Installation Instructions Pump Junction Box, Part No. 7133 638 Please file in Service Binder for Vitorond 100, Vitorond 200, Vitogas 050 (RS Series), and Vitogas 100 Safety and Installation Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below can cause product/property damage, severe personal injury, and/or loss of life. Working on the equipment The installation, adjustment, service, and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner, or control. Ensure main power supply to equipment, the heating system, and all external controls has been deactivated. Close main fuel supply valve. Take precautions in all instances to avoid accidental activation of power during service work. It is not permissible to perform service work on any component parts ensuring safe operation of the heating system. When replacing parts, use original Viessmann or Viessmann approved replacement parts. Ensure that the installation literature of other components is referenced. Product Information The pump junction box supplies power to field supplied pumps. It is shipped with the boiler and must be installed whenever each of the boilers listed above is installed in conjunction with the following controls: 1. - Vitotronic 100, KK10 - Vitotronic 100, KW10 If installing Vitotronic 200 or 300, discard the pump junction box. Installation instructions Install the pump junction box as follows: 1. Place the pump junction box for the Vitorond 100 / 200 underneath the top panel near the back of the boiler. See Fig. 1. 2. For Vitogas 100 and Vitogas 050, RS Series boilers, the pump junction box comes factory installed. Fig 1. Installation location of pump junction box 5167 425 v1.0 04/2008 1. Connect the RAST-5 plug-in of the Pump Junction connector Box to the main circuit board of the control, as shown in Fig. 2. 2. Feed the power supply cabling of the system pump through the opening at the back of the boiler and connect to terminals in pump junction box, as shown in Fig. 2. IMPORTANT Run BX (armoured cable) or any other approved wire (required by local authority having jurisdiction) from junction box terminal to heating circuit pump. Installation Instructions Vitotronic 100 Printed on environmentally friendly (recycled and recyclable) paper. Electrical connections Pump junction box GRN Space heating pump 120 VAC, 3 amps Maximum WHT L N 20 BLK 20 Pump Viessmann Manufacturing Company (U.S.) Inc. 45 Access Road Warwick, Rhode Island • 02886 • USA Tel. (401) 732-0667 • Fax (401) 732-0590 www.viessmann-us.com • info@viessmann-us.com Viessmann Manufacturing Company Inc. 750 McMurray Road Waterloo, Ontario • N2V 2G5 • Canada Tel. (519) 885-6300 • Fax (519) 885-0887 www.viessmann.ca • info@viessmann.ca 5167 425 v1.0 Technical information subject to change without notice. Fig. 2. Pump junction box