61.78 58.92 57.34 54.88 54.07 54.10 54.12 54.12 54.11 54.08 54.04 56.18 56.47 55.98 55.47 56.06 55.63 56.34 55.90 55.80 56.49 55.80 55.77 56.30 56.35 55.88 55.54 55.35 55.31 55.43 55.69 56.09 83.38 84.00 85.94 85.62 84.17 83.62 57.97 56.98 55.84 53.74 53.81 53.88 53.94 53.98 54.01 54.02 54.02 79.16 78.26 80.20 83.31 53.65 53.61 54.58 54.50 54.40 54.30 54.20 54.09 53.98 53.88 53.78 53.69 53.61 53.61 53.66 53.69 53.71 53.71 53.70 53.68 53.64 82.07 81.48 82.07 83.19 82.31 55.10 54.00 53.91 53.83 53.77 53.71 53.70 53.79 53.86 53.92 53.95 53.97 53.97 53.94 53.90 82.06 53.60 55.23 55.12 55.00 54.86 54.72 54.56 54.41 54.25 54.10 53.96 53.83 53.71 53.62 53.60 53.65 53.68 53.68 53.67 53.63 53.58 53.84 53.77 81.01 80.23 54.65 54.42 54.31 54.18 54.05 53.93 53.84 53.75 53.69 53.72 53.81 53.87 Vb (kV) 64.62 66.87 67.47 66.40 63.70 59.43 58.70 58.70 58.72 58.76 58.79 58.82 58.85 58.88 58.90 58.91 58.92 58.92 58.92 60.82 64.65 74.72 74.34 59.84 58.40 55.92 66.87 64.46 60.71 59.19 59.21 59.21 59.19 59.16 59.70 61.49 65.40 68.51 70.89 72.35 74.45 74.72 64.62 66.87 67.47 66.40 63.70 59.43 55.71 56.57 57.50 58.50 59.53 60.56 61.57 62.49 63.29 63.91 64.29 64.37 64.08 63.37 64.65 53.94 53.85 53.76 53.67 53.59 53.64 54.59 53.94 55.03 55.97 56.66 57.12 57.41 57.55 57.53 57.33 57.01 55.41 54.97 54.03 53.94 67.97 66.87 67.47 66.40 64.78 65.02 65.32 65.68 66.11 66.60 67.16 67.77 68.42 69.08 69.70 70.23 70.58 70.65 70.33 69.49 67.99 54.21 54.08 53.95 53.83 53.72 57.92 56.16 57.20 57.93 58.53 58.88 59.00 59.09 59.02 58.98 58.96 58.77 58.55 58.09 57.52 54.21 73.07 72.65 72.65 72.65 72.70 72.77 72.86 72.98 73.14 73.33 73.57 73.85 74.18 74.53 74.90 75.23 75.48 75.53 75.27 74.52 73.10 57.45 59.28 54.16 54.01 60.87 60.10 58.76 58.22 58.99 59.11 59.19 59.24 59.04 59.12 58.89 58.85 Vc (kV) 57.71 57.69 57.67 57.64 57.60 57.57 57.56 57.58 57.60 58.98 62.49 64.46 64.84 63.62 60.84 57.77 57.78 57.78 57.78 57.77 57.75 60.75 60.77 60.79 60.79 60.80 60.80 60.80 60.79 60.77 60.76 60.74 61.50 65.34 67.58 68.16 67.05 64.30 60.71 60.74 60.76 60.78 82.32 81.60 80.64 79.44 78.84 79.14 79.48 79.86 80.28 80.71 81.16 81.61 82.04 82.44 82.78 83.04 83.20 83.23 83.11 82.81 82.31 71.95 72.11 72.23 72.30 72.29 72.17 71.91 71.50 70.88 70.46 70.48 70.55 70.65 70.76 70.90 71.05 71.21 71.39 71.58 71.77 71.95 90.89 90.32 90.05 90.05 90.05 90.10 90.18 90.28 90.39 90.52 90.66 90.82 90.98 91.14 91.29 91.42 91.50 91.52 91.44 91.24 90.88 76.39 76.43 76.47 76.50 76.49 76.43 76.28 76.19 76.20 76.20 76.20 76.20 76.20 76.20 76.20 76.21 76.24 76.27 76.30 76.35 76.39 94.06 94.05 94.05 94.05 94.05 94.05 94.05 94.05 94.05 94.07 94.11 94.15 94.20 94.26 94.31 94.36 94.39 94.40 94.36 94.26 94.05 78.17 78.17 78.16 78.17 78.17 78.16 78.16 78.16 78.16 78.16 78.17 78.17 78.17 78.17 78.17 78.17 V Max (kV) 64.62 66.87 67.47 66.40 63.70 62.71 62.49 63.68 62.66 61.29 62.49 64.46 64.84 63.62 60.84 58.91 58.92 58.92 58.92 60.82 64.65 74.72 74.34 67.33 69.82 72.12 66.87 64.46 63.80 63.99 62.75 61.78 61.50 65.34 67.58 68.16 67.05 68.51 70.89 72.35 74.45 74.72 82.32 81.60 80.64 79.44 78.84 79.14 79.48 79.86 80.28 80.71 81.16 81.61 82.04 82.44 82.78 83.04 83.20 83.23 83.11 82.81 82.31 83.38 84.00 85.94 85.62 84.17 83.62 71.91 71.50 70.88 70.46 70.48 70.55 70.65 70.76 70.90 71.05 71.21 79.16 78.26 80.20 83.31 90.89 90.32 90.05 90.05 90.05 90.10 90.18 90.28 90.39 90.52 90.66 90.82 90.98 91.14 91.29 91.42 91.50 91.52 91.44 91.24 90.88 82.07 81.48 82.07 83.19 82.31 76.43 76.28 76.19 76.20 76.20 76.20 76.20 76.20 76.20 76.20 76.21 76.24 76.27 76.30 76.35 82.06 94.06 94.05 94.05 94.05 94.05 94.05 94.05 94.05 94.05 94.07 94.11 94.15 94.20 94.26 94.31 94.36 94.39 94.40 94.36 94.26 94.05 78.17 78.17 81.01 80.23 78.17 78.16 78.16 78.16 78.16 78.16 78.17 78.17 78.17 78.17 78.17 78.17 Ratio Vmax/Vnom 1.20 1.24 1.25 1.23 1.18 1.16 1.16 1.18 1.16 1.14 1.16 1.20 1.20 1.18 1.13 1.09 1.09 1.09 1.09 1.13 1.20 1.39 1.38 1.25 1.30 1.34 1.24 1.20 1.18 1.19 1.16 1.15 1.14 1.21 1.25 1.26 1.24 1.27 1.32 1.34 1.38 1.39 1.53 1.51 1.50 1.47 1.46 1.47 1.47 1.48 1.49 1.50 1.51 1.51 1.52 1.53 1.54 1.54 1.54 1.54 1.54 1.54 1.53 1.55 1.56 1.59 1.59 1.56 1.55 1.33 1.33 1.32 1.31 1.31 1.31 1.31 1.31 1.32 1.32 1.32 1.47 1.45 1.49 1.55 1.69 1.68 1.67 1.67 1.67 1.67 1.67 1.68 1.68 1.68 1.68 1.69 1.69 1.69 1.69 1.70 1.70 1.70 1.70 1.69 1.69 1.52 1.51 1.52 1.54 1.53 1.42 1.42 1.41 1.41 1.41 1.41 1.41 1.41 1.41 1.41 1.41 1.41 1.42 1.42 1.42 1.52 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.45 1.45 1.50 1.49 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 Simulation 5 Variables Simulation 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 Start-Delay (s) 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 Va (kV) 84.19 84.43 84.70 84.90 85.10 83.00 82.97 82.88 82.84 82.78 82.22 82.37 82.48 82.57 82.70 82.75 82.85 82.90 82.94 82.98 82.99 83.02 83.02 83.02 82.98 82.96 85.47 85.66 125.58 125.52 80.99 81.08 81.19 81.39 81.62 81.89 82.18 82.49 82.84 83.19 83.55 83.91 84.28 84.62 84.94 85.22 85.46 81.23 81.19 81.15 81.07 80.30 80.46 80.58 80.69 80.81 80.93 81.00 81.08 81.13 81.18 81.21 81.24 81.25 81.25 81.25 81.24 81.21 86.06 86.29 126.47 126.46 80.83 80.90 81.03 81.22 81.46 81.75 82.09 82.48 82.89 83.32 83.76 84.19 84.63 85.05 85.42 85.75 86.06 79.33 79.30 79.25 79.18 78.38 78.53 78.67 78.81 78.93 79.02 79.12 79.19 79.25 79.30 79.33 79.35 79.37 79.37 79.36 79.34 79.31 86.69 86.93 127.24 127.18 80.81 80.86 81.02 81.24 81.50 81.84 82.24 82.67 83.14 83.64 84.15 84.65 85.15 85.59 86.03 86.39 86.69 77.36 77.32 77.25 77.20 76.38 76.53 76.67 76.81 76.93 77.04 77.15 77.21 77.27 77.31 77.34 77.38 77.38 77.38 77.37 77.37 77.35 87.01 87.20 127.74 127.75 80.95 80.99 81.17 81.41 81.73 82.11 82.55 Vb (kV) 117.70 117.67 117.65 117.56 117.53 73.70 75.08 74.66 72.29 68.79 69.29 69.47 69.06 69.97 70.34 70.12 70.59 71.09 70.99 70.83 71.34 71.27 71.21 71.22 70.95 73.74 116.15 116.06 82.41 82.31 116.36 116.42 116.40 116.44 116.47 116.48 116.47 116.46 116.43 116.38 116.34 116.34 116.26 116.26 116.22 116.14 116.12 73.89 75.25 74.86 72.52 68.78 69.33 69.61 69.25 70.08 70.61 70.43 70.83 71.51 71.42 71.20 71.85 71.78 71.73 71.76 71.37 73.92 114.92 114.81 79.20 79.10 115.13 115.20 115.16 115.21 115.24 115.25 115.25 115.23 115.20 115.15 115.16 115.11 115.06 115.02 115.01 114.90 114.88 74.06 75.46 75.05 72.74 68.93 69.50 69.88 69.55 70.29 70.95 70.78 71.11 71.94 71.87 71.55 72.35 72.28 72.24 72.28 71.78 74.10 113.86 113.84 76.06 75.99 114.08 114.15 114.16 114.16 114.19 114.20 114.20 114.18 114.14 114.11 114.13 114.05 114.06 113.96 113.95 113.92 113.82 74.24 75.68 75.28 72.96 69.22 69.80 70.25 69.93 70.56 71.34 71.18 71.41 72.37 72.33 71.91 72.83 72.78 72.74 72.79 72.17 74.27 113.00 112.97 73.25 73.21 113.32 113.28 113.35 113.34 113.31 113.33 113.33 Vc (kV) 71.87 72.15 72.19 72.29 72.44 75.16 74.45 74.47 75.53 75.06 74.40 76.11 76.01 79.52 81.28 81.02 78.79 74.69 74.39 74.40 74.80 74.71 74.64 74.40 74.76 75.13 73.01 72.45 80.48 80.46 72.42 73.62 74.20 73.04 74.05 74.76 74.49 77.03 77.69 76.41 73.25 72.66 72.37 72.72 72.75 72.81 73.03 76.70 75.93 75.96 76.87 76.29 75.40 77.04 76.85 79.79 81.54 81.26 79.00 76.24 75.96 76.01 76.40 76.33 76.26 76.02 76.36 76.67 73.56 73.01 80.32 80.08 72.98 74.08 74.70 73.56 74.42 75.14 74.60 77.15 77.82 76.54 73.38 73.16 72.87 73.27 73.27 73.29 73.57 78.08 77.25 77.32 78.10 77.43 76.41 77.92 77.64 80.05 81.79 81.49 79.21 77.64 77.37 77.45 77.84 77.76 77.70 77.47 77.79 78.05 74.05 73.53 77.59 77.68 73.48 74.50 75.15 74.03 74.76 75.50 74.70 77.27 77.94 76.67 73.82 73.65 73.35 73.79 73.77 73.75 74.07 79.32 78.42 78.57 79.22 78.46 77.75 78.76 78.39 80.31 82.04 81.72 79.41 78.90 78.63 78.75 79.12 79.04 78.98 78.76 79.08 79.28 74.51 74.00 77.33 77.43 73.93 74.89 75.56 74.45 75.09 75.84 74.81 V Max (kV) 117.70 117.67 117.65 117.56 117.53 83.00 82.97 82.88 82.84 82.78 82.22 82.37 82.48 82.57 82.70 82.75 82.85 82.90 82.94 82.98 82.99 83.02 83.02 83.02 82.98 82.96 116.15 116.06 125.58 125.52 116.36 116.42 116.40 116.44 116.47 116.48 116.47 116.46 116.43 116.38 116.34 116.34 116.26 116.26 116.22 116.14 116.12 81.23 81.19 81.15 81.07 80.30 80.46 80.58 80.69 80.81 81.54 81.26 81.08 81.13 81.18 81.21 81.24 81.25 81.25 81.25 81.24 81.21 114.92 114.81 126.47 126.46 115.13 115.20 115.16 115.21 115.24 115.25 115.25 115.23 115.20 115.15 115.16 115.11 115.06 115.02 115.01 114.90 114.88 79.33 79.30 79.25 79.18 78.38 78.53 78.67 78.81 80.05 81.79 81.49 79.21 79.25 79.30 79.33 79.35 79.37 79.37 79.36 79.34 79.31 113.86 113.84 127.24 127.18 114.08 114.15 114.16 114.16 114.19 114.20 114.20 114.18 114.14 114.11 114.13 114.05 114.06 113.96 113.95 113.92 113.82 79.32 78.42 78.57 79.22 78.46 77.75 78.76 78.39 80.31 82.04 81.72 79.41 78.90 78.63 78.75 79.12 79.04 78.98 78.76 79.08 79.28 113.00 112.97 127.74 127.75 113.32 113.28 113.35 113.34 113.31 113.33 113.33 Line Length=10km Ratio Vmax/Vnom 2.18 2.18 2.18 2.18 2.18 1.54 1.54 1.54 1.54 1.54 1.53 1.53 1.53 1.53 1.53 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 1.54 2.16 2.15 2.33 2.33 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.15 1.51 1.51 1.51 1.50 1.49 1.49 1.50 1.50 1.50 1.51 1.51 1.50 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.51 2.13 2.13 2.35 2.35 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.14 2.13 2.13 2.13 2.13 1.47 1.47 1.47 1.47 1.45 1.46 1.46 1.46 1.49 1.52 1.51 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 2.11 2.11 2.36 2.36 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.11 2.11 2.11 2.11 1.47 1.46 1.46 1.47 1.46 1.44 1.46 1.45 1.49 1.52 1.52 1.47 1.46 1.46 1.46 1.47 1.47 1.47 1.46 1.47 1.47 2.10 2.10 2.37 2.37 2.10 2.10 2.10 2.10 2.10 2.10 2.10 Va (kV) 64.80 64.97 65.00 64.87 64.67 53.56 55.56 55.43 55.28 55.11 54.93 54.74 54.55 54.36 54.17 54.00 53.84 53.70 53.58 53.57 53.64 53.68 53.69 53.66 53.61 53.54 62.72 63.09 62.95 97.02 62.50 62.34 62.18 62.23 62.63 62.38 62.16 