Double Busbar Switchgear up to 12 kV

01
AIR INSULATED SWITCHGEAR
WBD
Double Busbar Switchgear
up to 12 kV
G8JZ0708_1
To ensure continuous power supply, utilities, industries and infrastructure
applications require effective distribution systems.
Based on our almost 100 years of experience providing air-insulated
switchgear - and with thousands of units installed around the world - WBD
is a reliable distribution network solution. It is characterized by high technical
reliability, low maintenance costs, reduced space requirements and intuitive
user guidance.
PM100919
Double busbar system for optimized network availabilty
The metal-enclosed medium voltage switchgear WBD is available at rated
voltages up to 12 kV, rated currents up to 3150 A and rated short time
withstand current up to 31.5 kA. WBD is characterized by a space saving
design, and it ensures high personnel safety in case of an internal fault.
The vacuum circuit breakers, switch disconnectors and vacuum contactors
are mounted on easy-to-handle and precisely operating slide-in modules.
Thanks to the modular construction and functional front panel design, easy
access to the individual functional cubicle compartments for inspections and
maintenance is ensured.
The partition class LSC 2B-PM (Loss of Service Continuity) double busbar
system with metallic partition (PM) offers enhanced operational flexibility and
service continuity during network upgrading or maintenance. The double
busbar systems are switched by disconnectors that act as system switches,
which are electromechanically interlocked, both mutually and in relation to
the circuit breaker.
The switchboards can be extended on both ends without busbar outage.
CUSTOMER BENEFITS
WBD offers all types of functions such as circuit breaker, contactor or switch
disconnector, direct incomer, feeder as well as coupler or metering, allowing
you to develop your project, whatever the scheme.
• Safe and user-friendly operation
• Internal arc tested in each compartment
according to IEC 62271-200
• Space saving cubicle width of 600 mm
and 800 mm
• Optimized network availability
• Network upgrading without outages
• Environmentally compatible, easy to
recycle
It meets IEC 62271-200 requirements.
02
WBD
Safety and ease of operation
WBD’s double busbar system ensures high operating safety thanks to its
metallic partition. The cubicle’s compartments are segregated by earthed
metal panels.
PM100920
AIR INSULATED SWITCHGEAR
Moreover each compartment incorporates independent pressure relief
flaps and completely separated gas exhausts, avoiding pollution in other
compartments in case of internal arc fault. The gases are expelled at the
top of the cubicle for improved safety.
All operations are performed with the front door closed. A comprehensive
range of mechanical interlocks reinforced by interrogation interlocks prevent
operational errors. These intelligent security interlocks are immune to external
force, resulting in a safer environment for both plant and personnel. The
metallic busbar and cable connection compartment cladding is provided with
pressure-tight shutters. They ensure protection against accidential contact
even when the module has been slide out.
The design of WBD ensures excellent individual compartment accessibility.
The horizontal metal plate between cable connection and circuit breaker
compartment can be quickly and easily demounted, giving access for
installation, inspection and testing in the cable connection compartment.
In addition, the spacious low voltage compartment makes access to the
various switching devices for routine protection tests comfortable, even with
maximum equipment.
1 - Low voltage compartment
2 - Module with vacuum circuit breaker
3 - Busbar system 1 with disconnector as
system switch
4 - Busbar system 2 with disconnector as
system switch
5 - Pressure relief duct for opposite slide-in
contact circuit breaker compartment
6 - Pressure relief duct for cable connection
compartment
7 - Shutters
8 - Opposite slide-in contact
9 - Current transformers
10 - Earthing switch
11 - Rotary shaft drive for earthing switch
12 - Door circuit breaker
13 - Cable connection compartment
Rated voltage
kV
12
Rated lightning impulse withstand voltage
kV
75
Rated power frequency withstand voltage
kV
28
Rated peak withstand current
up to kA
80
Rated short time withstand current
up to kA
31.5/1s*
Rated frequency
Hz
50/60
up to A
up to A
up to A
3150
2200
3150
kA-1s
31.5
Rated normal current
- Busbar
- T-offs
- T-offs with cooler
Internal arc classification IAC AFLR according to
IEC 62271-200
Loss of service continuity category LSC according
to
PM100917
Technical characteristics
LSC 2B-PM
Products-WBD-EN© 2011 Schneider Electric. All rights reserved.
Degree of protection: IP 2X even for open door and module in disconnecting position, IP 3X to the busbar; outside IP 52 possible
* 3s on request
Dimensions in mm (H x W x D)
WBD 6/12-2/623 up to 25 kA and 1250 A*
3000
600
1700
WBD 8/12-2/823
3000
800
1700
* 31.5 kA on request