626 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 4, JULY 2000 Power Factor Correction Converter Using Delay Control Kyu-Chan Lee, Student Member, IEEE, Hang-Seok Choi, and Bo Hyung Cho, Senior Member, IEEE Abstract—A low cost universal input voltage single-controller power factor correction converter for a 200 W power supply is proposed. It consists of the PFC part followed by a dc-dc converter as in a conventional two-stage scheme. However a single PWM controller is used as in a single-stage PFC scheme. The switch in the PFC part is synchronized with the switch in the dc-dc converter and has a fixed frequency. Employing an adaptive delay scheme, the PFC switch is controlled to limit the capacitor voltage within a desired range for optimum efficiency and to reduce input current harmonic distortion. The design procedures of the delay scheme, the feedback loop, and experimented results are presented to verify the performance. Index Terms—Delay control, personal computer power supply, single controller power factor correction converter. I. INTRODUCTION R ECENTLY the suppression on line current harmonics and power factor requirements were being imposed to lower power level applications. In particular, 200–300 W power supplies in PC’s belong to the IEC-1000-3-2 class D. For the last several years a great deal of effort has been made to develop efficient and cost effective power factor correction (PFC) schemes. A number of single-stage schemes were proposed [1]–[4] in order to improve efficiency and to reduce cost from conventional two stage schemes, which employ a PFC pre-regulator followed by a dc–dc converter. These types of converters operate in discontinuous conduction mode (DCM), which offer inherent capability of the power factor correction. Because the single switch is controlled by a conventional PWM control scheme, an additional control circuitry for PFC can be eliminated. However, one of the major problems in this type of converter is their high capacitor voltage, which forces the use of the high voltage rating switching device. To reduce the capacitor voltage, a frequency modulation technique can be employed [5]. In this scheme, the operating frequency varies over a wide range, and the converter efficiency is deteriorated. This is particularly true for the power supplies which have an universal input voltage (90–264 V) and a wide range of load current specification. Also the switch of the singlestage converter has a large current stress because it carries both the boost current operating in DCM, and dc–dc converter current. This results in using two or more switches in order to limit the current stress on the device above 100 W applications. Manuscript received September 4, 1998; revised December 5, 1999. Recommended by Associate Editor, K. Smedley. The authors are with the Electrical Engineering Department, Seoul National University, Seoul 151-742, Korea (e-mail: lkc@plaza1.snu.ac.kr). Publisher Item Identifier S 0885-8993(00)05565-4. Also, since the proposed PFC converter operates in DCM, it has a lower efficiency in comparison with CCM operated PFC converter. However proposed converter is targeted for PC power supply, in which the cost should be the most critical factor while meeting the minimum efficiency requirements. With this constraint, five different PFC converters are used for comparison. Conventional PFC scheme used boost converter in CCM is excluded due to expensive PFC control IC. First and second converters are single stage PFC converters which are integration of boost converter in DCM and forward converter, and halfbridge converter in CCM respectively. Third, fourth and fifth converters are all two stage PFC converters. Third converter is consisted of the boost converter in critical conduction mode with frequency control and forward converter in CCM. Fourth converter has the boost converter in DCM with an additional PWM controller. Fifth proposed converter has a proposed single controller using delay control. The results of trade-off study are shown in Table I. This trade-off study shows that a single stage, single-switch scheme is not a good candidate for the 200 W power supply in a Personal Computer in terms of efficiency and cost [6]. In order to overcome the above mentioned problems in single switch circuits, a two switch scheme with a single PWM controller is proposed. It resembles conventional two stage schemes. However a single PWM controller with an adaptive delay scheme drives the switches for both the PFC part and the dc–dc converter part differently to keep the capacitor voltage within the optimal range and to reduce the input current distortion. In Section II, the proposed scheme is described and its operating principle is explained. The design procedure of the delay control scheme and the loss analysis is summarized in Section III. Section IV presents the design of the feedback loop for the proposed PFC converter taking into consideration of the second harmonics of the input voltage and the input current distortion. In Section V, selected experimental verifications are presented. II. OPERATING PRINCIPLES The circuit diagram of the proposed SC PFC converter employing the delay control is shown in Fig. 1. The converter has a PFC switch, Q1 synchronized with the switch, Q2 of the cascaded forward converter. The switch, Q2 is controlled to regulate the dc output voltage by PWM controller. The