62.33 62.57 62.39 62.27 62.18 62.38 62.51 62.46 62.46 62.75 56.19 56.06 55.91 55.72 55.52 55.30 55.07 54.84 54.60 54.38 54.17 53.97 53.80 53.66 53.54 53.60 53.65 53.66 53.63 53.56 56.17 64.41 64.07 64.81 95.76 60.73 60.62 60.36 60.09 60.36 60.95 60.76 60.57 61.27 61.95 61.96 62.10 62.36 62.76 63.29 63.94 64.38 56.69 56.54 56.35 56.14 55.90 55.64 55.38 55.10 54.83 54.57 54.32 54.10 53.90 53.73 53.59 53.56 53.62 53.63 53.59 53.54 56.67 62.09 62.05 61.84 95.53 61.20 61.45 61.68 61.47 61.37 61.44 61.90 61.75 61.76 62.00 62.20 62.16 62.15 62.16 62.14 62.05 62.10 57.14 56.97 56.76 56.52 56.25 55.96 55.66 55.35 55.04 54.75 54.47 54.21 53.98 53.79 53.64 53.54 53.59 53.60 53.56 53.58 57.12 57.96 57.90 58.18 95.02 59.40 59.35 59.09 59.09 59.13 59.12 58.77 Vb (kV) 75.68 75.60 75.55 75.80 75.80 74.64 73.90 73.89 73.91 73.96 74.03 74.12 74.25 74.41 74.61 74.86 75.14 75.46 75.81 76.16 76.47 76.69 76.74 76.51 75.87 74.65 77.57 77.56 77.39 54.11 77.52 77.33 77.37 77.47 77.56 77.45 77.32 77.24 77.20 77.23 77.32 77.27 76.97 77.22 77.40 77.28 77.47 77.30 77.30 77.29 77.28 77.27 77.29 77.33 77.39 77.47 77.57 77.70 77.87 78.07 78.29 78.53 78.76 78.93 78.97 78.77 78.18 77.30 78.94 79.23 79.09 54.27 79.24 79.06 78.89 78.79 78.89 78.99 79.01 78.94 78.90 78.92 78.82 78.58 78.64 78.93 78.73 78.98 78.83 79.80 79.79 79.78 79.77 79.76 79.75 79.74 79.76 79.80 79.85 79.92 80.01 80.13 80.27 80.43 80.59 80.72 80.75 80.58 80.07 79.79 80.39 80.53 80.44 54.43 80.58 80.42 80.27 80.20 80.32 80.42 80.32 80.25 80.22 80.23 80.24 79.98 80.02 80.25 80.16 80.31 80.27 81.66 81.65 81.64 81.63 81.63 81.62 81.61 81.60 81.61 81.62 81.64 81.69 81.76 81.85 81.95 82.06 82.16 82.18 82.04 81.66 81.65 81.47 81.82 81.76 54.57 81.89 81.75 81.62 81.48 81.36 81.25 81.19 Vc (kV) 76.56 76.58 76.61 76.64 76.67 91.69 91.68 91.67 91.66 91.65 91.64 91.65 91.66 91.67 91.69 91.73 91.77 91.83 91.88 91.94 91.99 92.03 92.03 92.00 91.89 91.71 77.79 77.80 77.80 77.80 77.79 77.76 77.77 77.78 77.80 77.81 77.82 77.83 77.83 77.83 77.83 77.82 77.81 77.80 77.79 77.79 77.79 93.11 93.10 93.10 93.09 93.08 93.07 93.07 93.08 93.09 93.10 93.11 93.12 93.13 93.13 93.14 93.14 93.16 93.16 93.14 93.14 93.14 78.50 78.48 78.47 78.47 78.48 78.50 78.51 78.52 78.54 78.55 78.56 78.57 78.57 78.57 78.57 78.56 78.55 78.54 78.52 78.51 78.49 93.84 93.84 93.83 93.82 93.81 93.81 93.81 93.82 93.83 93.84 93.85 93.86 93.86 93.87 93.87 93.88 93.88 93.88 93.88 93.88 93.87 78.95 78.94 78.92 78.92 78.94 78.95 78.96 78.98 78.99 79.00 79.01 79.02 79.02 79.02 79.02 79.01 79.01 78.99 78.98 78.96 78.94 94.21 94.21 94.20 94.19 94.19 94.18 94.18 94.19 94.20 94.21 94.22 94.23 94.23 94.24 94.24 94.25 94.25 94.25 94.25 94.25 94.24 79.25 79.23 79.22 79.22 79.23 79.25 79.26 79.27 79.29 79.30 79.31 V Max (kV) 76.56 76.58 76.61 76.64 76.67 91.69 91.68 91.67 91.66 91.65 91.64 91.65 91.66 91.67 91.69 91.73 91.77 91.83 91.88 91.94 91.99 92.03 92.03 92.00 91.89 91.71 77.79 77.80 77.80 97.02 77.79 77.76 77.77 77.78 77.80 77.81 77.82 77.83 77.83 77.83 77.83 77.82 77.81 77.80 77.79 77.79 77.79 93.11 93.10 93.10 93.09 93.08 93.07 93.07 93.08 93.09 93.10 93.11 93.12 93.13 93.13 93.14 93.14 93.16 93.16 93.14 93.14 93.14 78.94 79.23 79.09 95.76 79.24 79.06 78.89 78.79 78.89 78.99 79.01 78.94 78.90 78.92 78.82 78.58 78.64 78.93 78.73 78.98 78.83 93.84 93.84 93.83 93.82 93.81 93.81 93.81 93.82 93.83 93.84 93.85 93.86 93.86 93.87 93.87 93.88 93.88 93.88 93.88 93.88 93.87 80.39 80.53 80.44 95.53 80.58 80.42 80.27 80.20 80.32 80.42 80.32 80.25 80.22 80.23 80.24 79.98 80.02 80.25 80.16 80.31 80.27 94.21 94.21 94.20 94.19 94.19 94.18 94.18 94.19 94.20 94.21 94.22 94.23 94.23 94.24 94.24 94.25 94.25 94.25 94.25 94.25 94.24 81.47 81.82 81.76 95.02 81.89 81.75 81.62 81.48 81.36 81.25 81.19 Line Length=0.2km Ratio Vmax/Vnom 1.42 1.42 1.42 1.42 1.42 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.70 1.44 1.44 1.44 1.80 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.46 1.47 1.47 1.78 1.47 1.47 1.46 1.46 1.46 1.47 1.47 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.47 1.46 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.49 1.49 1.49 1.77 1.50 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.48 1.48 1.49 1.49 1.49 1.49 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.51 1.52 1.52 1.76 1.52 1.52 1.51 1.51 1.51 1.51 1.51 Va (kV) 53.90 53.92 53.91 53.88 53.83 55.88 55.77 55.63 55.47 55.30 55.11 54.91 54.71 54.51 54.31 54.13 53.96 53.81 53.69 53.59 53.62 53.65 53.66 53.64 53.59 55.86 53.83 53.76 83.35 80.53 54.84 54.72 54.59 54.45 54.30 54.15 54.00 53.86 53.76 53.68 53.69 53.77 53.83 53.86 53.87 53.85 53.81 56.40 56.27 56.10 55.91 55.70 55.47 55.23 54.98 54.74 54.51 54.29 54.08 53.90 53.75 53.63 53.59 53.63 53.64 53.61 56.49 56.38 53.81 53.75 53.67 82.32 55.13 55.01 54.86 54.71 54.54 54.36 54.18 54.01 53.86 53.74 53.65 53.69 53.76 53.81 53.83 53.82 53.79 56.89 56.73 56.54 56.31 56.07 55.80 55.52 55.24 54.96 54.69 54.43 54.19 53.98 53.81 53.67 53.57 53.62 53.63 53.60 56.99 56.87 53.79 53.74 53.67 83.72 55.40 55.27 55.12 54.94 54.76 54.56 54.36 54.17 53.99 53.82 53.69 53.61 53.70 53.76 53.80 53.80 53.78 57.34 57.16 56.94 56.69 56.41 56.11 55.79 55.47 55.16 54.85 54.56 54.29 54.06 53.86 53.70 53.59 53.60 53.62 53.58 57.45 57.32 53.78 53.73 53.66 84.85 55.66 55.52 55.36 55.17 54.96 54.75 54.53 Vb (kV) 58.91 58.69 58.45 58.09 57.45 77.69 77.69 77.69 77.69 77.69 77.69 77.70 77.74 77.79 77.86 77.96 78.08 78.23 78.41 78.61 78.81 78.97 79.00 78.80 78.19 77.69 59.76 61.39 54.36 54.18 63.43 62.80 61.46 58.79 59.05 59.32 59.42 59.20 58.98 58.82 58.73 58.73 58.75 58.76 58.38 58.18 59.83 80.87 80.87 80.87 80.87 80.87 80.87 80.87 80.87 80.87 80.88 80.92 80.97 81.04 81.13 81.24 81.35 81.45 81.47 81.32 80.87 80.87 61.17 63.76 64.60 54.34 65.35 64.14 62.84 60.49 59.65 59.21 59.13 58.99 58.76 58.60 58.50 58.46 58.43 58.18 58.32 58.60 61.24 83.00 83.00 83.00 83.00 83.00 83.00 83.00 83.00 83.00 83.00 83.00 83.00 83.03 83.07 83.13 83.19 83.25 83.26 83.16 83.00 83.00 63.26 64.73 65.84 54.48 67.09 66.32 64.04 61.90 59.23 59.65 59.28 58.69 58.63 58.14 57.88 58.17 58.09 58.42 57.62 60.23 63.34 84.50 84.50 84.50 84.50 84.50 84.50 84.50 84.50 84.50 84.50 84.50 84.49 84.49 84.49 84.52 84.56 84.59 84.60 84.53 84.50 84.50 63.76 65.76 67.14 54.62 67.81 67.32 65.37 63.22 60.75 58.93 59.27 Vc (kV) 78.17 78.17 78.16 78.16 78.16 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.39 95.40 95.40 95.39 95.37 95.37 79.00 78.99 78.99 78.99 78.99 78.99 78.99 78.99 78.99 78.99 79.00 79.00 79.00 79.00 79.00 79.00 79.00 78.99 78.99 78.99 78.99 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 79.41 79.41 79.41 79.40 79.41 79.41 79.40 79.40 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.40 95.75 95.75 95.75 95.75 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 79.65 79.65 79.64 79.64 79.65 79.64 79.64 79.64 79.64 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.64 79.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 79.80 79.80 79.79 79.79 79.79 79.79 79.79 79.79 79.79 79.79 79.80 V Max (kV) 78.17 78.17 78.16 78.16 78.16 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.37 95.39 95.40 95.40 95.39 95.37 95.37 79.00 78.99 83.35 80.53 78.99 78.99 78.99 78.99 78.99 78.99 79.00 79.00 79.00 79.00 79.00 79.00 79.00 78.99 78.99 78.99 78.99 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 95.74 79.41 79.41 79.41 82.32 79.41 79.41 79.40 79.40 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.41 79.40 95.75 95.75 95.75 95.75 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 95.76 79.65 79.65 79.64 83.72 79.65 79.64 79.64 79.64 79.64 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.65 79.64 79.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 95.64 79.80 79.80 79.79 84.85 79.79 79.79 79.79 79.79 79.79 79.79 79.80 Ratio Vmax/Vnom 1.45 1.45 1.45 1.45 1.45 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.47 1.47 1.55 1.49 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.47 1.47 1.47 1.53 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.48 1.48 1.48 1.55 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.48 1.48 1.48 1.57 1.48 1.48 1.48 1.48 1.48 1.48 1.48 Simulation 5 Variables Simulation 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 Start-Delay (s) 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 35 35 35 35 35 35 35 35 35 35 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Va (kV) 83.03 83.54 84.07 84.59 85.12 85.61 86.05 86.45 86.80 87.02 75.33 75.28 75.20 75.16 74.32 74.48 74.63 74.77 74.90 75.02 75.11 75.18 75.24 75.27 75.31 75.33 75.35 75.35 75.33 75.34 75.32 86.57 86.64 128.21 81.20 81.16 81.25 81.38 81.65 81.98 82.38 82.83 83.32 83.83 84.34 84.83 85.30 85.72 85.98 86.31 86.44 86.55 73.24 73.18 73.17 72.08 72.24 72.40 72.56 72.72 72.83 72.92 73.02 73.12 73.18 73.23 73.25 73.30 73.26 73.26 73.28 73.25 73.23 84.93 84.83 128.38 81.34 81.31 81.39 81.54 81.79 82.11 82.49 82.90 83.33 83.75 84.13 84.50 84.79 84.95 85.06 85.01 84.99 84.89 71.19 71.13 71.10 70.01 70.17 70.32 70.47 70.64 70.78 70.87 70.96 71.05 71.13 71.14 71.16 71.20 71.21 71.22 71.19 71.21 71.19 82.65 82.57 128.56 81.20 81.16 81.25 81.39 81.58 81.83 82.15 82.47 82.77 83.03 83.21 83.27 83.25 83.15 82.99 82.84 82.70 82.60 57.53 59.50 59.22 58.89 58.50 58.07 57.61 57.11 56.60 56.09 56.25 56.69 57.06 57.37 57.60 57.77 57.87 57.88 57.83 57.70 57.49 64.46 65.02 125.45 59.36 59.43 59.44 Vb (kV) 113.30 113.31 113.33 113.26 113.26 113.19 113.19 113.07 113.06 113.04 74.41 75.89 75.53 73.21 69.62 70.17 70.69 70.37 70.90 71.76 71.62 71.73 72.81 72.79 72.30 73.30 73.26 73.24 73.29 72.56 74.44 112.38 112.31 70.84 112.58 112.61 112.65 112.64 112.70 112.73 112.70 112.70 112.72 112.68 112.62 112.60 112.58 112.52 112.48 112.48 112.35 112.34 74.57 76.10 75.77 73.49 70.10 70.62 71.18 70.87 71.27 72.21 72.07 72.07 73.25 73.25 72.80 73.75 73.74 73.73 73.77 72.93 74.61 111.83 111.82 68.77 112.09 