PLESE, DO NOT DELETE THIS TABLE AND DO NOT WRITE IN IT! THE TABLE WILL BE DELETED AND REPLACED WITH AN APPROPRIATE TEXT IN THE PROCESS OF TECHNICAL PROCESSING OF THE CONFERENCE PROCEEDINGS! Antun Foškulo, dipl.ing.el. Končar – Power Plant and Electric Traction Engineering Inc. antun.foskulo@koncar-ket.hr COMPLETE UTILIZATION OF BAY WIDTH IN A DOUBLE BUSBAR HV SWITCHYARD OF LOW-RISE (CLASSICAL) LAYOUT ABSTRACT Complete utilization of bay width in a double busbar switchyard of low-rise (classical) layout is achievable by means of adding an additional bay inside the space that was left unused and therefore empty according to a classical layout. By doing so switchyard area reduction can be achieved meaning lower cost for the investment. This article lists conceptual differences between these two layouts by limiting only on primary equipment types and its position and function. Additional equipment that is necessary for layout realization is also listed. Apart from giving graphical illustrations for both concepts some of the basic advantages and disadvantages are mentioned. Key words: switchyard, low-rise classical layout, diameter, complete utilization 1. INTRODUCTION AND OBJECT OF THE ANALYSIS Usual way for developing double busbar HV switchyards involves installation of HV equipment inside the bay width while at the same time such bay width is only used for one HV bay which may be oriented either towards power transformer or towards overhead line. The rest of the space with the same width is left to be empty and therefore unused. Possible usage of such an empty space not only does potentially reduce the switchyard area but may also reduce potential investments. For the purpose of graphical illustrations a 110 kV substation shall be used with its general layout given inside the figure 1. Orientation equipment alignment and positions were defined inside the Tender. Investor / Client and its Consultant / Representative leave the possibility of defining and offering such alternative solutions as long as the orientation of OHLs defined inside the Tender are respected. Additional requirements for providing space for two future bays were stated of which one has already prepared infrastructure while for another an extension of busbar system need to be provided. Figure 1. Top view of classical low-rise layout 2. OBJECTIVES Intention of this article apart from proposing another way for obtaining switchyard area reduction is to present this concept to a wider audience. Such a concept was detected during the bidding stage for substations in Iraqi region of Kurdistan and can be viewed upon as a rare concept since it is not covered or even mentioned inside the manuals provided by leading manufacturers of electric equipment. Furthermore, such a concept is not even mentioned inside the essential literature required on faculties when dealing with power engineering. 3. SOLUTION CONCEPT 3.1 Basis of the solution In order to reduce switchyard area, using of empty space inside the bay's width is proposed by means of installing HV equipment that forms another HV bay. Single line diagram representing such a solution is given by figure 3. while top view of such a solution can be seen on the figure 4. Figure 2. depicts single line diagram for a classical low-rise layout concept which is fully consistent with a substation top view that is given as figure 1. This kind of conceptual solution enables the definition of a diameter (if indeed preferred), otherwise already known inside the breaker-and-a-half and breaker-and-a-third switchyards. According to the existent bay types inside the case given by figures 2. and 3., a diameter could be comprised of the following combinations : • • • • Transformer - transformer bay Transformer – coupling bay Transformer – OHL bay Transformer – empty bay Figure 2. Single line diagram of existing switchyard concept • • • • OHL – OHL bay OHL – coupling bay OHL – empty bay Coupling – empty bay Figure 3. Single line diagram of proposed switchyard concept Empty bays defined just above as empty spaces can be upgraded to become : • • • Generator bays (is generator exists nearby) Compensation bays Metering bays (if they contain disconnectors and are not placed beneath and at the end of the busbars) Figure 4. Top view for proposed switchyard consisting of 6 diameters A diameter that is comprised of just one bay is given by figure 6. while a completely filled diameter can be seen on the figure 7. 3.2 Conceptual differences Low-rise (classical) layout for HV switchyard is characterized by the existence of a branch line which leads toward the circuit breaker and at the same time is risen above the busbar system. For such a concept to be feasible, high portals are required to be made, [1]. One portal must be placed between the busbar systems and another one represents outgoing (terminal) portal. This can be seen on the figure 5. Figure 5. Top view and side view for a classical low-rise layout Since the existence of the busbar systems (including the gantry in-between) and a terminal gantry is not questionable within the new concept, still by comparing it with a classical concept some differences were detected. 