ee 340l experiment # 3b parallel operation of synchronous

advertisement
EE 340L
EXPERIMENT # 3B
PARALLEL OPERATION OF SYNCHRONOUS GENERATOR WITH
THE UTILTY GRID
1. SYNCHRONIZATION
(a) Connect the DC-motor, synchronous machine, three light bulbs, and
meters to measure the generator line-to-line voltage, generator AC
current, generator field current, and three-phase real and reactive
power (see figure 1 below). Note: for those motors with non-functional
rheostats, connect the motor as series (see figure 2 below).
(b) Make sure that the three light bulb switch is OPEN. Start the motor and
bring its speed to near 1800 RPM.
(c) Energize the generator exciter and adjust the its field current until the
terminal line voltage of the synchronous generator reaches 208V. Bring
the rotor speed back to 1800 RPM.
(d) Connect the other terminals of the three light bulbs to the 3-ะค power
supply.
(e) Adjust the generator phase sequence, rotor speed, and field current
until all the light bulbs are all dark. Move the three bulb switch to CLOSE
position when the light bulbs are all dark.
(f) Check the synchronous speed of the rotor with a stroboscope.
IMPORTANT NOTE: During the next two sections, if for some reason the
generator loses synchronism, move the three light bulb
switch to OPEN position immediately.
2. REAL POWER CONTROL
(a) Vary the mechanical power supplied to the synchronous generator Pin
by slowly varying the DC-motor rheostat (for shunt motors) or voltage (for
series motors)until the real output power Pout is zero, then record the
torque angle δ. This angle will be used as a reference (=0o).
(b) Increase Pin slowly by attempting to increase the generator speed until
Pout reaches 50 W. Record the generator voltage, current, shaft speed,
Qout and δ.
(c) Repeat step (b) several times in increments of 50 W, until you reach 350
W.
3. REACTIVE POWER CONTROL
(a) Reduce Pin until Pout = 0 W and δ is equal to the reference value.
(b) Increase the internal voltage of the synchronous generator by slowly
increasing the generator field current (in increments of 0.1 A). Record
the field current If, generator voltage and current, Pout and Qout.
(c) Repeat step (b) several times until the line current is equal to 1 A.
Questions:
1. Use the data recorded in Part 2 to plot the change of Pout and Qout in terms
of torque angle δ. Note that the reactive power is not very sensitive to the
change in input power.
2. Use the data recorded in Part 3 to plot the change of Pout and Qout in terms
of the field current. Note that the active power is not very sensitive to the
change in generator filed current.
3. After the synchronous generator has been synchronized with the power
system, explain what happens if the prime mover (i.e., motor driving the
shaft) is shut-down.
4. Explain why a change in the generator field current does not result in a
change of terminal voltage (i.e., unlike the case of isolated operation).
Motor-Generator
P&Q
Sync.
Switch
Electric Utility
Fig. 1
Fig. 2
ABC
120/208V 3-Phase
Supply
Download