112.06 112.15 112.16 112.14 112.18 112.20 112.19 112.17 112.12 112.12 112.12 112.02 112.05 111.95 111.93 111.92 111.79 74.76 76.30 76.01 73.76 70.64 71.12 71.71 71.39 71.68 72.67 72.54 72.43 73.68 73.71 73.29 74.18 74.20 74.20 74.24 73.30 74.80 111.50 111.40 66.95 111.67 111.78 111.73 111.81 111.81 111.76 111.78 111.77 111.75 111.78 111.78 111.70 111.74 111.63 111.64 111.52 111.50 111.49 77.64 78.37 78.20 76.57 76.29 76.36 76.72 76.43 76.28 77.00 76.93 76.43 77.41 77.61 77.27 77.66 77.94 77.94 77.99 77.28 77.62 98.99 98.23 56.41 109.52 109.53 109.59 Vc (kV) 77.38 78.06 76.80 74.29 74.11 73.81 74.27 74.23 74.17 74.53 80.42 79.48 79.71 80.25 79.40 79.01 79.57 79.12 80.57 82.28 81.94 79.64 80.04 79.77 79.91 80.26 80.17 80.13 79.91 80.23 80.38 74.93 74.43 77.18 75.47 74.33 75.25 75.93 74.83 75.40 76.17 75.06 77.49 78.19 76.93 74.75 74.55 74.24 74.72 74.66 74.56 74.95 81.41 80.42 80.75 81.20 80.26 80.16 80.34 79.98 80.91 82.53 82.16 80.70 81.06 80.80 80.96 81.28 81.19 81.15 80.95 81.27 81.37 75.31 74.83 77.08 75.82 74.69 75.57 76.27 75.18 75.70 76.47 75.37 77.60 78.30 77.05 75.18 74.96 74.65 75.14 75.05 74.93 75.33 82.29 81.26 81.70 82.06 81.05 81.22 81.31 81.02 81.41 82.84 82.39 81.66 81.99 81.72 81.89 82.19 82.10 82.06 81.87 82.19 82.25 75.66 75.19 77.03 76.13 75.01 75.87 76.58 75.49 75.97 76.76 75.65 77.71 78.42 77.17 75.58 75.33 75.03 75.53 75.42 75.26 75.68 87.75 87.72 87.73 87.65 87.59 87.61 87.57 87.52 87.57 87.62 87.66 87.73 87.75 87.79 87.82 87.84 87.85 87.85 87.84 87.85 87.80 77.80 77.51 77.43 77.96 77.45 77.57 V Max (kV) 113.30 113.31 113.33 113.26 113.26 113.19 113.19 113.07 113.06 113.04 80.42 79.48 79.71 80.25 79.40 79.01 79.57 79.12 80.57 82.28 81.94 79.64 80.04 79.77 79.91 80.26 80.17 80.13 79.91 80.23 80.38 112.38 112.31 128.21 112.58 112.61 112.65 112.64 112.70 112.73 112.70 112.70 112.72 112.68 112.62 112.60 112.58 112.52 112.48 112.48 112.35 112.34 81.41 80.42 80.75 81.20 80.26 80.16 80.34 79.98 80.91 82.53 82.16 80.70 81.06 80.80 80.96 81.28 81.19 81.15 80.95 81.27 81.37 111.83 111.82 128.38 112.09 112.06 112.15 112.16 112.14 112.18 112.20 112.19 112.17 112.12 112.12 112.12 112.02 112.05 111.95 111.93 111.92 111.79 82.29 81.26 81.70 82.06 81.05 81.22 81.31 81.02 81.41 82.84 82.39 81.66 81.99 81.72 81.89 82.19 82.10 82.06 81.87 82.19 82.25 111.50 111.40 128.56 111.67 111.78 111.73 111.81 111.81 111.76 111.78 111.77 111.75 111.78 111.78 111.70 111.74 111.63 111.64 111.52 111.50 111.49 87.75 87.72 87.73 87.65 87.59 87.61 87.57 87.52 87.57 87.62 87.66 87.73 87.75 87.79 87.82 87.84 87.85 87.85 87.84 87.85 87.80 98.99 98.23 125.45 109.52 109.53 109.59 Line Length=10km Ratio Vmax/Vnom 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 1.49 1.47 1.48 1.49 1.47 1.47 1.48 1.47 1.50 1.53 1.52 1.48 1.49 1.48 1.48 1.49 1.49 1.49 1.48 1.49 1.49 2.09 2.08 2.38 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.08 2.08 1.51 1.49 1.50 1.51 1.49 1.49 1.49 1.48 1.50 1.53 1.52 1.50 1.50 1.50 1.50 1.51 1.51 1.51 1.50 1.51 1.51 2.08 2.07 2.38 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.07 1.53 1.51 1.52 1.52 1.50 1.51 1.51 1.50 1.51 1.54 1.53 1.52 1.52 1.52 1.52 1.53 1.52 1.52 1.52 1.53 1.53 2.07 2.07 2.39 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 2.07 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.62 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.63 1.84 1.82 2.33 2.03 2.03 2.03 Va (kV) 58.79 58.78 58.51 58.23 58.11 58.00 57.86 57.79 57.83 57.98 57.57 57.38 57.14 56.87 56.58 56.25 55.92 55.58 55.24 54.91 54.60 54.31 54.06 53.85 53.68 53.56 53.56 53.58 53.54 57.69 57.55 57.66 58.45 58.97 94.37 55.86 55.80 55.83 55.87 55.64 55.53 55.48 55.29 55.34 55.29 55.55 55.98 56.30 56.68 57.29 57.55 57.68 57.96 57.75 57.50 57.20 56.88 56.53 56.16 55.79 55.41 55.06 54.72 54.41 54.13 53.90 53.72 53.59 53.54 53.56 53.55 58.10 57.94 59.60 60.63 60.99 94.36 56.03 56.03 56.00 55.94 55.84 55.72 55.58 55.41 55.23 55.04 55.70 56.36 57.00 57.83 58.53 59.12 59.65 58.32 58.10 57.82 57.51 57.15 56.78 56.38 55.98 55.58 55.19 54.83 54.49 54.20 53.95 53.75 53.61 53.54 53.54 53.57 58.47 58.30 61.67 62.24 62.67 94.18 56.25 56.25 56.21 56.14 56.03 55.90 55.74 55.56 55.36 55.32 56.31 57.30 58.23 59.09 59.89 60.60 61.90 60.66 60.33 59.92 59.45 58.93 58.37 57.79 57.20 56.61 56.04 55.51 55.02 54.59 54.23 53.94 53.74 53.63 53.61 61.05 60.89 60.64 64.93 65.74 66.42 57.75 57.77 57.75 Vb (kV) 81.23 81.21 81.11 81.13 81.22 81.35 81.47 81.34 81.61 81.50 83.08 83.07 83.06 83.06 83.05 83.04 83.03 83.02 83.03 83.04 83.05 83.06 83.07 83.11 83.18 83.25 83.32 83.34 83.23 83.08 83.08 82.50 82.76 82.76 54.70 82.86 82.74 82.62 82.51 82.40 82.31 82.40 82.44 82.42 82.32 82.18 82.24 82.34 82.48 82.37 82.57 82.52 84.19 84.18 84.17 84.17 84.16 84.15 84.14 84.13 84.14 84.15 84.16 84.17 84.18 84.18 84.19 84.23 84.28 84.29 84.20 84.19 84.19 81.97 82.69 81.43 54.83 83.72 83.61 83.51 83.55 83.46 83.38 83.32 83.27 83.24 83.23 83.25 83.28 82.94 83.14 83.42 82.79 81.83 85.07 85.07 85.06 85.05 85.04 85.03 85.02 85.02 85.03 85.04 85.05 85.05 85.06 85.07 85.07 85.08 85.08 85.08 85.08 85.08 85.07 80.41 79.57 78.69 54.94 84.58 84.49 84.41 84.33 84.25 84.19 84.14 84.09 83.87 83.75 83.54 83.20 82.74 82.13 80.94 81.06 80.22 88.87 88.86 88.86 88.85 88.84 88.83 88.82 88.82 88.83 88.84 88.85 88.85 88.86 88.87 88.87 88.88 88.88 88.88 88.88 88.87 88.87 65.61 65.76 65.63 80.54 80.41 80.09 Vc (kV) 79.32 79.32 79.32 79.32 79.31 79.30 79.29 79.27 79.26 79.24 94.39 94.38 94.38 94.37 94.36 94.35 94.35 94.36 94.37 94.38 94.39 94.40 94.41 94.41 94.42 94.42 94.42 94.42 94.42 94.42 94.41 79.45 79.44 79.42 79.42 79.43 79.45 79.46 79.48 79.49 79.50 79.51 79.52 79.52 79.52 79.52 79.51 79.50 79.49 79.48 79.46 79.44 94.45 94.45 94.44 94.43 94.42 94.41 94.41 94.42 94.43 94.44 94.45 94.46 94.47 94.47 94.48 94.48 94.48 94.48 94.48 94.48 94.48 79.60 79.58 79.57 79.57 79.58 79.59 79.61 79.62 79.63 79.65 79.66 79.66 79.67 79.67 79.67 79.66 79.65 79.64 79.62 79.61 79.59 94.45 94.45 94.44 94.43 94.43 94.42 94.42 94.43 94.44 94.44 94.45 94.46 94.47 94.48 94.48 94.48 94.49 94.49 94.48 94.48 94.48 79.71 79.69 79.68 79.67 79.69 79.70 79.71 79.73 79.74 79.75 79.76 79.77 79.78 79.78 79.77 79.77 79.76 79.75 79.73 79.71 79.70 93.87 93.86 93.86 93.85 93.84 93.83 93.83 93.84 93.85 93.86 93.86 93.87 93.88 93.89 93.89 93.89 93.90 93.90 93.89 93.89 93.89 80.08 80.07 80.05 80.05 80.06 80.07 V Max (kV) 81.23 81.21 81.11 81.13 81.22 81.35 81.47 81.34 81.61 81.50 94.39 94.38 94.38 94.37 94.36 94.35 94.35 94.36 94.37 94.38 94.39 94.40 94.41 94.41 94.42 94.42 94.42 94.42 94.42 94.42 94.41 82.50 82.76 82.76 94.37 82.86 82.74 82.62 82.51 82.40 82.31 82.40 82.44 82.42 82.32 82.18 82.24 82.34 82.48 82.37 82.57 82.52 94.45 94.45 94.44 94.43 94.42 94.41 94.41 94.42 94.43 94.44 94.45 94.46 94.47 94.47 94.48 94.48 94.48 94.48 94.48 94.48 94.48 81.97 82.69 81.43 94.36 83.72 83.61 83.51 83.55 83.46 83.38 83.32 83.27 83.24 83.23 83.25 83.28 82.94 83.14 83.42 82.79 81.83 94.45 94.45 94.44 94.43 94.43 94.42 94.42 94.43 94.44 94.44 94.45 94.46 94.47 94.48 94.48 94.48 94.49 94.49 94.48 94.48 94.48 80.41 79.69 79.68 94.18 84.58 84.49 84.41 84.33 84.25 84.19 84.14 84.09 83.87 83.75 83.54 83.20 82.74 82.13 80.94 81.06 80.22 93.87 93.86 93.86 93.85 93.84 93.83 93.83 93.84 93.85 93.86 93.86 93.87 93.88 93.89 93.89 93.89 93.90 93.90 93.89 93.89 93.89 80.08 80.07 80.05 80.54 80.41 80.09 Line Length=0.2km Ratio Vmax/Vnom 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.53 1.54 1.54 1.75 1.54 1.54 1.53 1.53 1.53 1.53 1.53 1.53 1.53 1.53 1.52 1.53 1.53 1.53 1.53 1.53 1.53 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.52 1.53 1.51 1.75 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.54 1.54 1.54 1.55 1.54 1.54 1.55 1.54 1.52 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.49 1.48 1.48 1.75 1.57 1.57 1.57 1.56 1.56 1.56 1.56 1.56 1.56 1.55 1.55 1.54 1.54 1.52 1.50 1.50 1.49 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.49 1.49 1.49 1.49 1.49 1.49 Va (kV) 54.31 54.11 53.93 53.77 53.64 53.63 53.71 53.76 53.78 53.76 57.75 57.56 57.31 57.04 56.73 56.39 56.05 55.69 55.34 55.00 54.68 54.38 54.12 53.91 53.73 53.61 53.59 53.61 53.58 57.88 57.74 53.76 53.73 53.66 85.76 55.90 55.76 55.58 55.38 55.16 54.92 54.68 54.45 54.22 54.02 53.84 53.70 53.59 53.66 53.73 53.75 53.75 58.14 57.92 57.66 57.36 57.02 56.66 56.28 55.89 55.51 55.14 54.79 54.47 54.19 53.95 53.76 53.62 53.59 53.60 53.58 58.28 58.12 53.75 53.72 53.66 86.51 56.13 55.98 55.79 55.57 55.34 55.08 54.82 54.57 54.33 54.11 53.92 53.76 53.63 53.62 53.69 53.73 53.73 58.50 58.27 57.98 57.66 57.29 56.90 56.49 56.08 55.67 55.27 54.89 54.55 54.24 53.98 53.78 53.64 53.58 53.60 58.77 58.65 58.48 53.74 53.71 53.65 87.13 56.34 56.18 55.99 55.76 55.50 55.23 54.96 54.69 54.43 54.19 53.98 53.81 53.67 53.60 53.66 53.71 53.72 60.85 60.50 60.08 59.60 59.06 58.49 57.88 57.27 56.67 56.08 55.53 55.03 54.59 54.22 53.92 53.71 53.60 53.58 61.26 61.09 60.83 53.65 53.65 55.24 58.02 57.87 57.65 Vb (kV) 58.78 58.51 57.84 57.73 58.04 57.92 57.54 58.76 61.75 63.76 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.60 85.62 85.62 85.60 85.60 85.61 64.74 66.79 68.71 54.75 68.48 67.78 66.23 64.12 61.81 59.23 58.65 58.56 58.25 58.10 57.94 57.45 57.24 57.49 59.93 62.74 64.73 86.45 86.45 86.45 86.45 86.45 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.44 86.45 86.45 65.98 67.99 69.13 54.87 69.50 68.92 67.44 65.07 62.47 60.01 58.72 58.23 58.24 57.56 57.29 57.12 57.04 58.17 60.66 63.34 65.97 87.11 87.11 87.11 87.11 87.11 87.11 87.11 87.10 87.10 87.10 87.10 87.10 87.10 87.10 87.10 87.10 87.10 87.10 87.11 87.11 87.11 66.64 68.56 69.01 54.98 70.59 69.60 68.04 66.00 63.37 60.73 59.39 58.27 57.81 57.60 57.32 57.17 57.82 58.63 61.46 64.16 66.64 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 89.90 68.08 62.73 60.18 64.37 71.08 75.05 Vc (kV) 79.80 79.80 79.80 79.80 79.80 79.80 79.79 79.79 79.79 79.79 95.47 