Morten Lerche, s031889 Circuit Breaker Characteristics in Medium Voltage Equipment under Various Network Configurations MSc project, June 2009 Morten Lerche, s031889 Circuit Breaker Characteristics in Medium Voltage Equipment under Various Network Configurations MSc project, June 2009 Circuit Breaker Characteristics in Medium Voltage Equipment under Various Network Configurations, This report was prepared by Morten Lerche, s031889 Supervisor Lektor Joachim Holbøll Technical University of Denmark Department of Electrical Engineering Centre for Electric Technology (CET) Elektrovej 325 building 325 DK-2800 Kgs. Lyngby Denmark www.elektro.dtu.dk/cet Tel: (+45) 45 25 35 00 Fax: (+45) 45 88 61 11 E-mail: cet@elektro.dtu.dk Release date: Category: 30. June 2009 1 (public) Edition: First Comments: This report is part of the requirements to achieve the Master of Science in Engineering (MSc) at the Technical University of Denmark. This report represents 35 ECTS points. Rights: c Morten Lerche, 2009 Preface This Master’s thesis was prepared at the Technical University of Denmark (DTU). The work is conducted at the Department of Electrical Engineering, Centre for Electric Technology at DTU. The work done in this project continues the work performed by Örn I. Björgvinssonin in his MSs project in 2006. My supervisor has been lector Joachim Holbøll from Department of Electrical Engineering, which I would like to thank for guidance, support and inspiration throughout my project. A thanks should also be directed to engineer assistant Freddie Fahnøe and operation techinan Flemming Juul Petersen from Department of Electrical Engineering who have both contributed with great help during the laboratory tests. I would also like thank my fellow studens and specially PhD student Iván Arana, for theoretical discussions during the project. Kgs. Lyngby 2009-06-30 ——————————————– Morten Lerche, s031889 mortenler@gmail.com Summary This Master’s thesis presents an investigation of the transient overvoltages generated by a vacuum circuit breaker. A theoretical model of vacuum circuit breakers is investigated and the parameters used to describe the vacuum circuit breaker in a simulation model is described. A series of laboratory test were made in order to examine the transients created by the breaker and to calculate the parameters which are used to describe the vacuum circuit breaker in the simulation model. The laboratory setup consists of a transformer, a cable, a vacuum circuit breaker and a capacitive load. During the tests the cable lenght was varied to study how network changes effects the transient overvoltages. The load was varied in order to determine some parameters for the simulation model. The tests shows that the transient recovery voltage created by a switching operation is highly dependent on the system configuration. Further more it is shown how the transient recovery voltage and the breaking angle effects the number reignitions of the vacuum arc. A simulation model of the laboratory setup is designed and used to test the vacuum breaker model and the parameters found. The simulations shows the slower transients and the prestrikes, but the lack of detail in the simulation model makes the results less precise than desired. Dansk Resumé Dette kandidatspeciale præsenterer en undersøgelse af de transiente overspændinger som genereres af vakuumbrydere. En teoretisk model af vakuumbryderen bliver undersøgt og de parametre som bruges til at beskrive vakuumbryderen i en simuleringsmodel beskrives. En serie af laboratorietest blev udført for at kunne undersøge de transienter som bryderen danner og udregne de parametre som bruges til at beskrive bryderen i simuleringsmodellen. Laboratorieopstillingen består af en transformer, et kabel, en vakuumbryder og en kapacitiv belastning. Under forsøgene blev længden af kablet varieret for at undersøge hvordan ændringer i netværket påvirker de transiente overspændinger. Belastningen blev varieret for at kunne bestemme nogle af de parametre til simuleringsmodellen. Forsøgene viser at ”the transient recovery voltage” som dannes ved en skifte operation er afhænging af netwærks konfigurationen. Derudover vises det hvordan ”the transient recovery voltage” og brydevinklen påvirker antallet af gentændinger af vakuum lysbuen. En simuleringsmodel af laboratorieopstillingen bliver designet og denne model bruges til at teste vakuumbryder modellen samt de fundne parametre. Simuleringerne viser de langsomme transienter og antændinger af vakuum lysbuen under en lukke operation, men på grund af manglende detaljeringsgrad i simuleringsmodellen bliver resultaterne ikke så præsise som ønsket. List of Acronyms Acronym VCB TRV RRDS RDDS HF AC DC Meaning Vacuum Circuit Breaker Transient Recovery Voltage Rate of Recovery of Dielectric Strength Rate of Decay of Dielectric Strength High Frequency Alternating Current Direct Current List of Symbols Symbol R L C G I V Vm t φ ω θ τ fT RV fT RV 10 Unit Ω H F S A V V t rad rad/s rad s Hz Hz fT RV 100 Hz Ich |i| α β U A B A A s – V V /µs V t0 Cc Dd topen s s tclose s A µs2 A µs Meaning Resistance Inductance Capacitance Conductance Current Voltage Voltage amplitude time Phase angle Angular frequency Phase angle at breaker closing time Time constant Frequency of transient recovery voltage Frequency of transient recovery voltage in the system using the 10m cable Frequency of transient recovery voltage in the system using the 100m cable The chopping current level Amplitude of current Contact material constant Contact material constant Dielectric withstand Rate of rise of dielectric strength Breaker transient recovery voltage just before current zero Time of contact seperation Breaker constant Breaker constant Time of a opening operation of the VCB Time of a closing operation of the VCB Symbol Rclosed Unit Ω Ropen Ω VLoad V VT rans V Vopen V Vvacuum fopen V /mm Hz fopen10 Hz fopen100 Hz Z ex Ω – Vm Sm V VA Meaning Resistance over VCB contacts in closed position Resistance over VCB contacts in open position Voltage measured on the load side of the VCB Voltage measured on the transformer side of the VCB Dielectric withstand of the VCB in open position Dielectric withstand of vacuum Frequency of the oscillating transient caused by a VCB opening Frequency of the oscillating transient caused by a VCB opening when 10m cable is used Frequency of the oscillating transient caused by a VCB opening when 100m cable is used Impeadance of the HTT transformer Short circuit impeadance of the transformer Rated voltage level of transformer Rated load of transformer Contents Preface vii Summary ix Dansk Resumé xi List of Acronyms xiii List of Symbols xv 1 Introduction 1 1.1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Methods and restrictions . . . . . . . . . . . . . . . . . . . . . 3 1.3 Outline of Report . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 Switching Transients 5 2.1 Closing Circuit Transient . . . . . . . . . . . . . . . . . . . . 5 2.2 Opening Circuit Transient . . . . . . . . . . . . . . . . . . . . 9 3 Vacuum Circuit Breakers 13 3.1 Construction of Vacuum Circuit Breakers . . . . . . . . . . . 14 3.2 Modelling of Vacuum Circuit Breakers . . . . . . . . . . . . . 16 4 Laboratory Setup 25 4.1 The Existing Setup . . . . . . . . . . . . . . . . . . . . . . . . 25 4.2 Improvements to the Existing Setup . . . . . . . . . . . . . . 30 xviii 5 Laboratory Tests and Results 5.1 Preparatory tests . . . . . . . . . . . . 5.2 Transient Recovery Voltage . . . . . . 5.3 Chopping Current . . . . . . . . . . . 5.4 Reignitions . . . . . . . . . . . . . . . 5.5 High Frequency Quenching Capability 5.6 Closing the circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 36 37 41 43 47 51 6 Simulations 57 6.1 Opening the Vacuum Circuit Breaker . . . . . . . . . . . . . . 58 6.2 Closing the Vacuum Circuit Breaker . . . . . . . . . . . . . . 64 7 Discussion 7.1 Voltage Circuit Breaker Model Parameters . 7.2 Opening the Vacuum Circuit Breaker . . . . 7.3 Closing the Vacuum Circuit Breaker . . . . 7.4 Further Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 67 68 70 72 8 Conclusion 75 References 77 Appendix 79 List of Figures 79 List of Tables 82 A Plotting results 85 B Results of the TRV Calculations 89 C Results of Current Chopping Calculations 91 D Results of the Rate of Rise of Dielectric Strength Calculations 93 E Results of HF Current Quenching Capability Calculations 97 F Results of Rate of Decay of Dielectric Srength 99 Chapter 1 Introduction In the last part of the 19th century the demand of electric power started increasing rapidly because of new technical inventions. The increased use of electrical lighting, the introduction of the DC-motor and railway systems were just some of the inventions that called for a power system. In 1882 Tomas Edison opened the worlds first power station in New York City, this is referred to as the beginning of the electric utility industry. From this starting point and until 1872 the electric utility industry grew at a remarkable pace [3]. In 1885 William Stanley developed the first commercial and practical transformer and overcame the limitation of maximum distance and load in the exciting network. The year after the first AC distribution system was installed in Massachusetts. Nikola Tesla presented the first ideas of a polyphase AC system in 1888 introducing induction and synchronous motors, and the first transmission of tree-phase alternating current took place during the international electricity exhibition in Frankfurt in 1891, transmitting power at 12kV over 175km [3]. The industrialization during the 20th century made the electrical infrastructure a critical point. Interconnection of local distribution networks and the construction of large power plants were some of the main demands created by the industrialization. These demands have led us to the power networks we have today, which are designed to transport energy as efficient and reliably, from the producer to the consumer, as possible. To deal with the challenges of this task many network components have been developed and some of the main components of today’s power networks are overhead lines, cables, transformers, circuit breakers and switches. For many years lightning were the only phenomenon that could create steep front pulses in the power system and thereby produce high overvoltages [1]. When lightning strokes terminates on or near a power line they create a 2 path between the cloud and the power line or the adjacent earth and hereby changes the circuit conditions and creates a transient overvoltage. In order to protect the insulation of the equipment against the lightning overvoltages surge arresters were used, they kept the voltage on a level that was not harmful for the protected equipment. The research in this area was stopped until an increased number of failures were detected on the insulation of the equipment, even at low voltage levels. It was discovered that these failures were caused by some of the equipment that had been implemented in the power network. One of the components that led to failure of insulation was the breakers used in the electrical grid. Many types of breakers have been used in the power grid during the years. In the beginning of the 20th century oil circuit breakers were mainly used. In 1959, SF6 circuit breakers came to the marked, this type of circuit breaker had several advantages such as long life time and high reliability [15]. The first vacuum circuit breaker (VCB) was constructed in the 1960s. VCBs have low maintenance costs, good durability and provide the best breaker solution for medium voltage below 24kV [1]. But the use of VCBs resulted in worldwide reports on transformer insulation failures possibly due to switching operations of VCBs, also transformers that had previously passed all the standard tests and complied to all quality requirements suffered failures [2]. It has still not been finally proved that the high frequency transients have a negative influence on the transformer insulation. Some studies give a description of the phenomenon that produces the high overvoltages internally in the transformer winding, which are potentially responsible for the transformer insulation failure during the high frequency transients [10]. A problem of the transformer insulation failure also occured in the wind parks (WP) Middelgrunden and later at Hornsrev where almost all transformers had to be replaced with new ones due to the insulation failure [14]. This problem is suspected to be caused by fast switching breakers as e.g. VCBs. VCBs are the most used breaker type in the medium voltage area, due to its excellent breaking abilities and economic advantages. But as mentioned the VCB also seems to cause some faults in the power network. The physical phenomena in the VCB during a switching operation are very complex, and therefore the models of VCBs are also very complex. When performing a switching operation a conducting plasma channel is created between the breaker contacts, this channel is called the vacuum arc. When the arc is extinguished a transient recovery voltage appears across the terminals and this voltage can give rise to another breakdown in the vacuum and create a new conducting plasma channel between the breaker contacts. The arc formed by the plasma can become unstable and create high frequency currents, which the breaker must be able to interrupt. The advanced and unstable nature of the conducting plasma channels does that there is no universal precise vac- Introduction 3 uum arc model. The models that exist all take into account the stochastic properties of the phenomena that take place in the breaking process [7]. 1.1 Purpose The purpose of this thesis is to test a VCB and to observe the physical phenomena that occur in the VCB during the interruption process, especially the phenomena that cause high frequency transients. Based on laboratory tests the parameters, that are used to model the VCB, will be determined. In order to study the laboratory setup it is desirable to make a precise simulation model of the setup, this simulation model can be used to test the behaviour of the VCB model and compare it with the tests made on the VCB. 1.2 Methods and restrictions The VCB model that is used in this project takes into account the following stochastic properties of the VCB: • Current chopping ability. • Recovery of dielectric strength. • High frequency current quenching. In the test setup, used in order to determine these properties of the VCB, only one phase of the VCB is connected and measurements are performed on this phase. In order to supply the VCB with high voltages a transformer is used, the measurements are performed on the high voltage side on the transformer. In order to change the network configurations, two similar cables with different length are used to connect the VCB and the transformer. Two capacitive loads are used to load the system, these loads are both 0.5µF and the maximum load in the system is therefore 1.0µF . This means that the current running through the VCB during the tests will be rather limited. When analysing the results of the VCB tests, the main focus will be on determining the parameters for the VCB model. As these parameters are mainly determined by the opening process of the VCB most analysis will be on VCB open operations. As the parameters are mainly described by the very fast transients created by the VCB the main work will be put in this area. The simulations are performed in PSCAD, a model of the laboratory setup 4 1.3 Outline of Report is created using lumped circuit elements for the transformer and the cable. This will make the results of the simulations less accurate, but lumped circuit elements are used to be able to finish the simulations within the time limitations of the project. 1.3 Outline of Report The structure of the thesis is as follows: • Chapter 2 : Switching Transients This chapter will introduce two examples of switching transients ocurring due to an opening and a closing action of an ideal switch. For one example the full result of the transient current, caused by opening the switch, will be calculated, where the other example will explain the areas of interest. • Chapter 3 : Vacuum Circuit Breakers In this chapter the design principles of VCBs are described and the theory behind the vacuum arc will be explained. A model of the VCB will be introduced and the different parameters of the model will be explained according to the physical phenomena occurring in the VCB. • Chapter 4 : Laboratory Setup A description of the laboratory setup and its components is given in this chapter. The improvements and adjustment made on the setup are also described. • Chapter 5 : Laboratory Tests and Results This chapter concerns with the performed tests and the treatment of the test results. In this chapter the parameters of the VCB model will be calculated and the accuracy of the results will be discussed. Methods for achieving more accurate results will be discussed. • Chapter 6 : Simulations In this chapter the simulation model will be described. The results from the PSCAD simulation of an opening and a closing operation of the VCB is analysed. • Chapter 7 : Discussion In this chapter a discussion of the achieved results will be made, the discussion will mainly focus on comparing the simulation results with the measured results. A description of the further work that is needed in order to make a fully working model of the VCB will also be given. • Chapter 8 : Conclusion This section gives the conclusion. Chapter 2 Switching Transients An electrical transient is caused by a sudden change in the circuit conditions [4]. This change could be when a lightning hits the ground near a high voltage line or when lightning strikes a substation directly. But the most common transients in the power systems occur as a result of a switching action. This could be when circuit breakers, fuses, disconnectors etc, open and close in order to switch off parts of the network, interrupt higher currents and clear faults in the network and hereby secure the network. These switching actions give rise to switching transients. The transient time is usually very short, in the range of microseconds to milliseconds, but the transients periods are very important as it is in this period the network components are subject to the greatest stress. The transients may shorten the lifetime of the components in the network or in worst case cause a breakdown of the power system. In this chapter, two switching examples will be examined, both examples will use an ideal swich to represent a network switch as e.g. a VCB. An ideal switch acts as a disconnection when open and as a short circuit when closed and it switches between the two stages instantly. Using an ideal switch gives a good idea of what happens when a VCB is opened or closed even though it does not have the same characteristic. An ideal switch does not have the influence of reignitions and high frequency currents, which excist in a VCB due to arc instability. 2.1 Closing Circuit Transient In this example a sinusoidal voltage is switched on to a series connection of an inductance and a resistance. Figure 2.1 represent the simplest case of a high-voltage circuit breaker closing into a short-circuited transmission line or a short-circuited underground cable. The voltage source V represents the electromotive force from the connected generators [15]. The inductance L represents the synchronous inductance from the generators, the leakage 6 2.1 Closing Circuit Transient R S L Vmsin(ωt+θ) Figure 2.1: An sinusoidal voltage is switched on an RL-circuit. inductance in the transformers and the inductance of bus bar, cables and transmissions lines. The resistance R represents the resistive losses of the network. Since the network consist of linear elements only, the current flowing in the network after closing the switch can be seen as the superposition of a transient current and a steady-state current. Applying Kirchhoff’s voltage law on the circuit in figure 2.1 gives us the nonhomogeneous differential equation that represents the circuit after the switch has been closed [15] R·I +L· dI = V, dt (2.1) where V represents the sinusoidal voltage of the source and I is the current in the circuit. V = Vm · sin(ωt + θ) ⇔ V = Vm · [sin(ωt)cos(θ) + cos(ωt)sin(θ)] (2.2) The angle θ is the phase angle at which the switch is closed. The term sin(ωt+θ) has been rewritten in order to make the solution of the differential equation easier. The steady state power factor of the load in figure 2.1 is given by cos(φ) = R R =p . 