LV Circuit Components Bussmann ® A wide range of circuit components catering for the busy end-user installer are available to - BS, IEC, UL and CSA standards. Bussmann offer a global package to meet most circuit protection solutions. The range of circuit components includes fuse holders, fuse banks, fuse bases/blocks and switch disconnectors (skeleton). CAMASTER: The innovative BS fuse holder incorporating a cam action built into the fuse carrier for ease of removal from the base. OPM 1038 Series: offers unbeatable protection against short circuit damage, in eight combinations, for a broader coverage of todays process control panel applications. Modular Fuse Holders: A global solution in a 10 x 38mm package. The CH and CH--E will accommodate fuse links manufactured to European and USA standards, ensuring circuit protection up to 32 amps. 1 CAMASTER HRC Fuse Holders Bussmann ® A patented range of fully shrouded HRC Fuse Holders designed to accommodate offset bolted tag HRC fuse links to BS88: Parts 1 & 2; IEC 269-1 & 2. The compact dimensioned 32A Fuse Holder, type CM32FC accepts the A1 size fuse link NITD 2 to 32 Amps. The standard 32A fuse holder, type CM32F accepts the A2 size fuse link AAO - 2 to 32Amp. The 63A unit, type CM63F, accepts the A3 size fuse link BAO - 40 to 63 Amp and the 100A unit, type CM100F, accepts fuse link type OSD - 80 to 100 Amps, which has compact A3 fixing centres. The Fuse Holders are supplied as front connecting as standard but can be readily converted to front/back stud or double back stud connection types at the point of installation, using the appropriate size back stud accessories. CAMASTER Fuse Holders are offered with the following features Advanced patented design incorporating a high level of innovation, with enhanced performance characteristics. CAMASTER Fuse Holders fully comply with the requirements of BS88 section 2.2 (IEC269-2-1, section 2) and the 16th edition of the IEE Wiring Regulations (BS7671). The fuse carriers are fitted with a cam action for ease of removal from the fuse base. The design ensures high contact pressure between the fuse carrier contacts and the base contacts, with a corresponding enhanced electrical performance level. CAMASTER Fuse Holders have a unique channel and guide arrangement which prevents any tilting of the fuse carrier when it is being inserted or removed, eliminating any likelihood of inadvertent contact with live metal. Fixing screws to the fuse carrier are held in captive hinges, providing ease of fixing and preventing loss during installation. The hinges also act as pressure plates thereby reducing the contact resistance between the fuse link tags and the carrier contact. Cable terminations fully meet the requirements of Sub-clause 7.1.7 terminals of IEC947: Part 1 Low Voltage Switchgear and Controlgear. CAMASTER Fuse Holders, as standard, provide both bolted panel and DIN rail mounting features. When DIN rail mounted all ratings of fuse holder give equal height and depth above and below the DIN rail. Non removable full shrouding of live parts within the fuse base provided by the use on hinged shields which cannot be omitted during installation and are designed so that insertion of the fuse carrier can only be made with them correctly positioned. Neon clip-in indicator accessories are available, the neon being lit when the fuse link has operated. (Minimum system operation 90V). The fuse carrier has a marking label for ease of circuit identification. Ganging can be readily achieved by the use of standard accessories, providing improved safety related to isolation and protection of 2 and 3 pole electrical circuits. 