95.47 95.47 95.47 95.47 95.47 95.47 95.47 95.47 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 79.90 79.89 79.89 79.89 79.89 79.89 79.89 79.89 79.89 79.89 79.89 79.90 79.90 79.90 79.90 79.90 79.89 79.89 79.89 79.89 79.89 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 79.96 79.96 79.96 79.96 79.96 79.96 79.95 79.95 79.96 79.96 79.96 79.96 79.96 79.97 79.96 79.96 79.96 79.96 79.96 79.96 79.95 95.12 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 80.01 80.01 80.01 80.01 80.01 80.01 80.00 80.00 80.01 80.01 80.01 80.01 80.01 80.02 80.01 80.01 80.01 80.01 80.01 80.01 80.00 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 80.18 80.18 80.18 80.18 80.18 80.17 V Max (kV) 79.80 79.80 79.80 79.80 79.80 79.80 79.79 79.79 79.79 79.79 95.47 95.47 95.47 95.47 95.47 95.47 95.47 95.47 95.47 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 95.48 79.90 79.89 79.89 85.76 79.89 79.89 79.89 79.89 79.89 79.89 79.89 79.90 79.90 79.90 79.90 79.90 79.89 79.89 79.89 79.89 79.89 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 95.30 79.96 79.96 79.96 86.51 79.96 79.96 79.95 79.95 79.96 79.96 79.96 79.96 79.96 79.97 79.96 79.96 79.96 79.96 79.96 79.96 79.95 95.12 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 95.13 80.01 80.01 80.01 87.13 80.01 80.01 80.00 80.00 80.01 80.01 80.01 80.01 80.01 80.02 80.01 80.01 80.01 80.01 80.01 80.01 80.00 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.01 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 94.02 80.18 80.18 80.18 80.18 80.18 80.17 Ratio Vmax/Vnom 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.48 1.48 1.48 1.59 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.48 1.48 1.48 1.61 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.48 1.48 1.48 1.62 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.49 1.49 1.49 1.49 1.49 1.49 Simulation 5 Variables Simulation 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 Start-Delay (s) 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Line Length=100km Fault Duration (s) 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size (Ohm) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 Va (kV) 59.39 59.29 59.13 58.89 58.61 58.27 57.95 57.74 57.93 58.83 60.11 61.53 62.75 63.74 64.51 56.60 56.19 56.09 56.11 56.04 55.84 55.48 54.99 54.50 54.51 54.53 54.45 54.30 54.12 53.94 53.80 53.72 53.71 57.04 56.86 56.57 81.62 82.58 83.25 59.23 59.16 59.13 59.10 59.07 59.01 58.94 58.86 60.26 62.92 65.70 68.69 71.67 74.37 76.68 78.73 80.42 81.69 53.83 53.83 53.82 53.83 53.82 53.81 53.81 53.81 53.80 53.79 53.79 53.84 53.83 53.81 53.80 53.80 53.80 53.81 53.81 53.80 53.80 82.68 83.53 84.21 56.99 57.00 57.02 57.05 57.10 57.15 57.21 59.25 61.78 64.47 67.19 70.15 73.11 75.72 78.00 79.93 81.41 82.75 62.83 63.20 67.13 71.07 74.07 76.28 77.80 78.28 77.51 75.53 72.87 69.78 63.21 62.85 62.67 58.76 0.00 0.00 58.24 62.78 62.87 83.02 84.01 84.61 91.28 91.14 90.59 89.65 88.33 86.67 84.71 82.48 80.05 77.48 74.82 72.14 73.57 76.12 78.21 80.11 81.78 83.08 Vb (kV) 109.55 109.64 109.65 109.64 109.63 109.10 108.03 106.80 105.51 104.30 103.01 101.86 100.76 99.71 98.86 93.06 95.20 95.30 94.30 91.22 87.84 87.95 87.77 87.86 87.88 87.93 88.03 88.05 88.07 88.13 88.16 88.14 88.14 88.13 88.77 93.05 81.11 80.28 79.75 95.65 95.70 95.51 95.19 94.67 93.97 93.12 92.15 91.08 89.93 88.74 87.52 86.47 85.41 84.24 83.13 82.05 81.03 98.32 101.30 101.82 101.02 98.27 93.24 89.46 89.15 89.13 89.15 89.20 89.31 90.02 89.73 89.41 89.42 89.41 89.41 89.76 93.02 98.31 80.54 79.50 78.91 97.37 97.39 97.20 96.84 96.31 95.60 94.82 93.94 92.93 91.82 90.53 89.13 87.66 86.14 84.59 83.09 81.67 80.45 109.11 113.79 115.72 114.87 112.65 107.93 107.90 107.74 105.14 100.19 103.32 104.92 104.25 101.48 97.17 92.02 90.93 90.93 94.65 101.84 109.11 80.06 79.01 78.22 121.98 121.83 120.92 119.20 116.73 113.57 109.78 105.44 100.66 97.02 94.68 92.27 89.89 87.51 85.33 83.25 81.41 80.01 Vc (kV) 78.28 77.57 77.74 78.57 77.63 78.75 79.57 78.42 77.93 77.65 77.55 77.86 77.69 77.46 77.83 91.38 91.39 91.52 91.57 91.23 97.54 102.74 105.40 106.26 105.57 102.54 97.18 91.34 91.40 91.42 91.43 91.45 91.45 91.46 91.42 91.39 79.78 79.89 79.79 79.79 79.87 79.84 79.96 80.52 81.09 85.10 88.96 90.64 90.16 88.75 85.55 80.28 79.99 79.78 79.96 79.88 79.79 91.10 93.00 93.72 93.19 98.62 106.40 111.62 114.07 114.51 113.20 109.40 103.12 94.53 91.11 91.13 91.14 91.16 91.16 91.17 91.13 91.10 79.89 80.18 79.91 79.91 79.97 79.95 80.07 81.41 82.88 89.17 93.29 95.12 94.62 92.79 89.44 83.96 80.17 80.12 80.05 79.91 79.92 103.94 108.92 111.50 111.81 115.98 124.12 129.28 131.25 130.77 128.19 122.83 114.73 104.08 100.56 97.81 93.69 90.59 90.54 90.48 96.78 104.00 82.90 82.20 80.74 114.42 113.93 112.47 110.02 106.66 102.45 97.51 101.53 103.61 103.12 100.47 96.79 90.85 86.75 86.14 83.68 82.44 82.88 V Max (kV) 109.55 109.64 109.65 109.64 109.63 109.10 108.03 106.80 105.51 104.30 103.01 101.86 100.76 99.71 98.86 93.06 95.20 95.30 94.30 91.23 97.54 102.74 105.40 106.26 105.57 102.54 97.18 91.34 91.40 91.42 91.43 91.45 91.45 91.46 91.42 93.05 81.62 82.58 83.25 95.65 95.70 95.51 95.19 94.67 93.97 93.12 92.15 91.08 90.16 88.75 87.52 86.47 85.41 84.24 83.13 82.05 81.69 98.32 101.30 101.82 101.02 98.62 106.40 111.62 114.07 114.51 113.20 109.40 103.12 94.53 91.11 91.13 91.14 91.16 91.16 91.17 93.02 98.31 82.68 83.53 84.21 97.37 97.39 97.20 96.84 96.31 95.60 94.82 93.94 95.12 94.62 92.79 89.44 87.66 86.14 84.59 83.09 81.67 82.75 109.11 113.79 115.72 114.87 115.98 124.12 129.28 131.25 130.77 128.19 122.83 114.73 104.25 101.48 97.81 93.69 90.93 90.93 94.65 101.84 109.11 83.02 84.01 84.61 121.98 121.83 120.92 119.20 116.73 113.57 109.78 105.44 103.61 103.12 100.47 96.79 90.85 87.51 86.14 83.68 82.44 83.08 Line Length=10km Ratio Vmax/Vnom 2.03 2.03 2.03 2.03 2.03 2.02 2.00 1.98 1.96 1.94 1.91 1.89 1.87 1.85 1.83 1.73 1.77 1.77 1.75 1.69 1.81 1.91 1.96 1.97 1.96 1.90 1.80 1.69 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.73 1.51 1.53 1.54 1.77 1.78 1.77 1.77 1.76 1.74 1.73 1.71 1.69 1.67 1.65 1.62 1.60 1.58 1.56 1.54 1.52 1.52 1.82 1.88 1.89 1.87 1.83 1.97 2.07 2.12 2.13 2.10 2.03 1.91 1.75 1.69 1.69 1.69 1.69 1.69 1.69 1.73 1.82 1.53 1.55 1.56 1.81 1.81 1.80 1.80 1.79 1.77 1.76 1.74 1.77 1.76 1.72 1.66 1.63 1.60 1.57 1.54 1.52 1.54 2.02 2.11 2.15 2.13 2.15 2.30 2.40 2.44 2.43 2.38 2.28 2.13 1.93 1.88 1.82 1.74 1.69 1.69 1.76 1.89 2.02 1.54 1.56 1.57 2.26 2.26 2.24 2.21 2.17 2.11 2.04 1.96 1.92 1.91 1.86 1.80 1.69 1.62 1.60 1.55 1.53 1.54 Va (kV) 57.67 57.54 57.36 57.14 56.89 56.60 56.29 57.31 58.75 60.14 61.45 62.61 63.57 64.07 65.06 57.46 57.21 56.91 56.58 56.23 55.88 55.54 55.21 54.90 54.63 54.38 54.17 53.99 53.85 53.74 53.67 53.62 57.84 57.78 57.64 57.44 62.53 64.49 65.13 56.23 56.26 56.26 56.22 56.15 56.04 55.91 55.76 55.58 55.39 55.18 54.97 54.76 54.55 56.63 58.88 61.39 62.69 54.70 54.59 54.46 54.34 54.22 54.11 54.00 53.92 53.84 53.78 53.73 53.69 53.66 53.63 53.62 53.61 53.60 54.88 54.85 54.78 54.68 61.92 64.23 64.96 54.18 54.22 54.24 54.26 54.27 54.27 54.26 54.24 54.21 54.17 54.13 54.08 54.03 53.97 54.48 57.15 60.30 61.92 54.34 54.70 54.61 54.06 54.60 61.07 66.18 69.82 71.93 72.45 71.37 68.76 64.81 59.83 54.44 53.59 53.59 53.59 53.59 53.69 54.33 60.80 63.77 64.94 149.45 148.92 146.03 140.81 133.40 124.07 119.06 113.66 107.79 101.59 95.15 88.68 82.35 76.29 70.66 65.60 61.25 60.79 Vb (kV) 79.70 79.41 78.73 77.78 76.68 75.07 73.74 72.40 71.21 69.99 68.52 67.65 67.03 66.46 65.59 91.64 92.73 96.73 98.33 97.51 94.29 91.59 91.59 91.60 91.61 91.62 91.62 91.63 91.64 91.64 91.65 91.65 91.66 91.65 91.65 91.65 70.70 70.28 69.15 99.13 99.24 98.68 98.22 97.01 95.44 94.07 91.87 89.33 87.24 84.99 82.57 80.37 79.07 76.24 74.13 72.87 70.79 91.89 96.75 101.47 103.72 103.41 100.55 95.21 91.84 91.85 91.86 91.86 91.87 91.88 91.89 91.89 91.89 91.90 91.90 91.90 91.90 91.90 71.69 70.53 69.32 109.86 109.78 109.32 108.44 106.34 104.39 102.46 99.63 96.96 93.99 90.87 87.63 85.20 82.12 78.59 76.30 73.97 71.81 95.61 104.12 110.05 113.27 113.68 111.29 106.47 99.13 92.14 92.15 92.16 92.17 92.18 92.18 92.19 92.19 92.19 92.20 92.20 92.44 95.65 73.54 70.99 69.35 241.64 241.03 238.04 232.70 225.04 215.50 204.18 191.21 177.19 162.30 146.83 131.29 116.12 102.65 90.69 80.73 76.31 73.67 Vc (kV) 80.09 80.10 80.12 80.13 80.14 80.15 80.15 80.15 80.15 80.14 80.13 80.12 80.11 80.09 80.07 92.56 92.55 92.54 92.54 92.53 92.52 92.51 92.52 96.94 99.16 98.94 96.27 92.56 92.56 92.57 92.57 92.57 92.57 92.57 92.57 92.57 80.25 80.23 80.22 80.21 80.22 80.24 80.25 80.27 80.28 80.29 80.30 82.50 85.92 87.23 86.39 83.42 80.30 80.28 80.27 80.25 80.23 92.38 92.38 92.37 92.36 92.35 92.35 92.34 98.90 103.32 105.19 104.47 101.23 95.80 92.39 92.39 92.40 92.40 92.40 92.40 92.39 92.39 80.26 80.24 80.22 80.22 80.23 80.25 80.26 80.27 80.29 80.30 80.31 85.94 89.48 90.82 89.92 86.81 81.57 80.29 80.28 80.26 80.24 92.17 92.16 92.16 92.14 92.24 94.62 104.41 111.63 116.10 117.71 116.42 112.26 105.34 95.81 92.17 92.17 92.17 92.18 92.18 92.18 92.17 80.26 80.25 80.23 207.90 207.30 204.29 198.94 191.31 181.70 170.32 157.37 143.23 128.28 112.82 97.28 93.14 87.59 80.30 80.29 80.27 80.25 V Max (kV) 80.09 80.10 80.12 80.13 80.14 80.15 80.15 80.15 80.15 80.14 80.13 80.12 80.11 80.09 80.07 92.56 92.73 96.73 98.33 97.51 94.29 92.51 92.52 96.94 99.16 98.94 96.27 92.56 92.56 92.57 92.57 92.57 92.57 92.57 92.57 92.57 80.25 80.23 80.22 99.13 99.24 98.68 98.22 97.01 95.44 94.07 91.87 89.33 87.24 87.23 86.39 83.42 80.30 80.28 80.27 80.25 80.23 92.38 96.75 101.47 103.72 103.41 100.55 95.21 98.90 103.32 105.19 104.47 101.23 95.80 92.39 92.39 92.40 92.40 92.40 92.40 92.39 92.39 80.26 80.24 80.22 109.86 109.78 109.32 108.44 106.34 104.39 102.46 99.63 96.96 93.99 90.87 89.92 86.81 82.12 80.29 80.28 80.26 80.24 95.61 104.12 110.05 113.27 113.68 111.29 106.47 111.63 116.10 117.71 116.42 112.26 105.34 95.81 92.19 92.19 92.19 92.20 92.20 92.44 95.65 