2 |L| (R + ω 2 · L2 ) (2.3) The differential equation is solved by the Laplace method. Inserting equation (2.2) in (2.1) gives R·I +L· dI = Vm · (sin(ωt)cos(θ) + cos(ωt)sin(θ)), dt (2.4) Laplace transforming both sides yields R · i(s) + L · s · i(s) − L · I(0) = Vm ω · cos(θ) s · sin(θ) + 2 s2 + ω 2 s + ω2 . (2.5) Switching Transients 7 Setting I(0) = 0 in figure 2.1 makes it possible to find an expression for the current ω · cos(θ) s · sin(θ) ⇔ R · i(s) + L · s · i(s) = Vm + 2 s2 + ω 2 s + ω2 ω · cos(θ) s · sin(θ) Vm ⇔ + 2 i(s) = L·s+R s2 + ω 2 s + ω2 Vm 1 ω · cos(θ) s · sin(θ) i(s) = + 2 . (2.6) · L s+ R s2 + ω 2 s + ω2 L In order to transform back into the time domain the equation is rewritten to the following form i(s) = A B·s + , 2 2 (s + α)(s + ω ) (s + α)(s2 + ω 2 ) (2.7) where the constants A= Vm · ω · cos(θ), L B= Vm · sin(θ), L α= R . L (2.8) Equation (2.7) can be transformed back into the time domain when the following two inverse Laplace transforms are known L −1 A A = 2 · [e−α·t 2 2 (s + α)(s + ω ) (s + ω 2 ) − cos(ω · t) + L −1 α sin(ω · t)] ω B·s B = 2 · [−α · e−α·t 2 2 (s + α)(s + ω ) (s + ω 2 ) + ω · sin(ω · t) + αcos(ω · t)] (2.9) (2.10) Using equation (2.9) and (2.10), equation (2.7) can be transformed into the time domain A B·s −1 + i(t) =L (s + α)(s2 + ω 2 ) (s + α)(s2 + ω 2 ) = (s2 A α · [e−α·t − cos(ω · t) + sin(ω · t)] 2 +ω ) ω B + 2 · [−α · e−α·t + ω · sin(ω · t) + αcos(ω · t)]. (s + ω 2 ) (2.11) 8 2.1 Closing Circuit Transient Closing a RL−circuit at 90 degrees 0.8 Resultant current I(t) Steady−state current Transient current 0.6 0.4 Current[I] 0.2 0 −0.2 −0.4 −0.6 −0.8 −1 −1.2 0 20 40 60 80 100 Time[ms] Figure 2.2: The sinusoidal voltage is switched on to the RL-circuit with a switching angle of 90◦ . Incerting A and B from (2.8) into equation (2.11) yields i(t) = Vm · ω · cos(θ) α · [e−α·t − cos(ω · t) + sin(ω · t)] L · (s2 + ω 2 ) ω Vm · sin(θ) · [−α · e−α·t + ω · sin(ω · t) + αcos(ω · t)]. (2.12) + L · (s2 + ω 2 ) Equation (2.12) can be simplified by using the power factor described in (2.3) and inserting α from (2.8), the following expression for the current can be found [4] R Vm i(t) = √ [sin(ω · t + θ − φ) − sin(ω − φ)e− L ·t ]. R 2 + ω 2 · L2 (2.13) The first term is the steady-state term, it has an amplitude of Vm /|Z| and it has a phase angle of −φ with respect to the voltage. The second term is R the transient term, it includes an exponential function e− L ·t . At t = 0 the steady-state term and the transient term are the same but with different sign, assuring that the current starts in zero when the breaker closes. In figure 2.2 the transient current, the steady-state current and the resultant current is shown for a switching angle of θ − φ = 90◦ . As figure 2.2 shows the transient term starts at its lowest possible value, which is equal to the amplitude of the current. Opening the breaker at θ − φ = 90◦ gives the largest transient, on the other hand opening the θ − φ = 0◦ makes the Switching Transients 9 Closing a RL−circuit at 0 degrees 0.8 Resultant current I(t) Steady−state current Transient current 0.6 Current[I] 0.4 0.2 0 −0.2 −0.4 −0.6 −0.8 0 20 40 60 80 100 Time[ms] Figure 2.3: The sinusoidal voltage is switched on to the RL-circuit with a switching angle of 0◦ . transient term turn zero. This can be seen in figure 2.3. It is seen that the transient term is zero, which causes the resultant current to be equal to the steady state current from the moment of contact separation. 2.2 Opening Circuit Transient When a switch opens in order to switch off parts of the network or clear faults in the network it can cause high overvoltages in the network. This section will investigate what happens when interrupting a capacitive current using an ideal switch. A simple model of the laboratory setup used in this project is seen in figure 2.4, the inductance of the circuit represents a transformer, the capacitance C1 represents a cable and the capacitance C2 is the load of the network. When opening the switch in the system in figure 2.4 the circuit will only consist of the inductance L and the capacitance C1 . After the switch has opened, a HF voltage appears across the switch contacts, this voltage is called the transient recovery voltage (TRV). This transient will have the frequency fT RV = 1 √ . 2 · π L · C1 (2.14) The TRV has no real influence on the switching when using a ideal switch, but it is of high importance of the switching in real switching devices. In real 10 2.2 Opening Circuit Transient S L Vmsin(ωt+θ) C1 C2 Figure 2.4: An sinusoidal voltage is switched on an RL-circuit switching devices the characteristics (amplitude and rate of rise) determines if the current interruption is successful or fails (reignition of the arc between the contacts). As seen in eqation (2.14) the frequency of the TRV depends on the circuit in which the ideal switch or circuit breaker is working. In the example from figure 2.4, the TRV created by the switch when opening the circuit could look like the graph in figure 2.5, this figure shows how the TRV effects the transformer side of the circuit seen in figure 2.4. The TRV can be harmful for network equipment since its high amplitude can exceed the voltage level of the system. As mentioned the circuit in figure 2.4 represents the setup used in this project. In [11] the capacitance of the cable used is found to be 157.57 · 10−12 F/m and the in this project the value of L used to represent the transformer is found to be 0.318H (see chapter 6). In this project a 10m and a 100m cable is used, for the 10m cable the frequency of the TRV is expected to be fT RV 10 = 1 p = 7110Hz, 2 · π 0.318H · 157.57 · 10−12 F/m · 10m (2.15) and for the 100m cable a frequency of fT RV 100 = 1 p = 2248Hz. 2 · π 0.318H · 157.57 · 10−12 F/m · 100m (2.16) These TRVs are the only effect of interrupting current with ideal switches, but as mentioned in the use of real switching devices, such as VCBs, the TRV can cause reignitions of the conducting arc between the switching contacts. These reignitions can lead to high overvoltages and HF currents in the system. In order to describe the phenomena of reignitions in VCBs a more detailed study of the design and principles of the VCB must be made. This investigation is done in the following chapter. Switching Transients 11 Simulation of VCB opening Trans. side voltage[kV] 10 5 0 −5 −10 −15 50 55 60 65 70 75 80 Time[ms] Figure 2.5: The figure shows the voltage on the transformer side of a VCB under a opening operation in a circuit with a capacitive load. 12 2.2 Opening Circuit Transient Chapter 3 Vacuum Circuit Breakers A circuit breaker is in principle an electrical switch that is designed to protect the power system [9]. Circuit breakers play an important role in transmission and distribution networks. They must clear faults and isolate faulted network sections fast and clearly and they are also used for normal load switching [7]. For a circuit breaker to fulfil its purposes the following is required [15]: • It functions as a good conductor in closed position. • It functions as a good insulator in open position. • It is able to switch from open to closed in a short period of time. • It does not cause overvoltages during switching. • It is reliable in its operation. When a circuit breaker interrupts a current, an electric arc is usually formed between the breaker contacts and the current continues to flow in this arc. The current interruption is performed by cooling the arc plasma so that the electric arc disappears. Circuit breakers are classified according to the cooling and extinguishing medium used. There are four main types of circuit breakers namely, oil, air blast, vacuum and SF6 circuit breakers. This thesis concerns with the functions of a vacuum circuit breaker (VCB). Vacuum is used as an extinguishing medium for medium voltage circuit breakers. VCBs have excellent interruption and dielectric recovery characteristics and can interrupt the high frequency currents which results from arc instability [16]. VCBs are primarily designed for switching operations in capacitive circuits [12]. The main advantages of the VCB are: • It has excellent interruption capability. 14 3.1 Construction of Vacuum Circuit Breakers • It can interrupt high frequency currents, created by arc instability. • It is completely self-contained and does not need supply of gasses or liquids. • It does not need maintenance. • It is not flammable. These advantages of the vacuum breaker technique have been the driving force of VCB development [1]. Due to the fact that there is nothing to ionize between the contacts in VCBs, the characteristics of the electric arc in VCBs are different than the electric arc in other types of breakers. VCBs have a very little arc and the arc extinguishes with small distance between the breaker contacts [15]. 3.1 Construction of Vacuum Circuit Breakers A VCB consist, like other circuit breakers, of two contacts, a fixed contact and a moving contact. The moving contact has two positions, one where it is touching the other contact and one where the two contacts are apart. When the contacts are touching the VCB is conducting current and when the contacts are apart the VCB is not conducting current. The two contacts of a VCB are inside a vacuum chamber. When the moving contact starts to move away from the fixed contact, an arc is formed between the two contacts and the VCB does not stop conducting current before this arc is extinguished. In figure 3.1 the basic concept of the VCB design is shown. The moving contact is normally moved by a stored-energy operating mechanism, in most cases a closing and an opening spring [5]. These springs stores the energy to open and close the VCB, when the closing spring gets released the VCB closes. During the closing of the VCB the opening spring is charged so that the VCB is ready to open immediately after the closing operation is over. After the closing operation is over the closing spring recharges automatically. 3.1.1 Vacuum Arc The vacuum arc is a key element when analysing the behaviour of a VCB. The name vacuum arc is not entirely accurate, because an electric arc cannot exist in vacuum [5]. The arc that appears between the contacts of a VCB is a result of metal-vapour, ion- and electron emission. After being established the vacuum arc is relatively stable and will draw energy from the electrical system until the current reaches a zero crossing and thereby removes the energy source. When conducting small currents the vacuum arc can become unstable and extinguish before current zero is reached, this phenomenon is Vacuum Circuit Breakers 15 Figure 3.1: The design principle of a VCB, showing contacts, arching chamber and insulation, the picture is taken from [12] page 8. called current chopping. Depending on the current level and on the size and shape of the contact the vacuum arc appears in different ways [5]. At lower currents small spots on the negative electrode (the cathode) appear. These cathode spots are in constant movement over the cathode surface. Electrons and ions radiates from the spots and contributes with around 50A to 150A depending on the cathode material [15]. The plasma channel formed by the emitted electrons and ions is called a vacuum arc, this arc connects the cathode and the anode (the positive electrode). After leaving the cathode the arc spreads out filling almost the entire volume of the vacuum chamber before hitting the anode. The electrons and ions leave the arc and get collected all over the anode and for this reason the arc is said to be in diffuse mode at lower currents. When the current is increased the arc takes a different form, the arc be- 16 3.2 Modelling of Vacuum Circuit Breakers Figure 3.2: A vacuum interrupter with slits in the contacts to avoid uneven erosion of the contact surface, this picture is from [15] page 66. comes focused on a small area of the anode. These spots are normally formed around a sharp edge on the contact. Due to the high current density in these anode spots the contact material evaporates and when the vapour is ionised it supplies positive ions to the arc. The cathode spots becomes grouped together, giving the arc a much more defined and columnar appearance and the arc is said to be in constrict mode [5]. 3.1.2 Construction of Vacuum Circuit Breaker Contacts The constrict mode leads to erosion of both contacts, in diffuse mode the cathode spots leads to evaporation but in the constrict mode melting occurs at both contacts especially at the anode [5]. To avoid uneven erosion of the surface of the contacts the arc should be kept in motion or kept burning in diffused mode. The most common way of avoiding melting is to make slits in the contacts, as showed in figure 3.2, by doing this the arc is being kept in diffuse mode. The contact in figure 3.2 provides a axial magnetic field and it is this field that keeps the arc in diffuse mode. This means that the stress on the disc shaped contact surfaces is uniform and local melting is avoided [12]. 3.2 Modelling of Vacuum Circuit Breakers In order to study the behaviour of VCBs it is desirable to describe their physical phenomena by a mathematical model that can be used for simulations. In this project a breaker model will be investigated and be applied on the VCB tested in the project. The model used in this project describes Vacuum Circuit Breakers 17 the VCB according to the follow parameters: • The chopping current. • The dielectric withstand. • The high frequency quenching capability. The model is developed and described in [7]. The parameters used, and their effect on the VCB will be described in the following sections. 3.2.1 Current Chopping Current chopping is a phenomena that can lead to overvoltages, it occurs when small capacitive and inductive currents are interrupted [1]. When the vacuum arc is conducting a small current it will become very unstable and normally it will disappear and cause the current to be interrupted before it reaches its natural zero. This premature interruption of the current is called current chopping. The value of the current when the arc extinguishes is called the chopping current level and is referred to as Ich . Figure 3.3 shows current chopping during switching of a VCB. The value of the chopping level depends mainly on the type of contact material used in the breaker but also on the level and form of the current that is interrupted. The prediction of the actual current chopping value, considering all its dependents is very complex. But in [13] an expression of the mean chopping level has been estimated −1 Ich = (2 · π · f · |i| · α · β)(1−β) , (3.1) where • f = Power frequency. • |i| = Amplitude of the load current. • α,β = Contact material constants. Equation (3.1) is used to calculate the current chopping level of the VCB. When simulating the VCB the values of α and β are normally consider to be α = 6.2 · 10−16 s and β = 14.2 [6]. If the current through the breaker is lower than the chopping level, then the current is chopped immediately after contact separation. During current chopping the current declines with a very high di/dt (very steep slope) this produces very high overvoltages due to the inductances in the network. For 18 3.2 Modelling of Vacuum Circuit Breakers Current Chopping −3 5 0.5 0 Current[A] Current[A] Current Chopping 1 0 −0.5 x 10 −5 −10 −1 −15 −1.5 36 38 40 42 44 46 48 50 44.84 44.85 Time[ms] 44.86 44.87 44.88 44.89 44.9 44.91 44.92 Time[ms] (a) The current when the breaker opens (b) Zoomed plot at the point of arc extinguish Figure 3.3: The figure shows the current during an opening of the breaker. As seen on figure b the current chops around the value 0,005 and jumps to zero. this reason current chopping is considered to be a major disadvantage of the VCB. The current chopping level for VCBs usually varies between 3A and 8A [1]. When modelling the chopping current it is usually considered to have a Gaussian distribution with a standard deviation 15% of the mean chopping current, that is calculated using equation (3.1) [7]. 3.2.2 Reignitions A reignition of the vacuum arc is a temporary electrical breakdown of the vacuum in the VCB. The dielectric withstand of the VCB is an important subject in the analysis of the switching transients that occurs due to reignitions in the VCB [1]. When the breaker contacts start to separate the withstand voltage of the gap starts increasing. During the first millimetre of separation the withstand voltage increases linearly and here after it increases proportionally to the square of the distance between the contacts [1]. In the model that is used in this project a linearly relation between the withstand voltage and the time after separation is assumed [7]. This relation is seen in equation (3.2) U = A(t − t0 ) + B, where • t0 = The moment of contact separation. • A = Rate of rise of dielectric strength. (3.2) Vacuum Circuit Breakers 19 Dielectric withstand 80 60 TRV Breaker withstand voltage Voltage[kV] 40 20 0 −20 −40 −60 −80 32 33 34 35 36 37 38 Time[ms] Figure 3.4: The figure shows 5 reignitions of the vacuum arc during contact seperation. When the reignitions occur the TRV jumps to zero. The red line shows the RDDS of the circuit breaker. • B = Breaker transient recovery voltage (TRV) just before current zero. The values of A and B vary from the different VCBs. The constant A describes as mentioned the rate of rise of dielectric strength (RRDS) when the breaker is opening. When the breaker is closing the constant A describes the rate of decay of dielectric strength (RDDS). In [16] the value of the constant A is suggested to be between 2V /µS and 50V /µS when B is set to zero, which is quiet normal when determining the dielectric withstand of the breaker. The value of the dielectric strength determined in equation (3.2) is also following a Gaussian distribution with a standard deviation of 15% of the dielectric mean value [7]. When the contacts separate and the current is interrupted a TRV appears across the breaker contacts, as described in chapter 2. This TRV is determined by the configuration of the network on both sides of the breaker. If the value of the TRV exceeds the dielectric withstand of the gap between the contacts, the arc will be re-established and the breaker will conduct current again. This causes a high frequency (HF) current to be superimposed on the power frequency current. This HF current will be extinguished at current zero and the race between the TRV and the dielectric withstand will begin again. The relation between the reignitions and the dielectric withstand is illustrated in figure 3.4 and in figure 3.5 both the restrikes and the HF current is shown. 20 3.2 Modelling of Vacuum Circuit Breakers Voltage[kV] High frequency quenching capability TRV Breaker withstand voltage 20 0 −20 −40 34.65 34.7 34.75 34.7 34.75 34.8 34.85 34.9 34.95 34.8 34.85 34.9 34.95 Current[A] 0.5 0 −0.5 34.65 Time[ms] Figure 3.5: The figure shows 3 reignitions of the vacuum arc during contact separation. The figure also shows the high frequency currents caused by the arc. The simulation model simulates restrikes by sending a closing signal to the breaker whenever the TRV exceeds the dielectric strength of the gab [7]. This means that the resistance of the arc is expected to be the same as the resistance of the VCB in closed position. 3.2.3 High Frequency Quenching Capability The HF currents that occur after a reignition of the arc are mainly determined by the stray parameters of the VCB. The HF current will be superimposed on the power frequency current and if the HF current has a larger magnitude than the power frequency current it can cause the current to pass zeros. Most VCBs have the ability to quench the HF current at a zero crossing, and thereby extinguish the vacuum arc [7]. The VCB cannot extinguish these HF currents if the di/dt value of the current is too high. Since the magnitude of the currents is damped quite quickly the di/dt of the current is also decreasing. When di/dt is small enough the VCB quenches the HF current at one of its zero crossings. Figure 3.5 shows how a HF current is created when the vacuum arc is established and how the arc is extinguished when di/dt of the HF current becomes small enough. The critical value of di/dt represents the quenching capability of the VCB. A method of determining the quenching capability of a VCB is to model it as a linear function Vacuum Circuit Breakers 21 with respect to time di/dt = Cc (t − t0 ) + Dd , (3.3) where • t0 = The moment of contact separation. • Cc , Dd = Breaker constants. Equation (3.3) gives the mean value of the quenching capability and once again it follows a gaussian distribution where the standard deviation is 15% of the mean value. The suggested values of the constant Cc is between −0.034A/µs2 and 1A/µs2 . Some authors describes the HF quenching capability di/dt to be constant, Cc = 0 and suggested values of Dd to be between 100A/µs and 600A/µs [16]. 