2 Bussmann CAMASTER HRC Fuse Holders ® Ratings, Catalogue Numbers and Dimensions Standard front connected unit. Suitable for either bolted panel or DIN rail mounting. Max. Rec. Ratin g Cat. No. Cable F u se (A) A B mm2 Lin k 32 CM32FC 16 NITD 25.4 93.7 Front/Back Stud and Double Back Stud connected units. These allow easy customer conversion (illustrated below left) to either Front/ Back or Double Back configuration, by use of Back Stud Assembly Packs, using only a screwdriver. D imen sion s (mm) C 60 D E F G H J K 3.2 17.5 66.0 58.0 28.6 11.9 M6 32 CM32F 16 AAO 31.8 117.5 60 3.2 17.5 66.0 74.0 28.6 11.9 M6 63 CM63F 70 BAO 35.6 125 60 4.75 16.4 86.5 79.8 28.6 11.9 M8 100 CM100F 70 OSD 35.6 125 60 4.75 16.4 86.5 79.8 28.6 11.9 M8 Notes. 1 Type CM32FC is also available rated at 20A, catalogue number CM20F 2 For colours other than Black (standard) add the appropriate letter code: W = White; G = Green and GY = Grey. Conversion Sequence A Rating Catalogue Carton (A) No. Qty. 32 32BSC 10 32 32BS 10 Back Stud 63/100 63/100BS 5 Ganging Links GLP 1 set Neon 90-660NI 3 Indicator V ac Lockable 32LSCC 3 Safety 32LSC 3 Carriers 63/100LSC 3 Security Clip CMSC 20 Accessory B 1. Remove carrier using the Cam Lever. Insert screwdriver at position A gently lever and push ferrule upwards to remove. 2. Insert Back Stud accessory 3. Raise contact shield by inserting screwdriver at position B. Tighten terminal screw. 4. Repeat steps 1, 2 & 3 at opposite end to give Double Back Stud connection. 3 Bussmann SAFELOC HRC Fuse Holders ® The patented SAFELOC fuse holders provide a simple, safe range, designed to accommodate the compact rage of offset blade tag fuse links to BS88 part 6. The combination offers significant savings in volume and cost as well as a reduction in fitting time and power loss. They provide a safe and easy method of protecting a wide range of electrical equipment such as lighting, heating, motor and control equipment circuits. The NNS fuse holder accommodates the NSD range of compact HRC fuse links whilst the slightly larger ENS fuse holder accommodates the ESD range of compact HRC fuse links. Both holders are available in front connection or back stud arrangements or combinations of these. SAFELOC Fuse Holders are offered with the following features • Compact fuse link and fuse holder dimensions. • Fuse holders employ a unique slide/snap carrier action for positive and secure insertion and removal of the fuse link. This provides positive, stress free fitting of fuse links and locks the fuse link in position ensuring safe insertion and withdrawal from the base. • The direct contact between fuse link blades and the plated base contacts provides lower watts loss and increased reliability. • The compact range of fuse links (i.e. NSD & ESD) fitted into the SAFE LOC fuse holders, have an excellent ability to protect induction motor circuits. • Complete internal personnel protection against direct contact electric shock is obtained by fully insulated and shrouded fuse holder base contacts. • Fuse base consists of glass filled, high impact resistant, thermoplastic polyester and incorporates a 35mm DIN rail mounting facility as well as a single screw fixing. Motor Fuse Link Ratings Fuse Link Rating Safeloc type NNS ENS Safeloc type Fuse Link type NSD ESD Fuse Link type 2 2 20M25 4 4 20M32 6 6 20M36 10 10 32M36 16 16 20 20 25 25 32 32 550V ac 40 415V ac 50 63 4 NSD 415V ac ESD 415V ac NNS NSD 32M40 32M50 32M63 Notes on Motor Circuits All of the compact range of fuse links have an excellent ability to protect induction motor circuits. The ESD unique design of the SAFELOC fuse holders has enabled 63M80 the design of dual rated fuse links which offer protec63M100 tion for motor circuits up to 40 hp. Fuse links in this extended range have ratings, as defined in BS88 plus a higher rating, which relates to their ability to withstand motor starting surges. For example, an ESD63M 100 has a continuous current carrying capability of 63A, coupled with the time current characteristic, and thus the withstand capabilities, of a 100A fuse link. ENS The application of these fuse links in motor circuits can achieve significant economies in the size and cost of installations. The associated dual rated fuse links are shown left. Bussmann SAFELOC HRC Fuse Holders ® Ratings, Catalogue Numbers and Dimensions Available