switch, Q1 is controlled to keep the capacitor voltage within a desired range, depending on the operating condition and to reduce input current harmonic distortion. As can be seen in Fig. 1 the inputs of the delay controller are the gate drive signal for Q2 (GS2), 0885–8993/00$10.00 © 2000 IEEE LEE et al.: POWER FACTOR CORRECTION CONVERTER USING DELAY CONTROL 627 TABLE I RESULTS OF TRADE-OFF STUDY Fig. 1. Circuit diagram of the proposed SC PFC converter the error amplifier output voltage . voltage and the rectified input The delay controller adds turn-on delay and turn-off to the gate drive signal of Q2(GS2) as can be seen delay 628 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 4, JULY 2000 value of error amplifier output voltage where the Taylor series expansion is done; and are constants. From equation (1)–(3) the boost switch duty ratio is given by (4) Fig. 2. Gate signals for Q1 and Q2 in Fig. 2. The relation between forward duty ratio can be expressed as duty ratio where control. is a constant and is the gain of the turn-off delay and boost B. Turn off Delay (1) the capacitor voltage can By controlling turn-on delay be kept within a desired range, and by controlling turn-off delay the input current distortion can be reduced. Also, since the gate signals of the Q1 and Q2 are synchronized, the switch Q1 is protected automatically when the forward converter is protected by alarm signals such as over current and over voltage. Synchronized operation of the two switches happens at the no-load condition and the start-up condition. Therefore the PFC part of the proposed converter does not need an additional protection scheme and soft start-up circuit which can reduce the cost and complexity. A. Turn on Delay For the DCM boost converter, the boost gain (the ratio of the bulk capacitor voltage to the peak of the line voltage) should be kept relatively high in order to make a more sinusoidal current. The boost gain should be greater than 1.29 to achieve power factor greater than 0.95 [7]. In that case the capacitor voltage could be higher than 480 V for universal line voltage. This imposes high voltage stress on the bulk capacitor for high power factor. So far, some techniques to reduce input current distortion using variable frequency control or variable duty-ratio control have been proposed. However, the variable frequency control method requires wide range of frequency variation and the variable duty-ratio control method needs another PWM controller and complex control circuit [8]. The line current of the PFC part is expressed as (5) Though the boost PFC part operates in DCM for an inherent PFC capability, if the two switches, Q1 and Q2 operate with the same duty ratio, the bulk capacitor voltage will increase as the load current decreases and/or line voltage increases as in a conventional single-stage PFC converter. For the efficient and optimum design of the transformer, such a large variation of the capacitor voltage is undesirable. To keep the capacitor voltage should within a desired range, the boost switch duty ratio be modulated according to the capacitor voltage. By introducing turn-on delay proportional to the capacitor voltage to the gate without using drive signal of S2, it is possible to control another PWM controller. In the proposed control method, the error amplifier output is used as an input of the voltage of the PWM controller delay controller instead of the capacitor voltage since the capacitor voltage is given by is line voltage (instantaneous value) and is where switching frequency. From equation (5), to make the input current sinusoidal the duty-ratio of the boost should be (6) is a constant. The exact implementation of equawhere tion (6) requires complex control circuit because it involves the by and the square-root function. However, division of in the proposed control scheme the bulk capacitor voltage can be controlled around the peak of the maximum line voltage in equation (6) can be considered as a (about 400 V), and of equation (6) can be approximated as ; constant. Then, (7) (2) (3) where turn ratio of the transformer; output voltage; amplitude of ramp of PWM controller; is the gain of the turn-off delay control. Fig. 3 shows where of equation (6) and (7) as a function of rectified line voltage. As can be seen the plot generated using equation (6) can be approximated with the linear equation of equation (7) and the control law of equation (7) can be simply implemented by introducing the turn-off delay proportional to the line voltage. The can be expressed as overall control law of (8) LEE et al.: POWER FACTOR CORRECTION CONVERTER USING DELAY CONTROL 629 TABLE II SPECIFICATIONS OF THE POWER SUPPLY IN PC Fig. 3. D TABLE III LOSS BREAKDOWN OF THE PROPOSED 200 W PFC POWER SUPPLY as a function of line voltage III. DESIGN PROCEDURES From the input–output power quasibalance, the design expression for the bulk capacitor voltage can be approximated as (9) where input voltage in rms; load current; transformer turns ratio; inductance; estimated efficiency. Using the delay control scheme as shown in Fig. 2, minimum input voltage with a full load. is given by at the (10) is the minimum variable delay duty ratio by the where is the maximum duty ratio for the delay controller and optimal efficiency. In order to ensure the DCM operation for all conditions, it needs to be designed at the minimum input voltage