3.2.4 Multiple Reignitions and Voltage Escalation When the VCB breaks the HF current that has occurred due to a reignition of the arc, the TRV of the breaker starts rising again. When the TRV reaches the dielectric withstand of the breaker gab the arc will ignite again and course another HF current to be superimposed on the power frequency current. This phenomenon is called multiple reignitions. Figure 3.6 shows the current of the breaker during multiple reignitions of the vacuum arc. The occurrence of multiple reignitions depends mainly on tree parameters. • The arching time of the breaker. • The RRDS and the dielectric withstand of the breaker. • The HF current quenching capability. The two last areas have been discussed in the previous sections, but the arching time has not been introduced yet. The time between contact separation and first arc extinguishing is called the arching time, in other words the arching time is the time between contact separation and the time of current chopping. If the arcing time is short then the dielectric strength of the gap will not have time to reach a high value before the arc is extinguished and the probability of reignitions is higher. In VCB with high RRDS the possibly of restrikes will be smaller since the breaker regains its dielectric withstand faster than breakers with low RRDS. After some reignitions the VCB does not have a high enough HF quenching capability to break the HF current at a zero crossing in the last reignition, this is seen in figure 3.7. Due to this the power frequency takes over and 22 3.2 Modelling of Vacuum Circuit Breakers Unsuccessful current interruption 0.4 0.3 0.2 Current[A] 0.1 0 −0.1 −0.2 −0.3 −0.4 −0.5 −0.6 34.4 34.6 34.8 35 35.2 35.4 Time[ms] Figure 3.6: The figure shows the HF currents caused by 5 reignitions. The last current cannot be quenched at a zero crossing and therefore the arc is maintained until the next zero crossing of the current. Complete breaking operation Voltage[kV] 100 TRV Breaker withstand voltage 50 0 −50 −100 32 34 36 32 34 36 38 40 42 44 46 48 38 40 42 44 46 48 Current[A] 1 0.5 0 −0.5 −1 Time[ms] Figure 3.7: Multible reignitions lead to unsuccessful interruption of the current at first current zero. Vacuum Circuit Breakers 23 interruption is effected at the next current zero (around 45ms) as seen in figure 3.7. As seen in figure 3.7 successful interruption takes place after the contacts are fully apart and the dielectric withstand has reached its final value. The process of multiple restrikes can lead to voltage escalation, where every breakdown of the arc can lead to higher and higher voltage at the load side of the VCB since the TRV is superimposed on the steady state 50 Hz voltage. 3.2.5 Prestrikes Prestrikes are like reignitions a temporary breakdown of the vacuum dielectric. Prestrikes occur during the closing operation of the breaker. Prestrikes normally occur during energizing of capacitive loads and are caused by the same phenomena that cause reignitions during opening operations. When the VCB contacts starts to move towards each other the dielectric strength of the gap starts to decrease. As soon as the dielectric withstand of the VCB becomes smaller than the voltage over the breaker an arc will ignite and current will flow through this arc. This current consists of a HF current and a current at power frequency. The arc will be extinguished at a zero crossing, when di/dt of the HF current becomes lower than the quenching capability of the VCB [1]. The interruption of the HF current causes a TRV to build up over the breaker. When this voltage reaches the dielectric strength of the gab another prestrike will occur and the TRV will go to zero again. Figure 3.8 shows how prestrikes create a HF current and how these currents are quenched, causing the arc to be extinguished. This process continues to produce prestrikes until the dielectric withstand of the VCB is no longer high enough to extinguish the arc. And when the last HF current is damped the VCB only conducts current at the power frequency. The slope of the dielectric strength seen in picture 3.8 is called the rate of decay of dielectric strength (RDDS). RDDS is normally said to have the same value as RRDS. 24 3.2 Modelling of Vacuum Circuit Breakers Prestrikes Voltage[kV] 40 TRV Breaker withstand voltage 20 0 −20 −40 34.55 34.6 34.65 34.7 34.75 34.8 34.6 34.65 34.7 34.75 34.8 Current[A] 0.4 0.2 0 −0.2 −0.4 34.55 Time[ms] Figure 3.8: The figure shows 4 reignitions of the vacuum arc during contact separation. The figure also shows the high frequency currents caused by the arc. Chapter 4 Laboratory Setup In 2006 a laboratory setup for investigation of switching transients in wind turbine systems was made. The setup was completed and modified by Örn I. Björgvinssonin during his master’s project [11]. The modifications made by Örn I. Björgvinssonin made it possible to remotely open and close the VCB and at the same time, measure the voltage over the VCB and the current through the breaker using a LabVIEW interface. In a preparatory project [9] the laboratory setup was investigated and some improvements were implemented on both the measurement system and the control system. A MATLAB program that processes and shows the measured data was also constructed. 4.1 The Existing Setup As mentioned the existing laboratory setup was made to represent a windmill system, in order to examine the switching transients that are created in such a system [11]. In this project the setup will be used only to examine how the VCB behaves, and affects the system. These studies will be used to find the parameters of the VCB that are used in the simulation model. The high voltage components used in the laboratory setup are: • A AXA 3BT − 380/45 vario-transformer. • A HTT 10/0.4kV , 100kV A transformer. • A 100m and a 10m NKT ”1-conductor PEX-CU 17.5kV” cable. • A 12kV Siemens vacuum circuit breaker. • A 0.5µF and a 1.0µF capacitive load. 26 4.1 The Existing Setup Rogowski Current Transducer LabVIEW LeCroy Oscilloscope Ch1 Position Meter Ch2 Ch3 Ch4 Switch unit Voltage Probe HTT Transformer Cable Voltage Probe VCB Load Vario-transformer Net Voltage High Voltage Measurement signal Control Signal Figure 4.1: The laboratory setup including high voltage components and the control and measurement system The 3 phases from the vario-transformer are connected to the low voltage side of the HTT transformer. From the high voltage side of the HTT transformer only one phase is connected to one side of the Siemens VCB via the 100m or 10m NKT cable. The other side of the breaker is loaded with the capacitive load. In figure 4.1 the high voltage setup is shown. Figure 4.1 also shows the control and measurement system. The main element in this system is a LabVIEW program that is used to control the VCB and to measure the voltage, current and the position of the VCB moving contact. The full control and measurement system consist of: • The labVIEW program. • A four channel LeCroy LC334 oscilloscope. • A Hewlett Packard 34970A data acquisition/switch unit. • Two Tektronix P6015A voltages probes. Laboratory Setup 27 • A Rogowski current transducer of type CWT03. • A linear position meter. A more detailed description of the high voltage components and the control and measurement components, will be given in the following two sections. 4.1.1 High Voltage Setup The vario-transformer is a AXA 3BT-380/45 vario transformer with a voltage rating of 3x380V /3x0V − 380V . The transformer has a nominal current of 45A and is rated at 29.6kV A. The vario-transformer is on the primary side connected to the power grid and therefore supplied with 380V . The 3 phases from the secondary side of the vario-transformer is connected to the HTT transformer. The HTT transformer is a 10/0.4kV wire-wound transformer rated at 100kV A and has 1136 windings at the high voltage side. The transformer is star connected on both sides. The transformer is a dry type transformer. On the secondary side of the transformer a cable is connected on one of the three phases while the other two are left open. In the project two identical cables with different length are used in order to create various network characteristic. The cables are ”1-conductor PEX-CU 17.5kV” cables from NKT, the copper conductor has a diameter of 25mm and the insulation used is polyethylene. Some tests have been made on the cables in order to determine its losses [11], the main results of these tests are shown in table 4.1. As seen in table 4.1 the losses in the cable increases – R[Ω/m] L[H/m] C[F/m] G[S/m] 50Hz 727.00 · 10−6 239.79 · 10−9 157.57 · 10−12 14.85 · 10−12 1kHz 727.00 · 10−6 239.79 · 10−9 157.57 · 10−12 297.01 · 10−12 500kHz 738.17 · 10−6 239.79 · 10−9 157.57 · 10−12 148.51 · 10−9 1M Hz 770.11 · 10−6 239.79 · 10−9 157.57 · 10−12 297.01 · 10−9 Table 4.1: Cable parameters calculated at different frequencies [11] when the frequency exceeds 1kHz. The two cables are used to connect the HTT transformer and the VCB. The VCB used in this project is a 12kV Siemens ”3AH1 115-2” vacuum circuit breaker. The breaker has a rated short circuit current of 31.5kV and a rated normal current of 1250A. In the tests done for this project the current will not come close to the rated current. The breaker is a 3 phase VCB with a distance of 210mm between the centre of the 3 sets of 28 4.1 The Existing Setup breaker contacts. The distance between the two VCB contacts in each phase is in open position 9mm [12]. The operating drive of the VCB is using a stored-energy mechanism, an opening spring and a closing spring. The closing spring can be charged either electrically, by a motor, or mechanically, using a handle. It can also be unlatched either electrically by means of the remote control or mechanically using the local ”CLOSE” pushbutton [12]. When the closing spring unlatches the opening spring automatically charges. The loads chosen for the setup is a 0.5µF and a 1.0µF load. The reason for this is that the loads should represent a cable network under no-load conditions, where a very small current flows in the network [11]. The loads are installed on the frame of the VCB in order to avoid long connections that can cause undesired transients. 4.1.2 Measurement and Control System As mentioned the measurement and control system is build up around a LabVIEW program. This program concerns with controlling the variotransformer, opening and closing the breaker, defining the measurement settings and saving the measured data. As seen in figure 4.2 the LabVIEW program communicates with almost all parts of the laboratory setup. In figure 4.2, a screen shot of the program GUI is shown. The program has 4 graphs that show the measurements done on the high voltage system. In the middle of the GUI there are 6 control boxes, 4 that control the oscilloscope, 1 that controls the breaker and 1 that controls the vario transformer. On the right side of the GUI there is a button called Enable which is used to save the measured data to a .lvm file. A description on how to plot the data from the saved .lvm file is seen in appendix A. In order to control the vario-transformer and the VCB the LabVIEW program sends a signal to the ”Hewlett-Packard 34970A data acquisition/switch unit” via the GPIB interface. The switch unit is equipped with a I/O card which switches 26V on 4 different channels. This unit is used to control two relays that sends a 170V dc signal to the VCB, these signal energizes the two coils which are used for opening and closing the VCB. When the springs for opening or closing the breaker is unlatches they automatically latches again using a motor supplied with 230V ac. The ”Hewlett Pacard 34970A data acquisition/switch unit” is also used to send control signals to the vario-transformer in order to increase or decrease the ratio of the transformer or to bring the secondary side voltage to zero. The fact that it is possible to increase and decrease the ratio of the vario-transformer enables the user to control the voltage level in the system. Laboratory Setup 29 Figure 4.2: Screenshot of the LabVIEW program. The data measurements in the system are collected in an oscilloscope and are sent to the LabVIEW program using a GPIB interface. The oscilloscope used is a ”LeCroy LC334”, which can sample with a frequency of up to 500M S/s. When the LabVIEW program is running it controls the oscilloscope, it can setup the measurement range, it takes care of the trigger mode and setup, and the program enables the user to choose which measurements to show on the oscilloscope display. The voltage measurements are performed by two Tektronix P6015A voltage probes. The probes are set to have a scaling of 1000:1 and they can tolerate up to 20kV and can measure frequencies up to 75M Hz. The two probes are placed on each side of the VCB, the probe on the load side of the VCB is connected to channel 1 on the oscilloscope and the probe on the transformer side of the VCB is connected to channel 2. A Rogowski current transducer of type CWT03 is placed to measure the current that runs through the high voltage system. The current transducer is placed after the load, meaning that the connection from load to ground runs through the coil. The current transducer can measure currents from 300mA to 600A and can measure frequencies up to 16M Hz. The output of the Rogowski current transducer is connected to channel 3 on the oscillo- 30 4.2 Improvements to the Existing Setup scope. To measure the distance between the contacts in the VCB a position meter is used. The position meter is connected to a fibreglass rod which is fastened to the moving contact of the VCB [11]. When the contact moves, it moves the fibreglass rod and thereby changes the output from the position meter. The position meter, is in fact just a variable resistance, and is supplied by a 9V battery, which means that the output from the position meter is between 0V and 9V . The output is connected to channel 4 on the oscilloscope. 4.2 Improvements to the Existing Setup The first measurements showed the need for some improvements of the setup. The main improvements made to the setup were adjusting the probe connections, installing a discharging resistance to the load and changing the setup of the Rogowski current transducer. Some minor adjustments were also made, e.g. moving the loads closer to the circuit breaker and rewiring the ground connection from the cable and the load making the connections as short as possible. 4.2.1 Improving probe connections The first measurements made on the system gave rise to some strange oscillations. These oscillations were a result of a too movable connection between the voltage probes and the VCB, when the VCB switches, it does so with large mechanical forces causing both the VCB and its frame to move. During these movements the voltage probes lost the connections with the VCB in small time intervals, this causes the voltage oscillations seen in the measurements. This was avoided by fastening the connections as seen in figure 4.3. The result of the new setup can be seen in figure 4.4, where the two plots show the results of the measurements before and after the new setup was used. Figure 4.4 also shows the TRV caused be the switching operation, and as seen the shape of the TRV also changes when the probes are fastened. Before fastening the probes the shape of the TRV were effected by disturbances and after the improvement the TRV obtains the expected shape. 4.2.2 Installing discharging resistance When a test of opening the breaker is made, the voltage on the capacitive load has to go to zero before the next measurement is taken. For this reason a discharge resistance is installed in parallel with the capacitor in order to make the discharging of the capacitor faster. It was estimated that Laboratory Setup 31 (a) Transformer side (b) Load side Figure 4.3: The two pictures show how the probes are fastened to the setup. Before this was done the probes were connected loosely to the setup by the hooks on the tip of the probes. 4 HTTP1L100C1x05Dt1−6V5,75kOUT.lvm x 10 Voltage on trans. side of the VCB [V] Voltage on trans. side of the VCB [V] 4 HTTP1L100C1x05Dt1−6V5,75kOUT.lvm 1 0.5 0 −0.5 −1 −1.5 −2 0 10 20 30 40 50 1 x 10 0.8 0.6 0.4 0.2 0 −0.2 −0.4 −0.6 −0.8 −1 0 10 Time[ms] 20 30 40 50 Time[ms] (a) Before improving the setup (b) After improving the setup Figure 4.4: The plots show the voltage measured on the transformer side probe, before and after fastening the probe. At around 30ms oscillations can be seen on figure a. a discharging time of approximately 10 seconds would be suitable, due to the time used on saving the measurements to the .lvm file. The following calculations show how the size of the discharging resistance, R, is found τ = R · C, setting τ = 5s and C = 0, 5µF gives R= 5s = 10M Ω. 0.5µF As seen from the calculations a 10M Ω resistance gives a time constant of 5 seconds. This means that after 5 seconds the voltage will have decreased to 32 4.2 Improvements to the Existing Setup Figure 4.5: The picture shows the Rogowski current transducer. In order to improve the current-to-noise ratio the current measurement is led through the Rogowski coil 4 times as seen on the picture 37% of the initial voltage, which means that after 10 seconds the capacitor should be discharged, therefore a 10M Ω resistance is chosen as discharge resistance. 4.2.3 Improving the Rogwski current transducer setup The first tests of the laboratory setup showed a low frequency disturbance on the current measurement. Where this disturbance comes from is unknown, but since it had quiet a big influence on the current it was decided to improve the current-to-noise ratio so that the low frequency fault current had less influence. Therefore the wire conducting the current through the Rogowski transducer was twisted several times so that it runs through the Rogowski coil 4 times, increasing the output current by a factor 4, meaning that the ratio of the Rogowski transducer is changed from 10mV /A to 40mV /A. In figure 4.5 it can be seen how the new setup of the Rogowski current transducer looks. A change in the LabVIEW program was made in order to fit the program to the new voltage-current ratio of the Rogowski transducer. Chapter 5 Laboratory Tests and Results The main purpose of the tests is to determine the paremeters that are used to describe the VCB in the simulation model. All the measurements made in this project have been made on one phase. The tests have been performed with two different setups, one using the 10m cable to connect the HTT transformer and the VCB and one using the 100m cable. This is done in order to observe how the VCB reacts on different configurations of the network it is operating in. At both cable lengths tests were made at different voltage levels. The voltages levels were chosen based on the knowledge that the HTT transformer has a nominal voltage of 5.75kV on the secondary side. This voltage level was chosen to be the base of the measurements and test series were made on voltage levels of 20%, 40%, 60%, 80%, 100% and 120% of the 5.75kV . The reason why the system was tested at different voltage levels was to see how the voltage level effects the generated transients. In order to calculate the current chopping level of the breaker, the tests at the low voltage levels are very useful, since they do not create any significant transients. During the work with the current chopping level it was chosen to make use of the extra load capacitor in order to increase the current in the system. As this project mainly concentrates with the very fast transients caused by the breaking operation the measurement time has been set to 10ms. During this 10ms, 50000 data measurements are taken, which means that the time between each measurement, ∆t, is 0.2µs. This gives a good and precise picture of the fast transients. When analysing the chopping current of the VCB tests with a measuring time of 50ms is used, since the amplitude of the current is a parameter in the chopping current calculations and cannot be read on the 10ms measuremets. A few more measurements, with a measurement time of 50ms, were made to illustrate the breaking process and measure the opening and closing time of the VCB. 34 In order to observe the effect the arching time has on the VCB and the TRV it was decided to make several tests on each voltage levels to observe most possible breaking angles and thereby different arching times. Since it is not possible to control the breaking angle or the breaking time of the VCB, random tests were made and for every test the angle was registered. The voltage sine curve was divide in 8 sections and the testing was continued until a breaking angle in each section was obtained. The breaking angle was read on the voltage measurements, this means that with a breaking angle of 0◦ , the VCB opens when the power frequency voltage curve is at the rising zero crossing. A breaking of 90◦ would mean that the VCB opens when the voltage is at its maximum. When the breaker closes, the angle at which it starts conducting current is called the closing angle and is found in the same way as the breaking angle. To distinguish between the different test series it was decided to give each file containing the measurements a name referring to the test setup. An example of the file name could be: HT T P 1L100C1x05Dt2 − 7V 5, 75kIN 1 where the meaning of the different parts of the name are: • HTT : HTT transformer is used. • P1 : One phase is connected between the HTT transformer and