University of Technology, Department of Production Eng. & Metallurgy M.Sc. course Case Studies: A temperature measurement Requirement: Determination of temperature of a liquid in the range 0ºC to 100 ºC . Determination of the temperature of the cooling water for an engine and its display as a pointer moving across a scale marked to indicate safe and unsafe operating temperatures. Sensor: use a thermistor as a sensor. Signal processing: The resistance change of the thermistor has to be converted into a voltage which can then be applied across a meter and so converted to a current through it and hence a reading on the meter related to the temperature. Figure below shows a possible solution involving a potential divider circuit to convert the resistance change into a voltage change. Suppose we use a 4.7 k ohm, bead thermistor. This has a resistance of 4.7 k ohm at 25°C, 15.28 k ohm at OºC and 0.33 k ohm at lOOºC. The variable resistor might be 0 to 10 k ohm. It enables the sensitivity of the arrangement to be altered. However, if the variable resistor was set to zero resistance then, without a protective resistor, we could possibly have a large current passed through the thermistor. The protective resistor is there to prevent this occurring. The maximum power that the thermistor can withstand is specified as 250 mW. Thus, with a 6 V supply, the variable resistor set to zero resistance, the protective resistance R, and the thermistor at 100°C, the current I through the thermistor is given by V = IR as 6 = I(0 + R + 330), and so: I= 6 / (R+330) The power dissipated by the thermistor I ^2 x 330 and so if we want this to be significantly below the maximum possible, say 100 mW, then we have: 0.100 = ( ( 6 / ( R+ 330) )^2 ) x 330 Hence R needs to be about 15 Q. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 1 Display: When the temperature of the thermistor is OºC its resistance is 15.28 k ohm. If we set the variable resistor as, say, 5 k ohm and the protective resistor as 15 Kk ohm then the voltage output when the supply is 6 V is: Output voltage = ( 5.015 / (15.28 + 5.015)) x 6 = 1.48 V When the temperature rises to 100°C the output voltage becomes: Output voltage = ( 5.015 / (0.33 + 5.015)) x 6 = 5.63 V Thus, over the required temperature range, the voltage output varies from 1.48 V to 5.63 V. A voltmeter to cover this range could be used to display the output. An absolute pressure measurement Requirement: Measurement of the manifold absolute pressure in a car engine as part of the electronic control of engine power. Sensor: A sensor that is used for such a purpose is a diaphragm pressure gauge fig.a . The diaphragm is made of silicon with the strain gauges diffused directly into its surface. Four strain gauges are used and so arranged that when two are in tension the other two are in compression fig.b. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 2 Signal processing: The four gauges are so connected as to form the arms of a Wheatstone bridge (Figure (c)). This gives temperature compensation since a change in temperature affects all the gauges equally. Thus the output from the sensor with its signal processing is a voltage which is a measure of the pressure. Display: If required, the output voltage could be displayed on a meter, possibly following some amplification. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 3 Detection of the angular position of a shaft Requirement: Detection of the angular position of the throttle shaft of a car to give an indication of the throttle opening, and hence the driver's power demand on the engine, as part of a car engine management system. Sensor: A rotary potentiometer (Figure below) is generally used with the potentiometer wiper being rotated over the potentiometer track. Signal processing: For a 5 V d.c. voltage connected across the potentiometer, with the throttle closed and the engine idling the wiper can be at a position close to the 0 V terminal and so give a small voltage output, typically about 0.5 V. As the throttle is opened, the shaft rotates and the wiper moves over the track so that at wide-open throttle the wiper is nearly at the end of its track and the output voltage has risen to about 4.3 V. The engine management system uses an operational amplifier to compare the output from the potentiometer with a fixed voltage of 0.5 V so that the opamp gives a high output when the potentiometer output is 0.5 V or lower and a low output when higher. This high-low signal, together with signals from other sensors, is fed to a microprocessor which then can give an output to control the engine idle speed. