Flat Twin, PVC Insulated, Low Voltage Cable 300/500V, SABS 1574

advertisement
Flat Twin, PVC Insulated, Low Voltage Cable 300/500V,
SABS 1574, 70ºC
Conductors: Annealed Copper Compacted – Class 2
Insulation: PVC
Phase Color Code: Red & Black
Application: Used for House/Building Wiring.
FLAT TWIN PVC Insulated - 300/500V
PHYSICAL PROPERTIES
Approximate
Phase Conductor Size Conductor Diameter
Dimensions
mm2
No./mm
mm
0.5
0.9
3.0 x 6.0
0.75
1.14
3.2 x 6.4
1
1.13
4.7 x 8.6
1.5
1.38
5.6 x 10.0
2.5
1.78
6.2 x 11.5
4
2.55
7.2 x 13.0
6
3.12
8.0 x 15.0
10
4.05
9.6 x 19.0
16
5.25
11.0 x 22.5
ELECTRICAL PROPERTIES
Cable Mass
Coil length
DC Resistance @ 20°C
Current in Air (A)
kg/km
41
50
58
85
120
179
230
337
481
m
100
100
100
100
100
100
100
100
100
Ω/km/phase
39.00
26.00
18.10
13.60
7.41
4.61
3.08
1.83
1.15
3
6
10
21
30
39
50
68
91
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Flat Twin & Earth, PVC Insulated, Low Voltage Cable 300/500V,
SABS 1574, 70ºC
Conductors: Annealed Copper Compacted – Class 2
Insulation: PVC
Phase Color Code: 2 Cores -Red & Black
3 Cores – Red , Yellow & Blue
4 Cores – Red, Yellow, Blue, Black
Application: Used for House/Building and factory wiring.
FLAT TWIN PVC Insulated - 300/500V
PHYSICAL PROPERTIES
Approximate
Phase Conductor Size Earth Conductor Wires
Dimensions
mm2
mm2
mm
1
1
4.7 x 11
1.5
1
5.4 x 12.5
2.5
1.5
6.2 x 14.5
4
2.5
7.4 x 18
6
4
8.0 x 20.0
10
6
9.6 x 25.5
16
10
11 x 29.5
ELECTRICAL PROPERTIES
Cable Mass
Coil Length
DC Resistance @ 20°C
Current in Air (A)
kg/km
65
90
129
196
260
385
565
m
100
100
100
100
100
100
100
Ω/km/phase
18.10
13.60
7.41
4.61
3.08
1.83
1.15
16
21
30
39
50
68
91
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
House Wire, Single Core PVC Insulated,
Low Voltage Cable 0.6/1 kV, SABS 1507, 70ºC
Conductors: Annealed Copper Compacted – Class 2
Insulation: PVC
Phase Color Code: Red, Yellow, Blue, Black, Grn/Yellow, Orange,
Pink, Violet, White or any color required by customer
Application: Used for House/Building wiring.
HOUSE WIRE PVC INSULATED - 600/1000V
PHYSICAL PROPERTIES
Phase Conductor Conductor Diameter
Approximate
Size
Diameter
mm2
mm
mm2
1
1.13
2.8
1.5
1.5
3.1
2.5
1.9
3.5
4
2.4
4.4
6
2.9
4.9
10
3.7
5.7
16
4.8
6.8
25
6.1
8.5
35
7.1
9.5
50
8.2
11.0
70
9.9
12.7
95
11.7
14.9
120
13.4
16.6
150
14.6
18.2
185
16.4
20.4
240
18.8
23.2
300
21.4
26.2
400
24.3
29.5
500
27.3
32.9
630
31.0
36.6
800
35.1
40.7
1000
39.1
45.1
Cable Mass
Drum
kg/km
20
23
33
52
74
114
173
269
364
517
708
960
1199
1496
1847
2388
2980
3944
4913
6133
7716
9614
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC Resistance @
Current unenclosed
20°C
in Air (A)
Ω/km/phase
18.100
14
12.100
18
7.410
25
4.610
33
3.080
43
1.830
59
1.150
82
0.727
111
0.524
136
0.387
166
0.268
214
0.193
261
0.153
303
0.124
350
0.099
418
0.075
490
0.060
570
0.047
652
0.060
773
0.050
872
0.030
996
0.030
1081
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Ripcord, PVC Insulated, Low Voltage Cable 300/300V,
SABS 1574, 70ºC
Conductors: Flexible Copper – Class 5
Insulation: PVC
Phase Color Code: White, Transparent or Black with identification
thread or Black with Red
Application: Used for House Lighting Appliances, Audio
and Alarm Systems
Ripcord - 300/300V
Phase Conductor
Size
mm2
0.5
0.75
1
1.5
2.5
PHYSICAL PROPERTIES
Approximate
Conductor Diameter
Dimensions
mm2
mm
1
2.4 x 4.8
1.3
2.7 x 5.4
1.5
3.1 x 6.2
1.7
3.3 x 6.6
2.2
3.8 x 7.6
Cable Mass
Coil Length
kg/km
21
28
37
47
69
m
100
100
100
100
100
ELECTRICAL PROPERTIES
DC Resistance @
Current in Air (A)
20°C
Ω/km/phase
39.00
3
26.00
6
19.50
10
13.30
16
7.98
25
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Welding Cable, Single Core PVC Nitrile Insulated,
Low Voltage Cable 100V, SABS 1576, 70ºC
Conductors: Flexible Copper – Class 5
Insulation: PVC-Nitrile ( Flexible Grade)
Phase Color Code: As specified below or as per
customer specification
Application: Used for Electric Welding Equipment
WELDING CABLE PVC NITRILE(FLEXIBLE GRADE) INSULATED - 100V
PHYSICAL PROPERTIES
Phase
Approximate Cable Mass Drum
Conductor Phase Colour Conductor
Diameter
Diameter
Size
mm2
16
25
35
50
70
95
120
Green
Blue
Grey
Red
Brown
Yellow
Black
mm2
5.8
7.3
9.4
11.2
13.1
15.3
17.0
mm
10.4
11.8
13.9
16.2
18.4
21.1
23.1
kg/km
228
324
436
605
825
1098
1368
m
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC
Resistance @
20°C
Continuous
Ω/km/phase rating @ 30°C
1.210
82
0.780
111
0.554
133
0.386
166
0.272
214
0.206
261
0.161
303
Current unenclosed in Air (A)
100%
140
189
227
283
365
445
516
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
5 Min. Period Duty Cycle
85%
60%
150
181
203
245
244
294
304
367
392
473
478
577
555
669
30%
254
344
412
514
663
808
939
GenFlex®, Single Core PVC Nitrile Insulated,
Low Voltage Cable 1000V, SABS 1574, 70ºC
Conductors: Flexible Copper – Class 5
Insulation: PVC-Nitrile ( Flexible Grade)
Phase Color Code: Red or as requested by customer
Application: Used for Panel and Instrument Wiring
PANEL/INSTRUMENT WIRE PVC NITRILE INSULATED - 600/1000V
PHYSICAL PROPERTIES
Phase Conductor
Approximate
Conductor Diameter
Size
Diameter
mm2
mm
mm2
0.5
1
2.4
0.75
1.3
2.7
1
1.5
3.1
1.5
1.7
3.3
2.5
2.2
3.8
4
2.6
4.6
6
3.9
5.9
10
4.7
7.2
16
5.8
8.4
25
7.3
10.2
35
9.4
12.3
50
11.2
14.5
70
13.1
16.4
95
15.3
19.1
120
16.9
20.7
150
20.1
24.2
185
20.8
25.4
Cable Mass
Coils/Drums
kg/km
10
14
18
24
35
54
78
121
181
279
381
542
736
995
1234
1553
1901
m
100
100
100
100
100
100
100
100
100
500
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC Resistance @
Current unenclosed
20°C
in Air (A)
Ω/km/phase
39.000
3
26.000
6
19.500
10
13.300
16
7.980
25
4.950
32
3.300
43
1.910
59
1.210
82
0.780
111
0.554
136
0.386
166
0.272
214
0.206
261
0.161
303
0.129
350
0.106
418
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Interdac 3 Cable Low Voltage Power Cable 1.9/3.3 kV,
SABS 1507, 90ºC, APL MDPE Sheath.
Phase Conductors: Annealed Copper Compacted – Class 2
Earth Conductor: Tinned Annealed Copper – Class 2
Insulation: LV-XLPE
Phase Color Code: Red, Yellow and Blue
Application: Used to transfer power over long
distances, e.g. supply power to farm water pump motors.
INTERDAC 3 (1900/3300V)
Cable Size
Conductor Diameter
Phase Core Diameter
Phase Color Identification
Tinned Bare Copper Earth
Conductor Size
Cable Overall Diameter
Cable Mass
Conductor resistance (DC
Resistance @ 20°C)
Conductor resistance (AC
Resistance @ 90°C)
Conductor Impedance (Z)
Current (A)
Symmetrical Short Circuit current
(1 Sec.)
PHYSICAL PROPERTIES
10
16
3.83
4.75
8.83
9.75
Red, Yel & Blue
Red, Yel & Blue
10
25
6.1
11.1
Red, Yel & Blue
UNITS
mm2
mm
mm
16
25
mm2
26.4
903
29.4
1071
mm
kg/km
UNITS
1.830
1.150
0.727
Ω/km
2.19
1.38
0.93
Ω/km
2.340
80
1.474
103
0.934
130
Ω/km
A
1.4
2.3
3.6
kA
24.2
324
ELECTRICAL PROPERTIES
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Armoured XLPE Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 90ºC, PVC-FR Sheath.
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red or Black
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
600/1000V - 1 Cores XLPE AWA
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Screen
Cable Mass
Size Diam.
Diameter
Diam.
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
4.8
6.1
7.1
8.2
9.9
11.7
13.4
14.6
16.4
18.8
21.4
24.3
27.3
31.0
35.1
39.1
mm
6.2
7.9
8.9
10.2
12.1
13.9
15.8
17.4
19.6
22.2
25.0
28.3
31.7
35.8
40.3
44.7
mm
13.3
15.0
16.0
17.3
19.4
21.2
24.1
25.7
28.8
31.4
35.4
39.5
42.9
48.8
53.3
58.1
CU
AL
kg/km
342.7
242.7
463.1
306.9
576.8
358.1
742.0
429.6
974.3
536.9
1242.4 648.8
1572.2 822.4
1891.9 954.5
2351.9 1195.9
2929.0 1429.2
3681.9 1807.2
4778.5 2279.0
5823.5 2699.1
7411.1 3474.3
9143.1 4144.0
11206.2 4957.3
Drum
length
DC Resistance
@ 20°C
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
1.15
1.91
0.73
1.20
0.52
0.87
0.39
0.64
0.27
0.44
0.19
0.32
0.15
0.25
0.12
0.21
0.10
0.16
0.08
0.13
0.06
0.10
0.05
0.08
0.04
0.06
0.03
0.05
0.02
0.03
0.02
0.03
ELECTRICAL PROPERTIES
Sym.
Asym.
AC Resistance
Impedance
Current, in Current,in
@ 90°C
1sec
1sec
CU
AL
CU
AL
CU
AL
Ω/km/phase
Ω/km/phase
kA
1.47 2.420
1.47
2.460
2.3
1.5
2.6
0.93 1.540
0.93
1.542
3.5
2.3
3.0
0.67 1.110
0.68
1.11
5.0
3.3
3.4
0.49 0.820
0.52
0.84
7.2
4.7
3.7
0.34 0.570
0.37
0.59
10.0
6.6
4.2
0.25 0.410
0.28
0.43
13.6
9.0
4.8
0.2
0.330
0.24
0.350 17.2 11.3
5.4
0.16 0.270
0.2
0.29
21.5 14.2
5.9
0.13 0.210
0.18
0.24
26.5 17.5
8.5
0.1
0.160
0.15
0.200 34.3 22.7
9.5
0.08 0.130
0.14
0.17
42.9 28.3
13.4
0.06 0.100
0.13
0.15
57.2 37.8
14.8
0.05 0.080 0.120
0.14
71.5 47.2
16.6
0.04 0.060
0.11
0.12
90.1 59.5
23.7
0.04 0.042 0.039 0.045 114.4 73.6
26.0
0.03 0.038 0.034 0.040 143.0 92.0
28.3
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Ground
CU
91
117
147
174
217
261
304
342
388
456
525
596
693
778
843
895
Air
AL
CU
Amps
71
88
93
114
113
147
135
174
169
223
203
242
236
269
266
361
303
410
356
488
412
573
473
652
556
773
675
872
702
996
774 1081
AL
69
92
113
136
173
209
248
280
364
381
450
518
622
712
918
963
Armoured XLPE Low Voltage Power Cable 1.9/3.3 kV,
SABS 1507, 90ºC, PVC-FR Sheath.