the VCB. • L100 : The length of the cable between the HTT transformer and the VCB is 100m. • C1x05 : The load on the VCB is capacitive with a size of 0.5µF . • Dt2-7 : The time step between measurements is 2 · 10−7 s. • V5,75k : The voltage on the secondary side of the HTT transformer is 5.57kV . • IN1: The measurements are taken when the VCB closes. The HTT transformer and number of phases connected are included in the filename, even though they are not changed throughout the project. This is done so that it is easy to make more tests with different setups and compare the new tests with the ones made in this project in future work on the VCB. As described in chapter 4, the measurement system takes 4 measurements, the position of the moving VCB contact, the current, the voltage on the Laboratory Tests and Results 35 HTTP1L100C1x05Dt1−6V6,9kIN1.lvm 40 8 30 7 20 Current[A] Distance between VCB contacts[mm] HTTP1L100C1x05Dt1−6V6,9kIN1.lvm 9 6 5 4 10 0 −10 3 −20 2 −30 1 0 10 20 30 40 −40 50 0 10 Time[ms] HTTP1L100C1x05Dt1−6V6,9kIN1.lvm Trans. side voltage[V] Load side voltage[V] 0.5 0 −0.5 0 10 20 30 50 40 Time[ms] (c) The load side voltage HTTP1L100C1x05Dt1−6V6,9kIN1.lvm 4 1.5 1 −1 40 (b) The current 4 x 10 30 Time[ms] (a) The length of the VCB gab 1.5 20 50 x 10 1 0.5 0 −0.5 −1 0 10 20 30 40 50 Time[ms] (d) The transformer side voltage Figure 5.1: Closing the VCB at voltage level 6.9kV , the setup is using the 100m cable and the load with a capacitance of 0.5µF . The time between the measurements ∆t is 1 · 10−6 s, and the closing angle is 0◦ load side of the VCB and the voltage on the transformer side of the VCB. In figure 5.1 the 4 measurements from a closing process of the VCB are shown. As figure 5.1a shows, the moving VCB contact starts to move towards the fixed VCB contact after around 20ms. The picture shows a distance between the contacts is only 7.8mm and not 9mm, this is due to a small calibration error in the position meter. After around 30ms the distance between the contacts is 0mm and the VCB starts conducting current, as seen in figure 5.1b. Figure 5.1c and 5.1d show the voltage on both sides of the VCB, the voltage on the load side is zero until the contacts are together and after that it follows the transformer side voltage since the VCB forms a short circuit between the two voltage probes. This measurement is taken at aclosing angle of about 0◦ . As mentioned this angle can easiest be seen on the transformer side voltage curve, where a small switching transient appears in the area of 5.1 Preparatory tests HTTP1L100C1x05Dt1−6V5,75kIN3.lvm 9 8 X: 20.39 Y: 7.688 7 6 5 4 3 2 1 0 10 20 30 X: 32 Y: 1.312 40 50 Time[ms] (a) Closing the VCB Distance between VCB contacts[mm] Distance between VCB contacts[mm] 36 HTTP1L100C1x05Dt1−6V5,75kOUT3.lvm 8 X: 27.6 Y: 7.594 7 6 5 4 3 2 X: 19.89 Y: 1.219 1 0 5 10 15 20 25 30 35 40 45 50 Time[ms] (b) Opening the VCB Figure 5.2: The figure shows two plots of the distance between the VCB contacts, when the VCB is opening and closing. the rising zero crossing or around 0◦ . As this shows the measurement of the angle is not very precise and the closing and opening angles decribed will be approximate values. 5.1 5.1.1 Preparatory tests Breaker position The opening time of this type of VCB should be less than 15ms [12] and previous projects have measured the opening and closing time of the specific VCB to be around topen = 7ms and tclose = 12ms [9]. In figure 5.2 a measurement of the distance between the VCB contacts during a closing and an opening process is seen. In figure 5.2 two data markers are set, these data markers shows the time and the distance between the contacts and this data can be used to find the closing and opening time of the VCB. tclose = 32.001ms − 20.391ms = 11.61ms topen = 27.602ms − 19.889ms = 7.713ms The values used for the calculations are more exact than the values seen on the data markers on the figures. The exact values of the data markers can be exported to a file in MATLAB and the values from this file are used to make the calculations, this method was used throughout the project. The results of the closing and opening time corresponds to the values calculated in previous projects. As seen of figure 5.2b some vibrations occurs when the moving breaker contact reach the open position. These vibrations are caused by the mechanical impact the contact gets when reaching the open position Laboratory Tests and Results 37 and it stabilise after some time. The used breaker model does not offer an option to change the opening and the closing time of the VCB. Instead the model uses a fixed time of 0.55ms as both the opening time and the closing time of the VCB. 5.1.2 Resistance of the Voltage Circuit Breaker The simulation model of the VCB uses the resistance of the VCB in open and closed position as parameters and for this reason these values have to be measured. Since the resistance in open position is very high and the resistance in closed position is very small, a normal ohmmeter cannot be used in the measurement. In order to measure the resistance of the VCB in open position an insulation tester is used, the tester is a ”Fluke 1520 MegOhmMeter” that can measure a maximum of 4000M Ω. The test of the open resistance measurement gave Ropen > 4000M Ω. In order to measure the resistance of the VCB in closed position a Wheatstone bridge is used. This device is a bridge circuit which consists of 2 known resistors, one adjustable resistor and the last part of the bridge is the resistor being measured. A 4-point measurement technique, applying both a current and a voltage over the measured resistance, is used in order to get the most precise measurement. The measurement of the closed resistance gave the following result Rclosed = 200µΩ, The value of Ropen will be set to 1M Ω in the simulations, since it is the highest possible value in the simulation model, and Rclosed will be set to the measured 200µΩ. 5.2 Transient Recovery Voltage When the VCB contact separates and the vacuum arc extinguishes, a TRV will arise across the two contacts. This TRV is a critical parameter in the interruption process, the TRV can either cause the arc to be reestablished or it can lead to successful interruption. As described in chapter 2, the TRV is dependent on the network configuration. The TRV is calculated by using the voltage measurement from the load side of the VCB and the voltage measurement from the transformer side of the VCB, like this T RV = VLoad − VT rans . (5.1) 38 5.2 Transient Recovery Voltage HTTP1L100C1x05Dt2−7V5,75kOUT2.lvm 4000 2000 2000 0 0 TRV[V] TRV[V] HTTP1L10C1x05Dt2−7V5,75kOUT6.lvm 4000 −2000 −2000 −4000 −4000 −6000 −6000 −8000 3 3.5 4 4.5 5 5.5 6 Time[ms] (a) Test with 10m cable 6.5 7 −8000 2 2.5 3 3.5 4 4.5 5 5.5 6 Time[ms] (b) Test with 100m cable Figure 5.3: The TRV across the breaker contacts using a 10m and a 100m cable. The breaking angle is in both cases 0◦ . 5.2.1 Frequency of the Transient Recovery Voltage In chapter 2 it is described how the frequency of the TRV depends on the network configuration, and should be the same for all breaking angles. Tests have been performed with two network configurations in order to observe different frequencies of the TRV. Figure 5.3 shows the TRV in the two network configurations, in both cases the breaking angle is 0◦ . As figure 5.3 clearly shows the tests made with the different cable lengths gives different frequencies of the TRV. To find the two frequencies a number of measurements were made on the curves. In figure 5.4 the measurement from one test is shown. As seen in figure 5.4, 7 markers have been placed on the curve, one marker is placed to show at what time the TRV is damped, and the last 6 markers are placed to find the wavelength of the TRV at different places. If using the two first markers at the top tips of the TRV it can be found that the wavelength of the TRV in this area is λ = 4.2908ms − 4.1808ms = 0.11ms, and by using the wavelength the frequency can be found 1 1 ⇒ = 9090.9Hz λ 0.11ms In order to minimise inaccuracy caused by the data measurements, more data markers are set. The wavelength and the resulting frequencies are found between the other data markers as well and the mean of the four frequencies is found. In appendix B the results of all the tests made at 5, 75kV , for both 10m and 100m, is shown. In the full appendix, which is found on the cd, the measurements and data points used for the calculations are found. The results in tables B.1 and B.2 show the breaking angle, fT RV = Laboratory Tests and Results 39 HTTP1L10C1x05Dt2−7V5,75kOUT6.lvm 3000 X: 4.181 Y: 3000 2000 X: 4.291 Y: 1625 1000 X: 4.406 Y: 375 TRV[V] 0 −1000 −2000 X: 5.24 Y: −3000 −3000 X: 4.242 Y: −3625 X: 4.355 Y: −3000 −4000 −5000 −6000 3.5 X: 4.121 Y: −5125 4 4.5 5 5.5 Time[ms] Figure 5.4: The measurements for calculating the frequency of the TRV when using a 10m cable in the test. The breaking angle is again 0◦ . the amplitude, the frequency and the damping time of all the measurements. The two tables show that the frequency is independent of the breaking angle and the average value of the frequencies are: fT RV 10 = 8708, 92Hz fT RV 100 = 2953, 87Hz. The results show that when changing from a 100m cable to a 10m cable, the frequency of the TRV becomes almost 3 times higher. This is a result of the difference in capacitance and inductance in the two cables. As the cables used are of same type, the 100m cable has a capacitance and inductance that is 10 times higher than in the 10m cable, the specific parameters of the cable can be seen in table 4.1. 5.2.2 Amplitude of the Transient Recovery Voltage The amplitude of the TRV is a very important parameter as this voltage can reach values that are higher than the normal peak voltage and thereby apply a high eletrical stress to components. The amplitude of the TRV is measured as the first and undamped maximum of the TRV, e.g. in the test shown in figure 5.4 the amplitude of the TRV is 5125V . In contrast to the frequency of the TRV, the amplitude of the TRV is dependent of the breaking angle. This dependency can be seen in tables B.1 and B.2. In table 5.1 40 5.2 Transient Recovery Voltage some of the results from the tests using the 10m cable have been taken out and sorted by the breaking angle. From table 5.1 the relation between the breaking angle and the ampliTest nr. Brk. angle[◦ ] Amplitude[V ] 12 0 -5500 4 22.5 -5375 3 45 -4875 9 90 0 2 180 5250 8 202.5 4500 7 225 4250 10 247.5 1625 Table 5.1: The table shows the relation between the breaking angle and the amplitude of the TRV. The results are from the tests made at 5.75kV using the 10m cable. tude can be seen. When the VCB breaks the voltage close at a maximum value of the voltage, 90◦ and 270◦ , the amplitude of the TRV is low and when the VCB breaks the voltage close to a zero crossing, 0◦ and 180◦ , the amplitude is high. The reason for this is that the VCB conducts a capacitive current, causing the current to lag the voltage with 90◦ . This means that when the VCB breaks at a high voltage the current that is interrupted is low and will cause low amplitudes of the TRV. In the best case, if the interruption happens at a current zero crossing, no TRV will be generated. When the voltage is around zero at the time of interruption, the current will be interrupted around its maximum and cause a TRV with high amplitude. The tables B.1 and B.2 also show that for breaking angles from 90◦ to 270◦ the TRV will start by rising, resulting in a positive first amplitude. Similarly for breaking angles from 270◦ to 90◦ the TRV will start by falling, the reason for this relation is the direction of the current, which will be opposite in the two intervals. Table B.1 and B.2 show that there is a clear connection between breaking angles that are 180◦ apart. They have the same amplitude but with different sign, this is because measurements that are 180◦ apart are on the same place of both the voltage and current curve, except from the fact that one is on the negative part and one is on the positive part. This similarity has been observed throughout the project. The tests have shown that the setup with the short cable gave larger TRV amplitudes. As the short cables also have a larger frequency the rate of rise of the TRV will be higher when using the short cable. This will lead to more reignitions, since a circuit where the TRV has a high rate of rise will reach the dielectric withstand level of the VCB faster than in a setup where the rate of rise of the TRV is lower. The tables B.1 and B.2 also show the time it takes for the TRV to be completely damped. The TRV generated when using the short cable needs less than half the time to be damped than the TRV generated when using Laboratory Tests and Results 41 the long cable. The mean value of the damping time is 0.97ms when using the 10m cable and 2.3ms when using the 100m cable. 5.3 Chopping Current The current chopping is an undesirable effect of the VCB, since the steep slope of the current produces the TRV that can cause overvoltages in the network. As described the current chopping is a result of arc instability which causes the vacuum arc to be extinguished before reaching a current zero. The value of the current chopping level is found using equation (3.1). In order to find the contact parameters α and β, it is necessary to know the amplitude of the current through the breaker and the current chopping level. Figure 5.5 shows a measurement of the current when opening the VCB at voltage level 5.75kV with breaking angle 180◦ using the 100m cable. As seen in figure 5.5a there is a high spike on the current around 20ms, this current spike is a result of the HF currents, which occur after arc extinguises. In order to read the amplitude of the current and the current chopping level a zoomed plot of the current around the breaking time is needed. In figure 5.5b a plot zoomed around the power frequency current is shown. As seen the zoomed plot is very blurred and it is hard to make a precise measurement of the current chopping level and the current magnitude. This problem occurs when recording the measurements in LabVIEW. In order to get the full picture the settings of the oscilloscope have to be in a way so that all data points fit in the plot. For this reason the sensitivity of the oscilloscope has to be set so that the maximum point of the HF current is within the measuring range. This means that the measurements get less accurate and the picture gets blurred. Therefore it is convenient to look at measurements taken at lower voltage levels, where smaller or almost no HF currents are produced. In figure 5.6 a plot of the current during a breaking process is shown. As seen the current is interrupted at around 22ms, before this time the power frequency current (with disturbance) is conducted. At 22ms the current chopping level is apparently reached and the current is chopped. After this point the only current comes from discharging the capacitor and after a short time the current measured in the Rogowski coil is zero. The full appendix C on the CD contains the measurements for calculating the values α and β. From the graphs in the full appendix C, it can be observed that the current chopping occurs at the same time in all measurements. This indicates that the current level is under the level of the chopping 42 5.3 Chopping Current HTTP1L100C1x05Dt1−6V5,75kOUT1.lvm 5 80 4 60 3 40 2 Current[A] Current[A] HTTP1L100C1x05Dt1−6V5,75kOUT1.lvm 100 20 0 −20 1 0 −1 −40 −2 −60 −3 −80 −4 −100 0 10 20 30 40 50 −5 0 Time[ms] 10 20 30 40 50 Time[ms] (a) Unzoomed plot. (b) Zoomed plot. Figure 5.5: The plots shows the current through the VCB at 5, 75kV using a 100m cable. The interruption is made at a breaking angle of 180◦ . current and therefore the current is chopped instantaneously after contact separation. In table C.1 the value of α has been calculated when β has the value 14.3, this is expected to result in a value of α around 6.2 · 10−16 s. As seen in table C.1 the calculated values of α are very different from the expected value, and the calculated values vary a lot. The results from table C.1 indicate that the current is under the current chopping level of the breaker, which means that the VCB breaks the current as soon as the contacts separate. Therefore another test series with the extra capacitor, increasing the load to 1.0µF , was made. These tests can also be seen in the full appendix C on the CD. The constant α has been calculated again using the new measurements and the results can be seen in table C.2 the values of α are still very different from the expected value and they still vary a lot. And since it has not been possible to find a reasonable value of α no attempts at finding β has been made. The plots of the measurements and the calculations of the constant α strongly indicates that the current level in the tests is lower than the current chopping level of the VCB. This corresponds with the fact that the normal current chopping level for VCBs usually varies between 3A and 8A. In order to find the parameters of α and β for the breaker, different types of loads must be used in order to conduct a current that is larger than the current chopping level. But since only the small capacitive loads were available standard values of α and β will be used in the simulation model: α = 6.2 · 10−16 s β = 14.2. Laboratory Tests and Results 43 HTTP1L100C1x05Dt1−6V1,15kOUT6.lvm 0.4 0.3 Current[A] 0.2 0.1 0 −0.1 −0.2 −0.3 0 10 20 30 40 50 Time[ms] Figure 5.6: The plots shows the current through the VCB at 1, 15kV using a 100m cable. The interruption is made at a breaking angle of 45◦ . 5.4 Reignitions To find the dielectric withstand of the VCB, the reignitions that occur when opening the breaker have been studied. After the vacuum arc has been extinguished, the race between the TRV and the dielectric withstand of the VCB begins. When the TRV exceeds the dielectric withstand of the VCB a breakdown of the vacuum occurs and creates a conducting path between the two VCB contacts. When the conducting path is created the TRV jumps back to zero and does not start to rise again before the arc is extinguished. In figure 5.7 it is seen how reignitions appears after contact seperation. Figure 5.7 shows there is a difference in the number of reignitions between the tests made with the 100m cable and the 10m cable. In figure 5.7 there is 3 reignitions when the 100m cable is used and around 11 reignitions when using the 10m cable. It is also seen that the conducting time of the vacuum arc is a lot shorter when using the 10m cable, with this setup the arc is extinguished almost instantaneous. The reignitions when using the 100m cable appear for a longer time, around 0.2ms. The difference is a result of the different shape of the TRV, as mentioned the TRV has a large rate of rise in the system when the 10m cable is used. Therefore the TRV will reach the dielectric withstand of the VCB much faster and create more reignitions as seen in figure 5.7. 44 5.4 Reignitions HTTP1L10C1x05Dt2−7V5,75kOUT7.lvm 5000 4000 4000 3000 3000 2000 2000 TRV[V] TRV[V] HTTP1L100C1x05Dt2−7V5,75kOUT4.lvm 5000 1000 1000 0 0 −1000 −1000 −2000 −2000 −3000 2.6 2.7 2.8 2.9 3 3.1 3.2 −3000 3.75 3.8 3.85 Time[ms] (a) 100m cable 3.9 3.95 4 4.05 4.1 4.15 Time[ms] (b) 10m cable Figure 5.7: The plots shows the voltage across the breaker contacts during an opening of the VCB. Both tests have a breaking angle of 225◦ . 