80.26 80.25 80.23 241.64 241.03 238.04 232.70 225.04 215.50 204.18 191.21 177.19 162.30 146.83 131.29 116.12 102.65 90.69 80.73 80.27 80.25 Line Length=0.2km Ratio Vmax/Vnom 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.72 1.72 1.79 1.82 1.81 1.75 1.72 1.72 1.80 1.84 1.84 1.79 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.49 1.49 1.49 1.84 1.84 1.83 1.82 1.80 1.77 1.75 1.70 1.66 1.62 1.62 1.60 1.55 1.49 1.49 1.49 1.49 1.49 1.71 1.80 1.88 1.92 1.92 1.87 1.77 1.84 1.92 1.95 1.94 1.88 1.78 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.49 1.49 1.49 2.04 2.04 2.03 2.01 1.97 1.94 1.90 1.85 1.80 1.74 1.69 1.67 1.61 1.52 1.49 1.49 1.49 1.49 1.77 1.93 2.04 2.10 2.11 2.07 1.98 2.07 2.15 2.18 2.16 2.08 1.95 1.78 1.71 1.71 1.71 1.71 1.71 1.72 1.77 1.49 1.49 1.49 4.48 4.47 4.42 4.32 4.18 4.00 3.79 3.55 3.29 3.01 2.72 2.44 2.15 1.90 1.68 1.50 1.49 1.49 Va (kV) 57.37 57.03 56.66 56.27 55.87 55.47 55.09 54.74 54.43 54.17 53.95 53.78 53.65 53.64 53.64 57.59 57.32 57.01 56.66 56.30 55.94 55.58 55.24 54.93 54.64 54.38 54.16 53.98 53.83 53.72 53.64 53.60 57.98 57.92 57.78 57.57 53.73 53.68 55.47 56.56 56.28 55.98 55.66 55.35 55.04 54.76 54.49 54.26 54.06 53.90 53.83 53.83 53.82 53.81 53.78 53.75 53.71 54.84 54.71 54.57 54.43 54.30 54.17 54.06 53.96 53.87 53.80 53.74 53.69 53.66 53.63 53.61 53.60 53.60 55.03 55.00 54.93 54.82 53.74 53.69 55.60 54.46 54.30 54.15 54.00 53.86 53.77 53.81 53.84 53.87 53.88 53.89 53.89 53.88 53.86 53.84 53.81 53.77 53.72 53.64 53.65 53.64 53.64 53.64 57.88 61.85 64.41 65.48 65.01 63.06 59.71 55.14 53.90 53.91 53.68 53.64 2.44 53.64 53.64 53.64 54.60 54.52 55.51 53.64 53.64 56.32 59.65 62.33 64.26 65.34 65.58 64.99 63.67 86.94 66.13 60.42 57.77 56.14 55.17 54.77 54.58 Vb (kV) 74.49 72.03 69.01 66.35 63.29 60.99 59.14 58.09 58.88 59.83 61.79 64.33 67.50 69.64 68.11 91.91 91.91 92.89 94.44 93.66 91.90 91.90 91.90 91.90 91.90 91.90 91.90 91.90 91.90 91.91 91.91 91.91 91.91 91.91 91.91 91.91 67.95 66.71 64.92 93.95 96.24 96.78 97.02 94.95 92.30 89.15 85.88 82.36 79.09 76.52 73.56 72.18 71.64 70.59 69.98 68.74 67.92 92.09 92.32 96.82 99.04 98.82 96.16 92.08 92.08 92.08 92.09 92.09 92.09 92.09 92.09 92.09 92.09 92.09 92.09 92.09 92.09 92.09 68.87 67.31 65.23 110.49 109.97 109.44 107.68 103.90 100.62 97.55 93.64 89.44 87.03 82.86 79.88 76.97 74.74 72.71 71.70 70.24 68.86 94.97 104.66 111.76 116.09 117.55 116.12 111.83 104.78 95.14 92.39 92.39 92.39 92.39 92.39 92.39 92.39 92.39 92.40 92.39 92.39 95.02 64.61 63.41 61.89 126.19 126.35 125.16 122.47 119.27 115.07 110.49 106.05 102.26 99.47 163.65 142.87 124.61 108.02 93.97 81.66 71.13 64.56 Vc (kV) 80.17 80.17 80.17 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.17 80.17 92.67 92.67 92.67 92.67 92.67 92.67 92.67 92.68 92.68 94.31 94.82 92.99 92.68 92.68 92.68 92.68 92.68 92.68 92.68 92.68 92.68 80.25 80.24 80.24 80.24 80.24 80.24 80.24 80.24 80.24 80.24 80.24 80.24 82.03 83.39 82.70 80.25 80.24 80.24 80.24 80.24 80.24 92.52 92.52 92.52 92.52 92.52 92.52 92.52 92.70 97.71 100.31 100.44 98.09 93.32 92.52 92.53 92.53 92.53 92.53 92.53 92.53 92.52 80.25 80.25 80.24 80.25 80.24 80.24 80.24 80.24 80.24 80.24 80.25 80.47 83.79 85.04 84.21 81.29 80.25 80.24 80.24 80.24 80.24 92.42 92.42 92.42 92.42 92.42 94.08 104.16 111.69 116.47 118.37 117.36 113.46 106.76 97.42 92.42 92.43 92.43 92.44 92.43 92.43 92.43 80.28 80.28 80.28 91.94 90.73 88.41 84.91 80.28 80.28 80.28 85.67 91.90 95.88 97.50 96.72 93.56 88.10 80.48 80.28 80.28 80.28 V Max (kV) 80.17 80.17 80.17 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.18 80.17 80.17 92.67 92.67 92.89 94.44 93.66 92.67 92.67 92.68 92.68 94.31 94.82 92.99 92.68 92.68 92.68 92.68 92.68 92.68 92.68 92.68 92.68 80.25 80.24 80.24 93.95 96.24 96.78 97.02 94.95 92.30 89.15 85.88 82.36 82.03 83.39 82.70 80.25 80.24 80.24 80.24 80.24 80.24 92.52 92.52 96.82 99.04 98.82 96.16 92.52 92.70 97.71 100.31 100.44 98.09 93.32 92.52 92.53 92.53 92.53 92.53 92.53 92.53 92.52 80.25 80.25 80.24 110.49 109.97 109.44 107.68 103.90 100.62 97.55 93.64 89.44 87.03 85.04 84.21 81.29 80.25 80.24 80.24 80.24 80.24 94.97 104.66 111.76 116.09 117.55 116.12 111.83 111.69 116.47 118.37 117.36 113.46 106.76 97.42 92.42 92.43 92.43 92.44 92.43 92.43 95.02 80.28 80.28 80.28 126.19 126.35 125.16 122.47 119.27 115.07 110.49 106.05 102.26 99.47 163.65 142.87 124.61 108.02 93.97 81.66 80.28 80.28 Ratio Vmax/Vnom 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.72 1.72 1.72 1.75 1.74 1.72 1.72 1.72 1.72 1.75 1.76 1.73 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.49 1.49 1.49 1.74 1.79 1.80 1.80 1.76 1.71 1.65 1.59 1.53 1.52 1.55 1.53 1.49 1.49 1.49 1.49 1.49 1.49 1.72 1.72 1.80 1.84 1.83 1.78 1.72 1.72 1.81 1.86 1.86 1.82 1.73 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.49 1.49 1.49 2.05 2.04 2.03 2.00 1.93 1.87 1.81 1.74 1.66 1.61 1.58 1.56 1.51 1.49 1.49 1.49 1.49 1.49 1.76 1.94 2.07 2.15 2.18 2.15 2.08 2.07 2.16 2.20 2.18 2.11 1.98 1.81 1.72 1.72 1.72 1.72 1.72 1.72 1.76 1.49 1.49 1.49 2.34 2.34 2.32 2.27 2.21 2.14 2.05 1.97 1.90 1.85 3.04 2.65 2.31 2.00 1.74 1.52 1.49 1.49 Simulation 6 Variables Simulation 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 StartDelay 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 Type of Fault ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Results Fault Duration 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Va (kV) 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 82.14 79.32 76.08 72.45 68.49 64.29 53.69 53.69 53.69 53.69 88.09 89.16 89.85 90.18 90.17 89.81 89.09 87.98 86.46 84.52 82.13 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 89.18 86.29 82.75 78.57 73.79 53.69 53.69 53.69 53.69 53.69 53.69 95.33 95.83 96.06 96.05 95.80 95.28 94.43 93.18 91.45 89.16 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 92.24 89.70 86.41 82.32 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 97.11 97.24 97.24 97.10 96.79 Vb (kV) 54.84 54.59 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.76 54.86 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 57.75 54.24 53.68 53.77 54.24 54.81 55.48 56.26 57.12 58.08 59.10 60.15 61.19 62.15 62.95 63.47 63.61 63.21 62.15 60.33 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 70.95 70.72 70.72 70.72 70.72 70.72 70.75 70.86 71.01 71.19 71.42 71.70 72.02 72.39 72.78 73.14 73.42 73.50 73.22 72.39 70.81 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.58 78.60 78.69 78.80 78.94 79.09 79.22 79.26 79.09 78.57 78.57 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 Vc (kV) 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 54.02 54.91 54.43 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 54.69 55.93 55.79 54.26 53.69 53.69 53.69 53.69 53.69 89.64 88.60 88.40 88.49 88.63 88.79 88.99 89.22 89.47 89.74 90.03 90.31 90.59 90.85 91.05 91.19 91.22 91.12 90.85 90.36 75.00 75.09 75.16 75.20 75.20 75.11 74.90 74.70 76.71 74.66 74.64 74.62 74.61 74.60 74.60 74.61 74.65 74.72 74.81 74.91 75.00 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.62 96.66 96.71 96.76 96.80 96.84 96.85 96.81 96.71 96.59 78.74 78.74 78.75 78.75 78.75 78.75 78.75 88.33 85.93 83.18 80.09 78.69 78.68 78.67 78.67 78.68 78.69 78.71 78.72 78.73 78.74 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 79.69 79.69 79.69 79.69 79.70 79.70 79.69 79.69 89.82 87.19 84.14 80.68 79.65 79.65 79.65 79.65 79.66 V Max (kV) 54.84 54.59 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 54.02 54.91 54.43 53.69 53.69 53.69 53.69 53.76 54.86 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 54.69 55.93 55.79 54.26 53.69 53.69 53.69 53.69 53.69 89.64 88.60 88.40 88.49 88.63 88.79 88.99 89.22 89.47 89.74 90.03 90.31 90.59 90.85 91.05 91.19 91.22 91.12 90.85 90.36 82.14 79.32 76.08 75.20 75.20 75.11 74.90 74.70 76.71 74.66 88.09 89.16 89.85 90.18 90.17 89.81 89.09 87.98 86.46 84.52 82.13 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.59 96.62 96.66 96.71 96.76 96.80 96.84 96.85 96.81 96.71 96.59 89.18 86.29 82.75 78.75 78.75 78.75 78.75 88.33 85.93 83.18 80.09 95.33 95.83 96.06 96.05 95.80 95.28 94.43 93.18 91.45 89.16 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 97.66 92.24 89.70 86.41 82.32 79.70 79.70 79.69 79.69 89.82 87.19 84.14 80.68 97.11 97.24 97.24 97.10 96.79 Ratio Vmax/Vnom 1.02 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.02 1.01 1.00 1.00 1.00 1.00 1.00 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.01 1.04 1.04 1.01 1.00 1.00 1.00 1.00 1.00 1.66 1.64 1.64 1.64 1.64 1.65 1.65 1.66 1.66 1.67 1.67 1.68 1.68 1.69 1.69 1.69 1.69 1.69 1.69 1.68 1.52 1.47 1.41 1.40 1.40 1.39 1.39 1.39 1.42 1.39 1.63 1.65 1.67 1.67 1.67 1.67 1.65 1.63 1.60 1.57 1.52 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.80 1.80 1.80 1.80 1.80 1.79 1.79 1.65 1.60 1.54 1.46 1.46 1.46 1.46 1.64 1.59 1.54 1.49 1.77 1.78 1.78 1.78 1.78 1.77 1.75 1.73 1.70 1.65 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.71 1.66 1.60 1.53 1.48 1.48 1.48 1.48 1.67 1.62 1.56 1.50 1.80 1.80 1.80 1.80 1.80 Simulation 6 Variables Simulation 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 StartDelay 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Results Fault Duration 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 Va (kV) 96.25 95.39 94.08 92.21 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 93.72 91.57 88.60 84.74 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 97.18 97.24 97.24 97.17 97.00 96.68 96.11 95.16 93.