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red or Black
Application: Used for reticulation and underground power supply .
Outer sheath can also be stripped blue or white.
1900/3300V - 1 Cores XLPE AWA
PHYSICAL PROPERTIES
Insulation
Cable
Core
Overall
Screen
Cable Mass
Size
Diam.
Diameter
Diam.
CU
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
4.8
6.1
7.1
8.2
9.9
11.7
13.4
14.6
16.4
18.8
21.4
24.3
27.3
31.0
35.1
39.1
mm
8.8
10.1
11.1
12.2
13.9
15.7
17.4
18.6
20.4
22.8
25.4
28.3
31.7
35.8
40.3
44.7
mm
15.9
17.2
18.4
19.5
21.2
23.0
25.7
26.9
29.6
32.0
35.8
39.5
42.9
48.8
53.3
58.5
ELECTRICAL PROPERTIES
Drum
length
DC Resistance
@ 20°C
AC Resistance
@ 90°C
Impedance
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
1.15
1.91
0.727
1.2
0.524
0.87
0.387
0.640
0.268
0.440
0.193
0.320
0.153
0.250
0.124
0.210
0.099
0.160
0.075
0.130
0.060
0.100
0.047
0.080
0.037
0.060
0.028
0.050
0.021
0.033
0.019
0.032
CU
AL
Ω/km/phase
1.47
2.42
0.93
1.54
0.67
1.11
0.490 0.820
0.340 0.570
0.250 0.410
0.200 0.330
0.160 0.270
0.130 0.210
0.100 0.160
0.080 0.130
0.060 0.100
0.050 0.080
0.040 0.060
0.036 0.042
0.032 0.038
CU
AL
Ω/km/phase
1.474
2.46
0.934
1.542
0.676
1.113
0.517
0.836
0.371
0.586
0.282
0.433
0.236
0.350
0.204
0.294
0.177
0.244
0.153
0.200
0.139
0.173
0.129
0.151
0.120
0.135
0.112
0.122
0.039
0.045
0.034
0.04
AL
kg/km
420.3
320.4
536.7
380.5
659.3
440.5
823.3
510.9
1046.1
608.7
1315.6
722.0
1646.9
897.0
1950.3 1013.0
2392.4 1236.3
2962.9 1463.1
3702.8 1828.1
4778.5 2279.0
5823.5 2699.1
7411.1 3474.3
9143.1 4144.0
11263.3 5014.5
Asym.
Sym. Current, Current,in
in 1sec
1sec
CU
AL
kA
2.3
1.5
3.2
3.5
2.3
3.7
5
3.3
3.9
7.2
4.7
4.3
10.0
6.6
4.8
13.6
9.0
5.2
17.2
11.3
5.9
21.5
14.2
6.3
26.5
17.5
8.7
34.3
22.7
9.7
42.9
28.3
13.4
57.2
37.8
14.8
71.5
47.2
16.6
90.1
59.5
23.7
114.4 73.6
26.0
143
92
28.3
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Ground
Air
AL
CU
AL
Amps
91
71
88
69
117
93
114
92
147
113
147
113
174
135
174
136
217
169
223
173
261
203
242
209
304
236
269
248
342
266
361
280
388
303
410
364
456
356
488
381
525
412
573
450
596
473
652
518
693
556
773
622
778
675
872
712
843
702
996
918
895
774 1081 963
CU
Unarmoured XLPE Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 90ºC, PVC-FR Sheath.
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red or Black
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
600/1000V - 1 Cores XLPE Unarmoured
PHYSICAL PROPERTIES
Insulation
Cable Cond.
Overall
Screen
Cable Mass
Size
Diam.
Diameter
Diam.
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
4.8
6.1
7.1
8.2
9.9
11.7
13.4
14.6
16.4
18.8
21.4
24.3
27.3
31.0
35.1
39.1
mm
6.2
7.9
8.9
10.2
12.1
13.9
15.8
17.4
19.6
22.2
25.0
28.3
31.7
35.8
40.3
44.7
mm
9.4
11.1
12.1
13.8
15.7
17.5
19.4
21
23.2
26.2
29.0
32.3
36.1
40.2
45.1
50.0
CU
AL
kg/km
216
117
318
162
418
199
582
270
787
349
1033
439
1284
534
1582
644
1934
778
2494
994
3080
1205
4042
1542
5044
1919
6299
2363
7969
2970
9874
3625
ELECTRICAL PROPERTIES
Drum DC Resistance AC Resistance
length
@ 20°C
@ 90°C
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
1.15
1.91
0.73
1.20
0.52
0.87
0.39
0.64
0.27
0.44
0.19
0.32
0.15
0.25
0.12
0.21
0.10
0.16
0.08
0.13
0.06
0.10
0.05
0.08
0.04
0.06
0.03
0.05
0.02
0.03
0.02
0.03
CU
AL
Ω/km/phase
1.47
2.420
0.93
1.540
0.67
1.110
0.49
0.820
0.34
0.570
0.25
0.410
0.2
0.330
0.16
0.270
0.13
0.210
0.1
0.160
0.08
0.130
0.06
0.100
0.05
0.080
0.04
0.060
0.04
0.042
0.03
0.038
Impedance
CU
AL
Ω/km/phase
1.47 2.460
0.93 1.542
0.68
1.11
0.52
0.84
0.37
0.59
0.28
0.43
0.24 0.350
0.2
0.29
0.18
0.24
0.15 0.200
0.14
0.17
0.13
0.15
0.120 0.14
0.11
0.12
0.039 0.045
0.034 0.040
Sym. Current, in
1sec
CU
AL
kA
2.3
3.5
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.1
114.4
143.0
1.5
2.3
3.3
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
73.6
92.0
Current (I) in Trefoil
Ground
Air
CU
AL
CU
AL
Amps
91
71
88
69
117
93
114
92
147
113
147
113
174
135
174
136
217
169
223
173
261
203
242
209
304
236
269
248
342
266
361
280
388
303
410
364
456
356
488
381
525
412
573
450
596
473
652
518
693
556
773
622
778
675
872
712
843
702
996
918
895
774 1081
963
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Unarmoured XLPE Low Voltage Power Cable 1.9/3.3 kV,
SABS 1507, 90ºC, PVC-FR Sheath.
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red or Black
Application: Used for reticulation and underground power supply.
Outer sheath can be stripped blue or white.
1900/3300V - 1 Cores XLPE Unarmoured
PHYSICAL PROPERTIES
Cable Cond. Insulation
Overall
Screen
Cable Mass
Size
Diam.
Diameter
Diam.
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
4.8
6.1
7.1
8.2
9.9
11.7
13.4
14.6
16.4
18.8
21.4
24.3
27.3
31.0
35.1
39.1
mm
8.8
10.1
11.1
12.2
13.9
15.7
17.4
18.6
20.4
22.8
25.4
28.3
31.7
35.8
40.3
44.7
mm
12
13.7
14.7
15.8
17.5
19.3
21.0
22.2
24.4
26.8
29.4
32.3
36.1
40.2
45.1
49.5
CU
AL
kg/km
265
165
377
221
481
263
632
320
837
399
1087
494
1337
587
1624
686
1988
832
2519
1019
3098
1224
4042
1542
5044
1919
6299
2363
7969
2970
9874
3625
ELECTRICAL PROPERTIES
Drum DC Resistance AC Resistance
length
@ 20°C
@ 90°C
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
1.15
1.91
0.727
1.2
0.524 0.87
0.387 0.640
0.268 0.440
0.193 0.320
0.153 0.250
0.124 0.210
0.099 0.160
0.075 0.130
0.060 0.100
0.047 0.080
0.037 0.060
0.028 0.050
0.021 0.033
0.019 0.032
CU
AL
Ω/km/phase
1.47
2.42
0.93
1.54
0.67
1.11
0.490 0.820
0.340 0.570
0.250 0.410
0.200 0.330
0.160 0.270
0.130 0.210
0.100 0.160
0.080 0.130
0.060 0.100
0.050 0.080
0.040 0.060
0.036 0.042
0.032 0.038
Impedance
CU
AL
Ω/km/phase
1.474 2.46
0.934 1.542
0.676 1.113
0.517 0.836
0.371 0.586
0.282 0.433
0.236 0.350
0.204 0.294
0.177 0.244
0.153 0.200
0.139 0.173
0.129 0.151
0.120 0.135
0.112 0.122
0.039 0.045
0.034 0.04
Sym. Current, in
1sec
CU
AL
kA
2.3
3.5
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.1
114.4
143.0
1.5
2.3
3.3
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
73.6
92.0
Current (I)
Ground
Air
CU
AL
CU
AL
Amps
91
71
88
69
117
93
114
92
147
113
147
113
174
135
174
136
217
169
223
173
261
203
242
209
304
236
269
248
342
266
361
280
388
303
410
364
456
356
488
381
525
412
573
450
596
473
652
518
693
556
773
622
778
675
872
712
843
702
996
918
895
774 1081
963
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Armoured XLPE Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 90ºC, PVC-FR Sheath
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red, Yellow, Blue or Black
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
600/1000V - 2,3 & 4 Cores XLPE SWA Armoured
PHYSICAL PROPERTIES
Cable Cond. Insul.
Size Diam. Diam.
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
mm
1.19
1.46
1.86
2.35
2.89
3.74
4.72
4.1
4.9
5.5
6.4
11.6
12.5
14.5
16.0
18.5
mm
2.59
2.86
3.26
3.75
4.29
5.15
6.12
5.87
6.67
7.5
8.6
12.7
13.0
14.6
17.7
20.2
Overall
Diameter
2C
mm
12.0
12.5
13.3
14.3
15.4
17.1
19.3
21.7
23.3
24.9
27.0
-
3C
mm
12.4
12.9
13.8
14.9
16
18.1
20.2
24.9
26.1
28.7
31.9
39.0
39.7
43.5
52.0
57.9
4C
mm
13.1
13.7
14.7
15.9
17.1
19.4
22.8
27.5
30.1
33.0
38.8
44.8
49.9
56.0
60.6
67.9
DC
Drum Resistance
Cable Mass (kg/km)
length
@ 20°C
2C
3C
4C
CU
AL
CU
AL CU AL
CU
AL
m
Ω/km/phase
270
293
322
500 18.20
298
325
360
500 13.60
343
379
423
500 7.410
401
450
514
500 4.610
474
540
628
500 3.080
607
714
845
500 1.830
787
939
1189
500 1.150
1227 930 1608 1162 1960 1365 500 0.727 1.250
1469 1055 1908 1288 2416 1589 500 0.524 0.868
1760 1198 2371 1528 3002 1877 500 0.387 0.641
2223 1412 3071 1856 4286 2663 500 0.268 0.443
- 4371 2679 5553 3297 300 0.193 0.320
- 5050 2918 7178 4334 300 0.153 0.253
- 6053 3416 8642 5126 300 0.124 0.164
- 7974 4679 10106 5714 300 0.099 0.125
- 9903 5571 12419 6642 300 0.075 0.100
ELECTRICAL PROPERTIES
AC
Sym.
Asym.