5.4.1 Rate of rise of Dielectric Strength In order to model the VCB it is necessary to know its dielectric withstand. The dielectric withstand of the breaker can be found by using equation (3.2) and in order to simplify the calculations the value of the TRV just before current zero is set to be zero. This means that the dielectric withstand of the breaker is proportional to the RRDS or the value A used in the simulation model. Figure 5.8 shows how the RRDS of the VCB is found. The red line on figure 5.8 illustrates how the dielectric withstand is increased with respect to time. The time t0 is set to zero in the calculations, this is done because the time of contact separation is not know. This will give correct results when making the linear regression to find the RRDS, since the progress of t − t0 is the same as long as t0 is set constant. The data measurements that are showed in figure 5.8d are used to perform a linear regression, finding the RRDS of the VCB. In the example on figure 5.8d the value of the RRDS becomes 24.37V /µS. The full appendix D on the CD shows the data measurements that have been used to calculate the value of the RRDS and the tables D.1, D.2, D.3, D.4, D.5 and D.6 shows the results of the calculations. As the tables show an average value of the RRDS is found in each of the 6 test series, and these values can be seen in table 5.2. As it is seen in table 5.2 the calculated values of the RRDS is much smaller when using the 100m cable than the ones calculated for the 10m cable. The table also shows that the value of the RRDS seems to be dependent of the voltage when using the 100m cable, where the calculations of the RRDS are more constant when the 10m cable is used. The results found in appendix D also shows a much larger variance of the results using the 100m cable with many large and small values of the RRDS. This is particularly the case Laboratory Tests and Results 45 HTTP1L100C1x05Dt2−7V5,75kOUT4.lvm HTTP1L100C1x05Dt2−7V5,75kOUT4.lvm 5000 4000 4000 3000 3000 2000 TRV[V] TRV[V] 2000 1000 0 1000 0 −1000 −1000 −2000 −2000 −3000 2.6 2.7 2.8 2.9 3 3.1 3.2 3.3 3.4 2.8 2.85 Time[ms] 2.9 2.95 3 3.05 Time[ms] (a) The full measurement (b) Zoomed plot, showing the reignitions HTTP1L100C1x05Dt2−7V5,75kOUT4.lvm HTTP1L100C1x05Dt2−7V5,75kOUT4.lvm 4000 4000 3000 3000 X: 2.885 Y: 2250 2000 TRV[V] TRV[V] 2000 1000 1000 X: 2.842 Y: 750 0 0 −1000 −1000 −2000 X: 2.81 Y: 468.8 −2000 2.8 2.85 2.9 2.95 3 3.05 2.8 Time[ms] (c) Dielectric withstand curve 2.85 2.9 2.95 3 3.05 Time[ms] (d) Points for calculating the RRDS Figure 5.8: The figure illustrates how the RRDS is calculated from the laboratory measurements. Voltage level 4.6kV 5.75kV 6.9kV Average RRDS Cable 10m 38.24V /µS 39.39V /µS 36.02V /µS 37.88V /µS length 100m 18,52V /µS 21,94V /µS 24,50V /µS 21.65V /µS Table 5.2: The table shows the average RRDS, for the 6 analysed test series and the average value of the RRDS found for the two cable lengths. at voltage level 4.6kV and is probably due to the fact that less reignitions occurs at this voltage level and thereby makes the results vulnerable to measurement mistakes. In the tests using the 10m cable the results are more close to the average value and only a few results are very different from the 46 5.4 Reignitions average values. With basis in these consideration the value of the RRDS that is used in the simulations, has been chosen. It is decided to choose the value of the RRDS that was calculated in the tests where the 10m cable is used. This decision was made because of the lack of stability in the results from the 100m cable tests. Specially the fact that the value of the RRDS increases when the voltage level (number of reignitions) increases indicate that there is a lot of inaccuracy in the calculations, and therefore the results using the 10m cable, which creates a lot of reignitions, are used. The value of the RRDS that will be used when simulating the VCB will therefore be the average of the value found in the 10m cable tests and the value of B will be zero: A = 37.88V /µs B = 0. This means that the dielectric withstand of the VCB when it is fully open (after 7.23ms) will be: Vopen = 37.88V /µS · 7.23ms · 1000µs = 273.87kV. ms This means that the withstand of the vacuum between the breaker contacts is: Vvacuum = 273.87kV = 30.43kV /mm. 9mm As seen from the calculations the dielectric withstand of vacuum in the VCB is approximately 10 times larger that the withstand in air. 5.4.2 Effect of breaking angle As seen in table 5.1 the breaking angle has an influence in the amplitude of the TRV. Therefore it is also expected that the breaking angle has an influence in the number of reignitions that occurs after separating the VCB contacts. As figure 5.7 shows there is a difference in reignitions in the tests done with different cables. A closer look at tables D.1, D.2, D.3, D.4, D.5 and D.6 show that the number of reignitions are dependent on the breaking angle. To illustrate this the results from the test made at 5.75kV with 10m cable have been sorted by the breaking angle and are shown in table 5.3. Table 5.3 shows that the relation between number of reignitions and breaking angle follows the same pattern as the relation between amplitude of the TRV and the breaking angle. When the VCB breaks the voltage close a maximum value of the voltage at 90◦ and 270◦ , the number of reignitions Laboratory Tests and Results Test nr. Brk. angle[◦ ] Reignitions 6 0 20 5 22.5 18 47 3 45 15 9 90 0 1 180 15 8 202.5 15 7 225 10 10 270 1 Table 5.3: The table shows the relation between the breaking angle and the number of reignitions of the vacuum arc. The results are from the tests made at 5.75kV using the 10m cable. is low and close to zero and when the VCB breaks the voltage close to a zero crossing, 0◦ and 180◦ , the number of reignitions is quiet high. The reason for this is that the current is capacitive and therefore zero at voltage maximum and maximum at voltage zero. It is clear that the number of reignitions must be zero if the VCB opens at a current zero crossing since no current is interrupted and no vacuum arc is formed. During a current maximum a large current will be interrupted this creates a TRV with high amplitude which leads to many reignitions. Tabel 5.3 shows that the number of reignitions is almost the same at the positive part and the negative part of the curve, this can again be related to the TRV which had the same amplitude at the positive part and the negative part. 5.5 High Frequency Quenching Capability When a reignition of the vacuum arc occurs it will cause a HF current to be superimposed on the power frequency current. This HF current may be quenched at one of its zero crossings, if it has a low enough di/dt. If the current is quenched the TRV will again start rising over the VCB gab and depending if it reaches the dielectric withstand a new reignition and a new HF current will be created. In figure 5.9 the TRV and the current through the VCB is seen. Figure 5.9 is a measurement taken when the 100m cable is used, in this measurement it is easy to see that when the two first reignition occur (TRV jumps to 0), the HF current is formed. The third reignition (after 2940µs) gives only a short appearance of the HF current, which is quenched after only a half period. It is also seen that the first HF current (13 periods) is longer than the second HF current (1 21 periods). This phenomenon of shorter lifetime of the reignitions has been observed in almost all measurements on the 100m cable, but in most of the measurements the second reignition creates a HF current with a length of 3-7 periods. As figure 5.9 shows, the magnitude of each HF current is small at the first reignition and rises from reignition to reignition. In this case the magnitude starts at around 10A on the first HF current and at the second HF current the magnitude is around 30A ending at a magnitude of around 80A for the last HF current. This phenomenon is also observed in all the measurements. 48 5.5 High Frequency Quenching Capability HTTP1L100C1x05Dt2−7V5,75kOUT8.lvm TRV[V] 2000 0 −2000 −4000 −6000 2700 2750 2800 2750 2800 2850 2900 2950 3000 2850 2900 2950 3000 Current[A] 100 50 0 −50 −100 2700 Time[us] Figure 5.9: The plot shows how the reignitions of the VCB create a HF current that is superimposed on the power frequency current. The test is from the system with 100m cable and the breaking angle is 292.5◦ . The frequency of the HF currents is around 400kHz, which means that the wavelength is only 2.2µs. With this short wavelenght and a ∆t of 0.2µs the plots of the HF currents do not get as precise as desired. The plots are good enough to determine the HF current quenching capability, but in order to get a more precise result the measuring time, when examining HF currents, should be set down in comming projects. When the 10m cable is used in the measurement the shape of the HF currents become very different from the ones observed in figure 5.9. The HF currents that appear in the system using a 10m cable can be seen in figure 5.10. The HF currents seem to be quenched instantly after they appear and can just be seen as small spikes on the current curve, which occur when the TRV jumps to zero. Some of the HF currents are quenched even before they reach their first maximum, and therefore it is not possible to see the increase in magnitude in the HF currents. 5.5.1 Determining the High Frequency Quenching Capability Since the HF currents from the tests with the 10m cable have a very short life time and are often quenched even before the first maximum is reached, it is not possible to use them when calculating the HF quenching capability of Laboratory Tests and Results 49 HTTP1L10C1x05Dt2−7V5,75kOUT7.lvm TRV[V] 5000 0 −5000 3850 3900 3950 4000 4050 3950 4000 4050 Current[A] 50 0 −50 3850 3900 Time[us] Figure 5.10: The plot shows how the reignitions of the VCB create a HF current that is superimposed on the power frequency current. The test is from the system with 10m cable and the breaking angle is 225◦ . the VCB. Before determining the HF quenching capability of the VCB many considerations on the approach were made. The two main considerations were how to determine the constant Cc that appears in equation (3.3) and the second was how to set the opening time of the VCB, t0 . The value of Cc can be described as the change in di/dt with respect to time. The value is therefore found by finding the slopes of the HF current between a maximum and a minimum point and describe the slopes as a function of time. The time used to find Cc is in equation (3.3) given as t − t0 . The time t0 should be the opening time of the breaker, but since this time is not known it, was decided to set t0 as the time when the HF current starts appearing. When calculating the value of RRDS the time t0 was set to zero, but in this case the beginning time of the HF current was chosen, since this time have to be used anyway when finding the value of Dd . The value of the constant Cc can now be calculated from the measurements of the HF currents. In figure 5.11, 2 plots are seen, plot 5.11a shows 3 occurrences of HF currents during a breaking operation and plot 5.11b is a zoomed plot showing the values used to calculate the HF quenching capability of the VCB. As described the value of Cc is found by making a linear regression, using the di/dt, found between the data markers, and the difference between the time of a the zero crossing and the start time of the HF current. The value of Dd is found simply by 50 5.5 High Frequency Quenching Capability HTTP1L10C1x05Dt2−7V5,75kOUT8.lvm HTTP1L100C1x05Dt2−7V5,75kOUT8.lvm 100 25 80 20 60 40 10 Current[A] Current[A] X: 2785 X: 2787 X: 2790 Y: 14.06 X: 2795 Y: 12.5X: 2793 Y: 12.5 Y: 10.94 Y: 10.94 X: 2801 X: 2803 Y: 7.812 Y: 7.812 15 20 0 −20 −40 5 X: 2783 Y: −1.562 0 −10 −15 −20 −80 −25 −100 2700 2770 2750 2800 2850 2900 2950 2780 X: 2808 X: 2811 X: 2813 Y: 6.25 Y: 6.25 Y: 6.25 X: 2816 Y: 1.562 2790 2800 2810 2820 2830 Time[us] 3000 Time[us] (a) Plot showing the reignitions X: 2806 Y: 7.812 X: 2815 X: 2807 Y: −7.812 X: 2802Y: −9.375 X: 2794 X: 2797 Y: −10.94 Y: −12.5 Y: −12.5 X: 2809 X: 2787 X: 2804Y: −7.812 X: 2812 X: 2784 Y: −15.62 X: 2799Y: −9.375 Y: −9.375 Y: −17.19 X: 2792 Y: −10.94 X: 2789 Y: −12.5 Y: −14.06 −5 −60 X: 2798 Y: 7.812 (b) Zomed plot showing the first reignition Figure 5.11: The plots shows the data markers used to calculate HF current quenching capacity of the VCB. finding the slope between the first two data markers seen on figure 5.11b. Dd = A −1.562 − (−17, 1875) = −15.626 . 2783, 2 − 2784, 2 µs In the full appendix E on the CD the measurements and the data used for calculation of the HF quenching capability of the VCB are found. The results of the calculations is seen in table E.1, in the printed version, and as seen the calculations of Cc and Dd are made separately for each reignition. The results in the table are only results from HF currents that have a appearance time, which is long enough to give a realistic result (more that 1 period). The average value of Cc and Dd can be seen in table 5.4. As table 5.4, shows Arc nr. Average Arc 1 A C[ µs 2] -0.591 Arc 1 A D[ µs ] 25.670 Arc 2 A C[ µs 2] -1.190 Arc 2 A D[ µs ] 48.572 Arc 3 A C[ µs 2] -1.912 Arc 3 A D [ µs ] 75.703 Table 5.4: The average results of the calculations of C and D the values of Cc and Dd both increase depending on the number of reignition it is calculated for. And as seen in table E.1 in the appendix, the value of the constants vary a lot even for the calculation done on the same arc number. When comparing the results to the suggested values presented in chapter 3, it shows that the lowest value of Cc is pretty far from the suggested negative value, −0.034A/µs2 and the value of Dd is also far from the suggested values. Due to the found results, another approach of finding the HF quenching capability was tried. Instead of looking at the value of di/dt according to Laboratory Tests and Results 51 equation (3.3) the value was set to be constant. Using this approach the value of di/dt can be seen as the slope between the last two data pointers in figure 5.11b, the example from the figure gives Dd = −7.8125 − 1.562 A = 11.718 . 2814.8 − 2815.6 µs This approach leads to the results seen in table E.2 in appendix E. The average of the results is shown in table 5.5. As the table shows the results Arc nr. Arc 1 A D[ µs ] Arc 2 A D[ µs ] Arc 3 A D[ µs ] Average 13.255 34.03 55.742 Table 5.5: The average results of D when considering di/dt to be constant. calculated with this approach is again not close to the expected values preA A sented in chapter 3, (100 µs - 600 µs ). Since none of the two approaches gives results close to the expected values of the HF quenching capability parameters, it could indicate that the quenching capability of the VCB cannot be calculated when the current through the VCB is very low. Because of the results the values of the HF current quenching constants, Cc and Dd are set to the suggested values in [1] A µS µs2 A Dd = 350 . µs Cc = 0 5.6 Closing the circuit When the contacts in the VCB start moving together the dielectric withstand of the gab between them starts to get smaller. At one point the dielectric withstand of the gab will become smaller than the voltage across the contact and a breakdown of the vacuum will occur. 5.6.1 Prestrikes This conducting vacuum arc formed by the breakdown will cause the voltage between the breaker contacts to go to zero. In figure 5.12 a plot of the voltage across the VCB channels and the current during 3 prestrikes of the breaker is seen. As seen in figure 5.12 the prestrike creates an oscillating HF current. This current is interrupted at one of its current zeros, when di/dt is low enough and the voltage over the VCB channels reappears. The arc appears again the next time the voltage over the contacts reaches the 52 5.6 Closing the circuit HTTP1L100C1x05Dt2−7V6,9kIN11.lvm Voltage[V] 5000 0 −5000 −10000 6180 6190 6200 6210 6220 6230 6240 6250 6260 6190 6200 6210 6220 6230 6240 6250 6260 Current[A] 200 100 0 −100 −200 6180 Time[us] Figure 5.12: The plot shows the voltage across the breaker channels and the current through the breaker when during 3 prestrikes. The test is made with 100m cable and at a closing angle of 22.5◦ . decaying dielectric withstand of the VCB. Prestrikes are also observed in the system using a 10m cable and in the same way as the reignitions, the prestrikes created in this setup seems to have a much shorter lifetime. In figure 5.13, 4 prestrikes from measurements with the 10m cable are seen. In the same way as when the 100m cable is used the prestrike forces the voltage across the contact to go to zero. After the restrikes in figure 5.13 the voltage is going more smoothly back to the previous voltage level than when using the 100m cable. Just after it reaches the previous voltage level another restrike is created whereas in the case with 100m cable the voltage across the cannels kept were steady for a while before another restrike was created. In the VCB model used in the simulations the rate of decay of dielectric withstand (RDDS) is set to have the same value as the RRDS. In the description of the VCB model [7] prestrikes are not treated, and therefore it was decided to examine the RDDS to see if it has the same value as the RRDS. In appendix F the RDDS in the VCB have been calculated. On the CD the fulle appendix F is found, this contains the pictures and data used in the calculation, the result of the calculations is seen in appendix F in the report. The calculations have only been done at voltage level 5.75kV for the system using the 10m cable, due to the experiences made when calculating Laboratory Tests and Results 53 HTTP1L10C1x05Dt2−7V6,9kIN9.lvm Voltage[V] 10000 5000 0 −5000 5500 5510 5520 5530 5540 5550 5510 5520 5530 5540 5550 Current[A] 100 50 0 −50 −100 5500 Time[us] Figure 5.13: The plot shows the voltage across the breaker channels and the current through the breaker when during 4 prestrikes. The test is made with 10m cable and at a breaking angle of 202.5◦ . the RRDS. Table F.1 show the results of the calculations. As the results show the average value of the RDDS is found to be 147.1V /µs, this value is almost 4 times higher than the result of the RRDS which was found to be 37.88V /µs. This result points out a weakness of the used VCB model and shows a need of a VCB model where the RDDS is investigated and treated as a individual parameter. The results in table F.1 also show how the closing angle affects the number of prestrikes. This can be seen more clearly from table 5.6 where some results from table F.1 have been picked out and arranged according to the closing angle. As seen from table 5.6 the closing angle has the opposite effect Test nr. Clos. angle[◦ ] Prestrikes 9 0 0 8 67.5 3 7 90 6 3 112.5 4 4 180 2 5 202.5 4 10 270 6 6 316 2 Table 5.6: The table shows the relation between the opening angle and the number of prestrikes of the vacuum arc. The results are from the tests made at 5.75kV using the 10m cable. on the number of prestrikes than the breaking angle has on the number of 54 5.6 Closing the circuit HTTP1L10C1x05Dt1−6V6,9kIN1.lvm HTTP1L10C1x05Dt1−6V6,9kIN3.lvm 10 8 6 0 −10 2 Current[A] Current[A] 4 0 −2 −4 −20 −30 −6 −40 −8 −10 0 10 20 30 40 50 Time[ms] (a) Breaking angle 0◦ −50 0 10 20 30 40 50 Time[ms] (b) Breaking angle 270◦ Figure 5.14: The plots shows the current through the breaker when closing the circuit at 0◦ and at 270◦ , both measurements are made with 10m cable. reignitions. Table 5.6 shows that when closing the breaker at low voltage and high current the number of prestrikes is low and when closing the VCB at high voltage and low current the number of prestrikes is high. 5.6.2 Current During Closing The current during the closing operation of the breaker is expected to be of the same shape as found in the example in chapter 2. In figure 5.14 the current transients generated by an closing operation, with closing angles of 0◦ and 290◦ is seen. As seen from figure 5.14a the exponential transient term becomes almost zero and the current follows the power frequency current immediate after separation, when the closing angle is 0◦ . In figure 5.14b the closing angle is 270◦ this means that the exponential transient term will obtain its maximum starting value and after separation lead the current towards the steady state current. As figure 5.14 shows the current after the closing operation consist of the exponential transient term and the steady state term, as explained in chapter 2. But as seen in figure 5.14, a higher frequency term is also affecting the current just after contact separation. This term is caused by the same phenomena that causes the TRV and the oscillating term will have a constant frequency dependent of the inductances and capacitances in the system. The frequency of the oscillating transient caused by the closing operation can be found by using equation 2.14, which is also used to find the frequency of the TRV. The inductance of the system is the same as in the opening case, but now the load capacitance (0.5µF ) becomes the dominant capacitance. Laboratory Tests and Results 55 HTTP1L100C1x05Dt1−6V6,9kIN3.lvm HTTP1L10C1x05Dt1−6V6,9kIN3.lvm 20 8 0 6 −20 4 Current[A] Current[A] −40 2 0 −2 X: 13.47 Y: −1.953 −4 −80 −100 −120 X: 10.36 Y: −4.297 −6 −60 X: 34.52 Y: −125 −140 −8 X: 31.63 Y: −143.8 −160 −10 0 10 20 30 40 Time[ms] 50 −180 0 10 20 30 40 50 Time[ms] (a) 10m cable (b) 100m cable Figure 5.15: The plots shows the current through the breaker when closing the circuit at 0◦ and at 290◦ . Data measurements are set in order to calculate the frequency of the oscillating transient. This means that the frequency of the oscillating transient should be almost simular for the two cable lengths. In this case we will say that the load capacitance is the only capacitance in the system and the frequency is therefore expected to be fopen = 1 √ = 399.14Hz. 2 · π 0.318H · 0.5µF (5.2) In figure 5.15 data markers have been placed on the current curves and from the value of the data markers the frequency of the oscillating transient can be found. The frequency is only found in these two measurements, as the results from section 5.2 showed that the frequency of the oscillations is constant. The 2 frequencies is found to 1 = 390.63Hz 12.84ms − 10.28ms 1 = = 311.53Hz. 34.66ms − 31.45ms fopen10 = fopen100 The results shows that the frequency, for both cable lengths, is almost the same as the calculated frequency 399.14Hz. For the system using the 100m cable the frequency is more inaccurate. This is because the capacitance of the cable is larger in this system and thereby has a larger influence on the system. 