Mercmaster LED - Explosion Proof Electrical Equipment for

advertisement
Mercmaster LED
IMPROVING INDUSTRIAL LIGHTING WITH TODAY’S TECHNOLOGY
1
THE FUTURE OF LIGHTING HAS ARRIVED
• Light‐emitting diodes are not a particularly new technology
• LED were first used as a replacement for incandescent lamps in indicator lamps on electronic equipment
• The first breakthrough that paved the way for modern LEDs was found in 1992
2
CONVENTIONAL LAMPS VS. LED –
ENERGY CONSUMPTION AND SAVINGS
Significant energy reduction from all categories with LED
3
LIGHT SOURCE LAMP LIFE COMPARISON
4
UNDERSTANDING LED LANGUAGE
Junction Temperature
• The critical part for temperature of an LED is the “T junction”
• “T junction” is the location which determines the temperature code (T rating). The “T junction” also determines the life of the LED.
• Dissipating the heat via heatsinks
becomes the best solution
5
UNDERSTANDING LED LANGUAGE
Color
Correlated Color Temperature (CCT) measures the shade of white light:
• “Warm” white light: 3200 K and below
• “Cool” white light: 4000 K and above
• Appleton’s Mercmaster fixtures test at 5650 K
6
UNDERSTANDING LED LANGUAGE
Color
Color Rendering Index (CRI) measures the ability to accurately render the color of illuminated objects
CRI
Color Rendering
Examples
75‐100
Excellent
Incandescent, Halogen, Induction
60‐75
Good
LED, Pulse Start Metal Halide
0‐60
(not suitable for color critical applications)
Poor
High Pressure Sodium
7
UNDERSTANDING LED LANGUAGE
Device Efficiency / Efficacy
• Efficiency is the ratio of total lumens exiting the fixture to the total lumens initially produced by the light source
• Efficacy is how well a light source produces visible light
• lumens per watt (LPW or lm/w)
• HID/fluorescent efficacy should be calculated based on luminaire lumen (Efficiency)
• LED has minor loss, considered 100% efficient
BULB: HID lamps emit light in every direction; this light is controlled using a reflector or refractor. The result is poor utilization efficiencies.
LED: LED directs the light to where it’s needed without the use of external optics. 8
UNDERSTANDING LED LANGUAGE
Equivalent to
Mercmaster III KPBU175PMT, 175W PSMH lamp with KR2ST Dome Reflector Mounting Height 12ft – 4 meters
Initial Lamp lumen: 17,500
Luminaire lumen: 12,652
System watts: 198W
Mercmaster LED MLEDN17P5BU
Mounting Height 12ft – 4 meters
Luminaire lumen: 6,075 System watts: 74W
9
UNDERSTANDING LED LANGUAGE
Equivalent to
FEB236BUSN 2 x 36W fluorescent
Mounting Height 10ft – 3 meters
Initial Lamp lumen: 5,510
Luminaire lumen: 4,433 System watts: 72W Mercmaster LED MLEDN10P5BU
Mounting Height 10ft – 3 meters
Luminaire lumen: 3,450
System watts: 48.5W
10
LED TESTING COMPLIANCES
IES LM 79‐08: Electrical and photometric testing of solid state lighting
IES LM‐80‐08: Measuring lumen maintenance of LED light sources
IES TM‐21: Projecting long‐
term lumen maintenance of LED light sources
IES‐approved method that describes the procedures to be followed in performing reproducible measurements:
IES‐approved for measuring lumen maintenance and evaluating operating conditions for LED light sources Provides recommendations for projecting long term lumen maintenance of LED light sources using data obtained per IES LM‐80‐08
1. Total luminous flux (fixture lumens)
2. Luminous efficacy (lm/W)
• Operating for at least 6,000 hours at representative operating temperatures
3. Luminous intensity & distribution (candelas)
• Photometric data collected at a minimum of every 1,000 hours
4. Color characteristics:
• Chromaticity, color temperature, color rendering
• Chromaticity – quality of color, independent of brightness
• Correlated Color Temperature (CCT) – in kelvins
• CRI with 100 defined as black body radiator or daylight
The result: Projection of lumen degradation or LED’s operating life in accordance to LM‐80
The result: Photometric reports for long term lumen maintenance
The result: Solid‐state lighting photometric reports (absolute)
11
ADVANTAGES OF LED LIGHTING
LED lighting is revolutionizing the lighting industry
• LED is environmentally sound: No mercury content, no UV or IR, and a much smaller carbon footprint
• LED lowers energy costs: Greater lighting efficacy and efficiency and uses far less power than traditional lighting sources
• LED lowers maintenance costs: 60,000+ hours between replacements • LED is perfect for demanding environments: Solid‐state resistance to vibration and shock
• LED is efficient: Directional light source without the use of external optics
• LED is ready when you are: Instant‐on and cold‐start capable at –40°C, with no degradation of lumen output
12
Appleton’s LED Design Advantages
13
APPLETON’S LED DESIGN ADVANTAGES OPTIMIZED NEW FIXTURES
•
Wide range of LED products for most applications (70‐250W)
•
•
•
•
Compact light weight design
•
•
•
Fewer LEDs and provides higher efficacy
Original Mercmaster LED
Increased drive current to 700mA
•
•
•
•
11.4lbs(5.2kg) lighter (22lbs/10kg down to 10.6lbs/4.8kg)
New one piece design
Upgraded the LEDs
•
•
Plant retrofits now easily done
Uses the same mounting hood as the MMIII
Same electrical wiring for HID fixtures with lower electrical rating
Same current as Areamaster LED
Improved fin design to keep dust and debris out Supplied with terminals which allows for easy wiring
Certifications and Compliances will include
NEC/CEC
• cCSAus
• Class I, Div 2, Group A, B, C, D
• Class I, Zone 2, Group IIC
• Class II, Div 1, Group E, F,G
• Class II, Div 2 Group F,G
• Class III
• Wet Locations and Marine (Salt Water)
• Type 3R & 4X • IP66 IECEx/ATEX ‐ Pending
• Zone 2 and 22
•
II 3 GD
• Ex nA II
• Ex t IIIC
• IP66 NEW Mercmaster LED
MERCMASTER LED LINE EXPANSION
Equivalent to HPS/PSMH
MLEDN70
MLEDN10
MLEDN15
MLEDN17
MLEDN25
70W
100W
150W
175W
250W
Voltage Range
BU: 120‐277VAC 50/60Hz
BH: 347‐480VAC, 50/60Hz
LED Lumen
2,300
3,450
4,850
6,075
9,455
Input Power (W)
35/33
47.5/46
61/62
74/72
95.5/92
66
71
80
82
93
‐40⁰C – T4A
55⁰C – T4
65⁰C – T3C
‐40⁰C – T4A
55⁰C – T4
65⁰C – T4
‐40⁰C – T4A
55⁰C – T4
‐40⁰C – T4A
55⁰C – T4
‐40⁰C – T4A
50⁰C – T4
>14ft/4.27m
18ft/4.88m‐
25ft/7.62m
Efficacy
Ambient Temp – T Rating
CCT/CRI
5650K/70
Fixture Weight (lbs and kg)
Typical Mounting (ft and m)
Standard Materials
Lifetime
10.6lbs – 4.8Kg
Max. 9ft/2.74m
8ft/2.44m‐
12ft/3.66m
12ft/3.66m‐
14ft/4.27m
Housing – Copper‐free cast aluminum
Finish – Baked gray epoxy‐clad, electrostatically applied
Lens – polycarbonate
60K+ hours
15
TOOLS/RESOURCES
Appleton lighting cost and savings calculator
• Tool for comparing industrial lighting systems in terms of total costs and potential savings over time
• Available soon at www.egseg.com
Lighting Layout • Available upon request
19
MERCMASTER LED Series
SEE THE
FUTURE.
THE MercMaster LED
Pulp & paper mills
|
Processing plants
|
Chemical plants
|
Oil refineries
SOME THINGS DON’T CHANGE.
Hazardous industrial locations demand lighting fixtures that deliver utmost
safety and dependable illumination for critical tasks.
But some things are changing right before your eyes.
Hazardous locations are increasingly responsible for energy efficiency and “green”
operations to save money and precious resources.
That’s why this change is huge.
LED lighting has come to hazardous locations, and the Mercmaster LED is setting the
industry standard for safety, performance and efficiency. To control the future, you
need to see it. The Appleton Mercmaster LED Series of Luminaires.
|
Storage areas
|
MANUFACTURING PLANTS
|
Waste & sewage treatment plants
Mercmaster LED:
the choice for a smart future.
Why is LED the future?
It’s not just about efficiency. LED lighting delivers
real productivity benefits.
• Resistant to vibrations and shock.