with full load case, and the DCM condition must be satisfied at the peak of the input voltage. The condition for ensuring the DCM operation is satisfied if (11) where is given by (12) is the maximum duty ratio for the forward converter at low input voltage with a full load. is selected, the desired Once the value of the product can be calculated for the DCM condition at the minimum minimum input voltage with a full load using (13) where Using equation (13) and the loss analysis, the optimum and can be determined. The maximum value of and corresponding can be calculated and the can at the be determined by equation (12). For the maximum and high input voltage and minimum load, the minimum can be calculated using equations (9) and the maximum (10). In order to design the proposed converter for optimal efficiency, a loss analysis is performed according to the design specifications shown in Table II. Table III shows the loss analysis results of 200 W PFC converter at various input voltage. and affect , the As discussed earlier, the values of peak current in Q1, and efficiency. Fig. 4(a) shows the efficiency . at 90 V input with a 200 W load as a function of the Fig. 4(b) shows the capacitor voltage and the PFC switch Q1 630 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 4, JULY 2000 (a) Fig. 6. Proposed PFC converter model rectified input voltage and linearizing the square function [10], which can be expressed as (14) (b) Fig. 4. Simulated efficiencies V dc and Q1 peak current where : equivalent load resistance of the forward converter. This equation is valid only at harmonic frequencies of the input voltage. The second harmonic ripples appeared at the output voltage due to the duty ratio and the input voltage at the harmonic frequencies can be expressed as (15) Fig. 5. Simulated capacitor voltage at different load peak current. From the results of the loss analysis in Fig. 4, the switching frequency is chosen at 62 kHz, and the inductance is 105 uH for the optimal efficiency at 90 V input with a full load. The resulting capacitor voltage at different loads can be analyzed and the capacitor voltage is between 300 V and 410 V as shown in Fig. 5. IV. FEEDBACK LOOP DESIGN CONSIDERATIONS Fig. 6 shows the proposed Single Controller PFC converter considering the feedback loop. In PFC converters with the rectified AC voltage, there exists voltage ripples of the bulk capacitor at harmonic frequencies of the input voltage [9]. The amplitude of the ripple voltage can be calculated by the linearized input-to-output transfer function. This function can be derived by the fourier transformation of the is the duty ratio to the output voltage transfer funcwhere is the input voltage to the output voltage transfer tion and function. In order to regulate the output voltage within the specified at second harmonic frelimit, the required feedback gain quency is shown as (16) (17) is the regulation specifiwhere is the line frequency and cation. As shown in equation (16), the higher the feedback gain is selected, the lower the output ripples become. This makes the duty ratio fluctuated at second harmonic frequency with a large amplitude. This affects the PFC converter performances such as the DCM condition and the input current distortion. Using the harmonic analysis, the instantaneous capacitor voltage and the duty ratio are approximated as shown in equation (18) taking the dominant second harmonic component. (18) LEE et al.: POWER FACTOR CORRECTION CONVERTER USING DELAY CONTROL 631 Fig. 7. Relations of the feedback loop gain and boundary of the DCM conditions where The reset duty ratio shown as of the DCM Boost converter is (19) In order to ensure the DCM operation, (20) should be satisfied: (20) Fig. 8. where Control to output transfer function and loop gain T results, feedback loop gain and the smallest capacitor size can be designed. Fig. 8 shows the control to output transfer function uF and a feedback gain of 0.55. and loop gain using C1 V. EXPERIMENTAL VERIFICATIONS Harmonics of the input current of the SC PFC converter with the feedback loop closed are described in (21) Total harmonic distortion (THD) of the line current can be calculated by the fourier transformation of equation (21). As shown in equation (20) and (21), DCM condition and THD are affected by the capacitor size and feedback loop gain. Fig. 7 shows the relations of the feedback loop gain at second harmonic frequency and the boundary of the DCM conditions and THD’s with respect to the capacitor. Using these simulation A engineering prototype hardware included all auxiliary circuits is built for the 200 W power supply in a PC which is implemented with the following major components: Q1-IRFP450, Q2-2SK1217, D1-MUR860, C1-450 V 100 uF, L-105 uH V secondary (PQ3220), and TR (EER35 primary 70 turns, V secondary 9 turns). 