Variants Catalogue Reference NNS ENS Front Connected/Front Connected 32NNSF 63ENSF Back Stud/Back Stud 32NNSBS 63ENSBS Front Connected/Back Stud 32NNSFBS 63ENSFBS Suitable for either Bolted Panel or DIN rail mounting For colours other than Black (standard), add the appropriate letter code: W = White; G = Green; GY = Grey, at the end of the Catalogue Reference. Max. Rec. Dimen s ion s (mm) Ratin g Cat. No. Cable Fu s e (A) 2 A B C D E F G H J mm Lin k 32 NNS 16 NSD 25.4 76.2 46.5 2.3 16.0 39.2 57.7 17.0 9.7 63 ENS 35 ESD K M6 29.1 90.0 55.0 3.3 17.7 75.0 67.9 39.2 11.0 M8 Security seal (ref. 32551) available for 32A SAFELOC. Both CAMASTER and SAFELOC fuse holders can be used in Distribution Fuse Boards, CAMASTER is shown below on the left and SAFELOC on the right. Details of both these products can be found in our Fusegear Catalogue available on request. 5 Bussmann HRC Distribution Fuse Banks ® Two ranges of Fuse Banks are available, utilising the CAMASTER and SAFELOC HRC Fuse Holders. The fuse banks consist of single phase assemblies of busbar connected fuse holders mounted on a back strap, for incorporation in distribution fuse boards to facilitate compliance with BS5486: Part 1; (EN60439-1) and BS5486: Part 2. Compatible ranges of neutral bars and earth terminal busbars are also available, together with enclosure door circuit identification labels. The fuse banks are thermally rated and designed for mounting either horizontally or vertically. This flexibility is complemented by a fully insulated incoming cable termination shroud which may be rotationally positioned to accept cable entry from any direction. Complete personnel protection against direct contact electric shock is provided by fully shrouded busbars and shielded fuse holder base contacts. CAMASTER Fuse Bank Insulation of the busbar assembly and cable termination is by means of a PVC plastisol material, which has been shown, by thermal cycling tests, to be satisfactory for use at ambient temperatures from minus 20 degrees to plus 50 degrees centigrade. SAFELOC Fuse Bank Characteristics Gen eral CAMAS T ER F u se F u se Ban k P art Nu mbers Holder Ty pe 32F B--CMC O u tgoin g Circu it Rated Max. Rec. Rated Nomin al Cable F u se Voltage Cu rren t S ize Lin k (A) ( m m 2) In comin g Circu it Rated Normal Cu rren t (A) 4 6 8 12 W ay W ay W ay W ay Max. Cable Termin al size Bolt S ize ( m m 2) D iversity F actor Rec. Max. Normal Cu rren t 4 6 8 12 Ratin g of W ay W ay W ay W ay In comin g F u se Lin k (A) CM32FC 660 32 16 NITD 115 153 205 250 120 M10 250 0.9 0.8 0.8 0.66 32F B--CM CM32F 660 32 16 AAO 115 153 205 250 120 M10 250 0.9 0.8 0.8 0.66 63F B--CM CM63F 660 63 70 BAO 226 302 403 499 300 M12 500 0.9 0.8 0.8 0.66 100F B--CM CM100F 660 100 70 OSD 360 430 528 N/A 400 M12 560 0.9 0.8 0.66 N/A 32F B--NNS NNS 550 32 16 NSD 115 153 205 250 120 M10 250 0.9 0.8 0.8 0.66 63F B--ENS ENS 550 63 35 ESD 226 302 403 499 300 M12 500 0.9 0.8 0.8 0.66 S A F ELO C Fuse Bank P art Nu mbers 6 Bussmann HRC Distribution Fuse Banks ® Dimensions (see table below) Dimensions (mm) CAMAS T ER Catalogu e N u m b er No. of Ratin g W ay s (A) D imen sion s (mm) A B 32F B4CMC 4 32 110.9 265 32F B6CMC 6 32 167.9 265 C D E F G H J K L M N 74.6 46.8 64.5 124.2 93.7 25.4 62.3 77 143.5 80 34 46.1 32F B8CMC 8 32 224.9 365 32F B12CMC 12 32 338.9 515 85.6 32F B4CM 4 32 131.7 265 70.5 32F B6CM 6 32 198.3 265 58.8 64.5 124.2 117.5 25.4 64.7 77 143.5 80 34 67.6 37.2 32F B8CM 8 32 264.9 365 32F B12CM 12 32 398.0 515 53.9 63F B4CM 4 63 149.6 265 55.2 63F B6CM 6 63 225.6 265 17.2 63F B8CM 8 63 301.6 365 63F B12CM 12 63 453.6 515 27.7 100F B4CM 4 100 149.6 265 55.2 100F B6CM 6 100 225.6 365 100F B8CM 8 100 301.6 515 103.7 32F B4NNS 4 32 110.9 265 74.6 32F B6NNS 6 32 167.9 265 32F B8NNS 8 32 224.9 365 32F B12NNS 12 32 338.9 515 85.6 63F B4ENS 4 63 120.6 265 69.5 63F B6ENS 6 63 181.6 265 63F B8ENS 8 63 242.6 365 63F B12ENS 12 63 364.6 515 62.3 63 63 64.5 64.5 149.4 149.4 126 126 25.4 25.4 89.4 89.4 106 106 217 217 120 120 44 