Resistance @ Impedance
Current
Current
90°C
CU
AL
CU
AL
CU AL 2C 3C 4C
Ω/km/phase Ω/km/phase
kA(1sec)
19.150
19.200
0.1
- 0.7 0.8 0.8
14.400
14.433
0.2
- 0.8 0.8 0.9
8.600
8.660
0.4
- 0.8 0.9 1
5.400
5.485
0.6
1
1 1.1
3.600
3.695
0.9
- 1.1 1.1 1.2
2.100
2.193
1.4
- 1.2 1.3 1.4
1.470
1.385
2.3
- 1.4 1.5 1.7
0.930 1.540 0.528 1.542 3.5 2.3 2.8 3.3 3.7
0.670 1.110 0.675 1.120 5.0 3.3 3 3.5 4.1
0.490 0.820 0.501 0.825 7.2 4.7 3.3 3.9 4.6
0.340 0.570 0.352 0.572 10.0 6.6 3.6 4.4 6.9
0.250 0.410 0.260 0.416 13.6 9.0 - 6.8 8
0.200 0.330 0.211 0.331 17.2 11.3 - 6.9 11
0.160 0.270 0.177 0.220 21.5 14.2 - 7.7 12.5
0.130 0.210 0.150 0.173 26.5 17.5 - 11 12.7
0.100 0.160 0.125 0.144 34.3 22.7 - 13 12.8
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Ground
Air
CU AL CU
Amps
14
- 15
18
- 19
24
- 25
32
- 34
41
- 43
57
- 65
103 - 101
132 101 126
158 121 155
186 142 189
229 175 241
275 210 297
312 239 347
351 268 398
397 305 460
459 353 547
AL
95
116
142
180
223
260
298
346
412
Armoured PVC Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 70ºC, PVC-FR Sheath
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: PVC
Phase Color Code: Red, Yellow , Blue and Black
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
600/1000V - 2,3 & 4 Cores PVC SWA Armoured
PHYSICAL PROPERTIES
Cable Cond. Insul.
Overall Diameter
Size Diam. Diam.
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
mm
1.19
1.46
1.86
2.35
2.89
3.74
4.72
4.1
4.9
5.5
6.4
11.6
12.5
14.5
16.0
18.5
mm
2.59
2.86
3.26
3.75
4.29
5.15
6.12
5.87
6.67
7.5
8.6
12.7
13.0
14.6
17.7
20.2
2C
mm
12.0
12.5
13.3
14.3
15.4
17.1
19.3
21.7
23.3
24.9
27.0
-
3C
mm
12.4
12.9
13.8
14.9
16
18.1
20.2
24.9
26.1
28.7
31.9
39.0
39.7
43.5
52.0
57.9
4C
mm
13.1
13.7
14.7
15.9
17.1
19.4
22.8
27.5
30.1
33.0
38.8
44.8
49.9
56.0
60.6
67.9
DC
Drum
Cable Mass (kg/km)
Resistance @
length
20°C
2C
3C
4C
CU
AL
CU
AL
CU
AL
CU
AL
m
Ω/km/phase
270
293
322
500
18.2
298
325
360
500
13.6
343
379
423
500
7.41
401
450
514
500
4.61
474
540
628
500
3.08
607
714
845
500
1.83
787
939
1189
500
1.15
1245 943 1632 1178 1988 1384 500
0.727 1.250
1491 1070 1937 1307 2451 1612 500
0.524 0.868
1786 1216 2406 1550 3046 1905 500
0.387 0.641
2255 1432 3118 1883 4349 2702 500
0.268 0.443
4437 2718 5635 3346 300
0.193 0.320
5125 2961 7286 4399 300
0.153 0.253
6143 3466 8771 5203 300
0.124 0.164
8093 4749 10257 5799 300
0.099 0.125
10052 5654 12604 6741 300
0.075 0.100
ELECTRICAL PROPERTIES
AC Resistance
@ 70°C
Impedance
CU
AL
Ω/km/phase
19.150
14.430
8.660
5.480
3.700
2.190
1.380
1.500 2.500
1.100 1.800
0.800 1.350
0.550 0.900
0.410 0.670
0.330 0.530
0.260 0.420
0.210 0.340
0.165 0.260
CU
AL
Ω/km/phase
19.15
14.43
8.66
5.48
3.70
2.19
1.38
1.50
2.50
1.10
1.80
0.81
1.35
0.57
0.92
0.43
0.68
0.35
0.55
0.29
0.44
0.25
0.37
0.21
0.35
Sym.
Current
CU
0.1
0.2
0.3
0.5
0.7
1.2
1.8
2.9
4.0
5.8
8.1
10.9
13.8
17.3
21.3
27.8
Asym. Current
AL 2C 3C
kA(1sec)
0.7 0.8
0.8 0.8
0.8 0.9
1
1
1.1 1.1
1.2 1.3
1.4 1.5
1.9 2.8 3.3
2.7 3 3.5
3.8 3.3 3.9
5.3 3.6 4.4
7.2
- 6.8
9.1
- 6.9
11.4 - 7.7
14.1 - 11.4
18.2 - 12.7
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Ground
4C
CU
0.8
0.9
1
1.1
1.2
1.4
1.7
3.7
4.1
4.6
6.9
8
11
12.5
12.7
12.8
15
18
25
32
41
57
91
119
143
169
210
251
285
320
361
416
Air
AL CU
Amps
14
17
24
33
42
60
80
93 101
112 126
133 153
165 196
197 238
225 276
252 319
286 364
331 430
AL
84
102
122
154
189
219
249
287
339
Unarmoured PVC Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 70ºC, PVC-FR Sheath
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: PVC
Phase Color Code: Red, Yellow, Blue or Black
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
600/1000V - 2,3 & 4 Cores PVC Unarmoured
PHYSICAL PROPERTIES
Cable Cond. Insul.
Size Diam. Diam.
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
mm
1.19
1.46
1.86
2.35
2.89
3.74
4.72
4.1
4.9
5.5
6.4
11.6
12.5
14.5
16.0
18.5
mm
2.59
2.86
3.26
3.75
4.29
5.15
6.12
5.87
6.67
7.5
8.6
12.7
13
14.6
17.7
20.2
Overall Diameter
2C
mm
8.9
9.4
10.2
11.2
12.3
14.4
16.3
15.8
17.4
19.1
21.2
-
3C
mm
9.2
9.7
10.6
11.6
12.8
14.9
17.0
18.8
19.9
22.3
25.9
31.3
31.9
35.7
42.2
48.0
Cable Mass (kg/km)
4C
2C
mm CU
AL
9.4
82
10.1 97
11.1 124
12.3 162
13.9 209
16.0 315
18.3 447
21.2 612 282
23.6 815 351
26.9 1114 438
31.5 1512 577
37.5
40.3
46.5
51.5
58.4
-
3C
CU
98
118
155
208
276
421
612
892
1183
1634
2262
3033
3742
4680
5785
7464
4C
AL
CU
118
143
191
261
363
537
787
398 1169
487 1570
619 2198
859 3115
1143 4062
1357 5045
1678 6331
2108 7799
2715 10044
AL
509
642
845
1141
1543
1864
2328
2896
3712
DC
Drum
Resistance @
length
20°C
CU
AL
m
Ω/km/phase
500
18.2
500
13.6
500
7.41
500
4.61
500
3.08
500
1.83
500
1.15
500
0.727 1.250
500
0.524 0.868
500
0.387 0.641
500
0.268 0.443
300
0.193 0.320
300
0.153 0.253
300
0.124 0.164
300
0.099 0.125
300
0.075 0.100
AC Resistance
@ 90°C
Impedance
CU
AL
Ω/km/phase
19.15
14.43
8.66
5.48
3.7
2.19
1.38
1.500 2.500
1.100 1.800
0.800 1.350
0.550 0.900
0.410 0.670
0.330 0.530
0.260 0.420
0.210 0.340
0.165 0.260
CU
AL
Ω/km/phase
19.2
14.4
8.66
5.48
3.7
2.19
1.38
1.500 2.500
1.100 1.800
0.810 1.350
0.570 0.920
0.430 0.680
0.350 0.550
0.290 0.440
0.250 0.370
0.210 0.350
Sym.
Current
CU
0.1
0.2
0.3
0.5
0.7
1.2
1.8
2.9
4.0
5.8
8.1
10.9
13.8
17.3
21.3
27.8
Current (I)
AL CU AL
kA(1sec)
15
18
25
32
41
57
91
1.9 119 93
2.7 143 112
3.8 169 133
5.3 210 165
7.2 251 197
9.1 285 225
11.4 320 252
14.1 361 286
18.2 416 331
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Ground
CU
AL
14
17
24
33
42
60
80
101
126
153
196
238
276
319
364
430
84
102
122
154
189
219
249
287
339
Air
AL CU
Amps
14
17
24
33
42
60
80
93 101
112 126
133 153
165 196
197 238
225 276
252 319
286 364
331 430
AL
84
102
122
154
189
219
249
287
339
Unarmoured XLPE Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 90ºC, PVC-FR Sheath
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red, Yellow, Blue or Black
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
600/1000V - 2,3 & 4 Cores XLPE Unarmoured
PHYSICAL PROPERTIES
Cable Cond. Insul.
Overall Diameter
Size Diam. Diam.
mm2
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
mm
1.19
1.46
1.86
2.35
2.89
3.74
4.72
4.1
4.9
5.5
6.4
11.6
12.5
14.5
16.0
18.5
mm
2.59
2.86
3.26
3.75
4.29
5.15
6.12
5.87
6.67
7.5
8.6
12.7
13
14.6
17.7
20.2
2C
mm
8.9
9.4
10.2
11.2
12.3
14.4
16.3
15.8
17.4
19.1
21.2
-
3C
mm
9.2
9.7
10.6
11.6
12.8
14.9
17
18.8
19.9
22.3
25.9
31.3
31.9
35.7
42.2
48.0
4C
mm
9.4
10.1
11.1
12.3
13.9
16
18.3
21.2
23.6
26.9
31.5
37.5
40.3
46.5
51.5
58.4
DC
Drum
Cable Mass (kg/km)
Resistance @
length
20°C
2C
3C
4C
CU
AL
CU
AL
CU
AL
CU
AL
m
Ω/km/phase
80.3
95.5
114.64
500
18.2
94.6
114.9
139.67
500
13.6
120.6
151.1
186.57
500
7.41
157.6
203.0
254.19
500
4.61
204.2
269.1
354.39
500
3.08
306.9
410.7
523.47
500
1.83
436.3
597.0
768.27
500
1.15
597.3 275.6 870.4 387.8 1140.0 496.5
500
0.727 1.250
795.6 342.9 1153.8 474.8 1531.3 626.0
500
0.524 0.868
1087.1 427.3 1593.8 604.2 2144.4 824.8
500
0.387 0.641
1475.5 563.0 2206.7 838.0 2941.4 1113.4
500
0.268 0.443
2958.9 1115.4 3962.9 1504.9
300
0.193 0.320
3651.1 1323.7 4921.4 1818.2
300
0.153 0.253
4565.8 1636.7 6176.7 2271.3
300
0.124 0.164
5643.7 2056.5 7608.8 2825.8
300
0.099 0.125
7282.4 2649.2 9799.1 3621.6
300
0.075 0.100
ELECTRICAL PROPERTIES
AC
Resistance @
90°C
CU
AL
Ω/km/phase
19.15
14.4
8.6
5.4
3.6
2.1
1.47
0.930 1.540
0.670 1.110
0.490 0.820
0.340 0.570
0.250 0.410
0.200 0.330
0.160 0.270
0.130 0.210
0.100 0.160
Impedance
CU
AL
Ω/km/phase
19.20
14.43
8.66
5.485
3.695
2.193
1.385
0.528 1.542
0.675 1.120
0.501 0.825
0.352 0.572
0.260 0.416
0.211 0.331
0.177 0.220
0.150 0.173
0.125 0.144
Sym.
Current
CU
0.1
0.2
0.4
0.6
0.9
1.4
2.3
3.5
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
AL CU AL
kA(1sec)
14
18
24
32
41
57
- 103 2.3 132 101
3.3 158 121
4.7 186 142
6.6 229 175
9.0 275 210
11.3 312 239
14.2 351 268
17.5 397 305
22.7 459 353
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Current (I)
Ground
CU
AL
15
19
25
34
43
65
101
126
155
189
241
297
347
398
460
547
95
116
142
180
223
260
298
346
412
Air
AL CU
Amps
14
17
24
33
42
60
80
93 101
112 126
133 153
165 196
197 238
225 276
252 319
286 364
331 430
AL
84
102
122
154
189
219
249
287
339
Armoured XLPE Low Voltage Power Cable 1.9/3.3 kV,
SABS 1507, 90ºC, PVC-FR Sheath.
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red, Yellow, Blue
Application: Used for reticulation and underground power supply.
Outer sheath can also be stripped blue or white.
1900/3300V - 3 Cores XLPE AWA
PHYSICAL PROPERTIES
Insulation
Cable
Core
Overall
Screen Diameter
Cable Mass
Size
Diam.
