DATA SHEET | CURTAIN CONTROLS SKC-SC SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured on a PC via a USB interface to provide the required functionality for a project. Activation is via a fire alarm system or its own smoke alarm and manual control points.When the alarm is raised, the system provides status messages and optical or acoustic signalling. It monitors cables for wirebreak and short circuit. The control panel is designed for the safe operation of automatic smoke and fire curtains. It contains programs for intermediate positions for both drive up / drive down and ‚‘gravity fail-safe‘‘ operation, as well as for the re-opening of the curtain after it has been lowered. The control panel is designed to meet the requirements of the pr12101-9 product standard. It has a local power supply system to maintain all control functions over a period of at least 72 hours, meeting the requirements of EN 1210110.The control panel meets all the requirements of CE marking under the Construction Products Regulation. Its features and benefits are described overleaf. 360° 360° PRODUCT DATA SHEET | SKC-SC CONTROL 360° PRODUCT DATA SHEET | SKC-SC CONTROL Curtain up rest position Can control up to four groups of curtains, if necessary each with different functions. ASB types 2 and 4 Without fail-safe function ASB types 1 and 3 With fail-safe function The history relating to the system status and fault events is stored within the internal memory. way t1 S AM Signalling module Connection module Stop t4 hold t4 SKC-SC CONTROLS FFL BM curtain dropped t2 Curtain up rest position rest position HWD hold t2 ZM W Auxiliary module for added functions FFL Curtain down curtain dropped Supply module with backup rest position hold Floor FFL level EV your safety Heart module with processor and USB HWD-2 HWD-2 sketch (half 2 HWD way down) program sketch 1 Modular design for HWD-1 HWD-1 Stop holdt2 t2 t3 travel way t3 HWD Re-transmission module hold t4 curtain dropped sketch 1 HWD-1 Stop hold t2 t2 HWD-2.0m HWD +2,0 m FFL HWD-2 curtain dropped t1 travel way t1 Designed and tested in accordance with prEN 12101-9, EN 12101-10 and BS 8524. Certification being prepared. t2 way t1 Developed for automatic smoke and fire curtains Operation with ASB types 1 to 4 It provides the following functions: • Maintains the curtains in the raised position in the event of a temporary interruption to the power supply assuming the optional uninterruptible power supply (UPS) has been supplied and connected. • Automatically lowers the curtain in case of alarm. • Intermediate stop for curtains before they descend completely to the floor (HWD-1 + 2). • Emergency opening button to enable personnel leaving an area to be able to open the curtain once it has been lowered. • Fire-fighter’s override button. • Safety bottom bar to stop the curtain if there is an obstruction. • Beam detector to monitor the opening for obstructions. • Combination multi-tone siren and strobe light with the option of a voice warning system. • Manual operation • Status reports to building management. The system is modular and can be configured on a PC via a USB interface to provide the required functionality for a project. hold way t3 Processor controls: A wide range of modes Modular design USB interface Configuration via a PC 72 hours local power supply Monitoring of cables Intermediate drop position option way t1 SOME FEATURES OF THE SKC-SC CONTROL SYSTEM t1 travel way t1 rest position SKC-SC controls fire curtains and smoke curtains. It has been tested in accordance with prEN 12101-9 and BS 8524. It has a power supply to maintain the control functions for at least 72 hours in accordance with EN 12101-10. Floor FFL level Curtain down curtain dropped Emergency opening program sketch 3 sketch 2 KL monitoring LS monitoring WN Function WF Function Manual release Auto release S Signals S Signals Safety bottom bar Obstruction warning system Emergency opening by people escaping Emergency opening by fire-fighters Break glass push button Smoke or heat detector Multi-tone siren / strobe light Multi-tone siren / strobe light / voice warning system Attached to the bottom bar Installed in the wall opening Button adjacent to curtain Key switch with profile half-cylinder Button adjacent to curtain In front of or behind the curtain Installed in the immediate vicinity of the curtain Installed in the immediate vicinity of the curtain The panel has a switch for service and maintenance purposes. Parameters entered by use of the ''SmokiControl'' program “People feel better in Colt conditions.” | Version 08-2016 © Colt International Licensing Limited 2016 www.coltgroup.com