44 29.7 55.2 S AF ELO C Catalogu e Nu mbers 38 45 50 58 109 148.2 76 90 25.4 25.4 62.3 89.4 77 106 143.5 21.7 80 120 34 44 46.1 67.6 39.2 58.7 72.7 7 Bussmann Modular Fuse Holders CH Series ® The CH range of Modular Fuse Holders is available in three sizes: 10 x 38, 14 x 51 and 22 x 58 millimetres. Designed to accommodate Cylindrical type fuse links with ferrule end caps up to a maximum rating of 125 Amps. The CH101 series, to IEC269-2-1, accepts 0.5 to 32 Amp C10G and C10M style of 10 x 38mm European fuse links. The CHM accepts the North American midget style of fuse link and the CHCC accepts the North American Low Peak class CC fuse links. Both the CHM and CHCC are UL recognised, guide IZLT2, file E14853 and certified CSA Standard C22.2 No. 39. North American Design The North American design of CH range of fuse holders showing the interlocking system for the assembly of multiple poles. The flexibility of assembling multi-poles, ease of fuse link replacement, together with touch safe protection, ensures that the improved operating characteristics of the fuse link can now be achieved in a package comparable to that of alternative circuit protection devices. Ordering Codes 10 x 38m m D escription S in gle P ole S in gle P ole with In dicator D ou ble P ole D ou ble P ole with In dicator Triple P ole Triple P ole with In dicator Assembly P in s 2 P oles Assembly P in s 3 P oles Circu it Markers Circu it Marker Labels S pare F u se Holders 32A 660V North American * F u se Holder CH101* 30A 600V 30A 600V North American North American Midget F u se Class CC F u se Holder Holder C HM 1 C HC C 1 CH101I* CHM1I CHCC1I CH102* C HM 2 C HC C 2 CH102I* CHM2I CHCC2I CH103* C HM 3 C HC C 3 CH103I* CHM3I CHCC3I CH102AP CH102AP CH102AP CH103AP CH103AP CH103AP CH10CM CH10CM CH10CM CH10CL CH10CL CH10CL 5TPH 5TPH 5TPH • Unique dovetail feature built into the CH 10 x 38 design allows single pole units to be snapped together quickly and safely in the assembly of multi-poles. • Space saving design incorporates IP20 touch safe protection and lockout facility for increased safety. • Optional open fuse indication available on North American 10 x 38 designs. • • Fuse holders snap easily onto 35mm DIN rail. Circuit marking system available. * Although of North American design, all fuse holders marked with an asterisk are to IEC specification. Size 10 x 38 Fuse Holder Dimension (mm) A 57.5 B 44.0 C D E 45.2 49.9 82.2 I J K 17.5 35.0 80.7 F 6.0 L 7.6 For further detailed specifications on the CH range, please ask for Data Sheet number 1151 8 Dimension (mm) G 52.5 H 19.0 Bussmann Modular Fuse Holders CH Series ® The CH...E range of Modular Fuse Holders A range of cost-effective 10 x 38mm fuse holders, moulded from materials which are resistant to high temperatures. Silver plated contacts, 35mm DIN rail fixing with a degree of protection to IP20. Blown fuse indicator versions available. Standards: IEC947-1, NFC61 201, UNE21 103. North American UL approval. The CH.......E European design range. F u se h older size (mm) 10 x 38 F u se h older catalogu e n u m b er D escription F u se lin k ty pe CH101E 1 Pole C10G & C10M CH101EN 1 Pole + Neutral C10G & C10M CH102E 2 Pole C10G & C10M CH103E 3 Pole C10G & C10M CH103EN 3 Pole + Neutral C10G & C10M CH101EI 1 Pole + Indicator C10G & C10M CH101ENI 1 Pole + Neutral + Indicator C10G & C10M CH102EI 2 Pole + Indicator C10G & C10M CH103EI 3 Pole + Indicator C10G & C10M CH103ENI 3 Pole + Neutral + Indicator C10G & C10M Fuse links for use in Modular Fuse Holders Fuse Holder Size (mm) Fuse Holder Fuse Link Reference 10 x 38 CH--E C 10G C 10M 10 x 38 CH C 10G C 10M 10 x 38 CHM 10 x 38 CHCC LP-CC FNQ-R KTK-R 14 x 51 CH--G C14G C14M NON 22 x 58 CH--G C 22G C 22M FNQ KTK AGU BAF BAN FNM FWA FWC Cylindrical fuse links - C10G, C14G and C22G 9 Bussmann Modular Fuse Holders CH Series ® A range of larger dimensioned modular fuse holders rated up to 50A and 125A respectively. D escription S in gle P ole S in gle P ole with Microswitch D ou ble P