Diam.
mm2
10
16
25
35
50
70
95
120
150
185
240
mm
3.8
4.7
5.2
5.7
6.6
7.9
10.5
10.6
11.8
14.5
16.8
mm
7.8
8.7
9.2
9.7
10.6
11.9
14.5
14.6
15.8
18.5
20.8
mm
26.1
28.1
29.1
30.6
32.5
36.9
42.7
42.9
45.8
53.3
58.7
CU
AL
kg/km
1355
1636
1939
1835
2307
2151
2831
2549
3883
3539
4977
4555
5684
5153
6730
6006
8685
7870
10665
9671
ELECTRICAL PROPERTIES
Drum DC Resistance AC Resistance
length
@ 20°C
@ 90°C
m
500
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
1.15
0.727
0.524
0.87
0.387 0.640
0.268 0.440
0.193 0.320
0.153 0.250
0.124 0.210
0.099 0.160
0.075 0.130
0.060 0.100
CU
AL
Ω/km/phase
1.47
0.93
0.67
1.11
0.490 0.820
0.340 0.570
0.250 0.410
0.200 0.330
0.160 0.270
0.130 0.210
0.100 0.160
0.080 0.130
Impedance
CU
AL
Ω/km/phase
1.474
0.934
0.676 1.113
0.517 0.836
0.371 0.586
0.282 0.433
0.236 0.350
0.204 0.294
0.177 0.244
0.153 0.200
0.139 0.173
Asym.
Sym. Current, Current,in
in 1sec
1sec
CU
AL
kA
2.3
4.1
3.5
4.6
5
3.3
4.8
7.2
4.7
5.0
10.0
6.6
5.4
13.6
9.0
7.6
17.2
11.3
8.9
21.5
14.2
9.1
26.5
17.5
9.7
34.3
22.7
14.2
42.9
28.3
15.9
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current (I)
Ground
Air
CU
AL
CU
AL
Amps
91
88
117
114
147 113 147 113
174 135 174 136
217 169 223 173
261 203 242 209
304 236 269 248
342 266 361 280
388 303 410 364
456 356 488 381
525 412 573 450
Unarmoured XLPE Low Voltage Power Cable 1.9/3.3 kV,
SABS 1507, 90ºC, PVC-FR Sheath.
Conductor: Annealed Copper or Aluminium Compacted – Class 2
Insulation: LV-XLPE
Phase Color Code: Red, Yellow, Blue
Application: Used for reticulation and underground power supply .
Outer sheath can also be stripped blue or white.
1900/3300V - 3 Cores XLPE Unarmoured
PHYSICAL PROPERTIES
Cable Cond. Insulation Overall
Cable Mass
Size
Diam.
Diam.
Diameter
CU
AL
mm
mm
mm
kg/km
mm2
10
3.8
7.7
20
580
16
4.7
8.7
22
781
25
5.2
9.2
23
1048
944
35
5.7
9.7
25
1376
1220
50
6.6
10.6
26
1826
1544
70
7.9
11.9
29
2430
2087
95
10.5
14.5
35
3266
2844
120
10.6
14.6
36
3961
3431
150
11.8
15.8
38
4840
4116
185
14.5
18.5
43
5918
5103
240
16.8
20.8
49.0
7594
6600
Drum DC Resistance AC Resistance
length
@ 20°C
@ 90°C
CU
AL
CU
AL
m
Ω/km/phase
Ω/km/phase
500
1.15
1.47
500
0.73
0.93
500
0.52
0.87
0.67 1.110
500
0.39
0.64
0.49 0.820
500
0.27
0.44
0.34 0.570
500
0.19
0.32
0.25 0.410
500
0.15
0.25
0.2
0.330
500
0.12
0.21
0.16 0.270
500
0.10
0.16
0.13 0.210
500
0.08
0.13
0.1
0.160
500
0.06
0.10
0.08 0.130
ELECTRICAL PROPERTIES
Sym. Current,
Impedance
in 1sec
CU
AL
CU
AL
Ω/km/phase
kA
1.47
2.3
0.93
3.5
0.68
1.11
5.0
3.3
0.52
0.84
7.2
4.7
0.37
0.59
10.0
6.6
0.28
0.43
13.6
9.0
0.24
0.350 17.2
11.3
0.2
0.29
21.5
14.2
0.18
0.24
26.5
17.5
0.15
0.200 34.3
22.7
0.14
0.17
42.9
28.3
Current (I)
Ground
Air
CU
AL
CU
AL
Amps
91
88
117
114
147
113 147 113
174
135 174 136
217
169 223 173
261
203 242 209
304
236 269 248
342
266 361 280
388
303 410 364
456
356 488 381
525
412 573 450
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Armoured Multi-Core Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 90ºC, PVC-FR Sheath
Conductor: Annealed Stranded Copper – Class 2
Insulation: LV-XLPE
Phase Identification: Numbers
Application: Used to power control circuits like robots, etc. Outer
sheath can also be stripped blue or white .
600/1000V 7-37 Cores Armoured
PHYSICAL PROPERTIES
Cable
Size
mm2
1
1.5
2.5
4
6
No. of
Cores
Core
Diam.
Insulation
Diam.
7
12
19
27
37
7
12
19
27
37
7
12
19
27
37
7
12
19
27
37
7
mm
1.19
1.19
1.19
1.19
1.19
1.46
1.46
1.46
1.46
1.46
1.86
1.86
1.86
1.86
1.86
2.35
2.35
2.35
2.35
2.35
2.89
mm
2.59
2.59
2.59
2.59
2.59
2.86
2.86
2.86
2.86
2.86
3.26
3.26
3.26
3.26
3.26
3.75
3.75
3.75
3.75
3.75
4.29
Overall
Diameter Cable Mass
mm
15.5
20.7
21.7
27.0
28.9
17.0
21.2
25.9
29.8
32.8
18.5
24.8
28.1
32.6
37.6
21.0
28.2
32.5
39.8
43.8
24.4
kg/km
300
480
700
960
1380
629
901
1404
1783
2153
756
1306
1695
2181
3011
986
1211
2282
3354
4124
1412
Drum
length
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC
AC
Sym.
Resistance Resistance Impedance Current, in
@ 20°C
@ 90°C
1sec
Ω/km/phase Ω/km/phase Ω/km/phase
kA
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
13.6
14.43
14.47
0.2
13.6
14.43
14.47
0.2
13.6
14.43
14.47
0.2
13.6
14.430
14.47
0.2
13.6
14.430
14.47
0.2
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
3.08
3.68
3.7
0.7
Current (I)
Ground
Amps
15
14
13
12
11
18
15
12
11
9
24
19
16
14
12
31
25
21
18
16
38
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Air
14
13
12
11
10
15
12
11
10
8
20
17
14
13
11
26
22
19
17
15
33
Unarmoured Multi-Core Low Voltage Power Cable 0.6/1 kV,
SABS 1507, 90ºC, PVC-FR Sheath
Conductor: Annealed Stranded Copper – Class 2
Insulation: LV-XLPE
Phase Identification: Numbers
Application: Used to power control circuits like robots, etc.
Outer sheath can be stripped red, blue or white .
600/1000V 7-37 Cores Unarmoured
PHYSICAL PROPERTIES
Cable
Size
mm2
1
1.5
2.5
4
6
No. of
Cores
Core
Diam.
Insulation
Diam.
7
12
19
27
37
7
12
19
27
37
7
12
19
27
37
7
12
19
27
37
7
mm
1.19
1.19
1.19
1.19
1.19
1.46
1.46
1.46
1.46
1.46
1.86
1.86
1.86
1.86
1.86
2.35
2.35
2.35
2.35
2.35
2.89
mm
2.59
2.59
2.59
2.59
2.59
2.86
2.86
2.86
2.86
2.86
3.26
3.26
3.26
3.26
3.26
3.75
3.75
3.75
3.75
3.75
4.29
Overall
Diameter Cable Mass
mm
10
12.9
14.9
17.9
21.2
11.4
15.0
16.9
21.1
22.7
13.3
17.5
21
24.8
27.9
15.4
17.3
22.9
27.1
30.8
17
kg/km
150
240
350
480
690
195
320
450
670
840
300
490
760
1030
1380
493
606
1141
1677
2062
707
Drum
length
m
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC
AC
Sym.
Resistance Resistance Impedance Current, in
@ 20°C
@ 90°C
1sec
Ω/km/phase Ω/km/phase Ω/km/phase
kA
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
18.2
19.15
19.15
0.1
13.6
14.43
14.47
0.2
13.6
14.43
14.47
0.2
13.6
14.43
14.47
0.2
13.6
14.43
14.47
0.2
13.6
14.43
14.47
0.2
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
7.41
8.66
8.86
0.3
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
4.61
5.48
5.51
0.5
3.08
3.68
3.7
0.7
Current (I)
Ground
Amps
15
14
13
12
11
18
15
12
11
9
24
19
16
14
12
31
25
21
18
16
38
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Air
14
13
12
11
10
15
12
11
10
8
20
17
14
13
11
26
22
19
17
15
33
Aerial Bundle Conductor (LV-ABC) Low Voltage XLPE Power Cable ,
SABS 1418, 600/1000V (ABC XLPE Insulated + Insulated Support)
Conductor: Aluminium Compacted Circular- Class 2
Phase Color Identification: Numbered, 1, 2 & 3 + Insulated Support
Application: Used for aerial reticulation (sometimes with street
lighting core)
LV ABC - 600/1000V
Cable Size Conductor
Diameter
mm2
mm
25
6.5
35
7.3
50
8.3
70
10.2
95
12.3
120
13.5
150
15.3
PHYSICAL PROPERTIES
Insulation
Support
Overall
Diameter
Core Size
Diameter
mm
mm2
mm
9.5
54.6
22.9
10.5
54.6
25.3
11.7
54.6
28.1
13.6
54.6
32.8
15.9
54.6
38.2
17.1
70
41.2
19.3
95
46.5
Cable
mass
kg/km
420
555
752
1012
1348
1651
2065
Drum
length
m
500
500
500
500
500
500
500
Res. DC @
20°C
Ω/km
1.200
0.868
0.641
0.443
0.320
0.253
0.206
ELECTRICAL PROPERTIES
Res. AC @ Impedance Symmetrical
Current
90°C
Current
Rating in Air
Ω/km
Ω/km
kA
Amps
1.54
1.541
2.3
105
1.11
1.117
3.3
130
0.82
0.826
4.7
165
0.57
0.574
6.6
205
0.41
0.419
9
250
0.33
0.334
11.3
290
0.27
0.276
14.2
320
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Armoured Medium Voltage (MV) XLPE Type A,
Single Core, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
3.8/6.6kV - 1 Cores AWA
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall Cable Mass Drum
Screen
Size Diam.
Diameter
length
Diam.