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 4 Fluid level monitoring Requirement: Monitoring the level of a liquid to indicate when the level falls below some critical value. Sensor: One method would be to use a magnetic float (Figure below) which rises with the liquid level and opens a reed switch when the level falls too low. Signal conditioning: The reed switch is in series with a 39 ohm resistor so that this is switched in parallel with a 1 k ohm resistor by the action of the reed switch. Opening the reed switch thus increases the resistance from about 37 ohm to 1 k ohm. Such a resistance change can be further transformed by signal conditioning to give suitable light on-off signals. Dimension checking Requirement: A method by which the dimensions of components can be checked. Sensor: LVDT displacement sensors can be used. Signal processing: The e.m.f induced in a secondary coil by a changing current I in the primary coil is given by e = M di/dt, where M is the mutual inductance, its value depending on the number of turns on the coils and the M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 5 magnetic linkage between the coils, thus the material in the core of the coils. Thus, for a sinusoidal input current to the primary coil of an LVDT, alternating e.m.f s are induced in the two secondary coils A and B. The two outputs are in series so that their difference is the output. Figure below shows how the size and phase of the alternating output changes with the displacement of the core. The same amplitude output voltage is produced for two different displacements. To give an output voltage which distinguishes between these two situations, a phase sensitive demodulator, with a low pass filter, is used to convert the output into a d.c. voltage which gives a unique value for each displacement, fig. below. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 6 The coils with simple LVDT sensors and parallel-sided coils exhibit nonlinearities as the ferrite core approaches the ends of the coils. This can be corrected for by using stepped windings or, more cheaply, by using a microprocessor system and programming it to compensate for such nonlinearities. Such a microprocessor system could also be used to receive the inputs from a number of such LVDT sensors and compare the outputs with the required dimensions of the components and give outputs indicating divergence. Measurement of relative humidity Requirement: Direct measurement of relative humidity without the need for using the operator to use tables to convert temperature values to relative humidity. The traditional method of measuring relative humidity involves two thermometers, one with its bulb directly exposed to the air and giving the 'dry temperature' and the other with its bulb covered with muslin which dips into water. The rate of evaporation from the wet muslin depends on the amount of water vapour present in the air; when the air is far from being saturated then the water evaporates quickly, when saturated there is not net evaporation. This rate of evaporation affects the temperature indicated by the thermometer, so giving the 'wet temperature'. Tables are then used to convert these readings into the humidity. Sensor: Rather than use a 'wet' thermometer element, a capacitive humidity sensor can be used. The sensor (Figure (a)) consists of an aluminum substrate with its top surface oxidized to form a porous layer of aluminum oxide. On top of the oxide a very thin Gold layer is deposited, this being permeable to water vapour. Electrical connections are made to the gold layer and the aluminum substrate, the arrangement being a capacitor with an aluminum oxide dielectric. Water vapour enters the pores of the aluminium oxide and changes its dielectric constant and hence the capacitance of the capacitor. The capacitance thus gives a measure of the amount of water vapour present in the air. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 7 Signal processing: Figure (b) shows the type of system that might be used with such a sensor. For the capacitive sensor, signal conditioning is used to transform the change in capacitance to a suitable size voltage signal. A temperature sensor is also required since the maximum amount of water vapour that air can hold depends on the temperature and thus to compute the humidity the microprocessor needs to know the temperature, this also requiring signal conditioning to get a signal of the right size. An ADC is then used to convert the signals to digital for processing by a microprocessor system; a microcontroller is likely to be used with an integrated ADC, microprocessor and memory on a single chip, there then being a number of input connections for analogue signals to the system. The microprocessor takes the values for the two inputs and can use a 'look-up' table in its memory to determine the value of the relative humidity. This is then outputted to a digital meter. M.Sc. course, Measurement & Control Instrumentations, Dr. Laith A. Mohammed Page 8