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 94.46 92.65 90.00 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 96.93 96.93 96.89 96.80 96.62 96.25 95.58 94.43 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 94.83 93.30 90.93 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 96.57 96.55 96.50 96.39 96.16 95.69 94.79 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 94.99 93.70 91.57 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 Vb (kV) 53.68 53.68 53.68 53.68 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.55 82.57 82.63 82.65 82.55 82.54 82.54 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.87 84.86 84.86 84.86 84.86 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.37 86.36 86.36 86.36 86.36 86.36 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.41 87.40 87.40 87.40 87.40 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 Vc (kV) 79.67 79.68 79.68 79.69 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 80.04 80.04 80.05 80.05 80.05 80.05 80.05 80.04 80.04 89.41 86.51 83.22 80.01 80.01 80.01 80.01 80.02 80.03 80.03 80.04 80.04 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 80.21 80.22 80.22 80.23 80.23 80.22 80.22 80.21 80.21 80.20 80.20 84.90 81.59 80.44 80.39 80.19 80.19 80.20 80.20 80.21 80.22 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 80.31 80.31 80.31 80.32 80.32 80.32 80.31 80.31 80.31 80.30 80.29 80.29 80.29 80.28 82.50 81.25 80.29 80.30 80.30 80.31 80.31 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 80.37 80.37 80.37 80.38 80.38 80.38 80.37 80.37 80.36 80.36 80.35 80.35 V Max (kV) 96.25 95.39 94.08 92.21 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 97.46 93.72 91.57 88.60 84.74 80.05 80.05 80.05 80.04 80.04 89.41 86.51 83.22 97.18 97.24 97.24 97.17 97.00 96.68 96.11 95.16 93.69 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 97.05 94.46 92.65 90.00 80.23 80.23 80.22 80.22 80.21 80.21 80.20 80.20 84.90 81.59 96.93 96.93 96.89 96.80 96.62 96.25 95.58 94.43 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 96.65 94.83 93.30 90.93 80.32 80.32 80.32 80.31 80.31 80.31 80.30 80.29 80.29 80.29 80.28 96.57 96.55 96.50 96.39 96.16 95.69 94.79 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 96.29 94.99 93.70 91.57 80.38 80.38 80.38 80.37 80.37 80.36 80.36 80.35 80.35 Ratio Vmax/Vnom 1.79 1.77 1.75 1.71 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.81 1.74 1.70 1.64 1.57 1.49 1.49 1.49 1.49 1.49 1.66 1.61 1.54 1.80 1.80 1.80 1.80 1.80 1.79 1.78 1.77 1.74 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.80 1.75 1.72 1.67 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.58 1.51 1.80 1.80 1.80 1.80 1.79 1.79 1.77 1.75 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.76 1.73 1.69 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.79 1.79 1.79 1.79 1.78 1.78 1.76 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.76 1.74 1.70 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 Simulation 6 Variables Simulation 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 StartDelay 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Results Fault Duration 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size 35 35 35 35 35 35 35 35 35 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Va (kV) 53.69 53.69 53.69 53.69 96.19 96.13 95.98 95.65 94.95 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 95.04 93.95 92.02 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 95.87 95.77 95.54 95.00 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 95.02 94.09 92.35 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 95.57 95.40 94.98 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 94.97 94.17 92.59 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 95.26 94.92 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 93.97 53.69 53.69 53.69 53.69 53.69 Vb (kV) 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.17 88.16 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 88.75 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.21 89.20 89.20 89.20 89.20 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 91.16 53.68 53.68 53.68 53.68 53.68 53.68 53.68 Vc (kV) 80.35 80.34 80.34 80.35 80.46 80.35 80.36 80.36 80.37 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 80.41 80.41 80.41 80.42 80.42 80.42 80.41 80.41 80.40 80.40 80.39 80.39 80.39 80.38 80.38 80.39 80.39 80.39 80.40 80.40 80.41 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 80.43 80.44 80.44 80.45 80.45 80.44 80.44 80.43 80.43 80.43 80.42 80.42 80.41 80.41 80.41 80.41 80.42 80.42 80.43 80.43 80.44 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 80.45 80.46 80.46 80.47 80.47 80.46 80.46 80.45 80.45 80.45 80.44 80.44 80.43 80.43 80.43 80.43 80.44 80.44 80.45 80.45 80.46 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 80.52 80.52 80.53 80.53 80.53 80.53 80.53 V Max (kV) 80.35 80.34 80.34 80.35 96.19 96.13 95.98 95.65 94.95 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.98 95.04 93.95 92.02 80.42 80.42 80.42 80.41 80.41 80.40 80.40 80.39 80.39 80.39 80.38 80.38 80.39 80.39 95.87 95.77 95.54 95.00 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.72 95.02 94.09 92.35 80.45 80.45 80.44 80.44 80.43 80.43 80.43 80.42 80.42 80.41 80.41 80.41 80.41 80.42 80.42 95.57 95.40 94.98 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 95.50 94.97 94.17 92.59 80.47 80.47 80.46 80.46 80.45 80.45 80.45 80.44 80.44 80.43 80.43 80.43 80.43 80.44 80.44 80.45 95.26 94.92 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 94.34 80.52 93.97 80.53 80.53 80.53 80.53 80.53 Ratio Vmax/Vnom 1.49 1.49 1.49 1.49 1.78 1.78 1.78 1.77 1.76 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.76 1.74 1.71 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.78 1.78 1.77 1.76 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.76 1.75 1.71 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.77 1.77 1.76 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.76 1.75 1.72 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.77 1.76 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.49 1.74 1.49 1.49 1.49 1.49 1.49 Simulation 6 Variables Simulation 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 StartDelay 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 0.0000 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0045 0.0050 0.0055 0.0060 0.0065 0.0070 0.0075 0.0080 0.0085 0.0090 0.0095 0.0100 Type of Fault ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g ph-ph-g Results Fault Duration 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 NER Size 100 100 100 100 100 100 100 100 100 100 100 100 100 100 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 550 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 1000000 Va (kV) 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 53.69 Vb (kV) 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 92.61 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 92.74 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 92.91 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 53.68 Vc (kV) 80.52 80.52 80.51 80.51 80.50 80.50 80.50 80.50 80.50 80.50 80.51 80.51 80.52 80.52 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 80.55 80.55 80.56 80.56 80.56 80.56 80.56 80.55 80.55 80.54 80.54 80.53 80.53 80.53 80.53 80.53 80.53 80.54 80.54 80.55 80.55 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 80.55 80.55 80.56 80.56 80.56 80.56 80.56 80.55 80.55 80.54 80.54 80.53 80.53 80.53 80.53 80.53 80.54 80.54 80.54 80.55 80.55 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 80.55 80.56 80.56 80.57 80.57 80.56 80.56 80.55 80.55 80.55 80.54 80.54 80.53 80.53 80.53 80.53 80.54 80.54 80.55 80.55 80.56 V Max (kV) 80.52 80.52 80.51 80.51 80.50 80.50 80.50 80.50 80.50 80.50 80.51 80.51 80.52 80.52 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 93.21 80.55 80.55 80.56 80.56 80.56 80.56 80.56 80.55 80.55 80.54 80.54 80.53 80.53 80.53 80.53 80.53 80.53 80.54 80.54 80.55 80.55 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 93.09 80.55 80.55 80.56 80.56 80.56 80.56 80.56 80.55 80.55 80.54 80.54 80.53 80.53 80.53 80.53 80.53 80.54 80.54 80.54 80.55 80.55 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 92.94 80.55 80.56 80.56 80.57 80.57 80.56 80.56 80.55 80.55 80.55 80.54 80.54 80.53 80.53 80.53 80.53 80.54 80.54 80.55 80.55 80.56 Ratio Vmax/Vnom 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.49 1.49 1.49 1.50 1.50 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.49 1.49 1.50 1.50 1.50 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 1.49 Appendix C Overvoltage study – Steady State Voltage Data 135/138 Line Length S base 10 100 V base 220 and 66kV km MVA Zbase 484 Ohm Line Impedance per km (pu) 0.001676 NER per 1 Ohm ( pu) 0.0088 0.023 Positive and Sequence Impedance NER Ohm 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1E+06 Source Positive Impedance R 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 0.000869 X 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 0.00869 Transformer Positive Impedance R 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 Line Positive Impedance R 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 X 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 Load Positive Impedance R 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Z1 Total R 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 0.017629 X 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 Zero Sequence Impedance Z2 Total R 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 0.01763 X 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 0.24707 Z1 Total polar Magnitude angle ( rad) 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 0.2476981 1.4995648 Z2 Total Polar Magnitude 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 0.2476981 NER NER in rectangular form angle ( rad) Ohm R 1.4995648 0 0.000 1.4995648 5 0.344 1.4995648 10 0.689 1.4995648 15 1.033 1.4995648 20 1.377 1.4995648 25 1.722 1.4995648 30 2.066 1.4995648 35 2.410 1.4995648 40 2.755 1.4995648 45 3.099 1.4995648 50 3.444 1.4995648 100 6.887 1.4995648 550 37.879 1.4995648 1000 68.870 1.4995648 1000000 68870.400 X 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Transformer Zero