3.2.1 Quantities and types of primary equipment There are no differences in quantities of primary equipment between these two concepts. However, differences in primary equipment types are present and are manifested only on busbar disconnectors. While a classical low-rise layout required the presence of two busbar disconnectors of parallel type per bay, new concept requires substitution of one parallel disconnector with one line type disconnector per bay. Such line type disconnector is used to establish collection points on its poles and for continuation of line towards the circuit breaker. Types for other primary equipment can be left unchanged. 3.2.2 Position and function of primary equipment at bay level If we take into account that the primary equipment’s position within the bay are optimized for both concepts, only difference can be noticed in the position of busbar disconnectors. Both of busbar disconnectors of parallel type within the classical concept are placed opposite one another with the busbar centerline in between them and both of them must be moved in one or the other side of diameter thus losing their function for providing the joint connection point through connection of their nearer poles. These disconnectors shall serve another purpose by establishing connection on the same busbar system. Which busbar system they shall connect to depend on their position (under which busbar system are placed). Further poles on parallel disconnectors once used for providing connection towards different busbar systems now are used for providing current connection towards line disconnectors. Figure 7. OHL bay and transformer bay inside the diameter Figure 6. One OHL bay inside the diameter 3.2.3 Realization and the function of jointing / suspension equipment While classical layout involves cambering of only one busbar system, within the proposed concept cambering of both busbar systems is included and is independent of the number of bays which are installed within the diameter. Connection (branch) line between the central portal and the outgoing (terminal) portal inside the classical concept was uninterrupted thus forming the single circuit. However, new concept proposes the splitting of the same branch line on two parts by installing the insulator string somewhere in the middle of the branch line. Same rule applies on the branch line located on the opposite side of the central gantry. Both parts of such a divided line in-between connected with the rope of the same cross-section are enabling the transfer of the voltage from the busbars towards the poles of the line disconnector. By enabling so, voltage is taken from the busbar system that is not the nearest one. Everything described and mentioned above is illustrated on the following figure. Figure 8. Connections to be realized Connection between the other bay’s disconnector within the diameter can be made by means of tubular conductors or by rope. 3.2.4 Symmetry of phase conductors An overall symmetry of phase conductors cannot fully be achieved due to the presence of line disconnector. Positional variations of phase conductors and the variations in distance between the phases can be seen on the figure 4. and be visually compared with figures 1. and 5. representing the classical concept. Figure 9. Isometric view on an overall switchyard proposed 4. COMPARISON, ADVANTAGES AND DISADVANTAGES As any concept has its own advantages and disadvantages, this one is no exception. Some of the advantages and disadvantages of the proposed concept were detected and are given in the following text after the comparison. Proposed concept and its impact on a look of a whole substation can be seen on the figure 9. 4.1 Comparison For comparison purposes substation dimensions (length and width) are of prime importance along with the substation area information. Information of secondary importance for comparison can be defined as high portal columns number and number of spare bays that are available. Table 1. Table of comparison between two concepts PARAMETER CLASSICAL CONCEPT PROPOSED CONCEPT DIFFERENCE (%) Length (m) Width (m) Substation area (m2) No. of high portal columns No. of spare bays available 184 116 21344 30 2 130,5 117 15268,5 21 3 -29,1% +0,85% -28,5% -30% +50% 4.2 Concept advantages Some of the noticed advantages of the proposed concept are: • • • • • 4.3 less total substation area lesser operational substation costs in regards to outdoor lighting due to lesser lamps installed possible maintain of overhead line continuity regarding the incoming and outgoing OHL bays (inside the same diameter) less number of portal columns with their own foundations higher number of spare bays Concept disadvantages Some of the noticed disadvantages of the proposed concept are : • • • 5. higher switchyard complexity harder maintenance due to the proximity of installed primary and jointing / suspension equipment especially when performing tasks in the proximity of live voltage disparity in range between the phases inside the diameter CONCLUSION Presented concept even though more complicated in its concept than the classical one is feasible and therefore outdoor HV switchyard area can be reduced. Switchyard area reduction leads towards some other savings, mainly some operational savings due outdoor lighting, some constructional savings due to the reduced length of earthing system, less excavations tasks are needed to be performed (either manually or by mechanization) and so on. Savings based upon the number of gantry columns of high portals and their own foundations are mainly due to better planning and better alignment. Additional diameter can deliver two spare bays instead of one what was the case with classical layout. 6. [1] LITERATURE Požar, H. Visokonaponska rasklopna postrojenja. Zagreb : Tehnička knjiga, 1990.