• Directional light can improve efficiency, productivity and safety.
• Cold start capable to -40°C and instant-on (<100ns).
• Uses no mercury and its beam gives off no heat.
• Promises long life, 60,000+ hours.
• Delivers reduced maintenance costs.
And perhaps most importantly, it’s green –
offering an energy reduction up to 68% for similar
luminosities compared to the PSMH (Pulse Start
Metal Halide) you may be using today. Because of its
all-around benefits, LED will soon be the prevalent
lamp technology in manufacturing settings
worldwide. Your future can start now.
No LED industrial fixture surpasses the Appleton Mercmaster
LED in efficiency, performance and advanced engineering. In
day-to-day use, installation and maintenance, the Appleton
Mercmaster LED’s superior design simply shines.
In areas requiring better visibility and instant-on illumination,
the complete range of Mercmaster LEDs provide a low
maintenance, energy efficient solution. Whether low
temperatures or retrofit applications Appleton has the answer.
FEATURES
• 5 LED array choices for light levels equivalent to 70 W HPS/PSMH,
100 W HPS/PSMH, 150 W HPS/PSMH, 175 W PSMH and
250 W HPS/PSMH.
• Luminaires rated for NEC/CEC environments (ATEX/IECEx pending).
• Upgraded LED array provides higher efficacies.
• 700mA drive current.
• Ambient temperatures:
— 70W equivalent: -40 ˚F to 149 ˚F/-40 ˚C to 65 ˚C
— 100W to 175W equivalent: -40 ˚F to 131 ˚F/-40 ˚C to 55 ˚C
— 250W equivalent: -40 ˚F to 122 ˚F/-40 ˚C to 50 ˚C
LED vs. HID:
The future of efficacy.
• Electrical: 120-277 Vac, 50/60 Hz
BULB: HID lamps emit light in every direction; this
light is controlled using a reflector or refractor. The
result is poor utilization efficiencies.
• Supplied with terminals to allow for easier wiring.
347-480 Vac, 50/60 Hz
• Resistant to low temperatures; the lumen output does not decrease.
• Compact lightweight low profile design, well suited for low mounting
heights.
• Utilizes the same electrical wiring for HID fixtures with lower electrical
ratings.
• Fixture housing and mounting hoods are copperfree cast aluminum for
better heat dissipation. All exposed hardware is stainless steel.
LED: LED directs the light to where it’s needed
without the use of external optics.
• Heatsink design to keep dust and debris from accumulating on the fixture,
while maintaining the rounded edges to reduce risk of injury during
installation and maintenance.
• Hinge design increases safety during installation and servicing, assuring
360° compression on ballast housing gasket.
• Silicone rubber gasket seals out moisture, dirt and dust; stays flexible and
withstands high temperatures.
• High impact-resistant polycarbonate lens is threaded for easy removal.
• Epoxy powder coat finish and stainless steel latch assembly are corrosion
resistant.
• Dark Sky Compliant: meets specifications for low glare, focused beam and
avoidance of overlighting.
Easier installation,
easier maintenance,
easier to be green – everywhere.
The Appleton Mercmaster LED excels in a varied range of
demanding locations.
LED Testing Compliances
IES LM 79-08 “Electrical and
Photometric Measurements of SolidState Lighting Products”
APPLICATIONS
LED fixtures suitable for use in:
• Marine and wet locations.
• A wide range of industrial, chemical processing and other areas where
flammable gases and vapors are present.
• Areas of low clearance, low ceiling heights or where fixture weights must be
minimized.
• Hazardous locations where severe weather conditions, excessive moisture,
dirt, dust, corrosive atmosphere or high ambient temperatures are
encountered.
An IES approved method describes the procedures
to be followed in performing reproducible
measurements of the following:
• Total luminous flux (fixture lumens)
• Luminous efficacy (lm/watt)
• Luminous intensity & distribution (candelas)
• Color Characteristics
– Chromaticity-Quality of color, independent of
brightness.
– CCT-Correlated Color Temp (k)
Mounting Hoods
– CRI-Color Rendering Index
• Six different types of mounting hoods accommodate any application
requirement.
The Result: Solid-State Lighting Photometric reports
(Absolute).
• Utilizes the same mounting hoods as the Mercmaster III Series.
• Easily accommodates retrofitting.
LM80-08 “Measuring Lumen
Maintenance of LED Light Sources”
An IES approved method covers the measurement of
lumen maintenance and procedures by which LED
light sources can be operated.
• Operating for at least 6,000 hours at
representative operating temperatures
Pendant
Wall
• Photometric data collected at a minimum of every
1,000 hours
• Chromaticity, color temperature, color rendering
The Result: Photometric reports for long term lumen
maintenance.
Pendant Cone
25° Stanchion
IES TM-21 – “Projecting Long Term
Lumen Maintenance of LED Light
Sources”
Provides recommendations for projecting long term
lumen maintenance of LED light sources using data
obtained per IES LM-80-08.
The Result: To project lumen degradation or LED’s
operating life in accordance to LM-80.
Ceiling
90° Stanchion
Certifications and compliances
NEC/CEC
• UL Standard: UL 1598, UL 1598A, UL 8750, UL 844
• Class I, Division 2, Groups A, B, C, D
• CSA Standard: C22.2 No. 250.0, C22.2 No. 137
• Class I, Zone 2, Group IIC
• cCSAus
• Class II, Division 1, Group E, F, G
IEC/ATEX — Pending
• Class II, Division 2, Group F, G
• Zone 2 and 22
• Class III
• II 3 GD
• Type 3R, 4X
• IP66
• IP66
• Ex Standards: IEC 60079-0; 60079-15; 60079-31
• Suitable for Use in Wet Locations
• Marine Outside Type (Salt Water)
Catalog Numbering Guide
MLEDN
A
Mercmaster LED
Series:
MLEDN - NEC/CEC
MLEDNA - ATEX/
IECEx 
17
2
Light Level
Equivalent:
70 - 70 W HPS
10 - 100 W HPS
15 - 150 W HPS
17 - 175 W PSMH
25 - 250 W HPS/
PSMH
Mounting:
A - Pendant
C - Ceiling
D - Pendant Cone
R - 90º Stanchion
S - 25º Stanchion
W - Wall
P
Optical Assembly:
P - Polycarbonate
Globe
Hub Size:
2 - 3/4” NPT
3 - 1” NPT
4 - 1-1/4” NPT
stanchion
5 - 1-1/2” NPT
stanchion
6 - Metric M20
 Certification for ATEX/IECEx pending.
 Canadian Electrical Code does NOT allow fusing in hazardous locations. Fuse not CEC rated.
• Heatsink enables reliable heat transfer
via the die-cast, aluminum body
• Protective, high impact resistant
polycarbonate lens allows for easy
maintenance access
• 30 LEDs in internal array direct
light to where it is needed without
the use of external optics
5
BU
H1
Voltage:
BU - Universal
Voltages
120-277 Vac,
50/60 Hz
BH - 347-480 Vac,
50/60 Hz
Light Distribution:
5 - NEMA Type 5
Symmetrical
Options:
F - Fusing 
For NEC/CEC Only:
H1 - Photocontrol 120 V
H2 - Photocontrol 208 V
H3 - Photocontrol 240 V
H4 - Photocontrol 277 V
Technical Data
Equivalent to HPS/PSMH
MLEDN70
MLEDN10
MLEDN15
MLEDN17
MLEDN25
70 Watt
100 Watt
150 Watt
175 Watt
250 Watt
Voltage Range
120 - 277 Vac, 50/60 Hz, 347 - 480 Vac, 50/60 Hz
LED Lumen
2300
3450
4850
6075
9455
Input Power
35 / 33
47.5 / 46
61 / 62
74 / 72
95.5 / 92
Efficacy
66
73
80
82
99
Ambient Temperate / T Rating
-40 °C / T4A
55 °C / T4
65 °C / T3C
-40 °C / T4A
55 °C / T4
-40 °C / T4A
55 °C / T4
-40 °C / T4A
55 °C / T4
-40 °C / T4A
50 °C / T4
Maximum 14 ft
18 to 25 ft
CCT/CRI
5650K / 70
Typical Mounting Height
Maximum 9 ft
8 to 12 ft
12 to 14 ft
Standard Materials
Housing – Copperfree cast aluminium
Finish – Baked gray epoxy powder coat, electrostatically applied
Lens – Polycarbonate
Fixture Weight
10.6 lbs/4.8 kgs
Induction/HID/ LED Lamp Comparison
LED
LED
LED
LED
LED
(70 W PSMH (100 W PSMH (150 W PSMH (175 W PSMH (250 W PSMH
output)
output)
output)
output)
output)
85 W QL
165 W QL
100 W HPS
175 W
PSMH
System
Watts
85
165
130
208
35
47.5
61
74
95.5
CRI
85
80
22
62
70
70
70
70
70
Ignition
0.1 sec
0.1 sec
5 sec
10 sec
Instant
Instant
Instant
Instant
Instant
Warm Up
5 sec
5 sec
3 - 4 min
1.5 min
Instant
Instant
Instant
Instant
Instant
Re-strike
0.1 sec
0.1 sec
1 min
1 min
Instant
Instant
Instant
Instant
Instant
Life
100k
100k
24k+
15k
60k+
60k+
60k+
60k+
60k+
Energy Consumption Comparison
Light Source Lamp Life Comparision
Energy Consumption (Watts)
300
100,000
100K
90,000
250
80,000
70,000
200
60K+
60,000
150
50,000
40,000
100
30K
30,000
50
0
20,000
10K to 12K
10,000
70W 100W 150W 175W 250W 2x36 2x58
HID
Fluorescent
LED
Pulse Start Metal Halide
Fluorescent
High Pressure Sodium
0
24K
12K to 24K
11K to 20K
1K
1K to 2K
15K to 20K
Mercmaster™ LED Series Luminaires
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
Applications
Features
Standard Materials
• Mounting hoods and bodies: cast copperfree (4/10 of 1% max.)