4 turns, The delay control is implemented using one CMOS IC4011, two transistors, and one op amp as shown in Fig. 9. The inputs of the delay controller are the gate drive signals for Q2(GS2), and the output of the feedback control voltage, . As the capacitor decreases and increases. The amount voltage increases, is thus inversely proportioned to . T1, R1 and T2, R2 of act as a voltage controlled current source that makes the variable and turn off delay, respectively. The op turn-on delay, sets the gain of the delay controller. amp and 632 Fig. 9. Fig. 10. IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 15, NO. 4, JULY 2000 Circuit implementation of proposed delay scheme Measured capacitor voltages of SC PFC converter (a) (b) Fig. 11. Measured efficiencies of SC PFC converter Fig. 10 shows the measured capacitor voltage as a function of the output power and input voltage. As compared to simulation results as shown in Fig. 6, the experimental results match well. Fig. 11 shows the measured efficiencies which satisfy the specifications as shown in Table II. Fig. 12. Line current and output voltage ripples (current 5 A/div, output voltage ripple 50 mV/div). Fig. 12 shows the rectified line current and output voltage ripples. As shown in Fig. 12, output voltage ripples and noises can be maintained within 42 mV which satisfy the specifications of PC power supply. LEE et al.: POWER FACTOR CORRECTION CONVERTER USING DELAY CONTROL 633 [7] K. H. Liu and Y. L. Lin, “Current waveform distortion in power factor correction circuits employing discontinuous-mode boost converter,” in Proc. IEEE Power Electron. Specialists Conf. (PESC) Record, June 1989, pp. 825–829. [8] J. Lazar and S. Cuk, “Open loop control of a unity power factor, discontinuous conduction mode boost rectifier,” in Proc. INTELEC’95, 1995, pp. 671–677. [9] K.-C. Lee and B. H. Cho, “Design of feedback loop for single controller power factor correction converter,” in Proc. IEEE PESC’98, May 1998, pp. 899–904. [10] M. Nagao, etc., “Analysis of high power factor ac–dc boost converter,” T. IEE Jpn., vol. 114-D, no. 11, pp. 1139–1148, 1994. Fig. 13. Input harmonic current at a high line with a full load. Fig. 13(a) shows the input harmonic current at a high line with a full load. Fig. 13(b) shows that proposed power supply is able to meet the requirements of IEC1000-3-2 Class D. VI. CONCLUSION Due to the high current and voltage stresses, a single stage, single switch PFC converter is not suitable for a 200 W power supply in a PC in view of the efficiency and the cost requirements. In the proposed converter, the PFC switch and the dc–dc converter switch are separated for optimum device selection. The adaptive delay control scheme limits the capacitor voltage within the optimum range and it reduces the input current harmonic distortion. It is shown that the proposed converter can reduce the cost compared to the conventional two-stage scheme meeting all specifications including the IEC 1000-3-2. REFERENCES [1] I. Takahasi and R. Y. Igarashi, “A switching power supply of 99% power factor by the dither rectifier,” in Proc. INTELEC ’91, 1991, pp. 714–719. [2] M. Madigan et al., “Integrated high quality rectifier-regulators,” in Proc. PESC’92 Record, 1992, pp. 1043–1051. [3] R. Red, L. Balogh, and N. O. Sokal, “A new family of single-stage isolated power-factor correctors with fast regulation of the output voltage,” in Proc. PESC’94, 1994, pp. 1137–1144. [4] M. Daniele, P. Jain, and G. Joos, “A single stage single switch power factor corrected ac/dc converter,” in Proc. PESC’96, 1996, pp. 216–222. [5] M. M. Jovanovic et al., “Reduction of voltage stress in integrated high-quality rectifier-regulators by vailable-frequency control,” in Proc. APEC’94, 1994, pp. 569–575. [6] K. C. Lee and B. H. Cho, “Low cost power factor correction(PFC) converter using delay control,” in Proc. PCC-Nagaoka’97, 1997, pp. 335–340. Kyu-Chan Lee (S’97) was born in Seoul, Korea, in 1964. He received the B.S. and M.S. degrees in electrical engineering from Seoul National University in 1987 and 1989, respectively, where he is currently pursuing the Ph.D. degree. From 1989 to 1999, he was a Research Engineer with Hyosung Industries, Co., Ltd., Korea, developing and designing the power electronics system such as AGV driving system, high power converter and inverter systems. His research interests include developing and designing converter topologies and control methods, power factor corrections, electronics ballast for metal halid discharge lamp, neon lamp, and CCFL lamp. Hang-Seok Choi was born in Korea in 1970. He received the B.S. and M.S. degrees in electrical engineering from the Seoul National University, Seoul, Korea, in 1997 and 1999, respectively, where he is currently pursuing the Ph.D. degree. His research interests are in power factor correction converters and soft switching techniques. Bo Hyung Cho (M’89–SM’95) received the B.S. and M.E. degrees from the California Institute of Technology, Pasadena, and the Ph.D. degree, from Virginia Polytechnic Institute and State University (Virginia Tech), Blacksburg, all in electrical engineering. Prior to his research at Virginia Tech, he worked for two years as a Member of Technical Staff, Power Conversion Electronics Department, TRW Defense and Space System Group, where he was involved in the design and analysis of spacecraft power processing equipment. From 1982 to 1995, he was a Professor in the Department of Electrical Engineering, Virginia Tech. He joined the School of Electrical Engineering, Seoul National University, Seoul, Korea in 1995, where he is an Associate Professor. His main research interests include power electronics, modeling, analysis and control of spacecraft power processing equipment, power systems for space station and space platform, and distributed power systems. Dr. Cho received the 1989 Presidential Young Investigator Award from the National Science Foundation. He is a member of Tau Beta Pi.