Impedance R 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 X 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 Line Zero Impedance R 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 0.01676 X 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 0.08838 K2 and K0 factors Z0 Total R 0.01676 0.36111 0.70546 1.04982 1.39417 1.73852 2.08287 2.42722 2.77158 3.11593 3.46028 6.9038 37.8955 68.8872 68870.4 X 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 0.23838 Z0 total polar Magnitude 0.238968 0.432697 0.744651 1.07654 1.414401 1.754787 2.096469 2.438902 2.781809 3.125033 3.468481 6.907914 37.89623 68.88757 68870.42 angle 1.5006 0.5835 0.3259 0.2233 0.1693 0.1363 0.114 0.0979 0.0858 0.0764 0.0688 0.0345 0.0063 0.0035 3E-06 K2(Z2/Z1) polar 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 rectangular 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 K0(Z0/Z1) polar 0.96476 0.00104 1.74687 -0.9161 3.00628 -1.1737 4.34618 -1.2763 5.71018 -1.3302 7.08438 -1.3633 8.4638 -1.3856 9.84627 -1.4017 11.2306 -1.4138 12.6163 -1.4232 14.0029 -1.4308 27.8884 -1.465 152.994 -1.4933 278.111 -1.4961 278042 -1.4996 I Base at 66kv 876 Calculation of a2+aK2+K0 K0(Z0/Z1) NER Ohm rectangular 0.96476 0.001 0 1.0637 -1.3857 5 1.16264 -2.7724 10 1.26159 -4.159 15 1.36053 -5.5457 20 1.45947 -6.9324 25 1.55841 -8.3191 30 1.65736 -9.7058 35 1.7563 -11.092 40 1.85524 -12.479 45 1.95419 -13.866 50 2.94362 -27.733 100 11.8485 -152.53 550 20.7533 -277.34 1000 19789.6 -277337 1000000 3ph Fault Current I=1/Z1 pu 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 4.03717 angle (degree) -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 -85.9187 A 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 3536.6 Ph-g Fault Current I= 3/(1 + K2 + K0) * I3ph fault 1+ K2+K0 rectangular 2.965 0.001 3.064 -1.386 3.163 -2.772 3.262 -4.159 3.361 -5.546 3.459 -6.932 3.558 -8.319 3.657 -9.706 3.756 -11.092 3.855 -12.479 3.954 -13.866 4.944 -27.733 13.848 -152.534 22.753 -277.336 19791.553 -277336.572 polar 2.965 3.362 4.206 5.285 6.484 7.748 9.048 10.372 11.711 13.061 14.419 28.170 153.161 278.267 278041.866 0.000 -0.425 -0.720 -0.906 -1.026 -1.108 -1.167 -1.210 -1.244 -1.271 -1.293 -1.394 -1.480 -1.489 -1.500 pu 4.085 3.602 2.880 2.291 1.868 1.563 1.339 1.168 1.034 0.927 0.840 0.430 0.079 0.044 0.000 angle (degree) -85.938 -61.582 -44.681 -34.023 -27.133 -22.439 -19.077 -16.566 -14.627 -13.086 -11.836 -6.026 -1.106 -0.609 -0.001 A 3578.6 3155.3 2522.7 2007.4 1636.2 1369.4 1172.6 1022.9 905.9 812.3 735.8 376.6 69.3 38.1 0.0 NER Ratio I fault with NER/I fault solidly Ohm earthed 1.000 0 0.882 5 0.705 10 0.561 15 0.457 20 0.383 25 0.328 30 0.286 35 0.253 40 0.227 45 0.206 50 0.105 100 0.019 550 0.011 1000 0.000 1000000 a2 rectangular -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 -0.5 -0.86603 aK2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 polar 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 2.0944 K0 rectangular -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 Total rectangular rectangular 0.96476 0.001 -0.03524 0.001 1.0637 -1.38568 0.0637 -1.38568 1.16264 -2.77236 0.16264 -2.77236 1.26159 -4.15905 0.26159 -4.15905 1.36053 -5.54573 0.36053 -5.54573 1.45947 -6.93241 0.45947 -6.93241 1.55841 -8.31909 0.55841 -8.31909 1.65736 -9.70578 0.65736 -9.70578 1.7563 -11.0925 0.7563 -11.0925 1.85524 -12.4791 0.85524 -12.4791 1.95419 -13.8658 0.95419 -13.8658 2.94362 -27.7327 1.94362 -27.7327 11.8485 -152.534 10.8485 -152.534 20.7533 -277.336 19.7533 -277.336 19789.6 -277337 19788.6 -277337 polar 0.03526 -0.02845 1.38714 -1.52486 2.77713 -1.5122 4.16726 -1.50798 5.55744 -1.50588 6.94762 -1.50461 8.33781 -1.50377 9.72801 -1.50317 11.1182 -1.50272 12.5084 -1.50237 13.8986 -1.50209 27.8007 -1.50083 152.919 -1.49979 278.038 -1.49969 278042 -1.49956 a rectangular -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 -0.5 0.86603 a 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 polar -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 -2.094 Ea Eb 1 1 0 4.18 1 -0.50759 0 -0.8616 Ec 1 2.094 -0.49966 0.86622 Calculation of a+a2K2+K0 2 K2 rectangular -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 -0.49966 -0.86622 K0 rectangular 0.96476 0.001 1.0637 -1.38568 1.16264 -2.77236 1.26159 -4.15905 1.36053 -5.54573 1.45947 -6.93241 1.55841 -8.31909 1.65736 -9.70578 1.7563 -11.0925 1.85524 -12.4791 1.95419 -13.8658 2.94362 -27.7327 11.8485 -152.534 20.7533 -277.336 19789.6 -277337 Nominal Phase to Ground Voltage 38105.1 38105.1 Voltage Phase b to ground Total rectangular -0.0349 0.00081 0.06404 -1.38587 0.16298 -2.77256 0.26193 -4.15924 0.36087 -5.54592 0.45981 -6.9326 0.55876 -8.31929 0.6577 -9.70597 0.75664 -11.0927 0.85558 -12.4793 0.95453 -13.866 1.94396 -27.7328 10.8488 -152.534 19.7537 -277.336 19788.6 -277337 ratio a2+aK2+K0/1+K2+K0 NER Ohm polar 0.03491 -0.02319 0 1.38735 -1.52462 5 2.77734 -1.51208 10 4.16748 -1.5079 15 5.55765 -1.50582 20 6.94784 -1.50457 25 8.33803 -1.50373 30 9.72823 -1.50314 35 11.1184 -1.50269 40 12.5086 -1.50234 45 13.8988 -1.50207 50 27.8009 -1.50081 100 152.92 -1.49979 550 278.038 -1.49969 1000 278042 -1.49956 1000000 0.0119 0.4125 0.6603 0.7884 0.8570 0.8967 0.9215 0.9379 0.9494 0.9577 0.9639 0.9869 0.9984 0.9992 1.0000 polar -0.0288 -1.1001 -0.7925 -0.6022 -0.4799 -0.3967 -0.3372 -0.2927 -0.2584 -0.2312 -0.2091 -0.1064 -0.0195 -0.0108 0.0000 rectangular 0.0119 -0.0003 0.1871 -0.3677 0.4636 -0.4702 0.6497 -0.4466 0.7602 -0.3957 0.8271 -0.3465 0.8696 -0.3048 0.8980 -0.2707 0.9178 -0.2426 0.9322 -0.2195 0.9429 -0.2001 0.9813 -0.1048 0.9982 -0.0195 0.9991 -0.0107 1.0000 0.0000 Voltage Phase C to Ground Vb= Eb- a2+aK2+K0/1+K2+K0 rectangular -0.5195 -0.8613 -0.6947 -0.4939 -0.9712 -0.3914 -1.1573 -0.4150 -1.2678 -0.4659 -1.3347 -0.5151 -1.3772 -0.5568 -1.4056 -0.5909 -1.4254 -0.6190 -1.4398 -0.6421 -1.4505 -0.6615 -1.4889 -0.7568 -1.5058 -0.8421 -1.5067 -0.8509 -1.5076 -0.8616 polar 1.0058 0.8524 1.0471 1.2295 1.3507 1.4307 1.4855 1.5248 1.5540 1.5765 1.5943 1.6702 1.7253 1.7304 1.7364 angle (degree) 58.9030 35.4132 21.9495 19.7251 20.1784 21.1042 22.0118 22.8026 23.4720 24.0366 24.5152 26.9425 29.2149 29.4538 29.7479 Vb V 38326 32480 39900 46849 51470 54515 56604 58102 59216 60073 60749 63642 65742 65935 66167 ratio a+a2K2+K0/1+K2+K0 NER Ohm 0 5 10 15 20 25 30 35 40 45 50 100 550 1000 1000000 0.0118 0.4126 0.6604 0.7885 0.8571 0.8968 0.9215 0.9379 0.9494 0.9577 0.9640 0.9869 0.9984 0.9992 1.0000 polar -0.0235 -1.0999 -0.7923 -0.6021 -0.4798 -0.3966 -0.3371 -0.2927 -0.2584 -0.2312 -0.2091 -0.1064 -0.0195 -0.0108 0.0000 rectangular 0.0118 -0.0003 0.1872 -0.3677 0.4637 -0.4702 0.6498 -0.4466 0.7603 -0.3956 0.8271 -0.3464 0.8696 -0.3048 0.8980 -0.2706 0.9179 -0.2426 0.9322 -0.2194 0.9430 -0.2001 0.9813 -0.1048 0.9982 -0.0195 0.9991 -0.0107 1.0000 0.0000 Results Check using V Residual Vc= Eb- a+a2K2+K0/1+K2+K0 rectangular -0.5114 0.8665 -0.6869 1.2339 -0.9634 1.3364 -1.1495 1.3128 -1.2599 1.2619 -1.3268 1.2127 -1.3693 1.1710 -1.3977 1.1369 -1.4175 1.1088 -1.4319 1.0857 -1.4426 1.0663 -1.4810 0.9711 -1.4979 0.8857 -1.4988 0.8770 -1.4997 0.8662 polar 1.0062 1.4122 1.6474 1.7449 1.7832 1.7975 1.8018 1.8017 1.7997 1.7969 1.7939 1.7709 1.7402 1.7365 1.7319 angle (degree) -59.4498 -60.8973 -54.2139 -48.7959 -45.0435 -42.4265 -40.5374 -39.1243 -38.0337 -37.1695 -36.4695 -33.2523 -30.5966 -30.3328 -30.0116 Vc V 38340 53812 62776 66491 67949 68493 68656 68653 68577 68472 68357 67482 66309 66169 65993 V residual= (-3Ko/ ( 1 + K2 +K0 )) * E a polar 0.9762 1.5586 2.1444 2.4669 2.6418 2.7432 2.8062 2.8479 2.8769 2.8978 2.9135 2.9700 2.9967 2.9983 3.0000 -3.1403 -3.6323 -3.5950 -3.5115 -3.4452 -3.3964 -3.3600 -3.3322 -3.3105 -3.2930 -3.2788 -3.2117 -3.1540 -3.1482 -3.1410 rectangular -0.9762 -1.3746 -1.9278 -2.3000 -2.5209 -2.6546 -2.7396 -2.7963 -2.8360 -2.8647 -2.8861 -2.9627 -2.9965 -2.9982 -3.0000 Results Check using V Residual idual= (-3Ko/ ( 1 + K2 +K0 )) * E a rectangular -0.0013 0.7345 0.9393 0.8919 0.7898 0.6914 0.6081 0.5397 0.4836 0.4372 0.3985 0.2079 0.0372 0.0197 -0.0018 Calculation of Overvoltage Va during Phase b to Phase c to Ground Fault Check:V Residual -VBVC= 0 rectangular 0.0547 0.0069 0.0068 0.0068 0.0068 0.0069 0.0069 0.0070 0.0070 0.0070 0.0070 0.0071 0.0072 0.0072 0.0073 -0.0065 -0.0055 -0.0057 -0.0060 -0.0061 -0.0062 -0.0062 -0.0063 -0.0063 -0.0063 -0.0063 -0.0064 -0.0064 -0.0064 -0.0064 K2 rectangular 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 1.0000 0.0000 K0 rectangular polar 0.9648 0.0010 0.9648 1.0637 -1.3857 1.7469 1.1626 -2.7724 3.0063 1.2616 -4.1590 4.3462 1.3605 -5.5457 5.7102 1.4595 -6.9324 7.0844 1.5584 -8.3191 8.4638 1.6574 -9.7058 9.8463 1.7563 -11.0925 11.2306 1.8552 -12.4791 12.6163 1.9542 -13.8658 14.0029 2.9436 -27.7327 27.8884 11.8485 -152.5341 152.9936 20.7533 -277.3356 278.1110 19789.5528 -277336.5716 ########## K2K0 0.0010 -0.9161 -1.1737 -1.2763 -1.3302 -1.3633 -1.3856 -1.4017 -1.4138 -1.4232 -1.4308 -1.4650 -1.4933 -1.4961 -1.4996 polar 0.9880 90.0203 1.2541 79.0571 1.3949 81.7997 1.4434 83.9190 1.4643 85.2381 1.4751 86.1056 1.4814 86.7125 1.4855 87.1586 1.4882 87.4995 1.4902 87.7681 1.4916 87.9850 1.4969 88.9805 1.4996 89.8133 1.4998 89.8973 1.5000 89.9999 1 1 1.5708 -0.5236 3.3E-07 0.86603 1 -0.5 Ec 1 3.66519 -0.86603 -0.5 Voltage Factor Va=3 K2 K0/ (K2 + K0 + K2 K0) rectangular 0.9648 0.0007 1.0637 -0.7251 1.1626 -1.0306 1.2616 -1.1702 1.3605 -1.2471 1.4595 -1.2953 1.5584 -1.3282 1.6574 -1.3521 1.7563 -1.3701 1.8552 -1.3843 1.9542 -1.3956 2.9436 -1.4473 11.8485 -1.4900 20.7533 -1.4943 19789.5528 -1.4996 Ea Eb V 37646.7024 47789.2963 53154.2978 54999.4013 55796.3006 56208.4320 56449.5970 56603.5841 56708.4272 56783.3931 56839.0980 57040.6880 57142.9107 57149.9176 57157.6693 Max ph g Overvoltage Maximum Overvoltage Maximum ( between Vb also considering phPeak and Vc) ph-g fault Overvoltage V 38340 53812 62776 66491 67949 68493 68656 68653 68577 68472 68357 67482 66309 66169 66167 V 38340 53812 62776 66491 67949 68493 68656 68653 68577 68472 68357 67482 66309 66169 66167 V 54221 76102 88778 94032 96094 96864 97094 97090 96983 96834 96672 95434 93775 93577 93574 NER Ratio Overvoltage/Nominal Ohm Voltage 1.006 0 1.412 5 1.647 10 1.745 15 1.783 20 1.797 25 1.802 30 1.802 35 1.800 40 1.797 45 1.794 50 1.771 100 1.740 550 1.736 1000 1.736 1000000 Appendix D Overvoltage Study- PSCAD Model 136/138 PSCAD Software- System Model-Leonardo Torelli- RMIT University Analysis and Protection of Subtransmission Systems Using Neutral Earth Resistor Va |X| Vs C Vb |X| Vmax Max D Vc Is E |X| mrunout.out P+jQ #2 A V Resis #1 + RL T FLAT230 FaultType Bus Current,Bus Voltage : Graphs Current (kA) 1.00 0.75 Timed Fault Logic Is 0.50 0.25 0.00 -0.25 -0.50 -0.75 -1.00 Voltage (kV) 200 150 100 Vs 50 0 -50 -100 A TIME FltTime 0.00 ENAB B Comparator Vs -150 -200 Tim... 1 1 0.10 0.20 0.30 0.40 0.50 0.60 Ch. 1 . Meas-Enab . FDelay V1 Va ... ... ... 