CU
AL
mm
mm
mm
kg/km
m
mm2
50
8.4
16.7
26.7
1252 943
500
70
9.9
18.2
28.2
1495 1062 500
95
11.7
20.0
30.2
1810 1223 500
120
13.4
21.7
31.9
2107 1365 500
150
14.6
22.9
33.3
2443 1515 500
185
16.4
24.7
35.9
2927 1782 500
240
18.8
27.3
38.7
3563 2079 500
300
21.4
30.3
41.9
4276 2420 500
400
24.3
33.6
45.4
5365 2890 500
500
27.3
37.5
50.9
6724 3630 300
630
31.0
41.2
55.0
8143 4246 300
6.35/11kV 1 Cores AWA
50
8.4
18.5
28.6
1359 1049 500
70
9.9
20.0
30.3
1621 1188 500
95
11.7
21.8
32.1
1927 1339 500
120
13.4
23.5
34.0
2246 1503 500
150
14.6
24.7
36.2
2680 1752 500
185
16.4
26.5
38.0
3081 1937 500
240
18.8
28.9
40.6
3712 2227 500
300
21.4
31.5
43.2
4377 2521 500
400
24.3
34.4
46.5
5460 2986 500
500
27.3
37.9
51.4
6764 3670 300
630
31.0
41.6
55.5
8187 4289 300
Resistance @ Resistance @
20°C
90°C
Impedance
CU
AL
Ω/km/phase
0.387 0.641
0.268 0.443
0.193 0.320
0.153 0.253
0.124 0.206
0.099 0.164
0.075 0.125
0.060 0.100
0.047 0.077
0.037 0.061
0.028 0.047
CU
AL
Ω/km/phase
0.494 0.822
0.342 0.568
0.247 0.411
0.196 0.325
0.159 0.265
0.128 0.211
0.098 0.161
0.079 0.130
0.063 0.102
0.051 0.080
0.041 0.064
CU
AL
Ω/km/phase
0.513 0.834
0.366 0.583
0.275 0.429
0.229 0.346
0.196 0.288
0.170 0.239
0.146 0.194
0.131 0.167
0.121 0.145
0.115 0.130
0.107 0.118
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.06
0.047
0.037
0.028
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.079
0.063
0.051
0.041
0.513
0.366
0.275
0.229
0.196
0.170
0.146
0.131
0.121
0.115
0.107
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.077
0.061
0.047
0.82
0.57
0.41
0.33
0.27
0.21
0.16
0.13
0.1
0.08
0.06
0.834
0.583
0.429
0.346
0.288
0.239
0.194
0.167
0.145
0.130
0.118
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
CU AL
uf/km/phase
kA
7.2 4.7
9.0
323.754
10.0 6.6
9.6
363.980
13.6 9.0
10.4
412.112
17.2 11.3
11.1
457.470
21.5 14.2
11.6
489.445
26.5 17.5
15.4
537.356
34.3 22.7
16.7
580.516
42.9 28.3
18.3
605.340
57.2 37.8
20.1
633.487
71.5 47.2
27.6
670.139
90.0 59.5
30.1
746.857
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
9.7
10.4
11.1
12
15.3
16.3
17.7
19.1
20.5
27.8
30.5
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
253.773
283.609
319.249
352.793
376.419
411.798
458.882
509.806
566.532
634.529
706.761
Current (I)
Ground
CU
AL
206
250
298
336
373
411
468
522
580
618
669
206
250
297
334
370
412
470
520
579
620
672
Air
Duct
CU
AL
161
195
233
264
294
328
376
422
476
522
576
CU AL
Amps
239 186
295 230
358 280
412 324
464 365
520 414
605 485
690 557
784 641
860 722
949 814
165
200
238
269
298
329
374
418
464
494
535
129
156
186
211
235
262
301
338
381
418
461
161
195
233
263
292
328
377
421
476
523
579
242
297
361
412
464
524
611
688
783
864
957
165
200
238
267
296
330
376
416
463
496
538
129
156
186
210
234
262
302
337
381
418
463
188
232
283
324
366
416
489
555
640
724
819
Armoured Medium Voltage (MV) XLPE Type A,
Single Core, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
12.7/22kV - 1 Cores AWA
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall Cable Mass Drum Resistance @ Resistance @
Screen
Size Diam.
Diameter
length
20°C
90°C
Diam.
mm
mm
mm2
50
8.4
23.0
70
9.9
24.5
95
11.7
26.3
120
13.4
28.0
150
14.6
29.2
185
16.4
31.0
240
18.8
33.4
300
21.4
36.0
400
24.3
38.9
500
27.3
42.4
630
31
46.1
19/33kV 1 Cores AWA
50
8.4
28.2
70
9.9
29.7
95
11.7
31.5
120
13.4
33.2
150
14.6
34.4
185
16.4
36.2
240
18.8
38.6
300
21.4
41.2
400
24.3
44.1
500
27.3
47.6
630
31
51.3
mm
CU
AL
kg/km
m
CU
AL
Ω/km/phase
CU
AL
Ω/km/phase
ELECTRICAL PROPERTIES
Sym.
Asym.
Impedance Current, in Current,in Capacitance
1sec
1sec
CU
AL
CU AL
uf/km/phase
Ω/km/phase
kA
Current (I)
Ground
Air
Duct
CU
AL
CU AL
Amps
CU
AL
33.5
35.8
37.8
39.5
40.9
42.7
45.1
48.9
52.4
56.3
60.4
1668
2018
2361
2680
3036
3451
4101
4993
6089
7271
8727
1358
1585
1774
1938
2108
2306
2616
3137
3615
4178
4829
500
500
500
500
500
500
500
500
500
300
300
0.39
0.27
0.19
0.15
0.12
0.1
0.08
0.06
0.05
0.04
0.03
0.64
0.44
0.32
0.25
0.21
0.16
0.13
0.1
0.08
0.06
0.05
0.49
0.34
0.25
0.2
0.16
0.13
0.1
0.08
0.06
0.05
0.04
0.82
0.57
0.41
0.33
0.27
0.21
0.16
0.13
0.1
0.08
0.06
0.517
0.371
0.282
0.236
0.204
0.177
0.153
0.139
0.129
0.120
0.112
0.836
0.586
0.433
0.350
0.294
0.244
0.200
0.173
0.151
0.135
0.122
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
11.8
15.3
16.3
17
17.8
18.8
19.9
26.7
28.4
31
33.2
182.108
201.132
223.777
245.028
259.969
282.305
311.978
344.019
379.662
423.213
468.578
206
250
297
333
372
414
470
509
567
622
676
160
195
232
263
293
329
377
415
468
523
580
243
302
365
416
471
531
616
681
775
669
963
189
236
286
327
370
421
491
552
636
725
821
165
200
238
266
298
331
376
407
454
498
541
128
156
186
210
234
263
302
332
374
418
464
39.9
41.4
43.4
45.1
47.7
49.7
52.1
55.1
58.2
62.1
66.0
2169
2445
2806
3140
3687
4149
4807
5580
6705
7926
9387
1860
2011
2218
2397
2759
3004
3322
3724
4231
4832
5489
500
500
500
500
500
500
500
500
500
300
300
0.39
0.27
0.19
0.15
0.12
0.1
0.08
0.06
0.05
0.04
0.03
0.64
0.44
0.32
0.25
0.21
0.16
0.13
0.1
0.08
0.06
0.05
0.49
0.34
0.25
0.2
0.16
0.13
0.1
0.08
0.06
0.05
0.04
0.82
0.57
0.41
0.33
0.27
0.21
0.16
0.13
0.1
0.08
0.06
0.517
0.371
0.282
0.236
0.204
0.177
0.153
0.139
0.129
0.120
0.112
0.836
0.586
0.433
0.350
0.294
0.244
0.200
0.173
0.151
0.135
0.122
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
17.4
18.1
19.1
19.8
25.7
26.7
28.4
30
23.1
34.3
36.5
141.7481
155.2100
171.1653
186.0854
196.5494
212.1616
232.8540
255.1489
279.9040
309.9635
341.3560
206
250
297
333
372
414
470
509
567
622
676
160
195
232
263
293
329
377
415
468
523
580
243
302
365
416
471
531
616
681
775
669
963
189
236
286
327
370
421
491
552
636
725
821
165
200
238
266
298
331
376
407
454
498
541
128
156
186
210
234
263
302
332
374
418
464
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Unarmoured Medium Voltage (MV) XLPE Type B,
Single Core, Power Cable , SANS 1339
Conductor: Circular Annealed Copper or Aluminium Circular
Compacted - Class 2
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
3.8/6.6kV - 1 Cores AWA
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Drum Resistance @ Resistance @
Size Diam. Screen
Diameter Cable Mass length
20°C
90°C
Diam.
mm
mm
mm2 mm
50
8.4
16.7
21.1
70
9.9
18.2
22.5
95
11.7
20.0
24.3
120 13.4
21.7
26.2
150 14.6
22.9
27.4
185 16.4
24.7
29.4
240 18.8
27.3
32.0
300 21.4
30.3
35.1
400 24.3
33.6
38.8
500 27.3
37.5
42.9
630 31.0
41.2
46.8
6.35/11kV 1 Cores Unarmoured
50
8.4
18.5
23.2
70
9.9
20.0
24.4
95
11.7
21.8
26.4
120 13.4
23.5
28.1
150 14.6
24.7
29.5
185 16.4
26.5
31.3
240 18.8
28.9
33.9
300 21.4
31.5
36.6
400 24.3
34.4
39.7
500 27.3
37.9
43.4
630 31.0
41.6
47.3
CU
AL
kg/km
953 644
1188 755
1469 881
1760 1017
2066 1138
2452 1307
3035 1550
3593 1742
4647 2172
5722 2628
7031 3134
1050
1278
1578
1861
2186
2562
3156
3697
4705
5753
7065
741
845
990
1119
1258
1418
1671
1841
2230
2660
3168
Impedance
m
500
500
500
500
500
500
500
500
500
300
300
CU
AL
Ω/km/phase
0.387 0.641
0.268 0.443
0.193 0.320
0.153 0.253
0.124 0.206
0.099 0.164
0.075 0.125
0.060 0.100
0.047 0.077
0.037 0.061
0.028 0.047
CU
AL
Ω/km/phase
0.494 0.822
0.342 0.568
0.247 0.411
0.196 0.325
0.159 0.265
0.128 0.211
0.098 0.161
0.079 0.130
0.063 0.102
0.051 0.080
0.041 0.064
CU
AL
Ω/km/phase
0.513 0.834
0.366 0.583
0.275 0.429
0.229 0.346
0.196 0.288
0.170 0.239
0.146 0.194
0.131 0.167
0.121 0.145
0.115 0.130
0.107 0.118
500
500
500
500
500
500
500
500
500
300
300
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.06
0.047
0.037
0.028
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.079
0.063
0.051
0.041
0.513
0.366
0.275
0.229
0.196
0.170
0.146
0.131
0.121
0.115
0.107
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.077
0.061
0.047
0.82
0.57
0.41
0.33
0.27
0.21
0.16
0.13
0.1
0.08
0.06
0.834
0.583
0.429
0.346
0.288
0.239
0.194
0.167
0.145
0.130
0.118
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
CU
uf/km/phase
Current (I)
Ground
CU AL
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
AL
kA
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
2.5
2.7
3.0
3.2
3.4
3.7
4.0
3.0
3.3
3.7
4.0
323.754
363.980
412.112
457.470
489.445
537.356
580.516
605.340
633.487
670.139
746.857
206
250
298
336
373
411
468
522
580
618
669
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
2.8
3.0
3.3
3.5
3.7
3.9
4.3
3.1
3.4
3.7
4.1
253.773
283.609
319.249
352.793
376.419
411.798
458.882
509.806
566.532
634.529
706.761
206
250
297
334
370
412
470
520
579
620
672
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
161
195
233
264
294
328
376
422
476
522
576
Air
CU AL
Amps
239 186
295 230
358 280
412 324
464 365
520 414
605 485
690 557
784 641
860 722
949 814
165
200
238
269
298
329
374
418
464
494
535
129
156
186
211
235
262
301
338
381
418
461
161
195
233
263
292
328
377
421
476
523
579
242
297
361
412
464
524
611
688
783
864
957
165
200
238
267
296
330
376
416
463
496
538
129
156
186
210
234
262
302
337
381
418
463
188
232
283
324
366
416
489
555
640
724
819
Duct
CU AL
Unarmoured Medium Voltage (MV) XLPE Type B,
Single Core, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
12.7/22kV - 1 Cores Unarmoured
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Drum Resistance @ Resistance @
Screen
Size Diam.