aluminium
• All hardware and catch assemblies: stainless steel
• Globes: polycarbonate
Standard Finishes
• Mounting hoods, bodies and guards: baked gray epoxy-clad
finish, electrostatically applied for complete uniform protection
Certifications and Compliances
• NEC/CEC
— UL Standard: UL 1598, UL 1598A, UL 8750, UL 844
— CSA Standard: C22.2 No. 250.0, C22.2 No. 137
— cCSAus
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Pending Certifications and Compliances
• ATEX
— Gas: Zone 2
– Conforming to ATEX 94/9/CE: CE 0081
II 3 G
– ATEX Protection: Ex nA II
– T Rating:
• 70W equivalent: T4 (+104 ºF/+40 ºC), T4 (131 ˚F/55 ˚C)
T3C (149 ˚F/65 ˚C)
• 100W to 175W equivalent: T4 (+104 ºF/+40 ºC), T4
(131 ˚F/55 ˚C)
• 250W equivalent: T4 (+104 ºF/+40 ºC), T4 (122 ˚F/50 ˚C)
— Dust: Zone 22
– Conforming to ATEX 94/9/CE: CE 0081
II 3 D
– ATEX Protection: Ex t IIIC
– Surface Temperature: T197.6 ºF/T92 ºC Dc
– Ambient Temperature:
• 70W equivalent: -40 ˚F to 149 ˚F/-40 ˚C to 65 ˚C
• 100W to 175W equivalent: -40 ˚F to 131 ˚F/-40 ˚C to 55 ˚C
• 250W equivalent: -40 ˚F to 122 ˚F/-40 ˚C to 50 ˚C
– Index of Protection: IP66
• IECEx
— Gas: Zone 2
– IEC Protection: Ex nA II
– T Rating:
• 70W equivalent: T4 (+104 ºF/+40 ºC), T4 (131 ˚F/55 ˚C)
T3C (149 ˚F/65 ˚C)
• 100W to 175W equivalent: T4 (+104 ºF/+40 ºC), T4
(131 ˚F/55 ˚C)
• 250W equivalent: T4 (+104 ºF/+40 ºC), T4 (122 ˚F/50 ˚C)
— Dust: Zone 22
– IEC Protection: Ex t IIIC
– Surface Temperature: T197.6 ºF/T92 ºC Dc
– Ambient Temperature:
• 70W equivalent: -40 ˚F to 149 ˚F/-40 ˚C to 65 ˚C
• 100W to 175W equivalent: -40 ˚F to 131 ˚F/-40 ˚C to 55 ˚C
• 250W equivalent: -40 ˚F to 122 ˚F/-40 ˚C to 50 ˚C
– Index of Protection: IP66
• Ex Standards: IEC 60079-0; 60079-15; 60079-31
Related Products
• NEC, Class I, Division 2 photocells for classified use are available,
see PCD2 Series.
• Mounting hoods
— With photocontrols are not rated IP66
1
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
• Compact light-weight low profile design is suited for low
mounting heights.
• Modular design allows scores of fixture component
combinations to meet installation needs. Uses same mounting
hoods as Mercmaster III.
• Fixture housing and mounting hoods are copperfree cast
aluminium with baked epoxy finish. All exposed hardware is
stainless steel.
• Accommodates a wide range of voltages.
• Ambient temperatures:
— 70W equivalent: -40 ˚F to 149 ˚F/-40 ˚C to 65 ˚C
— 100W to 175W equivalent: -40 ˚F to 131 ˚F/-40 ˚C to 55 ˚C
— 250W equivalent: -40 ˚F to 122 ˚F/-40 ˚C to 50 ˚C
• Electrical: 120-277 Vac, 50/60 Hz; 347-480 Vac, 50/60 Hz
• Pole terminal block: 1 x 8-24 AWG; 1 x 0.75 to 6 mm2.
• Hinge has high lip for added safety during installation
and servicing. Hinge and bolt construction assures 360º
compression at all points on ballast housing gasket for positive
sealing. Swing away design of captive bolt and nut simplifies
servicing.
• All Mercmaster mounting hoods have provision for easy field
installation of fuses in fixtures (see Fixture Unit — Electrical
Specification).
• NPT and metric threads standard.
Lighting
• Enclosed and gasketed fixtures suitable for use in:
— Marine and wet locations
— A wide range of industrial, chemical processing and other
areas where flammable gases and vapors are present
— Areas of low clearance, low ceiling heights or where fixture
weights must be minimized
— Non-hazardous locations where severe weather conditions,
excessive moisture, dirt, dust, corrosive atmosphere or high
ambient temperatures are encountered
• Typical applications include:
— Pulp and paper mills
— Processing plants
— Chemical plants
— Oil refineries
— Foundries
— Manufacturing plants
— Storage areas
— Waste and sewage treatment
— Parking garages
— Other areas where dust, water, dirt and rough usage are a
problem
Mercmaster™ LED Series Luminaires
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
Lighting
Illustrated Features
Heatsink
Reliable heat transfer via the cast, epoxy
powder coat aluminium body. Provides
maximum heat dissipation from the LED
assembly to the outside environment.
Driver Assembly
Utilizing non-sparking components
avoiding the ignition of gases or vapors
that may be present (nA).
LED Chamber
Protected by polycarbonate lens, allows
for easy maintenance access.
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Modular Plug between LED and driver.
Terminal Blocks (Zone 2)
A seven-point terminal block is provided
to facilitate wiring. Terminal block
accommodates wire size ranging from #8
to #24 AWG.
Epoxy Finish
Ballast housing, hoods and guards are
copperfree aluminium with epoxy powder
coat finish.
Fuses
Two screws secure fuse kit to mounting
boss in any Mercmaster mounting hood.
Fuse included.
Photocell
Available for all fixtures except cone and
ceiling mount. Installs through knock-out
in mounting hood. Provides continuous
ON-OFF dusk-to-dawn control.
Electrical Protection
Ground wire provided to bond mounting
hood to ballast housing.
Safety
Rounded heatsink edges prevent possible
injury during installation.
Cooler Operating Cone Hood
Larger sloped surface sheds dusts, dirt
and combustible fibers providing better
heat dissipation.
Mounting Hood and Globe Gaskets
Silicone rubber gaskets seals out
moisture, dirt and dust. Stays flexible,
withstands high temperatures. Closure
design assures uniform gasket
compression.
"Safety" High Hinge
Extra-high hinge provides additional
protection against accidental ballast
housing disengagement during installation
or maintenance.
Stainless Steel Latch Assembly
Captive, stainless steel latch assembly
bolt and nut closes securely, resists attack
of corrosive atmospheres. Swing-away
design simplifies servicing.
2
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaires
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
Order using catalog numbering guide below or select catalog number from tables on following pages.
Catalog Numbering Guide
MLEDN
A
Mercmaster LED Series:
MLEDN - NEC/CEC
MLEDNA - ATEX/IECEx 
17
2
Light Level Equivalent:
70 - 70 W HPS/PSMH
10 - 100 W HPS/PSMH
15 - 150 W HPS/PSMH
17 - 175 W PSMH 
25 - 250 W HPS/PSMH
5
Optical Assembly:
P - Polycarbonate
Globe
Hub Size:
2 - 3/4” NPT
3 - 1” NPT
4 - 1-1/4” NPT
stanchion
5 - 1-1/2” NPT
stanchion
6 - Metric M20
BU
H1
Voltage:
BU - Universal
Voltages
120-277 Vac,
50/60 Hz
BH - 347-480 Vac,
50/60 Hz
Light Distribution:
5 - NEMA Type 5
Symmetrical
Options:
F - Fusing 
Lighting
Mounting:
A - Pendant
C - Ceiling 
D - Pendant Cone
R - 90º Stanchion
S - 25º Stanchion
W - Wall
P
For NEC Only:
H1 - Photocontrol 120 V
H2 - Photocontrol 208 V
H3 - Photocontrol 240 V
H4 - Photocontrol 277 V
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
 IECEx/ATEX Certification pending for: Zone 2 and 22;
II 3 GD.