ole Triple P ole Triple P ole with Microswitch 14 x 51 Catalogu e Referen ce CH141G 22 x 58 Catalogu e Referen ce CH221G CH141MSG CH221MSG CH142G CH143G CH222G CH223G CH143MSG CH223MSG Dimensions (mm) for CH range sizes 14 x 51 (50A) and 22 x 58 (125A). Size 14 x 51 Fuse Holder Dimension (mm) A 26.0 B 52.0 C 78.0 E 81.0 F 53.5 G H 44.5 52.6 Dimension (mm) I 89.0 J 5.0 K 32.5 L 98.0 M 106.0 N O 21.0 43.8 Triple Pole Unit Size 22 x 58 Fuse Holder Dimension (mm) A 35.0 B 70.0 C 105.0 E 88.0 F 53.0 G 45.0 H 58.0 Triple Pole Unit 10 Dimension (mm) I 103.0 J 4.5 K 45.0 L 112.0 M 140.0 N 26.5 O 63.0 Safety J Fuse Holders Bussmann ® The Safety J is a Class J Touch Safe Fuse Holder for use with Bussmann Class J fuse links such as the LPJ and JKS. It is made from thermoplastic with UL flammability 94VO and is available in 30 amp and 60 amp versions at 600V, with or without indication. Agency Approvals: UL listed UL 512 30-60A (guide IZLT, file 14853). CSA Certified 30-60A (class 6225-01, file 47235). • • Compact design saves valuable panel space. • Dual port wire management system simplifies installation of multiple loads connected to a single branch circuit (30A only). • Integral 35mm DIN rail adapter built in, providing convenient mounting. • The gangable system means reduced inventory, limiting the need to stock multiple poles. • Removable fuse carrier provides added safety while replacing the fuse link. • Probe holes incorporated in the carrier provide easy access to fuse for testing purposes. • Internal DIN rail release latch makes it easily removable from the DIN rail with just a screwdriver. • Reinforced fuse clips are standard giving low resistance performance. • • • Built-in labelling system to enable circuit marking. Touch safe design from direct or indirect contact with live parts (meets IP20). Terminals ready to accept cables, saving valuable installation time. Open fuse indication available to enable fast response in identifying open fuse links. Catalogue numbers for 30A - JT600030; JTN60030 with indication. Catalogue numbers for 60A - JT600060; JTN60060 with indication. 11 Bussmann Class J Fuse Blocks ® J600 Series Fuse Blocks For use with Class J Fuse Links such as Bussmann LPJ and JKS. Made of black thermoplastic with a 94VO UL flammability rating. Ratings: 0.5 to 600 Amps at 600 Volts ac. Agency Approvals: UL Listed UL512, guide IZLT, file E14853 CSA Certified, class 6225-01, file 47235 For more detailed information on dimensions, please ask for Data sheet number 1114. Ordering Codes Amps 0.5 to 30 31-60 61-100 101-200 201-400 401-600 Poles Catalogue Number Screw* Pressure Plate* Box Lug Box Lug with retaining clip 1 J60030-1S* J60030-1P* J60030-1C J60030-1CR 2 J60030-2S* J60030-2P* J60030-2C J60030-2CR 3 J60030-3S* J60030-3P* J60030-3C J60030-3CR 1 - - J60060-1C J60060-1CR 2 - - J60060-2C J60060-2CR 3 - - J60060-3C J60060-3CR 3 - - - J60100-3CR 1 - - - J60200-1CR 3 - - - J60200-3CR 1 - - - J60400-1CR 3 - - - J60400-3CR 1 - - - J60600-1CR 3 - - - J60600-3CR Max. Cable Size 5.3mm2 33mm2 53mm2 127mm2 253mm2 (2)253mm2 * Clip reinforcing springs are standard on fuse blocks rated 100A and above. Available on the 30A and 60A blocks, to order add the letter R to the end of the part number. Copper only connections available by changing CR suffix to COR LPJ-SP is an example of one type of fuse link that can be accommodated in the J600 series of Fuse Blocks. 