Diameter Cable Mass length
20°C
90°C
Diam.
mm
mm
mm2
50
8.4
23.2
70
9.9
24.7
95
11.7
26.5
120
13.4
28.2
150
14.6
29.4
185
16.4
31.2
240
18.8
33.6
300
21.4
36.2
400
24.3
39.1
500
27.3
42.5
630
31.0
46.2
19/33kV 1 Cores Unarmoured
50
8.4
28.4
70
9.9
29.9
95
11.7
31.7
120
13.4
33.4
150
14.6
34.6
185
16.4
36.4
240
18.8
38.8
300
21.4
41.4
400
24.3
44.3
500
27.3
47.8
630
31.0
51.5
mm
28.0
29.4
31.2
33.1
34.3
36.2
38.8
41.4
44.5
48.2
52.1
CU
AL
kg/km
1298 988
1551 1118
1852 1264
2164 1422
2483 1555
2786 1641
3393 1908
4034 2178
5066 2591
6142 3048
7484 3586
m
500
500
500
500
500
500
500
500
500
300
300
CU
AL
Ω/km/phase
0.39 0.64
0.27 0.44
0.19 0.32
0.15 0.25
0.12 0.21
0.1
0.16
0.08 0.13
0.06
0.1
0.05 0.08
0.04 0.06
0.03 0.05
33.5
34.7
36.7
38.4
39.8
41.6
44.2
47.0
50.1
53.8
57.7
1588
1787
2114
2419
2764
3164
3793
4480
5539
6649
8025
500
500
500
500
500
500
500
500
500
300
300
0.39
0.27
0.19
0.15
0.12
0.1
0.08
0.06
0.05
0.04
0.03
1278
1354
1526
1677
1836
2019
2308
2623
3065
3555
4128
0.64
0.44
0.32
0.25
0.21
0.16
0.13
0.1
0.08
0.06
0.05
CU
AL
Ω/km/phase
0.49
0.82
0.34
0.57
0.25
0.41
0.2
0.33
0.16
0.27
0.13
0.21
0.1
0.16
0.08
0.13
0.06
0.1
0.05
0.08
0.04
0.06
0.49
0.34
0.25
0.2
0.16
0.13
0.1
0.08
0.06
0.05
0.04
0.82
0.57
0.41
0.33
0.27
0.21
0.16
0.13
0.1
0.08
0.06
Impedance
CU
AL
Ω/km/phase
0.517 0.836
0.371 0.586
0.282 0.433
0.236 0.350
0.204 0.294
0.177 0.244
0.153 0.200
0.139 0.173
0.129 0.151
0.120 0.135
0.112 0.122
0.517
0.371
0.282
0.236
0.204
0.177
0.153
0.139
0.129
0.120
0.112
0.836
0.586
0.433
0.350
0.294
0.244
0.200
0.173
0.151
0.135
0.122
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
CU
uf/km/phase
Current (I)
Ground
CU AL
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
AL
kA
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
3.4
3.6
3.9
4.2
4.3
3.0
3.3
3.5
3.8
4.2
4.5
182.108
201.132
223.777
245.028
259.969
282.305
311.978
344.019
379.662
423.213
468.578
206
250
297
333
372
414
470
509
567
622
676
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
57.2
71.5
90.0
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.3
37.8
47.2
59.5
2.8
2.9
3.1
3.3
3.4
3.6
3.8
4.0
4.3
4.7
5.0
141.7481
155.2100
171.1653
186.0854
196.5494
212.1616
232.8540
255.1489
279.9040
309.9635
341.3560
206
250
297
333
372
414
470
509
567
622
676
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
160
195
232
263
293
329
377
415
468
523
580
Air
CU AL
Amps
243 189
302 236
365 286
416 327
471 370
531 421
616 491
681 552
775 636
669 725
963 821
165
200
238
266
298
331
376
407
454
498
541
128
156
186
210
234
263
302
332
374
418
464
160
195
232
263
293
329
377
415
468
523
580
243
302
365
416
471
531
616
681
775
669
963
165
200
238
266
298
331
376
407
454
498
541
128
156
186
210
234
263
302
332
374
418
464
189
236
286
327
370
421
491
552
636
725
821
Duct
CU AL
Armoured Medium Voltage (MV) XLPE Type A,
3 Cores, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Phase Color Identification: Numbered, 1, 2 & 3
Application: Used for underground reticulation, main distribution
system, sub-stationand mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
3.8/6.6kV - 3 Cores SWA
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall Cable Mass
Screen
Size Diam.
Diameter
Diam.
mm
mm
mm2
25
6.0
14.3
35
7.2
15.5
50
8.4
16.7
70
9.9
18.2
95
11.7
20.0
120
13.4
21.7
150
14.6
22.9
185
16.4
24.7
240
18.8
27.3
300
21.4
30.3
6.35/11kV 3 Cores SWA
25
6
16.1
35
7.2
17.3
50
8.4
18.5
70
9.9
20.0
95
11.7
21.8
120
13.4
23.5
150
14.6
24.7
185
16.4
26.5
240
18.8
28.9
300
21.4
31.5
mm
43.5
46.2
50.4
53.9
58.1
62.2
65.0
70.6
76.8
84.1
CU
AL
kg/km
3531 3067
4039 3389
5194 4266
6071 4772
7182 5419
8281 6054
9388 6604
11617 8183
13886 9432
16473 10905
49.1
51.9
54.9
58.3
62.6
66.9
71.0
75.2
81.0
87.2
4425
4974
5704
6600
7734
8889
10836
12322
14559
16997
3961
4324
4776
5301
5971
6662
8052
8888
10105
11429
Drum Resistance @ Resistance @
length
20°C
90°C
Impedance
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
uf/km/phase
m
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
0.927 1.540
0.668 0.110
0.494 0.822
0.342 0.568
0.247 0.411
0.196 0.325
0.159 0.265
0.128 0.211
0.099 0.162
0.080 0.130
CU
AL
Ω/km/phase
0.935 1.543
0.678 1.119
0.506 0.829
0.357 0.577
0.265 0.422
0.217 0.338
0.183 0.280
0.155 0.229
0.131 0.183
0.116 0.155
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
kA
2.3
3.2
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
15.8
17.1
15.8
17.1
18.6
19.9
20.9
27.7
30.2
33.5
259.035
291.463
323.754
363.980
412.112
457.470
489.445
537.356
580.516
605.340
131
160
198
240
282
320
358
405
462
508
500
500
500
500
500
500
500
500
500
500
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.06
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.099
0.080
0.935
0.678
0.506
0.357
0.265
0.217
0.183
0.155
0.131
0.116
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
2.3
3.2
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
15.5
16.4
17.4
18.6
20.2
21.5
27.7
29.7
32.1
34.5
205.632
229.780
253.773
283.609
319.249
352.793
376.419
411.798
458.882
509.806
131
160
198
240
282
320
358
405
462
508
1.540
0.110
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
1.543
1.119
0.829
0.577
0.422
0.338
0.280
0.229
0.183
0.155
AL
Ground
CU AL
CU
AL
Ω/km/phase
0.727 1.200
0.524 0.868
0.387 0.641
0.268 0.443
0.193 0.320
0.153 0.253
0.124 0.206
0.099 0.164
0.075 0.125
0.060 0.099
1.200
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.099
CU
Current (I)
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
108
127
150
183
219
249
282
314
357
406
Air
CU AL
Amps
125 101
151 123
190 149
233 184
291 222
324 258
372 288
423 336
493 394
553 441
122
147
177
211
250
284
322
362
416
449
91
110
130
159
192
215
244
278
321
356
108
127
150
183
219
249
282
314
357
406
125
151
190
233
291
324
372
423
493
553
122
147
177
211
250
284
322
362
416
449
91
110
130
159
192
215
244
278
321
356
101
123
149
184
222
258
288
336
394
441
Duct
CU AL
Armoured Medium Voltage (MV) XLPE Type A,
3 Cores, Power Cable, SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Phase Color Identification: Numbered, 1, 2 & 3
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
8.7/15kV - 3 Cores Unarmoured
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Size Diam. Screen
Diameter Cable Mass
Diam.
CU
mm2
mm
mm
mm
25
35
50
70
95
120
150
185
240
6.0
7.2
8.4
9.9
11.7
13.4
14.6
16.4
18.8
14.3
15.5
16.7
18.2
20
21.7
22.9
24.7
27.3
36.9
39.6
42.4
45.9
49.9
53.8
56.6
60.7
66.7
AL
kg/km
4975
5539
6327
7250
8385
10359
11528
13109
15325
Drum Resistance
length
@ 20°C
4511
4889
5399
5951
6622
8132
8744
9676
10870
CU
m
500
500
500
500
500
500
500
500
500
AL
Ω/km/phase
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.099
0.075
1.200
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
ELECTRICAL PROPERTIES
Sym.
Asym.
Current (I)
Resistance @ Impedance Current,
Current,in Capacitance
90°C
Ground
Air
in 1sec
1sec
CU
AL
CU
AL
CU AL
CU AL CU AL
uf/km/phase
Ω/km/
Ω/km/phase
kA
Amps
phase
0.927 1.540 0.935 1.543 3.6 2.3
17.0
174.527
131 108 125 101
0.668 0.110 0.678 1.119 5.0 3.2
18.0
193.942
160 127 151 123
0.494 0.822 0.506 0.829 7.2 4.6
18.9
213.192
198 150 190 149
0.342 0.568 0.357 0.577 10.0 6.4
20.2
237.085
240 183 233 184
0.247 0.411 0.265 0.422 13.6 8.7
21.8
265.580
282 219 291 222
0.196 0.325 0.217 0.338 17.2 11.0
28.2
292.362
320 249 324 258
0.159 0.265 0.183 0.280 21.5 13.8
29.7
311.210
358 282 372 288
0.128 0.211 0.155 0.229 26.5 17.0
31.6
339.413
405 314 423 336
0.099 0.162 0.131 0.183 34.3 22.1
34.0
376.918
462 357 493 394
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Duct
CU AL
122
147
177
211
250
284
322
362
416
91
110
130
159
192
215
244
278
321
Armoured Medium Voltage (MV) XLPE Type A,
3 Cores, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Phase Color Identification: Numbered, 1, 2 & 3
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
12.7/22kV - 3 Cores SWA
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Screen
Size Diam.
Diameter Cable Mass
Diam.
mm
mm
mm2
25
6.0
20.6
35
7.2
21.8
50
8.4
23.0
70
9.9
24.5
95
11.7
26.3
120
13.4
28.0
150
14.6
29.2
185
16.4
31.0
240
18.8
33.4
300
21.4
36.0
19/33kV 3 Cores SWA
50
8.4
228.4
70
9.9
29.9
95
11.7
31.7
120
13.4
33.4
150
14.6
34.6
185
16.4
36.4
240
18.8
38.8
300
21.4
41.4
mm
59.6
62.4
65.2
70.1
74.6
78.5
81.5
85.9
91.5
97.5
CU
AL
kg/km
5644 5180
6228 5579
6959 6031
8752 7452
10031 8268
11207 8980
12447 9663
14033 10599
16302 11847
18762 13193
79.8
83.3
88.3
92.4
95.2
99.5
105.2
111.4
9748
10735
12680
13997
15249
16886
19328
21984
8820
9436
10916
11769
12465
13453
14873
16415
Drum Resistance @ Resistance @
length
20°C
90°C
Impedance
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
uf/km/phase
m
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
0.927 1.540
0.668 0.110
0.494 0.822
0.342 0.568
0.247 0.411
0.196 0.325
0.159 0.265
0.128 0.211
0.099 0.162
0.080 0.130
CU
AL
Ω/km/phase
0.935 1.543
0.678 1.119
0.506 0.829
0.357 0.577
0.265 0.422
0.217 0.338
0.183 0.280
0.155 0.229
0.131 0.183
0.116 0.155
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
kA
2.3
3.2
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
19.0
19.9
21.1
27.3
29.2
31.1
32.1
34.0
36.4
38.9
178.367
197.244
219.704
240.775
255.586
277.726
255.586
277.726
307.134
338.884
131
160
198
240
282
320
358
405
462
508
500
500
500
500
500
500
500
500
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.06
0.494
0.342
0.247
0.196
0.159
0.128
0.099
0.080
0.506
0.357
0.265
0.217
0.183
0.155
0.131
0.116
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
31.6
33.0
38.9
40.8
42.0
44.4
46.8
49.9
140.887
154.233
170.048
184.836
195.207
210.679
231.183
253.275
198
240
282
320
358
405
462
508
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
0.829
0.577
0.422
0.338
0.280
0.229
0.183
0.155
AL
Ground
CU AL
CU
AL
Ω/km/phase
0.727 1.200
0.524 0.868
0.387 0.641
0.268 0.443
0.193 0.320
0.153 0.253
0.124 0.206
0.099 0.164
0.075 0.125
0.060 0.099
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.099
CU
Current (I)
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
108
127
150
183
219
249
282
314
357
406
Air
CU AL
Amps
125 101
151 123
190 149
233 184
291 222
324 258
372 288
423 336
493 394
553 441
122
147
177
211
250
284
322
362
416
449
91
110
130
159
192
215
244
278
321
356
150
183
219
249
282
314
357
406
190
233
291
324
372
423
493
553
177
211
250
284
322
362
416
449
130
159
192
215
244
278
321
356
149
184
222
258
288
336
394
441
Duct
CU AL
Unarmoured Medium Voltage (MV) XLPE Type B,
3 Core, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Phase Color Identification: Numbered, 1, 2 & 3
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminium or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
3.8/6.6kV - 3 Cores Unarmoured
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Screen
Size Diam.