 Ceiling mount luminaries are not designed to use the PCD2 photocontrol. Ceiling mounts must use an FS/FD box with a photocontrol. Contact your local
sales representative for more information.
 175 W Pulse Start Metal Halide only. Does not have a High Pressure Sodium equivalent.
 Canadian Electrical Code does NOT allow fusing in hazardous locations V. Fuse not CEC rated.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
3
Mercmaster™ LED Series Luminaire Technical Data
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
Technical Data
NEC/CEC
Lamp
Light Level
Equivalent
Type
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
100 Watt
HPS
150 Watt
HPS
175 Watt
PSMH
250 Watt
PSMH
IECEx/ATEX
Gas
Dust
Ambient
Temperature
(°F/°C)
Supply Wire
Temperature
(°F/°C)
Class I,
Division 2/
Class I, Zone 2 
104/40
140/66
T4A
131/55
167/75
T4
143/65
194/90
T3C
T6
T5
104/40
140/66
T4A
T6
T6
131/55
167/75
T4
104/40
140/66
T4A
LED
Lighting
70 Watt
HPS
Gas
Groups
Class II,
Division 1 and 2 
Ex II 3G 
Ex NA
Groups
T6
A, B, C, D
LED
T6
T6
E, F, G
A, B, C, D
T5
E, F, G
T6
T5
T6
LED
T6
A, B, C, D
E, F, G
131/55
167/75
T4
T6
T5
104/40
140/66
T4A
T6
T6
131/55
167/75
T4
104/40
140/66
T4A
LED
A, B, C, D
E, F, G
T6
T5
T6
LED
T6
A, B, C, D
122/50
167/75
E, F, G
T4
T6
T5
“T” Numbers Represent the Maximum Internal Temperature  or Maximum Surface Temperature 
NEC/CEC
“T” #
T1
350
325
T2
T2A
T2B
T2C
T2D
T3
T3A
T3B
T3C
T4
T4A
T5
T6
Temp.
Range (ºF)
351450
326350
301325
281300
261280
231260
216230
201215
181200
166180
161165
136160
121135
101120
86100
85
IEC
“T” #
T1
T2
T3
T4
T5
T6
Temp.
Range (°C)
301-450
201-300
136-200
101-135
86100
85
 T numbers represent the maximum internal temperature for Class I, Division 2 and Class I, Zone 2 locations designated by the NEC.
 T numbers represent the maximum surface temperature under a dust blanket for Class II, Division 1 and Class I, Zone 2 as designated by the NEC or Zone 2
(Gas) and 22 (Dust) locations as designated by the IEC.
4
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaire Technical Data
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
Lamp Comparison Chart
Lamp Data
Input Power
.31 @ 120 V
35
.17 @ 277 V
33
.41 @ 120 V
47.5
.20 @ 277 V
46
.53 @ 120 V
61
.25 @ 277 V
62
.63 @ 120 V
74
.29 @ 277 V
72
.80 @ 120 V
95.5
.36 @ 277 V
92
MLEDN70
MLEDN100
MLEDN150
MLEDN175
MLEDN250
Lumens
CRI
Lamp Life (Hours)
Color Temp CCT
2300
70
60,000+
5650
3450
70
60,000+
5650
4850
70
60,000+
5650
6076
70
60,000+
5650
9455
70
60,000+
5650
Lighting
Line Current Amps
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Mercmaster LED Ballast and Mounting Hood Weights
Description
Weight in Lbs/Kg
Description
Weight in Lbs/Kg
Description
Weight in Lbs/Kg
Fixture Unit
10.6/4.8
Pendant
2.25/1.0
Wall
4.00/1.8
Pendant Cone
2.50/1.1
25° Stanchion
3.25/1.5
Ceiling
3.00/1.4
90° Stanchion
3.75/1.7
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
5
Mercmaster™ LED Series Luminaires
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
LED Wattage
BU/BH
Lamp Wattage Equivalent
Hub Size
Conformance
Catalog Numbers 
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Lighting
Pendant — One Hub, Rigid Mounting
35/33 W
70 W HPS/PSMH
3/4
NEC/CEC
MLEDNA702P5
47.5/46 W
100 W HPS/PSMH
3/4
NEC/CEC
MLEDNA102P5
61/62 W
150 W HPS/PSMH
3/4
NEC/CEC
MLEDNA152P5
74/72 W
175 W PSMH
3/4
NEC/CEC
MLEDNA172P5
95.5/92 W
250 W HPS/MH
3/4
NEC/CEC
MLEDNA252P5
35/33 W
70 W HPS/PSMH
1
NEC/CEC
MLEDNA703P5
47.5/46 W
100 W HPS/PSMH
1
NEC/CEC
MLEDNA103P5
61/62 W
150 W HPS/PSMH
1
NEC/CEC
MLEDNA153P5
74/72 W
175 W PSMH
1
NEC/CEC
MLEDNA173P5
95.5/92 W
250 W HPS/PSMH
1
NEC/CEC
MLEDNA253P5
35/33 W
70 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAA706P5
47.5/46 W
100 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAA106P5
61/62 W
150 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAA156P5
74/72 W
175 W PSMH
M20
ATEX/IECEx 
MLEDNAA176P5
95.5/92 W
250 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAA256P5
Pendant Cone — One Hub, Rigid Mounting
35/33 W
70 W HPS/PSMH
3/4
NEC/CEC
MLEDND702P5
47.5/46 W
100 W HPS/PSMH
3/4
NEC/CEC
MLEDND102P5
61/62 W
150 W HPS/PSMH
3/4
NEC/CEC
MLEDND152P5
74/72 W
175 W PSMH
3/4
NEC/CEC
MLEDND172P5
95.5/92 W
250 W HPS/PSMH
3/4
NEC/CEC
MLEDND252P5
35/33 W
70 W HPS/PSMH
1
NEC/CEC
MLEDND703P5
47.5/46 W
100 W HPS/PSMH
1
NEC/CEC
MLEDND103P5
61/62 W
150 W HPS/PSMH
1
NEC/CEC
MLEDND153P5
74/72 W
175 W PSMH
1
NEC/CEC
MLEDND173P5
95.5/92 W
250 W HPS/PSMH
1
NEC/CEC
MLEDND253P5
35/33 W
70 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAD706P5
47.5/46 W
100 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAD106P5
61/62 W
150 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAD156P5
74/72 W
175 W PSMH
M20
ATEX/IECEx 
MLEDNAD176P5
95.5/92 W
250 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAD256P5
 IECEx/ATEX Certification pending for: Zone 2 and 22;
 Suffix
Voltage AC
Frequency
BU
120 - 277
50/60 Hz
BH
347 - 480
50/60 Hz
6
II 3 GD.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaires
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
LED Wattage
BU/BH
Lamp Wattage Equivalent
Hub Size
Conformance
Catalog Numbers 
Ceiling — Five Hubs, Four Close-up Plugs
35/33 W
70 W HPS/PSMH
3/4
NEC/CEC
MLEDNC702P5
47.5/46 W
100 W HPS/PSMH
3/4
NEC/CEC
MLEDNC102P5
61/62 W
150 W HPS/PSMH
3/4
NEC/CEC
MLEDNC152P5
74/72 W
175 W PSMH
3/4
NEC/CEC
MLEDNC172P5
95.5/92 W
250 W HPS/PSMH
3/4
NEC/CEC
MLEDNC252P5
70 W HPS/PSMH
1
NEC/CEC
MLEDNC703P5
100 W HPS/PSMH
1
NEC/CEC
MLEDNC103P5
61/62 W
150 W HPS/PSMH
1
NEC/CEC
MLEDNC153P5
74/72 W
175 W PSMH
1
NEC/CEC
MLEDNC173P5
95.5/92 W
250 W HPS/PSMH
1
NEC/CEC
MLEDNC253P5
35/33 W
70 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAC706P5
47.5/46 W
100 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAC106P5
61/62 W
150 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAC156P5
74/72 W
175 W PSMH
M20
ATEX/IECEx 
MLEDNAC176P5
95.5/92 W
250 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAC256P5
Lighting
35/33 W
47.5/46 W