12 Bussmann Class J Fuse Blocks ® JP Series Fuse Blocks For use with Class J Fuse Links such as Bussmann LPJ and J S. Made of black thermoplastic with a 94VO UL flammability rating. Rating: 30 amps, 600 volts. Agency Approvals: UL listed (UL512, guide IZLT, file E14853) CSA Certified (class 4225-04, file 47235). Catalogue Number Mounting Screws with Pressure Plate Panel JP60030-3PR (2.1 to 5.3mm wire) With DIN rail adaptor* JP60030-3PRA (2.1 to 5.3mm wire) Box Clamp Aluminium JP60030-3CR (8.4 to 33.6mm aluminium wire) (2.1 to 33.6mm copper wire) JP60030-3CRA (8.4 to 33.6mm aluminium wire) (2.1 to 33.6mm copper wire) Copper Only JP60030-3COR (2.1 to 33.6mm wire) JP60030-3CORA (2.1 to 33.6mm wire) * To order the DIN rail adaptor only use catalogue ref. JPA-3 13 Bussmann ® Class H and R Fuse Blocks H250 series for use with Class H fuse links such as Bussmann NON H600 series for use with Class H fuse links such as Bussmann NOS. R250 series for use with Class R fuse links such as Bussmann LPN-RK, FRN-R and KTS-R. R600 series for use with Class R fuse links such as Bussmann LPS-RK, FRS-R, DLS-R and KTS-R. H250 and R250 rated at 250V ac - 0.1A to 600A H600 and R600 rated at 600V ac - 0.1A to 600A Agency Approvals:UL Listed (UL512. guide IZLT, file E14852). CSA Certified (class 6225-01, file 47235). Dimension details (mm) for 250V class H & R single pole fuse blocks. 0.1 to 30A - 250V 101 to 600A - 250V 31 to 60A - 250V 61 to 100A - 250V Dimensions for 101A to 600A Blocks Rating (A) A B G H 101-200 181.0 78.5 76.2 19.05 201-400 230.0 101.6 76.2 25.4 401-600 279.4 126.2 101.6 25.4 These dimensions refer to single pole fuse blocks only. Double and triple pole configurations are available with slight variations in size of individual fuse blocks. Please ask for Data sheet numbers 1110 for R250 series and 1112 for the H250 series for further details. Various terminal types are available including Screw and Box Lug. Please telephone our application help line for further details or refer to the Data sheets listed above. 14 Bussmann Class H and R Fuse Blocks ® Dimensional Details (mm) for 600V Class H & R Fuse Blocks single pole. 0.1 to 30A 31A to 60A 61A to 100A Dimensions for 101 to 600A Rating (A) A B G H 101-200 244.6 78.5 76.2 19.05 201-400 304.8 101.6 76.2 25.4 401-600 355.6 126.2 101.6 25.4 All dimensions refer to Single Pole only. For further detailed information please ask for Data sheet number 1111 for R600 series and 1113 for H600 series Illustration of fuse link types that can be used in Class H & R fuse blocks. 15 Bussmann Modular Fuse Blocks ® A versatile design of fuse block able to accept a wide range of fuse link types and sizes. Two identical half blocks are included with each part number. Catalogue Reference: 1BS101, 1BS102, 1BS103 and 1BS104 Agency Approvals: UL Recognised, guide No. 1ZLT2, file No. E14853 Dimensions (mm) 1BS101 - 0 to 600V, 100Amps The 1BS101 features a dovetail interlock and anti pivot pin. The dovetail interlock permitting ganging of single pole units into multipole configurations. 1BS 101 fuse blocks Mounting dimensions for various fuse link types (mm). Catalogue References A B C FWA 70A-100A 49.3 16.0 95.4 FWH 35-60B 58.9 25.6 104.9 FWH 70-100B 72.4 39.1 118.3 FWX 35A-60A 59.4 26.1 105.4 FWX 70A-100A 59.7 26.4 105.6 KAC 1-30 63.5 30.2 109.4 KAC 35-60 88.9 55.6 134.8 KAC 70-100 105.7 72.3 151.6 KBC 35-60 88.9 55.6 134.8 KBC 70-100 93.0 59.6 138.9 LPJ 70SP-100SP 95.5 62.2 141.4 JJS 70-100 59.9 26.6 105.9 JKS 70-100 96.3 62.9 142.2 80-100L14C 89.9 56.6 135.8 80-100L09C 112.0 78.7 157.9 Mounting dimensions for various fuse link types (mm). Catalogue References FWA 70-100A A B C 50.3 8.9 167.9 FWH 125-200B 70.4 29.0 188.0 FWX 125A-200A 61.2 19.8 178.8 KBC 110-200 94.0 52.6 211.6 JJS 110-200 63.5 22.1 181.1 70A-100 CJ 92.2 50.8 209.8 125-400M09C 111.3 69.9 228.9 250-400P09C* 111.3 69.9 228.9 * When used in multiple pole configurations, 19.05 mm should be maintained between adjacent mouldings when mounting the fuses indicated. 16 1BS102 - 0 to 600V, 400Amps Bussmann Modular Fuse Blocks Dimensions (mm) 1BS103 - 0 to 600V, 400 Amps ® Mounting dimensions for various fuse link types (mm) Catalogue References A B C 83.8 42.4 201.4 FWX 225A-400A 67.6 26.2 185.2 KAC 110-200 109.2 67.8 226.8 KBC 225-400 103.1 61.7 220.7 160-400LMT 58.9 17.5 176.5 250-400P11C* 184.2 142.7 301.8 JJN 225-400 46.7 FWH 225A-400A JJS 225-400 CGL 225-400* 69.1 184.2 5.3 164.3 27.7 186.7 142.7 301.8 * When used in multiple configurations 25.4mm should be maintained between adjacent mouldings when mounting the fuse indicated. 