Diameter Cable Mass
Diam.
mm
mm
mm
mm2
25
6.0
14.3
36.9
35
7.2
15.5
39.6
50
8.4
16.7
42.4
70
9.9
18.2
45.9
95
11.7
20
49.9
120
13.4
21.7
53.8
150
14.6
22.9
56.6
185
16.4
24.7
60.7
240
18.8
27.3
66.7
300
21.4
30.3
73.6
6.35/11kV 3 Cores Unarmoured
25
6
16.1
41.1
35
7.2
17.3
43.9
50
8.4
18.5
46.7
70
9.9
20.0
50.1
95
11.7
21.8
54.4
120
13.4
23.5
58.3
150
14.6
24.7
61.1
185
16.4
26.5
65.1
240
18.8
28.9
70.5
300
21.4
31.5
76.5
CU
AL
kg/km
1807 1343
2195 1545
2728 1800
3422 2122
4276 2513
5126 2899
6082 3298
7224 3790
9043 4588
11068 5499
2025
2426
2973
3683
4583
5453
6424
7588
9365
11340
1561
1776
2045
2383
2819
3226
3640
4154
4911
5771
Drum Resistance @ Resistance @
length
20°C
90°C
Impedance
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
uf/km/phase
m
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
0.927 1.540
0.668 0.110
0.494 0.822
0.342 0.568
0.247 0.411
0.196 0.325
0.159 0.265
0.128 0.211
0.099 0.162
0.080 0.130
CU
AL
Ω/km/phase
0.935 1.543
0.678 1.119
0.506 0.829
0.357 0.577
0.265 0.422
0.217 0.338
0.183 0.280
0.155 0.229
0.131 0.183
0.116 0.155
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
kA
2.3
3.2
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
2.0
2.2
2.4
2.6
2.8
3.1
3.2
3.5
3.9
4.3
259.035
291.463
323.754
363.980
412.112
457.470
489.445
537.356
580.516
605.340
131
160
198
240
282
320
358
405
462
508
500
500
500
500
500
500
500
500
500
500
0.73
0.52
0.39
0.27
0.19
0.15
0.12
0.1
0.08
0.06
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.099
0.080
0.935
0.678
0.506
0.357
0.265
0.217
0.183
0.155
0.131
0.116
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
2.3
3.2
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
2.3
2.5
2.6
2.9
3.1
3.3
3.5
3.8
4.1
4.5
205.632
229.780
253.773
283.609
319.249
352.793
376.419
411.798
458.882
509.806
131
160
198
240
282
320
358
405
462
508
1.540
0.110
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
1.543
1.119
0.829
0.577
0.422
0.338
0.280
0.229
0.183
0.155
AL
Ground
CU AL
CU
AL
Ω/km/phase
0.727 1.200
0.524 0.868
0.387 0.641
0.268 0.443
0.193 0.320
0.153 0.253
0.124 0.206
0.099 0.164
0.075 0.125
0.060 0.099
1.200
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.099
CU
Current (I)
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
108
127
150
183
219
249
282
314
357
406
Air
CU AL
Amps
125 101
151 123
190 149
233 184
291 222
324 258
372 288
423 336
493 394
553 441
122
147
177
211
250
284
322
362
416
449
91
110
130
159
192
215
244
278
321
356
108
127
150
183
219
249
282
314
357
406
125
151
190
233
291
324
372
423
493
553
122
147
177
211
250
284
322
362
416
449
91
110
130
159
192
215
244
278
321
356
101
123
149
184
222
258
288
336
394
441
Duct
CU AL
Unarmoured Medium Voltage (MV) XLPE Type B,
3 Core, Power Cable , SANS 1339
Conductor: Annealed Copper or Aluminium Circular
Compacted - Class 2
Phase Color Identification: Numbered, 1, 2 & 3
Application: Used for underground reticulation, main distribution
system, sub-station and mining. Can be manufactured with
corrugated aluminum or steel tape. Outer-sheath can also be
stripped blue or white according to customer requirements.
12.7/22kV - 3 Cores Unarmoured
PHYSICAL PROPERTIES
Insulation
Cable Core
Overall
Screen
Size Diam.
Diameter Cable Mass
Diam.
mm
mm
mm2
25
6.0
20.6
35
7.2
21.8
50
8.4
23.0
70
9.9
24.5
95
11.7
26.3
120
13.4
28.0
150
14.6
29.2
185
16.4
31.0
240
18.8
33.4
300
21.4
36.0
19/33kV 3 Cores Unarmoured
50
8.4
28.4
70
9.9
29.9
95
11.7
31.7
120
13.4
33.4
150
14.6
34.6
185
16.4
36.4
240
18.8
38.8
300
21.4
41.4
mm
51.6
54.4
57.2
60.6
64.7
68.6
71.6
75.6
81.2
87.0
CU
AL
kg/km
2679 2216
3116 2466
3697 2770
4450 3151
5373 3610
6289 4062
7330 4546
8543 5109
10427 5972
12435 6867
69.7
73.2
77.2
81.3
84.1
88.2
93.7
99.5
4707
5509
6489
7501
8548
9819
11784
13873
3779
4209
4726
5274
5764
6385
7329
8304
Drum Resistance @ Resistance @
length
20°C
90°C
Impedance
ELECTRICAL PROPERTIES
Sym.
Asym.
Current, in Current,in Capacitance
1sec
1sec
uf/km/phase
m
500
500
500
500
500
500
500
500
500
500
CU
AL
Ω/km/phase
0.927 1.540
0.668 0.110
0.494 0.822
0.342 0.568
0.247 0.411
0.196 0.325
0.159 0.265
0.128 0.211
0.099 0.162
0.080 0.130
CU
AL
Ω/km/phase
0.935 1.543
0.678 1.119
0.506 0.829
0.357 0.577
0.265 0.422
0.217 0.338
0.183 0.280
0.155 0.229
0.131 0.183
0.116 0.155
3.6
5.0
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
kA
2.3
3.2
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
2.9
3.1
3.3
3.5
3.7
4.0
4.1
4.4
4.7
5.1
147.703
163.122
178.367
197.244
219.704
240.775
255.586
277.726
307.134
338.884
131
160
198
240
282
320
358
405
462
508
500
500
500
500
500
500
500
500
0.39
0.27
0.19
0.15
0.12
0.1
0.08
0.06
0.494
0.342
0.247
0.196
0.159
0.128
0.099
0.080
0.506
0.357
0.265
0.217
0.183
0.155
0.131
0.116
7.2
10.0
13.6
17.2
21.5
26.5
34.3
42.9
4.6
6.4
8.7
11.0
13.8
17.0
22.1
27.6
4.0
4.2
4.5
4.7
4.9
5.1
5.5
5.8
140.887
154.233
170.048
184.836
195.207
210.679
231.183
253.275
198
240
282
320
358
405
462
508
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
0.829
0.577
0.422
0.338
0.280
0.229
0.183
0.155
AL
Ground
CU AL
CU
AL
Ω/km/phase
0.727 1.200
0.524 0.868
0.387 0.641
0.268 0.443
0.193 0.320
0.153 0.253
0.124 0.206
0.099 0.164
0.075 0.125
0.060 0.099
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.099
CU
Current (I)
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
108
127
150
183
219
249
282
314
357
406
Air
CU AL
Amps
125 101
151 123
190 149
233 184
291 222
324 258
372 288
423 336
493 394
553 441
122
147
177
211
250
284
322
362
416
449
91
110
130
159
192
215
244
278
321
356
150
183
219
249
282
314
357
406
190
233
291
324
372
423
493
553
177
211
250
284
322
362
416
449
130
159
192
215
244
278
321
356
149
184
222
258
288
336
394
441
Duct
CU AL
All Aluminium Alloy Conductors (AAAC) Overhead Conductors
Cable Description: All Aluminium Alloy Conductors (AAAC)
Application: Used for overhead power lines
Specification: SANS 182 & IEC 61089
CODE Name
ACACIA
ALMOND
CEDAR
35
FIR
HAZEL
PINE
70
WILLOW
80
90
OAK
100
MULBERRY
ASH
ELM
POPLAR
225
SYCAMORE
UPAS
350
YEW
Equival.
copper
area
mm²
13
16
19
22
25
32
38
45
48
51
58
63
63
80
96
112
119
143
161
192
224
254
Stranding
and wire
diameter
mm
7/2,08
7/2,34
7/2,54
7/2,77
7/2,95
7/3,30
7/3,61
7/3,91
7/4,04
7/4,19
7/4,45
7/4,65
19/2,82
19/3,18
19/3,48
19/3,76
37/2,87
37/3,05
37/3,23
37/3,53
37/3,81
37/4,06
Overall Aluminium
diameter
area
mm
6,24
7,02
7,59
8,31
8,85
9,9
10,83
11,73
12,12
12,57
13,35
13,95
14,1
16,9
17,4
18,8
20,09
21,35
22,61
24,71
26,67
28,42
mm²
23,79
30,1
35,47
42,18
47,84
59,87
71,65
84,05
89,73
96,52
108,9
118,9
118,7
150,9
180,7
210,9
239,4
270,3
303,2
362,1
421,8
479
Mass
kg/km
65
82
97
115
131
164
196
230
245
264
298
325
326
415
497
580
660
744
835
997
1162
1319
Ultimate
tensile
strength
Newton
6690
8440
9960
11860
13430
16820
20200
23630
25200
27060
30400
33330
33330
42350
50690
59220
67350
75780
85000
101670
118430
134510
Coefficient
Initial
final
DC
of linear modulus of modulus of resistance
expansion elasticity elasticity
at 20°C
/C°x10-6
MPa
MPa
Ω/km
23
52500
61000
1,39
23
52400
61000
1,1
23
52400
61000
0,934
23
52400
61000
0,785
23
52400
61000
0,692
23
52400
61000
0,553
23
52400
61000
0,462
23
52400
61000
0,394
23
52400
61000
0,369
23
52400
61000
0,343
23
52400
61000
0,306
23
52400
61000
0,279
23
49650
59650
0,28
23
49650
59650
0,221
23
49650
59650
0,184
23
49650
59650
0,158
23
48250
58600
0,139
23
48250
58600
0,123
23
48250
58600
0,11
23
48250
58600
0,0921
23
48250
58600
0,0791
23
48250
58600
0,0696
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Current
rating
A
133
153
169
189
204
235
262
290
302
316
339
359
359
416
467
513
551
600
643
718
789
853
Standard
drum
length
m
3000
2500
2500
2500
2500
2500
2500
2000
1500
1500
1000
1000
2000
2000
2000
2000
2000
2000
2000
2000
1500
1500
All Aluminium Conductors (AAC) Overhead Conductors
Cable Description: All Aluminium Conductors (AAC)
Application: Used for overhead power lines
Specification: SANS 182 & IEC 61089
Code Name
MIDGE
APHIS
GNAT
WEEVIL
MOSQUITO
LADYBIRD
ANT
FLY
BLUEBOTTLE
EARWIG
GRASSHOPPER
CLEGG
WASP
BEETLE
BEE
CRICKET
HORNET
CATERPILLAR
CHAFER
SPIDER
COCKROACH
BUTTERFLY
MOTH
DRONE
LOCUST
CENTIPEDE
MAYBUG
SCORPION
CICADA
TARANTULA
Area of Aluminium
Nominal
(mm²)
22
25
25
30
35
40
50
60
70
75
80
90
100
100
125
150
150
175
200
225
250
300
350
350
400
400
450
500
600
750
Actual
(mm²)
23,33
24,89
26,85
31,56
36,88
42,79
52,83
63,55
73,65
78,55
84,05
95,6
106
106,4
132
157,9
157,6
185,9
213,2
237,6
265,7
322,7
373,1
372,4
428,7
415,2
486,1
529,8
628,3
794,9
Stranding N. of
wires X Diam.