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Wall — Five Hubs, Four Close-Up Plugs
35/33 W
70 W HPS/PSMH
3/4
NEC/CEC
MLEDNW702P5
47.5/46 W
100 W HPS/PSMH
3/4
NEC/CEC
MLEDNW102P5
61/62 W
150 W HPS/PSMH
3/4
NEC/CEC
MLEDNW152P5
74/72 W
175 W PSMH
3/4
NEC/CEC
MLEDNW172P5
95.5/92 W
250 W HPS/PSMH
3/4
NEC/CEC
MLEDNW252P5
35/33 W
70 W HPS/PSMH
1
NEC/CEC
MLEDNW703P5
47.5/46 W
100 W HPS/PSMH
1
NEC/CEC
MLEDNW103P5
61/62 W
150 W HPS/PSMH
1
NEC/CEC
MLEDNW153P5
74/72 W
175 W PSMH
1
NEC/CEC
MLEDNW173P5
95.5/92 W
250 W HPS/PSMH
1
NEC/CEC
MLEDNW253P5
35/33 W
70 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAW706P5
47.5/46 W
100 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAW106P5
61/62 W
150 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAW156P5
74/72 W
175 W PSMH
M20
ATEX/IECEx 
MLEDNAW176P5
95.5/92 W
250 W HPS/PSMH
M20
ATEX/IECEx 
MLEDNAW256P5
 IECEx/ATEX Certification pending for: Zone 2 and 22;
 Suffix
Voltage AC
Frequency
BU
120 - 277
50/60 Hz
BH
347 - 480
50/60 Hz
II 3 GD.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
7
Mercmaster™ LED Series Luminaires
Enclosed and Gasketed Fixtures
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
LED Wattage
BU/BH
Lamp Wattage Equivalent
Hub Size
Conformance
Catalog Numbers 
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
MLEDNS704P5
MLEDNS104P5
MLEDNS154P5
MLEDNS174P5
MLEDNS254P5
MLEDNS705P5
MLEDNS105P5
MLEDNS155P5
MLEDNS175P5
MLEDNS255P5
MLEDNAS704P5
MLEDNAS104P5
MLEDNAS154P5
MLEDNAS174P5
MLEDNAS254P5
MLEDNAS705P5
MLEDNAS105P5
MLEDNAS155P5
MLEDNAS175P5
MLEDNAS255P5
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Lighting
25° Stanchion — One Hub
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
70 W HPS/PSMH
100 W HPS/PSMH
150 W H HPS/PSMH
175 W PSMH
250 W HPS/PSMH
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
35/33 W
47.5/46 W
61/62 W
74/72 W
95.5/92 W
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
70 W HPS/PSMH
100 W HPS/PSMH
150 W HPS/PSMH
175 W PSMH
250 W HPS/PSMH
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/4
1-1/4
1-1/4
1-1/4
1-1/4
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
90° Stanchion — One Hub
 IECEx/ATEX Certification pending for: Zone 2 and 22;
 Suffix
Voltage AC
Frequency
BU
120 - 277
50/60 Hz
BH
347 - 480
50/60 Hz
8
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
NEC/CEC
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
ATEX/IECEx 
MLEDNR704P5
MLEDNR104P5
MLEDNR154P5
MLEDNR174P5
MLEDNR254P5
MLEDNR705P5
MLEDNR105P5
MLEDNR155P5
MLEDNR175P5
MLEDNR255P5
MLEDNAR704P5
MLEDNAR104P5
MLEDNAR154P5
MLEDNAR174P5
MLEDNAR254P5
MLEDNAR705P5
MLEDNAR105P5
MLEDNAR155P5
MLEDNAR175P5
MLEDNAR255P5
II 3 GD.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaire Ballast Bodies
Enclosed and Gasketed Fixtures
NEC/CEC
Simultaneous Exposure
Type 3R, 4X
IP66
Suitable for Use in Wet Locations
Marine Outside Type (Salt Water)
NEC/CEC
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Group IIC
Class II, Division 1, Group E, F, G
Class II, Division 2, Group F, G
Class III
Fixture Unit — Electrical Specification
LED Wattage
BU/BH
Light Level
Equivalent
35 / 33 W
70 W HPS
Catalog Number
Current Draw
Fuse Kit 
120 Vac @ .31 Amps
277 Vac @ .17 Amps
F3
Fixture Unit
MLEDN70P5
MLEDNA70P5
70 W HPS
347 Vac @ .32 Amps
480 Vac @ .23 Amps
F3
47.5 / 46 W
100 W HPS
120 Vac @ .41 Amps
277 Vac @ .20 Amps
F3
100 W HPS
347 Vac @ .32 Amps
480 Vac @ .23 Amps
F3
61 / 62 W
150 W HPS
120 Vac @ .53 Amps
277 Vac @ .25 Amps
F3
61 / 62 W
74 / 72 W
150 W HPS
347 Vac @ .32 Amps
480 Vac @ .23 Amps
175 W MH
120 Vac @ .63 Amps
277 Vac @ .29 Amps
F3
MLEDN10P5
NEC/CEC
95.5 / 92 W
175 W MH
347 Vac @ .32 Amps
480 Vac @ .23 Amps
250 W HPS/MH
120 Vac @ .80 Amps
277 Vac @ .36 Amps
NEC/CEC
MLEDN15P5
NEC/CEC
NEC/CEC
MLEDN17P5
NEC/CEC
F3
F3
250 W HPS/MH
347 Vac @ .32 Amps
480 Vac @ .23 Amps
MLEDN17P5
NEC/CEC
MLEDN25P5
NEC/CEC
MLEDN25P5
347-480 Vac,
50/60 Hz
BH
120-277 Vac,
50/60 Hz
BU
347-480 Vac,
50/60 Hz
BH
120-277 Vac,
50/60 Hz
BU
347-480 Vac,
50/60 Hz
BH
120-277 Vac,
50/60 Hz
BU
347-480 Vac,
50/60 Hz
BH
120-277 Vac,
50/60 Hz
BU
347-480 Vac,
50/60 Hz
BH
ATEX/IECEx 
F3
F3
BU
ATEX/IECEx 
MLEDN15P5
MLEDNA25P5
95.5 / 92 W
ATEX/IECEx 
MLEDN10P5
MLEDNA17P5
74 / 72 W
ATEX/IECEx 
NEC/CEC
MLEDNA15P5
120-277 Vac,
50/60 Hz
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
47.5 / 46 W
Voltage
Suffix
NEC/CEC
MLEDN70P5
MLEDNA10P5
Voltage Range
Lighting
35 / 33 W
Conformance
ATEX/IECEx 
NEC/CEC
 IECEx/ATEX Certification pending for: Zone 2 and 22;
II 3 GD.
 Canadian Electrical Code does NOT allow fusing in hazardous locations V. Fuse not CEC rated.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
9
Mercmaster™ LED Series Luminaire Mounting Hoods
Enclosed and Gasketed Fixtures
Mounting Hoods
Description
Hub Size
Catalog Number
Pendant
One Hub, Rigid Mounting
3/4
KPA-75
1
KPA-100
M20
KPA-M20
3/4
KPCH-75
1
KPCH-100
M20
KPCH-M20
3/4
1
KPC-75
KPC-100
M20
KPC-M20
3/4
KPWB-75
1
M20
KPWB-100
KPWB-M20
1-1/4
KPS-125
1-1/2
KPS-150
1-1/4
KPST-125
1-1/2
KPST-150
Pendant Cone
One Hub, Rigid Mounting
Lighting
Ceiling
Five Hubs, Four Close-Up Plugs
Wall
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Five Hubs, Four Close-Up Plugs
25° Stanchion
One Hub
90° Stanchion
One Hub
Replacement Parts
Description
Catalog Number
Globe
59607647000
Globe Gasket — Silicone Rubber
10
KRF-GK
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaire Dimensions
Enclosed and Gasketed Fixtures
Dimensions in Inches/Millimeters
5.59"
[142.0 mm]
Depending on
the length of
the conduit stem
10.92"
[277.36 mm]
6.66"
[169.16 mm]
15.40" Dia.
[391.16 mm]
15.40" Dia.
[391.16 mm]
Pendant Cone Mount
Lighting
Pendant Mount
18.63" [473.2 mm]
10.93" [277.6 mm]
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
7.22"
[183.38 mm]
4.06"
[103.1 mm]
8.54"
[216.9 mm]
15.40" Dia.
[391.16 mm]
15.40" Dia.
[391.16mm]
Ceiling Mount
Wall Mount
18.87" [479.3 mm]
16.93"
[430.0 mm]
17.22" [437.4 mm]
15.27"
[387.9 mm]
9.79" [248.7 mm]
9.25"
[235.0 mm]
25°
15.40" Dia.