1BS104 - 0 to 600V, 600 Amps Mounting dimensions for various fuse link types (mm) Catalogue References A B C FWA 500A-600A 62.0 19.1 222.3 FWH 450A-600A 74.7 31.8 235.0 FWX 450A-600A 62.5 19.6 222.8 KAC 225-400 123.7 80.8 284.0 KAC 450-600 122.9 80.0 283.2 KBC 450-600 95.0 52.1 255.3 JJN 450-600 51.6 8.6 211.8 JJS 450-600 74.9 32.0 235.2 450-600R11C* 184.2 141.2 344.4 CGL 450-600* 184.2 141.2 344.4 * When used in multiple configurations 12.7mm should be maintained between adjacent mouldings when mounting the fuse indicated. 17 Bussmann HRC Fuse Bases for NH Style Fuse Links ® Fuse bases to accommodate NH fuse links in sizes 00 to 3 single pole and 00 to 2 triple pole. Specifications: VDE 0636 and DIN43 620/3 HRC Fuse Bases are designed in accordance to DIN 43 620/1 and are available in sizes 00, 0, 1, 2 and 3. Both the single and triple pole versions are rated at 660V ac. Due to the excessive pull forces required to extract the fuse link from associated equipment, it is normal practice for size 4a/4 fuse links to be fitted into a switch fuse disconnect. NH Fuse Bases are designed from heat resistant lightweight moulded materials, with connection to the fuse link by means of silver plated contacts. Bolted cable terminals are available, with the option of a V clamp terminal connection on size 00, which accepts incoming cable sizes up to 70mm2 (add suffix V to the part number i.e. SB00V). Partition barriers can be mounted between poles on the bases (except size 00 with V clamp terminals). These are sold as separate items, catalogue reference PB followed by the fuse size. • Profiled shaped contact springs for secure mounting of the fuse link. • • Heat resistant lightweight moulded material. • • High resistance to short circuit. • Single pole bases packed in threes, triple pole packed in singles. Silver plating of the contacts ensuring durable fuse link contact. Ease of fuse link extraction with universal fuse link puller - ref. 630. Can be supplied with leather cuff to special order - ref. 630LC Single pole size 2 (reference SB2) Dimensions of Single and Triple Pole size 00 and 0 NH Fuse Base (mm) Catalogue reference SB (single pole) TB (triple pole). Cat. Rated Ref. & Current A Size (A) B C D E F G H J SB00 160 120 100 75 17 20 32 80 - - - - SB0 160 170 150 75 17 20 32 104 TB00 160 120 100 75 17 20 32 TB0 160 170 150 75 17 20 32 104 100 32 Size 0 fuse links fit into size 1 bases 18 80 100 32 HRC Fuse Bases for NH Style Fuse Links Bussmann ® Partition Barriers Partition barriers are used when additional security demands have to be met. To ensure additional safety, cover capes can be mounted on the contact springs. These cover capes are available for single pole and triple pole bases size 00 with bolt connections only. Cover capes are to special order only. To order Partition Barriers - reference PB followed by the size (00, 1, 2 or 3). Partition Barriers manufactured from a durable fabric. Dimensions of Single and Triple Pole NH Fuse Base (mm) sizes 1, 2 and 3 Triple Pole Base showing universal fuse puller to aid fuse extraction. Cat. Ref. 630 Catalogue reference SB (single pole) TB (triple pole). Triple pole base with Partition Barriers (reference PB-) fitted. C at . Rated Ref. & Current Size (A) A B C D E F G H J K L 27 2 M10 SB1 250 200 175 89 25 60 152 - - SB2 400 230 200 98 27.5 35 60 152 - - SB3 630 240 210 110 28 45 80 152 - - 27 TB1 250 200 175 89 25 60 152 184 60 TB2 400 230 200 98 27.5 35 60 152 184 60 TB3 630 240 210 110 80 152 244 80 28 45 2.5 M12 3 M12 2 M10 2.5 M12 3 M12 Size 0 fuse links fit into size 1 bases. 19 Bussmann Vertical Fuse Bases for NH Style Fuse Links ® A one-piece vertical arrangement of fuse base, moulded from a glass fibre strengthened self extinguishing synthetic material, incorporating a central corrosion resistant bar and stainless steel contact springs for secure fuse link positioning. Designed for 185mm busbar fixing (100mm for the size 00). Horizontal phase separation plates are included, vertical separation covers are available and can be fitted as required. (See table below). Dimensions according to DIN 43. 