Nominal
Diameter of
Conductor
Nominal Mass
Rated Strength
Current Carrying
Capacity (Amperes)
Electrical Resistance
at 20°C Maximum
(mm)
7X2,06
3X3,35
7X2,21
3X3,66
7X2,59
7X2,79
7X3,10
7X3,40
7X3,66
7X3,78
7X3,91
7X4,17
7X4,39
19X2,67
7X4,90
7X5,36
19X3,25
19X3,53
19X3,78
19X3,99
19X4,22
19X4,65
19X5,00
37X3,58
19X5,36
37X3,78
37X4,09
37X4,27
27X4,65
27X5,23
(mm)
6,18
7,21
6,63
7,87
7,77
8,37
9,3
10,2
10,98
11,34
11,73
12,51
13,17
13,35
14,7
16,08
16,25
17,65
18,9
19,95
21,1
23,25
25
25,06
26,8
26,46
28,63
29,89
32,55
36,61
(kg/kg)
64,3
68,6
74
87
101,7
118
145,7
175,2
203,1
216,6
231,7
263,6
292,2
293,3
363,9
435,3
434,5
512,5
587,8
655,1
732,6
889,7
1028
1027
1182
1145
1340
1461
1732
2068
(kN)
4,26
4,38
4,9
5,12
6,37
7,39
8,62
10,37
12,02
12,82
13,31
15,14
16,79
17,81
20,91
24,21
24,91
29,39
33,71
36,46
40,77
49,52
57,25
57,51
63,79
64,23
72,99
79,44
94,34
119,4
Amperes)
135
150
150
170
185
200
230
260
285
290
310
340
360
365
415
470
470
520
570
610
655
745
820
815
890
875
970
1020
1115
1295
(ohm/km)
1,23572
1,15827
1,07372
0,91348
0,7817
0,67374
0,5457
0,45365
0,39144
0,36702
0,343
0,30156
0,27197
0,27095
0,2184
0,18258
0,18292
0,15508
0,13522
0,12134
0,1085
0,08934
0,07727
0,07741
0,06725
0,06943
0,0593
0,05451
0,04588
0,3626
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Aluminium Conductor Steel Reinforced
(ACSR) Overhead Conductors
Cable Description: Aluminium Conductor Steel Reinforced
Application: Used for overhead power lines
Specification: SANS 182 & IEC 61089
Equival.
Copper
area
Stranding
and wire
diameter
MOLE
SQUIRREL
GOPHER
WEASEL
FOX
FERRET
RABBIT
MINK
SKUNK
BEAVER
HORSE
RACCOON
OTTER
CAT
HARE
DOG
mm²
6,45
12,9
16,3
19,35
22,58
25,81
32,26
38,71
38,71
45,16
45,16
48,39
51,61
58,06
64,52
64,52
HYENA
64,52
LEOPARD
80,65
COYOTE
80,65
TIGER
WOLF
LYNX
PANTHER
LION
BEAR
GOAT
SHEEP
ANTELOPE
BISON
DEER
ZEBRA
ELK
CAMEL
MOOSE
80,65
96,77
112,9
129
145,2
161,3
193,5
225,8
225,8
225,8
258,1
258,1
290,3
290,3
322,5
mm
6/1/1,50
6/1/2,11
6/1/2,36
6/1/2,59
6/1/2,79
6/1/3,00
6/1/3,35
6/1/3,66
12/7/2,59
6/1/3,99
12/7/2,79
6/1/4,09
6/1/4,22
6/1/4,50
6/1/4,72
6/4,72
4,458598726
7/4,39
3,626943005
6/5,28
4
26/2,87
3,664921466
30/7/2,36
30/7/2,59
30/7/2,79
30/7/3,00
30/7/3,18
30/7/3,35
30/7/3,71
30/7/3,99
54/7/2,97
54/7/3,00
30/7/4,27
54/7/3,18
30/7/4,50
54/7/3,35
54/7/3,53
Code name
Diameter Overall Aluminium Steel area
over steel diameter
area
(Std.)
Total
area
Ultimate
tensile
strength
Mass kg/km
cient Initial
Breaking Coeffi
of linear modulus
load
of
expansion elasticity
Final
DC
modulus resistance Current
of
at 20°C
rating
elasticity
(Std)
Standard
drum
length
Aluminium
Steel
Total
29,2
57,7
72,2
87
101
117
145
174
175
206
203
217
231
263
289
289
13,9
27,5
34,4
41,5
48,1
55,6
69,4
82,8
292
98,4
338
103
110
125
138
100
43,1
85,2
107
129
149
173
214
257
467
304
541
320
341
388
427
389
newtons
4780
8020
9610
11450
13100
15200
18500
21900
52900
25900
60700
27200
28900
32800
36000
34700
kg
487
818
990
1160
1340
1530
1890
2230
5390
2640
6190
2770
2950
3340
3670
3540
/C° x10-6
19,31
19,31
19,31
19,31
19,31
19,31
19,31
19,31
15,84
19,31
15,84
19,31
19,31
19,31
19,31
19,92
N/mm²
65000
54600
52700
51500
50700
50200
49500
49100
71900
48800
71000
48700
48700
48500
48500
48800
N/mm²
80400
80400
80400
80400
80400
80400
80400
80400
108000
80400
108000
80400
80400
80400
80400
76400
ohms/km
2,7062
1,3677
1,0933
0,9077
0,7822
0,6766
0,5426
0,4546
0,4571
0,3825
0,3939
0,364
0,03419
0,3007
0,2733
0,2733
amps
87
130
150
170
190
210
240
260
270
290
300
300
310
340
360
360
m
3000
3000
3000
2500
2500
1500
1500
1500
2000
1500
2000
1500
1500
1500
1500
2000
126,43
291
162
453
41900
4270
18,93
52400
82200
0,2697
360
2000
16,84
148,21
361
133
494
42200
4300
19,54
47800
76300
0,2184
410
2000
131,74
20,06
151,8
365
159
524
47300
4820
19,54
51900
76000
0,3035
420
2000
131,23
158,06
183,41
212,06
238,27
264,42
324,31
375,11
374,11
381,7
429,6
428,88
477,13
475,96
528,49
30,62
36,88
42,8
49,48
55,6
61,7
75,67
87,53
48,5
49,48
100,24
55,6
111,33
61,7
68,51
161,85
194,94
226,2
261,54
293,86
326,12
399,98
462,63
422,6
431,18
529,84
484,48
588,46
537,66
596,99
364
438
508
588
660
733
899
1040
1040
1060
1190
1190
1320
1320
1460
242
292
330
391
440
488
598
692
383
391
792
440
880
488
542
606
730
846
970
1100
1220
1500
1730
1420
1450
1980
1630
2200
1810
2000
58700
69200
79300
90800
101000
112000
136000
157000
117000
119000
179000
133000
199000
147000
162000
5980
7050
8080
9260
10300
11400
13900
16000
11900
12100
18200
13600
20300
15000
16500
18,43
18,43
18,43
18,43
18,43
18,43
18,43
18,43
19,91
19,91
18,43
19,91
18,43
19,91
19,91
56900
55700
54900
54300
53900
53600
53100
52900
47700
47600
52800
47300
52700
47000
46700
83400
83400
83400
83400
83400
83400
83400
83400
73200
73200
83400
73200
83400
73200
73200
0,2202
0,1828
0,1576
0,1363
0,1213
0,1093
0,0891
0,077
0,0773
0,0757
0,0673
0,0674
0,0606
0,0607
0,0547
420
470
520
560
610
650
730
800
790
800
870
860
930
920
980
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
1500
2000
2000
2000
mm
1,5
2,11
2,36
2,59
2,79
3
3,35
3,66
7,77
3,99
8,37
4,09
4,22
4,5
4,72
4,71
mm
4,5
6,33
7,08
7,77
8,37
9
10,05
10,98
12,95
11,97
13,95
12,27
12,66
13,5
14,16
14,15
mm²
10,6
20,98
26,25
31,61
36,68
42,41
52,88
63,13
63,22
75,02
73,36
78,83
83,92
95,43
104,98
104,98
mm²
1,77
3,5
4,37
5,27
6,11
7,07
8,81
10,52
36,88
12,5
42,8
13,14
13,99
15,9
17,5
12,7
mm²
12,37
24,48
30,62
36,88
42,8
49,48
61,7
73,65
100,1
87,53
116,16
91,97
97,91
111,33
122,48
117,69
5,79
14,57
105,95
20,48
5,25
15,81
131,37
5,73
15,89
4,72
7,77
8,37
9
9,54
10,05
11,13
11,97
8,91
9
12,81
9,54
13,5
10,05
10,59
16,52
18,13
19,53
21
22,26
23,45
25,97
27,93
26,73
27
29,89
28,62
31,5
30,15
31,77
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
Flexible PVC Insulated Submersible Pump Cable, Low Voltage
Power Cable 0.6/1 kV, SABS 1574, 70ºC
Conductor: Flexible Copper – Class 5
Insulation: PVC Nitrile Flexible Grade
Sheathing: PVC Nitrile Flexible Grade
Phase Color Code: Red , Yellow, Blue or Black
Application: Used for outdoors and indoors, mobile, portable and
fixed pumping equipment. Three core with blue outer-sheath and
four cores with green outer-sheath.
Flexible PVC Submersible Pump Cable - 600/1000V
PHYSICAL PROPERTIES
Approximate Diameter
Cable Size
Cond. Diam. Insul. Diam.
3C
4C
2
mm
mm
mm
mm
mm
1.5
1.7
3.3
9.7
10.7
2.5
2.2
3.8
10.8
11.9
4
2.6
4.6
12.9
14.7
6
3.9
5.9
16.0
18.2
10
4.7
7.2
19.3
21.8
16
5.8
8.4
22.1
25.3
25
7.3
10.2
26.7
30.2
35
9.4
12.3
32.0
36.1
50
11.2
14.5
37.9
43.1
70
13.1
16.4
41.8
47.6
95
15.3
19.1
49.0
55.6
Approximate Mass
3C
Kg/km
120
160
240
345
520
740
1125
1552
2205
2870
3925
4C
kg/km
145
195
310
445
660
970
1440
1980
2835
3700
5040
Drum length
m
500
500
500
500
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC
Resistance @ Symmetrical
Current in Air
Current
20°C
Ω/km/phase
kA(1 sec)
Amps
13.300
0.2
16
7.980
0.3
20
4.950
0.5
25
3.300
0.7
34
1.910
1.2
47
1.210
1.8
63
0.780
2.9
83
0.554
4.0
102
0.386
5.8
124
0.272
8.1
158
0.206
10.9
192
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
PVC Nitrile Trailing Cable, Low Voltage Power Cable 0.6/1 kV,
SABS 1574, 70ºC
Conductor: Flexible Copper – Class 5
Insulation: PVC Nitrile Flexible grade
Sheathing: PVC Nitrile Flexible Grade
Phase Color Code: Red, Yellow, Blue or Black
Application: Used for outdoors and indoors, mobile, portable and
fixed pumping equipment.
PVC Nitrile Trailing Cable - 600/1000V
Cable Size
Cond. Diam.
mm
1.5
2.5
4
6
10
16
25
35
50
70
95
mm
1.7
2.2
2.6
3.9
4.7
5.8
7.3
9.4
11.2
13.1
15.3
2
PHYSICAL PROPERTIES
Approximate
Insul. Diam.
Diameter
mm
mm
3.3
10.7
3.8
11.9
4.6
14.7
5.9
18.2
7.2
21.8
8.4
25.3
10.2
30.2
12.3
36.1
14.5
43.1
16.4
47.6
19.1
55.5
Approximate
Mass
Kg/km
150
202
320
456
680
990
1470
2015
2890
3760
5120
Drum length
m
500
500
500
500
500
500
500
500
500
500
500
ELECTRICAL PROPERTIES
DC Resistance
Symmetrical
Current in Air
@ 20°C
Current
Ω/km/phase
kA(1 sec)
Amps
13.300
0.2
16
7.980
0.3
20
4.950
0.5
25
3.300
0.7
34
1.910
1.2
47
1.210
1.8
63
0.780
2.9
83
0.554
4.0
102
0.386
5.8
124
0.272
8.1
158
0.206
10.9
192
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.
TROLLEY WIRE
Conductor: Copper Rod with Groove
Application: Used for fixed electric traction insulation
Specification: BS EN 50149 + Customer
PHYSICAL PROPERTIES
Cable Size
mm2
81
107
161
MECHANICAL & ELECTRICAL PROPERTIES
Approx.
Diameter
mm
10.6
12.3
15.0
Approximate
Mass
Kg/km
711
951
1431
Drum length
Tensile
Strength
Hardness
Torsion Test
Bending Test
DC Resistance
@ 20°C
m
1000
1000
1000
355
350
318
54
54
54
5
5
5
5
5
5
0.229
0.170
0.108
Note: Red Stripe – Fire Retardant Cable (FR) White Stripe – Halogen Free Cable (HFC) Blue Stripe – Low Halogen Cable (LHC)
Diagrams of cables are illustrative only and not necessarily to scale. General Cable SUB-SAHARA Africa reserves the right to change or vary the
construction of any of their product without notice. Whilst every care has been taken in the preparation of this publication, General Cable SUB-SAHARA
Africa accept no liability of any kind and are not responsible for results of any action on the basis of this information or resulting from errors or
omission. This technical data sheet is intended as a guide only, any person using it must make reference to appropriate local standards or authorities.