[391.16 mm]
25° Stanchion Mount
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
15.40" Dia.
[391.16 mm]
90° Stanchion Mount
11
PCD2 Series Factory Sealed Hazardous Location Photocontrol 
For Use in Class I, Division 2, Groups A, B, C, D Locations
Maintains Class I, Division 2 rating for Mercmaster III, Mercmaster III Low Profile, Mercmaster III 50-250 and 400 Series Luminaires; Mercmaster LED Series.
Class I, Division 2, Groups A, B, C, D
NEMA 4X
Applications
Materials
• Encapsulated photocontrol provides automatic dusk-to-dawn
lighting control in Class I, Division 2 locations.
• Typical applications include walkways, security areas and any
other outdoor lighting application.
• For use with Mercmaster III, Mercmaster III Low Profile,
Mercmaster III 50-250 and 400 Series Luminaires; Mercmaster
LED Series.
• For remote mounting in FS Boxes.
• Encapsulated with epoxy sealing compound
• FS: aluminium
Certifications and Compliances
• UL Standard: 1604 – Hazardous (Classified) Locations
• cULus Recognized
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
Lighting
Features
• Factory sealed design eliminates the need for an explosionproof
enclosure.
• Can be easily installed in the field.
• Solid state design for performance and reliability.
• Available for 120, 208, 240, or 277 volts.
• 50-400 W HID, incandescent, fluorescent and LED, 50/60 Hz.
• 1000 VA Voltage/Ampere
• Minimum time delay: 15 seconds to eliminate nuisance tripping.
• Provided with (3) 18AWG stranded leads 6”/152.4 mm in length.
• Will fit through standard 1/2” knockout.
Factory-Installed Photocontrol
Dimensions
Add to fixture catalog after voltage; i.e.: KPWBL1075MTH1.
Mercmaster III wall mounting hood
with photocontrol installed shown
Voltage Range
Suffix Designation
120 V, 50/60 Hz
H1
208 V, 50/60 Hz
H2
240 V, 50/60 Hz
H3
277 V, 50/60 Hz
H4
1.13/28.7
Photocontrol in FS Cover for Use with FS/FD Box
Supplied with two stainless steel screws. For neoprene gasket, order catalog number FS-GKR-1N.
Voltage Range
Catalog Number
120V, 50/60 Hz
FSKA-PC120D2
208-277V, 50/60 Hz
FSKA-PC247D2
1.38/34.9
2.56/65.0
Photocontrol for Field Installation
Max. Current
Catalog Number
120 V, 50/60 Hz
Voltage Range
8.3 Amp
PC120D2
208-277 V, 50/60 Hz
3.5 Amp
PC247D2
0.69/
17.5
1.19/30.2
1.94/49.2
 Fixtures with photocontrols are not rated IP66.
12
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaire Photometric Data
Enclosed and Gasketed Fixtures
DATA SHOWN IS ABSOLUTE
Zonal Lumen Summary
Zone
Lumens % Fixture
0-30
829
36.1
0-40
1326
57.7
0-60
2149
93.5
0-90
2292
99.7
CIE Type - Direct
Plane
Spacing Criteria
0-Deg
90-Deg
1.3
1.3
90°
75°
400
60°
Lighting
REPORT NUMBER: MLEDN70P5BU
Lamps: Mercmaster LED, Class 1, Div 2, Polycarbonate Optic
Candela Distribution
0.0
22.5
45.0
67.5
90.0
Flux
0 1054 1054 1054 1054 1054
5 1048 1047 1051 1047 1048
100
15 1016 1014 1016 1014 1016
287
25
977
961
941
961
977
442
35
805
779
824
779
805
497
45
583
607
603
607
583
465
55
408
425
411
425
408
358
65
185
146
139
146
185
133
75
5
5
4
5
5
9
85
1
0
0
0
1
1
90
0
0
0
0
0
800
45°
0°
REPORT NUMBER: MLEDN10P5BU
Lamps: Mercmaster LED, Class 1, Div 2, Polycarbonate Optic
Candela Distribution
0.0
22.5
45.0
67.5
90.0
Flux
0 1580 1580 1580 1580 1580
5 1569 1568 1568 1568 1569
149
15 1509 1510 1513 1510 1509
427
25 1412 1414 1437 1414 1412
655
35 1177 1215 1171 1215 1177
748
45
934
915
893
915
934
707
55
577
588
632
588
577
527
65
228
218
195
218
228
209
75
6
7
6
7
6
13
85
0
0
0
0
0
1
90
0
0
0
0
0
15°
30°
Zonal Lumen Summary
Zone
Lumens % Fixture
0-30
1231
35.8
0-40
1980
57.6
0-60
3213
93.5
0-90
3438
100.0
CIE Type - Direct
Plane
Spacing Criteria
0-Deg
90-Deg
1.2
1.2
90°
75°
550
60°
1100
45°
1650
0°
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
15°
30°
13
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
1200
Mercmaster™ LED Series Luminaire Photometric Data
Enclosed and Gasketed Fixtures
Lighting
DATA SHOWN IS ABSOLUTE
REPORT NUMBER: MLEDN15P5BU
Lamps: Mercmaster LED, Class 1, Div 2, Polycarbonate Optic
Candela Distribution
0.0
22.5
45.0
67.5
90.0
Flux
0 2208 2208 2208 2208 2208
5 2202 2195 2197 2195 2202
209
15 2137 2131 2127 2131 2137
603
25 2045 2003 1977 2003 2045
926
35 1669 1658 1735 1658 1669 1051
45 1252 1282 1297 1282 1252
988
55
836
850
838
850
834
746
65
276
307
333
307
276
298
75
16
12
11
12
16
22
85
2
1
1
1
2
2
90
1
0
0
0
1
Zonal Lumen Summary
Zone
Lumens % Fixture
0-30
1738
35.8
0-40
2789
57.5
0-60
4523
93.3
0-90
4844
99.9
CIE Type - Direct
Plane
Spacing Criteria
0-Deg
90-Deg
1.2
1.2
90°
75°
750
60°
1500
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
45°
2250
0°
REPORT NUMBER: MLEDN17P5BU
Lamps: Mercmaster LED, Class 1, Div 2, Polycarbonate Optic
Candela Distribution
0.0
22.5
45.0
67.5
90.0
Flux
0
0.0
22.5
45.0
67.5
90.0
Flux
5 2739 2739 2739 2739 2739
15 2724 2724 2725 2724 2724
259
25 2660 2658 2655 2658 2660
752
35 2553 2508 2462 2508 2553 1156
45 2069 2062 2201 2062 2069 1312
55 1580 1614 1655 1614 1580 1243
65 1047 1093 1046 1093 1047
943
75
353
380
391
390
353
378
85
19
15
16
15
19
28
90
2
1
1
1
2
2
15°
30°
Zonal Lumen Summary
Zone
Lumens % Fixture
0-30
2167
35.7
0-40
3478
57.2
0-60
5664
93.2
0-90
6072
99.9
CIE Type - Direct
Plane
Spacing Criteria
0-Deg
90-Deg
1.2
1.2
90°
75°
950
60°
1900
45°
2850
0°
14
15°
30°
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Mercmaster™ LED Series Luminaire Photometric Data
Enclosed and Gasketed Fixtures
DATA SHOWN IS ABSOLUTE
Zonal Lumen Summary
Zone
Lumens % Fixture
0-30
3326
35.2
0-40
5372
56.8
0-60
8844
93.5
0-90
9445
99.9
CIE Type - Direct
Plane
Spacing Criteria
0-Deg
90-Deg
1.2
1.2
90°
75°
1450
60°
Lighting
REPORT NUMBER: MLEDN250P5BU
Lamps: Mercmaster LED, Class 1, Div 2, Polycarbonate Optic
Candela Distribution
0.0
22.5
45.0
67.5
90.0
Flux
0 4206 4206 4206 4206 4206
5 4170 4182 4177 4182 4170
397
15 4035 4046 4038 4046 4035 1145
25 3913 3888 3829 3888 3913 1784
35 3211 3233 3380 3233 3211 2046
45 2484 2524 2532 2524 2484 1942
55 1710 1763 1708 1763 1710 1530
65
682
564
606
564
682
568
75
20
18
17
18
20
31
85
2
1
1
1
2
2
90
1
1
0
1
1
2900
45°
LIGHTING: ENCLOSED AND GASKETED — AREA — LED/INDUCTION
4350
0°
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
15°
30°
15
Areamaster™ Green LED Flood/High Bay Luminaires
General Duty
Marine Outside Type (Salt Water)
Wet Locations
Type 4X
IP66
Applications
• Locations where a green light is required to see flaws on steel.