2 Ch. 2 . V2 FaultType Vb 3 Vc Ch. 3 Multiple Run Ch. 4 Vmax V3 FaultDuration V4 Resis Control FaultDuration Faul... Initial Faul... Fault Type FStart + 0.1 + F 0.1 s FDelay 0.4 FltTime D Fault Moni... Resis 0 12 0 1e+006 0 #NaN 0.4 #NaN #NaN Appendix E Voltage and Current as function of SIR 137/138 Vb Vb Sb Zb Zb I Source Ohm pu 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 Tx pu 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 Source Ohm pu 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 Tx pu 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 Z1 Line 66000.000 220000.000 100000000.000 43.560 484.000 886.054 Z0 R pu X pu 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 Z1 Line Length km 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 2.000 Zs Total Zl Total pu pu 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 0.159 0.018 NER Ohm 0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000 18.000 20.000 22.000 24.000 26.000 28.000 30.000 32.000 34.000 36.000 38.000 40.000 42.000 44.000 46.000 48.000 50.000 52.000 54.000 56.000 58.000 60.000 62.000 64.000 66.000 68.000 Length km 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 Zs Total Zl Total pu pu 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 0.159 0.044 NER pu 0.000 0.046 0.092 0.138 0.184 0.230 0.275 0.321 0.367 0.413 0.459 0.505 0.551 0.597 0.643 0.689 0.735 0.781 0.826 0.872 0.918 0.964 1.010 1.056 1.102 1.148 1.194 1.240 1.286 1.331 1.377 1.423 1.469 1.515 1.561 Tx pu 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 pu 0.000 0.046 0.092 0.138 0.184 0.230 0.275 0.321 0.367 0.413 0.459 0.505 0.551 0.597 Tx pu 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 Line Ohm pu 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 Zs Total pu 0.150 0.288 0.425 0.563 0.701 0.839 0.976 1.114 1.252 1.390 1.527 1.665 1.803 1.941 2.078 2.216 2.354 2.492 2.629 2.767 2.905 3.043 3.180 3.318 3.456 3.594 3.731 3.869 4.007 4.144 4.282 4.420 4.558 4.695 4.833 Zl Total pu 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 0.071 Ifault 3Phase I fault pu pu 6.300 6.417 6.300 4.957 6.300 4.038 6.300 3.406 6.300 2.946 6.300 2.595 6.300 2.319 6.300 2.095 6.300 1.912 6.300 1.757 6.300 1.626 6.300 1.513 6.300 1.415 6.300 1.329 6.300 1.252 6.300 1.184 6.300 1.123 6.300 1.068 6.300 1.018 6.300 0.973 6.300 0.931 6.300 0.893 6.300 0.858 6.300 0.825 6.300 0.795 6.300 0.767 6.300 0.741 6.300 0.717 6.300 0.694 6.300 0.672 6.300 0.652 6.300 0.633 6.300 0.615 6.300 0.598 6.300 0.582 I1/I3 pu 1.019 0.787 0.641 0.541 0.468 0.412 0.368 0.333 0.303 0.279 0.258 0.240 0.225 0.211 0.199 0.188 0.178 0.170 0.162 0.154 0.148 0.142 0.136 0.131 0.126 0.122 0.118 0.114 0.110 0.107 0.104 0.101 0.098 0.095 0.092 Vrelay SIR pu 0.185 0.149 0.125 0.107 0.094 0.084 0.076 0.069 0.063 0.058 0.054 0.051 0.048 0.045 0.042 0.040 0.038 0.036 0.035 0.033 0.032 0.031 0.029 0.028 0.027 0.026 0.026 0.025 0.024 0.023 0.023 0.022 0.021 0.021 0.020 4.4 5.7 7.0 8.3 9.6 10.9 12.2 13.5 14.8 16.1 17.4 18.7 20.0 21.3 22.6 23.9 25.2 26.5 27.8 29.1 30.4 31.7 33.0 34.3 35.6 36.9 38.2 39.5 40.8 42.1 43.4 44.7 46.0 47.3 48.6 Zs Total pu 0.150 0.288 0.425 0.563 0.701 0.839 0.976 1.114 1.252 1.390 1.527 1.665 1.803 1.941 Zl Total pu 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 Ifault 3Phase I fault pu pu 6.300 6.417 6.300 4.957 6.300 4.038 6.300 3.406 6.300 2.946 6.300 2.595 6.300 2.319 6.300 2.095 6.300 1.912 6.300 1.757 6.300 1.626 6.300 1.513 6.300 1.415 6.300 1.329 I1/I3 pu 1.019 0.787 0.641 0.541 0.468 0.412 0.368 0.333 0.303 0.279 0.258 0.240 0.225 0.211 Vrelay SIR pu 0.362 0.305 0.263 0.231 0.207 0.187 0.170 0.156 0.145 0.134 0.126 0.118 0.111 0.105 1.8 2.3 2.8 3.3 3.8 4.4 4.9 5.4 5.9 6.4 7.0 7.5 8.0 8.5 Z0 R pu X pu 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 Ohm 0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000 18.000 20.000 22.000 24.000 26.000 Line Ohm pu 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 4.230 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.009 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 Source Ohm pu 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 4.230 0.009 Tx pu 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 Z1 Line 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 5.000 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.159 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 0.044 28.000 30.000 32.000 34.000 36.000 38.000 40.000 42.000 44.000 46.000 48.000 50.000 52.000 54.000 56.000 58.000 60.000 62.000 64.000 66.000 68.000 0.643 0.689 0.735 0.781 0.826 0.872 0.918 0.964 1.010 1.056 1.102 1.148 1.194 1.240 1.286 1.331 1.377 1.423 1.469 1.515 1.561 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 pu 0.000 0.046 0.092 0.138 0.184 0.230 0.275 0.321 0.367 0.413 0.459 0.505 0.551 0.597 0.643 0.689 0.735 0.781 0.826 0.872 0.918 0.964 1.010 1.056 1.102 1.148 1.194 1.240 1.286 1.331 1.377 1.423 1.469 1.515 1.561 Tx pu 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.150 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 2.078 2.216 2.354 2.492 2.629 2.767 2.905 3.043 3.180 3.318 3.456 3.594 3.731 3.869 4.007 4.144 4.282 4.420 4.558 4.695 4.833 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 0.177 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 6.300 1.252 1.184 1.123 1.068 1.018 0.973 0.931 0.893 0.858 0.825 0.795 0.767 0.741 0.717 0.694 0.672 0.652 0.633 0.615 0.598 0.582 0.199 0.188 0.178 0.170 0.162 0.154 0.148 0.142 0.136 0.131 0.126 0.122 0.118 0.114 0.110 0.107 0.104 0.101 0.098 0.095 0.092 Ifault 3Phase I fault pu pu 6.300 6.417 6.300 4.957 6.300 4.038 6.300 3.406 6.300 2.946 6.300 2.595 6.300 2.319 6.300 2.095 6.300 1.912 6.300 1.757 6.300 1.626 6.300 1.513 6.300 1.415 6.300 1.329 6.300 1.252 6.300 1.184 6.300 1.123 6.300 1.068 6.300 1.018 6.300 0.973 6.300 0.931 6.300 0.893 6.300 0.858 6.300 0.825 6.300 0.795 6.300 0.767 6.300 0.741 6.300 0.717 6.300 0.694 6.300 0.672 6.300 0.652 6.300 0.633 6.300 0.615 6.300 0.598 6.300 0.582 I1/I3 pu 1.019 0.787 0.641 0.541 0.468 0.412 0.368 0.333 0.303 0.279 0.258 0.240 0.225 0.211 0.199 0.188 0.178 0.170 0.162 0.154 0.148 0.142 0.136 0.131 0.126 0.122 0.118 0.114 0.110 0.107 0.104 0.101 0.098 0.095 0.092 0.100 0.095 0.090 0.086 0.083 0.079 0.076 0.073 0.070 0.068 0.066 0.063 0.061 0.060 0.058 0.056 0.055 0.053 0.052 0.050 0.049 9.0 9.6 10.1 10.6 11.1 11.6 12.2 12.7 13.2 13.7 14.2 14.8 15.3 15.8 16.3 16.8 17.3 17.9 18.4 18.9 19.4 Vrelay SIR pu 0.531 0.467 0.416 0.376 0.342 0.314 0.291 0.270 0.253 0.237 0.223 0.211 0.200 0.190 0.181 0.173 0.166 0.159 0.153 0.147 0.141 0.136 0.132 0.127 0.123 0.119 0.116 0.112 0.109 0.106 0.103 0.101 0.098 0.096 0.093 0.9 1.1 1.4 1.7 1.9 2.2 2.4 2.7 3.0 3.2 3.5 3.7 4.0 4.3 4.5 4.8 5.0 5.3 5.6 5.8 6.1 6.3 6.6 6.9 7.1 7.4 7.6 7.9 8.2 8.4 8.7 8.9 9.2 9.5 9.7 Z0 R pu X pu 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00168 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 0.00884 Length km 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 10.000 Zs Total Zl Total pu pu 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 0.159 0.088 NER Ohm 0.000 2.000 4.000 6.000 8.000 10.000 12.000 14.000 16.000 18.000 20.000 22.000 24.000 26.000 28.000 30.000 32.000 34.000 36.000 38.000 40.000 42.000 44.000 46.000 48.000 50.000 52.000 54.000 56.000 58.000 60.000 62.000 64.000 66.000 68.000 Line Ohm pu 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.00670 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 0.03535 Zs Total pu 0.150 0.288 0.425 0.563 0.701 0.839 0.976 1.114 1.252 1.390 1.527 1.665 1.803 1.941 2.078 2.216 2.354 2.492 2.629 2.767 2.905 3.043 3.180 3.318 3.456 3.594 3.731 3.869 4.007 4.144 4.282 4.420 4.558 4.695 4.833 Zl Total pu 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 0.354 Appendix F CVT Study – PSCAD Data 138/138 10 km line length and initial SIR of 1 SIR 1 5 10 20 30 60 Ifault kA 19.40 5.60 2.26 1.41 1.04 0.41 1st V Peak pu 1.29 4.49 8.62 17.86 22.00 43.59 2nd V Peak pu 1.46 1.40 1.95 3.71 4.44 8.35 3rd V Peak pu 1.08 1.20 1.26 1.12 1.06 1.53 4th V Peak pu 1 1 1 1 1 1 3rd V Peak pu 1.09 1.36 1.39 1.81 4th V Peak pu 1 1 1 1 3rd V Peak pu 1.01 0.99 1.01 1.19 1.12 1.76 4th V Peak pu 1 1 1 1 1 1 3rd V Peak pu 1.01 1.19 1.12 1.76 4th V Peak pu 1 1 1 1 10 km line length and initial SIR of 10 SIR 10 20 30 60 Ifault kA 3.71 1.71 1.10 0.44 1st V Peak pu 7.50 14.30 22.61 46.44 2nd V Peak pu 2.16 3.89 5.33 9.13 2 km line length and initial SIR of 1 SIR 1 5 10 20 30 60 Ifault kA 95.20 25.80 14.30 7.30 4.70 2.32 1st V Peak pu 1.47 4.80 8.04 17.44 22.67 43.59 2nd V Peak pu 1.09 1.48 2.03 3.51 4.58 8.53 2 km line length and initial SIR of 10 SIR 10 20 30 60 Ifault kA 17.50 7.39 4.24 2.40 1st V Peak pu 8.04 17.44 22.67 43.59 2nd V Peak pu 2.03 3.51 4.58 8.53