623 For fuse links according to DIN 43. 620 Sizes available 00, 1, 2, and 3 all at 660V ac. Catalogu e Referen ce S ize Rated Cu rren t (A) Rated Voltage (V) ac VF B100/00 00 160 660 VF B185/00 00 160 660 D escription 100mm bus bar fixing 185mm bus bar fixing 100mm bus bar fixing touch safe 185mm bus bar fixing touch safe For a full list of accessories and detail of touch safe requirement for size 1, 2 and 3, contact Bussmann Application engineers on +44 (0)1509 882760 and 882766. VF B100/00T S 00 160 660 VF B185/00T S 00 160 660 1 250 660 185mm bus bar fixing Vertical fuse bases are available to special order only. VF B185/1T S 1 250 660 185mm bus bar fixing touch safe VF B185/2 2 400 660 185mm bus bar fixing 185mm bus bar fixing touch safe VF B185/1 VF B185/2T S 2 400 660 VF B185/3 3 630 660 185mm bus bar fixing 660 185mm bus bar fixing touch safe VF B185/3T S 3 630 TS at the end of the catalogue reference means that vertical separation covers are fitted for touch safe application. Size 00 C D E F G 355 200 47 A B 28 - - - 54 84 1, 2 & 3 634 370 20 - J K L M 100 15 H 33 3 72 97 650 185 24 41 3 124 Bussmann Optima Overcurrent Protection Module ® Optima OPM-1038 Series The OPM-1038 series offers a high specification of protection against short circuit damage in eight feature combinations, for a broader coverage of todays process control panel applications. The unit is available as a three pole fuse module or, switch fuse disconnect; employing the unique cam action fuse carrier withdrawal and offering combinations accepting 10 x 38mm fuse links to European IEC 269 standard or alternatively North American 10 x 38mm LP-CC and midget types to UL approval and CSA standards. This overcurrent protection module can be adapted to suit a wide variety of applications, including communication to a remote PC or PLC. Types available: C = communication (remote indication) R = rejection (class CC) • • • Small size matches 45mm IEC starter width. • • • • • • • • Open fuse indicator lights. • Offered with Class CC rejection clips or European 10 x 38mm clips to meet global needs. Smallest 30 amp fusible disconnect available. Fits 0.8mm2 to 8.4mm2 cable, both stranded and solid. Recommended fuse link types Cam action handle for easy removal. Midget (nonrejection) European LP-CC KTK C10M KTK-R FNM C10G FNQ-R FNQ Class CC Finger safe terminals. Removable module for convenient fuse link loading. 35mm DIN rail or screw panel mounting. Dead-front construction Can be padlocked for additional security. Option for remote open fuse status indication feature available enabling less downtime. Current limiting fuse links can operate in as little as 2 milliseconds, breaking the circuit before let-through energy destroys components inside the panel. With the OPM and correctly sized fuse links, there is no welded contacts or burned open overload relays, thereby eliminating costly repairs to equipment and keeping down time to a minimum. Types available Non-switch series Voltage Amp SC ( ac ) Ratin g Ratin g Clips Remote Open Fu s e I n d ic at io n Non-rejection No Catalogu e Nu mber Approvals OPM-1038 IEC269-2-1 660 32 * OPM-1038R UL Listed 600 30 200kA Rejection No OPM-1038C IEC269-2-1 660 32 * Non-rejection Yes OPM-1038RC UL Listed 600 30 200kA Rejection Yes * Rating varies depending on fuse link used in module 21 Optima Overcurrent Protection Module Bussmann ® Types available Load Break Disconnect Switch Catalogu e N u m b er Approvals Voltage (ac ) Amp Ratin g SC Ratin g Clips Remote O p en F u s e In dication O P M-1038S W IEC947-3 660 32 * Non-rejection No O P M-1038RS W UL Listed 600 30 200kA Rejection No O P M-1038S WC IEC947-3 660 32 * Non-rejection Yes O P M-1038RS WC UL Listed 600 30 200kA Rejection Yes Dimensions (mm) for non-switch series * Rating varies depending on fuse link used in module Non-switched Dimensions (mm) for Load Break Disconnect Switch Switched 22