56 5.6 Closing the circuit Chapter 6 Simulations To simulate the system it was decided to set up a simulation model in PSCAD. The VCB model that is used in the simulation of the system is described in [7]. The model uses the parameters found in chapter 5 to describe the behaviour of the VCB. In figure 6.1 the setup of the simulation model for the system is seen. Figure 6.1: Setup of the system representing the laboratory setup when using the 10m cable. The ideal voltage generator in the left side of the circuit represents the net voltage supplying the vario-transformer, the vario-transformer and the cable leading from the vario transformer to the HTT transformer. The inductance of 0.318H represents the HTT transformer, the value of the inductance is found by looking at the nominal load of the transformer. The impedance of the transformer is calculated to be Z = ex · 10kV 2 Vm2 = 0.1 · = 100Ω Sm 100kV A (6.1) The factor ex , is the short-circuit impedance of the transformer, this value is set to be purely resistive and its value is set to 0.1. The inductance of the 58 6.1 Opening the Vacuum Circuit Breaker transformer can now be found. Z = 2 · π · f · L ⇒ L = 0.318 (6.2) The capacitance of 1575.7pF represents the 10m cable, the value of the capacitance is found according to table 4.1. The box called BRK is the model of the VCB where the values found in chapter 5 are inserted in order to represent the VCB used in this project. The box over the VCB called T imedBreakerLogicClosed@t0 is the control of the VCB, the box enables the user to open or close the VCB at a specific time. The capacitance of 0.5µF and the resistance of 10M Ω is the load and the discharging resistance. The signals Eload , Etrans and Iout correspond to the voltage and current measurements from the laboratory setup and the small boxes over the system handles the plotting of the simulation results. The measurement Ea is the voltage across the VCB contacts. 6.1 Opening the Vacuum Circuit Breaker In the first simulations made with the described system, a breaker opening is simulated. The breaking time is set to be 50ms, which should give a breaking angle of 180◦ (measured on the voltage) and should result in some reignitions of the breaker and a large amplitude of the TRV, as observed in the laboratory measurements. In figure 6.2 the simulation is seen. As seen from the simulation the current does not break at 50ms as expected, instead the vacuum arc remains and the current is not interrupted before it crosses zero at 55ms. It was discovered that this problem arises due to the current chopping level. The parameters used to find the current chopping level in the model of the VCB are α = 6.2 · 10−16 s and β = 14.2. These parameters should give a chopping level that is more than enough to chop the current as soon as the VCB contacts separate. It was tried to change the time of contact separation, to see if the arching time had any influence on the chopping level in the simulation model. It was discovered that if the VCB opens at current maximum or minimum the chopping level is set to zero. Therefore the time of contact separation was set to 0.49ms, the results of running the simulations with the new opening time of the VCB is seen in figure 6.3. As figure 6.3 shows the VCB has a current chopping level of 0.0005A for this current, and a oscillating TRV is created when the current is interrupted, when the oscillation is damped, the voltage between the VCB contacts follows the transformer side voltage as expected, with opposite sign due to the orientation of the measurement of Ea . The damping time of the oscillation is around 10ms, in the tests with the 10m cable the damping time was only 1ms. The reason for this difference is probably the lack of detail in the simulation model. Simulations 59 Simulation of VCB opening TRV[kV] 10 0 −10 −20 52 54 56 58 60 62 64 66 68 54 56 58 60 62 64 66 68 −4 Current[A] 5 x 10 0 −5 −10 −15 52 Time[ms] Figure 6.2: Simulation of opening the VCB with the constants found and described in chapter 5. The breaker opens at angle of 180◦ , but current is not interrupted before 270◦ . The simulation uses the parameters for the 10m cable. Simulation of VCB opening TRV[kV] 10 0 −10 −20 52 54 56 58 60 62 64 66 68 54 56 58 60 62 64 66 68 −4 Current[A] 5 x 10 0 −5 −10 −15 52 Time[ms] Figure 6.3: This simulation shows the TRV created by an opening operation, the current is interrupted just before 270◦ . The simulation is for the system using 10m cable 60 6.1 Opening the Vacuum Circuit Breaker It was expected to see some reignitions of the vacuum arc, but this is not seen in the simulation model. The reason why no reignitions occur is that the TRV never exceeds the dielectric withstand of the VCB. As mentioned before the lack of detail in the simulation models of the different components results in a TRV that is not the same as the measured TRV. Therefore it was decided to use the pi-equivalent circuit model for the cable, to try and improve the model. This model includes also the inductance and the resistance of the cable from table 4.1. The setup of the new simulation model is seen in figure 6.4. Figure 6.4: Setup of the system representing the laboratory setup when using the pi-equivalent circuit model and the parameters for the 10m cable. Using the pi-equivalent circuit to model the cable does not make any changes to the simulation results, the result is still the same as in figure 6.3, with a damping time of around 10ms. In figure 6.5 a graph of the TRV under the opening process is shown together with the dielectric withstand of the VCB. The parameters used to describe the dielectric withstand is set to A = 37.88V /µs and B = 0 according to the calculations from section 5.4. It can be seen from figure 6.5, that the problem of the simulations is found in the shape of the TRV created by the breaking operation. To try and force a reignition of the VCB, the opening time of the VCB was moved very close to the time of current chopping, but the amplitude of the TRV does not get a value that is high enough to make the TRV exceed the dielectric withstand of the VCB. The difference between the tests and the simulation model is that, as soon as the VCBs contact seperate in the real tests the current is chopped and the TRV starts rising. This causes reignitions of the vacuum arc. In the simulation the current is not chopped at the time of seperation and the dielectric withstand becomes too high for reignitions to occur. The simulation model of the VCB is a closed model and its source code cannot be seen. Therefore it is not possible to investigate the problem of the current chopping level further. The results of the simulations suggest that the VCB model always sets the current chopping level under the current level. This would explain why the current is not chopped immediately Simulations 61 Simulation of VCB opening 25 TRV Breaker withstand voltage 20 TRV[kV] 15 10 5 0 −5 53.8 53.9 54 54.1 54.2 54.3 54.4 54.5 54.6 Time[ms] Figure 6.5: The simulation shows the TRV and the dielectric withstand of the VCB. As seen the time of seperation has been moved to 54ms (270◦ ) to try and force reignitions. after contact seperation. In order to analyse the problem, the VCB model should be tested at a higher current level. Another step of improving the simulation model would be to use the PSCAD cable model to describe the cable and to transform an already made Simulink model of the HTT transformer to a PSCAD model in order to get a more precise model of the system. These opportunities were investigated, but they were found to be too time consuming to be included in this project. The VCB model should also be tested at other current levels to see if the problem with the chopping level is a fault in the model or a result of the low current level of the VCB. Instead it was decided to continue using the circuit in figure 6.4 and only analyse the frequency of the TRV and effect of breaking angle during the opening operation. As mentioned, figure 6.3 shows the simulated TRV in the system using a 10m cable. In figure 6.6 the result of a simulation, using the parameters for the 100m cable is seen. The simulation opens the VCB contacts after 49ms. Again it is seen that the current does not get chopped at contact seperation but a vacuum arc conducts the current and it is not extinguished before the current chopping level, set by the simulation model, is reached at 55ms. Figure 6.6 shows that the damping problem in the simulation model becomes more significant when simulating the 100m ca- 62 6.1 Opening the Vacuum Circuit Breaker Simulation of VCB opening TRV[kV] 10 0 −10 −20 52 54 56 58 60 62 64 66 68 54 56 58 60 62 64 66 68 −4 Current[A] 5 x 10 0 −5 −10 −15 52 Time[ms] Figure 6.6: Simulation of opening the VCB in the system with 100m cable, the current is interrupted at 270◦ . ble. The TRV created by the breaking process continues to oscillate without any damping, where the test result showed that the oscillation in this setup would be completely damped after around 2.3ms. These simulation results again show the need for a better simulation model of the circuit components. 6.1.1 Frequency analysis The frequency of the performed simulations was measured in order to make a comparison of the calculated frequencies and the measured frequencies. In figure 6.7 the simulations and data points for the frequency calculations are seen. Using this data the frequencies of the TRV for the two cable lengths were found to 1 = 7149Hz 54.4ms − 54.25ms 1 = = 2272Hz 54.92ms − 54.48ms fT RV 10 = fT RV 100 These results correspond to the data found in chapter 2 where a circuit representing a transformer and a cable where disconnected from a capacitive load. The frequencies found in the measurements where fT RV 10 = 8708, 92Hz and fT RV 100 = 2953, 87Hz. The difference in simulated and measured frequency can be seen as a result of the lack of detail in the simulation model, as already described. Simulations 63 Simulation of VCB opening 5 X: 54.26 Y: 4.362 Simulation of VCB opening 1.5 X: 54.4 Y: 4.223 4 1 3 0.5 TRV[kV] TRV[kV] 2 X: 54.92 Y: 1.332 X: 54.48 Y: 1.245 1 0 −1 0 −0.5 −2 −3 −1 −4 −5 54 54.5 55 55.5 56 −1.5 54 54.5 Time[ms] 55 55.5 56 Time[ms] (a) 10m cable (b) 100m cable Figure 6.7: The two plots shows the TRV generated in the system using 10m and 100m cable. For both simulations the breaking angle is 270◦ . Simulation of VCB opening 5 4 4 3 3 2 2 TRV[kV] TRV[kV] Simulation of VCB opening 5 1 0 −1 1 0 −1 −2 −2 −3 −3 −4 −4 −5 44 44.5 45 45.5 46 −5 54 Time[ms] (a) VCB contacts separates at 40ms 54.5 55 55.5 56 Time[ms] (b) VCB contacts separates at 50ms Figure 6.8: The simulation shows the TRV when the VCB is set to open at 39ms and 49ms which results in breaking angles of almost 90◦ and almost 270◦ . 6.1.2 Analysis of breaking angle As the current chopping level in the simulations cannot be changed, the breaking angle can only obtain two values. The two possible breaking angles of the voltage lay just before 90◦ or just before 270◦ . In the simulations already made the opening time of the VCB has been set to 49ms which gives a breaking angle of almost 270◦ and to obtain the breaking angle of almost 90◦ the opening time of the VCB was set to 39ms. Figure 6.8 shows the result of the simulations performed with the two opening times. The two simulations in figure 6.8, results in a TRV with the same amplitude but 64 6.2 Closing the Vacuum Circuit Breaker Simulation of VCB closing −3 Simulation of VCB closing 3 x 10 0.015 2 0.01 Current[A] Current[A] 1 0.005 0 −0.005 X: 51.23 Y: −0.003063 X: 58.37 Y: −0.008888 54 −1 −2 X: 55.9 Y: −0.009806 −0.01 −0.015 52 0 56 58 60 X: 53.74 Y: −0.002395 −3 62 Time[ms] (a) 10m cable 64 66 68 −4 42 44 46 48 50 52 54 56 58 Time[ms] (b) 100m cable Figure 6.9: The two plots shows simulations of closing the VCB with both cable lenghts. The data markers are used to find the frequency of the oscillating transients. The closing angle of the VCB is 270◦ for plot a and 180◦ for plot b. with different sign. This is similar to the results obtained in the laboratory tests, where breaking angles that are 180◦ apart have the same amplitude but with different sign. 6.2 Closing the Vacuum Circuit Breaker When closing the VCB model, the slow transients, described in chapter 2, the fast oscillating transients, described in section 5.6.2 and prestrikes of the vacuum arc, that were seen in section 5.6.2, can be seen from the simulation results. In this section the frequency of the oscillating transients will be calculated and an analyse of the prestrikes will be made. During the simulations of the closing operation it was discovered that the prestrikes in the VCB only occurs when the pi-equivalent model of the cable was used. This emphasises the importance of the level of detail in the simulation model. 6.2.1 Frequency of Oscillating Transient The frequency of the oscillation transient is expected to be around 400Hz. Figure 6.9 shows a plot of the oscillating transient for both cable lenghts, the frequency of the two setups can be found using the data markers seen on figure 6.9 Simulations 65 Simulation of VCB closing Voltage[kV] 15 Voltage between VCB contacts Breaker withstand voltage 10 5 0 −5 55.2 55.3 55.4 55.3 55.4 55.5 55.6 55.7 55.8 55.5 55.6 55.7 55.8 −3 Current[A] 5 x 10 0 −5 −10 55.2 Time[ms] Figure 6.10: The plot shows the voltage between the VCB contacts and the current through the VCB just before the VCB contacts meet. As the plot shows, prestrikes of the VCB occur. 1 = 411.35Hz 58.372msb − 55.941ms 1 fT RV 100 = = 399.2Hz 53.74ms − 51.235ms fT RV 10 = As these results show the two frequencies are both very close the expected frequency of 400Hz. The calculations shows that the frequencies are not the same for both cable lenghs, this is as mentioned earlier because the capacitance and inductance in the system changes a bit when changing the cable. But since the load capacitance 0.5µF is the dominant capacitance in the system, the change of cable will not have a very large effect on the frequency of the oscillations. 6.2.2 Prestrike simulation A look at what happens very close to the time where the two VCB contacts meet, shows that some prestrikes occur in the simulation results. These prestrikes take the same shape as expected, and force the voltage betweeen the VCB contacts to go to zero and after the vacuum arc extinguishes. In figure 6.10 simulated prestrikes from the system using a 10m cable are seen. The simulation shown in figure 6.10 is made with a cable length of 10m and at a closing angle of 270◦ . When the voltage between the VCB contacts goes to zero, because of a restrike, the current starts oscillating. These oscilla- 66 6.2 Closing the Vacuum Circuit Breaker Simulation of VCB closing Simulation of VCB closing 3 9 8 2.5 7 6 Voltage[kV] Voltage[kV] 2 1.5 1 5 4 3 2 0.5 1 0 0 −0.5 50.6 50.7 50.8 50.9 51 51.1 51.2 Time[ms] (a) Closing angle 180◦ 51.3 51.4 −1 55 55.1 55.2 55.3 55.4 55.5 55.6 55.7 55.8 Time[ms] (b) Closing angle 270◦ e Figure 6.11: The two plots shows simulations of closing the VCB at different times, iin the system using the 10m cable. As seen the two different closing angles causes a different number of prestrikes. tions are quenched very fast and the voltage between the contacts are led smoothly back to the previous level. This process repeats it self when more prestrikes occur. The voltage plot on figure 6.10 also shows how the dielectric withstand of the VCB decays and as expected the prestrikes occur when the voltage between the VCB contacts exceeds the dielectric withstand. The RDDS can be calculated from the plot and is found to be A = 37.88V /µs, the same value as the inserted value of RRDS. The VCB contacts start moving together at 55ms and are fully together at 55.55ms, this gives a closing time of the VCB of 0.55ms. This time is not adjusteble in the model and can therefore not be set to the value found in the laboratory tests. In order to investigate if the number of prestrikes were dependent on the closing angle of the VCB, a number of simulations were made. The relation between the number of prestrikes and the closing angle was found to be the same as in the laboratory tests and in figure 6.11 two simulations of a closing operation are seen. As seen from the plot in figure 6.11, a closing angle of 180◦ on the voltage gives few prestrikes, in this case 1, and a closing angle of 270◦ gives more prestrikes, in this case 4. So as found in the laboratory tests, high voltage between the VCB contacts when a closing operation is started gives many prestrikes and a little voltage between the contacts gives few prestrikes. Chapter 7 Discussion The results obtained in the project will be discussed and compared in this chapter. First a description of the measurements and calculations, made in order to find the VCB model parameters will be given. Then a description and comparison of the calculated, measured and simulated results when opening and closing the VCB is given. Finally a description of the further work needed, in order to determine the model parameters of the VCB and the further work on the simulation model, will be given. 7.1 Voltage Circuit Breaker Model Parameters The parameters used to model the VCB in the PSCAD simulation model, were found based on a series of tests. The result of these tests were analysed and from these analyses the parameters were calculated. The chopping current was the first parameter of the VCB model that was treated. The current chopping phenomena were hard to observe at high voltage levels because of the high current transients created at these levels. At lower voltage levels the chopping effect was seen quiet clearly and an attempt on calculating the current chopping level of the VCB was made. But since the laboratory setup conducts a current which is under the current chopping level of the breaker the value of the parameters α and β could not be determined for this breaker. The parameters of α and β were therefore chosen to standard values, which should give a current chopping level of 3A-8A in the simulation model. An analyse of the reignitions of the vacuum arc was made in order to determine the dielectric withstand of the VCB. As expected the circuit configuration changed the number of restrikes of the vacuum arc, when using the 100m cable few reignitions were created and when using the 10m cable 68 7.2 Opening the Vacuum Circuit Breaker many reignitions were created. The analyse of the reignitions showed that the VCB has a RRDS of 37.88V /µs. This value corresponds to the suggested value range of RRDS when testing VCBs. The value of the RRDS gives a maximum dielectric withstand of the vacuum between the VCB contacts of 30.43kV /mm. In [8] the dielectric withstand of vacuum is stated to be between 20kVrms /mm and 30kVrms /mm. The rms value in this project is 21.52kVrms /mm, therefore found value of the RRDS of the VCB seems to be acceptable. The HF quenching capability of the VCB was also examined and two methods of determening the simulation parameters were used. The methods gave very different and varying results. When the HF quenching capability is considered to be constant its values should lay between 100A/µs and 600A/s, which indicate that the result found in this project is wrong. The difference between the calculated value and the expected value, is most likely to be caused by the current level in the system, and it is expected that tests conducting larger currents will give better results of the HF quenching capability of the VCB. Due to this, the value of the HF quenching capability was set to be 350A/s in the simulation model. The prestrikes during a closing operation of the VCB were also observed and the RDDS of the VCB was calculated. The value of RDDS is calculated in the same way as the value of RRDS and the RDDS of the VCB was found to be 147.1V /µs. However it is not possible to set the RDDS in the simulation model, the value of the RDDS will be set to the the value of the RRDS, 37.88V /µs. When inserting the found and decided parameters in the VCB model and inserting the model in the simulation model of the laboratory setup it was expected to observe the phenomena, that is described by the VCB theory and is also seen from the test results. 