PARALLELLING MEDIUM VOLTAGE VACUUM BREAKERS – A HIGHER CONTINUOUS CURRENT SOLUTION James Benke Chand Tailor Eaton Corporation Eaton Corporation June 2006 ABSTRACT For systems that require continuous current ratings higher than the standard ANSI ratings, three possible solutions are available for consideration. (1) Cooling fans can be added to circuit breaker cell to allow increased current through the breaker (2) Two or more standard circuit breakers can be connected in parallel in an appropriate switchgear assembly (3) Two or more circuit breakers can be connected in parallel inside an appropriate fan-cooled switchgear assembly. These methods of forcedair cooling with additional fans or paralleling circuit breakers are not new in the industry. Today’s smaller, lighter circuit breakers and modern design practices, however, have refined the art of building switchgear assemblies to make it easier and more economical to connect circuit breakers in parallel. Regardless of which circuit breaker method is selected to meet the required continuous current requirement, special attention must be given to a number of switchgear assembly design areas. INTRODUCTION The focus of this paper will be on the technique of achieving higher continuous current ratings by connecting medium voltage vacuum circuit breakers in parallel. Depending upon the continuous current level desired, it may or may not be necessary to utilize additional fan cooling. For example, two standard 3000 A circuit breakers applied in a properly designed parallel connection can meet a 5000 A continuous current requirement without additional fan cooling. The same configuration can be provided with fan-cooling to enable it to carry continuous currents up to 6300 A. Some common parallel switchgear connection schemes include: a) Two 3000 A circuit breakers rated 5000 A, without fan cooling b) Two 3000 A circuit breakers rated 6300 A, with fan cooling. c) Three 3000 A circuit breakers rated 6300 A, without fan cooling d) Two 4000 A circuit breakers rated 6300 A, without fan cooling e) Two 4000 A circuit breakers rated 8000 A, with fan cooling f) Three 4000 A circuit breakers rated 8000 A, without fan cooling NOTICE: Each manufacturer must test his design to prove the performance meets the rating assigned. Customers have discovered that parallel connection schemes can be viable solutions to higher continuous current requirements. Although this subject can be complicated from a design and testing standpoint, this paper addresses many of the basic factors to consider when looking for solutions for applications which require continuous current carrying capabilities which are higher than the preferred ratings specified in C37.06-2000. Standards do, allow for just such solutions when designs are proven through appropriate testing in accordance with applicable standards. IA01301004E COOLING FANS ADDED TO CIRCUIT BREAEKR COMPARTMENT Let’s first consider a standard 3000 A vacuum circuit breaker. With cooling fans this circuit breaker can easily carry 4000 A without overheating (Figure 1). The standard 36-inch [914.4 mm] wide switchgear assembly units accommodate the necessary airflow requirements to enable the equipment to carry the 4000 A current without exceeding the temperature limits specified in the standards. All necessary control equipment is included to start the fans when the temperature or current indicate the fans are needed, and to operate them until the temperature or current indicate the fans are not needed. Alarm circuitry is provided to give warning if the flow of cooling air becomes insufficient or is lost entirely. If required by the customer, a redundant fan system can also be provided. Figure 1 – Typical Switchgear Assembly Unit With 3000A VCP-W Circuit Breaker Fan Cooled to Allow 4000A Continuous PARALLELING CIRCUIT BREAKERS A second method for providing higher continuous ratings is to connect circuit breakers in a parallel switchgear arrangement. This approach may or may not also utilize a fancooled configuration as just discussed. It depends upon the desired continuous current rating. When circuit breakers are connected in parallel, it is important that circuit breakers with identical ratings be used in the paralleling scheme. It should be recognized that the interrupting rating of the individual circuit breaker used in the scheme is neither increased nor decreased. Therefore, interrupting rating of the circuit breaker(s) should be selected based on maximum fault current that it will be required to interrupt. With identical breakers, precise timing during the closing or opening operations is not critical. The circuit breaker that closes first must be able to carry either fault current or the continuous current for the short period of time until the other circuit breaker closes. Similarly, the last circuit breaker to open is capable of interrupting the full fault current. It is important that the closing circuit be set up to ensure automatic closing of the second breaker within a minute following the closing of the first breaker unless the first circuit breaker has closed onto a fault, of course, in this situation, the second CB shall not close. An incomplete sequence control circuit must also be included in the design that would open the first breaker if the second breaker did not close within pre-set time limit, to prevent overheating of the first breaker from carrying increased circuit current. Additional electrical interlocks should be provided to ensure that both circuit breakers are racked-in and fully connected in the normal operating position within their respective compartments before either circuit breaker can be closed. Further, provision should be made to ensure that if one circuit breaker opens for any reason, the second breaker is automatically opened within a few seconds. Addition of visual or audible alarms should also be considered to indicate when either circuit breaker is withdrawn from its normal operating position. Adherence to this philosophy of circuit breaker selection and control reduces safety and reliability concerns. A parallel approach does IA01301004E require that steps be taken to balance the primary current flowing through each circuit breaker. Over-current protection should be provided for individual circuit breakers as well as for the current in the entire circuit. Main bus construction must also be configured to ensure balanced impedances in each phase of the circuit. Current transformers connected in series may be required to maintain balanced the primary current through each parallel circuit. Finally, the design must be verified by continuous current thermal tests. An example of such proven design with all of the above consideration is given in Figure 2 interrupted the current. Typical overall interrupting times can be in range of 69 to 117 milliseconds when using parallel breakers. The increase in the overall interrupting time should be taken into consideration when devising a specific relaying and protection scheme. CONCLUSIONS Regardless of which solution is chosen for increasing the continuous current rating, special attention must be given to: (1) selection of circuit breakers with required interrupting capability (2) design of electrical controls and protection scheme (3) design of switchgear assembly, including safety interlocks and primary circuit arrangement and layout for proper impedance balance (4) documented testing, and (5) economics. Connecting circuit breakers in parallel is not a new concept and has become an acceptable practice for some customers. When a circuit breaker with the preferred continuous current ratings does not meet the continuous current requirement for an intended application, solutions may be available in the form of fan cooling, paralleling or an appropriate combination these methods. AUTHORS Figure 2 – Switchgear Assembly Rated to Carry 5000 A Continuous Current, by Connecting two 3000 A Circuit Breakers in Parallel ADDITIONAL CONSIERATIONS In the parallel circuit configuration, opening the first circuit breaker commutates the current into the second circuit breaker. Then the second circuit breaker opens to interrupt the current. Therefore, it should be noted that the overall interrupting time from initiation of trip signal to first breaker until the second breaker interrupts the current is longer than if a single breaker James J. Benke is an Engineering Manager at the Eaton Technical Center in Pittsburgh, PA. Jim has more than 12 years of experience in the design, analysis and testing of medium-voltage circuit breakers. He has a Mechanical Engineering degree from University of Pittsburgh and an MBA from the University of Phoenix. Chand Tailor is a Product Applications Specialist at the Eaton Medium Voltage Assembly plant in Greenwood, SC. Chand has more than 24 years of experience in customer order engineering, marketing, and applications IA01301004E of medium voltage switchgear. He has a Bachelor of Engineering degree in Electrical from M S University, Baroda, India, and a Masters of Science in Electrical Engineering from University of Pittsburgh, PA. He is also a registered Professional Engineer in State of South Carolina. IA01301004E