DATA SHEET | CURTAIN CONTROLS
SKC-SC
SKC-SC controls fire curtains and smoke curtains.
The system is modular and can be configured on
a PC via a USB interface to provide the required
functionality for a project. Activation is via a
fire alarm system or its own smoke alarm and
manual control points.When the alarm is raised,
the system provides status messages and optical
or acoustic signalling. It monitors cables for wirebreak and short circuit.
The control panel is designed for the safe
operation of automatic smoke and fire curtains. It
contains programs for intermediate positions for
both drive up / drive down and ‚‘gravity fail-safe‘‘
operation, as well as for the re-opening of the
curtain after it has been lowered.
The control panel is designed to meet the
requirements of the pr12101-9 product standard.
It has a local power supply system to maintain
all control functions over a period of at least 72
hours, meeting the requirements of EN 1210110.The control panel meets all the requirements
of CE marking under the Construction Products
Regulation.
Its features and benefits are described overleaf.
360°
360°
PRODUCT DATA SHEET | SKC-SC CONTROL
360°
PRODUCT DATA SHEET | SKC-SC CONTROL
Curtain
up
rest position
Can control up to four groups of curtains, if
necessary each with different functions.
ASB types 2 and 4
Without fail-safe
function
ASB types 1 and 3
With fail-safe function
The history relating to the system status
and fault events is stored within the
internal memory.
way t1
S
AM
Signalling
module
Connection
module
Stop
t4
hold t4
SKC-SC
CONTROLS
FFL
BM
curtain dropped
t2
Curtain
up
rest position
rest position
HWD
hold t2
ZM
W
Auxiliary module
for added
functions
FFL
Curtain
down
curtain dropped
Supply module
with backup
rest position
hold
Floor
FFL level
EV
your safety
Heart module
with processor
and USB
HWD-2
HWD-2
sketch (half
2
HWD
way down) program
sketch 1
Modular design for
HWD-1
HWD-1
Stop
holdt2
t2
t3 travel
way
t3
HWD
Re-transmission
module
hold t4
curtain dropped
sketch 1
HWD-1
Stop
hold t2
t2
HWD-2.0m
HWD +2,0 m
FFL
HWD-2
curtain dropped
t1
travel
way
t1
Designed and tested in accordance with
prEN 12101-9, EN 12101-10 and BS 8524.
Certification being prepared.
t2
way t1
Developed for automatic smoke and fire
curtains
Operation with ASB types 1 to 4
It provides the following functions:
• Maintains the curtains in the raised
position in the event of a temporary
interruption to the power supply
assuming the optional uninterruptible
power supply (UPS) has been supplied
and connected.
• Automatically lowers the curtain in
case of alarm.
• Intermediate stop for curtains before
they descend completely to the floor
(HWD-1 + 2).
• Emergency opening button to enable
personnel leaving an area to be able
to open the curtain once it has been
lowered.
• Fire-fighter’s override button.
• Safety bottom bar to stop the curtain if
there is an obstruction.
• Beam detector to monitor the opening
for obstructions.
• Combination multi-tone siren and
strobe light with the option of a voice
warning system.
• Manual operation
• Status reports to building management.
The system is modular and can be
configured on a PC via a USB interface
to provide the required functionality for
a project.
hold
way t3
Processor controls:
A wide range of modes
Modular design
USB interface
Configuration via a PC
72 hours local power supply
Monitoring of cables
Intermediate drop position option
way t1
SOME FEATURES OF THE SKC-SC CONTROL SYSTEM
t1
travel
way
t1
rest position
SKC-SC controls fire curtains and smoke
curtains. It has been tested in accordance
with prEN 12101-9 and BS 8524. It
has a power supply to maintain the
control functions for at least 72 hours in
accordance with EN 12101-10.
Floor
FFL level
Curtain
down
curtain dropped
Emergency
opening program
sketch 3
sketch 2
KL monitoring
LS monitoring
WN Function
WF Function
Manual release
Auto release
S Signals
S Signals
Safety bottom bar
Obstruction warning
system
Emergency opening
by people escaping
Emergency opening
by fire-fighters
Break glass push
button
Smoke or heat
detector
Multi-tone siren /
strobe light
Multi-tone siren /
strobe light / voice
warning system
Attached to the
bottom bar
Installed in the wall
opening
Button adjacent to
curtain
Key switch with
profile half-cylinder
Button adjacent to
curtain
In front of or behind
the curtain
Installed in the
immediate vicinity of
the curtain
Installed in the
immediate vicinity of
the curtain
The panel has a switch for service and
maintenance purposes.
Parameters entered by use of the ''SmokiControl'' program
“People feel better in Colt conditions.” | Version 08-2016
© Colt International Licensing Limited 2016
www.coltgroup.com