7.2 Opening the Vacuum Circuit Breaker The TRV that arises in the system, after a breaking operation, was observed in both the laboratory tests and in the simulations of the system. In chapter 2 the expected frequency of the TRV was calculated based on the capacitance of the cable and the inductance of the HTT transformer. The results of these calculations were fT RV 10 = 7110Hz and fT RV 100 = 2248Hz. A comparison of the TRV found in the laboratory and the TRV found in the simulations is seen in figure 7.1. As figure 7.1 shows the measured frequency and the simulated frequency for the system using 10m cable are almost similar, and have been calculated to 8708, 92Hz for the measurements and 7149Hz for Discussion 69 Simulation of VCB opening TRV[kV] 5 0 −5 54 54.5 55 55.5 56 56.5 Measurement of VCB opening TRV[kV] 2 1 0 −1 −2 3.5 4 4.5 5 5.5 6 Time[ms] Figure 7.1: Comparison of the simulated and the measured results of at VCB opening, when the breaking angle is 270◦ and the 10m cable is used. the simulations. When using the 100m cable the frequency of the TRV have been calculated to 2953, 87Hz for the measurements and 2272Hz for the simulations. As the results shows the simulated value is almost equal to the value calculated, whereas the measured result is a bit different. This difference between the measured result and the simulated/calculated result comes from the lack of detail in the simulation/calculation model. In order to improve this a more detailed model of both transformer and cable, should be used in further work with the simulation model. As figure 7.1 shows the simulation does not apply the right damping to the system, the measured damping time of the TRV, using the 10m cable, is 1ms whereas the simulation gives a damping time of 10ms. This is also caused by the lack of detail in the simulation model. The damping problem of the simulation model gets worse when switching from the 10m cable to the 100m cable, where almost no damping is applied to the TRV. When simulating a opening operation of the VCB it was expected to observe some reignitions of the vacuum arc, but no reignitions were seen. It was found that these problems were caused by the current chopping level of the VCB. In the laboratory tests the current is chopped immediately after the contact seperation, since the current level in the tests is under the current chopping level of the VCB. This was also expected in the simulation, but in the simulation the current chopping level is set to be 0.0005A 70 7.3 Closing the Vacuum Circuit Breaker with the used values of α and β, where a current chopping level of 3A-8A is expected. Since it is not possible to see the source code of the simulation model a investigation of the problem could not be made. But the results suggest that the current chopping level in the VCB model is always set to be under the current level. As explained in the report the rate of rise of the TRV is a very important parameter in the generation of reignitions of the vacuum arc. Therefore it is important that the simulation model gives a correct TRV according to the laboratory measurement, when studying reignitions. When the problems with the current chopping level is solved the simulation model might be good enough to make a study of reignitions of the vacuum arc. But in order to get the best results, the problems with the simulation of the TRV should be solved, this is done by using more accurate models of the transforemr and the cable. PSCAD has a cable model that could be applied in the simulation setup, a detailed model of the HTT transformer is already made in Simulink, this model should be transformed to a PSCAD model and used in the simulation. 7.3 Closing the Vacuum Circuit Breaker The measurements taken during a VCB closing operation show that the exponential transient term is affecting the current through the VCB in the way described in section 2.1. The result of two tests is shown in figure 5.14, one where the VCB closes at 270◦ and one where the VCB closes at 0◦ . When the VCB closes at a angle of 90◦ or 270◦ the exponential transient will have maximum effect and when the VCB closes at angles of 0◦ or 180◦ the exponential transient will have minimum effect. When closing the VCB some fast oscillations occure due to the capacitances and the inductances of the system. The frequency of these oscillations is found in the same way as the frequency of the TRV. But when the circuit is closing the dominant capacitance of the system becomes the load and the frequency of the oscillations have been calculated considering the load capaticance to be the only capacitance of the system. The frequency of the oscillations have been calculated to 399.14Hz for both cable lenghts. When examining the system using the 10m cable a frequency of 390.63Hz is found from the measurements and a frequency of 411.35Hz is found in the simulations. And when using the 100m cable a frequency of 311.53Hz is found from the measurements and a frequency of 399.2Hz is found in the simulations. As seen the measured frequencies and the simulated frequencies are very similar, only the measurement using the 100m cable is a bit different. The reason for this is that the capacitance and inductance of the 100m cable Discussion 71 Simulation of VCB closing Voltage[kV] 10 5 0 −5 55 55.2 55.4 55.6 55.8 56 Measurement of VCB closing Voltage[kV] 10 5 0 −5 5.2 5.25 5.3 5.35 5.4 Time[ms] Figure 7.2: Comparison of prestrikes in simulation and measurement, both plots, shows the voltage between the VCB contacts. The system uses the 10m cable and have a closing angle of 270◦ . affects the system and the load capacitance is not as dominating as when the 10m cable is used. When simulating a VCB closing operation it was possible to observe the prestrikes that occur in the VCB. When a prestrike occurs in the simulation it forces the voltage between the contacts to jump to zero and causes a oscillating HF current. Figure 7.2 shows a plot of the voltage between the VCB contacts from simulation and from the measurement, during a closing operation of the VCB. Figure 7.2 shows a clear connection between the measured prestrikes and the simulated pretrikes. In both cases the voltage drops to zero when a restrike occurs, the created vacuum arc extinguishes almost immediately and the voltage between the contacts is smootly led back to its previous level. The opening time of the VCB and the RDDS are not variable parameters in the VCB model, this means that the simulation of restrikes is not as precise as desired. The simulation has a fixed closing time of 0.55ms where the actual closing of the VCB was measured to be 12ms. The RDDS of the VCB model is set to have the same value as the RRDS, and in this case 37.88V /µs where the RDDS measured on the VCB was found to be 147.1V /µs. This means that the voltage in the simulations, does not reach the right level when recovering after a prestrike, since the slope of the dielectric withstand 72 7.4 Further Work is too low. The simulation of the prestrikes showed the same dependency of closing angle as found in the measurements. Closing angles at high voltages gives many prestrikes and closing angles at low voltages gives few prestrikes. In figure 6.11 this is shown by simulating a closing angle of 180◦ (voltage zero crossing) and 270◦ (voltage maximum) these simulations give 1 and 4 prestrikes respectively. This also shows that 4 is the maximum number of prestrikes in the simulation, the measured results showed a maximum number of 6 prestrikes (at angle 270◦ ). The difference in the maximum number of prestrikes for the measurements and for the simulations can be seen in figure 7.2. This difference comes from the difference in closing time and the differene in RDDS between the real VCB and the simulation model of the VCB. The prestrikes of the VCB can only be simulated in the simulation model that is using the pi-equivalent model of the cable. This fact shows the importance of a precise simulation model and it suggestes to improve the model of the transformer and the cable as already described. The fact that it is possible to simulate the prestrikes in the VCB model, support the theory that the current chopping level is the reason why the restrikes of the VCB cannot be simulated. 7.4 Further Work The results of this project shows the need of some further work, both on the laboratory setup and on the simulation model. In order to determine the current chopping level and the HF quenching capability of the VCB, some test at a higher current level than used in this project are needed. The ideal scenario would be tests conducting the nominal current of the VCB 1250A. If this is not possible, tests with a current of at least 8A − 10A (expected current chopping level) should be applied. Tests done with these currents should make it possible to find the values of α and β and with the right values of these parameters the simulation model should be able to produce restrikes, HF currents etc. From tests with higher currents it is also expected that a more precise value of the quenching capability of the VCB can be found. The simulation model also requires some further work in order to fully represent the laboratory setup. In this project the laboratory setup has been represented by lumped circuit element, in order to improve the model this should be improved. The HTT transformer has already been modelled in Simulink in a previous project, so in order to improve the model used in this Discussion 73 project the Simulink model could be transformed to a PSCAD model and used. In order to improve the representation of the cable, a PSCAD cable model should be used. The above improvements should make it possible to fully test the VCB model. These tests will determine if the model is fulfilling its purpose or if changes in the model are required. Changes to the VCB model could be introducing the RDDS, the opening time and the closing time as variable parameters. 74 7.4 Further Work Chapter 8 Conclusion This project has investigated the generation of high voltage transients from a vacuum circuit breaker (VCB). The investigation has concerned with theoretical research, expermential tests and simulations studies. The different physical phenomena of a VCB were investigated, the current chopping level, the dielectric strength and the HF quenching capability. These phenomena are all described using a mathematical model and the model includes parameters which determine the behaviour of the specific VCB. Methods for finding the parameters from test results wer determined and a series of tests were performed on the VCB. The result of the tests showed that a transient recovery voltage (TRV) is created when the VCB is opened. The frequency of the TRV was found to be dependent of the network setup and when using a 100m cable the frequency was found to be 2953, 87Hz where the 10m cable gave a frequency of 8708, 92Hz. It was shown that the amplitude of the TRV is dependent of the VCB breaking angle. The rate of rise and the amplitude of the TRV were found to have a big influence on the behaviour of the VCB during current interruption. The two parameters play a big role in the creation of restrikes in the VCB, the reignitions in the VCB are created whenever the dielectric strength is exceeded by the TRV. The rate of rise of dielectric strength (RRDS) during an opening operation was found to be 37.88V /µs. The parameters for determening the current chopping level could not be found, as the current in the test setup was under the current chopping level of the VCB. An attempt of finding the HF quenching capability of the VCB was made, but the result was very varying, which is also expected to be because of the low currents level in the tests. The parameters of the current chopping and the HF quenching capability were therefore set to standart values in the simulations. 76 Measurements were also taken during closing operations of the VCB, these measurements showed an exponential current transient and a faster oscillating transient, as expected. The frequency of the fast oscillating transient was expected to be 399.14Hz for both cable lenghts and was found to be 390.63Hz when the 10m cable was used and 311.53Hz when 100m cable is used. On the measurement of the closing operation, prestrikes of the vacuum arc was observed and the RDDS of the VCB was calculated to be 147.1V /µs. The parameters of the VCB model were inserted in a PSCAD model of a VCB. The model of the VCB is used in a simulation model that represents the complete laboratory setup. The simulation results in a TRV with a frequency of 7149Hz for the system with 10m cable and 2272Hz for the system using 100m cable. During the simulations it was discovered that the level of the current chopping is always set to be smaller than the current in system, this meant that the simulations could not reproduce the restrikes of the vacuum arc seen in the VCB tests. The simulation of a closing action of the VCB, shows the exponential transient, the oscillating transients and the prestrikes of the VCB. The RDDS of the VCB found from the tests results cannot be inserted in the PSCAD model of the VCB, the PSCAD model uses the value of the RRDS as the value of the RDDS. In order determine the parameters for modelling the current chopping level and the HF quenching capability, new tests at higher current level should be made. In order to get more precise simulation results an improvement of the simulation model is also required. Bibliography [1] Tarik Abdulahovic. Analysis of high-frequency electrical transients in offshore wind parks. Master’s thesis, Chalmers University of Technology, Department of Energy and Environment Division of Electric Power Engineering, 2009. [2] D.J.Clare. Failures of encapsulated transformers for converter winders at oryx mine. Electron Magazine, March 1991. [3] J. Duncan Glover and Mulukutla S. Sarma. Power System Analysis and Design. The Wadsworth Group, 3th edition, 2002. [4] Allan Greenwood. Electrical Transients in Power Systems. John Wiley and Sons, inc, 2th edition, 1991. [5] Allan Greenwood. Vacuum Switchgear. The institution of Electrical Engineers, 2th edition, 1997. [6] J. Helmer and M. Lindmayer. Mathematical modeling of the high fiequency behavior of vacuum interrupters and comparison with measured transients in power systems. XVIIth International Symposium on Discharges and Electrical Insulation in Vacuum,, July. 1996. [7] Rao Kondala and Gajjar Gopal. Development and application of vacuum circuit breaker model in electromagnetic transient simulation. IEEE Power India Confrence, 2006. [8] F. H. Kreuger. Industrial High Voltage: Fields/Dielectrics/Constructions. Ios Pr Inc, 3th edition, 1991. [9] Morten Lerche. Optimization of laboratory setup for determination of breaker characteristics. Msc prepatory project, Technical University of Denmark, 2008. 78 BIBLIOGRAPHY [10] A. Mazur, I. Kerszenbaum, and J. Frank. Maximum insulation stresses under transient voltages in the hv barrel-type winding of distribution and power transformers. IEEE Transactions on Industry Applications, 1988. [11] Örn I. Björgvinsson. Theoretic and experimental investigations of switching transients in wind turbines. Msc project, Technical University of Denmark, 2006. [12] Siemens. 3ah vacuum circuit-breakers. Medium-Voltage Equipment, Catalog HG 11.11, 1999. [13] Rene Peter Paul Smeets. ow-current behaviour and current chopping of vacuum arcs. Proefschrift, Technische Universiteit Eindhoven, 1987. [14] W. Sweet. Danish wind turbines take unfortunate turn. Spectrum, IEEE, November 2004. [15] Lou van der Sluis. Transients in Power Systems. John Wiley and Sons, inc, 1th edition, 2002. [16] S.M. Wong, L.A. Snider, and E.W.C. Lo. Overvoltages and reignition behaviour of vacuum circuit breaker. International Conference on Power System Transients, 2003. List of Figures 2.1 An sinusoidal voltage is switched on an RL-circuit. . . . . . . 6 2.2 The sinusoidal voltage is switched on to the RL-circuit with a switching angle of 90◦ . . . . . . . . . . . . . . . . . . . . . . 8 The sinusoidal voltage is switched on to the RL-circuit with a switching angle of 0◦ . . . . . . . . . . . . . . . . . . . . . . 9 2.4 An sinusoidal voltage is switched on an RL-circuit . . . . . . 10 2.5 The figure shows the voltage on the transformer side of a VCB under a opening operation in a circuit with a capacitive load. 11 The design principle of a VCB, showing contacts, arching chamber and insulation, the picture is taken from [12] page 8. 15 A vacuum interrupter with slits in the contacts to avoid uneven erosion of the contact surface, this picture is from [15] page 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 The figure shows the current during an opening of the breaker. As seen on figure b the current chops around the value 0,005 and jumps to zero. . . . . . . . . . . . . . . . . . . . . . . . . 18 The figure shows 5 reignitions of the vacuum arc during contact seperation. When the reignitions occur the TRV jumps to zero. The red line shows the RDDS of the circuit breaker. 19 The figure shows 3 reignitions of the vacuum arc during contact separation. The figure also shows the high frequency currents caused by the arc. . . . . . . . . . . . . . . . . . . . 20 The figure shows the HF currents caused by 5 reignitions. The last current cannot be quenched at a zero crossing and therefore the arc is maintained until the next zero crossing of the current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 2.3 3.1 3.2 3.3 3.4 3.5 3.6 80 LIST OF FIGURES 3.7 Multible reignitions lead to unsuccessful interruption of the current at first current zero. . . . . . . . . . . . . . . . . . . . 22 The figure shows 4 reignitions of the vacuum arc during contact separation. The figure also shows the high frequency currents caused by the arc. . . . . . . . . . . . . . . . . . . . 24 The laboratory setup including high voltage components and the control and measurement system . . . . . . . . . . . . . . 26 4.2 Screenshot of the LabVIEW program. . . . . . . . . . . . . . 29 4.3 The two pictures show how the probes are fastened to the setup. Before this was done the probes were connected loosely to the setup by the hooks on the tip of the probes. . . . . . . 31 The plots show the voltage measured on the transformer side probe, before and after fastening the probe. At around 30ms oscillations can be seen on figure a. . . . . . . . . . . . . . . . 31 3.8 4.1 4.4 4.5 The picture shows the Rogowski current transducer. In order to improve the current-to-noise ratio the current measurement is led through the Rogowski coil 4 times as seen on the picture 32 5.1 Closing the VCB at voltage level 6.9kV , the setup is using the 100m cable and the load with a capacitance of 0.5µF . The time between the measurements ∆t is 1 · 10−6 s, and the closing angle is 0◦ . . . . . . . . . . . . . . . . . . . . . . . . . 35 The figure shows two plots of the distance between the VCB contacts, when the VCB is opening and closing. . . . . . . . . 36 The TRV across the breaker contacts using a 10m and a 100m cable. The breaking angle is in both cases 0◦ . . . . . . . . . . 38 The measurements for calculating the frequency of the TRV when using a 10m cable in the test. The breaking angle is again 0◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 The plots shows the current through the VCB at 5, 75kV using a 100m cable. The interruption is made at a breaking angle of 180◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 The plots shows the current through the VCB at 1, 15kV using a 100m cable. The interruption is made at a breaking angle of 45◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 The plots shows the voltage across the breaker contacts during an opening of the VCB. Both tests have a breaking angle of 225◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 The figure illustrates how the RRDS is calculated from the laboratory measurements. . . . . . . . . . . . . . . . . . . . . 45 5.2 5.3 5.4 5.5 5.6 5.7 5.8 LIST OF FIGURES 5.9 81 The plot shows how the reignitions of the VCB create a HF current that is superimposed on the power frequency current. The test is from the system with 100m cable and the breaking angle is 292.5◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 5.10 The plot shows how the reignitions of the VCB create a HF current that is superimposed on the power frequency current. The test is from the system with 10m cable and the breaking angle is 225◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 5.11 The plots shows the data markers used to calculate HF current quenching capacity of the VCB. . . . . . . . . . . . . . . 50 5.12 The plot shows the voltage across the breaker channels and the current through the breaker when during 3 prestrikes. The test is made with 100m cable and at a closing angle of 22.5◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 5.13 The plot shows the voltage across the breaker channels and the current through the breaker when during 4 prestrikes. The test is made with 10m cable and at a breaking angle of 202.5◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 5.14 The plots shows the current through the breaker when closing the circuit at 0◦ and at 270◦ , both measurements are made with 10m cable. . . . . . . . . . . . . . . . . . . . . . . . . . . 54 5.15 The plots shows the current through the breaker when closing the circuit at 0◦ and at 290◦ . Data measurements are set in order to calculate the frequency of the oscillating transient. . 55 6.1 6.2 6.3 6.4 6.5 Setup of the system representing the laboratory setup when using the 10m cable. . . . . . . . . . . . . . . . . . . . . . . . 