Features
• LED color: green.
• Compact in size, attractively styled contemporary design,
rugged and dependable.
• Easy to install and service.
• One-piece housing.
• One-piece lens cover. Secured by four M6 captive stainless
steel slotted hex-head bolts.
• Thermal shock and impact resistant glass lens.
• Heavy duty, high temperature silicone rubber gasket, firmly
seated.
• Floodlight Mounting:
— Yoke mount, zinc plated steel yoke with architectural bronze
polyester finish.
• High Bay Mounting:
— (1) Conduit entry on back of luminaire.
— Rotate yoke up or remove.
• Vibration rated in all configurations.
• Cool operating temperatures translate into long luminaire life.
• Total of three (3) 3/4" NPT entries with integral bushings.
• Two (2) aluminum close up plugs provided.
• Electrical: 120-277 Vac, 50/60 Hz.
• Nominal input power: 165.
• Maximum input Amps: 1.40 - 0.60.
• Power factor: > 0.90.
• Terminal block (screw type for secure connection) can accept
24-10 AWG wire.
Floodlight
High Bay
• Ballast housing and lens door: copperfree (4/10 of 1% max.)
aluminum
• Gasket: silicone rubber
• Reflector: metallized high reflectance finish
• Yoke mount: zinc plated steel
• Bolts: stainless steel
• Plugs: (2) aluminum provided
Standard Finishes
• Housing, lens cover and yoke mount: architectural bronze
polyester
Lighting
LIGHTING: GENERAL LIGHTING — AREA — FLOODLIGHTS
Standard Materials
1386
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Areamaster™ Green LED Flood/High Bay Luminaires
General Duty
Marine Outside Type (Salt Water)
Wet Locations
Type 4X
IP66
Line Voltage
Yoke Mount Catalog Number
120-277
50/60 Hz
AMLED77YBUGR
Accessories
Description
Catalog Numbers
Crossarm Mounting Bracket
Has 180° horizontal adjustment — degree marked. Facilitates mounting
floodlight to crossarm or other flat surface, or to G-AM-8-WB. Includes
floodlight yoke bolts. Malleable iron, zinc plated, chromate sealed,
architectural bronze polyester finish.
G-AM-8-CA
Used with G-AM-8-CA. Clamps to 1” to 2-1/2” pipe, vertical or horizontal,
or mounts on flat surfaces. Includes U-bolt and crossarm bracket bolts.
Malleable iron, zinc plated, chromate sealed, with architectural bronze polyster
finish.
G-AM-8-WB
Slip-fits 1-1/2” or 2” pipe size poletop tenons. Includes floodlight yoke bolts,
3 locking bolts, and cord grip. Body is malleable iron-zinc plated, chromate
sealed, with cast aluminum cap. Assembly has architectural bronze polyester
finish.
G-SF20
Slip-fits 2” or 2-1/2” poletop tenons. Includes floodlight yoke bolts, 3 locking
bolts, and cord grip. Malleable iron, zinc plated, chromate sealed, with
architectural bronze polyester finish.
G-AM-8-SF
Pipe or Wall Mount Bracket
Poletop Slip-Fitter
LIGHTING: GENERAL LIGHTING — AREA — FLOODLIGHTS
Poletop Slip-Fitter
Lighting
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
1387
Areamaster™ Green LED Flood/High Bay Luminaire Dimensions
General Duty
Dimensions in Inches/Millimeters
Floodlight
15.30 in./388.6 mm
3.70 in./93.9 mm
7.20 in2/
4645.2 mm2
14.10 in./
358.1 mm
Conduit
Entry
(Pendant
Mount)
15.40 in./
391.2 mm
Set
Screw 5.70 in./
144.78 mm
(4) Yoke Bolts
2.25 in./
57.2 mm
Conduit
Entry
Yoke
3.64 Turning Radius
180° Rotation
(3) hubs for
3/4" NPT Conduit
4.83 in./
122.7 mm 3.50 in./
88.9 mm
1.75 in./
(3) Mounting Holes
44.45 mm
0.56 Dia.
3.50 in./88.9 mm
LIGHTING: GENERAL LIGHTING — AREA — FLOODLIGHTS
High Bay Pendant Mount
Lighting
6 in./
152.4 mm
1388
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Areamaster™ Green LED Flood/High Bay Luminaire Photometrics
General Duty
DATA SHOWN IS ABSOLUTE
REPORT NUMBER: AMLED77YBUGR
Fixture: Flood Mount, Led Board 60 LED, Specular Reflector 6-1/2 X 6-1/2 Tapered To 3-1/2 X 3-1/2 , Lens Clear 7 x 7"
Floodlight Characteristics
IES Type
7H X 7V
Maximum Candlepower
3424. AT 22.5 H, 25.5 V
Horizontal Beam Angle (50%)
101.5 deg
Vertical Beam Angle (50%)
100.3 deg
Horizontal Field Angle (10%)
134.6 deg
Vertical Field Angle (10%)
134.2 deg
Beam Lumens (Efficiency)
6436. (79.7)
Field Lumens (Efficiency)
7949. (98.4)
Total Lumens (Efficiency)
8075. (100.0)
Plot(s) is/are single sweep(s) — Stray light is NOT accounted for. Lateral trace thru 90 deg Vertical.
Axial Candlepower
Deg
Horizontal
Deg
Vertical
90.0
0.
90.0
0.
85.0
20.
85.0
1.
22.
75.0
3.
65.0
438.
65.0
444.
55.0
147 9.
55.0
1460.
47.5
1889.
47.5
1828.
42.5
2146.
42.5
2121.
37.5
2539.
37.5
2515.
33.0
2807.
33.0
2928.
29.0
3043.
29.0
3121.
25.5
3163.
25.5
3186.
22.5
3063.
22.5
3080.
19.5
2968.
19.5
2936.
17.0
2807.
17.0
2758.
15.0
2795.
15.0
2731.
13.0
2771.
13.0
2706.
11.0
2732.
11.0
2704.
9.0
2714.
9.0
2711.
7.0
2721.
7.0
2722.
5.0
2728.
5.0
2731.
3.0
2736.
3.0
2730.
1.0
2729.
1.0
2731.
0.0
2730.
0.0
2730.
LIGHTING: GENERAL LIGHTING — AREA — FLOODLIGHTS
75.0
Lighting
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
1389
Areamaster™ LED Flood/High Bay Luminaires
NEC/CEC:
Class I, Division 2, A, B, C, D
Marine Outside Type (Salt Water)
Wet Locations
Type 4 and 3R
Applications
• Typical applications include:
— Pulp and paper mills
— Processing plants
— Chemical plants
— Oil refineries
— Foundries
— Storage areas
— Waste and sewage treatment
— Parking garages
— Other areas where dust, water, dirt and rough usage are a
problem
Features
• Compact in size, attractively styled contemporary design,
rugged and dependable.
• Easy to install and service.
• One-piece housing.
• One-piece lens hinged cover. Secured by four M6 captive
stainless steel slotted hex-head bolts.
• Thermal shock and impact resistant glass lens.
• Heavy duty, high temperature silicone rubber gasket,
mechanically secured.
• Universal design for flood and highbay mounting
• Floodlight Mounting:
— Yoke mount, zinc plated steel yoke with architectural bronze
polyester finish.
• High Bay Mounting:
— (1) Conduit entry on back of luminaire with locking set screw.
— Rotate yoke up or remove.
• Vibration rated in all configurations.
• Cool operating temperatures translate into long luminaire life.
• Total of three (3) 3/4" NPT entries with integral bushings.
• Two (2) aluminum close up plugs provided.
• Electrical: 120-277 Vac, 50/60 Hz; 347 – 480 Vac, 50/60 Hz
• Terminal block (screw type for secure connection) can accept
24-10 AWG wire.
Floodlight
High Bay
•
•
•
•
•
•
•
•
Lighting: Enclosed and Gasketed — Floodlight
Standard Materials
Ballast housing and lens door: aluminum
Gasket: silicone rubber
Reflector: polymaris metallized high reflectance finish
Yoke mount: zinc plated steel
Bolts: stainless steel
Plugs: (2) aluminum provided
Tempered glass lens
Locking set screw: stainless steel
Standard Finishes
• Housing, lens cover and yoke mount: architectural bronze
polyester
Certifications and Compliances
• NEC/CEC
— UL Standard: UL 1598, UL 1598A, UL 8750, UL 844
— CSA Standards: C22.2 No. 250.0, C22.2 No. 137
— cULus
Lighting
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© February 2012
1155
Areamaster™ LED Flood/High Bay Luminaires
NEC/CEC:
Class I, Division 2, A, B, C, D
Marine Outside Type (Salt Water)
Wet Locations
Type 4 and 3R
“T” Numbers
Lamp
Supply Wire Temp.