57 Simulation of opening the VCB with the constants found and described in chapter 5. The breaker opens at angle of 180◦ , but current is not interrupted before 270◦ . The simulation uses the parameters for the 10m cable. . . . . . . . . . . . . . 59 This simulation shows the TRV created by an opening operation, the current is interrupted just before 270◦ . The simulation is for the system using 10m cable . . . . . . . . . . . . 59 Setup of the system representing the laboratory setup when using the pi-equivalent circuit model and the parameters for the 10m cable. . . . . . . . . . . . . . . . . . . . . . . . . . . 60 The simulation shows the TRV and the dielectric withstand of the VCB. As seen the time of seperation has been moved to 54ms (270◦ ) to try and force reignitions. . . . . . . . . . . 61 82 LIST OF FIGURES 6.6 Simulation of opening the VCB in the system with 100m cable, the current is interrupted at 270◦ . . . . . . . . . . . . . . 6.7 The two plots shows the TRV generated in the system using 10m and 100m cable. For both simulations the breaking angle is 270◦ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.8 The simulation shows the TRV when the VCB is set to open at 39ms and 49ms which results in breaking angles of almost 90◦ and almost 270◦ . . . . . . . . . . . . . . . . . . . . . . . . 6.9 The two plots shows simulations of closing the VCB with both cable lenghts. The data markers are used to find the frequency of the oscillating transients. The closing angle of the VCB is 270◦ for plot a and 180◦ for plot b. . . . . . . . . 6.10 The plot shows the voltage between the VCB contacts and the current through the VCB just before the VCB contacts meet. As the plot shows, prestrikes of the VCB occur. . . . . 6.11 The two plots shows simulations of closing the VCB at different times, iin the system using the 10m cable. As seen the two different closing angles causes a different number of prestrikes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 7.2 Comparison of the simulated and the measured results of at VCB opening, when the breaking angle is 270◦ and the 10m cable is used. . . . . . . . . . . . . . . . . . . . . . . . . . . . Comparison of prestrikes in simulation and measurement, both plots, shows the voltage between the VCB contacts. The system uses the 10m cable and have a closing angle of 270◦ . . . . 62 63 63 64 65 66 69 71 List of Tables 4.1 Cable parameters calculated at different frequencies [11] . . . 27 5.1 The table shows the relation between the breaking angle and the amplitude of the TRV. The results are from the tests made at 5.75kV using the 10m cable. . . . . . . . . . . . . . . . . . 40 The table shows the average RRDS, for the 6 analysed test series and the average value of the RRDS found for the two cable lengths. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 The table shows the relation between the breaking angle and the number of reignitions of the vacuum arc. The results are from the tests made at 5.75kV using the 10m cable. . . . . . 47 5.4 The average results of the calculations of C and D . . . . . . 50 5.5 The average results of D when considering di/dt to be constant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 The table shows the relation between the opening angle and the number of prestrikes of the vacuum arc. The results are from the tests made at 5.75kV using the 10m cable. . . . . . 53 B.1 Results of the long TRV. The calculations have been made for the test where the 10m cable is used and at a voltage level of 5,75kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 B.2 Results of the long TRV. The calculations have been made for the test where the 100m cable is used and at a voltage level of 5,75kV . . . . . . . . . . . . . . . . . . . . . . . . . . 90 C.1 Measurements and results of the current chopping analysis. The data is based on measurements with a load of 0.5µF , 100m cable and a voltage level of 1.15kV . . . . . . . . . . . 92 5.2 5.3 5.6 84 LIST OF TABLES C.2 Measurements and results of the current chopping analysis. The data is based on measurements with a load of 1.0µF , 100m cable and a voltage level of 1.15kV . . . . . . . . . . . D.1 The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 4.6kV . . . D.2 The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 5.75kV . . . D.3 The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 6.9kV . . . D.4 The table shows the calculation of the RRDS for the system using with 10m cable and have a voltage level of 4.6kV . . . . D.5 The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 5.75kV . . . D.6 The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 6.9kV . . . E.1 The results of the parameters C and D when expressing the HF current quenching capability as a linear function. All tests are made at voltage level 5.75kV in the system using the 100m cable. . . . . . . . . . . . . . . . . . . . . . . . . . . E.2 The results of D when considering the HF current quenching capability to be constant. Again all tests are made with 100m cable and at voltage level 5.75kV . . . . . . . . . . . . . . . . 92 94 94 95 95 96 96 98 98 F.1 The results of the Rate of decay of Dielectric Strength, the calculations are made on test results from the system using the 10m cable and voltage level 5.75kV . . . . . . . . . . . . 100 Appendix A Plotting results The measurements in the LabVIEW program are stored in a .lvm file, this file concists of six columns. The data stored in each column is • Column 1, contains the measurement number. • Column 2, the measurement from channel 4 on the oscilloscope (breaker position). • Column 3, the measurement from channel 1 on the oscilloscope (voltage, transformer side). • Column 4, row 1 the time of the trigging moment. • Column 5, the measurement from channel 2 on the oscilloscope (voltage, load side). • Column 6, the measurement from channel 3 on the oscilloscope (current). MATLAB is used to take the data out of the columns, process it and plot it in the desired way. Later in this appendix an example of how the results are plotted is shown, this file is also found on the CD. The concept of the MATLAB file is that it loads a directory containing a number of measurement results files, .lvm files. The .m file then processes all the measurement files and saves a picture of the plotted results. The .m file is modified in order to get the desired plot, these modifications can be a zoom of the x − axis, plotting the difference between the load side- and transformer side voltage in order to plot the TRV, etc. In order to use the matlab file P lot res.m to plot the measured results it is important that the file is placed in the right directory. The file must be in the same directory as the folders containing the .lvm files. The file plot.m 86 has two parameters that the user must change to get the wanted plots. The first one is step time, delta t, this number has to be set in order to get the right time on the x-axis. Delta t is calculated by the labview program when the measurements are taken and can also be seen in the filename of the .lvm file. The second parameter that can be changed by the user is the directory name. The name must be the name of the directory containing the .lvm files with the data for which a plot is wanted. If you have any problem plotting the results or have questions on how to modify the Matlab file you can send me an email and i’ll try and help you. The code of the matlab file P lot res.m is seen here 1 2 clc ; clear a l l ; 3 4 5 6 7 8 9 %Values t h a t has t o be s e t by t h e u s e r %−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− d e l t a t =2e −7; %The s t e p time D e l t a t cd ChoopingCurrent ; % Name o f t h e d i r e c t o r y with t h e ... results %−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− 10 11 12 %Loads a l l t h e measurements f i l e s from t h e d i r e c t o r y d=dir ( ’ ./*. lvm ’ ) ; 13 14 15 16 17 18 %G e n e r a t e s a f o r −l o o p t h a t run through a l l t h e f i l e s f o r k=1: length ( d ) ; fname=d ( k ) . name ; 19 20 21 %Loads t h e measurement r e s u l t s t o a matrix x = csvread ( fname , 1 , 0 ) ; 22 23 24 25 26 %Loads t h e v o l t a g e from t h e p o s s i t i o n meter v o l t a g e p o s=x ( : , 2 ) ; %Converts t h e v o l t a g e t o t h e d i s t a n c e between t h e b r e a k e r ... contacts d i s t =(9− v o l t a g e p o s ) ∗ 9 / 9 ; 27 28 29 %Loads t h e v o l t a g e o f t h e l o a d s i d e o f t h e b r e a k e r v o l t a g e l o a d s i d e=x ( : , 5 ) ; 30 31 32 %Loads t h e v o l t a g e o f t h e t r a n s f o r m e r s i d e o f t h e b r e a k e r v o l t a g e t r a n s s i d e=x ( : , 3 ) ; 33 34 35 %Loads t h e t r o u g h t h e b r e a k e r c u r r e n t=x ( : , 6 ) ; Plotting results 87 36 37 38 %Loads and s e t s t h e time a c o r d i n g t o t h e s t e p time time=d e l t a t ∗x ( : , 1 ) ∗ 1 0 ˆ 3 ; 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 %Opens a new f i g u r e F=f i g u r e ; %S e t s t h e f i l e n a m e o f t h e p l o t t o t h e name o f t h e measurement ... f i l e followed %by R e s u l t f i l e n a m e =[ fname ( 1 : length ( fname ) −4) ’ Breakerpos ’ ] ; T i t l e=fname ; %P l o t s t h e d i s t a n c e between t h e b r e a k e r c o n t a c t s a s a f u n c t i o n ... o f time plot ( time , d i s t ) ; %S e t s t h e x−a x i s t o t h e l e n g t h o f t h e time v e c t o r xlim ( [ 0 time ( end ) ] ) %Adding a t i t l e t o t h e f i g u r e t i t l e ( T i t l e , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; %Adds l a b e l s t o t h e a x i s xlabel ( ’ Time [ ms ] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; ylabel ( ’ Distance between VCB contacts [ mm ] ’ , ’ FontWeight ’ , ’ bold ’ , ... ’ Fontsize ’ , 1 6 ) ; %Saves t h e p l o t a s a png f i l e under t h e f i l e name print (F , ’- dpng ’ , f i l e n a m e ) ; s a v e a s ( gcf , [ fname ( 1 : length ( fname ) −4) ’ Breakerpos . fig ’ ] ) 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 %New f i g u r e f o r p l o t t i n g t h e t r a n s f o r m e r s i d e v o l t a g e F=f i g u r e ; %P l o t s t h e l o a d s i d e v o l t a g e a s a f u n c t i o n o f time plot ( time , v o l t a g e t r a n s s i d e ) ; %S e t s t h e f i l e n a m e o f t h e p l o t t o t h e name o f t h e measurement ... f i l e followed %by R e s u l t f i l e n a m e =[ fname ( 1 : length ( fname ) −4) ’ Voltagetransside ’ ] ; T i t l e=fname ; %S e t s t h e x−a x i s t o t h e l e n g t h o f t h e time v e c t o r xlim ( [ 0 time ( end ) ] ) %Adding a t i t l e t o t h e f i g u r e t i t l e ( T i t l e , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; %Adds l a b e l s t o t h e a x i s xlabel ( ’ Time [ ms ] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; ylabel ( ’ Trans . side voltage [V] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’... ,16) ; %Saves t h e p l o t a s a png f i l e under t h e f i l e name print (F , ’- dpng ’ , f i l e n a m e ) ; s a v e a s ( gcf , [ fname ( 1 : length ( fname ) −4) ’ Voltagetransside . fig ’ ] ) 79 80 81 82 83 %New f i g u r e f o r p l o t t i n g t h e l o a d s i d e v o l t a g e F=f i g u r e ; %P l o t s t h e l o a d s i d e v o l t a g e a s a f u n c t i o n o f time plot ( time , v o l t a g e l o a d s i d e ) ; 88 84 85 86 87 88 89 90 91 92 93 94 95 96 97 %S e t s t h e f i l e n a m e o f t h e p l o t t o t h e name o f t h e measurement ... f i l e followed %by R e s u l t f i l e n a m e =[ fname ( 1 : length ( fname ) −4) ’ Voltageloadside ’ ] ; T i t l e=fname ; %S e t s t h e x−a x i s t o t h e l e n g t h o f t h e time v e c t o r xlim ( [ 0 time ( end ) ] ) %Adding a t i t l e t o t h e f i g u r e t i t l e ( T i t l e , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; %Adds l a b e l s t o t h e a x i s xlabel ( ’ Time [ ms ] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; ylabel ( ’ Load side voltage [V] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’... ,16) ; %Saves t h e p l o t a s a png f i l e under t h e f i l e name print (F , ’- dpng ’ , f i l e n a m e ) ; s a v e a s ( gcf , [ fname ( 1 : length ( fname ) −4) ’ Voltageloadside . fig ’ ] ) 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 %New f i g u r e f o r p l o t t i n g t h e l o a d s i d e v o l t a g e F=f i g u r e ; %P l o t s t h e l o a d s i d e v o l t a g e a s a f u n c t i o n o f time plot ( time , c u r r e n t ) ; %S e t s t h e f i l e n a m e o f t h e p l o t t o t h e name o f t h e measurement ... f i l e followed %by R e s u l t f i l e n a m e =[ fname ( 1 : length ( fname ) −4) ’ current ’ ] ; T i t l e=fname ; %S e t s t h e x−a x i s t o t h e l e n g t h o f t h e time v e c t o r xlim ( [ 0 time ( end ) ] ) %Adding a t i t l e t o t h e f i g u r e t i t l e ( T i t l e , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; %Adds l a b e l s t o t h e a x i s xlabel ( ’ Time [ ms ] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; ylabel ( ’ Current [A] ’ , ’ FontWeight ’ , ’ bold ’ , ’ Fontsize ’ , 1 6 ) ; %Saves t h e p l o t a s a png f i l e under t h e f i l e name print (F , ’- dpng ’ , f i l e n a m e ) ; s a v e a s ( gcf , [ fname ( 1 : length ( fname ) −4) ’ Current . fig ’ ] ) end 118 119 120 121 122 %Returns t o t h e top d i r e c t o r y with t h e measurement f o l d e r s cd . . Appendix B Results of the TRV Calculations The pictures contaning the data points used for the calculations is found on the cd. The PDF file named F ull Appendix.pdf contains the pictures showing the data and the results of the calculation. The appendix seen in the printed version only shows tabels contaning the calculation results. To get the full appendix, just send me an email and i will send the file. 90 Test nr. 1 2 3 4 5 6 7 8 9 10 11 12 Average Breaking angle[◦ ] 180 180 45 22.5 22.5 0 225 202.5 90 247.5 247.5 0 – Amplitude[V ] 5000 5250 -4875 -5375 -5500 -5125 4250 4500 0 1625 1625 -5500 – Frequency[Hz] 8739.824137 8827.700477 8502.21631 8753.602989 8750.663754 8729.068075 8717.853469 8941.000094 – 8473.056716 8587.166059 8775.923838 8708.915993 Time to damp[ms] 0.9876 1.1586 1.0652 1.0742 0.9426 1.119 1.0884 1.0278 – 0.9932 1.0114 1.19 0.9700 Table B.1: Results of the long TRV. The calculations have been made for the test where the 10m cable is used and at a voltage level of 5,75kV Test nr. 1 2 3 4 5 6 7 8 9 10 Average Breaking angle[◦ ] 22.5 0 67.5 202.5 315 135 180 225 90 337.5 – Amplitude[V ] -4218.75 -4500 -3000 3843.75 -1875 3468.75 4500 3468.75 468.8 -3937.5 – Frequency[Hz] 2914.948534 2978.72869 2948.610075 2881.742751 2951.113172 2866.342232 3047.715332 2945.719274 3053.748933 2950.057835 2953.872683 Time to damp[ms] 2.4964 2.5916 2.7594 2.6422 1.902 2.422 2.472 2.493 – 2.4624 2.30162 Table B.2: Results of the long TRV. The calculations have been made for the test where the 100m cable is used and at a voltage level of 5,75kV Appendix C Results of Current Chopping Calculations The pictures contaning the data points used for the calculations is found on the cd. The PDF file named F ull Appendix.pdf contains the pictures showing the data and the results of the calculation. The appendix seen in the printed version only shows tables contaning the calculation results. 92 Test nr. i Ich 1 2 3 4 5 6 0,28905 0,3086 0,2734 0,28905 0,2969 0,2818 0,1797 0,1484 0,2266 0,1875 0,1641 0,1016 α (when β = 14, 3) 6.3249·106 75.517·106 306.03·106 3.59·106 20.60·106 12.76·109 Table C.1: Measurements and results of the current chopping analysis. The data is based on measurements with a load of 0.5µF , 100m cable and a voltage level of 1.15kV Test nr. i Ich 1 2 3 4 5 6 0,54295 0,5547 0,53905 0,5547 0,5742 0,5625 0,3828 0,4688 0,1953 0,4141 0,2734 0,4062 α (when β = 14, 3) 144.29 9.54 1120844.08 49.65 11995.84 63.26s Table C.2: Measurements and results of the current chopping analysis. The data is based on measurements with a load of 1.0µF , 100m cable and a voltage level of 1.15kV Appendix D Results of the Rate of Rise of Dielectric Strength Calculations The pictures contaning the data points used for the calculations is found on the cd. The PDF file named F ull Appendix.pdf contains the pictures showing the data and the results of the calculation. The appendix seen in the printed version only shows tables contaning the calculation results. 94 Test nr. 1 2 3 4 5 6 7 8 9 10 11 12 13 Average A Breaking angle[◦ ] 0 225 247.5 337.5 22.5 202.5 22.5 315 0 45 0 292.5 315 – Number of reignitions 2 2 2 3 3 3 2 0 3 2 2 0 2 – A [V/µ S] 26.46 20.83 21.94 19.17 23.85 19.44 12.23 – 10.464 9.97 32.71 – 6.58 18.52 Table D.1: The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 4.6kV . Test nr. 1 2 3 4 5 6 7 8 9 10 Average A Breaking angle[◦ ] 0 0 67.5 225 315 135 0 202.5 90 337.5 – Number of reignitions 3 2 2 3 2 2 2 3 0 2 – A [V/µ S] 21.83 – 16.54 24.37 24.72 9.62 34.10 24.06 – 20.27 21.94 Table D.2: The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 5.75kV . Results of the Rate of Rise of Dielectric Strength Calculations Test nr. 1 2 3 4 5 6 7 8 9 10 11 Average A Breaking angle[◦ ] 135 180 247.5 315 67.5 22.5 157.5 0 0 0 45 – Number of reignitions 5 6 2 3 3 4 4 4 5 4 3 – 95 A [V/µ S] 28.82 25.66 10.20 22.43 24.13 31.73 20.68 21.45 26.60 27.23 31.64 24.50 Table D.3: The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 6.9kV . Test nr. 1 2 3 4 5 6 7 8 9 10 Average A Breaking angle[◦ ] 22.5 292.5 225 90 90 225 22.5 135 67.5 225 – Number of reignitions 15 8 8 4 0 6 11 5 6 9 – A [V/µ S] 44.29 47.94 29.71 23.54 – 37.90 54.27 34.78 51.78 58.20 38.24 Table D.4: The table shows the calculation of the RRDS for the system using with 10m cable and have a voltage level of 4.6kV . 96 Test nr. 1 2 3 4 5 6 7 8 9 10 11 12 Average A Breaking angle[◦ ] 180 180 45 22.5 22.5 0 225 202.5 90 270 270 0 – Number of reignitions 15 13 15 10 18 20 10 15 0 1 1 17 – A [V/µ S] 31.00 42.82 35.16 38.90 34.68 42.69 39.85 40.35 – – – 49.02 39.39 Table D.5: The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 5.75kV . Test nr. 1 2 3 4 5 6 7 8 9 10 11 12 Average A Breaking angle[◦ ] 247.5 45 112.5 202.5 0 247.5 202.5 0 315 45 0 225 – Number of reignitions 8 15 12 17 23 7 23 19 17 19 5 5 – A [V/µ S] 36.88 34.61 43.45 42.91 39.10 37.36 35.91 39.19 34.82 44.93 24.17 18.57 36.02 Table D.6: The table shows the calculation of the RRDS for the system using with 100m cable and have a voltage level of 6.9kV . Appendix E Results of HF Current Quenching Capability Calculations The pictures contaning the data points used for the calculations is found on the cd. The PDF file named F ull Appendix.pdf contains the pictures showing the data and the results of the calculation. The appendix seen in the printed version only shows tables contaning the calculation results. 98 Arc number Arc 2 Arc 2 A A C[ µs D[ µs ] 2] Test nr. Arc 1 A C[ µs 2] Arc 1 A D[ µs ] 1 2 3 4 5 6 7 8 9 10 11 12 Average -0.294 -0.489 -0.52524 -0.48529 -1.684 -0.316 -0.705 -0.429 -0.437 -0.114 -0.87 -0.74513 -0.59125 9.375 31.25 27.34375 36.45 29.296 5.580 21.484 15.626 17.188 9.766 117.188 85.938 25.67046 -0.668 -1.436 – – -2.182 -1.774 -0.673 – – -0.588 -0.609 -1.597 -1.19084 33.2 50.78 – – 52.734 85.937 14.5 – 51.563 19.531 85.938 42.969 48.57241 Arc 3 A C[ µs 2] Arc 3 A D [ µs ] -0.705 -3.272 – – – – 1.898 – -2.174 -1.512 – – -1.9121 62.5 103.516 – – – – 51.563 – 125 35.938 – – 75.70312 Table E.1: The results of the parameters C and D when expressing the HF current quenching capability as a linear function. All tests are made at voltage level 5.75kV in the system using the 100m cable. Test nr. Arc number Arc 1 Arc 2 Arc 3 A A A D[ µs ] D[ µs ] D[ µs ] 1 2 3 4 5 6 7 8 9 10 11 12 Average 7.812 19.531 11.718 11.718 24.553 6.696 12.695 11.718 12.695 6.696 21.875 13.021 13.255 28.125 15.625 – – 33.854 29.017 26.041 29.513 93.75 12.276 45.312 26.785 34.03 60.937 107.142 – – – – 30.273 47.991 32.366 – 55.742 Table E.2: The results of D when considering the HF current quenching capability to be constant. Again all tests are made with 100m cable and at voltage level 5.75kV Appendix F Results of Rate of Decay of Dielectric Srength The pictures contaning the data points used for the calculations is found on the cd. The PDF file named F ull Appendix.pdf contains the pictures showing the data and the results of the calculation. The appendix seen in the printed version only shows tables contaning the calculation results. 100 Test nr. 1 2 3 4 5 6 7 8 9 10 Average A Breaking angle[◦ ] 112.5 90 112.5 180 202.5 315 90 67.5 0 270 – Number of Prestrikes 3 4 4 2 4 2 6 3 0 6 – A [V/µ S] 125.97 149.23 136.35 240.38 103.86 174.54 147.37 130.79 – 115.37 147.1 Table F.1: The results of the Rate of decay of Dielectric Strength, the calculations are made on test results from the system using the 10m cable and voltage level 5.75kV www.elektro.dtu.dk Technical University of Denmark Department of Electrical Engineering Centre for Electric Technology (CET) Elektrovej 325 Building 325 DK-2800 Kgs. Lyngby Denmark Tel: (+45) 45 25 35 00 Fax: (+45) 45 88 61 11 Email: cet@elektro.dtu.dk