(°F/°C)
Ambient Temp.
(°F/°C)
NEC/CEC
Class I, Division 2,
Groups A, B, C, D
LED
140/60
104/40
T4
“T” Numbers Represent the Maximum Lamp Temperature for Class I, Division 2 Locations
“T”
Number
T1
350
325
T2
T2A
T2B
T2C
T2D
T3
T3A
T3B
T3C
T4
T4A
T5
T6
Temp.
Range
(˚ºF)
664842
619662
574617
538572
502536
448500
421446
394419
358392
331356
322329
277320
250275
214248
187212
185
Temp.
Range
(°C)
351450
326350
301325
281300
261280
231260
216230
201215
181200
166180
161165
136160
121135
101120
86100
85
Electrical Specifications
Vac
Hz
Watts Input Power (Nom.)
Input Amps
(Max.)
Total Harmonic
Distortion
Power Factor
BU
120 - 277
50/60
127
1.40 - 0.60
5% - 10%
> 0.90
BH
347 - 480
50/60
127
0.50 - 0.35
7.5% - 9%
> 0.90
Lighting
Lighting: Enclosed and Gasketed — Floodlight
Voltage Range
Voltage Suffix
1156
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© February 2012
Areamaster™ LED Flood/High Bay Luminaires
NEC/CEC:
Class I, Division 2, A, B, C, D
Class I, Zone 2, AEx NR, Ex NR
IP66, 67
Marine, Wet Location
Type 4X
IECEx/ATEX:
II 3 GD
nA II
IP66, 67
Line Voltage
For Class 1, Division 2 Classified Duty and Marine Yoke Mount
Catalog Number
120-277
50/60 Hz
AMLED77YBU
120-277
50/60 Hz
AMLED77YBUGR ①
347-480
50/60 Hz
AMLED77YBH
Accessories
Description
Catalog Numbers
Crossarm Mounting Bracket
Has 180° horizontal adjustment — degree marked. Facilitates mounting
floodlight to crossarm or other flat surface, or to G-AM-8-WB. Includes
floodlight yoke bolts. Malleable iron, zinc plated, chromate sealed,
architectural bronze polyester finish.
G-AM-8-CA
Used with G-AM-8-CA. Clamps to 1” to 2-1/2” pipe, vertical or horizontal,
or mounts on flat surfaces. Includes U-bolt and crossarm bracket bolts.
Malleable iron, zinc plated, chromate sealed, with architectural bronze polyster
finish.
G-AM-8-WB
Slip-fits 1-1/2” or 2” pipe size poletop tenons. Includes floodlight yoke bolts,
3 locking bolts, and cord grip. Body is malleable iron-zinc plated, chromate
sealed, with cast aluminum cap. Assembly has architectural bronze polyester
finish.
G-SF20
Slip-fits 2” or 2-1/2” poletop tenons. Includes floodlight yoke bolts, 3 locking
bolts, and cord grip. Malleable iron, zinc plated, chromate sealed, with
architectural bronze polyester finish.
G-AM-8-SF
Pipe or Wall Mount Bracket
Poletop Slip-Fitter
Lighting
① Green LED. Nema 4X, general duty only. Non certified.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© October 2012
Lighting: Enclosed and Gasketed — Floodlight
Poletop Slip-Fitter
1157
Areamaster™ LED Flood/High Bay Luminaires
NEC/CEC:
Class I, Division 2, A, B, C, D
Marine Outside Type (Salt Water)
Wet Locations
Type 4 and 3R
Dimensions in Inches/Millimeters
Floodlight
15.30 in./388.6 mm
3.70 in./93.9 mm
7.20 in2/
4645.2 mm2
14.10 in./
358.1 mm
Conduit 15.40 in./
Entry
391.2 mm
(Pendant
Mount)
Set 5.70 in./
Screw 144.78 mm
2.25 in./
57.2 mm
Conduit
Entry
(4) Yoke Bolts
1.75 in./
44.45 mm
3.50 in./88.9 mm
Ground Terminal
Yoke
4.83 in./
122.7 mm 3.50 in./
88.9 mm
3.64 Turning Radius
180° Rotation
(3) hubs for 3/4" NPT Conduit
(3) Mounting Holes
0.56 Dia.
High Bay Pendant Mount
Ceiling
Jct Box
Set Screw
Rotate Yoke
Up or Remove
6 in./
152.4 mm
Areamaster LED Weight
Description
Weight in Lbs/Kg
Fixture Unit
22.00/10.0
Lighting
Lighting: Enclosed and Gasketed — Floodlight
12 in./ Required Minimum
304.8 mm Mounting Distance
1158
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© February 2012
Areamaster™ LED Flood/High Bay Luminaires
NEC/CEC:
Class I, Division 2, A, B, C, D
Marine Outside Type (Salt Water)
Wet Locations
Type 4 and 3R
Floodlight
Luminaire Lumens = 13138
Mounting Height = 12.00 ft, Tilt = 45°
Maximum Calculated Value = 25 Fc
Typical Footcandle Values
10
20
.1 fc
.5 fc
-20
1 fc
2 fc
Distance in feet
20 fc
10 fc
5 fc
0 footcandles (fc)
-10
-20
Distance in feet
Floodlight
Luminaire Lumens = 13138
Mounting Height = 20.00 ft, Tilt = 45°
Maximum Calculated Value = 10 Fc
Typical Footcandle Values
0
20
.5 fc
1 fc
2 fc
-10
Distance in feet
5 fc
10 fc
2 fc
0 footcandles (fc)
-10
0
24
35
803
2179
3011
3457
3969
4390
4697
4714
4765
4619
4514
4435
4338
4241
4201
4199
4186
4186
4205
4210
Degree
90
85
75
65
55
47.5
42.5
37.5
33
29
25.5
22.5
19.5
17
15
13
11
9
7
5
3
1
0
-1
-3
-5
-7
-9
-11
-13
-15
-17
-19.5
-22.5
-25.5
-29
-33
-37.5
-42.5
-47.5
-55
-65
-75
-85
-90
Vertical
0
3
57
690
2348
3017
3371
3916
4432
4785
4992
4932
4726
4452
4350
4262
4214
4183
4198
4207
4212
4212
4210
4208
4196
4179
4183
4198
4234
4262
4334
4507
4733
4925
4929
4681
4357
3845
3319
2970
2299
648
7
3
0
Distance in feet
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© February 2012
1159
Lighting: Enclosed and Gasketed — Area — HID
-10
2 fc
90
85
75
65
55
47.5
42.5
37.5
33
29
25.5
22.5
19.5
17
15
13
11
9
7
5
3
1
0
Horizontal
Lighting
0
Axial Candela
Degree
Areamaster™ LED Flood/High Bay Luminaires
NEC/CEC:
Class I, Division 2, A, B, C, D
Marine Outside Type (Salt Water)
Wet Locations
Type 4 and 3R
High Bay
CIE Type - General Diffuse
Luminaire Lumens = 13211
Polar Graph - High Bay
Coefficients of Utilization - Zonal Cavity Method
4500
3000
Zonal Lumen Summary
Zone
Lumens
0-30
3849
% Fixture
29.1
1500
Effective Floor Cavity Reflectance 0.20
Rcc
80
Rw
70
50
70
30
10
70
50
50
30
10
50
30
30
10
50
30
10
10
50
30
0
10
0
0
119
119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100
1
111
107 103 100 108 105 102 99 101 98 96
97 95 93
93
91
90
88
2
102
95
89
84
100 93
88 83 90 85 81
86 83 79
83
80
78
76
6804
51.2
3
94
84
77
71
91
83
76 71 80 74 69
77 72 68
75
71
67
65
12051
91.2
4
86
75
67
61
84
74
66 61 71 65 60
69 63 59
67
62
58
56
0-90
13196
99.9
5
79
67
59
53
77
66
58 52 64 57 52
62 56 51
60
55
51
49
90-120
4
0.00
6
73
60
52
46
71
60
52 46 58 51 45
56 50 45
55
49
45
43
90-130
6
0.1
7
68
55
46
41
66
54
46 40 52 45 40
51 45 40
50
44
39
38
90-150
11
0.1
8
63
50
42
36
61
49
41 36 48 41 36
47 40 35
45
40
35
33
90-180
14
0.1
9
59
46
38
32
57
45
37 32 44 37 32
43 36
32 42
36
32
30
0-180
13211
100.0
10
55
42
34
29
54
41
34 29 40 34 29
39 33
29 39
33
29
27
Lighting
Lighting: Enclosed and Gasketed — Floodlight
0-40
0-60
1160
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© February 2012
Download